Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:41:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13953.84 | 1229.92 | 1229.92 |
Net Site Energy | 13953.84 | 1229.92 | 1229.92 |
Total Source Energy | 35259.96 | 3107.89 | 3107.89 |
Net Source Energy | 35259.96 | 3107.89 | 3107.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 21.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5037.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 867.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 538.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 186.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 312.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2477.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 9665.86 | 4287.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 21.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 5037.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 867.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 538.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 186.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 312.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 2477.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 21.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5037.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 867.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 538.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 186.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 312.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 2477.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 515.86 | 220.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.47 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 851.97 | 377.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 515.86 | 220.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.47 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 851.97 | 377.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 9665.865 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 9665.865 | 100.00 |
Total On-Site and Utility Electric Sources | 9665.865 | 100.00 |
Total Electricity End Uses | 9665.865 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 7329.38 | 100.00 |
Air to Air Heat Recovery for Heating | 0.02 | 0.00 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 7329.40 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 71.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7023.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.3255 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.5208 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.7005 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 11.5174 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.6875 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 9.7951 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.3255 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.5208 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.7005 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 11.5174 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.6875 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 9.7951 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 13.0243 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 5.0165 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JUN-19:10 | 12-JAN-18:10 | - | - | - | - | - | - | - | - | - | - | 10-MAY-20:10 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 240181.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32081.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31007.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7378.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3780.79 | 211381.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2392.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 501453.14 | 315630.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 240181.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1777.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 31007.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 7378.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3780.79 | 211381.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1060.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1090.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 22.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15952.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2748.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2058.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1705.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 590.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 988.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 2686.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 197.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 30611.79 | 4648.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1406.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 87.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 236.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2698.19 | 409.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1406.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 87.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 236.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2698.19 | 409.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.13 | 0.481096 | 0.512000 | 1.60 | 1.00 | 0.500000 | 0.000792 | 0.000074 | 1.60 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.326375 | 0.156594 | 0.512000 | 0.167104 | 0.512000 | 0.500000 | 0.002433 | 0.000011 | 0.167104 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.287718 | 0.205701 | 0.512000 | 0.147311 | 0.548535 | 0.500000 | 0.001852 | 0.000008 | 0.147311 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.286729 | 0.436487 | 0.512000 | 0.146805 | 1.00 | 0.500000 | 0.000873 | 0.000008 | 0.146805 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.176771 | 0.408474 | 0.512000 | 0.090507 | 1.00 | 0.500000 | 0.000933 | 0.000005 | 0.090507 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.21 | 0.073609 | 0.512000 | 1.64 | 0.512000 | 0.500000 | 0.020540 | 0.000079 | 1.64 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.34 | 0.107738 | 0.512000 | 0.683911 | 0.512000 | 0.500000 | 0.003536 | 0.000039 | 0.683911 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.74 | 0.210487 | 0.512000 | 2.42 | 0.561299 | 0.500000 | 0.001810 | 0.000125 | 2.42 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.57 | 0.754286 | 0.512000 | 0.805657 | 1.00 | 0.500000 | 0.000505 | 0.000051 | 0.805657 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.28 | 0.110935 | 0.512000 | 1.17 | 0.512000 | 0.500000 | 0.003434 | 0.000064 | 1.17 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.38 | 0.106129 | 0.512000 | 1.22 | 0.512000 | 0.500000 | 0.003590 | 0.000065 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.23 | 0.063624 | 0.512000 | 1.14 | 0.512000 | 0.500000 | 0.010771 | 0.000053 | 1.14 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.815125 | 0.385265 | 0.512000 | 0.417344 | 1.00 | 0.500000 | 0.000989 | 0.000029 | 0.417344 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8468.91 | 0.000074 | 176.60 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 1237.94 | 0.000011 | 26.37 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 872.23 | 0.000008 | 18.30 |
MECH_FLR_1 VAV BOX REHEAT COIL | 947.30 | 0.000008 | 19.99 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 586.41 | 0.000005 | 12.37 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9064.89 | 0.000079 | 189.49 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 4447.43 | 0.000039 | 93.87 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 14291.22 | 0.000125 | 299.83 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 1431.09 | 0.000013 | 40.82 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 1430.93 | 0.000013 | 40.81 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 19405.05 | 0.000170 | 553.49 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 19410.35 | 0.000170 | 553.66 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 1431.09 | 0.000013 | 40.82 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 1430.93 | 0.000013 | 40.81 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 5804.07 | 0.000051 | 123.37 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 357.77 | 0.000003 | 10.21 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 357.73 | 0.000003 | 10.21 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 2298.53 | 0.000020 | 65.58 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 7284.93 | 0.000064 | 153.37 |
DINING_FLR_6 VAV BOX REHEAT COIL | 7451.58 | 0.000065 | 156.67 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6012.98 | 0.000053 | 125.39 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 3362.75 | 0.000029 | 72.10 |
VAV WITH REHEAT HEATING COIL | 136928.98 | 0.001198 | 2398.63 |
FLR_3_DOAS HEATING COIL | 12429.56 | 0.000109 | 217.73 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.03 | 0.000013 | 0.000427 |
ROOM_2_FLR_3 FAN COIL | 1.04 | 0.000013 | 0.000432 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.79 | 0.000170 | 0.002361 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.87 | 0.000170 | 0.002934 |
ROOM_5_FLR_3 FAN COIL | 0.906718 | 0.000013 | 0.000381 |
ROOM_6_FLR_3 FAN COIL | 0.914996 | 0.000013 | 0.000384 |
ROOM_1_FLR_6 FAN COIL | 0.284965 | 0.000003 | 0.000118 |
ROOM_2_FLR_6 FAN COIL | 0.288143 | 0.000003 | 0.000119 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.14 | 0.000020 | 0.000484 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.03 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.04 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.79 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.87 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.906718 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.914996 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.284965 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.288143 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.14 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008744 | 12.80 | 0.008500 | 0.000427 | 1.03 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008741 | 12.80 | 0.008500 | 0.000432 | 1.04 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008664 | 12.80 | 0.008500 | 0.002361 | 5.79 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008840 | 12.80 | 0.008500 | 0.002934 | 6.87 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008778 | 12.80 | 0.008500 | 0.000381 | 0.906718 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008776 | 12.80 | 0.008500 | 0.000384 | 0.914996 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008720 | 12.80 | 0.008500 | 0.000118 | 0.284965 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008718 | 12.80 | 0.008500 | 0.000119 | 0.288143 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008824 | 12.80 | 0.008500 | 0.000484 | 1.14 | |
VAV WITH REHEAT COOLING COIL | 29.78 | 6.70 | 0.013537 | 11.09 | 0.008500 | 0.031040 | 22.60 | 869048.90 |
FLR_3_DOAS COOLING COIL | 35.20 | 6.70 | 0.017158 | 11.94 | 0.008500 | 0.004053 | 2.05 | 113467.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.65 | 11.65 | 22.76 | 11.65 | 22.60 | 22.60 | 0.300000 | 0.515728 | 22.60 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.60 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.60 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.031040 | 0.000015 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001198 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.004053 | 0.000117 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000109 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.042734 | 6977.17 | |
HEATSYS1 PUMP | 0.002334 | 702.78 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002334 | 0.280032 |
COOLSYS1 | 0.042734 | 5.13 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 266744.66 | 266744.66 | 0.002334 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.042734 | 4830.53 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.042734 | 1196441.34 | 1199757.49 | 136.77 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.325 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.705 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.521 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.901 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.700 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.390 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 11.517 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.897 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 20432.332 | 10.325 | 191.855 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20432.332 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.656 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.656 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.385 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.385 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 742.517 | 4.521 | 279.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 742.517 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 729.693 | 7.700 | 357.693 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 729.693 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2175.192 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2175.192 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 12673.066 | 9.688 | 30.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12673.066 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.470 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.470 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
29 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
30 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
31 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
32 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
33 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
34 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
35 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
36 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
37 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
38 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
39 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
40 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
41 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
42 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
43 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
44 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
45 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
46 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
47 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
48 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
49 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
50 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
51 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
52 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
53 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
54 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
55 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
56 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
57 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
58 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
59 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
60 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
61 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
62 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
63 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
64 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
65 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
66 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
67 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
68 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
69 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
70 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
71 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
72 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
73 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
74 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
75 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
76 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
77 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
78 | 7 | -0.54138470E-12 | 0.12463713E-14 | -0.64276224E-14 | 0.11113167E-15 |
79 | 6 | 0.12246794E-07 | 0.15689727E-09 | 0.20336639E-09 | -0.66085082E-11 |
80 | 5 | -0.43638646E-04 | 0.91064443E-06 | -0.10338442E-05 | 0.73798452E-07 |
81 | 4 | 0.19644206E-01 | 0.40532412E-03 | 0.96204216E-03 | -0.14823791E-03 |
82 | 3 | -1.4347347 | 0.16410182E-01 | -0.13915079 | 0.27725787E-01 |
83 | 2 | 17.082538 | 0.80550987E-01 | 2.2432332 | -0.47694951 |
84 | 1 | -41.597683 | 0.53207822E-01 | -6.4041654 | 1.4049886 |
85 | 0 | 26.083068 | 0.22662127E-02 | 4.4519555 | |
86 | 7 | -0.64276224E-14 | 0.12463713E-14 | -0.54138470E-12 | 0.11113167E-15 |
87 | 6 | 0.20336639E-09 | 0.15689727E-09 | 0.12246794E-07 | -0.66085082E-11 |
88 | 5 | -0.10338442E-05 | 0.91064443E-06 | -0.43638646E-04 | 0.73798452E-07 |
89 | 4 | 0.96204216E-03 | 0.40532412E-03 | 0.19644206E-01 | -0.14823791E-03 |
90 | 3 | -0.13915079 | 0.16410182E-01 | -1.4347347 | 0.27725787E-01 |
91 | 2 | 2.2432332 | 0.80550987E-01 | 17.082538 | -0.47694951 |
92 | 1 | -6.4041654 | 0.53207822E-01 | -41.597683 | 1.4049886 |
93 | 0 | 4.4519555 | 0.22662127E-02 | 26.083068 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.57_SHGC_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.0178E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.3491E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.1558E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.2728E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.2159E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.7486E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 6.7208E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0097E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 6.8772E-002 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.9417E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.8010E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.3112E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.0940E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1351E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6618E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 8.8107E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.4328E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 5.6600E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.0940E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1351E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6618E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 8.8107E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.4328E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 5.6600E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 43116.94244 | 43116.94244 | 3.13423 | 3.13423 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 21:30:00 | 29.80250 | 1.71479E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 20.10000 | 1.47983E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4489.02679 | 4489.02679 | 0.32638 | 0.32638 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 351.55936 | 351.55936 | 1.50770E-002 | 7.92179E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3957.50672 | 3957.50672 | 0.28772 | 0.28772 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:20:00 | 31.57333 | 1.71512E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 89.99737 | 89.99737 | 3.85946E-003 | 9.17347E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3944.69770 | 3944.69770 | 0.28673 | 0.28673 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:00:00 | 31.88500 | 1.71518E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 167.17853 | 167.17853 | 7.16931E-003 | 7.16931E-003 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2431.93194 | 2431.93194 | 0.17677 | 0.17677 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:40:00 | 34.23667 | 1.71563E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 105.58646 | 105.58646 | 4.52799E-003 | 5.77652E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44097.95724 | 44097.95724 | 3.20579 | 3.20579 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 352.95616 | 352.95616 | 1.51369E-002 | 1.51369E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18357.46876 | 18357.46876 | 1.33576 | 1.33576 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 820.47164 | 820.47164 | 3.51864E-002 | 0.67639 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65122.85405 | 65122.85405 | 4.73586 | 4.73586 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 1414.00390 | 1414.00390 | 6.06384E-002 | 1.89399 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10477.71627 | 10477.71627 | 1.02642 | 1.02642 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 678.21437 | 678.21437 | 2.92570E-002 | 6.17350E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10604.64302 | 10604.64302 | 1.03886 | 1.03886 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71567E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 684.00562 | 684.00562 | 2.95069E-002 | 6.17278E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 59120.69683 | 59120.69683 | 5.79102 | 5.79102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 3990.86592 | 3990.86592 | 0.17215 | 0.83707 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 70158.19011 | 70158.19011 | 6.87269 | 6.87269 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 34.69000 | 1.71572E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 4104.59161 | 4104.59161 | 0.17706 | 0.83730 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9255.73103 | 9255.73103 | 0.90672 | 0.90672 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 678.21437 | 678.21437 | 2.92570E-002 | 6.17350E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9340.24127 | 9340.24127 | 0.91500 | 0.91500 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 684.00562 | 684.00562 | 2.95069E-002 | 6.17278E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21647.06813 | 21647.06813 | 1.57355 | 1.57355 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:10:00 | 33.86833 | 1.71556E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 1536.74657 | 1536.74657 | 6.59016E-002 | 0.47476 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2908.92863 | 2908.92863 | 0.28497 | 0.28497 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 221.98232 | 221.98232 | 9.57600E-003 | 1.54338E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2941.36490 | 2941.36490 | 0.28814 | 0.28814 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 223.01414 | 223.01414 | 9.62051E-003 | 1.54319E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11635.14523 | 11635.14523 | 1.13981 | 1.13981 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 1093.34823 | 1093.34823 | 4.71649E-002 | 9.91540E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 01:30:00 | 20.10000 | 1.47983E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31301.38373 | 31301.38373 | 2.27812 | 2.27812 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 35.20000 | 1.71581E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 1111.57923 | 1111.57923 | 4.76696E-002 | 1.18780 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32719.30639 | 32719.30639 | 2.38129 | 2.38129 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 35.20000 | 1.71581E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 997.14172 | 997.14172 | 4.27620E-002 | 1.18780 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 20.10000 | 1.47983E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30532.06454 | 30532.06454 | 2.22533 | 2.22533 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 34.43500 | 1.71567E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.36735 | 00:10:00 | 20.10000 | 1.47983E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 | |
43 | CORRIDOR_FLR_6 | Cooling | 11213.54134 | 11213.54134 | 0.81513 | 0.81513 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 1154.73810 | 1154.73810 | 4.95201E-002 | 0.12562 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 20.10000 | 1.47983E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 463655.11 | 22.59812 | 22.59812 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | FLR_3_DOAS | Cooling | Sensible | 55571.34 | 18.00898 | 2.05125 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.13423 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48110 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.60473 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.91941E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.40897E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.60473 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8468.90949 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.40897E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 176.60451 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32638 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15659 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16710 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43305E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08300E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16710 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1237.93625 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08300E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 26.36797 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28772 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20570 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14731 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54853 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85221E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.63063E-006 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14731 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 872.22805 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.63063E-006 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 18.30453 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28673 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.43649 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14681 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.72879E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.28740E-006 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14681 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 947.30085 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.28740E-006 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 19.98523 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.17677 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40847 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.05069E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.32739E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.13014E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.05069E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 586.40681 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.13014E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12.37469 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.20579 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.36086E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.64136 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05395E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.93036E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.64136 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9064.89358 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.93036E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 189.48915 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33576 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10774 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68391 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.53635E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.89080E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68391 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4447.42651 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.89080E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 93.87434 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.73586 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21049 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.42476 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56130 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81009E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25026E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.42476 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14291.22338 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25026E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 299.83438 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02642 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.02642 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25198E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.27378E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68227 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74400E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.27378E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02642 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1431.09441 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25198E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.81543 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.03886 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.03886 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25184E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.32268E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68228 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74147E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.32268E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.03886 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1430.92644 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25184E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.81098 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.79102 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.79102 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69764E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.36068E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68319 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66370E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.36068E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.79102 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19405.04602 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69764E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 553.49160 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.87269 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.87269 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69810E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.93391E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68239 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84024E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.93391E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.87269 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19410.34648 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69810E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 553.65747 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.90672 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.90672 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25198E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.80937E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68221 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77836E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.80937E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.90672 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1431.09441 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25198E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.81543 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91500 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.91500 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25184E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.84174E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68221 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77595E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.84174E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.91500 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1430.92644 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25184E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.81098 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57355 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.75429 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80566 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.05113E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.07765E-005 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80566 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5804.07082 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.07765E-005 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 123.37271 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28497 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28497 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.12994E-006 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.17915E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68231 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72030E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.17915E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28497 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 357.77159 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12994E-006 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 10.20641 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28814 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28814 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.12957E-006 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.19152E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68232 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71781E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.19152E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28814 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 357.72964 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12957E-006 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 10.20526 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13981 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.13981 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.01085E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.84492E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68213 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82357E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.84492E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.13981 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2298.52967 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01085E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 65.57567 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27812 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11093 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16640 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43445E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.37318E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16640 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7284.93437 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.37318E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.37412 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.38129 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10613 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21922 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58998E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.51897E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21922 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7451.57908 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.51897E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 156.67423 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22533 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.36240E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13937 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07707E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.26042E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13937 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6012.98189 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.26042E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 125.39037 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81513 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38526 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41734 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.88930E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.94188E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41734 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3362.75220 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.94188E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 72.09869 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65448 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65448 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.76265 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65448 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.59812 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.59812 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51573 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.59812 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.59812 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.77944 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08978 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.35370E-002 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 869048.90443 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.10404E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.59812 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 136928.98387 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.19791E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2398.63124 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.59812 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.10404E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.53410E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.19791E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.20000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.94246 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.71581E-002 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 113467.38685 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.05279E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 12429.56338 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08739E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 217.73286 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.05279E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.17497E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.08739E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 4.27341E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6977.17475 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.33360E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.28003 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.33360E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 702.77742 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 266744.65562 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 266744.66000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.33360E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 4.27341E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 5.12809 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 4.27341E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4830.53341 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 4.27341E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1196441.33932 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1199757.49000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 136.77235 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8512.65 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 1244.20 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 876.71 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 952.14 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 589.40 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9111.60 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 4470.13 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 14364.60 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 1539.64 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 1539.47 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 20877.92 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 20883.95 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 1539.64 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 1539.47 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 5833.51 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 384.97 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 384.92 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 2473.33 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 7322.22 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 7489.76 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6044.04 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 3379.67 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 109705.12 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 9958.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 17463.59 | 13996.86 | 3466.73 | 0.80 | 1953.13 | 19.81 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17667.57 | 14162.63 | 3504.95 | 0.80 | 1976.03 | 20.04 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 97186.41 | 78297.80 | 18888.61 | 0.81 | 10885.81 | 110.41 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 118817.07 | 94660.08 | 24156.99 | 0.80 | 13266.83 | 134.56 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 15516.14 | 12409.05 | 3107.10 | 0.80 | 1734.27 | 17.59 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15651.51 | 12519.20 | 3132.31 | 0.80 | 1749.47 | 17.74 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4828.95 | 3876.21 | 952.74 | 0.80 | 540.30 | 5.48 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4880.72 | 3918.40 | 962.32 | 0.80 | 546.12 | 5.54 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19651.44 | 15672.18 | 3979.25 | 0.80 | 2194.83 | 22.26 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 695866.95 | 455984.43 | 239882.52 | 0.66 | 82765.08 | 839.45 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 68360.07 | 43807.88 | 24552.19 | 0.64 | 8222.82 | 83.40 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.2491428470E-002 | 1.7386646670E-002 | Pass | Pass | 1.3637759765E-003 | 2.4303252742E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5437879141E-002 | 1.9481674230E-002 | Pass | Pass | 2.6689882864E-003 | 2.6982697845E-003 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7776634511E-002 | 2.2980952186E-002 | Pass | Pass | 1.9141774378E-003 | 3.2313077662E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4330301836E-003 | 9.1669195866E-003 | Pass | Pass | 1.0936052116E-003 | 1.3629114819E-003 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.2986653045E-003 | 5.5666875667E-003 | Pass | Pass | 9.1938856915E-004 | 9.9468964107E-004 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6167732884E-002 | 0.2088932323 | Pass | Pass | 1.4496946220E-002 | 4.2668304492E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.6741135385E-002 | 5.8766670530E-002 | Pass | Pass | 3.7617655179E-003 | 7.3254351257E-003 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4524478310E-002 | 3.5751951748E-002 | Pass | Pass | 2.4914364925E-003 | 4.5340495189E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.5357698885E-002 | 0.3189123184 | Pass | Pass | 0.1277186125 | 0.5278531862 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4123496720E-002 | 0.3174011694 | Pass | Pass | 0.1262031134 | 0.5151433383 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4908889822E-005 | 8.4061143021E-005 | Pass | Pass | 1.9242391787E-002 | 3.7369215864E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.1763754142E-002 | 0.2555576129 | Pass | Pass | 9.7070457036E-002 | 0.3634714940 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.8416208081E-002 | 0.3172346153 | Pass | Pass | 0.1321750461 | 0.5426518212 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.7271344668E-002 | 0.3150446556 | Pass | Pass | 0.1279395487 | 0.5297651572 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.6090984772E-003 | 7.2638048758E-003 | Pass | Pass | 8.5712968193E-004 | 1.1663700382E-003 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.6750584544E-002 | 0.3234385012 | Pass | Pass | 0.1315570917 | 0.5453968457 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5326649281E-002 | 0.3214051747 | Pass | Pass | 0.1293882246 | 0.5313708328 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1007847635 | 0.3123212350 | Pass | Pass | 0.1237172304 | 0.5076166315 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.6434429301E-002 | 5.8745985129E-002 | Pass | Pass | 7.4856631878E-003 | 2.5742258353E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0684830728E-002 | 4.7054564998E-002 | Pass | Pass | 8.4061692791E-003 | 2.7007312509E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.3387084920E-002 | 9.6392173077E-002 | Pass | Pass | 1.7762379611E-002 | 3.3351857101E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.2215448741E-002 | 7.0759840922E-003 | Pass | Pass | 1.3637311953E-003 | 1.0288030321E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3141.05 | -210.3 | -2794.8 | -12170.6 | 22107.60 | 10072.98 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.241 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.241 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.241 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 3.241 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 3.241 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 3.241 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.241 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.241 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.3255 | 1978.83 | 20432.33 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 188.94 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.5625 | 67.07 | 909.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.76 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.5625 | 77.67 | 1053.39 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 10.14 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.5208 | 164.24 | 742.52 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.17 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.7005 | 94.76 | 729.69 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 4.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 11.5174 | 188.86 | 2175.19 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.16 | 0.0000 | Y | 16.40 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.6875 | 1308.19 | 12673.07 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.63 | 0.0000 | Y | 99.03 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 9.7951 | 1863.81 | 18256.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.45 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 9.7951 | 1864.32 | 18261.31 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.49 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.23 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.18 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 9.7951 | 220.77 | 2162.52 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 15.45 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.37 | 0.0000 | Y | 35.40 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.37 | 0.0000 | Y | 35.40 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 13.0243 | 103.30 | 1345.47 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 9.4981 | 11345.29 | 107758.18 | 495.27 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.83 | 83.83 | 262.65 | |
Exterior Lighting Total | 16690.39 | 262.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 266744.66 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1199757.49 | 2.96 | 1199968.38 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11965.67 | 17463.59 | 13996.86 | 3466.73 | 0.80 | - | 1953.13 | 19.81 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12102.59 | 17667.57 | 14162.63 | 3504.95 | 0.80 | - | 1976.03 | 20.04 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 66093.89 | 97186.41 | 78297.80 | 18888.61 | 0.81 | - | 10885.81 | 110.41 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 82143.32 | 118817.07 | 94660.08 | 24156.99 | 0.80 | - | 13266.83 | 134.56 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10665.41 | 15516.14 | 12409.05 | 3107.10 | 0.80 | - | 1734.27 | 17.59 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10756.04 | 15651.51 | 12519.20 | 3132.31 | 0.80 | - | 1749.47 | 17.74 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3301.38 | 4828.95 | 3876.21 | 952.74 | 0.80 | - | 540.30 | 5.48 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3335.99 | 4880.72 | 3918.40 | 962.32 | 0.80 | - | 546.12 | 5.54 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13564.73 | 19651.44 | 15672.18 | 3979.25 | 0.80 | - | 2194.83 | 22.26 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 869048.90 | 695866.95 | 455984.43 | 239882.52 | 0.66 | - | 82765.08 | 839.45 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 113467.39 | 68360.07 | 43807.88 | 24552.19 | 0.64 | - | 8222.82 | 83.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8468.91 | 8512.65 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1237.94 | 1244.20 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 872.23 | 876.71 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 947.30 | 952.14 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 586.41 | 589.40 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9064.89 | 9111.60 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4447.43 | 4470.13 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14291.22 | 14364.60 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1431.09 | 1539.64 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1430.93 | 1539.47 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19405.05 | 20877.92 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19410.35 | 20883.95 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1431.09 | 1539.64 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1430.93 | 1539.47 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5804.07 | 5833.51 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 357.77 | 384.97 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 357.73 | 384.92 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2298.53 | 2473.33 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7284.93 | 7322.22 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7451.58 | 7489.76 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6012.98 | 6044.04 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 3362.75 | 3379.67 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 136928.98 | 109705.12 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 12429.56 | 9958.35 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 722.23 | 703.64 | 1.00 | 1.19 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.04 | 730.98 | 703.64 | 1.00 | 1.19 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.79 | 4074.78 | 703.64 | 1.00 | 0.96 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.87 | 4835.87 | 703.64 | 1.00 | 0.95 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.91 | 638.00 | 703.64 | 1.00 | 1.22 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.91 | 643.82 | 703.64 | 1.00 | 1.22 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 200.51 | 703.64 | 1.00 | 1.75 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 202.75 | 703.64 | 1.00 | 1.74 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.14 | 802.02 | 703.64 | 1.00 | 1.17 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1314.72 | 22.60 | 47911.95 | 2120.17 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.042734 | 6977.17 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002334 | 702.78 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.042734 | 4830.53 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 43116.94 | 43116.94 | 21.79 | 3.134 | 3.134 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 21:30:00 | 24.00 | 24.00 | 0.00906 | 29.80 | 0.01715 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4489.03 | 4489.03 | 66.93 | 0.326 | 0.326 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00927 | 34.58 | 0.01716 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3957.51 | 3957.51 | 50.95 | 0.288 | 0.288 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:20:00 | 24.00 | 24.00 | 0.00931 | 31.57 | 0.01715 | 0.092 | 0.00 |
MECH_FLR_1 | 3944.70 | 3944.70 | 24.02 | 0.287 | 0.287 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:00:00 | 24.00 | 24.00 | 0.00889 | 31.89 | 0.01715 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2431.93 | 2431.93 | 25.66 | 0.177 | 0.177 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:40:00 | 24.00 | 24.00 | 0.00891 | 34.24 | 0.01716 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44097.96 | 44097.96 | 565.07 | 3.206 | 3.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00857 | 34.58 | 0.01716 | 0.000 | 0.00 |
CAFE_FLR_1 | 18357.47 | 18357.47 | 97.20 | 1.336 | 1.336 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 23.99 | 0.01035 | 35.20 | 0.01716 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65122.85 | 65122.85 | 49.78 | 4.736 | 4.736 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 23.99 | 0.01005 | 34.35 | 0.01716 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10477.72 | 10477.72 | 268.51 | 1.026 | 1.026 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00874 | 34.58 | 0.01716 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10604.64 | 10604.64 | 271.79 | 1.039 | 1.039 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 21.11 | 21.11 | 0.00874 | 34.46 | 0.01716 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 59120.70 | 59120.70 | 2410.74 | 5.791 | 5.791 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 21.11 | 21.11 | 0.00866 | 35.03 | 0.01716 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 70158.19 | 70158.19 | 2860.03 | 6.873 | 6.873 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 21.11 | 21.11 | 0.00884 | 34.69 | 0.01716 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9255.73 | 9255.73 | 237.19 | 0.907 | 0.907 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 21.11 | 21.11 | 0.00878 | 31.73 | 0.01715 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9340.24 | 9340.24 | 239.39 | 0.915 | 0.915 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 21.11 | 21.11 | 0.00878 | 31.73 | 0.01715 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21647.07 | 21647.07 | 55.59 | 1.574 | 1.574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:10:00 | 24.00 | 24.00 | 0.00950 | 33.87 | 0.01716 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2908.93 | 2908.93 | 74.55 | 0.285 | 0.285 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00872 | 34.58 | 0.01716 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2941.36 | 2941.36 | 75.39 | 0.288 | 0.288 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00872 | 34.58 | 0.01716 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11635.15 | 11635.15 | 474.31 | 1.140 | 1.140 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 21.11 | 21.11 | 0.00882 | 35.20 | 0.01716 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31301.38 | 31301.38 | 94.38 | 2.278 | 2.278 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 24.00 | 23.98 | 0.01034 | 35.20 | 0.01716 | 1.188 | 0.00 |
DINING_FLR_6 | 32719.31 | 32719.31 | 98.65 | 2.381 | 2.381 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 24.00 | 23.99 | 0.01026 | 35.20 | 0.01716 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30532.06 | 30532.06 | 295.55 | 2.225 | 2.225 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 24.00 | 23.97 | 0.01013 | 34.44 | 0.01716 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11213.54 | 11213.54 | 27.21 | 0.815 | 0.815 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00906 | 35.20 | 0.01716 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 22.09 | 0.01480 | 20.10 | 0.01480 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 351.56 | 351.56 | 5.24 | 0.015 | 0.079 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01064 | 20.10 | 0.01480 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 90.00 | 90.00 | 1.16 | 0.004 | 0.092 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01134 | 20.10 | 0.01480 | 0.092 | 0.00 |
MECH_FLR_1 | 167.18 | 167.18 | 1.02 | 0.007 | 0.007 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01175 | 20.10 | 0.01480 | 0.000 | 0.00 |
STORAGE_FLR_1 | 105.59 | 105.59 | 1.11 | 0.005 | 0.058 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01159 | 20.10 | 0.01480 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 352.96 | 352.96 | 4.52 | 0.015 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01100 | 20.10 | 0.01480 | 0.000 | 0.00 |
CAFE_FLR_1 | 820.47 | 820.47 | 4.34 | 0.035 | 0.676 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01055 | 20.10 | 0.01480 | 0.676 | 0.00 |
LOBBY_FLR_1 | 1414.00 | 1414.00 | 1.08 | 0.061 | 1.894 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01141 | 20.10 | 0.01480 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 678.21 | 678.21 | 17.38 | 0.029 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01093 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 684.01 | 684.01 | 17.53 | 0.030 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01092 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 3990.87 | 3990.87 | 162.73 | 0.172 | 0.837 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01076 | 20.10 | 0.01480 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4104.59 | 4104.59 | 167.33 | 0.177 | 0.837 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01072 | 20.10 | 0.01480 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 678.21 | 678.21 | 17.38 | 0.029 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01093 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 684.01 | 684.01 | 17.53 | 0.030 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01092 | 20.10 | 0.01480 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 1536.75 | 1536.75 | 3.95 | 0.066 | 0.475 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00997 | 20.10 | 0.01480 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 221.98 | 221.98 | 5.69 | 0.010 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01050 | 20.10 | 0.01480 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 223.01 | 223.01 | 5.72 | 0.010 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.01049 | 20.10 | 0.01480 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 1093.35 | 1093.35 | 44.57 | 0.047 | 0.099 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 01:30:00 | 21.11 | 21.11 | 0.01039 | 20.10 | 0.01480 | 0.099 | 0.00 |
BANQUET_FLR_6 | 1111.58 | 1111.58 | 3.35 | 0.048 | 1.188 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00951 | 20.10 | 0.01480 | 1.188 | 0.00 |
DINING_FLR_6 | 997.14 | 997.14 | 3.01 | 0.043 | 1.188 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 21.00 | 21.00 | 0.00964 | 20.10 | 0.01480 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.367 | 00:10:00 | 21.00 | 24.00 | 0.00887 | 20.10 | 0.01480 | 0.367 | 0.00 | |
