Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:42:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11178.98 | 985.34 | 985.34 |
Net Site Energy | 11178.98 | 985.34 | 985.34 |
Total Source Energy | 23045.58 | 2031.29 | 2031.29 |
Net Source Energy | 23045.58 | 2031.29 | 2031.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 848.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 770.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 867.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 603.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 84.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 198.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3295.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5246.07 | 5932.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 848.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 770.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 867.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 603.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 84.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 198.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3295.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 848.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 770.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 867.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 603.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 84.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 198.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3295.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.47 | 365.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 226.40 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 462.40 | 522.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.47 | 365.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 226.40 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 462.40 | 522.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5246.068 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5246.068 | 100.00 |
Total On-Site and Utility Electric Sources | 5246.068 | 100.00 |
Total Electricity End Uses | 5246.068 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 59.50 | 1.95 |
Air to Air Heat Recovery for Heating | 2995.47 | 98.05 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3054.97 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 10.00 |
Time Setpoint Not Met During Occupied Cooling | 735.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7809.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.3255 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.5208 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.7005 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 11.5174 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.6875 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 9.7951 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.3255 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.5208 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.7005 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 11.5174 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.6875 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 9.7951 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 13.0243 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 5.0165 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-19:30 | 21-DEC-17:49 | - | - | - | - | - | - | - | - | - | - | 10-JAN-21:10 |
Heating | 0.00 | 301004.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 145663.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32090.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 37771.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3590.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4056.98 | 259932.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2353.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 410155.66 | 650549.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 301004.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 145663.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1786.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 37771.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3590.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4056.98 | 259932.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1056.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1056.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 920.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2438.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2746.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 830.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2058.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1910.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 267.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 629.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.37 | 3572.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16614.30 | 6431.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 214.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 55.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 314.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1464.42 | 566.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 214.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 55.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 314.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1464.42 | 566.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.22 | 0.468405 | 0.424000 | 1.36 | 1.00 | 0.500000 | 0.000813 | 0.000051 | 1.36 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.471243 | 0.108454 | 0.424000 | 0.199807 | 0.424000 | 0.500000 | 0.003513 | 0.000037 | 0.199807 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.293313 | 0.201776 | 0.424000 | 0.124365 | 0.538071 | 0.500000 | 0.001888 | 0.000014 | 0.124365 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.222746 | 0.561866 | 0.424000 | 0.094444 | 1.00 | 0.500000 | 0.000678 | 0.000021 | 0.102140 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.148894 | 0.484952 | 0.424000 | 0.063131 | 1.00 | 0.500000 | 0.000786 | 0.000015 | 0.073510 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 4.02 | 0.058686 | 0.424000 | 1.70 | 0.424000 | 0.500000 | 0.025762 | 0.000086 | 1.70 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.93 | 0.074565 | 0.424000 | 0.818337 | 0.424000 | 0.500000 | 0.005110 | 0.000106 | 0.818337 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.89 | 0.169232 | 0.424000 | 2.50 | 0.451286 | 0.500000 | 0.002251 | 0.000263 | 2.50 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.92 | 0.616771 | 0.424000 | 0.815940 | 1.00 | 0.500000 | 0.000618 | 0.000133 | 0.815940 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.73 | 0.092566 | 0.424000 | 1.16 | 0.424000 | 0.500000 | 0.004116 | 0.000109 | 1.16 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.86 | 0.088361 | 0.424000 | 1.21 | 0.424000 | 0.500000 | 0.004312 | 0.000112 | 1.21 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.81 | 0.050459 | 0.424000 | 1.19 | 0.424000 | 0.500000 | 0.013581 | 0.000071 | 1.19 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 1.00 | 0.313947 | 0.424000 | 0.424125 | 0.837191 | 0.500000 | 0.001214 | 0.000085 | 0.424125 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5849.82 | 0.000051 | 121.99 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4231.52 | 0.000037 | 111.64 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1599.37 | 0.000014 | 37.26 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2371.52 | 0.000021 | 64.72 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1706.84 | 0.000015 | 46.58 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9882.58 | 0.000086 | 209.93 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 12082.31 | 0.000106 | 289.12 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 30082.58 | 0.000263 | 693.02 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 7480.94 | 0.000065 | 213.77 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 7486.57 | 0.000065 | 213.93 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 42756.52 | 0.000374 | 1221.79 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 42878.24 | 0.000375 | 1225.27 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 7480.94 | 0.000065 | 213.77 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 7486.57 | 0.000065 | 213.93 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15208.32 | 0.000133 | 385.50 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2275.75 | 0.000020 | 65.03 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2275.65 | 0.000020 | 65.03 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10915.22 | 0.000095 | 311.90 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12450.13 | 0.000109 | 281.85 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12841.12 | 0.000112 | 290.06 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8075.77 | 0.000071 | 173.68 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9665.41 | 0.000085 | 261.87 |
VAV WITH REHEAT HEATING COIL | 278972.33 | 0.002441 | 4327.73 |
FLR_3_DOAS HEATING COIL | 20913.38 | 0.000183 | 324.43 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.54 | 0.000065 | 0.000498 |
ROOM_2_FLR_3 FAN COIL | 1.51 | 0.000065 | 0.000487 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.92 | 0.000374 | 0.002865 |
ROOM_4_MULT19_FLR_3 FAN COIL | 8.03 | 0.000375 | 0.002701 |
ROOM_5_FLR_3 FAN COIL | 1.35 | 0.000065 | 0.000437 |
ROOM_6_FLR_3 FAN COIL | 1.32 | 0.000065 | 0.000427 |
ROOM_1_FLR_6 FAN COIL | 0.409918 | 0.000020 | 0.000132 |
ROOM_2_FLR_6 FAN COIL | 0.399985 | 0.000020 | 0.000129 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.79 | 0.000095 | 0.000586 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.54 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.51 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.92 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.03 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.35 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.32 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.409918 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.399985 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.79 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000498 | 1.54 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000487 | 1.51 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008462 | 12.80 | 0.008462 | 0.002865 | 8.92 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008671 | 12.80 | 0.008500 | 0.002701 | 8.03 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000437 | 1.35 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000427 | 1.32 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008515 | 12.80 | 0.008500 | 0.000132 | 0.409918 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000129 | 0.399985 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008572 | 12.80 | 0.008500 | 0.000586 | 1.79 | |
VAV WITH REHEAT COOLING COIL | 28.21 | 6.70 | 0.007840 | 10.55 | 0.007840 | 0.017200 | 27.36 | 481567.87 |
FLR_3_DOAS COOLING COIL | 33.90 | 6.70 | 0.005475 | 11.72 | 0.005475 | 0.001612 | 2.05 | 45136.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.76 | 11.67 | 27.52 | 11.67 | 27.36 | 27.36 | 0.300000 | 0.426390 | 27.36 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 27.36 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 27.36 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.017200 | 0.000028 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002441 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001612 | 0.000295 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000183 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.027076 | 4420.63 | |
HEATSYS1 PUMP | 0.004873 | 1467.42 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004873 | 0.584713 |
COOLSYS1 | 0.027076 | 3.25 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 556969.39 | 556969.39 | 0.004873 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.027076 | 3060.55 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.027076 | 758046.82 | 758765.36 | 86.50 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.325 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.705 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.521 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.901 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.700 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.390 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 11.517 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.897 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 20432.332 | 10.325 | 191.855 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20432.332 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.656 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.656 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.385 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.385 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 742.517 | 4.521 | 279.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 742.517 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 729.693 | 7.700 | 357.693 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 729.693 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2175.192 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2175.192 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 12673.066 | 9.688 | 30.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12673.066 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.470 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.470 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.219 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17110984E-14 | 0.24103936E-16 | -0.15943139E-09 | 0.44685538E-16 |
29 | 8 | 0.23237837E-07 | 0.98082464E-13 | 0.39196772E-03 | -0.26422217E-09 |
30 | 7 | -0.12664044E-01 | 0.50206963E-08 | -0.23693971E-01 | 0.14399480E-03 |
31 | 6 | 0.41682950 | 0.17394333E-05 | 0.48185553 | -0.48830741E-02 |
32 | 5 | -5.3025782 | 0.64717486E-04 | -4.5162048 | 0.64572787E-01 |
33 | 4 | 33.498276 | 0.52771084E-03 | 21.733161 | -0.42870077 |
34 | 3 | -112.28016 | 0.11468200E-02 | -56.202879 | 1.5304215 |
35 | 2 | 198.17562 | 0.64344368E-03 | 78.405936 | -2.9173034 |
36 | 1 | -171.55028 | 0.68528185E-04 | -55.409506 | 2.7523484 |
37 | 0 | 57.057407 | 0.38903588E-06 | 15.533392 | |
38 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
39 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
40 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
41 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
42 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
43 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
44 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
45 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
46 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
47 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
48 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
49 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
50 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
51 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
52 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
53 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
54 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
55 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
56 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
57 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
58 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
59 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
60 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
61 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
62 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
63 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
64 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
65 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
66 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
67 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
68 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
69 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
70 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
71 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
72 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
73 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
74 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
75 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
76 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
77 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 37 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.418_SHGC_0.4 | 38 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1607 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.3498E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1807 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.4403E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1149 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.5216E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.6285E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5376E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1831 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1008 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2066 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1136 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1272 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.6542E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1970E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.1022E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.9426E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.2759E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0227E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7130E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.9192E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1675E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.5560E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6155E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.9426E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.2759E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0227E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7130E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.9192E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1675E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.5560E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6155E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 35963.19085 | 35963.19085 | 3.21915 | 3.21915 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 27.04267 | 5.46480E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5264.22187 | 5264.22187 | 0.47124 | 0.47124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3376.10128 | 3376.10128 | 0.17826 | 0.17826 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3276.42414 | 3276.42414 | 0.29331 | 0.29331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.16000 | 5.47412E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1066.91962 | 1066.91962 | 5.63377E-002 | 9.17347E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2488.75915 | 2488.75915 | 0.22275 | 0.22275 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.01200 | 5.47390E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1934.33567 | 1934.33567 | 0.10214 | 0.10214 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1663.59473 | 1663.59473 | 0.14889 | 0.14889 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1392.13116 | 1392.13116 | 7.35099E-002 | 7.35099E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44922.35511 | 44922.35511 | 4.02093 | 4.02093 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2586.98351 | 2586.98351 | 0.13660 | 0.13660 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21540.76858 | 21540.76858 | 1.93004 | 1.93004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8578.30772 | 8578.30772 | 0.45295 | 0.67639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65777.21556 | 65777.21556 | 5.89036 | 5.89036 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 19388.91398 | 19388.91398 | 1.02381 | 1.89399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12805.84718 | 12805.84718 | 1.54454 | 1.54454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7480.98661 | 7480.98661 | 0.39732 | 0.39732 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12515.31173 | 12515.31173 | 1.50950 | 1.50950 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7486.61794 | 7486.61794 | 0.39762 | 0.39762 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 73950.72287 | 73950.72287 | 8.91908 | 8.91908 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 42756.63372 | 42756.63372 | 2.27096 | 2.27096 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 66565.41002 | 66565.41002 | 8.02902 | 8.02902 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 42878.36172 | 42878.36172 | 2.27743 | 2.27743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11221.01657 | 11221.01657 | 1.35339 | 1.35339 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.43733 | 5.46540E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7480.98661 | 7480.98661 | 0.39732 | 0.39732 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10967.07882 | 10967.07882 | 1.32276 | 1.32276 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7486.61794 | 7486.61794 | 0.39762 | 0.39762 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21499.27421 | 21499.27421 | 1.92439 | 1.92439 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.90000 | 5.47527E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11713.71938 | 11713.71938 | 0.61854 | 0.61854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3398.65209 | 3398.65209 | 0.40992 | 0.40992 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2275.75983 | 2275.75983 | 0.12087 | 0.12087 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3316.29616 | 3316.29616 | 0.39999 | 0.39999 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2275.66174 | 2275.66174 | 0.12086 | 0.12086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14830.53102 | 14830.53102 | 1.78880 | 1.78880 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 10915.26750 | 10915.26750 | 0.57973 | 0.57973 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30460.80032 | 30460.80032 | 2.73020 | 2.73020 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7491.92854 | 7491.92854 | 0.39560 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31910.97755 | 31910.97755 | 2.86013 | 2.86013 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7646.91529 | 7646.91529 | 0.40379 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31260.38784 | 31260.38784 | 2.80591 | 2.80591 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2988.30826 | 2988.30826 | 0.15778 | 0.36735 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11175.44027 | 11175.44027 | 1.00029 | 1.00029 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90000 | 5.47527E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7848.60128 | 7848.60128 | 0.41444 | 0.41444 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 414144.42 | 27.36338 | 27.36338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 264494.58 | 7.78299 | 7.78299 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 42510.28 | 23.72558 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 69708.81 | 6.95975 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.21915 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46841 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.36492 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.13398E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.11768E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.36492 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5849.81812 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.11768E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 121.98787 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.47124 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10845 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19981 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51300E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.70192E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19981 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4231.51718 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.70192E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 111.64242 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29331 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20178 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12436 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53807 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88823E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39920E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12436 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1599.37240 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39920E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 37.26135 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22275 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56187 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.44442E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.78098E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07471E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10214 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2371.51854 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07471E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 64.71967 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.14889 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48495 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.31312E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.85645E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49322E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.35099E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1706.83806 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49322E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 46.58100 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.02093 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.86863E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.70488 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57622E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.64571E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.70488 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9882.58333 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.64571E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 209.92668 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.93004 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.45647E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81834 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42400 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.10966E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05701E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81834 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12082.30657 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05701E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.12363 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.89036 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16923 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.49751 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45129 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25134E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.63176E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.49751 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30082.58134 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.63176E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 693.02033 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.54454 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.54454 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.54465E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.98455E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51643E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.98455E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.54454 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7480.94243 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.54465E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 213.77375 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.50950 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.50950 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.54958E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.87189E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51676E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.87189E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.50950 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7486.57373 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.54958E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 213.93462 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.91908 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.91908 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.74053E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.86527E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81650 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.46171E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.46171E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.86527E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.91908 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 42756.51531 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.74053E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1221.79046 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.02902 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.02902 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.75118E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.70077E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81555 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67059E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.70077E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.02902 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 42878.24300 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.75118E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1225.26819 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.35339 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.35339 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.54465E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.36920E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51771E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.36920E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.35339 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7480.94243 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.54465E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 213.77375 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.32276 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.32276 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.54958E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.27062E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51797E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.27062E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.32276 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7486.57373 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.54958E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 213.93462 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.92439 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61677 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81594 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.17734E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33049E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81594 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15208.32152 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33049E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 385.50418 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.40992 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.40992 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.99092E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.32255E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51550E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.32255E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.40992 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2275.74686 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99092E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 65.02845 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.39999 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.39999 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.99084E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.29063E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51585E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29063E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.39999 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2275.64877 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99084E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 65.02565 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.78880 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.78880 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.54911E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.86035E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81583 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57172E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.86035E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.78880 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 10915.21907 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.54911E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 311.89602 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.73020 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.25658E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15760 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42400 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.11599E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08919E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15760 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12450.13023 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08919E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 281.85479 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.86013 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.83607E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21269 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42400 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.31187E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12340E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21269 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12841.11771 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12340E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 290.06144 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.80591 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.04592E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18971 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42400 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35808E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.06503E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18971 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8075.76568 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.06503E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 173.67920 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00029 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31395 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42400 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42412 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83719 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21358E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.45572E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42412 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9665.40665 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.45572E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 261.87212 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.75880 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66746 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 27.51760 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66746 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 27.36338 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 27.36338 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.42639 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 27.36338 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 27.36338 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.21364 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.55130 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.83966E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.83966E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 481567.87164 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.72005E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 27.36338 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 278972.32565 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44057E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4327.72739 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 27.36338 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.72005E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.76847E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.44057E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.90000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.72145 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45136.60304 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.61217E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 20913.37763 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82959E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 324.43145 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.61217E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.95371E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.82959E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.70757E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4420.63057 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.87261E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.58471 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.87261E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1467.41650 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 556969.38595 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 556969.39000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.87261E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.70757E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.24908 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.70757E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3060.55164 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.70757E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 758046.82344 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 758765.36000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 86.49925 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5880.59 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4250.18 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1607.16 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2381.79 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1714.23 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9934.02 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 12139.49 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 30229.90 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 8061.11 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 8067.18 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 46072.56 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 46203.71 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 8061.11 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 8067.18 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15277.92 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2452.18 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2452.07 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 11761.44 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12511.73 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12904.74 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8117.51 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9707.41 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 183682.65 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 13769.91 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 26342.71 | 19085.60 | 7257.11 | 0.72 | 6579.84 | 66.74 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 25746.57 | 18653.06 | 7093.51 | 0.72 | 6429.87 | 65.22 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 152218.79 | 110302.31 | 41916.48 | 0.72 | 39843.45 | 404.11 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 140728.02 | 100409.80 | 40318.22 | 0.71 | 32844.56 | 333.13 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 23087.92 | 16725.26 | 6362.66 | 0.72 | 5763.09 | 58.45 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 22566.46 | 16347.08 | 6219.38 | 0.72 | 5632.20 | 57.12 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6990.13 | 5064.92 | 1925.21 | 0.72 | 1746.81 | 17.72 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 6821.18 | 4942.32 | 1878.86 | 0.72 | 1704.29 | 17.29 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 30814.59 | 22200.10 | 8614.49 | 0.72 | 7498.50 | 76.05 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 746575.60 | 437611.55 | 308964.04 | 0.59 | 182425.34 | 1850.26 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 46146.10 | 28462.74 | 17683.36 | 0.62 | 4499.01 | 45.63 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.6923373931E-002 | 5.1966329040E-002 | Pass | Pass | 0.7897317225 | 6.1100942539 | Pass | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.9371009949E-002 | 0.1855935042 | Fail | Pass | 0.2833916276 | 1.4251077470 | Fail | Fail |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.2333524565E-002 | 7.6178616355E-002 | Pass | Pass | 1.3283318478 | 10.2231103246 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3633361874E-002 | 2.8438115218E-002 | Pass | Pass | 0.1565303423 | 0.4551028213 | Pass | Fail |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8167138670E-002 | 3.2554117339E-002 | Pass | Pass | 0.1563187858 | 0.3799815715 | Pass | Fail |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1994496437 | 0.4385465898 | Fail | Pass | 0.1426827908 | 0.4644020811 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1234849826 | 0.2339613329 | Fail | Pass | 0.1890788636 | 0.7059945872 | Pass | Fail |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1451340412E-002 | 0.1056996321 | Pass | Pass | 0.1797164355 | 0.6054827207 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3252304553E-002 | 0.1939742235 | Pass | Pass | 0.2107127355 | 0.6640090660 | Pass | Fail |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9268485884E-002 | 0.2397473592 | Pass | Pass | 0.2410730844 | 0.9740422358 | Pass | Fail |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.1374113968E-002 | 4.2811208426E-002 | Pass | Pass | 3.6590140089E-002 | 6.7152901377E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.3761488814E-002 | 0.1262637962 | Pass | Pass | 0.2051892433 | 0.6703090879 | Fail | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.8189558196E-002 | 0.2557584479 | Pass | Pass | 0.2113365486 | 0.7350312490 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.7393629477E-002 | 0.2232241704 | Pass | Pass | 0.1479088563 | 0.5862479620 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5116741796E-002 | 3.5958536815E-002 | Pass | Pass | 0.1912738126 | 0.6720840816 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9495731939E-002 | 0.2156271907 | Pass | Pass | 0.2168977923 | 0.7275622542 | Pass | Fail |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.8195314949E-002 | 0.2896347959 | Pass | Pass | 0.3978319173 | 1.6700621269 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.8070374427E-002 | 0.3157134100 | Pass | Pass | 0.2682594678 | 0.9325266792 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.1840096685E-002 | 0.2039695879 | Pass | Fail | 0.5346047524 | 3.9444324438 | Pass | Fail |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.4223637331E-002 | 0.2156849935 | Pass | Pass | 0.2371424428 | 1.1762572415 | Pass | Fail |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.2300801274 | 0.5877204701 | Pass | Pass | 0.1143766351 | 0.2825898126 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7486997999E-002 | 6.7168402623E-002 | Pass | Pass | 0.3655233344 | 2.0328309277 | Fail | Fail |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4775.51 | 136.35 | 1557.63 | 7349.68 | 3650.31 | 17469.49 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.375 | 0.401 | 0.442 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.375 | 0.401 | 0.442 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.375 | 0.401 | 0.442 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.375 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.375 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.375 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.375 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.375 | 0.401 | 0.442 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.375 | 0.401 | 0.442 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.375 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.375 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.375 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.375 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.375 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.375 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.375 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.375 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.375 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.375 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.375 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.375 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.418_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.375 | 0.401 | 0.442 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.375 | 0.401 | 0.442 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.375 | 0.401 | 0.442 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.375 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.375 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.375 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.375 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.375 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.375 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.375 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 432.95 | 2.375 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.375 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.3255 | 1978.83 | 20432.33 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 188.94 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.5625 | 67.07 | 909.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.76 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.5625 | 77.67 | 1053.39 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 10.14 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.5208 | 164.24 | 742.52 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.17 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.7005 | 94.76 | 729.69 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 4.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 11.5174 | 188.86 | 2175.19 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.42 | 0.0000 | Y | 16.09 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.6875 | 1308.19 | 12673.07 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.52 | 0.0000 | Y | 98.78 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 9.7951 | 1863.81 | 18256.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.45 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 9.7951 | 1864.32 | 18261.31 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.49 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.23 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.18 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 9.7951 | 220.77 | 2162.52 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 15.45 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.24 | 0.0000 | Y | 35.31 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.24 | 0.0000 | Y | 35.31 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 13.0243 | 103.30 | 1345.47 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 9.4981 | 11345.29 | 107758.18 | 494.54 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.67 | 83.67 | 262.14 | |
Exterior Lighting Total | 16690.39 | 262.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 556969.39 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 758765.36 | 2.96 | 758898.73 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13955.66 | 26342.71 | 19085.60 | 7257.11 | 0.72 | - | 6579.84 | 66.74 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13640.26 | 25746.57 | 18653.06 | 7093.51 | 0.72 | - | 6429.87 | 65.22 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 80221.34 | 152218.79 | 110302.31 | 41916.48 | 0.72 | - | 39843.45 | 404.11 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75615.67 | 140728.02 | 100409.80 | 40318.22 | 0.71 | - | 32844.56 | 333.13 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12232.83 | 23087.92 | 16725.26 | 6362.66 | 0.72 | - | 5763.09 | 58.45 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11956.82 | 22566.46 | 16347.08 | 6219.38 | 0.72 | - | 5632.20 | 57.12 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3702.86 | 6990.13 | 5064.92 | 1925.21 | 0.72 | - | 1746.81 | 17.72 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3613.48 | 6821.18 | 4942.32 | 1878.86 | 0.72 | - | 1704.29 | 17.29 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 16407.73 | 30814.59 | 22200.10 | 8614.49 | 0.72 | - | 7498.50 | 76.05 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 481567.87 | 746575.60 | 437611.55 | 308964.04 | 0.59 | - | 182425.34 | 1850.26 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45136.60 | 46146.10 | 28462.74 | 17683.36 | 0.62 | - | 4499.01 | 45.63 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5849.82 | 5880.59 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4231.52 | 4250.18 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1599.37 | 1607.16 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2371.52 | 2381.79 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1706.84 | 1714.23 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9882.58 | 9934.02 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12082.31 | 12139.49 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30082.58 | 30229.90 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7480.94 | 8061.11 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7486.57 | 8067.18 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 42756.52 | 46072.56 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 42878.24 | 46203.71 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7480.94 | 8061.11 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7486.57 | 8067.18 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15208.32 | 15277.92 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2275.75 | 2452.18 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2275.65 | 2452.07 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 10915.22 | 11761.44 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12450.13 | 12511.73 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12841.12 | 12904.74 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8075.77 | 8117.51 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9665.41 | 9707.41 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 278972.33 | 183682.65 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 20913.38 | 13769.91 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.54 | 1086.79 | 703.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.51 | 1062.14 | 703.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.92 | 6275.79 | 703.64 | 1.00 | 0.94 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.03 | 5649.51 | 703.64 | 1.00 | 0.94 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.35 | 952.29 | 703.64 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.32 | 930.74 | 703.64 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.41 | 288.43 | 703.64 | 1.00 | 1.52 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.40 | 281.44 | 703.64 | 1.00 | 1.54 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.79 | 1258.67 | 703.64 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 27.36 | 61311.45 | 2240.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.027076 | 4420.63 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004873 | 1467.42 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027076 | 3060.55 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 35963.19 | 35963.19 | 18.17 | 3.219 | 3.219 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00917 | 27.04 | 0.00546 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5264.22 | 5264.22 | 78.49 | 0.471 | 0.471 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00890 | 33.41 | 0.00547 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3276.42 | 3276.42 | 42.18 | 0.293 | 0.293 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00932 | 33.16 | 0.00547 | 0.092 | 0.00 |
MECH_FLR_1 | 2488.76 | 2488.76 | 15.15 | 0.223 | 0.223 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00862 | 33.01 | 0.00547 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1663.59 | 1663.59 | 17.56 | 0.149 | 0.149 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00867 | 33.75 | 0.00548 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44922.36 | 44922.36 | 575.64 | 4.021 | 4.021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00853 | 33.90 | 0.00548 | 0.000 | 0.00 |
CAFE_FLR_1 | 21540.77 | 21540.77 | 114.06 | 1.930 | 1.930 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.00994 | 33.41 | 0.00547 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65777.22 | 65777.22 | 50.28 | 5.890 | 5.890 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00991 | 33.53 | 0.00547 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12805.85 | 12805.85 | 328.17 | 1.545 | 1.545 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12515.31 | 12515.31 | 320.76 | 1.509 | 1.509 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00547 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 73950.72 | 73950.72 | 3015.46 | 8.919 | 8.919 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00846 | 33.53 | 0.00547 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 66565.41 | 66565.41 | 2713.57 | 8.029 | 8.029 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00867 | 33.75 | 0.00548 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11221.02 | 11221.02 | 287.56 | 1.353 | 1.353 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00852 | 27.44 | 0.00547 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10967.08 | 10967.08 | 281.08 | 1.323 | 1.323 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 21.11 | 21.11 | 0.00852 | 26.60 | 0.00546 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21499.27 | 21499.27 | 55.21 | 1.924 | 1.924 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00933 | 33.90 | 0.00548 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3398.65 | 3398.65 | 87.10 | 0.410 | 0.410 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3316.30 | 3316.30 | 85.00 | 0.400 | 0.400 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14830.53 | 14830.53 | 604.57 | 1.789 | 1.789 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00857 | 33.53 | 0.00547 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30460.80 | 30460.80 | 91.84 | 2.730 | 2.730 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01033 | 33.90 | 0.00548 | 1.188 | 0.00 |
DINING_FLR_6 | 31910.98 | 31910.98 | 96.22 | 2.860 | 2.860 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01025 | 33.90 | 0.00548 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31260.39 | 31260.39 | 302.60 | 2.806 | 2.806 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01004 | 32.57 | 0.00547 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11175.44 | 11175.44 | 27.12 | 1.000 | 1.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00891 | 33.90 | 0.00548 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.35 | 0.00096 | -17.90 | 0.00096 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3376.10 | 3376.10 | 50.34 | 0.178 | 0.178 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00758 | -17.90 | 0.00096 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1066.92 | 1066.92 | 13.74 | 0.056 | 0.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00750 | -17.90 | 0.00096 | 0.092 | 0.00 |
MECH_FLR_1 | 1934.34 | 1934.34 | 11.78 | 0.102 | 0.102 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00736 | -17.90 | 0.00096 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1392.13 | 1392.13 | 14.69 | 0.074 | 0.074 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00748 | -17.90 | 0.00096 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2586.98 | 2586.98 | 33.15 | 0.137 | 0.137 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00734 | -17.90 | 0.00096 | 0.000 | 0.00 |
CAFE_FLR_1 | 8578.31 | 8578.31 | 45.42 | 0.453 | 0.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00763 | -17.90 | 0.00096 | 0.676 | 0.00 |
LOBBY_FLR_1 | 19388.91 | 19388.91 | 14.82 | 1.024 | 1.894 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00754 | -17.90 | 0.00096 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 7480.99 | 7480.99 | 191.71 | 0.397 | 0.397 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7486.62 | 7486.62 | 191.88 | 0.398 | 0.398 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 42756.63 | 42756.63 | 1743.47 | 2.271 | 2.271 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 42878.36 | 42878.36 | 1747.96 | 2.277 | 2.277 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7480.99 | 7480.99 | 191.71 | 0.397 | 0.397 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7486.62 | 7486.62 | 191.88 | 0.398 | 0.398 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -17.90 | 0.00096 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 11713.72 | 11713.72 | 30.08 | 0.619 | 0.619 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | -17.90 | 0.00096 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2275.76 | 2275.76 | 58.32 | 0.121 | 0.121 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00764 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2275.66 | 2275.66 | 58.32 | 0.121 | 0.121 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00764 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10915.27 | 10915.27 | 444.97 | 0.580 | 0.580 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | -17.90 | 0.00096 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7491.93 | 7491.93 | 22.59 | 0.396 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -17.90 | 0.00096 | 1.188 | 0.00 |
DINING_FLR_6 | 7646.92 | 7646.92 | 23.06 | 0.404 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00773 | -17.90 | 0.00096 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2988.31 | 2988.31 | 28.93 | 0.158 | 0.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00713 | -17.90 | 0.00096 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7848.60 | 7848.60 | 19.04 | 0.414 | 0.414 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 27.36 | 27.36 | 7.78 | 7.78 | 27.3634 | 11.6675 | 27.3634 | 0.4264 | 0.3000 |
FLR_3_DOAS | 23.73 | 2.05 | 6.96 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5849.818 | 5849.818 | 1.364921 | 0.00005118 | 121.988 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5849.82 | 5849.82 | 1.364921 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5882.70 | 5882.70 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4231.517 | 4231.517 | 0.199807 | 0.00003702 | 111.642 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4231.52 | 4231.52 | 0.199807 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00758213 | 39.8167 | 3376.10 | 0.00 | 4252.70 | 4252.70 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1599.372 | 1599.372 | 0.124365 | 0.00001399 | 37.261 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1599.37 | 1599.37 | 0.124365 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00749617 | 39.3686 | 1066.92 | 0.00 | 1607.92 | 1607.92 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2371.519 | 2371.519 | 0.102140 | 0.00002075 | 64.720 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2371.52 | 2371.52 | 0.102140 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00735715 | 38.6471 | 1934.34 | 0.00 | 2383.28 | 2383.28 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1706.838 | 1706.838 | 0.073510 | 0.00001493 | 46.581 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1706.84 | 1706.84 | 0.073510 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00747519 | 39.2598 | 1392.13 | 0.00 | 1715.30 | 1715.30 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9882.583 | 9882.583 | 1.704875 | 0.00008646 | 209.927 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9882.58 | 9882.58 | 1.704875 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00734499 | 38.5861 | 2586.98 | 0.00 | 9937.77 | 9937.77 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 12082.307 | 12082.307 | 0.818337 | 0.00010570 | 289.124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12082.31 | 12082.31 | 0.818337 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00763364 | 40.0832 | 8578.31 | 0.00 | 12145.55 | 12145.55 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 30082.581 | 30082.581 | 2.497511 | 0.00026318 | 693.020 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30082.58 | 30082.58 | 2.497511 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00754311 | 39.6122 | 19388.91 | 0.00 | 30243.84 | 30243.84 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13955.659 | -999.000 | 1.544539 | 0.00049845 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 13955.66 | 13912.96 | 1.544539 | 21.82 | 13.52 | 0.00851643 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851643 | 44.3498 | 12805.85 | 0.00 | 17575.56 | 16436.96 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7480.942 | 7480.942 | 0.397324 | 0.00006545 | 213.774 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7480.94 | 7480.94 | 0.397324 | 21.11 | 12.46 | 0.00756579 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00756579 | 39.4623 | 7480.99 | 0.00 | 8064.52 | 8064.52 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13640.258 | -999.000 | 1.509497 | 0.00048719 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 13640.26 | 13597.70 | 1.509497 | 21.82 | 13.52 | 0.00851676 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00547208 | 14.39 | 0.0000 | 21.11 | 0.00851676 | 44.3515 | 12515.31 | 0.00 | 17178.15 | 16064.09 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7486.574 | 7486.574 | 0.397623 | 0.00006550 | 213.935 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7486.57 | 7486.57 | 0.397623 | 21.11 | 12.46 | 0.00756613 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00756613 | 39.4641 | 7486.62 | 0.00 | 8070.59 | 8070.59 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 80221.343 | -999.000 | 8.919078 | 0.00286527 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 80221.34 | 80221.34 | 8.919078 | 21.82 | 13.48 | 0.00846171 | 12.80 | 10.18 | 0.00846171 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00846171 | 44.0680 | 73950.72 | 0.00 | 101209.42 | 95348.40 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 42756.515 | 42756.515 | 2.270961 | 0.00037405 | 1221.790 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 42756.52 | 42756.52 | 2.270961 | 21.11 | 12.49 | 0.00759546 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00759546 | 39.6132 | 42756.63 | 0.00 | 46092.49 | 46092.49 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 75615.675 | -999.000 | 8.029015 | 0.00270077 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 75615.67 | 73280.71 | 8.029015 | 21.82 | 13.65 | 0.00867059 | 12.80 | 10.21 | 0.00850000 | 33.75 | 0.00547504 | 15.02 | 0.0000 | 21.11 | 0.00867059 | 45.1428 | 66565.41 | 0.00 | 94766.77 | 85566.05 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 42878.243 | 42878.243 | 2.277427 | 0.00037512 | 1225.268 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 42878.24 | 42878.24 | 2.277427 | 21.11 | 12.49 | 0.00759644 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00759644 | 39.6182 | 42878.36 | 0.00 | 46223.72 | 46223.72 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12232.831 | -999.000 | 1.353388 | 0.00043692 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 12232.83 | 12192.49 | 1.353388 | 21.82 | 13.52 | 0.00851771 | 12.80 | 10.21 | 0.00850000 | 27.44 | 0.00546540 | 12.88 | 0.0000 | 21.11 | 0.00851771 | 44.3564 | 11221.02 | 0.00 | 15405.15 | 14402.89 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7480.942 | 7480.942 | 0.397324 | 0.00006545 | 213.774 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7480.94 | 7480.94 | 0.397324 | 21.11 | 12.46 | 0.00756579 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00756579 | 39.4623 | 7480.99 | 0.00 | 8064.52 | 8064.52 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11956.825 | -999.000 | 1.322760 | 0.00042706 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | 7/21 09:20:00 | 11956.82 | 11916.84 | 1.322760 | 21.82 | 13.53 | 0.00851797 | 12.80 | 10.21 | 0.00850000 | 26.60 | 0.00546414 | 12.59 | 0.0000 | 21.11 | 0.00851797 | 44.3577 | 10967.08 | 0.00 | 15057.44 | 14076.97 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7486.574 | 7486.574 | 0.397623 | 0.00006550 | 213.935 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7486.57 | 7486.57 | 0.397623 | 21.11 | 12.46 | 0.00756613 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00756613 | 39.4641 | 7486.62 | 0.00 | 8070.59 | 8070.59 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 15208.322 | 15208.322 | 0.815940 | 0.00013305 | 385.504 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15208.32 | 15208.32 | 0.815940 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00765797 | 40.2073 | 11713.72 | 0.00 | 15286.41 | 15286.41 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3702.861 | -999.000 | 0.409918 | 0.00013226 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3702.86 | 3692.17 | 0.409918 | 21.82 | 13.52 | 0.00851550 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851550 | 44.3450 | 3398.65 | 0.00 | 4663.48 | 4362.31 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2275.747 | 2275.747 | 0.120869 | 0.00001991 | 65.028 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2275.75 | 2275.75 | 0.120869 | 21.11 | 12.53 | 0.00763912 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00763912 | 39.8401 | 2275.76 | 0.00 | 2453.27 | 2453.27 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3613.483 | -999.000 | 0.399985 | 0.00012906 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3613.48 | 3602.82 | 0.399985 | 21.82 | 13.52 | 0.00851585 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851585 | 44.3468 | 3316.30 | 0.00 | 4550.86 | 4256.62 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2275.649 | 2275.649 | 0.120863 | 0.00001991 | 65.026 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2275.65 | 2275.65 | 0.120863 | 21.11 | 12.53 | 0.00763913 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00763913 | 39.8401 | 2275.66 | 0.00 | 2453.17 | 2453.17 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 16407.734 | -999.000 | 1.788801 | 0.00058604 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 16407.73 | 16190.85 | 1.788801 | 21.82 | 13.57 | 0.00857172 | 12.80 | 10.21 | 0.00850000 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00857172 | 44.6346 | 14830.53 | 0.00 | 20626.55 | 19045.55 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 10915.219 | 10915.219 | 0.579734 | 0.00009549 | 311.896 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10915.22 | 10915.22 | 0.579734 | 21.11 | 12.54 | 0.00765283 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00765283 | 39.9100 | 10915.27 | 0.00 | 11766.76 | 11766.76 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12450.130 | 12450.130 | 1.157605 | 0.00010892 | 281.855 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12450.13 | 12450.13 | 1.157605 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00772722 | 40.5672 | 7491.93 | 0.00 | 12517.28 | 12517.28 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12841.118 | 12841.118 | 1.212694 | 0.00011234 | 290.061 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 12841.12 | 12841.12 | 1.212694 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00773254 | 40.5947 | 7646.92 | 0.00 | 12910.43 | 12910.43 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8075.766 | 8075.766 | 1.189707 | 0.00007065 | 173.679 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 8075.77 | 8075.77 | 1.189707 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00712596 | 37.4515 | 2988.31 | 0.00 | 8120.69 | 8120.69 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9665.407 | 9665.407 | 0.424125 | 0.00008456 | 261.872 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 9665.41 | 9665.41 | 0.424125 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777040 | 40.7906 | 7848.60 | 0.00 | 9713.42 | 9713.42 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 481567.872 | -999.000 | 27.363382 | 0.01720049 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 481567.87 | 481567.87 | 27.363382 | 28.21 | 15.11 | 0.00783966 | 10.55 | 8.67 | 0.00783966 | 33.90 | 0.00547527 | 15.07 | 42.6170 | 23.99 | 0.00955096 | 41.6834 | 305402.77 | 0.00 | 572489.69 | 523966.88 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 278972.326 | 278972.326 | 8.209015 | 0.00244057 | 4327.727 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 278972.33 | 278972.33 | 8.209015 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 142.0568 | 21.18 | 0.00672916 | 34.9840 | 75067.33 | 0.00 | 221977.94 | 221977.94 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45136.603 | -999.000 | 2.051317 | 0.00161217 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 45136.60 | 45136.60 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 11.72 | 6.72 | 0.00547527 | 33.90 | 0.00547527 | 15.07 | 99.9965 | 21.11 | 0.00856115 | 44.5797 | 196707.96 | 0.00 | 45179.60 | 45179.60 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20913.38 | 20913.38 | 0.615395 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.3216 | 21.11 | 0.00759628 | 39.6175 | 131036.89 | 0.00 | 16640.75 | 16640.75 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5849.818 | 5849.818 | 1.364921 | 0.00005118 | 121.988 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.0296 | 1.050294 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5849.82 | 5849.82 | 1.0000 | 1.33412508 | 1.364921 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05117154 | 60.00 | 32.22 | 27.78 | 0.000 | 5849.82 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5882.70 | 5882.70 | 1.33412508 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4231.517 | 4231.517 | 0.199807 | 0.00003702 | 111.642 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 0.7448 | 0.759740 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4231.52 | 4231.52 | 1.0000 | 0.19529902 | 0.199807 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.03701538 | 60.00 | 32.22 | 27.78 | 0.000 | 4231.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00758213 | 21.00 | 0.00758213 | 39.8167 | 3376.10 | 0.00 | 4252.70 | 4252.70 | 0.19529902 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.95 | 20.57 | 0.00800000 | 58710.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1599.372 | 1599.372 | 0.124365 | 0.00001399 | 37.261 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 0.2815 | 0.287156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1599.37 | 1599.37 | 1.0000 | 0.12155881 | 0.124365 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01399058 | 60.00 | 32.22 | 27.78 | 0.000 | 1599.37 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00749617 | 21.00 | 0.00749617 | 39.3686 | 1066.92 | 0.00 | 1607.92 | 1607.92 | 0.12155881 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.57 | 17.89 | 0.00800000 | 50162.2 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2371.519 | 2371.519 | 0.102140 | 0.00002075 | 64.720 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 0.4174 | 0.425790 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2371.52 | 2371.52 | 1.0000 | 0.09983579 | 0.102140 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.02074496 | 60.00 | 32.22 | 27.78 | 0.000 | 2371.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00735715 | 21.00 | 0.00735715 | 38.6471 | 1934.34 | 0.00 | 2383.28 | 2383.28 | 0.09983579 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.7 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1706.838 | 1706.838 | 0.073510 | 0.00001493 | 46.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 0.3004 | 0.306451 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1706.84 | 1706.84 | 1.0000 | 0.07185133 | 0.073510 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01493064 | 60.00 | 32.22 | 27.78 | 0.000 | 1706.84 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00747519 | 21.00 | 0.00747519 | 39.2598 | 1392.13 | 0.00 | 1715.30 | 1715.30 | 0.07185133 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.7 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9882.583 | 9882.583 | 1.704875 | 0.00008646 | 209.927 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.7393 | 1.774349 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9882.58 | 9882.58 | 1.0000 | 1.66640939 | 1.704875 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08644833 | 60.00 | 32.22 | 27.78 | 0.000 | 9882.58 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00734499 | 21.00 | 0.00734499 | 38.5861 | 2586.98 | 0.00 | 9937.77 | 9937.77 | 1.66640939 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.45 | 15.39 | 0.00800000 | 42898.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12082.307 | 12082.307 | 0.818337 | 0.00010570 | 289.124 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 2.1265 | 2.169295 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12082.31 | 12082.31 | 1.0000 | 0.79987295 | 0.818337 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10569051 | 60.00 | 32.22 | 27.78 | 0.000 | 12082.31 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00763364 | 21.00 | 0.00763364 | 40.0832 | 8578.31 | 0.00 | 12145.55 | 12145.55 | 0.79987295 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.49 | 18.53 | 0.00800000 | 52119.1 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30082.581 | 30082.581 | 2.497511 | 0.00026318 | 693.020 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 5.2946 | 5.401119 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30082.58 | 30082.58 | 1.0000 | 2.44116089 | 2.497511 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.26314870 | 60.00 | 32.22 | 27.78 | 0.000 | 30082.58 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00754311 | 21.00 | 0.00754311 | 39.6122 | 19388.91 | 0.00 | 30243.84 | 30243.84 | 2.44116089 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.75 | 17.62 | 0.00800000 | 49323.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13955.659 | -999.000 | 1.544539 | 0.00049845 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6716 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.544539 | 1.50969016 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 1.8410 | 1.840968 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 13955.66 | 13912.96 | 1.0000 | 1.50969016 | 1.544539 | 21.82 | 13.52 | 0.00851643 | 43566.3 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.49840366 | 6.70 | 13.37 | 6.67 | 0.000 | 13955.66 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851643 | 21.11 | 0.00851643 | 44.3498 | 12805.85 | 0.00 | 17575.56 | 16436.96 | 1.50969016 | 21.82 | 15.62 | 0.00851643 | 43566.3 | 11.15 | 11.12 | 0.00821735 | 31924.4 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7480.942 | 7480.942 | 0.397324 | 0.00006545 | 213.774 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.544539 | 1.50969016 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.3167 | 1.343151 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7480.94 | 7480.94 | 1.0000 | 0.38835941 | 0.397324 | 21.11 | 12.46 | 0.00756579 | 40430.