Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:41:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13566.29 | 1195.76 | 1195.76 |
Net Site Energy | 13566.29 | 1195.76 | 1195.76 |
Total Source Energy | 25235.15 | 2224.29 | 2224.29 |
Net Source Energy | 25235.15 | 2224.29 | 2224.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3159.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 587.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 866.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 261.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 563.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 86.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 229.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 3563.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5054.87 | 8511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3159.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 587.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 866.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 261.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 563.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 86.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 229.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 3563.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3159.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 587.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 866.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 261.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 563.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 86.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 229.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 3563.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 117.07 | 592.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 229.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 445.55 | 750.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 117.07 | 592.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 229.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 445.55 | 750.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5054.871 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5054.871 | 100.00 |
Total On-Site and Utility Electric Sources | 5054.871 | 100.00 |
Total Electricity End Uses | 5054.871 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 124.37 | 2.34 |
Air to Air Heat Recovery for Heating | 5179.71 | 97.66 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5304.08 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 590.00 |
Time Setpoint Not Met During Occupied Cooling | 351.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8033.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.3255 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.5208 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.7005 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 11.5174 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.6875 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 9.7951 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.3255 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.5208 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.7005 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 11.5174 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.6875 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 9.7951 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 13.0243 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 5.0165 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-18:10 | 05-JAN-21:40 | - | - | - | - | - | - | - | - | - | - | 12-JAN-21:10 |
Heating | 0.00 | 843541.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 206113.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 58770.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31786.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30434.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5589.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4729.65 | 309329.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2416.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 427352.72 | 1227994.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 843541.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 206113.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 58770.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 30434.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5589.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4729.65 | 309329.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1093.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3424.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1859.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2743.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 828.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2058.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1784.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 274.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 725.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 3862.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16008.78 | 9226.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 301.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 163.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 241.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 157.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 63.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 340.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1411.05 | 813.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 301.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 163.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 241.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 157.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 63.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 340.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1411.05 | 813.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.81 | 0.536854 | 0.489000 | 1.37 | 1.00 | 0.500000 | 0.000710 | 0.000073 | 1.37 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.464861 | 0.109943 | 0.489000 | 0.227317 | 0.489000 | 0.500000 | 0.003465 | 0.000048 | 0.227317 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.249623 | 0.237092 | 0.489000 | 0.122066 | 0.632246 | 0.500000 | 0.001607 | 0.000017 | 0.122066 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.183365 | 0.682536 | 0.489000 | 0.089666 | 1.00 | 0.500000 | 0.000558 | 0.000027 | 0.112554 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.121430 | 0.594638 | 0.489000 | 0.059379 | 1.00 | 0.500000 | 0.000641 | 0.000020 | 0.083135 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.40 | 0.069341 | 0.489000 | 1.66 | 0.489000 | 0.500000 | 0.021804 | 0.000103 | 1.66 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.83 | 0.078631 | 0.489000 | 0.894977 | 0.489000 | 0.500000 | 0.004845 | 0.000137 | 0.894977 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.23 | 0.190685 | 0.489000 | 2.56 | 0.508493 | 0.500000 | 0.001998 | 0.000333 | 2.56 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.72 | 0.691611 | 0.489000 | 0.839196 | 1.00 | 0.500000 | 0.000551 | 0.000167 | 0.839196 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.25 | 0.112182 | 0.489000 | 1.10 | 0.489000 | 0.500000 | 0.003396 | 0.000131 | 1.10 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.36 | 0.107035 | 0.489000 | 1.15 | 0.489000 | 0.500000 | 0.003560 | 0.000135 | 1.15 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.40 | 0.059018 | 0.489000 | 1.17 | 0.489000 | 0.500000 | 0.011611 | 0.000090 | 1.17 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.836731 | 0.375317 | 0.489000 | 0.409161 | 1.00 | 0.500000 | 0.001015 | 0.000104 | 0.434365 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8305.87 | 0.000073 | 174.98 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5510.28 | 0.000048 | 143.88 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1992.33 | 0.000017 | 47.05 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3085.11 | 0.000027 | 84.19 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2278.84 | 0.000020 | 62.19 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11757.16 | 0.000103 | 250.33 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15603.61 | 0.000137 | 373.41 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 38035.68 | 0.000333 | 882.99 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 9955.44 | 0.000087 | 284.49 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 9964.77 | 0.000087 | 284.75 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 56334.12 | 0.000493 | 1609.79 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 56524.55 | 0.000495 | 1615.23 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 9974.98 | 0.000087 | 285.04 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 9984.31 | 0.000087 | 285.31 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 19136.05 | 0.000167 | 490.19 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2974.53 | 0.000026 | 85.00 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2974.83 | 0.000026 | 85.01 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 14193.95 | 0.000124 | 405.59 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14951.80 | 0.000131 | 341.89 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15400.42 | 0.000135 | 351.20 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10254.66 | 0.000090 | 222.26 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11907.69 | 0.000104 | 324.98 |
VAV WITH REHEAT HEATING COIL | 407585.11 | 0.003566 | 5672.67 |
FLR_3_DOAS HEATING COIL | 35250.36 | 0.000308 | 490.61 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.36 | 0.000087 | 0.000527 |
ROOM_2_FLR_3 FAN COIL | 1.30 | 0.000087 | 0.000504 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.79 | 0.000493 | 0.003342 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.58 | 0.000495 | 0.002668 |
ROOM_5_FLR_3 FAN COIL | 1.24 | 0.000087 | 0.000480 |
ROOM_6_FLR_3 FAN COIL | 1.17 | 0.000087 | 0.000457 |
ROOM_1_FLR_6 FAN COIL | 0.354178 | 0.000026 | 0.000137 |
ROOM_2_FLR_6 FAN COIL | 0.336307 | 0.000026 | 0.000130 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.74 | 0.000124 | 0.000680 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.36 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.30 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.79 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.58 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.24 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.17 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.354178 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.336307 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.74 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008622 | 12.80 | 0.008500 | 0.000527 | 1.36 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008628 | 12.80 | 0.008500 | 0.000504 | 1.30 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008554 | 12.80 | 0.008500 | 0.003342 | 8.79 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008792 | 12.80 | 0.008500 | 0.002668 | 6.58 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008635 | 12.80 | 0.008500 | 0.000480 | 1.24 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008642 | 12.80 | 0.008500 | 0.000457 | 1.17 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008617 | 12.80 | 0.008500 | 0.000137 | 0.354178 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008623 | 12.80 | 0.008500 | 0.000130 | 0.336307 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008658 | 12.80 | 0.008500 | 0.000680 | 1.74 | |
VAV WITH REHEAT COOLING COIL | 26.99 | 6.70 | 0.011150 | 10.91 | 0.008500 | 0.022659 | 23.72 | 634386.72 |
FLR_3_DOAS COOLING COIL | 30.10 | 6.70 | 0.012726 | 11.90 | 0.008500 | 0.002484 | 2.05 | 69550.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.93 | 11.66 | 23.85 | 11.66 | 23.72 | 23.72 | 0.300000 | 0.491809 | 23.72 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.72 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.72 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.022659 | 0.000021 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003566 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002484 | 0.000192 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000308 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.034069 | 5562.41 | |
HEATSYS1 PUMP | 0.006771 | 2039.05 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.006771 | 0.812488 |
COOLSYS1 | 0.034069 | 4.09 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 773936.43 | 773936.43 | 0.006771 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.034069 | 3851.04 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.034069 | 953838.04 | 954481.79 | 108.81 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.325 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.705 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.521 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.901 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.700 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.390 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 11.517 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.897 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 20432.332 | 10.325 | 191.855 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20432.332 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.656 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.656 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.385 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.385 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 742.517 | 4.521 | 279.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 742.517 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 729.693 | 7.700 | 357.693 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 729.693 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2175.192 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2175.192 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 12673.066 | 9.688 | 30.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12673.066 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.470 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.470 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.5913 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | 0.57998040E-15 | -0.30968906E-15 | -0.16543531E-09 | -0.94394381E-17 |
29 | 8 | 0.24079056E-07 | 0.80583727E-13 | 0.40057412E-03 | -0.27378716E-09 |
30 | 7 | -0.12920082E-01 | 0.41010748E-08 | -0.24062383E-01 | 0.14690605E-03 |
31 | 6 | 0.42378547 | 0.14160748E-05 | 0.48776087 | -0.49650686E-02 |
32 | 5 | -5.3704470 | 0.52534619E-04 | -4.5614765 | 0.65414341E-01 |
33 | 4 | 33.798395 | 0.42724899E-03 | 21.909926 | -0.43268566 |
34 | 3 | -112.91846 | 0.92631763E-03 | -56.552255 | 1.5396438 |
35 | 2 | 198.80798 | 0.51863526E-03 | 78.726696 | -2.9273457 |
36 | 1 | -171.78376 | 0.55128408E-04 | -55.503401 | 2.7564403 |
37 | 0 | 57.057407 | 0.31226006E-06 | 15.518392 | |
38 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
39 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
40 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
41 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
42 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
43 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
44 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
45 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
46 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
47 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
48 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
49 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
50 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
51 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
52 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
53 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
54 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
55 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
56 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
57 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
58 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
59 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
60 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
61 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
62 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
63 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
64 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
65 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
66 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
67 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
68 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
69 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
70 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
71 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
72 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
73 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
74 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
75 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
76 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
77 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
103 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
104 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
105 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
106 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
107 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
108 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
109 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
110 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
111 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
112 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
113 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
114 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
115 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
116 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
117 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
118 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
119 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
120 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
121 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
122 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
123 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
124 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
125 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
126 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
127 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
128 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
129 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
130 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
131 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
132 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
133 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.377_SHGC_0.45 | 37 | 1 | VerySmooth | 2.142 | 2.142 | 1.000 | 0.451 | ||
2 | RESWINDOW_U_0.377_SHGC_0.45 | 38 | 1 | VerySmooth | 2.142 | 2.142 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.48929E-002 | 0.36619 | 0.43221 | 0.43221 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.11849 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.48929E-002 | 0.36619 | 0.43221 | 0.43221 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.11849 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1899 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1095 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.2170 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1276 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1259 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 5.1187E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.2070E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.7298E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2163 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1307 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2480 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1518 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1392 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 6.3753E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.8462E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.3647E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.7877E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.7663E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.6897E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.0957E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.5066E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3987E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 5.1255E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.8174E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.7877E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.7663E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.6897E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.0957E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.5066E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3987E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 5.1255E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.8174E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 37044.04242 | 37044.04242 | 2.80871 | 2.80871 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 25.03667 | 1.27170E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1357.34198 | 1357.34198 | 6.07129E-002 | 0.85446 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6130.25517 | 6130.25517 | 0.46486 | 0.46486 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4361.61988 | 4361.61988 | 0.19507 | 0.19507 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3291.85164 | 3291.85164 | 0.24962 | 0.24962 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1375.44050 | 1375.44050 | 6.15199E-002 | 9.17347E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2418.60183 | 2418.60183 | 0.18337 | 0.18337 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2516.46251 | 2516.46251 | 0.11255 | 0.11255 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1601.65493 | 1601.65493 | 0.12143 | 0.12143 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1858.71247 | 1858.71247 | 8.31349E-002 | 8.31349E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44882.27569 | 44882.27569 | 3.40311 | 3.40311 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 3352.41249 | 3352.41249 | 0.14993 | 0.14993 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 24116.27925 | 24116.27925 | 1.83022 | 1.83022 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 11080.36101 | 11080.36101 | 0.49557 | 0.67639 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 68919.66473 | 68919.66473 | 5.22767 | 5.22767 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 25115.51392 | 25115.51392 | 1.12335 | 1.89399 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 13322.35273 | 13322.35273 | 1.36119 | 1.36119 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 9955.43592 | 9955.43592 | 0.44786 | 0.44786 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12703.94257 | 12703.94257 | 1.29800 | 1.29800 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 9964.76805 | 9964.76805 | 0.44828 | 0.44828 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 85994.81511 | 85994.81511 | 8.78575 | 8.78575 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 56334.12291 | 56334.12291 | 2.53444 | 2.53444 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 64417.00714 | 64417.00714 | 6.58175 | 6.58175 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 56524.55193 | 56524.55193 | 2.54301 | 2.54301 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 12094.60621 | 12094.60621 | 1.23575 | 1.23575 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 9974.97652 | 9974.97652 | 0.44874 | 0.44874 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 11480.05771 | 11480.05771 | 1.17296 | 1.17296 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 9984.30688 | 9984.30688 | 0.44916 | 0.44916 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 22634.62198 | 22634.62198 | 1.71615 | 1.71615 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 14893.24557 | 14893.24557 | 0.66615 | 0.66615 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3466.44335 | 3466.44335 | 0.35418 | 0.35418 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2974.52981 | 2974.52981 | 0.13381 | 0.13381 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3291.53823 | 3291.53823 | 0.33631 | 0.33631 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2974.83440 | 2974.83440 | 0.13383 | 0.13383 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 17013.91868 | 17013.91868 | 1.73839 | 1.73839 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 14193.94857 | 14193.94857 | 0.63855 | 0.63855 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29675.08842 | 29675.08842 | 2.25279 | 2.25279 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 9382.13480 | 9382.13480 | 0.41964 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31102.50007 | 31102.50007 | 2.36111 | 2.36111 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 9562.86829 | 9562.86829 | 0.42772 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31558.59349 | 31558.59349 | 2.39900 | 2.39900 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 25.03667 | 1.27170E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 4332.20356 | 4332.20356 | 0.19374 | 0.36735 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11035.84876 | 11035.84876 | 0.83673 | 0.83673 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9711.26512 | 9711.26512 | 0.43436 | 0.43436 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 390311.12 | 23.71852 | 23.71852 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 452560.28 | 7.90073 | 7.90073 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 41147.75 | 21.30425 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 117497.06 | 7.77768 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.80871 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53685 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.37346 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.09690E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.26634E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.37346 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8305.86781 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.26634E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 174.97631 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.46486 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10994 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22732 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46542E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.82063E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22732 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5510.27657 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.82063E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.87840 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24962 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23709 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12207 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63225 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60697E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74298E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12207 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1992.32797 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74298E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.04735 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18337 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68254 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.96655E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.58212E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.69899E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11255 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3085.11412 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69899E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.19337 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.12143 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59464 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.93790E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.40726E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99363E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.31349E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2278.84055 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99363E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 62.19116 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40311 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.93406E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.66412 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18038E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02857E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.66412 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11757.15689 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02857E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 250.32838 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.83022 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.86315E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.89498 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.84539E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36507E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.89498 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15603.61347 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36507E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 373.40627 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.22767 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19069 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.55633 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50849 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99806E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.32753E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.55633 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38035.68090 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.32753E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 882.98855 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.36119 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.36119 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.70945E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.27411E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70753 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62187E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.27411E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.36119 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9955.43592 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.70945E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 284.48552 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.29800 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.29800 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.71761E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.03698E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70752 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62752E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.03698E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.29800 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9964.76805 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.71761E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 284.75212 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.78575 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.78575 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.92835E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.34222E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70819 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55429E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.34222E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.78575 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 56334.12291 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.92835E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1609.79415 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.58175 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.58175 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.94501E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.66754E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70728 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.79220E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.66754E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.58175 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 56524.55193 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.94501E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1615.23463 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23575 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.23575 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.72654E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.80494E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70750 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63491E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.80494E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23575 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9974.97652 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.72654E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 285.04377 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.17296 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.17296 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.73471E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.56980E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70749 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64224E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.56980E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.17296 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9984.30688 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.73471E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 285.31032 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.71615 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69161 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83920 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.50888E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67410E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83920 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19136.04622 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67410E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 490.18536 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.35418 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.35418 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.60225E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.37059E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70754 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61723E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.37059E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.35418 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2974.52981 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.60225E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 84.99638 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33631 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33631 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.60251E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.30353E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70753 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62318E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.30353E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33631 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2974.83440 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.60251E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 85.00508 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.73839 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.73839 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.24175E-004 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.80137E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70737 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65803E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.80137E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.73839 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 14193.94857 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24175E-004 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 405.58712 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25279 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11218 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.10161 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48900 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.39626E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30805E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10161 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14951.80246 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30805E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 341.88704 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.36111 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10704 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15458 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48900 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.55957E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34730E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15458 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15400.41534 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34730E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 351.20140 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39900 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.90180E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17311 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48900 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16113E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.97122E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17311 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10254.65652 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.97122E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 222.26179 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83673 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37532 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40916 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01514E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04174E-004 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43436 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11907.68919 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04174E-004 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.98175 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.92739 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66498 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.85477 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66498 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.71852 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.71852 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49181 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.71852 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.71852 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.99398 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90665 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11495E-002 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 634386.71885 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.26588E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.71852 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 407585.10578 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.56573E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5672.67077 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.71852 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26588E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.10157E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.56573E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.10000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89838 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.27259E-002 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 69550.08568 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.48417E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 35250.35631 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08385E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 490.60592 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.48417E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.91690E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.08385E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.40689E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5562.40785 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.77073E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.81249 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.77073E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2039.04758 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 773936.42510 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 773936.43000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.77073E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.40689E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.08827 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.40689E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3851.04257 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.40689E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 953838.04193 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 954481.79000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 108.81092 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8348.53 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5532.49 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2001.43 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3097.03 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2287.65 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11816.98 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15673.06 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 38212.09 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 10723.30 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 10733.35 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 60679.84 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 60884.93 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 10744.34 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 10754.39 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 19215.91 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 3203.88 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 3204.21 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 15288.42 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 15022.11 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15473.02 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10306.06 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11953.69 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 233809.23 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 20221.20 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 22810.66 | 18084.80 | 4725.86 | 0.79 | 2743.53 | 27.83 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 21773.30 | 17255.17 | 4518.14 | 0.79 | 2618.15 | 26.55 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 145484.28 | 115927.74 | 29556.54 | 0.80 | 17548.64 | 177.99 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 113526.15 | 88923.05 | 24603.10 | 0.78 | 13565.19 | 137.59 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 20755.69 | 16439.78 | 4315.91 | 0.79 | 2495.02 | 25.31 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 19726.19 | 15615.95 | 4110.23 | 0.79 | 2370.56 | 24.04 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5930.45 | 4703.41 | 1227.04 | 0.79 | 713.42 | 7.24 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5637.10 | 4468.78 | 1168.31 | 0.79 | 677.96 | 6.88 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 29315.17 | 23180.30 | 6134.87 | 0.79 | 3520.65 | 35.71 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 657842.17 | 432798.73 | 225043.44 | 0.66 | 81071.89 | 822.28 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 60010.76 | 38734.94 | 21275.82 | 0.65 | 6954.16 | 70.53 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.377_SHGC_0.45 | N/A | 2.142 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 3.8017365453E-002 | 8.6892579046E-002 | Pass | Pass | 5.8375581980E-002 | 0.3353525013 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.3757391170E-002 | 0.1577694068 | Pass | Pass | 0.3134242565 | 1.6413194228 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.9527874431E-002 | 9.7325682427E-002 | Pass | Pass | 0.2245801244 | 0.5800584629 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9200106042E-002 | 4.8429073197E-002 | Pass | Pass | 3.5222485756E-002 | 0.1922970314 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2859318659E-002 | 5.3093249722E-002 | Pass | Pass | 2.0495772585E-002 | 0.1293756924 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1773344050 | 0.5411380616 | Pass | Pass | 2.6381082236E-002 | 6.6401651573E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.4425681747E-002 | 0.1322885634 | Pass | Pass | 6.8379654968E-002 | 0.1504323663 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4075558905E-002 | 9.2204560634E-002 | Pass | Pass | 5.9537052172E-002 | 0.1431651392 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.7161926602E-002 | 0.3452883028 | Pass | Pass | 0.5863123998 | 5.6005863681 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4173194112E-002 | 0.3441063704 | Pass | Pass | 6.2221367255E-002 | 0.1930954260 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.6441344664E-002 | 7.9077436380E-002 | Pass | Pass | 0.1484665881 | 0.4215026348 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.5838899365E-002 | 0.2358617889 | Pass | Pass | 0.2333579581 | 1.1507512557 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2705348286E-002 | 0.3390681775 | Pass | Pass | 0.1213725907 | 0.4843972785 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4523863419E-002 | 0.3337333405 | Pass | Pass | 6.1691017783E-002 | 0.1898059042 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.2653069506E-002 | 5.3252068928E-002 | Pass | Pass | 5.3322834557E-002 | 0.1080136816 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2698451202E-002 | 0.3564933255 | Pass | Pass | 9.0653053511E-002 | 0.2186319026 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.4294668805E-002 | 0.3402616433 | Pass | Pass | 4.7062299382E-002 | 0.1464190945 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2790344333E-002 | 0.3177906678 | Pass | Pass | 0.2894036422 | 0.8818218579 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.6684473860E-002 | 0.1635049165 | Pass | Pass | 2.0809293476E-002 | 5.1176891498E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.8608546767E-002 | 0.1594517919 | Pass | Pass | 1.7122388535E-002 | 4.0100542654E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1302303832 | 0.3514088395 | Pass | Pass | 2.6386747659E-002 | 4.9742092134E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.6841724287E-002 | 8.0012245189E-002 | Pass | Pass | 5.4538617785E-002 | 0.2444744992 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3880.69 | 204.56 | 2393.78 | 10315.04 | 3408.29 | 20202.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.142 | 0.451 | 0.497 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.142 | 0.451 | 0.497 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.142 | 0.451 | 0.497 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.142 | 0.451 | 0.497 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.142 | 0.451 | 0.497 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.142 | 0.451 | 0.497 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.142 | 0.451 | 0.497 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.142 | 0.451 | 0.497 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.142 | 0.451 | 0.497 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.142 | 0.451 | 0.497 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.142 | 0.451 | 0.497 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.142 | 0.451 | 0.497 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.142 | 0.451 | 0.497 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.142 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.142 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.142 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.142 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.142 | 0.451 | 0.497 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.142 | 0.451 | 0.497 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.142 | 0.451 | 0.497 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.142 | 0.451 | 0.497 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.377_SHGC_0.45 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.142 | 0.451 | 0.497 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.142 | 0.451 | 0.497 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.142 | 0.451 | 0.497 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.142 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.142 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.142 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.142 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.142 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.377_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.142 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.142 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 432.95 | 2.142 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.142 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.3255 | 1978.83 | 20432.33 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 188.94 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.5625 | 67.07 | 909.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.76 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.5625 | 77.67 | 1053.39 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 10.14 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.5208 | 164.24 | 742.52 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.17 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.7005 | 94.76 | 729.69 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 4.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 11.5174 | 188.86 | 2175.19 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.02 | 0.0000 | Y | 15.93 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.6875 | 1308.19 | 12673.07 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.49 | 0.0000 | Y | 98.70 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 9.7951 | 1863.81 | 18256.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.45 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 9.7951 | 1864.32 | 18261.31 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.49 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.23 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.18 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 9.7951 | 220.77 | 2162.52 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 15.45 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.94 | 0.0000 | Y | 35.09 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.94 | 0.0000 | Y | 35.09 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 13.0243 | 103.30 | 1345.47 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 9.4981 | 11345.29 | 107758.18 | 493.87 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.52 | 83.52 | 261.66 | |
Exterior Lighting Total | 16690.39 | 261.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 773936.43 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 954481.79 | 2.96 | 954649.56 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 14766.39 | 22810.66 | 18084.80 | 4725.86 | 0.79 | - | 2743.53 | 27.83 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 14102.46 | 21773.30 | 17255.17 | 4518.14 | 0.79 | - | 2618.15 | 26.55 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 93575.02 | 145484.28 | 115927.74 | 29556.54 | 0.80 | - | 17548.64 | 177.99 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 74685.41 | 113526.15 | 88923.05 | 24603.10 | 0.78 | - | 13565.19 | 137.59 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13452.82 | 20755.69 | 16439.78 | 4315.91 | 0.79 | - | 2495.02 | 25.31 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12794.46 | 19726.19 | 15615.95 | 4110.23 | 0.79 | - | 2370.56 | 24.04 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3837.36 | 5930.45 | 4703.41 | 1227.04 | 0.79 | - | 713.42 | 7.24 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3649.61 | 5637.10 | 4468.78 | 1168.31 | 0.79 | - | 677.96 | 6.88 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 19042.39 | 29315.17 | 23180.30 | 6134.87 | 0.79 | - | 3520.65 | 35.71 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 634386.72 | 657842.17 | 432798.73 | 225043.44 | 0.66 | - | 81071.89 | 822.28 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 69550.09 | 60010.76 | 38734.94 | 21275.82 | 0.65 | - | 6954.16 | 70.53 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8305.87 | 8348.53 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5510.28 | 5532.49 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1992.33 | 2001.43 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3085.11 | 3097.03 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2278.84 | 2287.65 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11757.16 | 11816.98 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15603.61 | 15673.06 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 38035.68 | 38212.09 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9955.44 | 10723.30 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9964.77 | 10733.35 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 56334.12 | 60679.84 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 56524.55 | 60884.93 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9974.98 | 10744.34 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9984.31 | 10754.39 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19136.05 | 19215.91 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2974.53 | 3203.88 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2974.83 | 3204.21 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 14193.95 | 15288.42 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14951.80 | 15022.11 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15400.42 | 15473.02 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10254.66 | 10306.06 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11907.69 | 11953.69 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 407585.11 | 233809.23 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 35250.36 | 20221.20 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.36 | 957.78 | 703.64 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.30 | 913.32 | 703.64 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.79 | 6181.97 | 703.64 | 1.00 | 0.94 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.58 | 4631.16 | 703.64 | 1.00 | 0.95 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.24 | 869.52 | 703.64 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 825.34 | 703.64 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.35 | 249.21 | 703.64 | 1.00 | 1.61 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.34 | 236.64 | 703.64 | 1.00 | 1.64 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.74 | 1223.20 | 703.64 | 1.00 | 1.09 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.72 | 53144.64 | 2240.64 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.034069 | 5562.41 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.006771 | 2039.05 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.034069 | 3851.04 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 37044.04 | 37044.04 | 18.72 | 2.809 | 2.809 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00915 | 25.04 | 0.01272 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6130.26 | 6130.26 | 91.40 | 0.465 | 0.465 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00897 | 29.79 | 0.01273 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3291.85 | 3291.85 | 42.38 | 0.250 | 0.250 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00941 | 29.85 | 0.01273 | 0.092 | 0.00 |
MECH_FLR_1 | 2418.60 | 2418.60 | 14.73 | 0.183 | 0.183 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00893 | 29.98 | 0.01273 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1601.65 | 1601.65 | 16.90 | 0.121 | 0.121 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00894 | 30.10 | 0.01273 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44882.28 | 44882.28 | 575.12 | 3.403 | 3.403 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00856 | 30.10 | 0.01273 | 0.000 | 0.00 |
CAFE_FLR_1 | 24116.28 | 24116.28 | 127.69 | 1.830 | 1.830 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00987 | 29.79 | 0.01273 | 0.676 | 0.00 |
LOBBY_FLR_1 | 68919.66 | 68919.66 | 52.68 | 5.228 | 5.228 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00992 | 29.89 | 0.01273 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 13322.35 | 13322.35 | 341.41 | 1.361 | 1.361 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00862 | 28.36 | 0.01272 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12703.94 | 12703.94 | 325.60 | 1.298 | 1.298 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00863 | 27.95 | 0.01272 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 85994.82 | 85994.82 | 3506.58 | 8.786 | 8.786 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00855 | 29.89 | 0.01273 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 64417.01 | 64417.01 | 2625.99 | 6.582 | 6.582 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 21.11 | 21.11 | 0.00879 | 24.81 | 0.01272 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 12094.61 | 12094.61 | 309.94 | 1.236 | 1.236 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00863 | 25.39 | 0.01272 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 11480.06 | 11480.06 | 294.23 | 1.173 | 1.173 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00864 | 23.63 | 0.01271 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 22634.62 | 22634.62 | 58.13 | 1.716 | 1.716 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00940 | 30.10 | 0.01273 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3466.44 | 3466.44 | 88.83 | 0.354 | 0.354 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00862 | 28.36 | 0.01272 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3291.54 | 3291.54 | 84.36 | 0.336 | 0.336 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00862 | 27.95 | 0.01272 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17013.92 | 17013.92 | 693.58 | 1.738 | 1.738 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00866 | 29.89 | 0.01273 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29675.09 | 29675.09 | 89.48 | 2.253 | 2.253 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01042 | 30.10 | 0.01273 | 1.188 | 0.00 |
DINING_FLR_6 | 31102.50 | 31102.50 | 93.78 | 2.361 | 2.361 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01033 | 30.10 | 0.01273 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31558.59 | 31558.59 | 305.49 | 2.399 | 2.399 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.00998 | 25.04 | 0.01272 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11035.85 | 11035.85 | 26.78 | 0.837 | 0.837 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00901 | 30.10 | 0.01273 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1357.34 | 1357.34 | 0.69 | 0.061 | 0.854 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | -32.70 | 0.00018 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4361.62 | 4361.62 | 65.03 | 0.195 | 0.195 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00755 | -32.70 | 0.00018 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1375.44 | 1375.44 | 17.71 | 0.062 | 0.092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00745 | -32.70 | 0.00018 | 0.092 | 0.00 |
MECH_FLR_1 | 2516.46 | 2516.46 | 15.32 | 0.113 | 0.113 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00731 | -32.70 | 0.00018 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1858.71 | 1858.71 | 19.62 | 0.083 | 0.083 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00745 | -32.70 | 0.00018 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 3352.41 | 3352.41 | 42.96 | 0.150 | 0.150 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00729 | -32.70 | 0.00018 | 0.000 | 0.00 |
CAFE_FLR_1 | 11080.36 | 11080.36 | 58.67 | 0.496 | 0.676 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00760 | -32.70 | 0.00018 | 0.676 | 0.00 |
LOBBY_FLR_1 | 25115.51 | 25115.51 | 19.20 | 1.123 | 1.894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00751 | -32.70 | 0.00018 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9955.44 | 9955.44 | 255.12 | 0.448 | 0.448 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00754 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9964.77 | 9964.77 | 255.39 | 0.448 | 0.448 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00754 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 56334.12 | 56334.12 | 2297.12 | 2.534 | 2.534 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 56524.55 | 56524.55 | 2304.25 | 2.543 | 2.543 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9974.98 | 9974.98 | 255.62 | 0.449 | 0.449 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00754 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9984.31 | 9984.31 | 255.89 | 0.449 | 0.449 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -32.70 | 0.00018 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 14893.25 | 14893.25 | 38.25 | 0.666 | 0.666 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00763 | -32.70 | 0.00018 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2974.53 | 2974.53 | 76.23 | 0.134 | 0.134 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2974.83 | 2974.83 | 76.24 | 0.134 | 0.134 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14193.95 | 14193.95 | 578.62 | 0.639 | 0.639 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00763 | -32.70 | 0.00018 | 0.099 | 0.00 |
BANQUET_FLR_6 | 9382.13 | 9382.13 | 28.29 | 0.420 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00770 | -32.70 | 0.00018 | 1.188 | 0.00 |
DINING_FLR_6 | 9562.87 | 9562.87 | 28.83 | 0.428 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00770 | -32.70 | 0.00018 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 4332.20 | 4332.20 | 41.94 | 0.194 | 0.367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00719 | -32.70 | 0.00018 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9711.27 | 9711.27 | 23.56 | 0.434 | 0.434 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -32.70 | 0.00018 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.72 | 23.72 | 7.90 | 7.90 | 23.7185 | 11.6650 | 23.7185 | 0.4918 | 0.3000 |
FLR_3_DOAS | 21.30 | 2.05 | 7.78 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8305.868 | 8305.868 | 1.373461 | 0.00007266 | 174.976 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8305.87 | 8305.87 | 1.373461 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00794154 | 49.2020 | 1357.34 | 0.00 | 8352.38 | 8352.38 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5510.277 | 5510.277 | 0.227317 | 0.00004821 | 143.878 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5510.28 | 5510.28 | 0.227317 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00754889 | 46.8044 | 4361.62 | 0.00 | 5537.96 | 5537.96 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1992.328 | 1992.328 | 0.122066 | 0.00001743 | 47.047 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1992.33 | 1992.33 | 0.122066 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00745491 | 46.2249 | 1375.44 | 0.00 | 2002.93 | 2002.93 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3085.114 | 3085.114 | 0.112554 | 0.00002699 | 84.193 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3085.11 | 3085.11 | 0.112554 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00730989 | 45.3366 | 2516.46 | 0.00 | 3100.41 | 3100.41 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2278.841 | 2278.841 | 0.083135 | 0.00001994 | 62.191 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2278.84 | 2278.84 | 0.083135 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00745033 | 46.1972 | 1858.71 | 0.00 | 2290.14 | 2290.14 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11757.157 | 11757.157 | 1.664121 | 0.00010286 | 250.328 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11757.16 | 11757.16 | 1.664121 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00729418 | 45.2439 | 3352.41 | 0.00 | 11822.76 | 11822.76 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15603.613 | 15603.613 | 0.894977 | 0.00013651 | 373.406 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15603.61 | 15603.61 | 0.894977 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00760451 | 47.1440 | 11080.36 | 0.00 | 15685.29 | 15685.29 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 38035.681 | 38035.681 | 2.556329 | 0.00033275 | 882.989 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 38035.68 | 38035.68 | 2.556329 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00750797 | 46.5502 | 25115.51 | 0.00 | 38239.07 | 38239.07 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 14766.392 | -999.000 | 1.361188 | 0.00052741 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 14766.39 | 14361.08 | 1.361188 | 21.71 | 15.24 | 0.00862187 | 12.80 | 11.72 | 0.00850000 | 28.36 | 0.01272282 | 20.62 | 0.0000 | 21.11 | 0.00862187 | 52.9992 | 13322.35 | 0.00 | 15368.18 | 14649.38 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9955.436 | 9955.436 | 0.447860 | 0.00008709 | 284.486 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9955.44 | 9955.44 | 0.447860 | 21.11 | 14.06 | 0.00754410 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00754410 | 46.4579 | 9955.44 | 0.00 | 10731.90 | 10731.90 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 14102.455 | -999.000 | 1.298005 | 0.00050370 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 14102.46 | 13697.93 | 1.298005 | 21.71 | 15.25 | 0.00862752 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00862752 | 53.0335 | 12703.94 | 0.00 | 14676.76 | 13972.23 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9964.768 | 9964.768 | 0.448280 | 0.00008718 | 284.752 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9964.77 | 9964.77 | 0.448280 | 21.11 | 14.06 | 0.00754453 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00754453 | 46.4606 | 9964.77 | 0.00 | 10741.96 | 10741.96 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 93575.015 | -999.000 | 8.785752 | 0.00334222 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 93575.02 | 92413.13 | 8.785752 | 21.71 | 15.19 | 0.00855429 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00855429 | 52.5875 | 85994.82 | 0.00 | 97422.39 | 94325.55 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 56334.123 | 56334.123 | 2.534439 | 0.00049284 | 1609.794 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 56334.12 | 56334.12 | 2.534439 | 21.11 | 14.09 | 0.00757134 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00757134 | 46.6201 | 56334.12 | 0.00 | 60729.09 | 60729.09 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 74685.407 | -999.000 | 6.581753 | 0.00266754 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | 7/21 19:20:00 | 74685.41 | 69951.80 | 6.581753 | 21.71 | 15.39 | 0.00879220 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 0.0000 | 21.11 | 0.00879220 | 54.0318 | 64417.01 | 0.00 | 77663.44 | 71255.68 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 56524.552 | 56524.552 | 2.543007 | 0.00049450 | 1615.235 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 56524.55 | 56524.55 | 2.543007 | 21.11 | 14.09 | 0.00757260 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00757260 | 46.6278 | 56524.55 | 0.00 | 60934.37 | 60934.37 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13452.816 | -999.000 | 1.235748 | 0.00048049 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 13452.82 | 13045.24 | 1.235748 | 21.71 | 15.26 | 0.00863491 | 12.80 | 11.72 | 0.00850000 | 25.39 | 0.01271761 | 19.73 | 0.0000 | 21.11 | 0.00863491 | 53.0783 | 12094.61 | 0.00 | 14000.14 | 13305.61 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9974.977 | 9974.977 | 0.448739 | 0.00008727 | 285.044 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9974.98 | 9974.98 | 0.448739 | 21.11 | 14.06 | 0.00754494 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00754494 | 46.4630 | 9974.98 | 0.00 | 10752.97 | 10752.97 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12794.462 | -999.000 | 1.172958 | 0.00045698 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 12794.46 | 12386.44 | 1.172958 | 21.71 | 15.26 | 0.00864224 | 12.80 | 11.72 | 0.00850000 | 23.63 | 0.01271456 | 19.19 | 0.0000 | 21.11 | 0.00864224 | 53.1228 | 11480.06 | 0.00 | 13314.50 | 12632.86 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9984.307 | 9984.307 | 0.449159 | 0.00008735 | 285.310 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9984.31 | 9984.31 | 0.449159 | 21.11 | 14.06 | 0.00754537 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00754537 | 46.4657 | 9984.31 | 0.00 | 10763.02 | 10763.02 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 19136.046 | 19136.046 | 0.839196 | 0.00016741 | 490.185 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 19136.05 | 19136.05 | 0.839196 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00762528 | 47.2674 | 14893.25 | 0.00 | 19234.05 | 19234.05 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3837.360 | -999.000 | 0.354178 | 0.00013706 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3837.36 | 3735.94 | 0.354178 | 21.71 | 15.24 | 0.00861723 | 12.80 | 11.72 | 0.00850000 | 28.36 | 0.01272282 | 20.62 | 0.0000 | 21.11 | 0.00861723 | 52.9710 | 3466.44 | 0.00 | 3993.84 | 3811.09 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2974.530 | 2974.530 | 0.133814 | 0.00002602 | 84.996 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2974.53 | 2974.53 | 0.133814 | 21.11 | 14.13 | 0.00761478 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00761478 | 46.8877 | 2974.53 | 0.00 | 3206.53 | 3206.53 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3649.610 | -999.000 | 0.336307 | 0.00013035 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3649.61 | 3548.39 | 0.336307 | 21.71 | 15.25 | 0.00862318 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00862318 | 53.0071 | 3291.54 | 0.00 | 3798.32 | 3619.58 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2974.834 | 2974.834 | 0.133828 | 0.00002603 | 85.005 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2974.83 | 2974.83 | 0.133828 | 21.11 | 14.13 | 0.00761484 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00761484 | 46.8881 | 2974.83 | 0.00 | 3206.86 | 3206.86 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 19042.387 | -999.000 | 1.738393 | 0.00068014 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 19042.39 | 18370.08 | 1.738393 | 21.71 | 15.28 | 0.00865803 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00865803 | 53.2188 | 17013.92 | 0.00 | 19814.80 | 18733.01 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14193.949 | 14193.949 | 0.638553 | 0.00012417 | 405.587 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14193.95 | 14193.95 | 0.638553 | 21.11 | 14.14 | 0.00762764 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00762764 | 46.9647 | 14193.95 | 0.00 | 15301.12 | 15301.12 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14951.802 | 14951.802 | 1.101614 | 0.00013080 | 341.887 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14951.80 | 14951.80 | 1.101614 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00769675 | 47.7063 | 9382.13 | 0.00 | 15032.16 | 15032.16 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15400.415 | 15400.415 | 1.154585 | 0.00013473 | 351.201 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15400.42 | 15400.42 | 1.154585 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00770226 | 47.7400 | 9562.87 | 0.00 | 15483.26 | 15483.26 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10254.657 | 10254.657 | 1.173112 | 0.00008971 | 222.262 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 10254.66 | 10254.66 | 1.173112 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00719381 | 44.6311 | 4332.20 | 0.00 | 10311.57 | 10311.57 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11907.689 | 11907.689 | 0.434365 | 0.00010417 | 324.982 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11907.69 | 11907.69 | 0.434365 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00774176 | 47.9811 | 9711.27 | 0.00 | 11966.74 | 11966.74 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 634386.719 | -999.000 | 23.718522 | 0.02265882 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 634386.72 | 448987.12 | 23.718522 | 26.99 | 19.06 | 0.01114954 | 10.91 | 10.91 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 49.1660 | 23.99 | 0.00958386 | 49.3755 | 312572.07 | 0.00 | 651309.55 | 443246.85 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 407585.106 | 407585.106 | 7.115557 | 0.00356573 | 5672.671 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 407585.11 | 407585.11 | 7.115557 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 163.8868 | 21.00 | 0.00758764 | 47.0380 | 97804.37 | 0.00 | 282379.70 | 282379.70 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 69550.086 | -999.000 | 2.051317 | 0.00248417 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 69550.09 | 44784.57 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 99.9965 | 21.11 | 0.00865840 | 53.2197 | 208515.92 | 0.00 | 71097.05 | 44995.87 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35250.36 | 35250.36 | 0.615395 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 333.3216 | 21.11 | 0.00757231 | 46.6261 | 172881.47 | 0.00 | 24421.86 | 24421.86 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8305.868 | 8305.868 | 1.373461 | 0.00007266 | 174.976 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.0520 | 1.073198 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8305.87 | 8305.87 | 1.0000 | 1.58487039 | 1.373461 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07265594 | 60.00 | 32.22 | 27.78 | 0.000 | 8305.87 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00794154 | 21.00 | 0.00794154 | 49.2020 | 1357.34 | 0.00 | 8352.38 | 8352.38 | 1.58487039 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.77 | 15.14 | 0.00800000 | 42204.8 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5510.277 | 5510.277 | 0.227317 | 0.00004821 | 143.878 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 0.6979 | 0.711981 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5510.28 | 5510.28 | 1.0000 | 0.26230703 | 0.227317 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.04820139 | 60.00 | 32.22 | 27.78 | 0.000 | 5510.28 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00754889 | 21.00 | 0.00754889 | 46.8044 | 4361.62 | 0.00 | 5537.96 | 5537.96 | 0.26230703 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.30 | 20.37 | 0.00800000 | 58047.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1992.328 | 1992.328 | 0.122066 | 0.00001743 | 47.047 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 0.2523 | 0.257428 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1992.33 | 1992.33 | 1.0000 | 0.14085473 | 0.122066 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01742798 | 60.00 | 32.22 | 27.78 | 0.000 | 1992.33 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00745491 | 21.00 | 0.00745491 | 46.2249 | 1375.44 | 0.00 | 2002.93 | 2002.93 | 0.14085473 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.54 | 18.22 | 0.00800000 | 51154.