Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:42:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11169.59 | 984.51 | 984.51 |
Net Site Energy | 11169.59 | 984.51 | 984.51 |
Total Source Energy | 25592.31 | 2255.77 | 2255.77 |
Net Source Energy | 25592.31 | 2255.77 | 2255.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 154.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1945.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 868.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 629.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 115.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 190.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6473.59 | 4696.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 154.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1945.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 868.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 629.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 115.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 190.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 154.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1945.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 868.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 629.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 115.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 190.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 245.21 | 256.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.66 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 570.60 | 413.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 245.21 | 256.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.66 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 570.60 | 413.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6473.587 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6473.587 | 100.00 |
Total On-Site and Utility Electric Sources | 6473.587 | 100.00 |
Total Electricity End Uses | 6473.587 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 638.46 | 52.43 |
Air to Air Heat Recovery for Heating | 579.28 | 47.57 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1217.73 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 120.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7356.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.3255 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.5208 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.7005 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 11.5174 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.6875 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 9.7951 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.3255 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.5208 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.7005 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 11.5174 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.6875 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 9.7951 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 13.0243 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 5.0165 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:00 | 06-DEC-22:10 | - | - | - | - | - | - | - | - | - | - | 24-JAN-21:00 |
Heating | 0.00 | 131416.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 191946.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 54264.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32090.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41848.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4695.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3754.67 | 244448.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1871.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 460836.76 | 430129.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 131416.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 191946.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 24992.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1787.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 41848.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4695.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3754.67 | 244448.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1094.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 167.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6161.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2751.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2058.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1994.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 367.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 602.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 2983.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 20501.85 | 5090.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 543.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1807.08 | 448.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 543.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1807.08 | 448.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.12 | 0.484067 | 0.467000 | 1.45 | 1.00 | 0.500000 | 0.000787 | 0.000061 | 1.45 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.386999 | 0.132063 | 0.467000 | 0.180728 | 0.467000 | 0.500000 | 0.002885 | 0.000028 | 0.180728 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.281745 | 0.210061 | 0.467000 | 0.131575 | 0.560163 | 0.500000 | 0.001814 | 0.000012 | 0.131575 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.243812 | 0.513318 | 0.467000 | 0.113860 | 1.00 | 0.500000 | 0.000742 | 0.000017 | 0.113860 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.159905 | 0.451558 | 0.467000 | 0.074676 | 1.00 | 0.500000 | 0.000844 | 0.000011 | 0.074676 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.63 | 0.064963 | 0.467000 | 1.70 | 0.467000 | 0.500000 | 0.023273 | 0.000088 | 1.70 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.60 | 0.090092 | 0.467000 | 0.745987 | 0.467000 | 0.500000 | 0.004229 | 0.000083 | 0.745987 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.27 | 0.189332 | 0.467000 | 2.46 | 0.504886 | 0.500000 | 0.002012 | 0.000222 | 2.46 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.78 | 0.667411 | 0.467000 | 0.830500 | 1.00 | 0.500000 | 0.000571 | 0.000108 | 0.830500 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.50 | 0.101143 | 0.467000 | 1.17 | 0.467000 | 0.500000 | 0.003767 | 0.000095 | 1.17 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.61 | 0.096658 | 0.467000 | 1.22 | 0.467000 | 0.500000 | 0.003942 | 0.000098 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.51 | 0.056502 | 0.467000 | 1.17 | 0.467000 | 0.500000 | 0.012128 | 0.000061 | 1.17 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.898232 | 0.349619 | 0.467000 | 0.419474 | 0.932317 | 0.500000 | 0.001090 | 0.000066 | 0.419474 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6972.98 | 0.000061 | 145.41 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3209.44 | 0.000028 | 78.05 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1395.63 | 0.000012 | 31.07 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1943.09 | 0.000017 | 46.83 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1277.29 | 0.000011 | 30.80 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10015.95 | 0.000088 | 211.41 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9481.71 | 0.000083 | 216.42 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 25356.12 | 0.000222 | 562.51 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5064.53 | 0.000044 | 144.72 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5069.55 | 0.000044 | 144.86 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 29292.60 | 0.000256 | 837.01 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 29402.70 | 0.000257 | 840.16 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5053.88 | 0.000044 | 144.41 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5058.90 | 0.000044 | 144.56 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12301.45 | 0.000108 | 288.13 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1542.05 | 0.000013 | 44.06 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1542.65 | 0.000013 | 44.08 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7428.94 | 0.000065 | 212.27 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10817.56 | 0.000095 | 237.13 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11189.09 | 0.000098 | 244.97 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7004.12 | 0.000061 | 147.97 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7514.34 | 0.000066 | 183.11 |
VAV WITH REHEAT HEATING COIL | 132676.55 | 0.001161 | 2328.00 |
FLR_3_DOAS HEATING COIL | 10951.44 | 0.000096 | 192.16 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.27 | 0.000044 | 0.000455 |
ROOM_2_FLR_3 FAN COIL | 1.26 | 0.000044 | 0.000452 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.58 | 0.000256 | 0.002700 |
ROOM_4_MULT19_FLR_3 FAN COIL | 8.11 | 0.000257 | 0.003010 |
ROOM_5_FLR_3 FAN COIL | 1.12 | 0.000044 | 0.000402 |
ROOM_6_FLR_3 FAN COIL | 1.12 | 0.000044 | 0.000399 |
ROOM_1_FLR_6 FAN COIL | 0.336452 | 0.000013 | 0.000120 |
ROOM_2_FLR_6 FAN COIL | 0.334213 | 0.000013 | 0.000120 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.50 | 0.000065 | 0.000546 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.27 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.26 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.58 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.11 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.12 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.12 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.336452 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.334213 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.50 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000455 | 1.27 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000452 | 1.26 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008458 | 12.80 | 0.008458 | 0.002700 | 7.58 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008650 | 12.80 | 0.008500 | 0.003010 | 8.11 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000402 | 1.12 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000399 | 1.12 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008515 | 12.80 | 0.008500 | 0.000120 | 0.336452 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008515 | 12.80 | 0.008500 | 0.000120 | 0.334213 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008575 | 12.80 | 0.008500 | 0.000546 | 1.50 | |
VAV WITH REHEAT COOLING COIL | 31.88 | 6.70 | 0.007725 | 10.79 | 0.007725 | 0.020857 | 24.85 | 583927.65 |
FLR_3_DOAS COOLING COIL | 40.80 | 6.70 | 0.005631 | 11.84 | 0.005631 | 0.002355 | 2.05 | 65945.86 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.49 | 11.66 | 24.98 | 11.66 | 24.85 | 24.85 | 0.300000 | 0.469374 | 24.85 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.85 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.85 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020857 | 0.000023 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001161 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002355 | 0.000202 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000096 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.031415 | 5129.06 | |
HEATSYS1 PUMP | 0.002988 | 899.90 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002988 | 0.358577 |
COOLSYS1 | 0.031415 | 3.77 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 341562.57 | 341562.57 | 0.002988 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.031415 | 3551.02 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.031415 | 879527.37 | 880196.86 | 100.34 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.325 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.705 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.521 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.901 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.700 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.390 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 11.517 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.897 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 20432.332 | 10.325 | 191.855 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20432.332 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.656 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.656 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.385 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.385 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 742.517 | 4.521 | 279.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 742.517 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 729.693 | 7.700 | 357.693 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 729.693 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2175.192 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2175.192 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 12673.066 | 9.688 | 30.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12673.066 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.470 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.470 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.173 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6855 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.12938067E-14 | 0.41601190E-16 | -0.13825196E-09 | -0.61617685E-17 |
29 | 8 | 0.20259350E-07 | 0.15574452E-12 | 0.36060849E-03 | -0.23035579E-09 |
30 | 7 | -0.11728067E-01 | 0.82340017E-08 | -0.22346249E-01 | 0.13335239E-03 |
31 | 6 | 0.39139693 | 0.28900057E-05 | 0.46018966 | -0.45832853E-02 |
32 | 5 | -5.0543823 | 0.10873450E-03 | -4.3497742 | 0.61495273E-01 |
33 | 4 | 32.400414 | 0.89561747E-03 | 21.082566 | -0.41412424 |
34 | 3 | -109.94425 | 0.19639160E-02 | -54.916625 | 1.4966738 |
35 | 2 | 195.86041 | 0.11107406E-02 | 77.226367 | -2.8805378 |
36 | 1 | -170.69506 | 0.11917429E-03 | -55.066722 | 2.7373596 |
37 | 0 | 57.057407 | 0.68218560E-06 | 15.590186 | |
38 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
39 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
40 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
41 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
42 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
43 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
44 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
45 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
46 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
47 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
48 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
49 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
50 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
51 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
52 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
53 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
54 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
55 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
56 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
57 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
58 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
59 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
60 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
61 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
62 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
63 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
64 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
65 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
66 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
67 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
68 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
69 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
70 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
71 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
72 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
73 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
74 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
75 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
76 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
77 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.564_SHGC_0.25 | 37 | 1 | VerySmooth | 3.207 | 3.207 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.564_SHGC_0.25 | 38 | 1 | VerySmooth | 3.207 | 3.207 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60285 | 0.60285 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.40515E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60285 | 0.60285 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.40515E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.6041E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2579E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1068 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.6408E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2226E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6724E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1083 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.2112E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1206 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.6741E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9915E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3747E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3261E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3285E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7936E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0043E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7153E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8520E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3261E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3285E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7936E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0043E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7153E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8520E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 38921.34785 | 38921.34785 | 3.11500 | 3.11500 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 32.55400 | 5.61839E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 0.50000 | 4.31558E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4835.16713 | 4835.16713 | 0.38700 | 0.38700 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2343.70322 | 2343.70322 | 0.11065 | 0.11065 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3519.98976 | 3519.98976 | 0.28175 | 0.28175 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 37.82967 | 5.62649E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 765.37947 | 765.37947 | 3.61363E-002 | 9.17347E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3046.75854 | 3046.75854 | 0.24381 | 0.24381 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 34.88150 | 5.62194E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1397.78922 | 1397.78922 | 6.59945E-002 | 6.59945E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1998.21176 | 1998.21176 | 0.15991 | 0.15991 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 37.82967 | 5.62649E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 919.61696 | 919.61696 | 4.34183E-002 | 5.77652E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45388.21267 | 45388.21267 | 3.63242 | 3.63242 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 39.82467 | 5.62958E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1892.27286 | 1892.27286 | 8.93390E-002 | 8.93390E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19940.58886 | 19940.58886 | 1.59740 | 1.59740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5907.94835 | 5907.94835 | 0.27893 | 0.67639 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65759.46735 | 65759.46735 | 5.26502 | 5.26502 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13577.97734 | 13577.97734 | 0.64106 | 1.89399 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11775.54644 | 11775.54644 | 1.26988 | 1.26988 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5064.61586 | 5064.61586 | 0.24052 | 0.24052 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11702.89671 | 11702.89671 | 1.26205 | 1.26205 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5069.63618 | 5069.63618 | 0.24076 | 0.24076 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 70264.74144 | 70264.74144 | 7.57717 | 7.57717 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 29292.83920 | 29292.83920 | 1.39114 | 1.39114 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 75185.37013 | 75185.37013 | 8.10843 | 8.10843 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 29402.93985 | 29402.93985 | 1.39637 | 1.39637 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10404.06402 | 10404.06402 | 1.12198 | 1.12198 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 36.74350 | 5.62481E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5053.96131 | 5053.96131 | 0.24001 | 0.24001 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10340.36187 | 10340.36187 | 1.11511 | 1.11511 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5058.98413 | 5058.98413 | 0.24025 | 0.24025 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 22221.09202 | 22221.09202 | 1.77837 | 1.77837 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8322.44659 | 8322.44659 | 0.39293 | 0.47476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3119.90924 | 3119.90924 | 0.33645 | 0.33645 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1542.07719 | 1542.07719 | 7.32329E-002 | 7.32329E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3099.14607 | 3099.14607 | 0.33421 | 0.33421 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1542.67978 | 1542.67978 | 7.32615E-002 | 7.32615E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13916.22728 | 13916.22728 | 1.50078 | 1.50078 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7429.04074 | 7429.04074 | 0.35281 | 0.35281 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31181.73727 | 31181.73727 | 2.49866 | 2.49866 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5226.55475 | 5226.55475 | 0.24676 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32629.20552 | 32629.20552 | 2.61461 | 2.61461 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5338.88451 | 5338.88451 | 0.25207 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31227.11819 | 31227.11819 | 2.50582 | 2.50582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1416.93605 | 1416.93605 | 6.68896E-002 | 0.36735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 0.50000 | 4.31558E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11223.70913 | 11223.70913 | 0.89823 | 0.89823 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 40.80000 | 5.63111E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5504.38825 | 5504.38825 | 0.25988 | 0.25988 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 0.50000 | 4.31558E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 520810.32 | 24.85167 | 24.85167 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 130227.22 | 7.31787 | 7.31787 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 63092.52 | 22.09856 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 36503.53 | 4.24834 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.11500 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48407 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.45471 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.87082E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.10027E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.45471 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6972.97826 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.10027E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 145.40944 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.38700 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13206 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18073 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88498E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80776E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18073 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3209.44033 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80776E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.04886 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28175 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21006 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13158 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56016 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81376E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22096E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13158 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1395.62964 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22096E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.06791 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24381 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51332 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11386 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.42230E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69990E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11386 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1943.08918 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69990E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 46.82914 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15991 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.45156 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.46758E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.43745E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11743E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.46758E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1277.28718 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11743E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.79857 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.63242 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.49631E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.69634 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32730E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.76239E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.69634 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10015.95117 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.76239E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 211.40769 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59740 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.00918E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74599 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22902E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.29501E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74599 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9481.70827 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.29501E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 216.42014 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.26502 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18933 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.45876 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50489 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01234E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.21826E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.45876 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25356.11739 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21826E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 562.50865 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.26988 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.26988 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.43067E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.54538E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51617E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.54538E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.26988 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5064.53034 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.43067E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 144.71649 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.26205 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.26205 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.43506E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.51746E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51627E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.51746E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.26205 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5069.55058 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.43506E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 144.85992 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.57717 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.57717 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.56264E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.69988E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74182 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45836E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45836E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.69988E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.57717 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29292.59850 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.56264E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 837.01102 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.10843 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.10843 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.57228E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.00957E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74095 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64971E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.00957E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.10843 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29402.69830 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.57228E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 840.15654 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.12198 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.12198 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.42135E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.01762E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51764E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.01762E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.12198 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5053.87596 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.42135E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 144.41210 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11511 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.11511 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.42575E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.99307E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51768E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.99307E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11511 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5058.89869 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.42575E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 144.55560 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.77837 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66741 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83050 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.70862E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07618E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83050 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12301.45399 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07618E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 288.12650 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33645 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33645 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.34905E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.20399E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51527E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.20399E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33645 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1542.05195 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34905E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 44.06194 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33421 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33421 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.34958E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.19601E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51537E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.19601E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33421 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1542.65453 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34958E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 44.07916 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.50078 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.50078 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.49916E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.45893E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74118 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57477E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.45893E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.50078 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7428.94302 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.49916E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 212.27021 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.49866 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10114 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16688 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.76693E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.46368E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16688 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10817.56403 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.46368E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.12683 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.61461 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.66579E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22102 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.94174E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.78870E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22102 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11189.08986 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.78870E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.96979 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.50582 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.65022E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17022 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21283E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.12751E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17022 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7004.12085 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.12751E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 147.96800 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89823 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34962 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41947 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93232 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08976E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.57387E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41947 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7514.34281 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.57387E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 183.10997 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.48900 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66473 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.97801 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66473 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.85167 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.85167 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46937 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.85167 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.85167 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.87751 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.78899 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.72549E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.72549E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 583927.64963 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.08565E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.85167 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 132676.54667 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16071E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2327.99531 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.85167 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.08565E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.28317E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.16071E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 40.80000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.83593 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 65945.85541 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.35543E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 10951.44367 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.58080E-005 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 192.15837 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.35543E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.02167E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.58080E-005 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.14147E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5129.05725 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.98814E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.35858 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.98814E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 899.89604 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 341562.56517 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 341562.57000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.98814E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.14147E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.76976 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.14147E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3551.01933 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.14147E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 879527.36606 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 880196.86000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 100.34244 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7009.28 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3223.80 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1402.44 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1951.85 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1283.04 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10067.60 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9526.99 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 25480.17 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5455.76 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5461.17 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 31555.25 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 31673.85 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5444.28 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5449.69 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12359.01 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1661.14 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1661.79 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8002.65 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10871.81 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11245.25 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7040.21 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7547.90 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 106854.89 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 8820.06 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 21099.26 | 16423.63 | 4675.63 | 0.78 | 2900.42 | 29.42 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20969.46 | 16322.45 | 4647.00 | 0.78 | 2882.55 | 29.24 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 126048.67 | 98222.31 | 27826.36 | 0.78 | 17587.32 | 178.38 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 137910.42 | 106136.62 | 31773.80 | 0.77 | 18738.11 | 190.05 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 18646.76 | 14512.74 | 4134.03 | 0.78 | 2562.94 | 25.99 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 18532.73 | 14423.93 | 4108.80 | 0.78 | 2547.25 | 25.84 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5589.31 | 4351.05 | 1238.26 | 0.78 | 768.40 | 7.79 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5552.20 | 4322.13 | 1230.07 | 0.78 | 763.29 | 7.74 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 25196.50 | 19513.55 | 5682.96 | 0.77 | 3445.41 | 34.95 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 696242.50 | 440067.81 | 256174.69 | 0.63 | 102236.27 | 1036.94 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 54169.20 | 34464.63 | 19704.58 | 0.64 | 5364.64 | 54.41 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.564_SHGC_0.25 | N/A | 3.207 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 3.1163838454E-002 | 7.8045275735E-002 | Pass | Pass | 3.8854618414E-002 | 8.8516399676E-002 | Pass | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.0568739865E-002 | 7.9390838684E-002 | Pass | Pass | 8.4332212187E-002 | 0.1125421790 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.8335110104E-002 | 4.3821034655E-002 | Pass | Pass | 4.9702875453E-002 | 0.1054508251 | Pass | Fail |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4995813722E-003 | 1.6976247792E-002 | Pass | Pass | 7.5178590417E-002 | 0.1794643773 | Fail | Fail |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5496549319E-003 | 8.4729106375E-003 | Pass | Pass | 0.1075685346 | 0.4914788539 | Pass | Fail |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1172186067 | 0.2269961492 | Fail | Pass | 3.4774028247E-002 | 7.6457907149E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4002260707E-002 | 9.4353342570E-002 | Pass | Pass | 4.9549110033E-002 | 9.5350933748E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5926263518E-002 | 5.2307796303E-002 | Pass | Pass | 4.5724656349E-002 | 9.4571781558E-002 | Pass | Fail |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2136924297E-002 | 0.1935191371 | Pass | Pass | 0.2877552075 | 0.8431270548 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.2945999685E-002 | 0.2067178279 | Pass | Pass | 0.3594532695 | 2.0671377502 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.4768622542E-002 | 4.3596068993E-002 | Pass | Pass | 3.3269224970E-002 | 5.8136585586E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.7956528566E-002 | 7.2341356170E-002 | Pass | Pass | 0.4752005307 | 3.5802529743 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.6508008028E-002 | 0.1416113205 | Pass | Pass | 0.1164209152 | 0.2775741702 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.2144695831E-002 | 0.1379848239 | Pass | Pass | 0.1940365036 | 0.7028259549 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.2868771035E-002 | 1.7368767404E-002 | Pass | Pass | 7.3108892618E-002 | 0.1340714888 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.2884809212E-002 | 0.2218538029 | Pass | Fail | 0.2492418257 | 0.9965432513 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.5230044260E-002 | 0.2396304558 | Pass | Pass | 0.3980571849 | 1.5577883478 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.7131646866E-002 | 0.2593286319 | Pass | Pass | 0.2128831605 | 0.6236864379 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.1481605362E-002 | 0.2482917243 | Pass | Fail | 4.2381139607E-002 | 9.4535836458E-002 | Pass | Fail |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2111856157E-002 | 0.2449243684 | Fail | Fail | 4.1628282062E-002 | 9.4419287406E-002 | Pass | Fail |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.8838723995E-002 | 0.2155813527 | Fail | Pass | 4.0160666846E-002 | 7.7373267049E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.5538604442E-002 | 2.2520800477E-002 | Pass | Pass | 8.2915463820E-002 | 0.1270730576 | Pass | Fail |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2733.45 | 44.54 | 448.85 | 2506.04 | 7902.01 | 13634.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.207 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.207 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.207 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.207 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.207 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.207 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.207 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 3.207 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 3.207 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.207 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.207 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.207 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.207 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.207 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 3.207 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 3.207 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.207 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.207 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.207 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.207 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.207 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.564_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 3.207 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.207 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.207 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.207 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.207 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.207 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 3.207 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 3.207 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.564_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.207 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 3.207 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 3.207 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 3.207 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.3255 | 1978.83 | 20432.33 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 188.94 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.5625 | 67.07 | 909.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.76 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.5625 | 77.67 | 1053.39 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 10.14 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.5208 | 164.24 | 742.52 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.17 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.7005 | 94.76 | 729.69 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 4.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 11.5174 | 188.86 | 2175.19 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.03 | 0.0000 | Y | 16.34 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.6875 | 1308.19 | 12673.07 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 99.16 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 9.7951 | 1863.81 | 18256.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.45 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 9.7951 | 1864.32 | 18261.31 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.49 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.23 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.18 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 9.7951 | 220.77 | 2162.52 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 15.45 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.08 | 0.0000 | Y | 35.91 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.08 | 0.0000 | Y | 35.91 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 13.0243 | 103.30 | 1345.47 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 9.4981 | 11345.29 | 107758.18 | 496.38 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.79 | 83.79 | 262.50 | |
Exterior Lighting Total | 16690.39 | 262.50 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 341562.57 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 880196.86 | 2.96 | 880351.58 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12726.10 | 21099.26 | 16423.63 | 4675.63 | 0.78 | - | 2900.42 | 29.42 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12647.93 | 20969.46 | 16322.45 | 4647.00 | 0.78 | - | 2882.55 | 29.24 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75590.98 | 126048.67 | 98222.31 | 27826.36 | 0.78 | - | 17587.32 | 178.38 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 84261.59 | 137910.42 | 106136.62 | 31773.80 | 0.77 | - | 18738.11 | 190.05 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11248.47 | 18646.76 | 14512.74 | 4134.03 | 0.78 | - | 2562.94 | 25.99 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11179.73 | 18532.73 | 14423.93 | 4108.80 | 0.78 | - | 2547.25 | 25.84 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3370.92 | 5589.31 | 4351.05 | 1238.26 | 0.78 | - | 768.40 | 7.79 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3348.57 | 5552.20 | 4322.13 | 1230.07 | 0.78 | - | 763.29 | 7.74 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15283.85 | 25196.50 | 19513.55 | 5682.96 | 0.77 | - | 3445.41 | 34.95 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 583927.65 | 696242.50 | 440067.81 | 256174.69 | 0.63 | - | 102236.27 | 1036.94 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 65945.86 | 54169.20 | 34464.63 | 19704.58 | 0.64 | - | 5364.64 | 54.41 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6972.98 | 7009.28 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3209.44 | 3223.80 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1395.63 | 1402.44 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1943.09 | 1951.85 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1277.29 | 1283.04 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10015.95 | 10067.60 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9481.71 | 9526.99 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25356.12 | 25480.17 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5064.53 | 5455.76 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5069.55 | 5461.17 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29292.60 | 31555.25 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29402.70 | 31673.85 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5053.88 | 5444.28 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5058.90 | 5449.69 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12301.45 | 12359.01 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1542.05 | 1661.14 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1542.65 | 1661.79 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7428.94 | 8002.65 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10817.56 | 10871.81 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11189.09 | 11245.25 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7004.12 | 7040.21 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7514.34 | 7547.90 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 132676.55 | 106854.89 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 10951.44 | 8820.06 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.27 | 893.53 | 703.64 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.26 | 888.02 | 703.64 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.58 | 5331.57 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.11 | 5705.38 | 703.64 | 1.00 | 0.94 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.12 | 789.46 | 703.64 | 1.00 | 1.17 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.12 | 784.63 | 703.64 | 1.00 | 1.17 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.34 | 236.74 | 703.64 | 1.00 | 1.64 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 235.16 | 703.64 | 1.00 | 1.64 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.50 | 1056.00 | 703.64 | 1.00 | 1.11 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.85 | 55683.62 | 2240.64 | 1.00 | 1.11 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.031415 | 5129.06 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002988 | 899.90 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.031415 | 3551.02 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 38921.35 | 38921.35 | 19.67 | 3.115 | 3.115 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00912 | 32.55 | 0.00562 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4835.17 | 4835.17 | 72.09 | 0.387 | 0.387 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00893 | 40.80 | 0.00563 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3519.99 | 3519.99 | 45.32 | 0.282 | 0.282 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00926 | 37.83 | 0.00563 | 0.092 | 0.00 |
MECH_FLR_1 | 3046.76 | 3046.76 | 18.55 | 0.244 | 0.244 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00860 | 34.88 | 0.00562 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1998.21 | 1998.21 | 21.09 | 0.160 | 0.160 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00864 | 37.83 | 0.00563 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45388.21 | 45388.21 | 581.61 | 3.632 | 3.632 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00853 | 39.82 | 0.00563 | 0.000 | 0.00 |
CAFE_FLR_1 | 19940.59 | 19940.59 | 105.58 | 1.597 | 1.597 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01006 | 40.80 | 0.00563 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65759.47 | 65759.47 | 50.27 | 5.265 | 5.265 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.99 | 0.00991 | 40.80 | 0.00563 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11775.55 | 11775.55 | 301.77 | 1.270 | 1.270 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 39.12 | 0.00563 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11702.90 | 11702.90 | 299.94 | 1.262 | 1.262 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 38.94 | 0.00563 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 70264.74 | 70264.74 | 2865.16 | 7.577 | 7.577 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00846 | 40.80 | 0.00563 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 75185.37 | 75185.37 | 3064.97 | 8.108 | 8.108 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00865 | 40.27 | 0.00563 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10404.06 | 10404.06 | 266.62 | 1.122 | 1.122 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00852 | 36.74 | 0.00562 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10340.36 | 10340.36 | 265.02 | 1.115 | 1.115 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00852 | 36.41 | 0.00562 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 22221.09 | 22221.09 | 57.06 | 1.778 | 1.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00930 | 40.53 | 0.00563 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3119.91 | 3119.91 | 79.95 | 0.336 | 0.336 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 39.12 | 0.00563 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3099.15 | 3099.15 | 79.43 | 0.334 | 0.334 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 39.12 | 0.00563 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13916.23 | 13916.23 | 567.30 | 1.501 | 1.501 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00857 | 40.80 | 0.00563 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31181.74 | 31181.74 | 94.02 | 2.499 | 2.499 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01029 | 40.67 | 0.00563 | 1.188 | 0.00 |
DINING_FLR_6 | 32629.21 | 32629.21 | 98.38 | 2.615 | 2.615 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01021 | 40.67 | 0.00563 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31227.12 | 31227.12 | 302.28 | 2.506 | 2.506 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01004 | 39.60 | 0.00563 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11223.71 | 11223.71 | 27.23 | 0.898 | 0.898 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 40.80 | 0.00563 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 24.00 | 0.00846 | 0.50 | 0.00432 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 2343.70 | 2343.70 | 34.94 | 0.111 | 0.111 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00768 | 0.50 | 0.00432 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 765.38 | 765.38 | 9.85 | 0.036 | 0.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00763 | 0.50 | 0.00432 | 0.092 | 0.00 |
MECH_FLR_1 | 1397.79 | 1397.79 | 8.51 | 0.066 | 0.066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00754 | 0.50 | 0.00432 | 0.000 | 0.00 |
STORAGE_FLR_1 | 919.62 | 919.62 | 9.70 | 0.043 | 0.058 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00759 | 0.50 | 0.00432 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1892.27 | 1892.27 | 24.25 | 0.089 | 0.089 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00753 | 0.50 | 0.00432 | 0.000 | 0.00 |
CAFE_FLR_1 | 5907.95 | 5907.95 | 31.28 | 0.279 | 0.676 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00772 | 0.50 | 0.00432 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13577.98 | 13577.98 | 10.38 | 0.641 | 1.894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | 0.50 | 0.00432 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5064.62 | 5064.62 | 129.79 | 0.241 | 0.241 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5069.64 | 5069.64 | 129.93 | 0.241 | 0.241 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 29292.84 | 29292.84 | 1194.46 | 1.391 | 1.391 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00769 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 29402.94 | 29402.94 | 1198.63 | 1.396 | 1.396 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00769 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5053.96 | 5053.96 | 129.52 | 0.240 | 0.240 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5058.98 | 5058.98 | 129.66 | 0.240 | 0.240 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8322.45 | 8322.45 | 21.37 | 0.393 | 0.475 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00774 | 0.50 | 0.00432 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1542.08 | 1542.08 | 39.52 | 0.073 | 0.073 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1542.68 | 1542.68 | 39.54 | 0.073 | 0.073 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7429.04 | 7429.04 | 302.85 | 0.353 | 0.353 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | 0.50 | 0.00432 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5226.55 | 5226.55 | 15.76 | 0.247 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 1.188 | 0.00 |
DINING_FLR_6 | 5338.88 | 5338.88 | 16.10 | 0.252 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00780 | 0.50 | 0.00432 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1416.94 | 1416.94 | 13.72 | 0.067 | 0.367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00622 | 0.50 | 0.00432 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5504.39 | 5504.39 | 13.36 | 0.260 | 0.260 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00783 | 0.50 | 0.00432 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.85 | 24.85 | 7.32 | 7.32 | 24.8517 | 11.6647 | 24.8517 | 0.4694 | 0.3000 |
FLR_3_DOAS | 22.10 | 2.05 | 4.25 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6972.978 | 6972.978 | 1.454706 | 0.00006100 | 145.409 | 12/21 00:10:00 | 12/21 00:10:00 | 6972.98 | 6972.98 | 1.454706 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 7012.17 | 7012.17 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3209.440 | 3209.440 | 0.180728 | 0.00002808 | 78.049 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3209.44 | 3209.44 | 0.180728 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00768265 | 45.1124 | 2343.70 | 0.00 | 3226.14 | 3226.14 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1395.630 | 1395.630 | 0.131575 | 0.00001221 | 31.068 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1395.63 | 1395.63 | 0.131575 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00763066 | 44.8102 | 765.38 | 0.00 | 1403.21 | 1403.21 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1943.089 | 1943.089 | 0.113860 | 0.00001700 | 46.829 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1943.09 | 1943.09 | 0.113860 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00753570 | 44.2593 | 1397.79 | 0.00 | 1953.23 | 1953.23 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1277.287 | 1277.287 | 0.074676 | 0.00001117 | 30.799 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1277.29 | 1277.29 | 0.074676 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00758644 | 44.5537 | 919.62 | 0.00 | 1283.95 | 1283.95 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10015.951 | 10015.951 | 1.696342 | 0.00008762 | 211.408 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10015.95 | 10015.95 | 1.696342 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00753224 | 44.2397 | 1892.27 | 0.00 | 10072.00 | 10072.00 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9481.708 | 9481.708 | 0.745987 | 0.00008295 | 216.420 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9481.71 | 9481.71 | 0.745987 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00771873 | 45.3214 | 5907.95 | 0.00 | 9532.70 | 9532.70 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 25356.117 | 25356.117 | 2.458763 | 0.00022183 | 562.509 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25356.12 | 25356.12 | 2.458763 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00765667 | 44.9611 | 13577.98 | 0.00 | 25493.94 | 25493.94 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12726.104 | -999.000 | 1.269880 | 0.00045454 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 12726.10 | 12682.07 | 1.269880 | 21.74 | 14.62 | 0.00851617 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00851617 | 49.6005 | 11775.55 | 0.00 | 13998.44 | 13600.44 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5064.530 | 5064.530 | 0.240517 | 0.00004431 | 144.716 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5064.53 | 5064.53 | 0.240517 | 21.11 | 13.65 | 0.00766301 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00766301 | 44.6928 | 5064.62 | 0.00 | 5459.71 | 5459.71 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12647.932 | -999.000 | 1.262045 | 0.00045175 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12647.93 | 12603.91 | 1.262045 | 21.74 | 14.62 | 0.00851627 | 12.80 | 11.23 | 0.00850000 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00851627 | 49.6011 | 11702.90 | 0.00 | 13912.43 | 13516.57 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5069.551 | 5069.551 | 0.240756 | 0.00004435 | 144.860 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5069.55 | 5069.55 | 0.240756 | 21.11 | 13.65 | 0.00766334 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00766334 | 44.6947 | 5069.64 | 0.00 | 5465.12 | 5465.12 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 75590.976 | -999.000 | 7.577166 | 0.00269988 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 75590.98 | 75590.98 | 7.577166 | 21.74 | 14.57 | 0.00845836 | 12.80 | 11.19 | 0.00845836 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00845836 | 49.2677 | 70264.74 | 0.00 | 83200.90 | 81630.55 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 29292.599 | 29292.599 | 1.391138 | 0.00025626 | 837.011 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 29292.60 | 29292.60 | 1.391138 | 21.11 | 13.67 | 0.00768875 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00768875 | 44.8405 | 29292.84 | 0.00 | 31578.38 | 31578.38 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 84261.594 | -999.000 | 8.108426 | 0.00300957 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 84261.59 | 81637.22 | 8.108426 | 21.74 | 14.74 | 0.00864971 | 12.80 | 11.23 | 0.00850000 | 40.27 | 0.00563027 | 18.42 | 0.0000 | 21.11 | 0.00864971 | 50.3689 | 75185.37 | 0.00 | 92533.54 | 87116.15 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 29402.698 | 29402.698 | 1.396366 | 0.00025723 | 840.157 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 29402.70 | 29402.70 | 1.396366 | 21.11 | 13.67 | 0.00768974 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00768974 | 44.8462 | 29402.94 | 0.00 | 31697.07 | 31697.07 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11248.473 | -999.000 | 1.121978 | 0.00040176 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 11248.47 | 11206.04 | 1.121978 | 21.74 | 14.63 | 0.00851764 | 12.80 | 11.23 | 0.00850000 | 36.74 | 0.00562481 | 17.31 | 0.0000 | 21.11 | 0.00851764 | 49.6089 | 10404.06 | 0.00 | 12372.85 | 12016.84 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5053.876 | 5053.876 | 0.240011 | 0.00004421 | 144.412 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5053.88 | 5053.88 | 0.240011 | 21.11 | 13.65 | 0.00766237 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00766237 | 44.6891 | 5053.96 | 0.00 | 5448.23 | 5448.23 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11179.734 | -999.000 | 1.115108 | 0.00039931 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 11179.73 | 11137.46 | 1.115108 | 21.74 | 14.63 | 0.00851768 | 12.80 | 11.23 | 0.00850000 | 36.41 | 0.00562429 | 17.20 | 0.0000 | 21.11 | 0.00851768 | 49.6092 | 10340.36 | 0.00 | 12297.23 | 11943.28 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5058.899 | 5058.899 | 0.240250 | 0.00004426 | 144.556 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5058.90 | 5058.90 | 0.240250 | 21.11 | 13.65 | 0.00766269 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00766269 | 44.6910 | 5058.98 | 0.00 | 5453.64 | 5453.64 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12301.454 | 12301.454 | 0.830500 | 0.00010762 | 288.127 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12301.45 | 12301.45 | 0.830500 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00774440 | 45.4697 | 8322.45 | 0.00 | 12367.06 | 12367.06 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3370.920 | -999.000 | 0.336452 | 0.00012040 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3370.92 | 3359.90 | 0.336452 | 21.74 | 14.62 | 0.00851527 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00851527 | 49.5954 | 3119.91 | 0.00 | 3707.98 | 3603.33 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1542.052 | 1542.052 | 0.073233 | 0.00001349 | 44.062 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1542.05 | 1542.05 | 0.073233 | 21.11 | 13.70 | 0.00771865 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00771865 | 45.0133 | 1542.08 | 0.00 | 1662.38 | 1662.38 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3348.571 | -999.000 | 0.334213 | 0.00011960 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3348.57 | 3337.56 | 0.334213 | 21.74 | 14.62 | 0.00851537 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00851537 | 49.5959 | 3099.15 | 0.00 | 3683.39 | 3579.36 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1542.655 | 1542.655 | 0.073262 | 0.00001350 | 44.079 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1542.65 | 1542.65 | 0.073262 | 21.11 | 13.70 | 0.00771877 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00771877 | 45.0140 | 1542.68 | 0.00 | 1663.03 | 1663.03 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15283.846 | -999.000 | 1.500781 | 0.00054589 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 15283.85 | 15042.33 | 1.500781 | 21.74 | 14.67 | 0.00857477 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00857477 | 49.9381 | 13916.23 | 0.00 | 16799.62 | 16095.73 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7428.943 | 7428.943 | 0.352806 | 0.00006499 | 212.270 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7428.94 | 7428.94 | 0.352806 | 21.11 | 13.71 | 0.00773017 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00773017 | 45.0795 | 7429.04 | 0.00 | 8008.63 | 8008.63 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10817.564 | 10817.564 | 1.166876 | 0.00009464 | 237.127 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10817.56 | 10817.56 | 1.166876 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00779173 | 45.7444 | 5226.55 | 0.00 | 10877.42 | 10877.42 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11189.090 | 11189.090 | 1.221024 | 0.00009789 | 244.970 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 11189.09 | 11189.09 | 1.221024 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00779587 | 45.7690 | 5338.88 | 0.00 | 11251.02 | 11251.02 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7004.121 | 7004.121 | 1.170217 | 0.00006128 | 147.968 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7004.12 | 7004.12 | 1.170217 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00621883 | 36.6080 | 1416.94 | 0.00 | 7043.31 | 7043.31 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7514.343 | 7514.343 | 0.419474 | 0.00006574 | 183.110 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 7514.34 | 7514.34 | 0.419474 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00782506 | 45.9380 | 5504.39 | 0.00 | 7553.41 | 7553.41 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 583927.650 | -999.000 | 24.851672 | 0.02085654 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 583927.65 | 583927.65 | 24.851672 | 31.88 | 17.39 | 0.00772549 | 10.79 | 9.63 | 0.00772549 | 40.80 | 0.00563111 | 18.58 | 46.9242 | 23.99 | 0.00952975 | 46.5165 | 310317.98 | 0.00 | 623426.14 | 607757.83 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 132676.547 | 132676.547 | 7.455502 | 0.00116071 | 2327.995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | 132676.55 | 132676.55 | 7.455502 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 156.4142 | 21.61 | 0.00786125 | 44.4592 | 52232.28 | 0.00 | 129301.89 | 129301.89 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 65945.855 | -999.000 | 2.051317 | 0.00235543 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 65945.86 | 65945.86 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 11.84 | 7.85 | 0.00563111 | 40.80 | 0.00563111 | 18.58 | 99.9965 | 21.11 | 0.00855707 | 49.8358 | 204384.58 | 0.00 | 66000.58 | 66000.58 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10951.44 | 10951.44 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 333.3216 | 21.11 | 0.00768939 | 44.8442 | 89456.77 | 0.00 | 10672.89 | 10672.89 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6972.978 | 6972.978 | 1.454706 | 0.00006100 | 145.409 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 2.0012 | 2.041494 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6972.98 | 6972.98 | 1.0000 | 1.59027597 | 1.454706 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06099643 | 60.00 | 32.22 | 27.78 | 0.000 | 6972.98 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 7012.17 | 7012.17 | 1.59027597 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3209.440 | 3209.440 | 0.180728 | 0.00002808 | 78.049 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 0.9211 | 0.939635 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3209.44 | 3209.44 | 1.0000 | 0.19757128 | 0.180728 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.02807472 | 60.00 | 32.22 | 27.78 | 0.000 | 3209.44 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00768265 | 21.00 | 0.00768265 | 45.1124 | 2343.70 | 0.00 | 3226.14 | 3226.14 | 0.19757128 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.61 | 18.90 | 0.00800000 | 53263.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1395.630 | 1395.630 | 0.131575 | 0.00001221 | 31.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 0.4005 | 0.408601 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1395.63 | 1395.63 | 1.0000 | 0.14383709 | 0.131575 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01220833 | 60.00 | 32.22 | 27.78 | 0.000 | 1395.63 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00763066 | 21.00 | 0.00763066 | 44.8102 | 765.38 | 0.00 | 1403.21 | 1403.21 | 0.14383709 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.17 | 16.73 | 0.00800000 | 46690.3 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1943.089 | 1943.089 | 0.113860 | 0.00001700 | 46.829 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 0.5577 | 0.568882 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1943.09 | 1943.09 | 1.0000 | 0.12447146 | 0.113860 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01699726 | 60.00 | 32.22 | 27.78 | 0.000 | 1943.09 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00753570 | 21.00 | 0.00753570 | 44.2593 | 1397.79 | 0.00 | 1953.23 | 1953.23 | 0.12447146 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.99 | 18.69 | 0.00800000 | 52626.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1277.287 | 1277.287 | 0.074676 | 0.00001117 | 30.799 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 0.3666 | 0.373954 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1277.29 | 1277.29 | 1.0000 | 0.08163511 | 0.074676 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01117313 | 60.00 | 32.22 | 27.78 | 0.000 | 1277.29 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00758644 | 21.00 | 0.00758644 | 44.5537 | 919.62 | 0.00 | 1283.95 | 1283.95 | 0.08163511 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.02 | 18.71 | 0.00800000 | 52662.7 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10015.951 | 10015.951 | 1.696342 | 0.00008762 | 211.408 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 2.8745 | 2.932391 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10015.95 | 10015.95 | 1.0000 | 1.85443164 | 1.696342 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.08761497 | 60.00 | 32.22 | 27.78 | 0.000 | 10015.95 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00753224 | 21.00 | 0.00753224 | 44.2397 | 1892.27 | 0.00 | 10072.00 | 10072.00 | 1.85443164 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.93 | 15.20 | 0.00800000 | 42366.