CORRIDOR_FLR_6 | 1154.74 | 1154.74 | 2.80 | 0.050 | 0.126 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 21.00 | 21.00 | 0.00932 | 20.10 | 0.01480 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.60 | 22.60 | 0.00 | 0.00 | 22.5981 | 11.6545 | 22.5981 | 0.5157 | 0.3000 |
FLR_3_DOAS | 18.01 | 2.05 | 0.00 | 0.00 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8468.909 | 8468.909 | 1.604728 | 0.00007409 | 176.605 | 12/21 00:10:00 | 12/21 00:10:00 | 8468.91 | 8468.91 | 1.604728 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 8516.51 | 8516.51 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 1237.936 | 1237.936 | 0.167104 | 0.00001083 | 26.368 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1237.94 | 1237.94 | 0.167104 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01064045 | 68.4624 | 351.56 | 0.00 | 1244.84 | 1244.84 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 872.228 | 872.228 | 0.147311 | 0.00000763 | 18.305 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 872.23 | 872.23 | 0.147311 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01133868 | 72.8782 | 90.00 | 0.00 | 877.12 | 877.12 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 947.301 | 947.301 | 0.146805 | 0.00000829 | 19.985 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 947.30 | 947.30 | 0.146805 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01174857 | 75.4638 | 167.18 | 0.00 | 952.60 | 952.60 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 586.407 | 586.407 | 0.090507 | 0.00000513 | 12.375 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 586.41 | 586.41 | 0.090507 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01159404 | 74.4893 | 105.59 | 0.00 | 589.69 | 589.69 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9064.894 | 9064.894 | 1.641365 | 0.00007930 | 189.489 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9064.89 | 9064.89 | 1.641365 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01099616 | 70.7114 | 352.96 | 0.00 | 9115.80 | 9115.80 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 4447.427 | 4447.427 | 0.683911 | 0.00003891 | 93.874 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4447.43 | 4447.43 | 0.683911 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01055366 | 67.9142 | 820.47 | 0.00 | 4472.32 | 4472.32 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14291.223 | 14291.223 | 2.424761 | 0.00012503 | 299.834 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14291.22 | 14291.22 | 2.424761 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01140863 | 73.3197 | 1414.00 | 0.00 | 14371.37 | 14371.37 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11965.674 | -999.000 | 1.026424 | 0.00042738 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 11965.67 | 11286.19 | 1.026424 | 21.68 | 15.76 | 0.00874400 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00874400 | 56.0544 | 10477.72 | 0.00 | 11982.52 | 11141.57 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 1431.094 | 1431.094 | 0.061735 | 0.00001252 | 40.815 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1431.09 | 1431.09 | 0.061735 | 21.11 | 17.42 | 0.01093462 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01093462 | 69.8440 | 678.21 | 0.00 | 1542.81 | 1542.81 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12102.586 | -999.000 | 1.038858 | 0.00043227 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | 4/21 16:20:00 | 12102.59 | 11422.06 | 1.038858 | 21.68 | 15.76 | 0.00874147 | 12.80 | 12.09 | 0.00850000 | 34.46 | 0.01715674 | 25.64 | 0.0000 | 21.11 | 0.00874147 | 56.0384 | 10604.64 | 0.00 | 12119.64 | 11275.32 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 1430.926 | 1430.926 | 0.061728 | 0.00001252 | 40.811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1430.93 | 1430.93 | 0.061728 | 21.11 | 17.41 | 0.01092032 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01092032 | 69.7542 | 684.01 | 0.00 | 1542.63 | 1542.63 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 66093.894 | -999.000 | 5.791024 | 0.00236068 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | unknown | 4/21 15:20:00 | 66093.89 | 63528.07 | 5.791024 | 21.68 | 15.69 | 0.00866370 | 12.80 | 12.09 | 0.00850000 | 35.03 | 0.01715783 | 25.79 | 0.0000 | 21.11 | 0.00866370 | 55.5439 | 59120.70 | 0.00 | 66189.25 | 62646.18 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 19405.046 | 19405.046 | 0.837072 | 0.00016976 | 553.492 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19405.05 | 19405.05 | 0.837072 | 21.11 | 17.28 | 0.01076201 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01076201 | 68.7630 | 3990.87 | 0.00 | 20919.61 | 20919.61 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 82143.324 | -999.000 | 6.872686 | 0.00293391 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | unknown | 4/21 16:00:00 | 82143.32 | 75781.43 | 6.872686 | 21.68 | 15.85 | 0.00884024 | 12.80 | 12.09 | 0.00850000 | 34.69 | 0.01715717 | 25.70 | 0.0000 | 21.11 | 0.00884024 | 56.6619 | 70158.19 | 0.00 | 82255.85 | 74903.47 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 19410.346 | 19410.346 | 0.837300 | 0.00016981 | 553.657 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19410.35 | 19410.35 | 0.837300 | 21.11 | 17.24 | 0.01071650 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01071650 | 68.4771 | 4104.59 | 0.00 | 20925.32 | 20925.32 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10665.414 | -999.000 | 0.906718 | 0.00038094 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | 4/21 09:50:00 | 10665.41 | 9979.95 | 0.906718 | 21.68 | 15.79 | 0.00877836 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01715153 | 24.95 | 0.0000 | 21.11 | 0.00877836 | 56.2717 | 9255.73 | 0.00 | 10680.28 | 9856.51 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 1431.094 | 1431.094 | 0.061735 | 0.00001252 | 40.815 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1431.09 | 1431.09 | 0.061735 | 21.11 | 17.42 | 0.01093462 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01093462 | 69.8440 | 678.21 | 0.00 | 1542.81 | 1542.81 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10756.042 | -999.000 | 0.914996 | 0.00038417 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | 4/21 09:50:00 | 10756.04 | 10070.37 | 0.914996 | 21.68 | 15.79 | 0.00877595 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01715153 | 24.95 | 0.0000 | 21.11 | 0.00877595 | 56.2564 | 9340.24 | 0.00 | 10771.05 | 9945.50 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 1430.926 | 1430.926 | 0.061728 | 0.00001252 | 40.811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1430.93 | 1430.93 | 0.061728 | 21.11 | 17.41 | 0.01092032 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01092032 | 69.7542 | 684.01 | 0.00 | 1542.63 | 1542.63 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 5804.071 | 5804.071 | 0.805657 | 0.00005078 | 123.373 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5804.07 | 5804.07 | 0.805657 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00996925 | 64.2157 | 1536.75 | 0.00 | 5836.48 | 5836.48 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3301.380 | -999.000 | 0.284965 | 0.00011792 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 3301.38 | 3131.18 | 0.284965 | 21.68 | 15.74 | 0.00872030 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00872030 | 55.9045 | 2908.93 | 0.00 | 3306.06 | 3090.08 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 357.772 | 357.772 | 0.015434 | 0.00000313 | 10.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 357.77 | 357.77 | 0.015434 | 21.11 | 17.06 | 0.01049630 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01049630 | 67.0902 | 221.98 | 0.00 | 385.70 | 385.70 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3335.994 | -999.000 | 0.288143 | 0.00011915 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 3335.99 | 3165.86 | 0.288143 | 21.68 | 15.74 | 0.00871781 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00871781 | 55.8887 | 2941.36 | 0.00 | 3340.73 | 3124.20 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 357.730 | 357.730 | 0.015432 | 0.00000313 | 10.205 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 357.73 | 357.73 | 0.015432 | 21.11 | 17.06 | 0.01048886 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01048886 | 67.0434 | 223.01 | 0.00 | 385.66 | 385.66 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13564.735 | -999.000 | 1.139815 | 0.00048449 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | unknown | 4/21 14:50:00 | 13564.73 | 12561.83 | 1.139815 | 21.68 | 15.83 | 0.00882357 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 0.0000 | 21.11 | 0.00882357 | 56.5575 | 11635.15 | 0.00 | 13583.40 | 12413.67 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 2298.530 | 2298.530 | 0.099154 | 0.00002011 | 65.576 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 01:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 01:30:00 | 2298.53 | 2298.53 | 0.099154 | 21.11 | 16.97 | 0.01039095 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01039095 | 66.4290 | 1093.35 | 0.00 | 2477.95 | 2477.95 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7284.934 | 7284.934 | 1.166399 | 0.00006373 | 153.374 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 7284.93 | 7284.93 | 1.166399 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00950624 | 61.2769 | 1111.58 | 0.00 | 7325.74 | 7325.74 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7451.579 | 7451.579 | 1.219219 | 0.00006519 | 156.674 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 7451.58 | 7451.58 | 1.219219 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00963747 | 62.1099 | 997.14 | 0.00 | 7493.34 | 7493.34 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6012.982 | 6012.982 | 1.139367 | 0.00005260 | 125.390 | 12/21 00:10:00 | 12/21 00:10:00 | 6012.98 | 6012.98 | 1.139367 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6046.78 | 6046.78 | ||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 3362.752 | 3362.752 | 0.417344 | 0.00002942 | 72.099 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 3362.75 | 3362.75 | 0.417344 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00931610 | 60.0700 | 1154.74 | 0.00 | 3381.47 | 3381.47 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 869048.904 | -999.000 | 22.598122 | 0.03104041 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 869048.90 | 513130.91 | 22.598122 | 29.78 | 22.09 | 0.01353700 | 11.09 | 11.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 51.6037 | 23.99 | 0.00964381 | 51.8183 | 310395.91 | 0.00 | 870129.07 | 512383.60 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 136928.984 | 136928.984 | 6.779436 | 0.00119791 | 2398.631 | unknown | unknown | unknown | 136928.98 | 136928.98 | 6.779436 | 0.00 | -6.26 | 0.00000000 | 16.70 | 13.18 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 172.0122 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 132629.66 | 132629.66 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 113467.387 | -999.000 | 2.051317 | 0.00405279 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 113467.39 | 59031.63 | 2.051317 | 35.20 | 25.83 | 0.01715815 | 11.94 | 11.74 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 99.9965 | 21.11 | 0.00876099 | 56.1601 | 183311.94 | 0.00 | 113580.35 | 59887.34 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 12429.563 | 12429.563 | 0.615395 | 0.00010874 | 217.733 | unknown | unknown | unknown | 12429.56 | 12429.56 | 0.615395 | 0.00 | -6.26 | 0.00000000 | 16.70 | 13.18 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 333.3216 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 12039.30 | 12039.30 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8468.909 | 8468.909 | 1.604728 | 0.00007409 | 176.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 3.1123 | 3.174913 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 8468.91 | 8468.91 | 1.0000 | 1.93144202 | 1.604728 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07408216 | 60.00 | 32.22 | 27.78 | 0.000 | 8468.91 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 8516.51 | 8516.51 | 1.93144202 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1237.936 | 1237.936 | 0.167104 | 0.00001083 | 26.368 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.4549 | 0.464090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1237.94 | 1237.94 | 1.0000 | 0.20112575 | 0.167104 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01082890 | 60.00 | 32.22 | 27.78 | 0.000 | 1237.94 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01064045 | 21.00 | 0.01064045 | 68.4624 | 351.56 | 0.00 | 1244.84 | 1244.84 | 0.20112575 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.67 | 15.47 | 0.00800000 | 43124.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 872.228 | 872.228 | 0.147311 | 0.00000763 | 18.305 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.3205 | 0.326990 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 872.23 | 872.23 | 1.0000 | 0.17730333 | 0.147311 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00762985 | 60.00 | 32.22 | 27.78 | 0.000 | 872.23 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01133868 | 21.00 | 0.01133868 | 72.8782 | 90.00 | 0.00 | 877.12 | 877.12 | 0.17730333 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.45 | 15.02 | 0.00800000 | 41881.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 947.301 | 947.301 | 0.146805 | 0.00000829 | 19.985 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.3481 | 0.355134 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 947.30 | 947.30 | 1.0000 | 0.17669399 | 0.146805 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00828656 | 60.00 | 32.22 | 27.78 | 0.000 | 947.30 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01174857 | 21.00 | 0.01174857 | 75.4638 | 167.18 | 0.00 | 952.60 | 952.60 | 0.17669399 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.89 | 15.18 | 0.00800000 | 42326.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 586.407 | 586.407 | 0.090507 | 0.00000513 | 12.375 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.2155 | 0.219838 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 586.41 | 586.41 | 1.0000 | 0.10893368 | 0.090507 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00512962 | 60.00 | 32.22 | 27.78 | 0.000 | 586.41 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01159404 | 21.00 | 0.01159404 | 74.4893 | 105.59 | 0.00 | 589.69 | 589.69 | 0.10893368 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.91 | 15.19 | 0.00800000 | 42348.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9064.894 | 9064.894 | 1.641365 | 0.00007930 | 189.489 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 3.3313 | 3.398341 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9064.89 | 9064.89 | 1.0000 | 1.97553810 | 1.641365 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07929555 | 60.00 | 32.22 | 27.78 | 0.000 | 9064.89 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01099616 | 21.00 | 0.01099616 | 70.7114 | 352.96 | 0.00 | 9115.80 | 9115.80 | 1.97553810 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.13 | 14.90 | 0.00800000 | 41549.1 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4447.427 | 4447.427 | 0.683911 | 0.00003891 | 93.874 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 1.6344 | 1.667297 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4447.43 | 4447.43 | 1.0000 | 0.82315223 | 0.683911 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03890406 | 60.00 | 32.22 | 27.78 | 0.000 | 4447.43 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01055366 | 21.00 | 0.01055366 | 67.9142 | 820.47 | 0.00 | 4472.32 | 4472.32 | 0.82315223 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.93 | 15.20 | 0.00800000 | 42367.9 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14291.223 | 14291.223 | 2.424761 | 0.00012503 | 299.834 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 5.2519 | 5.357642 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14291.22 | 14291.22 | 1.0000 | 2.91843040 | 2.424761 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.12501310 | 60.00 | 32.22 | 27.78 | 0.000 | 14291.22 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01140863 | 21.00 | 0.01140863 | 73.3197 | 1414.00 | 0.00 | 14371.37 | 14371.37 | 2.91843040 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.43 | 15.01 | 0.00800000 | 41859.1 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11965.674 | -999.000 | 1.026424 | 0.00042738 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0947 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.026424 | 1.23539916 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 1.0001 | 1.000087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 11965.67 | 11286.19 | 1.0000 | 1.23539916 | 1.026424 | 21.68 | 15.76 | 0.00874400 | 44007.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.42733457 | 6.70 | 13.37 | 6.67 | 0.000 | 11965.67 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00874400 | 21.11 | 0.00874400 | 56.0544 | 10477.72 | 0.00 | 11982.52 | 11141.57 | 1.23539916 | 21.68 | 15.77 | 0.00874400 | 44007.9 | 12.85 | 12.10 | 0.00847439 | 34308.6 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1431.094 | 1431.094 | 0.061735 | 0.00001252 | 40.815 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.026424 | 1.23539916 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.5259 | 0.536503 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1431.09 | 1431.09 | 1.0000 | 0.07430396 | 0.061735 | 21.11 | 17.42 | 0.01093462 | 48990.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251856 | 60.00 | 32.22 | 27.78 | 0.000 | 1431.09 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01093462 | 21.11 | 0.01093462 | 69.8440 | 678.21 | 0.00 | 1542.81 | 1542.81 | 0.07430396 | 16.60 | 15.84 | 0.01093462 | 44364.6 | 36.85 | 22.33 | 0.01093462 | 65128.1 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12102.586 | -999.000 | 1.038858 | 0.00043227 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0900 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.038858 | 1.25036374 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 1.0115 | 1.011530 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | unknown | unknown | 4/21 16:20:00 | Sensible | 12102.59 | 11422.06 | 1.0000 | 1.25036374 | 1.038858 | 21.68 | 15.76 | 0.00874147 | 44001.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.43222417 | 6.70 | 13.37 | 6.67 | 0.000 | 12102.59 | 34.46 | 0.01715674 | 25.64 | 0.00000000 | 0.0000 | 21.11 | 0.00874147 | 21.11 | 0.00874147 | 56.0384 | 10604.64 | 0.00 | 12119.64 | 11275.32 | 1.25036374 | 21.68 | 15.77 | 0.00874147 | 44001.4 | 12.85 | 12.10 | 0.00847402 | 34308.6 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1430.926 | 1430.926 | 0.061728 | 0.00001252 | 40.811 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.038858 | 1.25036374 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.5259 | 0.536441 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1430.93 | 1430.93 | 1.0000 | 0.07429526 | 0.061728 | 21.11 | 17.41 | 0.01092032 | 48954.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251709 | 60.00 | 32.22 | 27.78 | 0.000 | 1430.93 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01092032 | 21.11 | 0.01092032 | 69.7542 | 684.01 | 0.00 | 1542.63 | 1542.63 | 0.07429526 | 16.60 | 15.83 | 0.01092032 | 44328.4 | 36.85 | 22.32 | 0.01092032 | 65091.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66093.894 | -999.000 | 5.791024 | 0.00236068 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9454 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.791024 | 6.97004745 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 5.5242 | 5.524104 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | unknown | unknown | unknown | 4/21 15:20:00 | Sensible | 66093.89 | 63528.07 | 1.0000 | 6.97004745 | 5.791024 | 21.68 | 15.69 | 0.00866370 | 43804.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.36043584 | 6.70 | 13.37 | 6.67 | 0.000 | 66093.89 | 35.03 | 0.01715783 | 25.79 | 0.00000000 | 0.0000 | 21.11 | 0.00866370 | 21.11 | 0.00866370 | 55.5439 | 59120.70 | 0.00 | 66189.25 | 62646.18 | 6.97004745 | 21.68 | 15.70 | 0.00866370 | 43804.8 | 12.88 | 12.10 | 0.00846238 | 34308.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19405.046 | 19405.046 | 0.837072 | 0.00016976 | 553.492 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.791024 | 6.97004745 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 7.1312 | 7.274765 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19405.05 | 19405.05 | 1.0000 | 1.00749507 | 0.837072 | 21.11 | 17.28 | 0.01076201 | 48551.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16974649 | 60.00 | 32.22 | 27.78 | 0.000 | 19405.05 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01076201 | 21.11 | 0.01076201 | 68.7630 | 3990.87 | 0.00 | 20919.61 | 20919.61 | 1.00749507 | 16.60 | 15.69 | 0.01076201 | 43927.6 | 36.86 | 22.22 | 0.01076201 | 64691.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 82143.324 | -999.000 | 6.872686 | 0.00293391 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2736 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.872686 | 8.27193028 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 6.8656 | 6.865509 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | unknown | unknown | unknown | 4/21 16:00:00 | Sensible | 82143.32 | 75781.43 | 1.0000 | 8.27193028 | 6.872686 | 21.68 | 15.85 | 0.00884024 | 44252.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.93361512 | 6.70 | 13.37 | 6.67 | 0.000 | 82143.32 | 34.69 | 0.01715717 | 25.70 | 0.00000000 | 0.0000 | 21.11 | 0.00884024 | 21.11 | 0.00884024 | 56.6619 | 70158.19 | 0.00 | 82255.85 | 74903.47 | 8.27193028 | 21.68 | 15.85 | 0.00884024 | 44252.6 | 12.82 | 12.09 | 0.00848820 | 34308.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19410.346 | 19410.346 | 0.837300 | 0.00016981 | 553.657 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.872686 | 8.27193028 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 7.1332 | 7.276752 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19410.35 | 19410.35 | 1.0000 | 1.00777057 | 0.837300 | 21.11 | 17.24 | 0.01071650 | 48435.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16979286 | 60.00 | 32.22 | 27.78 | 0.000 | 19410.35 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01071650 | 21.11 | 0.01071650 | 68.4771 | 4104.59 | 0.00 | 20925.32 | 20925.32 | 1.00777057 | 16.60 | 15.65 | 0.01071650 | 43812.4 | 36.86 | 22.19 | 0.01071650 | 64576.3 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10665.414 | -999.000 | 0.906718 | 0.00038094 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1585 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.906718 | 1.09132098 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 0.8914 | 0.891411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | unknown | unknown | 4/21 09:50:00 | Sensible | 10665.41 | 9979.95 | 1.0000 | 1.09132098 | 0.906718 | 21.68 | 15.79 | 0.00877836 | 44095.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.38089790 | 6.70 | 13.37 | 6.67 | 0.000 | 10665.41 | 31.73 | 0.01715153 | 24.95 | 0.00000000 | 0.0000 | 21.11 | 0.00877836 | 21.11 | 0.00877836 | 56.2717 | 9255.73 | 0.00 | 10680.28 | 9856.51 | 1.09132098 | 21.68 | 15.80 | 0.00877836 | 44095.1 | 12.84 | 12.10 | 0.00847939 | 34308.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1431.094 | 1431.094 | 0.061735 | 0.00001252 | 40.815 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.906718 | 1.09132098 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.5259 | 0.536503 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1431.09 | 1431.09 | 1.0000 | 0.07430396 | 0.061735 | 21.11 | 17.42 | 0.01093462 | 48990.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251856 | 60.00 | 32.22 | 27.78 | 0.000 | 1431.09 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01093462 | 21.11 | 0.01093462 | 69.8440 | 678.21 | 0.00 | 1542.81 | 1542.81 | 0.07430396 | 16.60 | 15.84 | 0.01093462 | 44364.6 | 36.85 | 22.33 | 0.01093462 | 65128.1 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10756.042 | -999.000 | 0.914996 | 0.00038417 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1541 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.914996 | 1.10128504 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 0.8990 | 0.898986 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | unknown | unknown | 4/21 09:50:00 | Sensible | 10756.04 | 10070.37 | 1.0000 | 1.10128504 | 0.914996 | 21.68 | 15.79 | 0.00877595 | 44089.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.38413455 | 6.70 | 13.37 | 6.67 | 0.000 | 10756.04 | 31.73 | 0.01715153 | 24.95 | 0.00000000 | 0.0000 | 21.11 | 0.00877595 | 21.11 | 0.00877595 | 56.2564 | 9340.24 | 0.00 | 10771.05 | 9945.50 | 1.10128504 | 21.68 | 15.80 | 0.00877595 | 44089.0 | 12.84 | 12.10 | 0.00847905 | 34308.6 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1430.926 | 1430.926 | 0.061728 | 0.00001252 | 40.811 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.914996 | 1.10128504 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.5259 | 0.536441 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1430.93 | 1430.93 | 1.0000 | 0.07429526 | 0.061728 | 21.11 | 17.41 | 0.01092032 | 48954.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251709 | 60.00 | 32.22 | 27.78 | 0.000 | 1430.93 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01092032 | 21.11 | 0.01092032 | 69.7542 | 684.01 | 0.00 | 1542.63 | 1542.63 | 0.07429526 | 16.60 | 15.83 | 0.01092032 | 44328.4 | 36.85 | 22.32 | 0.01092032 | 65091.9 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5804.071 | 5804.071 | 0.805657 | 0.00005078 | 123.373 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 2.1330 | 2.175890 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5804.07 | 5804.07 | 1.0000 | 0.96968422 | 0.805657 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05077136 | 60.00 | 32.22 | 27.78 | 0.000 | 5804.07 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00996925 | 21.00 | 0.00996925 | 64.2157 | 1536.75 | 0.00 | 5836.48 | 5836.48 | 0.96968422 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.50 | 15.41 | 0.00800000 | 42953.7 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3301.380 | -999.000 | 0.284965 | 0.00011792 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0506 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.284965 | 0.34298300 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 0.2759 | 0.275928 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 3301.38 | 3131.18 | 1.0000 | 0.34298300 | 0.284965 | 21.68 | 15.74 | 0.00872030 | 43947.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11790342 | 6.70 | 13.37 | 6.67 | 0.000 | 3301.38 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00872030 | 21.11 | 0.00872030 | 55.9045 | 2908.93 | 0.00 | 3306.06 | 3090.08 | 0.34298300 | 21.68 | 15.75 | 0.00872030 | 43947.7 | 12.86 | 12.10 | 0.00847090 | 34308.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 357.772 | 357.772 | 0.015434 | 0.00000313 | 10.206 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.284965 | 0.34298300 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.1315 | 0.134125 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 357.77 | 357.77 | 1.0000 | 0.01857599 | 0.015434 | 21.11 | 17.06 | 0.01049630 | 47877.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00312962 | 60.00 | 32.22 | 27.78 | 0.000 | 357.77 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01049630 | 21.11 | 0.01049630 | 67.0902 | 221.98 | 0.00 | 385.70 | 385.70 | 0.01857599 | 16.60 | 15.46 | 0.01049630 | 43254.9 | 36.87 | 22.04 | 0.01049630 | 64018.2 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3335.994 | -999.000 | 0.288143 | 0.00011915 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0460 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.288143 | 0.34680744 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 0.2788 | 0.278821 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 3335.99 | 3165.86 | 1.0000 | 0.34680744 | 0.288143 | 21.68 | 15.74 | 0.00871781 | 43941.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11913960 | 6.70 | 13.37 | 6.67 | 0.000 | 3335.99 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00871781 | 21.11 | 0.00871781 | 55.8887 | 2941.36 | 0.00 | 3340.73 | 3124.20 | 0.34680744 | 21.68 | 15.75 | 0.00871781 | 43941.3 | 12.86 | 12.10 | 0.00847052 | 34308.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 357.730 | 357.730 | 0.015432 | 0.00000313 | 10.205 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.288143 | 0.34680744 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.1315 | 0.134109 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 357.73 | 357.73 | 1.0000 | 0.01857381 | 0.015432 | 21.11 | 17.06 | 0.01048886 | 47858.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00312926 | 60.00 | 32.22 | 27.78 | 0.000 | 357.73 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01048886 | 21.11 | 0.01048886 | 67.0434 | 223.01 | 0.00 | 385.66 | 385.66 | 0.01857381 | 16.60 | 15.45 | 0.01048886 | 43236.0 | 36.87 | 22.03 | 0.01048886 | 63999.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13564.735 | -999.000 | 1.139815 | 0.00048449 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2426 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.139815 | 1.37187540 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 1.1338 | 1.133736 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | unknown | unknown | unknown | 4/21 14:50:00 | Sensible | 13564.73 | 12561.83 | 1.0000 | 1.37187540 | 1.139815 | 21.68 | 15.83 | 0.00882357 | 44209.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.48444242 | 6.70 | 13.37 | 6.67 | 0.000 | 13564.73 | 35.20 | 0.01715815 | 25.83 | 0.00000000 | 0.0000 | 21.11 | 0.00882357 | 21.11 | 0.00882357 | 56.5575 | 11635.15 | 0.00 | 13583.40 | 12413.67 | 1.37187540 | 21.68 | 15.84 | 0.00882357 | 44209.9 | 12.82 | 12.09 | 0.00848585 | 34308.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2298.530 | 2298.530 | 0.099154 | 0.00002011 | 65.576 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.139815 | 1.37187540 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 0.8447 | 0.861697 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 01:30:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 01:30:00 | Sensible | 2298.53 | 2298.53 | 1.0000 | 0.11934125 | 0.099154 | 21.11 | 16.97 | 0.01039095 | 47609.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02010649 | 60.00 | 32.22 | 27.78 | 0.000 | 2298.53 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01039095 | 21.11 | 0.01039095 | 66.4290 | 1093.35 | 0.00 | 2477.95 | 2477.95 | 0.11934125 | 16.60 | 15.36 | 0.01039095 | 42988.1 | 36.87 | 21.96 | 0.01039095 | 63751.7 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7284.934 | 7284.934 | 1.166399 | 0.00006373 | 153.374 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 2.6772 | 2.731052 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 7284.93 | 7284.93 | 1.0000 | 1.40387258 | 1.166399 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06372528 | 60.00 | 32.22 | 27.78 | 0.000 | 7284.93 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00950624 | 21.00 | 0.00950624 | 61.2769 | 1111.58 | 0.00 | 7325.74 | 7325.74 | 1.40387258 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.72 | 15.12 | 0.00800000 | 42153.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7451.579 | 7451.579 | 1.219219 | 0.00006519 | 156.674 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 2.7384 | 2.793525 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | Sensible | 7451.58 | 7451.58 | 1.0000 | 1.46744625 | 1.219219 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06518301 | 60.00 | 32.22 | 27.78 | 0.000 | 7451.58 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00963747 | 21.00 | 0.00963747 | 62.1099 | 997.14 | 0.00 | 7493.34 | 7493.34 | 1.46744625 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.61 | 15.08 | 0.00800000 | 42041.1 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6012.982 | 6012.982 | 1.139367 | 0.00005260 | 125.390 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 2.2097 | 2.254209 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6012.98 | 6012.98 | 1.0000 | 1.37133664 | 1.139367 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05259882 | 60.00 | 32.22 | 27.78 | 0.000 | 6012.98 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6046.78 | 6046.78 | 1.37133664 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3362.752 | 3362.752 | 0.417344 | 0.00002942 | 72.099 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 1.2358 | 1.260663 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | Sensible | 3362.75 | 3362.75 | 1.0000 | 0.50231331 | 0.417344 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02941582 | 60.00 | 32.22 | 27.78 | 0.000 | 3362.75 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00931610 | 21.00 | 0.00931610 | 60.0700 | 1154.74 | 0.00 | 3381.47 | 3381.47 | 0.50231331 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.20 | 15.67 | 0.00800000 | 43666.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 869048.904 | -999.000 | 22.598122 | 0.03104041 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1030.0046 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.598122 | 27.19898580 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 72.6361 | 72.636148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 869048.90 | 513130.91 | 1.0000 | 27.19898580 | 22.598122 | 29.78 | 22.09 | 0.01353700 | 64528.2 | 11.09 | 11.09 | 0.00850000 | 32576.7 | 31.03724683 | 6.70 | 13.37 | 6.67 | 47911.954 | 821136.95 | 35.20 | 0.01715815 | 25.83 | 11.66146000 | 51.6037 | 23.99 | 0.00966877 | 23.99 | 0.00964381 | 51.8183 | 310395.91 | 0.00 | 870129.07 | 512383.60 | 27.19898580 | 29.78 | 22.10 | 0.01353700 | 64528.2 | 11.49 | 11.37 | 0.00832236 | 32537.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 136928.984 | 136928.984 | 6.779436 | 0.00119791 | 2398.631 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.598122 | 27.19898580 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 50.3206 | 51.333356 | unknown | unknown | unknown | unknown | unknown | Sensible | 136928.98 | 136928.98 | 1.0000 | 8.15969574 | 6.779436 | 0.00 | -6.26 | 0.00000000 | 25.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 1.19779228 | 60.00 | 32.22 | 27.78 | 0.000 | 136928.98 | 0.00 | 0.00000000 | -6.26 | 11.66146000 | 172.0122 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 132629.66 | 132629.66 | 8.15969574 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 18.98 | 5.31 | 0.00000000 | 19092.9 | ||
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 113467.387 | -999.000 | 2.051317 | 0.00405279 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7361 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 42.72975315 | 13.37 | 6.70 | 6.67 | 1196441.34 | 9.4837 | 9.483740 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 113467.39 | 59031.63 | 1.0000 | 2.46895513 | 2.051317 | 35.20 | 25.83 | 0.01715815 | 79404.6 | 11.94 | 11.74 | 0.00850000 | 33447.0 | 4.05237873 | 6.70 | 13.37 | 6.67 | 2195.006 | 111272.38 | 35.20 | 0.01715815 | 25.83 | 2.05124512 | 99.9965 | 21.11 | 0.00876708 | 21.11 | 0.00876099 | 56.1601 | 183311.94 | 0.00 | 113580.35 | 59887.34 | 2.46895513 | 35.20 | 25.84 | 0.01715815 | 79404.6 | 11.80 | 11.72 | 0.00853814 | 33401.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12429.563 | 12429.563 | 0.615395 | 0.00010874 | 217.733 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 2.33336056 | 54.44 | 82.22 | 27.78 | 272113.00 | 4.5678 | 4.659723 | unknown | unknown | unknown | unknown | unknown | Sensible | 12429.56 | 12429.56 | 1.0000 | 0.74068654 | 0.615395 | 0.00 | -6.26 | 0.00000000 | 25.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.10872815 | 60.00 | 32.22 | 27.78 | 0.000 | 12429.56 | 0.00 | 0.00000000 | -6.26 | 2.05124512 | 333.3216 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 12039.30 | 12039.30 | 0.74068654 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 18.98 | 5.31 | 0.00000000 | 19092.9 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 97.00 | 4842.00 | 0.00 |
RETAIL_1_FLR_1 | 5943.17 | 1447.17 | 0.00 |
RETAIL_2_FLR_1 | 2950.33 | 3033.00 | 0.00 |
MECH_FLR_1 | 2033.67 | 3737.00 | 0.00 |
STORAGE_FLR_1 | 1373.67 | 4846.67 | 0.00 |
LAUNDRY_FLR_1 | 8299.17 | 2030.83 | 2025.17 |
CAFE_FLR_1 | 7787.17 | 730.67 | 421.00 |
LOBBY_FLR_1 | 5849.67 | 709.67 | 0.00 |
ROOM_1_FLR_3 | 252.00 | 6936.50 | 58.50 |
ROOM_2_FLR_3 | 179.00 | 7102.33 | 64.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 36.67 | 8757.00 | 36.67 |
ROOM_5_FLR_3 | 184.33 | 6656.83 | 67.83 |
ROOM_6_FLR_3 | 161.67 | 6762.33 | 70.33 |
CORRIDOR_FLR_3 | 146.00 | 7298.50 | 0.00 |
ROOM_1_FLR_6 | 1233.67 | 6722.67 | 117.83 |
ROOM_2_FLR_6 | 1152.83 | 6822.33 | 142.33 |
ROOM_3_MULT9_FLR_6 | 418.50 | 6959.67 | 83.33 |
BANQUET_FLR_6 | 8586.00 | 20.67 | 3.67 |
DINING_FLR_6 | 8722.17 | 3.50 | 0.00 |
KITCHEN_FLR_6 | 8750.17 | 6609.83 | 6609.83 |
CORRIDOR_FLR_6 | 3085.00 | 3201.50 | 0.00 |
Facility | 8760.00 | 8760.00 | 7023.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 5.33 | 0.00 | 5.33 |
ROOM_2_FLR_3 | 0.00 | 1.67 | 0.00 | 1.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 11.67 | 0.00 | 11.67 |
ROOM_5_FLR_3 | 0.00 | 12.00 | 0.00 | 12.00 |
ROOM_6_FLR_3 | 0.00 | 8.17 | 0.00 | 8.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 17.00 | 0.00 | 17.00 |
ROOM_2_FLR_6 | 0.00 | 10.33 | 0.00 | 10.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 64.17 | 0.00 | 64.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 71.33 | 0.00 | 71.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.139 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.318 | 0.129 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.657 | 0.043 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.792 | 0.048 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.835 | 0.048 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.237 | 0.137 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.288 | 0.102 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.645 | 0.042 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.478 | 0.166 | 0.000 | 0.006 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.478 | 0.166 | 0.000 | 0.007 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.543 | 0.074 | 0.000 | 0.011 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.478 | 0.166 | 0.000 | 0.007 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.478 | 0.166 | 0.000 | 0.007 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.582 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.478 | 0.166 | 0.000 | 0.007 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.478 | 0.166 | 0.000 | 0.008 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.543 | 0.135 | 0.000 | 0.012 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.400 | 0.048 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.636 | 0.048 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 17.534 | 0.138 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.157 | 0.034 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.875 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.846 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.341 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.637 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.678 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.369 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.580 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.381 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.469 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.469 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.532 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.469 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.469 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.458 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.469 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.469 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.532 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.693 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.963 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 11.615 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.934 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 46787830.41 | 0.00 | 46787830.41 | 0.00 | 46787830.41 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5237845.47 | 0.00 | 5237845.47 | 291644.21 | 5529489.68 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4340021.10 | 0.00 | 4340021.10 | 112575.04 | 4452596.14 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 4384807.92 | 0.00 | 4384807.92 | 266060.50 | 4650868.42 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2669162.34 | 0.00 | 2669162.34 | 153502.25 | 2822664.60 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 50849569.81 | 0.00 | 50849569.81 | 363292.03 | 51212861.84 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 20880006.81 | 0.00 | 20880006.81 | 644696.04 | 21524702.85 | 21330615.53 | 5559.68 | 1097.57 | 2102.76 | 0.00 |
LOBBY_FLR_1 | 72399900.09 | 0.00 | 72399900.09 | 1842043.85 | 74241943.94 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 6438.79 | 1953314.41 | 169277.80 | 2122592.21 | 1946875.62 | 0.00 | 8542.67 | 217.33 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 6940.42 | 1953587.93 | 169264.88 | 2122852.81 | 1946647.51 | 0.00 | 8542.72 | 217.28 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 6107.10 | 26403994.37 | 47230.40 | 26451224.78 | 26397887.27 | 0.00 | 8678.00 | 82.00 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 6927.99 | 26412033.72 | 47243.32 | 26459277.03 | 26405105.73 | 0.00 | 8649.49 | 110.51 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 6766.10 | 1953641.72 | 169277.80 | 2122919.52 | 1946875.62 | 0.00 | 8542.75 | 217.25 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 7178.36 | 1953825.88 | 169264.88 | 2123090.76 | 1946647.51 | 0.00 | 8542.75 | 217.25 | 0.00 |
CORRIDOR_FLR_3 | 23504078.32 | 0.00 | 23504078.32 | 204690.91 | 23708769.23 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 7437.49 | 494156.40 | 169311.27 | 663467.67 | 486718.90 | 0.00 | 8537.67 | 222.33 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 8233.91 | 494895.79 | 169298.35 | 664194.14 | 486661.88 | 0.00 | 8537.67 | 222.33 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 7564.11 | 3134484.52 | 86625.57 | 3221110.10 | 3126920.42 | 0.00 | 8537.86 | 222.14 | 0.00 |
BANQUET_FLR_6 | 37723469.09 | 0.00 | 37723469.09 | 413415.57 | 38136884.66 | 37458366.31 | 4467.52 | 441.94 | 3850.54 | 0.00 |
DINING_FLR_6 | 39750860.31 | 0.00 | 39750860.31 | 413415.57 | 40164275.88 | 37458366.31 | 2863.56 | 594.92 | 5301.52 | 0.00 |
KITCHEN_FLR_6 | 46858788.35 | 0.00 | 46858788.35 | 370102.78 | 47228891.14 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12362741.95 | 0.00 | 12362741.95 | 362235.95 | 12724977.90 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 1183709.85 | 0.45E+10 | 17058331.55 | 0.45E+10 | 0.43E+10 | 6515.16 | 8727.00 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4836 | 0.0000 | 1.4836 | 0.0000 | 1.4836 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1661 | 0.0000 | 0.1661 | 0.0092 | 0.1753 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1376 | 0.0000 | 0.1376 | 0.0036 | 0.1412 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1390 | 0.0000 | 0.1390 | 0.0084 | 0.1475 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0846 | 0.0000 | 0.0846 | 0.0049 | 0.0895 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 1.6124 | 0.0000 | 1.6124 | 0.0115 | 1.6239 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.6621 | 0.0000 | 0.6621 | 0.0204 | 0.6825 | 0.6764 | 5559.68 | 1097.57 | 2102.76 |
LOBBY_FLR_1 | 2.2958 | 0.0000 | 2.2958 | 0.0584 | 2.3542 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0002 | 0.0619 | 0.0054 | 0.0673 | 0.0617 | 0.00 | 8542.67 | 217.33 |
ROOM_2_FLR_3 | 0.0617 | 0.0002 | 0.0619 | 0.0054 | 0.0673 | 0.0617 | 0.00 | 8542.72 | 217.28 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0002 | 0.8375 | 0.0015 | 0.8390 | 0.8373 | 0.00 | 8649.49 | 110.51 |
ROOM_5_FLR_3 | 0.0617 | 0.0002 | 0.0619 | 0.0054 | 0.0673 | 0.0617 | 0.00 | 8542.75 | 217.25 |
ROOM_6_FLR_3 | 0.0617 | 0.0002 | 0.0620 | 0.0054 | 0.0673 | 0.0617 | 0.00 | 8542.75 | 217.25 |
CORRIDOR_FLR_3 | 0.7453 | 0.0000 | 0.7453 | 0.0065 | 0.7518 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0002 | 0.0157 | 0.0054 | 0.0210 | 0.0154 | 0.00 | 8537.67 | 222.33 |
ROOM_2_FLR_6 | 0.0154 | 0.0003 | 0.0157 | 0.0054 | 0.0211 | 0.0154 | 0.00 | 8537.67 | 222.33 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0002 | 0.0994 | 0.0027 | 0.1021 | 0.0992 | 0.00 | 8537.86 | 222.14 |
BANQUET_FLR_6 | 1.1962 | 0.0000 | 1.1962 | 0.0131 | 1.2093 | 1.1878 | 4467.52 | 441.94 | 3850.54 |
DINING_FLR_6 | 1.2605 | 0.0000 | 1.2605 | 0.0131 | 1.2736 | 1.1878 | 2863.56 | 594.92 | 5301.52 |
KITCHEN_FLR_6 | 1.4859 | 0.0000 | 1.4859 | 0.0117 | 1.4976 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3920 | 0.0000 | 0.3920 | 0.0115 | 0.4035 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 79.4430 | 0.0228 | 79.4658 | 0.4271 | 79.8929 | 73.9670 | 6515.16 | 8727.00 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.53E+09 | 0.00 | 0.53E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 93713071.71 | 63594.28 | 93776665.99 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 16.8930 | 0.0000 | 16.8930 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.9716 | 0.0020 | 2.9736 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 8486.72 | 0.00 | 0.00 | 273.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8548.37 | 211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 16.8947 | 0.0000 | 0.0000 | 16.9006 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.9717 | 2.9806 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 3997 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
Electricity:Building | 2533.08 | 32086.41 | 25-NOV-06:00 | 158241.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 332.05 | 3744.83 | 02-JAN-02:10 | 25084.28 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2525.98 | 31945.26 | 25-NOV-06:00 | 158000.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 867.81 | 7743.29 | 25-NOV-06:00 | 71560.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 867.81 | 7743.29 | 25-NOV-06:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 867.81 | 7743.29 | 25-NOV-06:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 867.81 | 7743.29 | 25-NOV-06:00 | 71560.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.95 | 223.93 | 02-JAN-02:10 | 1401.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.94 | 259.31 | 02-JAN-02:10 | 1623.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.64 | 250.98 | 02-JAN-02:10 | 1507.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 7.74 | 88.65 | 02-JAN-02:10 | 581.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 30.74 | 335.90 | 25-NOV-06:00 | 2922.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.40 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.40 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 248.03 | 3017.54 | 25-NOV-06:00 | 18583.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.03 | 906.12 | 25-NOV-06:00 | 8554.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.03 | 906.12 | 25-NOV-06:00 | 8554.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 325.45 | 4437.75 | 01-JAN-02:10 | 23570.01 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 325.54 | 4438.96 | 01-JAN-02:10 | 23576.46 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.35 | 67.90 | 01-JAN-02:10 | 391.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.35 | 67.89 | 01-JAN-02:10 | 391.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 38.55 | 525.67 | 01-JAN-02:10 | 2791.95 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 211.25 | 2605.82 | 25-NOV-06:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.40 | 356.52 | 25-NOV-06:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.40 | 356.52 | 25-NOV-06:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 211.25 | 2605.82 | 25-NOV-06:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.40 | 356.52 | 25-NOV-06:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.40 | 356.52 | 25-NOV-06:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.47 | 1173.58 | 15-JUN-22:30 | 3257.72 | 28-NOV-08:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 5369.54 | 87309.79 | 23-JAN-06:20 | 284886.33 | 13-JUN-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.41 | 0.00 | 01-JAN-11:10 | 1891.94 | 07-MAY-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.97 | 1008.23 | 16-SEP-03:10 | 1192.49 | 17-MAY-13:10 |
Fans:Electricity | 538.37 | 11673.91 | 20-AUG-05:20 | 31775.86 | 12-JUN-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 881.57 | 21041.67 | 16-JAN-06:20 | 43246.81 | 13-JUN-20:10 |
ExteriorEquipment:Electricity | 650.10 | 9607.53 | 02-JAN-02:20 | 39721.54 | 13-MAR-06:20 |
Transformer:ExteriorEquipment:Electricity | 31.07 | 542.72 | 02-JAN-02:20 | 1847.44 | 10-MAY-20:10 |
ElectricityPurchased:Facility | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
ElectricityPurchased:Plant | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
Cogeneration:ElectricityPurchased | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
ElectricityNet:Plant | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
Cogeneration:ElectricityNet | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
General:Cogeneration:ElectricityNet | 9665.86 | 173223.87 | 23-JAN-05:00 | 501453.14 | 12-JUN-19:10 |
General:Fans:Electricity | 538.37 | 11673.91 | 20-AUG-05:20 | 31775.86 | 12-JUN-18:20 |
ExteriorLights:Electricity | 262.65 | 0.00 | 01-JAN-06:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.65 | 0.00 | 01-JAN-06:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 312.13 | 8417.13 | 07-JAN-06:10 | 9938.94 | 07-JAN-09:20 |
General:HeatRecovery:Electricity | 312.13 | 8417.13 | 07-JAN-06:10 | 9938.94 | 07-JAN-09:20 |
WaterSystems:Electricity | 90.75 | 1086.70 | 28-SEP-00:20 | 4738.76 | 03-MAR-19:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.70 | 28-SEP-00:20 | 4738.76 | 03-MAR-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5037.04 | 76296.26 | 23-JAN-06:20 | 274138.93 | 13-JUN-15:20 |
General:Cooling:Electricity | 5037.04 | 76296.26 | 23-JAN-06:20 | 274138.93 | 13-JUN-15:20 |
Pumps:Electricity | 186.37 | 5014.80 | 23-JAN-06:20 | 7587.56 | 14-JUN-20:40 |
General:Pumps:Electricity | 186.37 | 5014.80 | 23-JAN-06:20 | 7587.56 | 14-JUN-20:40 |
WIRED_LTG_ELECTRICITY | 30.55 | 0.00 | 01-JAN-00:10 | 2518.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4287.97 | 32759.61 | 06-MAY-01:10 | 315630.29 | 12-JAN-18:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2499.13 | 18467.44 | 01-JAN-07:00 | 214382.14 | 25-FEB-19:10 |
WaterSystems:NaturalGas | 2477.96 | 18467.44 | 24-JAN-10:00 | 211704.30 | 09-JAN-21:40 |
Water Heater:WaterSystems:NaturalGas | 2477.96 | 18467.44 | 24-JAN-10:00 | 211704.30 | 09-JAN-21:40 |
Heating:NaturalGas | 21.17 | 0.00 | 01-JAN-00:10 | 9350.92 | 23-OCT-04:00 |
Boiler:Heating:NaturalGas | 21.17 | 0.00 | 01-JAN-00:10 | 9350.92 | 23-OCT-04:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16723.74 | 220875.36 | 23-JAN-06:20 | 829099.54 | 13-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 16723.74 | 220875.36 | 23-JAN-06:20 | 829099.54 | 13-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 16723.74 | 220875.36 | 23-JAN-06:20 | 829099.54 | 13-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-MAY-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-MAY-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-MAY-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-MAY-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-MAY-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-MAY-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 71205.69 | 935383.21 | 23-JAN-06:20 | 3514211.62 | 13-JUN-18:10 |
EnergyTransfer:Building | 7767.06 | 168607.34 | 20-AUG-13:20 | 384597.90 | 12-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 783.16 | 14207.73 | 16-SEP-03:00 | 36021.46 | 07-MAY-10:50 |
Refrigeration:EnergyTransfer | 187.00 | 4363.97 | 15-JUN-22:20 | 10341.49 | 08-DEC-08:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.50 | 2181.98 | 15-JUN-22:20 | 5170.75 | 08-DEC-08:20 |
General:Refrigeration:EnergyTransfer | 93.50 | 2181.98 | 15-JUN-22:20 | 5170.75 | 08-DEC-08:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.50 | 2181.98 | 15-JUN-22:20 | 5170.75 | 08-DEC-08:20 |
EnergyTransfer:Plant | 39372.20 | 537962.39 | 23-JAN-06:20 | 1947274.60 | 13-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.71 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.79 | 1974.69 | 16-SEP-03:10 | 2527.48 | 17-MAY-13:10 |
EnergyTransfer:Zone:BASEMENT | 651.85 | 18742.27 | 01-JAN-16:00 | 23778.63 | 15-JUN-21:00 |
Heating:EnergyTransfer | 0.16 | 0.00 | 01-JAN-00:10 | 4724.63 | 21-AUG-08:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.16 | 0.00 | 01-JAN-00:10 | 4724.63 | 21-AUG-08:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 7673.40 | 165649.87 | 20-AUG-13:20 | 380994.09 | 12-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 651.85 | 18742.27 | 01-JAN-16:00 | 23778.63 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer | 7673.40 | 165649.87 | 20-AUG-13:20 | 380994.09 | 12-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 651.85 | 18742.27 | 01-JAN-16:00 | 23778.63 | 15-JUN-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 74.72 | 1726.05 | 20-AUG-17:00 | 4179.67 | 05-JAN-14:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 74.72 | 1726.05 | 20-AUG-17:00 | 4179.67 | 05-JAN-14:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 74.72 | 1726.05 | 20-AUG-17:00 | 4179.67 | 05-JAN-14:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 60.26 | 1547.40 | 20-AUG-15:00 | 2865.98 | 13-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 60.26 | 1547.40 | 20-AUG-15:00 | 2865.98 | 13-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 60.26 | 1547.40 | 20-AUG-15:00 | 2865.98 | 13-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 61.96 | 1657.53 | 21-AUG-04:00 | 3794.52 | 13-JUN-19:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 61.96 | 1657.53 | 21-AUG-04:00 | 3794.52 | 13-JUN-19:30 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 61.96 | 1657.53 | 21-AUG-04:00 | 3794.52 | 13-JUN-19:30 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 37.11 | 1006.89 | 20-AUG-16:00 | 1979.90 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 37.11 | 1006.89 | 20-AUG-16:00 | 1979.90 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 37.11 | 1006.89 | 20-AUG-16:00 | 1979.90 | 13-JUN-18:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 637.64 | 11131.75 | 23-OCT-04:00 | 37136.89 | 05-MAY-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 637.64 | 11131.75 | 23-OCT-04:00 | 37136.89 | 05-MAY-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 637.64 | 11131.75 | 23-OCT-04:00 | 37136.89 | 05-MAY-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 301.92 | 6764.21 | 20-AUG-15:00 | 13527.27 | 05-JAN-16:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 301.92 | 6764.21 | 20-AUG-15:00 | 13527.27 | 05-JAN-16:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 301.92 | 6764.21 | 20-AUG-15:00 | 13527.27 | 05-JAN-16:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 1036.96 | 26376.91 | 20-AUG-15:00 | 48195.59 | 13-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1036.96 | 26376.91 | 20-AUG-15:00 | 48195.59 | 13-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1036.96 | 26376.91 | 20-AUG-15:00 | 48195.59 | 13-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 127.44 | 573.24 | 21-DEC-06:20 | 10964.29 | 22-FEB-16:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 320.20 | 16-MAY-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 320.20 | 16-MAY-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 127.42 | 573.24 | 21-DEC-06:20 | 10964.29 | 22-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 127.42 | 573.24 | 21-DEC-06:20 | 10964.29 | 22-FEB-16:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 123.44 | 566.68 | 21-DEC-06:20 | 11145.75 | 06-MAY-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 321.07 | 26-MAY-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 321.07 | 26-MAY-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 123.42 | 566.68 | 21-DEC-06:20 | 11145.75 | 06-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 123.42 | 566.68 | 21-DEC-06:20 | 11145.75 | 06-MAY-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 777.95 | 9332.78 | 21-DEC-06:10 | 47981.50 | 07-DEC-13:50 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 777.95 | 9332.78 | 21-DEC-06:10 | 47981.50 | 07-DEC-13:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 777.95 | 9332.78 | 21-DEC-06:10 | 47981.50 | 07-DEC-13:50 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 951.75 | 7607.22 | 21-DEC-06:20 | 77236.19 | 13-JUN-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.10 | 0.00 | 01-JAN-00:10 | 2982.18 | 02-OCT-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.10 | 0.00 | 01-JAN-00:10 | 2982.18 | 02-OCT-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 951.65 | 7607.22 | 21-DEC-06:20 | 77236.19 | 13-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 951.65 | 7607.22 | 21-DEC-06:20 | 77236.19 | 13-JUN-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 127.38 | 581.49 | 21-DEC-06:20 | 9675.67 | 24-FEB-09:30 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 299.65 | 21-AUG-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 299.65 | 21-AUG-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 127.38 | 581.49 | 21-DEC-06:20 | 9675.67 | 24-FEB-09:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 127.38 | 581.49 | 21-DEC-06:20 | 9675.67 | 24-FEB-09:30 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 123.33 | 575.10 | 21-DEC-06:20 | 9569.10 | 13-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 302.18 | 21-AUG-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 302.18 | 21-AUG-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 123.32 | 575.10 | 21-DEC-06:20 | 9569.10 | 13-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 123.32 | 575.10 | 21-DEC-06:20 | 9569.10 | 13-JUN-15:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 326.75 | 9284.02 | 21-AUG-11:10 | 13718.66 | 13-JUN-20:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 326.75 | 9284.02 | 21-AUG-11:10 | 13718.66 | 13-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 326.75 | 9284.02 | 21-AUG-11:10 | 13718.66 | 13-JUN-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 33.09 | 138.43 | 21-DEC-06:20 | 3226.48 | 24-FEB-16:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 81.77 | 25-JUN-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 81.77 | 25-JUN-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 33.08 | 138.43 | 21-DEC-06:20 | 3226.48 | 24-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 33.08 | 138.43 | 21-DEC-06:20 | 3226.48 | 24-FEB-16:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 32.03 | 136.98 | 21-DEC-06:20 | 3177.93 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 83.72 | 26-MAY-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 83.72 | 26-MAY-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 32.02 | 136.98 | 21-DEC-06:20 | 3177.93 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 32.02 | 136.98 | 21-DEC-06:20 | 3177.93 | 06-MAY-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 176.70 | 908.44 | 21-DEC-06:20 | 13975.14 | 16-JAN-16:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 418.83 | 11-JUL-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 418.83 | 11-JUL-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 176.69 | 908.44 | 21-DEC-06:20 | 13975.14 | 16-JAN-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 176.69 | 908.44 | 21-DEC-06:20 | 13975.14 | 16-JAN-16:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 557.43 | 13324.80 | 20-AUG-15:00 | 25885.86 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 557.43 | 13324.80 | 20-AUG-15:00 | 25885.86 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 557.43 | 13324.80 | 20-AUG-15:00 | 25885.86 | 12-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 589.79 | 14287.00 | 03-MAR-14:50 | 27113.45 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 589.79 | 14287.00 | 03-MAR-14:50 | 27113.45 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 589.79 | 14287.00 | 03-MAR-14:50 | 27113.45 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 689.66 | 11983.21 | 16-SEP-03:00 | 30952.24 | 07-MAY-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 689.66 | 11983.21 | 16-SEP-03:00 | 30952.24 | 07-MAY-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 174.41 | 4495.31 | 21-AUG-06:30 | 8143.20 | 13-JUN-15:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 174.41 | 4495.31 | 21-AUG-06:30 | 8143.20 | 13-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 174.41 | 4495.31 | 21-AUG-06:30 | 8143.20 | 13-JUN-15:30 |