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3085.114 | 3085.114 | 0.112554 | 0.00002699 | 84.193 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 0.3908 | 0.398626 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3085.11 | 3085.11 | 1.0000 | 0.12987895 | 0.112554 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02698717 | 60.00 | 32.22 | 27.78 | 0.000 | 3085.11 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00730989 | 21.00 | 0.00730989 | 45.3366 | 2516.46 | 0.00 | 3100.41 | 3100.41 | 0.12987895 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2278.841 | 2278.841 | 0.083135 | 0.00001994 | 62.191 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 0.2886 | 0.294448 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2278.84 | 2278.84 | 1.0000 | 0.09593144 | 0.083135 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01993426 | 60.00 | 32.22 | 27.78 | 0.000 | 2278.84 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00745033 | 21.00 | 0.00745033 | 46.1972 | 1858.71 | 0.00 | 2290.14 | 2290.14 | 0.09593144 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11757.157 | 11757.157 | 1.664121 | 0.00010286 | 250.328 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.4892 | 1.519137 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11757.16 | 11757.16 | 1.0000 | 1.92027107 | 1.664121 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10284624 | 60.00 | 32.22 | 27.78 | 0.000 | 11757.16 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00729418 | 21.00 | 0.00729418 | 45.2439 | 3352.41 | 0.00 | 11822.76 | 11822.76 | 1.92027107 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.64 | 15.46 | 0.00800000 | 43091.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15603.613 | 15603.613 | 0.894977 | 0.00013651 | 373.406 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.9764 | 2.016136 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15603.61 | 15603.61 | 1.0000 | 1.03273563 | 0.894977 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13649329 | 60.00 | 32.22 | 27.78 | 0.000 | 15603.61 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00760451 | 21.00 | 0.00760451 | 47.1440 | 11080.36 | 0.00 | 15685.29 | 15685.29 | 1.03273563 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.49 | 18.53 | 0.00800000 | 52122.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38035.681 | 38035.681 | 2.556329 | 0.00033275 | 882.989 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 4.8176 | 4.914574 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 38035.68 | 38035.68 | 1.0000 | 2.94981207 | 2.556329 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.33271878 | 60.00 | 32.22 | 27.78 | 0.000 | 38035.68 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00750797 | 21.00 | 0.00750797 | 46.5502 | 25115.51 | 0.00 | 38239.07 | 38239.07 | 2.94981207 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.31 | 17.81 | 0.00800000 | 49898.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14766.392 | -999.000 | 1.361188 | 0.00052741 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8676 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.361188 | 1.57070910 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 1.5481 | 1.548074 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 14766.39 | 14361.08 | 1.0000 | 1.57070910 | 1.361188 | 21.71 | 15.24 | 0.00862187 | 43723.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.52735766 | 6.70 | 13.37 | 6.67 | 0.000 | 14766.39 | 28.36 | 0.01272282 | 20.62 | 0.00000000 | 0.0000 | 21.11 | 0.00862187 | 21.11 | 0.00862187 | 52.9992 | 13322.35 | 0.00 | 15368.18 | 14649.38 | 1.57070910 | 21.71 | 15.67 | 0.00862187 | 43723.3 | 12.57 | 11.95 | 0.00844058 | 33939.1 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9955.436 | 9955.436 | 0.447860 | 0.00008709 | 284.486 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.361188 | 1.57070910 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.2610 | 1.286338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9955.44 | 9955.44 | 1.0000 | 0.51679693 | 0.447860 | 21.11 | 14.06 | 0.00754410 | 40374.2 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08708561 | 60.00 | 32.22 | 27.78 | 0.000 | 9955.44 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00754410 | 21.11 | 0.00754410 | 46.4579 | 9955.44 | 0.00 | 10731.90 | 10731.90 | 0.51679693 | 16.60 | 12.71 | 0.00754410 | 35780.5 | 36.98 | 19.93 | 0.00754410 | 56546.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14102.455 | -999.000 | 1.298005 | 0.00050370 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8781 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.298005 | 1.49779986 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 1.4785 | 1.478468 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 14102.46 | 13697.93 | 1.0000 | 1.49779986 | 1.298005 | 21.71 | 15.25 | 0.00862752 | 43737.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.50364624 | 6.70 | 13.37 | 6.67 | 0.000 | 14102.46 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00862752 | 21.11 | 0.00862752 | 53.0335 | 12703.94 | 0.00 | 14676.76 | 13972.23 | 1.49779986 | 21.71 | 15.68 | 0.00862752 | 43737.6 | 12.57 | 11.95 | 0.00844118 | 33938.8 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9964.768 | 9964.768 | 0.448280 | 0.00008718 | 284.752 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.298005 | 1.49779986 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.2621 | 1.287543 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9964.77 | 9964.77 | 1.0000 | 0.51728137 | 0.448280 | 21.11 | 14.06 | 0.00754453 | 40375.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08716725 | 60.00 | 32.22 | 27.78 | 0.000 | 9964.77 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00754453 | 21.11 | 0.00754453 | 46.4606 | 9964.77 | 0.00 | 10741.96 | 10741.96 | 0.51728137 | 16.60 | 12.71 | 0.00754453 | 35781.6 | 36.98 | 19.93 | 0.00754453 | 56547.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 93575.015 | -999.000 | 8.785752 | 0.00334222 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7420 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.785752 | 10.13809742 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 9.8104 | 9.810184 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 93575.02 | 92413.13 | 1.0000 | 10.13809742 | 8.785752 | 21.71 | 15.19 | 0.00855429 | 43552.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 3.34187936 | 6.70 | 13.37 | 6.67 | 0.000 | 93575.02 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00855429 | 21.11 | 0.00855429 | 52.5875 | 85994.82 | 0.00 | 97422.39 | 94325.55 | 10.13809742 | 21.71 | 15.61 | 0.00855429 | 43552.2 | 12.59 | 11.95 | 0.00843329 | 33942.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 56334.123 | 56334.123 | 2.534439 | 0.00049284 | 1609.794 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.785752 | 10.13809742 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 7.1353 | 7.278908 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 56334.12 | 56334.12 | 1.0000 | 2.92455273 | 2.534439 | 21.11 | 14.09 | 0.00757134 | 40444.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.49278521 | 60.00 | 32.22 | 27.78 | 0.000 | 56334.12 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00757134 | 21.11 | 0.00757134 | 46.6201 | 56334.12 | 0.00 | 60729.09 | 60729.09 | 2.92455273 | 16.60 | 12.73 | 0.00757134 | 35849.5 | 36.98 | 19.95 | 0.00757134 | 56614.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74685.407 | -999.000 | 6.581753 | 0.00266754 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1843 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.581753 | 7.59484834 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 7.8300 | 7.829842 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | unknown | unknown | 7/21 19:20:00 | Sensible | 74685.41 | 69951.80 | 1.0000 | 7.59484834 | 6.581753 | 21.71 | 15.39 | 0.00879220 | 44155.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.66726776 | 6.70 | 13.37 | 6.67 | 0.000 | 74685.41 | 24.81 | 0.01271660 | 19.55 | 0.00000000 | 0.0000 | 21.11 | 0.00879220 | 21.11 | 0.00879220 | 54.0318 | 64417.01 | 0.00 | 77663.44 | 71255.68 | 7.59484834 | 21.71 | 15.82 | 0.00879220 | 44155.9 | 12.52 | 11.94 | 0.00845796 | 33930.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 56524.552 | 56524.552 | 2.543007 | 0.00049450 | 1615.235 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.581753 | 7.59484834 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 7.1594 | 7.303514 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 56524.55 | 56524.55 | 1.0000 | 2.93443878 | 2.543007 | 21.11 | 14.09 | 0.00757260 | 40447.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.49445099 | 60.00 | 32.22 | 27.78 | 0.000 | 56524.55 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00757260 | 21.11 | 0.00757260 | 46.6278 | 56524.55 | 0.00 | 60934.37 | 60934.37 | 2.93443878 | 16.60 | 12.73 | 0.00757260 | 35852.6 | 36.98 | 19.95 | 0.00757260 | 56617.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13452.816 | -999.000 | 1.235748 | 0.00048049 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8919 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.235748 | 1.42595994 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 1.4104 | 1.410362 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 13452.82 | 13045.24 | 1.0000 | 1.42595994 | 1.235748 | 21.71 | 15.26 | 0.00863491 | 43756.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.48044542 | 6.70 | 13.37 | 6.67 | 0.000 | 13452.82 | 25.39 | 0.01271761 | 19.73 | 0.00000000 | 0.0000 | 21.11 | 0.00863491 | 21.11 | 0.00863491 | 53.0783 | 12094.61 | 0.00 | 14000.14 | 13305.61 | 1.42595994 | 21.71 | 15.68 | 0.00863491 | 43756.4 | 12.57 | 11.95 | 0.00844196 | 33938.4 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9974.977 | 9974.977 | 0.448739 | 0.00008727 | 285.044 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.235748 | 1.42595994 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.2634 | 1.288863 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9974.98 | 9974.98 | 1.0000 | 0.51781131 | 0.448739 | 21.11 | 14.06 | 0.00754494 | 40376.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08725654 | 60.00 | 32.22 | 27.78 | 0.000 | 9974.98 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00754494 | 21.11 | 0.00754494 | 46.4630 | 9974.98 | 0.00 | 10752.97 | 10752.97 | 0.51781131 | 16.60 | 12.71 | 0.00754494 | 35782.6 | 36.98 | 19.93 | 0.00754494 | 56548.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12794.462 | -999.000 | 1.172958 | 0.00045698 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9055 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.172958 | 1.35350593 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 1.3414 | 1.341341 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 12794.46 | 12386.44 | 1.0000 | 1.35350593 | 1.172958 | 21.71 | 15.26 | 0.00864224 | 43775.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.45693339 | 6.70 | 13.37 | 6.67 | 0.000 | 12794.46 | 23.63 | 0.01271456 | 19.19 | 0.00000000 | 0.0000 | 21.11 | 0.00864224 | 21.11 | 0.00864224 | 53.1228 | 11480.06 | 0.00 | 13314.50 | 12632.86 | 1.35350593 | 21.71 | 15.69 | 0.00864224 | 43775.0 | 12.57 | 11.95 | 0.00844274 | 33938.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9984.307 | 9984.307 | 0.449159 | 0.00008735 | 285.310 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.172958 | 1.35350593 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.2646 | 1.290068 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9984.31 | 9984.31 | 1.0000 | 0.51829566 | 0.449159 | 21.11 | 14.06 | 0.00754537 | 40377.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08733816 | 60.00 | 32.22 | 27.78 | 0.000 | 9984.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00754537 | 21.11 | 0.00754537 | 46.4657 | 9984.31 | 0.00 | 10763.02 | 10763.02 | 0.51829566 | 16.60 | 12.71 | 0.00754537 | 35783.7 | 36.98 | 19.93 | 0.00754537 | 56549.9 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19136.046 | 19136.046 | 0.839196 | 0.00016741 | 490.185 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 2.4238 | 2.472560 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 19136.05 | 19136.05 | 1.0000 | 0.96836910 | 0.839196 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.16739340 | 60.00 | 32.22 | 27.78 | 0.000 | 19136.05 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00762528 | 21.00 | 0.00762528 | 47.2674 | 14893.25 | 0.00 | 19234.05 | 19234.05 | 0.96836910 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.08 | 19.99 | 0.00800000 | 56797.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3837.360 | -999.000 | 0.354178 | 0.00013706 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8590 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.354178 | 0.40869438 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 0.4023 | 0.402300 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3837.36 | 3735.94 | 1.0000 | 0.40869438 | 0.354178 | 21.71 | 15.24 | 0.00861723 | 43711.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.13704507 | 6.70 | 13.37 | 6.67 | 0.000 | 3837.36 | 28.36 | 0.01272282 | 20.62 | 0.00000000 | 0.0000 | 21.11 | 0.00861723 | 21.11 | 0.00861723 | 52.9710 | 3466.44 | 0.00 | 3993.84 | 3811.09 | 0.40869438 | 21.71 | 15.67 | 0.00861723 | 43711.5 | 12.57 | 11.95 | 0.00844009 | 33939.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2974.530 | 2974.530 | 0.133814 | 0.00002602 | 84.996 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.354178 | 0.40869438 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 0.3768 | 0.384338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2974.53 | 2974.53 | 1.0000 | 0.15441141 | 0.133814 | 21.11 | 14.13 | 0.00761478 | 40553.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02601983 | 60.00 | 32.22 | 27.78 | 0.000 | 2974.53 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00761478 | 21.11 | 0.00761478 | 46.8877 | 2974.53 | 0.00 | 3206.53 | 3206.53 | 0.15441141 | 16.60 | 12.78 | 0.00761478 | 35959.4 | 36.98 | 19.98 | 0.00761478 | 56725.6 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3649.610 | -999.000 | 0.336307 | 0.00013035 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8701 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.336307 | 0.38807344 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 0.3826 | 0.382616 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 3649.61 | 3548.39 | 1.0000 | 0.38807344 | 0.336307 | 21.71 | 15.25 | 0.00862318 | 43726.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.13033988 | 6.70 | 13.37 | 6.67 | 0.000 | 3649.61 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00862318 | 21.11 | 0.00862318 | 53.0071 | 3291.54 | 0.00 | 3798.32 | 3619.58 | 0.38807344 | 21.71 | 15.67 | 0.00862318 | 43726.6 | 12.57 | 11.95 | 0.00844072 | 33939.0 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2974.834 | 2974.834 | 0.133828 | 0.00002603 | 85.005 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.336307 | 0.38807344 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 0.3768 | 0.384377 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2974.83 | 2974.83 | 1.0000 | 0.15442722 | 0.133828 | 21.11 | 14.13 | 0.00761484 | 40554.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02602249 | 60.00 | 32.22 | 27.78 | 0.000 | 2974.83 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00761484 | 21.11 | 0.00761484 | 46.8881 | 2974.83 | 0.00 | 3206.86 | 3206.86 | 0.15442722 | 16.60 | 12.78 | 0.00761484 | 35959.6 | 36.98 | 19.98 | 0.00761484 | 56725.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19042.387 | -999.000 | 1.738393 | 0.00068014 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9348 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.738393 | 2.00597544 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 1.9964 | 1.996359 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 19042.39 | 18370.08 | 1.0000 | 2.00597544 | 1.738393 | 21.71 | 15.28 | 0.00865803 | 43815.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.68006785 | 6.70 | 13.37 | 6.67 | 0.000 | 19042.39 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00865803 | 21.11 | 0.00865803 | 53.2188 | 17013.92 | 0.00 | 19814.80 | 18733.01 | 2.00597544 | 21.71 | 15.70 | 0.00865803 | 43815.0 | 12.56 | 11.95 | 0.00844439 | 33937.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14193.949 | 14193.949 | 0.638553 | 0.00012417 | 405.587 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.738393 | 2.00597544 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.7978 | 1.833994 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14193.95 | 14193.95 | 1.0000 | 0.73684218 | 0.638553 | 21.11 | 14.14 | 0.00762764 | 40586.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12416219 | 60.00 | 32.22 | 27.78 | 0.000 | 14193.95 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00762764 | 21.11 | 0.00762764 | 46.9647 | 14193.95 | 0.00 | 15301.12 | 15301.12 | 0.73684218 | 16.60 | 12.79 | 0.00762764 | 35992.0 | 36.98 | 19.99 | 0.00762764 | 56757.8 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14951.802 | 14951.802 | 1.101614 | 0.00013080 | 341.887 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.8938 | 1.931916 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14951.80 | 14951.80 | 1.0000 | 1.27117931 | 1.101614 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13079155 | 60.00 | 32.22 | 27.78 | 0.000 | 14951.80 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00769675 | 21.00 | 0.00769675 | 47.7063 | 9382.13 | 0.00 | 15032.16 | 15032.16 | 1.27117931 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.20 | 17.43 | 0.00800000 | 48760.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15400.415 | 15400.415 | 1.154585 | 0.00013473 | 351.201 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.9506 | 1.989881 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15400.42 | 15400.42 | 1.0000 | 1.33230410 | 1.154585 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13471581 | 60.00 | 32.22 | 27.78 | 0.000 | 15400.42 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00770226 | 21.00 | 0.00770226 | 47.7400 | 9562.87 | 0.00 | 15483.26 | 15483.26 | 1.33230410 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.00 | 17.36 | 0.00800000 | 48556.1 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10254.657 | 10254.657 | 1.173112 | 0.00008971 | 222.262 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.2989 | 1.325000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 10254.66 | 10254.66 | 1.0000 | 1.35368338 | 1.173112 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08970306 | 60.00 | 32.22 | 27.78 | 0.000 | 10254.66 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.77 | 0.00719381 | 21.00 | 0.00719381 | 44.6311 | 4332.20 | 0.00 | 10311.57 | 10311.57 | 1.35368338 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.07 | 15.98 | 0.00800000 | 44552.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11907.689 | 11907.689 | 0.434365 | 0.00010417 | 324.982 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 1.5082 | 1.538588 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11907.69 | 11907.69 | 1.0000 | 0.50122409 | 0.434365 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10416303 | 60.00 | 32.22 | 27.78 | 0.000 | 11907.69 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00774176 | 21.00 | 0.00774176 | 47.9811 | 9711.27 | 0.00 | 11966.74 | 11966.74 | 0.50122409 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 634386.719 | -999.000 | 23.718522 | 0.02265882 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5664 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.718522 | 27.36939217 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 66.5089 | 66.508851 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 634386.72 | 448987.12 | 1.0000 | 27.36939217 | 23.718522 | 26.99 | 19.06 | 0.01114954 | 55568.5 | 10.91 | 10.91 | 0.00850000 | 32389.8 | 22.65651228 | 6.70 | 13.37 | 6.67 | 53144.636 | 581242.08 | 30.10 | 0.01272586 | 21.13 | 11.66146000 | 49.1660 | 23.99 | 0.00962450 | 23.99 | 0.00958386 | 49.3755 | 312572.07 | 0.00 | 651309.55 | 443246.85 | 27.36939217 | 26.99 | 19.54 | 0.01114954 | 55568.5 | 11.20 | 11.06 | 0.00813498 | 31771.5 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 407585.106 | 407585.106 | 7.115557 | 0.00356573 | 5672.671 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.718522 | 27.36939217 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 51.6249 | 52.663900 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 407585.11 | 407585.11 | 1.0000 | 8.21081765 | 7.115557 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 3.56536857 | 60.00 | 32.22 | 27.78 | 0.000 | 407585.11 | -32.70 | 0.00018338 | -32.70 | 11.66146000 | 163.8868 | 20.94 | 0.00760796 | 21.00 | 0.00758764 | 47.0380 | 97804.37 | 0.00 | 282379.70 | 282379.70 | 8.21081765 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 69550.086 | -999.000 | 2.051317 | 0.00248417 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 34.06540942 | 13.37 | 6.70 | 6.67 | 953838.04 | 7.2916 | 7.291603 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 69550.09 | 44784.57 | 1.0000 | 2.36706595 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 11.90 | 11.35 | 0.00850000 | 33402.0 | 2.48391450 | 6.70 | 13.37 | 6.67 | 2195.006 | 67355.08 | 30.10 | 0.01272586 | 21.13 | 2.05124512 | 99.9965 | 21.11 | 0.00865992 | 21.11 | 0.00865840 | 53.2197 | 208515.92 | 0.00 | 71097.05 | 44995.87 | 2.36706595 | 30.10 | 21.63 | 0.01272586 | 62784.4 | 11.62 | 11.46 | 0.00835454 | 32748.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 6.77004278 | 54.44 | 82.22 | 27.78 | 789512.20 | 4.4648 | 4.554684 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35250.36 | 35250.36 | 1.0000 | 0.71011979 | 0.615395 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 0.30835404 | 60.00 | 32.22 | 27.78 | 0.000 | 35250.36 | -32.70 | 0.00018338 | -32.70 | 2.05124512 | 333.3216 | 21.11 | 0.00757173 | 21.11 | 0.00757231 | 46.6261 | 172881.47 | 0.00 | 24421.86 | 24421.86 | 0.71011979 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 23.72 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1012.17 | 6800.17 | 547.17 |
RETAIL_1_FLR_1 | 3602.00 | 7594.67 | 2812.33 |
RETAIL_2_FLR_1 | 2231.33 | 7172.83 | 1489.00 |
MECH_FLR_1 | 2907.17 | 7888.17 | 2636.83 |
STORAGE_FLR_1 | 3025.00 | 8404.00 | 2955.50 |
LAUNDRY_FLR_1 | 6764.50 | 3678.00 | 2733.67 |
CAFE_FLR_1 | 3645.50 | 6580.67 | 2142.83 |
LOBBY_FLR_1 | 2661.17 | 6354.50 | 1340.50 |
ROOM_1_FLR_3 | 4577.17 | 7904.33 | 4088.83 |
ROOM_2_FLR_3 | 4809.00 | 8067.00 | 4414.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3771.67 | 8699.33 | 3764.67 |
ROOM_5_FLR_3 | 4451.00 | 7761.67 | 3908.17 |
ROOM_6_FLR_3 | 4602.50 | 7926.00 | 4240.67 |
CORRIDOR_FLR_3 | 2901.83 | 8129.83 | 2755.00 |
ROOM_1_FLR_6 | 4980.67 | 7925.17 | 4481.00 |
ROOM_2_FLR_6 | 5156.17 | 8074.17 | 4766.17 |
ROOM_3_MULT9_FLR_6 | 3901.33 | 7711.50 | 3335.50 |
BANQUET_FLR_6 | 3774.00 | 4244.50 | 1014.50 |
DINING_FLR_6 | 4220.67 | 3336.67 | 825.50 |
KITCHEN_FLR_6 | 7899.67 | 6284.83 | 5792.50 |
CORRIDOR_FLR_6 | 3074.83 | 7700.00 | 2553.50 |
Facility | 8760.00 | 8760.00 | 8033.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 204.67 | 0.00 | 204.67 | 0.00 |
RETAIL_1_FLR_1 | 395.17 | 0.00 | 395.17 | 0.00 |
RETAIL_2_FLR_1 | 358.83 | 0.00 | 358.83 | 0.00 |
MECH_FLR_1 | 431.33 | 0.00 | 431.33 | 0.00 |
STORAGE_FLR_1 | 542.67 | 0.00 | 542.67 | 0.00 |
LAUNDRY_FLR_1 | 217.33 | 140.67 | 217.33 | 140.67 |
CAFE_FLR_1 | 351.67 | 0.00 | 351.67 | 0.00 |
LOBBY_FLR_1 | 315.00 | 0.00 | 315.00 | 0.00 |
ROOM_1_FLR_3 | 30.33 | 12.00 | 30.33 | 12.00 |
ROOM_2_FLR_3 | 76.67 | 7.83 | 76.67 | 7.83 |
ROOM_3_MULT19_FLR_3 | 0.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 275.67 | 13.50 | 275.67 | 13.50 |
ROOM_5_FLR_3 | 41.83 | 18.00 | 41.83 | 18.00 |
ROOM_6_FLR_3 | 93.67 | 17.00 | 93.67 | 17.00 |
CORRIDOR_FLR_3 | 389.17 | 0.00 | 389.17 | 0.00 |
ROOM_1_FLR_6 | 41.17 | 17.17 | 41.17 | 17.17 |
ROOM_2_FLR_6 | 98.83 | 12.33 | 98.83 | 12.33 |
ROOM_3_MULT9_FLR_6 | 6.83 | 6.67 | 6.83 | 6.67 |
BANQUET_FLR_6 | 109.33 | 18.67 | 109.33 | 18.67 |
DINING_FLR_6 | 96.83 | 22.83 | 96.83 | 22.83 |
KITCHEN_FLR_6 | 139.67 | 252.83 | 139.67 | 252.83 |
CORRIDOR_FLR_6 | 411.17 | 0.00 | 411.17 | 0.00 |
Facility | 590.00 | 351.83 | 590.00 | 351.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.991 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.932 | 0.142 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.358 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.466 | 0.053 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.533 | 0.053 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.441 | 0.153 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 4.113 | 0.112 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.708 | 0.046 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.184 | 0.000 | 0.029 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.184 | 0.000 | 0.031 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.082 | 0.000 | 0.067 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.184 | 0.000 | 0.045 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.184 | 0.000 | 0.043 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.597 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.184 | 0.000 | 0.031 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.184 | 0.000 | 0.033 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.150 | 0.000 | 0.081 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.392 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.754 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 20.331 | 0.153 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.101 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.575 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.631 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.778 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.263 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.301 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 10.609 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.352 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 0.998 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.515 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.337 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.516 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 2.207 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 2.313 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 7.560 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.621 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41195791.91 | 0.00 | 41195791.91 | 0.00 | 41195791.91 | 26946214.98 | 3.98 | 0.96 | 8755.06 | 0.00 |
RETAIL_1_FLR_1 | 6747024.03 | 0.00 | 6747024.03 | 326761.06 | 7073785.09 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3604638.82 | 0.00 | 3604638.82 | 126130.18 | 3730769.01 | 2892943.94 | 225.93 | 93.22 | 8440.85 | 0.00 |
MECH_FLR_1 | 2621767.35 | 0.00 | 2621767.35 | 298096.82 | 2919864.17 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1732707.13 | 0.00 | 1732707.13 | 171985.45 | 1904692.58 | 1821682.01 | 5312.25 | 435.57 | 3012.18 | 0.00 |
LAUNDRY_FLR_1 | 57129528.73 | 0.00 | 57129528.73 | 407035.98 | 57536564.71 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26552082.89 | 0.00 | 26552082.89 | 722323.83 | 27274406.72 | 21330615.53 | 303.82 | 111.06 | 8345.12 | 0.00 |
LOBBY_FLR_1 | 76228704.35 | 0.00 | 76228704.35 | 2063844.16 | 78292548.52 | 59728886.00 | 134.74 | 70.41 | 8554.86 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 29380.79 | 1976256.41 | 189663.05 | 2165919.46 | 1946875.62 | 0.00 | 8326.57 | 433.43 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 31019.66 | 1977667.17 | 189648.58 | 2167315.75 | 1946647.51 | 0.00 | 8290.92 | 469.08 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 45698.14 | 26443585.41 | 52918.12 | 26496503.53 | 26397887.27 | 0.00 | 8103.17 | 656.83 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 42662.75 | 26447768.47 | 52932.59 | 26500701.06 | 26405105.73 | 0.00 | 8102.95 | 657.05 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 45561.01 | 1992436.63 | 189663.05 | 2182099.68 | 1946875.62 | 0.00 | 8116.61 | 643.39 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 43602.18 | 1990249.69 | 189648.58 | 2179898.27 | 1946647.51 | 0.00 | 8115.22 | 644.78 | 0.00 |
CORRIDOR_FLR_3 | 24484756.72 | 0.00 | 24484756.72 | 229340.78 | 24714097.50 | 14972100.18 | 2.00 | 0.52 | 8757.48 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 31550.14 | 518269.04 | 189704.08 | 707973.12 | 486718.90 | 0.00 | 8350.50 | 409.50 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 33295.12 | 519957.00 | 189689.61 | 709646.60 | 486661.88 | 0.00 | 8313.95 | 446.05 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 51522.44 | 3178442.86 | 97059.25 | 3275502.11 | 3126920.42 | 0.00 | 8117.97 | 642.03 | 0.00 |
BANQUET_FLR_6 | 38069787.34 | 0.00 | 38069787.34 | 463209.69 | 38532997.03 | 37458366.31 | 5336.66 | 218.32 | 3205.03 | 0.00 |
DINING_FLR_6 | 41195042.48 | 0.00 | 41195042.48 | 463209.69 | 41658252.17 | 37458366.31 | 3998.03 | 229.08 | 4532.89 | 0.00 |
KITCHEN_FLR_6 | 54883449.50 | 0.00 | 54883449.50 | 414680.06 | 55298129.57 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11965820.99 | 0.00 | 11965820.99 | 405865.71 | 12371686.69 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 7842229.37 | 0.45E+10 | 19112579.17 | 0.46E+10 | 0.43E+10 | 7196.52 | 8407.33 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3063 | 0.0000 | 1.3063 | 0.0000 | 1.3063 | 0.8545 | 3.98 | 0.96 | 8755.06 |
RETAIL_1_FLR_1 | 0.2139 | 0.0000 | 0.2139 | 0.0104 | 0.2243 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1143 | 0.0000 | 0.1143 | 0.0040 | 0.1183 | 0.0917 | 225.93 | 93.22 | 8440.85 |
MECH_FLR_1 | 0.0831 | 0.0000 | 0.0831 | 0.0095 | 0.0926 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0549 | 0.0000 | 0.0549 | 0.0055 | 0.0604 | 0.0578 | 5312.25 | 435.57 | 3012.18 |
LAUNDRY_FLR_1 | 1.8116 | 0.0000 | 1.8116 | 0.0129 | 1.8245 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8420 | 0.0000 | 0.8420 | 0.0229 | 0.8649 | 0.6764 | 303.82 | 111.06 | 8345.12 |
LOBBY_FLR_1 | 2.4172 | 0.0000 | 2.4172 | 0.0654 | 2.4826 | 1.8940 | 134.74 | 70.41 | 8554.86 |
ROOM_1_FLR_3 | 0.0617 | 0.0009 | 0.0627 | 0.0060 | 0.0687 | 0.0617 | 0.00 | 8326.57 | 433.43 |
ROOM_2_FLR_3 | 0.0617 | 0.0010 | 0.0627 | 0.0060 | 0.0687 | 0.0617 | 0.00 | 8290.92 | 469.08 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0014 | 0.8387 | 0.0017 | 0.8403 | 0.8373 | 0.00 | 8102.95 | 657.05 |
ROOM_5_FLR_3 | 0.0617 | 0.0014 | 0.0632 | 0.0060 | 0.0692 | 0.0617 | 0.00 | 8116.61 | 643.39 |
ROOM_6_FLR_3 | 0.0617 | 0.0014 | 0.0631 | 0.0060 | 0.0691 | 0.0617 | 0.00 | 8115.22 | 644.78 |
CORRIDOR_FLR_3 | 0.7764 | 0.0000 | 0.7764 | 0.0073 | 0.7837 | 0.4748 | 2.00 | 0.52 | 8757.48 |
ROOM_1_FLR_6 | 0.0154 | 0.0010 | 0.0164 | 0.0060 | 0.0224 | 0.0154 | 0.00 | 8350.50 | 409.50 |
ROOM_2_FLR_6 | 0.0154 | 0.0011 | 0.0165 | 0.0060 | 0.0225 | 0.0154 | 0.00 | 8313.95 | 446.05 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0016 | 0.1008 | 0.0031 | 0.1039 | 0.0992 | 0.00 | 8117.97 | 642.03 |
BANQUET_FLR_6 | 1.2072 | 0.0000 | 1.2072 | 0.0147 | 1.2219 | 1.1878 | 5336.66 | 218.32 | 3205.03 |
DINING_FLR_6 | 1.3063 | 0.0000 | 1.3063 | 0.0147 | 1.3210 | 1.1878 | 3998.03 | 229.08 | 4532.89 |
KITCHEN_FLR_6 | 1.7403 | 0.0000 | 1.7403 | 0.0131 | 1.7535 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3794 | 0.0000 | 0.3794 | 0.0129 | 0.3923 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.1280 | 0.1385 | 80.2666 | 0.4785 | 80.7451 | 73.9670 | 7196.52 | 8407.33 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 86137942.48 | 354292.24 | 86492234.72 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 16.3188 | 0.0000 | 16.3188 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.7314 | 0.0112 | 2.7427 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 6306.25 | 2453.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 15.5284 | 18.3574 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.7317 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
Electricity:Building | 2531.67 | 31753.02 | 03-JUN-05:00 | 158241.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 332.05 | 3744.83 | 02-JAN-02:10 | 25084.28 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2524.58 | 31611.87 | 03-JUN-05:00 | 158000.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 866.40 | 7409.90 | 03-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 866.40 | 7409.90 | 03-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 866.40 | 7409.90 | 03-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 866.40 | 7409.90 | 03-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.95 | 223.93 | 02-JAN-02:10 | 1401.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.94 | 259.31 | 02-JAN-02:10 | 1623.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.64 | 250.98 | 02-JAN-02:10 | 1507.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 7.74 | 88.65 | 02-JAN-02:10 | 581.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 30.28 | 279.35 | 03-JUN-05:00 | 2922.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 15.93 | 76.13 | 03-JUN-05:00 | 1957.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 15.93 | 76.13 | 03-JUN-05:00 | 1957.67 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 247.70 | 2995.36 | 27-MAY-05:00 | 18583.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 98.70 | 883.95 | 27-MAY-05:00 | 8554.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 98.70 | 883.95 | 27-MAY-05:00 | 8554.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 325.45 | 4437.75 | 01-JAN-02:10 | 23570.01 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 325.54 | 4438.96 | 01-JAN-02:10 | 23576.46 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.35 | 67.90 | 01-JAN-02:10 | 391.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.35 | 67.89 | 01-JAN-02:10 | 391.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 38.55 | 525.67 | 01-JAN-02:10 | 2791.95 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.95 | 2478.49 | 27-MAY-05:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.09 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.09 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.95 | 2478.49 | 27-MAY-05:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.09 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.09 | 229.19 | 27-MAY-05:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.15 | 886.80 | 05-JAN-23:30 | 3447.39 | 03-OCT-06:40 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 818.75 | 2611.53 | 19-APR-00:50 | 218620.03 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.26 | 0.00 | 01-JAN-11:10 | 2041.01 | 08-OCT-10:40 |
MedTempRefrigeration:Refrigeration:Electricity | 33.80 | 608.23 | 06-JAN-04:10 | 1245.48 | 08-MAY-06:40 |
Fans:Electricity | 563.55 | 12185.53 | 22-OCT-01:30 | 42620.91 | 25-SEP-21:40 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 823.77 | 14303.21 | 04-SEP-04:10 | 47429.79 | 30-JUN-19:20 |
ExteriorEquipment:Electricity | 650.09 | 9607.53 | 02-JAN-02:20 | 39721.54 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 31.06 | 542.62 | 03-JUN-05:00 | 1847.44 | 31-MAR-20:10 |
ElectricityPurchased:Facility | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
ElectricityPurchased:Plant | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
Cogeneration:ElectricityPurchased | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
ElectricityNet:Plant | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
Cogeneration:ElectricityNet | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
General:Cogeneration:ElectricityNet | 5054.87 | 75244.94 | 10-JUN-04:30 | 427352.72 | 29-JUN-18:10 |
General:Fans:Electricity | 563.55 | 12185.53 | 22-OCT-01:30 | 42620.91 | 25-SEP-21:40 |
ExteriorLights:Electricity | 261.66 | 0.00 | 01-JAN-08:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 261.66 | 0.00 | 01-JAN-08:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 229.15 | 0.00 | 11-APR-11:50 | 9938.94 | 01-JAN-00:40 |
General:HeatRecovery:Electricity | 229.15 | 0.00 | 11-APR-11:50 | 9938.94 | 01-JAN-00:40 |
WaterSystems:Electricity | 90.75 | 1086.56 | 25-JUL-00:50 | 4743.91 | 13-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 25-JUL-00:50 | 4743.91 | 13-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 587.21 | 0.00 | 01-JAN-00:10 | 206113.93 | 29-JUN-18:10 |
General:Cooling:Electricity | 587.21 | 0.00 | 01-JAN-00:10 | 206113.93 | 29-JUN-18:10 |
Pumps:Electricity | 86.71 | 47.91 | 09-MAY-14:20 | 5652.11 | 09-JAN-10:50 |
General:Pumps:Electricity | 86.71 | 47.91 | 09-MAY-14:20 | 5652.11 | 09-JAN-10:50 |
WIRED_LTG_ELECTRICITY | 30.50 | 0.00 | 01-JAN-00:10 | 2518.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 8511.42 | 31829.34 | 11-MAY-01:10 | 1227994.65 | 05-JAN-21:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 6722.58 | 18467.44 | 05-MAY-15:30 | 1152870.89 | 05-JAN-21:40 |
WaterSystems:NaturalGas | 3563.13 | 18467.44 | 16-APR-13:10 | 314198.63 | 28-FEB-21:30 |
Water Heater:WaterSystems:NaturalGas | 3563.13 | 18467.44 | 16-APR-13:10 | 314198.63 | 28-FEB-21:30 |
Heating:NaturalGas | 3159.45 | 0.00 | 31-MAR-13:50 | 902207.62 | 06-JAN-05:00 |
Boiler:Heating:NaturalGas | 3159.45 | 0.00 | 31-MAR-13:50 | 902207.62 | 06-JAN-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1802.81 | 0.00 | 01-JAN-00:10 | 651131.02 | 29-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 1802.81 | 0.00 | 01-JAN-00:10 | 651131.02 | 29-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 1802.81 | 0.00 | 01-JAN-00:10 | 651131.02 | 29-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 08-JUL-00:40 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 08-JUL-00:40 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22409.38 | 147713.18 | 21-NOV-13:50 | 2793672.57 | 29-JUN-18:10 |
EnergyTransfer:Building | 5123.15 | 61243.11 | 28-SEP-03:20 | 371745.28 | 29-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 697.38 | 5853.49 | 07-JAN-04:20 | 37166.22 | 29-JUL-10:50 |
Refrigeration:EnergyTransfer | 179.63 | 1977.52 | 06-JAN-04:00 | 10723.16 | 20-OCT-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.82 | 988.76 | 06-JAN-04:00 | 5361.58 | 20-OCT-07:20 |
General:Refrigeration:EnergyTransfer | 89.82 | 988.76 | 06-JAN-04:00 | 5361.58 | 20-OCT-07:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.82 | 988.76 | 06-JAN-04:00 | 5361.58 | 20-OCT-07:20 |
EnergyTransfer:Plant | 7735.29 | 19589.40 | 13-SEP-02:40 | 1556856.59 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.52 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.30 | 774.68 | 06-JAN-04:10 | 2686.44 | 08-MAY-06:40 |
EnergyTransfer:Zone:BASEMENT | 422.35 | 16.04 | 06-JAN-14:30 | 34464.12 | 25-JAN-21:00 |
Heating:EnergyTransfer | 575.35 | 0.00 | 08-FEB-13:20 | 153147.28 | 07-JAN-04:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.03 | 0.00 | 01-JAN-00:10 | 1885.25 | 06-JAN-13:40 |
General:Heating:EnergyTransfer | 575.35 | 0.00 | 08-FEB-13:20 | 153147.28 | 07-JAN-04:30 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.03 | 0.00 | 01-JAN-00:10 | 1885.25 | 06-JAN-13:40 |
Cooling:EnergyTransfer | 4457.98 | 21504.74 | 21-DEC-11:00 | 368123.38 | 29-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 422.32 | 0.00 | 06-JAN-13:40 | 34464.12 | 25-JAN-21:00 |
General:Cooling:EnergyTransfer | 4457.98 | 21504.74 | 21-DEC-11:00 | 368123.38 | 29-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 422.32 | 0.00 | 06-JAN-13:40 | 34464.12 | 25-JAN-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.14 | 0.02 | 11-NOV-17:50 | 5134.75 | 22-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.40 | 0.00 | 01-JAN-09:50 | 2938.50 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.40 | 0.00 | 01-JAN-09:50 | 2938.50 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.74 | 0.00 | 01-JAN-00:10 | 5134.75 | 22-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.74 | 0.00 | 01-JAN-00:10 | 5134.75 | 22-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.56 | 1.50 | 25-FEB-10:30 | 2220.77 | 30-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.15 | 0.00 | 01-JAN-00:10 | 979.91 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.15 | 0.00 | 01-JAN-00:10 | 979.91 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.41 | 0.00 | 01-JAN-10:30 | 2220.77 | 30-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.41 | 0.00 | 01-JAN-10:30 | 2220.77 | 30-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 19.71 | 0.01 | 24-FEB-21:30 | 1712.29 | 30-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 4.12 | 0.00 | 16-JAN-19:10 | 1648.57 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 4.12 | 0.00 | 16-JAN-19:10 | 1648.57 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 15.60 | 0.00 | 01-JAN-00:10 | 1712.29 | 30-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 15.60 | 0.00 | 01-JAN-00:10 | 1712.29 | 30-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 13.48 | 0.06 | 05-DEC-23:20 | 1192.46 | 06-JAN-13:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 4.67 | 0.00 | 19-JAN-20:50 | 1192.46 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 4.67 | 0.00 | 19-JAN-20:50 | 1192.46 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.80 | 0.00 | 01-JAN-00:10 | 905.94 | 30-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.80 | 0.00 | 01-JAN-00:10 | 905.94 | 30-JUN-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 583.24 | 2727.87 | 07-JAN-04:30 | 39016.18 | 29-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1141.76 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1141.76 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 583.24 | 1708.67 | 14-JAN-05:00 | 39016.18 | 29-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 583.24 | 1708.67 | 14-JAN-05:00 | 39016.18 | 29-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 211.12 | 0.20 | 15-FEB-14:00 | 17934.42 | 22-OCT-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.64 | 0.00 | 01-JAN-00:10 | 7039.94 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.64 | 0.00 | 01-JAN-00:10 | 7039.94 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 210.49 | 0.00 | 02-JAN-07:40 | 17934.42 | 22-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 210.49 | 0.00 | 02-JAN-07:40 | 17934.42 | 22-OCT-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 696.97 | 2.89 | 07-JAN-14:30 | 41209.65 | 29-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.79 | 0.00 | 01-JAN-00:10 | 15595.35 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.79 | 0.00 | 01-JAN-00:10 | 15595.35 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 696.18 | 0.00 | 06-JAN-13:30 | 41209.65 | 29-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 696.18 | 0.00 | 06-JAN-13:30 | 41209.65 | 29-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 80.66 | 0.16 | 02-JAN-13:10 | 14295.96 | 05-JUL-17:00 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 43.88 | 0.00 | 01-JAN-11:10 | 8329.39 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 43.88 | 0.00 | 01-JAN-11:10 | 8329.39 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 36.78 | 0.00 | 01-JAN-00:10 | 14295.96 | 05-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 36.78 | 0.00 | 01-JAN-00:10 | 14295.96 | 05-JUL-17:00 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 81.69 | 0.01 | 21-APR-23:00 | 13940.94 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 51.58 | 0.00 | 16-JAN-08:10 | 9034.18 | 09-JAN-10:50 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 51.58 | 0.00 | 16-JAN-08:10 | 9034.18 | 09-JAN-10:50 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 30.10 | 0.00 | 01-JAN-00:10 | 13940.94 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 30.10 | 0.00 | 01-JAN-00:10 | 13940.94 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 394.37 | 0.02 | 07-FEB-01:50 | 70983.86 | 22-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 83.51 | 0.00 | 01-JAN-09:00 | 34353.85 | 19-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 83.51 | 0.00 | 01-JAN-09:00 | 34353.85 | 19-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 310.86 | 0.00 | 01-JAN-00:10 | 70983.86 | 22-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 310.86 | 0.00 | 01-JAN-00:10 | 70983.86 | 22-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 447.77 | 0.54 | 12-DEC-18:50 | 73045.98 | 25-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 180.34 | 0.00 | 01-JAN-11:10 | 50893.43 | 06-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 180.34 | 0.00 | 01-JAN-11:10 | 50893.43 | 06-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 267.43 | 0.00 | 01-JAN-00:10 | 73045.98 | 25-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 267.43 | 0.00 | 01-JAN-00:10 | 73045.98 | 25-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 80.87 | 0.18 | 24-MAR-15:20 | 14334.84 | 24-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.70 | 0.00 | 01-JAN-11:10 | 8387.47 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.70 | 0.00 | 01-JAN-11:10 | 8387.47 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.18 | 0.00 | 01-JAN-00:10 | 14334.84 | 24-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.18 | 0.00 | 01-JAN-00:10 | 14334.84 | 24-JUL-09:00 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 81.80 | 0.04 | 24-SEP-07:00 | 13652.73 | 24-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 51.46 | 0.00 | 02-JAN-11:10 | 9100.95 | 06-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 51.46 | 0.00 | 02-JAN-11:10 | 9100.95 | 06-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.35 | 0.00 | 01-JAN-00:10 | 13652.73 | 24-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.35 | 0.00 | 01-JAN-00:10 | 13652.73 | 24-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 159.81 | 0.01 | 06-NOV-07:40 | 12945.38 | 30-JUN-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 13.75 | 0.00 | 01-JAN-00:40 | 9314.79 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 13.75 | 0.00 | 01-JAN-00:40 | 9314.79 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 146.06 | 0.00 | 01-JAN-00:10 | 12945.38 | 30-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 146.06 | 0.00 | 01-JAN-00:10 | 12945.38 | 30-JUN-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.00 | 0.11 | 13-OCT-12:00 | 4223.06 | 06-MAY-19:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 14.75 | 0.00 | 02-JAN-11:10 | 2547.57 | 18-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 14.75 | 0.00 | 02-JAN-11:10 | 2547.57 | 18-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.25 | 0.00 | 01-JAN-00:10 | 4223.06 | 06-MAY-19:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.25 | 0.00 | 01-JAN-00:10 | 4223.06 | 06-MAY-19:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 24.56 | 0.03 | 24-MAR-12:00 | 3975.27 | 06-MAY-19:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.06 | 0.00 | 16-JAN-08:10 | 2644.93 | 09-JAN-10:50 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.06 | 0.00 | 16-JAN-08:10 | 2644.93 | 09-JAN-10:50 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.50 | 0.00 | 01-JAN-00:10 | 3975.27 | 06-MAY-19:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.50 | 0.00 | 01-JAN-00:10 | 3975.27 | 06-MAY-19:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 106.79 | 0.14 | 05-DEC-19:00 | 18523.56 | 25-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 45.63 | 0.00 | 01-JAN-10:20 | 11234.16 | 11-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 45.63 | 0.00 | 01-JAN-10:20 | 11234.16 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 61.16 | 0.00 | 01-JAN-00:10 | 18523.56 | 25-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 61.16 | 0.00 | 01-JAN-00:10 | 18523.56 | 25-AUG-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 402.69 | 229.71 | 06-JAN-15:00 | 23422.74 | 29-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 4437.17 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 4437.17 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 402.66 | 0.00 | 06-JAN-13:40 | 23422.74 | 29-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 402.66 | 0.00 | 06-JAN-13:40 | 23422.74 | 29-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 442.94 | 120.55 | 06-JAN-14:10 | 25702.00 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4079.12 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4079.12 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 442.93 | 0.00 | 06-JAN-13:40 | 25702.00 | 24-FEB-23:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 442.93 | 0.00 | 06-JAN-13:40 | 25702.00 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 462.78 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 462.78 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 607.57 | 3163.21 | 07-JAN-04:20 | 32103.55 | 29-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 607.57 | 3163.21 | 07-JAN-04:20 | 32103.55 | 29-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 80.24 | 0.00 | 19-NOV-08:00 | 6928.02 | 30-JUN-13:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 12.85 | 0.00 | 16-JAN-10:40 | 6318.37 | 07-JAN-04:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 12.85 | 0.00 | 16-JAN-10:40 | 6318.37 | 07-JAN-04:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 67.39 | 0.00 | 01-JAN-00:10 | 6928.02 | 30-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 67.39 | 0.00 | 01-JAN-00:10 | 6928.02 | 30-JUN-13:20 |
PlantLoopHeatingDemand:Facility | 3344.63 | 10719.48 | 26-AUG-00:10 | 799650.73 | 06-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 900.58 | 10719.48 | 26-AUG-00:10 | 66766.56 | 24-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 900.58 | 10719.48 | 26-AUG-00:10 | 66766.56 | 24-FEB-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 900.58 | 10719.48 | 26-AUG-00:10 | 66766.56 | 24-FEB-08:00 |
EnergyTransfer:HVAC | 9550.94 | 212.69 | 17-AUG-07:40 | 865070.70 | 29-JUN-18:10 |
HeatingCoils:EnergyTransfer | 2444.05 | 0.00 | 11-APR-12:20 | 737959.63 | 06-JAN-05:00 |
PlantLoopHeatingDemand:HVAC | 2444.05 | 0.00 | 11-APR-12:20 | 737959.63 | 06-JAN-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 2444.05 | 0.00 | 11-APR-12:20 | 737959.63 | 06-JAN-05:00 |
CoolingCoils:EnergyTransfer | 1802.81 | 0.00 | 01-JAN-00:10 | 651131.02 | 29-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 5179.71 | 0.00 | 01-JAN-00:40 | 586205.99 | 24-FEB-06:20 |
HeatRecoveryForCooling:EnergyTransfer | 124.37 | 0.00 | 01-JAN-00:10 | 251496.55 | 15-JUL-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 900.58 | 10719.48 | 26-AUG-00:10 | 66766.56 | 24-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 900.58 | 10719.48 | 26-AUG-00:10 | 66766.56 | 24-FEB-08:00 |
Boilers:EnergyTransfer | 2427.74 | 0.00 | 31-MAR-13:50 | 735116.28 | 06-JAN-05:00 |
Chillers:EnergyTransfer | 1864.97 | 0.00 | 01-JAN-00:10 | 655336.17 | 29-JUN-18:10 |
HeatRejection:EnergyTransfer | 2452.18 | 0.00 | 01-JAN-00:10 | 861450.11 | 29-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 2452.18 | 0.00 | 01-JAN-00:10 | 861450.11 | 29-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.029 | -422.324 | 0.000 | 0.000 | 141.955 | 188.948 | 143.105 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -51.713 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 6.398 | -33.738 | 0.000 | 0.000 | 15.925 | 8.760 | 10.186 | 27.821 | 0.000 | 0.054 | 0.002 | 0.000 | -16.542 | 0.000 | -7.242 | -11.621 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.153 | -30.406 | 0.000 | 0.000 | 17.353 | 10.144 | 11.795 | 0.000 | 0.000 | 0.021 | 0.000 | 0.000 | 0.000 | 0.000 | -2.921 | -6.139 |
MECH_FLR_1 | 0.000 | 0.000 | 4.117 | -15.597 | 0.000 | 0.000 | 3.771 | 8.172 | 12.471 | 0.000 | 0.000 | 0.050 | 0.000 | 0.000 | 0.000 | 0.000 | -6.766 | -6.219 |
STORAGE_FLR_1 | 0.000 | 0.000 | 4.670 | -8.805 | 0.000 | 0.000 | 2.944 | 4.146 | 3.598 | 0.000 | 0.000 | 0.031 | 0.000 | 0.000 | 0.000 | 0.000 | -3.855 | -2.729 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.006 | -583.237 | 0.000 | 0.000 | 11.377 | 5.547 | 658.131 | 0.000 | 0.000 | 0.074 | 0.000 | 0.000 | 0.000 | 0.000 | -9.689 | -82.210 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.636 | -210.490 | 0.000 | 0.000 | 199.495 | 15.935 | 14.341 | 77.407 | 0.000 | 0.112 | 0.001 | 0.000 | -48.122 | 0.000 | -16.570 | -32.744 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.788 | -696.187 | 0.000 | 0.000 | 572.960 | 98.699 | 148.998 | 102.039 | 0.000 | 0.323 | 0.002 | 0.000 | -65.409 | 0.000 | -48.507 | -113.705 |
ROOM_1_FLR_3 | 51.710 | -27.493 | 0.000 | -17.110 | 0.000 | 0.000 | 9.588 | 10.925 | 10.478 | 49.776 | 0.000 | 0.175 | 0.000 | 0.000 | -39.503 | 0.000 | -17.545 | -31.001 |
ROOM_2_FLR_3 | 59.851 | -21.562 | 0.000 | -16.809 | 0.000 | 0.000 | 9.626 | 10.924 | 10.477 | 34.276 | 0.000 | 0.176 | 0.000 | 0.000 | -41.954 | 0.000 | -17.474 | -27.531 |
ROOM_3_MULT19_FLR_3 | 138.573 | -135.495 | 0.000 | -230.429 | 0.000 | 0.000 | 0.000 | 130.455 | 194.997 | 332.869 | 0.000 | 0.736 | 0.014 | 0.000 | -208.078 | 0.000 | -105.613 | -118.015 |
ROOM_4_MULT19_FLR_3 | 273.990 | -139.385 | 0.000 | -221.684 | 0.000 | 0.000 | 185.118 | 130.491 | 195.050 | 84.348 | 0.000 | 1.240 | 0.000 | 0.000 | -236.950 | 0.000 | -101.270 | -170.948 |
ROOM_5_FLR_3 | 51.512 | -27.989 | 0.000 | -16.999 | 0.000 | 0.000 | 9.642 | 10.925 | 10.478 | 49.291 | 0.000 | 0.176 | 0.000 | 0.000 | -38.723 | 0.000 | -17.875 | -30.438 |
ROOM_6_FLR_3 | 59.750 | -21.902 | 0.000 | -16.733 | 0.000 | 0.000 | 9.677 | 10.924 | 10.477 | 33.457 | 0.000 | 0.176 | 0.000 | 0.000 | -40.875 | 0.000 | -17.688 | -27.263 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 13.748 | -146.061 | 0.000 | 0.000 | 119.811 | 91.336 | 0.000 | 44.830 | 0.000 | 0.149 | 0.004 | 0.000 | -50.043 | 0.000 | -20.792 | -52.978 |
ROOM_1_FLR_6 | 16.810 | -7.043 | 0.000 | -4.272 | 0.000 | 0.000 | 2.394 | 2.731 | 2.620 | 12.357 | 0.000 | 0.044 | 0.000 | 0.000 | -9.900 | 0.000 | -4.402 | -11.339 |
ROOM_2_FLR_6 | 19.220 | -5.462 | 0.000 | -4.198 | 0.000 | 0.000 | 2.404 | 2.731 | 2.619 | 8.511 | 0.000 | 0.044 | 0.000 | 0.000 | -10.511 | 0.000 | -4.385 | -10.974 |
ROOM_3_MULT9_FLR_6 | 56.998 | -44.858 | 0.000 | -27.672 | 0.000 | 0.000 | 21.639 | 15.453 | 23.098 | 71.475 | 0.000 | 0.215 | 0.000 | 0.000 | -45.540 | 0.000 | -21.985 | -48.822 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.030 | -402.661 | 0.000 | 0.000 | 322.416 | 35.090 | 175.857 | 8.519 | 0.000 | 0.060 | 0.000 | 0.000 | -30.503 | 0.000 | -11.394 | -97.415 |
DINING_FLR_6 | 0.000 | 0.000 | 0.019 | -442.929 | 0.000 | 0.000 | 320.712 | 35.090 | 175.857 | 8.341 | 0.000 | 0.060 | 0.000 | 0.000 | -31.131 | 0.000 | -11.465 | -54.554 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.001 | -607.551 | 0.000 | 0.000 | 28.857 | 14.807 | 550.372 | 22.392 | 0.000 | 0.053 | 21.577 | 0.000 | -20.222 | 0.000 | -10.287 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 12.850 | -67.388 | 0.000 | 0.000 | 31.883 | 24.166 | 0.000 | 22.384 | 0.000 | 0.057 | 7.451 | 0.000 | -22.216 | 0.000 | -9.186 | -0.000 |
Total Facility | 728.415 | -431.190 | 43.446 | -4223.280 | 0.000 | 0.000 | 2039.548 | 866.399 | 2365.005 | 990.094 | 0.000 | 4.026 | 29.053 | 0.000 | -956.224 | 0.000 | -466.909 | -988.358 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-OCT-05:56 | 0.00 | 0.00 | 0.00 | -39183.35 | 0.00 | 0.00 | 5183.76 | 6867.51 | 5069.75 | 0.00 | 0.00 | 0.00 | 22062.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 17-NOV-11:31 | 0.00 | 0.00 | 0.00 | -5512.89 | 0.00 | 0.00 | 143.71 | 198.99 | 252.59 | 7913.49 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -188.96 | -2806.92 |
RETAIL_2_FLR_1 | 05-SEP-21:08 | 0.00 | 0.00 | 0.00 | -3249.70 | 0.00 | 0.00 | 784.79 | 553.03 | 585.00 | 0.00 | 0.00 | 0.00 | 1405.87 | 0.00 | -0.00 | 0.00 | -79.00 | 0.00 |
MECH_FLR_1 | 30-JUN-20:00 | 0.00 | 0.00 | 0.00 | -1712.25 | 0.00 | 0.00 | 129.08 | 668.27 | 839.45 | 0.00 | 0.00 | 4.06 | 71.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 02-JUL-04:44 | 0.00 | 0.00 | 0.00 | -1057.04 | 0.00 | 0.00 | 105.49 | 75.34 | 76.47 | 0.00 | 0.00 | 0.00 | 903.40 | 0.00 | -0.00 | 0.00 | -103.66 | 0.00 |
LAUNDRY_FLR_1 | 16-OCT-19:27 | 0.00 | 0.00 | 0.00 | -53173.91 | 0.00 | 0.00 | 401.93 | 453.60 | 44299.38 | 0.00 | 0.00 | 0.00 | 8313.22 | 0.00 | -0.00 | 0.00 | -294.21 | 0.00 |
CAFE_FLR_1 | 17-NOV-11:31 | 0.00 | 0.00 | 0.00 | -20433.47 | 0.00 | 0.00 | 1860.21 | 119.64 | 355.63 | 22187.99 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -418.07 | -3671.92 |
LOBBY_FLR_1 | 14-SEP-23:35 | 0.00 | 0.00 | 0.00 | -70828.93 | 0.00 | 0.00 | 26438.38 | 1900.96 | 3167.12 | 0.00 | 0.00 | 0.00 | 43594.17 | 0.00 | -2917.08 | 0.00 | -1354.62 | 0.00 |
ROOM_1_FLR_3 | 06-MAY-18:42 | 0.00 | -19341.50 | 0.00 | -785.37 | 0.00 | 0.00 | 191.24 | 840.90 | 484.65 | 4821.97 | 0.00 | 0.00 | 14107.10 | 0.00 | -0.00 | 0.00 | -319.00 | 0.00 |
ROOM_2_FLR_3 | 06-MAY-18:42 | 0.00 | -18462.85 | 0.00 | -786.09 | 0.00 | 0.00 | 191.62 | 840.80 | 484.60 | 5559.74 | 0.00 | 0.00 | 12491.51 | 0.00 | -0.00 | 0.00 | -319.32 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-12:30 | 0.00 | -62306.60 | 0.00 | -8678.24 | 0.00 | 0.00 | 0.00 | 3313.52 | 2548.95 | 101562.31 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -831.25 | -35608.68 |
ROOM_4_MULT19_FLR_3 | 05-JUL-21:51 | 0.00 | -80508.56 | 0.00 | -9138.37 | 0.00 | 0.00 | 7763.95 | 6729.29 | 6668.31 | 0.00 | 0.00 | 0.00 | 74121.06 | 0.00 | -4680.34 | 0.00 | -955.33 | 0.00 |
ROOM_5_FLR_3 | 01-JUL-08:32 | 0.00 | -16738.14 | 0.00 | -913.67 | 0.00 | 0.00 | 88.31 | 470.90 | 653.23 | 10909.90 | 0.00 | 0.00 | 5736.31 | 0.00 | -0.00 | 0.00 | -206.85 | 0.00 |
ROOM_6_FLR_3 | 01-JUL-08:32 | 0.00 | -15975.29 | 0.00 | -917.34 | 0.00 | 0.00 | 88.32 | 470.85 | 653.15 | 10483.26 | 0.00 | 0.00 | 5405.25 | 0.00 | -0.00 | 0.00 | -208.21 | 0.00 |
CORRIDOR_FLR_3 | 02-JUL-04:44 | 0.00 | 0.00 | 0.00 | -15287.96 | 0.00 | 0.00 | 4245.33 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 10145.87 | 0.00 | -197.70 | 0.00 | -565.38 | 0.00 |
ROOM_1_FLR_6 | 06-MAY-18:42 | 0.00 | -5099.51 | 0.00 | -199.96 | 0.00 | 0.00 | 47.81 | 210.22 | 121.16 | 1171.74 | 0.00 | 0.00 | 3830.06 | 0.00 | -0.00 | 0.00 | -81.52 | 0.00 |
ROOM_2_FLR_6 | 06-MAY-18:32 | 0.00 | -4815.77 | 0.00 | -230.12 | 0.00 | 0.00 | 36.56 | 210.20 | 121.15 | 1609.04 | 0.00 | 0.00 | 3159.83 | 0.00 | -0.00 | 0.00 | -90.89 | 0.00 |
ROOM_3_MULT9_FLR_6 | 20-OCT-18:11 | 0.00 | -22500.38 | 0.00 | -1035.30 | 0.00 | 0.00 | 657.65 | 1058.56 | 1068.37 | 0.00 | 0.00 | 0.00 | 22831.29 | 0.00 | -1694.25 | 0.00 | -385.93 | 0.00 |
BANQUET_FLR_6 | 14-SEP-01:18 | 0.00 | 0.00 | 0.00 | -38092.07 | 0.00 | 0.00 | 15311.52 | 381.98 | 2249.30 | 0.00 | 0.00 | 0.00 | 21597.35 | 0.00 | -1150.02 | 0.00 | -298.06 | 0.00 |
DINING_FLR_6 | 20-OCT-04:03 | 0.00 | 0.00 | 0.00 | -40380.31 | 0.00 | 0.00 | 15814.41 | 763.96 | 2249.30 | 0.00 | 0.00 | 0.00 | 22919.68 | 0.00 | -1092.84 | 0.00 | -274.21 | 0.00 |
KITCHEN_FLR_6 | 27-OCT-17:27 | 0.00 | 0.00 | 0.00 | -41871.25 | 0.00 | 0.00 | 770.29 | 807.28 | 26759.11 | 0.00 | 0.00 | 0.00 | 14403.58 | 0.00 | -584.45 | 0.00 | -284.55 | 0.00 |
CORRIDOR_FLR_6 | 15-SEP-01:55 | 0.00 | 0.00 | 0.00 | -7124.75 | 0.00 | 0.00 | 1557.82 | 219.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6482.95 | 0.00 | -898.12 | 0.00 | -237.49 | 0.00 |
Total Facility | 30-JUN-18:02 | 0.00 | -183361.09 | 0.00 | -218929.22 | 0.00 | 0.00 | 74285.20 | 58770.64 | 120482.43 | 79340.20 | 0.00 | 4048.70 | 65363.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-OCT-01:06 | 0.00 | 0.00 | 5040.61 | 0.00 | 0.00 | 0.00 | 5206.95 | 3433.65 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16723.06 |
RETAIL_1_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 3240.39 | 0.00 | 0.00 | 0.00 | 940.97 | 79.59 | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1595.35 | 0.00 | -546.19 | -2263.75 |
RETAIL_2_FLR_1 | 09-JAN-10:41 | 0.00 | 0.00 | 1069.50 | 0.00 | 0.00 | 0.00 | 242.30 | 230.43 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -210.97 | -1623.76 |
MECH_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 1668.81 | 0.00 | 0.00 | 0.00 | 51.44 | 185.63 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -500.01 | -1715.14 |
STORAGE_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 1207.07 | 0.00 | 0.00 | 0.00 | 40.19 | 94.17 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -284.96 | -1145.69 |
LAUNDRY_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 6997.40 | 0.00 | 0.00 | 0.00 | 774.80 | 50.40 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -661.41 | -16487.38 |
CAFE_FLR_1 | 21-DEC-10:51 | 0.00 | 0.00 | 8622.31 | 0.00 | 0.00 | 0.00 | 2817.70 | 119.64 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -794.80 | 0.00 | -1206.24 | -9914.22 |
LOBBY_FLR_1 | 09-JAN-10:41 | 0.00 | 0.00 | 18289.56 | 0.00 | 0.00 | 0.00 | 8016.43 | 2043.53 | 3694.97 | 25598.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3498.79 | -54144.15 |
ROOM_1_FLR_3 | 25-DEC-16:13 | 9404.06 | 371.02 | 0.00 | -371.02 | 0.00 | 0.00 | 148.00 | 277.50 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3239.09 | 0.00 | -1079.72 | -5732.00 |
ROOM_2_FLR_3 | 06-JAN-16:13 | 9403.59 | 357.58 | 0.00 | -357.58 | 0.00 | 0.00 | 266.57 | 235.42 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2726.65 | 0.00 | -1354.90 | -6024.19 |
ROOM_3_MULT19_FLR_3 | 19-DEC-05:00 | 34353.62 | 25232.24 | 0.00 | -25232.24 | 0.00 | 0.00 | 0.00 | 1104.51 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23273.91 | 0.00 | -7476.30 | -8041.16 |
ROOM_4_MULT19_FLR_3 | 06-JAN-16:02 | 51571.74 | 3434.76 | 0.00 | -3434.76 | 0.00 | 0.00 | 5585.68 | 2812.24 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19855.70 | 0.00 | -6908.44 | -36931.93 |
ROOM_5_FLR_3 | 25-DEC-16:13 | 9187.31 | 365.48 | 0.00 | -365.48 | 0.00 | 0.00 | 148.01 | 277.50 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3249.31 | 0.00 | -1077.42 | -5507.36 |
ROOM_6_FLR_3 | 06-JAN-16:13 | 9285.88 | 320.19 | 0.00 | -320.19 | 0.00 | 0.00 | 275.76 | 235.42 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3835.60 | 0.00 | -1338.52 | -4823.10 |
CORRIDOR_FLR_3 | 06-JAN-13:31 | 0.00 | 0.00 | 9584.45 | 0.00 | 0.00 | 0.00 | 1526.96 | 2074.80 | 0.00 | 7131.37 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1605.89 | -18711.70 |
ROOM_1_FLR_6 | 25-DEC-16:13 | 2726.11 | 91.86 | 0.00 | -91.86 | 0.00 | 0.00 | 37.00 | 69.37 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -809.71 | 0.00 | -270.06 | -1808.03 |
ROOM_2_FLR_6 | 06-JAN-16:13 | 2711.90 | 88.75 | 0.00 | -88.75 | 0.00 | 0.00 | 66.68 | 58.86 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -690.34 | 0.00 | -338.99 | -1858.15 |
ROOM_3_MULT9_FLR_6 | 11-DEC-16:13 | 12888.21 | 602.75 | 0.00 | -602.75 | 0.00 | 0.00 | 599.31 | 333.03 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4041.00 | 0.00 | -1331.54 | -8889.30 |
BANQUET_FLR_6 | 09-JAN-10:41 | 0.00 | 0.00 | 6690.46 | 0.00 | 0.00 | 0.00 | 4744.95 | 636.64 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1838.98 | 0.00 | -790.73 | -16190.24 |
DINING_FLR_6 | 09-JAN-10:41 | 0.00 | 0.00 | 6478.87 | 0.00 | 0.00 | 0.00 | 4704.33 | 636.64 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1865.49 | 0.00 | -795.65 | -15906.60 |
KITCHEN_FLR_6 | 14-JAN-04:51 | 0.00 | 0.00 | 3218.45 | 0.00 | 0.00 | 0.00 | 1895.67 | 134.55 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1947.81 | 0.00 | -712.76 | -8004.07 |
CORRIDOR_FLR_6 | 07-JAN-04:22 | 0.00 | 0.00 | 6422.55 | 0.00 | 0.00 | 0.00 | 1853.06 | 219.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2241.11 | 0.00 | -694.99 | -5559.10 |
Total Facility | 14-JAN-04:51 | 100837.35 | 26978.70 | 49623.13 | -26978.70 | 0.00 | 0.00 | 116338.87 | 7923.41 | 31990.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -93816.65 | 0.00 | -34102.19 | -178794.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.8548 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.7185 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.9274 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6650 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8087 | 2.8087 | 1.3735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4649 | 0.4649 | 0.2273 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2496 | 0.2496 | 0.1221 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1834 | 0.1834 | 0.0897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1214 | 0.1214 | 0.0594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4031 | 3.4031 | 1.6641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8302 | 1.8302 | 0.8950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2277 | 5.2277 | 2.5563 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7161 | 1.7161 | 0.8392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2528 | 2.2528 | 1.1016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3611 | 2.3611 | 1.1546 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3990 | 2.3990 | 1.1731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8367 | 0.8367 | 0.4092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.8548 | 23.7185 | 23.8548 | 11.6650 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4044 | 1.4044 | 1.3735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2324 | 0.2324 | 0.2273 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1248 | 0.1248 | 0.1221 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0917 | 0.0917 | 0.0897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0607 | 0.0607 | 0.0594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7016 | 1.7016 | 1.6641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9151 | 0.9151 | 0.8950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6138 | 2.6138 | 2.5563 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8581 | 0.8581 | 0.8392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1264 | 1.1264 | 1.1016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1806 | 1.1806 | 1.1546 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1995 | 1.1995 | 1.1731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4184 | 0.4184 | 0.4092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.9274 | 11.6650 | 11.6650 | 11.6650 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 590.00 |
Number of hours cooling loads not met | 351.83 |
Number of hours not met | 941.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3159.45 | 902207.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 587.21 | 206113.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 866.40 | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 261.66 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.06 | 1847.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 563.55 | 42620.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 86.71 | 5652.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 229.15 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4743.91 | 3563.13 | 314198.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.26 | 2041.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.80 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.33 | 5054.87 |
Natural Gas | 1788.84 | 8511.42 |
Additional | 0.00 | 0.00 |
Total | 3508.17 | 13566.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 76.37 |
Space Heating | 0.00 |
Space Cooling | 51.76 |
Fans (All) | 49.67 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 445.55 |
Subtotal | 445.55 |
Natural Gas [MJ/m2] | |
Space Heating | 278.48 |
Service Water Heating | 314.06 |
Miscellaneous (All) | 750.22 |
Subtotal | 750.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.39 |
Space Heating | 23.29 |
Space Cooling | 4.33 |
Fans (All) | 4.15 |
Service Water Heating | 26.93 |
Receptacle Equipment | 25.41 |
Miscellaneous | 9.50 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8616.83 | 143.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8645.33 | 114.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8724.33 | 35.67 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8564.50 | 195.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8592.83 | 167.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8564.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 195.50 | 0.00 | 0.00 | 0.00 |
Average | 8728.53 | 31.47 | 0.00 | 0.00 | 0.00 |
Sum | 192027.67 | 692.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37202.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4107.50 | 46.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4110.00 | 44.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4077.50 | 76.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4084.17 | 69.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108258.33 | 10.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 76.50 | 0.00 | 0.00 | 0.00 |
Average | 288875.77 | 11.27 | 0.00 | 0.00 | 0.00 |
Sum | 6355267.00 | 248.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8720.00 | 40.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8450.33 | 309.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8389.33 | 370.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8515.33 | 244.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8541.17 | 218.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8633.50 | 126.50 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8655.17 | 104.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8462.50 | 297.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8493.67 | 266.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8673.67 | 86.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8373.50 | 386.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8416.83 | 343.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8373.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 386.50 | 0.00 | 0.00 | 0.00 |
Average | 8630.53 | 129.47 | 0.00 | 0.00 | 0.00 |
Sum | 189871.67 | 2848.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58724.00 | 432.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 671734.83 | 38682.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1983346.00 | 132083.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4020.00 | 134.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4036.50 | 117.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4143.67 | 10.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4108.83 | 45.17 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4125.17 | 28.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 3984.83 | 169.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4001.17 | 152.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4096.67 | 57.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1165147.33 | 80567.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1173420.67 | 72294.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107969.50 | 299.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1983346.00 | 132083.00 | 0.00 | 0.00 | 0.00 |
Average | 274110.96 | 14776.08 | 0.00 | 0.00 | 0.00 |
Sum | 6030441.17 | 325073.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:36
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366763E+11 | 34464.12 | 25-JAN-21:00 | -27.2 | -27.4 | 0.655569E+10 | 4836.93 | 24-JAN-22:19 | -27.2 | -27.4 |
February | 0.307025E+11 | 32705.48 | 24-FEB-22:52 | -23.9 | -24.3 | 0.643682E+10 | 4781.34 | 10-FEB-22:10 | -23.9 | -24.3 |
March | 0.304124E+11 | 31400.92 | 12-MAR-03:51 | -23.9 | -24.1 | 0.713397E+10 | 4725.72 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.290823E+11 | 22880.53 | 12-APR-07:40 | 5.00 | 1.49 | 0.697039E+10 | 4637.62 | 18-APR-21:30 | 3.90 | -0.9 |
May | 0.319263E+11 | 24412.28 | 08-MAY-07:05 | 5.82 | 3.91 | 0.736168E+10 | 4648.62 | 09-MAY-22:10 | 4.68 | 2.39 |
June | 0.326503E+11 | 24185.04 | 17-JUN-00:08 | 6.20 | 5.93 | 0.729297E+10 | 4710.43 | 02-JUN-22:10 | 6.20 | 5.93 |
July | 0.363370E+11 | 24565.69 | 02-JUL-04:44 | 6.38 | 6.38 | 0.784639E+10 | 4837.10 | 07-JUL-21:30 | 10.85 | 10.06 |
August | 0.391043E+11 | 33797.05 | 25-AUG-02:30 | 9.15 | 9.03 | 0.813866E+10 | 4910.78 | 18-AUG-23:19 | 9.15 | 9.03 |
September | 0.390237E+11 | 37921.97 | 14-SEP-23:35 | 6.30 | 5.78 | 0.791930E+10 | 5022.20 | 12-SEP-22:10 | 6.30 | 5.78 |
October | 0.401877E+11 | 39184.36 | 26-OCT-05:56 | 7.20 | 5.87 | 0.819906E+10 | 5009.99 | 25-OCT-22:19 | 7.20 | 5.87 |
November | 0.375179E+11 | 37115.21 | 19-NOV-23:08 | 5.60 | 2.44 | 0.790423E+10 | 4906.78 | 01-NOV-23:00 | 5.60 | 2.44 |
December | 0.387026E+11 | 33976.41 | 02-DEC-06:00 | -27.8 | -28.0 | 0.714707E+10 | 4837.03 | 01-DEC-00:20 | -27.8 | -28.0 |
Annual Sum or Average | 0.422323E+12 | 0.889062E+11 | ||||||||
Minimum of Months | 0.290823E+11 | 22880.53 | -27.8 | -28.0 | 0.643682E+10 | 4637.62 | -27.8 | -28.0 | ||
Maximum of Months | 0.401877E+11 | 39184.36 | 9.15 | 9.03 | 0.819906E+10 | 5022.20 | 10.85 | 10.06 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343485E+09 | 2140.20 | 27-JAN-13:40 | -14.8 | -15.9 | 0.549622E+09 | 364.19 | 23-JAN-03:20 | -14.8 | -15.9 |
February | 0.103606E+10 | 4063.26 | 28-FEB-15:28 | 6.10 | 1.55 | 0.544897E+09 | 364.34 | 13-FEB-05:30 | 6.10 | 1.55 |
March | 0.153958E+10 | 4375.51 | 26-MAR-13:10 | 8.40 | 4.17 | 0.627014E+09 | 417.30 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.278487E+10 | 4612.79 | 19-APR-14:03 | 6.70 | 0.87 | 0.625894E+09 | 429.71 | 13-APR-21:30 | 6.70 | 0.87 |
May | 0.446909E+10 | 3901.06 | 18-MAY-13:10 | 28.25 | 16.75 | 0.672062E+09 | 465.03 | 25-MAY-21:19 | 22.50 | 16.44 |
June | 0.474010E+10 | 4040.80 | 30-JUN-13:00 | 31.70 | 24.46 | 0.664438E+09 | 483.92 | 29-JUN-21:19 | 31.70 | 24.46 |
July | 0.544842E+10 | 4143.34 | 23-JUL-13:10 | 30.00 | 22.77 | 0.709011E+09 | 470.47 | 24-JUL-21:30 | 19.15 | 17.68 |
August | 0.525250E+10 | 4508.85 | 26-AUG-12:40 | 25.40 | 19.23 | 0.699338E+09 | 467.78 | 08-AUG-21:30 | 25.40 | 19.23 |
September | 0.422231E+10 | 4534.92 | 01-SEP-13:20 | 24.80 | 18.00 | 0.642472E+09 | 452.38 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.264534E+10 | 5325.69 | 09-OCT-13:21 | 5.85 | 1.19 | 0.640732E+09 | 438.00 | 19-OCT-21:30 | 12.50 | 9.82 |
November | 0.101641E+10 | 5513.14 | 17-NOV-11:31 | 8.17 | 2.57 | 0.603853E+09 | 376.52 | 01-NOV-23:00 | 8.17 | 2.57 |
December | 0.239437E+09 | 2261.19 | 10-DEC-12:22 | -23.6 | -24.1 | 0.569625E+09 | 364.31 | 14-DEC-05:30 | -23.6 | -23.9 |
Annual Sum or Average | 0.337376E+11 | 0.754896E+10 | ||||||||
Minimum of Months | 0.239437E+09 | 2140.20 | -23.6 | -24.1 | 0.544897E+09 | 364.19 | -23.6 | -23.9 | ||
Maximum of Months | 0.544842E+10 | 5513.14 | 31.70 | 24.46 | 0.709011E+09 | 483.92 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156258E+10 | 2659.35 | 25-JAN-20:01 | -24.0 | -24.2 | 0.678062E+09 | 479.24 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.173208E+10 | 2513.67 | 13-FEB-21:22 | -23.9 | -24.3 | 0.666328E+09 | 518.89 | 22-FEB-22:19 | -6.1 | -7.7 |
March | 0.221406E+10 | 2117.81 | 07-MAR-00:41 | -23.8 | -24.0 | 0.782716E+09 | 570.31 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.257650E+10 | 3151.70 | 18-APR-21:21 | 3.90 | -0.9 | 0.823343E+09 | 580.31 | 18-APR-21:19 | 3.90 | -0.9 |
May | 0.308587E+10 | 2267.80 | 06-MAY-23:08 | 6.67 | 2.76 | 0.912680E+09 | 569.70 | 05-MAY-00:30 | 6.67 | 2.76 |
June | 0.315962E+10 | 2220.77 | 30-JUN-20:10 | 23.77 | 17.76 | 0.895760E+09 | 575.88 | 16-JUN-23:49 | 23.77 | 17.76 |
July | 0.345329E+10 | 2226.89 | 02-JUL-04:44 | 6.38 | 6.38 | 0.941302E+09 | 569.55 | 07-JUL-21:30 | 10.85 | 10.06 |
August | 0.332953E+10 | 2489.91 | 25-AUG-05:45 | 8.22 | 8.16 | 0.937853E+09 | 569.55 | 04-AUG-21:40 | 8.22 | 8.16 |
September | 0.291683E+10 | 3249.73 | 05-SEP-21:08 | 6.93 | 6.14 | 0.879040E+09 | 582.67 | 12-SEP-22:10 | 6.93 | 6.18 |
October | 0.263222E+10 | 2626.78 | 26-OCT-20:43 | 4.82 | 3.34 | 0.855208E+09 | 578.03 | 25-OCT-22:19 | 4.82 | 3.34 |
November | 0.215976E+10 | 2001.69 | 02-NOV-01:07 | 6.02 | 4.77 | 0.758238E+09 | 544.94 | 17-NOV-22:10 | 2.62 | -1.0 |
December | 0.158395E+10 | 1510.70 | 02-DEC-00:22 | -23.8 | -24.0 | 0.699436E+09 | 481.40 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.304063E+11 | 0.982997E+10 | ||||||||
Minimum of Months | 0.156258E+10 | 1510.70 | -24.0 | -24.3 | 0.666328E+09 | 479.24 | -24.0 | -24.2 | ||
Maximum of Months | 0.345329E+10 | 3249.73 | 23.77 | 17.76 | 0.941302E+09 | 582.67 | 23.77 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30644685.86 | 558.77 | 19-JAN-22:00 | -3.9 | -4.6 | 0.141464E+09 | 89.14 | 25-JAN-04:00 | -23.9 | -24.1 |
February | 0.169732E+09 | 774.52 | 20-FEB-19:05 | 4.32 | 1.27 | 0.135768E+09 | 92.30 | 21-FEB-22:10 | -3.0 | -4.4 |
March | 0.516454E+09 | 1277.38 | 31-MAR-21:49 | 4.58 | 0.73 | 0.153002E+09 | 99.50 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.141531E+10 | 1420.89 | 15-APR-01:03 | 6.60 | 5.55 | 0.155396E+09 | 107.42 | 18-APR-21:30 | 3.90 | -0.9 |
May | 0.207111E+10 | 1570.34 | 20-MAY-06:36 | 5.93 | 3.35 | 0.181761E+09 | 120.45 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.222425E+10 | 1712.29 | 30-JUN-20:00 | 24.40 | 17.93 | 0.184409E+09 | 120.45 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.243728E+10 | 1645.16 | 02-JUL-04:44 | 6.38 | 6.38 | 0.197005E+09 | 120.45 | 01-JUL-01:10 | 6.38 | 6.38 |
August | 0.230771E+10 | 1539.24 | 18-AUG-23:22 | 7.25 | 7.10 | 0.193567E+09 | 120.45 | 25-AUG-21:19 | 17.43 | 16.14 |
September | 0.198561E+10 | 1636.12 | 15-SEP-01:55 | 6.10 | 5.58 | 0.176162E+09 | 120.45 | 01-SEP-21:40 | 6.10 | 5.58 |
October | 0.162917E+10 | 1551.55 | 23-OCT-22:20 | 6.30 | 4.43 | 0.164103E+09 | 108.80 | 20-OCT-21:30 | 6.30 | 4.43 |
November | 0.766272E+09 | 1378.03 | 02-NOV-01:07 | 6.02 | 4.77 | 0.148065E+09 | 98.39 | 01-NOV-21:10 | 6.02 | 4.77 |
December | 43454175.15 | 604.45 | 05-DEC-22:00 | 0.00 | -0.0 | 0.146666E+09 | 89.19 | 05-DEC-22:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.155970E+11 | 0.197737E+10 | ||||||||
Minimum of Months | 30644685.86 | 558.77 | -3.9 | -4.6 | 0.135768E+09 | 89.14 | -23.9 | -24.1 | ||
Maximum of Months | 0.243728E+10 | 1712.29 | 24.40 | 17.93 | 0.197005E+09 | 120.45 | 21.73 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71526.48 | 23.96 | 19-JAN-21:50 | -3.8 | -4.5 | 0.106140E+09 | 68.57 | 25-JAN-04:49 | -23.6 | -23.8 |
February | 21012903.01 | 264.72 | 21-FEB-21:00 | -1.1 | -2.5 | 0.103696E+09 | 68.58 | 13-FEB-05:30 | -1.1 | -2.5 |
March | 0.136978E+09 | 811.60 | 31-MAR-21:49 | 4.58 | 0.73 | 0.116968E+09 | 72.82 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.696868E+09 | 912.10 | 15-APR-01:03 | 6.60 | 5.55 | 0.116067E+09 | 78.57 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.128938E+10 | 1003.86 | 20-MAY-06:36 | 5.93 | 3.35 | 0.134151E+09 | 89.79 | 25-MAY-21:40 | 22.20 | 16.43 |
June | 0.139069E+10 | 1013.03 | 08-JUN-01:55 | 6.10 | 5.88 | 0.136879E+09 | 92.66 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.152660E+10 | 1057.06 | 02-JUL-04:44 | 6.38 | 6.38 | 0.146421E+09 | 92.44 | 24-JUL-21:30 | 19.15 | 17.68 |
August | 0.145103E+10 | 981.30 | 18-AUG-23:22 | 7.25 | 7.10 | 0.143104E+09 | 90.49 | 09-AUG-21:40 | 7.25 | 7.10 |
September | 0.123282E+10 | 1050.67 | 15-SEP-01:55 | 6.10 | 5.58 | 0.129232E+09 | 88.63 | 01-SEP-21:30 | 6.10 | 5.58 |