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9481.708 | 9481.708 | 0.745987 | 0.00008295 | 216.420 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 2.7212 | 2.775980 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9481.71 | 9481.71 | 1.0000 | 0.81550816 | 0.745987 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.08294166 | 60.00 | 32.22 | 27.78 | 0.000 | 9481.71 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00771873 | 21.00 | 0.00771873 | 45.3214 | 5907.95 | 0.00 | 9532.70 | 9532.70 | 0.81550816 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.06 | 17.38 | 0.00800000 | 48624.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25356.117 | 25356.117 | 2.458763 | 0.00022183 | 562.509 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 7.2771 | 7.423565 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25356.12 | 25356.12 | 1.0000 | 2.68790571 | 2.458763 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.22180375 | 60.00 | 32.22 | 27.78 | 0.000 | 25356.12 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00765667 | 21.00 | 0.00765667 | 44.9611 | 13577.98 | 0.00 | 25493.94 | 25493.94 | 2.68790571 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.90 | 16.63 | 0.00800000 | 46419.4 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12726.104 | -999.000 | 1.269880 | 0.00045454 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6711 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.269880 | 1.38822506 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 1.4469 | 1.446898 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 12726.10 | 12682.07 | 1.0000 | 1.38822506 | 1.269880 | 21.74 | 14.62 | 0.00851617 | 43489.4 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.45449207 | 6.70 | 13.37 | 6.67 | 0.000 | 12726.10 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00851617 | 21.11 | 0.00851617 | 49.6005 | 11775.55 | 0.00 | 13998.44 | 13600.44 | 1.38822506 | 21.74 | 15.59 | 0.00851617 | 43489.4 | 12.14 | 11.73 | 0.00840256 | 33405.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5064.530 | 5064.530 | 0.240517 | 0.00004431 | 144.716 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.269880 | 1.38822506 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 1.4535 | 1.482753 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5064.53 | 5064.53 | 1.0000 | 0.26293226 | 0.240517 | 21.11 | 13.65 | 0.00766301 | 40678.2 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04430220 | 60.00 | 32.22 | 27.78 | 0.000 | 5064.53 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00766301 | 21.11 | 0.00766301 | 44.6928 | 5064.62 | 0.00 | 5459.71 | 5459.71 | 0.26293226 | 16.60 | 12.82 | 0.00766301 | 36081.5 | 36.98 | 20.02 | 0.00766301 | 56846.2 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12647.932 | -999.000 | 1.262045 | 0.00045175 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6713 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.262045 | 1.37966031 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 1.4380 | 1.438010 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12647.93 | 12603.91 | 1.0000 | 1.37966031 | 1.262045 | 21.74 | 14.62 | 0.00851627 | 43489.6 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.45170030 | 6.70 | 13.37 | 6.67 | 0.000 | 12647.93 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00851627 | 21.11 | 0.00851627 | 49.6011 | 11702.90 | 0.00 | 13912.43 | 13516.57 | 1.37966031 | 21.74 | 15.59 | 0.00851627 | 43489.6 | 12.14 | 11.73 | 0.00840257 | 33405.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5069.551 | 5069.551 | 0.240756 | 0.00004435 | 144.860 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.262045 | 1.37966031 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 1.4549 | 1.484223 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5069.55 | 5069.55 | 1.0000 | 0.26319289 | 0.240756 | 21.11 | 13.65 | 0.00766334 | 40679.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04434612 | 60.00 | 32.22 | 27.78 | 0.000 | 5069.55 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00766334 | 21.11 | 0.00766334 | 44.6947 | 5069.64 | 0.00 | 5465.12 | 5465.12 | 0.26319289 | 16.60 | 12.82 | 0.00766334 | 36082.4 | 36.98 | 20.02 | 0.00766334 | 56847.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75590.976 | -999.000 | 7.577166 | 0.00269988 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5637 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.577166 | 8.28331390 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 8.5945 | 8.594339 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 75590.98 | 75590.98 | 1.0000 | 8.28331390 | 7.577166 | 21.74 | 14.57 | 0.00845836 | 43342.8 | 12.80 | 11.19 | 0.00845836 | 34217.1 | 2.69960868 | 6.70 | 13.37 | 6.67 | 0.000 | 75590.98 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00845836 | 21.11 | 0.00845836 | 49.2677 | 70264.74 | 0.00 | 83200.90 | 81630.55 | 8.28331390 | 21.74 | 15.54 | 0.00845836 | 43342.8 | 12.09 | 11.69 | 0.00838323 | 33298.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29292.599 | 29292.599 | 1.391138 | 0.00025626 | 837.011 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.577166 | 8.28331390 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 8.4069 | 8.576056 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 29292.60 | 29292.60 | 1.0000 | 1.52078370 | 1.391138 | 21.11 | 13.67 | 0.00768875 | 40743.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.25623829 | 60.00 | 32.22 | 27.78 | 0.000 | 29292.60 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00768875 | 21.11 | 0.00768875 | 44.8405 | 29292.84 | 0.00 | 31578.38 | 31578.38 | 1.52078370 | 16.60 | 12.85 | 0.00768875 | 36146.7 | 36.97 | 20.04 | 0.00768875 | 56911.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 84261.594 | -999.000 | 8.108426 | 0.00300957 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9194 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.108426 | 8.86408478 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 9.5803 | 9.580148 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 84261.59 | 81637.22 | 1.0000 | 8.86408478 | 8.108426 | 21.74 | 14.74 | 0.00864971 | 43828.2 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 3.00926569 | 6.70 | 13.37 | 6.67 | 0.000 | 84261.59 | 40.27 | 0.00563027 | 18.42 | 0.00000000 | 0.0000 | 21.11 | 0.00864971 | 21.11 | 0.00864971 | 50.3689 | 75185.37 | 0.00 | 92533.54 | 87116.15 | 8.86408478 | 21.74 | 15.71 | 0.00864971 | 43828.2 | 12.11 | 11.72 | 0.00840751 | 33389.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29402.698 | 29402.698 | 1.396366 | 0.00025723 | 840.157 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.108426 | 8.86408478 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 8.4385 | 8.608291 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 29402.70 | 29402.70 | 1.0000 | 1.52649975 | 1.396366 | 21.11 | 13.67 | 0.00768974 | 40746.3 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.25720139 | 60.00 | 32.22 | 27.78 | 0.000 | 29402.70 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00768974 | 21.11 | 0.00768974 | 44.8462 | 29402.94 | 0.00 | 31697.07 | 31697.07 | 1.52649975 | 16.60 | 12.85 | 0.00768974 | 36149.2 | 36.97 | 20.04 | 0.00768974 | 56913.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11248.473 | -999.000 | 1.121978 | 0.00040176 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6739 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.121978 | 1.22653963 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 1.2789 | 1.278899 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 11248.47 | 11206.04 | 1.0000 | 1.22653963 | 1.121978 | 21.74 | 14.63 | 0.00851764 | 43493.1 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.40172089 | 6.70 | 13.37 | 6.67 | 0.000 | 11248.47 | 36.74 | 0.00562481 | 17.31 | 0.00000000 | 0.0000 | 21.11 | 0.00851764 | 21.11 | 0.00851764 | 49.6089 | 10404.06 | 0.00 | 12372.85 | 12016.84 | 1.22653963 | 21.74 | 15.59 | 0.00851764 | 43493.1 | 12.14 | 11.73 | 0.00840262 | 33405.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5053.876 | 5053.876 | 0.240011 | 0.00004421 | 144.412 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.121978 | 1.22653963 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 1.4504 | 1.479634 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5053.88 | 5053.88 | 1.0000 | 0.26237913 | 0.240011 | 21.11 | 13.65 | 0.00766237 | 40676.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04420900 | 60.00 | 32.22 | 27.78 | 0.000 | 5053.88 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00766237 | 21.11 | 0.00766237 | 44.6891 | 5053.96 | 0.00 | 5448.23 | 5448.23 | 0.26237913 | 16.60 | 12.82 | 0.00766237 | 36079.9 | 36.98 | 20.02 | 0.00766237 | 56844.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11179.734 | -999.000 | 1.115108 | 0.00039931 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6739 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.115108 | 1.21902971 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 1.2711 | 1.271083 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 11179.73 | 11137.46 | 1.0000 | 1.21902971 | 1.115108 | 21.74 | 14.63 | 0.00851768 | 43493.2 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.39926602 | 6.70 | 13.37 | 6.67 | 0.000 | 11179.73 | 36.41 | 0.00562429 | 17.20 | 0.00000000 | 0.0000 | 21.11 | 0.00851768 | 21.11 | 0.00851768 | 49.6092 | 10340.36 | 0.00 | 12297.23 | 11943.28 | 1.21902971 | 21.74 | 15.59 | 0.00851768 | 43493.2 | 12.14 | 11.73 | 0.00840262 | 33405.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5058.899 | 5058.899 | 0.240250 | 0.00004426 | 144.556 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.115108 | 1.21902971 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 1.4519 | 1.481105 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5058.90 | 5058.90 | 1.0000 | 0.26263989 | 0.240250 | 21.11 | 13.65 | 0.00766269 | 40677.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04425294 | 60.00 | 32.22 | 27.78 | 0.000 | 5058.90 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00766269 | 21.11 | 0.00766269 | 44.6910 | 5058.98 | 0.00 | 5453.64 | 5453.64 | 0.26263989 | 16.60 | 12.82 | 0.00766269 | 36080.7 | 36.98 | 20.02 | 0.00766269 | 56845.4 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12301.454 | 12301.454 | 0.830500 | 0.00010762 | 288.127 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 3.5305 | 3.601523 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12301.45 | 12301.45 | 1.0000 | 0.90789737 | 0.830500 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.10760751 | 60.00 | 32.22 | 27.78 | 0.000 | 12301.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00774440 | 21.00 | 0.00774440 | 45.4697 | 8322.45 | 0.00 | 12367.06 | 12367.06 | 0.90789737 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.96 | 18.02 | 0.00800000 | 50556.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3370.920 | -999.000 | 0.336452 | 0.00012040 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6695 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.336452 | 0.36780761 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 0.3833 | 0.383258 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3370.92 | 3359.90 | 1.0000 | 0.36780761 | 0.336452 | 21.74 | 14.62 | 0.00851527 | 43487.1 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.12038692 | 6.70 | 13.37 | 6.67 | 0.000 | 3370.92 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00851527 | 21.11 | 0.00851527 | 49.5954 | 3119.91 | 0.00 | 3707.98 | 3603.33 | 0.36780761 | 21.74 | 15.59 | 0.00851527 | 43487.1 | 12.14 | 11.73 | 0.00840253 | 33405.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1542.052 | 1542.052 | 0.073233 | 0.00001349 | 44.062 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.336452 | 0.36780761 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 0.4426 | 0.451470 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1542.05 | 1542.05 | 1.0000 | 0.08005781 | 0.073233 | 21.11 | 13.70 | 0.00771865 | 40819.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01348917 | 60.00 | 32.22 | 27.78 | 0.000 | 1542.05 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00771865 | 21.11 | 0.00771865 | 45.0133 | 1542.08 | 0.00 | 1662.38 | 1662.38 | 0.08005781 | 16.60 | 12.88 | 0.00771865 | 36222.4 | 36.97 | 20.06 | 0.00771865 | 56987.1 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3348.571 | -999.000 | 0.334213 | 0.00011960 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6696 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.334213 | 0.36535984 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 0.3807 | 0.380717 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3348.57 | 3337.56 | 1.0000 | 0.36535984 | 0.334213 | 21.74 | 14.62 | 0.00851537 | 43487.3 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.11958878 | 6.70 | 13.37 | 6.67 | 0.000 | 3348.57 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00851537 | 21.11 | 0.00851537 | 49.5959 | 3099.15 | 0.00 | 3683.39 | 3579.36 | 0.36535984 | 21.74 | 15.59 | 0.00851537 | 43487.3 | 12.14 | 11.73 | 0.00840253 | 33405.8 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1542.655 | 1542.655 | 0.073262 | 0.00001350 | 44.079 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.334213 | 0.36535984 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 0.4427 | 0.451646 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1542.65 | 1542.65 | 1.0000 | 0.08008909 | 0.073262 | 21.11 | 13.70 | 0.00771877 | 40819.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01349444 | 60.00 | 32.22 | 27.78 | 0.000 | 1542.65 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00771877 | 21.11 | 0.00771877 | 45.0140 | 1542.68 | 0.00 | 1663.03 | 1663.03 | 0.08008909 | 16.60 | 12.88 | 0.00771877 | 36222.7 | 36.97 | 20.06 | 0.00771877 | 56987.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15283.846 | -999.000 | 1.500781 | 0.00054589 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7801 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.500781 | 1.64064544 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 1.7377 | 1.737702 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 15283.85 | 15042.33 | 1.0000 | 1.64064544 | 1.500781 | 21.74 | 14.67 | 0.00857477 | 43637.9 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.54583769 | 6.70 | 13.37 | 6.67 | 0.000 | 15283.85 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00857477 | 21.11 | 0.00857477 | 49.9381 | 13916.23 | 0.00 | 16799.62 | 16095.73 | 1.64064544 | 21.74 | 15.64 | 0.00857477 | 43637.9 | 12.13 | 11.73 | 0.00840476 | 33398.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7428.943 | 7428.943 | 0.352806 | 0.00006499 | 212.270 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.500781 | 1.64064544 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 2.1321 | 2.174987 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7428.94 | 7428.94 | 1.0000 | 0.38568558 | 0.352806 | 21.11 | 13.71 | 0.00773017 | 40848.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06498500 | 60.00 | 32.22 | 27.78 | 0.000 | 7428.94 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00773017 | 21.11 | 0.00773017 | 45.0795 | 7429.04 | 0.00 | 8008.63 | 8008.63 | 0.38568558 | 16.60 | 12.89 | 0.00773017 | 36251.6 | 36.97 | 20.07 | 0.00773017 | 57016.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10817.564 | 10817.564 | 1.166876 | 0.00009464 | 237.127 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 3.1046 | 3.167081 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10817.56 | 10817.56 | 1.0000 | 1.27562194 | 1.166876 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09462712 | 60.00 | 32.22 | 27.78 | 0.000 | 10817.56 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00779173 | 21.00 | 0.00779173 | 45.7444 | 5226.55 | 0.00 | 10877.42 | 10877.42 | 1.27562194 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.96 | 16.30 | 0.00800000 | 45461.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11189.090 | 11189.090 | 1.221024 | 0.00009789 | 244.970 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 3.2112 | 3.275854 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 11189.09 | 11189.09 | 1.0000 | 1.33481634 | 1.221024 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09787705 | 60.00 | 32.22 | 27.78 | 0.000 | 11189.09 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00779587 | 21.00 | 0.00779587 | 45.7690 | 5338.88 | 0.00 | 11251.02 | 11251.02 | 1.33481634 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.87 | 16.27 | 0.00800000 | 45363.6 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7004.121 | 7004.121 | 1.170217 | 0.00006128 | 147.968 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 2.0102 | 2.050611 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7004.12 | 7004.12 | 1.0000 | 1.27927484 | 1.170217 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06126885 | 60.00 | 32.22 | 27.78 | 0.000 | 7004.12 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.27 | 0.00621883 | 21.00 | 0.00621883 | 36.6080 | 1416.94 | 0.00 | 7043.31 | 7043.31 | 1.27927484 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.00 | 15.22 | 0.00800000 | 42440.4 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7514.343 | 7514.343 | 0.419474 | 0.00006574 | 183.110 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 2.1566 | 2.199990 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 7514.34 | 7514.34 | 1.0000 | 0.45856700 | 0.419474 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06573204 | 60.00 | 32.22 | 27.78 | 0.000 | 7514.34 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00782506 | 21.00 | 0.00782506 | 45.9380 | 5504.39 | 0.00 | 7553.41 | 7553.41 | 0.45856700 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.75 | 18.94 | 0.00800000 | 53406.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 583927.650 | -999.000 | 24.851672 | 0.02085654 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2013 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.851672 | 27.16770424 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 66.3911 | 66.391072 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 583927.65 | 583927.65 | 1.0000 | 27.16770424 | 24.851672 | 31.88 | 17.39 | 0.00772549 | 51810.6 | 10.79 | 9.63 | 0.00772549 | 30317.1 | 20.85441509 | 6.70 | 13.37 | 6.67 | 55683.616 | 528244.03 | 40.80 | 0.00563111 | 18.58 | 11.66146000 | 46.9242 | 23.99 | 0.00957713 | 23.99 | 0.00952975 | 46.5165 | 310317.98 | 0.00 | 623426.14 | 607757.83 | 27.16770424 | 31.88 | 18.44 | 0.00772549 | 51810.6 | 9.93 | 9.82 | 0.00749657 | 28863.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 132676.547 | 132676.547 | 7.455502 | 0.00116071 | 2327.995 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.851672 | 27.16770424 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 38.0777 | 38.843995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | Sensible | 132676.55 | 132676.55 | 1.0000 | 8.15031127 | 7.455502 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 1.16059390 | 60.00 | 32.22 | 27.78 | 0.000 | 132676.55 | 0.50 | 0.00431558 | 0.50 | 11.66146000 | 156.4142 | 18.52 | 0.00774417 | 21.61 | 0.00786125 | 44.4592 | 52232.28 | 0.00 | 129301.89 | 129301.89 | 8.15031127 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 65945.855 | -999.000 | 2.051317 | 0.00235543 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.3079 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 31.41147502 | 13.37 | 6.70 | 6.67 | 879527.37 | 7.4979 | 7.497874 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 65945.86 | 65945.86 | 1.0000 | 2.24248814 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 55507.6 | 11.84 | 7.85 | 0.00563111 | 26100.2 | 2.35519288 | 6.70 | 13.37 | 6.67 | 2195.006 | 63750.85 | 40.80 | 0.00563111 | 18.58 | 2.05124512 | 99.9965 | 21.11 | 0.00855006 | 21.11 | 0.00855707 | 49.8358 | 204384.58 | 0.00 | 66000.58 | 66000.58 | 2.24248814 | 40.80 | 19.66 | 0.00563111 | 55507.6 | 11.81 | 8.61 | 0.00563111 | 26075.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 2.98783350 | 54.44 | 82.22 | 27.78 | 348436.65 | 3.1430 | 3.206277 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10951.44 | 10951.44 | 1.0000 | 0.67274644 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 0.09579823 | 60.00 | 32.22 | 27.78 | 0.000 | 10951.44 | 0.50 | 0.00431558 | 0.50 | 2.05124512 | 333.3216 | 21.11 | 0.00768768 | 21.11 | 0.00768939 | 44.8442 | 89456.77 | 0.00 | 10672.89 | 10672.89 | 0.67274644 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 24.85 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1930.17 | 6036.00 | 526.83 |
RETAIL_1_FLR_1 | 3135.17 | 4608.83 | 565.67 |
RETAIL_2_FLR_1 | 2294.83 | 5065.50 | 660.17 |
MECH_FLR_1 | 1731.00 | 6016.50 | 76.00 |
STORAGE_FLR_1 | 1625.33 | 6268.00 | 133.50 |
LAUNDRY_FLR_1 | 8073.00 | 3675.50 | 3471.83 |
CAFE_FLR_1 | 4770.17 | 3033.50 | 1150.00 |
LOBBY_FLR_1 | 2988.33 | 3767.00 | 1039.67 |
ROOM_1_FLR_3 | 448.33 | 7890.17 | 269.50 |
ROOM_2_FLR_3 | 722.17 | 8106.00 | 619.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 506.67 | 8756.83 | 506.50 |
ROOM_5_FLR_3 | 583.33 | 7671.00 | 272.00 |
ROOM_6_FLR_3 | 819.50 | 7802.17 | 611.00 |
CORRIDOR_FLR_3 | 1619.50 | 7037.83 | 766.83 |
ROOM_1_FLR_6 | 866.50 | 7736.50 | 556.33 |
ROOM_2_FLR_6 | 1318.50 | 7978.50 | 1123.17 |
ROOM_3_MULT9_FLR_6 | 305.17 | 7664.33 | 148.00 |
BANQUET_FLR_6 | 4867.83 | 2013.83 | 1086.67 |
DINING_FLR_6 | 5599.50 | 1307.83 | 1020.50 |
KITCHEN_FLR_6 | 8595.67 | 6708.17 | 6699.33 |
CORRIDOR_FLR_6 | 1993.83 | 5888.00 | 484.33 |
Facility | 8748.83 | 8760.00 | 7356.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 46.33 | 0.00 | 46.33 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 8.50 | 0.00 | 8.50 |
ROOM_2_FLR_3 | 0.00 | 5.50 | 0.00 | 5.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 2.50 | 0.00 | 2.50 |
ROOM_5_FLR_3 | 0.00 | 27.83 | 0.00 | 27.83 |
ROOM_6_FLR_3 | 0.00 | 25.33 | 0.00 | 25.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 12.33 | 0.00 | 12.33 |
ROOM_2_FLR_6 | 0.00 | 9.00 | 0.00 | 9.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 14.17 | 0.00 | 14.17 |
BANQUET_FLR_6 | 0.00 | 3.33 | 0.00 | 3.33 |
DINING_FLR_6 | 0.00 | 6.00 | 0.00 | 6.00 |
KITCHEN_FLR_6 | 0.00 | 68.00 | 0.00 | 68.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 120.50 | 0.00 | 120.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 1.082 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.424 | 0.134 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.500 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.597 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.651 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 21.444 | 0.143 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 3.721 | 0.105 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.735 | 0.043 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.474 | 0.173 | 0.000 | 0.056 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.474 | 0.172 | 0.000 | 0.051 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.538 | 0.077 | 0.000 | 0.078 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.474 | 0.173 | 0.000 | 0.056 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.474 | 0.173 | 0.000 | 0.051 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.571 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.474 | 0.173 | 0.000 | 0.063 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.474 | 0.172 | 0.000 | 0.058 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.539 | 0.141 | 0.000 | 0.104 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 4.922 | 0.050 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.285 | 0.050 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 21.430 | 0.144 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 1.136 | 0.035 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.604 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.240 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.794 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.319 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.362 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 10.586 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 1.896 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 0.998 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.464 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.463 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.527 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.464 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.464 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.318 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.464 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.462 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.528 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.289 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.902 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 7.671 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.608 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 44814709.89 | 0.00 | 44814709.89 | 0.00 | 44814709.89 | 26946214.98 | 37.13 | 27.00 | 8695.88 | 0.00 |
RETAIL_1_FLR_1 | 5538301.86 | 0.00 | 5538301.86 | 305216.72 | 5843518.58 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3959273.45 | 0.00 | 3959273.45 | 117814.04 | 4077087.49 | 2892943.94 | 30.02 | 15.58 | 8714.40 | 0.00 |
MECH_FLR_1 | 3341589.53 | 0.00 | 3341589.53 | 278442.40 | 3620031.93 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2106022.24 | 0.00 | 2106022.24 | 160645.93 | 2266668.17 | 1821682.01 | 950.45 | 236.89 | 7572.66 | 0.00 |
LAUNDRY_FLR_1 | 56951722.88 | 0.00 | 56951722.88 | 380198.88 | 57331921.76 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23847867.89 | 0.00 | 23847867.89 | 674698.84 | 24522566.73 | 21330615.53 | 2469.29 | 408.88 | 5881.83 | 0.00 |
LOBBY_FLR_1 | 76989992.98 | 0.00 | 76989992.98 | 1927768.70 | 78917761.68 | 59728886.00 | 73.56 | 18.68 | 8667.76 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 57090.66 | 2003966.28 | 177156.17 | 2181122.46 | 1946875.62 | 0.00 | 7875.61 | 884.39 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 52706.51 | 1999354.03 | 177142.66 | 2176496.69 | 1946647.51 | 0.00 | 7866.25 | 893.75 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 58816.39 | 26456703.66 | 49428.56 | 26506132.22 | 26397887.27 | 0.00 | 7878.50 | 881.50 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 50704.26 | 26455809.99 | 49442.08 | 26505252.07 | 26405105.73 | 0.00 | 7904.87 | 855.13 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 57332.56 | 2004208.18 | 177156.17 | 2181364.35 | 1946875.62 | 0.00 | 7869.33 | 890.67 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 52311.42 | 1998958.93 | 177142.66 | 2176101.59 | 1946647.51 | 0.00 | 7872.08 | 887.92 | 0.00 |
CORRIDOR_FLR_3 | 23287183.71 | 0.00 | 23287183.71 | 214217.46 | 23501401.17 | 14972100.18 | 2.71 | 1.38 | 8755.90 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 64365.93 | 551084.84 | 177191.96 | 728276.80 | 486718.90 | 0.00 | 7886.37 | 873.63 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 59341.23 | 546003.11 | 177178.45 | 723181.55 | 486661.88 | 0.00 | 7869.75 | 890.25 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 66708.61 | 3193629.03 | 90657.61 | 3284286.64 | 3126920.42 | 0.00 | 7869.33 | 890.67 | 0.00 |
BANQUET_FLR_6 | 42565221.43 | 0.00 | 42565221.43 | 432658.25 | 42997879.67 | 37458366.31 | 2796.07 | 370.47 | 5593.46 | 0.00 |
DINING_FLR_6 | 45699657.22 | 0.00 | 45699657.22 | 432658.25 | 46132315.47 | 37458366.31 | 823.76 | 203.00 | 7733.24 | 0.00 |
KITCHEN_FLR_6 | 57773215.78 | 0.00 | 57773215.78 | 387329.44 | 58160545.22 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12277488.00 | 0.00 | 12277488.00 | 379096.44 | 12656584.44 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 9925418.89 | 0.46E+10 | 17852245.51 | 0.46E+10 | 0.43E+10 | 4620.11 | 7958.78 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4211 | 0.0000 | 1.4211 | 0.0000 | 1.4211 | 0.8545 | 37.13 | 27.00 | 8695.88 |
RETAIL_1_FLR_1 | 0.1756 | 0.0000 | 0.1756 | 0.0097 | 0.1853 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1255 | 0.0000 | 0.1255 | 0.0037 | 0.1293 | 0.0917 | 30.02 | 15.58 | 8714.40 |
MECH_FLR_1 | 0.1060 | 0.0000 | 0.1060 | 0.0088 | 0.1148 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0668 | 0.0000 | 0.0668 | 0.0051 | 0.0719 | 0.0578 | 950.45 | 236.89 | 7572.66 |
LAUNDRY_FLR_1 | 1.8059 | 0.0000 | 1.8059 | 0.0121 | 1.8180 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7562 | 0.0000 | 0.7562 | 0.0214 | 0.7776 | 0.6764 | 2469.29 | 408.88 | 5881.83 |
LOBBY_FLR_1 | 2.4413 | 0.0000 | 2.4413 | 0.0611 | 2.5025 | 1.8940 | 73.56 | 18.68 | 8667.76 |
ROOM_1_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0056 | 0.0692 | 0.0617 | 0.00 | 7875.61 | 884.39 |
ROOM_2_FLR_3 | 0.0617 | 0.0017 | 0.0634 | 0.0056 | 0.0690 | 0.0617 | 0.00 | 7866.25 | 893.75 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0016 | 0.8389 | 0.0016 | 0.8405 | 0.8373 | 0.00 | 7904.87 | 855.13 |
ROOM_5_FLR_3 | 0.0617 | 0.0018 | 0.0636 | 0.0056 | 0.0692 | 0.0617 | 0.00 | 7869.33 | 890.67 |
ROOM_6_FLR_3 | 0.0617 | 0.0017 | 0.0634 | 0.0056 | 0.0690 | 0.0617 | 0.00 | 7872.08 | 887.92 |
CORRIDOR_FLR_3 | 0.7384 | 0.0000 | 0.7384 | 0.0068 | 0.7452 | 0.4748 | 2.71 | 1.38 | 8755.90 |
ROOM_1_FLR_6 | 0.0154 | 0.0020 | 0.0175 | 0.0056 | 0.0231 | 0.0154 | 0.00 | 7886.37 | 873.63 |
ROOM_2_FLR_6 | 0.0154 | 0.0019 | 0.0173 | 0.0056 | 0.0229 | 0.0154 | 0.00 | 7869.75 | 890.25 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0021 | 0.1013 | 0.0029 | 0.1041 | 0.0992 | 0.00 | 7869.33 | 890.67 |
BANQUET_FLR_6 | 1.3497 | 0.0000 | 1.3497 | 0.0137 | 1.3635 | 1.1878 | 2796.07 | 370.47 | 5593.46 |
DINING_FLR_6 | 1.4491 | 0.0000 | 1.4491 | 0.0137 | 1.4628 | 1.1878 | 823.76 | 203.00 | 7733.24 |
KITCHEN_FLR_6 | 1.8320 | 0.0000 | 1.8320 | 0.0123 | 1.8443 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3893 | 0.0000 | 0.3893 | 0.0120 | 0.4013 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.4181 | 0.1730 | 80.5911 | 0.4470 | 81.0381 | 73.9670 | 4620.11 | 7958.78 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.48E+09 | 0.00 | 0.48E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 77309717.76 | 519377.59 | 77829095.35 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 15.1253 | 0.0000 | 15.1253 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.4515 | 0.0165 | 2.4679 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 5122.80 | 3637.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 6407.16 | 2352.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 13.9385 | 16.8009 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.4515 | 2.4523 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
Electricity:Building | 2534.18 | 32266.52 | 02-JAN-02:10 | 158241.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 332.05 | 3744.83 | 02-JAN-02:10 | 25084.28 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2527.09 | 32125.38 | 02-JAN-02:10 | 158000.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 868.91 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 868.91 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 868.91 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 868.91 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.95 | 223.93 | 02-JAN-02:10 | 1401.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.94 | 259.31 | 02-JAN-02:10 | 1623.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.64 | 250.98 | 02-JAN-02:10 | 1507.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 7.74 | 88.65 | 02-JAN-02:10 | 581.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 30.68 | 400.53 | 01-JAN-13:10 | 2922.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.34 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.34 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 248.16 | 3061.89 | 02-JAN-02:10 | 18583.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.16 | 950.48 | 02-JAN-02:10 | 8554.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.16 | 950.48 | 02-JAN-02:10 | 8554.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 325.45 | 4437.75 | 01-JAN-02:10 | 23570.01 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 325.54 | 4438.96 | 01-JAN-02:10 | 23576.46 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.35 | 67.90 | 01-JAN-02:10 | 391.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.35 | 67.89 | 01-JAN-02:10 | 391.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 38.55 | 525.67 | 01-JAN-02:10 | 2791.95 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 211.77 | 2631.28 | 02-JAN-02:10 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.91 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.91 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 211.77 | 2631.28 | 02-JAN-02:10 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.91 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.91 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.75 | 1113.22 | 08-DEC-23:30 | 3440.66 | 24-MAR-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2206.82 | 2594.30 | 30-MAR-01:30 | 230218.28 | 28-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.48 | 0.00 | 01-JAN-11:10 | 2021.58 | 24-MAR-06:20 |
MedTempRefrigeration:Refrigeration:Electricity | 34.18 | 941.88 | 26-OCT-03:10 | 1227.84 | 24-MAR-06:20 |
Fans:Electricity | 629.82 | 11783.79 | 16-NOV-03:20 | 50699.91 | 07-SEP-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 851.05 | 13487.06 | 08-JAN-06:00 | 61842.59 | 07-SEP-21:10 |
ExteriorEquipment:Electricity | 650.10 | 9607.53 | 02-JAN-02:20 | 39721.54 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 31.07 | 542.72 | 06-JAN-03:20 | 1847.44 | 18-JAN-21:10 |
ElectricityPurchased:Facility | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
ElectricityPurchased:Plant | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
Cogeneration:ElectricityPurchased | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
General:Cogeneration:ElectricityPurchased | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
ElectricityNet:Plant | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
Cogeneration:ElectricityNet | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
General:Cogeneration:ElectricityNet | 6473.59 | 76349.80 | 15-FEB-04:00 | 460836.76 | 21-JUL-20:00 |
General:Fans:Electricity | 629.82 | 11783.79 | 16-NOV-03:20 | 50699.91 | 07-SEP-21:10 |
ExteriorLights:Electricity | 262.50 | 0.00 | 01-JAN-07:30 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.50 | 0.00 | 01-JAN-07:30 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 190.17 | 0.00 | 01-JAN-14:30 | 9938.94 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 190.17 | 0.00 | 01-JAN-14:30 | 9938.94 | 02-JAN-07:10 |
WaterSystems:Electricity | 90.74 | 1086.56 | 04-MAY-00:20 | 4738.76 | 01-JUN-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 04-MAY-00:20 | 4738.76 | 01-JUN-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1945.46 | 0.00 | 01-JAN-00:10 | 218003.91 | 28-JUN-18:10 |
General:Cooling:Electricity | 1945.46 | 0.00 | 01-JAN-00:10 | 218003.91 | 28-JUN-18:10 |
Pumps:Electricity | 115.96 | 47.91 | 23-JAN-08:10 | 5820.03 | 28-JUN-18:50 |
General:Pumps:Electricity | 115.96 | 47.91 | 23-JAN-08:10 | 5820.03 | 28-JUN-18:50 |
WIRED_LTG_ELECTRICITY | 30.59 | 0.00 | 01-JAN-00:10 | 2518.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4696.00 | 31829.34 | 11-MAR-02:20 | 430129.87 | 06-DEC-22:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2907.16 | 18467.44 | 02-JAN-16:20 | 375865.62 | 06-DEC-22:10 |
WaterSystems:NaturalGas | 2752.58 | 18467.44 | 02-FEB-03:20 | 248721.57 | 13-DEC-22:00 |
Water Heater:WaterSystems:NaturalGas | 2752.58 | 18467.44 | 02-FEB-03:20 | 248721.57 | 13-DEC-22:00 |
Heating:NaturalGas | 154.58 | 0.00 | 02-JAN-13:40 | 133538.56 | 02-FEB-03:40 |
Boiler:Heating:NaturalGas | 154.58 | 0.00 | 02-JAN-13:40 | 133538.56 | 02-FEB-03:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5610.11 | -187.54 | 15-DEC-01:10 | 665623.27 | 10-SEP-22:00 |
PlantLoopCoolingDemand:HVAC | 5610.11 | -187.54 | 15-DEC-01:10 | 665623.27 | 10-SEP-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5610.11 | -187.54 | 15-DEC-01:10 | 665623.27 | 10-SEP-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 11-JAN-02:00 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 11-JAN-02:00 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 27314.06 | 133739.25 | 12-FEB-15:30 | 2536106.74 | 10-SEP-22:00 |
EnergyTransfer:Building | 6233.64 | 68914.68 | 26-FEB-05:10 | 408848.13 | 28-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 747.85 | 8492.13 | 02-FEB-02:20 | 36706.29 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 181.97 | 3959.83 | 04-DEC-23:10 | 10639.91 | 24-MAR-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.99 | 1979.92 | 04-DEC-23:10 | 5319.95 | 24-MAR-06:20 |
General:Refrigeration:EnergyTransfer | 90.99 | 1979.92 | 04-DEC-23:10 | 5319.95 | 24-MAR-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.99 | 1979.92 | 04-DEC-23:10 | 5319.95 | 24-MAR-06:20 |
EnergyTransfer:Plant | 14143.92 | 13725.83 | 08-NOV-03:10 | 1547885.13 | 10-SEP-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.57 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.42 | 1775.64 | 26-OCT-03:10 | 2633.51 | 24-MAR-06:20 |
EnergyTransfer:Zone:BASEMENT | 481.01 | 3009.33 | 24-MAR-06:10 | 30688.02 | 06-DEC-22:20 |
Heating:EnergyTransfer | 15.04 | 0.00 | 01-JAN-08:10 | 26630.85 | 07-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 15.04 | 0.00 | 01-JAN-08:10 | 26630.85 | 07-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6127.62 | 59128.78 | 10-DEC-03:10 | 405315.08 | 28-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 481.01 | 3009.33 | 24-MAR-06:10 | 30688.02 | 06-DEC-22:20 |
General:Cooling:EnergyTransfer | 6127.62 | 59128.78 | 10-DEC-03:10 | 405315.08 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 481.01 | 3009.33 | 24-MAR-06:10 | 30688.02 | 06-DEC-22:20 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 55.98 | 0.26 | 26-MAR-04:20 | 4029.03 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 212.82 | 06-DEC-22:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 212.82 | 06-DEC-22:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 55.98 | 0.00 | 26-MAR-04:30 | 4029.03 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 55.98 | 0.00 | 26-MAR-04:30 | 4029.03 | 02-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.07 | 238.61 | 09-DEC-07:20 | 2679.52 | 28-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 6.39 | 06-DEC-22:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 6.39 | 06-DEC-22:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.07 | 238.61 | 09-DEC-07:20 | 2679.52 | 28-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.07 | 238.61 | 09-DEC-07:20 | 2679.52 | 28-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 34.01 | 14.54 | 09-DEC-07:20 | 2510.24 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 140.55 | 06-DEC-22:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 140.55 | 06-DEC-22:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.01 | 14.54 | 09-DEC-07:20 | 2510.24 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.01 | 14.54 | 09-DEC-07:20 | 2510.24 | 28-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 20.46 | 5.55 | 09-DEC-07:20 | 1407.03 | 28-JUN-18:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 110.15 | 06-DEC-22:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 110.15 | 06-DEC-22:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 20.46 | 0.00 | 10-DEC-03:10 | 1407.03 | 28-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 20.46 | 0.00 | 10-DEC-03:10 | 1407.03 | 28-JUN-18:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.68 | 6945.88 | 13-FEB-04:40 | 40069.18 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.68 | 6945.88 | 13-FEB-04:40 | 40069.18 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.68 | 6945.88 | 13-FEB-04:40 | 40069.18 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 262.88 | 1601.05 | 09-DEC-07:20 | 14312.50 | 01-NOV-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 37.75 | 25-MAR-07:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 37.75 | 25-MAR-07:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 262.88 | 1601.05 | 09-DEC-07:20 | 14312.50 | 01-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 262.88 | 1601.05 | 09-DEC-07:20 | 14312.50 | 01-NOV-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 854.33 | 6304.07 | 09-DEC-07:20 | 51438.58 | 29-DEC-04:20 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 854.33 | 6304.07 | 09-DEC-07:20 | 51438.58 | 29-DEC-04:20 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 854.33 | 6304.07 | 09-DEC-07:20 | 51438.58 | 29-DEC-04:20 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 89.04 | 0.26 | 15-MAR-04:00 | 13129.10 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.44 | 0.00 | 01-JAN-08:10 | 2511.20 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.44 | 0.00 | 01-JAN-08:10 | 2511.20 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 87.60 | 0.00 | 01-JAN-00:10 | 13129.10 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 87.60 | 0.00 | 01-JAN-00:10 | 13129.10 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 80.53 | 0.06 | 02-DEC-24:00 | 13397.63 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 3.11 | 0.00 | 01-JAN-08:10 | 3845.19 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 3.11 | 0.00 | 01-JAN-08:10 | 3845.19 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 77.42 | 0.00 | 01-JAN-00:10 | 13397.63 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 77.42 | 0.00 | 01-JAN-00:10 | 13397.63 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 636.73 | 4479.82 | 13-FEB-06:00 | 53878.26 | 20-NOV-14:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 636.73 | 4479.82 | 13-FEB-06:00 | 53878.26 | 20-NOV-14:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 636.73 | 4479.82 | 13-FEB-06:00 | 53878.26 | 20-NOV-14:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 597.96 | 3.96 | 27-MAR-01:00 | 79315.06 | 16-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.69 | 0.00 | 01-JAN-08:10 | 22837.45 | 07-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.69 | 0.00 | 01-JAN-08:10 | 22837.45 | 07-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 595.26 | 0.00 | 01-JAN-00:10 | 79315.06 | 16-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 595.26 | 0.00 | 01-JAN-00:10 | 79315.06 | 16-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 91.82 | 0.04 | 05-MAR-02:30 | 12180.54 | 06-MAY-09:00 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.48 | 0.00 | 01-JAN-08:10 | 2541.35 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.48 | 0.00 | 01-JAN-08:10 | 2541.35 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 90.33 | 0.00 | 01-JAN-00:10 | 12180.54 | 06-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 90.33 | 0.00 | 01-JAN-00:10 | 12180.54 | 06-MAY-09:00 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 83.10 | 0.03 | 03-JAN-22:30 | 12267.08 | 01-JUL-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 3.05 | 0.00 | 01-JAN-08:10 | 3217.69 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 3.05 | 0.00 | 01-JAN-08:10 | 3217.69 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 80.04 | 0.00 | 01-JAN-00:10 | 12267.08 | 01-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 80.04 | 0.00 | 01-JAN-00:10 | 12267.08 | 01-JUL-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 232.79 | 44.12 | 10-DEC-03:10 | 15146.34 | 28-JUN-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 1018.79 | 06-DEC-22:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 1018.79 | 06-DEC-22:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 232.78 | 44.12 | 10-DEC-03:10 | 15146.34 | 28-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 232.78 | 44.12 | 10-DEC-03:10 | 15146.34 | 28-JUN-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.89 | 0.03 | 06-JAN-03:10 | 3519.21 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.88 | 0.00 | 01-JAN-08:10 | 924.31 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.88 | 0.00 | 01-JAN-08:10 | 924.31 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.01 | 0.00 | 01-JAN-00:10 | 3519.21 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.01 | 0.00 | 01-JAN-00:10 | 3519.21 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.19 | 0.06 | 23-FEB-23:00 | 3589.06 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.64 | 0.00 | 01-JAN-08:10 | 1107.09 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.64 | 0.00 | 01-JAN-08:10 | 1107.09 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.55 | 0.00 | 01-JAN-00:10 | 3589.06 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.55 | 0.00 | 01-JAN-00:10 | 3589.06 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 135.65 | 0.60 | 21-JAN-05:30 | 17297.61 | 28-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.71 | 0.00 | 01-JAN-00:10 | 2396.63 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.71 | 0.00 | 01-JAN-00:10 | 2396.63 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 134.94 | 0.00 | 01-JAN-01:40 | 17297.61 | 28-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 134.94 | 0.00 | 01-JAN-01:40 | 17297.61 | 28-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 481.76 | 6303.74 | 07-DEC-09:40 | 25185.18 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 481.76 | 6303.74 | 07-DEC-09:40 | 25185.18 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 481.76 | 6303.74 | 07-DEC-09:40 | 25185.18 | 28-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 518.61 | 7044.51 | 07-DEC-09:40 | 26377.96 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 518.61 | 7044.51 | 07-DEC-09:40 | 26377.96 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 518.61 | 7044.51 | 07-DEC-09:40 | 26377.96 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 656.86 | 6327.56 | 10-JAN-03:00 | 31618.62 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 656.86 | 6327.56 | 10-JAN-03:00 | 31618.62 | 13-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.32 | 23.31 | 07-DEC-07:20 | 8170.62 | 28-JUN-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 605.96 | 06-DEC-22:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 605.96 | 06-DEC-22:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.30 | 0.00 | 06-DEC-07:10 | 8170.62 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.30 | 0.00 | 06-DEC-07:10 | 8170.62 | 28-JUN-18:20 |
PlantLoopHeatingDemand:Facility | 693.21 | 6298.07 | 24-JUL-01:20 | 154151.32 | 18-DEC-08:00 |
PlantLoopHeatingDemand:Plant | 584.55 | 6298.07 | 24-JUL-01:20 | 46113.05 | 25-JAN-07:50 |
WaterSystems:PlantLoopHeatingDemand | 584.55 | 6298.07 | 24-JUL-01:20 | 46113.05 | 25-JAN-07:50 |
General:WaterSystems:PlantLoopHeatingDemand | 584.55 | 6298.07 | 24-JUL-01:20 | 46113.05 | 25-JAN-07:50 |
EnergyTransfer:HVAC | 6936.50 | 83.81 | 26-MAR-11:20 | 748531.87 | 13-JUL-18:10 |
HeatingCoils:EnergyTransfer | 108.65 | 0.00 | 02-JAN-13:40 | 109644.96 | 10-DEC-07:30 |
PlantLoopHeatingDemand:HVAC | 108.65 | 0.00 | 02-JAN-13:40 | 109644.96 | 10-DEC-07:30 |
HeatingCoils:PlantLoopHeatingDemand | 108.65 | 0.00 | 02-JAN-13:40 | 109644.96 | 10-DEC-07:30 |
CoolingCoils:EnergyTransfer | 5610.11 | -187.54 | 15-DEC-01:10 | 665623.27 | 10-SEP-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 579.28 | 0.00 | 01-JAN-14:30 | 314787.53 | 07-DEC-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 638.46 | 0.00 | 01-JAN-00:10 | 206052.91 | 17-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 584.55 | 6298.07 | 24-JUL-01:20 | 46113.05 | 25-JAN-07:50 |
WaterUse:WaterSystems:EnergyTransfer | 584.55 | 6298.07 | 24-JUL-01:20 | 46113.05 | 25-JAN-07:50 |
Boilers:EnergyTransfer | 107.38 | 0.00 | 02-JAN-13:40 | 107378.65 | 06-DEC-22:10 |
Chillers:EnergyTransfer | 5707.77 | 0.00 | 01-JAN-00:10 | 676525.50 | 10-SEP-22:00 |
HeatRejection:EnergyTransfer | 7653.23 | 0.00 | 01-JAN-00:10 | 843804.15 | 10-SEP-22:00 |
General:HeatRejection:EnergyTransfer | 7653.23 | 0.00 | 01-JAN-00:10 | 843804.15 | 10-SEP-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -481.009 | 0.000 | 0.000 | 137.312 | 188.948 | 143.105 | 0.000 | 0.000 | 0.000 | 11.644 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.007 | -55.976 | 0.000 | 0.000 | 14.531 | 8.760 | 10.186 | 26.354 | 0.000 | 0.906 | 4.502 | 0.000 | -7.822 | 0.000 | -1.449 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -43.071 | 0.000 | 0.000 | 16.136 | 10.144 | 11.795 | 0.000 | 0.000 | 0.353 | 5.269 | 0.000 | 0.000 | 0.000 | -0.626 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.001 | -34.010 | 0.000 | 0.000 | 3.543 | 8.172 | 12.471 | 0.000 | 0.000 | 0.848 | 10.292 | 0.000 | 0.000 | 0.000 | -1.317 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.002 | -20.457 | 0.000 | 0.000 | 2.761 | 4.146 | 3.598 | 0.000 | 0.000 | 0.497 | 10.184 | 0.000 | 0.000 | 0.000 | -0.730 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -618.680 | 0.000 | 0.000 | 10.976 | 5.547 | 658.131 | 0.000 | 0.000 | 1.180 | 0.000 | 0.000 | 0.000 | 0.000 | -2.037 | -55.116 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -262.884 | 0.000 | 0.000 | 181.582 | 16.344 | 14.341 | 73.134 | 0.000 | 1.996 | 3.383 | 0.000 | -24.210 | 0.000 | -3.685 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -854.343 | 0.000 | 0.000 | 536.250 | 99.162 | 148.998 | 97.910 | 0.000 | 5.725 | 8.756 | 0.000 | -31.789 | 0.000 | -10.669 | -0.001 |
ROOM_1_FLR_3 | 2.600 | -71.370 | 0.000 | -17.390 | 0.000 | 0.000 | 9.542 | 10.925 | 10.478 | 58.045 | 0.000 | 2.768 | 14.743 | 0.000 | -16.263 | 0.000 | -4.078 | -0.001 |
ROOM_2_FLR_3 | 4.997 | -62.276 | 0.000 | -17.032 | 0.000 | 0.000 | 9.594 | 10.924 | 10.477 | 45.538 | 0.000 | 2.784 | 15.265 | 0.000 | -16.470 | 0.000 | -3.800 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.001 | -362.143 | 0.000 | -274.581 | 0.000 | 0.000 | 0.000 | 130.455 | 194.997 | 327.994 | 0.000 | 12.065 | 110.135 | 0.000 | -99.106 | 0.000 | -39.816 | -0.002 |
ROOM_4_MULT19_FLR_3 | 10.606 | -377.430 | 0.000 | -225.744 | 0.000 | 0.000 | 183.431 | 130.491 | 195.050 | 144.772 | 0.000 | 15.647 | 37.014 | 0.000 | -86.195 | 0.000 | -27.643 | -0.016 |
ROOM_5_FLR_3 | 2.652 | -73.978 | 0.000 | -17.525 | 0.000 | 0.000 | 9.532 | 10.925 | 10.478 | 59.570 | 0.000 | 2.755 | 15.102 | 0.000 | -15.411 | 0.000 | -4.100 | -0.002 |
ROOM_6_FLR_3 | 4.798 | -64.632 | 0.000 | -17.159 | 0.000 | 0.000 | 9.588 | 10.924 | 10.477 | 46.467 | 0.000 | 2.774 | 15.585 | 0.000 | -15.023 | 0.000 | -3.798 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.010 | -232.780 | 0.000 | 0.000 | 112.134 | 91.336 | 0.000 | 51.918 | 0.000 | 2.600 | 0.237 | 0.000 | -21.381 | 0.000 | -4.073 | -0.000 |
ROOM_1_FLR_6 | 1.305 | -18.102 | 0.000 | -4.331 | 0.000 | 0.000 | 2.388 | 2.731 | 2.620 | 14.443 | 0.000 | 0.688 | 3.302 | 0.000 | -4.004 | 0.000 | -1.041 | -0.000 |
ROOM_2_FLR_6 | 2.236 | -15.910 | 0.000 | -4.231 | 0.000 | 0.000 | 2.403 | 2.731 | 2.619 | 11.359 | 0.000 | 0.693 | 3.087 | 0.000 | -4.025 | 0.000 | -0.961 | -0.000 |
ROOM_3_MULT9_FLR_6 | 1.546 | -107.588 | 0.000 | -28.187 | 0.000 | 0.000 | 21.411 | 15.453 | 23.098 | 72.982 | 0.000 | 3.189 | 23.084 | 0.000 | -18.717 | 0.000 | -6.271 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -481.767 | 0.000 | 0.000 | 314.743 | 35.911 | 175.857 | 13.271 | 0.000 | 1.241 | 0.000 | 0.000 | -13.700 | 0.000 | -2.482 | -43.073 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -518.615 | 0.000 | 0.000 | 314.325 | 35.911 | 175.857 | 12.969 | 0.000 | 1.239 | 0.001 | 0.000 | -14.118 | 0.000 | -2.501 | -5.067 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -656.847 | 0.000 | 0.000 | 28.072 | 14.807 | 550.372 | 25.699 | 0.000 | 1.109 | 49.778 | 0.000 | -10.756 | 0.000 | -2.235 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.011 | -123.305 | 0.000 | 0.000 | 29.813 | 24.166 | 0.000 | 24.533 | 0.000 | 1.112 | 55.059 | 0.000 | -9.611 | 0.000 | -1.778 | -0.000 |
Total Facility | 30.742 | -1153.429 | 0.031 | -4989.924 | 0.000 | 0.000 | 1950.066 | 868.913 | 2365.005 | 1106.957 | 0.000 | 62.169 | 396.422 | 0.000 | -408.603 | 0.000 | -125.092 | -103.281 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-DEC-22:00 | 0.00 | 0.00 | 0.00 | -41357.73 | 0.00 | 0.00 | 5826.47 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 12670.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 02-OCT-12:40 | 0.00 | 0.00 | 0.00 | -4029.07 | 0.00 | 0.00 | 150.60 | 198.99 | 252.59 | 4238.63 | 0.00 | 103.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -914.77 |
RETAIL_2_FLR_1 | 28-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2679.18 | 0.00 | 0.00 | 697.63 | 737.37 | 752.15 | 0.00 | 0.00 | 49.75 | 442.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2509.80 | 0.00 | 0.00 | 129.09 | 668.27 | 839.45 | 0.00 | 0.00 | 120.55 | 752.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 28-JUN-18:40 | 0.00 | 0.00 | 0.00 | -1406.82 | 0.00 | 0.00 | 99.30 | 301.36 | 229.41 | 0.00 | 0.00 | 86.57 | 690.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 05-DEC-21:43 | 0.00 | 0.00 | 0.00 | -50367.36 | 0.00 | 0.00 | 457.09 | 403.20 | 41967.83 | 0.00 | 0.00 | 0.00 | 7862.40 | 0.00 | -0.00 | 0.00 | -323.16 | 0.00 |
CAFE_FLR_1 | 12-OCT-02:18 | 0.00 | 0.00 | 0.00 | -23373.96 | 0.00 | 0.00 | 9255.34 | 217.52 | 203.22 | 0.00 | 0.00 | 0.00 | 16813.97 | 0.00 | -2763.92 | 0.00 | -352.16 | 0.00 |
LOBBY_FLR_1 | 07-NOV-05:30 | 0.00 | 0.00 | 0.00 | -80145.48 | 0.00 | 0.00 | 27056.76 | 1900.96 | 3167.12 | 0.00 | 0.00 | 0.00 | 52949.69 | 0.00 | -3869.97 | 0.00 | -1059.09 | 0.00 |
ROOM_1_FLR_3 | 01-JUL-08:61 | 0.00 | -15845.41 | 0.00 | -753.51 | 0.00 | 0.00 | 118.33 | 470.90 | 653.23 | 1032.58 | 0.00 | 88.79 | 14235.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 01-JUL-08:61 | 0.00 | -15980.87 | 0.00 | -769.88 | 0.00 | 0.00 | 116.17 | 470.85 | 653.15 | 1191.64 | 0.00 | 82.93 | 14236.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-NOV-14:30 | 0.00 | -44111.46 | 0.00 | -9764.06 | 0.00 | 0.00 | 0.00 | 2811.47 | 2352.88 | 57333.09 | 0.00 | 469.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9091.65 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -102808.65 | 0.00 | -10060.47 | 0.00 | 0.00 | 2345.70 | 5624.48 | 12159.85 | 9000.37 | 0.00 | 491.09 | 83247.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 06-MAY-08:41 | 0.00 | -15281.60 | 0.00 | -849.75 | 0.00 | 0.00 | 107.49 | 470.90 | 653.23 | 7383.92 | 0.00 | 10.24 | 7505.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 18-MAY-08:11 | 0.00 | -15192.21 | 0.00 | -850.36 | 0.00 | 0.00 | 71.66 | 369.95 | 452.99 | 7993.78 | 0.00 | 59.16 | 7095.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 28-JUN-18:40 | 0.00 | 0.00 | 0.00 | -15144.69 | 0.00 | 0.00 | 4080.39 | 6639.35 | 0.00 | 4285.26 | 0.00 | 460.54 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -320.86 |
ROOM_1_FLR_6 | 01-FEB-17:11 | 0.00 | -4215.14 | 0.00 | -143.91 | 0.00 | 0.00 | 52.65 | 58.86 | 126.43 | 608.46 | 0.00 | 0.00 | 3572.29 | 0.00 | -0.00 | 0.00 | -59.64 | 0.00 |
ROOM_2_FLR_6 | 01-JUL-08:61 | 0.00 | -4150.99 | 0.00 | -187.42 | 0.00 | 0.00 | 29.62 | 117.71 | 163.29 | 307.50 | 0.00 | 22.18 | 3698.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10-NOV-09:51 | 0.00 | -20164.20 | 0.00 | -1326.79 | 0.00 | 0.00 | 165.28 | 523.33 | 998.70 | 10110.69 | 0.00 | 0.00 | 9749.96 | 0.00 | -0.00 | 0.00 | -56.98 | 0.00 |
BANQUET_FLR_6 | 01-FEB-06:43 | 0.00 | 0.00 | 0.00 | -37265.05 | 0.00 | 0.00 | 12168.04 | 1527.93 | 5623.25 | 0.00 | 0.00 | 0.00 | 19997.19 | 0.00 | -1753.66 | 0.00 | -297.70 | 0.00 |
DINING_FLR_6 | 01-FEB-06:43 | 0.00 | 0.00 | 0.00 | -41648.16 | 0.00 | 0.00 | 12167.94 | 1527.93 | 5623.25 | 0.00 | 0.00 | 0.00 | 24401.14 | 0.00 | -1775.36 | 0.00 | -296.74 | 0.00 |
KITCHEN_FLR_6 | 01-DEC-08:08 | 0.00 | 0.00 | 0.00 | -34760.69 | 0.00 | 0.00 | 618.79 | 538.19 | 21760.70 | 1832.97 | 0.00 | 0.00 | 10241.33 | 0.00 | -0.00 | 0.00 | -231.28 | 0.00 |
CORRIDOR_FLR_6 | 28-JUN-18:13 | 0.00 | 0.00 | 0.00 | -8170.96 | 0.00 | 0.00 | 1079.60 | 1756.68 | 0.00 | 1872.24 | 0.00 | 206.96 | 3255.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUN-18:02 | 0.00 | -207042.88 | 0.00 | -235733.25 | 0.00 | 0.00 | 74057.49 | 58948.06 | 120482.43 | 90648.75 | 0.00 | 9731.50 | 88907.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 06-DEC-22:10 | 0.00 | 0.00 | 425.69 | 0.00 | 0.00 | 0.00 | 775.18 | 477.57 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1218.48 | 0.00 | -216.39 | -748.74 |
RETAIL_2_FLR_1 | 06-DEC-22:10 | 0.00 | 0.00 | 12.79 | 0.00 | 0.00 | 0.00 | 794.39 | 553.03 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -92.54 | -1852.67 |
MECH_FLR_1 | 06-DEC-22:10 | 0.00 | 0.00 | 281.11 | 0.00 | 0.00 | 0.00 | 190.36 | 445.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -196.30 | -1339.22 |
STORAGE_FLR_1 | 06-DEC-22:10 | 0.00 | 0.00 | 220.31 | 0.00 | 0.00 | 0.00 | 149.92 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -110.64 | -664.05 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 25-MAR-07:00 | 0.00 | 0.00 | 264.27 | 0.00 | 0.00 | 0.00 | 5565.48 | 228.40 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2405.45 | 0.00 | -415.91 | -3643.21 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-JAN-21:33 | 5698.78 | 384.46 | 0.00 | -384.46 | 0.00 | 0.00 | 336.23 | 840.90 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1605.94 | 0.00 | -192.46 | -5804.48 |
ROOM_2_FLR_3 | 01-FEB-17:13 | 5780.98 | 380.28 | 0.00 | -380.28 | 0.00 | 0.00 | 234.19 | 235.42 | 505.67 | 2039.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -164.19 | -8631.19 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 29-OCT-21:54 | 31159.62 | 5203.33 | 0.00 | -5203.33 | 0.00 | 0.00 | 6647.78 | 8537.16 | 6668.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6962.45 | 0.00 | -832.43 | -45217.98 |
ROOM_5_FLR_3 | 14-JAN-21:33 | 5443.77 | 384.77 | 0.00 | -384.77 | 0.00 | 0.00 | 341.22 | 840.90 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1571.04 | 0.00 | -192.58 | -5589.25 |
ROOM_6_FLR_3 | 14-DEC-17:01 | 5039.69 | 362.59 | 0.00 | -362.59 | 0.00 | 0.00 | 274.48 | 235.42 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1052.27 | 0.00 | -184.08 | -4818.92 |
CORRIDOR_FLR_3 | 06-DEC-22:10 | 0.00 | 0.00 | 2037.76 | 0.00 | 0.00 | 0.00 | 6025.71 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3452.48 | 0.00 | -606.01 | -8984.50 |
ROOM_1_FLR_6 | 09-FEB-09:01 | 1535.73 | 86.46 | 0.00 | -86.46 | 0.00 | 0.00 | 25.85 | 92.50 | 113.26 | 212.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -79.07 | -1900.76 |
ROOM_2_FLR_6 | 06-DEC-09:11 | 1617.99 | 89.57 | 0.00 | -89.57 | 0.00 | 0.00 | 24.66 | 92.49 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -258.80 | 0.00 | -90.78 | -1498.81 |
ROOM_3_MULT9_FLR_6 | 12-FEB-16:02 | 6982.50 | 563.01 | 0.00 | -563.01 | 0.00 | 0.00 | 349.43 | 392.50 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -453.14 | 0.00 | -196.94 | -7562.09 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 06-DEC-22:10 | 0.00 | 0.00 | 1212.04 | 0.00 | 0.00 | 0.00 | 1628.81 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1529.65 | 0.00 | -263.35 | -2365.37 |
Total Facility | 12-FEB-16:02 | -41295.90 | 105473.36 | 0.00 | -105473.36 | 0.00 | 0.00 | 35058.17 | 17735.32 | 71286.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11238.16 | 0.00 | -4650.68 | -66895.04 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 24.9780 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.8517 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.4890 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6647 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1150 | 3.1150 | 1.4547 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3870 | 0.3870 | 0.1807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2817 | 0.2817 | 0.1316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2438 | 0.2438 | 0.1139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1599 | 0.1599 | 0.0747 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6324 | 3.6324 | 1.6963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5974 | 1.5974 | 0.7460 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2650 | 5.2650 | 2.4588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7784 | 1.7784 | 0.8305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4987 | 2.4987 | 1.1669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6146 | 2.6146 | 1.2210 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5058 | 2.5058 | 1.1702 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8982 | 0.8982 | 0.4195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 24.9780 | 24.8517 | 24.9780 | 11.6647 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5575 | 1.5575 | 1.4547 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1935 | 0.1935 | 0.1807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1409 | 0.1409 | 0.1316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1219 | 0.1219 | 0.1139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0800 | 0.0800 | 0.0747 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8162 | 1.8162 | 1.6963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7987 | 0.7987 | 0.7460 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6325 | 2.6325 | 2.4588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8892 | 0.8892 | 0.8305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2493 | 1.2493 | 1.1669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3073 | 1.3073 | 1.2210 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2529 | 1.2529 | 1.1702 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4491 | 0.4491 | 0.4195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.4890 | 11.6647 | 11.6647 | 11.6647 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 120.50 |
Number of hours not met | 120.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 154.58 | 133538.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1945.46 | 218003.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 868.91 | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.50 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.07 | 1847.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 629.82 | 50699.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 115.96 | 5820.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 190.17 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.76 | 2752.58 | 248721.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.48 | 2021.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.18 | 1227.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.93 | 6473.59 |
Natural Gas | 1788.84 | 4696.00 |
Additional | 0.00 | 0.00 |
Total | 3508.76 | 11169.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 76.59 |
Space Heating | 0.00 |
Space Cooling | 171.48 |
Fans (All) | 55.51 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 570.60 |
Subtotal | 570.60 |
Natural Gas [MJ/m2] | |
Space Heating | 13.62 |
Service Water Heating | 242.62 |
Miscellaneous (All) | 413.92 |
Subtotal | 413.92 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.78 |
Space Heating | 1.38 |
Space Cooling | 17.42 |
Fans (All) | 5.64 |
Service Water Heating | 25.46 |
Receptacle Equipment | 30.86 |
Miscellaneous | 11.46 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Average | 8759.98 | 0.02 | 0.00 | 0.00 | 0.00 |
Sum | 192719.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108267.17 | 1.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 1.83 | 0.00 | 0.00 | 0.00 |
Average | 288886.96 | 0.08 | 0.00 | 0.00 | 0.00 |
Sum | 6355513.17 | 1.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8194.17 | 565.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8306.33 | 453.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8275.17 | 484.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8313.00 | 447.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8194.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 565.83 | 0.00 | 0.00 | 0.00 |
Average | 8666.05 | 93.95 | 0.00 | 0.00 | 0.00 |
Sum | 190653.17 | 2066.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59088.17 | 67.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 643628.17 | 66788.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1956094.00 | 159335.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4149.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4149.67 | 4.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4152.33 | 1.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4150.50 | 3.50 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4150.50 | 3.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100295.67 | 62.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4149.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4149.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4149.83 | 4.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1144237.33 | 101477.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1151207.83 | 94507.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108148.50 | 120.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1956094.00 | 159335.00 | 0.00 | 0.00 | 0.00 |
Average | 269687.49 | 19199.55 | 0.00 | 0.00 | 0.00 |
Sum | 5933124.83 | 422390.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387873E+11 | 40914.99 | 01-JAN-01:05 | 5.43 | 1.83 | 0.812818E+10 | 4899.02 | 10-JAN-03:39 | 7.00 | 6.45 |
February | 0.307366E+11 | 35701.87 | 01-FEB-08:63 | 5.67 | 3.96 | 0.703324E+10 | 4837.97 | 01-FEB-03:30 | 5.67 | 3.96 |
March | 0.319078E+11 | 24151.14 | 25-MAR-06:53 | 5.00 | 0.64 | 0.742912E+10 | 4762.92 | 01-MAR-22:10 | 5.00 | 0.64 |
April | 0.332745E+11 | 20428.56 | 21-APR-04:00 | 8.00 | 0.42 | 0.737836E+10 | 4772.04 | 21-APR-22:10 | 20.08 | 6.55 |
May | 0.335021E+11 | 15456.79 | 07-MAY-10:33 | 30.00 | 12.89 | 0.742067E+10 | 4687.50 | 01-MAY-22:10 | 30.00 | 12.89 |
June | 0.344901E+11 | 16596.73 | 28-JUN-18:10 | 40.83 | 17.83 | 0.738531E+10 | 4744.52 | 13-JUN-22:10 | 40.83 | 17.83 |
July | 0.416772E+11 | 22616.49 | 14-JUL-21:00 | 28.00 | 20.32 | 0.814253E+10 | 4837.16 | 07-JUL-22:10 | 28.00 | 20.32 |
August | 0.453914E+11 | 24634.26 | 04-AUG-21:00 | 23.00 | 18.90 | 0.823542E+10 | 4837.10 | 21-AUG-00:20 | 26.00 | 16.49 |
September | 0.489924E+11 | 27487.50 | 28-SEP-21:00 | 28.80 | 14.20 | 0.797489E+10 | 4837.19 | 20-SEP-03:30 | 28.80 | 14.20 |
October | 0.495333E+11 | 39131.28 | 26-OCT-00:36 | 7.33 | 2.70 | 0.823408E+10 | 4929.89 | 26-OCT-01:49 | 8.67 | 2.96 |
November | 0.469214E+11 | 41316.25 | 23-NOV-21:50 | 3.33 | -1.3 | 0.796158E+10 | 4896.45 | 25-NOV-02:39 | 9.67 | 4.25 |
December | 0.457917E+11 | 41355.15 | 06-DEC-22:00 | 3.00 | -3.0 | 0.822635E+10 | 5074.33 | 06-DEC-22:19 | 2.67 | -3.2 |
Annual Sum or Average | 0.481006E+12 | 0.935497E+11 | ||||||||
Minimum of Months | 0.307366E+11 | 15456.79 | 3.00 | -3.0 | 0.703324E+10 | 4687.50 | 2.67 | -3.2 | ||
Maximum of Months | 0.495333E+11 | 41355.15 | 40.83 | 20.32 | 0.823542E+10 | 5074.33 | 40.83 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448406E+10 | 3697.83 | 14-JAN-13:40 | 26.67 | 10.98 | 0.718856E+09 | 471.74 | 19-JAN-22:19 | 14.33 | 6.76 |
February | 0.284135E+10 | 2683.87 | 01-FEB-14:00 | 16.00 | 7.74 | 0.602351E+09 | 441.76 | 28-FEB-22:19 | 12.50 | 9.12 |
March | 0.340742E+10 | 2820.68 | 18-MAR-13:40 | 26.27 | 12.12 | 0.688992E+09 | 487.36 | 16-MAR-21:30 | 26.27 | 12.12 |
April | 0.468729E+10 | 3182.61 | 14-APR-14:10 | 34.17 | 14.15 | 0.756191E+09 | 491.84 | 12-APR-23:10 | 34.17 | 14.15 |
May | 0.486117E+10 | 2715.36 | 31-MAY-18:15 | 35.33 | 13.34 | 0.796292E+09 | 491.86 | 10-MAY-23:10 | 35.33 | 13.34 |
June | 0.568601E+10 | 3558.73 | 28-JUN-18:13 | 40.67 | 17.68 | 0.801080E+09 | 491.86 | 09-JUN-23:19 | 40.67 | 17.68 |
July | 0.565781E+10 | 3299.45 | 21-JUL-18:30 | 38.00 | 19.28 | 0.823634E+09 | 491.85 | 01-JUL-00:10 | 38.00 | 19.28 |
August | 0.582967E+10 | 3716.60 | 28-AUG-12:30 | 37.00 | 20.85 | 0.823607E+09 | 491.84 | 04-AUG-22:10 | 37.00 | 20.85 |
September | 0.559025E+10 | 4001.42 | 28-SEP-13:30 | 36.10 | 16.03 | 0.790282E+09 | 491.84 | 07-SEP-21:19 | 36.10 | 16.03 |
October | 0.507351E+10 | 4029.03 | 02-OCT-12:40 | 34.00 | 19.29 | 0.766022E+09 | 491.86 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.420533E+10 | 3872.29 | 21-NOV-13:40 | 25.00 | 10.74 | 0.692662E+09 | 491.84 | 01-NOV-22:10 | 25.00 | 10.74 |
December | 0.365234E+10 | 3577.35 | 25-DEC-13:00 | 25.00 | 11.61 | 0.682994E+09 | 468.38 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.559762E+11 | 0.894296E+10 | ||||||||
Minimum of Months | 0.284135E+10 | 2683.87 | 16.00 | 7.74 | 0.602351E+09 | 441.76 | 12.50 | 6.76 | ||
Maximum of Months | 0.582967E+10 | 4029.03 | 40.67 | 20.85 | 0.823634E+09 | 491.86 | 40.67 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316837E+10 | 2407.73 | 12-JAN-07:18 | 5.33 | 4.67 | 0.918643E+09 | 571.54 | 12-JAN-23:00 | 9.00 | 6.92 |
February | 0.260573E+10 | 2325.42 | 01-FEB-06:43 | 5.00 | 3.59 | 0.795531E+09 | 570.73 | 27-FEB-23:10 | 8.67 | 6.31 |
March | 0.303209E+10 | 2142.80 | 25-MAR-06:53 | 5.00 | 0.64 | 0.904700E+09 | 569.55 | 22-MAR-21:40 | 5.00 | 0.64 |
April | 0.365814E+10 | 2389.05 | 14-APR-20:50 | 29.33 | 13.37 | 0.926520E+09 | 569.56 | 16-APR-23:10 | 18.83 | 12.52 |
May | 0.396813E+10 | 2343.58 | 19-MAY-20:10 | 30.67 | 12.42 | 0.963971E+09 | 569.57 | 10-MAY-23:19 | 30.67 | 12.42 |
June | 0.436197E+10 | 2679.52 | 28-JUN-20:10 | 36.67 | 15.41 | 0.939738E+09 | 569.56 | 09-JUN-23:19 | 36.67 | 15.41 |
July | 0.432191E+10 | 2544.42 | 20-JUL-20:10 | 35.17 | 18.52 | 0.966219E+09 | 569.55 | 01-JUL-00:10 | 35.17 | 18.52 |
August | 0.430352E+10 | 2578.47 | 15-AUG-20:10 | 34.67 | 18.05 | 0.969866E+09 | 569.55 | 04-AUG-22:10 | 34.67 | 18.05 |
September | 0.398784E+10 | 2535.49 | 07-SEP-21:00 | 33.30 | 19.43 | 0.935508E+09 | 569.55 | 20-SEP-03:20 | 23.80 | 14.15 |
October | 0.360980E+10 | 2357.95 | 05-OCT-20:10 | 26.50 | 13.28 | 0.946045E+09 | 569.57 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.310533E+10 | 2204.84 | 18-NOV-07:02 | 6.33 | 6.24 | 0.891728E+09 | 570.45 | 22-NOV-22:49 | 8.13 | 0.84 |
December | 0.294759E+10 | 2333.80 | 15-DEC-00:55 | 6.00 | 1.03 | 0.888528E+09 | 569.52 | 01-DEC-22:19 | 6.00 | 1.03 |
Annual Sum or Average | 0.430704E+11 | 0.110470E+11 | ||||||||
Minimum of Months | 0.260573E+10 | 2142.80 | 5.00 | 0.64 | 0.795531E+09 | 569.52 | 5.00 | 0.64 | ||
Maximum of Months | 0.436197E+10 | 2679.52 | 36.67 | 19.43 | 0.969866E+09 | 571.54 | 36.67 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223341E+10 | 1960.27 | 12-JAN-07:18 | 5.33 | 4.67 | 0.170416E+09 | 109.31 | 27-JAN-22:10 | 11.83 | 4.49 |
February | 0.189812E+10 | 1867.36 | 01-FEB-06:43 | 5.00 | 3.59 | 0.148484E+09 | 105.45 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.224515E+10 | 1773.16 | 25-MAR-06:53 | 5.00 | 0.64 | 0.171486E+09 | 113.92 | 17-MAR-21:19 | 5.00 | 0.64 |
April | 0.269799E+10 | 1609.88 | 25-APR-21:00 | 27.00 | 14.17 | 0.187174E+09 | 120.46 | 11-APR-22:10 | 27.00 | 14.17 |
May | 0.311852E+10 | 1861.09 | 18-MAY-20:00 | 30.00 | 12.86 | 0.201681E+09 | 120.46 | 10-MAY-23:30 | 30.00 | 12.86 |
June | 0.392099E+10 | 2510.24 | 28-JUN-20:00 | 37.00 | 15.57 | 0.199119E+09 | 120.46 | 09-JUN-23:40 | 37.00 | 15.57 |
July | 0.390087E+10 | 2396.56 | 21-JUL-20:00 | 37.00 | 20.84 | 0.204774E+09 | 120.46 | 07-JUL-22:10 | 37.00 | 20.84 |
August | 0.367756E+10 | 2273.25 | 15-AUG-20:00 | 35.00 | 18.06 | 0.205139E+09 | 120.46 | 21-AUG-00:10 | 26.00 | 16.49 |
September | 0.327850E+10 | 2156.64 | 08-SEP-20:00 | 33.80 | 19.77 | 0.197352E+09 | 120.46 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.274305E+10 | 1975.52 | 02-OCT-20:00 | 27.00 | 20.01 | 0.189294E+09 | 120.46 | 06-OCT-22:10 | 26.00 | 14.45 |
November | 0.225665E+10 | 1771.65 | 05-NOV-02:63 | 7.00 | 3.35 | 0.168563E+09 | 115.48 | 02-NOV-21:10 | 7.00 | 3.35 |
December | 0.203897E+10 | 1833.90 | 15-DEC-00:55 | 6.00 | 1.03 | 0.162806E+09 | 106.85 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.340098E+11 | 0.220629E+10 | ||||||||
Minimum of Months | 0.189812E+10 | 1609.88 | 5.00 | 0.64 | 0.148484E+09 | 105.45 | 5.00 | 0.64 | ||
Maximum of Months | 0.392099E+10 | 2510.24 | 37.00 | 20.84 | 0.205139E+09 | 120.46 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139299E+10 | 1247.61 | 12-JAN-07:18 | 5.33 | 4.67 | 0.127063E+09 | 80.11 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.117821E+10 | 1188.33 | 01-FEB-06:43 | 5.00 | 3.59 | 0.110522E+09 | 78.29 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.139649E+10 | 1125.71 | 25-MAR-06:53 | 5.00 | 0.64 | 0.127716E+09 | 84.07 | 17-MAR-21:40 | 5.00 | 0.64 |
April | 0.169195E+10 | 981.36 | 21-APR-04:00 | 8.00 | 0.42 | 0.139611E+09 | 92.53 | 14-APR-21:40 | 8.00 | 0.42 |
May | 0.188962E+10 | 890.29 | 09-MAY-20:00 | 31.00 | 13.10 | 0.151712E+09 | 92.66 | 11-MAY-21:19 | 25.67 | 12.70 |
June | 0.225930E+10 | 1407.03 | 28-JUN-18:40 | 40.33 | 17.38 | 0.152729E+09 | 92.66 | 09-JUN-23:40 | 40.33 | 17.38 |
July | 0.224738E+10 | 1296.08 | 21-JUL-19:10 | 37.83 | 19.56 | 0.156976E+09 | 92.66 | 07-JUL-22:10 | 37.83 | 19.56 |
August | 0.213208E+10 | 1194.06 | 15-AUG-20:00 | 35.00 | 18.06 | 0.156682E+09 | 92.66 | 10-AUG-22:00 | 35.00 | 18.06 |
September | 0.193217E+10 | 1116.67 | 08-SEP-20:00 | 33.80 | 19.77 | 0.149812E+09 | 92.66 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.169423E+10 | 1160.83 | 25-OCT-05:02 | 6.67 | 1.21 | 0.141328E+09 | 92.66 | 06-OCT-22:10 | 6.67 | 1.21 |
November | 0.141444E+10 | 1127.64 | 05-NOV-02:63 | 7.00 | 3.35 | 0.125315E+09 | 85.08 | 02-NOV-22:10 | 7.00 | 3.35 |
December | 0.122772E+10 | 1157.81 | 27-DEC-05:15 | 6.67 | 2.46 | 0.121742E+09 | 78.67 | 26-DEC-22:30 | 6.67 | 2.46 |
Annual Sum or Average | 0.204566E+11 | 0.166121E+10 | ||||||||
Minimum of Months | 0.117821E+10 | 890.29 | 5.00 | 0.42 | 0.110522E+09 | 78.29 | 5.00 | 0.42 | ||
Maximum of Months | 0.225930E+10 | 1407.03 | 40.33 | 19.77 | 0.156976E+09 | 92.66 | 40.33 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505646E+11 | 38928.07 | 12-JAN-07:56 | 6.00 | 5.01 | 0.608487E+09 | 417.90 | 02-JAN-23:00 | 6.00 | 5.01 |
February | 0.450865E+11 | 44470.61 | 01-FEB-06:43 | 5.00 | 3.59 | 0.548261E+09 | 405.52 | 28-FEB-01:19 | 6.00 | 5.47 |
March | 0.507970E+11 | 39327.67 | 13-MAR-05:10 | 6.10 | 5.26 | 0.610662E+09 | 400.46 | 07-MAR-00:00 | 6.10 | 5.26 |
April | 0.514535E+11 | 39305.46 | 14-APR-20:00 | 31.00 | 13.66 | 0.596606E+09 | 381.78 | 14-APR-21:10 | 28.67 | 13.19 |
May | 0.540250E+11 | 39424.82 | 18-MAY-20:00 | 30.00 | 12.86 | 0.619372E+09 | 381.81 | 11-MAY-21:10 | 30.00 | 12.86 |
June | 0.536763E+11 | 40069.18 | 28-JUN-20:00 | 37.00 | 15.57 | 0.602853E+09 | 381.87 | 23-JUN-21:10 | 37.00 | 15.57 |
July | 0.548369E+11 | 39899.10 | 21-JUL-20:00 | 37.00 | 20.84 | 0.619799E+09 | 381.86 | 07-JUL-21:10 | 37.00 | 20.84 |
August | 0.548391E+11 | 39793.88 | 15-AUG-20:00 | 35.00 | 18.06 | 0.620487E+09 | 382.27 | 09-AUG-21:10 | 35.00 | 18.06 |
September | 0.522628E+11 | 39637.00 | 08-SEP-20:00 | 33.80 | 19.77 | 0.597967E+09 | 381.89 | 19-SEP-21:10 | 28.02 | 15.82 |
October | 0.523130E+11 | 39243.43 | 03-OCT-20:00 | 30.00 | 18.25 | 0.613629E+09 | 381.87 | 05-OCT-21:10 | 24.00 | 13.05 |
November | 0.491832E+11 | 48845.86 | 23-NOV-20:28 | 6.50 | 0.12 | 0.588656E+09 | 476.48 | 23-NOV-22:10 | 3.17 | -1.3 |
December | 0.496385E+11 | 50364.24 | 05-DEC-21:43 | 2.33 | -3.4 | 0.606090E+09 | 551.17 | 06-DEC-22:19 | 2.67 | -3.2 |
Annual Sum or Average | 0.618676E+12 | 0.723287E+10 | ||||||||
Minimum of Months | 0.450865E+11 | 38928.07 | 2.33 | -3.4 | 0.548261E+09 | 381.78 | 2.67 | -3.2 | ||