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06543987 | 60.00 | 32.22 | 27.78 | 0.000 | 7480.94 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756579 | 21.11 | 0.00756579 | 39.4623 | 7480.99 | 0.00 | 8064.52 | 8064.52 | 0.38835941 | 16.60 | 12.73 | 0.00756579 | 35835.4 | 36.98 | 19.95 | 0.00756579 | 56601.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13640.258 | -999.000 | 1.509497 | 0.00048719 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6722 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.509497 | 1.47543881 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 1.7994 | 1.799362 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 13640.26 | 13597.70 | 1.0000 | 1.47543881 | 1.509497 | 21.82 | 13.52 | 0.00851676 | 43567.1 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.48713960 | 6.70 | 13.37 | 6.67 | 0.000 | 13640.26 | 31.83 | 0.00547208 | 14.39 | 0.00000000 | 0.0000 | 21.11 | 0.00851676 | 21.11 | 0.00851676 | 44.3515 | 12515.31 | 0.00 | 17178.15 | 16064.09 | 1.47543881 | 21.82 | 15.62 | 0.00851676 | 43567.1 | 11.15 | 11.12 | 0.00821732 | 31924.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7486.574 | 7486.574 | 0.397623 | 0.00006550 | 213.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.509497 | 1.47543881 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.3176 | 1.344163 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7486.57 | 7486.57 | 1.0000 | 0.38865175 | 0.397623 | 21.11 | 12.46 | 0.00756613 | 40430.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06548913 | 60.00 | 32.22 | 27.78 | 0.000 | 7486.57 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756613 | 21.11 | 0.00756613 | 39.4641 | 7486.62 | 0.00 | 8070.59 | 8070.59 | 0.38865175 | 16.60 | 12.73 | 0.00756613 | 35836.3 | 36.98 | 19.95 | 0.00756613 | 56601.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 80221.343 | -999.000 | 8.919078 | 0.00286527 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5699 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.919078 | 8.71784260 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 10.5826 | 10.582439 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 80221.34 | 80221.34 | 1.0000 | 8.71784260 | 8.919078 | 21.82 | 13.48 | 0.00846171 | 43427.5 | 12.80 | 10.18 | 0.00846171 | 34225.5 | 2.86497470 | 6.70 | 13.37 | 6.67 | 0.000 | 80221.34 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00846171 | 21.11 | 0.00846171 | 44.0680 | 73950.72 | 0.00 | 101209.42 | 95348.40 | 8.71784260 | 21.82 | 15.57 | 0.00846171 | 43427.5 | 11.10 | 11.08 | 0.00819509 | 31818.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42756.515 | 42756.515 | 2.270961 | 0.00037405 | 1221.790 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.919078 | 8.71784260 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 7.5252 | 7.676637 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 42756.52 | 42756.52 | 1.0000 | 2.21972318 | 2.270961 | 21.11 | 12.49 | 0.00759546 | 40506.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.37401449 | 60.00 | 32.22 | 27.78 | 0.000 | 42756.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00759546 | 21.11 | 0.00759546 | 39.6132 | 42756.63 | 0.00 | 46092.49 | 46092.49 | 2.21972318 | 16.60 | 12.76 | 0.00759546 | 35910.5 | 36.98 | 19.97 | 0.00759546 | 56675.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75615.675 | -999.000 | 8.029015 | 0.00270077 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9582 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.029015 | 7.84786146 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 9.9751 | 9.974880 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | Sensible | 75615.67 | 73280.71 | 1.0000 | 7.84786146 | 8.029015 | 21.82 | 13.65 | 0.00867059 | 43957.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 2.70049075 | 6.70 | 13.37 | 6.67 | 0.000 | 75615.67 | 33.75 | 0.00547504 | 15.02 | 0.00000000 | 0.0000 | 21.11 | 0.00867059 | 21.11 | 0.00867059 | 45.1428 | 66565.41 | 0.00 | 94766.77 | 85566.05 | 7.84786146 | 21.82 | 15.75 | 0.00867059 | 43957.4 | 11.14 | 11.10 | 0.00820566 | 31881.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42878.243 | 42878.243 | 2.277427 | 0.00037512 | 1225.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.029015 | 7.84786146 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 7.5466 | 7.698492 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 42878.24 | 42878.24 | 1.0000 | 2.22604274 | 2.277427 | 21.11 | 12.49 | 0.00759644 | 40508.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.37507931 | 60.00 | 32.22 | 27.78 | 0.000 | 42878.24 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00759644 | 21.11 | 0.00759644 | 39.6182 | 42878.36 | 0.00 | 46223.72 | 46223.72 | 2.22604274 | 16.60 | 12.76 | 0.00759644 | 35913.0 | 36.98 | 19.97 | 0.00759644 | 56678.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12232.831 | -999.000 | 1.353388 | 0.00043692 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6740 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.353388 | 1.32285225 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 1.6137 | 1.613700 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 12232.83 | 12192.49 | 1.0000 | 1.32285225 | 1.353388 | 21.82 | 13.52 | 0.00851771 | 43569.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.43687564 | 6.70 | 13.37 | 6.67 | 0.000 | 12232.83 | 27.44 | 0.00546540 | 12.88 | 0.00000000 | 0.0000 | 21.11 | 0.00851771 | 21.11 | 0.00851771 | 44.3564 | 11221.02 | 0.00 | 15405.15 | 14402.89 | 1.32285225 | 21.82 | 15.62 | 0.00851771 | 43569.5 | 11.15 | 11.12 | 0.00821726 | 31924.1 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7480.942 | 7480.942 | 0.397324 | 0.00006545 | 213.774 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.353388 | 1.32285225 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.3167 | 1.343151 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7480.94 | 7480.94 | 1.0000 | 0.38835941 | 0.397324 | 21.11 | 12.46 | 0.00756579 | 40430.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06543987 | 60.00 | 32.22 | 27.78 | 0.000 | 7480.94 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756579 | 21.11 | 0.00756579 | 39.4623 | 7480.99 | 0.00 | 8064.52 | 8064.52 | 0.38835941 | 16.60 | 12.73 | 0.00756579 | 35835.4 | 36.98 | 19.95 | 0.00756579 | 56601.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11956.825 | -999.000 | 1.322760 | 0.00042706 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6745 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.322760 | 1.29291526 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 1.5773 | 1.577291 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | unknown | unknown | 7/21 09:20:00 | Sensible | 11956.82 | 11916.84 | 1.0000 | 1.29291526 | 1.322760 | 21.82 | 13.53 | 0.00851797 | 43570.2 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.42701854 | 6.70 | 13.37 | 6.67 | 0.000 | 11956.82 | 26.60 | 0.00546414 | 12.59 | 0.00000000 | 0.0000 | 21.11 | 0.00851797 | 21.11 | 0.00851797 | 44.3577 | 10967.08 | 0.00 | 15057.44 | 14076.97 | 1.29291526 | 21.82 | 15.62 | 0.00851797 | 43570.2 | 11.15 | 11.12 | 0.00821724 | 31924.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7486.574 | 7486.574 | 0.397623 | 0.00006550 | 213.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.322760 | 1.29291526 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.3176 | 1.344163 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7486.57 | 7486.57 | 1.0000 | 0.38865175 | 0.397623 | 21.11 | 12.46 | 0.00756613 | 40430.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06548913 | 60.00 | 32.22 | 27.78 | 0.000 | 7486.57 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756613 | 21.11 | 0.00756613 | 39.4641 | 7486.62 | 0.00 | 8070.59 | 8070.59 | 0.38865175 | 16.60 | 12.73 | 0.00756613 | 35836.3 | 36.98 | 19.95 | 0.00756613 | 56601.9 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15208.322 | 15208.322 | 0.815940 | 0.00013305 | 385.504 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 2.6767 | 2.730549 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15208.32 | 15208.32 | 1.0000 | 0.79753056 | 0.815940 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.13303546 | 60.00 | 32.22 | 27.78 | 0.000 | 15208.32 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00765797 | 21.00 | 0.00765797 | 40.2073 | 11713.72 | 0.00 | 15286.41 | 15286.41 | 0.79753056 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.40 | 19.78 | 0.00800000 | 56101.9 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3702.861 | -999.000 | 0.409918 | 0.00013226 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6699 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.409918 | 0.40066938 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 0.4885 | 0.488465 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3702.86 | 3692.17 | 1.0000 | 0.40066938 | 0.409918 | 21.82 | 13.52 | 0.00851550 | 43563.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.13224166 | 6.70 | 13.37 | 6.67 | 0.000 | 3702.86 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851550 | 21.11 | 0.00851550 | 44.3450 | 3398.65 | 0.00 | 4663.48 | 4362.31 | 0.40066938 | 21.82 | 15.62 | 0.00851550 | 43563.9 | 11.15 | 11.12 | 0.00821742 | 31924.7 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2275.747 | 2275.747 | 0.120869 | 0.00001991 | 65.028 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.409918 | 0.40066938 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 0.4005 | 0.408595 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2275.75 | 2275.75 | 1.0000 | 0.11814146 | 0.120869 | 21.11 | 12.53 | 0.00763912 | 40616.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01990720 | 60.00 | 32.22 | 27.78 | 0.000 | 2275.75 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00763912 | 21.11 | 0.00763912 | 39.8401 | 2275.76 | 0.00 | 2453.27 | 2453.27 | 0.11814146 | 16.60 | 12.80 | 0.00763912 | 36021.1 | 36.98 | 20.00 | 0.00763912 | 56786.6 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3613.483 | -999.000 | 0.399985 | 0.00012906 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6705 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.399985 | 0.39096043 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 0.4767 | 0.476674 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3613.48 | 3602.82 | 1.0000 | 0.39096043 | 0.399985 | 21.82 | 13.52 | 0.00851585 | 43564.8 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.12904967 | 6.70 | 13.37 | 6.67 | 0.000 | 3613.48 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851585 | 21.11 | 0.00851585 | 44.3468 | 3316.30 | 0.00 | 4550.86 | 4256.62 | 0.39096043 | 21.82 | 15.62 | 0.00851585 | 43564.8 | 11.15 | 11.12 | 0.00821739 | 31924.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2275.649 | 2275.649 | 0.120863 | 0.00001991 | 65.026 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.399985 | 0.39096043 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 0.4005 | 0.408577 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2275.65 | 2275.65 | 1.0000 | 0.11813637 | 0.120863 | 21.11 | 12.53 | 0.00763913 | 40616.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01990634 | 60.00 | 32.22 | 27.78 | 0.000 | 2275.65 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00763913 | 21.11 | 0.00763913 | 39.8401 | 2275.66 | 0.00 | 2453.17 | 2453.17 | 0.11813637 | 16.60 | 12.80 | 0.00763913 | 36021.1 | 36.98 | 20.00 | 0.00763913 | 56786.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16407.734 | -999.000 | 1.788801 | 0.00058604 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7744 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.788801 | 1.74844141 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 2.1645 | 2.164435 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 16407.73 | 16190.85 | 1.0000 | 1.74844141 | 1.788801 | 21.82 | 13.57 | 0.00857172 | 43706.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.58597553 | 6.70 | 13.37 | 6.67 | 0.000 | 16407.73 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00857172 | 21.11 | 0.00857172 | 44.6346 | 14830.53 | 0.00 | 20626.55 | 19045.55 | 1.74844141 | 21.82 | 15.67 | 0.00857172 | 43706.4 | 11.14 | 11.11 | 0.00821313 | 31909.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10915.219 | 10915.219 | 0.579734 | 0.00009549 | 311.896 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.788801 | 1.74844141 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.9211 | 1.959752 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10915.22 | 10915.22 | 1.0000 | 0.56665357 | 0.579734 | 21.11 | 12.54 | 0.00765283 | 40651.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09548136 | 60.00 | 32.22 | 27.78 | 0.000 | 10915.22 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00765283 | 21.11 | 0.00765283 | 39.9100 | 10915.27 | 0.00 | 11766.76 | 11766.76 | 0.56665357 | 16.60 | 12.81 | 0.00765283 | 36055.8 | 36.98 | 20.01 | 0.00765283 | 56821.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12450.130 | 12450.130 | 1.157605 | 0.00010892 | 281.855 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 2.1912 | 2.235335 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12450.13 | 12450.13 | 1.0000 | 1.13148619 | 1.157605 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10890806 | 60.00 | 32.22 | 27.78 | 0.000 | 12450.13 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00772722 | 21.00 | 0.00772722 | 40.5672 | 7491.93 | 0.00 | 12517.28 | 12517.28 | 1.13148619 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.45 | 17.17 | 0.00800000 | 47997.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12841.118 | 12841.118 | 1.212694 | 0.00011234 | 290.061 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 2.2600 | 2.305534 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 12841.12 | 12841.12 | 1.0000 | 1.18533313 | 1.212694 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11232824 | 60.00 | 32.22 | 27.78 | 0.000 | 12841.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773254 | 21.00 | 0.00773254 | 40.5947 | 7646.92 | 0.00 | 12910.43 | 12910.43 | 1.18533313 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.28 | 17.11 | 0.00800000 | 47826.6 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8075.766 | 8075.766 | 1.189707 | 0.00007065 | 173.679 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.4213 | 1.449948 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 8075.77 | 8075.77 | 1.0000 | 1.16286448 | 1.189707 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.07064311 | 60.00 | 32.22 | 27.78 | 0.000 | 8075.77 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.66 | 0.00712596 | 21.00 | 0.00712596 | 37.4515 | 2988.31 | 0.00 | 8120.69 | 8120.69 | 1.16286448 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.45 | 15.76 | 0.00800000 | 43918.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9665.407 | 9665.407 | 0.424125 | 0.00008456 | 261.872 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 1.7011 | 1.735357 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 9665.41 | 9665.41 | 1.0000 | 0.41455542 | 0.424125 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08454857 | 60.00 | 32.22 | 27.78 | 0.000 | 9665.41 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00777040 | 21.00 | 0.00777040 | 40.7906 | 7848.60 | 0.00 | 9713.42 | 9713.42 | 0.41455542 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.58 | 21.06 | 0.00800000 | 60365.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 481567.872 | -999.000 | 27.363382 | 0.01720049 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4135 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 27.363382 | 26.74599877 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 63.5275 | 63.527457 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 481567.87 | 481567.87 | 1.0000 | 26.74599877 | 27.363382 | 28.21 | 15.11 | 0.00783966 | 48367.9 | 10.55 | 8.67 | 0.00783966 | 30362.7 | 17.19873395 | 6.70 | 13.37 | 6.67 | 61311.450 | 420256.42 | 33.90 | 0.00547527 | 15.07 | 11.66146000 | 42.6170 | 23.99 | 0.00959646 | 23.99 | 0.00955096 | 41.6834 | 305402.77 | 0.00 | 572489.69 | 523966.88 | 26.74599877 | 28.21 | 17.30 | 0.00783966 | 48367.9 | 9.00 | 8.99 | 0.00711907 | 26963.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 278972.326 | 278972.326 | 8.209015 | 0.00244057 | 4327.727 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 27.363382 | 26.74599877 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 49.0994 | 50.087551 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 278972.33 | 278972.33 | 1.0000 | 8.02379963 | 8.209015 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 2.44032264 | 60.00 | 32.22 | 27.78 | 0.000 | 278972.33 | -17.90 | 0.00095524 | -17.90 | 11.66146000 | 142.0568 | 18.68 | 0.00686621 | 21.18 | 0.00672916 | 34.9840 | 75067.33 | 0.00 | 221977.94 | 221977.94 | 8.02379963 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45136.603 | -999.000 | 2.051317 | 0.00161217 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.0183 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 27.07291413 | 13.37 | 6.70 | 6.67 | 758046.82 | 5.9543 | 5.954329 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 45136.60 | 45136.60 | 1.0000 | 2.00503462 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 48102.5 | 11.72 | 6.72 | 0.00547527 | 25590.8 | 1.61201042 | 6.70 | 13.37 | 6.67 | 2195.006 | 42941.60 | 33.90 | 0.00547527 | 15.07 | 2.05124512 | 99.9965 | 21.11 | 0.00855359 | 21.11 | 0.00856115 | 44.5797 | 196707.96 | 0.00 | 45179.60 | 45179.60 | 2.00503462 | 33.90 | 17.27 | 0.00547527 | 48102.5 | 11.70 | 8.38 | 0.00547527 | 25569.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 4.87211410 | 54.44 | 82.22 | 27.78 | 568178.62 | 3.6808 | 3.754852 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 20913.38 | 20913.38 | 1.0000 | 0.60151039 | 0.615395 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 0.18294069 | 60.00 | 32.22 | 27.78 | 0.000 | 20913.38 | -17.90 | 0.00095524 | -17.90 | 2.05124512 | 333.3216 | 21.11 | 0.00759534 | 21.11 | 0.00759628 | 39.6175 | 131036.89 | 0.00 | 16640.75 | 16640.75 | 0.60151039 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 27.36 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 665.50 | 6020.17 | 352.67 |
RETAIL_1_FLR_1 | 2847.50 | 6038.67 | 1036.67 |
RETAIL_2_FLR_1 | 1306.33 | 5762.83 | 428.67 |
MECH_FLR_1 | 882.67 | 7282.83 | 518.00 |
STORAGE_FLR_1 | 882.67 | 7817.00 | 687.50 |
LAUNDRY_FLR_1 | 8121.67 | 3426.67 | 3262.17 |
CAFE_FLR_1 | 3997.83 | 3780.33 | 762.83 |
LOBBY_FLR_1 | 2079.33 | 3543.00 | 520.17 |
ROOM_1_FLR_3 | 2211.33 | 7667.00 | 1822.17 |
ROOM_2_FLR_3 | 2927.33 | 7962.00 | 2642.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2035.67 | 8717.50 | 2017.50 |
ROOM_5_FLR_3 | 2276.83 | 7636.17 | 1866.50 |
ROOM_6_FLR_3 | 3008.33 | 7851.17 | 2725.83 |
CORRIDOR_FLR_3 | 913.67 | 7459.17 | 656.17 |
ROOM_1_FLR_6 | 2946.50 | 7608.67 | 2484.83 |
ROOM_2_FLR_6 | 3773.83 | 7882.17 | 3420.33 |
ROOM_3_MULT9_FLR_6 | 1655.00 | 7359.50 | 1269.33 |
BANQUET_FLR_6 | 3637.83 | 2267.33 | 516.00 |
DINING_FLR_6 | 4555.17 | 1322.50 | 499.17 |
KITCHEN_FLR_6 | 8551.83 | 6319.00 | 6256.00 |
CORRIDOR_FLR_6 | 1192.17 | 7068.00 | 705.00 |
Facility | 8759.50 | 8760.00 | 7809.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.17 | 0.00 | 0.17 |
RETAIL_1_FLR_1 | 2.67 | 10.67 | 2.67 | 10.67 |
RETAIL_2_FLR_1 | 0.00 | 0.33 | 0.00 | 0.33 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 407.83 | 0.00 | 407.83 |
CAFE_FLR_1 | 0.00 | 27.33 | 0.00 | 27.33 |
LOBBY_FLR_1 | 0.00 | 1.83 | 0.00 | 1.83 |
ROOM_1_FLR_3 | 0.83 | 1.00 | 0.83 | 1.00 |
ROOM_2_FLR_3 | 1.67 | 0.50 | 1.67 | 0.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 6.83 | 4.67 | 6.83 | 4.67 |
ROOM_5_FLR_3 | 1.50 | 24.50 | 1.50 | 24.50 |
ROOM_6_FLR_3 | 3.33 | 21.67 | 3.33 | 21.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 1.33 | 1.50 | 1.33 | 1.50 |
ROOM_2_FLR_6 | 2.83 | 1.00 | 2.83 | 1.00 |
ROOM_3_MULT9_FLR_6 | 1.00 | 4.17 | 1.00 | 4.17 |
BANQUET_FLR_6 | 0.00 | 73.50 | 0.00 | 73.50 |
DINING_FLR_6 | 0.00 | 92.33 | 0.00 | 92.33 |
KITCHEN_FLR_6 | 0.00 | 651.17 | 0.00 | 651.17 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 10.00 | 735.83 | 10.00 | 735.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 1.025 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.680 | 0.139 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.396 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.478 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.535 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 22.758 | 0.149 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 4.060 | 0.110 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.764 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.180 | 0.000 | 0.049 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.180 | 0.000 | 0.050 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.535 | 0.080 | 0.000 | 0.086 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.180 | 0.000 | 0.055 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.180 | 0.000 | 0.053 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.555 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.472 | 0.180 | 0.000 | 0.053 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.471 | 0.180 | 0.000 | 0.055 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.536 | 0.147 | 0.000 | 0.103 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.017 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.454 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 22.892 | 0.150 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 1.100 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.477 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.237 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.666 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.238 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.275 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 9.679 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 1.902 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 0.815 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.521 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.458 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.281 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.522 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 1.945 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.038 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 6.443 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.553 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42638430.06 | 0.00 | 42638430.06 | 0.00 | 42638430.06 | 26946214.98 | 45.67 | 10.57 | 8703.76 | 0.00 |
RETAIL_1_FLR_1 | 6170693.24 | 0.00 | 6170693.24 | 319936.80 | 6490630.04 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3706876.50 | 0.00 | 3706876.50 | 123496.01 | 3830372.51 | 2892943.94 | 667.43 | 116.94 | 7975.63 | 0.00 |
MECH_FLR_1 | 2692082.25 | 0.00 | 2692082.25 | 291871.20 | 2983953.44 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1742016.48 | 0.00 | 1742016.48 | 168393.60 | 1910410.09 | 1821682.01 | 5081.09 | 440.38 | 3238.53 | 0.00 |
LAUNDRY_FLR_1 | 60726694.36 | 0.00 | 60726694.36 | 398535.21 | 61125229.58 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26198782.40 | 0.00 | 26198782.40 | 707238.41 | 26906020.81 | 21330615.53 | 1654.02 | 253.38 | 6852.60 | 0.00 |
LOBBY_FLR_1 | 78773841.57 | 0.00 | 78773841.57 | 2020741.67 | 80794583.24 | 59728886.00 | 514.78 | 79.00 | 8166.22 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 50098.99 | 1996974.61 | 185701.25 | 2182675.87 | 1946875.62 | 0.00 | 8147.68 | 612.32 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 51559.23 | 1998206.74 | 185687.09 | 2183893.83 | 1946647.51 | 0.00 | 8103.17 | 656.83 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 58862.40 | 26456749.67 | 51812.73 | 26508562.40 | 26397887.27 | 0.00 | 8018.67 | 741.33 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 55794.54 | 26460900.27 | 51826.90 | 26512727.17 | 26405105.73 | 0.00 | 8016.19 | 743.81 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 56158.36 | 2003033.98 | 185701.25 | 2188735.23 | 1946875.62 | 0.00 | 8070.55 | 689.45 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 54508.08 | 2001155.59 | 185687.09 | 2186842.67 | 1946647.51 | 0.00 | 8063.60 | 696.40 | 0.00 |
CORRIDOR_FLR_3 | 22813064.34 | 0.00 | 22813064.34 | 224550.18 | 23037614.51 | 14972100.18 | 82.63 | 18.99 | 8658.37 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 54845.23 | 541564.14 | 185740.37 | 727304.50 | 486718.90 | 0.00 | 8185.95 | 574.05 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 56702.53 | 543364.41 | 185726.20 | 729090.61 | 486661.88 | 0.00 | 8140.11 | 619.89 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 66499.17 | 3193419.59 | 95031.27 | 3288450.86 | 3126920.42 | 0.00 | 8054.77 | 705.23 | 0.00 |
BANQUET_FLR_6 | 43631056.80 | 0.00 | 43631056.80 | 453531.30 | 44084588.10 | 37458366.31 | 3121.12 | 238.02 | 5400.85 | 0.00 |
DINING_FLR_6 | 47430571.95 | 0.00 | 47430571.95 | 453531.30 | 47884103.25 | 37458366.31 | 1755.70 | 171.79 | 6832.50 | 0.00 |
KITCHEN_FLR_6 | 62065674.26 | 0.00 | 62065674.26 | 406015.66 | 62471689.93 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11970644.80 | 0.00 | 11970644.80 | 397385.47 | 12368030.27 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.46E+10 | 10273266.13 | 0.46E+10 | 18713344.22 | 0.46E+10 | 0.43E+10 | 5772.09 | 8254.89 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3521 | 0.0000 | 1.3521 | 0.0000 | 1.3521 | 0.8545 | 45.67 | 10.57 | 8703.76 |
RETAIL_1_FLR_1 | 0.1957 | 0.0000 | 0.1957 | 0.0101 | 0.2058 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1175 | 0.0000 | 0.1175 | 0.0039 | 0.1215 | 0.0917 | 667.43 | 116.94 | 7975.63 |
MECH_FLR_1 | 0.0854 | 0.0000 | 0.0854 | 0.0093 | 0.0946 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0552 | 0.0000 | 0.0552 | 0.0053 | 0.0606 | 0.0578 | 5081.09 | 440.38 | 3238.53 |
LAUNDRY_FLR_1 | 1.9256 | 0.0000 | 1.9256 | 0.0126 | 1.9383 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8308 | 0.0000 | 0.8308 | 0.0224 | 0.8532 | 0.6764 | 1654.02 | 253.38 | 6852.60 |
LOBBY_FLR_1 | 2.4979 | 0.0000 | 2.4979 | 0.0641 | 2.5620 | 1.8940 | 514.78 | 79.00 | 8166.22 |
ROOM_1_FLR_3 | 0.0617 | 0.0016 | 0.0633 | 0.0059 | 0.0692 | 0.0617 | 0.00 | 8147.68 | 612.32 |
ROOM_2_FLR_3 | 0.0617 | 0.0016 | 0.0634 | 0.0059 | 0.0693 | 0.0617 | 0.00 | 8103.17 | 656.83 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0018 | 0.8391 | 0.0016 | 0.8407 | 0.8373 | 0.00 | 8016.19 | 743.81 |
ROOM_5_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0059 | 0.0694 | 0.0617 | 0.00 | 8070.55 | 689.45 |
ROOM_6_FLR_3 | 0.0617 | 0.0017 | 0.0635 | 0.0059 | 0.0693 | 0.0617 | 0.00 | 8063.60 | 696.40 |
CORRIDOR_FLR_3 | 0.7234 | 0.0000 | 0.7234 | 0.0071 | 0.7305 | 0.4748 | 82.63 | 18.99 | 8658.37 |
ROOM_1_FLR_6 | 0.0154 | 0.0017 | 0.0172 | 0.0059 | 0.0231 | 0.0154 | 0.00 | 8185.95 | 574.05 |
ROOM_2_FLR_6 | 0.0154 | 0.0018 | 0.0172 | 0.0059 | 0.0231 | 0.0154 | 0.00 | 8140.11 | 619.89 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0021 | 0.1013 | 0.0030 | 0.1043 | 0.0992 | 0.00 | 8054.77 | 705.23 |
BANQUET_FLR_6 | 1.3835 | 0.0000 | 1.3835 | 0.0144 | 1.3979 | 1.1878 | 3121.12 | 238.02 | 5400.85 |
DINING_FLR_6 | 1.5040 | 0.0000 | 1.5040 | 0.0144 | 1.5184 | 1.1878 | 1755.70 | 171.79 | 6832.50 |
KITCHEN_FLR_6 | 1.9681 | 0.0000 | 1.9681 | 0.0129 | 1.9810 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3796 | 0.0000 | 0.3796 | 0.0126 | 0.3922 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.7348 | 0.1839 | 80.9187 | 0.4685 | 81.3872 | 73.9670 | 5772.09 | 8254.89 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.39E+09 | 0.00 | 0.39E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 61804134.73 | 505028.53 | 62309163.26 | 64690340.46 | 8034.60 | 93.86 | 631.53 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 12.4308 | 0.0000 | 12.4308 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.9598 | 0.0160 | 1.9758 | 2.0513 | 8034.60 | 93.86 | 631.53 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 5364.87 | 3395.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 11.1430 | 14.4692 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 1.9600 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
Electricity:Building | 2532.35 | 31781.30 | 27-MAY-05:00 | 158241.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 332.05 | 3744.83 | 02-JAN-02:10 | 25084.28 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2525.25 | 31640.15 | 27-MAY-05:00 | 158000.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 867.08 | 7438.18 | 27-MAY-05:00 | 71560.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 867.08 | 7438.18 | 27-MAY-05:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 867.08 | 7438.18 | 27-MAY-05:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 867.08 | 7438.18 | 27-MAY-05:00 | 71560.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.95 | 223.93 | 02-JAN-02:10 | 1401.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.94 | 259.31 | 02-JAN-02:10 | 1623.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.64 | 250.98 | 02-JAN-02:10 | 1507.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 7.74 | 88.65 | 02-JAN-02:10 | 581.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 30.44 | 307.62 | 27-MAY-05:00 | 2922.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.09 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.09 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 247.78 | 2995.36 | 27-MAY-05:00 | 18583.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 98.78 | 883.95 | 27-MAY-05:00 | 8554.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 98.78 | 883.95 | 27-MAY-05:00 | 8554.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 325.45 | 4437.75 | 01-JAN-02:10 | 23570.01 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 325.54 | 4438.96 | 01-JAN-02:10 | 23576.46 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.35 | 67.90 | 01-JAN-02:10 | 391.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.35 | 67.89 | 01-JAN-02:10 | 391.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 38.55 | 525.67 | 01-JAN-02:10 | 2791.95 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 211.17 | 2478.49 | 27-MAY-05:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.31 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.31 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 211.17 | 2478.49 | 27-MAY-05:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.31 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.31 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.56 | 1097.01 | 09-APR-22:30 | 3466.90 | 17-NOV-07:40 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 999.64 | 2678.06 | 23-SEP-02:00 | 186172.40 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.51 | 0.00 | 01-JAN-11:10 | 2039.78 | 17-NOV-07:40 |
MedTempRefrigeration:Refrigeration:Electricity | 33.96 | 944.61 | 06-NOV-04:00 | 1245.48 | 01-JAN-09:40 |
Fans:Electricity | 603.11 | 11033.99 | 11-MAR-04:00 | 53749.96 | 13-NOV-10:30 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 832.91 | 13871.64 | 09-APR-01:40 | 60035.80 | 16-AUG-21:10 |
ExteriorEquipment:Electricity | 650.09 | 9607.53 | 02-JAN-02:20 | 39721.54 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 31.07 | 542.66 | 10-JUN-05:00 | 1847.44 | 10-JAN-21:10 |
ElectricityPurchased:Facility | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
ElectricityPurchased:Plant | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
Cogeneration:ElectricityPurchased | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
General:Cogeneration:ElectricityPurchased | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
ElectricityNet:Plant | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
Cogeneration:ElectricityNet | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
General:Cogeneration:ElectricityNet | 5246.07 | 76675.75 | 12-APR-01:50 | 410155.66 | 26-JUN-19:30 |
General:Fans:Electricity | 603.11 | 11033.99 | 11-MAR-04:00 | 53749.96 | 13-NOV-10:30 |
ExteriorLights:Electricity | 262.14 | 0.00 | 01-JAN-07:30 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.14 | 0.00 | 01-JAN-07:30 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 198.73 | 0.00 | 09-JAN-12:50 | 9938.94 | 01-JAN-13:20 |
General:HeatRecovery:Electricity | 198.73 | 0.00 | 09-JAN-12:50 | 9938.94 | 01-JAN-13:20 |
WaterSystems:Electricity | 90.74 | 1086.32 | 19-OCT-01:00 | 4738.77 | 12-JAN-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.32 | 19-OCT-01:00 | 4738.77 | 12-JAN-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 770.02 | 0.00 | 01-JAN-00:10 | 175630.45 | 26-JUN-18:10 |
General:Cooling:Electricity | 770.02 | 0.00 | 01-JAN-00:10 | 175630.45 | 26-JUN-18:10 |
Pumps:Electricity | 84.41 | 47.91 | 19-FEB-12:00 | 4364.43 | 17-JUL-19:10 |
General:Pumps:Electricity | 84.41 | 47.91 | 19-FEB-12:00 | 4364.43 | 17-JUL-19:10 |
WIRED_LTG_ELECTRICITY | 30.52 | 0.00 | 01-JAN-00:10 | 2518.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5932.92 | 31829.34 | 15-MAR-02:00 | 650549.76 | 21-DEC-17:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4144.08 | 18467.44 | 12-AUG-15:30 | 560937.54 | 21-DEC-17:50 |
WaterSystems:NaturalGas | 3295.28 | 18467.44 | 01-JAN-12:00 | 302896.75 | 08-MAR-21:40 |
Water Heater:WaterSystems:NaturalGas | 3295.28 | 18467.44 | 01-JAN-12:00 | 302896.75 | 08-MAR-21:40 |
Heating:NaturalGas | 848.80 | 0.00 | 01-JAN-11:50 | 325699.63 | 21-DEC-09:20 |
Boiler:Heating:NaturalGas | 848.80 | 0.00 | 01-JAN-11:50 | 325699.63 | 21-DEC-09:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2311.13 | -1483.23 | 15-OCT-01:30 | 483289.91 | 26-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 2311.13 | -1483.23 | 15-OCT-01:30 | 483289.91 | 26-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 2311.13 | -1483.23 | 15-OCT-01:30 | 483289.91 | 26-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 09-JAN-01:30 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 09-JAN-01:30 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 18276.15 | 132679.48 | 23-MAR-13:00 | 2112598.37 | 26-JUN-18:10 |
EnergyTransfer:Building | 5304.05 | 43127.58 | 09-APR-00:50 | 381418.82 | 26-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 717.84 | 6443.34 | 09-APR-00:50 | 36862.08 | 05-AUG-10:50 |
Refrigeration:EnergyTransfer | 180.61 | 3911.58 | 09-APR-22:30 | 10693.27 | 28-APR-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.30 | 1955.79 | 09-APR-22:30 | 5346.63 | 28-APR-06:30 |
General:Refrigeration:EnergyTransfer | 90.30 | 1955.79 | 09-APR-22:30 | 5346.63 | 28-APR-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.30 | 1955.79 | 09-APR-22:30 | 5346.63 | 28-APR-06:30 |
EnergyTransfer:Plant | 7001.92 | 17770.58 | 31-MAR-02:30 | 1178128.63 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.53 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.77 | 1783.82 | 06-NOV-04:00 | 2686.44 | 01-JAN-09:40 |
EnergyTransfer:Zone:BASEMENT | 414.12 | 34.68 | 05-MAR-18:40 | 29777.86 | 21-SEP-21:00 |
Heating:EnergyTransfer | 192.39 | 0.00 | 01-JAN-08:10 | 120361.60 | 21-DEC-09:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.16 | 0.00 | 01-JAN-00:10 | 3505.99 | 18-NOV-02:40 |
General:Heating:EnergyTransfer | 192.39 | 0.00 | 01-JAN-08:10 | 120361.60 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.16 | 0.00 | 01-JAN-00:10 | 3505.99 | 18-NOV-02:40 |
Cooling:EnergyTransfer | 5021.36 | 15537.81 | 23-MAR-04:40 | 377930.90 | 26-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 413.96 | 0.00 | 29-JAN-08:30 | 29777.86 | 21-SEP-21:00 |
General:Cooling:EnergyTransfer | 5021.36 | 15537.81 | 23-MAR-04:40 | 377930.90 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 413.96 | 0.00 | 29-JAN-08:30 | 29777.86 | 21-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 47.87 | 0.37 | 20-MAR-23:20 | 5287.57 | 07-NOV-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.85 | 0.00 | 01-JAN-00:10 | 1933.15 | 21-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.85 | 0.00 | 01-JAN-00:10 | 1933.15 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.02 | 0.00 | 03-JAN-04:20 | 5287.57 | 07-NOV-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.02 | 0.00 | 03-JAN-04:20 | 5287.57 | 07-NOV-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.07 | 25.84 | 03-MAY-06:20 | 2365.82 | 13-NOV-19:20 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 263.70 | 25-DEC-17:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 263.70 | 25-DEC-17:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.03 | 0.00 | 17-JAN-10:20 | 2325.39 | 13-NOV-19:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.03 | 0.00 | 17-JAN-10:20 | 2325.39 | 13-NOV-19:20 |
EnergyTransfer:Zone:MECH_FLR_1 | 21.69 | 0.01 | 05-MAR-05:10 | 1864.09 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.43 | 0.00 | 01-JAN-00:10 | 895.32 | 22-DEC-04:50 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.43 | 0.00 | 01-JAN-00:10 | 895.32 | 22-DEC-04:50 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.26 | 0.00 | 01-JAN-09:30 | 1864.09 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.26 | 0.00 | 01-JAN-09:30 | 1864.09 | 26-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.98 | 0.02 | 16-APR-12:50 | 1002.16 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.66 | 0.00 | 01-JAN-00:10 | 738.51 | 23-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.66 | 0.00 | 01-JAN-00:10 | 738.51 | 23-DEC-07:50 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.32 | 0.00 | 01-JAN-09:30 | 1002.16 | 26-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.32 | 0.00 | 01-JAN-09:30 | 1002.16 | 26-JUN-18:30 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 593.38 | 5573.77 | 02-OCT-03:40 | 40157.01 | 28-FEB-20:50 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 783.10 | 02-OCT-02:20 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 783.10 | 02-OCT-02:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 593.35 | 5573.77 | 02-OCT-03:40 | 40157.01 | 28-FEB-20:50 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 593.35 | 5573.77 | 02-OCT-03:40 | 40157.01 | 28-FEB-20:50 |
EnergyTransfer:Zone:CAFE_FLR_1 | 240.05 | 12.24 | 20-DEC-08:20 | 18576.42 | 05-NOV-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.27 | 0.00 | 01-JAN-00:10 | 3330.75 | 21-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.27 | 0.00 | 01-JAN-00:10 | 3330.75 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 239.78 | 0.00 | 05-JAN-09:10 | 18576.42 | 05-NOV-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 239.78 | 0.00 | 05-JAN-09:10 | 18576.42 | 05-NOV-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 749.44 | 322.75 | 11-NOV-16:30 | 52568.36 | 09-OCT-04:30 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.38 | 0.00 | 01-JAN-00:10 | 5910.16 | 23-NOV-14:30 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.38 | 0.00 | 01-JAN-00:10 | 5910.16 | 23-NOV-14:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 749.07 | 0.00 | 17-JAN-10:20 | 52568.36 | 09-OCT-04:30 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 749.07 | 0.00 | 17-JAN-10:20 | 52568.36 | 09-OCT-04:30 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 68.54 | 0.03 | 24-JAN-07:50 | 14495.37 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 16.49 | 0.00 | 01-JAN-08:10 | 7542.02 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 16.49 | 0.00 | 01-JAN-08:10 | 7542.02 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.05 | 0.00 | 01-JAN-00:10 | 14495.37 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.05 | 0.00 | 01-JAN-00:10 | 14495.37 | 16-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 63.02 | 0.08 | 07-APR-03:50 | 13678.75 | 26-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 22.55 | 0.00 | 01-JAN-08:10 | 7570.99 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 22.55 | 0.00 | 01-JAN-08:10 | 7570.99 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.48 | 0.00 | 01-JAN-00:10 | 13678.75 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.48 | 0.00 | 01-JAN-00:10 | 13678.75 | 26-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 495.25 | 0.22 | 20-MAR-16:10 | 71405.86 | 07-NOV-12:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 11.30 | 0.00 | 01-JAN-00:10 | 29700.82 | 21-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 11.30 | 0.00 | 01-JAN-00:10 | 29700.82 | 21-DEC-05:40 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 483.96 | 0.00 | 05-JAN-01:40 | 71405.86 | 07-NOV-12:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 483.96 | 0.00 | 05-JAN-01:40 | 71405.86 | 07-NOV-12:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 390.09 | 0.70 | 18-FEB-02:50 | 74122.22 | 26-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 62.36 | 0.00 | 01-JAN-08:10 | 41624.06 | 21-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 62.36 | 0.00 | 01-JAN-08:10 | 41624.06 | 21-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 327.74 | 0.00 | 01-JAN-00:10 | 74122.22 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 327.74 | 0.00 | 01-JAN-00:10 | 74122.22 | 26-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 72.64 | 0.10 | 09-DEC-09:00 | 16317.86 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 16.90 | 0.00 | 01-JAN-08:00 | 7361.53 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 16.90 | 0.00 | 01-JAN-08:00 | 7361.53 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 55.74 | 0.00 | 01-JAN-00:10 | 16317.86 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 55.74 | 0.00 | 01-JAN-00:10 | 16317.86 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 66.97 | 0.31 | 27-MAY-01:10 | 16392.62 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 22.90 | 0.00 | 01-JAN-08:10 | 7463.43 | 21-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 22.90 | 0.00 | 01-JAN-08:10 | 7463.43 | 21-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 44.06 | 0.00 | 01-JAN-00:10 | 16392.62 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 44.06 | 0.00 | 01-JAN-00:10 | 16392.62 | 01-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 179.68 | 2.40 | 01-FEB-10:40 | 13604.66 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 2.34 | 0.00 | 01-JAN-00:10 | 5684.62 | 21-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 2.34 | 0.00 | 01-JAN-00:10 | 5684.62 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 177.34 | 0.00 | 04-JAN-12:10 | 13604.66 | 26-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 177.34 | 0.00 | 04-JAN-12:10 | 13604.66 | 26-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.31 | 0.01 | 06-OCT-04:20 | 3980.32 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.39 | 0.00 | 01-JAN-08:10 | 2262.79 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.39 | 0.00 | 01-JAN-08:10 | 2262.79 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.92 | 0.00 | 01-JAN-00:10 | 3980.32 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.92 | 0.00 | 01-JAN-00:10 | 3980.32 | 16-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.45 | 0.13 | 13-OCT-23:40 | 3721.60 | 26-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.45 | 0.00 | 01-JAN-08:10 | 2262.99 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.45 | 0.00 | 01-JAN-08:10 | 2262.99 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.00 | 0.00 | 01-JAN-00:10 | 3721.60 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.00 | 0.00 | 01-JAN-00:10 | 3721.60 | 26-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 113.74 | 0.04 | 02-OCT-04:50 | 19311.07 | 05-NOV-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 16.20 | 0.00 | 01-JAN-00:10 | 10457.35 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 16.20 | 0.00 | 01-JAN-00:10 | 10457.35 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 97.54 | 0.00 | 01-JAN-01:40 | 19311.07 | 05-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 97.54 | 0.00 | 01-JAN-01:40 | 19311.07 | 05-NOV-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 426.99 | 1271.21 | 12-OCT-10:00 | 23638.42 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1757.62 | 23-NOV-14:30 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1757.62 | 23-NOV-14:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 426.94 | 1271.21 | 12-OCT-10:00 | 23638.42 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 426.94 | 1271.21 | 12-OCT-10:00 | 23638.42 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 466.79 | 1128.57 | 21-FEB-10:10 | 24848.73 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 1566.20 | 23-NOV-14:30 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 1566.20 | 23-NOV-14:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 466.76 | 698.49 | 21-FEB-10:10 | 24848.73 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 466.76 | 698.49 | 21-FEB-10:10 | 24848.73 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 388.11 | 12-APR-00:40 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 388.11 | 12-APR-00:40 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 627.53 | 3809.69 | 23-MAR-04:40 | 31806.37 | 05-AUG-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 627.53 | 3809.69 | 23-MAR-04:40 | 31806.37 | 05-AUG-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.15 | 0.18 | 29-MAR-03:40 | 7408.19 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.64 | 0.00 | 01-JAN-00:10 | 4015.41 | 21-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.64 | 0.00 | 01-JAN-00:10 | 4015.41 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 88.51 | 0.00 | 01-JAN-09:30 | 7408.19 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 88.51 | 0.00 | 01-JAN-09:30 | 7408.19 | 16-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 1390.10 | 9317.68 | 12-AUG-01:30 | 300193.14 | 21-DEC-09:10 |
PlantLoopHeatingDemand:Plant | 786.03 | 9317.68 | 12-AUG-01:30 | 58334.93 | 13-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 786.03 | 9317.68 | 12-AUG-01:30 | 58334.93 | 13-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 786.03 | 9317.68 | 12-AUG-01:30 | 58334.93 | 13-FEB-07:10 |
EnergyTransfer:HVAC | 5970.18 | 212.82 | 30-MAY-07:50 | 711123.03 | 22-DEC-03:00 |
HeatingCoils:EnergyTransfer | 604.07 | 0.00 | 01-JAN-11:50 | 268105.61 | 21-DEC-09:10 |
PlantLoopHeatingDemand:HVAC | 604.07 | 0.00 | 01-JAN-11:50 | 268105.61 | 21-DEC-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 604.07 | 0.00 | 01-JAN-11:50 | 268105.61 | 21-DEC-09:10 |
CoolingCoils:EnergyTransfer | 2311.13 | -1483.23 | 15-OCT-01:30 | 483289.91 | 26-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2995.47 | 0.00 | 09-JAN-12:50 | 502306.93 | 22-DEC-03:00 |
HeatRecoveryForCooling:EnergyTransfer | 59.50 | 0.00 | 01-JAN-00:10 | 127766.04 | 16-AUG-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 786.03 | 9317.68 | 12-AUG-01:30 | 58334.93 | 13-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 786.03 | 9317.68 | 12-AUG-01:30 | 58334.93 | 13-FEB-07:10 |
Boilers:EnergyTransfer | 597.79 | 0.00 | 01-JAN-11:50 | 265021.42 | 21-DEC-09:20 |
Chillers:EnergyTransfer | 2378.89 | 0.00 | 01-JAN-00:10 | 483817.23 | 26-JUN-18:10 |
HeatRejection:EnergyTransfer | 3148.91 | 0.00 | 01-JAN-00:10 | 659447.68 | 26-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 3148.91 | 0.00 | 01-JAN-00:10 | 659447.68 | 26-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.159 | -413.965 | 0.000 | 0.000 | 135.093 | 188.948 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.339 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.850 | -46.021 | 0.000 | 0.000 | 15.108 | 8.760 | 10.186 | 36.045 | 0.000 | 0.160 | 0.001 | 0.000 | -14.177 | 0.000 | -4.227 | -7.682 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.039 | -34.029 | 0.000 | 0.000 | 16.327 | 10.144 | 11.795 | 0.000 | 0.000 | 0.062 | 0.000 | 0.000 | 0.000 | 0.000 | -1.740 | -2.598 |
MECH_FLR_1 | 0.000 | 0.000 | 0.431 | -21.261 | 0.000 | 0.000 | 3.629 | 8.172 | 12.471 | 0.000 | 0.000 | 0.149 | 0.294 | 0.000 | 0.000 | 0.000 | -3.884 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.660 | -12.318 | 0.000 | 0.000 | 2.842 | 4.146 | 3.598 | 0.000 | 0.000 | 0.088 | 3.179 | 0.000 | 0.000 | 0.000 | -2.195 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.036 | -593.347 | 0.000 | 0.000 | 10.810 | 5.547 | 658.131 | 0.000 | 0.000 | 0.202 | 0.000 | 0.000 | 0.000 | 0.000 | -5.768 | -75.611 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.271 | -239.784 | 0.000 | 0.000 | 185.396 | 16.095 | 14.341 | 100.335 | 0.000 | 0.350 | 0.001 | 0.000 | -42.337 | 0.000 | -9.980 | -24.686 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.376 | -749.073 | 0.000 | 0.000 | 539.960 | 98.780 | 148.998 | 132.836 | 0.000 | 1.004 | 0.000 | 0.000 | -56.772 | 0.000 | -29.062 | -87.048 |
ROOM_1_FLR_3 | 19.603 | -41.701 | 0.000 | -13.467 | 0.000 | 0.000 | 9.531 | 10.925 | 10.478 | 63.604 | 0.000 | 0.509 | 0.001 | 0.000 | -31.698 | 0.000 | -10.298 | -17.487 |
ROOM_2_FLR_3 | 26.367 | -31.218 | 0.000 | -13.078 | 0.000 | 0.000 | 9.585 | 10.924 | 10.477 | 41.986 | 0.000 | 0.510 | 0.000 | 0.000 | -32.378 | 0.000 | -10.190 | -12.985 |
ROOM_3_MULT19_FLR_3 | 15.340 | -285.206 | 0.000 | -202.790 | 0.000 | 0.000 | 0.000 | 130.455 | 194.997 | 436.550 | 0.000 | 2.247 | 0.022 | 0.000 | -179.622 | 0.000 | -70.438 | -41.531 |
ROOM_4_MULT19_FLR_3 | 99.865 | -192.995 | 0.000 | -172.249 | 0.000 | 0.000 | 183.723 | 130.491 | 195.050 | 102.468 | 0.000 | 3.084 | 0.000 | 0.000 | -178.350 | 0.000 | -62.771 | -108.316 |
ROOM_5_FLR_3 | 20.027 | -45.323 | 0.000 | -13.550 | 0.000 | 0.000 | 9.534 | 10.925 | 10.478 | 66.657 | 0.000 | 0.506 | 0.000 | 0.000 | -31.165 | 0.000 | -10.494 | -17.596 |
ROOM_6_FLR_3 | 26.649 | -34.650 | 0.000 | -13.157 | 0.000 | 0.000 | 9.588 | 10.924 | 10.477 | 44.766 | 0.000 | 0.506 | 0.000 | 0.000 | -31.585 | 0.000 | -10.277 | -13.241 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 2.339 | -177.338 | 0.000 | 0.000 | 115.222 | 91.336 | 0.000 | 59.650 | 0.000 | 0.448 | 0.001 | 0.000 | -41.019 | 0.000 | -11.932 | -38.706 |
ROOM_1_FLR_6 | 7.286 | -10.466 | 0.000 | -3.354 | 0.000 | 0.000 | 2.383 | 2.731 | 2.620 | 15.808 | 0.000 | 0.127 | 0.000 | 0.000 | -7.904 | 0.000 | -2.587 | -6.643 |
ROOM_2_FLR_6 | 9.502 | -7.801 | 0.000 | -3.253 | 0.000 | 0.000 | 2.397 | 2.731 | 2.619 | 10.446 | 0.000 | 0.127 | 0.000 | 0.000 | -8.055 | 0.000 | -2.562 | -6.151 |
ROOM_3_MULT9_FLR_6 | 20.059 | -79.641 | 0.000 | -21.754 | 0.000 | 0.000 | 21.464 | 15.453 | 23.098 | 94.388 | 0.000 | 0.601 | 0.002 | 0.000 | -37.066 | 0.000 | -13.307 | -23.295 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.042 | -426.948 | 0.000 | 0.000 | 314.844 | 35.308 | 175.857 | 10.163 | 0.000 | 0.217 | 0.000 | 0.000 | -24.526 | 0.000 | -6.673 | -78.284 |
DINING_FLR_6 | 0.000 | 0.000 | 0.028 | -466.768 | 0.000 | 0.000 | 314.134 | 35.308 | 175.857 | 9.987 | 0.000 | 0.217 | 0.000 | 0.000 | -25.057 | 0.000 | -6.702 | -37.003 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.005 | -627.515 | 0.000 | 0.000 | 27.909 | 14.807 | 550.372 | 29.329 | 0.000 | 0.194 | 28.456 | 0.000 | -17.517 | 0.000 | -6.041 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 2.643 | -88.509 | 0.000 | 0.000 | 30.781 | 24.166 | 0.000 | 29.748 | 0.000 | 0.192 | 24.531 | 0.000 | -18.294 | 0.000 | -5.259 | -0.001 |
Total Facility | 244.698 | -729.002 | 8.877 | -4353.528 | 0.000 | 0.000 | 1960.257 | 867.075 | 2365.005 | 1284.766 | 0.000 | 11.500 | 56.488 | 0.000 | -777.522 | 0.000 | -286.385 | -652.203 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-MAY-00:23 | 0.00 | 0.00 | 0.00 | -55503.58 | 0.00 | 0.00 | 6730.18 | 2575.29 | 2534.88 | 0.00 | 0.00 | 0.00 | 43663.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 15-JAN-12:48 | 0.00 | 0.00 | 0.00 | -7665.31 | 0.00 | 0.00 | 225.86 | 238.78 | 288.68 | 7629.05 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -223.09 | -493.98 |
RETAIL_2_FLR_1 | 09-APR-01:13 | 0.00 | 0.00 | 0.00 | -5298.59 | 0.00 | 0.00 | 620.64 | 184.34 | 250.72 | 0.00 | 0.00 | 0.00 | 4323.40 | 0.00 | -0.00 | 0.00 | -80.51 | 0.00 |
MECH_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -1864.24 | 0.00 | 0.00 | 129.08 | 668.27 | 839.45 | 0.00 | 0.00 | 74.14 | 153.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 09-APR-01:13 | 0.00 | 0.00 | 0.00 | -1056.45 | 0.00 | 0.00 | 111.04 | 75.34 | 76.47 | 0.00 | 0.00 | 0.00 | 896.41 | 0.00 | -0.00 | 0.00 | -102.81 | 0.00 |
LAUNDRY_FLR_1 | 28-FEB-19:10 | 0.00 | 0.00 | 0.00 | -61196.72 | 0.00 | 0.00 | 394.92 | 403.20 | 41967.83 | 0.00 | 0.00 | 0.00 | 18710.62 | 0.00 | -0.00 | 0.00 | -279.86 | 0.00 |
CAFE_FLR_1 | 15-JAN-12:48 | 0.00 | 0.00 | 0.00 | -31423.73 | 0.00 | 0.00 | 2967.82 | 143.56 | 406.43 | 21372.89 | 0.00 | 0.00 | 7026.26 | 0.00 | -0.00 | 0.00 | -493.24 | 0.00 |
LOBBY_FLR_1 | 24-FEB-08:23 | 0.00 | 0.00 | 0.00 | -90109.32 | 0.00 | 0.00 | 11724.82 | 3269.65 | 5278.53 | 11522.88 | 0.00 | 0.00 | 59578.95 | 0.00 | -0.00 | 0.00 | -1265.51 | 0.00 |
ROOM_1_FLR_3 | 14-OCT-16:11 | 0.00 | -21791.14 | 0.00 | -556.24 | 0.00 | 0.00 | 189.89 | 277.50 | 421.44 | 6726.24 | 0.00 | 0.00 | 14979.37 | 0.00 | -0.00 | 0.00 | -247.06 | 0.00 |
ROOM_2_FLR_3 | 08-APR-18:01 | 0.00 | -21057.93 | 0.00 | -543.76 | 0.00 | 0.00 | 238.24 | 840.80 | 484.60 | 1988.47 | 0.00 | 0.00 | 18300.53 | 0.00 | -0.00 | 0.00 | -250.95 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-NOV-12:10 | 0.00 | -63104.59 | 0.00 | -8300.65 | 0.00 | 0.00 | 0.00 | 2811.47 | 2352.88 | 100454.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -406.78 | -33806.32 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -108945.47 | 0.00 | -9032.93 | 0.00 | 0.00 | 2326.64 | 5624.48 | 12159.85 | 9743.97 | 0.00 | 264.25 | 87859.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 01-JUL-07:42 | 0.00 | -20028.21 | 0.00 | -823.07 | 0.00 | 0.00 | 155.93 | 470.90 | 948.23 | 11720.29 | 0.00 | 0.00 | 7573.26 | 0.00 | -0.00 | 0.00 | -17.35 | 0.00 |
ROOM_6_FLR_3 | 01-JUL-07:42 | 0.00 | -20355.38 | 0.00 | -823.02 | 0.00 | 0.00 | 155.93 | 470.85 | 948.12 | 11747.99 | 0.00 | 0.00 | 7872.86 | 0.00 | -0.00 | 0.00 | -17.35 | 0.00 |
CORRIDOR_FLR_3 | 02-OCT-05:10 | 0.00 | 0.00 | 0.00 | -14003.18 | 0.00 | 0.00 | 4314.90 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 9628.81 | 0.00 | -2680.20 | 0.00 | -580.01 | 0.00 |
ROOM_1_FLR_6 | 08-APR-18:01 | 0.00 | -5821.10 | 0.00 | -140.54 | 0.00 | 0.00 | 58.22 | 210.22 | 121.16 | 435.69 | 0.00 | 0.00 | 5201.14 | 0.00 | -0.00 | 0.00 | -64.80 | 0.00 |
ROOM_2_FLR_6 | 08-APR-18:01 | 0.00 | -5656.70 | 0.00 | -139.62 | 0.00 | 0.00 | 58.22 | 210.20 | 121.15 | 470.12 | 0.00 | 0.00 | 5001.10 | 0.00 | -0.00 | 0.00 | -64.47 | 0.00 |
ROOM_3_MULT9_FLR_6 | 09-NOV-09:51 | 0.00 | -25616.74 | 0.00 | -1031.36 | 0.00 | 0.00 | 161.33 | 523.33 | 998.70 | 18037.68 | 0.00 | 0.00 | 7104.56 | 0.00 | -0.00 | 0.00 | -177.51 | 0.00 |
BANQUET_FLR_6 | 29-DEC-02:45 | 0.00 | 0.00 | 0.00 | -44243.11 | 0.00 | 0.00 | 15656.04 | 381.98 | 2249.30 | 0.00 | 0.00 | 0.00 | 27554.99 | 0.00 | -1329.16 | 0.00 | -270.04 | 0.00 |
DINING_FLR_6 | 29-DEC-02:45 | 0.00 | 0.00 | 0.00 | -46650.11 | 0.00 | 0.00 | 15658.45 | 381.98 | 2249.30 | 0.00 | 0.00 | 0.00 | 29986.13 | 0.00 | -1354.08 | 0.00 | -271.67 | 0.00 |
KITCHEN_FLR_6 | 12-NOV-16:41 | 0.00 | 0.00 | 0.00 | -49494.90 | 0.00 | 0.00 | 300.20 | 269.09 | 26759.11 | 0.00 | 0.00 | 0.00 | 23284.45 | 0.00 | -835.77 | 0.00 | -282.19 | 0.00 |
CORRIDOR_FLR_6 | 16-AUG-15:01 | 0.00 | 0.00 | 0.00 | -7416.09 | 0.00 | 0.00 | 771.11 | 548.96 | 0.00 | 2499.50 | 0.00 | 138.68 | 3457.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-18:02 | 0.00 | -229708.87 | 0.00 | -224067.87 | 0.00 | 0.00 | 73812.49 | 58948.06 | 120482.43 | 81780.54 | 0.00 | 7622.45 | 111130.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-JAN-22:50 | 0.00 | 0.00 | 8160.06 | 0.00 | 0.00 | 0.00 | 6664.67 | 10301.16 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32223.55 |
RETAIL_1_FLR_1 | 21-DEC-08:10 | 0.00 | 0.00 | 1941.72 | 0.00 | 0.00 | 0.00 | 370.46 | 318.38 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2180.76 | 0.00 | -446.35 | -364.30 |
RETAIL_2_FLR_1 | 25-JAN-22:50 | 0.00 | 0.00 | 634.57 | 0.00 | 0.00 | 0.00 | 787.65 | 553.03 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -91.08 | -2469.17 |
MECH_FLR_1 | 22-DEC-04:50 | 0.00 | 0.00 | 895.35 | 0.00 | 0.00 | 0.00 | 197.30 | 74.25 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -430.68 | -912.95 |
STORAGE_FLR_1 | 21-DEC-18:02 | 0.00 | 0.00 | 740.49 | 0.00 | 0.00 | 0.00 | 84.74 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -252.44 | -977.24 |
LAUNDRY_FLR_1 | 12-APR-00:40 | 0.00 | 0.00 | 6123.78 | 0.00 | 0.00 | 0.00 | 556.45 | 75.60 | 11657.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -262.79 | -18150.77 |
CAFE_FLR_1 | 12-APR-00:40 | 0.00 | 0.00 | 4095.77 | 0.00 | 0.00 | 0.00 | 9152.68 | 326.28 | 254.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2701.82 | 0.00 | -452.18 | -10674.75 |
LOBBY_FLR_1 | 25-JAN-22:50 | 0.00 | 0.00 | 13869.27 | 0.00 | 0.00 | 0.00 | 26435.31 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3999.37 | 0.00 | -1496.89 | -47901.14 |
ROOM_1_FLR_3 | 16-MAR-18:03 | 7875.80 | 344.01 | 0.00 | -344.01 | 0.00 | 0.00 | 308.03 | 748.40 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1325.16 | 0.00 | -173.76 | -7917.96 |
ROOM_2_FLR_3 | 10-MAR-17:33 | 7966.97 | 342.58 | 0.00 | -342.58 | 0.00 | 0.00 | 219.20 | 235.42 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -504.04 | 0.00 | -172.16 | -8251.06 |
ROOM_3_MULT19_FLR_3 | 21-DEC-05:40 | 29701.12 | 2796.69 | 0.00 | -2796.69 | 0.00 | 0.00 | 0.00 | 2209.01 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26135.84 | 0.00 | -5102.28 | -4005.26 |
ROOM_4_MULT19_FLR_3 | 21-DEC-16:13 | 42512.84 | 3720.43 | 0.00 | -3720.43 | 0.00 | 0.00 | 5181.41 | 2812.24 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20660.95 | 0.00 | -5306.82 | -28265.12 |
ROOM_5_FLR_3 | 20-DEC-16:13 | 7561.38 | 290.36 | 0.00 | -290.36 | 0.00 | 0.00 | 270.25 | 235.45 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3722.41 | 0.00 | -960.60 | -3584.25 |
ROOM_6_FLR_3 | 21-DEC-16:13 | 7581.77 | 282.64 | 0.00 | -282.64 | 0.00 | 0.00 | 271.87 | 235.42 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3815.40 | 0.00 | -1004.20 | -3469.63 |
CORRIDOR_FLR_3 | 21-DEC-09:30 | 0.00 | 0.00 | 5683.59 | 0.00 | 0.00 | 0.00 | 1388.12 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4501.52 | 0.00 | -1282.40 | -4607.47 |
ROOM_1_FLR_6 | 20-DEC-16:13 | 2318.65 | 72.85 | 0.00 | -72.85 | 0.00 | 0.00 | 67.49 | 58.86 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -871.59 | 0.00 | -240.69 | -1382.76 |
ROOM_2_FLR_6 | 20-DEC-16:13 | 2312.64 | 70.72 | 0.00 | -70.72 | 0.00 | 0.00 | 68.15 | 58.86 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -888.62 | 0.00 | -239.78 | -1361.28 |
ROOM_3_MULT9_FLR_6 | 20-DEC-16:13 | 10721.24 | 468.54 | 0.00 | -468.54 | 0.00 | 0.00 | 605.71 | 333.03 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4189.59 | 0.00 | -1108.43 | -6803.25 |
BANQUET_FLR_6 | 25-JAN-22:50 | 0.00 | 0.00 | 5621.12 | 0.00 | 0.00 | 0.00 | 15624.00 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1535.93 | 0.00 | -346.43 | -28402.56 |
DINING_FLR_6 | 25-JAN-22:50 | 0.00 | 0.00 | 5704.73 | 0.00 | 0.00 | 0.00 | 15618.86 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1556.87 | 0.00 | -347.36 | -28459.15 |
KITCHEN_FLR_6 | 12-APR-00:40 | 0.00 | 0.00 | 3881.22 | 0.00 | 0.00 | 0.00 | 1433.90 | 201.82 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1233.78 | 0.00 | -272.13 | -9427.00 |
CORRIDOR_FLR_6 | 21-DEC-08:02 | 0.00 | 0.00 | 4025.31 | 0.00 | 0.00 | 0.00 | 733.31 | 878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2817.02 | 0.00 | -567.24 | -2252.70 |
Total Facility | 21-DEC-09:15 | 43620.66 | 73199.78 | 16308.54 | -73199.78 | 0.00 | 0.00 | 23927.21 | 29958.11 | 88178.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83290.42 | 0.00 | -26535.25 | -92167.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 27.5176 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 27.3634 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.7588 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6675 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2192 | 3.2192 | 1.3649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4712 | 0.4712 | 0.1998 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2933 | 0.2933 | 0.1244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2227 | 0.2227 | 0.0944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1489 | 0.1489 | 0.0631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0209 | 4.0209 | 1.7049 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9300 | 1.9300 | 0.8183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8904 | 5.8904 | 2.4975 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9244 | 1.9244 | 0.8159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7302 | 2.7302 | 1.1576 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8601 | 2.8601 | 1.2127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8059 | 2.8059 | 1.1897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0003 | 1.0003 | 0.4241 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 27.5176 | 27.3634 | 27.5176 | 11.6675 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6096 | 1.6096 | 1.3649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2356 | 0.2356 | 0.1998 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1467 | 0.1467 | 0.1244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1114 | 0.1114 | 0.0944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0744 | 0.0744 | 0.0631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0105 | 2.0105 | 1.7049 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9650 | 0.9650 | 0.8183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9452 | 2.9452 | 2.4975 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9622 | 0.9622 | 0.8159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3651 | 1.3651 | 1.1576 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4301 | 1.4301 | 1.2127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4030 | 1.4030 | 1.1897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5001 | 0.5001 | 0.4241 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.7588 | 11.6675 | 11.6675 | 11.6675 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 10.00 |
Number of hours cooling loads not met | 735.83 |
Number of hours not met | 745.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 848.80 | 325699.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 770.02 | 175630.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 867.08 | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.14 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.07 | 1847.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 603.11 | 53749.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 84.41 | 4364.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 198.73 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.77 | 3295.28 | 302896.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.51 | 2039.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.96 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.74 | 5246.07 |
Natural Gas | 1788.84 | 5932.92 |
Additional | 0.00 | 0.00 |
Total | 3508.58 | 11178.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 76.43 |
Space Heating | 0.00 |
Space Cooling | 67.87 |
Fans (All) | 53.16 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 462.40 |
Subtotal | 462.40 |
Natural Gas [MJ/m2] | |
Space Heating | 74.82 |
Service Water Heating | 290.45 |
Miscellaneous (All) | 522.94 |
Subtotal | 522.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.76 |
Space Heating | 7.59 |
Space Cooling | 6.89 |
Fans (All) | 5.40 |
Service Water Heating | 30.29 |
Receptacle Equipment | 30.83 |
Miscellaneous | 11.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8711.00 | 49.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8712.17 | 47.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8698.00 | 62.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8698.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 62.00 | 0.00 | 0.00 | 0.00 |
Average | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
Sum | 192470.83 | 249.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37181.17 | 21.83 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4151.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.17 | 2.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4141.83 | 12.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4143.83 | 10.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108196.00 | 73.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 73.00 | 0.00 | 0.00 | 0.00 |
Average | 288881.47 | 5.58 | 0.00 | 0.00 | 0.00 |
Sum | 6355392.33 | 122.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8680.67 | 79.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8711.00 | 49.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8727.50 | 32.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8696.83 | 63.17 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8705.33 | 54.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8714.00 | 46.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8717.17 | 42.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8711.33 | 48.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8680.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 79.33 | 0.00 | 0.00 | 0.00 |
Average | 8736.99 | 23.01 | 0.00 | 0.00 | 0.00 |
Sum | 192213.83 | 506.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59136.33 | 19.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 700756.83 | 9660.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2097786.00 | 17643.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4134.33 | 19.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4137.83 | 16.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4141.33 | 12.67 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4146.50 | 7.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4130.33 | 23.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4131.83 | 22.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4148.83 | 5.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1235226.17 | 10488.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1237665.00 | 8050.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108244.67 | 24.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2097786.00 | 17643.00 | 0.00 | 0.00 | 0.00 |
Average | 286796.45 | 2090.59 | 0.00 | 0.00 | 0.00 |
Sum | 6309522.00 | 45993.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331939E+11 | 48903.96 | 13-JAN-15:45 | 4.17 | -1.9 | 0.817290E+10 | 4975.36 | 28-JAN-00:40 | 3.00 | 3.00 |
February | 0.280711E+11 | 51273.97 | 24-FEB-08:23 | 3.00 | 1.14 | 0.730431E+10 | 4992.09 | 24-FEB-23:49 | 2.00 | 0.18 |
March | 0.296400E+11 | 52822.33 | 26-MAR-01:32 | 4.00 | 0.95 | 0.800171E+10 | 4958.78 | 17-MAR-21:49 | 4.00 | 0.95 |
April | 0.289478E+11 | 44946.80 | 11-APR-23:00 | 6.00 | 1.12 | 0.775741E+10 | 4956.96 | 05-APR-21:40 | 6.00 | 1.12 |
May | 0.304308E+11 | 55517.08 | 12-MAY-00:23 | 4.50 | 2.57 | 0.796224E+10 | 4983.28 | 02-MAY-21:19 | 4.50 | 2.57 |
June | 0.320443E+11 | 21235.85 | 09-JUN-03:56 | 6.60 | 3.45 | 0.783625E+10 | 4865.05 | 09-JUN-03:49 | 6.60 | 3.45 |
July | 0.337228E+11 | 18640.58 | 28-JUL-21:00 | 16.00 | 15.35 | 0.810880E+10 | 4837.13 | 15-JUL-00:10 | 16.00 | 15.35 |
August | 0.375662E+11 | 21309.85 | 18-AUG-21:00 | 19.00 | 9.02 | 0.822573E+10 | 4843.67 | 23-AUG-04:00 | 11.00 | 8.67 |
September | 0.405127E+11 | 38636.96 | 21-SEP-19:40 | 0.00 | -0.5 | 0.797056E+10 | 4874.68 | 27-SEP-03:20 | 9.40 | 2.62 |
October | 0.416437E+11 | 44919.04 | 26-OCT-00:09 | 3.67 | 0.54 | 0.823603E+10 | 5126.22 | 02-OCT-01:00 | 3.67 | 0.54 |
November | 0.395867E+11 | 48521.11 | 09-NOV-01:37 | 7.00 | 3.66 | 0.796488E+10 | 5061.75 | 24-NOV-22:00 | 1.00 | -1.8 |
December | 0.386018E+11 | 49033.24 | 17-DEC-06:11 | 3.67 | -0.8 | 0.822785E+10 | 5013.08 | 05-DEC-02:00 | 3.67 | -0.8 |
Annual Sum or Average | 0.413962E+12 | 0.957687E+11 | ||||||||
Minimum of Months | 0.280711E+11 | 18640.58 | 0.00 | -1.9 | 0.730431E+10 | 4837.13 | 1.00 | -1.8 | ||
Maximum of Months | 0.416437E+11 | 55517.08 | 19.00 | 15.35 | 0.823603E+10 | 5126.22 | 16.00 | 15.35 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350596E+10 | 7665.35 | 15-JAN-12:48 | 2.50 | -0.5 | 0.669674E+09 | 455.56 | 20-JAN-22:19 | 7.67 | 1.92 |
February | 0.288041E+10 | 6851.10 | 13-FEB-14:41 | 5.00 | -1.8 | 0.604906E+09 | 447.94 | 17-FEB-22:30 | 7.00 | 3.16 |
March | 0.314265E+10 | 5397.18 | 05-MAR-13:36 | 3.67 | -2.2 | 0.681885E+09 | 482.55 | 14-MAR-21:19 | 13.00 | 3.87 |
April | 0.241825E+10 | 3502.07 | 07-APR-12:30 | 20.50 | 8.13 | 0.640414E+09 | 460.54 | 07-APR-21:19 | 11.67 | 6.33 |
May | 0.364281E+10 | 3024.55 | 11-MAY-23:53 | 5.00 | 3.03 | 0.694557E+09 | 471.84 | 31-MAY-21:30 | 17.65 | 11.72 |
June | 0.468315E+10 | 3197.55 | 26-JUN-12:40 | 36.43 | 15.33 | 0.755268E+09 | 491.88 | 07-JUN-21:10 | 36.43 | 15.33 |
July | 0.490230E+10 | 3453.00 | 23-JUL-12:00 | 32.00 | 15.97 | 0.780652E+09 | 491.84 | 12-JUL-22:10 | 32.00 | 15.97 |
August | 0.528286E+10 | 4217.65 | 31-AUG-12:40 | 30.00 | 12.25 | 0.784524E+09 | 491.87 | 25-AUG-22:10 | 30.00 | 12.25 |
September | 0.512254E+10 | 5154.40 | 28-SEP-12:50 | 30.42 | 11.32 | 0.744058E+09 | 491.84 | 08-SEP-22:10 | 30.42 | 11.32 |
October | 0.401659E+10 | 5202.24 | 10-OCT-12:30 | 23.50 | 7.91 | 0.698777E+09 | 491.06 | 10-OCT-21:19 | 13.67 | 4.16 |
November | 0.358821E+10 | 7122.84 | 23-NOV-13:30 | 4.00 | 1.61 | 0.656295E+09 | 457.18 | 16-NOV-23:30 | 4.00 | 1.61 |
December | 0.283557E+10 | 7573.64 | 18-DEC-13:32 | 4.00 | -0.4 | 0.655772E+09 | 452.80 | 14-DEC-22:10 | 4.00 | -0.4 |
Annual Sum or Average | 0.460213E+11 | 0.836678E+10 | ||||||||
Minimum of Months | 0.241825E+10 | 3024.55 | 2.50 | -2.2 | 0.604906E+09 | 447.94 | 4.00 | -0.4 | ||
Maximum of Months | 0.528286E+10 | 7665.35 | 36.43 | 15.97 | 0.784524E+09 | 491.88 | 36.43 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249455E+10 | 3261.47 | 25-JAN-22:33 | 1.67 | -0.6 | 0.895840E+09 | 585.11 | 25-JAN-22:00 | 1.00 | -1.0 |
February | 0.218373E+10 | 3281.19 | 27-FEB-22:10 | 2.00 | -0.8 | 0.793098E+09 | 591.34 | 22-FEB-22:00 | 2.00 | -0.8 |
March | 0.257390E+10 | 3753.16 | 08-MAR-04:03 | 6.17 | 0.18 | 0.900692E+09 | 586.73 | 07-MAR-23:10 | 6.17 | 0.18 |
April | 0.241623E+10 | 5299.02 | 09-APR-01:13 | 3.00 | 1.62 | 0.866587E+09 | 579.39 | 05-APR-21:40 | 3.00 | 1.62 |
May | 0.288926E+10 | 4959.78 | 12-MAY-00:23 | 4.50 | 2.57 | 0.939381E+09 | 586.25 | 02-MAY-21:19 | 4.50 | 2.57 |
June | 0.346714E+10 | 2318.84 | 26-JUN-20:10 | 32.05 | 13.25 | 0.937793E+09 | 589.14 | 09-JUN-03:49 | 32.05 | 13.25 |
July | 0.355874E+10 | 2221.82 | 17-JUL-21:00 | 29.00 | 13.54 | 0.965767E+09 | 569.55 | 12-JUL-22:10 | 29.00 | 13.54 |
August | 0.357579E+10 | 2307.78 | 16-AUG-20:10 | 28.50 | 11.68 | 0.969939E+09 | 569.59 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.330010E+10 | 2793.22 | 21-SEP-19:54 | 0.00 | -0.6 | 0.932352E+09 | 573.15 | 27-SEP-04:10 | 9.40 | 2.62 |
October | 0.278136E+10 | 3110.01 | 16-OCT-21:40 | 2.00 | -1.9 | 0.920568E+09 | 584.40 | 02-OCT-01:00 | 2.00 | -1.9 |
November | 0.248700E+10 | 5155.00 | 13-NOV-19:13 | 1.67 | 1.08 | 0.870917E+09 | 591.05 | 24-NOV-22:10 | 1.83 | -1.3 |
December | 0.230067E+10 | 3005.24 | 15-DEC-21:53 | 2.00 | -0.8 | 0.863484E+09 | 577.34 | 14-DEC-23:30 | 2.00 | -0.8 |
Annual Sum or Average | 0.340285E+11 | 0.108564E+11 | ||||||||
Minimum of Months | 0.218373E+10 | 2221.82 | 0.00 | -1.9 | 0.793098E+09 | 569.55 | 1.00 | -1.9 | ||
Maximum of Months | 0.357579E+10 | 5299.02 | 32.05 | 13.54 | 0.969939E+09 | 591.34 | 32.05 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134520E+10 | 1529.30 | 19-JAN-03:37 | 3.67 | 2.25 | 0.162501E+09 | 108.86 | 24-JAN-22:19 | 3.00 | 0.25 |
February | 0.100244E+10 | 1526.44 | 27-FEB-06:09 | 3.83 | -0.9 | 0.145002E+09 | 109.89 | 27-FEB-22:49 | 2.00 | -0.8 |
March | 0.148637E+10 | 1537.68 | 01-MAR-10:53 | 2.00 | -0.8 | 0.167736E+09 | 117.02 | 15-MAR-21:19 | 12.67 | 3.04 |
April | 0.146731E+10 | 1628.94 | 09-APR-01:13 | 3.00 | 1.62 | 0.163265E+09 | 113.15 | 20-APR-21:19 | 14.00 | 7.96 |
May | 0.193846E+10 | 1625.92 | 12-MAY-00:23 | 4.50 | 2.57 | 0.187534E+09 | 120.45 | 16-MAY-21:10 | 16.83 | 10.08 |
June | 0.249894E+10 | 1864.09 | 26-JUN-20:00 | 32.70 | 13.66 | 0.197120E+09 | 120.46 | 07-JUN-21:10 | 32.70 | 13.66 |
July | 0.264473E+10 | 1860.06 | 17-JUL-20:00 | 30.00 | 13.88 | 0.203673E+09 | 120.46 | 15-JUL-00:10 | 30.00 | 13.88 |
August | 0.248735E+10 | 1734.03 | 16-AUG-20:00 | 29.00 | 11.91 | 0.203685E+09 | 120.46 | 10-AUG-21:10 | 29.00 | 11.91 |
September | 0.219404E+10 | 1562.93 | 12-SEP-20:00 | 23.80 | 13.35 | 0.192274E+09 | 120.46 | 20-SEP-21:10 | 15.32 | 11.76 |
October | 0.168446E+10 | 1611.08 | 02-OCT-05:10 | 3.00 | 3.00 | 0.177030E+09 | 119.43 | 11-OCT-21:10 | 9.67 | 4.56 |
November | 0.139064E+10 | 1598.71 | 13-NOV-19:13 | 1.67 | 1.08 | 0.160641E+09 | 113.69 | 09-NOV-22:10 | 1.67 | 1.08 |
December | 0.112075E+10 | 1514.59 | 04-DEC-00:20 | 4.33 | 1.34 | 0.159663E+09 | 108.39 | 04-DEC-22:10 | 7.17 | 0.72 |
Annual Sum or Average | 0.212607E+11 | 0.212012E+10 | ||||||||
Minimum of Months | 0.100244E+10 | 1514.59 | 1.67 | -0.9 | 0.145002E+09 | 108.39 | 1.67 | -0.8 | ||
Maximum of Months | 0.264473E+10 | 1864.09 | 32.70 | 13.88 | 0.203685E+09 | 120.46 | 32.70 | 13.88 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720528E+09 | 1002.56 | 19-JAN-03:37 | 3.67 | 2.25 | 0.120698E+09 | 78.50 | 20-JAN-22:30 | 7.50 | 1.84 |
February | 0.508543E+09 | 990.82 | 27-FEB-06:09 | 3.83 | -0.9 | 0.108568E+09 | 79.35 | 27-FEB-22:49 | 2.00 | -0.8 |
March | 0.809608E+09 | 998.46 | 01-MAR-10:53 | 2.00 | -0.8 | 0.124444E+09 | 84.87 | 15-MAR-21:30 | 12.50 | 3.03 |
April | 0.840723E+09 | 1056.45 | 09-APR-01:13 | 3.00 | 1.62 | 0.120706E+09 | 82.86 | 20-APR-22:10 | 13.83 | 7.91 |
May | 0.122711E+10 | 1052.43 | 12-MAY-00:23 | 4.50 | 2.57 | 0.138141E+09 | 89.80 | 17-MAY-22:10 | 18.00 | 9.14 |
June | 0.147397E+10 | 1002.16 | 26-JUN-18:30 | 36.60 | 14.84 | 0.148812E+09 | 92.66 | 07-JUN-21:10 | 36.60 | 14.84 |
July | 0.154267E+10 | 952.01 | 17-JUL-19:10 | 30.83 | 14.16 | 0.154289E+09 | 92.66 | 14-JUL-23:00 | 30.83 | 14.16 |
August | 0.147714E+10 | 852.45 | 16-AUG-20:00 | 29.00 | 11.91 | 0.153368E+09 | 92.66 | 10-AUG-21:10 | 29.00 | 11.91 |
September | 0.133616E+10 | 925.14 | 16-SEP-02:46 | 7.20 | 3.43 | 0.143167E+09 | 92.66 | 08-SEP-21:00 | 7.20 | 3.43 |
October | 0.100298E+10 | 1043.13 | 02-OCT-05:10 | 3.00 | 3.00 | 0.130282E+09 | 86.46 | 11-OCT-21:19 | 9.33 | 4.48 |
November | 0.797286E+09 | 1029.46 | 13-NOV-19:13 | 1.67 | 1.08 | 0.118750E+09 | 82.20 | 09-NOV-22:30 | 1.67 | 1.08 |
December | 0.581085E+09 | 984.70 | 04-DEC-00:20 | 4.33 | 1.34 | 0.119434E+09 | 78.39 | 04-DEC-23:10 | 7.83 | 0.81 |
Annual Sum or Average | 0.123178E+11 | 0.158066E+10 | ||||||||
Minimum of Months | 0.508543E+09 | 852.45 | 1.67 | -0.9 | 0.108568E+09 | 78.39 | 1.67 | -0.8 | ||
Maximum of Months | 0.154267E+10 | 1056.45 | 36.60 | 14.84 | 0.154289E+09 | 92.66 | 36.60 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485752E+11 | 56231.70 | 09-JAN-07:10 | 4.17 | 1.17 | 0.627063E+09 | 519.69 | 25-JAN-22:00 | 1.00 | -1.0 |
February | 0.436166E+11 | 61205.43 | 28-FEB-19:10 | 2.00 | 2.00 | 0.564045E+09 | 548.85 | 22-FEB-22:00 | 2.00 | 2.00 |
March | 0.493410E+11 | 54952.26 | 05-MAR-20:47 | 0.17 | -4.1 | 0.631601E+09 | 533.51 | 03-MAR-21:30 | 0.17 | -4.1 |
April | 0.476543E+11 | 55150.37 | 22-APR-20:46 | 1.33 | 1.26 | 0.611575E+09 | 532.24 | 05-APR-21:40 | 1.33 | 1.26 |
May | 0.512250E+11 | 49107.03 | 02-MAY-21:45 | 2.40 | -0.3 | 0.627726E+09 | 538.50 | 02-MAY-21:19 | 2.40 | -0.3 |
June | 0.514377E+11 | 39416.17 | 26-JUN-20:00 | 32.70 | 13.66 | 0.610681E+09 | 428.37 | 09-JUN-03:49 | 32.70 | 13.66 |
July | 0.529327E+11 | 39376.50 | 17-JUL-20:00 | 30.00 | 13.88 | 0.629164E+09 | 381.88 | 28-JUL-21:10 | 16.00 | 15.35 |
August | 0.530342E+11 | 39319.15 | 16-AUG-20:00 | 29.00 | 11.91 | 0.630342E+09 | 382.01 | 31-AUG-21:10 | 23.70 | 11.86 |
September | 0.505039E+11 | 52936.02 | 21-SEP-19:27 | 0.00 | -0.4 | 0.608431E+09 | 509.59 | 21-SEP-20:00 | 1.10 | -0.6 |
October | 0.498221E+11 | 52166.12 | 02-OCT-20:14 | 3.67 | 3.67 | 0.627605E+09 | 559.73 | 02-OCT-22:10 | 3.07 | 3.07 |
November | 0.474280E+11 | 58140.78 | 02-NOV-19:49 | 1.00 | -2.8 | 0.608447E+09 | 578.47 | 24-NOV-22:10 | 1.83 | -1.3 |
December | 0.477762E+11 | 53045.69 | 12-DEC-20:28 | 0.50 | -1.8 | 0.622651E+09 | 491.68 | 02-DEC-00:10 | 0.50 | -1.8 |
Annual Sum or Average | 0.593347E+12 | 0.739933E+10 | ||||||||
Minimum of Months | 0.436166E+11 | 39319.15 | 0.00 | -4.1 | 0.564045E+09 | 381.88 | 0.17 | -4.1 | ||
Maximum of Months | 0.530342E+11 | 61205.43 | 32.70 | 13.88 | 0.631601E+09 | 578.47 | 32.70 | 15.35 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196808E+11 | 31424.37 | 15-JAN-12:48 | 2.50 | -0.5 | 0.102267E+11 | 7126.39 | 20-JAN-02:20 | 6.67 | 1.12 |
February | 0.169150E+11 | 26611.86 | 13-FEB-14:41 | 5.00 | -1.8 | 0.906578E+10 | 7141.06 | 24-FEB-23:49 | 2.00 | 0.18 |
March | 0.185180E+11 | 29423.22 | 26-MAR-01:32 | 4.00 | 0.95 | 0.101948E+11 | 7188.43 | 23-MAR-04:49 | 4.00 | 0.95 |
April | 0.158062E+11 | 20368.91 | 17-APR-21:57 | 4.00 | 0.42 | 0.972965E+10 | 6948.24 | 14-APR-04:10 | 4.00 | 0.42 |
May | 0.187602E+11 | 17205.37 | 09-MAY-04:41 | 3.00 | 0.59 | 0.106319E+11 | 7079.88 | 09-MAY-04:49 | 3.00 | 0.59 |
June | 0.218325E+11 | 13672.96 | 09-JUN-04:00 | 6.60 | 3.45 | 0.106087E+11 | 7085.85 | 09-JUN-03:49 | 6.60 | 3.45 |