October | 0.848740E+09 | 987.70 | 23-OCT-22:20 | 6.30 | 4.43 | 0.121476E+09 | 79.53 | 22-OCT-23:30 | 6.30 | 4.43 |
November | 0.209991E+09 | 889.03 | 02-NOV-01:07 | 6.02 | 4.77 | 0.113006E+09 | 72.16 | 01-NOV-22:10 | 6.02 | 4.77 |
December | 731329.47 | 96.89 | 05-DEC-22:00 | 0.00 | -0.0 | 0.110791E+09 | 68.57 | 14-DEC-05:30 | -23.6 | -23.9 |
Annual Sum or Average | 0.880492E+10 | 0.147793E+10 | ||||||||
Minimum of Months | 71526.48 | 23.96 | -3.8 | -4.5 | 0.103696E+09 | 68.57 | -23.6 | -23.9 | ||
Maximum of Months | 0.152660E+10 | 1057.06 | 7.25 | 7.10 | 0.146421E+09 | 92.66 | 22.20 | 17.68 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462148E+11 | 40321.17 | 25-JAN-20:01 | -24.0 | -24.2 | 0.486914E+09 | 381.60 | 23-JAN-22:10 | -24.0 | -24.2 |
February | 0.422420E+11 | 39386.15 | 04-FEB-19:06 | 4.22 | 0.37 | 0.494055E+09 | 381.58 | 22-FEB-22:10 | -6.1 | -7.6 |
March | 0.477717E+11 | 50171.01 | 28-MAR-19:37 | 4.80 | 1.11 | 0.581619E+09 | 525.65 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.479139E+11 | 49409.49 | 11-APR-20:49 | 5.83 | 1.30 | 0.582915E+09 | 510.06 | 18-APR-21:19 | 4.27 | -0.7 |
May | 0.516407E+11 | 49339.13 | 08-MAY-20:57 | 5.60 | 3.57 | 0.607142E+09 | 475.10 | 09-MAY-22:49 | 4.22 | 2.06 |
June | 0.508011E+11 | 41995.81 | 03-JUN-21:50 | 8.17 | 5.80 | 0.587007E+09 | 451.24 | 02-JUN-21:49 | 8.17 | 5.80 |
July | 0.527363E+11 | 38862.08 | 21-JUL-20:00 | 22.20 | 20.61 | 0.605012E+09 | 381.69 | 12-JUL-21:19 | 22.20 | 20.61 |
August | 0.524686E+11 | 38776.97 | 08-AUG-20:00 | 25.00 | 20.33 | 0.605847E+09 | 431.18 | 18-AUG-21:00 | 7.20 | 6.97 |
September | 0.494837E+11 | 51063.98 | 23-SEP-21:46 | 4.60 | 4.11 | 0.588003E+09 | 528.01 | 12-SEP-22:10 | 4.60 | 4.11 |
October | 0.494841E+11 | 53178.45 | 16-OCT-19:27 | 5.00 | 3.16 | 0.607665E+09 | 486.80 | 25-OCT-22:19 | 6.50 | 4.89 |
November | 0.463085E+11 | 49084.52 | 17-NOV-20:34 | 3.67 | -0.6 | 0.574522E+09 | 413.29 | 01-NOV-23:00 | 3.67 | -0.6 |
December | 0.461702E+11 | 38905.34 | 23-DEC-21:42 | -23.9 | -24.3 | 0.511043E+09 | 381.61 | 08-DEC-22:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.583236E+12 | 0.683174E+10 | ||||||||
Minimum of Months | 0.422420E+11 | 38776.97 | -24.0 | -24.3 | 0.486914E+09 | 381.58 | -24.0 | -24.3 | ||
Maximum of Months | 0.527363E+11 | 53178.45 | 25.00 | 20.61 | 0.607665E+09 | 528.01 | 22.20 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102338E+11 | 9078.81 | 01-JAN-10:22 | -23.6 | -23.8 | 0.752264E+10 | 5196.79 | 19-JAN-22:40 | -3.9 | -4.6 |
February | 0.124072E+11 | 16533.49 | 28-FEB-15:28 | 6.10 | 1.55 | 0.748716E+10 | 5963.87 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.153630E+11 | 17344.63 | 31-MAR-15:18 | 8.50 | 3.01 | 0.878326E+10 | 6649.49 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.182968E+11 | 18321.84 | 19-APR-14:03 | 6.70 | 0.87 | 0.910535E+10 | 6781.23 | 14-APR-02:30 | 6.70 | 0.87 |
May | 0.218013E+11 | 16152.25 | 02-MAY-23:57 | 6.70 | 2.95 | 0.100681E+11 | 6679.55 | 16-MAY-03:39 | 8.13 | 6.00 |
June | 0.220395E+11 | 15572.05 | 17-JUN-00:08 | 6.20 | 5.93 | 0.992641E+10 | 6641.94 | 16-JUN-23:49 | 6.20 | 5.93 |
July | 0.240712E+11 | 15085.74 | 02-JUL-04:44 | 6.38 | 6.38 | 0.104477E+11 | 6493.07 | 18-JUL-03:30 | 8.30 | 8.06 |
August | 0.237527E+11 | 15672.23 | 18-AUG-23:22 | 7.25 | 7.10 | 0.104400E+11 | 6468.66 | 18-AUG-23:49 | 7.62 | 7.56 |
September | 0.211436E+11 | 19277.18 | 15-SEP-00:55 | 6.10 | 5.81 | 0.969867E+10 | 6758.15 | 28-SEP-03:30 | 6.65 | 5.00 |
October | 0.183464E+11 | 19864.95 | 09-OCT-11:00 | 3.30 | -0.7 | 0.938806E+10 | 6847.78 | 25-OCT-22:19 | 6.50 | 4.89 |
November | 0.135906E+11 | 20434.73 | 17-NOV-11:31 | 8.17 | 2.57 | 0.838182E+10 | 6247.11 | 02-NOV-00:10 | 8.17 | 2.57 |
December | 0.944143E+10 | 10383.21 | 10-DEC-12:28 | -23.6 | -24.1 | 0.772425E+10 | 5271.56 | 05-DEC-22:40 | -23.6 | -24.1 |
Annual Sum or Average | 0.210488E+12 | 0.108973E+12 | ||||||||
Minimum of Months | 0.944143E+10 | 9078.81 | -23.6 | -24.1 | 0.748716E+10 | 5196.79 | -23.6 | -24.1 | ||
Maximum of Months | 0.240712E+11 | 20434.73 | 8.50 | 7.10 | 0.104477E+11 | 6847.78 | 8.30 | 8.06 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.428676E+11 | 56670.78 | 25-JAN-20:01 | -24.0 | -24.2 | 0.236537E+11 | 17145.05 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.438023E+11 | 55561.89 | 24-FEB-22:52 | -23.9 | -24.3 | 0.235446E+11 | 18441.40 | 22-FEB-22:49 | -23.9 | -24.3 |
March | 0.519725E+11 | 66958.61 | 31-MAR-21:41 | 4.58 | 0.73 | 0.277767E+11 | 19789.96 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.573763E+11 | 66796.05 | 18-APR-22:47 | 4.63 | 0.33 | 0.289230E+11 | 19774.10 | 18-APR-21:19 | 4.63 | 0.33 |
May | 0.675242E+11 | 64895.19 | 06-MAY-00:47 | 6.22 | 2.18 | 0.315388E+11 | 19997.39 | 09-MAY-22:49 | 4.22 | 2.06 |
June | 0.689887E+11 | 64172.58 | 17-JUN-01:10 | 6.42 | 5.93 | 0.308623E+11 | 19945.80 | 16-JUN-04:10 | 6.42 | 5.93 |
July | 0.747759E+11 | 52737.64 | 08-JUL-01:27 | 8.60 | 8.15 | 0.320956E+11 | 19316.50 | 08-JUL-01:00 | 9.40 | 8.81 |
August | 0.730091E+11 | 58073.25 | 05-AUG-01:28 | 9.15 | 8.70 | 0.321692E+11 | 19542.64 | 25-AUG-04:00 | 7.80 | 7.48 |
September | 0.646875E+11 | 70838.71 | 14-SEP-23:35 | 6.30 | 5.78 | 0.306017E+11 | 20170.43 | 12-SEP-22:10 | 6.30 | 5.78 |
October | 0.590928E+11 | 69286.21 | 22-OCT-22:18 | 6.70 | 5.40 | 0.301390E+11 | 20134.32 | 25-OCT-22:19 | 6.50 | 4.89 |
November | 0.497861E+11 | 49665.58 | 17-NOV-21:15 | 3.13 | -0.9 | 0.269693E+11 | 19183.32 | 17-NOV-22:00 | 1.70 | -1.4 |
December | 0.422993E+11 | 47888.10 | 02-DEC-00:31 | -23.9 | -24.2 | 0.244922E+11 | 17257.99 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.696182E+12 | 0.342766E+12 | ||||||||
Minimum of Months | 0.422993E+11 | 47888.10 | -24.0 | -24.3 | 0.235446E+11 | 17145.05 | -24.0 | -24.3 | ||
Maximum of Months | 0.747759E+11 | 70838.71 | 9.15 | 8.70 | 0.321692E+11 | 20170.43 | 9.40 | 8.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16293447.45 | 877.07 | 17-JAN-16:03 | -4.2 | -5.3 | 91973742.60 | 56.69 | 14-JAN-05:10 | -4.2 | -5.3 |
February | 73052229.95 | 3903.38 | 20-FEB-16:01 | 8.62 | 2.77 | 84368577.31 | 56.69 | 26-FEB-02:20 | -11.1 | -12.0 |
March | 0.204619E+09 | 4028.01 | 31-MAR-15:01 | 8.40 | 2.82 | 94383355.03 | 56.69 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.589018E+09 | 4690.71 | 11-APR-18:11 | 13.90 | 5.53 | 94636414.10 | 75.69 | 17-APR-18:10 | 15.63 | 7.70 |
May | 0.143175E+10 | 5031.81 | 06-MAY-18:42 | 14.68 | 6.91 | 0.105683E+09 | 90.68 | 15-MAY-21:10 | 15.82 | 10.59 |
June | 0.169215E+10 | 4345.12 | 07-JUN-21:41 | 13.27 | 10.80 | 0.105740E+09 | 96.11 | 20-JUN-21:10 | 16.65 | 12.83 |
July | 0.215543E+10 | 4604.28 | 04-JUL-16:32 | 24.63 | 19.94 | 0.111068E+09 | 103.05 | 06-JUL-21:10 | 16.38 | 13.60 |
August | 0.171524E+10 | 4499.42 | 05-AUG-20:41 | 15.50 | 12.15 | 0.109756E+09 | 94.86 | 04-AUG-21:10 | 15.50 | 12.15 |
September | 0.921035E+09 | 4558.06 | 04-SEP-18:01 | 14.03 | 8.92 | 99206079.34 | 85.82 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 0.331782E+09 | 4137.39 | 20-OCT-18:11 | 12.23 | 7.41 | 95995675.35 | 58.25 | 19-OCT-18:49 | 12.23 | 7.41 |
November | 51350042.14 | 3822.01 | 17-NOV-16:01 | 9.45 | 2.90 | 90352422.79 | 56.69 | 01-NOV-01:00 | 9.45 | 2.90 |
December | 12206626.10 | 569.68 | 24-DEC-08:62 | -31.1 | -31.3 | 92158313.91 | 56.69 | 12-DEC-04:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.919392E+10 | 0.117532E+10 | ||||||||
Minimum of Months | 12206626.10 | 569.68 | -31.1 | -31.3 | 84368577.31 | 56.69 | -31.1 | -31.3 | ||
Maximum of Months | 0.215543E+10 | 5031.81 | 24.63 | 19.94 | 0.111068E+09 | 103.05 | 16.65 | 13.60 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5636197.46 | 597.08 | 20-JAN-16:04 | -5.9 | -7.4 | 91251644.83 | 56.69 | 14-JAN-05:10 | -5.9 | -7.4 |
February | 23044444.29 | 2240.40 | 28-FEB-16:02 | 6.02 | 1.46 | 83578618.50 | 56.69 | 28-FEB-04:19 | 6.02 | 1.46 |
March | 94077264.69 | 3781.05 | 27-MAR-18:01 | 5.92 | 2.01 | 93334393.35 | 56.69 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.377388E+09 | 4418.33 | 11-APR-18:11 | 13.90 | 5.53 | 93331341.44 | 68.34 | 11-APR-18:10 | 13.90 | 5.53 |
May | 0.122658E+10 | 4812.35 | 06-MAY-18:42 | 14.68 | 6.91 | 0.104911E+09 | 87.56 | 15-MAY-21:10 | 15.82 | 10.59 |
June | 0.156563E+10 | 4155.76 | 07-JUN-21:41 | 13.27 | 10.80 | 0.105475E+09 | 95.19 | 20-JUN-21:10 | 16.65 | 12.83 |
July | 0.195675E+10 | 4287.43 | 05-JUL-16:51 | 24.40 | 18.25 | 0.110689E+09 | 102.34 | 06-JUL-20:10 | 18.43 | 14.14 |
August | 0.144117E+10 | 4321.30 | 05-AUG-20:41 | 15.50 | 12.15 | 0.108723E+09 | 92.12 | 04-AUG-21:10 | 15.50 | 12.15 |
September | 0.641085E+09 | 4218.86 | 04-SEP-18:01 | 14.03 | 8.92 | 97842873.45 | 80.76 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 0.160421E+09 | 3740.28 | 21-OCT-15:02 | 20.00 | 11.21 | 94900071.65 | 56.69 | 19-OCT-21:30 | 20.00 | 11.21 |
November | 28580493.30 | 688.10 | 15-NOV-19:04 | 4.32 | 1.54 | 89701081.54 | 56.69 | 01-NOV-02:49 | 4.32 | 1.54 |
December | 5629939.77 | 566.02 | 24-DEC-08:62 | -31.1 | -31.3 | 91886741.64 | 56.69 | 08-DEC-04:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.752599E+10 | 0.116562E+10 | ||||||||
Minimum of Months | 5629939.77 | 566.02 | -31.1 | -31.3 | 83578618.50 | 56.69 | -31.1 | -31.3 | ||
Maximum of Months | 0.195675E+10 | 4812.35 | 24.40 | 18.25 | 0.110689E+09 | 102.34 | 20.00 | 14.14 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47565135.27 | 362.98 | 05-JAN-12:00 | -28.3 | -28.6 | 0.00 | 0.00 | 01-JAN-00:10 | -28.3 | -28.6 |
February | 0.100869E+09 | 381.00 | 22-FEB-14:30 | -0.6 | -3.8 | 0.00 | 0.00 | 01-FEB-00:10 | -0.6 | -3.8 |
March | 0.157459E+09 | 512.99 | 20-MAR-12:30 | 1.70 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | 1.70 | -1.1 |
April | 0.329311E+09 | 649.72 | 13-APR-13:20 | 18.17 | 6.98 | 0.00 | 0.00 | 01-APR-00:10 | 18.17 | 6.98 |
May | 0.519685E+09 | 682.10 | 18-MAY-13:10 | 28.25 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.25 | 16.75 |
June | 0.575645E+09 | 676.18 | 30-JUN-13:00 | 31.70 | 24.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.46 |
July | 0.716270E+09 | 717.76 | 23-JUL-13:20 | 30.00 | 22.71 | 0.00 | 0.00 | 01-JUL-00:10 | 30.00 | 22.71 |
August | 0.670299E+09 | 785.09 | 25-AUG-13:10 | 27.38 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 27.38 | 18.58 |
September | 0.509672E+09 | 789.59 | 01-SEP-13:10 | 24.60 | 17.97 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 17.97 |
October | 0.330016E+09 | 934.00 | 22-OCT-12:30 | 17.50 | 12.84 | 0.00 | 0.00 | 01-OCT-00:10 | 17.50 | 12.84 |
November | 0.104882E+09 | 391.62 | 17-NOV-13:30 | 10.30 | 3.32 | 0.00 | 0.00 | 01-NOV-00:10 | 10.30 | 3.32 |
December | 28624573.08 | 351.06 | 24-DEC-12:00 | -27.2 | -27.6 | 0.00 | 0.00 | 01-DEC-00:10 | -27.2 | -27.6 |
Annual Sum or Average | 0.409030E+10 | 0.00 | ||||||||
Minimum of Months | 28624573.08 | 351.06 | -28.3 | -28.6 | 0.00 | 0.00 | -28.3 | -28.6 | ||
Maximum of Months | 0.716270E+09 | 934.00 | 31.70 | 24.46 | 0.00 | 0.00 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18226361.11 | 414.96 | 26-JAN-08:61 | -32.1 | -32.2 | 89540580.31 | 56.69 | 02-JAN-00:20 | -32.1 | -32.2 |
February | 28893531.00 | 407.26 | 14-FEB-08:61 | -31.2 | -31.4 | 83541134.64 | 56.69 | 28-FEB-04:19 | -15.6 | -16.0 |
March | 55080532.92 | 443.81 | 31-MAR-15:03 | 8.40 | 2.82 | 93770031.19 | 56.69 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.180432E+09 | 1089.80 | 13-APR-19:41 | 14.60 | 6.84 | 92377680.59 | 56.69 | 13-APR-22:10 | 11.52 | 6.37 |
May | 0.540098E+09 | 1168.95 | 21-MAY-21:01 | 13.12 | 7.18 | 99908640.07 | 76.03 | 26-MAY-21:49 | 16.87 | 14.10 |
June | 0.678312E+09 | 1168.43 | 07-JUN-08:51 | 21.10 | 11.94 | 99538487.22 | 78.25 | 07-JUN-21:30 | 14.20 | 11.20 |
July | 0.749695E+09 | 1179.57 | 05-JUL-21:51 | 17.20 | 13.25 | 0.103883E+09 | 78.71 | 26-JUL-21:10 | 13.03 | 11.94 |
August | 0.614324E+09 | 1153.84 | 02-AUG-20:21 | 13.05 | 11.42 | 0.102458E+09 | 76.72 | 01-AUG-21:10 | 13.05 | 11.42 |
September | 0.401820E+09 | 1113.61 | 08-SEP-19:41 | 13.68 | 8.00 | 94597365.70 | 74.16 | 01-SEP-21:10 | 13.68 | 8.00 |
October | 0.171832E+09 | 1042.30 | 21-OCT-18:31 | 12.40 | 7.64 | 95183797.25 | 56.69 | 04-OCT-21:49 | 12.40 | 7.64 |
November | 59338290.89 | 464.57 | 01-NOV-18:03 | 12.02 | 10.48 | 90829874.97 | 56.69 | 01-NOV-21:10 | 12.62 | 11.43 |
December | 20769217.54 | 401.10 | 24-DEC-08:62 | -31.1 | -31.3 | 90847737.78 | 56.69 | 12-DEC-04:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.351882E+10 | 0.113648E+10 | ||||||||
Minimum of Months | 18226361.11 | 401.10 | -32.1 | -32.2 | 83541134.64 | 56.69 | -32.1 | -32.2 | ||
Maximum of Months | 0.749695E+09 | 1179.57 | 21.10 | 13.25 | 0.103883E+09 | 78.71 | 16.87 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14449528.72 | 596.43 | 26-JAN-08:61 | -32.1 | -32.2 | 91649701.46 | 56.69 | 03-JAN-04:19 | -32.1 | -32.2 |
February | 57803652.52 | 2469.57 | 28-FEB-16:02 | 6.02 | 1.46 | 84256040.26 | 56.69 | 24-FEB-05:19 | 6.02 | 1.46 |
March | 0.161747E+09 | 3621.43 | 31-MAR-15:01 | 8.40 | 2.82 | 94570286.38 | 56.69 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.626154E+09 | 3789.76 | 22-APR-19:21 | 13.05 | 5.48 | 94238502.32 | 57.33 | 13-APR-19:30 | 13.05 | 5.48 |
May | 0.139679E+10 | 4221.90 | 18-MAY-08:32 | 22.90 | 15.34 | 0.103100E+09 | 79.48 | 18-MAY-21:40 | 17.67 | 12.46 |
June | 0.183827E+10 | 4245.34 | 27-JUN-08:32 | 24.27 | 19.07 | 0.103315E+09 | 82.28 | 15-JUN-21:10 | 24.27 | 19.07 |
July | 0.216287E+10 | 4412.98 | 01-JUL-08:32 | 18.67 | 15.21 | 0.108654E+09 | 83.38 | 26-JUL-21:10 | 13.03 | 11.94 |
August | 0.169207E+10 | 4187.88 | 13-AUG-08:51 | 18.90 | 15.14 | 0.106743E+09 | 80.94 | 04-AUG-21:10 | 18.90 | 15.14 |
September | 0.951395E+09 | 3930.44 | 01-SEP-08:51 | 20.00 | 17.77 | 97261103.05 | 79.28 | 01-SEP-21:10 | 14.82 | 14.12 |
October | 0.316152E+09 | 3644.64 | 20-OCT-18:11 | 12.23 | 7.41 | 95707116.81 | 56.69 | 19-OCT-21:40 | 12.23 | 7.41 |
November | 64797016.82 | 2229.46 | 16-NOV-09:01 | -0.2 | -1.8 | 90277368.03 | 56.69 | 01-NOV-01:00 | -0.2 | -1.8 |
December | 11277393.56 | 565.58 | 24-DEC-08:62 | -31.1 | -31.3 | 92041814.72 | 56.69 | 29-DEC-04:19 | -15.8 | -16.1 |
Annual Sum or Average | 0.929377E+10 | 0.116181E+10 | ||||||||
Minimum of Months | 11277393.56 | 565.58 | -32.1 | -32.2 | 84256040.26 | 56.69 | -32.1 | -32.2 | ||
Maximum of Months | 0.216287E+10 | 4412.98 | 24.27 | 19.07 | 0.108654E+09 | 83.38 | 24.27 | 19.07 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5836792.25 | 589.67 | 26-JAN-08:61 | -32.1 | -32.2 | 90764974.90 | 56.69 | 24-JAN-04:19 | -32.1 | -32.2 |
February | 17285350.18 | 820.01 | 27-FEB-09:03 | -15.7 | -16.5 | 83417577.05 | 56.69 | 04-FEB-02:20 | -15.7 | -16.5 |
March | 67610816.36 | 3055.06 | 26-MAR-08:61 | -0.9 | -2.8 | 93376161.63 | 56.69 | 31-MAR-21:00 | 4.50 | 0.69 |
April | 0.388120E+09 | 3538.49 | 22-APR-08:61 | 8.77 | 2.60 | 93286306.93 | 56.69 | 13-APR-21:49 | 8.77 | 2.60 |
May | 0.118185E+10 | 4021.22 | 18-MAY-08:32 | 22.90 | 15.34 | 0.102573E+09 | 77.61 | 18-MAY-21:40 | 17.67 | 12.46 |
June | 0.170416E+10 | 4064.06 | 28-JUN-08:62 | 25.37 | 20.52 | 0.103175E+09 | 81.30 | 15-JUN-21:10 | 25.37 | 20.52 |
July | 0.195972E+10 | 4223.19 | 01-JUL-08:32 | 18.67 | 15.21 | 0.108351E+09 | 81.79 | 26-JUL-21:10 | 13.03 | 11.94 |
August | 0.141265E+10 | 4008.62 | 13-AUG-08:51 | 18.90 | 15.14 | 0.105908E+09 | 78.63 | 04-AUG-21:10 | 18.90 | 15.14 |
September | 0.662363E+09 | 3738.07 | 01-SEP-08:51 | 20.00 | 17.77 | 96245298.28 | 76.03 | 01-SEP-21:10 | 14.82 | 14.12 |
October | 0.152161E+09 | 3248.34 | 01-OCT-15:01 | 15.10 | 9.13 | 94597581.73 | 56.69 | 22-OCT-04:30 | 11.15 | 9.75 |
November | 28277884.05 | 870.19 | 17-NOV-09:03 | 0.05 | -2.1 | 89687877.49 | 56.69 | 01-NOV-02:49 | 0.05 | -2.1 |
December | 6291220.89 | 561.50 | 24-DEC-08:62 | -31.1 | -31.3 | 91639489.63 | 56.69 | 22-DEC-04:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.758633E+10 | 0.115302E+10 | ||||||||
Minimum of Months | 5836792.25 | 561.50 | -32.1 | -32.2 | 83417577.05 | 56.69 | -32.1 | -32.2 | ||
Maximum of Months | 0.195972E+10 | 4223.19 | 25.37 | 20.52 | 0.108351E+09 | 81.79 | 25.37 | 20.52 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547222E+09 | 1450.49 | 26-JAN-07:00 | -33.3 | -33.4 | 0.113923E+10 | 704.47 | 11-JAN-05:19 | -33.3 | -33.4 |
February | 0.849585E+09 | 2220.48 | 04-FEB-16:06 | 7.70 | 2.52 | 0.107216E+10 | 712.06 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.170811E+10 | 2929.69 | 31-MAR-21:49 | 4.58 | 0.73 | 0.120739E+10 | 769.86 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.335082E+10 | 3298.23 | 15-APR-01:03 | 6.60 | 5.55 | 0.122552E+10 | 835.04 | 23-APR-23:19 | 14.27 | 10.45 |
May | 0.478828E+10 | 3682.06 | 06-MAY-23:08 | 6.67 | 2.76 | 0.141980E+10 | 925.05 | 26-MAY-21:40 | 16.93 | 14.12 |
June | 0.509252E+10 | 3701.28 | 17-JUN-01:17 | 6.13 | 5.69 | 0.144351E+10 | 951.85 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.563714E+10 | 3822.07 | 02-JUL-04:44 | 6.38 | 6.38 | 0.155038E+10 | 951.85 | 07-JUL-21:30 | 10.85 | 10.06 |
August | 0.529066E+10 | 3479.72 | 18-AUG-23:22 | 7.25 | 7.10 | 0.150515E+10 | 946.59 | 01-AUG-21:30 | 7.25 | 7.10 |
September | 0.442109E+10 | 3816.77 | 15-SEP-01:55 | 6.10 | 5.58 | 0.134116E+10 | 923.80 | 01-SEP-21:40 | 6.10 | 5.58 |
October | 0.311066E+10 | 3501.13 | 20-OCT-04:03 | 6.88 | 6.88 | 0.124835E+10 | 833.63 | 22-OCT-23:30 | 6.40 | 5.11 |
November | 0.132969E+10 | 2917.82 | 16-NOV-14:26 | 6.95 | 1.79 | 0.116083E+10 | 732.45 | 02-NOV-00:10 | 6.95 | 1.79 |
December | 0.389376E+09 | 1100.25 | 24-DEC-07:30 | -31.1 | -31.3 | 0.116294E+10 | 704.49 | 14-DEC-05:30 | -31.1 | -31.3 |
Annual Sum or Average | 0.365152E+11 | 0.154764E+11 | ||||||||
Minimum of Months | 0.389376E+09 | 1100.25 | -33.3 | -33.4 | 0.107216E+10 | 704.47 | -33.3 | -33.4 | ||
Maximum of Months | 0.563714E+10 | 3822.07 | 7.70 | 7.10 | 0.155038E+10 | 951.85 | 18.85 | 15.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9432670.56 | 843.64 | 20-JAN-16:03 | -5.9 | -7.4 | 91745314.23 | 56.69 | 10-JAN-04:19 | -5.9 | -7.4 |
February | 64768988.88 | 4041.38 | 20-FEB-16:01 | 8.62 | 2.77 | 84090232.61 | 56.69 | 03-FEB-04:19 | 8.62 | 2.77 |
March | 0.200571E+09 | 4174.65 | 31-MAR-15:01 | 8.40 | 2.82 | 94092431.61 | 56.69 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.591718E+09 | 4987.01 | 11-APR-17:52 | 15.00 | 6.07 | 94580856.08 | 82.21 | 17-APR-18:19 | 15.17 | 7.51 |
May | 0.146663E+10 | 5299.53 | 06-MAY-18:42 | 14.68 | 6.91 | 0.106625E+09 | 100.10 | 04-MAY-18:40 | 14.68 | 6.91 |
June | 0.174695E+10 | 4575.33 | 07-JUN-21:41 | 13.27 | 10.80 | 0.106945E+09 | 105.46 | 20-JUN-21:10 | 16.65 | 12.83 |
July | 0.222161E+10 | 4959.89 | 04-JUL-16:32 | 24.63 | 19.94 | 0.112080E+09 | 114.18 | 06-JUL-21:10 | 16.38 | 13.60 |
August | 0.174143E+10 | 4879.70 | 02-AUG-20:02 | 13.62 | 11.96 | 0.110901E+09 | 103.79 | 04-AUG-21:10 | 14.45 | 11.90 |
September | 0.861379E+09 | 4819.93 | 04-SEP-18:01 | 14.03 | 8.92 | 99602431.38 | 94.97 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 0.302921E+09 | 4445.48 | 20-OCT-18:11 | 12.23 | 7.41 | 95764170.69 | 67.34 | 19-OCT-18:10 | 12.23 | 7.41 |
November | 38905871.69 | 3977.88 | 17-NOV-16:01 | 9.45 | 2.90 | 90031992.96 | 56.69 | 01-NOV-03:39 | 9.45 | 2.90 |
December | 6833244.10 | 563.64 | 24-DEC-08:62 | -31.1 | -31.3 | 92036012.13 | 56.69 | 23-DEC-02:20 | -31.1 | -31.3 |
Annual Sum or Average | 0.925314E+10 | 0.117849E+10 | ||||||||
Minimum of Months | 6833244.10 | 563.64 | -31.1 | -31.3 | 84090232.61 | 56.69 | -31.1 | -31.3 | ||
Maximum of Months | 0.222161E+10 | 5299.53 | 24.63 | 19.94 | 0.112080E+09 | 114.18 | 16.65 | 13.60 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3457390.50 | 584.16 | 26-JAN-08:61 | -32.1 | -32.2 | 90875382.27 | 56.69 | 24-JAN-04:19 | -32.1 | -32.2 |
February | 14987491.14 | 1035.23 | 28-FEB-16:02 | 6.02 | 1.46 | 83426161.58 | 56.69 | 12-FEB-02:20 | 6.02 | 1.46 |
March | 84558167.33 | 3943.55 | 27-MAR-18:01 | 5.92 | 2.01 | 93163324.16 | 56.69 | 07-MAR-05:30 | 5.92 | 2.01 |
April | 0.367820E+09 | 4640.82 | 11-APR-18:11 | 13.90 | 5.53 | 93229445.74 | 75.20 | 17-APR-18:30 | 14.70 | 7.31 |
May | 0.124063E+10 | 5045.85 | 06-MAY-18:32 | 14.97 | 7.01 | 0.105815E+09 | 96.54 | 04-MAY-18:40 | 14.97 | 7.01 |
June | 0.160816E+10 | 4368.20 | 07-JUN-21:41 | 13.27 | 10.80 | 0.106669E+09 | 104.73 | 20-JUN-21:10 | 16.65 | 12.83 |
July | 0.200823E+10 | 4691.23 | 04-JUL-16:32 | 24.63 | 19.94 | 0.111683E+09 | 115.04 | 06-JUL-20:10 | 18.43 | 14.14 |
August | 0.144390E+10 | 4640.83 | 02-AUG-20:02 | 13.62 | 11.96 | 0.109717E+09 | 100.56 | 04-AUG-21:10 | 14.45 | 11.90 |
September | 0.568676E+09 | 4527.80 | 08-SEP-19:41 | 13.68 | 8.00 | 98006487.72 | 87.46 | 05-SEP-18:10 | 13.68 | 8.00 |
October | 0.135193E+09 | 3856.84 | 01-OCT-15:01 | 15.10 | 9.13 | 94499029.11 | 56.69 | 22-OCT-01:00 | 7.20 | 5.62 |
November | 18312605.33 | 876.74 | 09-NOV-16:03 | 0.82 | -3.8 | 89508471.07 | 56.69 | 01-NOV-04:40 | 0.82 | -3.8 |
December | 4160548.40 | 558.78 | 24-DEC-08:62 | -31.1 | -31.3 | 91644825.62 | 56.69 | 29-DEC-04:19 | -15.8 | -16.1 |
Annual Sum or Average | 0.749809E+10 | 0.116824E+10 | ||||||||
Minimum of Months | 3457390.50 | 558.78 | -32.1 | -32.2 | 83426161.58 | 56.69 | -32.1 | -32.2 | ||
Maximum of Months | 0.200823E+10 | 5045.85 | 24.63 | 19.94 | 0.111683E+09 | 115.04 | 18.43 | 14.14 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93741697.05 | 2272.94 | 27-JAN-16:01 | -14.8 | -15.9 | 93524541.91 | 56.69 | 14-JAN-05:10 | -14.8 | -15.9 |
February | 0.202781E+09 | 2307.74 | 04-FEB-16:01 | 7.70 | 2.52 | 85996570.04 | 56.69 | 03-FEB-04:19 | 7.70 | 2.52 |
March | 0.279800E+09 | 2354.82 | 31-MAR-15:01 | 8.40 | 2.82 | 95705341.76 | 56.69 | 29-MAR-21:10 | 8.40 | 2.82 |
April | 0.497922E+09 | 2560.68 | 13-APR-19:41 | 14.60 | 6.84 | 94635829.47 | 64.14 | 13-APR-19:30 | 14.60 | 6.84 |
May | 0.873901E+09 | 2530.24 | 05-MAY-19:51 | 13.70 | 6.75 | 0.102891E+09 | 80.04 | 15-MAY-21:40 | 14.97 | 10.17 |
June | 0.996234E+09 | 2419.20 | 20-JUN-21:51 | 13.90 | 11.62 | 0.101756E+09 | 83.61 | 15-JUN-21:10 | 13.90 | 11.62 |
July | 0.124943E+10 | 2433.10 | 26-JUL-21:11 | 12.77 | 11.83 | 0.106574E+09 | 85.14 | 26-JUL-21:10 | 12.77 | 11.83 |
August | 0.114697E+10 | 2553.02 | 05-AUG-20:41 | 15.50 | 12.15 | 0.106961E+09 | 88.23 | 04-AUG-21:10 | 15.50 | 12.15 |
September | 0.791066E+09 | 2556.86 | 04-SEP-18:01 | 14.03 | 8.92 | 98220984.17 | 83.84 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.456944E+09 | 2615.03 | 20-OCT-18:11 | 12.23 | 7.41 | 96845141.13 | 70.03 | 19-OCT-18:10 | 12.23 | 7.41 |
November | 0.151783E+09 | 2280.42 | 17-NOV-16:01 | 9.45 | 2.90 | 91558822.40 | 56.69 | 01-NOV-01:00 | 9.45 | 2.90 |
December | 55502633.49 | 2171.00 | 02-DEC-16:02 | -18.7 | -19.4 | 93266935.35 | 56.69 | 15-DEC-04:19 | -14.2 | -15.1 |
Annual Sum or Average | 0.679607E+10 | 0.116794E+10 | ||||||||
Minimum of Months | 55502633.49 | 2171.00 | -18.7 | -19.4 | 85996570.04 | 56.69 | -14.8 | -15.9 | ||
Maximum of Months | 0.124943E+10 | 2615.03 | 15.50 | 12.15 | 0.106961E+09 | 88.23 | 15.50 | 12.15 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268974E+11 | 26120.72 | 25-JAN-20:01 | -24.0 | -24.2 | 0.163110E+11 | 11347.86 | 17-JAN-00:20 | -24.0 | -24.2 |
February | 0.250040E+11 | 25344.53 | 24-FEB-22:52 | -23.9 | -24.3 | 0.160142E+11 | 11347.88 | 06-FEB-00:20 | -23.9 | -24.3 |
March | 0.295344E+11 | 31527.46 | 31-MAR-21:40 | 4.67 | 0.78 | 0.186459E+11 | 12733.97 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.323806E+11 | 32020.08 | 14-APR-02:42 | 6.28 | 4.16 | 0.185398E+11 | 12889.19 | 12-APR-23:10 | 6.28 | 4.16 |
May | 0.392092E+11 | 32804.56 | 15-MAY-05:43 | 7.13 | 4.32 | 0.193352E+11 | 12970.75 | 09-MAY-22:49 | 7.13 | 4.32 |
June | 0.404242E+11 | 32106.76 | 02-JUN-22:20 | 5.00 | 4.07 | 0.187598E+11 | 12938.05 | 08-JUN-02:49 | 7.52 | 7.22 |
July | 0.428010E+11 | 31693.32 | 02-JUL-01:24 | 7.75 | 7.63 | 0.193057E+11 | 12198.73 | 10-JUL-03:20 | 7.80 | 7.49 |
August | 0.411164E+11 | 31009.68 | 19-AUG-01:47 | 6.28 | 6.10 | 0.193721E+11 | 12390.42 | 18-AUG-23:19 | 6.28 | 6.10 |
September | 0.362477E+11 | 38100.27 | 14-SEP-01:18 | 6.33 | 5.46 | 0.186721E+11 | 13493.17 | 28-SEP-03:30 | 6.65 | 5.00 |
October | 0.333429E+11 | 37186.86 | 20-OCT-04:03 | 6.88 | 6.88 | 0.191611E+11 | 12999.10 | 25-OCT-22:19 | 6.50 | 4.89 |
November | 0.288386E+11 | 30801.65 | 19-NOV-23:20 | 5.60 | 2.47 | 0.181773E+11 | 12078.40 | 01-NOV-23:00 | 5.60 | 2.47 |
December | 0.268608E+11 | 24603.14 | 23-DEC-21:42 | -23.9 | -24.3 | 0.169973E+11 | 11347.86 | 05-DEC-04:19 | -23.9 | -24.3 |
Annual Sum or Average | 0.402657E+12 | 0.219292E+12 | ||||||||
Minimum of Months | 0.250040E+11 | 24603.14 | -24.0 | -24.3 | 0.160142E+11 | 11347.86 | -24.0 | -24.3 | ||
Maximum of Months | 0.428010E+11 | 38100.27 | 7.75 | 7.63 | 0.193721E+11 | 13493.17 | 7.80 | 7.49 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298525E+11 | 27772.79 | 25-JAN-20:01 | -24.0 | -24.2 | 0.166197E+11 | 11347.93 | 30-JAN-00:20 | -4.0 | -4.5 |
February | 0.278540E+11 | 26874.12 | 24-FEB-22:52 | -23.9 | -24.3 | 0.163056E+11 | 11347.93 | 06-FEB-00:20 | -23.9 | -24.3 |
March | 0.330925E+11 | 33388.98 | 31-MAR-21:40 | 4.67 | 0.78 | 0.188796E+11 | 12847.43 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.361024E+11 | 34071.69 | 24-APR-02:50 | 7.07 | 5.33 | 0.186544E+11 | 13012.30 | 12-APR-23:10 | 7.07 | 5.33 |
May | 0.427575E+11 | 36335.30 | 15-MAY-05:43 | 7.13 | 4.32 | 0.193657E+11 | 13379.11 | 09-MAY-22:49 | 7.13 | 4.32 |
June | 0.436908E+11 | 38963.24 | 17-JUN-00:40 | 6.50 | 6.07 | 0.187720E+11 | 13005.27 | 08-JUN-02:49 | 6.50 | 6.07 |
July | 0.459114E+11 | 33354.69 | 02-JUL-01:24 | 7.75 | 7.63 | 0.193125E+11 | 12237.54 | 10-JUL-03:20 | 7.80 | 7.49 |
August | 0.443659E+11 | 33277.29 | 19-AUG-00:17 | 7.60 | 7.60 | 0.193900E+11 | 12497.45 | 18-AUG-23:19 | 7.60 | 7.60 |
September | 0.397436E+11 | 39986.71 | 14-SEP-01:18 | 6.33 | 5.46 | 0.187209E+11 | 13594.95 | 28-SEP-03:30 | 6.65 | 5.00 |
October | 0.372260E+11 | 40395.29 | 20-OCT-04:03 | 6.88 | 6.88 | 0.192737E+11 | 13125.18 | 25-OCT-22:19 | 6.50 | 4.89 |
November | 0.323893E+11 | 32681.41 | 19-NOV-23:20 | 5.60 | 2.47 | 0.183986E+11 | 12132.21 | 20-NOV-23:49 | 7.80 | 7.24 |
December | 0.299395E+11 | 26279.33 | 23-DEC-21:42 | -23.9 | -24.3 | 0.173031E+11 | 11347.94 | 04-DEC-00:20 | -23.9 | -24.3 |
Annual Sum or Average | 0.442925E+12 | 0.220996E+12 | ||||||||
Minimum of Months | 0.278540E+11 | 26279.33 | -24.0 | -24.3 | 0.163056E+11 | 11347.93 | -23.9 | -24.3 | ||
Maximum of Months | 0.459114E+11 | 40395.29 | 7.75 | 7.63 | 0.193900E+11 | 13594.95 | 7.80 | 7.60 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443013E+11 | 28430.58 | 25-JAN-20:01 | -24.0 | -24.2 | 0.185673E+11 | 11319.71 | 07-JAN-18:19 | -24.0 | -24.2 |
February | 0.417271E+11 | 37321.88 | 21-FEB-15:05 | 5.92 | 2.85 | 0.168904E+11 | 11516.54 | 04-FEB-18:40 | 5.92 | 2.85 |
March | 0.484191E+11 | 35585.43 | 31-MAR-10:36 | 3.17 | 0.23 | 0.187886E+11 | 11349.59 | 28-MAR-16:30 | 3.17 | 0.23 |
April | 0.504117E+11 | 38809.11 | 10-APR-09:17 | 5.73 | 1.63 | 0.182349E+11 | 11398.04 | 25-APR-17:49 | 5.18 | 3.25 |
May | 0.559533E+11 | 37138.40 | 06-MAY-07:38 | 7.63 | 2.93 | 0.188642E+11 | 11340.36 | 08-MAY-17:30 | 7.70 | 5.62 |
June | 0.560869E+11 | 33946.02 | 02-JUN-06:35 | 9.63 | 6.41 | 0.182593E+11 | 11319.67 | 24-JUN-17:19 | 29.03 | 22.25 |
July | 0.586609E+11 | 32127.28 | 23-JUL-10:40 | 27.77 | 23.32 | 0.188617E+11 | 11319.68 | 22-JUL-17:19 | 27.77 | 23.32 |
August | 0.572633E+11 | 33910.28 | 19-AUG-06:36 | 8.13 | 7.65 | 0.188678E+11 | 11319.71 | 26-AUG-17:19 | 25.17 | 18.70 |
September | 0.528399E+11 | 40373.87 | 05-SEP-06:07 | 6.05 | 5.72 | 0.182530E+11 | 11324.22 | 27-SEP-17:40 | 8.30 | 5.82 |
October | 0.511072E+11 | 41873.63 | 27-OCT-17:27 | 5.60 | 4.79 | 0.188561E+11 | 11470.19 | 07-OCT-17:30 | 5.60 | 4.79 |
November | 0.463646E+11 | 36350.30 | 17-NOV-18:34 | 4.80 | 0.33 | 0.182053E+11 | 11363.29 | 14-NOV-16:49 | 4.80 | 0.33 |
December | 0.444298E+11 | 27318.12 | 23-DEC-21:42 | -23.9 | -24.3 | 0.186299E+11 | 11319.71 | 02-DEC-18:19 | -23.9 | -24.3 |
Annual Sum or Average | 0.607565E+12 | 0.221278E+12 | ||||||||
Minimum of Months | 0.417271E+11 | 27318.12 | -24.0 | -24.3 | 0.168904E+11 | 11319.67 | -24.0 | -24.3 | ||
Maximum of Months | 0.586609E+11 | 41873.63 | 27.77 | 23.32 | 0.188678E+11 | 11516.54 | 29.03 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93703597.00 | 1031.24 | 29-JAN-13:00 | -0.6 | -2.1 | 0.117598E+10 | 745.65 | 09-JAN-23:00 | -0.6 | -2.1 |
February | 0.103731E+10 | 6258.64 | 21-FEB-15:05 | 5.92 | 2.85 | 0.112719E+10 | 745.68 | 24-FEB-22:49 | -23.7 | -24.1 |
March | 0.265685E+10 | 5696.00 | 31-MAR-21:49 | 4.58 | 0.73 | 0.127770E+10 | 825.68 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.606838E+10 | 6290.00 | 15-APR-01:03 | 6.60 | 5.55 | 0.128615E+10 | 881.22 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.931045E+10 | 7004.95 | 06-MAY-23:08 | 6.67 | 2.76 | 0.148943E+10 | 1001.83 | 25-MAY-21:30 | 22.35 | 16.43 |
June | 0.100108E+11 | 6961.49 | 17-JUN-00:08 | 6.20 | 5.93 | 0.150991E+10 | 1007.40 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.109760E+11 | 7058.11 | 02-JUL-04:44 | 6.38 | 6.38 | 0.161039E+10 | 1007.40 | 21-JUL-22:10 | 21.60 | 20.03 |
August | 0.102343E+11 | 6644.67 | 18-AUG-23:22 | 7.25 | 7.10 | 0.156633E+10 | 992.84 | 08-AUG-21:40 | 7.25 | 7.10 |
September | 0.848507E+10 | 7125.34 | 15-SEP-01:55 | 6.10 | 5.58 | 0.139318E+10 | 969.97 | 01-SEP-21:30 | 6.10 | 5.58 |
October | 0.603354E+10 | 6761.02 | 20-OCT-04:03 | 6.88 | 6.88 | 0.131841E+10 | 885.05 | 22-OCT-23:30 | 6.40 | 5.11 |
November | 0.239850E+10 | 5856.99 | 16-NOV-14:26 | 6.95 | 1.79 | 0.122938E+10 | 790.71 | 02-NOV-00:10 | 6.95 | 1.79 |
December | 82826450.35 | 1255.29 | 05-DEC-22:10 | 0.00 | -0.0 | 0.121349E+10 | 745.75 | 14-DEC-05:19 | -23.5 | -23.8 |
Annual Sum or Average | 0.673877E+11 | 0.161975E+11 | ||||||||
Minimum of Months | 82826450.35 | 1031.24 | -0.6 | -2.1 | 0.112719E+10 | 745.65 | -23.7 | -24.1 | ||
Maximum of Months | 0.109760E+11 | 7125.34 | 7.25 | 7.10 | 0.161039E+10 | 1007.40 | 22.35 | 20.03 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3279583.55 | 2595.28 | 06-JAN-13:31 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 1189518.34 | 3195.41 | 31-MAR-21:35 | 4.67 |
April | 3667423.28 | 3463.08 | 08-APR-07:55 | 5.60 |
May | 3845737.69 | 3267.61 | 21-MAY-06:26 | 4.80 |
June | 2146601.80 | 3007.60 | 02-JUN-04:36 | 7.07 |
July | 38568.47 | 128.56 | 18-JUL-03:15 | 8.30 |
August | 257905.85 | 1782.61 | 18-AUG-23:30 | 7.25 |
September | 6535740.50 | 4217.64 | 14-SEP-23:33 | 6.30 |
October | 6986961.63 | 5040.78 | 01-OCT-01:06 | 5.82 |
November | 1186498.68 | 3333.64 | 19-NOV-23:07 | 5.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 29134539.80 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 6986961.63 | 5040.78 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193423E+10 | 3240.30 | 14-JAN-04:51 | -23.3 |
February | 0.104822E+10 | 2847.00 | 15-FEB-07:32 | -23.3 |
March | 0.618076E+09 | 3099.44 | 05-MAR-08:31 | -23.4 |
April | 72124647.52 | 921.76 | 08-APR-07:55 | 5.60 |
May | 2646528.22 | 1703.89 | 20-MAY-06:38 | 5.93 |
June | 1279846.48 | 1013.14 | 02-JUN-04:36 | 7.07 |
July | 278437.27 | 563.08 | 18-JUL-03:15 | 8.30 |
August | 594003.45 | 897.66 | 18-AUG-23:30 | 7.25 |
September | 6849626.76 | 1226.88 | 07-SEP-04:58 | 6.10 |
October | 50146347.26 | 2211.05 | 24-OCT-07:38 | 5.60 |
November | 0.580675E+09 | 1796.38 | 25-NOV-07:10 | -19.2 |
December | 0.208243E+10 | 3192.07 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.639754E+10 | |||
Minimum of Months | 278437.27 | 563.08 | -23.4 | |
Maximum of Months | 0.208243E+10 | 3240.30 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75293327.54 | 1069.50 | 09-JAN-10:41 | -23.4 |
February | 15952926.58 | 804.05 | 14-FEB-10:42 | -23.2 |
March | 1046476.61 | 753.06 | 05-MAR-08:31 | -23.4 |
April | 203400.00 | 354.43 | 08-APR-07:55 | 5.60 |
May | 153128.44 | 266.72 | 21-MAY-06:26 | 4.80 |
June | 91178.59 | 215.78 | 02-JUN-04:36 | 7.07 |
July | 425.71 | 1.42 | 18-JUL-03:15 | 8.30 |
August | 60925.98 | 156.10 | 18-AUG-23:30 | 7.25 |
September | 894412.90 | 380.34 | 23-SEP-07:25 | 5.30 |
October | 1319062.30 | 312.33 | 30-OCT-23:19 | 6.87 |
November | 324818.17 | 375.12 | 19-NOV-23:07 | 5.60 |
December | 57910420.82 | 933.20 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.153251E+09 | |||
Minimum of Months | 425.71 | 1.42 | -23.4 | |
Maximum of Months | 75293327.54 | 1069.50 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156499E+10 | 1668.81 | 06-JAN-13:31 | -23.3 |
February | 0.767922E+09 | 1382.91 | 14-FEB-10:42 | -23.2 |
March | 0.329388E+09 | 1308.34 | 05-MAR-08:31 | -23.4 |
April | 1847848.76 | 397.73 | 08-APR-07:55 | 5.60 |
May | 371211.35 | 257.95 | 21-MAY-06:26 | 4.80 |
June | 179163.19 | 231.48 | 02-JUN-04:36 | 7.07 |
July | 17481.93 | 58.27 | 18-JUL-03:15 | 8.30 |
August | 93385.35 | 184.05 | 18-AUG-23:30 | 7.25 |
September | 1240759.71 | 361.94 | 23-SEP-07:25 | 5.30 |
October | 2426592.53 | 365.12 | 30-OCT-23:19 | 6.87 |
November | 0.127390E+09 | 544.99 | 25-NOV-17:00 | -15.6 |
December | 0.132129E+10 | 1499.63 | 25-DEC-10:12 | -23.0 |
Annual Sum or Average | 0.411716E+10 | |||
Minimum of Months | 17481.93 | 58.27 | -23.4 | |
Maximum of Months | 0.156499E+10 | 1668.81 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152398E+10 | 1207.07 | 06-JAN-13:31 | -23.3 |
February | 0.926087E+09 | 1020.14 | 14-FEB-10:42 | -23.2 |
March | 0.517578E+09 | 972.75 | 05-MAR-08:31 | -23.4 |
April | 28710022.26 | 270.51 | 08-APR-07:55 | 5.60 |
May | 324592.56 | 205.42 | 21-MAY-06:26 | 4.80 |
June | 168890.62 | 182.31 | 02-JUN-04:36 | 7.07 |
July | 20740.40 | 69.13 | 18-JUL-03:15 | 8.30 |
August | 82882.81 | 158.71 | 18-AUG-23:30 | 7.25 |
September | 1092451.40 | 277.51 | 23-SEP-07:25 | 5.30 |
October | 7795555.42 | 255.45 | 30-OCT-23:19 | 6.87 |
November | 0.279041E+09 | 609.50 | 25-NOV-17:00 | -15.6 |
December | 0.138530E+10 | 1102.47 | 25-DEC-10:12 | -23.0 |
Annual Sum or Average | 0.467018E+10 | |||
Minimum of Months | 20740.40 | 69.13 | -23.4 | |
Maximum of Months | 0.152398E+10 | 1207.07 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1917620.72 | 6996.45 | 14-JAN-04:51 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 65397.10 | 716.94 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 772843.21 | 3896.24 | 08-JUN-01:50 | 6.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 1234986.19 | 3400.40 | 07-SEP-04:58 | 6.10 |
October | 2062931.71 | 2809.62 | 20-OCT-02:56 | 6.10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 381319.08 | 4023.20 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 6435098.02 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 2062931.71 | 6996.45 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204636E+09 | 6508.48 | 09-JAN-10:41 | -23.4 |
February | 70684345.73 | 6908.72 | 17-FEB-09:41 | -23.4 |
March | 19046231.80 | 7396.99 | 05-MAR-08:31 | -23.4 |
April | 1759492.62 | 2644.42 | 08-APR-07:55 | 5.60 |
May | 556289.06 | 2601.23 | 21-MAY-06:26 | 4.80 |
June | 424651.86 | 1380.92 | 02-JUN-04:36 | 7.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 271068.77 | 1123.24 | 18-AUG-23:30 | 7.25 |
September | 6801371.62 | 3048.34 | 14-SEP-06:15 | 4.63 |
October | 9120873.09 | 2736.02 | 24-OCT-07:54 | 5.60 |
November | 8632721.91 | 2834.48 | 19-NOV-23:07 | 5.60 |
December | 0.314426E+09 | 8622.19 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.636358E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.314426E+09 | 8622.19 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301838E+09 | 18289.45 | 09-JAN-10:41 | -23.4 |
February | 73759196.96 | 13343.26 | 17-FEB-09:52 | -22.8 |
March | 7739264.11 | 12849.43 | 05-MAR-08:31 | -23.4 |
April | 3549089.82 | 5943.30 | 08-APR-07:55 | 5.60 |
May | 1112597.57 | 4453.09 | 21-MAY-06:26 | 4.80 |
June | 1111360.46 | 4773.97 | 02-JUN-04:36 | 7.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 396948.61 | 2536.44 | 18-AUG-23:30 | 7.25 |
September | 14386072.98 | 11011.92 | 07-SEP-04:58 | 6.10 |
October | 18613054.70 | 6594.60 | 23-OCT-00:49 | 6.10 |
November | 4727073.39 | 6154.28 | 15-NOV-11:55 | 5.00 |
December | 0.360518E+09 | 17293.66 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.787751E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.360518E+09 | 18289.45 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286556E+10 | 2342.86 | 07-JAN-09:13 | -20.2 |
February | 0.178036E+10 | 2317.49 | 15-FEB-09:02 | -21.0 |
March | 0.126334E+10 | 2287.99 | 15-MAR-08:62 | -22.3 |
April | 0.403361E+09 | 2265.93 | 04-APR-08:61 | -7.6 |
May | 23938714.59 | 2129.73 | 01-MAY-08:62 | 1.73 |
June | 3964916.30 | 1036.23 | 03-JUN-18:03 | 14.32 |
July | 465970.85 | 754.09 | 09-JUL-08:04 | 13.40 |
August | 3709923.22 | 1270.47 | 04-AUG-08:53 | 18.30 |
September | 36797199.75 | 2218.80 | 21-SEP-08:61 | 6.88 |
October | 0.459713E+09 | 2271.43 | 30-OCT-08:61 | -6.1 |
November | 0.131664E+10 | 2317.13 | 15-NOV-19:01 | 4.32 |
December | 0.281242E+10 | 2351.01 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.109703E+11 | |||
Minimum of Months | 465970.85 | 754.09 | -22.3 | |
Maximum of Months | 0.286556E+10 | 2351.01 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331764E+10 | 2350.88 | 06-JAN-16:13 | -22.6 |
February | 0.217807E+10 | 2313.12 | 10-FEB-09:01 | -20.3 |
March | 0.155967E+10 | 2297.69 | 15-MAR-08:62 | -22.3 |
April | 0.501719E+09 | 2256.52 | 04-APR-08:61 | -7.6 |
May | 29492726.09 | 2128.37 | 01-MAY-08:62 | 1.73 |
June | 3681366.82 | 1234.95 | 05-JUN-08:53 | 17.80 |
July | 518861.40 | 763.84 | 09-JUL-08:04 | 13.40 |
August | 4142357.08 | 1115.09 | 04-AUG-08:53 | 18.30 |
September | 45168801.14 | 2199.21 | 21-SEP-08:61 | 6.88 |
October | 0.557522E+09 | 2264.28 | 30-OCT-08:61 | -6.1 |
November | 0.153307E+10 | 2314.67 | 15-NOV-19:01 | 4.32 |
December | 0.316482E+10 | 2343.86 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.128955E+11 | |||
Minimum of Months | 518861.40 | 763.84 | -22.6 | |
Maximum of Months | 0.331764E+10 | 2350.88 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364679E+09 | 440.88 | 13-JAN-02:30 | -28.3 |
February | 0.151829E+09 | 426.01 | 17-FEB-05:00 | -30.0 |
March | 71484397.40 | 387.15 | 05-MAR-06:00 | -27.2 |
April | 412737.50 | 43.71 | 04-APR-05:00 | -8.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 1555087.53 | 71.01 | 30-OCT-05:00 | -10.0 |
November | 0.105423E+09 | 358.24 | 25-NOV-06:00 | -19.4 |
December | 0.403433E+09 | 452.02 | 19-DEC-05:00 | -25.4 |
Annual Sum or Average | 0.109882E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.0 | |
Maximum of Months | 0.403433E+09 | 452.02 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.705608E+09 | 678.57 | 06-JAN-16:02 | -22.4 |
February | 0.452666E+09 | 666.22 | 01-FEB-16:01 | -20.2 |
March | 0.292427E+09 | 659.73 | 15-MAR-15:01 | -11.0 |
April | 40180290.02 | 634.32 | 05-APR-15:01 | -0.5 |
May | 627438.58 | 332.95 | 03-MAY-08:03 | 12.18 |
June | 293957.30 | 388.46 | 13-JUN-08:05 | 15.18 |
July | 76586.94 | 203.14 | 10-JUL-08:54 | 20.60 |
August | 422271.04 | 346.15 | 14-AUG-08:05 | 15.60 |
September | 1055901.92 | 491.55 | 23-SEP-15:03 | 16.10 |
October | 20827973.93 | 633.58 | 30-OCT-15:01 | 5.00 |
November | 0.216837E+09 | 658.07 | 25-NOV-16:02 | -14.2 |
December | 0.641880E+09 | 672.18 | 20-DEC-16:02 | -20.4 |
Annual Sum or Average | 0.237290E+10 | |||
Minimum of Months | 76586.94 | 203.14 | -22.4 | |
Maximum of Months | 0.705608E+09 | 678.57 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285124E+10 | 2286.27 | 06-JAN-16:13 | -22.6 |
February | 0.176860E+10 | 2266.68 | 15-FEB-09:02 | -21.0 |
March | 0.124803E+10 | 2241.18 | 07-MAR-16:01 | -8.3 |
April | 0.387951E+09 | 2213.29 | 26-APR-15:01 | -0.6 |
May | 27227933.30 | 978.10 | 31-MAY-08:02 | 8.13 |
June | 1882580.46 | 755.45 | 11-JUN-18:04 | 14.90 |
July | 345727.24 | 688.59 | 05-JUL-21:54 | 17.20 |
August | 3007406.55 | 730.74 | 03-AUG-21:54 | 15.60 |
September | 41741292.48 | 2160.96 | 21-SEP-08:61 | 6.88 |
October | 0.478554E+09 | 2220.50 | 29-OCT-18:01 | -3.0 |
November | 0.132064E+10 | 2262.12 | 15-NOV-19:01 | 4.32 |
December | 0.279503E+10 | 2296.82 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.109242E+11 | |||
Minimum of Months | 345727.24 | 688.59 | -22.6 | |
Maximum of Months | 0.285124E+10 | 2296.82 | 17.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330698E+10 | 2321.46 | 06-JAN-16:13 | -22.6 |
February | 0.217692E+10 | 2282.27 | 01-FEB-16:01 | -20.2 |
March | 0.154761E+10 | 2236.76 | 07-MAR-16:01 | -8.3 |
April | 0.474723E+09 | 2191.75 | 03-APR-08:61 | -1.5 |
May | 34767919.76 | 1225.91 | 02-MAY-19:43 | 13.25 |
June | 1797960.37 | 667.45 | 14-JUN-21:54 | 14.40 |
July | 319629.78 | 660.84 | 09-JUL-15:04 | 18.48 |
August | 3361206.15 | 678.01 | 03-AUG-21:54 | 15.60 |
September | 53491079.84 | 2137.31 | 21-SEP-08:61 | 6.88 |
October | 0.585945E+09 | 2196.95 | 29-OCT-18:01 | -3.0 |
November | 0.153105E+10 | 2254.82 | 15-NOV-19:01 | 4.32 |
December | 0.314785E+10 | 2307.53 | 24-DEC-16:02 | -22.9 |
Annual Sum or Average | 0.128648E+11 | |||
Minimum of Months | 319629.78 | 660.84 | -22.9 | |
Maximum of Months | 0.330698E+10 | 2321.46 | 18.48 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136458E+10 | 2396.11 | 06-JAN-13:31 | -23.3 |
February | 0.456584E+09 | 2073.47 | 17-FEB-09:52 | -22.8 |
March | 0.147381E+09 | 2050.54 | 05-MAR-08:31 | -23.4 |
April | 1316061.92 | 949.51 | 08-APR-07:55 | 5.60 |
May | 904749.31 | 619.30 | 21-MAY-06:26 | 4.80 |
June | 437360.24 | 575.16 | 02-JUN-04:36 | 7.07 |
July | 42104.12 | 140.35 | 18-JUL-03:15 | 8.30 |
August | 283887.76 | 551.84 | 18-AUG-23:30 | 7.25 |
September | 3822756.68 | 1020.22 | 23-SEP-07:25 | 5.30 |
October | 8272264.27 | 1807.39 | 15-OCT-14:45 | 6.70 |
November | 0.167338E+09 | 1001.88 | 19-NOV-23:07 | 5.60 |
December | 0.128610E+10 | 2238.65 | 25-DEC-10:12 | -23.0 |
Annual Sum or Average | 0.343707E+10 | |||
Minimum of Months | 42104.12 | 140.35 | -23.4 | |
Maximum of Months | 0.136458E+10 | 2396.11 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367786E+10 | 2716.08 | 12-JAN-19:13 | -22.4 |
February | 0.237516E+10 | 2684.50 | 15-FEB-09:02 | -21.0 |
March | 0.173965E+10 | 2651.36 | 15-MAR-08:62 | -22.3 |
April | 0.624652E+09 | 2606.67 | 04-APR-08:61 | -7.6 |
May | 56399942.64 | 2516.08 | 09-MAY-08:61 | 6.62 |
June | 9347795.97 | 1257.58 | 05-JUN-08:53 | 17.80 |
July | 443296.96 | 1055.48 | 31-JUL-08:53 | 18.90 |
August | 9721536.95 | 1209.72 | 22-AUG-08:53 | 20.00 |
September | 89460476.11 | 2581.57 | 21-SEP-08:61 | 6.88 |
October | 0.723660E+09 | 2617.31 | 30-OCT-08:61 | -6.1 |
November | 0.181576E+10 | 2661.82 | 15-NOV-19:01 | 4.32 |
December | 0.362582E+10 | 2726.11 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.147479E+11 | |||
Minimum of Months | 443296.96 | 1055.48 | -22.4 | |
Maximum of Months | 0.367786E+10 | 2726.11 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418449E+10 | 2711.89 | 06-JAN-16:13 | -22.6 |
February | 0.284264E+10 | 2668.75 | 02-FEB-16:13 | -15.2 |
March | 0.210071E+10 | 2653.87 | 15-MAR-08:62 | -22.3 |
April | 0.758201E+09 | 2587.06 | 04-APR-08:61 | -7.6 |
May | 66234262.89 | 2489.76 | 09-MAY-08:61 | 6.62 |
June | 8935113.88 | 1099.71 | 05-JUN-08:53 | 17.80 |
July | 474594.66 | 975.69 | 31-JUL-08:53 | 18.90 |
August | 10683564.13 | 1129.94 | 20-AUG-08:53 | 20.60 |
September | 0.115702E+09 | 2553.04 | 21-SEP-08:61 | 6.88 |
October | 0.870784E+09 | 2605.34 | 30-OCT-08:61 | -6.1 |
November | 0.208248E+10 | 2634.13 | 25-NOV-19:02 | -15.0 |
December | 0.401687E+10 | 2710.00 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.170582E+11 | |||
Minimum of Months | 474594.66 | 975.69 | -22.6 | |
Maximum of Months | 0.418449E+10 | 2711.89 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133846E+10 | 1425.66 | 12-JAN-19:13 | -22.4 |
February | 0.787816E+09 | 1403.53 | 15-FEB-09:02 | -21.0 |
March | 0.565466E+09 | 1391.56 | 16-MAR-08:62 | -19.0 |
April | 0.180288E+09 | 1387.13 | 26-APR-15:01 | -0.6 |
May | 13522700.85 | 816.43 | 01-MAY-08:62 | 1.73 |
June | 2715684.00 | 565.73 | 03-JUN-18:03 | 14.32 |
July | 326828.29 | 488.26 | 15-JUL-08:54 | 23.90 |
August | 1784744.53 | 526.61 | 19-AUG-08:03 | 12.77 |
September | 11723136.98 | 1350.00 | 21-SEP-08:61 | 6.88 |
October | 0.191009E+09 | 1385.95 | 29-OCT-15:01 | 0.50 |
November | 0.599183E+09 | 1400.38 | 25-NOV-19:02 | -15.0 |
December | 0.137764E+10 | 1432.00 | 11-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.506994E+10 | |||
Minimum of Months | 326828.29 | 488.26 | -22.4 | |
Maximum of Months | 0.137764E+10 | 1432.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17338287.11 | 6690.38 | 09-JAN-10:41 | -23.4 |
February | 1979463.37 | 3514.41 | 14-FEB-10:42 | -23.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 34991.42 | 524.87 | 18-APR-22:46 | 4.63 |
May | 140697.75 | 1008.07 | 21-MAY-06:26 | 4.80 |
June | 150195.05 | 1461.48 | 02-JUN-04:36 | 7.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 7011.50 | 70.11 | 18-AUG-23:30 | 7.25 |
September | 1511951.40 | 1959.30 | 14-SEP-23:33 | 6.30 |
October | 1283983.48 | 2856.38 | 01-OCT-01:06 | 5.82 |
November | 244465.02 | 881.57 | 19-NOV-23:07 | 5.60 |
December | 7323275.95 | 5159.98 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 30014322.06 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 17338287.11 | 6690.38 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10826241.30 | 6478.78 | 09-JAN-10:41 | -23.4 |
February | 1264627.17 | 3187.64 | 14-FEB-10:42 | -23.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 31676.76 | 475.15 | 18-APR-22:46 | 4.63 |
May | 134590.66 | 994.65 | 21-MAY-06:26 | 4.80 |
June | 144797.35 | 1434.31 | 02-JUN-04:36 | 7.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 1321087.24 | 1946.75 | 07-SEP-04:58 | 6.10 |
October | 1028709.44 | 2788.06 | 01-OCT-01:06 | 5.82 |
November | 65208.53 | 851.58 | 19-NOV-23:07 | 5.60 |
December | 4467628.38 | 4911.55 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 19284566.83 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 10826241.30 | 6478.78 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 307786.90 | 3217.63 | 14-JAN-04:51 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 98017.66 | 1000.74 | 08-JUN-01:50 | 6.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 436273.49 | 2704.89 | 07-SEP-04:58 | 6.10 |
October | 414911.34 | 1263.26 | 01-OCT-01:06 | 5.82 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 1256989.39 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 436273.49 | 3217.63 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477250E+10 | 6422.44 | 07-JAN-04:22 | -23.4 |
February | 0.223763E+10 | 5689.67 | 17-FEB-09:52 | -22.8 |
March | 0.867620E+09 | 5692.87 | 05-MAR-08:31 | -23.4 |
April | 19011662.13 | 1781.61 | 08-APR-07:55 | 5.60 |
May | 2008821.55 | 1490.36 | 21-MAY-06:26 | 4.80 |
June | 1096287.53 | 1290.46 | 02-JUN-04:36 | 7.07 |
July | 143339.01 | 477.80 | 18-JUL-03:15 | 8.30 |
August | 622633.36 | 1187.37 | 18-AUG-23:30 | 7.25 |
September | 8472558.31 | 2007.77 | 23-SEP-07:25 | 5.30 |
October | 28010694.68 | 1796.96 | 01-OCT-01:06 | 5.82 |
November | 0.578842E+09 | 2672.02 | 25-NOV-07:20 | -19.0 |
December | 0.433364E+10 | 6214.87 | 25-DEC-10:12 | -23.0 |
Annual Sum or Average | 0.128496E+11 | |||
Minimum of Months | 143339.01 | 477.80 | -23.4 | |
Maximum of Months | 0.477250E+10 | 6422.44 | 8.30 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160421E+11 | 15451.75 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.144845E+11 | 15451.75 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.160915E+11 | 15451.75 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.154982E+11 | 15451.75 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.160699E+11 | 15451.75 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.155692E+11 | 15451.75 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.159988E+11 | 15451.75 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.160977E+11 | 15451.75 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.155043E+11 | 15451.75 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.160359E+11 | 15451.75 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.155569E+11 | 15451.75 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.159988E+11 | 15451.75 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.188948E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.144845E+11 | 15451.75 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.160977E+11 | 15451.75 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743719E+09 | 716.35 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.671510E+09 | 716.35 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.746011E+09 | 716.35 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.718503E+09 | 716.35 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.745008E+09 | 716.35 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.721798E+09 | 716.35 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.741713E+09 | 716.35 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.746298E+09 | 716.35 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.718790E+09 | 716.35 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.743432E+09 | 716.35 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.721225E+09 | 716.35 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.741713E+09 | 716.35 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.875972E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.671510E+09 | 716.35 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.746298E+09 | 716.35 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861229E+09 | 829.54 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.777612E+09 | 829.54 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.863884E+09 | 829.54 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.832029E+09 | 829.54 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.862722E+09 | 829.54 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.835845E+09 | 829.54 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.858907E+09 | 829.54 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.864216E+09 | 829.54 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.832361E+09 | 829.54 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.860897E+09 | 829.54 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.835182E+09 | 829.54 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.858907E+09 | 829.54 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.101438E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.777612E+09 | 829.54 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.864216E+09 | 829.54 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693793E+09 | 668.27 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.626432E+09 | 668.27 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.695932E+09 | 668.27 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.670270E+09 | 668.27 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.694996E+09 | 668.27 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.673344E+09 | 668.27 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.691922E+09 | 668.27 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.696199E+09 | 668.27 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.670538E+09 | 668.27 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.693526E+09 | 668.27 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.672810E+09 | 668.27 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.691922E+09 | 668.27 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.817168E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.626432E+09 | 668.27 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.696199E+09 | 668.27 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351983E+09 | 339.04 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.317809E+09 | 339.04 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.353068E+09 | 339.04 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.340049E+09 | 339.04 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.352593E+09 | 339.04 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.341609E+09 | 339.04 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.351034E+09 | 339.04 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.353204E+09 | 339.04 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.340185E+09 | 339.04 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.351847E+09 | 339.04 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.341337E+09 | 339.04 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.351034E+09 | 339.04 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.414575E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.317809E+09 | 339.04 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.353204E+09 | 339.04 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160274E+10 | 1957.67 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.136726E+10 | 1957.67 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.142015E+10 | 1957.67 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.121575E+10 | 1957.67 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.110343E+10 | 1957.67 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.995205E+09 | 1957.67 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.105691E+10 | 1957.67 | 07-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.122054E+10 | 1957.67 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.131082E+10 | 1957.67 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.149757E+10 | 1957.67 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.152534E+10 | 1957.67 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.161885E+10 | 1957.67 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.159346E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.995205E+09 | 1957.67 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.161885E+10 | 1957.67 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.855505E+10 | 8554.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.766201E+10 | 8554.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.845219E+10 | 8554.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.803592E+10 | 8554.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.821565E+10 | 8554.32 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.790848E+10 | 8554.32 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.814869E+10 | 8554.32 | 07-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.831204E+10 | 8554.32 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.810293E+10 | 8554.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.847852E+10 | 8554.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.827711E+10 | 8554.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.855088E+10 | 8554.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.986995E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.766201E+10 | 8554.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.855505E+10 | 8554.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146022E+09 | 132.12 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.131872E+09 | 132.12 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.144861E+09 | 132.12 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.141479E+09 | 132.12 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.145441E+09 | 132.12 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.140357E+09 | 132.12 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.146583E+09 | 132.12 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.144861E+09 | 132.12 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.141518E+09 | 132.12 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.146003E+09 | 132.12 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.140918E+09 | 132.12 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.146602E+09 | 132.12 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.171652E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.131872E+09 | 132.12 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.146602E+09 | 132.12 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.324527E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.284145E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.306224E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.278380E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.271004E+10 | 3437.84 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.254631E+10 | 3437.84 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.265725E+10 | 3437.84 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.284394E+10 | 3437.84 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.288690E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.313409E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.312121E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.325760E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.350901E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.254631E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.325760E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.324527E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.284145E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.306224E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.278380E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.271004E+10 | 3437.84 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.254631E+10 | 3437.84 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.265725E+10 | 3437.84 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.284394E+10 | 3437.84 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.288690E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.313409E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.312121E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.325760E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.350901E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.254631E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.325760E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126106E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121504E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125670E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148074E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.160421E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.160915E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.154982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.160699E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.155692E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.155043E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.160359E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.155569E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.188948E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.743719E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130071E+10 |
February | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101493E+10 |
March | 0.199990E+10 | 0.746011E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926620E+09 |
April | 0.192973E+10 | 0.718503E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 432394.40 | 0.555059E+09 |
May | 0.199475E+10 | 0.745008E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6237396.38 | 0.274821E+09 |
June | 0.193394E+10 | 0.721798E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17702678.55 | 0.140587E+09 |
July | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22100588.78 | 0.109152E+09 |
August | 0.199896E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7500561.74 | 0.142000E+09 |
September | 0.192879E+10 | 0.718790E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 286076.08 | 0.291246E+09 |
October | 0.199148E+10 | 0.743432E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518465E+09 |
November | 0.192552E+10 | 0.721225E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742800E+09 |
December | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122539E+10 |
Annual Sum or Average | 0.234744E+11 | 0.875972E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54259695.93 | 0.724179E+10 |
Minimum of Months | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109152E+09 |
Maximum of Months | 0.199990E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22100588.78 | 0.130071E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.861229E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507891E+09 |
February | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395160E+09 |
March | 0.231589E+10 | 0.863884E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363111E+09 |
April | 0.223463E+10 | 0.832029E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 186030.00 | 0.225158E+09 |
May | 0.230993E+10 | 0.862722E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2511611.53 | 0.121833E+09 |
June | 0.223950E+10 | 0.835845E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6502435.72 | 68518495.17 |
July | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8308655.44 | 55282014.84 |
August | 0.231480E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3171671.49 | 69608267.26 |
September | 0.223354E+10 | 0.832361E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166651.81 | 0.128416E+09 |
October | 0.230614E+10 | 0.860897E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213883E+09 |
November | 0.222975E+10 | 0.835182E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293204E+09 |
December | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478968E+09 |
Annual Sum or Average | 0.271834E+11 | 0.101438E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20847055.99 | 0.292103E+10 |
Minimum of Months | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55282014.84 |
Maximum of Months | 0.231589E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8308655.44 | 0.507891E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.693793E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119778E+10 |
February | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926784E+09 |
March | 0.489771E+09 | 0.695932E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839955E+09 |
April | 0.472586E+09 | 0.670270E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 664313.67 | 0.504294E+09 |
May | 0.488511E+09 | 0.694996E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6700838.86 | 0.273615E+09 |
June | 0.473617E+09 | 0.673344E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15197308.88 | 0.156662E+09 |
July | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19222178.88 | 0.129259E+09 |
August | 0.489542E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7907225.93 | 0.159994E+09 |
September | 0.472357E+09 | 0.670538E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 495926.51 | 0.290761E+09 |
October | 0.487709E+09 | 0.693526E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.94 | 0.480742E+09 |
November | 0.471555E+09 | 0.672810E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674813E+09 |
December | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113090E+10 |
Annual Sum or Average | 0.574883E+10 | 0.817168E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50188074.67 | 0.676556E+10 |
Minimum of Months | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129259E+09 |
Maximum of Months | 0.489771E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19222178.88 | 0.119778E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.351983E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686671E+09 |
February | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533584E+09 |
March | 0.376747E+09 | 0.353068E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483852E+09 |
April | 0.363528E+09 | 0.340049E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 411883.08 | 0.286916E+09 |
May | 0.375778E+09 | 0.352593E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4191268.94 | 0.151815E+09 |
June | 0.364321E+09 | 0.341609E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9313872.70 | 85505559.45 |
July | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11998079.46 | 70026705.59 |
August | 0.376571E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5076045.54 | 86511400.43 |
September | 0.363352E+09 | 0.340185E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 352303.00 | 0.160583E+09 |
October | 0.375161E+09 | 0.351847E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2256.19 | 0.271743E+09 |
November | 0.362735E+09 | 0.341337E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388410E+09 |
December | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649212E+09 |
Annual Sum or Average | 0.442217E+10 | 0.414575E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31345708.92 | 0.385483E+10 |
Minimum of Months | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70026705.59 |
Maximum of Months | 0.376747E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11998079.46 | 0.686671E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165760E+10 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131480E+10 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122336E+10 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 688031.07 | 0.757899E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 8478809.20 | 0.398785E+09 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 22697474.80 | 0.221536E+09 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 29474192.43 | 0.170395E+09 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 12001678.95 | 0.219144E+09 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 727199.11 | 0.421864E+09 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723794E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100311E+10 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157668E+10 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 74067385.56 | 0.968897E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170395E+09 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 29474192.43 | 0.165760E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.160274E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289875E+10 |
February | 0.236489E+11 | 0.136726E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226700E+10 |
March | 0.262800E+11 | 0.142015E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208260E+10 |
April | 0.253579E+11 | 0.121575E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 885015.78 | 0.127834E+10 |
May | 0.262123E+11 | 0.110343E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12817478.45 | 0.676942E+09 |
June | 0.254132E+11 | 0.995205E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36282327.99 | 0.373843E+09 |
July | 0.261570E+11 | 0.105691E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46025615.97 | 0.298722E+09 |
August | 0.262677E+11 | 0.122054E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15564633.66 | 0.380341E+09 |
September | 0.253456E+11 | 0.131082E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 612328.46 | 0.715384E+09 |
October | 0.261693E+11 | 0.149757E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120194E+10 |
November | 0.253025E+11 | 0.152534E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166801E+10 |
December | 0.261570E+11 | 0.161885E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272826E+10 |
Annual Sum or Average | 0.308468E+12 | 0.159346E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112187E+09 | 0.165701E+11 |
Minimum of Months | 0.236489E+11 | 0.995205E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298722E+09 |
Maximum of Months | 0.262800E+11 | 0.161885E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46025615.97 | 0.289875E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.855505E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836203E+10 |
February | 0.702046E+11 | 0.766201E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654071E+10 |
March | 0.780153E+11 | 0.845219E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603387E+10 |
April | 0.752779E+11 | 0.803592E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2792469.24 | 0.376105E+10 |
May | 0.778146E+11 | 0.821565E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38547993.93 | 0.203854E+10 |
June | 0.754422E+11 | 0.790848E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102745E+09 | 0.115680E+10 |
July | 0.776503E+11 | 0.814869E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130502E+09 | 0.921943E+09 |
August | 0.779788E+11 | 0.831204E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46436416.68 | 0.116820E+10 |
September | 0.752414E+11 | 0.810293E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1798578.18 | 0.216115E+10 |
October | 0.776868E+11 | 0.847852E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358192E+10 |
November | 0.751137E+11 | 0.827711E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488637E+10 |
December | 0.776503E+11 | 0.855088E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789400E+10 |
Annual Sum or Average | 0.915726E+12 | 0.986995E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322822E+09 | 0.485066E+11 |
Minimum of Months | 0.702046E+11 | 0.766201E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921943E+09 |
Maximum of Months | 0.780153E+11 | 0.855505E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130502E+09 | 0.836203E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766011E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587089E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531892E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401454.71 | 0.319763E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4944809.05 | 0.167209E+09 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12727842.12 | 92637657.22 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16504838.48 | 72615553.26 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6663259.58 | 90947828.46 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 393352.53 | 0.172138E+09 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2698.26 | 0.296385E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423694E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716553E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41638254.74 | 0.423694E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72615553.26 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16504838.48 | 0.766011E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764092E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583552E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527390E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 402746.65 | 0.315411E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973045.01 | 0.165484E+09 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12763086.90 | 92162956.06 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16568838.50 | 72097662.13 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6724584.40 | 89283554.09 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 404897.84 | 0.169071E+09 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3136.91 | 0.292750E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420736E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715727E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41840336.21 | 0.420776E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72097662.13 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16568838.50 | 0.764092E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.146022E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206085E+09 |
February | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159395E+09 |
March | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145862E+09 |
April | 0.00 | 0.141479E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72138.57 | 91172645.48 |
May | 0.00 | 0.145441E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1027069.10 | 50677204.85 |
June | 0.00 | 0.140357E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2786910.18 | 28345168.08 |
July | 0.00 | 0.146583E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549599.63 | 22113319.09 |
August | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1370690.96 | 28382873.59 |
September | 0.00 | 0.141518E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77360.62 | 53075114.17 |
October | 0.00 | 0.146003E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84031855.82 |
November | 0.00 | 0.140918E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113364E+09 |
December | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191749E+09 |
Annual Sum or Average | 0.00 | 0.171652E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8883769.06 | 0.117425E+10 |
Minimum of Months | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22113319.09 |
Maximum of Months | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549599.63 | 0.206085E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212546E+09 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163057E+09 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147757E+09 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 143066.13 | 87768420.56 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1585811.22 | 43937570.74 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3759966.24 | 23358464.95 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4937471.05 | 17518063.28 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2194155.74 | 22284809.24 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 184604.55 | 45518229.74 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13058.80 | 82197930.17 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118469E+09 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199419E+09 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12818133.72 | 0.116383E+10 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17518063.28 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4937471.05 | 0.212546E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765411E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586860E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533438E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 413005.37 | 0.320611E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4968109.69 | 0.164611E+09 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12678110.27 | 91133145.29 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16415904.88 | 71478711.68 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6690121.87 | 87999423.39 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 397716.20 | 0.169578E+09 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3038.68 | 0.296132E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423382E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716354E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41566006.97 | 0.422699E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71478711.68 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16415904.88 | 0.765411E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763516E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583225E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528440E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 419342.07 | 0.317549E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4979978.37 | 0.163540E+09 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12680552.86 | 90890779.41 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16438296.17 | 71048156.17 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6732538.09 | 86683013.32 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 402748.92 | 0.167381E+09 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4683.34 | 0.292545E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420668E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715448E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41658139.83 | 0.420093E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71048156.17 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16438296.17 | 0.763516E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927652E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713923E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647157E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448825.05 | 0.388960E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4968870.85 | 0.209282E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11398951.51 | 0.119425E+09 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14126654.74 | 99260625.87 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5926696.14 | 0.120612E+09 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333537.83 | 0.216907E+09 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363466E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518938E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872309E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37203536.12 | 0.519789E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99260625.87 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14126654.74 | 0.927652E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766685E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587034E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531889E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 392852.53 | 0.320109E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4841786.30 | 0.169112E+09 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12540649.90 | 94655116.15 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16226963.29 | 74310618.92 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6516779.52 | 92956942.70 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 377469.60 | 0.173314E+09 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2475.38 | 0.296326E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423595E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717503E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40898976.52 | 0.424749E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74310618.92 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16226963.29 | 0.766685E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764723E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584220E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527924E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 394564.79 | 0.315665E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4865817.56 | 0.167384E+09 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12563064.45 | 94171842.87 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16277630.31 | 73758700.03 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6574042.14 | 91122736.92 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 387330.30 | 0.169814E+09 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2909.32 | 0.292312E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421134E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716594E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41065358.87 | 0.421882E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73758700.03 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16277630.31 | 0.764723E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396181E+09 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304546E+09 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275726E+09 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 203915.99 | 0.165073E+09 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2498332.67 | 84196891.01 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6447467.27 | 45154449.63 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8337085.53 | 34488289.96 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3340633.92 | 45040177.84 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 194102.91 | 88078658.71 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 626.12 | 0.153610E+09 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219791E+09 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370009E+09 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21022164.41 | 0.218189E+10 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34488289.96 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8337085.53 | 0.396181E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.324527E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194098E+10 |