PlantLoopHeatingDemand:Facility | 495.62 | 6139.45 | 28-JUN-00:20 | 34663.07 | 15-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 482.33 | 6129.68 | 13-JUL-02:20 | 33465.00 | 02-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 482.33 | 6129.68 | 13-JUL-02:20 | 33465.00 | 02-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 482.33 | 6129.68 | 13-JUL-02:20 | 33465.00 | 02-JAN-07:10 |
EnergyTransfer:HVAC | 24066.43 | 220875.36 | 23-JAN-06:20 | 1209322.94 | 15-JUN-10:00 |
HeatingCoils:EnergyTransfer | 13.29 | 0.00 | 01-JAN-00:10 | 5424.59 | 23-OCT-04:00 |
PlantLoopHeatingDemand:HVAC | 13.29 | 0.00 | 01-JAN-00:10 | 5424.59 | 23-OCT-04:00 |
HeatingCoils:PlantLoopHeatingDemand | 13.29 | 0.00 | 01-JAN-00:10 | 5424.59 | 23-OCT-04:00 |
CoolingCoils:EnergyTransfer | 16723.74 | 220875.36 | 23-JAN-06:20 | 829099.54 | 13-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 0.02 | 0.00 | 01-JAN-00:10 | 24071.46 | 10-FEB-01:00 |
HeatRecoveryForCooling:EnergyTransfer | 7329.38 | 0.00 | 07-JAN-05:20 | 453677.47 | 15-JUN-10:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 482.33 | 6129.68 | 13-JUL-02:20 | 33465.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 482.33 | 6129.68 | 13-JUL-02:20 | 33465.00 | 02-JAN-07:10 |
Boilers:EnergyTransfer | 13.18 | 0.00 | 01-JAN-00:10 | 5617.60 | 23-OCT-04:00 |
Chillers:EnergyTransfer | 16873.07 | 216346.72 | 23-JAN-06:20 | 833971.28 | 13-JUN-18:10 |
HeatRejection:EnergyTransfer | 21910.11 | 292642.98 | 23-JAN-06:20 | 1090772.86 | 13-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 21910.11 | 292642.98 | 23-JAN-06:20 | 1090772.86 | 13-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -651.849 | 0.000 | 0.000 | 139.599 | 188.948 | 143.105 | 0.000 | 0.000 | 0.000 | 180.197 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -74.715 | 0.000 | 0.000 | 14.163 | 8.760 | 10.186 | 20.106 | 0.000 | 1.523 | 20.807 | 0.000 | -0.814 | 0.000 | -0.015 | 0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -60.264 | 0.000 | 0.000 | 16.436 | 10.144 | 11.795 | 0.000 | 0.000 | 0.621 | 21.275 | 0.000 | 0.000 | 0.000 | -0.008 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -61.962 | 0.000 | 0.000 | 3.460 | 8.172 | 12.471 | 0.000 | 0.000 | 1.411 | 36.464 | 0.000 | 0.000 | 0.000 | -0.015 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -37.106 | 0.000 | 0.000 | 2.692 | 4.146 | 3.598 | 0.000 | 0.000 | 0.840 | 25.837 | 0.000 | 0.000 | 0.000 | -0.007 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -637.642 | 0.000 | 0.000 | 11.714 | 5.547 | 658.131 | 0.000 | 0.000 | 2.431 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 | -40.172 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -301.918 | 0.000 | 0.000 | 181.978 | 16.397 | 14.341 | 56.721 | 0.000 | 3.276 | 31.849 | 0.000 | -2.575 | 0.000 | -0.070 | 0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -1036.968 | 0.000 | 0.000 | 542.083 | 99.029 | 148.998 | 76.764 | 0.000 | 9.554 | 163.687 | 0.000 | -2.951 | 0.000 | -0.196 | 0.000 |
ROOM_1_FLR_3 | 0.025 | -105.871 | 0.000 | -21.557 | 0.000 | 0.000 | 9.588 | 10.925 | 10.478 | 57.110 | 0.000 | 4.875 | 34.915 | 0.000 | -0.444 | 0.000 | -0.045 | 0.000 |
ROOM_2_FLR_3 | 0.035 | -101.899 | 0.000 | -21.533 | 0.000 | 0.000 | 9.591 | 10.924 | 10.477 | 53.803 | 0.000 | 4.882 | 34.190 | 0.000 | -0.431 | 0.000 | -0.040 | 0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -436.100 | 0.000 | -341.846 | 0.000 | 0.000 | 0.000 | 130.455 | 194.997 | 261.410 | 0.000 | 19.136 | 179.176 | 0.000 | -6.333 | 0.000 | -0.896 | 0.000 |
ROOM_4_MULT19_FLR_3 | 0.418 | -664.001 | 0.000 | -287.928 | 0.000 | 0.000 | 182.948 | 130.491 | 195.050 | 241.574 | 0.000 | 26.751 | 176.500 | 0.000 | -1.464 | 0.000 | -0.340 | 0.000 |
ROOM_5_FLR_3 | 0.002 | -105.758 | 0.000 | -21.615 | 0.000 | 0.000 | 9.580 | 10.925 | 10.478 | 57.228 | 0.000 | 4.861 | 34.791 | 0.000 | -0.430 | 0.000 | -0.063 | -0.000 |
ROOM_6_FLR_3 | 0.002 | -101.726 | 0.000 | -21.595 | 0.000 | 0.000 | 9.583 | 10.924 | 10.477 | 53.908 | 0.000 | 4.865 | 34.024 | 0.000 | -0.406 | 0.000 | -0.056 | 0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -326.748 | 0.000 | 0.000 | 110.382 | 91.336 | 0.000 | 55.077 | 0.000 | 4.447 | 66.724 | 0.000 | -1.158 | 0.000 | -0.061 | 0.000 |
ROOM_1_FLR_6 | 0.010 | -27.696 | 0.000 | -5.387 | 0.000 | 0.000 | 2.398 | 2.731 | 2.620 | 14.182 | 0.000 | 1.209 | 10.034 | 0.000 | -0.090 | 0.000 | -0.011 | 0.000 |
ROOM_2_FLR_6 | 0.012 | -26.646 | 0.000 | -5.381 | 0.000 | 0.000 | 2.399 | 2.731 | 2.619 | 13.358 | 0.000 | 1.211 | 9.794 | 0.000 | -0.087 | 0.000 | -0.010 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.008 | -142.038 | 0.000 | -34.653 | 0.000 | 0.000 | 21.571 | 15.453 | 23.098 | 61.179 | 0.000 | 5.573 | 50.279 | 0.000 | -0.376 | 0.000 | -0.095 | 0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -557.437 | 0.000 | 0.000 | 316.002 | 35.398 | 175.857 | 22.417 | 0.000 | 1.955 | 7.173 | 0.000 | -1.304 | 0.000 | -0.060 | -0.000 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -589.798 | 0.000 | 0.000 | 315.516 | 35.398 | 175.857 | 21.966 | 0.000 | 1.931 | 40.651 | 0.000 | -1.460 | 0.000 | -0.061 | 0.000 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -689.637 | 0.000 | 0.000 | 28.857 | 14.807 | 550.372 | 26.470 | 0.000 | 1.792 | 68.632 | 0.000 | -1.263 | 0.000 | -0.031 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -174.410 | 0.000 | 0.000 | 29.046 | 24.166 | 0.000 | 23.599 | 0.000 | 1.869 | 96.419 | 0.000 | -0.669 | 0.000 | -0.021 | 0.000 |
Total Facility | 0.513 | -1711.735 | 0.000 | -5961.946 | 0.000 | 0.000 | 1959.587 | 867.806 | 2365.005 | 1116.871 | 0.000 | 105.015 | 1323.420 | 0.000 | -22.254 | 0.000 | -2.108 | -40.172 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUN-21:00 | 0.00 | 0.00 | 0.00 | -23778.83 | 0.00 | 0.00 | 5924.48 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5006.03 |
RETAIL_1_FLR_1 | 05-JAN-14:30 | 0.00 | 0.00 | 0.00 | -4179.68 | 0.00 | 0.00 | 150.60 | 198.99 | 252.59 | 3218.93 | 0.00 | 110.83 | 247.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 13-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2866.05 | 0.00 | 0.00 | 697.63 | 737.37 | 752.15 | 0.00 | 0.00 | 29.45 | 649.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 13-JUN-19:30 | 0.00 | 0.00 | 0.00 | -3794.44 | 0.00 | 0.00 | 129.09 | 668.27 | 839.45 | 0.00 | 0.00 | 71.92 | 2085.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 13-JUN-18:03 | 0.00 | 0.00 | 0.00 | -1981.76 | 0.00 | 0.00 | 99.30 | 301.36 | 229.41 | 0.00 | 0.00 | 46.72 | 1304.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 05-MAY-20:00 | 0.00 | 0.00 | 0.00 | -37137.03 | 0.00 | 0.00 | 408.89 | 453.60 | 44299.38 | 0.00 | 0.00 | 85.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8110.34 |
CAFE_FLR_1 | 05-JAN-16:03 | 0.00 | 0.00 | 0.00 | -13542.19 | 0.00 | 0.00 | 4947.99 | 119.64 | 355.63 | 5396.01 | 0.00 | 205.18 | 2517.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 13-JUN-21:10 | 0.00 | 0.00 | 0.00 | -48199.62 | 0.00 | 0.00 | 26440.96 | 5702.88 | 7389.94 | 438.60 | 0.00 | 361.43 | 7865.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 12-SEP-15:02 | 0.00 | -11804.81 | 0.00 | -752.69 | 0.00 | 0.00 | 235.28 | 235.45 | 200.18 | 7258.96 | 0.00 | 265.32 | 4362.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 13-SEP-15:02 | 0.00 | -11922.89 | 0.00 | -752.36 | 0.00 | 0.00 | 235.28 | 235.42 | 200.16 | 7460.65 | 0.00 | 267.41 | 4276.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-DEC-13:50 | 0.00 | -37146.54 | 0.00 | -10834.89 | 0.00 | 0.00 | 0.00 | 2811.47 | 2352.88 | 42091.37 | 0.00 | 1315.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -590.10 |
ROOM_4_MULT19_FLR_3 | 13-JUL-18:02 | 0.00 | -77792.40 | 0.00 | -10330.93 | 0.00 | 0.00 | 6374.59 | 8938.91 | 9021.83 | 9477.12 | 0.00 | 1037.54 | 53273.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 24-FEB-09:11 | 0.00 | -11195.73 | 0.00 | -952.78 | 0.00 | 0.00 | 72.08 | 370.00 | 453.05 | 6588.46 | 0.00 | 19.28 | 4645.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 24-FEB-09:11 | 0.00 | -11025.36 | 0.00 | -927.09 | 0.00 | 0.00 | 74.19 | 369.95 | 452.99 | 5804.96 | 0.00 | 28.40 | 5221.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 13-JUN-20:10 | 0.00 | 0.00 | 0.00 | -13718.88 | 0.00 | 0.00 | 4663.30 | 6639.35 | 0.00 | 790.18 | 0.00 | 212.78 | 1413.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 05-JAN-16:02 | 0.00 | -3292.91 | 0.00 | -189.83 | 0.00 | 0.00 | 58.82 | 58.86 | 50.05 | 1564.03 | 0.00 | 61.09 | 1689.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 07-JUN-15:02 | 0.00 | -3334.53 | 0.00 | -189.74 | 0.00 | 0.00 | 58.82 | 58.86 | 50.04 | 1845.51 | 0.00 | 73.36 | 1437.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 28-JAN-09:41 | 0.00 | -13775.18 | 0.00 | -1517.89 | 0.00 | 0.00 | 247.52 | 666.06 | 1439.98 | 6502.40 | 0.00 | 13.86 | 6423.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -25888.64 | 0.00 | 0.00 | 15645.39 | 2291.89 | 6747.90 | 262.09 | 0.00 | 91.78 | 849.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -27116.40 | 0.00 | 0.00 | 15645.31 | 2291.89 | 6747.90 | 245.26 | 0.00 | 91.78 | 2094.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 07-MAY-10:50 | 0.00 | 0.00 | 0.00 | -30942.10 | 0.00 | 0.00 | 461.90 | 403.64 | 24259.91 | 2301.38 | 0.00 | 127.40 | 3387.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 | -8143.28 | 0.00 | 0.00 | 771.14 | 548.96 | 0.00 | 1942.89 | 0.00 | 162.49 | 4717.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-18:02 | 0.00 | -158519.11 | 0.00 | -247719.57 | 0.00 | 0.00 | 73806.71 | 62596.07 | 120482.43 | 36186.25 | 0.00 | 5661.76 | 107505.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 18-JUL-08:04 | 1975.67 | 633.30 | 0.00 | -633.30 | 0.00 | 0.00 | 87.37 | 370.00 | 453.05 | 1482.59 | 0.00 | 101.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4470.52 |
ROOM_2_FLR_3 | 20-AUG-18:04 | 1974.85 | 632.87 | 0.00 | -632.87 | 0.00 | 0.00 | 283.91 | 840.80 | 484.60 | 141.95 | 0.00 | 103.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3829.64 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 02-OCT-08:05 | 17892.93 | 8556.70 | 0.00 | -8556.70 | 0.00 | 0.00 | 1726.74 | 4419.24 | 8433.45 | 11066.38 | 0.00 | 883.12 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -44421.84 |
ROOM_5_FLR_3 | 21-AUG-08:05 | 1797.69 | 628.40 | 0.00 | -628.40 | 0.00 | 0.00 | 88.31 | 370.00 | 453.05 | 2612.11 | 0.00 | 167.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5488.87 |
ROOM_6_FLR_3 | 21-AUG-08:05 | 1812.89 | 627.48 | 0.00 | -627.48 | 0.00 | 0.00 | 88.24 | 369.95 | 452.99 | 2649.72 | 0.00 | 168.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5541.79 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 10-APR-08:04 | 529.56 | 156.95 | 0.00 | -156.95 | 0.00 | 0.00 | 21.83 | 92.50 | 113.26 | 525.70 | 0.00 | 50.77 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1333.62 |
ROOM_2_FLR_6 | 22-OCT-08:04 | 533.40 | 156.70 | 0.00 | -156.70 | 0.00 | 0.00 | 32.69 | 117.71 | 163.29 | 355.06 | 0.00 | 30.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1232.73 |
ROOM_3_MULT9_FLR_6 | 11-JUL-08:05 | 2512.86 | 1007.67 | 0.00 | -1007.67 | 0.00 | 0.00 | 200.30 | 523.33 | 998.70 | 1847.71 | 0.00 | 137.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6220.52 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-08:05 | -136164.94 | 168718.13 | 0.00 | -168718.13 | 0.00 | 0.00 | 22450.13 | 29260.13 | 88178.92 | 45458.27 | 0.00 | 3598.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52781.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.7627 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.5981 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6545 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6545 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1342 | 3.1342 | 1.6047 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3264 | 0.3264 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2877 | 0.2877 | 0.1473 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2867 | 0.2867 | 0.1468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1768 | 0.1768 | 0.0905 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2058 | 3.2058 | 1.6414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3358 | 1.3358 | 0.6839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7359 | 4.7359 | 2.4248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5735 | 1.5735 | 0.8057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2781 | 2.2781 | 1.1664 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3813 | 2.3813 | 1.2192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2253 | 2.2253 | 1.1394 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8151 | 0.8151 | 0.4173 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.7627 | 22.5981 | 22.7627 | 11.6545 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6047 | 1.6047 | 1.6047 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1671 | 0.1671 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1473 | 0.1473 | 0.1473 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1468 | 0.1468 | 0.1468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0905 | 0.0905 | 0.0905 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6414 | 1.6414 | 1.6414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6839 | 0.6839 | 0.6839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4248 | 2.4248 | 2.4248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8057 | 0.8057 | 0.8057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1664 | 1.1664 | 1.1664 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2192 | 1.2192 | 1.2192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1394 | 1.1394 | 1.1394 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4173 | 0.4173 | 0.4173 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6545 | 11.6545 | 11.6545 | 11.6545 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 71.33 |
Number of hours not met | 71.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 21.17 | 9350.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5037.04 | 274138.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 867.81 | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.65 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.07 | 1847.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 538.37 | 31775.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 186.37 | 7587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 312.13 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.76 | 2477.96 | 211704.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.41 | 1891.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.97 | 1192.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.65 | 9665.86 |
Natural Gas | 1788.84 | 4287.97 |
Additional | 0.00 | 0.00 |
Total | 3509.48 | 13953.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 76.49 |
Space Heating | 0.00 |
Space Cooling | 443.98 |
Fans (All) | 47.45 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 851.97 |
Subtotal | 851.97 |
Natural Gas [MJ/m2] | |
Space Heating | 1.87 |
Service Water Heating | 218.41 |
Miscellaneous (All) | 377.95 |
Subtotal | 377.95 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.22 |
Space Heating | 0.15 |
Space Cooling | 36.10 |
Fans (All) | 3.86 |
Service Water Heating | 18.41 |
Receptacle Equipment | 24.70 |
Miscellaneous | 10.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7941.67 | 818.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8699.33 | 60.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8716.17 | 43.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8645.67 | 114.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8655.50 | 104.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8662.50 | 97.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8675.33 | 84.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8656.17 | 103.83 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8667.50 | 92.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7941.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 818.33 | 0.00 | 0.00 | 0.00 |
Average | 8689.75 | 70.25 | 0.00 | 0.00 | 0.00 |
Sum | 191174.50 | 1545.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 605670.33 | 104746.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4131.67 | 22.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4132.50 | 21.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4140.50 | 13.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4131.33 | 22.67 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4132.50 | 21.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4130.33 | 23.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4130.67 | 23.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4128.50 | 25.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1224995.00 | 20720.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245416.33 | 298.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 104746.67 | 0.00 | 0.00 | 0.00 |
Average | 283162.53 | 5724.52 | 0.00 | 0.00 | 0.00 |
Sum | 6229575.67 | 125939.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:34
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549251E+11 | 21871.23 | 06-JAN-22:00 | 24.60 | 22.00 | 0.767900E+10 | 4781.06 | 06-JAN-22:10 | 24.50 | 21.98 |
February | 0.500984E+11 | 21859.79 | 24-FEB-22:00 | 26.80 | 22.90 | 0.701088E+10 | 4778.58 | 24-FEB-22:10 | 26.67 | 22.83 |
March | 0.550225E+11 | 21700.43 | 01-MAR-22:00 | 26.00 | 23.18 | 0.772954E+10 | 4742.90 | 01-MAR-22:10 | 25.83 | 23.12 |
April | 0.533257E+11 | 21795.56 | 28-APR-21:00 | 28.50 | 25.82 | 0.746685E+10 | 4764.09 | 28-APR-21:10 | 28.43 | 25.81 |
May | 0.556320E+11 | 22101.67 | 05-MAY-21:00 | 29.00 | 26.74 | 0.779313E+10 | 4833.32 | 05-MAY-21:10 | 29.02 | 26.76 |
June | 0.546065E+11 | 23778.63 | 15-JUN-21:00 | 29.00 | 26.74 | 0.765869E+10 | 4836.86 | 13-JUN-21:30 | 29.00 | 26.74 |
July | 0.558817E+11 | 22079.49 | 28-JUL-21:00 | 25.00 | 23.59 | 0.781068E+10 | 4828.28 | 27-JUL-21:10 | 25.00 | 23.59 |
August | 0.554360E+11 | 22103.65 | 15-AUG-21:00 | 27.00 | 24.83 | 0.778266E+10 | 4834.11 | 15-AUG-21:10 | 26.87 | 24.82 |
September | 0.536746E+11 | 22044.54 | 08-SEP-21:00 | 28.00 | 25.20 | 0.751186E+10 | 4820.36 | 08-SEP-21:10 | 27.68 | 24.93 |
October | 0.546690E+11 | 21770.31 | 05-OCT-21:00 | 26.50 | 25.32 | 0.764515E+10 | 4758.02 | 05-OCT-21:10 | 26.65 | 25.42 |
November | 0.533605E+11 | 21968.16 | 22-NOV-22:00 | 25.60 | 23.63 | 0.745591E+10 | 4803.25 | 22-NOV-22:10 | 25.42 | 23.59 |
December | 0.552161E+11 | 22017.79 | 08-DEC-22:00 | 28.10 | 23.77 | 0.771811E+10 | 4814.51 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.651848E+12 | 0.912625E+11 | ||||||||
Minimum of Months | 0.500984E+11 | 21700.43 | 24.60 | 22.00 | 0.701088E+10 | 4742.90 | 24.50 | 21.98 | ||
Maximum of Months | 0.558817E+11 | 23778.63 | 29.00 | 26.74 | 0.781068E+10 | 4836.86 | 29.02 | 26.76 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.680780E+10 | 4179.67 | 05-JAN-14:30 | 33.80 | 23.21 | 0.792097E+09 | 491.82 | 17-JAN-23:19 | 24.30 | 21.68 |
February | 0.627551E+10 | 3780.58 | 03-FEB-15:10 | 33.07 | 23.71 | 0.726486E+09 | 491.82 | 02-FEB-23:19 | 33.07 | 23.71 |
March | 0.660808E+10 | 3325.07 | 13-MAR-18:15 | 30.33 | 23.91 | 0.806656E+09 | 491.82 | 10-MAR-23:19 | 30.33 | 23.91 |
April | 0.614723E+10 | 3202.72 | 01-APR-17:13 | 32.00 | 27.14 | 0.775652E+09 | 491.81 | 27-APR-23:19 | 27.83 | 24.40 |
May | 0.623382E+10 | 3461.01 | 05-MAY-19:10 | 30.92 | 26.05 | 0.795162E+09 | 491.83 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.615066E+10 | 3481.72 | 12-JUN-19:10 | 31.17 | 27.49 | 0.777841E+09 | 491.81 | 11-JUN-23:19 | 31.17 | 27.49 |
July | 0.589025E+10 | 3096.30 | 14-JUL-19:30 | 29.85 | 24.95 | 0.782409E+09 | 491.80 | 14-JUL-22:19 | 27.27 | 24.17 |
August | 0.585624E+10 | 3075.29 | 14-AUG-19:20 | 29.40 | 27.71 | 0.774825E+09 | 491.83 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.586027E+10 | 3321.86 | 13-SEP-19:20 | 30.33 | 26.40 | 0.759022E+09 | 491.81 | 13-SEP-23:19 | 28.00 | 25.79 |
October | 0.599838E+10 | 3296.02 | 28-OCT-13:30 | 31.95 | 26.58 | 0.774718E+09 | 491.81 | 12-OCT-22:19 | 31.95 | 26.58 |
November | 0.621317E+10 | 3781.17 | 19-NOV-13:00 | 32.40 | 24.76 | 0.759810E+09 | 491.81 | 22-NOV-23:19 | 24.33 | 23.33 |
December | 0.667363E+10 | 4166.63 | 08-DEC-14:00 | 33.00 | 23.23 | 0.786697E+09 | 491.84 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.747150E+11 | 0.931138E+10 | ||||||||
Minimum of Months | 0.585624E+10 | 3075.29 | 29.40 | 23.21 | 0.726486E+09 | 491.80 | 22.00 | 19.41 | ||
Maximum of Months | 0.680780E+10 | 4179.67 | 33.80 | 27.71 | 0.806656E+09 | 491.84 | 33.07 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504516E+10 | 2453.67 | 31-JAN-21:10 | 26.73 | 22.00 | 0.905043E+09 | 569.53 | 31-JAN-23:19 | 26.07 | 22.28 |
February | 0.468929E+10 | 2567.32 | 22-FEB-21:10 | 27.43 | 22.28 | 0.834210E+09 | 569.53 | 21-FEB-23:19 | 27.43 | 22.28 |
March | 0.523518E+10 | 2597.75 | 29-MAR-20:10 | 28.00 | 23.68 | 0.929911E+09 | 569.53 | 10-MAR-23:19 | 28.00 | 23.68 |
April | 0.509160E+10 | 2642.80 | 27-APR-20:10 | 29.37 | 24.32 | 0.897264E+09 | 569.53 | 02-APR-23:19 | 29.37 | 24.32 |
May | 0.519279E+10 | 2767.86 | 05-MAY-20:10 | 29.83 | 26.38 | 0.921065E+09 | 569.55 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.515022E+10 | 2865.98 | 13-JUN-20:10 | 30.67 | 27.30 | 0.902749E+09 | 569.53 | 11-JUN-23:19 | 30.67 | 27.30 |
July | 0.507388E+10 | 2576.42 | 14-JUL-20:40 | 28.77 | 24.59 | 0.909979E+09 | 569.55 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.504147E+10 | 2541.53 | 14-AUG-20:10 | 29.00 | 28.18 | 0.904621E+09 | 569.55 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.491624E+10 | 2702.18 | 13-SEP-20:10 | 29.92 | 26.86 | 0.878611E+09 | 569.53 | 13-SEP-23:19 | 28.00 | 25.79 |
October | 0.496141E+10 | 2441.58 | 04-OCT-20:10 | 27.92 | 25.10 | 0.892770E+09 | 569.52 | 04-OCT-22:19 | 27.00 | 25.53 |
November | 0.485299E+10 | 2422.30 | 03-NOV-20:10 | 25.50 | 24.73 | 0.870373E+09 | 569.53 | 20-NOV-23:19 | 26.27 | 24.09 |
December | 0.501373E+10 | 2388.72 | 07-DEC-21:10 | 26.88 | 23.89 | 0.900400E+09 | 569.55 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.602640E+11 | 0.107470E+11 | ||||||||
Minimum of Months | 0.468929E+10 | 2388.72 | 25.50 | 22.00 | 0.834210E+09 | 569.52 | 22.00 | 19.41 | ||
Maximum of Months | 0.523518E+10 | 2865.98 | 30.67 | 28.18 | 0.929911E+09 | 569.55 | 30.67 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495041E+10 | 2001.82 | 05-JAN-21:00 | 27.00 | 23.38 | 0.188105E+09 | 119.03 | 05-JAN-22:10 | 26.38 | 23.18 |
February | 0.459353E+10 | 2018.60 | 22-FEB-21:00 | 27.50 | 22.29 | 0.174693E+09 | 120.11 | 22-FEB-22:10 | 27.00 | 22.22 |
March | 0.513370E+10 | 2318.66 | 29-MAR-20:00 | 28.00 | 23.68 | 0.195431E+09 | 120.45 | 20-MAR-21:30 | 28.00 | 23.68 |
April | 0.516338E+10 | 2878.18 | 30-APR-19:20 | 32.33 | 26.74 | 0.191824E+09 | 120.45 | 26-APR-23:19 | 32.33 | 26.74 |
May | 0.568797E+10 | 3321.66 | 05-MAY-19:20 | 30.73 | 26.11 | 0.200531E+09 | 120.45 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.604401E+10 | 3794.52 | 13-JUN-19:30 | 30.90 | 27.22 | 0.196975E+09 | 120.45 | 26-JUN-22:19 | 24.27 | 24.10 |
July | 0.548278E+10 | 3227.07 | 14-JUL-20:00 | 29.50 | 24.72 | 0.199737E+09 | 120.45 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.522209E+10 | 2884.25 | 01-AUG-20:00 | 29.00 | 27.47 | 0.194932E+09 | 120.45 | 15-AUG-23:19 | 26.00 | 26.00 |
September | 0.495700E+10 | 2476.90 | 08-SEP-20:00 | 29.00 | 25.99 | 0.187505E+09 | 120.45 | 08-SEP-22:19 | 25.93 | 23.63 |
October | 0.496596E+10 | 2048.84 | 04-OCT-20:00 | 28.00 | 25.05 | 0.188550E+09 | 120.45 | 04-OCT-21:10 | 27.42 | 25.35 |
November | 0.482930E+10 | 2010.96 | 21-NOV-21:00 | 28.00 | 25.20 | 0.183128E+09 | 119.62 | 21-NOV-22:10 | 27.33 | 25.20 |
December | 0.493225E+10 | 1994.08 | 08-DEC-22:00 | 28.10 | 23.77 | 0.187224E+09 | 118.67 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.619624E+11 | 0.228863E+10 | ||||||||
Minimum of Months | 0.459353E+10 | 1994.08 | 27.00 | 22.29 | 0.174693E+09 | 118.67 | 23.42 | 22.22 | ||
Maximum of Months | 0.604401E+10 | 3794.52 | 32.33 | 27.47 | 0.200531E+09 | 120.45 | 32.33 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300237E+10 | 1194.16 | 05-JAN-22:10 | 26.38 | 23.18 | 0.141756E+09 | 88.52 | 05-JAN-22:10 | 26.38 | 23.18 |
February | 0.278468E+10 | 1202.73 | 22-FEB-22:10 | 27.00 | 22.22 | 0.131549E+09 | 89.19 | 22-FEB-22:10 | 27.00 | 22.22 |
March | 0.310357E+10 | 1229.17 | 29-MAR-21:10 | 28.03 | 23.69 | 0.147285E+09 | 91.18 | 29-MAR-21:10 | 28.03 | 23.69 |
April | 0.308068E+10 | 1484.57 | 30-APR-19:10 | 33.02 | 26.80 | 0.145203E+09 | 92.65 | 26-APR-21:30 | 33.02 | 26.80 |
May | 0.334421E+10 | 1741.58 | 06-MAY-17:25 | 32.50 | 26.16 | 0.152559E+09 | 92.65 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.352035E+10 | 1981.77 | 13-JUN-18:03 | 31.80 | 28.00 | 0.150359E+09 | 92.65 | 11-JUN-23:19 | 31.80 | 28.00 |
July | 0.323319E+10 | 1654.49 | 14-JUL-18:03 | 31.45 | 25.13 | 0.151392E+09 | 92.65 | 14-JUL-23:19 | 27.00 | 24.11 |
August | 0.311912E+10 | 1442.37 | 01-AUG-20:00 | 29.00 | 27.47 | 0.147363E+09 | 92.65 | 01-AUG-22:30 | 28.05 | 26.76 |
September | 0.299034E+10 | 1243.40 | 07-SEP-21:10 | 28.97 | 26.76 | 0.141342E+09 | 92.23 | 07-SEP-21:10 | 28.97 | 26.76 |
October | 0.300982E+10 | 1207.64 | 04-OCT-21:10 | 27.42 | 25.35 | 0.142098E+09 | 89.53 | 04-OCT-21:10 | 27.42 | 25.35 |
November | 0.292717E+10 | 1199.77 | 21-NOV-21:20 | 27.83 | 25.24 | 0.137956E+09 | 88.95 | 21-NOV-22:10 | 27.33 | 25.20 |
December | 0.299015E+10 | 1193.74 | 08-DEC-22:10 | 27.92 | 23.84 | 0.141043E+09 | 88.52 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.371056E+11 | 0.172991E+10 | ||||||||
Minimum of Months | 0.278468E+10 | 1193.74 | 26.38 | 22.22 | 0.131549E+09 | 88.52 | 24.07 | 22.22 | ||
Maximum of Months | 0.352035E+10 | 1981.77 | 33.02 | 28.00 | 0.152559E+09 | 92.65 | 33.02 | 28.00 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536015E+11 | 35880.46 | 04-JAN-21:00 | 26.80 | 23.34 | 0.548717E+09 | 381.52 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.491741E+11 | 36107.08 | 22-FEB-21:00 | 27.50 | 22.29 | 0.498814E+09 | 381.50 | 22-FEB-22:30 | 26.80 | 22.14 |
March | 0.547966E+11 | 36466.50 | 29-MAR-20:00 | 28.00 | 23.68 | 0.555176E+09 | 381.50 | 14-MAR-21:30 | 28.00 | 23.68 |
April | 0.532501E+11 | 36743.99 | 28-APR-20:00 | 29.00 | 25.99 | 0.537055E+09 | 381.49 | 26-APR-21:30 | 29.00 | 25.99 |
May | 0.547498E+11 | 37136.89 | 05-MAY-20:00 | 30.00 | 26.30 | 0.554560E+09 | 381.51 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.535549E+11 | 37085.67 | 13-JUN-20:00 | 31.00 | 27.23 | 0.539128E+09 | 381.49 | 07-JUN-21:30 | 31.00 | 27.23 |
July | 0.541200E+11 | 36588.44 | 14-JUL-20:00 | 29.50 | 24.72 | 0.550621E+09 | 381.52 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.538280E+11 | 36458.63 | 01-AUG-20:00 | 29.00 | 27.47 | 0.551647E+09 | 381.51 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.522742E+11 | 36393.24 | 06-SEP-20:00 | 28.50 | 26.55 | 0.533069E+09 | 381.51 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.531601E+11 | 36039.47 | 04-OCT-20:00 | 28.00 | 25.05 | 0.547726E+09 | 381.51 | 30-OCT-21:10 | 23.98 | 23.94 |
November | 0.518276E+11 | 35767.60 | 22-NOV-21:00 | 25.00 | 23.59 | 0.531048E+09 | 381.51 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.533046E+11 | 35776.41 | 08-DEC-21:00 | 28.00 | 24.30 | 0.547620E+09 | 381.52 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.637641E+12 | 0.649518E+10 | ||||||||
Minimum of Months | 0.491741E+11 | 35767.60 | 25.00 | 22.29 | 0.498814E+09 | 381.49 | 21.00 | 17.84 | ||
Maximum of Months | 0.547966E+11 | 37136.89 | 31.00 | 27.47 | 0.555176E+09 | 381.52 | 31.00 | 27.23 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269914E+11 | 13541.11 | 05-JAN-16:03 | 32.17 | 22.74 | 0.108112E+11 | 6462.43 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.245021E+11 | 13074.25 | 03-FEB-16:03 | 33.17 | 23.89 | 0.983217E+10 | 6461.92 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.261177E+11 | 12665.78 | 13-MAR-21:10 | 28.03 | 22.97 | 0.108666E+11 | 6461.87 | 14-MAR-03:20 | 25.37 | 22.91 |
April | 0.246586E+11 | 12400.27 | 19-APR-21:10 | 28.97 | 26.21 | 0.104068E+11 | 6461.86 | 14-APR-22:19 | 28.97 | 26.21 |
May | 0.253287E+11 | 12863.43 | 05-MAY-21:10 | 29.02 | 26.76 | 0.107396E+11 | 6462.53 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.247676E+11 | 12780.85 | 13-JUN-21:10 | 28.97 | 27.36 | 0.104410E+11 | 6461.82 | 20-JUN-03:20 | 24.70 | 24.53 |
July | 0.244857E+11 | 11938.65 | 26-JUL-21:10 | 26.87 | 24.52 | 0.106288E+11 | 6462.61 | 19-JUL-22:10 | 26.87 | 24.52 |
August | 0.243300E+11 | 12252.09 | 14-AUG-21:10 | 28.95 | 27.94 | 0.106010E+11 | 6462.54 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.241047E+11 | 12500.37 | 13-SEP-21:10 | 29.32 | 26.39 | 0.103215E+11 | 6462.47 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.248488E+11 | 12535.42 | 16-OCT-21:10 | 27.02 | 25.86 | 0.106409E+11 | 6461.88 | 23-OCT-22:19 | 24.17 | 23.84 |
November | 0.251216E+11 | 12691.56 | 21-NOV-22:10 | 27.33 | 25.20 | 0.104114E+11 | 6462.49 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.266586E+11 | 13223.53 | 08-DEC-22:10 | 27.92 | 23.84 | 0.107890E+11 | 6462.59 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.301915E+12 | 0.126490E+12 | ||||||||
Minimum of Months | 0.241047E+11 | 11938.65 | 26.87 | 22.74 | 0.983217E+10 | 6461.82 | 21.00 | 17.84 | ||
Maximum of Months | 0.269914E+11 | 13541.11 | 33.17 | 27.94 | 0.108666E+11 | 6462.61 | 28.97 | 26.21 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873130E+11 | 42836.49 | 05-JAN-22:10 | 26.38 | 23.18 | 0.316036E+11 | 19185.79 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.804136E+11 | 42440.69 | 22-FEB-22:10 | 27.00 | 22.22 | 0.288516E+11 | 19184.76 | 21-FEB-00:20 | 27.00 | 22.22 |
March | 0.884575E+11 | 42254.46 | 29-MAR-21:10 | 28.03 | 23.69 | 0.319750E+11 | 19184.75 | 02-MAR-23:19 | 28.03 | 23.69 |
April | 0.859541E+11 | 43467.00 | 28-APR-21:10 | 28.43 | 25.81 | 0.308486E+11 | 19184.98 | 28-APR-03:20 | 28.43 | 25.81 |
May | 0.901167E+11 | 46363.65 | 05-MAY-21:10 | 29.02 | 26.76 | 0.319692E+11 | 19185.91 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.899148E+11 | 48195.59 | 13-JUN-21:10 | 28.97 | 27.36 | 0.311917E+11 | 19184.97 | 20-JUN-03:20 | 24.70 | 24.53 |
July | 0.881823E+11 | 44402.33 | 14-JUL-21:10 | 28.23 | 24.46 | 0.317741E+11 | 19186.01 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.865498E+11 | 43402.37 | 01-AUG-21:10 | 28.85 | 27.27 | 0.315542E+11 | 19185.92 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.839752E+11 | 42325.53 | 13-SEP-21:10 | 29.32 | 26.39 | 0.305383E+11 | 19184.97 | 08-SEP-03:20 | 29.32 | 26.39 |
October | 0.852860E+11 | 41259.37 | 04-OCT-21:10 | 27.42 | 25.35 | 0.312905E+11 | 19184.67 | 10-OCT-22:19 | 24.57 | 23.94 |
November | 0.839547E+11 | 41802.94 | 21-NOV-22:10 | 27.33 | 25.20 | 0.305081E+11 | 19185.86 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.868456E+11 | 42757.65 | 08-DEC-22:10 | 27.92 | 23.84 | 0.315387E+11 | 19185.98 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.103696E+13 | 0.373644E+12 | ||||||||
Minimum of Months | 0.804136E+11 | 41259.37 | 26.38 | 22.22 | 0.288516E+11 | 19184.67 | 21.00 | 17.84 | ||
Maximum of Months | 0.901167E+11 | 48195.59 | 29.32 | 27.36 | 0.319750E+11 | 19186.01 | 29.32 | 26.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268058E+10 | 3097.92 | 19-JAN-16:02 | 30.50 | 23.70 | 0.100620E+09 | 72.34 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.261400E+10 | 3101.23 | 15-FEB-16:02 | 30.08 | 24.90 | 90718980.53 | 56.70 | 22-FEB-22:10 | 27.00 | 22.22 |
March | 0.295670E+10 | 3109.10 | 16-MAR-15:02 | 31.08 | 25.10 | 99351582.17 | 56.70 | 27-MAR-21:10 | 27.10 | 24.88 |
April | 0.286378E+10 | 3130.16 | 17-APR-15:02 | 33.35 | 26.60 | 95943914.93 | 56.70 | 05-APR-21:10 | 33.35 | 26.60 |
May | 0.282899E+10 | 3129.80 | 31-MAY-15:02 | 34.33 | 27.03 | 99378009.54 | 80.13 | 10-MAY-21:00 | 34.33 | 27.03 |
June | 0.283738E+10 | 3135.83 | 07-JUN-15:02 | 34.10 | 27.25 | 96297490.50 | 61.12 | 25-JUN-21:00 | 23.10 | 22.86 |
July | 0.253450E+10 | 3055.48 | 14-JUL-15:02 | 32.52 | 24.86 | 99456130.49 | 81.68 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.252466E+10 | 3045.29 | 27-AUG-15:02 | 32.17 | 25.99 | 99375883.50 | 79.10 | 23-AUG-21:00 | 32.17 | 25.99 |
September | 0.249763E+10 | 3139.16 | 12-SEP-15:02 | 32.83 | 26.95 | 96245714.48 | 76.65 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.246837E+10 | 3124.37 | 28-OCT-15:02 | 30.35 | 26.36 | 99556778.73 | 68.64 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.248108E+10 | 3098.54 | 29-NOV-16:02 | 29.17 | 24.47 | 97245574.22 | 77.33 | 24-NOV-22:10 | 29.17 | 24.47 |
December | 0.256793E+10 | 3109.02 | 29-DEC-16:02 | 29.83 | 24.49 | 0.101031E+09 | 78.57 | 26-DEC-22:30 | 29.83 | 24.49 |
Annual Sum or Average | 0.318556E+11 | 0.117522E+10 | ||||||||
Minimum of Months | 0.246837E+10 | 3045.29 | 29.17 | 23.70 | 90718980.53 | 56.70 | 22.50 | 18.29 | ||
Maximum of Months | 0.295670E+10 | 3139.16 | 34.33 | 27.25 | 0.101031E+09 | 81.68 | 34.33 | 27.03 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234428E+10 | 3134.43 | 30-JAN-16:02 | 29.92 | 24.51 | 0.100353E+09 | 71.17 | 23-JAN-22:00 | 29.92 | 24.51 |
February | 0.236615E+10 | 3149.62 | 13-FEB-16:02 | 33.25 | 25.80 | 90577551.12 | 56.70 | 16-FEB-01:39 | 26.03 | 23.68 |
March | 0.283039E+10 | 3147.95 | 15-MAR-15:02 | 32.08 | 24.14 | 99324727.71 | 56.70 | 20-MAR-21:10 | 27.90 | 23.14 |
April | 0.288008E+10 | 3164.91 | 07-APR-15:02 | 32.53 | 26.07 | 95948865.67 | 56.70 | 03-APR-21:10 | 32.53 | 26.07 |
May | 0.292368E+10 | 3157.51 | 04-MAY-15:02 | 32.83 | 27.07 | 99401954.70 | 80.61 | 10-MAY-21:00 | 24.20 | 24.20 |
June | 0.301022E+10 | 3162.61 | 10-JUN-18:02 | 30.78 | 27.22 | 96333275.16 | 61.85 | 25-JUN-21:00 | 23.10 | 22.86 |
July | 0.264033E+10 | 3167.52 | 14-JUL-18:02 | 31.45 | 25.13 | 99503141.92 | 82.74 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.257290E+10 | 3078.14 | 27-AUG-15:02 | 32.17 | 25.99 | 99392699.74 | 79.37 | 23-AUG-21:00 | 32.17 | 25.99 |
September | 0.246524E+10 | 3168.59 | 13-SEP-15:02 | 32.92 | 26.53 | 96236343.75 | 76.47 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.234449E+10 | 3071.77 | 04-OCT-15:02 | 32.33 | 26.11 | 99509937.42 | 68.24 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.224875E+10 | 3127.48 | 20-NOV-16:02 | 30.83 | 24.62 | 97091059.45 | 75.96 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.222915E+10 | 3121.27 | 31-DEC-16:02 | 31.00 | 24.10 | 0.100701E+09 | 76.09 | 26-DEC-22:30 | 31.00 | 24.10 |
Annual Sum or Average | 0.308557E+11 | 0.117437E+10 | ||||||||
Minimum of Months | 0.222915E+10 | 3071.77 | 29.92 | 24.10 | 90577551.12 | 56.70 | 22.87 | 20.57 | ||
Maximum of Months | 0.301022E+10 | 3168.59 | 33.25 | 27.22 | 0.100701E+09 | 82.74 | 32.53 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101484E+10 | 630.04 | 05-JAN-14:30 | 33.80 | 23.21 | 0.00 | 0.00 | 01-JAN-00:10 | 33.80 | 23.21 |
February | 0.908784E+09 | 568.21 | 04-FEB-14:30 | 32.50 | 24.95 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 24.95 |
March | 0.895821E+09 | 461.78 | 09-MAR-14:00 | 35.00 | 24.83 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 24.83 |
April | 0.797712E+09 | 440.39 | 01-APR-20:20 | 29.33 | 26.00 | 0.00 | 0.00 | 01-APR-00:10 | 29.33 | 26.00 |
May | 0.819596E+09 | 456.71 | 06-MAY-20:10 | 30.83 | 25.83 | 0.00 | 0.00 | 01-MAY-00:10 | 30.83 | 25.83 |
June | 0.792546E+09 | 442.82 | 13-JUN-20:20 | 30.33 | 27.35 | 0.00 | 0.00 | 01-JUN-00:10 | 30.33 | 27.35 |
July | 0.756985E+09 | 420.17 | 15-JUL-20:10 | 28.92 | 25.01 | 0.00 | 0.00 | 01-JUL-00:10 | 28.92 | 25.01 |
August | 0.741972E+09 | 414.50 | 14-AUG-20:40 | 29.00 | 28.18 | 0.00 | 0.00 | 01-AUG-00:10 | 29.00 | 28.18 |
September | 0.769093E+09 | 428.38 | 27-SEP-20:40 | 28.00 | 25.79 | 0.00 | 0.00 | 01-SEP-00:10 | 28.00 | 25.79 |
October | 0.832003E+09 | 488.03 | 28-OCT-13:00 | 32.90 | 26.70 | 0.00 | 0.00 | 01-OCT-00:10 | 32.90 | 26.70 |
November | 0.907513E+09 | 566.15 | 23-NOV-09:00 | 28.50 | 23.82 | 0.00 | 0.00 | 01-NOV-00:10 | 28.50 | 23.82 |
December | 0.999328E+09 | 631.34 | 07-DEC-13:50 | 32.80 | 23.14 | 0.00 | 0.00 | 01-DEC-00:10 | 32.80 | 23.14 |
Annual Sum or Average | 0.102362E+11 | 0.00 | ||||||||
Minimum of Months | 0.741972E+09 | 414.50 | 28.00 | 23.14 | 0.00 | 0.00 | 28.00 | 23.14 | ||
Maximum of Months | 0.101484E+10 | 631.34 | 35.00 | 28.18 | 0.00 | 0.00 | 35.00 | 28.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.946209E+09 | 1134.29 | 24-JAN-19:02 | 25.75 | 21.45 | 99246525.99 | 67.40 | 23-JAN-22:00 | 25.75 | 21.45 |
February | 0.909530E+09 | 1153.75 | 24-FEB-19:02 | 28.83 | 21.28 | 89739094.29 | 56.69 | 10-FEB-22:10 | 28.83 | 21.28 |
March | 0.105591E+10 | 1145.57 | 04-MAR-09:02 | 29.40 | 20.98 | 98572539.44 | 56.69 | 28-MAR-21:30 | 28.00 | 25.20 |
April | 0.108889E+10 | 1140.43 | 27-APR-18:02 | 30.35 | 24.51 | 95367401.56 | 56.69 | 03-APR-21:30 | 30.35 | 24.51 |
May | 0.119560E+10 | 1151.17 | 27-MAY-18:02 | 30.93 | 25.78 | 98927331.21 | 74.35 | 10-MAY-21:10 | 30.93 | 25.78 |
June | 0.123797E+10 | 1153.66 | 24-JUN-20:11 | 24.00 | 24.00 | 95997215.67 | 58.07 | 25-JUN-21:10 | 23.02 | 22.98 |
July | 0.114507E+10 | 1159.54 | 13-JUL-18:02 | 30.25 | 23.67 | 98957207.64 | 76.51 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.107716E+10 | 1132.36 | 01-AUG-18:02 | 30.75 | 27.05 | 98684071.92 | 73.15 | 23-AUG-21:10 | 23.22 | 23.00 |
September | 0.101083E+10 | 1134.01 | 09-SEP-08:62 | 28.33 | 25.27 | 95448089.36 | 73.39 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.990513E+09 | 1128.64 | 01-OCT-08:62 | 27.25 | 25.59 | 98549215.64 | 66.76 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.940389E+09 | 1139.71 | 23-NOV-09:02 | 28.57 | 23.85 | 96035463.05 | 72.12 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.923675E+09 | 1141.00 | 19-DEC-19:02 | 26.00 | 20.73 | 99507332.77 | 71.51 | 20-DEC-22:10 | 21.83 | 18.17 |
Annual Sum or Average | 0.125217E+11 | 0.116503E+10 | ||||||||
Minimum of Months | 0.909530E+09 | 1128.64 | 24.00 | 20.73 | 89739094.29 | 56.69 | 21.83 | 18.17 | ||
Maximum of Months | 0.123797E+10 | 1159.54 | 30.93 | 27.05 | 99507332.77 | 76.51 | 30.93 | 25.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265721E+10 | 2920.70 | 21-JAN-09:11 | 25.70 | 20.28 | 0.101092E+09 | 72.78 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.261705E+10 | 3037.45 | 24-FEB-09:11 | 26.07 | 19.98 | 91094603.11 | 56.70 | 24-FEB-22:30 | 26.40 | 22.68 |
March | 0.294285E+10 | 2803.98 | 26-MAR-15:02 | 33.90 | 25.32 | 99437063.02 | 56.70 | 20-MAR-21:49 | 33.90 | 25.32 |
April | 0.287408E+10 | 2734.05 | 01-APR-15:02 | 34.87 | 26.77 | 95995870.85 | 56.70 | 26-APR-21:19 | 28.43 | 23.59 |
May | 0.284784E+10 | 2788.64 | 05-MAY-15:02 | 35.93 | 26.31 | 99402827.26 | 78.16 | 10-MAY-21:00 | 24.20 | 24.20 |
June | 0.284301E+10 | 2723.29 | 15-JUN-15:02 | 34.93 | 28.17 | 96343458.17 | 59.99 | 25-JUN-21:10 | 23.02 | 22.98 |
July | 0.252906E+10 | 2680.17 | 15-JUL-15:02 | 33.03 | 25.65 | 99524676.28 | 78.88 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.252605E+10 | 2651.89 | 27-AUG-15:02 | 32.17 | 25.99 | 99449055.32 | 77.44 | 23-AUG-21:00 | 32.17 | 25.99 |
September | 0.251371E+10 | 2684.39 | 05-SEP-15:02 | 32.87 | 25.74 | 96299117.45 | 76.13 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.246677E+10 | 2696.75 | 08-OCT-15:02 | 31.22 | 25.87 | 99632548.67 | 68.87 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.247996E+10 | 2858.51 | 22-NOV-07:41 | 25.67 | 22.37 | 97402223.60 | 77.10 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.254666E+10 | 2913.24 | 27-DEC-09:01 | 26.40 | 20.69 | 0.101474E+09 | 77.41 | 26-DEC-22:30 | 26.40 | 20.69 |
Annual Sum or Average | 0.318443E+11 | 0.117715E+10 | ||||||||
Minimum of Months | 0.246677E+10 | 2651.89 | 25.67 | 19.98 | 91094603.11 | 56.70 | 22.50 | 18.29 | ||
Maximum of Months | 0.294285E+10 | 3037.45 | 35.93 | 28.17 | 0.101474E+09 | 78.88 | 33.90 | 25.99 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231716E+10 | 2840.94 | 21-JAN-09:11 | 25.70 | 20.28 | 0.100861E+09 | 71.65 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.236761E+10 | 2988.44 | 24-FEB-09:11 | 26.07 | 19.98 | 90978073.80 | 56.70 | 05-FEB-02:00 | 26.07 | 19.98 |
March | 0.281449E+10 | 2798.98 | 29-MAR-15:02 | 34.07 | 24.72 | 99426925.45 | 56.70 | 17-MAR-21:10 | 34.07 | 24.72 |
April | 0.289052E+10 | 2750.78 | 12-APR-15:02 | 32.90 | 25.05 | 95996585.30 | 56.70 | 27-APR-21:40 | 28.37 | 24.22 |
May | 0.294292E+10 | 2837.81 | 20-MAY-15:02 | 34.05 | 26.52 | 99415012.65 | 78.80 | 31-MAY-21:00 | 24.10 | 23.85 |
June | 0.301655E+10 | 2847.49 | 13-JUN-15:02 | 35.92 | 28.46 | 96362458.93 | 60.68 | 25-JUN-21:10 | 23.02 | 22.98 |
July | 0.263658E+10 | 2741.63 | 14-JUL-15:02 | 32.52 | 24.86 | 99553017.00 | 79.96 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.257483E+10 | 2685.39 | 01-AUG-15:02 | 32.95 | 27.47 | 99457377.83 | 77.72 | 23-AUG-21:00 | 24.30 | 22.91 |
September | 0.248087E+10 | 2699.89 | 05-SEP-15:02 | 32.87 | 25.74 | 96291872.64 | 75.95 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.234064E+10 | 2668.24 | 04-OCT-15:02 | 32.33 | 26.11 | 99600867.18 | 68.48 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.224421E+10 | 2785.76 | 22-NOV-07:41 | 25.67 | 22.37 | 97277788.19 | 75.75 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.220486E+10 | 2802.64 | 27-DEC-09:01 | 26.40 | 20.69 | 0.101175E+09 | 74.92 | 26-DEC-22:30 | 26.40 | 20.69 |
Annual Sum or Average | 0.308312E+11 | 0.117640E+10 | ||||||||
Minimum of Months | 0.220486E+10 | 2668.24 | 25.67 | 19.98 | 90978073.80 | 56.70 | 22.50 | 18.29 | ||
Maximum of Months | 0.301655E+10 | 2988.44 | 35.92 | 28.46 | 0.101175E+09 | 79.96 | 34.07 | 24.72 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.693024E+10 | 2720.57 | 31-JAN-22:10 | 26.33 | 22.10 | 0.151075E+10 | 929.47 | 31-JAN-22:30 | 26.20 | 22.13 |
February | 0.638925E+10 | 2742.92 | 24-FEB-22:10 | 26.67 | 22.83 | 0.139455E+10 | 937.37 | 24-FEB-22:30 | 26.40 | 22.68 |
March | 0.698886E+10 | 2716.70 | 29-MAR-21:10 | 28.03 | 23.69 | 0.153270E+10 | 927.92 | 21-MAR-21:30 | 28.03 | 23.69 |
April | 0.675135E+10 | 2721.30 | 30-APR-21:10 | 29.10 | 26.16 | 0.147627E+10 | 929.00 | 28-APR-21:30 | 29.10 | 26.16 |
May | 0.705108E+10 | 2978.24 | 06-MAY-20:10 | 30.83 | 25.83 | 0.154104E+10 | 951.80 | 05-MAY-21:10 | 30.83 | 25.83 |
June | 0.700210E+10 | 3429.67 | 13-JUN-20:10 | 30.67 | 27.30 | 0.151947E+10 | 951.83 | 12-JUN-23:19 | 30.67 | 27.30 |
July | 0.688252E+10 | 2682.99 | 27-JUL-21:10 | 26.97 | 24.11 | 0.150237E+10 | 915.54 | 27-JUL-21:30 | 26.90 | 24.09 |
August | 0.678513E+10 | 2703.73 | 14-AUG-21:10 | 28.95 | 27.94 | 0.148759E+10 | 922.48 | 14-AUG-21:40 | 28.80 | 27.23 |
September | 0.656942E+10 | 2681.38 | 08-SEP-21:10 | 27.68 | 24.93 | 0.143576E+10 | 915.35 | 08-SEP-21:30 | 27.05 | 24.38 |
October | 0.676907E+10 | 2665.86 | 04-OCT-21:10 | 27.42 | 25.35 | 0.147736E+10 | 909.64 | 04-OCT-21:30 | 27.25 | 25.42 |
November | 0.666302E+10 | 2720.76 | 22-NOV-22:10 | 25.42 | 23.59 | 0.145152E+10 | 928.74 | 22-NOV-22:30 | 25.05 | 23.51 |
December | 0.690470E+10 | 2746.25 | 08-DEC-22:10 | 27.92 | 23.84 | 0.150427E+10 | 938.29 | 08-DEC-22:30 | 27.55 | 23.96 |
Annual Sum or Average | 0.816868E+11 | 0.178336E+11 | ||||||||
Minimum of Months | 0.638925E+10 | 2665.86 | 25.42 | 22.10 | 0.139455E+10 | 909.64 | 25.05 | 22.13 | ||
Maximum of Months | 0.705108E+10 | 3429.67 | 30.83 | 27.94 | 0.154104E+10 | 951.83 | 30.83 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277940E+10 | 3482.63 | 05-JAN-16:02 | 32.17 | 22.74 | 0.100370E+09 | 71.46 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.269295E+10 | 3457.03 | 22-FEB-16:02 | 34.42 | 21.55 | 90520833.50 | 56.70 | 15-FEB-23:49 | 34.42 | 21.55 |
March | 0.308284E+10 | 3448.70 | 11-MAR-16:02 | 32.33 | 25.59 | 99299185.62 | 56.70 | 27-MAR-23:49 | 27.00 | 24.83 |
April | 0.302010E+10 | 3473.68 | 18-APR-15:02 | 33.75 | 26.72 | 95931930.43 | 56.70 | 08-APR-23:00 | 33.75 | 26.72 |
May | 0.293895E+10 | 3424.43 | 05-MAY-15:02 | 35.93 | 26.31 | 99359982.47 | 81.33 | 10-MAY-21:00 | 24.20 | 24.20 |
June | 0.292592E+10 | 3435.43 | 13-JUN-15:02 | 35.92 | 28.46 | 96274592.41 | 63.38 | 25-JUN-21:00 | 23.10 | 22.86 |
July | 0.262328E+10 | 3411.52 | 04-JUL-18:02 | 27.18 | 24.74 | 99440649.30 | 85.22 | 19-JUL-21:00 | 23.40 | 22.42 |
August | 0.262501E+10 | 3423.26 | 31-AUG-15:02 | 30.88 | 27.01 | 99370858.89 | 81.22 | 23-AUG-21:00 | 30.88 | 27.01 |
September | 0.262094E+10 | 3412.60 | 13-SEP-15:02 | 32.92 | 26.53 | 96267367.87 | 78.54 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.255969E+10 | 3427.94 | 15-OCT-15:02 | 29.48 | 26.03 | 99550895.84 | 71.07 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.256144E+10 | 3402.94 | 10-NOV-16:02 | 29.58 | 25.82 | 97189863.20 | 77.51 | 24-NOV-22:00 | 23.20 | 20.55 |
December | 0.264920E+10 | 3400.12 | 07-DEC-16:02 | 30.50 | 22.94 | 0.100799E+09 | 78.61 | 26-DEC-22:00 | 22.00 | 19.30 |
Annual Sum or Average | 0.330797E+11 | 0.117438E+10 | ||||||||
Minimum of Months | 0.255969E+10 | 3400.12 | 27.18 | 21.55 | 90520833.50 | 56.70 | 22.00 | 18.29 | ||
Maximum of Months | 0.308284E+10 | 3482.63 | 35.93 | 28.46 | 0.100799E+09 | 85.22 | 34.42 | 27.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242431E+10 | 3380.81 | 19-JAN-16:02 | 30.50 | 23.70 | 0.100104E+09 | 70.42 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.243522E+10 | 3416.43 | 07-FEB-16:02 | 30.08 | 24.34 | 90384111.76 | 56.70 | 02-FEB-22:40 | 30.08 | 24.34 |
March | 0.295333E+10 | 3428.72 | 20-MAR-18:02 | 29.87 | 23.66 | 99277055.93 | 56.70 | 29-MAR-23:49 | 27.00 | 24.12 |
April | 0.303752E+10 | 3486.84 | 02-APR-15:02 | 34.75 | 27.18 | 95937059.66 | 56.70 | 08-APR-23:49 | 27.67 | 25.03 |
May | 0.303708E+10 | 3520.28 | 05-MAY-15:02 | 35.93 | 26.31 | 99384631.80 | 81.84 | 10-MAY-21:00 | 24.20 | 24.20 |
June | 0.310456E+10 | 3524.19 | 07-JUN-15:02 | 34.10 | 27.25 | 96318206.84 | 64.20 | 25-JUN-21:00 | 23.10 | 22.86 |
July | 0.273366E+10 | 3436.03 | 15-JUL-18:02 | 31.95 | 25.35 | 99489119.17 | 86.54 | 19-JUL-21:00 | 23.40 | 22.42 |
August | 0.267517E+10 | 3456.00 | 31-AUG-15:02 | 30.88 | 27.01 | 99387820.20 | 81.51 | 23-AUG-21:00 | 30.88 | 27.01 |
September | 0.258695E+10 | 3413.47 | 04-SEP-15:02 | 32.17 | 27.38 | 96259340.90 | 78.34 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.242926E+10 | 3456.67 | 14-OCT-15:02 | 30.85 | 26.82 | 99509368.16 | 70.70 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.231595E+10 | 3419.46 | 06-NOV-16:02 | 29.83 | 24.51 | 97042082.36 | 76.05 | 24-NOV-22:00 | 23.20 | 20.55 |
December | 0.229023E+10 | 3415.61 | 12-DEC-16:02 | 30.50 | 25.51 | 0.100470E+09 | 76.11 | 26-DEC-22:00 | 22.00 | 19.30 |
Annual Sum or Average | 0.320232E+11 | 0.117356E+10 | ||||||||
Minimum of Months | 0.229023E+10 | 3380.81 | 29.83 | 23.66 | 90384111.76 | 56.70 | 22.00 | 18.29 | ||
Maximum of Months | 0.310456E+10 | 3524.19 | 35.93 | 27.38 | 0.100470E+09 | 86.54 | 30.88 | 27.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189141E+10 | 1699.43 | 28-JAN-09:41 | 25.75 | 20.36 | 0.100820E+09 | 72.49 | 23-JAN-22:00 | 25.75 | 20.36 |
February | 0.170749E+10 | 1680.16 | 02-FEB-09:41 | 26.17 | 21.24 | 90742422.77 | 56.70 | 09-FEB-22:40 | 25.13 | 22.87 |
March | 0.173704E+10 | 1613.99 | 30-MAR-15:02 | 31.87 | 24.75 | 99306236.69 | 56.70 | 17-MAR-21:49 | 31.87 | 24.75 |
April | 0.158496E+10 | 1621.42 | 06-APR-15:02 | 33.17 | 26.09 | 95874409.85 | 56.70 | 24-APR-21:30 | 28.30 | 24.73 |
May | 0.161139E+10 | 1623.97 | 07-MAY-15:02 | 33.87 | 27.43 | 99291610.71 | 78.58 | 10-MAY-21:00 | 24.20 | 24.20 |
June | 0.156473E+10 | 1583.30 | 15-JUN-15:02 | 34.93 | 28.17 | 96207584.88 | 60.63 | 25-JUN-21:00 | 23.10 | 22.86 |
July | 0.147010E+10 | 1569.68 | 15-JUL-15:02 | 33.03 | 25.65 | 99354773.56 | 79.87 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.144429E+10 | 1556.77 | 27-AUG-15:02 | 32.17 | 25.99 | 99297329.43 | 77.56 | 23-AUG-21:00 | 32.17 | 25.99 |
September | 0.149310E+10 | 1619.01 | 30-SEP-15:02 | 29.77 | 26.27 | 96226222.05 | 78.50 | 15-SEP-21:10 | 29.77 | 26.27 |
October | 0.158079E+10 | 1621.73 | 27-OCT-15:02 | 29.42 | 26.13 | 99600405.78 | 73.91 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.169920E+10 | 1681.03 | 25-NOV-09:51 | 24.50 | 20.65 | 97388774.37 | 78.93 | 24-NOV-22:00 | 24.50 | 20.65 |
December | 0.184805E+10 | 1669.17 | 27-DEC-09:01 | 26.40 | 20.69 | 0.101315E+09 | 80.19 | 26-DEC-22:00 | 26.40 | 20.69 |
Annual Sum or Average | 0.196325E+11 | 0.117543E+10 | ||||||||
Minimum of Months | 0.144429E+10 | 1556.77 | 24.50 | 20.36 | 90742422.77 | 56.70 | 23.10 | 20.36 | ||
Maximum of Months | 0.189141E+10 | 1699.43 | 34.93 | 28.17 | 0.101315E+09 | 80.19 | 32.17 | 26.27 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459507E+11 | 23439.06 | 03-JAN-22:10 | 26.88 | 23.35 | 0.190727E+11 | 11348.42 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.423568E+11 | 23505.64 | 21-FEB-22:10 | 27.17 | 22.80 | 0.173066E+11 | 11347.31 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.476787E+11 | 24192.36 | 28-MAR-21:10 | 28.00 | 25.10 | 0.192524E+11 | 11347.34 | 03-MAR-23:19 | 28.00 | 25.10 |
April | 0.470479E+11 | 24629.82 | 28-APR-21:10 | 28.43 | 25.81 | 0.186181E+11 | 11347.29 | 14-APR-22:19 | 28.43 | 25.81 |
May | 0.491250E+11 | 25318.41 | 05-MAY-21:10 | 29.02 | 26.76 | 0.192449E+11 | 11348.72 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.486328E+11 | 25885.86 | 12-JUN-21:10 | 29.73 | 26.89 | 0.186969E+11 | 11347.27 | 30-JUN-22:19 | 25.83 | 24.97 |
July | 0.479770E+11 | 25203.68 | 14-JUL-21:10 | 28.23 | 24.46 | 0.191784E+11 | 11348.87 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.471048E+11 | 24750.93 | 01-AUG-21:10 | 28.85 | 27.27 | 0.191908E+11 | 11348.73 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.455405E+11 | 24333.50 | 05-SEP-21:10 | 28.97 | 26.71 | 0.185356E+11 | 11348.57 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.460047E+11 | 23713.32 | 16-OCT-21:10 | 27.02 | 25.86 | 0.190868E+11 | 11347.53 | 30-OCT-21:10 | 23.98 | 23.94 |
November | 0.445323E+11 | 23445.80 | 14-NOV-22:10 | 27.15 | 26.04 | 0.184627E+11 | 11348.59 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.454822E+11 | 23539.75 | 08-DEC-22:10 | 27.92 | 23.84 | 0.190604E+11 | 11348.76 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.557433E+12 | 0.225706E+12 | ||||||||
Minimum of Months | 0.423568E+11 | 23439.06 | 26.88 | 22.80 | 0.173066E+11 | 11347.27 | 21.00 | 17.84 | ||
Maximum of Months | 0.491250E+11 | 25885.86 | 29.73 | 27.27 | 0.192524E+11 | 11348.87 | 28.43 | 25.81 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485918E+11 | 24659.32 | 03-JAN-22:10 | 26.88 | 23.35 | 0.191209E+11 | 11348.43 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.447242E+11 | 24700.87 | 15-FEB-22:10 | 27.00 | 24.52 | 0.173398E+11 | 11347.32 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.503543E+11 | 25402.02 | 28-MAR-21:10 | 28.00 | 25.10 | 0.192875E+11 | 11347.36 | 03-MAR-23:19 | 28.00 | 25.10 |
April | 0.496897E+11 | 25861.92 | 28-APR-21:10 | 28.43 | 25.81 | 0.186470E+11 | 11347.30 | 14-APR-22:19 | 28.43 | 25.81 |
May | 0.519062E+11 | 26534.91 | 05-MAY-21:10 | 29.02 | 26.76 | 0.192718E+11 | 11348.73 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.513256E+11 | 27113.45 | 12-JUN-21:10 | 29.73 | 26.89 | 0.187172E+11 | 11347.29 | 30-JUN-22:19 | 25.83 | 24.97 |
July | 0.508374E+11 | 26487.16 | 14-JUL-21:10 | 28.23 | 24.46 | 0.192165E+11 | 11348.87 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.499777E+11 | 26022.18 | 01-AUG-21:10 | 28.85 | 27.27 | 0.192430E+11 | 11348.73 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.482649E+11 | 25582.80 | 05-SEP-21:10 | 28.97 | 26.71 | 0.185813E+11 | 11348.57 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.488043E+11 | 24941.65 | 16-OCT-21:10 | 27.02 | 25.86 | 0.191405E+11 | 11347.55 | 30-OCT-21:10 | 23.98 | 23.94 |
November | 0.471595E+11 | 24699.51 | 14-NOV-22:10 | 27.15 | 26.04 | 0.185118E+11 | 11348.59 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.481591E+11 | 24711.75 | 08-DEC-22:10 | 27.92 | 23.84 | 0.191142E+11 | 11348.77 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.589795E+12 | 0.226192E+12 | ||||||||
Minimum of Months | 0.447242E+11 | 24659.32 | 26.88 | 23.35 | 0.173398E+11 | 11347.29 | 21.00 | 17.84 | ||
Maximum of Months | 0.519062E+11 | 27113.45 | 29.73 | 27.27 | 0.192875E+11 | 11348.87 | 28.43 | 25.81 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581279E+11 | 29878.74 | 04-JAN-11:50 | 33.00 | 23.69 | 0.187842E+11 | 11319.62 | 28-JAN-18:19 | 26.73 | 22.58 |
February | 0.532661E+11 | 30048.40 | 20-FEB-11:50 | 31.33 | 23.96 | 0.169730E+11 | 11319.58 | 25-FEB-18:19 | 28.57 | 21.30 |
March | 0.591385E+11 | 30448.25 | 19-MAR-10:50 | 33.70 | 23.06 | 0.188009E+11 | 11319.65 | 18-MAR-17:19 | 33.70 | 23.06 |
April | 0.577015E+11 | 30771.43 | 09-APR-10:50 | 33.42 | 26.18 | 0.181952E+11 | 11319.65 | 15-APR-17:19 | 30.50 | 25.05 |
May | 0.592365E+11 | 30952.24 | 07-MAY-10:50 | 33.03 | 26.51 | 0.188012E+11 | 11319.65 | 27-MAY-17:19 | 32.33 | 26.08 |
June | 0.578626E+11 | 30759.87 | 24-JUN-10:50 | 32.20 | 27.56 | 0.182007E+11 | 11319.65 | 17-JUN-17:19 | 32.20 | 27.56 |
July | 0.584169E+11 | 29968.26 | 15-JUL-18:03 | 31.95 | 25.35 | 0.187923E+11 | 11319.62 | 29-JUL-17:19 | 31.17 | 23.90 |
August | 0.580100E+11 | 30395.42 | 27-AUG-10:50 | 32.72 | 27.53 | 0.187962E+11 | 11319.65 | 26-AUG-17:19 | 32.72 | 27.53 |
September | 0.565599E+11 | 30554.98 | 03-SEP-10:50 | 31.78 | 28.02 | 0.181887E+11 | 11319.65 | 02-SEP-17:19 | 31.78 | 28.02 |
October | 0.575179E+11 | 30285.52 | 07-OCT-10:50 | 31.43 | 26.03 | 0.187867E+11 | 11319.65 | 28-OCT-17:19 | 29.50 | 26.26 |
November | 0.560197E+11 | 30011.08 | 23-NOV-11:50 | 30.88 | 24.99 | 0.181789E+11 | 11319.62 | 04-NOV-17:19 | 30.88 | 24.99 |
December | 0.578002E+11 | 29962.78 | 03-DEC-11:50 | 31.00 | 22.63 | 0.187810E+11 | 11319.58 | 02-DEC-18:19 | 31.00 | 22.63 |
Annual Sum or Average | 0.689658E+12 | 0.221279E+12 | ||||||||
Minimum of Months | 0.532661E+11 | 29878.74 | 30.88 | 22.63 | 0.169730E+11 | 11319.58 | 26.73 | 21.30 | ||
Maximum of Months | 0.592365E+11 | 30952.24 | 33.70 | 28.02 | 0.188012E+11 | 11319.65 | 33.70 | 28.02 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147259E+11 | 7567.28 | 05-JAN-15:10 | 33.73 | 23.23 | 0.160913E+10 | 1007.35 | 31-JAN-22:10 | 26.33 | 22.10 |
February | 0.136002E+11 | 7375.53 | 22-FEB-16:03 | 34.42 | 21.55 | 0.147848E+10 | 1007.35 | 24-FEB-22:10 | 26.67 | 22.83 |
March | 0.150539E+11 | 7463.53 | 28-MAR-15:03 | 34.70 | 25.52 | 0.164509E+10 | 1007.37 | 13-MAR-22:19 | 34.70 | 25.52 |
April | 0.147602E+11 | 7334.25 | 01-APR-14:40 | 35.17 | 26.82 | 0.159521E+10 | 1007.37 | 27-APR-22:19 | 28.13 | 24.32 |
May | 0.153255E+11 | 7986.08 | 06-MAY-14:20 | 37.00 | 27.34 | 0.164109E+10 | 1007.37 | 05-MAY-23:19 | 37.00 | 27.34 |
June | 0.152556E+11 | 8143.20 | 13-JUN-15:30 | 35.75 | 28.52 | 0.160674E+10 | 1007.37 | 12-JUN-23:19 | 35.75 | 28.52 |
July | 0.145317E+11 | 6936.90 | 14-JUL-16:20 | 32.73 | 24.97 | 0.160879E+10 | 1007.35 | 14-JUL-21:30 | 27.90 | 24.36 |
August | 0.142993E+11 | 6964.45 | 14-AUG-15:03 | 31.30 | 27.86 | 0.158884E+10 | 1007.36 | 14-AUG-22:19 | 28.47 | 26.67 |
September | 0.140262E+11 | 6727.11 | 12-SEP-15:15 | 32.67 | 26.92 | 0.154961E+10 | 1007.34 | 08-SEP-21:30 | 32.67 | 26.92 |
October | 0.142333E+11 | 6431.47 | 07-OCT-14:00 | 31.80 | 26.27 | 0.157760E+10 | 1007.34 | 16-OCT-21:10 | 27.02 | 25.86 |
November | 0.140530E+11 | 6997.13 | 22-NOV-13:50 | 31.50 | 24.56 | 0.154225E+10 | 1007.34 | 21-NOV-22:30 | 31.50 | 24.56 |
December | 0.145451E+11 | 7545.13 | 08-DEC-14:30 | 33.00 | 23.44 | 0.159107E+10 | 1007.35 | 07-DEC-22:30 | 33.00 | 23.44 |
Annual Sum or Average | 0.174410E+12 | 0.190339E+11 | ||||||||
Minimum of Months | 0.136002E+11 | 6431.47 | 31.30 | 21.55 | 0.147848E+10 | 1007.34 | 26.33 | 22.10 | ||
Maximum of Months | 0.153255E+11 | 8143.20 | 37.00 | 28.52 | 0.164509E+10 | 1007.37 | 37.00 | 28.52 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 127456.29 | 449.62 | 01-JAN-19:05 | 25.08 |
February | 72069.85 | 464.78 | 20-FEB-07:54 | 26.00 |
March | 157293.11 | 269.30 | 04-MAR-09:05 | 29.40 |
April | 126414.75 | 476.62 | 21-APR-08:05 | 26.17 |
May | 330908.82 | 480.30 | 16-MAY-08:05 | 26.17 |
June | 218827.95 | 426.44 | 22-JUN-08:05 | 27.17 |
July | 886770.29 | 493.96 | 18-JUL-08:04 | 24.93 |
August | 420633.39 | 473.70 | 20-AUG-18:04 | 25.00 |
September | 364775.32 | 459.61 | 21-SEP-08:05 | 24.83 |
October | 642766.21 | 469.78 | 02-OCT-08:05 | 27.33 |
November | 156632.42 | 473.80 | 01-NOV-08:05 | 26.17 |
December | 76491.93 | 413.11 | 22-DEC-09:05 | 26.17 |
Annual Sum or Average | 3581040.33 | |||
Minimum of Months | 72069.85 | 269.30 | 24.83 | |
Maximum of Months | 886770.29 | 493.96 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 370117.32 | 466.96 | 03-JAN-09:05 | 29.27 |
February | 231447.29 | 446.55 | 20-FEB-07:54 | 26.00 |
March | 620404.34 | 462.76 | 08-MAR-09:05 | 28.50 |
April | 153855.45 | 477.43 | 21-APR-08:05 | 26.17 |
May | 291760.80 | 481.60 | 26-MAY-08:05 | 27.17 |
June | 84443.99 | 271.77 | 22-JUN-08:05 | 27.17 |
July | 588681.30 | 466.45 | 17-JUL-08:05 | 25.75 |
August | 352842.03 | 493.75 | 20-AUG-18:04 | 25.00 |
September | 562039.64 | 458.21 | 21-SEP-08:05 | 24.83 |
October | 1002111.97 | 487.61 | 18-OCT-08:04 | 26.17 |
November | 640720.85 | 473.26 | 28-NOV-09:05 | 26.55 |
December | 168618.73 | 376.08 | 17-DEC-19:05 | 24.50 |
Annual Sum or Average | 5067043.69 | |||
Minimum of Months | 84443.99 | 271.77 | 24.50 | |
Maximum of Months | 1002111.97 | 493.75 | 29.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90323.81 | 127.85 | 11-JAN-09:05 | 26.62 |
February | 133607.61 | 120.08 | 24-FEB-09:15 | 26.07 |
March | 112444.57 | 231.98 | 13-MAR-08:05 | 27.25 |
April | 50951.50 | 143.70 | 21-APR-08:05 | 26.17 |
May | 86761.62 | 230.90 | 17-MAY-08:05 | 24.00 |
June | 22081.72 | 99.44 | 30-JUN-18:07 | 26.90 |
July | 109631.38 | 189.37 | 12-JUL-08:05 | 25.23 |
August | 120000.78 | 235.29 | 21-AUG-08:05 | 27.33 |
September | 124462.81 | 234.14 | 19-SEP-08:05 | 25.00 |
October | 282591.38 | 235.44 | 02-OCT-08:05 | 27.33 |
November | 101118.10 | 234.98 | 01-NOV-08:05 | 26.17 |
December | 94989.25 | 138.06 | 27-DEC-09:05 | 26.40 |
Annual Sum or Average | 1328964.53 | |||
Minimum of Months | 22081.72 | 99.44 | 24.00 | |
Maximum of Months | 282591.38 | 235.44 | 27.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16601.81 | 193.69 | 10-JAN-07:36 | 25.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 42999.08 | 429.99 | 17-MAY-08:05 | 24.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 68234.44 | 314.07 | 07-JUL-08:05 | 25.25 |
August | 46041.00 | 449.47 | 21-AUG-08:05 | 27.33 |
September | 26807.40 | 160.48 | 19-SEP-08:05 | 25.00 |
October | 21647.65 | 160.13 | 24-OCT-08:05 | 25.67 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 37267.94 | 265.90 | 21-DEC-22:55 | 23.00 |
Annual Sum or Average | 259599.32 | |||
Minimum of Months | 0.00 | 0.00 | 23.00 | |
Maximum of Months | 68234.44 | 449.47 | 27.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12734.31 | 148.57 | 10-JAN-07:36 | 25.00 |
February | 3969.68 | 46.31 | 15-FEB-07:16 | 25.40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 43231.86 | 432.32 | 17-MAY-08:05 | 24.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 58263.37 | 236.42 | 07-JUL-08:05 | 25.25 |
August | 45327.09 | 453.27 | 21-AUG-08:05 | 27.33 |
September | 39230.21 | 239.16 | 19-SEP-08:05 | 25.00 |
October | 51661.65 | 379.04 | 24-OCT-08:05 | 25.67 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 25572.04 | 161.51 | 21-DEC-22:55 | 23.00 |
Annual Sum or Average | 279990.21 | |||
Minimum of Months | 0.00 | 0.00 | 23.00 | |
Maximum of Months | 58263.37 | 453.27 | 27.53 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 192487.80 | 513.04 | 23-JAN-22:54 | 22.50 |
February | 150883.95 | 494.29 | 15-FEB-07:14 | 25.40 |
March | 581560.26 | 514.49 | 16-MAR-08:04 | 27.17 |
April | 473097.21 | 529.64 | 10-APR-08:04 | 28.75 |
May | 494839.75 | 521.90 | 12-MAY-08:04 | 27.33 |
June | 437525.85 | 490.60 | 25-JUN-08:05 | 27.33 |
July | 1149942.86 | 528.59 | 08-JUL-08:04 | 25.17 |
August | 964105.08 | 526.20 | 19-AUG-08:04 | 25.33 |
September | 768982.89 | 527.30 | 16-SEP-08:04 | 26.33 |
October | 976004.26 | 523.27 | 22-OCT-08:04 | 25.67 |
November | 206884.43 | 486.30 | 01-NOV-08:05 | 26.17 |
December | 93980.67 | 404.28 | 22-DEC-09:05 | 26.17 |
Annual Sum or Average | 6490294.99 | |||
Minimum of Months | 93980.67 | 404.28 | 22.50 | |