July | 0.228217E+11 | 12162.01 | 23-JUL-12:00 | 32.00 | 15.97 | 0.109263E+11 | 6462.74 | 12-JUL-22:10 | 32.00 | 15.97 |
August | 0.241614E+11 | 14261.16 | 26-AUG-12:40 | 31.67 | 13.33 | 0.109795E+11 | 6462.73 | 11-AUG-22:10 | 31.67 | 13.33 |
September | 0.234674E+11 | 16788.64 | 28-SEP-12:50 | 30.42 | 11.32 | 0.105496E+11 | 6548.11 | 27-SEP-03:20 | 30.42 | 11.32 |
October | 0.206541E+11 | 25904.04 | 26-OCT-03:31 | 3.67 | 1.48 | 0.103864E+11 | 7177.92 | 20-OCT-03:20 | 3.67 | 1.48 |
November | 0.195745E+11 | 30379.20 | 11-NOV-09:10 | 2.33 | 1.42 | 0.991320E+10 | 7109.98 | 07-NOV-02:39 | 2.33 | 1.42 |
December | 0.175905E+11 | 27235.18 | 18-DEC-10:13 | 3.33 | -0.7 | 0.985961E+10 | 6982.24 | 02-DEC-00:10 | 3.33 | -0.7 |
Annual Sum or Average | 0.239782E+12 | 0.123072E+12 | ||||||||
Minimum of Months | 0.158062E+11 | 12162.01 | 2.33 | -1.8 | 0.906578E+10 | 6462.73 | 2.00 | -0.7 | ||
Maximum of Months | 0.241614E+11 | 31424.37 | 32.00 | 15.97 | 0.109795E+11 | 7188.43 | 32.00 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.568498E+11 | 81717.39 | 08-JAN-08:35 | 5.67 | 0.06 | 0.316628E+11 | 20221.84 | 28-JAN-00:40 | 3.00 | 3.00 |
February | 0.497078E+11 | 90146.65 | 24-FEB-08:23 | 3.00 | 1.14 | 0.281117E+11 | 20388.94 | 24-FEB-23:49 | 2.00 | 0.18 |
March | 0.574556E+11 | 67667.83 | 03-MAR-21:27 | 2.00 | -2.1 | 0.315739E+11 | 20551.89 | 23-MAR-04:49 | 3.83 | 0.79 |
April | 0.534058E+11 | 70313.08 | 30-APR-07:35 | 6.33 | 5.60 | 0.303579E+11 | 20169.47 | 07-APR-02:00 | 6.33 | 5.60 |
May | 0.633899E+11 | 74298.66 | 19-MAY-07:07 | 6.33 | 4.13 | 0.322945E+11 | 20783.37 | 09-MAY-04:49 | 6.33 | 4.13 |
June | 0.723126E+11 | 63775.88 | 09-JUN-04:00 | 6.60 | 3.45 | 0.316357E+11 | 20328.89 | 09-JUN-03:49 | 6.60 | 3.45 |
July | 0.751809E+11 | 42024.02 | 17-JUL-21:10 | 28.50 | 13.44 | 0.325822E+11 | 19186.26 | 12-JUL-22:10 | 28.50 | 13.44 |
August | 0.762241E+11 | 42321.90 | 16-AUG-20:10 | 28.50 | 11.68 | 0.327361E+11 | 19235.02 | 23-AUG-04:00 | 11.00 | 8.67 |
September | 0.718393E+11 | 62307.31 | 21-SEP-19:08 | 0.00 | -0.4 | 0.315672E+11 | 19475.37 | 27-SEP-03:20 | 9.40 | 2.62 |
October | 0.627151E+11 | 88781.85 | 09-OCT-04:25 | 5.00 | 5.00 | 0.318715E+11 | 21028.67 | 02-OCT-01:00 | 5.00 | 5.00 |
November | 0.568220E+11 | 87169.83 | 18-NOV-17:27 | 4.00 | 3.74 | 0.306329E+11 | 20275.42 | 07-NOV-02:39 | 4.00 | 3.74 |
December | 0.531627E+11 | 66508.39 | 30-DEC-18:45 | 1.00 | 0.07 | 0.307400E+11 | 20234.40 | 05-DEC-02:00 | 1.00 | 0.07 |
Annual Sum or Average | 0.749066E+12 | 0.375766E+12 | ||||||||
Minimum of Months | 0.497078E+11 | 42024.02 | 0.00 | -2.1 | 0.281117E+11 | 19186.26 | 1.00 | 0.07 | ||
Maximum of Months | 0.762241E+11 | 90146.65 | 28.50 | 13.44 | 0.327361E+11 | 21028.67 | 28.50 | 13.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367669E+09 | 5079.48 | 20-JAN-17:11 | 11.00 | 4.86 | 96489764.39 | 56.69 | 24-JAN-22:49 | 3.00 | 0.25 |
February | 0.379774E+09 | 4938.39 | 26-FEB-17:51 | 12.00 | 3.75 | 86866517.51 | 56.69 | 27-FEB-22:19 | 2.00 | -0.8 |
March | 0.651475E+09 | 5573.07 | 08-MAR-17:11 | 14.33 | 3.92 | 98576682.38 | 79.35 | 13-MAR-18:10 | 17.33 | 4.68 |
April | 0.456877E+09 | 5581.85 | 08-APR-18:01 | 13.50 | 4.30 | 94870700.25 | 80.74 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.102967E+10 | 5513.08 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103734E+09 | 82.62 | 15-MAY-21:10 | 14.33 | 8.19 |
June | 0.229737E+10 | 5266.25 | 06-JUN-21:51 | 25.60 | 8.71 | 0.102860E+09 | 88.61 | 22-JUN-21:10 | 16.18 | 13.70 |
July | 0.218877E+10 | 5303.65 | 01-JUL-21:51 | 18.40 | 6.90 | 0.106495E+09 | 90.72 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.223068E+10 | 5564.99 | 13-AUG-21:51 | 16.00 | 8.07 | 0.106897E+09 | 85.97 | 03-AUG-21:10 | 16.00 | 8.07 |
September | 0.178445E+10 | 5426.32 | 15-SEP-19:51 | 12.70 | 6.10 | 0.103889E+09 | 82.36 | 01-SEP-21:40 | 12.70 | 6.10 |
October | 0.893911E+09 | 5586.82 | 14-OCT-16:11 | 14.00 | 3.81 | 99737067.98 | 69.72 | 10-OCT-20:40 | 14.00 | 3.81 |
November | 0.483743E+09 | 4954.38 | 07-NOV-17:41 | 12.50 | 4.12 | 93793638.22 | 56.69 | 06-NOV-22:10 | 12.50 | 4.12 |
December | 0.248553E+09 | 4682.80 | 02-DEC-16:01 | 17.33 | 5.85 | 95374810.13 | 56.69 | 02-DEC-05:30 | 17.33 | 5.85 |
Annual Sum or Average | 0.130129E+11 | 0.118958E+10 | ||||||||
Minimum of Months | 0.248553E+09 | 4682.80 | 11.00 | 3.75 | 86866517.51 | 56.69 | 2.00 | -0.8 | ||
Maximum of Months | 0.229737E+10 | 5586.82 | 25.60 | 8.71 | 0.106897E+09 | 90.72 | 17.33 | 13.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101762E+09 | 4577.35 | 23-JAN-16:01 | 18.17 | 6.14 | 94335417.75 | 56.69 | 19-JAN-04:49 | 18.17 | 6.14 |
February | 0.120472E+09 | 4597.20 | 24-FEB-16:01 | 7.67 | 2.33 | 85253288.09 | 56.69 | 27-FEB-04:00 | 5.00 | 0.18 |
March | 0.347275E+09 | 5304.55 | 15-MAR-18:31 | 13.00 | 3.03 | 97137739.90 | 72.86 | 31-MAR-18:10 | 14.33 | 7.61 |
April | 0.310959E+09 | 5400.40 | 08-APR-18:01 | 13.50 | 4.30 | 94027355.30 | 76.43 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.923378E+09 | 5335.21 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103265E+09 | 81.31 | 15-MAY-21:10 | 14.33 | 8.19 |
June | 0.221798E+10 | 5167.45 | 27-JUN-08:51 | 25.00 | 10.85 | 0.102912E+09 | 88.34 | 22-JUN-21:10 | 25.00 | 10.85 |
July | 0.208823E+10 | 5204.33 | 01-JUL-08:61 | 26.00 | 9.47 | 0.106391E+09 | 89.96 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.195565E+10 | 5372.80 | 13-AUG-21:51 | 16.00 | 8.07 | 0.106417E+09 | 84.83 | 03-AUG-21:10 | 16.00 | 8.07 |
September | 0.138593E+10 | 5130.70 | 15-SEP-19:51 | 12.70 | 6.10 | 0.102492E+09 | 79.74 | 12-SEP-21:10 | 12.70 | 6.10 |
October | 0.457224E+09 | 5236.65 | 14-OCT-16:11 | 14.00 | 3.81 | 97993065.82 | 64.94 | 10-OCT-20:40 | 14.00 | 3.81 |
November | 0.145931E+09 | 4627.49 | 07-NOV-16:01 | 20.00 | 7.03 | 92010151.68 | 56.69 | 18-NOV-05:30 | 3.50 | 2.81 |
December | 64484979.18 | 4510.31 | 02-DEC-16:01 | 17.33 | 5.85 | 93757108.97 | 56.69 | 26-DEC-05:30 | 5.00 | 0.11 |
Annual Sum or Average | 0.101193E+11 | 0.117599E+10 | ||||||||
Minimum of Months | 64484979.18 | 4510.31 | 7.67 | 2.33 | 85253288.09 | 56.69 | 3.50 | 0.11 | ||
Maximum of Months | 0.221798E+10 | 5400.40 | 26.00 | 10.85 | 0.106417E+09 | 89.96 | 25.00 | 10.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549852E+09 | 938.96 | 20-JAN-12:40 | 20.67 | 7.18 | 0.00 | 0.00 | 01-JAN-00:10 | 20.67 | 7.18 |
February | 0.417479E+09 | 895.54 | 18-FEB-13:00 | 20.00 | 7.74 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.74 |
March | 0.417903E+09 | 824.93 | 14-MAR-12:40 | 23.33 | 7.71 | 0.00 | 0.00 | 01-MAR-00:10 | 23.33 | 7.71 |
April | 0.234154E+09 | 502.97 | 08-APR-13:00 | 16.00 | 5.15 | 0.00 | 0.00 | 01-APR-00:10 | 16.00 | 5.15 |
May | 0.371299E+09 | 399.37 | 16-MAY-13:20 | 27.33 | 12.20 | 0.00 | 0.00 | 01-MAY-00:10 | 27.33 | 12.20 |
June | 0.636016E+09 | 504.82 | 14-JUN-13:30 | 34.95 | 13.21 | 0.00 | 0.00 | 01-JUN-00:10 | 34.95 | 13.21 |
July | 0.687304E+09 | 541.23 | 23-JUL-13:00 | 34.00 | 16.01 | 0.00 | 0.00 | 01-JUL-00:10 | 34.00 | 16.01 |
August | 0.766114E+09 | 677.65 | 31-AUG-12:40 | 30.00 | 12.25 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 12.25 |
September | 0.765285E+09 | 859.70 | 28-SEP-13:00 | 30.50 | 11.31 | 0.00 | 0.00 | 01-SEP-00:10 | 30.50 | 11.31 |
October | 0.599766E+09 | 885.86 | 10-OCT-12:30 | 23.50 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 | 23.50 | 7.91 |
November | 0.533185E+09 | 939.55 | 07-NOV-12:10 | 20.00 | 7.48 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 7.48 |
December | 0.389513E+09 | 839.49 | 17-DEC-13:00 | 18.00 | 5.78 | 0.00 | 0.00 | 01-DEC-00:10 | 18.00 | 5.78 |
Annual Sum or Average | 0.636787E+10 | 0.00 | ||||||||
Minimum of Months | 0.234154E+09 | 399.37 | 16.00 | 5.15 | 0.00 | 0.00 | 16.00 | 5.15 | ||
Maximum of Months | 0.766114E+09 | 939.55 | 34.95 | 16.01 | 0.00 | 0.00 | 34.95 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75962661.45 | 1283.40 | 21-JAN-09:01 | 13.00 | 3.75 | 94336122.41 | 56.69 | 27-JAN-22:19 | 3.00 | 3.00 |
February | 66388929.69 | 1275.09 | 19-FEB-09:01 | 5.17 | 2.82 | 85132240.46 | 56.69 | 27-FEB-22:40 | 2.00 | -0.8 |
March | 0.163970E+09 | 1425.32 | 14-MAR-20:51 | 13.00 | 3.78 | 95538426.60 | 62.94 | 14-MAR-20:49 | 13.00 | 3.78 |
April | 0.209158E+09 | 1448.59 | 20-APR-20:31 | 14.33 | 7.97 | 92875583.77 | 64.09 | 20-APR-20:40 | 14.33 | 7.97 |
May | 0.494195E+09 | 1491.23 | 17-MAY-21:51 | 18.00 | 9.24 | 99937640.82 | 75.04 | 30-MAY-21:10 | 14.00 | 11.46 |
June | 0.800461E+09 | 1523.21 | 06-JUN-21:51 | 25.60 | 8.71 | 0.100121E+09 | 79.05 | 22-JUN-21:49 | 16.52 | 14.01 |
July | 0.824299E+09 | 1552.36 | 01-JUL-08:61 | 26.00 | 9.47 | 0.103664E+09 | 80.36 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.728744E+09 | 1550.23 | 01-AUG-21:51 | 21.00 | 10.09 | 0.103127E+09 | 78.52 | 03-AUG-21:19 | 21.33 | 15.95 |
September | 0.558282E+09 | 1522.85 | 09-SEP-21:51 | 21.60 | 11.20 | 98506336.19 | 76.06 | 11-SEP-21:49 | 17.20 | 10.39 |
October | 0.225240E+09 | 1415.13 | 10-OCT-20:31 | 14.33 | 4.12 | 95904105.46 | 62.18 | 10-OCT-20:40 | 14.33 | 4.12 |
November | 0.102352E+09 | 1296.43 | 09-NOV-09:51 | 18.00 | 8.60 | 91701696.39 | 56.69 | 15-NOV-22:19 | 3.00 | 2.83 |
December | 63275063.49 | 1047.24 | 02-DEC-09:01 | 11.75 | 4.10 | 93982561.22 | 56.69 | 29-DEC-22:10 | 2.00 | -0.5 |
Annual Sum or Average | 0.431233E+10 | 0.115483E+10 | ||||||||
Minimum of Months | 63275063.49 | 1047.24 | 5.17 | 2.82 | 85132240.46 | 56.69 | 2.00 | -0.8 | ||
Maximum of Months | 0.824299E+09 | 1552.36 | 26.00 | 11.20 | 0.103664E+09 | 80.36 | 21.33 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366624E+09 | 4275.07 | 01-JAN-09:01 | 3.17 | 0.20 | 96597415.15 | 56.69 | 25-JAN-22:19 | 2.33 | -0.3 |
February | 0.422361E+09 | 4247.09 | 18-FEB-09:01 | 11.67 | 4.30 | 87071730.86 | 56.69 | 27-FEB-04:10 | 5.00 | 0.18 |
March | 0.726258E+09 | 4547.67 | 15-MAR-18:31 | 13.00 | 3.03 | 97832770.60 | 70.76 | 14-MAR-20:40 | 13.00 | 3.03 |
April | 0.563669E+09 | 5008.21 | 19-APR-08:51 | 18.00 | 8.66 | 94379788.41 | 67.40 | 20-APR-20:30 | 14.50 | 7.98 |
May | 0.115556E+10 | 5053.43 | 17-MAY-08:51 | 25.00 | 11.73 | 0.102894E+09 | 78.43 | 16-MAY-21:40 | 25.00 | 11.73 |
June | 0.236883E+10 | 5108.73 | 07-JUN-08:41 | 25.82 | 11.10 | 0.104122E+09 | 83.43 | 22-JUN-21:40 | 16.43 | 13.94 |
July | 0.239694E+10 | 5212.77 | 01-JUL-07:42 | 25.50 | 9.48 | 0.107436E+09 | 83.84 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.241838E+10 | 5095.65 | 19-AUG-08:51 | 24.00 | 11.71 | 0.107610E+09 | 85.43 | 31-AUG-21:10 | 23.70 | 11.86 |
September | 0.189447E+10 | 5086.35 | 18-SEP-08:51 | 22.70 | 10.68 | 0.102976E+09 | 81.33 | 08-SEP-21:00 | 22.70 | 10.68 |
October | 0.892855E+09 | 5029.17 | 11-OCT-08:51 | 20.20 | 7.65 | 98677028.38 | 68.31 | 10-OCT-20:40 | 20.20 | 7.65 |
November | 0.472567E+09 | 4878.27 | 09-NOV-09:51 | 18.00 | 8.60 | 93737814.98 | 56.69 | 07-NOV-22:10 | 18.00 | 8.60 |
December | 0.257409E+09 | 4169.90 | 17-DEC-09:01 | 7.83 | 1.76 | 95464542.43 | 56.69 | 29-DEC-02:00 | 5.00 | 0.56 |
Annual Sum or Average | 0.139359E+11 | 0.118880E+10 | ||||||||
Minimum of Months | 0.257409E+09 | 4169.90 | 3.17 | 0.20 | 87071730.86 | 56.69 | 2.33 | -0.3 | ||
Maximum of Months | 0.241838E+10 | 5212.77 | 25.82 | 11.73 | 0.107610E+09 | 85.43 | 25.00 | 13.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112563E+09 | 3941.47 | 22-JAN-09:01 | 1.33 | 0.34 | 94039808.22 | 56.69 | 19-JAN-00:40 | 1.33 | 0.34 |
February | 0.158139E+09 | 4099.57 | 27-FEB-09:01 | 9.17 | 2.67 | 85324099.71 | 56.69 | 19-FEB-04:49 | 9.17 | 2.67 |
March | 0.401934E+09 | 4260.13 | 14-MAR-20:51 | 13.00 | 3.78 | 96553765.31 | 66.31 | 14-MAR-20:40 | 13.00 | 3.78 |
April | 0.409612E+09 | 4890.43 | 19-APR-08:51 | 18.00 | 8.66 | 93735087.91 | 65.69 | 20-APR-20:30 | 14.50 | 7.98 |
May | 0.104016E+10 | 4946.39 | 17-MAY-08:51 | 25.00 | 11.73 | 0.102565E+09 | 77.40 | 16-MAY-21:40 | 25.00 | 11.73 |
June | 0.228572E+10 | 5005.70 | 07-JUN-08:41 | 25.82 | 11.10 | 0.104145E+09 | 82.63 | 29-JUN-21:40 | 20.90 | 11.81 |
July | 0.229375E+10 | 5294.55 | 01-JUL-07:42 | 25.50 | 9.48 | 0.107374E+09 | 83.50 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.213601E+10 | 4981.16 | 19-AUG-08:51 | 24.00 | 11.71 | 0.107151E+09 | 83.24 | 03-AUG-21:19 | 24.00 | 11.71 |
September | 0.148441E+10 | 4960.09 | 07-SEP-08:51 | 22.70 | 11.26 | 0.101896E+09 | 79.55 | 08-SEP-21:00 | 21.60 | 11.21 |
October | 0.449506E+09 | 4858.03 | 11-OCT-08:51 | 20.20 | 7.65 | 97245281.69 | 63.74 | 10-OCT-20:40 | 20.20 | 7.65 |
November | 0.165420E+09 | 4323.53 | 09-NOV-09:51 | 18.00 | 8.60 | 91637778.72 | 56.69 | 18-NOV-05:30 | 3.50 | 2.81 |
December | 78649414.90 | 3913.89 | 02-DEC-09:01 | 11.75 | 4.10 | 93504053.82 | 56.69 | 26-DEC-05:30 | 5.00 | 0.11 |
Annual Sum or Average | 0.110159E+11 | 0.117517E+10 | ||||||||
Minimum of Months | 78649414.90 | 3913.89 | 1.33 | 0.34 | 85324099.71 | 56.69 | 1.33 | 0.11 | ||
Maximum of Months | 0.229375E+10 | 5294.55 | 25.82 | 11.73 | 0.107374E+09 | 83.50 | 25.00 | 11.81 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292983E+10 | 3268.61 | 19-JAN-03:37 | 3.67 | 2.25 | 0.127158E+10 | 840.26 | 24-JAN-23:00 | 2.00 | 0.10 |
February | 0.226345E+10 | 3291.85 | 27-FEB-06:09 | 3.83 | -0.9 | 0.114580E+10 | 846.29 | 27-FEB-22:49 | 2.00 | -0.8 |
March | 0.311792E+10 | 3365.70 | 01-MAR-10:53 | 2.00 | -0.8 | 0.132100E+10 | 932.89 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.299571E+10 | 3455.87 | 09-APR-01:13 | 3.00 | 1.62 | 0.125710E+10 | 849.73 | 20-APR-21:40 | 14.00 | 7.96 |
May | 0.404775E+10 | 3465.79 | 12-MAY-00:23 | 4.50 | 2.57 | 0.144132E+10 | 929.01 | 17-MAY-22:10 | 18.00 | 9.14 |
June | 0.500485E+10 | 3401.16 | 26-JUN-18:30 | 36.60 | 14.84 | 0.154921E+10 | 951.90 | 07-JUN-21:10 | 36.60 | 14.84 |
July | 0.524670E+10 | 3031.26 | 15-JUL-18:30 | 32.50 | 12.97 | 0.160633E+10 | 951.86 | 15-JUL-00:10 | 32.50 | 12.97 |
August | 0.519196E+10 | 3080.05 | 11-AUG-18:20 | 30.33 | 11.29 | 0.161025E+10 | 951.88 | 07-AUG-21:19 | 30.33 | 11.29 |
September | 0.470208E+10 | 3134.12 | 16-SEP-04:15 | 7.20 | 3.77 | 0.152683E+10 | 951.90 | 01-SEP-00:49 | 7.20 | 3.77 |
October | 0.361497E+10 | 3500.98 | 02-OCT-05:10 | 3.00 | 3.00 | 0.140513E+10 | 937.07 | 11-OCT-21:30 | 9.00 | 4.40 |
November | 0.295170E+10 | 3409.31 | 13-NOV-19:13 | 1.67 | 1.08 | 0.125260E+10 | 857.51 | 09-NOV-22:40 | 1.67 | 1.08 |
December | 0.226732E+10 | 3209.26 | 04-DEC-00:20 | 4.33 | 1.34 | 0.123655E+10 | 802.31 | 05-DEC-02:00 | 4.00 | -2.2 |
Annual Sum or Average | 0.443343E+11 | 0.166237E+11 | ||||||||
Minimum of Months | 0.226345E+10 | 3031.26 | 1.67 | -0.9 | 0.114580E+10 | 802.31 | 1.67 | -2.2 | ||
Maximum of Months | 0.524670E+10 | 3500.98 | 36.60 | 14.84 | 0.161025E+10 | 951.90 | 36.60 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334821E+09 | 5564.41 | 20-JAN-17:11 | 11.00 | 4.86 | 96081697.81 | 56.69 | 09-JAN-04:10 | 11.00 | 4.86 |
February | 0.356471E+09 | 5340.28 | 26-FEB-17:51 | 12.00 | 3.75 | 86600850.60 | 56.69 | 27-FEB-04:00 | 5.00 | 0.18 |
March | 0.637390E+09 | 5908.21 | 08-MAR-17:11 | 14.33 | 3.92 | 98655428.37 | 88.80 | 13-MAR-18:10 | 17.33 | 4.68 |
April | 0.456899E+09 | 5961.62 | 08-APR-18:01 | 13.50 | 4.30 | 94952635.85 | 90.46 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.100451E+10 | 5888.05 | 27-MAY-16:11 | 14.33 | 8.19 | 0.104356E+09 | 88.69 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.237591E+10 | 5572.02 | 27-JUN-08:51 | 25.00 | 10.85 | 0.102879E+09 | 92.33 | 22-JUN-21:10 | 25.00 | 10.85 |
July | 0.223375E+10 | 5586.69 | 01-JUL-21:51 | 18.40 | 6.90 | 0.106468E+09 | 95.86 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.228386E+10 | 5919.33 | 13-AUG-21:51 | 16.00 | 8.07 | 0.106919E+09 | 89.45 | 03-AUG-21:10 | 16.00 | 8.07 |
September | 0.174755E+10 | 5854.17 | 15-SEP-19:51 | 12.70 | 6.10 | 0.104086E+09 | 87.37 | 01-SEP-21:10 | 12.70 | 6.10 |
October | 0.819452E+09 | 5908.08 | 14-OCT-16:11 | 14.00 | 3.81 | 99909935.82 | 71.52 | 05-OCT-18:10 | 14.00 | 3.81 |
November | 0.445256E+09 | 5396.49 | 05-NOV-17:41 | 13.33 | 3.43 | 93530359.64 | 56.69 | 18-NOV-04:00 | 4.00 | 2.57 |
December | 0.225030E+09 | 4990.26 | 02-DEC-17:21 | 14.00 | 4.47 | 94980207.31 | 56.69 | 26-DEC-05:30 | 5.00 | 0.11 |
Annual Sum or Average | 0.129209E+11 | 0.118942E+10 | ||||||||
Minimum of Months | 0.225030E+09 | 4990.26 | 11.00 | 3.43 | 86600850.60 | 56.69 | 4.00 | 0.11 | ||
Maximum of Months | 0.237591E+10 | 5961.62 | 25.00 | 10.85 | 0.106919E+09 | 95.86 | 25.00 | 10.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82596767.61 | 4913.15 | 20-JAN-17:11 | 11.00 | 4.86 | 93869331.11 | 56.69 | 27-JAN-01:39 | 3.33 | 2.38 |
February | 0.105281E+09 | 4836.31 | 26-FEB-17:51 | 12.00 | 3.75 | 84956879.42 | 56.69 | 27-FEB-04:19 | 5.00 | 0.18 |
March | 0.321889E+09 | 5716.69 | 15-MAR-18:31 | 13.00 | 3.03 | 97139029.36 | 81.39 | 31-MAR-18:10 | 14.33 | 7.61 |
April | 0.302569E+09 | 5796.30 | 08-APR-18:01 | 13.50 | 4.30 | 94068980.14 | 84.67 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.885242E+09 | 5706.88 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103801E+09 | 86.97 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.229236E+10 | 5466.61 | 27-JUN-08:51 | 25.00 | 10.85 | 0.102943E+09 | 92.14 | 22-JUN-21:10 | 25.00 | 10.85 |
July | 0.212758E+10 | 5461.89 | 01-JUL-21:51 | 18.40 | 6.90 | 0.106359E+09 | 95.10 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.199084E+10 | 5760.03 | 13-AUG-21:51 | 16.00 | 8.07 | 0.106392E+09 | 89.17 | 03-AUG-21:10 | 16.00 | 8.07 |
September | 0.132422E+10 | 5527.21 | 15-SEP-19:51 | 12.70 | 6.10 | 0.102469E+09 | 80.31 | 01-SEP-21:40 | 12.70 | 6.10 |
October | 0.389341E+09 | 5574.73 | 08-OCT-18:11 | 13.33 | 7.54 | 97921340.10 | 63.46 | 10-OCT-20:30 | 14.50 | 4.15 |
November | 0.126385E+09 | 4881.17 | 07-NOV-16:01 | 20.00 | 7.03 | 91639832.36 | 56.69 | 18-NOV-05:30 | 3.50 | 2.81 |
December | 52341187.49 | 4750.59 | 02-DEC-16:01 | 17.33 | 5.85 | 93388946.72 | 56.69 | 28-DEC-05:10 | 4.17 | -1.4 |
Annual Sum or Average | 0.100006E+11 | 0.117495E+10 | ||||||||
Minimum of Months | 52341187.49 | 4750.59 | 11.00 | 3.03 | 84956879.42 | 56.69 | 3.33 | -1.4 | ||
Maximum of Months | 0.229236E+10 | 5796.30 | 25.00 | 10.85 | 0.106392E+09 | 95.10 | 25.00 | 10.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.834861E+09 | 2904.96 | 20-JAN-17:11 | 11.00 | 4.86 | 97847151.53 | 56.74 | 20-JAN-04:30 | 11.00 | 4.86 |
February | 0.677028E+09 | 2713.40 | 26-FEB-17:51 | 12.00 | 3.75 | 87935025.62 | 56.69 | 21-FEB-22:19 | 12.00 | 3.75 |
March | 0.693054E+09 | 2955.56 | 13-MAR-19:21 | 13.50 | 3.24 | 98762627.15 | 81.25 | 14-MAR-20:30 | 14.50 | 4.42 |
April | 0.379140E+09 | 2711.73 | 08-APR-18:01 | 13.50 | 4.30 | 94439380.37 | 70.50 | 20-APR-20:40 | 14.33 | 7.97 |
May | 0.628481E+09 | 2661.03 | 09-MAY-20:31 | 13.67 | 7.41 | 0.102093E+09 | 77.87 | 15-MAY-21:10 | 13.83 | 9.39 |
June | 0.119604E+10 | 2733.20 | 06-JUN-21:51 | 25.60 | 8.71 | 0.101033E+09 | 80.30 | 22-JUN-21:40 | 16.43 | 13.94 |
July | 0.126322E+10 | 2731.84 | 01-JUL-08:61 | 26.00 | 9.47 | 0.104838E+09 | 82.15 | 25-JUL-21:40 | 20.00 | 15.92 |
August | 0.140337E+10 | 2805.32 | 01-AUG-21:51 | 21.00 | 10.09 | 0.105341E+09 | 85.30 | 31-AUG-21:19 | 23.40 | 11.78 |
September | 0.131790E+10 | 2950.64 | 25-SEP-20:41 | 13.08 | 5.99 | 0.103086E+09 | 85.70 | 28-SEP-21:40 | 19.60 | 7.11 |
October | 0.957821E+09 | 2957.66 | 09-OCT-19:51 | 13.00 | 6.07 | 99949682.46 | 75.68 | 10-OCT-20:40 | 14.33 | 4.12 |
November | 0.865797E+09 | 2960.90 | 09-NOV-09:51 | 18.00 | 8.60 | 94973927.63 | 56.69 | 08-NOV-23:00 | 18.00 | 8.60 |
December | 0.620811E+09 | 2709.03 | 02-DEC-17:21 | 14.00 | 4.47 | 97100397.70 | 56.69 | 01-DEC-22:49 | 14.00 | 4.47 |
Annual Sum or Average | 0.108375E+11 | 0.118740E+10 | ||||||||
Minimum of Months | 0.379140E+09 | 2661.03 | 11.00 | 3.24 | 87935025.62 | 56.69 | 11.00 | 3.75 | ||
Maximum of Months | 0.140337E+10 | 2960.90 | 26.00 | 10.09 | 0.105341E+09 | 85.70 | 23.40 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304334E+11 | 34770.88 | 30-JAN-21:23 | 0.50 | 0.27 | 0.191632E+11 | 13012.48 | 20-JAN-02:20 | 0.50 | 0.27 |
February | 0.272695E+11 | 40659.63 | 27-FEB-02:33 | 5.67 | 0.28 | 0.172899E+11 | 13306.97 | 28-FEB-22:30 | 0.50 | 0.50 |
March | 0.329420E+11 | 37616.47 | 26-MAR-01:51 | 4.00 | 0.82 | 0.193354E+11 | 14911.40 | 23-MAR-04:49 | 4.00 | 0.82 |
April | 0.326100E+11 | 38587.18 | 28-APR-04:46 | 5.17 | 4.62 | 0.187014E+11 | 13308.27 | 25-APR-22:49 | 5.17 | 4.62 |
May | 0.389416E+11 | 41318.12 | 12-MAY-00:23 | 4.50 | 2.57 | 0.193633E+11 | 13616.96 | 09-MAY-04:49 | 4.50 | 2.57 |
June | 0.430177E+11 | 34139.48 | 09-JUN-03:56 | 6.60 | 3.45 | 0.187630E+11 | 13009.93 | 09-JUN-03:49 | 6.60 | 3.45 |
July | 0.443488E+11 | 23545.80 | 17-JUL-21:20 | 28.00 | 13.33 | 0.193095E+11 | 11396.02 | 07-JUL-21:19 | 28.00 | 13.33 |
August | 0.435729E+11 | 23300.40 | 16-AUG-21:20 | 25.33 | 11.70 | 0.193908E+11 | 11423.46 | 23-AUG-04:00 | 11.00 | 8.67 |
September | 0.397055E+11 | 31295.81 | 21-SEP-19:27 | 0.00 | -0.4 | 0.187098E+11 | 11947.37 | 27-SEP-03:20 | 9.40 | 2.62 |
October | 0.343648E+11 | 36612.56 | 26-OCT-00:09 | 3.67 | 0.54 | 0.192622E+11 | 13865.63 | 02-OCT-01:00 | 3.67 | 0.54 |
November | 0.305941E+11 | 36059.70 | 09-NOV-01:37 | 7.00 | 3.66 | 0.185851E+11 | 13157.03 | 07-NOV-02:39 | 7.00 | 3.66 |
December | 0.291438E+11 | 44253.33 | 29-DEC-02:45 | 5.00 | 0.56 | 0.189898E+11 | 13046.69 | 05-DEC-02:00 | 5.00 | 0.56 |
Annual Sum or Average | 0.426944E+12 | 0.226863E+12 | ||||||||
Minimum of Months | 0.272695E+11 | 23300.40 | 0.00 | -0.4 | 0.172899E+11 | 11396.02 | 0.50 | 0.27 | ||
Maximum of Months | 0.443488E+11 | 44253.33 | 28.00 | 13.33 | 0.193908E+11 | 14911.40 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340822E+11 | 39076.05 | 30-JAN-21:23 | 0.50 | 0.27 | 0.192799E+11 | 13121.58 | 20-JAN-02:20 | 0.50 | 0.27 |
February | 0.305569E+11 | 42760.34 | 27-FEB-02:33 | 5.67 | 0.28 | 0.173999E+11 | 13476.34 | 28-FEB-22:30 | 0.50 | 0.50 |
March | 0.366338E+11 | 41090.52 | 26-MAR-01:51 | 4.00 | 0.82 | 0.194206E+11 | 15065.41 | 23-MAR-04:49 | 4.00 | 0.82 |
April | 0.363312E+11 | 42948.13 | 13-APR-02:59 | 6.00 | 2.20 | 0.187677E+11 | 13426.36 | 25-APR-22:49 | 2.17 | 1.68 |
May | 0.424471E+11 | 44294.64 | 12-MAY-00:23 | 4.50 | 2.57 | 0.193738E+11 | 13685.77 | 09-MAY-04:49 | 4.50 | 2.57 |
June | 0.458436E+11 | 35809.23 | 09-JUN-03:56 | 6.60 | 3.45 | 0.187634E+11 | 13062.27 | 09-JUN-03:49 | 6.60 | 3.45 |
July | 0.472247E+11 | 24751.67 | 17-JUL-21:20 | 28.00 | 13.33 | 0.193098E+11 | 11411.62 | 07-JUL-21:19 | 28.00 | 13.33 |
August | 0.464469E+11 | 24502.04 | 16-AUG-21:20 | 25.33 | 11.70 | 0.193912E+11 | 11426.44 | 23-AUG-04:00 | 11.00 | 8.67 |
September | 0.425984E+11 | 32933.51 | 21-SEP-19:27 | 0.00 | -0.4 | 0.187129E+11 | 11978.53 | 27-SEP-03:20 | 9.40 | 2.62 |
October | 0.377645E+11 | 40490.83 | 26-OCT-00:09 | 3.67 | 0.54 | 0.193203E+11 | 13919.11 | 02-OCT-01:00 | 3.67 | 0.54 |
November | 0.341111E+11 | 37342.31 | 09-NOV-01:37 | 7.00 | 3.66 | 0.186714E+11 | 13261.53 | 07-NOV-01:00 | 7.00 | 3.66 |
December | 0.327232E+11 | 46661.61 | 29-DEC-02:45 | 5.00 | 0.56 | 0.191631E+11 | 13155.16 | 05-DEC-02:00 | 5.00 | 0.56 |
Annual Sum or Average | 0.466764E+12 | 0.227574E+12 | ||||||||
Minimum of Months | 0.305569E+11 | 24502.04 | 0.00 | -0.4 | 0.173999E+11 | 11411.62 | 0.50 | 0.27 | ||
Maximum of Months | 0.472247E+11 | 46661.61 | 28.00 | 13.33 | 0.194206E+11 | 15065.41 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494354E+11 | 46759.66 | 29-JAN-18:40 | 3.00 | 3.00 | 0.188753E+11 | 11504.69 | 11-JAN-16:49 | 3.00 | 3.00 |
February | 0.445021E+11 | 45698.28 | 17-FEB-07:56 | 3.00 | -1.7 | 0.170415E+11 | 11596.45 | 13-FEB-18:49 | 3.00 | -1.7 |
March | 0.511681E+11 | 41487.66 | 09-MAR-07:15 | 4.33 | -0.9 | 0.188862E+11 | 11482.28 | 25-MAR-17:49 | 7.00 | 4.43 |
April | 0.497561E+11 | 42929.69 | 09-APR-06:06 | 4.33 | 1.86 | 0.182778E+11 | 11492.81 | 14-APR-15:09 | 3.00 | 0.27 |
May | 0.550623E+11 | 42975.00 | 03-MAY-07:42 | 5.67 | 0.72 | 0.188742E+11 | 11321.40 | 20-MAY-17:19 | 21.00 | 12.11 |
June | 0.570427E+11 | 31505.27 | 26-JUN-10:37 | 32.70 | 15.62 | 0.182664E+11 | 11321.46 | 03-JUN-17:19 | 32.70 | 15.62 |
July | 0.587235E+11 | 31722.55 | 23-JUL-10:50 | 29.83 | 15.95 | 0.188681E+11 | 11322.17 | 29-JUL-17:19 | 23.00 | 18.17 |
August | 0.585757E+11 | 31807.18 | 05-AUG-10:40 | 29.00 | 17.63 | 0.188754E+11 | 11323.35 | 12-AUG-17:19 | 20.67 | 10.67 |
September | 0.548696E+11 | 36396.18 | 21-SEP-17:41 | 0.50 | -0.0 | 0.182616E+11 | 11404.58 | 21-SEP-17:40 | 0.50 | -0.0 |
October | 0.518874E+11 | 42898.62 | 21-OCT-07:47 | 3.67 | 0.90 | 0.188736E+11 | 11539.23 | 02-OCT-15:50 | 3.67 | 0.90 |
November | 0.485112E+11 | 49537.99 | 12-NOV-16:41 | 4.17 | 2.72 | 0.182678E+11 | 11507.27 | 14-NOV-16:30 | 6.50 | 4.29 |
December | 0.479948E+11 | 44936.97 | 16-DEC-18:23 | 0.50 | -2.0 | 0.188583E+11 | 11595.04 | 30-DEC-18:49 | 1.00 | 0.07 |
Annual Sum or Average | 0.627529E+12 | 0.222226E+12 | ||||||||
Minimum of Months | 0.445021E+11 | 31505.27 | 0.50 | -2.0 | 0.170415E+11 | 11321.40 | 0.50 | -1.7 | ||
Maximum of Months | 0.587235E+11 | 49537.99 | 32.70 | 17.63 | 0.188862E+11 | 11596.45 | 32.70 | 18.17 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516149E+10 | 6681.88 | 19-JAN-03:37 | 3.67 | 2.25 | 0.131995E+10 | 862.98 | 20-JAN-22:30 | 7.50 | 1.84 |
February | 0.413532E+10 | 6558.34 | 27-FEB-06:09 | 3.83 | -0.9 | 0.119624E+10 | 869.58 | 27-FEB-22:49 | 2.00 | -0.8 |
March | 0.578401E+10 | 6895.82 | 01-MAR-10:53 | 2.00 | -0.8 | 0.137700E+10 | 958.60 | 15-MAR-21:30 | 12.50 | 3.03 |
April | 0.582044E+10 | 7053.91 | 09-APR-01:13 | 3.00 | 1.62 | 0.132398E+10 | 915.58 | 20-APR-21:30 | 14.00 | 7.96 |
May | 0.838380E+10 | 6972.94 | 12-MAY-00:23 | 4.50 | 2.57 | 0.150885E+10 | 977.77 | 17-MAY-21:30 | 17.50 | 8.72 |
June | 0.107877E+11 | 7151.34 | 26-JUN-14:10 | 37.98 | 15.29 | 0.162113E+10 | 1007.47 | 07-JUN-21:10 | 37.98 | 15.29 |
July | 0.111882E+11 | 7108.19 | 23-JUL-13:00 | 34.00 | 16.01 | 0.167439E+10 | 1007.41 | 14-JUL-23:49 | 34.00 | 16.01 |
August | 0.111107E+11 | 7416.02 | 16-AUG-15:01 | 36.17 | 16.19 | 0.167339E+10 | 1007.44 | 25-AUG-22:10 | 23.67 | 16.10 |
September | 0.966753E+10 | 7049.22 | 09-SEP-12:50 | 32.62 | 13.01 | 0.156569E+10 | 1007.41 | 08-SEP-21:00 | 32.62 | 13.01 |
October | 0.687917E+10 | 6905.79 | 02-OCT-05:10 | 3.00 | 3.00 | 0.143361E+10 | 966.46 | 10-OCT-21:30 | 13.50 | 4.21 |
November | 0.553271E+10 | 6917.73 | 13-NOV-19:13 | 1.67 | 1.08 | 0.130407E+10 | 893.30 | 09-NOV-22:30 | 1.67 | 1.08 |
December | 0.405724E+10 | 6594.80 | 04-DEC-00:20 | 4.33 | 1.34 | 0.130131E+10 | 840.24 | 05-DEC-02:00 | 4.00 | -2.2 |
Annual Sum or Average | 0.885083E+11 | 0.172996E+11 | ||||||||
Minimum of Months | 0.405724E+10 | 6558.34 | 1.67 | -0.9 | 0.119624E+10 | 840.24 | 1.67 | -2.2 | ||
Maximum of Months | 0.111882E+11 | 7416.02 | 37.98 | 16.19 | 0.167439E+10 | 1007.47 | 37.98 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17282349.39 | 8159.76 | 25-JAN-22:50 | 1.33 |
February | 13000326.25 | 1848.20 | 15-FEB-19:10 | -0.8 |
March | 29365325.56 | 2195.94 | 12-MAR-04:03 | 6.17 |
April | 23654028.72 | 3529.37 | 12-APR-00:40 | 4.33 |
May | 12557053.77 | 1891.92 | 05-MAY-05:17 | 6.00 |
June | 71512.93 | 1044.95 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 1285051.81 | 3366.87 | 23-SEP-05:29 | 7.20 |
October | 20820444.98 | 2965.98 | 11-OCT-23:42 | 7.00 |
November | 24339409.90 | 7266.41 | 07-NOV-05:47 | 5.00 |
December | 16257445.76 | 5314.32 | 15-DEC-23:27 | 1.00 |
Annual Sum or Average | 0.158633E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 29365325.56 | 8159.76 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175593E+09 | 1491.95 | 05-JAN-09:04 | -17.0 |
February | 0.345590E+09 | 1277.62 | 12-FEB-05:40 | -19.3 |
March | 0.217172E+09 | 1458.83 | 19-MAR-08:62 | -13.0 |
April | 0.176476E+09 | 1703.18 | 14-APR-07:27 | 1.50 |
May | 14626248.26 | 769.49 | 27-MAY-00:52 | 5.00 |
June | 128786.35 | 549.48 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 1684747.25 | 795.10 | 23-SEP-05:29 | 7.20 |
October | 0.225487E+09 | 1743.91 | 27-OCT-11:08 | 5.17 |
November | 0.171243E+09 | 1133.86 | 29-NOV-05:00 | -10.0 |
December | 0.521664E+09 | 1941.77 | 21-DEC-08:10 | -20.0 |
Annual Sum or Average | 0.184966E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.521664E+09 | 1941.77 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5518574.73 | 634.55 | 25-JAN-22:50 | 1.33 |
February | 3358869.04 | 331.15 | 07-FEB-16:58 | 5.00 |
March | 6512493.42 | 418.16 | 20-MAR-10:13 | 3.67 |
April | 5989974.42 | 326.26 | 12-APR-00:40 | 4.33 |
May | 1552306.35 | 237.33 | 01-MAY-05:04 | 6.00 |
June | 4565.38 | 76.09 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 183124.42 | 204.42 | 23-SEP-05:29 | 7.20 |
October | 4082088.35 | 277.10 | 25-OCT-08:23 | 5.50 |
November | 5224455.96 | 492.07 | 16-NOV-00:35 | 3.00 |
December | 6114738.23 | 334.99 | 25-DEC-16:43 | 3.50 |
Annual Sum or Average | 38541190.31 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 6512493.42 | 634.55 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45137374.43 | 435.34 | 05-JAN-14:00 | -16.0 |
February | 59726077.21 | 361.92 | 15-FEB-19:10 | -0.8 |
March | 16148941.15 | 371.44 | 23-MAR-04:53 | 4.00 |
April | 14176025.40 | 387.03 | 12-APR-00:40 | 4.33 |
May | 3370098.60 | 285.36 | 01-MAY-03:10 | 5.92 |
June | 12283.46 | 83.08 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 277487.28 | 243.44 | 23-SEP-05:29 | 7.20 |
October | 19972352.04 | 324.13 | 26-OCT-00:17 | 3.63 |
November | 26672564.58 | 434.92 | 23-NOV-14:25 | 4.00 |
December | 0.245149E+09 | 895.32 | 22-DEC-04:50 | -21.2 |
Annual Sum or Average | 0.430643E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.2 | |
Maximum of Months | 0.245149E+09 | 895.32 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78341803.52 | 510.51 | 05-JAN-18:00 | -18.0 |
February | 0.126957E+09 | 449.37 | 12-FEB-05:40 | -19.3 |
March | 34895793.28 | 294.93 | 19-MAR-08:04 | -13.0 |
April | 25751472.38 | 287.46 | 12-APR-00:40 | 4.33 |
May | 3083816.08 | 215.87 | 01-MAY-03:10 | 5.92 |
June | 17070.76 | 81.32 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 317950.28 | 193.19 | 23-SEP-05:29 | 7.20 |
October | 40181004.90 | 380.51 | 31-OCT-15:00 | -8.0 |
November | 60692077.55 | 365.53 | 30-NOV-04:50 | -13.2 |
December | 0.289780E+09 | 740.49 | 21-DEC-18:02 | -21.7 |
Annual Sum or Average | 0.660017E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.289780E+09 | 740.49 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2812428.10 | 3130.06 | 20-JAN-03:58 | 5.00 |
February | 1612837.23 | 3645.25 | 27-FEB-03:57 | 5.00 |
March | 2862539.44 | 2549.01 | 09-MAR-04:35 | 3.67 |
April | 4353675.56 | 6121.17 | 12-APR-00:40 | 4.33 |
May | 3951991.96 | 2981.24 | 20-MAY-04:39 | 6.33 |
June | 149748.74 | 2495.81 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 339273.57 | 2627.95 | 16-SEP-04:57 | 7.20 |
October | 10110094.18 | 3773.39 | 02-OCT-01:40 | 4.33 |
November | 5000245.99 | 4395.99 | 07-NOV-05:47 | 5.00 |
December | 4352831.92 | 3356.85 | 05-DEC-03:33 | 3.33 |
Annual Sum or Average | 35545666.69 | |||
Minimum of Months | 0.00 | 0.00 | 3.33 | |
Maximum of Months | 10110094.18 | 6121.17 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19228153.98 | 3303.12 | 25-JAN-22:50 | 1.33 |
February | 28123112.95 | 2316.83 | 07-FEB-14:25 | 7.50 |
March | 27532724.27 | 2676.82 | 20-MAR-10:13 | 3.67 |
April | 37470074.88 | 4096.08 | 12-APR-00:40 | 4.33 |
May | 8551868.52 | 2041.33 | 03-MAY-06:33 | 3.33 |
June | 23959.50 | 399.32 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 1548111.25 | 1974.71 | 22-SEP-08:42 | 4.03 |
October | 45532094.76 | 3303.27 | 27-OCT-11:08 | 5.17 |
November | 21509443.01 | 2661.97 | 18-NOV-02:35 | 4.67 |
December | 81008352.03 | 3330.90 | 21-DEC-09:15 | -20.0 |
Annual Sum or Average | 0.270528E+09 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 81008352.03 | 4096.08 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43130837.95 | 13868.68 | 25-JAN-22:50 | 1.33 |
February | 25873947.29 | 7454.40 | 15-FEB-19:10 | -0.8 |
March | 68271938.01 | 7768.79 | 20-MAR-10:13 | 3.67 |
April | 60952332.94 | 13603.13 | 12-APR-00:40 | 4.33 |
May | 14458355.36 | 5263.79 | 09-MAY-01:05 | 5.83 |
June | 61080.79 | 1018.01 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 2619078.16 | 4428.25 | 24-SEP-04:41 | 6.10 |
October | 48211259.62 | 5296.28 | 06-OCT-03:58 | 7.00 |
November | 57013594.87 | 13067.04 | 07-NOV-05:47 | 5.00 |
December | 55778320.05 | 7397.41 | 15-DEC-23:27 | 1.00 |
Annual Sum or Average | 0.376371E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 68271938.01 | 13868.68 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581100E+09 | 1897.42 | 05-JAN-09:13 | -17.0 |
February | 0.686426E+09 | 1916.49 | 07-FEB-16:01 | 5.83 |
March | 0.518380E+09 | 1968.90 | 16-MAR-18:03 | 13.50 |
April | 0.412273E+09 | 1883.65 | 20-APR-20:33 | 14.33 |
May | 34406425.93 | 1779.20 | 03-MAY-08:61 | 6.33 |
June | 1827424.36 | 1867.58 | 14-JUN-06:53 | 28.30 |
July | 1310463.69 | 1814.55 | 13-JUL-21:53 | 21.00 |
August | 1856384.82 | 1755.82 | 18-AUG-08:13 | 26.33 |
September | 13536741.67 | 1787.91 | 08-SEP-21:53 | 21.60 |
October | 0.359751E+09 | 1898.38 | 31-OCT-15:13 | -8.0 |
November | 0.491714E+09 | 1858.70 | 28-NOV-16:13 | -7.3 |
December | 0.101891E+10 | 1949.61 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.412149E+10 | |||
Minimum of Months | 1310463.69 | 1755.82 | -17.3 | |
Maximum of Months | 0.101891E+10 | 1968.90 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.948620E+09 | 1897.98 | 05-JAN-19:13 | -18.3 |
February | 0.958897E+09 | 1907.77 | 07-FEB-16:01 | 5.83 |
March | 0.631722E+09 | 1991.71 | 10-MAR-17:33 | 13.67 |
April | 0.456132E+09 | 1854.24 | 25-APR-08:61 | 1.17 |
May | 38455513.74 | 1779.78 | 03-MAY-08:61 | 6.33 |
June | 1656372.90 | 1756.24 | 12-JUN-21:53 | 18.80 |
July | 1272566.56 | 1776.64 | 07-JUL-08:33 | 26.33 |
August | 2015916.18 | 1751.81 | 17-AUG-21:53 | 19.00 |
September | 17692520.14 | 1921.80 | 09-SEP-08:53 | 27.70 |
October | 0.430706E+09 | 1918.72 | 21-OCT-16:53 | 12.00 |
November | 0.743400E+09 | 1866.06 | 28-NOV-16:13 | -7.3 |
December | 0.140619E+10 | 1948.74 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.563676E+10 | |||
Minimum of Months | 1272566.56 | 1751.81 | -18.3 | |
Maximum of Months | 0.140619E+10 | 1991.71 | 27.70 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6038486.86 | 196.91 | 06-JAN-04:30 | -10.0 |
February | 40320609.09 | 263.14 | 07-FEB-05:00 | -7.0 |
March | 19361590.85 | 133.69 | 22-MAR-04:00 | -2.0 |
April | 6448821.96 | 140.99 | 17-APR-04:00 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 16131616.00 | 205.52 | 31-OCT-24:00 | -5.8 |
November | 11055790.17 | 234.37 | 01-NOV-02:70 | -4.2 |
December | 49263794.48 | 390.80 | 21-DEC-05:40 | -18.7 |
Annual Sum or Average | 0.148621E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 49263794.48 | 390.80 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154255E+09 | 557.11 | 06-JAN-16:01 | 2.33 |
February | 0.169802E+09 | 553.92 | 12-FEB-16:01 | -6.2 |
March | 69244985.79 | 540.34 | 04-MAR-16:02 | -9.0 |
April | 32032712.92 | 544.75 | 09-APR-15:03 | 16.33 |
May | 1027868.29 | 499.22 | 27-MAY-16:13 | 14.33 |
June | 321293.29 | 417.89 | 16-JUN-08:04 | 15.78 |
July | 303889.38 | 490.25 | 07-JUL-08:34 | 26.33 |
August | 504317.73 | 421.87 | 10-AUG-08:53 | 22.00 |
September | 823261.69 | 525.92 | 25-SEP-08:03 | 14.18 |
October | 43211961.47 | 542.75 | 31-OCT-15:13 | -8.0 |
November | 0.101381E+09 | 552.76 | 29-NOV-16:01 | -9.3 |
December | 0.247562E+09 | 559.37 | 21-DEC-16:13 | -18.7 |
Annual Sum or Average | 0.820470E+09 | |||
Minimum of Months | 303889.38 | 417.89 | -18.7 | |
Maximum of Months | 0.247562E+09 | 559.37 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.615284E+09 | 1840.92 | 05-JAN-19:13 | -18.3 |
February | 0.723511E+09 | 1858.15 | 07-FEB-16:01 | 5.83 |
March | 0.511632E+09 | 1799.26 | 19-MAR-08:62 | -13.0 |
April | 0.403634E+09 | 1794.42 | 30-APR-15:01 | 5.00 |
May | 32107438.02 | 1430.33 | 09-MAY-20:33 | 13.67 |
June | 439934.86 | 1382.36 | 10-JUN-21:53 | 15.50 |
July | 433689.80 | 679.66 | 28-JUL-21:54 | 16.00 |
August | 238833.63 | 804.78 | 18-AUG-21:53 | 18.00 |
September | 11528057.36 | 1693.97 | 24-SEP-21:03 | 12.83 |
October | 0.363806E+09 | 1837.01 | 31-OCT-15:13 | -8.0 |
November | 0.523903E+09 | 1805.80 | 28-NOV-16:13 | -7.3 |
December | 0.103741E+10 | 1890.34 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.422392E+10 | |||
Minimum of Months | 238833.63 | 679.66 | -18.3 | |
Maximum of Months | 0.103741E+10 | 1890.34 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.981596E+09 | 1856.79 | 05-JAN-16:13 | -15.3 |
February | 0.985702E+09 | 1848.87 | 07-FEB-16:01 | 5.83 |
March | 0.613632E+09 | 1791.86 | 19-MAR-08:62 | -13.0 |
April | 0.449989E+09 | 1787.50 | 30-APR-15:01 | 5.00 |
May | 35630520.38 | 1414.45 | 03-MAY-15:03 | 16.17 |
June | 428973.03 | 1297.18 | 10-JUN-21:53 | 15.50 |
July | 422025.80 | 582.27 | 28-JUL-21:54 | 16.00 |
August | 348374.64 | 1032.97 | 18-AUG-21:53 | 18.00 |
September | 15241608.24 | 1666.39 | 22-SEP-08:62 | 2.57 |
October | 0.439815E+09 | 1828.75 | 31-OCT-15:13 | -8.0 |
November | 0.788904E+09 | 1832.04 | 29-NOV-16:01 | -9.3 |
December | 0.141422E+10 | 1895.44 | 21-DEC-16:13 | -18.7 |
Annual Sum or Average | 0.572593E+10 | |||
Minimum of Months | 348374.64 | 582.27 | -18.7 | |
Maximum of Months | 0.141422E+10 | 1895.44 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58280151.22 | 1280.66 | 08-JAN-18:59 | 6.00 |
February | 0.111012E+09 | 924.22 | 05-FEB-16:00 | -6.0 |
March | 33987628.60 | 853.57 | 26-MAR-06:50 | 4.67 |
April | 38127644.47 | 835.02 | 12-APR-00:40 | 4.33 |
May | 9394409.12 | 703.00 | 01-MAY-05:04 | 6.00 |
June | 27019.80 | 184.52 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 611902.90 | 522.95 | 23-SEP-05:29 | 7.20 |
October | 61520575.95 | 871.00 | 31-OCT-14:00 | -7.0 |
November | 54207073.15 | 923.40 | 23-NOV-14:25 | 4.00 |
December | 0.217593E+09 | 1421.15 | 21-DEC-09:30 | -20.0 |
Annual Sum or Average | 0.584762E+09 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.217593E+09 | 1421.15 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942808E+09 | 2265.15 | 05-JAN-09:13 | -17.0 |
February | 0.102869E+10 | 2253.03 | 07-FEB-16:01 | 5.83 |
March | 0.797183E+09 | 2193.78 | 19-MAR-08:15 | -13.0 |
April | 0.645966E+09 | 2207.12 | 30-APR-15:01 | 5.00 |
May | 74819828.11 | 2103.97 | 03-MAY-08:61 | 6.33 |
June | 2192962.59 | 1982.08 | 06-JUN-21:53 | 25.60 |
July | 1673262.62 | 2063.17 | 01-JUL-08:03 | 26.00 |
August | 2195584.93 | 1745.62 | 17-AUG-21:53 | 19.00 |
September | 31567829.88 | 2062.74 | 22-SEP-08:62 | 2.57 |
October | 0.584810E+09 | 2258.48 | 31-OCT-15:13 | -8.0 |
November | 0.791471E+09 | 2219.56 | 28-NOV-16:13 | -7.3 |
December | 0.148258E+10 | 2318.65 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.638596E+10 | |||
Minimum of Months | 1673262.62 | 1745.62 | -17.3 | |
Maximum of Months | 0.148258E+10 | 2318.65 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143379E+10 | 2266.45 | 05-JAN-19:13 | -18.3 |
February | 0.138669E+10 | 2241.72 | 05-FEB-16:13 | -6.3 |
March | 0.953402E+09 | 2185.97 | 19-MAR-08:15 | -13.0 |
April | 0.710487E+09 | 2195.79 | 30-APR-15:01 | 5.00 |
May | 82193827.64 | 2102.36 | 03-MAY-08:61 | 6.33 |
June | 2080352.15 | 1881.50 | 06-JUN-21:53 | 25.60 |
July | 1598124.16 | 1612.00 | 01-JUL-08:03 | 26.00 |
August | 2351869.71 | 1936.46 | 11-AUG-21:53 | 23.00 |
September | 40405533.56 | 2064.85 | 22-SEP-08:62 | 2.57 |
October | 0.715893E+09 | 2247.03 | 31-OCT-15:13 | -8.0 |
November | 0.114969E+10 | 2222.75 | 28-NOV-16:13 | -7.3 |
December | 0.197026E+10 | 2312.64 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.844884E+10 | |||
Minimum of Months | 1598124.16 | 1612.00 | -18.3 | |
Maximum of Months | 0.197026E+10 | 2312.64 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195984E+09 | 1157.15 | 05-JAN-09:13 | -17.0 |
February | 0.299723E+09 | 1168.67 | 07-FEB-16:01 | 5.83 |
March | 0.264077E+09 | 1140.07 | 19-MAR-15:13 | 0.00 |
April | 0.229531E+09 | 1137.65 | 30-APR-15:01 | 5.00 |
May | 21047152.37 | 1103.63 | 05-MAY-21:13 | 15.00 |
June | 975708.75 | 1052.12 | 12-JUN-08:03 | 26.97 |
July | 850160.38 | 1071.84 | 02-JUL-21:53 | 20.00 |
August | 813013.66 | 955.43 | 17-AUG-08:53 | 18.00 |
September | 6146168.68 | 1057.91 | 22-SEP-08:62 | 2.57 |
October | 0.189699E+09 | 1168.54 | 31-OCT-15:13 | -8.0 |
November | 0.188882E+09 | 1138.19 | 28-NOV-16:13 | -7.3 |
December | 0.402041E+09 | 1191.23 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.179977E+10 | |||
Minimum of Months | 813013.66 | 955.43 | -17.3 | |
Maximum of Months | 0.402041E+09 | 1191.23 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6716542.04 | 5620.67 | 25-JAN-22:50 | 1.33 |
February | 2476609.35 | 1330.04 | 10-FEB-10:32 | 2.00 |
March | 4238290.51 | 1786.23 | 26-MAR-06:50 | 4.67 |
April | 3240722.34 | 5275.64 | 12-APR-00:40 | 4.33 |
May | 1683629.58 | 2374.16 | 05-MAY-05:17 | 6.00 |
June | 19714.46 | 328.57 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 460388.39 | 1304.09 | 24-SEP-04:41 | 6.10 |
October | 5895745.51 | 2066.12 | 11-OCT-23:42 | 7.00 |
November | 10177346.85 | 4713.47 | 07-NOV-05:47 | 5.00 |
December | 6667248.76 | 2365.09 | 03-DEC-03:14 | 4.67 |
Annual Sum or Average | 41576237.78 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 10177346.85 | 5620.67 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3567958.48 | 5704.18 | 25-JAN-22:50 | 1.33 |
February | 1412934.84 | 1250.53 | 21-FEB-10:18 | 2.67 |
March | 2219688.09 | 1888.23 | 26-MAR-06:50 | 4.67 |
April | 2540146.28 | 5419.19 | 12-APR-00:40 | 4.33 |
May | 1513112.32 | 2569.66 | 05-MAY-05:17 | 6.00 |
June | 14290.13 | 238.17 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 366323.33 | 1259.28 | 24-SEP-04:41 | 6.10 |
October | 5197109.16 | 2073.66 | 11-OCT-23:42 | 7.00 |
November | 7451276.59 | 4927.47 | 07-NOV-05:47 | 5.00 |
December | 4030246.35 | 2350.83 | 03-DEC-03:14 | 4.67 |
Annual Sum or Average | 28313085.58 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 7451276.59 | 5704.18 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 419297.88 | 1263.57 | 24-JAN-02:33 | 3.67 |
February | 91999.32 | 1044.84 | 27-FEB-03:57 | 5.00 |
March | 341878.75 | 1053.30 | 09-MAR-01:43 | 4.83 |
April | 647492.26 | 3881.14 | 12-APR-00:40 | 4.33 |
May | 496095.20 | 1312.17 | 27-MAY-00:52 | 5.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 1315129.94 | 1284.50 | 11-OCT-23:42 | 7.00 |
November | 879723.98 | 2516.25 | 07-NOV-05:47 | 5.00 |
December | 852704.10 | 1818.78 | 29-DEC-03:36 | 5.00 |
Annual Sum or Average | 5044321.44 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 1315129.94 | 3881.14 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341353E+09 | 2650.39 | 05-JAN-09:04 | -17.0 |
February | 0.454512E+09 | 2479.94 | 12-FEB-05:40 | -19.3 |
March | 0.144262E+09 | 1784.83 | 26-MAR-06:50 | 4.67 |
April | 0.110033E+09 | 1917.47 | 12-APR-00:40 | 4.33 |
May | 22796541.71 | 1559.59 | 01-MAY-03:10 | 5.92 |
June | 129223.55 | 639.61 | 09-JUN-03:59 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 2424204.86 | 1445.58 | 23-SEP-05:29 | 7.20 |
October | 0.207721E+09 | 2122.33 | 27-OCT-11:08 | 5.17 |
November | 0.240827E+09 | 2024.00 | 30-NOV-07:10 | -11.3 |
December | 0.111913E+10 | 4025.44 | 21-DEC-08:02 | -20.0 |
Annual Sum or Average | 0.264319E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.111913E+10 | 4025.44 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160421E+11 | 15451.75 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.144845E+11 | 15451.75 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.160915E+11 | 15451.75 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.154982E+11 | 15451.75 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.160699E+11 | 15451.75 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.155692E+11 | 15451.75 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.159988E+11 | 15451.75 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.160977E+11 | 15451.75 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.155043E+11 | 15451.75 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.160359E+11 | 15451.75 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.155569E+11 | 15451.75 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.159988E+11 | 15451.75 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.188948E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.144845E+11 | 15451.75 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.160977E+11 | 15451.75 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743719E+09 | 716.35 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.671510E+09 | 716.35 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.746011E+09 | 716.35 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.718503E+09 | 716.35 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.745008E+09 | 716.35 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.721798E+09 | 716.35 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.741713E+09 | 716.35 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.746298E+09 | 716.35 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.718790E+09 | 716.35 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.743432E+09 | 716.35 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.721225E+09 | 716.35 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.741713E+09 | 716.35 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.875972E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.671510E+09 | 716.35 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.746298E+09 | 716.35 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861229E+09 | 829.54 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.777612E+09 | 829.54 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.863884E+09 | 829.54 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.832029E+09 | 829.54 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.862722E+09 | 829.54 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.835845E+09 | 829.54 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.858907E+09 | 829.54 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.864216E+09 | 829.54 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.832361E+09 | 829.54 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.860897E+09 | 829.54 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.835182E+09 | 829.54 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.858907E+09 | 829.54 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.101438E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.777612E+09 | 829.54 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.864216E+09 | 829.54 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693793E+09 | 668.27 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.626432E+09 | 668.27 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.695932E+09 | 668.27 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.670270E+09 | 668.27 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.694996E+09 | 668.27 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.673344E+09 | 668.27 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.691922E+09 | 668.27 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.696199E+09 | 668.27 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.670538E+09 | 668.27 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.693526E+09 | 668.27 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.672810E+09 | 668.27 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.691922E+09 | 668.27 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.817168E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.626432E+09 | 668.27 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.696199E+09 | 668.27 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351983E+09 | 339.04 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.317809E+09 | 339.04 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.353068E+09 | 339.04 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.340049E+09 | 339.04 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.352593E+09 | 339.04 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.341609E+09 | 339.04 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.351034E+09 | 339.04 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.353204E+09 | 339.04 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.340185E+09 | 339.04 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.351847E+09 | 339.04 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.341337E+09 | 339.04 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.351034E+09 | 339.04 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.414575E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.317809E+09 | 339.04 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.353204E+09 | 339.04 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.153747E+10 | 1957.67 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.134449E+10 | 1957.67 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.140748E+10 | 1957.67 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.127707E+10 | 1957.67 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.119768E+10 | 1957.67 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.109319E+10 | 1957.67 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.114938E+10 | 1957.67 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.126732E+10 | 1957.67 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.130816E+10 | 1957.67 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.148986E+10 | 1957.67 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.147121E+10 | 1957.67 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.155129E+10 | 1957.67 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.160946E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.109319E+10 | 1957.67 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.155129E+10 | 1957.67 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.850086E+10 | 8554.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.764693E+10 | 8554.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.843935E+10 | 8554.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.807735E+10 | 8554.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.828027E+10 | 8554.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.797848E+10 | 8554.32 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.821839E+10 | 8554.32 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.834211E+10 | 8554.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.809853E+10 | 8554.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.847180E+10 | 8554.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.823383E+10 | 8554.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.849222E+10 | 8554.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.987801E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.764693E+10 | 8554.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.850086E+10 | 8554.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146022E+09 | 132.12 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.131872E+09 | 132.12 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.144861E+09 | 132.12 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.141479E+09 | 132.12 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.145441E+09 | 132.12 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.140357E+09 | 132.12 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.146583E+09 | 132.12 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.144861E+09 | 132.12 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.141518E+09 | 132.12 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.146003E+09 | 132.12 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.140918E+09 | 132.12 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.146602E+09 | 132.12 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.171652E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.131872E+09 | 132.12 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.146602E+09 | 132.12 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.321963E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.283901E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.304429E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.283928E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.280885E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.263565E+10 | 3437.84 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.274248E+10 | 3437.84 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.288118E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.288334E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.312289E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.308031E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.321118E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.353081E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.263565E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.321963E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.321963E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.283901E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.304429E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.283928E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.280885E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.263565E+10 | 3437.84 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.274248E+10 | 3437.84 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.288118E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.288334E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.312289E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.308031E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.321118E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.353081E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.263565E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.321963E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126106E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121504E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125670E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148074E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.160421E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.160915E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.154982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.160699E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.155692E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.155043E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.160359E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.155569E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.188948E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.743719E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589616E+09 |
February | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562941E+09 |
March | 0.199990E+10 | 0.746011E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473858E+09 |
April | 0.192973E+10 | 0.718503E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415037E+09 |
May | 0.199475E+10 | 0.745008E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3159641.93 | 0.231726E+09 |
June | 0.193394E+10 | 0.721798E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47007480.78 | 79124093.76 |
July | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49954362.53 | 69662424.31 |
August | 0.199896E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39801898.65 | 85141637.34 |
September | 0.192879E+10 | 0.718790E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19533659.44 | 0.142535E+09 |
October | 0.199148E+10 | 0.743432E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 395805.73 | 0.418773E+09 |
November | 0.192552E+10 | 0.721225E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511941E+09 |
December | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646777E+09 |
Annual Sum or Average | 0.234744E+11 | 0.875972E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159853E+09 | 0.422713E+10 |
Minimum of Months | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69662424.31 |
Maximum of Months | 0.199990E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49954362.53 | 0.646777E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.861229E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238299E+09 |
February | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225024E+09 |
March | 0.231589E+10 | 0.863884E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.65 | 0.193154E+09 |
April | 0.223463E+10 | 0.832029E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172759E+09 |
May | 0.230993E+10 | 0.862722E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1338663.51 | 0.102936E+09 |
June | 0.223950E+10 | 0.835845E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18177595.79 | 36286743.09 |
July | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19304976.93 | 32530220.92 |
August | 0.231480E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15560997.88 | 38559527.10 |
September | 0.223354E+10 | 0.832361E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7706127.59 | 61603546.40 |
October | 0.230614E+10 | 0.860897E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175142.06 | 0.172316E+09 |
November | 0.222975E+10 | 0.835182E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207450E+09 |
December | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258948E+09 |
Annual Sum or Average | 0.271834E+11 | 0.101438E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62265172.41 | 0.173987E+10 |
Minimum of Months | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32530220.92 |
Maximum of Months | 0.231589E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19304976.93 | 0.258948E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.693793E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526373E+09 |
February | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500904E+09 |
March | 0.489771E+09 | 0.695932E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51779.42 | 0.426828E+09 |
April | 0.472586E+09 | 0.670270E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383058E+09 |
May | 0.488511E+09 | 0.694996E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3934727.71 | 0.231049E+09 |
June | 0.473617E+09 | 0.673344E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42830900.28 | 84766063.28 |
July | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45109988.82 | 76288975.91 |
August | 0.489542E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36914777.27 | 89935463.02 |
September | 0.472357E+09 | 0.670538E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19107096.69 | 0.140375E+09 |
October | 0.487709E+09 | 0.693526E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 672894.07 | 0.384837E+09 |
November | 0.471555E+09 | 0.672810E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458662E+09 |
December | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14194.30 | 0.580815E+09 |
Annual Sum or Average | 0.574883E+10 | 0.817168E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148636E+09 | 0.388389E+10 |
Minimum of Months | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76288975.91 |
Maximum of Months | 0.489771E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45109988.82 | 0.580815E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.351983E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299343E+09 |
February | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286039E+09 |
March | 0.376747E+09 | 0.353068E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49479.75 | 0.241867E+09 |
April | 0.363528E+09 | 0.340049E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 617.83 | 0.216200E+09 |
May | 0.375778E+09 | 0.352593E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2499152.25 | 0.127856E+09 |
June | 0.364321E+09 | 0.341609E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25305522.97 | 46890493.99 |
July | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26497877.64 | 42285092.57 |
August | 0.376571E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21987600.63 | 49436664.60 |
September | 0.363352E+09 | 0.340185E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11602687.44 | 77150410.48 |
October | 0.375161E+09 | 0.351847E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 446915.19 | 0.216330E+09 |
November | 0.362735E+09 | 0.341337E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.38 | 0.259760E+09 |
December | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8154.07 | 0.331692E+09 |
Annual Sum or Average | 0.442217E+10 | 0.414575E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88398132.16 | 0.219485E+10 |
Minimum of Months | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42285092.57 |
Maximum of Months | 0.376747E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26497877.64 | 0.331692E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791966E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752684E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 18861.80 | 0.647913E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584032E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3553196.37 | 0.338145E+09 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 58664484.57 | 0.111464E+09 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 62578490.90 | 99188411.61 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50506609.77 | 0.118128E+09 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 25684248.44 | 0.194485E+09 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 800413.07 | 0.569558E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690226E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869779E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.201806E+09 | 0.576757E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99188411.61 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 62578490.90 | 0.869779E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.153747E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137479E+10 |
February | 0.236489E+11 | 0.134449E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129974E+10 |
March | 0.262800E+11 | 0.140748E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110731E+10 |
April | 0.253579E+11 | 0.127707E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983060E+09 |
May | 0.262123E+11 | 0.119768E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6190449.89 | 0.586434E+09 |
June | 0.254132E+11 | 0.109319E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103107E+09 | 0.204438E+09 |
July | 0.261570E+11 | 0.114938E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109786E+09 | 0.183232E+09 |
August | 0.262677E+11 | 0.126732E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87369288.85 | 0.217837E+09 |
September | 0.253456E+11 | 0.130816E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43098908.09 | 0.350664E+09 |
October | 0.261693E+11 | 0.148986E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 876741.23 | 0.984001E+09 |
November | 0.253025E+11 | 0.147121E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119525E+10 |
December | 0.261570E+11 | 0.155129E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149369E+10 |
Annual Sum or Average | 0.308468E+12 | 0.160946E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350428E+09 | 0.998045E+10 |
Minimum of Months | 0.236489E+11 | 0.109319E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183232E+09 |
Maximum of Months | 0.262800E+11 | 0.155129E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109786E+09 | 0.149369E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.850086E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399013E+10 |
February | 0.702046E+11 | 0.764693E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376724E+10 |
March | 0.780153E+11 | 0.843935E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323237E+10 |
April | 0.752779E+11 | 0.807735E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289243E+10 |
May | 0.778146E+11 | 0.828027E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19233764.56 | 0.171942E+10 |
June | 0.754422E+11 | 0.797848E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295277E+09 | 0.595158E+09 |
July | 0.776503E+11 | 0.821839E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313313E+09 | 0.533925E+09 |
August | 0.779788E+11 | 0.834211E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250461E+09 | 0.633287E+09 |
September | 0.752414E+11 | 0.809853E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123525E+09 | 0.101765E+10 |
October | 0.776868E+11 | 0.847180E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2503678.75 | 0.286997E+10 |
November | 0.751137E+11 | 0.823383E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347337E+10 |
December | 0.776503E+11 | 0.849222E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433677E+10 |
Annual Sum or Average | 0.915726E+12 | 0.987801E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100431E+10 | 0.290617E+11 |
Minimum of Months | 0.702046E+11 | 0.764693E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533925E+09 |
Maximum of Months | 0.780153E+11 | 0.850086E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313313E+09 | 0.433677E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330998E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315950E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17291.25 | 0.265919E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236142E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979274.90 | 0.133945E+09 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35485305.26 | 40146460.51 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38134457.76 | 35344995.73 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30987559.36 | 42902541.39 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16043718.45 | 75823956.55 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 522879.61 | 0.233016E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285460E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364890E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124170E+09 | 0.236054E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35344995.73 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38134457.76 | 0.364890E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324034E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310480E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17994.01 | 0.262118E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233869E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3037024.96 | 0.132986E+09 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35475348.07 | 40243473.65 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38145391.70 | 35245671.07 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31082352.89 | 42288282.49 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16181613.60 | 73824024.79 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 554060.25 | 0.229101E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279984E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359550E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124494E+09 | 0.232373E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35245671.07 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38145391.70 | 0.359550E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.146022E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97615179.94 |
February | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91003832.15 |
March | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.75 | 75643877.16 |
April | 0.00 | 0.141479E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66600398.11 |
May | 0.00 | 0.145441E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 593017.57 | 40781780.86 |
June | 0.00 | 0.140357E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8380900.28 | 13697865.47 |
July | 0.00 | 0.146583E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8937858.37 | 12086539.54 |
August | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7252251.46 | 14526993.25 |
September | 0.00 | 0.141518E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3716641.37 | 23991460.68 |
October | 0.00 | 0.146003E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99046.18 | 68388535.57 |
November | 0.00 | 0.140918E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84047319.62 |
December | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104545E+09 |
Annual Sum or Average | 0.00 | 0.171652E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28981360.97 | 0.692929E+09 |
Minimum of Months | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12086539.54 |
Maximum of Months | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8937858.37 | 0.104545E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 866.12 | 90367084.24 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86505343.65 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47750.70 | 72542071.49 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.83 | 64902236.28 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1025331.79 | 35729669.15 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10169060.18 | 10385435.35 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10873309.62 | 8966838.37 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9013401.25 | 10734492.34 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4942820.71 | 19241881.48 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 246688.51 | 62969649.78 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12893.85 | 77851149.04 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17479.07 | 0.100465E+09 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36350140.63 | 0.640661E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8966838.37 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10873309.62 | 0.100465E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331307E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316510E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17636.97 | 0.265749E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236418E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2944870.44 | 0.133815E+09 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35251433.27 | 43102529.07 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37840820.35 | 37481486.48 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30792029.94 | 45204249.49 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15956574.96 | 75536795.85 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 523738.40 | 0.231928E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285448E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365025E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123327E+09 | 0.236753E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37481486.48 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37840820.35 | 0.365025E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323220E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310691E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18778.09 | 0.262436E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234751E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2950485.46 | 0.133160E+09 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35239985.73 | 43169600.19 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37839311.87 | 37430146.25 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30830132.71 | 44655973.04 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16021393.65 | 74076511.02 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 530114.42 | 0.228743E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278960E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23030.47 | 0.358731E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123453E+09 | 0.233002E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37430146.25 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37839311.87 | 0.358731E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404857E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386815E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5728.78 | 0.329181E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291367E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3123836.17 | 0.173766E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32705726.95 | 64752507.35 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34308357.38 | 58744245.66 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27640806.02 | 69474058.78 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13845933.14 | 0.109204E+09 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349493.09 | 0.298092E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352067E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3094.00 | 0.444750E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111983E+09 | 0.298307E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58744245.66 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34308357.38 | 0.444750E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330852E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316101E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15818.58 | 0.266523E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236744E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2901439.22 | 0.135380E+09 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35160250.48 | 40560097.64 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37788156.25 | 35648256.27 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30669376.88 | 43287768.98 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15850669.75 | 76472802.36 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 508736.27 | 0.233807E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285646E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364756E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122894E+09 | 0.236578E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35648256.27 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37788156.25 | 0.364756E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323599E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310469E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16302.01 | 0.262582E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234459E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2941668.10 | 0.134340E+09 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35141943.23 | 40665686.49 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37788623.18 | 35540377.11 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30754041.94 | 42621803.40 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15998761.11 | 74221077.75 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 540327.21 | 0.229426E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279850E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.48 | 0.359410E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123182E+09 | 0.232718E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35540377.11 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37788623.18 | 0.359410E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171665E+09 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163632E+09 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7702.26 | 0.137214E+09 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121423E+09 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1487707.63 | 67972442.72 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18047953.71 | 19733194.57 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19358029.48 | 17308264.67 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15692447.45 | 21265601.42 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8086091.93 | 38661929.62 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 258583.35 | 0.120090E+09 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148162E+09 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189810E+09 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62938515.82 | 0.121694E+10 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17308264.67 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19358029.48 | 0.189810E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.321963E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907614E+09 |
February | 0.415303E+11 | 0.283901E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862998E+09 |
March | 0.461508E+11 | 0.304429E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746244E+09 |
April | 0.445315E+11 | 0.283928E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674061E+09 |
May | 0.460320E+11 | 0.280885E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3540652.40 | 0.398706E+09 |
June | 0.446286E+11 | 0.263565E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63686238.99 | 0.137070E+09 |
July | 0.459349E+11 | 0.274248E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67757753.24 | 0.122935E+09 |
August | 0.461292E+11 | 0.288118E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54461562.83 | 0.145575E+09 |
September | 0.445099E+11 | 0.288334E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26830018.20 | 0.232582E+09 |
October | 0.459565E+11 | 0.312289E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 553591.16 | 0.658434E+09 |
November | 0.444343E+11 | 0.308031E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792724E+09 |
December | 0.459349E+11 | 0.321118E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993825E+09 |