February | 0.415303E+11 | 0.284145E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152566E+10 |
March | 0.461508E+11 | 0.306224E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141789E+10 |
April | 0.445315E+11 | 0.278380E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 421155.04 | 0.889216E+09 |
May | 0.460320E+11 | 0.271004E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6701882.70 | 0.483693E+09 |
June | 0.446286E+11 | 0.254631E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19679586.13 | 0.280027E+09 |
July | 0.459349E+11 | 0.265725E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23983674.10 | 0.219625E+09 |
August | 0.461292E+11 | 0.284394E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8598866.30 | 0.279076E+09 |
September | 0.445099E+11 | 0.288690E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339749.97 | 0.508587E+09 |
October | 0.459565E+11 | 0.313409E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847490E+09 |
November | 0.444343E+11 | 0.312121E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116069E+10 |
December | 0.459349E+11 | 0.325760E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184111E+10 |
Annual Sum or Average | 0.541708E+12 | 0.350901E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 59724914.25 | 0.113940E+11 |
Minimum of Months | 0.415303E+11 | 0.254631E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219625E+09 |
Maximum of Months | 0.461508E+11 | 0.325760E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23983674.10 | 0.194098E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.324527E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195217E+10 |
February | 0.415303E+11 | 0.284145E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153639E+10 |
March | 0.461508E+11 | 0.306224E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142808E+10 |
April | 0.445315E+11 | 0.278380E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 419478.51 | 0.895038E+09 |
May | 0.460320E+11 | 0.271004E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6673600.55 | 0.485443E+09 |
June | 0.446286E+11 | 0.254631E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19663346.33 | 0.280741E+09 |
July | 0.459349E+11 | 0.265725E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23906607.99 | 0.219939E+09 |
August | 0.461292E+11 | 0.284394E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8560200.17 | 0.280155E+09 |
September | 0.445099E+11 | 0.288690E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339715.78 | 0.511214E+09 |
October | 0.459565E+11 | 0.313409E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852994E+09 |
November | 0.444343E+11 | 0.312121E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117029E+10 |
December | 0.459349E+11 | 0.325760E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185237E+10 |
Annual Sum or Average | 0.541708E+12 | 0.350901E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 59562949.32 | 0.114648E+11 |
Minimum of Months | 0.415303E+11 | 0.254631E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219939E+09 |
Maximum of Months | 0.461508E+11 | 0.325760E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23906607.99 | 0.195217E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175233E+10 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137866E+10 |
March | 0.410691E+10 | 0.126106E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128143E+10 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 377776.33 | 0.802079E+09 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5988728.78 | 0.434612E+09 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 17630380.81 | 0.250215E+09 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21433093.52 | 0.195732E+09 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7678143.04 | 0.249816E+09 |
September | 0.396089E+10 | 0.121504E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 306267.49 | 0.458540E+09 |
October | 0.408962E+10 | 0.125670E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768770E+09 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105207E+10 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166304E+10 |
Annual Sum or Average | 0.482060E+11 | 0.148074E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 53414389.98 | 0.102873E+11 |
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195732E+09 |
Maximum of Months | 0.410691E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21433093.52 | 0.175233E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163435E+10 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126371E+10 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114862E+10 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658212.66 | 0.689497E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6976489.89 | 0.370157E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18371825.42 | 0.209856E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22521000.10 | 0.170463E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8408458.33 | 0.209514E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358763.88 | 0.381466E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646422E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921183E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154082E+10 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57294750.29 | 0.918606E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170463E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22521000.10 | 0.163435E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 15451.75 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 15451.75 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 15451.75 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 15451.75 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 15451.75 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 15451.75 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 15451.75 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 15451.75 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 15451.75 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 15451.75 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 15451.75 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 15451.75 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 716.35 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 691.89 | 06-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 716.35 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 677.97 | 14-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 716.35 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 619.35 | 05-MAR-04:00 |
April | 1169.53 | 01-APR-00:10 | 716.35 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 23-APR-17:00 | 451.54 | 05-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 716.35 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.78 | 25-MAY-18:00 | 312.18 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 716.35 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 29-JUN-16:00 | 242.32 | 04-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 716.35 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.62 | 15-JUL-14:00 | 179.70 | 02-JUL-04:57 |
August | 1169.53 | 01-AUG-00:10 | 716.35 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 | 08-AUG-15:30 | 199.86 | 19-AUG-04:20 |
September | 1169.53 | 01-SEP-00:10 | 716.35 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 01-SEP-15:30 | 242.62 | 06-SEP-04:20 |
October | 1169.53 | 01-OCT-23:10 | 716.35 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 398.42 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 716.35 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 553.03 | 29-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 716.35 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 671.90 | 24-DEC-10:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.70 | |||||
Maximum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 691.89 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 829.54 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 277.86 | 06-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 829.54 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 279.13 | 14-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 829.54 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 254.39 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 829.54 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 23-APR-16:00 | 177.75 | 05-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 829.54 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 | 25-MAY-17:01 | 126.64 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 829.54 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 | 29-JUN-16:00 | 100.53 | 04-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 829.54 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 15-JUL-14:00 | 80.05 | 02-JUL-04:58 |
August | 1354.32 | 01-AUG-00:10 | 829.54 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 | 08-AUG-15:00 | 85.34 | 19-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 829.54 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 | 01-SEP-15:00 | 104.36 | 06-SEP-04:50 |
October | 1354.32 | 01-OCT-23:10 | 829.54 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 156.82 | 30-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 829.54 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 213.46 | 29-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 829.54 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 266.24 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.05 | |||||
Maximum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 | 279.13 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 668.27 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 674.63 | 06-JAN-09:00 |
February | 286.42 | 01-FEB-00:10 | 668.27 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 675.05 | 14-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 668.27 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 615.36 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 668.27 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 | 23-APR-16:00 | 411.92 | 05-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 668.27 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 25-MAY-17:01 | 286.35 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 668.27 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.50 | 29-JUN-16:00 | 234.52 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 668.27 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 | 15-JUL-14:00 | 188.51 | 02-JUL-04:58 |
August | 286.42 | 01-AUG-00:10 | 668.27 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.22 | 08-AUG-16:00 | 197.36 | 19-AUG-04:00 |
September | 286.42 | 01-SEP-00:10 | 668.27 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 01-SEP-16:00 | 239.10 | 06-SEP-04:40 |
October | 286.42 | 01-OCT-23:10 | 668.27 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 19-OCT-15:00 | 363.45 | 30-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 668.27 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 504.49 | 29-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 668.27 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 643.61 | 24-DEC-06:13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.51 | |||||
Maximum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 109.50 | 675.05 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 339.04 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 382.98 | 06-JAN-09:00 |
February | 220.32 | 01-FEB-00:10 | 339.04 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 384.45 | 14-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 339.04 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 350.77 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 339.04 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 23-APR-16:00 | 237.65 | 05-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 339.04 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.31 | 25-MAY-17:01 | 164.29 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 339.04 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 | 29-JUN-16:00 | 132.17 | 04-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 339.04 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 15-JUL-14:00 | 106.20 | 02-JUL-04:58 |
August | 220.32 | 01-AUG-00:10 | 339.04 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.10 | 08-AUG-16:00 | 110.75 | 19-AUG-04:00 |
September | 220.32 | 01-SEP-00:10 | 339.04 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 01-SEP-16:00 | 134.38 | 06-SEP-04:10 |
October | 220.32 | 01-OCT-23:10 | 339.04 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 19-OCT-15:00 | 209.69 | 30-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 339.04 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 291.05 | 29-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 339.04 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 366.70 | 24-DEC-06:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.20 | |||||
Maximum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 | 384.45 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 883.94 | 05-JAN-22:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 814.31 | 14-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 794.29 | 15-MAR-07:30 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 63.00 | 23-APR-16:00 | 610.66 | 05-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 92.39 | 25-MAY-17:00 | 435.59 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 166.90 | 29-JUN-16:00 | 329.49 | 04-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 110.56 | 23-JUL-16:00 | 263.17 | 02-JUL-04:57 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 110.05 | 08-AUG-16:00 | 277.00 | 19-AUG-06:10 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 47.51 | 01-SEP-16:00 | 356.92 | 21-SEP-06:10 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 540.03 | 30-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 727.57 | 29-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 827.52 | 19-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 263.17 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 166.90 | 883.94 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1957.67 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1570.90 | 06-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1957.67 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1532.04 | 14-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1957.67 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1397.84 | 05-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1957.67 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.29 | 23-APR-17:20 | 998.32 | 05-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1957.67 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.09 | 25-MAY-18:00 | 702.44 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1957.67 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 29-JUN-16:00 | 552.56 | 04-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1957.67 | 07-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.62 | 15-JUL-15:10 | 441.20 | 02-JUL-04:58 |
August | 15368.40 | 01-AUG-00:10 | 1957.67 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.63 | 08-AUG-15:30 | 482.35 | 19-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1957.67 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 01-SEP-15:40 | 588.32 | 06-SEP-04:10 |
October | 15368.40 | 01-OCT-23:10 | 1957.67 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 882.17 | 30-OCT-04:20 |
November | 15368.40 | 01-NOV-00:10 | 1957.67 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1222.53 | 29-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1957.67 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1487.09 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.20 | |||||
Maximum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 1570.90 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 8554.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4601.62 | 06-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 8554.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4566.64 | 14-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 8554.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4167.18 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 8554.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.57 | 23-APR-16:00 | 2948.29 | 05-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 8554.32 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.49 | 25-MAY-18:00 | 2112.42 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 8554.32 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 754.25 | 29-JUN-16:00 | 1682.91 | 04-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 8554.32 | 07-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.75 | 15-JUL-15:00 | 1332.23 | 02-JUL-04:58 |
August | 45622.98 | 01-AUG-00:10 | 8554.32 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.70 | 08-AUG-16:00 | 1454.08 | 19-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 8554.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.62 | 01-SEP-15:40 | 1750.92 | 06-SEP-04:50 |
October | 45622.98 | 01-OCT-23:10 | 8554.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2631.16 | 30-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 8554.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3562.81 | 29-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 8554.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4369.84 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.23 | |||||
Maximum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 754.25 | 4601.62 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 456.10 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.50 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.08 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.69 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 01-SEP-15:50 | 141.89 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.38 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 424.46 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 456.10 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 453.17 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 443.56 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.06 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.68 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.88 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:08 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.13 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 422.74 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 453.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 132.12 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 126.45 | 06-JAN-09:00 |
February | 0.00 | 01-FEB-00:10 | 132.12 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 119.23 | 14-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 132.12 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 106.68 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 132.12 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 23-APR-16:00 | 69.00 | 05-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 132.12 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 | 25-MAY-18:00 | 49.56 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 132.12 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 29-JUN-16:00 | 40.60 | 04-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 132.12 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 15-JUL-14:00 | 31.90 | 02-JUL-04:51 |
August | 0.00 | 01-AUG-00:10 | 132.12 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 08-AUG-15:00 | 34.04 | 19-AUG-04:00 |
September | 0.00 | 01-SEP-00:10 | 132.12 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 01-SEP-15:00 | 42.22 | 06-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 132.12 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 60.22 | 30-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 132.12 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 85.10 | 29-NOV-06:00 |
December | 0.00 | 01-DEC-00:10 | 132.12 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 114.21 | 24-DEC-08:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 | |||||
Maximum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 126.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 124.42 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 121.75 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 111.02 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 23-APR-16:00 | 73.46 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 25-MAY-17:00 | 50.88 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 29-JUN-16:00 | 39.56 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 15-JUL-15:10 | 28.94 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 08-AUG-15:10 | 32.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 01-SEP-15:08 | 39.60 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 19-OCT-15:00 | 64.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 89.91 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 116.51 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 124.42 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 460.05 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 443.92 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.08 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.69 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.89 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:08 | 232.39 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 425.32 | 24-DEC-09:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 460.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 453.36 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 440.33 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.05 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.68 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:08 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.88 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:07 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.13 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 423.58 | 24-DEC-09:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 453.36 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 531.22 | 06-JAN-09:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 520.25 | 14-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 470.65 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 | 23-APR-16:00 | 317.31 | 05-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 | 25-MAY-18:00 | 219.47 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.37 | 29-JUN-16:00 | 179.00 | 04-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 15-JUL-14:00 | 144.82 | 02-JUL-04:58 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.27 | 08-AUG-16:00 | 149.07 | 19-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 01-SEP-16:00 | 184.57 | 06-SEP-04:03 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 280.02 | 30-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 388.53 | 29-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 496.39 | 24-DEC-06:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.82 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.37 | 531.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 454.92 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.44 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 23-APR-16:00 | 263.74 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 25-MAY-17:00 | 182.76 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 29-JUN-16:00 | 142.18 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 | 15-JUL-15:10 | 104.73 | 07-JUL-20:50 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-15:10 | 117.49 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 01-SEP-16:00 | 142.34 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:10 | 232.88 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.69 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 423.95 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.73 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 454.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 453.12 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 441.64 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 400.63 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.80 | 23-APR-16:00 | 263.72 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.04 | 25-MAY-17:00 | 182.75 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 29-JUN-16:00 | 142.17 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.36 | 15-JUL-15:10 | 104.12 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-15:10 | 117.48 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 01-SEP-15:10 | 142.33 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:08 | 232.87 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.67 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 420.97 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 453.12 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 237.80 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 228.23 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 204.99 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 23-APR-16:00 | 134.94 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 25-MAY-17:00 | 93.51 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 29-JUN-16:00 | 72.75 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 15-JUL-15:10 | 53.27 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 08-AUG-15:10 | 60.11 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 01-SEP-16:00 | 72.83 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 | 19-OCT-15:10 | 119.15 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 165.10 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 217.91 | 24-DEC-09:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 237.80 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1061.94 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1049.04 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 968.36 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 23-APR-16:00 | 696.65 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 25-MAY-18:00 | 497.51 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 29-JUN-16:00 | 396.96 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 | 15-JUL-14:00 | 308.04 | 02-JUL-04:57 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | 08-AUG-15:40 | 336.06 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 01-SEP-15:40 | 397.44 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 621.17 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 836.28 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1015.57 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.04 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 1061.94 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1061.52 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1049.92 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 970.39 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 23-APR-16:00 | 696.88 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 25-MAY-18:00 | 497.52 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 29-JUN-16:00 | 396.97 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 | 15-JUL-14:00 | 308.45 | 02-JUL-04:57 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | 08-AUG-15:40 | 336.07 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 01-SEP-15:40 | 397.44 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 621.17 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 840.72 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1019.10 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.45 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 1061.52 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 927.20 | 06-JAN-08:20 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 893.92 | 14-FEB-07:30 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 816.85 | 05-MAR-07:10 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 36.19 | 23-APR-16:00 | 623.77 | 05-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 74.18 | 25-MAY-18:00 | 445.32 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 149.69 | 29-JUN-16:00 | 355.10 | 04-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 97.20 | 15-JUL-14:00 | 285.98 | 02-JUL-05:03 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 91.54 | 08-AUG-15:40 | 319.85 | 19-AUG-06:10 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 28.43 | 01-SEP-15:40 | 358.81 | 13-SEP-06:10 |
October | 2401.70 | 01-OCT-23:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 553.55 | 30-OCT-05:10 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 740.83 | 29-NOV-06:20 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 879.41 | 24-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 285.98 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 149.69 | 927.20 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 901.94 | 06-JAN-09:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 900.05 | 14-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 821.26 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.65 | 23-APR-16:00 | 562.51 | 05-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.59 | 25-MAY-18:00 | 389.31 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 29-JUN-16:00 | 307.01 | 04-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 15-JUL-14:00 | 246.85 | 02-JUL-04:58 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 08-AUG-16:00 | 256.63 | 19-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 01-SEP-15:30 | 314.20 | 06-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 496.49 | 30-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 688.58 | 29-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 859.49 | 24-DEC-06:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.85 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 901.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34464.12 | 25-JAN-21:00 | 8945.92 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32705.48 | 24-FEB-22:52 | 57509.46 | 51505.82 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31400.92 | 12-MAR-03:51 | 89459.16 | 34336.53 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22880.53 | 12-APR-07:40 | 51119.52 | 68675.11 | 50697.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24412.28 | 08-MAY-07:05 | 20447.81 | 27470.04 | 20279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24185.04 | 17-JUN-00:08 | 57509.46 | 17168.27 | 15209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24565.69 | 02-JUL-04:44 | 89459.16 | 34336.53 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33797.05 | 25-AUG-02:30 | 69011.35 | 10301.57 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37921.97 | 14-SEP-23:35 | 69011.35 | 20601.92 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39184.36 | 26-OCT-05:56 | 89459.16 | 68675.11 | 50697.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37115.21 | 19-NOV-23:08 | 102239.04 | 51505.82 | 40558.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33976.41 | 02-DEC-06:00 | 11501.89 | 1716.93 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22880.53 | 8945.92 | 1716.93 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39184.36 | 102239.04 | 68675.11 | 50697.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2140.20 | 27-JAN-13:40 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.34 |
February | 4063.26 | 28-FEB-15:28 | 1559.38 | 795.95 | 1010.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.68 |
March | 4375.51 | 26-MAR-13:10 | 2339.06 | 1432.71 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.45 |
April | 4612.79 | 19-APR-14:03 | 3508.60 | 1790.89 | 2273.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.47 |
May | 3901.06 | 18-MAY-13:10 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 47.28 | 0.00 |
June | 4040.80 | 30-JUN-13:00 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 0.00 |
July | 4143.34 | 23-JUL-13:10 | 259.90 | 159.19 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 | 0.00 |
August | 4508.85 | 26-AUG-12:40 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 0.00 |
September | 4534.92 | 01-SEP-13:20 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 0.00 |
October | 5325.69 | 09-OCT-13:21 | 2598.96 | 1591.90 | 2165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.54 |
November | 5513.14 | 17-NOV-11:31 | 2079.17 | 1591.90 | 2020.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.96 |
December | 2261.19 | 10-DEC-12:22 | 1949.22 | 1193.92 | 1443.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2140.20 | 259.90 | 159.19 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5513.14 | 3508.60 | 1790.89 | 2273.32 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 601.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2659.35 | 25-JAN-20:01 | 8426.88 | 6636.33 | 6351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 |
February | 2513.67 | 13-FEB-21:22 | 7223.04 | 4424.22 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.75 |
March | 2117.81 | 07-MAR-00:41 | 10834.56 | 1474.74 | 2005.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.64 |
April | 3151.70 | 18-APR-21:21 | 10834.56 | 4424.22 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.32 |
May | 2267.80 | 06-MAY-23:08 | 4213.44 | 1106.05 | 1337.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.17 |
June | 2220.77 | 30-JUN-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
July | 2226.89 | 02-JUL-04:44 | 10533.60 | 1843.42 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 |
August | 2489.91 | 25-AUG-05:45 | 2106.72 | 737.37 | 835.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.82 |
September | 3249.73 | 05-SEP-21:08 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.00 |
October | 2626.78 | 26-OCT-20:43 | 10834.56 | 6636.33 | 6769.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.45 |
November | 2001.69 | 02-NOV-01:07 | 4062.96 | 276.51 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.25 |
December | 1510.70 | 02-DEC-00:22 | 6771.60 | 921.71 | 1253.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1510.70 | 1203.84 | 276.51 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | |
Maximum of Months | 3249.73 | 13543.20 | 6636.33 | 6769.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 558.77 | 19-JAN-22:00 | 254.59 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.21 |
February | 774.52 | 20-FEB-19:05 | 1145.66 | 3118.57 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.02 |
March | 1277.38 | 31-MAR-21:49 | 2577.74 | 4009.59 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.52 |
April | 1420.89 | 15-APR-01:03 | 859.25 | 222.76 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.17 |
May | 1570.34 | 20-MAY-06:36 | 795.60 | 1113.78 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.80 |
June | 1712.29 | 30-JUN-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
July | 1645.16 | 02-JUL-04:44 | 2227.68 | 1485.03 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.69 |
August | 1539.24 | 18-AUG-23:22 | 1718.50 | 891.02 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.11 |
September | 1636.12 | 15-SEP-01:55 | 1145.66 | 297.01 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 |
October | 1551.55 | 23-OCT-22:20 | 2864.16 | 2227.55 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.89 |
November | 1378.03 | 02-NOV-01:07 | 859.25 | 222.76 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.17 |
December | 604.45 | 05-DEC-22:00 | 254.59 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 558.77 | 222.77 | 222.76 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1712.29 | 2864.16 | 4009.59 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 282.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23.96 | 19-JAN-21:50 | 195.84 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.11 |
February | 264.72 | 21-FEB-21:00 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.16 |
March | 811.60 | 31-MAR-21:49 | 1982.88 | 2034.20 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.20 |
April | 912.10 | 15-APR-01:03 | 660.96 | 113.02 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.85 |
May | 1003.86 | 20-MAY-06:36 | 612.00 | 565.04 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.92 |
June | 1013.03 | 08-JUN-01:55 | 440.64 | 75.35 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.26 |
July | 1057.06 | 02-JUL-04:44 | 1713.60 | 753.41 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.66 |
August | 981.30 | 18-AUG-23:22 | 1321.92 | 452.04 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 |
September | 1050.67 | 15-SEP-01:55 | 881.28 | 150.70 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.55 |
October | 987.70 | 23-OCT-22:20 | 2203.20 | 1130.08 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.13 |
November | 889.03 | 02-NOV-01:07 | 660.96 | 113.02 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 |
December | 96.89 | 05-DEC-22:00 | 195.84 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23.96 | 171.36 | 75.35 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 | |
Maximum of Months | 1057.06 | 2203.20 | 2034.20 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40321.17 | 25-JAN-20:01 | 5644.80 | 3628.84 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 0.00 | 795.19 |
February | 39386.15 | 04-FEB-19:06 | 4233.60 | 2469.63 | 26955.46 | 234177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 298.23 |
March | 50171.01 | 28-MAR-19:37 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 320.26 |
April | 49409.49 | 11-APR-20:49 | 5644.80 | 2822.43 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 |
May | 49339.13 | 08-MAY-20:57 | 7257.60 | 3628.84 | 38989.14 | 338721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 284.20 |
June | 41995.81 | 03-JUN-21:50 | 6350.40 | 2721.63 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 237.90 |
July | 38862.08 | 21-JUL-20:00 | 1411.20 | 907.21 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
August | 38776.97 | 08-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
September | 51063.98 | 23-SEP-21:46 | 7056.00 | 3024.03 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 263.70 |
October | 53178.45 | 16-OCT-19:27 | 6350.40 | 4082.44 | 41155.21 | 357539.19 | 0.00 | 0.00 | 0.00 | 0.00 | 294.21 |
November | 49084.52 | 17-NOV-20:34 | 6350.40 | 4082.44 | 41155.21 | 357539.19 | 0.00 | 0.00 | 0.00 | 0.00 | 319.79 |
December | 38905.34 | 23-DEC-21:42 | 4233.60 | 2116.82 | 23104.68 | 200723.75 | 0.00 | 0.00 | 0.00 | 0.00 | 788.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38776.97 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53178.45 | 7257.60 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 14.02 | 795.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9078.81 | 01-JAN-10:22 | 76842.00 | 1292.06 | 3657.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1328.30 |
February | 16533.49 | 28-FEB-15:28 | 20491.20 | 478.54 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.06 |
March | 17344.63 | 31-MAR-15:18 | 68304.00 | 957.08 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.73 |
April | 18321.84 | 19-APR-14:03 | 46105.20 | 1076.72 | 3200.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.77 |
May | 16152.25 | 02-MAY-23:57 | 92210.40 | 2610.23 | 1828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.36 |
June | 15572.05 | 17-JUN-00:08 | 76842.00 | 2175.19 | 1524.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.35 |
July | 15085.74 | 02-JUL-04:44 | 119532.00 | 2653.73 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.68 |
August | 15672.23 | 18-AUG-23:22 | 92210.40 | 2610.23 | 1828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.82 |
September | 19277.18 | 15-SEP-00:55 | 92210.40 | 1957.67 | 1524.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.15 |
October | 19864.95 | 09-OCT-11:00 | 15368.40 | 430.69 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.32 |
November | 20434.73 | 17-NOV-11:31 | 27321.60 | 957.08 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.07 |
December | 10383.21 | 10-DEC-12:28 | 25614.00 | 717.81 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9078.81 | 15368.40 | 430.69 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.73 | |
Maximum of Months | 20434.73 | 119532.00 | 2653.73 | 3657.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56670.78 | 25-JAN-20:01 | 283876.32 | 68434.56 | 80233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3876.67 |
February | 55561.89 | 24-FEB-22:52 | 228114.90 | 28514.40 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.68 |
March | 66958.61 | 31-MAR-21:41 | 410606.82 | 51325.92 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1481.50 |
April | 66796.05 | 18-APR-22:47 | 410606.82 | 25662.96 | 38005.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1467.25 |
May | 64895.19 | 06-MAY-00:47 | 136868.94 | 5702.88 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1353.63 |
June | 64172.58 | 17-JUN-01:10 | 364983.84 | 7603.84 | 16891.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.51 |
July | 52737.64 | 08-JUL-01:27 | 273737.88 | 5702.88 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.00 |
August | 58073.25 | 05-AUG-01:28 | 456229.80 | 9504.80 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.87 |
September | 70838.71 | 14-SEP-23:35 | 273737.88 | 11405.76 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1354.62 |
October | 69286.21 | 22-OCT-22:18 | 405537.60 | 28514.40 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1312.49 |
November | 49665.58 | 17-NOV-21:15 | 81107.52 | 15207.68 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1534.61 |
December | 47888.10 | 02-DEC-00:31 | 364983.84 | 15207.68 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3854.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 47888.10 | 81107.52 | 5702.88 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.87 | |
Maximum of Months | 70838.71 | 456229.80 | 68434.56 | 80233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 877.07 | 17-JAN-16:03 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.13 |
February | 3903.38 | 20-FEB-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.49 |
March | 4028.01 | 31-MAR-15:01 | 874.80 | 529.77 | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.76 |
April | 4690.71 | 11-APR-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.84 |
May | 5031.81 | 06-MAY-18:42 | 702.00 | 1261.35 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.75 |
June | 4345.12 | 07-JUN-21:41 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.89 |
July | 4604.28 | 04-JUL-16:32 | 572.40 | 416.24 | 632.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 |
August | 4499.42 | 05-AUG-20:41 | 1386.00 | 2102.25 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 |
September | 4558.06 | 04-SEP-18:01 | 1170.00 | 2102.25 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.23 |
October | 4137.39 | 20-OCT-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.62 |
November | 3822.01 | 17-NOV-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.42 |
December | 569.68 | 24-DEC-08:62 | 572.40 | 706.35 | 1422.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 569.68 | 378.00 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | |
Maximum of Months | 5031.81 | 1800.00 | 2102.25 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 597.08 | 20-JAN-16:04 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.63 |
February | 2240.40 | 28-FEB-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.55 |
March | 3781.05 | 27-MAR-18:01 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 |
April | 4418.33 | 11-APR-18:11 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 |
May | 4812.35 | 06-MAY-18:42 | 702.00 | 1261.20 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 |
June | 4155.76 | 07-JUN-21:41 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.84 |
July | 4287.43 | 05-JUL-16:51 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
August | 4321.30 | 05-AUG-20:41 | 1386.00 | 2102.00 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.52 |
September | 4218.86 | 04-SEP-18:01 | 1170.00 | 2102.00 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 |
October | 3740.28 | 21-OCT-15:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 |
November | 688.10 | 15-NOV-19:04 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.73 |
December | 566.02 | 24-DEC-08:62 | 572.40 | 706.27 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 566.02 | 324.00 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | |
Maximum of Months | 4812.35 | 1800.00 | 2102.00 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 362.98 | 05-JAN-12:00 | 0.00 | 73.99 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.12 |
February | 381.00 | 22-FEB-14:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.48 |
March | 512.99 | 20-MAR-12:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 |
April | 649.72 | 13-APR-13:20 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
May | 682.10 | 18-MAY-13:10 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 0.00 |
June | 676.18 | 30-JUN-13:00 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 0.00 |
July | 717.76 | 23-JUL-13:20 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 0.00 |
August | 785.09 | 25-AUG-13:10 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 | 0.00 |
September | 789.59 | 01-SEP-13:10 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 | 0.00 |
October | 934.00 | 22-OCT-12:30 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
November | 391.62 | 17-NOV-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 |
December | 351.06 | 24-DEC-12:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 351.06 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 934.00 | 0.00 | 73.99 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 106.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 414.96 | 26-JAN-08:61 | 619.20 | 465.18 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.37 |
February | 407.26 | 14-FEB-08:61 | 619.20 | 465.18 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.95 |
March | 443.81 | 31-MAR-15:03 | 874.80 | 333.03 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 |
April | 1089.80 | 13-APR-19:41 | 1386.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
May | 1168.95 | 21-MAY-21:01 | 1386.00 | 1123.31 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 |
June | 1168.43 | 07-JUN-08:51 | 288.00 | 465.18 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 |
July | 1179.57 | 05-JUL-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 |
August | 1153.84 | 02-AUG-20:21 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.06 |
September | 1113.61 | 08-SEP-19:41 | 1386.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
October | 1042.30 | 21-OCT-18:31 | 1170.00 | 1321.54 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 |
November | 464.57 | 01-NOV-18:03 | 554.40 | 470.47 | 474.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 |
December | 401.10 | 24-DEC-08:62 | 572.40 | 444.04 | 1393.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 401.10 | 288.00 | 333.03 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | |
Maximum of Months | 1179.57 | 1800.00 | 1321.54 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 596.43 | 26-JAN-08:61 | 619.20 | 739.99 | 906.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.08 |
February | 2469.57 | 28-FEB-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.69 |
March | 3621.43 | 31-MAR-15:01 | 874.80 | 529.77 | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.65 |
April | 3789.76 | 22-APR-19:21 | 1170.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.77 |
May | 4221.90 | 18-MAY-08:32 | 216.00 | 554.99 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.74 |
June | 4245.34 | 27-JUN-08:32 | 216.00 | 554.99 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 |
July | 4412.98 | 01-JUL-08:32 | 324.00 | 706.35 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 |
August | 4187.88 | 13-AUG-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.08 |
September | 3930.44 | 01-SEP-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.54 |
October | 3644.64 | 20-OCT-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.83 |
November | 2229.46 | 16-NOV-09:01 | 252.00 | 647.49 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.31 |
December | 565.58 | 24-DEC-08:62 | 572.40 | 706.35 | 1422.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 565.58 | 216.00 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | |
Maximum of Months | 4412.98 | 1386.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 589.67 | 26-JAN-08:61 | 619.20 | 739.90 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.05 |
February | 820.01 | 27-FEB-09:03 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.63 |
March | 3055.06 | 26-MAR-08:61 | 378.00 | 823.98 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.89 |
April | 3538.49 | 22-APR-08:61 | 432.00 | 941.70 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.73 |
May | 4021.22 | 18-MAY-08:32 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 |
June | 4064.06 | 28-JUN-08:62 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 |
July | 4223.19 | 01-JUL-08:32 | 324.00 | 706.27 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 |
August | 4008.62 | 13-AUG-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.05 |
September | 3738.07 | 01-SEP-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.41 |
October | 3248.34 | 01-OCT-15:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 |
November | 870.19 | 17-NOV-09:03 | 252.00 | 647.42 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.54 |
December | 561.50 | 24-DEC-08:62 | 572.40 | 706.27 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 561.50 | 216.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 | |
Maximum of Months | 4223.19 | 619.20 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1450.49 | 26-JAN-07:00 | 1760.39 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.59 |
February | 2220.48 | 04-FEB-16:06 | 6035.62 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.33 |
March | 2929.69 | 31-MAR-21:49 | 20370.20 | 11203.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.00 |
April | 3298.23 | 15-APR-01:03 | 6790.07 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.86 |
May | 3682.06 | 06-MAY-23:08 | 7041.55 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.13 |
June | 3701.28 | 17-JUN-01:17 | 6790.07 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.44 |
July | 3822.07 | 02-JUL-04:44 | 17603.88 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.35 |
August | 3479.72 | 18-AUG-23:22 | 13580.14 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.93 |
September | 3816.77 | 15-SEP-01:55 | 9053.42 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.15 |
October | 3501.13 | 20-OCT-04:03 | 9053.42 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.42 |
November | 2917.82 | 16-NOV-14:26 | 2514.84 | 2593.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.80 |
December | 1100.25 | 24-DEC-07:30 | 1760.39 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1100.25 | 1760.39 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.33 | |
Maximum of Months | 3822.07 | 20370.20 | 11203.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 843.64 | 20-JAN-16:03 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.11 |
February | 4041.38 | 20-FEB-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.69 |
March | 4174.65 | 31-MAR-15:01 | 874.80 | 529.77 | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.03 |
April | 4987.01 | 11-APR-17:52 | 583.20 | 845.10 | 758.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.22 |
May | 5299.53 | 06-MAY-18:42 | 702.00 | 1261.35 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.52 |
June | 4575.33 | 07-JUN-21:41 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 |
July | 4959.89 | 04-JUL-16:32 | 572.40 | 416.24 | 632.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 |
August | 4879.70 | 02-AUG-20:02 | 961.20 | 1122.60 | 1090.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.84 |
September | 4819.93 | 04-SEP-18:01 | 1170.00 | 2102.25 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.80 |
October | 4445.48 | 20-OCT-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.70 |
November | 3977.88 | 17-NOV-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 |
December | 563.64 | 24-DEC-08:62 | 572.40 | 706.35 | 1422.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 563.64 | 378.00 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | |
Maximum of Months | 5299.53 | 1800.00 | 2102.25 | 1422.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 584.16 | 26-JAN-08:61 | 619.20 | 739.90 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.13 |
February | 1035.23 | 28-FEB-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.63 |
March | 3943.55 | 27-MAR-18:01 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.98 |
April | 4640.82 | 11-APR-18:11 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.32 |
May | 5045.85 | 06-MAY-18:32 | 702.00 | 1261.20 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.89 |
June | 4368.20 | 07-JUN-21:41 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.50 |
July | 4691.23 | 04-JUL-16:32 | 572.40 | 416.20 | 632.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 |
August | 4640.83 | 02-AUG-20:02 | 961.20 | 1122.47 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.92 |
September | 4527.80 | 08-SEP-19:41 | 1386.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.57 |
October | 3856.84 | 01-OCT-15:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 |
November | 876.74 | 09-NOV-16:03 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.17 |
December | 558.78 | 24-DEC-08:62 | 572.40 | 706.27 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 558.78 | 378.00 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | |
Maximum of Months | 5045.85 | 1800.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2272.94 | 27-JAN-16:01 | 680.40 | 259.02 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.57 |
February | 2307.74 | 04-FEB-16:01 | 432.00 | 348.89 | 433.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 |
March | 2354.82 | 31-MAR-15:01 | 874.80 | 333.03 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.81 |
April | 2560.68 | 13-APR-19:41 | 1386.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 |
May | 2530.24 | 05-MAY-19:51 | 1386.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.66 |
June | 2419.20 | 20-JUN-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.52 |
July | 2433.10 | 26-JUL-21:11 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 |
August | 2553.02 | 05-AUG-20:41 | 1386.00 | 1321.54 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 |
September | 2556.86 | 04-SEP-18:01 | 1170.00 | 1321.54 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.06 |
October | 2615.03 | 20-OCT-18:11 | 1386.00 | 1176.17 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.88 |
November | 2280.42 | 17-NOV-16:01 | 680.40 | 259.02 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.80 |
December | 2171.00 | 02-DEC-16:02 | 324.00 | 261.67 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2171.00 | 324.00 | 259.02 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 | |
Maximum of Months | 2615.03 | 1800.00 | 1321.54 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26120.72 | 25-JAN-20:01 | 167930.11 | 27502.72 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.60 |
February | 25344.53 | 24-FEB-22:52 | 134943.84 | 11459.46 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.52 |
March | 31527.46 | 31-MAR-21:40 | 53977.54 | 4583.79 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.79 |
April | 32020.08 | 14-APR-02:42 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.07 |
May | 32804.56 | 15-MAY-05:43 | 209912.64 | 10186.19 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.09 |
June | 32106.76 | 02-JUN-22:20 | 53977.54 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.03 |
July | 31693.32 | 02-JUL-01:24 | 209912.64 | 7639.64 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.86 |
August | 31009.68 | 19-AUG-01:47 | 80966.30 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.29 |
September | 38100.27 | 14-SEP-01:18 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.06 |
October | 37186.86 | 20-OCT-04:03 | 107955.07 | 3055.86 | 8997.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.27 |
November | 30801.65 | 19-NOV-23:20 | 71970.05 | 3437.84 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.08 |
December | 24603.14 | 23-DEC-21:42 | 125947.58 | 16043.25 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24603.14 | 53977.54 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.86 | |
Maximum of Months | 38100.27 | 209912.64 | 27502.72 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27772.79 | 25-JAN-20:01 | 167930.11 | 27502.72 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.25 |
February | 26874.12 | 24-FEB-22:52 | 134943.84 | 11459.46 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.17 |
March | 33388.98 | 31-MAR-21:40 | 53977.54 | 4583.79 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.97 |
April | 34071.69 | 24-APR-02:50 | 80966.30 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.51 |
May | 36335.30 | 15-MAY-05:43 | 209912.64 | 10186.19 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.18 |
June | 38963.24 | 17-JUN-00:40 | 80966.30 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.58 |
July | 33354.69 | 02-JUL-01:24 | 209912.64 | 7639.64 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.90 |
August | 33277.29 | 19-AUG-00:17 | 188921.38 | 5347.75 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.06 |
September | 39986.71 | 14-SEP-01:18 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.47 |
October | 40395.29 | 20-OCT-04:03 | 107955.07 | 3055.86 | 8997.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.21 |
November | 32681.41 | 19-NOV-23:20 | 71970.05 | 3437.84 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.61 |
December | 26279.33 | 23-DEC-21:42 | 125947.58 | 16043.25 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26279.33 | 53977.54 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.90 | |
Maximum of Months | 40395.29 | 209912.64 | 27502.72 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28430.58 | 25-JAN-20:01 | 14943.94 | 9687.39 | 119302.85 | 119961.77 | 0.00 | 0.00 | 0.00 | 0.00 | 810.98 |
February | 37321.88 | 21-FEB-15:05 | 8005.68 | 3363.68 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 253.03 |
March | 35585.43 | 31-MAR-10:36 | 4269.70 | 2690.94 | 119302.85 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 344.34 |
April | 38809.11 | 10-APR-09:17 | 3202.27 | 2018.21 | 89477.13 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 255.38 |
May | 37138.40 | 06-MAY-07:38 | 12008.52 | 4843.69 | 134215.70 | 134956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 253.23 |
June | 33946.02 | 02-JUN-06:35 | 6404.54 | 4036.41 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 0.00 | 225.85 |
July | 32127.28 | 23-JUL-10:40 | 2401.70 | 1210.92 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 49.90 | 0.00 |
August | 33910.28 | 19-AUG-06:36 | 13342.80 | 4036.41 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 243.01 |
September | 40373.87 | 05-SEP-06:07 | 10674.24 | 6727.35 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 278.00 |
October | 41873.63 | 27-OCT-17:27 | 13342.80 | 8072.82 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 284.55 |
November | 36350.30 | 17-NOV-18:34 | 13342.80 | 8072.82 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 314.08 |
December | 27318.12 | 23-DEC-21:42 | 11207.95 | 5650.98 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 0.00 | 802.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27318.12 | 2401.70 | 1210.92 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41873.63 | 14943.94 | 9687.39 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 49.90 | 810.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1031.24 | 29-JAN-13:00 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.46 |
February | 6258.64 | 21-FEB-15:05 | 7984.80 | 5489.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.74 |
March | 5696.00 | 31-MAR-21:49 | 21558.96 | 11857.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.25 |
April | 6290.00 | 15-APR-01:03 | 7186.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.89 |
May | 7004.95 | 06-MAY-23:08 | 7452.48 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.67 |
June | 6961.49 | 17-JUN-00:08 | 11977.20 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.34 |
July | 7058.11 | 02-JUL-04:44 | 18631.20 | 4391.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.20 |
August | 6644.67 | 18-AUG-23:22 | 14372.64 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.41 |
September | 7125.34 | 15-SEP-01:55 | 9581.76 | 878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.49 |
October | 6761.02 | 20-OCT-04:03 | 9581.76 | 1756.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.52 |
November | 5856.99 | 16-NOV-14:26 | 2661.60 | 2744.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.24 |
December | 1255.29 | 05-DEC-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1031.24 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.24 | |
Maximum of Months | 7125.34 | 21558.96 | 11857.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.46 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.394615E+12 | 251077.93 | 04-JAN-20:00 | 0.143007E+13 | 1227994.65 | 05-JAN-21:40 |
February | 0.350718E+12 | 248978.23 | 08-FEB-20:10 | 0.964568E+12 | 1123941.71 | 01-FEB-21:00 |
March | 0.383794E+12 | 252997.13 | 28-MAR-19:19 | 0.804083E+12 | 984612.83 | 05-MAR-07:19 |
April | 0.379365E+12 | 305543.36 | 23-APR-19:10 | 0.530746E+12 | 526327.99 | 28-APR-17:00 |
May | 0.439088E+12 | 365559.24 | 25-MAY-19:00 | 0.483861E+12 | 450270.34 | 08-MAY-17:19 |
June | 0.489874E+12 | 427352.72 | 29-JUN-18:10 | 0.444637E+12 | 398479.23 | 02-JUN-22:30 |
July | 0.545868E+12 | 393525.41 | 03-JUL-20:19 | 0.443205E+12 | 382453.39 | 11-JUL-17:19 |
August | 0.498766E+12 | 388342.71 | 08-AUG-19:40 | 0.439139E+12 | 377568.04 | 03-AUG-17:40 |
September | 0.407535E+12 | 309742.34 | 01-SEP-19:10 | 0.453500E+12 | 429221.02 | 28-SEP-17:00 |
October | 0.395291E+12 | 273605.02 | 19-OCT-19:19 | 0.530016E+12 | 490397.99 | 09-OCT-17:40 |
November | 0.375664E+12 | 258359.61 | 02-NOV-19:00 | 0.666583E+12 | 643697.38 | 25-NOV-17:30 |
December | 0.394291E+12 | 250169.45 | 18-DEC-20:10 | 0.132101E+13 | 1182945.31 | 24-DEC-22:00 |
Annual Sum or Average | 0.505487E+13 | 0.851142E+13 | ||||
Minimum of Months | 0.350718E+12 | 248978.23 | 0.439139E+12 | 377568.04 | ||
Maximum of Months | 0.545868E+12 | 427352.72 | 0.143007E+13 | 1227994.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.745705E+11 | 0.287108E+11 | 0.140828E+12 | 0.552135E+11 | 0.514089E+11 | 0.430547E+10 | 0.00 | 0.299038E+09 | 0.00 | 0.00 | 0.266205E+11 | 0.770917E+10 | 0.00 |
February | 0.670158E+11 | 0.235835E+11 | 0.127191E+12 | 0.498702E+11 | 0.418950E+11 | 0.432990E+10 | 0.00 | 0.127103E+10 | 0.00 | 0.00 | 0.240267E+11 | 0.696402E+10 | 0.00 |
March | 0.737920E+11 | 0.229226E+11 | 0.140882E+12 | 0.552166E+11 | 0.442342E+11 | 0.481617E+10 | 0.00 | 0.251996E+10 | 0.00 | 0.00 | 0.265660E+11 | 0.770414E+10 | 0.00 |
April | 0.708551E+11 | 0.189770E+11 | 0.136245E+12 | 0.534310E+11 | 0.427105E+11 | 0.686907E+10 | 0.00 | 0.151745E+11 | 0.00 | 0.00 | 0.226184E+11 | 0.746501E+10 | 0.00 |
May | 0.726037E+11 | 0.167238E+11 | 0.140860E+12 | 0.552136E+11 | 0.478715E+11 | 0.101630E+11 | 0.00 | 0.683341E+11 | 0.00 | 0.00 | 0.143562E+11 | 0.770431E+10 | 0.00 |
June | 0.699532E+11 | 0.146208E+11 | 0.136336E+12 | 0.534335E+11 | 0.482072E+11 | 0.104402E+11 | 0.00 | 0.134341E+12 | 0.00 | 0.00 | 0.993350E+10 | 0.745688E+10 | 0.00 |
July | 0.724672E+11 | 0.158425E+11 | 0.140770E+12 | 0.552099E+11 | 0.511052E+11 | 0.110202E+11 | 0.00 | 0.176700E+12 | 0.00 | 0.00 | 0.971353E+10 | 0.771254E+10 | 0.00 |
August | 0.730273E+11 | 0.183160E+11 | 0.140892E+12 | 0.552159E+11 | 0.498188E+11 | 0.107434E+11 | 0.00 | 0.130893E+12 | 0.00 | 0.00 | 0.680744E+10 | 0.770439E+10 | 0.00 |
September | 0.712422E+11 | 0.207795E+11 | 0.136256E+12 | 0.534314E+11 | 0.461717E+11 | 0.939025E+10 | 0.00 | 0.442462E+11 | 0.00 | 0.00 | 0.134224E+11 | 0.746626E+10 | 0.00 |
October | 0.741512E+11 | 0.247952E+11 | 0.140818E+12 | 0.552131E+11 | 0.461282E+11 | 0.638923E+10 | 0.00 | 0.114166E+11 | 0.00 | 0.00 | 0.234288E+11 | 0.770277E+10 | 0.00 |
November | 0.720849E+11 | 0.269082E+11 | 0.136330E+12 | 0.534334E+11 | 0.434333E+11 | 0.418088E+10 | 0.00 | 0.180723E+10 | 0.00 | 0.00 | 0.250341E+11 | 0.744932E+10 | 0.00 |
December | 0.746356E+11 | 0.294819E+11 | 0.140770E+12 | 0.552119E+11 | 0.505684E+11 | 0.406713E+10 | 0.00 | 0.212129E+09 | 0.00 | 0.00 | 0.266205E+11 | 0.771618E+10 | 0.00 |
Annual Sum or Average | 0.866399E+12 | 0.261662E+12 | 0.165818E+13 | 0.650094E+12 | 0.563553E+12 | 0.867149E+11 | 0.00 | 0.587215E+12 | 0.00 | 0.00 | 0.229148E+12 | 0.907550E+11 | 0.00 |
Minimum of Months | 0.670158E+11 | 0.146208E+11 | 0.127191E+12 | 0.498702E+11 | 0.418950E+11 | 0.406713E+10 | 0.00 | 0.212129E+09 | 0.00 | 0.00 | 0.680744E+10 | 0.696402E+10 | 0.00 |
Maximum of Months | 0.746356E+11 | 0.294819E+11 | 0.140892E+12 | 0.552166E+11 | 0.514089E+11 | 0.110202E+11 | 0.00 | 0.176700E+12 | 0.00 | 0.00 | 0.266205E+11 | 0.771618E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.961986E+12 | 0.00 | 0.316166E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.539431E+12 | 0.00 | 0.287933E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.333609E+12 | 0.00 | 0.318450E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.791363E+11 | 0.00 | 0.304654E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.227930E+11 | 0.00 | 0.309090E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.855345E+10 | 0.00 | 0.288970E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.353748E+10 | 0.00 | 0.287847E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.476471E+10 | 0.00 | 0.282335E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.324014E+11 | 0.00 | 0.274128E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.877086E+11 | 0.00 | 0.290404E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.227160E+12 | 0.00 | 0.292332E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.858368E+12 | 0.00 | 0.310821E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.315945E+13 | 0.00 | 0.356313E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.353748E+10 | 0.00 | 0.274128E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.961986E+12 | 0.00 | 0.318450E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 71560.59 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39721.54 | 02-JAN-07:19 | 28882.25 | 09-JAN-07:10 | 5652.11 | 09-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 71560.59 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39721.54 | 01-FEB-07:19 | 28179.65 | 17-FEB-05:10 | 5433.18 | 14-FEB-10:50 | 0.00 | 01-FEB-00:10 |
March | 71560.59 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39721.54 | 01-MAR-07:19 | 29329.43 | 31-MAR-21:19 | 5217.34 | 15-MAR-08:39 | 0.00 | 01-MAR-00:10 |
April | 71560.59 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39720.93 | 03-APR-06:19 | 36064.57 | 22-APR-23:49 | 4946.53 | 11-APR-21:19 | 0.00 | 01-APR-00:10 |
May | 71560.59 | 01-MAY-19:30 | 16690.39 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39718.45 | 22-MAY-06:19 | 39887.77 | 06-MAY-00:30 | 4976.36 | 13-MAY-00:30 | 0.00 | 01-MAY-00:10 |
June | 71560.59 | 01-JUN-19:49 | 16690.39 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39719.36 | 09-JUN-06:19 | 35835.67 | 30-JUN-20:10 | 5589.06 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 71560.59 | 07-JUL-19:30 | 16690.39 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39718.62 | 03-JUL-06:19 | 36072.71 | 21-JUL-21:00 | 5255.71 | 21-JUL-19:19 | 0.00 | 01-JUL-00:10 |
August | 71560.59 | 01-AUG-19:40 | 16690.39 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39721.06 | 31-AUG-06:19 | 36267.59 | 24-AUG-21:30 | 5028.97 | 09-AUG-19:49 | 0.00 | 01-AUG-00:10 |
September | 71560.59 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39721.54 | 18-SEP-06:19 | 42620.91 | 25-SEP-21:40 | 5044.09 | 15-SEP-00:49 | 0.00 | 01-SEP-00:10 |
October | 71560.59 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39721.54 | 02-OCT-06:19 | 40592.48 | 23-OCT-22:30 | 5117.94 | 26-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 71560.59 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39721.54 | 01-NOV-06:19 | 31064.19 | 15-NOV-19:40 | 5012.95 | 17-NOV-10:50 | 0.00 | 01-NOV-00:10 |
December | 71560.59 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39721.54 | 01-DEC-07:19 | 28890.71 | 24-DEC-07:10 | 5592.76 | 02-DEC-10:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 71560.59 | 16690.39 | 89171.45 | 39718.45 | 28179.65 | 4946.53 | 0.00 | |||||||
Maximum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.54 | 42620.91 | 5652.11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3585.68 | 27-JAN-16:19 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 4743.91 | 13-JAN-07:10 | 0.00 |
February | 13369.16 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4743.07 | 14-FEB-07:30 | 0.00 |
March | 18460.71 | 31-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4739.67 | 15-MAR-06:00 | 0.00 |
April | 97850.01 | 23-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.33 | 10-APR-18:10 | 0.00 |
May | 140269.94 | 25-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.27 | 19-MAY-18:30 | 0.00 |
June | 206113.93 | 29-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.31 | 05-JUN-06:10 | 0.00 |
July | 174490.63 | 15-JUL-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUL-01:49 | 4738.36 | 11-JUL-06:49 | 0.00 |
August | 171515.17 | 08-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-23:49 | 4738.32 | 11-AUG-18:00 | 0.00 |
September | 118462.98 | 01-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-11:30 | 4738.50 | 05-SEP-18:00 | 0.00 |
October | 79131.52 | 19-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.52 | 20-OCT-18:19 | 0.00 |
November | 26407.41 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.43 | 03-NOV-18:10 | 0.00 |
December | 2743.45 | 02-DEC-13:39 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4742.49 | 20-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2743.45 | 0.00 | 0.00 | 9938.94 | 4738.27 | 0.00 | |||
Maximum of Months | 206113.93 | 0.00 | 0.00 | 9938.94 | 4743.91 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 251077.93 | 04-JAN-20:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 26012.27 | 2134.42 | 0.00 | 0.00 | 0.00 |
February | 248978.23 | 08-FEB-20:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 20351.45 | 4247.11 | 0.00 | 1506.85 | 0.00 |
March | 252997.13 | 28-MAR-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 22186.02 | 4173.06 | 0.00 | 4060.15 | 0.00 |
April | 305543.36 | 23-APR-19:10 | 66393.55 | 84978.71 | 16690.39 | 32028.15 | 20778.08 | 4126.08 | 0.00 | 73529.92 | 0.00 |
May | 365559.24 | 25-MAY-19:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 29176.94 | 4488.42 | 0.00 | 109221.89 | 0.00 |
June | 427352.72 | 29-JUN-18:10 | 58770.64 | 77573.37 | 0.00 | 31786.42 | 30434.51 | 5589.06 | 0.00 | 206113.93 | 0.00 |
July | 393525.41 | 03-JUL-20:19 | 63637.18 | 88218.55 | 16690.39 | 24564.92 | 31128.94 | 5007.34 | 0.00 | 148022.92 | 0.00 |
August | 388342.71 | 08-AUG-19:40 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 30040.57 | 4815.94 | 0.00 | 131106.91 | 0.00 |
September | 309742.34 | 01-SEP-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 26015.65 | 4034.52 | 0.00 | 67503.63 | 0.00 |
October | 273605.02 | 19-OCT-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 27574.10 | 4009.81 | 0.00 | 27460.29 | 0.00 |
November | 258359.61 | 02-NOV-19:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 29357.55 | 4193.44 | 0.00 | 2003.97 | 0.00 |
December | 250169.45 | 18-DEC-20:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 25509.17 | 1985.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 248978.23 | 58770.64 | 77573.37 | 0.00 | 24564.92 | 20351.45 | 1985.04 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 427352.72 | 71560.59 | 88218.55 | 16690.39 | 32090.84 | 31128.94 | 5589.06 | 0.00 | 206113.93 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 902207.62 | 06-JAN-04:00 | 0.00 | 312815.02 | 30-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 873575.39 | 17-FEB-05:00 | 0.00 | 314198.63 | 28-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 839746.08 | 05-MAR-06:49 | 0.00 | 314108.87 | 02-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 202759.29 | 05-APR-06:10 | 0.00 | 311523.25 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 158044.14 | 22-MAY-03:09 | 0.00 | 306077.53 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 107827.38 | 17-JUN-05:40 | 0.00 | 296123.04 | 07-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 69379.38 | 07-JUL-23:00 | 0.00 | 288329.62 | 05-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 92123.46 | 19-AUG-06:30 | 0.00 | 281565.32 | 10-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 160556.92 | 15-SEP-00:10 | 0.00 | 292823.06 | 20-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 184117.98 | 30-OCT-08:09 | 0.00 | 291332.14 | 30-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 326164.19 | 25-NOV-07:10 | 0.00 | 300520.09 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 873020.96 | 24-DEC-07:10 | 0.00 | 307782.03 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 69379.38 | 0.00 | 281565.32 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 902207.62 | 0.00 | 314198.63 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 143.67 | 18.91 | 143.67 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
February | 11.17 | 20.03 | 11.17 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49.83 | 19.63 | 49.83 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
Annual Sum or Average | 204.67 | 19.15 | 204.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.67 | 20.03 | 143.67 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 177.67 | 16.76 | 177.67 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
February | 63.67 | 17.53 | 63.67 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
March | 19.67 | 18.13 | 19.67 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 134.17 | 17.04 | 134.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
Annual Sum or Average | 395.17 | 17.05 | 395.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.67 | 18.13 | 177.67 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 164.67 | 18.13 | 164.67 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
February | 50.17 | 19.20 | 50.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
March | 11.00 | 19.73 | 11.00 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 133.00 | 18.94 | 133.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 358.83 | 18.63 | 358.83 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 164.67 | 19.73 | 164.67 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 224.33 | 18.91 | 224.33 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
February | 44.67 | 19.77 | 44.67 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