Maximum of Months | 0.548391E+11 | 50364.24 | 37.00 | 20.84 | 0.620487E+09 | 551.17 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217536E+11 | 19031.51 | 26-JAN-05:20 | 7.33 | 3.97 | 0.107329E+11 | 6699.98 | 26-JAN-05:00 | 8.00 | 4.31 |
February | 0.160848E+11 | 17141.38 | 25-FEB-05:33 | 6.33 | 6.15 | 0.933675E+10 | 6862.87 | 28-FEB-01:19 | 6.00 | 5.47 |
March | 0.182469E+11 | 17068.29 | 13-MAR-03:45 | 6.70 | 5.86 | 0.105104E+11 | 6561.86 | 03-MAR-01:00 | 6.70 | 5.86 |
April | 0.216565E+11 | 12303.42 | 14-APR-21:10 | 28.67 | 13.19 | 0.105395E+11 | 6462.78 | 07-APR-01:19 | 28.67 | 13.19 |
May | 0.223537E+11 | 11867.30 | 09-MAY-21:10 | 28.83 | 12.76 | 0.109078E+11 | 6461.97 | 31-MAY-04:19 | 19.00 | 9.54 |
June | 0.243746E+11 | 13479.92 | 28-JUN-21:10 | 34.67 | 14.46 | 0.106385E+11 | 6462.36 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.249002E+11 | 13378.46 | 21-JUL-21:10 | 33.83 | 20.81 | 0.109544E+11 | 6462.06 | 07-JUL-04:19 | 33.83 | 20.81 |
August | 0.254819E+11 | 13239.96 | 15-AUG-21:10 | 32.67 | 17.73 | 0.109985E+11 | 6462.69 | 04-AUG-22:10 | 32.67 | 17.73 |
September | 0.246476E+11 | 14029.18 | 28-SEP-15:03 | 37.52 | 15.49 | 0.106178E+11 | 6462.64 | 21-SEP-22:10 | 37.52 | 15.49 |
October | 0.233806E+11 | 23382.51 | 12-OCT-02:18 | 8.67 | 3.55 | 0.108491E+11 | 6512.67 | 31-OCT-01:39 | 11.33 | 5.56 |
November | 0.204327E+11 | 14720.96 | 25-NOV-04:23 | 10.00 | 4.16 | 0.103495E+11 | 6520.50 | 25-NOV-04:30 | 10.00 | 4.16 |
December | 0.195677E+11 | 19020.40 | 09-DEC-00:02 | 9.00 | 1.11 | 0.104516E+11 | 6624.49 | 18-DEC-23:10 | 7.00 | 1.94 |
Annual Sum or Average | 0.262881E+12 | 0.126887E+12 | ||||||||
Minimum of Months | 0.160848E+11 | 11867.30 | 6.33 | 1.11 | 0.933675E+10 | 6461.97 | 6.00 | 1.94 | ||
Maximum of Months | 0.254819E+11 | 23382.51 | 37.52 | 20.81 | 0.109985E+11 | 6862.87 | 37.52 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.653248E+11 | 64338.45 | 11-JAN-05:18 | 7.00 | 6.13 | 0.321071E+11 | 20094.43 | 10-JAN-03:39 | 7.00 | 6.13 |
February | 0.535084E+11 | 63414.39 | 26-FEB-04:52 | 7.00 | 7.00 | 0.282939E+11 | 20124.15 | 28-FEB-01:19 | 6.00 | 5.47 |
March | 0.615764E+11 | 66318.38 | 03-MAR-07:10 | 8.17 | 6.62 | 0.317381E+11 | 19440.45 | 03-MAR-01:00 | 8.17 | 6.62 |
April | 0.711045E+11 | 44287.49 | 21-APR-04:08 | 8.00 | 0.42 | 0.313821E+11 | 19186.78 | 07-APR-01:19 | 8.00 | 0.42 |
May | 0.763643E+11 | 41594.53 | 09-MAY-21:10 | 28.83 | 12.76 | 0.324888E+11 | 19185.65 | 26-MAY-03:09 | 21.00 | 13.54 |
June | 0.820967E+11 | 46654.11 | 28-JUN-21:10 | 34.67 | 14.46 | 0.316290E+11 | 19186.09 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.837252E+11 | 45885.96 | 21-JUL-21:10 | 33.83 | 20.81 | 0.325525E+11 | 19185.41 | 07-JUL-04:19 | 33.83 | 20.81 |
August | 0.835721E+11 | 45402.60 | 15-AUG-21:10 | 32.67 | 17.73 | 0.327024E+11 | 19186.12 | 04-AUG-22:10 | 32.67 | 17.73 |
September | 0.794061E+11 | 45362.50 | 07-SEP-21:10 | 32.75 | 19.42 | 0.315683E+11 | 19186.06 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.732857E+11 | 79595.51 | 12-OCT-02:18 | 8.67 | 3.55 | 0.323982E+11 | 19372.90 | 12-OCT-02:49 | 8.17 | 3.48 |
November | 0.635840E+11 | 80186.99 | 07-NOV-05:30 | 7.50 | 1.51 | 0.310647E+11 | 19305.39 | 09-NOV-03:20 | 10.33 | 4.34 |
December | 0.607856E+11 | 80174.20 | 29-DEC-04:20 | 7.00 | 2.27 | 0.315514E+11 | 19734.59 | 06-DEC-22:19 | 7.00 | 2.27 |
Annual Sum or Average | 0.854334E+12 | 0.379476E+12 | ||||||||
Minimum of Months | 0.535084E+11 | 41594.53 | 7.00 | 0.42 | 0.282939E+11 | 19185.41 | 6.00 | 0.42 | ||
Maximum of Months | 0.837252E+11 | 80186.99 | 34.67 | 20.81 | 0.327024E+11 | 20124.15 | 34.67 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.863300E+09 | 3823.20 | 25-JAN-21:31 | 13.67 | 6.96 | 0.101733E+09 | 73.07 | 19-JAN-22:10 | 13.67 | 6.96 |
February | 0.354325E+09 | 4098.18 | 01-FEB-17:11 | 14.67 | 6.54 | 88392990.29 | 62.89 | 09-FEB-22:30 | 15.00 | 8.57 |
March | 0.675422E+09 | 3828.08 | 23-MAR-21:11 | 14.60 | 7.74 | 0.101986E+09 | 76.29 | 17-MAR-21:19 | 14.60 | 7.74 |
April | 0.217647E+10 | 3998.07 | 06-APR-21:51 | 15.00 | 8.04 | 98577569.33 | 79.62 | 06-APR-21:40 | 15.00 | 8.04 |
May | 0.262599E+10 | 4025.45 | 08-MAY-08:61 | 27.17 | 12.22 | 0.100424E+09 | 58.05 | 13-MAY-21:49 | 22.17 | 7.89 |
June | 0.336980E+10 | 4085.91 | 16-JUN-06:41 | 26.50 | 12.19 | 97357172.02 | 56.70 | 28-JUN-04:10 | 26.83 | 14.55 |
July | 0.311229E+10 | 4149.73 | 01-JUL-08:61 | 27.50 | 10.46 | 99626034.85 | 56.70 | 21-JUL-21:00 | 33.00 | 20.21 |
August | 0.302639E+10 | 3996.92 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100551E+09 | 80.42 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.263160E+10 | 3889.47 | 28-SEP-15:01 | 37.52 | 15.49 | 97681588.56 | 77.95 | 21-SEP-21:10 | 37.52 | 15.49 |
October | 0.171152E+10 | 4036.32 | 17-OCT-21:51 | 19.00 | 7.14 | 0.103212E+09 | 78.72 | 17-OCT-21:19 | 19.00 | 7.14 |
November | 0.876181E+09 | 3913.96 | 10-NOV-09:51 | 23.00 | 9.98 | 98522509.93 | 77.93 | 01-NOV-21:40 | 23.00 | 9.98 |
December | 0.477299E+09 | 3996.44 | 14-DEC-17:01 | 13.67 | 5.29 | 98774924.74 | 65.09 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.219006E+11 | 0.118684E+10 | ||||||||
Minimum of Months | 0.354325E+09 | 3823.20 | 13.67 | 5.29 | 88392990.29 | 56.70 | 13.67 | 6.96 | ||
Maximum of Months | 0.336980E+10 | 4149.73 | 37.52 | 15.49 | 0.103212E+09 | 80.42 | 37.52 | 20.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406458E+09 | 3711.53 | 26-JAN-16:01 | 25.00 | 10.57 | 98754758.13 | 67.13 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.182695E+09 | 3746.27 | 01-FEB-17:11 | 14.67 | 6.54 | 86804902.91 | 58.14 | 09-FEB-22:30 | 15.00 | 8.57 |
March | 0.505530E+09 | 3736.99 | 18-MAR-18:01 | 25.13 | 12.09 | 0.100249E+09 | 73.93 | 17-MAR-21:19 | 25.13 | 12.09 |
April | 0.193773E+10 | 3937.56 | 26-APR-21:51 | 16.00 | 9.61 | 98258971.45 | 78.17 | 26-APR-21:40 | 16.00 | 9.61 |
May | 0.255918E+10 | 4028.67 | 20-MAY-08:61 | 26.50 | 11.05 | 0.100507E+09 | 57.63 | 13-MAY-21:49 | 26.50 | 11.05 |
June | 0.340342E+10 | 4132.35 | 16-JUN-06:41 | 26.50 | 12.19 | 97490247.62 | 56.70 | 23-JUN-21:10 | 30.67 | 15.46 |
July | 0.310037E+10 | 4187.68 | 01-JUL-08:61 | 27.50 | 10.46 | 99675652.82 | 56.70 | 21-JUL-21:00 | 33.00 | 20.21 |
August | 0.288478E+10 | 3953.48 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100524E+09 | 80.15 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.238334E+10 | 3831.58 | 28-SEP-15:01 | 37.52 | 15.49 | 97555761.10 | 77.27 | 21-SEP-21:10 | 37.52 | 15.49 |
October | 0.130647E+10 | 3883.67 | 17-OCT-21:51 | 19.00 | 7.14 | 0.101604E+09 | 75.12 | 17-OCT-21:10 | 19.00 | 7.14 |
November | 0.487335E+09 | 3762.12 | 20-NOV-16:01 | 26.83 | 12.13 | 96192660.11 | 73.20 | 01-NOV-21:40 | 26.83 | 12.13 |
December | 0.197608E+09 | 3707.76 | 24-DEC-16:01 | 22.83 | 10.09 | 96017448.51 | 58.73 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.193549E+11 | 0.117363E+10 | ||||||||
Minimum of Months | 0.182695E+09 | 3707.76 | 14.67 | 6.54 | 86804902.91 | 56.70 | 14.48 | 5.13 | ||
Maximum of Months | 0.340342E+10 | 4187.68 | 37.52 | 15.49 | 0.101604E+09 | 80.15 | 37.52 | 20.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.716937E+09 | 680.17 | 14-JAN-13:40 | 26.67 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 26.67 | 10.98 |
February | 0.351324E+09 | 526.49 | 01-FEB-14:20 | 15.67 | 7.45 | 0.00 | 0.00 | 01-FEB-00:10 | 15.67 | 7.45 |
March | 0.393130E+09 | 495.80 | 18-MAR-13:40 | 26.27 | 12.12 | 0.00 | 0.00 | 01-MAR-00:10 | 26.27 | 12.12 |
April | 0.677663E+09 | 511.76 | 14-APR-13:40 | 34.00 | 14.40 | 0.00 | 0.00 | 01-APR-00:10 | 34.00 | 14.40 |
May | 0.694159E+09 | 445.94 | 09-MAY-17:12 | 34.67 | 14.40 | 0.00 | 0.00 | 01-MAY-00:10 | 34.67 | 14.40 |
June | 0.860202E+09 | 545.93 | 28-JUN-19:10 | 39.50 | 16.83 | 0.00 | 0.00 | 01-JUN-00:10 | 39.50 | 16.83 |
July | 0.877829E+09 | 531.05 | 21-JUL-20:20 | 36.00 | 20.94 | 0.00 | 0.00 | 01-JUL-00:10 | 36.00 | 20.94 |
August | 0.914191E+09 | 578.94 | 27-AUG-14:00 | 40.00 | 18.27 | 0.00 | 0.00 | 01-AUG-00:10 | 40.00 | 18.27 |
September | 0.903877E+09 | 659.07 | 28-SEP-13:30 | 36.10 | 16.03 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 16.03 |
October | 0.795439E+09 | 679.74 | 18-OCT-13:30 | 30.50 | 12.03 | 0.00 | 0.00 | 01-OCT-00:10 | 30.50 | 12.03 |
November | 0.618556E+09 | 708.92 | 20-NOV-14:30 | 27.00 | 11.68 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 11.68 |
December | 0.574687E+09 | 675.45 | 25-DEC-13:30 | 25.50 | 11.81 | 0.00 | 0.00 | 01-DEC-00:10 | 25.50 | 11.81 |
Annual Sum or Average | 0.837800E+10 | 0.00 | ||||||||
Minimum of Months | 0.351324E+09 | 445.94 | 15.67 | 7.45 | 0.00 | 0.00 | 15.67 | 7.45 | ||
Maximum of Months | 0.914191E+09 | 708.92 | 40.00 | 20.94 | 0.00 | 0.00 | 40.00 | 20.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281089E+09 | 1319.18 | 24-JAN-21:51 | 13.00 | 6.75 | 96598750.94 | 67.38 | 27-JAN-22:10 | 11.83 | 4.49 |
February | 0.229327E+09 | 1232.07 | 09-FEB-22:51 | 14.00 | 8.26 | 86484844.16 | 62.33 | 09-FEB-22:49 | 14.00 | 8.26 |
March | 0.360315E+09 | 1351.10 | 19-MAR-21:51 | 18.30 | 11.45 | 98323745.40 | 72.00 | 22-MAR-21:10 | 13.35 | 7.10 |
April | 0.699990E+09 | 1395.32 | 30-APR-08:51 | 25.00 | 9.17 | 96238312.15 | 72.33 | 26-APR-21:49 | 25.00 | 9.17 |
May | 0.910448E+09 | 1446.84 | 20-MAY-08:61 | 26.50 | 11.05 | 99598063.82 | 56.69 | 11-MAY-21:10 | 26.50 | 11.05 |
June | 0.116465E+10 | 1472.36 | 11-JUN-08:61 | 26.33 | 12.62 | 96841725.06 | 56.69 | 16-JUN-21:10 | 33.83 | 13.77 |
July | 0.114559E+10 | 1485.13 | 01-JUL-08:61 | 27.50 | 10.46 | 99166472.35 | 56.70 | 18-JUL-21:40 | 30.33 | 19.75 |
August | 0.104958E+10 | 1395.39 | 23-AUG-18:01 | 35.83 | 16.05 | 99809891.33 | 77.14 | 04-AUG-21:10 | 35.83 | 16.05 |
September | 0.917700E+09 | 1392.57 | 28-SEP-15:01 | 37.52 | 15.49 | 96712823.20 | 74.95 | 21-SEP-21:10 | 37.52 | 15.49 |
October | 0.575609E+09 | 1387.67 | 06-OCT-18:01 | 31.67 | 14.16 | 99415703.32 | 71.07 | 11-OCT-21:19 | 15.00 | 6.77 |
November | 0.310348E+09 | 1319.75 | 21-NOV-21:11 | 15.00 | 8.22 | 94206071.80 | 70.26 | 02-NOV-21:00 | 15.00 | 8.22 |
December | 0.187757E+09 | 1300.92 | 26-DEC-21:31 | 15.00 | 7.15 | 95273487.22 | 58.36 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.783241E+10 | 0.115867E+10 | ||||||||
Minimum of Months | 0.187757E+09 | 1232.07 | 13.00 | 6.75 | 86484844.16 | 56.69 | 11.83 | 4.49 | ||
Maximum of Months | 0.116465E+10 | 1485.13 | 37.52 | 16.05 | 99809891.33 | 77.14 | 37.52 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.851268E+09 | 3730.01 | 27-JAN-09:51 | 20.00 | 7.78 | 0.101230E+09 | 71.23 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.428282E+09 | 3363.73 | 01-FEB-17:11 | 14.67 | 6.54 | 88531879.32 | 63.86 | 09-FEB-22:30 | 15.00 | 8.57 |
March | 0.741774E+09 | 3460.88 | 16-MAR-08:51 | 21.10 | 10.40 | 0.101626E+09 | 74.30 | 16-MAR-21:10 | 20.92 | 12.27 |
April | 0.217578E+10 | 4019.54 | 14-APR-08:41 | 26.50 | 12.19 | 99078247.56 | 75.51 | 19-APR-21:40 | 20.33 | 9.05 |
May | 0.264903E+10 | 4032.83 | 06-MAY-08:41 | 25.67 | 11.01 | 0.101843E+09 | 57.56 | 13-MAY-21:49 | 22.17 | 7.89 |
June | 0.342716E+10 | 4021.10 | 13-JUN-08:11 | 26.00 | 10.40 | 97889894.55 | 58.08 | 19-JUN-05:00 | 23.00 | 10.71 |
July | 0.330752E+10 | 4026.50 | 01-JUL-08:61 | 27.50 | 10.46 | 99925003.40 | 56.70 | 21-JUL-22:00 | 32.00 | 19.95 |
August | 0.318241E+10 | 4019.08 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100878E+09 | 80.05 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.270123E+10 | 3732.58 | 15-SEP-08:51 | 25.00 | 16.27 | 98109592.08 | 77.87 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.177744E+10 | 4008.16 | 15-OCT-08:51 | 24.00 | 9.76 | 0.103279E+09 | 77.19 | 17-OCT-21:19 | 20.33 | 7.59 |
November | 0.833778E+09 | 3997.26 | 10-NOV-09:51 | 23.00 | 9.98 | 98080252.44 | 74.91 | 01-NOV-21:40 | 23.00 | 9.98 |
December | 0.508007E+09 | 3649.95 | 25-DEC-09:51 | 18.00 | 8.29 | 98712512.82 | 62.94 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.225837E+11 | 0.118918E+10 | ||||||||
Minimum of Months | 0.428282E+09 | 3363.73 | 14.67 | 6.54 | 88531879.32 | 56.70 | 14.48 | 5.13 | ||
Maximum of Months | 0.342716E+10 | 4032.83 | 27.50 | 16.27 | 0.103279E+09 | 80.05 | 32.00 | 19.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412232E+09 | 3452.30 | 27-JAN-09:51 | 20.00 | 7.78 | 97926346.04 | 65.82 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.245391E+09 | 2978.99 | 26-FEB-09:01 | 11.33 | 8.84 | 86823466.51 | 59.07 | 09-FEB-22:30 | 11.33 | 8.84 |
March | 0.561164E+09 | 3379.36 | 16-MAR-08:51 | 21.10 | 10.40 | 99978253.43 | 72.14 | 16-MAR-21:10 | 20.92 | 12.27 |
April | 0.192746E+10 | 3990.07 | 14-APR-08:41 | 26.50 | 12.19 | 98876814.94 | 74.26 | 19-APR-21:40 | 20.33 | 9.05 |
May | 0.258054E+10 | 4010.66 | 18-MAY-08:11 | 27.67 | 12.65 | 0.101929E+09 | 57.14 | 13-MAY-21:49 | 27.67 | 12.65 |
June | 0.346011E+10 | 4004.40 | 13-JUN-08:11 | 26.00 | 10.40 | 97981402.64 | 58.69 | 19-JUN-05:00 | 23.00 | 10.71 |
July | 0.329466E+10 | 4009.58 | 01-JUL-08:61 | 27.50 | 10.46 | 99959090.05 | 57.07 | 05-JUL-05:00 | 23.00 | 11.31 |
August | 0.303948E+10 | 3993.70 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100862E+09 | 79.80 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.245078E+10 | 3688.19 | 15-SEP-08:51 | 25.00 | 16.27 | 98012303.22 | 77.19 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.135295E+10 | 3906.96 | 17-OCT-08:51 | 24.00 | 9.54 | 0.101835E+09 | 73.71 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.463958E+09 | 3678.15 | 10-NOV-09:51 | 23.00 | 9.98 | 95498794.11 | 71.48 | 02-NOV-21:30 | 23.00 | 9.98 |
December | 0.222339E+09 | 3339.90 | 25-DEC-09:51 | 18.00 | 8.29 | 95640885.37 | 56.69 | 12-DEC-22:10 | 18.00 | 8.29 |
Annual Sum or Average | 0.200111E+11 | 0.117532E+10 | ||||||||
Minimum of Months | 0.222339E+09 | 2978.99 | 11.33 | 7.78 | 86823466.51 | 56.69 | 11.33 | 5.13 | ||
Maximum of Months | 0.346011E+10 | 4010.66 | 27.67 | 16.27 | 0.101929E+09 | 79.80 | 27.67 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419536E+10 | 3574.25 | 12-JAN-07:18 | 5.33 | 4.67 | 0.136481E+10 | 863.62 | 31-JAN-22:19 | 14.27 | 4.94 |
February | 0.340559E+10 | 3437.75 | 01-FEB-06:43 | 5.00 | 3.59 | 0.116293E+10 | 851.41 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.409164E+10 | 3219.41 | 25-MAR-06:53 | 5.00 | 0.64 | 0.134978E+10 | 869.20 | 17-MAR-22:10 | 5.00 | 0.64 |
April | 0.485317E+10 | 2881.72 | 21-APR-04:00 | 8.00 | 0.42 | 0.146779E+10 | 951.84 | 14-APR-21:19 | 8.00 | 0.42 |
May | 0.530780E+10 | 2447.95 | 20-MAY-10:33 | 31.33 | 12.44 | 0.157118E+10 | 951.87 | 10-MAY-23:10 | 31.33 | 12.44 |
June | 0.603782E+10 | 3786.59 | 28-JUN-18:40 | 40.33 | 17.38 | 0.156716E+10 | 951.87 | 09-JUN-23:40 | 40.33 | 17.38 |
July | 0.596087E+10 | 3424.21 | 21-JUL-19:10 | 37.83 | 19.56 | 0.160949E+10 | 951.86 | 07-JUL-22:10 | 37.83 | 19.56 |
August | 0.588321E+10 | 3267.71 | 15-AUG-18:15 | 37.67 | 18.63 | 0.161123E+10 | 951.85 | 04-AUG-22:10 | 37.67 | 18.63 |
September | 0.547036E+10 | 3137.66 | 08-SEP-18:15 | 35.90 | 20.02 | 0.154999E+10 | 951.86 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.499801E+10 | 3348.83 | 25-OCT-05:02 | 6.67 | 1.21 | 0.150828E+10 | 951.86 | 06-OCT-23:19 | 6.67 | 1.21 |
November | 0.418030E+10 | 3255.26 | 05-NOV-02:63 | 7.00 | 3.35 | 0.134152E+10 | 895.35 | 02-NOV-22:10 | 7.00 | 3.35 |
December | 0.381065E+10 | 3370.53 | 30-DEC-00:22 | 5.50 | 1.43 | 0.129140E+10 | 841.92 | 26-DEC-22:40 | 5.50 | 1.43 |
Annual Sum or Average | 0.581948E+11 | 0.173956E+11 | ||||||||
Minimum of Months | 0.340559E+10 | 2447.95 | 5.00 | 0.42 | 0.116293E+10 | 841.92 | 5.00 | 0.42 | ||
Maximum of Months | 0.603782E+10 | 3786.59 | 40.33 | 20.02 | 0.161123E+10 | 951.87 | 40.33 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.759205E+09 | 4006.84 | 26-JAN-16:01 | 25.00 | 10.57 | 0.101588E+09 | 72.15 | 19-JAN-22:10 | 25.00 | 10.57 |
February | 0.298302E+09 | 4359.04 | 01-FEB-17:11 | 14.67 | 6.54 | 88176311.80 | 61.33 | 09-FEB-22:30 | 15.00 | 8.57 |
March | 0.625431E+09 | 4045.99 | 23-MAR-21:11 | 14.60 | 7.74 | 0.102050E+09 | 76.74 | 22-MAR-21:10 | 14.60 | 7.74 |
April | 0.221064E+10 | 4226.39 | 20-APR-21:51 | 17.00 | 5.59 | 98348180.61 | 80.45 | 06-APR-21:30 | 17.00 | 5.59 |
May | 0.268901E+10 | 4184.18 | 08-MAY-08:61 | 27.17 | 12.22 | 0.100052E+09 | 57.11 | 13-MAY-21:49 | 22.17 | 7.89 |
June | 0.354008E+10 | 4227.01 | 16-JUN-06:41 | 26.50 | 12.19 | 97209577.67 | 56.70 | 29-JUN-02:20 | 29.67 | 15.30 |
July | 0.324504E+10 | 4301.63 | 01-JUL-08:61 | 27.50 | 10.46 | 99522391.49 | 56.70 | 20-JUL-21:30 | 32.00 | 18.39 |
August | 0.314540E+10 | 4140.65 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100397E+09 | 80.05 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.267697E+10 | 4111.98 | 28-SEP-15:01 | 37.52 | 15.49 | 97396287.75 | 76.82 | 21-SEP-21:10 | 37.52 | 15.49 |
October | 0.163422E+10 | 4198.61 | 17-OCT-21:51 | 19.00 | 7.14 | 0.102758E+09 | 77.35 | 17-OCT-21:30 | 19.00 | 7.14 |
November | 0.776067E+09 | 4067.68 | 21-NOV-21:11 | 15.00 | 8.22 | 98167271.10 | 77.80 | 01-NOV-21:40 | 15.00 | 8.22 |
December | 0.410377E+09 | 4281.07 | 14-DEC-17:01 | 13.67 | 5.29 | 98541668.95 | 64.50 | 26-DEC-21:30 | 15.00 | 7.09 |
Annual Sum or Average | 0.220107E+11 | 0.118421E+10 | ||||||||
Minimum of Months | 0.298302E+09 | 4006.84 | 13.67 | 5.29 | 88176311.80 | 56.70 | 14.60 | 5.59 | ||
Maximum of Months | 0.354008E+10 | 4359.04 | 37.52 | 15.49 | 0.102758E+09 | 80.45 | 37.52 | 18.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335370E+09 | 3900.21 | 26-JAN-16:01 | 25.00 | 10.57 | 98183524.51 | 64.97 | 19-JAN-22:10 | 25.00 | 10.57 |
February | 0.150399E+09 | 3917.53 | 01-FEB-17:11 | 14.67 | 6.54 | 86405141.50 | 56.69 | 01-FEB-00:20 | 14.67 | 6.54 |
March | 0.457296E+09 | 3939.83 | 18-MAR-18:01 | 25.13 | 12.09 | 0.100083E+09 | 73.98 | 17-MAR-21:19 | 25.13 | 12.09 |
April | 0.196015E+10 | 4121.86 | 20-APR-21:51 | 17.00 | 5.59 | 98033265.59 | 78.07 | 06-APR-21:30 | 17.00 | 5.59 |
May | 0.262132E+10 | 4165.09 | 20-MAY-08:61 | 26.50 | 11.05 | 0.100136E+09 | 56.70 | 13-MAY-21:49 | 26.50 | 11.05 |
June | 0.357552E+10 | 4267.07 | 16-JUN-06:41 | 26.50 | 12.19 | 97338620.44 | 56.70 | 09-JUN-23:49 | 26.50 | 12.19 |
July | 0.323298E+10 | 4338.39 | 01-JUL-08:61 | 27.50 | 10.46 | 99570155.06 | 56.70 | 20-JUL-21:30 | 32.00 | 18.39 |
August | 0.299963E+10 | 4093.88 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100367E+09 | 79.77 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.242013E+10 | 4046.83 | 28-SEP-15:01 | 37.52 | 15.49 | 97269523.74 | 76.10 | 21-SEP-21:10 | 37.52 | 15.49 |
October | 0.122614E+10 | 4026.00 | 17-OCT-21:51 | 19.00 | 7.14 | 0.100954E+09 | 73.61 | 17-OCT-21:10 | 19.00 | 7.14 |
November | 0.405312E+09 | 3964.06 | 20-NOV-16:01 | 26.83 | 12.13 | 95526642.62 | 72.66 | 01-NOV-21:30 | 26.83 | 12.13 |
December | 0.165254E+09 | 3893.15 | 24-DEC-16:01 | 22.83 | 10.09 | 95452656.49 | 56.87 | 26-DEC-21:30 | 15.00 | 7.09 |
Annual Sum or Average | 0.195495E+11 | 0.116932E+10 | ||||||||
Minimum of Months | 0.150399E+09 | 3893.15 | 14.67 | 5.59 | 86405141.50 | 56.69 | 14.67 | 5.59 | ||
Maximum of Months | 0.357552E+10 | 4338.39 | 37.52 | 15.49 | 0.100954E+09 | 79.77 | 37.52 | 18.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111010E+10 | 2257.47 | 25-JAN-21:31 | 13.67 | 6.96 | 0.103912E+09 | 82.57 | 19-JAN-22:10 | 13.67 | 6.96 |
February | 0.511838E+09 | 2290.20 | 01-FEB-17:11 | 14.67 | 6.54 | 89700537.32 | 72.56 | 09-FEB-22:40 | 14.67 | 8.47 |
March | 0.600164E+09 | 2108.40 | 22-MAR-21:21 | 12.45 | 6.77 | 0.102624E+09 | 79.38 | 22-MAR-21:10 | 12.45 | 6.77 |
April | 0.127069E+10 | 2124.77 | 07-APR-21:51 | 19.00 | 9.43 | 97747649.32 | 76.73 | 07-APR-21:30 | 19.00 | 9.43 |
May | 0.135762E+10 | 2141.13 | 20-MAY-08:61 | 26.50 | 11.05 | 99930215.75 | 56.69 | 10-MAY-22:00 | 26.50 | 11.05 |
June | 0.172247E+10 | 2147.34 | 16-JUN-06:41 | 26.50 | 12.19 | 96975732.30 | 56.70 | 29-JUN-21:10 | 34.83 | 16.44 |
July | 0.174533E+10 | 2188.71 | 01-JUL-08:61 | 27.50 | 10.46 | 99457809.84 | 56.70 | 18-JUL-21:19 | 30.67 | 19.71 |
August | 0.178488E+10 | 2105.70 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100359E+09 | 80.08 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.170764E+10 | 2135.66 | 29-SEP-08:21 | 27.75 | 14.34 | 97578894.32 | 78.52 | 21-SEP-21:10 | 27.75 | 14.34 |
October | 0.135898E+10 | 2230.72 | 17-OCT-21:51 | 19.00 | 7.14 | 0.103877E+09 | 81.47 | 31-OCT-21:19 | 15.23 | 7.72 |
November | 0.976481E+09 | 2387.88 | 10-NOV-09:51 | 23.00 | 9.98 | 0.100026E+09 | 83.29 | 01-NOV-21:40 | 23.00 | 9.98 |
December | 0.846876E+09 | 2297.15 | 26-DEC-21:31 | 15.00 | 7.15 | 0.101029E+09 | 75.78 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.149931E+11 | 0.119322E+10 | ||||||||
Minimum of Months | 0.511838E+09 | 2105.70 | 12.45 | 6.54 | 89700537.32 | 56.69 | 12.45 | 6.77 | ||
Maximum of Months | 0.178488E+10 | 2387.88 | 27.75 | 14.34 | 0.103912E+09 | 83.29 | 34.83 | 19.71 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353406E+11 | 31969.81 | 23-JAN-05:00 | 6.00 | 5.01 | 0.191684E+11 | 12418.32 | 10-JAN-03:39 | 6.00 | 5.01 |
February | 0.311404E+11 | 37273.08 | 01-FEB-06:43 | 5.00 | 3.59 | 0.173132E+11 | 12949.35 | 28-FEB-01:19 | 6.00 | 5.47 |
March | 0.364216E+11 | 32115.17 | 24-MAR-03:34 | 7.57 | 5.18 | 0.193057E+11 | 12322.22 | 02-MAR-03:49 | 7.57 | 5.18 |
April | 0.408661E+11 | 26539.71 | 21-APR-04:39 | 8.00 | 0.42 | 0.187076E+11 | 11361.50 | 21-APR-04:19 | 8.00 | 0.42 |
May | 0.445875E+11 | 23533.60 | 09-MAY-21:10 | 28.83 | 12.76 | 0.193488E+11 | 11347.42 | 31-MAY-04:19 | 19.00 | 9.54 |
June | 0.468555E+11 | 25185.18 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187613E+11 | 11377.24 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.476103E+11 | 24852.23 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193101E+11 | 11381.83 | 07-JUL-21:19 | 33.67 | 20.69 |
August | 0.468759E+11 | 24411.36 | 10-AUG-21:20 | 32.67 | 17.86 | 0.193910E+11 | 11363.49 | 15-AUG-22:00 | 30.00 | 16.88 |
September | 0.438834E+11 | 24214.53 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187095E+11 | 11361.95 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.399793E+11 | 31563.51 | 26-OCT-00:36 | 7.33 | 2.70 | 0.192723E+11 | 12099.70 | 26-OCT-02:39 | 7.67 | 2.54 |
November | 0.348564E+11 | 31129.87 | 07-NOV-05:08 | 7.17 | 1.22 | 0.185731E+11 | 11907.37 | 28-NOV-05:10 | 8.70 | 2.33 |
December | 0.333450E+11 | 31807.22 | 15-DEC-23:58 | 5.00 | -0.4 | 0.191043E+11 | 12879.34 | 06-DEC-22:19 | 5.00 | -0.4 |
Annual Sum or Average | 0.481762E+12 | 0.226965E+12 | ||||||||
Minimum of Months | 0.311404E+11 | 23533.60 | 5.00 | -0.4 | 0.173132E+11 | 11347.42 | 5.00 | -0.4 | ||
Maximum of Months | 0.476103E+11 | 37273.08 | 34.33 | 20.69 | 0.193910E+11 | 12949.35 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387449E+11 | 34041.23 | 23-JAN-05:00 | 6.00 | 5.01 | 0.192403E+11 | 12512.14 | 10-JAN-03:39 | 6.00 | 5.01 |
February | 0.344637E+11 | 41657.99 | 01-FEB-06:43 | 5.00 | 3.59 | 0.173940E+11 | 13084.23 | 28-FEB-01:19 | 6.00 | 5.47 |
March | 0.399963E+11 | 33673.46 | 24-MAR-03:34 | 7.57 | 5.18 | 0.193697E+11 | 12396.95 | 02-MAR-03:49 | 7.57 | 5.18 |
April | 0.438041E+11 | 27829.04 | 21-APR-04:39 | 8.00 | 0.42 | 0.187158E+11 | 11366.35 | 21-APR-04:19 | 8.00 | 0.42 |
May | 0.474714E+11 | 24708.59 | 09-MAY-21:20 | 28.67 | 12.70 | 0.193502E+11 | 11359.97 | 19-MAY-21:19 | 28.33 | 11.33 |
June | 0.495540E+11 | 26377.96 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187620E+11 | 11385.69 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.503635E+11 | 26043.03 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193108E+11 | 11389.24 | 07-JUL-21:19 | 33.67 | 20.69 |
August | 0.496311E+11 | 25605.96 | 10-AUG-21:20 | 32.67 | 17.86 | 0.193919E+11 | 11363.27 | 15-AUG-22:00 | 30.00 | 16.88 |
September | 0.465398E+11 | 25380.03 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187106E+11 | 11371.31 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.430396E+11 | 33137.03 | 26-OCT-00:36 | 7.33 | 2.70 | 0.192975E+11 | 12150.96 | 26-OCT-01:30 | 8.00 | 2.85 |
November | 0.381254E+11 | 33049.26 | 18-NOV-06:39 | 6.00 | 6.00 | 0.186334E+11 | 12031.57 | 28-NOV-05:10 | 8.70 | 2.33 |
December | 0.368758E+11 | 33569.34 | 04-DEC-22:58 | 4.00 | -0.6 | 0.192063E+11 | 13067.69 | 06-DEC-22:19 | 2.67 | -3.2 |
Annual Sum or Average | 0.518610E+12 | 0.227383E+12 | ||||||||
Minimum of Months | 0.344637E+11 | 24708.59 | 4.00 | -0.6 | 0.173940E+11 | 11359.97 | 2.67 | -3.2 | ||
Maximum of Months | 0.503635E+11 | 41657.99 | 34.33 | 20.69 | 0.193919E+11 | 13084.23 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522207E+11 | 34220.63 | 10-JAN-08:07 | 8.33 | 7.02 | 0.188434E+11 | 11319.22 | 21-JAN-18:10 | 15.83 | 10.85 |
February | 0.464736E+11 | 34544.56 | 24-FEB-07:18 | 7.33 | 7.15 | 0.170256E+11 | 11319.31 | 18-FEB-18:19 | 7.33 | 7.15 |
March | 0.526420E+11 | 33895.47 | 07-MAR-07:25 | 7.70 | 7.01 | 0.188601E+11 | 11319.67 | 18-MAR-17:19 | 26.63 | 12.71 |
April | 0.549896E+11 | 30574.58 | 30-APR-10:33 | 30.00 | 11.09 | 0.182592E+11 | 11319.67 | 08-APR-17:19 | 30.00 | 11.09 |
May | 0.581306E+11 | 30777.35 | 07-MAY-10:33 | 30.00 | 12.89 | 0.188711E+11 | 11319.66 | 13-MAY-17:19 | 29.67 | 11.30 |
June | 0.587903E+11 | 31591.36 | 18-JUN-10:50 | 35.67 | 17.76 | 0.182662E+11 | 11319.65 | 17-JUN-17:19 | 35.67 | 17.76 |
July | 0.602223E+11 | 31595.29 | 22-JUL-10:50 | 35.83 | 19.54 | 0.188684E+11 | 11319.67 | 29-JUL-17:19 | 35.90 | 19.14 |
August | 0.599012E+11 | 31633.55 | 13-AUG-10:37 | 33.67 | 21.36 | 0.188757E+11 | 11320.03 | 05-AUG-17:19 | 33.67 | 21.36 |
September | 0.567837E+11 | 31433.79 | 09-SEP-10:33 | 33.43 | 20.70 | 0.182618E+11 | 11319.67 | 23-SEP-17:19 | 33.27 | 17.89 |
October | 0.552351E+11 | 34081.30 | 25-OCT-08:00 | 8.00 | 2.12 | 0.188588E+11 | 11319.99 | 07-OCT-17:19 | 8.00 | 2.12 |
November | 0.507869E+11 | 33918.41 | 24-NOV-07:37 | 6.00 | -0.8 | 0.182381E+11 | 11319.24 | 18-NOV-18:19 | 6.00 | -0.8 |
December | 0.506841E+11 | 34763.30 | 01-DEC-08:08 | 8.83 | 3.99 | 0.188354E+11 | 11324.51 | 16-DEC-18:10 | 12.67 | 4.06 |
Annual Sum or Average | 0.656860E+12 | 0.222064E+12 | ||||||||
Minimum of Months | 0.464736E+11 | 30574.58 | 6.00 | -0.8 | 0.170256E+11 | 11319.22 | 6.00 | -0.8 | ||
Maximum of Months | 0.602223E+11 | 34763.30 | 35.83 | 21.36 | 0.188757E+11 | 11324.51 | 35.90 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.825041E+10 | 6214.21 | 13-JAN-02:26 | 6.50 | 5.01 | 0.141382E+10 | 896.18 | 31-JAN-22:19 | 14.27 | 4.94 |
February | 0.675497E+10 | 6581.47 | 01-FEB-06:43 | 5.00 | 3.59 | 0.121744E+10 | 875.79 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.813604E+10 | 5713.45 | 12-MAR-04:45 | 8.20 | 7.30 | 0.141487E+10 | 940.38 | 17-MAR-21:40 | 20.87 | 12.09 |
April | 0.101927E+11 | 6467.52 | 14-APR-15:03 | 35.00 | 14.57 | 0.156328E+10 | 1007.41 | 11-APR-22:10 | 35.00 | 14.57 |
May | 0.114559E+11 | 6144.14 | 09-MAY-15:03 | 35.00 | 14.52 | 0.166869E+10 | 1007.44 | 10-MAY-23:19 | 25.67 | 15.01 |
June | 0.137863E+11 | 8171.16 | 28-JUN-18:13 | 40.67 | 17.68 | 0.165537E+10 | 1007.44 | 09-JUN-23:19 | 40.67 | 17.68 |
July | 0.137111E+11 | 7502.11 | 20-JUL-18:17 | 38.33 | 19.15 | 0.170501E+10 | 1007.43 | 07-JUL-22:10 | 38.33 | 19.15 |
August | 0.134226E+11 | 7537.86 | 11-AUG-15:30 | 38.00 | 21.21 | 0.170621E+10 | 1007.41 | 21-AUG-00:10 | 26.00 | 16.49 |
September | 0.120940E+11 | 7566.47 | 07-SEP-15:03 | 37.28 | 19.77 | 0.163761E+10 | 1007.41 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.101281E+11 | 7114.40 | 02-OCT-13:10 | 34.17 | 19.45 | 0.155962E+10 | 1007.41 | 06-OCT-23:19 | 25.67 | 15.00 |
November | 0.820986E+10 | 6240.33 | 05-NOV-02:63 | 7.00 | 3.35 | 0.138199E+10 | 949.44 | 01-NOV-21:30 | 7.00 | 3.35 |
December | 0.716258E+10 | 6506.86 | 30-DEC-00:22 | 5.50 | 1.43 | 0.134361E+10 | 879.66 | 26-DEC-22:30 | 5.50 | 1.43 |
Annual Sum or Average | 0.123305E+12 | 0.182675E+11 | ||||||||
Minimum of Months | 0.675497E+10 | 5713.45 | 5.00 | 1.43 | 0.121744E+10 | 875.79 | 5.00 | 1.43 | ||
Maximum of Months | 0.137863E+11 | 8171.16 | 40.67 | 21.21 | 0.170621E+10 | 1007.44 | 40.67 | 19.15 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 599570.98 | 301.79 | 02-JAN-06:35 | 5.33 |
February | 1484982.50 | 279.41 | 25-FEB-05:05 | 6.83 |
March | 1387567.39 | 179.85 | 25-MAR-07:00 | 5.00 |
April | 16731.12 | 107.43 | 21-APR-04:27 | 8.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 265404.00 | 206.29 | 13-OCT-06:20 | 8.67 |
November | 602028.14 | 369.86 | 23-NOV-21:40 | 3.67 |
December | 2240578.64 | 425.63 | 06-DEC-22:10 | 2.83 |
Annual Sum or Average | 6596862.78 | |||
Minimum of Months | 0.00 | 0.00 | 2.83 | |
Maximum of Months | 2240578.64 | 425.63 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 3913.00 | 12.79 | 06-DEC-22:10 | 2.83 |
Annual Sum or Average | 3913.00 | |||
Minimum of Months | 0.00 | 0.00 | 2.83 | |
Maximum of Months | 3913.00 | 12.79 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 104625.97 | 202.75 | 02-JAN-06:35 | 5.33 |
February | 330348.96 | 141.61 | 25-FEB-05:05 | 6.83 |
March | 32958.62 | 67.23 | 27-MAR-07:40 | 7.53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 155246.50 | 216.67 | 23-NOV-21:40 | 3.67 |
December | 657515.52 | 281.09 | 06-DEC-22:10 | 2.83 |
Annual Sum or Average | 1280695.58 | |||
Minimum of Months | 0.00 | 0.00 | 2.83 | |
Maximum of Months | 657515.52 | 281.09 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 166352.27 | 134.43 | 02-JAN-06:35 | 5.33 |
February | 499045.61 | 116.07 | 25-FEB-05:05 | 6.83 |
March | 159395.48 | 54.22 | 26-MAR-08:15 | 8.30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 13303.89 | 24.56 | 26-OCT-06:20 | 8.33 |
November | 217236.52 | 184.92 | 23-NOV-21:40 | 3.67 |
December | 701712.49 | 220.30 | 06-DEC-22:10 | 2.83 |
Annual Sum or Average | 1757046.27 | |||
Minimum of Months | 0.00 | 0.00 | 2.83 | |
Maximum of Months | 701712.49 | 220.30 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 29575.39 | 264.26 | 25-MAR-07:00 | 5.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 29575.39 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 29575.39 | 264.26 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32197761.56 | 1424.67 | 14-JAN-21:33 | 13.67 |
February | 82508981.98 | 1280.66 | 09-FEB-09:01 | 8.50 |
March | 50432310.56 | 1255.54 | 26-MAR-08:62 | 7.75 |
April | 1585816.76 | 1353.03 | 11-APR-08:53 | 25.00 |
May | 730184.67 | 1381.23 | 13-MAY-08:53 | 22.00 |
June | 176652.17 | 713.58 | 04-JUN-06:44 | 25.67 |
July | 425811.40 | 903.64 | 01-JUL-08:04 | 27.50 |
August | 372188.99 | 763.91 | 19-AUG-08:14 | 26.00 |
September | 581772.73 | 796.08 | 04-SEP-08:54 | 25.00 |
October | 4297932.12 | 1390.57 | 14-OCT-08:53 | 24.00 |
November | 22071805.61 | 1386.32 | 20-NOV-09:53 | 22.00 |
December | 0.165070E+09 | 1403.54 | 22-DEC-21:13 | 13.33 |
Annual Sum or Average | 0.360451E+09 | |||
Minimum of Months | 176652.17 | 713.58 | 7.75 | |
Maximum of Months | 0.165070E+09 | 1424.67 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101171E+09 | 1341.60 | 04-JAN-20:42 | 12.50 |
February | 0.156816E+09 | 1445.23 | 01-FEB-17:13 | 14.67 |
March | 82077487.71 | 1269.52 | 26-MAR-08:62 | 7.75 |
April | 1856521.01 | 1377.90 | 23-APR-08:53 | 25.00 |
May | 685589.74 | 1379.41 | 13-MAY-08:53 | 22.00 |
June | 209623.78 | 882.20 | 04-JUN-06:44 | 25.67 |
July | 426562.23 | 942.55 | 02-JUL-08:14 | 27.07 |
August | 378052.53 | 722.11 | 19-AUG-08:14 | 26.00 |
September | 725249.61 | 856.85 | 30-SEP-08:14 | 26.60 |
October | 11122471.47 | 1304.83 | 15-OCT-21:53 | 20.00 |
November | 66120623.61 | 1280.34 | 24-NOV-09:02 | 9.00 |
December | 0.355228E+09 | 1353.99 | 06-DEC-09:11 | 7.00 |
Annual Sum or Average | 0.776817E+09 | |||
Minimum of Months | 209623.78 | 722.11 | 7.00 | |
Maximum of Months | 0.355228E+09 | 1445.23 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4889510.30 | 405.48 | 15-JAN-09:03 | 12.67 |
February | 1503887.97 | 403.76 | 28-FEB-19:32 | 14.33 |
March | 2060641.75 | 402.72 | 31-MAR-21:44 | 15.42 |
April | 880763.29 | 389.01 | 27-APR-08:53 | 18.00 |
May | 358670.20 | 374.52 | 01-MAY-08:53 | 22.00 |
June | 29426.09 | 91.93 | 05-JUN-08:07 | 30.17 |
July | 25879.16 | 77.72 | 11-JUL-08:06 | 31.17 |
August | 96761.56 | 372.42 | 29-AUG-08:04 | 26.67 |
September | 161785.70 | 328.51 | 27-SEP-08:54 | 26.60 |
October | 1219223.20 | 409.99 | 29-OCT-21:54 | 15.00 |
November | 2540873.45 | 405.80 | 26-NOV-09:03 | 13.33 |
December | 21675675.89 | 408.28 | 25-DEC-20:53 | 13.00 |
Annual Sum or Average | 35443098.56 | |||
Minimum of Months | 25879.16 | 77.72 | 12.67 | |
Maximum of Months | 21675675.89 | 409.99 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40965131.88 | 1360.92 | 14-JAN-21:33 | 13.67 |
February | 81280865.02 | 1242.72 | 06-FEB-16:03 | 16.00 |
March | 50547956.97 | 1020.82 | 23-MAR-21:14 | 14.60 |
April | 202233.97 | 688.00 | 04-APR-06:14 | 15.67 |
May | 76095.37 | 724.62 | 26-MAY-08:44 | 26.50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 25845.38 | 426.49 | 03-AUG-19:45 | 24.00 |
September | 202055.59 | 740.82 | 03-SEP-21:54 | 23.30 |
October | 2994435.15 | 1068.25 | 26-OCT-21:13 | 14.33 |
November | 28481130.83 | 1280.14 | 05-NOV-21:03 | 13.50 |
December | 0.165785E+09 | 1305.31 | 06-DEC-16:03 | 15.67 |
Annual Sum or Average | 0.370561E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.50 | |
Maximum of Months | 0.165785E+09 | 1360.92 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118517E+09 | 1222.75 | 01-JAN-16:02 | 15.03 |
February | 0.139636E+09 | 1235.05 | 12-FEB-16:02 | 14.00 |
March | 79698973.14 | 1142.96 | 12-MAR-15:03 | 16.18 |
April | 484725.32 | 1049.59 | 21-APR-21:54 | 20.50 |
May | 93558.86 | 733.21 | 26-MAY-08:44 | 26.50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 32635.59 | 410.80 | 03-AUG-19:45 | 24.00 |
September | 180446.09 | 730.73 | 03-SEP-21:54 | 23.30 |
October | 9163254.85 | 1102.34 | 25-OCT-15:03 | 17.00 |
November | 79843518.50 | 1212.32 | 25-NOV-16:01 | 17.00 |
December | 0.335168E+09 | 1259.92 | 14-DEC-17:01 | 13.67 |
Annual Sum or Average | 0.762818E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.67 | |
Maximum of Months | 0.335168E+09 | 1259.92 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 170798.74 | 371.37 | 02-JAN-06:35 | 5.33 |
February | 727433.18 | 238.82 | 25-FEB-05:05 | 6.83 |
March | 111578.66 | 86.77 | 27-MAR-07:40 | 7.53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 180627.09 | 355.33 | 23-NOV-21:40 | 3.67 |
December | 1278631.95 | 509.40 | 06-DEC-22:10 | 2.83 |
Annual Sum or Average | 2469069.63 | |||
Minimum of Months | 0.00 | 0.00 | 2.83 | |
Maximum of Months | 1278631.95 | 509.40 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103314E+09 | 1500.76 | 25-JAN-21:33 | 13.67 |
February | 0.206443E+09 | 1535.74 | 09-FEB-09:01 | 8.50 |
March | 0.122314E+09 | 1509.45 | 26-MAR-08:62 | 7.75 |
April | 2223805.55 | 1432.02 | 24-APR-08:53 | 26.00 |
May | 1715622.77 | 1458.14 | 12-MAY-08:43 | 24.83 |
June | 63130.54 | 397.21 | 24-JUN-06:44 | 26.50 |
July | 298182.33 | 507.71 | 18-JUL-08:04 | 27.17 |
August | 457125.61 | 666.99 | 05-AUG-08:54 | 25.00 |
September | 817537.88 | 1256.75 | 22-SEP-08:53 | 23.80 |
October | 22849661.74 | 1464.26 | 16-OCT-08:53 | 24.00 |
November | 80393988.28 | 1522.24 | 10-NOV-09:53 | 23.00 |
December | 0.342566E+09 | 1519.67 | 07-DEC-09:02 | 6.67 |
Annual Sum or Average | 0.883456E+09 | |||
Minimum of Months | 63130.54 | 397.21 | 6.67 | |
Maximum of Months | 0.342566E+09 | 1535.74 | 27.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255018E+09 | 1519.98 | 01-JAN-09:02 | 5.90 |
February | 0.338164E+09 | 1578.88 | 09-FEB-09:01 | 8.50 |
March | 0.180141E+09 | 1523.97 | 26-MAR-08:62 | 7.75 |
April | 2174037.30 | 1445.69 | 03-APR-21:53 | 22.00 |
May | 1485906.20 | 1477.60 | 14-MAY-08:43 | 25.92 |
June | 90105.63 | 638.35 | 24-JUN-06:44 | 26.50 |
July | 314745.17 | 726.44 | 01-JUL-08:04 | 27.50 |
August | 505596.64 | 695.39 | 05-AUG-08:54 | 25.00 |
September | 892265.85 | 1183.14 | 15-SEP-08:53 | 25.00 |
October | 50230234.50 | 1572.86 | 18-OCT-21:53 | 19.00 |
November | 0.180901E+09 | 1582.39 | 23-NOV-09:11 | 5.90 |
December | 0.633640E+09 | 1618.00 | 06-DEC-09:11 | 7.00 |
Annual Sum or Average | 0.164356E+10 | |||
Minimum of Months | 90105.63 | 638.35 | 5.90 | |
Maximum of Months | 0.633640E+09 | 1618.00 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4738408.84 | 509.09 | 31-JAN-22:04 | 14.48 |
February | 18045589.75 | 775.83 | 12-FEB-16:02 | 14.00 |
March | 17545499.74 | 759.24 | 27-MAR-08:62 | 9.77 |
April | 648002.31 | 745.36 | 08-APR-08:53 | 20.00 |
May | 635773.16 | 771.67 | 23-MAY-08:53 | 26.00 |
June | 252294.59 | 341.77 | 12-JUN-08:04 | 27.33 |
July | 595861.38 | 452.16 | 24-JUL-08:04 | 28.00 |
August | 415346.93 | 458.74 | 08-AUG-08:04 | 27.67 |
September | 266687.38 | 518.54 | 03-SEP-21:54 | 23.30 |
October | 699675.54 | 486.79 | 27-OCT-19:34 | 15.00 |
November | 3908918.86 | 509.19 | 11-NOV-09:54 | 21.80 |
December | 30853706.30 | 509.59 | 02-DEC-22:14 | 13.33 |
Annual Sum or Average | 78605764.77 | |||
Minimum of Months | 252294.59 | 341.77 | 9.77 | |
Maximum of Months | 30853706.30 | 775.83 | 28.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1127267.87 | 747.56 | 02-JAN-06:35 | 5.33 |
February | 2992058.15 | 624.42 | 25-FEB-05:05 | 6.83 |
March | 1273107.73 | 404.96 | 25-MAR-07:00 | 5.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 276881.60 | 333.50 | 26-OCT-06:20 | 8.33 |
November | 1335783.11 | 1018.71 | 23-NOV-21:40 | 3.67 |
December | 4116882.40 | 1211.93 | 06-DEC-22:10 | 2.83 |
Annual Sum or Average | 11121980.86 | |||
Minimum of Months | 0.00 | 0.00 | 2.83 | |
Maximum of Months | 4116882.40 | 1211.93 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160421E+11 | 15451.75 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.144845E+11 | 15451.75 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.160915E+11 | 15451.75 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.154982E+11 | 15451.75 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.160699E+11 | 15451.75 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.155692E+11 | 15451.75 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.159988E+11 | 15451.75 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.160977E+11 | 15451.75 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.155043E+11 | 15451.75 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.160359E+11 | 15451.75 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.155569E+11 | 15451.75 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.159988E+11 | 15451.75 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.188948E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.144845E+11 | 15451.75 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.160977E+11 | 15451.75 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743719E+09 | 716.35 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.671510E+09 | 716.35 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.746011E+09 | 716.35 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.718503E+09 | 716.35 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.745008E+09 | 716.35 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.721798E+09 | 716.35 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.741713E+09 | 716.35 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.746298E+09 | 716.35 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.718790E+09 | 716.35 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.743432E+09 | 716.35 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.721225E+09 | 716.35 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.741713E+09 | 716.35 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.875972E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.671510E+09 | 716.35 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.746298E+09 | 716.35 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861229E+09 | 829.54 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.777612E+09 | 829.54 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.863884E+09 | 829.54 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.832029E+09 | 829.54 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.862722E+09 | 829.54 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.835845E+09 | 829.54 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.858907E+09 | 829.54 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.864216E+09 | 829.54 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.832361E+09 | 829.54 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.860897E+09 | 829.54 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.835182E+09 | 829.54 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.858907E+09 | 829.54 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.101438E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.777612E+09 | 829.54 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.864216E+09 | 829.54 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693793E+09 | 668.27 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.626432E+09 | 668.27 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.695932E+09 | 668.27 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.670270E+09 | 668.27 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.694996E+09 | 668.27 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.673344E+09 | 668.27 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.691922E+09 | 668.27 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.696199E+09 | 668.27 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.670538E+09 | 668.27 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.693526E+09 | 668.27 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.672810E+09 | 668.27 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.691922E+09 | 668.27 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.817168E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.626432E+09 | 668.27 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.696199E+09 | 668.27 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351983E+09 | 339.04 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.317809E+09 | 339.04 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.353068E+09 | 339.04 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.340049E+09 | 339.04 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.352593E+09 | 339.04 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.341609E+09 | 339.04 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.351034E+09 | 339.04 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.353204E+09 | 339.04 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.340185E+09 | 339.04 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.351847E+09 | 339.04 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.341337E+09 | 339.04 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.351034E+09 | 339.04 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.414575E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.317809E+09 | 339.04 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.353204E+09 | 339.04 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.150909E+10 | 1957.67 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.135902E+10 | 1957.67 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.141501E+10 | 1957.67 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.129481E+10 | 1957.67 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.127585E+10 | 1957.67 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.115533E+10 | 1957.67 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.122577E+10 | 1957.67 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.134917E+10 | 1957.67 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.134180E+10 | 1957.67 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.145209E+10 | 1957.67 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.144669E+10 | 1957.67 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.151968E+10 | 1957.67 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.163443E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.115533E+10 | 1957.67 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.151968E+10 | 1957.67 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.847585E+10 | 8554.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.766839E+10 | 8554.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.845777E+10 | 8554.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.809672E+10 | 8554.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.836768E+10 | 8554.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.808231E+10 | 8554.32 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.831896E+10 | 8554.32 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.843449E+10 | 8554.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.813269E+10 | 8554.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.844728E+10 | 8554.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.821393E+10 | 8554.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.846550E+10 | 8554.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.991616E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.766839E+10 | 8554.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.847585E+10 | 8554.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146022E+09 | 132.12 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.131872E+09 | 132.12 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.144861E+09 | 132.12 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.141479E+09 | 132.12 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.145441E+09 | 132.12 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.140357E+09 | 132.12 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.146583E+09 | 132.12 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.144861E+09 | 132.12 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.141518E+09 | 132.12 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.146003E+09 | 132.12 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.140918E+09 | 132.12 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.146602E+09 | 132.12 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.171652E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.131872E+09 | 132.12 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.146602E+09 | 132.12 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.325141E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.290299E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.309412E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.286592E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.285325E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.266811E+10 | 3437.84 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.279760E+10 | 3437.84 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.297999E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.293136E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.318645E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.313050E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.324964E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.359113E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.266811E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.325141E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.325141E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.290299E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.309412E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.286592E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.285325E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.266811E+10 | 3437.84 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.279760E+10 | 3437.84 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.297999E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.293136E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.318645E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.313050E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.324964E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.359113E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.266811E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.325141E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126106E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121504E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125670E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148074E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.160421E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.160915E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.154982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.160699E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.155692E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.155043E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.160359E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.155569E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.188948E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.743719E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2336506.07 | 0.237813E+09 |
February | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245582E+09 |
March | 0.199990E+10 | 0.746011E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6842153.95 | 0.204856E+09 |
April | 0.192973E+10 | 0.718503E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63988131.96 | 66939622.81 |
May | 0.199475E+10 | 0.745008E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109950E+09 | 32335634.53 |
June | 0.193394E+10 | 0.721798E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200148E+09 | 5181887.52 |
July | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185383E+09 | 3144887.77 |
August | 0.199896E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170944E+09 | 4510138.48 |
September | 0.192879E+10 | 0.718790E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118390E+09 | 10962010.48 |
October | 0.199148E+10 | 0.743432E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43388502.42 | 0.113931E+09 |
November | 0.192552E+10 | 0.721225E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4386076.66 | 0.211411E+09 |
December | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 631453.01 | 0.311941E+09 |
Annual Sum or Average | 0.234744E+11 | 0.875972E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906387E+09 | 0.144861E+10 |
Minimum of Months | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3144887.77 |
Maximum of Months | 0.199990E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200148E+09 | 0.311941E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.861229E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1585809.18 | 99653664.62 |
February | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104710E+09 |
March | 0.231589E+10 | 0.863884E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3081473.87 | 90638291.99 |
April | 0.223463E+10 | 0.832029E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25611392.82 | 31534306.17 |
May | 0.230993E+10 | 0.862722E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42493171.29 | 16589215.70 |
June | 0.223950E+10 | 0.835845E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77095922.30 | 2868748.81 |
July | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71193608.27 | 1829413.31 |
August | 0.231480E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65658402.74 | 2804035.26 |
September | 0.223354E+10 | 0.832361E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45831882.90 | 6099016.26 |
October | 0.230614E+10 | 0.860897E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17463888.96 | 49939531.08 |
November | 0.222975E+10 | 0.835182E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2146482.60 | 90190510.57 |
December | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 492592.03 | 0.129203E+09 |
Annual Sum or Average | 0.271834E+11 | 0.101438E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352655E+09 | 0.626059E+09 |
Minimum of Months | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1829413.31 |
Maximum of Months | 0.231589E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77095922.30 | 0.129203E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.693793E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7528458.10 | 0.205374E+09 |
February | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17880.84 | 0.219847E+09 |
March | 0.489771E+09 | 0.695932E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9681721.96 | 0.189883E+09 |
April | 0.472586E+09 | 0.670270E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65233816.74 | 67718725.65 |
May | 0.488511E+09 | 0.694996E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100646E+09 | 37311598.19 |
June | 0.473617E+09 | 0.673344E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180907E+09 | 6773537.72 |
July | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166724E+09 | 4276515.56 |
August | 0.489542E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154183E+09 | 6429834.50 |
September | 0.472357E+09 | 0.670538E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107876E+09 | 13897971.81 |
October | 0.487709E+09 | 0.693526E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44269290.71 | 0.106620E+09 |
November | 0.471555E+09 | 0.672810E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7991245.77 | 0.188113E+09 |
December | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2686616.61 | 0.270438E+09 |
Annual Sum or Average | 0.574883E+10 | 0.817168E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847745E+09 | 0.131668E+10 |
Minimum of Months | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17880.84 | 4276515.56 |
Maximum of Months | 0.489771E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180907E+09 | 0.270438E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.351983E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4590004.52 | 0.114496E+09 |
February | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16367.45 | 0.122781E+09 |
March | 0.376747E+09 | 0.353068E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5917099.59 | 0.105481E+09 |
April | 0.363528E+09 | 0.340049E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39297517.16 | 36457280.63 |
May | 0.375778E+09 | 0.352593E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59764186.77 | 19770990.06 |
June | 0.364321E+09 | 0.341609E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104639E+09 | 3680629.32 |
July | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96624117.92 | 2311523.06 |
August | 0.376571E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89724068.40 | 3284764.32 |
September | 0.363352E+09 | 0.340185E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63421358.10 | 7082119.32 |
October | 0.375161E+09 | 0.351847E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26494535.31 | 58056768.39 |
November | 0.362735E+09 | 0.341337E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4876758.28 | 0.104212E+09 |
December | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636659.80 | 0.152411E+09 |
Annual Sum or Average | 0.442217E+10 | 0.414575E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497001E+09 | 0.730025E+09 |
Minimum of Months | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16367.45 | 2311523.06 |
Maximum of Months | 0.376747E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104639E+09 | 0.152411E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 4363532.89 | 0.324561E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356372E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 8342950.18 | 0.304155E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 83335997.88 | 93999940.72 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.138543E+09 | 44531020.52 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.258269E+09 | 5928492.78 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.241018E+09 | 3969029.71 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.223216E+09 | 6539902.17 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.156258E+09 | 14616867.17 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 58896504.96 | 0.157898E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 6377118.03 | 0.292899E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 1287445.25 | 0.432023E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.117991E+10 | 0.203749E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3969029.71 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.258269E+09 | 0.432023E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.150909E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5128310.02 | 0.593349E+09 |
February | 0.236489E+11 | 0.135902E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621440E+09 |
March | 0.262800E+11 | 0.141501E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13478434.77 | 0.530947E+09 |
April | 0.253579E+11 | 0.129481E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140317E+09 | 0.176994E+09 |
May | 0.262123E+11 | 0.127585E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242826E+09 | 91764122.38 |
June | 0.254132E+11 | 0.115533E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443988E+09 | 16114792.51 |
July | 0.261570E+11 | 0.122577E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408537E+09 | 10314309.93 |
August | 0.262677E+11 | 0.134917E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375806E+09 | 15513916.62 |
September | 0.253456E+11 | 0.134180E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260281E+09 | 33728581.04 |
October | 0.261693E+11 | 0.145209E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95109253.09 | 0.291970E+09 |
November | 0.253025E+11 | 0.144669E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9372834.82 | 0.532824E+09 |
December | 0.261570E+11 | 0.151968E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1324420.73 | 0.770183E+09 |
Annual Sum or Average | 0.308468E+12 | 0.163443E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199617E+10 | 0.368514E+10 |
Minimum of Months | 0.236489E+11 | 0.115533E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10314309.93 |
Maximum of Months | 0.262800E+11 | 0.151968E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443988E+09 | 0.770183E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.847585E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16242691.57 | 0.170072E+10 |
February | 0.702046E+11 | 0.766839E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180343E+10 |
March | 0.780153E+11 | 0.845777E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43827780.55 | 0.155107E+10 |
April | 0.752779E+11 | 0.809672E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412359E+09 | 0.520790E+09 |
May | 0.778146E+11 | 0.836768E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695746E+09 | 0.271711E+09 |
June | 0.754422E+11 | 0.808231E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126539E+10 | 46883588.32 |
July | 0.776503E+11 | 0.831896E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116554E+10 | 30070430.57 |
August | 0.779788E+11 | 0.843449E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107286E+10 | 46598274.76 |
September | 0.752414E+11 | 0.813269E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744735E+09 | 0.100384E+09 |
October | 0.776868E+11 | 0.844728E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275736E+09 | 0.845051E+09 |
November | 0.751137E+11 | 0.821393E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28068787.66 | 0.153690E+10 |
December | 0.776503E+11 | 0.846550E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4644949.41 | 0.221555E+10 |
Annual Sum or Average | 0.915726E+12 | 0.991616E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572515E+10 | 0.106692E+11 |
Minimum of Months | 0.702046E+11 | 0.766839E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30070430.57 |
Maximum of Months | 0.780153E+11 | 0.847585E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126539E+10 | 0.221555E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3107236.11 | 0.127227E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.77 | 0.136976E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5531232.18 | 0.117258E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50954751.65 | 32028639.67 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82571495.54 | 12659203.03 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144086E+09 | 1132361.13 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138935E+09 | 731465.33 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128556E+09 | 1487717.02 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93726714.96 | 3431702.87 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35407738.17 | 58510901.68 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4322145.52 | 0.113813E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 811900.68 | 0.171752E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688012E+09 | 0.777008E+09 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.77 | 731465.33 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144086E+09 | 0.171752E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4353033.55 | 0.121427E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10210.25 | 0.132410E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5991241.72 | 0.113696E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51239148.94 | 31628714.30 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82564532.56 | 12807668.90 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143926E+09 | 1226101.94 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138879E+09 | 772741.31 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128611E+09 | 1480168.48 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93917387.93 | 3313727.44 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36016028.71 | 55714603.00 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5057887.64 | 0.109030E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512350.32 | 0.164687E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692078E+09 | 0.748193E+09 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10210.25 | 772741.31 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143926E+09 | 0.164687E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.146022E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 614244.02 | 41379630.76 |
February | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44030438.72 |
March | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1116201.66 | 37533773.10 |
April | 0.00 | 0.141479E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11366984.63 | 11990045.54 |
May | 0.00 | 0.145441E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18941022.10 | 5879293.76 |
June | 0.00 | 0.140357E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34451444.95 | 849063.89 |
July | 0.00 | 0.146583E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32136925.79 | 548451.63 |
August | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29656448.54 | 817606.61 |
September | 0.00 | 0.141518E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20930908.19 | 1897779.47 |
October | 0.00 | 0.146003E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7912362.49 | 20012518.25 |
November | 0.00 | 0.140918E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 878733.50 | 37000513.92 |
December | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166335.13 | 54604823.81 |
Annual Sum or Average | 0.00 | 0.171652E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158172E+09 | 0.256544E+09 |
Minimum of Months | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548451.63 |
Maximum of Months | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34451444.95 | 54604823.81 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1901870.39 | 33159082.00 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7266.37 | 36781356.02 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2059569.68 | 31077005.72 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15095155.94 | 8385952.89 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23602055.11 | 3421694.79 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40500341.13 | 262343.84 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39102712.86 | 180771.07 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36301478.60 | 334189.81 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26691400.82 | 809882.35 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10792781.00 | 14989866.77 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1948925.64 | 29624733.33 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 701771.85 | 45696731.17 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198705E+09 | 0.204724E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7266.37 | 180771.07 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40500341.13 | 45696731.17 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125941.59 | 0.126991E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1619.81 | 0.137945E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5408243.34 | 0.117978E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50583712.91 | 33924816.70 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81785212.54 | 15179885.99 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143516E+09 | 1713779.06 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138548E+09 | 1034930.98 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128166E+09 | 1934494.42 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93314476.95 | 4202346.97 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35256995.13 | 59445242.52 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4288762.49 | 0.113698E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 796259.28 | 0.172072E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684790E+09 | 0.786119E+09 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1619.81 | 1034930.98 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143516E+09 | 0.172072E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4606221.59 | 0.120749E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1796.30 | 0.133154E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5652591.98 | 0.114565E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50629621.01 | 33644387.66 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81781759.88 | 15337650.83 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143461E+09 | 1842191.45 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138526E+09 | 1084622.06 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128185E+09 | 1927866.26 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93385373.80 | 4059356.79 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35629643.47 | 57112365.11 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5066939.28 | 0.108357E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1657482.69 | 0.164391E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688584E+09 | 0.756224E+09 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1796.30 | 1084622.06 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143461E+09 | 0.164391E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4497129.47 | 0.160978E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26616.07 | 0.168699E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7095980.02 | 0.146207E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49828992.21 | 51481303.01 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78338994.60 | 27475484.73 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139357E+09 | 5012274.59 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128903E+09 | 3170795.22 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119131E+09 | 4664019.28 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83079845.96 | 10194268.42 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32676447.78 | 83695642.37 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5270799.13 | 0.146705E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1675556.18 | 0.209962E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649881E+09 | 0.101825E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26616.07 | 3170795.22 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139357E+09 | 0.209962E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3024829.37 | 0.127743E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1540.09 | 0.137224E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5434492.77 | 0.117935E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50503615.79 | 31950109.52 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82027061.42 | 12360854.23 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143311E+09 | 1031555.67 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138088E+09 | 674805.50 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127751E+09 | 1378946.84 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93062454.38 | 3158152.66 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35126314.62 | 58290895.01 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4250277.83 | 0.113858E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 779465.78 | 0.172055E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683361E+09 | 0.777661E+09 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1540.09 | 674805.50 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143311E+09 | 0.172055E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4443338.13 | 0.121207E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8993.59 | 0.132198E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5856988.45 | 0.113975E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50734863.16 | 31548666.04 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82004491.69 | 12504235.14 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143146E+09 | 1110125.95 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138029E+09 | 710372.65 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127808E+09 | 1372830.04 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93268483.02 | 3055337.14 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35799376.54 | 55167623.03 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5070293.54 | 0.108466E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1559136.95 | 0.164222E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687729E+09 | 0.745537E+09 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8993.59 | 710372.65 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143146E+09 | 0.164222E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1522032.61 | 67536152.51 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 702.65 | 72282078.77 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714915.49 | 61376436.05 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25835122.86 | 16020665.25 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42077975.59 | 6262034.53 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73513142.25 | 480882.01 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70727204.79 | 329655.92 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65401877.39 | 704917.94 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47522543.47 | 1727244.71 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17871666.60 | 30838552.90 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2090394.27 | 60111919.25 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 380760.47 | 90925440.11 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349658E+09 | 0.408596E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 702.65 | 329655.92 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73513142.25 | 90925440.11 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.325141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3528953.79 | 0.390073E+09 |
February | 0.415303E+11 | 0.290299E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425564E+09 |
March | 0.461508E+11 | 0.309412E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7402961.48 | 0.367598E+09 |
April | 0.445315E+11 | 0.286592E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86076581.80 | 0.121124E+09 |
May | 0.460320E+11 | 0.285325E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147488E+09 | 63016080.21 |
June | 0.446286E+11 | 0.266811E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277680E+09 | 11101388.73 |
July | 0.459349E+11 | 0.279760E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254930E+09 | 7160637.52 |
August | 0.461292E+11 | 0.297999E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234736E+09 | 11129619.93 |
September | 0.445099E+11 | 0.293136E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162372E+09 | 23763569.68 |
October | 0.459565E+11 | 0.318645E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59888680.63 | 0.195682E+09 |
November | 0.444343E+11 | 0.313050E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5717203.76 | 0.354241E+09 |
December | 0.459349E+11 | 0.324964E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 974261.58 | 0.511944E+09 |
Annual Sum or Average | 0.541708E+12 | 0.359113E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124079E+10 | 0.248240E+10 |
Minimum of Months | 0.415303E+11 | 0.266811E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7160637.52 |
Maximum of Months | 0.461508E+11 | 0.325141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277680E+09 | 0.511944E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.325141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3131181.25 | 0.393191E+09 |
February | 0.415303E+11 | 0.290299E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429630E+09 |
March | 0.461508E+11 | 0.309412E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7137454.57 | 0.370706E+09 |
April | 0.445315E+11 | 0.286592E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85843487.75 | 0.121387E+09 |
May | 0.460320E+11 | 0.285325E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147414E+09 | 63025989.86 |
June | 0.446286E+11 | 0.266811E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277652E+09 | 11101667.64 |
July | 0.459349E+11 | 0.279760E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254900E+09 | 7160872.66 |
August | 0.461292E+11 | 0.297999E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234694E+09 | 11129988.62 |
September | 0.445099E+11 | 0.293136E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162314E+09 | 23767231.30 |
October | 0.459565E+11 | 0.318645E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59648401.91 | 0.196858E+09 |
November | 0.444343E+11 | 0.313050E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5279684.77 | 0.356908E+09 |
December | 0.459349E+11 | 0.324964E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 795987.30 | 0.516491E+09 |
Annual Sum or Average | 0.541708E+12 | 0.359113E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123881E+10 | 0.250136E+10 |
Minimum of Months | 0.415303E+11 | 0.266811E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7160872.66 |
Maximum of Months | 0.461508E+11 | 0.325141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277652E+09 | 0.516491E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2768280.28 | 0.350904E+09 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385208E+09 |