Maximum of Months | 1149942.86 | 529.64 | 28.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 427188.69 | 533.20 | 13-JAN-09:04 | 27.87 |
February | 259993.37 | 480.63 | 15-FEB-07:14 | 25.40 |
March | 783366.96 | 531.13 | 16-MAR-08:04 | 27.17 |
April | 429441.28 | 531.97 | 10-APR-08:04 | 28.75 |
May | 415737.28 | 525.06 | 12-MAY-08:04 | 27.33 |
June | 261275.50 | 377.45 | 20-JUN-08:05 | 26.33 |
July | 855719.61 | 527.65 | 08-JUL-08:04 | 25.17 |
August | 803228.93 | 529.29 | 19-AUG-08:04 | 25.33 |
September | 841245.21 | 532.78 | 16-SEP-08:04 | 26.33 |
October | 1197928.06 | 533.47 | 22-OCT-08:04 | 25.67 |
November | 749911.65 | 509.10 | 17-NOV-07:24 | 25.15 |
December | 328986.19 | 491.98 | 27-DEC-09:04 | 26.40 |
Annual Sum or Average | 7354022.73 | |||
Minimum of Months | 259993.37 | 377.45 | 25.15 | |
Maximum of Months | 1197928.06 | 533.47 | 28.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3915.98 | 45.69 | 23-JAN-22:56 | 22.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 560.53 | 5.61 | 21-APR-08:05 | 26.17 |
May | 70060.48 | 277.94 | 09-MAY-08:05 | 26.17 |
June | 14732.25 | 79.89 | 01-JUN-08:05 | 26.00 |
July | 126813.15 | 279.22 | 11-JUL-08:05 | 25.58 |
August | 57899.50 | 274.54 | 21-AUG-08:05 | 27.33 |
September | 69682.10 | 278.61 | 19-SEP-08:05 | 25.00 |
October | 34615.28 | 198.35 | 24-OCT-08:05 | 25.67 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 2558.25 | 34.11 | 22-DEC-09:06 | 26.17 |
Annual Sum or Average | 380837.52 | |||
Minimum of Months | 0.00 | 0.00 | 22.50 | |
Maximum of Months | 126813.15 | 279.22 | 27.33 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160421E+11 | 15451.75 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.144845E+11 | 15451.75 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.160915E+11 | 15451.75 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.154982E+11 | 15451.75 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.160699E+11 | 15451.75 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.155692E+11 | 15451.75 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.159988E+11 | 15451.75 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.160977E+11 | 15451.75 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.155043E+11 | 15451.75 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.160359E+11 | 15451.75 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.155569E+11 | 15451.75 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.159988E+11 | 15451.75 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.188948E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.144845E+11 | 15451.75 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.160977E+11 | 15451.75 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743719E+09 | 716.35 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.671510E+09 | 716.35 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.746011E+09 | 716.35 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.718503E+09 | 716.35 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.745008E+09 | 716.35 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.721798E+09 | 716.35 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.741713E+09 | 716.35 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.746298E+09 | 716.35 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.718790E+09 | 716.35 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.743432E+09 | 716.35 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.721225E+09 | 716.35 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.741713E+09 | 716.35 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.875972E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.671510E+09 | 716.35 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.746298E+09 | 716.35 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861229E+09 | 829.54 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.777612E+09 | 829.54 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.863884E+09 | 829.54 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.832029E+09 | 829.54 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.862722E+09 | 829.54 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.835845E+09 | 829.54 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.858907E+09 | 829.54 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.864216E+09 | 829.54 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.832361E+09 | 829.54 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.860897E+09 | 829.54 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.835182E+09 | 829.54 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.858907E+09 | 829.54 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.101438E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.777612E+09 | 829.54 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.864216E+09 | 829.54 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693793E+09 | 668.27 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.626432E+09 | 668.27 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.695932E+09 | 668.27 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.670270E+09 | 668.27 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.694996E+09 | 668.27 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.673344E+09 | 668.27 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.691922E+09 | 668.27 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.696199E+09 | 668.27 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.670538E+09 | 668.27 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.693526E+09 | 668.27 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.672810E+09 | 668.27 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.691922E+09 | 668.27 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.817168E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.626432E+09 | 668.27 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.696199E+09 | 668.27 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351983E+09 | 339.04 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.317809E+09 | 339.04 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.353068E+09 | 339.04 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.340049E+09 | 339.04 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.352593E+09 | 339.04 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.341609E+09 | 339.04 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.351034E+09 | 339.04 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.353204E+09 | 339.04 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.340185E+09 | 339.04 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.351847E+09 | 339.04 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.341337E+09 | 339.04 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.351034E+09 | 339.04 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.414575E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.317809E+09 | 339.04 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.353204E+09 | 339.04 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141986E+10 | 1957.67 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.128277E+10 | 1957.67 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.139789E+10 | 1957.67 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.131550E+10 | 1957.67 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.137292E+10 | 1957.67 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.131151E+10 | 1957.67 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.136507E+10 | 1957.67 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.137275E+10 | 1957.67 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.136467E+10 | 1957.67 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.141448E+10 | 1957.67 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.136418E+10 | 1957.67 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.141559E+10 | 1957.67 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.163972E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.128277E+10 | 1957.67 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.141986E+10 | 1957.67 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.840978E+10 | 8554.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.759636E+10 | 8554.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.843215E+10 | 8554.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.810556E+10 | 8554.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.842189E+10 | 8554.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.814434E+10 | 8554.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.838735E+10 | 8554.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.842932E+10 | 8554.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.814177E+10 | 8554.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.841923E+10 | 8554.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.815319E+10 | 8554.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.838827E+10 | 8554.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.990292E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.759636E+10 | 8554.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.843215E+10 | 8554.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146022E+09 | 132.12 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.131872E+09 | 132.12 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.144861E+09 | 132.12 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.141479E+09 | 132.12 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.145441E+09 | 132.12 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.140357E+09 | 132.12 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.146583E+09 | 132.12 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.144861E+09 | 132.12 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.141518E+09 | 132.12 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.146003E+09 | 132.12 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.140918E+09 | 132.12 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.146602E+09 | 132.12 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.171652E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.131872E+09 | 132.12 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.146602E+09 | 132.12 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.306417E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.275172E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.302357E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.286532E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.296410E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.283807E+10 | 3437.84 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.293516E+10 | 3437.84 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.297375E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.292222E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.304507E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.295598E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.305841E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.353975E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.275172E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.306417E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.306417E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.275172E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.302357E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.286532E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.296410E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.283807E+10 | 3437.84 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.293516E+10 | 3437.84 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.297375E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.292222E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.304507E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.295598E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.305841E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.353975E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.275172E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.306417E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126106E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121504E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125670E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148074E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.160421E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.160915E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.154982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.160699E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.155692E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.155043E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.160359E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.155569E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.188948E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.743719E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95653051.95 | 6339514.27 |
February | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107636E+09 | 572168.60 |
March | 0.199990E+10 | 0.746011E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145210E+09 | 50081.85 |
April | 0.192973E+10 | 0.718503E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166545E+09 | 0.00 |
May | 0.199475E+10 | 0.745008E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170351E+09 | 122293.62 |
June | 0.193394E+10 | 0.721798E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157659E+09 | 107615.74 |
July | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122447E+09 | 130276.64 |
August | 0.199896E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135754E+09 | 63216.11 |
September | 0.192879E+10 | 0.718790E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127026E+09 | 1849.02 |
October | 0.199148E+10 | 0.743432E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112972E+09 | 12450.34 |
November | 0.192552E+10 | 0.721225E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97633714.47 | 430985.28 |
December | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84247457.33 | 6872999.62 |
Annual Sum or Average | 0.234744E+11 | 0.875972E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152313E+10 | 14703451.09 |
Minimum of Months | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84247457.33 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170351E+09 | 6872999.62 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.861229E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42134183.81 | 3136686.21 |
February | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44986993.80 | 359764.76 |
March | 0.231589E+10 | 0.863884E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58950013.07 | 53697.85 |
April | 0.223463E+10 | 0.832029E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66298386.16 | 0.00 |
May | 0.230993E+10 | 0.862722E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67571708.13 | 49302.48 |
June | 0.223950E+10 | 0.835845E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62355367.10 | 71885.97 |
July | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48534128.73 | 56505.01 |
August | 0.231480E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53220298.89 | 26265.53 |
September | 0.223354E+10 | 0.832361E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51103179.45 | 10425.95 |
October | 0.230614E+10 | 0.860897E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46634627.29 | 223.33 |
November | 0.222975E+10 | 0.835182E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41857175.88 | 325804.93 |
December | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37841977.19 | 3546665.70 |
Annual Sum or Average | 0.271834E+11 | 0.101438E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621488E+09 | 7637227.73 |
Minimum of Months | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37841977.19 | 0.00 |
Maximum of Months | 0.231589E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67571708.13 | 3546665.70 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.693793E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101215E+09 | 6390223.49 |
February | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106774E+09 | 717195.98 |
March | 0.489771E+09 | 0.695932E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138647E+09 | 127823.86 |
April | 0.472586E+09 | 0.670270E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150944E+09 | 2055.69 |
May | 0.488511E+09 | 0.694996E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147958E+09 | 122661.25 |
June | 0.473617E+09 | 0.673344E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135278E+09 | 395306.02 |
July | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100658E+09 | 164752.21 |
August | 0.489542E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117265E+09 | 54713.67 |
September | 0.472357E+09 | 0.670538E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115656E+09 | 10665.23 |
October | 0.487709E+09 | 0.693526E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107906E+09 | 625.64 |
November | 0.471555E+09 | 0.672810E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97925994.89 | 700364.42 |
December | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90431558.68 | 6796987.20 |
Annual Sum or Average | 0.574883E+10 | 0.817168E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141066E+10 | 15483374.66 |
Minimum of Months | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90431558.68 | 625.64 |
Maximum of Months | 0.489771E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150944E+09 | 6796987.20 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.351983E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60575635.59 | 3122512.37 |
February | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64082377.60 | 286511.75 |
March | 0.376747E+09 | 0.353068E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82752789.29 | 22961.67 |
April | 0.363528E+09 | 0.340049E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89237715.94 | 282.06 |
May | 0.375778E+09 | 0.352593E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86782143.86 | 67401.06 |
June | 0.364321E+09 | 0.341609E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78902095.31 | 137004.34 |
July | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59990061.16 | 66015.40 |
August | 0.376571E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70057316.56 | 14359.46 |
September | 0.363352E+09 | 0.340185E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69464896.40 | 0.00 |
October | 0.375161E+09 | 0.351847E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65096917.65 | 0.00 |
November | 0.362735E+09 | 0.341337E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59105799.57 | 249784.79 |
December | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54230240.14 | 3171320.11 |
Annual Sum or Average | 0.442217E+10 | 0.414575E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840278E+09 | 7138153.00 |
Minimum of Months | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54230240.14 | 0.00 |
Maximum of Months | 0.376747E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89237715.94 | 3171320.11 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.166363E+09 | 3715483.18 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.182465E+09 | 735485.96 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.231411E+09 | 16334.62 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.252935E+09 | 0.00 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.256542E+09 | 150172.93 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.241219E+09 | 183067.29 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.193658E+09 | 165412.48 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.205177E+09 | 151764.67 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.199892E+09 | 229921.75 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.183016E+09 | 107692.37 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.168361E+09 | 738540.07 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.150025E+09 | 3246108.14 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.243106E+10 | 9439983.46 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.150025E+09 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.256542E+09 | 3715483.18 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.141986E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204995E+09 | 25422737.76 |
February | 0.236489E+11 | 0.128277E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228541E+09 | 3873606.75 |
March | 0.262800E+11 | 0.139789E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314945E+09 | 1160529.43 |
April | 0.253579E+11 | 0.131550E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366364E+09 | 0.00 |
May | 0.262123E+11 | 0.137292E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371076E+09 | 292055.13 |
June | 0.254132E+11 | 0.131151E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347657E+09 | 999283.14 |
July | 0.261570E+11 | 0.136507E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263161E+09 | 542288.99 |
August | 0.262677E+11 | 0.137275E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288250E+09 | 220267.66 |
September | 0.253456E+11 | 0.136467E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272126E+09 | 425382.15 |
October | 0.261693E+11 | 0.141448E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233906E+09 | 336226.05 |
November | 0.253025E+11 | 0.136418E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202470E+09 | 4866525.17 |
December | 0.261570E+11 | 0.141559E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182718E+09 | 31727437.94 |
Annual Sum or Average | 0.308468E+12 | 0.163972E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327621E+10 | 69866340.17 |
Minimum of Months | 0.236489E+11 | 0.128277E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182718E+09 | 0.00 |
Maximum of Months | 0.262800E+11 | 0.141986E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371076E+09 | 31727437.94 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.840978E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639029E+09 | 71475706.09 |
February | 0.702046E+11 | 0.759636E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695357E+09 | 11426126.89 |
March | 0.780153E+11 | 0.843215E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931072E+09 | 3183579.10 |
April | 0.752779E+11 | 0.810556E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105174E+10 | 4506.73 |
May | 0.778146E+11 | 0.842189E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105044E+10 | 838875.36 |
June | 0.754422E+11 | 0.814434E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974560E+09 | 3354813.43 |
July | 0.776503E+11 | 0.838735E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728782E+09 | 1694640.21 |
August | 0.779788E+11 | 0.842932E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810133E+09 | 641679.08 |
September | 0.752414E+11 | 0.814177E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784560E+09 | 1106985.75 |
October | 0.776868E+11 | 0.841923E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693465E+09 | 675423.37 |
November | 0.751137E+11 | 0.815319E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621377E+09 | 13448290.83 |
December | 0.776503E+11 | 0.838827E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573004E+09 | 87716397.29 |
Annual Sum or Average | 0.915726E+12 | 0.990292E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955352E+10 | 0.195567E+09 |
Minimum of Months | 0.702046E+11 | 0.759636E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573004E+09 | 4506.73 |
Maximum of Months | 0.780153E+11 | 0.843215E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105174E+10 | 87716397.29 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82171900.50 | 2273990.20 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90484193.50 | 425372.56 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116574E+09 | 487.04 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127075E+09 | 935.35 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128465E+09 | 78728.51 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121510E+09 | 95819.00 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97640394.78 | 104402.35 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103030E+09 | 68180.52 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100321E+09 | 77329.64 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91246030.60 | 64878.66 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83641403.18 | 542329.43 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73349533.70 | 1617479.10 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121551E+10 | 5349932.36 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73349533.70 | 487.04 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128465E+09 | 2273990.20 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82578201.74 | 2003619.73 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90752707.91 | 331248.61 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116655E+09 | 311.02 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127056E+09 | 947.24 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128400E+09 | 85410.86 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121406E+09 | 107128.29 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97538755.34 | 116893.55 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102983E+09 | 70621.92 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100338E+09 | 74262.28 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91353280.28 | 52471.75 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83880133.20 | 448508.80 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73831318.98 | 1373816.00 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121677E+10 | 4665240.07 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73831318.98 | 311.02 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128400E+09 | 2003619.73 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.146022E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16713434.33 | 1600420.45 |
February | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18743294.71 | 194609.80 |
March | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24641370.31 | 36777.81 |
April | 0.00 | 0.141479E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27750775.96 | 545.63 |
May | 0.00 | 0.145441E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27908876.58 | 7648.49 |
June | 0.00 | 0.140357E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26315396.31 | 21750.26 |
July | 0.00 | 0.146583E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19315645.13 | 5154.77 |
August | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20790731.54 | 30959.93 |
September | 0.00 | 0.141518E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20323053.45 | 14703.67 |
October | 0.00 | 0.146003E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17603650.03 | 19870.32 |
November | 0.00 | 0.140918E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16264207.96 | 277558.45 |
December | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14774166.85 | 1846587.52 |
Annual Sum or Average | 0.00 | 0.171652E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251145E+09 | 4056587.10 |
Minimum of Months | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14774166.85 | 545.63 |
Maximum of Months | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27908876.58 | 1846587.52 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23824365.00 | 474462.58 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25931229.50 | 51113.85 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33212543.11 | 0.00 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35959497.81 | 0.00 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36187885.51 | 8100.55 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34113155.53 | 14087.44 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27611754.78 | 12570.40 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29326967.23 | 3932.17 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28648862.34 | 8851.04 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26288545.99 | 39.23 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24160000.04 | 71599.93 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21424660.97 | 318902.89 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346689E+09 | 963660.09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21424660.97 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36187885.51 | 474462.58 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81790182.38 | 3027416.26 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90070117.84 | 895687.56 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116300E+09 | 1125.58 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126858E+09 | 265.71 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128284E+09 | 62921.20 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121298E+09 | 84151.50 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97384211.87 | 82076.66 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102777E+09 | 64270.04 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100117E+09 | 69488.58 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91022383.87 | 68552.81 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83348565.77 | 647064.16 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72876300.31 | 2145173.34 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121213E+10 | 7148193.39 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72876300.31 | 265.71 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128284E+09 | 3027416.26 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82012491.77 | 2664233.44 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90209674.71 | 732653.29 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116344E+09 | 579.67 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126844E+09 | 274.82 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128242E+09 | 69605.47 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121229E+09 | 97281.71 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97312844.51 | 94740.95 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102745E+09 | 66697.64 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100129E+09 | 67056.05 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91095954.29 | 56482.35 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83519055.22 | 537171.94 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73185158.43 | 1805547.09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121287E+10 | 6192324.42 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73185158.43 | 274.82 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128242E+09 | 2664233.44 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74082301.53 | 6372654.90 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78959118.90 | 828262.28 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107042E+09 | 120799.18 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120966E+09 | 1315.85 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119459E+09 | 73891.94 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108844E+09 | 155081.37 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87495398.73 | 20908.97 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96962589.58 | 7491.95 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94703428.44 | 11546.32 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83729895.31 | 4131.73 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73742588.47 | 864007.19 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65802151.93 | 6695814.93 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111179E+10 | 15155906.61 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65802151.93 | 1315.85 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120966E+09 | 6695814.93 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81296551.10 | 2079167.46 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89717335.30 | 311717.74 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115576E+09 | 0.00 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126044E+09 | 1656.63 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127442E+09 | 86377.28 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120550E+09 | 119665.40 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96656516.92 | 141350.87 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101994E+09 | 97035.66 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99294655.87 | 121715.79 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90237908.76 | 117101.59 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82720340.41 | 576083.05 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72499230.27 | 1480952.45 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120403E+10 | 5132823.93 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72499230.27 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127442E+09 | 2079167.46 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81724798.21 | 1816317.23 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89986540.18 | 221855.12 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115651E+09 | 0.00 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126025E+09 | 1690.23 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127378E+09 | 93159.72 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120434E+09 | 130781.53 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96551636.22 | 155110.38 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101946E+09 | 100102.61 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99308434.63 | 118039.89 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90338197.81 | 104686.94 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82945141.41 | 475201.53 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73023920.15 | 1266335.92 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120531E+10 | 4483281.09 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73023920.15 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127378E+09 | 1816317.23 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41249737.27 | 1308167.60 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45696514.36 | 242295.05 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59125650.30 | 43.84 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64573597.00 | 99.73 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65267473.08 | 31594.94 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61740564.81 | 43135.58 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49509130.56 | 47339.62 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52261463.80 | 35156.18 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50842021.39 | 58396.05 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46110243.72 | 67417.80 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42144709.46 | 370084.86 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36684866.33 | 980255.63 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615206E+09 | 3183986.86 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36684866.33 | 43.84 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65267473.08 | 1308167.60 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.306417E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131917E+09 | 19743212.96 |
February | 0.415303E+11 | 0.275172E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145484E+09 | 3901329.46 |
March | 0.461508E+11 | 0.302357E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193173E+09 | 1242155.07 |
April | 0.445315E+11 | 0.286532E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217991E+09 | 22904.65 |
May | 0.460320E+11 | 0.296410E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219063E+09 | 361423.47 |
June | 0.446286E+11 | 0.283807E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204242E+09 | 1066786.89 |
July | 0.459349E+11 | 0.293516E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145530E+09 | 857508.96 |
August | 0.461292E+11 | 0.297375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161322E+09 | 794414.44 |
September | 0.445099E+11 | 0.292222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157027E+09 | 827648.72 |
October | 0.459565E+11 | 0.304507E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135376E+09 | 1124620.33 |
November | 0.444343E+11 | 0.295598E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125354E+09 | 5289949.03 |
December | 0.459349E+11 | 0.305841E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118143E+09 | 24668190.16 |
Annual Sum or Average | 0.541708E+12 | 0.353975E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195462E+10 | 59900144.14 |
Minimum of Months | 0.415303E+11 | 0.275172E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118143E+09 | 22904.65 |
Maximum of Months | 0.461508E+11 | 0.306417E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219063E+09 | 24668190.16 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.306417E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129823E+09 | 19959633.16 |
February | 0.415303E+11 | 0.275172E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143832E+09 | 3967330.17 |
March | 0.461508E+11 | 0.302357E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191303E+09 | 1245908.59 |
April | 0.445315E+11 | 0.286532E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216434E+09 | 26715.93 |
May | 0.460320E+11 | 0.296410E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217579E+09 | 361595.10 |
June | 0.446286E+11 | 0.283807E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203088E+09 | 1070845.35 |
July | 0.459349E+11 | 0.293516E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143476E+09 | 864715.99 |
August | 0.461292E+11 | 0.297375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158805E+09 | 861807.61 |
September | 0.445099E+11 | 0.292222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154772E+09 | 841724.61 |
October | 0.459565E+11 | 0.304507E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132792E+09 | 1161290.31 |
November | 0.444343E+11 | 0.295598E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123096E+09 | 5383449.30 |
December | 0.459349E+11 | 0.305841E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115834E+09 | 24849046.14 |
Annual Sum or Average | 0.541708E+12 | 0.353975E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193083E+10 | 60594062.27 |
Minimum of Months | 0.415303E+11 | 0.275172E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115834E+09 | 26715.93 |
Maximum of Months | 0.461508E+11 | 0.306417E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217579E+09 | 24849046.14 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.115921E+09 | 11094464.40 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.134657E+09 | 2551018.27 |
March | 0.410691E+10 | 0.126106E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.177835E+09 | 346679.88 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.201823E+09 | 16811.51 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.202864E+09 | 247759.65 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.190519E+09 | 515517.36 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.136610E+09 | 405489.67 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.148462E+09 | 484067.10 |
September | 0.396089E+10 | 0.121504E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.144821E+09 | 444762.42 |
October | 0.408962E+10 | 0.125670E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.124239E+09 | 510556.36 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.114267E+09 | 2448537.72 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.100069E+09 | 11862271.30 |
Annual Sum or Average | 0.482060E+11 | 0.148074E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.179209E+10 | 30927935.64 |
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.100069E+09 | 16811.51 |
Maximum of Months | 0.410691E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.202864E+09 | 11862271.30 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121250E+09 | 8808017.40 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133968E+09 | 777183.39 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179265E+09 | 114973.78 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201678E+09 | 3108.24 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204936E+09 | 178776.76 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188796E+09 | 204540.32 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146366E+09 | 123433.38 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164298E+09 | 55404.53 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155931E+09 | 12797.78 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140362E+09 | 1260.33 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123208E+09 | 651192.95 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109327E+09 | 9690478.02 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186938E+10 | 20621166.88 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109327E+09 | 1260.33 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204936E+09 | 9690478.02 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 15451.75 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 15451.75 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 15451.75 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 15451.75 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 15451.75 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 15451.75 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 15451.75 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 15451.75 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 15451.75 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 15451.75 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 15451.75 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 15451.75 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 716.35 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.30 | 04-JAN-13:00 | 42.55 | 24-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 716.35 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.39 | 26-FEB-14:00 | 42.28 | 21-FEB-10:00 |
March | 1169.53 | 01-MAR-00:10 | 716.35 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.68 | 21-MAR-13:00 | 6.37 | 03-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 716.35 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.07 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 1169.53 | 01-MAY-00:10 | 716.35 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.84 | 06-MAY-13:00 | 23.54 | 10-MAY-19:58 |
June | 1169.53 | 01-JUN-00:10 | 716.35 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.81 | 13-JUN-14:00 | 9.30 | 25-JUN-20:00 |
July | 1169.53 | 01-JUL-00:10 | 716.35 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.13 | 01-JUL-13:00 | 11.76 | 19-JUL-18:53 |
August | 1169.53 | 01-AUG-00:10 | 716.35 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.65 | 22-AUG-15:00 | 11.78 | 23-AUG-19:56 |
September | 1169.53 | 01-SEP-00:10 | 716.35 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.11 | 12-SEP-14:00 | 1.13 | 15-SEP-17:00 |
October | 1169.53 | 01-OCT-23:10 | 716.35 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.22 | 04-OCT-14:00 | 4.72 | 09-OCT-18:55 |
November | 1169.53 | 01-NOV-00:10 | 716.35 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 | 18-NOV-13:00 | 27.18 | 25-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 716.35 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 | 08-DEC-14:00 | 45.42 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 | 0.00 | |||||
Maximum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 151.84 | 45.42 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 829.54 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.30 | 04-JAN-13:00 | 19.26 | 23-JAN-06:00 |
February | 1354.32 | 01-FEB-00:10 | 829.54 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.73 | 26-FEB-14:00 | 11.97 | 21-FEB-10:00 |
March | 1354.32 | 01-MAR-00:10 | 829.54 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.98 | 21-MAR-13:00 | 5.29 | 03-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 829.54 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.46 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 1354.32 | 01-MAY-00:10 | 829.54 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 06-MAY-13:00 | 9.09 | 10-MAY-20:00 |
June | 1354.32 | 01-JUN-00:10 | 829.54 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.24 | 18-JUN-14:00 | 3.68 | 25-JUN-20:10 |
July | 1354.32 | 01-JUL-00:10 | 829.54 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 28-JUL-13:00 | 4.54 | 19-JUL-18:53 |
August | 1354.32 | 01-AUG-00:10 | 829.54 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 | 22-AUG-15:00 | 4.55 | 23-AUG-20:00 |
September | 1354.32 | 01-SEP-00:10 | 829.54 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.37 | 10-SEP-14:00 | 2.10 | 15-SEP-21:00 |
October | 1354.32 | 01-OCT-23:10 | 829.54 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 28-OCT-13:00 | 0.24 | 09-OCT-19:00 |
November | 1354.32 | 01-NOV-00:10 | 829.54 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 18-NOV-13:00 | 13.46 | 25-NOV-05:00 |
December | 1354.32 | 01-DEC-00:10 | 829.54 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 | 07-DEC-14:00 | 21.44 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 | 0.00 | |||||
Maximum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 21.44 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 668.27 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.24 | 04-JAN-13:00 | 42.57 | 23-JAN-06:00 |
February | 286.42 | 01-FEB-00:10 | 668.27 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.49 | 21-FEB-14:00 | 30.38 | 21-FEB-10:00 |
March | 286.42 | 01-MAR-00:10 | 668.27 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.88 | 21-MAR-13:00 | 11.48 | 03-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 668.27 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.71 | 01-APR-14:00 | 3.55 | 14-APR-15:52 |
May | 286.42 | 01-MAY-00:10 | 668.27 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.52 | 06-MAY-13:00 | 21.48 | 10-MAY-20:00 |
June | 286.42 | 01-JUN-00:10 | 668.27 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.97 | 13-JUN-14:00 | 10.75 | 25-JUN-21:00 |
July | 286.42 | 01-JUL-00:10 | 668.27 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.48 | 01-JUL-13:00 | 10.73 | 19-JUL-19:00 |
August | 286.42 | 01-AUG-00:10 | 668.27 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.84 | 22-AUG-15:00 | 9.96 | 23-AUG-20:00 |
September | 286.42 | 01-SEP-00:10 | 668.27 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.31 | 12-SEP-14:00 | 3.03 | 15-SEP-21:00 |
October | 286.42 | 01-OCT-23:10 | 668.27 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.19 | 28-OCT-13:00 | 0.80 | 09-OCT-19:00 |
November | 286.42 | 01-NOV-00:10 | 668.27 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.73 | 18-NOV-13:00 | 31.30 | 25-NOV-05:00 |
December | 286.42 | 01-DEC-00:10 | 668.27 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.48 | 07-DEC-14:00 | 48.13 | 21-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 97.48 | 0.80 | |||||
Maximum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 138.52 | 48.13 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 339.04 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.73 | 04-JAN-13:00 | 23.04 | 23-JAN-06:00 |
February | 220.32 | 01-FEB-00:10 | 339.04 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 | 21-FEB-14:00 | 16.50 | 21-FEB-10:00 |
March | 220.32 | 01-MAR-00:10 | 339.04 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 | 21-MAR-13:00 | 5.16 | 03-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 339.04 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 01-APR-14:00 | 0.55 | 14-APR-15:52 |
May | 220.32 | 01-MAY-00:10 | 339.04 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 06-MAY-13:00 | 12.39 | 10-MAY-20:00 |
June | 220.32 | 01-JUN-00:10 | 339.04 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 | 13-JUN-14:00 | 5.28 | 20-JUN-24:00 |
July | 220.32 | 01-JUL-00:10 | 339.04 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 01-JUL-13:00 | 5.80 | 19-JUL-19:00 |
August | 220.32 | 01-AUG-00:10 | 339.04 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.96 | 22-AUG-15:00 | 3.19 | 23-AUG-19:52 |
September | 220.32 | 01-SEP-00:10 | 339.04 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.01 | 12-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 220.32 | 01-OCT-23:10 | 339.04 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.74 | 28-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 220.32 | 01-NOV-00:10 | 339.04 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 | 18-NOV-13:00 | 16.70 | 25-NOV-05:00 |
December | 220.32 | 01-DEC-00:10 | 339.04 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.03 | 07-DEC-14:00 | 26.32 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 0.00 | |||||
Maximum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 26.32 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 174.57 | 04-JAN-13:00 | 57.81 | 24-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 195.48 | 26-FEB-15:00 | 41.04 | 21-FEB-10:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 205.12 | 19-MAR-14:00 | 5.90 | 14-MAR-22:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 192.23 | 02-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 216.57 | 06-MAY-13:00 | 29.33 | 10-MAY-19:56 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 203.66 | 18-JUN-14:00 | 14.67 | 25-JUN-21:00 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 161.66 | 15-JUL-16:00 | 14.65 | 19-JUL-18:53 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 180.02 | 27-AUG-14:00 | 14.68 | 23-AUG-19:54 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 180.04 | 10-SEP-14:00 | 14.69 | 16-SEP-20:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 160.70 | 28-OCT-13:00 | 12.57 | 30-OCT-17:08 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 179.75 | 18-NOV-13:00 | 19.11 | 25-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 160.01 | 08-DEC-14:00 | 66.78 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 160.01 | 0.00 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 216.57 | 66.78 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1957.67 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.68 | 04-JAN-13:00 | 126.89 | 23-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1957.67 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.99 | 26-FEB-14:00 | 76.00 | 21-FEB-10:00 |
March | 15368.40 | 01-MAR-00:10 | 1957.67 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.76 | 21-MAR-13:00 | 48.63 | 03-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1957.67 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.94 | 09-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 15368.40 | 01-MAY-00:10 | 1957.67 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.69 | 06-MAY-13:00 | 52.02 | 10-MAY-19:56 |
June | 15368.40 | 01-JUN-00:10 | 1957.67 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.73 | 16-JUN-13:00 | 25.92 | 25-JUN-21:00 |
July | 15368.40 | 01-JUL-00:10 | 1957.67 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.58 | 28-JUL-13:00 | 25.98 | 19-JUL-18:55 |
August | 15368.40 | 01-AUG-00:10 | 1957.67 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.13 | 22-AUG-15:00 | 26.02 | 23-AUG-19:56 |
September | 15368.40 | 01-SEP-00:10 | 1957.67 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.22 | 06-SEP-14:00 | 24.58 | 15-SEP-21:10 |
October | 15368.40 | 01-OCT-23:10 | 1957.67 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.98 | 04-OCT-14:00 | 23.15 | 23-OCT-24:00 |
November | 15368.40 | 01-NOV-00:10 | 1957.67 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.44 | 18-NOV-13:00 | 97.89 | 25-NOV-05:00 |
December | 15368.40 | 01-DEC-00:10 | 1957.67 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.51 | 08-DEC-14:00 | 143.49 | 21-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 225.51 | 0.00 | |||||
Maximum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 335.69 | 143.49 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 8554.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 770.79 | 04-JAN-13:00 | 365.93 | 23-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 8554.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 844.74 | 26-FEB-14:00 | 207.56 | 02-FEB-06:55 |
March | 45622.98 | 01-MAR-00:10 | 8554.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 941.82 | 21-MAR-13:00 | 134.36 | 03-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 8554.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 863.97 | 01-APR-14:00 | 8.29 | 14-APR-15:52 |
May | 45622.98 | 01-MAY-00:10 | 8554.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 984.47 | 06-MAY-13:00 | 148.68 | 10-MAY-19:56 |
June | 45622.98 | 01-JUN-00:10 | 8554.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 890.67 | 16-JUN-13:00 | 74.28 | 25-JUN-21:00 |
July | 45622.98 | 01-JUL-00:10 | 8554.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.12 | 28-JUL-13:00 | 74.27 | 19-JUL-18:55 |
August | 45622.98 | 01-AUG-00:10 | 8554.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 809.39 | 22-AUG-15:00 | 74.40 | 23-AUG-19:56 |
September | 45622.98 | 01-SEP-00:10 | 8554.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 788.02 | 12-SEP-14:00 | 70.10 | 15-SEP-21:00 |
October | 45622.98 | 01-OCT-23:10 | 8554.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 716.50 | 04-OCT-14:00 | 54.59 | 23-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 8554.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 775.90 | 18-NOV-13:00 | 275.46 | 25-NOV-05:00 |
December | 45622.98 | 01-DEC-00:10 | 8554.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.47 | 07-DEC-14:00 | 410.43 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 687.47 | 8.29 | |||||
Maximum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 984.47 | 410.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 | 03-JAN-16:10 | 29.73 | 24-JAN-09:40 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.88 | 22-FEB-16:10 | 14.89 | 01-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 | 19-MAR-15:10 | 1.51 | 03-MAR-06:30 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 4.52 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 | 06-MAY-15:10 | 12.15 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 | 13-JUN-15:10 | 10.65 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 | 15-JUL-16:00 | 10.89 | 19-JUL-20:40 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 13-AUG-15:10 | 9.89 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 | 04-SEP-16:00 | 8.05 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 04-OCT-15:10 | 4.98 | 30-OCT-17:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.68 | 18-NOV-13:00 | 13.36 | 25-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 13-DEC-16:10 | 29.18 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 1.51 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 | 29.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 | 03-JAN-16:08 | 26.58 | 24-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 | 22-FEB-16:10 | 13.61 | 02-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 | 19-MAR-15:10 | 1.06 | 03-MAR-06:30 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 4.55 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.64 | 06-MAY-15:10 | 12.50 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.18 | 13-JUN-15:10 | 11.48 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 15-JUL-16:00 | 11.87 | 19-JUL-20:40 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 13-AUG-15:10 | 10.12 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.03 | 04-SEP-16:00 | 7.88 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 | 04-OCT-15:10 | 4.46 | 30-OCT-17:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 18-NOV-13:00 | 11.84 | 25-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 13-DEC-16:10 | 27.94 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 1.06 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 100.64 | 27.94 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 132.12 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 | 04-JAN-13:00 | 9.05 | 23-JAN-06:00 |
February | 0.00 | 01-FEB-00:10 | 132.12 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 26-FEB-14:00 | 5.94 | 21-FEB-10:00 |
March | 0.00 | 01-MAR-00:10 | 132.12 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 21-MAR-13:00 | 2.63 | 03-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 132.12 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 01-APR-14:00 | 0.91 | 14-APR-15:52 |
May | 0.00 | 01-MAY-00:10 | 132.12 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | 06-MAY-13:00 | 2.62 | 10-MAY-19:52 |
June | 0.00 | 01-JUN-00:10 | 132.12 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 13-JUN-14:00 | 0.72 | 25-JUN-23:00 |
July | 0.00 | 01-JUL-00:10 | 132.12 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 | 15-JUL-16:00 | 0.72 | 19-JUL-18:52 |
August | 0.00 | 01-AUG-00:10 | 132.12 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 13-AUG-13:00 | 2.63 | 20-AUG-11:00 |
September | 0.00 | 01-SEP-00:10 | 132.12 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 12-SEP-14:00 | 0.91 | 19-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 132.12 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 | 04-OCT-14:00 | 1.57 | 23-OCT-05:00 |
November | 0.00 | 01-NOV-00:10 | 132.12 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 18-NOV-13:00 | 6.49 | 25-NOV-05:00 |
December | 0.00 | 01-DEC-00:10 | 132.12 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 | 08-DEC-14:00 | 10.44 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 | 0.72 | |||||