March | 8.67 | 20.26 | 8.67 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 153.67 | 19.56 | 153.67 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Annual Sum or Average | 431.33 | 19.26 | 431.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.33 | 20.26 | 224.33 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 266.33 | 18.63 | 266.33 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
February | 63.33 | 19.53 | 63.33 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
March | 15.33 | 20.00 | 15.33 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 197.67 | 19.24 | 197.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 542.67 | 18.99 | 542.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.33 | 20.00 | 266.33 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.50 | 12.64 | 104.50 | 12.64 | 0.00 | 12.64 | 0.00 | 12.64 |
February | 33.33 | 13.23 | 33.33 | 13.23 | 1.17 | 13.43 | 1.17 | 13.63 |
March | 10.67 | 14.88 | 10.67 | 14.88 | 10.50 | 18.20 | 10.50 | 19.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 24.96 | 25.33 | 24.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 24.97 | 16.33 | 24.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.05 | 2.00 | 25.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.88 | 0.67 | 24.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 25.15 | 21.17 | 25.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 25.05 | 54.00 | 25.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.05 | 9.50 | 25.05 |
December | 68.83 | 13.87 | 68.83 | 13.87 | 0.00 | 13.87 | 0.00 | 13.87 |
Annual Sum or Average | 217.33 | 13.23 | 217.33 | 13.23 | 140.67 | 16.11 | 140.67 | 17.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.50 | 14.88 | 104.50 | 14.88 | 54.00 | 25.15 | 54.00 | 25.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 157.33 | 17.35 | 157.33 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
February | 54.67 | 18.28 | 54.67 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
March | 12.17 | 18.53 | 12.17 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 127.50 | 17.98 | 127.50 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
Annual Sum or Average | 351.67 | 17.77 | 351.67 | 17.77 | 0.00 | 17.77 | 0.00 | 17.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.33 | 18.53 | 157.33 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 150.83 | 18.19 | 150.83 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
February | 40.83 | 19.22 | 40.83 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
March | 6.67 | 19.49 | 6.67 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 116.67 | 19.00 | 116.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
Annual Sum or Average | 315.00 | 18.65 | 315.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.83 | 19.49 | 150.83 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 20.21 | 26.17 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
February | 1.00 | 20.43 | 1.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.81 | 1.50 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.82 | 2.33 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.84 | 3.67 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.81 | 2.50 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.90 | 1.50 | 21.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.17 | 20.32 | 3.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 30.33 | 20.23 | 30.33 | 20.23 | 12.00 | 20.50 | 12.00 | 20.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.17 | 20.43 | 26.17 | 20.43 | 3.67 | 21.90 | 3.67 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.83 | 19.97 | 51.83 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 |
February | 2.00 | 20.30 | 2.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.83 | 2.17 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.89 | 2.83 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.87 | 1.33 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.07 | 0.33 | 22.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22.83 | 20.32 | 22.83 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 76.67 | 20.08 | 76.67 | 20.08 | 7.83 | 20.17 | 7.83 | 20.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.83 | 20.32 | 51.83 | 20.32 | 2.83 | 22.07 | 2.83 | 22.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 134.17 | 19.60 | 134.17 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 35.67 | 20.26 | 35.67 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
March | 2.33 | 20.40 | 2.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.85 | 0.50 | 21.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.83 | 5.17 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.82 | 5.17 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.73 | 2.50 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 20.42 | 2.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
December | 101.50 | 20.02 | 101.50 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 |
Annual Sum or Average | 275.67 | 19.85 | 275.67 | 19.85 | 13.50 | 19.90 | 13.50 | 19.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.17 | 20.42 | 134.17 | 20.42 | 5.17 | 21.85 | 5.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.33 | 20.01 | 30.33 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
February | 0.67 | 20.48 | 0.67 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.14 | 1.33 | 22.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.30 | 4.83 | 22.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 22.24 | 7.67 | 22.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.14 | 3.83 | 22.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.23 | 0.33 | 22.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.83 | 20.43 | 10.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 41.83 | 20.13 | 41.83 | 20.13 | 18.00 | 20.50 | 18.00 | 20.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.33 | 20.48 | 30.33 | 20.48 | 7.67 | 22.30 | 7.67 | 22.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.67 | 19.87 | 61.67 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
February | 4.00 | 20.43 | 4.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.10 | 1.33 | 22.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.30 | 5.17 | 22.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.29 | 7.50 | 22.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.21 | 2.83 | 22.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.47 | 0.17 | 22.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28.00 | 20.21 | 28.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
Annual Sum or Average | 93.67 | 20.00 | 93.67 | 20.00 | 17.00 | 20.19 | 17.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.67 | 20.43 | 61.67 | 20.43 | 7.50 | 22.47 | 7.50 | 22.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 182.67 | 19.24 | 182.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 50.83 | 19.90 | 50.83 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
March | 10.50 | 20.13 | 10.50 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 145.17 | 19.68 | 145.17 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
Annual Sum or Average | 389.17 | 19.51 | 389.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.67 | 20.13 | 182.67 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.50 | 20.09 | 29.50 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
February | 1.00 | 20.38 | 1.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.90 | 2.33 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.88 | 3.33 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.87 | 4.83 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.85 | 3.67 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.97 | 2.00 | 21.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.67 | 20.42 | 10.67 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 41.17 | 20.18 | 41.17 | 20.18 | 17.17 | 20.48 | 17.17 | 20.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.50 | 20.42 | 29.50 | 20.42 | 4.83 | 21.97 | 4.83 | 21.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.33 | 19.86 | 62.33 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
February | 3.83 | 20.35 | 3.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.86 | 2.17 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.90 | 3.00 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.95 | 3.50 | 21.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.89 | 2.17 | 21.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.96 | 1.00 | 21.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32.67 | 20.20 | 32.67 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
Annual Sum or Average | 98.83 | 19.99 | 98.83 | 19.99 | 12.33 | 20.10 | 12.33 | 20.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.33 | 20.35 | 62.33 | 20.35 | 3.50 | 21.96 | 3.50 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 20.44 | 5.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.85 | 1.17 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.44 | 1.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 6.83 | 20.45 | 6.83 | 20.45 | 6.67 | 20.88 | 6.67 | 21.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 20.51 | 5.33 | 20.51 | 1.83 | 21.85 | 1.83 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.67 | 17.72 | 64.67 | 17.72 | 0.00 | 17.72 | 0.00 | 17.72 |
February | 9.17 | 18.89 | 9.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.88 | 0.50 | 24.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.78 | 2.17 | 24.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.75 | 3.50 | 24.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.88 | 1.50 | 24.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.79 | 0.17 | 24.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.94 | 0.50 | 24.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.83 | 4.67 | 24.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.78 | 5.33 | 24.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.33 | 24.63 |
December | 35.50 | 18.75 | 35.50 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
Annual Sum or Average | 109.33 | 18.15 | 109.33 | 18.15 | 18.67 | 18.67 | 18.67 | 19.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 0.00 | 17.72 |
Maximum of Months | 64.67 | 18.89 | 64.67 | 18.89 | 5.33 | 24.94 | 5.33 | 24.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.50 | 17.71 | 59.50 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
February | 7.67 | 18.92 | 7.67 | 18.92 | 0.17 | 18.99 | 0.17 | 19.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.95 | 0.50 | 24.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.85 | 2.50 | 24.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.83 | 4.17 | 24.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.86 | 1.83 | 24.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.82 | 0.17 | 24.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.03 | 0.50 | 25.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.86 | 5.67 | 24.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.84 | 6.67 | 24.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 |
December | 29.67 | 18.77 | 29.67 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 96.83 | 18.13 | 96.83 | 18.13 | 22.83 | 18.84 | 22.83 | 19.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 | 0.00 | 17.71 |
Maximum of Months | 59.50 | 18.92 | 59.50 | 18.92 | 6.67 | 25.03 | 6.67 | 25.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.50 | 14.55 | 66.50 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
February | 23.00 | 15.43 | 23.00 | 15.43 | 4.83 | 16.35 | 4.83 | 17.12 |
March | 6.83 | 16.72 | 6.83 | 16.72 | 13.50 | 20.81 | 13.50 | 22.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 24.97 | 38.50 | 24.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 24.96 | 36.83 | 24.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.99 | 5.67 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.78 | 0.83 | 24.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.94 | 4.17 | 24.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 25.13 | 40.00 | 25.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 85.33 | 25.07 | 85.33 | 25.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 25.03 | 23.17 | 25.03 |
December | 43.33 | 15.27 | 43.33 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
Annual Sum or Average | 139.67 | 15.02 | 139.67 | 15.02 | 252.83 | 19.78 | 252.83 | 21.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 | 14.55 |
Maximum of Months | 66.50 | 16.72 | 66.50 | 16.72 | 85.33 | 25.13 | 85.33 | 25.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 190.67 | 18.44 | 190.67 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
February | 58.00 | 19.32 | 58.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 15.50 | 19.81 | 15.50 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 147.00 | 19.06 | 147.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Annual Sum or Average | 411.17 | 18.84 | 411.17 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 190.67 | 19.81 | 190.67 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.58 | 242.00 | 21.12 | 242.00 | 20.84 |
February | 672.00 | 22.40 | 46.50 | 22.28 | 46.50 | 22.17 |
March | 744.00 | 22.36 | 7.83 | 22.35 | 7.83 | 22.33 |
April | 720.00 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
May | 744.00 | 22.70 | 0.00 | 22.70 | 0.00 | 22.70 |
June | 703.00 | 22.90 | 31.17 | 22.90 | 31.17 | 22.90 |
July | 443.00 | 23.17 | 139.67 | 23.30 | 57.17 | 23.31 |
August | 124.17 | 23.55 | 298.00 | 23.81 | 41.67 | 23.82 |
September | 182.00 | 23.70 | 137.00 | 23.81 | 11.83 | 23.81 |
October | 348.67 | 23.83 | 0.00 | 23.83 | 0.00 | 23.83 |
November | 631.33 | 23.86 | 1.00 | 23.86 | 0.00 | 23.86 |
December | 744.00 | 22.43 | 109.00 | 22.15 | 109.00 | 21.94 |
Annual Sum or Average | 6800.17 | 22.72 | 1012.17 | 22.66 | 547.17 | 22.55 |
Minimum of Months | 124.17 | 21.58 | 0.00 | 21.12 | 0.00 | 20.84 |
Maximum of Months | 744.00 | 23.86 | 298.00 | 23.86 | 242.00 | 23.86 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.50 | 20.02 | 675.17 | 19.95 | 675.17 | 19.93 |
February | 642.67 | 20.77 | 472.00 | 20.69 | 463.50 | 20.64 |
March | 707.17 | 21.07 | 407.67 | 21.03 | 396.67 | 20.98 |
April | 650.83 | 21.31 | 131.83 | 21.37 | 102.17 | 21.33 |
May | 620.17 | 21.55 | 82.33 | 21.79 | 5.50 | 21.78 |
June | 548.17 | 21.61 | 121.83 | 21.99 | 0.00 | 21.99 |
July | 458.83 | 21.83 | 208.50 | 22.39 | 0.00 | 22.39 |
August | 507.83 | 21.67 | 179.83 | 22.20 | 0.00 | 22.20 |
September | 598.33 | 21.41 | 96.00 | 21.75 | 0.00 | 21.75 |
October | 676.67 | 21.17 | 126.17 | 21.34 | 73.17 | 21.32 |
November | 697.50 | 21.07 | 411.33 | 21.06 | 406.83 | 21.04 |
December | 744.00 | 20.30 | 689.33 | 20.26 | 689.33 | 20.25 |
Annual Sum or Average | 7594.67 | 21.09 | 3602.00 | 21.11 | 2812.33 | 20.98 |
Minimum of Months | 458.83 | 20.02 | 82.33 | 19.95 | 0.00 | 19.93 |
Maximum of Months | 744.00 | 21.83 | 689.33 | 22.39 | 689.33 | 22.39 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.44 | 464.00 | 20.26 | 464.00 | 20.18 |
February | 672.00 | 21.18 | 203.33 | 21.03 | 203.33 | 20.94 |
March | 744.00 | 21.63 | 80.17 | 21.55 | 80.17 | 21.48 |
April | 709.67 | 22.43 | 2.50 | 22.43 | 0.00 | 22.43 |
May | 570.67 | 22.99 | 56.50 | 23.08 | 0.00 | 23.08 |
June | 454.00 | 23.07 | 208.00 | 23.31 | 76.50 | 23.35 |
July | 264.00 | 23.36 | 391.67 | 23.65 | 119.33 | 23.68 |
August | 292.50 | 23.14 | 313.67 | 23.50 | 77.00 | 23.53 |
September | 546.50 | 22.97 | 61.83 | 23.05 | 19.00 | 23.06 |
October | 711.50 | 22.46 | 0.00 | 22.46 | 0.00 | 22.46 |
November | 720.00 | 21.69 | 32.67 | 21.66 | 32.67 | 21.63 |
December | 744.00 | 20.73 | 417.00 | 20.58 | 417.00 | 20.52 |
Annual Sum or Average | 7172.83 | 21.96 | 2231.33 | 21.96 | 1489.00 | 21.82 |
Minimum of Months | 264.00 | 20.44 | 0.00 | 20.26 | 0.00 | 20.18 |
Maximum of Months | 744.00 | 23.36 | 464.00 | 23.65 | 464.00 | 23.68 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.35 | 705.00 | 20.33 | 705.00 | 20.32 |
February | 672.00 | 20.91 | 554.17 | 20.90 | 554.17 | 20.90 |
March | 744.00 | 21.03 | 407.00 | 21.01 | 407.00 | 21.00 |
April | 720.00 | 21.46 | 58.50 | 21.43 | 58.50 | 21.40 |
May | 708.67 | 22.60 | 4.83 | 22.61 | 0.00 | 22.61 |
June | 550.00 | 22.93 | 73.67 | 23.05 | 0.00 | 23.05 |
July | 316.00 | 23.24 | 150.67 | 23.45 | 0.00 | 23.45 |
August | 533.67 | 23.13 | 37.83 | 23.19 | 0.00 | 23.19 |
September | 691.83 | 22.65 | 3.33 | 22.66 | 0.00 | 22.66 |
October | 744.00 | 21.68 | 0.83 | 21.68 | 0.83 | 21.68 |
November | 720.00 | 21.06 | 257.33 | 21.05 | 257.33 | 21.04 |
December | 744.00 | 20.68 | 654.00 | 20.66 | 654.00 | 20.65 |
Annual Sum or Average | 7888.17 | 21.67 | 2907.17 | 21.49 | 2636.83 | 21.34 |
Minimum of Months | 316.00 | 20.35 | 0.83 | 20.33 | 0.00 | 20.32 |
Maximum of Months | 744.00 | 23.24 | 705.00 | 23.45 | 705.00 | 23.45 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.12 | 721.50 | 20.11 | 721.50 | 20.10 |
February | 672.00 | 20.85 | 590.83 | 20.84 | 590.83 | 20.84 |
March | 744.00 | 20.98 | 469.17 | 20.98 | 469.17 | 20.97 |
April | 720.00 | 21.21 | 109.67 | 21.19 | 109.67 | 21.16 |
May | 736.50 | 22.25 | 3.67 | 22.25 | 3.67 | 22.24 |
June | 625.50 | 22.64 | 45.67 | 22.73 | 0.00 | 22.73 |
July | 532.00 | 23.04 | 23.83 | 23.07 | 0.00 | 23.07 |
August | 705.50 | 22.86 | 0.00 | 22.86 | 0.00 | 22.86 |
September | 716.50 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
October | 744.00 | 21.35 | 13.00 | 21.34 | 13.00 | 21.33 |
November | 720.00 | 21.01 | 344.50 | 21.01 | 344.50 | 21.00 |
December | 744.00 | 20.51 | 703.17 | 20.50 | 703.17 | 20.49 |
Annual Sum or Average | 8404.00 | 21.54 | 3025.00 | 21.31 | 2955.50 | 21.17 |
Minimum of Months | 532.00 | 20.12 | 0.00 | 20.11 | 0.00 | 20.10 |
Maximum of Months | 744.00 | 23.04 | 721.50 | 23.07 | 721.50 | 23.07 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.67 | 19.41 | 377.83 | 19.75 | 211.00 | 19.26 |
February | 309.00 | 21.18 | 364.00 | 21.91 | 149.67 | 21.74 |
March | 263.50 | 22.32 | 458.33 | 23.00 | 150.83 | 23.03 |
April | 231.83 | 23.35 | 575.17 | 23.54 | 166.00 | 23.65 |
May | 281.83 | 23.85 | 667.17 | 23.60 | 258.00 | 23.71 |
June | 300.50 | 23.97 | 692.17 | 23.53 | 298.83 | 23.64 |
July | 345.33 | 23.96 | 734.33 | 23.51 | 345.33 | 23.62 |
August | 327.00 | 23.96 | 729.33 | 23.51 | 325.50 | 23.62 |
September | 288.83 | 24.00 | 672.00 | 23.64 | 278.67 | 23.74 |
October | 256.33 | 23.77 | 636.33 | 23.68 | 210.00 | 23.80 |
November | 233.33 | 23.00 | 481.00 | 23.46 | 142.67 | 23.56 |
December | 403.83 | 20.16 | 376.83 | 20.68 | 197.17 | 20.34 |
Annual Sum or Average | 3678.00 | 22.53 | 6764.50 | 22.90 | 2733.67 | 22.91 |
Minimum of Months | 231.83 | 19.41 | 364.00 | 19.75 | 142.67 | 19.26 |
Maximum of Months | 436.67 | 24.00 | 734.33 | 23.68 | 345.33 | 23.80 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.50 | 20.29 | 520.50 | 20.12 | 520.50 | 20.05 |
February | 625.50 | 21.06 | 324.33 | 20.96 | 299.17 | 20.84 |
March | 683.33 | 21.49 | 174.00 | 21.47 | 140.83 | 21.37 |
April | 599.67 | 22.00 | 71.17 | 22.20 | 2.50 | 22.19 |
May | 446.83 | 22.48 | 179.83 | 22.84 | 7.67 | 22.85 |
June | 380.33 | 22.69 | 343.00 | 23.13 | 107.83 | 23.19 |
July | 315.17 | 23.18 | 554.50 | 23.45 | 203.50 | 23.49 |
August | 337.83 | 22.91 | 502.17 | 23.35 | 170.00 | 23.41 |
September | 417.67 | 22.34 | 214.83 | 22.81 | 29.67 | 22.84 |
October | 608.50 | 21.85 | 85.17 | 22.10 | 1.83 | 22.10 |
November | 685.67 | 21.42 | 135.83 | 21.41 | 119.17 | 21.36 |
December | 741.67 | 20.53 | 540.17 | 20.43 | 540.17 | 20.38 |
Annual Sum or Average | 6580.67 | 21.62 | 3645.50 | 21.82 | 2142.83 | 21.70 |
Minimum of Months | 315.17 | 20.29 | 71.17 | 20.12 | 1.83 | 20.05 |
Maximum of Months | 741.67 | 23.18 | 554.50 | 23.45 | 540.17 | 23.49 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 357.67 | 20.39 | 357.67 | 20.24 |
February | 672.00 | 21.56 | 113.83 | 21.38 | 113.83 | 21.24 |
March | 743.17 | 22.07 | 38.00 | 22.00 | 38.00 | 21.93 |
April | 669.00 | 22.76 | 8.17 | 22.77 | 0.00 | 22.77 |
May | 407.00 | 23.10 | 136.50 | 23.30 | 7.00 | 23.30 |
June | 304.50 | 23.27 | 359.50 | 23.59 | 114.50 | 23.64 |
July | 236.00 | 23.76 | 583.33 | 23.81 | 195.33 | 23.84 |
August | 246.33 | 23.58 | 553.67 | 23.76 | 171.67 | 23.79 |
September | 300.67 | 23.04 | 189.50 | 23.36 | 43.83 | 23.39 |
October | 570.33 | 22.64 | 22.33 | 22.69 | 0.00 | 22.69 |
November | 717.50 | 22.13 | 2.67 | 22.12 | 2.67 | 22.12 |
December | 744.00 | 20.98 | 296.00 | 20.76 | 296.00 | 20.63 |
Annual Sum or Average | 6354.50 | 22.15 | 2661.17 | 22.31 | 1340.50 | 22.22 |
Minimum of Months | 236.00 | 20.67 | 2.67 | 20.39 | 0.00 | 20.24 |
Maximum of Months | 744.00 | 23.76 | 583.33 | 23.81 | 357.67 | 23.84 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.46 | 742.83 | 20.46 | 742.83 | 20.46 |
February | 672.00 | 20.72 | 613.67 | 20.68 | 613.67 | 20.67 |
March | 744.00 | 20.85 | 574.17 | 20.77 | 574.17 | 20.74 |
April | 691.33 | 21.21 | 282.17 | 21.20 | 263.17 | 21.13 |
May | 619.83 | 21.81 | 94.67 | 22.28 | 32.00 | 22.45 |
June | 556.33 | 22.04 | 155.67 | 22.73 | 60.50 | 23.00 |
July | 520.00 | 22.22 | 214.67 | 23.04 | 83.00 | 23.37 |
August | 542.33 | 22.05 | 190.83 | 22.80 | 64.83 | 23.08 |
September | 631.67 | 21.61 | 62.50 | 21.97 | 20.17 | 22.10 |
October | 718.83 | 21.02 | 286.83 | 20.96 | 275.33 | 20.89 |
November | 720.00 | 20.71 | 615.17 | 20.67 | 615.17 | 20.66 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 7904.33 | 21.20 | 4577.17 | 21.25 | 4088.83 | 21.17 |
Minimum of Months | 520.00 | 20.46 | 62.50 | 20.46 | 20.17 | 20.46 |
Maximum of Months | 744.00 | 22.22 | 744.00 | 23.04 | 744.00 | 23.37 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.38 | 744.00 | 20.38 | 744.00 | 20.38 |
February | 672.00 | 20.52 | 659.67 | 20.51 | 659.67 | 20.51 |
March | 744.00 | 20.62 | 662.00 | 20.58 | 662.00 | 20.57 |
April | 699.50 | 21.02 | 371.00 | 20.95 | 361.83 | 20.88 |
May | 638.67 | 21.73 | 91.83 | 22.12 | 33.50 | 22.22 |
June | 578.00 | 22.06 | 141.50 | 22.70 | 59.17 | 22.95 |
July | 541.00 | 22.20 | 187.67 | 22.96 | 77.17 | 23.26 |
August | 579.00 | 22.00 | 149.67 | 22.63 | 54.67 | 22.86 |
September | 666.83 | 21.51 | 47.33 | 21.76 | 10.00 | 21.80 |
October | 740.00 | 20.92 | 342.17 | 20.81 | 340.50 | 20.75 |
November | 720.00 | 20.55 | 668.17 | 20.54 | 668.17 | 20.53 |
December | 744.00 | 20.44 | 744.00 | 20.44 | 744.00 | 20.44 |
Annual Sum or Average | 8067.00 | 21.10 | 4809.00 | 21.10 | 4414.67 | 21.02 |
Minimum of Months | 541.00 | 20.38 | 47.33 | 20.38 | 10.00 | 20.38 |
Maximum of Months | 744.00 | 22.20 | 744.00 | 22.96 | 744.00 | 23.26 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.26 | 744.00 | 20.26 | 744.00 | 20.26 |
February | 672.00 | 20.56 | 664.17 | 20.56 | 664.17 | 20.56 |
March | 744.00 | 20.72 | 629.33 | 20.69 | 629.33 | 20.68 |
April | 720.00 | 21.06 | 227.67 | 21.00 | 227.67 | 20.97 |
May | 740.33 | 21.61 | 3.83 | 21.60 | 3.83 | 21.60 |
June | 696.67 | 21.88 | 20.33 | 21.92 | 18.17 | 21.95 |
July | 712.83 | 21.99 | 34.17 | 22.06 | 29.33 | 22.11 |
August | 741.50 | 21.86 | 11.17 | 21.88 | 11.17 | 21.89 |
September | 720.00 | 21.39 | 2.00 | 21.39 | 2.00 | 21.39 |
October | 744.00 | 21.02 | 121.67 | 20.97 | 121.67 | 20.93 |
November | 720.00 | 20.76 | 580.50 | 20.72 | 580.50 | 20.71 |
December | 744.00 | 20.38 | 732.83 | 20.38 | 732.83 | 20.38 |
Annual Sum or Average | 8699.33 | 21.12 | 3771.67 | 20.95 | 3764.67 | 20.86 |
Minimum of Months | 672.00 | 20.26 | 2.00 | 20.26 | 2.00 | 20.26 |
Maximum of Months | 744.00 | 21.99 | 744.00 | 22.06 | 744.00 | 22.11 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.44 | 743.17 | 20.44 | 743.17 | 20.44 |
February | 672.00 | 20.71 | 603.33 | 20.67 | 603.33 | 20.66 |
March | 744.00 | 20.93 | 553.50 | 20.84 | 553.50 | 20.80 |
April | 713.50 | 21.39 | 238.00 | 21.26 | 238.00 | 21.17 |
May | 623.33 | 21.71 | 50.83 | 21.88 | 9.33 | 21.88 |
June | 489.33 | 21.71 | 165.33 | 22.40 | 35.67 | 22.53 |
July | 459.67 | 21.89 | 260.00 | 22.81 | 56.67 | 23.02 |
August | 488.33 | 21.63 | 181.00 | 22.32 | 30.33 | 22.42 |
September | 633.50 | 21.53 | 22.67 | 21.61 | 5.00 | 21.63 |
October | 730.00 | 21.07 | 276.50 | 20.95 | 276.50 | 20.88 |
November | 720.00 | 20.70 | 616.17 | 20.66 | 616.17 | 20.65 |
December | 744.00 | 20.46 | 740.50 | 20.46 | 740.50 | 20.46 |
Annual Sum or Average | 7761.67 | 21.12 | 4451.00 | 21.13 | 3908.17 | 21.03 |
Minimum of Months | 459.67 | 20.44 | 22.67 | 20.44 | 5.00 | 20.44 |
Maximum of Months | 744.00 | 21.89 | 743.17 | 22.81 | 743.17 | 23.02 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.35 | 744.00 | 20.35 | 744.00 | 20.35 |
February | 672.00 | 20.50 | 663.50 | 20.50 | 663.50 | 20.50 |
March | 744.00 | 20.67 | 641.33 | 20.64 | 641.33 | 20.63 |
April | 719.83 | 21.24 | 306.83 | 21.11 | 306.83 | 21.04 |
May | 653.83 | 21.74 | 35.33 | 21.84 | 13.50 | 21.84 |
June | 503.17 | 21.75 | 139.33 | 22.36 | 35.00 | 22.49 |
July | 465.00 | 21.89 | 205.00 | 22.74 | 56.83 | 22.96 |
August | 518.50 | 21.67 | 110.50 | 22.13 | 24.50 | 22.20 |
September | 697.67 | 21.59 | 6.83 | 21.61 | 5.33 | 21.61 |
October | 744.00 | 20.92 | 348.83 | 20.82 | 348.83 | 20.76 |
November | 720.00 | 20.55 | 657.00 | 20.53 | 657.00 | 20.53 |
December | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
Annual Sum or Average | 7926.00 | 21.04 | 4602.50 | 21.00 | 4240.67 | 20.91 |
Minimum of Months | 465.00 | 20.35 | 6.83 | 20.35 | 5.33 | 20.35 |
Maximum of Months | 744.00 | 21.89 | 744.00 | 22.74 | 744.00 | 22.96 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.55 | 675.83 | 20.53 | 675.83 | 20.52 |
February | 672.00 | 20.91 | 501.50 | 20.90 | 501.50 | 20.89 |
March | 744.00 | 21.02 | 347.00 | 21.00 | 347.00 | 21.00 |
April | 720.00 | 21.47 | 44.50 | 21.44 | 44.50 | 21.42 |
May | 731.33 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
June | 600.83 | 22.91 | 119.67 | 23.03 | 71.50 | 23.06 |
July | 388.67 | 23.32 | 207.33 | 23.45 | 113.17 | 23.46 |
August | 610.00 | 23.03 | 70.17 | 23.06 | 65.67 | 23.07 |
September | 711.00 | 22.32 | 15.67 | 22.33 | 15.67 | 22.33 |
October | 744.00 | 21.35 | 10.00 | 21.35 | 10.00 | 21.34 |
November | 720.00 | 21.01 | 266.00 | 21.01 | 266.00 | 21.01 |
December | 744.00 | 20.73 | 644.17 | 20.71 | 644.17 | 20.70 |
Annual Sum or Average | 8129.83 | 21.66 | 2901.83 | 21.53 | 2755.00 | 21.42 |
Minimum of Months | 388.67 | 20.55 | 0.00 | 20.53 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 23.32 | 675.83 | 23.45 | 675.83 | 23.46 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 744.00 | 20.43 | 744.00 | 20.43 |
February | 672.00 | 20.65 | 631.00 | 20.62 | 631.00 | 20.61 |
March | 744.00 | 20.79 | 609.33 | 20.72 | 609.33 | 20.69 |
April | 692.33 | 21.19 | 383.33 | 21.17 | 367.50 | 21.11 |
May | 616.33 | 21.90 | 121.17 | 22.43 | 54.50 | 22.67 |
June | 559.50 | 22.21 | 177.00 | 22.96 | 82.50 | 23.31 |
July | 531.67 | 22.42 | 241.67 | 23.23 | 105.50 | 23.61 |
August | 554.50 | 22.21 | 218.00 | 23.00 | 91.17 | 23.34 |
September | 630.67 | 21.62 | 83.83 | 22.04 | 37.50 | 22.21 |
October | 716.17 | 20.94 | 381.83 | 20.89 | 368.50 | 20.82 |
November | 720.00 | 20.64 | 645.50 | 20.61 | 645.50 | 20.60 |
December | 744.00 | 20.45 | 744.00 | 20.45 | 744.00 | 20.45 |
Annual Sum or Average | 7925.17 | 21.21 | 4980.67 | 21.27 | 4481.00 | 21.21 |
Minimum of Months | 531.67 | 20.43 | 83.83 | 20.43 | 37.50 | 20.43 |
Maximum of Months | 744.00 | 22.42 | 744.00 | 23.23 | 744.00 | 23.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.34 | 744.00 | 20.34 | 744.00 | 20.34 |
February | 672.00 | 20.49 | 664.00 | 20.49 | 664.00 | 20.49 |
March | 744.00 | 20.58 | 688.67 | 20.55 | 688.67 | 20.54 |
April | 697.00 | 20.94 | 463.83 | 20.90 | 449.33 | 20.84 |
May | 633.83 | 21.80 | 117.50 | 22.26 | 55.50 | 22.42 |
June | 577.33 | 22.20 | 157.67 | 22.90 | 78.67 | 23.23 |
July | 551.67 | 22.37 | 208.33 | 23.14 | 102.00 | 23.51 |
August | 584.17 | 22.12 | 172.83 | 22.80 | 83.00 | 23.10 |
September | 666.67 | 21.50 | 69.83 | 21.78 | 33.67 | 21.86 |
October | 739.50 | 20.83 | 442.17 | 20.72 | 440.00 | 20.67 |
November | 720.00 | 20.51 | 683.33 | 20.50 | 683.33 | 20.49 |
December | 744.00 | 20.41 | 744.00 | 20.41 | 744.00 | 20.41 |
Annual Sum or Average | 8074.17 | 21.10 | 5156.17 | 21.12 | 4766.17 | 21.05 |
Minimum of Months | 551.67 | 20.34 | 69.83 | 20.34 | 33.67 | 20.34 |
Maximum of Months | 744.00 | 22.37 | 744.00 | 23.14 | 744.00 | 23.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.80 | 665.17 | 20.73 | 665.17 | 20.70 |
February | 659.33 | 21.07 | 490.83 | 20.95 | 490.83 | 20.90 |
March | 728.50 | 21.10 | 470.00 | 20.98 | 470.00 | 20.92 |
April | 674.83 | 21.31 | 212.33 | 21.21 | 208.50 | 21.14 |
May | 615.00 | 21.61 | 45.00 | 21.73 | 8.67 | 21.72 |
June | 540.17 | 21.64 | 122.17 | 22.08 | 31.50 | 22.15 |
July | 508.17 | 21.68 | 202.00 | 22.33 | 46.00 | 22.42 |
August | 515.00 | 21.61 | 197.50 | 22.32 | 28.83 | 22.38 |
September | 581.00 | 21.39 | 76.83 | 21.70 | 3.83 | 21.71 |
October | 688.00 | 21.06 | 218.00 | 21.11 | 180.67 | 21.03 |
November | 713.50 | 20.95 | 513.50 | 20.86 | 513.50 | 20.82 |
December | 744.00 | 20.73 | 688.00 | 20.67 | 688.00 | 20.65 |
Annual Sum or Average | 7711.50 | 21.21 | 3901.33 | 21.23 | 3335.50 | 21.14 |
Minimum of Months | 508.17 | 20.73 | 45.00 | 20.67 | 3.83 | 20.65 |
Maximum of Months | 744.00 | 21.68 | 688.00 | 22.33 | 688.00 | 22.42 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.17 | 21.83 | 223.83 | 21.35 | 223.83 | 21.04 |
February | 632.33 | 22.70 | 61.00 | 22.50 | 61.00 | 22.34 |
March | 584.83 | 23.11 | 3.67 | 23.10 | 3.33 | 23.08 |
April | 273.17 | 23.38 | 40.00 | 23.46 | 0.00 | 23.46 |
May | 25.00 | 23.56 | 392.67 | 23.97 | 6.17 | 23.97 |
June | 125.17 | 23.99 | 679.50 | 23.99 | 125.17 | 23.99 |
July | 195.83 | 24.00 | 744.00 | 23.99 | 195.83 | 23.99 |
August | 180.33 | 24.00 | 738.83 | 23.97 | 180.33 | 23.98 |
September | 64.17 | 23.84 | 531.67 | 23.98 | 50.33 | 23.98 |
October | 206.67 | 23.26 | 160.33 | 23.60 | 0.00 | 23.60 |
November | 505.00 | 23.22 | 30.00 | 23.27 | 0.00 | 23.27 |
December | 722.83 | 22.25 | 168.50 | 21.89 | 168.50 | 21.64 |
Annual Sum or Average | 4244.50 | 22.84 | 3774.00 | 23.16 | 1014.50 | 23.05 |
Minimum of Months | 25.00 | 21.83 | 3.67 | 21.35 | 0.00 | 21.04 |
Maximum of Months | 729.17 | 24.00 | 744.00 | 23.99 | 223.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 678.00 | 21.92 | 167.50 | 21.43 | 167.50 | 21.10 |
February | 557.33 | 22.83 | 32.50 | 22.68 | 32.50 | 22.54 |
March | 429.17 | 23.17 | 11.17 | 23.18 | 1.50 | 23.17 |
April | 111.00 | 23.38 | 104.50 | 23.70 | 0.00 | 23.70 |
May | 7.83 | 23.87 | 531.50 | 24.01 | 6.00 | 24.01 |
June | 113.50 | 24.00 | 707.67 | 24.00 | 113.50 | 24.00 |
July | 180.33 | 24.00 | 744.00 | 23.99 | 180.33 | 23.99 |
August | 163.00 | 24.00 | 744.00 | 23.99 | 163.00 | 23.99 |
September | 37.50 | 23.99 | 658.50 | 24.00 | 37.33 | 24.00 |
October | 81.50 | 23.26 | 334.17 | 23.88 | 0.00 | 23.88 |
November | 327.50 | 23.28 | 60.50 | 23.39 | 0.00 | 23.39 |
December | 650.00 | 22.32 | 124.67 | 21.98 | 123.83 | 21.73 |
Annual Sum or Average | 3336.67 | 22.84 | 4220.67 | 23.31 | 825.50 | 23.21 |
Minimum of Months | 7.83 | 21.92 | 11.17 | 21.43 | 0.00 | 21.10 |
Maximum of Months | 678.00 | 24.00 | 744.00 | 24.01 | 180.33 | 24.01 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.83 | 21.61 | 548.00 | 22.11 | 348.00 | 22.04 |
February | 480.17 | 22.96 | 520.00 | 23.22 | 375.17 | 23.24 |
March | 525.50 | 23.62 | 616.50 | 23.74 | 462.17 | 23.77 |
April | 499.33 | 24.09 | 660.67 | 24.04 | 489.67 | 24.07 |
May | 544.00 | 24.09 | 738.00 | 24.04 | 544.00 | 24.06 |
June | 559.33 | 24.01 | 720.00 | 23.99 | 559.33 | 23.99 |
July | 592.50 | 23.99 | 744.00 | 23.98 | 592.50 | 23.98 |
August | 577.17 | 24.00 | 744.00 | 23.98 | 577.17 | 23.99 |
September | 529.33 | 24.11 | 720.00 | 24.05 | 529.33 | 24.07 |
October | 517.83 | 24.23 | 718.50 | 24.14 | 515.00 | 24.17 |
November | 489.17 | 23.89 | 608.67 | 23.94 | 443.83 | 23.97 |
December | 478.67 | 22.24 | 561.33 | 22.65 | 356.33 | 22.62 |
Annual Sum or Average | 6284.83 | 23.60 | 7899.67 | 23.70 | 5792.50 | 23.72 |
Minimum of Months | 478.67 | 21.61 | 520.00 | 22.11 | 348.00 | 22.04 |
Maximum of Months | 592.50 | 24.23 | 744.00 | 24.14 | 592.50 | 24.17 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.33 | 697.50 | 20.31 | 697.50 | 20.30 |
February | 672.00 | 20.86 | 498.00 | 20.84 | 498.00 | 20.82 |
March | 744.00 | 21.05 | 353.67 | 21.01 | 353.67 | 21.00 |
April | 720.00 | 21.45 | 36.17 | 21.42 | 36.17 | 21.40 |
May | 658.50 | 22.41 | 35.50 | 22.48 | 0.00 | 22.48 |
June | 502.33 | 22.70 | 121.33 | 22.93 | 0.00 | 22.93 |
July | 266.00 | 22.88 | 252.17 | 23.34 | 0.00 | 23.34 |
August | 487.33 | 22.73 | 103.50 | 22.92 | 0.00 | 22.92 |
September | 697.83 | 22.18 | 8.83 | 22.20 | 0.00 | 22.20 |
October | 744.00 | 21.38 | 16.33 | 21.37 | 16.33 | 21.36 |
November | 720.00 | 21.02 | 286.17 | 21.02 | 286.17 | 21.01 |
December | 744.00 | 20.61 | 665.67 | 20.59 | 665.67 | 20.58 |
Annual Sum or Average | 7700.00 | 21.48 | 3074.83 | 21.40 | 2553.50 | 21.25 |
Minimum of Months | 266.00 | 20.33 | 8.83 | 20.31 | 0.00 | 20.30 |
Maximum of Months | 744.00 | 22.88 | 697.50 | 23.34 | 697.50 | 23.34 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57615 | 14.70841 | -0.4057 | 11.48079 |
February | 672.00000 | 22.39816 | 17.27257 | -0.2035 | 6.60646 |
March | 744.00000 | 22.36388 | 21.76460 | -0.1935 | 6.12053 |
April | 720.00000 | 22.48729 | 25.95469 | -0.1401 | 5.60675 |
May | 744.00000 | 22.70069 | 36.96664 | -1.0541 | 28.73566 |
June | 720.00000 | 22.91458 | 50.78965 | -0.8840 | 21.82145 |
July | 744.00000 | 23.37907 | 56.13843 | -0.6749 | 14.83832 |
August | 744.00000 | 23.75488 | 53.87367 | -0.5468 | 11.42124 |
September | 720.00000 | 23.87204 | 42.13052 | -0.5805 | 12.24392 |
October | 744.00000 | 23.91310 | 31.45547 | 0.27352 | 6.62333 |
November | 720.00000 | 23.87022 | 23.77434 | 0.20624 | 5.99360 |
December | 744.00000 | 22.42990 | 15.99666 | -0.1895 | 7.62254 |
Annual Sum or Average | 8760.00000 | 22.97293 | 32.66063 | -0.3676 | 11.63580 |
Minimum of Months | 672.00000 | 21.57615 | 14.70841 | -1.0541 | 5.60675 |
Maximum of Months | 744.00000 | 23.91310 | 56.13843 | 0.27352 | 28.73566 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.02569 | 13.71048 | -0.9103 | 25.48346 |
February | 672.00000 | 20.90786 | 16.42989 | -0.6225 | 16.23785 |
March | 744.00000 | 21.21216 | 21.06846 | -0.4883 | 12.00838 |
April | 720.00000 | 21.55240 | 25.46041 | -0.3044 | 8.90869 |
May | 744.00000 | 21.89326 | 36.75583 | -1.1425 | 35.51070 |
June | 720.00000 | 22.05379 | 51.85166 | -0.9736 | 28.27697 |
July | 744.00000 | 22.43215 | 57.90134 | -0.7729 | 20.61125 |
August | 744.00000 | 22.24912 | 57.28985 | -0.8531 | 23.95426 |
September | 720.00000 | 21.80480 | 45.94131 | -1.1276 | 35.22383 |
October | 744.00000 | 21.41912 | 34.33936 | -0.2966 | 8.90275 |
November | 720.00000 | 21.16099 | 25.53265 | -0.5090 | 11.47836 |
December | 744.00000 | 20.29840 | 15.52059 | -0.8563 | 22.80301 |
Annual Sum or Average | 8760.00000 | 21.41920 | 33.58296 | -0.7392 | 20.81858 |
Minimum of Months | 672.00000 | 20.02569 | 13.71048 | -1.1425 | 8.90275 |
Maximum of Months | 744.00000 | 22.43215 | 57.90134 | -0.2966 | 35.51070 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43711 | 16.13596 | -0.6954 | 17.24280 |
February | 672.00000 | 21.17824 | 18.87089 | -0.4860 | 10.79269 |
March | 744.00000 | 21.63105 | 23.19212 | -0.3399 | 8.12997 |
April | 720.00000 | 22.44842 | 26.85626 | -0.1066 | 5.97529 |
May | 744.00000 | 23.17977 | 36.88493 | -0.8226 | 20.25655 |
June | 720.00000 | 23.31032 | 50.74206 | -0.6779 | 15.55580 |
July | 744.00000 | 23.55291 | 56.68680 | -0.5418 | 11.58670 |
August | 744.00000 | 23.45844 | 55.93693 | -0.5874 | 12.78628 |
September | 720.00000 | 23.15481 | 45.11861 | -0.7810 | 18.60341 |
October | 744.00000 | 22.52101 | 34.96817 | -0.0387 | 5.83022 |
November | 720.00000 | 21.69226 | 27.31905 | -0.3031 | 7.45727 |
December | 744.00000 | 20.72516 | 17.94906 | -0.6167 | 14.17765 |
Annual Sum or Average | 8760.00000 | 22.27900 | 34.31188 | -0.5002 | 12.38428 |
Minimum of Months | 672.00000 | 20.43711 | 16.13596 | -0.8226 | 5.83022 |
Maximum of Months | 744.00000 | 23.55291 | 56.68680 | -0.0387 | 20.25655 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.93542 | 11.09046 | -0.0095 | 19.98180 |
February | 672.00000 | 22.24409 | 13.48549 | 0.32234 | 15.28148 |
March | 744.00000 | 22.87293 | 17.56918 | 0.51545 | 14.91358 |
April | 720.00000 | 23.24589 | 21.46253 | 0.66504 | 16.79201 |
May | 744.00000 | 23.31364 | 32.22177 | 0.10340 | 9.85998 |
June | 720.00000 | 23.27529 | 46.30702 | 0.20587 | 10.29829 |
July | 744.00000 | 23.27453 | 52.94413 | 0.26066 | 10.65884 |
August | 744.00000 | 23.27061 | 51.92778 | 0.24072 | 10.58029 |
September | 720.00000 | 23.34560 | 40.09697 | 0.15352 | 10.00535 |
October | 744.00000 | 23.35349 | 29.15059 | 0.73951 | 19.03068 |
November | 720.00000 | 23.12478 | 21.30470 | 0.59729 | 15.15089 |
December | 744.00000 | 21.49629 | 12.64176 | 0.12992 | 16.90195 |
Annual Sum or Average | 8760.00000 | 22.81262 | 29.27848 | 0.32620 | 14.12334 |
Minimum of Months | 672.00000 | 20.93542 | 11.09046 | -0.0095 | 9.85998 |
Maximum of Months | 744.00000 | 23.35349 | 52.94413 | 0.73951 | 19.98180 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.31742 | 18.51376 | -0.7417 | 19.72943 |
February | 672.00000 | 21.24987 | 21.27991 | -0.4394 | 12.18306 |
March | 744.00000 | 21.67843 | 25.76460 | -0.2817 | 8.90904 |
April | 720.00000 | 22.29656 | 29.75339 | -0.0501 | 6.97600 |
May | 744.00000 | 22.90590 | 40.13485 | -0.7378 | 18.85834 |
June | 720.00000 | 23.04632 | 54.20190 | -0.5770 | 14.08350 |
July | 744.00000 | 23.31449 | 60.14650 | -0.4127 | 10.06496 |
August | 744.00000 | 23.23130 | 59.35835 | -0.4574 | 11.58516 |
September | 720.00000 | 22.86616 | 48.45728 | -0.7016 | 18.16777 |
October | 744.00000 | 22.20405 | 38.04119 | -0.0326 | 7.31248 |
November | 720.00000 | 21.53453 | 30.13696 | -0.3213 | 8.53534 |
December | 744.00000 | 20.54114 | 20.42377 | -0.6980 | 17.35229 |
Annual Sum or Average | 8760.00000 | 22.10213 | 37.27725 | -0.4548 | 12.82786 |
Minimum of Months | 672.00000 | 20.31742 | 18.51376 | -0.7417 | 6.97600 |
Maximum of Months | 744.00000 | 23.31449 | 60.14650 | -0.0326 | 19.72943 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67182 | 18.77454 | -0.6144 | 15.20603 |
February | 672.00000 | 21.56427 | 21.50472 | -0.3652 | 8.94112 |
March | 744.00000 | 22.06765 | 25.76661 | -0.2084 | 6.84013 |
April | 720.00000 | 22.83705 | 29.39961 | 0.02051 | 5.72629 |
May | 744.00000 | 23.41873 | 39.36575 | -0.6870 | 15.75747 |
June | 720.00000 | 23.51766 | 52.94726 | -0.5476 | 12.01206 |
July | 744.00000 | 23.67034 | 58.92610 | -0.4377 | 9.36230 |
August | 744.00000 | 23.63615 | 58.06877 | -0.4636 | 9.97387 |
September | 720.00000 | 23.47181 | 47.26110 | -0.6182 | 13.76912 |
October | 744.00000 | 22.92477 | 37.24797 | 0.09263 | 6.14936 |
November | 720.00000 | 22.13326 | 29.76465 | -0.1736 | 6.43270 |
December | 744.00000 | 20.98499 | 20.60257 | -0.5328 | 12.34733 |
Annual Sum or Average | 8760.00000 | 22.57863 | 36.72502 | -0.3786 | 10.22819 |
Minimum of Months | 672.00000 | 20.67182 | 18.77454 | -0.6870 | 5.72629 |
Maximum of Months | 744.00000 | 23.67034 | 58.92610 | 0.09263 | 15.75747 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.46463 | 17.67676 | -0.8921 | 22.32788 |
February | 672.00000 | 20.72298 | 19.66296 | -0.7567 | 17.92492 |
March | 744.00000 | 20.85425 | 23.93622 | -0.6465 | 14.84088 |
April | 720.00000 | 21.36888 | 28.88137 | -0.4070 | 10.49575 |
May | 744.00000 | 22.20598 | 39.45967 | -1.0988 | 36.00736 |
June | 720.00000 | 22.50645 | 50.47737 | -0.8975 | 28.63862 |
July | 744.00000 | 22.70009 | 53.20804 | -0.7710 | 24.58951 |
August | 744.00000 | 22.55462 | 54.16898 | -0.8585 | 27.17064 |
September | 720.00000 | 21.92913 | 48.91900 | -1.1898 | 39.08414 |
October | 744.00000 | 21.13225 | 38.88470 | -0.4367 | 10.51635 |
November | 720.00000 | 20.71357 | 28.68325 | -0.6888 | 15.66815 |
December | 744.00000 | 20.47316 | 19.25419 | -0.8844 | 22.02534 |
Annual Sum or Average | 8760.00000 | 21.47320 | 35.35243 | -0.7943 | 22.46662 |
Minimum of Months | 672.00000 | 20.46463 | 17.67676 | -1.1898 | 10.49575 |
Maximum of Months | 744.00000 | 22.70009 | 54.16898 | -0.4070 | 39.08414 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.37614 | 17.73876 | -0.9483 | 24.66642 |
February | 672.00000 | 20.52155 | 19.89923 | -0.8442 | 20.64367 |
March | 744.00000 | 20.62103 | 24.22462 | -0.7358 | 17.20070 |
April | 720.00000 | 21.12633 | 29.12114 | -0.4915 | 11.53856 |
May | 744.00000 | 22.10923 | 39.71161 | -1.1536 | 37.70439 |
June | 720.00000 | 22.47704 | 50.67439 | -0.9194 | 29.11627 |
July | 744.00000 | 22.66742 | 53.76326 | -0.7982 | 25.10630 |
August | 744.00000 | 22.45804 | 55.20521 | -0.9144 | 28.34353 |
September | 720.00000 | 21.75229 | 49.59916 | -1.2819 | 42.17416 |
October | 744.00000 | 20.93556 | 39.30687 | -0.5083 | 11.29846 |
November | 720.00000 | 20.55327 | 28.92603 | -0.7478 | 17.37520 |
December | 744.00000 | 20.43629 | 19.28478 | -0.9209 | 23.53176 |
Annual Sum or Average | 8760.00000 | 21.34133 | 35.70709 | -0.8554 | 24.07547 |
Minimum of Months | 672.00000 | 20.37614 | 17.73876 | -1.2819 | 11.29846 |
Maximum of Months | 744.00000 | 22.66742 | 55.20521 | -0.4915 | 42.17416 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.26134 | 16.28869 | -0.8633 | 21.69463 |
February | 672.00000 | 20.56315 | 18.58945 | -0.7582 | 17.66353 |
March | 744.00000 | 20.72414 | 22.96381 | -0.6713 | 14.91082 |
April | 720.00000 | 21.05874 | 28.10319 | -0.5128 | 10.76249 |
May | 744.00000 | 21.61583 | 39.22353 | -1.3939 | 45.82649 |
June | 720.00000 | 21.94076 | 50.63070 | -1.1861 | 35.79020 |
July | 744.00000 | 22.07644 | 55.21327 | -1.1038 | 32.07189 |
August | 744.00000 | 21.86225 | 55.80822 | -1.1969 | 35.99272 |
September | 720.00000 | 21.38881 | 48.62465 | -1.4386 | 47.80957 |
October | 744.00000 | 21.02232 | 38.09907 | -0.4648 | 9.67867 |
November | 720.00000 | 20.75631 | 27.49276 | -0.6333 | 13.87837 |
December | 744.00000 | 20.38409 | 17.89741 | -0.8202 | 19.97694 |
Annual Sum or Average | 8760.00000 | 21.14095 | 35.00372 | -0.9214 | 25.55209 |
Minimum of Months | 672.00000 | 20.26134 | 16.28869 | -1.4386 | 9.67867 |
Maximum of Months | 744.00000 | 22.07644 | 55.80822 | -0.4648 | 47.80957 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43608 | 17.66040 | -0.8972 | 22.56691 |
February | 672.00000 | 20.70868 | 19.65580 | -0.7596 | 17.90924 |
March | 744.00000 | 20.93308 | 23.82879 | -0.6292 | 14.44178 |
April | 720.00000 | 21.41009 | 28.75708 | -0.3909 | 9.73629 |
May | 744.00000 | 22.05704 | 39.37955 | -1.1498 | 35.71087 |
June | 720.00000 | 22.42100 | 50.19303 | -0.9088 | 26.99043 |
July | 744.00000 | 22.64105 | 53.14253 | -0.7876 | 23.59140 |
August | 744.00000 | 22.38631 | 54.65979 | -0.9131 | 26.51526 |
September | 720.00000 | 21.77978 | 49.22182 | -1.2361 | 39.16774 |
October | 744.00000 | 21.11702 | 38.87800 | -0.4442 | 10.40106 |
November | 720.00000 | 20.69639 | 28.69096 | -0.6915 | 15.73279 |
December | 744.00000 | 20.46386 | 19.23916 | -0.8850 | 22.09311 |
Annual Sum or Average | 8760.00000 | 21.42501 | 35.36078 | -0.8082 | 22.09646 |
Minimum of Months | 672.00000 | 20.43608 | 17.66040 | -1.2361 | 9.73629 |
Maximum of Months | 744.00000 | 22.64105 | 54.65979 | -0.3909 | 39.16774 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.34938 | 17.71074 | -0.9544 | 24.97667 |
February | 672.00000 | 20.50197 | 19.88400 | -0.8492 | 20.79688 |
March | 744.00000 | 20.67484 | 24.10775 | -0.7245 | 16.75596 |
April | 720.00000 | 21.24094 | 28.94433 | -0.4602 | 10.57191 |
May | 744.00000 | 21.99750 | 39.56851 | -1.1939 | 37.39654 |
June | 720.00000 | 22.40706 | 50.38611 | -0.9261 | 27.46910 |
July | 744.00000 | 22.61568 | 53.70157 | -0.8125 | 24.18966 |
August | 744.00000 | 22.31032 | 55.53558 | -0.9632 | 27.84691 |
September | 720.00000 | 21.65342 | 49.72499 | -1.3139 | 42.27233 |
October | 744.00000 | 20.92288 | 39.27575 | -0.5159 | 11.26727 |
November | 720.00000 | 20.54923 | 28.91771 | -0.7484 | 17.44714 |
December | 744.00000 | 20.42337 | 19.26641 | -0.9231 | 23.66742 |
Annual Sum or Average | 8760.00000 | 21.30873 | 35.67151 | -0.8656 | 23.73764 |
Minimum of Months | 672.00000 | 20.34938 | 17.71074 | -1.3139 | 10.57191 |
Maximum of Months | 744.00000 | 22.61568 | 55.53558 | -0.4602 | 42.27233 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43007 | 17.78994 | -0.9549 | 24.79625 |
February | 672.00000 | 20.65134 | 19.87141 | -0.8215 | 20.12910 |
March | 744.00000 | 20.78789 | 24.22614 | -0.6997 | 16.50283 |
April | 720.00000 | 21.32625 | 29.22795 | -0.4386 | 11.62393 |
May | 744.00000 | 22.25675 | 39.62010 | -1.0861 | 37.25611 |
June | 720.00000 | 22.57420 | 50.89840 | -0.8693 | 29.65440 |
July | 744.00000 | 22.75114 | 53.72550 | -0.7453 | 25.50064 |
August | 744.00000 | 22.61510 | 54.79295 | -0.8351 | 28.21675 |
September | 720.00000 | 21.93642 | 49.59532 | -1.2046 | 40.95156 |
October | 744.00000 | 21.06663 | 39.36353 | -0.4792 | 11.71333 |
November | 720.00000 | 20.64276 | 29.08462 | -0.7461 | 17.44141 |
December | 744.00000 | 20.45280 | 19.38504 | -0.9442 | 24.35445 |
Annual Sum or Average | 8760.00000 | 21.46246 | 35.71668 | -0.8187 | 24.03371 |
Minimum of Months | 672.00000 | 20.43007 | 17.78994 | -1.2046 | 11.62393 |
Maximum of Months | 744.00000 | 22.75114 | 54.79295 | -0.4386 | 40.95156 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.34081 | 17.85167 | -1.0121 | 27.32863 |
February | 672.00000 | 20.49101 | 20.06649 | -0.9033 | 22.84447 |
March | 744.00000 | 20.58193 | 24.49851 | -0.7866 | 18.91417 |
April | 720.00000 | 21.07839 | 29.50150 | -0.5276 | 12.73290 |
May | 744.00000 | 22.16013 | 39.87502 | -1.1435 | 38.80598 |
June | 720.00000 | 22.54507 | 51.07597 | -0.8924 | 30.05350 |
July | 744.00000 | 22.71731 | 54.25455 | -0.7743 | 25.97497 |
August | 744.00000 | 22.50921 | 55.96080 | -0.8956 | 29.26397 |
September | 720.00000 | 21.73475 | 50.37152 | -1.3089 | 44.22487 |
October | 744.00000 | 20.84887 | 39.83098 | -0.5587 | 12.60448 |
November | 720.00000 | 20.50930 | 29.30351 | -0.8016 | 19.18543 |
December | 744.00000 | 20.41266 | 19.41775 | -0.9816 | 25.99057 |
Annual Sum or Average | 8760.00000 | 21.33280 | 36.08713 | -0.8820 | 25.67373 |
Minimum of Months | 672.00000 | 20.34081 | 17.85167 | -1.3089 | 12.60448 |
Maximum of Months | 744.00000 | 22.71731 | 55.96080 | -0.5276 | 44.22487 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80472 | 19.24877 | -0.7529 | 18.25165 |
February | 672.00000 | 21.11362 | 21.11188 | -0.6051 | 14.56283 |
March | 744.00000 | 21.15008 | 25.26174 | -0.5384 | 12.76009 |
April | 720.00000 | 21.46088 | 30.22788 | -0.3706 | 9.69201 |
May | 744.00000 | 21.99815 | 40.56983 | -1.1945 | 37.68321 |
June | 720.00000 | 22.19750 | 51.57885 | -1.0341 | 30.70585 |
July | 744.00000 | 22.35821 | 54.74091 | -0.9234 | 26.40644 |
August | 744.00000 | 22.33738 | 54.82563 | -0.9463 | 27.91060 |
September | 720.00000 | 21.86722 | 49.33066 | -1.1983 | 38.23860 |
October | 744.00000 | 21.27603 | 40.09930 | -0.3713 | 9.83922 |
November | 720.00000 | 20.97020 | 29.79604 | -0.5890 | 13.58584 |
December | 744.00000 | 20.72920 | 20.79113 | -0.7771 | 18.80818 |
Annual Sum or Average | 8760.00000 | 21.52417 | 36.55011 | -0.7762 | 21.57772 |
Minimum of Months | 672.00000 | 20.72920 | 19.24877 | -1.1983 | 9.69201 |
Maximum of Months | 744.00000 | 22.35821 | 54.82563 | -0.3706 | 38.23860 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.87544 | 21.07736 | -0.3319 | 11.37253 |
February | 672.00000 | 22.77787 | 23.56086 | -0.0827 | 6.95642 |
March | 744.00000 | 23.29998 | 27.09146 | 0.09360 | 6.21528 |
April | 720.00000 | 23.75195 | 29.84961 | 0.26990 | 6.87570 |
May | 744.00000 | 23.95179 | 38.99934 | -0.4144 | 8.93220 |
June | 720.00000 | 23.98026 | 52.02723 | -0.2760 | 6.79833 |
July | 744.00000 | 23.98532 | 58.25331 | -0.2142 | 6.03871 |
August | 744.00000 | 23.96323 | 57.54145 | -0.2543 | 6.46943 |
September | 720.00000 | 23.91855 | 46.90967 | -0.3992 | 8.61512 |
October | 744.00000 | 23.77168 | 37.28878 | 0.32399 | 7.51491 |
November | 720.00000 | 23.44588 | 30.50146 | 0.15412 | 6.24475 |
December | 744.00000 | 22.29936 | 22.71154 | -0.2170 | 8.86517 |
Annual Sum or Average | 8760.00000 | 23.41981 | 37.23344 | -0.1131 | 7.58480 |
Minimum of Months | 672.00000 | 21.87544 | 21.07736 | -0.4144 | 6.03871 |
Maximum of Months | 744.00000 | 23.98532 | 58.25331 | 0.32399 | 11.37253 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.10358 | 20.36409 | -0.2382 | 10.47817 |
February | 672.00000 | 23.02448 | 22.71306 | 0.01583 | 6.80364 |
March | 744.00000 | 23.51444 | 26.06706 | 0.18520 | 6.55336 |
April | 720.00000 | 23.88347 | 28.86409 | 0.34080 | 7.64418 |
May | 744.00000 | 23.99197 | 38.29572 | -0.3512 | 7.83599 |
June | 720.00000 | 23.99755 | 51.41895 | -0.2244 | 6.22989 |
July | 744.00000 | 23.99437 | 57.72463 | -0.1696 | 5.67418 |
August | 744.00000 | 23.98884 | 56.91377 | -0.2013 | 5.93403 |
September | 720.00000 | 23.97976 | 46.09086 | -0.3266 | 7.42321 |
October | 744.00000 | 23.89235 | 36.25300 | 0.39314 | 8.43473 |
November | 720.00000 | 23.65839 | 29.41477 | 0.24661 | 6.79285 |
December | 744.00000 | 22.52968 | 21.91568 | -0.1216 | 8.29004 |
Annual Sum or Average | 8760.00000 | 23.54721 | 36.41967 | -0.0386 | 7.34910 |
Minimum of Months | 672.00000 | 22.10358 | 20.36409 | -0.3512 | 5.67418 |
Maximum of Months | 744.00000 | 23.99755 | 57.72463 | 0.39314 | 10.47817 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.23745 | 20.65815 | 0.40997 | 21.72064 |
February | 672.00000 | 23.12679 | 21.55777 | 0.66708 | 22.20116 |
March | 744.00000 | 23.59364 | 24.64612 | 0.84341 | 24.42272 |
April | 720.00000 | 23.90773 | 27.99720 | 1.01289 | 29.15464 |
May | 744.00000 | 23.99335 | 37.78870 | 0.62432 | 18.14237 |
June | 720.00000 | 23.96801 | 50.64850 | 0.75226 | 21.07528 |
July | 744.00000 | 23.96423 | 56.84345 | 0.81255 | 22.91533 |
August | 744.00000 | 23.96370 | 55.92390 | 0.76459 | 21.31438 |
September | 720.00000 | 24.00259 | 45.30085 | 0.63617 | 17.95189 |
October | 744.00000 | 24.02069 | 35.43745 | 1.06886 | 31.34159 |
November | 720.00000 | 23.77088 | 28.05532 | 0.89488 | 24.59231 |
December | 744.00000 | 22.65725 | 21.66932 | 0.51864 | 20.85867 |
Annual Sum or Average | 8760.00000 | 23.60100 | 35.63193 | 0.75035 | 22.97820 |
Minimum of Months | 672.00000 | 22.23745 | 20.65815 | 0.40997 | 17.95189 |
Maximum of Months | 744.00000 | 24.02069 | 56.84345 | 1.06886 | 31.34159 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.11929 | 13.04571 | -0.8593 | 22.45510 |
February | 672.00000 | 20.84845 | 15.70478 | -0.6589 | 14.48143 |
March | 744.00000 | 20.98263 | 20.40688 | -0.5761 | 12.08900 |
April | 720.00000 | 21.21338 | 24.90645 | -0.4527 | 9.54738 |
May | 744.00000 | 22.26761 | 35.06057 | -1.1923 | 35.83737 |
June | 720.00000 | 22.78046 | 49.09277 | -0.9244 | 23.98218 |
July | 744.00000 | 23.18155 | 55.08937 | -0.7433 | 16.97545 |
August | 744.00000 | 22.89645 | 54.62241 | -0.8488 | 20.56770 |
September | 720.00000 | 22.24087 | 43.92695 | -1.1466 | 33.19608 |
October | 744.00000 | 21.34636 | 33.66348 | -0.3618 | 8.07571 |
November | 720.00000 | 21.00769 | 24.73963 | -0.5330 | 11.05799 |
December | 744.00000 | 20.51262 | 14.73626 | -0.7563 | 18.06662 |
Annual Sum or Average | 8760.00000 | 21.62063 | 32.17828 | -0.7551 | 18.89059 |
Minimum of Months | 672.00000 | 20.11929 | 13.04571 | -1.1923 | 8.07571 |
Maximum of Months | 744.00000 | 23.18155 | 55.08937 | -0.3618 | 35.83737 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54773 | 16.15086 | -0.7163 | 16.66268 |
February | 672.00000 | 20.91225 | 19.04026 | -0.5996 | 12.73311 |
March | 744.00000 | 21.02342 | 23.75988 | -0.5325 | 11.04515 |
April | 720.00000 | 21.46895 | 27.92185 | -0.3817 | 8.44384 |
May | 744.00000 | 22.56507 | 37.81575 | -1.0961 | 31.28328 |
June | 720.00000 | 23.04511 | 51.37689 | -0.8390 | 20.72000 |
July | 744.00000 | 23.49983 | 56.95139 | -0.6387 | 13.79322 |
August | 744.00000 | 23.13543 | 56.91672 | -0.7714 | 17.99274 |
September | 720.00000 | 22.33617 | 46.96347 | -1.1202 | 32.26863 |
October | 744.00000 | 21.35293 | 36.93124 | -0.3600 | 8.06482 |
November | 720.00000 | 21.00964 | 28.09049 | -0.5189 | 10.71448 |
December | 744.00000 | 20.73015 | 17.96642 | -0.6669 | 14.81697 |
Annual Sum or Average | 8760.00000 | 21.80775 | 35.08210 | -0.6872 | 16.55989 |
Minimum of Months | 672.00000 | 20.54773 | 16.15086 | -1.1202 | 8.06482 |
Maximum of Months | 744.00000 | 23.49983 | 56.95139 | -0.3600 | 32.26863 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.33253 | 14.18008 | -0.8054 | 20.43657 |
February | 672.00000 | 20.86468 | 17.03627 | -0.6345 | 13.95237 |
March | 744.00000 | 21.04602 | 21.70960 | -0.5344 | 11.23617 |
April | 720.00000 | 21.44562 | 25.92838 | -0.3730 | 8.40823 |
May | 744.00000 | 22.55249 | 35.67012 | -1.0528 | 29.89968 |
June | 720.00000 | 22.99799 | 49.33323 | -0.8008 | 19.78384 |
July | 744.00000 | 23.37319 | 55.10299 | -0.6250 | 13.88639 |
August | 744.00000 | 23.03141 | 55.03910 | -0.7541 | 17.85801 |
September | 720.00000 | 22.22245 | 45.08490 | -1.1146 | 32.13677 |
October | 744.00000 | 21.37534 | 34.83258 | -0.3391 | 7.89997 |
November | 720.00000 | 21.02173 | 26.09209 | -0.5178 | 10.74021 |
December | 744.00000 | 20.61019 | 15.96927 | -0.7299 | 17.21586 |
Annual Sum or Average | 8760.00000 | 21.74466 | 33.08983 | -0.6905 | 16.97027 |
Minimum of Months | 672.00000 | 20.33253 | 14.18008 | -1.1146 | 7.89997 |
Maximum of Months | 744.00000 | 23.37319 | 55.10299 | -0.3391 | 32.13677 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.34837 | 12.72365 | -0.7919 | 19.69286 |
February | 672.00000 | 20.91350 | 15.39020 | -0.6255 | 13.44293 |
March | 744.00000 | 21.02561 | 20.05584 | -0.5505 | 11.47632 |
April | 720.00000 | 21.46222 | 24.28193 | -0.3941 | 8.63210 |
May | 744.00000 | 22.65420 | 34.06137 | -1.0776 | 30.63901 |
June | 720.00000 | 23.12531 | 47.93766 | -0.8228 | 20.13876 |
July | 744.00000 | 23.51947 | 53.86679 | -0.6430 | 13.99098 |
August | 744.00000 | 23.28437 | 53.22728 | -0.7332 | 16.69254 |
September | 720.00000 | 22.69287 | 42.57680 | -1.0107 | 27.15230 |
October | 744.00000 | 21.67853 | 32.74823 | -0.2863 | 7.19391 |
November | 720.00000 | 21.06386 | 24.33922 | -0.5056 | 10.49319 |
December | 744.00000 | 20.68278 | 14.42293 | -0.7003 | 15.97703 |
Annual Sum or Average | 8760.00000 | 21.87644 | 31.39529 | -0.6788 | 16.31352 |
Minimum of Months | 672.00000 | 20.34837 | 12.72365 | -1.0776 | 7.19391 |
Maximum of Months | 744.00000 | 23.51947 | 53.86679 | -0.2863 | 30.63901 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.299038E+09 | 6794.53 | 29-JAN-09:05 | 40.83 | 0.931783E+09 | 0.00 | 0.123082E+10 | 0.17 | 3.12 | 01-JAN-10:50 | 0.00 | 0.00 |
February | 0.127103E+10 | 15983.89 | 22-FEB-16:02 | 128.41 | 0.396043E+10 | 0.00 | 0.523146E+10 | 0.60 | 3.12 | 01-FEB-12:20 | 0.00 | 0.00 |
March | 0.251996E+10 | 26535.96 | 31-MAR-15:03 | 205.05 | 0.785203E+10 | 0.00 | 0.103720E+11 | 0.86 | 3.12 | 01-MAR-06:20 | 0.00 | 0.00 |
April | 0.151745E+11 | 111338.58 | 23-APR-18:03 | 437.71 | 0.456025E+11 | 0.00 | 0.607770E+11 | 1.88 | 3.51 | 23-APR-18:03 | 0.00 | 0.00 |
May | 0.683341E+11 | 150163.04 | 25-MAY-18:03 | 697.04 | 0.202486E+12 | 0.00 | 0.270820E+12 | 2.83 | 3.81 | 26-MAY-08:53 | 0.00 | 0.00 |
June | 0.134341E+12 | 216675.81 | 29-JUN-18:03 | 706.99 | 0.428027E+12 | 0.00 | 0.562367E+12 | 3.04 | 4.29 | 19-JUN-21:52 | 0.00 | 0.00 |
July | 0.176700E+12 | 184800.32 | 15-JUL-15:03 | 737.61 | 0.585516E+12 | 0.00 | 0.762216E+12 | 3.16 | 4.31 | 25-JUL-21:53 | 0.00 | 0.00 |
August | 0.130893E+12 | 180878.67 | 08-AUG-15:03 | 734.51 | 0.418676E+12 | 0.00 | 0.549569E+12 | 3.06 | 4.25 | 09-AUG-21:52 | 0.00 | 0.00 |
September | 0.442462E+11 | 128401.38 | 01-SEP-15:03 | 642.94 | 0.131620E+12 | 0.00 | 0.175866E+12 | 2.71 | 4.02 | 01-SEP-08:52 | 0.00 | 0.00 |
October | 0.114166E+11 | 84519.03 | 19-OCT-15:03 | 395.46 | 0.341155E+11 | 0.00 | 0.455322E+11 | 1.64 | 3.40 | 22-OCT-15:02 | 0.00 | 0.00 |
November | 0.180723E+10 | 30792.69 | 01-NOV-15:07 | 181.11 | 0.552025E+10 | 0.00 | 0.732748E+10 | 0.78 | 3.12 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 0.212129E+09 | 4743.05 | 04-DEC-19:07 | 35.18 | 0.660980E+09 | 0.00 | 0.873110E+09 | 0.15 | 3.12 | 01-DEC-10:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587215E+12 | 4942.85 | 0.186497E+13 | 0.00 | 0.245218E+13 | 1.74 | 0.00 | 0.00 | ||||
Minimum of Months | 0.212129E+09 | 4743.05 | 35.18 | 0.660980E+09 | 0.00 | 0.873110E+09 | 0.15 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.176700E+12 | 216675.81 | 737.61 | 0.585516E+12 | 0.00 | 0.762216E+12 | 3.16 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.767830E+12 | 0.00 | 744.00 | 735116.28 | 06-JAN-05:00 | 0.00 | 37.37 | 60.02 | 2.94 | 0.00 | 0.37 | 0.95 | 06-JAN-05:00 |
February | 0.416892E+12 | 0.00 | 672.00 | 713166.86 | 17-FEB-06:00 | 0.00 | 38.90 | 60.01 | 1.83 | 0.00 | 0.22 | 0.92 | 17-FEB-06:00 |
March | 0.243806E+12 | 0.00 | 743.65 | 687592.78 | 05-MAR-06:50 | 0.00 | 40.07 | 60.00 | 1.02 | 0.00 | 0.12 | 0.89 | 05-MAR-06:50 |
April | 0.518173E+11 | 0.00 | 635.26 | 182186.16 | 02-APR-08:61 | 0.00 | 41.44 | 57.07 | 0.28 | 0.00 | 0.03 | 0.24 | 02-APR-08:61 |
May | 0.155031E+11 | 0.00 | 354.33 | 151870.70 | 11-MAY-22:55 | 0.00 | 36.39 | 46.58 | 0.07 | 0.00 | 0.01 | 0.20 | 11-MAY-22:55 |
June | 0.582608E+10 | 0.00 | 202.54 | 172156.49 | 02-JUN-22:30 | 0.00 | 33.52 | 40.42 | 0.03 | 0.00 | 0.00 | 0.22 | 02-JUN-22:30 |
July | 0.241868E+10 | 0.00 | 98.28 | 139846.25 | 07-JUL-23:57 | 0.00 | 34.09 | 37.37 | 0.01 | 0.00 | 0.00 | 0.18 | 07-JUL-23:57 |
August | 0.319813E+10 | 0.00 | 140.49 | 112523.98 | 18-AUG-23:35 | 0.00 | 36.62 | 41.08 | 0.01 | 0.00 | 0.00 | 0.15 | 18-AUG-23:35 |
September | 0.218505E+11 | 0.00 | 422.39 | 173678.43 | 07-SEP-01:44 | 0.00 | 36.67 | 49.44 | 0.11 | 0.00 | 0.01 | 0.22 | 07-SEP-01:44 |
October | 0.579016E+11 | 0.00 | 681.45 | 216406.28 | 16-OCT-08:62 | 0.00 | 42.79 | 58.31 | 0.32 | 0.00 | 0.03 | 0.28 | 16-OCT-08:62 |
November | 0.159397E+12 | 0.00 | 719.98 | 278474.90 | 25-NOV-09:03 | 0.00 | 41.23 | 60.00 | 0.77 | 0.00 | 0.08 | 0.36 | 25-NOV-09:03 |
December | 0.681303E+12 | 0.00 | 744.00 | 711885.37 | 24-DEC-06:07 | 0.00 | 38.05 | 60.01 | 2.67 | 0.00 | 0.33 | 0.92 | 24-DEC-06:07 |
Annual Sum or Average | 0.242774E+13 | 0.00 | 6158.37 | 0.00 | 38.09 | 52.47 | 0.84 | 0.00 | 0.10 | ||||
Minimum of Months | 0.241868E+10 | 0.00 | 98.28 | 112523.98 | 0.00 | 33.52 | 37.37 | 0.01 | 0.00 | 0.00 | 0.15 | ||
Maximum of Months | 0.767830E+12 | 0.00 | 744.00 | 735116.28 | 0.00 | 42.79 | 60.02 | 2.94 | 0.00 | 0.37 | 0.95 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4252751.44 | 0.00 | 3.44 | 4252751.44 | 0.00 | 0.00 | 0.00 | 0.00 | 1992.91 | 19-JAN-06:20 | 1992.91 | 19-JAN-06:20 | 0.00 | 0.00 | 0.00 |
February | 62131457.28 | 0.00 | 30.28 | 62131457.28 | 0.00 | 0.00 | 0.00 | 0.00 | 11107.87 | 20-FEB-19:25 | 11107.87 | 20-FEB-19:25 | 0.00 | 0.00 | 0.00 |
March | 0.144057E+09 | 0.00 | 56.86 | 0.144057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17336.45 | 19-MAR-18:30 | 17336.45 | 19-MAR-18:30 | 0.00 | 0.00 | 0.00 |
April | 0.136926E+11 | 0.00 | 186.39 | 0.136926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184584.78 | 23-APR-18:10 | 184584.78 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.104106E+12 | 0.00 | 375.95 | 0.101553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286012.73 | 25-MAY-18:08 | 235301.30 | 25-MAY-18:08 | 0.00 | 0.00 | 0.00 |
June | 0.271758E+12 | 0.00 | 524.36 | 0.190415E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 478765.73 | 27-JUN-19:50 | 266474.72 | 29-JUN-18:03 | 0.00 | 0.00 | 0.00 |
July | 0.380595E+12 | 0.00 | 624.75 | 0.245857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 494812.20 | 21-JUL-19:23 | 234962.13 | 24-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.259339E+12 | 0.00 | 588.37 | 0.180963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 463269.44 | 31-AUG-19:04 | 227806.25 | 08-AUG-19:10 | 0.00 | 0.00 | 0.00 |
September | 0.583751E+11 | 0.00 | 303.12 | 0.502738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 255550.72 | 01-SEP-10:50 | 188595.54 | 01-SEP-15:13 | 0.00 | 0.00 | 0.00 |
October | 0.855039E+10 | 0.00 | 166.19 | 0.855039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132401.94 | 19-OCT-15:03 | 132401.94 | 19-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 0.127489E+10 | 0.00 | 103.23 | 0.127489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53629.16 | 01-NOV-15:30 | 53629.16 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 16114192.88 | 0.00 | 13.83 | 16114192.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.98 | 05-DEC-21:10 | 4761.98 | 05-DEC-21:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109792E+13 | 0.00 | 2976.77 | 0.792806E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4252751.44 | 0.00 | 3.44 | 4252751.44 | 0.00 | 0.00 | 0.00 | 0.00 | 1992.91 | 1992.91 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.380595E+12 | 0.00 | 624.75 | 0.245857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 494812.20 | 266474.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 0.220450E+10 | 0.00 | 63.83 | 0.220450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28401.35 | 23-APR-18:00 | 28401.35 | 23-APR-18:00 | 0.00 | 0.00 | 0.00 |
May | 0.181486E+11 | 0.00 | 313.00 | 0.173525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41735.56 | 26-MAY-13:10 | 31390.85 | 25-MAY-18:00 | 0.00 | 0.00 | 0.00 |
June | 0.481002E+11 | 0.00 | 495.83 | 0.327954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64926.24 | 19-JUN-17:25 | 34823.92 | 29-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.674810E+11 | 0.00 | 611.39 | 0.423568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70555.00 | 04-JUL-02:50 | 32903.80 | 15-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.474239E+11 | 0.00 | 576.33 | 0.316156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62434.83 | 31-AUG-20:00 | 32374.70 | 08-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.106511E+11 | 0.00 | 227.21 | 0.879735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41432.33 | 01-SEP-10:25 | 28938.69 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.144276E+10 | 0.00 | 42.23 | 0.144276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24823.32 | 19-OCT-15:00 | 24823.32 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.223309E+09 | 0.00 | 8.83 | 0.223309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12273.98 | 01-NOV-15:00 | 12273.98 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195675E+12 | 0.00 | 2338.66 | 0.136788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.674810E+11 | 0.00 | 611.39 | 0.423568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70555.00 | 34823.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 986442.77 | 0.00 | 0.15 | 986442.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3267.63 | 17-JAN-16:03 | 3267.63 | 17-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 0.129050E+09 | 0.00 | 17.36 | 0.129050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17802.23 | 20-FEB-16:01 | 17802.23 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.553757E+09 | 0.00 | 58.83 | 0.553757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17820.99 | 28-MAR-18:01 | 17820.99 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.184231E+10 | 0.00 | 203.70 | 0.175497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20638.59 | 11-APR-18:11 | 20638.59 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.484224E+10 | 0.00 | 473.31 | 0.357446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22586.58 | 06-MAY-18:42 | 22586.58 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.623976E+10 | 0.00 | 471.87 | 0.371301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23443.67 | 25-JUN-08:51 | 19199.54 | 07-JUN-21:41 | 0.00 | 0.00 | 0.00 |
July | 0.851941E+10 | 0.00 | 509.05 | 0.499360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24029.14 | 25-JUL-21:51 | 20307.62 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 |
August | 0.649542E+10 | 0.00 | 476.12 | 0.353687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22897.47 | 27-AUG-21:51 | 19684.83 | 05-AUG-20:41 | 0.00 | 0.00 | 0.00 |
September | 0.291491E+10 | 0.00 | 389.08 | 0.158959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22107.50 | 01-SEP-21:21 | 20351.95 | 23-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 0.865691E+09 | 0.00 | 136.77 | 0.594947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18415.06 | 20-OCT-18:11 | 18415.06 | 20-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 19646568.60 | 0.00 | 4.67 | 18740248.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17660.90 | 17-NOV-16:01 | 17660.90 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324232E+11 | 0.00 | 2740.91 | 0.204600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.851941E+10 | 0.00 | 509.05 | 0.499360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24029.14 | 22586.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 276407.25 | 0.00 | 0.05 | 276407.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.64 | 20-JAN-16:04 | 2084.64 | 20-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 18761145.87 | 0.00 | 5.28 | 18761145.87 | 0.00 | 0.00 | 0.00 | 0.00 | 9688.71 | 28-FEB-16:02 | 9688.71 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.214814E+09 | 0.00 | 29.09 | 0.214814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17004.97 | 28-MAR-18:01 | 17004.97 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.105481E+10 | 0.00 | 137.99 | 0.990524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19420.99 | 11-APR-18:11 | 19420.99 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.398930E+10 | 0.00 | 432.29 | 0.285566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21579.97 | 06-MAY-18:42 | 21579.97 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.569078E+10 | 0.00 | 459.45 | 0.334333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22383.48 | 25-JUN-08:51 | 18261.70 | 07-JUN-21:41 | 0.00 | 0.00 | 0.00 |
July | 0.762922E+10 | 0.00 | 501.42 | 0.433910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22885.66 | 25-JUL-21:51 | 18685.01 | 07-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.525332E+10 | 0.00 | 455.82 | 0.267436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21411.65 | 25-AUG-21:51 | 18848.11 | 05-AUG-20:41 | 0.00 | 0.00 | 0.00 |
September | 0.176962E+10 | 0.00 | 301.56 | 0.892996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20799.14 | 01-SEP-21:21 | 18742.19 | 23-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 0.266533E+09 | 0.00 | 57.30 | 0.201745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17017.37 | 21-OCT-15:02 | 17017.37 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 2306004.28 | 0.00 | 0.69 | 1597506.11 | 0.00 | 0.00 | 0.00 | 0.00 | 2474.96 | 15-NOV-19:04 | 2474.96 | 15-NOV-19:04 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258897E+11 | 0.00 | 2380.93 | 0.155332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.762922E+10 | 0.00 | 501.42 | 0.433910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22885.66 | 21579.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.711711E+09 | 0.00 | 17.25 | 0.711711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22405.38 | 22-FEB-14:30 | 22405.38 | 22-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.160808E+10 | 0.00 | 46.19 | 0.160808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32793.41 | 20-MAR-12:30 | 32793.41 | 20-MAR-12:30 | 0.00 | 0.00 | 0.00 |
April | 0.953499E+10 | 0.00 | 163.96 | 0.914319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42665.48 | 22-APR-13:00 | 42665.48 | 22-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.191033E+11 | 0.00 | 427.60 | 0.131981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45005.88 | 18-MAY-13:00 | 39693.54 | 06-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.234216E+11 | 0.00 | 464.14 | 0.123804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48264.04 | 30-JUN-13:00 | 38187.42 | 30-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.342252E+11 | 0.00 | 580.69 | 0.158546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51683.33 | 23-JUL-13:00 | 43815.93 | 23-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.311240E+11 | 0.00 | 531.65 | 0.156901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57943.03 | 25-AUG-14:30 | 48704.31 | 24-AUG-13:20 | 0.00 | 0.00 | 0.00 |
September | 0.201469E+11 | 0.00 | 343.91 | 0.150644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57127.40 | 01-SEP-14:20 | 49238.02 | 04-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.102088E+11 | 0.00 | 127.85 | 0.934904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65966.35 | 22-OCT-12:15 | 57571.55 | 21-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.438519E+09 | 0.00 | 10.99 | 0.438519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23231.55 | 17-NOV-13:30 | 23231.55 | 17-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150523E+12 | 0.00 | 2714.24 | 0.934382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.342252E+11 | 0.00 | 580.69 | 0.158546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65966.35 | 57571.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3470859.09 | 0.00 | 0.13 | 3470859.09 | 0.00 | 0.00 | 0.00 | 0.00 | 16534.44 | 29-JAN-09:05 | 16534.44 | 29-JAN-09:05 | 0.00 | 0.00 | 0.00 |
February | 16603113.19 | 0.00 | 0.52 | 16603113.19 | 0.00 | 0.00 | 0.00 | 0.00 | 25134.28 | 07-FEB-19:04 | 25134.28 | 07-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 0.230885E+09 | 0.00 | 21.97 | 0.230885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29600.87 | 31-MAR-15:03 | 29600.87 | 31-MAR-15:03 | 0.00 | 0.00 | 0.00 |
April | 0.448642E+10 | 0.00 | 187.07 | 0.414134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83728.44 | 13-APR-19:41 | 83728.44 | 13-APR-19:41 | 0.00 | 0.00 | 0.00 |
May | 0.262493E+11 | 0.00 | 408.04 | 0.202272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98929.27 | 26-MAY-21:51 | 89070.49 | 21-MAY-21:01 | 0.00 | 0.00 | 0.00 |
June | 0.396438E+11 | 0.00 | 386.96 | 0.263714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114607.27 | 19-JUN-21:51 | 87921.65 | 20-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.465329E+11 | 0.00 | 382.64 | 0.296915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112505.13 | 25-JUL-21:51 | 88782.28 | 01-JUL-21:01 | 0.00 | 0.00 | 0.00 |
August | 0.355835E+11 | 0.00 | 364.58 | 0.202643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108727.27 | 28-AUG-21:51 | 87326.56 | 02-AUG-20:21 | 0.00 | 0.00 | 0.00 |
September | 0.176866E+11 | 0.00 | 407.49 | 0.901086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103521.94 | 18-SEP-21:52 | 85276.59 | 08-SEP-19:41 | 0.00 | 0.00 | 0.00 |
October | 0.324290E+10 | 0.00 | 186.02 | 0.195093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80933.21 | 01-OCT-18:01 | 80933.21 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.326112E+09 | 0.00 | 23.76 | 0.147536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39901.29 | 01-NOV-18:03 | 31676.81 | 01-NOV-18:03 | 0.00 | 0.00 | 0.00 |
December | 3323064.47 | 0.00 | 0.21 | 3323064.47 | 0.00 | 0.00 | 0.00 | 0.00 | 11281.16 | 30-DEC-09:05 | 11281.16 | 30-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174006E+12 | 0.00 | 2369.39 | 0.112059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3323064.47 | 0.00 | 0.13 | 3323064.47 | 0.00 | 0.00 | 0.00 | 0.00 | 11281.16 | 11281.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.465329E+11 | 0.00 | 408.04 | 0.296915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114607.27 | 89070.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 52513058.87 | 0.00 | 13.20 | 52513058.87 | 0.00 | 0.00 | 0.00 | 0.00 | 10856.66 | 28-FEB-16:02 | 10856.66 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.339283E+09 | 0.00 | 61.06 | 0.339283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16200.76 | 26-MAR-15:01 | 16200.76 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.196462E+10 | 0.00 | 242.36 | 0.188345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16680.95 | 22-APR-19:21 | 16680.95 | 22-APR-19:21 | 0.00 | 0.00 | 0.00 |
May | 0.473917E+10 | 0.00 | 485.96 | 0.349097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19241.79 | 26-MAY-08:51 | 18772.37 | 18-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.690246E+10 | 0.00 | 500.81 | 0.435667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22772.11 | 25-JUN-08:32 | 18661.66 | 27-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.859932E+10 | 0.00 | 521.86 | 0.519324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23241.14 | 23-JUL-08:32 | 19826.25 | 01-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.641811E+10 | 0.00 | 486.65 | 0.355906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21425.19 | 30-AUG-08:51 | 17951.05 | 13-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.307725E+10 | 0.00 | 382.41 | 0.180607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20257.02 | 01-SEP-08:51 | 16839.30 | 09-SEP-18:51 | 0.00 | 0.00 | 0.00 |
October | 0.821900E+09 | 0.00 | 126.95 | 0.556331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16216.03 | 21-OCT-15:02 | 16216.03 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 70794697.61 | 0.00 | 12.75 | 69923007.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9556.99 | 16-NOV-09:01 | 9556.99 | 16-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 271276.53 | 0.00 | 0.05 | 271276.53 | 0.00 | 0.00 | 0.00 | 0.00 | 1528.03 | 28-DEC-09:04 | 1528.03 | 28-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329857E+11 | 0.00 | 2834.05 | 0.213078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.859932E+10 | 0.00 | 521.86 | 0.519324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23241.14 | 19826.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 985794.00 | 0.00 | 0.28 | 985794.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3026.33 | 27-FEB-09:03 | 3026.33 | 27-FEB-09:03 | 0.00 | 0.00 | 0.00 |
March | 92887812.85 | 0.00 | 18.15 | 92887812.85 | 0.00 | 0.00 | 0.00 | 0.00 | 13921.78 | 26-MAR-08:61 | 13921.78 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.104308E+10 | 0.00 | 154.44 | 0.995774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15406.06 | 18-APR-08:62 | 15406.06 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.385015E+10 | 0.00 | 449.73 | 0.273246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18187.84 | 26-MAY-08:51 | 17773.93 | 18-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.631673E+10 | 0.00 | 495.81 | 0.390647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21573.21 | 25-JUN-08:32 | 17712.92 | 27-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.768381E+10 | 0.00 | 516.96 | 0.443439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21975.29 | 23-JUL-08:32 | 18832.95 | 01-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.515899E+10 | 0.00 | 479.21 | 0.266423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20122.37 | 30-AUG-08:51 | 17136.01 | 13-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.190466E+10 | 0.00 | 308.50 | 0.106621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19249.65 | 01-SEP-08:51 | 15846.80 | 01-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.252544E+09 | 0.00 | 41.00 | 0.168323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14794.53 | 22-OCT-08:62 | 14794.53 | 22-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 3751859.22 | 0.00 | 1.78 | 3020986.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3210.42 | 17-NOV-09:03 | 3210.42 | 17-NOV-09:03 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263076E+11 | 0.00 | 2465.87 | 0.160648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.768381E+10 | 0.00 | 516.96 | 0.443439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21975.29 | 18832.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 243416.90 | 0.00 | 0.15 | 243416.90 | 0.00 | 0.00 | 0.00 | 0.00 | 775.36 | 20-JAN-16:03 | 775.36 | 20-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 33227618.09 | 0.00 | 15.67 | 33227618.09 | 0.00 | 0.00 | 0.00 | 0.00 | 4629.55 | 20-FEB-16:01 | 4629.55 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.147019E+09 | 0.00 | 54.05 | 0.147019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4634.45 | 28-MAR-18:01 | 4634.45 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.478187E+09 | 0.00 | 185.28 | 0.455929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5739.21 | 11-APR-17:52 | 5739.21 | 11-APR-17:52 | 0.00 | 0.00 | 0.00 |
May | 0.126094E+10 | 0.00 | 436.24 | 0.955030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5938.71 | 06-MAY-18:32 | 5938.71 | 06-MAY-18:32 | 0.00 | 0.00 | 0.00 |
June | 0.162627E+10 | 0.00 | 448.48 | 0.994248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6279.62 | 25-JUN-08:51 | 5050.71 | 07-JUN-21:41 | 0.00 | 0.00 | 0.00 |
July | 0.220091E+10 | 0.00 | 508.98 | 0.131446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6430.70 | 25-JUL-21:51 | 5657.93 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 |
August | 0.165135E+10 | 0.00 | 468.29 | 0.925942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6139.93 | 27-AUG-21:51 | 5568.68 | 02-AUG-20:02 | 0.00 | 0.00 | 0.00 |
September | 0.681761E+09 | 0.00 | 334.81 | 0.390989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5899.73 | 01-SEP-21:21 | 5338.36 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.208761E+09 | 0.00 | 103.32 | 0.151081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4958.07 | 20-OCT-18:11 | 4958.07 | 20-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 4407749.48 | 0.00 | 3.08 | 4177213.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4619.16 | 17-NOV-16:01 | 4619.16 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 6012.87 | 0.00 | 0.03 | 6012.87 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 02-DEC-16:05 | 60.13 | 02-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829307E+10 | 0.00 | 2558.40 | 0.537235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6012.87 | 0.00 | 0.03 | 6012.87 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 60.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.220091E+10 | 0.00 | 508.98 | 0.131446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6430.70 | 5938.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 2503238.39 | 0.00 | 4.76 | 2503238.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.41 | 28-FEB-16:02 | 1008.41 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 53290732.13 | 0.00 | 28.16 | 53290732.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4403.68 | 28-MAR-18:01 | 4403.68 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.268065E+09 | 0.00 | 114.57 | 0.253586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5098.99 | 11-APR-18:11 | 5098.99 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.102798E+10 | 0.00 | 395.94 | 0.752368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5685.21 | 06-MAY-18:32 | 5685.21 | 06-MAY-18:32 | 0.00 | 0.00 | 0.00 |