March | 0.410691E+10 | 0.126106E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 6356729.50 | 0.331427E+09 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 76890179.95 | 0.108246E+09 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.132063E+09 | 56286356.00 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.248708E+09 | 9931668.58 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.228313E+09 | 6406658.99 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.210196E+09 | 9947642.81 |
September | 0.396089E+10 | 0.121504E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.145363E+09 | 21249328.37 |
October | 0.408962E+10 | 0.125670E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 53401804.23 | 0.175598E+09 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4676318.64 | 0.318068E+09 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 680553.16 | 0.461861E+09 |
Annual Sum or Average | 0.482060E+11 | 0.148074E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.110942E+10 | 0.223513E+10 |
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6406658.99 |
Maximum of Months | 0.410691E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.248708E+09 | 0.461861E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5855842.27 | 0.280529E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299364E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10224200.52 | 0.257407E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80190246.24 | 89535325.01 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131955E+09 | 47317606.53 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243932E+09 | 8363935.13 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224261E+09 | 5322039.80 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207086E+09 | 7910869.14 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143770E+09 | 17243285.19 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55469699.18 | 0.141193E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7654327.19 | 0.253600E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1961656.26 | 0.370083E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111236E+10 | 0.177787E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5322039.80 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243932E+09 | 0.370083E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 15451.75 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 15451.75 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 15451.75 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 15451.75 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 15451.75 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 15451.75 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 15451.75 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 15451.75 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 15451.75 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 15451.75 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 15451.75 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 15451.75 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 716.35 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 31-JAN-16:00 | 237.29 | 01-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 716.35 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 184.74 | 01-FEB-07:54 |
March | 1169.53 | 01-MAR-00:10 | 716.35 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 20-MAR-17:00 | 236.45 | 26-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 716.35 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.52 | 14-APR-16:00 | 151.91 | 21-APR-04:08 |
May | 1169.53 | 01-MAY-00:10 | 716.35 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.37 | 31-MAY-17:00 | 111.85 | 01-MAY-04:00 |
June | 1169.53 | 01-JUN-00:10 | 716.35 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 28-JUN-16:00 | 54.31 | 21-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 716.35 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.60 | 19-JUL-13:00 | 56.28 | 01-JUL-05:55 |
August | 1169.53 | 01-AUG-00:10 | 716.35 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.91 | 25-AUG-14:00 | 66.27 | 05-AUG-18:00 |
September | 1169.53 | 01-SEP-00:10 | 716.35 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.70 | 08-SEP-15:00 | 62.60 | 22-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 716.35 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 01-OCT-13:00 | 183.96 | 25-OCT-06:26 |
November | 1169.53 | 01-NOV-00:10 | 716.35 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.30 | 01-NOV-15:00 | 243.47 | 23-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 716.35 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 21-DEC-15:00 | 255.98 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.31 | |||||
Maximum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 255.98 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 829.54 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.35 | 31-JAN-16:00 | 98.01 | 01-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 829.54 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 80.35 | 01-FEB-06:20 |
March | 1354.32 | 01-MAR-00:10 | 829.54 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 | 20-MAR-17:00 | 97.48 | 26-MAR-05:50 |
April | 1354.32 | 01-APR-00:10 | 829.54 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.69 | 14-APR-15:00 | 68.08 | 21-APR-04:08 |
May | 1354.32 | 01-MAY-00:10 | 829.54 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 | 15-MAY-17:00 | 50.58 | 01-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 829.54 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 28-JUN-16:00 | 25.01 | 21-JUN-06:00 |
July | 1354.32 | 01-JUL-00:10 | 829.54 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.92 | 19-JUL-13:00 | 25.19 | 01-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 829.54 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 | 25-AUG-14:00 | 29.52 | 05-AUG-18:00 |
September | 1354.32 | 01-SEP-00:10 | 829.54 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.24 | 08-SEP-15:00 | 31.06 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 829.54 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.29 | 01-OCT-13:00 | 79.71 | 25-OCT-06:28 |
November | 1354.32 | 01-NOV-00:10 | 829.54 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 01-NOV-15:00 | 102.74 | 23-NOV-06:40 |
December | 1354.32 | 01-DEC-00:10 | 829.54 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 21-DEC-15:00 | 106.30 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | |||||
Maximum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 106.30 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 668.27 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.74 | 31-JAN-16:50 | 216.45 | 01-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 668.27 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 18-FEB-14:00 | 178.54 | 01-FEB-07:40 |
March | 286.42 | 01-MAR-00:10 | 668.27 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 20-MAR-17:00 | 219.64 | 26-MAR-04:00 |
April | 286.42 | 01-APR-00:10 | 668.27 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 | 14-APR-15:50 | 151.67 | 21-APR-04:10 |
May | 286.42 | 01-MAY-00:10 | 668.27 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.04 | 15-MAY-17:00 | 114.69 | 01-MAY-04:00 |
June | 286.42 | 01-JUN-00:10 | 668.27 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.77 | 28-JUN-16:00 | 59.12 | 21-JUN-06:00 |
July | 286.42 | 01-JUL-00:10 | 668.27 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.33 | 19-JUL-13:00 | 59.55 | 01-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 668.27 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.83 | 25-AUG-14:00 | 69.53 | 05-AUG-18:00 |
September | 286.42 | 01-SEP-00:10 | 668.27 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.92 | 08-SEP-15:00 | 71.54 | 22-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 668.27 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.82 | 01-OCT-13:00 | 180.73 | 25-OCT-06:28 |
November | 286.42 | 01-NOV-00:10 | 668.27 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.03 | 01-NOV-15:00 | 231.92 | 23-NOV-06:20 |
December | 286.42 | 01-DEC-00:10 | 668.27 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 | 21-DEC-15:00 | 237.06 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 59.12 | |||||
Maximum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 164.77 | 237.06 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 339.04 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 | 31-JAN-17:00 | 124.88 | 01-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 339.04 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 18-FEB-14:00 | 100.12 | 01-FEB-07:40 |
March | 220.32 | 01-MAR-00:10 | 339.04 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 | 20-MAR-17:00 | 124.45 | 26-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 339.04 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.25 | 14-APR-16:40 | 85.01 | 21-APR-04:08 |
May | 220.32 | 01-MAY-00:10 | 339.04 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 | 15-MAY-17:00 | 63.91 | 01-MAY-04:00 |
June | 220.32 | 01-JUN-00:10 | 339.04 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 | 28-JUN-16:00 | 33.43 | 21-JUN-06:00 |
July | 220.32 | 01-JUL-00:10 | 339.04 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 19-JUL-13:00 | 34.19 | 01-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 339.04 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.48 | 25-AUG-14:00 | 37.58 | 05-AUG-18:00 |
September | 220.32 | 01-SEP-00:10 | 339.04 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.69 | 08-SEP-15:00 | 38.98 | 22-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 339.04 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.66 | 01-OCT-13:00 | 101.22 | 25-OCT-06:28 |
November | 220.32 | 01-NOV-00:10 | 339.04 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 | 01-NOV-15:00 | 130.86 | 23-NOV-06:10 |
December | 220.32 | 01-DEC-00:10 | 339.04 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 21-DEC-15:00 | 134.72 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 33.43 | |||||
Maximum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 | 134.72 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 76.04 | 31-JAN-17:00 | 338.71 | 01-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 300.04 | 09-FEB-07:05 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 77.06 | 20-MAR-17:00 | 334.86 | 26-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 153.78 | 14-APR-17:00 | 220.60 | 21-APR-05:50 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 179.16 | 15-MAY-17:00 | 151.33 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 239.12 | 28-JUN-17:00 | 80.72 | 21-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 208.61 | 19-JUL-13:00 | 81.30 | 01-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 228.23 | 25-AUG-17:00 | 95.26 | 05-AUG-18:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 192.90 | 08-SEP-16:00 | 100.68 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 177.78 | 01-OCT-13:00 | 297.38 | 25-OCT-06:26 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 70.37 | 01-NOV-15:20 | 357.29 | 23-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 39.77 | 25-DEC-16:00 | 362.55 | 06-DEC-22:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.72 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 239.12 | 362.55 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1957.67 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 31-JAN-17:00 | 562.49 | 01-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1957.67 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 467.68 | 28-FEB-01:10 |
March | 15368.40 | 01-MAR-00:10 | 1957.67 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.06 | 20-MAR-17:00 | 546.00 | 26-MAR-04:00 |
April | 15368.40 | 01-APR-00:10 | 1957.67 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.78 | 14-APR-16:00 | 396.68 | 21-APR-04:08 |
May | 15368.40 | 01-MAY-00:10 | 1957.67 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.66 | 31-MAY-17:00 | 293.64 | 01-MAY-04:00 |
June | 15368.40 | 01-JUN-00:10 | 1957.67 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.31 | 28-JUN-16:00 | 143.21 | 21-JUN-06:00 |
July | 15368.40 | 01-JUL-00:10 | 1957.67 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.45 | 19-JUL-13:00 | 144.24 | 01-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1957.67 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.04 | 25-AUG-14:00 | 159.58 | 05-AUG-18:00 |
September | 15368.40 | 01-SEP-00:10 | 1957.67 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.11 | 08-SEP-15:00 | 175.13 | 22-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1957.67 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.70 | 01-OCT-13:00 | 439.10 | 25-OCT-06:26 |
November | 15368.40 | 01-NOV-00:10 | 1957.67 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.67 | 01-NOV-15:00 | 573.78 | 23-NOV-06:10 |
December | 15368.40 | 01-DEC-00:10 | 1957.67 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.90 | 21-DEC-15:00 | 615.89 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.21 | |||||
Maximum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 399.31 | 615.89 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 8554.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.77 | 31-JAN-17:00 | 1653.20 | 01-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 8554.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1359.42 | 01-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 8554.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.65 | 20-MAR-17:00 | 1634.54 | 26-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 8554.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.72 | 14-APR-16:00 | 1144.03 | 21-APR-04:05 |
May | 45622.98 | 01-MAY-00:10 | 8554.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 843.27 | 15-MAY-17:00 | 839.83 | 01-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 8554.32 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.85 | 28-JUN-16:00 | 409.26 | 21-JUN-06:00 |
July | 45622.98 | 01-JUL-00:10 | 8554.32 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.09 | 19-JUL-13:00 | 412.20 | 01-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 8554.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.82 | 25-AUG-14:00 | 482.99 | 05-AUG-18:00 |
September | 45622.98 | 01-SEP-00:10 | 8554.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 920.29 | 08-SEP-15:00 | 510.57 | 22-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 8554.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 847.28 | 01-OCT-13:00 | 1324.31 | 25-OCT-06:28 |
November | 45622.98 | 01-NOV-00:10 | 8554.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.45 | 01-NOV-15:00 | 1713.08 | 23-NOV-06:40 |
December | 45622.98 | 01-DEC-00:10 | 8554.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.46 | 21-DEC-15:00 | 1802.94 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.26 | |||||
Maximum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.85 | 1802.94 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 31-JAN-17:00 | 138.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:09 | 106.71 | 28-FEB-06:54 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 16-MAR-15:10 | 138.27 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 | 14-APR-16:00 | 85.69 | 21-APR-04:08 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.65 | 31-MAY-17:00 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.29 | 16-JUN-16:00 | 30.44 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 | 20-JUL-15:10 | 30.23 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.38 | 25-AUG-17:00 | 38.64 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.32 | 08-SEP-15:10 | 34.77 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 03-OCT-16:00 | 106.07 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | 01-NOV-15:10 | 142.34 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.72 | 25-DEC-16:10 | 149.60 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 30.23 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 121.29 | 149.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 31-JAN-16:50 | 138.73 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:06 | 106.70 | 28-FEB-06:54 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 16-MAR-15:08 | 138.26 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.20 | 14-APR-15:09 | 85.69 | 21-APR-04:23 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.65 | 31-MAY-17:00 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.28 | 16-JUN-16:00 | 31.82 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.89 | 20-JUL-15:10 | 31.26 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 25-AUG-16:30 | 37.73 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.37 | 08-SEP-15:10 | 34.67 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 | 03-OCT-16:00 | 106.06 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | 01-NOV-15:10 | 142.33 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 | 25-DEC-16:07 | 149.59 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 31.26 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 121.28 | 149.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 132.12 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.57 | 31-JAN-16:00 | 40.61 | 01-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 132.12 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 33.75 | 01-FEB-07:51 |
March | 0.00 | 01-MAR-00:10 | 132.12 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 16-MAR-15:00 | 38.95 | 26-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 132.12 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 14-APR-16:00 | 26.37 | 21-APR-03:55 |
May | 0.00 | 01-MAY-00:10 | 132.12 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | 31-MAY-17:00 | 19.95 | 01-MAY-03:55 |
June | 0.00 | 01-JUN-00:10 | 132.12 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 | 28-JUN-16:00 | 9.39 | 21-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 132.12 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.36 | 19-JUL-13:00 | 9.13 | 01-JUL-05:55 |
August | 0.00 | 01-AUG-00:10 | 132.12 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 25-AUG-14:00 | 11.16 | 05-AUG-18:00 |
September | 0.00 | 01-SEP-00:10 | 132.12 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 08-SEP-15:00 | 11.14 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 132.12 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 01-OCT-13:00 | 33.21 | 25-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 132.12 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 01-NOV-15:00 | 41.34 | 23-NOV-06:20 |
December | 0.00 | 01-DEC-00:10 | 132.12 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 21-DEC-15:00 | 43.39 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | |||||
Maximum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 | 43.39 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 31-JAN-16:30 | 38.72 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 18-FEB-16:06 | 29.78 | 28-FEB-06:53 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 16-MAR-15:08 | 38.59 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 14-APR-16:00 | 23.92 | 21-APR-04:33 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 31-MAY-17:00 | 16.43 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 28-JUN-16:00 | 8.05 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 20-JUL-15:10 | 7.47 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 25-AUG-16:40 | 9.43 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 08-SEP-15:08 | 9.55 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 03-OCT-16:00 | 29.60 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 | 01-NOV-15:08 | 39.73 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 21-DEC-15:00 | 41.75 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 7.47 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 41.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 31-JAN-16:50 | 138.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:06 | 106.71 | 28-FEB-06:54 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 16-MAR-15:10 | 138.27 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 | 14-APR-16:00 | 85.69 | 21-APR-04:31 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 | 31-MAY-17:00 | 58.88 | 01-MAY-03:55 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | 28-JUN-16:00 | 34.64 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 | 20-JUL-15:10 | 33.03 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.38 | 25-AUG-15:10 | 39.39 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 | 08-SEP-15:10 | 34.75 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 03-OCT-16:00 | 106.67 | 25-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | 01-NOV-15:10 | 142.34 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.72 | 25-DEC-16:08 | 149.60 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 33.03 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | 149.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 31-JAN-16:40 | 138.73 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:10 | 106.70 | 28-FEB-06:54 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 16-MAR-15:07 | 138.26 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 | 14-APR-16:00 | 85.69 | 21-APR-04:34 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.65 | 31-MAY-17:00 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.40 | 28-JUN-16:00 | 35.89 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 | 20-JUL-15:10 | 33.96 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 25-AUG-15:10 | 38.49 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.37 | 08-SEP-15:10 | 34.66 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 | 03-OCT-16:00 | 106.06 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | 01-NOV-15:07 | 142.33 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 | 25-DEC-16:07 | 149.59 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 33.96 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 121.40 | 149.59 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | 31-JAN-16:00 | 166.87 | 01-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 18-FEB-14:00 | 138.54 | 01-FEB-05:03 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.81 | 16-MAR-15:00 | 170.36 | 26-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.89 | 14-APR-17:00 | 118.51 | 21-APR-04:08 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.77 | 15-MAY-17:00 | 87.25 | 01-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.47 | 28-JUN-16:00 | 44.58 | 21-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.40 | 19-JUL-13:00 | 45.33 | 01-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.35 | 25-AUG-14:00 | 50.79 | 05-AUG-18:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.96 | 08-SEP-15:00 | 53.18 | 22-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.06 | 01-OCT-13:00 | 137.80 | 25-OCT-06:28 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 | 01-NOV-15:00 | 179.81 | 23-NOV-06:03 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 | 21-DEC-15:00 | 184.55 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 44.58 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.47 | 184.55 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 31-JAN-17:00 | 139.17 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 18-FEB-16:10 | 107.12 | 28-FEB-06:54 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 | 16-MAR-15:10 | 138.69 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.87 | 14-APR-16:00 | 86.10 | 21-APR-04:33 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.32 | 31-MAY-17:00 | 59.28 | 01-MAY-03:55 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 16-JUN-16:00 | 28.23 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.56 | 20-JUL-15:10 | 28.29 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.05 | 25-AUG-15:10 | 37.92 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.91 | 08-SEP-16:00 | 32.19 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 03-OCT-16:00 | 106.48 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.31 | 01-NOV-15:10 | 142.77 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 25-DEC-16:08 | 150.03 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 28.23 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 150.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 31-JAN-16:50 | 139.16 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 18-FEB-16:06 | 107.12 | 28-FEB-06:54 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 | 16-MAR-15:10 | 138.68 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.87 | 14-APR-16:00 | 86.09 | 21-APR-04:33 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.31 | 31-MAY-17:00 | 59.27 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.94 | 16-JUN-16:00 | 29.63 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.56 | 20-JUL-15:10 | 29.31 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.04 | 25-AUG-17:00 | 36.88 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 08-SEP-15:10 | 32.16 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.08 | 03-OCT-16:00 | 106.47 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.31 | 01-NOV-15:10 | 142.76 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 25-DEC-16:07 | 150.02 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 29.31 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.94 | 150.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 31-JAN-17:00 | 71.20 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 18-FEB-16:07 | 54.81 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 | 16-MAR-15:10 | 70.96 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 14-APR-15:50 | 44.05 | 21-APR-04:31 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 | 31-MAY-17:00 | 30.33 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 28-JUN-16:00 | 13.76 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 | 20-JUL-15:10 | 13.32 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 | 25-AUG-16:10 | 18.77 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 | 08-SEP-16:00 | 17.02 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 03-OCT-16:00 | 54.48 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | 01-NOV-15:10 | 73.05 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 25-DEC-16:10 | 76.76 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 13.32 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 76.76 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 | 31-JAN-17:00 | 387.14 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 314.57 | 28-FEB-01:10 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 16-MAR-15:00 | 385.81 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.06 | 14-APR-16:00 | 264.70 | 21-APR-04:05 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.21 | 31-MAY-17:00 | 190.05 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 28-JUN-16:00 | 93.38 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.03 | 19-JUL-13:00 | 94.06 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.24 | 25-AUG-14:00 | 109.94 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.09 | 08-SEP-15:00 | 116.13 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 | 01-OCT-13:00 | 312.03 | 25-OCT-06:26 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 01-NOV-15:00 | 396.02 | 23-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 | 21-DEC-15:00 | 413.89 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.38 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 413.89 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 | 31-JAN-17:00 | 387.14 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 316.49 | 28-FEB-01:10 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 16-MAR-15:00 | 385.81 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.06 | 14-APR-16:00 | 265.53 | 21-APR-04:05 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.21 | 31-MAY-17:00 | 190.05 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 28-JUN-16:00 | 93.39 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.03 | 19-JUL-13:00 | 94.06 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.24 | 25-AUG-14:00 | 109.94 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.09 | 08-SEP-15:00 | 116.13 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 | 01-OCT-13:00 | 313.15 | 25-OCT-06:26 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 01-NOV-15:00 | 396.04 | 23-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 21-DEC-15:00 | 413.89 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.39 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 413.89 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 65.51 | 31-JAN-16:40 | 346.49 | 01-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 305.62 | 03-FEB-07:15 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 62.54 | 16-MAR-15:40 | 345.32 | 26-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 141.68 | 14-APR-15:40 | 242.72 | 21-APR-04:37 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 166.87 | 31-MAY-17:00 | 169.71 | 01-MAY-04:00 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 228.10 | 28-JUN-16:00 | 83.54 | 21-JUN-05:55 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 205.17 | 19-JUL-13:00 | 84.14 | 01-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 216.97 | 25-AUG-14:00 | 98.26 | 05-AUG-18:00 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 183.72 | 08-SEP-15:00 | 103.90 | 22-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 167.42 | 01-OCT-13:00 | 300.41 | 25-OCT-06:26 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 65.18 | 01-NOV-15:00 | 359.06 | 23-NOV-22:00 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 25.67 | 21-DEC-15:00 | 370.45 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 228.10 | 370.45 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.04 | 31-JAN-17:00 | 296.16 | 01-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 236.99 | 01-FEB-05:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.52 | 15-MAR-15:00 | 295.16 | 26-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.45 | 14-APR-15:00 | 199.64 | 21-APR-04:08 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.11 | 31-MAY-17:00 | 151.33 | 01-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.06 | 28-JUN-16:00 | 75.32 | 21-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.66 | 19-JUL-13:00 | 77.55 | 01-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.24 | 25-AUG-14:00 | 91.09 | 05-AUG-18:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.67 | 08-SEP-15:00 | 88.74 | 22-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.71 | 01-OCT-13:00 | 234.03 | 25-OCT-06:26 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.77 | 01-NOV-15:00 | 304.25 | 23-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 | 21-DEC-15:00 | 319.41 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.32 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.06 | 319.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 40914.99 | 01-JAN-01:05 | 17891.83 | 10301.16 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35701.87 | 01-FEB-08:63 | 15335.86 | 20602.53 | 15209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24151.14 | 25-MAR-06:53 | 44729.58 | 36054.08 | 28390.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20428.56 | 21-APR-04:00 | 23003.78 | 3433.86 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15456.79 | 07-MAY-10:33 | 11501.89 | 15451.75 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16596.73 | 28-JUN-18:10 | 53675.50 | 82408.91 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22616.49 | 14-JUL-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24634.26 | 04-AUG-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27487.50 | 28-SEP-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39131.28 | 26-OCT-00:36 | 103517.03 | 23177.62 | 22813.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41316.25 | 23-NOV-21:50 | 20447.81 | 20602.33 | 14195.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41355.15 | 06-DEC-22:00 | 20447.81 | 27469.64 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15456.79 | 10223.90 | 3433.86 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41355.15 | 103517.03 | 82408.91 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3697.83 | 14-JAN-13:40 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 0.00 |
February | 2683.87 | 01-FEB-14:00 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.47 |
March | 2820.68 | 18-MAR-13:40 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.07 | 0.00 |
April | 3182.61 | 14-APR-14:10 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 104.37 | 0.00 |
May | 2715.36 | 31-MAY-18:15 | 1819.27 | 1273.52 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 115.85 | 0.00 |
June | 3558.73 | 28-JUN-18:13 | 2728.91 | 1910.28 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 0.00 |
July | 3299.45 | 21-JUL-18:30 | 909.64 | 636.76 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 142.30 | 0.00 |
August | 3716.60 | 28-AUG-12:30 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 0.00 |
September | 4001.42 | 28-SEP-13:30 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 124.11 | 0.00 |
October | 4029.03 | 02-OCT-12:40 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 103.03 | 0.00 |
November | 3872.29 | 21-NOV-13:40 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 0.00 |
December | 3577.35 | 25-DEC-13:00 | 389.84 | 238.78 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2683.87 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4029.03 | 2728.91 | 1910.28 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 87.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2407.73 | 12-JAN-07:18 | 3611.52 | 2765.14 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.97 |
February | 2325.42 | 01-FEB-06:43 | 10533.60 | 3686.85 | 4178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 |
March | 2142.80 | 25-MAR-06:53 | 5266.80 | 1935.60 | 2340.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.98 |
April | 2389.05 | 14-APR-20:50 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 0.00 |
May | 2343.58 | 19-MAY-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 0.00 |
June | 2679.52 | 28-JUN-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 0.00 |
July | 2544.42 | 20-JUL-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 0.00 |
August | 2578.47 | 15-AUG-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 | 0.00 |
September | 2535.49 | 07-SEP-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 0.00 |
October | 2357.95 | 05-OCT-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
November | 2204.84 | 18-NOV-07:02 | 3762.00 | 1382.57 | 1671.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.03 |
December | 2333.80 | 15-DEC-00:55 | 5417.28 | 737.37 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2142.80 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2679.52 | 10533.60 | 3686.85 | 4178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 79.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1960.27 | 12-JAN-07:18 | 763.78 | 2227.55 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.64 |
February | 1867.36 | 01-FEB-06:43 | 2227.68 | 2970.07 | 4418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.94 |
March | 1773.16 | 25-MAR-06:53 | 1113.84 | 1559.29 | 2474.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.19 |
April | 1609.88 | 25-APR-21:00 | 254.59 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.77 | 0.00 |
May | 1861.09 | 18-MAY-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 0.00 |
June | 2510.24 | 28-JUN-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 120.55 | 0.00 |
July | 2396.56 | 21-JUL-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 121.00 | 0.00 |
August | 2273.25 | 15-AUG-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 102.86 | 0.00 |
September | 2156.64 | 08-SEP-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 | 0.00 |
October | 1975.52 | 02-OCT-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | 0.00 |
November | 1771.65 | 05-NOV-02:63 | 668.30 | 445.51 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.83 |
December | 1833.90 | 15-DEC-00:55 | 1145.66 | 594.01 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1609.88 | 222.77 | 445.51 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2510.24 | 2227.68 | 2970.07 | 4418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 121.00 | 176.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1247.61 | 12-JAN-07:18 | 587.52 | 1130.09 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.11 |
February | 1188.33 | 01-FEB-06:43 | 1713.60 | 1506.82 | 1274.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 |
March | 1125.71 | 25-MAR-06:53 | 856.80 | 791.05 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 |
April | 981.36 | 21-APR-04:00 | 440.64 | 75.35 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.62 |
May | 890.29 | 09-MAY-20:00 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 38.13 | 0.00 |
June | 1407.03 | 28-JUN-18:40 | 171.36 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 0.00 |
July | 1296.08 | 21-JUL-19:10 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 | 0.00 |
August | 1194.06 | 15-AUG-20:00 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 0.00 |
September | 1116.67 | 08-SEP-20:00 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 0.00 |
October | 1160.83 | 25-OCT-05:02 | 1028.16 | 904.09 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.81 |
November | 1127.64 | 05-NOV-02:63 | 514.08 | 226.02 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.02 |
December | 1157.81 | 27-DEC-05:15 | 440.64 | 150.68 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 890.29 | 171.36 | 75.35 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1407.03 | 1713.60 | 1506.82 | 1274.51 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 99.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38928.07 | 12-JAN-07:56 | 3628.80 | 2268.02 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 260.16 |
February | 44470.61 | 01-FEB-06:43 | 7056.00 | 2016.02 | 24067.37 | 209087.24 | 0.00 | 0.00 | 0.00 | 0.00 | 241.30 |
March | 39327.67 | 13-MAR-05:10 | 7056.00 | 2016.02 | 24067.37 | 209087.24 | 0.00 | 0.00 | 0.00 | 0.00 | 222.38 |
April | 39305.46 | 14-APR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 90.16 | 0.00 |
May | 39424.82 | 18-MAY-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.94 | 0.00 |
June | 40069.18 | 28-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 164.62 | 0.00 |
July | 39899.10 | 21-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 165.22 | 0.00 |
August | 39793.88 | 15-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 140.45 | 0.00 |
September | 39637.00 | 08-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 125.95 | 0.00 |
October | 39243.43 | 03-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.91 | 0.00 |
November | 48845.86 | 23-NOV-20:28 | 6048.00 | 4032.04 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 258.94 |
December | 50364.24 | 05-DEC-21:43 | 7257.60 | 3628.84 | 38989.14 | 338721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 323.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38928.07 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50364.24 | 7257.60 | 4032.04 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 165.22 | 323.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19031.51 | 26-JAN-05:20 | 30736.80 | 870.08 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.46 |
February | 17141.38 | 25-FEB-05:33 | 61473.60 | 870.08 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.82 |
March | 17068.29 | 13-MAR-03:45 | 61473.60 | 870.08 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.19 |
April | 12303.42 | 14-APR-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 107.57 | 0.00 |
May | 11867.30 | 09-MAY-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 111.58 | 0.00 |
June | 13479.92 | 28-JUN-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 241.59 | 0.00 |
July | 13378.46 | 21-JUL-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 224.41 | 0.00 |
August | 13239.96 | 15-AUG-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 198.19 | 0.00 |
September | 14029.18 | 28-SEP-15:03 | 59766.00 | 837.45 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 304.50 | 0.00 |
October | 23382.51 | 12-OCT-02:18 | 92210.40 | 1305.12 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.16 |
November | 14720.96 | 25-NOV-04:23 | 46105.20 | 652.56 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.30 |
December | 19020.40 | 09-DEC-00:02 | 92210.40 | 2610.23 | 1828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11867.30 | 15368.40 | 652.56 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23382.51 | 92210.40 | 2610.23 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 304.50 | 417.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 64338.45 | 11-JAN-05:18 | 273737.88 | 11405.76 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.98 |
February | 63414.39 | 26-FEB-04:52 | 212907.24 | 11405.76 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172.25 |
March | 66318.38 | 03-MAR-07:10 | 40553.76 | 8839.46 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.67 |
April | 44287.49 | 21-APR-04:08 | 182491.92 | 7603.84 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1134.77 |
May | 41594.53 | 09-MAY-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 318.67 | 0.00 |
June | 46654.11 | 28-JUN-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 690.13 | 0.00 |
July | 45885.96 | 21-JUL-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 641.05 | 0.00 |
August | 45402.60 | 15-AUG-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 566.12 | 0.00 |
September | 45362.50 | 07-SEP-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 573.45 | 0.00 |
October | 79595.51 | 12-OCT-02:18 | 273737.88 | 5702.88 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.05 |
November | 80186.99 | 07-NOV-05:30 | 91245.96 | 3801.92 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.09 |
December | 80174.20 | 29-DEC-04:20 | 91245.96 | 1900.96 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41594.53 | 40553.76 | 1900.96 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80186.99 | 273737.88 | 11405.76 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 690.13 | 1183.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3823.20 | 25-JAN-21:31 | 1602.00 | 1871.00 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 |
February | 4098.18 | 01-FEB-17:11 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.53 |
March | 3828.08 | 23-MAR-21:11 | 1440.00 | 1126.80 | 716.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 |
April | 3998.07 | 06-APR-21:51 | 1620.00 | 1267.65 | 806.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 |
May | 4025.45 | 08-MAY-08:61 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 | 0.00 |
June | 4085.91 | 16-JUN-06:41 | 774.00 | 1177.26 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | 0.00 |
July | 4149.73 | 01-JUL-08:61 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 0.00 |
August | 3996.92 | 24-AUG-08:21 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 0.00 |
September | 3889.47 | 28-SEP-15:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 0.00 |
October | 4036.32 | 17-OCT-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.23 |
November | 3913.96 | 10-NOV-09:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
December | 3996.44 | 14-DEC-17:01 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3823.20 | 360.00 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4149.73 | 1800.00 | 1871.00 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 62.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3711.53 | 26-JAN-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 0.00 |
February | 3746.27 | 01-FEB-17:11 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.36 |
March | 3736.99 | 18-MAR-18:01 | 819.00 | 1471.40 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 0.00 |
April | 3937.56 | 26-APR-21:51 | 1620.00 | 1267.51 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 |
May | 4028.67 | 20-MAY-08:61 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 18.44 | 0.00 |
June | 4132.35 | 16-JUN-06:41 | 774.00 | 1177.12 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 | 0.00 |
July | 4187.68 | 01-JUL-08:61 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 | 0.00 |
August | 3953.48 | 24-AUG-08:21 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 | 0.00 |
September | 3831.58 | 28-SEP-15:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 0.00 |
October | 3883.67 | 17-OCT-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 |
November | 3762.12 | 20-NOV-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 0.00 |
December | 3707.76 | 24-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3707.76 | 360.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4187.68 | 1800.00 | 1471.40 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 50.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 680.17 | 14-JAN-13:40 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
February | 526.49 | 01-FEB-14:20 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 |
March | 495.80 | 18-MAR-13:40 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
April | 511.76 | 14-APR-13:40 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 0.00 |
May | 445.94 | 09-MAY-17:12 | 0.00 | 354.08 | 495.34 | 0.00 | 0.00 | 0.00 | 0.00 | 18.72 | 0.00 |
June | 545.93 | 28-JUN-19:10 | 0.00 | 132.12 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | 0.00 |
July | 531.05 | 21-JUL-20:20 | 0.00 | 117.59 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 0.00 |
August | 578.94 | 27-AUG-14:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 | 0.00 |
September | 659.07 | 28-SEP-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 0.00 |
October | 679.74 | 18-OCT-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 0.00 |
November | 708.92 | 20-NOV-14:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 0.00 |
December | 675.45 | 25-DEC-13:30 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 445.94 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 708.92 | 0.00 | 354.08 | 495.34 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 | 13.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1319.18 | 24-JAN-21:51 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 |
February | 1232.07 | 09-FEB-22:51 | 1260.00 | 619.80 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 |
March | 1351.10 | 19-MAR-21:51 | 970.20 | 786.32 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 |
April | 1395.32 | 30-APR-08:51 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.00 |
May | 1446.84 | 20-MAY-08:61 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 0.00 |
June | 1472.36 | 11-JUN-08:61 | 486.00 | 666.06 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 | 0.00 |
July | 1485.13 | 01-JUL-08:61 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 0.00 |
August | 1395.39 | 23-AUG-18:01 | 970.20 | 823.32 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 | 0.00 |
September | 1392.57 | 28-SEP-15:01 | 680.40 | 259.02 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 24.37 | 0.00 |
October | 1387.67 | 06-OCT-18:01 | 970.20 | 823.32 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 0.00 |
November | 1319.75 | 21-NOV-21:11 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 |
December | 1300.92 | 26-DEC-21:31 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1232.07 | 486.00 | 259.02 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1485.13 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 24.37 | 16.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3730.01 | 27-JAN-09:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 |
February | 3363.73 | 01-FEB-17:11 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 |
March | 3460.88 | 16-MAR-08:51 | 288.00 | 739.99 | 906.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 |
April | 4019.54 | 14-APR-08:41 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
May | 4032.83 | 06-MAY-08:41 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 0.00 |
June | 4021.10 | 13-JUN-08:11 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 0.00 |
July | 4026.50 | 01-JUL-08:61 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 0.00 |
August | 4019.08 | 24-AUG-08:21 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
September | 3732.58 | 15-SEP-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
October | 4008.16 | 15-OCT-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
November | 3997.26 | 10-NOV-09:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 |
December | 3649.95 | 25-DEC-09:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3363.73 | 288.00 | 588.63 | 906.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4032.83 | 972.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 50.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3452.30 | 27-JAN-09:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 |
February | 2978.99 | 26-FEB-09:01 | 378.00 | 823.98 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.36 |
March | 3379.36 | 16-MAR-08:51 | 288.00 | 739.90 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
April | 3990.07 | 14-APR-08:41 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
May | 4010.66 | 18-MAY-08:11 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 |
June | 4004.40 | 13-JUN-08:11 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 0.00 |
July | 4009.58 | 01-JUL-08:61 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 0.00 |
August | 3993.70 | 24-AUG-08:21 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 0.00 |
September | 3688.19 | 15-SEP-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
October | 3906.96 | 17-OCT-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
November | 3678.15 | 10-NOV-09:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 |
December | 3339.90 | 25-DEC-09:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2978.99 | 288.00 | 739.90 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4010.66 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 71.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3574.25 | 12-JAN-07:18 | 6035.62 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.63 |
February | 3437.75 | 01-FEB-06:43 | 17603.88 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.37 |
March | 3219.41 | 25-MAR-06:53 | 8801.94 | 4357.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.92 |
April | 2881.72 | 21-APR-04:00 | 4526.71 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.91 |
May | 2447.95 | 20-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 | 0.00 |
June | 3786.59 | 28-JUN-18:40 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.13 | 0.00 |
July | 3424.21 | 21-JUL-19:10 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.44 | 0.00 |
August | 3267.71 | 15-AUG-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.28 | 0.00 |
September | 3137.66 | 08-SEP-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.29 | 0.00 |
October | 3348.83 | 25-OCT-05:02 | 10562.33 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.05 |
November | 3255.26 | 05-NOV-02:63 | 5281.16 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.67 |
December | 3370.53 | 30-DEC-00:22 | 22633.56 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2447.95 | 1760.39 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3786.59 | 22633.56 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.13 | 137.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4006.84 | 26-JAN-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 |
February | 4359.04 | 01-FEB-17:11 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.64 |
March | 4045.99 | 23-MAR-21:11 | 1440.00 | 1126.80 | 716.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.02 |
April | 4226.39 | 20-APR-21:51 | 1620.00 | 1267.65 | 806.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 |
May | 4184.18 | 08-MAY-08:61 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 |
June | 4227.01 | 16-JUN-06:41 | 774.00 | 1177.26 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 | 0.00 |
July | 4301.63 | 01-JUL-08:61 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 23.61 | 0.00 |
August | 4140.65 | 24-AUG-08:21 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 | 0.00 |
September | 4111.98 | 28-SEP-15:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 | 0.00 |
October | 4198.61 | 17-OCT-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 |
November | 4067.68 | 21-NOV-21:11 | 1602.00 | 1871.00 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 |
December | 4281.07 | 14-DEC-17:01 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4006.84 | 360.00 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4359.04 | 1800.00 | 1871.00 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 | 64.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3900.21 | 26-JAN-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 0.00 |
February | 3917.53 | 01-FEB-17:11 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.84 |
March | 3939.83 | 18-MAR-18:01 | 819.00 | 1471.40 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 | 0.00 |
April | 4121.86 | 20-APR-21:51 | 1620.00 | 1267.51 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 |
May | 4165.09 | 20-MAY-08:61 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 | 0.00 |
June | 4267.07 | 16-JUN-06:41 | 774.00 | 1177.12 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 0.00 |
July | 4338.39 | 01-JUL-08:61 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 0.00 |
August | 4093.88 | 24-AUG-08:21 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 0.00 |
September | 4046.83 | 28-SEP-15:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 | 0.00 |
October | 4026.00 | 17-OCT-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 |
November | 3964.06 | 20-NOV-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 | 0.00 |
December | 3893.15 | 24-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3893.15 | 360.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4338.39 | 1800.00 | 1471.40 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 | 49.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2257.47 | 25-JAN-21:31 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.93 |
February | 2290.20 | 01-FEB-17:11 | 972.00 | 370.03 | 1238.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 |
March | 2108.40 | 22-MAR-21:21 | 1440.00 | 708.35 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 |
April | 2124.77 | 07-APR-21:51 | 1440.00 | 708.35 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 |
May | 2141.13 | 20-MAY-08:61 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 0.00 |
June | 2147.34 | 16-JUN-06:41 | 774.00 | 740.06 | 2322.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 0.00 |
July | 2188.71 | 01-JUL-08:61 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 | 0.00 |
August | 2105.70 | 24-AUG-08:21 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 | 0.00 |
September | 2135.66 | 29-SEP-08:21 | 324.00 | 523.33 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 | 0.00 |
October | 2230.72 | 17-OCT-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 |
November | 2387.88 | 10-NOV-09:51 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 |
December | 2297.15 | 26-DEC-21:31 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2105.70 | 324.00 | 370.03 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2387.88 | 1800.00 | 1176.17 | 2322.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 | 35.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31969.81 | 23-JAN-05:00 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.25 |
February | 37273.08 | 01-FEB-06:43 | 209912.64 | 15279.29 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.70 |
March | 32115.17 | 24-MAR-03:34 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.78 |
April | 26539.71 | 21-APR-04:39 | 188921.38 | 5347.75 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.27 |
May | 23533.60 | 09-MAY-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 70.06 | 0.00 |
June | 25185.18 | 28-JUN-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 148.70 | 0.00 |
July | 24852.23 | 21-JUL-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 139.98 | 0.00 |
August | 24411.36 | 10-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 125.48 | 0.00 |
September | 24214.53 | 07-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 127.24 | 0.00 |
October | 31563.51 | 26-OCT-00:36 | 242898.91 | 5156.76 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.12 |
November | 31129.87 | 07-NOV-05:08 | 269887.68 | 7639.64 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.59 |
December | 31807.22 | 15-DEC-23:58 | 242898.91 | 10313.52 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23533.60 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37273.08 | 269887.68 | 15279.29 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 148.70 | 307.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34041.23 | 23-JAN-05:00 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.44 |
February | 41657.99 | 01-FEB-06:43 | 209912.64 | 15279.29 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.74 |
March | 33673.46 | 24-MAR-03:34 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.21 |
April | 27829.04 | 21-APR-04:39 | 188921.38 | 5347.75 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.62 |
May | 24708.59 | 09-MAY-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.58 | 0.00 |
June | 26377.96 | 28-JUN-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 148.68 | 0.00 |
July | 26043.03 | 21-JUL-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 139.96 | 0.00 |
August | 25605.96 | 10-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 125.45 | 0.00 |
September | 25380.03 | 07-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 127.23 | 0.00 |
October | 33137.03 | 26-OCT-00:36 | 242898.91 | 5156.76 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.78 |
November | 33049.26 | 18-NOV-06:39 | 209912.64 | 11459.46 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.22 |
December | 33569.34 | 04-DEC-22:58 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24708.59 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41657.99 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 148.68 | 326.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34220.63 | 10-JAN-08:07 | 10674.24 | 5381.88 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 235.65 |
February | 34544.56 | 24-FEB-07:18 | 10674.24 | 6727.35 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 246.64 |
March | 33895.47 | 07-MAR-07:25 | 8539.39 | 5381.88 | 119302.85 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 244.03 |
April | 30574.58 | 30-APR-10:33 | 2401.70 | 1210.92 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 78.25 | 0.00 |
May | 30777.35 | 07-MAY-10:33 | 2401.70 | 1210.92 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 78.56 | 0.00 |
June | 31591.36 | 18-JUN-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 149.34 | 0.00 |
July | 31595.29 | 22-JUL-10:50 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 152.09 | 0.00 |
August | 31633.55 | 13-AUG-10:37 | 2401.70 | 1210.92 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 125.01 | 0.00 |
September | 31433.79 | 09-SEP-10:33 | 2401.70 | 1009.10 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 122.97 | 0.00 |
October | 34081.30 | 25-OCT-08:00 | 7471.97 | 3767.32 | 104389.99 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 235.18 |
November | 33918.41 | 24-NOV-07:37 | 10674.24 | 6727.35 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 264.62 |
December | 34763.30 | 01-DEC-08:08 | 6404.54 | 3229.13 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 231.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 30574.58 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34763.30 | 10674.24 | 6727.35 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 152.09 | 264.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6214.21 | 13-JAN-02:26 | 19163.52 | 1756.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.51 |
February | 6581.47 | 01-FEB-06:43 | 18631.20 | 8783.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.17 |
March | 5713.45 | 12-MAR-04:45 | 3726.24 | 878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.13 |
April | 6467.52 | 14-APR-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.45 | 0.00 |
May | 6144.14 | 09-MAY-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.60 | 0.00 |
June | 8171.16 | 28-JUN-18:13 | 5589.36 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 | 0.00 |
July | 7502.11 | 20-JUL-18:17 | 5589.36 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.78 | 0.00 |
August | 7537.86 | 11-AUG-15:30 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.76 | 0.00 |
September | 7566.47 | 07-SEP-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.33 | 0.00 |
October | 7114.40 | 02-OCT-13:10 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 0.00 |
November | 6240.33 | 05-NOV-02:63 | 5589.36 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.18 |
December | 6506.86 | 30-DEC-00:22 | 23954.40 | 4391.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5713.45 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8171.16 | 23954.40 | 8783.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 | 233.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.442947E+12 | 312878.15 | 31-JAN-19:10 | 0.438545E+12 | 367512.07 | 01-JAN-21:40 |
February | 0.355507E+12 | 268171.37 | 16-FEB-20:19 | 0.401186E+12 | 402978.18 | 04-FEB-19:49 |
March | 0.432288E+12 | 326301.53 | 16-MAR-18:30 | 0.422191E+12 | 366301.52 | 25-MAR-21:40 |
April | 0.534161E+12 | 387258.44 | 14-APR-19:10 | 0.378330E+12 | 343753.60 | 04-APR-17:49 |
May | 0.600233E+12 | 398229.92 | 31-MAY-19:19 | 0.376845E+12 | 320590.65 | 01-MAY-17:19 |
June | 0.674643E+12 | 458210.88 | 28-JUN-19:30 | 0.354432E+12 | 316657.39 | 01-JUN-17:19 |
July | 0.706078E+12 | 460836.76 | 21-JUL-19:00 | 0.360767E+12 | 313671.54 | 05-JUL-17:19 |
August | 0.698156E+12 | 441925.48 | 15-AUG-19:10 | 0.362614E+12 | 314939.30 | 31-AUG-17:30 |
September | 0.648397E+12 | 445756.41 | 08-SEP-19:10 | 0.358344E+12 | 318171.32 | 29-SEP-17:30 |
October | 0.529781E+12 | 406285.25 | 03-OCT-19:10 | 0.390805E+12 | 330342.16 | 31-OCT-17:00 |
November | 0.434641E+12 | 328760.82 | 01-NOV-18:10 | 0.402274E+12 | 417471.42 | 23-NOV-21:00 |
December | 0.416754E+12 | 273500.30 | 26-DEC-21:40 | 0.449668E+12 | 430129.87 | 06-DEC-22:10 |
Annual Sum or Average | 0.647359E+13 | 0.469600E+13 | ||||
Minimum of Months | 0.355507E+12 | 268171.37 | 0.354432E+12 | 313671.54 | ||
Maximum of Months | 0.706078E+12 | 460836.76 | 0.449668E+12 | 430129.87 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.744099E+11 | 0.257065E+11 | 0.140828E+12 | 0.552134E+11 | 0.465966E+11 | 0.952196E+10 | 0.00 | 0.662601E+11 | 0.00 | 0.00 | 0.115027E+11 | 0.770455E+10 | 0.00 |
February | 0.671370E+11 | 0.220513E+11 | 0.127191E+12 | 0.498703E+11 | 0.388990E+11 | 0.741982E+10 | 0.00 | 0.206309E+11 | 0.00 | 0.00 | 0.105893E+11 | 0.696202E+10 | 0.00 |
March | 0.738562E+11 | 0.226722E+11 | 0.140882E+12 | 0.552166E+11 | 0.441318E+11 | 0.900793E+10 | 0.00 | 0.623674E+11 | 0.00 | 0.00 | 0.112201E+11 | 0.770300E+10 | 0.00 |
April | 0.711592E+11 | 0.201587E+11 | 0.136245E+12 | 0.534313E+11 | 0.505133E+11 | 0.975597E+10 | 0.00 | 0.166333E+12 | 0.00 | 0.00 | 0.140788E+11 | 0.746498E+10 | 0.00 |
May | 0.732145E+11 | 0.192974E+11 | 0.140860E+12 | 0.552142E+11 | 0.551199E+11 | 0.101726E+11 | 0.00 | 0.215999E+12 | 0.00 | 0.00 | 0.174564E+11 | 0.770427E+10 | 0.00 |
June | 0.705307E+11 | 0.180356E+11 | 0.136336E+12 | 0.534341E+11 | 0.616231E+11 | 0.103623E+11 | 0.00 | 0.289196E+12 | 0.00 | 0.00 | 0.225920E+11 | 0.745688E+10 | 0.00 |
July | 0.730870E+11 | 0.188768E+11 | 0.140770E+12 | 0.552105E+11 | 0.625338E+11 | 0.108500E+11 | 0.00 | 0.306869E+12 | 0.00 | 0.00 | 0.248672E+11 | 0.771238E+10 | 0.00 |
August | 0.735505E+11 | 0.201386E+11 | 0.140892E+12 | 0.552164E+11 | 0.628429E+11 | 0.108086E+11 | 0.00 | 0.298287E+12 | 0.00 | 0.00 | 0.233750E+11 | 0.770436E+10 | 0.00 |
September | 0.713919E+11 | 0.211501E+11 | 0.136256E+12 | 0.534316E+11 | 0.602210E+11 | 0.104272E+11 | 0.00 | 0.262984E+12 | 0.00 | 0.00 | 0.199023E+11 | 0.746623E+10 | 0.00 |
October | 0.741792E+11 | 0.237137E+11 | 0.140818E+12 | 0.552131E+11 | 0.542252E+11 | 0.100212E+11 | 0.00 | 0.146681E+12 | 0.00 | 0.00 | 0.119904E+11 | 0.770300E+10 | 0.00 |
November | 0.719616E+11 | 0.245048E+11 | 0.136330E+12 | 0.534333E+11 | 0.469134E+11 | 0.914279E+10 | 0.00 | 0.706696E+11 | 0.00 | 0.00 | 0.918511E+10 | 0.744905E+10 | 0.00 |
December | 0.744351E+11 | 0.261972E+11 | 0.140770E+12 | 0.552118E+11 | 0.461963E+11 | 0.846975E+10 | 0.00 | 0.391849E+11 | 0.00 | 0.00 | 0.134065E+11 | 0.771270E+10 | 0.00 |
Annual Sum or Average | 0.868913E+12 | 0.262503E+12 | 0.165818E+13 | 0.650096E+12 | 0.629816E+12 | 0.115960E+12 | 0.00 | 0.194546E+13 | 0.00 | 0.00 | 0.190166E+12 | 0.907434E+11 | 0.00 |
Minimum of Months | 0.671370E+11 | 0.180356E+11 | 0.127191E+12 | 0.498703E+11 | 0.388990E+11 | 0.741982E+10 | 0.00 | 0.206309E+11 | 0.00 | 0.00 | 0.918511E+10 | 0.696202E+10 | 0.00 |
Maximum of Months | 0.744351E+11 | 0.261972E+11 | 0.140892E+12 | 0.552166E+11 | 0.628429E+11 | 0.108500E+11 | 0.00 | 0.306869E+12 | 0.00 | 0.00 | 0.248672E+11 | 0.771270E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.279753E+11 | 0.00 | 0.258651E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.317595E+11 | 0.00 | 0.232222E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.205462E+11 | 0.00 | 0.249621E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.141361E+10 | 0.00 | 0.229961E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.160037E+09 | 0.00 | 0.224706E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 25188872.38 | 0.00 | 0.207293E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 39746368.93 | 0.00 | 0.208907E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 40181836.88 | 0.00 | 0.210535E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 65099068.29 | 0.00 | 0.211308E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.856837E+10 | 0.00 | 0.230333E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.197590E+11 | 0.00 | 0.235424E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.442249E+11 | 0.00 | 0.253623E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.154577E+12 | 0.00 | 0.275258E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 25188872.38 | 0.00 | 0.207293E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.442249E+11 | 0.00 | 0.258651E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 71560.59 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39721.54 | 02-JAN-07:19 | 33349.77 | 31-JAN-22:10 | 4199.02 | 01-JAN-09:30 | 0.00 | 01-JAN-00:10 |
February | 71560.59 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39721.54 | 01-FEB-07:19 | 38935.93 | 13-FEB-22:49 | 4186.16 | 08-FEB-06:30 | 0.00 | 01-FEB-00:10 |
March | 71560.59 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39721.54 | 13-MAR-06:19 | 32519.43 | 16-MAR-21:00 | 4404.51 | 20-MAR-18:30 | 0.00 | 01-MAR-00:10 |
April | 71560.59 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39721.54 | 03-APR-06:19 | 40014.80 | 14-APR-21:10 | 4722.02 | 25-APR-18:49 | 0.00 | 01-APR-00:10 |
May | 71560.59 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39721.37 | 26-MAY-06:19 | 40063.18 | 09-MAY-21:10 | 4421.16 | 11-MAY-21:49 | 0.00 | 01-MAY-00:10 |
June | 71560.59 | 01-JUN-19:19 | 16690.39 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39719.05 | 02-JUN-06:19 | 46948.58 | 28-JUN-21:10 | 5820.03 | 28-JUN-18:49 | 0.00 | 01-JUN-00:10 |
July | 71560.59 | 03-JUL-19:30 | 16690.39 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39721.06 | 14-JUL-06:19 | 48295.53 | 21-JUL-21:10 | 5094.28 | 07-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 71560.59 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39721.54 | 04-AUG-06:19 | 49022.15 | 15-AUG-21:10 | 5302.41 | 27-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 71560.59 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39721.54 | 01-SEP-06:19 | 50699.91 | 07-SEP-21:10 | 5234.57 | 18-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 71560.59 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39721.54 | 02-OCT-06:19 | 48592.74 | 06-OCT-21:10 | 5072.81 | 05-OCT-18:30 | 0.00 | 01-OCT-00:10 |
November | 71560.59 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39721.54 | 01-NOV-06:19 | 43565.24 | 17-NOV-05:40 | 4424.59 | 01-NOV-18:10 | 0.00 | 01-NOV-00:10 |
December | 71560.59 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39721.54 | 01-DEC-07:19 | 48749.60 | 04-DEC-22:40 | 4222.30 | 06-DEC-22:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 71560.59 | 16690.39 | 89171.45 | 39719.05 | 32519.43 | 4186.16 | 0.00 | |||||||
Maximum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.54 | 50699.91 | 5820.03 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 104112.67 | 31-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.36 | 10-JAN-07:19 | 0.00 |
February | 63585.81 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.26 | 01-FEB-07:10 | 0.00 |
March | 102741.54 | 16-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4738.49 | 29-MAR-06:40 | 0.00 |
April | 145845.61 | 14-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-04:49 | 4738.70 | 27-APR-18:10 | 0.00 |
May | 161889.54 | 31-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-03:20 | 4738.71 | 04-MAY-18:10 | 0.00 |
June | 218003.91 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.76 | 01-JUN-18:10 | 0.00 |
July | 195963.48 | 20-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.75 | 13-JUL-18:10 | 0.00 |
August | 193895.15 | 25-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.63 | 28-AUG-18:40 | 0.00 |
September | 183038.83 | 08-SEP-18:10 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4738.74 | 07-SEP-18:10 | 0.00 |
October | 157379.26 | 01-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.57 | 05-OCT-18:10 | 0.00 |
November | 113056.86 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-10:20 | 4738.12 | 03-NOV-06:19 | 0.00 |
December | 87246.52 | 25-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.42 | 27-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 63585.81 | 0.00 | 0.00 | 9938.94 | 4738.12 | 0.00 | |||
Maximum of Months | 218003.91 | 0.00 | 0.00 | 9938.94 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 312878.15 | 31-JAN-19:10 | 63637.18 | 77573.37 | 16690.39 | 31790.09 | 26848.87 | 3893.73 | 0.00 | 84648.00 | 0.00 |
February | 268171.37 | 16-FEB-20:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 23904.74 | 3696.60 | 0.00 | 27522.23 | 0.00 |
March | 326301.53 | 16-MAR-18:30 | 63637.18 | 77573.37 | 16690.39 | 31806.12 | 25426.79 | 4402.80 | 0.00 | 89925.18 | 0.00 |
April | 387258.44 | 14-APR-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 34019.55 | 4047.09 | 0.00 | 127107.54 | 0.00 |
May | 398229.92 | 31-MAY-19:19 | 71560.59 | 86439.81 | 16690.39 | 32088.69 | 32741.32 | 4089.21 | 0.00 | 138521.38 | 0.00 |
June | 458210.88 | 28-JUN-19:30 | 71560.59 | 86439.81 | 16690.39 | 32089.76 | 40335.22 | 4378.84 | 0.00 | 190825.24 | 0.00 |
July | 460836.76 | 21-JUL-19:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 41848.73 | 4695.28 | 0.00 | 191946.31 | 0.00 |
August | 441925.48 | 15-AUG-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 40994.20 | 4696.62 | 0.00 | 173976.22 | 0.00 |
September | 445756.41 | 08-SEP-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 41879.85 | 4618.68 | 0.00 | 177127.49 | 0.00 |
October | 406285.25 | 03-OCT-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 39087.35 | 4393.29 | 0.00 | 140535.14 | 0.00 |
November | 328760.82 | 01-NOV-18:10 | 63637.18 | 77573.37 | 16690.39 | 31790.09 | 29370.90 | 4424.59 | 0.00 | 96718.83 | 0.00 |
December | 273500.30 | 26-DEC-21:40 | 63637.18 | 88218.55 | 16690.39 | 24565.68 | 32050.80 | 3714.31 | 0.00 | 38720.85 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 268171.37 | 63637.18 | 77573.37 | 16690.39 | 24565.68 | 23904.74 | 3696.60 | 0.00 | 27522.23 | 0.00 | |
Maximum of Months | 460836.76 | 71560.59 | 88218.55 | 16690.39 | 32090.84 | 41879.85 | 4696.62 | 0.00 | 191946.31 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 130212.80 | 02-JAN-06:00 | 0.00 | 248071.21 | 26-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 133538.56 | 02-FEB-03:39 | 0.00 | 248224.34 | 24-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 131600.12 | 30-MAR-06:49 | 0.00 | 247069.20 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 82444.46 | 22-APR-04:49 | 0.00 | 241012.30 | 01-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 23170.45 | 01-MAY-04:19 | 0.00 | 216599.80 | 01-MAY-20:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 3927.37 | 05-JUN-08:09 | 0.00 | 212792.65 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 3873.49 | 11-JUL-08:09 | 0.00 | 209763.04 | 05-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 5364.09 | 29-AUG-08:09 | 0.00 | 211061.57 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 4661.17 | 03-SEP-08:00 | 0.00 | 214363.70 | 29-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 121499.58 | 25-OCT-05:19 | 0.00 | 226093.84 | 31-OCT-17:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 123842.29 | 23-NOV-21:00 | 0.00 | 246057.83 | 29-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 131421.73 | 07-DEC-08:50 | 0.00 | 248721.57 | 13-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 3873.49 | 0.00 | 209763.04 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 133538.56 | 0.00 | 248721.57 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 25.03 | 7.00 | 25.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 25.08 | 9.83 | 25.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.05 | 8.83 | 25.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.96 | 2.67 | 24.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.05 | 4.83 | 25.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 25.04 | 13.17 | 25.04 |