Annual Sum or Average | 0.541708E+12 | 0.353081E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216830E+09 | 0.667277E+10 |
Minimum of Months | 0.415303E+11 | 0.263565E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122935E+09 |
Maximum of Months | 0.461508E+11 | 0.321963E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67757753.24 | 0.993825E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.321963E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912408E+09 |
February | 0.415303E+11 | 0.283901E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867569E+09 |
March | 0.461508E+11 | 0.304429E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749810E+09 |
April | 0.445315E+11 | 0.283928E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676834E+09 |
May | 0.460320E+11 | 0.280885E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3538253.02 | 0.399121E+09 |
June | 0.446286E+11 | 0.263565E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63685052.50 | 0.137077E+09 |
July | 0.459349E+11 | 0.274248E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67756466.55 | 0.122941E+09 |
August | 0.461292E+11 | 0.288118E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54456656.68 | 0.145584E+09 |
September | 0.445099E+11 | 0.288334E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26815670.07 | 0.232701E+09 |
October | 0.459565E+11 | 0.312289E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 525290.45 | 0.661058E+09 |
November | 0.444343E+11 | 0.308031E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796502E+09 |
December | 0.459349E+11 | 0.321118E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100018E+10 |
Annual Sum or Average | 0.541708E+12 | 0.353081E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216777E+09 | 0.670178E+10 |
Minimum of Months | 0.415303E+11 | 0.263565E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122941E+09 |
Maximum of Months | 0.461508E+11 | 0.321963E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67756466.55 | 0.100018E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824047E+09 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782552E+09 |
March | 0.410691E+10 | 0.126106E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676103E+09 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610658E+09 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3183850.80 | 0.358144E+09 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 57108343.06 | 0.122680E+09 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 60749137.16 | 0.110002E+09 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 48824519.31 | 0.130268E+09 |
September | 0.396089E+10 | 0.121504E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 24066874.77 | 0.208325E+09 |
October | 0.408962E+10 | 0.125670E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 468920.45 | 0.595655E+09 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719413E+09 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902873E+09 |
Annual Sum or Average | 0.482060E+11 | 0.148074E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.194402E+09 | 0.604072E+10 |
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110002E+09 |
Maximum of Months | 0.410691E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 60749137.16 | 0.902873E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715294E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685019E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582468E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518221E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3880143.21 | 0.307284E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56106954.51 | 0.112539E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59647219.80 | 0.100863E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47973549.66 | 0.119059E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23798360.22 | 0.185825E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467488.18 | 0.520244E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622954E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789318E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191874E+09 | 0.525909E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100863E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59647219.80 | 0.789318E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 15451.75 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 15451.75 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 15451.75 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 15451.75 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 15451.75 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 15451.75 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 15451.75 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 15451.75 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 15451.75 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 15451.75 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 15451.75 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 15451.75 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 716.35 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 439.30 | 05-JAN-19:00 |
February | 1169.53 | 01-FEB-00:10 | 716.35 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 458.73 | 12-FEB-05:00 |
March | 1169.53 | 01-MAR-00:10 | 716.35 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 400.59 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 716.35 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 311.40 | 17-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 716.35 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 | 17-MAY-13:00 | 229.12 | 03-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 716.35 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 26-JUN-15:00 | 158.12 | 09-JUN-03:40 |
July | 1169.53 | 01-JUL-00:10 | 716.35 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.77 | 16-JUL-13:00 | 130.78 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 716.35 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.11 | 16-AUG-16:00 | 119.36 | 12-AUG-23:00 |
September | 1169.53 | 01-SEP-00:10 | 716.35 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 | 09-SEP-13:00 | 238.74 | 22-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 716.35 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 | 11-OCT-14:00 | 334.21 | 30-OCT-06:20 |
November | 1169.53 | 01-NOV-00:10 | 716.35 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 392.12 | 29-NOV-21:00 |
December | 1169.53 | 01-DEC-00:10 | 716.35 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 494.24 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.36 | |||||
Maximum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 494.24 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 829.54 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 171.27 | 05-JAN-19:00 |
February | 1354.32 | 01-FEB-00:10 | 829.54 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 180.90 | 12-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 829.54 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 14-MAR-13:00 | 157.81 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 829.54 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 123.85 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 829.54 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 | 17-MAY-13:00 | 96.46 | 03-MAY-02:00 |
June | 1354.32 | 01-JUN-00:10 | 829.54 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.54 | 26-JUN-15:00 | 68.69 | 09-JUN-04:20 |
July | 1354.32 | 01-JUL-00:10 | 829.54 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.70 | 16-JUL-13:00 | 58.34 | 02-JUL-04:53 |
August | 1354.32 | 01-AUG-00:10 | 829.54 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 16-AUG-16:00 | 50.57 | 12-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 829.54 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 | 10-SEP-13:00 | 101.07 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 829.54 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 11-OCT-14:00 | 133.42 | 30-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 829.54 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 157.57 | 29-NOV-21:00 |
December | 1354.32 | 01-DEC-00:10 | 829.54 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 191.59 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.57 | |||||
Maximum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 54.54 | 191.59 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 668.27 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 400.73 | 05-JAN-19:00 |
February | 286.42 | 01-FEB-00:10 | 668.27 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 418.45 | 12-FEB-05:00 |
March | 286.42 | 01-MAR-00:10 | 668.27 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.79 | 14-MAR-13:00 | 365.43 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 668.27 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 284.05 | 17-APR-03:00 |
May | 286.42 | 01-MAY-00:10 | 668.27 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 17-MAY-13:00 | 216.20 | 03-MAY-02:00 |
June | 286.42 | 01-JUN-00:10 | 668.27 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 26-JUN-15:00 | 159.57 | 09-JUN-04:50 |
July | 286.42 | 01-JUL-00:10 | 668.27 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.18 | 16-JUL-13:00 | 137.09 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 668.27 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.57 | 16-AUG-14:00 | 119.50 | 12-AUG-23:00 |
September | 286.42 | 01-SEP-00:10 | 668.27 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.90 | 09-SEP-13:00 | 233.15 | 22-SEP-05:40 |
October | 286.42 | 01-OCT-23:10 | 668.27 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.18 | 11-OCT-14:00 | 304.84 | 30-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 668.27 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 357.73 | 29-NOV-21:00 |
December | 286.42 | 01-DEC-00:10 | 668.27 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 | 01-DEC-14:00 | 452.77 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.50 | |||||
Maximum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 452.77 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 339.04 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 231.20 | 05-JAN-19:00 |
February | 220.32 | 01-FEB-00:10 | 339.04 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 241.43 | 12-FEB-05:00 |
March | 220.32 | 01-MAR-00:10 | 339.04 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 14-MAR-13:00 | 210.83 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 339.04 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 19-APR-13:00 | 163.88 | 17-APR-03:00 |
May | 220.32 | 01-MAY-00:10 | 339.04 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 | 17-MAY-13:00 | 121.96 | 03-MAY-02:00 |
June | 220.32 | 01-JUN-00:10 | 339.04 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 | 26-JUN-15:00 | 89.82 | 09-JUN-04:50 |
July | 220.32 | 01-JUL-00:10 | 339.04 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.57 | 16-JUL-13:00 | 77.19 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 339.04 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.21 | 16-AUG-14:00 | 66.78 | 12-AUG-23:00 |
September | 220.32 | 01-SEP-00:10 | 339.04 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 | 09-SEP-13:00 | 130.78 | 22-SEP-05:30 |
October | 220.32 | 01-OCT-23:10 | 339.04 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 11-OCT-14:00 | 175.88 | 30-OCT-06:40 |
November | 220.32 | 01-NOV-00:10 | 339.04 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 06-NOV-13:00 | 206.39 | 29-NOV-21:00 |
December | 220.32 | 01-DEC-00:10 | 339.04 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 01-DEC-14:00 | 260.73 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 | |||||
Maximum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 | 260.73 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 588.21 | 05-JAN-19:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 613.00 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 9.92 | 14-MAR-13:00 | 539.84 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 427.93 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 58.89 | 17-MAY-13:00 | 336.91 | 02-MAY-23:03 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 176.15 | 26-JUN-15:20 | 232.59 | 09-JUN-03:40 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 155.36 | 16-JUL-13:00 | 183.69 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 154.14 | 16-AUG-16:00 | 163.22 | 12-AUG-24:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 108.64 | 10-SEP-13:00 | 379.93 | 21-SEP-19:35 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 45.71 | 11-OCT-14:00 | 456.51 | 30-OCT-07:20 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 529.16 | 29-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 644.55 | 23-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 163.22 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 176.15 | 644.55 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1957.67 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 971.05 | 05-JAN-19:00 |
February | 15368.40 | 01-FEB-00:10 | 1957.67 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1014.10 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1957.67 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 885.67 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1957.67 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 705.05 | 17-APR-03:00 |
May | 15368.40 | 01-MAY-00:10 | 1957.67 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.51 | 17-MAY-13:00 | 552.85 | 03-MAY-02:00 |
June | 15368.40 | 01-JUN-00:10 | 1957.67 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.38 | 26-JUN-15:00 | 406.66 | 09-JUN-03:40 |
July | 15368.40 | 01-JUL-00:10 | 1957.67 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.00 | 16-JUL-13:00 | 325.61 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1957.67 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.55 | 16-AUG-16:00 | 289.57 | 12-AUG-24:00 |
September | 15368.40 | 01-SEP-00:10 | 1957.67 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.53 | 10-SEP-13:00 | 574.13 | 22-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1957.67 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 | 11-OCT-14:00 | 756.22 | 30-OCT-04:50 |
November | 15368.40 | 01-NOV-00:10 | 1957.67 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 875.03 | 29-NOV-21:10 |
December | 15368.40 | 01-DEC-00:10 | 1957.67 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1097.22 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.57 | |||||
Maximum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 312.38 | 1097.22 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 8554.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2828.65 | 05-JAN-19:10 |
February | 45622.98 | 01-FEB-00:10 | 8554.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2999.27 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 8554.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2624.29 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 8554.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2091.50 | 17-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 8554.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.77 | 17-MAY-13:00 | 1630.46 | 03-MAY-02:00 |
June | 45622.98 | 01-JUN-00:10 | 8554.32 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 892.49 | 26-JUN-15:00 | 1137.37 | 09-JUN-03:40 |
July | 45622.98 | 01-JUL-00:10 | 8554.32 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 765.78 | 16-JUL-13:00 | 956.32 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 8554.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 758.65 | 16-AUG-16:00 | 827.48 | 12-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 8554.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.80 | 10-SEP-13:00 | 1705.28 | 22-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 8554.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.34 | 11-OCT-14:00 | 2245.93 | 30-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 8554.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2606.64 | 29-NOV-21:00 |
December | 45622.98 | 01-DEC-00:10 | 8554.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3193.01 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.48 | |||||
Maximum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 892.49 | 3193.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.54 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.24 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:10 | 233.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.68 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.90 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:10 | 86.23 | 09-JUN-04:45 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.46 | 16-JUL-15:07 | 71.21 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.98 | 16-AUG-16:00 | 67.09 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:10 | 194.91 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.57 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 289.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.09 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.52 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.22 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:06 | 233.46 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.67 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.89 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:10 | 86.23 | 09-JUN-04:45 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.45 | 16-JUL-15:07 | 71.21 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 16-AUG-16:00 | 65.35 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.48 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:07 | 194.89 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.55 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 289.06 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.35 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 132.12 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 67.46 | 05-JAN-19:00 |
February | 0.00 | 01-FEB-00:10 | 132.12 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 71.60 | 12-FEB-05:00 |
March | 0.00 | 01-MAR-00:10 | 132.12 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 14-MAR-13:00 | 61.20 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 132.12 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 46.83 | 17-APR-03:00 |
May | 0.00 | 01-MAY-00:10 | 132.12 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 17-MAY-13:00 | 36.00 | 03-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 132.12 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 | 26-JUN-15:00 | 26.84 | 09-JUN-03:51 |
July | 0.00 | 01-JUL-00:10 | 132.12 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 16-JUL-13:00 | 22.93 | 02-JUL-04:53 |
August | 0.00 | 01-AUG-00:10 | 132.12 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 16-AUG-16:00 | 20.20 | 12-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 132.12 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 10-SEP-13:00 | 39.99 | 21-SEP-22:00 |
October | 0.00 | 01-OCT-00:10 | 132.12 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 11-OCT-14:00 | 51.35 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 132.12 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 60.92 | 29-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 132.12 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 76.60 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | |||||
Maximum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 | 76.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 20-JAN-14:00 | 70.76 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 74.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 14-MAR-13:00 | 65.16 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 19-APR-13:00 | 50.71 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 31-MAY-15:08 | 37.37 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 | 26-JUN-15:07 | 24.07 | 09-JUN-04:50 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 16-JUL-15:07 | 19.87 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 16-AUG-16:00 | 16.58 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 10-SEP-16:00 | 38.93 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 11-OCT-14:00 | 54.40 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 07-NOV-15:00 | 63.79 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 01-DEC-14:00 | 80.68 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 | 80.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.54 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.24 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:06 | 233.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.68 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.95 | 31-MAY-15:10 | 133.90 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:09 | 86.24 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.46 | 16-JUL-15:07 | 71.21 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.98 | 16-AUG-16:00 | 65.13 | 12-AUG-08:30 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:07 | 194.91 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.57 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 289.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.13 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.51 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.22 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:09 | 233.45 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.67 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.89 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:07 | 86.23 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.45 | 16-JUL-15:07 | 71.21 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 16-AUG-16:00 | 64.06 | 12-AUG-08:30 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.48 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:10 | 194.89 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.56 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 01-DEC-14:00 | 289.06 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.06 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.06 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 308.64 | 05-JAN-19:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 322.28 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 | 14-MAR-13:00 | 281.47 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 218.87 | 17-APR-03:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.29 | 17-MAY-13:00 | 163.90 | 03-MAY-02:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 | 26-JUN-15:00 | 122.70 | 09-JUN-04:50 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.49 | 16-JUL-13:00 | 104.37 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.02 | 16-AUG-16:00 | 91.57 | 12-AUG-23:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 10-SEP-13:00 | 180.02 | 22-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.52 | 11-OCT-14:00 | 234.86 | 30-OCT-06:30 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 275.56 | 29-NOV-21:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 01-DEC-14:00 | 348.69 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 | 348.69 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.98 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.69 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 13-MAR-15:10 | 233.90 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.09 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 31-MAY-15:10 | 134.29 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.38 | 26-JUN-15:10 | 86.60 | 09-JUN-04:45 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 16-JUL-15:09 | 71.58 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.68 | 16-AUG-16:00 | 69.70 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 10-SEP-16:00 | 139.88 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 11-OCT-15:10 | 195.32 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 229.00 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 289.54 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.38 | 289.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.95 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.66 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 13-MAR-15:07 | 233.89 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.08 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 31-MAY-15:10 | 134.28 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 26-JUN-15:10 | 86.60 | 09-JUN-04:45 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 16-JUL-15:07 | 71.57 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 16-AUG-16:00 | 67.85 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 10-SEP-16:00 | 139.88 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 11-OCT-15:07 | 195.31 | 30-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.98 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 01-DEC-12:40 | 289.52 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.85 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 289.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 129.95 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 136.95 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 13-MAR-15:10 | 119.67 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 93.17 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 | 31-MAY-15:08 | 68.71 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 26-JUN-15:10 | 44.31 | 09-JUN-04:50 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 16-JUL-15:07 | 36.62 | 02-JUL-04:55 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 | 16-AUG-16:00 | 32.99 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 10-SEP-16:00 | 71.57 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 11-OCT-15:10 | 99.93 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 117.17 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 148.14 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.99 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 148.14 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 664.18 | 05-JAN-19:10 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 695.01 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 615.87 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 488.50 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.65 | 17-MAY-13:00 | 378.52 | 02-MAY-23:03 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 26-JUN-15:00 | 269.58 | 09-JUN-03:40 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.87 | 16-JUL-13:00 | 216.08 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.96 | 16-AUG-16:00 | 187.19 | 23-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.42 | 10-SEP-13:00 | 384.57 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.21 | 11-OCT-14:00 | 520.98 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 603.68 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 745.59 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.19 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 745.59 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 665.06 | 05-JAN-19:08 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 699.12 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 615.87 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 488.50 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.65 | 17-MAY-13:00 | 380.34 | 02-MAY-23:03 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 26-JUN-15:00 | 270.25 | 09-JUN-03:40 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.87 | 16-JUL-13:00 | 216.08 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.96 | 16-AUG-16:00 | 187.20 | 23-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.42 | 10-SEP-13:00 | 384.57 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.89 | 11-OCT-14:00 | 520.99 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 603.69 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 749.79 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.20 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 749.79 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 600.48 | 05-JAN-19:00 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 626.00 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 551.25 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 437.25 | 17-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 58.91 | 17-MAY-13:00 | 357.40 | 02-MAY-07:17 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 178.26 | 26-JUN-15:00 | 258.98 | 09-JUN-03:40 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 152.21 | 16-JUL-13:00 | 193.43 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 151.41 | 16-AUG-16:00 | 167.97 | 23-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 102.57 | 10-SEP-13:00 | 373.60 | 21-SEP-17:35 |
October | 2401.70 | 01-OCT-23:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 34.95 | 11-OCT-14:00 | 466.42 | 30-OCT-07:07 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 540.33 | 29-NOV-21:00 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 660.62 | 23-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 167.97 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 178.26 | 660.62 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 547.04 | 05-JAN-19:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 571.18 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 498.94 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 388.13 | 17-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 | 17-MAY-13:00 | 285.89 | 03-MAY-02:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.34 | 26-JUN-15:00 | 210.28 | 09-JUN-04:50 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.83 | 16-JUL-13:00 | 177.89 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.00 | 16-AUG-16:00 | 158.39 | 12-AUG-23:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.24 | 10-SEP-13:00 | 302.83 | 22-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.06 | 11-OCT-14:00 | 416.45 | 30-OCT-06:50 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 488.46 | 29-NOV-21:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 617.94 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.39 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.34 | 617.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 48903.96 | 13-JAN-15:45 | 7667.93 | 8584.44 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51273.97 | 24-FEB-08:23 | 15335.86 | 20602.53 | 15209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52822.33 | 26-MAR-01:32 | 53675.50 | 20601.92 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44946.80 | 11-APR-23:00 | 115018.92 | 51505.82 | 40558.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55517.08 | 12-MAY-00:23 | 34505.68 | 7725.87 | 7604.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21235.85 | 09-JUN-03:56 | 115018.92 | 17169.29 | 20279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18640.58 | 28-JUL-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21309.85 | 18-AUG-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38636.96 | 21-SEP-19:40 | 17891.83 | 30903.49 | 19265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44919.04 | 26-OCT-00:09 | 115018.92 | 25752.91 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48521.11 | 09-NOV-01:37 | 80513.24 | 18027.04 | 17744.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49033.24 | 17-DEC-06:11 | 89459.16 | 51505.82 | 40558.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18640.58 | 7667.93 | 7725.87 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55517.08 | 115018.92 | 51505.82 | 40558.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7665.35 | 15-JAN-12:48 | 3898.44 | 2387.85 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.09 |
February | 6851.10 | 13-FEB-14:41 | 1819.27 | 1392.91 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.80 |
March | 5397.18 | 05-MAR-13:36 | 2598.96 | 1591.90 | 2165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.28 |
April | 3502.07 | 07-APR-12:30 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.99 |
May | 3024.55 | 11-MAY-23:53 | 11695.32 | 1591.90 | 2165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.02 |
June | 3197.55 | 26-JUN-12:40 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 0.00 |
July | 3453.00 | 23-JUL-12:00 | 389.84 | 238.78 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 75.42 | 0.00 |
August | 4217.65 | 31-AUG-12:40 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 0.00 |
September | 5154.40 | 28-SEP-12:50 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 | 0.00 |
October | 5202.24 | 10-OCT-12:30 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
November | 7122.84 | 23-NOV-13:30 | 2598.96 | 1591.90 | 2165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.00 |
December | 7573.64 | 18-DEC-13:32 | 1559.38 | 1193.92 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3024.55 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7665.35 | 11695.32 | 2387.85 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 223.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3261.47 | 25-JAN-22:33 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.52 |
February | 3281.19 | 27-FEB-22:10 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.83 |
March | 3753.16 | 08-MAR-04:03 | 5417.28 | 368.68 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.07 |
April | 5299.02 | 09-APR-01:13 | 10533.60 | 1843.42 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.51 |
May | 4959.78 | 12-MAY-00:23 | 4062.96 | 414.77 | 626.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.09 |
June | 2318.84 | 26-JUN-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 0.00 |
July | 2221.82 | 17-JUL-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 0.00 |
August | 2307.78 | 16-AUG-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 0.00 |
September | 2793.22 | 21-SEP-19:54 | 10533.60 | 8295.41 | 7939.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.96 |
October | 3110.01 | 16-OCT-21:40 | 4062.96 | 1659.08 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.77 |
November | 5155.00 | 13-NOV-19:13 | 3160.08 | 2212.11 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.84 |
December | 3005.24 | 15-DEC-21:53 | 10834.56 | 6636.33 | 6769.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2221.82 | 1203.84 | 368.68 | 626.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5299.02 | 13543.20 | 8295.41 | 7939.31 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 96.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1529.30 | 19-JAN-03:37 | 2864.16 | 742.52 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.97 |
February | 1526.44 | 27-FEB-06:09 | 1782.14 | 2376.05 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.34 |
March | 1537.68 | 01-MAR-10:53 | 190.94 | 556.89 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.71 |
April | 1628.94 | 09-APR-01:13 | 2227.68 | 1485.03 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.05 |
May | 1625.92 | 12-MAY-00:23 | 859.25 | 334.13 | 662.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.72 |
June | 1864.09 | 26-JUN-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 | 0.00 |
July | 1860.06 | 17-JUL-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 51.72 | 0.00 |
August | 1734.03 | 16-AUG-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 0.00 |
September | 1562.93 | 12-SEP-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
October | 1611.08 | 02-OCT-05:10 | 891.07 | 1188.03 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.47 |
November | 1598.71 | 13-NOV-19:13 | 668.30 | 1782.04 | 2385.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.25 |
December | 1514.59 | 04-DEC-00:20 | 2864.16 | 1485.03 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1514.59 | 190.94 | 334.13 | 662.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1864.09 | 2864.16 | 2376.05 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 | 192.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1002.56 | 19-JAN-03:37 | 2203.20 | 376.74 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.62 |
February | 990.82 | 27-FEB-06:09 | 1370.88 | 1205.45 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.16 |
March | 998.46 | 01-MAR-10:53 | 146.88 | 282.52 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.04 |
April | 1056.45 | 09-APR-01:13 | 1713.60 | 753.41 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.81 |
May | 1052.43 | 12-MAY-00:23 | 660.96 | 169.52 | 191.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.24 |
June | 1002.16 | 26-JUN-18:30 | 171.36 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 61.29 | 0.00 |
July | 952.01 | 17-JUL-19:10 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 0.00 |
August | 852.45 | 16-AUG-20:00 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 |
September | 925.14 | 16-SEP-02:46 | 1101.60 | 188.37 | 254.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 |
October | 1043.13 | 02-OCT-05:10 | 685.44 | 602.73 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.24 |
November | 1029.46 | 13-NOV-19:13 | 514.08 | 904.09 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.51 |
December | 984.70 | 04-DEC-00:20 | 2203.20 | 753.41 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 852.45 | 146.88 | 169.52 | 191.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1056.45 | 2203.20 | 1205.45 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 61.29 | 107.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56231.70 | 09-JAN-07:10 | 4032.00 | 2520.03 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 242.39 |
February | 61205.43 | 28-FEB-19:10 | 7056.00 | 4032.04 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 279.86 |
March | 54952.26 | 05-MAR-20:47 | 4233.60 | 2822.43 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 323.27 |
April | 55150.37 | 22-APR-20:46 | 4939.20 | 2469.63 | 26955.46 | 234177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 303.00 |
May | 49107.03 | 02-MAY-21:45 | 9072.00 | 3024.03 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 289.54 |
June | 39416.17 | 26-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 101.24 | 0.00 |
July | 39376.50 | 17-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 70.62 | 0.00 |
August | 39319.15 | 16-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 58.83 | 0.00 |
September | 52936.02 | 21-SEP-19:27 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 337.02 |
October | 52166.12 | 02-OCT-20:14 | 5644.80 | 2822.43 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 281.63 |
November | 58140.78 | 02-NOV-19:49 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 309.50 |
December | 53045.69 | 12-DEC-20:28 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 331.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39319.15 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61205.43 | 9072.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 101.24 | 337.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31424.37 | 15-JAN-12:48 | 51228.00 | 1435.63 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.24 |
February | 26611.86 | 13-FEB-14:41 | 23906.40 | 837.45 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.68 |
March | 29423.22 | 26-MAR-01:32 | 71719.20 | 2610.23 | 1828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.91 |
April | 20368.91 | 17-APR-21:57 | 61473.60 | 5220.46 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.18 |
May | 17205.37 | 09-MAY-04:41 | 107578.80 | 3045.27 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.86 |
June | 13672.96 | 09-JUN-04:00 | 153684.00 | 2175.19 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.65 |
July | 12162.01 | 23-JUL-12:00 | 5122.80 | 143.56 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 166.74 | 0.00 |
August | 14261.16 | 26-AUG-12:40 | 5122.80 | 119.64 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 159.65 | 0.00 |
September | 16788.64 | 28-SEP-12:50 | 3415.20 | 119.64 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 | 0.00 |
October | 25904.04 | 26-OCT-03:31 | 107578.80 | 1522.63 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.58 |
November | 30379.20 | 11-NOV-09:10 | 85380.00 | 1435.63 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.44 |
December | 27235.18 | 18-DEC-10:13 | 34152.00 | 1196.36 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12162.01 | 3415.20 | 119.64 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31424.37 | 153684.00 | 5220.46 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 166.74 | 493.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 81717.39 | 08-JAN-08:35 | 50692.20 | 6539.30 | 10557.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.05 |
February | 90146.65 | 24-FEB-08:23 | 60830.64 | 9808.95 | 15835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.51 |
March | 67667.83 | 03-MAR-21:27 | 121661.28 | 22811.52 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.66 |
April | 70313.08 | 30-APR-07:35 | 50692.20 | 6894.15 | 10557.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.15 |
May | 74298.66 | 19-MAY-07:07 | 60830.64 | 10075.09 | 15835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.99 |
June | 63775.88 | 09-JUN-04:00 | 456229.80 | 9504.80 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1122.37 |
July | 42024.02 | 17-JUL-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 269.87 | 0.00 |
August | 42321.90 | 16-AUG-20:10 | 40553.76 | 7603.84 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 268.91 | 0.00 |
September | 62307.31 | 21-SEP-19:08 | 354845.40 | 85543.20 | 100292.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1586.74 |
October | 88781.85 | 09-OCT-04:25 | 70969.08 | 3801.92 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.51 |
November | 87169.83 | 18-NOV-17:27 | 101384.40 | 9504.80 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.68 |
December | 66508.39 | 30-DEC-18:45 | 60830.64 | 11405.76 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1411.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 42024.02 | 40553.76 | 3801.92 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 90146.65 | 456229.80 | 85543.20 | 100292.09 | 0.00 | 0.00 | 0.00 | 0.00 | 269.87 | 1586.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5079.48 | 20-JAN-17:11 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.18 |
February | 4938.39 | 26-FEB-17:51 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.25 |
March | 5573.07 | 08-MAR-17:11 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.05 |
April | 5581.85 | 08-APR-18:01 | 1170.00 | 2102.25 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 |
May | 5513.08 | 27-MAY-16:11 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.27 |
June | 5266.25 | 06-JUN-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 0.00 |
July | 5303.65 | 01-JUL-21:51 | 1386.00 | 1786.91 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 |
August | 5564.99 | 13-AUG-21:51 | 1386.00 | 1786.91 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 |
September | 5426.32 | 15-SEP-19:51 | 1386.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 |
October | 5586.82 | 14-OCT-16:11 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 |
November | 4954.38 | 07-NOV-17:41 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.31 |
December | 4682.80 | 02-DEC-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4682.80 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5586.82 | 1800.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 70.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4577.35 | 23-JAN-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.16 |
February | 4597.20 | 24-FEB-16:01 | 777.60 | 470.85 | 400.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.68 |
March | 5304.55 | 15-MAR-18:31 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.79 |
April | 5400.40 | 08-APR-18:01 | 1170.00 | 2102.00 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.74 |
May | 5335.21 | 27-MAY-16:11 | 954.00 | 693.66 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.22 |
June | 5167.45 | 27-JUN-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
July | 5204.33 | 01-JUL-08:61 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 0.00 |
August | 5372.80 | 13-AUG-21:51 | 1386.00 | 1786.70 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.59 |
September | 5130.70 | 15-SEP-19:51 | 1386.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.30 |
October | 5236.65 | 14-OCT-16:11 | 954.00 | 693.66 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.70 |
November | 4627.49 | 07-NOV-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
December | 4510.31 | 02-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4510.31 | 360.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5400.40 | 1386.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 83.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 938.96 | 20-JAN-12:40 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
February | 895.54 | 18-FEB-13:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
March | 824.93 | 14-MAR-12:40 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
April | 502.97 | 08-APR-13:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.64 |
May | 399.37 | 16-MAY-13:20 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.12 | 0.00 |
June | 504.82 | 14-JUN-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 0.00 |
July | 541.23 | 23-JUL-13:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 | 0.00 |
August | 677.65 | 31-AUG-12:40 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 0.00 |
September | 859.70 | 28-SEP-13:00 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 0.00 |
October | 885.86 | 10-OCT-12:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
November | 939.55 | 07-NOV-12:10 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
December | 839.49 | 17-DEC-13:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 399.37 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 939.55 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 11.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1283.40 | 21-JAN-09:01 | 378.00 | 518.04 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 |
February | 1275.09 | 19-FEB-09:01 | 378.00 | 518.04 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 |
March | 1425.32 | 14-MAR-20:51 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 |
April | 1448.59 | 20-APR-20:31 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
May | 1491.23 | 17-MAY-21:51 | 1620.00 | 796.89 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
June | 1523.21 | 06-JUN-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 0.00 |
July | 1552.36 | 01-JUL-08:61 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 0.00 |
August | 1550.23 | 01-AUG-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 |
September | 1522.85 | 09-SEP-21:51 | 1386.00 | 1123.31 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 |
October | 1415.13 | 10-OCT-20:31 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 |
November | 1296.43 | 09-NOV-09:51 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 |
December | 1047.24 | 02-DEC-09:01 | 378.00 | 518.04 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1047.24 | 360.00 | 518.04 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1552.36 | 1800.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 26.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4275.07 | 01-JAN-09:01 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.84 |
February | 4247.09 | 18-FEB-09:01 | 378.00 | 824.08 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 |
March | 4547.67 | 15-MAR-18:31 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.24 |
April | 5008.21 | 19-APR-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.14 |
May | 5053.43 | 17-MAY-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
June | 5108.73 | 07-JUN-08:41 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
July | 5212.77 | 01-JUL-07:42 | 572.40 | 706.35 | 1422.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 |
August | 5095.65 | 19-AUG-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
September | 5086.35 | 18-SEP-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 |
October | 5029.17 | 11-OCT-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 |
November | 4878.27 | 09-NOV-09:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.05 |
December | 4169.90 | 17-DEC-09:01 | 378.00 | 824.08 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4169.90 | 360.00 | 706.35 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5212.77 | 1386.00 | 1871.00 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 112.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3941.47 | 22-JAN-09:01 | 378.00 | 823.98 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.30 |
February | 4099.57 | 27-FEB-09:01 | 252.00 | 647.42 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.27 |
March | 4260.13 | 14-MAR-20:51 | 1602.00 | 1870.78 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 |
April | 4890.43 | 19-APR-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 |
May | 4946.39 | 17-MAY-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
June | 5005.70 | 07-JUN-08:41 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
July | 5294.55 | 01-JUL-07:42 | 572.40 | 706.27 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 |
August | 4981.16 | 19-AUG-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
September | 4960.09 | 07-SEP-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
October | 4858.03 | 11-OCT-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 |
November | 4323.53 | 09-NOV-09:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 |
December | 3913.89 | 02-DEC-09:01 | 378.00 | 823.98 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3913.89 | 252.00 | 647.42 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5294.55 | 1602.00 | 1870.78 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 122.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3268.61 | 19-JAN-03:37 | 22633.56 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.30 |
February | 3291.85 | 27-FEB-06:09 | 14083.10 | 6639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.15 |
March | 3365.70 | 01-MAR-10:53 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.91 |
April | 3455.87 | 09-APR-01:13 | 17603.88 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.71 |
May | 3465.79 | 12-MAY-00:23 | 6790.07 | 933.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.04 |
June | 3401.16 | 26-JUN-18:30 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.45 | 0.00 |
July | 3031.26 | 15-JUL-18:30 | 1508.90 | 1452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.98 | 0.00 |
August | 3080.05 | 11-AUG-18:20 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.58 | 0.00 |
September | 3134.12 | 16-SEP-04:15 | 9053.42 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.63 |
October | 3500.98 | 02-OCT-05:10 | 7041.55 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.00 |
November | 3409.31 | 13-NOV-19:13 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.53 |
December | 3209.26 | 04-DEC-00:20 | 22633.56 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3031.26 | 1508.90 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3500.98 | 22633.56 | 6639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.45 | 146.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5564.41 | 20-JAN-17:11 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.66 |
February | 5340.28 | 26-FEB-17:51 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.46 |
March | 5908.21 | 08-MAR-17:11 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 |
April | 5961.62 | 08-APR-18:01 | 1170.00 | 2102.25 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.80 |
May | 5888.05 | 27-MAY-16:11 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.44 |
June | 5572.02 | 27-JUN-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
July | 5586.69 | 01-JUL-21:51 | 1386.00 | 1786.91 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 |
August | 5919.33 | 13-AUG-21:51 | 1386.00 | 1786.91 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
September | 5854.17 | 15-SEP-19:51 | 1386.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.67 |
October | 5908.08 | 14-OCT-16:11 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 |
November | 5396.49 | 05-NOV-17:41 | 777.60 | 1429.53 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 |
December | 4990.26 | 02-DEC-17:21 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4990.26 | 360.00 | 588.63 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5961.62 | 1386.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 73.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4913.15 | 20-JAN-17:11 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 |
February | 4836.31 | 26-FEB-17:51 | 954.00 | 693.66 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.98 |
March | 5716.69 | 15-MAR-18:31 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.95 |
April | 5796.30 | 08-APR-18:01 | 1170.00 | 2102.00 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.47 |
May | 5706.88 | 27-MAY-16:11 | 954.00 | 693.66 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.70 |
June | 5466.61 | 27-JUN-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
July | 5461.89 | 01-JUL-21:51 | 1386.00 | 1786.70 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 |
August | 5760.03 | 13-AUG-21:51 | 1386.00 | 1786.70 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.23 |
September | 5527.21 | 15-SEP-19:51 | 1386.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 |
October | 5574.73 | 08-OCT-18:11 | 1170.00 | 2102.00 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.27 |
November | 4881.17 | 07-NOV-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 |
December | 4750.59 | 02-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4750.59 | 360.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5796.30 | 1386.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 65.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2904.96 | 20-JAN-17:11 | 972.00 | 370.03 | 1238.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 |
February | 2713.40 | 26-FEB-17:51 | 954.00 | 436.11 | 1032.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 |
March | 2955.56 | 13-MAR-19:21 | 1386.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 |
April | 2711.73 | 08-APR-18:01 | 1170.00 | 1321.54 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 |
May | 2661.03 | 09-MAY-20:31 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.31 |
June | 2733.20 | 06-JUN-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | 0.00 |
July | 2731.84 | 01-JUL-08:61 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 0.00 |
August | 2805.32 | 01-AUG-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 |
September | 2950.64 | 25-SEP-20:41 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.97 |
October | 2957.66 | 09-OCT-19:51 | 1170.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 |
November | 2960.90 | 09-NOV-09:51 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.72 |
December | 2709.03 | 02-DEC-17:21 | 954.00 | 436.11 | 1032.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2661.03 | 360.00 | 370.03 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2960.90 | 1800.00 | 1321.54 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 40.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34770.88 | 30-JAN-21:23 | 71970.05 | 9167.57 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.58 |
February | 40659.63 | 27-FEB-02:33 | 80966.30 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.61 |
March | 37616.47 | 26-MAR-01:51 | 167930.11 | 6111.71 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.62 |
April | 38587.18 | 28-APR-04:46 | 269887.68 | 7639.64 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.94 |
May | 41318.12 | 12-MAY-00:23 | 80966.30 | 1718.92 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.70 |
June | 34139.48 | 09-JUN-03:56 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.51 |
July | 23545.80 | 17-JUL-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 | 0.00 |
August | 23300.40 | 16-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 | 0.00 |
September | 31295.81 | 21-SEP-19:27 | 209912.64 | 34378.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 |
October | 36612.56 | 26-OCT-00:09 | 269887.68 | 5729.73 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.08 |
November | 36059.70 | 09-NOV-01:37 | 188921.38 | 4010.81 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.15 |
December | 44253.33 | 29-DEC-02:45 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23300.40 | 26988.77 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44253.33 | 269887.68 | 34378.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 | 359.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39076.05 | 30-JAN-21:23 | 71970.05 | 9167.57 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.42 |
February | 42760.34 | 27-FEB-02:33 | 80966.30 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.53 |
March | 41090.52 | 26-MAR-01:51 | 167930.11 | 6111.71 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.99 |
April | 42948.13 | 13-APR-02:59 | 215910.14 | 3055.86 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.76 |
May | 44294.64 | 12-MAY-00:23 | 80966.30 | 1718.92 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.32 |
June | 35809.23 | 09-JUN-03:56 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.18 |
July | 24751.67 | 17-JUL-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 0.00 |
August | 24502.04 | 16-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 | 0.00 |
September | 32933.51 | 21-SEP-19:27 | 209912.64 | 34378.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.85 |
October | 40490.83 | 26-OCT-00:09 | 269887.68 | 5729.73 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.19 |
November | 37342.31 | 09-NOV-01:37 | 188921.38 | 4010.81 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.81 |
December | 46661.61 | 29-DEC-02:45 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24502.04 | 26988.77 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46661.61 | 269887.68 | 34378.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 359.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 46759.66 | 29-JAN-18:40 | 10674.24 | 6727.35 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 276.52 |
February | 45698.28 | 17-FEB-07:56 | 8539.39 | 5381.88 | 119302.85 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 288.24 |
March | 41487.66 | 09-MAR-07:15 | 10674.24 | 6727.35 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 260.78 |
April | 42929.69 | 09-APR-06:06 | 18679.92 | 5381.88 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 224.58 |
May | 42975.00 | 03-MAY-07:42 | 6404.54 | 3229.13 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 227.77 |
June | 31505.27 | 26-JUN-10:37 | 1601.14 | 1009.10 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 102.00 | 0.00 |
July | 31722.55 | 23-JUL-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 68.08 | 0.00 |
August | 31807.18 | 05-AUG-10:40 | 2401.70 | 1009.10 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 58.26 | 0.00 |
September | 36396.18 | 21-SEP-17:41 | 10674.24 | 6458.26 | 119302.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 0.00 | 332.31 |
October | 42898.62 | 21-OCT-07:47 | 9339.96 | 3767.32 | 104389.99 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 272.57 |
November | 49537.99 | 12-NOV-16:41 | 8005.68 | 2690.94 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 282.19 |
December | 44936.97 | 16-DEC-18:23 | 16011.36 | 8072.82 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 327.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31505.27 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49537.99 | 18679.92 | 8072.82 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 102.00 | 332.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6681.88 | 19-JAN-03:37 | 23954.40 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.81 |
February | 6558.34 | 27-FEB-06:09 | 14904.96 | 7026.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.75 |
March | 6895.82 | 01-MAR-10:53 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.60 |
April | 7053.91 | 09-APR-01:13 | 18631.20 | 4391.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.36 |
May | 6972.94 | 12-MAY-00:23 | 7186.32 | 988.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.60 |
June | 7151.34 | 26-JUN-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.92 | 0.00 |
July | 7108.19 | 23-JUL-13:00 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.12 | 0.00 |
August | 7416.02 | 16-AUG-15:01 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.68 | 0.00 |
September | 7049.22 | 09-SEP-12:50 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.28 | 0.00 |
October | 6905.79 | 02-OCT-05:10 | 7452.48 | 3513.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.49 |
November | 6917.73 | 13-NOV-19:13 | 5589.36 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.96 |
December | 6594.80 | 04-DEC-00:20 | 23954.40 | 4391.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6558.34 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7416.02 | 23954.40 | 7026.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.92 | 254.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.403855E+12 | 274206.78 | 11-JAN-20:30 | 0.580470E+12 | 572953.07 | 05-JAN-19:10 |
February | 0.360702E+12 | 270043.35 | 13-FEB-20:40 | 0.543098E+12 | 546307.73 | 21-FEB-21:19 |
March | 0.399640E+12 | 283561.12 | 13-MAR-19:30 | 0.545331E+12 | 538992.14 | 05-MAR-17:00 |
April | 0.377755E+12 | 276291.52 | 07-APR-19:19 | 0.511048E+12 | 559220.12 | 03-APR-16:00 |
May | 0.423741E+12 | 313579.63 | 31-MAY-18:10 | 0.454126E+12 | 416696.30 | 02-MAY-21:30 |
June | 0.515190E+12 | 410155.66 | 26-JUN-19:30 | 0.408231E+12 | 354047.40 | 01-JUN-17:10 |
July | 0.544008E+12 | 385637.70 | 17-JUL-19:30 | 0.413732E+12 | 352296.12 | 03-JUL-17:19 |
August | 0.532459E+12 | 389407.18 | 16-AUG-19:10 | 0.411281E+12 | 351598.96 | 30-AUG-17:19 |
September | 0.479208E+12 | 363718.17 | 12-SEP-19:10 | 0.406562E+12 | 435508.97 | 21-SEP-18:10 |
October | 0.414979E+12 | 284631.06 | 10-OCT-19:10 | 0.499188E+12 | 507125.18 | 31-OCT-16:40 |
November | 0.394005E+12 | 269863.18 | 14-NOV-20:40 | 0.522404E+12 | 534270.95 | 29-NOV-17:40 |
December | 0.400527E+12 | 267187.92 | 12-DEC-20:40 | 0.637446E+12 | 650549.76 | 21-DEC-17:49 |
Annual Sum or Average | 0.524607E+13 | 0.593292E+13 | ||||
Minimum of Months | 0.360702E+12 | 267187.92 | 0.406562E+12 | 351598.96 | ||
Maximum of Months | 0.544008E+12 | 410155.66 | 0.637446E+12 | 650549.76 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.743997E+11 | 0.269283E+11 | 0.140828E+12 | 0.552133E+11 | 0.480281E+11 | 0.620300E+10 | 0.00 | 0.159099E+11 | 0.00 | 0.00 | 0.234187E+11 | 0.770396E+10 | 0.00 |
February | 0.669731E+11 | 0.226722E+11 | 0.127191E+12 | 0.498701E+11 | 0.429137E+11 | 0.529605E+10 | 0.00 | 0.122745E+11 | 0.00 | 0.00 | 0.218483E+11 | 0.696160E+10 | 0.00 |
March | 0.737306E+11 | 0.227724E+11 | 0.140882E+12 | 0.552165E+11 | 0.472587E+11 | 0.609305E+10 | 0.00 | 0.205272E+11 | 0.00 | 0.00 | 0.202466E+11 | 0.770258E+10 | 0.00 |
April | 0.710688E+11 | 0.196780E+11 | 0.136245E+12 | 0.534312E+11 | 0.441652E+11 | 0.574148E+10 | 0.00 | 0.160251E+11 | 0.00 | 0.00 | 0.188818E+11 | 0.746455E+10 | 0.00 |
May | 0.729602E+11 | 0.182860E+11 | 0.140860E+12 | 0.552140E+11 | 0.477504E+11 | 0.817726E+10 | 0.00 | 0.555538E+11 | 0.00 | 0.00 | 0.120003E+11 | 0.770417E+10 | 0.00 |
June | 0.702998E+11 | 0.166136E+11 | 0.136336E+12 | 0.534339E+11 | 0.547671E+11 | 0.849149E+10 | 0.00 | 0.152102E+12 | 0.00 | 0.00 | 0.105896E+11 | 0.745690E+10 | 0.00 |
July | 0.727998E+11 | 0.176551E+11 | 0.140770E+12 | 0.552103E+11 | 0.567049E+11 | 0.885109E+10 | 0.00 | 0.167726E+12 | 0.00 | 0.00 | 0.113247E+11 | 0.771242E+10 | 0.00 |
August | 0.731787E+11 | 0.194276E+11 | 0.140892E+12 | 0.552160E+11 | 0.578329E+11 | 0.884091E+10 | 0.00 | 0.154350E+12 | 0.00 | 0.00 | 0.973879E+10 | 0.770435E+10 | 0.00 |
September | 0.712280E+11 | 0.210099E+11 | 0.136256E+12 | 0.534314E+11 | 0.548157E+11 | 0.825491E+10 | 0.00 | 0.112331E+12 | 0.00 | 0.00 | 0.935512E+10 | 0.746629E+10 | 0.00 |
October | 0.741143E+11 | 0.241443E+11 | 0.140818E+12 | 0.552131E+11 | 0.512266E+11 | 0.683173E+10 | 0.00 | 0.324835E+11 | 0.00 | 0.00 | 0.172308E+11 | 0.770266E+10 | 0.00 |
November | 0.719057E+11 | 0.254462E+11 | 0.136330E+12 | 0.534332E+11 | 0.485092E+11 | 0.635340E+10 | 0.00 | 0.186458E+11 | 0.00 | 0.00 | 0.208818E+11 | 0.744852E+10 | 0.00 |
December | 0.744165E+11 | 0.275091E+11 | 0.140770E+12 | 0.552117E+11 | 0.491424E+11 | 0.527731E+10 | 0.00 | 0.120884E+11 | 0.00 | 0.00 | 0.232128E+11 | 0.771228E+10 | 0.00 |
Annual Sum or Average | 0.867075E+12 | 0.262143E+12 | 0.165818E+13 | 0.650095E+12 | 0.603115E+12 | 0.844117E+11 | 0.00 | 0.770017E+12 | 0.00 | 0.00 | 0.198729E+12 | 0.907403E+11 | 0.00 |
Minimum of Months | 0.669731E+11 | 0.166136E+11 | 0.127191E+12 | 0.498701E+11 | 0.429137E+11 | 0.527731E+10 | 0.00 | 0.120884E+11 | 0.00 | 0.00 | 0.935512E+10 | 0.696160E+10 | 0.00 |
Maximum of Months | 0.744165E+11 | 0.275091E+11 | 0.140892E+12 | 0.552165E+11 | 0.578329E+11 | 0.885109E+10 | 0.00 | 0.167726E+12 | 0.00 | 0.00 | 0.234187E+11 | 0.771242E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.129875E+12 | 0.00 | 0.298676E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.133737E+12 | 0.00 | 0.272157E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.950227E+11 | 0.00 | 0.298285E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.831632E+11 | 0.00 | 0.280929E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.225225E+11 | 0.00 | 0.279625E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.727591E+09 | 0.00 | 0.260389E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.587789E+09 | 0.00 | 0.261324E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.523981E+09 | 0.00 | 0.258718E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.630440E+10 | 0.00 | 0.253287E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.776175E+11 | 0.00 | 0.269667E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.104007E+12 | 0.00 | 0.271306E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.194710E+12 | 0.00 | 0.290916E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.848799E+12 | 0.00 | 0.329528E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.523981E+09 | 0.00 | 0.253287E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.194710E+12 | 0.00 | 0.298676E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 71560.59 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39721.54 | 02-JAN-07:19 | 46257.70 | 23-JAN-06:30 | 4096.23 | 13-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 71560.59 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39721.54 | 01-FEB-07:19 | 52815.33 | 22-FEB-23:00 | 4072.31 | 16-FEB-17:10 | 0.00 | 01-FEB-00:10 |
March | 71560.59 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39721.54 | 13-MAR-06:19 | 53144.46 | 06-MAR-22:10 | 4031.77 | 05-MAR-17:00 | 0.00 | 01-MAR-00:10 |
April | 71560.59 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39721.06 | 03-APR-06:19 | 40651.31 | 21-APR-21:19 | 4006.74 | 04-APR-09:20 | 0.00 | 01-APR-00:10 |
May | 71560.59 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39718.92 | 19-MAY-06:19 | 41251.57 | 20-MAY-04:00 | 3992.69 | 02-MAY-21:30 | 0.00 | 01-MAY-00:10 |
June | 71560.59 | 01-JUN-19:19 | 16690.39 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39719.09 | 16-JUN-06:19 | 46654.13 | 30-JUN-21:10 | 4246.56 | 15-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 71560.59 | 03-JUL-19:30 | 16690.39 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39719.09 | 28-JUL-06:19 | 46772.41 | 17-JUL-21:10 | 4364.43 | 17-JUL-19:10 | 0.00 | 01-JUL-00:10 |
August | 71560.59 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39719.23 | 18-AUG-06:19 | 48893.12 | 16-AUG-21:10 | 4190.08 | 10-AUG-18:30 | 0.00 | 01-AUG-00:10 |
September | 71560.59 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39720.76 | 19-SEP-06:19 | 47602.81 | 12-SEP-21:10 | 4158.66 | 12-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 71560.59 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39721.54 | 02-OCT-06:19 | 51442.91 | 05-OCT-03:00 | 4027.22 | 13-OCT-06:30 | 0.00 | 01-OCT-00:10 |
November | 71560.59 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39721.54 | 01-NOV-06:19 | 53749.96 | 13-NOV-10:30 | 4053.01 | 25-NOV-23:49 | 0.00 | 01-NOV-00:10 |
December | 71560.59 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39721.54 | 01-DEC-07:19 | 53075.09 | 01-DEC-22:49 | 4093.39 | 25-DEC-10:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 71560.59 | 16690.39 | 89171.45 | 39718.92 | 40651.31 | 3992.69 | 0.00 | |||||||
Maximum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.54 | 53749.96 | 4364.43 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 66442.93 | 20-JAN-13:09 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.77 | 12-JAN-19:10 | 0.00 |
February | 62141.36 | 18-FEB-13:30 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.14 | 06-FEB-19:10 | 0.00 |
March | 84337.97 | 13-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4738.33 | 15-MAR-18:10 | 0.00 |
April | 63412.72 | 07-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.29 | 27-APR-18:10 | 0.00 |
May | 96261.21 | 31-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.42 | 01-MAY-06:10 | 0.00 |
June | 175630.45 | 26-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-10:50 | 4738.72 | 15-JUN-18:10 | 0.00 |
July | 141879.98 | 16-JUL-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUL-07:30 | 4738.38 | 10-JUL-18:10 | 0.00 |
August | 156517.85 | 16-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 02-AUG-09:00 | 4738.22 | 04-AUG-18:30 | 0.00 |
September | 125403.43 | 10-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-03:39 | 4738.28 | 06-SEP-18:49 | 0.00 |
October | 99233.63 | 11-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.52 | 05-OCT-18:10 | 0.00 |
November | 69951.47 | 07-NOV-13:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.39 | 06-NOV-07:30 | 0.00 |
December | 63235.32 | 02-DEC-14:30 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.43 | 27-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 62141.36 | 0.00 | 0.00 | 9938.94 | 4738.14 | 0.00 | |||
Maximum of Months | 175630.45 | 0.00 | 0.00 | 9938.94 | 4738.77 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 274206.78 | 11-JAN-20:30 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 43129.67 | 3636.11 | 0.00 | 4472.65 | 0.00 |
February | 270043.35 | 13-FEB-20:40 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 42102.18 | 3663.37 | 0.00 | 1579.37 | 0.00 |
March | 283561.12 | 13-MAR-19:30 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 30194.15 | 3236.46 | 0.00 | 35734.42 | 0.00 |
April | 276291.52 | 07-APR-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 28710.87 | 3218.24 | 0.00 | 30229.38 | 0.00 |
May | 313579.63 | 31-MAY-18:10 | 58948.06 | 77573.37 | 0.00 | 31786.55 | 28407.04 | 3813.93 | 0.00 | 96261.21 | 0.00 |
June | 410155.66 | 26-JUN-19:30 | 71560.59 | 86439.81 | 16690.39 | 32090.30 | 37771.34 | 3590.11 | 0.00 | 145663.40 | 0.00 |
July | 385637.70 | 17-JUL-19:30 | 71560.59 | 86439.81 | 16690.39 | 32090.30 | 36123.45 | 4270.08 | 0.00 | 122098.34 | 0.00 |
August | 389407.18 | 16-AUG-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 37221.22 | 3609.30 | 0.00 | 125774.10 | 0.00 |
September | 363718.17 | 12-SEP-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 38715.81 | 3972.64 | 0.00 | 98794.18 | 0.00 |
October | 284631.06 | 10-OCT-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 29750.05 | 3148.41 | 0.00 | 39543.14 | 0.00 |
November | 269863.18 | 14-NOV-20:40 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 43194.45 | 3874.86 | 0.00 | 4447.15 | 0.00 |
December | 267187.92 | 12-DEC-20:40 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 40160.43 | 3692.57 | 0.00 | 990.67 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 267187.92 | 58948.06 | 77573.37 | 0.00 | 31786.55 | 28407.04 | 3148.41 | 0.00 | 990.67 | 0.00 | |
Maximum of Months | 410155.66 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 43194.45 | 4270.08 | 0.00 | 145663.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 257972.63 | 05-JAN-09:09 | 0.00 | 299540.65 | 24-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 242312.80 | 12-FEB-07:10 | 0.00 | 302076.79 | 24-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 225289.23 | 20-MAR-22:30 | 0.00 | 302896.75 | 08-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 202262.72 | 03-APR-16:00 | 0.00 | 293189.57 | 04-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 170223.09 | 27-MAY-02:30 | 0.00 | 282429.99 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 67815.90 | 09-JUN-04:49 | 0.00 | 250533.10 | 02-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 34732.53 | 02-JUL-04:49 | 0.00 | 248793.71 | 03-JUL-20:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 34357.38 | 23-AUG-04:30 | 0.00 | 247976.66 | 22-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 189345.73 | 21-SEP-15:39 | 0.00 | 250523.95 | 21-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 219854.43 | 26-OCT-04:40 | 0.00 | 252488.75 | 25-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 193523.17 | 25-NOV-23:49 | 0.00 | 281237.41 | 22-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 325699.63 | 21-DEC-09:20 | 0.00 | 289783.77 | 22-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 34357.38 | 0.00 | 247976.66 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 325699.63 | 0.00 | 302896.75 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.75 | 4.33 | 24.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.74 | 2.50 | 24.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.79 | 0.33 | 24.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.90 | 1.50 | 24.90 |
December | 2.67 | 20.38 | 2.67 | 20.38 | 2.00 | 21.58 | 2.00 | 22.27 |
Annual Sum or Average | 2.67 | 20.38 | 2.67 | 20.38 | 10.67 | 23.31 | 10.67 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.38 | 2.67 | 20.38 | 4.33 | 24.90 | 4.33 | 24.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.33 | 24.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.62 | 0.33 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.33 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 25.37 | 60.17 | 25.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 25.44 | 50.00 | 25.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 25.35 | 62.17 | 25.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 59.33 | 25.34 | 59.33 | 25.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 25.17 | 15.17 | 25.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.43 | 4.33 | 25.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 25.33 | 39.00 | 25.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 25.35 | 65.50 | 25.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 | 25.27 | 52.17 | 25.27 |
Annual Sum or Average | 0.00 | 0.00 | 407.83 | 25.34 | 407.83 | 25.34 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 25.44 | 65.50 | 25.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.81 | 9.00 | 24.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.82 | 6.33 | 24.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.79 | 1.33 | 24.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.75 | 1.33 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.93 | 0.17 | 24.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.79 | 5.00 | 24.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.76 | 3.50 | 24.76 |
Annual Sum or Average | 0.00 | 0.00 | 27.33 | 24.80 | 27.33 | 24.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.93 | 9.00 | 24.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.68 | 0.50 | 24.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.78 | 0.67 | 24.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.74 | 0.17 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.78 | 0.17 | 24.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.62 | 0.17 | 24.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 24.72 | 1.83 | 24.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.78 | 0.67 | 24.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.36 | 0.83 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 0.83 | 20.36 | 0.83 | 20.36 | 1.00 | 20.86 | 1.00 | 21.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.36 | 0.83 | 20.36 | 0.50 | 21.70 | 0.50 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.36 | 1.50 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 1.67 | 20.38 | 1.67 | 20.38 | 0.50 | 20.55 | 0.50 | 20.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.54 | 1.50 | 20.54 | 0.17 | 21.72 | 0.17 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.37 | 0.83 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 0.83 | 20.35 | 0.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.77 | 2.17 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
October | 0.33 | 20.32 | 0.33 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
November | 0.50 | 20.38 | 0.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