Maximum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | 10.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 | 03-JAN-16:10 | 6.62 | 24-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 22-FEB-16:10 | 3.16 | 02-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 19-MAR-15:08 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 | 06-MAY-15:10 | 2.13 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 | 13-JUN-15:10 | 1.92 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 15-JUL-16:00 | 1.65 | 19-JUL-20:40 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 13-AUG-15:10 | 1.29 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 04-SEP-16:00 | 1.36 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 04-OCT-15:10 | 0.07 | 30-OCT-17:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 18-NOV-13:00 | 2.50 | 25-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 13-DEC-16:10 | 7.52 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 0.00 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 | 7.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 | 03-JAN-16:10 | 38.45 | 24-JAN-09:50 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.06 | 22-FEB-16:10 | 18.75 | 02-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 | 19-MAR-15:10 | 1.86 | 03-MAR-06:30 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 1.85 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 | 06-MAY-15:10 | 10.71 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 | 13-JUN-15:10 | 9.26 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 | 15-JUL-16:00 | 8.26 | 19-JUL-20:40 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 13-AUG-15:10 | 8.45 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 | 04-SEP-16:00 | 7.55 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 04-OCT-15:10 | 5.13 | 30-OCT-17:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.68 | 18-NOV-13:00 | 17.83 | 25-NOV-07:30 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 13-DEC-16:10 | 31.83 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 1.85 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 | 38.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 | 03-JAN-16:08 | 35.32 | 24-JAN-09:30 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.06 | 22-FEB-16:10 | 17.65 | 24-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 | 19-MAR-15:10 | 1.43 | 03-MAR-06:30 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 1.90 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 06-MAY-15:10 | 11.06 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.18 | 13-JUN-15:10 | 10.11 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 15-JUL-16:00 | 9.28 | 19-JUL-20:40 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.26 | 13-AUG-15:10 | 8.69 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.03 | 04-SEP-16:00 | 7.38 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 04-OCT-15:10 | 4.62 | 30-OCT-17:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.68 | 18-NOV-13:00 | 16.22 | 25-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 13-DEC-16:08 | 30.38 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 1.43 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 35.32 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.80 | 04-JAN-13:00 | 37.15 | 23-JAN-06:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.42 | 21-FEB-14:00 | 24.60 | 21-FEB-10:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.04 | 21-MAR-13:00 | 10.55 | 03-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 01-APR-14:00 | 2.26 | 14-APR-15:52 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.84 | 06-MAY-13:00 | 15.10 | 10-MAY-19:52 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.86 | 24-JUN-14:00 | 6.62 | 20-JUN-24:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.87 | 15-JUL-16:00 | 2.91 | 19-JUL-18:52 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.40 | 22-AUG-15:00 | 3.74 | 20-AUG-11:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.90 | 12-SEP-14:00 | 1.83 | 15-SEP-21:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.30 | 28-OCT-13:00 | 1.28 | 23-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 | 18-NOV-13:00 | 27.11 | 25-NOV-05:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 | 07-DEC-14:00 | 40.06 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 | 1.28 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.84 | 40.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 | 03-JAN-16:10 | 30.54 | 24-JAN-09:50 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.40 | 22-FEB-16:10 | 12.55 | 01-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.28 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.98 | 01-APR-15:10 | 6.18 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 | 06-MAY-15:10 | 12.19 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.81 | 13-JUN-15:10 | 13.24 | 25-JUN-21:50 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.66 | 15-JUL-16:00 | 14.09 | 19-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.90 | 13-AUG-15:10 | 11.39 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 | 04-SEP-16:00 | 10.27 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 04-OCT-15:10 | 7.07 | 09-OCT-20:40 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.30 | 18-NOV-13:00 | 14.40 | 25-NOV-22:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.71 | 13-DEC-16:10 | 26.27 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 70.71 | 0.00 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 | 30.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 | 03-JAN-16:10 | 26.06 | 24-JAN-09:50 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.66 | 22-FEB-16:10 | 11.10 | 02-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 | 01-APR-15:10 | 6.22 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.08 | 06-MAY-15:10 | 12.52 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.92 | 12-JUN-15:10 | 14.23 | 25-JUN-21:50 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 15-JUL-16:00 | 15.23 | 19-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 13-AUG-15:10 | 11.63 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.65 | 04-SEP-16:00 | 10.08 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 04-OCT-15:10 | 6.49 | 30-OCT-17:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.30 | 18-NOV-13:00 | 12.84 | 25-NOV-22:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 13-DEC-16:10 | 25.10 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 0.00 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.08 | 26.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.78 | 03-JAN-16:10 | 18.86 | 24-JAN-09:50 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.55 | 22-FEB-16:10 | 7.39 | 02-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 19-MAR-15:10 | 0.22 | 03-MAR-06:30 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 01-APR-15:10 | 0.73 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.29 | 06-MAY-15:10 | 5.39 | 10-MAY-20:10 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.01 | 13-JUN-15:10 | 5.06 | 25-JUN-21:50 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 | 15-JUL-16:00 | 4.84 | 19-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.88 | 13-AUG-15:10 | 4.49 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 | 04-SEP-16:00 | 5.23 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.53 | 04-OCT-15:10 | 3.90 | 30-OCT-20:40 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 18-NOV-13:00 | 8.47 | 25-NOV-22:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 13-DEC-16:10 | 14.53 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 0.22 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.29 | 18.86 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.21 | 04-JAN-13:00 | 91.39 | 23-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.33 | 28-FEB-14:00 | 53.76 | 02-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.10 | 21-MAR-13:00 | 35.07 | 03-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.36 | 01-APR-14:00 | 16.46 | 14-APR-15:52 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 06-MAY-13:00 | 35.05 | 10-MAY-19:56 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 13-JUN-14:00 | 18.34 | 27-JUN-05:10 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.63 | 28-JUL-13:00 | 18.35 | 19-JUL-18:55 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.60 | 10-AUG-14:00 | 18.38 | 23-AUG-19:56 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.47 | 12-SEP-14:00 | 19.96 | 19-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.90 | 04-OCT-14:00 | 26.60 | 23-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.65 | 18-NOV-13:00 | 68.89 | 25-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.59 | 07-DEC-15:00 | 103.37 | 21-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 151.63 | 16.46 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 103.37 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.42 | 04-JAN-13:00 | 91.39 | 23-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.28 | 28-FEB-14:00 | 53.76 | 02-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.10 | 21-MAR-13:00 | 35.07 | 03-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.36 | 01-APR-14:00 | 18.71 | 14-APR-15:52 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 06-MAY-13:00 | 35.05 | 10-MAY-19:56 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 13-JUN-14:00 | 18.34 | 27-JUN-05:23 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.14 | 28-JUL-13:00 | 18.35 | 19-JUL-18:55 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.50 | 10-AUG-14:00 | 19.39 | 20-AUG-11:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.33 | 12-SEP-14:00 | 19.96 | 19-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.81 | 04-OCT-14:00 | 26.61 | 23-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.46 | 18-NOV-13:00 | 68.90 | 25-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.08 | 07-DEC-15:00 | 103.61 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 149.14 | 18.34 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 103.61 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 143.79 | 04-JAN-13:00 | 77.10 | 24-JAN-09:00 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 156.57 | 26-FEB-14:00 | 57.32 | 21-FEB-10:00 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 174.72 | 21-MAR-13:00 | 27.92 | 03-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 162.49 | 01-APR-14:00 | 17.86 | 14-APR-15:57 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 191.43 | 06-MAY-13:00 | 31.32 | 10-MAY-20:00 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 169.77 | 13-JUN-14:00 | 16.38 | 27-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 130.74 | 15-JUL-16:00 | 16.38 | 19-JUL-18:57 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 142.24 | 22-AUG-15:00 | 31.24 | 20-AUG-11:00 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 142.23 | 12-SEP-14:00 | 16.34 | 15-SEP-23:00 |
October | 2401.70 | 01-OCT-23:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 128.41 | 04-OCT-14:00 | 18.15 | 23-OCT-05:40 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 146.52 | 18-NOV-13:00 | 51.41 | 25-NOV-06:20 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 128.16 | 08-DEC-14:00 | 89.61 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 128.16 | 16.34 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 191.43 | 89.61 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.52 | 04-JAN-13:00 | 55.02 | 23-JAN-06:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.06 | 26-FEB-14:00 | 46.19 | 21-FEB-10:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.82 | 21-MAR-13:00 | 13.51 | 03-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.87 | 01-APR-14:00 | 5.41 | 14-APR-15:52 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.17 | 06-MAY-13:00 | 30.73 | 10-MAY-19:54 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 | 13-JUN-14:00 | 11.08 | 20-JUN-24:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.44 | 28-JUL-13:00 | 13.46 | 19-JUL-18:52 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.53 | 22-AUG-15:00 | 11.76 | 23-AUG-19:52 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.04 | 12-SEP-14:00 | 3.71 | 15-SEP-17:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.27 | 04-OCT-14:00 | 1.60 | 09-OCT-18:53 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.19 | 18-NOV-13:00 | 40.10 | 25-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 | 08-DEC-14:00 | 63.09 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 | 1.60 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.17 | 63.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21871.23 | 06-JAN-22:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21859.79 | 24-FEB-22:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21700.43 | 01-MAR-22:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21795.56 | 28-APR-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22101.67 | 05-MAY-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23778.63 | 15-JUN-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22079.49 | 28-JUL-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22103.65 | 15-AUG-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22044.54 | 08-SEP-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21770.31 | 05-OCT-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21968.16 | 22-NOV-22:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22017.79 | 08-DEC-22:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21700.43 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23778.63 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4179.67 | 05-JAN-14:30 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 110.83 | 0.00 |
February | 3780.58 | 03-FEB-15:10 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 | 0.00 |
March | 3325.07 | 13-MAR-18:15 | 1819.27 | 1273.52 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 72.32 | 0.00 |
April | 3202.72 | 01-APR-17:13 | 2339.06 | 1432.71 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 0.00 |
May | 3461.01 | 05-MAY-19:10 | 909.64 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 78.81 | 0.00 |
June | 3481.72 | 12-JUN-19:10 | 909.64 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 81.80 | 0.00 |
July | 3096.30 | 14-JUL-19:30 | 909.64 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 67.02 | 0.00 |
August | 3075.29 | 14-AUG-19:20 | 909.64 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 | 0.00 |
September | 3321.86 | 13-SEP-19:20 | 909.64 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 | 0.00 |
October | 3296.02 | 28-OCT-13:30 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 90.41 | 0.00 |
November | 3781.17 | 19-NOV-13:00 | 389.84 | 238.78 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 95.36 | 0.00 |
December | 4166.63 | 08-DEC-14:00 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3075.29 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 | 0.00 | |
Maximum of Months | 4179.67 | 2339.06 | 1432.71 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 110.83 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2453.67 | 31-JAN-21:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 0.00 |
February | 2567.32 | 22-FEB-21:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 | 0.00 |
March | 2597.75 | 29-MAR-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 0.00 |
April | 2642.80 | 27-APR-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 0.00 |
May | 2767.86 | 05-MAY-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 0.00 |
June | 2865.98 | 13-JUN-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 0.00 |
July | 2576.42 | 14-JUL-20:40 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.16 | 0.00 |
August | 2541.53 | 14-AUG-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
September | 2702.18 | 13-SEP-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 | 0.00 |
October | 2441.58 | 04-OCT-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 0.00 |
November | 2422.30 | 03-NOV-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 |
December | 2388.72 | 07-DEC-21:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2388.72 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 | |
Maximum of Months | 2865.98 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2001.82 | 05-JAN-21:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 | 0.00 |
February | 2018.60 | 22-FEB-21:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 37.26 | 0.00 |
March | 2318.66 | 29-MAR-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 0.00 |
April | 2878.18 | 30-APR-19:20 | 190.94 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 86.30 | 0.00 |
May | 3321.66 | 05-MAY-19:20 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 70.04 | 0.00 |
June | 3794.52 | 13-JUN-19:30 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 71.92 | 0.00 |
July | 3227.07 | 14-JUL-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.56 | 0.00 |
August | 2884.25 | 01-AUG-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 0.00 |
September | 2476.90 | 08-SEP-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 | 0.00 |
October | 2048.84 | 04-OCT-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 0.00 |
November | 2010.96 | 21-NOV-21:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 | 0.00 |
December | 1994.08 | 08-DEC-22:00 | 254.59 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1994.08 | 190.94 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 | 0.00 | |
Maximum of Months | 3794.52 | 254.59 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 86.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1194.16 | 05-JAN-22:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 0.00 |
February | 1202.73 | 22-FEB-22:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 0.00 |
March | 1229.17 | 29-MAR-21:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 0.00 |
April | 1484.57 | 30-APR-19:10 | 146.88 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 53.75 | 0.00 |
May | 1741.58 | 06-MAY-17:25 | 293.76 | 452.04 | 356.86 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 0.00 |
June | 1981.77 | 13-JUN-18:03 | 1028.16 | 1808.18 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 | 0.00 |
July | 1654.49 | 14-JUL-18:03 | 1028.16 | 1808.18 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 44.66 | 0.00 |
August | 1442.37 | 01-AUG-20:00 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 0.00 |
September | 1243.40 | 07-SEP-21:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 | 0.00 |
October | 1207.64 | 04-OCT-21:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 | 0.00 |
November | 1199.77 | 21-NOV-21:20 | 195.84 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 25.94 | 0.00 |
December | 1193.74 | 08-DEC-22:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1193.74 | 146.88 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 0.00 | |
Maximum of Months | 1981.77 | 1028.16 | 1808.18 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 53.75 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35880.46 | 04-JAN-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 40.43 | 0.00 |
February | 36107.08 | 22-FEB-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 50.61 | 0.00 |
March | 36466.50 | 29-MAR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.55 | 0.00 |
April | 36743.99 | 28-APR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 71.55 | 0.00 |
May | 37136.89 | 05-MAY-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 85.50 | 0.00 |
June | 37085.67 | 13-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 99.65 | 0.00 |
July | 36588.44 | 14-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 78.61 | 0.00 |
August | 36458.63 | 01-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 71.52 | 0.00 |
September | 36393.24 | 06-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 64.71 | 0.00 |
October | 36039.47 | 04-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.58 | 0.00 |
November | 35767.60 | 22-NOV-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 |
December | 35776.41 | 08-DEC-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35767.60 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 | |
Maximum of Months | 37136.89 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 99.65 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13541.11 | 05-JAN-16:03 | 51228.00 | 717.81 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 205.18 | 0.00 |
February | 13074.25 | 03-FEB-16:03 | 51228.00 | 717.81 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 229.82 | 0.00 |
March | 12665.78 | 13-MAR-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 103.05 | 0.00 |
April | 12400.27 | 19-APR-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.41 | 0.00 |
May | 12863.43 | 05-MAY-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 127.56 | 0.00 |
June | 12780.85 | 13-JUN-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.58 | 0.00 |
July | 11938.65 | 26-JUL-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.54 | 0.00 |
August | 12252.09 | 14-AUG-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 125.86 | 0.00 |
September | 12500.37 | 13-SEP-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 135.41 | 0.00 |
October | 12535.42 | 16-OCT-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 | 0.00 |
November | 12691.56 | 21-NOV-22:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 85.45 | 0.00 |
December | 13223.53 | 08-DEC-22:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 100.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11938.65 | 15368.40 | 717.81 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.54 | 0.00 | |
Maximum of Months | 13541.11 | 51228.00 | 1305.12 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 229.82 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42836.49 | 05-JAN-22:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 174.87 | 0.00 |
February | 42440.69 | 22-FEB-22:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 220.64 | 0.00 |
March | 42254.46 | 29-MAR-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 294.60 | 0.00 |
April | 43467.00 | 28-APR-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 322.68 | 0.00 |
May | 46363.65 | 05-MAY-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 364.25 | 0.00 |
June | 48195.59 | 13-JUN-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 361.43 | 0.00 |
July | 44402.33 | 14-JUL-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 308.22 | 0.00 |
August | 43402.37 | 01-AUG-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 352.14 | 0.00 |
September | 42325.53 | 13-SEP-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 386.67 | 0.00 |
October | 41259.37 | 04-OCT-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 249.99 | 0.00 |
November | 41802.94 | 21-NOV-22:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 243.95 | 0.00 |
December | 42757.65 | 08-DEC-22:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 286.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41259.37 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 174.87 | 0.00 | |
Maximum of Months | 48195.59 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 386.67 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3097.92 | 19-JAN-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 52.11 | 0.00 |
February | 3101.23 | 15-FEB-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 48.92 | 0.00 |
March | 3109.10 | 16-MAR-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 | 0.00 |
April | 3130.16 | 17-APR-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 69.61 | 0.00 |
May | 3129.80 | 31-MAY-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 | 0.00 |
June | 3135.83 | 07-JUN-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 74.23 | 0.00 |
July | 3055.48 | 14-JUL-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 | 0.00 |
August | 3045.29 | 27-AUG-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 | 0.00 |
September | 3139.16 | 12-SEP-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 0.00 |
October | 3124.37 | 28-OCT-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 50.38 | 0.00 |
November | 3098.54 | 29-NOV-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.11 | 0.00 |
December | 3109.02 | 29-DEC-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3045.29 | 324.00 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.11 | 0.00 | |
Maximum of Months | 3139.16 | 583.20 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3134.43 | 30-JAN-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.02 | 0.00 |
February | 3149.62 | 13-FEB-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 69.41 | 0.00 |
March | 3147.95 | 15-MAR-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 61.99 | 0.00 |
April | 3164.91 | 07-APR-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 64.65 | 0.00 |
May | 3157.51 | 04-MAY-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 66.28 | 0.00 |
June | 3162.61 | 10-JUN-18:02 | 702.00 | 1261.20 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 53.09 | 0.00 |
July | 3167.52 | 14-JUL-18:02 | 831.60 | 1122.47 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.56 | 0.00 |
August | 3078.14 | 27-AUG-15:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 62.10 | 0.00 |
September | 3168.59 | 13-SEP-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 66.85 | 0.00 |
October | 3071.77 | 04-OCT-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 | 0.00 |
November | 3127.48 | 20-NOV-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 53.94 | 0.00 |
December | 3121.27 | 31-DEC-16:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 55.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3071.77 | 324.00 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.02 | 0.00 | |
Maximum of Months | 3168.59 | 831.60 | 1261.20 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 69.41 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 630.04 | 05-JAN-14:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 0.00 |
February | 568.21 | 04-FEB-14:30 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 0.00 |
March | 461.78 | 09-MAR-14:00 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 0.00 |
April | 440.39 | 01-APR-20:20 | 0.00 | 132.12 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 | 0.00 |
May | 456.71 | 06-MAY-20:10 | 0.00 | 132.12 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | 0.00 |
June | 442.82 | 13-JUN-20:20 | 0.00 | 117.59 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 | 0.00 |
July | 420.17 | 15-JUL-20:10 | 0.00 | 132.12 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 0.00 |
August | 414.50 | 14-AUG-20:40 | 0.00 | 117.59 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 | 0.00 |
September | 428.38 | 27-SEP-20:40 | 0.00 | 117.59 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 0.00 |
October | 488.03 | 28-OCT-13:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
November | 566.15 | 23-NOV-09:00 | 0.00 | 73.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 | 0.00 |
December | 631.34 | 07-DEC-13:50 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 414.50 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 0.00 | |
Maximum of Months | 631.34 | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1134.29 | 24-JAN-19:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 0.00 |
February | 1153.75 | 24-FEB-19:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 0.00 |
March | 1145.57 | 04-MAR-09:02 | 324.00 | 444.04 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 0.00 |
April | 1140.43 | 27-APR-18:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 | 0.00 |
May | 1151.17 | 27-MAY-18:02 | 702.00 | 792.93 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 |
June | 1153.66 | 24-JUN-20:11 | 1247.40 | 1189.39 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
July | 1159.54 | 13-JUL-18:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 0.00 |
August | 1132.36 | 01-AUG-18:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 0.00 |
September | 1134.01 | 09-SEP-08:62 | 324.00 | 444.04 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 0.00 |
October | 1128.64 | 01-OCT-08:62 | 324.00 | 444.04 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 |
November | 1139.71 | 23-NOV-09:02 | 324.00 | 444.04 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 10.79 | 0.00 |
December | 1141.00 | 19-DEC-19:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1128.64 | 324.00 | 444.04 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 | |
Maximum of Months | 1159.54 | 1247.40 | 1189.39 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2920.70 | 21-JAN-09:11 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 0.00 |
February | 3037.45 | 24-FEB-09:11 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 | 0.00 |
March | 2803.98 | 26-MAR-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 72.97 | 0.00 |
April | 2734.05 | 01-APR-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 78.67 | 0.00 |
May | 2788.64 | 05-MAY-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 85.24 | 0.00 |
June | 2723.29 | 15-JUN-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | 0.00 |
July | 2680.17 | 15-JUL-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 67.48 | 0.00 |
August | 2651.89 | 27-AUG-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 62.04 | 0.00 |
September | 2684.39 | 05-SEP-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 0.00 |
October | 2696.75 | 08-OCT-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 55.99 | 0.00 |
November | 2858.51 | 22-NOV-07:41 | 774.00 | 1177.26 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 0.00 |
December | 2913.24 | 27-DEC-09:01 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2651.89 | 324.00 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 0.00 | |
Maximum of Months | 3037.45 | 774.00 | 1177.26 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 85.24 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2840.94 | 21-JAN-09:11 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
February | 2988.44 | 24-FEB-09:11 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 | 0.00 |
March | 2798.98 | 29-MAR-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 74.10 | 0.00 |
April | 2750.78 | 12-APR-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 66.70 | 0.00 |
May | 2837.81 | 20-MAY-15:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 73.80 | 0.00 |
June | 2847.49 | 13-JUN-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 85.30 | 0.00 |
July | 2741.63 | 14-JUL-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 64.16 | 0.00 |
August | 2685.39 | 01-AUG-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 66.76 | 0.00 |
September | 2699.89 | 05-SEP-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 | 0.00 |
October | 2668.24 | 04-OCT-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 63.24 | 0.00 |
November | 2785.76 | 22-NOV-07:41 | 774.00 | 1177.12 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 0.00 |
December | 2802.64 | 27-DEC-09:01 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2668.24 | 324.00 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 | |
Maximum of Months | 2988.44 | 774.00 | 1177.12 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 85.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2720.57 | 31-JAN-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 0.00 |
February | 2742.92 | 24-FEB-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.78 | 0.00 |
March | 2716.70 | 29-MAR-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 | 0.00 |
April | 2721.30 | 30-APR-21:10 | 2011.87 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 0.00 |
May | 2978.24 | 06-MAY-20:10 | 1760.39 | 1452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.42 | 0.00 |
June | 3429.67 | 13-JUN-20:10 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.20 | 0.00 |
July | 2682.99 | 27-JUL-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 0.00 |
August | 2703.73 | 14-AUG-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.29 | 0.00 |
September | 2681.38 | 08-SEP-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 0.00 |
October | 2665.86 | 04-OCT-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 | 0.00 |
November | 2720.76 | 22-NOV-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 | 0.00 |
December | 2746.25 | 08-DEC-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2665.86 | 1760.39 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 | 0.00 | |
Maximum of Months | 3429.67 | 2263.36 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.42 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3482.63 | 05-JAN-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 61.09 | 0.00 |
February | 3457.03 | 22-FEB-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 | 0.00 |
March | 3448.70 | 11-MAR-16:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 62.31 | 0.00 |
April | 3473.68 | 18-APR-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 71.19 | 0.00 |
May | 3424.43 | 05-MAY-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 84.55 | 0.00 |
June | 3435.43 | 13-JUN-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 | 0.00 |
July | 3411.52 | 04-JUL-18:02 | 702.00 | 1261.35 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 29.93 | 0.00 |
August | 3423.26 | 31-AUG-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 | 0.00 |
September | 3412.60 | 13-SEP-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 | 0.00 |
October | 3427.94 | 15-OCT-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 44.75 | 0.00 |
November | 3402.94 | 10-NOV-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | 0.00 |
December | 3400.12 | 07-DEC-16:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3400.12 | 324.00 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 29.93 | 0.00 | |
Maximum of Months | 3482.63 | 702.00 | 1261.35 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3380.81 | 19-JAN-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 | 0.00 |
February | 3416.43 | 07-FEB-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 49.35 | 0.00 |
March | 3428.72 | 20-MAR-18:02 | 831.60 | 1122.47 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 | 0.00 |
April | 3486.84 | 02-APR-15:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 77.33 | 0.00 |
May | 3520.28 | 05-MAY-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 84.61 | 0.00 |
June | 3524.19 | 07-JUN-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 73.36 | 0.00 |
July | 3436.03 | 15-JUL-18:02 | 702.00 | 1261.20 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 0.00 |
August | 3456.00 | 31-AUG-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 | 0.00 |
September | 3413.47 | 04-SEP-15:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 0.00 |
October | 3456.67 | 14-OCT-15:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 53.85 | 0.00 |
November | 3419.46 | 06-NOV-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 | 0.00 |
December | 3415.61 | 12-DEC-16:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 52.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3380.81 | 324.00 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 | 0.00 | |
Maximum of Months | 3524.19 | 831.60 | 1261.20 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 84.61 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1699.43 | 28-JAN-09:41 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
February | 1680.16 | 02-FEB-09:41 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 0.00 |
March | 1613.99 | 30-MAR-15:02 | 583.20 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 | 0.00 |
April | 1621.42 | 06-APR-15:02 | 583.20 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 | 0.00 |
May | 1623.97 | 07-MAY-15:02 | 324.00 | 261.67 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 36.73 | 0.00 |
June | 1583.30 | 15-JUN-15:02 | 583.20 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 39.97 | 0.00 |
July | 1569.68 | 15-JUL-15:02 | 324.00 | 261.67 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 0.00 |
August | 1556.77 | 27-AUG-15:02 | 324.00 | 261.67 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 0.00 |
September | 1619.01 | 30-SEP-15:02 | 324.00 | 261.67 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 0.00 |
October | 1621.73 | 27-OCT-15:02 | 583.20 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 0.00 |
November | 1681.03 | 25-NOV-09:51 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
December | 1669.17 | 27-DEC-09:01 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1556.77 | 324.00 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1699.43 | 583.20 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 39.97 | 2.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23439.06 | 03-JAN-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 |
February | 23505.64 | 21-FEB-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.58 | 0.00 |
March | 24192.36 | 28-MAR-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 | 0.00 |
April | 24629.82 | 28-APR-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 70.82 | 0.00 |
May | 25318.41 | 05-MAY-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 80.15 | 0.00 |
June | 25885.86 | 12-JUN-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
July | 25203.68 | 14-JUL-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 | 0.00 |
August | 24750.93 | 01-AUG-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 77.43 | 0.00 |
September | 24333.50 | 05-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 | 0.00 |
October | 23713.32 | 16-OCT-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 0.00 |
November | 23445.80 | 14-NOV-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 | 0.00 |
December | 23539.75 | 08-DEC-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23439.06 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 | |
Maximum of Months | 25885.86 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24659.32 | 03-JAN-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 |
February | 24700.87 | 15-FEB-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.61 | 0.00 |
March | 25402.02 | 28-MAR-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 | 0.00 |
April | 25861.92 | 28-APR-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 70.82 | 0.00 |
May | 26534.91 | 05-MAY-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 80.15 | 0.00 |
June | 27113.45 | 12-JUN-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
July | 26487.16 | 14-JUL-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 | 0.00 |
August | 26022.18 | 01-AUG-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 77.43 | 0.00 |
September | 25582.80 | 05-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 | 0.00 |
October | 24941.65 | 16-OCT-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 0.00 |
November | 24699.51 | 14-NOV-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 | 0.00 |
December | 24711.75 | 08-DEC-22:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24659.32 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 | |
Maximum of Months | 27113.45 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29878.74 | 04-JAN-11:50 | 533.71 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 128.64 | 0.00 |
February | 30048.40 | 20-FEB-11:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 105.29 | 0.00 |
March | 30448.25 | 19-MAR-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 138.09 | 0.00 |
April | 30771.43 | 09-APR-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 133.82 | 0.00 |
May | 30952.24 | 07-MAY-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 127.40 | 0.00 |
June | 30759.87 | 24-JUN-10:50 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 116.87 | 0.00 |
July | 29968.26 | 15-JUL-18:03 | 9606.82 | 5650.98 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 113.24 | 0.00 |
August | 30395.42 | 27-AUG-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 124.74 | 0.00 |
September | 30554.98 | 03-SEP-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 111.60 | 0.00 |
October | 30285.52 | 07-OCT-10:50 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 106.69 | 0.00 |
November | 30011.08 | 23-NOV-11:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.84 | 0.00 |
December | 29962.78 | 03-DEC-11:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 100.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29878.74 | 533.71 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.84 | 0.00 | |
Maximum of Months | 30952.24 | 9606.82 | 5650.98 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 138.09 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7567.28 | 05-JAN-15:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.25 | 0.00 |
February | 7375.53 | 22-FEB-16:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 0.00 |
March | 7463.53 | 28-MAR-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.03 | 0.00 |
April | 7334.25 | 01-APR-14:40 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.29 | 0.00 |
May | 7986.08 | 06-MAY-14:20 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.10 | 0.00 |
June | 8143.20 | 13-JUN-15:30 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.49 | 0.00 |
July | 6936.90 | 14-JUL-16:20 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.49 | 0.00 |
August | 6964.45 | 14-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.78 | 0.00 |
September | 6727.11 | 12-SEP-15:15 | 2661.60 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.75 | 0.00 |
October | 6431.47 | 07-OCT-14:00 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.03 | 0.00 |
November | 6997.13 | 22-NOV-13:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.93 | 0.00 |
December | 7545.13 | 08-DEC-14:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6431.47 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.78 | 0.00 | |
Maximum of Months | 8143.20 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.10 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.771010E+12 | 427323.06 | 09-JAN-20:10 | 0.369161E+12 | 315630.29 | 12-JAN-18:10 |
February | 0.711685E+12 | 440993.80 | 14-FEB-20:10 | 0.332508E+12 | 315382.47 | 06-FEB-18:40 |
March | 0.804798E+12 | 447698.82 | 28-MAR-19:10 | 0.366487E+12 | 314992.32 | 02-MAR-18:30 |
April | 0.822187E+12 | 478744.83 | 30-APR-19:10 | 0.351891E+12 | 314216.55 | 03-APR-17:30 |
May | 0.881401E+12 | 487094.11 | 19-MAY-19:10 | 0.361538E+12 | 313384.02 | 02-MAY-17:19 |
June | 0.859217E+12 | 501453.14 | 12-JUN-19:10 | 0.348018E+12 | 312562.82 | 02-JUN-17:40 |
July | 0.802944E+12 | 458143.62 | 14-JUL-19:10 | 0.359108E+12 | 312205.50 | 05-JUL-17:10 |
August | 0.838952E+12 | 479931.99 | 14-AUG-19:49 | 0.360495E+12 | 312605.11 | 24-AUG-17:10 |
September | 0.806795E+12 | 468782.50 | 13-SEP-19:00 | 0.350224E+12 | 313358.43 | 26-SEP-17:19 |
October | 0.812420E+12 | 455285.28 | 16-OCT-19:10 | 0.364696E+12 | 314219.40 | 26-OCT-17:30 |
November | 0.774136E+12 | 457260.37 | 17-NOV-19:10 | 0.355194E+12 | 315096.94 | 30-NOV-18:30 |
December | 0.780320E+12 | 447224.51 | 29-DEC-19:10 | 0.368653E+12 | 315449.04 | 27-DEC-18:40 |
Annual Sum or Average | 0.966586E+13 | 0.428797E+13 | ||||
Minimum of Months | 0.711685E+12 | 427323.06 | 0.332508E+12 | 312205.50 | ||
Maximum of Months | 0.881401E+12 | 501453.14 | 0.369161E+12 | 315630.29 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.738801E+11 | 0.233933E+11 | 0.140828E+12 | 0.552129E+11 | 0.452016E+11 | 0.152006E+11 | 0.00 | 0.378125E+12 | 0.00 | 0.00 | 0.261580E+11 | 0.770527E+10 | 0.00 |
February | 0.666862E+11 | 0.207996E+11 | 0.127191E+12 | 0.498698E+11 | 0.416953E+11 | 0.138107E+11 | 0.00 | 0.355930E+12 | 0.00 | 0.00 | 0.239488E+11 | 0.696269E+10 | 0.00 |
March | 0.736724E+11 | 0.223217E+11 | 0.140882E+12 | 0.552165E+11 | 0.461843E+11 | 0.154611E+11 | 0.00 | 0.411427E+12 | 0.00 | 0.00 | 0.266189E+11 | 0.770389E+10 | 0.00 |
April | 0.711875E+11 | 0.210900E+11 | 0.136245E+12 | 0.534313E+11 | 0.451699E+11 | 0.155026E+11 | 0.00 | 0.441202E+12 | 0.00 | 0.00 | 0.257617E+11 | 0.746562E+10 | 0.00 |
May | 0.735875E+11 | 0.214204E+11 | 0.140860E+12 | 0.552145E+11 | 0.473118E+11 | 0.165870E+11 | 0.00 | 0.486793E+12 | 0.00 | 0.00 | 0.266092E+11 | 0.770522E+10 | 0.00 |
June | 0.710888E+11 | 0.204891E+11 | 0.136336E+12 | 0.534347E+11 | 0.474291E+11 | 0.161698E+11 | 0.00 | 0.475921E+12 | 0.00 | 0.00 | 0.257452E+11 | 0.745769E+10 | 0.00 |
July | 0.735698E+11 | 0.213403E+11 | 0.140770E+12 | 0.552110E+11 | 0.454786E+11 | 0.156058E+11 | 0.00 | 0.411366E+12 | 0.00 | 0.00 | 0.266052E+11 | 0.771325E+10 | 0.00 |
August | 0.735564E+11 | 0.216107E+11 | 0.140892E+12 | 0.552164E+11 | 0.447563E+11 | 0.161521E+11 | 0.00 | 0.447149E+12 | 0.00 | 0.00 | 0.266043E+11 | 0.770528E+10 | 0.00 |
September | 0.714056E+11 | 0.214505E+11 | 0.136256E+12 | 0.534316E+11 | 0.433897E+11 | 0.155118E+11 | 0.00 | 0.426998E+12 | 0.00 | 0.00 | 0.257423E+11 | 0.746713E+10 | 0.00 |
October | 0.738307E+11 | 0.227423E+11 | 0.140818E+12 | 0.552128E+11 | 0.439730E+11 | 0.158154E+11 | 0.00 | 0.420405E+12 | 0.00 | 0.00 | 0.266129E+11 | 0.770383E+10 | 0.00 |
November | 0.714693E+11 | 0.224519E+11 | 0.136330E+12 | 0.534328E+11 | 0.431651E+11 | 0.151393E+11 | 0.00 | 0.393937E+12 | 0.00 | 0.00 | 0.256345E+11 | 0.744969E+10 | 0.00 |
December | 0.738714E+11 | 0.235435E+11 | 0.140770E+12 | 0.552113E+11 | 0.446185E+11 | 0.154163E+11 | 0.00 | 0.387786E+12 | 0.00 | 0.00 | 0.260858E+11 | 0.771357E+10 | 0.00 |
Annual Sum or Average | 0.867806E+12 | 0.262653E+12 | 0.165818E+13 | 0.650096E+12 | 0.538373E+12 | 0.186372E+12 | 0.00 | 0.503704E+13 | 0.00 | 0.00 | 0.312127E+12 | 0.907531E+11 | 0.00 |
Minimum of Months | 0.666862E+11 | 0.204891E+11 | 0.127191E+12 | 0.498698E+11 | 0.416953E+11 | 0.138107E+11 | 0.00 | 0.355930E+12 | 0.00 | 0.00 | 0.239488E+11 | 0.696269E+10 | 0.00 |
Maximum of Months | 0.738801E+11 | 0.235435E+11 | 0.140892E+12 | 0.552165E+11 | 0.474291E+11 | 0.165870E+11 | 0.00 | 0.486793E+12 | 0.00 | 0.00 | 0.266189E+11 | 0.771357E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.200589E+10 | 0.00 | 0.215237E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.153640E+10 | 0.00 | 0.193768E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.168204E+10 | 0.00 | 0.212781E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.141968E+10 | 0.00 | 0.203515E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.163981E+10 | 0.00 | 0.207920E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.136017E+10 | 0.00 | 0.199544E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.168100E+10 | 0.00 | 0.205607E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.201416E+10 | 0.00 | 0.206442E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.171644E+10 | 0.00 | 0.201537E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.212082E+10 | 0.00 | 0.210672E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.191590E+10 | 0.00 | 0.206187E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.207741E+10 | 0.00 | 0.214755E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.211697E+11 | 0.00 | 0.247796E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.136017E+10 | 0.00 | 0.193768E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.212082E+10 | 0.00 | 0.215237E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 71560.59 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39719.23 | 09-JAN-07:19 | 25863.10 | 05-JAN-19:19 | 6398.13 | 09-JAN-21:40 | 0.00 | 01-JAN-00:10 |
February | 71560.59 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39718.92 | 06-FEB-07:19 | 25896.63 | 22-FEB-19:19 | 6568.04 | 15-FEB-19:19 | 0.00 | 01-FEB-00:10 |
March | 71560.59 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39721.54 | 13-MAR-06:19 | 26015.98 | 20-MAR-18:19 | 6753.12 | 14-MAR-21:00 | 0.00 | 01-MAR-00:10 |
April | 71560.59 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39721.06 | 21-APR-06:19 | 26875.27 | 27-APR-18:19 | 6976.99 | 10-APR-18:19 | 0.00 | 01-APR-00:10 |
May | 71560.59 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39720.14 | 11-MAY-06:19 | 29462.40 | 05-MAY-18:30 | 7387.50 | 31-MAY-20:19 | 0.00 | 01-MAY-00:10 |
June | 71560.59 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39721.06 | 20-JUN-06:19 | 31775.86 | 12-JUN-18:19 | 7587.56 | 14-JUN-20:40 | 0.00 | 01-JUN-00:10 |
July | 71560.59 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39721.06 | 11-JUL-06:19 | 27956.09 | 14-JUL-18:19 | 6861.71 | 17-JUL-18:49 | 0.00 | 01-JUL-00:10 |
August | 71560.59 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39720.93 | 02-AUG-06:19 | 26887.13 | 14-AUG-18:19 | 7428.69 | 14-AUG-20:19 | 0.00 | 01-AUG-00:10 |
September | 71560.59 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39721.06 | 21-SEP-06:19 | 26070.72 | 13-SEP-20:10 | 6957.35 | 08-SEP-18:30 | 0.00 | 01-SEP-00:10 |
October | 71560.59 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39721.54 | 23-OCT-06:19 | 25147.87 | 04-OCT-20:10 | 6794.08 | 16-OCT-18:19 | 0.00 | 01-OCT-00:10 |
November | 71560.59 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39720.76 | 03-NOV-06:19 | 24811.54 | 21-NOV-21:10 | 6832.86 | 30-NOV-22:00 | 0.00 | 01-NOV-00:10 |
December | 71560.59 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39718.62 | 11-DEC-07:19 | 25542.67 | 08-DEC-21:10 | 6745.61 | 21-DEC-21:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 71560.59 | 16690.39 | 89171.45 | 39718.62 | 24811.54 | 6398.13 | 0.00 | |||||||
Maximum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.54 | 31775.86 | 7587.56 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 195915.75 | 04-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.71 | 13-JAN-19:10 | 0.00 |
February | 215450.76 | 13-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.68 | 03-FEB-19:10 | 0.00 |
March | 220454.93 | 28-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.76 | 03-MAR-19:10 | 0.00 |
April | 236929.69 | 02-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.51 | 27-APR-18:10 | 0.00 |
May | 257164.61 | 06-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.49 | 19-MAY-18:10 | 0.00 |
June | 274138.93 | 13-JUN-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.60 | 14-JUN-18:10 | 0.00 |
July | 218410.10 | 20-JUL-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.70 | 21-JUL-18:10 | 0.00 |
August | 243470.53 | 13-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.75 | 16-AUG-18:10 | 0.00 |
September | 224214.91 | 30-SEP-10:00 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4738.62 | 22-SEP-18:10 | 0.00 |
October | 220156.42 | 16-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.73 | 20-OCT-18:10 | 0.00 |
November | 220765.76 | 17-NOV-19:10 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.75 | 17-NOV-19:10 | 0.00 |
December | 210806.98 | 29-DEC-19:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.71 | 06-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 195915.75 | 0.00 | 0.00 | 9938.94 | 4738.49 | 0.00 | |||
Maximum of Months | 274138.93 | 0.00 | 0.00 | 9938.94 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 427323.06 | 09-JAN-20:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 22789.50 | 6330.18 | 0.00 | 175235.42 | 0.00 |
February | 440993.80 | 14-FEB-20:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 24175.34 | 6467.68 | 0.00 | 188240.02 | 0.00 |
March | 447698.82 | 28-MAR-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 25213.58 | 6623.60 | 0.00 | 193734.76 | 0.00 |
April | 478744.83 | 30-APR-19:10 | 66393.55 | 84978.71 | 16690.39 | 32030.64 | 25293.64 | 6821.83 | 0.00 | 231084.40 | 0.00 |
May | 487094.11 | 19-MAY-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 26331.07 | 7287.80 | 0.00 | 231061.96 | 0.00 |
June | 501453.14 | 12-JUN-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 31007.90 | 7378.52 | 0.00 | 240181.98 | 0.00 |
July | 458143.62 | 14-JUL-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 26900.91 | 6612.54 | 0.00 | 202206.32 | 0.00 |
August | 479931.99 | 14-AUG-19:49 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 25992.24 | 7309.26 | 0.00 | 223515.97 | 0.00 |
September | 468782.50 | 13-SEP-19:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 25427.44 | 6884.29 | 0.00 | 213825.91 | 0.00 |
October | 455285.28 | 16-OCT-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 24521.96 | 6773.22 | 0.00 | 201044.74 | 0.00 |
November | 457260.37 | 17-NOV-19:10 | 63637.18 | 77573.37 | 16690.39 | 31790.09 | 23597.81 | 6673.31 | 0.00 | 220765.76 | 0.00 |
December | 447224.51 | 29-DEC-19:10 | 63637.18 | 77573.37 | 16690.39 | 31790.09 | 24010.29 | 6559.20 | 0.00 | 210806.98 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 427323.06 | 63637.18 | 77573.37 | 16690.39 | 31790.09 | 22789.50 | 6330.18 | 0.00 | 175235.42 | 0.00 | |
Maximum of Months | 501453.14 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 31007.90 | 7378.52 | 0.00 | 240181.98 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 8099.41 | 02-JAN-04:00 | 0.00 | 211704.30 | 09-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 7208.26 | 11-FEB-05:00 | 0.00 | 211582.16 | 03-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 8475.34 | 04-MAR-05:49 | 0.00 | 211148.66 | 02-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 8384.73 | 10-APR-03:00 | 0.00 | 210206.54 | 05-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 8014.71 | 26-MAY-03:00 | 0.00 | 209484.19 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 7371.32 | 05-JUN-03:49 | 0.00 | 208652.19 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 8067.80 | 01-JUL-04:49 | 0.00 | 208243.27 | 31-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 9161.13 | 21-AUG-03:00 | 0.00 | 208746.84 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 9050.80 | 16-SEP-04:00 | 0.00 | 209539.98 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 9350.92 | 23-OCT-03:00 | 0.00 | 210392.61 | 27-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 8663.41 | 27-NOV-04:00 | 0.00 | 211245.03 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 8089.22 | 18-DEC-04:00 | 0.00 | 211659.40 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 7208.26 | 0.00 | 208243.27 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 9350.92 | 0.00 | 211704.30 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.72 | 1.50 | 21.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.72 | 1.50 | 21.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.82 | 0.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
Annual Sum or Average | 0.00 | 0.00 | 5.33 | 21.74 | 5.33 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.82 | 1.50 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 21.77 | 1.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.83 | 0.50 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.70 | 2.50 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.73 | 6.17 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.92 | 0.33 | 21.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.67 | 21.73 | 11.67 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.92 | 6.17 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.09 | 3.00 | 22.09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.02 | 2.50 | 22.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.86 | 1.67 | 21.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.94 | 2.67 | 21.94 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 21.95 | 12.00 | 21.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.09 | 3.00 | 22.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.96 | 2.17 | 21.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.01 | 1.50 | 22.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.80 | 0.33 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.80 | 0.33 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.84 | 0.67 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.90 | 1.33 | 21.90 |
Annual Sum or Average | 0.00 | 0.00 | 8.17 | 21.90 | 8.17 | 21.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.01 | 2.17 | 22.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.73 | 2.50 | 21.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.73 | 2.50 | 21.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.71 | 3.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.71 | 2.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.89 | 0.33 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.72 | 1.67 | 21.72 |
Annual Sum or Average | 0.00 | 0.00 | 17.00 | 21.73 | 17.00 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.89 | 3.17 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.71 | 1.50 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.69 | 2.33 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.76 | 2.00 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.83 | 0.67 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 21.73 | 10.33 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.83 | 2.33 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 21.97 | 15.33 | 21.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 21.91 | 9.33 | 21.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.78 | 4.17 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.69 | 1.83 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.71 | 2.17 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.72 | 2.50 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.03 | 0.33 | 22.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.73 | 2.00 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.78 | 3.67 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.86 | 7.00 | 21.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 21.94 | 15.00 | 21.94 |
Annual Sum or Average | 0.00 | 0.00 | 64.17 | 21.88 | 64.17 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 22.03 | 15.33 | 22.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.50 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
February | 336.33 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
March | 505.83 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
April | 452.67 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
May | 355.50 | 23.11 | 10.17 | 23.13 | 0.00 | 23.13 |
June | 178.33 | 23.16 | 53.33 | 23.34 | 0.00 | 23.34 |
July | 279.33 | 23.13 | 9.83 | 23.16 | 0.00 | 23.16 |
August | 398.67 | 23.07 | 12.50 | 23.10 | 0.00 | 23.10 |
September | 378.33 | 23.09 | 7.67 | 23.10 | 0.00 | 23.10 |
October | 566.50 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
November | 447.67 | 23.07 | 1.17 | 23.07 | 0.00 | 23.07 |
December | 446.33 | 23.08 | 2.33 | 23.08 | 0.00 | 23.08 |
Annual Sum or Average | 4842.00 | 23.08 | 97.00 | 23.10 | 0.00 | 23.10 |
Minimum of Months | 178.33 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
Maximum of Months | 566.50 | 23.16 | 53.33 | 23.34 | 0.00 | 23.34 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.67 | 22.43 | 522.67 | 23.59 | 0.00 | 23.59 |
February | 55.83 | 22.62 | 521.33 | 23.76 | 0.00 | 23.76 |
March | 53.50 | 22.52 | 561.50 | 23.72 | 0.00 | 23.72 |
April | 58.17 | 22.32 | 562.67 | 23.62 | 0.00 | 23.62 |
May | 113.17 | 22.35 | 536.83 | 23.52 | 0.00 | 23.52 |
June | 73.00 | 22.52 | 561.67 | 23.62 | 0.00 | 23.62 |
July | 149.67 | 22.45 | 437.67 | 23.37 | 0.00 | 23.37 |
August | 199.83 | 22.20 | 389.50 | 23.19 | 0.00 | 23.19 |
September | 141.50 | 22.30 | 447.00 | 23.41 | 0.00 | 23.41 |
October | 201.33 | 22.27 | 421.00 | 23.29 | 0.00 | 23.29 |
November | 125.33 | 22.36 | 482.00 | 23.52 | 0.00 | 23.52 |
December | 144.17 | 22.38 | 499.33 | 23.54 | 0.00 | 23.54 |
Annual Sum or Average | 1447.17 | 22.36 | 5943.17 | 23.51 | 0.00 | 23.51 |
Minimum of Months | 53.50 | 22.20 | 389.50 | 23.19 | 0.00 | 23.19 |
Maximum of Months | 201.33 | 22.62 | 562.67 | 23.76 | 0.00 | 23.76 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.67 | 22.68 | 196.50 | 23.10 | 0.00 | 23.10 |
February | 134.33 | 22.82 | 257.83 | 23.46 | 0.00 | 23.46 |
March | 164.83 | 22.77 | 326.33 | 23.44 | 0.00 | 23.44 |
April | 145.50 | 22.71 | 335.83 | 23.45 | 0.00 | 23.45 |
May | 193.33 | 22.64 | 316.00 | 23.34 | 0.00 | 23.34 |
June | 143.33 | 22.73 | 364.00 | 23.49 | 0.00 | 23.49 |
July | 292.17 | 22.70 | 221.00 | 23.16 | 0.00 | 23.16 |
August | 320.17 | 22.51 | 220.50 | 23.02 | 0.00 | 23.02 |
September | 275.67 | 22.60 | 228.17 | 23.13 | 0.00 | 23.13 |
October | 384.00 | 22.57 | 151.00 | 22.90 | 0.00 | 22.90 |
November | 316.17 | 22.65 | 161.17 | 23.03 | 0.00 | 23.03 |
December | 341.83 | 22.68 | 172.00 | 23.05 | 0.00 | 23.05 |
Annual Sum or Average | 3033.00 | 22.65 | 2950.33 | 23.20 | 0.00 | 23.20 |
Minimum of Months | 134.33 | 22.51 | 151.00 | 22.90 | 0.00 | 22.90 |
Maximum of Months | 384.00 | 22.82 | 364.00 | 23.49 | 0.00 | 23.49 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 596.83 | 22.92 | 1.33 | 22.92 | 0.00 | 22.92 |
February | 368.67 | 23.11 | 23.50 | 23.16 | 0.00 | 23.16 |
March | 287.33 | 23.06 | 91.83 | 23.27 | 0.00 | 23.27 |
April | 113.17 | 23.06 | 221.00 | 23.63 | 0.00 | 23.63 |
May | 84.50 | 23.00 | 458.83 | 23.79 | 0.00 | 23.79 |
June | 8.83 | 23.17 | 567.33 | 23.95 | 0.00 | 23.95 |
July | 67.83 | 23.11 | 320.83 | 23.79 | 0.00 | 23.79 |
August | 293.17 | 22.88 | 200.17 | 23.29 | 0.00 | 23.29 |
September | 258.17 | 22.88 | 117.17 | 23.21 | 0.00 | 23.21 |
October | 522.67 | 22.87 | 24.00 | 22.92 | 0.00 | 22.92 |
November | 519.00 | 22.96 | 7.67 | 22.98 | 0.00 | 22.98 |
December | 616.83 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
Annual Sum or Average | 3737.00 | 22.95 | 2033.67 | 23.30 | 0.00 | 23.30 |
Minimum of Months | 8.83 | 22.87 | 0.00 | 22.89 | 0.00 | 22.89 |
Maximum of Months | 616.83 | 23.17 | 567.33 | 23.95 | 0.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 709.67 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
February | 498.50 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
March | 434.17 | 23.02 | 4.00 | 23.02 | 0.00 | 23.02 |
April | 174.67 | 23.03 | 120.00 | 23.38 | 0.00 | 23.38 |
May | 131.33 | 22.98 | 388.67 | 23.68 | 0.00 | 23.68 |
June | 30.17 | 23.12 | 508.00 | 23.90 | 0.00 | 23.90 |
July | 117.33 | 23.09 | 205.17 | 23.61 | 0.00 | 23.61 |
August | 377.17 | 22.83 | 124.50 | 23.10 | 0.00 | 23.10 |
September | 381.33 | 22.87 | 23.33 | 22.93 | 0.00 | 22.93 |
October | 633.00 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
November | 644.50 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
December | 714.83 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
Annual Sum or Average | 4846.67 | 22.89 | 1373.67 | 23.12 | 0.00 | 23.12 |
Minimum of Months | 30.17 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
Maximum of Months | 714.83 | 23.12 | 508.00 | 23.90 | 0.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.17 | 23.95 | 691.33 | 22.58 | 159.17 | 22.80 |
February | 156.33 | 23.92 | 650.67 | 22.61 | 156.33 | 22.82 |
March | 183.00 | 23.90 | 721.50 | 22.64 | 183.00 | 22.85 |
April | 181.33 | 23.89 | 705.17 | 22.66 | 181.33 | 22.87 |
May | 180.50 | 23.90 | 706.50 | 22.67 | 180.50 | 22.88 |
June | 185.17 | 23.89 | 708.17 | 22.67 | 185.17 | 22.88 |
July | 172.33 | 23.92 | 717.83 | 22.58 | 172.33 | 22.79 |
August | 174.33 | 23.87 | 692.17 | 22.60 | 171.00 | 22.82 |
September | 168.17 | 23.90 | 683.17 | 22.60 | 167.17 | 22.82 |
October | 159.83 | 23.92 | 668.00 | 22.59 | 158.50 | 22.81 |
November | 154.33 | 23.95 | 668.50 | 22.59 | 154.33 | 22.80 |
December | 156.33 | 23.95 | 686.17 | 22.57 | 156.33 | 22.79 |
Annual Sum or Average | 2030.83 | 23.91 | 8299.17 | 22.61 | 2025.17 | 22.83 |
Minimum of Months | 154.33 | 23.87 | 650.67 | 22.57 | 154.33 | 22.79 |