Annual Sum or Average | 0.00 | 0.00 | 46.33 | 25.05 | 46.33 | 25.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 25.08 | 13.17 | 25.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.91 | 3.33 | 21.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.81 | 2.83 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.88 | 0.67 | 21.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 21.84 | 8.50 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.91 | 3.33 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.93 | 4.00 | 21.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.90 | 0.83 | 21.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 21.90 | 5.50 | 21.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.93 | 4.00 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.79 | 1.33 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.80 | 0.33 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 21.78 | 2.50 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.80 | 1.33 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.05 | 4.50 | 22.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.08 | 5.33 | 22.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.93 | 6.50 | 21.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.03 | 1.00 | 22.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.97 | 2.00 | 21.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.05 | 3.33 | 22.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 22.07 | 3.17 | 22.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.84 | 1.17 | 21.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.83 | 22.01 | 27.83 | 22.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 22.08 | 6.50 | 22.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.02 | 4.33 | 22.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.09 | 5.33 | 22.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 21.94 | 7.83 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.06 | 1.00 | 22.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.97 | 1.83 | 21.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.11 | 2.33 | 22.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.96 | 2.33 | 21.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 25.33 | 22.00 | 25.33 | 22.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 22.11 | 7.83 | 22.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.92 | 5.00 | 21.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.86 | 4.33 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.83 | 1.33 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.93 | 0.67 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.33 | 21.88 | 12.33 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.93 | 5.00 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.96 | 5.67 | 21.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.87 | 1.50 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.00 | 21.89 | 9.00 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.96 | 5.67 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.80 | 1.50 | 21.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.73 | 1.33 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.83 | 2.00 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.85 | 3.33 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.92 | 2.50 | 21.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
Annual Sum or Average | 0.00 | 0.00 | 14.17 | 21.83 | 14.17 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.92 | 3.33 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.68 | 0.83 | 24.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.86 | 0.83 | 24.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.74 | 0.50 | 24.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.17 | 24.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.33 | 24.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.70 | 0.67 | 24.70 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 24.73 | 3.33 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.86 | 0.83 | 24.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.72 | 1.00 | 24.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.76 | 2.00 | 24.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.73 | 1.00 | 24.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.59 | 0.33 | 24.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.81 | 0.50 | 24.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.72 | 1.17 | 24.72 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 24.73 | 6.00 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.81 | 2.00 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.04 | 10.50 | 25.04 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 25.08 | 17.00 | 25.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 25.18 | 13.00 | 25.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.87 | 0.17 | 24.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.90 | 3.17 | 24.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.00 | 7.50 | 25.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 25.04 | 16.67 | 25.04 |
Annual Sum or Average | 0.00 | 0.00 | 68.00 | 25.07 | 68.00 | 25.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 25.18 | 17.00 | 25.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 593.17 | 23.77 | 9.50 | 23.78 | 0.00 | 23.78 |
February | 620.50 | 23.26 | 4.50 | 23.27 | 0.00 | 23.27 |
March | 743.83 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
April | 720.00 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
May | 744.00 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
June | 718.67 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
July | 303.17 | 23.81 | 449.67 | 23.88 | 179.67 | 23.90 |
August | 241.00 | 23.97 | 588.83 | 23.94 | 181.00 | 23.95 |
September | 116.17 | 24.00 | 548.33 | 23.99 | 116.17 | 23.99 |
October | 273.17 | 24.00 | 158.17 | 23.99 | 21.17 | 23.99 |
November | 330.50 | 23.99 | 164.17 | 24.00 | 28.83 | 24.00 |
December | 631.83 | 23.98 | 7.00 | 23.98 | 0.00 | 23.98 |
Annual Sum or Average | 6036.00 | 23.36 | 1930.17 | 23.51 | 526.83 | 23.54 |
Minimum of Months | 116.17 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Maximum of Months | 744.00 | 24.00 | 588.83 | 24.00 | 181.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 524.83 | 22.17 | 112.50 | 22.50 | 0.00 | 22.50 |
February | 588.33 | 21.59 | 29.50 | 21.70 | 0.00 | 21.70 |
March | 655.83 | 21.84 | 37.17 | 21.91 | 9.83 | 21.90 |
April | 352.00 | 22.66 | 99.33 | 22.96 | 0.00 | 22.96 |
May | 341.17 | 22.92 | 36.50 | 23.02 | 0.00 | 23.02 |
June | 102.17 | 23.32 | 427.83 | 23.86 | 0.00 | 23.86 |
July | 203.67 | 23.61 | 641.50 | 23.80 | 163.33 | 23.78 |
August | 199.67 | 23.53 | 668.33 | 23.76 | 170.00 | 23.73 |
September | 179.17 | 23.36 | 614.33 | 23.73 | 131.83 | 23.70 |
October | 369.17 | 22.45 | 248.83 | 23.04 | 22.50 | 23.06 |
November | 498.50 | 22.06 | 131.50 | 22.34 | 29.00 | 22.30 |
December | 594.33 | 21.79 | 87.83 | 21.90 | 39.17 | 21.85 |
Annual Sum or Average | 4608.83 | 22.30 | 3135.17 | 22.92 | 565.67 | 22.94 |
Minimum of Months | 102.17 | 21.59 | 29.50 | 21.70 | 0.00 | 21.70 |
Maximum of Months | 655.83 | 23.61 | 668.33 | 23.86 | 170.00 | 23.86 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 631.67 | 23.20 | 5.00 | 23.20 | 0.00 | 23.20 |
February | 610.50 | 22.72 | 10.33 | 22.73 | 3.17 | 22.73 |
March | 638.33 | 22.89 | 0.33 | 22.90 | 0.00 | 22.90 |
April | 406.33 | 23.56 | 19.33 | 23.58 | 0.00 | 23.58 |
May | 372.50 | 23.67 | 10.33 | 23.68 | 0.00 | 23.68 |
June | 71.00 | 23.66 | 208.67 | 23.91 | 0.00 | 23.91 |
July | 239.17 | 23.97 | 577.33 | 23.94 | 197.00 | 23.95 |
August | 221.33 | 23.96 | 624.33 | 23.93 | 214.50 | 23.94 |
September | 166.67 | 23.98 | 589.17 | 23.93 | 166.00 | 23.94 |
October | 410.83 | 23.42 | 155.50 | 23.56 | 32.83 | 23.58 |
November | 567.33 | 23.21 | 94.50 | 23.27 | 46.67 | 23.27 |
December | 729.83 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
Annual Sum or Average | 5065.50 | 23.25 | 2294.83 | 23.46 | 660.17 | 23.50 |
Minimum of Months | 71.00 | 22.72 | 0.00 | 22.73 | 0.00 | 22.73 |
Maximum of Months | 729.83 | 23.98 | 624.33 | 23.94 | 214.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.05 | 3.50 | 22.05 | 3.50 | 22.04 |
February | 672.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
March | 744.00 | 22.04 | 2.50 | 22.04 | 2.50 | 22.03 |
April | 701.17 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
May | 680.17 | 23.72 | 0.00 | 23.72 | 0.00 | 23.72 |
June | 205.00 | 23.98 | 46.17 | 23.98 | 0.00 | 23.98 |
July | 95.50 | 24.00 | 531.17 | 23.98 | 12.33 | 23.99 |
August | 56.67 | 23.97 | 573.67 | 23.96 | 0.00 | 23.96 |
September | 64.33 | 23.82 | 435.33 | 23.92 | 15.17 | 23.92 |
October | 591.00 | 22.87 | 97.00 | 23.03 | 0.83 | 23.03 |
November | 718.67 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
December | 744.00 | 21.62 | 41.67 | 21.58 | 41.67 | 21.56 |
Annual Sum or Average | 6016.50 | 22.53 | 1731.00 | 22.83 | 76.00 | 22.82 |
Minimum of Months | 56.67 | 21.62 | 0.00 | 21.58 | 0.00 | 21.56 |
Maximum of Months | 744.00 | 24.00 | 573.67 | 23.98 | 41.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.78 | 0.33 | 21.78 | 0.33 | 21.78 |
February | 672.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
March | 744.00 | 21.76 | 5.33 | 21.75 | 5.33 | 21.75 |
April | 715.17 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
May | 725.17 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
June | 246.67 | 23.89 | 45.83 | 23.91 | 0.00 | 23.91 |
July | 109.83 | 23.92 | 519.67 | 23.94 | 19.67 | 23.94 |
August | 85.00 | 23.78 | 531.83 | 23.89 | 7.00 | 23.89 |
September | 143.83 | 23.61 | 369.83 | 23.77 | 24.00 | 23.77 |
October | 618.33 | 22.60 | 78.33 | 22.74 | 3.00 | 22.75 |
November | 720.00 | 21.96 | 3.67 | 21.96 | 3.67 | 21.96 |
December | 744.00 | 21.38 | 70.50 | 21.35 | 70.50 | 21.32 |
Annual Sum or Average | 6268.00 | 22.32 | 1625.33 | 22.62 | 133.50 | 22.61 |
Minimum of Months | 85.00 | 21.38 | 0.00 | 21.35 | 0.00 | 21.32 |
Maximum of Months | 744.00 | 23.92 | 531.83 | 23.94 | 70.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 238.00 | 23.62 | 645.17 | 23.65 | 199.50 | 23.72 |
February | 251.00 | 23.85 | 611.83 | 23.64 | 233.17 | 23.72 |
March | 260.33 | 23.81 | 658.50 | 23.67 | 237.50 | 23.74 |
April | 238.67 | 23.90 | 650.00 | 23.73 | 228.67 | 23.78 |
May | 253.33 | 23.99 | 679.50 | 23.76 | 252.67 | 23.81 |
June | 348.67 | 23.98 | 698.33 | 23.73 | 348.67 | 23.79 |
July | 454.17 | 23.92 | 735.17 | 23.70 | 454.17 | 23.76 |
August | 460.33 | 23.91 | 737.67 | 23.68 | 460.33 | 23.74 |
September | 414.83 | 23.94 | 717.33 | 23.67 | 414.83 | 23.74 |
October | 288.00 | 23.82 | 679.67 | 23.68 | 269.00 | 23.75 |
November | 248.00 | 23.69 | 642.83 | 23.63 | 217.17 | 23.70 |
December | 220.17 | 23.31 | 617.00 | 23.59 | 156.17 | 23.67 |
Annual Sum or Average | 3675.50 | 23.84 | 8073.00 | 23.68 | 3471.83 | 23.75 |
Minimum of Months | 220.17 | 23.31 | 611.83 | 23.59 | 156.17 | 23.67 |
Maximum of Months | 460.33 | 23.99 | 737.67 | 23.76 | 460.33 | 23.81 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 206.00 | 23.17 | 270.83 | 23.62 | 13.00 | 23.61 |
February | 367.00 | 22.70 | 207.67 | 23.08 | 55.17 | 23.11 |
March | 391.67 | 22.80 | 175.33 | 23.15 | 6.50 | 23.16 |
April | 138.83 | 23.18 | 289.00 | 23.72 | 0.00 | 23.72 |
May | 122.50 | 23.19 | 274.83 | 23.74 | 0.00 | 23.74 |
June | 13.50 | 23.39 | 554.83 | 23.96 | 4.17 | 23.96 |
July | 309.67 | 23.93 | 686.67 | 23.92 | 305.33 | 23.92 |
August | 349.83 | 23.91 | 712.00 | 23.91 | 347.83 | 23.91 |
September | 280.00 | 23.90 | 709.33 | 23.92 | 280.00 | 23.92 |
October | 181.50 | 23.40 | 416.33 | 23.79 | 58.17 | 23.80 |
November | 249.67 | 23.18 | 345.33 | 23.52 | 79.83 | 23.48 |
December | 423.33 | 23.08 | 128.00 | 23.29 | 0.00 | 23.29 |
Annual Sum or Average | 3033.50 | 23.30 | 4770.17 | 23.68 | 1150.00 | 23.70 |
Minimum of Months | 13.50 | 22.70 | 128.00 | 23.08 | 0.00 | 23.11 |
Maximum of Months | 423.33 | 23.93 | 712.00 | 23.96 | 347.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 320.67 | 23.51 | 39.67 | 23.55 | 12.00 | 23.55 |
February | 430.00 | 23.07 | 108.67 | 23.23 | 41.33 | 23.27 |
March | 439.50 | 23.13 | 56.17 | 23.22 | 5.67 | 23.23 |
April | 269.33 | 23.57 | 46.00 | 23.63 | 0.00 | 23.63 |
May | 238.17 | 23.54 | 37.67 | 23.61 | 0.00 | 23.61 |
June | 35.50 | 23.49 | 334.00 | 23.94 | 2.00 | 23.94 |
July | 289.50 | 23.97 | 619.33 | 23.94 | 280.33 | 23.95 |
August | 320.33 | 23.97 | 662.83 | 23.94 | 320.33 | 23.95 |
September | 248.00 | 23.96 | 672.83 | 23.95 | 248.00 | 23.95 |
October | 231.83 | 23.62 | 227.33 | 23.79 | 53.17 | 23.81 |
November | 350.50 | 23.55 | 183.17 | 23.62 | 76.83 | 23.62 |
December | 593.67 | 23.41 | 0.67 | 23.41 | 0.00 | 23.41 |
Annual Sum or Average | 3767.00 | 23.52 | 2988.33 | 23.70 | 1039.67 | 23.73 |
Minimum of Months | 35.50 | 23.07 | 0.67 | 23.22 | 0.00 | 23.23 |
Maximum of Months | 593.67 | 23.97 | 672.83 | 23.95 | 320.33 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 722.67 | 21.85 | 17.00 | 21.86 | 12.33 | 21.85 |
February | 664.00 | 21.42 | 6.83 | 21.42 | 5.50 | 21.41 |
March | 719.50 | 21.74 | 32.17 | 21.76 | 24.00 | 21.73 |
April | 665.00 | 21.81 | 8.33 | 21.86 | 0.00 | 21.86 |
May | 704.33 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
June | 609.50 | 21.63 | 10.50 | 21.65 | 0.00 | 21.65 |
July | 604.50 | 21.45 | 30.83 | 21.54 | 3.17 | 21.55 |
August | 580.33 | 21.46 | 54.33 | 21.64 | 9.67 | 21.67 |
September | 549.33 | 21.49 | 56.83 | 21.68 | 12.33 | 21.71 |
October | 654.50 | 21.84 | 17.50 | 21.90 | 1.00 | 21.90 |
November | 678.33 | 21.81 | 63.00 | 21.83 | 51.67 | 21.81 |
December | 738.17 | 21.60 | 151.00 | 21.51 | 149.83 | 21.44 |
Annual Sum or Average | 7890.17 | 21.67 | 448.33 | 21.70 | 269.50 | 21.69 |
Minimum of Months | 549.33 | 21.42 | 0.00 | 21.42 | 0.00 | 21.41 |
Maximum of Months | 738.17 | 21.85 | 151.00 | 21.90 | 149.83 | 21.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.67 | 21.50 | 49.83 | 21.46 | 49.83 | 21.42 |
February | 672.00 | 21.16 | 27.83 | 21.13 | 27.83 | 21.10 |
March | 734.83 | 21.56 | 56.50 | 21.52 | 55.00 | 21.47 |
April | 687.67 | 21.83 | 6.50 | 21.86 | 0.00 | 21.86 |
May | 711.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
June | 604.67 | 21.62 | 14.17 | 21.66 | 0.00 | 21.66 |
July | 605.33 | 21.45 | 25.50 | 21.53 | 2.00 | 21.53 |
August | 596.50 | 21.50 | 42.33 | 21.64 | 9.50 | 21.67 |
September | 590.67 | 21.60 | 33.50 | 21.70 | 12.17 | 21.73 |
October | 701.50 | 21.75 | 10.50 | 21.75 | 8.17 | 21.74 |
November | 714.17 | 21.57 | 96.33 | 21.53 | 95.83 | 21.50 |
December | 744.00 | 21.16 | 359.17 | 21.06 | 359.17 | 21.01 |
Annual Sum or Average | 8106.00 | 21.54 | 722.17 | 21.53 | 619.50 | 21.50 |
Minimum of Months | 590.67 | 21.16 | 0.00 | 21.06 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.85 | 359.17 | 21.86 | 359.17 | 21.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.20 | 34.17 | 21.18 | 34.17 | 21.16 |
February | 672.00 | 21.12 | 19.00 | 21.11 | 19.00 | 21.09 |
March | 744.00 | 21.37 | 32.67 | 21.35 | 32.67 | 21.33 |
April | 720.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
May | 744.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
June | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
July | 744.00 | 21.72 | 1.00 | 21.72 | 1.00 | 21.72 |
August | 741.83 | 21.76 | 7.67 | 21.78 | 7.50 | 21.79 |
September | 719.00 | 21.78 | 10.33 | 21.80 | 10.33 | 21.82 |
October | 744.00 | 21.58 | 9.33 | 21.57 | 9.33 | 21.56 |
November | 720.00 | 21.29 | 75.50 | 21.29 | 75.50 | 21.28 |
December | 744.00 | 21.04 | 317.00 | 20.99 | 317.00 | 20.97 |
Annual Sum or Average | 8756.83 | 21.51 | 506.67 | 21.48 | 506.50 | 21.46 |
Minimum of Months | 672.00 | 21.04 | 0.00 | 20.99 | 0.00 | 20.97 |
Maximum of Months | 744.00 | 21.82 | 317.00 | 21.82 | 317.00 | 21.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.50 | 21.90 | 15.67 | 21.89 | 15.67 | 21.87 |
February | 672.00 | 21.52 | 7.00 | 21.51 | 7.00 | 21.50 |
March | 735.17 | 21.86 | 22.00 | 21.85 | 20.17 | 21.83 |
April | 643.00 | 21.85 | 23.83 | 21.99 | 0.17 | 21.99 |
May | 658.50 | 21.76 | 39.33 | 22.00 | 0.00 | 22.00 |
June | 521.17 | 21.34 | 35.50 | 21.56 | 0.00 | 21.56 |
July | 558.17 | 21.31 | 40.00 | 21.48 | 3.67 | 21.50 |
August | 531.00 | 21.30 | 80.83 | 21.63 | 9.83 | 21.67 |
September | 520.00 | 21.42 | 86.00 | 21.78 | 12.33 | 21.83 |
October | 648.00 | 21.88 | 27.50 | 21.98 | 1.00 | 21.99 |
November | 696.83 | 21.85 | 62.00 | 21.83 | 58.50 | 21.80 |
December | 743.67 | 21.63 | 143.67 | 21.55 | 143.67 | 21.48 |
Annual Sum or Average | 7671.00 | 21.66 | 583.33 | 21.76 | 272.00 | 21.75 |
Minimum of Months | 520.00 | 21.30 | 7.00 | 21.48 | 0.00 | 21.48 |
Maximum of Months | 743.67 | 21.90 | 143.67 | 22.00 | 143.67 | 22.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.45 | 57.50 | 21.41 | 57.50 | 21.38 |
February | 672.00 | 21.21 | 19.83 | 21.19 | 19.83 | 21.17 |
March | 742.17 | 21.66 | 38.33 | 21.64 | 37.67 | 21.61 |
April | 675.83 | 21.91 | 22.17 | 22.03 | 0.00 | 22.03 |
May | 673.67 | 21.80 | 41.00 | 22.04 | 0.00 | 22.04 |
June | 517.83 | 21.33 | 39.50 | 21.57 | 0.00 | 21.57 |
July | 555.33 | 21.30 | 33.67 | 21.46 | 2.50 | 21.47 |
August | 536.33 | 21.32 | 42.67 | 21.53 | 9.67 | 21.58 |
September | 536.50 | 21.47 | 42.83 | 21.69 | 12.00 | 21.74 |
October | 686.00 | 21.81 | 12.33 | 21.86 | 2.67 | 21.86 |
November | 718.50 | 21.54 | 116.17 | 21.49 | 115.67 | 21.44 |
December | 744.00 | 21.13 | 353.50 | 21.07 | 353.50 | 21.03 |
Annual Sum or Average | 7802.17 | 21.50 | 819.50 | 21.56 | 611.00 | 21.53 |
Minimum of Months | 517.83 | 21.13 | 12.33 | 21.07 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 21.91 | 353.50 | 22.04 | 353.50 | 22.04 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
February | 672.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
March | 744.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
April | 711.50 | 23.22 | 0.00 | 23.22 | 0.00 | 23.22 |
May | 733.67 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
June | 377.17 | 23.88 | 34.00 | 23.89 | 0.00 | 23.89 |
July | 353.00 | 23.90 | 494.67 | 23.90 | 227.67 | 23.90 |
August | 335.33 | 23.85 | 533.83 | 23.87 | 250.83 | 23.86 |
September | 280.67 | 23.79 | 410.33 | 23.83 | 198.50 | 23.83 |
October | 622.50 | 23.07 | 91.50 | 23.17 | 34.67 | 23.20 |
November | 720.00 | 22.37 | 50.33 | 22.36 | 50.33 | 22.35 |
December | 744.00 | 21.68 | 4.83 | 21.68 | 4.83 | 21.68 |
Annual Sum or Average | 7037.83 | 22.73 | 1619.50 | 22.94 | 766.83 | 23.00 |
Minimum of Months | 280.67 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
Maximum of Months | 744.00 | 23.90 | 533.83 | 23.90 | 250.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 713.67 | 21.79 | 42.50 | 21.80 | 34.67 | 21.76 |
February | 659.83 | 21.36 | 45.33 | 21.34 | 41.00 | 21.29 |
March | 705.83 | 21.67 | 67.83 | 21.69 | 55.33 | 21.64 |
April | 639.50 | 21.70 | 11.17 | 21.77 | 1.00 | 21.77 |
May | 682.17 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
June | 575.00 | 21.53 | 27.00 | 21.61 | 0.00 | 21.61 |
July | 586.00 | 21.38 | 65.00 | 21.57 | 5.50 | 21.59 |
August | 567.33 | 21.41 | 92.83 | 21.69 | 15.83 | 21.73 |
September | 551.17 | 21.47 | 88.00 | 21.73 | 21.00 | 21.78 |
October | 652.17 | 21.77 | 47.83 | 21.85 | 20.17 | 21.83 |
November | 670.33 | 21.73 | 119.00 | 21.71 | 103.83 | 21.66 |
December | 733.50 | 21.54 | 260.00 | 21.41 | 258.00 | 21.33 |
Annual Sum or Average | 7736.50 | 21.60 | 866.50 | 21.65 | 556.33 | 21.62 |
Minimum of Months | 551.17 | 21.36 | 0.00 | 21.34 | 0.00 | 21.29 |
Maximum of Months | 733.50 | 21.79 | 260.00 | 21.85 | 258.00 | 21.83 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.50 | 21.42 | 145.00 | 21.33 | 145.00 | 21.26 |
February | 671.83 | 21.09 | 107.33 | 21.00 | 107.33 | 20.94 |
March | 730.83 | 21.50 | 99.33 | 21.45 | 94.17 | 21.39 |
April | 670.83 | 21.75 | 11.83 | 21.80 | 3.33 | 21.79 |
May | 691.17 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
June | 568.83 | 21.53 | 29.33 | 21.62 | 0.00 | 21.62 |
July | 586.33 | 21.39 | 57.50 | 21.56 | 5.00 | 21.57 |
August | 579.33 | 21.44 | 73.33 | 21.66 | 15.00 | 21.70 |
September | 578.50 | 21.53 | 57.00 | 21.69 | 20.17 | 21.73 |
October | 700.17 | 21.67 | 55.17 | 21.63 | 51.33 | 21.59 |
November | 713.17 | 21.47 | 195.00 | 21.38 | 194.17 | 21.32 |
December | 744.00 | 21.07 | 487.67 | 20.97 | 487.67 | 20.93 |
Annual Sum or Average | 7978.50 | 21.47 | 1318.50 | 21.44 | 1123.17 | 21.39 |
Minimum of Months | 568.83 | 21.07 | 0.00 | 20.97 | 0.00 | 20.93 |
Maximum of Months | 744.00 | 21.76 | 487.67 | 21.80 | 487.67 | 21.79 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 581.17 | 21.68 | 16.17 | 21.76 | 2.00 | 21.77 |
February | 628.17 | 21.55 | 3.17 | 21.55 | 2.83 | 21.55 |
March | 713.50 | 21.87 | 20.83 | 21.84 | 20.83 | 21.82 |
April | 681.50 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
May | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
June | 664.33 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
July | 631.50 | 21.50 | 5.00 | 21.51 | 5.00 | 21.53 |
August | 596.33 | 21.49 | 29.00 | 21.58 | 10.67 | 21.62 |
September | 559.50 | 21.51 | 75.67 | 21.74 | 16.50 | 21.79 |
October | 598.83 | 21.77 | 31.83 | 21.86 | 1.33 | 21.87 |
November | 594.67 | 21.75 | 67.50 | 21.85 | 38.83 | 21.84 |
December | 670.83 | 21.70 | 56.00 | 21.69 | 50.00 | 21.65 |
Annual Sum or Average | 7664.33 | 21.69 | 305.17 | 21.74 | 148.00 | 21.74 |
Minimum of Months | 559.50 | 21.49 | 0.00 | 21.51 | 0.00 | 21.53 |
Maximum of Months | 744.00 | 21.87 | 75.67 | 21.86 | 50.00 | 21.87 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 172.33 | 23.44 | 124.00 | 23.67 | 9.33 | 23.68 |
February | 146.67 | 23.50 | 332.50 | 23.83 | 52.50 | 23.85 |
March | 110.67 | 23.45 | 330.50 | 23.86 | 4.83 | 23.86 |
April | 7.67 | 23.70 | 287.17 | 23.99 | 0.00 | 23.99 |
May | 0.00 | 0.00 | 365.83 | 24.00 | 0.00 | 24.00 |
June | 2.83 | 24.00 | 674.67 | 24.00 | 2.83 | 24.00 |
July | 285.83 | 24.00 | 699.33 | 24.00 | 285.83 | 24.00 |
August | 328.83 | 24.00 | 724.83 | 24.00 | 328.83 | 24.00 |
September | 263.83 | 24.00 | 720.00 | 23.99 | 263.83 | 23.99 |
October | 106.00 | 23.74 | 346.50 | 23.93 | 58.67 | 23.94 |
November | 205.00 | 23.69 | 250.83 | 23.83 | 80.00 | 23.84 |
December | 384.17 | 23.56 | 11.67 | 23.57 | 0.00 | 23.57 |
Annual Sum or Average | 2013.83 | 23.75 | 4867.83 | 23.92 | 1086.67 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 11.67 | 23.57 | 0.00 | 23.57 |
Maximum of Months | 384.17 | 24.00 | 724.83 | 24.00 | 328.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.50 | 23.55 | 212.83 | 23.91 | 7.83 | 23.91 |
February | 55.50 | 23.82 | 468.17 | 23.95 | 41.33 | 23.95 |
March | 30.83 | 23.59 | 455.33 | 23.96 | 4.33 | 23.96 |
April | 0.17 | 23.54 | 383.50 | 23.99 | 0.00 | 23.99 |
May | 0.00 | 0.00 | 457.83 | 24.00 | 0.00 | 24.00 |
June | 2.50 | 24.00 | 696.00 | 24.00 | 2.50 | 24.00 |
July | 271.50 | 24.00 | 710.67 | 24.00 | 271.50 | 24.00 |
August | 310.17 | 24.00 | 730.83 | 24.00 | 310.17 | 24.00 |
September | 248.17 | 24.00 | 720.00 | 24.00 | 248.17 | 24.00 |
October | 73.17 | 23.89 | 439.67 | 23.98 | 56.33 | 23.98 |
November | 110.33 | 23.84 | 305.67 | 23.94 | 78.33 | 23.94 |
December | 156.00 | 23.53 | 19.00 | 23.58 | 0.00 | 23.58 |
Annual Sum or Average | 1307.83 | 23.89 | 5599.50 | 23.97 | 1020.50 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 19.00 | 23.58 | 0.00 | 23.58 |
Maximum of Months | 310.17 | 24.00 | 730.83 | 24.00 | 310.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 510.17 | 24.02 | 719.83 | 23.96 | 510.17 | 23.98 |
February | 478.50 | 24.04 | 667.83 | 23.97 | 478.50 | 23.99 |
March | 518.17 | 24.02 | 729.83 | 23.98 | 518.00 | 23.99 |
April | 511.33 | 23.99 | 718.00 | 23.98 | 511.33 | 23.99 |
May | 535.67 | 23.99 | 744.00 | 23.99 | 535.67 | 23.99 |
June | 555.00 | 23.99 | 720.00 | 23.99 | 555.00 | 23.99 |
July | 692.17 | 23.99 | 744.00 | 23.99 | 692.17 | 23.99 |
August | 703.50 | 23.99 | 744.00 | 23.99 | 703.50 | 23.99 |
September | 643.67 | 23.99 | 720.00 | 23.99 | 643.67 | 23.99 |
October | 549.67 | 24.00 | 734.83 | 23.98 | 549.67 | 23.98 |
November | 520.83 | 24.00 | 691.17 | 23.97 | 520.00 | 23.98 |
December | 489.50 | 24.02 | 662.17 | 23.99 | 481.67 | 24.01 |
Annual Sum or Average | 6708.17 | 24.00 | 8595.67 | 23.98 | 6699.33 | 23.99 |
Minimum of Months | 478.50 | 23.99 | 662.17 | 23.96 | 478.50 | 23.98 |
Maximum of Months | 703.50 | 24.04 | 744.00 | 23.99 | 703.50 | 24.01 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
February | 672.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
March | 744.00 | 21.99 | 0.00 | 21.99 | 0.00 | 21.99 |
April | 587.67 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
May | 468.00 | 23.52 | 1.33 | 23.53 | 0.00 | 23.53 |
June | 114.00 | 23.69 | 113.83 | 23.85 | 0.00 | 23.85 |
July | 184.17 | 23.84 | 579.00 | 23.93 | 137.33 | 23.92 |
August | 182.17 | 23.77 | 627.00 | 23.88 | 146.83 | 23.87 |
September | 163.00 | 23.65 | 497.67 | 23.83 | 116.00 | 23.82 |
October | 574.33 | 22.76 | 111.17 | 22.95 | 20.33 | 22.97 |
November | 710.67 | 22.18 | 23.83 | 22.17 | 23.83 | 22.17 |
December | 744.00 | 21.62 | 40.00 | 21.59 | 40.00 | 21.56 |
Annual Sum or Average | 5888.00 | 22.45 | 1993.83 | 22.80 | 484.33 | 22.84 |
Minimum of Months | 114.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.56 |
Maximum of Months | 744.00 | 23.84 | 627.00 | 23.93 | 146.83 | 23.92 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.80393 | 26.00517 | 0.20608 | 6.02676 |
February | 672.00000 | 23.30069 | 39.79225 | 0.16053 | 5.72391 |
March | 744.00000 | 22.77184 | 32.45468 | -0.0229 | 5.24978 |
April | 720.00000 | 23.06246 | 23.75822 | -0.0029 | 5.21695 |
May | 744.00000 | 22.77565 | 23.50973 | -1.1079 | 31.10002 |
June | 720.00000 | 23.03956 | 33.80400 | -0.9428 | 24.07974 |
July | 744.00000 | 23.81438 | 49.04072 | -0.5477 | 11.75942 |
August | 744.00000 | 23.92013 | 51.29821 | -0.4827 | 10.03413 |
September | 720.00000 | 23.99359 | 49.89562 | -0.4475 | 9.29420 |
October | 744.00000 | 23.99493 | 30.39483 | 0.31090 | 7.20537 |
November | 720.00000 | 23.99694 | 29.90879 | 0.30523 | 7.15784 |
December | 744.00000 | 23.98659 | 18.94709 | 0.21996 | 6.04403 |
Annual Sum or Average | 8760.00000 | 23.54051 | 34.01738 | -0.1981 | 10.77462 |
Minimum of Months | 672.00000 | 22.77184 | 18.94709 | -1.1079 | 5.21695 |
Maximum of Months | 744.00000 | 23.99694 | 51.29821 | 0.31090 | 31.10002 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.69627 | 26.85804 | 0.04697 | 6.98289 |
February | 672.00000 | 21.86182 | 42.37519 | -0.1185 | 6.62659 |
March | 744.00000 | 22.06853 | 32.81700 | -0.1122 | 6.71376 |
April | 720.00000 | 23.30645 | 22.36692 | 0.17992 | 6.85391 |
May | 744.00000 | 23.46640 | 21.61911 | -0.6957 | 16.48156 |
June | 720.00000 | 23.84452 | 30.98315 | -0.4483 | 9.77947 |
July | 744.00000 | 23.83468 | 48.21827 | -0.3442 | 8.09081 |
August | 744.00000 | 23.79117 | 51.07278 | -0.3318 | 8.00021 |
September | 720.00000 | 23.74694 | 50.41379 | -0.3523 | 8.45003 |
October | 744.00000 | 23.17796 | 31.43535 | 0.21872 | 8.07513 |
November | 720.00000 | 22.61796 | 32.28507 | 0.05685 | 7.04878 |
December | 744.00000 | 22.23015 | 20.34687 | -0.1406 | 7.72860 |
Annual Sum or Average | 8760.00000 | 23.05980 | 34.16812 | -0.1708 | 8.42129 |
Minimum of Months | 672.00000 | 21.86182 | 20.34687 | -0.6957 | 6.62659 |
Maximum of Months | 744.00000 | 23.84452 | 51.07278 | 0.21872 | 16.48156 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.30721 | 27.70401 | 0.12635 | 5.62159 |
February | 672.00000 | 22.81427 | 41.78488 | 0.08418 | 5.52094 |
March | 744.00000 | 23.03594 | 32.87036 | 0.08789 | 5.68948 |
April | 720.00000 | 23.74058 | 23.42359 | 0.22483 | 6.30421 |
May | 744.00000 | 23.82756 | 22.66412 | -0.6526 | 14.19372 |
June | 720.00000 | 23.93983 | 32.13420 | -0.5215 | 10.87336 |
July | 744.00000 | 23.92176 | 49.20435 | -0.4191 | 8.92567 |
August | 744.00000 | 23.91509 | 51.96800 | -0.4037 | 8.58167 |
September | 720.00000 | 23.90657 | 51.29198 | -0.4187 | 8.84070 |
October | 744.00000 | 23.63483 | 32.37622 | 0.25530 | 6.90567 |
November | 720.00000 | 23.34436 | 32.62916 | 0.16991 | 6.06808 |
December | 744.00000 | 22.95691 | 21.45893 | -0.0088 | 5.38296 |
Annual Sum or Average | 8760.00000 | 23.53238 | 34.90403 | -0.1246 | 7.75754 |
Minimum of Months | 672.00000 | 22.81427 | 21.45893 | -0.6526 | 5.38296 |
Maximum of Months | 744.00000 | 23.93983 | 51.96800 | 0.25530 | 14.19372 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.41170 | 23.26145 | 0.73244 | 18.28590 |
February | 672.00000 | 23.37207 | 36.27802 | 0.79498 | 20.36763 |
March | 744.00000 | 23.40182 | 28.03083 | 0.76478 | 19.32121 |
April | 720.00000 | 23.49962 | 19.79876 | 0.78678 | 19.87941 |
May | 744.00000 | 23.53627 | 19.23804 | 0.15920 | 9.12607 |
June | 720.00000 | 23.56054 | 29.46590 | 0.27885 | 9.99073 |
July | 744.00000 | 23.54476 | 46.69451 | 0.37260 | 11.24336 |
August | 744.00000 | 23.52019 | 49.54625 | 0.37959 | 11.39067 |
September | 720.00000 | 23.51377 | 48.67931 | 0.35004 | 11.03571 |
October | 744.00000 | 23.47271 | 28.71597 | 0.82161 | 21.17970 |
November | 720.00000 | 23.41446 | 28.28675 | 0.77100 | 19.65515 |
December | 744.00000 | 23.37510 | 16.80375 | 0.66076 | 16.24909 |
Annual Sum or Average | 8760.00000 | 23.46907 | 31.18828 | 0.57118 | 15.61041 |
Minimum of Months | 672.00000 | 23.37207 | 16.80375 | 0.15920 | 9.12607 |
Maximum of Months | 744.00000 | 23.56054 | 49.54625 | 0.82161 | 21.17970 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.71848 | 31.10466 | 0.35377 | 8.19688 |
February | 672.00000 | 23.18509 | 45.41500 | 0.25232 | 7.20783 |
March | 744.00000 | 23.28724 | 36.84220 | 0.23155 | 6.97345 |
April | 720.00000 | 23.78911 | 27.28083 | 0.35803 | 8.12085 |
May | 744.00000 | 23.78640 | 26.65658 | -0.5134 | 11.01027 |
June | 720.00000 | 23.89382 | 35.80734 | -0.3523 | 7.94998 |
July | 744.00000 | 23.90674 | 52.72131 | -0.2353 | 6.51855 |
August | 744.00000 | 23.91073 | 55.32655 | -0.2060 | 6.20604 |
September | 720.00000 | 23.92425 | 54.48254 | -0.2054 | 6.26110 |
October | 744.00000 | 23.80665 | 35.77844 | 0.43469 | 9.73094 |
November | 720.00000 | 23.65276 | 36.23941 | 0.36245 | 8.46704 |
December | 744.00000 | 23.44553 | 25.24418 | 0.21150 | 6.86975 |
Annual Sum or Average | 8760.00000 | 23.69506 | 38.52004 | 0.05625 | 7.79855 |
Minimum of Months | 672.00000 | 23.18509 | 25.24418 | -0.5134 | 6.20604 |
Maximum of Months | 744.00000 | 23.92425 | 55.32655 | 0.43469 | 11.01027 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73494 | 30.42563 | 0.26323 | 6.61002 |
February | 672.00000 | 23.34716 | 44.12933 | 0.23876 | 6.56052 |
March | 744.00000 | 23.43631 | 35.65511 | 0.21251 | 6.40695 |
April | 720.00000 | 23.80653 | 26.34650 | 0.27587 | 6.77951 |
May | 744.00000 | 23.82656 | 25.54298 | -0.6095 | 13.01103 |
June | 720.00000 | 23.91655 | 34.90226 | -0.4813 | 10.04342 |
July | 744.00000 | 23.91910 | 51.82740 | -0.3672 | 8.07522 |
August | 744.00000 | 23.92760 | 54.54327 | -0.3467 | 7.66447 |
September | 720.00000 | 23.94047 | 53.74199 | -0.3512 | 7.71191 |
October | 744.00000 | 23.84129 | 34.99596 | 0.34464 | 7.85307 |
November | 720.00000 | 23.72332 | 35.29477 | 0.29476 | 7.14492 |
December | 744.00000 | 23.51475 | 24.47421 | 0.15441 | 5.77374 |
Annual Sum or Average | 8760.00000 | 23.74670 | 37.60435 | -0.0328 | 7.81183 |
Minimum of Months | 672.00000 | 23.34716 | 24.47421 | -0.6095 | 5.77374 |
Maximum of Months | 744.00000 | 23.94047 | 54.54327 | 0.34464 | 13.01103 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.91862 | 32.59923 | -0.2034 | 7.10747 |
February | 672.00000 | 21.45939 | 47.45876 | -0.2756 | 7.29868 |
March | 744.00000 | 21.83601 | 37.46759 | -0.2132 | 7.14823 |
April | 720.00000 | 21.97218 | 27.55474 | -0.1219 | 6.53722 |
May | 744.00000 | 21.90541 | 26.47699 | -1.1753 | 35.36998 |
June | 720.00000 | 21.89408 | 35.24548 | -1.0492 | 29.81050 |
July | 744.00000 | 21.79817 | 45.25243 | -1.0511 | 29.85909 |
August | 744.00000 | 21.87621 | 47.43797 | -1.0199 | 28.72810 |
September | 720.00000 | 21.94068 | 48.67874 | -1.0155 | 28.58812 |
October | 744.00000 | 22.06004 | 35.18637 | -0.0903 | 6.57183 |
November | 720.00000 | 21.92693 | 37.04471 | -0.1689 | 6.96095 |
December | 744.00000 | 21.61704 | 25.38246 | -0.3649 | 8.94710 |
Annual Sum or Average | 8760.00000 | 21.85270 | 37.06425 | -0.5645 | 16.97795 |
Minimum of Months | 672.00000 | 21.45939 | 25.38246 | -1.1753 | 6.53722 |
Maximum of Months | 744.00000 | 22.06004 | 48.67874 | -0.0903 | 35.36998 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50295 | 33.28772 | -0.3505 | 8.22887 |
February | 672.00000 | 21.16205 | 48.21722 | -0.3741 | 8.28208 |
March | 744.00000 | 21.59769 | 37.89555 | -0.2885 | 7.64889 |
April | 720.00000 | 21.92953 | 27.64723 | -0.1501 | 6.56642 |
May | 744.00000 | 21.91437 | 26.52272 | -1.1789 | 35.51013 |
June | 720.00000 | 21.90935 | 35.24922 | -1.0408 | 29.49726 |
July | 744.00000 | 21.80342 | 45.27923 | -1.0503 | 29.80806 |
August | 744.00000 | 21.87174 | 47.65293 | -1.0336 | 29.22023 |
September | 720.00000 | 21.92092 | 49.13944 | -1.0447 | 29.64341 |
October | 744.00000 | 21.85723 | 35.73482 | -0.1692 | 6.78044 |
November | 720.00000 | 21.58999 | 37.94764 | -0.2872 | 7.73345 |
December | 744.00000 | 21.15968 | 25.93668 | -0.5204 | 11.27192 |
Annual Sum or Average | 8760.00000 | 21.68754 | 37.45531 | -0.6260 | 17.58257 |
Minimum of Months | 672.00000 | 21.15968 | 25.93668 | -1.1789 | 6.56642 |
Maximum of Months | 744.00000 | 21.92953 | 49.13944 | -0.1501 | 35.51013 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.19883 | 32.15505 | -0.4409 | 9.20074 |
February | 672.00000 | 21.11834 | 46.33785 | -0.3802 | 8.17031 |
March | 744.00000 | 21.37258 | 36.64509 | -0.3582 | 7.99547 |
April | 720.00000 | 21.65164 | 26.45980 | -0.3067 | 7.36928 |
May | 744.00000 | 21.75877 | 25.16699 | -1.3799 | 44.87095 |
June | 720.00000 | 21.81590 | 34.32612 | -1.2610 | 39.06149 |
July | 744.00000 | 21.72070 | 45.70878 | -1.2315 | 37.60752 |
August | 744.00000 | 21.76528 | 48.26699 | -1.2169 | 36.95261 |
September | 720.00000 | 21.78677 | 49.50973 | -1.2165 | 36.87937 |
October | 744.00000 | 21.57548 | 34.83132 | -0.2922 | 7.35689 |
November | 720.00000 | 21.29219 | 36.64959 | -0.3825 | 8.53088 |
December | 744.00000 | 21.04035 | 24.54594 | -0.5423 | 11.30347 |
Annual Sum or Average | 8760.00000 | 21.50986 | 36.63765 | -0.7533 | 21.36416 |
Minimum of Months | 672.00000 | 21.04035 | 24.54594 | -1.3799 | 7.35689 |
Maximum of Months | 744.00000 | 21.81590 | 49.50973 | -0.2922 | 44.87095 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.90242 | 32.52525 | -0.2089 | 6.93346 |
February | 672.00000 | 21.52147 | 46.84953 | -0.2551 | 7.05926 |
March | 744.00000 | 21.88458 | 37.22496 | -0.1954 | 6.83859 |
April | 720.00000 | 22.11210 | 27.37374 | -0.0871 | 6.75979 |
May | 744.00000 | 22.10453 | 26.33269 | -1.1042 | 33.54078 |
June | 720.00000 | 21.96626 | 35.27103 | -1.0159 | 29.09593 |
July | 744.00000 | 21.84001 | 45.19456 | -1.0169 | 28.76974 |
August | 744.00000 | 21.92663 | 47.26327 | -0.9869 | 27.78666 |
September | 720.00000 | 22.01425 | 48.47201 | -0.9834 | 27.88805 |
October | 744.00000 | 22.12429 | 35.04085 | -0.0693 | 6.64710 |
November | 720.00000 | 21.92132 | 37.11249 | -0.1744 | 6.86483 |
December | 744.00000 | 21.63548 | 25.34148 | -0.3574 | 8.67302 |
Annual Sum or Average | 8760.00000 | 21.91500 | 36.91857 | -0.5399 | 16.46791 |
Minimum of Months | 672.00000 | 21.52147 | 25.34148 | -1.1042 | 6.64710 |
Maximum of Months | 744.00000 | 22.12429 | 48.47201 | -0.0693 | 33.54078 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.44629 | 33.31247 | -0.3635 | 8.13734 |
February | 672.00000 | 21.20981 | 47.76914 | -0.3539 | 7.90135 |
March | 744.00000 | 21.66821 | 37.64685 | -0.2657 | 7.25711 |
April | 720.00000 | 22.09180 | 27.43382 | -0.1104 | 6.74820 |
May | 744.00000 | 22.11387 | 26.38337 | -1.1076 | 33.73736 |
June | 720.00000 | 21.97709 | 35.29435 | -1.0089 | 28.88069 |
July | 744.00000 | 21.84364 | 45.25993 | -1.0165 | 28.75052 |
August | 744.00000 | 21.92445 | 47.45661 | -0.9998 | 28.24654 |
September | 720.00000 | 22.00046 | 48.81925 | -1.0111 | 28.83122 |
October | 744.00000 | 21.96333 | 35.41703 | -0.1397 | 6.73214 |
November | 720.00000 | 21.54744 | 38.00620 | -0.3004 | 7.69283 |
December | 744.00000 | 21.13177 | 25.93501 | -0.5212 | 11.05225 |
Annual Sum or Average | 8760.00000 | 21.74580 | 37.30930 | -0.6018 | 17.06065 |
Minimum of Months | 672.00000 | 21.13177 | 25.93501 | -1.1076 | 6.73214 |
Maximum of Months | 744.00000 | 22.11387 | 48.81925 | -0.1104 | 33.73736 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.89280 | 32.89256 | -0.2287 | 7.63720 |
February | 672.00000 | 21.41415 | 48.18565 | -0.3060 | 7.92048 |
March | 744.00000 | 21.82110 | 37.81453 | -0.2296 | 7.64946 |
April | 720.00000 | 21.93667 | 27.67882 | -0.1285 | 6.80226 |
May | 744.00000 | 21.86257 | 26.54488 | -1.1831 | 35.95749 |
June | 720.00000 | 21.88015 | 35.37010 | -1.0345 | 29.42464 |
July | 744.00000 | 21.78932 | 45.50428 | -1.0377 | 29.50074 |
August | 744.00000 | 21.86154 | 47.77193 | -1.0100 | 28.53280 |
September | 720.00000 | 21.90767 | 49.27984 | -1.0181 | 28.84437 |
October | 744.00000 | 22.00452 | 35.52419 | -0.1126 | 6.89569 |
November | 720.00000 | 21.87315 | 37.69374 | -0.1974 | 7.45153 |
December | 744.00000 | 21.57496 | 25.56667 | -0.4012 | 9.81269 |
Annual Sum or Average | 8760.00000 | 21.82065 | 37.39743 | -0.5759 | 17.26856 |
Minimum of Months | 672.00000 | 21.41415 | 25.56667 | -1.1831 | 6.80226 |
Maximum of Months | 744.00000 | 22.00452 | 49.27984 | -0.1126 | 35.95749 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42350 | 33.70016 | -0.3940 | 9.04029 |
February | 672.00000 | 21.08696 | 48.99495 | -0.4147 | 9.11010 |
March | 744.00000 | 21.56146 | 38.26751 | -0.3124 | 8.19469 |
April | 720.00000 | 21.89730 | 27.78404 | -0.1565 | 6.81879 |
May | 744.00000 | 21.87217 | 26.61311 | -1.1864 | 36.05354 |
June | 720.00000 | 21.89481 | 35.38089 | -1.0261 | 29.09009 |
July | 744.00000 | 21.79442 | 45.52171 | -1.0369 | 29.43830 |
August | 744.00000 | 21.85703 | 48.00991 | -1.0237 | 29.00237 |
September | 720.00000 | 21.88788 | 49.79915 | -1.0475 | 29.89271 |
October | 744.00000 | 21.77842 | 36.14650 | -0.1994 | 7.22546 |
November | 720.00000 | 21.49394 | 38.69131 | -0.3302 | 8.47784 |
December | 744.00000 | 21.06752 | 26.18960 | -0.5724 | 12.59147 |
Annual Sum or Average | 8760.00000 | 21.63738 | 37.83404 | -0.6436 | 17.97643 |
Minimum of Months | 672.00000 | 21.06752 | 26.18960 | -1.1864 | 6.81879 |
Maximum of Months | 744.00000 | 21.89730 | 49.79915 | -0.1565 | 36.05354 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.14486 | 33.23463 | -0.0945 | 7.04200 |
February | 672.00000 | 21.67706 | 47.04616 | -0.1934 | 6.91620 |
March | 744.00000 | 21.94748 | 37.86731 | -0.1760 | 6.92348 |
April | 720.00000 | 21.89767 | 28.68143 | -0.1642 | 6.71348 |
May | 744.00000 | 21.84215 | 27.60748 | -1.2634 | 39.54210 |
June | 720.00000 | 21.85055 | 36.33402 | -1.1472 | 34.06588 |
July | 744.00000 | 21.77828 | 45.99891 | -1.1149 | 32.67124 |
August | 744.00000 | 21.85655 | 47.95104 | -1.0716 | 30.97575 |
September | 720.00000 | 21.93237 | 49.13050 | -1.0399 | 29.78325 |
October | 744.00000 | 22.13368 | 35.73930 | -0.0576 | 6.67898 |
November | 720.00000 | 22.10382 | 37.28162 | -0.0905 | 6.91909 |
December | 744.00000 | 21.90811 | 26.58506 | -0.2266 | 7.92480 |
Annual Sum or Average | 8760.00000 | 21.92448 | 37.71128 | -0.5556 | 18.08935 |
Minimum of Months | 672.00000 | 21.67706 | 26.58506 | -1.2634 | 6.67898 |
Maximum of Months | 744.00000 | 22.14486 | 49.13050 | -0.0576 | 39.54210 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.83414 | 31.01476 | 0.31686 | 7.29320 |
February | 672.00000 | 23.79563 | 43.64324 | 0.38349 | 8.33790 |
March | 744.00000 | 23.86218 | 35.33619 | 0.36595 | 8.02580 |
April | 720.00000 | 23.97874 | 26.53349 | 0.39876 | 8.45222 |
May | 744.00000 | 23.99303 | 25.67634 | -0.4147 | 8.70573 |
June | 720.00000 | 23.99598 | 35.20028 | -0.2934 | 6.92598 |
July | 744.00000 | 23.99574 | 51.93773 | -0.1874 | 5.94420 |
August | 744.00000 | 23.99496 | 54.72274 | -0.1803 | 5.81267 |
September | 720.00000 | 23.99367 | 54.03666 | -0.2055 | 6.01019 |
October | 744.00000 | 23.93459 | 35.48439 | 0.42537 | 9.17632 |
November | 720.00000 | 23.86612 | 35.67926 | 0.36504 | 8.16454 |
December | 744.00000 | 23.76153 | 25.12206 | 0.23377 | 6.36388 |
Annual Sum or Average | 8760.00000 | 23.91774 | 37.81814 | 0.09872 | 7.42747 |
Minimum of Months | 672.00000 | 23.76153 | 25.12206 | -0.4147 | 5.81267 |
Maximum of Months | 744.00000 | 23.99598 | 54.72274 | 0.42537 | 9.17632 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.91886 | 30.22590 | 0.37111 | 8.01110 |
February | 672.00000 | 23.90361 | 42.69237 | 0.44668 | 9.35472 |
March | 744.00000 | 23.94367 | 34.53975 | 0.42090 | 8.85502 |
April | 720.00000 | 23.99139 | 26.04420 | 0.43000 | 8.98651 |
May | 744.00000 | 23.99512 | 25.26420 | -0.3757 | 8.06392 |
June | 720.00000 | 23.99673 | 34.85598 | -0.2572 | 6.51532 |
July | 744.00000 | 23.99652 | 51.58517 | -0.1515 | 5.69361 |
August | 744.00000 | 23.99602 | 54.35929 | -0.1440 | 5.57080 |
September | 720.00000 | 23.99526 | 53.65283 | -0.1689 | 5.72636 |
October | 744.00000 | 23.96903 | 34.91485 | 0.46279 | 9.81463 |
November | 720.00000 | 23.94377 | 34.91171 | 0.41696 | 8.95113 |
December | 744.00000 | 23.87486 | 24.25717 | 0.29764 | 6.98467 |
Annual Sum or Average | 8760.00000 | 23.96064 | 37.22976 | 0.14370 | 7.69895 |
Minimum of Months | 672.00000 | 23.87486 | 24.25717 | -0.3757 | 5.57080 |
Maximum of Months | 744.00000 | 23.99673 | 54.35929 | 0.46279 | 9.81463 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.89299 | 29.56910 | 1.01388 | 28.64969 |
February | 672.00000 | 23.92211 | 41.69335 | 1.08494 | 31.48985 |
March | 744.00000 | 23.93410 | 33.79567 | 1.06045 | 30.49388 |
April | 720.00000 | 23.97846 | 25.83927 | 1.10395 | 32.38545 |
May | 744.00000 | 23.98876 | 25.24954 | 0.59709 | 16.33653 |
June | 720.00000 | 23.99221 | 34.86340 | 0.73441 | 19.92943 |
July | 744.00000 | 23.99303 | 51.13566 | 0.82628 | 22.74816 |
August | 744.00000 | 23.99300 | 53.78669 | 0.83173 | 22.91385 |
September | 720.00000 | 23.99287 | 53.01644 | 0.79286 | 21.56537 |
October | 744.00000 | 23.95244 | 34.40036 | 1.12182 | 33.30422 |
November | 720.00000 | 23.90682 | 34.17009 | 1.05346 | 30.34122 |
December | 744.00000 | 23.86530 | 23.54641 | 0.93618 | 25.73064 |
Annual Sum or Average | 8760.00000 | 23.95106 | 36.71254 | 0.92857 | 26.28451 |
Minimum of Months | 672.00000 | 23.86530 | 23.54641 | 0.59709 | 16.33653 |
Maximum of Months | 744.00000 | 23.99303 | 53.78669 | 1.12182 | 33.30422 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.77935 | 26.56826 | -0.2842 | 6.87760 |
February | 672.00000 | 21.39429 | 41.65591 | -0.2894 | 6.89627 |
March | 744.00000 | 21.75671 | 31.74672 | -0.2572 | 6.80766 |
April | 720.00000 | 22.99404 | 21.21237 | -0.0169 | 5.35551 |
May | 744.00000 | 23.51661 | 20.04232 | -0.8472 | 20.38033 |
June | 720.00000 | 23.95880 | 29.45036 | -0.6145 | 13.03993 |
July | 744.00000 | 23.94105 | 46.63080 | -0.5057 | 10.55520 |
August | 744.00000 | 23.86686 | 49.58020 | -0.5169 | 10.76628 |
September | 720.00000 | 23.75767 | 49.13821 | -0.5620 | 11.81024 |
October | 744.00000 | 22.80402 | 30.50192 | -0.0005 | 6.14229 |
November | 720.00000 | 21.96406 | 31.62888 | -0.2050 | 6.43650 |
December | 744.00000 | 21.37934 | 19.68287 | -0.4254 | 8.99177 |
Annual Sum or Average | 8760.00000 | 22.76614 | 33.08659 | -0.3781 | 9.53018 |
Minimum of Months | 672.00000 | 21.37934 | 19.68287 | -0.8472 | 5.35551 |
Maximum of Months | 744.00000 | 23.95880 | 49.58020 | -0.0005 | 20.38033 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.21580 | 29.48729 | -0.1866 | 5.94665 |
February | 672.00000 | 21.61567 | 44.68497 | -0.2448 | 6.34007 |
March | 744.00000 | 22.02140 | 34.83593 | -0.2011 | 6.15983 |
April | 720.00000 | 23.23097 | 24.65136 | 0.03340 | 5.33713 |
May | 744.00000 | 23.59791 | 23.73481 | -0.8368 | 19.95886 |
June | 720.00000 | 23.93095 | 33.05014 | -0.6481 | 13.93656 |
July | 744.00000 | 23.89989 | 50.16520 | -0.5447 | 11.41092 |
August | 744.00000 | 23.86456 | 53.04374 | -0.5386 | 11.20620 |
September | 720.00000 | 23.83195 | 52.40463 | -0.5558 | 11.60822 |
October | 744.00000 | 23.20111 | 33.53110 | 0.08753 | 6.00868 |
November | 720.00000 | 22.37041 | 34.54368 | -0.1158 | 5.65287 |
December | 744.00000 | 21.68425 | 22.86616 | -0.3574 | 7.96023 |
Annual Sum or Average | 8760.00000 | 22.96219 | 36.35141 | -0.3434 | 9.31989 |
Minimum of Months | 672.00000 | 21.61567 | 22.86616 | -0.8368 | 5.33713 |
Maximum of Months | 744.00000 | 23.93095 | 53.04374 | 0.08753 | 19.95886 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.10072 | 27.46818 | -0.1897 | 6.12518 |
February | 672.00000 | 21.58571 | 42.57572 | -0.2299 | 6.31953 |
March | 744.00000 | 21.99482 | 32.66649 | -0.1826 | 6.24189 |
April | 720.00000 | 23.36498 | 22.17287 | 0.10186 | 5.74128 |
May | 744.00000 | 23.69559 | 21.24113 | -0.7389 | 16.93121 |
June | 720.00000 | 23.93787 | 30.72305 | -0.5586 | 11.73051 |
July | 744.00000 | 23.94389 | 47.61995 | -0.4458 | 9.43256 |
August | 744.00000 | 23.90354 | 50.50596 | -0.4442 | 9.35044 |
September | 720.00000 | 23.84644 | 49.94076 | -0.4780 | 10.03371 |
October | 744.00000 | 23.02039 | 31.46002 | 0.07807 | 6.44358 |
November | 720.00000 | 22.19363 | 32.56215 | -0.1322 | 6.08137 |
December | 744.00000 | 21.61636 | 20.76520 | -0.3561 | 8.07719 |
Annual Sum or Average | 8760.00000 | 22.94034 | 34.07567 | -0.2989 | 8.56224 |
Minimum of Months | 672.00000 | 21.58571 | 20.76520 | -0.7389 | 5.74128 |
Maximum of Months | 744.00000 | 23.94389 | 50.50596 | 0.10186 | 16.93121 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.05072 | 25.95136 | -0.2300 | 6.36440 |
February | 672.00000 | 21.68251 | 40.76045 | -0.2310 | 6.29882 |
March | 744.00000 | 22.04058 | 31.03134 | -0.1998 | 6.31552 |
April | 720.00000 | 23.28604 | 20.66273 | 0.04243 | 5.41397 |
May | 744.00000 | 23.74721 | 19.60189 | -0.7784 | 17.96778 |
June | 720.00000 | 23.99315 | 29.13543 | -0.6028 | 12.71435 |
July | 744.00000 | 23.98062 | 46.26658 | -0.4927 | 10.27156 |
August | 744.00000 | 23.94685 | 49.10318 | -0.4918 | 10.19987 |
September | 720.00000 | 23.90410 | 48.51485 | -0.5173 | 10.75295 |
October | 744.00000 | 23.09261 | 29.84220 | 0.05876 | 6.12900 |
November | 720.00000 | 22.26886 | 30.88862 | -0.1432 | 6.01787 |
December | 744.00000 | 21.61526 | 19.21233 | -0.3776 | 8.26288 |
Annual Sum or Average | 8760.00000 | 22.97360 | 32.51676 | -0.3314 | 8.91557 |
Minimum of Months | 672.00000 | 21.61526 | 19.21233 | -0.7784 | 5.41397 |
Maximum of Months | 744.00000 | 23.99315 | 49.10318 | 0.05876 | 17.96778 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.662601E+11 | 123466.62 | 31-JAN-16:02 | 709.82 | 0.192620E+12 | 0.00 | 0.258880E+12 | 2.86 | 3.81 | 31-JAN-19:01 | 0.00 | 0.00 |
February | 0.206309E+11 | 77331.00 | 18-FEB-16:01 | 550.54 | 0.603271E+11 | 0.00 | 0.809580E+11 | 2.48 | 3.42 | 18-FEB-16:01 | 0.00 | 0.00 |
March | 0.623674E+11 | 123464.78 | 16-MAR-15:02 | 673.74 | 0.177379E+12 | 0.00 | 0.239747E+12 | 2.67 | 3.87 | 17-MAR-21:51 | 0.00 | 0.00 |
April | 0.166333E+12 | 167216.42 | 14-APR-18:03 | 719.71 | 0.486790E+12 | 0.00 | 0.653123E+12 | 2.92 | 3.91 | 03-APR-21:51 | 0.00 | 0.00 |
May | 0.215999E+12 | 180557.38 | 31-MAY-18:03 | 744.00 | 0.622340E+12 | 0.00 | 0.838339E+12 | 2.87 | 3.87 | 13-MAY-21:51 | 0.00 | 0.00 |
June | 0.289196E+12 | 234846.93 | 30-JUN-18:07 | 720.00 | 0.803172E+12 | 0.00 | 0.109237E+13 | 2.81 | 3.64 | 20-JUN-06:41 | 0.00 | 0.00 |
July | 0.306869E+12 | 206204.27 | 20-JUL-18:03 | 744.00 | 0.910379E+12 | 0.00 | 0.121725E+13 | 2.98 | 3.96 | 14-JUL-01:00 | 0.00 | 0.00 |
August | 0.298287E+12 | 213280.84 | 25-AUG-15:03 | 744.00 | 0.886989E+12 | 0.00 | 0.118528E+13 | 3.00 | 4.10 | 04-AUG-21:52 | 0.00 | 0.00 |
September | 0.262984E+12 | 198351.79 | 08-SEP-18:03 | 720.00 | 0.811286E+12 | 0.00 | 0.107427E+13 | 3.08 | 4.24 | 03-SEP-08:53 | 0.00 | 0.00 |
October | 0.146681E+12 | 175546.06 | 01-OCT-18:03 | 734.36 | 0.436636E+12 | 0.00 | 0.583318E+12 | 2.93 | 3.95 | 09-OCT-08:51 | 0.00 | 0.00 |
November | 0.706696E+11 | 127397.97 | 01-NOV-15:02 | 684.09 | 0.206747E+12 | 0.00 | 0.277416E+12 | 2.84 | 4.22 | 11-NOV-22:52 | 0.00 | 0.00 |
December | 0.391849E+11 | 103548.47 | 25-DEC-16:02 | 621.29 | 0.113102E+12 | 0.00 | 0.152287E+12 | 2.52 | 3.54 | 23-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.194546E+13 | 8365.55 | 0.570777E+13 | 0.00 | 0.765323E+13 | 2.83 | 0.00 | 0.00 | ||||
Minimum of Months | 0.206309E+11 | 77331.00 | 550.54 | 0.603271E+11 | 0.00 | 0.809580E+11 | 2.48 | 3.42 | 0.00 | 0.00 | ||
Maximum of Months | 0.306869E+12 | 234846.93 | 744.00 | 0.910379E+12 | 0.00 | 0.121725E+13 | 3.08 | 4.24 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.196446E+11 | 0.00 | 376.00 | 110182.52 | 02-JAN-07:00 | 0.00 | 42.25 | 51.34 | 0.10 | 0.00 | 0.02 | 0.32 | 02-JAN-07:00 |
February | 0.218544E+11 | 0.00 | 464.52 | 106830.65 | 02-FEB-03:40 | 0.00 | 42.23 | 54.23 | 0.13 | 0.00 | 0.03 | 0.31 | 02-FEB-03:40 |
March | 0.142722E+11 | 0.00 | 320.23 | 104907.50 | 27-MAR-08:62 | 0.00 | 40.25 | 48.17 | 0.08 | 0.00 | 0.02 | 0.31 | 27-MAR-08:62 |
April | 0.937120E+09 | 0.00 | 40.34 | 76911.88 | 21-APR-04:31 | 0.00 | 38.88 | 40.25 | 0.00 | 0.00 | 0.00 | 0.23 | 21-APR-04:31 |
May | 0.102702E+09 | 0.00 | 5.73 | 50965.36 | 01-MAY-08:53 | 0.00 | 37.72 | 37.91 | 0.00 | 0.00 | 0.00 | 0.15 | 01-MAY-08:53 |
June | 15681340.33 | 0.00 | 0.88 | 13418.02 | 05-JUN-08:07 | 0.00 | 42.80 | 42.82 | 0.00 | 0.00 | 0.00 | 0.04 | 05-JUN-08:07 |
July | 24744114.34 | 0.00 | 1.16 | 12321.75 | 18-JUL-08:04 | 0.00 | 44.59 | 44.62 | 0.00 | 0.00 | 0.00 | 0.04 | 18-JUL-08:04 |
August | 25314541.71 | 0.00 | 1.31 | 25895.03 | 29-AUG-08:04 | 0.00 | 44.83 | 44.85 | 0.00 | 0.00 | 0.00 | 0.08 | 29-AUG-08:04 |
September | 40739530.47 | 0.00 | 1.62 | 20560.29 | 29-SEP-08:24 | 0.00 | 43.69 | 43.72 | 0.00 | 0.00 | 0.00 | 0.06 | 29-SEP-08:24 |
October | 0.601638E+10 | 0.00 | 127.59 | 92579.44 | 25-OCT-05:20 | 0.00 | 39.01 | 42.66 | 0.03 | 0.00 | 0.01 | 0.27 | 25-OCT-05:20 |
November | 0.137905E+11 | 0.00 | 302.52 | 120156.83 | 23-NOV-21:55 | 0.00 | 40.74 | 48.41 | 0.07 | 0.00 | 0.02 | 0.35 | 23-NOV-21:55 |
December | 0.306595E+11 | 0.00 | 523.92 | 125897.39 | 06-DEC-22:05 | 0.00 | 42.79 | 55.01 | 0.17 | 0.00 | 0.03 | 0.37 | 06-DEC-22:05 |
Annual Sum or Average | 0.107384E+12 | 0.00 | 2165.82 | 0.00 | 41.64 | 46.12 | 0.05 | 0.00 | 0.01 | ||||
Minimum of Months | 15681340.33 | 0.00 | 0.88 | 12321.75 | 0.00 | 37.72 | 37.91 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.306595E+11 | 0.00 | 523.92 | 125897.39 | 0.00 | 44.83 | 55.01 | 0.17 | 0.00 | 0.03 | 0.37 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.107127E+12 | 0.00 | 425.99 | 0.106705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 182317.52 | 31-JAN-16:30 | 182317.52 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.258547E+11 | 0.00 | 257.64 | 0.258307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104697.61 | 18-FEB-14:00 | 104697.61 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.116108E+12 | 0.00 | 454.12 | 0.116108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 202958.26 | 20-MAR-18:10 | 202958.26 | 20-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.320815E+12 | 0.00 | 669.41 | 0.320815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260823.15 | 14-APR-18:10 | 260823.15 | 14-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.417603E+12 | 0.00 | 736.17 | 0.417603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272771.71 | 31-MAY-18:20 | 272771.71 | 31-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.534011E+12 | 0.00 | 720.00 | 0.533129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345256.04 | 17-JUN-17:17 | 328173.15 | 28-JUN-18:30 | 0.00 | 0.00 | 0.00 |
July | 0.620124E+12 | 0.00 | 744.00 | 0.542711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 415516.76 | 13-JUL-21:00 | 324441.56 | 21-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.604339E+12 | 0.00 | 744.00 | 0.534345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 447182.11 | 18-AUG-22:00 | 314809.99 | 15-AUG-19:20 | 0.00 | 0.00 | 0.00 |
September | 0.555024E+12 | 0.00 | 720.00 | 0.479022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 476421.37 | 10-SEP-20:40 | 310647.27 | 08-SEP-19:20 | 0.00 | 0.00 | 0.00 |
October | 0.282703E+12 | 0.00 | 628.43 | 0.274634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 342867.84 | 02-OCT-20:00 | 279915.26 | 03-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.122584E+12 | 0.00 | 461.36 | 0.108767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 203902.02 | 01-NOV-18:10 | 203902.02 | 01-NOV-18:10 | 0.00 | 0.00 | 0.00 |
December | 0.569862E+11 | 0.00 | 344.55 | 0.569862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158976.86 | 22-DEC-16:03 | 158976.86 | 22-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.376328E+13 | 0.00 | 6905.68 | 0.351666E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.258547E+11 | 0.00 | 257.64 | 0.258307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104697.61 | 104697.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.620124E+12 | 0.00 | 744.00 | 0.542711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 476421.37 | 328173.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.198678E+11 | 0.00 | 362.33 | 0.197345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28050.24 | 31-JAN-16:02 | 28050.24 | 31-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.520636E+10 | 0.00 | 212.00 | 0.520636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23246.09 | 18-FEB-14:00 | 23246.09 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.213418E+11 | 0.00 | 408.00 | 0.213418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28577.87 | 16-MAR-15:02 | 28577.87 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.508091E+11 | 0.00 | 662.50 | 0.508091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32710.68 | 14-APR-15:01 | 32710.68 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.644422E+11 | 0.00 | 735.50 | 0.644422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33359.99 | 31-MAY-17:40 | 33359.99 | 31-MAY-17:40 | 0.00 | 0.00 | 0.00 |
June | 0.750470E+11 | 0.00 | 720.00 | 0.749599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40819.70 | 17-JUN-16:00 | 36580.57 | 28-JUN-17:30 | 0.00 | 0.00 | 0.00 |
July | 0.881593E+11 | 0.00 | 744.00 | 0.767338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53022.95 | 27-JUL-07:10 | 36037.94 | 19-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.878394E+11 | 0.00 | 744.00 | 0.758079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56729.28 | 05-AUG-08:20 | 36161.20 | 25-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.825085E+11 | 0.00 | 720.00 | 0.694566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60390.84 | 04-SEP-08:20 | 34860.88 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.444327E+11 | 0.00 | 603.22 | 0.429241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48769.00 | 03-OCT-07:00 | 34112.43 | 01-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.228037E+11 | 0.00 | 407.33 | 0.196608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44169.39 | 12-NOV-14:30 | 28784.86 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.111667E+11 | 0.00 | 250.33 | 0.111667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26242.78 | 25-DEC-16:00 | 26242.78 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573625E+12 | 0.00 | 6569.22 | 0.532244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.520636E+10 | 0.00 | 212.00 | 0.520636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23246.09 | 23246.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.881593E+11 | 0.00 | 744.00 | 0.767338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60390.84 | 36580.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.244179E+10 | 0.00 | 387.28 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18453.15 | 08-JAN-20:12 | 16931.01 | 25-JAN-21:31 | 0.00 | 0.00 | 0.00 |
February | 0.771818E+09 | 0.00 | 188.68 | 0.488945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18074.47 | 01-FEB-17:11 | 18074.47 | 01-FEB-17:11 | 0.00 | 0.00 | 0.00 |
March | 0.168173E+10 | 0.00 | 299.95 | 0.119659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17247.54 | 23-MAR-21:11 | 17247.54 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.764645E+10 | 0.00 | 580.34 | 0.739679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17779.32 | 06-APR-21:51 | 17779.32 | 06-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.941312E+10 | 0.00 | 627.44 | 0.934154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17589.18 | 20-MAY-08:61 | 17589.18 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.126525E+11 | 0.00 | 655.21 | 0.117393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17823.91 | 16-JUN-06:41 | 17823.91 | 16-JUN-06:41 | 0.00 | 0.00 | 0.00 |
July | 0.123995E+11 | 0.00 | 693.36 | 0.898585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19293.58 | 27-JUL-08:11 | 18091.72 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.120498E+11 | 0.00 | 668.95 | 0.851087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20092.79 | 04-AUG-21:51 | 17446.90 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.103157E+11 | 0.00 | 616.26 | 0.691159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21810.19 | 10-SEP-21:51 | 16681.84 | 18-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.590752E+10 | 0.00 | 509.98 | 0.473159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19115.25 | 03-OCT-08:61 | 17677.30 | 17-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.258746E+10 | 0.00 | 381.06 | 0.200001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19537.47 | 11-NOV-22:52 | 17249.43 | 21-NOV-21:11 | 0.00 | 0.00 | 0.00 |
December | 0.114059E+10 | 0.00 | 236.46 | 0.113670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17689.72 | 14-DEC-17:01 | 17689.72 | 14-DEC-17:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790080E+11 | 0.00 | 5844.96 | 0.646093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.771818E+09 | 0.00 | 188.68 | 0.488945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17247.54 | 16681.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.126525E+11 | 0.00 | 693.36 | 0.117393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21810.19 | 18091.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.763718E+09 | 0.00 | 170.31 | 0.677089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16928.25 | 08-JAN-16:01 | 16574.77 | 07-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.224723E+09 | 0.00 | 75.33 | 0.148355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16627.02 | 01-FEB-17:11 | 16627.02 | 01-FEB-17:11 | 0.00 | 0.00 | 0.00 |
March | 0.107361E+10 | 0.00 | 214.95 | 0.759694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16718.12 | 23-MAR-21:11 | 16718.12 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.664935E+10 | 0.00 | 558.26 | 0.640981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17487.47 | 26-APR-21:51 | 17487.47 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.913188E+10 | 0.00 | 623.85 | 0.906060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17587.96 | 20-MAY-08:61 | 17587.96 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.127978E+11 | 0.00 | 656.96 | 0.118907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18024.19 | 10-JUN-07:31 | 18024.19 | 10-JUN-07:31 | 0.00 | 0.00 | 0.00 |
July | 0.123478E+11 | 0.00 | 693.65 | 0.896681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19197.54 | 27-JUL-08:11 | 18222.44 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.114297E+11 | 0.00 | 665.72 | 0.794854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20146.84 | 28-AUG-18:31 | 17252.61 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.922112E+10 | 0.00 | 609.34 | 0.591954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21415.51 | 10-SEP-21:51 | 16579.31 | 18-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.424932E+10 | 0.00 | 424.28 | 0.321490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18731.56 | 03-OCT-08:61 | 17038.59 | 17-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.108251E+10 | 0.00 | 223.53 | 0.750919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19238.48 | 11-NOV-22:52 | 16572.44 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.223835E+09 | 0.00 | 60.36 | 0.223770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16560.68 | 27-DEC-16:01 | 16560.68 | 27-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.691954E+11 | 0.00 | 4976.54 | 0.559707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.223835E+09 | 0.00 | 60.36 | 0.148355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16560.68 | 16560.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127978E+11 | 0.00 | 693.65 | 0.118907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21415.51 | 18222.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.349990E+11 | 0.00 | 508.41 | 0.337504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44243.94 | 14-JAN-13:40 | 44243.94 | 14-JAN-13:40 | 0.00 | 0.00 | 0.00 |
February | 0.102901E+11 | 0.00 | 248.26 | 0.864185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34150.63 | 01-FEB-14:30 | 34150.63 | 01-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.972669E+10 | 0.00 | 293.93 | 0.855289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29209.87 | 18-MAR-13:40 | 28997.97 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.294415E+11 | 0.00 | 583.17 | 0.292288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30450.28 | 14-APR-13:40 | 30450.28 | 14-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.288836E+11 | 0.00 | 631.03 | 0.288715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25269.67 | 09-MAY-17:12 | 25269.67 | 09-MAY-17:12 | 0.00 | 0.00 | 0.00 |
June | 0.421973E+11 | 0.00 | 715.08 | 0.397816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34484.25 | 17-JUN-19:10 | 33091.97 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.444588E+11 | 0.00 | 732.11 | 0.261608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33913.46 | 21-JUL-20:20 | 28759.16 | 07-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.476579E+11 | 0.00 | 727.36 | 0.281020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38861.38 | 28-AUG-12:30 | 35704.85 | 27-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.482183E+11 | 0.00 | 701.50 | 0.308877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42008.70 | 28-SEP-13:30 | 42008.70 | 28-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.394231E+11 | 0.00 | 608.17 | 0.340280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44935.79 | 02-OCT-12:40 | 44231.17 | 18-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.282151E+11 | 0.00 | 448.50 | 0.254329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46510.87 | 20-NOV-14:30 | 46510.87 | 20-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.251000E+11 | 0.00 | 424.66 | 0.250053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43873.77 | 25-DEC-13:30 | 43873.77 | 25-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388611E+12 | 0.00 | 6622.17 | 0.318444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.972669E+10 | 0.00 | 248.26 | 0.855289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25269.67 | 25269.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.482183E+11 | 0.00 | 732.11 | 0.397816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46510.87 | 46510.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.696330E+10 | 0.00 | 283.23 | 0.572531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118185.18 | 08-JAN-20:12 | 104259.48 | 27-JAN-22:01 | 0.00 | 0.00 | 0.00 |
February | 0.641823E+10 | 0.00 | 277.07 | 0.266909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107967.58 | 18-FEB-19:12 | 99378.71 | 09-FEB-22:51 | 0.00 | 0.00 | 0.00 |
March | 0.121340E+11 | 0.00 | 322.23 | 0.817614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106959.05 | 23-MAR-21:11 | 106959.05 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.356544E+11 | 0.00 | 431.48 | 0.343647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109002.21 | 26-APR-21:51 | 109002.21 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.505852E+11 | 0.00 | 499.60 | 0.501903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110593.48 | 20-MAY-08:61 | 110593.48 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.714484E+11 | 0.00 | 592.72 | 0.667749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113080.27 | 19-JUN-07:01 | 113080.27 | 19-JUN-07:01 | 0.00 | 0.00 | 0.00 |
July | 0.759793E+11 | 0.00 | 607.60 | 0.559519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118385.76 | 27-JUL-08:11 | 113226.27 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.682470E+11 | 0.00 | 568.91 | 0.474723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126732.58 | 28-AUG-18:31 | 107949.18 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.574238E+11 | 0.00 | 497.63 | 0.380304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134706.83 | 10-SEP-21:51 | 107945.87 | 29-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.275837E+11 | 0.00 | 403.43 | 0.212073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115410.06 | 03-OCT-08:61 | 107897.05 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.100031E+11 | 0.00 | 290.02 | 0.629661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125604.93 | 12-NOV-22:52 | 103891.55 | 21-NOV-21:11 | 0.00 | 0.00 | 0.00 |
December | 0.328696E+10 | 0.00 | 180.03 | 0.321716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102583.69 | 26-DEC-21:31 | 102583.69 | 26-DEC-21:31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425727E+12 | 0.00 | 4953.94 | 0.340076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.328696E+10 | 0.00 | 180.03 | 0.266909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102583.69 | 99378.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.759793E+11 | 0.00 | 607.60 | 0.667749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134706.83 | 113226.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.242675E+10 | 0.00 | 389.48 | 0.217024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16258.60 | 08-JAN-20:12 | 16009.07 | 27-JAN-09:51 | 0.00 | 0.00 | 0.00 |
February | 0.110479E+10 | 0.00 | 217.67 | 0.686261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15360.94 | 18-FEB-09:02 | 14740.64 | 21-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.195640E+10 | 0.00 | 333.59 | 0.141473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15142.12 | 16-MAR-08:51 | 15142.12 | 16-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.761919E+10 | 0.00 | 603.61 | 0.738330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17070.41 | 12-APR-08:51 | 17070.41 | 12-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.948417E+10 | 0.00 | 646.45 | 0.941994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17068.99 | 31-MAY-07:41 | 17068.99 | 31-MAY-07:41 | 0.00 | 0.00 | 0.00 |
June | 0.128943E+11 | 0.00 | 671.20 | 0.120830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17070.49 | 22-JUN-07:11 | 17070.49 | 22-JUN-07:11 | 0.00 | 0.00 | 0.00 |
July | 0.132381E+11 | 0.00 | 709.59 | 0.988358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18613.05 | 27-JUL-08:11 | 17050.55 | 04-JUL-07:31 | 0.00 | 0.00 | 0.00 |
August | 0.127315E+11 | 0.00 | 682.91 | 0.928528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18375.82 | 05-AUG-08:51 | 17065.38 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.106401E+11 | 0.00 | 626.25 | 0.734452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19636.88 | 04-SEP-08:51 | 15853.48 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.618827E+10 | 0.00 | 534.97 | 0.502117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17805.91 | 03-OCT-08:61 | 17041.28 | 15-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.243034E+10 | 0.00 | 368.95 | 0.193054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17128.99 | 11-NOV-22:52 | 17045.96 | 10-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.126561E+10 | 0.00 | 243.53 | 0.125521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15767.21 | 25-DEC-09:51 | 15767.21 | 25-DEC-09:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819796E+11 | 0.00 | 6028.20 | 0.678777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.110479E+10 | 0.00 | 217.67 | 0.686261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15142.12 | 14740.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.132381E+11 | 0.00 | 709.59 | 0.120830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19636.88 | 17070.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.795310E+09 | 0.00 | 164.37 | 0.675989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14899.04 | 27-JAN-09:51 | 14899.04 | 27-JAN-09:51 | 0.00 | 0.00 | 0.00 |
February | 0.442074E+09 | 0.00 | 111.60 | 0.217079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15259.32 | 20-FEB-09:02 | 13405.48 | 26-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.127216E+10 | 0.00 | 257.59 | 0.897626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14804.49 | 16-MAR-08:51 | 14804.49 | 16-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.657703E+10 | 0.00 | 597.03 | 0.634650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16965.86 | 12-APR-08:51 | 16965.86 | 12-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.919517E+10 | 0.00 | 646.21 | 0.913041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16965.14 | 31-MAY-07:41 | 16965.14 | 31-MAY-07:41 | 0.00 | 0.00 | 0.00 |
June | 0.130370E+11 | 0.00 | 671.66 | 0.122427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16967.11 | 19-JUN-07:01 | 16967.11 | 19-JUN-07:01 | 0.00 | 0.00 | 0.00 |
July | 0.131776E+11 | 0.00 | 709.52 | 0.983359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18430.39 | 27-JUL-08:11 | 16947.90 | 04-JUL-07:31 | 0.00 | 0.00 | 0.00 |
August | 0.121083E+11 | 0.00 | 682.01 | 0.862814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18201.87 | 05-AUG-08:51 | 16961.22 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.954152E+10 | 0.00 | 622.89 | 0.629644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19475.39 | 04-SEP-08:51 | 15690.77 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.444102E+10 | 0.00 | 450.29 | 0.339668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17481.75 | 03-OCT-08:61 | 16677.38 | 17-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.995126E+09 | 0.00 | 204.36 | 0.694173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16864.19 | 11-NOV-22:52 | 15773.96 | 10-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.293309E+09 | 0.00 | 83.76 | 0.290153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14525.92 | 25-DEC-09:51 | 14525.92 | 25-DEC-09:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718755E+11 | 0.00 | 5201.31 | 0.586494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.293309E+09 | 0.00 | 83.76 | 0.217079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14525.92 | 13405.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131776E+11 | 0.00 | 709.52 | 0.122427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19475.39 | 16967.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.532184E+09 | 0.00 | 297.52 | 0.480519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4479.80 | 08-JAN-16:01 | 4453.48 | 25-JAN-21:31 | 0.00 | 0.00 | 0.00 |
February | 0.157833E+09 | 0.00 | 139.73 | 0.105308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4834.62 | 01-FEB-17:11 | 4834.62 | 01-FEB-17:11 | 0.00 | 0.00 | 0.00 |
March | 0.388257E+09 | 0.00 | 250.02 | 0.290342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.67 | 23-MAR-21:11 | 4590.67 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.195028E+10 | 0.00 | 577.86 | 0.188750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4724.88 | 06-APR-21:51 | 4724.88 | 06-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.242289E+10 | 0.00 | 629.10 | 0.240450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4604.95 | 08-MAY-08:61 | 4604.95 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.334687E+10 | 0.00 | 656.93 | 0.309631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4647.26 | 16-JUN-06:41 | 4647.26 | 16-JUN-06:41 | 0.00 | 0.00 | 0.00 |
July | 0.325090E+10 | 0.00 | 694.59 | 0.234214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5264.27 | 27-JUL-08:11 | 4725.39 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.314929E+10 | 0.00 | 669.94 | 0.221516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5428.79 | 05-AUG-08:51 | 4555.49 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.263058E+10 | 0.00 | 616.02 | 0.174212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5897.41 | 10-SEP-21:51 | 4419.40 | 18-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.140934E+10 | 0.00 | 468.89 | 0.111821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5211.43 | 03-OCT-08:61 | 4633.81 | 17-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.562012E+09 | 0.00 | 303.38 | 0.442977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5275.65 | 11-NOV-22:52 | 4529.31 | 21-NOV-21:11 | 0.00 | 0.00 | 0.00 |
December | 0.240170E+09 | 0.00 | 182.41 | 0.239469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.44 | 14-DEC-17:01 | 4760.44 | 14-DEC-17:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200406E+11 | 0.00 | 5486.38 | 0.163645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.157833E+09 | 0.00 | 139.73 | 0.105308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4479.80 | 4419.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.334687E+10 | 0.00 | 694.59 | 0.309631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5897.41 | 4834.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.150257E+09 | 0.00 | 108.73 | 0.139584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4460.81 | 08-JAN-16:01 | 4388.91 | 07-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 39666461.21 | 0.00 | 42.29 | 28538158.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4389.92 | 21-FEB-16:01 | 4389.92 | 21-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.238927E+09 | 0.00 | 167.40 | 0.179875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4420.79 | 23-MAR-21:11 | 4420.79 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.169003E+10 | 0.00 | 555.06 | 0.163011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4611.81 | 06-APR-21:51 | 4611.81 | 06-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.235152E+10 | 0.00 | 626.77 | 0.233300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4582.33 | 20-MAY-08:61 | 4582.33 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.338566E+10 | 0.00 | 658.61 | 0.313669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4681.66 | 16-JUN-06:41 | 4681.66 | 16-JUN-06:41 | 0.00 | 0.00 | 0.00 |
July | 0.323784E+10 | 0.00 | 694.91 | 0.233591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5228.82 | 27-JUL-08:11 | 4757.21 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.298904E+10 | 0.00 | 667.03 | 0.206216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5430.18 | 28-AUG-18:31 | 4502.44 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.234693E+10 | 0.00 | 609.50 | 0.147690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5790.65 | 10-SEP-21:51 | 4390.08 | 18-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.995269E+09 | 0.00 | 387.00 | 0.741902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5113.45 | 03-OCT-08:61 | 4457.51 | 16-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.208447E+09 | 0.00 | 151.25 | 0.150926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5191.94 | 11-NOV-22:52 | 4388.33 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 40984408.20 | 0.00 | 33.70 | 40947497.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4384.99 | 25-DEC-16:02 | 4384.99 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176746E+11 | 0.00 | 4702.25 | 0.142566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 39666461.21 | 0.00 | 33.70 | 28538158.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4384.99 | 4384.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.338566E+10 | 0.00 | 694.91 | 0.313669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5790.65 | 4757.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.837328E+10 | 0.00 | 538.42 | 0.770736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22708.08 | 08-JAN-20:12 | 21779.10 | 25-JAN-21:31 | 0.00 | 0.00 | 0.00 |