December | 4.00 | 20.29 | 4.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Annual Sum or Average | 6.83 | 20.33 | 6.83 | 20.33 | 4.67 | 20.69 | 4.67 | 20.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.50 | 4.00 | 20.50 | 2.17 | 21.77 | 2.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.88 | 1.33 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.12 | 5.33 | 22.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.05 | 5.67 | 22.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.14 | 7.50 | 22.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.11 | 4.33 | 22.11 |
October | 0.17 | 20.55 | 0.17 | 20.55 | 0.17 | 20.95 | 0.17 | 21.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.37 | 1.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 1.50 | 20.39 | 1.50 | 20.39 | 24.50 | 21.90 | 24.50 | 21.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.55 | 1.33 | 20.55 | 7.50 | 22.14 | 7.50 | 22.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.48 | 0.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.90 | 1.17 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.13 | 5.83 | 22.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.09 | 5.33 | 22.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.17 | 6.00 | 22.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 22.05 | 3.17 | 22.05 |
October | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 20.30 | 2.50 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 3.33 | 20.35 | 3.33 | 20.35 | 21.67 | 21.69 | 21.67 | 21.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.55 | 2.50 | 20.55 | 6.00 | 22.17 | 6.00 | 22.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
October | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.29 | 1.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Annual Sum or Average | 1.33 | 20.35 | 1.33 | 20.35 | 1.50 | 20.85 | 1.50 | 21.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.55 | 1.00 | 20.55 | 0.50 | 21.76 | 0.50 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.32 | 2.33 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 2.83 | 20.35 | 2.83 | 20.35 | 1.00 | 20.56 | 1.00 | 20.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.54 | 2.33 | 20.54 | 0.50 | 21.76 | 0.50 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
October | 0.17 | 20.52 | 0.17 | 20.52 | 0.83 | 21.38 | 0.83 | 21.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
December | 0.67 | 20.34 | 0.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 1.00 | 20.41 | 1.00 | 20.41 | 4.17 | 21.31 | 4.17 | 21.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.55 | 0.67 | 20.55 | 1.83 | 21.78 | 1.83 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.89 | 9.00 | 24.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.87 | 8.33 | 24.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.91 | 9.50 | 24.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 24.87 | 12.83 | 24.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.86 | 5.67 | 24.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.76 | 0.17 | 24.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.75 | 0.50 | 24.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.82 | 9.50 | 24.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.79 | 10.83 | 24.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.80 | 7.17 | 24.80 |
Annual Sum or Average | 0.00 | 0.00 | 73.50 | 24.85 | 73.50 | 24.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 24.91 | 12.83 | 24.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 24.90 | 12.50 | 24.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 24.89 | 10.67 | 24.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 24.94 | 11.83 | 24.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 24.89 | 15.67 | 24.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.91 | 6.00 | 24.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.78 | 0.17 | 24.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.75 | 0.67 | 24.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 24.84 | 11.33 | 24.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 24.82 | 13.83 | 24.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 24.84 | 9.67 | 24.84 |
Annual Sum or Average | 0.00 | 0.00 | 92.33 | 24.88 | 92.33 | 24.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 24.94 | 15.67 | 24.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 106.17 | 25.33 | 106.17 | 25.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 85.17 | 25.37 | 85.17 | 25.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 91.50 | 25.28 | 91.50 | 25.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 95.33 | 25.23 | 95.33 | 25.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 25.18 | 27.67 | 25.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.15 | 0.33 | 25.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.14 | 5.33 | 25.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 | 25.25 | 60.50 | 25.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 98.17 | 25.33 | 98.17 | 25.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 25.28 | 81.00 | 25.28 |
Annual Sum or Average | 0.00 | 0.00 | 651.17 | 25.29 | 651.17 | 25.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 106.17 | 25.37 | 106.17 | 25.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 563.33 | 23.83 | 0.00 | 23.83 | 0.00 | 23.83 |
February | 635.50 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
March | 735.00 | 23.55 | 0.00 | 23.55 | 0.00 | 23.55 |
April | 657.67 | 23.58 | 0.00 | 23.58 | 0.00 | 23.58 |
May | 673.33 | 23.49 | 0.67 | 23.49 | 0.00 | 23.49 |
June | 465.50 | 23.59 | 131.33 | 23.65 | 85.17 | 23.66 |
July | 468.00 | 23.67 | 213.67 | 23.73 | 164.33 | 23.75 |
August | 309.83 | 23.85 | 269.67 | 23.90 | 102.33 | 23.91 |
September | 229.83 | 23.96 | 46.50 | 23.97 | 0.83 | 23.97 |
October | 356.83 | 23.98 | 0.83 | 23.98 | 0.00 | 23.98 |
November | 288.50 | 23.97 | 2.83 | 23.97 | 0.00 | 23.97 |
December | 636.83 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
Annual Sum or Average | 6020.17 | 23.72 | 665.50 | 23.74 | 352.67 | 23.75 |
Minimum of Months | 229.83 | 23.49 | 0.00 | 23.49 | 0.00 | 23.49 |
Maximum of Months | 735.00 | 23.98 | 269.67 | 23.98 | 164.33 | 23.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 574.67 | 21.50 | 196.50 | 21.86 | 74.67 | 21.78 |
February | 524.17 | 21.50 | 237.17 | 21.73 | 142.83 | 21.61 |
March | 602.67 | 21.63 | 149.83 | 21.77 | 82.00 | 21.70 |
April | 650.67 | 21.51 | 123.17 | 21.51 | 102.67 | 21.45 |
May | 637.33 | 21.97 | 34.33 | 22.05 | 4.67 | 22.05 |
June | 325.67 | 22.73 | 345.00 | 23.27 | 63.33 | 23.26 |
July | 350.67 | 22.84 | 424.00 | 23.27 | 138.33 | 23.24 |
August | 313.50 | 22.75 | 424.67 | 23.31 | 91.50 | 23.28 |
September | 336.83 | 22.48 | 247.67 | 23.11 | 0.83 | 23.11 |
October | 545.83 | 21.75 | 218.50 | 22.05 | 87.50 | 21.94 |
November | 552.00 | 21.62 | 188.00 | 21.98 | 61.83 | 21.90 |
December | 624.67 | 21.41 | 258.67 | 21.53 | 186.50 | 21.43 |
Annual Sum or Average | 6038.67 | 21.85 | 2847.50 | 22.25 | 1036.67 | 22.18 |
Minimum of Months | 313.50 | 21.41 | 34.33 | 21.51 | 0.83 | 21.43 |
Maximum of Months | 650.67 | 22.84 | 424.67 | 23.31 | 186.50 | 23.28 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 684.00 | 22.99 | 0.67 | 22.99 | 0.67 | 22.99 |
February | 624.33 | 22.76 | 6.00 | 22.74 | 6.00 | 22.73 |
March | 694.33 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
April | 644.50 | 22.86 | 3.17 | 22.87 | 0.00 | 22.87 |
May | 474.50 | 23.30 | 44.33 | 23.36 | 2.67 | 23.36 |
June | 147.17 | 23.83 | 308.17 | 23.90 | 99.00 | 23.91 |
July | 202.50 | 23.84 | 367.83 | 23.89 | 170.17 | 23.88 |
August | 161.83 | 23.87 | 414.00 | 23.93 | 120.50 | 23.94 |
September | 178.17 | 23.62 | 128.17 | 23.77 | 2.33 | 23.77 |
October | 580.67 | 23.16 | 3.83 | 23.17 | 0.00 | 23.17 |
November | 636.50 | 23.01 | 2.83 | 23.02 | 0.00 | 23.02 |
December | 734.33 | 22.67 | 27.33 | 22.61 | 27.33 | 22.55 |
Annual Sum or Average | 5762.83 | 23.05 | 1306.33 | 23.20 | 428.67 | 23.23 |
Minimum of Months | 147.17 | 22.67 | 0.00 | 22.61 | 0.00 | 22.55 |
Maximum of Months | 734.33 | 23.87 | 414.00 | 23.93 | 170.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.61 | 25.33 | 21.59 | 25.33 | 21.57 |
February | 672.00 | 21.49 | 95.67 | 21.43 | 95.67 | 21.38 |
March | 744.00 | 21.84 | 1.33 | 21.84 | 1.33 | 21.84 |
April | 720.00 | 21.92 | 6.17 | 21.91 | 6.17 | 21.90 |
May | 737.83 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
June | 321.33 | 23.81 | 131.67 | 23.84 | 24.83 | 23.84 |
July | 304.50 | 23.83 | 242.83 | 23.85 | 111.67 | 23.84 |
August | 299.33 | 23.80 | 177.50 | 23.85 | 50.83 | 23.85 |
September | 531.83 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
October | 744.00 | 22.42 | 16.17 | 22.39 | 16.17 | 22.36 |
November | 720.00 | 21.82 | 20.67 | 21.79 | 20.67 | 21.77 |
December | 744.00 | 21.45 | 165.33 | 21.37 | 165.33 | 21.31 |
Annual Sum or Average | 7282.83 | 22.30 | 882.67 | 22.35 | 518.00 | 22.33 |
Minimum of Months | 299.33 | 21.45 | 0.00 | 21.37 | 0.00 | 21.31 |
Maximum of Months | 744.00 | 23.83 | 242.83 | 23.85 | 165.33 | 23.85 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.31 | 58.83 | 21.28 | 58.83 | 21.26 |
February | 672.00 | 21.27 | 136.83 | 21.22 | 136.83 | 21.19 |
March | 744.00 | 21.53 | 22.17 | 21.52 | 22.17 | 21.50 |
April | 720.00 | 21.57 | 16.17 | 21.56 | 16.17 | 21.55 |
May | 744.00 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
June | 453.67 | 23.60 | 79.33 | 23.62 | 35.67 | 23.62 |
July | 404.50 | 23.63 | 210.17 | 23.65 | 114.83 | 23.62 |
August | 463.00 | 23.56 | 113.50 | 23.59 | 57.33 | 23.59 |
September | 663.83 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
October | 744.00 | 22.02 | 22.33 | 21.99 | 22.33 | 21.96 |
November | 720.00 | 21.47 | 39.17 | 21.44 | 39.17 | 21.42 |
December | 744.00 | 21.21 | 184.17 | 21.17 | 184.17 | 21.14 |
Annual Sum or Average | 7817.00 | 22.09 | 882.67 | 22.11 | 687.50 | 22.08 |
Minimum of Months | 404.50 | 21.21 | 0.00 | 21.17 | 0.00 | 21.14 |
Maximum of Months | 744.00 | 23.63 | 210.17 | 23.65 | 184.17 | 23.62 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 229.17 | 24.12 | 664.67 | 23.99 | 206.83 | 24.06 |
February | 206.33 | 23.96 | 583.33 | 23.95 | 173.67 | 24.03 |
March | 216.00 | 24.20 | 663.83 | 24.02 | 199.83 | 24.09 |
April | 234.83 | 24.22 | 663.17 | 24.00 | 222.50 | 24.08 |
May | 288.00 | 24.05 | 714.00 | 23.86 | 287.00 | 23.91 |
June | 399.00 | 23.97 | 714.50 | 23.82 | 399.00 | 23.86 |
July | 444.50 | 23.93 | 741.17 | 23.81 | 444.50 | 23.84 |
August | 426.67 | 23.93 | 736.33 | 23.80 | 426.67 | 23.84 |
September | 292.00 | 24.01 | 693.17 | 23.85 | 290.67 | 23.89 |
October | 242.17 | 24.12 | 687.50 | 23.93 | 230.83 | 23.99 |
November | 231.00 | 24.16 | 652.67 | 23.99 | 210.00 | 24.08 |
December | 217.00 | 23.74 | 607.33 | 23.90 | 170.67 | 23.97 |
Annual Sum or Average | 3426.67 | 24.02 | 8121.67 | 23.90 | 3262.17 | 23.96 |
Minimum of Months | 206.33 | 23.74 | 583.33 | 23.80 | 170.67 | 23.84 |
Maximum of Months | 444.50 | 24.22 | 741.17 | 24.02 | 444.50 | 24.09 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.33 | 22.66 | 193.67 | 23.03 | 15.83 | 22.98 |
February | 386.00 | 22.36 | 204.33 | 22.72 | 44.83 | 22.60 |
March | 429.33 | 22.40 | 146.50 | 22.73 | 16.17 | 22.68 |
April | 470.33 | 22.34 | 112.33 | 22.61 | 8.17 | 22.59 |
May | 264.33 | 22.99 | 245.00 | 23.43 | 19.33 | 23.45 |
June | 166.50 | 23.86 | 623.00 | 23.89 | 158.67 | 23.90 |
July | 206.17 | 23.81 | 670.67 | 23.89 | 199.17 | 23.88 |
August | 190.50 | 23.88 | 651.83 | 23.92 | 182.33 | 23.92 |
September | 73.17 | 23.14 | 492.83 | 23.87 | 5.17 | 23.87 |
October | 310.00 | 22.39 | 254.50 | 22.98 | 24.67 | 22.90 |
November | 348.67 | 22.51 | 205.67 | 23.03 | 8.17 | 23.00 |
December | 522.00 | 22.39 | 197.50 | 22.51 | 80.33 | 22.36 |
Annual Sum or Average | 3780.33 | 22.70 | 3997.83 | 23.27 | 762.83 | 23.26 |
Minimum of Months | 73.17 | 22.34 | 112.33 | 22.51 | 5.17 | 22.36 |
Maximum of Months | 522.00 | 23.88 | 670.67 | 23.92 | 199.17 | 23.92 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.33 | 23.20 | 6.83 | 23.22 | 0.00 | 23.22 |
February | 383.83 | 22.94 | 1.17 | 22.95 | 0.00 | 22.95 |
March | 455.83 | 23.11 | 1.17 | 23.12 | 0.00 | 23.12 |
April | 465.83 | 23.05 | 38.17 | 23.12 | 0.00 | 23.12 |
May | 235.17 | 23.39 | 171.50 | 23.64 | 10.67 | 23.65 |
June | 148.67 | 23.93 | 460.83 | 23.94 | 142.67 | 23.94 |
July | 191.33 | 23.93 | 520.67 | 23.95 | 191.17 | 23.95 |
August | 167.00 | 23.97 | 544.17 | 23.97 | 162.67 | 23.97 |
September | 32.83 | 23.51 | 265.17 | 23.93 | 4.00 | 23.93 |
October | 235.67 | 22.91 | 41.50 | 23.07 | 0.00 | 23.07 |
November | 318.17 | 23.12 | 19.17 | 23.17 | 0.00 | 23.17 |
December | 549.33 | 22.99 | 9.00 | 22.96 | 9.00 | 22.92 |
Annual Sum or Average | 3543.00 | 23.20 | 2079.33 | 23.48 | 520.17 | 23.52 |
Minimum of Months | 32.83 | 22.91 | 1.17 | 22.95 | 0.00 | 22.92 |
Maximum of Months | 549.33 | 23.97 | 544.17 | 23.97 | 191.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.67 | 21.29 | 215.00 | 21.17 | 215.00 | 21.10 |
February | 662.00 | 21.23 | 272.50 | 21.09 | 272.50 | 21.01 |
March | 712.33 | 21.29 | 264.17 | 21.26 | 250.00 | 21.19 |
April | 700.33 | 21.28 | 198.67 | 21.21 | 189.33 | 21.12 |
May | 645.83 | 21.73 | 55.00 | 21.94 | 14.33 | 21.95 |
June | 517.17 | 21.75 | 108.17 | 22.20 | 31.67 | 22.33 |
July | 539.00 | 21.84 | 122.67 | 22.31 | 58.00 | 22.48 |
August | 521.33 | 21.78 | 118.50 | 22.30 | 34.67 | 22.45 |
September | 520.83 | 21.74 | 81.00 | 22.19 | 7.67 | 22.25 |
October | 674.83 | 21.33 | 157.00 | 21.39 | 131.83 | 21.30 |
November | 698.83 | 21.30 | 187.00 | 21.18 | 185.50 | 21.10 |
December | 742.83 | 21.12 | 431.67 | 20.99 | 431.67 | 20.92 |
Annual Sum or Average | 7667.00 | 21.44 | 2211.33 | 21.51 | 1822.17 | 21.44 |
Minimum of Months | 517.17 | 21.12 | 55.00 | 20.99 | 7.67 | 20.92 |
Maximum of Months | 742.83 | 21.84 | 431.67 | 22.31 | 431.67 | 22.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.88 | 431.17 | 20.78 | 431.17 | 20.74 |
February | 672.00 | 20.88 | 404.33 | 20.78 | 404.33 | 20.73 |
March | 722.67 | 21.06 | 354.33 | 20.99 | 340.50 | 20.90 |
April | 705.50 | 21.14 | 225.50 | 21.06 | 214.83 | 20.95 |
May | 663.00 | 21.72 | 49.50 | 21.87 | 17.83 | 21.87 |
June | 535.67 | 21.81 | 102.50 | 22.23 | 32.17 | 22.35 |
July | 560.00 | 21.89 | 106.50 | 22.31 | 59.17 | 22.47 |
August | 581.67 | 21.91 | 88.67 | 22.27 | 34.33 | 22.41 |
September | 598.17 | 21.85 | 49.00 | 22.10 | 3.00 | 22.11 |
October | 715.33 | 21.23 | 170.33 | 21.16 | 159.17 | 21.06 |
November | 720.00 | 21.01 | 320.17 | 20.88 | 320.17 | 20.82 |
December | 744.00 | 20.79 | 625.33 | 20.73 | 625.33 | 20.71 |
Annual Sum or Average | 7962.00 | 21.31 | 2927.33 | 21.28 | 2642.00 | 21.19 |
Minimum of Months | 535.67 | 20.79 | 49.00 | 20.73 | 3.00 | 20.71 |
Maximum of Months | 744.00 | 21.91 | 625.33 | 22.31 | 625.33 | 22.47 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 343.83 | 20.78 | 343.83 | 20.74 |
February | 672.00 | 20.84 | 408.83 | 20.78 | 408.83 | 20.75 |
March | 744.00 | 21.04 | 216.67 | 20.96 | 216.67 | 20.91 |
April | 720.00 | 21.14 | 103.33 | 21.09 | 103.33 | 21.05 |
May | 744.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
June | 705.33 | 22.01 | 25.00 | 22.07 | 19.00 | 22.10 |
July | 731.67 | 22.08 | 51.33 | 22.17 | 47.50 | 22.23 |
August | 728.67 | 21.96 | 25.67 | 22.01 | 17.33 | 22.03 |
September | 719.83 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
October | 744.00 | 21.12 | 95.17 | 21.06 | 95.17 | 21.01 |
November | 720.00 | 20.93 | 228.33 | 20.84 | 228.33 | 20.79 |
December | 744.00 | 20.81 | 537.50 | 20.76 | 537.50 | 20.74 |
Annual Sum or Average | 8717.50 | 21.35 | 2035.67 | 21.25 | 2017.50 | 21.17 |
Minimum of Months | 672.00 | 20.81 | 0.00 | 20.76 | 0.00 | 20.74 |
Maximum of Months | 744.00 | 22.08 | 537.50 | 22.17 | 537.50 | 22.23 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.34 | 226.00 | 21.22 | 226.00 | 21.15 |
February | 670.00 | 21.29 | 276.17 | 21.14 | 276.17 | 21.06 |
March | 729.00 | 21.38 | 238.50 | 21.20 | 238.50 | 21.10 |
April | 712.67 | 21.38 | 186.00 | 21.23 | 185.00 | 21.13 |
May | 686.33 | 21.91 | 22.17 | 21.95 | 12.33 | 21.95 |
June | 476.00 | 21.88 | 152.50 | 22.62 | 50.17 | 22.87 |
July | 487.17 | 21.86 | 181.33 | 22.60 | 69.00 | 22.83 |
August | 467.83 | 21.82 | 176.17 | 22.60 | 46.67 | 22.83 |
September | 492.50 | 21.69 | 58.33 | 22.01 | 4.67 | 22.05 |
October | 709.83 | 21.46 | 126.33 | 21.32 | 125.17 | 21.22 |
November | 716.83 | 21.36 | 199.50 | 21.22 | 199.00 | 21.14 |
December | 744.00 | 21.13 | 433.83 | 21.00 | 433.83 | 20.94 |
Annual Sum or Average | 7636.17 | 21.51 | 2276.83 | 21.56 | 1866.50 | 21.50 |
Minimum of Months | 467.83 | 21.13 | 22.17 | 21.00 | 4.67 | 20.94 |
Maximum of Months | 744.00 | 21.91 | 433.83 | 22.62 | 433.83 | 22.87 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.83 | 441.50 | 20.75 | 441.50 | 20.71 |
February | 672.00 | 20.90 | 403.50 | 20.80 | 403.50 | 20.75 |
March | 744.00 | 21.22 | 328.83 | 21.07 | 328.83 | 20.98 |
April | 716.33 | 21.28 | 221.83 | 21.13 | 221.17 | 21.03 |
May | 700.50 | 21.90 | 22.33 | 21.94 | 13.67 | 21.93 |
June | 479.00 | 21.90 | 133.00 | 22.61 | 51.67 | 22.88 |
July | 496.33 | 21.89 | 151.50 | 22.57 | 70.33 | 22.81 |
August | 502.00 | 21.88 | 122.50 | 22.49 | 43.67 | 22.71 |
September | 590.83 | 21.92 | 33.17 | 22.09 | 2.00 | 22.10 |
October | 742.17 | 21.35 | 163.83 | 21.21 | 163.17 | 21.11 |
November | 720.00 | 20.94 | 354.00 | 20.83 | 354.00 | 20.78 |
December | 744.00 | 20.73 | 632.33 | 20.70 | 632.33 | 20.69 |
Annual Sum or Average | 7851.17 | 21.34 | 3008.33 | 21.33 | 2725.83 | 21.25 |
Minimum of Months | 479.00 | 20.73 | 22.33 | 20.70 | 2.00 | 20.69 |
Maximum of Months | 744.00 | 21.92 | 632.33 | 22.61 | 632.33 | 22.88 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.56 | 25.00 | 21.54 | 25.00 | 21.52 |
February | 672.00 | 21.53 | 47.00 | 21.50 | 47.00 | 21.47 |
March | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
April | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 744.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
June | 429.67 | 23.74 | 154.00 | 23.77 | 107.00 | 23.77 |
July | 374.00 | 23.84 | 275.83 | 23.85 | 170.17 | 23.84 |
August | 332.00 | 23.84 | 218.83 | 23.86 | 119.67 | 23.86 |
September | 491.50 | 23.59 | 5.67 | 23.59 | 0.00 | 23.59 |
October | 744.00 | 22.50 | 19.67 | 22.46 | 19.67 | 22.42 |
November | 720.00 | 21.73 | 12.50 | 21.72 | 12.50 | 21.71 |
December | 744.00 | 21.30 | 155.17 | 21.25 | 155.17 | 21.21 |
Annual Sum or Average | 7459.17 | 22.27 | 913.67 | 22.36 | 656.17 | 22.38 |
Minimum of Months | 332.00 | 21.30 | 0.00 | 21.25 | 0.00 | 21.21 |
Maximum of Months | 744.00 | 23.84 | 275.83 | 23.86 | 170.17 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.83 | 21.19 | 354.17 | 21.08 | 352.50 | 21.01 |
February | 657.33 | 21.16 | 343.50 | 21.02 | 343.50 | 20.96 |
March | 710.17 | 21.28 | 358.17 | 21.25 | 345.17 | 21.19 |
April | 697.00 | 21.26 | 265.00 | 21.18 | 258.00 | 21.10 |
May | 621.50 | 21.67 | 87.50 | 21.96 | 33.33 | 21.97 |
June | 506.00 | 21.73 | 133.67 | 22.25 | 35.00 | 22.39 |
July | 540.50 | 21.86 | 146.33 | 22.37 | 68.17 | 22.56 |
August | 519.83 | 21.79 | 141.50 | 22.36 | 40.00 | 22.54 |
September | 524.50 | 21.77 | 102.00 | 22.27 | 25.33 | 22.38 |
October | 674.33 | 21.32 | 219.33 | 21.40 | 190.50 | 21.32 |
November | 691.17 | 21.22 | 271.67 | 21.10 | 269.67 | 21.02 |
December | 739.50 | 21.04 | 523.67 | 20.91 | 523.67 | 20.86 |
Annual Sum or Average | 7608.67 | 21.40 | 2946.50 | 21.47 | 2484.83 | 21.40 |
Minimum of Months | 506.00 | 21.04 | 87.50 | 20.91 | 25.33 | 20.86 |
Maximum of Months | 739.50 | 21.86 | 523.67 | 22.37 | 523.67 | 22.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 588.33 | 20.72 | 588.33 | 20.70 |
February | 672.00 | 20.82 | 507.00 | 20.73 | 507.00 | 20.70 |
March | 723.50 | 21.04 | 447.67 | 20.98 | 433.67 | 20.91 |
April | 706.17 | 21.13 | 298.33 | 21.04 | 288.83 | 20.95 |
May | 644.33 | 21.68 | 85.50 | 21.91 | 38.33 | 21.90 |
June | 517.33 | 21.77 | 121.17 | 22.25 | 35.17 | 22.39 |
July | 554.00 | 21.88 | 132.83 | 22.34 | 68.17 | 22.52 |
August | 561.00 | 21.85 | 101.33 | 22.27 | 40.50 | 22.44 |
September | 588.33 | 21.79 | 78.00 | 22.07 | 23.17 | 22.07 |
October | 708.67 | 21.15 | 275.00 | 21.09 | 258.50 | 20.98 |
November | 718.83 | 20.93 | 463.67 | 20.82 | 463.67 | 20.77 |
December | 744.00 | 20.71 | 675.00 | 20.67 | 675.00 | 20.65 |
Annual Sum or Average | 7882.17 | 21.25 | 3773.83 | 21.23 | 3420.33 | 21.14 |
Minimum of Months | 517.33 | 20.71 | 78.00 | 20.67 | 23.17 | 20.65 |
Maximum of Months | 744.00 | 21.88 | 675.00 | 22.34 | 675.00 | 22.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 643.50 | 21.25 | 133.00 | 21.26 | 109.50 | 21.21 |
February | 593.00 | 21.21 | 199.50 | 21.12 | 190.83 | 21.05 |
March | 659.17 | 21.19 | 206.83 | 21.16 | 189.33 | 21.06 |
April | 695.83 | 21.33 | 176.83 | 21.18 | 176.83 | 21.08 |
May | 705.33 | 21.85 | 12.33 | 21.84 | 12.00 | 21.83 |
June | 569.17 | 21.80 | 43.17 | 21.95 | 25.00 | 22.02 |
July | 574.67 | 21.84 | 93.67 | 22.13 | 53.00 | 22.25 |
August | 525.50 | 21.66 | 117.83 | 22.05 | 26.00 | 22.12 |
September | 491.50 | 21.58 | 94.50 | 22.01 | 1.00 | 22.01 |
October | 603.67 | 21.13 | 172.33 | 21.31 | 115.33 | 21.20 |
November | 617.67 | 21.26 | 140.00 | 21.28 | 108.67 | 21.21 |
December | 680.50 | 21.26 | 265.00 | 21.16 | 261.83 | 21.10 |
Annual Sum or Average | 7359.50 | 21.44 | 1655.00 | 21.49 | 1269.33 | 21.42 |
Minimum of Months | 491.50 | 21.13 | 12.33 | 21.12 | 1.00 | 21.05 |
Maximum of Months | 705.33 | 21.85 | 265.00 | 22.13 | 261.83 | 22.25 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 325.83 | 23.50 | 40.67 | 23.58 | 0.00 | 23.58 |
February | 310.00 | 23.48 | 34.33 | 23.55 | 0.00 | 23.55 |
March | 195.50 | 23.50 | 53.83 | 23.64 | 0.00 | 23.64 |
April | 128.50 | 23.51 | 187.33 | 23.84 | 0.00 | 23.84 |
May | 22.17 | 23.77 | 496.00 | 24.00 | 10.50 | 24.00 |
June | 141.00 | 24.00 | 690.00 | 24.00 | 141.00 | 24.00 |
July | 195.00 | 24.00 | 728.50 | 24.00 | 195.00 | 24.00 |
August | 165.17 | 24.00 | 710.67 | 24.00 | 165.17 | 24.00 |
September | 8.00 | 23.80 | 478.17 | 23.99 | 4.33 | 23.99 |
October | 122.67 | 23.36 | 146.50 | 23.75 | 0.00 | 23.75 |
November | 207.17 | 23.41 | 69.50 | 23.60 | 0.00 | 23.60 |
December | 446.33 | 23.40 | 2.33 | 23.41 | 0.00 | 23.41 |
Annual Sum or Average | 2267.33 | 23.57 | 3637.83 | 23.85 | 516.00 | 23.86 |
Minimum of Months | 8.00 | 23.36 | 2.33 | 23.41 | 0.00 | 23.41 |
Maximum of Months | 446.33 | 24.00 | 728.50 | 24.00 | 195.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 144.50 | 23.56 | 167.17 | 23.85 | 0.00 | 23.85 |
February | 168.83 | 23.53 | 102.83 | 23.75 | 0.00 | 23.75 |
March | 71.17 | 23.58 | 147.00 | 23.94 | 0.00 | 23.94 |
April | 33.83 | 23.47 | 310.50 | 24.01 | 0.00 | 24.01 |
May | 10.17 | 23.94 | 586.17 | 24.01 | 9.33 | 24.01 |
June | 134.00 | 24.00 | 707.00 | 24.00 | 134.00 | 24.00 |
July | 191.00 | 24.00 | 733.00 | 24.00 | 191.00 | 24.00 |
August | 160.50 | 24.00 | 733.33 | 24.00 | 160.50 | 24.00 |
September | 4.50 | 23.97 | 579.00 | 24.00 | 4.33 | 24.00 |
October | 47.67 | 23.24 | 267.67 | 23.93 | 0.00 | 23.93 |
November | 83.50 | 23.42 | 200.17 | 23.89 | 0.00 | 23.89 |
December | 272.83 | 23.45 | 21.33 | 23.51 | 0.00 | 23.51 |
Annual Sum or Average | 1322.50 | 23.68 | 4555.17 | 23.94 | 499.17 | 23.95 |
Minimum of Months | 4.50 | 23.24 | 21.33 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 272.83 | 24.00 | 733.33 | 24.01 | 191.00 | 24.01 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 507.67 | 24.28 | 709.50 | 24.22 | 498.33 | 24.25 |
February | 449.50 | 24.26 | 626.33 | 24.20 | 437.50 | 24.23 |
March | 512.83 | 24.23 | 725.50 | 24.18 | 508.17 | 24.20 |
April | 503.83 | 24.26 | 707.17 | 24.20 | 503.83 | 24.22 |
May | 546.83 | 24.06 | 743.83 | 24.04 | 546.83 | 24.05 |
June | 561.33 | 23.99 | 720.00 | 23.99 | 561.33 | 23.99 |
July | 603.33 | 23.99 | 744.00 | 23.99 | 603.33 | 23.99 |
August | 609.50 | 23.99 | 744.00 | 23.99 | 609.50 | 23.99 |
September | 524.00 | 24.01 | 719.83 | 24.00 | 524.00 | 24.00 |
October | 513.67 | 24.16 | 734.83 | 24.11 | 512.50 | 24.13 |
November | 495.50 | 24.28 | 697.50 | 24.21 | 490.33 | 24.24 |
December | 491.00 | 24.14 | 679.33 | 24.14 | 460.33 | 24.17 |
Annual Sum or Average | 6319.00 | 24.13 | 8551.83 | 24.10 | 6256.00 | 24.12 |
Minimum of Months | 449.50 | 23.99 | 626.33 | 23.99 | 437.50 | 23.99 |
Maximum of Months | 609.50 | 24.28 | 744.00 | 24.22 | 609.50 | 24.25 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.47 | 60.50 | 21.43 | 60.50 | 21.40 |
February | 672.00 | 21.49 | 97.67 | 21.43 | 97.67 | 21.38 |
March | 744.00 | 21.79 | 27.67 | 21.76 | 27.67 | 21.73 |
April | 720.00 | 21.72 | 7.00 | 21.71 | 7.00 | 21.71 |
May | 721.33 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
June | 258.83 | 23.48 | 180.67 | 23.64 | 59.83 | 23.65 |
July | 289.00 | 23.54 | 295.50 | 23.67 | 141.33 | 23.65 |
August | 269.50 | 23.46 | 269.00 | 23.64 | 86.00 | 23.64 |
September | 454.17 | 23.13 | 29.17 | 23.19 | 0.00 | 23.19 |
October | 731.17 | 22.20 | 28.83 | 22.15 | 28.83 | 22.11 |
November | 720.00 | 21.67 | 30.33 | 21.65 | 30.33 | 21.62 |
December | 744.00 | 21.31 | 165.83 | 21.25 | 165.83 | 21.21 |
Annual Sum or Average | 7068.00 | 22.07 | 1192.17 | 22.18 | 705.00 | 22.17 |
Minimum of Months | 258.83 | 21.31 | 0.00 | 21.25 | 0.00 | 21.21 |
Maximum of Months | 744.00 | 23.54 | 295.50 | 23.67 | 165.83 | 23.65 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.86990 | 24.46280 | 0.19318 | 5.86963 |
February | 672.00000 | 23.72790 | 23.29687 | 0.14448 | 5.56701 |
March | 744.00000 | 23.55365 | 22.78665 | 0.09475 | 5.35457 |
April | 720.00000 | 23.60905 | 26.76183 | 0.13448 | 5.56153 |
May | 744.00000 | 23.52239 | 31.04166 | -0.8201 | 19.44178 |
June | 720.00000 | 23.68637 | 38.17066 | -0.7039 | 15.71919 |
July | 744.00000 | 23.75327 | 40.55305 | -0.6618 | 14.49541 |
August | 744.00000 | 23.89589 | 39.54470 | -0.6025 | 12.83355 |
September | 720.00000 | 23.98032 | 28.52811 | -0.6309 | 13.45802 |
October | 744.00000 | 23.99365 | 23.84770 | 0.24447 | 6.30176 |
November | 720.00000 | 23.99491 | 24.83181 | 0.24936 | 6.34442 |
December | 744.00000 | 23.98029 | 18.86356 | 0.19805 | 5.85581 |
Annual Sum or Average | 8760.00000 | 23.79765 | 28.58956 | -0.1821 | 9.76192 |
Minimum of Months | 672.00000 | 23.52239 | 18.86356 | -0.8201 | 5.35457 |
Maximum of Months | 744.00000 | 23.99491 | 40.55305 | 0.24936 | 19.44178 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07503 | 25.51430 | -0.1600 | 8.93423 |
February | 672.00000 | 22.05509 | 23.82924 | -0.2011 | 9.51795 |
March | 744.00000 | 22.07141 | 23.27258 | -0.1991 | 8.73536 |
April | 720.00000 | 21.74350 | 28.11174 | -0.2727 | 8.53154 |
May | 744.00000 | 22.22515 | 31.85240 | -1.1151 | 33.24649 |
June | 720.00000 | 23.32649 | 37.65260 | -0.6320 | 15.02638 |
July | 744.00000 | 23.36744 | 40.26749 | -0.5973 | 14.08720 |
August | 744.00000 | 23.38012 | 39.72280 | -0.5764 | 13.81241 |
September | 720.00000 | 23.23892 | 29.06648 | -0.6942 | 18.25867 |
October | 744.00000 | 22.33367 | 25.50678 | -0.0837 | 8.49581 |
November | 720.00000 | 22.17398 | 26.68950 | -0.1232 | 8.71224 |
December | 744.00000 | 21.82425 | 20.07972 | -0.2986 | 10.24045 |
Annual Sum or Average | 8760.00000 | 22.48663 | 29.33021 | -0.4143 | 13.16843 |
Minimum of Months | 672.00000 | 21.74350 | 20.07972 | -1.1151 | 8.49581 |
Maximum of Months | 744.00000 | 23.38012 | 40.26749 | -0.0837 | 33.24649 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.07165 | 26.43779 | 0.03364 | 5.61894 |
February | 672.00000 | 22.84736 | 25.05552 | -0.0330 | 6.03641 |
March | 744.00000 | 23.03609 | 24.26376 | 0.01055 | 5.68623 |
April | 720.00000 | 22.97190 | 28.44221 | 0.01821 | 5.78408 |
May | 744.00000 | 23.51288 | 31.76017 | -0.7584 | 17.67253 |
June | 720.00000 | 23.90505 | 38.01256 | -0.5414 | 11.32007 |
July | 744.00000 | 23.91819 | 40.59246 | -0.5204 | 10.83442 |
August | 744.00000 | 23.91735 | 40.18796 | -0.5222 | 10.90262 |
September | 720.00000 | 23.87872 | 29.89427 | -0.6135 | 13.19358 |
October | 744.00000 | 23.33559 | 26.30193 | 0.10709 | 6.00047 |
November | 720.00000 | 23.12465 | 27.58756 | 0.05632 | 5.76539 |
December | 744.00000 | 22.68593 | 21.49980 | -0.0995 | 6.30819 |
Annual Sum or Average | 8760.00000 | 23.35327 | 30.03291 | -0.2399 | 8.77983 |
Minimum of Months | 672.00000 | 22.68593 | 21.49980 | -0.7584 | 5.61894 |
Maximum of Months | 744.00000 | 23.91819 | 40.59246 | 0.10709 | 17.67253 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73546 | 21.30884 | 0.75851 | 19.11486 |
February | 672.00000 | 23.68960 | 19.85023 | 0.73022 | 18.40226 |
March | 744.00000 | 23.75179 | 18.97390 | 0.75979 | 19.09468 |
April | 720.00000 | 23.77565 | 22.98145 | 0.79109 | 20.11721 |
May | 744.00000 | 23.71864 | 27.04899 | 0.18907 | 8.88966 |
June | 720.00000 | 23.72791 | 34.47038 | 0.30195 | 9.91407 |
July | 744.00000 | 23.73282 | 37.13994 | 0.31759 | 10.00120 |
August | 744.00000 | 23.71651 | 36.67699 | 0.30870 | 9.96739 |
September | 720.00000 | 23.71729 | 26.12984 | 0.21603 | 9.02899 |
October | 744.00000 | 23.71634 | 21.37777 | 0.78003 | 19.56330 |
November | 720.00000 | 23.74529 | 22.42657 | 0.77681 | 19.74527 |
December | 744.00000 | 23.65267 | 16.29180 | 0.68697 | 17.07896 |
Annual Sum or Average | 8760.00000 | 23.72341 | 25.42306 | 0.55026 | 15.05326 |
Minimum of Months | 672.00000 | 23.65267 | 16.29180 | 0.18907 | 8.88966 |
Maximum of Months | 744.00000 | 23.77565 | 37.13994 | 0.79109 | 20.11721 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.24379 | 29.28308 | 0.18655 | 7.94629 |
February | 672.00000 | 23.05110 | 27.92755 | 0.11066 | 8.37059 |
March | 744.00000 | 23.06071 | 27.39155 | 0.10551 | 7.56571 |
April | 720.00000 | 22.87168 | 31.91261 | 0.05726 | 7.06912 |
May | 744.00000 | 23.48878 | 35.23431 | -0.6369 | 14.55139 |
June | 720.00000 | 23.86358 | 41.32192 | -0.3766 | 8.36249 |
July | 744.00000 | 23.87949 | 43.85976 | -0.3475 | 7.96153 |
August | 744.00000 | 23.89731 | 43.13572 | -0.3203 | 7.69705 |
September | 720.00000 | 23.86151 | 32.84526 | -0.4042 | 9.54712 |
October | 744.00000 | 23.29767 | 29.30309 | 0.21242 | 8.46148 |
November | 720.00000 | 23.25248 | 30.40086 | 0.20270 | 8.19444 |
December | 744.00000 | 22.86596 | 24.48500 | 0.02533 | 8.03606 |
Annual Sum or Average | 8760.00000 | 23.38809 | 33.12290 | -0.1001 | 8.65309 |
Minimum of Months | 672.00000 | 22.86596 | 24.48500 | -0.6369 | 7.06912 |
Maximum of Months | 744.00000 | 23.89731 | 43.85976 | 0.21242 | 14.55139 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.59288 | 28.71649 | 0.19361 | 6.31790 |
February | 672.00000 | 23.38284 | 27.44351 | 0.12681 | 6.30589 |
March | 744.00000 | 23.45108 | 26.62585 | 0.14217 | 6.01764 |
April | 720.00000 | 23.36531 | 30.78616 | 0.14116 | 6.09280 |
May | 744.00000 | 23.73693 | 34.00039 | -0.6346 | 13.82525 |
June | 720.00000 | 23.92762 | 40.31063 | -0.4773 | 9.90452 |
July | 744.00000 | 23.94397 | 42.82727 | -0.4520 | 9.41668 |
August | 744.00000 | 23.95720 | 42.33649 | -0.4465 | 9.30147 |
September | 720.00000 | 23.95408 | 32.07540 | -0.5245 | 10.94015 |
October | 744.00000 | 23.62971 | 28.50732 | 0.21760 | 6.69678 |
November | 720.00000 | 23.59325 | 29.77695 | 0.20540 | 6.44750 |
December | 744.00000 | 23.25065 | 24.00015 | 0.06632 | 6.21728 |
Annual Sum or Average | 8760.00000 | 23.65031 | 32.31322 | -0.1217 | 8.13616 |
Minimum of Months | 672.00000 | 23.25065 | 24.00015 | -0.6346 | 6.01764 |
Maximum of Months | 744.00000 | 23.95720 | 42.82727 | 0.21760 | 13.82525 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32359 | 29.41717 | -0.4478 | 10.58396 |
February | 672.00000 | 21.26237 | 27.18384 | -0.4843 | 11.61699 |
March | 744.00000 | 21.44738 | 27.66298 | -0.4059 | 11.03718 |
April | 720.00000 | 21.38891 | 32.54236 | -0.3992 | 10.47295 |
May | 744.00000 | 22.07370 | 36.03998 | -1.2109 | 38.62869 |
June | 720.00000 | 22.31863 | 40.19050 | -0.9653 | 27.85354 |
July | 744.00000 | 22.37509 | 41.96985 | -0.9527 | 27.58771 |
August | 744.00000 | 22.38098 | 41.61139 | -0.9494 | 27.72068 |
September | 720.00000 | 22.40686 | 34.09304 | -1.0246 | 31.24160 |
October | 744.00000 | 21.63333 | 30.77072 | -0.3076 | 9.96462 |
November | 720.00000 | 21.36680 | 31.17279 | -0.4115 | 10.15773 |
December | 744.00000 | 21.12495 | 23.74611 | -0.5719 | 13.41091 |
Annual Sum or Average | 8760.00000 | 21.76140 | 33.06540 | -0.6789 | 19.24383 |
Minimum of Months | 672.00000 | 21.12495 | 23.74611 | -1.2109 | 9.96462 |
Maximum of Months | 744.00000 | 22.40686 | 41.96985 | -0.3076 | 38.62869 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88375 | 30.07715 | -0.6110 | 13.57042 |
February | 672.00000 | 20.88366 | 27.67697 | -0.6270 | 14.23640 |
March | 744.00000 | 21.20465 | 27.89477 | -0.5002 | 12.04042 |
April | 720.00000 | 21.23799 | 32.74421 | -0.4527 | 10.94187 |
May | 744.00000 | 22.00802 | 36.15596 | -1.2459 | 39.99674 |
June | 720.00000 | 22.32596 | 40.23793 | -0.9708 | 27.99379 |
July | 744.00000 | 22.36787 | 42.11160 | -0.9643 | 27.85936 |
August | 744.00000 | 22.33432 | 41.98743 | -0.9914 | 29.02794 |
September | 720.00000 | 22.26237 | 34.34816 | -1.1167 | 34.28078 |
October | 744.00000 | 21.37873 | 30.99261 | -0.4115 | 10.41709 |
November | 720.00000 | 21.00812 | 31.71950 | -0.5537 | 12.32290 |
December | 744.00000 | 20.78953 | 24.14157 | -0.7040 | 16.29097 |
Annual Sum or Average | 8760.00000 | 21.56096 | 33.37163 | -0.7634 | 20.79477 |
Minimum of Months | 672.00000 | 20.78953 | 24.14157 | -1.2459 | 10.41709 |
Maximum of Months | 744.00000 | 22.36787 | 42.11160 | -0.4115 | 39.99674 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86268 | 28.99397 | -0.5935 | 12.66697 |
February | 672.00000 | 20.84142 | 26.74283 | -0.6144 | 13.26184 |
March | 744.00000 | 21.04359 | 26.72156 | -0.5368 | 11.22934 |
April | 720.00000 | 21.14018 | 31.69511 | -0.4700 | 9.90223 |
May | 744.00000 | 21.63908 | 35.26803 | -1.4214 | 47.00205 |
June | 720.00000 | 22.05262 | 40.02562 | -1.1964 | 36.22214 |
July | 744.00000 | 22.10825 | 41.93190 | -1.1664 | 34.94284 |
August | 744.00000 | 22.00087 | 41.78017 | -1.2214 | 37.28537 |
September | 720.00000 | 21.82514 | 33.60103 | -1.3565 | 43.82499 |
October | 744.00000 | 21.12424 | 29.97647 | -0.4833 | 10.15317 |
November | 720.00000 | 20.93024 | 30.72784 | -0.5564 | 11.72791 |
December | 744.00000 | 20.80646 | 23.06999 | -0.6526 | 14.34359 |
Annual Sum or Average | 8760.00000 | 21.36752 | 32.57614 | -0.8573 | 23.61088 |
Minimum of Months | 672.00000 | 20.80646 | 23.06999 | -1.4214 | 9.90223 |
Maximum of Months | 744.00000 | 22.10825 | 41.93190 | -0.4700 | 47.00205 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.34241 | 29.38823 | -0.4468 | 10.46855 |
February | 672.00000 | 21.30090 | 27.11860 | -0.4745 | 11.51659 |
March | 744.00000 | 21.43219 | 27.56100 | -0.4022 | 10.29245 |
April | 720.00000 | 21.40435 | 32.37068 | -0.3853 | 9.88027 |
May | 744.00000 | 22.06650 | 35.89020 | -1.1988 | 37.39468 |
June | 720.00000 | 22.53650 | 39.82760 | -0.8832 | 26.70845 |
July | 744.00000 | 22.53610 | 41.67277 | -0.8771 | 25.94704 |
August | 744.00000 | 22.54518 | 41.11153 | -0.8757 | 26.35030 |
September | 720.00000 | 22.39345 | 33.94845 | -1.0164 | 30.39882 |
October | 744.00000 | 21.56044 | 30.68214 | -0.3246 | 9.40081 |
November | 720.00000 | 21.36556 | 31.15276 | -0.4162 | 10.15012 |
December | 744.00000 | 21.13315 | 23.71210 | -0.5707 | 13.32042 |
Annual Sum or Average | 8760.00000 | 21.80415 | 32.90099 | -0.6572 | 18.53424 |
Minimum of Months | 672.00000 | 21.13315 | 23.71210 | -1.1988 | 9.40081 |
Maximum of Months | 744.00000 | 22.54518 | 41.67277 | -0.3246 | 37.39468 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83032 | 30.09601 | -0.6249 | 13.79262 |
February | 672.00000 | 20.89759 | 27.58380 | -0.6213 | 14.14394 |
March | 744.00000 | 21.22114 | 27.74342 | -0.4892 | 11.25983 |
April | 720.00000 | 21.29445 | 32.52120 | -0.4301 | 10.32967 |
May | 744.00000 | 22.02415 | 35.96969 | -1.2272 | 38.55151 |
June | 720.00000 | 22.54193 | 39.90872 | -0.8891 | 26.95469 |
July | 744.00000 | 22.53287 | 41.78801 | -0.8877 | 26.28146 |
August | 744.00000 | 22.50667 | 41.37100 | -0.9148 | 27.43874 |
September | 720.00000 | 22.29047 | 34.17463 | -1.0949 | 33.09129 |
October | 744.00000 | 21.35484 | 30.88274 | -0.4186 | 10.02689 |
November | 720.00000 | 20.93918 | 31.77416 | -0.5718 | 12.62395 |
December | 744.00000 | 20.73420 | 24.14359 | -0.7155 | 16.50798 |
Annual Sum or Average | 8760.00000 | 21.60121 | 33.19325 | -0.7413 | 20.12506 |
Minimum of Months | 672.00000 | 20.73420 | 24.14359 | -1.2272 | 10.02689 |
Maximum of Months | 744.00000 | 22.54193 | 41.78801 | -0.4186 | 38.55151 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25026 | 29.71559 | -0.5013 | 11.89854 |
February | 672.00000 | 21.20854 | 27.45934 | -0.5319 | 12.88688 |
March | 744.00000 | 21.42372 | 27.94786 | -0.4383 | 12.31860 |
April | 720.00000 | 21.36706 | 32.84868 | -0.4264 | 11.61615 |
May | 744.00000 | 22.11117 | 36.31684 | -1.2094 | 39.51799 |
June | 720.00000 | 22.30985 | 40.46969 | -0.9592 | 28.17241 |
July | 744.00000 | 22.35882 | 42.30339 | -0.9524 | 28.16770 |
August | 744.00000 | 22.36813 | 42.14322 | -0.9465 | 28.34331 |
September | 720.00000 | 22.40360 | 34.36667 | -1.0344 | 32.56805 |
October | 744.00000 | 21.62314 | 31.04002 | -0.3389 | 11.18191 |
November | 720.00000 | 21.31567 | 31.46784 | -0.4562 | 11.30310 |
December | 744.00000 | 21.05179 | 23.95093 | -0.6291 | 15.07834 |
Annual Sum or Average | 8760.00000 | 21.73568 | 33.36822 | -0.7032 | 20.30773 |
Minimum of Months | 672.00000 | 21.05179 | 23.95093 | -1.2094 | 11.18191 |
Maximum of Months | 744.00000 | 22.40360 | 42.30339 | -0.3389 | 39.51799 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.79136 | 30.42274 | -0.6740 | 15.34824 |
February | 672.00000 | 20.81793 | 27.98428 | -0.6817 | 15.81150 |
March | 744.00000 | 21.17186 | 28.17902 | -0.5380 | 13.38166 |
April | 720.00000 | 21.21525 | 33.04945 | -0.4822 | 12.06510 |
May | 744.00000 | 22.04139 | 36.42294 | -1.2473 | 40.86954 |
June | 720.00000 | 22.31835 | 40.52181 | -0.9645 | 28.27383 |
July | 744.00000 | 22.35175 | 42.44903 | -0.9644 | 28.40873 |
August | 744.00000 | 22.31877 | 42.54218 | -0.9906 | 29.64663 |
September | 720.00000 | 22.24148 | 34.65855 | -1.1356 | 35.72772 |
October | 744.00000 | 21.33818 | 31.31353 | -0.4544 | 11.68204 |
November | 720.00000 | 20.93550 | 32.06336 | -0.6085 | 13.79594 |
December | 744.00000 | 20.71489 | 24.36154 | -0.7651 | 18.26303 |
Annual Sum or Average | 8760.00000 | 21.52546 | 33.69528 | -0.7930 | 21.98410 |
Minimum of Months | 672.00000 | 20.71489 | 24.36154 | -1.2473 | 11.68204 |
Maximum of Months | 744.00000 | 22.35175 | 42.54218 | -0.4544 | 40.86954 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.54314 | 30.99997 | -0.3116 | 9.28451 |
February | 672.00000 | 21.46404 | 28.88144 | -0.3690 | 10.39303 |
March | 744.00000 | 21.52607 | 29.35166 | -0.3550 | 10.33315 |
April | 720.00000 | 21.40146 | 34.00476 | -0.3889 | 10.00201 |
May | 744.00000 | 21.94449 | 37.19258 | -1.2793 | 40.89672 |
June | 720.00000 | 22.16639 | 41.22347 | -1.0784 | 31.75560 |
July | 744.00000 | 22.23624 | 42.74261 | -1.0407 | 30.43938 |
August | 744.00000 | 22.25447 | 42.28633 | -1.0169 | 29.58714 |
September | 720.00000 | 22.34480 | 34.96459 | -1.0400 | 31.36528 |
October | 744.00000 | 21.67930 | 32.36521 | -0.2590 | 9.66784 |
November | 720.00000 | 21.57072 | 32.78151 | -0.2890 | 9.13379 |
December | 744.00000 | 21.43580 | 25.47554 | -0.4182 | 10.99760 |
Annual Sum or Average | 8760.00000 | 21.79917 | 34.38559 | -0.6557 | 19.55096 |
Minimum of Months | 672.00000 | 21.40146 | 25.47554 | -1.2793 | 9.13379 |
Maximum of Months | 744.00000 | 22.34480 | 42.74261 | -0.2590 | 40.89672 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.79339 | 29.44288 | 0.23663 | 6.47844 |
February | 672.00000 | 23.76524 | 28.06736 | 0.21722 | 6.36462 |
March | 744.00000 | 23.88065 | 26.60792 | 0.26867 | 6.69028 |
April | 720.00000 | 23.92575 | 30.35020 | 0.31470 | 7.29948 |
May | 744.00000 | 23.99599 | 33.52107 | -0.4436 | 9.26643 |
June | 720.00000 | 23.99673 | 40.22572 | -0.3119 | 7.15328 |
July | 744.00000 | 23.99602 | 42.84644 | -0.2949 | 6.95447 |
August | 744.00000 | 23.99584 | 42.47288 | -0.3103 | 7.13746 |
September | 720.00000 | 23.99204 | 32.46615 | -0.4189 | 8.83581 |
October | 744.00000 | 23.89086 | 28.81979 | 0.30502 | 7.20767 |
November | 720.00000 | 23.83394 | 30.35483 | 0.26787 | 6.77410 |
December | 744.00000 | 23.65277 | 24.80158 | 0.15358 | 6.14019 |
Annual Sum or Average | 8760.00000 | 23.89384 | 32.52516 | -0.0027 | 7.19510 |
Minimum of Months | 672.00000 | 23.65277 | 24.80158 | -0.4436 | 6.14019 |
Maximum of Months | 744.00000 | 23.99673 | 42.84644 | 0.31470 | 9.26643 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.91625 | 28.50918 | 0.30665 | 7.16195 |
February | 672.00000 | 23.89357 | 27.13004 | 0.28863 | 6.96828 |
March | 744.00000 | 23.97243 | 25.77520 | 0.32996 | 7.37667 |
April | 720.00000 | 23.99946 | 29.53070 | 0.37261 | 8.05420 |
May | 744.00000 | 24.00700 | 32.94555 | -0.3901 | 8.30112 |
June | 720.00000 | 23.99694 | 39.84479 | -0.2729 | 6.68446 |
July | 744.00000 | 23.99623 | 42.47083 | -0.2565 | 6.52041 |
August | 744.00000 | 23.99623 | 42.07981 | -0.2716 | 6.67015 |
September | 720.00000 | 23.99565 | 32.00594 | -0.3763 | 8.11186 |
October | 744.00000 | 23.95873 | 28.07775 | 0.35640 | 7.82036 |
November | 720.00000 | 23.93426 | 29.45927 | 0.33119 | 7.45966 |
December | 744.00000 | 23.81189 | 23.88416 | 0.23310 | 6.57901 |
Annual Sum or Average | 8760.00000 | 23.95680 | 31.83802 | 0.05278 | 7.30887 |
Minimum of Months | 672.00000 | 23.81189 | 23.88416 | -0.3901 | 6.52041 |
Maximum of Months | 744.00000 | 24.00700 | 42.47083 | 0.37261 | 8.30112 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.12625 | 27.45118 | 1.00457 | 28.66954 |
February | 672.00000 | 24.08236 | 26.06899 | 0.97943 | 27.81893 |
March | 744.00000 | 24.11362 | 25.06291 | 1.01945 | 29.00606 |
April | 720.00000 | 24.14146 | 28.99014 | 1.05754 | 30.59304 |
May | 744.00000 | 24.03067 | 32.54610 | 0.57458 | 15.84593 |
June | 720.00000 | 23.99277 | 39.53843 | 0.71885 | 19.81934 |
July | 744.00000 | 23.99166 | 42.09192 | 0.73028 | 20.14808 |
August | 744.00000 | 23.99208 | 41.60573 | 0.72100 | 19.72068 |
September | 720.00000 | 23.99367 | 31.62456 | 0.60367 | 16.67170 |
October | 744.00000 | 24.06904 | 27.43971 | 1.03926 | 29.63649 |
November | 720.00000 | 24.12428 | 28.55321 | 1.02607 | 29.47212 |
December | 744.00000 | 24.02440 | 22.89010 | 0.91738 | 25.42747 |
Annual Sum or Average | 8760.00000 | 24.05658 | 31.18586 | 0.86523 | 24.37725 |
Minimum of Months | 672.00000 | 23.99166 | 22.89010 | 0.57458 | 15.84593 |
Maximum of Months | 744.00000 | 24.14146 | 42.09192 | 1.05754 | 30.59304 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30557 | 25.30086 | -0.4288 | 9.06723 |
February | 672.00000 | 21.26676 | 23.49462 | -0.4587 | 9.65417 |
March | 744.00000 | 21.53168 | 22.59498 | -0.3890 | 8.53723 |
April | 720.00000 | 21.57087 | 27.02605 | -0.3516 | 7.98359 |
May | 744.00000 | 22.57641 | 30.00867 | -1.1282 | 32.24908 |
June | 720.00000 | 23.67286 | 35.83227 | -0.7062 | 15.67645 |
July | 744.00000 | 23.75651 | 38.21635 | -0.6603 | 14.33484 |
August | 744.00000 | 23.63424 | 38.13240 | -0.7060 | 15.70769 |
September | 720.00000 | 23.29065 | 27.85795 | -0.8934 | 22.56529 |
October | 744.00000 | 22.01723 | 24.73926 | -0.2530 | 6.83212 |
November | 720.00000 | 21.46876 | 26.47632 | -0.3795 | 8.31122 |
December | 744.00000 | 21.21494 | 19.49141 | -0.4996 | 10.44694 |
Annual Sum or Average | 8760.00000 | 22.28136 | 28.29214 | -0.5720 | 13.47628 |
Minimum of Months | 672.00000 | 21.21494 | 19.49141 | -1.1282 | 6.83212 |
Maximum of Months | 744.00000 | 23.75651 | 38.21635 | -0.2530 | 32.24908 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.55878 | 28.45285 | -0.3632 | 8.07155 |
February | 672.00000 | 21.53443 | 26.69037 | -0.3866 | 8.57264 |
March | 744.00000 | 21.84450 | 25.80422 | -0.3108 | 7.68940 |
April | 720.00000 | 21.69487 | 30.34331 | -0.3203 | 7.55165 |
May | 744.00000 | 22.71981 | 33.25364 | -1.0873 | 30.49008 |
June | 720.00000 | 23.81450 | 38.92060 | -0.6610 | 14.34994 |
July | 744.00000 | 23.89841 | 41.21140 | -0.6152 | 13.07052 |
August | 744.00000 | 23.87723 | 41.01382 | -0.6247 | 13.32649 |
September | 720.00000 | 23.69159 | 30.75766 | -0.7608 | 17.66902 |
October | 744.00000 | 22.49575 | 27.73956 | -0.1372 | 6.26895 |
November | 720.00000 | 21.73291 | 29.59929 | -0.3141 | 7.48900 |
December | 744.00000 | 21.29862 | 22.92820 | -0.4687 | 9.81383 |
Annual Sum or Average | 8760.00000 | 22.51908 | 31.42047 | -0.5050 | 12.06158 |
Minimum of Months | 672.00000 | 21.29862 | 22.92820 | -1.0873 | 6.26895 |
Maximum of Months | 744.00000 | 23.89841 | 41.21140 | -0.1372 | 30.49008 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.46683 | 26.41689 | -0.3798 | 8.46988 |
February | 672.00000 | 21.49103 | 24.58462 | -0.3929 | 8.81079 |
March | 744.00000 | 21.78572 | 23.63707 | -0.3141 | 7.87955 |
April | 720.00000 | 21.71986 | 28.08744 | -0.3006 | 7.51743 |
May | 744.00000 | 22.70842 | 30.95150 | -1.0461 | 28.95617 |
June | 720.00000 | 23.74879 | 36.68425 | -0.6185 | 13.37925 |
July | 744.00000 | 23.77866 | 39.21330 | -0.5908 | 12.64451 |
August | 744.00000 | 23.72957 | 38.91030 | -0.6108 | 13.18644 |
September | 720.00000 | 23.42510 | 28.78798 | -0.7957 | 19.45326 |
October | 744.00000 | 22.22906 | 25.74480 | -0.1847 | 6.72991 |
November | 720.00000 | 21.67429 | 27.50194 | -0.3179 | 7.76251 |
December | 744.00000 | 21.30660 | 20.72194 | -0.4706 | 10.04756 |
Annual Sum or Average | 8760.00000 | 22.42723 | 29.29777 | -0.5027 | 12.09701 |
Minimum of Months | 672.00000 | 21.30660 | 20.72194 | -1.0461 | 6.72991 |
Maximum of Months | 744.00000 | 23.77866 | 39.21330 | -0.1847 | 28.95617 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.60667 | 24.58554 | -0.3611 | 8.10611 |
February | 672.00000 | 21.49343 | 22.90166 | -0.4049 | 8.87118 |
March | 744.00000 | 21.84047 | 21.98128 | -0.3206 | 7.66004 |
April | 720.00000 | 21.91823 | 26.23712 | -0.2764 | 7.12146 |
May | 744.00000 | 22.97987 | 29.10619 | -1.0093 | 27.06712 |
June | 720.00000 | 23.86855 | 35.11433 | -0.6475 | 13.95209 |
July | 744.00000 | 23.91593 | 37.53680 | -0.6127 | 13.00780 |
August | 744.00000 | 23.86190 | 37.41817 | -0.6372 | 13.71458 |
September | 720.00000 | 23.61783 | 27.09950 | -0.7955 | 18.93641 |
October | 744.00000 | 22.42026 | 23.94672 | -0.1657 | 6.20433 |
November | 720.00000 | 21.81727 | 25.68292 | -0.3030 | 7.35881 |
December | 744.00000 | 21.44983 | 18.95993 | -0.4433 | 9.48967 |
Annual Sum or Average | 8760.00000 | 22.57204 | 27.57489 | -0.4988 | 11.81423 |
Minimum of Months | 672.00000 | 21.44983 | 18.95993 | -1.0093 | 6.20433 |
Maximum of Months | 744.00000 | 23.91593 | 37.53680 | -0.1657 | 27.06712 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.159099E+11 | 66442.93 | 20-JAN-13:10 | 465.32 | 0.494211E+11 | 0.00 | 0.653310E+11 | 1.95 | 3.53 | 20-JAN-16:01 | 0.00 | 0.00 |
February | 0.122745E+11 | 62141.36 | 18-FEB-13:30 | 386.20 | 0.380670E+11 | 0.00 | 0.503415E+11 | 1.79 | 3.44 | 18-FEB-13:30 | 0.00 | 0.00 |
March | 0.205272E+11 | 99951.85 | 13-MAR-15:01 | 474.00 | 0.631921E+11 | 0.00 | 0.837193E+11 | 1.97 | 4.00 | 15-MAR-15:01 | 0.00 | 0.00 |
April | 0.160251E+11 | 84795.78 | 19-APR-15:01 | 453.34 | 0.472299E+11 | 0.00 | 0.632550E+11 | 1.93 | 3.95 | 19-APR-15:01 | 0.00 | 0.00 |
May | 0.555538E+11 | 114193.02 | 16-MAY-15:02 | 706.47 | 0.165388E+12 | 0.00 | 0.220942E+12 | 2.88 | 4.06 | 17-MAY-21:51 | 0.00 | 0.00 |
June | 0.152102E+12 | 193327.99 | 26-JUN-15:03 | 720.00 | 0.467286E+12 | 0.00 | 0.619388E+12 | 3.04 | 4.18 | 12-JUN-21:51 | 0.00 | 0.00 |
July | 0.167726E+12 | 158531.29 | 16-JUL-15:03 | 744.00 | 0.521528E+12 | 0.00 | 0.689254E+12 | 3.07 | 4.48 | 30-JUL-21:52 | 0.00 | 0.00 |
August | 0.154350E+12 | 178360.04 | 16-AUG-15:03 | 744.00 | 0.481165E+12 | 0.00 | 0.635516E+12 | 3.07 | 4.31 | 07-AUG-21:52 | 0.00 | 0.00 |
September | 0.112331E+12 | 147787.77 | 28-SEP-15:01 | 706.52 | 0.349404E+12 | 0.00 | 0.461735E+12 | 3.01 | 4.19 | 28-SEP-21:52 | 0.00 | 0.00 |
October | 0.324835E+11 | 121207.67 | 11-OCT-15:01 | 552.87 | 0.101083E+12 | 0.00 | 0.133567E+12 | 2.30 | 4.03 | 09-OCT-15:01 | 0.00 | 0.00 |
November | 0.186458E+11 | 69951.47 | 07-NOV-14:00 | 493.00 | 0.581529E+11 | 0.00 | 0.767987E+11 | 2.13 | 3.90 | 09-NOV-09:51 | 0.00 | 0.00 |
December | 0.120884E+11 | 63235.32 | 02-DEC-14:30 | 361.00 | 0.369720E+11 | 0.00 | 0.490604E+11 | 1.50 | 3.33 | 02-DEC-13:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.770017E+12 | 6806.71 | 0.237889E+13 | 0.00 | 0.314891E+13 | 2.39 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120884E+11 | 62141.36 | 361.00 | 0.369720E+11 | 0.00 | 0.490604E+11 | 1.50 | 3.33 | 0.00 | 0.00 | ||
Maximum of Months | 0.167726E+12 | 193327.99 | 744.00 | 0.521528E+12 | 0.00 | 0.689254E+12 | 3.07 | 4.48 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.910233E+11 | 0.00 | 690.26 | 214746.84 | 05-JAN-09:06 | 0.00 | 43.09 | 58.94 | 0.45 | 0.00 | 0.06 | 0.39 | 05-JAN-09:06 |
February | 0.944881E+11 | 0.00 | 625.15 | 186268.67 | 12-FEB-07:10 | 0.00 | 42.08 | 58.98 | 0.49 | 0.00 | 0.07 | 0.33 | 12-FEB-07:10 |
March | 0.652511E+11 | 0.00 | 590.86 | 183546.31 | 19-MAR-08:04 | 0.00 | 41.20 | 55.39 | 0.33 | 0.00 | 0.04 | 0.33 | 19-MAR-08:04 |
April | 0.571473E+11 | 0.00 | 559.24 | 194363.43 | 15-APR-18:02 | 0.00 | 39.31 | 54.27 | 0.29 | 0.00 | 0.04 | 0.35 | 15-APR-18:02 |
May | 0.155613E+11 | 0.00 | 301.17 | 146127.48 | 02-MAY-08:62 | 0.00 | 35.82 | 44.75 | 0.08 | 0.00 | 0.01 | 0.26 | 02-MAY-08:62 |
June | 0.502079E+09 | 0.00 | 16.71 | 98382.49 | 09-JUN-03:56 | 0.00 | 38.69 | 39.21 | 0.00 | 0.00 | 0.00 | 0.18 | 09-JUN-03:56 |
July | 0.386052E+09 | 0.00 | 17.46 | 48162.43 | 04-JUL-21:54 | 0.00 | 38.57 | 39.16 | 0.00 | 0.00 | 0.00 | 0.09 | 04-JUL-21:54 |
August | 0.333814E+09 | 0.00 | 16.04 | 48368.10 | 17-AUG-08:53 | 0.00 | 40.79 | 41.23 | 0.00 | 0.00 | 0.00 | 0.09 | 17-AUG-08:53 |
September | 0.430632E+10 | 0.00 | 97.72 | 143253.46 | 21-SEP-18:57 | 0.00 | 39.69 | 42.46 | 0.02 | 0.00 | 0.00 | 0.26 | 21-SEP-18:57 |
October | 0.546389E+11 | 0.00 | 505.82 | 167992.19 | 31-OCT-15:06 | 0.00 | 40.23 | 52.70 | 0.27 | 0.00 | 0.04 | 0.30 | 31-OCT-15:06 |
November | 0.720473E+11 | 0.00 | 625.97 | 169608.79 | 26-NOV-16:03 | 0.00 | 42.43 | 57.42 | 0.38 | 0.00 | 0.05 | 0.30 | 26-NOV-16:03 |
December | 0.142101E+12 | 0.00 | 695.03 | 266895.97 | 21-DEC-09:13 | 0.00 | 41.76 | 59.13 | 0.62 | 0.00 | 0.10 | 0.48 | 21-DEC-09:13 |
Annual Sum or Average | 0.597787E+12 | 0.00 | 4741.44 | 0.00 | 40.29 | 50.25 | 0.24 | 0.00 | 0.03 | ||||
Minimum of Months | 0.333814E+09 | 0.00 | 16.04 | 48162.43 | 0.00 | 35.82 | 39.16 | 0.00 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.142101E+12 | 0.00 | 695.03 | 266895.97 | 0.00 | 43.09 | 59.13 | 0.62 | 0.00 | 0.10 | 0.48 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.608306E+10 | 0.00 | 150.17 | 0.608306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125900.60 | 20-JAN-13:00 | 125900.60 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 |
February | 0.348979E+10 | 0.00 | 110.66 | 0.348979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114211.36 | 18-FEB-13:00 | 114211.36 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.186262E+11 | 0.00 | 197.97 | 0.186262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156078.96 | 14-MAR-13:00 | 156078.96 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.194588E+11 | 0.00 | 191.30 | 0.194588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108781.00 | 20-APR-13:00 | 108781.00 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.890709E+11 | 0.00 | 363.83 | 0.890709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202729.19 | 31-MAY-18:06 | 202729.19 | 31-MAY-18:06 | 0.00 | 0.00 | 0.00 |
June | 0.289771E+12 | 0.00 | 662.54 | 0.287127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286350.21 | 26-JUN-18:15 | 286350.21 | 26-JUN-18:15 | 0.00 | 0.00 | 0.00 |
July | 0.331797E+12 | 0.00 | 707.36 | 0.316696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271505.78 | 30-JUL-10:40 | 264004.81 | 17-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.297342E+12 | 0.00 | 690.39 | 0.292054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 269522.92 | 16-AUG-18:15 | 269522.92 | 16-AUG-18:15 | 0.00 | 0.00 | 0.00 |
September | 0.207123E+12 | 0.00 | 537.75 | 0.207123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236782.06 | 12-SEP-18:20 | 236782.06 | 12-SEP-18:20 | 0.00 | 0.00 | 0.00 |
October | 0.343237E+11 | 0.00 | 232.18 | 0.343237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179667.17 | 11-OCT-15:10 | 179667.17 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.116144E+11 | 0.00 | 174.46 | 0.116144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138561.52 | 06-NOV-13:00 | 138561.52 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.777872E+10 | 0.00 | 141.24 | 0.777872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118131.66 | 02-DEC-13:00 | 118131.66 | 02-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131648E+13 | 0.00 | 4159.86 | 0.129345E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.348979E+10 | 0.00 | 110.66 | 0.348979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108781.00 | 108781.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.331797E+12 | 0.00 | 707.36 | 0.316696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286350.21 | 286350.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.806506E+09 | 0.00 | 29.37 | 0.806506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18772.42 | 20-JAN-14:00 | 18772.42 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.433400E+09 | 0.00 | 16.50 | 0.433400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15786.59 | 18-FEB-14:00 | 15786.59 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.270944E+10 | 0.00 | 84.85 | 0.270944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22841.19 | 14-MAR-13:00 | 22841.19 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.323868E+10 | 0.00 | 97.85 | 0.323868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20853.69 | 20-APR-13:00 | 20853.69 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.145294E+11 | 0.00 | 301.25 | 0.145294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26465.04 | 17-MAY-14:00 | 26465.04 | 17-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.429232E+11 | 0.00 | 663.67 | 0.417028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36862.46 | 21-JUN-17:10 | 31797.23 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.508285E+11 | 0.00 | 705.67 | 0.465922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40912.32 | 30-JUL-15:19 | 30562.15 | 16-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.441315E+11 | 0.00 | 691.50 | 0.420448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40916.51 | 05-AUG-14:40 | 30599.28 | 16-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.305248E+11 | 0.00 | 522.67 | 0.305248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28386.96 | 10-SEP-13:00 | 28386.96 | 10-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.512786E+10 | 0.00 | 132.52 | 0.512786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24666.44 | 11-OCT-14:00 | 24666.44 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.173917E+10 | 0.00 | 48.00 | 0.173917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20791.18 | 07-NOV-15:00 | 20791.18 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.121725E+10 | 0.00 | 37.37 | 0.121725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20813.10 | 02-DEC-15:00 | 20813.10 | 02-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198210E+12 | 0.00 | 3331.21 | 0.190666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.433400E+09 | 0.00 | 16.50 | 0.433400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15786.59 | 15786.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.508285E+11 | 0.00 | 705.67 | 0.465922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40916.51 | 31797.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.107061E+10 | 0.00 | 173.86 | 0.106706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22990.34 | 20-JAN-17:11 | 22990.34 | 20-JAN-17:11 | 0.00 | 0.00 | 0.00 |
February | 0.118230E+10 | 0.00 | 164.72 | 0.118197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22385.12 | 26-FEB-17:51 | 22385.12 | 26-FEB-17:51 | 0.00 | 0.00 | 0.00 |
March | 0.213628E+10 | 0.00 | 249.41 | 0.213203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24972.41 | 08-MAR-17:11 | 24972.41 | 08-MAR-17:11 | 0.00 | 0.00 | 0.00 |
April | 0.133481E+10 | 0.00 | 215.00 | 0.121640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24889.25 | 08-APR-18:01 | 24889.25 | 08-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.327331E+10 | 0.00 | 453.62 | 0.238926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24766.82 | 27-MAY-16:11 | 24766.82 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.867976E+10 | 0.00 | 540.99 | 0.644801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25044.83 | 22-JUN-21:51 | 23591.22 | 06-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.818964E+10 | 0.00 | 543.59 | 0.565881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25403.78 | 31-JUL-21:51 | 23793.38 | 01-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.845166E+10 | 0.00 | 545.94 | 0.591708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24975.69 | 13-AUG-21:51 | 24975.69 | 13-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.629342E+10 | 0.00 | 497.61 | 0.511488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24396.48 | 15-SEP-19:51 | 24396.48 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.298917E+10 | 0.00 | 353.90 | 0.281919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24974.42 | 14-OCT-16:11 | 24974.42 | 14-OCT-16:11 | 0.00 | 0.00 | 0.00 |
November | 0.149550E+10 | 0.00 | 219.84 | 0.145305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22405.71 | 07-NOV-17:41 | 22405.71 | 07-NOV-17:41 | 0.00 | 0.00 | 0.00 |
December | 0.676368E+09 | 0.00 | 117.45 | 0.676368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21648.56 | 29-DEC-16:01 | 21648.56 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457728E+11 | 0.00 | 4075.95 | 0.360741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.676368E+09 | 0.00 | 117.45 | 0.676368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21648.56 | 21648.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.867976E+10 | 0.00 | 545.94 | 0.644801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25403.78 | 24975.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.153006E+09 | 0.00 | 38.75 | 0.152776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21181.01 | 22-JAN-16:01 | 21181.01 | 22-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.258242E+09 | 0.00 | 47.92 | 0.258242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21180.58 | 23-FEB-16:01 | 21180.58 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.960464E+09 | 0.00 | 159.15 | 0.959409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23865.85 | 15-MAR-18:31 | 23865.85 | 15-MAR-18:31 | 0.00 | 0.00 | 0.00 |
April | 0.788429E+09 | 0.00 | 151.87 | 0.700783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24096.12 | 08-APR-18:01 | 24096.12 | 08-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.284034E+10 | 0.00 | 425.39 | 0.201763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23920.77 | 27-MAY-16:11 | 23920.77 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.833960E+10 | 0.00 | 537.55 | 0.621221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24445.88 | 22-JUN-21:51 | 23034.56 | 27-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.775283E+10 | 0.00 | 539.65 | 0.534740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24699.74 | 31-JUL-21:51 | 23260.68 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.726250E+10 | 0.00 | 534.64 | 0.496110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24078.40 | 13-AUG-21:51 | 24078.40 | 13-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.463377E+10 | 0.00 | 460.47 | 0.360785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23058.64 | 15-SEP-19:51 | 23058.64 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.129111E+10 | 0.00 | 211.89 | 0.121342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23520.47 | 14-OCT-16:11 | 23520.47 | 14-OCT-16:11 | 0.00 | 0.00 | 0.00 |
November | 0.282726E+09 | 0.00 | 67.53 | 0.277980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21193.29 | 04-NOV-15:01 | 21193.29 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 58714387.70 | 0.00 | 20.38 | 58714387.70 | 0.00 | 0.00 | 0.00 | 0.00 | 21142.13 | 03-DEC-16:01 | 21142.13 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346217E+11 | 0.00 | 3195.18 | 0.257675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 58714387.70 | 0.00 | 20.38 | 58714387.70 | 0.00 | 0.00 | 0.00 | 0.00 | 21142.13 | 21142.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.833960E+10 | 0.00 | 539.65 | 0.621221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24699.74 | 24096.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.275811E+11 | 0.00 | 325.94 | 0.275811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65843.61 | 20-JAN-12:30 | 65843.61 | 20-JAN-12:30 | 0.00 | 0.00 | 0.00 |
February | 0.205023E+11 | 0.00 | 257.21 | 0.205023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62700.78 | 18-FEB-12:50 | 62700.78 | 18-FEB-12:50 | 0.00 | 0.00 | 0.00 |
March | 0.195207E+11 | 0.00 | 266.87 | 0.195171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57151.40 | 11-MAR-13:00 | 57151.40 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.498448E+10 | 0.00 | 123.78 | 0.494940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32959.04 | 08-APR-13:00 | 32959.04 | 08-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.108168E+11 | 0.00 | 367.67 | 0.916952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22596.07 | 16-MAY-13:20 | 22596.07 | 16-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.298306E+11 | 0.00 | 601.44 | 0.220881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30972.72 | 14-JUN-13:30 | 30972.72 | 14-JUN-13:30 | 0.00 | 0.00 | 0.00 |
July | 0.333129E+11 | 0.00 | 641.00 | 0.239975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35149.94 | 23-JUL-13:00 | 31391.11 | 18-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.397581E+11 | 0.00 | 654.04 | 0.287754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44600.64 | 31-AUG-12:40 | 44600.64 | 31-AUG-12:40 | 0.00 | 0.00 | 0.00 |
September | 0.403871E+11 | 0.00 | 605.68 | 0.370935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59408.76 | 28-SEP-13:00 | 59408.76 | 28-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.316041E+11 | 0.00 | 358.30 | 0.314504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61475.91 | 10-OCT-12:30 | 61475.91 | 10-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.270715E+11 | 0.00 | 318.69 | 0.270698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66174.24 | 07-NOV-12:10 | 66174.24 | 07-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.171775E+11 | 0.00 | 200.08 | 0.171775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59619.54 | 17-DEC-12:10 | 59619.54 | 17-DEC-12:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302547E+12 | 0.00 | 4720.71 | 0.269372E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.498448E+10 | 0.00 | 123.78 | 0.494940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22596.07 | 22596.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.403871E+11 | 0.00 | 654.04 | 0.370935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66174.24 | 66174.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.780103E+09 | 0.00 | 64.64 | 0.753945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104253.41 | 21-JAN-09:01 | 104253.41 | 21-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.778115E+09 | 0.00 | 56.65 | 0.774202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 103728.07 | 19-FEB-09:01 | 103728.07 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.470935E+10 | 0.00 | 180.28 | 0.461287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112468.48 | 14-MAR-20:51 | 112468.48 | 14-MAR-20:51 | 0.00 | 0.00 | 0.00 |
April | 0.685286E+10 | 0.00 | 244.32 | 0.529950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114143.37 | 20-APR-20:31 | 114143.37 | 20-APR-20:31 | 0.00 | 0.00 | 0.00 |
May | 0.249425E+11 | 0.00 | 409.47 | 0.186392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116770.43 | 17-MAY-21:51 | 116770.43 | 17-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.488259E+11 | 0.00 | 446.45 | 0.384146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127925.56 | 20-JUN-21:51 | 117383.69 | 06-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.500541E+11 | 0.00 | 463.15 | 0.380016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130789.06 | 31-JUL-21:51 | 119513.40 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.435478E+11 | 0.00 | 423.93 | 0.311791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124599.05 | 29-AUG-21:51 | 119299.86 | 01-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.283710E+11 | 0.00 | 372.68 | 0.233240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117395.68 | 09-SEP-21:51 | 117395.68 | 09-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.728878E+10 | 0.00 | 267.63 | 0.649353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111722.16 | 10-OCT-20:31 | 111722.16 | 10-OCT-20:31 | 0.00 | 0.00 | 0.00 |
November | 0.178996E+10 | 0.00 | 100.83 | 0.164854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104441.99 | 09-NOV-19:01 | 104441.99 | 09-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.568888E+09 | 0.00 | 44.54 | 0.568888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83568.81 | 02-DEC-09:01 | 83568.81 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218509E+12 | 0.00 | 3074.58 | 0.169710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.568888E+09 | 0.00 | 44.54 | 0.568888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83568.81 | 83568.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.500541E+11 | 0.00 | 463.15 | 0.384146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130789.06 | 119513.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.107308E+10 | 0.00 | 159.00 | 0.106653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19013.32 | 22-JAN-09:01 | 19013.32 | 22-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.134892E+10 | 0.00 | 181.46 | 0.134889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19017.56 | 23-FEB-09:01 | 19017.56 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.244548E+10 | 0.00 | 272.48 | 0.242707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20242.60 | 15-MAR-18:31 | 20242.60 | 15-MAR-18:31 | 0.00 | 0.00 | 0.00 |
April | 0.178114E+10 | 0.00 | 239.26 | 0.163436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21955.31 | 19-APR-08:51 | 21955.31 | 19-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.382053E+10 | 0.00 | 494.75 | 0.292947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21977.58 | 17-MAY-08:51 | 21977.58 | 17-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.900118E+10 | 0.00 | 559.77 | 0.681256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21967.13 | 07-JUN-08:41 | 21967.13 | 07-JUN-08:41 | 0.00 | 0.00 | 0.00 |
July | 0.910075E+10 | 0.00 | 560.17 | 0.662717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23156.39 | 01-JUL-07:42 | 23156.39 | 01-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.929588E+10 | 0.00 | 565.75 | 0.679398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22965.93 | 04-AUG-08:32 | 21969.64 | 19-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.677576E+10 | 0.00 | 512.79 | 0.567032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21960.47 | 07-SEP-08:51 | 21960.47 | 07-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.302628E+10 | 0.00 | 349.82 | 0.286688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21927.29 | 11-OCT-08:51 | 21927.29 | 11-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.146386E+10 | 0.00 | 211.00 | 0.140472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21483.53 | 09-NOV-09:51 | 21483.53 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.702487E+09 | 0.00 | 123.96 | 0.702487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18994.00 | 16-DEC-09:01 | 18994.00 | 16-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498353E+11 | 0.00 | 4230.23 | 0.402844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.702487E+09 | 0.00 | 123.96 | 0.702487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18994.00 | 18994.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.929588E+10 | 0.00 | 565.75 | 0.681256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23156.39 | 23156.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.194174E+09 | 0.00 | 39.46 | 0.188678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18211.12 | 20-JAN-09:02 | 18211.12 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.396369E+09 | 0.00 | 64.46 | 0.396369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18587.24 | 23-FEB-09:01 | 18587.24 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.117327E+10 | 0.00 | 174.04 | 0.116006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18983.77 | 14-MAR-20:51 | 18983.77 | 14-MAR-20:51 | 0.00 | 0.00 | 0.00 |
April | 0.118463E+10 | 0.00 | 181.11 | 0.106140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21455.74 | 19-APR-08:51 | 21455.74 | 19-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.334973E+10 | 0.00 | 459.62 | 0.252327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21480.31 | 17-MAY-08:51 | 21480.31 | 17-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.864166E+10 | 0.00 | 559.63 | 0.652023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22036.02 | 27-JUN-08:32 | 22036.02 | 27-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.865266E+10 | 0.00 | 559.19 | 0.625219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23504.49 | 01-JUL-07:42 | 23504.49 | 01-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.807898E+10 | 0.00 | 563.91 | 0.568178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22477.37 | 04-AUG-08:32 | 21472.96 | 19-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.505683E+10 | 0.00 | 495.99 | 0.403251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21461.61 | 07-SEP-08:51 | 21461.61 | 07-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.127514E+10 | 0.00 | 206.26 | 0.117255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21270.66 | 11-OCT-08:51 | 21270.66 | 11-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.362807E+09 | 0.00 | 64.64 | 0.328220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19153.87 | 09-NOV-09:51 | 19153.87 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.116859E+09 | 0.00 | 24.75 | 0.116859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18073.86 | 02-DEC-09:01 | 18073.86 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384831E+11 | 0.00 | 3393.07 | 0.294341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.116859E+09 | 0.00 | 24.75 | 0.116859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18073.86 | 18073.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.865266E+10 | 0.00 | 563.91 | 0.652023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23504.49 | 23504.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.250440E+09 | 0.00 | 136.17 | 0.249940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6326.29 | 20-JAN-17:11 | 6326.29 | 20-JAN-17:11 | 0.00 | 0.00 | 0.00 |
February | 0.285597E+09 | 0.00 | 132.93 | 0.285385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6089.19 | 26-FEB-17:51 | 6089.19 | 26-FEB-17:51 | 0.00 | 0.00 | 0.00 |
March | 0.533783E+09 | 0.00 | 215.71 | 0.533706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6644.44 | 31-MAR-18:41 | 6644.44 | 31-MAR-18:41 | 0.00 | 0.00 | 0.00 |
April | 0.348752E+09 | 0.00 | 188.30 | 0.321696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6634.63 | 08-APR-18:01 | 6634.63 | 08-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.804651E+09 | 0.00 | 404.08 | 0.609767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6645.80 | 27-MAY-16:11 | 6645.80 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.225064E+10 | 0.00 | 541.96 | 0.169368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6794.05 | 22-JUN-21:51 | 6270.33 | 27-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.209292E+10 | 0.00 | 544.76 | 0.145911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6885.57 | 31-JUL-21:51 | 6311.62 | 01-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.216323E+10 | 0.00 | 545.48 | 0.153560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6655.60 | 13-AUG-21:51 | 6655.60 | 13-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.153613E+10 | 0.00 | 486.29 | 0.125442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6615.61 | 15-SEP-19:51 | 6615.61 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.692102E+09 | 0.00 | 286.12 | 0.659230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6640.72 | 21-OCT-16:51 | 6640.72 | 21-OCT-16:51 | 0.00 | 0.00 | 0.00 |
November | 0.353871E+09 | 0.00 | 171.51 | 0.347567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6247.55 | 05-NOV-17:41 | 6247.55 | 05-NOV-17:41 | 0.00 | 0.00 | 0.00 |
December | 0.156995E+09 | 0.00 | 98.07 | 0.156995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5745.40 | 29-DEC-16:01 | 5745.40 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114691E+11 | 0.00 | 3751.37 | 0.910710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.156995E+09 | 0.00 | 98.07 | 0.156995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5745.40 | 5745.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.225064E+10 | 0.00 | 545.48 | 0.169368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6885.57 | 6655.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 32370765.81 | 0.00 | 25.59 | 32309627.75 | 0.00 | 0.00 | 0.00 | 0.00 | 5611.92 | 20-JAN-17:11 | 5611.92 | 20-JAN-17:11 | 0.00 | 0.00 | 0.00 |
February | 59583240.31 | 0.00 | 36.87 | 59564509.69 | 0.00 | 0.00 | 0.00 | 0.00 | 5612.23 | 23-FEB-16:01 | 5612.23 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.227909E+09 | 0.00 | 130.93 | 0.227836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6461.77 | 15-MAR-18:31 | 6461.77 | 15-MAR-18:31 | 0.00 | 0.00 | 0.00 |
April | 0.201886E+09 | 0.00 | 129.04 | 0.182716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6473.00 | 08-APR-18:01 | 6473.00 | 08-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.683624E+09 | 0.00 | 374.77 | 0.506482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6433.92 | 27-MAY-16:11 | 6433.92 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.216096E+10 | 0.00 | 539.28 | 0.162687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6623.60 | 22-JUN-21:51 | 6132.91 | 27-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.197769E+10 | 0.00 | 541.01 | 0.137547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6673.84 | 31-JUL-21:51 | 6152.49 | 01-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.184616E+10 | 0.00 | 535.21 | 0.128148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6471.88 | 13-AUG-21:51 | 6471.88 | 13-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.109486E+10 | 0.00 | 447.86 | 0.857649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6246.84 | 15-SEP-19:51 | 6246.84 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.272518E+09 | 0.00 | 156.34 | 0.262279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6305.05 | 08-OCT-18:11 | 6305.05 | 08-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 62308474.64 | 0.00 | 52.35 | 62121183.94 | 0.00 | 0.00 | 0.00 | 0.00 | 5614.09 | 18-NOV-16:01 | 5614.09 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 13798450.93 | 0.00 | 14.43 | 13798450.93 | 0.00 | 0.00 | 0.00 | 0.00 | 5602.05 | 03-DEC-16:01 | 5602.05 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.863366E+10 | 0.00 | 2983.70 | 0.648858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13798450.93 | 0.00 | 14.43 | 13798450.93 | 0.00 | 0.00 | 0.00 | 0.00 | 5602.05 | 5602.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.216096E+10 | 0.00 | 541.01 | 0.162687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6673.84 | 6473.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.679991E+10 | 0.00 | 362.55 | 0.668404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28623.39 | 20-JAN-17:11 | 28623.39 | 20-JAN-17:11 | 0.00 | 0.00 | 0.00 |
February | 0.549784E+10 | 0.00 | 307.62 | 0.542013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26868.04 | 26-FEB-17:51 | 26868.04 | 26-FEB-17:51 | 0.00 | 0.00 | 0.00 |
March | 0.544656E+10 | 0.00 | 332.14 | 0.541913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29011.57 | 13-MAR-19:21 | 29011.57 | 13-MAR-19:21 | 0.00 | 0.00 | 0.00 |
April | 0.256906E+10 | 0.00 | 261.16 | 0.233959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26869.20 | 20-APR-20:31 | 26869.20 | 20-APR-20:31 | 0.00 | 0.00 | 0.00 |
May | 0.426562E+10 | 0.00 | 455.05 | 0.316111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26390.19 | 09-MAY-20:31 | 26390.19 | 09-MAY-20:31 | 0.00 | 0.00 | 0.00 |
June | 0.967476E+10 | 0.00 | 538.00 | 0.694069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28603.05 | 20-JUN-21:51 | 26795.41 | 06-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.102882E+11 | 0.00 | 542.14 | 0.709347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29458.73 | 31-JUL-21:51 | 26773.62 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.117773E+11 | 0.00 | 548.17 | 0.845039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28120.53 | 29-AUG-21:51 | 27453.37 | 13-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.105406E+11 | 0.00 | 505.93 | 0.895910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29040.01 | 25-SEP-20:41 | 29040.01 | 25-SEP-20:41 | 0.00 | 0.00 | 0.00 |