Maximum of Months | 185.17 | 23.95 | 721.50 | 22.67 | 185.17 | 22.88 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.67 | 22.97 | 711.00 | 23.80 | 6.67 | 23.80 |
February | 0.67 | 23.99 | 669.33 | 23.84 | 0.67 | 23.84 |
March | 15.67 | 23.15 | 696.67 | 23.76 | 8.67 | 23.76 |
April | 21.33 | 23.27 | 653.17 | 23.65 | 13.00 | 23.65 |
May | 96.17 | 23.22 | 652.33 | 23.62 | 60.17 | 23.64 |
June | 54.67 | 23.65 | 652.83 | 23.66 | 45.67 | 23.68 |
July | 83.33 | 23.11 | 592.17 | 23.56 | 44.17 | 23.58 |
August | 162.17 | 22.99 | 537.33 | 23.49 | 77.67 | 23.53 |
September | 105.17 | 23.21 | 608.17 | 23.57 | 61.83 | 23.60 |
October | 104.83 | 23.02 | 631.17 | 23.57 | 51.50 | 23.59 |
November | 40.50 | 23.37 | 673.33 | 23.74 | 28.17 | 23.75 |
December | 30.50 | 23.53 | 709.67 | 23.79 | 22.83 | 23.79 |
Annual Sum or Average | 730.67 | 23.17 | 7787.17 | 23.67 | 421.00 | 23.68 |
Minimum of Months | 0.67 | 22.97 | 537.33 | 23.49 | 0.67 | 23.53 |
Maximum of Months | 162.17 | 23.99 | 711.00 | 23.84 | 77.67 | 23.84 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.67 | 22.60 | 488.50 | 23.64 | 0.00 | 23.64 |
February | 0.00 | 0.00 | 504.00 | 23.76 | 0.00 | 23.76 |
March | 23.33 | 22.68 | 499.33 | 23.75 | 0.00 | 23.75 |
April | 34.17 | 22.67 | 493.83 | 23.72 | 0.00 | 23.72 |
May | 55.33 | 22.59 | 558.17 | 23.68 | 0.00 | 23.68 |
June | 8.83 | 22.70 | 595.50 | 23.79 | 0.00 | 23.79 |
July | 55.50 | 22.66 | 489.67 | 23.69 | 0.00 | 23.69 |
August | 152.33 | 22.58 | 423.33 | 23.47 | 0.00 | 23.47 |
September | 90.00 | 22.57 | 436.50 | 23.57 | 0.00 | 23.57 |
October | 137.33 | 22.57 | 404.17 | 23.44 | 0.00 | 23.44 |
November | 56.17 | 22.59 | 465.67 | 23.60 | 0.00 | 23.60 |
December | 50.00 | 22.62 | 491.00 | 23.61 | 0.00 | 23.61 |
Annual Sum or Average | 709.67 | 22.60 | 5849.67 | 23.64 | 0.00 | 23.64 |
Minimum of Months | 0.00 | 0.00 | 404.17 | 23.44 | 0.00 | 23.44 |
Maximum of Months | 152.33 | 22.70 | 595.50 | 23.79 | 0.00 | 23.79 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 561.17 | 21.42 | 32.17 | 21.55 | 3.67 | 21.56 |
February | 499.33 | 21.37 | 32.00 | 21.50 | 1.17 | 21.51 |
March | 599.50 | 21.38 | 13.83 | 21.42 | 1.33 | 21.42 |
April | 577.83 | 21.35 | 13.67 | 21.40 | 0.00 | 21.40 |
May | 591.83 | 21.34 | 15.67 | 21.40 | 1.17 | 21.40 |
June | 564.50 | 21.34 | 31.17 | 21.45 | 2.17 | 21.46 |
July | 610.83 | 21.42 | 3.67 | 21.44 | 2.83 | 21.45 |
August | 611.67 | 21.40 | 15.00 | 21.45 | 5.83 | 21.47 |
September | 584.67 | 21.40 | 16.00 | 21.45 | 7.00 | 21.48 |
October | 607.83 | 21.42 | 14.50 | 21.47 | 9.50 | 21.51 |
November | 565.00 | 21.44 | 28.67 | 21.56 | 12.00 | 21.60 |
December | 562.33 | 21.46 | 35.67 | 21.60 | 11.83 | 21.64 |
Annual Sum or Average | 6936.50 | 21.39 | 252.00 | 21.47 | 58.50 | 21.49 |
Minimum of Months | 499.33 | 21.34 | 3.67 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 611.67 | 21.46 | 35.67 | 21.60 | 12.00 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 615.67 | 21.57 | 6.67 | 21.59 | 6.00 | 21.61 |
February | 535.83 | 21.48 | 2.17 | 21.49 | 0.67 | 21.50 |
March | 611.17 | 21.41 | 4.17 | 21.42 | 1.67 | 21.43 |
April | 577.33 | 21.35 | 15.67 | 21.40 | 0.00 | 21.40 |
May | 584.67 | 21.32 | 22.83 | 21.40 | 1.17 | 21.41 |
June | 552.33 | 21.30 | 49.33 | 21.47 | 2.17 | 21.48 |
July | 602.17 | 21.40 | 6.00 | 21.42 | 2.83 | 21.44 |
August | 608.33 | 21.40 | 17.17 | 21.45 | 5.67 | 21.47 |
September | 588.17 | 21.41 | 13.33 | 21.45 | 7.33 | 21.48 |
October | 620.17 | 21.45 | 10.67 | 21.49 | 10.00 | 21.52 |
November | 591.17 | 21.51 | 15.00 | 21.56 | 12.00 | 21.61 |
December | 615.33 | 21.59 | 16.00 | 21.64 | 15.33 | 21.68 |
Annual Sum or Average | 7102.33 | 21.43 | 179.00 | 21.48 | 64.83 | 21.50 |
Minimum of Months | 535.83 | 21.30 | 2.17 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 620.17 | 21.59 | 49.33 | 21.64 | 15.33 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.70 | 1.17 | 21.71 | 1.17 | 21.71 |
February | 672.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
March | 744.00 | 21.62 | 0.33 | 21.62 | 0.33 | 21.62 |
April | 720.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
May | 742.83 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
June | 719.83 | 21.72 | 2.17 | 21.73 | 2.17 | 21.74 |
July | 743.33 | 21.68 | 2.50 | 21.69 | 2.50 | 21.70 |
August | 744.00 | 21.63 | 5.33 | 21.64 | 5.33 | 21.65 |
September | 720.00 | 21.62 | 7.33 | 21.64 | 7.33 | 21.66 |
October | 743.50 | 21.60 | 7.00 | 21.62 | 7.00 | 21.63 |
November | 719.50 | 21.67 | 5.33 | 21.69 | 5.33 | 21.70 |
December | 744.00 | 21.72 | 5.50 | 21.73 | 5.50 | 21.74 |
Annual Sum or Average | 8757.00 | 21.67 | 36.67 | 21.67 | 36.67 | 21.68 |
Minimum of Months | 672.00 | 21.60 | 0.00 | 21.62 | 0.00 | 21.62 |
Maximum of Months | 744.00 | 21.72 | 7.33 | 21.73 | 7.33 | 21.74 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 541.17 | 21.40 | 41.50 | 21.62 | 9.17 | 21.67 |
February | 475.33 | 21.30 | 29.83 | 21.49 | 2.83 | 21.51 |
March | 562.67 | 21.27 | 2.33 | 21.28 | 0.83 | 21.28 |
April | 542.33 | 21.24 | 0.50 | 21.24 | 0.00 | 21.24 |
May | 572.17 | 21.29 | 4.33 | 21.30 | 3.33 | 21.32 |
June | 540.00 | 21.26 | 5.50 | 21.29 | 2.17 | 21.30 |
July | 592.33 | 21.37 | 4.67 | 21.40 | 3.17 | 21.41 |
August | 589.83 | 21.35 | 5.67 | 21.37 | 5.50 | 21.39 |
September | 565.17 | 21.34 | 7.67 | 21.38 | 7.17 | 21.40 |
October | 590.17 | 21.38 | 9.67 | 21.42 | 8.67 | 21.45 |
November | 544.83 | 21.39 | 24.83 | 21.51 | 12.00 | 21.57 |
December | 540.83 | 21.42 | 47.83 | 21.65 | 13.00 | 21.71 |
Annual Sum or Average | 6656.83 | 21.33 | 184.33 | 21.41 | 67.83 | 21.44 |
Minimum of Months | 475.33 | 21.24 | 0.50 | 21.24 | 0.00 | 21.24 |
Maximum of Months | 592.33 | 21.42 | 47.83 | 21.65 | 13.00 | 21.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 574.33 | 21.49 | 34.83 | 21.65 | 10.00 | 21.70 |
February | 492.50 | 21.36 | 24.83 | 21.51 | 3.33 | 21.53 |
March | 573.17 | 21.30 | 2.50 | 21.31 | 1.17 | 21.32 |
April | 541.50 | 21.24 | 0.50 | 21.24 | 0.00 | 21.24 |
May | 567.17 | 21.27 | 3.33 | 21.29 | 2.17 | 21.30 |
June | 534.83 | 21.24 | 9.17 | 21.29 | 2.17 | 21.30 |
July | 582.17 | 21.34 | 5.00 | 21.37 | 3.00 | 21.38 |
August | 585.83 | 21.34 | 5.83 | 21.36 | 5.50 | 21.38 |
September | 567.00 | 21.35 | 7.83 | 21.38 | 7.67 | 21.41 |
October | 602.50 | 21.42 | 9.50 | 21.45 | 8.83 | 21.48 |
November | 565.83 | 21.45 | 20.67 | 21.54 | 11.83 | 21.59 |
December | 575.50 | 21.51 | 37.67 | 21.67 | 14.67 | 21.73 |
Annual Sum or Average | 6762.33 | 21.36 | 161.67 | 21.42 | 70.33 | 21.45 |
Minimum of Months | 492.50 | 21.24 | 0.50 | 21.24 | 0.00 | 21.24 |
Maximum of Months | 602.50 | 21.51 | 37.67 | 21.67 | 14.67 | 21.73 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 671.17 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
February | 440.67 | 23.36 | 0.00 | 23.36 | 0.00 | 23.36 |
March | 619.33 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
April | 598.50 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
May | 457.50 | 23.23 | 24.50 | 23.27 | 0.00 | 23.27 |
June | 273.50 | 23.29 | 121.50 | 23.50 | 0.00 | 23.50 |
July | 728.83 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
August | 711.83 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
September | 709.33 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
October | 743.00 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
November | 678.67 | 23.14 | 0.00 | 23.14 | 0.00 | 23.14 |
December | 666.17 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
Annual Sum or Average | 7298.50 | 23.15 | 146.00 | 23.16 | 0.00 | 23.16 |
Minimum of Months | 273.50 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
Maximum of Months | 743.00 | 23.36 | 121.50 | 23.50 | 0.00 | 23.50 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 561.33 | 21.43 | 123.17 | 21.79 | 22.83 | 21.86 |
February | 491.00 | 21.33 | 110.67 | 21.71 | 5.83 | 21.73 |
March | 572.00 | 21.29 | 97.33 | 21.59 | 2.00 | 21.59 |
April | 550.00 | 21.26 | 98.17 | 21.58 | 0.00 | 21.58 |
May | 570.50 | 21.27 | 103.17 | 21.59 | 1.17 | 21.60 |
June | 549.17 | 21.29 | 112.83 | 21.64 | 5.67 | 21.66 |
July | 586.00 | 21.34 | 70.33 | 21.56 | 4.83 | 21.58 |
August | 586.67 | 21.33 | 90.17 | 21.60 | 7.17 | 21.61 |
September | 561.33 | 21.33 | 97.50 | 21.63 | 7.83 | 21.65 |
October | 584.17 | 21.35 | 92.83 | 21.63 | 12.67 | 21.66 |
November | 549.83 | 21.39 | 107.17 | 21.73 | 17.33 | 21.79 |
December | 560.67 | 21.45 | 130.33 | 21.83 | 30.50 | 21.90 |
Annual Sum or Average | 6722.67 | 21.34 | 1233.67 | 21.66 | 117.83 | 21.69 |
Minimum of Months | 491.00 | 21.26 | 70.33 | 21.56 | 0.00 | 21.58 |
Maximum of Months | 586.67 | 21.45 | 130.33 | 21.83 | 30.50 | 21.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 590.83 | 21.47 | 91.67 | 21.72 | 27.50 | 21.79 |
February | 515.67 | 21.40 | 93.00 | 21.70 | 10.67 | 21.73 |
March | 579.17 | 21.31 | 87.17 | 21.57 | 2.50 | 21.58 |
April | 549.00 | 21.26 | 99.83 | 21.58 | 0.00 | 21.58 |
May | 566.00 | 21.26 | 112.67 | 21.61 | 1.50 | 21.62 |
June | 540.17 | 21.27 | 128.17 | 21.67 | 5.67 | 21.69 |
July | 580.83 | 21.33 | 82.00 | 21.59 | 4.83 | 21.61 |
August | 583.83 | 21.32 | 94.67 | 21.60 | 7.00 | 21.62 |
September | 562.50 | 21.33 | 93.33 | 21.62 | 8.00 | 21.65 |
October | 590.67 | 21.36 | 81.50 | 21.61 | 13.00 | 21.64 |
November | 569.17 | 21.44 | 84.17 | 21.69 | 18.67 | 21.75 |
December | 594.50 | 21.51 | 104.67 | 21.78 | 43.00 | 21.86 |
Annual Sum or Average | 6822.33 | 21.36 | 1152.83 | 21.65 | 142.33 | 21.68 |
Minimum of Months | 515.67 | 21.26 | 81.50 | 21.57 | 0.00 | 21.58 |
Maximum of Months | 594.50 | 21.51 | 128.17 | 21.78 | 43.00 | 21.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 545.17 | 21.42 | 118.83 | 21.81 | 10.00 | 21.85 |
February | 494.67 | 21.37 | 70.00 | 21.64 | 2.33 | 21.65 |
March | 597.33 | 21.37 | 1.67 | 21.37 | 1.67 | 21.38 |
April | 586.17 | 21.37 | 0.33 | 21.37 | 0.00 | 21.37 |
May | 607.83 | 21.38 | 2.17 | 21.39 | 1.83 | 21.40 |
June | 585.17 | 21.39 | 4.33 | 21.41 | 3.83 | 21.43 |
July | 626.17 | 21.45 | 3.83 | 21.47 | 3.83 | 21.49 |
August | 626.50 | 21.44 | 7.33 | 21.46 | 7.33 | 21.48 |
September | 590.33 | 21.41 | 8.50 | 21.45 | 8.50 | 21.48 |
October | 605.00 | 21.42 | 14.00 | 21.48 | 10.67 | 21.52 |
November | 552.00 | 21.43 | 62.17 | 21.66 | 15.83 | 21.72 |
December | 543.33 | 21.45 | 125.33 | 21.86 | 17.50 | 21.92 |
Annual Sum or Average | 6959.67 | 21.41 | 418.50 | 21.54 | 83.33 | 21.56 |
Minimum of Months | 494.67 | 21.37 | 0.33 | 21.37 | 0.00 | 21.37 |
Maximum of Months | 626.50 | 21.45 | 125.33 | 21.86 | 17.50 | 21.92 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 729.67 | 23.75 | 0.00 | 23.75 |
February | 0.00 | 0.00 | 672.00 | 23.80 | 0.00 | 23.80 |
March | 4.33 | 22.34 | 737.50 | 23.81 | 0.00 | 23.81 |
April | 0.00 | 0.00 | 720.00 | 23.86 | 0.00 | 23.86 |
May | 4.00 | 22.45 | 733.33 | 23.87 | 0.00 | 23.87 |
June | 0.00 | 0.00 | 718.67 | 23.91 | 0.00 | 23.91 |
July | 0.00 | 0.00 | 742.00 | 23.83 | 0.00 | 23.83 |
August | 9.33 | 23.00 | 717.33 | 23.78 | 3.67 | 23.79 |
September | 0.00 | 0.00 | 699.33 | 23.81 | 0.00 | 23.81 |
October | 3.00 | 22.45 | 700.83 | 23.77 | 0.00 | 23.77 |
November | 0.00 | 0.00 | 703.00 | 23.76 | 0.00 | 23.76 |
December | 0.00 | 0.00 | 712.33 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 20.67 | 22.68 | 8586.00 | 23.81 | 3.67 | 23.81 |
Minimum of Months | 0.00 | 0.00 | 672.00 | 23.75 | 0.00 | 23.75 |
Maximum of Months | 9.33 | 23.00 | 742.00 | 23.91 | 3.67 | 23.91 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 742.67 | 23.78 | 0.00 | 23.78 |
February | 0.00 | 0.00 | 672.00 | 23.84 | 0.00 | 23.84 |
March | 1.83 | 22.39 | 738.17 | 23.86 | 0.00 | 23.86 |
April | 0.00 | 0.00 | 720.00 | 23.90 | 0.00 | 23.90 |
May | 0.00 | 0.00 | 737.50 | 23.90 | 0.00 | 23.90 |
June | 0.00 | 0.00 | 720.00 | 23.94 | 0.00 | 23.94 |
July | 0.00 | 0.00 | 744.00 | 23.87 | 0.00 | 23.87 |
August | 1.67 | 22.40 | 736.83 | 23.82 | 0.00 | 23.82 |
September | 0.00 | 0.00 | 720.00 | 23.83 | 0.00 | 23.83 |
October | 0.00 | 0.00 | 729.50 | 23.80 | 0.00 | 23.80 |
November | 0.00 | 0.00 | 719.17 | 23.79 | 0.00 | 23.79 |
December | 0.00 | 0.00 | 742.33 | 23.78 | 0.00 | 23.78 |
Annual Sum or Average | 3.50 | 22.39 | 8722.17 | 23.84 | 0.00 | 23.84 |
Minimum of Months | 0.00 | 0.00 | 672.00 | 23.78 | 0.00 | 23.78 |
Maximum of Months | 1.83 | 22.40 | 744.00 | 23.94 | 0.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 557.00 | 23.98 | 743.83 | 23.78 | 557.00 | 23.84 |
February | 506.50 | 23.98 | 672.00 | 23.79 | 506.50 | 23.85 |
March | 563.17 | 23.98 | 743.83 | 23.80 | 563.17 | 23.86 |
April | 549.67 | 23.98 | 720.00 | 23.82 | 549.67 | 23.87 |
May | 565.83 | 23.98 | 743.83 | 23.81 | 565.83 | 23.86 |
June | 550.00 | 23.98 | 719.67 | 23.82 | 550.00 | 23.87 |
July | 561.67 | 23.98 | 744.00 | 23.80 | 561.67 | 23.85 |
August | 559.83 | 23.98 | 741.83 | 23.80 | 559.83 | 23.85 |
September | 543.50 | 23.98 | 717.83 | 23.80 | 543.50 | 23.86 |
October | 555.83 | 23.98 | 740.83 | 23.79 | 555.83 | 23.85 |
November | 540.67 | 23.98 | 719.67 | 23.78 | 540.67 | 23.84 |
December | 556.17 | 23.98 | 742.83 | 23.77 | 556.17 | 23.83 |
Annual Sum or Average | 6609.83 | 23.98 | 8750.17 | 23.80 | 6609.83 | 23.85 |
Minimum of Months | 506.50 | 23.98 | 672.00 | 23.77 | 506.50 | 23.83 |
Maximum of Months | 565.83 | 23.98 | 744.00 | 23.82 | 565.83 | 23.87 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 289.33 | 22.81 | 258.17 | 23.33 | 0.00 | 23.33 |
February | 193.50 | 22.94 | 328.50 | 23.56 | 0.00 | 23.56 |
March | 206.50 | 22.94 | 337.00 | 23.55 | 0.00 | 23.55 |
April | 139.67 | 22.96 | 348.00 | 23.65 | 0.00 | 23.65 |
May | 183.33 | 22.86 | 344.00 | 23.55 | 0.00 | 23.55 |
June | 117.67 | 22.97 | 388.33 | 23.70 | 0.00 | 23.70 |
July | 292.17 | 22.89 | 176.50 | 23.25 | 0.00 | 23.25 |
August | 393.17 | 22.71 | 163.33 | 23.06 | 0.00 | 23.06 |
September | 331.33 | 22.80 | 197.67 | 23.21 | 0.00 | 23.21 |
October | 403.83 | 22.74 | 132.00 | 23.01 | 0.00 | 23.01 |
November | 314.83 | 22.79 | 207.00 | 23.22 | 0.00 | 23.22 |
December | 336.17 | 22.75 | 204.50 | 23.19 | 0.00 | 23.19 |
Annual Sum or Average | 3201.50 | 22.82 | 3085.00 | 23.35 | 0.00 | 23.35 |
Minimum of Months | 117.67 | 22.71 | 132.00 | 23.01 | 0.00 | 23.01 |
Maximum of Months | 403.83 | 22.97 | 388.33 | 23.70 | 0.00 | 23.70 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.18705 | 52.47058 | 0.27589 | 6.66603 |
February | 672.00000 | 23.28946 | 52.14087 | 0.30094 | 6.93602 |
March | 744.00000 | 23.20562 | 52.29205 | 0.27968 | 6.68258 |
April | 720.00000 | 23.22069 | 52.26142 | 0.28224 | 6.73622 |
May | 744.00000 | 23.32031 | 51.99425 | -0.6472 | 13.91747 |
June | 720.00000 | 23.46265 | 51.56233 | -0.5979 | 12.61556 |
July | 744.00000 | 23.36763 | 51.84926 | -0.6314 | 13.46969 |
August | 744.00000 | 23.28305 | 52.17775 | -0.6607 | 14.33662 |
September | 720.00000 | 23.28845 | 52.27275 | -0.6564 | 14.22560 |
October | 744.00000 | 23.13830 | 52.63523 | 0.26369 | 6.51264 |
November | 720.00000 | 23.22733 | 52.36862 | 0.28562 | 6.76220 |
December | 744.00000 | 23.24174 | 52.42465 | 0.28989 | 6.81219 |
Annual Sum or Average | 8760.00000 | 23.26886 | 52.20563 | -0.1038 | 9.65674 |
Minimum of Months | 672.00000 | 23.13830 | 51.56233 | -0.6607 | 6.51264 |
Maximum of Months | 744.00000 | 23.46265 | 52.63523 | 0.30094 | 14.33662 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.50958 | 52.86704 | 0.51152 | 11.20471 |
February | 672.00000 | 23.64605 | 52.43822 | 0.54827 | 11.77655 |
March | 744.00000 | 23.59806 | 52.79803 | 0.52558 | 11.21998 |
April | 720.00000 | 23.53972 | 53.72736 | 0.50606 | 10.81369 |
May | 744.00000 | 23.44597 | 54.65068 | -0.4051 | 9.55591 |
June | 720.00000 | 23.53971 | 54.26932 | -0.3678 | 8.66675 |
July | 744.00000 | 23.27896 | 54.48579 | -0.4814 | 10.74018 |
August | 744.00000 | 23.13530 | 55.68013 | -0.5268 | 12.30777 |
September | 720.00000 | 23.32458 | 55.00332 | -0.4522 | 10.59094 |
October | 744.00000 | 23.23737 | 55.07456 | 0.42691 | 9.59408 |
November | 720.00000 | 23.42967 | 53.92375 | 0.48416 | 10.59991 |
December | 744.00000 | 23.45947 | 53.41346 | 0.49746 | 10.95128 |
Annual Sum or Average | 8760.00000 | 23.42659 | 54.03847 | 0.10261 | 10.66486 |
Minimum of Months | 672.00000 | 23.13530 | 52.43822 | -0.5268 | 8.66675 |
Maximum of Months | 744.00000 | 23.64605 | 55.68013 | 0.54827 | 12.30777 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.12688 | 54.34842 | 0.33005 | 7.54223 |
February | 672.00000 | 23.33580 | 53.70038 | 0.38341 | 8.25361 |
March | 744.00000 | 23.35276 | 53.63112 | 0.38788 | 8.37016 |
April | 720.00000 | 23.36070 | 53.90513 | 0.39100 | 8.46302 |
May | 744.00000 | 23.28887 | 54.42906 | -0.5575 | 12.11001 |
June | 720.00000 | 23.40815 | 53.98686 | -0.5120 | 10.99119 |
July | 744.00000 | 23.16935 | 54.44049 | -0.6038 | 13.13966 |
August | 744.00000 | 23.06301 | 55.15156 | -0.6389 | 14.40971 |
September | 720.00000 | 23.14271 | 54.96320 | -0.6087 | 13.48652 |
October | 744.00000 | 22.97980 | 55.34099 | 0.29600 | 7.14228 |
November | 720.00000 | 23.07951 | 54.83879 | 0.32016 | 7.39637 |
December | 744.00000 | 23.08518 | 54.70599 | 0.32109 | 7.39130 |
Annual Sum or Average | 8760.00000 | 23.19774 | 54.46002 | -0.0438 | 9.90269 |
Minimum of Months | 672.00000 | 22.97980 | 53.63112 | -0.6389 | 7.14228 |
Maximum of Months | 744.00000 | 23.40815 | 55.34099 | 0.39100 | 14.40971 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.17835 | 52.95436 | 0.68212 | 16.82002 |
February | 672.00000 | 22.25584 | 52.67153 | 0.71907 | 17.84947 |
March | 744.00000 | 22.27908 | 52.52941 | 0.72982 | 18.22328 |
April | 720.00000 | 22.31151 | 52.54511 | 0.74388 | 18.63078 |
May | 744.00000 | 22.28589 | 52.72854 | -0.0340 | 9.28081 |
June | 720.00000 | 22.33068 | 52.54785 | -0.0001 | 9.15769 |
July | 744.00000 | 22.20986 | 52.84897 | -0.0754 | 9.35658 |
August | 744.00000 | 22.19717 | 53.07063 | -0.0933 | 9.52906 |
September | 720.00000 | 22.21221 | 53.12017 | -0.0768 | 9.37967 |
October | 744.00000 | 22.14145 | 53.26925 | 0.66396 | 16.34997 |
November | 720.00000 | 22.18258 | 53.06307 | 0.68165 | 16.79014 |
December | 744.00000 | 22.15665 | 53.17870 | 0.67275 | 16.53988 |
Annual Sum or Average | 8760.00000 | 22.22788 | 52.87963 | 0.38224 | 13.96609 |
Minimum of Months | 672.00000 | 22.14145 | 52.52941 | -0.0933 | 9.15769 |
Maximum of Months | 744.00000 | 22.33068 | 53.26925 | 0.74388 | 18.63078 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76509 | 57.81282 | 0.63051 | 13.64957 |
February | 672.00000 | 23.83696 | 57.57534 | 0.64975 | 14.03426 |
March | 744.00000 | 23.69865 | 58.16082 | 0.60345 | 12.89005 |
April | 720.00000 | 23.56329 | 59.00151 | 0.56425 | 11.96114 |
May | 744.00000 | 23.52256 | 59.48728 | -0.3191 | 7.81629 |
June | 720.00000 | 23.56000 | 59.27482 | -0.3012 | 7.41836 |
July | 744.00000 | 23.38820 | 59.66393 | -0.3821 | 8.67965 |
August | 744.00000 | 23.30496 | 60.36785 | -0.4127 | 9.48221 |
September | 720.00000 | 23.45758 | 59.84880 | -0.3470 | 8.21937 |
October | 744.00000 | 23.46862 | 59.70607 | 0.53601 | 11.43213 |
November | 720.00000 | 23.68586 | 58.63909 | 0.60148 | 12.88893 |
December | 744.00000 | 23.74563 | 58.22910 | 0.62324 | 13.45617 |
Annual Sum or Average | 8760.00000 | 23.58121 | 58.98986 | 0.20103 | 10.97858 |
Minimum of Months | 672.00000 | 23.30496 | 57.57534 | -0.4127 | 7.41836 |
Maximum of Months | 744.00000 | 23.83696 | 60.36785 | 0.64975 | 14.03426 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.48487 | 57.42170 | 0.44653 | 9.36372 |
February | 672.00000 | 23.59654 | 57.03496 | 0.47720 | 9.89522 |
March | 744.00000 | 23.53538 | 57.22876 | 0.46063 | 9.63718 |
April | 720.00000 | 23.53546 | 57.47745 | 0.46207 | 9.69906 |
May | 744.00000 | 23.57189 | 57.53430 | -0.4264 | 9.23352 |
June | 720.00000 | 23.66171 | 57.03648 | -0.3871 | 8.45951 |
July | 744.00000 | 23.50653 | 57.50328 | -0.4558 | 9.77055 |
August | 744.00000 | 23.37340 | 58.34635 | -0.5049 | 10.97594 |
September | 720.00000 | 23.41867 | 58.28458 | -0.4865 | 10.50197 |
October | 744.00000 | 23.33725 | 58.46017 | 0.40968 | 8.78042 |
November | 720.00000 | 23.45560 | 57.86663 | 0.44053 | 9.26450 |
December | 744.00000 | 23.46924 | 57.72407 | 0.44344 | 9.29126 |
Annual Sum or Average | 8760.00000 | 23.49447 | 57.66496 | 0.07068 | 9.57109 |
Minimum of Months | 672.00000 | 23.33725 | 57.03496 | -0.5049 | 8.45951 |
Maximum of Months | 744.00000 | 23.66171 | 58.46017 | 0.47720 | 10.97594 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.91384 | 55.43571 | 0.06477 | 6.03822 |
February | 672.00000 | 21.88868 | 54.73179 | 0.06827 | 6.01783 |
March | 744.00000 | 21.75623 | 54.55526 | 0.03842 | 5.82761 |
April | 720.00000 | 21.74241 | 55.62979 | 0.03951 | 5.86706 |
May | 744.00000 | 21.75024 | 56.93253 | -1.0220 | 28.49288 |
June | 720.00000 | 21.76828 | 56.77881 | -1.0065 | 27.87888 |
July | 744.00000 | 21.76182 | 56.46744 | -1.0468 | 29.53530 |
August | 744.00000 | 21.74636 | 57.80554 | -1.0461 | 29.51622 |
September | 720.00000 | 21.76127 | 57.44702 | -1.0357 | 29.12905 |
October | 744.00000 | 21.77393 | 57.44087 | 0.02886 | 5.87367 |
November | 720.00000 | 21.85909 | 56.40029 | 0.05051 | 5.98983 |
December | 744.00000 | 21.93604 | 56.10393 | 0.06724 | 6.07571 |
Annual Sum or Average | 8760.00000 | 21.80440 | 56.32095 | -0.4028 | 15.57970 |
Minimum of Months | 672.00000 | 21.74241 | 54.55526 | -1.0468 | 5.82761 |
Maximum of Months | 744.00000 | 21.93604 | 57.80554 | 0.06827 | 29.53530 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.87632 | 56.11669 | 0.03659 | 5.87473 |
February | 672.00000 | 21.86613 | 55.23180 | 0.04723 | 5.90241 |
March | 744.00000 | 21.75119 | 54.84717 | 0.03031 | 5.79826 |
April | 720.00000 | 21.74296 | 55.60624 | 0.04069 | 5.86990 |
May | 744.00000 | 21.75368 | 56.76799 | -1.0126 | 28.13223 |
June | 720.00000 | 21.77441 | 56.38684 | -0.9897 | 27.24111 |
July | 744.00000 | 21.76774 | 56.13059 | -1.0362 | 29.11743 |
August | 744.00000 | 21.74869 | 57.63581 | -1.0415 | 29.32990 |
September | 720.00000 | 21.75970 | 57.57885 | -1.0388 | 29.24824 |
October | 744.00000 | 21.76689 | 57.92616 | 0.02127 | 5.84763 |
November | 720.00000 | 21.83974 | 57.01857 | 0.03268 | 5.90404 |
December | 744.00000 | 21.89587 | 56.95592 | 0.03900 | 5.90564 |
Annual Sum or Average | 8760.00000 | 21.79487 | 56.52602 | -0.4087 | 15.40643 |
Minimum of Months | 672.00000 | 21.74296 | 54.84717 | -1.0415 | 5.79826 |
Maximum of Months | 744.00000 | 21.89587 | 57.92616 | 0.04723 | 29.32990 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70457 | 56.68968 | -0.0855 | 5.60341 |
February | 672.00000 | 21.72400 | 56.08142 | -0.0782 | 5.62390 |
March | 744.00000 | 21.61966 | 55.32341 | -0.1020 | 5.64562 |
April | 720.00000 | 21.63934 | 55.69560 | -0.0888 | 5.69503 |
May | 744.00000 | 21.68009 | 56.26663 | -1.1729 | 34.82453 |
June | 720.00000 | 21.72392 | 56.35190 | -1.1439 | 33.58589 |
July | 744.00000 | 21.68629 | 55.52565 | -1.1819 | 35.22805 |
August | 744.00000 | 21.62861 | 56.77074 | -1.2051 | 36.20460 |
September | 720.00000 | 21.62420 | 56.91816 | -1.2097 | 36.42130 |
October | 744.00000 | 21.60567 | 57.16121 | -0.1006 | 5.64472 |
November | 720.00000 | 21.67413 | 56.92105 | -0.0879 | 5.63693 |
December | 744.00000 | 21.72001 | 57.31201 | -0.0807 | 5.60250 |
Annual Sum or Average | 8760.00000 | 21.66880 | 56.42030 | -0.5477 | 18.05206 |
Minimum of Months | 672.00000 | 21.60567 | 55.32341 | -1.2097 | 5.60250 |
Maximum of Months | 744.00000 | 21.72400 | 57.31201 | -0.0782 | 36.42130 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.97597 | 55.24994 | 0.07830 | 6.29650 |
February | 672.00000 | 21.94237 | 54.56171 | 0.08152 | 6.24640 |
March | 744.00000 | 21.77147 | 54.61981 | 0.04267 | 5.85822 |
April | 720.00000 | 21.75491 | 55.61856 | 0.04430 | 5.88611 |
May | 744.00000 | 21.75945 | 57.02204 | -1.0156 | 28.24500 |
June | 720.00000 | 21.77983 | 56.72776 | -1.0009 | 27.67013 |
July | 744.00000 | 21.77480 | 56.56778 | -1.0409 | 29.30937 |
August | 744.00000 | 21.76026 | 57.81387 | -1.0396 | 29.27231 |
September | 720.00000 | 21.77254 | 57.41711 | -1.0293 | 28.87748 |
October | 744.00000 | 21.78653 | 57.51496 | 0.03301 | 5.89645 |
November | 720.00000 | 21.88172 | 56.53414 | 0.05731 | 6.05271 |
December | 744.00000 | 21.99088 | 56.07133 | 0.07991 | 6.29761 |
Annual Sum or Average | 8760.00000 | 21.82865 | 56.32139 | -0.3954 | 15.55050 |
Minimum of Months | 672.00000 | 21.75491 | 54.56171 | -1.0409 | 5.85822 |
Maximum of Months | 744.00000 | 21.99088 | 57.81387 | 0.08152 | 29.30937 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.94350 | 56.39440 | 0.05433 | 6.11028 |
February | 672.00000 | 21.92352 | 55.41181 | 0.06366 | 6.11657 |
March | 744.00000 | 21.76848 | 54.98558 | 0.03561 | 5.83310 |
April | 720.00000 | 21.75512 | 55.58124 | 0.04528 | 5.88868 |
May | 744.00000 | 21.76166 | 56.78465 | -1.0072 | 27.91967 |
June | 720.00000 | 21.78404 | 56.42101 | -0.9845 | 27.04002 |
July | 744.00000 | 21.77905 | 56.21779 | -1.0310 | 28.92076 |
August | 744.00000 | 21.76173 | 57.65560 | -1.0352 | 29.09617 |
September | 720.00000 | 21.77127 | 57.57740 | -1.0321 | 28.98583 |
October | 744.00000 | 21.78139 | 58.03312 | 0.02613 | 5.87224 |
November | 720.00000 | 21.86537 | 57.40420 | 0.04192 | 5.97004 |
December | 744.00000 | 21.95497 | 57.26736 | 0.05499 | 6.10803 |
Annual Sum or Average | 8760.00000 | 21.82029 | 56.65353 | -0.4002 | 15.37937 |
Minimum of Months | 672.00000 | 21.75512 | 54.98558 | -1.0352 | 5.83310 |
Maximum of Months | 744.00000 | 21.95497 | 58.03312 | 0.06366 | 29.09617 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.89332 | 56.08238 | 0.07087 | 6.31946 |
February | 672.00000 | 21.87081 | 55.34161 | 0.07395 | 6.31412 |
March | 744.00000 | 21.75376 | 54.97419 | 0.05004 | 6.11555 |
April | 720.00000 | 21.74406 | 55.80730 | 0.05373 | 6.14607 |
May | 744.00000 | 21.74989 | 57.22260 | -1.0073 | 28.31676 |
June | 720.00000 | 21.76708 | 56.98004 | -0.9944 | 27.83406 |
July | 744.00000 | 21.76026 | 56.96650 | -1.0331 | 29.36874 |
August | 744.00000 | 21.74736 | 58.25762 | -1.0309 | 29.26817 |
September | 720.00000 | 21.76440 | 57.68495 | -1.0181 | 28.82816 |
October | 744.00000 | 21.77436 | 57.93335 | 0.03947 | 6.09858 |
November | 720.00000 | 21.85535 | 56.87401 | 0.05916 | 6.24567 |
December | 744.00000 | 21.91708 | 56.85824 | 0.07296 | 6.34424 |
Annual Sum or Average | 8760.00000 | 21.79941 | 56.75917 | -0.3915 | 15.65806 |
Minimum of Months | 672.00000 | 21.74406 | 54.97419 | -1.0331 | 6.09858 |
Maximum of Months | 744.00000 | 21.91708 | 58.25762 | 0.07395 | 29.36874 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.85504 | 56.90050 | 0.04259 | 6.09072 |
February | 672.00000 | 21.84850 | 55.83008 | 0.05261 | 6.14440 |
March | 744.00000 | 21.74907 | 55.27064 | 0.04217 | 6.06259 |
April | 720.00000 | 21.74459 | 55.78248 | 0.05495 | 6.14958 |
May | 744.00000 | 21.75331 | 57.02363 | -0.9980 | 27.98451 |
June | 720.00000 | 21.77388 | 56.62075 | -0.9770 | 27.22301 |
July | 744.00000 | 21.76642 | 56.59793 | -1.0224 | 28.97797 |
August | 744.00000 | 21.74976 | 58.09157 | -1.0261 | 29.08778 |
September | 720.00000 | 21.76296 | 57.83093 | -1.0210 | 28.93073 |
October | 744.00000 | 21.76771 | 58.47000 | 0.03214 | 6.05211 |
November | 720.00000 | 21.83642 | 57.65190 | 0.04191 | 6.11989 |
December | 744.00000 | 21.87618 | 57.90532 | 0.04484 | 6.11455 |
Annual Sum or Average | 8760.00000 | 21.78996 | 57.00787 | -0.3972 | 15.46909 |
Minimum of Months | 672.00000 | 21.74459 | 55.27064 | -1.0261 | 6.05211 |
Maximum of Months | 744.00000 | 21.87618 | 58.47000 | 0.05495 | 29.08778 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.95666 | 55.60770 | 0.07424 | 6.47680 |
February | 672.00000 | 21.90533 | 55.08555 | 0.05819 | 6.28137 |
March | 744.00000 | 21.75453 | 55.01559 | 0.00649 | 5.94076 |
April | 720.00000 | 21.73437 | 56.24937 | -0.0027 | 5.93313 |
May | 744.00000 | 21.74155 | 57.24723 | -1.0778 | 31.04985 |
June | 720.00000 | 21.75792 | 57.30622 | -1.0707 | 30.77208 |
July | 744.00000 | 21.75143 | 56.86278 | -1.0967 | 31.87860 |
August | 744.00000 | 21.73729 | 58.11218 | -1.0984 | 31.94457 |
September | 720.00000 | 21.75954 | 57.48042 | -1.0773 | 31.14877 |
October | 744.00000 | 21.78150 | 57.05019 | 0.01016 | 6.01728 |
November | 720.00000 | 21.88358 | 56.09959 | 0.04730 | 6.25093 |
December | 744.00000 | 21.98491 | 56.14830 | 0.08012 | 6.52621 |
Annual Sum or Average | 8760.00000 | 21.81193 | 56.53103 | -0.4319 | 16.75036 |
Minimum of Months | 672.00000 | 21.73437 | 55.01559 | -1.0984 | 5.93313 |
Maximum of Months | 744.00000 | 21.98491 | 58.11218 | 0.08012 | 31.94457 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.72744 | 57.47800 | 0.58839 | 12.41563 |
February | 672.00000 | 23.79514 | 57.12685 | 0.61282 | 12.98791 |
March | 744.00000 | 23.80742 | 56.88275 | 0.62169 | 13.24488 |
April | 720.00000 | 23.86283 | 56.70372 | 0.64347 | 13.80145 |
May | 744.00000 | 23.85755 | 56.74805 | -0.1844 | 5.96244 |
June | 720.00000 | 23.91113 | 56.39763 | -0.1527 | 5.62636 |
July | 744.00000 | 23.82731 | 56.87154 | -0.2092 | 6.11206 |
August | 744.00000 | 23.75430 | 57.42512 | -0.2452 | 6.61428 |
September | 720.00000 | 23.77877 | 57.46913 | -0.2342 | 6.43704 |
October | 744.00000 | 23.71829 | 57.72546 | 0.58798 | 12.46066 |
November | 720.00000 | 23.73781 | 57.58547 | 0.59249 | 12.51994 |
December | 744.00000 | 23.71620 | 57.77868 | 0.58262 | 12.28296 |
Annual Sum or Average | 8760.00000 | 23.79081 | 57.18473 | 0.26474 | 10.01941 |
Minimum of Months | 672.00000 | 23.71620 | 56.39763 | -0.2452 | 5.62636 |
Maximum of Months | 744.00000 | 23.91113 | 57.77868 | 0.64347 | 13.80145 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.78016 | 56.84243 | 0.62403 | 13.29320 |
February | 672.00000 | 23.83873 | 56.53253 | 0.64590 | 13.84414 |
March | 744.00000 | 23.85055 | 56.29427 | 0.65514 | 14.11890 |
April | 720.00000 | 23.89998 | 56.13265 | 0.67577 | 14.68184 |
May | 744.00000 | 23.89168 | 56.17819 | -0.1380 | 5.59577 |
June | 720.00000 | 23.93865 | 55.86471 | -0.1087 | 5.36087 |
July | 744.00000 | 23.87447 | 56.24299 | -0.1571 | 5.66261 |
August | 744.00000 | 23.81348 | 56.73903 | -0.1885 | 6.00265 |
September | 720.00000 | 23.83230 | 56.80662 | -0.1803 | 5.89572 |
October | 744.00000 | 23.77817 | 57.03005 | 0.62685 | 13.40830 |
November | 720.00000 | 23.79325 | 56.92122 | 0.62951 | 13.43599 |
December | 744.00000 | 23.77292 | 57.11276 | 0.61966 | 13.18553 |
Annual Sum or Average | 8760.00000 | 23.83840 | 56.55972 | 0.30652 | 10.35108 |
Minimum of Months | 672.00000 | 23.77292 | 55.86471 | -0.1885 | 5.36087 |
Maximum of Months | 744.00000 | 23.93865 | 57.11276 | 0.67577 | 14.68184 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.62195 | 56.23206 | 1.23889 | 39.56531 |
February | 672.00000 | 23.64921 | 56.01935 | 1.26107 | 40.50761 |
March | 744.00000 | 23.66733 | 55.86985 | 1.26768 | 40.71871 |
April | 720.00000 | 23.68954 | 55.85145 | 1.28249 | 41.34385 |
May | 744.00000 | 23.68588 | 55.99935 | 0.71732 | 21.78879 |
June | 720.00000 | 23.69975 | 55.86565 | 0.73719 | 22.31671 |
July | 744.00000 | 23.66018 | 56.05346 | 0.68845 | 21.06826 |
August | 744.00000 | 23.64901 | 56.30312 | 0.67168 | 20.69054 |
September | 720.00000 | 23.66267 | 56.30776 | 0.69002 | 21.12060 |
October | 744.00000 | 23.63228 | 56.42786 | 1.23051 | 39.02687 |
November | 720.00000 | 23.62873 | 56.33490 | 1.23733 | 39.39557 |
December | 744.00000 | 23.60863 | 56.46476 | 1.23041 | 39.22073 |
Annual Sum or Average | 8760.00000 | 23.65447 | 56.14575 | 1.01949 | 32.17526 |
Minimum of Months | 672.00000 | 23.60863 | 55.85145 | 0.67168 | 20.69054 |
Maximum of Months | 744.00000 | 23.69975 | 56.46476 | 1.28249 | 41.34385 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.86822 | 53.18783 | 0.20655 | 5.96602 |
February | 672.00000 | 23.13856 | 52.39603 | 0.27132 | 6.57051 |
March | 744.00000 | 23.20665 | 52.30955 | 0.28780 | 6.81237 |
April | 720.00000 | 23.43716 | 52.28646 | 0.34599 | 7.61396 |
May | 744.00000 | 23.62179 | 52.20649 | -0.5230 | 11.06277 |
June | 720.00000 | 23.80285 | 51.39456 | -0.4522 | 9.45907 |
July | 744.00000 | 23.55042 | 51.68222 | -0.5549 | 11.63931 |
August | 744.00000 | 23.21827 | 53.48075 | -0.6626 | 14.79945 |
September | 720.00000 | 23.15738 | 53.66418 | -0.6822 | 15.15876 |
October | 744.00000 | 22.88913 | 54.28920 | 0.21901 | 6.12606 |
November | 720.00000 | 22.94065 | 53.71222 | 0.22886 | 6.17569 |
December | 744.00000 | 22.82617 | 53.68705 | 0.19919 | 5.90116 |
Annual Sum or Average | 8760.00000 | 23.22088 | 52.86287 | -0.0955 | 8.95266 |
Minimum of Months | 672.00000 | 22.82617 | 51.39456 | -0.6822 | 5.90116 |
Maximum of Months | 744.00000 | 23.80285 | 54.28920 | 0.34599 | 15.15876 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.23214 | 55.22155 | 0.25610 | 6.45407 |
February | 672.00000 | 23.44792 | 54.62351 | 0.30792 | 6.99472 |
March | 744.00000 | 23.31970 | 55.03098 | 0.27741 | 6.63451 |
April | 720.00000 | 23.29938 | 55.49982 | 0.27392 | 6.62276 |
May | 744.00000 | 23.40420 | 55.56186 | -0.6654 | 14.47495 |
June | 720.00000 | 23.58492 | 54.96050 | -0.6037 | 12.82225 |
July | 744.00000 | 23.15874 | 55.75619 | -0.7515 | 16.95947 |
August | 744.00000 | 23.01056 | 56.70595 | -0.7981 | 18.62868 |
September | 720.00000 | 23.01594 | 56.72612 | -0.7948 | 18.51206 |
October | 744.00000 | 22.98722 | 56.63577 | 0.20248 | 5.91127 |
November | 720.00000 | 23.16266 | 55.86833 | 0.24269 | 6.28079 |
December | 744.00000 | 23.19298 | 55.59299 | 0.24865 | 6.35648 |
Annual Sum or Average | 8760.00000 | 23.23260 | 55.68977 | -0.1534 | 10.57806 |
Minimum of Months | 672.00000 | 22.98722 | 54.62351 | -0.7981 | 5.91127 |
Maximum of Months | 744.00000 | 23.58492 | 56.72612 | 0.30792 | 18.62868 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.36758 | 52.23226 | 0.33973 | 7.72106 |
February | 672.00000 | 23.53777 | 51.72677 | 0.38192 | 8.28013 |
March | 744.00000 | 23.52543 | 51.77545 | 0.37971 | 8.24251 |
April | 720.00000 | 23.57711 | 51.95050 | 0.39470 | 8.47498 |
May | 744.00000 | 23.51739 | 52.41243 | -0.5419 | 11.71305 |
June | 720.00000 | 23.62853 | 51.98815 | -0.5010 | 10.64645 |
July | 744.00000 | 23.32385 | 52.63290 | -0.6165 | 13.40542 |
August | 744.00000 | 23.14433 | 53.61650 | -0.6753 | 15.40942 |
September | 720.00000 | 23.27139 | 53.27182 | -0.6296 | 14.01199 |
October | 744.00000 | 23.13240 | 53.55441 | 0.28579 | 7.02033 |
November | 720.00000 | 23.27785 | 52.88989 | 0.32010 | 7.45862 |
December | 744.00000 | 23.26511 | 52.78006 | 0.31597 | 7.42557 |
Annual Sum or Average | 8760.00000 | 23.37880 | 52.57667 | -0.0484 | 9.99634 |
Minimum of Months | 672.00000 | 23.13240 | 51.72677 | -0.6753 | 7.02033 |
Maximum of Months | 744.00000 | 23.62853 | 53.61650 | 0.39470 | 15.40942 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.03478 | 52.59223 | 0.24200 | 6.32486 |
February | 672.00000 | 23.31432 | 51.78326 | 0.30896 | 7.05450 |
March | 744.00000 | 23.37862 | 51.71044 | 0.32481 | 7.31413 |
April | 720.00000 | 23.57356 | 51.78019 | 0.37637 | 8.07740 |
May | 744.00000 | 23.70858 | 51.81867 | -0.4930 | 10.38385 |
June | 720.00000 | 23.86228 | 51.05072 | -0.4287 | 8.98825 |
July | 744.00000 | 23.66885 | 51.18634 | -0.5153 | 10.74232 |
August | 744.00000 | 23.36600 | 52.96305 | -0.6159 | 13.52283 |
September | 720.00000 | 23.33036 | 53.10338 | -0.6288 | 13.72969 |
October | 744.00000 | 23.06240 | 53.73553 | 0.25637 | 6.52951 |
November | 720.00000 | 23.11441 | 53.13548 | 0.26621 | 6.58588 |
December | 744.00000 | 22.99608 | 53.09229 | 0.23563 | 6.25645 |
Annual Sum or Average | 8760.00000 | 23.36683 | 52.33446 | -0.0584 | 8.80070 |
Minimum of Months | 672.00000 | 22.99608 | 51.05072 | -0.6288 | 6.25645 |
Maximum of Months | 744.00000 | 23.86228 | 53.73553 | 0.37637 | 13.72969 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.378125E+12 | 205379.22 | 04-JAN-16:03 | 744.00 | 0.126212E+13 | 0.00 | 0.164025E+13 | 3.35 | 4.11 | 08-JAN-09:53 | 0.00 | 0.00 |
February | 0.355930E+12 | 225174.03 | 13-FEB-16:05 | 672.00 | 0.116402E+13 | 0.00 | 0.151995E+13 | 3.28 | 3.81 | 03-FEB-06:05 | 0.00 | 0.00 |
March | 0.411427E+12 | 229798.85 | 28-MAR-15:03 | 744.00 | 0.133327E+13 | 0.00 | 0.174469E+13 | 3.25 | 3.92 | 14-MAR-23:00 | 0.00 | 0.00 |
April | 0.441202E+12 | 246251.16 | 02-APR-15:03 | 720.00 | 0.143883E+13 | 0.00 | 0.188003E+13 | 3.27 | 3.82 | 14-APR-16:00 | 0.00 | 0.00 |
May | 0.486793E+12 | 263421.81 | 06-MAY-15:03 | 744.00 | 0.161718E+13 | 0.00 | 0.210397E+13 | 3.34 | 4.00 | 10-MAY-19:50 | 0.00 | 0.00 |
June | 0.475921E+12 | 277356.04 | 13-JUN-15:03 | 720.00 | 0.158944E+13 | 0.00 | 0.206536E+13 | 3.36 | 4.08 | 25-JUN-21:53 | 0.00 | 0.00 |
July | 0.411366E+12 | 226070.66 | 20-JUL-15:03 | 744.00 | 0.138363E+13 | 0.00 | 0.179499E+13 | 3.37 | 4.05 | 19-JUL-21:52 | 0.00 | 0.00 |
August | 0.447149E+12 | 252518.32 | 13-AUG-15:03 | 744.00 | 0.152270E+13 | 0.00 | 0.196985E+13 | 3.42 | 3.95 | 23-AUG-21:00 | 0.00 | 0.00 |
September | 0.426998E+12 | 237755.60 | 08-SEP-18:03 | 720.00 | 0.144886E+13 | 0.00 | 0.187586E+13 | 3.41 | 4.08 | 15-SEP-21:52 | 0.00 | 0.00 |
October | 0.420405E+12 | 230734.56 | 16-OCT-15:05 | 744.00 | 0.144027E+13 | 0.00 | 0.186067E+13 | 3.43 | 3.92 | 30-OCT-20:43 | 0.00 | 0.00 |
November | 0.393937E+12 | 234178.46 | 17-NOV-19:03 | 720.00 | 0.134325E+13 | 0.00 | 0.173718E+13 | 3.42 | 4.05 | 25-NOV-22:53 | 0.00 | 0.00 |
December | 0.387786E+12 | 222825.31 | 29-DEC-19:03 | 744.00 | 0.132952E+13 | 0.00 | 0.171731E+13 | 3.44 | 3.99 | 15-DEC-22:52 | 0.00 | 0.00 |
Annual Sum or Average | 0.503704E+13 | 8760.00 | 0.168731E+14 | 0.00 | 0.219101E+14 | 3.36 | 0.00 | 0.00 | ||||
Minimum of Months | 0.355930E+12 | 205379.22 | 672.00 | 0.116402E+13 | 0.00 | 0.151995E+13 | 3.25 | 3.81 | 0.00 | 0.00 | ||
Maximum of Months | 0.486793E+12 | 277356.04 | 744.00 | 0.161718E+13 | 0.00 | 0.210397E+13 | 3.44 | 4.11 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.125325E+10 | 0.00 | 167.93 | 24149.38 | 11-JAN-09:05 | 0.00 | 30.64 | 37.41 | 0.00 | 0.00 | 0.00 | 0.09 | 11-JAN-09:05 |
February | 0.947787E+09 | 0.00 | 125.87 | 22391.90 | 24-FEB-09:15 | 0.00 | 30.25 | 35.90 | 0.00 | 0.00 | 0.00 | 0.08 | 24-FEB-09:15 |
March | 0.103737E+10 | 0.00 | 140.39 | 24728.46 | 13-MAR-08:05 | 0.00 | 29.99 | 35.74 | 0.00 | 0.00 | 0.00 | 0.09 | 13-MAR-08:05 |
April | 0.885112E+09 | 0.00 | 122.54 | 23074.23 | 21-APR-08:05 | 0.00 | 29.54 | 34.80 | 0.00 | 0.00 | 0.00 | 0.09 | 21-APR-08:05 |
May | 0.103062E+10 | 0.00 | 136.45 | 29596.27 | 17-MAY-08:05 | 0.00 | 29.35 | 35.04 | 0.00 | 0.00 | 0.00 | 0.11 | 17-MAY-08:05 |
June | 0.856737E+09 | 0.00 | 121.32 | 18967.54 | 30-JUN-18:07 | 0.00 | 28.55 | 33.93 | 0.00 | 0.00 | 0.00 | 0.07 | 30-JUN-18:07 |
July | 0.103959E+10 | 0.00 | 146.39 | 29457.35 | 11-JUL-08:05 | 0.00 | 30.12 | 36.09 | 0.00 | 0.00 | 0.00 | 0.11 | 11-JUL-08:05 |
August | 0.125189E+10 | 0.00 | 156.97 | 26873.66 | 21-AUG-08:05 | 0.00 | 30.28 | 36.62 | 0.00 | 0.00 | 0.00 | 0.10 | 21-AUG-08:05 |
September | 0.106889E+10 | 0.00 | 141.90 | 29332.55 | 19-SEP-08:05 | 0.00 | 30.01 | 35.96 | 0.00 | 0.00 | 0.00 | 0.11 | 19-SEP-08:05 |
October | 0.132176E+10 | 0.00 | 172.45 | 28457.26 | 24-OCT-08:05 | 0.00 | 31.08 | 37.86 | 0.00 | 0.00 | 0.00 | 0.11 | 24-OCT-08:05 |
November | 0.119673E+10 | 0.00 | 152.10 | 24327.79 | 01-NOV-08:05 | 0.00 | 30.76 | 37.04 | 0.00 | 0.00 | 0.00 | 0.09 | 01-NOV-08:05 |
December | 0.129458E+10 | 0.00 | 159.56 | 20663.44 | 15-DEC-09:05 | 0.00 | 31.22 | 37.51 | 0.00 | 0.00 | 0.00 | 0.08 | 15-DEC-09:05 |
Annual Sum or Average | 0.131843E+11 | 0.00 | 1743.87 | 0.00 | 30.15 | 36.17 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.856737E+09 | 0.00 | 121.32 | 18967.54 | 0.00 | 28.55 | 33.93 | 0.00 | 0.00 | 0.00 | 0.07 | ||
Maximum of Months | 0.132176E+10 | 0.00 | 172.45 | 29596.27 | 0.00 | 31.22 | 37.86 | 0.00 | 0.00 | 0.00 | 0.11 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.932200E+12 | 0.00 | 744.00 | 0.510207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 463652.18 | 08-JAN-07:40 | 244664.10 | 05-JAN-21:10 | 0.00 | 0.00 | 0.00 |
February | 0.856379E+12 | 0.00 | 672.00 | 0.485734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 470611.75 | 14-FEB-19:20 | 252866.86 | 22-FEB-19:03 | 0.00 | 0.00 | 0.00 |
March | 0.989988E+12 | 0.00 | 744.00 | 0.550251E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 537444.54 | 14-MAR-21:20 | 259741.33 | 13-MAR-18:07 | 0.00 | 0.00 | 0.00 |
April | 0.108269E+13 | 0.00 | 720.00 | 0.547138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 538134.53 | 10-APR-18:20 | 273295.53 | 30-APR-19:10 | 0.00 | 0.00 | 0.00 |
May | 0.122583E+13 | 0.00 | 744.00 | 0.568067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 600063.56 | 31-MAY-20:20 | 280245.59 | 05-MAY-18:15 | 0.00 | 0.00 | 0.00 |
June | 0.120141E+13 | 0.00 | 720.00 | 0.557106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 589241.25 | 14-JUN-20:10 | 292164.23 | 13-JUN-20:10 | 0.00 | 0.00 | 0.00 |
July | 0.104107E+13 | 0.00 | 744.00 | 0.532114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 554634.56 | 06-JUL-21:20 | 269759.77 | 14-JUL-18:05 | 0.00 | 0.00 | 0.00 |
August | 0.116372E+13 | 0.00 | 744.00 | 0.533222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 589794.65 | 14-AUG-21:00 | 267223.17 | 14-AUG-18:03 | 0.00 | 0.00 | 0.00 |
September | 0.110296E+13 | 0.00 | 720.00 | 0.517075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 570013.43 | 30-SEP-11:00 | 265022.29 | 13-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.109382E+13 | 0.00 | 744.00 | 0.517911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 534910.40 | 09-OCT-22:00 | 249600.28 | 04-OCT-18:20 | 0.00 | 0.00 | 0.00 |
November | 0.100930E+13 | 0.00 | 720.00 | 0.501210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 556029.38 | 30-NOV-23:00 | 249325.04 | 17-NOV-19:10 | 0.00 | 0.00 | 0.00 |
December | 0.994618E+12 | 0.00 | 744.00 | 0.501270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 557028.78 | 05-DEC-23:07 | 250605.14 | 29-DEC-19:08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126940E+14 | 0.00 | 8760.00 | 0.632131E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.856379E+12 | 0.00 | 672.00 | 0.485734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 463652.18 | 244664.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.122583E+13 | 0.00 | 744.00 | 0.568067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 600063.56 | 292164.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.132338E+12 | 0.00 | 744.00 | 0.772683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81153.21 | 08-JAN-08:30 | 35596.41 | 05-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.120192E+12 | 0.00 | 672.00 | 0.722705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75985.20 | 10-FEB-07:20 | 36511.88 | 26-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.138626E+12 | 0.00 | 744.00 | 0.812970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63720.48 | 27-MAR-13:00 | 37096.16 | 19-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.154072E+12 | 0.00 | 720.00 | 0.804173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74311.54 | 10-APR-18:02 | 37133.09 | 01-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.175770E+12 | 0.00 | 744.00 | 0.831930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90888.03 | 10-MAY-21:30 | 38394.77 | 06-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.170193E+12 | 0.00 | 720.00 | 0.803660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85687.76 | 25-JUN-19:04 | 37674.68 | 16-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.149804E+12 | 0.00 | 744.00 | 0.796971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79535.40 | 19-JUL-21:51 | 35443.82 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.170212E+12 | 0.00 | 744.00 | 0.803970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85563.31 | 19-AUG-18:10 | 36363.75 | 13-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.160323E+12 | 0.00 | 720.00 | 0.777978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87705.47 | 15-SEP-20:00 | 36059.57 | 10-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.160080E+12 | 0.00 | 744.00 | 0.790772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88367.53 | 30-OCT-17:40 | 35246.68 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.145277E+12 | 0.00 | 720.00 | 0.761487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80394.72 | 16-NOV-19:40 | 35891.37 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.141781E+12 | 0.00 | 744.00 | 0.768266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85981.44 | 24-DEC-08:70 | 34963.83 | 08-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181867E+13 | 0.00 | 8760.00 | 0.944757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120192E+12 | 0.00 | 672.00 | 0.722705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63720.48 | 34963.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.175770E+12 | 0.00 | 744.00 | 0.831930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90888.03 | 38394.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.112833E+11 | 0.00 | 648.87 | 0.699822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17517.23 | 08-JAN-09:51 | 13281.47 | 19-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.111005E+11 | 0.00 | 602.43 | 0.710682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17458.41 | 12-FEB-09:41 | 13220.03 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.127273E+11 | 0.00 | 702.68 | 0.817868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17040.52 | 15-MAR-08:62 | 13241.70 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.126238E+11 | 0.00 | 685.25 | 0.797206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16424.64 | 14-APR-17:02 | 13271.04 | 17-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.127228E+11 | 0.00 | 701.58 | 0.772450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17935.85 | 10-MAY-21:51 | 13279.56 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.127450E+11 | 0.00 | 678.36 | 0.788757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18992.24 | 25-JUN-21:51 | 13277.10 | 07-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.110132E+11 | 0.00 | 686.46 | 0.649842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19029.77 | 19-JUL-21:51 | 12980.77 | 14-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.112645E+11 | 0.00 | 687.28 | 0.654012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18650.08 | 19-AUG-20:11 | 12928.81 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.110934E+11 | 0.00 | 668.82 | 0.647254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18671.79 | 15-SEP-21:51 | 13303.46 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.108702E+11 | 0.00 | 682.56 | 0.625129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18816.86 | 30-OCT-20:41 | 13255.37 | 28-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.107827E+11 | 0.00 | 646.76 | 0.635352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18210.46 | 16-NOV-21:41 | 13229.02 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.108977E+11 | 0.00 | 643.53 | 0.657763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18385.43 | 24-DEC-09:41 | 13264.14 | 29-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139124E+12 | 0.00 | 8034.56 | 0.845614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.107827E+11 | 0.00 | 602.43 | 0.625129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16424.64 | 12928.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127450E+11 | 0.00 | 702.68 | 0.817868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19029.77 | 13303.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.979428E+10 | 0.00 | 638.29 | 0.580001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17473.65 | 08-JAN-09:51 | 13408.05 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.100087E+11 | 0.00 | 596.21 | 0.616030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17370.70 | 12-FEB-09:41 | 13455.91 | 13-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.121619E+11 | 0.00 | 698.93 | 0.764285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17415.01 | 15-MAR-08:62 | 13447.58 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.126955E+11 | 0.00 | 685.70 | 0.799336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16672.35 | 14-APR-17:02 | 13454.21 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.131416E+11 | 0.00 | 704.26 | 0.802390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18192.43 | 10-MAY-21:51 | 13463.84 | 06-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.135145E+11 | 0.00 | 683.52 | 0.854048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19311.95 | 25-JUN-21:51 | 13426.51 | 10-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.114979E+11 | 0.00 | 691.55 | 0.688791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19365.88 | 19-JUL-21:51 | 13460.47 | 14-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.114880E+11 | 0.00 | 688.89 | 0.670526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18875.86 | 19-AUG-20:11 | 13088.34 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.109459E+11 | 0.00 | 667.60 | 0.632753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18884.34 | 15-SEP-21:51 | 13443.50 | 13-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.102940E+11 | 0.00 | 677.18 | 0.576781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18918.44 | 30-OCT-20:41 | 13066.84 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.973254E+10 | 0.00 | 638.67 | 0.553481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18219.58 | 16-NOV-21:41 | 13359.66 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.939111E+10 | 0.00 | 632.64 | 0.538419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18223.84 | 24-DEC-09:41 | 13419.94 | 28-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134666E+12 | 0.00 | 8003.45 | 0.807684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.939111E+10 | 0.00 | 596.21 | 0.538419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16672.35 | 13066.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135145E+11 | 0.00 | 704.26 | 0.854048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19365.88 | 13463.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.579905E+11 | 0.00 | 743.72 | 0.365571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40775.99 | 05-JAN-14:30 | 32521.55 | 16-JAN-12:10 | 0.00 | 0.00 | 0.00 |
February | 0.516054E+11 | 0.00 | 672.00 | 0.316397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41020.67 | 04-FEB-15:40 | 32451.37 | 03-FEB-13:20 | 0.00 | 0.00 | 0.00 |
March | 0.469450E+11 | 0.00 | 743.17 | 0.245055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31671.33 | 05-MAR-09:00 | 20464.97 | 09-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.397891E+11 | 0.00 | 720.00 | 0.180689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28318.65 | 01-APR-20:10 | 18162.84 | 01-APR-20:20 | 0.00 | 0.00 | 0.00 |
May | 0.414982E+11 | 0.00 | 741.33 | 0.186574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31072.70 | 07-MAY-08:00 | 20101.64 | 06-MAY-08:00 | 0.00 | 0.00 | 0.00 |
June | 0.402025E+11 | 0.00 | 720.00 | 0.179025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28883.19 | 13-JUN-20:20 | 18448.40 | 13-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.345252E+11 | 0.00 | 744.00 | 0.143254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27142.88 | 19-JUL-20:40 | 15908.65 | 15-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.339977E+11 | 0.00 | 732.06 | 0.136315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27341.73 | 13-AUG-08:00 | 15456.78 | 14-AUG-20:40 | 0.00 | 0.00 | 0.00 |
September | 0.376677E+11 | 0.00 | 713.72 | 0.164599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27355.28 | 13-SEP-20:20 | 16808.07 | 27-SEP-20:20 | 0.00 | 0.00 | 0.00 |
October | 0.423580E+11 | 0.00 | 733.33 | 0.201730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33839.84 | 29-OCT-08:00 | 23813.71 | 28-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.501931E+11 | 0.00 | 716.67 | 0.285609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40880.48 | 19-NOV-14:40 | 32222.43 | 19-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.569699E+11 | 0.00 | 743.33 | 0.348160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41831.57 | 31-DEC-08:40 | 32290.87 | 27-DEC-11:15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533742E+12 | 0.00 | 8723.33 | 0.275298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.339977E+11 | 0.00 | 672.00 | 0.136315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27142.88 | 15456.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.579905E+11 | 0.00 | 744.00 | 0.365571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41831.57 | 32521.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.622963E+11 | 0.00 | 471.35 | 0.385246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109459.80 | 27-JAN-09:02 | 85951.70 | 24-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.610518E+11 | 0.00 | 447.64 | 0.389849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106562.91 | 26-FEB-09:02 | 86964.09 | 24-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.728180E+11 | 0.00 | 536.15 | 0.475684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109257.16 | 15-MAR-08:62 | 86789.31 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.774560E+11 | 0.00 | 546.70 | 0.518655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105870.13 | 14-APR-18:02 | 85737.16 | 09-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.869019E+11 | 0.00 | 606.03 | 0.586463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113052.40 | 31-MAY-21:51 | 86236.05 | 27-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.905206E+11 | 0.00 | 618.10 | 0.618304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123829.49 | 25-JUN-21:51 | 85478.95 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.811451E+11 | 0.00 | 581.56 | 0.551612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124113.01 | 19-JUL-21:51 | 86851.53 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.767645E+11 | 0.00 | 547.48 | 0.496397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123393.48 | 19-AUG-20:11 | 85226.27 | 12-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.713198E+11 | 0.00 | 512.14 | 0.453725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122338.89 | 15-SEP-21:51 | 85546.93 | 09-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.685594E+11 | 0.00 | 513.78 | 0.421122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121674.95 | 30-OCT-20:41 | 85305.25 | 01-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 0.639880E+11 | 0.00 | 475.93 | 0.394432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114957.88 | 26-NOV-22:51 | 86018.47 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.609146E+11 | 0.00 | 466.52 | 0.370156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114630.57 | 24-DEC-09:41 | 86304.28 | 20-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873736E+12 | 0.00 | 6323.38 | 0.566164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.609146E+11 | 0.00 | 447.64 | 0.370156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105870.13 | 85226.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.905206E+11 | 0.00 | 618.10 | 0.618304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124113.01 | 86964.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.112120E+11 | 0.00 | 654.96 | 0.716367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16105.19 | 07-JAN-09:11 | 12019.52 | 21-JAN-09:11 | 0.00 | 0.00 | 0.00 |
February | 0.111351E+11 | 0.00 | 610.10 | 0.736938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16267.26 | 12-FEB-09:41 | 12501.67 | 24-FEB-09:11 | 0.00 | 0.00 | 0.00 |
March | 0.126752E+11 | 0.00 | 716.00 | 0.829144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15003.50 | 02-MAR-07:41 | 11796.10 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.126879E+11 | 0.00 | 699.22 | 0.817176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14476.10 | 14-APR-17:02 | 11477.52 | 12-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.128087E+11 | 0.00 | 713.04 | 0.797596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15752.12 | 10-MAY-21:51 | 11665.07 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.127860E+11 | 0.00 | 690.37 | 0.807285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16731.68 | 25-JUN-21:51 | 11409.74 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.109831E+11 | 0.00 | 698.85 | 0.657543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16646.12 | 19-JUL-21:51 | 11290.57 | 15-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.112803E+11 | 0.00 | 700.21 | 0.664657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16582.57 | 19-AUG-20:11 | 11176.18 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.111748E+11 | 0.00 | 678.64 | 0.669876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16543.36 | 15-SEP-21:51 | 11284.07 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.108613E+11 | 0.00 | 693.11 | 0.638506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16750.31 | 30-OCT-20:41 | 11345.43 | 08-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.107702E+11 | 0.00 | 654.40 | 0.652785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16225.60 | 25-NOV-22:51 | 11806.42 | 22-NOV-07:41 | 0.00 | 0.00 | 0.00 |
December | 0.108188E+11 | 0.00 | 647.46 | 0.671411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16878.18 | 24-DEC-09:41 | 11997.91 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139193E+12 | 0.00 | 8156.35 | 0.865928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.107702E+11 | 0.00 | 610.10 | 0.638506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14476.10 | 11176.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128087E+11 | 0.00 | 716.00 | 0.829144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16878.18 | 12501.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.965337E+10 | 0.00 | 646.11 | 0.567599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16003.14 | 07-JAN-09:11 | 11735.23 | 21-JAN-09:11 | 0.00 | 0.00 | 0.00 |
February | 0.100059E+11 | 0.00 | 604.07 | 0.621381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16202.01 | 12-FEB-09:41 | 12335.82 | 24-FEB-09:11 | 0.00 | 0.00 | 0.00 |
March | 0.120904E+11 | 0.00 | 713.45 | 0.769307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15149.05 | 02-MAR-07:41 | 11784.50 | 29-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.127603E+11 | 0.00 | 699.74 | 0.821485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14649.06 | 14-APR-17:02 | 11573.90 | 12-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.132346E+11 | 0.00 | 715.37 | 0.834742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15931.03 | 10-MAY-21:51 | 11911.39 | 20-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.135578E+11 | 0.00 | 692.95 | 0.874064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16964.49 | 25-JUN-21:51 | 11897.82 | 13-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.114760E+11 | 0.00 | 702.27 | 0.700539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16890.99 | 19-JUL-21:51 | 11534.01 | 14-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.115054E+11 | 0.00 | 702.74 | 0.682510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16734.02 | 19-AUG-20:11 | 11290.51 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.110216E+11 | 0.00 | 677.43 | 0.653746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16685.80 | 15-SEP-21:51 | 11363.97 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.102736E+11 | 0.00 | 688.43 | 0.586165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16795.15 | 30-OCT-20:41 | 11267.28 | 08-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.968022E+10 | 0.00 | 646.20 | 0.556445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16197.44 | 25-NOV-22:51 | 11534.51 | 22-NOV-07:41 | 0.00 | 0.00 | 0.00 |
December | 0.925405E+10 | 0.00 | 638.59 | 0.530970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16726.69 | 24-DEC-09:41 | 11591.49 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134513E+12 | 0.00 | 8127.36 | 0.819895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.925405E+10 | 0.00 | 604.07 | 0.530970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14649.06 | 11267.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135578E+11 | 0.00 | 715.37 | 0.874064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16964.49 | 12335.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.293395E+10 | 0.00 | 653.27 | 0.181981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5091.94 | 08-JAN-09:51 | 3678.08 | 05-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.286642E+10 | 0.00 | 606.31 | 0.181958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5052.40 | 12-FEB-09:41 | 3652.00 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.332423E+10 | 0.00 | 703.69 | 0.210756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4913.35 | 15-MAR-08:62 | 3677.49 | 29-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.333642E+10 | 0.00 | 685.73 | 0.206969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4610.48 | 14-APR-17:02 | 3710.84 | 14-APR-17:02 | 0.00 | 0.00 | 0.00 |