February | 0.347311E+10 | 0.00 | 365.58 | 0.228579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22090.53 | 01-FEB-17:11 | 22090.53 | 01-FEB-17:11 | 0.00 | 0.00 | 0.00 |
March | 0.369234E+10 | 0.00 | 393.81 | 0.265735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20745.45 | 22-MAR-21:21 | 20745.45 | 22-MAR-21:21 | 0.00 | 0.00 | 0.00 |
April | 0.959090E+10 | 0.00 | 580.41 | 0.921607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20728.86 | 07-APR-21:51 | 20728.86 | 07-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.102214E+11 | 0.00 | 620.03 | 0.101183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20480.71 | 20-MAY-08:61 | 20480.71 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.138061E+11 | 0.00 | 646.77 | 0.124593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20500.86 | 16-JUN-06:41 | 20500.86 | 16-JUN-06:41 | 0.00 | 0.00 | 0.00 |
July | 0.151808E+11 | 0.00 | 685.38 | 0.108162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22612.77 | 27-JUL-08:11 | 20895.62 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.156125E+11 | 0.00 | 664.15 | 0.111414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24238.57 | 28-AUG-18:31 | 20159.23 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.148299E+11 | 0.00 | 616.50 | 0.104520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26468.12 | 10-SEP-21:51 | 20558.38 | 29-SEP-08:21 | 0.00 | 0.00 | 0.00 |
October | 0.107253E+11 | 0.00 | 551.94 | 0.899081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22807.52 | 03-OCT-08:61 | 21375.61 | 31-OCT-21:41 | 0.00 | 0.00 | 0.00 |
November | 0.737242E+10 | 0.00 | 471.64 | 0.632910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23583.10 | 11-NOV-22:52 | 22588.87 | 10-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.621482E+10 | 0.00 | 456.36 | 0.617413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22131.20 | 26-DEC-21:31 | 22131.20 | 26-DEC-21:31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119093E+12 | 0.00 | 6591.00 | 0.983477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.347311E+10 | 0.00 | 365.58 | 0.228579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20480.71 | 20159.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.156125E+11 | 0.00 | 685.38 | 0.124593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26468.12 | 22588.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.71 | 667.64 | 168.07 | 1280.22 | 440.98 | 0.00 | 0.00 | 0.00 |
February | 521.47 | 349.59 | 171.87 | 717.95 | 412.69 | 0.00 | 0.00 | 0.00 |
March | 431.69 | 218.75 | 212.94 | 650.65 | 374.85 | 0.00 | 0.00 | 0.00 |
April | 378.88 | 156.07 | 222.81 | 733.05 | 214.23 | 0.00 | 0.00 | 0.00 |
May | 253.16 | 44.04 | 209.12 | 550.79 | 144.71 | 0.00 | 0.00 | 0.00 |
June | 214.28 | 16.35 | 197.94 | 633.59 | 54.87 | 0.00 | 0.00 | 0.00 |
July | 217.14 | 20.65 | 196.50 | 622.82 | 36.69 | 0.00 | 0.00 | 0.00 |
August | 268.51 | 75.62 | 192.88 | 712.07 | 49.19 | 0.00 | 0.00 | 0.00 |
September | 381.40 | 161.20 | 220.20 | 840.57 | 74.82 | 0.00 | 0.00 | 0.00 |
October | 612.22 | 423.82 | 188.40 | 1044.55 | 264.78 | 0.00 | 0.00 | 0.00 |
November | 719.63 | 552.71 | 166.92 | 1090.76 | 393.64 | 0.00 | 0.00 | 0.00 |
December | 778.28 | 616.61 | 161.67 | 1138.46 | 522.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 467.74 | 275.23 | 192.51 | 835.69 | 248.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 214.28 | 16.35 | 161.67 | 550.79 | 36.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 835.71 | 667.64 | 222.81 | 1280.22 | 522.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2353.32 | 1880.03 | 473.29 | 3553.12 | 1355.84 | 0.00 | 0.00 | 0.00 |
February | 1468.41 | 984.43 | 483.99 | 1967.31 | 1317.03 | 0.00 | 0.00 | 0.00 |
March | 1215.60 | 615.98 | 599.62 | 1773.30 | 1187.03 | 0.00 | 0.00 | 0.00 |
April | 1066.89 | 439.48 | 627.41 | 2035.31 | 648.02 | 0.00 | 0.00 | 0.00 |
May | 712.87 | 124.01 | 588.87 | 1530.23 | 434.89 | 0.00 | 0.00 | 0.00 |
June | 603.41 | 46.04 | 557.38 | 1778.91 | 159.10 | 0.00 | 0.00 | 0.00 |
July | 611.46 | 58.14 | 553.32 | 1742.55 | 112.10 | 0.00 | 0.00 | 0.00 |
August | 756.09 | 212.94 | 543.15 | 1990.75 | 152.14 | 0.00 | 0.00 | 0.00 |
September | 1074.00 | 453.93 | 620.07 | 2346.55 | 228.76 | 0.00 | 0.00 | 0.00 |
October | 1723.96 | 1193.45 | 530.51 | 2902.60 | 811.16 | 0.00 | 0.00 | 0.00 |
November | 2026.44 | 1556.40 | 470.05 | 3021.26 | 1222.33 | 0.00 | 0.00 | 0.00 |
December | 2191.58 | 1736.32 | 455.26 | 3149.81 | 1611.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1317.12 | 775.03 | 542.09 | 2319.06 | 767.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 603.41 | 46.04 | 455.26 | 1530.23 | 112.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2353.32 | 1880.03 | 627.41 | 3553.12 | 1611.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3057.09 | 2442.27 | 614.83 | 4728.97 | 1770.71 | 0.00 | 0.00 | 0.00 |
February | 1907.55 | 1278.83 | 628.73 | 2625.60 | 1764.14 | 0.00 | 0.00 | 0.00 |
March | 1579.13 | 800.19 | 778.94 | 2367.05 | 1583.27 | 0.00 | 0.00 | 0.00 |
April | 1385.95 | 570.91 | 815.04 | 2735.36 | 844.63 | 0.00 | 0.00 | 0.00 |
May | 926.06 | 161.09 | 764.97 | 2063.46 | 567.40 | 0.00 | 0.00 | 0.00 |
June | 783.87 | 59.80 | 724.06 | 2407.40 | 203.21 | 0.00 | 0.00 | 0.00 |
July | 794.32 | 75.52 | 718.79 | 2359.39 | 140.43 | 0.00 | 0.00 | 0.00 |
August | 982.21 | 276.63 | 705.58 | 2684.81 | 188.55 | 0.00 | 0.00 | 0.00 |
September | 1395.19 | 589.68 | 805.51 | 3150.19 | 284.86 | 0.00 | 0.00 | 0.00 |
October | 2239.52 | 1550.35 | 689.17 | 3873.69 | 1055.48 | 0.00 | 0.00 | 0.00 |
November | 2632.46 | 2021.85 | 610.62 | 4019.47 | 1604.38 | 0.00 | 0.00 | 0.00 |
December | 2846.99 | 2255.58 | 591.41 | 4191.20 | 2127.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1711.02 | 1006.81 | 704.21 | 3104.70 | 1008.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 783.87 | 59.80 | 591.41 | 2063.46 | 140.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3057.09 | 2442.27 | 815.04 | 4728.97 | 2127.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 258.77 | 83.25 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 144.72 | 79.47 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 130.24 | 73.85 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 152.49 | 34.74 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 120.12 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 146.00 | 5.35 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 146.08 | 3.33 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 160.27 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 181.85 | 7.02 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 213.85 | 45.91 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.05 | 74.02 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.14 | 100.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 175.72 | 44.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 120.12 | 3.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 258.77 | 100.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 184.52 | 171.78 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 119.76 | 161.00 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 189.09 | 140.32 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 376.50 | 64.39 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 412.93 | 37.51 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 515.60 | 9.72 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 407.99 | 6.10 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 380.14 | 7.62 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 311.97 | 13.29 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 239.01 | 91.91 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 180.97 | 151.90 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 130.82 | 209.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 288.18 | 88.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 119.76 | 6.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 515.60 | 209.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 18.60 | 88.74 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 12.64 | 85.37 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 32.28 | 75.69 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 71.99 | 32.97 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 100.80 | 17.73 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 159.73 | 4.51 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 144.23 | 2.92 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 118.48 | 3.81 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 97.89 | 6.87 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 45.81 | 48.16 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 18.98 | 79.23 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 11.53 | 109.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 69.69 | 46.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 11.53 | 2.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 159.73 | 109.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 193.51 | 164.10 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 125.85 | 155.76 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 194.61 | 137.15 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 379.32 | 63.36 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 413.45 | 37.41 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 515.09 | 9.76 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 408.07 | 6.12 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 381.56 | 7.49 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 314.72 | 12.84 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 245.16 | 88.35 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 188.34 | 145.52 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 139.60 | 201.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 292.34 | 85.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 125.85 | 6.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 515.09 | 201.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.16 | 105.58 | 26.58 | 202.36 | 75.94 | 0.00 | 0.00 | 0.00 |
February | 82.47 | 55.29 | 27.18 | 111.35 | 74.28 | 0.00 | 0.00 | 0.00 |
March | 68.27 | 34.59 | 33.67 | 100.52 | 66.44 | 0.00 | 0.00 | 0.00 |
April | 59.92 | 24.68 | 35.24 | 120.43 | 33.07 | 0.00 | 0.00 | 0.00 |
May | 40.04 | 6.96 | 33.07 | 94.68 | 20.79 | 0.00 | 0.00 | 0.00 |
June | 33.89 | 2.59 | 31.30 | 114.45 | 6.33 | 0.00 | 0.00 | 0.00 |
July | 34.34 | 3.26 | 31.07 | 111.58 | 4.12 | 0.00 | 0.00 | 0.00 |
August | 42.46 | 11.96 | 30.50 | 123.76 | 5.47 | 0.00 | 0.00 | 0.00 |
September | 60.32 | 25.49 | 34.82 | 141.42 | 8.98 | 0.00 | 0.00 | 0.00 |
October | 96.82 | 67.02 | 29.79 | 167.76 | 42.84 | 0.00 | 0.00 | 0.00 |
November | 113.80 | 87.41 | 26.40 | 172.11 | 67.73 | 0.00 | 0.00 | 0.00 |
December | 123.08 | 97.51 | 25.57 | 179.35 | 91.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.97 | 43.53 | 30.44 | 136.85 | 41.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.89 | 2.59 | 25.57 | 94.68 | 4.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.16 | 105.58 | 35.24 | 202.36 | 91.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.03 | 0.00 | 16.03 | 16.74 | 69.71 | 0.00 | 0.00 | 0.00 |
February | 18.27 | 0.00 | 18.27 | 10.65 | 69.47 | 0.00 | 0.00 | 0.00 |
March | 24.29 | 0.00 | 24.28 | 27.86 | 59.70 | 0.00 | 0.00 | 0.00 |
April | 29.74 | 0.44 | 29.30 | 63.87 | 24.05 | 0.00 | 0.00 | 0.00 |
May | 34.89 | 2.96 | 31.92 | 87.58 | 12.56 | 0.00 | 0.00 | 0.00 |
June | 40.29 | 7.36 | 32.93 | 136.74 | 2.69 | 0.00 | 0.00 | 0.00 |
July | 34.47 | 3.70 | 30.76 | 123.41 | 1.87 | 0.00 | 0.00 | 0.00 |
August | 27.73 | 0.68 | 27.05 | 102.51 | 2.34 | 0.00 | 0.00 | 0.00 |
September | 26.15 | 0.02 | 26.14 | 84.86 | 4.33 | 0.00 | 0.00 | 0.00 |
October | 20.22 | 0.00 | 20.22 | 40.82 | 36.47 | 0.00 | 0.00 | 0.00 |
November | 16.85 | 0.00 | 16.85 | 17.18 | 61.82 | 0.00 | 0.00 | 0.00 |
December | 14.98 | 0.00 | 14.98 | 9.79 | 88.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.35 | 1.27 | 24.08 | 60.40 | 35.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.98 | 0.00 | 14.98 | 9.79 | 1.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.29 | 7.36 | 32.93 | 136.74 | 88.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 157.14 | 154.64 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 138.22 | 150.33 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 200.01 | 129.56 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 376.61 | 56.97 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 426.66 | 32.33 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 531.85 | 8.16 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 467.09 | 5.31 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 431.53 | 7.19 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 338.50 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 254.36 | 84.24 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 150.45 | 138.52 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 120.88 | 190.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 300.22 | 80.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 120.88 | 5.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 531.85 | 190.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 257.88 | 82.04 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 143.08 | 79.27 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 128.34 | 73.14 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 150.63 | 34.54 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 117.87 | 20.37 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 144.68 | 5.21 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 144.51 | 3.30 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 158.87 | 4.23 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 180.60 | 7.03 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.11 | 45.41 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 219.17 | 72.75 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 230.04 | 100.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 174.24 | 43.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 117.87 | 3.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 257.88 | 100.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 17.88 | 87.39 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 11.66 | 85.74 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 30.53 | 75.33 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 69.96 | 32.92 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 98.06 | 17.50 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 158.40 | 4.35 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 142.62 | 2.87 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 116.94 | 3.82 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 96.59 | 6.92 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 44.13 | 48.13 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 18.34 | 77.89 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 10.89 | 108.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 68.27 | 45.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 10.89 | 2.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 158.40 | 108.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 166.29 | 146.45 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 143.85 | 144.63 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 204.86 | 126.22 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 379.11 | 56.07 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 427.10 | 32.20 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 531.42 | 8.20 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 467.20 | 5.32 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 432.90 | 7.06 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 341.16 | 11.78 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 259.86 | 80.80 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 157.90 | 131.58 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 129.06 | 181.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 304.17 | 77.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 129.06 | 5.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 531.42 | 181.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 21.19 | 123.17 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 14.83 | 118.09 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 40.64 | 102.32 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 91.06 | 49.56 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 124.91 | 30.13 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 195.17 | 9.67 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 170.99 | 6.64 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 140.19 | 9.09 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 115.58 | 15.47 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 54.08 | 71.50 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 22.15 | 111.23 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 12.32 | 150.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 83.91 | 66.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 12.32 | 6.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 195.17 | 150.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.36 | 0.00 | 9.36 | 7.81 | 45.40 | 0.00 | 0.00 | 0.00 |
February | 10.66 | 0.00 | 10.66 | 5.47 | 43.53 | 0.00 | 0.00 | 0.00 |
March | 14.17 | 0.00 | 14.17 | 14.98 | 37.72 | 0.00 | 0.00 | 0.00 |
April | 17.35 | 0.26 | 17.10 | 33.57 | 18.27 | 0.00 | 0.00 | 0.00 |
May | 20.36 | 1.73 | 18.63 | 46.05 | 11.11 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 4.30 | 19.21 | 71.95 | 3.57 | 0.00 | 0.00 | 0.00 |
July | 20.11 | 2.16 | 17.95 | 63.03 | 2.45 | 0.00 | 0.00 | 0.00 |
August | 16.18 | 0.40 | 15.78 | 51.68 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 15.26 | 0.01 | 15.25 | 42.61 | 5.70 | 0.00 | 0.00 | 0.00 |
October | 11.80 | 0.00 | 11.80 | 19.93 | 26.36 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 0.00 | 9.83 | 8.17 | 41.00 | 0.00 | 0.00 | 0.00 |
December | 8.74 | 0.00 | 8.74 | 4.54 | 55.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.79 | 0.74 | 14.05 | 30.93 | 24.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.74 | 0.00 | 8.74 | 4.54 | 2.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.51 | 4.30 | 19.21 | 71.95 | 55.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.10 | 61.59 | 15.51 | 121.96 | 40.51 | 0.00 | 0.00 | 0.00 |
February | 48.11 | 32.25 | 15.86 | 68.30 | 39.13 | 0.00 | 0.00 | 0.00 |
March | 39.82 | 20.18 | 19.64 | 61.81 | 35.93 | 0.00 | 0.00 | 0.00 |
April | 34.95 | 14.40 | 20.56 | 71.66 | 18.81 | 0.00 | 0.00 | 0.00 |
May | 23.36 | 4.06 | 19.29 | 55.33 | 12.48 | 0.00 | 0.00 | 0.00 |
June | 19.77 | 1.51 | 18.26 | 65.47 | 4.13 | 0.00 | 0.00 | 0.00 |
July | 20.03 | 1.90 | 18.13 | 63.91 | 2.71 | 0.00 | 0.00 | 0.00 |
August | 24.77 | 6.98 | 17.79 | 71.47 | 3.55 | 0.00 | 0.00 | 0.00 |
September | 35.19 | 14.87 | 20.31 | 82.26 | 5.65 | 0.00 | 0.00 | 0.00 |
October | 56.48 | 39.10 | 17.38 | 99.46 | 24.16 | 0.00 | 0.00 | 0.00 |
November | 66.39 | 50.99 | 15.40 | 103.57 | 36.56 | 0.00 | 0.00 | 0.00 |
December | 71.80 | 56.88 | 14.92 | 108.88 | 48.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.15 | 25.39 | 17.76 | 81.28 | 22.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.77 | 1.51 | 14.92 | 55.33 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.10 | 61.59 | 20.56 | 121.96 | 48.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.26 | 167.17 | 42.09 | 331.02 | 109.95 | 0.00 | 0.00 | 0.00 |
February | 130.57 | 87.54 | 43.04 | 185.37 | 106.21 | 0.00 | 0.00 | 0.00 |
March | 108.09 | 54.77 | 53.32 | 167.78 | 97.51 | 0.00 | 0.00 | 0.00 |
April | 94.87 | 39.08 | 55.79 | 194.49 | 51.06 | 0.00 | 0.00 | 0.00 |
May | 63.39 | 11.03 | 52.36 | 150.19 | 33.87 | 0.00 | 0.00 | 0.00 |
June | 53.66 | 4.09 | 49.56 | 177.70 | 11.20 | 0.00 | 0.00 | 0.00 |
July | 54.37 | 5.17 | 49.20 | 173.47 | 7.36 | 0.00 | 0.00 | 0.00 |
August | 67.23 | 18.94 | 48.30 | 193.98 | 9.62 | 0.00 | 0.00 | 0.00 |
September | 95.50 | 40.36 | 55.14 | 223.27 | 15.33 | 0.00 | 0.00 | 0.00 |
October | 153.30 | 106.12 | 47.17 | 269.96 | 65.58 | 0.00 | 0.00 | 0.00 |
November | 180.19 | 138.40 | 41.80 | 281.12 | 99.23 | 0.00 | 0.00 | 0.00 |
December | 194.88 | 154.40 | 40.48 | 295.51 | 132.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.12 | 68.92 | 48.20 | 220.62 | 61.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.66 | 4.09 | 40.48 | 150.19 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.26 | 167.17 | 55.79 | 331.02 | 132.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 256.99 | 82.84 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 143.49 | 78.76 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 128.84 | 73.83 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 151.35 | 33.84 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 120.18 | 19.14 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 146.64 | 4.79 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 146.53 | 3.08 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 160.37 | 3.80 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 181.44 | 6.35 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.55 | 44.88 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 218.51 | 73.40 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 230.07 | 100.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 175.01 | 43.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 120.18 | 3.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 256.99 | 100.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 182.70 | 169.89 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 117.94 | 158.89 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 186.54 | 139.50 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 373.22 | 62.63 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 410.93 | 35.57 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 514.00 | 8.82 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 407.22 | 5.70 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 379.38 | 7.03 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 311.32 | 12.14 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 237.58 | 89.47 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 179.19 | 149.85 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 129.62 | 207.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 286.54 | 86.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 117.94 | 5.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 514.00 | 207.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 19.16 | 87.01 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 12.67 | 83.92 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 32.16 | 75.03 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 71.90 | 32.11 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 101.20 | 16.92 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 160.18 | 4.15 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 144.63 | 2.75 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 118.92 | 3.53 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 98.40 | 6.27 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 46.37 | 46.55 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 19.44 | 77.55 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 12.01 | 107.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 70.03 | 45.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 12.01 | 2.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 160.18 | 107.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 192.89 | 160.89 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 124.76 | 152.98 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 192.63 | 135.82 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 376.11 | 61.55 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 411.44 | 35.46 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 513.45 | 8.86 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 407.29 | 5.71 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 380.85 | 6.89 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 314.18 | 11.69 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 244.43 | 85.40 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 187.58 | 142.44 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 139.49 | 197.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 291.16 | 83.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 124.76 | 5.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 513.45 | 197.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 242.33 | 193.60 | 48.74 | 370.45 | 128.00 | 0.00 | 0.00 | 0.00 |
February | 151.21 | 101.37 | 49.84 | 204.94 | 121.71 | 0.00 | 0.00 | 0.00 |
March | 125.18 | 63.43 | 61.75 | 185.81 | 110.39 | 0.00 | 0.00 | 0.00 |
April | 109.86 | 45.26 | 64.61 | 225.59 | 47.71 | 0.00 | 0.00 | 0.00 |
May | 73.41 | 12.77 | 60.64 | 182.83 | 26.40 | 0.00 | 0.00 | 0.00 |
June | 62.14 | 4.74 | 57.40 | 225.01 | 5.91 | 0.00 | 0.00 | 0.00 |
July | 62.97 | 5.99 | 56.98 | 222.36 | 4.03 | 0.00 | 0.00 | 0.00 |
August | 77.86 | 21.93 | 55.93 | 241.22 | 5.09 | 0.00 | 0.00 | 0.00 |
September | 110.60 | 46.74 | 63.85 | 268.97 | 8.93 | 0.00 | 0.00 | 0.00 |
October | 177.53 | 122.90 | 54.63 | 309.29 | 67.85 | 0.00 | 0.00 | 0.00 |
November | 208.67 | 160.27 | 48.40 | 315.02 | 112.74 | 0.00 | 0.00 | 0.00 |
December | 225.68 | 178.80 | 46.88 | 329.29 | 155.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.63 | 79.81 | 55.82 | 257.14 | 65.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.14 | 4.74 | 46.88 | 182.83 | 4.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.33 | 193.60 | 64.61 | 370.45 | 155.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 82.37 | 790.83 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 46.11 | 811.63 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 164.73 | 685.44 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 448.59 | 319.31 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 637.89 | 192.45 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1032.58 | 65.07 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 894.08 | 48.66 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 730.15 | 68.08 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 599.48 | 109.12 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 264.67 | 449.91 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 88.02 | 720.44 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 40.52 | 971.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 420.82 | 434.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 40.52 | 48.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1032.58 | 971.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 73.83 | 811.96 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 39.37 | 838.92 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 153.57 | 705.05 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 438.76 | 328.32 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 627.35 | 198.40 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1020.51 | 67.98 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 881.92 | 51.49 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 719.09 | 72.23 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 589.52 | 114.78 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 255.95 | 463.02 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 80.13 | 741.25 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 34.61 | 999.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 411.25 | 447.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 34.61 | 51.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1020.51 | 999.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 13.65 | 115.11 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 7.46 | 119.36 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 25.84 | 102.04 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 69.75 | 50.12 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 98.24 | 32.65 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 154.14 | 13.20 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 133.95 | 10.53 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 111.67 | 14.09 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 92.66 | 20.13 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 41.80 | 68.37 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 14.55 | 105.48 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 7.25 | 139.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 64.51 | 65.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 7.25 | 10.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 154.14 | 139.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.87 | 151.81 | 90.06 | 305.79 | 386.55 | 0.00 | 0.00 | 0.00 |
February | 240.43 | 138.34 | 102.10 | 262.31 | 405.50 | 0.00 | 0.00 | 0.00 |
March | 298.56 | 153.60 | 144.96 | 382.31 | 344.17 | 0.00 | 0.00 | 0.00 |
April | 425.45 | 253.49 | 171.96 | 754.84 | 174.54 | 0.00 | 0.00 | 0.00 |
May | 441.66 | 262.07 | 179.60 | 852.91 | 120.31 | 0.00 | 0.00 | 0.00 |
June | 459.53 | 285.49 | 174.04 | 1044.08 | 49.45 | 0.00 | 0.00 | 0.00 |
July | 388.70 | 219.32 | 169.38 | 899.74 | 39.33 | 0.00 | 0.00 | 0.00 |
August | 369.23 | 210.95 | 158.27 | 843.07 | 52.75 | 0.00 | 0.00 | 0.00 |
September | 302.56 | 145.93 | 156.63 | 664.85 | 73.24 | 0.00 | 0.00 | 0.00 |
October | 303.63 | 184.69 | 118.94 | 505.82 | 232.34 | 0.00 | 0.00 | 0.00 |
November | 233.65 | 140.21 | 93.44 | 292.77 | 357.72 | 0.00 | 0.00 | 0.00 |
December | 213.43 | 129.08 | 84.35 | 232.12 | 465.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.95 | 189.82 | 137.13 | 588.26 | 224.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.43 | 129.08 | 84.35 | 232.12 | 39.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.53 | 285.49 | 179.60 | 1044.08 | 465.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 256.91 | 102.56 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 139.74 | 106.32 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 125.11 | 96.69 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 151.18 | 51.30 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 117.91 | 35.64 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 140.08 | 14.34 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 136.17 | 11.14 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 154.29 | 14.47 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 177.69 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 211.88 | 62.55 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 217.82 | 93.91 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 228.27 | 121.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 171.68 | 60.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 117.91 | 11.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 256.91 | 121.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 18.72 | 124.13 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 12.37 | 120.92 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 37.11 | 104.20 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 85.60 | 51.39 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 119.63 | 31.54 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 190.04 | 10.38 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 164.90 | 7.44 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 134.68 | 10.27 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 110.83 | 16.94 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 51.29 | 71.23 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 19.85 | 111.73 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 10.41 | 151.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 79.93 | 67.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 10.41 | 7.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 190.04 | 151.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.71 | 0.00 | 22.71 | 16.74 | 111.05 | 0.00 | 0.00 | 0.00 |
February | 25.87 | 0.00 | 25.87 | 11.06 | 108.19 | 0.00 | 0.00 | 0.00 |
March | 34.39 | 0.00 | 34.39 | 33.20 | 93.23 | 0.00 | 0.00 | 0.00 |
April | 42.12 | 0.62 | 41.50 | 76.59 | 45.98 | 0.00 | 0.00 | 0.00 |
May | 49.41 | 4.20 | 45.21 | 107.04 | 28.22 | 0.00 | 0.00 | 0.00 |
June | 57.06 | 10.43 | 46.63 | 170.03 | 9.29 | 0.00 | 0.00 | 0.00 |
July | 48.81 | 5.24 | 43.56 | 147.54 | 6.65 | 0.00 | 0.00 | 0.00 |
August | 39.27 | 0.96 | 38.31 | 120.50 | 9.19 | 0.00 | 0.00 | 0.00 |
September | 37.04 | 0.02 | 37.01 | 99.16 | 15.16 | 0.00 | 0.00 | 0.00 |
October | 28.64 | 0.00 | 28.64 | 45.89 | 63.73 | 0.00 | 0.00 | 0.00 |
November | 23.86 | 0.00 | 23.86 | 17.76 | 99.96 | 0.00 | 0.00 | 0.00 |
December | 21.21 | 0.00 | 21.21 | 9.31 | 135.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.90 | 1.79 | 34.11 | 71.51 | 60.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.21 | 0.00 | 21.21 | 9.31 | 6.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.06 | 10.43 | 46.63 | 170.03 | 135.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 616.87 | 492.81 | 124.06 | 959.77 | 327.58 | 0.00 | 0.00 | 0.00 |
February | 384.91 | 258.05 | 126.87 | 532.94 | 321.02 | 0.00 | 0.00 | 0.00 |
March | 318.65 | 161.47 | 157.18 | 479.22 | 294.09 | 0.00 | 0.00 | 0.00 |
April | 279.66 | 115.20 | 164.46 | 553.45 | 156.23 | 0.00 | 0.00 | 0.00 |
May | 186.87 | 32.51 | 154.36 | 426.53 | 104.11 | 0.00 | 0.00 | 0.00 |
June | 158.17 | 12.07 | 146.11 | 509.57 | 35.06 | 0.00 | 0.00 | 0.00 |
July | 160.28 | 15.24 | 145.04 | 493.40 | 24.02 | 0.00 | 0.00 | 0.00 |
August | 198.20 | 55.82 | 142.38 | 554.34 | 31.78 | 0.00 | 0.00 | 0.00 |
September | 281.53 | 118.99 | 162.54 | 640.78 | 49.39 | 0.00 | 0.00 | 0.00 |
October | 451.90 | 312.84 | 139.06 | 781.43 | 193.34 | 0.00 | 0.00 | 0.00 |
November | 531.19 | 407.98 | 123.21 | 814.49 | 294.71 | 0.00 | 0.00 | 0.00 |
December | 574.48 | 455.14 | 119.34 | 857.39 | 394.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 345.26 | 203.16 | 142.10 | 634.48 | 184.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 158.17 | 12.07 | 119.34 | 426.53 | 24.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 616.87 | 492.81 | 164.46 | 959.77 | 394.48 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.342894E+10 | 0.118112E+10 |
February | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.173686E+10 | 0.998376E+09 |
March | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.174271E+10 | 0.100400E+10 |
April | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.190007E+10 | 0.555290E+09 |
May | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.147524E+10 | 0.387599E+09 |
June | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.164226E+10 | 0.142217E+09 |
July | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.166817E+10 | 98267454.74 |
August | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.190720E+10 | 0.131755E+09 |
September | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.217876E+10 | 0.193921E+09 |
October | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.279772E+10 | 0.709179E+09 |
November | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.282726E+10 | 0.102030E+10 |
December | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.304925E+10 | 0.139953E+10 |
Annual Sum or Average | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.263544E+11 | 0.782155E+10 |
Minimum of Months | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.147524E+10 | 98267454.74 |
Maximum of Months | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.342894E+10 | 0.139953E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.951667E+10 | 0.363148E+10 |
February | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.475932E+10 | 0.318617E+10 |
March | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.474962E+10 | 0.317935E+10 |
April | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.527552E+10 | 0.167966E+10 |
May | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.409856E+10 | 0.116481E+10 |
June | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.461093E+10 | 0.412383E+09 |
July | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.466724E+10 | 0.300236E+09 |
August | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.533203E+10 | 0.407480E+09 |
September | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.608226E+10 | 0.592939E+09 |
October | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.777432E+10 | 0.217262E+10 |
November | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.783109E+10 | 0.316829E+10 |
December | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.843644E+10 | 0.431508E+10 |
Annual Sum or Average | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.731340E+11 | 0.242105E+11 |
Minimum of Months | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.409856E+10 | 0.300236E+09 |
Maximum of Months | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.951667E+10 | 0.431508E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.126661E+11 | 0.474266E+10 |
February | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.635184E+10 | 0.426780E+10 |
March | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.633991E+10 | 0.424062E+10 |
April | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.709005E+10 | 0.218928E+10 |
May | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.552676E+10 | 0.151972E+10 |
June | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.623999E+10 | 0.526715E+09 |
July | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.631939E+10 | 0.376122E+09 |
August | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.719100E+10 | 0.505015E+09 |
September | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.816530E+10 | 0.738357E+09 |
October | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.103753E+11 | 0.282699E+10 |
November | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.104185E+11 | 0.415856E+10 |
December | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.112257E+11 | 0.569731E+10 |
Annual Sum or Average | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.979098E+11 | 0.317892E+11 |
Minimum of Months | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.552676E+10 | 0.376122E+09 |
Maximum of Months | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.126661E+11 | 0.569731E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.693094E+09 | 0.222979E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.350118E+09 | 0.192260E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.348835E+09 | 0.197809E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.395264E+09 | 90042200.67 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.321729E+09 | 54206171.23 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.378423E+09 | 13868058.36 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.391250E+09 | 8908667.01 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.429258E+09 | 11168621.33 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.471358E+09 | 18186242.94 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.572785E+09 | 0.122975E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.570360E+09 | 0.191858E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.619072E+09 | 0.269466E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.554155E+10 | 0.139373E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.321729E+09 | 8908667.01 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.693094E+09 | 0.269466E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.494225E+09 | 0.460086E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.289728E+09 | 0.389497E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.506472E+09 | 0.375832E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.975884E+09 | 0.166896E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.110599E+10 | 0.100470E+09 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.133644E+10 | 25191543.48 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.109275E+10 | 16344201.28 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.101816E+10 | 20414696.02 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.808635E+09 | 34450914.79 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.640152E+09 | 0.246178E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.469068E+09 | 0.393736E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.350397E+09 | 0.561086E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.908791E+10 | 0.279018E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.289728E+09 | 16344201.28 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.133644E+10 | 0.561086E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 49817424.81 | 0.237685E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 30568460.31 | 0.206534E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 86462119.89 | 0.202719E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.186607E+09 | 85466516.49 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.269976E+09 | 47478100.63 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.414031E+09 | 11700567.63 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.386309E+09 | 7820397.80 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.317346E+09 | 10200345.82 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.253737E+09 | 17817622.97 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.122709E+09 | 0.128985E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 49187651.16 | 0.205371E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 30878870.27 | 0.292301E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.219763E+10 | 0.145408E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 30568460.31 | 7820397.80 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.414031E+09 | 0.292301E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.518304E+09 | 0.439529E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.304456E+09 | 0.376804E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.521242E+09 | 0.367332E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.983208E+09 | 0.164216E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.110739E+10 | 0.100186E+09 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.133510E+10 | 25293544.01 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.109297E+10 | 16378935.34 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.102198E+10 | 20055998.50 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.815743E+09 | 33279817.26 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.656640E+09 | 0.236635E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.488174E+09 | 0.377188E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.373893E+09 | 0.538872E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.921911E+10 | 0.269577E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.304456E+09 | 16378935.34 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.133510E+10 | 0.538872E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.541995E+09 | 0.203410E+09 |
February | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.269378E+09 | 0.179700E+09 |
March | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.269230E+09 | 0.177964E+09 |
April | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.312151E+09 | 85724681.85 |
May | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.253592E+09 | 55676746.09 |
June | 87837819.98 | 6701448.63 | 81136371.35 | 0.296647E+09 | 16409232.72 |
July | 91975290.32 | 8744924.55 | 83230365.76 | 0.298868E+09 | 11030670.16 |
August | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.331473E+09 | 14637750.41 |
September | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.366558E+09 | 23268454.23 |
October | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.449340E+09 | 0.114749E+09 |
November | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.446099E+09 | 0.175545E+09 |
December | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.480378E+09 | 0.245917E+09 |
Annual Sum or Average | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.431571E+10 | 0.130403E+10 |
Minimum of Months | 87837819.98 | 6701448.63 | 65755807.07 | 0.253592E+09 | 11030670.16 |
Maximum of Months | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.541995E+09 | 0.245917E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42944949.46 | 0.00 | 42944949.46 | 44845693.18 | 0.186713E+09 |
February | 44199004.85 | 0.00 | 44199004.85 | 25761976.81 | 0.168067E+09 |
March | 65045237.58 | 2573.27 | 65042664.31 | 74631670.24 | 0.159909E+09 |
April | 77090857.89 | 1135053.46 | 75955804.43 | 0.165561E+09 | 62333869.82 |
May | 93441433.49 | 7934259.35 | 85507174.14 | 0.234561E+09 | 33640998.93 |
June | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.354419E+09 | 6984403.84 |
July | 92312481.83 | 9919050.97 | 82393430.86 | 0.330537E+09 | 4998216.33 |
August | 74279179.59 | 1823766.12 | 72455413.47 | 0.274556E+09 | 6254403.95 |
September | 67785290.05 | 41951.47 | 67743338.59 | 0.219949E+09 | 11234229.69 |
October | 54159300.98 | 0.00 | 54159300.98 | 0.109330E+09 | 97678152.30 |
November | 43668987.75 | 0.00 | 43668987.75 | 44530025.56 | 0.160231E+09 |
December | 40114513.77 | 0.00 | 40114513.77 | 26214178.11 | 0.236103E+09 |
Annual Sum or Average | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.190490E+10 | 0.113415E+10 |
Minimum of Months | 40114513.77 | 0.00 | 40114513.77 | 25761976.81 | 4998216.33 |
Maximum of Months | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.354419E+09 | 0.236103E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.420874E+09 | 0.414189E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.334389E+09 | 0.363684E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.535695E+09 | 0.347005E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.976167E+09 | 0.147670E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.114276E+10 | 86600391.88 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.137857E+10 | 21147396.70 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.125107E+10 | 14225844.06 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.115581E+10 | 19264714.32 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.877390E+09 | 31577539.77 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.681273E+09 | 0.225625E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.389978E+09 | 0.359036E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.323754E+09 | 0.511366E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.946773E+10 | 0.254139E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.323754E+09 | 14225844.06 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.137857E+10 | 0.511366E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.690705E+09 | 0.219739E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.346139E+09 | 0.191780E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.343745E+09 | 0.195911E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.390445E+09 | 89529278.90 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.315697E+09 | 54567309.70 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.374999E+09 | 13498498.03 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.387046E+09 | 8827847.28 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.425511E+09 | 11335837.50 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.468122E+09 | 18228943.55 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.568123E+09 | 0.121630E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.568088E+09 | 0.188560E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.616149E+09 | 0.267853E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.549477E+10 | 0.138146E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.315697E+09 | 8827847.28 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.690705E+09 | 0.267853E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 47877824.74 | 0.234075E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 28202208.25 | 0.207433E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 81769596.97 | 0.201767E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.181349E+09 | 85323578.43 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.262643E+09 | 46861829.45 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.410577E+09 | 11284403.97 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.381998E+09 | 7673830.74 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.313213E+09 | 10230437.64 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.250349E+09 | 17942328.16 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.118185E+09 | 0.128922E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 47542189.02 | 0.201887E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 29162148.78 | 0.290739E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.215287E+10 | 0.144414E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 28202208.25 | 7673830.74 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.410577E+09 | 0.290739E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.445397E+09 | 0.392256E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.348000E+09 | 0.349881E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.548687E+09 | 0.338057E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.982661E+09 | 0.145339E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.114395E+10 | 86239416.98 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.137743E+10 | 21247506.07 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.125136E+10 | 14245218.18 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.115948E+10 | 18913586.87 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.884278E+09 | 30531505.28 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.695997E+09 | 0.216409E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.409281E+09 | 0.341065E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.345683E+09 | 0.485974E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.959222E+10 | 0.244016E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.345683E+09 | 14245218.18 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.137743E+10 | 0.485974E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 56765532.27 | 0.329887E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 35873868.31 | 0.285676E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.108843E+09 | 0.274049E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.236031E+09 | 0.128461E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.334554E+09 | 80698052.13 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.505868E+09 | 25066990.90 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.457986E+09 | 17796498.67 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.375475E+09 | 24347146.97 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.299578E+09 | 40085561.28 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.144837E+09 | 0.191503E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 57415573.64 | 0.288298E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 33000942.24 | 0.402188E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.264623E+10 | 0.208806E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 33000942.24 | 17796498.67 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.505868E+09 | 0.402188E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25058335.32 | 0.00 | 25058335.32 | 20926125.67 | 0.121610E+09 |
February | 25790075.39 | 0.00 | 25790075.39 | 13224593.28 | 0.105312E+09 |
March | 37953831.47 | 1501.50 | 37952329.97 | 40123955.44 | 0.101026E+09 |
April | 44982438.94 | 662302.56 | 44320136.38 | 87010784.69 | 47355946.28 |
May | 54522983.56 | 4629632.44 | 49893351.11 | 0.123330E+09 | 29748643.46 |
June | 60934981.96 | 11133860.83 | 49801121.12 | 0.186484E+09 | 9240730.79 |
July | 53864241.38 | 5787756.38 | 48076485.00 | 0.168833E+09 | 6560526.31 |
August | 43341827.45 | 1064165.72 | 42277661.74 | 0.138416E+09 | 8975366.51 |
September | 39552649.37 | 24478.64 | 39528170.73 | 0.110437E+09 | 14777197.70 |
October | 31601898.29 | 0.00 | 31601898.29 | 53392896.09 | 70595984.49 |
November | 25480810.94 | 0.00 | 25480810.94 | 21165757.83 | 0.106278E+09 |
December | 23406778.91 | 0.00 | 23406778.91 | 12165513.77 | 0.148263E+09 |
Annual Sum or Average | 0.466491E+09 | 23303698.08 | 0.443187E+09 | 0.975509E+09 | 0.769744E+09 |
Minimum of Months | 23406778.91 | 0.00 | 23406778.91 | 12165513.77 | 6560526.31 |
Maximum of Months | 60934981.96 | 11133860.83 | 49893351.11 | 0.186484E+09 | 0.148263E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206500E+09 | 0.164969E+09 | 41530470.22 | 0.326651E+09 | 0.108502E+09 |
February | 0.116382E+09 | 78022138.43 | 38359370.38 | 0.165225E+09 | 94668073.88 |
March | 0.106667E+09 | 54051088.25 | 52616188.64 | 0.165562E+09 | 96225327.58 |
April | 90598271.93 | 37319698.27 | 53278573.67 | 0.185733E+09 | 48762552.39 |
May | 62554278.62 | 10881561.56 | 51672717.06 | 0.148208E+09 | 33425429.77 |
June | 51241154.51 | 3909363.47 | 47331791.04 | 0.169696E+09 | 10696365.19 |
July | 53654793.16 | 5101447.54 | 48553345.62 | 0.171181E+09 | 7264266.60 |
August | 66346579.02 | 18685521.81 | 47661057.22 | 0.191421E+09 | 9496481.07 |
September | 91202342.18 | 38546673.46 | 52655668.72 | 0.213216E+09 | 14642270.71 |
October | 0.151275E+09 | 0.104723E+09 | 46552209.79 | 0.266399E+09 | 64712596.17 |
November | 0.172081E+09 | 0.132165E+09 | 39915655.96 | 0.268464E+09 | 94763071.19 |
December | 0.192308E+09 | 0.152359E+09 | 39948749.01 | 0.291612E+09 | 0.130457E+09 |
Annual Sum or Average | 0.136081E+10 | 0.800734E+09 | 0.560076E+09 | 0.256337E+10 | 0.713615E+09 |
Minimum of Months | 51241154.51 | 3909363.47 | 38359370.38 | 0.148208E+09 | 7264266.60 |
Maximum of Months | 0.206500E+09 | 0.164969E+09 | 53278573.67 | 0.326651E+09 | 0.130457E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.560483E+09 | 0.447760E+09 | 0.112722E+09 | 0.886597E+09 | 0.294496E+09 |
February | 0.315883E+09 | 0.211768E+09 | 0.104115E+09 | 0.448454E+09 | 0.256949E+09 |
March | 0.289517E+09 | 0.146706E+09 | 0.142811E+09 | 0.449370E+09 | 0.261175E+09 |
April | 0.245902E+09 | 0.101293E+09 | 0.144609E+09 | 0.504117E+09 | 0.132351E+09 |
May | 0.169785E+09 | 29534783.85 | 0.140250E+09 | 0.402267E+09 | 90723453.40 |
June | 0.139079E+09 | 10610812.10 | 0.128468E+09 | 0.460589E+09 | 29032123.02 |
July | 0.145630E+09 | 13846372.09 | 0.131784E+09 | 0.464620E+09 | 19716705.43 |
August | 0.180078E+09 | 50716328.22 | 0.129362E+09 | 0.519555E+09 | 25775392.08 |
September | 0.247542E+09 | 0.104624E+09 | 0.142918E+09 | 0.578712E+09 | 39742117.72 |
October | 0.410591E+09 | 0.284239E+09 | 0.126352E+09 | 0.723061E+09 | 0.175643E+09 |
November | 0.467063E+09 | 0.358724E+09 | 0.108339E+09 | 0.728666E+09 | 0.257206E+09 |
December | 0.521963E+09 | 0.413534E+09 | 0.108429E+09 | 0.791494E+09 | 0.354087E+09 |
Annual Sum or Average | 0.369352E+10 | 0.217336E+10 | 0.152016E+10 | 0.695750E+10 | 0.193690E+10 |
Minimum of Months | 0.139079E+09 | 10610812.10 | 0.104115E+09 | 0.402267E+09 | 19716705.43 |
Maximum of Months | 0.560483E+09 | 0.447760E+09 | 0.144609E+09 | 0.886597E+09 | 0.354087E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.688322E+09 | 0.221890E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.347137E+09 | 0.190534E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.345072E+09 | 0.197748E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.392305E+09 | 87704663.76 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.321900E+09 | 51276979.42 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.380099E+09 | 12418868.58 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.392459E+09 | 8247023.60 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.429528E+09 | 10183414.97 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.470295E+09 | 16448199.28 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.569298E+09 | 0.120200E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.566378E+09 | 0.190257E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.616222E+09 | 0.267859E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.551902E+10 | 0.137477E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.321900E+09 | 8247023.60 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.688322E+09 | 0.267859E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.489342E+09 | 0.455029E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.285331E+09 | 0.384383E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.499640E+09 | 0.373650E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.967384E+09 | 0.162343E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.110064E+10 | 95272690.17 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.133229E+10 | 22872744.15 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.109070E+10 | 15264415.30 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.101613E+10 | 18816353.68 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.806935E+09 | 31470870.57 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.636339E+09 | 0.239624E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.464458E+09 | 0.388411E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.347185E+09 | 0.554550E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.903637E+10 | 0.274169E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.285331E+09 | 15264415.30 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.133229E+10 | 0.554550E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 51326803.64 | 0.233059E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 30653247.95 | 0.203013E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 86126127.98 | 0.200967E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.186352E+09 | 83216932.27 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.271053E+09 | 45318234.98 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.415192E+09 | 10766562.46 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.387376E+09 | 7361095.09 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.318522E+09 | 9467160.23 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.255043E+09 | 16254755.76 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.124193E+09 | 0.124677E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 50378378.77 | 0.201019E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 32157432.07 | 0.287209E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.220837E+10 | 0.142233E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 30653247.95 | 7361095.09 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.415192E+09 | 0.287209E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.516647E+09 | 0.430936E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.301822E+09 | 0.370094E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.515950E+09 | 0.363789E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.974886E+09 | 0.159538E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.110200E+10 | 94967042.43 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.133087E+10 | 22956425.50 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.109089E+10 | 15290153.72 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.102006E+10 | 18465044.40 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.814358E+09 | 30303230.15 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.654675E+09 | 0.228732E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.486209E+09 | 0.369213E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.373614E+09 | 0.529774E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.918198E+10 | 0.263406E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.301822E+09 | 15290153.72 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.133087E+10 | 0.529774E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.992222E+09 | 0.342846E+09 |
February | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.495785E+09 | 0.294430E+09 |
March | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.497683E+09 | 0.295681E+09 |
April | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.584720E+09 | 0.123657E+09 |
May | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.489695E+09 | 70710604.92 |
June | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.583235E+09 | 15305827.81 |
July | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.595565E+09 | 10788022.55 |
August | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.646080E+09 | 13621517.36 |
September | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.697182E+09 | 23134003.86 |
October | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.828415E+09 | 0.181739E+09 |
November | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.816520E+09 | 0.292228E+09 |
December | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.881967E+09 | 0.415506E+09 |
Annual Sum or Average | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.810907E+10 | 0.207965E+10 |
Minimum of Months | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.489695E+09 | 10788022.55 |
Maximum of Months | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.992222E+09 | 0.415506E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.220628E+09 | 0.211815E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.111553E+09 | 0.196349E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.441203E+09 | 0.183589E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.116275E+10 | 0.827654E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.170852E+10 | 0.515454E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.267644E+10 | 0.168662E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.239471E+10 | 0.130322E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.195564E+10 | 0.182356E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.155386E+10 | 0.282832E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.708903E+09 | 0.120504E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.228155E+09 | 0.186739E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.108540E+09 | 0.260312E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.132709E+11 | 0.137004E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.108540E+09 | 0.130322E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.267644E+10 | 0.260312E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.197746E+09 | 0.217474E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 95244521.34 | 0.202951E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.411309E+09 | 0.188839E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.113726E+10 | 0.851017E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.168029E+10 | 0.531383E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.264516E+10 | 0.176216E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.236214E+10 | 0.137902E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.192602E+10 | 0.193453E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.152804E+10 | 0.297512E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.685525E+09 | 0.124016E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.207698E+09 | 0.192131E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 92709689.07 | 0.267644E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.129692E+11 | 0.141180E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 92709689.07 | 0.137902E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.264516E+10 | 0.267644E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 36548017.82 | 0.308323E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 18036999.40 | 0.288744E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 69200506.71 | 0.273315E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.180787E+09 | 0.129907E+09 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.263137E+09 | 87439662.08 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.399528E+09 | 34221393.37 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.358771E+09 | 28200891.23 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.299093E+09 | 37749665.92 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.240163E+09 | 52188105.47 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.111969E+09 | 0.183125E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 37720590.76 | 0.273397E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 19413904.88 | 0.372874E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.203437E+10 | 0.206948E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 18036999.40 | 28200891.23 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.399528E+09 | 0.372874E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.647832E+09 | 0.406608E+09 | 0.241223E+09 | 0.819018E+09 | 0.103532E+10 |
February | 0.581660E+09 | 0.334662E+09 | 0.246998E+09 | 0.634583E+09 | 0.980979E+09 |
March | 0.799654E+09 | 0.411405E+09 | 0.388250E+09 | 0.102397E+10 | 0.921824E+09 |
April | 0.110278E+10 | 0.657056E+09 | 0.445720E+09 | 0.195654E+10 | 0.452397E+09 |
May | 0.118295E+10 | 0.701920E+09 | 0.481032E+09 | 0.228444E+10 | 0.322232E+09 |
June | 0.119111E+10 | 0.739991E+09 | 0.451119E+09 | 0.270625E+10 | 0.128182E+09 |
July | 0.104108E+10 | 0.587423E+09 | 0.453658E+09 | 0.240988E+10 | 0.105341E+09 |
August | 0.988937E+09 | 0.565014E+09 | 0.423923E+09 | 0.225808E+10 | 0.141294E+09 |
September | 0.784240E+09 | 0.378243E+09 | 0.405997E+09 | 0.172328E+10 | 0.189848E+09 |
October | 0.813243E+09 | 0.494683E+09 | 0.318561E+09 | 0.135479E+10 | 0.622298E+09 |
November | 0.605626E+09 | 0.363437E+09 | 0.242189E+09 | 0.758858E+09 | 0.927202E+09 |
December | 0.571644E+09 | 0.345721E+09 | 0.225923E+09 | 0.621709E+09 | 0.124697E+10 |
Annual Sum or Average | 0.103108E+11 | 0.598616E+10 | 0.432459E+10 | 0.185514E+11 | 0.707389E+10 |
Minimum of Months | 0.571644E+09 | 0.334662E+09 | 0.225923E+09 | 0.621709E+09 | 0.105341E+09 |
Maximum of Months | 0.119111E+10 | 0.739991E+09 | 0.481032E+09 | 0.270625E+10 | 0.124697E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.688107E+09 | 0.274695E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.338061E+09 | 0.257200E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.335085E+09 | 0.258986E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.391849E+09 | 0.132957E+09 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.315809E+09 | 95450750.28 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.363089E+09 | 37172572.25 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.364716E+09 | 29827985.89 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.413243E+09 | 38764503.19 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.460576E+09 | 52117817.36 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.567490E+09 | 0.167541E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.564601E+09 | 0.243405E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.611401E+09 | 0.325384E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.541403E+10 | 0.191350E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.315809E+09 | 29827985.89 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.688107E+09 | 0.325384E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 50127513.93 | 0.332468E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 29915098.42 | 0.292530E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 99397220.88 | 0.279091E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.221882E+09 | 0.133211E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.320425E+09 | 84472118.06 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.492578E+09 | 26906535.23 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.441665E+09 | 19918416.67 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.360733E+09 | 27501015.00 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.287264E+09 | 43918251.42 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.137364E+09 | 0.190774E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 51441606.98 | 0.289596E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 27883754.57 | 0.407061E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.252068E+10 | 0.212745E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 27883754.57 | 19918416.67 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.492578E+09 | 0.407061E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60817333.99 | 0.00 | 60817333.99 | 44849276.64 | 0.297428E+09 |
February | 62593289.17 | 0.00 | 62593289.17 | 26765151.90 | 0.261728E+09 |
March | 92115091.26 | 3644.19 | 92111447.08 | 88931070.13 | 0.249704E+09 |
April | 0.109174E+09 | 1607428.26 | 0.107566E+09 | 0.198519E+09 | 0.119185E+09 |
May | 0.132329E+09 | 11236257.28 | 0.121093E+09 | 0.286686E+09 | 75577524.09 |
June | 0.147891E+09 | 27022215.34 | 0.120869E+09 | 0.440711E+09 | 24073379.02 |
July | 0.130730E+09 | 14047058.93 | 0.116683E+09 | 0.395160E+09 | 17821082.87 |
August | 0.105192E+09 | 2582762.23 | 0.102609E+09 | 0.322749E+09 | 24605262.32 |
September | 95995470.41 | 59410.39 | 95936060.02 | 0.257016E+09 | 39293825.95 |
October | 76698758.25 | 0.00 | 76698758.25 | 0.122900E+09 | 0.170689E+09 |
November | 61842695.04 | 0.00 | 61842695.04 | 46025000.67 | 0.259093E+09 |
December | 56808956.88 | 0.00 | 56808956.88 | 24947700.86 | 0.364155E+09 |
Annual Sum or Average | 0.113219E+10 | 56558776.60 | 0.107563E+10 | 0.225526E+10 | 0.190335E+10 |
Minimum of Months | 56808956.88 | 0.00 | 56808956.88 | 24947700.86 | 17821082.87 |
Maximum of Months | 0.147891E+09 | 27022215.34 | 0.121093E+09 | 0.440711E+09 | 0.364155E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165223E+10 | 0.131994E+10 | 0.332291E+09 | 0.257065E+10 | 0.877393E+09 |
February | 0.931184E+09 | 0.624266E+09 | 0.306919E+09 | 0.128928E+10 | 0.776610E+09 |
March | 0.853459E+09 | 0.432470E+09 | 0.420989E+09 | 0.128355E+10 | 0.787700E+09 |
April | 0.724889E+09 | 0.298600E+09 | 0.426289E+09 | 0.143455E+10 | 0.404947E+09 |
May | 0.500505E+09 | 87064857.88 | 0.413440E+09 | 0.114241E+10 | 0.278836E+09 |
June | 0.409987E+09 | 31279350.23 | 0.378708E+09 | 0.132081E+10 | 90876792.95 |
July | 0.429299E+09 | 40817377.39 | 0.388482E+09 | 0.132152E+10 | 64337443.62 |
August | 0.530848E+09 | 0.149505E+09 | 0.381343E+09 | 0.148475E+10 | 85112102.59 |
September | 0.729722E+09 | 0.308417E+09 | 0.421305E+09 | 0.166090E+10 | 0.128014E+09 |
October | 0.121037E+10 | 0.837901E+09 | 0.372471E+09 | 0.209298E+10 | 0.517846E+09 |
November | 0.137684E+10 | 0.105747E+10 | 0.319371E+09 | 0.211115E+10 | 0.763881E+09 |
December | 0.153868E+10 | 0.121905E+10 | 0.319635E+09 | 0.229643E+10 | 0.105656E+10 |
Annual Sum or Average | 0.108880E+11 | 0.640678E+10 | 0.448124E+10 | 0.200090E+11 | 0.583212E+10 |
Minimum of Months | 0.409987E+09 | 31279350.23 | 0.306919E+09 | 0.114241E+10 | 64337443.62 |
Maximum of Months | 0.165223E+10 | 0.131994E+10 | 0.426289E+09 | 0.257065E+10 | 0.105656E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1280.22 | 440.98 | 835.71 | 667.64 | 168.07 | 0.00 | 0.00 |
February | 717.95 | 412.69 | 521.47 | 349.59 | 171.87 | 0.00 | 0.00 |
March | 650.65 | 374.85 | 431.69 | 218.75 | 212.94 | 0.00 | 0.00 |
April | 733.05 | 214.23 | 378.88 | 156.07 | 222.81 | 0.00 | 0.00 |
May | 550.79 | 144.71 | 253.16 | 44.04 | 209.12 | 0.00 | 0.00 |
June | 633.59 | 54.87 | 214.28 | 16.35 | 197.94 | 0.00 | 0.00 |
July | 622.82 | 36.69 | 217.14 | 20.65 | 196.50 | 0.00 | 0.00 |
August | 712.07 | 49.19 | 268.51 | 75.62 | 192.88 | 0.00 | 0.00 |
September | 840.57 | 74.82 | 381.40 | 161.20 | 220.20 | 0.00 | 0.00 |
October | 1044.55 | 264.78 | 612.22 | 423.82 | 188.40 | 0.00 | 0.00 |
November | 1090.76 | 393.64 | 719.63 | 552.71 | 166.92 | 0.00 | 0.00 |
December | 1138.46 | 522.52 | 778.28 | 616.61 | 161.67 | 0.00 | 0.00 |
Annual Sum or Average | 835.69 | 248.02 | 467.74 | 275.23 | 192.51 | 0.00 | 0.00 |
Minimum of Months | 550.79 | 36.69 | 214.28 | 16.35 | 161.67 | 0.00 | 0.00 |
Maximum of Months | 1280.22 | 522.52 | 835.71 | 667.64 | 222.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3553.12 | 1355.84 | 2353.32 | 1880.03 | 473.29 | 0.00 | 0.00 |
February | 1967.31 | 1317.03 | 1468.41 | 984.43 | 483.99 | 0.00 | 0.00 |
March | 1773.30 | 1187.03 | 1215.60 | 615.98 | 599.62 | 0.00 | 0.00 |
April | 2035.31 | 648.02 | 1066.89 | 439.48 | 627.41 | 0.00 | 0.00 |
May | 1530.23 | 434.89 | 712.87 | 124.01 | 588.87 | 0.00 | 0.00 |
June | 1778.91 | 159.10 | 603.41 | 46.04 | 557.38 | 0.00 | 0.00 |
July | 1742.55 | 112.10 | 611.46 | 58.14 | 553.32 | 0.00 | 0.00 |
August | 1990.75 | 152.14 | 756.09 | 212.94 | 543.15 | 0.00 | 0.00 |
September | 2346.55 | 228.76 | 1074.00 | 453.93 | 620.07 | 0.00 | 0.00 |
October | 2902.60 | 811.16 | 1723.96 | 1193.45 | 530.51 | 0.00 | 0.00 |
November | 3021.26 | 1222.33 | 2026.44 | 1556.40 | 470.05 | 0.00 | 0.00 |
December | 3149.81 | 1611.07 | 2191.58 | 1736.32 | 455.26 | 0.00 | 0.00 |
Annual Sum or Average | 2319.06 | 767.71 | 1317.12 | 775.03 | 542.09 | 0.00 | 0.00 |
Minimum of Months | 1530.23 | 112.10 | 603.41 | 46.04 | 455.26 | 0.00 | 0.00 |
Maximum of Months | 3553.12 | 1611.07 | 2353.32 | 1880.03 | 627.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4728.97 | 1770.71 | 3057.09 | 2442.27 | 614.83 | 0.00 | 0.00 |
February | 2625.60 | 1764.14 | 1907.55 | 1278.83 | 628.73 | 0.00 | 0.00 |
March | 2367.05 | 1583.27 | 1579.13 | 800.19 | 778.94 | 0.00 | 0.00 |
April | 2735.36 | 844.63 | 1385.95 | 570.91 | 815.04 | 0.00 | 0.00 |
May | 2063.46 | 567.40 | 926.06 | 161.09 | 764.97 | 0.00 | 0.00 |
June | 2407.40 | 203.21 | 783.87 | 59.80 | 724.06 | 0.00 | 0.00 |
July | 2359.39 | 140.43 | 794.32 | 75.52 | 718.79 | 0.00 | 0.00 |
August | 2684.81 | 188.55 | 982.21 | 276.63 | 705.58 | 0.00 | 0.00 |
September | 3150.19 | 284.86 | 1395.19 | 589.68 | 805.51 | 0.00 | 0.00 |
October | 3873.69 | 1055.48 | 2239.52 | 1550.35 | 689.17 | 0.00 | 0.00 |
November | 4019.47 | 1604.38 | 2632.46 | 2021.85 | 610.62 | 0.00 | 0.00 |
December | 4191.20 | 2127.13 | 2846.99 | 2255.58 | 591.41 | 0.00 | 0.00 |
Annual Sum or Average | 3104.70 | 1008.03 | 1711.02 | 1006.81 | 704.21 | 0.00 | 0.00 |
Minimum of Months | 2063.46 | 140.43 | 783.87 | 59.80 | 591.41 | 0.00 | 0.00 |