June | 0.147624E+10 | 0.00 | 439.92 | 0.889580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5969.70 | 25-JUN-08:51 | 4792.74 | 07-JUN-21:41 | 0.00 | 0.00 | 0.00 |
July | 0.196324E+10 | 0.00 | 502.21 | 0.113781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6108.86 | 25-JUL-21:51 | 5327.85 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 |
August | 0.131448E+10 | 0.00 | 448.75 | 0.680755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5761.19 | 10-AUG-21:41 | 5282.35 | 02-AUG-20:02 | 0.00 | 0.00 | 0.00 |
September | 0.388256E+09 | 0.00 | 244.61 | 0.209938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5458.40 | 01-SEP-21:21 | 5004.29 | 23-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 58298557.54 | 0.00 | 42.79 | 46018595.69 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.81 | 21-OCT-15:02 | 4406.81 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 646294.05 | 0.00 | 0.45 | 451490.39 | 0.00 | 0.00 | 0.00 | 0.00 | 811.98 | 09-NOV-16:03 | 811.98 | 09-NOV-16:03 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.655300E+10 | 0.00 | 2222.15 | 0.402630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.196324E+10 | 0.00 | 502.21 | 0.113781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6108.86 | 5685.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.412280E+09 | 0.00 | 37.23 | 0.412280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22815.16 | 27-JAN-16:01 | 22815.16 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.132835E+10 | 0.00 | 110.27 | 0.132835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22841.89 | 04-FEB-16:01 | 22841.89 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.191189E+10 | 0.00 | 145.47 | 0.191189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22856.79 | 26-MAR-15:01 | 22856.79 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.355432E+10 | 0.00 | 274.00 | 0.339642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25110.34 | 13-APR-19:41 | 25110.34 | 13-APR-19:41 | 0.00 | 0.00 | 0.00 |
May | 0.639393E+10 | 0.00 | 472.22 | 0.465660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26390.56 | 26-MAY-21:51 | 24806.99 | 05-MAY-19:51 | 0.00 | 0.00 | 0.00 |
June | 0.792345E+10 | 0.00 | 462.38 | 0.461441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30264.80 | 19-JUN-21:51 | 23701.12 | 20-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.107452E+11 | 0.00 | 504.63 | 0.624133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30452.83 | 30-JUL-08:41 | 23820.97 | 26-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.965998E+10 | 0.00 | 477.67 | 0.559204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29888.58 | 31-AUG-21:51 | 24873.76 | 05-AUG-20:41 | 0.00 | 0.00 | 0.00 |
September | 0.595276E+10 | 0.00 | 429.89 | 0.376267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28550.26 | 01-SEP-21:21 | 25014.48 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.326333E+10 | 0.00 | 214.49 | 0.252214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25559.91 | 20-OCT-18:11 | 25559.91 | 20-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 0.901779E+09 | 0.00 | 71.01 | 0.896699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22843.64 | 16-NOV-16:02 | 22843.64 | 16-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.191219E+09 | 0.00 | 21.11 | 0.191219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22473.84 | 02-DEC-16:02 | 22473.84 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.522385E+11 | 0.00 | 3220.38 | 0.355260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.191219E+09 | 0.00 | 21.11 | 0.191219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22473.84 | 22473.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107452E+11 | 0.00 | 504.63 | 0.624133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30452.83 | 25559.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 955.44 | 665.88 | 289.56 | 764.69 | 1036.90 | 0.00 | 0.00 | 0.00 |
February | 1192.84 | 802.58 | 390.26 | 1078.00 | 887.78 | 0.00 | 0.00 | 0.00 |
March | 1048.51 | 659.96 | 388.55 | 974.24 | 737.78 | 0.00 | 0.00 | 0.00 |
April | 957.67 | 519.22 | 438.45 | 978.38 | 483.04 | 0.00 | 0.00 | 0.00 |
May | 819.75 | 289.21 | 530.53 | 937.71 | 250.12 | 0.00 | 0.00 | 0.00 |
June | 720.29 | 189.77 | 530.53 | 889.60 | 159.01 | 0.00 | 0.00 | 0.00 |
July | 792.53 | 252.19 | 540.34 | 1019.58 | 144.20 | 0.00 | 0.00 | 0.00 |
August | 840.95 | 349.61 | 491.34 | 1044.93 | 169.48 | 0.00 | 0.00 | 0.00 |
September | 886.96 | 464.05 | 422.92 | 1007.60 | 286.89 | 0.00 | 0.00 | 0.00 |
October | 788.67 | 470.16 | 318.50 | 782.01 | 458.57 | 0.00 | 0.00 | 0.00 |
November | 688.88 | 431.96 | 256.92 | 588.42 | 684.86 | 0.00 | 0.00 | 0.00 |
December | 733.86 | 481.50 | 252.36 | 537.91 | 1015.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.80 | 462.59 | 404.21 | 882.18 | 524.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.88 | 189.77 | 252.36 | 537.91 | 144.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1192.84 | 802.58 | 540.34 | 1078.00 | 1036.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2690.46 | 1875.07 | 815.40 | 2135.99 | 2949.25 | 0.00 | 0.00 | 0.00 |
February | 3358.95 | 2260.01 | 1098.94 | 3009.92 | 2530.06 | 0.00 | 0.00 | 0.00 |
March | 2952.53 | 1858.39 | 1094.13 | 2718.66 | 2119.52 | 0.00 | 0.00 | 0.00 |
April | 2696.73 | 1462.08 | 1234.65 | 2725.38 | 1419.05 | 0.00 | 0.00 | 0.00 |
May | 2308.35 | 814.40 | 1493.95 | 2599.17 | 764.71 | 0.00 | 0.00 | 0.00 |
June | 2028.29 | 534.37 | 1493.93 | 2458.25 | 502.09 | 0.00 | 0.00 | 0.00 |
July | 2231.71 | 710.16 | 1521.56 | 2831.95 | 451.55 | 0.00 | 0.00 | 0.00 |
August | 2368.05 | 984.47 | 1383.58 | 2905.42 | 537.65 | 0.00 | 0.00 | 0.00 |
September | 2497.62 | 1306.72 | 1190.90 | 2801.96 | 882.61 | 0.00 | 0.00 | 0.00 |
October | 2220.83 | 1323.95 | 896.88 | 2176.70 | 1355.96 | 0.00 | 0.00 | 0.00 |
November | 1939.83 | 1216.37 | 723.46 | 1638.63 | 1966.96 | 0.00 | 0.00 | 0.00 |
December | 2066.49 | 1355.87 | 710.62 | 1500.04 | 2885.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2440.87 | 1302.62 | 1138.24 | 2454.55 | 1525.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1939.83 | 534.37 | 710.62 | 1500.04 | 451.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3358.95 | 2260.01 | 1521.56 | 3009.92 | 2949.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3495.06 | 2435.82 | 1059.24 | 2810.93 | 3976.46 | 0.00 | 0.00 | 0.00 |
February | 4363.46 | 2935.88 | 1427.58 | 3978.70 | 3408.05 | 0.00 | 0.00 | 0.00 |
March | 3835.50 | 2414.16 | 1421.34 | 3596.56 | 2865.48 | 0.00 | 0.00 | 0.00 |
April | 3503.21 | 1899.33 | 1603.88 | 3601.61 | 1938.36 | 0.00 | 0.00 | 0.00 |
May | 2998.68 | 1057.96 | 1940.72 | 3428.17 | 1047.30 | 0.00 | 0.00 | 0.00 |
June | 2634.87 | 694.17 | 1940.70 | 3240.06 | 691.44 | 0.00 | 0.00 | 0.00 |
July | 2899.12 | 922.53 | 1976.59 | 3739.50 | 611.07 | 0.00 | 0.00 | 0.00 |
August | 3076.23 | 1278.88 | 1797.35 | 3831.35 | 729.75 | 0.00 | 0.00 | 0.00 |
September | 3244.55 | 1697.51 | 1547.05 | 3686.37 | 1214.00 | 0.00 | 0.00 | 0.00 |
October | 2884.99 | 1719.89 | 1165.10 | 2856.25 | 1871.00 | 0.00 | 0.00 | 0.00 |
November | 2519.95 | 1580.13 | 939.82 | 2154.98 | 2696.90 | 0.00 | 0.00 | 0.00 |
December | 2684.49 | 1761.35 | 923.13 | 1966.79 | 3911.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3170.82 | 1692.18 | 1478.64 | 3235.64 | 2074.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2519.95 | 694.17 | 923.13 | 1966.79 | 611.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4363.46 | 2935.88 | 1976.59 | 3978.70 | 3976.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 151.25 | 217.32 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 214.04 | 182.10 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 194.35 | 149.58 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 194.13 | 97.97 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 183.61 | 51.88 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 173.78 | 33.23 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 200.28 | 29.55 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 205.43 | 34.92 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 199.04 | 58.11 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 156.32 | 90.98 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 117.80 | 137.64 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 106.29 | 211.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 174.41 | 107.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 106.29 | 29.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 214.04 | 217.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 42.26 | 472.01 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 109.69 | 381.99 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 180.95 | 295.96 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 282.18 | 179.64 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 420.23 | 92.54 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 433.32 | 59.55 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 479.59 | 53.21 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 379.41 | 63.61 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 260.72 | 107.10 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 125.20 | 176.50 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 44.77 | 283.47 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 22.40 | 456.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 232.47 | 217.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 22.40 | 53.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 479.59 | 472.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.07 | 272.48 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 2.15 | 218.63 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 6.86 | 167.18 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 29.19 | 97.98 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 82.23 | 46.12 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 115.74 | 29.85 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 116.02 | 26.81 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 79.04 | 32.74 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 45.12 | 58.06 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 14.89 | 96.73 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.06 | 159.06 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 260.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 41.36 | 121.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 26.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 116.02 | 272.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 43.77 | 468.99 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 113.79 | 378.30 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 185.69 | 292.66 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 287.86 | 177.66 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 423.18 | 91.76 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 434.76 | 59.14 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 481.37 | 52.62 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 382.38 | 62.45 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 265.19 | 105.48 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 129.17 | 174.35 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 47.24 | 281.03 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 23.31 | 454.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 235.54 | 215.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 23.31 | 52.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 481.37 | 468.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.10 | 105.30 | 45.79 | 120.07 | 170.58 | 0.00 | 0.00 | 0.00 |
February | 188.64 | 126.92 | 61.72 | 169.93 | 144.37 | 0.00 | 0.00 | 0.00 |
March | 165.81 | 104.37 | 61.45 | 154.37 | 119.69 | 0.00 | 0.00 | 0.00 |
April | 151.45 | 82.11 | 69.34 | 154.05 | 81.31 | 0.00 | 0.00 | 0.00 |
May | 129.64 | 45.74 | 83.90 | 146.35 | 44.45 | 0.00 | 0.00 | 0.00 |
June | 113.91 | 30.01 | 83.90 | 139.31 | 28.62 | 0.00 | 0.00 | 0.00 |
July | 125.33 | 39.88 | 85.45 | 161.38 | 25.09 | 0.00 | 0.00 | 0.00 |
August | 132.99 | 55.29 | 77.70 | 164.47 | 30.28 | 0.00 | 0.00 | 0.00 |
September | 140.27 | 73.39 | 66.88 | 157.56 | 51.43 | 0.00 | 0.00 | 0.00 |
October | 124.72 | 74.35 | 50.37 | 123.59 | 75.93 | 0.00 | 0.00 | 0.00 |
November | 108.94 | 68.31 | 40.63 | 93.63 | 108.01 | 0.00 | 0.00 | 0.00 |
December | 116.05 | 76.15 | 39.91 | 84.55 | 165.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.08 | 73.16 | 63.92 | 138.88 | 86.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.94 | 30.01 | 39.91 | 84.55 | 25.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.64 | 126.92 | 85.45 | 169.93 | 170.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.79 | 0.00 | 21.79 | 0.04 | 223.42 | 0.00 | 0.00 | 0.00 |
February | 33.47 | 0.00 | 33.47 | 1.49 | 179.40 | 0.00 | 0.00 | 0.00 |
March | 41.19 | 0.00 | 41.19 | 5.28 | 136.42 | 0.00 | 0.00 | 0.00 |
April | 54.17 | 0.56 | 53.61 | 24.65 | 78.77 | 0.00 | 0.00 | 0.00 |
May | 75.97 | 4.03 | 71.94 | 70.84 | 35.52 | 0.00 | 0.00 | 0.00 |
June | 84.90 | 9.45 | 75.45 | 98.21 | 22.36 | 0.00 | 0.00 | 0.00 |
July | 81.17 | 7.12 | 74.04 | 99.15 | 19.31 | 0.00 | 0.00 | 0.00 |
August | 61.63 | 1.17 | 60.46 | 68.43 | 23.97 | 0.00 | 0.00 | 0.00 |
September | 47.99 | 0.05 | 47.94 | 38.59 | 45.11 | 0.00 | 0.00 | 0.00 |
October | 33.27 | 0.00 | 33.27 | 11.68 | 79.35 | 0.00 | 0.00 | 0.00 |
November | 22.03 | 0.00 | 22.03 | 1.42 | 132.33 | 0.00 | 0.00 | 0.00 |
December | 18.46 | 0.00 | 18.46 | 0.00 | 214.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.08 | 1.87 | 46.20 | 35.19 | 98.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.46 | 0.00 | 18.46 | 0.00 | 19.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.90 | 9.45 | 75.45 | 99.15 | 223.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.18 | 46.10 | 65.08 | 34.63 | 465.50 | 0.00 | 0.00 | 0.00 |
February | 176.67 | 75.98 | 100.69 | 90.69 | 369.22 | 0.00 | 0.00 | 0.00 |
March | 240.14 | 120.73 | 119.42 | 168.31 | 286.35 | 0.00 | 0.00 | 0.00 |
April | 330.74 | 178.31 | 152.43 | 302.93 | 171.78 | 0.00 | 0.00 | 0.00 |
May | 359.21 | 158.43 | 200.78 | 389.32 | 85.56 | 0.00 | 0.00 | 0.00 |
June | 405.32 | 193.86 | 211.46 | 483.33 | 56.38 | 0.00 | 0.00 | 0.00 |
July | 397.90 | 187.19 | 210.71 | 486.18 | 49.71 | 0.00 | 0.00 | 0.00 |
August | 306.28 | 133.85 | 172.43 | 358.99 | 60.12 | 0.00 | 0.00 | 0.00 |
September | 245.93 | 110.35 | 135.58 | 251.65 | 102.65 | 0.00 | 0.00 | 0.00 |
October | 148.07 | 55.67 | 92.39 | 107.20 | 171.82 | 0.00 | 0.00 | 0.00 |
November | 94.85 | 31.59 | 63.26 | 39.43 | 278.80 | 0.00 | 0.00 | 0.00 |
December | 87.20 | 32.73 | 54.47 | 21.55 | 452.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.20 | 110.48 | 131.71 | 228.52 | 211.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.20 | 31.59 | 54.47 | 21.55 | 49.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.32 | 193.86 | 211.46 | 486.18 | 465.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 151.07 | 216.99 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 213.71 | 181.68 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 193.12 | 149.01 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 192.53 | 97.19 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 183.36 | 50.25 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 172.39 | 31.94 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 199.12 | 27.95 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 205.29 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 198.91 | 56.75 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 156.16 | 90.44 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 117.68 | 137.45 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 106.10 | 211.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 173.83 | 106.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 106.10 | 27.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 213.71 | 216.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.07 | 272.27 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 2.06 | 218.47 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 6.27 | 167.02 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 27.76 | 97.92 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 82.45 | 45.26 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 114.61 | 28.99 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 115.25 | 25.70 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 79.04 | 31.46 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 44.64 | 56.82 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 14.55 | 96.04 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.02 | 159.06 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 260.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 40.97 | 121.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 25.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 115.25 | 272.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.18 | 46.10 | 65.08 | 35.53 | 461.76 | 0.00 | 0.00 | 0.00 |
February | 176.67 | 75.98 | 100.69 | 93.40 | 364.08 | 0.00 | 0.00 | 0.00 |
March | 240.14 | 120.73 | 119.42 | 172.09 | 281.62 | 0.00 | 0.00 | 0.00 |
April | 330.74 | 178.31 | 152.43 | 307.42 | 169.56 | 0.00 | 0.00 | 0.00 |
May | 359.21 | 158.43 | 200.78 | 391.80 | 84.75 | 0.00 | 0.00 | 0.00 |
June | 405.32 | 193.86 | 211.46 | 484.64 | 56.04 | 0.00 | 0.00 | 0.00 |
July | 397.90 | 187.19 | 210.71 | 487.92 | 49.17 | 0.00 | 0.00 | 0.00 |
August | 306.28 | 133.85 | 172.43 | 361.69 | 58.99 | 0.00 | 0.00 | 0.00 |
September | 245.93 | 110.35 | 135.58 | 255.28 | 100.91 | 0.00 | 0.00 | 0.00 |
October | 148.07 | 55.67 | 92.39 | 110.70 | 169.17 | 0.00 | 0.00 | 0.00 |
November | 94.85 | 31.59 | 63.26 | 40.61 | 275.22 | 0.00 | 0.00 | 0.00 |
December | 87.20 | 32.73 | 54.47 | 22.05 | 449.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.20 | 110.48 | 131.71 | 230.93 | 209.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.20 | 31.59 | 54.47 | 22.05 | 49.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.32 | 193.86 | 211.46 | 487.92 | 461.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.49 | 0.00 | 34.49 | 0.03 | 362.28 | 0.00 | 0.00 | 0.00 |
February | 52.98 | 0.00 | 52.98 | 1.74 | 292.61 | 0.00 | 0.00 | 0.00 |
March | 65.20 | 0.00 | 65.20 | 7.14 | 222.77 | 0.00 | 0.00 | 0.00 |
April | 85.74 | 0.88 | 84.86 | 36.47 | 129.56 | 0.00 | 0.00 | 0.00 |
May | 120.24 | 6.38 | 113.86 | 107.74 | 61.75 | 0.00 | 0.00 | 0.00 |
June | 134.38 | 14.95 | 119.43 | 150.01 | 40.54 | 0.00 | 0.00 | 0.00 |
July | 128.47 | 11.28 | 117.20 | 149.69 | 37.22 | 0.00 | 0.00 | 0.00 |
August | 97.56 | 1.86 | 95.70 | 102.41 | 45.31 | 0.00 | 0.00 | 0.00 |
September | 75.96 | 0.08 | 75.88 | 57.29 | 78.75 | 0.00 | 0.00 | 0.00 |
October | 52.65 | 0.00 | 52.65 | 16.90 | 130.27 | 0.00 | 0.00 | 0.00 |
November | 34.86 | 0.00 | 34.86 | 2.06 | 216.04 | 0.00 | 0.00 | 0.00 |
December | 29.23 | 0.00 | 29.23 | 0.00 | 348.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.10 | 2.97 | 73.13 | 52.95 | 163.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.23 | 0.00 | 29.23 | 0.00 | 37.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.38 | 14.95 | 119.43 | 150.01 | 362.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.72 | 0.00 | 12.72 | 0.01 | 133.55 | 0.00 | 0.00 | 0.00 |
February | 19.53 | 0.00 | 19.53 | 0.64 | 107.87 | 0.00 | 0.00 | 0.00 |
March | 24.04 | 0.00 | 24.04 | 2.63 | 82.12 | 0.00 | 0.00 | 0.00 |
April | 31.61 | 0.32 | 31.28 | 13.45 | 47.76 | 0.00 | 0.00 | 0.00 |
May | 44.33 | 2.35 | 41.98 | 39.72 | 22.76 | 0.00 | 0.00 | 0.00 |
June | 49.54 | 5.51 | 44.03 | 55.30 | 14.94 | 0.00 | 0.00 | 0.00 |
July | 47.36 | 4.16 | 43.20 | 55.18 | 13.72 | 0.00 | 0.00 | 0.00 |
August | 35.96 | 0.68 | 35.28 | 37.75 | 16.70 | 0.00 | 0.00 | 0.00 |
September | 28.00 | 0.03 | 27.97 | 21.12 | 29.03 | 0.00 | 0.00 | 0.00 |
October | 19.41 | 0.00 | 19.41 | 6.23 | 48.02 | 0.00 | 0.00 | 0.00 |
November | 12.85 | 0.00 | 12.85 | 0.76 | 79.64 | 0.00 | 0.00 | 0.00 |
December | 10.77 | 0.00 | 10.77 | 0.00 | 128.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.05 | 1.09 | 26.96 | 19.52 | 60.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.77 | 0.00 | 10.77 | 0.00 | 13.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.54 | 5.51 | 44.03 | 55.30 | 133.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.14 | 61.43 | 26.71 | 69.61 | 104.78 | 0.00 | 0.00 | 0.00 |
February | 110.04 | 74.04 | 36.00 | 99.29 | 87.95 | 0.00 | 0.00 | 0.00 |
March | 96.73 | 60.88 | 35.85 | 90.66 | 72.19 | 0.00 | 0.00 | 0.00 |
April | 88.35 | 47.90 | 40.45 | 91.53 | 47.02 | 0.00 | 0.00 | 0.00 |
May | 75.63 | 26.68 | 48.94 | 87.36 | 25.04 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 17.51 | 48.94 | 82.45 | 16.43 | 0.00 | 0.00 | 0.00 |
July | 73.11 | 23.27 | 49.85 | 94.69 | 14.88 | 0.00 | 0.00 | 0.00 |
August | 77.58 | 32.25 | 45.33 | 97.23 | 17.32 | 0.00 | 0.00 | 0.00 |
September | 81.83 | 42.81 | 39.02 | 93.95 | 28.58 | 0.00 | 0.00 | 0.00 |
October | 72.76 | 43.37 | 29.38 | 73.12 | 44.39 | 0.00 | 0.00 | 0.00 |
November | 63.55 | 39.85 | 23.70 | 54.35 | 67.54 | 0.00 | 0.00 | 0.00 |
December | 67.70 | 44.42 | 23.28 | 48.65 | 102.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.97 | 42.68 | 37.29 | 81.78 | 52.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.55 | 17.51 | 23.28 | 48.65 | 14.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.04 | 74.04 | 49.85 | 99.29 | 104.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.24 | 166.73 | 72.51 | 188.93 | 284.40 | 0.00 | 0.00 | 0.00 |
February | 298.68 | 200.96 | 97.72 | 269.48 | 238.71 | 0.00 | 0.00 | 0.00 |
March | 262.54 | 165.25 | 97.29 | 246.07 | 195.93 | 0.00 | 0.00 | 0.00 |
April | 239.80 | 130.01 | 109.79 | 248.44 | 127.63 | 0.00 | 0.00 | 0.00 |
May | 205.26 | 72.42 | 132.84 | 237.10 | 67.96 | 0.00 | 0.00 | 0.00 |
June | 180.36 | 47.52 | 132.84 | 223.78 | 44.61 | 0.00 | 0.00 | 0.00 |
July | 198.45 | 63.15 | 135.30 | 257.00 | 40.40 | 0.00 | 0.00 | 0.00 |
August | 210.57 | 87.54 | 123.03 | 263.90 | 47.02 | 0.00 | 0.00 | 0.00 |
September | 222.09 | 116.20 | 105.90 | 255.00 | 77.57 | 0.00 | 0.00 | 0.00 |
October | 197.48 | 117.73 | 79.75 | 198.47 | 120.48 | 0.00 | 0.00 | 0.00 |
November | 172.49 | 108.16 | 64.33 | 147.52 | 183.31 | 0.00 | 0.00 | 0.00 |
December | 183.76 | 120.57 | 63.19 | 132.04 | 279.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.05 | 115.83 | 101.21 | 221.96 | 141.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 172.49 | 47.52 | 63.19 | 132.04 | 40.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.68 | 200.96 | 135.30 | 269.48 | 284.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 150.59 | 218.07 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 213.01 | 182.45 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 193.67 | 149.69 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 193.11 | 98.02 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 182.12 | 52.41 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 172.38 | 33.73 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 198.96 | 29.95 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 204.02 | 35.47 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 197.94 | 58.26 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 155.90 | 90.62 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 117.45 | 137.54 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 105.74 | 212.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 173.46 | 107.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 105.74 | 29.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 213.01 | 218.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 41.83 | 474.07 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 108.89 | 383.23 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 179.93 | 296.24 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 279.99 | 179.51 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 416.87 | 92.96 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 430.01 | 59.99 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 476.36 | 53.55 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 376.60 | 64.25 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 258.73 | 107.01 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 124.70 | 175.73 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 44.69 | 283.43 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 22.14 | 459.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 230.80 | 218.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 22.14 | 53.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 476.36 | 474.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.07 | 273.25 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 2.20 | 219.25 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 6.84 | 167.53 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 29.03 | 98.08 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 81.03 | 46.43 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 114.50 | 30.14 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 115.03 | 27.06 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 78.30 | 33.04 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 44.99 | 57.99 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 15.16 | 96.12 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.13 | 158.86 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 261.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 41.01 | 122.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 27.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 115.03 | 273.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 43.33 | 470.78 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 112.98 | 379.60 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 184.81 | 292.98 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 286.12 | 177.39 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 420.01 | 92.12 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 431.55 | 59.57 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 478.27 | 52.94 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 379.81 | 62.93 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 263.76 | 105.07 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 129.14 | 173.25 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 47.22 | 281.10 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 23.05 | 457.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 234.07 | 216.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 23.05 | 52.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 478.27 | 470.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 277.05 | 193.09 | 83.97 | 213.13 | 327.93 | 0.00 | 0.00 | 0.00 |
February | 345.89 | 232.72 | 113.16 | 303.26 | 274.93 | 0.00 | 0.00 | 0.00 |
March | 304.04 | 191.37 | 112.67 | 277.53 | 224.89 | 0.00 | 0.00 | 0.00 |
April | 277.70 | 150.56 | 127.14 | 279.70 | 145.14 | 0.00 | 0.00 | 0.00 |
May | 237.70 | 83.86 | 153.84 | 269.04 | 73.81 | 0.00 | 0.00 | 0.00 |
June | 208.87 | 55.03 | 153.84 | 256.84 | 46.20 | 0.00 | 0.00 | 0.00 |
July | 229.81 | 73.13 | 156.68 | 296.23 | 40.16 | 0.00 | 0.00 | 0.00 |
August | 243.85 | 101.38 | 142.48 | 301.26 | 49.26 | 0.00 | 0.00 | 0.00 |
September | 257.19 | 134.56 | 122.63 | 288.88 | 85.19 | 0.00 | 0.00 | 0.00 |
October | 228.69 | 136.33 | 92.36 | 224.57 | 136.75 | 0.00 | 0.00 | 0.00 |
November | 199.75 | 125.26 | 74.50 | 166.64 | 208.12 | 0.00 | 0.00 | 0.00 |
December | 212.80 | 139.62 | 73.18 | 149.34 | 319.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.35 | 134.14 | 117.21 | 251.83 | 160.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.75 | 55.03 | 73.18 | 149.34 | 40.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 345.89 | 232.72 | 156.68 | 303.26 | 327.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.65 | 0.00 | 190.65 | 0.05 | 2059.57 | 0.00 | 0.00 | 0.00 |
February | 292.85 | 0.00 | 292.85 | 6.08 | 1707.51 | 0.00 | 0.00 | 0.00 |
March | 360.38 | 0.01 | 360.37 | 27.71 | 1339.08 | 0.00 | 0.00 | 0.00 |
April | 473.88 | 4.87 | 469.02 | 164.62 | 807.53 | 0.00 | 0.00 | 0.00 |
May | 664.60 | 35.26 | 629.34 | 545.19 | 373.98 | 0.00 | 0.00 | 0.00 |
June | 742.73 | 82.63 | 660.10 | 785.62 | 242.29 | 0.00 | 0.00 | 0.00 |
July | 710.09 | 62.33 | 647.75 | 801.28 | 212.37 | 0.00 | 0.00 | 0.00 |
August | 539.20 | 10.26 | 528.94 | 535.27 | 268.80 | 0.00 | 0.00 | 0.00 |
September | 419.81 | 0.43 | 419.38 | 280.15 | 485.54 | 0.00 | 0.00 | 0.00 |
October | 291.02 | 0.00 | 291.02 | 68.01 | 823.04 | 0.00 | 0.00 | 0.00 |
November | 192.69 | 0.00 | 192.69 | 7.31 | 1323.18 | 0.00 | 0.00 | 0.00 |
December | 161.53 | 0.00 | 161.53 | 0.00 | 2003.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.59 | 16.39 | 404.20 | 270.15 | 967.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.53 | 0.00 | 161.53 | 0.00 | 212.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.73 | 82.63 | 660.10 | 801.28 | 2059.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.65 | 0.00 | 190.65 | 0.01 | 2092.56 | 0.00 | 0.00 | 0.00 |
February | 292.85 | 0.00 | 292.85 | 4.88 | 1741.30 | 0.00 | 0.00 | 0.00 |
March | 360.38 | 0.01 | 360.37 | 24.46 | 1369.01 | 0.00 | 0.00 | 0.00 |
April | 473.88 | 4.87 | 469.02 | 155.55 | 826.29 | 0.00 | 0.00 | 0.00 |
May | 664.60 | 35.26 | 629.34 | 534.47 | 381.64 | 0.00 | 0.00 | 0.00 |
June | 742.73 | 82.63 | 660.10 | 775.54 | 247.93 | 0.00 | 0.00 | 0.00 |
July | 710.09 | 62.33 | 647.75 | 792.72 | 217.33 | 0.00 | 0.00 | 0.00 |
August | 539.20 | 10.26 | 528.94 | 526.64 | 275.98 | 0.00 | 0.00 | 0.00 |
September | 419.81 | 0.43 | 419.38 | 270.99 | 497.02 | 0.00 | 0.00 | 0.00 |
October | 291.02 | 0.00 | 291.02 | 61.99 | 843.89 | 0.00 | 0.00 | 0.00 |
November | 192.69 | 0.00 | 192.69 | 6.44 | 1356.30 | 0.00 | 0.00 | 0.00 |
December | 161.53 | 0.00 | 161.53 | 0.00 | 2036.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.59 | 16.39 | 404.20 | 264.50 | 987.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.53 | 0.00 | 161.53 | 0.00 | 217.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.73 | 82.63 | 660.10 | 792.72 | 2092.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.07 | 267.36 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 1.88 | 220.96 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 7.18 | 171.52 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 33.80 | 104.10 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 101.06 | 50.41 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 138.35 | 33.93 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 141.71 | 29.37 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 100.18 | 34.90 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 56.63 | 60.94 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 17.55 | 101.65 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.38 | 166.80 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 259.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 50.38 | 124.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 29.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 141.71 | 267.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.34 | 92.18 | 130.15 | 78.90 | 911.90 | 0.00 | 0.00 | 0.00 |
February | 353.32 | 151.95 | 201.37 | 191.77 | 740.79 | 0.00 | 0.00 | 0.00 |
March | 480.26 | 241.44 | 238.82 | 353.27 | 584.14 | 0.00 | 0.00 | 0.00 |
April | 661.43 | 356.59 | 304.84 | 644.95 | 365.48 | 0.00 | 0.00 | 0.00 |
May | 718.37 | 316.83 | 401.53 | 852.67 | 188.32 | 0.00 | 0.00 | 0.00 |
June | 810.58 | 387.70 | 422.89 | 1055.04 | 128.28 | 0.00 | 0.00 | 0.00 |
July | 795.75 | 374.36 | 421.39 | 1073.77 | 110.27 | 0.00 | 0.00 | 0.00 |
August | 612.52 | 267.68 | 344.83 | 801.82 | 130.33 | 0.00 | 0.00 | 0.00 |
September | 491.82 | 220.68 | 271.14 | 559.82 | 219.91 | 0.00 | 0.00 | 0.00 |
October | 296.11 | 111.34 | 184.77 | 236.93 | 361.25 | 0.00 | 0.00 | 0.00 |
November | 189.68 | 63.17 | 126.51 | 84.59 | 579.67 | 0.00 | 0.00 | 0.00 |
December | 174.39 | 65.46 | 108.93 | 48.68 | 896.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.36 | 220.95 | 263.40 | 500.08 | 433.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 174.39 | 63.17 | 108.93 | 48.68 | 110.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.58 | 387.70 | 422.89 | 1073.77 | 911.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 154.69 | 212.74 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 217.59 | 182.93 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 199.47 | 152.60 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 203.32 | 102.26 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 203.30 | 54.25 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 196.01 | 36.24 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 225.89 | 30.87 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 227.27 | 35.71 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 214.24 | 60.37 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 163.57 | 95.68 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 119.89 | 143.77 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 108.42 | 210.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 185.91 | 109.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 108.42 | 30.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 227.27 | 212.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.49 | 0.00 | 34.49 | 0.02 | 363.52 | 0.00 | 0.00 | 0.00 |
February | 52.98 | 0.00 | 52.98 | 1.46 | 296.34 | 0.00 | 0.00 | 0.00 |
March | 65.20 | 0.00 | 65.20 | 6.09 | 226.76 | 0.00 | 0.00 | 0.00 |
April | 85.74 | 0.88 | 84.86 | 33.77 | 131.78 | 0.00 | 0.00 | 0.00 |
May | 120.24 | 6.38 | 113.86 | 103.65 | 62.67 | 0.00 | 0.00 | 0.00 |
June | 134.38 | 14.95 | 119.43 | 146.17 | 41.05 | 0.00 | 0.00 | 0.00 |
July | 128.47 | 11.28 | 117.20 | 146.57 | 37.45 | 0.00 | 0.00 | 0.00 |
August | 97.56 | 1.86 | 95.70 | 99.39 | 45.82 | 0.00 | 0.00 | 0.00 |
September | 75.96 | 0.08 | 75.88 | 54.61 | 79.72 | 0.00 | 0.00 | 0.00 |
October | 52.65 | 0.00 | 52.65 | 15.03 | 133.28 | 0.00 | 0.00 | 0.00 |
November | 34.86 | 0.00 | 34.86 | 1.85 | 220.52 | 0.00 | 0.00 | 0.00 |
December | 29.23 | 0.00 | 29.23 | 0.00 | 350.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.10 | 2.97 | 73.13 | 51.03 | 165.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.23 | 0.00 | 29.23 | 0.00 | 37.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.38 | 14.95 | 119.43 | 146.57 | 363.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 0.00 | 30.86 | 0.02 | 325.20 | 0.00 | 0.00 | 0.00 |
February | 47.40 | 0.00 | 47.40 | 1.31 | 265.13 | 0.00 | 0.00 | 0.00 |
March | 58.34 | 0.00 | 58.33 | 5.45 | 202.88 | 0.00 | 0.00 | 0.00 |
April | 76.71 | 0.79 | 75.92 | 30.22 | 117.91 | 0.00 | 0.00 | 0.00 |
May | 107.58 | 5.71 | 101.88 | 92.74 | 56.07 | 0.00 | 0.00 | 0.00 |
June | 120.23 | 13.38 | 106.85 | 130.78 | 36.73 | 0.00 | 0.00 | 0.00 |
July | 114.95 | 10.09 | 104.86 | 131.14 | 33.51 | 0.00 | 0.00 | 0.00 |
August | 87.28 | 1.66 | 85.62 | 88.93 | 41.00 | 0.00 | 0.00 | 0.00 |
September | 67.96 | 0.07 | 67.89 | 48.86 | 71.33 | 0.00 | 0.00 | 0.00 |
October | 47.11 | 0.00 | 47.11 | 13.45 | 119.25 | 0.00 | 0.00 | 0.00 |
November | 31.19 | 0.00 | 31.19 | 1.65 | 197.29 | 0.00 | 0.00 | 0.00 |
December | 26.15 | 0.00 | 26.15 | 0.00 | 313.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.08 | 2.65 | 65.43 | 45.66 | 147.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.15 | 0.00 | 26.15 | 0.00 | 33.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 13.38 | 106.85 | 131.14 | 325.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 705.25 | 491.51 | 213.74 | 552.47 | 840.90 | 0.00 | 0.00 | 0.00 |
February | 880.48 | 592.41 | 288.06 | 784.30 | 709.78 | 0.00 | 0.00 | 0.00 |
March | 773.94 | 487.14 | 286.81 | 715.78 | 585.25 | 0.00 | 0.00 | 0.00 |
April | 706.89 | 383.25 | 323.64 | 720.89 | 381.85 | 0.00 | 0.00 | 0.00 |
May | 605.09 | 213.48 | 391.61 | 685.53 | 203.57 | 0.00 | 0.00 | 0.00 |
June | 531.68 | 140.07 | 391.60 | 647.28 | 133.53 | 0.00 | 0.00 | 0.00 |
July | 585.00 | 186.15 | 398.85 | 746.64 | 119.91 | 0.00 | 0.00 | 0.00 |
August | 620.74 | 258.06 | 362.68 | 766.45 | 140.63 | 0.00 | 0.00 | 0.00 |
September | 654.70 | 342.53 | 312.17 | 740.81 | 231.86 | 0.00 | 0.00 | 0.00 |
October | 582.15 | 347.05 | 235.10 | 575.40 | 362.74 | 0.00 | 0.00 | 0.00 |
November | 508.49 | 318.84 | 189.64 | 427.73 | 550.43 | 0.00 | 0.00 | 0.00 |
December | 541.69 | 355.41 | 186.27 | 385.18 | 829.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.82 | 341.46 | 298.37 | 644.69 | 422.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.49 | 140.07 | 186.27 | 385.18 | 119.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 880.48 | 592.41 | 398.85 | 784.30 | 840.90 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255906E+10 | 0.178349E+10 | 0.775570E+09 | 0.204815E+10 | 0.277725E+10 |
February | 0.288571E+10 | 0.194160E+10 | 0.944108E+09 | 0.260790E+10 | 0.214771E+10 |
March | 0.280832E+10 | 0.176763E+10 | 0.104070E+10 | 0.260940E+10 | 0.197606E+10 |
April | 0.248228E+10 | 0.134581E+10 | 0.113646E+10 | 0.253596E+10 | 0.125205E+10 |
May | 0.219561E+10 | 0.774627E+09 | 0.142098E+10 | 0.251157E+10 | 0.669926E+09 |
June | 0.186699E+10 | 0.491871E+09 | 0.137512E+10 | 0.230585E+10 | 0.412159E+09 |
July | 0.212271E+10 | 0.675472E+09 | 0.144724E+10 | 0.273084E+10 | 0.386214E+09 |
August | 0.225239E+10 | 0.936387E+09 | 0.131600E+10 | 0.279873E+10 | 0.453939E+09 |
September | 0.229900E+10 | 0.120281E+10 | 0.109620E+10 | 0.261170E+10 | 0.743610E+09 |
October | 0.211236E+10 | 0.125929E+10 | 0.853077E+09 | 0.209453E+10 | 0.122822E+10 |
November | 0.178557E+10 | 0.111964E+10 | 0.665932E+09 | 0.152519E+10 | 0.177517E+10 |
December | 0.196556E+10 | 0.128965E+10 | 0.675911E+09 | 0.144075E+10 | 0.272015E+10 |
Annual Sum or Average | 0.273356E+11 | 0.145883E+11 | 0.127473E+11 | 0.278206E+11 | 0.165424E+11 |
Minimum of Months | 0.178557E+10 | 0.491871E+09 | 0.665932E+09 | 0.144075E+10 | 0.386214E+09 |
Maximum of Months | 0.288571E+10 | 0.194160E+10 | 0.144724E+10 | 0.279873E+10 | 0.277725E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.720613E+10 | 0.502218E+10 | 0.218395E+10 | 0.572104E+10 | 0.789928E+10 |
February | 0.812596E+10 | 0.546742E+10 | 0.265854E+10 | 0.728160E+10 | 0.612071E+10 |
March | 0.790805E+10 | 0.497752E+10 | 0.293053E+10 | 0.728167E+10 | 0.567693E+10 |
April | 0.698993E+10 | 0.378972E+10 | 0.320021E+10 | 0.706419E+10 | 0.367818E+10 |
May | 0.618268E+10 | 0.218130E+10 | 0.400138E+10 | 0.696161E+10 | 0.204821E+10 |
June | 0.525733E+10 | 0.138508E+10 | 0.387226E+10 | 0.637178E+10 | 0.130143E+10 |
July | 0.597742E+10 | 0.190208E+10 | 0.407534E+10 | 0.758510E+10 | 0.120944E+10 |
August | 0.634258E+10 | 0.263680E+10 | 0.370578E+10 | 0.778187E+10 | 0.144005E+10 |
September | 0.647384E+10 | 0.338702E+10 | 0.308682E+10 | 0.726268E+10 | 0.228772E+10 |
October | 0.594828E+10 | 0.354607E+10 | 0.240221E+10 | 0.583007E+10 | 0.363181E+10 |
November | 0.502804E+10 | 0.315282E+10 | 0.187522E+10 | 0.424732E+10 | 0.509837E+10 |
December | 0.553489E+10 | 0.363157E+10 | 0.190332E+10 | 0.401770E+10 | 0.772983E+10 |
Annual Sum or Average | 0.769751E+11 | 0.410796E+11 | 0.358956E+11 | 0.774066E+11 | 0.481220E+11 |
Minimum of Months | 0.502804E+10 | 0.138508E+10 | 0.187522E+10 | 0.401770E+10 | 0.120944E+10 |
Maximum of Months | 0.812596E+10 | 0.546742E+10 | 0.407534E+10 | 0.778187E+10 | 0.789928E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936118E+10 | 0.652410E+10 | 0.283708E+10 | 0.752878E+10 | 0.106506E+11 |
February | 0.105561E+11 | 0.710249E+10 | 0.345360E+10 | 0.962526E+10 | 0.824475E+10 |
March | 0.102730E+11 | 0.646608E+10 | 0.380693E+10 | 0.963302E+10 | 0.767491E+10 |
April | 0.908032E+10 | 0.492306E+10 | 0.415725E+10 | 0.933538E+10 | 0.502422E+10 |
May | 0.803166E+10 | 0.283363E+10 | 0.519802E+10 | 0.918202E+10 | 0.280510E+10 |
June | 0.682958E+10 | 0.179929E+10 | 0.503028E+10 | 0.839825E+10 | 0.179221E+10 |
July | 0.776501E+10 | 0.247092E+10 | 0.529410E+10 | 0.100159E+11 | 0.163668E+10 |
August | 0.823937E+10 | 0.342536E+10 | 0.481402E+10 | 0.102619E+11 | 0.195458E+10 |
September | 0.840988E+10 | 0.439993E+10 | 0.400995E+10 | 0.955508E+10 | 0.314668E+10 |
October | 0.772715E+10 | 0.460654E+10 | 0.312061E+10 | 0.765017E+10 | 0.501129E+10 |
November | 0.653171E+10 | 0.409570E+10 | 0.243602E+10 | 0.558571E+10 | 0.699036E+10 |
December | 0.719013E+10 | 0.471761E+10 | 0.247252E+10 | 0.526784E+10 | 0.104776E+11 |
Annual Sum or Average | 0.999951E+11 | 0.533647E+11 | 0.466304E+11 | 0.102039E+12 | 0.654089E+11 |
Minimum of Months | 0.653171E+10 | 0.179929E+10 | 0.243602E+10 | 0.526784E+10 | 0.163668E+10 |
Maximum of Months | 0.105561E+11 | 0.710249E+10 | 0.529410E+10 | 0.102619E+11 | 0.106506E+11 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.405121E+09 | 0.582069E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.517802E+09 | 0.440526E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.520553E+09 | 0.400641E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.503172E+09 | 0.253947E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.491790E+09 | 0.138946E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.450444E+09 | 86144857.29 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.536439E+09 | 79156404.61 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.550235E+09 | 93530068.69 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.515919E+09 | 0.150609E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.418680E+09 | 0.243681E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.305326E+09 | 0.356753E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.284696E+09 | 0.566400E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.550018E+10 | 0.339240E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.284696E+09 | 79156404.61 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.550235E+09 | 0.582069E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.113196E+09 | 0.126423E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.265362E+09 | 0.924107E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.484650E+09 | 0.792709E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.731407E+09 | 0.465619E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.112554E+10 | 0.247850E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.112317E+10 | 0.154361E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.128453E+10 | 0.142519E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.101620E+10 | 0.170372E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.675786E+09 | 0.277614E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.335345E+09 | 0.472732E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.116050E+09 | 0.734756E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 60006851.28 | 0.122386E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.733125E+10 | 0.687073E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 60006851.28 | 0.142519E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.128453E+10 | 0.126423E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 197093.98 | 0.729820E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 5202902.90 | 0.528912E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 18364999.22 | 0.447766E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 75662286.49 | 0.253967E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.220258E+09 | 0.123529E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.300004E+09 | 77379875.52 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.310748E+09 | 71807770.74 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.211689E+09 | 87685865.54 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.116942E+09 | 0.150492E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 39894626.65 | 0.259089E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 5346902.54 | 0.412295E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 0.698884E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.130431E+10 | 0.384163E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 71807770.74 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.310748E+09 | 0.729820E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.117221E+09 | 0.125615E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.275286E+09 | 0.915192E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.497354E+09 | 0.783873E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.746120E+09 | 0.460507E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.113345E+10 | 0.245773E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.112690E+10 | 0.153300E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.128931E+10 | 0.140947E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.102417E+10 | 0.167274E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.687361E+09 | 0.273403E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.345975E+09 | 0.466970E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.122446E+09 | 0.728421E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 62425435.43 | 0.121849E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.742802E+10 | 0.681030E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 62425435.43 | 0.140947E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.128931E+10 | 0.125615E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.404696E+09 | 0.282045E+09 | 0.122651E+09 | 0.321584E+09 | 0.456874E+09 |
February | 0.456353E+09 | 0.307049E+09 | 0.149304E+09 | 0.411102E+09 | 0.349259E+09 |
March | 0.444116E+09 | 0.279536E+09 | 0.164579E+09 | 0.413478E+09 | 0.320586E+09 |
April | 0.392555E+09 | 0.212830E+09 | 0.179725E+09 | 0.399303E+09 | 0.210757E+09 |
May | 0.347220E+09 | 0.122501E+09 | 0.224719E+09 | 0.391995E+09 | 0.119060E+09 |
June | 0.295253E+09 | 77785603.32 | 0.217467E+09 | 0.361082E+09 | 74183088.58 |
July | 0.335693E+09 | 0.106821E+09 | 0.228873E+09 | 0.432234E+09 | 67200025.21 |
August | 0.356200E+09 | 0.148082E+09 | 0.208118E+09 | 0.440519E+09 | 81099903.96 |
September | 0.363571E+09 | 0.190214E+09 | 0.173356E+09 | 0.408385E+09 | 0.133295E+09 |
October | 0.334055E+09 | 0.199146E+09 | 0.134908E+09 | 0.331024E+09 | 0.203366E+09 |
November | 0.282374E+09 | 0.177062E+09 | 0.105312E+09 | 0.242693E+09 | 0.279966E+09 |
December | 0.310839E+09 | 0.203948E+09 | 0.106891E+09 | 0.226451E+09 | 0.442218E+09 |
Annual Sum or Average | 0.432292E+10 | 0.230702E+10 | 0.201590E+10 | 0.437985E+10 | 0.273786E+10 |
Minimum of Months | 0.282374E+09 | 77785603.32 | 0.105312E+09 | 0.226451E+09 | 67200025.21 |
Maximum of Months | 0.456353E+09 | 0.307049E+09 | 0.228873E+09 | 0.440519E+09 | 0.456874E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58367319.83 | 0.00 | 58367319.83 | 102373.11 | 0.598400E+09 |
February | 80980322.72 | 0.00 | 80980322.72 | 3600115.84 | 0.434016E+09 |
March | 0.110332E+09 | 4218.19 | 0.110328E+09 | 14130125.49 | 0.365382E+09 |
April | 0.140402E+09 | 1442095.54 | 0.138960E+09 | 63895804.02 | 0.204169E+09 |
May | 0.203471E+09 | 10794416.27 | 0.192676E+09 | 0.189727E+09 | 95123573.86 |
June | 0.220055E+09 | 24482516.34 | 0.195573E+09 | 0.254565E+09 | 57944507.69 |
July | 0.217397E+09 | 19083501.21 | 0.198313E+09 | 0.265551E+09 | 51708950.56 |
August | 0.165078E+09 | 3140560.24 | 0.161937E+09 | 0.183273E+09 | 64193611.74 |
September | 0.124382E+09 | 128388.17 | 0.124253E+09 | 0.100024E+09 | 0.116927E+09 |
October | 89098491.50 | 0.00 | 89098491.50 | 31290605.39 | 0.212520E+09 |
November | 57091439.30 | 0.00 | 57091439.30 | 3684989.17 | 0.342997E+09 |
December | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.574379E+09 |
Annual Sum or Average | 0.151611E+10 | 59075695.98 | 0.145703E+10 | 0.110984E+10 | 0.311776E+10 |
Minimum of Months | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 51708950.56 |
Maximum of Months | 0.220055E+09 | 24482516.34 | 0.198313E+09 | 0.265551E+09 | 0.598400E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297774E+09 | 0.123462E+09 | 0.174311E+09 | 92748787.18 | 0.124678E+10 |
February | 0.427402E+09 | 0.183814E+09 | 0.243589E+09 | 0.219405E+09 | 0.893206E+09 |
March | 0.643204E+09 | 0.323358E+09 | 0.319845E+09 | 0.450792E+09 | 0.766963E+09 |
April | 0.857276E+09 | 0.462179E+09 | 0.395098E+09 | 0.785198E+09 | 0.445248E+09 |
May | 0.962106E+09 | 0.424335E+09 | 0.537771E+09 | 0.104275E+10 | 0.229151E+09 |
June | 0.105059E+10 | 0.502492E+09 | 0.548099E+09 | 0.125280E+10 | 0.146131E+09 |
July | 0.106574E+10 | 0.501379E+09 | 0.564361E+09 | 0.130218E+10 | 0.133133E+09 |
August | 0.820339E+09 | 0.358507E+09 | 0.461832E+09 | 0.961507E+09 | 0.161020E+09 |
September | 0.637450E+09 | 0.286023E+09 | 0.351427E+09 | 0.652266E+09 | 0.266064E+09 |
October | 0.396582E+09 | 0.149118E+09 | 0.247464E+09 | 0.287131E+09 | 0.460215E+09 |
November | 0.245847E+09 | 81876671.53 | 0.163970E+09 | 0.102206E+09 | 0.722647E+09 |
December | 0.233566E+09 | 87671849.66 | 0.145894E+09 | 57717394.16 | 0.121135E+10 |
Annual Sum or Average | 0.763788E+10 | 0.348422E+10 | 0.415366E+10 | 0.720670E+10 | 0.668190E+10 |
Minimum of Months | 0.233566E+09 | 81876671.53 | 0.145894E+09 | 57717394.16 | 0.133133E+09 |
Maximum of Months | 0.106574E+10 | 0.502492E+09 | 0.564361E+09 | 0.130218E+10 | 0.124678E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.404628E+09 | 0.581186E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.516999E+09 | 0.439515E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.517242E+09 | 0.399113E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.499048E+09 | 0.251917E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.491115E+09 | 0.134600E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.446837E+09 | 82797318.31 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.533319E+09 | 74870686.58 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.549854E+09 | 89192023.11 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.515565E+09 | 0.147099E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.418249E+09 | 0.242226E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.305023E+09 | 0.356282E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.284180E+09 | 0.565953E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.548206E+10 | 0.336475E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.284180E+09 | 74870686.58 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.549854E+09 | 0.581186E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 197713.58 | 0.729250E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 4976075.37 | 0.528533E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 16789398.88 | 0.447343E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 71946355.79 | 0.253810E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.220826E+09 | 0.121225E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.297058E+09 | 75149187.31 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.308675E+09 | 68842001.57 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.211692E+09 | 84269327.68 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.115711E+09 | 0.147277E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 38977453.51 | 0.257239E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 5229842.83 | 0.412295E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 0.698410E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.129208E+10 | 0.382364E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 68842001.57 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.308675E+09 | 0.729250E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297774E+09 | 0.123462E+09 | 0.174311E+09 | 95160382.86 | 0.123677E+10 |
February | 0.427402E+09 | 0.183814E+09 | 0.243589E+09 | 0.225942E+09 | 0.880787E+09 |
March | 0.643204E+09 | 0.323358E+09 | 0.319845E+09 | 0.460939E+09 | 0.754298E+09 |
April | 0.857276E+09 | 0.462179E+09 | 0.395098E+09 | 0.796844E+09 | 0.439492E+09 |
May | 0.962106E+09 | 0.424335E+09 | 0.537771E+09 | 0.104939E+10 | 0.226988E+09 |
June | 0.105059E+10 | 0.502492E+09 | 0.548099E+09 | 0.125618E+10 | 0.145249E+09 |
July | 0.106574E+10 | 0.501379E+09 | 0.564361E+09 | 0.130684E+10 | 0.131696E+09 |
August | 0.820339E+09 | 0.358507E+09 | 0.461832E+09 | 0.968744E+09 | 0.157997E+09 |
September | 0.637450E+09 | 0.286023E+09 | 0.351427E+09 | 0.661689E+09 | 0.261552E+09 |
October | 0.396582E+09 | 0.149118E+09 | 0.247464E+09 | 0.296507E+09 | 0.453115E+09 |
November | 0.245847E+09 | 81876671.53 | 0.163970E+09 | 0.105259E+09 | 0.713368E+09 |
December | 0.233566E+09 | 87671849.66 | 0.145894E+09 | 59064688.95 | 0.120428E+10 |
Annual Sum or Average | 0.763788E+10 | 0.348422E+10 | 0.415366E+10 | 0.728256E+10 | 0.660559E+10 |
Minimum of Months | 0.233566E+09 | 81876671.53 | 0.145894E+09 | 59064688.95 | 0.131696E+09 |
Maximum of Months | 0.106574E+10 | 0.502492E+09 | 0.564361E+09 | 0.130684E+10 | 0.123677E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92385913.46 | 0.00 | 92385913.46 | 85982.98 | 0.970325E+09 |
February | 0.128179E+09 | 0.00 | 0.128179E+09 | 4205738.43 | 0.707884E+09 |
March | 0.174638E+09 | 6676.71 | 0.174632E+09 | 19130119.90 | 0.596656E+09 |
April | 0.222233E+09 | 2282601.20 | 0.219950E+09 | 94543013.46 | 0.335825E+09 |
May | 0.322061E+09 | 17085794.07 | 0.304975E+09 | 0.288575E+09 | 0.165398E+09 |
June | 0.348311E+09 | 38751815.96 | 0.309560E+09 | 0.388813E+09 | 0.105070E+09 |
July | 0.344104E+09 | 30206058.75 | 0.313897E+09 | 0.400940E+09 | 99698420.11 |
August | 0.261291E+09 | 4970992.81 | 0.256320E+09 | 0.274288E+09 | 0.121349E+09 |
September | 0.196876E+09 | 203217.46 | 0.196673E+09 | 0.148494E+09 | 0.204127E+09 |
October | 0.141028E+09 | 0.00 | 0.141028E+09 | 45266042.29 | 0.348910E+09 |
November | 90366403.43 | 0.00 | 90366403.43 | 5335203.11 | 0.559976E+09 |
December | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 0.932721E+09 |
Annual Sum or Average | 0.239975E+10 | 93507156.96 | 0.230624E+10 | 0.166968E+10 | 0.514794E+10 |
Minimum of Months | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 99698420.11 |
Maximum of Months | 0.348311E+09 | 38751815.96 | 0.313897E+09 | 0.400940E+09 | 0.970325E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34057273.10 | 0.00 | 34057273.10 | 31696.89 | 0.357702E+09 |
February | 47251937.81 | 0.00 | 47251937.81 | 1550409.33 | 0.260955E+09 |
March | 64378875.70 | 2461.31 | 64376414.39 | 7052154.31 | 0.219952E+09 |
April | 81924229.66 | 841461.32 | 81082768.34 | 34852469.48 | 0.123799E+09 |
May | 0.118725E+09 | 6298531.16 | 0.112426E+09 | 0.106381E+09 | 60972476.07 |
June | 0.128402E+09 | 14285523.95 | 0.114116E+09 | 0.143333E+09 | 38733145.09 |
July | 0.126851E+09 | 11135203.99 | 0.115716E+09 | 0.147803E+09 | 36752965.84 |
August | 96322837.24 | 1832513.78 | 94490323.46 | 0.101114E+09 | 44734405.27 |
September | 72576611.07 | 74914.37 | 72501696.70 | 54740923.47 | 75249828.92 |
October | 51988881.22 | 0.00 | 51988881.22 | 16686937.51 | 0.128623E+09 |
November | 33312798.08 | 0.00 | 33312798.08 | 1966776.78 | 0.206430E+09 |
December | 28856024.80 | 0.00 | 28856024.80 | 0.00 | 0.343839E+09 |
Annual Sum or Average | 0.884647E+09 | 34470609.88 | 0.850177E+09 | 0.615512E+09 | 0.189774E+10 |
Minimum of Months | 28856024.80 | 0.00 | 28856024.80 | 0.00 | 36752965.84 |
Maximum of Months | 0.128402E+09 | 14285523.95 | 0.115716E+09 | 0.147803E+09 | 0.357702E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236084E+09 | 0.164534E+09 | 71549800.91 | 0.186440E+09 | 0.280653E+09 |
February | 0.266219E+09 | 0.179120E+09 | 87098230.94 | 0.240191E+09 | 0.212761E+09 |
March | 0.259080E+09 | 0.163071E+09 | 96009120.53 | 0.242823E+09 | 0.193345E+09 |
April | 0.229001E+09 | 0.124157E+09 | 0.104844E+09 | 0.237250E+09 | 0.121886E+09 |
May | 0.202555E+09 | 71462483.28 | 0.131092E+09 | 0.233972E+09 | 67058946.51 |
June | 0.172239E+09 | 45377083.81 | 0.126862E+09 | 0.213703E+09 | 42597927.81 |
July | 0.195830E+09 | 62315011.60 | 0.133515E+09 | 0.253611E+09 | 39865480.30 |
August | 0.207793E+09 | 86385450.33 | 0.121408E+09 | 0.260415E+09 | 46401632.99 |
September | 0.212093E+09 | 0.110964E+09 | 0.101129E+09 | 0.243518E+09 | 74080326.93 |
October | 0.194875E+09 | 0.116174E+09 | 78700257.98 | 0.195853E+09 | 0.118888E+09 |
November | 0.164726E+09 | 0.103291E+09 | 61435163.42 | 0.140882E+09 | 0.175060E+09 |
December | 0.181331E+09 | 0.118975E+09 | 62355771.56 | 0.130295E+09 | 0.275555E+09 |
Annual Sum or Average | 0.252183E+10 | 0.134583E+10 | 0.117600E+10 | 0.257895E+10 | 0.164815E+10 |
Minimum of Months | 0.164726E+09 | 45377083.81 | 61435163.42 | 0.130295E+09 | 39865480.30 |
Maximum of Months | 0.266219E+09 | 0.179120E+09 | 0.133515E+09 | 0.260415E+09 | 0.280653E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.640779E+09 | 0.446578E+09 | 0.194201E+09 | 0.506036E+09 | 0.761748E+09 |
February | 0.722572E+09 | 0.486170E+09 | 0.236402E+09 | 0.651928E+09 | 0.577477E+09 |
March | 0.703195E+09 | 0.442607E+09 | 0.260588E+09 | 0.659071E+09 | 0.524779E+09 |
April | 0.621556E+09 | 0.336987E+09 | 0.284569E+09 | 0.643946E+09 | 0.330823E+09 |
May | 0.549775E+09 | 0.193964E+09 | 0.355811E+09 | 0.635049E+09 | 0.182012E+09 |
June | 0.467492E+09 | 0.123163E+09 | 0.344329E+09 | 0.580034E+09 | 0.115619E+09 |
July | 0.531524E+09 | 0.169136E+09 | 0.362388E+09 | 0.688351E+09 | 0.108203E+09 |
August | 0.563993E+09 | 0.234468E+09 | 0.329525E+09 | 0.706820E+09 | 0.125944E+09 |
September | 0.575664E+09 | 0.301178E+09 | 0.274486E+09 | 0.660958E+09 | 0.201069E+09 |
October | 0.528929E+09 | 0.315321E+09 | 0.213609E+09 | 0.531584E+09 | 0.322687E+09 |
November | 0.447101E+09 | 0.280353E+09 | 0.166748E+09 | 0.382382E+09 | 0.475147E+09 |
December | 0.492170E+09 | 0.322923E+09 | 0.169246E+09 | 0.353648E+09 | 0.747913E+09 |
Annual Sum or Average | 0.684475E+10 | 0.365285E+10 | 0.319190E+10 | 0.699981E+10 | 0.447342E+10 |
Minimum of Months | 0.447101E+09 | 0.123163E+09 | 0.166748E+09 | 0.353648E+09 | 0.108203E+09 |
Maximum of Months | 0.722572E+09 | 0.486170E+09 | 0.362388E+09 | 0.706820E+09 | 0.761748E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.403349E+09 | 0.584073E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.515322E+09 | 0.441380E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.518733E+09 | 0.400921E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.500549E+09 | 0.254075E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.487802E+09 | 0.140376E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.446808E+09 | 87420882.94 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.532889E+09 | 80218094.89 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.546454E+09 | 95014990.20 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.513057E+09 | 0.150998E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.417561E+09 | 0.242723E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.304422E+09 | 0.356495E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.283213E+09 | 0.568694E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.547016E+10 | 0.340239E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.283213E+09 | 80218094.89 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.546454E+09 | 0.584073E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.112041E+09 | 0.126974E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.263426E+09 | 0.927121E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.481911E+09 | 0.793446E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.725741E+09 | 0.465294E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.111653E+10 | 0.248991E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.111460E+10 | 0.155499E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.127589E+10 | 0.143417E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.100867E+10 | 0.172097E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.670636E+09 | 0.277381E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.334002E+09 | 0.470678E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.115847E+09 | 0.734661E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 59288668.14 | 0.123040E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.727859E+10 | 0.688872E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 59288668.14 | 0.143417E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.127589E+10 | 0.126974E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 198278.03 | 0.731872E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 5310668.43 | 0.530411E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 18310336.19 | 0.448724E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 75248726.26 | 0.254213E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.217024E+09 | 0.124356E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.296783E+09 | 78135691.87 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.308092E+09 | 72465083.92 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.209706E+09 | 88489415.00 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.116626E+09 | 0.150298E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 40594859.05 | 0.257456E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 5533759.70 | 0.411774E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 0.701471E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.129343E+10 | 0.384966E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 72465083.92 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.308092E+09 | 0.731872E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.116062E+09 | 0.126094E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.273323E+09 | 0.918329E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.494986E+09 | 0.784730E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.741634E+09 | 0.459804E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.112495E+10 | 0.246739E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.111858E+10 | 0.154417E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.128100E+10 | 0.141782E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.101727E+10 | 0.168564E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.683663E+09 | 0.272351E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.345877E+09 | 0.464031E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.122394E+09 | 0.728620E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 61734690.89 | 0.122455E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.738148E+10 | 0.682485E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 61734690.89 | 0.141782E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.128100E+10 | 0.126094E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742054E+09 | 0.517160E+09 | 0.224894E+09 | 0.570855E+09 | 0.878323E+09 |
February | 0.836774E+09 | 0.563008E+09 | 0.273766E+09 | 0.733656E+09 | 0.665109E+09 |
March | 0.814335E+09 | 0.512561E+09 | 0.301774E+09 | 0.743333E+09 | 0.602344E+09 |
April | 0.719792E+09 | 0.390247E+09 | 0.329545E+09 | 0.724984E+09 | 0.376192E+09 |
May | 0.636666E+09 | 0.224620E+09 | 0.412047E+09 | 0.720595E+09 | 0.197688E+09 |
June | 0.541379E+09 | 0.142628E+09 | 0.398750E+09 | 0.665726E+09 | 0.119746E+09 |
July | 0.615530E+09 | 0.195867E+09 | 0.419663E+09 | 0.793435E+09 | 0.107553E+09 |
August | 0.653132E+09 | 0.271525E+09 | 0.381606E+09 | 0.806892E+09 | 0.131943E+09 |
September | 0.666647E+09 | 0.348779E+09 | 0.317868E+09 | 0.748766E+09 | 0.220821E+09 |
October | 0.612526E+09 | 0.365157E+09 | 0.247369E+09 | 0.601487E+09 | 0.366267E+09 |
November | 0.517764E+09 | 0.324662E+09 | 0.193102E+09 | 0.431933E+09 | 0.539459E+09 |
December | 0.569956E+09 | 0.373961E+09 | 0.195996E+09 | 0.399984E+09 | 0.854609E+09 |
Annual Sum or Average | 0.792655E+10 | 0.423018E+10 | 0.369638E+10 | 0.794165E+10 | 0.506005E+10 |
Minimum of Months | 0.517764E+09 | 0.142628E+09 | 0.193102E+09 | 0.399984E+09 | 0.107553E+09 |
Maximum of Months | 0.836774E+09 | 0.563008E+09 | 0.419663E+09 | 0.806892E+09 | 0.878323E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510627E+09 | 0.00 | 0.510627E+09 | 132186.18 | 0.551635E+10 |
February | 0.708457E+09 | 0.00 | 0.708457E+09 | 14700685.36 | 0.413081E+10 |
March | 0.965244E+09 | 36902.88 | 0.965208E+09 | 74212507.86 | 0.358660E+10 |
April | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.426707E+09 | 0.209311E+10 |
May | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.146023E+10 | 0.100167E+10 |
June | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.203634E+10 | 0.628005E+09 |
July | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.214614E+10 | 0.568799E+09 |
August | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.143367E+10 | 0.719956E+09 |
September | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.726147E+09 | 0.125851E+10 |
October | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.182163E+09 | 0.220443E+10 |
November | 0.499465E+09 | 0.00 | 0.499465E+09 | 18951968.14 | 0.342968E+10 |
December | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.536482E+10 |
Annual Sum or Average | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.851939E+10 | 0.305027E+11 |
Minimum of Months | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.568799E+09 |
Maximum of Months | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.214614E+10 | 0.551635E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510627E+09 | 0.00 | 0.510627E+09 | 37175.77 | 0.560471E+10 |
February | 0.708457E+09 | 0.00 | 0.708457E+09 | 11797800.83 | 0.421254E+10 |
March | 0.965244E+09 | 36902.88 | 0.965208E+09 | 65521127.62 | 0.366677E+10 |
April | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.403182E+09 | 0.214173E+10 |
May | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.143151E+10 | 0.102218E+10 |
June | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.201021E+10 | 0.642623E+09 |
July | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.212321E+10 | 0.582091E+09 |
August | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.141054E+10 | 0.739183E+09 |
September | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.702410E+09 | 0.128829E+10 |
October | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.166028E+09 | 0.226026E+10 |
November | 0.499465E+09 | 0.00 | 0.499465E+09 | 16693613.84 | 0.351552E+10 |
December | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.545552E+10 |
Annual Sum or Average | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.834114E+10 | 0.311314E+11 |
Minimum of Months | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.582091E+09 |
Maximum of Months | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.212321E+10 | 0.560471E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 175091.75 | 0.716108E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 4549716.68 | 0.534539E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 19230997.66 | 0.459400E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 87604257.33 | 0.269823E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.270673E+09 | 0.135011E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.358591E+09 | 87939211.12 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.379568E+09 | 78655522.91 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.268312E+09 | 93486197.86 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.146778E+09 | 0.157964E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 46994995.91 | 0.272252E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 6163629.27 | 0.432337E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 0.694314E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.158864E+10 | 0.393183E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 0.00 | 78655522.91 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.379568E+09 | 0.716108E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.595505E+09 | 0.246907E+09 | 0.348598E+09 | 0.211332E+09 | 0.244242E+10 |
February | 0.854744E+09 | 0.367601E+09 | 0.487143E+09 | 0.463925E+09 | 0.179212E+10 |
March | 0.128632E+10 | 0.646670E+09 | 0.639645E+09 | 0.946192E+09 | 0.156456E+10 |
April | 0.171443E+10 | 0.924292E+09 | 0.790139E+09 | 0.167171E+10 | 0.947326E+09 |
May | 0.192408E+10 | 0.848610E+09 | 0.107547E+10 | 0.228380E+10 | 0.504400E+09 |
June | 0.210103E+10 | 0.100491E+10 | 0.109612E+10 | 0.273466E+10 | 0.332511E+09 |
July | 0.213133E+10 | 0.100269E+10 | 0.112864E+10 | 0.287599E+10 | 0.295351E+09 |
August | 0.164056E+10 | 0.716963E+09 | 0.923598E+09 | 0.214760E+10 | 0.349071E+09 |
September | 0.127481E+10 | 0.572005E+09 | 0.702805E+09 | 0.145105E+10 | 0.570005E+09 |
October | 0.793108E+09 | 0.298216E+09 | 0.494892E+09 | 0.634603E+09 | 0.967560E+09 |
November | 0.491659E+09 | 0.163742E+09 | 0.327917E+09 | 0.219253E+09 | 0.150251E+10 |
December | 0.467099E+09 | 0.175331E+09 | 0.291768E+09 | 0.130390E+09 | 0.240104E+10 |
Annual Sum or Average | 0.152747E+11 | 0.696794E+10 | 0.830673E+10 | 0.157705E+11 | 0.136689E+11 |
Minimum of Months | 0.467099E+09 | 0.163742E+09 | 0.291768E+09 | 0.130390E+09 | 0.295351E+09 |
Maximum of Months | 0.213133E+10 | 0.100491E+10 | 0.112864E+10 | 0.287599E+10 | 0.244242E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.414320E+09 | 0.569794E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.526384E+09 | 0.442541E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.534266E+09 | 0.408719E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.527004E+09 | 0.265061E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.544508E+09 | 0.145315E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.508060E+09 | 93927578.45 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.605028E+09 | 82680668.12 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.608732E+09 | 95643108.18 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.555303E+09 | 0.156488E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.438110E+09 | 0.256270E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.310755E+09 | 0.372645E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.290391E+09 | 0.562612E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.586286E+10 | 0.345170E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.290391E+09 | 82680668.12 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.608732E+09 | 0.569794E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92385913.46 | 0.00 | 92385913.46 | 57459.82 | 0.973663E+09 |
February | 0.128179E+09 | 0.00 | 0.128179E+09 | 3535646.18 | 0.716896E+09 |
March | 0.174638E+09 | 6676.71 | 0.174632E+09 | 16316027.57 | 0.607342E+09 |
April | 0.222233E+09 | 2282601.20 | 0.219950E+09 | 87541752.94 | 0.341582E+09 |
May | 0.322061E+09 | 17085794.07 | 0.304975E+09 | 0.277624E+09 | 0.167845E+09 |
June | 0.348311E+09 | 38751815.96 | 0.309560E+09 | 0.378883E+09 | 0.106401E+09 |
July | 0.344104E+09 | 30206058.75 | 0.313897E+09 | 0.392570E+09 | 0.100313E+09 |
August | 0.261291E+09 | 4970992.81 | 0.256320E+09 | 0.266211E+09 | 0.122732E+09 |
September | 0.196876E+09 | 203217.46 | 0.196673E+09 | 0.141549E+09 | 0.206633E+09 |
October | 0.141028E+09 | 0.00 | 0.141028E+09 | 40259143.07 | 0.356987E+09 |
November | 90366403.43 | 0.00 | 90366403.43 | 4787679.31 | 0.571587E+09 |
December | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 0.940039E+09 |
Annual Sum or Average | 0.239975E+10 | 93507156.96 | 0.230624E+10 | 0.160933E+10 | 0.521202E+10 |
Minimum of Months | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 0.100313E+09 |
Maximum of Months | 0.348311E+09 | 38751815.96 | 0.313897E+09 | 0.392570E+09 | 0.973663E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82658026.82 | 0.00 | 82658026.82 | 51409.52 | 0.871013E+09 |
February | 0.114682E+09 | 0.00 | 0.114682E+09 | 3163356.03 | 0.641400E+09 |
March | 0.156249E+09 | 5973.67 | 0.156243E+09 | 14598011.69 | 0.543392E+09 |
April | 0.198833E+09 | 2042251.94 | 0.196790E+09 | 78323938.05 | 0.305615E+09 |
May | 0.288149E+09 | 15286724.70 | 0.272862E+09 | 0.248392E+09 | 0.150172E+09 |
June | 0.311635E+09 | 34671396.57 | 0.276964E+09 | 0.338988E+09 | 95197042.94 |
July | 0.307871E+09 | 27025475.21 | 0.280845E+09 | 0.351233E+09 | 89750319.62 |
August | 0.233778E+09 | 4447566.10 | 0.229331E+09 | 0.238180E+09 | 0.109809E+09 |
September | 0.176146E+09 | 181819.44 | 0.175964E+09 | 0.126645E+09 | 0.184876E+09 |
October | 0.126179E+09 | 0.00 | 0.126179E+09 | 36020007.85 | 0.319398E+09 |
November | 80851163.55 | 0.00 | 80851163.55 | 4283554.82 | 0.511376E+09 |
December | 70034440.66 | 0.00 | 70034440.66 | 0.00 | 0.840971E+09 |
Annual Sum or Average | 0.214707E+10 | 83661207.63 | 0.206340E+10 | 0.143988E+10 | 0.466297E+10 |
Minimum of Months | 70034440.66 | 0.00 | 70034440.66 | 0.00 | 89750319.62 |
Maximum of Months | 0.311635E+09 | 34671396.57 | 0.280845E+09 | 0.351233E+09 | 0.871013E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188894E+10 | 0.131646E+10 | 0.572480E+09 | 0.147974E+10 | 0.225227E+10 |
February | 0.213005E+10 | 0.143317E+10 | 0.696885E+09 | 0.189738E+10 | 0.171710E+10 |
March | 0.207293E+10 | 0.130475E+10 | 0.768182E+09 | 0.191714E+10 | 0.156752E+10 |
April | 0.183227E+10 | 0.993394E+09 | 0.838875E+09 | 0.186854E+10 | 0.989749E+09 |
May | 0.162067E+10 | 0.571781E+09 | 0.104889E+10 | 0.183613E+10 | 0.545238E+09 |
June | 0.137811E+10 | 0.363068E+09 | 0.101504E+10 | 0.167774E+10 | 0.346106E+09 |
July | 0.156686E+10 | 0.498591E+09 | 0.106827E+10 | 0.199980E+10 | 0.321164E+09 |
August | 0.166258E+10 | 0.691182E+09 | 0.971399E+09 | 0.205287E+10 | 0.376660E+09 |
September | 0.169698E+10 | 0.887836E+09 | 0.809149E+09 | 0.192017E+10 | 0.600993E+09 |
October | 0.155922E+10 | 0.929526E+09 | 0.629691E+09 | 0.154116E+10 | 0.971560E+09 |
November | 0.131800E+10 | 0.826446E+09 | 0.491551E+09 | 0.110867E+10 | 0.142671E+10 |
December | 0.145085E+10 | 0.951937E+09 | 0.498917E+09 | 0.103168E+10 | 0.222267E+10 |
Annual Sum or Average | 0.201775E+11 | 0.107681E+11 | 0.940933E+10 | 0.203310E+11 | 0.133377E+11 |
Minimum of Months | 0.131800E+10 | 0.363068E+09 | 0.491551E+09 | 0.103168E+10 | 0.321164E+09 |
Maximum of Months | 0.213005E+10 | 0.143317E+10 | 0.106827E+10 | 0.205287E+10 | 0.225227E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 764.69 | 1036.90 | 955.44 | 665.88 | 289.56 | 0.00 | 0.00 |
February | 1078.00 | 887.78 | 1192.84 | 802.58 | 390.26 | 0.00 | 0.00 |
March | 974.24 | 737.78 | 1048.51 | 659.96 | 388.55 | 0.00 | 0.00 |
April | 978.38 | 483.04 | 957.67 | 519.22 | 438.45 | 0.00 | 0.00 |
May | 937.71 | 250.12 | 819.75 | 289.21 | 530.53 | 0.00 | 0.00 |
June | 889.60 | 159.01 | 720.29 | 189.77 | 530.53 | 0.00 | 0.00 |
July | 1019.58 | 144.20 | 792.53 | 252.19 | 540.34 | 0.00 | 0.00 |
August | 1044.93 | 169.48 | 840.95 | 349.61 | 491.34 | 0.00 | 0.00 |
September | 1007.60 | 286.89 | 886.96 | 464.05 | 422.92 | 0.00 | 0.00 |
October | 782.01 | 458.57 | 788.67 | 470.16 | 318.50 | 0.00 | 0.00 |
November | 588.42 | 684.86 | 688.88 | 431.96 | 256.92 | 0.00 | 0.00 |
December | 537.91 | 1015.59 | 733.86 | 481.50 | 252.36 | 0.00 | 0.00 |
Annual Sum or Average | 882.18 | 524.56 | 866.80 | 462.59 | 404.21 | 0.00 | 0.00 |
Minimum of Months | 537.91 | 144.20 | 688.88 | 189.77 | 252.36 | 0.00 | 0.00 |
Maximum of Months | 1078.00 | 1036.90 | 1192.84 | 802.58 | 540.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2135.99 | 2949.25 | 2690.46 | 1875.07 | 815.40 | 0.00 | 0.00 |
February | 3009.92 | 2530.06 | 3358.95 | 2260.01 | 1098.94 | 0.00 | 0.00 |
March | 2718.66 | 2119.52 | 2952.53 | 1858.39 | 1094.13 | 0.00 | 0.00 |
April | 2725.38 | 1419.05 | 2696.73 | 1462.08 | 1234.65 | 0.00 | 0.00 |
May | 2599.17 | 764.71 | 2308.35 | 814.40 | 1493.95 | 0.00 | 0.00 |
June | 2458.25 | 502.09 | 2028.29 | 534.37 | 1493.93 | 0.00 | 0.00 |
July | 2831.95 | 451.55 | 2231.71 | 710.16 | 1521.56 | 0.00 | 0.00 |
August | 2905.42 | 537.65 | 2368.05 | 984.47 | 1383.58 | 0.00 | 0.00 |
September | 2801.96 | 882.61 | 2497.62 | 1306.72 | 1190.90 | 0.00 | 0.00 |
October | 2176.70 | 1355.96 | 2220.83 | 1323.95 | 896.88 | 0.00 | 0.00 |
November | 1638.63 | 1966.96 | 1939.83 | 1216.37 | 723.46 | 0.00 | 0.00 |
December | 1500.04 | 2885.99 | 2066.49 | 1355.87 | 710.62 | 0.00 | 0.00 |
Annual Sum or Average | 2454.55 | 1525.94 | 2440.87 | 1302.62 | 1138.24 | 0.00 | 0.00 |
Minimum of Months | 1500.04 | 451.55 | 1939.83 | 534.37 | 710.62 | 0.00 | 0.00 |
Maximum of Months | 3009.92 | 2949.25 | 3358.95 | 2260.01 | 1521.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2810.93 | 3976.46 | 3495.06 | 2435.82 | 1059.24 | 0.00 | 0.00 |
February | 3978.70 | 3408.05 | 4363.46 | 2935.88 | 1427.58 | 0.00 | 0.00 |
March | 3596.56 | 2865.48 | 3835.50 | 2414.16 | 1421.34 | 0.00 | 0.00 |
April | 3601.61 | 1938.36 | 3503.21 | 1899.33 | 1603.88 | 0.00 | 0.00 |
May | 3428.17 | 1047.30 | 2998.68 | 1057.96 | 1940.72 | 0.00 | 0.00 |
June | 3240.06 | 691.44 | 2634.87 | 694.17 | 1940.70 | 0.00 | 0.00 |
July | 3739.50 | 611.07 | 2899.12 | 922.53 | 1976.59 | 0.00 | 0.00 |
August | 3831.35 | 729.75 | 3076.23 | 1278.88 | 1797.35 | 0.00 | 0.00 |
September | 3686.37 | 1214.00 | 3244.55 | 1697.51 | 1547.05 | 0.00 | 0.00 |
October | 2856.25 | 1871.00 | 2884.99 | 1719.89 | 1165.10 | 0.00 | 0.00 |
November | 2154.98 | 2696.90 | 2519.95 | 1580.13 | 939.82 | 0.00 | 0.00 |
December | 1966.79 | 3911.88 | 2684.49 | 1761.35 | 923.13 | 0.00 | 0.00 |
Annual Sum or Average | 3235.64 | 2074.10 | 3170.82 | 1692.18 | 1478.64 | 0.00 | 0.00 |
Minimum of Months | 1966.79 | 611.07 | 2519.95 | 694.17 | 923.13 | 0.00 | 0.00 |
Maximum of Months | 3978.70 | 3976.46 | 4363.46 | 2935.88 | 1976.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 151.95 | 647.76 | 303.16 | 180.01 | 123.14 | 0.00 | 0.00 |