October | 0.771783E+10 | 0.00 | 419.79 | 0.736550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29037.89 | 09-OCT-19:51 | 29037.89 | 09-OCT-19:51 | 0.00 | 0.00 | 0.00 |
November | 0.705143E+10 | 0.00 | 386.33 | 0.672166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28881.97 | 05-NOV-17:41 | 28881.97 | 05-NOV-17:41 | 0.00 | 0.00 | 0.00 |
December | 0.494476E+10 | 0.00 | 268.83 | 0.494476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26807.81 | 02-DEC-17:21 | 26807.81 | 02-DEC-17:21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.865739E+11 | 0.00 | 4927.71 | 0.734996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.256906E+10 | 0.00 | 261.16 | 0.233959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26390.19 | 26390.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117773E+11 | 0.00 | 548.17 | 0.895910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29458.73 | 29040.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1420.50 | 1169.35 | 251.15 | 1584.94 | 674.33 | 0.00 | 0.00 | 0.00 |
February | 1344.14 | 1068.74 | 275.40 | 1484.47 | 707.80 | 0.00 | 0.00 | 0.00 |
March | 1009.67 | 667.29 | 342.38 | 1127.54 | 565.27 | 0.00 | 0.00 | 0.00 |
April | 661.13 | 273.51 | 387.62 | 674.43 | 507.55 | 0.00 | 0.00 | 0.00 |
May | 600.77 | 115.53 | 485.24 | 683.40 | 290.80 | 0.00 | 0.00 | 0.00 |
June | 546.20 | 98.60 | 447.60 | 779.62 | 156.66 | 0.00 | 0.00 | 0.00 |
July | 564.16 | 96.11 | 468.05 | 809.55 | 140.16 | 0.00 | 0.00 | 0.00 |
August | 717.82 | 295.32 | 422.50 | 1028.58 | 163.71 | 0.00 | 0.00 | 0.00 |
September | 942.92 | 530.01 | 412.91 | 1260.35 | 256.78 | 0.00 | 0.00 | 0.00 |
October | 1113.04 | 788.63 | 324.41 | 1320.37 | 546.17 | 0.00 | 0.00 | 0.00 |
November | 1364.27 | 1088.18 | 276.09 | 1564.95 | 633.09 | 0.00 | 0.00 | 0.00 |
December | 1301.97 | 1053.98 | 247.99 | 1421.09 | 769.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.39 | 601.11 | 362.28 | 1142.97 | 449.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 546.20 | 96.11 | 247.99 | 674.43 | 140.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1420.50 | 1169.35 | 485.24 | 1584.94 | 769.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4000.02 | 3292.81 | 707.21 | 4421.27 | 2005.73 | 0.00 | 0.00 | 0.00 |
February | 3785.00 | 3009.49 | 775.51 | 4140.53 | 2087.16 | 0.00 | 0.00 | 0.00 |
March | 2843.17 | 1879.05 | 964.11 | 3138.77 | 1685.02 | 0.00 | 0.00 | 0.00 |
April | 1861.71 | 770.19 | 1091.52 | 1862.11 | 1536.70 | 0.00 | 0.00 | 0.00 |
May | 1691.72 | 325.32 | 1366.40 | 1868.30 | 908.46 | 0.00 | 0.00 | 0.00 |
June | 1538.07 | 277.65 | 1260.42 | 2164.17 | 471.17 | 0.00 | 0.00 | 0.00 |
July | 1588.64 | 270.64 | 1318.00 | 2248.60 | 424.54 | 0.00 | 0.00 | 0.00 |
August | 2021.34 | 831.60 | 1189.74 | 2865.61 | 493.39 | 0.00 | 0.00 | 0.00 |
September | 2655.19 | 1492.48 | 1162.71 | 3518.12 | 768.11 | 0.00 | 0.00 | 0.00 |
October | 3134.24 | 2220.72 | 913.53 | 3685.97 | 1626.46 | 0.00 | 0.00 | 0.00 |
November | 3841.68 | 3064.24 | 777.45 | 4369.11 | 1882.79 | 0.00 | 0.00 | 0.00 |
December | 3666.25 | 2967.93 | 698.32 | 3963.20 | 2269.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2712.84 | 1692.69 | 1020.15 | 3181.60 | 1342.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1538.07 | 270.64 | 698.32 | 1862.11 | 424.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4000.02 | 3292.81 | 1366.40 | 4421.27 | 2269.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5196.26 | 4277.55 | 918.71 | 5837.24 | 2682.55 | 0.00 | 0.00 | 0.00 |
February | 4916.93 | 3909.50 | 1007.43 | 5475.05 | 2801.64 | 0.00 | 0.00 | 0.00 |
March | 3693.44 | 2441.00 | 1252.44 | 4151.32 | 2281.05 | 0.00 | 0.00 | 0.00 |
April | 2418.46 | 1000.52 | 1417.94 | 2464.37 | 2103.42 | 0.00 | 0.00 | 0.00 |
May | 2197.65 | 422.61 | 1775.03 | 2477.74 | 1221.20 | 0.00 | 0.00 | 0.00 |
June | 1998.04 | 360.68 | 1637.36 | 2886.26 | 618.72 | 0.00 | 0.00 | 0.00 |
July | 2063.73 | 351.57 | 1712.16 | 2996.97 | 556.07 | 0.00 | 0.00 | 0.00 |
August | 2625.83 | 1080.29 | 1545.53 | 3809.60 | 641.84 | 0.00 | 0.00 | 0.00 |
September | 3449.25 | 1938.81 | 1510.43 | 4663.61 | 1005.53 | 0.00 | 0.00 | 0.00 |
October | 4071.56 | 2884.84 | 1186.73 | 4870.56 | 2184.71 | 0.00 | 0.00 | 0.00 |
November | 4990.57 | 3980.62 | 1009.95 | 5770.63 | 2523.42 | 0.00 | 0.00 | 0.00 |
December | 4762.67 | 3855.52 | 907.16 | 5231.02 | 3049.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3524.13 | 2198.90 | 1325.23 | 4212.21 | 1800.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1998.04 | 351.57 | 907.16 | 2464.37 | 556.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5196.26 | 4277.55 | 1775.03 | 5837.24 | 3049.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 319.06 | 131.72 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 297.43 | 140.48 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 225.23 | 112.15 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 134.18 | 102.00 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 135.28 | 58.23 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 158.63 | 27.37 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 164.93 | 23.64 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 208.01 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 253.38 | 47.47 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 264.38 | 106.79 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 314.57 | 123.63 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 284.58 | 153.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 229.58 | 87.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 134.18 | 23.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 319.06 | 153.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 164.89 | 272.38 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 196.40 | 281.22 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 247.14 | 212.64 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 224.19 | 185.76 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 333.16 | 105.05 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 495.03 | 50.39 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 406.91 | 43.58 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 415.68 | 51.53 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 350.22 | 88.81 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 240.86 | 204.89 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 176.70 | 245.74 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 123.84 | 312.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 281.62 | 170.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 123.84 | 43.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 495.03 | 312.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 5.65 | 150.76 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 6.56 | 156.60 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 21.64 | 117.67 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 33.48 | 100.50 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 78.18 | 53.44 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 129.24 | 24.95 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 125.15 | 22.05 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 94.77 | 26.66 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 69.73 | 47.00 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 23.65 | 110.23 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 9.08 | 134.63 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 4.68 | 174.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 50.40 | 92.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 4.68 | 22.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 129.24 | 174.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 172.57 | 265.70 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 204.27 | 275.54 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 253.44 | 209.49 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 227.97 | 184.22 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 335.04 | 104.45 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 495.56 | 50.13 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 407.71 | 43.24 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 418.21 | 50.62 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 354.76 | 86.59 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 247.28 | 201.20 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 184.21 | 240.09 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 130.18 | 307.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 286.28 | 167.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 130.18 | 43.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 495.56 | 307.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 224.64 | 184.92 | 39.72 | 251.00 | 114.60 | 0.00 | 0.00 | 0.00 |
February | 212.57 | 169.01 | 43.55 | 234.46 | 118.56 | 0.00 | 0.00 | 0.00 |
March | 159.67 | 105.53 | 54.14 | 178.81 | 93.14 | 0.00 | 0.00 | 0.00 |
April | 104.55 | 43.25 | 61.30 | 107.09 | 84.35 | 0.00 | 0.00 | 0.00 |
May | 95.01 | 18.27 | 76.74 | 107.56 | 50.30 | 0.00 | 0.00 | 0.00 |
June | 86.38 | 15.59 | 70.79 | 127.28 | 24.43 | 0.00 | 0.00 | 0.00 |
July | 89.22 | 15.20 | 74.02 | 132.12 | 21.71 | 0.00 | 0.00 | 0.00 |
August | 113.52 | 46.70 | 66.82 | 166.32 | 25.42 | 0.00 | 0.00 | 0.00 |
September | 149.12 | 83.82 | 65.30 | 202.04 | 41.46 | 0.00 | 0.00 | 0.00 |
October | 176.02 | 124.71 | 51.30 | 210.02 | 91.51 | 0.00 | 0.00 | 0.00 |
November | 215.75 | 172.09 | 43.66 | 248.51 | 107.16 | 0.00 | 0.00 | 0.00 |
December | 205.90 | 166.68 | 39.22 | 224.17 | 129.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.35 | 95.06 | 57.29 | 182.14 | 74.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.38 | 15.20 | 39.22 | 107.09 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.64 | 184.92 | 76.74 | 251.00 | 129.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.36 | 0.00 | 23.36 | 4.53 | 123.07 | 0.00 | 0.00 | 0.00 |
February | 29.36 | 0.00 | 29.36 | 5.53 | 127.19 | 0.00 | 0.00 | 0.00 |
March | 39.97 | 0.00 | 39.96 | 18.59 | 94.50 | 0.00 | 0.00 | 0.00 |
April | 50.24 | 0.33 | 49.91 | 28.20 | 81.41 | 0.00 | 0.00 | 0.00 |
May | 68.63 | 2.30 | 66.33 | 66.45 | 41.72 | 0.00 | 0.00 | 0.00 |
June | 75.25 | 8.41 | 66.83 | 108.97 | 17.99 | 0.00 | 0.00 | 0.00 |
July | 71.37 | 4.87 | 66.50 | 105.15 | 15.93 | 0.00 | 0.00 | 0.00 |
August | 56.82 | 1.54 | 55.28 | 80.97 | 19.11 | 0.00 | 0.00 | 0.00 |
September | 47.58 | 0.04 | 47.54 | 60.09 | 34.84 | 0.00 | 0.00 | 0.00 |
October | 34.04 | 0.00 | 34.04 | 20.83 | 87.92 | 0.00 | 0.00 | 0.00 |
November | 25.84 | 0.00 | 25.84 | 7.57 | 109.40 | 0.00 | 0.00 | 0.00 |
December | 21.86 | 0.00 | 21.86 | 3.66 | 143.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.44 | 1.46 | 43.98 | 42.75 | 74.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.86 | 0.00 | 21.86 | 3.66 | 15.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.25 | 8.41 | 66.83 | 108.97 | 143.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.16 | 104.08 | 66.09 | 143.93 | 267.54 | 0.00 | 0.00 | 0.00 |
February | 228.12 | 144.37 | 83.74 | 205.79 | 280.07 | 0.00 | 0.00 | 0.00 |
March | 274.79 | 160.40 | 114.40 | 268.55 | 208.06 | 0.00 | 0.00 | 0.00 |
April | 280.52 | 136.63 | 143.89 | 271.31 | 181.18 | 0.00 | 0.00 | 0.00 |
May | 328.86 | 137.67 | 191.19 | 371.00 | 98.73 | 0.00 | 0.00 | 0.00 |
June | 400.16 | 210.02 | 190.14 | 540.36 | 46.31 | 0.00 | 0.00 | 0.00 |
July | 363.22 | 172.60 | 190.62 | 496.69 | 41.23 | 0.00 | 0.00 | 0.00 |
August | 367.26 | 202.34 | 164.92 | 494.33 | 49.88 | 0.00 | 0.00 | 0.00 |
September | 306.08 | 166.38 | 139.70 | 388.64 | 83.50 | 0.00 | 0.00 | 0.00 |
October | 221.49 | 121.47 | 100.02 | 227.42 | 200.27 | 0.00 | 0.00 | 0.00 |
November | 171.88 | 96.86 | 75.02 | 154.29 | 243.91 | 0.00 | 0.00 | 0.00 |
December | 149.07 | 85.90 | 63.17 | 118.25 | 310.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.96 | 144.81 | 127.15 | 307.19 | 167.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.07 | 85.90 | 63.17 | 118.25 | 41.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 400.16 | 210.02 | 191.19 | 540.36 | 310.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 318.49 | 131.09 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 296.33 | 139.78 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 223.82 | 111.13 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 132.66 | 101.39 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 133.95 | 57.51 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 155.65 | 26.81 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 162.17 | 23.36 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 205.16 | 27.87 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 251.91 | 46.52 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 263.99 | 105.71 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 314.18 | 122.91 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 284.04 | 152.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 228.13 | 86.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 132.66 | 23.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 318.49 | 152.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 5.34 | 150.01 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 5.77 | 156.16 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 20.31 | 117.10 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 31.88 | 100.20 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 76.70 | 52.86 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 126.28 | 24.48 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 122.36 | 21.86 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 91.87 | 26.35 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 68.06 | 46.27 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 22.77 | 109.06 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 8.50 | 133.58 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 4.35 | 173.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 48.92 | 92.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 4.35 | 21.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 126.28 | 173.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.16 | 104.08 | 66.09 | 149.17 | 257.43 | 0.00 | 0.00 | 0.00 |
February | 228.12 | 144.37 | 83.74 | 211.01 | 271.41 | 0.00 | 0.00 | 0.00 |
March | 274.79 | 160.40 | 114.40 | 273.73 | 204.30 | 0.00 | 0.00 | 0.00 |
April | 280.52 | 136.63 | 143.89 | 274.41 | 179.56 | 0.00 | 0.00 | 0.00 |
May | 328.86 | 137.67 | 191.19 | 372.56 | 98.14 | 0.00 | 0.00 | 0.00 |
June | 400.16 | 210.02 | 190.14 | 540.96 | 46.12 | 0.00 | 0.00 | 0.00 |
July | 363.22 | 172.60 | 190.62 | 497.47 | 40.95 | 0.00 | 0.00 | 0.00 |
August | 367.26 | 202.34 | 164.92 | 496.68 | 48.96 | 0.00 | 0.00 | 0.00 |
September | 306.08 | 166.38 | 139.70 | 392.59 | 81.38 | 0.00 | 0.00 | 0.00 |
October | 221.49 | 121.47 | 100.02 | 232.87 | 196.18 | 0.00 | 0.00 | 0.00 |
November | 171.88 | 96.86 | 75.02 | 159.87 | 235.56 | 0.00 | 0.00 | 0.00 |
December | 149.07 | 85.90 | 63.17 | 122.81 | 302.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.96 | 144.81 | 127.15 | 310.81 | 162.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.07 | 85.90 | 63.17 | 122.81 | 40.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 400.16 | 210.02 | 191.19 | 540.96 | 302.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.98 | 0.00 | 36.98 | 5.52 | 206.97 | 0.00 | 0.00 | 0.00 |
February | 46.48 | 0.00 | 46.48 | 6.49 | 212.74 | 0.00 | 0.00 | 0.00 |
March | 63.26 | 0.00 | 63.26 | 25.85 | 159.43 | 0.00 | 0.00 | 0.00 |
April | 79.52 | 0.52 | 79.00 | 42.33 | 135.66 | 0.00 | 0.00 | 0.00 |
May | 108.63 | 3.64 | 104.99 | 100.20 | 73.23 | 0.00 | 0.00 | 0.00 |
June | 119.10 | 13.32 | 105.78 | 162.66 | 36.87 | 0.00 | 0.00 | 0.00 |
July | 112.96 | 7.71 | 105.25 | 156.65 | 34.23 | 0.00 | 0.00 | 0.00 |
August | 89.94 | 2.43 | 87.51 | 118.21 | 40.89 | 0.00 | 0.00 | 0.00 |
September | 75.31 | 0.06 | 75.25 | 86.28 | 68.25 | 0.00 | 0.00 | 0.00 |
October | 53.88 | 0.00 | 53.88 | 27.71 | 153.25 | 0.00 | 0.00 | 0.00 |
November | 40.90 | 0.00 | 40.90 | 9.55 | 185.09 | 0.00 | 0.00 | 0.00 |
December | 34.60 | 0.00 | 34.60 | 4.65 | 237.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.93 | 2.31 | 69.61 | 62.49 | 128.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.60 | 0.00 | 34.60 | 4.65 | 34.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.10 | 13.32 | 105.78 | 162.66 | 237.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.63 | 0.00 | 13.63 | 2.04 | 76.30 | 0.00 | 0.00 | 0.00 |
February | 17.13 | 0.00 | 17.13 | 2.39 | 78.43 | 0.00 | 0.00 | 0.00 |
March | 23.32 | 0.00 | 23.32 | 9.53 | 58.77 | 0.00 | 0.00 | 0.00 |
April | 29.31 | 0.19 | 29.12 | 15.61 | 50.01 | 0.00 | 0.00 | 0.00 |
May | 40.05 | 1.34 | 38.70 | 36.94 | 27.00 | 0.00 | 0.00 | 0.00 |
June | 43.91 | 4.91 | 39.00 | 59.96 | 13.59 | 0.00 | 0.00 | 0.00 |
July | 41.64 | 2.84 | 38.80 | 57.75 | 12.62 | 0.00 | 0.00 | 0.00 |
August | 33.16 | 0.90 | 32.26 | 43.58 | 15.07 | 0.00 | 0.00 | 0.00 |
September | 27.76 | 0.02 | 27.74 | 31.81 | 25.16 | 0.00 | 0.00 | 0.00 |
October | 19.86 | 0.00 | 19.86 | 10.22 | 56.49 | 0.00 | 0.00 | 0.00 |
November | 15.08 | 0.00 | 15.08 | 3.52 | 68.23 | 0.00 | 0.00 | 0.00 |
December | 12.75 | 0.00 | 12.75 | 1.71 | 87.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.52 | 0.85 | 25.66 | 23.04 | 47.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.75 | 0.00 | 12.75 | 1.71 | 12.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.91 | 4.91 | 39.00 | 59.96 | 87.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.05 | 107.88 | 23.17 | 149.65 | 64.09 | 0.00 | 0.00 | 0.00 |
February | 124.00 | 98.60 | 25.41 | 139.63 | 68.46 | 0.00 | 0.00 | 0.00 |
March | 93.15 | 61.56 | 31.59 | 105.91 | 55.19 | 0.00 | 0.00 | 0.00 |
April | 60.99 | 25.23 | 35.76 | 63.34 | 50.17 | 0.00 | 0.00 | 0.00 |
May | 55.42 | 10.66 | 44.77 | 64.05 | 29.17 | 0.00 | 0.00 | 0.00 |
June | 50.39 | 9.10 | 41.29 | 73.91 | 14.99 | 0.00 | 0.00 | 0.00 |
July | 52.05 | 8.87 | 43.18 | 76.57 | 13.52 | 0.00 | 0.00 | 0.00 |
August | 66.22 | 27.24 | 38.98 | 96.90 | 15.63 | 0.00 | 0.00 | 0.00 |
September | 86.99 | 48.90 | 38.09 | 118.36 | 24.74 | 0.00 | 0.00 | 0.00 |
October | 102.68 | 72.75 | 29.93 | 123.97 | 53.64 | 0.00 | 0.00 | 0.00 |
November | 125.86 | 100.39 | 25.47 | 147.63 | 60.60 | 0.00 | 0.00 | 0.00 |
December | 120.11 | 97.23 | 22.88 | 133.22 | 74.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.88 | 55.46 | 33.42 | 107.58 | 43.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.39 | 8.87 | 22.88 | 63.34 | 13.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.05 | 107.88 | 44.77 | 149.65 | 74.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.69 | 292.80 | 62.89 | 406.17 | 173.95 | 0.00 | 0.00 | 0.00 |
February | 336.57 | 267.61 | 68.96 | 378.98 | 185.83 | 0.00 | 0.00 | 0.00 |
March | 252.82 | 167.09 | 85.73 | 287.47 | 149.80 | 0.00 | 0.00 | 0.00 |
April | 165.55 | 68.49 | 97.06 | 171.93 | 136.17 | 0.00 | 0.00 | 0.00 |
May | 150.43 | 28.93 | 121.50 | 173.85 | 79.19 | 0.00 | 0.00 | 0.00 |
June | 136.77 | 24.69 | 112.08 | 200.60 | 40.70 | 0.00 | 0.00 | 0.00 |
July | 141.26 | 24.07 | 117.20 | 207.83 | 36.70 | 0.00 | 0.00 | 0.00 |
August | 179.74 | 73.95 | 105.79 | 262.99 | 42.42 | 0.00 | 0.00 | 0.00 |
September | 236.10 | 132.71 | 103.39 | 321.25 | 67.15 | 0.00 | 0.00 | 0.00 |
October | 278.70 | 197.47 | 81.23 | 336.48 | 145.59 | 0.00 | 0.00 | 0.00 |
November | 341.61 | 272.48 | 69.13 | 400.69 | 164.49 | 0.00 | 0.00 | 0.00 |
December | 326.01 | 263.91 | 62.10 | 361.60 | 202.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.23 | 150.52 | 90.71 | 291.98 | 118.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.77 | 24.07 | 62.10 | 171.93 | 36.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.69 | 292.80 | 121.50 | 406.17 | 202.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 318.16 | 131.13 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 295.80 | 140.61 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 223.80 | 112.17 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 133.02 | 102.10 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 133.95 | 58.58 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 157.61 | 27.14 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 164.11 | 23.36 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 206.77 | 28.01 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 252.15 | 47.24 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 263.20 | 106.53 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 313.29 | 123.28 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 283.29 | 153.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 228.37 | 87.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 133.02 | 23.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 318.16 | 153.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 164.11 | 270.51 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 194.92 | 280.98 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 245.07 | 212.31 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 221.99 | 185.56 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 329.99 | 105.28 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 492.36 | 49.87 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 404.88 | 42.96 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 413.36 | 50.95 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 348.48 | 88.16 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 239.32 | 204.01 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 175.57 | 244.62 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 123.16 | 312.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 279.80 | 170.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 123.16 | 42.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 492.36 | 312.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 5.87 | 149.40 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 6.63 | 156.12 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 21.54 | 117.44 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 33.02 | 100.43 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 77.11 | 53.60 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 128.47 | 24.78 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 124.61 | 21.83 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 94.22 | 26.39 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 69.66 | 46.53 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 23.78 | 109.64 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 9.21 | 133.63 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 4.85 | 173.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 50.16 | 92.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 4.85 | 21.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 128.47 | 173.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 172.70 | 263.62 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 203.57 | 275.11 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 251.90 | 208.95 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 226.02 | 183.89 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 332.02 | 104.58 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 492.90 | 49.63 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 405.71 | 42.59 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 416.02 | 49.96 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 353.39 | 85.58 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 246.48 | 199.76 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 183.89 | 238.58 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 130.10 | 306.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 284.90 | 166.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 130.10 | 42.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 492.90 | 306.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.90 | 339.08 | 72.83 | 458.10 | 199.39 | 0.00 | 0.00 | 0.00 |
February | 389.76 | 309.90 | 79.86 | 426.44 | 212.56 | 0.00 | 0.00 | 0.00 |
March | 292.78 | 193.50 | 99.28 | 324.24 | 167.60 | 0.00 | 0.00 | 0.00 |
April | 191.71 | 79.31 | 112.40 | 193.30 | 151.25 | 0.00 | 0.00 | 0.00 |
May | 174.21 | 33.50 | 140.71 | 198.28 | 84.15 | 0.00 | 0.00 | 0.00 |
June | 158.38 | 28.59 | 129.79 | 235.92 | 37.01 | 0.00 | 0.00 | 0.00 |
July | 163.59 | 27.87 | 135.72 | 244.32 | 32.32 | 0.00 | 0.00 | 0.00 |
August | 208.15 | 85.63 | 122.51 | 305.54 | 39.04 | 0.00 | 0.00 | 0.00 |
September | 273.42 | 153.69 | 119.73 | 369.45 | 68.59 | 0.00 | 0.00 | 0.00 |
October | 322.75 | 228.68 | 94.07 | 382.76 | 159.84 | 0.00 | 0.00 | 0.00 |
November | 395.60 | 315.54 | 80.06 | 452.37 | 187.40 | 0.00 | 0.00 | 0.00 |
December | 377.53 | 305.62 | 71.91 | 406.53 | 233.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 279.36 | 174.31 | 105.05 | 332.56 | 130.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 158.38 | 27.87 | 71.91 | 193.30 | 32.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.90 | 339.08 | 140.71 | 458.10 | 233.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.38 | 0.00 | 204.38 | 20.67 | 1253.07 | 0.00 | 0.00 | 0.00 |
February | 256.88 | 0.00 | 256.88 | 25.54 | 1298.80 | 0.00 | 0.00 | 0.00 |
March | 349.64 | 0.02 | 349.63 | 114.23 | 984.35 | 0.00 | 0.00 | 0.00 |
April | 439.52 | 2.88 | 436.64 | 188.78 | 858.79 | 0.00 | 0.00 | 0.00 |
May | 600.41 | 20.14 | 580.28 | 496.17 | 446.87 | 0.00 | 0.00 | 0.00 |
June | 658.28 | 73.61 | 584.67 | 872.18 | 213.08 | 0.00 | 0.00 | 0.00 |
July | 624.37 | 42.62 | 581.75 | 843.43 | 197.77 | 0.00 | 0.00 | 0.00 |
August | 497.11 | 13.45 | 483.66 | 634.31 | 233.99 | 0.00 | 0.00 | 0.00 |
September | 416.23 | 0.33 | 415.90 | 459.62 | 390.03 | 0.00 | 0.00 | 0.00 |
October | 297.79 | 0.00 | 297.79 | 134.54 | 915.29 | 0.00 | 0.00 | 0.00 |
November | 226.06 | 0.00 | 226.06 | 40.76 | 1130.33 | 0.00 | 0.00 | 0.00 |
December | 191.22 | 0.00 | 191.22 | 17.17 | 1444.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.56 | 12.79 | 384.77 | 322.28 | 777.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.22 | 0.00 | 191.22 | 17.17 | 197.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 658.28 | 73.61 | 584.67 | 872.18 | 1444.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.38 | 0.00 | 204.38 | 18.01 | 1279.48 | 0.00 | 0.00 | 0.00 |
February | 256.88 | 0.00 | 256.88 | 23.42 | 1327.05 | 0.00 | 0.00 | 0.00 |
March | 349.64 | 0.02 | 349.63 | 108.36 | 1005.89 | 0.00 | 0.00 | 0.00 |
April | 439.52 | 2.88 | 436.64 | 181.18 | 878.00 | 0.00 | 0.00 | 0.00 |
May | 600.41 | 20.14 | 580.28 | 486.67 | 455.70 | 0.00 | 0.00 | 0.00 |
June | 658.28 | 73.61 | 584.67 | 864.10 | 218.25 | 0.00 | 0.00 | 0.00 |
July | 624.37 | 42.62 | 581.75 | 835.62 | 203.13 | 0.00 | 0.00 | 0.00 |
August | 497.11 | 13.45 | 483.66 | 627.21 | 240.15 | 0.00 | 0.00 | 0.00 |
September | 416.23 | 0.33 | 415.90 | 453.21 | 398.25 | 0.00 | 0.00 | 0.00 |
October | 297.79 | 0.00 | 297.79 | 129.20 | 932.95 | 0.00 | 0.00 | 0.00 |
November | 226.06 | 0.00 | 226.06 | 38.05 | 1154.76 | 0.00 | 0.00 | 0.00 |
December | 191.22 | 0.00 | 191.22 | 15.33 | 1475.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.56 | 12.79 | 384.77 | 316.67 | 794.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.22 | 0.00 | 191.22 | 15.33 | 203.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 658.28 | 73.61 | 584.67 | 864.10 | 1475.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 5.56 | 164.15 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 5.94 | 172.88 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 22.04 | 132.29 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 34.46 | 116.34 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 88.18 | 62.68 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 146.14 | 31.51 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 141.78 | 29.31 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 110.61 | 33.24 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 81.99 | 52.82 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 26.61 | 121.30 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 9.44 | 148.17 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 4.15 | 192.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 56.70 | 104.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 4.15 | 29.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 146.14 | 192.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 340.30 | 208.14 | 132.16 | 300.45 | 566.04 | 0.00 | 0.00 | 0.00 |
February | 456.20 | 288.73 | 167.48 | 423.55 | 605.39 | 0.00 | 0.00 | 0.00 |
March | 549.55 | 320.77 | 228.78 | 556.33 | 465.23 | 0.00 | 0.00 | 0.00 |
April | 560.99 | 273.23 | 287.76 | 558.76 | 420.17 | 0.00 | 0.00 | 0.00 |
May | 657.67 | 275.33 | 382.35 | 787.93 | 232.48 | 0.00 | 0.00 | 0.00 |
June | 800.26 | 420.00 | 380.26 | 1155.03 | 118.30 | 0.00 | 0.00 | 0.00 |
July | 726.38 | 345.17 | 381.22 | 1067.10 | 109.93 | 0.00 | 0.00 | 0.00 |
August | 734.48 | 404.66 | 329.82 | 1063.64 | 123.77 | 0.00 | 0.00 | 0.00 |
September | 612.12 | 332.73 | 279.39 | 840.21 | 189.74 | 0.00 | 0.00 | 0.00 |
October | 442.95 | 242.93 | 200.02 | 483.26 | 438.25 | 0.00 | 0.00 | 0.00 |
November | 343.73 | 193.71 | 150.02 | 324.04 | 524.71 | 0.00 | 0.00 | 0.00 |
December | 298.11 | 171.79 | 126.33 | 243.28 | 675.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.89 | 289.61 | 254.28 | 651.40 | 371.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 298.11 | 171.79 | 126.33 | 243.28 | 109.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 800.26 | 420.00 | 382.35 | 1155.03 | 675.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 325.10 | 140.54 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 301.67 | 152.66 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 230.35 | 124.57 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 137.71 | 116.64 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 146.90 | 67.19 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 175.60 | 34.09 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 181.85 | 30.91 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 225.01 | 34.14 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 268.71 | 52.56 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 273.33 | 115.95 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 320.93 | 133.47 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 287.06 | 166.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 239.16 | 97.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 137.71 | 30.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 325.10 | 166.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.98 | 0.00 | 36.98 | 4.65 | 209.40 | 0.00 | 0.00 | 0.00 |
February | 46.48 | 0.00 | 46.48 | 5.36 | 216.43 | 0.00 | 0.00 | 0.00 |
March | 63.26 | 0.00 | 63.26 | 23.25 | 161.34 | 0.00 | 0.00 | 0.00 |
April | 79.52 | 0.52 | 79.00 | 39.08 | 138.19 | 0.00 | 0.00 | 0.00 |
May | 108.63 | 3.64 | 104.99 | 95.88 | 74.44 | 0.00 | 0.00 | 0.00 |
June | 119.10 | 13.32 | 105.78 | 158.88 | 37.76 | 0.00 | 0.00 | 0.00 |
July | 112.96 | 7.71 | 105.25 | 153.42 | 34.97 | 0.00 | 0.00 | 0.00 |
August | 89.94 | 2.43 | 87.51 | 115.18 | 41.49 | 0.00 | 0.00 | 0.00 |
September | 75.31 | 0.06 | 75.25 | 83.98 | 67.79 | 0.00 | 0.00 | 0.00 |
October | 53.88 | 0.00 | 53.88 | 25.68 | 153.34 | 0.00 | 0.00 | 0.00 |
November | 40.90 | 0.00 | 40.90 | 8.10 | 187.90 | 0.00 | 0.00 | 0.00 |
December | 34.60 | 0.00 | 34.60 | 3.79 | 241.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.93 | 2.31 | 69.61 | 60.08 | 129.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.60 | 0.00 | 34.60 | 3.79 | 34.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.10 | 13.32 | 105.78 | 158.88 | 241.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.08 | 0.00 | 33.08 | 4.16 | 187.32 | 0.00 | 0.00 | 0.00 |
February | 41.58 | 0.00 | 41.58 | 4.79 | 193.64 | 0.00 | 0.00 | 0.00 |
March | 56.60 | 0.00 | 56.60 | 20.80 | 144.35 | 0.00 | 0.00 | 0.00 |
April | 71.15 | 0.47 | 70.68 | 34.97 | 123.64 | 0.00 | 0.00 | 0.00 |
May | 97.19 | 3.26 | 93.93 | 85.78 | 66.60 | 0.00 | 0.00 | 0.00 |
June | 106.56 | 11.92 | 94.64 | 142.15 | 33.78 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 6.90 | 94.17 | 137.26 | 31.29 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 2.18 | 78.29 | 103.05 | 37.13 | 0.00 | 0.00 | 0.00 |
September | 67.38 | 0.05 | 67.32 | 75.14 | 60.65 | 0.00 | 0.00 | 0.00 |
October | 48.21 | 0.00 | 48.21 | 22.98 | 137.19 | 0.00 | 0.00 | 0.00 |
November | 36.59 | 0.00 | 36.59 | 7.25 | 168.11 | 0.00 | 0.00 | 0.00 |
December | 30.95 | 0.00 | 30.95 | 3.39 | 216.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.35 | 2.07 | 62.28 | 53.75 | 116.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.95 | 0.00 | 30.95 | 3.39 | 31.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.56 | 11.92 | 94.64 | 142.15 | 216.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1048.52 | 863.14 | 185.38 | 1184.86 | 515.84 | 0.00 | 0.00 | 0.00 |
February | 992.16 | 788.87 | 203.28 | 1102.32 | 554.85 | 0.00 | 0.00 | 0.00 |
March | 745.28 | 492.55 | 252.72 | 834.00 | 446.74 | 0.00 | 0.00 | 0.00 |
April | 488.01 | 201.89 | 286.12 | 494.56 | 409.74 | 0.00 | 0.00 | 0.00 |
May | 443.45 | 85.28 | 358.18 | 498.86 | 238.16 | 0.00 | 0.00 | 0.00 |
June | 403.18 | 72.78 | 330.40 | 579.40 | 122.93 | 0.00 | 0.00 | 0.00 |
July | 416.43 | 70.94 | 345.49 | 602.19 | 110.66 | 0.00 | 0.00 | 0.00 |
August | 529.85 | 217.99 | 311.87 | 764.06 | 127.08 | 0.00 | 0.00 | 0.00 |
September | 696.01 | 391.22 | 304.78 | 936.78 | 197.25 | 0.00 | 0.00 | 0.00 |
October | 821.58 | 582.11 | 239.46 | 981.88 | 429.47 | 0.00 | 0.00 | 0.00 |
November | 1007.02 | 803.22 | 203.79 | 1167.46 | 489.93 | 0.00 | 0.00 | 0.00 |
December | 961.03 | 777.98 | 183.05 | 1052.16 | 605.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 711.12 | 443.70 | 267.41 | 848.41 | 352.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 403.18 | 70.94 | 183.05 | 494.56 | 110.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1048.52 | 863.14 | 358.18 | 1184.86 | 605.13 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380465E+10 | 0.313198E+10 | 0.672671E+09 | 0.424509E+10 | 0.180612E+10 |
February | 0.325173E+10 | 0.258549E+10 | 0.666247E+09 | 0.359123E+10 | 0.171231E+10 |
March | 0.270430E+10 | 0.178728E+10 | 0.917025E+09 | 0.301999E+10 | 0.151401E+10 |
April | 0.171366E+10 | 0.708940E+09 | 0.100472E+10 | 0.174813E+10 | 0.131558E+10 |
May | 0.160910E+10 | 0.309432E+09 | 0.129967E+10 | 0.183041E+10 | 0.778891E+09 |
June | 0.141576E+10 | 0.255570E+09 | 0.116019E+10 | 0.202078E+10 | 0.406060E+09 |
July | 0.151105E+10 | 0.257418E+09 | 0.125363E+10 | 0.216829E+10 | 0.375401E+09 |
August | 0.192261E+10 | 0.790983E+09 | 0.113163E+10 | 0.275496E+10 | 0.438468E+09 |
September | 0.244404E+10 | 0.137379E+10 | 0.107025E+10 | 0.326683E+10 | 0.665578E+09 |
October | 0.298116E+10 | 0.211225E+10 | 0.868910E+09 | 0.353648E+10 | 0.146286E+10 |
November | 0.353618E+10 | 0.282056E+10 | 0.715622E+09 | 0.405635E+10 | 0.164098E+10 |
December | 0.348719E+10 | 0.282298E+10 | 0.664211E+09 | 0.380624E+10 | 0.206093E+10 |
Annual Sum or Average | 0.303814E+11 | 0.189567E+11 | 0.114248E+11 | 0.360448E+11 | 0.141772E+11 |
Minimum of Months | 0.141576E+10 | 0.255570E+09 | 0.664211E+09 | 0.174813E+10 | 0.375401E+09 |
Maximum of Months | 0.380465E+10 | 0.313198E+10 | 0.129967E+10 | 0.424509E+10 | 0.206093E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107137E+11 | 0.881946E+10 | 0.189420E+10 | 0.118419E+11 | 0.537214E+10 |
February | 0.915667E+10 | 0.728056E+10 | 0.187611E+10 | 0.100168E+11 | 0.504927E+10 |
March | 0.761514E+10 | 0.503286E+10 | 0.258228E+10 | 0.840688E+10 | 0.451315E+10 |
April | 0.482554E+10 | 0.199633E+10 | 0.282922E+10 | 0.482658E+10 | 0.398313E+10 |
May | 0.453111E+10 | 0.871340E+09 | 0.365977E+10 | 0.500405E+10 | 0.243323E+10 |
June | 0.398667E+10 | 0.719668E+09 | 0.326701E+10 | 0.560954E+10 | 0.122127E+10 |
July | 0.425500E+10 | 0.724873E+09 | 0.353013E+10 | 0.602264E+10 | 0.113709E+10 |
August | 0.541394E+10 | 0.222736E+10 | 0.318659E+10 | 0.767526E+10 | 0.132150E+10 |
September | 0.688226E+10 | 0.386850E+10 | 0.301376E+10 | 0.911896E+10 | 0.199095E+10 |
October | 0.839476E+10 | 0.594797E+10 | 0.244679E+10 | 0.987249E+10 | 0.435630E+10 |
November | 0.995764E+10 | 0.794250E+10 | 0.201515E+10 | 0.113247E+11 | 0.488018E+10 |
December | 0.981969E+10 | 0.794932E+10 | 0.187038E+10 | 0.106150E+11 | 0.607885E+10 |
Annual Sum or Average | 0.855521E+11 | 0.533807E+11 | 0.321714E+11 | 0.100335E+12 | 0.423371E+11 |
Minimum of Months | 0.398667E+10 | 0.719668E+09 | 0.187038E+10 | 0.482658E+10 | 0.113709E+10 |
Maximum of Months | 0.107137E+11 | 0.881946E+10 | 0.365977E+10 | 0.118419E+11 | 0.607885E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139177E+11 | 0.114570E+11 | 0.246067E+10 | 0.156345E+11 | 0.718494E+10 |
February | 0.118950E+11 | 0.945786E+10 | 0.243717E+10 | 0.132452E+11 | 0.677772E+10 |
March | 0.989250E+10 | 0.653797E+10 | 0.335453E+10 | 0.111189E+11 | 0.610957E+10 |
April | 0.626865E+10 | 0.259334E+10 | 0.367531E+10 | 0.638766E+10 | 0.545207E+10 |
May | 0.588617E+10 | 0.113192E+10 | 0.475425E+10 | 0.663637E+10 | 0.327087E+10 |
June | 0.517892E+10 | 0.934890E+09 | 0.424403E+10 | 0.748118E+10 | 0.160373E+10 |
July | 0.552749E+10 | 0.941651E+09 | 0.458584E+10 | 0.802708E+10 | 0.148939E+10 |
August | 0.703302E+10 | 0.289346E+10 | 0.413956E+10 | 0.102036E+11 | 0.171911E+10 |
September | 0.894045E+10 | 0.502541E+10 | 0.391504E+10 | 0.120881E+11 | 0.260632E+10 |
October | 0.109053E+11 | 0.772675E+10 | 0.317852E+10 | 0.130453E+11 | 0.585153E+10 |
November | 0.129355E+11 | 0.103178E+11 | 0.261779E+10 | 0.149575E+11 | 0.654070E+10 |
December | 0.127563E+11 | 0.103266E+11 | 0.242972E+10 | 0.140108E+11 | 0.816652E+10 |
Annual Sum or Average | 0.111137E+12 | 0.693446E+11 | 0.417924E+11 | 0.132836E+12 | 0.567725E+11 |
Minimum of Months | 0.517892E+10 | 0.934890E+09 | 0.242972E+10 | 0.638766E+10 | 0.148939E+10 |
Maximum of Months | 0.139177E+11 | 0.114570E+11 | 0.475425E+10 | 0.156345E+11 | 0.816652E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.854563E+09 | 0.352799E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.719553E+09 | 0.339838E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.603251E+09 | 0.300380E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.347797E+09 | 0.264388E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.362335E+09 | 0.155953E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.411164E+09 | 70955627.34 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.441754E+09 | 63322471.14 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.557129E+09 | 75685660.35 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.656768E+09 | 0.123041E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.708112E+09 | 0.286032E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.815356E+09 | 0.320443E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.762221E+09 | 0.410072E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.724000E+10 | 0.276291E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.347797E+09 | 63322471.14 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.854563E+09 | 0.410072E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.441635E+09 | 0.729530E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.475134E+09 | 0.680331E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.661947E+09 | 0.569534E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.581106E+09 | 0.481501E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.892324E+09 | 0.281369E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.128312E+10 | 0.130603E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.108986E+10 | 0.116723E+09 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.111335E+10 | 0.138011E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.907774E+09 | 0.230189E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.645125E+09 | 0.548771E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.457996E+09 | 0.636956E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.331688E+09 | 0.838060E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.888106E+10 | 0.538158E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.331688E+09 | 0.116723E+09 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.128312E+10 | 0.838060E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 15127230.60 | 0.403793E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 15879313.51 | 0.378836E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 57952255.27 | 0.315175E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 86784770.11 | 0.260494E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.209387E+09 | 0.143132E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.334979E+09 | 64668272.96 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.335215E+09 | 59066258.58 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.253843E+09 | 71413705.30 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.180728E+09 | 0.121834E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 63349792.70 | 0.295248E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 23534032.82 | 0.348949E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 12538170.74 | 0.466524E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.158932E+10 | 0.292913E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 12538170.74 | 59066258.58 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.335215E+09 | 0.466524E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.462220E+09 | 0.711654E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.494181E+09 | 0.666596E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.678822E+09 | 0.561096E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.590905E+09 | 0.477511E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.897380E+09 | 0.279764E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.128448E+10 | 0.129943E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.109202E+10 | 0.115814E+09 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.112015E+10 | 0.135591E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.919549E+09 | 0.224433E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.662324E+09 | 0.538903E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.477480E+09 | 0.622322E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.348668E+09 | 0.822681E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.902818E+10 | 0.528631E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.348668E+09 | 0.115814E+09 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.128448E+10 | 0.822681E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.601678E+09 | 0.495299E+09 | 0.106379E+09 | 0.672287E+09 | 0.306951E+09 |
February | 0.514238E+09 | 0.408875E+09 | 0.105363E+09 | 0.567215E+09 | 0.286821E+09 |
March | 0.427666E+09 | 0.282644E+09 | 0.145022E+09 | 0.478919E+09 | 0.249462E+09 |
April | 0.271003E+09 | 0.112113E+09 | 0.158890E+09 | 0.277572E+09 | 0.218628E+09 |
May | 0.254468E+09 | 48934276.29 | 0.205534E+09 | 0.288102E+09 | 0.134713E+09 |
June | 0.223893E+09 | 40416423.07 | 0.183477E+09 | 0.329907E+09 | 63322346.27 |
July | 0.238962E+09 | 40708703.25 | 0.198254E+09 | 0.353876E+09 | 58139922.83 |
August | 0.304048E+09 | 0.125088E+09 | 0.178960E+09 | 0.445463E+09 | 68072182.06 |
September | 0.386508E+09 | 0.217254E+09 | 0.169254E+09 | 0.523687E+09 | 0.107466E+09 |
October | 0.471449E+09 | 0.334037E+09 | 0.137413E+09 | 0.562510E+09 | 0.245110E+09 |
November | 0.559220E+09 | 0.446049E+09 | 0.113171E+09 | 0.644127E+09 | 0.277748E+09 |
December | 0.551473E+09 | 0.446432E+09 | 0.105041E+09 | 0.600412E+09 | 0.347020E+09 |
Annual Sum or Average | 0.480461E+10 | 0.299785E+10 | 0.180676E+10 | 0.574408E+10 | 0.236345E+10 |
Minimum of Months | 0.223893E+09 | 40416423.07 | 0.105041E+09 | 0.277572E+09 | 58139922.83 |
Maximum of Months | 0.601678E+09 | 0.495299E+09 | 0.205534E+09 | 0.672287E+09 | 0.347020E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62572574.96 | 0.00 | 62572574.96 | 12130992.25 | 0.329635E+09 |
February | 71035352.99 | 0.00 | 71035352.99 | 13389136.51 | 0.307706E+09 |
March | 0.107045E+09 | 5523.69 | 0.107040E+09 | 49794382.74 | 0.253109E+09 |
April | 0.130222E+09 | 853207.10 | 0.129368E+09 | 73090091.02 | 0.211025E+09 |
May | 0.183819E+09 | 6164948.81 | 0.177654E+09 | 0.177985E+09 | 0.111741E+09 |
June | 0.195035E+09 | 21810480.60 | 0.173225E+09 | 0.282445E+09 | 46622236.92 |
July | 0.191153E+09 | 13048148.50 | 0.178104E+09 | 0.281624E+09 | 42674726.75 |
August | 0.152193E+09 | 4118668.79 | 0.148074E+09 | 0.216861E+09 | 51179240.43 |
September | 0.123321E+09 | 98489.96 | 0.123223E+09 | 0.155744E+09 | 90301563.54 |
October | 91170274.99 | 0.00 | 91170274.99 | 55787656.83 | 0.235482E+09 |
November | 66977226.59 | 0.00 | 66977226.59 | 19611518.82 | 0.283560E+09 |
December | 58544410.09 | 0.00 | 58544410.09 | 9793376.42 | 0.383675E+09 |
Annual Sum or Average | 0.143309E+10 | 46099467.45 | 0.138699E+10 | 0.134826E+10 | 0.234671E+10 |
Minimum of Months | 58544410.09 | 0.00 | 58544410.09 | 9793376.42 | 42674726.75 |
Maximum of Months | 0.195035E+09 | 21810480.60 | 0.178104E+09 | 0.282445E+09 | 0.383675E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455767E+09 | 0.278765E+09 | 0.177003E+09 | 0.385508E+09 | 0.716576E+09 |
February | 0.551865E+09 | 0.349271E+09 | 0.202594E+09 | 0.497838E+09 | 0.677537E+09 |
March | 0.736009E+09 | 0.429611E+09 | 0.306398E+09 | 0.719273E+09 | 0.557263E+09 |
April | 0.727100E+09 | 0.354133E+09 | 0.372967E+09 | 0.703224E+09 | 0.469627E+09 |
May | 0.880818E+09 | 0.368744E+09 | 0.512074E+09 | 0.993684E+09 | 0.264443E+09 |
June | 0.103721E+10 | 0.544363E+09 | 0.492848E+09 | 0.140061E+10 | 0.120035E+09 |
July | 0.972841E+09 | 0.462281E+09 | 0.510560E+09 | 0.133033E+10 | 0.110435E+09 |
August | 0.983679E+09 | 0.541955E+09 | 0.441724E+09 | 0.132400E+10 | 0.133590E+09 |
September | 0.793362E+09 | 0.431250E+09 | 0.362112E+09 | 0.100734E+10 | 0.216438E+09 |
October | 0.593245E+09 | 0.325358E+09 | 0.267887E+09 | 0.609128E+09 | 0.536413E+09 |
November | 0.445508E+09 | 0.251066E+09 | 0.194443E+09 | 0.399920E+09 | 0.632216E+09 |
December | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.316715E+09 | 0.832867E+09 |
Annual Sum or Average | 0.857667E+10 | 0.456687E+10 | 0.400980E+10 | 0.968757E+10 | 0.526744E+10 |
Minimum of Months | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.316715E+09 | 0.110435E+09 |
Maximum of Months | 0.103721E+10 | 0.544363E+09 | 0.512074E+09 | 0.140061E+10 | 0.832867E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.853047E+09 | 0.351105E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.716874E+09 | 0.338157E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.599486E+09 | 0.297663E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.343848E+09 | 0.262812E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.358762E+09 | 0.154037E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.403441E+09 | 69488788.53 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.434368E+09 | 62574471.35 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.549487E+09 | 74654823.54 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.652961E+09 | 0.120578E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.707069E+09 | 0.283139E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.814345E+09 | 0.318573E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.760774E+09 | 0.408705E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.719446E+10 | 0.274149E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.343848E+09 | 62574471.35 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.853047E+09 | 0.408705E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 14290827.30 | 0.401788E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 13957192.99 | 0.377793E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 54397885.10 | 0.313631E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 82622773.57 | 0.259730E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.205446E+09 | 0.141585E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.327309E+09 | 63446637.30 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.327729E+09 | 58549117.58 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.246063E+09 | 70575390.37 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.176410E+09 | 0.119926E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 60978029.99 | 0.292117E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 22042660.44 | 0.346241E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 11638155.07 | 0.464736E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.154288E+10 | 0.291012E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 11638155.07 | 58549117.58 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.327729E+09 | 0.464736E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455767E+09 | 0.278765E+09 | 0.177003E+09 | 0.399526E+09 | 0.689502E+09 |
February | 0.551865E+09 | 0.349271E+09 | 0.202594E+09 | 0.510471E+09 | 0.656591E+09 |
March | 0.736009E+09 | 0.429611E+09 | 0.306398E+09 | 0.733158E+09 | 0.547188E+09 |
April | 0.727100E+09 | 0.354133E+09 | 0.372967E+09 | 0.711274E+09 | 0.465410E+09 |
May | 0.880818E+09 | 0.368744E+09 | 0.512074E+09 | 0.997865E+09 | 0.262853E+09 |
June | 0.103721E+10 | 0.544363E+09 | 0.492848E+09 | 0.140217E+10 | 0.119539E+09 |
July | 0.972841E+09 | 0.462281E+09 | 0.510560E+09 | 0.133242E+10 | 0.109687E+09 |
August | 0.983679E+09 | 0.541955E+09 | 0.441724E+09 | 0.133031E+10 | 0.131123E+09 |
September | 0.793362E+09 | 0.431250E+09 | 0.362112E+09 | 0.101759E+10 | 0.210934E+09 |
October | 0.593245E+09 | 0.325358E+09 | 0.267887E+09 | 0.623713E+09 | 0.525453E+09 |
November | 0.445508E+09 | 0.251066E+09 | 0.194443E+09 | 0.414375E+09 | 0.610583E+09 |
December | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.328937E+09 | 0.810382E+09 |
Annual Sum or Average | 0.857667E+10 | 0.456687E+10 | 0.400980E+10 | 0.980181E+10 | 0.513924E+10 |
Minimum of Months | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.328937E+09 | 0.109687E+09 |
Maximum of Months | 0.103721E+10 | 0.544363E+09 | 0.512074E+09 | 0.140217E+10 | 0.810382E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 99042143.99 | 0.00 | 99042143.99 | 14788795.12 | 0.554345E+09 |
February | 0.112437E+09 | 0.00 | 0.112437E+09 | 15710752.75 | 0.514665E+09 |
March | 0.169435E+09 | 8743.09 | 0.169426E+09 | 69248444.48 | 0.427019E+09 |
April | 0.206120E+09 | 1350487.19 | 0.204769E+09 | 0.109724E+09 | 0.351639E+09 |
May | 0.290956E+09 | 9758104.85 | 0.281198E+09 | 0.268387E+09 | 0.196138E+09 |
June | 0.308709E+09 | 34522420.75 | 0.274187E+09 | 0.421627E+09 | 95564465.47 |
July | 0.302563E+09 | 20653083.30 | 0.281910E+09 | 0.419563E+09 | 91670616.87 |
August | 0.240897E+09 | 6519178.53 | 0.234377E+09 | 0.316624E+09 | 0.109510E+09 |
September | 0.195197E+09 | 155893.49 | 0.195041E+09 | 0.223630E+09 | 0.176916E+09 |
October | 0.144308E+09 | 0.00 | 0.144308E+09 | 74226130.17 | 0.410471E+09 |
November | 0.106014E+09 | 0.00 | 0.106014E+09 | 24746952.25 | 0.479746E+09 |
December | 92666218.35 | 0.00 | 92666218.35 | 12447414.12 | 0.635646E+09 |
Annual Sum or Average | 0.226834E+10 | 72967911.20 | 0.219538E+10 | 0.197072E+10 | 0.404333E+10 |
Minimum of Months | 92666218.35 | 0.00 | 92666218.35 | 12447414.12 | 91670616.87 |
Maximum of Months | 0.308709E+09 | 34522420.75 | 0.281910E+09 | 0.421627E+09 | 0.635646E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36511035.29 | 0.00 | 36511035.29 | 5451762.24 | 0.204355E+09 |
February | 41449057.86 | 0.00 | 41449057.86 | 5791633.99 | 0.189728E+09 |
March | 62460760.84 | 3223.07 | 62457537.77 | 25527843.99 | 0.157417E+09 |
April | 75984197.42 | 497845.50 | 75486351.92 | 40448925.02 | 0.129629E+09 |
May | 0.107258E+09 | 3597241.50 | 0.103661E+09 | 98938580.52 | 72304735.87 |
June | 0.113803E+09 | 12726393.75 | 0.101077E+09 | 0.155429E+09 | 35229018.99 |
July | 0.111537E+09 | 7613581.68 | 0.103924E+09 | 0.154668E+09 | 33793585.16 |
August | 88804449.62 | 2403239.14 | 86401210.48 | 0.116721E+09 | 40369871.70 |
September | 71957805.44 | 57468.79 | 71900336.65 | 82439296.44 | 65218732.66 |
October | 53197764.83 | 0.00 | 53197764.83 | 27362825.04 | 0.151316E+09 |
November | 39081145.14 | 0.00 | 39081145.14 | 9122751.29 | 0.176854E+09 |
December | 34160605.09 | 0.00 | 34160605.09 | 4588632.25 | 0.234326E+09 |
Annual Sum or Average | 0.836205E+09 | 26898993.43 | 0.809306E+09 | 0.726490E+09 | 0.149054E+10 |
Minimum of Months | 34160605.09 | 0.00 | 34160605.09 | 4588632.25 | 33793585.16 |
Maximum of Months | 0.113803E+09 | 12726393.75 | 0.103924E+09 | 0.155429E+09 | 0.234326E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350995E+09 | 0.288938E+09 | 62057156.81 | 0.400812E+09 | 0.171654E+09 |
February | 0.299986E+09 | 0.238522E+09 | 61464635.60 | 0.337790E+09 | 0.165628E+09 |
March | 0.249484E+09 | 0.164884E+09 | 84600115.41 | 0.283682E+09 | 0.147821E+09 |
April | 0.158093E+09 | 65402535.88 | 92690045.02 | 0.164185E+09 | 0.130043E+09 |
May | 0.148447E+09 | 28546346.13 | 0.119901E+09 | 0.171555E+09 | 78141790.89 |
June | 0.130611E+09 | 23577363.14 | 0.107033E+09 | 0.191570E+09 | 38863852.26 |
July | 0.139401E+09 | 23747867.99 | 0.115653E+09 | 0.205090E+09 | 36220603.74 |
August | 0.177370E+09 | 72971361.76 | 0.104398E+09 | 0.259526E+09 | 41862727.25 |
September | 0.225474E+09 | 0.126738E+09 | 98735936.14 | 0.306788E+09 | 64127292.20 |
October | 0.275025E+09 | 0.194864E+09 | 80161197.76 | 0.332037E+09 | 0.143665E+09 |
November | 0.326227E+09 | 0.260208E+09 | 66019589.62 | 0.382653E+09 | 0.157084E+09 |
December | 0.321708E+09 | 0.260431E+09 | 61276619.87 | 0.356826E+09 | 0.199607E+09 |
Annual Sum or Average | 0.280282E+10 | 0.174883E+10 | 0.105399E+10 | 0.339251E+10 | 0.137472E+10 |
Minimum of Months | 0.130611E+09 | 23577363.14 | 61276619.87 | 0.164185E+09 | 36220603.74 |
Maximum of Months | 0.350995E+09 | 0.288938E+09 | 0.119901E+09 | 0.400812E+09 | 0.199607E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.952673E+09 | 0.784237E+09 | 0.168436E+09 | 0.108788E+10 | 0.465905E+09 |
February | 0.814224E+09 | 0.647396E+09 | 0.166828E+09 | 0.916832E+09 | 0.449548E+09 |
March | 0.677150E+09 | 0.447528E+09 | 0.229622E+09 | 0.769971E+09 | 0.401218E+09 |
April | 0.429096E+09 | 0.177516E+09 | 0.251580E+09 | 0.445632E+09 | 0.352964E+09 |
May | 0.402915E+09 | 77480622.41 | 0.325435E+09 | 0.465635E+09 | 0.212093E+09 |
June | 0.354504E+09 | 63993786.21 | 0.290510E+09 | 0.519961E+09 | 0.105484E+09 |
July | 0.378364E+09 | 64456571.24 | 0.313907E+09 | 0.556656E+09 | 98310127.30 |
August | 0.481418E+09 | 0.198059E+09 | 0.283359E+09 | 0.704406E+09 | 0.113624E+09 |
September | 0.611982E+09 | 0.343992E+09 | 0.267990E+09 | 0.832684E+09 | 0.174055E+09 |
October | 0.746474E+09 | 0.528901E+09 | 0.217574E+09 | 0.901217E+09 | 0.389937E+09 |
November | 0.885447E+09 | 0.706257E+09 | 0.179191E+09 | 0.103860E+10 | 0.426358E+09 |
December | 0.873180E+09 | 0.706863E+09 | 0.166317E+09 | 0.968498E+09 | 0.541775E+09 |
Annual Sum or Average | 0.760743E+10 | 0.474668E+10 | 0.286075E+10 | 0.920798E+10 | 0.373127E+10 |
Minimum of Months | 0.354504E+09 | 63993786.21 | 0.166317E+09 | 0.445632E+09 | 98310127.30 |
Maximum of Months | 0.952673E+09 | 0.784237E+09 | 0.325435E+09 | 0.108788E+10 | 0.541775E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.852158E+09 | 0.351224E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.715605E+09 | 0.340175E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.599414E+09 | 0.300446E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.344782E+09 | 0.264643E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.358783E+09 | 0.156896E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.408535E+09 | 70342538.83 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.439555E+09 | 62559862.02 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.553823E+09 | 75024618.92 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.653562E+09 | 0.122442E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.704956E+09 | 0.285337E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.812038E+09 | 0.319537E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.758775E+09 | 0.410305E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.720199E+10 | 0.275893E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.344782E+09 | 62559862.02 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.852158E+09 | 0.410305E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.439542E+09 | 0.724530E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.471547E+09 | 0.679747E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.656402E+09 | 0.568652E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.575391E+09 | 0.480982E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.883845E+09 | 0.281982E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.127620E+10 | 0.129265E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.108444E+10 | 0.115051E+09 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.110713E+10 | 0.136470E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.903263E+09 | 0.228515E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.640983E+09 | 0.546417E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.455071E+09 | 0.634066E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.329878E+09 | 0.836621E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.882369E+10 | 0.536230E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.329878E+09 | 0.115051E+09 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.127620E+10 | 0.836621E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 15731433.51 | 0.400143E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 16050730.53 | 0.377690E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 57683710.21 | 0.314562E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 85591197.41 | 0.260323E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.206541E+09 | 0.143553E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.333003E+09 | 64242633.15 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.333745E+09 | 58460322.79 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.252366E+09 | 70679329.18 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.180570E+09 | 0.120604E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 63684933.20 | 0.293668E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 23873256.38 | 0.346362E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 13001495.01 | 0.464950E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.158184E+10 | 0.291524E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 13001495.01 | 58460322.79 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.333745E+09 | 0.464950E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.462572E+09 | 0.706089E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.492489E+09 | 0.665557E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.674680E+09 | 0.559647E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.585843E+09 | 0.476641E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.889277E+09 | 0.280108E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.127760E+10 | 0.128643E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.108667E+10 | 0.114084E+09 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.111427E+10 | 0.133821E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.915982E+09 | 0.221825E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.660177E+09 | 0.535043E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.476655E+09 | 0.618409E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.348463E+09 | 0.820899E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.898467E+10 | 0.526077E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.348463E+09 | 0.114084E+09 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.127760E+10 | 0.820899E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110324E+10 | 0.908185E+09 | 0.195057E+09 | 0.122698E+10 | 0.534045E+09 |
February | 0.942911E+09 | 0.749717E+09 | 0.193195E+09 | 0.103165E+10 | 0.514236E+09 |
March | 0.784173E+09 | 0.518259E+09 | 0.265914E+09 | 0.868437E+09 | 0.448897E+09 |
April | 0.496914E+09 | 0.205572E+09 | 0.291342E+09 | 0.501027E+09 | 0.392032E+09 |
May | 0.466596E+09 | 89726356.12 | 0.376869E+09 | 0.531067E+09 | 0.225380E+09 |
June | 0.410533E+09 | 74107939.14 | 0.336425E+09 | 0.611515E+09 | 95925880.40 |
July | 0.438164E+09 | 74643866.89 | 0.363520E+09 | 0.654387E+09 | 86572305.60 |
August | 0.557506E+09 | 0.229362E+09 | 0.328143E+09 | 0.818365E+09 | 0.104568E+09 |
September | 0.708705E+09 | 0.398360E+09 | 0.310345E+09 | 0.957601E+09 | 0.177782E+09 |
October | 0.864454E+09 | 0.612493E+09 | 0.251961E+09 | 0.102519E+10 | 0.428117E+09 |
November | 0.102539E+10 | 0.817880E+09 | 0.207512E+09 | 0.117254E+10 | 0.485731E+09 |
December | 0.101119E+10 | 0.818582E+09 | 0.192604E+09 | 0.108884E+10 | 0.625106E+09 |
Annual Sum or Average | 0.880977E+10 | 0.549689E+10 | 0.331288E+10 | 0.104876E+11 | 0.411839E+10 |
Minimum of Months | 0.410533E+09 | 74107939.14 | 0.192604E+09 | 0.501027E+09 | 86572305.60 |
Maximum of Months | 0.110324E+10 | 0.908185E+09 | 0.376869E+09 | 0.122698E+10 | 0.625106E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.547417E+09 | 0.00 | 0.547417E+09 | 55356045.57 | 0.335623E+10 |
February | 0.621453E+09 | 0.00 | 0.621453E+09 | 61777369.29 | 0.314205E+10 |
March | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.305952E+09 | 0.263648E+10 |
April | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.489327E+09 | 0.222599E+10 |
May | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.132893E+10 | 0.119688E+10 |
June | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.226069E+10 | 0.552301E+09 |
July | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.225905E+10 | 0.529699E+09 |
August | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.169894E+10 | 0.626717E+09 |
September | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.119134E+10 | 0.101096E+10 |
October | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.360346E+09 | 0.245150E+10 |
November | 0.585951E+09 | 0.00 | 0.585951E+09 | 0.105638E+09 | 0.292982E+10 |
December | 0.512176E+09 | 0.00 | 0.512176E+09 | 45976339.81 | 0.386778E+10 |
Annual Sum or Average | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.101633E+11 | 0.245264E+11 |
Minimum of Months | 0.512176E+09 | 0.00 | 0.512176E+09 | 45976339.81 | 0.529699E+09 |
Maximum of Months | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.226069E+10 | 0.386778E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.547417E+09 | 0.00 | 0.547417E+09 | 48242197.41 | 0.342695E+10 |
February | 0.621453E+09 | 0.00 | 0.621453E+09 | 56667788.71 | 0.321041E+10 |
March | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.290230E+09 | 0.269416E+10 |
April | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.469629E+09 | 0.227577E+10 |
May | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.130350E+10 | 0.122055E+10 |
June | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.223976E+10 | 0.565710E+09 |
July | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.223812E+10 | 0.544067E+09 |
August | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.167991E+10 | 0.643224E+09 |
September | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.117472E+10 | 0.103226E+10 |
October | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.346042E+09 | 0.249882E+10 |
November | 0.585951E+09 | 0.00 | 0.585951E+09 | 98629646.65 | 0.299315E+10 |
December | 0.512176E+09 | 0.00 | 0.512176E+09 | 41060624.79 | 0.395219E+10 |
Annual Sum or Average | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.998652E+10 | 0.250573E+11 |
Minimum of Months | 0.512176E+09 | 0.00 | 0.512176E+09 | 41060624.79 | 0.544067E+09 |
Maximum of Months | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.223976E+10 | 0.395219E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 14879477.02 | 0.439671E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 14365230.09 | 0.418219E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 59044164.03 | 0.354331E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 89332360.95 | 0.301554E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.236190E+09 | 0.167887E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.378801E+09 | 81685561.18 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.379744E+09 | 78510772.59 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.296269E+09 | 89030783.06 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.212528E+09 | 0.136899E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 71271232.16 | 0.324882E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 24458182.66 | 0.384065E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 11111086.79 | 0.516058E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.178799E+10 | 0.329279E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 11111086.79 | 78510772.59 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.379744E+09 | 0.516058E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.911470E+09 | 0.557490E+09 | 0.353981E+09 | 0.804719E+09 | 0.151608E+10 |
February | 0.110365E+10 | 0.698492E+09 | 0.405159E+09 | 0.102465E+10 | 0.146456E+10 |
March | 0.147191E+10 | 0.859162E+09 | 0.612752E+09 | 0.149008E+10 | 0.124607E+10 |
April | 0.145410E+10 | 0.708216E+09 | 0.745881E+09 | 0.144831E+10 | 0.108907E+10 |
May | 0.176151E+10 | 0.737435E+09 | 0.102408E+10 | 0.211040E+10 | 0.622687E+09 |
June | 0.207428E+10 | 0.108865E+10 | 0.985627E+09 | 0.299385E+10 | 0.306638E+09 |
July | 0.194554E+10 | 0.924497E+09 | 0.102105E+10 | 0.285812E+10 | 0.294443E+09 |
August | 0.196722E+10 | 0.108383E+10 | 0.883386E+09 | 0.284885E+10 | 0.331502E+09 |
September | 0.158661E+10 | 0.862438E+09 | 0.724173E+09 | 0.217783E+10 | 0.491795E+09 |
October | 0.118641E+10 | 0.650670E+09 | 0.535736E+09 | 0.129437E+10 | 0.117380E+10 |
November | 0.890953E+09 | 0.502095E+09 | 0.388858E+09 | 0.839908E+09 | 0.136004E+10 |
December | 0.798466E+09 | 0.460116E+09 | 0.338350E+09 | 0.651599E+09 | 0.180869E+10 |
Annual Sum or Average | 0.171521E+11 | 0.913309E+10 | 0.801902E+10 | 0.205427E+11 | 0.117054E+11 |
Minimum of Months | 0.798466E+09 | 0.460116E+09 | 0.338350E+09 | 0.651599E+09 | 0.294443E+09 |
Maximum of Months | 0.207428E+10 | 0.108865E+10 | 0.102408E+10 | 0.299385E+10 | 0.180869E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.870742E+09 | 0.376427E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.729801E+09 | 0.369312E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.616967E+09 | 0.333654E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.356932E+09 | 0.302329E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.393466E+09 | 0.179960E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.455142E+09 | 88349565.74 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.487061E+09 | 82782938.05 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.602659E+09 | 91431977.73 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.696501E+09 | 0.136232E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.732092E+09 | 0.310564E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.831853E+09 | 0.345945E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.768864E+09 | 0.445711E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.754208E+10 | 0.306270E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.356932E+09 | 82782938.05 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.870742E+09 | 0.445711E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 99042143.99 | 0.00 | 99042143.99 | 12463212.14 | 0.560851E+09 |
February | 0.112437E+09 | 0.00 | 0.112437E+09 | 12961494.60 | 0.523592E+09 |
March | 0.169435E+09 | 8743.09 | 0.169426E+09 | 62278061.90 | 0.432123E+09 |
April | 0.206120E+09 | 1350487.19 | 0.204769E+09 | 0.101302E+09 | 0.358197E+09 |
May | 0.290956E+09 | 9758104.85 | 0.281198E+09 | 0.256793E+09 | 0.199374E+09 |
June | 0.308709E+09 | 34522420.75 | 0.274187E+09 | 0.411820E+09 | 97865746.26 |
July | 0.302563E+09 | 20653083.30 | 0.281910E+09 | 0.410917E+09 | 93673870.51 |
August | 0.240897E+09 | 6519178.53 | 0.234377E+09 | 0.308493E+09 | 0.111139E+09 |
September | 0.195197E+09 | 155893.49 | 0.195041E+09 | 0.217683E+09 | 0.175704E+09 |
October | 0.144308E+09 | 0.00 | 0.144308E+09 | 68787287.52 | 0.410708E+09 |
November | 0.106014E+09 | 0.00 | 0.106014E+09 | 20990765.99 | 0.487044E+09 |
December | 92666218.35 | 0.00 | 92666218.35 | 10140789.14 | 0.646891E+09 |
Annual Sum or Average | 0.226834E+10 | 72967911.20 | 0.219538E+10 | 0.189463E+10 | 0.409716E+10 |
Minimum of Months | 92666218.35 | 0.00 | 92666218.35 | 10140789.14 | 93673870.51 |
Maximum of Months | 0.308709E+09 | 34522420.75 | 0.281910E+09 | 0.411820E+09 | 0.646891E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88613381.50 | 0.00 | 88613381.50 | 11150883.12 | 0.501716E+09 |
February | 0.100598E+09 | 0.00 | 0.100598E+09 | 11596698.33 | 0.468465E+09 |
March | 0.151594E+09 | 7822.48 | 0.151586E+09 | 55720417.95 | 0.386622E+09 |
April | 0.184416E+09 | 1208286.00 | 0.183208E+09 | 90635263.60 | 0.320480E+09 |
May | 0.260319E+09 | 8730613.39 | 0.251589E+09 | 0.229754E+09 | 0.178380E+09 |
June | 0.276203E+09 | 30887340.65 | 0.245316E+09 | 0.368457E+09 | 87560853.99 |
July | 0.270705E+09 | 18478391.88 | 0.252226E+09 | 0.367649E+09 | 83810366.87 |
August | 0.215531E+09 | 5832733.73 | 0.209698E+09 | 0.276010E+09 | 99436538.04 |
September | 0.174644E+09 | 139478.49 | 0.174504E+09 | 0.194762E+09 | 0.157203E+09 |
October | 0.129113E+09 | 0.00 | 0.129113E+09 | 61544246.77 | 0.367462E+09 |
November | 94851115.46 | 0.00 | 94851115.46 | 18780517.86 | 0.435748E+09 |
December | 82908816.67 | 0.00 | 82908816.67 | 9073002.47 | 0.578729E+09 |
Annual Sum or Average | 0.202950E+10 | 65284666.62 | 0.196421E+10 | 0.169513E+10 | 0.366561E+10 |
Minimum of Months | 82908816.67 | 0.00 | 82908816.67 | 9073002.47 | 83810366.87 |
Maximum of Months | 0.276203E+09 | 30887340.65 | 0.252226E+09 | 0.368457E+09 | 0.578729E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.280836E+10 | 0.231183E+10 | 0.496528E+09 | 0.317353E+10 | 0.138162E+10 |
February | 0.240023E+10 | 0.190844E+10 | 0.491787E+09 | 0.266673E+10 | 0.134230E+10 |
March | 0.199615E+10 | 0.131926E+10 | 0.676897E+09 | 0.223378E+10 | 0.119655E+10 |
April | 0.126492E+10 | 0.523295E+09 | 0.741626E+09 | 0.128190E+10 | 0.106204E+10 |
May | 0.118774E+10 | 0.228403E+09 | 0.959340E+09 | 0.133614E+10 | 0.637879E+09 |
June | 0.104503E+10 | 0.188646E+09 | 0.856387E+09 | 0.150181E+10 | 0.318622E+09 |
July | 0.111537E+10 | 0.190010E+09 | 0.925359E+09 | 0.161291E+10 | 0.296404E+09 |
August | 0.141916E+10 | 0.583854E+09 | 0.835306E+09 | 0.204647E+10 | 0.340374E+09 |
September | 0.180405E+10 | 0.101405E+10 | 0.790000E+09 | 0.242814E+10 | 0.511280E+09 |
October | 0.220051E+10 | 0.155913E+10 | 0.641381E+09 | 0.262986E+10 | 0.115029E+10 |
November | 0.261019E+10 | 0.208196E+10 | 0.528232E+09 | 0.302605E+10 | 0.126989E+10 |
December | 0.257403E+10 | 0.208374E+10 | 0.490283E+09 | 0.281810E+10 | 0.162079E+10 |
Annual Sum or Average | 0.224257E+11 | 0.139926E+11 | 0.843312E+10 | 0.267554E+11 | 0.111280E+11 |
Minimum of Months | 0.104503E+10 | 0.188646E+09 | 0.490283E+09 | 0.128190E+10 | 0.296404E+09 |
Maximum of Months | 0.280836E+10 | 0.231183E+10 | 0.959340E+09 | 0.317353E+10 | 0.162079E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1584.94 | 674.33 | 1420.50 | 1169.35 | 251.15 | 0.00 | 0.00 |
February | 1484.47 | 707.80 | 1344.14 | 1068.74 | 275.40 | 0.00 | 0.00 |
March | 1127.54 | 565.27 | 1009.67 | 667.29 | 342.38 | 0.00 | 0.00 |
April | 674.43 | 507.55 | 661.13 | 273.51 | 387.62 | 0.00 | 0.00 |
May | 683.40 | 290.80 | 600.77 | 115.53 | 485.24 | 0.00 | 0.00 |
June | 779.62 | 156.66 | 546.20 | 98.60 | 447.60 | 0.00 | 0.00 |
July | 809.55 | 140.16 | 564.16 | 96.11 | 468.05 | 0.00 | 0.00 |
August | 1028.58 | 163.71 | 717.82 | 295.32 | 422.50 | 0.00 | 0.00 |
September | 1260.35 | 256.78 | 942.92 | 530.01 | 412.91 | 0.00 | 0.00 |
October | 1320.37 | 546.17 | 1113.04 | 788.63 | 324.41 | 0.00 | 0.00 |
November | 1564.95 | 633.09 | 1364.27 | 1088.18 | 276.09 | 0.00 | 0.00 |
December | 1421.09 | 769.46 | 1301.97 | 1053.98 | 247.99 | 0.00 | 0.00 |
Annual Sum or Average | 1142.97 | 449.56 | 963.39 | 601.11 | 362.28 | 0.00 | 0.00 |
Minimum of Months | 674.43 | 140.16 | 546.20 | 96.11 | 247.99 | 0.00 | 0.00 |
Maximum of Months | 1584.94 | 769.46 | 1420.50 | 1169.35 | 485.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4421.27 | 2005.73 | 4000.02 | 3292.81 | 707.21 | 0.00 | 0.00 |
February | 4140.53 | 2087.16 | 3785.00 | 3009.49 | 775.51 | 0.00 | 0.00 |
March | 3138.77 | 1685.02 | 2843.17 | 1879.05 | 964.11 | 0.00 | 0.00 |
April | 1862.11 | 1536.70 | 1861.71 | 770.19 | 1091.52 | 0.00 | 0.00 |
May | 1868.30 | 908.46 | 1691.72 | 325.32 | 1366.40 | 0.00 | 0.00 |
June | 2164.17 | 471.17 | 1538.07 | 277.65 | 1260.42 | 0.00 | 0.00 |
July | 2248.60 | 424.54 | 1588.64 | 270.64 | 1318.00 | 0.00 | 0.00 |
August | 2865.61 | 493.39 | 2021.34 | 831.60 | 1189.74 | 0.00 | 0.00 |
September | 3518.12 | 768.11 | 2655.19 | 1492.48 | 1162.71 | 0.00 | 0.00 |
October | 3685.97 | 1626.46 | 3134.24 | 2220.72 | 913.53 | 0.00 | 0.00 |
November | 4369.11 | 1882.79 | 3841.68 | 3064.24 | 777.45 | 0.00 | 0.00 |
December | 3963.20 | 2269.58 | 3666.25 | 2967.93 | 698.32 | 0.00 | 0.00 |
Annual Sum or Average | 3181.60 | 1342.50 | 2712.84 | 1692.69 | 1020.15 | 0.00 | 0.00 |
Minimum of Months | 1862.11 | 424.54 | 1538.07 | 270.64 | 698.32 | 0.00 | 0.00 |
Maximum of Months | 4421.27 | 2269.58 | 4000.02 | 3292.81 | 1366.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5837.24 | 2682.55 | 5196.26 | 4277.55 | 918.71 | 0.00 | 0.00 |
February | 5475.05 | 2801.64 | 4916.93 | 3909.50 | 1007.43 | 0.00 | 0.00 |
March | 4151.32 | 2281.05 | 3693.44 | 2441.00 | 1252.44 | 0.00 | 0.00 |
April | 2464.37 | 2103.42 | 2418.46 | 1000.52 | 1417.94 | 0.00 | 0.00 |
May | 2477.74 | 1221.20 | 2197.65 | 422.61 | 1775.03 | 0.00 | 0.00 |
June | 2886.26 | 618.72 | 1998.04 | 360.68 | 1637.36 | 0.00 | 0.00 |
July | 2996.97 | 556.07 | 2063.73 | 351.57 | 1712.16 | 0.00 | 0.00 |
August | 3809.60 | 641.84 | 2625.83 | 1080.29 | 1545.53 | 0.00 | 0.00 |
September | 4663.61 | 1005.53 | 3449.25 | 1938.81 | 1510.43 | 0.00 | 0.00 |
October | 4870.56 | 2184.71 | 4071.56 | 2884.84 | 1186.73 | 0.00 | 0.00 |
November | 5770.63 | 2523.42 | 4990.57 | 3980.62 | 1009.95 | 0.00 | 0.00 |
December | 5231.02 | 3049.03 | 4762.67 | 3855.52 | 907.16 | 0.00 | 0.00 |
Annual Sum or Average | 4212.21 | 1800.24 | 3524.13 | 2198.90 | 1325.23 | 0.00 | 0.00 |
Minimum of Months | 2464.37 | 556.07 | 1998.04 | 351.57 | 907.16 | 0.00 | 0.00 |
Maximum of Months | 5837.24 | 3049.03 | 5196.26 | 4277.55 | 1775.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 464.08 | 384.23 | 462.62 | 346.40 | 116.23 | 0.00 | 0.00 |
February | 478.27 | 406.13 | 485.34 | 347.52 | 137.82 | 0.00 | 0.00 |
March | 465.74 | 318.16 | 455.70 | 272.99 | 182.71 | 0.00 | 0.00 |
April | 355.16 | 284.55 | 372.24 | 156.39 | 215.85 | 0.00 | 0.00 |
May | 467.00 | 161.84 | 414.08 | 127.13 | 286.95 | 0.00 | 0.00 |
June | 653.27 | 77.37 | 468.51 | 192.81 | 275.70 | 0.00 | 0.00 |
July | 571.58 | 66.96 | 404.96 | 126.13 | 278.83 | 0.00 | 0.00 |
August | 623.01 | 79.11 | 449.18 | 210.23 | 238.95 | 0.00 | 0.00 |
September | 602.52 | 135.19 | 459.81 | 236.32 | 223.49 | 0.00 | 0.00 |
October | 501.60 | 308.04 | 448.99 | 286.77 | 162.22 | 0.00 | 0.00 |
November | 480.43 | 358.53 | 457.72 | 329.32 | 128.40 | 0.00 | 0.00 |
December | 387.87 | 445.45 | 409.03 | 297.91 | 111.12 | 0.00 | 0.00 |
Annual Sum or Average | 504.22 | 251.28 | 440.33 | 243.48 | 196.85 | 0.00 | 0.00 |
Minimum of Months | 355.16 | 66.96 | 372.24 | 126.13 | 111.12 | 0.00 | 0.00 |
Maximum of Months | 653.27 | 445.45 | 485.34 | 347.52 | 286.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.00 | 408.24 | 210.96 | 115.20 | 95.77 | 0.00 | 0.00 |
February | 201.99 | 423.29 | 256.28 | 136.21 | 120.07 | 0.00 | 0.00 |
March | 270.44 | 322.52 | 306.02 | 141.06 | 164.96 | 0.00 | 0.00 |
April | 259.08 | 282.35 | 304.32 | 102.72 | 201.59 | 0.00 | 0.00 |
May | 411.54 | 156.22 | 381.08 | 107.17 | 273.91 | 0.00 | 0.00 |
June | 622.60 | 72.89 | 454.56 | 183.84 | 270.73 | 0.00 | 0.00 |
July | 531.46 | 63.88 | 382.62 | 113.22 | 269.40 | 0.00 | 0.00 |
August | 512.36 | 76.66 | 378.27 | 153.76 | 224.51 | 0.00 | 0.00 |
September | 423.76 | 132.86 | 332.84 | 131.57 | 201.27 | 0.00 | 0.00 |
October | 268.60 | 309.11 | 271.47 | 130.85 | 140.62 | 0.00 | 0.00 |
November | 187.77 | 369.19 | 220.28 | 114.17 | 106.10 | 0.00 | 0.00 |
December | 127.05 | 473.53 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Annual Sum or Average | 332.84 | 256.67 | 306.64 | 126.46 | 180.19 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 63.88 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Maximum of Months | 622.60 | 473.53 | 454.56 | 183.84 | 273.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 251.00 | 114.60 | 224.64 | 184.92 | 39.72 | 0.00 | 0.00 |
February | 234.46 | 118.56 | 212.57 | 169.01 | 43.55 | 0.00 | 0.00 |
March | 178.81 | 93.14 | 159.67 | 105.53 | 54.14 | 0.00 | 0.00 |
April | 107.09 | 84.35 | 104.55 | 43.25 | 61.30 | 0.00 | 0.00 |