Maximum of Months | 4728.97 | 2127.13 | 3057.09 | 2442.27 | 815.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 433.61 | 245.35 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 257.20 | 233.19 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 316.29 | 211.12 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 528.62 | 98.76 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 533.05 | 57.75 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 661.60 | 15.07 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 554.06 | 9.43 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 540.37 | 11.76 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 493.80 | 20.28 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 449.54 | 134.51 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 392.80 | 217.70 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 348.85 | 296.98 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 460.15 | 128.92 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 257.20 | 9.43 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 661.60 | 296.98 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.11 | 251.84 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 136.52 | 239.16 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 224.70 | 210.64 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 451.08 | 96.09 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 512.62 | 53.50 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 673.74 | 13.19 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 551.94 | 8.67 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 499.86 | 11.11 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 412.60 | 19.71 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 290.25 | 135.78 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 205.96 | 223.39 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 149.52 | 308.72 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 361.00 | 130.57 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 136.52 | 8.67 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 673.74 | 308.72 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 202.36 | 75.94 | 132.16 | 105.58 | 26.58 | 0.00 | 0.00 |
February | 111.35 | 74.28 | 82.47 | 55.29 | 27.18 | 0.00 | 0.00 |
March | 100.52 | 66.44 | 68.27 | 34.59 | 33.67 | 0.00 | 0.00 |
April | 120.43 | 33.07 | 59.92 | 24.68 | 35.24 | 0.00 | 0.00 |
May | 94.68 | 20.79 | 40.04 | 6.96 | 33.07 | 0.00 | 0.00 |
June | 114.45 | 6.33 | 33.89 | 2.59 | 31.30 | 0.00 | 0.00 |
July | 111.58 | 4.12 | 34.34 | 3.26 | 31.07 | 0.00 | 0.00 |
August | 123.76 | 5.47 | 42.46 | 11.96 | 30.50 | 0.00 | 0.00 |
September | 141.42 | 8.98 | 60.32 | 25.49 | 34.82 | 0.00 | 0.00 |
October | 167.76 | 42.84 | 96.82 | 67.02 | 29.79 | 0.00 | 0.00 |
November | 172.11 | 67.73 | 113.80 | 87.41 | 26.40 | 0.00 | 0.00 |
December | 179.35 | 91.81 | 123.08 | 97.51 | 25.57 | 0.00 | 0.00 |
Annual Sum or Average | 136.85 | 41.35 | 73.97 | 43.53 | 30.44 | 0.00 | 0.00 |
Minimum of Months | 94.68 | 4.12 | 33.89 | 2.59 | 25.57 | 0.00 | 0.00 |
Maximum of Months | 202.36 | 91.81 | 132.16 | 105.58 | 35.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.74 | 69.71 | 16.03 | 0.00 | 16.03 | 0.00 | 0.00 |
February | 10.65 | 69.47 | 18.27 | 0.00 | 18.27 | 0.00 | 0.00 |
March | 27.86 | 59.70 | 24.29 | 0.00 | 24.28 | 0.00 | 0.00 |
April | 63.87 | 24.05 | 29.74 | 0.44 | 29.30 | 0.00 | 0.00 |
May | 87.58 | 12.56 | 34.89 | 2.96 | 31.92 | 0.00 | 0.00 |
June | 136.74 | 2.69 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
July | 123.41 | 1.87 | 34.47 | 3.70 | 30.76 | 0.00 | 0.00 |
August | 102.51 | 2.34 | 27.73 | 0.68 | 27.05 | 0.00 | 0.00 |
September | 84.86 | 4.33 | 26.15 | 0.02 | 26.14 | 0.00 | 0.00 |
October | 40.82 | 36.47 | 20.22 | 0.00 | 20.22 | 0.00 | 0.00 |
November | 17.18 | 61.82 | 16.85 | 0.00 | 16.85 | 0.00 | 0.00 |
December | 9.79 | 88.15 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Annual Sum or Average | 60.40 | 35.96 | 25.35 | 1.27 | 24.08 | 0.00 | 0.00 |
Minimum of Months | 9.79 | 1.87 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Maximum of Months | 136.74 | 88.15 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 412.85 | 234.52 | 286.18 | 207.91 | 78.27 | 0.00 | 0.00 |
February | 278.05 | 226.35 | 223.33 | 138.29 | 85.04 | 0.00 | 0.00 |
March | 324.24 | 198.60 | 234.64 | 120.06 | 114.59 | 0.00 | 0.00 |
April | 523.22 | 87.49 | 287.65 | 157.61 | 130.04 | 0.00 | 0.00 |
May | 541.60 | 49.78 | 270.90 | 139.75 | 131.15 | 0.00 | 0.00 |
June | 675.75 | 12.59 | 272.15 | 145.99 | 126.16 | 0.00 | 0.00 |
July | 611.17 | 8.18 | 237.29 | 113.75 | 123.55 | 0.00 | 0.00 |
August | 590.03 | 11.06 | 237.72 | 120.44 | 117.28 | 0.00 | 0.00 |
September | 518.62 | 18.73 | 226.70 | 104.84 | 121.86 | 0.00 | 0.00 |
October | 464.97 | 128.15 | 272.87 | 176.15 | 96.72 | 0.00 | 0.00 |
November | 366.99 | 208.63 | 259.12 | 179.39 | 79.73 | 0.00 | 0.00 |
December | 346.84 | 286.85 | 260.60 | 186.46 | 74.14 | 0.00 | 0.00 |
Annual Sum or Average | 472.23 | 122.17 | 255.97 | 149.33 | 106.63 | 0.00 | 0.00 |
Minimum of Months | 278.05 | 8.18 | 223.33 | 104.84 | 74.14 | 0.00 | 0.00 |
Maximum of Months | 675.75 | 286.85 | 287.65 | 207.91 | 131.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.00 | 225.68 | 140.98 | 75.91 | 65.07 | 0.00 | 0.00 |
February | 147.59 | 222.46 | 143.06 | 69.17 | 73.89 | 0.00 | 0.00 |
March | 228.66 | 194.82 | 179.64 | 76.81 | 102.83 | 0.00 | 0.00 |
April | 446.09 | 86.00 | 249.91 | 127.30 | 122.61 | 0.00 | 0.00 |
May | 524.91 | 49.44 | 264.45 | 134.75 | 129.71 | 0.00 | 0.00 |
June | 689.82 | 12.55 | 280.14 | 151.96 | 128.18 | 0.00 | 0.00 |
July | 609.79 | 8.15 | 237.44 | 114.30 | 123.14 | 0.00 | 0.00 |
August | 549.79 | 10.82 | 219.29 | 106.33 | 112.95 | 0.00 | 0.00 |
September | 437.20 | 18.16 | 183.98 | 72.99 | 110.99 | 0.00 | 0.00 |
October | 299.29 | 124.24 | 177.10 | 92.35 | 84.75 | 0.00 | 0.00 |
November | 168.95 | 202.18 | 137.89 | 70.11 | 67.78 | 0.00 | 0.00 |
December | 129.55 | 279.60 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Annual Sum or Average | 368.36 | 119.10 | 195.17 | 96.50 | 98.67 | 0.00 | 0.00 |
Minimum of Months | 129.55 | 8.15 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Maximum of Months | 689.82 | 279.60 | 280.14 | 151.96 | 129.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 469.52 | 306.57 | 321.09 | 228.77 | 92.33 | 0.00 | 0.00 |
February | 264.16 | 297.16 | 218.26 | 119.79 | 98.47 | 0.00 | 0.00 |
March | 282.95 | 271.22 | 200.53 | 74.96 | 125.57 | 0.00 | 0.00 |
April | 390.60 | 137.53 | 194.25 | 54.43 | 139.83 | 0.00 | 0.00 |
May | 374.40 | 85.51 | 162.32 | 21.51 | 140.82 | 0.00 | 0.00 |
June | 508.80 | 27.09 | 160.71 | 21.55 | 139.16 | 0.00 | 0.00 |
July | 470.85 | 18.61 | 149.07 | 15.10 | 133.97 | 0.00 | 0.00 |
August | 457.04 | 25.34 | 152.08 | 27.39 | 124.70 | 0.00 | 0.00 |
September | 463.66 | 42.10 | 187.34 | 55.27 | 132.07 | 0.00 | 0.00 |
October | 439.04 | 183.21 | 253.58 | 145.22 | 108.36 | 0.00 | 0.00 |
November | 403.61 | 276.61 | 283.08 | 189.39 | 93.69 | 0.00 | 0.00 |
December | 403.91 | 369.08 | 299.12 | 211.28 | 87.84 | 0.00 | 0.00 |
Annual Sum or Average | 411.58 | 169.49 | 215.19 | 97.05 | 118.14 | 0.00 | 0.00 |
Minimum of Months | 264.16 | 18.61 | 149.07 | 15.10 | 87.84 | 0.00 | 0.00 |
Maximum of Months | 508.80 | 369.08 | 321.09 | 228.77 | 140.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 430.58 | 243.63 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 254.46 | 230.67 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 312.35 | 210.30 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 524.18 | 96.08 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 531.11 | 54.71 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 660.64 | 13.61 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 553.75 | 8.78 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 539.71 | 10.79 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 492.74 | 18.47 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 447.08 | 131.29 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 389.93 | 215.48 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 347.27 | 294.63 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 457.99 | 126.98 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 254.46 | 8.78 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 660.64 | 294.63 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.06 | 246.91 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 135.45 | 234.92 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 222.53 | 208.60 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 447.74 | 93.39 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 511.13 | 50.87 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 672.70 | 12.08 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 551.60 | 8.14 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 499.60 | 10.26 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 412.57 | 17.96 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 290.11 | 131.26 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 205.68 | 218.66 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 149.99 | 303.52 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 360.19 | 127.63 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 135.45 | 8.14 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 672.70 | 303.52 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 370.45 | 128.00 | 242.33 | 193.60 | 48.74 | 0.00 | 0.00 |
February | 204.94 | 121.71 | 151.21 | 101.37 | 49.84 | 0.00 | 0.00 |
March | 185.81 | 110.39 | 125.18 | 63.43 | 61.75 | 0.00 | 0.00 |
April | 225.59 | 47.71 | 109.86 | 45.26 | 64.61 | 0.00 | 0.00 |
May | 182.83 | 26.40 | 73.41 | 12.77 | 60.64 | 0.00 | 0.00 |
June | 225.01 | 5.91 | 62.14 | 4.74 | 57.40 | 0.00 | 0.00 |
July | 222.36 | 4.03 | 62.97 | 5.99 | 56.98 | 0.00 | 0.00 |
August | 241.22 | 5.09 | 77.86 | 21.93 | 55.93 | 0.00 | 0.00 |
September | 268.97 | 8.93 | 110.60 | 46.74 | 63.85 | 0.00 | 0.00 |
October | 309.29 | 67.85 | 177.53 | 122.90 | 54.63 | 0.00 | 0.00 |
November | 315.02 | 112.74 | 208.67 | 160.27 | 48.40 | 0.00 | 0.00 |
December | 329.29 | 155.13 | 225.68 | 178.80 | 46.88 | 0.00 | 0.00 |
Annual Sum or Average | 257.14 | 65.95 | 135.63 | 79.81 | 55.82 | 0.00 | 0.00 |
Minimum of Months | 182.83 | 4.03 | 62.14 | 4.74 | 46.88 | 0.00 | 0.00 |
Maximum of Months | 370.45 | 155.13 | 242.33 | 193.60 | 64.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 82.37 | 790.83 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 46.11 | 811.63 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 164.73 | 685.44 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 448.59 | 319.31 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 637.89 | 192.45 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1032.58 | 65.07 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 894.08 | 48.66 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 730.15 | 68.08 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 599.48 | 109.12 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 264.67 | 449.91 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 88.02 | 720.44 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 40.52 | 971.89 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 420.82 | 434.44 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 40.52 | 48.66 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1032.58 | 971.89 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 73.83 | 811.96 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 39.37 | 838.92 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 153.57 | 705.05 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 438.76 | 328.32 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 627.35 | 198.40 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1020.51 | 67.98 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 881.92 | 51.49 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 719.09 | 72.23 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 589.52 | 114.78 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 255.95 | 463.02 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 80.13 | 741.25 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 34.61 | 999.27 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 411.25 | 447.68 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 34.61 | 51.49 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1020.51 | 999.27 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 560.37 | 588.25 | 427.15 | 283.81 | 143.33 | 0.00 | 0.00 |
February | 390.60 | 612.26 | 366.37 | 207.46 | 158.92 | 0.00 | 0.00 |
March | 519.63 | 529.29 | 414.26 | 196.85 | 217.41 | 0.00 | 0.00 |
April | 967.30 | 267.49 | 537.54 | 284.90 | 252.64 | 0.00 | 0.00 |
May | 1065.18 | 184.70 | 535.32 | 274.48 | 260.84 | 0.00 | 0.00 |
June | 1337.16 | 75.86 | 552.26 | 297.92 | 254.33 | 0.00 | 0.00 |
July | 1169.20 | 60.34 | 474.70 | 228.03 | 246.68 | 0.00 | 0.00 |
August | 1108.53 | 80.82 | 456.98 | 226.75 | 230.22 | 0.00 | 0.00 |
September | 933.96 | 112.26 | 410.66 | 177.82 | 232.84 | 0.00 | 0.00 |
October | 751.08 | 354.84 | 449.95 | 268.49 | 181.46 | 0.00 | 0.00 |
November | 508.19 | 540.14 | 396.99 | 249.50 | 147.50 | 0.00 | 0.00 |
December | 442.36 | 700.99 | 386.03 | 250.99 | 135.03 | 0.00 | 0.00 |
Annual Sum or Average | 814.91 | 341.07 | 451.12 | 245.82 | 205.30 | 0.00 | 0.00 |
Minimum of Months | 390.60 | 60.34 | 366.37 | 177.82 | 135.03 | 0.00 | 0.00 |
Maximum of Months | 1337.16 | 700.99 | 552.26 | 297.92 | 260.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 976.50 | 544.03 | 664.96 | 492.81 | 172.15 | 0.00 | 0.00 |
February | 541.07 | 534.83 | 439.71 | 258.05 | 181.66 | 0.00 | 0.00 |
March | 545.95 | 487.94 | 391.48 | 161.47 | 230.01 | 0.00 | 0.00 |
April | 715.37 | 253.33 | 368.86 | 116.51 | 252.35 | 0.00 | 0.00 |
May | 649.66 | 160.33 | 291.49 | 41.39 | 250.10 | 0.00 | 0.00 |
June | 866.73 | 51.82 | 279.00 | 34.15 | 244.86 | 0.00 | 0.00 |
July | 804.70 | 36.98 | 263.64 | 26.35 | 237.30 | 0.00 | 0.00 |
August | 808.95 | 50.65 | 281.37 | 57.86 | 223.51 | 0.00 | 0.00 |
September | 850.68 | 81.41 | 359.96 | 119.04 | 240.92 | 0.00 | 0.00 |
October | 872.20 | 321.90 | 512.54 | 312.84 | 199.71 | 0.00 | 0.00 |
November | 834.97 | 489.27 | 581.72 | 407.98 | 173.74 | 0.00 | 0.00 |
December | 850.60 | 655.90 | 619.39 | 455.14 | 164.25 | 0.00 | 0.00 |
Annual Sum or Average | 777.94 | 304.77 | 421.29 | 206.96 | 214.33 | 0.00 | 0.00 |
Minimum of Months | 541.07 | 36.98 | 263.64 | 26.35 | 164.25 | 0.00 | 0.00 |
Maximum of Months | 976.50 | 655.90 | 664.96 | 492.81 | 252.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.342894E+10 | 0.118112E+10 | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.00 | 0.00 |
February | 0.173686E+10 | 0.998376E+09 | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.00 | 0.00 |
March | 0.174271E+10 | 0.100400E+10 | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.00 | 0.00 |
April | 0.190007E+10 | 0.555290E+09 | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.00 | 0.00 |
May | 0.147524E+10 | 0.387599E+09 | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.00 | 0.00 |
June | 0.164226E+10 | 0.142217E+09 | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.00 | 0.00 |
July | 0.166817E+10 | 98267454.74 | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.00 | 0.00 |
August | 0.190720E+10 | 0.131755E+09 | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.00 | 0.00 |
September | 0.217876E+10 | 0.193921E+09 | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.00 | 0.00 |
October | 0.279772E+10 | 0.709179E+09 | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.00 | 0.00 |
November | 0.282726E+10 | 0.102030E+10 | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.00 | 0.00 |
December | 0.304925E+10 | 0.139953E+10 | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.263544E+11 | 0.782155E+10 | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.00 | 0.00 |
Minimum of Months | 0.147524E+10 | 98267454.74 | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.00 | 0.00 |
Maximum of Months | 0.342894E+10 | 0.139953E+10 | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.951667E+10 | 0.363148E+10 | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.00 | 0.00 |
February | 0.475932E+10 | 0.318617E+10 | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.00 | 0.00 |
March | 0.474962E+10 | 0.317935E+10 | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.00 | 0.00 |
April | 0.527552E+10 | 0.167966E+10 | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.00 | 0.00 |
May | 0.409856E+10 | 0.116481E+10 | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.00 | 0.00 |
June | 0.461093E+10 | 0.412383E+09 | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.00 | 0.00 |
July | 0.466724E+10 | 0.300236E+09 | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.00 | 0.00 |
August | 0.533203E+10 | 0.407480E+09 | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.00 | 0.00 |
September | 0.608226E+10 | 0.592939E+09 | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.00 | 0.00 |
October | 0.777432E+10 | 0.217262E+10 | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.00 | 0.00 |
November | 0.783109E+10 | 0.316829E+10 | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.00 | 0.00 |
December | 0.843644E+10 | 0.431508E+10 | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.731340E+11 | 0.242105E+11 | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409856E+10 | 0.300236E+09 | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.00 | 0.00 |
Maximum of Months | 0.951667E+10 | 0.431508E+10 | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126661E+11 | 0.474266E+10 | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.00 | 0.00 |
February | 0.635184E+10 | 0.426780E+10 | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.00 | 0.00 |
March | 0.633991E+10 | 0.424062E+10 | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.00 | 0.00 |
April | 0.709005E+10 | 0.218928E+10 | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.00 | 0.00 |
May | 0.552676E+10 | 0.151972E+10 | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.00 | 0.00 |
June | 0.623999E+10 | 0.526715E+09 | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.00 | 0.00 |
July | 0.631939E+10 | 0.376122E+09 | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.00 | 0.00 |
August | 0.719100E+10 | 0.505015E+09 | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.00 | 0.00 |
September | 0.816530E+10 | 0.738357E+09 | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.00 | 0.00 |
October | 0.103753E+11 | 0.282699E+10 | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.00 | 0.00 |
November | 0.104185E+11 | 0.415856E+10 | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.00 | 0.00 |
December | 0.112257E+11 | 0.569731E+10 | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.979098E+11 | 0.317892E+11 | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.00 | 0.00 |
Minimum of Months | 0.552676E+10 | 0.376122E+09 | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126661E+11 | 0.569731E+10 | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116139E+10 | 0.657137E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.622228E+09 | 0.564138E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.847140E+09 | 0.565474E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.137019E+10 | 0.255976E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.142772E+10 | 0.154674E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.171486E+10 | 39056939.98 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.148400E+10 | 25252365.18 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.144733E+10 | 31491797.62 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.127993E+10 | 52570342.15 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.120404E+10 | 0.360260E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.101813E+10 | 0.564291E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.934354E+09 | 0.795438E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.145113E+11 | 0.406576E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.622228E+09 | 25252365.18 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.171486E+10 | 0.795438E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.565430E+09 | 0.674522E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.330269E+09 | 0.578582E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.601828E+09 | 0.564174E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.116920E+10 | 0.249064E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.137301E+10 | 0.143302E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.174634E+10 | 34200649.79 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.147830E+10 | 23221624.40 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.133884E+10 | 29765108.86 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.106947E+10 | 51087887.06 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.777413E+09 | 0.363685E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.533840E+09 | 0.579038E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.400469E+09 | 0.826871E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113844E+11 | 0.411751E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.330269E+09 | 23221624.40 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.174634E+10 | 0.826871E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.541995E+09 | 0.203410E+09 | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.00 | 0.00 |
February | 0.269378E+09 | 0.179700E+09 | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.00 | 0.00 |
March | 0.269230E+09 | 0.177964E+09 | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.00 | 0.00 |
April | 0.312151E+09 | 85724681.85 | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.00 | 0.00 |
May | 0.253592E+09 | 55676746.09 | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.00 | 0.00 |
June | 0.296647E+09 | 16409232.72 | 87837819.98 | 6701448.63 | 81136371.35 | 0.00 | 0.00 |
July | 0.298868E+09 | 11030670.16 | 91975290.32 | 8744924.55 | 83230365.76 | 0.00 | 0.00 |
August | 0.331473E+09 | 14637750.41 | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.00 | 0.00 |
September | 0.366558E+09 | 23268454.23 | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.00 | 0.00 |
October | 0.449340E+09 | 0.114749E+09 | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.00 | 0.00 |
November | 0.446099E+09 | 0.175545E+09 | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.00 | 0.00 |
December | 0.480378E+09 | 0.245917E+09 | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.00 | 0.00 |
Annual Sum or Average | 0.431571E+10 | 0.130403E+10 | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.00 | 0.00 |
Minimum of Months | 0.253592E+09 | 11030670.16 | 87837819.98 | 6701448.63 | 65755807.07 | 0.00 | 0.00 |
Maximum of Months | 0.541995E+09 | 0.245917E+09 | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 44845693.18 | 0.186713E+09 | 42944949.46 | 0.00 | 42944949.46 | 0.00 | 0.00 |
February | 25761976.81 | 0.168067E+09 | 44199004.85 | 0.00 | 44199004.85 | 0.00 | 0.00 |
March | 74631670.24 | 0.159909E+09 | 65045237.58 | 2573.27 | 65042664.31 | 0.00 | 0.00 |
April | 0.165561E+09 | 62333869.82 | 77090857.89 | 1135053.46 | 75955804.43 | 0.00 | 0.00 |
May | 0.234561E+09 | 33640998.93 | 93441433.49 | 7934259.35 | 85507174.14 | 0.00 | 0.00 |
June | 0.354419E+09 | 6984403.84 | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.00 | 0.00 |
July | 0.330537E+09 | 4998216.33 | 92312481.83 | 9919050.97 | 82393430.86 | 0.00 | 0.00 |
August | 0.274556E+09 | 6254403.95 | 74279179.59 | 1823766.12 | 72455413.47 | 0.00 | 0.00 |
September | 0.219949E+09 | 11234229.69 | 67785290.05 | 41951.47 | 67743338.59 | 0.00 | 0.00 |
October | 0.109330E+09 | 97678152.30 | 54159300.98 | 0.00 | 54159300.98 | 0.00 | 0.00 |
November | 44530025.56 | 0.160231E+09 | 43668987.75 | 0.00 | 43668987.75 | 0.00 | 0.00 |
December | 26214178.11 | 0.236103E+09 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.190490E+10 | 0.113415E+10 | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.00 | 0.00 |
Minimum of Months | 25761976.81 | 4998216.33 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Maximum of Months | 0.354419E+09 | 0.236103E+09 | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110579E+10 | 0.628140E+09 | 0.766505E+09 | 0.556878E+09 | 0.209627E+09 | 0.00 | 0.00 |
February | 0.672655E+09 | 0.547591E+09 | 0.540277E+09 | 0.334558E+09 | 0.205719E+09 | 0.00 | 0.00 |
March | 0.868446E+09 | 0.531921E+09 | 0.628463E+09 | 0.321558E+09 | 0.306905E+09 | 0.00 | 0.00 |
April | 0.135618E+10 | 0.226767E+09 | 0.745596E+09 | 0.408534E+09 | 0.337062E+09 | 0.00 | 0.00 |
May | 0.145062E+10 | 0.133328E+09 | 0.725583E+09 | 0.374306E+09 | 0.351277E+09 | 0.00 | 0.00 |
June | 0.175154E+10 | 32621581.37 | 0.705417E+09 | 0.378400E+09 | 0.327016E+09 | 0.00 | 0.00 |
July | 0.163697E+10 | 21911967.51 | 0.635569E+09 | 0.304666E+09 | 0.330904E+09 | 0.00 | 0.00 |
August | 0.158034E+10 | 29613504.69 | 0.636696E+09 | 0.322574E+09 | 0.314123E+09 | 0.00 | 0.00 |
September | 0.134426E+10 | 48558521.33 | 0.587611E+09 | 0.271747E+09 | 0.315864E+09 | 0.00 | 0.00 |
October | 0.124537E+10 | 0.343225E+09 | 0.730860E+09 | 0.471799E+09 | 0.259061E+09 | 0.00 | 0.00 |
November | 0.951245E+09 | 0.540774E+09 | 0.671635E+09 | 0.464986E+09 | 0.206650E+09 | 0.00 | 0.00 |
December | 0.928982E+09 | 0.768298E+09 | 0.697993E+09 | 0.499406E+09 | 0.198587E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148924E+11 | 0.385275E+10 | 0.807221E+10 | 0.470941E+10 | 0.336279E+10 | 0.00 | 0.00 |
Minimum of Months | 0.672655E+09 | 21911967.51 | 0.540277E+09 | 0.271747E+09 | 0.198587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175154E+10 | 0.768298E+09 | 0.766505E+09 | 0.556878E+09 | 0.351277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.471393E+09 | 0.604448E+09 | 0.377613E+09 | 0.203319E+09 | 0.174294E+09 | 0.00 | 0.00 |
February | 0.357054E+09 | 0.538166E+09 | 0.346092E+09 | 0.167343E+09 | 0.178749E+09 | 0.00 | 0.00 |
March | 0.612433E+09 | 0.521801E+09 | 0.481151E+09 | 0.205720E+09 | 0.275431E+09 | 0.00 | 0.00 |
April | 0.115625E+10 | 0.222907E+09 | 0.647778E+09 | 0.329970E+09 | 0.317808E+09 | 0.00 | 0.00 |
May | 0.140591E+10 | 0.132412E+09 | 0.708304E+09 | 0.360901E+09 | 0.347403E+09 | 0.00 | 0.00 |
June | 0.178800E+10 | 32525222.36 | 0.726118E+09 | 0.393870E+09 | 0.332248E+09 | 0.00 | 0.00 |
July | 0.163327E+10 | 21832720.13 | 0.635953E+09 | 0.306130E+09 | 0.329823E+09 | 0.00 | 0.00 |
August | 0.147255E+10 | 28992027.74 | 0.587340E+09 | 0.284806E+09 | 0.302534E+09 | 0.00 | 0.00 |
September | 0.113323E+10 | 47080659.29 | 0.476868E+09 | 0.189187E+09 | 0.287681E+09 | 0.00 | 0.00 |
October | 0.801619E+09 | 0.332767E+09 | 0.474341E+09 | 0.247359E+09 | 0.226982E+09 | 0.00 | 0.00 |
November | 0.437914E+09 | 0.524043E+09 | 0.357413E+09 | 0.181731E+09 | 0.175682E+09 | 0.00 | 0.00 |
December | 0.347000E+09 | 0.748867E+09 | 0.335979E+09 | 0.172873E+09 | 0.163106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116166E+11 | 0.375584E+10 | 0.615495E+10 | 0.304321E+10 | 0.311174E+10 | 0.00 | 0.00 |
Minimum of Months | 0.347000E+09 | 21832720.13 | 0.335979E+09 | 0.167343E+09 | 0.163106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178800E+10 | 0.748867E+09 | 0.726118E+09 | 0.393870E+09 | 0.347403E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125755E+10 | 0.821107E+09 | 0.860015E+09 | 0.612730E+09 | 0.247286E+09 | 0.00 | 0.00 |
February | 0.639059E+09 | 0.718886E+09 | 0.528015E+09 | 0.289790E+09 | 0.238224E+09 | 0.00 | 0.00 |
March | 0.757848E+09 | 0.726425E+09 | 0.537094E+09 | 0.200762E+09 | 0.336332E+09 | 0.00 | 0.00 |
April | 0.101243E+10 | 0.356466E+09 | 0.503505E+09 | 0.141072E+09 | 0.362433E+09 | 0.00 | 0.00 |
May | 0.100279E+10 | 0.229023E+09 | 0.434765E+09 | 57604611.69 | 0.377160E+09 | 0.00 | 0.00 |
June | 0.131881E+10 | 70207943.02 | 0.416551E+09 | 55856451.63 | 0.360695E+09 | 0.00 | 0.00 |
July | 0.126111E+10 | 49833089.77 | 0.399265E+09 | 40435810.09 | 0.358829E+09 | 0.00 | 0.00 |
August | 0.122414E+10 | 67869034.11 | 0.407338E+09 | 73352738.99 | 0.333986E+09 | 0.00 | 0.00 |
September | 0.120182E+10 | 0.109120E+09 | 0.485590E+09 | 0.143261E+09 | 0.342329E+09 | 0.00 | 0.00 |
October | 0.117594E+10 | 0.490702E+09 | 0.679193E+09 | 0.388962E+09 | 0.290232E+09 | 0.00 | 0.00 |
November | 0.104615E+10 | 0.716984E+09 | 0.733746E+09 | 0.490890E+09 | 0.242857E+09 | 0.00 | 0.00 |
December | 0.108183E+10 | 0.988549E+09 | 0.801172E+09 | 0.565893E+09 | 0.235279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129795E+11 | 0.534517E+10 | 0.678625E+10 | 0.306061E+10 | 0.372564E+10 | 0.00 | 0.00 |
Minimum of Months | 0.639059E+09 | 49833089.77 | 0.399265E+09 | 40435810.09 | 0.235279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131881E+10 | 0.988549E+09 | 0.860015E+09 | 0.612730E+09 | 0.377160E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115328E+10 | 0.652532E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.615586E+09 | 0.558034E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.836593E+09 | 0.563279E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.135868E+10 | 0.249037E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.142253E+10 | 0.146541E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.171238E+10 | 35288635.19 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.148315E+10 | 23510667.13 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.144557E+10 | 28911265.89 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.127718E+10 | 47865015.71 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.119745E+10 | 0.351640E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.101070E+10 | 0.558528E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.930136E+09 | 0.789139E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144432E+11 | 0.400431E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.615586E+09 | 23510667.13 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.171238E+10 | 0.789139E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.565313E+09 | 0.661334E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.327678E+09 | 0.568310E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.596030E+09 | 0.558709E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.116055E+10 | 0.242064E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.136900E+10 | 0.136238E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.174364E+10 | 31304092.67 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.147741E+10 | 21791342.36 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.133814E+10 | 27488425.89 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.106939E+10 | 46545008.87 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.777018E+09 | 0.351560E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.533131E+09 | 0.566776E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.401723E+09 | 0.812935E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113590E+11 | 0.402505E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.327678E+09 | 21791342.36 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.174364E+10 | 0.812935E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.992222E+09 | 0.342846E+09 | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.00 | 0.00 |
February | 0.495785E+09 | 0.294430E+09 | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.00 | 0.00 |
March | 0.497683E+09 | 0.295681E+09 | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.00 | 0.00 |
April | 0.584720E+09 | 0.123657E+09 | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.00 | 0.00 |
May | 0.489695E+09 | 70710604.92 | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.00 | 0.00 |
June | 0.583235E+09 | 15305827.81 | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.00 | 0.00 |
July | 0.595565E+09 | 10788022.55 | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.00 | 0.00 |
August | 0.646080E+09 | 13621517.36 | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.00 | 0.00 |
September | 0.697182E+09 | 23134003.86 | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.00 | 0.00 |
October | 0.828415E+09 | 0.181739E+09 | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.00 | 0.00 |
November | 0.816520E+09 | 0.292228E+09 | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.00 | 0.00 |
December | 0.881967E+09 | 0.415506E+09 | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810907E+10 | 0.207965E+10 | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.00 | 0.00 |
Minimum of Months | 0.489695E+09 | 10788022.55 | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.00 | 0.00 |
Maximum of Months | 0.992222E+09 | 0.415506E+09 | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220628E+09 | 0.211815E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.111553E+09 | 0.196349E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.441203E+09 | 0.183589E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.116275E+10 | 0.827654E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.170852E+10 | 0.515454E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.267644E+10 | 0.168662E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.239471E+10 | 0.130322E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.195564E+10 | 0.182356E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.155386E+10 | 0.282832E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.708903E+09 | 0.120504E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.228155E+09 | 0.186739E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.108540E+09 | 0.260312E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132709E+11 | 0.137004E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.108540E+09 | 0.130322E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.267644E+10 | 0.260312E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197746E+09 | 0.217474E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 95244521.34 | 0.202951E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.411309E+09 | 0.188839E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.113726E+10 | 0.851017E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.168029E+10 | 0.531383E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.264516E+10 | 0.176216E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.236214E+10 | 0.137902E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.192602E+10 | 0.193453E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.152804E+10 | 0.297512E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.685525E+09 | 0.124016E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.207698E+09 | 0.192131E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 92709689.07 | 0.267644E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129692E+11 | 0.141180E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 92709689.07 | 0.137902E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264516E+10 | 0.267644E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150089E+10 | 0.157556E+10 | 0.114407E+10 | 0.760168E+09 | 0.383905E+09 | 0.00 | 0.00 |
February | 0.944943E+09 | 0.148119E+10 | 0.886328E+09 | 0.501877E+09 | 0.384451E+09 | 0.00 | 0.00 |
March | 0.139178E+10 | 0.141765E+10 | 0.110956E+10 | 0.527249E+09 | 0.582308E+09 | 0.00 | 0.00 |
April | 0.250725E+10 | 0.693329E+09 | 0.139330E+10 | 0.738458E+09 | 0.654838E+09 | 0.00 | 0.00 |
May | 0.285298E+10 | 0.494709E+09 | 0.143380E+10 | 0.735158E+09 | 0.698645E+09 | 0.00 | 0.00 |
June | 0.346593E+10 | 0.196632E+09 | 0.143145E+10 | 0.772218E+09 | 0.659232E+09 | 0.00 | 0.00 |
July | 0.313160E+10 | 0.161603E+09 | 0.127145E+10 | 0.610754E+09 | 0.660695E+09 | 0.00 | 0.00 |
August | 0.296907E+10 | 0.216464E+09 | 0.122397E+10 | 0.607340E+09 | 0.616627E+09 | 0.00 | 0.00 |
September | 0.242083E+10 | 0.290966E+09 | 0.106442E+10 | 0.460908E+09 | 0.603516E+09 | 0.00 | 0.00 |
October | 0.201168E+10 | 0.950396E+09 | 0.120514E+10 | 0.719123E+09 | 0.486021E+09 | 0.00 | 0.00 |
November | 0.131722E+10 | 0.140005E+10 | 0.102901E+10 | 0.646691E+09 | 0.382315E+09 | 0.00 | 0.00 |
December | 0.118482E+10 | 0.187752E+10 | 0.103393E+10 | 0.672254E+09 | 0.361677E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.256990E+11 | 0.107561E+11 | 0.142264E+11 | 0.775220E+10 | 0.647423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.944943E+09 | 0.161603E+09 | 0.886328E+09 | 0.460908E+09 | 0.361677E+09 | 0.00 | 0.00 |
Maximum of Months | 0.346593E+10 | 0.187752E+10 | 0.143380E+10 | 0.772218E+09 | 0.698645E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261546E+10 | 0.145712E+10 | 0.178102E+10 | 0.131994E+10 | 0.461083E+09 | 0.00 | 0.00 |
February | 0.130896E+10 | 0.129387E+10 | 0.106374E+10 | 0.624266E+09 | 0.439472E+09 | 0.00 | 0.00 |
March | 0.146227E+10 | 0.130689E+10 | 0.104853E+10 | 0.432478E+09 | 0.616053E+09 | 0.00 | 0.00 |
April | 0.185425E+10 | 0.656634E+09 | 0.956085E+09 | 0.302004E+09 | 0.654081E+09 | 0.00 | 0.00 |
May | 0.174006E+10 | 0.429429E+09 | 0.780737E+09 | 0.110860E+09 | 0.669877E+09 | 0.00 | 0.00 |
June | 0.224655E+10 | 0.134308E+09 | 0.723175E+09 | 88503980.79 | 0.634671E+09 | 0.00 | 0.00 |
July | 0.215531E+10 | 99045820.94 | 0.706145E+09 | 70564670.40 | 0.635580E+09 | 0.00 | 0.00 |
August | 0.216669E+10 | 0.135674E+09 | 0.753612E+09 | 0.154975E+09 | 0.598637E+09 | 0.00 | 0.00 |
September | 0.220497E+10 | 0.211023E+09 | 0.933011E+09 | 0.308543E+09 | 0.624468E+09 | 0.00 | 0.00 |
October | 0.233610E+10 | 0.862165E+09 | 0.137280E+10 | 0.837901E+09 | 0.534895E+09 | 0.00 | 0.00 |
November | 0.216424E+10 | 0.126819E+10 | 0.150781E+10 | 0.105747E+10 | 0.450334E+09 | 0.00 | 0.00 |
December | 0.227824E+10 | 0.175676E+10 | 0.165898E+10 | 0.121905E+10 | 0.439939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.245331E+11 | 0.961112E+10 | 0.132856E+11 | 0.652656E+10 | 0.675909E+10 | 0.00 | 0.00 |
Minimum of Months | 0.130896E+10 | 99045820.94 | 0.706145E+09 | 70564670.40 | 0.439472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261546E+10 | 0.175676E+10 | 0.178102E+10 | 0.131994E+10 | 0.669877E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770446E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161676463.4 | 81.21 | 0.00 | 0.00 |
February | 0.696191E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145953084.4 | 81.21 | 0.00 | 0.00 |
March | 0.770301E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161563316.7 | 81.21 | 0.00 | 0.00 |
April | 0.746483E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156240984.7 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161420435.7 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203824.4 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408178.4 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408416.2 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156202028.0 | 81.21 | 0.00 | 0.00 |
October | 0.770295E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161516664.0 | 81.21 | 0.00 | 0.00 |
November | 0.744886E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156429224.3 | 81.21 | 0.00 | 0.00 |
December | 0.771262E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161756155.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907422E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190178E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696191E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161756155.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771262E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145953084.4 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.107704E+12 | -0.105973E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173153E+10 | 81.25 | 0.00 | 0.00 |
February | 0.966618E+11 | -0.950841E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157765E+10 | 81.25 | 0.00 | 0.00 |
March | 0.103759E+12 | -0.101997E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176277E+10 | 81.25 | 0.00 | 0.00 |
April | 0.954265E+11 | -0.937295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169703E+10 | 81.24 | 0.00 | 0.00 |
May | 0.930315E+11 | -0.912690E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176242E+10 | 81.25 | 0.00 | 0.00 |
June | 0.856445E+11 | -0.839465E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169792E+10 | 81.25 | 0.00 | 0.00 |
July | 0.862454E+11 | -0.845147E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173075E+10 | 81.23 | 0.00 | 0.00 |
August | 0.869201E+11 | -0.851923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172786E+10 | 81.24 | 0.00 | 0.00 |
September | 0.873918E+11 | -0.857220E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166976E+10 | 81.23 | 0.00 | 0.00 |
October | 0.954881E+11 | -0.937627E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172546E+10 | 81.24 | 0.00 | 0.00 |
November | 0.978035E+11 | -0.961336E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166989E+10 | 81.24 | 0.00 | 0.00 |
December | 0.105527E+12 | -0.103801E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172595E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.114160E+13 | -0.112112E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204790E+11 | 81.24 | 0.00 | 0.00 |
Minimum of Months | 0.856445E+11 | -0.105973E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176277E+10 | 81.23 | 0.00 | 0.00 |
Maximum of Months | 0.107704E+12 | -0.839465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157765E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.603958E+11 | -0.589259E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146991E+10 | 58.98 | 0.00 | 0.00 |
February | 0.540342E+11 | -0.526876E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134660E+10 | 58.98 | 0.00 | 0.00 |
March | 0.570601E+11 | -0.555472E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151294E+10 | 58.98 | 0.00 | 0.00 |
April | 0.508817E+11 | -0.494294E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145231E+10 | 58.98 | 0.00 | 0.00 |
May | 0.477766E+11 | -0.462640E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151262E+10 | 58.98 | 0.00 | 0.00 |
June | 0.424585E+11 | -0.410054E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145310E+10 | 58.97 | 0.00 | 0.00 |
July | 0.418740E+11 | -0.404049E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146911E+10 | 58.97 | 0.00 | 0.00 |
August | 0.424979E+11 | -0.410332E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146474E+10 | 58.97 | 0.00 | 0.00 |
September | 0.439341E+11 | -0.425195E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141460E+10 | 58.98 | 0.00 | 0.00 |
October | 0.498508E+11 | -0.483890E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146179E+10 | 58.98 | 0.00 | 0.00 |
November | 0.528993E+11 | -0.514847E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141464E+10 | 58.98 | 0.00 | 0.00 |
December | 0.585119E+11 | -0.570496E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146228E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.602175E+12 | -0.584740E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.174346E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.418740E+11 | -0.589259E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.151294E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.603958E+11 | -0.404049E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.134660E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.87 | 0.86 | 01-JAN-07:00 | 8303.49 | 39.08 | 307.00 | 292.67 | 1154.85 | 28.03 | 189.17 | 287.50 |
February | 241.00 | 0.87 | 0.86 | 01-FEB-07:49 | 4813.81 | 32.61 | 187.33 | 267.33 | 592.11 | 23.38 | 134.33 | 205.83 |
March | 344.33 | 0.88 | 0.86 | 01-MAR-07:00 | 1114.22 | 19.69 | 11.50 | 326.67 | 422.82 | 21.05 | 162.83 | 258.17 |
April | 380.33 | 0.88 | 0.86 | 01-APR-08:50 | 772.00 | 19.30 | 0.00 | 333.17 | 336.58 | 21.05 | 183.00 | 267.33 |
May | 403.17 | 0.88 | 0.86 | 01-MAY-08:09 | 622.65 | 19.09 | 0.00 | 359.67 | 275.63 | 20.87 | 100.83 | 235.67 |
June | 418.17 | 0.89 | 0.86 | 01-JUN-08:20 | 503.83 | 18.46 | 0.00 | 361.33 | 229.43 | 20.28 | 29.00 | 129.50 |
July | 399.50 | 0.88 | 0.86 | 01-JUL-09:30 | 620.48 | 18.53 | 0.00 | 362.67 | 264.72 | 20.32 | 90.00 | 195.83 |
August | 361.83 | 0.88 | 0.86 | 01-AUG-08:50 | 691.97 | 18.90 | 0.00 | 340.33 | 294.45 | 20.66 | 96.33 | 212.83 |
September | 350.17 | 0.88 | 0.86 | 01-SEP-07:30 | 1020.11 | 19.22 | 0.50 | 322.00 | 409.17 | 20.97 | 176.33 | 265.00 |
October | 348.00 | 0.87 | 0.86 | 01-OCT-07:49 | 2798.30 | 25.74 | 135.33 | 321.00 | 455.52 | 21.69 | 142.83 | 273.67 |
November | 288.50 | 0.87 | 0.86 | 01-NOV-08:09 | 7916.24 | 37.84 | 282.83 | 287.00 | 904.39 | 26.57 | 167.83 | 264.67 |
December | 290.67 | 0.87 | 0.86 | 01-DEC-07:40 | 7638.18 | 38.90 | 287.83 | 280.83 | 1321.43 | 28.77 | 185.33 | 273.33 |
Annual Sum or Average | 4135.50 | 0.88 | 2709.49 | 24.58 | 1212.33 | 3854.67 | 517.54 | 22.48 | 1657.83 | 2869.33 | ||
Minimum of Months | 241.00 | 0.87 | 0.86 | 503.83 | 18.46 | 0.00 | 267.33 | 229.43 | 20.28 | 29.00 | 129.50 | |
Maximum of Months | 418.17 | 0.89 | 0.86 | 8303.49 | 39.08 | 307.00 | 362.67 | 1321.43 | 28.77 | 189.17 | 287.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.26 | 0.22 | 01-JAN-07:49 | 8767.75 | 39.13 | 307.00 | 295.17 | 1616.31 | 27.50 | 165.00 | 292.67 |
February | 241.00 | 0.26 | 0.22 | 01-FEB-07:49 | 5159.06 | 32.56 | 187.67 | 273.17 | 936.90 | 23.24 | 132.00 | 249.00 |
March | 344.33 | 0.28 | 0.22 | 01-MAR-07:30 | 1351.04 | 20.13 | 23.50 | 338.67 | 660.27 | 21.32 | 186.83 | 306.83 |
April | 380.33 | 0.29 | 0.22 | 01-APR-07:30 | 967.61 | 19.83 | 22.67 | 345.00 | 531.77 | 21.38 | 219.33 | 321.00 |
May | 403.17 | 0.28 | 0.22 | 01-MAY-07:10 | 762.05 | 19.86 | 0.33 | 378.00 | 414.67 | 21.41 | 235.17 | 342.17 |
June | 418.17 | 0.29 | 0.22 | 01-JUN-06:00 | 619.25 | 19.33 | 0.00 | 383.33 | 344.55 | 20.92 | 140.67 | 345.33 |
July | 399.50 | 0.29 | 0.22 | 01-JUL-07:19 | 742.53 | 19.40 | 0.50 | 386.50 | 386.40 | 20.95 | 177.83 | 335.50 |
August | 361.83 | 0.28 | 0.22 | 01-AUG-07:40 | 846.46 | 19.63 | 2.17 | 355.67 | 448.53 | 21.17 | 172.83 | 315.17 |
September | 350.17 | 0.28 | 0.22 | 01-SEP-06:00 | 1229.75 | 19.79 | 24.33 | 332.33 | 618.23 | 21.34 | 206.67 | 305.17 |
October | 348.00 | 0.27 | 0.22 | 01-OCT-07:19 | 3119.56 | 25.77 | 140.17 | 326.50 | 775.82 | 21.62 | 140.33 | 308.67 |
November | 288.50 | 0.25 | 0.22 | 01-NOV-07:40 | 8331.06 | 37.91 | 283.33 | 292.50 | 1319.63 | 26.16 | 148.67 | 279.83 |
December | 290.67 | 0.24 | 0.22 | 01-DEC-07:30 | 8096.77 | 38.96 | 287.83 | 285.33 | 1778.08 | 28.28 | 168.33 | 278.00 |
Annual Sum or Average | 4135.50 | 0.27 | 2958.63 | 25.04 | 1279.50 | 3992.17 | 766.08 | 22.67 | 2093.67 | 3679.33 | ||
Minimum of Months | 241.00 | 0.24 | 0.22 | 619.25 | 19.33 | 0.00 | 273.17 | 344.55 | 20.92 | 132.00 | 249.00 | |
Maximum of Months | 418.17 | 0.29 | 0.22 | 8767.75 | 39.13 | 307.00 | 386.50 | 1778.08 | 28.28 | 235.17 | 345.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.73 | 0.60 | 01-JAN-11:50 | 266.73 | 13.67 | 0.00 | 219.17 | 147.98 | 17.31 | 0.00 | 34.67 |
February | 241.00 | 0.71 | 0.60 | 02-FEB-14:00 | 347.56 | 14.56 | 0.00 | 223.00 | 173.80 | 17.97 | 0.00 | 88.50 |
March | 344.33 | 0.67 | 0.60 | 01-MAR-08:20 | 409.52 | 15.79 | 0.00 | 314.67 | 197.02 | 19.05 | 0.00 | 174.67 |
April | 380.33 | 0.65 | 0.60 | 01-APR-09:20 | 459.69 | 16.79 | 0.00 | 344.00 | 234.93 | 20.05 | 24.83 | 265.83 |
May | 403.17 | 0.62 | 0.60 | 01-MAY-06:10 | 574.19 | 18.43 | 23.67 | 392.67 | 299.59 | 22.01 | 93.33 | 360.50 |
June | 418.17 | 0.62 | 0.60 | 01-JUN-05:49 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 595.61 | 19.20 | 48.00 | 401.17 | 308.99 | 23.02 | 116.67 | 330.83 |
August | 361.83 | 0.65 | 0.60 | 01-AUG-06:30 | 478.41 | 16.75 | 0.00 | 358.67 | 235.02 | 20.29 | 30.50 | 231.00 |
September | 350.17 | 0.65 | 0.60 | 01-SEP-07:10 | 474.65 | 16.29 | 0.00 | 325.83 | 224.71 | 19.50 | 1.83 | 227.83 |
October | 348.00 | 0.71 | 0.60 | 01-OCT-07:00 | 315.35 | 14.67 | 0.00 | 255.50 | 163.79 | 18.13 | 0.00 | 95.50 |
November | 288.50 | 0.72 | 0.60 | 01-NOV-08:50 | 298.70 | 14.24 | 0.00 | 235.17 | 156.71 | 17.83 | 0.00 | 46.83 |
December | 290.67 | 0.73 | 0.60 | 02-DEC-10:39 | 276.53 | 13.81 | 0.00 | 209.83 | 149.00 | 17.48 | 0.00 | 30.00 |
Annual Sum or Average | 4135.50 | 0.67 | 440.93 | 16.42 | 132.33 | 3681.33 | 226.89 | 19.95 | 399.17 | 2259.00 | ||
Minimum of Months | 241.00 | 0.62 | 0.60 | 266.73 | 13.67 | 0.00 | 209.83 | 147.98 | 17.31 | 0.00 | 30.00 | |
Maximum of Months | 418.17 | 0.73 | 0.60 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.73 | 0.60 | 01-JAN-11:50 | 266.73 | 13.67 | 0.00 | 219.17 | 147.98 | 17.31 | 0.00 | 34.67 |
February | 241.00 | 0.71 | 0.60 | 02-FEB-14:00 | 347.56 | 14.56 | 0.00 | 223.00 | 173.80 | 17.97 | 0.00 | 88.50 |
March | 344.33 | 0.67 | 0.60 | 01-MAR-08:20 | 409.52 | 15.79 | 0.00 | 314.67 | 197.02 | 19.05 | 0.00 | 174.67 |
April | 380.33 | 0.65 | 0.60 | 01-APR-09:20 | 459.69 | 16.79 | 0.00 | 344.00 | 234.93 | 20.05 | 24.83 | 265.83 |
May | 403.17 | 0.62 | 0.60 | 01-MAY-06:10 | 574.19 | 18.43 | 23.67 | 392.67 | 299.59 | 22.01 | 93.33 | 360.50 |
June | 418.17 | 0.62 | 0.60 | 01-JUN-05:49 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 595.61 | 19.20 | 48.00 | 401.17 | 308.99 | 23.02 | 116.67 | 330.83 |
August | 361.83 | 0.65 | 0.60 | 01-AUG-06:30 | 478.41 | 16.75 | 0.00 | 358.67 | 235.02 | 20.29 | 30.50 | 231.00 |
September | 350.17 | 0.65 | 0.60 | 01-SEP-07:10 | 474.65 | 16.29 | 0.00 | 325.83 | 224.71 | 19.50 | 1.83 | 227.83 |
October | 348.00 | 0.71 | 0.60 | 01-OCT-07:00 | 315.35 | 14.67 | 0.00 | 255.50 | 163.79 | 18.13 | 0.00 | 95.50 |
November | 288.50 | 0.72 | 0.60 | 01-NOV-08:50 | 298.70 | 14.24 | 0.00 | 235.17 | 156.71 | 17.83 | 0.00 | 46.83 |
December | 290.67 | 0.73 | 0.60 | 02-DEC-10:39 | 276.53 | 13.81 | 0.00 | 209.83 | 149.00 | 17.48 | 0.00 | 30.00 |
Annual Sum or Average | 4135.50 | 0.67 | 440.93 | 16.42 | 132.33 | 3681.33 | 226.89 | 19.95 | 399.17 | 2259.00 | ||
Minimum of Months | 241.00 | 0.62 | 0.60 | 266.73 | 13.67 | 0.00 | 209.83 | 147.98 | 17.31 | 0.00 | 30.00 | |
Maximum of Months | 418.17 | 0.73 | 0.60 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156251E+11 | 104781.93 | 12-JAN-06:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163348E+11 | 99342.00 | 27-FEB-06:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109662E+11 | 100133.85 | 26-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.818723E+09 | 89361.53 | 21-APR-04:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43716174.86 | 19623.03 | 01-MAY-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.543809E+10 | 97529.56 | 26-OCT-00:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111692E+11 | 107674.23 | 23-NOV-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183375E+11 | 107884.71 | 06-DEC-22:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183375E+11 | 107884.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 67112844.88 | 2354.49 | 12-JAN-07:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327172E+09 | 2171.88 | 27-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222463E+09 | 2432.08 | 25-MAR-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 595806.56 | 635.07 | 21-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24268276.98 | 1754.09 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57464618.76 | 1818.22 | 24-NOV-07:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318922E+09 | 1727.06 | 20-DEC-07:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327172E+09 | 2432.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14684400.16 | 965.10 | 01-JAN-09:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 201478.67 | 94.04 | 13-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2489433.20 | 332.55 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38067579.35 | 618.75 | 07-DEC-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55442891.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38067579.35 | 965.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 21444869.12 | 728.69 | 01-JAN-09:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9180217.43 | 546.31 | 13-FEB-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14805810.97 | 429.51 | 27-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275480.21 | 569.51 | 24-NOV-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82657360.85 | 629.92 | 20-DEC-07:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82657360.85 | 728.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110069E+09 | 7613.73 | 13-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55014216.26 | 7446.36 | 01-FEB-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33416861.95 | 7383.68 | 12-MAR-04:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5209413.90 | 7225.74 | 21-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 247554.82 | 412.59 | 01-MAY-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44610690.40 | 7304.51 | 12-OCT-03:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63138563.65 | 7642.18 | 07-NOV-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82845879.14 | 7654.16 | 29-DEC-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110069E+09 | 7654.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 232228.15 | 774.09 | 21-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26074440.75 | 1505.83 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 743297.30 | 1887.62 | 27-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 140179.25 | 467.26 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27190145.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26074440.75 | 1887.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43360818.07 | 4130.78 | 02-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89247181.87 | 6212.99 | 13-FEB-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95347689.23 | 5291.90 | 18-DEC-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95347689.23 | 6212.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 97978409.73 | 4519.36 | 12-JAN-07:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133465E+09 | 4480.50 | 09-FEB-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91934627.50 | 3750.49 | 30-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16870930.70 | 4163.84 | 24-NOV-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.495379E+09 | 4147.00 | 20-DEC-07:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495379E+09 | 4519.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1853542.64 | 2634.01 | 11-JAN-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 193660.89 | 325.83 | 01-FEB-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 317888.61 | 683.01 | 25-MAR-02:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54813.79 | 639.49 | 26-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 246179.90 | 670.69 | 05-NOV-02:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3981062.98 | 2688.63 | 29-DEC-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6647148.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3981062.98 | 2688.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 32774.01 | 0.46 | 10-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22476.64 | 0.46 | 09-FEB-21:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20623.00 | 0.46 | 21-MAR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42833.88 | 0.46 | 18-APR-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54567.07 | 0.46 | 26-MAY-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76852.81 | 0.46 | 01-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35169.58 | 0.46 | 12-JUL-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33281.72 | 0.46 | 29-AUG-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32824.97 | 0.46 | 06-SEP-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32909.51 | 0.46 | 08-OCT-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34884.42 | 0.47 | 14-NOV-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 341901.64 | 84.81 | 07-DEC-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 761099.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20623.00 | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 341901.64 | 84.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240994E+09 | 5146.66 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.568197E+09 | 5220.29 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337706E+09 | 5198.94 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6564784.14 | 4970.53 | 11-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3320037.26 | 5035.41 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1196235.09 | 3148.91 | 04-JUN-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2415587.08 | 3845.61 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2198039.35 | 3340.51 | 19-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3061750.95 | 3451.44 | 04-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41672966.91 | 5028.75 | 14-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176666E+09 | 5032.42 | 20-NOV-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.907354E+09 | 5207.36 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1196235.09 | 3148.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.907354E+09 | 5220.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.649201E+09 | 5276.53 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.957996E+09 | 5230.07 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.514170E+09 | 5234.33 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7736120.05 | 5035.90 | 23-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3209349.43 | 5033.51 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1052743.48 | 3763.69 | 04-JUN-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2340167.34 | 3780.26 | 02-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2272794.00 | 3185.10 | 19-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3706080.63 | 3677.34 | 30-SEP-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101405E+09 | 5143.67 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439793E+09 | 5237.50 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176837E+10 | 5334.85 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.445125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1052743.48 | 3185.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176837E+10 | 5334.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141144E+10 | 30351.45 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114270E+10 | 30065.13 | 03-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725211E+09 | 30012.46 | 27-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95688032.93 | 29714.26 | 01-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38789044.68 | 29701.48 | 01-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7535317.84 | 13350.22 | 05-JUN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11699602.12 | 12375.37 | 11-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15440761.30 | 29593.42 | 24-AUG-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27147748.46 | 27084.95 | 27-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167161E+09 | 29702.87 | 26-OCT-21:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.869219E+09 | 30209.67 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.470590E+10 | 30562.61 | 07-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.921793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7535317.84 | 12375.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.470590E+10 | 30562.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.295684E+09 | 4932.82 | 14-JAN-21:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.554033E+09 | 5097.76 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335482E+09 | 3919.14 | 23-MAR-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1063760.61 | 2874.78 | 04-APR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 463033.18 | 3182.04 | 26-MAY-08:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 190207.32 | 2084.47 | 03-AUG-19:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1059227.08 | 3256.97 | 03-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36524507.65 | 4128.52 | 26-OCT-21:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221612E+09 | 4609.99 | 05-NOV-21:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.918213E+09 | 5027.36 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.918213E+09 | 5097.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.715506E+09 | 5084.68 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.849518E+09 | 5106.28 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.485332E+09 | 4401.52 | 12-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3072168.31 | 4169.27 | 21-APR-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 510480.84 | 3215.23 | 26-MAY-08:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 207520.46 | 2026.17 | 03-AUG-19:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1008033.34 | 3221.67 | 03-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91575039.90 | 4273.86 | 25-OCT-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.498555E+09 | 5030.07 | 23-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167631E+10 | 5124.63 | 07-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167631E+10 | 5124.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152444E+09 | 1558.73 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277089E+09 | 1573.69 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168307E+09 | 1569.72 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2565722.44 | 1322.00 | 24-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1737467.66 | 1377.54 | 14-MAY-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 135477.67 | 491.93 | 24-JUN-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 461202.39 | 594.50 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 624107.38 | 743.97 | 05-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1024063.47 | 1233.26 | 22-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38205741.95 | 1535.81 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118093E+09 | 1544.66 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413554E+09 | 1578.23 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 135477.67 | 491.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413554E+09 | 1578.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332321E+09 | 1587.52 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422145E+09 | 1575.99 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237063E+09 | 1579.37 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3630470.42 | 1359.84 | 18-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1546236.97 | 1377.09 | 27-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 137473.22 | 715.11 | 24-JUN-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471108.07 | 800.02 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 676210.96 | 770.81 | 05-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1106240.50 | 1167.22 | 15-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74929615.53 | 1559.38 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237837E+09 | 1585.08 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718136E+09 | 1587.46 | 18-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 137473.22 | 715.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.718136E+09 | 1587.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 86660807.85 | 4823.44 | 31-JAN-22:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361699E+09 | 7337.06 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304242E+09 | 7311.92 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7178181.62 | 6471.23 | 08-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6983372.44 | 6717.47 | 23-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3417876.95 | 3682.06 | 12-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6880278.15 | 4617.41 | 24-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5226093.33 | 4673.41 | 08-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3593182.65 | 5182.25 | 03-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19208304.73 | 4637.89 | 27-OCT-19:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89002248.62 | 5097.37 | 11-NOV-09:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.482234E+09 | 4809.13 | 02-DEC-22:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3417876.95 | 3682.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.482234E+09 | 7337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107127E+12 | 0.106705E+12 | 182317.52 | 31-JAN-16:30 | 182317.52 | 0.05 |
February | 0.00 | 0.00 | 0.258547E+11 | 0.258307E+11 | 104697.61 | 18-FEB-14:00 | 104697.61 | 0.17 |
March | 0.00 | 0.00 | 0.116108E+12 | 0.116108E+12 | 202958.26 | 20-MAR-18:10 | 202958.26 | 0.13 |
April | 0.00 | 0.00 | 0.320815E+12 | 0.320815E+12 | 260823.15 | 14-APR-18:10 | 260823.15 | 0.05 |
May | 0.00 | 0.00 | 0.417603E+12 | 0.417603E+12 | 272771.71 | 31-MAY-18:20 | 272771.71 | 0.02 |
June | 0.00 | 0.00 | 0.534011E+12 | 0.533129E+12 | 345256.04 | 17-JUN-17:17 | 282612.79 | 0.27 |
July | 0.00 | 0.00 | 0.620124E+12 | 0.542711E+12 | 415516.76 | 13-JUL-21:00 | 244305.96 | 0.80 |
August | 0.00 | 0.00 | 0.604339E+12 | 0.534345E+12 | 447182.11 | 18-AUG-22:00 | 209348.10 | 0.86 |
September | 0.00 | 0.00 | 0.555024E+12 | 0.479022E+12 | 476421.37 | 10-SEP-20:40 | 210601.21 | 0.88 |
October | 0.00 | 0.00 | 0.282703E+12 | 0.274634E+12 | 342867.84 | 02-OCT-20:00 | 256155.04 | 0.30 |
November | 0.00 | 0.00 | 0.122584E+12 | 0.108767E+12 | 203902.02 | 01-NOV-18:10 | 203902.02 | 0.25 |
December | 0.00 | 0.00 | 0.569862E+11 | 0.569862E+11 | 158976.86 | 22-DEC-16:03 | 158976.86 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.376328E+13 | 0.351666E+13 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.258547E+11 | 0.258307E+11 | 104697.61 | 104697.61 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.620124E+12 | 0.542711E+12 | 476421.37 | 282612.79 | 0.88 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.198678E+11 | 0.197345E+11 | 28050.24 | 31-JAN-16:02 | 28050.24 | 0.04 |
February | 0.00 | 0.00 | 0.520636E+10 | 0.520636E+10 | 23246.09 | 18-FEB-14:00 | 23246.09 | 0.13 |
March | 0.00 | 0.00 | 0.213418E+11 | 0.213418E+11 | 28577.87 | 16-MAR-15:02 | 28577.87 | 0.11 |
April | 0.00 | 0.00 | 0.508091E+11 | 0.508091E+11 | 32710.68 | 14-APR-15:01 | 32710.68 | 0.02 |
May | 0.00 | 0.00 | 0.644422E+11 | 0.644422E+11 | 33359.99 | 31-MAY-17:40 | 33359.99 | 0.01 |
June | 0.00 | 0.00 | 0.750470E+11 | 0.749599E+11 | 40819.70 | 17-JUN-16:00 | 34474.48 | 0.11 |
July | 0.00 | 0.00 | 0.881593E+11 | 0.767338E+11 | 53022.95 | 27-JUL-07:10 | 26219.83 | 0.78 |
August | 0.00 | 0.00 | 0.878394E+11 | 0.758079E+11 | 56729.28 | 05-AUG-08:20 | 26103.45 | 0.85 |
September | 0.00 | 0.00 | 0.825085E+11 | 0.694566E+11 | 60390.84 | 04-SEP-08:20 | 24732.99 | 0.82 |
October | 0.00 | 0.00 | 0.444327E+11 | 0.429241E+11 | 48769.00 | 03-OCT-07:00 | 25765.70 | 0.27 |
November | 0.00 | 0.00 | 0.228037E+11 | 0.196608E+11 | 44169.39 | 12-NOV-14:30 | 21149.34 | 0.24 |
December | 0.00 | 0.00 | 0.111667E+11 | 0.111667E+11 | 26242.78 | 25-DEC-16:00 | 26242.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.573625E+12 | 0.532244E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.520636E+10 | 0.520636E+10 | 23246.09 | 21149.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.881593E+11 | 0.767338E+11 | 60390.84 | 34474.48 | 0.85 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.244179E+10 | 0.216954E+10 | 18453.15 | 08-JAN-20:12 | 12775.89 | 0.12 |
February | 0.00 | 0.00 | 0.771818E+09 | 0.488945E+09 | 18074.47 | 01-FEB-17:11 | 18074.47 | 0.19 |
March | 0.00 | 0.00 | 0.168173E+10 | 0.119659E+10 | 17247.54 | 23-MAR-21:11 | 17247.54 | 0.25 |
April | 0.00 | 0.00 | 0.764645E+10 | 0.739679E+10 | 17779.32 | 06-APR-21:51 | 17779.32 | 0.09 |
May | 0.00 | 0.00 | 0.941312E+10 | 0.934154E+10 | 17589.18 | 20-MAY-08:61 | 17589.18 | 0.02 |
June | 0.00 | 0.00 | 0.126525E+11 | 0.117393E+11 | 17823.91 | 16-JUN-06:41 | 17823.91 | 0.33 |
July | 0.00 | 0.00 | 0.123995E+11 | 0.898585E+10 | 19293.58 | 27-JUL-08:11 | 13921.61 | 0.76 |
August | 0.00 | 0.00 | 0.120498E+11 | 0.851087E+10 | 20092.79 | 04-AUG-21:51 | 14807.27 | 0.80 |
September | 0.00 | 0.00 | 0.103157E+11 | 0.691159E+10 | 21810.19 | 10-SEP-21:51 | 14593.60 | 0.82 |
October | 0.00 | 0.00 | 0.590752E+10 | 0.473159E+10 | 19115.25 | 03-OCT-08:61 | 14718.98 | 0.33 |
November | 0.00 | 0.00 | 0.258746E+10 | 0.200001E+10 | 19537.47 | 11-NOV-22:52 | 12752.12 | 0.23 |
December | 0.00 | 0.00 | 0.114059E+10 | 0.113670E+10 | 17689.72 | 14-DEC-17:01 | 17689.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.790080E+11 | 0.646093E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.771818E+09 | 0.488945E+09 | 17247.54 | 12752.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126525E+11 | 0.117393E+11 | 21810.19 | 18074.47 | 0.82 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.763718E+09 | 0.677089E+09 | 16928.25 | 08-JAN-16:01 | 14747.03 | 0.06 |
February | 0.00 | 0.00 | 0.224723E+09 | 0.148355E+09 | 16627.02 | 01-FEB-17:11 | 16627.02 | 0.08 |
March | 0.00 | 0.00 | 0.107361E+10 | 0.759694E+09 | 16718.12 | 23-MAR-21:11 | 16718.12 | 0.19 |
April | 0.00 | 0.00 | 0.664935E+10 | 0.640981E+10 | 17487.47 | 26-APR-21:51 | 17487.47 | 0.08 |
May | 0.00 | 0.00 | 0.913188E+10 | 0.906060E+10 | 17587.96 | 20-MAY-08:61 | 17587.96 | 0.02 |
June | 0.00 | 0.00 | 0.127978E+11 | 0.118907E+11 | 18024.19 | 10-JUN-07:31 | 18024.19 | 0.33 |
July | 0.00 | 0.00 | 0.123478E+11 | 0.896681E+10 | 19197.54 | 27-JUL-08:11 | 13978.67 | 0.76 |
August | 0.00 | 0.00 | 0.114297E+11 | 0.794854E+10 | 20146.84 | 28-AUG-18:31 | 15007.37 | 0.79 |
September | 0.00 | 0.00 | 0.922112E+10 | 0.591954E+10 | 21415.51 | 10-SEP-21:51 | 14325.52 | 0.81 |
October | 0.00 | 0.00 | 0.424932E+10 | 0.321490E+10 | 18731.56 | 03-OCT-08:61 | 14353.98 | 0.30 |
November | 0.00 | 0.00 | 0.108251E+10 | 0.750919E+09 | 19238.48 | 11-NOV-22:52 | 12476.68 | 0.16 |
December | 0.00 | 0.00 | 0.223835E+09 | 0.223770E+09 | 16560.68 | 27-DEC-16:01 | 16560.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.691954E+11 | 0.559707E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.223835E+09 | 0.148355E+09 | 16560.68 | 12476.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127978E+11 | 0.118907E+11 | 21415.51 | 18024.19 | 0.81 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.349990E+11 | 0.337504E+11 | 44243.94 | 14-JAN-13:40 | 44243.94 | 0.07 |
February | 0.00 | 0.00 | 0.102901E+11 | 0.864185E+10 | 34150.63 | 01-FEB-14:30 | 34150.63 | 0.13 |
March | 0.00 | 0.00 | 0.972669E+10 | 0.855289E+10 | 29209.87 | 18-MAR-13:40 | 22269.97 | 0.08 |
April | 0.00 | 0.00 | 0.294415E+11 | 0.292288E+11 | 30450.28 | 14-APR-13:40 | 30450.28 | 0.01 |
May | 0.00 | 0.00 | 0.288836E+11 | 0.288715E+11 | 25269.67 | 09-MAY-17:12 | 25269.67 | 0.00 |
June | 0.00 | 0.00 | 0.421973E+11 | 0.397816E+11 | 34484.25 | 17-JUN-19:10 | 24810.22 | 0.11 |
July | 0.00 | 0.00 | 0.444588E+11 | 0.261608E+11 | 33913.46 | 21-JUL-20:20 | 24895.78 | 0.76 |
August | 0.00 | 0.00 | 0.476579E+11 | 0.281020E+11 | 38861.38 | 28-AUG-12:30 | 30537.27 | 0.83 |
September | 0.00 | 0.00 | 0.482183E+11 | 0.308877E+11 | 42008.70 | 28-SEP-13:30 | 42008.70 | 0.79 |
October | 0.00 | 0.00 | 0.394231E+11 | 0.340280E+11 | 44935.79 | 02-OCT-12:40 | 41626.89 | 0.28 |
November | 0.00 | 0.00 | 0.282151E+11 | 0.254329E+11 | 46510.87 | 20-NOV-14:30 | 46510.87 | 0.16 |
December | 0.00 | 0.00 | 0.251000E+11 | 0.250053E+11 | 43873.77 | 25-DEC-13:30 | 43873.77 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.388611E+12 | 0.318444E+12 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.972669E+10 | 0.855289E+10 | 25269.67 | 22269.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.482183E+11 | 0.397816E+11 | 46510.87 | 46510.87 | 0.83 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.696330E+10 | 0.572531E+10 | 118185.18 | 08-JAN-20:12 | 83606.11 | 0.10 |
February | 0.00 | 0.00 | 0.641823E+10 | 0.266909E+10 | 107967.58 | 18-FEB-19:12 | 86811.89 | 0.34 |
March | 0.00 | 0.00 | 0.121340E+11 | 0.817614E+10 | 106959.05 | 23-MAR-21:11 | 106959.05 | 0.27 |
April | 0.00 | 0.00 | 0.356544E+11 | 0.343647E+11 | 109002.21 | 26-APR-21:51 | 109002.21 | 0.07 |
May | 0.00 | 0.00 | 0.505852E+11 | 0.501903E+11 | 110593.48 | 20-MAY-08:61 | 110593.48 | 0.02 |
June | 0.00 | 0.00 | 0.714484E+11 | 0.667749E+11 | 113080.27 | 19-JUN-07:01 | 113080.27 | 0.28 |
July | 0.00 | 0.00 | 0.759793E+11 | 0.559519E+11 | 118385.76 | 27-JUL-08:11 | 90642.14 | 0.65 |
August | 0.00 | 0.00 | 0.682470E+11 | 0.474723E+11 | 126732.58 | 28-AUG-18:31 | 91705.82 | 0.66 |
September | 0.00 | 0.00 | 0.574238E+11 | 0.380304E+11 | 134706.83 | 10-SEP-21:51 | 89837.33 | 0.65 |
October | 0.00 | 0.00 | 0.275837E+11 | 0.212073E+11 | 115410.06 | 03-OCT-08:61 | 92096.15 | 0.25 |
November | 0.00 | 0.00 | 0.100031E+11 | 0.629661E+10 | 125604.93 | 12-NOV-22:52 | 81188.76 | 0.19 |
December | 0.00 | 0.00 | 0.328696E+10 | 0.321716E+10 | 102583.69 | 26-DEC-21:31 | 102583.69 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.425727E+12 | 0.340076E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.328696E+10 | 0.266909E+10 | 102583.69 | 81188.76 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.759793E+11 | 0.667749E+11 | 134706.83 | 113080.27 | 0.66 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.242675E+10 | 0.217024E+10 | 16258.60 | 08-JAN-20:12 | 11212.09 | 0.13 |
February | 0.00 | 0.00 | 0.110479E+10 | 0.686261E+09 | 15360.94 | 18-FEB-09:02 | 12212.20 | 0.24 |
March | 0.00 | 0.00 | 0.195640E+10 | 0.141473E+10 | 15142.12 | 16-MAR-08:51 | 15142.12 | 0.28 |
April | 0.00 | 0.00 | 0.761919E+10 | 0.738330E+10 | 17070.41 | 12-APR-08:51 | 17070.41 | 0.09 |
May | 0.00 | 0.00 | 0.948417E+10 | 0.941994E+10 | 17068.99 | 31-MAY-07:41 | 17068.99 | 0.03 |
June | 0.00 | 0.00 | 0.128943E+11 | 0.120830E+11 | 17070.49 | 22-JUN-07:11 | 17070.49 | 0.34 |
July | 0.00 | 0.00 | 0.132381E+11 | 0.988358E+10 | 18613.05 | 27-JUL-08:11 | 14496.90 | 0.78 |
August | 0.00 | 0.00 | 0.127315E+11 | 0.928528E+10 | 18375.82 | 05-AUG-08:51 | 13721.88 | 0.81 |
September | 0.00 | 0.00 | 0.106401E+11 | 0.734452E+10 | 19636.88 | 04-SEP-08:51 | 13844.39 | 0.84 |
October | 0.00 | 0.00 | 0.618827E+10 | 0.502117E+10 | 17805.91 | 03-OCT-08:61 | 14429.71 | 0.35 |
November | 0.00 | 0.00 | 0.243034E+10 | 0.193054E+10 | 17128.99 | 11-NOV-22:52 | 11101.11 | 0.21 |
December | 0.00 | 0.00 | 0.126561E+10 | 0.125521E+10 | 15767.21 | 25-DEC-09:51 | 15767.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.819796E+11 | 0.678777E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.110479E+10 | 0.686261E+09 | 15142.12 | 11101.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132381E+11 | 0.120830E+11 | 19636.88 | 17070.49 | 0.84 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.795310E+09 | 0.675989E+09 | 14899.04 | 27-JAN-09:51 | 14899.04 | 0.07 |
February | 0.00 | 0.00 | 0.442074E+09 | 0.217079E+09 | 15259.32 | 20-FEB-09:02 | 12875.43 | 0.14 |
March | 0.00 | 0.00 | 0.127216E+10 | 0.897626E+09 | 14804.49 | 16-MAR-08:51 | 14804.49 | 0.22 |
April | 0.00 | 0.00 | 0.657703E+10 | 0.634650E+10 | 16965.86 | 12-APR-08:51 | 16965.86 | 0.09 |
May | 0.00 | 0.00 | 0.919517E+10 | 0.913041E+10 | 16965.14 | 31-MAY-07:41 | 16965.14 | 0.03 |
June | 0.00 | 0.00 | 0.130370E+11 | 0.122427E+11 | 16967.11 | 19-JUN-07:01 | 16967.11 | 0.35 |
July | 0.00 | 0.00 | 0.131776E+11 | 0.983359E+10 | 18430.39 | 27-JUL-08:11 | 14452.07 | 0.78 |
August | 0.00 | 0.00 | 0.121083E+11 | 0.862814E+10 | 18201.87 | 05-AUG-08:51 | 13696.40 | 0.81 |
September | 0.00 | 0.00 | 0.954152E+10 | 0.629644E+10 | 19475.39 | 04-SEP-08:51 | 13786.17 | 0.83 |
October | 0.00 | 0.00 | 0.444102E+10 | 0.339668E+10 | 17481.75 | 03-OCT-08:61 | 14123.75 | 0.32 |
November | 0.00 | 0.00 | 0.995126E+09 | 0.694173E+09 | 16864.19 | 11-NOV-22:52 | 10860.14 | 0.15 |