February | 295.69 | 536.04 | 420.67 | 243.51 | 177.16 | 0.00 | 0.00 |
March | 360.13 | 430.37 | 449.81 | 254.87 | 194.93 | 0.00 | 0.00 |
April | 470.53 | 271.84 | 498.83 | 259.66 | 239.17 | 0.00 | 0.00 |
May | 601.82 | 142.40 | 542.66 | 239.28 | 303.38 | 0.00 | 0.00 |
June | 605.75 | 91.44 | 508.06 | 195.44 | 312.62 | 0.00 | 0.00 |
July | 678.82 | 81.71 | 547.61 | 231.67 | 315.94 | 0.00 | 0.00 |
August | 583.98 | 97.67 | 487.16 | 214.55 | 272.62 | 0.00 | 0.00 |
September | 457.93 | 163.38 | 427.28 | 204.85 | 222.43 | 0.00 | 0.00 |
October | 277.44 | 263.39 | 315.24 | 157.07 | 158.18 | 0.00 | 0.00 |
November | 149.09 | 407.62 | 233.14 | 118.36 | 114.78 | 0.00 | 0.00 |
December | 95.89 | 635.60 | 230.54 | 124.80 | 105.74 | 0.00 | 0.00 |
Annual Sum or Average | 394.60 | 313.16 | 413.59 | 201.75 | 211.84 | 0.00 | 0.00 |
Minimum of Months | 95.89 | 81.71 | 230.54 | 118.36 | 105.74 | 0.00 | 0.00 |
Maximum of Months | 678.82 | 647.76 | 547.61 | 259.66 | 315.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.46 | 728.09 | 141.49 | 48.36 | 93.13 | 0.00 | 0.00 |
February | 103.82 | 584.81 | 226.67 | 84.82 | 141.84 | 0.00 | 0.00 |
March | 183.22 | 450.52 | 293.98 | 124.39 | 169.59 | 0.00 | 0.00 |
April | 313.48 | 272.08 | 377.18 | 157.70 | 219.48 | 0.00 | 0.00 |
May | 504.07 | 136.53 | 475.53 | 187.14 | 288.39 | 0.00 | 0.00 |
June | 548.42 | 86.91 | 471.76 | 169.73 | 302.03 | 0.00 | 0.00 |
July | 595.74 | 77.78 | 492.35 | 190.71 | 301.64 | 0.00 | 0.00 |
August | 460.93 | 94.71 | 397.92 | 146.89 | 251.04 | 0.00 | 0.00 |
September | 308.83 | 162.07 | 311.89 | 113.16 | 198.73 | 0.00 | 0.00 |
October | 141.79 | 268.80 | 200.89 | 64.11 | 136.78 | 0.00 | 0.00 |
November | 43.52 | 434.31 | 124.47 | 32.95 | 91.51 | 0.00 | 0.00 |
December | 14.21 | 706.77 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Annual Sum or Average | 271.72 | 332.59 | 302.29 | 112.63 | 189.67 | 0.00 | 0.00 |
Minimum of Months | 14.21 | 77.78 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Maximum of Months | 595.74 | 728.09 | 492.35 | 190.71 | 302.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 120.07 | 170.58 | 151.10 | 105.30 | 45.79 | 0.00 | 0.00 |
February | 169.93 | 144.37 | 188.64 | 126.92 | 61.72 | 0.00 | 0.00 |
March | 154.37 | 119.69 | 165.81 | 104.37 | 61.45 | 0.00 | 0.00 |
April | 154.05 | 81.31 | 151.45 | 82.11 | 69.34 | 0.00 | 0.00 |
May | 146.35 | 44.45 | 129.64 | 45.74 | 83.90 | 0.00 | 0.00 |
June | 139.31 | 28.62 | 113.91 | 30.01 | 83.90 | 0.00 | 0.00 |
July | 161.38 | 25.09 | 125.33 | 39.88 | 85.45 | 0.00 | 0.00 |
August | 164.47 | 30.28 | 132.99 | 55.29 | 77.70 | 0.00 | 0.00 |
September | 157.56 | 51.43 | 140.27 | 73.39 | 66.88 | 0.00 | 0.00 |
October | 123.59 | 75.93 | 124.72 | 74.35 | 50.37 | 0.00 | 0.00 |
November | 93.63 | 108.01 | 108.94 | 68.31 | 40.63 | 0.00 | 0.00 |
December | 84.55 | 165.11 | 116.05 | 76.15 | 39.91 | 0.00 | 0.00 |
Annual Sum or Average | 138.88 | 86.82 | 137.08 | 73.16 | 63.92 | 0.00 | 0.00 |
Minimum of Months | 84.55 | 25.09 | 108.94 | 30.01 | 39.91 | 0.00 | 0.00 |
Maximum of Months | 169.93 | 170.58 | 188.64 | 126.92 | 85.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.04 | 223.42 | 21.79 | 0.00 | 21.79 | 0.00 | 0.00 |
February | 1.49 | 179.40 | 33.47 | 0.00 | 33.47 | 0.00 | 0.00 |
March | 5.28 | 136.42 | 41.19 | 0.00 | 41.19 | 0.00 | 0.00 |
April | 24.65 | 78.77 | 54.17 | 0.56 | 53.61 | 0.00 | 0.00 |
May | 70.84 | 35.52 | 75.97 | 4.03 | 71.94 | 0.00 | 0.00 |
June | 98.21 | 22.36 | 84.90 | 9.45 | 75.45 | 0.00 | 0.00 |
July | 99.15 | 19.31 | 81.17 | 7.12 | 74.04 | 0.00 | 0.00 |
August | 68.43 | 23.97 | 61.63 | 1.17 | 60.46 | 0.00 | 0.00 |
September | 38.59 | 45.11 | 47.99 | 0.05 | 47.94 | 0.00 | 0.00 |
October | 11.68 | 79.35 | 33.27 | 0.00 | 33.27 | 0.00 | 0.00 |
November | 1.42 | 132.33 | 22.03 | 0.00 | 22.03 | 0.00 | 0.00 |
December | 0.00 | 214.45 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Annual Sum or Average | 35.19 | 98.86 | 48.08 | 1.87 | 46.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 19.31 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Maximum of Months | 99.15 | 223.42 | 84.90 | 9.45 | 75.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 146.87 | 643.65 | 300.08 | 177.75 | 122.33 | 0.00 | 0.00 |
February | 280.64 | 527.13 | 412.52 | 234.66 | 177.85 | 0.00 | 0.00 |
March | 347.16 | 421.10 | 447.45 | 251.21 | 196.24 | 0.00 | 0.00 |
April | 488.81 | 262.31 | 520.09 | 280.97 | 239.12 | 0.00 | 0.00 |
May | 568.74 | 131.87 | 521.29 | 215.61 | 305.68 | 0.00 | 0.00 |
June | 654.07 | 86.67 | 547.74 | 231.38 | 316.35 | 0.00 | 0.00 |
July | 684.06 | 76.42 | 554.60 | 237.06 | 317.54 | 0.00 | 0.00 |
August | 563.18 | 92.32 | 472.55 | 202.97 | 269.58 | 0.00 | 0.00 |
September | 448.67 | 157.51 | 421.30 | 202.10 | 219.20 | 0.00 | 0.00 |
October | 260.94 | 259.84 | 304.00 | 148.63 | 155.37 | 0.00 | 0.00 |
November | 144.41 | 403.55 | 231.05 | 116.99 | 114.06 | 0.00 | 0.00 |
December | 96.45 | 632.36 | 232.30 | 127.93 | 104.37 | 0.00 | 0.00 |
Annual Sum or Average | 390.75 | 306.97 | 413.58 | 201.95 | 211.63 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 76.42 | 231.05 | 116.99 | 104.37 | 0.00 | 0.00 |
Maximum of Months | 684.06 | 643.65 | 554.60 | 280.97 | 317.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.58 | 719.01 | 138.41 | 46.10 | 92.32 | 0.00 | 0.00 |
February | 78.51 | 565.62 | 218.51 | 75.98 | 142.53 | 0.00 | 0.00 |
March | 164.35 | 434.62 | 291.63 | 120.73 | 170.90 | 0.00 | 0.00 |
April | 327.80 | 260.10 | 398.44 | 179.01 | 219.43 | 0.00 | 0.00 |
May | 472.17 | 127.93 | 454.16 | 163.47 | 290.69 | 0.00 | 0.00 |
June | 597.90 | 83.68 | 511.43 | 205.67 | 305.76 | 0.00 | 0.00 |
July | 602.29 | 73.99 | 499.35 | 196.10 | 303.25 | 0.00 | 0.00 |
August | 440.10 | 89.83 | 383.31 | 135.32 | 247.99 | 0.00 | 0.00 |
September | 297.48 | 155.28 | 305.91 | 110.41 | 195.50 | 0.00 | 0.00 |
October | 121.78 | 261.74 | 189.64 | 55.67 | 133.97 | 0.00 | 0.00 |
November | 36.43 | 428.09 | 122.38 | 31.59 | 90.79 | 0.00 | 0.00 |
December | 11.69 | 700.02 | 110.28 | 32.73 | 77.55 | 0.00 | 0.00 |
Annual Sum or Average | 265.23 | 324.04 | 302.28 | 112.83 | 189.46 | 0.00 | 0.00 |
Minimum of Months | 11.69 | 73.99 | 110.28 | 31.59 | 77.55 | 0.00 | 0.00 |
Maximum of Months | 602.29 | 719.01 | 511.43 | 205.67 | 305.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.15 | 811.58 | 374.59 | 228.16 | 146.43 | 0.00 | 0.00 |
February | 321.96 | 677.95 | 481.24 | 275.00 | 206.24 | 0.00 | 0.00 |
March | 323.25 | 549.75 | 448.51 | 226.14 | 222.37 | 0.00 | 0.00 |
April | 386.70 | 348.79 | 445.49 | 179.12 | 266.38 | 0.00 | 0.00 |
May | 468.93 | 174.52 | 445.46 | 107.83 | 337.63 | 0.00 | 0.00 |
June | 507.53 | 112.52 | 430.73 | 85.48 | 345.24 | 0.00 | 0.00 |
July | 553.44 | 103.10 | 447.40 | 101.85 | 345.55 | 0.00 | 0.00 |
August | 500.40 | 125.47 | 421.67 | 122.33 | 299.34 | 0.00 | 0.00 |
September | 426.54 | 213.12 | 407.87 | 159.11 | 248.76 | 0.00 | 0.00 |
October | 288.33 | 336.76 | 342.30 | 161.10 | 181.20 | 0.00 | 0.00 |
November | 178.89 | 520.73 | 283.76 | 148.01 | 135.75 | 0.00 | 0.00 |
December | 122.84 | 800.88 | 291.46 | 164.99 | 126.47 | 0.00 | 0.00 |
Annual Sum or Average | 355.39 | 396.72 | 401.16 | 162.57 | 238.59 | 0.00 | 0.00 |
Minimum of Months | 122.84 | 103.10 | 283.76 | 85.48 | 126.47 | 0.00 | 0.00 |
Maximum of Months | 553.44 | 811.58 | 481.24 | 275.00 | 345.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.64 | 650.35 | 303.16 | 180.01 | 123.14 | 0.00 | 0.00 |
February | 293.66 | 537.44 | 420.67 | 243.51 | 177.16 | 0.00 | 0.00 |
March | 358.41 | 430.74 | 449.81 | 254.87 | 194.93 | 0.00 | 0.00 |
April | 467.19 | 271.62 | 498.83 | 259.66 | 239.17 | 0.00 | 0.00 |
May | 596.70 | 143.09 | 542.66 | 239.28 | 303.38 | 0.00 | 0.00 |
June | 600.80 | 92.13 | 508.06 | 195.44 | 312.62 | 0.00 | 0.00 |
July | 674.07 | 82.25 | 547.61 | 231.67 | 315.94 | 0.00 | 0.00 |
August | 579.59 | 98.70 | 487.16 | 214.55 | 272.62 | 0.00 | 0.00 |
September | 454.74 | 163.34 | 427.28 | 204.85 | 222.43 | 0.00 | 0.00 |
October | 276.58 | 262.33 | 315.24 | 157.07 | 158.18 | 0.00 | 0.00 |
November | 148.73 | 407.56 | 233.14 | 118.36 | 114.78 | 0.00 | 0.00 |
December | 94.93 | 638.75 | 230.54 | 124.80 | 105.74 | 0.00 | 0.00 |
Annual Sum or Average | 391.85 | 313.92 | 413.59 | 201.75 | 211.84 | 0.00 | 0.00 |
Minimum of Months | 94.93 | 82.25 | 230.54 | 118.36 | 105.74 | 0.00 | 0.00 |
Maximum of Months | 674.07 | 650.35 | 547.61 | 259.66 | 315.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.12 | 730.74 | 141.49 | 48.36 | 93.13 | 0.00 | 0.00 |
February | 103.09 | 586.76 | 226.67 | 84.82 | 141.84 | 0.00 | 0.00 |
March | 182.24 | 451.11 | 293.98 | 124.39 | 169.59 | 0.00 | 0.00 |
April | 311.44 | 271.76 | 377.18 | 157.70 | 219.48 | 0.00 | 0.00 |
May | 499.67 | 137.19 | 475.53 | 187.14 | 288.39 | 0.00 | 0.00 |
June | 544.00 | 87.67 | 471.76 | 169.73 | 302.03 | 0.00 | 0.00 |
July | 591.66 | 78.35 | 492.35 | 190.71 | 301.64 | 0.00 | 0.00 |
August | 457.59 | 95.46 | 397.92 | 146.89 | 251.04 | 0.00 | 0.00 |
September | 307.15 | 161.46 | 311.89 | 113.16 | 198.73 | 0.00 | 0.00 |
October | 142.03 | 267.11 | 200.89 | 64.11 | 136.78 | 0.00 | 0.00 |
November | 43.69 | 434.30 | 124.47 | 32.95 | 91.51 | 0.00 | 0.00 |
December | 14.01 | 710.06 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Annual Sum or Average | 269.90 | 333.30 | 302.29 | 112.63 | 189.67 | 0.00 | 0.00 |
Minimum of Months | 14.01 | 78.35 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Maximum of Months | 591.66 | 730.74 | 492.35 | 190.71 | 302.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 213.13 | 327.93 | 277.05 | 193.09 | 83.97 | 0.00 | 0.00 |
February | 303.26 | 274.93 | 345.89 | 232.72 | 113.16 | 0.00 | 0.00 |
March | 277.53 | 224.89 | 304.04 | 191.37 | 112.67 | 0.00 | 0.00 |
April | 279.70 | 145.14 | 277.70 | 150.56 | 127.14 | 0.00 | 0.00 |
May | 269.04 | 73.81 | 237.70 | 83.86 | 153.84 | 0.00 | 0.00 |
June | 256.84 | 46.20 | 208.87 | 55.03 | 153.84 | 0.00 | 0.00 |
July | 296.23 | 40.16 | 229.81 | 73.13 | 156.68 | 0.00 | 0.00 |
August | 301.26 | 49.26 | 243.85 | 101.38 | 142.48 | 0.00 | 0.00 |
September | 288.88 | 85.19 | 257.19 | 134.56 | 122.63 | 0.00 | 0.00 |
October | 224.57 | 136.75 | 228.69 | 136.33 | 92.36 | 0.00 | 0.00 |
November | 166.64 | 208.12 | 199.75 | 125.26 | 74.50 | 0.00 | 0.00 |
December | 149.34 | 319.07 | 212.80 | 139.62 | 73.18 | 0.00 | 0.00 |
Annual Sum or Average | 251.83 | 160.45 | 251.35 | 134.14 | 117.21 | 0.00 | 0.00 |
Minimum of Months | 149.34 | 40.16 | 199.75 | 55.03 | 73.18 | 0.00 | 0.00 |
Maximum of Months | 303.26 | 327.93 | 345.89 | 232.72 | 156.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.05 | 2059.57 | 190.65 | 0.00 | 190.65 | 0.00 | 0.00 |
February | 6.08 | 1707.51 | 292.85 | 0.00 | 292.85 | 0.00 | 0.00 |
March | 27.71 | 1339.08 | 360.38 | 0.01 | 360.37 | 0.00 | 0.00 |
April | 164.62 | 807.53 | 473.88 | 4.87 | 469.02 | 0.00 | 0.00 |
May | 545.19 | 373.98 | 664.60 | 35.26 | 629.34 | 0.00 | 0.00 |
June | 785.62 | 242.29 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
July | 801.28 | 212.37 | 710.09 | 62.33 | 647.75 | 0.00 | 0.00 |
August | 535.27 | 268.80 | 539.20 | 10.26 | 528.94 | 0.00 | 0.00 |
September | 280.15 | 485.54 | 419.81 | 0.43 | 419.38 | 0.00 | 0.00 |
October | 68.01 | 823.04 | 291.02 | 0.00 | 291.02 | 0.00 | 0.00 |
November | 7.31 | 1323.18 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
December | 0.00 | 2003.00 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Annual Sum or Average | 270.15 | 967.24 | 420.59 | 16.39 | 404.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 212.37 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Maximum of Months | 801.28 | 2059.57 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.01 | 2092.56 | 190.65 | 0.00 | 190.65 | 0.00 | 0.00 |
February | 4.88 | 1741.30 | 292.85 | 0.00 | 292.85 | 0.00 | 0.00 |
March | 24.46 | 1369.01 | 360.38 | 0.01 | 360.37 | 0.00 | 0.00 |
April | 155.55 | 826.29 | 473.88 | 4.87 | 469.02 | 0.00 | 0.00 |
May | 534.47 | 381.64 | 664.60 | 35.26 | 629.34 | 0.00 | 0.00 |
June | 775.54 | 247.93 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
July | 792.72 | 217.33 | 710.09 | 62.33 | 647.75 | 0.00 | 0.00 |
August | 526.64 | 275.98 | 539.20 | 10.26 | 528.94 | 0.00 | 0.00 |
September | 270.99 | 497.02 | 419.81 | 0.43 | 419.38 | 0.00 | 0.00 |
October | 61.99 | 843.89 | 291.02 | 0.00 | 291.02 | 0.00 | 0.00 |
November | 6.44 | 1356.30 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
December | 0.00 | 2036.86 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Annual Sum or Average | 264.50 | 987.17 | 420.59 | 16.39 | 404.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 217.33 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Maximum of Months | 792.72 | 2092.56 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 146.70 | 1305.04 | 438.48 | 223.84 | 214.64 | 0.00 | 0.00 |
February | 348.85 | 1082.29 | 631.00 | 310.64 | 320.36 | 0.00 | 0.00 |
March | 524.54 | 872.87 | 739.05 | 371.93 | 367.12 | 0.00 | 0.00 |
April | 869.41 | 559.18 | 918.48 | 459.95 | 458.53 | 0.00 | 0.00 |
May | 1151.70 | 287.66 | 975.39 | 379.05 | 596.34 | 0.00 | 0.00 |
June | 1386.60 | 195.65 | 1059.11 | 437.02 | 622.08 | 0.00 | 0.00 |
July | 1439.64 | 168.77 | 1053.89 | 433.13 | 620.76 | 0.00 | 0.00 |
August | 1128.00 | 199.67 | 855.82 | 338.27 | 517.54 | 0.00 | 0.00 |
September | 827.23 | 337.77 | 727.17 | 312.49 | 414.68 | 0.00 | 0.00 |
October | 412.59 | 553.11 | 493.62 | 204.30 | 289.32 | 0.00 | 0.00 |
November | 176.62 | 860.00 | 353.42 | 148.58 | 204.84 | 0.00 | 0.00 |
December | 87.27 | 1295.90 | 342.57 | 160.66 | 181.91 | 0.00 | 0.00 |
Annual Sum or Average | 710.05 | 641.25 | 715.83 | 314.76 | 401.07 | 0.00 | 0.00 |
Minimum of Months | 87.27 | 168.77 | 342.57 | 148.58 | 181.91 | 0.00 | 0.00 |
Maximum of Months | 1439.64 | 1305.04 | 1059.11 | 459.95 | 622.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 444.78 | 1421.89 | 770.60 | 491.51 | 279.09 | 0.00 | 0.00 |
February | 712.94 | 1197.12 | 980.87 | 592.41 | 388.45 | 0.00 | 0.00 |
March | 691.57 | 979.13 | 897.48 | 487.14 | 410.34 | 0.00 | 0.00 |
April | 779.76 | 626.42 | 869.34 | 384.92 | 484.42 | 0.00 | 0.00 |
May | 876.62 | 316.99 | 832.91 | 225.57 | 607.35 | 0.00 | 0.00 |
June | 916.35 | 203.42 | 786.29 | 168.40 | 617.89 | 0.00 | 0.00 |
July | 1018.22 | 184.75 | 828.42 | 207.52 | 620.90 | 0.00 | 0.00 |
August | 953.14 | 225.81 | 805.57 | 261.57 | 544.00 | 0.00 | 0.00 |
September | 843.02 | 381.66 | 798.61 | 342.68 | 455.94 | 0.00 | 0.00 |
October | 593.70 | 605.09 | 681.91 | 347.05 | 334.86 | 0.00 | 0.00 |
November | 391.59 | 928.60 | 574.54 | 318.84 | 255.70 | 0.00 | 0.00 |
December | 298.98 | 1408.60 | 597.06 | 355.41 | 241.65 | 0.00 | 0.00 |
Annual Sum or Average | 709.78 | 704.47 | 784.00 | 347.07 | 436.93 | 0.00 | 0.00 |
Minimum of Months | 298.98 | 184.75 | 574.54 | 168.40 | 241.65 | 0.00 | 0.00 |
Maximum of Months | 1018.22 | 1421.89 | 980.87 | 592.41 | 620.90 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.204815E+10 | 0.277725E+10 | 0.255906E+10 | 0.178349E+10 | 0.775570E+09 | 0.00 | 0.00 |
February | 0.260790E+10 | 0.214771E+10 | 0.288571E+10 | 0.194160E+10 | 0.944108E+09 | 0.00 | 0.00 |
March | 0.260940E+10 | 0.197606E+10 | 0.280832E+10 | 0.176763E+10 | 0.104070E+10 | 0.00 | 0.00 |
April | 0.253596E+10 | 0.125205E+10 | 0.248228E+10 | 0.134581E+10 | 0.113646E+10 | 0.00 | 0.00 |
May | 0.251157E+10 | 0.669926E+09 | 0.219561E+10 | 0.774627E+09 | 0.142098E+10 | 0.00 | 0.00 |
June | 0.230585E+10 | 0.412159E+09 | 0.186699E+10 | 0.491871E+09 | 0.137512E+10 | 0.00 | 0.00 |
July | 0.273084E+10 | 0.386214E+09 | 0.212271E+10 | 0.675472E+09 | 0.144724E+10 | 0.00 | 0.00 |
August | 0.279873E+10 | 0.453939E+09 | 0.225239E+10 | 0.936387E+09 | 0.131600E+10 | 0.00 | 0.00 |
September | 0.261170E+10 | 0.743610E+09 | 0.229900E+10 | 0.120281E+10 | 0.109620E+10 | 0.00 | 0.00 |
October | 0.209453E+10 | 0.122822E+10 | 0.211236E+10 | 0.125929E+10 | 0.853077E+09 | 0.00 | 0.00 |
November | 0.152519E+10 | 0.177517E+10 | 0.178557E+10 | 0.111964E+10 | 0.665932E+09 | 0.00 | 0.00 |
December | 0.144075E+10 | 0.272015E+10 | 0.196556E+10 | 0.128965E+10 | 0.675911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.278206E+11 | 0.165424E+11 | 0.273356E+11 | 0.145883E+11 | 0.127473E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144075E+10 | 0.386214E+09 | 0.178557E+10 | 0.491871E+09 | 0.665932E+09 | 0.00 | 0.00 |
Maximum of Months | 0.279873E+10 | 0.277725E+10 | 0.288571E+10 | 0.194160E+10 | 0.144724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.572104E+10 | 0.789928E+10 | 0.720613E+10 | 0.502218E+10 | 0.218395E+10 | 0.00 | 0.00 |
February | 0.728160E+10 | 0.612071E+10 | 0.812596E+10 | 0.546742E+10 | 0.265854E+10 | 0.00 | 0.00 |
March | 0.728167E+10 | 0.567693E+10 | 0.790805E+10 | 0.497752E+10 | 0.293053E+10 | 0.00 | 0.00 |
April | 0.706419E+10 | 0.367818E+10 | 0.698993E+10 | 0.378972E+10 | 0.320021E+10 | 0.00 | 0.00 |
May | 0.696161E+10 | 0.204821E+10 | 0.618268E+10 | 0.218130E+10 | 0.400138E+10 | 0.00 | 0.00 |
June | 0.637178E+10 | 0.130143E+10 | 0.525733E+10 | 0.138508E+10 | 0.387226E+10 | 0.00 | 0.00 |
July | 0.758510E+10 | 0.120944E+10 | 0.597742E+10 | 0.190208E+10 | 0.407534E+10 | 0.00 | 0.00 |
August | 0.778187E+10 | 0.144005E+10 | 0.634258E+10 | 0.263680E+10 | 0.370578E+10 | 0.00 | 0.00 |
September | 0.726268E+10 | 0.228772E+10 | 0.647384E+10 | 0.338702E+10 | 0.308682E+10 | 0.00 | 0.00 |
October | 0.583007E+10 | 0.363181E+10 | 0.594828E+10 | 0.354607E+10 | 0.240221E+10 | 0.00 | 0.00 |
November | 0.424732E+10 | 0.509837E+10 | 0.502804E+10 | 0.315282E+10 | 0.187522E+10 | 0.00 | 0.00 |
December | 0.401770E+10 | 0.772983E+10 | 0.553489E+10 | 0.363157E+10 | 0.190332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.774066E+11 | 0.481220E+11 | 0.769751E+11 | 0.410796E+11 | 0.358956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.401770E+10 | 0.120944E+10 | 0.502804E+10 | 0.138508E+10 | 0.187522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.778187E+10 | 0.789928E+10 | 0.812596E+10 | 0.546742E+10 | 0.407534E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.752878E+10 | 0.106506E+11 | 0.936118E+10 | 0.652410E+10 | 0.283708E+10 | 0.00 | 0.00 |
February | 0.962526E+10 | 0.824475E+10 | 0.105561E+11 | 0.710249E+10 | 0.345360E+10 | 0.00 | 0.00 |
March | 0.963302E+10 | 0.767491E+10 | 0.102730E+11 | 0.646608E+10 | 0.380693E+10 | 0.00 | 0.00 |
April | 0.933538E+10 | 0.502422E+10 | 0.908032E+10 | 0.492306E+10 | 0.415725E+10 | 0.00 | 0.00 |
May | 0.918202E+10 | 0.280510E+10 | 0.803166E+10 | 0.283363E+10 | 0.519802E+10 | 0.00 | 0.00 |
June | 0.839825E+10 | 0.179221E+10 | 0.682958E+10 | 0.179929E+10 | 0.503028E+10 | 0.00 | 0.00 |
July | 0.100159E+11 | 0.163668E+10 | 0.776501E+10 | 0.247092E+10 | 0.529410E+10 | 0.00 | 0.00 |
August | 0.102619E+11 | 0.195458E+10 | 0.823937E+10 | 0.342536E+10 | 0.481402E+10 | 0.00 | 0.00 |
September | 0.955508E+10 | 0.314668E+10 | 0.840988E+10 | 0.439993E+10 | 0.400995E+10 | 0.00 | 0.00 |
October | 0.765017E+10 | 0.501129E+10 | 0.772715E+10 | 0.460654E+10 | 0.312061E+10 | 0.00 | 0.00 |
November | 0.558571E+10 | 0.699036E+10 | 0.653171E+10 | 0.409570E+10 | 0.243602E+10 | 0.00 | 0.00 |
December | 0.526784E+10 | 0.104776E+11 | 0.719013E+10 | 0.471761E+10 | 0.247252E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102039E+12 | 0.654089E+11 | 0.999951E+11 | 0.533647E+11 | 0.466304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.526784E+10 | 0.163668E+10 | 0.653171E+10 | 0.179929E+10 | 0.243602E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102619E+11 | 0.106506E+11 | 0.105561E+11 | 0.710249E+10 | 0.529410E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.406974E+09 | 0.173496E+10 | 0.811979E+09 | 0.482150E+09 | 0.329829E+09 | 0.00 | 0.00 |
February | 0.715326E+09 | 0.129680E+10 | 0.101769E+10 | 0.589096E+09 | 0.428596E+09 | 0.00 | 0.00 |
March | 0.964560E+09 | 0.115271E+10 | 0.120476E+10 | 0.682657E+09 | 0.522105E+09 | 0.00 | 0.00 |
April | 0.121961E+10 | 0.704598E+09 | 0.129296E+10 | 0.673039E+09 | 0.619921E+09 | 0.00 | 0.00 |
May | 0.161193E+10 | 0.381394E+09 | 0.145346E+10 | 0.640897E+09 | 0.812562E+09 | 0.00 | 0.00 |
June | 0.157012E+10 | 0.237008E+09 | 0.131690E+10 | 0.506592E+09 | 0.810308E+09 | 0.00 | 0.00 |
July | 0.181815E+10 | 0.218856E+09 | 0.146671E+10 | 0.620496E+09 | 0.846213E+09 | 0.00 | 0.00 |
August | 0.156414E+10 | 0.261611E+09 | 0.130482E+10 | 0.574637E+09 | 0.730180E+09 | 0.00 | 0.00 |
September | 0.118695E+10 | 0.423470E+09 | 0.110752E+10 | 0.530973E+09 | 0.576547E+09 | 0.00 | 0.00 |
October | 0.743084E+09 | 0.705473E+09 | 0.844350E+09 | 0.420688E+09 | 0.423662E+09 | 0.00 | 0.00 |
November | 0.386430E+09 | 0.105656E+10 | 0.604307E+09 | 0.306789E+09 | 0.297519E+09 | 0.00 | 0.00 |
December | 0.256844E+09 | 0.170240E+10 | 0.617484E+09 | 0.334278E+09 | 0.283207E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.124441E+11 | 0.987583E+10 | 0.130429E+11 | 0.636229E+10 | 0.668065E+10 | 0.00 | 0.00 |
Minimum of Months | 0.256844E+09 | 0.218856E+09 | 0.604307E+09 | 0.306789E+09 | 0.283207E+09 | 0.00 | 0.00 |
Maximum of Months | 0.181815E+10 | 0.173496E+10 | 0.146671E+10 | 0.682657E+09 | 0.846213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 81576587.95 | 0.195012E+10 | 0.378959E+09 | 0.129524E+09 | 0.249434E+09 | 0.00 | 0.00 |
February | 0.251156E+09 | 0.141477E+10 | 0.548349E+09 | 0.205208E+09 | 0.343141E+09 | 0.00 | 0.00 |
March | 0.490740E+09 | 0.120666E+10 | 0.787404E+09 | 0.333172E+09 | 0.454232E+09 | 0.00 | 0.00 |
April | 0.812531E+09 | 0.705222E+09 | 0.977647E+09 | 0.408751E+09 | 0.568897E+09 | 0.00 | 0.00 |
May | 0.135010E+10 | 0.365694E+09 | 0.127365E+10 | 0.501231E+09 | 0.772420E+09 | 0.00 | 0.00 |
June | 0.142150E+10 | 0.225276E+09 | 0.122279E+10 | 0.439939E+09 | 0.782853E+09 | 0.00 | 0.00 |
July | 0.159563E+10 | 0.208326E+09 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
August | 0.123457E+10 | 0.253664E+09 | 0.106580E+10 | 0.393423E+09 | 0.672376E+09 | 0.00 | 0.00 |
September | 0.800491E+09 | 0.420083E+09 | 0.808423E+09 | 0.293318E+09 | 0.515104E+09 | 0.00 | 0.00 |
October | 0.379774E+09 | 0.719963E+09 | 0.538056E+09 | 0.171705E+09 | 0.366351E+09 | 0.00 | 0.00 |
November | 0.112811E+09 | 0.112573E+10 | 0.322624E+09 | 85417046.86 | 0.237207E+09 | 0.00 | 0.00 |
December | 38050875.30 | 0.189300E+10 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.856893E+10 | 0.104885E+11 | 0.953309E+10 | 0.355178E+10 | 0.598132E+10 | 0.00 | 0.00 |
Minimum of Months | 38050875.30 | 0.208326E+09 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159563E+10 | 0.195012E+10 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.321584E+09 | 0.456874E+09 | 0.404696E+09 | 0.282045E+09 | 0.122651E+09 | 0.00 | 0.00 |
February | 0.411102E+09 | 0.349259E+09 | 0.456353E+09 | 0.307049E+09 | 0.149304E+09 | 0.00 | 0.00 |
March | 0.413478E+09 | 0.320586E+09 | 0.444116E+09 | 0.279536E+09 | 0.164579E+09 | 0.00 | 0.00 |
April | 0.399303E+09 | 0.210757E+09 | 0.392555E+09 | 0.212830E+09 | 0.179725E+09 | 0.00 | 0.00 |
May | 0.391995E+09 | 0.119060E+09 | 0.347220E+09 | 0.122501E+09 | 0.224719E+09 | 0.00 | 0.00 |
June | 0.361082E+09 | 74183088.58 | 0.295253E+09 | 77785603.32 | 0.217467E+09 | 0.00 | 0.00 |
July | 0.432234E+09 | 67200025.21 | 0.335693E+09 | 0.106821E+09 | 0.228873E+09 | 0.00 | 0.00 |
August | 0.440519E+09 | 81099903.96 | 0.356200E+09 | 0.148082E+09 | 0.208118E+09 | 0.00 | 0.00 |
September | 0.408385E+09 | 0.133295E+09 | 0.363571E+09 | 0.190214E+09 | 0.173356E+09 | 0.00 | 0.00 |
October | 0.331024E+09 | 0.203366E+09 | 0.334055E+09 | 0.199146E+09 | 0.134908E+09 | 0.00 | 0.00 |
November | 0.242693E+09 | 0.279966E+09 | 0.282374E+09 | 0.177062E+09 | 0.105312E+09 | 0.00 | 0.00 |
December | 0.226451E+09 | 0.442218E+09 | 0.310839E+09 | 0.203948E+09 | 0.106891E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.437985E+10 | 0.273786E+10 | 0.432292E+10 | 0.230702E+10 | 0.201590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.226451E+09 | 67200025.21 | 0.282374E+09 | 77785603.32 | 0.105312E+09 | 0.00 | 0.00 |
Maximum of Months | 0.440519E+09 | 0.456874E+09 | 0.456353E+09 | 0.307049E+09 | 0.228873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 102373.11 | 0.598400E+09 | 58367319.83 | 0.00 | 58367319.83 | 0.00 | 0.00 |
February | 3600115.84 | 0.434016E+09 | 80980322.72 | 0.00 | 80980322.72 | 0.00 | 0.00 |
March | 14130125.49 | 0.365382E+09 | 0.110332E+09 | 4218.19 | 0.110328E+09 | 0.00 | 0.00 |
April | 63895804.02 | 0.204169E+09 | 0.140402E+09 | 1442095.54 | 0.138960E+09 | 0.00 | 0.00 |
May | 0.189727E+09 | 95123573.86 | 0.203471E+09 | 10794416.27 | 0.192676E+09 | 0.00 | 0.00 |
June | 0.254565E+09 | 57944507.69 | 0.220055E+09 | 24482516.34 | 0.195573E+09 | 0.00 | 0.00 |
July | 0.265551E+09 | 51708950.56 | 0.217397E+09 | 19083501.21 | 0.198313E+09 | 0.00 | 0.00 |
August | 0.183273E+09 | 64193611.74 | 0.165078E+09 | 3140560.24 | 0.161937E+09 | 0.00 | 0.00 |
September | 0.100024E+09 | 0.116927E+09 | 0.124382E+09 | 128388.17 | 0.124253E+09 | 0.00 | 0.00 |
October | 31290605.39 | 0.212520E+09 | 89098491.50 | 0.00 | 89098491.50 | 0.00 | 0.00 |
November | 3684989.17 | 0.342997E+09 | 57091439.30 | 0.00 | 57091439.30 | 0.00 | 0.00 |
December | 0.00 | 0.574379E+09 | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.110984E+10 | 0.311776E+10 | 0.151611E+10 | 59075695.98 | 0.145703E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 51708950.56 | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.00 |
Maximum of Months | 0.265551E+09 | 0.598400E+09 | 0.220055E+09 | 24482516.34 | 0.198313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.393371E+09 | 0.172396E+10 | 0.803744E+09 | 0.476088E+09 | 0.327656E+09 | 0.00 | 0.00 |
February | 0.678917E+09 | 0.127523E+10 | 0.997957E+09 | 0.567701E+09 | 0.430256E+09 | 0.00 | 0.00 |
March | 0.929820E+09 | 0.112786E+10 | 0.119846E+10 | 0.672848E+09 | 0.525610E+09 | 0.00 | 0.00 |
April | 0.126698E+10 | 0.679904E+09 | 0.134807E+10 | 0.728269E+09 | 0.619798E+09 | 0.00 | 0.00 |
May | 0.152331E+10 | 0.353188E+09 | 0.139622E+10 | 0.577492E+09 | 0.818725E+09 | 0.00 | 0.00 |
June | 0.169535E+10 | 0.224647E+09 | 0.141973E+10 | 0.599743E+09 | 0.819988E+09 | 0.00 | 0.00 |
July | 0.183218E+10 | 0.204683E+09 | 0.148544E+10 | 0.634931E+09 | 0.850508E+09 | 0.00 | 0.00 |
August | 0.150843E+10 | 0.247282E+09 | 0.126568E+10 | 0.543647E+09 | 0.722031E+09 | 0.00 | 0.00 |
September | 0.116294E+10 | 0.408273E+09 | 0.109200E+10 | 0.523838E+09 | 0.568166E+09 | 0.00 | 0.00 |
October | 0.698904E+09 | 0.695965E+09 | 0.814234E+09 | 0.398101E+09 | 0.416133E+09 | 0.00 | 0.00 |
November | 0.374312E+09 | 0.104601E+10 | 0.598885E+09 | 0.303248E+09 | 0.295637E+09 | 0.00 | 0.00 |
December | 0.258324E+09 | 0.169373E+10 | 0.622191E+09 | 0.342657E+09 | 0.279534E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123228E+11 | 0.968074E+10 | 0.130426E+11 | 0.636856E+10 | 0.667404E+10 | 0.00 | 0.00 |
Minimum of Months | 0.258324E+09 | 0.204683E+09 | 0.598885E+09 | 0.303248E+09 | 0.279534E+09 | 0.00 | 0.00 |
Maximum of Months | 0.183218E+10 | 0.172396E+10 | 0.148544E+10 | 0.728269E+09 | 0.850508E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 55126462.54 | 0.192579E+10 | 0.370723E+09 | 0.123462E+09 | 0.247261E+09 | 0.00 | 0.00 |
February | 0.189937E+09 | 0.136834E+10 | 0.528614E+09 | 0.183814E+09 | 0.344801E+09 | 0.00 | 0.00 |
March | 0.440182E+09 | 0.116409E+10 | 0.781101E+09 | 0.323363E+09 | 0.457737E+09 | 0.00 | 0.00 |
April | 0.849658E+09 | 0.674169E+09 | 0.103276E+10 | 0.463981E+09 | 0.568774E+09 | 0.00 | 0.00 |
May | 0.126466E+10 | 0.342651E+09 | 0.121641E+10 | 0.437826E+09 | 0.778584E+09 | 0.00 | 0.00 |
June | 0.154975E+10 | 0.216906E+09 | 0.132562E+10 | 0.533091E+09 | 0.792533E+09 | 0.00 | 0.00 |
July | 0.161316E+10 | 0.198186E+09 | 0.133745E+10 | 0.525230E+09 | 0.812220E+09 | 0.00 | 0.00 |
August | 0.117876E+10 | 0.240595E+09 | 0.102666E+10 | 0.362432E+09 | 0.664227E+09 | 0.00 | 0.00 |
September | 0.771059E+09 | 0.402489E+09 | 0.792907E+09 | 0.286183E+09 | 0.506723E+09 | 0.00 | 0.00 |
October | 0.326172E+09 | 0.701042E+09 | 0.507940E+09 | 0.149118E+09 | 0.358822E+09 | 0.00 | 0.00 |
November | 94435290.40 | 0.110961E+10 | 0.317202E+09 | 81876671.53 | 0.235325E+09 | 0.00 | 0.00 |
December | 31311801.52 | 0.187494E+10 | 0.295375E+09 | 87671849.66 | 0.207703E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.836421E+10 | 0.102188E+11 | 0.953276E+10 | 0.355805E+10 | 0.597471E+10 | 0.00 | 0.00 |
Minimum of Months | 31311801.52 | 0.198186E+09 | 0.295375E+09 | 81876671.53 | 0.207703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161316E+10 | 0.192579E+10 | 0.133745E+10 | 0.533091E+09 | 0.812220E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.495899E+09 | 0.217373E+10 | 0.100331E+10 | 0.611112E+09 | 0.392194E+09 | 0.00 | 0.00 |
February | 0.778886E+09 | 0.164009E+10 | 0.116422E+10 | 0.665290E+09 | 0.498931E+09 | 0.00 | 0.00 |
March | 0.865796E+09 | 0.147245E+10 | 0.120129E+10 | 0.605687E+09 | 0.595605E+09 | 0.00 | 0.00 |
April | 0.100233E+10 | 0.904072E+09 | 0.115471E+10 | 0.464267E+09 | 0.690447E+09 | 0.00 | 0.00 |
May | 0.125598E+10 | 0.467439E+09 | 0.119312E+10 | 0.288811E+09 | 0.904305E+09 | 0.00 | 0.00 |
June | 0.131551E+10 | 0.291646E+09 | 0.111644E+10 | 0.221577E+09 | 0.894867E+09 | 0.00 | 0.00 |
July | 0.148234E+10 | 0.276151E+09 | 0.119831E+10 | 0.272792E+09 | 0.925516E+09 | 0.00 | 0.00 |
August | 0.134027E+10 | 0.336064E+09 | 0.112940E+10 | 0.327657E+09 | 0.801744E+09 | 0.00 | 0.00 |
September | 0.110560E+10 | 0.552418E+09 | 0.105721E+10 | 0.412420E+09 | 0.644789E+09 | 0.00 | 0.00 |
October | 0.772251E+09 | 0.901970E+09 | 0.916821E+09 | 0.431495E+09 | 0.485326E+09 | 0.00 | 0.00 |
November | 0.463683E+09 | 0.134973E+10 | 0.735506E+09 | 0.383644E+09 | 0.351862E+09 | 0.00 | 0.00 |
December | 0.329002E+09 | 0.214509E+10 | 0.780633E+09 | 0.441899E+09 | 0.338735E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112075E+11 | 0.125109E+11 | 0.126510E+11 | 0.512665E+10 | 0.752432E+10 | 0.00 | 0.00 |
Minimum of Months | 0.329002E+09 | 0.276151E+09 | 0.735506E+09 | 0.221577E+09 | 0.338735E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148234E+10 | 0.217373E+10 | 0.120129E+10 | 0.665290E+09 | 0.925516E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403468E+09 | 0.174189E+10 | 0.811979E+09 | 0.482150E+09 | 0.329829E+09 | 0.00 | 0.00 |
February | 0.710429E+09 | 0.130018E+10 | 0.101769E+10 | 0.589096E+09 | 0.428596E+09 | 0.00 | 0.00 |
March | 0.959963E+09 | 0.115368E+10 | 0.120476E+10 | 0.682657E+09 | 0.522105E+09 | 0.00 | 0.00 |
April | 0.121095E+10 | 0.704031E+09 | 0.129296E+10 | 0.673039E+09 | 0.619921E+09 | 0.00 | 0.00 |
May | 0.159821E+10 | 0.383243E+09 | 0.145346E+10 | 0.640897E+09 | 0.812562E+09 | 0.00 | 0.00 |
June | 0.155728E+10 | 0.238792E+09 | 0.131690E+10 | 0.506592E+09 | 0.810308E+09 | 0.00 | 0.00 |
July | 0.180543E+10 | 0.220285E+09 | 0.146671E+10 | 0.620496E+09 | 0.846213E+09 | 0.00 | 0.00 |
August | 0.155236E+10 | 0.264351E+09 | 0.130482E+10 | 0.574637E+09 | 0.730180E+09 | 0.00 | 0.00 |
September | 0.117868E+10 | 0.423366E+09 | 0.110752E+10 | 0.530973E+09 | 0.576547E+09 | 0.00 | 0.00 |
October | 0.740792E+09 | 0.702630E+09 | 0.844350E+09 | 0.420688E+09 | 0.423662E+09 | 0.00 | 0.00 |
November | 0.385502E+09 | 0.105639E+10 | 0.604307E+09 | 0.306789E+09 | 0.297519E+09 | 0.00 | 0.00 |
December | 0.254247E+09 | 0.171084E+10 | 0.617484E+09 | 0.334278E+09 | 0.283207E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123573E+11 | 0.989968E+10 | 0.130429E+11 | 0.636229E+10 | 0.668065E+10 | 0.00 | 0.00 |
Minimum of Months | 0.254247E+09 | 0.220285E+09 | 0.604307E+09 | 0.306789E+09 | 0.283207E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180543E+10 | 0.174189E+10 | 0.146671E+10 | 0.682657E+09 | 0.846213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 80672370.22 | 0.195722E+10 | 0.378959E+09 | 0.129524E+09 | 0.249434E+09 | 0.00 | 0.00 |
February | 0.249396E+09 | 0.141950E+10 | 0.548349E+09 | 0.205208E+09 | 0.343141E+09 | 0.00 | 0.00 |
March | 0.488104E+09 | 0.120826E+10 | 0.787404E+09 | 0.333172E+09 | 0.454232E+09 | 0.00 | 0.00 |
April | 0.807261E+09 | 0.704395E+09 | 0.977647E+09 | 0.408751E+09 | 0.568897E+09 | 0.00 | 0.00 |
May | 0.133832E+10 | 0.367443E+09 | 0.127365E+10 | 0.501231E+09 | 0.772420E+09 | 0.00 | 0.00 |
June | 0.141004E+10 | 0.227232E+09 | 0.122279E+10 | 0.439939E+09 | 0.782853E+09 | 0.00 | 0.00 |
July | 0.158470E+10 | 0.209857E+09 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
August | 0.122561E+10 | 0.255689E+09 | 0.106580E+10 | 0.393423E+09 | 0.672376E+09 | 0.00 | 0.00 |
September | 0.796137E+09 | 0.418496E+09 | 0.808423E+09 | 0.293318E+09 | 0.515104E+09 | 0.00 | 0.00 |
October | 0.380405E+09 | 0.715421E+09 | 0.538056E+09 | 0.171705E+09 | 0.366351E+09 | 0.00 | 0.00 |
November | 0.113238E+09 | 0.112570E+10 | 0.322624E+09 | 85417046.86 | 0.237207E+09 | 0.00 | 0.00 |
December | 37529216.83 | 0.190181E+10 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851142E+10 | 0.105110E+11 | 0.953309E+10 | 0.355178E+10 | 0.598132E+10 | 0.00 | 0.00 |
Minimum of Months | 37529216.83 | 0.209857E+09 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.158470E+10 | 0.195722E+10 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.570855E+09 | 0.878323E+09 | 0.742054E+09 | 0.517160E+09 | 0.224894E+09 | 0.00 | 0.00 |
February | 0.733656E+09 | 0.665109E+09 | 0.836774E+09 | 0.563008E+09 | 0.273766E+09 | 0.00 | 0.00 |
March | 0.743333E+09 | 0.602344E+09 | 0.814335E+09 | 0.512561E+09 | 0.301774E+09 | 0.00 | 0.00 |
April | 0.724984E+09 | 0.376192E+09 | 0.719792E+09 | 0.390247E+09 | 0.329545E+09 | 0.00 | 0.00 |
May | 0.720595E+09 | 0.197688E+09 | 0.636666E+09 | 0.224620E+09 | 0.412047E+09 | 0.00 | 0.00 |
June | 0.665726E+09 | 0.119746E+09 | 0.541379E+09 | 0.142628E+09 | 0.398750E+09 | 0.00 | 0.00 |
July | 0.793435E+09 | 0.107553E+09 | 0.615530E+09 | 0.195867E+09 | 0.419663E+09 | 0.00 | 0.00 |
August | 0.806892E+09 | 0.131943E+09 | 0.653132E+09 | 0.271525E+09 | 0.381606E+09 | 0.00 | 0.00 |
September | 0.748766E+09 | 0.220821E+09 | 0.666647E+09 | 0.348779E+09 | 0.317868E+09 | 0.00 | 0.00 |
October | 0.601487E+09 | 0.366267E+09 | 0.612526E+09 | 0.365157E+09 | 0.247369E+09 | 0.00 | 0.00 |
November | 0.431933E+09 | 0.539459E+09 | 0.517764E+09 | 0.324662E+09 | 0.193102E+09 | 0.00 | 0.00 |
December | 0.399984E+09 | 0.854609E+09 | 0.569956E+09 | 0.373961E+09 | 0.195996E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.794165E+10 | 0.506005E+10 | 0.792655E+10 | 0.423018E+10 | 0.369638E+10 | 0.00 | 0.00 |
Minimum of Months | 0.399984E+09 | 0.107553E+09 | 0.517764E+09 | 0.142628E+09 | 0.193102E+09 | 0.00 | 0.00 |
Maximum of Months | 0.806892E+09 | 0.878323E+09 | 0.836774E+09 | 0.563008E+09 | 0.419663E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 132186.18 | 0.551635E+10 | 0.510627E+09 | 0.00 | 0.510627E+09 | 0.00 | 0.00 |
February | 14700685.36 | 0.413081E+10 | 0.708457E+09 | 0.00 | 0.708457E+09 | 0.00 | 0.00 |
March | 74212507.86 | 0.358660E+10 | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.00 | 0.00 |
April | 0.426707E+09 | 0.209311E+10 | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.00 | 0.00 |
May | 0.146023E+10 | 0.100167E+10 | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.00 | 0.00 |
June | 0.203634E+10 | 0.628005E+09 | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.00 | 0.00 |
July | 0.214614E+10 | 0.568799E+09 | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.00 | 0.00 |
August | 0.143367E+10 | 0.719956E+09 | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.00 | 0.00 |
September | 0.726147E+09 | 0.125851E+10 | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.00 | 0.00 |
October | 0.182163E+09 | 0.220443E+10 | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.00 | 0.00 |
November | 18951968.14 | 0.342968E+10 | 0.499465E+09 | 0.00 | 0.499465E+09 | 0.00 | 0.00 |
December | 0.00 | 0.536482E+10 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851939E+10 | 0.305027E+11 | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.568799E+09 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.214614E+10 | 0.551635E+10 | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37175.77 | 0.560471E+10 | 0.510627E+09 | 0.00 | 0.510627E+09 | 0.00 | 0.00 |
February | 11797800.83 | 0.421254E+10 | 0.708457E+09 | 0.00 | 0.708457E+09 | 0.00 | 0.00 |
March | 65521127.62 | 0.366677E+10 | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.00 | 0.00 |
April | 0.403182E+09 | 0.214173E+10 | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.00 | 0.00 |
May | 0.143151E+10 | 0.102218E+10 | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.00 | 0.00 |
June | 0.201021E+10 | 0.642623E+09 | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.00 | 0.00 |
July | 0.212321E+10 | 0.582091E+09 | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.00 | 0.00 |
August | 0.141054E+10 | 0.739183E+09 | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.00 | 0.00 |
September | 0.702410E+09 | 0.128829E+10 | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.00 | 0.00 |
October | 0.166028E+09 | 0.226026E+10 | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.00 | 0.00 |
November | 16693613.84 | 0.351552E+10 | 0.499465E+09 | 0.00 | 0.499465E+09 | 0.00 | 0.00 |
December | 0.00 | 0.545552E+10 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.834114E+10 | 0.311314E+11 | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.582091E+09 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212321E+10 | 0.560471E+10 | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.392911E+09 | 0.349541E+10 | 0.117442E+10 | 0.599533E+09 | 0.574892E+09 | 0.00 | 0.00 |
February | 0.843938E+09 | 0.261827E+10 | 0.152651E+10 | 0.751489E+09 | 0.775022E+09 | 0.00 | 0.00 |
March | 0.140492E+10 | 0.233791E+10 | 0.197947E+10 | 0.996166E+09 | 0.983302E+09 | 0.00 | 0.00 |
April | 0.225352E+10 | 0.144941E+10 | 0.238070E+10 | 0.119218E+10 | 0.118852E+10 | 0.00 | 0.00 |
May | 0.308471E+10 | 0.770456E+09 | 0.261249E+10 | 0.101526E+10 | 0.159723E+10 | 0.00 | 0.00 |
June | 0.359406E+10 | 0.507128E+09 | 0.274521E+10 | 0.113276E+10 | 0.161244E+10 | 0.00 | 0.00 |
July | 0.385594E+10 | 0.452041E+09 | 0.282274E+10 | 0.116009E+10 | 0.166265E+10 | 0.00 | 0.00 |
August | 0.302124E+10 | 0.534805E+09 | 0.229222E+10 | 0.906028E+09 | 0.138619E+10 | 0.00 | 0.00 |
September | 0.214418E+10 | 0.875502E+09 | 0.188482E+10 | 0.809981E+09 | 0.107484E+10 | 0.00 | 0.00 |
October | 0.110508E+10 | 0.148145E+10 | 0.132212E+10 | 0.547198E+09 | 0.774919E+09 | 0.00 | 0.00 |
November | 0.457803E+09 | 0.222912E+10 | 0.916052E+09 | 0.385113E+09 | 0.530939E+09 | 0.00 | 0.00 |
December | 0.233744E+09 | 0.347093E+10 | 0.917533E+09 | 0.430317E+09 | 0.487216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223921E+11 | 0.202224E+11 | 0.225743E+11 | 0.992612E+10 | 0.126482E+11 | 0.00 | 0.00 |
Minimum of Months | 0.233744E+09 | 0.452041E+09 | 0.916052E+09 | 0.385113E+09 | 0.487216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385594E+10 | 0.349541E+10 | 0.282274E+10 | 0.119218E+10 | 0.166265E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119129E+10 | 0.380839E+10 | 0.206398E+10 | 0.131646E+10 | 0.747524E+09 | 0.00 | 0.00 |
February | 0.172474E+10 | 0.289606E+10 | 0.237291E+10 | 0.143317E+10 | 0.939745E+09 | 0.00 | 0.00 |
March | 0.185230E+10 | 0.262250E+10 | 0.240382E+10 | 0.130476E+10 | 0.109906E+10 | 0.00 | 0.00 |
April | 0.202113E+10 | 0.162367E+10 | 0.225333E+10 | 0.997719E+09 | 0.125562E+10 | 0.00 | 0.00 |
May | 0.234793E+10 | 0.849037E+09 | 0.223088E+10 | 0.604154E+09 | 0.162672E+10 | 0.00 | 0.00 |
June | 0.237517E+10 | 0.527266E+09 | 0.203806E+10 | 0.436491E+09 | 0.160156E+10 | 0.00 | 0.00 |
July | 0.272721E+10 | 0.494837E+09 | 0.221884E+10 | 0.555822E+09 | 0.166302E+10 | 0.00 | 0.00 |
August | 0.255288E+10 | 0.604818E+09 | 0.215765E+10 | 0.700600E+09 | 0.145705E+10 | 0.00 | 0.00 |
September | 0.218512E+10 | 0.989252E+09 | 0.207001E+10 | 0.888221E+09 | 0.118179E+10 | 0.00 | 0.00 |
October | 0.159017E+10 | 0.162067E+10 | 0.182642E+10 | 0.929526E+09 | 0.896898E+09 | 0.00 | 0.00 |
November | 0.101500E+10 | 0.240693E+10 | 0.148921E+10 | 0.826446E+09 | 0.662769E+09 | 0.00 | 0.00 |
December | 0.800781E+09 | 0.377278E+10 | 0.159917E+10 | 0.951937E+09 | 0.647228E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223837E+11 | 0.222162E+11 | 0.247243E+11 | 0.109453E+11 | 0.137790E+11 | 0.00 | 0.00 |
Minimum of Months | 0.800781E+09 | 0.494837E+09 | 0.148921E+10 | 0.436491E+09 | 0.647228E+09 | 0.00 | 0.00 |
Maximum of Months | 0.272721E+10 | 0.380839E+10 | 0.240382E+10 | 0.143317E+10 | 0.166302E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770912E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166343336.4 | 81.21 | 0.00 | 0.00 |
February | 0.696393E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -147979591.3 | 81.21 | 0.00 | 0.00 |
March | 0.770399E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162508836.1 | 81.21 | 0.00 | 0.00 |
April | 0.746498E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156389289.3 | 81.21 | 0.00 | 0.00 |
May | 0.770416E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161375055.1 | 81.21 | 0.00 | 0.00 |
June | 0.745679E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156263114.2 | 81.21 | 0.00 | 0.00 |
July | 0.771233E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161484412.1 | 81.21 | 0.00 | 0.00 |
August | 0.770429E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161489964.4 | 81.21 | 0.00 | 0.00 |
September | 0.746608E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156154064.4 | 81.21 | 0.00 | 0.00 |
October | 0.770271E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161281198.4 | 81.21 | 0.00 | 0.00 |
November | 0.744922E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156785761.7 | 81.21 | 0.00 | 0.00 |
December | 0.771602E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165162332.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907536E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191322E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696393E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -166343336.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771602E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147979591.3 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129329E+12 | -0.127565E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176414E+10 | 80.10 | 0.00 | 0.00 |
February | 0.116968E+12 | -0.115406E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156164E+10 | 79.76 | 0.00 | 0.00 |
March | 0.129467E+12 | -0.127735E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173184E+10 | 79.82 | 0.00 | 0.00 |
April | 0.125043E+12 | -0.123357E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168587E+10 | 80.28 | 0.00 | 0.00 |
May | 0.128796E+12 | -0.127038E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175833E+10 | 81.03 | 0.00 | 0.00 |
June | 0.120970E+12 | -0.119266E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170325E+10 | 81.30 | 0.00 | 0.00 |
July | 0.120309E+12 | -0.118564E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174490E+10 | 81.27 | 0.00 | 0.00 |
August | 0.117891E+12 | -0.116157E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173332E+10 | 81.26 | 0.00 | 0.00 |
September | 0.114496E+12 | -0.112822E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167400E+10 | 81.26 | 0.00 | 0.00 |
October | 0.121421E+12 | -0.119692E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172866E+10 | 81.26 | 0.00 | 0.00 |
November | 0.122515E+12 | -0.120840E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167571E+10 | 81.32 | 0.00 | 0.00 |
December | 0.128931E+12 | -0.127171E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175946E+10 | 80.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.147613E+13 | -0.145561E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205211E+11 | 80.79 | 0.00 | 0.00 |
Minimum of Months | 0.114496E+12 | -0.127735E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176414E+10 | 79.76 | 0.00 | 0.00 |
Maximum of Months | 0.129467E+12 | -0.112822E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156164E+10 | 81.32 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.849936E+11 | -0.834304E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156318E+10 | 58.99 | 0.00 | 0.00 |
February | 0.784883E+11 | -0.771074E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.138088E+10 | 58.99 | 0.00 | 0.00 |
March | 0.866158E+11 | -0.850856E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153022E+10 | 58.99 | 0.00 | 0.00 |
April | 0.812753E+11 | -0.797995E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147583E+10 | 58.99 | 0.00 | 0.00 |
May | 0.798070E+11 | -0.782909E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151615E+10 | 58.99 | 0.00 | 0.00 |
June | 0.727525E+11 | -0.712939E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145861E+10 | 58.98 | 0.00 | 0.00 |
July | 0.712277E+11 | -0.697399E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148779E+10 | 58.98 | 0.00 | 0.00 |
August | 0.692256E+11 | -0.677536E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147204E+10 | 58.98 | 0.00 | 0.00 |
September | 0.673051E+11 | -0.658852E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141985E+10 | 58.98 | 0.00 | 0.00 |
October | 0.721653E+11 | -0.706998E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146545E+10 | 58.99 | 0.00 | 0.00 |
November | 0.739094E+11 | -0.724895E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141990E+10 | 58.98 | 0.00 | 0.00 |
December | 0.810719E+11 | -0.795444E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152747E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.918838E+12 | -0.901120E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177174E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.673051E+11 | -0.850856E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156318E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.866158E+11 | -0.658852E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138088E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.87 | 0.86 | 01-JAN-08:39 | 4819.80 | 35.99 | 235.33 | 243.67 | 3997.19 | 36.97 | 241.00 | 225.50 |
February | 265.33 | 0.87 | 0.86 | 01-FEB-08:39 | 7655.64 | 36.13 | 258.50 | 259.50 | 3210.03 | 32.22 | 259.17 | 241.50 |
March | 254.17 | 0.87 | 0.86 | 02-MAR-10:39 | 9970.23 | 33.91 | 213.50 | 326.33 | 897.95 | 23.19 | 239.50 | 277.83 |
April | 296.33 | 0.87 | 0.86 | 01-APR-08:09 | 1705.92 | 20.99 | 110.00 | 357.33 | 694.46 | 22.60 | 262.67 | 303.50 |
May | 437.50 | 0.87 | 0.86 | 01-MAY-06:49 | 1602.41 | 20.64 | 166.33 | 417.83 | 625.90 | 22.35 | 329.33 | 353.00 |
June | 401.83 | 0.87 | 0.86 | 01-JUN-05:40 | 1523.50 | 20.69 | 175.83 | 418.00 | 607.49 | 22.40 | 297.67 | 355.67 |
July | 409.17 | 0.87 | 0.86 | 01-JUL-05:49 | 1637.74 | 21.04 | 209.50 | 424.83 | 657.02 | 22.75 | 321.17 | 366.00 |
August | 352.83 | 0.87 | 0.86 | 01-AUG-07:40 | 1925.02 | 21.20 | 187.33 | 383.50 | 759.40 | 22.90 | 280.33 | 328.17 |
September | 344.17 | 0.87 | 0.86 | 01-SEP-06:00 | 3364.22 | 24.27 | 204.17 | 335.50 | 764.38 | 22.46 | 255.17 | 289.67 |
October | 299.00 | 0.87 | 0.86 | 01-OCT-06:49 | 5513.14 | 32.20 | 271.00 | 301.83 | 1085.70 | 24.94 | 232.33 | 265.17 |
November | 255.50 | 0.87 | 0.86 | 01-NOV-08:09 | 3835.37 | 34.60 | 245.83 | 246.00 | 3025.34 | 35.21 | 247.83 | 218.00 |
December | 226.33 | 0.87 | 0.86 | 01-DEC-08:20 | 3528.46 | 34.05 | 211.00 | 229.00 | 2800.49 | 35.09 | 216.50 | 202.50 |
Annual Sum or Average | 3785.50 | 0.87 | 3563.90 | 26.72 | 2488.33 | 3943.33 | 1402.09 | 26.00 | 3182.67 | 3426.50 | ||
Minimum of Months | 226.33 | 0.87 | 0.86 | 1523.50 | 20.64 | 110.00 | 229.00 | 607.49 | 22.35 | 216.50 | 202.50 | |
Maximum of Months | 437.50 | 0.87 | 0.86 | 9970.23 | 36.13 | 271.00 | 424.83 | 3997.19 | 36.97 | 329.33 | 366.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.24 | 0.22 | 01-JAN-08:30 | 5293.54 | 36.08 | 237.17 | 249.50 | 4468.69 | 37.04 | 241.83 | 236.50 |
February | 265.33 | 0.24 | 0.22 | 01-FEB-08:39 | 8207.70 | 36.22 | 258.83 | 266.50 | 3756.81 | 32.08 | 240.50 | 252.50 |
March | 254.17 | 0.25 | 0.22 | 02-MAR-10:39 | 10529.02 | 34.08 | 214.67 | 335.83 | 1454.63 | 22.93 | 230.33 | 307.33 |
April | 296.33 | 0.26 | 0.22 | 01-APR-07:40 | 2142.65 | 21.01 | 113.83 | 371.17 | 1129.97 | 22.50 | 263.17 | 338.33 |
May | 437.50 | 0.26 | 0.22 | 01-MAY-05:00 | 1903.58 | 21.03 | 196.67 | 430.00 | 926.01 | 22.57 | 339.00 | 397.33 |
June | 401.83 | 0.26 | 0.22 | 01-JUN-05:10 | 1799.80 | 21.14 | 210.17 | 434.00 | 882.83 | 22.68 | 318.83 | 396.17 |
July | 409.17 | 0.25 | 0.22 | 01-JUL-05:19 | 1947.23 | 21.40 | 231.83 | 439.83 | 965.49 | 22.95 | 342.50 | 403.50 |
August | 352.83 | 0.25 | 0.22 | 01-AUG-07:40 | 2294.05 | 21.46 | 191.00 | 395.33 | 1127.09 | 23.02 | 299.33 | 361.67 |
September | 344.17 | 0.25 | 0.22 | 01-SEP-06:40 | 3748.01 | 24.45 | 204.17 | 345.17 | 1147.00 | 22.57 | 255.67 | 318.33 |
October | 299.00 | 0.24 | 0.22 | 01-OCT-06:49 | 5889.62 | 32.37 | 274.67 | 309.83 | 1463.02 | 25.03 | 226.00 | 286.67 |
November | 255.50 | 0.25 | 0.22 | 01-NOV-07:00 | 4174.22 | 34.69 | 246.67 | 253.00 | 3363.43 | 35.30 | 248.50 | 234.33 |
December | 226.33 | 0.24 | 0.22 | 01-DEC-08:09 | 3896.98 | 34.19 | 212.67 | 238.00 | 3166.85 | 35.20 | 217.83 | 217.67 |
Annual Sum or Average | 3785.50 | 0.25 | 3946.27 | 26.94 | 2592.33 | 4068.17 | 1783.04 | 26.09 | 3223.50 | 3750.33 | ||
Minimum of Months | 226.33 | 0.24 | 0.22 | 1799.80 | 21.01 | 113.83 | 238.00 | 882.83 | 22.50 | 217.83 | 217.67 | |
Maximum of Months | 437.50 | 0.26 | 0.22 | 10529.02 | 36.22 | 274.67 | 439.83 | 4468.69 | 37.04 | 342.50 | 403.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.66 | 0.60 | 01-JAN-11:20 | 479.20 | 15.50 | 0.00 | 222.33 | 219.27 | 18.95 | 0.00 | 138.67 |
February | 265.33 | 0.64 | 0.60 | 01-FEB-09:30 | 587.25 | 16.55 | 0.00 | 248.50 | 276.36 | 19.92 | 10.50 | 197.00 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 601.52 | 17.25 | 0.00 | 324.50 | 300.20 | 20.58 | 42.67 | 254.67 |
April | 296.33 | 0.62 | 0.60 | 01-APR-08:09 | 687.88 | 17.97 | 0.00 | 371.33 | 334.92 | 21.27 | 107.67 | 326.00 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 1001.27 | 19.54 | 22.67 | 438.33 | 452.99 | 23.33 | 298.67 | 414.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1199.64 | 21.33 | 62.50 | 445.50 | 559.90 | 24.96 | 320.83 | 419.00 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1137.20 | 21.02 | 51.50 | 448.67 | 534.71 | 24.46 | 331.33 | 421.67 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 938.53 | 19.08 | 7.17 | 397.00 | 433.90 | 22.23 | 217.17 | 354.33 |
September | 344.17 | 0.63 | 0.60 | 01-SEP-06:40 | 709.75 | 17.53 | 0.00 | 339.50 | 321.91 | 20.70 | 61.50 | 287.17 |
October | 299.00 | 0.64 | 0.60 | 01-OCT-07:19 | 603.17 | 16.49 | 0.00 | 293.00 | 261.99 | 19.72 | 1.50 | 214.00 |
November | 255.50 | 0.66 | 0.60 | 01-NOV-08:00 | 472.72 | 15.26 | 0.00 | 228.83 | 205.95 | 18.54 | 0.00 | 141.33 |
December | 226.33 | 0.67 | 0.60 | 01-DEC-09:39 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.57 | 0.00 | 110.83 |
Annual Sum or Average | 3785.50 | 0.63 | 790.78 | 18.13 | 143.83 | 3966.67 | 365.63 | 21.52 | 1391.83 | 3278.83 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.54 | 0.00 | 110.83 | |
Maximum of Months | 437.50 | 0.67 | 0.60 | 1199.64 | 21.33 | 62.50 | 448.67 | 559.90 | 24.96 | 331.33 | 421.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.66 | 0.60 | 01-JAN-11:20 | 479.20 | 15.50 | 0.00 | 222.33 | 219.27 | 18.95 | 0.00 | 138.67 |
February | 265.33 | 0.64 | 0.60 | 01-FEB-09:30 | 587.25 | 16.55 | 0.00 | 248.50 | 276.36 | 19.92 | 10.50 | 197.00 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 601.52 | 17.25 | 0.00 | 324.50 | 300.20 | 20.58 | 42.67 | 254.67 |
April | 296.33 | 0.62 | 0.60 | 01-APR-08:09 | 687.88 | 17.97 | 0.00 | 371.33 | 334.92 | 21.27 | 107.67 | 326.00 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 1001.27 | 19.54 | 22.67 | 438.33 | 452.99 | 23.33 | 298.67 | 414.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1199.64 | 21.33 | 62.50 | 445.50 | 559.90 | 24.96 | 320.83 | 419.00 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1137.20 | 21.02 | 51.50 | 448.67 | 534.71 | 24.46 | 331.33 | 421.67 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 938.53 | 19.08 | 7.17 | 397.00 | 433.90 | 22.23 | 217.17 | 354.33 |
September | 344.17 | 0.63 | 0.60 | 01-SEP-06:40 | 709.75 | 17.53 | 0.00 | 339.50 | 321.91 | 20.70 | 61.50 | 287.17 |
October | 299.00 | 0.64 | 0.60 | 01-OCT-07:19 | 603.17 | 16.49 | 0.00 | 293.00 | 261.99 | 19.72 | 1.50 | 214.00 |
November | 255.50 | 0.66 | 0.60 | 01-NOV-08:00 | 472.72 | 15.26 | 0.00 | 228.83 | 205.95 | 18.54 | 0.00 | 141.33 |
December | 226.33 | 0.67 | 0.60 | 01-DEC-09:39 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.57 | 0.00 | 110.83 |
Annual Sum or Average | 3785.50 | 0.63 | 790.78 | 18.13 | 143.83 | 3966.67 | 365.63 | 21.52 | 1391.83 | 3278.83 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.54 | 0.00 | 110.83 | |
Maximum of Months | 437.50 | 0.67 | 0.60 | 1199.64 | 21.33 | 62.50 | 448.67 | 559.90 | 24.96 | 331.33 | 421.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397920E+12 | 385853.62 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220429E+12 | 378361.37 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124369E+12 | 364089.04 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251853E+11 | 168305.79 | 11-APR-21:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137482E+11 | 171457.74 | 21-MAY-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.549775E+10 | 163800.08 | 02-JUN-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.235115E+10 | 110107.45 | 02-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.288906E+10 | 122869.20 | 19-AUG-01:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194449E+11 | 168234.91 | 15-SEP-00:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.308687E+11 | 164214.70 | 07-OCT-22:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.600303E+11 | 137064.77 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344143E+12 | 371421.91 | 24-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124688E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.235115E+10 | 110107.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397920E+12 | 385853.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.488872E+10 | 7701.91 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112082E+10 | 7545.86 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.399992E+09 | 7183.73 | 05-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263195E+10 | 7378.49 | 24-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.904149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.488872E+10 | 7701.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737084E+10 | 5183.34 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437335E+10 | 5075.09 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340403E+10 | 4851.78 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157158E+10 | 2498.49 | 08-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341852E+09 | 3485.27 | 08-MAY-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155248E+09 | 2029.63 | 03-JUN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36883625.86 | 2316.03 | 02-JUL-04:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89509959.02 | 2704.86 | 19-AUG-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.438286E+09 | 3206.46 | 21-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173217E+10 | 3659.11 | 24-OCT-07:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341392E+10 | 3222.80 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.714165E+10 | 4966.23 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 36883625.86 | 2029.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.737084E+10 | 5183.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177589E+10 | 1861.93 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.699567E+09 | 1823.58 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248580E+09 | 1744.35 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1385166.34 | 188.77 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1324458.32 | 130.83 | 30-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95790718.60 | 569.91 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148658E+10 | 1784.98 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177589E+10 | 1861.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391042E+10 | 2576.83 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230584E+10 | 2523.27 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144972E+10 | 2412.73 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204653E+09 | 1024.94 | 10-APR-09:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 314833.69 | 330.48 | 01-MAY-10:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61195543.84 | 556.15 | 15-OCT-14:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.844854E+09 | 1107.85 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348102E+10 | 2469.39 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.391042E+10 | 2576.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305672E+10 | 1799.79 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202577E+10 | 1762.55 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145652E+10 | 1685.66 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.358650E+09 | 816.08 | 10-APR-09:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9458841.09 | 325.34 | 01-MAY-10:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214966E+09 | 717.47 | 10-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104143E+10 | 982.20 | 25-NOV-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281262E+10 | 1725.08 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305672E+10 | 1799.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.614999E+10 | 10910.38 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227665E+10 | 10630.49 | 14-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.781286E+09 | 10175.26 | 05-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21766453.29 | 8750.15 | 15-APR-01:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25015981.30 | 8814.97 | 22-MAY-02:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26672881.19 | 8825.24 | 17-JUN-01:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14649072.55 | 8637.27 | 18-JUL-03:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11053423.19 | 6992.90 | 25-AUG-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61646516.73 | 8919.37 | 15-SEP-01:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54200273.06 | 8826.61 | 20-OCT-04:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70829158.48 | 8771.86 | 02-NOV-01:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492182E+10 | 10456.10 | 24-DEC-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11053423.19 | 6992.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.614999E+10 | 10910.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135529E+11 | 14594.59 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573724E+10 | 14293.38 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306571E+10 | 13671.32 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617388E+09 | 6251.36 | 25-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15154891.15 | 3692.96 | 08-MAY-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3608065.61 | 1309.91 | 09-JUN-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13120395.11 | 1665.18 | 17-AUG-12:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49706721.05 | 6313.65 | 21-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.864517E+09 | 10252.35 | 10-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263161E+10 | 6284.91 | 24-NOV-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124326E+11 | 13990.27 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135529E+11 | 14594.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276611E+11 | 35505.13 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.965650E+10 | 34775.51 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314486E+10 | 33268.00 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7455418.38 | 1683.40 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7840454.29 | 1452.21 | 30-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.940522E+09 | 9839.99 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232167E+11 | 34041.06 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276611E+11 | 35505.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.260232E+11 | 17979.40 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144103E+11 | 17604.87 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907774E+10 | 16832.07 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177746E+10 | 8657.00 | 10-APR-09:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6021804.17 | 1094.20 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254309E+10 | 12686.93 | 15-OCT-14:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.910396E+10 | 9174.14 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243231E+11 | 17228.17 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260232E+11 | 17979.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154879E+11 | 10877.83 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893447E+10 | 10650.00 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570647E+10 | 10180.16 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131604E+10 | 3695.92 | 05-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28481046.18 | 1355.58 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1883959.39 | 2338.46 | 21-SEP-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130961E+10 | 4973.55 | 10-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.489923E+10 | 5237.47 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142007E+11 | 10420.93 | 24-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154879E+11 | 10877.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.780414E+10 | 13942.66 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258478E+10 | 13581.28 | 14-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.655973E+09 | 12932.49 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618991E+10 | 13350.36 | 24-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.780414E+10 | 13942.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.775006E+10 | 14358.36 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251870E+10 | 13986.35 | 14-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637462E+09 | 13318.71 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608351E+10 | 13727.05 | 24-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.775006E+10 | 14358.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.503236E+10 | 9494.76 | 06-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173358E+10 | 9282.91 | 14-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.572827E+09 | 8871.65 | 05-MAR-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 767426.52 | 1180.17 | 15-APR-01:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 558327.83 | 1040.37 | 04-MAY-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 760992.93 | 2363.11 | 08-JUN-01:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2013085.69 | 2736.38 | 07-SEP-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 516243.99 | 1513.63 | 26-OCT-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378779E+10 | 9124.80 | 24-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.503236E+10 | 9494.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.493115E+11 | 45518.63 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281189E+11 | 44604.81 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161768E+11 | 42823.35 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192736E+10 | 10933.70 | 05-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38270476.02 | 2781.18 | 01-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28379.49 | 0.45 | 01-JUN-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25378.21 | 0.46 | 18-JUL-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29874.83 | 0.46 | 15-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12787.74 | 0.46 | 19-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820670E+09 | 8403.77 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.857434E+10 | 15790.95 | 29-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433020E+11 | 43719.47 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12787.74 | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.493115E+11 | 45518.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124998E+11 | 9444.54 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772554E+10 | 9443.40 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.553484E+10 | 9443.97 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193545E+10 | 9443.40 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165584E+09 | 9185.29 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27371015.91 | 4229.33 | 03-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2498247.55 | 3154.43 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29488060.79 | 5248.36 | 04-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.273720E+09 | 9123.55 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.224044E+10 | 9443.78 | 13-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569189E+10 | 9443.92 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121293E+11 | 9444.97 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2498247.55 | 3154.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124998E+11 | 9444.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141921E+11 | 9395.94 | 05-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.928305E+10 | 9343.22 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674301E+10 | 9344.88 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236872E+10 | 9343.34 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196615E+09 | 9136.15 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26183605.87 | 5116.10 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2815989.54 | 3199.52 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32261557.41 | 4680.77 | 04-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345066E+09 | 9043.18 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269550E+10 | 9344.08 | 13-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656663E+10 | 9345.46 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134407E+11 | 9344.58 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2815989.54 | 3199.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141921E+11 | 9395.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.446441E+11 | 55750.30 | 09-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186132E+11 | 55125.05 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.864568E+10 | 51059.70 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134758E+09 | 6001.95 | 04-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.311587E+09 | 7957.69 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104556E+11 | 28843.00 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453135E+11 | 55474.63 | 24-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128118E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453135E+11 | 55750.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.739788E+11 | 52653.16 | 06-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.463955E+11 | 51483.28 | 09-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314948E+11 | 51489.16 | 03-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.723089E+10 | 50695.63 | 04-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283984E+09 | 29232.08 | 03-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35978453.56 | 32306.50 | 13-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14940585.66 | 22210.13 | 10-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 56701020.30 | 31155.83 | 20-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183074E+09 | 40125.84 | 23-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.568593E+10 | 50603.97 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241210E+11 | 51487.15 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665895E+11 | 51576.55 | 24-DEC-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14940585.66 | 22210.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.739788E+11 | 52653.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124769E+11 | 9285.32 | 06-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768958E+10 | 9236.51 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.548534E+10 | 9237.12 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186565E+10 | 9237.12 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187712E+09 | 4082.03 | 31-MAY-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16688073.84 | 3164.38 | 11-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1930902.03 | 3009.22 | 05-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24604701.53 | 3094.68 | 03-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312975E+09 | 8897.33 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233700E+10 | 9236.02 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571871E+10 | 9237.05 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120902E+11 | 9238.13 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1930902.03 | 3009.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124769E+11 | 9285.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142108E+11 | 9175.68 | 09-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.929387E+10 | 9119.46 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.671524E+10 | 9119.83 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225067E+10 | 9119.82 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233043E+09 | 5028.42 | 02-MAY-19:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16896618.98 | 2929.23 | 12-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1871510.52 | 2957.14 | 09-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27325668.00 | 3014.71 | 31-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.403770E+09 | 8798.55 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282995E+10 | 9119.36 | 13-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657928E+10 | 9121.83 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134231E+11 | 9120.89 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1871510.52 | 2929.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142108E+11 | 9175.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.389760E+10 | 2742.71 | 06-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250163E+10 | 2726.51 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184847E+10 | 2727.08 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706521E+09 | 2726.76 | 26-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82995363.00 | 2677.27 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18666103.11 | 1297.57 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 637273.04 | 1112.78 | 31-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15305521.65 | 1272.39 | 22-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134207E+09 | 2667.36 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.829688E+09 | 2727.09 | 11-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191006E+10 | 2728.41 | 21-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380325E+10 | 2726.95 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 637273.04 | 1112.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.389760E+10 | 2742.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.437753E+10 | 2706.63 | 09-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.295171E+10 | 2689.87 | 21-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220959E+10 | 2690.05 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.849140E+09 | 2689.87 | 26-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96471151.81 | 2655.20 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18201847.81 | 1152.33 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 698064.76 | 1041.29 | 31-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16576226.01 | 1205.18 | 20-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174387E+09 | 2635.02 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.986661E+09 | 2690.27 | 11-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217650E+10 | 2691.55 | 21-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417048E+10 | 2689.89 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 698064.76 | 1041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437753E+10 | 2706.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140279E+11 | 13105.59 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.818809E+10 | 13103.34 | 26-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.592202E+10 | 13103.37 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212756E+10 | 13104.62 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242596E+09 | 7930.92 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47129518.36 | 5338.69 | 03-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4275558.17 | 5033.10 | 15-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33036470.44 | 5048.14 | 19-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265938E+09 | 12595.57 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229052E+10 | 13102.56 | 29-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613857E+10 | 13105.38 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141109E+11 | 13106.85 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4275558.17 | 5033.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141109E+11 | 13106.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4252751.44 | 4252751.44 | 1992.91 | 19-JAN-06:20 | 1992.91 | 0.00 |
February | 0.00 | 0.00 | 62131457.28 | 62131457.28 | 11107.87 | 20-FEB-19:25 | 11107.87 | 0.00 |
March | 0.00 | 0.00 | 0.144057E+09 | 0.144057E+09 | 17336.45 | 19-MAR-18:30 | 17336.45 | 0.00 |
April | 0.00 | 0.00 | 0.136926E+11 | 0.136926E+11 | 184584.78 | 23-APR-18:10 | 184584.78 | 0.02 |
May | 0.00 | 0.00 | 0.104106E+12 | 0.101553E+12 | 286012.73 | 25-MAY-18:08 | 235301.30 | 0.30 |
June | 0.00 | 0.00 | 0.271758E+12 | 0.190415E+12 | 478765.73 | 27-JUN-19:50 | 211756.10 | 0.62 |
July | 0.00 | 0.00 | 0.380595E+12 | 0.245857E+12 | 494812.20 | 21-JUL-19:23 | 201815.73 | 0.84 |
August | 0.00 | 0.00 | 0.259339E+12 | 0.180963E+12 | 463269.44 | 31-AUG-19:04 | 206074.85 | 0.79 |
September | 0.00 | 0.00 | 0.583751E+11 | 0.502738E+11 | 255550.72 | 01-SEP-10:50 | 165613.78 | 0.30 |
October | 0.00 | 0.00 | 0.855039E+10 | 0.855039E+10 | 132401.94 | 19-OCT-15:03 | 132401.94 | 0.04 |
November | 0.00 | 0.00 | 0.127489E+10 | 0.127489E+10 | 53629.16 | 01-NOV-15:30 | 53629.16 | 0.02 |
December | 0.00 | 0.00 | 16114192.88 | 16114192.88 | 4761.98 | 05-DEC-21:10 | 4761.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109792E+13 | 0.792806E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 4252751.44 | 4252751.44 | 1992.91 | 1992.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.380595E+12 | 0.245857E+12 | 494812.20 | 235301.30 | 0.84 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220450E+10 | 0.220450E+10 | 28401.35 | 23-APR-18:00 | 28401.35 | 0.02 |
May | 0.00 | 0.00 | 0.181486E+11 | 0.173525E+11 | 41735.56 | 26-MAY-13:10 | 27380.17 | 0.29 |
June | 0.00 | 0.00 | 0.481002E+11 | 0.327954E+11 | 64926.24 | 19-JUN-17:25 | 26688.87 | 0.59 |
July | 0.00 | 0.00 | 0.674810E+11 | 0.423568E+11 | 70555.00 | 04-JUL-02:50 | 24257.69 | 0.82 |
August | 0.00 | 0.00 | 0.474239E+11 | 0.316156E+11 | 62434.83 | 31-AUG-20:00 | 27875.57 | 0.77 |
September | 0.00 | 0.00 | 0.106511E+11 | 0.879735E+10 | 41432.33 | 01-SEP-10:25 | 25771.45 | 0.22 |
October | 0.00 | 0.00 | 0.144276E+10 | 0.144276E+10 | 24823.32 | 19-OCT-15:00 | 24823.32 | 0.03 |
November | 0.00 | 0.00 | 0.223309E+09 | 0.223309E+09 | 12273.98 | 01-NOV-15:00 | 12273.98 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195675E+12 | 0.136788E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.674810E+11 | 0.423568E+11 | 70555.00 | 28401.35 | 0.82 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 986442.77 | 986442.77 | 3267.63 | 17-JAN-16:03 | 3267.63 | 0.00 |
February | 0.00 | 0.00 | 0.129050E+09 | 0.129050E+09 | 17802.23 | 20-FEB-16:01 | 17802.23 | 0.00 |
March | 0.00 | 0.00 | 0.553757E+09 | 0.553757E+09 | 17820.99 | 28-MAR-18:01 | 17820.99 | 0.00 |
April | 0.00 | 0.00 | 0.184231E+10 | 0.175497E+10 | 20638.59 | 11-APR-18:11 | 20638.59 | 0.03 |
May | 0.00 | 0.00 | 0.484224E+10 | 0.357446E+10 | 22586.58 | 06-MAY-18:42 | 22586.58 | 0.39 |
June | 0.00 | 0.00 | 0.623976E+10 | 0.371301E+10 | 23443.67 | 25-JUN-08:51 | 15886.55 | 0.63 |
July | 0.00 | 0.00 | 0.851941E+10 | 0.499360E+10 | 24029.14 | 25-JUL-21:51 | 16425.94 | 0.68 |
August | 0.00 | 0.00 | 0.649542E+10 | 0.353687E+10 | 22897.47 | 27-AUG-21:51 | 16921.04 | 0.64 |
September | 0.00 | 0.00 | 0.291491E+10 | 0.158959E+10 | 22107.50 | 01-SEP-21:21 | 16479.02 | 0.50 |
October | 0.00 | 0.00 | 0.865691E+09 | 0.594947E+09 | 18415.06 | 20-OCT-18:11 | 18415.06 | 0.13 |
November | 0.00 | 0.00 | 19646568.60 | 18740248.25 | 17660.90 | 17-NOV-16:01 | 17660.90 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.324232E+11 | 0.204600E+11 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.851941E+10 | 0.499360E+10 | 24029.14 | 22586.58 | 0.68 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 276407.25 | 276407.25 | 2084.64 | 20-JAN-16:04 | 2084.64 | 0.00 |
February | 0.00 | 0.00 | 18761145.87 | 18761145.87 | 9688.71 | 28-FEB-16:02 | 9688.71 | 0.00 |
March | 0.00 | 0.00 | 0.214814E+09 | 0.214814E+09 | 17004.97 | 28-MAR-18:01 | 17004.97 | 0.00 |
April | 0.00 | 0.00 | 0.105481E+10 | 0.990524E+09 | 19420.99 | 11-APR-18:11 | 19420.99 | 0.03 |
May | 0.00 | 0.00 | 0.398930E+10 | 0.285566E+10 | 21579.97 | 06-MAY-18:42 | 21579.97 | 0.37 |
June | 0.00 | 0.00 | 0.569078E+10 | 0.334333E+10 | 22383.48 | 25-JUN-08:51 | 15096.97 | 0.62 |
July | 0.00 | 0.00 | 0.762922E+10 | 0.433910E+10 | 22885.66 | 25-JUL-21:51 | 15615.69 | 0.67 |
August | 0.00 | 0.00 | 0.525332E+10 | 0.267436E+10 | 21411.65 | 25-AUG-21:51 | 15229.93 | 0.61 |
September | 0.00 | 0.00 | 0.176962E+10 | 0.892996E+09 | 20799.14 | 01-SEP-21:21 | 15177.98 | 0.38 |