May | 0.331182E+10 | 0.00 | 704.57 | 0.195868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5026.94 | 10-MAY-21:51 | 3687.52 | 29-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.329693E+10 | 0.00 | 680.23 | 0.198961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5474.39 | 25-JUN-21:51 | 3676.31 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.285635E+10 | 0.00 | 689.61 | 0.161861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5504.02 | 19-JUL-21:51 | 3686.40 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.293560E+10 | 0.00 | 691.50 | 0.164192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5543.22 | 19-AUG-20:11 | 3680.33 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.292017E+10 | 0.00 | 671.15 | 0.166231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5383.85 | 15-SEP-21:51 | 3624.17 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.282585E+10 | 0.00 | 684.92 | 0.157883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5448.22 | 30-OCT-20:41 | 3680.45 | 15-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.279124E+10 | 0.00 | 650.55 | 0.161972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5191.14 | 25-NOV-22:51 | 3677.08 | 13-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.281588E+10 | 0.00 | 647.41 | 0.170216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5380.57 | 24-DEC-09:41 | 3675.84 | 04-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362149E+11 | 0.00 | 8068.95 | 0.215885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.279124E+10 | 0.00 | 606.31 | 0.157883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4610.48 | 3624.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.333642E+10 | 0.00 | 704.57 | 0.210756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5543.22 | 3710.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.253807E+10 | 0.00 | 643.95 | 0.147819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5077.93 | 08-JAN-09:51 | 3678.11 | 23-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.258126E+10 | 0.00 | 599.77 | 0.157528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5013.16 | 12-FEB-09:41 | 3708.74 | 07-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.317919E+10 | 0.00 | 699.76 | 0.196688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5019.07 | 15-MAR-08:62 | 3725.45 | 19-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.335586E+10 | 0.00 | 686.43 | 0.207719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4680.22 | 14-APR-17:02 | 3744.72 | 14-APR-17:02 | 0.00 | 0.00 | 0.00 |
May | 0.342125E+10 | 0.00 | 707.38 | 0.204469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5115.98 | 10-MAY-21:51 | 3718.95 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.349582E+10 | 0.00 | 684.89 | 0.215732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5558.74 | 25-JUN-21:51 | 3728.09 | 25-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.298283E+10 | 0.00 | 693.58 | 0.172685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5593.76 | 19-JUL-21:51 | 3721.38 | 15-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.299328E+10 | 0.00 | 693.26 | 0.168509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5604.97 | 19-AUG-20:11 | 3721.64 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.288138E+10 | 0.00 | 670.27 | 0.162071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5442.95 | 15-SEP-21:51 | 3683.08 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.267445E+10 | 0.00 | 680.91 | 0.143715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5478.14 | 30-OCT-20:41 | 3724.77 | 14-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.251232E+10 | 0.00 | 641.68 | 0.137204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5198.00 | 25-NOV-22:51 | 3714.63 | 06-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.241375E+10 | 0.00 | 636.98 | 0.134971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5330.72 | 24-DEC-09:41 | 3711.73 | 12-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350295E+11 | 0.00 | 8038.86 | 0.204911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.241375E+10 | 0.00 | 599.77 | 0.134971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4680.22 | 3678.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.349582E+10 | 0.00 | 707.38 | 0.215732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5604.97 | 3744.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.174395E+11 | 0.00 | 657.05 | 0.122640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20235.88 | 08-JAN-09:51 | 15315.53 | 28-JAN-09:41 | 0.00 | 0.00 | 0.00 |
February | 0.158264E+11 | 0.00 | 607.82 | 0.111184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20053.21 | 12-FEB-09:41 | 15180.44 | 02-FEB-09:41 | 0.00 | 0.00 | 0.00 |
March | 0.161808E+11 | 0.00 | 699.37 | 0.107979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19047.94 | 15-MAR-08:62 | 14837.90 | 30-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.150180E+11 | 0.00 | 675.73 | 0.948309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18441.41 | 14-APR-17:02 | 14914.51 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.155393E+11 | 0.00 | 692.80 | 0.963992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20081.36 | 10-MAY-21:51 | 14920.96 | 07-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.150831E+11 | 0.00 | 669.87 | 0.936780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21665.38 | 25-JUN-21:51 | 14515.63 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.136800E+11 | 0.00 | 677.56 | 0.828219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21596.79 | 19-JUL-21:51 | 14439.48 | 15-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.137446E+11 | 0.00 | 677.49 | 0.809507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22682.94 | 19-AUG-20:11 | 14327.78 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.142167E+11 | 0.00 | 662.84 | 0.861104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21643.38 | 15-SEP-21:51 | 14867.40 | 30-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.149861E+11 | 0.00 | 681.97 | 0.931799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21946.27 | 30-OCT-20:41 | 14867.51 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.160127E+11 | 0.00 | 653.77 | 0.106434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20982.35 | 25-NOV-22:51 | 15164.41 | 25-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.171341E+11 | 0.00 | 651.58 | 0.118881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21633.40 | 24-DEC-09:41 | 15066.31 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184861E+12 | 0.00 | 8007.86 | 0.119509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.136800E+11 | 0.00 | 607.82 | 0.809507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18441.41 | 14327.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.174395E+11 | 0.00 | 699.37 | 0.122640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22682.94 | 15315.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 465.88 | 194.00 | 271.88 | 921.42 | 60.72 | 0.00 | 0.00 | 0.00 |
February | 394.09 | 127.09 | 267.00 | 830.92 | 46.23 | 0.00 | 0.00 | 0.00 |
March | 274.81 | 40.79 | 234.03 | 636.01 | 24.51 | 0.00 | 0.00 | 0.00 |
April | 203.73 | 1.17 | 202.56 | 507.16 | 3.29 | 0.00 | 0.00 | 0.00 |
May | 201.70 | 0.00 | 201.70 | 525.71 | 7.26 | 0.00 | 0.00 | 0.00 |
June | 200.97 | 0.00 | 200.97 | 511.03 | 8.46 | 0.00 | 0.00 | 0.00 |
July | 207.03 | 0.00 | 207.03 | 468.95 | 19.40 | 0.00 | 0.00 | 0.00 |
August | 201.30 | 0.02 | 201.28 | 460.62 | 9.57 | 0.00 | 0.00 | 0.00 |
September | 222.14 | 6.09 | 216.05 | 509.28 | 11.19 | 0.00 | 0.00 | 0.00 |
October | 289.30 | 43.90 | 245.40 | 612.55 | 17.08 | 0.00 | 0.00 | 0.00 |
November | 381.85 | 117.98 | 263.87 | 767.66 | 32.71 | 0.00 | 0.00 | 0.00 |
December | 467.52 | 199.55 | 267.97 | 909.95 | 69.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 292.13 | 60.66 | 231.47 | 637.56 | 25.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.97 | 0.00 | 200.97 | 460.62 | 3.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 467.52 | 199.55 | 271.88 | 921.42 | 69.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1311.89 | 546.30 | 765.60 | 2578.89 | 179.32 | 0.00 | 0.00 | 0.00 |
February | 1109.73 | 357.89 | 751.84 | 2331.34 | 132.16 | 0.00 | 0.00 | 0.00 |
March | 773.86 | 114.85 | 659.01 | 1798.35 | 71.09 | 0.00 | 0.00 | 0.00 |
April | 573.69 | 3.30 | 570.39 | 1450.17 | 13.13 | 0.00 | 0.00 | 0.00 |
May | 567.98 | 0.00 | 567.98 | 1493.48 | 28.26 | 0.00 | 0.00 | 0.00 |
June | 565.93 | 0.00 | 565.93 | 1460.75 | 29.07 | 0.00 | 0.00 | 0.00 |
July | 582.99 | 0.00 | 582.99 | 1334.11 | 66.01 | 0.00 | 0.00 | 0.00 |
August | 566.85 | 0.05 | 566.80 | 1302.94 | 38.36 | 0.00 | 0.00 | 0.00 |
September | 625.53 | 17.14 | 608.39 | 1444.29 | 43.68 | 0.00 | 0.00 | 0.00 |
October | 814.64 | 123.61 | 691.03 | 1721.02 | 65.37 | 0.00 | 0.00 | 0.00 |
November | 1075.26 | 332.21 | 743.04 | 2151.95 | 106.04 | 0.00 | 0.00 | 0.00 |
December | 1316.49 | 561.92 | 754.57 | 2545.50 | 207.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.63 | 170.82 | 651.81 | 1798.62 | 81.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 565.93 | 0.00 | 565.93 | 1302.94 | 13.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1316.49 | 561.92 | 765.60 | 2578.89 | 207.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1704.22 | 709.67 | 994.55 | 3499.18 | 204.74 | 0.00 | 0.00 | 0.00 |
February | 1441.61 | 464.92 | 976.69 | 3171.06 | 148.29 | 0.00 | 0.00 | 0.00 |
March | 1005.29 | 149.19 | 856.09 | 2456.62 | 76.31 | 0.00 | 0.00 | 0.00 |
April | 745.26 | 4.29 | 740.97 | 1976.96 | 16.02 | 0.00 | 0.00 | 0.00 |
May | 737.83 | 0.00 | 737.83 | 2007.52 | 34.53 | 0.00 | 0.00 | 0.00 |
June | 735.18 | 0.00 | 735.18 | 1949.97 | 38.19 | 0.00 | 0.00 | 0.00 |
July | 757.34 | 0.00 | 757.34 | 1775.36 | 84.29 | 0.00 | 0.00 | 0.00 |
August | 736.37 | 0.06 | 736.31 | 1746.79 | 46.21 | 0.00 | 0.00 | 0.00 |
September | 812.60 | 22.27 | 790.33 | 1958.25 | 48.11 | 0.00 | 0.00 | 0.00 |
October | 1058.27 | 160.58 | 897.69 | 2335.16 | 67.51 | 0.00 | 0.00 | 0.00 |
November | 1396.82 | 431.56 | 965.26 | 2925.53 | 117.35 | 0.00 | 0.00 | 0.00 |
December | 1710.20 | 729.97 | 980.23 | 3449.02 | 241.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1068.65 | 221.90 | 846.74 | 2434.17 | 93.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 735.18 | 0.00 | 735.18 | 1746.79 | 16.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1710.20 | 729.97 | 994.55 | 3499.18 | 241.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.11 | 38.36 | 53.76 | 196.39 | 4.44 | 0.00 | 0.00 | 0.00 |
February | 77.92 | 25.13 | 52.79 | 180.56 | 1.61 | 0.00 | 0.00 | 0.00 |
March | 54.34 | 8.06 | 46.27 | 147.12 | 0.32 | 0.00 | 0.00 | 0.00 |
April | 40.28 | 0.23 | 40.05 | 124.90 | 0.02 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 0.00 | 39.88 | 126.96 | 0.11 | 0.00 | 0.00 | 0.00 |
June | 39.74 | 0.00 | 39.74 | 124.44 | 0.17 | 0.00 | 0.00 | 0.00 |
July | 40.93 | 0.00 | 40.93 | 109.32 | 0.29 | 0.00 | 0.00 | 0.00 |
August | 39.80 | 0.00 | 39.80 | 109.18 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 43.92 | 1.20 | 42.72 | 119.44 | 0.14 | 0.00 | 0.00 | 0.00 |
October | 57.20 | 8.68 | 48.52 | 137.51 | 0.21 | 0.00 | 0.00 | 0.00 |
November | 75.50 | 23.33 | 52.17 | 167.34 | 1.31 | 0.00 | 0.00 | 0.00 |
December | 92.44 | 39.45 | 52.98 | 192.48 | 5.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.76 | 11.99 | 45.77 | 144.46 | 1.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.74 | 0.00 | 39.74 | 109.18 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.44 | 39.45 | 53.76 | 196.39 | 5.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.21 | 44.81 | 82.40 | 276.20 | 8.64 | 0.00 | 0.00 | 0.00 |
February | 139.62 | 49.45 | 90.16 | 309.49 | 3.11 | 0.00 | 0.00 | 0.00 |
March | 156.24 | 61.63 | 94.61 | 359.66 | 0.57 | 0.00 | 0.00 | 0.00 |
April | 157.04 | 60.05 | 96.99 | 378.36 | 0.04 | 0.00 | 0.00 | 0.00 |
May | 133.85 | 39.72 | 94.13 | 342.21 | 0.20 | 0.00 | 0.00 | 0.00 |
June | 144.91 | 49.92 | 94.98 | 358.26 | 0.30 | 0.00 | 0.00 | 0.00 |
July | 123.53 | 29.08 | 94.45 | 289.53 | 0.52 | 0.00 | 0.00 | 0.00 |
August | 134.73 | 40.04 | 94.69 | 310.14 | 0.22 | 0.00 | 0.00 | 0.00 |
September | 125.77 | 34.85 | 90.92 | 298.42 | 0.26 | 0.00 | 0.00 | 0.00 |
October | 118.25 | 30.53 | 87.72 | 268.19 | 0.41 | 0.00 | 0.00 | 0.00 |
November | 115.30 | 31.48 | 83.82 | 257.16 | 2.56 | 0.00 | 0.00 | 0.00 |
December | 118.11 | 38.71 | 79.40 | 254.45 | 11.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.79 | 42.45 | 90.34 | 308.34 | 2.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.30 | 29.08 | 79.40 | 254.45 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.04 | 61.63 | 96.99 | 378.36 | 11.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.84 | 0.00 | 34.84 | 88.48 | 4.41 | 0.00 | 0.00 | 0.00 |
February | 37.16 | 0.00 | 37.16 | 98.53 | 1.55 | 0.00 | 0.00 | 0.00 |
March | 38.17 | 0.00 | 38.17 | 111.38 | 0.29 | 0.00 | 0.00 | 0.00 |
April | 42.30 | 1.02 | 41.28 | 129.36 | 0.02 | 0.00 | 0.00 | 0.00 |
May | 53.07 | 5.53 | 47.54 | 154.60 | 0.12 | 0.00 | 0.00 | 0.00 |
June | 65.21 | 13.35 | 51.86 | 177.21 | 0.18 | 0.00 | 0.00 | 0.00 |
July | 55.99 | 5.94 | 50.05 | 140.52 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 46.30 | 2.17 | 44.12 | 122.69 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 39.27 | 0.07 | 39.21 | 109.82 | 0.15 | 0.00 | 0.00 | 0.00 |
October | 37.75 | 0.00 | 37.75 | 98.58 | 0.21 | 0.00 | 0.00 | 0.00 |
November | 35.72 | 0.00 | 35.72 | 91.72 | 1.28 | 0.00 | 0.00 | 0.00 |
December | 33.85 | 0.00 | 33.85 | 83.65 | 5.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.33 | 2.35 | 40.98 | 117.26 | 1.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.85 | 0.00 | 33.85 | 83.65 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.21 | 13.35 | 51.86 | 177.21 | 5.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.21 | 44.81 | 82.40 | 279.84 | 8.10 | 0.00 | 0.00 | 0.00 |
February | 139.62 | 49.45 | 90.16 | 312.45 | 2.83 | 0.00 | 0.00 | 0.00 |
March | 156.24 | 61.63 | 94.61 | 361.07 | 0.51 | 0.00 | 0.00 | 0.00 |
April | 157.04 | 60.05 | 96.99 | 378.18 | 0.04 | 0.00 | 0.00 | 0.00 |
May | 133.85 | 39.72 | 94.13 | 341.18 | 0.22 | 0.00 | 0.00 | 0.00 |
June | 144.91 | 49.92 | 94.98 | 356.36 | 0.34 | 0.00 | 0.00 | 0.00 |
July | 123.53 | 29.08 | 94.45 | 288.35 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 134.73 | 40.04 | 94.69 | 309.55 | 0.23 | 0.00 | 0.00 | 0.00 |
September | 125.77 | 34.85 | 90.92 | 298.80 | 0.25 | 0.00 | 0.00 | 0.00 |
October | 118.25 | 30.53 | 87.72 | 269.69 | 0.36 | 0.00 | 0.00 | 0.00 |
November | 115.30 | 31.48 | 83.82 | 259.82 | 2.31 | 0.00 | 0.00 | 0.00 |
December | 118.11 | 38.71 | 79.40 | 258.01 | 10.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.79 | 42.45 | 90.34 | 309.26 | 2.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.30 | 29.08 | 79.40 | 258.01 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.04 | 61.63 | 96.99 | 378.18 | 10.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 30.68 | 43.00 | 152.34 | 6.99 | 0.00 | 0.00 | 0.00 |
February | 62.32 | 20.10 | 42.22 | 139.89 | 4.16 | 0.00 | 0.00 | 0.00 |
March | 43.46 | 6.45 | 37.01 | 111.08 | 1.58 | 0.00 | 0.00 | 0.00 |
April | 32.22 | 0.19 | 32.03 | 92.73 | 0.28 | 0.00 | 0.00 | 0.00 |
May | 31.90 | 0.00 | 31.90 | 93.91 | 0.58 | 0.00 | 0.00 | 0.00 |
June | 31.78 | 0.00 | 31.78 | 92.66 | 0.65 | 0.00 | 0.00 | 0.00 |
July | 32.74 | 0.00 | 32.74 | 80.60 | 1.63 | 0.00 | 0.00 | 0.00 |
August | 31.83 | 0.00 | 31.83 | 79.57 | 0.97 | 0.00 | 0.00 | 0.00 |
September | 35.13 | 0.96 | 34.17 | 88.07 | 1.03 | 0.00 | 0.00 | 0.00 |
October | 45.75 | 6.94 | 38.81 | 102.20 | 1.63 | 0.00 | 0.00 | 0.00 |
November | 60.39 | 18.66 | 41.73 | 127.78 | 3.49 | 0.00 | 0.00 | 0.00 |
December | 73.93 | 31.56 | 42.38 | 149.85 | 8.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.20 | 9.59 | 36.61 | 109.07 | 2.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.78 | 0.00 | 31.78 | 79.57 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.93 | 31.56 | 43.00 | 152.34 | 8.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.88 | 0.00 | 27.88 | 77.04 | 2.55 | 0.00 | 0.00 | 0.00 |
February | 29.74 | 0.00 | 29.74 | 86.00 | 0.54 | 0.00 | 0.00 | 0.00 |
March | 30.54 | 0.00 | 30.54 | 97.50 | 0.08 | 0.00 | 0.00 | 0.00 |
April | 33.84 | 0.82 | 33.03 | 111.79 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42.46 | 4.42 | 38.04 | 130.95 | 0.03 | 0.00 | 0.00 | 0.00 |
June | 52.17 | 10.68 | 41.50 | 148.89 | 0.05 | 0.00 | 0.00 | 0.00 |
July | 44.80 | 4.75 | 40.04 | 118.57 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 37.04 | 1.74 | 35.30 | 105.22 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 31.42 | 0.06 | 31.37 | 94.97 | 0.02 | 0.00 | 0.00 | 0.00 |
October | 30.20 | 0.00 | 30.20 | 85.81 | 0.01 | 0.00 | 0.00 | 0.00 |
November | 28.58 | 0.00 | 28.58 | 79.80 | 0.50 | 0.00 | 0.00 | 0.00 |
December | 27.08 | 0.00 | 27.08 | 72.57 | 3.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.67 | 1.88 | 32.79 | 100.79 | 0.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.08 | 0.00 | 27.08 | 72.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.17 | 10.68 | 41.50 | 148.89 | 3.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.39 | 42.28 | 83.12 | 271.87 | 8.17 | 0.00 | 0.00 | 0.00 |
February | 142.12 | 52.05 | 90.07 | 314.48 | 2.95 | 0.00 | 0.00 | 0.00 |
March | 155.17 | 60.74 | 94.44 | 358.97 | 0.55 | 0.00 | 0.00 | 0.00 |
April | 156.55 | 59.72 | 96.83 | 381.39 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 134.76 | 40.84 | 93.91 | 346.77 | 0.17 | 0.00 | 0.00 | 0.00 |
June | 143.44 | 47.23 | 96.21 | 358.49 | 0.26 | 0.00 | 0.00 | 0.00 |
July | 122.67 | 27.54 | 95.13 | 289.37 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 134.85 | 39.64 | 95.21 | 312.36 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 126.68 | 34.55 | 92.13 | 302.76 | 0.24 | 0.00 | 0.00 | 0.00 |
October | 118.85 | 30.50 | 88.36 | 271.14 | 0.38 | 0.00 | 0.00 | 0.00 |
November | 115.06 | 31.84 | 83.22 | 257.55 | 2.45 | 0.00 | 0.00 | 0.00 |
December | 117.61 | 37.77 | 79.84 | 251.92 | 10.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.66 | 41.96 | 90.69 | 309.55 | 2.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.06 | 27.54 | 79.84 | 251.92 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.55 | 60.74 | 96.83 | 381.39 | 10.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.11 | 38.36 | 53.76 | 195.69 | 4.34 | 0.00 | 0.00 | 0.00 |
February | 77.92 | 25.13 | 52.79 | 179.86 | 1.54 | 0.00 | 0.00 | 0.00 |
March | 54.34 | 8.06 | 46.27 | 146.97 | 0.29 | 0.00 | 0.00 | 0.00 |
April | 40.28 | 0.23 | 40.05 | 124.68 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 0.00 | 39.88 | 126.74 | 0.10 | 0.00 | 0.00 | 0.00 |
June | 39.74 | 0.00 | 39.74 | 124.23 | 0.15 | 0.00 | 0.00 | 0.00 |
July | 40.93 | 0.00 | 40.93 | 109.11 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 39.80 | 0.00 | 39.80 | 108.89 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 43.92 | 1.20 | 42.72 | 119.18 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 57.20 | 8.68 | 48.52 | 137.33 | 0.20 | 0.00 | 0.00 | 0.00 |
November | 75.50 | 23.33 | 52.17 | 167.07 | 1.29 | 0.00 | 0.00 | 0.00 |
December | 92.44 | 39.45 | 52.98 | 191.82 | 5.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.76 | 11.99 | 45.77 | 144.12 | 1.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.74 | 0.00 | 39.74 | 108.89 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.44 | 39.45 | 53.76 | 195.69 | 5.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.84 | 0.00 | 34.84 | 87.74 | 4.31 | 0.00 | 0.00 | 0.00 |
February | 37.16 | 0.00 | 37.16 | 97.83 | 1.49 | 0.00 | 0.00 | 0.00 |
March | 38.17 | 0.00 | 38.17 | 111.17 | 0.27 | 0.00 | 0.00 | 0.00 |
April | 42.30 | 1.02 | 41.28 | 129.13 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 53.07 | 5.53 | 47.54 | 154.41 | 0.10 | 0.00 | 0.00 | 0.00 |
June | 65.21 | 13.35 | 51.86 | 177.04 | 0.16 | 0.00 | 0.00 | 0.00 |
July | 55.99 | 5.94 | 50.05 | 140.34 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 46.30 | 2.17 | 44.12 | 122.42 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 39.27 | 0.07 | 39.21 | 109.56 | 0.13 | 0.00 | 0.00 | 0.00 |
October | 37.75 | 0.00 | 37.75 | 98.37 | 0.20 | 0.00 | 0.00 | 0.00 |
November | 35.72 | 0.00 | 35.72 | 91.42 | 1.26 | 0.00 | 0.00 | 0.00 |
December | 33.85 | 0.00 | 33.85 | 82.95 | 5.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.33 | 2.35 | 40.98 | 116.91 | 1.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.85 | 0.00 | 33.85 | 82.95 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.21 | 13.35 | 51.86 | 177.04 | 5.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.39 | 42.28 | 83.12 | 275.48 | 7.65 | 0.00 | 0.00 | 0.00 |
February | 142.12 | 52.05 | 90.07 | 317.42 | 2.68 | 0.00 | 0.00 | 0.00 |
March | 155.17 | 60.74 | 94.44 | 360.34 | 0.50 | 0.00 | 0.00 | 0.00 |
April | 156.55 | 59.72 | 96.83 | 381.22 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 134.76 | 40.84 | 93.91 | 345.77 | 0.19 | 0.00 | 0.00 | 0.00 |
June | 143.44 | 47.23 | 96.21 | 356.65 | 0.29 | 0.00 | 0.00 | 0.00 |
July | 122.67 | 27.54 | 95.13 | 288.24 | 0.50 | 0.00 | 0.00 | 0.00 |
August | 134.85 | 39.64 | 95.21 | 311.80 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 126.68 | 34.55 | 92.13 | 303.14 | 0.23 | 0.00 | 0.00 | 0.00 |
October | 118.85 | 30.50 | 88.36 | 272.60 | 0.34 | 0.00 | 0.00 | 0.00 |
November | 115.06 | 31.84 | 83.22 | 260.15 | 2.20 | 0.00 | 0.00 | 0.00 |
December | 117.61 | 37.77 | 79.84 | 255.45 | 10.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.66 | 41.96 | 90.69 | 310.47 | 2.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.06 | 27.54 | 79.84 | 255.45 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.55 | 60.74 | 96.83 | 381.22 | 10.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.12 | 0.00 | 44.12 | 107.83 | 10.10 | 0.00 | 0.00 | 0.00 |
February | 47.07 | 0.00 | 47.07 | 118.80 | 6.22 | 0.00 | 0.00 | 0.00 |
March | 48.34 | 0.00 | 48.33 | 133.56 | 1.96 | 0.00 | 0.00 | 0.00 |
April | 53.57 | 1.29 | 52.28 | 155.96 | 0.28 | 0.00 | 0.00 | 0.00 |
May | 67.21 | 7.00 | 60.21 | 186.14 | 0.83 | 0.00 | 0.00 | 0.00 |
June | 82.58 | 16.90 | 65.68 | 213.51 | 1.00 | 0.00 | 0.00 | 0.00 |
July | 70.91 | 7.52 | 63.38 | 172.03 | 1.80 | 0.00 | 0.00 | 0.00 |
August | 58.63 | 2.75 | 55.88 | 150.04 | 0.69 | 0.00 | 0.00 | 0.00 |
September | 49.74 | 0.09 | 49.65 | 133.92 | 0.84 | 0.00 | 0.00 | 0.00 |
October | 47.81 | 0.00 | 47.81 | 119.36 | 1.35 | 0.00 | 0.00 | 0.00 |
November | 45.24 | 0.00 | 45.24 | 110.66 | 4.25 | 0.00 | 0.00 | 0.00 |
December | 42.86 | 0.00 | 42.86 | 102.50 | 12.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.87 | 2.97 | 51.90 | 142.09 | 3.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.86 | 0.00 | 42.86 | 102.50 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.58 | 16.90 | 65.68 | 213.51 | 12.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.27 | 0.00 | 16.27 | 39.75 | 3.72 | 0.00 | 0.00 | 0.00 |
February | 17.35 | 0.00 | 17.35 | 43.79 | 2.29 | 0.00 | 0.00 | 0.00 |
March | 17.82 | 0.00 | 17.82 | 49.24 | 0.72 | 0.00 | 0.00 | 0.00 |
April | 19.75 | 0.48 | 19.27 | 57.49 | 0.10 | 0.00 | 0.00 | 0.00 |
May | 24.78 | 2.58 | 22.19 | 68.62 | 0.31 | 0.00 | 0.00 | 0.00 |
June | 30.44 | 6.23 | 24.21 | 78.71 | 0.37 | 0.00 | 0.00 | 0.00 |
July | 26.14 | 2.77 | 23.37 | 63.42 | 0.66 | 0.00 | 0.00 | 0.00 |
August | 21.61 | 1.01 | 20.60 | 55.31 | 0.25 | 0.00 | 0.00 | 0.00 |
September | 18.34 | 0.03 | 18.30 | 49.37 | 0.31 | 0.00 | 0.00 | 0.00 |
October | 17.62 | 0.00 | 17.62 | 44.00 | 0.50 | 0.00 | 0.00 | 0.00 |
November | 16.68 | 0.00 | 16.68 | 40.80 | 1.57 | 0.00 | 0.00 | 0.00 |
December | 15.80 | 0.00 | 15.80 | 37.79 | 4.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.23 | 1.09 | 19.13 | 52.38 | 1.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.80 | 0.00 | 15.80 | 37.79 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.44 | 6.23 | 24.21 | 78.71 | 4.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.98 | 17.90 | 25.08 | 90.86 | 3.55 | 0.00 | 0.00 | 0.00 |
February | 36.36 | 11.72 | 24.63 | 82.61 | 2.20 | 0.00 | 0.00 | 0.00 |
March | 25.35 | 3.76 | 21.59 | 66.15 | 0.72 | 0.00 | 0.00 | 0.00 |
April | 18.80 | 0.11 | 18.69 | 55.35 | 0.10 | 0.00 | 0.00 | 0.00 |
May | 18.61 | 0.00 | 18.61 | 55.46 | 0.31 | 0.00 | 0.00 | 0.00 |
June | 18.54 | 0.00 | 18.54 | 53.63 | 0.38 | 0.00 | 0.00 | 0.00 |
July | 19.10 | 0.00 | 19.10 | 48.58 | 0.67 | 0.00 | 0.00 | 0.00 |
August | 18.57 | 0.00 | 18.57 | 48.86 | 0.26 | 0.00 | 0.00 | 0.00 |
September | 20.49 | 0.56 | 19.93 | 53.91 | 0.30 | 0.00 | 0.00 | 0.00 |
October | 26.69 | 4.05 | 22.64 | 62.42 | 0.47 | 0.00 | 0.00 | 0.00 |
November | 35.23 | 10.88 | 24.34 | 76.58 | 1.48 | 0.00 | 0.00 | 0.00 |
December | 43.13 | 18.41 | 24.72 | 89.31 | 4.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.95 | 5.60 | 21.35 | 65.23 | 1.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.54 | 0.00 | 18.54 | 48.58 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.13 | 18.41 | 25.08 | 90.86 | 4.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.66 | 48.58 | 68.08 | 246.61 | 9.63 | 0.00 | 0.00 | 0.00 |
February | 98.68 | 31.82 | 66.86 | 224.22 | 5.98 | 0.00 | 0.00 | 0.00 |
March | 68.81 | 10.21 | 58.60 | 179.55 | 1.95 | 0.00 | 0.00 | 0.00 |
April | 51.01 | 0.29 | 50.72 | 150.24 | 0.27 | 0.00 | 0.00 | 0.00 |
May | 50.51 | 0.00 | 50.51 | 150.53 | 0.84 | 0.00 | 0.00 | 0.00 |
June | 50.32 | 0.00 | 50.32 | 145.56 | 1.02 | 0.00 | 0.00 | 0.00 |
July | 51.84 | 0.00 | 51.84 | 131.87 | 1.83 | 0.00 | 0.00 | 0.00 |
August | 50.41 | 0.00 | 50.40 | 132.62 | 0.70 | 0.00 | 0.00 | 0.00 |
September | 55.62 | 1.52 | 54.10 | 146.32 | 0.81 | 0.00 | 0.00 | 0.00 |
October | 72.44 | 10.99 | 61.45 | 169.43 | 1.26 | 0.00 | 0.00 | 0.00 |
November | 95.61 | 29.54 | 66.07 | 207.85 | 4.02 | 0.00 | 0.00 | 0.00 |
December | 117.06 | 49.97 | 67.10 | 242.39 | 11.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.15 | 15.19 | 57.96 | 177.04 | 3.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.32 | 0.00 | 50.32 | 131.87 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.06 | 49.97 | 68.08 | 246.61 | 11.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.11 | 38.36 | 53.76 | 194.73 | 3.66 | 0.00 | 0.00 | 0.00 |
February | 77.92 | 25.13 | 52.79 | 179.42 | 1.03 | 0.00 | 0.00 | 0.00 |
March | 54.34 | 8.06 | 46.27 | 146.79 | 0.14 | 0.00 | 0.00 | 0.00 |
April | 40.28 | 0.23 | 40.05 | 124.73 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 0.00 | 39.88 | 126.82 | 0.10 | 0.00 | 0.00 | 0.00 |
June | 39.74 | 0.00 | 39.74 | 124.49 | 0.16 | 0.00 | 0.00 | 0.00 |
July | 40.93 | 0.00 | 40.93 | 108.64 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 39.80 | 0.00 | 39.80 | 108.71 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 43.92 | 1.20 | 42.72 | 118.46 | 0.16 | 0.00 | 0.00 | 0.00 |
October | 57.20 | 8.68 | 48.52 | 136.31 | 0.18 | 0.00 | 0.00 | 0.00 |
November | 75.50 | 23.33 | 52.17 | 165.94 | 1.05 | 0.00 | 0.00 | 0.00 |
December | 92.44 | 39.45 | 52.98 | 190.64 | 4.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.76 | 11.99 | 45.77 | 143.63 | 0.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.74 | 0.00 | 39.74 | 108.64 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.44 | 39.45 | 53.76 | 194.73 | 4.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.21 | 44.81 | 82.40 | 273.43 | 7.08 | 0.00 | 0.00 | 0.00 |
February | 139.62 | 49.45 | 90.16 | 307.25 | 1.97 | 0.00 | 0.00 | 0.00 |
March | 156.24 | 61.63 | 94.61 | 357.72 | 0.27 | 0.00 | 0.00 | 0.00 |
April | 157.04 | 60.05 | 96.99 | 376.14 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 133.85 | 39.72 | 94.13 | 340.64 | 0.18 | 0.00 | 0.00 | 0.00 |
June | 144.91 | 49.92 | 94.98 | 356.87 | 0.29 | 0.00 | 0.00 | 0.00 |
July | 123.53 | 29.08 | 94.45 | 287.25 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 134.73 | 40.04 | 94.69 | 308.01 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 125.77 | 34.85 | 90.92 | 295.80 | 0.29 | 0.00 | 0.00 | 0.00 |
October | 118.25 | 30.53 | 87.72 | 265.86 | 0.34 | 0.00 | 0.00 | 0.00 |
November | 115.30 | 31.48 | 83.82 | 254.89 | 2.03 | 0.00 | 0.00 | 0.00 |
December | 118.11 | 38.71 | 79.40 | 251.48 | 9.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.79 | 42.45 | 90.34 | 306.11 | 1.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.30 | 29.08 | 79.40 | 251.48 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.04 | 61.63 | 96.99 | 376.14 | 9.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.84 | 0.00 | 34.84 | 87.63 | 3.64 | 0.00 | 0.00 | 0.00 |
February | 37.16 | 0.00 | 37.16 | 98.01 | 1.00 | 0.00 | 0.00 | 0.00 |
March | 38.17 | 0.00 | 38.17 | 111.09 | 0.14 | 0.00 | 0.00 | 0.00 |
April | 42.30 | 1.02 | 41.28 | 128.76 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53.07 | 5.53 | 47.54 | 153.89 | 0.11 | 0.00 | 0.00 | 0.00 |
June | 65.21 | 13.35 | 51.86 | 176.32 | 0.17 | 0.00 | 0.00 | 0.00 |
July | 55.99 | 5.94 | 50.05 | 139.36 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 46.30 | 2.17 | 44.12 | 121.85 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 39.27 | 0.07 | 39.21 | 108.88 | 0.16 | 0.00 | 0.00 | 0.00 |
October | 37.75 | 0.00 | 37.75 | 97.80 | 0.18 | 0.00 | 0.00 | 0.00 |
November | 35.72 | 0.00 | 35.72 | 90.99 | 1.01 | 0.00 | 0.00 | 0.00 |
December | 33.85 | 0.00 | 33.85 | 82.68 | 4.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.33 | 2.35 | 40.98 | 116.48 | 0.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.85 | 0.00 | 33.85 | 82.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.21 | 13.35 | 51.86 | 176.32 | 4.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.21 | 44.81 | 82.40 | 277.34 | 6.67 | 0.00 | 0.00 | 0.00 |
February | 139.62 | 49.45 | 90.16 | 310.37 | 1.79 | 0.00 | 0.00 | 0.00 |
March | 156.24 | 61.63 | 94.61 | 359.15 | 0.25 | 0.00 | 0.00 | 0.00 |
April | 157.04 | 60.05 | 96.99 | 375.94 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 133.85 | 39.72 | 94.13 | 339.57 | 0.20 | 0.00 | 0.00 | 0.00 |
June | 144.91 | 49.92 | 94.98 | 354.88 | 0.31 | 0.00 | 0.00 | 0.00 |
July | 123.53 | 29.08 | 94.45 | 286.01 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 134.73 | 40.04 | 94.69 | 307.40 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 125.77 | 34.85 | 90.92 | 296.19 | 0.28 | 0.00 | 0.00 | 0.00 |
October | 118.25 | 30.53 | 87.72 | 267.39 | 0.31 | 0.00 | 0.00 | 0.00 |
November | 115.30 | 31.48 | 83.82 | 257.69 | 1.83 | 0.00 | 0.00 | 0.00 |
December | 118.11 | 38.71 | 79.40 | 255.35 | 8.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.79 | 42.45 | 90.34 | 307.10 | 1.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.30 | 29.08 | 79.40 | 255.35 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.04 | 61.63 | 96.99 | 375.94 | 8.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.09 | 56.25 | 78.84 | 286.53 | 5.09 | 0.00 | 0.00 | 0.00 |
February | 114.28 | 36.85 | 77.42 | 266.22 | 1.21 | 0.00 | 0.00 | 0.00 |
March | 79.69 | 11.83 | 67.86 | 221.89 | 0.16 | 0.00 | 0.00 | 0.00 |
April | 59.08 | 0.34 | 58.74 | 191.26 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58.49 | 0.00 | 58.49 | 193.15 | 0.09 | 0.00 | 0.00 | 0.00 |
June | 58.28 | 0.00 | 58.28 | 190.26 | 0.14 | 0.00 | 0.00 | 0.00 |
July | 60.03 | 0.00 | 60.03 | 165.32 | 0.20 | 0.00 | 0.00 | 0.00 |
August | 58.37 | 0.00 | 58.37 | 166.14 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 64.41 | 1.77 | 62.65 | 179.57 | 0.16 | 0.00 | 0.00 | 0.00 |
October | 83.89 | 12.73 | 71.16 | 203.88 | 0.20 | 0.00 | 0.00 | 0.00 |
November | 110.73 | 34.21 | 76.52 | 245.56 | 1.44 | 0.00 | 0.00 | 0.00 |
December | 135.57 | 57.86 | 77.70 | 279.93 | 6.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.71 | 17.59 | 67.12 | 215.55 | 1.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.28 | 0.00 | 58.28 | 165.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 135.57 | 57.86 | 78.84 | 286.53 | 6.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 243.87 | 0.00 | 243.87 | 544.88 | 86.33 | 0.00 | 0.00 | 0.00 |
February | 260.14 | 0.00 | 260.14 | 609.51 | 59.37 | 0.00 | 0.00 | 0.00 |
March | 267.16 | 0.01 | 267.14 | 664.86 | 30.87 | 0.00 | 0.00 | 0.00 |
April | 296.09 | 7.14 | 288.96 | 765.32 | 7.64 | 0.00 | 0.00 | 0.00 |
May | 371.46 | 38.69 | 332.77 | 939.75 | 16.57 | 0.00 | 0.00 | 0.00 |
June | 456.45 | 93.42 | 363.03 | 1098.09 | 17.31 | 0.00 | 0.00 | 0.00 |
July | 391.91 | 41.58 | 350.33 | 867.57 | 36.80 | 0.00 | 0.00 | 0.00 |
August | 324.07 | 15.22 | 308.85 | 732.22 | 23.39 | 0.00 | 0.00 | 0.00 |
September | 274.91 | 0.48 | 274.43 | 649.62 | 25.31 | 0.00 | 0.00 | 0.00 |
October | 264.24 | 0.00 | 264.24 | 581.08 | 37.28 | 0.00 | 0.00 | 0.00 |
November | 250.03 | 0.00 | 250.03 | 553.09 | 52.42 | 0.00 | 0.00 | 0.00 |
December | 236.92 | 0.00 | 236.92 | 521.40 | 102.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 303.28 | 16.42 | 286.86 | 710.84 | 41.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.92 | 0.00 | 236.92 | 521.40 | 7.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 456.45 | 93.42 | 363.03 | 1098.09 | 102.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 243.87 | 0.00 | 243.87 | 532.52 | 93.00 | 0.00 | 0.00 | 0.00 |
February | 260.14 | 0.00 | 260.14 | 597.20 | 64.95 | 0.00 | 0.00 | 0.00 |
March | 267.16 | 0.01 | 267.14 | 650.70 | 35.37 | 0.00 | 0.00 | 0.00 |
April | 296.09 | 7.14 | 288.96 | 748.87 | 9.22 | 0.00 | 0.00 | 0.00 |
May | 371.46 | 38.69 | 332.77 | 924.07 | 19.23 | 0.00 | 0.00 | 0.00 |
June | 456.45 | 93.42 | 363.03 | 1083.36 | 19.81 | 0.00 | 0.00 | 0.00 |
July | 391.91 | 41.58 | 350.33 | 853.38 | 41.99 | 0.00 | 0.00 | 0.00 |
August | 324.07 | 15.22 | 308.85 | 715.32 | 28.27 | 0.00 | 0.00 | 0.00 |
September | 274.91 | 0.48 | 274.43 | 634.60 | 30.28 | 0.00 | 0.00 | 0.00 |
October | 264.24 | 0.00 | 264.24 | 566.55 | 44.06 | 0.00 | 0.00 | 0.00 |
November | 250.03 | 0.00 | 250.03 | 540.08 | 58.95 | 0.00 | 0.00 | 0.00 |
December | 236.92 | 0.00 | 236.92 | 509.22 | 109.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 303.28 | 16.42 | 286.86 | 696.53 | 46.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.92 | 0.00 | 236.92 | 509.22 | 9.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 456.45 | 93.42 | 363.03 | 1083.36 | 109.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.84 | 0.00 | 34.84 | 87.17 | 13.40 | 0.00 | 0.00 | 0.00 |
February | 37.16 | 0.00 | 37.16 | 96.33 | 9.59 | 0.00 | 0.00 | 0.00 |
March | 38.17 | 0.00 | 38.17 | 102.27 | 5.94 | 0.00 | 0.00 | 0.00 |
April | 42.30 | 1.02 | 41.28 | 117.08 | 1.96 | 0.00 | 0.00 | 0.00 |
May | 53.07 | 5.53 | 47.54 | 141.47 | 3.37 | 0.00 | 0.00 | 0.00 |
June | 65.21 | 13.35 | 51.86 | 166.10 | 3.47 | 0.00 | 0.00 | 0.00 |
July | 55.99 | 5.94 | 50.05 | 134.57 | 5.99 | 0.00 | 0.00 | 0.00 |
August | 46.30 | 2.17 | 44.12 | 110.24 | 4.56 | 0.00 | 0.00 | 0.00 |
September | 39.27 | 0.07 | 39.21 | 102.09 | 4.77 | 0.00 | 0.00 | 0.00 |
October | 37.75 | 0.00 | 37.75 | 89.70 | 6.81 | 0.00 | 0.00 | 0.00 |
November | 35.72 | 0.00 | 35.72 | 88.78 | 8.33 | 0.00 | 0.00 | 0.00 |
December | 33.85 | 0.00 | 33.85 | 84.18 | 15.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.33 | 2.35 | 40.98 | 110.02 | 6.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.85 | 0.00 | 33.85 | 84.18 | 1.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.21 | 13.35 | 51.86 | 166.10 | 15.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.77 | 84.55 | 166.22 | 546.34 | 49.64 | 0.00 | 0.00 | 0.00 |
February | 284.22 | 104.10 | 180.12 | 626.08 | 35.86 | 0.00 | 0.00 | 0.00 |
March | 310.33 | 121.47 | 188.86 | 680.24 | 22.47 | 0.00 | 0.00 | 0.00 |
April | 313.07 | 119.42 | 193.65 | 712.45 | 7.46 | 0.00 | 0.00 | 0.00 |
May | 269.49 | 81.68 | 187.82 | 639.44 | 12.79 | 0.00 | 0.00 | 0.00 |
June | 286.86 | 94.45 | 192.41 | 670.17 | 13.29 | 0.00 | 0.00 | 0.00 |
July | 245.32 | 55.07 | 190.25 | 554.39 | 22.51 | 0.00 | 0.00 | 0.00 |
August | 269.67 | 79.27 | 190.40 | 576.33 | 17.43 | 0.00 | 0.00 | 0.00 |
September | 253.34 | 69.10 | 184.25 | 575.84 | 17.99 | 0.00 | 0.00 | 0.00 |
October | 237.69 | 60.99 | 176.70 | 509.41 | 25.92 | 0.00 | 0.00 | 0.00 |
November | 230.10 | 63.67 | 166.43 | 507.65 | 31.35 | 0.00 | 0.00 | 0.00 |
December | 235.21 | 75.54 | 159.66 | 513.75 | 57.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.29 | 83.92 | 181.38 | 592.14 | 26.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.10 | 55.07 | 159.66 | 507.65 | 7.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 313.07 | 121.47 | 193.65 | 712.45 | 57.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.11 | 38.36 | 53.76 | 196.67 | 13.15 | 0.00 | 0.00 | 0.00 |
February | 77.92 | 25.13 | 52.79 | 179.34 | 9.52 | 0.00 | 0.00 | 0.00 |
March | 54.34 | 8.06 | 46.27 | 137.64 | 5.96 | 0.00 | 0.00 | 0.00 |
April | 40.28 | 0.23 | 40.05 | 112.11 | 1.98 | 0.00 | 0.00 | 0.00 |
May | 39.88 | 0.00 | 39.88 | 112.80 | 3.39 | 0.00 | 0.00 | 0.00 |
June | 39.74 | 0.00 | 39.74 | 111.54 | 3.55 | 0.00 | 0.00 | 0.00 |
July | 40.93 | 0.00 | 40.93 | 102.95 | 6.04 | 0.00 | 0.00 | 0.00 |
August | 39.80 | 0.00 | 39.80 | 95.86 | 4.64 | 0.00 | 0.00 | 0.00 |
September | 43.92 | 1.20 | 42.72 | 111.69 | 4.77 | 0.00 | 0.00 | 0.00 |
October | 57.20 | 8.68 | 48.52 | 128.97 | 6.77 | 0.00 | 0.00 | 0.00 |
November | 75.50 | 23.33 | 52.17 | 165.47 | 8.25 | 0.00 | 0.00 | 0.00 |
December | 92.44 | 39.45 | 52.98 | 194.79 | 15.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.76 | 11.99 | 45.77 | 137.27 | 6.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.74 | 0.00 | 39.74 | 95.86 | 1.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.44 | 39.45 | 53.76 | 196.67 | 15.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.12 | 0.00 | 44.12 | 100.30 | 11.92 | 0.00 | 0.00 | 0.00 |
February | 47.07 | 0.00 | 47.07 | 111.64 | 7.76 | 0.00 | 0.00 | 0.00 |
March | 48.34 | 0.00 | 48.33 | 124.04 | 2.85 | 0.00 | 0.00 | 0.00 |
April | 53.57 | 1.29 | 52.28 | 144.42 | 0.45 | 0.00 | 0.00 | 0.00 |
May | 67.21 | 7.00 | 60.21 | 176.87 | 1.30 | 0.00 | 0.00 | 0.00 |
June | 82.58 | 16.90 | 65.68 | 204.97 | 1.56 | 0.00 | 0.00 | 0.00 |
July | 70.91 | 7.52 | 63.38 | 163.06 | 3.16 | 0.00 | 0.00 | 0.00 |
August | 58.63 | 2.75 | 55.88 | 141.13 | 1.16 | 0.00 | 0.00 | 0.00 |
September | 49.74 | 0.09 | 49.65 | 123.46 | 1.58 | 0.00 | 0.00 | 0.00 |
October | 47.81 | 0.00 | 47.81 | 110.81 | 2.33 | 0.00 | 0.00 | 0.00 |
November | 45.24 | 0.00 | 45.24 | 103.03 | 5.59 | 0.00 | 0.00 | 0.00 |
December | 42.86 | 0.00 | 42.86 | 96.18 | 14.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.87 | 2.97 | 51.90 | 133.39 | 4.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.86 | 0.00 | 42.86 | 96.18 | 0.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.58 | 16.90 | 65.68 | 204.97 | 14.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.48 | 0.00 | 39.48 | 89.74 | 10.67 | 0.00 | 0.00 | 0.00 |
February | 42.11 | 0.00 | 42.11 | 99.88 | 6.95 | 0.00 | 0.00 | 0.00 |
March | 43.25 | 0.00 | 43.24 | 110.98 | 2.55 | 0.00 | 0.00 | 0.00 |
April | 47.93 | 1.15 | 46.77 | 129.21 | 0.40 | 0.00 | 0.00 | 0.00 |
May | 60.13 | 6.26 | 53.87 | 158.25 | 1.16 | 0.00 | 0.00 | 0.00 |
June | 73.89 | 15.12 | 58.77 | 183.38 | 1.39 | 0.00 | 0.00 | 0.00 |
July | 63.44 | 6.73 | 56.71 | 145.89 | 2.83 | 0.00 | 0.00 | 0.00 |
August | 52.46 | 2.46 | 50.00 | 126.27 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 44.50 | 0.08 | 44.42 | 110.46 | 1.41 | 0.00 | 0.00 | 0.00 |
October | 42.77 | 0.00 | 42.77 | 99.14 | 2.09 | 0.00 | 0.00 | 0.00 |
November | 40.47 | 0.00 | 40.47 | 92.18 | 5.00 | 0.00 | 0.00 | 0.00 |
December | 38.35 | 0.00 | 38.35 | 86.06 | 12.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.09 | 2.66 | 46.44 | 119.34 | 4.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.35 | 0.00 | 38.35 | 86.06 | 0.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.89 | 15.12 | 58.77 | 183.38 | 12.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 343.89 | 143.20 | 200.69 | 702.05 | 33.79 | 0.00 | 0.00 | 0.00 |
February | 290.89 | 93.81 | 197.08 | 637.75 | 22.16 | 0.00 | 0.00 | 0.00 |
March | 202.85 | 30.10 | 172.75 | 500.40 | 8.19 | 0.00 | 0.00 | 0.00 |
April | 150.38 | 0.87 | 149.52 | 409.86 | 1.30 | 0.00 | 0.00 | 0.00 |
May | 148.88 | 0.00 | 148.88 | 417.87 | 3.90 | 0.00 | 0.00 | 0.00 |
June | 148.35 | 0.00 | 148.35 | 406.48 | 4.74 | 0.00 | 0.00 | 0.00 |
July | 152.82 | 0.00 | 152.82 | 363.63 | 9.58 | 0.00 | 0.00 | 0.00 |
August | 148.59 | 0.01 | 148.58 | 365.35 | 3.48 | 0.00 | 0.00 | 0.00 |
September | 163.97 | 4.49 | 159.48 | 400.10 | 4.69 | 0.00 | 0.00 | 0.00 |
October | 213.54 | 32.40 | 181.14 | 472.54 | 6.72 | 0.00 | 0.00 | 0.00 |
November | 281.86 | 87.08 | 194.77 | 587.91 | 15.98 | 0.00 | 0.00 | 0.00 |
December | 345.09 | 147.30 | 197.80 | 693.22 | 40.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 215.64 | 44.78 | 170.86 | 495.77 | 12.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.35 | 0.00 | 148.35 | 363.63 | 1.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 345.09 | 147.30 | 200.69 | 702.05 | 40.36 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124782E+10 | 0.519614E+09 | 0.728204E+09 | 0.246792E+10 | 0.162629E+09 |
February | 0.953384E+09 | 0.307467E+09 | 0.645917E+09 | 0.201016E+10 | 0.111834E+09 |
March | 0.736064E+09 | 0.109239E+09 | 0.626825E+09 | 0.170349E+10 | 65653767.82 |
April | 0.528069E+09 | 3040094.91 | 0.525028E+09 | 0.131456E+10 | 8524930.07 |
May | 0.540235E+09 | 0.00 | 0.540235E+09 | 0.140805E+10 | 19456734.89 |
June | 0.520926E+09 | 0.00 | 0.520926E+09 | 0.132458E+10 | 21937728.97 |
July | 0.554520E+09 | 0.00 | 0.554520E+09 | 0.125602E+10 | 51971248.29 |
August | 0.539162E+09 | 45477.52 | 0.539117E+09 | 0.123373E+10 | 25643660.70 |
September | 0.575783E+09 | 15778028.20 | 0.560005E+09 | 0.132007E+10 | 29008057.04 |
October | 0.774853E+09 | 0.117575E+09 | 0.657278E+09 | 0.164065E+10 | 45752873.41 |
November | 0.989750E+09 | 0.305795E+09 | 0.683955E+09 | 0.198976E+10 | 84795344.29 |
December | 0.125219E+10 | 0.534476E+09 | 0.717718E+09 | 0.243720E+10 | 0.187155E+09 |
Annual Sum or Average | 0.921276E+10 | 0.191303E+10 | 0.729973E+10 | 0.201062E+11 | 0.814362E+09 |
Minimum of Months | 0.520926E+09 | 0.00 | 0.520926E+09 | 0.123373E+10 | 8524930.07 |
Maximum of Months | 0.125219E+10 | 0.534476E+09 | 0.728204E+09 | 0.246792E+10 | 0.187155E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351377E+10 | 0.146320E+10 | 0.205057E+10 | 0.690730E+10 | 0.480283E+09 |
February | 0.268467E+10 | 0.865807E+09 | 0.181886E+10 | 0.563997E+10 | 0.319725E+09 |
March | 0.207271E+10 | 0.307609E+09 | 0.176510E+10 | 0.481671E+10 | 0.190414E+09 |
April | 0.148701E+10 | 8560706.83 | 0.147845E+10 | 0.375885E+10 | 34031737.43 |
May | 0.152127E+10 | 0.00 | 0.152127E+10 | 0.400015E+10 | 75684908.06 |
June | 0.146689E+10 | 0.00 | 0.146689E+10 | 0.378627E+10 | 75341424.11 |
July | 0.156149E+10 | 0.00 | 0.156149E+10 | 0.357327E+10 | 0.176804E+09 |
August | 0.151825E+10 | 128061.71 | 0.151812E+10 | 0.348980E+10 | 0.102740E+09 |
September | 0.162137E+10 | 44429887.09 | 0.157694E+10 | 0.374359E+10 | 0.113230E+09 |
October | 0.218194E+10 | 0.331084E+09 | 0.185085E+10 | 0.460958E+10 | 0.175095E+09 |
November | 0.278707E+10 | 0.861099E+09 | 0.192597E+10 | 0.557785E+10 | 0.274861E+09 |
December | 0.352610E+10 | 0.150505E+10 | 0.202105E+10 | 0.681786E+10 | 0.556805E+09 |
Annual Sum or Average | 0.259425E+11 | 0.538697E+10 | 0.205556E+11 | 0.567212E+11 | 0.257502E+10 |
Minimum of Months | 0.146689E+10 | 0.00 | 0.146689E+10 | 0.348980E+10 | 34031737.43 |
Maximum of Months | 0.352610E+10 | 0.150505E+10 | 0.205057E+10 | 0.690730E+10 | 0.556805E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456459E+10 | 0.190078E+10 | 0.266381E+10 | 0.937221E+10 | 0.548368E+09 |
February | 0.348753E+10 | 0.112473E+10 | 0.236280E+10 | 0.767142E+10 | 0.358746E+09 |
March | 0.269257E+10 | 0.399602E+09 | 0.229296E+10 | 0.657981E+10 | 0.204389E+09 |
April | 0.193171E+10 | 11120845.37 | 0.192058E+10 | 0.512427E+10 | 41515935.21 |
May | 0.197621E+10 | 0.00 | 0.197621E+10 | 0.537694E+10 | 92478439.84 |
June | 0.190558E+10 | 0.00 | 0.190558E+10 | 0.505433E+10 | 98992429.74 |
July | 0.202847E+10 | 0.00 | 0.202847E+10 | 0.475513E+10 | 0.225761E+09 |
August | 0.197229E+10 | 166359.45 | 0.197212E+10 | 0.467861E+10 | 0.123781E+09 |
September | 0.210625E+10 | 57716951.86 | 0.204853E+10 | 0.507579E+10 | 0.124707E+09 |
October | 0.283446E+10 | 0.430097E+09 | 0.240436E+10 | 0.625449E+10 | 0.180827E+09 |
November | 0.362056E+10 | 0.111862E+10 | 0.250195E+10 | 0.758298E+10 | 0.304170E+09 |
December | 0.458060E+10 | 0.195515E+10 | 0.262545E+10 | 0.923785E+10 | 0.647378E+09 |
Annual Sum or Average | 0.337008E+11 | 0.699798E+10 | 0.267028E+11 | 0.767638E+11 | 0.295112E+10 |
Minimum of Months | 0.190558E+10 | 0.00 | 0.190558E+10 | 0.467861E+10 | 41515935.21 |
Maximum of Months | 0.458060E+10 | 0.195515E+10 | 0.266381E+10 | 0.937221E+10 | 0.647378E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246716E+09 | 0.102737E+09 | 0.143979E+09 | 0.526021E+09 | 11889780.44 |
February | 0.188501E+09 | 60791535.26 | 0.127710E+09 | 0.436802E+09 | 3890290.47 |
March | 0.145534E+09 | 21598386.14 | 0.123935E+09 | 0.394056E+09 | 864756.83 |
April | 0.104410E+09 | 601078.98 | 0.103808E+09 | 0.323748E+09 | 50816.12 |
May | 0.106815E+09 | 0.00 | 0.106815E+09 | 0.340042E+09 | 307135.14 |
June | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.322556E+09 | 442509.43 |
July | 0.109639E+09 | 0.00 | 0.109639E+09 | 0.292814E+09 | 764855.24 |
August | 0.106603E+09 | 8991.69 | 0.106594E+09 | 0.292431E+09 | 343021.24 |
September | 0.113843E+09 | 3119587.16 | 0.110724E+09 | 0.309583E+09 | 363500.18 |
October | 0.153203E+09 | 23246622.26 | 0.129956E+09 | 0.368313E+09 | 550158.17 |
November | 0.195692E+09 | 60460936.36 | 0.135231E+09 | 0.433743E+09 | 3391886.36 |
December | 0.247581E+09 | 0.105675E+09 | 0.141906E+09 | 0.515546E+09 | 15642992.86 |
Annual Sum or Average | 0.182153E+10 | 0.378239E+09 | 0.144329E+10 | 0.455566E+10 | 38501702.49 |
Minimum of Months | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.292431E+09 | 50816.12 |
Maximum of Months | 0.247581E+09 | 0.105675E+09 | 0.143979E+09 | 0.526021E+09 | 15642992.86 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340721E+09 | 0.120027E+09 | 0.220694E+09 | 0.739779E+09 | 23151003.25 |
February | 0.337767E+09 | 0.119640E+09 | 0.218126E+09 | 0.748717E+09 | 7521118.55 |
March | 0.418480E+09 | 0.165079E+09 | 0.253401E+09 | 0.963321E+09 | 1528404.36 |
April | 0.407051E+09 | 0.155660E+09 | 0.251391E+09 | 0.980715E+09 | 91220.11 |
May | 0.358510E+09 | 0.106392E+09 | 0.252118E+09 | 0.916583E+09 | 545113.12 |
June | 0.375602E+09 | 0.129405E+09 | 0.246197E+09 | 0.928611E+09 | 782477.66 |
July | 0.330866E+09 | 77896981.51 | 0.252969E+09 | 0.775488E+09 | 1388021.44 |
August | 0.360854E+09 | 0.107247E+09 | 0.253607E+09 | 0.830685E+09 | 600794.47 |
September | 0.326000E+09 | 90332823.10 | 0.235667E+09 | 0.773500E+09 | 685252.42 |
October | 0.316730E+09 | 81775732.61 | 0.234955E+09 | 0.718332E+09 | 1094450.47 |
November | 0.298863E+09 | 81603046.92 | 0.217260E+09 | 0.666564E+09 | 6645227.85 |
December | 0.316342E+09 | 0.103668E+09 | 0.212674E+09 | 0.681527E+09 | 30392355.52 |
Annual Sum or Average | 0.418779E+10 | 0.133873E+10 | 0.284906E+10 | 0.972382E+10 | 74425439.23 |
Minimum of Months | 0.298863E+09 | 77896981.51 | 0.212674E+09 | 0.666564E+09 | 91220.11 |
Maximum of Months | 0.418480E+09 | 0.165079E+09 | 0.253607E+09 | 0.980715E+09 | 30392355.52 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93314774.48 | 0.00 | 93314774.48 | 0.236979E+09 | 11804247.89 |
February | 89908303.92 | 0.00 | 89908303.92 | 0.238370E+09 | 3760123.93 |
March | 0.102226E+09 | 5097.39 | 0.102221E+09 | 0.298325E+09 | 787482.42 |
April | 0.109642E+09 | 2642112.80 | 0.107000E+09 | 0.335294E+09 | 50044.01 |
May | 0.142137E+09 | 14803736.87 | 0.127333E+09 | 0.414089E+09 | 316206.87 |
June | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.459324E+09 | 470334.39 |
July | 0.149961E+09 | 15910101.18 | 0.134051E+09 | 0.376381E+09 | 835305.20 |
August | 0.124003E+09 | 5822871.80 | 0.118180E+09 | 0.328616E+09 | 340686.54 |
September | 0.101800E+09 | 179187.76 | 0.101620E+09 | 0.284665E+09 | 388456.68 |
October | 0.101109E+09 | 0.00 | 0.101109E+09 | 0.264049E+09 | 561234.84 |
November | 92584943.17 | 0.00 | 92584943.17 | 0.237749E+09 | 3307758.79 |
December | 90654000.44 | 0.00 | 90654000.44 | 0.224048E+09 | 15498841.99 |
Annual Sum or Average | 0.136636E+10 | 73956578.22 | 0.129241E+10 | 0.369789E+10 | 38120723.52 |
Minimum of Months | 89908303.92 | 0.00 | 89908303.92 | 0.224048E+09 | 50044.01 |
Maximum of Months | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.459324E+09 | 15498841.99 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340721E+09 | 0.120027E+09 | 0.220694E+09 | 0.749516E+09 | 21698093.75 |
February | 0.337767E+09 | 0.119640E+09 | 0.218126E+09 | 0.755878E+09 | 6846874.02 |
March | 0.418480E+09 | 0.165079E+09 | 0.253401E+09 | 0.967091E+09 | 1374320.13 |
April | 0.407051E+09 | 0.155660E+09 | 0.251391E+09 | 0.980231E+09 | 94308.26 |
May | 0.358510E+09 | 0.106392E+09 | 0.252118E+09 | 0.913805E+09 | 589299.64 |
June | 0.375602E+09 | 0.129405E+09 | 0.246197E+09 | 0.923680E+09 | 872898.51 |
July | 0.330866E+09 | 77896981.51 | 0.252969E+09 | 0.772315E+09 | 1533501.14 |
August | 0.360854E+09 | 0.107247E+09 | 0.253607E+09 | 0.829108E+09 | 618094.78 |
September | 0.326000E+09 | 90332823.10 | 0.235667E+09 | 0.774495E+09 | 660060.63 |
October | 0.316730E+09 | 81775732.61 | 0.234955E+09 | 0.722348E+09 | 975348.22 |
November | 0.298863E+09 | 81603046.92 | 0.217260E+09 | 0.673455E+09 | 5975911.92 |
December | 0.316342E+09 | 0.103668E+09 | 0.212674E+09 | 0.691054E+09 | 28501516.29 |
Annual Sum or Average | 0.418779E+10 | 0.133873E+10 | 0.284906E+10 | 0.975298E+10 | 69740227.29 |
Minimum of Months | 0.298863E+09 | 77896981.51 | 0.212674E+09 | 0.673455E+09 | 94308.26 |
Maximum of Months | 0.418480E+09 | 0.165079E+09 | 0.253607E+09 | 0.980231E+09 | 28501516.29 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197334E+09 | 82172949.63 | 0.115161E+09 | 0.408014E+09 | 18713581.84 |
February | 0.150771E+09 | 48623558.29 | 0.102148E+09 | 0.338425E+09 | 10071988.64 |
March | 0.116404E+09 | 17275273.32 | 99128629.48 | 0.297516E+09 | 4220030.02 |
April | 83511001.41 | 480767.57 | 83030233.84 | 0.240356E+09 | 719349.26 |
May | 85434963.14 | 0.00 | 85434963.14 | 0.251527E+09 | 1559448.10 |
June | 82381427.42 | 0.00 | 82381427.42 | 0.240164E+09 | 1673149.56 |
July | 87693961.87 | 0.00 | 87693961.87 | 0.215875E+09 | 4358083.88 |
August | 85265283.69 | 7191.92 | 85258091.77 | 0.213131E+09 | 2608318.10 |
September | 91056489.49 | 2495173.50 | 88561315.99 | 0.228276E+09 | 2672383.29 |
October | 0.122538E+09 | 18593600.04 | 0.103944E+09 | 0.273737E+09 | 4354555.61 |
November | 0.156522E+09 | 48359131.76 | 0.108163E+09 | 0.331217E+09 | 9054824.50 |
December | 0.198026E+09 | 84523294.81 | 0.113502E+09 | 0.401371E+09 | 23323159.61 |
Annual Sum or Average | 0.145694E+10 | 0.302531E+09 | 0.115441E+10 | 0.343961E+10 | 83328872.40 |
Minimum of Months | 82381427.42 | 0.00 | 82381427.42 | 0.213131E+09 | 719349.26 |
Maximum of Months | 0.198026E+09 | 84523294.81 | 0.115161E+09 | 0.408014E+09 | 23323159.61 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 74661715.11 | 0.00 | 74661715.11 | 0.206346E+09 | 6842232.71 |
February | 71936177.42 | 0.00 | 71936177.42 | 0.208058E+09 | 1305767.41 |
March | 81791837.43 | 4078.45 | 81787758.98 | 0.261132E+09 | 222729.35 |
April | 87725489.87 | 2113970.43 | 85611519.45 | 0.289766E+09 | 0.00 |
May | 0.113725E+09 | 11844559.35 | 0.101880E+09 | 0.350750E+09 | 70480.89 |
June | 0.135236E+09 | 27678444.78 | 0.107558E+09 | 0.385926E+09 | 134197.59 |
July | 0.119985E+09 | 12729768.12 | 0.107255E+09 | 0.317586E+09 | 191854.00 |
August | 99215610.17 | 4658914.93 | 94556695.25 | 0.281818E+09 | 30821.11 |
September | 81450457.60 | 143369.21 | 81307088.38 | 0.246165E+09 | 51580.73 |
October | 80897687.62 | 0.00 | 80897687.62 | 0.229839E+09 | 27511.65 |
November | 74077772.67 | 0.00 | 74077772.67 | 0.206841E+09 | 1294591.91 |
December | 72532813.71 | 0.00 | 72532813.71 | 0.194382E+09 | 9097354.35 |
Annual Sum or Average | 0.109324E+10 | 59173105.27 | 0.103406E+10 | 0.317861E+10 | 19269121.71 |
Minimum of Months | 71936177.42 | 0.00 | 71936177.42 | 0.194382E+09 | 0.00 |
Maximum of Months | 0.135236E+09 | 27678444.78 | 0.107558E+09 | 0.385926E+09 | 9097354.35 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.335853E+09 | 0.113235E+09 | 0.222618E+09 | 0.728170E+09 | 21876425.86 |
February | 0.343814E+09 | 0.125927E+09 | 0.217887E+09 | 0.760790E+09 | 7126050.24 |
March | 0.415617E+09 | 0.162678E+09 | 0.252939E+09 | 0.961479E+09 | 1469030.70 |
April | 0.405768E+09 | 0.154785E+09 | 0.250983E+09 | 0.988572E+09 | 33986.28 |
May | 0.360930E+09 | 0.109389E+09 | 0.251541E+09 | 0.928796E+09 | 467624.17 |
June | 0.371797E+09 | 0.122417E+09 | 0.249381E+09 | 0.929196E+09 | 674249.92 |
July | 0.328555E+09 | 73755618.33 | 0.254799E+09 | 0.775043E+09 | 1190620.97 |
August | 0.361169E+09 | 0.106169E+09 | 0.255000E+09 | 0.836621E+09 | 505219.75 |
September | 0.328355E+09 | 89555101.95 | 0.238800E+09 | 0.784753E+09 | 620248.50 |
October | 0.318335E+09 | 81681591.01 | 0.236654E+09 | 0.726232E+09 | 1011854.12 |
November | 0.298231E+09 | 82517905.01 | 0.215713E+09 | 0.667569E+09 | 6339771.59 |
December | 0.315009E+09 | 0.101173E+09 | 0.213836E+09 | 0.674752E+09 | 28835928.10 |
Annual Sum or Average | 0.418343E+10 | 0.132328E+10 | 0.286015E+10 | 0.976197E+10 | 70151010.20 |
Minimum of Months | 0.298231E+09 | 73755618.33 | 0.213836E+09 | 0.667569E+09 | 33986.28 |
Maximum of Months | 0.415617E+09 | 0.162678E+09 | 0.255000E+09 | 0.988572E+09 | 28835928.10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246716E+09 | 0.102737E+09 | 0.143979E+09 | 0.524137E+09 | 11625420.93 |
February | 0.188501E+09 | 60791535.26 | 0.127710E+09 | 0.435125E+09 | 3725258.32 |
March | 0.145534E+09 | 21598386.14 | 0.123935E+09 | 0.393633E+09 | 786356.10 |
April | 0.104410E+09 | 601078.98 | 0.103808E+09 | 0.323170E+09 | 28459.90 |
May | 0.106815E+09 | 0.00 | 0.106815E+09 | 0.339470E+09 | 263744.56 |
June | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.322000E+09 | 379571.82 |
July | 0.109639E+09 | 0.00 | 0.109639E+09 | 0.292242E+09 | 680562.43 |
August | 0.106603E+09 | 8991.69 | 0.106594E+09 | 0.291655E+09 | 288597.78 |
September | 0.113843E+09 | 3119587.16 | 0.110724E+09 | 0.308925E+09 | 322497.80 |
October | 0.153203E+09 | 23246622.26 | 0.129956E+09 | 0.367820E+09 | 523673.68 |
November | 0.195692E+09 | 60460936.36 | 0.135231E+09 | 0.433038E+09 | 3346934.01 |
December | 0.247581E+09 | 0.105675E+09 | 0.141906E+09 | 0.513758E+09 | 15294283.45 |
Annual Sum or Average | 0.182153E+10 | 0.378239E+09 | 0.144329E+10 | 0.454497E+10 | 37265360.78 |
Minimum of Months | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.291655E+09 | 28459.90 |
Maximum of Months | 0.247581E+09 | 0.105675E+09 | 0.143979E+09 | 0.524137E+09 | 15294283.45 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93314774.48 | 0.00 | 93314774.48 | 0.234998E+09 | 11534217.49 |
February | 89908303.92 | 0.00 | 89908303.92 | 0.236677E+09 | 3611603.75 |
March | 0.102226E+09 | 5097.39 | 0.102221E+09 | 0.297763E+09 | 715887.25 |
April | 0.109642E+09 | 2642112.80 | 0.107000E+09 | 0.334712E+09 | 25613.67 |
May | 0.142137E+09 | 14803736.87 | 0.127333E+09 | 0.413573E+09 | 272890.95 |
June | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.458880E+09 | 410033.94 |
July | 0.149961E+09 | 15910101.18 | 0.134051E+09 | 0.375882E+09 | 749603.45 |
August | 0.124003E+09 | 5822871.80 | 0.118180E+09 | 0.327894E+09 | 287255.16 |
September | 0.101800E+09 | 179187.76 | 0.101620E+09 | 0.283989E+09 | 344895.59 |
October | 0.101109E+09 | 0.00 | 0.101109E+09 | 0.263481E+09 | 534740.84 |
November | 92584943.17 | 0.00 | 92584943.17 | 0.236958E+09 | 3267510.69 |
December | 90654000.44 | 0.00 | 90654000.44 | 0.222161E+09 | 15108302.92 |
Annual Sum or Average | 0.136636E+10 | 73956578.22 | 0.129241E+10 | 0.368697E+10 | 36862555.68 |
Minimum of Months | 89908303.92 | 0.00 | 89908303.92 | 0.222161E+09 | 25613.67 |
Maximum of Months | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.458880E+09 | 15108302.92 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.335853E+09 | 0.113235E+09 | 0.222618E+09 | 0.737836E+09 | 20501003.86 |
February | 0.343814E+09 | 0.125927E+09 | 0.217887E+09 | 0.767894E+09 | 6494493.49 |
March | 0.415617E+09 | 0.162678E+09 | 0.252939E+09 | 0.965141E+09 | 1326291.80 |
April | 0.405768E+09 | 0.154785E+09 | 0.250983E+09 | 0.988120E+09 | 36604.36 |
May | 0.360930E+09 | 0.109389E+09 | 0.251541E+09 | 0.926099E+09 | 507890.10 |
June | 0.371797E+09 | 0.122417E+09 | 0.249381E+09 | 0.924430E+09 | 761707.65 |
July | 0.328555E+09 | 73755618.33 | 0.254799E+09 | 0.772011E+09 | 1329476.14 |
August | 0.361169E+09 | 0.106169E+09 | 0.255000E+09 | 0.835131E+09 | 522102.56 |
September | 0.328355E+09 | 89555101.95 | 0.238800E+09 | 0.785731E+09 | 596915.82 |
October | 0.318335E+09 | 81681591.01 | 0.236654E+09 | 0.730133E+09 | 897981.19 |
November | 0.298231E+09 | 82517905.01 | 0.215713E+09 | 0.674312E+09 | 5699316.10 |
December | 0.315009E+09 | 0.101173E+09 | 0.213836E+09 | 0.684198E+09 | 26979015.54 |
Annual Sum or Average | 0.418343E+10 | 0.132328E+10 | 0.286015E+10 | 0.979104E+10 | 65652798.62 |
Minimum of Months | 0.298231E+09 | 73755618.33 | 0.213836E+09 | 0.674312E+09 | 36604.36 |
Maximum of Months | 0.415617E+09 | 0.162678E+09 | 0.255000E+09 | 0.988120E+09 | 26979015.54 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118177E+09 | 0.00 | 0.118177E+09 | 0.288815E+09 | 27047417.46 |
February | 0.113863E+09 | 0.00 | 0.113863E+09 | 0.287389E+09 | 15044761.11 |
March | 0.129463E+09 | 6455.52 | 0.129457E+09 | 0.357728E+09 | 5242601.44 |
April | 0.138855E+09 | 3346069.16 | 0.135509E+09 | 0.404252E+09 | 721058.83 |
May | 0.180007E+09 | 18747998.68 | 0.161259E+09 | 0.498545E+09 | 2218159.06 |
June | 0.214057E+09 | 43810447.55 | 0.170247E+09 | 0.553412E+09 | 2591956.49 |
July | 0.189916E+09 | 20149139.27 | 0.169767E+09 | 0.460762E+09 | 4825968.73 |
August | 0.157042E+09 | 7374299.74 | 0.149668E+09 | 0.401857E+09 | 1837486.63 |
September | 0.128923E+09 | 226930.00 | 0.128696E+09 | 0.347134E+09 | 2184869.12 |
October | 0.128048E+09 | 0.00 | 0.128048E+09 | 0.319691E+09 | 3612969.57 |
November | 0.117253E+09 | 0.00 | 0.117253E+09 | 0.286839E+09 | 11007860.79 |
December | 0.114808E+09 | 0.00 | 0.114808E+09 | 0.274546E+09 | 32840037.02 |
Annual Sum or Average | 0.173041E+10 | 93661339.92 | 0.163675E+10 | 0.448097E+10 | 0.109175E+09 |
Minimum of Months | 0.113863E+09 | 0.00 | 0.113863E+09 | 0.274546E+09 | 721058.83 |
Maximum of Months | 0.214057E+09 | 43810447.55 | 0.170247E+09 | 0.553412E+09 | 32840037.02 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43565036.55 | 0.00 | 43565036.55 | 0.106469E+09 | 9970798.02 |
February | 41974688.02 | 0.00 | 41974688.02 | 0.105944E+09 | 5546486.41 |
March | 47725455.84 | 2379.77 | 47723076.07 | 0.131874E+09 | 1932639.97 |
April | 51187736.14 | 1233499.64 | 49954236.50 | 0.149024E+09 | 265812.14 |
May | 66358182.66 | 6911288.61 | 59446894.06 | 0.183784E+09 | 817705.28 |
June | 78910349.82 | 16150345.02 | 62760004.80 | 0.204011E+09 | 955502.48 |
July | 70010876.68 | 7427807.05 | 62583069.63 | 0.169856E+09 | 1779051.90 |
August | 57892209.91 | 2718472.23 | 55173737.68 | 0.148141E+09 | 677373.66 |
September | 47526261.04 | 83655.79 | 47442605.25 | 0.127968E+09 | 805433.23 |
October | 47203720.31 | 0.00 | 47203720.31 | 0.117851E+09 | 1331890.18 |
November | 43224306.71 | 0.00 | 43224306.71 | 0.105741E+09 | 4057953.29 |
December | 42322824.70 | 0.00 | 42322824.70 | 0.101209E+09 | 12106197.45 |
Annual Sum or Average | 0.637902E+09 | 34527448.11 | 0.603374E+09 | 0.165187E+10 | 40246844.00 |
Minimum of Months | 41974688.02 | 0.00 | 41974688.02 | 0.101209E+09 | 265812.14 |
Maximum of Months | 78910349.82 | 16150345.02 | 62760004.80 | 0.204011E+09 | 12106197.45 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115117E+09 | 47936490.34 | 67180201.76 | 0.243356E+09 | 9499756.49 |
February | 87953996.74 | 28365085.38 | 59588911.36 | 0.199850E+09 | 5326316.05 |
March | 67905491.86 | 10077719.94 | 57827771.92 | 0.177181E+09 | 1920907.12 |
April | 48717057.50 | 280461.03 | 48436596.47 | 0.143474E+09 | 254126.22 |
May | 49839421.65 | 0.00 | 49839421.65 | 0.148544E+09 | 831941.28 |
June | 48058108.14 | 0.00 | 48058108.14 | 0.139009E+09 | 976350.66 |
July | 51157233.31 | 0.00 | 51157233.31 | 0.130127E+09 | 1806924.05 |
August | 49740437.29 | 4195.49 | 49736241.80 | 0.130875E+09 | 690025.15 |
September | 53118800.63 | 1455586.80 | 51663213.83 | 0.139730E+09 | 774819.39 |
October | 71483794.04 | 10846780.27 | 60637013.77 | 0.167197E+09 | 1248239.68 |
November | 91308869.45 | 28210829.27 | 63098040.18 | 0.198487E+09 | 3836224.53 |
December | 0.115520E+09 | 49307589.95 | 66212781.69 | 0.239195E+09 | 11533580.69 |