December | 0.00 | 0.00 | 0.293309E+09 | 0.290153E+09 | 14525.92 | 25-DEC-09:51 | 14525.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.718755E+11 | 0.586494E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.293309E+09 | 0.217079E+09 | 14525.92 | 10860.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131776E+11 | 0.122427E+11 | 19475.39 | 16967.11 | 0.83 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.532184E+09 | 0.480519E+09 | 4479.80 | 08-JAN-16:01 | 3981.40 | 0.10 |
February | 0.00 | 0.00 | 0.157833E+09 | 0.105308E+09 | 4834.62 | 01-FEB-17:11 | 4834.62 | 0.14 |
March | 0.00 | 0.00 | 0.388257E+09 | 0.290342E+09 | 4590.67 | 23-MAR-21:11 | 4590.67 | 0.20 |
April | 0.00 | 0.00 | 0.195028E+10 | 0.188750E+10 | 4724.88 | 06-APR-21:51 | 4724.88 | 0.09 |
May | 0.00 | 0.00 | 0.242289E+10 | 0.240450E+10 | 4604.95 | 08-MAY-08:61 | 4604.95 | 0.02 |
June | 0.00 | 0.00 | 0.334687E+10 | 0.309631E+10 | 4647.26 | 16-JUN-06:41 | 4647.26 | 0.33 |
July | 0.00 | 0.00 | 0.325090E+10 | 0.234214E+10 | 5264.27 | 27-JUL-08:11 | 3530.29 | 0.76 |
August | 0.00 | 0.00 | 0.314929E+10 | 0.221516E+10 | 5428.79 | 05-AUG-08:51 | 3673.16 | 0.80 |
September | 0.00 | 0.00 | 0.263058E+10 | 0.174212E+10 | 5897.41 | 10-SEP-21:51 | 3788.04 | 0.82 |
October | 0.00 | 0.00 | 0.140934E+10 | 0.111821E+10 | 5211.43 | 03-OCT-08:61 | 3701.73 | 0.32 |
November | 0.00 | 0.00 | 0.562012E+09 | 0.442977E+09 | 5275.65 | 11-NOV-22:52 | 3230.64 | 0.18 |
December | 0.00 | 0.00 | 0.240170E+09 | 0.239469E+09 | 4760.44 | 14-DEC-17:01 | 4760.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200406E+11 | 0.163645E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.157833E+09 | 0.105308E+09 | 4479.80 | 3230.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.334687E+10 | 0.309631E+10 | 5897.41 | 4834.62 | 0.82 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.150257E+09 | 0.139584E+09 | 4460.81 | 08-JAN-16:01 | 3858.68 | 0.04 |
February | 0.00 | 0.00 | 39666461.21 | 28538158.05 | 4389.92 | 21-FEB-16:01 | 4389.92 | 0.04 |
March | 0.00 | 0.00 | 0.238927E+09 | 0.179875E+09 | 4420.79 | 23-MAR-21:11 | 4420.79 | 0.14 |
April | 0.00 | 0.00 | 0.169003E+10 | 0.163011E+10 | 4611.81 | 06-APR-21:51 | 4611.81 | 0.09 |
May | 0.00 | 0.00 | 0.235152E+10 | 0.233300E+10 | 4582.33 | 20-MAY-08:61 | 4582.33 | 0.02 |
June | 0.00 | 0.00 | 0.338566E+10 | 0.313669E+10 | 4681.66 | 16-JUN-06:41 | 4681.66 | 0.33 |
July | 0.00 | 0.00 | 0.323784E+10 | 0.233591E+10 | 5228.82 | 27-JUL-08:11 | 3548.37 | 0.76 |
August | 0.00 | 0.00 | 0.298904E+10 | 0.206216E+10 | 5430.18 | 28-AUG-18:31 | 3885.68 | 0.80 |
September | 0.00 | 0.00 | 0.234693E+10 | 0.147690E+10 | 5790.65 | 10-SEP-21:51 | 3712.89 | 0.81 |
October | 0.00 | 0.00 | 0.995269E+09 | 0.741902E+09 | 5113.45 | 03-OCT-08:61 | 3600.21 | 0.28 |
November | 0.00 | 0.00 | 0.208447E+09 | 0.150926E+09 | 5191.94 | 11-NOV-22:52 | 3142.34 | 0.11 |
December | 0.00 | 0.00 | 40984408.20 | 40947497.02 | 4384.99 | 25-DEC-16:02 | 4384.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.176746E+11 | 0.142566E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 39666461.21 | 28538158.05 | 4384.99 | 3142.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.338566E+10 | 0.313669E+10 | 5790.65 | 4681.66 | 0.81 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.837328E+10 | 0.770736E+10 | 22708.08 | 08-JAN-20:12 | 16254.42 | 0.22 |
February | 0.00 | 0.00 | 0.347311E+10 | 0.228579E+10 | 22090.53 | 01-FEB-17:11 | 22090.53 | 0.43 |
March | 0.00 | 0.00 | 0.369234E+10 | 0.265735E+10 | 20745.45 | 22-MAR-21:21 | 20745.45 | 0.35 |
April | 0.00 | 0.00 | 0.959090E+10 | 0.921607E+10 | 20728.86 | 07-APR-21:51 | 20728.86 | 0.11 |
May | 0.00 | 0.00 | 0.102214E+11 | 0.101183E+11 | 20480.71 | 20-MAY-08:61 | 20480.71 | 0.03 |
June | 0.00 | 0.00 | 0.138061E+11 | 0.124593E+11 | 20500.86 | 16-JUN-06:41 | 20500.86 | 0.38 |
July | 0.00 | 0.00 | 0.151808E+11 | 0.108162E+11 | 22612.77 | 27-JUL-08:11 | 16344.81 | 0.75 |
August | 0.00 | 0.00 | 0.156125E+11 | 0.111414E+11 | 24238.57 | 28-AUG-18:31 | 17976.39 | 0.80 |
September | 0.00 | 0.00 | 0.148299E+11 | 0.104520E+11 | 26468.12 | 10-SEP-21:51 | 17377.20 | 0.83 |
October | 0.00 | 0.00 | 0.107253E+11 | 0.899081E+10 | 22807.52 | 03-OCT-08:61 | 17729.42 | 0.38 |
November | 0.00 | 0.00 | 0.737242E+10 | 0.632910E+10 | 23583.10 | 11-NOV-22:52 | 15647.95 | 0.26 |
December | 0.00 | 0.00 | 0.621482E+10 | 0.617413E+10 | 22131.20 | 26-DEC-21:31 | 22131.20 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.119093E+12 | 0.983477E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.347311E+10 | 0.228579E+10 | 20480.71 | 15647.95 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.156125E+11 | 0.124593E+11 | 26468.12 | 22131.20 | 0.83 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7334.46 | 110182.52 | 02-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9033.71 | 106830.65 | 02-FEB-03:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5328.64 | 104907.50 | 27-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 361.55 | 76911.88 | 21-APR-04:31 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 38.35 | 50965.36 | 01-MAY-08:53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 6.06 | 13418.02 | 05-JUN-08:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9.24 | 12321.75 | 18-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 9.45 | 25895.03 | 29-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 15.72 | 20560.29 | 29-SEP-08:24 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2246.26 | 92579.44 | 25-OCT-05:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 5320.41 | 120156.83 | 23-NOV-21:55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11446.95 | 125897.39 | 06-DEC-22:05 |
Annual Sum or Average | 0.00 | 3405.13 | ||||
Minimum of Months | 0.00 | 0.00 | 6.06 | 12321.75 | ||
Maximum of Months | 0.00 | 0.00 | 11446.95 | 125897.39 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 71915.96 | 407788.29 | 31-JAN-19:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 24936.81 | 264301.25 | 18-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66225.78 | 437656.48 | 15-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 187804.88 | 508046.30 | 14-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 232355.16 | 517611.73 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 309865.57 | 623887.08 | 30-JUN-18:07 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 339896.51 | 658407.76 | 13-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 331163.82 | 637457.11 | 28-AUG-18:33 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 312996.03 | 772395.16 | 10-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 163021.25 | 565658.58 | 01-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 79763.34 | 426853.17 | 01-NOV-18:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 42227.48 | 358968.18 | 25-DEC-16:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 180992.08 | 0.00 | ||||
Minimum of Months | 24936.81 | 264301.25 | 0.00 | 0.00 | ||
Maximum of Months | 339896.51 | 772395.16 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 23524.86 | 58255.45 | 26-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23303.11 | 56499.39 | 05-FEB-08:51 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22284.20 | 52922.74 | 13-MAR-06:31 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20643.65 | 45416.13 | 07-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 18859.26 | 39432.33 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17412.99 | 35892.44 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16681.00 | 33478.06 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16914.26 | 34390.22 | 30-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 17995.10 | 37206.88 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19633.17 | 47587.05 | 12-OCT-06:21 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21403.13 | 53150.95 | 23-NOV-08:31 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22816.47 | 56052.47 | 20-DEC-07:01 |
Annual Sum or Average | 0.00 | 20104.77 | ||||
Minimum of Months | 0.00 | 0.00 | 16681.00 | 33478.06 | ||
Maximum of Months | 0.00 | 0.00 | 23524.86 | 58255.45 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.97 | 2194.93 | 01-JAN-00:10 | 0.97 |
February | 0.530997E+10 | 0.96 | 2194.93 | 01-FEB-00:10 | 0.97 |
March | 0.587890E+10 | 0.96 | 2194.93 | 01-MAR-00:10 | 0.96 |
April | 0.568926E+10 | 0.97 | 2194.93 | 01-APR-00:10 | 0.97 |
May | 0.587890E+10 | 0.97 | 2194.93 | 01-MAY-00:05 | 0.97 |
June | 0.568926E+10 | 0.96 | 2194.93 | 01-JUN-00:05 | 0.97 |
July | 0.587890E+10 | 0.96 | 2194.93 | 01-JUL-00:10 | 0.96 |
August | 0.587890E+10 | 0.96 | 2194.93 | 01-AUG-00:05 | 0.96 |
September | 0.568926E+10 | 0.96 | 2194.93 | 01-SEP-00:05 | 0.96 |
October | 0.587890E+10 | 0.96 | 2194.93 | 01-OCT-00:10 | 0.96 |
November | 0.568926E+10 | 0.96 | 2194.93 | 01-NOV-00:05 | 0.96 |
December | 0.587890E+10 | 0.97 | 2194.93 | 01-DEC-00:10 | 0.97 |
Annual Sum or Average | 0.692193E+11 | 0.96 | |||
Minimum of Months | 0.530997E+10 | 0.96 | 2194.93 | 0.96 | |
Maximum of Months | 0.587890E+10 | 0.97 | 2194.93 | 0.97 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358500E+11 | 0.85 | 44878.25 | 21-JAN-05:37 | 1.75 |
February | 0.303501E+11 | 0.82 | 36664.09 | 02-FEB-05:15 | 1.55 |
March | 0.345520E+11 | 0.84 | 36141.33 | 02-MAR-02:10 | 1.53 |
April | 0.378445E+11 | 0.89 | 32943.96 | 14-APR-21:10 | 1.45 |
May | 0.408442E+11 | 0.92 | 33005.43 | 09-MAY-21:10 | 1.45 |
June | 0.446243E+11 | 0.98 | 36875.84 | 29-JUN-21:10 | 1.55 |
July | 0.458533E+11 | 0.97 | 39198.75 | 21-JUL-21:10 | 1.60 |
August | 0.466216E+11 | 0.97 | 40330.84 | 25-AUG-21:10 | 1.65 |
September | 0.452283E+11 | 0.98 | 42066.53 | 08-SEP-21:10 | 1.67 |
October | 0.417540E+11 | 0.92 | 44878.25 | 26-OCT-04:10 | 1.76 |
November | 0.367678E+11 | 0.88 | 45682.18 | 23-NOV-21:45 | 1.79 |
December | 0.355972E+11 | 0.85 | 45608.90 | 19-DEC-22:55 | 1.78 |
Annual Sum or Average | 0.475887E+12 | 0.91 | |||
Minimum of Months | 0.303501E+11 | 0.82 | 32943.96 | 1.45 | |
Maximum of Months | 0.466216E+11 | 0.98 | 45682.18 | 1.79 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.29 | 76.61 | 01-JAN-00:10 | 0.29 |
February | 0.185347E+09 | 0.29 | 76.61 | 01-FEB-00:10 | 0.29 |
March | 0.205205E+09 | 0.29 | 76.61 | 01-MAR-00:10 | 0.29 |
April | 0.198586E+09 | 0.29 | 76.61 | 01-APR-00:10 | 0.29 |
May | 0.205205E+09 | 0.29 | 76.61 | 01-MAY-00:05 | 0.29 |
June | 0.198586E+09 | 0.29 | 76.61 | 01-JUN-00:05 | 0.29 |
July | 0.205205E+09 | 0.29 | 76.61 | 01-JUL-00:10 | 0.29 |
August | 0.205205E+09 | 0.29 | 76.61 | 01-AUG-00:05 | 0.29 |
September | 0.198586E+09 | 0.29 | 76.61 | 01-SEP-00:05 | 0.29 |
October | 0.205205E+09 | 0.29 | 76.61 | 01-OCT-00:10 | 0.29 |
November | 0.198586E+09 | 0.29 | 76.61 | 01-NOV-00:05 | 0.29 |
December | 0.205205E+09 | 0.29 | 76.61 | 01-DEC-00:10 | 0.29 |
Annual Sum or Average | 0.241613E+10 | 0.29 | |||
Minimum of Months | 0.185347E+09 | 0.29 | 76.61 | 0.29 | |
Maximum of Months | 0.205205E+09 | 0.29 | 76.61 | 0.29 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.21 | 612.92 | 01-JAN-07:10 | 0.29 |
February | 0.105030E+10 | 0.21 | 612.92 | 01-FEB-07:05 | 0.29 |
March | 0.116283E+10 | 0.21 | 612.92 | 01-MAR-07:05 | 0.29 |
April | 0.112532E+10 | 0.21 | 612.92 | 01-APR-06:05 | 0.29 |
May | 0.116283E+10 | 0.21 | 612.92 | 01-MAY-06:05 | 0.29 |
June | 0.112532E+10 | 0.21 | 612.92 | 01-JUN-06:05 | 0.29 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:05 | 0.29 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.29 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:10 | 0.29 |
October | 0.116283E+10 | 0.21 | 612.92 | 01-OCT-06:10 | 0.29 |
November | 0.112532E+10 | 0.21 | 612.92 | 01-NOV-06:05 | 0.29 |
December | 0.116283E+10 | 0.21 | 612.92 | 01-DEC-07:05 | 0.29 |
Annual Sum or Average | 0.136914E+11 | 0.21 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.29 | |
Maximum of Months | 0.116283E+10 | 0.21 | 612.92 | 0.29 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182054E+09 | 0.45 | 893.53 | 01-JAN-09:02 | 0.63 |
February | 0.130326E+09 | 0.42 | 893.53 | 01-FEB-16:01 | 0.64 |
March | 0.153270E+09 | 0.39 | 893.53 | 02-MAR-16:01 | 0.63 |
April | 0.415313E+09 | 0.51 | 893.53 | 01-APR-08:51 | 0.63 |
May | 0.499079E+09 | 0.54 | 893.53 | 01-MAY-08:51 | 0.64 |
June | 0.689255E+09 | 0.58 | 893.53 | 01-JUN-08:62 | 0.63 |
July | 0.612514E+09 | 0.59 | 893.53 | 01-JUL-08:61 | 0.64 |
August | 0.599629E+09 | 0.57 | 893.53 | 01-AUG-08:61 | 0.63 |
September | 0.511077E+09 | 0.54 | 893.53 | 01-SEP-08:62 | 0.63 |
October | 0.324375E+09 | 0.46 | 893.53 | 01-OCT-08:61 | 0.63 |
November | 0.173938E+09 | 0.42 | 893.53 | 01-NOV-08:51 | 0.63 |
December | 0.182200E+09 | 0.45 | 893.53 | 01-DEC-16:01 | 0.64 |
Annual Sum or Average | 0.447303E+10 | 0.49 | |||
Minimum of Months | 0.130326E+09 | 0.39 | 893.53 | 0.63 | |
Maximum of Months | 0.689255E+09 | 0.59 | 893.53 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136514E+09 | 0.39 | 888.02 | 01-JAN-09:02 | 0.63 |
February | 0.141596E+09 | 0.40 | 888.02 | 01-FEB-09:02 | 0.63 |
March | 0.137753E+09 | 0.36 | 888.02 | 02-MAR-16:01 | 0.63 |
April | 0.367984E+09 | 0.49 | 888.02 | 01-APR-08:51 | 0.63 |
May | 0.486509E+09 | 0.53 | 888.02 | 01-MAY-08:51 | 0.64 |
June | 0.700655E+09 | 0.58 | 888.02 | 01-JUN-08:62 | 0.63 |
July | 0.611010E+09 | 0.59 | 888.02 | 01-JUL-08:61 | 0.64 |
August | 0.565861E+09 | 0.56 | 888.02 | 01-AUG-08:61 | 0.63 |
September | 0.455232E+09 | 0.53 | 888.02 | 01-SEP-08:62 | 0.63 |
October | 0.248933E+09 | 0.42 | 888.02 | 01-OCT-08:61 | 0.63 |
November | 0.126322E+09 | 0.37 | 888.02 | 01-NOV-08:51 | 0.63 |
December | 0.210199E+09 | 0.40 | 888.02 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.418857E+10 | 0.47 | |||
Minimum of Months | 0.126322E+09 | 0.36 | 888.02 | 0.63 | |
Maximum of Months | 0.700655E+09 | 0.59 | 888.02 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163284E+10 | 0.43 | 2307.53 | 14-JAN-13:40 | 0.64 |
February | 0.539656E+09 | 0.23 | 1446.54 | 01-FEB-14:30 | 0.64 |
March | 0.546947E+09 | 0.25 | 1759.42 | 25-MAR-11:30 | 0.64 |
April | 0.146841E+10 | 0.52 | 1315.88 | 14-APR-13:40 | 0.64 |
May | 0.148203E+10 | 0.54 | 1131.87 | 09-MAY-17:12 | 0.64 |
June | 0.205090E+10 | 0.63 | 1523.19 | 28-JUN-17:13 | 0.63 |
July | 0.202155E+10 | 0.62 | 1373.06 | 21-JUL-20:20 | 0.63 |
August | 0.212079E+10 | 0.62 | 1514.83 | 28-AUG-12:30 | 0.63 |
September | 0.212682E+10 | 0.61 | 2659.98 | 28-SEP-12:40 | 0.63 |
October | 0.183639E+10 | 0.52 | 2674.90 | 05-OCT-14:10 | 0.63 |
November | 0.133964E+10 | 0.40 | 2484.23 | 01-NOV-13:50 | 0.63 |
December | 0.120565E+10 | 0.36 | 2292.90 | 25-DEC-13:30 | 0.64 |
Annual Sum or Average | 0.183716E+11 | 0.48 | |||
Minimum of Months | 0.539656E+09 | 0.23 | 1131.87 | 0.63 | |
Maximum of Months | 0.212682E+10 | 0.63 | 2674.90 | 0.64 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.694537E+09 | 0.36 | 5705.38 | 01-JAN-16:02 | 0.64 |
February | 0.608250E+09 | 0.40 | 5705.38 | 02-FEB-16:01 | 0.64 |
March | 0.862451E+09 | 0.34 | 5705.38 | 01-MAR-20:42 | 0.63 |
April | 0.191886E+10 | 0.38 | 5705.38 | 01-APR-08:51 | 0.64 |
May | 0.275570E+10 | 0.43 | 5705.38 | 01-MAY-08:51 | 0.64 |
June | 0.398265E+10 | 0.52 | 5705.38 | 01-JUN-08:62 | 0.63 |
July | 0.379682E+10 | 0.52 | 5705.38 | 01-JUL-08:61 | 0.64 |
August | 0.337815E+10 | 0.48 | 5705.38 | 01-AUG-08:61 | 0.63 |
September | 0.288250E+10 | 0.44 | 5705.38 | 01-SEP-08:62 | 0.63 |
October | 0.150756E+10 | 0.35 | 5705.38 | 01-OCT-08:61 | 0.63 |
November | 0.728267E+09 | 0.34 | 5705.38 | 01-NOV-08:51 | 0.63 |
December | 0.887232E+09 | 0.39 | 5705.38 | 01-DEC-19:11 | 0.64 |
Annual Sum or Average | 0.240030E+11 | 0.41 | |||
Minimum of Months | 0.608250E+09 | 0.34 | 5705.38 | 0.63 | |
Maximum of Months | 0.398265E+10 | 0.52 | 5705.38 | 0.64 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177521E+09 | 0.47 | 789.46 | 01-JAN-16:02 | 0.64 |
February | 0.133806E+09 | 0.43 | 789.46 | 01-FEB-09:02 | 0.63 |
March | 0.158559E+09 | 0.41 | 789.46 | 02-MAR-09:02 | 0.63 |
April | 0.410578E+09 | 0.53 | 789.46 | 01-APR-08:51 | 0.63 |
May | 0.506973E+09 | 0.55 | 789.46 | 01-MAY-08:51 | 0.64 |
June | 0.715278E+09 | 0.59 | 789.46 | 01-JUN-07:21 | 0.63 |
July | 0.662570E+09 | 0.60 | 789.46 | 01-JUL-08:61 | 0.64 |
August | 0.633316E+09 | 0.58 | 789.46 | 01-AUG-08:61 | 0.63 |
September | 0.533117E+09 | 0.55 | 789.46 | 01-SEP-07:02 | 0.63 |
October | 0.336732E+09 | 0.48 | 789.46 | 01-OCT-08:61 | 0.63 |
November | 0.166505E+09 | 0.43 | 789.46 | 01-NOV-08:51 | 0.63 |
December | 0.175804E+09 | 0.45 | 789.46 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.461076E+10 | 0.51 | |||
Minimum of Months | 0.133806E+09 | 0.41 | 789.46 | 0.63 | |
Maximum of Months | 0.715278E+09 | 0.60 | 789.46 | 0.64 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132194E+09 | 0.36 | 784.63 | 01-JAN-16:02 | 0.64 |
February | 0.126879E+09 | 0.40 | 784.63 | 01-FEB-09:02 | 0.63 |
March | 0.135768E+09 | 0.37 | 784.63 | 02-MAR-16:01 | 0.63 |
April | 0.359297E+09 | 0.53 | 784.63 | 01-APR-08:51 | 0.63 |
May | 0.493736E+09 | 0.55 | 784.63 | 01-MAY-08:51 | 0.64 |
June | 0.726152E+09 | 0.59 | 784.63 | 01-JUN-07:21 | 0.63 |
July | 0.661691E+09 | 0.60 | 784.63 | 01-JUL-08:61 | 0.64 |
August | 0.603563E+09 | 0.58 | 784.63 | 01-AUG-08:61 | 0.63 |
September | 0.475120E+09 | 0.55 | 784.63 | 01-SEP-07:02 | 0.63 |
October | 0.252208E+09 | 0.44 | 784.63 | 01-OCT-08:61 | 0.63 |
November | 0.118138E+09 | 0.35 | 784.63 | 01-NOV-08:51 | 0.63 |
December | 0.186059E+09 | 0.39 | 784.63 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.427081E+10 | 0.48 | |||
Minimum of Months | 0.118138E+09 | 0.35 | 784.63 | 0.63 | |
Maximum of Months | 0.726152E+09 | 0.60 | 784.63 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 50364372.63 | 0.44 | 236.74 | 01-JAN-09:02 | 0.63 |
February | 41990110.16 | 0.42 | 236.74 | 01-FEB-16:01 | 0.64 |
March | 44006989.45 | 0.39 | 236.74 | 02-MAR-16:01 | 0.63 |
April | 0.106430E+09 | 0.51 | 236.74 | 01-APR-08:51 | 0.63 |
May | 0.129201E+09 | 0.54 | 236.74 | 01-MAY-08:51 | 0.64 |
June | 0.182719E+09 | 0.58 | 236.74 | 01-JUN-08:62 | 0.63 |
July | 0.161623E+09 | 0.59 | 236.74 | 01-JUL-08:61 | 0.64 |
August | 0.158703E+09 | 0.57 | 236.74 | 01-AUG-08:61 | 0.63 |
September | 0.131220E+09 | 0.54 | 236.74 | 01-SEP-08:62 | 0.63 |
October | 81136943.53 | 0.46 | 236.74 | 01-OCT-08:61 | 0.63 |
November | 46372279.70 | 0.42 | 236.74 | 01-NOV-08:51 | 0.63 |
December | 56947164.13 | 0.45 | 236.74 | 01-DEC-16:01 | 0.64 |
Annual Sum or Average | 0.119071E+10 | 0.49 | |||
Minimum of Months | 41990110.16 | 0.39 | 236.74 | 0.63 | |
Maximum of Months | 0.182719E+09 | 0.59 | 236.74 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 45942951.68 | 0.38 | 235.16 | 01-JAN-09:02 | 0.63 |
February | 47766637.84 | 0.40 | 235.16 | 01-FEB-09:02 | 0.63 |
March | 41570824.90 | 0.36 | 235.16 | 02-MAR-09:02 | 0.63 |
April | 94456377.60 | 0.50 | 235.16 | 01-APR-08:51 | 0.63 |
May | 0.125929E+09 | 0.54 | 235.16 | 01-MAY-08:51 | 0.64 |
June | 0.186043E+09 | 0.58 | 235.16 | 01-JUN-08:62 | 0.63 |
July | 0.161291E+09 | 0.59 | 235.16 | 01-JUL-08:61 | 0.64 |
August | 0.150074E+09 | 0.57 | 235.16 | 01-AUG-08:61 | 0.63 |
September | 0.117179E+09 | 0.53 | 235.16 | 01-SEP-08:62 | 0.63 |
October | 63949312.57 | 0.42 | 235.16 | 01-OCT-08:61 | 0.63 |
November | 39030564.35 | 0.37 | 235.16 | 01-NOV-15:02 | 0.63 |
December | 69357143.69 | 0.40 | 235.16 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.114259E+10 | 0.47 | |||
Minimum of Months | 39030564.35 | 0.36 | 235.16 | 0.63 | |
Maximum of Months | 0.186043E+09 | 0.59 | 235.16 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.447735E+09 | 0.49 | 1056.00 | 01-JAN-16:02 | 0.63 |
February | 0.233018E+09 | 0.48 | 1056.00 | 01-FEB-09:02 | 0.63 |
March | 0.252558E+09 | 0.43 | 1056.00 | 01-MAR-16:02 | 0.63 |
April | 0.514334E+09 | 0.51 | 1056.00 | 01-APR-08:51 | 0.63 |
May | 0.549592E+09 | 0.53 | 1056.00 | 01-MAY-08:51 | 0.64 |
June | 0.751997E+09 | 0.57 | 1056.00 | 01-JUN-08:62 | 0.63 |
July | 0.744435E+09 | 0.58 | 1056.00 | 01-JUL-08:61 | 0.64 |
August | 0.764305E+09 | 0.56 | 1056.00 | 01-AUG-08:61 | 0.63 |
September | 0.747318E+09 | 0.54 | 1056.00 | 01-SEP-08:62 | 0.63 |
October | 0.573008E+09 | 0.48 | 1056.00 | 01-OCT-08:61 | 0.63 |
November | 0.394158E+09 | 0.45 | 1056.00 | 01-NOV-08:51 | 0.63 |
December | 0.378803E+09 | 0.51 | 1056.00 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.635126E+10 | 0.51 | |||
Minimum of Months | 0.233018E+09 | 0.43 | 1056.00 | 0.63 | |
Maximum of Months | 0.764305E+09 | 0.58 | 1056.00 | 0.64 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.206663E+09 | 0.185997E+09 | 646.38 | 12-JAN-06:31 | 581.74 | 581.74 | 52.59 | 1.26 |
February | 0.238859E+09 | 0.214973E+09 | 634.05 | 08-FEB-04:11 | 570.65 | 570.65 | 50.97 | 1.19 |
March | 0.163363E+09 | 0.147027E+09 | 618.82 | 31-MAR-03:41 | 556.94 | 556.94 | 51.72 | 1.12 |
April | 8230279.53 | 7407251.58 | 517.39 | 21-APR-04:23 | 465.65 | 465.65 | 44.31 | 0.78 |
May | 940847.59 | 846762.83 | 319.43 | 01-MAY-08:53 | 287.48 | 287.48 | 29.29 | 0.40 |
June | 205037.40 | 184533.66 | 157.86 | 05-JUN-08:07 | 142.07 | 142.07 | 41.61 | 0.17 |
July | 359848.09 | 323863.28 | 175.91 | 18-JUL-08:04 | 158.32 | 158.32 | 44.99 | 0.20 |
August | 365889.00 | 329300.10 | 318.42 | 29-AUG-08:04 | 286.57 | 286.57 | 44.25 | 0.39 |
September | 546885.01 | 492196.51 | 243.49 | 25-SEP-08:24 | 219.14 | 219.14 | 43.35 | 0.28 |
October | 54407435.18 | 48966691.67 | 586.46 | 26-OCT-03:15 | 527.81 | 527.81 | 38.54 | 1.00 |
November | 0.145496E+09 | 0.130946E+09 | 637.86 | 23-NOV-21:55 | 574.07 | 574.07 | 36.39 | 1.22 |
December | 0.341477E+09 | 0.307329E+09 | 658.10 | 06-DEC-22:05 | 592.29 | 592.29 | 37.42 | 1.33 |
Annual Sum or Average | 0.116091E+10 | 0.104482E+10 | ||||||
Minimum of Months | 205037.40 | 184533.66 | 157.86 | 142.07 | 142.07 | 29.29 | 0.17 | |
Maximum of Months | 0.341477E+09 | 0.307329E+09 | 658.10 | 592.29 | 592.29 | 52.59 | 1.33 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112813E+09 | 0.101532E+09 | 496.13 | 31-JAN-16:02 | 446.51 | 446.51 | 6.72 | 11.84 |
February | 27185514.26 | 24466962.84 | 334.27 | 18-FEB-16:01 | 300.85 | 300.85 | 6.72 | 9.90 |
March | 0.103366E+09 | 93029099.55 | 880.30 | 16-MAR-18:06 | 792.27 | 792.27 | 6.72 | 15.22 |
April | 0.423051E+09 | 0.380746E+09 | 1123.09 | 25-APR-18:50 | 1010.78 | 1010.78 | 6.72 | 16.89 |
May | 0.532252E+09 | 0.479027E+09 | 822.23 | 11-MAY-21:50 | 740.01 | 740.01 | 6.72 | 14.78 |
June | 0.103368E+10 | 0.930316E+09 | 2221.11 | 28-JUN-18:50 | 1999.00 | 1999.00 | 6.72 | 22.42 |
July | 0.121029E+10 | 0.108926E+10 | 1497.70 | 13-JUL-18:02 | 1347.93 | 1347.93 | 6.72 | 19.06 |
August | 0.116886E+10 | 0.105197E+10 | 1735.92 | 27-AUG-18:02 | 1562.33 | 1562.33 | 6.72 | 20.26 |
September | 0.109825E+10 | 0.988423E+09 | 1709.54 | 18-SEP-18:08 | 1538.58 | 1538.58 | 6.72 | 20.14 |
October | 0.450661E+09 | 0.405595E+09 | 1473.89 | 05-OCT-18:30 | 1326.50 | 1326.50 | 6.72 | 18.93 |
November | 0.128001E+09 | 0.115201E+09 | 1037.29 | 01-NOV-18:01 | 933.56 | 933.56 | 6.72 | 16.33 |
December | 57552327.75 | 51797094.98 | 457.75 | 25-DEC-16:02 | 411.98 | 411.98 | 6.72 | 11.42 |
Annual Sum or Average | 0.634596E+10 | 0.571137E+10 | ||||||
Minimum of Months | 27185514.26 | 24466962.84 | 334.27 | 300.85 | 300.85 | 6.72 | 9.90 | |
Maximum of Months | 0.121029E+10 | 0.108926E+10 | 2221.11 | 1999.00 | 1999.00 | 6.72 | 22.42 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.907417E+10 | 0.816675E+10 | 3551.02 | 01-JAN-01:00 | 3195.92 | 3195.92 | 6.73 | 31.41 |
February | 0.703787E+10 | 0.633409E+10 | 3551.02 | 01-FEB-00:10 | 3195.92 | 3195.92 | 6.88 | 31.41 |
March | 0.861289E+10 | 0.775160E+10 | 3551.02 | 01-MAR-00:10 | 3195.92 | 3195.92 | 6.76 | 31.41 |
April | 0.920051E+10 | 0.828046E+10 | 3551.02 | 01-APR-00:10 | 3195.92 | 3195.92 | 6.91 | 31.41 |
May | 0.951105E+10 | 0.855995E+10 | 3551.02 | 01-MAY-00:05 | 3195.92 | 3195.92 | 7.64 | 31.41 |
June | 0.920424E+10 | 0.828382E+10 | 3551.02 | 01-JUN-00:05 | 3195.92 | 3195.92 | 8.54 | 31.41 |
July | 0.951105E+10 | 0.855995E+10 | 3551.02 | 01-JUL-00:10 | 3195.92 | 3195.92 | 8.87 | 31.41 |
August | 0.951105E+10 | 0.855995E+10 | 3551.02 | 01-AUG-00:05 | 3195.92 | 3195.92 | 9.10 | 31.41 |
September | 0.920424E+10 | 0.828382E+10 | 3551.02 | 01-SEP-00:05 | 3195.92 | 3195.92 | 8.65 | 31.41 |
October | 0.938783E+10 | 0.844905E+10 | 3551.02 | 01-OCT-00:10 | 3195.92 | 3195.92 | 8.55 | 31.41 |
November | 0.874512E+10 | 0.787061E+10 | 3551.02 | 01-NOV-00:05 | 3195.92 | 3195.92 | 7.28 | 31.41 |
December | 0.794241E+10 | 0.714817E+10 | 3551.02 | 01-DEC-00:10 | 3195.92 | 3195.92 | 6.75 | 31.41 |
Annual Sum or Average | 0.106942E+12 | 0.962482E+11 | ||||||
Minimum of Months | 0.703787E+10 | 0.633409E+10 | 3551.02 | 3195.92 | 3195.92 | 6.73 | 31.41 | |
Maximum of Months | 0.951105E+10 | 0.855995E+10 | 3551.02 | 3195.92 | 3195.92 | 9.10 | 31.41 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.26 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 50.37 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 51.22 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.96 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.96 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 54.27 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.36 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.20 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 54.40 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.41 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.06 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 51.36 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.26 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.40 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 43.47 | 60.00 | 7334.46 | 110182.52 | 02-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 39.35 | 60.00 | 9033.71 | 106830.65 | 02-FEB-03:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 40.64 | 60.00 | 5328.64 | 104907.50 | 27-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 45.32 | 45.32 | 361.55 | 76911.88 | 21-APR-04:31 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 36.81 | 36.81 | 38.35 | 50965.36 | 01-MAY-08:53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 40.94 | 40.94 | 6.06 | 13418.02 | 05-JUN-08:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 44.06 | 44.06 | 9.24 | 12321.75 | 18-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 45.11 | 45.11 | 9.45 | 25895.03 | 29-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 43.51 | 43.51 | 15.72 | 20560.29 | 29-SEP-08:24 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 42.90 | 42.90 | 2246.26 | 92579.44 | 25-OCT-05:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 36.01 | 36.01 | 5320.41 | 120156.83 | 23-NOV-21:55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 39.12 | 60.00 | 11446.95 | 125897.39 | 06-DEC-22:05 |
Annual Sum or Average | 0.00 | 3405.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 36.01 | 36.01 | 6.06 | 12321.75 | ||
Maximum of Months | 0.00 | 0.00 | 45.32 | 60.00 | 11446.95 | 125897.39 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 71915.96 | 407788.29 | 31-JAN-19:01 | 9.80 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 24936.81 | 264301.25 | 18-FEB-16:01 | 8.71 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66225.78 | 437656.48 | 15-MAR-18:01 | 10.02 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 187804.88 | 508046.30 | 14-APR-18:03 | 10.56 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 232355.16 | 517611.73 | 31-MAY-18:03 | 10.63 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 309865.57 | 623887.08 | 30-JUN-18:07 | 11.44 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 339896.51 | 658407.76 | 13-JUL-18:03 | 11.70 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 331163.82 | 637457.11 | 28-AUG-18:33 | 11.54 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 312996.03 | 772395.16 | 10-SEP-21:52 | 12.57 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 163021.25 | 565658.58 | 01-OCT-18:03 | 11.00 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 79763.34 | 426853.17 | 01-NOV-18:01 | 9.94 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 42227.48 | 358968.18 | 25-DEC-16:02 | 9.43 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 180992.08 | 0.00 | ||||||
Minimum of Months | 24936.81 | 264301.25 | 8.71 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 339896.51 | 772395.16 | 12.57 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.26 | 59.51 | 23524.86 | 58255.45 | 26-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 50.37 | 58.39 | 23303.11 | 56499.39 | 05-FEB-08:51 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 51.22 | 59.49 | 22284.20 | 52922.74 | 13-MAR-06:31 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.96 | 58.49 | 20643.65 | 45416.13 | 07-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.96 | 59.20 | 18859.26 | 39432.33 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.27 | 58.95 | 17412.99 | 35892.44 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.36 | 58.54 | 16681.00 | 33478.06 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.20 | 58.37 | 16914.26 | 34390.22 | 30-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 54.40 | 58.87 | 17995.10 | 37206.88 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.41 | 58.73 | 19633.17 | 47587.05 | 12-OCT-06:21 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.06 | 58.57 | 21403.13 | 53150.95 | 23-NOV-08:31 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 51.36 | 59.29 | 22816.47 | 56052.47 | 20-DEC-07:01 |
Annual Sum or Average | 0.00 | 20104.77 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.26 | 58.37 | 16681.00 | 33478.06 | ||
Maximum of Months | 0.00 | 0.00 | 54.40 | 59.51 | 23524.86 | 58255.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.159818E+11 | 0.00 | 0.107127E+12 | 0.358500E+11 | 0.00 | 0.00 |
February | 0.169754E+11 | 0.00 | 0.258547E+11 | 0.303501E+11 | 0.00 | 0.00 |
March | 0.113324E+11 | 0.00 | 0.116108E+12 | 0.345520E+11 | 0.00 | 0.00 |
April | 0.824528E+09 | 0.00 | 0.320815E+12 | 0.378445E+11 | 0.00 | 0.00 |
May | 43963729.68 | 0.00 | 0.417603E+12 | 0.408442E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.534011E+12 | 0.446243E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.620124E+12 | 0.458533E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.604339E+12 | 0.466216E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.555024E+12 | 0.452283E+11 | 0.00 | 0.00 |
October | 0.550703E+10 | 0.00 | 0.282703E+12 | 0.417540E+11 | 0.00 | 0.00 |
November | 0.113072E+11 | 0.00 | 0.122584E+12 | 0.367678E+11 | 0.00 | 0.00 |
December | 0.194548E+11 | 0.00 | 0.569862E+11 | 0.355972E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.814270E+11 | 0.00 | 0.376328E+13 | 0.475887E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.258547E+11 | 0.303501E+11 | 0.00 | 0.00 |
Maximum of Months | 0.194548E+11 | 0.00 | 0.620124E+12 | 0.466216E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 32774.01 | 0.00 | 0.198678E+11 | 0.587890E+10 | 0.00 | 0.00 |
February | 22476.64 | 0.00 | 0.520636E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 20623.00 | 0.00 | 0.213418E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 42833.88 | 0.00 | 0.508091E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 54567.07 | 0.00 | 0.644422E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 76852.81 | 0.00 | 0.750470E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 35169.58 | 0.00 | 0.881593E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 33281.72 | 0.00 | 0.878394E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 32824.97 | 0.00 | 0.825085E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 32909.51 | 0.00 | 0.444327E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 34884.42 | 0.00 | 0.228037E+11 | 0.568926E+10 | 0.00 | 0.00 |
December | 341901.64 | 0.00 | 0.111667E+11 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 761099.26 | 0.00 | 0.573625E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 20623.00 | 0.00 | 0.520636E+10 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 341901.64 | 0.00 | 0.881593E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.358500E+11 | 0.107127E+12 | 0.159818E+11 | 0.691003E+11 | 0.160990E+09 | 0.00 | 0.00 | 0.00 |
February | 0.303501E+11 | 0.258550E+11 | 0.169754E+11 | 0.610560E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345520E+11 | 0.116108E+12 | 0.113324E+11 | 0.675051E+11 | 0.726513E+09 | 0.00 | 0.00 | 0.00 |
April | 0.378445E+11 | 0.320815E+12 | 0.824528E+09 | 0.137085E+11 | 0.197317E+11 | 0.00 | 0.00 | 0.00 |
May | 0.408442E+11 | 0.417603E+12 | 43963729.68 | 0.143641E+11 | 0.391945E+11 | 0.00 | 0.00 | 0.00 |
June | 0.446243E+11 | 0.534011E+12 | 0.00 | 0.241765E+11 | 0.858902E+11 | 0.00 | 0.00 | 0.00 |
July | 0.458533E+11 | 0.620124E+12 | 0.00 | 0.120640E+11 | 0.116802E+12 | 0.00 | 0.00 | 0.00 |
August | 0.466216E+11 | 0.604339E+12 | 0.00 | 0.135616E+11 | 0.989689E+11 | 0.00 | 0.00 | 0.00 |
September | 0.452283E+11 | 0.555024E+12 | 0.00 | 0.109884E+11 | 0.691362E+11 | 0.00 | 0.00 | 0.00 |
October | 0.417540E+11 | 0.282703E+12 | 0.550703E+10 | 0.193621E+11 | 0.170324E+11 | 0.00 | 0.00 | 0.00 |
November | 0.367678E+11 | 0.122584E+12 | 0.113072E+11 | 0.456404E+11 | 0.327360E+09 | 0.00 | 0.00 | 0.00 |
December | 0.355972E+11 | 0.569866E+11 | 0.194548E+11 | 0.125692E+12 | 6135463.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475887E+12 | 0.376328E+13 | 0.814270E+11 | 0.477219E+12 | 0.447977E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303501E+11 | 0.258550E+11 | 0.00 | 0.109884E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.466216E+11 | 0.620124E+12 | 0.194548E+11 | 0.125692E+12 | 0.116802E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.198678E+11 | 32774.01 | 0.177281E+11 | 0.190232E+09 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.520636E+10 | 22476.64 | 0.168654E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.213418E+11 | 20623.00 | 0.150263E+11 | 0.563863E+09 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.508091E+11 | 42833.88 | 0.160855E+10 | 0.828114E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.644422E+11 | 54567.07 | 0.870690E+09 | 0.143828E+11 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.750470E+11 | 76852.81 | 0.868459E+09 | 0.286162E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.881593E+11 | 35169.58 | 0.264036E+09 | 0.497220E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.878394E+11 | 33281.72 | 0.236110E+09 | 0.450480E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.825085E+11 | 32824.97 | 0.262939E+09 | 0.340660E+11 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.444327E+11 | 32909.51 | 0.464448E+10 | 0.899697E+10 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.228037E+11 | 34884.42 | 0.135034E+11 | 0.513252E+09 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.111667E+11 | 341901.64 | 0.301799E+11 | 99808845.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.573625E+12 | 761099.26 | 0.102058E+12 | 0.190480E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.520636E+10 | 20623.00 | 0.236110E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.881593E+11 | 341901.64 | 0.301799E+11 | 0.497220E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.358500E+11 | 0.159818E+11 | 0.107127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303501E+11 | 0.169754E+11 | 0.258547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345520E+11 | 0.113324E+11 | 0.116108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.378445E+11 | 0.824528E+09 | 0.320815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.408442E+11 | 43963729.68 | 0.417603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.446243E+11 | 0.00 | 0.534011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.458533E+11 | 0.00 | 0.620124E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.466216E+11 | 0.00 | 0.604339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452283E+11 | 0.00 | 0.555024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417540E+11 | 0.550703E+10 | 0.282703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367678E+11 | 0.113072E+11 | 0.122584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355972E+11 | 0.194548E+11 | 0.569862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475887E+12 | 0.814270E+11 | 0.376328E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303501E+11 | 0.00 | 0.258547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.466216E+11 | 0.194548E+11 | 0.620124E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 32774.01 | 0.198678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 22476.64 | 0.520636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 20623.00 | 0.213418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 42833.88 | 0.508091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 54567.07 | 0.644422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 76852.81 | 0.750470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 35169.58 | 0.881593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 33281.72 | 0.878394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 32824.97 | 0.825085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 32909.51 | 0.444327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 34884.42 | 0.228037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 341901.64 | 0.111667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 761099.26 | 0.573625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 20623.00 | 0.520636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 341901.64 | 0.881593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.421329E+10 | 166948.68 | 0.00 | 57929805.53 | 0.00 | 0.00 | 0.409712E+11 | 0.00 | 1.10 |
February | 0.326776E+11 | 0.00 | 0.00 | 7938496.98 | 0.00 | 0.00 | 0.113207E+11 | 0.00 | 1.04 |
March | 0.385083E+11 | 0.00 | 0.00 | 288701.11 | 9065015.32 | 0.00 | 0.742117E+09 | 0.00 | 1.04 |
April | 0.180403E+11 | 0.00 | 0.00 | 2549321.56 | 0.579350E+09 | 0.00 | 0.200752E+10 | 0.00 | 0.99 |
May | 0.133696E+11 | 0.00 | 0.00 | 207381.68 | 0.135379E+10 | 0.00 | 0.265913E+09 | 0.00 | 0.95 |
June | 0.571261E+10 | 67987430.71 | 0.00 | 1747931.75 | 0.345076E+10 | 0.00 | 0.282527E+09 | 0.00 | 0.87 |
July | 0.354487E+09 | 0.601361E+10 | 0.00 | 22413484.60 | 0.946872E+09 | 0.00 | 0.255454E+10 | 0.00 | 0.92 |
August | 109392.75 | 0.571117E+10 | 0.00 | 35917056.98 | 0.249487E+09 | 0.00 | 0.402379E+10 | 0.00 | 1.01 |
September | 0.00 | 0.605964E+10 | 0.00 | 48986090.37 | 5071455.44 | 0.00 | 0.757804E+10 | 0.00 | 1.17 |
October | 25332191.40 | 0.794149E+09 | 0.00 | 0.110910E+09 | 0.00 | 0.00 | 0.367096E+11 | 0.00 | 1.31 |
November | 53004133.03 | 14923384.49 | 0.00 | 0.125693E+09 | 0.00 | 0.00 | 0.517110E+11 | 0.00 | 1.34 |
December | 0.155807E+09 | 0.00 | 0.00 | 0.132705E+09 | 0.00 | 0.00 | 0.590491E+11 | 0.00 | 1.24 |
Annual Sum or Average | 0.113110E+12 | 0.186617E+11 | 0.00 | 0.547287E+09 | 0.659440E+10 | 0.00 | 0.217216E+12 | 0.00 | 1.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 207381.68 | 0.00 | 0.00 | 0.265913E+09 | 0.00 | 0.87 |
Maximum of Months | 0.385083E+11 | 0.605964E+10 | 0.00 | 0.132705E+09 | 0.345076E+10 | 0.00 | 0.590491E+11 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.372880E+10 | 40025.11 | 0.00 | 5414595.86 | 0.00 | 0.00 | 0.168045E+10 | 0.00 | 2.64 |
February | 0.484215E+10 | 0.00 | 0.00 | 1055050.40 | 0.00 | 2777302.39 | 0.665964E+09 | 0.00 | 2.36 |
March | 0.446072E+10 | 867109.76 | 0.00 | 1081766.70 | 364762.21 | 22409287.71 | 0.398425E+09 | 0.00 | 2.37 |
April | 0.168476E+10 | 99840459.43 | 0.00 | 3748739.44 | 85893.28 | 0.00 | 0.822056E+09 | 0.00 | 2.41 |
May | 0.104874E+10 | 0.196008E+09 | 0.00 | 2810470.76 | 2073774.84 | 0.00 | 0.658570E+09 | 0.00 | 2.27 |
June | 0.122049E+09 | 0.582246E+09 | 0.00 | 3485804.53 | 812946.56 | 0.00 | 0.647524E+09 | 0.00 | 2.33 |
July | 65954687.33 | 0.960357E+09 | 0.00 | 1987617.74 | 26311163.42 | 0.00 | 0.293432E+09 | 0.00 | 2.25 |
August | 95021720.62 | 0.862284E+09 | 0.00 | 2220260.29 | 17824674.51 | 0.00 | 0.340016E+09 | 0.00 | 2.36 |
September | 0.194750E+09 | 0.699975E+09 | 0.00 | 2760397.82 | 82518828.41 | 0.00 | 0.497402E+09 | 0.00 | 2.45 |
October | 0.220730E+10 | 0.136674E+09 | 0.00 | 4999295.66 | 489496.86 | 0.00 | 0.118475E+10 | 0.00 | 2.61 |
November | 0.354402E+10 | 1812.69 | 0.00 | 4559554.07 | 1851992.27 | 0.00 | 0.141075E+10 | 0.00 | 2.58 |
December | 0.466055E+10 | 0.00 | 0.00 | 3210682.24 | 0.00 | 42418546.67 | 0.119521E+10 | 0.00 | 2.44 |
Annual Sum or Average | 0.266548E+11 | 0.353829E+10 | 0.00 | 37334235.52 | 0.132334E+09 | 67605136.77 | 0.979455E+10 | 0.00 | 2.42 |
Minimum of Months | 65954687.33 | 0.00 | 0.00 | 1055050.40 | 0.00 | 0.00 | 0.293432E+09 | 0.00 | 2.25 |
Maximum of Months | 0.484215E+10 | 0.960357E+09 | 0.00 | 5414595.86 | 82518828.41 | 42418546.67 | 0.168045E+10 | 0.00 | 2.64 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216526E+10 | 0.00 | 0.00 | 1955739.27 | 15100.15 | 0.00 | 0.170752E+10 | 0.00 | 1.49 |
February | 0.317226E+10 | 0.00 | 0.00 | 566021.87 | 0.00 | 0.00 | 0.803368E+09 | 0.00 | 1.47 |
March | 0.232800E+10 | 0.00 | 0.00 | 1408876.88 | 819911.41 | 0.00 | 0.125828E+10 | 0.00 | 1.50 |
April | 0.181302E+09 | 45328889.02 | 0.00 | 4871927.13 | 7276420.54 | 0.00 | 0.180776E+10 | 0.00 | 1.55 |
May | 15248984.83 | 0.115206E+09 | 0.00 | 5134506.19 | 8732529.83 | 0.00 | 0.137875E+10 | 0.00 | 1.53 |
June | 91176.98 | 0.337745E+09 | 0.00 | 5184124.44 | 6092884.12 | 0.00 | 0.695217E+09 | 0.00 | 1.54 |
July | 93266.72 | 0.658629E+09 | 0.00 | 2772496.23 | 22462928.58 | 0.00 | 0.319027E+09 | 0.00 | 1.47 |
August | 543580.48 | 0.530592E+09 | 0.00 | 3235835.96 | 22891706.36 | 0.00 | 0.375866E+09 | 0.00 | 1.48 |
September | 1879629.14 | 0.471779E+09 | 0.00 | 3394456.76 | 28109578.34 | 0.00 | 0.572683E+09 | 0.00 | 1.49 |
October | 0.799400E+09 | 66080502.77 | 0.00 | 4112721.54 | 2882393.70 | 0.00 | 0.177741E+10 | 0.00 | 1.54 |
November | 0.182492E+10 | 0.00 | 0.00 | 2114169.04 | 1349618.80 | 0.00 | 0.173701E+10 | 0.00 | 1.50 |
December | 0.315302E+10 | 0.00 | 0.00 | 849738.24 | 0.00 | 0.00 | 0.104752E+10 | 0.00 | 1.44 |
Annual Sum or Average | 0.136420E+11 | 0.222536E+10 | 0.00 | 35600613.57 | 0.100633E+09 | 0.00 | 0.134804E+11 | 0.00 | 1.50 |
Minimum of Months | 91176.98 | 0.00 | 0.00 | 566021.87 | 0.00 | 0.00 | 0.319027E+09 | 0.00 | 1.44 |
Maximum of Months | 0.317226E+10 | 0.658629E+09 | 0.00 | 5184124.44 | 28109578.34 | 0.00 | 0.180776E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326903E+10 | 0.00 | 0.00 | 0.00 | 13067.13 | 0.00 | 0.00 | 0.00 | 0.59 |
February | 0.343080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.307216E+10 | 0.00 | 0.00 | 0.00 | 709521.96 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.134299E+10 | 472549.30 | 0.00 | 624859.32 | 44873510.47 | 0.00 | 0.231448E+09 | 0.00 | 0.58 |
May | 0.422687E+09 | 46558484.36 | 0.00 | 2092477.68 | 59680357.57 | 0.00 | 0.671341E+09 | 0.00 | 0.58 |
June | 0.00 | 0.325086E+09 | 0.00 | 4618629.87 | 917677.72 | 0.00 | 0.581274E+09 | 0.00 | 0.65 |
July | 4441247.90 | 0.611106E+09 | 0.00 | 2392735.65 | 14535297.55 | 0.00 | 0.267677E+09 | 0.00 | 0.62 |
August | 27544159.53 | 0.462810E+09 | 0.00 | 2465930.17 | 26943057.27 | 0.00 | 0.273503E+09 | 0.00 | 0.60 |
September | 39661732.56 | 0.367852E+09 | 0.00 | 2106966.04 | 60583477.21 | 0.00 | 0.414441E+09 | 0.00 | 0.58 |
October | 0.186529E+10 | 45925911.87 | 0.00 | 779267.19 | 13332284.34 | 0.00 | 0.240849E+09 | 0.00 | 0.59 |
November | 0.299768E+10 | 0.00 | 0.00 | 0.00 | 1167911.76 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.360958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.200819E+11 | 0.185981E+10 | 0.00 | 15080865.91 | 0.222756E+09 | 0.00 | 0.268053E+10 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.360958E+10 | 0.611106E+09 | 0.00 | 4618629.87 | 60583477.21 | 0.00 | 0.671341E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214401E+10 | 0.00 | 0.00 | 0.00 | 8570.13 | 0.00 | 0.00 | 0.00 | 0.68 |
February | 0.225010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
March | 0.201489E+10 | 0.00 | 0.00 | 0.00 | 465342.82 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.101045E+10 | 50760.14 | 0.00 | 48550.46 | 29689563.39 | 0.00 | 18772175.34 | 0.00 | 0.65 |
May | 0.574525E+09 | 16114792.76 | 0.00 | 454843.96 | 53381236.01 | 0.00 | 0.125963E+09 | 0.00 | 0.63 |
June | 19201999.96 | 0.200311E+09 | 0.00 | 2114356.66 | 2625908.81 | 0.00 | 0.306234E+09 | 0.00 | 0.65 |
July | 10599597.57 | 0.351614E+09 | 0.00 | 1132034.21 | 19719094.05 | 0.00 | 0.141127E+09 | 0.00 | 0.63 |
August | 45048353.77 | 0.257853E+09 | 0.00 | 905635.38 | 36246735.36 | 0.00 | 0.133245E+09 | 0.00 | 0.61 |
September | 0.153685E+09 | 0.168146E+09 | 0.00 | 554838.01 | 92851112.10 | 0.00 | 0.128079E+09 | 0.00 | 0.61 |
October | 0.133048E+10 | 24674060.18 | 0.00 | 150068.84 | 12300976.05 | 0.00 | 45641972.59 | 0.00 | 0.66 |
November | 0.196604E+10 | 0.00 | 0.00 | 0.00 | 765979.60 | 0.00 | 0.00 | 0.00 | 0.68 |
December | 0.236736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.138864E+11 | 0.101876E+10 | 0.00 | 5360327.52 | 0.248055E+09 | 0.00 | 0.899063E+09 | 0.00 | 0.65 |
Minimum of Months | 10599597.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.236736E+10 | 0.351614E+09 | 0.00 | 2114356.66 | 92851112.10 | 0.00 | 0.306234E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143842E+10 | 194680.00 | 0.00 | 0.123543E+09 | 0.00 | 0.00 | 0.602141E+11 | 0.00 | 23.11 |
February | 0.101388E+10 | 0.00 | 0.00 | 0.109815E+09 | 0.00 | 0.00 | 0.625048E+11 | 0.00 | 22.96 |
March | 0.815763E+09 | 10570776.14 | 0.00 | 0.118100E+09 | 0.00 | 0.00 | 0.563284E+11 | 0.00 | 23.55 |
April | 18634999.86 | 0.683625E+09 | 0.00 | 0.103500E+09 | 0.00 | 0.00 | 0.278107E+11 | 0.00 | 21.88 |
May | 0.00 | 0.163602E+10 | 0.00 | 87500733.26 | 0.00 | 0.00 | 0.182880E+11 | 0.00 | 20.91 |
June | 0.00 | 0.450140E+10 | 0.00 | 60454669.78 | 0.00 | 0.00 | 0.774865E+10 | 0.00 | 19.16 |
July | 0.00 | 0.924600E+10 | 0.00 | 31346250.29 | 0.00 | 0.00 | 0.362342E+10 | 0.00 | 18.87 |
August | 0.00 | 0.757895E+10 | 0.00 | 37888420.05 | 0.00 | 0.00 | 0.447526E+10 | 0.00 | 19.30 |
September | 0.00 | 0.693864E+10 | 0.00 | 47567668.96 | 0.00 | 0.00 | 0.733565E+10 | 0.00 | 19.82 |
October | 0.527986E+09 | 0.929767E+09 | 0.00 | 0.107337E+09 | 0.00 | 0.00 | 0.380816E+11 | 0.00 | 22.49 |
November | 0.105632E+10 | 17400072.84 | 0.00 | 0.115952E+09 | 0.00 | 0.00 | 0.551392E+11 | 0.00 | 23.18 |
December | 0.122765E+10 | 0.00 | 0.00 | 0.128164E+09 | 0.00 | 0.00 | 0.662805E+11 | 0.00 | 22.17 |
Annual Sum or Average | 0.609865E+10 | 0.315426E+11 | 0.00 | 0.107117E+10 | 0.00 | 0.00 | 0.407830E+12 | 0.00 | 21.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 31346250.29 | 0.00 | 0.00 | 0.362342E+10 | 0.00 | 18.87 |
Maximum of Months | 0.143842E+10 | 0.924600E+10 | 0.00 | 0.128164E+09 | 0.00 | 0.00 | 0.662805E+11 | 0.00 | 23.55 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280370E+10 | 143810.47 | 0.00 | 46045280.95 | 0.00 | 0.00 | 0.207399E+11 | 0.00 | 4.00 |
February | 0.661487E+10 | 0.00 | 0.00 | 20371699.93 | 0.00 | 0.00 | 0.166004E+11 | 0.00 | 3.55 |
March | 0.528928E+10 | 5068400.13 | 0.00 | 24460528.12 | 0.00 | 0.00 | 0.153832E+11 | 0.00 | 3.59 |
April | 0.902278E+09 | 0.367231E+09 | 0.00 | 32272163.49 | 686101.28 | 0.00 | 0.106170E+11 | 0.00 | 3.77 |
May | 0.178738E+09 | 0.746660E+09 | 0.00 | 27261335.31 | 8835478.07 | 0.00 | 0.791015E+10 | 0.00 | 3.60 |
June | 12691919.21 | 0.205451E+10 | 0.00 | 25262804.81 | 17745271.12 | 0.00 | 0.396316E+10 | 0.00 | 3.57 |
July | 2545349.12 | 0.390685E+10 | 0.00 | 14813055.67 | 56787836.21 | 0.00 | 0.182645E+10 | 0.00 | 3.50 |
August | 3344972.54 | 0.333966E+10 | 0.00 | 17695645.47 | 34445242.14 | 0.00 | 0.223147E+10 | 0.00 | 3.64 |
September | 12093580.93 | 0.310407E+10 | 0.00 | 20305189.81 | 23748590.10 | 0.00 | 0.349610E+10 | 0.00 | 3.80 |
October | 0.146242E+10 | 0.506844E+09 | 0.00 | 39598253.52 | 838720.15 | 0.00 | 0.138454E+11 | 0.00 | 4.02 |
November | 0.205027E+10 | 9147.80 | 0.00 | 40690885.82 | 7644404.78 | 0.00 | 0.194116E+11 | 0.00 | 3.91 |
December | 0.491699E+10 | 0.00 | 0.00 | 32341300.82 | 0.00 | 0.00 | 0.201197E+11 | 0.00 | 3.68 |
Annual Sum or Average | 0.242492E+11 | 0.140311E+11 | 0.00 | 0.341118E+09 | 0.150732E+09 | 0.00 | 0.136145E+12 | 0.00 | 3.72 |
Minimum of Months | 2545349.12 | 0.00 | 0.00 | 14813055.67 | 0.00 | 0.00 | 0.182645E+10 | 0.00 | 3.50 |
Maximum of Months | 0.661487E+10 | 0.390685E+10 | 0.00 | 46045280.95 | 56787836.21 | 0.00 | 0.207399E+11 | 0.00 | 4.02 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111771E+11 | 282178.90 | 0.00 | 0.110894E+09 | 0.00 | 0.00 | 0.653485E+11 | 0.00 | 1.73 |
February | 0.300572E+11 | 0.00 | 0.00 | 46141391.76 | 0.00 | 0.00 | 0.461201E+11 | 0.00 | 1.67 |
March | 0.208914E+11 | 6040672.64 | 0.00 | 68083831.22 | 9281137.53 | 0.00 | 0.485991E+11 | 0.00 | 1.72 |
April | 0.193488E+10 | 0.946437E+09 | 0.00 | 0.104936E+09 | 40266671.50 | 0.00 | 0.382888E+11 | 0.00 | 1.79 |
May | 0.217721E+09 | 0.219792E+10 | 0.00 | 0.102926E+09 | 0.108144E+09 | 0.00 | 0.286171E+11 | 0.00 | 1.77 |
June | 5211471.95 | 0.614651E+10 | 0.00 | 98300666.29 | 0.183741E+09 | 0.00 | 0.141550E+11 | 0.00 | 1.74 |
July | 1154434.38 | 0.125944E+11 | 0.00 | 55672414.54 | 0.344264E+09 | 0.00 | 0.654020E+10 | 0.00 | 1.70 |
August | 1534202.23 | 0.101542E+11 | 0.00 | 65397612.83 | 0.295952E+09 | 0.00 | 0.778644E+10 | 0.00 | 1.72 |
September | 22728413.15 | 0.960056E+10 | 0.00 | 70760498.06 | 0.168062E+09 | 0.00 | 0.122030E+11 | 0.00 | 1.77 |
October | 0.517783E+10 | 0.136421E+10 | 0.00 | 0.115477E+09 | 3860083.10 | 0.00 | 0.466698E+11 | 0.00 | 1.83 |
November | 0.834109E+10 | 0.00 | 0.00 | 0.100664E+09 | 25220533.42 | 0.00 | 0.618411E+11 | 0.00 | 1.75 |
December | 0.242111E+11 | 0.00 | 0.00 | 71826636.12 | 0.00 | 0.00 | 0.566171E+11 | 0.00 | 1.63 |
Annual Sum or Average | 0.102039E+12 | 0.430106E+11 | 0.00 | 0.101108E+10 | 0.117879E+10 | 0.00 | 0.432786E+12 | 0.00 | 1.73 |
Minimum of Months | 1154434.38 | 0.00 | 0.00 | 46141391.76 | 0.00 | 0.00 | 0.654020E+10 | 0.00 | 1.63 |
Maximum of Months | 0.300572E+11 | 0.125944E+11 | 0.00 | 0.115477E+09 | 0.344264E+09 | 0.00 | 0.653485E+11 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298081E+09 | 579888.08 | 11084.86 | 8427266.28 | 330785.54 | 0.174730E+09 | 0.798370E+09 | 1364.91 | 0.47 |
February | 0.387151E+09 | 81682.08 | 0.00 | 3537966.02 | 0.00 | 0.420830E+09 | 0.563136E+09 | 0.00 | 0.48 |
March | 0.375045E+09 | 2004322.69 | 7437.58 | 5682545.96 | 292017.54 | 0.237338E+09 | 0.606129E+09 | 1924.57 | 0.47 |
April | 0.132766E+09 | 46111964.74 | 899.01 | 9020689.29 | 1797154.51 | 502166.62 | 0.428449E+09 | 5269.75 | 0.47 |
May | 82986908.80 | 82748941.28 | 2683.80 | 6498444.63 | 2463198.92 | 62212.41 | 0.251269E+09 | 6352.97 | 0.47 |
June | 27132757.19 | 0.200101E+09 | 1678.05 | 4977517.10 | 3803349.54 | 8478.66 | 68810501.73 | 1948.55 | 0.48 |
July | 8946625.80 | 0.623416E+09 | 354845.52 | 1294211.85 | 30677179.85 | 224.81 | 27437585.96 | 16946.20 | 0.47 |
August | 8487575.43 | 0.574927E+09 | 345170.21 | 1210891.23 | 43041698.02 | 0.00 | 17011954.84 | 19032.75 | 0.48 |
September | 20284562.03 | 0.447384E+09 | 352975.03 | 2216629.26 | 61473384.66 | 1295.48 | 33456808.14 | 29061.68 | 0.48 |
October | 0.225242E+09 | 92372930.60 | 56511.67 | 7788581.02 | 7586761.89 | 34311146.99 | 0.491909E+09 | 16615.20 | 0.47 |
November | 0.295330E+09 | 4690407.68 | 65447.84 | 7659478.83 | 9948056.82 | 0.143838E+09 | 0.689755E+09 | 5760.98 | 0.47 |
December | 0.345078E+09 | 210413.54 | 0.00 | 4805821.73 | 746250.94 | 0.499161E+09 | 0.592801E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.220653E+10 | 0.207463E+10 | 1198733.55 | 63120043.19 | 0.162160E+09 | 0.151078E+10 | 0.456853E+10 | 104277.56 | 0.47 |
Minimum of Months | 8487575.43 | 81682.08 | 0.00 | 1210891.23 | 0.00 | 0.00 | 17011954.84 | 0.00 | 0.47 |
Maximum of Months | 0.387151E+09 | 0.623416E+09 | 354845.52 | 9020689.29 | 61473384.66 | 0.499161E+09 | 0.798370E+09 | 29061.68 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.347309E+09 | 355762.73 | 9739.45 | 3379444.92 | 554804.19 | 0.465824E+09 | 0.462946E+09 | 2708.86 | 0.47 |
February | 0.441324E+09 | 81672.51 | 0.00 | 1500019.29 | 0.00 | 0.656876E+09 | 0.274794E+09 | 0.00 | 0.48 |
March | 0.398916E+09 | 1746584.44 | 5029.33 | 3861877.95 | 549486.74 | 0.349627E+09 | 0.471646E+09 | 4331.72 | 0.47 |
April | 0.137422E+09 | 45408066.57 | 3048.93 | 8127260.77 | 2487097.69 | 548445.90 | 0.424572E+09 | 11460.84 | 0.47 |
May | 83113700.53 | 82582676.05 | 5606.28 | 6375152.64 | 2616040.18 | 59920.12 | 0.251228E+09 | 6869.55 | 0.47 |
June | 27058189.57 | 0.200275E+09 | 206.08 | 5087115.15 | 3606183.89 | 7735.54 | 68764389.08 | 2660.54 | 0.48 |
July | 8945577.58 | 0.623728E+09 | 331326.95 | 1301025.16 | 30311463.89 | 224.78 | 27427406.30 | 17298.68 | 0.47 |
August | 8486334.97 | 0.572432E+09 | 334223.46 | 1163883.28 | 45475645.70 | 0.00 | 17057073.73 | 19135.62 | 0.48 |
September | 20282185.40 | 0.442897E+09 | 362617.07 | 2069818.03 | 65888438.82 | 4856.05 | 33595878.98 | 32270.20 | 0.48 |
October | 0.245593E+09 | 88738327.97 | 63655.67 | 5473686.59 | 11199619.67 | 79174808.99 | 0.428921E+09 | 19495.75 | 0.47 |
November | 0.353944E+09 | 3932074.31 | 70747.78 | 3612604.35 | 10696383.00 | 0.331668E+09 | 0.447225E+09 | 8744.77 | 0.47 |
December | 0.404192E+09 | 83320.11 | 0.00 | 1405658.53 | 873232.28 | 0.829178E+09 | 0.206902E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.247659E+10 | 0.206226E+10 | 1186201.00 | 43357546.67 | 0.174258E+09 | 0.271297E+10 | 0.311508E+10 | 124976.52 | 0.47 |
Minimum of Months | 8486334.97 | 81672.51 | 0.00 | 1163883.28 | 0.00 | 0.00 | 17057073.73 | 0.00 | 0.47 |
Maximum of Months | 0.441324E+09 | 0.623728E+09 | 362617.07 | 8127260.77 | 65888438.82 | 0.829178E+09 | 0.471646E+09 | 32270.20 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.566312E+10 | 12383149.07 | 0.00 | 0.127416E+09 | 133576.00 | 0.00 | 0.115598E+11 | 0.00 | 0.54 |
February | 0.102718E+11 | 1107535.81 | 0.00 | 42116900.49 | 0.00 | 0.00 | 0.832516E+10 | 0.00 | 0.54 |
March | 0.988571E+10 | 31263256.28 | 0.00 | 44386675.74 | 0.00 | 0.00 | 0.666888E+10 | 0.00 | 0.54 |
April | 0.193880E+10 | 0.649688E+09 | 0.00 | 57437237.10 | 0.00 | 0.00 | 0.574245E+10 | 0.00 | 0.54 |
May | 0.917807E+09 | 0.115552E+10 | 0.00 | 39710807.80 | 0.00 | 0.00 | 0.366365E+10 | 0.00 | 0.54 |
June | 12069774.15 | 0.276481E+10 | 0.00 | 36423467.39 | 0.00 | 0.00 | 0.132002E+10 | 0.00 | 0.54 |
July | 24978889.07 | 0.885949E+10 | 0.00 | 8236664.44 | 14476115.22 | 0.00 | 0.477673E+09 | 0.00 | 0.54 |
August | 418549.85 | 0.835461E+10 | 0.00 | 8721204.42 | 29428615.78 | 0.00 | 0.353030E+09 | 0.00 | 0.54 |
September | 36160395.56 | 0.689529E+10 | 0.00 | 15793693.64 | 9538400.22 | 0.00 | 0.706804E+09 | 0.00 | 0.54 |
October | 0.264387E+10 | 0.135636E+10 | 0.00 | 75888733.08 | 0.00 | 0.00 | 0.757500E+10 | 0.00 | 0.54 |
November | 0.527262E+10 | 70620862.99 | 0.00 | 99233019.94 | 0.128829E+09 | 0.00 | 0.100392E+11 | 0.00 | 0.54 |
December | 0.818749E+10 | 2853018.84 | 0.00 | 94236632.60 | 10118493.44 | 0.00 | 0.112684E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.448549E+11 | 0.301540E+11 | 0.00 | 0.649601E+09 | 0.192524E+09 | 0.00 | 0.677001E+11 | 0.00 | 0.54 |
Minimum of Months | 418549.85 | 1107535.81 | 0.00 | 8236664.44 | 0.00 | 0.00 | 0.353030E+09 | 0.00 | 0.54 |
Maximum of Months | 0.102718E+11 | 0.885949E+10 | 0.00 | 0.127416E+09 | 0.128829E+09 | 0.00 | 0.115598E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.484946E+10 | 981399.03 | 131237.24 | 48311649.19 | 11376451.24 | 0.624497E+09 | 0.118328E+11 | 31060.24 | 0.53 |
February | 0.609335E+10 | 1107838.66 | 0.00 | 35390012.60 | 0.00 | 0.239536E+09 | 0.122759E+11 | 0.00 | 0.54 |
March | 0.552010E+10 | 15560296.73 | 120376.74 | 57582703.79 | 15529078.14 | 0.351158E+09 | 0.106747E+11 | 62053.55 | 0.54 |
April | 0.195285E+10 | 0.364782E+09 | 1487691.41 | 68199419.59 | 0.283273E+09 | 5288918.50 | 0.571446E+10 | 323705.86 | 0.54 |
May | 0.115659E+10 | 0.916425E+09 | 555570.37 | 54035791.42 | 0.238707E+09 | 434900.04 | 0.341137E+10 | 151043.18 | 0.54 |
June | 0.372139E+09 | 0.252124E+10 | 813395.33 | 41390446.56 | 0.243493E+09 | 16996.51 | 0.955338E+09 | 19596.31 | 0.54 |
July | 0.123171E+09 | 0.776597E+10 | 2596896.40 | 10095707.19 | 0.110780E+10 | 0.00 | 0.377762E+09 | 21959.98 | 0.54 |
August | 0.115051E+09 | 0.697824E+10 | 2147665.41 | 9071976.33 | 0.140585E+10 | 0.00 | 0.238146E+09 | 97582.72 | 0.54 |
September | 0.279516E+09 | 0.522864E+10 | 3977806.52 | 17461408.31 | 0.167395E+10 | 87084.11 | 0.461901E+09 | 155501.05 | 0.54 |
October | 0.339504E+10 | 0.932697E+09 | 1510473.23 | 60366641.12 | 0.422307E+09 | 26395341.11 | 0.681578E+10 | 211794.34 | 0.54 |
November | 0.501449E+10 | 37570234.72 | 873828.43 | 46119292.43 | 0.160951E+09 | 0.413270E+09 | 0.994137E+10 | 109488.08 | 0.54 |
December | 0.553128E+10 | 354385.28 | 18629.93 | 27218361.72 | 12594085.28 | 0.357203E+10 | 0.104250E+11 | 7958.82 | 0.53 |
Annual Sum or Average | 0.344030E+11 | 0.247636E+11 | 14233571.00 | 0.475243E+09 | 0.557583E+10 | 0.523271E+10 | 0.731245E+11 | 1191744.14 | 0.54 |
Minimum of Months | 0.115051E+09 | 354385.28 | 0.00 | 9071976.33 | 0.00 | 0.00 | 0.238146E+09 | 0.00 | 0.53 |
Maximum of Months | 0.609335E+10 | 0.776597E+10 | 3977806.52 | 68199419.59 | 0.167395E+10 | 0.357203E+10 | 0.122759E+11 | 323705.86 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263331E+09 | 487544.78 | 9641.93 | 8925600.19 | 423128.84 | 0.219521E+09 | 0.787831E+09 | 2807.83 | 0.47 |
February | 0.345569E+09 | 81682.08 | 0.00 | 4678066.83 | 0.00 | 0.402294E+09 | 0.622114E+09 | 0.00 | 0.48 |
March | 0.330285E+09 | 2033656.02 | 5920.87 | 7040447.11 | 260795.99 | 0.230811E+09 | 0.656057E+09 | 5329.49 | 0.47 |
April | 0.117679E+09 | 46545776.84 | 0.00 | 10099803.36 | 1367639.33 | 265551.65 | 0.442692E+09 | 1871.83 | 0.47 |
May | 80799273.21 | 83316704.55 | 5853.61 | 7055967.74 | 1898404.19 | 23575.46 | 0.252938E+09 | 214.62 | 0.47 |
June | 26123712.25 | 0.201400E+09 | 0.00 | 5470048.93 | 2508033.15 | 0.00 | 69335493.49 | 0.00 | 0.48 |
July | 8819436.86 | 0.635806E+09 | 0.00 | 1324556.99 | 18659162.85 | 0.00 | 27534654.57 | 0.00 | 0.47 |
August | 8466153.90 | 0.585322E+09 | 14265.27 | 1136942.74 | 32995479.72 | 0.00 | 17107324.87 | 1693.72 | 0.48 |
September | 20115141.73 | 0.453411E+09 | 125902.00 | 2196785.26 | 55695491.54 | 1295.48 | 33646072.45 | 6884.74 | 0.48 |
October | 0.195349E+09 | 93700030.27 | 2968.07 | 8619568.81 | 6326346.30 | 25873761.91 | 0.529409E+09 | 3474.72 | 0.47 |
November | 0.278551E+09 | 4006020.97 | 73052.80 | 8088266.36 | 10625363.31 | 0.173274E+09 | 0.676669E+09 | 5236.23 | 0.47 |
December | 0.358421E+09 | 210413.54 | 0.00 | 5426651.18 | 746250.94 | 0.509600E+09 | 0.568399E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.203351E+10 | 0.210632E+10 | 237604.55 | 70062705.49 | 0.131506E+09 | 0.156166E+10 | 0.468373E+10 | 27513.19 | 0.47 |
Minimum of Months | 8466153.90 | 81682.08 | 0.00 | 1136942.74 | 0.00 | 0.00 | 17107324.87 | 0.00 | 0.47 |
Maximum of Months | 0.358421E+09 | 0.635806E+09 | 125902.00 | 10099803.36 | 55695491.54 | 0.509600E+09 | 0.787831E+09 | 6884.74 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.355649E+09 | 120662.57 | 8364.95 | 3392888.41 | 790166.57 | 0.473239E+09 | 0.447178E+09 | 3821.12 | 0.47 |
February | 0.447117E+09 | 81672.51 | 0.00 | 2089514.68 | 0.00 | 0.543240E+09 | 0.382048E+09 | 0.00 | 0.48 |
March | 0.392808E+09 | 1858039.57 | 2993.14 | 4914370.43 | 436143.62 | 0.311500E+09 | 0.514828E+09 | 8255.90 | 0.47 |
April | 0.118843E+09 | 46272901.44 | 5895.40 | 9139017.05 | 1628639.23 | 378372.73 | 0.442310E+09 | 2237.95 | 0.47 |
May | 80810380.91 | 83293128.28 | 5645.65 | 6930645.45 | 1911996.26 | 23572.70 | 0.253012E+09 | 421.86 | 0.47 |
June | 26002218.56 | 0.201455E+09 | 0.00 | 5553107.80 | 2428674.39 | 0.00 | 69362102.97 | 0.00 | 0.48 |
July | 8800316.80 | 0.635811E+09 | 0.00 | 1333248.23 | 18577783.85 | 0.00 | 27540668.78 | 0.00 | 0.47 |
August | 8465161.97 | 0.584857E+09 | 23238.99 | 1090633.47 | 33378049.38 | 0.00 | 17151496.55 | 2123.44 | 0.48 |
September | 20125325.65 | 0.451940E+09 | 123082.11 | 2048166.98 | 57111513.76 | 1295.33 | 33777950.51 | 5758.01 | 0.48 |
October | 0.240419E+09 | 92957145.91 | 12785.92 | 6033446.22 | 7043232.38 | 75466622.62 | 0.437243E+09 | 7934.85 | 0.47 |
November | 0.368955E+09 | 3917690.78 | 65739.86 | 3708806.82 | 10712904.92 | 0.345678E+09 | 0.418108E+09 | 11614.31 | 0.47 |
December | 0.407779E+09 | 26126.13 | 0.00 | 1514310.73 | 928466.07 | 0.773876E+09 | 0.258509E+09 | 1960.19 | 0.47 |
Annual Sum or Average | 0.247577E+10 | 0.210259E+10 | 247746.02 | 47748156.28 | 0.134948E+09 | 0.252340E+10 | 0.330107E+10 | 44127.64 | 0.47 |
Minimum of Months | 8465161.97 | 26126.13 | 0.00 | 1090633.47 | 0.00 | 0.00 | 17151496.55 | 0.00 | 0.47 |
Maximum of Months | 0.447117E+09 | 0.635811E+09 | 123082.11 | 9139017.05 | 57111513.76 | 0.773876E+09 | 0.514828E+09 | 11614.31 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238444E+11 | 0.00 | 0.00 | 0.00 | 95311.93 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.250243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.224084E+11 | 0.00 | 0.00 | 0.00 | 5175267.50 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.108581E+11 | 18333287.31 | 0.00 | 1086641.85 | 0.312421E+09 | 0.00 | 0.588473E+09 | 0.00 | 0.57 |
May | 0.578498E+10 | 0.180431E+09 | 0.00 | 5488883.76 | 0.592456E+09 | 0.00 | 0.200489E+10 | 0.00 | 0.56 |
June | 0.383948E+09 | 0.201516E+10 | 0.00 | 18297284.64 | 0.125283E+09 | 0.00 | 0.318951E+10 | 0.00 | 0.55 |
July | 0.178552E+09 | 0.343160E+10 | 0.00 | 9345403.85 | 0.505160E+09 | 0.00 | 0.148234E+10 | 0.00 | 0.53 |
August | 0.463961E+09 | 0.258213E+10 | 0.00 | 9890128.53 | 0.641660E+09 | 0.00 | 0.152932E+10 | 0.00 | 0.53 |
September | 0.110493E+10 | 0.194242E+10 | 0.00 | 8056565.47 | 0.976586E+09 | 0.00 | 0.204797E+10 | 0.00 | 0.54 |
October | 0.138691E+11 | 0.301574E+09 | 0.00 | 3137028.19 | 0.115411E+09 | 0.00 | 0.145259E+10 | 0.00 | 0.59 |
November | 0.218652E+11 | 0.00 | 0.00 | 0.00 | 8518771.97 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.263284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.152114E+12 | 0.104716E+11 | 0.00 | 55301936.30 | 0.328277E+10 | 0.00 | 0.122951E+11 | 0.00 | 0.57 |
Minimum of Months | 0.178552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.263284E+11 | 0.343160E+10 | 0.00 | 18297284.64 | 0.976586E+09 | 0.00 | 0.318951E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75955195.34 | 137963.16 | 2854.97 | 1752093.38 | 89705.24 | 0.100708E+09 | 0.141487E+09 | 257.47 | 0.47 |
February | 96750345.48 | 20420.52 | 0.00 | 761386.62 | 0.00 | 0.149264E+09 | 96888290.10 | 0.00 | 0.48 |
March | 93519564.40 | 502309.40 | 1196.27 | 1256470.25 | 72751.90 | 92480776.18 | 0.118792E+09 | 168.02 | 0.47 |
April | 33204062.22 | 11564108.50 | 0.00 | 2076676.11 | 411025.11 | 143567.76 | 0.107260E+09 | 3688.39 | 0.47 |
May | 20742607.78 | 20726141.18 | 1972.00 | 1476052.12 | 573328.67 | 16007.74 | 62969495.32 | 3852.40 | 0.47 |
June | 6792684.34 | 50111650.09 | 244.24 | 1171365.67 | 864953.31 | 2627.11 | 17265636.55 | 99.75 | 0.48 |
July | 2233523.22 | 0.156253E+09 | 78544.83 | 305653.04 | 7281995.07 | 56.20 | 6880429.64 | 3130.41 | 0.47 |
August | 2121832.35 | 0.143842E+09 | 70972.13 | 284863.81 | 10664184.45 | 0.00 | 4270909.22 | 6005.40 | 0.48 |
September | 5088382.85 | 0.111760E+09 | 96817.60 | 506674.66 | 15443891.47 | 2201.23 | 8392564.99 | 9203.01 | 0.48 |
October | 57664870.03 | 23077413.49 | 12999.33 | 1654410.54 | 1914578.23 | 27967757.05 | 0.102526E+09 | 3213.79 | 0.47 |
November | 75269641.08 | 1128561.80 | 16505.90 | 1596831.49 | 2531054.32 | 73722684.92 | 0.133556E+09 | 1296.30 | 0.47 |
December | 87660922.76 | 52603.38 | 0.00 | 1005849.69 | 186562.73 | 0.173850E+09 | 97944394.11 | 0.00 | 0.47 |
Annual Sum or Average | 0.557004E+09 | 0.519176E+09 | 282107.28 | 13848327.35 | 40034030.50 | 0.618158E+09 | 0.898232E+09 | 30914.94 | 0.47 |
Minimum of Months | 2121832.35 | 20420.52 | 0.00 | 284863.81 | 0.00 | 0.00 | 4270909.22 | 0.00 | 0.47 |
Maximum of Months | 96750345.48 | 0.156253E+09 | 96817.60 | 2076676.11 | 15443891.47 | 0.173850E+09 | 0.141487E+09 | 9203.01 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 87230084.83 | 83741.98 | 2671.47 | 647623.53 | 143899.74 | 0.172594E+09 | 59392891.56 | 440.61 | 0.47 |
February | 0.110525E+09 | 20418.13 | 0.00 | 305205.61 | 0.00 | 0.195716E+09 | 37076977.28 | 0.00 | 0.48 |
March | 99513946.70 | 444156.68 | 1735.35 | 818584.70 | 129861.11 | 0.118270E+09 | 87409916.27 | 604.92 | 0.47 |
April | 34318119.39 | 11428644.66 | 0.00 | 1849328.87 | 545085.88 | 509620.96 | 0.105990E+09 | 3687.96 | 0.47 |
May | 20759970.57 | 20695306.95 | 2195.47 | 1447155.25 | 601955.78 | 16005.87 | 62971048.36 | 3339.81 | 0.47 |
June | 6772116.37 | 50146752.78 | 332.06 | 1195791.68 | 823698.49 | 999.43 | 17260449.85 | 191.38 | 0.48 |
July | 2233519.30 | 0.156288E+09 | 84074.11 | 307396.26 | 7221555.27 | 56.19 | 6877586.69 | 3082.30 | 0.47 |
August | 2121583.74 | 0.143385E+09 | 80662.66 | 273279.20 | 11092974.14 | 0.00 | 4281960.05 | 6680.21 | 0.48 |
September | 5087786.67 | 0.110673E+09 | 90414.76 | 469971.66 | 16521928.93 | 2200.97 | 8428225.32 | 9202.01 | 0.48 |
October | 61656963.59 | 22130421.50 | 10669.35 | 1112400.52 | 2860434.98 | 47849210.13 | 79171930.57 | 3748.94 | 0.47 |
November | 89315515.96 | 939803.22 | 18312.33 | 676715.96 | 2717311.10 | 0.123811E+09 | 70309476.48 | 1560.81 | 0.47 |
December | 99533561.34 | 18316.74 | 0.00 | 261637.28 | 220821.36 | 0.234828E+09 | 25795858.29 | 0.00 | 0.47 |
Annual Sum or Average | 0.619068E+09 | 0.516254E+09 | 291067.55 | 9365090.53 | 42879526.80 | 0.893598E+09 | 0.564967E+09 | 32538.94 | 0.47 |
Minimum of Months | 2121583.74 | 18316.74 | 0.00 | 261637.28 | 0.00 | 0.00 | 4281960.05 | 0.00 | 0.47 |
Maximum of Months | 0.110525E+09 | 0.156288E+09 | 90414.76 | 1849328.87 | 16521928.93 | 0.234828E+09 | 0.105990E+09 | 9202.01 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.394917E+09 | 1276673.36 | 0.00 | 26951552.81 | 205975.72 | 60406727.67 | 0.157293E+10 | 0.00 | 0.54 |
February | 0.415521E+09 | 131191.42 | 0.00 | 12320900.15 | 0.00 | 0.262606E+09 | 0.151742E+10 | 0.00 | 0.54 |
March | 0.516157E+09 | 3301718.66 | 5190.77 | 12219241.23 | 392756.56 | 0.208866E+09 | 0.122896E+10 | 3574.10 | 0.54 |
April | 0.211366E+09 | 73720175.89 | 7424.75 | 11819399.29 | 3227316.21 | 900996.66 | 0.692587E+09 | 2897.42 | 0.54 |
May | 0.133373E+09 | 0.130957E+09 | 11909.37 | 7746259.84 | 5888082.12 | 104208.51 | 0.406170E+09 | 18479.80 | 0.54 |
June | 43805608.01 | 0.316987E+09 | 30829.67 | 5894412.50 | 10469349.63 | 13763.09 | 0.112391E+09 | 13238.69 | 0.54 |
July | 14424736.06 | 0.991906E+09 | 837937.41 | 1502468.61 | 58348061.04 | 361.07 | 44588953.06 | 59175.97 | 0.54 |
August | 13628986.43 | 0.918530E+09 | 675975.35 | 1497722.87 | 73868039.18 | 0.00 | 27773495.27 | 44569.58 | 0.54 |
September | 32691359.78 | 0.719000E+09 | 495783.20 | 3057971.57 | 98381070.54 | 2080.70 | 54126061.40 | 24226.88 | 0.54 |
October | 0.323489E+09 | 0.149550E+09 | 25689.72 | 15535794.55 | 11080939.00 | 6893462.04 | 0.873532E+09 | 8725.66 | 0.54 |
November | 0.399928E+09 | 7282976.37 | 100414.17 | 21762714.42 | 16231411.13 | 58123552.63 | 0.134568E+10 | 10733.19 | 0.54 |
December | 0.391901E+09 | 337949.88 | 0.00 | 21634603.72 | 1198570.30 | 0.322241E+09 | 0.158001E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.289120E+10 | 0.331298E+10 | 2191154.41 | 0.141943E+09 | 0.279292E+09 | 0.920157E+09 | 0.945616E+10 | 185621.29 | 0.54 |
Minimum of Months | 13628986.43 | 131191.42 | 0.00 | 1497722.87 | 0.00 | 0.00 | 27773495.27 | 0.00 | 0.54 |
Maximum of Months | 0.516157E+09 | 0.991906E+09 | 837937.41 | 26951552.81 | 98381070.54 | 0.322241E+09 | 0.158001E+10 | 59175.97 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.526880E+09 | 133916.01 | 0.00 | 90112423.95 | 0.00 | 0.00 | 0.413959E+11 | 0.00 | 4.74 |
February | 0.628881E+09 | 0.00 | 0.00 | 74818915.94 | 0.00 | 0.00 | 0.419098E+11 | 0.00 | 4.69 |
March | 0.307865E+09 | 7689985.16 | 0.00 | 86431473.28 | 0.00 | 0.00 | 0.397795E+11 | 0.00 | 4.96 |
April | 3950724.13 | 0.557468E+09 | 0.00 | 80711118.84 | 0.00 | 0.00 | 0.231789E+11 | 0.00 | 5.20 |
May | 0.00 | 0.136080E+10 | 0.00 | 72989144.44 | 0.00 | 0.00 | 0.167323E+11 | 0.00 | 5.22 |
June | 0.00 | 0.374755E+10 | 0.00 | 58092185.55 | 0.00 | 0.00 | 0.792630E+10 | 0.00 | 5.05 |
July | 0.00 | 0.736578E+10 | 0.00 | 32374751.45 | 0.00 | 0.00 | 0.364757E+10 | 0.00 | 4.92 |
August | 0.00 | 0.587285E+10 | 0.00 | 37970709.04 | 0.00 | 0.00 | 0.434281E+10 | 0.00 | 4.94 |
September | 0.00 | 0.541026E+10 | 0.00 | 42413412.47 | 0.00 | 0.00 | 0.681050E+10 | 0.00 | 5.00 |
October | 0.138043E+09 | 0.719538E+09 | 0.00 | 82612482.37 | 0.00 | 0.00 | 0.287132E+11 | 0.00 | 5.08 |
November | 0.327421E+09 | 11972244.06 | 0.00 | 83152039.38 | 0.00 | 0.00 | 0.382935E+11 | 0.00 | 4.82 |
December | 0.143593E+10 | 0.00 | 0.00 | 81660774.78 | 0.00 | 0.00 | 0.423042E+11 | 0.00 | 4.44 |
Annual Sum or Average | 0.336897E+10 | 0.250540E+11 | 0.00 | 0.823339E+09 | 0.00 | 0.00 | 0.295034E+12 | 0.00 | 4.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32374751.45 | 0.00 | 0.00 | 0.364757E+10 | 0.00 | 4.44 |
Maximum of Months | 0.143593E+10 | 0.736578E+10 | 0.00 | 90112423.95 | 0.00 | 0.00 | 0.423042E+11 | 0.00 | 5.22 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175334E+09 | 144044.34 | 0.00 | 0.105473E+09 | 0.00 | 0.00 | 0.453965E+11 | 0.00 | 5.16 |
February | 0.169178E+09 | 0.00 | 0.00 | 90695549.13 | 0.00 | 0.00 | 0.464073E+11 | 0.00 | 5.14 |
March | 69147659.51 | 8543161.72 | 0.00 | 0.100898E+09 | 0.00 | 0.00 | 0.435537E+11 | 0.00 | 5.40 |
April | 0.00 | 0.604384E+09 | 0.00 | 87873836.78 | 0.00 | 0.00 | 0.246699E+11 | 0.00 | 5.56 |
May | 0.00 | 0.146489E+10 | 0.00 | 77731121.66 | 0.00 | 0.00 | 0.176468E+11 | 0.00 | 5.56 |
June | 0.00 | 0.400273E+10 | 0.00 | 61152282.43 | 0.00 | 0.00 | 0.829241E+10 | 0.00 | 5.34 |
July | 0.00 | 0.783448E+10 | 0.00 | 34031828.93 | 0.00 | 0.00 | 0.381919E+10 | 0.00 | 5.21 |
August | 0.00 | 0.626678E+10 | 0.00 | 39948761.06 | 0.00 | 0.00 | 0.455203E+10 | 0.00 | 5.23 |
September | 0.00 | 0.576729E+10 | 0.00 | 44902044.07 | 0.00 | 0.00 | 0.715939E+10 | 0.00 | 5.30 |
October | 25180778.81 | 0.770557E+09 | 0.00 | 92027880.31 | 0.00 | 0.00 | 0.309500E+11 | 0.00 | 5.45 |
November | 0.101210E+09 | 12528654.53 | 0.00 | 97492342.34 | 0.00 | 0.00 | 0.418264E+11 | 0.00 | 5.23 |
December | 0.513419E+09 | 0.00 | 0.00 | 99446093.18 | 0.00 | 0.00 | 0.473287E+11 | 0.00 | 4.84 |
Annual Sum or Average | 0.105347E+10 | 0.267323E+11 | 0.00 | 0.931672E+09 | 0.00 | 0.00 | 0.321602E+12 | 0.00 | 5.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34031828.93 | 0.00 | 0.00 | 0.381919E+10 | 0.00 | 4.84 |
Maximum of Months | 0.513419E+09 | 0.783448E+10 | 0.00 | 0.105473E+09 | 0.00 | 0.00 | 0.473287E+11 | 0.00 | 5.56 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141584E+09 | 271824.72 | 0.00 | 0.144627E+09 | 0.00 | 0.00 | 0.540093E+11 | 0.00 | 22.35 |
February | 73973676.99 | 0.00 | 0.00 | 0.128379E+09 | 0.00 | 0.00 | 0.588087E+11 | 0.00 | 22.17 |
March | 32752106.36 | 14988583.14 | 0.00 | 0.136900E+09 | 0.00 | 0.00 | 0.508941E+11 | 0.00 | 22.73 |
April | 0.00 | 0.996342E+09 | 0.00 | 0.111284E+09 | 0.00 | 0.00 | 0.240350E+11 | 0.00 | 21.93 |
May | 0.00 | 0.232800E+10 | 0.00 | 91031246.28 | 0.00 | 0.00 | 0.156993E+11 | 0.00 | 21.33 |
June | 0.00 | 0.605226E+10 | 0.00 | 62964344.07 | 0.00 | 0.00 | 0.680878E+10 | 0.00 | 20.13 |
July | 0.00 | 0.107417E+11 | 0.00 | 33238632.51 | 0.00 | 0.00 | 0.315407E+10 | 0.00 | 19.90 |
August | 0.00 | 0.917367E+10 | 0.00 | 39262036.61 | 0.00 | 0.00 | 0.386489E+10 | 0.00 | 20.13 |
September | 0.00 | 0.788866E+10 | 0.00 | 49480645.10 | 0.00 | 0.00 | 0.642531E+10 | 0.00 | 20.47 |
October | 43811487.35 | 0.117152E+10 | 0.00 | 0.118612E+09 | 0.00 | 0.00 | 0.339545E+11 | 0.00 | 22.18 |
November | 98515720.65 | 22424751.62 | 0.00 | 0.134565E+09 | 0.00 | 0.00 | 0.497835E+11 | 0.00 | 22.45 |
December | 0.192939E+09 | 0.00 | 0.00 | 0.145283E+09 | 0.00 | 0.00 | 0.604787E+11 | 0.00 | 21.43 |
Annual Sum or Average | 0.583576E+09 | 0.383898E+11 | 0.00 | 0.119563E+10 | 0.00 | 0.00 | 0.367916E+12 | 0.00 | 21.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33238632.51 | 0.00 | 0.00 | 0.315407E+10 | 0.00 | 19.90 |
Maximum of Months | 0.192939E+09 | 0.107417E+11 | 0.00 | 0.145283E+09 | 0.00 | 0.00 | 0.604787E+11 | 0.00 | 22.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120435E+11 | 0.00 | 0.00 | 0.00 | 48140.80 | 0.00 | 0.00 | 0.00 | 1.14 |
February | 0.126395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
March | 0.113073E+11 | 0.00 | 0.00 | 25810.66 | 2613959.45 | 0.00 | 10871871.58 | 0.00 | 1.15 |
April | 0.474606E+10 | 0.175731E+09 | 0.00 | 3859665.36 | 11857807.84 | 0.00 | 0.103962E+10 | 0.00 | 1.11 |
May | 0.246328E+10 | 0.454001E+09 | 0.00 | 6301511.03 | 6823195.94 | 0.00 | 0.148710E+10 | 0.00 | 1.11 |
June | 0.266745E+09 | 0.145082E+10 | 0.00 | 8961620.77 | 265714.81 | 0.00 | 0.153601E+10 | 0.00 | 1.19 |
July | 0.147020E+09 | 0.236436E+10 | 0.00 | 5321553.59 | 26982935.07 | 0.00 | 0.695285E+09 | 0.00 | 1.14 |
August | 0.224597E+09 | 0.197103E+10 | 0.00 | 5263060.56 | 27295911.20 | 0.00 | 0.782465E+09 | 0.00 | 1.14 |
September | 0.542995E+09 | 0.148739E+10 | 0.00 | 5255807.33 | 0.181212E+09 | 0.00 | 0.105239E+10 | 0.00 | 1.12 |
October | 0.694859E+10 | 0.241140E+09 | 0.00 | 2555515.64 | 5753962.19 | 0.00 | 0.786112E+09 | 0.00 | 1.14 |
November | 0.110261E+11 | 0.00 | 0.00 | 85443.80 | 4302719.52 | 0.00 | 17574787.67 | 0.00 | 1.14 |
December | 0.132870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11133322.03 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.756426E+11 | 0.814447E+10 | 0.00 | 37629988.75 | 0.267157E+09 | 11133322.03 | 0.740743E+10 | 0.00 | 1.14 |
Minimum of Months | 0.147020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 0.132870E+11 | 0.236436E+10 | 0.00 | 8961620.77 | 0.181212E+09 | 11133322.03 | 0.153601E+10 | 0.00 | 1.19 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:42:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149985E+12 | 0.868282E+10 | 0.924349E+11 | 0.483368E+12 | 0.286173E+12 |
February | 0.186794E+12 | 0.866612E+10 | 0.105178E+12 | 0.480724E+12 | 0.108296E+12 |
March | 0.248613E+12 | 0.818301E+10 | 0.876214E+11 | 0.449480E+12 | 0.263727E+12 |
April | 0.295800E+12 | 0.324166E+10 | 0.294905E+11 | 0.184107E+12 | 0.669050E+12 |
May | 0.301298E+12 | 0.164021E+10 | 0.983032E+10 | 0.928755E+11 | 0.854115E+12 |
June | 0.315223E+12 | -882473917.6 | -0.247899E+11 | -0.471314E+11 | 0.110810E+13 |
July | 0.299456E+12 | -0.340194E+10 | -0.447186E+11 | -0.184785E+12 | 0.123299E+13 |
August | 0.251129E+12 | -0.276583E+10 | -0.366835E+11 | -0.146014E+12 | 0.120132E+13 |
September | 0.211807E+12 | -0.170186E+10 | -0.203944E+11 | -0.851864E+11 | 0.108993E+13 |
October | 0.191801E+12 | 0.450933E+10 | 0.468094E+11 | 0.261373E+12 | 0.602711E+12 |
November | 0.162932E+12 | 0.770238E+10 | 0.845299E+11 | 0.431535E+12 | 0.300542E+12 |
December | 0.118614E+12 | 0.106632E+11 | 0.119538E+12 | 0.585476E+12 | 0.185048E+12 |
Annual Sum or Average | 0.273345E+13 | 0.445366E+11 | 0.448846E+12 | 0.250582E+13 | 0.790200E+13 |
Minimum of Months | 0.118614E+12 | -0.340194E+10 | -0.447186E+11 | -0.184785E+12 | 0.108296E+12 |
Maximum of Months | 0.315223E+12 | 0.106632E+11 | 0.119538E+12 | 0.585476E+12 | 0.123299E+13 |