May | 107.56 | 50.30 | 95.01 | 18.27 | 76.74 | 0.00 | 0.00 |
June | 127.28 | 24.43 | 86.38 | 15.59 | 70.79 | 0.00 | 0.00 |
July | 132.12 | 21.71 | 89.22 | 15.20 | 74.02 | 0.00 | 0.00 |
August | 166.32 | 25.42 | 113.52 | 46.70 | 66.82 | 0.00 | 0.00 |
September | 202.04 | 41.46 | 149.12 | 83.82 | 65.30 | 0.00 | 0.00 |
October | 210.02 | 91.51 | 176.02 | 124.71 | 51.30 | 0.00 | 0.00 |
November | 248.51 | 107.16 | 215.75 | 172.09 | 43.66 | 0.00 | 0.00 |
December | 224.17 | 129.56 | 205.90 | 166.68 | 39.22 | 0.00 | 0.00 |
Annual Sum or Average | 182.14 | 74.94 | 152.35 | 95.06 | 57.29 | 0.00 | 0.00 |
Minimum of Months | 107.09 | 21.71 | 86.38 | 15.20 | 39.22 | 0.00 | 0.00 |
Maximum of Months | 251.00 | 129.56 | 224.64 | 184.92 | 76.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.53 | 123.07 | 23.36 | 0.00 | 23.36 | 0.00 | 0.00 |
February | 5.53 | 127.19 | 29.36 | 0.00 | 29.36 | 0.00 | 0.00 |
March | 18.59 | 94.50 | 39.97 | 0.00 | 39.96 | 0.00 | 0.00 |
April | 28.20 | 81.41 | 50.24 | 0.33 | 49.91 | 0.00 | 0.00 |
May | 66.45 | 41.72 | 68.63 | 2.30 | 66.33 | 0.00 | 0.00 |
June | 108.97 | 17.99 | 75.25 | 8.41 | 66.83 | 0.00 | 0.00 |
July | 105.15 | 15.93 | 71.37 | 4.87 | 66.50 | 0.00 | 0.00 |
August | 80.97 | 19.11 | 56.82 | 1.54 | 55.28 | 0.00 | 0.00 |
September | 60.09 | 34.84 | 47.58 | 0.04 | 47.54 | 0.00 | 0.00 |
October | 20.83 | 87.92 | 34.04 | 0.00 | 34.04 | 0.00 | 0.00 |
November | 7.57 | 109.40 | 25.84 | 0.00 | 25.84 | 0.00 | 0.00 |
December | 3.66 | 143.25 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
Annual Sum or Average | 42.75 | 74.41 | 45.44 | 1.46 | 43.98 | 0.00 | 0.00 |
Minimum of Months | 3.66 | 15.93 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
Maximum of Months | 108.97 | 143.25 | 75.25 | 8.41 | 66.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 443.78 | 379.99 | 451.02 | 335.28 | 115.74 | 0.00 | 0.00 |
February | 486.73 | 404.46 | 493.88 | 355.68 | 138.20 | 0.00 | 0.00 |
March | 488.15 | 314.98 | 474.42 | 292.33 | 182.09 | 0.00 | 0.00 |
April | 399.79 | 278.40 | 411.24 | 190.70 | 220.53 | 0.00 | 0.00 |
May | 500.98 | 152.28 | 447.64 | 160.52 | 287.13 | 0.00 | 0.00 |
June | 694.06 | 71.17 | 508.15 | 229.51 | 278.64 | 0.00 | 0.00 |
July | 657.64 | 63.37 | 474.76 | 191.60 | 283.16 | 0.00 | 0.00 |
August | 698.33 | 76.60 | 509.19 | 260.73 | 248.46 | 0.00 | 0.00 |
September | 638.76 | 128.23 | 492.51 | 271.17 | 221.34 | 0.00 | 0.00 |
October | 489.08 | 303.65 | 441.56 | 277.40 | 164.16 | 0.00 | 0.00 |
November | 457.61 | 355.96 | 441.62 | 312.01 | 129.60 | 0.00 | 0.00 |
December | 384.60 | 445.86 | 406.49 | 294.29 | 112.20 | 0.00 | 0.00 |
Annual Sum or Average | 528.42 | 247.06 | 462.44 | 263.66 | 198.78 | 0.00 | 0.00 |
Minimum of Months | 384.60 | 63.37 | 406.49 | 160.52 | 112.20 | 0.00 | 0.00 |
Maximum of Months | 698.33 | 445.86 | 509.19 | 355.68 | 287.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 143.26 | 396.20 | 199.36 | 104.08 | 95.28 | 0.00 | 0.00 |
February | 206.27 | 417.07 | 264.82 | 144.37 | 120.44 | 0.00 | 0.00 |
March | 286.98 | 314.33 | 324.75 | 160.40 | 164.34 | 0.00 | 0.00 |
April | 302.32 | 275.79 | 343.31 | 137.04 | 206.27 | 0.00 | 0.00 |
May | 447.97 | 149.70 | 414.64 | 140.55 | 274.09 | 0.00 | 0.00 |
June | 666.93 | 70.29 | 494.20 | 220.53 | 273.67 | 0.00 | 0.00 |
July | 619.64 | 62.62 | 452.42 | 178.68 | 273.73 | 0.00 | 0.00 |
August | 588.04 | 74.79 | 438.28 | 204.26 | 234.02 | 0.00 | 0.00 |
September | 458.27 | 125.26 | 365.55 | 166.42 | 199.12 | 0.00 | 0.00 |
October | 251.82 | 301.43 | 264.04 | 121.47 | 142.56 | 0.00 | 0.00 |
November | 161.56 | 362.33 | 204.17 | 96.86 | 107.31 | 0.00 | 0.00 |
December | 116.63 | 465.54 | 176.39 | 85.90 | 90.49 | 0.00 | 0.00 |
Annual Sum or Average | 354.88 | 250.39 | 328.76 | 146.64 | 182.12 | 0.00 | 0.00 |
Minimum of Months | 116.63 | 62.62 | 176.39 | 85.90 | 90.49 | 0.00 | 0.00 |
Maximum of Months | 666.93 | 465.54 | 494.20 | 220.53 | 274.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 525.93 | 483.86 | 537.34 | 400.68 | 136.67 | 0.00 | 0.00 |
February | 498.69 | 516.65 | 524.18 | 366.20 | 157.98 | 0.00 | 0.00 |
March | 422.13 | 416.55 | 432.55 | 228.65 | 203.89 | 0.00 | 0.00 |
April | 292.64 | 371.45 | 335.37 | 94.43 | 240.94 | 0.00 | 0.00 |
May | 373.15 | 206.70 | 354.53 | 44.57 | 309.96 | 0.00 | 0.00 |
June | 493.72 | 102.73 | 350.16 | 52.01 | 298.15 | 0.00 | 0.00 |
July | 496.61 | 94.88 | 347.92 | 43.49 | 304.43 | 0.00 | 0.00 |
August | 521.02 | 113.35 | 369.06 | 104.52 | 264.54 | 0.00 | 0.00 |
September | 557.07 | 184.68 | 426.16 | 181.69 | 244.47 | 0.00 | 0.00 |
October | 492.63 | 403.23 | 455.12 | 270.22 | 184.90 | 0.00 | 0.00 |
November | 539.51 | 456.54 | 523.45 | 372.86 | 150.58 | 0.00 | 0.00 |
December | 463.59 | 564.02 | 493.47 | 361.15 | 132.33 | 0.00 | 0.00 |
Annual Sum or Average | 472.87 | 325.17 | 428.55 | 209.14 | 219.41 | 0.00 | 0.00 |
Minimum of Months | 292.64 | 94.88 | 335.37 | 43.49 | 132.33 | 0.00 | 0.00 |
Maximum of Months | 557.07 | 564.02 | 537.34 | 400.68 | 309.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 462.94 | 382.31 | 462.62 | 346.40 | 116.23 | 0.00 | 0.00 |
February | 475.36 | 406.24 | 485.34 | 347.52 | 137.82 | 0.00 | 0.00 |
March | 462.20 | 317.82 | 455.70 | 272.99 | 182.71 | 0.00 | 0.00 |
April | 351.65 | 284.31 | 372.24 | 156.39 | 215.85 | 0.00 | 0.00 |
May | 462.38 | 162.29 | 414.08 | 127.13 | 286.95 | 0.00 | 0.00 |
June | 649.54 | 76.57 | 468.51 | 192.81 | 275.70 | 0.00 | 0.00 |
July | 568.70 | 66.01 | 404.96 | 126.13 | 278.83 | 0.00 | 0.00 |
August | 619.38 | 78.22 | 449.18 | 210.23 | 238.95 | 0.00 | 0.00 |
September | 599.50 | 134.28 | 459.81 | 236.32 | 223.49 | 0.00 | 0.00 |
October | 499.00 | 307.03 | 448.99 | 286.77 | 162.22 | 0.00 | 0.00 |
November | 478.24 | 357.29 | 457.72 | 329.32 | 128.40 | 0.00 | 0.00 |
December | 386.21 | 445.30 | 409.03 | 297.91 | 111.12 | 0.00 | 0.00 |
Annual Sum or Average | 501.27 | 250.62 | 440.33 | 243.48 | 196.85 | 0.00 | 0.00 |
Minimum of Months | 351.65 | 66.01 | 372.24 | 126.13 | 111.12 | 0.00 | 0.00 |
Maximum of Months | 649.54 | 445.30 | 485.34 | 347.52 | 286.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.53 | 404.97 | 210.96 | 115.20 | 95.77 | 0.00 | 0.00 |
February | 201.35 | 422.38 | 256.28 | 136.21 | 120.07 | 0.00 | 0.00 |
March | 268.64 | 321.60 | 306.02 | 141.06 | 164.96 | 0.00 | 0.00 |
April | 256.55 | 281.83 | 304.32 | 102.72 | 201.59 | 0.00 | 0.00 |
May | 407.39 | 156.44 | 381.08 | 107.17 | 273.91 | 0.00 | 0.00 |
June | 619.26 | 72.30 | 454.56 | 183.84 | 270.73 | 0.00 | 0.00 |
July | 528.98 | 63.08 | 382.62 | 113.22 | 269.40 | 0.00 | 0.00 |
August | 509.61 | 75.72 | 378.27 | 153.76 | 224.51 | 0.00 | 0.00 |
September | 422.26 | 131.32 | 332.84 | 131.57 | 201.27 | 0.00 | 0.00 |
October | 267.83 | 306.97 | 271.47 | 130.85 | 140.62 | 0.00 | 0.00 |
November | 187.63 | 366.74 | 220.28 | 114.17 | 106.10 | 0.00 | 0.00 |
December | 127.30 | 472.43 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Annual Sum or Average | 331.23 | 255.42 | 306.64 | 126.46 | 180.19 | 0.00 | 0.00 |
Minimum of Months | 127.30 | 63.08 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Maximum of Months | 619.26 | 472.43 | 454.56 | 183.84 | 273.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 458.10 | 199.39 | 411.90 | 339.08 | 72.83 | 0.00 | 0.00 |
February | 426.44 | 212.56 | 389.76 | 309.90 | 79.86 | 0.00 | 0.00 |
March | 324.24 | 167.60 | 292.78 | 193.50 | 99.28 | 0.00 | 0.00 |
April | 193.30 | 151.25 | 191.71 | 79.31 | 112.40 | 0.00 | 0.00 |
May | 198.28 | 84.15 | 174.21 | 33.50 | 140.71 | 0.00 | 0.00 |
June | 235.92 | 37.01 | 158.38 | 28.59 | 129.79 | 0.00 | 0.00 |
July | 244.32 | 32.32 | 163.59 | 27.87 | 135.72 | 0.00 | 0.00 |
August | 305.54 | 39.04 | 208.15 | 85.63 | 122.51 | 0.00 | 0.00 |
September | 369.45 | 68.59 | 273.42 | 153.69 | 119.73 | 0.00 | 0.00 |
October | 382.76 | 159.84 | 322.75 | 228.68 | 94.07 | 0.00 | 0.00 |
November | 452.37 | 187.40 | 395.60 | 315.54 | 80.06 | 0.00 | 0.00 |
December | 406.53 | 233.39 | 377.53 | 305.62 | 71.91 | 0.00 | 0.00 |
Annual Sum or Average | 332.56 | 130.59 | 279.36 | 174.31 | 105.05 | 0.00 | 0.00 |
Minimum of Months | 193.30 | 32.32 | 158.38 | 27.87 | 71.91 | 0.00 | 0.00 |
Maximum of Months | 458.10 | 233.39 | 411.90 | 339.08 | 140.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.67 | 1253.07 | 204.38 | 0.00 | 204.38 | 0.00 | 0.00 |
February | 25.54 | 1298.80 | 256.88 | 0.00 | 256.88 | 0.00 | 0.00 |
March | 114.23 | 984.35 | 349.64 | 0.02 | 349.63 | 0.00 | 0.00 |
April | 188.78 | 858.79 | 439.52 | 2.88 | 436.64 | 0.00 | 0.00 |
May | 496.17 | 446.87 | 600.41 | 20.14 | 580.28 | 0.00 | 0.00 |
June | 872.18 | 213.08 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
July | 843.43 | 197.77 | 624.37 | 42.62 | 581.75 | 0.00 | 0.00 |
August | 634.31 | 233.99 | 497.11 | 13.45 | 483.66 | 0.00 | 0.00 |
September | 459.62 | 390.03 | 416.23 | 0.33 | 415.90 | 0.00 | 0.00 |
October | 134.54 | 915.29 | 297.79 | 0.00 | 297.79 | 0.00 | 0.00 |
November | 40.76 | 1130.33 | 226.06 | 0.00 | 226.06 | 0.00 | 0.00 |
December | 17.17 | 1444.06 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Annual Sum or Average | 322.28 | 777.73 | 397.56 | 12.79 | 384.77 | 0.00 | 0.00 |
Minimum of Months | 17.17 | 197.77 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Maximum of Months | 872.18 | 1444.06 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.01 | 1279.48 | 204.38 | 0.00 | 204.38 | 0.00 | 0.00 |
February | 23.42 | 1327.05 | 256.88 | 0.00 | 256.88 | 0.00 | 0.00 |
March | 108.36 | 1005.89 | 349.64 | 0.02 | 349.63 | 0.00 | 0.00 |
April | 181.18 | 878.00 | 439.52 | 2.88 | 436.64 | 0.00 | 0.00 |
May | 486.67 | 455.70 | 600.41 | 20.14 | 580.28 | 0.00 | 0.00 |
June | 864.10 | 218.25 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
July | 835.62 | 203.13 | 624.37 | 42.62 | 581.75 | 0.00 | 0.00 |
August | 627.21 | 240.15 | 497.11 | 13.45 | 483.66 | 0.00 | 0.00 |
September | 453.21 | 398.25 | 416.23 | 0.33 | 415.90 | 0.00 | 0.00 |
October | 129.20 | 932.95 | 297.79 | 0.00 | 297.79 | 0.00 | 0.00 |
November | 38.05 | 1154.76 | 226.06 | 0.00 | 226.06 | 0.00 | 0.00 |
December | 15.33 | 1475.58 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Annual Sum or Average | 316.67 | 794.56 | 397.56 | 12.79 | 384.77 | 0.00 | 0.00 |
Minimum of Months | 15.33 | 203.13 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Maximum of Months | 864.10 | 1475.58 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 583.00 | 822.63 | 650.36 | 439.34 | 211.02 | 0.00 | 0.00 |
February | 690.38 | 890.15 | 758.66 | 500.04 | 258.63 | 0.00 | 0.00 |
March | 795.93 | 709.30 | 799.13 | 452.71 | 346.42 | 0.00 | 0.00 |
April | 722.47 | 644.69 | 754.50 | 327.72 | 426.78 | 0.00 | 0.00 |
May | 1017.41 | 356.74 | 862.23 | 301.05 | 561.19 | 0.00 | 0.00 |
June | 1474.10 | 181.23 | 1002.30 | 450.02 | 552.28 | 0.00 | 0.00 |
July | 1389.11 | 168.53 | 927.13 | 370.26 | 556.87 | 0.00 | 0.00 |
August | 1397.80 | 189.68 | 947.42 | 464.97 | 482.45 | 0.00 | 0.00 |
September | 1187.25 | 291.44 | 858.01 | 437.57 | 420.44 | 0.00 | 0.00 |
October | 776.78 | 669.07 | 705.56 | 398.86 | 306.71 | 0.00 | 0.00 |
November | 627.00 | 778.94 | 645.77 | 408.86 | 236.91 | 0.00 | 0.00 |
December | 485.17 | 985.06 | 582.85 | 380.18 | 202.68 | 0.00 | 0.00 |
Annual Sum or Average | 930.02 | 555.47 | 791.17 | 410.29 | 380.88 | 0.00 | 0.00 |
Minimum of Months | 485.17 | 168.53 | 582.85 | 301.05 | 202.68 | 0.00 | 0.00 |
Maximum of Months | 1474.10 | 985.06 | 1002.30 | 500.04 | 561.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1137.08 | 855.96 | 1118.58 | 863.14 | 255.44 | 0.00 | 0.00 |
February | 1067.70 | 920.16 | 1080.22 | 788.87 | 291.35 | 0.00 | 0.00 |
March | 867.48 | 741.85 | 865.14 | 492.56 | 372.58 | 0.00 | 0.00 |
April | 567.65 | 670.61 | 638.68 | 202.88 | 435.80 | 0.00 | 0.00 |
May | 677.35 | 376.03 | 649.28 | 92.18 | 557.10 | 0.00 | 0.00 |
June | 873.86 | 187.89 | 628.84 | 98.02 | 530.82 | 0.00 | 0.00 |
July | 888.73 | 172.78 | 630.46 | 85.55 | 544.91 | 0.00 | 0.00 |
August | 981.05 | 204.46 | 700.26 | 222.60 | 477.67 | 0.00 | 0.00 |
September | 1094.99 | 324.78 | 838.69 | 391.34 | 447.36 | 0.00 | 0.00 |
October | 1021.88 | 711.35 | 923.66 | 582.11 | 341.55 | 0.00 | 0.00 |
November | 1148.74 | 811.88 | 1084.51 | 803.22 | 281.29 | 0.00 | 0.00 |
December | 1002.36 | 1005.75 | 1026.58 | 777.98 | 248.60 | 0.00 | 0.00 |
Annual Sum or Average | 943.31 | 580.09 | 847.40 | 448.09 | 399.31 | 0.00 | 0.00 |
Minimum of Months | 567.65 | 172.78 | 628.84 | 85.55 | 248.60 | 0.00 | 0.00 |
Maximum of Months | 1148.74 | 1005.75 | 1118.58 | 863.14 | 557.10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424509E+10 | 0.180612E+10 | 0.380465E+10 | 0.313198E+10 | 0.672671E+09 | 0.00 | 0.00 |
February | 0.359123E+10 | 0.171231E+10 | 0.325173E+10 | 0.258549E+10 | 0.666247E+09 | 0.00 | 0.00 |
March | 0.301999E+10 | 0.151401E+10 | 0.270430E+10 | 0.178728E+10 | 0.917025E+09 | 0.00 | 0.00 |
April | 0.174813E+10 | 0.131558E+10 | 0.171366E+10 | 0.708940E+09 | 0.100472E+10 | 0.00 | 0.00 |
May | 0.183041E+10 | 0.778891E+09 | 0.160910E+10 | 0.309432E+09 | 0.129967E+10 | 0.00 | 0.00 |
June | 0.202078E+10 | 0.406060E+09 | 0.141576E+10 | 0.255570E+09 | 0.116019E+10 | 0.00 | 0.00 |
July | 0.216829E+10 | 0.375401E+09 | 0.151105E+10 | 0.257418E+09 | 0.125363E+10 | 0.00 | 0.00 |
August | 0.275496E+10 | 0.438468E+09 | 0.192261E+10 | 0.790983E+09 | 0.113163E+10 | 0.00 | 0.00 |
September | 0.326683E+10 | 0.665578E+09 | 0.244404E+10 | 0.137379E+10 | 0.107025E+10 | 0.00 | 0.00 |
October | 0.353648E+10 | 0.146286E+10 | 0.298116E+10 | 0.211225E+10 | 0.868910E+09 | 0.00 | 0.00 |
November | 0.405635E+10 | 0.164098E+10 | 0.353618E+10 | 0.282056E+10 | 0.715622E+09 | 0.00 | 0.00 |
December | 0.380624E+10 | 0.206093E+10 | 0.348719E+10 | 0.282298E+10 | 0.664211E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360448E+11 | 0.141772E+11 | 0.303814E+11 | 0.189567E+11 | 0.114248E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174813E+10 | 0.375401E+09 | 0.141576E+10 | 0.255570E+09 | 0.664211E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424509E+10 | 0.206093E+10 | 0.380465E+10 | 0.313198E+10 | 0.129967E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118419E+11 | 0.537214E+10 | 0.107137E+11 | 0.881946E+10 | 0.189420E+10 | 0.00 | 0.00 |
February | 0.100168E+11 | 0.504927E+10 | 0.915667E+10 | 0.728056E+10 | 0.187611E+10 | 0.00 | 0.00 |
March | 0.840688E+10 | 0.451315E+10 | 0.761514E+10 | 0.503286E+10 | 0.258228E+10 | 0.00 | 0.00 |
April | 0.482658E+10 | 0.398313E+10 | 0.482554E+10 | 0.199633E+10 | 0.282922E+10 | 0.00 | 0.00 |
May | 0.500405E+10 | 0.243323E+10 | 0.453111E+10 | 0.871340E+09 | 0.365977E+10 | 0.00 | 0.00 |
June | 0.560954E+10 | 0.122127E+10 | 0.398667E+10 | 0.719668E+09 | 0.326701E+10 | 0.00 | 0.00 |
July | 0.602264E+10 | 0.113709E+10 | 0.425500E+10 | 0.724873E+09 | 0.353013E+10 | 0.00 | 0.00 |
August | 0.767526E+10 | 0.132150E+10 | 0.541394E+10 | 0.222736E+10 | 0.318659E+10 | 0.00 | 0.00 |
September | 0.911896E+10 | 0.199095E+10 | 0.688226E+10 | 0.386850E+10 | 0.301376E+10 | 0.00 | 0.00 |
October | 0.987249E+10 | 0.435630E+10 | 0.839476E+10 | 0.594797E+10 | 0.244679E+10 | 0.00 | 0.00 |
November | 0.113247E+11 | 0.488018E+10 | 0.995764E+10 | 0.794250E+10 | 0.201515E+10 | 0.00 | 0.00 |
December | 0.106150E+11 | 0.607885E+10 | 0.981969E+10 | 0.794932E+10 | 0.187038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100335E+12 | 0.423371E+11 | 0.855521E+11 | 0.533807E+11 | 0.321714E+11 | 0.00 | 0.00 |
Minimum of Months | 0.482658E+10 | 0.113709E+10 | 0.398667E+10 | 0.719668E+09 | 0.187038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118419E+11 | 0.607885E+10 | 0.107137E+11 | 0.881946E+10 | 0.365977E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.156345E+11 | 0.718494E+10 | 0.139177E+11 | 0.114570E+11 | 0.246067E+10 | 0.00 | 0.00 |
February | 0.132452E+11 | 0.677772E+10 | 0.118950E+11 | 0.945786E+10 | 0.243717E+10 | 0.00 | 0.00 |
March | 0.111189E+11 | 0.610957E+10 | 0.989250E+10 | 0.653797E+10 | 0.335453E+10 | 0.00 | 0.00 |
April | 0.638766E+10 | 0.545207E+10 | 0.626865E+10 | 0.259334E+10 | 0.367531E+10 | 0.00 | 0.00 |
May | 0.663637E+10 | 0.327087E+10 | 0.588617E+10 | 0.113192E+10 | 0.475425E+10 | 0.00 | 0.00 |
June | 0.748118E+10 | 0.160373E+10 | 0.517892E+10 | 0.934890E+09 | 0.424403E+10 | 0.00 | 0.00 |
July | 0.802708E+10 | 0.148939E+10 | 0.552749E+10 | 0.941651E+09 | 0.458584E+10 | 0.00 | 0.00 |
August | 0.102036E+11 | 0.171911E+10 | 0.703302E+10 | 0.289346E+10 | 0.413956E+10 | 0.00 | 0.00 |
September | 0.120881E+11 | 0.260632E+10 | 0.894045E+10 | 0.502541E+10 | 0.391504E+10 | 0.00 | 0.00 |
October | 0.130453E+11 | 0.585153E+10 | 0.109053E+11 | 0.772675E+10 | 0.317852E+10 | 0.00 | 0.00 |
November | 0.149575E+11 | 0.654070E+10 | 0.129355E+11 | 0.103178E+11 | 0.261779E+10 | 0.00 | 0.00 |
December | 0.140108E+11 | 0.816652E+10 | 0.127563E+11 | 0.103266E+11 | 0.242972E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.132836E+12 | 0.567725E+11 | 0.111137E+12 | 0.693446E+11 | 0.417924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.638766E+10 | 0.148939E+10 | 0.517892E+10 | 0.934890E+09 | 0.242972E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156345E+11 | 0.816652E+10 | 0.139177E+11 | 0.114570E+11 | 0.475425E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124300E+10 | 0.102913E+10 | 0.123908E+10 | 0.927787E+09 | 0.311298E+09 | 0.00 | 0.00 |
February | 0.115704E+10 | 0.982520E+09 | 0.117414E+10 | 0.840713E+09 | 0.333422E+09 | 0.00 | 0.00 |
March | 0.124744E+10 | 0.852156E+09 | 0.122054E+10 | 0.731177E+09 | 0.489367E+09 | 0.00 | 0.00 |
April | 0.920573E+09 | 0.737558E+09 | 0.964852E+09 | 0.405358E+09 | 0.559494E+09 | 0.00 | 0.00 |
May | 0.125081E+10 | 0.433469E+09 | 0.110908E+10 | 0.340516E+09 | 0.768564E+09 | 0.00 | 0.00 |
June | 0.169327E+10 | 0.200549E+09 | 0.121439E+10 | 0.499776E+09 | 0.714612E+09 | 0.00 | 0.00 |
July | 0.153091E+10 | 0.179340E+09 | 0.108465E+10 | 0.337838E+09 | 0.746816E+09 | 0.00 | 0.00 |
August | 0.166867E+10 | 0.211893E+09 | 0.120308E+10 | 0.563068E+09 | 0.640014E+09 | 0.00 | 0.00 |
September | 0.156173E+10 | 0.350422E+09 | 0.119182E+10 | 0.612531E+09 | 0.579290E+09 | 0.00 | 0.00 |
October | 0.134348E+10 | 0.825050E+09 | 0.120259E+10 | 0.768092E+09 | 0.434495E+09 | 0.00 | 0.00 |
November | 0.124527E+10 | 0.929320E+09 | 0.118641E+10 | 0.853604E+09 | 0.332805E+09 | 0.00 | 0.00 |
December | 0.103888E+10 | 0.119310E+10 | 0.109554E+10 | 0.797925E+09 | 0.297618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159011E+11 | 0.792451E+10 | 0.138862E+11 | 0.767839E+10 | 0.620780E+10 | 0.00 | 0.00 |
Minimum of Months | 0.920573E+09 | 0.179340E+09 | 0.964852E+09 | 0.337838E+09 | 0.297618E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169327E+10 | 0.119310E+10 | 0.123908E+10 | 0.927787E+09 | 0.768564E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.455331E+09 | 0.109343E+10 | 0.565044E+09 | 0.308540E+09 | 0.256504E+09 | 0.00 | 0.00 |
February | 0.488643E+09 | 0.102401E+10 | 0.619992E+09 | 0.329518E+09 | 0.290474E+09 | 0.00 | 0.00 |
March | 0.724333E+09 | 0.863830E+09 | 0.819644E+09 | 0.377808E+09 | 0.441835E+09 | 0.00 | 0.00 |
April | 0.671542E+09 | 0.731858E+09 | 0.788786E+09 | 0.266255E+09 | 0.522531E+09 | 0.00 | 0.00 |
May | 0.110228E+10 | 0.418409E+09 | 0.102068E+10 | 0.287041E+09 | 0.733634E+09 | 0.00 | 0.00 |
June | 0.161378E+10 | 0.188933E+09 | 0.117823E+10 | 0.476505E+09 | 0.701723E+09 | 0.00 | 0.00 |
July | 0.142346E+10 | 0.171109E+09 | 0.102480E+10 | 0.303250E+09 | 0.721551E+09 | 0.00 | 0.00 |
August | 0.137231E+10 | 0.205330E+09 | 0.101316E+10 | 0.411825E+09 | 0.601338E+09 | 0.00 | 0.00 |
September | 0.109839E+10 | 0.344379E+09 | 0.862721E+09 | 0.341032E+09 | 0.521689E+09 | 0.00 | 0.00 |
October | 0.719431E+09 | 0.827909E+09 | 0.727106E+09 | 0.350463E+09 | 0.376643E+09 | 0.00 | 0.00 |
November | 0.486695E+09 | 0.956952E+09 | 0.570956E+09 | 0.295932E+09 | 0.275024E+09 | 0.00 | 0.00 |
December | 0.340299E+09 | 0.126830E+10 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104965E+11 | 0.809445E+10 | 0.967035E+10 | 0.398795E+10 | 0.568241E+10 | 0.00 | 0.00 |
Minimum of Months | 0.340299E+09 | 0.171109E+09 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161378E+10 | 0.126830E+10 | 0.117823E+10 | 0.476505E+09 | 0.733634E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.672287E+09 | 0.306951E+09 | 0.601678E+09 | 0.495299E+09 | 0.106379E+09 | 0.00 | 0.00 |
February | 0.567215E+09 | 0.286821E+09 | 0.514238E+09 | 0.408875E+09 | 0.105363E+09 | 0.00 | 0.00 |
March | 0.478919E+09 | 0.249462E+09 | 0.427666E+09 | 0.282644E+09 | 0.145022E+09 | 0.00 | 0.00 |
April | 0.277572E+09 | 0.218628E+09 | 0.271003E+09 | 0.112113E+09 | 0.158890E+09 | 0.00 | 0.00 |
May | 0.288102E+09 | 0.134713E+09 | 0.254468E+09 | 48934276.29 | 0.205534E+09 | 0.00 | 0.00 |
June | 0.329907E+09 | 63322346.27 | 0.223893E+09 | 40416423.07 | 0.183477E+09 | 0.00 | 0.00 |
July | 0.353876E+09 | 58139922.83 | 0.238962E+09 | 40708703.25 | 0.198254E+09 | 0.00 | 0.00 |
August | 0.445463E+09 | 68072182.06 | 0.304048E+09 | 0.125088E+09 | 0.178960E+09 | 0.00 | 0.00 |
September | 0.523687E+09 | 0.107466E+09 | 0.386508E+09 | 0.217254E+09 | 0.169254E+09 | 0.00 | 0.00 |
October | 0.562510E+09 | 0.245110E+09 | 0.471449E+09 | 0.334037E+09 | 0.137413E+09 | 0.00 | 0.00 |
November | 0.644127E+09 | 0.277748E+09 | 0.559220E+09 | 0.446049E+09 | 0.113171E+09 | 0.00 | 0.00 |
December | 0.600412E+09 | 0.347020E+09 | 0.551473E+09 | 0.446432E+09 | 0.105041E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.574408E+10 | 0.236345E+10 | 0.480461E+10 | 0.299785E+10 | 0.180676E+10 | 0.00 | 0.00 |
Minimum of Months | 0.277572E+09 | 58139922.83 | 0.223893E+09 | 40416423.07 | 0.105041E+09 | 0.00 | 0.00 |
Maximum of Months | 0.672287E+09 | 0.347020E+09 | 0.601678E+09 | 0.495299E+09 | 0.205534E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12130992.25 | 0.329635E+09 | 62572574.96 | 0.00 | 62572574.96 | 0.00 | 0.00 |
February | 13389136.51 | 0.307706E+09 | 71035352.99 | 0.00 | 71035352.99 | 0.00 | 0.00 |
March | 49794382.74 | 0.253109E+09 | 0.107045E+09 | 5523.69 | 0.107040E+09 | 0.00 | 0.00 |
April | 73090091.02 | 0.211025E+09 | 0.130222E+09 | 853207.10 | 0.129368E+09 | 0.00 | 0.00 |
May | 0.177985E+09 | 0.111741E+09 | 0.183819E+09 | 6164948.81 | 0.177654E+09 | 0.00 | 0.00 |
June | 0.282445E+09 | 46622236.92 | 0.195035E+09 | 21810480.60 | 0.173225E+09 | 0.00 | 0.00 |
July | 0.281624E+09 | 42674726.75 | 0.191153E+09 | 13048148.50 | 0.178104E+09 | 0.00 | 0.00 |
August | 0.216861E+09 | 51179240.43 | 0.152193E+09 | 4118668.79 | 0.148074E+09 | 0.00 | 0.00 |
September | 0.155744E+09 | 90301563.54 | 0.123321E+09 | 98489.96 | 0.123223E+09 | 0.00 | 0.00 |
October | 55787656.83 | 0.235482E+09 | 91170274.99 | 0.00 | 91170274.99 | 0.00 | 0.00 |
November | 19611518.82 | 0.283560E+09 | 66977226.59 | 0.00 | 66977226.59 | 0.00 | 0.00 |
December | 9793376.42 | 0.383675E+09 | 58544410.09 | 0.00 | 58544410.09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134826E+10 | 0.234671E+10 | 0.143309E+10 | 46099467.45 | 0.138699E+10 | 0.00 | 0.00 |
Minimum of Months | 9793376.42 | 42674726.75 | 58544410.09 | 0.00 | 58544410.09 | 0.00 | 0.00 |
Maximum of Months | 0.282445E+09 | 0.383675E+09 | 0.195035E+09 | 21810480.60 | 0.178104E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118863E+10 | 0.101776E+10 | 0.120801E+10 | 0.898011E+09 | 0.310003E+09 | 0.00 | 0.00 |
February | 0.117749E+10 | 0.978474E+09 | 0.119479E+10 | 0.860466E+09 | 0.334324E+09 | 0.00 | 0.00 |
March | 0.130746E+10 | 0.843631E+09 | 0.127070E+10 | 0.782987E+09 | 0.487711E+09 | 0.00 | 0.00 |
April | 0.103625E+10 | 0.721618E+09 | 0.106592E+10 | 0.494303E+09 | 0.571619E+09 | 0.00 | 0.00 |
May | 0.134182E+10 | 0.407856E+09 | 0.119897E+10 | 0.429924E+09 | 0.769043E+09 | 0.00 | 0.00 |
June | 0.179900E+10 | 0.184480E+09 | 0.131713E+10 | 0.594894E+09 | 0.722240E+09 | 0.00 | 0.00 |
July | 0.176142E+10 | 0.169727E+09 | 0.127160E+10 | 0.513177E+09 | 0.758426E+09 | 0.00 | 0.00 |
August | 0.187041E+10 | 0.205166E+09 | 0.136381E+10 | 0.698346E+09 | 0.665469E+09 | 0.00 | 0.00 |
September | 0.165566E+10 | 0.332375E+09 | 0.127659E+10 | 0.702872E+09 | 0.573721E+09 | 0.00 | 0.00 |
October | 0.130995E+10 | 0.813309E+09 | 0.118267E+10 | 0.742987E+09 | 0.439687E+09 | 0.00 | 0.00 |
November | 0.118613E+10 | 0.922655E+09 | 0.114467E+10 | 0.808738E+09 | 0.335935E+09 | 0.00 | 0.00 |
December | 0.103011E+10 | 0.119419E+10 | 0.108874E+10 | 0.788225E+09 | 0.300514E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166643E+11 | 0.779124E+10 | 0.145836E+11 | 0.831493E+10 | 0.626869E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103011E+10 | 0.169727E+09 | 0.106592E+10 | 0.429924E+09 | 0.300514E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187041E+10 | 0.119419E+10 | 0.136381E+10 | 0.898011E+09 | 0.769043E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.383702E+09 | 0.106117E+10 | 0.533973E+09 | 0.278765E+09 | 0.255208E+09 | 0.00 | 0.00 |
February | 0.499016E+09 | 0.100897E+10 | 0.640647E+09 | 0.349271E+09 | 0.291376E+09 | 0.00 | 0.00 |
March | 0.768640E+09 | 0.841902E+09 | 0.869798E+09 | 0.429618E+09 | 0.440180E+09 | 0.00 | 0.00 |
April | 0.783604E+09 | 0.714847E+09 | 0.889856E+09 | 0.355199E+09 | 0.534656E+09 | 0.00 | 0.00 |
May | 0.119983E+10 | 0.400956E+09 | 0.111056E+10 | 0.376449E+09 | 0.734112E+09 | 0.00 | 0.00 |
June | 0.172867E+10 | 0.182181E+09 | 0.128097E+10 | 0.571623E+09 | 0.709351E+09 | 0.00 | 0.00 |
July | 0.165964E+10 | 0.167726E+09 | 0.121175E+10 | 0.478590E+09 | 0.733161E+09 | 0.00 | 0.00 |
August | 0.157500E+10 | 0.200327E+09 | 0.117389E+10 | 0.547102E+09 | 0.626792E+09 | 0.00 | 0.00 |
September | 0.118782E+10 | 0.324682E+09 | 0.947493E+09 | 0.431373E+09 | 0.516120E+09 | 0.00 | 0.00 |
October | 0.674484E+09 | 0.807363E+09 | 0.707193E+09 | 0.325358E+09 | 0.381835E+09 | 0.00 | 0.00 |
November | 0.418758E+09 | 0.939165E+09 | 0.529219E+09 | 0.251066E+09 | 0.278153E+09 | 0.00 | 0.00 |
December | 0.312372E+09 | 0.124691E+10 | 0.472432E+09 | 0.230075E+09 | 0.242358E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111915E+11 | 0.789621E+10 | 0.103678E+11 | 0.462449E+10 | 0.574330E+10 | 0.00 | 0.00 |
Minimum of Months | 0.312372E+09 | 0.167726E+09 | 0.472432E+09 | 0.230075E+09 | 0.242358E+09 | 0.00 | 0.00 |
Maximum of Months | 0.172867E+10 | 0.124691E+10 | 0.128097E+10 | 0.571623E+09 | 0.734112E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140864E+10 | 0.129597E+10 | 0.143922E+10 | 0.107318E+10 | 0.366046E+09 | 0.00 | 0.00 |
February | 0.120643E+10 | 0.124988E+10 | 0.126810E+10 | 0.885918E+09 | 0.382179E+09 | 0.00 | 0.00 |
March | 0.113064E+10 | 0.111568E+10 | 0.115853E+10 | 0.612423E+09 | 0.546106E+09 | 0.00 | 0.00 |
April | 0.758521E+09 | 0.962806E+09 | 0.869292E+09 | 0.244767E+09 | 0.624525E+09 | 0.00 | 0.00 |
May | 0.999453E+09 | 0.553616E+09 | 0.949576E+09 | 0.119382E+09 | 0.830194E+09 | 0.00 | 0.00 |
June | 0.127972E+10 | 0.266270E+09 | 0.907626E+09 | 0.134820E+09 | 0.772806E+09 | 0.00 | 0.00 |
July | 0.133012E+10 | 0.254139E+09 | 0.931865E+09 | 0.116471E+09 | 0.815394E+09 | 0.00 | 0.00 |
August | 0.139551E+10 | 0.303603E+09 | 0.988489E+09 | 0.279953E+09 | 0.708536E+09 | 0.00 | 0.00 |
September | 0.144392E+10 | 0.478694E+09 | 0.110461E+10 | 0.470943E+09 | 0.633667E+09 | 0.00 | 0.00 |
October | 0.131946E+10 | 0.108001E+10 | 0.121900E+10 | 0.723764E+09 | 0.495240E+09 | 0.00 | 0.00 |
November | 0.139842E+10 | 0.118334E+10 | 0.135677E+10 | 0.966464E+09 | 0.390305E+09 | 0.00 | 0.00 |
December | 0.124167E+10 | 0.151066E+10 | 0.132171E+10 | 0.967294E+09 | 0.354421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.149125E+11 | 0.102547E+11 | 0.135148E+11 | 0.659538E+10 | 0.691942E+10 | 0.00 | 0.00 |
Minimum of Months | 0.758521E+09 | 0.254139E+09 | 0.869292E+09 | 0.116471E+09 | 0.354421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144392E+10 | 0.151066E+10 | 0.143922E+10 | 0.107318E+10 | 0.830194E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123993E+10 | 0.102399E+10 | 0.123908E+10 | 0.927787E+09 | 0.311298E+09 | 0.00 | 0.00 |
February | 0.115000E+10 | 0.982771E+09 | 0.117414E+10 | 0.840713E+09 | 0.333422E+09 | 0.00 | 0.00 |
March | 0.123797E+10 | 0.851248E+09 | 0.122054E+10 | 0.731177E+09 | 0.489367E+09 | 0.00 | 0.00 |
April | 0.911488E+09 | 0.736940E+09 | 0.964852E+09 | 0.405358E+09 | 0.559494E+09 | 0.00 | 0.00 |
May | 0.123843E+10 | 0.434679E+09 | 0.110908E+10 | 0.340516E+09 | 0.768564E+09 | 0.00 | 0.00 |
June | 0.168360E+10 | 0.198474E+09 | 0.121439E+10 | 0.499776E+09 | 0.714612E+09 | 0.00 | 0.00 |
July | 0.152320E+10 | 0.176814E+09 | 0.108465E+10 | 0.337838E+09 | 0.746816E+09 | 0.00 | 0.00 |
August | 0.165896E+10 | 0.209501E+09 | 0.120308E+10 | 0.563068E+09 | 0.640014E+09 | 0.00 | 0.00 |
September | 0.155391E+10 | 0.348047E+09 | 0.119182E+10 | 0.612531E+09 | 0.579290E+09 | 0.00 | 0.00 |
October | 0.133653E+10 | 0.822350E+09 | 0.120259E+10 | 0.768092E+09 | 0.434495E+09 | 0.00 | 0.00 |
November | 0.123960E+10 | 0.926090E+09 | 0.118641E+10 | 0.853604E+09 | 0.332805E+09 | 0.00 | 0.00 |
December | 0.103443E+10 | 0.119270E+10 | 0.109554E+10 | 0.797925E+09 | 0.297618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158080E+11 | 0.790360E+10 | 0.138862E+11 | 0.767839E+10 | 0.620780E+10 | 0.00 | 0.00 |
Minimum of Months | 0.911488E+09 | 0.176814E+09 | 0.964852E+09 | 0.337838E+09 | 0.297618E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168360E+10 | 0.119270E+10 | 0.123908E+10 | 0.927787E+09 | 0.768564E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456746E+09 | 0.108467E+10 | 0.565044E+09 | 0.308540E+09 | 0.256504E+09 | 0.00 | 0.00 |
February | 0.487104E+09 | 0.102181E+10 | 0.619992E+09 | 0.329518E+09 | 0.290474E+09 | 0.00 | 0.00 |
March | 0.719525E+09 | 0.861371E+09 | 0.819644E+09 | 0.377808E+09 | 0.441835E+09 | 0.00 | 0.00 |
April | 0.664973E+09 | 0.730503E+09 | 0.788786E+09 | 0.266255E+09 | 0.522531E+09 | 0.00 | 0.00 |
May | 0.109116E+10 | 0.419000E+09 | 0.102068E+10 | 0.287041E+09 | 0.733634E+09 | 0.00 | 0.00 |
June | 0.160512E+10 | 0.187408E+09 | 0.117823E+10 | 0.476505E+09 | 0.701723E+09 | 0.00 | 0.00 |
July | 0.141682E+10 | 0.168955E+09 | 0.102480E+10 | 0.303250E+09 | 0.721551E+09 | 0.00 | 0.00 |
August | 0.136495E+10 | 0.202816E+09 | 0.101316E+10 | 0.411825E+09 | 0.601338E+09 | 0.00 | 0.00 |
September | 0.109449E+10 | 0.340369E+09 | 0.862721E+09 | 0.341032E+09 | 0.521689E+09 | 0.00 | 0.00 |
October | 0.717346E+09 | 0.822195E+09 | 0.727106E+09 | 0.350463E+09 | 0.376643E+09 | 0.00 | 0.00 |
November | 0.486340E+09 | 0.950583E+09 | 0.570956E+09 | 0.295932E+09 | 0.275024E+09 | 0.00 | 0.00 |
December | 0.340960E+09 | 0.126534E+10 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104455E+11 | 0.805503E+10 | 0.967035E+10 | 0.398795E+10 | 0.568241E+10 | 0.00 | 0.00 |
Minimum of Months | 0.340960E+09 | 0.168955E+09 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160512E+10 | 0.126534E+10 | 0.117823E+10 | 0.476505E+09 | 0.733634E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122698E+10 | 0.534045E+09 | 0.110324E+10 | 0.908185E+09 | 0.195057E+09 | 0.00 | 0.00 |
February | 0.103165E+10 | 0.514236E+09 | 0.942911E+09 | 0.749717E+09 | 0.193195E+09 | 0.00 | 0.00 |
March | 0.868437E+09 | 0.448897E+09 | 0.784173E+09 | 0.518259E+09 | 0.265914E+09 | 0.00 | 0.00 |
April | 0.501027E+09 | 0.392032E+09 | 0.496914E+09 | 0.205572E+09 | 0.291342E+09 | 0.00 | 0.00 |
May | 0.531067E+09 | 0.225380E+09 | 0.466596E+09 | 89726356.12 | 0.376869E+09 | 0.00 | 0.00 |
June | 0.611515E+09 | 95925880.40 | 0.410533E+09 | 74107939.14 | 0.336425E+09 | 0.00 | 0.00 |
July | 0.654387E+09 | 86572305.60 | 0.438164E+09 | 74643866.89 | 0.363520E+09 | 0.00 | 0.00 |
August | 0.818365E+09 | 0.104568E+09 | 0.557506E+09 | 0.229362E+09 | 0.328143E+09 | 0.00 | 0.00 |
September | 0.957601E+09 | 0.177782E+09 | 0.708705E+09 | 0.398360E+09 | 0.310345E+09 | 0.00 | 0.00 |
October | 0.102519E+10 | 0.428117E+09 | 0.864454E+09 | 0.612493E+09 | 0.251961E+09 | 0.00 | 0.00 |
November | 0.117254E+10 | 0.485731E+09 | 0.102539E+10 | 0.817880E+09 | 0.207512E+09 | 0.00 | 0.00 |
December | 0.108884E+10 | 0.625106E+09 | 0.101119E+10 | 0.818582E+09 | 0.192604E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104876E+11 | 0.411839E+10 | 0.880977E+10 | 0.549689E+10 | 0.331288E+10 | 0.00 | 0.00 |
Minimum of Months | 0.501027E+09 | 86572305.60 | 0.410533E+09 | 74107939.14 | 0.192604E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122698E+10 | 0.625106E+09 | 0.110324E+10 | 0.908185E+09 | 0.376869E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 55356045.57 | 0.335623E+10 | 0.547417E+09 | 0.00 | 0.547417E+09 | 0.00 | 0.00 |
February | 61777369.29 | 0.314205E+10 | 0.621453E+09 | 0.00 | 0.621453E+09 | 0.00 | 0.00 |
March | 0.305952E+09 | 0.263648E+10 | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.00 | 0.00 |
April | 0.489327E+09 | 0.222599E+10 | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.00 | 0.00 |
May | 0.132893E+10 | 0.119688E+10 | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.00 | 0.00 |
June | 0.226069E+10 | 0.552301E+09 | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.00 | 0.00 |
July | 0.225905E+10 | 0.529699E+09 | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.00 | 0.00 |
August | 0.169894E+10 | 0.626717E+09 | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.00 | 0.00 |
September | 0.119134E+10 | 0.101096E+10 | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.00 | 0.00 |
October | 0.360346E+09 | 0.245150E+10 | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.00 | 0.00 |
November | 0.105638E+09 | 0.292982E+10 | 0.585951E+09 | 0.00 | 0.585951E+09 | 0.00 | 0.00 |
December | 45976339.81 | 0.386778E+10 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101633E+11 | 0.245264E+11 | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.00 | 0.00 |
Minimum of Months | 45976339.81 | 0.529699E+09 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Maximum of Months | 0.226069E+10 | 0.386778E+10 | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 48242197.41 | 0.342695E+10 | 0.547417E+09 | 0.00 | 0.547417E+09 | 0.00 | 0.00 |
February | 56667788.71 | 0.321041E+10 | 0.621453E+09 | 0.00 | 0.621453E+09 | 0.00 | 0.00 |
March | 0.290230E+09 | 0.269416E+10 | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.00 | 0.00 |
April | 0.469629E+09 | 0.227577E+10 | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.00 | 0.00 |
May | 0.130350E+10 | 0.122055E+10 | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.00 | 0.00 |
June | 0.223976E+10 | 0.565710E+09 | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.00 | 0.00 |
July | 0.223812E+10 | 0.544067E+09 | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.00 | 0.00 |
August | 0.167991E+10 | 0.643224E+09 | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.00 | 0.00 |
September | 0.117472E+10 | 0.103226E+10 | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.00 | 0.00 |
October | 0.346042E+09 | 0.249882E+10 | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.00 | 0.00 |
November | 98629646.65 | 0.299315E+10 | 0.585951E+09 | 0.00 | 0.585951E+09 | 0.00 | 0.00 |
December | 41060624.79 | 0.395219E+10 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.998652E+10 | 0.250573E+11 | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.00 | 0.00 |
Minimum of Months | 41060624.79 | 0.544067E+09 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223976E+10 | 0.395219E+10 | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.156150E+10 | 0.220334E+10 | 0.174192E+10 | 0.117674E+10 | 0.565186E+09 | 0.00 | 0.00 |
February | 0.167017E+10 | 0.215345E+10 | 0.183536E+10 | 0.120969E+10 | 0.625671E+09 | 0.00 | 0.00 |
March | 0.213183E+10 | 0.189979E+10 | 0.214039E+10 | 0.121254E+10 | 0.927847E+09 | 0.00 | 0.00 |
April | 0.187264E+10 | 0.167103E+10 | 0.195567E+10 | 0.849452E+09 | 0.110622E+10 | 0.00 | 0.00 |
May | 0.272502E+10 | 0.955499E+09 | 0.230940E+10 | 0.806321E+09 | 0.150308E+10 | 0.00 | 0.00 |
June | 0.382087E+10 | 0.469752E+09 | 0.259796E+10 | 0.116644E+10 | 0.143152E+10 | 0.00 | 0.00 |
July | 0.372059E+10 | 0.451402E+09 | 0.248322E+10 | 0.991701E+09 | 0.149151E+10 | 0.00 | 0.00 |
August | 0.374386E+10 | 0.508047E+09 | 0.253757E+10 | 0.124537E+10 | 0.129220E+10 | 0.00 | 0.00 |
September | 0.307734E+10 | 0.755405E+09 | 0.222397E+10 | 0.113418E+10 | 0.108979E+10 | 0.00 | 0.00 |
October | 0.208054E+10 | 0.179205E+10 | 0.188978E+10 | 0.106830E+10 | 0.821483E+09 | 0.00 | 0.00 |
November | 0.162519E+10 | 0.201902E+10 | 0.167383E+10 | 0.105977E+10 | 0.614060E+09 | 0.00 | 0.00 |
December | 0.129949E+10 | 0.263838E+10 | 0.156111E+10 | 0.101827E+10 | 0.542847E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293290E+11 | 0.175172E+11 | 0.249502E+11 | 0.129388E+11 | 0.120114E+11 | 0.00 | 0.00 |
Minimum of Months | 0.129949E+10 | 0.451402E+09 | 0.156111E+10 | 0.806321E+09 | 0.542847E+09 | 0.00 | 0.00 |
Maximum of Months | 0.382087E+10 | 0.263838E+10 | 0.259796E+10 | 0.124537E+10 | 0.150308E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.304556E+10 | 0.229260E+10 | 0.299602E+10 | 0.231183E+10 | 0.684183E+09 | 0.00 | 0.00 |
February | 0.258298E+10 | 0.222605E+10 | 0.261327E+10 | 0.190844E+10 | 0.704822E+09 | 0.00 | 0.00 |
March | 0.232345E+10 | 0.198697E+10 | 0.231718E+10 | 0.131927E+10 | 0.997910E+09 | 0.00 | 0.00 |
April | 0.147136E+10 | 0.173823E+10 | 0.165546E+10 | 0.525853E+09 | 0.112960E+10 | 0.00 | 0.00 |
May | 0.181422E+10 | 0.100717E+10 | 0.173902E+10 | 0.246892E+09 | 0.149213E+10 | 0.00 | 0.00 |
June | 0.226505E+10 | 0.487008E+09 | 0.162994E+10 | 0.254055E+09 | 0.137589E+10 | 0.00 | 0.00 |
July | 0.238036E+10 | 0.462771E+09 | 0.168864E+10 | 0.229141E+09 | 0.145949E+10 | 0.00 | 0.00 |
August | 0.262765E+10 | 0.547630E+09 | 0.187559E+10 | 0.596206E+09 | 0.127938E+10 | 0.00 | 0.00 |
September | 0.283822E+10 | 0.841820E+09 | 0.217389E+10 | 0.101434E+10 | 0.115955E+10 | 0.00 | 0.00 |
October | 0.273701E+10 | 0.190528E+10 | 0.247393E+10 | 0.155913E+10 | 0.914801E+09 | 0.00 | 0.00 |
November | 0.297753E+10 | 0.210439E+10 | 0.281105E+10 | 0.208196E+10 | 0.729097E+09 | 0.00 | 0.00 |
December | 0.268471E+10 | 0.269381E+10 | 0.274960E+10 | 0.208374E+10 | 0.665858E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.297481E+11 | 0.182937E+11 | 0.267236E+11 | 0.141309E+11 | 0.125927E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147136E+10 | 0.462771E+09 | 0.162994E+10 | 0.229141E+09 | 0.665858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.304556E+10 | 0.269381E+10 | 0.299602E+10 | 0.231183E+10 | 0.149213E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770380E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161023031.7 | 81.21 | 0.00 | 0.00 |
February | 0.696149E+10 | -0.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145540293.8 | 81.21 | 0.00 | 0.00 |
March | 0.770250E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161040101.6 | 81.21 | 0.00 | 0.00 |
April | 0.746436E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155760931.2 | 81.21 | 0.00 | 0.00 |
May | 0.770409E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161294867.2 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156202688.5 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412622.9 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411073.4 | 81.21 | 0.00 | 0.00 |
September | 0.746613E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156198421.2 | 81.21 | 0.00 | 0.00 |
October | 0.770261E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161171515.4 | 81.21 | 0.00 | 0.00 |
November | 0.744826E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155833019.0 | 81.21 | 0.00 | 0.00 |
December | 0.771215E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161309670.0 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907386E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189820E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696149E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161412622.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771226E+10 | -0.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145540293.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.125053E+12 | -0.123322E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173071E+10 | 81.29 | 0.00 | 0.00 |
February | 0.113995E+12 | -0.112427E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156747E+10 | 81.30 | 0.00 | 0.00 |
March | 0.124835E+12 | -0.123095E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174020E+10 | 81.29 | 0.00 | 0.00 |
April | 0.117442E+12 | -0.115760E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168181E+10 | 81.27 | 0.00 | 0.00 |
May | 0.116734E+12 | -0.114994E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174023E+10 | 81.26 | 0.00 | 0.00 |
June | 0.108538E+12 | -0.106859E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167913E+10 | 81.25 | 0.00 | 0.00 |
July | 0.108851E+12 | -0.107118E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173315E+10 | 81.25 | 0.00 | 0.00 |
August | 0.107687E+12 | -0.105959E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172881E+10 | 81.25 | 0.00 | 0.00 |
September | 0.105497E+12 | -0.103827E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167054E+10 | 81.25 | 0.00 | 0.00 |
October | 0.112452E+12 | -0.110726E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172591E+10 | 81.25 | 0.00 | 0.00 |
November | 0.113291E+12 | -0.111621E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167032E+10 | 81.26 | 0.00 | 0.00 |
December | 0.121646E+12 | -0.119919E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172668E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.137602E+13 | -0.135563E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203950E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.105497E+12 | -0.123322E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.174023E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.125053E+12 | -0.103827E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156747E+10 | 81.30 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.752022E+11 | -0.737349E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146732E+10 | 58.99 | 0.00 | 0.00 |
February | 0.687703E+11 | -0.674396E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.133063E+10 | 58.99 | 0.00 | 0.00 |
March | 0.750964E+11 | -0.736160E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148044E+10 | 58.99 | 0.00 | 0.00 |
April | 0.698184E+11 | -0.683879E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143049E+10 | 58.99 | 0.00 | 0.00 |
May | 0.682036E+11 | -0.667218E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148179E+10 | 58.98 | 0.00 | 0.00 |
June | 0.622138E+11 | -0.607865E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142726E+10 | 58.98 | 0.00 | 0.00 |
July | 0.613803E+11 | -0.599083E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147199E+10 | 58.98 | 0.00 | 0.00 |
August | 0.604363E+11 | -0.589703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146603E+10 | 58.98 | 0.00 | 0.00 |
September | 0.595612E+11 | -0.581458E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141538E+10 | 58.98 | 0.00 | 0.00 |
October | 0.644783E+11 | -0.630162E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146208E+10 | 58.98 | 0.00 | 0.00 |
November | 0.662376E+11 | -0.648227E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141490E+10 | 58.98 | 0.00 | 0.00 |
December | 0.723547E+11 | -0.708920E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146269E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.803753E+12 | -0.786442E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.173110E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.595612E+11 | -0.737349E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.148179E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.752022E+11 | -0.581458E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.133063E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.87 | 0.86 | 01-JAN-07:49 | 9907.10 | 39.96 | 274.17 | 271.67 | 3773.68 | 33.98 | 235.67 | 260.67 |
February | 245.50 | 0.86 | 0.86 | 01-FEB-10:39 | 13503.17 | 39.34 | 238.17 | 267.33 | 1144.85 | 26.26 | 194.50 | 234.83 |
March | 296.17 | 0.87 | 0.86 | 01-MAR-06:00 | 4817.37 | 25.98 | 142.33 | 334.00 | 695.04 | 22.65 | 243.50 | 282.67 |
April | 296.67 | 0.87 | 0.86 | 03-APR-09:39 | 1535.21 | 20.68 | 108.50 | 346.00 | 616.68 | 22.39 | 226.50 | 287.00 |
May | 415.33 | 0.87 | 0.86 | 01-MAY-06:30 | 1449.82 | 20.32 | 164.33 | 397.83 | 568.14 | 22.03 | 303.17 | 343.50 |
June | 421.50 | 0.87 | 0.86 | 01-JUN-06:10 | 1117.20 | 20.38 | 100.00 | 398.83 | 470.03 | 22.14 | 322.00 | 333.17 |
July | 430.33 | 0.87 | 0.86 | 01-JUL-08:09 | 1297.97 | 20.21 | 145.67 | 404.33 | 518.81 | 21.94 | 305.50 | 340.67 |
August | 394.50 | 0.87 | 0.86 | 01-AUG-06:19 | 1295.70 | 20.45 | 117.83 | 376.33 | 540.98 | 22.18 | 301.67 | 324.17 |
September | 354.00 | 0.87 | 0.86 | 01-SEP-07:10 | 1605.68 | 20.70 | 121.17 | 337.67 | 660.00 | 22.47 | 284.00 | 296.17 |
October | 262.67 | 0.87 | 0.86 | 01-OCT-06:49 | 10584.59 | 35.30 | 227.17 | 303.50 | 884.09 | 24.29 | 240.00 | 261.50 |
November | 257.67 | 0.87 | 0.86 | 01-NOV-08:39 | 11438.29 | 39.84 | 254.00 | 268.50 | 2084.27 | 30.45 | 224.00 | 240.83 |
December | 251.17 | 0.86 | 0.86 | 01-DEC-07:40 | 9182.45 | 40.37 | 250.83 | 261.00 | 5621.87 | 38.48 | 240.33 | 245.83 |
Annual Sum or Average | 3902.00 | 0.87 | 4787.68 | 26.99 | 2144.17 | 3967.00 | 1281.13 | 25.04 | 3120.83 | 3451.00 | ||
Minimum of Months | 245.50 | 0.86 | 0.86 | 1117.20 | 20.21 | 100.00 | 261.00 | 470.03 | 21.94 | 194.50 | 234.83 | |
Maximum of Months | 430.33 | 0.87 | 0.86 | 13503.17 | 40.37 | 274.17 | 404.33 | 5621.87 | 38.48 | 322.00 | 343.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.25 | 0.22 | 01-JAN-07:40 | 10595.85 | 40.01 | 274.17 | 277.17 | 4461.76 | 33.56 | 225.83 | 269.33 |
February | 245.50 | 0.24 | 0.22 | 01-FEB-10:39 | 14192.37 | 39.42 | 238.17 | 274.17 | 1832.65 | 25.48 | 133.67 | 258.67 |
March | 296.17 | 0.25 | 0.22 | 01-MAR-06:00 | 5314.88 | 25.95 | 145.83 | 341.33 | 1191.01 | 22.36 | 191.83 | 314.83 |
April | 296.67 | 0.26 | 0.22 | 03-APR-09:39 | 1864.93 | 20.97 | 128.50 | 356.83 | 945.43 | 22.52 | 227.83 | 327.17 |
May | 415.33 | 0.27 | 0.22 | 01-MAY-05:00 | 1693.77 | 20.86 | 210.50 | 408.50 | 811.22 | 22.39 | 329.50 | 381.00 |
June | 421.50 | 0.26 | 0.22 | 01-JUN-05:40 | 1337.57 | 20.92 | 170.50 | 414.00 | 689.77 | 22.49 | 338.83 | 380.50 |
July | 430.33 | 0.27 | 0.22 | 01-JUL-05:00 | 1524.57 | 20.78 | 198.17 | 420.33 | 744.65 | 22.33 | 333.83 | 383.67 |
August | 394.50 | 0.27 | 0.22 | 01-AUG-05:00 | 1594.97 | 20.77 | 141.67 | 385.50 | 839.49 | 22.34 | 304.00 | 360.50 |
September | 354.00 | 0.26 | 0.22 | 01-SEP-06:19 | 2006.64 | 20.76 | 133.00 | 348.33 | 1059.93 | 22.41 | 260.67 | 324.17 |
October | 262.67 | 0.24 | 0.22 | 01-OCT-06:40 | 11192.33 | 35.25 | 220.50 | 313.17 | 1489.96 | 23.82 | 191.17 | 290.67 |
November | 257.67 | 0.24 | 0.22 | 01-NOV-08:39 | 12147.13 | 39.90 | 254.00 | 276.17 | 2790.30 | 29.79 | 178.17 | 260.67 |
December | 251.17 | 0.24 | 0.22 | 01-DEC-07:40 | 9878.33 | 40.41 | 250.83 | 264.50 | 6315.88 | 38.33 | 232.67 | 258.00 |
Annual Sum or Average | 3902.00 | 0.26 | 5216.58 | 27.24 | 2365.83 | 4080.00 | 1708.86 | 24.99 | 2948.00 | 3809.17 | ||
Minimum of Months | 245.50 | 0.24 | 0.22 | 1337.57 | 20.76 | 128.50 | 264.50 | 689.77 | 22.33 | 133.67 | 258.00 | |
Maximum of Months | 430.33 | 0.27 | 0.22 | 14192.37 | 40.41 | 274.17 | 420.33 | 6315.88 | 38.33 | 338.83 | 383.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.69 | 0.60 | 01-JAN-10:09 | 367.55 | 14.51 | 0.00 | 231.00 | 193.82 | 18.19 | 0.00 | 98.83 |
February | 245.50 | 0.65 | 0.60 | 01-FEB-10:39 | 415.64 | 15.83 | 0.00 | 254.33 | 225.09 | 19.43 | 3.83 | 129.33 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 573.63 | 17.07 | 0.00 | 329.83 | 286.86 | 20.41 | 36.33 | 271.50 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 811.80 | 18.20 | 0.00 | 357.17 | 369.71 | 21.37 | 132.00 | 309.33 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-05:00 | 1035.33 | 18.52 | 0.00 | 416.00 | 437.65 | 22.16 | 278.67 | 388.00 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1099.36 | 19.21 | 11.00 | 423.83 | 470.93 | 24.43 | 314.83 | 410.33 |
July | 430.33 | 0.62 | 0.60 | 01-JUL-04:00 | 1069.38 | 18.66 | 1.83 | 429.00 | 451.16 | 23.03 | 300.00 | 402.67 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 804.41 | 18.19 | 0.00 | 390.33 | 364.76 | 21.43 | 181.67 | 354.33 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:30 | 643.17 | 17.47 | 0.00 | 342.83 | 313.22 | 20.74 | 86.83 | 290.83 |
October | 262.67 | 0.64 | 0.60 | 01-OCT-06:00 | 522.05 | 16.85 | 0.00 | 294.50 | 278.27 | 20.30 | 10.17 | 222.50 |
November | 257.67 | 0.67 | 0.60 | 01-NOV-08:50 | 405.28 | 15.30 | 0.00 | 246.50 | 220.52 | 18.94 | 0.67 | 135.00 |
December | 251.17 | 0.68 | 0.60 | 01-DEC-08:50 | 385.21 | 14.92 | 0.00 | 232.83 | 205.45 | 18.60 | 0.00 | 110.67 |
Annual Sum or Average | 3902.00 | 0.64 | 730.73 | 17.34 | 12.83 | 3948.17 | 336.80 | 21.09 | 1345.00 | 3123.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 367.55 | 14.51 | 0.00 | 231.00 | 193.82 | 18.19 | 0.00 | 98.83 | |
Maximum of Months | 430.33 | 0.69 | 0.60 | 1099.36 | 19.21 | 11.00 | 429.00 | 470.93 | 24.43 | 314.83 | 410.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.69 | 0.60 | 01-JAN-10:09 | 367.55 | 14.51 | 0.00 | 231.00 | 193.82 | 18.19 | 0.00 | 98.83 |
February | 245.50 | 0.65 | 0.60 | 01-FEB-10:39 | 415.64 | 15.83 | 0.00 | 254.33 | 225.09 | 19.43 | 3.83 | 129.33 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 573.63 | 17.07 | 0.00 | 329.83 | 286.86 | 20.41 | 36.33 | 271.50 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 811.80 | 18.20 | 0.00 | 357.17 | 369.71 | 21.37 | 132.00 | 309.33 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-05:00 | 1035.33 | 18.52 | 0.00 | 416.00 | 437.65 | 22.16 | 278.67 | 388.00 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1099.36 | 19.21 | 11.00 | 423.83 | 470.93 | 24.43 | 314.83 | 410.33 |
July | 430.33 | 0.62 | 0.60 | 01-JUL-04:00 | 1069.38 | 18.66 | 1.83 | 429.00 | 451.16 | 23.03 | 300.00 | 402.67 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 804.41 | 18.19 | 0.00 | 390.33 | 364.76 | 21.43 | 181.67 | 354.33 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:30 | 643.17 | 17.47 | 0.00 | 342.83 | 313.22 | 20.74 | 86.83 | 290.83 |
October | 262.67 | 0.64 | 0.60 | 01-OCT-06:00 | 522.05 | 16.85 | 0.00 | 294.50 | 278.27 | 20.30 | 10.17 | 222.50 |
November | 257.67 | 0.67 | 0.60 | 01-NOV-08:50 | 405.28 | 15.30 | 0.00 | 246.50 | 220.52 | 18.94 | 0.67 | 135.00 |
December | 251.17 | 0.68 | 0.60 | 01-DEC-08:50 | 385.21 | 14.92 | 0.00 | 232.83 | 205.45 | 18.60 | 0.00 | 110.67 |
Annual Sum or Average | 3902.00 | 0.64 | 730.73 | 17.34 | 12.83 | 3948.17 | 336.80 | 21.09 | 1345.00 | 3123.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 367.55 | 14.51 | 0.00 | 231.00 | 193.82 | 18.19 | 0.00 | 98.83 | |
Maximum of Months | 430.33 | 0.69 | 0.60 | 1099.36 | 19.21 | 11.00 | 429.00 | 470.93 | 24.43 | 314.83 | 410.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486396E+11 | 164348.42 | 13-JAN-16:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426069E+11 | 168894.84 | 15-FEB-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342040E+11 | 163635.08 | 09-MAR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360863E+11 | 164674.85 | 09-APR-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140362E+11 | 159331.82 | 02-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.423366E+09 | 120966.99 | 09-JUN-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.331551E+09 | 48901.57 | 02-JUL-04:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.257156E+09 | 25125.61 | 23-AUG-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368298E+10 | 153918.72 | 21-SEP-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325327E+11 | 173163.56 | 21-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384663E+11 | 171185.00 | 13-NOV-23:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697756E+11 | 169635.75 | 05-DEC-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.257156E+09 | 25125.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.697756E+11 | 173163.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.853256E+09 | 2555.32 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118882E+10 | 2391.12 | 07-FEB-10:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107645E+10 | 2523.31 | 19-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101170E+10 | 3027.39 | 14-APR-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106307E+09 | 2204.74 | 01-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31249641.99 | 1588.14 | 24-SEP-05:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.775367E+09 | 3011.62 | 27-OCT-11:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803806E+09 | 2202.04 | 29-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155872E+10 | 3011.03 | 20-DEC-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.740569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155872E+10 | 3027.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2984296.84 | 211.94 | 05-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17783654.24 | 607.65 | 07-FEB-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4245153.80 | 255.44 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 584137.84 | 109.95 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8662711.84 | 335.80 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 534779.42 | 142.12 | 01-NOV-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41996960.38 | 594.00 | 21-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76791694.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41996960.38 | 607.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181654E+09 | 947.90 | 06-JAN-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376762E+09 | 990.78 | 07-FEB-10:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93580185.23 | 775.65 | 20-MAR-11:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69934455.73 | 769.96 | 17-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83933116.01 | 788.66 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141750E+09 | 964.57 | 30-NOV-11:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568424E+09 | 1399.47 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.568424E+09 | 1399.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297788E+09 | 846.68 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466096E+09 | 785.91 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218930E+09 | 659.93 | 20-MAR-11:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146759E+09 | 620.23 | 03-APR-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138418E+09 | 717.20 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213357E+09 | 702.90 | 30-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.639161E+09 | 1127.65 | 21-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.639161E+09 | 1127.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17900864.57 | 7008.17 | 20-JAN-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18524046.25 | 7430.11 | 18-FEB-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18722088.20 | 7436.43 | 10-MAR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27091469.44 | 7468.77 | 14-APR-03:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39557755.63 | 7519.91 | 13-MAY-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1464839.14 | 3462.24 | 10-JUN-03:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14864876.81 | 7446.82 | 23-SEP-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44573844.28 | 7561.22 | 26-OCT-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45755552.30 | 7473.43 | 07-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15099531.64 | 7537.50 | 02-DEC-02:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45755552.30 | 7561.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226827E+09 | 5745.96 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.561640E+09 | 6726.86 | 07-FEB-14:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.484509E+09 | 5705.10 | 21-MAR-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372578E+09 | 4210.44 | 03-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 106393.26 | 886.61 | 02-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540347E+09 | 8523.12 | 27-OCT-11:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227900E+09 | 4583.11 | 29-NOV-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.692451E+09 | 7683.48 | 21-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.692451E+09 | 8523.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3019485.15 | 2122.61 | 05-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170762E+09 | 5872.38 | 07-FEB-11:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21496141.96 | 2815.19 | 19-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85584485.64 | 4920.81 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205464E+09 | 8697.24 | 21-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205464E+09 | 8697.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122627E+10 | 10915.75 | 08-JAN-18:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288143E+10 | 8887.06 | 07-FEB-14:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119958E+10 | 7592.93 | 21-MAR-10:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874459E+09 | 6013.58 | 04-APR-09:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107459E+10 | 7834.79 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125688E+10 | 6791.66 | 01-NOV-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396220E+10 | 10756.59 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396220E+10 | 10915.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167784E+10 | 4998.34 | 08-JAN-18:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224333E+10 | 4740.12 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134044E+10 | 3680.78 | 19-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.915039E+09 | 3251.58 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19014408.46 | 4021.07 | 01-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992051E+09 | 4425.52 | 27-OCT-11:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131572E+10 | 4284.41 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338632E+10 | 6276.90 | 21-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338632E+10 | 6276.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 212603.15 | 708.68 | 18-FEB-04:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 161711.21 | 205.78 | 11-MAR-02:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 583977.17 | 1488.83 | 12-MAY-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1202022.00 | 1443.46 | 06-NOV-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 683722.66 | 2111.65 | 02-DEC-02:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2844036.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1202022.00 | 2111.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.310600E+10 | 13912.57 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381810E+10 | 12450.52 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166399E+10 | 10748.40 | 19-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102635E+10 | 5427.32 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 431997.36 | 328.61 | 03-MAY-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88650.10 | 0.60 | 03-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 97989.27 | 0.61 | 29-JUL-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71689.02 | 0.60 | 03-AUG-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357813.50 | 214.87 | 22-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148342E+10 | 7927.26 | 30-OCT-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185459E+10 | 9719.51 | 29-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675228E+10 | 15263.33 | 21-DEC-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 71689.02 | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.675228E+10 | 15263.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.256781E+10 | 7463.96 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293365E+10 | 7462.80 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226300E+10 | 7464.76 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184986E+10 | 7463.38 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189376E+09 | 7285.50 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7539483.22 | 6676.79 | 14-JUN-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5609200.40 | 6494.02 | 13-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7709521.15 | 6321.65 | 18-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68794140.34 | 7266.36 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157677E+10 | 7463.68 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217723E+10 | 7463.71 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422142E+10 | 7462.22 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5609200.40 | 6321.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.422142E+10 | 7464.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.404600E+10 | 7435.02 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.404502E+10 | 7434.14 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274183E+10 | 7435.66 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205229E+10 | 7434.27 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210583E+09 | 7266.81 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6931730.06 | 6263.04 | 12-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5465045.73 | 6386.47 | 07-JUL-08:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8346705.42 | 6232.75 | 17-AUG-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92121330.25 | 7266.33 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192366E+10 | 7434.56 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323947E+10 | 7435.16 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.573848E+10 | 7433.98 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5465045.73 | 6232.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.573848E+10 | 7435.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.586379E+09 | 16397.95 | 06-JAN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360529E+10 | 21184.20 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226541E+10 | 11864.54 | 22-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732601E+09 | 12377.35 | 17-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154532E+10 | 17023.75 | 31-OCT-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106606E+10 | 19107.89 | 01-NOV-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.416775E+10 | 30439.86 | 21-DEC-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.416775E+10 | 30439.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171322E+11 | 41924.05 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178004E+11 | 41926.83 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.892831E+10 | 41757.56 | 04-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.488594E+10 | 41436.66 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268106E+09 | 36641.04 | 27-MAY-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36454092.23 | 32759.90 | 16-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30236646.37 | 38331.31 | 07-JUL-08:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 56822857.80 | 34861.34 | 10-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159146E+09 | 39660.04 | 08-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.548784E+10 | 41923.61 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123068E+11 | 41926.67 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241299E+11 | 41920.94 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 30236646.37 | 32759.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241299E+11 | 41926.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271631E+10 | 7264.39 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308260E+10 | 7263.11 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224852E+10 | 7265.25 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182866E+10 | 7263.75 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179047E+09 | 5411.32 | 09-MAY-20:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2029627.72 | 5163.66 | 10-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2007530.56 | 2847.86 | 29-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1207379.05 | 3267.11 | 18-AUG-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62917406.40 | 6471.29 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162455E+10 | 7264.08 | 24-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232136E+10 | 7264.11 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430426E+10 | 7262.78 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1207379.05 | 2847.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.430426E+10 | 7265.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418884E+10 | 7232.76 | 30-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414920E+10 | 7231.22 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268201E+10 | 7233.39 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203476E+10 | 7231.88 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200947E+09 | 5338.67 | 03-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2018133.35 | 4856.30 | 10-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2000439.89 | 2489.38 | 28-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1756556.50 | 4152.66 | 18-AUG-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81894246.72 | 7002.48 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197733E+10 | 7232.20 | 24-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342089E+10 | 7232.84 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.579198E+10 | 7231.10 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1756556.50 | 2489.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579198E+10 | 7233.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.992539E+09 | 2207.99 | 30-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106472E+10 | 2207.58 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.840057E+09 | 2208.10 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.695073E+09 | 2208.19 | 30-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97277228.03 | 2182.52 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2280422.60 | 1863.19 | 06-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1770863.28 | 1854.05 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2379242.05 | 1640.68 | 17-AUG-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36847132.45 | 2194.94 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.624646E+09 | 2207.80 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.840982E+09 | 2207.87 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149625E+10 | 2207.67 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.669482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1770863.28 | 1640.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149625E+10 | 2208.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147871E+10 | 2196.12 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142037E+10 | 2195.98 | 20-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.999652E+09 | 2196.23 | 18-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.764216E+09 | 2196.34 | 25-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106628E+09 | 2173.66 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2150546.45 | 1771.92 | 06-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1716077.54 | 1500.89 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2770428.95 | 1828.91 | 11-AUG-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47267213.88 | 2192.04 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.765321E+09 | 2196.21 | 29-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120026E+10 | 2196.10 | 14-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196736E+10 | 2195.82 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.875642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1716077.54 | 1500.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196736E+10 | 2196.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.210933E+10 | 10362.58 | 04-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300094E+10 | 10364.67 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269809E+10 | 10367.87 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241508E+10 | 10364.91 | 23-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290480E+09 | 10085.46 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10162587.96 | 8911.24 | 12-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8634491.36 | 9033.27 | 02-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8534665.30 | 8286.45 | 17-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79503760.44 | 10061.58 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192616E+10 | 10366.20 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198621E+10 | 10365.81 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393578E+10 | 10362.01 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8534665.30 | 8286.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393578E+10 | 10367.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.608306E+10 | 0.608306E+10 | 125900.60 | 20-JAN-13:00 | 125900.60 | 0.00 |
February | 0.00 | 0.00 | 0.348979E+10 | 0.348979E+10 | 114211.36 | 18-FEB-13:00 | 114211.36 | 0.00 |
March | 0.00 | 0.00 | 0.186262E+11 | 0.186262E+11 | 156078.96 | 14-MAR-13:00 | 156078.96 | 0.00 |
April | 0.00 | 0.00 | 0.194588E+11 | 0.194588E+11 | 108781.00 | 20-APR-13:00 | 108781.00 | 0.01 |
May | 0.00 | 0.00 | 0.890709E+11 | 0.890709E+11 | 202729.19 | 31-MAY-18:06 | 202729.19 | 0.10 |
June | 0.00 | 0.00 | 0.289771E+12 | 0.287127E+12 | 286350.21 | 26-JUN-18:15 | 286350.21 | 0.43 |
July | 0.00 | 0.00 | 0.331797E+12 | 0.316696E+12 | 271505.78 | 30-JUL-10:40 | 157143.64 | 0.51 |
August | 0.00 | 0.00 | 0.297342E+12 | 0.292054E+12 | 269522.92 | 16-AUG-18:15 | 269522.92 | 0.57 |
September | 0.00 | 0.00 | 0.207123E+12 | 0.207123E+12 | 236782.06 | 12-SEP-18:20 | 236782.06 | 0.16 |
October | 0.00 | 0.00 | 0.343237E+11 | 0.343237E+11 | 179667.17 | 11-OCT-15:10 | 179667.17 | 0.00 |
November | 0.00 | 0.00 | 0.116144E+11 | 0.116144E+11 | 138561.52 | 06-NOV-13:00 | 138561.52 | 0.00 |
December | 0.00 | 0.00 | 0.777872E+10 | 0.777872E+10 | 118131.66 | 02-DEC-13:00 | 118131.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131648E+13 | 0.129345E+13 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 0.348979E+10 | 0.348979E+10 | 108781.00 | 108781.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.331797E+12 | 0.316696E+12 | 286350.21 | 286350.21 | 0.57 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.806506E+09 | 0.806506E+09 | 18772.42 | 20-JAN-14:00 | 18772.42 | 0.00 |
February | 0.00 | 0.00 | 0.433400E+09 | 0.433400E+09 | 15786.59 | 18-FEB-14:00 | 15786.59 | 0.00 |
March | 0.00 | 0.00 | 0.270944E+10 | 0.270944E+10 | 22841.19 | 14-MAR-13:00 | 22841.19 | 0.00 |
April | 0.00 | 0.00 | 0.323868E+10 | 0.323868E+10 | 20853.69 | 20-APR-13:00 | 20853.69 | 0.01 |
May | 0.00 | 0.00 | 0.145294E+11 | 0.145294E+11 | 26465.04 | 17-MAY-14:00 | 26465.04 | 0.07 |
June | 0.00 | 0.00 | 0.429232E+11 | 0.417028E+11 | 36862.46 | 21-JUN-17:10 | 24400.94 | 0.42 |
July | 0.00 | 0.00 | 0.508285E+11 | 0.465922E+11 | 40912.32 | 30-JUL-15:19 | 22671.31 | 0.46 |
August | 0.00 | 0.00 | 0.441315E+11 | 0.420448E+11 | 40916.51 | 05-AUG-14:40 | 20603.29 | 0.54 |
September | 0.00 | 0.00 | 0.305248E+11 | 0.305248E+11 | 28386.96 | 10-SEP-13:00 | 28386.96 | 0.14 |
October | 0.00 | 0.00 | 0.512786E+10 | 0.512786E+10 | 24666.44 | 11-OCT-14:00 | 24666.44 | 0.00 |
November | 0.00 | 0.00 | 0.173917E+10 | 0.173917E+10 | 20791.18 | 07-NOV-15:00 | 20791.18 | 0.00 |
December | 0.00 | 0.00 | 0.121725E+10 | 0.121725E+10 | 20813.10 | 02-DEC-15:00 | 20813.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198210E+12 | 0.190666E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 0.433400E+09 | 0.433400E+09 | 15786.59 | 15786.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.508285E+11 | 0.465922E+11 | 40916.51 | 28386.96 | 0.54 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107061E+10 | 0.106706E+10 | 22990.34 | 20-JAN-17:11 | 22990.34 | 0.00 |
February | 0.00 | 0.00 | 0.118230E+10 | 0.118197E+10 | 22385.12 | 26-FEB-17:51 | 22385.12 | 0.00 |
March | 0.00 | 0.00 | 0.213628E+10 | 0.213203E+10 | 24972.41 | 08-MAR-17:11 | 24972.41 | 0.00 |
April | 0.00 | 0.00 | 0.133481E+10 | 0.121640E+10 | 24889.25 | 08-APR-18:01 | 24889.25 | 0.06 |
May | 0.00 | 0.00 | 0.327331E+10 | 0.238926E+10 | 24766.82 | 27-MAY-16:11 | 24766.82 | 0.30 |
June | 0.00 | 0.00 | 0.867976E+10 | 0.644801E+10 | 25044.83 | 22-JUN-21:51 | 18786.16 | 0.48 |
July | 0.00 | 0.00 | 0.818964E+10 | 0.565881E+10 | 25403.78 | 31-JUL-21:51 | 17389.56 | 0.52 |
August | 0.00 | 0.00 | 0.845166E+10 | 0.591708E+10 | 24975.69 | 13-AUG-21:51 | 24975.69 | 0.51 |
September | 0.00 | 0.00 | 0.629342E+10 | 0.511488E+10 | 24396.48 | 15-SEP-19:51 | 24396.48 | 0.28 |
October | 0.00 | 0.00 | 0.298917E+10 | 0.281919E+10 | 24974.42 | 14-OCT-16:11 | 24974.42 | 0.07 |
November | 0.00 | 0.00 | 0.149550E+10 | 0.145305E+10 | 22405.71 | 07-NOV-17:41 | 22405.71 | 0.02 |
December | 0.00 | 0.00 | 0.676368E+09 | 0.676368E+09 | 21648.56 | 29-DEC-16:01 | 21648.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.457728E+11 | 0.360741E+11 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.676368E+09 | 0.676368E+09 | 21648.56 | 17389.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.867976E+10 | 0.644801E+10 | 25403.78 | 24975.69 | 0.52 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.153006E+09 | 0.152776E+09 | 21181.01 | 22-JAN-16:01 | 21181.01 | 0.00 |
February | 0.00 | 0.00 | 0.258242E+09 | 0.258242E+09 | 21180.58 | 23-FEB-16:01 | 21180.58 | 0.00 |
March | 0.00 | 0.00 | 0.960464E+09 | 0.959409E+09 | 23865.85 | 15-MAR-18:31 | 23865.85 | 0.00 |
April | 0.00 | 0.00 | 0.788429E+09 | 0.700783E+09 | 24096.12 | 08-APR-18:01 | 24096.12 | 0.05 |
May | 0.00 | 0.00 | 0.284034E+10 | 0.201763E+10 | 23920.77 | 27-MAY-16:11 | 23920.77 | 0.29 |
June | 0.00 | 0.00 | 0.833960E+10 | 0.621221E+10 | 24445.88 | 22-JUN-21:51 | 18314.62 | 0.47 |
July | 0.00 | 0.00 | 0.775283E+10 | 0.534740E+10 | 24699.74 | 31-JUL-21:51 | 16800.04 | 0.51 |
August | 0.00 | 0.00 | 0.726250E+10 | 0.496110E+10 | 24078.40 | 13-AUG-21:51 | 24078.40 | 0.50 |
September | 0.00 | 0.00 | 0.463377E+10 | 0.360785E+10 | 23058.64 | 15-SEP-19:51 | 23058.64 | 0.27 |
October | 0.00 | 0.00 | 0.129111E+10 | 0.121342E+10 | 23520.47 | 14-OCT-16:11 | 23520.47 | 0.04 |
November | 0.00 | 0.00 | 0.282726E+09 | 0.277980E+09 | 21193.29 | 04-NOV-15:01 | 21193.29 | 0.00 |
December | 0.00 | 0.00 | 58714387.70 | 58714387.70 | 21142.13 | 03-DEC-16:01 | 21142.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.346217E+11 | 0.257675E+11 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 58714387.70 | 58714387.70 | 21142.13 | 16800.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.833960E+10 | 0.621221E+10 | 24699.74 | 24096.12 | 0.51 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.275811E+11 | 0.275811E+11 | 65843.61 | 20-JAN-12:30 | 65843.61 | 0.00 |
February | 0.00 | 0.00 | 0.205023E+11 | 0.205023E+11 | 62700.78 | 18-FEB-12:50 | 62700.78 | 0.00 |
March | 0.00 | 0.00 | 0.195207E+11 | 0.195171E+11 | 57151.40 | 11-MAR-13:00 | 57151.40 | 0.00 |
April | 0.00 | 0.00 | 0.498448E+10 | 0.494940E+10 | 32959.04 | 08-APR-13:00 | 32959.04 | 0.00 |
May | 0.00 | 0.00 | 0.108168E+11 | 0.916952E+10 | 22596.07 | 16-MAY-13:20 | 22596.07 | 0.13 |
June | 0.00 | 0.00 | 0.298306E+11 | 0.220881E+11 | 30972.72 | 14-JUN-13:30 | 30972.72 | 0.36 |
July | 0.00 | 0.00 | 0.333129E+11 | 0.239975E+11 | 35149.94 | 23-JUL-13:00 | 25786.90 | 0.39 |
August | 0.00 | 0.00 | 0.397581E+11 | 0.287754E+11 | 44600.64 | 31-AUG-12:40 | 44600.64 | 0.51 |
September | 0.00 | 0.00 | 0.403871E+11 | 0.370935E+11 | 59408.76 | 28-SEP-13:00 | 59408.76 | 0.18 |
October | 0.00 | 0.00 | 0.316041E+11 | 0.314504E+11 | 61475.91 | 10-OCT-12:30 | 61475.91 | 0.01 |
November | 0.00 | 0.00 | 0.270715E+11 | 0.270698E+11 | 66174.24 | 07-NOV-12:10 | 66174.24 | 0.00 |
December | 0.00 | 0.00 | 0.171775E+11 | 0.171775E+11 | 59619.54 | 17-DEC-12:10 | 59619.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.302547E+12 | 0.269372E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 0.498448E+10 | 0.494940E+10 | 22596.07 | 22596.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.403871E+11 | 0.370935E+11 | 66174.24 | 66174.24 | 0.51 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.780103E+09 | 0.753945E+09 | 104253.41 | 21-JAN-09:01 | 104253.41 | 0.01 |
February | 0.00 | 0.00 | 0.778115E+09 | 0.774202E+09 | 103728.07 | 19-FEB-09:01 | 103728.07 | 0.00 |
March | 0.00 | 0.00 | 0.470935E+10 | 0.461287E+10 | 112468.48 | 14-MAR-20:51 | 112468.48 | 0.01 |
April | 0.00 | 0.00 | 0.685286E+10 | 0.529950E+10 | 114143.37 | 20-APR-20:31 | 114143.37 | 0.12 |
May | 0.00 | 0.00 | 0.249425E+11 | 0.186392E+11 | 116770.43 | 17-MAY-21:51 | 116770.43 | 0.28 |
June | 0.00 | 0.00 | 0.488259E+11 | 0.384146E+11 | 127925.56 | 20-JUN-21:51 | 91058.91 | 0.36 |
July | 0.00 | 0.00 | 0.500541E+11 | 0.380016E+11 | 130789.06 | 31-JUL-21:51 | 89644.59 | 0.41 |
August | 0.00 | 0.00 | 0.435478E+11 | 0.311791E+11 | 124599.05 | 29-AUG-21:51 | 89128.81 | 0.40 |
September | 0.00 | 0.00 | 0.283710E+11 | 0.233240E+11 | 117395.68 | 09-SEP-21:51 | 117395.68 | 0.20 |
October | 0.00 | 0.00 | 0.728878E+10 | 0.649353E+10 | 111722.16 | 10-OCT-20:31 | 111722.16 | 0.08 |
November | 0.00 | 0.00 | 0.178996E+10 | 0.164854E+10 | 104441.99 | 09-NOV-19:01 | 104441.99 | 0.02 |