October | 0.00 | 0.00 | 0.266533E+09 | 0.201745E+09 | 17017.37 | 21-OCT-15:02 | 17017.37 | 0.04 |
November | 0.00 | 0.00 | 2306004.28 | 1597506.11 | 2474.96 | 15-NOV-19:04 | 2474.96 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.258897E+11 | 0.155332E+11 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.762922E+10 | 0.433910E+10 | 22885.66 | 21579.97 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.711711E+09 | 0.711711E+09 | 22405.38 | 22-FEB-14:30 | 22405.38 | 0.00 |
March | 0.00 | 0.00 | 0.160808E+10 | 0.160808E+10 | 32793.41 | 20-MAR-12:30 | 32793.41 | 0.00 |
April | 0.00 | 0.00 | 0.953499E+10 | 0.914319E+10 | 42665.48 | 22-APR-13:00 | 42665.48 | 0.02 |
May | 0.00 | 0.00 | 0.191033E+11 | 0.131981E+11 | 45005.88 | 18-MAY-13:00 | 38492.97 | 0.31 |
June | 0.00 | 0.00 | 0.234216E+11 | 0.123804E+11 | 48264.04 | 30-JUN-13:00 | 38187.42 | 0.53 |
July | 0.00 | 0.00 | 0.342252E+11 | 0.158546E+11 | 51683.33 | 23-JUL-13:00 | 43606.51 | 0.78 |
August | 0.00 | 0.00 | 0.311240E+11 | 0.156901E+11 | 57943.03 | 25-AUG-14:30 | 47762.10 | 0.71 |
September | 0.00 | 0.00 | 0.201469E+11 | 0.150644E+11 | 57127.40 | 01-SEP-14:20 | 46797.65 | 0.31 |
October | 0.00 | 0.00 | 0.102088E+11 | 0.934904E+10 | 65966.35 | 22-OCT-12:15 | 57336.74 | 0.04 |
November | 0.00 | 0.00 | 0.438519E+09 | 0.438519E+09 | 23231.55 | 17-NOV-13:30 | 23231.55 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150523E+12 | 0.934382E+11 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.342252E+11 | 0.158546E+11 | 65966.35 | 57336.74 | 0.78 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3470859.09 | 3470859.09 | 16534.44 | 29-JAN-09:05 | 16534.44 | 0.00 |
February | 0.00 | 0.00 | 16603113.19 | 16603113.19 | 25134.28 | 07-FEB-19:04 | 25134.28 | 0.00 |
March | 0.00 | 0.00 | 0.230885E+09 | 0.230885E+09 | 29600.87 | 31-MAR-15:03 | 29600.87 | 0.00 |
April | 0.00 | 0.00 | 0.448642E+10 | 0.414134E+10 | 83728.44 | 13-APR-19:41 | 83728.44 | 0.03 |
May | 0.00 | 0.00 | 0.262493E+11 | 0.202272E+11 | 98929.27 | 26-MAY-21:51 | 81780.61 | 0.30 |
June | 0.00 | 0.00 | 0.396438E+11 | 0.263714E+11 | 114607.27 | 19-JUN-21:51 | 70873.17 | 0.51 |
July | 0.00 | 0.00 | 0.465329E+11 | 0.296915E+11 | 112505.13 | 25-JUL-21:51 | 73931.85 | 0.51 |
August | 0.00 | 0.00 | 0.355835E+11 | 0.202643E+11 | 108727.27 | 28-AUG-21:51 | 71802.78 | 0.49 |
September | 0.00 | 0.00 | 0.176866E+11 | 0.901086E+10 | 103521.94 | 18-SEP-21:52 | 70973.57 | 0.53 |
October | 0.00 | 0.00 | 0.324290E+10 | 0.195093E+10 | 80933.21 | 01-OCT-18:01 | 80933.21 | 0.15 |
November | 0.00 | 0.00 | 0.326112E+09 | 0.147536E+09 | 39901.29 | 01-NOV-18:03 | 31676.81 | 0.02 |
December | 0.00 | 0.00 | 3323064.47 | 3323064.47 | 11281.16 | 30-DEC-09:05 | 11281.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174006E+12 | 0.112059E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 3323064.47 | 3323064.47 | 11281.16 | 11281.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.465329E+11 | 0.296915E+11 | 114607.27 | 83728.44 | 0.53 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 52513058.87 | 52513058.87 | 10856.66 | 28-FEB-16:02 | 10856.66 | 0.00 |
March | 0.00 | 0.00 | 0.339283E+09 | 0.339283E+09 | 16200.76 | 26-MAR-15:01 | 16200.76 | 0.00 |
April | 0.00 | 0.00 | 0.196462E+10 | 0.188345E+10 | 16680.95 | 22-APR-19:21 | 16680.95 | 0.03 |
May | 0.00 | 0.00 | 0.473917E+10 | 0.349097E+10 | 19241.79 | 26-MAY-08:51 | 16391.91 | 0.40 |
June | 0.00 | 0.00 | 0.690246E+10 | 0.435667E+10 | 22772.11 | 25-JUN-08:32 | 18023.50 | 0.66 |
July | 0.00 | 0.00 | 0.859932E+10 | 0.519324E+10 | 23241.14 | 23-JUL-08:32 | 17685.02 | 0.70 |
August | 0.00 | 0.00 | 0.641811E+10 | 0.355906E+10 | 21425.19 | 30-AUG-08:51 | 15973.95 | 0.65 |
September | 0.00 | 0.00 | 0.307725E+10 | 0.180607E+10 | 20257.02 | 01-SEP-08:51 | 16681.74 | 0.49 |
October | 0.00 | 0.00 | 0.821900E+09 | 0.556331E+09 | 16216.03 | 21-OCT-15:02 | 16216.03 | 0.12 |
November | 0.00 | 0.00 | 70794697.61 | 69923007.19 | 9556.99 | 16-NOV-09:01 | 9556.99 | 0.00 |
December | 0.00 | 0.00 | 271276.53 | 271276.53 | 1528.03 | 28-DEC-09:04 | 1528.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.329857E+11 | 0.213078E+11 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.859932E+10 | 0.519324E+10 | 23241.14 | 18023.50 | 0.70 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 985794.00 | 985794.00 | 3026.33 | 27-FEB-09:03 | 3026.33 | 0.00 |
March | 0.00 | 0.00 | 92887812.85 | 92887812.85 | 13921.78 | 26-MAR-08:61 | 13921.78 | 0.00 |
April | 0.00 | 0.00 | 0.104308E+10 | 0.995774E+09 | 15406.06 | 18-APR-08:62 | 15406.06 | 0.02 |
May | 0.00 | 0.00 | 0.385015E+10 | 0.273246E+10 | 18187.84 | 26-MAY-08:51 | 15406.75 | 0.39 |
June | 0.00 | 0.00 | 0.631673E+10 | 0.390647E+10 | 21573.21 | 25-JUN-08:32 | 17155.95 | 0.66 |
July | 0.00 | 0.00 | 0.768381E+10 | 0.443439E+10 | 21975.29 | 23-JUL-08:32 | 16713.34 | 0.69 |
August | 0.00 | 0.00 | 0.515899E+10 | 0.266423E+10 | 20122.37 | 30-AUG-08:51 | 14955.44 | 0.64 |
September | 0.00 | 0.00 | 0.190466E+10 | 0.106621E+10 | 19249.65 | 01-SEP-08:51 | 15846.80 | 0.39 |
October | 0.00 | 0.00 | 0.252544E+09 | 0.168323E+09 | 14794.53 | 22-OCT-08:62 | 14794.53 | 0.04 |
November | 0.00 | 0.00 | 3751859.22 | 3020986.23 | 3210.42 | 17-NOV-09:03 | 3210.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.263076E+11 | 0.160648E+11 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.768381E+10 | 0.443439E+10 | 21975.29 | 17155.95 | 0.69 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 243416.90 | 243416.90 | 775.36 | 20-JAN-16:03 | 775.36 | 0.00 |
February | 0.00 | 0.00 | 33227618.09 | 33227618.09 | 4629.55 | 20-FEB-16:01 | 4629.55 | 0.00 |
March | 0.00 | 0.00 | 0.147019E+09 | 0.147019E+09 | 4634.45 | 28-MAR-18:01 | 4634.45 | 0.00 |
April | 0.00 | 0.00 | 0.478187E+09 | 0.455929E+09 | 5739.21 | 11-APR-17:52 | 5739.21 | 0.03 |
May | 0.00 | 0.00 | 0.126094E+10 | 0.955030E+09 | 5938.71 | 06-MAY-18:32 | 5938.71 | 0.36 |
June | 0.00 | 0.00 | 0.162627E+10 | 0.994248E+09 | 6279.62 | 25-JUN-08:51 | 4062.79 | 0.60 |
July | 0.00 | 0.00 | 0.220091E+10 | 0.131446E+10 | 6430.70 | 25-JUL-21:51 | 4351.88 | 0.68 |
August | 0.00 | 0.00 | 0.165135E+10 | 0.925942E+09 | 6139.93 | 27-AUG-21:51 | 4538.54 | 0.63 |
September | 0.00 | 0.00 | 0.681761E+09 | 0.390989E+09 | 5899.73 | 01-SEP-21:21 | 4326.54 | 0.43 |
October | 0.00 | 0.00 | 0.208761E+09 | 0.151081E+09 | 4958.07 | 20-OCT-18:11 | 4958.07 | 0.09 |
November | 0.00 | 0.00 | 4407749.48 | 4177213.42 | 4619.16 | 17-NOV-16:01 | 4619.16 | 0.00 |
December | 0.00 | 0.00 | 6012.87 | 6012.87 | 60.13 | 02-DEC-16:05 | 60.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.829307E+10 | 0.537235E+10 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 6012.87 | 6012.87 | 60.13 | 60.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220091E+10 | 0.131446E+10 | 6430.70 | 5938.71 | 0.68 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2503238.39 | 2503238.39 | 1008.41 | 28-FEB-16:02 | 1008.41 | 0.00 |
March | 0.00 | 0.00 | 53290732.13 | 53290732.13 | 4403.68 | 28-MAR-18:01 | 4403.68 | 0.00 |
April | 0.00 | 0.00 | 0.268065E+09 | 0.253586E+09 | 5098.99 | 11-APR-18:11 | 5098.99 | 0.02 |
May | 0.00 | 0.00 | 0.102798E+10 | 0.752368E+09 | 5685.21 | 06-MAY-18:32 | 5685.21 | 0.34 |
June | 0.00 | 0.00 | 0.147624E+10 | 0.889580E+09 | 5969.70 | 25-JUN-08:51 | 3855.05 | 0.59 |
July | 0.00 | 0.00 | 0.196324E+10 | 0.113781E+10 | 6108.86 | 25-JUL-21:51 | 4133.52 | 0.68 |
August | 0.00 | 0.00 | 0.131448E+10 | 0.680755E+09 | 5761.19 | 10-AUG-21:41 | 3944.08 | 0.60 |
September | 0.00 | 0.00 | 0.388256E+09 | 0.209938E+09 | 5458.40 | 01-SEP-21:21 | 3953.72 | 0.31 |
October | 0.00 | 0.00 | 58298557.54 | 46018595.69 | 4406.81 | 21-OCT-15:02 | 4406.81 | 0.03 |
November | 0.00 | 0.00 | 646294.05 | 451490.39 | 811.98 | 09-NOV-16:03 | 811.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.655300E+10 | 0.402630E+10 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196324E+10 | 0.113781E+10 | 6108.86 | 5685.21 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.412280E+09 | 0.412280E+09 | 22815.16 | 27-JAN-16:01 | 22815.16 | 0.00 |
February | 0.00 | 0.00 | 0.132835E+10 | 0.132835E+10 | 22841.89 | 04-FEB-16:01 | 22841.89 | 0.00 |
March | 0.00 | 0.00 | 0.191189E+10 | 0.191189E+10 | 22856.79 | 26-MAR-15:01 | 22856.79 | 0.00 |
April | 0.00 | 0.00 | 0.355432E+10 | 0.339642E+10 | 25110.34 | 13-APR-19:41 | 25110.34 | 0.05 |
May | 0.00 | 0.00 | 0.639393E+10 | 0.465660E+10 | 26390.56 | 26-MAY-21:51 | 21713.64 | 0.40 |
June | 0.00 | 0.00 | 0.792345E+10 | 0.461441E+10 | 30264.80 | 19-JUN-21:51 | 18320.50 | 0.62 |
July | 0.00 | 0.00 | 0.107452E+11 | 0.624133E+10 | 30452.83 | 30-JUL-08:41 | 19979.22 | 0.68 |
August | 0.00 | 0.00 | 0.965998E+10 | 0.559204E+10 | 29888.58 | 31-AUG-21:51 | 18819.12 | 0.64 |
September | 0.00 | 0.00 | 0.595276E+10 | 0.376267E+10 | 28550.26 | 01-SEP-21:21 | 21170.10 | 0.57 |
October | 0.00 | 0.00 | 0.326333E+10 | 0.252214E+10 | 25559.91 | 20-OCT-18:11 | 25559.91 | 0.22 |
November | 0.00 | 0.00 | 0.901779E+09 | 0.896699E+09 | 22843.64 | 16-NOV-16:02 | 22843.64 | 0.01 |
December | 0.00 | 0.00 | 0.191219E+09 | 0.191219E+09 | 22473.84 | 02-DEC-16:02 | 22473.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.522385E+11 | 0.355260E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.191219E+09 | 0.191219E+09 | 22473.84 | 18320.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107452E+11 | 0.624133E+10 | 30452.83 | 25559.91 | 0.68 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 286674.84 | 735116.28 | 06-JAN-05:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 172326.38 | 713166.86 | 17-FEB-06:00 |
March | 0.04 | 136.32 | 31-MAR-14:00 | 91026.76 | 687592.78 | 05-MAR-06:50 |
April | 0.02 | 99.40 | 19-APR-14:00 | 19991.25 | 182186.16 | 02-APR-08:61 |
May | 0.62 | 1687.70 | 04-MAY-01:00 | 5788.21 | 151870.70 | 11-MAY-22:55 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2247.72 | 172156.49 | 02-JUN-22:30 |
July | 0.09 | 324.20 | 02-JUL-02:50 | 903.04 | 139846.25 | 07-JUL-23:57 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1194.05 | 112523.98 | 18-AUG-23:35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8429.97 | 173678.43 | 07-SEP-01:44 |
October | 0.16 | 457.16 | 09-OCT-15:00 | 21617.98 | 216406.28 | 16-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 61495.90 | 278474.90 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 254369.23 | 711885.37 | 24-DEC-06:07 |
Annual Sum or Average | 0.08 | 76983.24 | ||||
Minimum of Months | 0.00 | 0.00 | 903.04 | 112523.98 | ||
Maximum of Months | 0.62 | 1687.70 | 286674.84 | 735116.28 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 347.89 | 21171.29 | 29-JAN-09:05 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1637.08 | 49804.70 | 22-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2931.61 | 82684.22 | 31-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 17593.56 | 390439.52 | 23-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75599.52 | 508429.51 | 25-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 165133.73 | 691533.13 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218606.66 | 726335.40 | 22-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 156315.77 | 621496.37 | 31-AUG-21:52 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 50779.27 | 458996.61 | 01-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 12737.28 | 285977.63 | 19-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2129.73 | 87359.37 | 01-NOV-15:07 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 246.78 | 14779.00 | 04-DEC-19:07 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 59137.75 | 0.00 | ||||
Minimum of Months | 246.78 | 14779.00 | 0.00 | 0.00 | ||
Maximum of Months | 218606.66 | 726335.40 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 32705.11 | 67623.82 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 33426.83 | 68321.43 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 33320.04 | 68997.59 | 27-MAR-17:39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32327.36 | 74625.58 | 15-APR-07:36 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30760.97 | 79115.58 | 03-MAY-06:31 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 29048.31 | 68145.86 | 04-JUN-07:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27590.54 | 61737.00 | 17-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 26843.12 | 62386.11 | 19-AUG-06:31 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26926.86 | 66728.04 | 05-SEP-06:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27911.46 | 67938.99 | 26-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 29520.27 | 68033.30 | 21-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 31257.04 | 65006.56 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 30116.91 | ||||
Minimum of Months | 0.00 | 0.00 | 26843.12 | 61737.00 | ||
Maximum of Months | 0.00 | 0.00 | 33426.83 | 79115.58 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.92 | 2194.93 | 01-JAN-00:03 | 0.92 |
February | 0.530997E+10 | 0.92 | 2194.93 | 01-FEB-00:03 | 0.92 |
March | 0.587890E+10 | 0.92 | 2194.93 | 01-MAR-00:05 | 0.92 |
April | 0.568926E+10 | 0.92 | 2194.93 | 01-APR-00:10 | 0.92 |
May | 0.587890E+10 | 0.91 | 2194.93 | 01-MAY-00:05 | 0.92 |
June | 0.568926E+10 | 0.91 | 2194.93 | 01-JUN-00:05 | 0.91 |
July | 0.587890E+10 | 0.91 | 2194.93 | 01-JUL-00:10 | 0.91 |
August | 0.587890E+10 | 0.91 | 2194.93 | 01-AUG-00:05 | 0.91 |
September | 0.568926E+10 | 0.91 | 2194.93 | 01-SEP-00:05 | 0.91 |
October | 0.587890E+10 | 0.91 | 2194.93 | 01-OCT-00:10 | 0.91 |
November | 0.568926E+10 | 0.92 | 2194.93 | 01-NOV-00:05 | 0.92 |
December | 0.587890E+10 | 0.92 | 2194.93 | 01-DEC-00:03 | 0.92 |
Annual Sum or Average | 0.692193E+11 | 0.91 | |||
Minimum of Months | 0.530997E+10 | 0.91 | 2194.93 | 0.91 | |
Maximum of Months | 0.587890E+10 | 0.92 | 2194.93 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.289678E+11 | 0.75 | 16583.64 | 19-JAN-21:10 | 0.94 |
February | 0.272819E+11 | 0.76 | 21889.74 | 04-FEB-19:33 | 1.11 |
March | 0.316097E+11 | 0.78 | 33267.88 | 31-MAR-21:41 | 1.43 |
April | 0.328226E+11 | 0.81 | 36740.19 | 20-APR-21:12 | 1.52 |
May | 0.366228E+11 | 0.84 | 36605.27 | 06-MAY-00:30 | 1.52 |
June | 0.363154E+11 | 0.84 | 36051.99 | 03-JUN-03:07 | 1.49 |
July | 0.379776E+11 | 0.85 | 33964.60 | 18-JUL-03:15 | 1.43 |
August | 0.378620E+11 | 0.85 | 38542.30 | 18-AUG-22:33 | 1.55 |
September | 0.360941E+11 | 0.84 | 42200.69 | 14-SEP-21:49 | 1.65 |
October | 0.361306E+11 | 0.83 | 44040.93 | 20-OCT-21:43 | 1.70 |
November | 0.316303E+11 | 0.79 | 36640.32 | 17-NOV-21:15 | 1.52 |
December | 0.293362E+11 | 0.75 | 17207.76 | 06-DEC-21:10 | 0.96 |
Annual Sum or Average | 0.402651E+12 | 0.81 | |||
Minimum of Months | 0.272819E+11 | 0.75 | 16583.64 | 0.94 | |
Maximum of Months | 0.379776E+11 | 0.85 | 44040.93 | 1.70 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:03 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:05 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:05 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:03 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:05 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.987678E+09 | 0.56 | 957.78 | 01-JAN-09:02 | 0.60 |
February | 0.552638E+09 | 0.51 | 957.78 | 01-FEB-09:02 | 0.60 |
March | 0.415436E+09 | 0.48 | 957.78 | 01-MAR-09:01 | 0.60 |
April | 0.264336E+09 | 0.46 | 957.78 | 01-APR-18:01 | 0.60 |
May | 0.289451E+09 | 0.44 | 957.78 | 01-MAY-08:62 | 0.60 |
June | 0.317637E+09 | 0.41 | 957.78 | 01-JUN-08:51 | 0.60 |
July | 0.403526E+09 | 0.41 | 957.78 | 01-JUL-08:51 | 0.60 |
August | 0.312476E+09 | 0.40 | 957.78 | 01-AUG-08:51 | 0.59 |
September | 0.194826E+09 | 0.43 | 957.78 | 01-SEP-08:51 | 0.59 |
October | 0.238839E+09 | 0.45 | 957.78 | 01-OCT-15:01 | 0.60 |
November | 0.387587E+09 | 0.48 | 957.78 | 01-NOV-08:62 | 0.60 |
December | 0.907910E+09 | 0.57 | 957.78 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.527234E+10 | 0.47 | |||
Minimum of Months | 0.194826E+09 | 0.40 | 957.78 | 0.59 | |
Maximum of Months | 0.987678E+09 | 0.57 | 957.78 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112986E+10 | 0.59 | 913.32 | 01-JAN-03:20 | 0.60 |
February | 0.646128E+09 | 0.55 | 913.32 | 01-FEB-09:02 | 0.60 |
March | 0.456522E+09 | 0.52 | 913.32 | 01-MAR-09:01 | 0.60 |
April | 0.243872E+09 | 0.44 | 913.32 | 01-APR-08:62 | 0.60 |
May | 0.244560E+09 | 0.42 | 913.32 | 01-MAY-08:62 | 0.60 |
June | 0.291405E+09 | 0.39 | 913.32 | 01-JUN-08:51 | 0.60 |
July | 0.364013E+09 | 0.40 | 913.32 | 01-JUL-08:51 | 0.60 |
August | 0.256101E+09 | 0.38 | 913.32 | 01-AUG-08:51 | 0.59 |
September | 0.141756E+09 | 0.39 | 913.32 | 01-SEP-08:51 | 0.59 |
October | 0.231520E+09 | 0.43 | 913.32 | 01-OCT-15:01 | 0.60 |
November | 0.424959E+09 | 0.52 | 913.32 | 01-NOV-08:62 | 0.60 |
December | 0.102795E+10 | 0.59 | 913.32 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.545865E+10 | 0.47 | |||
Minimum of Months | 0.141756E+09 | 0.38 | 913.32 | 0.59 | |
Maximum of Months | 0.112986E+10 | 0.59 | 913.32 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.366771E+10 | 0.49 | 6181.97 | 05-JAN-01:20 | 0.61 |
February | 0.151201E+10 | 0.29 | 6181.97 | 17-FEB-04:40 | 0.61 |
March | 0.814749E+09 | 0.21 | 5866.16 | 05-MAR-05:00 | 0.61 |
April | 0.502325E+09 | 0.15 | 1790.01 | 22-APR-13:00 | 0.60 |
May | 0.102495E+10 | 0.34 | 1816.44 | 18-MAY-13:10 | 0.60 |
June | 0.114776E+10 | 0.39 | 1818.96 | 30-JUN-13:00 | 0.60 |
July | 0.153988E+10 | 0.47 | 1938.90 | 23-JUL-13:10 | 0.60 |
August | 0.141807E+10 | 0.43 | 2856.85 | 25-AUG-12:30 | 0.60 |
September | 0.100318E+10 | 0.29 | 3227.01 | 04-SEP-12:20 | 0.60 |
October | 0.562764E+09 | 0.13 | 3546.35 | 22-OCT-12:15 | 0.60 |
November | 0.881542E+09 | 0.26 | 1683.60 | 25-NOV-06:00 | 0.60 |
December | 0.367461E+10 | 0.54 | 6181.97 | 24-DEC-02:40 | 0.61 |
Annual Sum or Average | 0.177496E+11 | 0.33 | |||
Minimum of Months | 0.502325E+09 | 0.13 | 1683.60 | 0.60 | |
Maximum of Months | 0.367461E+10 | 0.54 | 6181.97 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.575917E+10 | 0.54 | 4631.16 | 01-JAN-00:31 | 0.60 |
February | 0.321529E+10 | 0.49 | 4631.16 | 01-FEB-09:02 | 0.60 |
March | 0.211489E+10 | 0.45 | 4631.16 | 01-MAR-09:01 | 0.60 |
April | 0.877142E+09 | 0.41 | 4631.16 | 01-APR-15:02 | 0.60 |
May | 0.141965E+10 | 0.35 | 4631.16 | 01-MAY-18:02 | 0.60 |
June | 0.190968E+10 | 0.32 | 4631.16 | 01-JUN-08:51 | 0.60 |
July | 0.211785E+10 | 0.31 | 4631.16 | 01-JUL-08:51 | 0.60 |
August | 0.156660E+10 | 0.29 | 4631.16 | 01-AUG-08:51 | 0.59 |
September | 0.941249E+09 | 0.36 | 4631.16 | 01-SEP-08:51 | 0.59 |
October | 0.752119E+09 | 0.42 | 4631.16 | 01-OCT-08:62 | 0.60 |
November | 0.161897E+10 | 0.44 | 4631.16 | 02-NOV-15:01 | 0.60 |
December | 0.496888E+10 | 0.53 | 4631.16 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.272615E+11 | 0.41 | |||
Minimum of Months | 0.752119E+09 | 0.29 | 4631.16 | 0.59 | |
Maximum of Months | 0.575917E+10 | 0.54 | 4631.16 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.951167E+09 | 0.57 | 869.52 | 01-JAN-09:02 | 0.60 |
February | 0.523286E+09 | 0.50 | 869.52 | 01-FEB-09:02 | 0.60 |
March | 0.375311E+09 | 0.48 | 869.52 | 01-MAR-09:01 | 0.60 |
April | 0.254748E+09 | 0.48 | 869.52 | 01-APR-15:02 | 0.60 |
May | 0.278484E+09 | 0.46 | 869.52 | 01-MAY-08:62 | 0.60 |
June | 0.344783E+09 | 0.43 | 869.52 | 01-JUN-08:51 | 0.60 |
July | 0.401192E+09 | 0.42 | 869.52 | 01-JUL-08:32 | 0.60 |
August | 0.307387E+09 | 0.40 | 869.52 | 01-AUG-08:51 | 0.59 |
September | 0.205299E+09 | 0.44 | 869.52 | 01-SEP-08:51 | 0.59 |
October | 0.230365E+09 | 0.45 | 869.52 | 01-OCT-08:62 | 0.60 |
November | 0.369684E+09 | 0.49 | 869.52 | 01-NOV-08:62 | 0.60 |
December | 0.875709E+09 | 0.58 | 869.52 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.511742E+10 | 0.47 | |||
Minimum of Months | 0.205299E+09 | 0.40 | 869.52 | 0.59 | |
Maximum of Months | 0.951167E+09 | 0.58 | 869.52 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105957E+10 | 0.59 | 825.34 | 01-JAN-01:05 | 0.60 |
February | 0.631562E+09 | 0.55 | 825.34 | 01-FEB-09:02 | 0.60 |
March | 0.430502E+09 | 0.50 | 825.34 | 01-MAR-09:01 | 0.60 |
April | 0.221643E+09 | 0.44 | 825.34 | 01-APR-08:62 | 0.60 |
May | 0.236014E+09 | 0.44 | 825.34 | 01-MAY-08:62 | 0.60 |
June | 0.319125E+09 | 0.43 | 825.34 | 01-JUN-08:51 | 0.60 |
July | 0.362217E+09 | 0.42 | 825.34 | 01-JUL-08:32 | 0.60 |
August | 0.250352E+09 | 0.40 | 825.34 | 01-AUG-08:51 | 0.59 |
September | 0.151052E+09 | 0.41 | 825.34 | 01-SEP-08:51 | 0.59 |
October | 0.222847E+09 | 0.43 | 825.34 | 01-OCT-08:62 | 0.60 |
November | 0.404753E+09 | 0.52 | 825.34 | 01-NOV-08:62 | 0.60 |
December | 0.968828E+09 | 0.59 | 825.34 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.525847E+10 | 0.48 | |||
Minimum of Months | 0.151052E+09 | 0.40 | 825.34 | 0.59 | |
Maximum of Months | 0.105957E+10 | 0.59 | 825.34 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.292631E+09 | 0.58 | 249.21 | 01-JAN-09:02 | 0.60 |
February | 0.169584E+09 | 0.53 | 249.21 | 01-FEB-09:02 | 0.60 |
March | 0.125447E+09 | 0.50 | 249.21 | 01-MAR-09:01 | 0.60 |
April | 77792565.69 | 0.47 | 249.21 | 01-APR-08:62 | 0.60 |
May | 78275981.51 | 0.44 | 249.21 | 01-MAY-08:62 | 0.60 |
June | 84547350.81 | 0.41 | 249.21 | 01-JUN-08:51 | 0.60 |
July | 0.105759E+09 | 0.41 | 249.21 | 01-JUL-08:51 | 0.60 |
August | 80885058.12 | 0.39 | 249.21 | 01-AUG-08:51 | 0.59 |
September | 51218048.69 | 0.43 | 249.21 | 01-SEP-08:51 | 0.59 |
October | 72665538.32 | 0.47 | 249.21 | 01-OCT-15:01 | 0.60 |
November | 0.118447E+09 | 0.51 | 249.21 | 01-NOV-08:62 | 0.60 |
December | 0.274791E+09 | 0.59 | 249.21 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.153204E+10 | 0.48 | |||
Minimum of Months | 51218048.69 | 0.39 | 249.21 | 0.59 | |
Maximum of Months | 0.292631E+09 | 0.59 | 249.21 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.320700E+09 | 0.60 | 236.64 | 01-JAN-01:15 | 0.60 |
February | 0.200421E+09 | 0.57 | 236.64 | 01-FEB-09:02 | 0.60 |
March | 0.139168E+09 | 0.54 | 236.64 | 01-MAR-09:01 | 0.60 |
April | 72474716.44 | 0.45 | 236.64 | 01-APR-08:62 | 0.60 |
May | 66926303.26 | 0.42 | 236.64 | 01-MAY-08:62 | 0.60 |
June | 77433059.69 | 0.40 | 236.64 | 01-JUN-08:51 | 0.60 |
July | 94947030.95 | 0.40 | 236.64 | 01-JUL-08:51 | 0.60 |
August | 65938310.43 | 0.38 | 236.64 | 01-AUG-08:51 | 0.59 |
September | 39032483.79 | 0.39 | 236.64 | 01-SEP-08:51 | 0.59 |
October | 71886870.52 | 0.45 | 236.64 | 01-OCT-15:01 | 0.60 |
November | 0.129821E+09 | 0.55 | 236.64 | 01-NOV-08:62 | 0.60 |
December | 0.299797E+09 | 0.59 | 236.64 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.157855E+10 | 0.48 | |||
Minimum of Months | 39032483.79 | 0.38 | 236.64 | 0.59 | |
Maximum of Months | 0.320700E+09 | 0.60 | 236.64 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102564E+10 | 0.53 | 1223.20 | 01-JAN-09:02 | 0.60 |
February | 0.616533E+09 | 0.51 | 1223.20 | 01-FEB-09:02 | 0.60 |
March | 0.505521E+09 | 0.49 | 1223.20 | 01-MAR-09:01 | 0.60 |
April | 0.360317E+09 | 0.48 | 1223.20 | 02-APR-08:61 | 0.60 |
May | 0.363427E+09 | 0.44 | 1223.20 | 01-MAY-15:02 | 0.60 |
June | 0.386224E+09 | 0.40 | 1223.20 | 01-JUN-08:51 | 0.60 |
July | 0.491342E+09 | 0.41 | 1223.20 | 01-JUL-08:51 | 0.60 |
August | 0.452070E+09 | 0.39 | 1223.20 | 01-AUG-08:51 | 0.59 |
September | 0.336848E+09 | 0.44 | 1223.20 | 01-SEP-08:51 | 0.59 |
October | 0.367646E+09 | 0.45 | 1223.20 | 01-OCT-08:62 | 0.60 |
November | 0.454078E+09 | 0.48 | 1223.20 | 01-NOV-08:62 | 0.60 |
December | 0.986815E+09 | 0.54 | 1223.20 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.634646E+10 | 0.46 | |||
Minimum of Months | 0.336848E+09 | 0.39 | 1223.20 | 0.59 | |
Maximum of Months | 0.102564E+10 | 0.54 | 1223.20 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.361090E+10 | 0.324981E+10 | 2107.76 | 04-JAN-05:40 | 1896.99 | 1896.99 | 35.26 | 6.73 |
February | 0.243261E+10 | 0.218935E+10 | 2107.76 | 14-FEB-04:15 | 1896.99 | 1896.99 | 35.02 | 6.73 |
March | 0.184196E+10 | 0.165776E+10 | 2093.86 | 05-MAR-07:03 | 1884.47 | 1884.47 | 35.56 | 6.69 |
April | 0.643749E+09 | 0.579374E+09 | 1081.23 | 05-APR-06:10 | 973.11 | 973.11 | 37.27 | 1.56 |
May | 0.177613E+09 | 0.159852E+09 | 1083.28 | 21-MAY-06:24 | 974.95 | 974.95 | 48.24 | 1.56 |
June | 57968293.56 | 52171464.21 | 1026.35 | 08-JUN-01:49 | 923.71 | 923.71 | 33.62 | 1.44 |
July | 26700411.84 | 24030370.65 | 941.47 | 07-JUL-23:57 | 847.33 | 847.33 | 33.72 | 1.27 |
August | 34072677.72 | 30665409.95 | 1048.17 | 19-AUG-01:43 | 943.35 | 943.35 | 43.99 | 1.48 |
September | 0.249768E+09 | 0.224791E+09 | 1139.11 | 15-SEP-00:50 | 1025.20 | 1025.20 | 54.21 | 1.69 |
October | 0.753545E+09 | 0.678191E+09 | 1275.99 | 16-OCT-08:62 | 1148.39 | 1148.39 | 35.13 | 2.08 |
November | 0.154448E+10 | 0.139003E+10 | 1450.73 | 25-NOV-07:10 | 1305.65 | 1305.65 | 37.90 | 2.79 |
December | 0.345096E+10 | 0.310586E+10 | 2107.76 | 20-DEC-00:25 | 1896.99 | 1896.99 | 35.69 | 6.73 |
Annual Sum or Average | 0.148243E+11 | 0.133419E+11 | ||||||
Minimum of Months | 26700411.84 | 24030370.65 | 941.47 | 847.33 | 847.33 | 33.62 | 1.27 | |
Maximum of Months | 0.361090E+10 | 0.324981E+10 | 2107.76 | 1896.99 | 1896.99 | 54.21 | 6.73 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 146590.12 | 131931.11 | 10.16 | 29-JAN-09:05 | 9.14 | 9.14 | 6.72 | 1.54 |
February | 1214095.57 | 1092686.01 | 39.81 | 22-FEB-16:02 | 35.83 | 35.83 | 6.72 | 3.53 |
March | 3171414.72 | 2854273.25 | 73.51 | 31-MAR-15:03 | 66.16 | 66.16 | 6.72 | 4.91 |
April | 32903119.48 | 29612807.53 | 582.13 | 23-APR-15:02 | 523.91 | 523.91 | 6.72 | 13.29 |
May | 0.193489E+09 | 0.174140E+09 | 918.42 | 25-MAY-18:02 | 826.57 | 826.57 | 6.72 | 16.23 |
June | 0.456488E+09 | 0.410839E+09 | 1798.47 | 29-JUN-18:03 | 1618.62 | 1618.62 | 6.72 | 21.56 |
July | 0.639155E+09 | 0.575240E+09 | 1412.38 | 03-JUL-18:02 | 1271.14 | 1271.14 | 6.72 | 19.50 |
August | 0.397851E+09 | 0.358066E+09 | 1163.43 | 08-AUG-18:03 | 1047.09 | 1047.09 | 6.72 | 17.96 |
September | 0.102815E+09 | 92533899.44 | 755.03 | 01-SEP-15:13 | 679.52 | 679.52 | 6.72 | 14.91 |
October | 24758252.20 | 22282426.98 | 601.84 | 19-OCT-15:03 | 541.65 | 541.65 | 6.72 | 13.49 |
November | 1305857.98 | 1175272.18 | 35.03 | 01-NOV-15:07 | 31.52 | 31.52 | 6.72 | 3.28 |
December | 72918.73 | 65626.86 | 6.68 | 30-DEC-09:05 | 6.02 | 6.02 | 6.72 | 1.16 |
Annual Sum or Average | 0.185337E+10 | 0.166803E+10 | ||||||
Minimum of Months | 72918.73 | 65626.86 | 6.68 | 6.02 | 6.02 | 6.72 | 1.16 | |
Maximum of Months | 0.639155E+09 | 0.575240E+09 | 1798.47 | 1618.62 | 1618.62 | 6.72 | 21.56 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.566103E+09 | 0.509493E+09 | 3851.04 | 01-JAN-10:31 | 3465.94 | 3465.94 | 6.73 | 34.07 |
February | 0.178018E+10 | 0.160216E+10 | 3851.04 | 01-FEB-11:00 | 3465.94 | 3465.94 | 6.73 | 34.07 |
March | 0.284272E+10 | 0.255845E+10 | 3851.04 | 01-MAR-00:05 | 3465.94 | 3465.94 | 6.72 | 34.07 |
April | 0.606825E+10 | 0.546142E+10 | 3851.04 | 01-APR-01:07 | 3465.94 | 3465.94 | 6.72 | 34.07 |
May | 0.966362E+10 | 0.869725E+10 | 3851.04 | 01-MAY-00:10 | 3465.94 | 3465.94 | 6.72 | 34.07 |
June | 0.980156E+10 | 0.882141E+10 | 3851.04 | 01-JUN-00:05 | 3465.94 | 3465.94 | 6.78 | 34.07 |
July | 0.102261E+11 | 0.920345E+10 | 3851.04 | 01-JUL-00:10 | 3465.94 | 3465.94 | 7.30 | 34.07 |
August | 0.101831E+11 | 0.916481E+10 | 3851.04 | 01-AUG-00:05 | 3465.94 | 3465.94 | 7.44 | 34.07 |
September | 0.891349E+10 | 0.802215E+10 | 3851.04 | 01-SEP-00:05 | 3465.94 | 3465.94 | 8.42 | 34.07 |
October | 0.548261E+10 | 0.493435E+10 | 3851.04 | 01-OCT-00:10 | 3465.94 | 3465.94 | 6.78 | 34.07 |
November | 0.251092E+10 | 0.225983E+10 | 3851.04 | 01-NOV-00:10 | 3465.94 | 3465.94 | 6.72 | 34.07 |
December | 0.487790E+09 | 0.439011E+09 | 3851.04 | 01-DEC-09:05 | 3465.94 | 3465.94 | 6.78 | 34.07 |
Annual Sum or Average | 0.685264E+11 | 0.616738E+11 | ||||||
Minimum of Months | 0.487790E+09 | 0.439011E+09 | 3851.04 | 3465.94 | 3465.94 | 6.72 | 34.07 | |
Maximum of Months | 0.102261E+11 | 0.920345E+10 | 3851.04 | 3465.94 | 3465.94 | 8.42 | 34.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 45.78 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 46.54 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 46.63 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 49.86 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 50.22 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 50.80 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.34 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 51.66 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 51.31 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.01 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 50.71 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 47.59 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 45.78 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 51.66 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 37.02 | 60.00 | 286674.84 | 735116.28 | 06-JAN-05:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 37.09 | 60.00 | 172326.38 | 713166.86 | 17-FEB-06:00 |
March | 0.04 | 136.32 | 31-MAR-14:00 | 60.06 | 60.06 | 91026.76 | 687592.78 | 05-MAR-06:50 |
April | 0.02 | 99.40 | 19-APR-14:00 | 60.03 | 60.03 | 19991.25 | 182186.16 | 02-APR-08:61 |
May | 0.62 | 1687.70 | 04-MAY-01:00 | 60.31 | 60.31 | 5788.21 | 151870.70 | 11-MAY-22:55 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 40.55 | 60.00 | 2247.72 | 172156.49 | 02-JUN-22:30 |
July | 0.09 | 324.20 | 02-JUL-02:50 | 60.07 | 60.07 | 903.04 | 139846.25 | 07-JUL-23:57 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 45.40 | 45.40 | 1194.05 | 112523.98 | 18-AUG-23:35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 42.34 | 42.34 | 8429.97 | 173678.43 | 07-SEP-01:44 |
October | 0.16 | 457.16 | 09-OCT-15:00 | 60.14 | 60.14 | 21617.98 | 216406.28 | 16-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 48.37 | 60.00 | 61495.90 | 278474.90 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 40.75 | 60.00 | 254369.23 | 711885.37 | 24-DEC-06:07 |
Annual Sum or Average | 0.08 | 76983.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.02 | 42.34 | 903.04 | 112523.98 | ||
Maximum of Months | 0.62 | 1687.70 | 60.31 | 60.31 | 286674.84 | 735116.28 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 347.89 | 21171.29 | 29-JAN-09:05 | 6.85 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1637.08 | 49804.70 | 22-FEB-16:02 | 7.05 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2931.61 | 82684.22 | 31-MAR-15:03 | 7.28 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 17593.56 | 390439.52 | 23-APR-18:03 | 9.43 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75599.52 | 508429.51 | 25-MAY-18:03 | 10.26 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 165133.73 | 691533.13 | 29-JUN-18:03 | 11.55 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218606.66 | 726335.40 | 22-JUL-21:52 | 11.79 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 156315.77 | 621496.37 | 31-AUG-21:52 | 11.05 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 50779.27 | 458996.61 | 01-SEP-15:03 | 9.91 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 12737.28 | 285977.63 | 19-OCT-15:03 | 8.70 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2129.73 | 87359.37 | 01-NOV-15:07 | 7.31 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 246.78 | 14779.00 | 04-DEC-19:07 | 6.80 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 59137.75 | 0.00 | ||||||
Minimum of Months | 246.78 | 14779.00 | 6.80 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 218606.66 | 726335.40 | 11.79 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 45.78 | 59.76 | 32705.11 | 67623.82 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46.54 | 58.83 | 33426.83 | 68321.43 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 46.63 | 58.85 | 33320.04 | 68997.59 | 27-MAR-17:39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 49.86 | 58.59 | 32327.36 | 74625.58 | 15-APR-07:36 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 50.22 | 58.89 | 30760.97 | 79115.58 | 03-MAY-06:31 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 50.80 | 59.04 | 29048.31 | 68145.86 | 04-JUN-07:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.34 | 58.79 | 27590.54 | 61737.00 | 17-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 51.66 | 59.07 | 26843.12 | 62386.11 | 19-AUG-06:31 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 51.31 | 58.40 | 26926.86 | 66728.04 | 05-SEP-06:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.01 | 59.40 | 27911.46 | 67938.99 | 26-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 50.71 | 58.35 | 29520.27 | 68033.30 | 21-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 47.59 | 58.51 | 31257.04 | 65006.56 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 30116.91 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.78 | 58.35 | 26843.12 | 61737.00 | ||
Maximum of Months | 0.00 | 0.00 | 51.66 | 59.76 | 33426.83 | 79115.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.528385E+12 | 0.00 | 4252751.44 | 0.289678E+11 | 0.00 | 0.00 |
February | 0.278806E+12 | 0.00 | 62131457.28 | 0.272819E+11 | 0.00 | 0.00 |
March | 0.154970E+12 | 0.00 | 0.144057E+09 | 0.316097E+11 | 0.00 | 0.00 |
April | 0.310625E+11 | 0.00 | 0.136926E+11 | 0.328226E+11 | 0.00 | 0.00 |
May | 0.141750E+11 | 0.00 | 0.104106E+12 | 0.366228E+11 | 0.00 | 0.00 |
June | 0.568404E+10 | 0.00 | 0.271758E+12 | 0.363154E+11 | 0.00 | 0.00 |
July | 0.240268E+10 | 0.00 | 0.380595E+12 | 0.379776E+11 | 0.00 | 0.00 |
August | 0.300274E+10 | 0.00 | 0.259339E+12 | 0.378620E+11 | 0.00 | 0.00 |
September | 0.199984E+11 | 0.00 | 0.583751E+11 | 0.360941E+11 | 0.00 | 0.00 |
October | 0.376582E+11 | 0.00 | 0.855039E+10 | 0.361306E+11 | 0.00 | 0.00 |
November | 0.830724E+11 | 0.00 | 0.127489E+10 | 0.316303E+11 | 0.00 | 0.00 |
December | 0.456853E+12 | 0.00 | 16114192.88 | 0.293362E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.161607E+13 | 0.00 | 0.109792E+13 | 0.402651E+12 | 0.00 | 0.00 |
Minimum of Months | 0.240268E+10 | 0.00 | 4252751.44 | 0.272819E+11 | 0.00 | 0.00 |
Maximum of Months | 0.528385E+12 | 0.00 | 0.380595E+12 | 0.379776E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.493115E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.281189E+11 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.161768E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.192736E+10 | 0.00 | 0.220450E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 38270476.02 | 0.00 | 0.181486E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 28379.49 | 0.00 | 0.481002E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 25378.21 | 0.00 | 0.674810E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 29874.83 | 0.00 | 0.474239E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 12787.74 | 0.00 | 0.106511E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.820670E+09 | 0.00 | 0.144276E+10 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.857434E+10 | 0.00 | 0.223309E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.433020E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.148270E+12 | 0.00 | 0.195675E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 12787.74 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.493115E+11 | 0.00 | 0.674810E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.289678E+11 | 4252751.44 | 0.528385E+12 | 0.682926E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272819E+11 | 62131457.28 | 0.278806E+12 | 0.664511E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316097E+11 | 0.144057E+09 | 0.154970E+12 | 0.699036E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328226E+11 | 0.136926E+11 | 0.310625E+11 | 0.409414E+12 | 55729426.13 | 0.00 | 0.00 | 0.00 |
May | 0.366228E+11 | 0.104106E+12 | 0.141750E+11 | 0.116536E+12 | 0.189796E+10 | 0.00 | 0.00 | 0.00 |
June | 0.363154E+11 | 0.271758E+12 | 0.568404E+10 | 0.298399E+11 | 0.318556E+11 | 0.00 | 0.00 | 0.00 |
July | 0.379776E+11 | 0.380595E+12 | 0.240268E+10 | 0.134512E+11 | 0.418562E+11 | 0.00 | 0.00 | 0.00 |
August | 0.378620E+11 | 0.259339E+12 | 0.300274E+10 | 0.151929E+11 | 0.149303E+11 | 0.00 | 0.00 | 0.00 |
September | 0.360941E+11 | 0.583757E+11 | 0.199984E+11 | 0.956073E+11 | 94404751.85 | 0.00 | 0.00 | 0.00 |
October | 0.361306E+11 | 0.855099E+10 | 0.376582E+11 | 0.344223E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316303E+11 | 0.127489E+10 | 0.830724E+11 | 0.598941E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293362E+11 | 16114192.88 | 0.456853E+12 | 0.693309E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402651E+12 | 0.109792E+13 | 0.161607E+13 | 0.436299E+13 | 0.906902E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272819E+11 | 4252751.44 | 0.240268E+10 | 0.134512E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.379776E+11 | 0.380595E+12 | 0.528385E+12 | 0.699036E+12 | 0.418562E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.00 | 0.493115E+11 | 0.125181E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.00 | 0.281189E+11 | 0.120408E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.00 | 0.161768E+11 | 0.125691E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.220450E+10 | 0.192736E+10 | 0.762646E+11 | 0.130570E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.181486E+11 | 38270476.02 | 0.260400E+11 | 0.168158E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.481002E+11 | 28379.49 | 0.744355E+10 | 0.101509E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.674810E+11 | 25378.21 | 0.345035E+10 | 0.150282E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.474239E+11 | 29874.83 | 0.417615E+10 | 0.639330E+10 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.106511E+11 | 12787.74 | 0.251326E+11 | 0.296641E+09 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.144276E+10 | 0.820670E+09 | 0.698188E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.223309E+09 | 0.857434E+10 | 0.107192E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.00 | 0.433020E+11 | 0.125922E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.195675E+12 | 0.148270E+12 | 0.816720E+12 | 0.336811E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.00 | 12787.74 | 0.345035E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.674810E+11 | 0.493115E+11 | 0.125922E+12 | 0.150282E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.289678E+11 | 0.528385E+12 | 4252751.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272819E+11 | 0.278806E+12 | 62131457.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316097E+11 | 0.154970E+12 | 0.144057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328226E+11 | 0.310625E+11 | 0.136926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.366228E+11 | 0.141750E+11 | 0.104106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.363154E+11 | 0.568404E+10 | 0.271758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.379776E+11 | 0.240268E+10 | 0.380595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.378620E+11 | 0.300274E+10 | 0.259339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360941E+11 | 0.199984E+11 | 0.583751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361306E+11 | 0.376582E+11 | 0.855039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316303E+11 | 0.830724E+11 | 0.127489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293362E+11 | 0.456853E+12 | 16114192.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402651E+12 | 0.161607E+13 | 0.109792E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272819E+11 | 0.240268E+10 | 4252751.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.379776E+11 | 0.528385E+12 | 0.380595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.493115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.281189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.161768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.192736E+10 | 0.220450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 38270476.02 | 0.181486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 28379.49 | 0.481002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 25378.21 | 0.674810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 29874.83 | 0.474239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 12787.74 | 0.106511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.820670E+09 | 0.144276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.857434E+10 | 0.223309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.433020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.148270E+12 | 0.195675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 12787.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.493115E+11 | 0.674810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.589396E+11 | 0.00 | 0.00 | 1444827.33 | 0.00 | 0.371405E+11 | 0.300703E+10 | 0.00 | 0.98 |
February | 0.616228E+11 | 0.00 | 0.00 | 722422.57 | 0.00 | 0.384333E+10 | 0.266584E+10 | 0.00 | 0.96 |
March | 0.591252E+11 | 0.00 | 0.00 | 12928.81 | 0.00 | 0.292722E+09 | 97021193.75 | 0.00 | 0.94 |
April | 0.466138E+11 | 0.00 | 0.00 | 232.19 | 0.00 | 0.00 | 8530610.82 | 0.00 | 0.93 |
May | 0.408969E+11 | 0.00 | 0.00 | 6310.66 | 0.107375E+09 | 0.00 | 0.129197E+09 | 0.00 | 0.96 |
June | 0.257754E+11 | 0.245014E+09 | 0.00 | 514592.40 | 0.352633E+10 | 0.00 | 0.176072E+10 | 0.00 | 0.99 |
July | 0.126693E+11 | 0.155141E+10 | 0.00 | 10683122.76 | 0.475791E+10 | 0.00 | 0.957881E+10 | 0.00 | 1.00 |
August | 0.350127E+10 | 0.113083E+10 | 0.00 | 44242447.47 | 0.139980E+10 | 0.00 | 0.273129E+11 | 0.00 | 1.06 |
September | 0.319258E+10 | 535429.51 | 0.00 | 90406752.72 | 16893864.16 | 0.00 | 0.466399E+11 | 0.00 | 1.06 |
October | 0.325748E+10 | 0.00 | 0.00 | 0.119189E+09 | 0.00 | 0.00 | 0.534701E+11 | 0.00 | 1.03 |
November | 0.323373E+10 | 0.00 | 0.00 | 66143553.48 | 0.00 | 0.00 | 0.513400E+11 | 0.00 | 1.02 |
December | 0.647300E+11 | 0.00 | 0.00 | 7442435.05 | 0.00 | 0.145166E+11 | 0.117932E+11 | 0.00 | 0.98 |
Annual Sum or Average | 0.383558E+12 | 0.292780E+10 | 0.00 | 0.340808E+09 | 0.980831E+10 | 0.557931E+11 | 0.207803E+12 | 0.00 | 0.99 |
Minimum of Months | 0.319258E+10 | 0.00 | 0.00 | 232.19 | 0.00 | 0.00 | 8530610.82 | 0.00 | 0.93 |
Maximum of Months | 0.647300E+11 | 0.155141E+10 | 0.00 | 0.119189E+09 | 0.475791E+10 | 0.371405E+11 | 0.534701E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118786E+10 | 0.00 | 0.00 | 26351.54 | 0.00 | 0.151689E+11 | 85801506.58 | 0.00 | 2.93 |
February | 0.273104E+10 | 0.00 | 0.00 | 559044.11 | 0.00 | 0.817939E+10 | 0.466678E+09 | 0.00 | 2.89 |
March | 0.441763E+10 | 0.00 | 0.00 | 976450.60 | 0.00 | 0.494936E+10 | 0.560738E+09 | 0.00 | 2.84 |
April | 0.598352E+10 | 0.00 | 0.00 | 2030092.09 | 0.00 | 0.103239E+10 | 0.811077E+09 | 0.00 | 2.86 |
May | 0.625417E+10 | 17212030.41 | 0.00 | 1700555.50 | 2384596.56 | 3608358.22 | 0.569522E+09 | 0.00 | 2.93 |
June | 0.427995E+10 | 0.398593E+09 | 0.00 | 834342.18 | 0.272180E+09 | 0.00 | 0.281477E+09 | 0.00 | 2.99 |
July | 0.331964E+10 | 0.644753E+09 | 0.00 | 948719.81 | 0.457999E+09 | 0.00 | 0.358738E+09 | 0.00 | 3.05 |
August | 0.438423E+10 | 0.281524E+09 | 0.00 | 1835073.48 | 0.153006E+09 | 238241.28 | 0.522802E+09 | 0.00 | 3.12 |
September | 0.646696E+10 | 3875100.65 | 0.00 | 2592458.17 | 23993.11 | 7419881.01 | 0.102952E+10 | 0.00 | 2.98 |
October | 0.686578E+10 | 0.00 | 0.00 | 2127465.08 | 0.00 | 0.683148E+09 | 0.845641E+09 | 0.00 | 2.86 |
November | 0.393101E+10 | 0.00 | 0.00 | 620635.66 | 0.00 | 0.407559E+10 | 0.330055E+09 | 0.00 | 2.82 |
December | 0.121856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138456E+11 | 0.00 | 0.00 | 2.90 |
Annual Sum or Average | 0.510404E+11 | 0.134596E+10 | 0.00 | 14251188.21 | 0.885594E+09 | 0.479456E+11 | 0.586205E+10 | 0.00 | 2.93 |
Minimum of Months | 0.118786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 |
Maximum of Months | 0.686578E+10 | 0.644753E+09 | 0.00 | 2592458.17 | 0.457999E+09 | 0.151689E+11 | 0.102952E+10 | 0.00 | 3.12 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.425339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456900E+10 | 0.00 | 0.00 | 1.36 |
February | 0.458902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148802E+10 | 0.00 | 0.00 | 1.33 |
March | 0.489452E+10 | 0.00 | 0.00 | 26651.48 | 0.00 | 0.340615E+09 | 61377192.71 | 0.00 | 1.31 |
April | 0.370029E+10 | 0.00 | 0.00 | 567603.70 | 0.00 | 0.00 | 0.454763E+09 | 0.00 | 1.30 |
May | 0.233136E+10 | 4878953.44 | 0.00 | 1899655.48 | 4817717.66 | 0.00 | 0.137151E+10 | 0.00 | 1.37 |
June | 0.134968E+10 | 0.237341E+09 | 0.00 | 1777650.55 | 0.120058E+09 | 0.00 | 0.114713E+10 | 0.00 | 1.42 |
July | 0.593613E+09 | 0.432982E+09 | 0.00 | 2413298.11 | 0.164520E+09 | 0.00 | 0.144822E+10 | 0.00 | 1.45 |
August | 0.924810E+09 | 0.124362E+09 | 0.00 | 2523439.30 | 0.100486E+09 | 0.00 | 0.176706E+10 | 0.00 | 1.46 |
September | 0.264925E+10 | 152703.18 | 0.00 | 1465350.32 | 1397262.39 | 0.00 | 0.134624E+10 | 0.00 | 1.35 |
October | 0.389684E+10 | 0.00 | 0.00 | 511995.96 | 0.00 | 0.00 | 0.505110E+09 | 0.00 | 1.28 |
November | 0.444972E+10 | 0.00 | 0.00 | 2265.57 | 0.00 | 0.00 | 9909632.07 | 0.00 | 1.31 |
December | 0.443697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365075E+10 | 0.00 | 0.00 | 1.35 |
Annual Sum or Average | 0.380694E+11 | 0.799717E+09 | 0.00 | 11187910.48 | 0.391279E+09 | 0.100484E+11 | 0.811131E+10 | 0.00 | 1.36 |
Minimum of Months | 0.593613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
Maximum of Months | 0.489452E+10 | 0.432982E+09 | 0.00 | 2523439.30 | 0.164520E+09 | 0.456900E+10 | 0.176706E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629667E+10 | 0.00 | 0.00 | 0.47 |
February | 0.848038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362092E+10 | 0.00 | 0.00 | 0.46 |
March | 0.186198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203070E+10 | 0.00 | 0.00 | 0.45 |
April | 0.300421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39496258.11 | 0.00 | 0.00 | 0.45 |
May | 0.261316E+10 | 286714.88 | 0.00 | 100797.43 | 6723190.04 | 0.00 | 66044507.11 | 0.00 | 0.47 |
June | 0.173618E+10 | 0.137785E+09 | 0.00 | 172392.26 | 0.121759E+09 | 0.00 | 65848201.72 | 0.00 | 0.48 |
July | 0.115690E+10 | 0.180303E+09 | 0.00 | 577767.17 | 0.245055E+09 | 0.00 | 0.296547E+09 | 0.00 | 0.49 |
August | 0.178520E+10 | 24295868.40 | 0.00 | 259351.53 | 0.134818E+09 | 0.00 | 0.139563E+09 | 0.00 | 0.49 |
September | 0.287127E+10 | 0.00 | 0.00 | 40121.47 | 1137860.81 | 0.00 | 26566360.39 | 0.00 | 0.46 |
October | 0.322384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 0.242546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850438E+09 | 0.00 | 0.00 | 0.45 |
December | 0.343455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560868E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.220714E+11 | 0.342671E+09 | 0.00 | 1150429.87 | 0.509493E+09 | 0.184469E+11 | 0.594569E+09 | 0.00 | 0.47 |
Minimum of Months | 0.201746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.322384E+10 | 0.180303E+09 | 0.00 | 577767.17 | 0.245055E+09 | 0.629667E+10 | 0.296547E+09 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3754349.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430820E+10 | 0.00 | 0.00 | 0.54 |
February | 0.176127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278653E+10 | 0.00 | 0.00 | 0.53 |
March | 0.628353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194990E+10 | 0.00 | 0.00 | 0.52 |
April | 0.173432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281309E+09 | 0.00 | 0.00 | 0.52 |
May | 0.177369E+10 | 0.00 | 0.00 | 0.00 | 4642156.58 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.118226E+10 | 55687160.22 | 0.00 | 33843.71 | 0.108644E+09 | 0.00 | 8580256.37 | 0.00 | 0.55 |
July | 0.948910E+09 | 32290209.53 | 0.00 | 8088.18 | 0.239677E+09 | 0.00 | 9081570.47 | 0.00 | 0.55 |
August | 0.127395E+10 | 1171658.74 | 0.00 | 0.00 | 0.103154E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.191835E+10 | 0.00 | 0.00 | 0.00 | 753523.50 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.207774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57181695.70 | 0.00 | 0.00 | 0.51 |
November | 0.952245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121715E+10 | 0.00 | 0.00 | 0.52 |
December | 9451540.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393628E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.126791E+11 | 89149028.48 | 0.00 | 41931.89 | 0.456871E+09 | 0.145365E+11 | 17661826.83 | 0.00 | 0.53 |
Minimum of Months | 3754349.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.207774E+10 | 55687160.22 | 0.00 | 33843.71 | 0.239677E+09 | 0.430820E+10 | 9081570.47 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.979158E+10 | 0.00 | 0.00 | 73491072.70 | 0.00 | 0.353717E+11 | 0.845067E+11 | 0.00 | 20.48 |
February | 0.530002E+10 | 0.00 | 0.00 | 79187142.11 | 0.00 | 0.116336E+11 | 0.769139E+11 | 0.00 | 20.85 |
March | 0.294424E+10 | 0.00 | 0.00 | 0.110502E+09 | 0.00 | 0.359802E+10 | 0.783389E+11 | 0.00 | 20.90 |
April | 0.344764E+09 | 0.00 | 0.00 | 0.145210E+09 | 0.00 | 0.00 | 0.681695E+11 | 0.00 | 21.00 |
May | 0.415575E+09 | 0.140370E+09 | 0.00 | 0.148488E+09 | 0.00 | 0.00 | 0.603576E+11 | 0.00 | 22.01 |
June | 0.308425E+09 | 0.560380E+10 | 0.00 | 98295275.00 | 5819912.46 | 0.00 | 0.397681E+11 | 0.00 | 22.52 |
July | 0.272041E+09 | 0.937532E+10 | 0.00 | 81477387.99 | 14325038.16 | 0.00 | 0.312320E+11 | 0.00 | 22.48 |
August | 0.282788E+09 | 0.363852E+10 | 0.00 | 97660441.58 | 9354076.42 | 0.00 | 0.421925E+11 | 0.00 | 23.02 |
September | 0.101087E+10 | 21427370.12 | 0.00 | 0.143192E+09 | 0.00 | 0.00 | 0.649793E+11 | 0.00 | 21.80 |
October | 0.999549E+09 | 0.00 | 0.00 | 0.183716E+09 | 0.00 | 0.00 | 0.724458E+11 | 0.00 | 20.73 |
November | 0.388849E+09 | 0.00 | 0.00 | 0.108874E+09 | 0.00 | 0.00 | 0.722488E+11 | 0.00 | 20.90 |
December | 0.128807E+11 | 0.00 | 0.00 | 75629700.76 | 0.00 | 0.231298E+11 | 0.844766E+11 | 0.00 | 20.56 |
Annual Sum or Average | 0.349394E+11 | 0.187794E+11 | 0.00 | 0.134572E+10 | 29499027.04 | 0.737331E+11 | 0.775630E+12 | 0.00 | 21.44 |
Minimum of Months | 0.272041E+09 | 0.00 | 0.00 | 73491072.70 | 0.00 | 0.00 | 0.312320E+11 | 0.00 | 20.48 |
Maximum of Months | 0.128807E+11 | 0.937532E+10 | 0.00 | 0.183716E+09 | 14325038.16 | 0.353717E+11 | 0.845067E+11 | 0.00 | 23.02 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308137E+11 | 0.00 | 0.00 | 336433.29 | 0.00 | 0.328860E+11 | 0.960414E+09 | 0.00 | 4.09 |
February | 0.291458E+11 | 0.00 | 0.00 | 3741739.38 | 0.00 | 0.112053E+11 | 0.443353E+10 | 0.00 | 4.06 |
March | 0.293094E+11 | 0.00 | 0.00 | 6273185.94 | 0.00 | 0.289343E+10 | 0.692189E+10 | 0.00 | 3.99 |
April | 0.184465E+11 | 0.00 | 0.00 | 15463477.39 | 0.00 | 0.00 | 0.124184E+11 | 0.00 | 4.01 |
May | 0.996516E+10 | 68927413.38 | 0.00 | 21697866.49 | 5755616.81 | 0.00 | 0.169972E+11 | 0.00 | 4.12 |
June | 0.582291E+10 | 0.220243E+10 | 0.00 | 18140614.89 | 0.396009E+09 | 0.00 | 0.121950E+11 | 0.00 | 4.21 |
July | 0.297770E+10 | 0.385342E+10 | 0.00 | 20265811.45 | 0.437219E+09 | 0.00 | 0.115418E+11 | 0.00 | 4.28 |
August | 0.447502E+10 | 0.147301E+10 | 0.00 | 26382197.18 | 0.208064E+09 | 0.00 | 0.148982E+11 | 0.00 | 4.38 |
September | 0.108482E+11 | 13858410.47 | 0.00 | 23524490.22 | 0.00 | 0.00 | 0.187347E+11 | 0.00 | 4.18 |
October | 0.213058E+11 | 0.00 | 0.00 | 15185326.30 | 0.00 | 2537200.12 | 0.117458E+11 | 0.00 | 4.00 |
November | 0.284831E+11 | 0.00 | 0.00 | 3711431.18 | 0.00 | 0.462287E+09 | 0.389990E+10 | 0.00 | 3.96 |
December | 0.313904E+11 | 0.00 | 0.00 | 105723.86 | 0.00 | 0.276305E+11 | 0.245515E+09 | 0.00 | 4.06 |
Annual Sum or Average | 0.222984E+12 | 0.761165E+10 | 0.00 | 0.154828E+09 | 0.104705E+10 | 0.750800E+11 | 0.114992E+12 | 0.00 | 4.11 |
Minimum of Months | 0.297770E+10 | 0.00 | 0.00 | 105723.86 | 0.00 | 0.00 | 0.245515E+09 | 0.00 | 3.96 |
Maximum of Months | 0.313904E+11 | 0.385342E+10 | 0.00 | 26382197.18 | 0.437219E+09 | 0.328860E+11 | 0.187347E+11 | 0.00 | 4.38 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820702E+11 | 0.00 | 0.00 | 1.69 |
February | 0.102263E+12 | 0.00 | 0.00 | 515487.06 | 0.00 | 0.228173E+11 | 0.206862E+10 | 0.00 | 1.66 |
March | 0.988203E+11 | 0.00 | 0.00 | 3972431.36 | 0.00 | 0.447207E+10 | 0.763337E+10 | 0.00 | 1.63 |
April | 0.579756E+11 | 0.00 | 0.00 | 33269583.51 | 0.00 | 0.00 | 0.296227E+11 | 0.00 | 1.63 |
May | 0.270788E+11 | 0.128913E+09 | 0.00 | 76988107.84 | 72581021.94 | 0.00 | 0.520663E+11 | 0.00 | 1.73 |
June | 0.135645E+11 | 0.592228E+10 | 0.00 | 73741569.32 | 0.155758E+10 | 0.00 | 0.401888E+11 | 0.00 | 1.80 |
July | 0.603094E+10 | 0.104251E+11 | 0.00 | 79251459.89 | 0.198223E+10 | 0.00 | 0.385754E+11 | 0.00 | 1.85 |
August | 0.100757E+11 | 0.364147E+10 | 0.00 | 91148631.47 | 0.105175E+10 | 0.00 | 0.484994E+11 | 0.00 | 1.86 |
September | 0.262485E+11 | 23727901.86 | 0.00 | 87052317.90 | 8736010.90 | 0.00 | 0.590615E+11 | 0.00 | 1.71 |
October | 0.569954E+11 | 0.00 | 0.00 | 46176388.23 | 0.00 | 0.00 | 0.362942E+11 | 0.00 | 1.61 |
November | 0.859514E+11 | 0.00 | 0.00 | 2894930.22 | 0.00 | 0.00 | 0.747689E+10 | 0.00 | 1.63 |
December | 0.104366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648106E+11 | 0.00 | 0.00 | 1.68 |
Annual Sum or Average | 0.691924E+12 | 0.201415E+11 | 0.00 | 0.495011E+09 | 0.467288E+10 | 0.174170E+12 | 0.321487E+12 | 0.00 | 1.71 |
Minimum of Months | 0.603094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 |
Maximum of Months | 0.104366E+12 | 0.104251E+11 | 0.00 | 91148631.47 | 0.198223E+10 | 0.820702E+11 | 0.590615E+11 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172906E+09 | 0.00 | 0.00 | 12469.21 | 0.00 | 0.371705E+10 | 424935.17 | 0.00 | 0.47 |
February | 0.280181E+09 | 0.00 | 0.00 | 805901.32 | 0.00 | 0.217423E+10 | 43735678.83 | 0.00 | 0.47 |
March | 0.352907E+09 | 0.00 | 0.00 | 3506619.23 | 0.00 | 0.154703E+10 | 0.160429E+09 | 0.00 | 0.47 |
April | 0.367388E+09 | 1675482.51 | 0.00 | 8393986.60 | 14263.09 | 0.698017E+09 | 0.515587E+09 | 0.00 | 0.47 |
May | 0.331832E+09 | 23772715.73 | 21424.45 | 14119377.27 | 1414707.67 | 0.112738E+09 | 0.928025E+09 | 1447.09 | 0.48 |
June | 0.238379E+09 | 0.236329E+09 | 185768.94 | 10978392.82 | 47175492.20 | 15455436.67 | 0.552857E+09 | 16268.53 | 0.48 |
July | 0.162066E+09 | 0.379056E+09 | 208661.78 | 10076199.96 | 99178000.33 | 445845.29 | 0.370050E+09 | 7337.35 | 0.48 |
August | 0.233373E+09 | 0.172280E+09 | 222921.65 | 10847993.31 | 50262910.64 | 17861787.36 | 0.496062E+09 | 10121.92 | 0.48 |
September | 0.352813E+09 | 11460098.43 | 25595.28 | 10724145.88 | 1870517.30 | 0.204414E+09 | 0.869843E+09 | 2842.03 | 0.48 |
October | 0.374620E+09 | 0.00 | 0.00 | 4303963.12 | 0.00 | 0.817631E+09 | 0.397363E+09 | 0.00 | 0.47 |
November | 0.291860E+09 | 0.00 | 0.00 | 240323.88 | 0.00 | 0.129593E+10 | 22525866.56 | 0.00 | 0.47 |
December | 0.130558E+09 | 0.00 | 0.00 | 357.47 | 0.00 | 0.332313E+10 | 89772.08 | 0.00 | 0.47 |
Annual Sum or Average | 0.328888E+10 | 0.824573E+09 | 664372.10 | 74009730.08 | 0.199916E+09 | 0.139239E+11 | 0.435699E+10 | 38016.91 | 0.47 |
Minimum of Months | 0.130558E+09 | 0.00 | 0.00 | 357.47 | 0.00 | 445845.29 | 89772.08 | 0.00 | 0.47 |
Maximum of Months | 0.374620E+09 | 0.379056E+09 | 222921.65 | 14119377.27 | 99178000.33 | 0.371705E+10 | 0.928025E+09 | 16268.53 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 54698096.42 | 0.00 | 0.00 | 3796.06 | 0.00 | 0.383513E+10 | 100518.20 | 0.00 | 0.47 |
February | 0.141001E+09 | 0.00 | 0.00 | 148304.10 | 0.00 | 0.234197E+10 | 15535078.80 | 0.00 | 0.47 |
March | 0.242946E+09 | 0.00 | 0.00 | 1565802.83 | 0.00 | 0.173169E+10 | 87424897.66 | 0.00 | 0.47 |
April | 0.419187E+09 | 1577291.13 | 0.00 | 5213562.88 | 112256.49 | 0.808354E+09 | 0.356445E+09 | 0.00 | 0.47 |
May | 0.382211E+09 | 23263801.43 | 19670.36 | 12154667.13 | 1920670.90 | 0.124967E+09 | 0.867219E+09 | 3198.51 | 0.48 |
June | 0.248707E+09 | 0.234332E+09 | 232890.49 | 10402827.01 | 49092734.10 | 14400459.86 | 0.544064E+09 | 15753.27 | 0.48 |
July | 0.166849E+09 | 0.375406E+09 | 219222.55 | 9573803.32 | 0.102761E+09 | 465259.11 | 0.365687E+09 | 8195.00 | 0.48 |
August | 0.243244E+09 | 0.167085E+09 | 242361.45 | 9519783.92 | 55404200.03 | 19997618.91 | 0.485294E+09 | 17774.14 | 0.48 |
September | 0.421472E+09 | 10479404.38 | 25636.55 | 7361414.88 | 2845507.67 | 0.246456E+09 | 0.762336E+09 | 6939.22 | 0.48 |
October | 0.419719E+09 | 0.00 | 0.00 | 1722979.63 | 0.00 | 0.967921E+09 | 0.204368E+09 | 0.00 | 0.47 |
November | 0.208431E+09 | 0.00 | 0.00 | 33909.44 | 0.00 | 0.139800E+10 | 3909133.65 | 0.00 | 0.47 |
December | 53885021.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339949E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.300235E+10 | 0.812143E+09 | 739781.41 | 57700851.20 | 0.212137E+09 | 0.148888E+11 | 0.369238E+10 | 51860.13 | 0.47 |
Minimum of Months | 53885021.76 | 0.00 | 0.00 | 0.00 | 0.00 | 465259.11 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.421472E+09 | 0.375406E+09 | 242361.45 | 12154667.13 | 0.102761E+09 | 0.383513E+10 | 0.867219E+09 | 17774.14 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106032E+11 | 0.00 | 0.00 | 25682.32 | 0.00 | 0.420999E+11 | 46986099.27 | 0.00 | 0.53 |
February | 0.143883E+11 | 0.00 | 0.00 | 3294600.54 | 0.00 | 0.188596E+11 | 0.632355E+09 | 0.00 | 0.53 |
March | 0.161479E+11 | 0.00 | 0.00 | 11053672.83 | 0.00 | 0.998007E+10 | 0.184518E+10 | 0.00 | 0.53 |
April | 0.159445E+11 | 22911434.78 | 0.00 | 49572507.67 | 0.00 | 0.234607E+09 | 0.532200E+10 | 0.00 | 0.54 |
May | 0.761784E+10 | 0.341829E+09 | 0.00 | 72923951.41 | 0.00 | 0.00 | 0.111118E+11 | 0.00 | 0.54 |
June | 0.421669E+10 | 0.376152E+10 | 0.00 | 55518924.84 | 85278761.14 | 0.00 | 0.681467E+10 | 0.00 | 0.54 |
July | 0.186261E+10 | 0.640638E+10 | 0.00 | 50611345.24 | 80974980.81 | 0.00 | 0.544447E+10 | 0.00 | 0.54 |
August | 0.296175E+10 | 0.301298E+10 | 0.00 | 62928917.30 | 7655863.57 | 0.00 | 0.725508E+10 | 0.00 | 0.54 |
September | 0.927907E+10 | 0.179335E+09 | 0.00 | 76210535.97 | 1801738.75 | 0.00 | 0.101399E+11 | 0.00 | 0.54 |
October | 0.167732E+11 | 0.00 | 0.00 | 44766995.09 | 0.00 | 0.368299E+09 | 0.442578E+10 | 0.00 | 0.53 |
November | 0.127760E+11 | 0.00 | 0.00 | 3429489.91 | 0.00 | 0.851088E+10 | 0.547416E+09 | 0.00 | 0.53 |
December | 0.622016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406100E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.118791E+12 | 0.137250E+11 | 0.00 | 0.430337E+09 | 0.175711E+09 | 0.120663E+12 | 0.535857E+11 | 0.00 | 0.54 |
Minimum of Months | 0.186261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.167732E+11 | 0.640638E+10 | 0.00 | 76210535.97 | 85278761.14 | 0.420999E+11 | 0.111118E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.363390E+10 | 0.00 | 0.00 | 80807.46 | 0.00 | 0.491057E+11 | 24928387.06 | 0.00 | 0.53 |
February | 0.490392E+10 | 0.00 | 0.00 | 426834.47 | 0.00 | 0.286601E+11 | 0.328341E+09 | 0.00 | 0.53 |
March | 0.623662E+10 | 0.00 | 0.00 | 4910629.16 | 0.00 | 0.194379E+11 | 0.231244E+10 | 0.00 | 0.53 |
April | 0.635224E+10 | 10948862.74 | 0.00 | 38164747.22 | 11968837.13 | 0.545151E+10 | 0.971462E+10 | 0.00 | 0.54 |
May | 0.619907E+10 | 0.188182E+09 | 145438.72 | 0.120590E+09 | 0.153582E+09 | 87010246.10 | 0.124011E+11 | 13500.61 | 0.54 |
June | 0.393569E+10 | 0.263528E+10 | 716030.95 | 0.111031E+09 | 0.121184E+10 | 10452139.48 | 0.703273E+10 | 15843.98 | 0.54 |
July | 0.275013E+10 | 0.423424E+10 | 2054082.13 | 93059384.65 | 0.225282E+10 | 4342530.32 | 0.451217E+10 | 23260.93 | 0.54 |
August | 0.365914E+10 | 0.132406E+10 | 2374626.09 | 97142391.67 | 0.169494E+10 | 13428741.11 | 0.651286E+10 | 98149.80 | 0.54 |
September | 0.636459E+10 | 88923190.39 | 556064.75 | 90326086.35 | 91675771.49 | 52135951.13 | 0.129935E+11 | 31282.45 | 0.54 |
October | 0.609084E+10 | 0.00 | 0.00 | 39404273.89 | 0.00 | 0.379011E+10 | 0.116977E+11 | 0.00 | 0.53 |
November | 0.555956E+10 | 0.00 | 0.00 | 4597637.26 | 0.00 | 0.137254E+11 | 0.255415E+10 | 0.00 | 0.54 |
December | 0.418327E+10 | 0.00 | 0.00 | 108359.05 | 0.00 | 0.426058E+11 | 53702515.14 | 0.00 | 0.53 |
Annual Sum or Average | 0.598690E+11 | 0.848163E+10 | 5846242.65 | 0.599843E+09 | 0.541682E+10 | 0.162944E+12 | 0.701382E+11 | 182037.77 | 0.54 |
Minimum of Months | 0.275013E+10 | 0.00 | 0.00 | 80807.46 | 0.00 | 4342530.32 | 24928387.06 | 0.00 | 0.53 |
Maximum of Months | 0.636459E+10 | 0.423424E+10 | 2374626.09 | 0.120590E+09 | 0.225282E+10 | 0.491057E+11 | 0.129935E+11 | 98149.80 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373710E+10 | 0.00 | 0.00 | 0.47 |
February | 0.318874E+09 | 0.00 | 0.00 | 268264.35 | 0.00 | 0.213039E+10 | 49418628.39 | 0.00 | 0.47 |
March | 0.371357E+09 | 0.00 | 0.00 | 1731319.98 | 0.00 | 0.150676E+10 | 0.184019E+09 | 0.00 | 0.47 |
April | 0.314761E+09 | 1565364.96 | 1940.43 | 9597609.57 | 121216.12 | 0.664629E+09 | 0.600397E+09 | 1224.09 | 0.47 |
May | 0.286732E+09 | 24104949.16 | 1074.88 | 15838985.21 | 1102590.88 | 0.127968E+09 | 0.956176E+09 | 1680.02 | 0.47 |
June | 0.197931E+09 | 0.239240E+09 | 121109.39 | 14561058.81 | 44337066.21 | 9147423.72 | 0.596031E+09 | 7974.74 | 0.48 |
July | 0.160409E+09 | 0.383832E+09 | 201927.66 | 11007039.10 | 94413792.78 | 481440.29 | 0.370741E+09 | 2807.66 | 0.48 |
August | 0.226963E+09 | 0.175261E+09 | 156671.39 | 11696446.68 | 47350460.22 | 14948441.10 | 0.504537E+09 | 7416.71 | 0.48 |
September | 0.325496E+09 | 11605467.18 | 24417.19 | 11278014.83 | 1725148.54 | 0.228735E+09 | 0.872284E+09 | 4020.11 | 0.48 |
October | 0.363000E+09 | 0.00 | 0.00 | 4162274.43 | 0.00 | 0.843784E+09 | 0.382972E+09 | 0.00 | 0.47 |
November | 0.288265E+09 | 0.00 | 0.00 | 302395.75 | 0.00 | 0.128760E+10 | 34393380.87 | 0.00 | 0.47 |
December | 0.116209E+09 | 0.00 | 0.00 | 3903.42 | 0.00 | 0.333653E+10 | 1038364.94 | 0.00 | 0.47 |
Annual Sum or Average | 0.312328E+10 | 0.835609E+09 | 507140.93 | 80447312.13 | 0.189050E+09 | 0.138881E+11 | 0.455201E+10 | 25123.34 | 0.47 |
Minimum of Months | 0.116209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 481440.29 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.371357E+09 | 0.383832E+09 | 201927.66 | 15838985.21 | 94413792.78 | 0.373710E+10 | 0.956176E+09 | 7974.74 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58720546.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383121E+10 | 0.00 | 0.00 | 0.47 |
February | 0.156855E+09 | 0.00 | 0.00 | 15319.62 | 0.00 | 0.233686E+10 | 4927047.29 | 0.00 | 0.47 |
March | 0.287550E+09 | 0.00 | 0.00 | 362132.67 | 0.00 | 0.170948E+10 | 66238661.86 | 0.00 | 0.47 |
April | 0.389105E+09 | 1513133.38 | 9333.28 | 5549058.49 | 163981.56 | 0.742658E+09 | 0.451887E+09 | 3099.40 | 0.47 |
May | 0.337266E+09 | 23942982.31 | 1200.05 | 13593157.92 | 1261604.29 | 0.148835E+09 | 0.886858E+09 | 1554.53 | 0.47 |
June | 0.200418E+09 | 0.238160E+09 | 161817.97 | 13934834.63 | 45345529.86 | 8705387.36 | 0.594516E+09 | 5630.88 | 0.48 |
July | 0.163700E+09 | 0.382372E+09 | 200669.28 | 10492771.03 | 95817877.07 | 428129.19 | 0.367954E+09 | 4042.05 | 0.48 |
August | 0.230605E+09 | 0.170495E+09 | 154919.16 | 10299117.14 | 52090444.20 | 17197399.47 | 0.499955E+09 | 9149.72 | 0.48 |
September | 0.372963E+09 | 10639179.42 | 40587.76 | 7696571.86 | 2675007.75 | 0.291676E+09 | 0.765290E+09 | 2712.88 | 0.48 |
October | 0.433618E+09 | 0.00 | 0.00 | 1474449.74 | 0.00 | 0.100214E+10 | 0.156496E+09 | 0.00 | 0.47 |
November | 0.197437E+09 | 0.00 | 0.00 | 51011.96 | 0.00 | 0.140161E+10 | 11274717.53 | 0.00 | 0.47 |
December | 61096556.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339228E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.288933E+10 | 0.827122E+09 | 568527.50 | 63468425.06 | 0.197354E+09 | 0.148831E+11 | 0.380540E+10 | 26189.46 | 0.47 |
Minimum of Months | 58720546.75 | 0.00 | 0.00 | 0.00 | 0.00 | 428129.19 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.433618E+09 | 0.382372E+09 | 200669.28 | 13934834.63 | 95817877.07 | 0.383121E+10 | 0.886858E+09 | 9149.72 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554742E+11 | 0.00 | 0.00 | 0.61 |
February | 0.149079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269186E+11 | 0.00 | 0.00 | 0.59 |
March | 0.262739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101599E+11 | 0.00 | 0.00 | 0.58 |
April | 0.284441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42509538.82 | 0.00 | 0.00 | 0.58 |
May | 0.250354E+11 | 231280.57 | 0.00 | 1324.67 | 65375683.83 | 0.00 | 31916080.41 | 0.00 | 0.60 |
June | 0.162925E+11 | 0.939332E+09 | 0.00 | 911853.81 | 0.138963E+10 | 0.00 | 0.542380E+09 | 0.00 | 0.61 |
July | 0.111863E+11 | 0.132286E+10 | 0.00 | 3829077.63 | 0.253021E+10 | 0.00 | 0.241592E+10 | 0.00 | 0.62 |
August | 0.172786E+11 | 63049540.04 | 0.00 | 478691.96 | 0.141137E+10 | 0.00 | 0.725536E+09 | 0.00 | 0.63 |
September | 0.271117E+11 | 0.00 | 0.00 | 0.00 | 10649444.57 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.300773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95220207.38 | 0.00 | 0.00 | 0.57 |
November | 0.239634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669629E+10 | 0.00 | 0.00 | 0.58 |
December | 0.594466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497332E+11 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.231809E+12 | 0.232547E+10 | 0.00 | 5220948.07 | 0.540723E+10 | 0.149120E+12 | 0.371575E+10 | 0.00 | 0.60 |
Minimum of Months | 0.529333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.300773E+11 | 0.132286E+10 | 0.00 | 3829077.63 | 0.253021E+10 | 0.554742E+11 | 0.241592E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24100528.89 | 0.00 | 0.00 | 3148.54 | 0.00 | 0.948374E+09 | 119974.61 | 0.00 | 0.47 |
February | 53411070.78 | 0.00 | 0.00 | 198916.07 | 0.00 | 0.561476E+09 | 9652469.61 | 0.00 | 0.47 |
March | 71120388.32 | 0.00 | 0.00 | 923413.24 | 0.00 | 0.409774E+09 | 34149753.46 | 0.00 | 0.47 |
April | 85051605.64 | 418870.63 | 0.00 | 2127094.01 | 3565.77 | 0.196953E+09 | 0.113215E+09 | 0.00 | 0.47 |
May | 82504303.21 | 5973754.71 | 4626.79 | 3546214.59 | 323101.14 | 47258633.55 | 0.213370E+09 | 1091.09 | 0.48 |
June | 57912464.65 | 59065603.83 | 51283.96 | 2830029.88 | 11806218.90 | 10784130.36 | 0.132891E+09 | 3465.98 | 0.48 |
July | 40473068.65 | 94760978.21 | 35544.64 | 2542838.58 | 24814172.12 | 85166.76 | 92558489.44 | 1922.81 | 0.48 |
August | 58231287.92 | 43071899.71 | 62809.50 | 2709445.33 | 12556579.67 | 9804768.60 | 0.118791E+09 | 2664.64 | 0.48 |
September | 88494781.54 | 2837246.23 | 6546.49 | 2523683.97 | 495407.70 | 76969827.36 | 0.191460E+09 | 562.83 | 0.48 |
October | 86326405.32 | 0.00 | 0.00 | 972880.97 | 0.00 | 0.236474E+09 | 74706503.40 | 0.00 | 0.47 |
November | 56466999.08 | 0.00 | 0.00 | 54717.26 | 0.00 | 0.343123E+09 | 2994751.48 | 0.00 | 0.47 |
December | 17666885.52 | 0.00 | 0.00 | 151.24 | 0.00 | 0.845755E+09 | 22381.15 | 0.00 | 0.47 |
Annual Sum or Average | 0.721760E+09 | 0.206128E+09 | 160811.37 | 18432533.68 | 49999045.31 | 0.368683E+10 | 0.983931E+09 | 9707.37 | 0.47 |
Minimum of Months | 17666885.52 | 0.00 | 0.00 | 151.24 | 0.00 | 85166.76 | 22381.15 | 0.00 | 0.47 |
Maximum of Months | 88494781.54 | 94760978.21 | 62809.50 | 3546214.59 | 24814172.12 | 0.948374E+09 | 0.213370E+09 | 3465.98 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8526226.84 | 0.00 | 0.00 | 136.23 | 0.00 | 0.963931E+09 | 25942.33 | 0.00 | 0.47 |
February | 22831851.08 | 0.00 | 0.00 | 22264.77 | 0.00 | 0.598619E+09 | 3191351.17 | 0.00 | 0.47 |
March | 46696169.70 | 0.00 | 0.00 | 398990.57 | 0.00 | 0.449690E+09 | 19121685.98 | 0.00 | 0.47 |
April | 94678067.61 | 396011.41 | 0.00 | 1295262.82 | 26375.50 | 0.222206E+09 | 79120249.63 | 0.00 | 0.47 |
May | 94218163.60 | 5842305.22 | 4471.11 | 3002015.18 | 453812.86 | 53335537.39 | 0.196082E+09 | 1246.11 | 0.48 |
June | 60398113.63 | 58601178.91 | 46693.28 | 2674119.71 | 12266703.77 | 10456734.66 | 0.130865E+09 | 3686.62 | 0.48 |
July | 41373484.36 | 94024490.19 | 42750.42 | 2413690.21 | 25529504.39 | 95447.02 | 91761047.34 | 1858.41 | 0.48 |
August | 60688927.76 | 41694257.65 | 64934.62 | 2356284.04 | 13922952.27 | 10053856.31 | 0.116415E+09 | 5283.62 | 0.48 |
September | 0.105405E+09 | 2662137.54 | 6399.30 | 1650567.88 | 669090.48 | 0.104661E+09 | 0.147690E+09 | 1744.64 | 0.48 |
October | 95498002.11 | 0.00 | 0.00 | 373705.68 | 0.00 | 0.271050E+09 | 31510986.51 | 0.00 | 0.47 |
November | 34278019.17 | 0.00 | 0.00 | 8039.38 | 0.00 | 0.367904E+09 | 401973.13 | 0.00 | 0.47 |
December | 9732623.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853611E+09 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.674324E+09 | 0.203220E+09 | 165248.73 | 14195076.46 | 52868439.26 | 0.390561E+10 | 0.816185E+09 | 13819.41 | 0.47 |
Minimum of Months | 8526226.84 | 0.00 | 0.00 | 0.00 | 0.00 | 95447.02 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.105405E+09 | 94024490.19 | 64934.62 | 3002015.18 | 25529504.39 | 0.963931E+09 | 0.196082E+09 | 5283.62 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.645593E+09 | 0.00 | 0.00 | 1458930.78 | 0.00 | 0.535143E+10 | 0.249962E+09 | 0.00 | 0.53 |
February | 0.461762E+09 | 0.00 | 0.00 | 5154004.38 | 0.00 | 0.306002E+10 | 0.486682E+09 | 0.00 | 0.53 |
March | 0.499881E+09 | 0.00 | 0.00 | 8564953.67 | 0.00 | 0.220118E+10 | 0.605203E+09 | 0.00 | 0.53 |
April | 0.458516E+09 | 2610333.71 | 0.00 | 16364639.88 | 103604.44 | 0.951003E+09 | 0.112686E+10 | 0.00 | 0.54 |
May | 0.517248E+09 | 38175588.40 | 20221.41 | 19310031.03 | 2288151.84 | 0.173622E+09 | 0.151705E+10 | 6856.15 | 0.54 |
June | 0.383573E+09 | 0.371719E+09 | 405572.34 | 14297005.29 | 83516397.02 | 25502696.32 | 0.889906E+09 | 25825.17 | 0.54 |
July | 0.275397E+09 | 0.601097E+09 | 518172.91 | 12014299.25 | 0.166819E+09 | 720522.25 | 0.583412E+09 | 16484.58 | 0.54 |
August | 0.381091E+09 | 0.277522E+09 | 374640.35 | 15673351.28 | 79894189.02 | 22092785.33 | 0.798816E+09 | 14636.67 | 0.54 |
September | 0.537582E+09 | 18701932.89 | 16001.24 | 20007562.99 | 2735768.44 | 0.219783E+09 | 0.153190E+10 | 2570.87 | 0.54 |
October | 0.562968E+09 | 0.00 | 0.00 | 14378188.85 | 0.00 | 0.994657E+09 | 0.988024E+09 | 0.00 | 0.54 |
November | 0.444380E+09 | 0.00 | 0.00 | 3993600.62 | 0.00 | 0.182914E+10 | 0.309236E+09 | 0.00 | 0.54 |
December | 0.494208E+09 | 0.00 | 0.00 | 683257.60 | 0.00 | 0.487494E+10 | 0.177361E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.566220E+10 | 0.130983E+10 | 1334608.25 | 0.131900E+09 | 0.335357E+09 | 0.197041E+11 | 0.926442E+10 | 66373.43 | 0.54 |
Minimum of Months | 0.275397E+09 | 0.00 | 0.00 | 683257.60 | 0.00 | 720522.25 | 0.177361E+09 | 0.00 | 0.53 |
Maximum of Months | 0.645593E+09 | 0.601097E+09 | 518172.91 | 20007562.99 | 0.166819E+09 | 0.535143E+10 | 0.153190E+10 | 25825.17 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.435416E+11 | 0.00 | 0.00 | 15346904.54 | 0.00 | 0.145348E+11 | 0.216921E+11 | 0.00 | 3.79 |
February | 0.255798E+11 | 0.00 | 0.00 | 22880151.09 | 0.00 | 0.207377E+10 | 0.282928E+11 | 0.00 | 3.79 |
March | 0.138731E+11 | 0.00 | 0.00 | 45246610.58 | 0.00 | 0.00 | 0.371184E+11 | 0.00 | 3.89 |
April | 0.214456E+10 | 0.00 | 0.00 | 83949304.21 | 0.00 | 0.00 | 0.420752E+11 | 0.00 | 4.19 |
May | 0.327269E+09 | 0.102166E+09 | 0.00 | 0.115200E+09 | 0.00 | 0.00 | 0.438729E+11 | 0.00 | 4.85 |
June | 10348615.79 | 0.404036E+10 | 0.00 | 89832920.60 | 0.00 | 0.00 | 0.311491E+11 | 0.00 | 5.15 |
July | 11861647.31 | 0.668644E+10 | 0.00 | 77534252.32 | 0.00 | 0.00 | 0.257232E+11 | 0.00 | 5.27 |
August | 12266107.19 | 0.242033E+10 | 0.00 | 86728028.34 | 0.00 | 0.00 | 0.331029E+11 | 0.00 | 5.20 |
September | 0.580679E+09 | 14176426.83 | 0.00 | 0.112406E+09 | 0.00 | 0.00 | 0.457160E+11 | 0.00 | 4.65 |
October | 0.220728E+10 | 0.00 | 0.00 | 0.106649E+09 | 0.00 | 0.00 | 0.455314E+11 | 0.00 | 4.16 |
November | 0.758296E+10 | 0.00 | 0.00 | 47638099.22 | 0.00 | 0.00 | 0.363835E+11 | 0.00 | 3.93 |
December | 0.408184E+11 | 0.00 | 0.00 | 19386896.31 | 0.00 | 0.785539E+10 | 0.247072E+11 | 0.00 | 3.78 |
Annual Sum or Average | 0.136690E+12 | 0.132635E+11 | 0.00 | 0.822799E+09 | 0.00 | 0.244639E+11 | 0.415365E+12 | 0.00 | 4.39 |
Minimum of Months | 10348615.79 | 0.00 | 0.00 | 15346904.54 | 0.00 | 0.00 | 0.216921E+11 | 0.00 | 3.78 |
Maximum of Months | 0.435416E+11 | 0.668644E+10 | 0.00 | 0.115200E+09 | 0.00 | 0.145348E+11 | 0.457160E+11 | 0.00 | 5.27 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412008E+11 | 0.00 | 0.00 | 21838963.56 | 0.00 | 0.139761E+11 | 0.290979E+11 | 0.00 | 4.03 |
February | 0.222069E+11 | 0.00 | 0.00 | 32877106.55 | 0.00 | 0.183906E+10 | 0.356502E+11 | 0.00 | 4.07 |
March | 0.101304E+11 | 0.00 | 0.00 | 61906117.78 | 0.00 | 0.00 | 0.452827E+11 | 0.00 | 4.23 |
April | 0.680306E+09 | 0.00 | 0.00 | 0.107272E+09 | 0.00 | 0.00 | 0.479463E+11 | 0.00 | 4.61 |
May | 49148844.41 | 0.110849E+09 | 0.00 | 0.132859E+09 | 0.00 | 0.00 | 0.479266E+11 | 0.00 | 5.27 |
June | 9066953.65 | 0.434303E+10 | 0.00 | 99054878.79 | 0.00 | 0.00 | 0.335825E+11 | 0.00 | 5.56 |
July | 10988205.82 | 0.718912E+10 | 0.00 | 84049265.68 | 0.00 | 0.00 | 0.274609E+11 | 0.00 | 5.64 |
August | 4137863.89 | 0.262284E+10 | 0.00 | 95550671.01 | 0.00 | 0.00 | 0.355179E+11 | 0.00 | 5.60 |
September | 0.116791E+09 | 15042397.24 | 0.00 | 0.131621E+09 | 0.00 | 0.00 | 0.503249E+11 | 0.00 | 5.07 |
October | 0.723873E+09 | 0.00 | 0.00 | 0.134100E+09 | 0.00 | 0.00 | 0.519490E+11 | 0.00 | 4.59 |
November | 0.308588E+10 | 0.00 | 0.00 | 64840318.95 | 0.00 | 0.00 | 0.450417E+11 | 0.00 | 4.30 |
December | 0.395923E+11 | 0.00 | 0.00 | 27275887.04 | 0.00 | 0.686394E+10 | 0.313404E+11 | 0.00 | 4.03 |
Annual Sum or Average | 0.117811E+12 | 0.142809E+11 | 0.00 | 0.993245E+09 | 0.00 | 0.226791E+11 | 0.481121E+12 | 0.00 | 4.75 |
Minimum of Months | 4137863.89 | 0.00 | 0.00 | 21838963.56 | 0.00 | 0.00 | 0.274609E+11 | 0.00 | 4.03 |
Maximum of Months | 0.412008E+11 | 0.718912E+10 | 0.00 | 0.134100E+09 | 0.00 | 0.139761E+11 | 0.519490E+11 | 0.00 | 5.64 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.834987E+10 | 0.00 | 0.00 | 89037513.32 | 0.00 | 0.160714E+11 | 0.806421E+11 | 0.00 | 17.41 |
February | 0.411951E+10 | 0.00 | 0.00 | 98226887.11 | 0.00 | 0.557827E+10 | 0.709771E+11 | 0.00 | 18.61 |
March | 0.241454E+10 | 0.00 | 0.00 | 0.133087E+09 | 0.00 | 0.160366E+10 | 0.731526E+11 | 0.00 | 19.34 |
April | 18433687.07 | 0.00 | 0.00 | 0.185985E+09 | 0.00 | 0.00 | 0.650633E+11 | 0.00 | 20.30 |
May | 17908763.38 | 0.187307E+09 | 0.00 | 0.189468E+09 | 0.00 | 0.00 | 0.573159E+11 | 0.00 | 21.83 |
June | 12469230.78 | 0.637330E+10 | 0.00 | 0.124887E+09 | 0.00 | 0.00 | 0.371874E+11 | 0.00 | 22.70 |
July | 17611781.06 | 0.104853E+11 | 0.00 | 0.102069E+09 | 0.00 | 0.00 | 0.287887E+11 | 0.00 | 22.77 |
August | 6474698.65 | 0.418910E+10 | 0.00 | 0.121157E+09 | 0.00 | 0.00 | 0.389471E+11 | 0.00 | 22.93 |
September | 0.115058E+09 | 30411010.10 | 0.00 | 0.182961E+09 | 0.00 | 0.00 | 0.620847E+11 | 0.00 | 21.48 |
October | 99865625.42 | 0.00 | 0.00 | 0.219704E+09 | 0.00 | 0.00 | 0.681720E+11 | 0.00 | 19.67 |
November | 10832801.21 | 0.00 | 0.00 | 0.128979E+09 | 0.00 | 0.00 | 0.665116E+11 | 0.00 | 19.25 |
December | 0.859986E+10 | 0.00 | 0.00 | 93164958.86 | 0.00 | 0.102769E+11 | 0.799760E+11 | 0.00 | 17.58 |
Annual Sum or Average | 0.237824E+11 | 0.212654E+11 | 0.00 | 0.166873E+10 | 0.00 | 0.335302E+11 | 0.728819E+12 | 0.00 | 20.33 |
Minimum of Months | 6474698.65 | 0.00 | 0.00 | 89037513.32 | 0.00 | 0.00 | 0.287887E+11 | 0.00 | 17.41 |
Maximum of Months | 0.859986E+10 | 0.104853E+11 | 0.00 | 0.219704E+09 | 0.00 | 0.160714E+11 | 0.806421E+11 | 0.00 | 22.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281177E+11 | 0.00 | 0.00 | 1.12 |
February | 0.499909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153935E+11 | 0.00 | 0.00 | 1.09 |
March | 0.102315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753241E+10 | 0.00 | 0.00 | 1.07 |
April | 0.136022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286806E+09 | 0.00 | 0.00 | 1.06 |
May | 0.118689E+11 | 29601888.80 | 0.00 | 883481.53 | 3443545.35 | 0.00 | 0.352268E+09 | 0.00 | 1.10 |
June | 0.772657E+10 | 0.855339E+09 | 0.00 | 1164791.80 | 0.382193E+09 | 0.00 | 0.477875E+09 | 0.00 | 1.14 |
July | 0.545628E+10 | 0.141350E+10 | 0.00 | 2427794.86 | 0.553172E+09 | 0.00 | 0.114367E+10 | 0.00 | 1.15 |
August | 0.816472E+10 | 0.382916E+09 | 0.00 | 1099502.11 | 0.345542E+09 | 0.00 | 0.613624E+09 | 0.00 | 1.16 |
September | 0.130724E+11 | 3786474.98 | 0.00 | 200211.46 | 1441948.57 | 0.00 | 0.146405E+09 | 0.00 | 1.09 |
October | 0.145191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191868E+09 | 0.00 | 0.00 | 1.04 |
November | 0.101816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476695E+10 | 0.00 | 0.00 | 1.07 |
December | 0.129272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258432E+11 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.102614E+12 | 0.268514E+10 | 0.00 | 5775781.76 | 0.128579E+10 | 0.821323E+11 | 0.273384E+10 | 0.00 | 1.10 |
Minimum of Months | 0.129272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
Maximum of Months | 0.145191E+11 | 0.141350E+10 | 0.00 | 2427794.86 | 0.553172E+09 | 0.281177E+11 | 0.114367E+10 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:36
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148915E+12 | 0.338858E+11 | 0.391616E+12 | 0.160643E+13 | 0.211495E+12 |
February | 0.235495E+12 | 0.272179E+11 | 0.314116E+12 | 0.132139E+13 | 0.142397E+12 |
March | 0.333754E+12 | 0.259038E+11 | 0.305167E+12 | 0.128890E+13 | 0.117219E+12 |
April | 0.448009E+12 | 0.170340E+11 | 0.203089E+12 | 0.886436E+12 | 0.108405E+12 |
May | 0.501998E+12 | 0.988759E+10 | 0.111851E+12 | 0.539301E+12 | 0.299249E+12 |
June | 0.523939E+12 | 0.412814E+10 | 0.403669E+11 | 0.234705E+12 | 0.583543E+12 |
July | 0.533539E+12 | 0.189523E+10 | 0.119680E+11 | 0.119252E+12 | 0.782473E+12 |
August | 0.442541E+12 | 0.450163E+10 | 0.480296E+11 | 0.266715E+12 | 0.569194E+12 |
September | 0.333687E+12 | 0.101127E+11 | 0.121786E+12 | 0.554933E+12 | 0.208533E+12 |
October | 0.179509E+12 | 0.161821E+11 | 0.202517E+12 | 0.854768E+12 | 0.100333E+12 |
November | 0.942628E+11 | 0.214927E+11 | 0.265513E+12 | 0.109911E+13 | 0.914935E+11 |
December | 0.105044E+12 | 0.323206E+11 | 0.377761E+12 | 0.154295E+13 | 0.193940E+12 |
Annual Sum or Average | 0.388069E+13 | 0.204562E+12 | 0.239378E+13 | 0.103149E+14 | 0.340828E+13 |
Minimum of Months | 0.942628E+11 | 0.189523E+10 | 0.119680E+11 | 0.119252E+12 | 0.914935E+11 |
Maximum of Months | 0.533539E+12 | 0.338858E+11 | 0.391616E+12 | 0.160643E+13 | 0.782473E+12 |