December | 0.00 | 0.00 | 0.568888E+09 | 0.568888E+09 | 83568.81 | 02-DEC-09:01 | 83568.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218509E+12 | 0.169710E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.568888E+09 | 0.568888E+09 | 83568.81 | 83568.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.500541E+11 | 0.384146E+11 | 130789.06 | 117395.68 | 0.41 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107308E+10 | 0.106653E+10 | 19013.32 | 22-JAN-09:01 | 19013.32 | 0.00 |
February | 0.00 | 0.00 | 0.134892E+10 | 0.134889E+10 | 19017.56 | 23-FEB-09:01 | 19017.56 | 0.00 |
March | 0.00 | 0.00 | 0.244548E+10 | 0.242707E+10 | 20242.60 | 15-MAR-18:31 | 20242.60 | 0.01 |
April | 0.00 | 0.00 | 0.178114E+10 | 0.163436E+10 | 21955.31 | 19-APR-08:51 | 21955.31 | 0.07 |
May | 0.00 | 0.00 | 0.382053E+10 | 0.292947E+10 | 21977.58 | 17-MAY-08:51 | 21977.58 | 0.31 |
June | 0.00 | 0.00 | 0.900118E+10 | 0.681256E+10 | 21967.13 | 07-JUN-08:41 | 21967.13 | 0.50 |
July | 0.00 | 0.00 | 0.910075E+10 | 0.662717E+10 | 23156.39 | 01-JUL-07:42 | 23156.39 | 0.55 |
August | 0.00 | 0.00 | 0.929588E+10 | 0.679398E+10 | 22965.93 | 04-AUG-08:32 | 19904.52 | 0.54 |
September | 0.00 | 0.00 | 0.677576E+10 | 0.567032E+10 | 21960.47 | 07-SEP-08:51 | 21960.47 | 0.30 |
October | 0.00 | 0.00 | 0.302628E+10 | 0.286688E+10 | 21927.29 | 11-OCT-08:51 | 21927.29 | 0.07 |
November | 0.00 | 0.00 | 0.146386E+10 | 0.140472E+10 | 21483.53 | 09-NOV-09:51 | 21483.53 | 0.03 |
December | 0.00 | 0.00 | 0.702487E+09 | 0.702487E+09 | 18994.00 | 16-DEC-09:01 | 18994.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.498353E+11 | 0.402844E+11 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.702487E+09 | 0.702487E+09 | 18994.00 | 18994.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.929588E+10 | 0.681256E+10 | 23156.39 | 23156.39 | 0.55 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.194174E+09 | 0.188678E+09 | 18211.12 | 20-JAN-09:02 | 18211.12 | 0.00 |
February | 0.00 | 0.00 | 0.396369E+09 | 0.396369E+09 | 18587.24 | 23-FEB-09:01 | 18587.24 | 0.00 |
March | 0.00 | 0.00 | 0.117327E+10 | 0.116006E+10 | 18983.77 | 14-MAR-20:51 | 18983.77 | 0.01 |
April | 0.00 | 0.00 | 0.118463E+10 | 0.106140E+10 | 21455.74 | 19-APR-08:51 | 21455.74 | 0.06 |
May | 0.00 | 0.00 | 0.334973E+10 | 0.252327E+10 | 21480.31 | 17-MAY-08:51 | 21480.31 | 0.30 |
June | 0.00 | 0.00 | 0.864166E+10 | 0.652023E+10 | 22036.02 | 27-JUN-08:32 | 22036.02 | 0.50 |
July | 0.00 | 0.00 | 0.865266E+10 | 0.625219E+10 | 23504.49 | 01-JUL-07:42 | 23504.49 | 0.54 |
August | 0.00 | 0.00 | 0.807898E+10 | 0.568178E+10 | 22477.37 | 04-AUG-08:32 | 19433.27 | 0.53 |
September | 0.00 | 0.00 | 0.505683E+10 | 0.403251E+10 | 21461.61 | 07-SEP-08:51 | 21461.61 | 0.29 |
October | 0.00 | 0.00 | 0.127514E+10 | 0.117255E+10 | 21270.66 | 11-OCT-08:51 | 21270.66 | 0.05 |
November | 0.00 | 0.00 | 0.362807E+09 | 0.328220E+09 | 19153.87 | 09-NOV-09:51 | 19153.87 | 0.02 |
December | 0.00 | 0.00 | 0.116859E+09 | 0.116859E+09 | 18073.86 | 02-DEC-09:01 | 18073.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.384831E+11 | 0.294341E+11 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.116859E+09 | 0.116859E+09 | 18073.86 | 18073.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.865266E+10 | 0.652023E+10 | 23504.49 | 23504.49 | 0.54 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.250440E+09 | 0.249940E+09 | 6326.29 | 20-JAN-17:11 | 6326.29 | 0.00 |
February | 0.00 | 0.00 | 0.285597E+09 | 0.285385E+09 | 6089.19 | 26-FEB-17:51 | 6089.19 | 0.00 |
March | 0.00 | 0.00 | 0.533783E+09 | 0.533706E+09 | 6644.44 | 31-MAR-18:41 | 6644.44 | 0.00 |
April | 0.00 | 0.00 | 0.348752E+09 | 0.321696E+09 | 6634.63 | 08-APR-18:01 | 6634.63 | 0.05 |
May | 0.00 | 0.00 | 0.804651E+09 | 0.609767E+09 | 6645.80 | 27-MAY-16:11 | 6645.80 | 0.26 |
June | 0.00 | 0.00 | 0.225064E+10 | 0.169368E+10 | 6794.05 | 22-JUN-21:51 | 5065.12 | 0.48 |
July | 0.00 | 0.00 | 0.209292E+10 | 0.145911E+10 | 6885.57 | 31-JUL-21:51 | 4640.50 | 0.52 |
August | 0.00 | 0.00 | 0.216323E+10 | 0.153560E+10 | 6655.60 | 13-AUG-21:51 | 6655.60 | 0.51 |
September | 0.00 | 0.00 | 0.153613E+10 | 0.125442E+10 | 6615.61 | 15-SEP-19:51 | 6615.61 | 0.28 |
October | 0.00 | 0.00 | 0.692102E+09 | 0.659230E+09 | 6640.72 | 21-OCT-16:51 | 6640.72 | 0.05 |
November | 0.00 | 0.00 | 0.353871E+09 | 0.347567E+09 | 6247.55 | 05-NOV-17:41 | 6247.55 | 0.01 |
December | 0.00 | 0.00 | 0.156995E+09 | 0.156995E+09 | 5745.40 | 29-DEC-16:01 | 5745.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114691E+11 | 0.910710E+10 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.156995E+09 | 0.156995E+09 | 5745.40 | 4640.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.225064E+10 | 0.169368E+10 | 6885.57 | 6655.60 | 0.52 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 32370765.81 | 32309627.75 | 5611.92 | 20-JAN-17:11 | 5611.92 | 0.00 |
February | 0.00 | 0.00 | 59583240.31 | 59564509.69 | 5612.23 | 23-FEB-16:01 | 5612.23 | 0.00 |
March | 0.00 | 0.00 | 0.227909E+09 | 0.227836E+09 | 6461.77 | 15-MAR-18:31 | 6461.77 | 0.00 |
April | 0.00 | 0.00 | 0.201886E+09 | 0.182716E+09 | 6473.00 | 08-APR-18:01 | 6473.00 | 0.04 |
May | 0.00 | 0.00 | 0.683624E+09 | 0.506482E+09 | 6433.92 | 27-MAY-16:11 | 6433.92 | 0.25 |
June | 0.00 | 0.00 | 0.216096E+10 | 0.162687E+10 | 6623.60 | 22-JUN-21:51 | 4930.45 | 0.47 |
July | 0.00 | 0.00 | 0.197769E+10 | 0.137547E+10 | 6673.84 | 31-JUL-21:51 | 4463.52 | 0.51 |
August | 0.00 | 0.00 | 0.184616E+10 | 0.128148E+10 | 6471.88 | 13-AUG-21:51 | 6471.88 | 0.50 |
September | 0.00 | 0.00 | 0.109486E+10 | 0.857649E+09 | 6246.84 | 15-SEP-19:51 | 6246.84 | 0.27 |
October | 0.00 | 0.00 | 0.272518E+09 | 0.262279E+09 | 6305.05 | 08-OCT-18:11 | 6305.05 | 0.03 |
November | 0.00 | 0.00 | 62308474.64 | 62121183.94 | 5614.09 | 18-NOV-16:01 | 5614.09 | 0.00 |
December | 0.00 | 0.00 | 13798450.93 | 13798450.93 | 5602.05 | 03-DEC-16:01 | 5602.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.863366E+10 | 0.648858E+10 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 13798450.93 | 13798450.93 | 5602.05 | 4463.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216096E+10 | 0.162687E+10 | 6673.84 | 6473.00 | 0.51 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.679991E+10 | 0.668404E+10 | 28623.39 | 20-JAN-17:11 | 28623.39 | 0.04 |
February | 0.00 | 0.00 | 0.549784E+10 | 0.542013E+10 | 26868.04 | 26-FEB-17:51 | 26868.04 | 0.03 |
March | 0.00 | 0.00 | 0.544656E+10 | 0.541913E+10 | 29011.57 | 13-MAR-19:21 | 29011.57 | 0.02 |
April | 0.00 | 0.00 | 0.256906E+10 | 0.233959E+10 | 26869.20 | 20-APR-20:31 | 26869.20 | 0.09 |
May | 0.00 | 0.00 | 0.426562E+10 | 0.316111E+10 | 26390.19 | 09-MAY-20:31 | 26390.19 | 0.31 |
June | 0.00 | 0.00 | 0.967476E+10 | 0.694069E+10 | 28603.05 | 20-JUN-21:51 | 20183.62 | 0.49 |
July | 0.00 | 0.00 | 0.102882E+11 | 0.709347E+10 | 29458.73 | 31-JUL-21:51 | 20112.06 | 0.55 |
August | 0.00 | 0.00 | 0.117773E+11 | 0.845039E+10 | 28120.53 | 29-AUG-21:51 | 20280.33 | 0.54 |
September | 0.00 | 0.00 | 0.105406E+11 | 0.895910E+10 | 29040.01 | 25-SEP-20:41 | 29040.01 | 0.33 |
October | 0.00 | 0.00 | 0.771783E+10 | 0.736550E+10 | 29037.89 | 09-OCT-19:51 | 29037.89 | 0.10 |
November | 0.00 | 0.00 | 0.705143E+10 | 0.672166E+10 | 28881.97 | 05-NOV-17:41 | 28881.97 | 0.12 |
December | 0.00 | 0.00 | 0.494476E+10 | 0.494476E+10 | 26807.81 | 02-DEC-17:21 | 26807.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.865739E+11 | 0.734996E+11 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.256906E+10 | 0.233959E+10 | 26390.19 | 20112.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117773E+11 | 0.895910E+10 | 29458.73 | 29040.01 | 0.55 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 33984.19 | 214746.84 | 05-JAN-09:06 |
February | 0.21 | 542.16 | 20-FEB-15:20 | 39057.59 | 186268.67 | 12-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24361.98 | 183546.31 | 19-MAR-08:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22047.56 | 194363.43 | 15-APR-18:02 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 5809.94 | 146127.48 | 02-MAY-08:62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 193.72 | 98382.49 | 09-JUN-03:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 144.15 | 48162.43 | 04-JUL-21:54 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 124.64 | 48368.10 | 17-AUG-08:53 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1661.40 | 143253.46 | 21-SEP-18:57 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20399.83 | 167992.19 | 31-OCT-15:06 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27796.01 | 169608.79 | 26-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 53054.56 | 266895.97 | 21-DEC-09:13 |
Annual Sum or Average | 0.02 | 18955.70 | ||||
Minimum of Months | 0.00 | 0.00 | 124.64 | 48162.43 | ||
Maximum of Months | 0.21 | 542.16 | 53054.56 | 266895.97 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18451.74 | 231623.35 | 20-JAN-13:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15735.38 | 213861.85 | 18-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23593.23 | 390259.56 | 13-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18221.41 | 334640.61 | 19-APR-15:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 61748.97 | 435225.16 | 17-MAY-18:01 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 180280.20 | 531716.10 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 194716.15 | 498461.09 | 17-JUL-18:01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 179646.62 | 517909.51 | 16-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 134801.07 | 510083.63 | 28-SEP-15:01 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 37740.06 | 456414.14 | 11-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 22435.52 | 269363.17 | 09-NOV-09:51 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 13803.77 | 209673.13 | 02-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 75434.12 | 0.00 | ||||
Minimum of Months | 13803.77 | 209673.13 | 0.00 | 0.00 | ||
Maximum of Months | 194716.15 | 531716.10 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 29028.19 | 73276.77 | 24-JAN-07:51 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29387.24 | 70328.55 | 27-FEB-07:26 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28990.28 | 72588.52 | 16-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27884.40 | 69550.17 | 10-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26415.07 | 63497.60 | 09-MAY-06:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25016.63 | 54797.66 | 09-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23937.67 | 52292.05 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23590.27 | 47680.91 | 31-AUG-06:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23985.80 | 54138.75 | 27-SEP-06:33 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25022.49 | 62447.10 | 20-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 26501.22 | 63178.62 | 26-NOV-08:42 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 27969.21 | 65320.15 | 17-DEC-08:50 |
Annual Sum or Average | 0.00 | 26460.36 | ||||
Minimum of Months | 0.00 | 0.00 | 23590.27 | 47680.91 | ||
Maximum of Months | 0.00 | 0.00 | 29387.24 | 73276.77 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.08 | 2194.93 | 01-JAN-00:10 | 1.08 |
February | 0.530997E+10 | 1.08 | 2194.93 | 01-FEB-00:10 | 1.08 |
March | 0.587890E+10 | 1.08 | 2194.93 | 01-MAR-00:10 | 1.08 |
April | 0.568926E+10 | 1.08 | 2194.93 | 01-APR-00:10 | 1.08 |
May | 0.587890E+10 | 1.08 | 2194.93 | 01-MAY-00:02 | 1.08 |
June | 0.568926E+10 | 1.07 | 2194.93 | 01-JUN-00:10 | 1.07 |
July | 0.587890E+10 | 1.07 | 2194.93 | 01-JUL-00:10 | 1.08 |
August | 0.587890E+10 | 1.07 | 2194.93 | 01-AUG-00:05 | 1.07 |
September | 0.568926E+10 | 1.08 | 2194.93 | 01-SEP-00:10 | 1.08 |
October | 0.587890E+10 | 1.08 | 2194.93 | 01-OCT-00:10 | 1.07 |
November | 0.568926E+10 | 1.08 | 2194.93 | 01-NOV-00:05 | 1.08 |
December | 0.587890E+10 | 1.08 | 2194.93 | 01-DEC-00:05 | 1.08 |
Annual Sum or Average | 0.692193E+11 | 1.08 | |||
Minimum of Months | 0.530997E+10 | 1.07 | 2194.93 | 1.07 | |
Maximum of Months | 0.587890E+10 | 1.08 | 2194.93 | 1.08 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.356361E+11 | 0.90 | 51119.21 | 11-JAN-16:40 | 2.01 |
February | 0.312741E+11 | 0.89 | 49654.90 | 13-FEB-20:12 | 1.98 |
March | 0.356916E+11 | 0.90 | 49654.90 | 02-MAR-19:47 | 1.98 |
April | 0.343585E+11 | 0.90 | 49654.90 | 04-APR-21:15 | 1.97 |
May | 0.374573E+11 | 0.92 | 49654.90 | 02-MAY-21:10 | 1.98 |
June | 0.415147E+11 | 0.99 | 39252.95 | 30-JUN-21:10 | 1.70 |
July | 0.430714E+11 | 0.99 | 39279.16 | 17-JUL-21:10 | 1.70 |
August | 0.443191E+11 | 1.01 | 41865.33 | 16-AUG-21:10 | 1.77 |
September | 0.426081E+11 | 1.01 | 49654.90 | 21-SEP-19:35 | 1.97 |
October | 0.395372E+11 | 0.95 | 49654.90 | 02-OCT-21:20 | 1.97 |
November | 0.368488E+11 | 0.93 | 50204.15 | 14-NOV-09:00 | 1.99 |
December | 0.352849E+11 | 0.90 | 50204.15 | 15-DEC-09:15 | 1.99 |
Annual Sum or Average | 0.457602E+12 | 0.94 | |||
Minimum of Months | 0.312741E+11 | 0.89 | 39252.95 | 1.70 | |
Maximum of Months | 0.443191E+11 | 1.01 | 51119.21 | 2.01 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.33 | 76.61 | 01-JAN-00:10 | 0.33 |
February | 0.185347E+09 | 0.33 | 76.61 | 01-FEB-00:10 | 0.33 |
March | 0.205205E+09 | 0.33 | 76.61 | 01-MAR-00:10 | 0.33 |
April | 0.198586E+09 | 0.33 | 76.61 | 01-APR-00:10 | 0.33 |
May | 0.205205E+09 | 0.33 | 76.61 | 01-MAY-00:02 | 0.33 |
June | 0.198586E+09 | 0.33 | 76.61 | 01-JUN-00:10 | 0.33 |
July | 0.205205E+09 | 0.33 | 76.61 | 01-JUL-00:10 | 0.33 |
August | 0.205205E+09 | 0.33 | 76.61 | 01-AUG-00:05 | 0.32 |
September | 0.198586E+09 | 0.33 | 76.61 | 01-SEP-00:10 | 0.33 |
October | 0.205205E+09 | 0.33 | 76.61 | 01-OCT-00:10 | 0.33 |
November | 0.198586E+09 | 0.33 | 76.61 | 01-NOV-00:05 | 0.33 |
December | 0.205205E+09 | 0.33 | 76.61 | 01-DEC-00:05 | 0.33 |
Annual Sum or Average | 0.241613E+10 | 0.33 | |||
Minimum of Months | 0.185347E+09 | 0.33 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.33 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.33 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.33 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.33 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.33 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:01 | 0.33 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:03 | 0.33 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.33 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:05 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.33 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:10 | 0.33 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:05 | 0.33 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.33 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.317492E+09 | 0.57 | 1086.79 | 01-JAN-16:01 | 0.71 |
February | 0.334772E+09 | 0.58 | 1086.79 | 01-FEB-09:02 | 0.71 |
March | 0.331613E+09 | 0.57 | 1086.79 | 01-MAR-19:02 | 0.71 |
April | 0.261998E+09 | 0.54 | 1086.79 | 01-APR-15:02 | 0.71 |
May | 0.200939E+09 | 0.50 | 1086.79 | 02-MAY-08:62 | 0.71 |
June | 0.433032E+09 | 0.53 | 1086.79 | 01-JUN-08:51 | 0.70 |
July | 0.400424E+09 | 0.52 | 1086.79 | 01-JUL-08:61 | 0.71 |
August | 0.410237E+09 | 0.52 | 1086.79 | 01-AUG-08:51 | 0.71 |
September | 0.327822E+09 | 0.51 | 1086.79 | 01-SEP-08:51 | 0.70 |
October | 0.311364E+09 | 0.58 | 1086.79 | 01-OCT-08:61 | 0.71 |
November | 0.294795E+09 | 0.58 | 1086.79 | 01-NOV-08:62 | 0.71 |
December | 0.475503E+09 | 0.58 | 1086.79 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.409999E+10 | 0.55 | |||
Minimum of Months | 0.200939E+09 | 0.50 | 1086.79 | 0.70 | |
Maximum of Months | 0.475503E+09 | 0.58 | 1086.79 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.394575E+09 | 0.54 | 1062.14 | 01-JAN-09:01 | 0.71 |
February | 0.377916E+09 | 0.56 | 1062.14 | 01-FEB-09:02 | 0.71 |
March | 0.312764E+09 | 0.54 | 1062.14 | 01-MAR-09:01 | 0.71 |
April | 0.251321E+09 | 0.51 | 1062.14 | 01-APR-15:02 | 0.71 |
May | 0.181402E+09 | 0.48 | 1062.14 | 02-MAY-08:62 | 0.71 |
June | 0.418069E+09 | 0.53 | 1062.14 | 01-JUN-08:51 | 0.70 |
July | 0.381366E+09 | 0.51 | 1062.14 | 01-JUL-08:61 | 0.71 |
August | 0.356127E+09 | 0.51 | 1062.14 | 01-AUG-08:51 | 0.71 |
September | 0.253423E+09 | 0.48 | 1062.14 | 01-SEP-08:51 | 0.70 |
October | 0.263049E+09 | 0.53 | 1062.14 | 01-OCT-15:01 | 0.71 |
November | 0.328883E+09 | 0.54 | 1062.14 | 01-NOV-08:62 | 0.71 |
December | 0.581869E+09 | 0.57 | 1062.14 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.410077E+10 | 0.52 | |||
Minimum of Months | 0.181402E+09 | 0.48 | 1062.14 | 0.70 | |
Maximum of Months | 0.581869E+09 | 0.57 | 1062.14 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130966E+10 | 0.33 | 3054.40 | 20-JAN-12:40 | 0.71 |
February | 0.125654E+10 | 0.37 | 2923.94 | 18-FEB-12:50 | 0.71 |
March | 0.116821E+10 | 0.37 | 2696.80 | 11-MAR-13:00 | 0.71 |
April | 0.327231E+09 | 0.16 | 1408.56 | 08-APR-13:00 | 0.71 |
May | 0.560190E+09 | 0.35 | 994.78 | 16-MAY-13:20 | 0.71 |
June | 0.136449E+10 | 0.59 | 1356.57 | 26-JUN-12:10 | 0.71 |
July | 0.149508E+10 | 0.61 | 1526.49 | 23-JUL-13:20 | 0.71 |
August | 0.177238E+10 | 0.62 | 1863.58 | 31-AUG-12:40 | 0.71 |
September | 0.182698E+10 | 0.60 | 2788.40 | 28-SEP-13:00 | 0.71 |
October | 0.158262E+10 | 0.39 | 2872.56 | 10-OCT-12:30 | 0.71 |
November | 0.134259E+10 | 0.35 | 3068.97 | 07-NOV-12:10 | 0.71 |
December | 0.113392E+10 | 0.27 | 2798.12 | 17-DEC-12:10 | 0.71 |
Annual Sum or Average | 0.151399E+11 | 0.42 | |||
Minimum of Months | 0.327231E+09 | 0.16 | 994.78 | 0.71 | |
Maximum of Months | 0.182698E+10 | 0.62 | 3068.97 | 0.71 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167533E+10 | 0.51 | 5649.51 | 01-JAN-16:01 | 0.71 |
February | 0.167391E+10 | 0.51 | 5649.51 | 01-FEB-09:02 | 0.71 |
March | 0.118641E+10 | 0.48 | 5649.51 | 01-MAR-09:01 | 0.71 |
April | 0.936321E+09 | 0.47 | 5649.51 | 01-APR-15:02 | 0.71 |
May | 0.132038E+10 | 0.41 | 5649.51 | 03-MAY-18:51 | 0.71 |
June | 0.244587E+10 | 0.44 | 5649.51 | 01-JUN-08:51 | 0.70 |
July | 0.252403E+10 | 0.44 | 5649.51 | 01-JUL-08:61 | 0.71 |
August | 0.211514E+10 | 0.40 | 5649.51 | 01-AUG-08:51 | 0.71 |
September | 0.147676E+10 | 0.38 | 5649.51 | 01-SEP-08:51 | 0.70 |
October | 0.100600E+10 | 0.47 | 5649.51 | 01-OCT-08:61 | 0.71 |
November | 0.133542E+10 | 0.50 | 5649.51 | 01-NOV-08:62 | 0.71 |
December | 0.245998E+10 | 0.53 | 5649.51 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.201555E+11 | 0.46 | |||
Minimum of Months | 0.936321E+09 | 0.38 | 5649.51 | 0.70 | |
Maximum of Months | 0.252403E+10 | 0.53 | 5649.51 | 0.71 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.314138E+09 | 0.56 | 952.29 | 01-JAN-09:01 | 0.71 |
February | 0.333949E+09 | 0.59 | 952.29 | 01-FEB-09:02 | 0.71 |
March | 0.327085E+09 | 0.59 | 952.29 | 01-MAR-09:01 | 0.71 |
April | 0.264726E+09 | 0.56 | 952.29 | 01-APR-15:02 | 0.71 |
May | 0.222126E+09 | 0.54 | 952.29 | 03-MAY-08:61 | 0.71 |
June | 0.450471E+09 | 0.55 | 952.29 | 01-JUN-08:51 | 0.70 |
July | 0.454337E+09 | 0.53 | 952.29 | 01-JUL-08:61 | 0.71 |
August | 0.454821E+09 | 0.54 | 952.29 | 01-AUG-08:51 | 0.71 |
September | 0.352550E+09 | 0.53 | 952.29 | 01-SEP-08:51 | 0.70 |
October | 0.307386E+09 | 0.60 | 952.29 | 01-OCT-08:61 | 0.71 |
November | 0.291836E+09 | 0.58 | 952.29 | 01-NOV-08:62 | 0.71 |
December | 0.457098E+09 | 0.57 | 952.29 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.423052E+10 | 0.56 | |||
Minimum of Months | 0.222126E+09 | 0.53 | 952.29 | 0.70 | |
Maximum of Months | 0.457098E+09 | 0.60 | 952.29 | 0.71 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.373368E+09 | 0.53 | 930.74 | 01-JAN-09:01 | 0.71 |
February | 0.369439E+09 | 0.56 | 930.74 | 01-FEB-09:02 | 0.71 |
March | 0.297254E+09 | 0.54 | 930.74 | 01-MAR-09:01 | 0.71 |
April | 0.249521E+09 | 0.53 | 930.74 | 01-APR-15:02 | 0.71 |
May | 0.201467E+09 | 0.52 | 930.74 | 03-MAY-08:61 | 0.71 |
June | 0.435321E+09 | 0.55 | 930.74 | 01-JUN-08:51 | 0.70 |
July | 0.434038E+09 | 0.53 | 930.74 | 01-JUL-08:61 | 0.71 |
August | 0.396801E+09 | 0.54 | 930.74 | 01-AUG-08:51 | 0.71 |
September | 0.272545E+09 | 0.52 | 930.74 | 01-SEP-08:51 | 0.70 |
October | 0.250816E+09 | 0.53 | 930.74 | 01-OCT-08:61 | 0.71 |
November | 0.321564E+09 | 0.53 | 930.74 | 01-NOV-08:62 | 0.71 |
December | 0.552401E+09 | 0.57 | 930.74 | 01-DEC-17:11 | 0.71 |
Annual Sum or Average | 0.415453E+10 | 0.54 | |||
Minimum of Months | 0.201467E+09 | 0.52 | 930.74 | 0.70 | |
Maximum of Months | 0.552401E+09 | 0.57 | 930.74 | 0.71 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103953E+09 | 0.57 | 288.43 | 01-JAN-09:01 | 0.71 |
February | 0.106631E+09 | 0.59 | 288.43 | 01-FEB-09:02 | 0.71 |
March | 0.100602E+09 | 0.58 | 288.43 | 01-MAR-09:01 | 0.71 |
April | 81182191.38 | 0.56 | 288.43 | 01-APR-15:02 | 0.71 |
May | 54478909.68 | 0.51 | 288.43 | 01-MAY-08:62 | 0.71 |
June | 0.112870E+09 | 0.53 | 288.43 | 01-JUN-08:51 | 0.70 |
July | 0.102798E+09 | 0.52 | 288.43 | 01-JUL-08:61 | 0.71 |
August | 0.105777E+09 | 0.52 | 288.43 | 01-AUG-08:51 | 0.71 |
September | 82203133.89 | 0.51 | 288.43 | 01-SEP-08:51 | 0.70 |
October | 91768898.45 | 0.58 | 288.43 | 01-OCT-15:01 | 0.71 |
November | 93885755.02 | 0.58 | 288.43 | 01-NOV-08:62 | 0.71 |
December | 0.151316E+09 | 0.59 | 288.43 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.118747E+10 | 0.55 | |||
Minimum of Months | 54478909.68 | 0.51 | 288.43 | 0.70 | |
Maximum of Months | 0.151316E+09 | 0.59 | 288.43 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127262E+09 | 0.56 | 281.44 | 01-JAN-09:01 | 0.71 |
February | 0.121787E+09 | 0.58 | 281.44 | 01-FEB-09:02 | 0.71 |
March | 97912254.28 | 0.55 | 281.44 | 01-MAR-09:01 | 0.71 |
April | 78669953.20 | 0.53 | 281.44 | 01-APR-15:02 | 0.71 |
May | 49398232.50 | 0.49 | 281.44 | 01-MAY-08:62 | 0.71 |
June | 0.109059E+09 | 0.53 | 281.44 | 01-JUN-08:51 | 0.70 |
July | 97716622.04 | 0.51 | 281.44 | 01-JUL-08:61 | 0.71 |
August | 91158732.31 | 0.51 | 281.44 | 01-AUG-08:51 | 0.71 |
September | 62579146.02 | 0.48 | 281.44 | 01-SEP-08:51 | 0.70 |
October | 83217965.49 | 0.53 | 281.44 | 01-OCT-15:01 | 0.71 |
November | 0.107342E+09 | 0.55 | 281.44 | 01-NOV-08:62 | 0.71 |
December | 0.186413E+09 | 0.60 | 281.44 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.121252E+10 | 0.54 | |||
Minimum of Months | 49398232.50 | 0.48 | 281.44 | 0.70 | |
Maximum of Months | 0.186413E+09 | 0.60 | 281.44 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.529275E+09 | 0.63 | 1258.67 | 01-JAN-09:01 | 0.71 |
February | 0.518993E+09 | 0.64 | 1258.67 | 01-FEB-09:02 | 0.71 |
March | 0.498264E+09 | 0.60 | 1258.67 | 01-MAR-16:02 | 0.71 |
April | 0.342478E+09 | 0.56 | 1258.67 | 01-APR-15:02 | 0.71 |
May | 0.255767E+09 | 0.52 | 1258.67 | 02-MAY-08:62 | 0.71 |
June | 0.470089E+09 | 0.53 | 1258.67 | 01-JUN-08:51 | 0.70 |
July | 0.496807E+09 | 0.51 | 1258.67 | 01-JUL-08:61 | 0.71 |
August | 0.564425E+09 | 0.52 | 1258.67 | 01-AUG-08:51 | 0.71 |
September | 0.539606E+09 | 0.52 | 1258.67 | 01-SEP-08:51 | 0.70 |
October | 0.546228E+09 | 0.60 | 1258.67 | 01-OCT-08:61 | 0.71 |
November | 0.530969E+09 | 0.63 | 1258.67 | 01-NOV-08:62 | 0.71 |
December | 0.612034E+09 | 0.61 | 1258.67 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.590494E+10 | 0.57 | |||
Minimum of Months | 0.255767E+09 | 0.51 | 1258.67 | 0.70 | |
Maximum of Months | 0.612034E+09 | 0.64 | 1258.67 | 0.71 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.922322E+09 | 0.830090E+09 | 1041.12 | 05-JAN-09:13 | 937.01 | 937.01 | 34.94 | 1.99 |
February | 0.904430E+09 | 0.813987E+09 | 1067.53 | 07-FEB-10:12 | 960.78 | 960.78 | 43.35 | 2.13 |
March | 0.705415E+09 | 0.634873E+09 | 1048.89 | 22-MAR-08:62 | 944.00 | 944.00 | 40.16 | 2.03 |
April | 0.602564E+09 | 0.542308E+09 | 1026.70 | 14-APR-15:02 | 924.03 | 924.03 | 37.12 | 1.92 |
May | 0.166221E+09 | 0.149599E+09 | 947.81 | 02-MAY-21:25 | 853.03 | 853.03 | 48.52 | 1.59 |
June | 4957422.91 | 4461680.62 | 784.71 | 09-JUN-03:56 | 706.24 | 706.24 | 39.32 | 1.14 |
July | 3325641.80 | 2993077.62 | 419.09 | 04-JUL-21:54 | 377.18 | 377.18 | 36.75 | 0.50 |
August | 3406000.78 | 3065400.70 | 468.93 | 17-AUG-08:53 | 422.04 | 422.04 | 39.58 | 0.57 |
September | 48198953.46 | 43379058.12 | 954.98 | 22-SEP-08:62 | 859.48 | 859.48 | 53.30 | 1.61 |
October | 0.547364E+09 | 0.492628E+09 | 988.95 | 26-OCT-01:05 | 890.05 | 890.05 | 57.03 | 1.74 |
November | 0.765968E+09 | 0.689371E+09 | 1051.01 | 30-NOV-23:35 | 945.91 | 945.91 | 44.14 | 2.04 |
December | 0.115336E+10 | 0.103803E+10 | 1123.94 | 21-DEC-09:13 | 1011.55 | 1011.55 | 35.17 | 2.57 |
Annual Sum or Average | 0.582753E+10 | 0.524478E+10 | ||||||
Minimum of Months | 3325641.80 | 2993077.62 | 419.09 | 377.18 | 377.18 | 34.94 | 0.50 | |
Maximum of Months | 0.115336E+10 | 0.103803E+10 | 1123.94 | 1011.55 | 1011.55 | 57.03 | 2.57 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 25510813.22 | 22959731.89 | 156.09 | 23-JAN-16:03 | 140.48 | 140.48 | 6.72 | 6.39 |
February | 20568896.49 | 18512006.84 | 155.53 | 18-FEB-09:01 | 139.98 | 139.98 | 6.72 | 6.38 |
March | 36843858.93 | 33159473.03 | 511.02 | 13-MAR-15:01 | 459.92 | 459.92 | 6.72 | 11.04 |
April | 19868694.90 | 17881825.41 | 314.86 | 07-APR-15:01 | 283.38 | 283.38 | 6.72 | 8.88 |
May | 98840147.07 | 88956132.36 | 842.67 | 31-MAY-18:01 | 758.40 | 758.40 | 6.72 | 13.72 |
June | 0.429405E+09 | 0.386465E+09 | 1164.79 | 15-JUN-18:15 | 1048.31 | 1048.31 | 6.72 | 15.74 |
July | 0.522073E+09 | 0.469866E+09 | 1255.98 | 17-JUL-19:10 | 1130.38 | 1130.38 | 6.72 | 16.24 |
August | 0.511813E+09 | 0.460632E+09 | 1116.88 | 25-AUG-18:01 | 1005.19 | 1005.19 | 6.72 | 15.46 |
September | 0.298131E+09 | 0.268318E+09 | 1215.30 | 12-SEP-18:01 | 1093.77 | 1093.77 | 6.72 | 16.02 |
October | 64551965.18 | 58096768.67 | 587.01 | 10-OCT-15:01 | 528.31 | 528.31 | 6.72 | 11.73 |
November | 31350932.79 | 28215839.51 | 356.62 | 09-NOV-09:51 | 320.96 | 320.96 | 6.72 | 9.40 |
December | 18172130.82 | 16354917.74 | 150.81 | 02-DEC-14:30 | 135.73 | 135.73 | 6.72 | 6.29 |
Annual Sum or Average | 0.207713E+10 | 0.186942E+10 | ||||||
Minimum of Months | 18172130.82 | 16354917.74 | 150.81 | 135.73 | 135.73 | 6.72 | 6.29 | |
Maximum of Months | 0.522073E+09 | 0.469866E+09 | 1255.98 | 1130.38 | 1130.38 | 6.72 | 16.24 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.512686E+10 | 0.461417E+10 | 3060.55 | 01-JAN-04:10 | 2754.50 | 2754.50 | 6.72 | 27.07 |
February | 0.425515E+10 | 0.382964E+10 | 3060.55 | 01-FEB-01:10 | 2754.50 | 2754.50 | 6.72 | 27.07 |
March | 0.522247E+10 | 0.470023E+10 | 3060.55 | 01-MAR-01:05 | 2754.50 | 2754.50 | 6.72 | 27.07 |
April | 0.499487E+10 | 0.449538E+10 | 3060.55 | 01-APR-00:10 | 2754.50 | 2754.50 | 6.77 | 27.07 |
May | 0.778389E+10 | 0.700550E+10 | 3060.55 | 01-MAY-05:01 | 2754.50 | 2754.50 | 6.74 | 27.07 |
June | 0.793295E+10 | 0.713965E+10 | 3060.55 | 01-JUN-00:10 | 2754.50 | 2754.50 | 7.26 | 27.07 |
July | 0.819738E+10 | 0.737764E+10 | 3060.55 | 01-JUL-00:10 | 2754.50 | 2754.50 | 8.49 | 27.07 |
August | 0.819738E+10 | 0.737764E+10 | 3060.55 | 01-AUG-00:05 | 2754.50 | 2754.50 | 8.01 | 27.07 |
September | 0.778440E+10 | 0.700596E+10 | 3060.55 | 01-SEP-00:10 | 2754.50 | 2754.50 | 7.80 | 27.07 |
October | 0.609150E+10 | 0.548235E+10 | 3060.55 | 01-OCT-00:10 | 2754.50 | 2754.50 | 6.91 | 27.07 |
November | 0.543190E+10 | 0.488871E+10 | 3060.55 | 01-NOV-02:20 | 2754.50 | 2754.50 | 6.73 | 27.07 |
December | 0.397746E+10 | 0.357972E+10 | 3060.55 | 01-DEC-07:45 | 2754.50 | 2754.50 | 6.73 | 27.07 |
Annual Sum or Average | 0.749962E+11 | 0.674966E+11 | ||||||
Minimum of Months | 0.397746E+10 | 0.357972E+10 | 3060.55 | 2754.50 | 2754.50 | 6.72 | 27.07 | |
Maximum of Months | 0.819738E+10 | 0.737764E+10 | 3060.55 | 2754.50 | 2754.50 | 8.49 | 27.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 47.97 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 48.37 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 48.61 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.67 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:02 | 14.37 | 14.37 | 50.78 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.25 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.28 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.23 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.10 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.56 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.99 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 49.31 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.97 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.10 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 46.68 | 60.00 | 33984.19 | 214746.84 | 05-JAN-09:06 |
February | 0.21 | 542.16 | 20-FEB-15:20 | 60.14 | 60.14 | 39057.59 | 186268.67 | 12-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 45.57 | 60.00 | 24361.98 | 183546.31 | 19-MAR-08:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 48.10 | 60.00 | 22047.56 | 194363.43 | 15-APR-18:02 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 40.53 | 60.00 | 5809.94 | 146127.48 | 02-MAY-08:62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.92 | 32.92 | 193.72 | 98382.49 | 09-JUN-03:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 43.27 | 43.27 | 144.15 | 48162.43 | 04-JUL-21:54 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 43.64 | 43.64 | 124.64 | 48368.10 | 17-AUG-08:53 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 35.95 | 35.95 | 1661.40 | 143253.46 | 21-SEP-18:57 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35.94 | 60.00 | 20399.83 | 167992.19 | 31-OCT-15:06 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 41.88 | 60.00 | 27796.01 | 169608.79 | 26-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 37.55 | 60.00 | 53054.56 | 266895.97 | 21-DEC-09:13 |
Annual Sum or Average | 0.02 | 18955.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 32.92 | 32.92 | 124.64 | 48162.43 | ||
Maximum of Months | 0.21 | 542.16 | 60.14 | 60.14 | 53054.56 | 266895.97 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18451.74 | 231623.35 | 20-JAN-13:10 | 8.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15735.38 | 213861.85 | 18-FEB-13:30 | 8.58 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23593.23 | 390259.56 | 13-MAR-15:01 | 10.14 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18221.41 | 334640.61 | 19-APR-15:01 | 9.65 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 61748.97 | 435225.16 | 17-MAY-18:01 | 10.54 | 6.70 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 180280.20 | 531716.10 | 26-JUN-18:03 | 11.39 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 194716.15 | 498461.09 | 17-JUL-18:01 | 11.09 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 179646.62 | 517909.51 | 16-AUG-18:03 | 11.27 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 134801.07 | 510083.63 | 28-SEP-15:01 | 11.20 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 37740.06 | 456414.14 | 11-OCT-15:01 | 10.72 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 22435.52 | 269363.17 | 09-NOV-09:51 | 9.07 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 13803.77 | 209673.13 | 02-DEC-14:30 | 8.55 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 75434.12 | 0.00 | ||||||
Minimum of Months | 13803.77 | 209673.13 | 8.55 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 194716.15 | 531716.10 | 11.39 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 47.97 | 59.40 | 29028.19 | 73276.77 | 24-JAN-07:51 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 48.37 | 58.66 | 29387.24 | 70328.55 | 27-FEB-07:26 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 48.61 | 59.11 | 28990.28 | 72588.52 | 16-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.67 | 59.59 | 27884.40 | 69550.17 | 10-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 50.78 | 58.56 | 26415.07 | 63497.60 | 09-MAY-06:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.25 | 59.21 | 25016.63 | 54797.66 | 09-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.28 | 58.57 | 23937.67 | 52292.05 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.23 | 58.42 | 23590.27 | 47680.91 | 31-AUG-06:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.10 | 59.66 | 23985.80 | 54138.75 | 27-SEP-06:33 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.56 | 58.65 | 25022.49 | 62447.10 | 20-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.99 | 58.92 | 26501.22 | 63178.62 | 26-NOV-08:42 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 49.31 | 59.13 | 27969.21 | 65320.15 | 17-DEC-08:50 |
Annual Sum or Average | 0.00 | 26460.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.97 | 58.42 | 23590.27 | 47680.91 | ||
Maximum of Months | 0.00 | 0.00 | 53.10 | 59.66 | 29387.24 | 73276.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.531272E+11 | 0.00 | 0.608306E+10 | 0.356361E+11 | 0.00 | 0.00 |
February | 0.505322E+11 | 0.00 | 0.348979E+10 | 0.312741E+11 | 0.00 | 0.00 |
March | 0.386621E+11 | 0.00 | 0.186262E+11 | 0.356916E+11 | 0.00 | 0.00 |
April | 0.395044E+11 | 0.00 | 0.194588E+11 | 0.343585E+11 | 0.00 | 0.00 |
May | 0.142018E+11 | 0.00 | 0.890709E+11 | 0.374573E+11 | 0.00 | 0.00 |
June | 0.424831E+09 | 0.00 | 0.289771E+12 | 0.415147E+11 | 0.00 | 0.00 |
July | 0.331551E+09 | 0.00 | 0.331797E+12 | 0.430714E+11 | 0.00 | 0.00 |
August | 0.257156E+09 | 0.00 | 0.297342E+12 | 0.443191E+11 | 0.00 | 0.00 |
September | 0.372910E+10 | 0.00 | 0.207123E+12 | 0.426081E+11 | 0.00 | 0.00 |
October | 0.362763E+11 | 0.00 | 0.343237E+11 | 0.395372E+11 | 0.00 | 0.00 |
November | 0.424732E+11 | 0.00 | 0.116144E+11 | 0.368488E+11 | 0.00 | 0.00 |
December | 0.808461E+11 | 0.00 | 0.777872E+10 | 0.352849E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.360366E+12 | 0.00 | 0.131648E+13 | 0.457602E+12 | 0.00 | 0.00 |
Minimum of Months | 0.257156E+09 | 0.00 | 0.348979E+10 | 0.312741E+11 | 0.00 | 0.00 |
Maximum of Months | 0.808461E+11 | 0.00 | 0.331797E+12 | 0.443191E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.310600E+10 | 0.00 | 0.806506E+09 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.381810E+10 | 0.00 | 0.433400E+09 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.166399E+10 | 0.00 | 0.270944E+10 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.102635E+10 | 0.00 | 0.323868E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 431997.36 | 0.00 | 0.145294E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 88650.10 | 0.00 | 0.429232E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 97989.27 | 0.00 | 0.508285E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 71689.02 | 0.00 | 0.441315E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 357813.50 | 0.00 | 0.305248E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.148342E+10 | 0.00 | 0.512786E+10 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.185459E+10 | 0.00 | 0.173917E+10 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.675228E+10 | 0.00 | 0.121725E+10 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.197058E+11 | 0.00 | 0.198210E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 71689.02 | 0.00 | 0.433400E+09 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.675228E+10 | 0.00 | 0.508285E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.356361E+11 | 0.608306E+10 | 0.531272E+11 | 0.413100E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312741E+11 | 0.349236E+10 | 0.505322E+11 | 0.413416E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356916E+11 | 0.186264E+11 | 0.386621E+11 | 0.299973E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343585E+11 | 0.194613E+11 | 0.395044E+11 | 0.247819E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374573E+11 | 0.890728E+11 | 0.142018E+11 | 0.636560E+11 | 0.213897E+09 | 0.00 | 0.00 | 0.00 |
June | 0.415147E+11 | 0.289771E+12 | 0.424831E+09 | 0.815236E+10 | 0.129625E+11 | 0.00 | 0.00 | 0.00 |
July | 0.430714E+11 | 0.331797E+12 | 0.331551E+09 | 0.859418E+10 | 0.138196E+11 | 0.00 | 0.00 | 0.00 |
August | 0.443191E+11 | 0.297342E+12 | 0.257156E+09 | 0.723470E+10 | 0.887190E+10 | 0.00 | 0.00 | 0.00 |
September | 0.426081E+11 | 0.207123E+12 | 0.372910E+10 | 0.257009E+11 | 0.307125E+10 | 0.00 | 0.00 | 0.00 |
October | 0.395372E+11 | 0.343335E+11 | 0.362763E+11 | 0.213079E+12 | 1732125.98 | 0.00 | 0.00 | 0.00 |
November | 0.368488E+11 | 0.116152E+11 | 0.424732E+11 | 0.325172E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352849E+11 | 0.777976E+10 | 0.808461E+11 | 0.449790E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457602E+12 | 0.131650E+13 | 0.360366E+12 | 0.247569E+13 | 0.389409E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312741E+11 | 0.349236E+10 | 0.257156E+09 | 0.723470E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.443191E+11 | 0.331797E+12 | 0.808461E+11 | 0.449790E+12 | 0.138196E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.806506E+09 | 0.310600E+10 | 0.831480E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.433400E+09 | 0.381810E+10 | 0.795515E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.270944E+10 | 0.166399E+10 | 0.625337E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.323868E+10 | 0.102635E+10 | 0.545446E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.145294E+11 | 431997.36 | 0.194127E+11 | 0.220950E+09 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.429232E+11 | 88650.10 | 0.125846E+10 | 0.613309E+10 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.508285E+11 | 97989.27 | 0.959251E+09 | 0.732771E+10 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.441315E+11 | 71689.02 | 0.929266E+09 | 0.500818E+10 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.305248E+11 | 357813.50 | 0.755880E+10 | 0.185541E+10 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.512786E+10 | 0.148342E+10 | 0.502942E+11 | 12968235.91 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.173917E+10 | 0.185459E+10 | 0.699372E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.121725E+10 | 0.675228E+10 | 0.896584E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.198210E+12 | 0.197058E+11 | 0.519786E+12 | 0.205583E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.433400E+09 | 71689.02 | 0.929266E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.508285E+11 | 0.675228E+10 | 0.896584E+11 | 0.732771E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.356361E+11 | 0.531272E+11 | 0.608306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312741E+11 | 0.505322E+11 | 0.348979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356916E+11 | 0.386621E+11 | 0.186262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343585E+11 | 0.395044E+11 | 0.194588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374573E+11 | 0.142018E+11 | 0.890709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415147E+11 | 0.424831E+09 | 0.289771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.430714E+11 | 0.331551E+09 | 0.331797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.443191E+11 | 0.257156E+09 | 0.297342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.426081E+11 | 0.372910E+10 | 0.207123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.395372E+11 | 0.362763E+11 | 0.343237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368488E+11 | 0.424732E+11 | 0.116144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352849E+11 | 0.808461E+11 | 0.777872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457602E+12 | 0.360366E+12 | 0.131648E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312741E+11 | 0.257156E+09 | 0.348979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.443191E+11 | 0.808461E+11 | 0.331797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.310600E+10 | 0.806506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.381810E+10 | 0.433400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.166399E+10 | 0.270944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.102635E+10 | 0.323868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 431997.36 | 0.145294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 88650.10 | 0.429232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 97989.27 | 0.508285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 71689.02 | 0.441315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 357813.50 | 0.305248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.148342E+10 | 0.512786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.185459E+10 | 0.173917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.675228E+10 | 0.121725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.197058E+11 | 0.198210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 71689.02 | 0.433400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.675228E+10 | 0.508285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.586834E+10 | 0.00 | 0.00 | 79423359.75 | 0.00 | 0.00 | 0.467856E+11 | 0.00 | 0.97 |
February | 0.141138E+11 | 0.00 | 0.00 | 41705714.37 | 0.00 | 0.00 | 0.306699E+11 | 0.00 | 0.92 |
March | 0.239010E+11 | 0.00 | 0.00 | 25506589.55 | 0.00 | 0.00 | 0.219163E+11 | 0.00 | 0.91 |
April | 0.194184E+11 | 0.00 | 0.00 | 32975997.61 | 0.00 | 0.00 | 0.250570E+11 | 0.00 | 0.92 |
May | 0.186880E+11 | 0.00 | 0.00 | 18308856.53 | 1058262.07 | 0.00 | 0.198460E+11 | 0.00 | 0.94 |
June | 0.254729E+10 | 17620246.19 | 0.00 | 35966618.20 | 0.298182E+09 | 0.00 | 0.188099E+11 | 0.00 | 0.97 |
July | 0.113052E+10 | 37005023.90 | 0.00 | 41832883.76 | 0.352059E+09 | 0.00 | 0.182530E+11 | 0.00 | 0.97 |
August | 0.468233E+09 | 0.196010E+09 | 0.00 | 73050353.44 | 11479885.55 | 0.00 | 0.252341E+11 | 0.00 | 1.08 |
September | 51392827.01 | 27683021.04 | 0.00 | 0.104479E+09 | 353253.95 | 0.00 | 0.373715E+11 | 0.00 | 1.22 |
October | 0.146890E+09 | 0.00 | 0.00 | 0.149259E+09 | 0.00 | 0.00 | 0.601098E+11 | 0.00 | 1.16 |
November | 0.308077E+09 | 0.00 | 0.00 | 0.151233E+09 | 0.00 | 0.00 | 0.599372E+11 | 0.00 | 1.14 |
December | 0.503377E+09 | 0.00 | 0.00 | 0.132274E+09 | 0.00 | 0.00 | 0.617585E+11 | 0.00 | 1.10 |
Annual Sum or Average | 0.871453E+11 | 0.278319E+09 | 0.00 | 0.886015E+09 | 0.663132E+09 | 0.00 | 0.425749E+12 | 0.00 | 1.03 |
Minimum of Months | 51392827.01 | 0.00 | 0.00 | 18308856.53 | 0.00 | 0.00 | 0.182530E+11 | 0.00 | 0.91 |
Maximum of Months | 0.239010E+11 | 0.196010E+09 | 0.00 | 0.151233E+09 | 0.352059E+09 | 0.00 | 0.617585E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444814E+10 | 0.00 | 0.00 | 7777575.20 | 0.00 | 0.868522E+09 | 0.253625E+10 | 0.00 | 2.73 |
February | 0.334597E+10 | 0.00 | 0.00 | 6847590.93 | 0.00 | 0.143238E+10 | 0.225864E+10 | 0.00 | 2.70 |
March | 0.374687E+10 | 0.00 | 0.00 | 4711547.42 | 0.00 | 0.125977E+10 | 0.203841E+10 | 0.00 | 2.67 |
April | 0.458709E+10 | 0.00 | 0.00 | 1311779.22 | 0.00 | 0.101970E+10 | 0.757627E+09 | 0.00 | 2.43 |
May | 0.489252E+10 | 193921.14 | 0.00 | 1235771.27 | 0.00 | 9879172.78 | 0.642771E+09 | 0.00 | 2.47 |
June | 0.186373E+10 | 66408691.40 | 0.00 | 4896352.62 | 16443.93 | 0.00 | 0.116297E+10 | 0.00 | 2.63 |
July | 0.161585E+10 | 76509933.94 | 0.00 | 5040383.48 | 738948.22 | 0.00 | 0.109286E+10 | 0.00 | 2.64 |
August | 0.182203E+10 | 50839330.41 | 0.00 | 7068300.45 | 0.00 | 0.00 | 0.144590E+10 | 0.00 | 2.82 |
September | 0.233910E+10 | 7637736.68 | 0.00 | 8342349.17 | 0.00 | 0.00 | 0.181524E+10 | 0.00 | 2.93 |
October | 0.368408E+10 | 0.00 | 0.00 | 6281301.97 | 0.00 | 0.901811E+09 | 0.261959E+10 | 0.00 | 2.80 |
November | 0.411478E+10 | 0.00 | 0.00 | 6963763.43 | 0.00 | 0.766582E+09 | 0.254941E+10 | 0.00 | 2.72 |
December | 0.426306E+10 | 0.00 | 0.00 | 4848096.24 | 0.00 | 0.179756E+10 | 0.171781E+10 | 0.00 | 2.63 |
Annual Sum or Average | 0.407232E+11 | 0.201590E+09 | 0.00 | 65324811.39 | 755392.15 | 0.805620E+10 | 0.206375E+11 | 0.00 | 2.68 |
Minimum of Months | 0.161585E+10 | 0.00 | 0.00 | 1235771.27 | 0.00 | 0.00 | 0.642771E+09 | 0.00 | 2.43 |
Maximum of Months | 0.489252E+10 | 76509933.94 | 0.00 | 8342349.17 | 738948.22 | 0.179756E+10 | 0.261959E+10 | 0.00 | 2.93 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299842E+10 | 0.00 | 0.00 | 1772576.14 | 0.00 | 0.00 | 0.135069E+10 | 0.00 | 1.27 |
February | 0.280850E+10 | 0.00 | 0.00 | 1588506.44 | 0.00 | 0.00 | 0.112151E+10 | 0.00 | 1.27 |
March | 0.257444E+10 | 0.00 | 0.00 | 2394043.06 | 0.00 | 0.00 | 0.164424E+10 | 0.00 | 1.32 |
April | 0.274677E+10 | 0.00 | 0.00 | 1549655.05 | 0.00 | 0.00 | 0.125044E+10 | 0.00 | 1.30 |
May | 0.135228E+10 | 96423.55 | 0.00 | 2906431.14 | 0.00 | 0.00 | 0.229648E+10 | 0.00 | 1.39 |
June | 44044012.75 | 30791208.21 | 0.00 | 6902150.05 | 98396.05 | 0.00 | 0.224053E+10 | 0.00 | 1.60 |
July | 22819304.07 | 35505178.45 | 0.00 | 6892852.46 | 985222.16 | 0.00 | 0.202210E+10 | 0.00 | 1.58 |
August | 61978509.37 | 20763036.26 | 0.00 | 7187485.04 | 40515.34 | 0.00 | 0.232113E+10 | 0.00 | 1.61 |
September | 0.248596E+09 | 2687144.03 | 0.00 | 6690358.65 | 0.00 | 0.00 | 0.266804E+10 | 0.00 | 1.57 |
October | 0.183453E+10 | 0.00 | 0.00 | 3456161.88 | 0.00 | 0.00 | 0.241264E+10 | 0.00 | 1.32 |
November | 0.254715E+10 | 0.00 | 0.00 | 2224308.23 | 0.00 | 0.00 | 0.159738E+10 | 0.00 | 1.26 |
December | 0.349116E+10 | 0.00 | 0.00 | 1063349.91 | 0.00 | 0.00 | 0.931902E+09 | 0.00 | 1.25 |
Annual Sum or Average | 0.207307E+11 | 89842990.50 | 0.00 | 44627878.05 | 1124133.56 | 0.00 | 0.218571E+11 | 0.00 | 1.40 |
Minimum of Months | 22819304.07 | 0.00 | 0.00 | 1063349.91 | 0.00 | 0.00 | 0.931902E+09 | 0.00 | 1.25 |
Maximum of Months | 0.349116E+10 | 35505178.45 | 0.00 | 7187485.04 | 985222.16 | 0.00 | 0.266804E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.304483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185971E+09 | 0.00 | 0.00 | 0.44 |
February | 0.249570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411480E+09 | 0.00 | 0.00 | 0.45 |
March | 0.304947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23505715.20 | 0.00 | 0.00 | 0.45 |
April | 0.294488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14501032.17 | 0.00 | 0.00 | 0.46 |
May | 0.252200E+10 | 0.00 | 0.00 | 101307.65 | 73225.30 | 0.00 | 98130607.20 | 0.00 | 0.47 |
June | 0.390723E+09 | 24591878.42 | 0.00 | 3797433.09 | 186932.97 | 0.00 | 0.119494E+10 | 0.00 | 0.54 |
July | 0.210041E+09 | 23439418.22 | 0.00 | 4532621.52 | 5974949.83 | 0.00 | 0.124523E+10 | 0.00 | 0.55 |
August | 0.427204E+09 | 14184894.09 | 0.00 | 3527556.20 | 907817.38 | 0.00 | 0.120830E+10 | 0.00 | 0.53 |
September | 0.107396E+10 | 1386364.02 | 0.00 | 2022929.74 | 558514.02 | 0.00 | 0.885613E+09 | 0.00 | 0.51 |
October | 0.290142E+10 | 0.00 | 0.00 | 10771.83 | 0.00 | 0.102317E+09 | 27503594.43 | 0.00 | 0.45 |
November | 0.288332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159079E+09 | 0.00 | 0.00 | 0.44 |
December | 0.258948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732891E+09 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.245330E+11 | 63602554.75 | 0.00 | 13992620.03 | 7701439.51 | 0.162974E+10 | 0.465972E+10 | 0.00 | 0.48 |
Minimum of Months | 0.210041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.304947E+10 | 24591878.42 | 0.00 | 4532621.52 | 5974949.83 | 0.732891E+09 | 0.124523E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313203E+09 | 0.00 | 0.00 | 0.51 |
February | 0.136285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580449E+09 | 0.00 | 0.00 | 0.52 |
March | 0.189183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162296E+09 | 0.00 | 0.00 | 0.52 |
April | 0.184650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131692E+09 | 0.00 | 0.00 | 0.53 |
May | 0.174950E+10 | 0.00 | 0.00 | 0.00 | 48947.41 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.623801E+09 | 14949190.83 | 0.00 | 1001815.36 | 841328.11 | 0.00 | 0.340427E+09 | 0.00 | 0.57 |
July | 0.444130E+09 | 14375653.63 | 0.00 | 1324921.12 | 4855303.22 | 0.00 | 0.423633E+09 | 0.00 | 0.57 |
August | 0.749710E+09 | 8044660.69 | 0.00 | 677732.30 | 1624223.24 | 0.00 | 0.262306E+09 | 0.00 | 0.56 |
September | 0.110742E+10 | 817551.41 | 0.00 | 267438.79 | 466182.50 | 0.00 | 0.146183E+09 | 0.00 | 0.55 |
October | 0.187416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152081E+09 | 0.00 | 0.00 | 0.52 |
November | 0.179755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236139E+09 | 0.00 | 0.00 | 0.51 |
December | 0.155081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685278E+09 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.168447E+11 | 38187056.56 | 0.00 | 3271907.58 | 7835984.49 | 0.226114E+10 | 0.117255E+10 | 0.00 | 0.54 |
Minimum of Months | 0.444130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.189183E+10 | 14949190.83 | 0.00 | 1324921.12 | 4855303.22 | 0.685278E+09 | 0.423633E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298376E+09 | 0.00 | 0.00 | 0.184353E+09 | 0.00 | 0.00 | 0.769937E+11 | 0.00 | 21.87 |
February | 0.202707E+09 | 0.00 | 0.00 | 0.161911E+09 | 0.00 | 0.00 | 0.689704E+11 | 0.00 | 21.88 |
March | 0.205104E+09 | 0.00 | 0.00 | 0.181927E+09 | 0.00 | 0.00 | 0.739727E+11 | 0.00 | 22.48 |
April | 0.491021E+09 | 0.00 | 0.00 | 0.191000E+09 | 0.00 | 0.00 | 0.707881E+11 | 0.00 | 22.65 |
May | 0.475526E+09 | 1420289.54 | 0.00 | 0.143346E+09 | 0.00 | 0.00 | 0.631827E+11 | 0.00 | 23.78 |
June | 12497617.14 | 0.419665E+09 | 0.00 | 0.129881E+09 | 0.00 | 0.00 | 0.331712E+11 | 0.00 | 23.75 |
July | 0.00 | 0.513079E+09 | 0.00 | 0.123060E+09 | 0.00 | 0.00 | 0.296567E+11 | 0.00 | 23.55 |
August | 0.00 | 0.274173E+09 | 0.00 | 0.134496E+09 | 0.00 | 0.00 | 0.354009E+11 | 0.00 | 23.94 |
September | 0.122060E+09 | 36200079.86 | 0.00 | 0.136272E+09 | 0.00 | 0.00 | 0.453917E+11 | 0.00 | 24.15 |
October | 0.577200E+09 | 0.00 | 0.00 | 0.168400E+09 | 0.00 | 0.00 | 0.721007E+11 | 0.00 | 22.03 |
November | 0.404387E+09 | 0.00 | 0.00 | 0.184363E+09 | 0.00 | 0.00 | 0.724011E+11 | 0.00 | 21.41 |
December | 0.436455E+09 | 0.00 | 0.00 | 0.172447E+09 | 0.00 | 0.00 | 0.779536E+11 | 0.00 | 21.55 |
Annual Sum or Average | 0.322533E+10 | 0.124454E+10 | 0.00 | 0.191146E+10 | 0.00 | 0.00 | 0.719983E+12 | 0.00 | 22.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123060E+09 | 0.00 | 0.00 | 0.296567E+11 | 0.00 | 21.41 |
Maximum of Months | 0.577200E+09 | 0.513079E+09 | 0.00 | 0.191000E+09 | 0.00 | 0.00 | 0.779536E+11 | 0.00 | 24.15 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.764650E+10 | 0.00 | 0.00 | 52232086.18 | 0.00 | 34904603.48 | 0.250805E+11 | 0.00 | 4.03 |
February | 0.817171E+10 | 0.00 | 0.00 | 46027883.16 | 0.00 | 0.384307E+09 | 0.208823E+11 | 0.00 | 3.99 |
March | 0.876105E+10 | 0.00 | 0.00 | 38216895.45 | 0.00 | 10464651.62 | 0.210518E+11 | 0.00 | 3.97 |
April | 0.115651E+11 | 0.00 | 0.00 | 24405038.57 | 0.00 | 0.00 | 0.152242E+11 | 0.00 | 3.65 |
May | 0.389889E+10 | 779456.88 | 0.00 | 31167703.93 | 0.00 | 0.00 | 0.196919E+11 | 0.00 | 3.74 |
June | 0.353494E+09 | 0.239487E+09 | 0.00 | 42386944.54 | 77122.20 | 0.00 | 0.138840E+11 | 0.00 | 4.16 |
July | 0.173383E+09 | 0.285021E+09 | 0.00 | 42930815.61 | 0.00 | 0.00 | 0.127046E+11 | 0.00 | 4.19 |
August | 0.345921E+09 | 0.181723E+09 | 0.00 | 50253216.21 | 0.00 | 0.00 | 0.149886E+11 | 0.00 | 4.44 |
September | 0.906975E+09 | 26347866.30 | 0.00 | 53397209.81 | 0.00 | 0.00 | 0.182138E+11 | 0.00 | 4.54 |
October | 0.679286E+10 | 0.00 | 0.00 | 47243586.24 | 0.00 | 0.513895E+09 | 0.232534E+11 | 0.00 | 4.15 |
November | 0.708841E+10 | 0.00 | 0.00 | 51583849.33 | 0.00 | 21126903.95 | 0.241221E+11 | 0.00 | 4.02 |
December | 0.117007E+11 | 0.00 | 0.00 | 36190460.03 | 0.00 | 0.680600E+09 | 0.197828E+11 | 0.00 | 3.85 |
Annual Sum or Average | 0.674049E+11 | 0.733358E+09 | 0.00 | 0.516036E+09 | 77122.20 | 0.164530E+10 | 0.228880E+12 | 0.00 | 4.06 |
Minimum of Months | 0.173383E+09 | 0.00 | 0.00 | 24405038.57 | 0.00 | 0.00 | 0.127046E+11 | 0.00 | 3.65 |
Maximum of Months | 0.117007E+11 | 0.285021E+09 | 0.00 | 53397209.81 | 77122.20 | 0.680600E+09 | 0.250805E+11 | 0.00 | 4.54 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235089E+11 | 0.00 | 0.00 | 0.126230E+09 | 0.00 | 0.00 | 0.691900E+11 | 0.00 | 1.60 |
February | 0.276375E+11 | 0.00 | 0.00 | 0.101599E+09 | 0.00 | 0.00 | 0.552536E+11 | 0.00 | 1.60 |
March | 0.274143E+11 | 0.00 | 0.00 | 0.108495E+09 | 0.00 | 0.00 | 0.617277E+11 | 0.00 | 1.65 |
April | 0.312238E+11 | 0.00 | 0.00 | 93848090.50 | 0.00 | 0.00 | 0.532099E+11 | 0.00 | 1.62 |
May | 0.106788E+11 | 1936391.15 | 0.00 | 0.121676E+09 | 0.00 | 0.00 | 0.688104E+11 | 0.00 | 1.77 |
June | 0.626193E+09 | 0.625058E+09 | 0.00 | 0.150483E+09 | 1179452.47 | 0.00 | 0.496349E+11 | 0.00 | 2.00 |
July | 0.288494E+09 | 0.739981E+09 | 0.00 | 0.152155E+09 | 10668341.64 | 0.00 | 0.452524E+11 | 0.00 | 2.00 |
August | 0.472080E+09 | 0.441711E+09 | 0.00 | 0.163853E+09 | 55301.14 | 0.00 | 0.521860E+11 | 0.00 | 2.04 |
September | 0.139226E+10 | 59666033.00 | 0.00 | 0.171215E+09 | 0.00 | 0.00 | 0.626780E+11 | 0.00 | 2.01 |
October | 0.175180E+11 | 0.00 | 0.00 | 0.152806E+09 | 0.00 | 0.00 | 0.744622E+11 | 0.00 | 1.71 |
November | 0.205202E+11 | 0.00 | 0.00 | 0.139525E+09 | 0.00 | 0.00 | 0.687883E+11 | 0.00 | 1.60 |
December | 0.395131E+11 | 0.00 | 0.00 | 90762166.44 | 0.00 | 0.00 | 0.533993E+11 | 0.00 | 1.56 |
Annual Sum or Average | 0.200794E+12 | 0.186835E+10 | 0.00 | 0.157265E+10 | 11903095.25 | 0.00 | 0.714593E+12 | 0.00 | 1.76 |
Minimum of Months | 0.288494E+09 | 0.00 | 0.00 | 90762166.44 | 0.00 | 0.00 | 0.452524E+11 | 0.00 | 1.56 |
Maximum of Months | 0.395131E+11 | 0.739981E+09 | 0.00 | 0.171215E+09 | 10668341.64 | 0.00 | 0.744622E+11 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286258E+09 | 0.00 | 0.00 | 5454030.99 | 0.00 | 0.867273E+09 | 0.416263E+09 | 0.00 | 0.47 |
February | 0.231252E+09 | 0.00 | 0.00 | 6263443.18 | 0.00 | 0.789237E+09 | 0.391684E+09 | 0.00 | 0.47 |
March | 0.267567E+09 | 0.00 | 0.00 | 7928520.09 | 0.00 | 0.642917E+09 | 0.545081E+09 | 0.00 | 0.47 |
April | 0.298961E+09 | 0.00 | 0.00 | 6044650.80 | 0.00 | 0.580675E+09 | 0.489733E+09 | 0.00 | 0.47 |
May | 0.312758E+09 | 677780.86 | 0.00 | 10656362.87 | 58892.09 | 98039685.61 | 0.831630E+09 | 0.00 | 0.47 |
June | 0.149958E+09 | 43570048.96 | 3732.57 | 11492644.31 | 5324578.35 | 632280.19 | 0.377408E+09 | 5207.54 | 0.47 |
July | 0.145663E+09 | 76907690.97 | 10856.42 | 8380934.64 | 11443749.98 | 376002.46 | 0.274936E+09 | 6671.28 | 0.47 |
August | 0.178427E+09 | 62970248.48 | 9557.01 | 11743829.15 | 6211912.52 | 616583.18 | 0.346740E+09 | 4410.13 | 0.47 |
September | 0.235160E+09 | 7216770.10 | 0.00 | 13511130.01 | 612352.04 | 35503698.57 | 0.577796E+09 | 1106.06 | 0.47 |
October | 0.238101E+09 | 0.00 | 0.00 | 10252140.64 | 0.00 | 0.461639E+09 | 0.756955E+09 | 0.00 | 0.47 |
November | 0.253217E+09 | 0.00 | 0.00 | 6648769.66 | 0.00 | 0.698069E+09 | 0.514728E+09 | 0.00 | 0.47 |
December | 0.276418E+09 | 0.00 | 0.00 | 3040660.54 | 0.00 | 0.106433E+10 | 0.269678E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.287374E+10 | 0.191343E+09 | 24146.00 | 0.101417E+09 | 23651484.98 | 0.523930E+10 | 0.579263E+10 | 17395.02 | 0.47 |
Minimum of Months | 0.145663E+09 | 0.00 | 0.00 | 3040660.54 | 0.00 | 376002.46 | 0.269678E+09 | 0.00 | 0.47 |
Maximum of Months | 0.312758E+09 | 76907690.97 | 10856.42 | 13511130.01 | 11443749.98 | 0.106433E+10 | 0.831630E+09 | 6671.28 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.351747E+09 | 0.00 | 0.00 | 1121771.31 | 0.00 | 0.112391E+10 | 98281451.20 | 0.00 | 0.47 |
February | 0.282849E+09 | 0.00 | 0.00 | 1667325.02 | 0.00 | 0.100065E+10 | 0.133105E+09 | 0.00 | 0.47 |
March | 0.339198E+09 | 0.00 | 0.00 | 4169291.58 | 0.00 | 0.756195E+09 | 0.363761E+09 | 0.00 | 0.47 |
April | 0.349349E+09 | 0.00 | 0.00 | 4011732.89 | 0.00 | 0.658678E+09 | 0.363214E+09 | 0.00 | 0.47 |
May | 0.340611E+09 | 677701.45 | 0.00 | 9595930.51 | 58885.19 | 0.113574E+09 | 0.789156E+09 | 0.00 | 0.47 |
June | 0.151643E+09 | 43309651.22 | 4043.30 | 11179951.57 | 5579247.36 | 635890.26 | 0.375969E+09 | 4895.77 | 0.47 |
July | 0.146342E+09 | 76162980.11 | 10147.92 | 8114474.14 | 12177790.82 | 267875.01 | 0.274582E+09 | 7696.09 | 0.47 |
August | 0.183686E+09 | 62478643.77 | 11596.31 | 10281375.90 | 6691789.20 | 680819.67 | 0.342817E+09 | 5991.54 | 0.47 |
September | 0.256845E+09 | 7139745.08 | 0.00 | 10424763.05 | 688459.77 | 43625802.38 | 0.550974E+09 | 1105.93 | 0.47 |
October | 0.346192E+09 | 0.00 | 0.00 | 5210488.02 | 0.00 | 0.615554E+09 | 0.499818E+09 | 0.00 | 0.47 |
November | 0.336006E+09 | 0.00 | 0.00 | 1602248.89 | 0.00 | 0.966500E+09 | 0.168381E+09 | 0.00 | 0.47 |
December | 0.282976E+09 | 0.00 | 0.00 | 543959.11 | 0.00 | 0.127073E+10 | 59020518.99 | 0.00 | 0.47 |
Annual Sum or Average | 0.336744E+10 | 0.189769E+09 | 25787.53 | 67923312.01 | 25196172.34 | 0.655101E+10 | 0.401908E+10 | 19689.33 | 0.47 |
Minimum of Months | 0.146342E+09 | 0.00 | 0.00 | 543959.11 | 0.00 | 267875.01 | 59020518.99 | 0.00 | 0.47 |
Maximum of Months | 0.351747E+09 | 76162980.11 | 11596.31 | 11179951.57 | 12177790.82 | 0.127073E+10 | 0.789156E+09 | 7696.09 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112004E+11 | 0.00 | 0.00 | 0.137144E+09 | 0.00 | 0.601213E+09 | 0.942018E+10 | 0.00 | 0.54 |
February | 0.900967E+10 | 0.00 | 0.00 | 0.112963E+09 | 0.00 | 0.243562E+10 | 0.767448E+10 | 0.00 | 0.54 |
March | 0.991824E+10 | 0.00 | 0.00 | 77253707.39 | 0.00 | 0.214983E+10 | 0.769834E+10 | 0.00 | 0.54 |
April | 0.142897E+11 | 0.00 | 0.00 | 22206084.82 | 0.00 | 0.823430E+09 | 0.351407E+10 | 0.00 | 0.54 |
May | 0.834151E+10 | 9988624.57 | 0.00 | 53544160.63 | 0.00 | 0.00 | 0.859564E+10 | 0.00 | 0.54 |
June | 0.108937E+10 | 0.663089E+09 | 0.00 | 71478228.87 | 0.00 | 0.00 | 0.615417E+10 | 0.00 | 0.54 |
July | 0.831468E+09 | 0.119820E+10 | 0.00 | 60921437.79 | 0.00 | 0.00 | 0.492929E+10 | 0.00 | 0.54 |
August | 0.650141E+09 | 0.937792E+09 | 0.00 | 94711069.12 | 445134.31 | 0.00 | 0.654354E+10 | 0.00 | 0.54 |
September | 0.169170E+10 | 0.106171E+09 | 0.00 | 0.123806E+09 | 0.00 | 0.00 | 0.987205E+10 | 0.00 | 0.53 |
October | 0.839403E+10 | 0.00 | 0.00 | 0.117769E+09 | 0.00 | 0.132278E+10 | 0.100559E+11 | 0.00 | 0.54 |
November | 0.975729E+10 | 0.00 | 0.00 | 0.128464E+09 | 0.00 | 0.100358E+10 | 0.907864E+10 | 0.00 | 0.54 |
December | 0.128804E+11 | 0.00 | 0.00 | 75613623.46 | 0.00 | 0.299140E+10 | 0.592968E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.880539E+11 | 0.291524E+10 | 0.00 | 0.107587E+10 | 445134.31 | 0.113279E+11 | 0.894660E+11 | 0.00 | 0.54 |
Minimum of Months | 0.650141E+09 | 0.00 | 0.00 | 22206084.82 | 0.00 | 0.00 | 0.351407E+10 | 0.00 | 0.53 |
Maximum of Months | 0.142897E+11 | 0.119820E+10 | 0.00 | 0.137144E+09 | 445134.31 | 0.299140E+10 | 0.100559E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.566121E+10 | 0.00 | 0.00 | 12494622.64 | 0.00 | 0.108834E+11 | 0.480771E+10 | 0.00 | 0.54 |
February | 0.524400E+10 | 0.00 | 0.00 | 10230882.19 | 0.00 | 0.104682E+11 | 0.351556E+10 | 0.00 | 0.54 |
March | 0.582428E+10 | 0.00 | 0.00 | 31701857.61 | 0.00 | 0.619231E+10 | 0.780080E+10 | 0.00 | 0.54 |
April | 0.558888E+10 | 0.00 | 0.00 | 51272060.13 | 0.00 | 0.358665E+10 | 0.942768E+10 | 0.00 | 0.54 |
May | 0.563154E+10 | 7041196.59 | 7970.86 | 0.109429E+09 | 2932809.91 | 53514111.62 | 0.112009E+11 | 9378.59 | 0.53 |
June | 0.217326E+10 | 0.486610E+09 | 234756.75 | 0.106910E+09 | 0.176369E+09 | 5222493.35 | 0.503163E+10 | 56680.34 | 0.53 |
July | 0.205354E+10 | 0.857238E+09 | 392116.42 | 81999270.46 | 0.340850E+09 | 2218740.98 | 0.368551E+10 | 51518.31 | 0.53 |
August | 0.284866E+10 | 0.748484E+09 | 570538.48 | 91774541.31 | 0.189328E+09 | 6154534.73 | 0.434380E+10 | 111295.14 | 0.53 |
September | 0.381790E+10 | 73140245.80 | 482539.18 | 95659561.29 | 32478618.04 | 16192199.43 | 0.776099E+10 | 98500.86 | 0.53 |
October | 0.604554E+10 | 0.00 | 0.00 | 46494647.24 | 0.00 | 0.308059E+10 | 0.107233E+11 | 0.00 | 0.53 |
November | 0.556641E+10 | 0.00 | 0.00 | 18727713.74 | 0.00 | 0.835217E+10 | 0.603613E+10 | 0.00 | 0.54 |
December | 0.507331E+10 | 0.00 | 0.00 | 7969008.94 | 0.00 | 0.131474E+11 | 0.365437E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.555285E+11 | 0.217251E+10 | 1687921.69 | 0.664664E+09 | 0.741958E+09 | 0.557941E+11 | 0.779884E+11 | 327373.24 | 0.53 |
Minimum of Months | 0.205354E+10 | 0.00 | 0.00 | 7969008.94 | 0.00 | 2218740.98 | 0.351556E+10 | 0.00 | 0.53 |
Maximum of Months | 0.604554E+10 | 0.857238E+09 | 570538.48 | 0.109429E+09 | 0.340850E+09 | 0.131474E+11 | 0.112009E+11 | 111295.14 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293097E+09 | 0.00 | 0.00 | 5272831.40 | 0.00 | 0.889867E+09 | 0.387012E+09 | 0.00 | 0.47 |
February | 0.212409E+09 | 0.00 | 0.00 | 7580613.92 | 0.00 | 0.780083E+09 | 0.418364E+09 | 0.00 | 0.47 |
March | 0.234855E+09 | 0.00 | 0.00 | 9337595.47 | 0.00 | 0.639467E+09 | 0.579835E+09 | 0.00 | 0.47 |
April | 0.261356E+09 | 0.00 | 0.00 | 8376205.73 | 0.00 | 0.575777E+09 | 0.529905E+09 | 0.00 | 0.47 |
May | 0.245086E+09 | 652224.88 | 759.60 | 13203520.34 | 83595.56 | 89331586.97 | 0.905463E+09 | 92.92 | 0.47 |
June | 0.137619E+09 | 44380747.06 | 0.00 | 14229742.89 | 4521511.46 | 343674.00 | 0.387298E+09 | 1308.91 | 0.47 |
July | 0.140164E+09 | 78172844.08 | 5460.88 | 10170795.07 | 10185760.47 | 216413.50 | 0.278804E+09 | 4903.22 | 0.47 |
August | 0.163264E+09 | 63255662.29 | 0.00 | 15418373.80 | 5940465.86 | 175411.41 | 0.358670E+09 | 0.00 | 0.47 |
September | 0.212539E+09 | 7191853.23 | 0.00 | 16115389.17 | 636946.62 | 34742295.08 | 0.598574E+09 | 1428.35 | 0.47 |
October | 0.194772E+09 | 0.00 | 0.00 | 11431564.79 | 0.00 | 0.491210E+09 | 0.769532E+09 | 0.00 | 0.47 |
November | 0.246227E+09 | 0.00 | 0.00 | 7144858.97 | 0.00 | 0.710752E+09 | 0.508538E+09 | 0.00 | 0.47 |
December | 0.278824E+09 | 0.00 | 0.00 | 3757552.78 | 0.00 | 0.105725E+10 | 0.273636E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.262021E+10 | 0.193653E+09 | 6220.48 | 0.122039E+09 | 21368279.96 | 0.526921E+10 | 0.599563E+10 | 7733.40 | 0.47 |
Minimum of Months | 0.137619E+09 | 0.00 | 0.00 | 3757552.78 | 0.00 | 175411.41 | 0.273636E+09 | 0.00 | 0.47 |
Maximum of Months | 0.293097E+09 | 78172844.08 | 5460.88 | 16115389.17 | 10185760.47 | 0.105725E+10 | 0.905463E+09 | 4903.22 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371580E+09 | 0.00 | 0.00 | 1087595.79 | 0.00 | 0.108519E+10 | 0.117208E+09 | 0.00 | 0.47 |
February | 0.287016E+09 | 0.00 | 0.00 | 2630584.81 | 0.00 | 0.961269E+09 | 0.167355E+09 | 0.00 | 0.47 |
March | 0.322390E+09 | 0.00 | 0.00 | 5039423.92 | 0.00 | 0.726262E+09 | 0.409631E+09 | 0.00 | 0.47 |
April | 0.308470E+09 | 0.00 | 0.00 | 6117745.58 | 0.00 | 0.644775E+09 | 0.415891E+09 | 0.00 | 0.47 |
May | 0.283525E+09 | 653000.88 | 0.00 | 11928392.34 | 83585.76 | 0.103665E+09 | 0.853819E+09 | 0.00 | 0.47 |
June | 0.137615E+09 | 44371269.73 | 0.00 | 13892178.51 | 4525259.17 | 372469.77 | 0.387548E+09 | 1308.76 | 0.47 |
July | 0.140181E+09 | 78059471.31 | 5508.99 | 9905504.26 | 10288780.73 | 216388.15 | 0.279003E+09 | 4853.90 | 0.47 |
August | 0.164254E+09 | 63199438.93 | 0.00 | 13804575.86 | 5988581.88 | 373506.42 | 0.359032E+09 | 0.00 | 0.47 |
September | 0.219740E+09 | 7153500.31 | 392.07 | 12698965.28 | 674382.28 | 46248010.84 | 0.583182E+09 | 1036.11 | 0.47 |
October | 0.346083E+09 | 0.00 | 0.00 | 5639746.44 | 0.00 | 0.634228E+09 | 0.480824E+09 | 0.00 | 0.47 |
November | 0.349363E+09 | 0.00 | 0.00 | 2105240.56 | 0.00 | 0.935607E+09 | 0.185414E+09 | 0.00 | 0.47 |
December | 0.292788E+09 | 0.00 | 0.00 | 736822.63 | 0.00 | 0.124829E+10 | 71457625.97 | 0.00 | 0.47 |
Annual Sum or Average | 0.322300E+10 | 0.193437E+09 | 5901.07 | 85586775.98 | 21560589.83 | 0.638650E+10 | 0.431037E+10 | 7198.76 | 0.47 |
Minimum of Months | 0.137615E+09 | 0.00 | 0.00 | 736822.63 | 0.00 | 216388.15 | 71457625.97 | 0.00 | 0.47 |
Maximum of Months | 0.371580E+09 | 78059471.31 | 5508.99 | 13892178.51 | 10288780.73 | 0.124829E+10 | 0.853819E+09 | 4853.90 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124688E+10 | 0.00 | 0.00 | 0.53 |
February | 0.224001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271613E+10 | 0.00 | 0.00 | 0.53 |
March | 0.261231E+11 | 0.00 | 0.00 | 41847.36 | 0.00 | 0.208416E+09 | 0.216979E+09 | 0.00 | 0.54 |
April | 0.252361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331107E+09 | 0.00 | 0.00 | 0.54 |
May | 0.225939E+11 | 0.00 | 0.00 | 2618.93 | 632621.60 | 0.00 | 17557655.20 | 0.00 | 0.56 |
June | 0.462411E+10 | 0.216251E+09 | 0.00 | 22978844.47 | 2278777.90 | 0.00 | 0.819990E+10 | 0.00 | 0.60 |
July | 0.253993E+10 | 0.238121E+09 | 0.00 | 28210667.01 | 20734704.07 | 0.00 | 0.903066E+10 | 0.00 | 0.60 |
August | 0.386368E+10 | 0.144177E+09 | 0.00 | 26664115.54 | 731011.69 | 0.00 | 0.968084E+10 | 0.00 | 0.60 |
September | 0.848132E+10 | 18959496.02 | 0.00 | 19265106.91 | 0.00 | 0.00 | 0.809477E+10 | 0.00 | 0.59 |
October | 0.248929E+11 | 0.00 | 0.00 | 147513.98 | 0.00 | 0.995990E+09 | 0.299176E+09 | 0.00 | 0.53 |
November | 0.251630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112144E+10 | 0.00 | 0.00 | 0.52 |
December | 0.233149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539561E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.215899E+12 | 0.617509E+09 | 0.00 | 97310714.21 | 24377115.26 | 0.120156E+11 | 0.355399E+11 | 0.00 | 0.56 |
Minimum of Months | 0.253993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.266654E+11 | 0.238121E+09 | 0.00 | 28210667.01 | 20734704.07 | 0.539561E+10 | 0.968084E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71633633.42 | 0.00 | 0.00 | 1222677.37 | 0.00 | 0.245667E+09 | 75288843.44 | 0.00 | 0.47 |
February | 55514819.44 | 0.00 | 0.00 | 1439765.83 | 0.00 | 0.222127E+09 | 75527732.08 | 0.00 | 0.47 |
March | 62550378.25 | 0.00 | 0.00 | 1937023.75 | 0.00 | 0.185000E+09 | 0.116386E+09 | 0.00 | 0.47 |
April | 67175516.06 | 0.00 | 0.00 | 1475601.99 | 0.00 | 0.174115E+09 | 0.101087E+09 | 0.00 | 0.47 |
May | 76477960.08 | 169445.22 | 0.00 | 2520960.79 | 14723.02 | 48982275.12 | 0.185290E+09 | 0.00 | 0.47 |
June | 37531443.45 | 10940065.88 | 920.86 | 2793779.91 | 1283805.43 | 155221.99 | 94392344.85 | 1099.68 | 0.47 |
July | 36122526.07 | 19272933.41 | 1499.87 | 1990578.86 | 2815643.32 | 95496.47 | 69130412.60 | 2165.57 | 0.47 |
August | 44829070.72 | 15762710.48 | 858.39 | 2868532.30 | 1533964.82 | 172024.29 | 86512287.82 | 1498.34 | 0.47 |
September | 59320268.50 | 1805325.52 | 0.00 | 3177417.89 | 151955.02 | 14674387.04 | 0.138321E+09 | 276.51 | 0.47 |
October | 59218505.58 | 0.00 | 0.00 | 2276785.72 | 0.00 | 0.153899E+09 | 0.151342E+09 | 0.00 | 0.47 |
November | 60031765.17 | 0.00 | 0.00 | 1446154.83 | 0.00 | 0.209692E+09 | 96995349.38 | 0.00 | 0.47 |
December | 62453198.68 | 0.00 | 0.00 | 670781.08 | 0.00 | 0.288586E+09 | 51655639.26 | 0.00 | 0.47 |
Annual Sum or Average | 0.692859E+09 | 47950480.50 | 3279.12 | 23820060.32 | 5800091.61 | 0.154317E+10 | 0.124193E+10 | 5040.11 | 0.47 |
Minimum of Months | 36122526.07 | 0.00 | 0.00 | 670781.08 | 0.00 | 95496.47 | 51655639.26 | 0.00 | 0.47 |
Maximum of Months | 76477960.08 | 19272933.41 | 1499.87 | 3177417.89 | 2815643.32 | 0.288586E+09 | 0.185290E+09 | 2165.57 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76270345.75 | 0.00 | 0.00 | 224156.34 | 0.00 | 0.302301E+09 | 14970387.25 | 0.00 | 0.47 |
February | 64533677.06 | 0.00 | 0.00 | 371048.99 | 0.00 | 0.268106E+09 | 21557474.31 | 0.00 | 0.47 |
March | 77809217.23 | 0.00 | 0.00 | 997838.36 | 0.00 | 0.212744E+09 | 74279157.60 | 0.00 | 0.47 |
April | 79266323.51 | 0.00 | 0.00 | 975259.87 | 0.00 | 0.189786E+09 | 73785850.79 | 0.00 | 0.47 |
May | 83977726.13 | 169425.36 | 0.00 | 2234547.72 | 14721.30 | 53062280.80 | 0.173960E+09 | 0.00 | 0.47 |
June | 37788711.57 | 10886538.01 | 836.59 | 2713213.39 | 1335686.64 | 154537.52 | 94200525.39 | 1398.17 | 0.47 |
July | 36255473.34 | 19075300.55 | 1516.20 | 1919254.18 | 3010688.17 | 96273.00 | 69055437.14 | 2148.81 | 0.47 |
August | 45728304.59 | 15664588.48 | 821.44 | 2485985.83 | 1630060.26 | 451176.71 | 85700703.20 | 1535.02 | 0.47 |
September | 64210425.20 | 1782553.86 | 0.00 | 2373090.33 | 174497.36 | 17422344.86 | 0.131462E+09 | 276.48 | 0.47 |
October | 85552787.59 | 0.00 | 0.00 | 1125034.84 | 0.00 | 0.192880E+09 | 87135570.96 | 0.00 | 0.47 |
November | 76875934.03 | 0.00 | 0.00 | 355529.05 | 0.00 | 0.263611E+09 | 27279483.58 | 0.00 | 0.47 |
December | 57965686.93 | 0.00 | 0.00 | 121091.74 | 0.00 | 0.337533E+09 | 7698664.70 | 0.00 | 0.47 |
Annual Sum or Average | 0.786235E+09 | 47578406.26 | 3174.24 | 15896050.63 | 6165653.72 | 0.183815E+10 | 0.861085E+09 | 5358.48 | 0.47 |
Minimum of Months | 36255473.34 | 0.00 | 0.00 | 121091.74 | 0.00 | 96273.00 | 7698664.70 | 0.00 | 0.47 |
Maximum of Months | 85552787.59 | 19075300.55 | 1516.20 | 2713213.39 | 3010688.17 | 0.337533E+09 | 0.173960E+09 | 2148.81 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266281E+09 | 0.00 | 0.00 | 30815640.23 | 0.00 | 0.922347E+09 | 0.131060E+10 | 0.00 | 0.54 |
February | 0.209561E+09 | 0.00 | 0.00 | 26614298.18 | 0.00 | 0.963940E+09 | 0.107807E+10 | 0.00 | 0.54 |
March | 0.322417E+09 | 0.00 | 0.00 | 19440104.27 | 0.00 | 0.847954E+09 | 0.116074E+10 | 0.00 | 0.54 |
April | 0.432653E+09 | 0.00 | 0.00 | 10828448.63 | 0.00 | 0.826802E+09 | 0.938800E+09 | 0.00 | 0.54 |
May | 0.469141E+09 | 1048922.20 | 0.00 | 14536042.40 | 134264.69 | 0.160873E+09 | 0.136806E+10 | 0.00 | 0.54 |
June | 0.242601E+09 | 69243902.44 | 18099.35 | 14592447.43 | 9274536.41 | 1470838.23 | 0.607824E+09 | 8573.73 | 0.54 |
July | 0.233927E+09 | 0.123560E+09 | 15927.17 | 11178283.01 | 18344436.22 | 663441.28 | 0.443830E+09 | 11052.52 | 0.53 |
August | 0.287443E+09 | 0.101112E+09 | 22346.29 | 17600782.96 | 9987195.76 | 882575.44 | 0.557409E+09 | 16350.61 | 0.53 |
September | 0.360876E+09 | 11565358.37 | 0.00 | 23714538.41 | 1010630.83 | 48707894.78 | 0.951132E+09 | 315.21 | 0.53 |
October | 0.314276E+09 | 0.00 | 0.00 | 25014820.36 | 0.00 | 0.600542E+09 | 0.141626E+10 | 0.00 | 0.54 |
November | 0.251275E+09 | 0.00 | 0.00 | 31128779.55 | 0.00 | 0.725188E+09 | 0.135768E+10 | 0.00 | 0.54 |
December | 0.336013E+09 | 0.00 | 0.00 | 21068599.90 | 0.00 | 0.125106E+10 | 0.983281E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.372646E+10 | 0.306530E+09 | 56372.81 | 0.246533E+09 | 38751063.91 | 0.635043E+10 | 0.121737E+11 | 36292.07 | 0.54 |
Minimum of Months | 0.209561E+09 | 0.00 | 0.00 | 10828448.63 | 0.00 | 663441.28 | 0.443830E+09 | 0.00 | 0.53 |
Maximum of Months | 0.469141E+09 | 0.123560E+09 | 22346.29 | 31128779.55 | 18344436.22 | 0.125106E+10 | 0.141626E+10 | 16350.61 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242326E+10 | 0.00 | 0.00 | 94698863.59 | 0.00 | 0.00 | 0.462783E+11 | 0.00 | 4.28 |
February | 0.238584E+10 | 0.00 | 0.00 | 80275240.60 | 0.00 | 0.00 | 0.409846E+11 | 0.00 | 4.26 |
March | 0.103442E+10 | 0.00 | 0.00 | 0.107042E+09 | 0.00 | 0.00 | 0.483681E+11 | 0.00 | 4.62 |
April | 0.703649E+09 | 0.00 | 0.00 | 0.124153E+09 | 0.00 | 0.00 | 0.481294E+11 | 0.00 | 4.75 |
May | 0.123859E+09 | 1237015.25 | 0.00 | 0.117542E+09 | 0.00 | 0.00 | 0.477142E+11 | 0.00 | 5.41 |
June | 1773411.74 | 0.384533E+09 | 0.00 | 0.104621E+09 | 0.00 | 0.00 | 0.296110E+11 | 0.00 | 6.05 |
July | 0.00 | 0.454305E+09 | 0.00 | 0.100541E+09 | 0.00 | 0.00 | 0.266474E+11 | 0.00 | 6.03 |
August | 0.00 | 0.251039E+09 | 0.00 | 0.106292E+09 | 0.00 | 0.00 | 0.303087E+11 | 0.00 | 5.98 |
September | 51320992.29 | 31040318.67 | 0.00 | 0.103714E+09 | 0.00 | 0.00 | 0.360425E+11 | 0.00 | 5.70 |
October | 0.132874E+10 | 0.00 | 0.00 | 0.115184E+09 | 0.00 | 0.00 | 0.484442E+11 | 0.00 | 4.64 |
November | 0.187716E+10 | 0.00 | 0.00 | 0.102257E+09 | 0.00 | 0.00 | 0.452533E+11 | 0.00 | 4.29 |
December | 0.512906E+10 | 0.00 | 0.00 | 84050129.93 | 0.00 | 0.00 | 0.432263E+11 | 0.00 | 4.13 |
Annual Sum or Average | 0.150591E+11 | 0.112215E+10 | 0.00 | 0.124037E+10 | 0.00 | 0.00 | 0.491008E+12 | 0.00 | 5.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 80275240.60 | 0.00 | 0.00 | 0.266474E+11 | 0.00 | 4.13 |
Maximum of Months | 0.512906E+10 | 0.454305E+09 | 0.00 | 0.124153E+09 | 0.00 | 0.00 | 0.484442E+11 | 0.00 | 6.05 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.952276E+09 | 0.00 | 0.00 | 0.119256E+09 | 0.00 | 0.00 | 0.529399E+11 | 0.00 | 4.73 |
February | 0.720267E+09 | 0.00 | 0.00 | 0.101267E+09 | 0.00 | 0.00 | 0.472391E+11 | 0.00 | 4.71 |
March | 0.248549E+09 | 0.00 | 0.00 | 0.130187E+09 | 0.00 | 0.00 | 0.542334E+11 | 0.00 | 5.10 |
April | 0.164902E+09 | 0.00 | 0.00 | 0.149749E+09 | 0.00 | 0.00 | 0.537966E+11 | 0.00 | 5.26 |
May | 61565708.31 | 1349844.50 | 0.00 | 0.130080E+09 | 0.00 | 0.00 | 0.518903E+11 | 0.00 | 5.90 |
June | 952218.06 | 0.412727E+09 | 0.00 | 0.111634E+09 | 0.00 | 0.00 | 0.313471E+11 | 0.00 | 6.45 |
July | 0.00 | 0.489433E+09 | 0.00 | 0.107139E+09 | 0.00 | 0.00 | 0.281613E+11 | 0.00 | 6.42 |
August | 0.00 | 0.269251E+09 | 0.00 | 0.113595E+09 | 0.00 | 0.00 | 0.321306E+11 | 0.00 | 6.37 |
September | 27977988.43 | 33435009.29 | 0.00 | 0.112184E+09 | 0.00 | 0.00 | 0.385479E+11 | 0.00 | 6.11 |
October | 0.291158E+09 | 0.00 | 0.00 | 0.133438E+09 | 0.00 | 0.00 | 0.540471E+11 | 0.00 | 5.07 |
November | 0.607006E+09 | 0.00 | 0.00 | 0.125093E+09 | 0.00 | 0.00 | 0.514355E+11 | 0.00 | 4.73 |
December | 0.303458E+10 | 0.00 | 0.00 | 0.107515E+09 | 0.00 | 0.00 | 0.502975E+11 | 0.00 | 4.56 |
Annual Sum or Average | 0.610924E+10 | 0.120620E+10 | 0.00 | 0.144114E+10 | 0.00 | 0.00 | 0.546066E+12 | 0.00 | 5.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101267E+09 | 0.00 | 0.00 | 0.281613E+11 | 0.00 | 4.56 |
Maximum of Months | 0.303458E+10 | 0.489433E+09 | 0.00 | 0.149749E+09 | 0.00 | 0.00 | 0.542334E+11 | 0.00 | 6.45 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14483599.62 | 0.00 | 0.00 | 0.213680E+09 | 0.00 | 0.00 | 0.734356E+11 | 0.00 | 21.15 |
February | 10430693.81 | 0.00 | 0.00 | 0.190584E+09 | 0.00 | 0.00 | 0.660862E+11 | 0.00 | 21.13 |
March | 26594491.24 | 0.00 | 0.00 | 0.208295E+09 | 0.00 | 0.00 | 0.711277E+11 | 0.00 | 22.27 |
April | 39140405.42 | 0.00 | 0.00 | 0.223748E+09 | 0.00 | 0.00 | 0.684905E+11 | 0.00 | 22.55 |
May | 30054339.45 | 2167493.15 | 0.00 | 0.167860E+09 | 0.00 | 0.00 | 0.610001E+11 | 0.00 | 24.50 |
June | 934168.24 | 0.647834E+09 | 0.00 | 0.142357E+09 | 0.00 | 0.00 | 0.308673E+11 | 0.00 | 24.90 |
July | 0.00 | 0.797944E+09 | 0.00 | 0.135045E+09 | 0.00 | 0.00 | 0.271005E+11 | 0.00 | 24.69 |
August | 0.00 | 0.422632E+09 | 0.00 | 0.150366E+09 | 0.00 | 0.00 | 0.333845E+11 | 0.00 | 24.91 |
September | 13831491.65 | 55381026.10 | 0.00 | 0.152538E+09 | 0.00 | 0.00 | 0.420765E+11 | 0.00 | 24.76 |
October | 37360469.63 | 0.00 | 0.00 | 0.194429E+09 | 0.00 | 0.00 | 0.696876E+11 | 0.00 | 22.09 |
November | 42138636.06 | 0.00 | 0.00 | 0.211853E+09 | 0.00 | 0.00 | 0.694333E+11 | 0.00 | 20.94 |
December | 30862526.27 | 0.00 | 0.00 | 0.197136E+09 | 0.00 | 0.00 | 0.736349E+11 | 0.00 | 20.68 |
Annual Sum or Average | 0.245831E+09 | 0.192596E+10 | 0.00 | 0.218789E+10 | 0.00 | 0.00 | 0.686325E+12 | 0.00 | 22.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135045E+09 | 0.00 | 0.00 | 0.271005E+11 | 0.00 | 20.68 |
Maximum of Months | 42138636.06 | 0.797944E+09 | 0.00 | 0.223748E+09 | 0.00 | 0.00 | 0.736349E+11 | 0.00 | 24.91 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181190E+10 | 0.00 | 0.00 | 1.03 |
February | 0.102771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277834E+10 | 0.00 | 0.00 | 1.04 |
March | 0.126008E+11 | 0.00 | 0.00 | 828178.08 | 0.00 | 0.847457E+09 | 0.358638E+09 | 0.00 | 1.06 |
April | 0.127350E+11 | 0.00 | 0.00 | 6428.34 | 0.00 | 0.526115E+09 | 28725591.58 | 0.00 | 1.06 |
May | 0.113327E+11 | 331912.49 | 0.00 | 785899.54 | 0.00 | 0.00 | 0.420808E+09 | 0.00 | 1.10 |
June | 0.304614E+10 | 0.150365E+09 | 0.00 | 14006023.24 | 0.00 | 0.00 | 0.344449E+10 | 0.00 | 1.22 |
July | 0.237875E+10 | 0.168083E+09 | 0.00 | 14157638.83 | 49768.23 | 0.00 | 0.343429E+10 | 0.00 | 1.21 |
August | 0.330852E+10 | 99593794.80 | 0.00 | 14782658.04 | 0.00 | 0.00 | 0.356311E+10 | 0.00 | 1.22 |
September | 0.576320E+10 | 12630376.65 | 0.00 | 9646016.92 | 0.00 | 0.00 | 0.269959E+10 | 0.00 | 1.16 |
October | 0.119159E+11 | 0.00 | 0.00 | 1241003.75 | 0.00 | 0.104084E+10 | 0.660249E+09 | 0.00 | 1.04 |
November | 0.124086E+11 | 0.00 | 0.00 | 50092.47 | 0.00 | 0.117661E+10 | 77387795.99 | 0.00 | 1.02 |
December | 0.109657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395421E+10 | 0.00 | 0.00 | 1.03 |
Annual Sum or Average | 0.109429E+12 | 0.431004E+09 | 0.00 | 55503939.21 | 49768.23 | 0.121355E+11 | 0.146873E+11 | 0.00 | 1.10 |
Minimum of Months | 0.237875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
Maximum of Months | 0.127350E+11 | 0.168083E+09 | 0.00 | 14782658.04 | 49768.23 | 0.395421E+10 | 0.356311E+10 | 0.00 | 1.22 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:42:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.232544E+12 | 0.178290E+11 | 0.211312E+12 | 0.930860E+12 | 0.127748E+12 |
February | 0.317862E+12 | 0.168980E+11 | 0.198458E+12 | 0.874428E+12 | 0.110121E+12 |
March | 0.423683E+12 | 0.148732E+11 | 0.175451E+12 | 0.791500E+12 | 0.136517E+12 |
April | 0.474673E+12 | 0.134768E+11 | 0.159160E+12 | 0.719944E+12 | 0.114457E+12 |
May | 0.532685E+12 | 0.887828E+10 | 0.927530E+11 | 0.491729E+12 | 0.248009E+12 |
June | 0.576449E+12 | 0.353801E+10 | 0.318433E+11 | 0.227120E+12 | 0.636944E+12 |
July | 0.550628E+12 | 0.309808E+10 | 0.277448E+11 | 0.197591E+12 | 0.706354E+12 |
August | 0.513055E+12 | 0.379549E+10 | 0.380996E+11 | 0.243875E+12 | 0.653124E+12 |
September | 0.385265E+12 | 0.583465E+10 | 0.577990E+11 | 0.346872E+12 | 0.480711E+12 |
October | 0.317035E+12 | 0.132789E+11 | 0.153729E+12 | 0.719925E+12 | 0.179584E+12 |
November | 0.250686E+12 | 0.156707E+11 | 0.185924E+12 | 0.826502E+12 | 0.132395E+12 |
December | 0.200950E+12 | 0.191796E+11 | 0.225359E+12 | 0.979087E+12 | 0.124338E+12 |
Annual Sum or Average | 0.477551E+13 | 0.136351E+12 | 0.155763E+13 | 0.734943E+13 | 0.365030E+13 |
Minimum of Months | 0.200950E+12 | 0.309808E+10 | 0.277448E+11 | 0.197591E+12 | 0.110121E+12 |
Maximum of Months | 0.576449E+12 | 0.191796E+11 | 0.225359E+12 | 0.979087E+12 | 0.706354E+12 |