Annual Sum or Average | 0.849920E+09 | 0.176485E+09 | 0.673436E+09 | 0.205703E+10 | 38699211.32 |
Minimum of Months | 48058108.14 | 0.00 | 48058108.14 | 0.130127E+09 | 254126.22 |
Maximum of Months | 0.115520E+09 | 49307589.95 | 67180201.76 | 0.243356E+09 | 11533580.69 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312450E+09 | 0.130109E+09 | 0.182341E+09 | 0.660518E+09 | 25784282.23 |
February | 0.238725E+09 | 76988643.67 | 0.161736E+09 | 0.542434E+09 | 14456711.23 |
March | 0.184309E+09 | 27352993.26 | 0.156956E+09 | 0.480906E+09 | 5213734.83 |
April | 0.132228E+09 | 761228.60 | 0.131467E+09 | 0.389420E+09 | 689750.55 |
May | 0.135274E+09 | 0.00 | 0.135274E+09 | 0.403178E+09 | 2258058.80 |
June | 0.130440E+09 | 0.00 | 0.130440E+09 | 0.377298E+09 | 2650015.40 |
July | 0.138851E+09 | 0.00 | 0.138851E+09 | 0.353191E+09 | 4904361.48 |
August | 0.135006E+09 | 11387.40 | 0.134994E+09 | 0.355221E+09 | 1872869.40 |
September | 0.144175E+09 | 3950760.30 | 0.140225E+09 | 0.379255E+09 | 2103018.31 |
October | 0.194022E+09 | 29440380.31 | 0.164581E+09 | 0.453807E+09 | 3387977.82 |
November | 0.247831E+09 | 76569961.02 | 0.171261E+09 | 0.538734E+09 | 10412298.06 |
December | 0.313546E+09 | 0.133831E+09 | 0.179715E+09 | 0.649225E+09 | 31304497.14 |
Annual Sum or Average | 0.230686E+10 | 0.479016E+09 | 0.182784E+10 | 0.558319E+10 | 0.105038E+09 |
Minimum of Months | 0.130440E+09 | 0.00 | 0.130440E+09 | 0.353191E+09 | 689750.55 |
Maximum of Months | 0.313546E+09 | 0.133831E+09 | 0.182341E+09 | 0.660518E+09 | 31304497.14 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246716E+09 | 0.102737E+09 | 0.143979E+09 | 0.521555E+09 | 9815878.34 |
February | 0.188501E+09 | 60791535.26 | 0.127710E+09 | 0.434060E+09 | 2494623.21 |
March | 0.145534E+09 | 21598386.14 | 0.123935E+09 | 0.393160E+09 | 386966.34 |
April | 0.104410E+09 | 601078.98 | 0.103808E+09 | 0.323311E+09 | 14639.16 |
May | 0.106815E+09 | 0.00 | 0.106815E+09 | 0.339663E+09 | 274217.77 |
June | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.322677E+09 | 412659.00 |
July | 0.109639E+09 | 0.00 | 0.109639E+09 | 0.290976E+09 | 663537.35 |
August | 0.106603E+09 | 8991.69 | 0.106594E+09 | 0.291171E+09 | 289130.25 |
September | 0.113843E+09 | 3119587.16 | 0.110724E+09 | 0.307049E+09 | 412233.91 |
October | 0.153203E+09 | 23246622.26 | 0.129956E+09 | 0.365096E+09 | 472684.09 |
November | 0.195692E+09 | 60460936.36 | 0.135231E+09 | 0.430110E+09 | 2730955.24 |
December | 0.247581E+09 | 0.105675E+09 | 0.141906E+09 | 0.510621E+09 | 13276608.16 |
Annual Sum or Average | 0.182153E+10 | 0.378239E+09 | 0.144329E+10 | 0.452945E+10 | 31244132.82 |
Minimum of Months | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.290976E+09 | 14639.16 |
Maximum of Months | 0.247581E+09 | 0.105675E+09 | 0.143979E+09 | 0.521555E+09 | 13276608.16 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340721E+09 | 0.120027E+09 | 0.220694E+09 | 0.732355E+09 | 18973258.59 |
February | 0.337767E+09 | 0.119640E+09 | 0.218126E+09 | 0.743291E+09 | 4761888.55 |
March | 0.418480E+09 | 0.165079E+09 | 0.253401E+09 | 0.958109E+09 | 719218.80 |
April | 0.407051E+09 | 0.155660E+09 | 0.251391E+09 | 0.974965E+09 | 22326.01 |
May | 0.358510E+09 | 0.106392E+09 | 0.252118E+09 | 0.912361E+09 | 494520.42 |
June | 0.375602E+09 | 0.129405E+09 | 0.246197E+09 | 0.924999E+09 | 741735.09 |
July | 0.330866E+09 | 77896981.51 | 0.252969E+09 | 0.769373E+09 | 1199339.51 |
August | 0.360854E+09 | 0.107247E+09 | 0.253607E+09 | 0.824986E+09 | 498211.84 |
September | 0.326000E+09 | 90332823.10 | 0.235667E+09 | 0.766712E+09 | 757619.29 |
October | 0.316730E+09 | 81775732.61 | 0.234955E+09 | 0.712079E+09 | 901421.45 |
November | 0.298863E+09 | 81603046.92 | 0.217260E+09 | 0.660684E+09 | 5270122.88 |
December | 0.316342E+09 | 0.103668E+09 | 0.212674E+09 | 0.673569E+09 | 25575946.49 |
Annual Sum or Average | 0.418779E+10 | 0.133873E+10 | 0.284906E+10 | 0.965348E+10 | 59915608.92 |
Minimum of Months | 0.298863E+09 | 77896981.51 | 0.212674E+09 | 0.660684E+09 | 22326.01 |
Maximum of Months | 0.418480E+09 | 0.165079E+09 | 0.253607E+09 | 0.974965E+09 | 25575946.49 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93314774.48 | 0.00 | 93314774.48 | 0.234700E+09 | 9750008.38 |
February | 89908303.92 | 0.00 | 89908303.92 | 0.237104E+09 | 2416543.55 |
March | 0.102226E+09 | 5097.39 | 0.102221E+09 | 0.297540E+09 | 381360.76 |
April | 0.109642E+09 | 2642112.80 | 0.107000E+09 | 0.333755E+09 | 12662.21 |
May | 0.142137E+09 | 14803736.87 | 0.127333E+09 | 0.412170E+09 | 286649.12 |
June | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.457034E+09 | 445097.76 |
July | 0.149961E+09 | 15910101.18 | 0.134051E+09 | 0.373264E+09 | 715200.66 |
August | 0.124003E+09 | 5822871.80 | 0.118180E+09 | 0.326354E+09 | 288279.35 |
September | 0.101800E+09 | 179187.76 | 0.101620E+09 | 0.282221E+09 | 410339.34 |
October | 0.101109E+09 | 0.00 | 0.101109E+09 | 0.261934E+09 | 474318.65 |
November | 92584943.17 | 0.00 | 92584943.17 | 0.235855E+09 | 2628932.82 |
December | 90654000.44 | 0.00 | 90654000.44 | 0.221450E+09 | 13091332.28 |
Annual Sum or Average | 0.136636E+10 | 73956578.22 | 0.129241E+10 | 0.367338E+10 | 30900724.89 |
Minimum of Months | 89908303.92 | 0.00 | 89908303.92 | 0.221450E+09 | 12662.21 |
Maximum of Months | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.457034E+09 | 13091332.28 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340721E+09 | 0.120027E+09 | 0.220694E+09 | 0.742835E+09 | 17871332.66 |
February | 0.337767E+09 | 0.119640E+09 | 0.218126E+09 | 0.750851E+09 | 4331067.10 |
March | 0.418480E+09 | 0.165079E+09 | 0.253401E+09 | 0.961945E+09 | 680234.67 |
April | 0.407051E+09 | 0.155660E+09 | 0.251391E+09 | 0.974445E+09 | 23668.92 |
May | 0.358510E+09 | 0.106392E+09 | 0.252118E+09 | 0.909496E+09 | 528004.08 |
June | 0.375602E+09 | 0.129405E+09 | 0.246197E+09 | 0.919844E+09 | 815931.31 |
July | 0.330866E+09 | 77896981.51 | 0.252969E+09 | 0.766062E+09 | 1305679.13 |
August | 0.360854E+09 | 0.107247E+09 | 0.253607E+09 | 0.823352E+09 | 511734.94 |
September | 0.326000E+09 | 90332823.10 | 0.235667E+09 | 0.767720E+09 | 736687.40 |
October | 0.316730E+09 | 81775732.61 | 0.234955E+09 | 0.716190E+09 | 819137.86 |
November | 0.298863E+09 | 81603046.92 | 0.217260E+09 | 0.667927E+09 | 4740917.09 |
December | 0.316342E+09 | 0.103668E+09 | 0.212674E+09 | 0.683932E+09 | 24050223.81 |
Annual Sum or Average | 0.418779E+10 | 0.133873E+10 | 0.284906E+10 | 0.968460E+10 | 56414618.98 |
Minimum of Months | 0.298863E+09 | 77896981.51 | 0.212674E+09 | 0.667927E+09 | 23668.92 |
Maximum of Months | 0.418480E+09 | 0.165079E+09 | 0.253607E+09 | 0.974445E+09 | 24050223.81 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.361833E+09 | 0.150673E+09 | 0.211160E+09 | 0.767436E+09 | 13632921.67 |
February | 0.276455E+09 | 89156620.63 | 0.187299E+09 | 0.644051E+09 | 2938722.11 |
March | 0.213439E+09 | 31676106.08 | 0.181763E+09 | 0.594308E+09 | 422878.03 |
April | 0.153127E+09 | 881540.01 | 0.152245E+09 | 0.495755E+09 | 0.00 |
May | 0.156654E+09 | 0.00 | 0.156654E+09 | 0.517344E+09 | 244930.55 |
June | 0.151055E+09 | 0.00 | 0.151055E+09 | 0.493159E+09 | 363271.62 |
July | 0.160796E+09 | 0.00 | 0.160796E+09 | 0.442785E+09 | 539966.18 |
August | 0.156343E+09 | 13187.17 | 0.156330E+09 | 0.444984E+09 | 220416.32 |
September | 0.166962E+09 | 4575173.96 | 0.162387E+09 | 0.465455E+09 | 427512.31 |
October | 0.224687E+09 | 34093402.53 | 0.190593E+09 | 0.546080E+09 | 535788.89 |
November | 0.287000E+09 | 88671765.62 | 0.198329E+09 | 0.636500E+09 | 3725639.00 |
December | 0.363102E+09 | 0.154983E+09 | 0.208119E+09 | 0.749763E+09 | 18729218.95 |
Annual Sum or Average | 0.267145E+10 | 0.554724E+09 | 0.211673E+10 | 0.679762E+10 | 41781265.63 |
Minimum of Months | 0.151055E+09 | 0.00 | 0.151055E+09 | 0.442785E+09 | 0.00 |
Maximum of Months | 0.363102E+09 | 0.154983E+09 | 0.211160E+09 | 0.767436E+09 | 18729218.95 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.653179E+09 | 0.00 | 0.653179E+09 | 0.145940E+10 | 0.231219E+09 |
February | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.147452E+10 | 0.143619E+09 |
March | 0.715557E+09 | 35680.36 | 0.715521E+09 | 0.178076E+10 | 82674421.23 |
April | 0.767467E+09 | 18494089.18 | 0.748973E+09 | 0.198372E+10 | 19812495.03 |
May | 0.994921E+09 | 0.103622E+09 | 0.891298E+09 | 0.251703E+10 | 44369146.40 |
June | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.284625E+10 | 44855093.64 |
July | 0.104969E+10 | 0.111366E+09 | 0.938320E+09 | 0.232370E+10 | 98558935.32 |
August | 0.867989E+09 | 40758558.92 | 0.827230E+09 | 0.196119E+10 | 62660956.96 |
September | 0.712570E+09 | 1254266.85 | 0.711316E+09 | 0.168383E+10 | 65615680.94 |
October | 0.707734E+09 | 0.00 | 0.707734E+09 | 0.155637E+10 | 99845998.36 |
November | 0.648070E+09 | 0.00 | 0.648070E+09 | 0.143362E+10 | 0.135863E+09 |
December | 0.634554E+09 | 0.00 | 0.634554E+09 | 0.139653E+10 | 0.274642E+09 |
Annual Sum or Average | 0.956418E+10 | 0.517676E+09 | 0.904650E+10 | 0.224169E+11 | 0.130374E+10 |
Minimum of Months | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.139653E+10 | 19812495.03 |
Maximum of Months | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.284625E+10 | 0.274642E+09 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.653179E+09 | 0.00 | 0.653179E+09 | 0.142631E+10 | 0.249085E+09 |
February | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.144474E+10 | 0.157136E+09 |
March | 0.715557E+09 | 35680.36 | 0.715521E+09 | 0.174282E+10 | 94736109.78 |
April | 0.767467E+09 | 18494089.18 | 0.748973E+09 | 0.194107E+10 | 23906131.91 |
May | 0.994921E+09 | 0.103622E+09 | 0.891298E+09 | 0.247503E+10 | 51501603.10 |
June | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.280807E+10 | 51359055.42 |
July | 0.104969E+10 | 0.111366E+09 | 0.938320E+09 | 0.228569E+10 | 0.112476E+09 |
August | 0.867989E+09 | 40758558.92 | 0.827230E+09 | 0.191591E+10 | 75727023.38 |
September | 0.712570E+09 | 1254266.85 | 0.711316E+09 | 0.164489E+10 | 78492957.92 |
October | 0.707734E+09 | 0.00 | 0.707734E+09 | 0.151744E+10 | 0.118006E+09 |
November | 0.648070E+09 | 0.00 | 0.648070E+09 | 0.139988E+10 | 0.152806E+09 |
December | 0.634554E+09 | 0.00 | 0.634554E+09 | 0.136391E+10 | 0.294469E+09 |
Annual Sum or Average | 0.956418E+10 | 0.517676E+09 | 0.904650E+10 | 0.219658E+11 | 0.145970E+10 |
Minimum of Months | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.136391E+10 | 23906131.91 |
Maximum of Months | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.280807E+10 | 0.294469E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93314774.48 | 0.00 | 93314774.48 | 0.233474E+09 | 35886978.13 |
February | 89908303.92 | 0.00 | 89908303.92 | 0.233030E+09 | 23198499.85 |
March | 0.102226E+09 | 5097.39 | 0.102221E+09 | 0.273915E+09 | 15901951.01 |
April | 0.109642E+09 | 2642112.80 | 0.107000E+09 | 0.303474E+09 | 5080932.31 |
May | 0.142137E+09 | 14803736.87 | 0.127333E+09 | 0.378926E+09 | 9013251.54 |
June | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.430525E+09 | 8999896.60 |
July | 0.149961E+09 | 15910101.18 | 0.134051E+09 | 0.360420E+09 | 16036394.88 |
August | 0.124003E+09 | 5822871.80 | 0.118180E+09 | 0.295264E+09 | 12226185.87 |
September | 0.101800E+09 | 179187.76 | 0.101620E+09 | 0.264608E+09 | 12372373.28 |
October | 0.101109E+09 | 0.00 | 0.101109E+09 | 0.240248E+09 | 18245287.18 |
November | 92584943.17 | 0.00 | 92584943.17 | 0.230127E+09 | 21592983.54 |
December | 90654000.44 | 0.00 | 90654000.44 | 0.225456E+09 | 41329706.43 |
Annual Sum or Average | 0.136636E+10 | 73956578.22 | 0.129241E+10 | 0.346947E+10 | 0.219884E+09 |
Minimum of Months | 89908303.92 | 0.00 | 89908303.92 | 0.225456E+09 | 5080932.31 |
Maximum of Months | 0.169023E+09 | 34593470.42 | 0.134430E+09 | 0.430525E+09 | 41329706.43 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.671657E+09 | 0.226453E+09 | 0.445204E+09 | 0.146331E+10 | 0.132953E+09 |
February | 0.687579E+09 | 0.251836E+09 | 0.435743E+09 | 0.151461E+10 | 86760317.14 |
March | 0.831176E+09 | 0.325333E+09 | 0.505843E+09 | 0.182195E+10 | 60184995.70 |
April | 0.811478E+09 | 0.309548E+09 | 0.501930E+09 | 0.184668E+10 | 19340276.86 |
May | 0.721809E+09 | 0.218763E+09 | 0.503046E+09 | 0.171267E+10 | 34263262.65 |
June | 0.743542E+09 | 0.244816E+09 | 0.498726E+09 | 0.173707E+10 | 34435834.54 |
July | 0.657062E+09 | 0.147501E+09 | 0.509562E+09 | 0.148488E+10 | 60278659.10 |
August | 0.722287E+09 | 0.212324E+09 | 0.509963E+09 | 0.154365E+10 | 46685334.64 |
September | 0.656664E+09 | 0.179097E+09 | 0.477567E+09 | 0.149257E+10 | 46633300.77 |
October | 0.636626E+09 | 0.163352E+09 | 0.473274E+09 | 0.136440E+10 | 69418169.26 |
November | 0.596419E+09 | 0.165024E+09 | 0.431395E+09 | 0.131582E+10 | 81271048.68 |
December | 0.629974E+09 | 0.202332E+09 | 0.427642E+09 | 0.137602E+10 | 0.153860E+09 |
Annual Sum or Average | 0.836627E+10 | 0.264638E+10 | 0.571989E+10 | 0.186736E+11 | 0.826085E+09 |
Minimum of Months | 0.596419E+09 | 0.147501E+09 | 0.427642E+09 | 0.131582E+10 | 19340276.86 |
Maximum of Months | 0.831176E+09 | 0.325333E+09 | 0.509963E+09 | 0.184668E+10 | 0.153860E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246716E+09 | 0.102737E+09 | 0.143979E+09 | 0.526750E+09 | 35232912.08 |
February | 0.188501E+09 | 60791535.26 | 0.127710E+09 | 0.433849E+09 | 23027259.82 |
March | 0.145534E+09 | 21598386.14 | 0.123935E+09 | 0.368648E+09 | 15961505.50 |
April | 0.104410E+09 | 601078.98 | 0.103808E+09 | 0.290587E+09 | 5130571.45 |
May | 0.106815E+09 | 0.00 | 0.106815E+09 | 0.302115E+09 | 9068499.45 |
June | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.289099E+09 | 9208401.04 |
July | 0.109639E+09 | 0.00 | 0.109639E+09 | 0.275735E+09 | 16188904.46 |
August | 0.106603E+09 | 8991.69 | 0.106594E+09 | 0.256748E+09 | 12434048.49 |
September | 0.113843E+09 | 3119587.16 | 0.110724E+09 | 0.289488E+09 | 12372327.10 |
October | 0.153203E+09 | 23246622.26 | 0.129956E+09 | 0.345423E+09 | 18128366.91 |
November | 0.195692E+09 | 60460936.36 | 0.135231E+09 | 0.428887E+09 | 21373844.31 |
December | 0.247581E+09 | 0.105675E+09 | 0.141906E+09 | 0.521730E+09 | 40753988.78 |
Annual Sum or Average | 0.182153E+10 | 0.378239E+09 | 0.144329E+10 | 0.432906E+10 | 0.218881E+09 |
Minimum of Months | 0.102997E+09 | 0.00 | 0.102997E+09 | 0.256748E+09 | 5130571.45 |
Maximum of Months | 0.247581E+09 | 0.105675E+09 | 0.143979E+09 | 0.526750E+09 | 40753988.78 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118177E+09 | 0.00 | 0.118177E+09 | 0.268645E+09 | 31935229.53 |
February | 0.113863E+09 | 0.00 | 0.113863E+09 | 0.270069E+09 | 18781653.96 |
March | 0.129463E+09 | 6455.52 | 0.129457E+09 | 0.332228E+09 | 7639654.33 |
April | 0.138855E+09 | 3346069.16 | 0.135509E+09 | 0.374335E+09 | 1158412.48 |
May | 0.180007E+09 | 18747998.68 | 0.161259E+09 | 0.473729E+09 | 3468886.15 |
June | 0.214057E+09 | 43810447.55 | 0.170247E+09 | 0.531269E+09 | 4040604.52 |
July | 0.189916E+09 | 20149139.27 | 0.169767E+09 | 0.436739E+09 | 8465909.23 |
August | 0.157042E+09 | 7374299.74 | 0.149668E+09 | 0.378007E+09 | 3104014.73 |
September | 0.128923E+09 | 226930.00 | 0.128696E+09 | 0.320021E+09 | 4095874.39 |
October | 0.128048E+09 | 0.00 | 0.128048E+09 | 0.296798E+09 | 6248073.92 |
November | 0.117253E+09 | 0.00 | 0.117253E+09 | 0.267048E+09 | 14497190.19 |
December | 0.114808E+09 | 0.00 | 0.114808E+09 | 0.257617E+09 | 37990955.03 |
Annual Sum or Average | 0.173041E+10 | 93661339.92 | 0.163675E+10 | 0.420651E+10 | 0.141426E+09 |
Minimum of Months | 0.113863E+09 | 0.00 | 0.113863E+09 | 0.257617E+09 | 1158412.48 |
Maximum of Months | 0.214057E+09 | 43810447.55 | 0.170247E+09 | 0.531269E+09 | 37990955.03 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105734E+09 | 0.00 | 0.105734E+09 | 0.240358E+09 | 28572570.86 |
February | 0.101874E+09 | 0.00 | 0.101874E+09 | 0.241632E+09 | 16806633.11 |
March | 0.115831E+09 | 5775.78 | 0.115825E+09 | 0.297246E+09 | 6835227.68 |
April | 0.124234E+09 | 2993740.75 | 0.121240E+09 | 0.334919E+09 | 1036436.04 |
May | 0.161053E+09 | 16773905.45 | 0.144279E+09 | 0.423848E+09 | 3103625.58 |
June | 0.191518E+09 | 39197373.42 | 0.152320E+09 | 0.475329E+09 | 3615144.17 |
July | 0.169919E+09 | 18027511.25 | 0.151891E+09 | 0.390752E+09 | 7574481.06 |
August | 0.140506E+09 | 6597813.92 | 0.133908E+09 | 0.338205E+09 | 2777173.74 |
September | 0.115348E+09 | 203035.13 | 0.115145E+09 | 0.286324E+09 | 3664594.33 |
October | 0.114565E+09 | 0.00 | 0.114565E+09 | 0.265546E+09 | 5590175.41 |
November | 0.104907E+09 | 0.00 | 0.104907E+09 | 0.238928E+09 | 12971444.02 |
December | 0.102719E+09 | 0.00 | 0.102719E+09 | 0.230491E+09 | 33990651.41 |
Annual Sum or Average | 0.154821E+10 | 83799155.71 | 0.146441E+10 | 0.376358E+10 | 0.126538E+09 |
Minimum of Months | 0.101874E+09 | 0.00 | 0.101874E+09 | 0.230491E+09 | 1036436.04 |
Maximum of Months | 0.191518E+09 | 39197373.42 | 0.152320E+09 | 0.475329E+09 | 33990651.41 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921064E+09 | 0.383546E+09 | 0.537518E+09 | 0.188036E+10 | 90497583.77 |
February | 0.703732E+09 | 0.226953E+09 | 0.476779E+09 | 0.154284E+10 | 53614869.63 |
March | 0.543321E+09 | 80633211.45 | 0.462688E+09 | 0.134028E+10 | 21947170.00 |
April | 0.389792E+09 | 2244006.94 | 0.387548E+09 | 0.106235E+10 | 3365353.54 |
May | 0.398772E+09 | 0.00 | 0.398772E+09 | 0.111923E+10 | 10449223.35 |
June | 0.384519E+09 | 0.00 | 0.384519E+09 | 0.105360E+10 | 12296893.28 |
July | 0.409316E+09 | 0.00 | 0.409316E+09 | 0.973944E+09 | 25658836.15 |
August | 0.397980E+09 | 33568.65 | 0.397946E+09 | 0.978561E+09 | 9308269.74 |
September | 0.425011E+09 | 11646348.46 | 0.413364E+09 | 0.103706E+10 | 12148869.60 |
October | 0.571952E+09 | 86786568.05 | 0.485165E+09 | 0.126566E+10 | 18010345.41 |
November | 0.730575E+09 | 0.225719E+09 | 0.504856E+09 | 0.152387E+10 | 41412131.79 |
December | 0.924294E+09 | 0.394517E+09 | 0.529777E+09 | 0.185672E+10 | 0.108096E+09 |
Annual Sum or Average | 0.680033E+10 | 0.141208E+10 | 0.538825E+10 | 0.156345E+11 | 0.406806E+09 |
Minimum of Months | 0.384519E+09 | 0.00 | 0.384519E+09 | 0.973944E+09 | 3365353.54 |
Maximum of Months | 0.924294E+09 | 0.394517E+09 | 0.537518E+09 | 0.188036E+10 | 0.108096E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 921.42 | 60.72 | 465.88 | 194.00 | 271.88 | 0.00 | 0.00 |
February | 830.92 | 46.23 | 394.09 | 127.09 | 267.00 | 0.00 | 0.00 |
March | 636.01 | 24.51 | 274.81 | 40.79 | 234.03 | 0.00 | 0.00 |
April | 507.16 | 3.29 | 203.73 | 1.17 | 202.56 | 0.00 | 0.00 |
May | 525.71 | 7.26 | 201.70 | 0.00 | 201.70 | 0.00 | 0.00 |
June | 511.03 | 8.46 | 200.97 | 0.00 | 200.97 | 0.00 | 0.00 |
July | 468.95 | 19.40 | 207.03 | 0.00 | 207.03 | 0.00 | 0.00 |
August | 460.62 | 9.57 | 201.30 | 0.02 | 201.28 | 0.00 | 0.00 |
September | 509.28 | 11.19 | 222.14 | 6.09 | 216.05 | 0.00 | 0.00 |
October | 612.55 | 17.08 | 289.30 | 43.90 | 245.40 | 0.00 | 0.00 |
November | 767.66 | 32.71 | 381.85 | 117.98 | 263.87 | 0.00 | 0.00 |
December | 909.95 | 69.88 | 467.52 | 199.55 | 267.97 | 0.00 | 0.00 |
Annual Sum or Average | 637.56 | 25.82 | 292.13 | 60.66 | 231.47 | 0.00 | 0.00 |
Minimum of Months | 460.62 | 3.29 | 200.97 | 0.00 | 200.97 | 0.00 | 0.00 |
Maximum of Months | 921.42 | 69.88 | 467.52 | 199.55 | 271.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2578.89 | 179.32 | 1311.89 | 546.30 | 765.60 | 0.00 | 0.00 |
February | 2331.34 | 132.16 | 1109.73 | 357.89 | 751.84 | 0.00 | 0.00 |
March | 1798.35 | 71.09 | 773.86 | 114.85 | 659.01 | 0.00 | 0.00 |
April | 1450.17 | 13.13 | 573.69 | 3.30 | 570.39 | 0.00 | 0.00 |
May | 1493.48 | 28.26 | 567.98 | 0.00 | 567.98 | 0.00 | 0.00 |
June | 1460.75 | 29.07 | 565.93 | 0.00 | 565.93 | 0.00 | 0.00 |
July | 1334.11 | 66.01 | 582.99 | 0.00 | 582.99 | 0.00 | 0.00 |
August | 1302.94 | 38.36 | 566.85 | 0.05 | 566.80 | 0.00 | 0.00 |
September | 1444.29 | 43.68 | 625.53 | 17.14 | 608.39 | 0.00 | 0.00 |
October | 1721.02 | 65.37 | 814.64 | 123.61 | 691.03 | 0.00 | 0.00 |
November | 2151.95 | 106.04 | 1075.26 | 332.21 | 743.04 | 0.00 | 0.00 |
December | 2545.50 | 207.89 | 1316.49 | 561.92 | 754.57 | 0.00 | 0.00 |
Annual Sum or Average | 1798.62 | 81.65 | 822.63 | 170.82 | 651.81 | 0.00 | 0.00 |
Minimum of Months | 1302.94 | 13.13 | 565.93 | 0.00 | 565.93 | 0.00 | 0.00 |
Maximum of Months | 2578.89 | 207.89 | 1316.49 | 561.92 | 765.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3499.18 | 204.74 | 1704.22 | 709.67 | 994.55 | 0.00 | 0.00 |
February | 3171.06 | 148.29 | 1441.61 | 464.92 | 976.69 | 0.00 | 0.00 |
March | 2456.62 | 76.31 | 1005.29 | 149.19 | 856.09 | 0.00 | 0.00 |
April | 1976.96 | 16.02 | 745.26 | 4.29 | 740.97 | 0.00 | 0.00 |
May | 2007.52 | 34.53 | 737.83 | 0.00 | 737.83 | 0.00 | 0.00 |
June | 1949.97 | 38.19 | 735.18 | 0.00 | 735.18 | 0.00 | 0.00 |
July | 1775.36 | 84.29 | 757.34 | 0.00 | 757.34 | 0.00 | 0.00 |
August | 1746.79 | 46.21 | 736.37 | 0.06 | 736.31 | 0.00 | 0.00 |
September | 1958.25 | 48.11 | 812.60 | 22.27 | 790.33 | 0.00 | 0.00 |
October | 2335.16 | 67.51 | 1058.27 | 160.58 | 897.69 | 0.00 | 0.00 |
November | 2925.53 | 117.35 | 1396.82 | 431.56 | 965.26 | 0.00 | 0.00 |
December | 3449.02 | 241.70 | 1710.20 | 729.97 | 980.23 | 0.00 | 0.00 |
Annual Sum or Average | 2434.17 | 93.58 | 1068.65 | 221.90 | 846.74 | 0.00 | 0.00 |
Minimum of Months | 1746.79 | 16.02 | 735.18 | 0.00 | 735.18 | 0.00 | 0.00 |
Maximum of Months | 3499.18 | 241.70 | 1710.20 | 729.97 | 994.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 472.29 | 12.78 | 219.32 | 83.17 | 136.15 | 0.00 | 0.00 |
February | 489.93 | 4.60 | 217.54 | 74.58 | 142.95 | 0.00 | 0.00 |
March | 506.78 | 0.89 | 210.58 | 69.70 | 140.88 | 0.00 | 0.00 |
April | 503.27 | 0.05 | 197.32 | 60.29 | 137.04 | 0.00 | 0.00 |
May | 469.17 | 0.32 | 173.73 | 39.72 | 134.01 | 0.00 | 0.00 |
June | 482.70 | 0.47 | 184.64 | 49.92 | 134.72 | 0.00 | 0.00 |
July | 398.86 | 0.80 | 164.47 | 29.08 | 135.38 | 0.00 | 0.00 |
August | 419.32 | 0.35 | 174.53 | 40.04 | 134.48 | 0.00 | 0.00 |
September | 417.86 | 0.40 | 169.69 | 36.05 | 133.64 | 0.00 | 0.00 |
October | 405.71 | 0.61 | 175.45 | 39.21 | 136.24 | 0.00 | 0.00 |
November | 424.47 | 3.84 | 190.80 | 54.81 | 135.99 | 0.00 | 0.00 |
December | 446.65 | 16.90 | 210.54 | 78.16 | 132.39 | 0.00 | 0.00 |
Annual Sum or Average | 452.74 | 3.52 | 190.55 | 54.44 | 136.11 | 0.00 | 0.00 |
Minimum of Months | 398.86 | 0.05 | 164.47 | 29.08 | 132.39 | 0.00 | 0.00 |
Maximum of Months | 506.78 | 16.90 | 219.32 | 83.17 | 142.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 368.31 | 12.51 | 162.05 | 44.81 | 117.24 | 0.00 | 0.00 |
February | 410.98 | 4.38 | 176.78 | 49.45 | 127.33 | 0.00 | 0.00 |
March | 472.45 | 0.81 | 194.41 | 61.64 | 132.77 | 0.00 | 0.00 |
April | 507.53 | 0.06 | 199.34 | 61.07 | 138.27 | 0.00 | 0.00 |
May | 495.78 | 0.34 | 186.92 | 45.25 | 141.67 | 0.00 | 0.00 |
June | 533.56 | 0.52 | 210.12 | 63.27 | 146.85 | 0.00 | 0.00 |
July | 428.87 | 0.88 | 179.52 | 35.02 | 144.50 | 0.00 | 0.00 |
August | 432.24 | 0.36 | 181.02 | 42.22 | 138.81 | 0.00 | 0.00 |
September | 408.63 | 0.40 | 165.05 | 34.92 | 130.13 | 0.00 | 0.00 |
October | 368.28 | 0.57 | 156.00 | 30.53 | 125.47 | 0.00 | 0.00 |
November | 351.54 | 3.58 | 151.02 | 31.48 | 119.54 | 0.00 | 0.00 |
December | 341.66 | 16.43 | 151.96 | 38.71 | 113.25 | 0.00 | 0.00 |
Annual Sum or Average | 426.52 | 3.42 | 176.12 | 44.80 | 131.33 | 0.00 | 0.00 |
Minimum of Months | 341.66 | 0.06 | 151.02 | 30.53 | 113.25 | 0.00 | 0.00 |
Maximum of Months | 533.56 | 16.43 | 210.12 | 63.27 | 146.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.34 | 6.99 | 73.68 | 30.68 | 43.00 | 0.00 | 0.00 |
February | 139.89 | 4.16 | 62.32 | 20.10 | 42.22 | 0.00 | 0.00 |
March | 111.08 | 1.58 | 43.46 | 6.45 | 37.01 | 0.00 | 0.00 |
April | 92.73 | 0.28 | 32.22 | 0.19 | 32.03 | 0.00 | 0.00 |
May | 93.91 | 0.58 | 31.90 | 0.00 | 31.90 | 0.00 | 0.00 |
June | 92.66 | 0.65 | 31.78 | 0.00 | 31.78 | 0.00 | 0.00 |
July | 80.60 | 1.63 | 32.74 | 0.00 | 32.74 | 0.00 | 0.00 |
August | 79.57 | 0.97 | 31.83 | 0.00 | 31.83 | 0.00 | 0.00 |
September | 88.07 | 1.03 | 35.13 | 0.96 | 34.17 | 0.00 | 0.00 |
October | 102.20 | 1.63 | 45.75 | 6.94 | 38.81 | 0.00 | 0.00 |
November | 127.78 | 3.49 | 60.39 | 18.66 | 41.73 | 0.00 | 0.00 |
December | 149.85 | 8.71 | 73.93 | 31.56 | 42.38 | 0.00 | 0.00 |
Annual Sum or Average | 109.07 | 2.64 | 46.20 | 9.59 | 36.61 | 0.00 | 0.00 |
Minimum of Months | 79.57 | 0.28 | 31.78 | 0.00 | 31.78 | 0.00 | 0.00 |
Maximum of Months | 152.34 | 8.71 | 73.93 | 31.56 | 43.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 77.04 | 2.55 | 27.88 | 0.00 | 27.88 | 0.00 | 0.00 |
February | 86.00 | 0.54 | 29.74 | 0.00 | 29.74 | 0.00 | 0.00 |
March | 97.50 | 0.08 | 30.54 | 0.00 | 30.54 | 0.00 | 0.00 |
April | 111.79 | 0.00 | 33.84 | 0.82 | 33.03 | 0.00 | 0.00 |
May | 130.95 | 0.03 | 42.46 | 4.42 | 38.04 | 0.00 | 0.00 |
June | 148.89 | 0.05 | 52.17 | 10.68 | 41.50 | 0.00 | 0.00 |
July | 118.57 | 0.07 | 44.80 | 4.75 | 40.04 | 0.00 | 0.00 |
August | 105.22 | 0.01 | 37.04 | 1.74 | 35.30 | 0.00 | 0.00 |
September | 94.97 | 0.02 | 31.42 | 0.06 | 31.37 | 0.00 | 0.00 |
October | 85.81 | 0.01 | 30.20 | 0.00 | 30.20 | 0.00 | 0.00 |
November | 79.80 | 0.50 | 28.58 | 0.00 | 28.58 | 0.00 | 0.00 |
December | 72.57 | 3.40 | 27.08 | 0.00 | 27.08 | 0.00 | 0.00 |
Annual Sum or Average | 100.79 | 0.61 | 34.67 | 1.88 | 32.79 | 0.00 | 0.00 |
Minimum of Months | 72.57 | 0.00 | 27.08 | 0.00 | 27.08 | 0.00 | 0.00 |
Maximum of Months | 148.89 | 3.40 | 52.17 | 10.68 | 41.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 467.56 | 12.51 | 217.51 | 80.63 | 136.87 | 0.00 | 0.00 |
February | 494.34 | 4.49 | 220.04 | 77.18 | 142.86 | 0.00 | 0.00 |
March | 505.94 | 0.84 | 209.51 | 68.80 | 140.71 | 0.00 | 0.00 |
April | 506.07 | 0.02 | 196.83 | 59.95 | 136.88 | 0.00 | 0.00 |
May | 473.52 | 0.27 | 174.64 | 40.84 | 133.79 | 0.00 | 0.00 |
June | 482.71 | 0.41 | 183.18 | 47.23 | 135.95 | 0.00 | 0.00 |
July | 398.48 | 0.70 | 163.60 | 27.54 | 136.07 | 0.00 | 0.00 |
August | 421.25 | 0.30 | 174.65 | 39.64 | 135.00 | 0.00 | 0.00 |
September | 421.94 | 0.36 | 170.60 | 35.75 | 134.85 | 0.00 | 0.00 |
October | 408.47 | 0.57 | 176.05 | 39.18 | 136.88 | 0.00 | 0.00 |
November | 424.62 | 3.74 | 190.56 | 55.16 | 135.39 | 0.00 | 0.00 |
December | 443.74 | 16.48 | 210.05 | 77.23 | 132.82 | 0.00 | 0.00 |
Annual Sum or Average | 453.67 | 3.41 | 190.42 | 53.95 | 136.46 | 0.00 | 0.00 |
Minimum of Months | 398.48 | 0.02 | 163.60 | 27.54 | 132.82 | 0.00 | 0.00 |
Maximum of Months | 506.07 | 16.48 | 220.04 | 80.63 | 142.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.04 | 11.78 | 160.23 | 42.28 | 117.96 | 0.00 | 0.00 |
February | 415.18 | 4.11 | 179.28 | 52.05 | 127.23 | 0.00 | 0.00 |
March | 471.51 | 0.76 | 193.34 | 60.74 | 132.60 | 0.00 | 0.00 |
April | 510.35 | 0.02 | 198.85 | 60.74 | 138.11 | 0.00 | 0.00 |
May | 500.18 | 0.29 | 187.82 | 46.37 | 141.46 | 0.00 | 0.00 |
June | 533.68 | 0.45 | 208.65 | 60.57 | 148.07 | 0.00 | 0.00 |
July | 428.57 | 0.78 | 178.66 | 33.48 | 145.18 | 0.00 | 0.00 |
August | 434.22 | 0.30 | 181.14 | 41.81 | 139.33 | 0.00 | 0.00 |
September | 412.70 | 0.36 | 165.95 | 34.62 | 131.34 | 0.00 | 0.00 |
October | 370.97 | 0.53 | 156.60 | 30.50 | 126.11 | 0.00 | 0.00 |
November | 351.55 | 3.44 | 150.78 | 31.84 | 118.94 | 0.00 | 0.00 |
December | 338.24 | 15.55 | 151.46 | 37.77 | 113.68 | 0.00 | 0.00 |
Annual Sum or Average | 427.35 | 3.21 | 175.98 | 44.31 | 131.68 | 0.00 | 0.00 |
Minimum of Months | 338.24 | 0.02 | 150.78 | 30.50 | 113.68 | 0.00 | 0.00 |
Maximum of Months | 533.68 | 15.55 | 208.65 | 60.74 | 148.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 484.54 | 26.48 | 220.02 | 66.47 | 153.55 | 0.00 | 0.00 |
February | 469.13 | 16.40 | 199.45 | 43.55 | 155.90 | 0.00 | 0.00 |
March | 428.49 | 5.34 | 160.32 | 13.98 | 146.34 | 0.00 | 0.00 |
April | 419.05 | 0.74 | 143.13 | 2.17 | 140.96 | 0.00 | 0.00 |
May | 460.74 | 2.28 | 161.10 | 9.58 | 151.52 | 0.00 | 0.00 |
June | 491.39 | 2.75 | 181.89 | 23.13 | 158.76 | 0.00 | 0.00 |
July | 415.89 | 4.97 | 167.99 | 10.30 | 157.69 | 0.00 | 0.00 |
August | 386.83 | 1.89 | 149.22 | 3.77 | 145.45 | 0.00 | 0.00 |
September | 383.52 | 2.26 | 144.19 | 2.21 | 141.99 | 0.00 | 0.00 |
October | 395.21 | 3.57 | 164.56 | 15.04 | 149.52 | 0.00 | 0.00 |
November | 435.79 | 11.22 | 192.75 | 40.42 | 152.33 | 0.00 | 0.00 |
December | 471.47 | 32.25 | 218.86 | 68.38 | 150.48 | 0.00 | 0.00 |
Annual Sum or Average | 436.62 | 9.18 | 175.20 | 24.85 | 150.35 | 0.00 | 0.00 |
Minimum of Months | 383.52 | 0.74 | 143.13 | 2.17 | 140.96 | 0.00 | 0.00 |
Maximum of Months | 491.39 | 32.25 | 220.02 | 68.38 | 158.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 467.94 | 10.53 | 219.32 | 83.17 | 136.15 | 0.00 | 0.00 |
February | 486.61 | 2.94 | 217.54 | 74.58 | 142.95 | 0.00 | 0.00 |
March | 504.50 | 0.41 | 210.58 | 69.70 | 140.88 | 0.00 | 0.00 |
April | 500.88 | 0.01 | 197.32 | 60.29 | 137.04 | 0.00 | 0.00 |
May | 467.45 | 0.29 | 173.73 | 39.72 | 134.01 | 0.00 | 0.00 |
June | 481.36 | 0.44 | 184.64 | 49.92 | 134.72 | 0.00 | 0.00 |
July | 395.89 | 0.70 | 164.47 | 29.08 | 135.38 | 0.00 | 0.00 |
August | 416.72 | 0.29 | 174.53 | 40.04 | 134.48 | 0.00 | 0.00 |
September | 414.26 | 0.45 | 169.69 | 36.05 | 133.64 | 0.00 | 0.00 |
October | 402.17 | 0.51 | 175.45 | 39.21 | 136.24 | 0.00 | 0.00 |
November | 420.81 | 3.07 | 190.80 | 54.81 | 135.99 | 0.00 | 0.00 |
December | 441.92 | 14.30 | 210.54 | 78.16 | 132.39 | 0.00 | 0.00 |
Annual Sum or Average | 449.69 | 2.85 | 190.55 | 54.44 | 136.11 | 0.00 | 0.00 |
Minimum of Months | 395.89 | 0.01 | 164.47 | 29.08 | 132.39 | 0.00 | 0.00 |
Maximum of Months | 504.50 | 14.30 | 219.32 | 83.17 | 142.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 364.97 | 10.31 | 162.05 | 44.81 | 117.24 | 0.00 | 0.00 |
February | 408.38 | 2.79 | 176.78 | 49.45 | 127.33 | 0.00 | 0.00 |
March | 470.24 | 0.40 | 194.41 | 61.64 | 132.77 | 0.00 | 0.00 |
April | 504.71 | 0.01 | 199.34 | 61.07 | 138.27 | 0.00 | 0.00 |
May | 493.45 | 0.30 | 186.92 | 45.25 | 141.67 | 0.00 | 0.00 |
June | 531.20 | 0.49 | 210.12 | 63.27 | 146.85 | 0.00 | 0.00 |
July | 425.38 | 0.75 | 179.52 | 35.02 | 144.50 | 0.00 | 0.00 |
August | 429.25 | 0.30 | 181.02 | 42.22 | 138.81 | 0.00 | 0.00 |
September | 405.07 | 0.44 | 165.05 | 34.92 | 130.13 | 0.00 | 0.00 |
October | 365.19 | 0.48 | 156.00 | 30.53 | 125.47 | 0.00 | 0.00 |
November | 348.68 | 2.84 | 151.02 | 31.48 | 119.54 | 0.00 | 0.00 |
December | 338.03 | 13.87 | 151.96 | 38.71 | 113.25 | 0.00 | 0.00 |
Annual Sum or Average | 423.58 | 2.77 | 176.12 | 44.80 | 131.33 | 0.00 | 0.00 |
Minimum of Months | 338.03 | 0.01 | 151.02 | 30.53 | 113.25 | 0.00 | 0.00 |
Maximum of Months | 531.20 | 13.87 | 210.12 | 63.27 | 146.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.53 | 5.09 | 135.09 | 56.25 | 78.84 | 0.00 | 0.00 |
February | 266.22 | 1.21 | 114.28 | 36.85 | 77.42 | 0.00 | 0.00 |
March | 221.89 | 0.16 | 79.69 | 11.83 | 67.86 | 0.00 | 0.00 |
April | 191.26 | 0.00 | 59.08 | 0.34 | 58.74 | 0.00 | 0.00 |
May | 193.15 | 0.09 | 58.49 | 0.00 | 58.49 | 0.00 | 0.00 |
June | 190.26 | 0.14 | 58.28 | 0.00 | 58.28 | 0.00 | 0.00 |
July | 165.32 | 0.20 | 60.03 | 0.00 | 60.03 | 0.00 | 0.00 |
August | 166.14 | 0.08 | 58.37 | 0.00 | 58.37 | 0.00 | 0.00 |
September | 179.57 | 0.16 | 64.41 | 1.77 | 62.65 | 0.00 | 0.00 |
October | 203.88 | 0.20 | 83.89 | 12.73 | 71.16 | 0.00 | 0.00 |
November | 245.56 | 1.44 | 110.73 | 34.21 | 76.52 | 0.00 | 0.00 |
December | 279.93 | 6.99 | 135.57 | 57.86 | 77.70 | 0.00 | 0.00 |
Annual Sum or Average | 215.55 | 1.32 | 84.71 | 17.59 | 67.12 | 0.00 | 0.00 |
Minimum of Months | 165.32 | 0.00 | 58.28 | 0.00 | 58.28 | 0.00 | 0.00 |
Maximum of Months | 286.53 | 6.99 | 135.57 | 57.86 | 78.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 544.88 | 86.33 | 243.87 | 0.00 | 243.87 | 0.00 | 0.00 |
February | 609.51 | 59.37 | 260.14 | 0.00 | 260.14 | 0.00 | 0.00 |
March | 664.86 | 30.87 | 267.16 | 0.01 | 267.14 | 0.00 | 0.00 |
April | 765.32 | 7.64 | 296.09 | 7.14 | 288.96 | 0.00 | 0.00 |
May | 939.75 | 16.57 | 371.46 | 38.69 | 332.77 | 0.00 | 0.00 |
June | 1098.09 | 17.31 | 456.45 | 93.42 | 363.03 | 0.00 | 0.00 |
July | 867.57 | 36.80 | 391.91 | 41.58 | 350.33 | 0.00 | 0.00 |
August | 732.22 | 23.39 | 324.07 | 15.22 | 308.85 | 0.00 | 0.00 |
September | 649.62 | 25.31 | 274.91 | 0.48 | 274.43 | 0.00 | 0.00 |
October | 581.08 | 37.28 | 264.24 | 0.00 | 264.24 | 0.00 | 0.00 |
November | 553.09 | 52.42 | 250.03 | 0.00 | 250.03 | 0.00 | 0.00 |
December | 521.40 | 102.54 | 236.92 | 0.00 | 236.92 | 0.00 | 0.00 |
Annual Sum or Average | 710.84 | 41.34 | 303.28 | 16.42 | 286.86 | 0.00 | 0.00 |
Minimum of Months | 521.40 | 7.64 | 236.92 | 0.00 | 236.92 | 0.00 | 0.00 |
Maximum of Months | 1098.09 | 102.54 | 456.45 | 93.42 | 363.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 532.52 | 93.00 | 243.87 | 0.00 | 243.87 | 0.00 | 0.00 |
February | 597.20 | 64.95 | 260.14 | 0.00 | 260.14 | 0.00 | 0.00 |
March | 650.70 | 35.37 | 267.16 | 0.01 | 267.14 | 0.00 | 0.00 |
April | 748.87 | 9.22 | 296.09 | 7.14 | 288.96 | 0.00 | 0.00 |
May | 924.07 | 19.23 | 371.46 | 38.69 | 332.77 | 0.00 | 0.00 |
June | 1083.36 | 19.81 | 456.45 | 93.42 | 363.03 | 0.00 | 0.00 |
July | 853.38 | 41.99 | 391.91 | 41.58 | 350.33 | 0.00 | 0.00 |
August | 715.32 | 28.27 | 324.07 | 15.22 | 308.85 | 0.00 | 0.00 |
September | 634.60 | 30.28 | 274.91 | 0.48 | 274.43 | 0.00 | 0.00 |
October | 566.55 | 44.06 | 264.24 | 0.00 | 264.24 | 0.00 | 0.00 |
November | 540.08 | 58.95 | 250.03 | 0.00 | 250.03 | 0.00 | 0.00 |
December | 509.22 | 109.94 | 236.92 | 0.00 | 236.92 | 0.00 | 0.00 |
Annual Sum or Average | 696.53 | 46.29 | 303.28 | 16.42 | 286.86 | 0.00 | 0.00 |
Minimum of Months | 509.22 | 9.22 | 236.92 | 0.00 | 236.92 | 0.00 | 0.00 |
Maximum of Months | 1083.36 | 109.94 | 456.45 | 93.42 | 363.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 829.92 | 75.94 | 377.72 | 122.91 | 254.82 | 0.00 | 0.00 |
February | 901.66 | 54.89 | 399.30 | 129.23 | 270.07 | 0.00 | 0.00 |
March | 920.13 | 34.35 | 402.83 | 129.53 | 273.30 | 0.00 | 0.00 |
April | 941.64 | 11.40 | 395.65 | 120.68 | 274.98 | 0.00 | 0.00 |
May | 893.67 | 19.51 | 362.44 | 87.20 | 275.24 | 0.00 | 0.00 |
June | 947.76 | 20.27 | 391.81 | 107.80 | 284.01 | 0.00 | 0.00 |
July | 791.86 | 34.50 | 342.24 | 61.01 | 281.23 | 0.00 | 0.00 |
August | 782.40 | 26.61 | 355.77 | 81.45 | 274.32 | 0.00 | 0.00 |
September | 789.59 | 27.52 | 336.54 | 70.37 | 266.17 | 0.00 | 0.00 |
October | 728.05 | 39.47 | 332.64 | 69.67 | 262.97 | 0.00 | 0.00 |
November | 761.79 | 47.83 | 341.32 | 86.99 | 254.33 | 0.00 | 0.00 |
December | 792.50 | 87.88 | 361.49 | 115.00 | 246.49 | 0.00 | 0.00 |
Annual Sum or Average | 839.35 | 40.04 | 366.38 | 98.26 | 268.13 | 0.00 | 0.00 |
Minimum of Months | 728.05 | 11.40 | 332.64 | 61.01 | 246.49 | 0.00 | 0.00 |
Maximum of Months | 947.76 | 87.88 | 402.83 | 129.53 | 284.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 891.34 | 55.64 | 427.48 | 143.20 | 284.28 | 0.00 | 0.00 |
February | 848.85 | 36.46 | 380.07 | 93.81 | 286.26 | 0.00 | 0.00 |
March | 735.41 | 13.58 | 294.44 | 30.11 | 264.33 | 0.00 | 0.00 |
April | 683.49 | 2.14 | 251.88 | 3.31 | 248.57 | 0.00 | 0.00 |
May | 752.99 | 6.35 | 276.22 | 13.26 | 262.96 | 0.00 | 0.00 |
June | 794.77 | 7.64 | 304.82 | 32.02 | 272.80 | 0.00 | 0.00 |
July | 672.56 | 15.55 | 287.17 | 14.25 | 272.91 | 0.00 | 0.00 |
August | 632.75 | 5.66 | 259.68 | 5.23 | 254.45 | 0.00 | 0.00 |
September | 634.02 | 7.67 | 258.21 | 4.66 | 253.55 | 0.00 | 0.00 |
October | 682.49 | 11.14 | 304.12 | 32.40 | 271.72 | 0.00 | 0.00 |
November | 782.98 | 26.43 | 367.57 | 87.08 | 280.48 | 0.00 | 0.00 |
December | 874.73 | 66.50 | 426.31 | 147.30 | 279.01 | 0.00 | 0.00 |
Annual Sum or Average | 748.32 | 21.22 | 319.60 | 50.40 | 269.20 | 0.00 | 0.00 |
Minimum of Months | 632.75 | 2.14 | 251.88 | 3.31 | 248.57 | 0.00 | 0.00 |
Maximum of Months | 891.34 | 66.50 | 427.48 | 147.30 | 286.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246792E+10 | 0.162629E+09 | 0.124782E+10 | 0.519614E+09 | 0.728204E+09 | 0.00 | 0.00 |
February | 0.201016E+10 | 0.111834E+09 | 0.953384E+09 | 0.307467E+09 | 0.645917E+09 | 0.00 | 0.00 |
March | 0.170349E+10 | 65653767.82 | 0.736064E+09 | 0.109239E+09 | 0.626825E+09 | 0.00 | 0.00 |
April | 0.131456E+10 | 8524930.07 | 0.528069E+09 | 3040094.91 | 0.525028E+09 | 0.00 | 0.00 |
May | 0.140805E+10 | 19456734.89 | 0.540235E+09 | 0.00 | 0.540235E+09 | 0.00 | 0.00 |
June | 0.132458E+10 | 21937728.97 | 0.520926E+09 | 0.00 | 0.520926E+09 | 0.00 | 0.00 |
July | 0.125602E+10 | 51971248.29 | 0.554520E+09 | 0.00 | 0.554520E+09 | 0.00 | 0.00 |
August | 0.123373E+10 | 25643660.70 | 0.539162E+09 | 45477.52 | 0.539117E+09 | 0.00 | 0.00 |
September | 0.132007E+10 | 29008057.04 | 0.575783E+09 | 15778028.20 | 0.560005E+09 | 0.00 | 0.00 |
October | 0.164065E+10 | 45752873.41 | 0.774853E+09 | 0.117575E+09 | 0.657278E+09 | 0.00 | 0.00 |
November | 0.198976E+10 | 84795344.29 | 0.989750E+09 | 0.305795E+09 | 0.683955E+09 | 0.00 | 0.00 |
December | 0.243720E+10 | 0.187155E+09 | 0.125219E+10 | 0.534476E+09 | 0.717718E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.201062E+11 | 0.814362E+09 | 0.921276E+10 | 0.191303E+10 | 0.729973E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123373E+10 | 8524930.07 | 0.520926E+09 | 0.00 | 0.520926E+09 | 0.00 | 0.00 |
Maximum of Months | 0.246792E+10 | 0.187155E+09 | 0.125219E+10 | 0.534476E+09 | 0.728204E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.690730E+10 | 0.480283E+09 | 0.351377E+10 | 0.146320E+10 | 0.205057E+10 | 0.00 | 0.00 |
February | 0.563997E+10 | 0.319725E+09 | 0.268467E+10 | 0.865807E+09 | 0.181886E+10 | 0.00 | 0.00 |
March | 0.481671E+10 | 0.190414E+09 | 0.207271E+10 | 0.307609E+09 | 0.176510E+10 | 0.00 | 0.00 |
April | 0.375885E+10 | 34031737.43 | 0.148701E+10 | 8560706.83 | 0.147845E+10 | 0.00 | 0.00 |
May | 0.400015E+10 | 75684908.06 | 0.152127E+10 | 0.00 | 0.152127E+10 | 0.00 | 0.00 |
June | 0.378627E+10 | 75341424.11 | 0.146689E+10 | 0.00 | 0.146689E+10 | 0.00 | 0.00 |
July | 0.357327E+10 | 0.176804E+09 | 0.156149E+10 | 0.00 | 0.156149E+10 | 0.00 | 0.00 |
August | 0.348980E+10 | 0.102740E+09 | 0.151825E+10 | 128061.71 | 0.151812E+10 | 0.00 | 0.00 |
September | 0.374359E+10 | 0.113230E+09 | 0.162137E+10 | 44429887.09 | 0.157694E+10 | 0.00 | 0.00 |
October | 0.460958E+10 | 0.175095E+09 | 0.218194E+10 | 0.331084E+09 | 0.185085E+10 | 0.00 | 0.00 |
November | 0.557785E+10 | 0.274861E+09 | 0.278707E+10 | 0.861099E+09 | 0.192597E+10 | 0.00 | 0.00 |
December | 0.681786E+10 | 0.556805E+09 | 0.352610E+10 | 0.150505E+10 | 0.202105E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.567212E+11 | 0.257502E+10 | 0.259425E+11 | 0.538697E+10 | 0.205556E+11 | 0.00 | 0.00 |
Minimum of Months | 0.348980E+10 | 34031737.43 | 0.146689E+10 | 0.00 | 0.146689E+10 | 0.00 | 0.00 |
Maximum of Months | 0.690730E+10 | 0.556805E+09 | 0.352610E+10 | 0.150505E+10 | 0.205057E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.937221E+10 | 0.548368E+09 | 0.456459E+10 | 0.190078E+10 | 0.266381E+10 | 0.00 | 0.00 |
February | 0.767142E+10 | 0.358746E+09 | 0.348753E+10 | 0.112473E+10 | 0.236280E+10 | 0.00 | 0.00 |
March | 0.657981E+10 | 0.204389E+09 | 0.269257E+10 | 0.399602E+09 | 0.229296E+10 | 0.00 | 0.00 |
April | 0.512427E+10 | 41515935.21 | 0.193171E+10 | 11120845.37 | 0.192058E+10 | 0.00 | 0.00 |
May | 0.537694E+10 | 92478439.84 | 0.197621E+10 | 0.00 | 0.197621E+10 | 0.00 | 0.00 |
June | 0.505433E+10 | 98992429.74 | 0.190558E+10 | 0.00 | 0.190558E+10 | 0.00 | 0.00 |
July | 0.475513E+10 | 0.225761E+09 | 0.202847E+10 | 0.00 | 0.202847E+10 | 0.00 | 0.00 |
August | 0.467861E+10 | 0.123781E+09 | 0.197229E+10 | 166359.45 | 0.197212E+10 | 0.00 | 0.00 |
September | 0.507579E+10 | 0.124707E+09 | 0.210625E+10 | 57716951.86 | 0.204853E+10 | 0.00 | 0.00 |
October | 0.625449E+10 | 0.180827E+09 | 0.283446E+10 | 0.430097E+09 | 0.240436E+10 | 0.00 | 0.00 |
November | 0.758298E+10 | 0.304170E+09 | 0.362056E+10 | 0.111862E+10 | 0.250195E+10 | 0.00 | 0.00 |
December | 0.923785E+10 | 0.647378E+09 | 0.458060E+10 | 0.195515E+10 | 0.262545E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.767638E+11 | 0.295112E+10 | 0.337008E+11 | 0.699798E+10 | 0.267028E+11 | 0.00 | 0.00 |
Minimum of Months | 0.467861E+10 | 41515935.21 | 0.190558E+10 | 0.00 | 0.190558E+10 | 0.00 | 0.00 |
Maximum of Months | 0.937221E+10 | 0.647378E+09 | 0.458060E+10 | 0.195515E+10 | 0.266381E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126498E+10 | 34225139.16 | 0.587437E+09 | 0.222763E+09 | 0.364674E+09 | 0.00 | 0.00 |
February | 0.118523E+10 | 11126586.25 | 0.526268E+09 | 0.180432E+09 | 0.345836E+09 | 0.00 | 0.00 |
March | 0.135737E+10 | 2387218.42 | 0.564014E+09 | 0.186677E+09 | 0.377336E+09 | 0.00 | 0.00 |
April | 0.130446E+10 | 141993.46 | 0.511461E+09 | 0.156261E+09 | 0.355200E+09 | 0.00 | 0.00 |
May | 0.125662E+10 | 849749.49 | 0.465325E+09 | 0.106392E+09 | 0.358933E+09 | 0.00 | 0.00 |
June | 0.125117E+10 | 1224436.41 | 0.478599E+09 | 0.129405E+09 | 0.349195E+09 | 0.00 | 0.00 |
July | 0.106830E+10 | 2152163.94 | 0.440505E+09 | 77896981.51 | 0.362608E+09 | 0.00 | 0.00 |
August | 0.112311E+10 | 938989.43 | 0.467457E+09 | 0.107256E+09 | 0.360201E+09 | 0.00 | 0.00 |
September | 0.108308E+10 | 1047542.64 | 0.439843E+09 | 93452410.26 | 0.346391E+09 | 0.00 | 0.00 |
October | 0.108664E+10 | 1640630.18 | 0.469933E+09 | 0.105022E+09 | 0.364911E+09 | 0.00 | 0.00 |
November | 0.110023E+10 | 9962961.17 | 0.494554E+09 | 0.142064E+09 | 0.352490E+09 | 0.00 | 0.00 |
December | 0.119631E+10 | 45274586.80 | 0.563924E+09 | 0.209343E+09 | 0.354580E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142775E+11 | 0.110972E+09 | 0.600932E+10 | 0.171697E+10 | 0.429235E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106830E+10 | 141993.46 | 0.439843E+09 | 77896981.51 | 0.345836E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135737E+10 | 45274586.80 | 0.587437E+09 | 0.222763E+09 | 0.377336E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.986492E+09 | 33498962.65 | 0.434036E+09 | 0.120027E+09 | 0.314009E+09 | 0.00 | 0.00 |
February | 0.994246E+09 | 10604924.03 | 0.427675E+09 | 0.119640E+09 | 0.308035E+09 | 0.00 | 0.00 |
March | 0.126541E+10 | 2160875.03 | 0.520706E+09 | 0.165084E+09 | 0.355622E+09 | 0.00 | 0.00 |
April | 0.131552E+10 | 144352.27 | 0.516694E+09 | 0.158302E+09 | 0.358391E+09 | 0.00 | 0.00 |
May | 0.132789E+10 | 904286.33 | 0.500647E+09 | 0.121196E+09 | 0.379452E+09 | 0.00 | 0.00 |
June | 0.138300E+10 | 1335871.00 | 0.544625E+09 | 0.163998E+09 | 0.380627E+09 | 0.00 | 0.00 |
July | 0.114869E+10 | 2367448.11 | 0.480827E+09 | 93807082.69 | 0.387020E+09 | 0.00 | 0.00 |
August | 0.115772E+10 | 955055.65 | 0.484857E+09 | 0.113070E+09 | 0.371787E+09 | 0.00 | 0.00 |
September | 0.105916E+10 | 1045054.03 | 0.427799E+09 | 90512010.87 | 0.337287E+09 | 0.00 | 0.00 |
October | 0.986390E+09 | 1529684.32 | 0.417839E+09 | 81775732.61 | 0.336063E+09 | 0.00 | 0.00 |
November | 0.911200E+09 | 9280686.38 | 0.391448E+09 | 81603046.92 | 0.309845E+09 | 0.00 | 0.00 |
December | 0.915099E+09 | 43997566.63 | 0.406996E+09 | 0.103668E+09 | 0.303328E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134508E+11 | 0.107825E+09 | 0.555415E+10 | 0.141268E+10 | 0.414147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.911200E+09 | 144352.27 | 0.391448E+09 | 81603046.92 | 0.303328E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138300E+10 | 43997566.63 | 0.544625E+09 | 0.165084E+09 | 0.387020E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.408014E+09 | 18713581.84 | 0.197334E+09 | 82172949.63 | 0.115161E+09 | 0.00 | 0.00 |
February | 0.338425E+09 | 10071988.64 | 0.150771E+09 | 48623558.29 | 0.102148E+09 | 0.00 | 0.00 |
March | 0.297516E+09 | 4220030.02 | 0.116404E+09 | 17275273.32 | 99128629.48 | 0.00 | 0.00 |
April | 0.240356E+09 | 719349.26 | 83511001.41 | 480767.57 | 83030233.84 | 0.00 | 0.00 |
May | 0.251527E+09 | 1559448.10 | 85434963.14 | 0.00 | 85434963.14 | 0.00 | 0.00 |
June | 0.240164E+09 | 1673149.56 | 82381427.42 | 0.00 | 82381427.42 | 0.00 | 0.00 |
July | 0.215875E+09 | 4358083.88 | 87693961.87 | 0.00 | 87693961.87 | 0.00 | 0.00 |
August | 0.213131E+09 | 2608318.10 | 85265283.69 | 7191.92 | 85258091.77 | 0.00 | 0.00 |
September | 0.228276E+09 | 2672383.29 | 91056489.49 | 2495173.50 | 88561315.99 | 0.00 | 0.00 |
October | 0.273737E+09 | 4354555.61 | 0.122538E+09 | 18593600.04 | 0.103944E+09 | 0.00 | 0.00 |
November | 0.331217E+09 | 9054824.50 | 0.156522E+09 | 48359131.76 | 0.108163E+09 | 0.00 | 0.00 |
December | 0.401371E+09 | 23323159.61 | 0.198026E+09 | 84523294.81 | 0.113502E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.343961E+10 | 83328872.40 | 0.145694E+10 | 0.302531E+09 | 0.115441E+10 | 0.00 | 0.00 |
Minimum of Months | 0.213131E+09 | 719349.26 | 82381427.42 | 0.00 | 82381427.42 | 0.00 | 0.00 |
Maximum of Months | 0.408014E+09 | 23323159.61 | 0.198026E+09 | 84523294.81 | 0.115161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.206346E+09 | 6842232.71 | 74661715.11 | 0.00 | 74661715.11 | 0.00 | 0.00 |
February | 0.208058E+09 | 1305767.41 | 71936177.42 | 0.00 | 71936177.42 | 0.00 | 0.00 |
March | 0.261132E+09 | 222729.35 | 81791837.43 | 4078.45 | 81787758.98 | 0.00 | 0.00 |
April | 0.289766E+09 | 0.00 | 87725489.87 | 2113970.43 | 85611519.45 | 0.00 | 0.00 |
May | 0.350750E+09 | 70480.89 | 0.113725E+09 | 11844559.35 | 0.101880E+09 | 0.00 | 0.00 |
June | 0.385926E+09 | 134197.59 | 0.135236E+09 | 27678444.78 | 0.107558E+09 | 0.00 | 0.00 |
July | 0.317586E+09 | 191854.00 | 0.119985E+09 | 12729768.12 | 0.107255E+09 | 0.00 | 0.00 |
August | 0.281818E+09 | 30821.11 | 99215610.17 | 4658914.93 | 94556695.25 | 0.00 | 0.00 |
September | 0.246165E+09 | 51580.73 | 81450457.60 | 143369.21 | 81307088.38 | 0.00 | 0.00 |
October | 0.229839E+09 | 27511.65 | 80897687.62 | 0.00 | 80897687.62 | 0.00 | 0.00 |
November | 0.206841E+09 | 1294591.91 | 74077772.67 | 0.00 | 74077772.67 | 0.00 | 0.00 |
December | 0.194382E+09 | 9097354.35 | 72532813.71 | 0.00 | 72532813.71 | 0.00 | 0.00 |
Annual Sum or Average | 0.317861E+10 | 19269121.71 | 0.109324E+10 | 59173105.27 | 0.103406E+10 | 0.00 | 0.00 |
Minimum of Months | 0.194382E+09 | 0.00 | 71936177.42 | 0.00 | 71936177.42 | 0.00 | 0.00 |
Maximum of Months | 0.385926E+09 | 9097354.35 | 0.135236E+09 | 27678444.78 | 0.107558E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125231E+10 | 33501371.96 | 0.582569E+09 | 0.215971E+09 | 0.366597E+09 | 0.00 | 0.00 |
February | 0.119591E+10 | 10850778.04 | 0.532316E+09 | 0.186719E+09 | 0.345597E+09 | 0.00 | 0.00 |
March | 0.135511E+10 | 2255094.77 | 0.561151E+09 | 0.184276E+09 | 0.376875E+09 | 0.00 | 0.00 |
April | 0.131174E+10 | 62379.37 | 0.510177E+09 | 0.155386E+09 | 0.354791E+09 | 0.00 | 0.00 |
May | 0.126826E+10 | 729408.92 | 0.467745E+09 | 0.109389E+09 | 0.358356E+09 | 0.00 | 0.00 |
June | 0.125119E+10 | 1051506.88 | 0.474795E+09 | 0.122417E+09 | 0.352378E+09 | 0.00 | 0.00 |
July | 0.106728E+10 | 1869118.79 | 0.438194E+09 | 73755618.33 | 0.364438E+09 | 0.00 | 0.00 |
August | 0.112827E+10 | 792645.80 | 0.467772E+09 | 0.106178E+09 | 0.361593E+09 | 0.00 | 0.00 |
September | 0.109368E+10 | 940780.93 | 0.442199E+09 | 92674689.11 | 0.349524E+09 | 0.00 | 0.00 |
October | 0.109405E+10 | 1533021.06 | 0.471538E+09 | 0.104928E+09 | 0.366610E+09 | 0.00 | 0.00 |
November | 0.110060E+10 | 9684473.56 | 0.493922E+09 | 0.142979E+09 | 0.350943E+09 | 0.00 | 0.00 |
December | 0.118851E+10 | 44129720.40 | 0.562590E+09 | 0.206848E+09 | 0.355742E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143069E+11 | 0.107400E+09 | 0.600497E+10 | 0.170152E+10 | 0.430344E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106728E+10 | 62379.37 | 0.438194E+09 | 73755618.33 | 0.345597E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135511E+10 | 44129720.40 | 0.582569E+09 | 0.215971E+09 | 0.376875E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.972362E+09 | 31563355.10 | 0.429167E+09 | 0.113235E+09 | 0.315933E+09 | 0.00 | 0.00 |
February | 0.100441E+10 | 9947238.98 | 0.433722E+09 | 0.125927E+09 | 0.307795E+09 | 0.00 | 0.00 |
March | 0.126290E+10 | 2035204.37 | 0.517844E+09 | 0.162683E+09 | 0.355161E+09 | 0.00 | 0.00 |
April | 0.132283E+10 | 61699.56 | 0.515410E+09 | 0.157427E+09 | 0.357983E+09 | 0.00 | 0.00 |
May | 0.133967E+10 | 778178.79 | 0.503067E+09 | 0.124193E+09 | 0.378874E+09 | 0.00 | 0.00 |
June | 0.138331E+10 | 1171709.74 | 0.540821E+09 | 0.157010E+09 | 0.383810E+09 | 0.00 | 0.00 |
July | 0.114789E+10 | 2078568.23 | 0.478515E+09 | 89665719.51 | 0.388850E+09 | 0.00 | 0.00 |
August | 0.116302E+10 | 808534.50 | 0.485172E+09 | 0.111992E+09 | 0.373180E+09 | 0.00 | 0.00 |
September | 0.106972E+10 | 940759.16 | 0.430155E+09 | 89734289.71 | 0.340421E+09 | 0.00 | 0.00 |
October | 0.993608E+09 | 1427573.33 | 0.419444E+09 | 81681591.01 | 0.337763E+09 | 0.00 | 0.00 |
November | 0.911222E+09 | 8918823.32 | 0.390816E+09 | 82517905.01 | 0.308298E+09 | 0.00 | 0.00 |
December | 0.905929E+09 | 41656491.06 | 0.405663E+09 | 0.101173E+09 | 0.304490E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134769E+11 | 0.101388E+09 | 0.554980E+10 | 0.139724E+10 | 0.415256E+10 | 0.00 | 0.00 |
Minimum of Months | 0.905929E+09 | 61699.56 | 0.390816E+09 | 81681591.01 | 0.304490E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138331E+10 | 41656491.06 | 0.540821E+09 | 0.162683E+09 | 0.388850E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129779E+10 | 70937335.94 | 0.589309E+09 | 0.178046E+09 | 0.411263E+09 | 0.00 | 0.00 |
February | 0.113492E+10 | 39675672.00 | 0.482517E+09 | 0.105354E+09 | 0.377163E+09 | 0.00 | 0.00 |
March | 0.114768E+10 | 14299221.61 | 0.429403E+09 | 37439548.49 | 0.391964E+09 | 0.00 | 0.00 |
April | 0.108617E+10 | 1928154.15 | 0.370988E+09 | 5621258.43 | 0.365367E+09 | 0.00 | 0.00 |
May | 0.123404E+10 | 6119678.00 | 0.431479E+09 | 25659287.28 | 0.405820E+09 | 0.00 | 0.00 |
June | 0.127368E+10 | 7126962.23 | 0.471465E+09 | 59960792.57 | 0.411504E+09 | 0.00 | 0.00 |
July | 0.111393E+10 | 13307581.27 | 0.449935E+09 | 27576946.32 | 0.422358E+09 | 0.00 | 0.00 |
August | 0.103609E+10 | 5071863.78 | 0.399680E+09 | 10108354.86 | 0.389572E+09 | 0.00 | 0.00 |
September | 0.994080E+09 | 5862465.07 | 0.373743E+09 | 5716932.89 | 0.368026E+09 | 0.00 | 0.00 |
October | 0.105854E+10 | 9575190.60 | 0.440757E+09 | 40287160.58 | 0.400470E+09 | 0.00 | 0.00 |
November | 0.112957E+10 | 29086966.22 | 0.499617E+09 | 0.104781E+09 | 0.394836E+09 | 0.00 | 0.00 |
December | 0.126278E+10 | 86386021.91 | 0.586197E+09 | 0.183138E+09 | 0.403058E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137693E+11 | 0.289377E+09 | 0.552509E+10 | 0.783689E+09 | 0.474140E+10 | 0.00 | 0.00 |
Minimum of Months | 0.994080E+09 | 1928154.15 | 0.370988E+09 | 5621258.43 | 0.365367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129779E+10 | 86386021.91 | 0.589309E+09 | 0.183138E+09 | 0.422358E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125333E+10 | 28209751.97 | 0.587437E+09 | 0.222763E+09 | 0.364674E+09 | 0.00 | 0.00 |
February | 0.117721E+10 | 7117028.88 | 0.526268E+09 | 0.180432E+09 | 0.345836E+09 | 0.00 | 0.00 |
March | 0.135127E+10 | 1103581.60 | 0.564014E+09 | 0.186677E+09 | 0.377336E+09 | 0.00 | 0.00 |
April | 0.129828E+10 | 36810.73 | 0.511461E+09 | 0.156261E+09 | 0.355200E+09 | 0.00 | 0.00 |
May | 0.125202E+10 | 768554.41 | 0.465325E+09 | 0.106392E+09 | 0.358933E+09 | 0.00 | 0.00 |
June | 0.124767E+10 | 1152909.23 | 0.478599E+09 | 0.129405E+09 | 0.349195E+09 | 0.00 | 0.00 |
July | 0.106035E+10 | 1862580.65 | 0.440505E+09 | 77896981.51 | 0.362608E+09 | 0.00 | 0.00 |
August | 0.111616E+10 | 785976.81 | 0.467457E+09 | 0.107256E+09 | 0.360201E+09 | 0.00 | 0.00 |
September | 0.107375E+10 | 1162513.57 | 0.439843E+09 | 93452410.26 | 0.346391E+09 | 0.00 | 0.00 |
October | 0.107717E+10 | 1365163.49 | 0.469933E+09 | 0.105022E+09 | 0.364911E+09 | 0.00 | 0.00 |
November | 0.109075E+10 | 7953232.82 | 0.494554E+09 | 0.142064E+09 | 0.352490E+09 | 0.00 | 0.00 |
December | 0.118363E+10 | 38289656.23 | 0.563924E+09 | 0.209343E+09 | 0.354580E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.141816E+11 | 89807760.41 | 0.600932E+10 | 0.171697E+10 | 0.429235E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106035E+10 | 36810.73 | 0.439843E+09 | 77896981.51 | 0.345836E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135127E+10 | 38289656.23 | 0.587437E+09 | 0.222763E+09 | 0.377336E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.977534E+09 | 27619469.40 | 0.434036E+09 | 0.120027E+09 | 0.314009E+09 | 0.00 | 0.00 |
February | 0.987954E+09 | 6745905.28 | 0.427675E+09 | 0.119640E+09 | 0.308035E+09 | 0.00 | 0.00 |
March | 0.125948E+10 | 1060621.38 | 0.520706E+09 | 0.165084E+09 | 0.355622E+09 | 0.00 | 0.00 |
April | 0.130820E+10 | 36022.15 | 0.516694E+09 | 0.158302E+09 | 0.358391E+09 | 0.00 | 0.00 |
May | 0.132167E+10 | 813898.77 | 0.500647E+09 | 0.121196E+09 | 0.379452E+09 | 0.00 | 0.00 |
June | 0.137688E+10 | 1260447.93 | 0.544625E+09 | 0.163998E+09 | 0.380627E+09 | 0.00 | 0.00 |
July | 0.113933E+10 | 2020392.89 | 0.480827E+09 | 93807082.69 | 0.387020E+09 | 0.00 | 0.00 |
August | 0.114970E+10 | 798378.62 | 0.484857E+09 | 0.113070E+09 | 0.371787E+09 | 0.00 | 0.00 |
September | 0.104993E+10 | 1139844.15 | 0.427799E+09 | 90512010.87 | 0.337287E+09 | 0.00 | 0.00 |
October | 0.978113E+09 | 1281569.69 | 0.417839E+09 | 81775732.61 | 0.336063E+09 | 0.00 | 0.00 |
November | 0.903779E+09 | 7366934.97 | 0.391448E+09 | 81603046.92 | 0.309845E+09 | 0.00 | 0.00 |
December | 0.905379E+09 | 37138541.64 | 0.406996E+09 | 0.103668E+09 | 0.303328E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133579E+11 | 87282026.87 | 0.555415E+10 | 0.141268E+10 | 0.414147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.903779E+09 | 36022.15 | 0.391448E+09 | 81603046.92 | 0.303328E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137688E+10 | 37138541.64 | 0.544625E+09 | 0.165084E+09 | 0.387020E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.767436E+09 | 13632921.67 | 0.361833E+09 | 0.150673E+09 | 0.211160E+09 | 0.00 | 0.00 |
February | 0.644051E+09 | 2938722.11 | 0.276455E+09 | 89156620.63 | 0.187299E+09 | 0.00 | 0.00 |
March | 0.594308E+09 | 422878.03 | 0.213439E+09 | 31676106.08 | 0.181763E+09 | 0.00 | 0.00 |
April | 0.495755E+09 | 0.00 | 0.153127E+09 | 881540.01 | 0.152245E+09 | 0.00 | 0.00 |
May | 0.517344E+09 | 244930.55 | 0.156654E+09 | 0.00 | 0.156654E+09 | 0.00 | 0.00 |
June | 0.493159E+09 | 363271.62 | 0.151055E+09 | 0.00 | 0.151055E+09 | 0.00 | 0.00 |
July | 0.442785E+09 | 539966.18 | 0.160796E+09 | 0.00 | 0.160796E+09 | 0.00 | 0.00 |
August | 0.444984E+09 | 220416.32 | 0.156343E+09 | 13187.17 | 0.156330E+09 | 0.00 | 0.00 |
September | 0.465455E+09 | 427512.31 | 0.166962E+09 | 4575173.96 | 0.162387E+09 | 0.00 | 0.00 |
October | 0.546080E+09 | 535788.89 | 0.224687E+09 | 34093402.53 | 0.190593E+09 | 0.00 | 0.00 |
November | 0.636500E+09 | 3725639.00 | 0.287000E+09 | 88671765.62 | 0.198329E+09 | 0.00 | 0.00 |
December | 0.749763E+09 | 18729218.95 | 0.363102E+09 | 0.154983E+09 | 0.208119E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.679762E+10 | 41781265.63 | 0.267145E+10 | 0.554724E+09 | 0.211673E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442785E+09 | 0.00 | 0.151055E+09 | 0.00 | 0.151055E+09 | 0.00 | 0.00 |
Maximum of Months | 0.767436E+09 | 18729218.95 | 0.363102E+09 | 0.154983E+09 | 0.211160E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145940E+10 | 0.231219E+09 | 0.653179E+09 | 0.00 | 0.653179E+09 | 0.00 | 0.00 |
February | 0.147452E+10 | 0.143619E+09 | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.00 | 0.00 |
March | 0.178076E+10 | 82674421.23 | 0.715557E+09 | 35680.36 | 0.715521E+09 | 0.00 | 0.00 |
April | 0.198372E+10 | 19812495.03 | 0.767467E+09 | 18494089.18 | 0.748973E+09 | 0.00 | 0.00 |
May | 0.251703E+10 | 44369146.40 | 0.994921E+09 | 0.103622E+09 | 0.891298E+09 | 0.00 | 0.00 |
June | 0.284625E+10 | 44855093.64 | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.00 | 0.00 |
July | 0.232370E+10 | 98558935.32 | 0.104969E+10 | 0.111366E+09 | 0.938320E+09 | 0.00 | 0.00 |
August | 0.196119E+10 | 62660956.96 | 0.867989E+09 | 40758558.92 | 0.827230E+09 | 0.00 | 0.00 |
September | 0.168383E+10 | 65615680.94 | 0.712570E+09 | 1254266.85 | 0.711316E+09 | 0.00 | 0.00 |
October | 0.155637E+10 | 99845998.36 | 0.707734E+09 | 0.00 | 0.707734E+09 | 0.00 | 0.00 |
November | 0.143362E+10 | 0.135863E+09 | 0.648070E+09 | 0.00 | 0.648070E+09 | 0.00 | 0.00 |
December | 0.139653E+10 | 0.274642E+09 | 0.634554E+09 | 0.00 | 0.634554E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224169E+11 | 0.130374E+10 | 0.956418E+10 | 0.517676E+09 | 0.904650E+10 | 0.00 | 0.00 |
Minimum of Months | 0.139653E+10 | 19812495.03 | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.00 | 0.00 |
Maximum of Months | 0.284625E+10 | 0.274642E+09 | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142631E+10 | 0.249085E+09 | 0.653179E+09 | 0.00 | 0.653179E+09 | 0.00 | 0.00 |
February | 0.144474E+10 | 0.157136E+09 | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.00 | 0.00 |
March | 0.174282E+10 | 94736109.78 | 0.715557E+09 | 35680.36 | 0.715521E+09 | 0.00 | 0.00 |
April | 0.194107E+10 | 23906131.91 | 0.767467E+09 | 18494089.18 | 0.748973E+09 | 0.00 | 0.00 |
May | 0.247503E+10 | 51501603.10 | 0.994921E+09 | 0.103622E+09 | 0.891298E+09 | 0.00 | 0.00 |
June | 0.280807E+10 | 51359055.42 | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.00 | 0.00 |
July | 0.228569E+10 | 0.112476E+09 | 0.104969E+10 | 0.111366E+09 | 0.938320E+09 | 0.00 | 0.00 |
August | 0.191591E+10 | 75727023.38 | 0.867989E+09 | 40758558.92 | 0.827230E+09 | 0.00 | 0.00 |
September | 0.164489E+10 | 78492957.92 | 0.712570E+09 | 1254266.85 | 0.711316E+09 | 0.00 | 0.00 |
October | 0.151744E+10 | 0.118006E+09 | 0.707734E+09 | 0.00 | 0.707734E+09 | 0.00 | 0.00 |
November | 0.139988E+10 | 0.152806E+09 | 0.648070E+09 | 0.00 | 0.648070E+09 | 0.00 | 0.00 |
December | 0.136391E+10 | 0.294469E+09 | 0.634554E+09 | 0.00 | 0.634554E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.219658E+11 | 0.145970E+10 | 0.956418E+10 | 0.517676E+09 | 0.904650E+10 | 0.00 | 0.00 |
Minimum of Months | 0.136391E+10 | 23906131.91 | 0.629334E+09 | 0.00 | 0.629334E+09 | 0.00 | 0.00 |
Maximum of Months | 0.280807E+10 | 0.294469E+09 | 0.118312E+10 | 0.242145E+09 | 0.940972E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.222285E+10 | 0.203388E+09 | 0.101169E+10 | 0.329190E+09 | 0.682499E+09 | 0.00 | 0.00 |
February | 0.218129E+10 | 0.132789E+09 | 0.965989E+09 | 0.312628E+09 | 0.653361E+09 | 0.00 | 0.00 |
March | 0.246448E+10 | 92014457.02 | 0.107894E+10 | 0.346936E+09 | 0.731999E+09 | 0.00 | 0.00 |
April | 0.244074E+10 | 29546080.73 | 0.102553E+10 | 0.312792E+09 | 0.712738E+09 | 0.00 | 0.00 |
May | 0.239360E+10 | 52243002.66 | 0.970761E+09 | 0.233566E+09 | 0.737194E+09 | 0.00 | 0.00 |
June | 0.245659E+10 | 52533743.71 | 0.101556E+10 | 0.279410E+09 | 0.736153E+09 | 0.00 | 0.00 |
July | 0.212092E+10 | 92393746.38 | 0.916663E+09 | 0.163411E+09 | 0.753252E+09 | 0.00 | 0.00 |
August | 0.209559E+10 | 71276034.96 | 0.952893E+09 | 0.218156E+09 | 0.734737E+09 | 0.00 | 0.00 |
September | 0.204662E+10 | 71331460.65 | 0.872307E+09 | 0.182396E+09 | 0.689911E+09 | 0.00 | 0.00 |
October | 0.195000E+10 | 0.105718E+09 | 0.890937E+09 | 0.186598E+09 | 0.704339E+09 | 0.00 | 0.00 |
November | 0.197457E+10 | 0.123974E+09 | 0.884696E+09 | 0.225485E+09 | 0.659211E+09 | 0.00 | 0.00 |
December | 0.212263E+10 | 0.235366E+09 | 0.968209E+09 | 0.308007E+09 | 0.660202E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.264699E+11 | 0.126257E+10 | 0.115542E+11 | 0.309857E+10 | 0.845560E+10 | 0.00 | 0.00 |
Minimum of Months | 0.195000E+10 | 29546080.73 | 0.872307E+09 | 0.163411E+09 | 0.653361E+09 | 0.00 | 0.00 |
Maximum of Months | 0.246448E+10 | 0.235366E+09 | 0.107894E+10 | 0.346936E+09 | 0.753252E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.238738E+10 | 0.149017E+09 | 0.114498E+10 | 0.383546E+09 | 0.761429E+09 | 0.00 | 0.00 |
February | 0.205354E+10 | 88198780.67 | 0.919469E+09 | 0.226953E+09 | 0.692516E+09 | 0.00 | 0.00 |
March | 0.196971E+10 | 36379874.40 | 0.788615E+09 | 80645442.75 | 0.707970E+09 | 0.00 | 0.00 |
April | 0.177160E+10 | 5549720.96 | 0.652881E+09 | 8583816.85 | 0.644297E+09 | 0.00 | 0.00 |
May | 0.201680E+10 | 17009277.64 | 0.739833E+09 | 35521904.13 | 0.704311E+09 | 0.00 | 0.00 |
June | 0.206005E+10 | 19806113.48 | 0.790094E+09 | 83007820.98 | 0.707087E+09 | 0.00 | 0.00 |
July | 0.180140E+10 | 41660604.74 | 0.769150E+09 | 38176650.53 | 0.730974E+09 | 0.00 | 0.00 |
August | 0.169475E+10 | 15163271.76 | 0.695528E+09 | 14005682.30 | 0.681523E+09 | 0.00 | 0.00 |
September | 0.164339E+10 | 19891909.01 | 0.669281E+09 | 12076313.58 | 0.657205E+09 | 0.00 | 0.00 |
October | 0.182799E+10 | 29836271.60 | 0.814564E+09 | 86786568.05 | 0.727778E+09 | 0.00 | 0.00 |
November | 0.202949E+10 | 68519504.58 | 0.952734E+09 | 0.225719E+09 | 0.727016E+09 | 0.00 | 0.00 |
December | 0.234287E+10 | 0.178119E+09 | 0.114182E+10 | 0.394517E+09 | 0.747304E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.235990E+11 | 0.669152E+09 | 0.100789E+11 | 0.158954E+10 | 0.848941E+10 | 0.00 | 0.00 |
Minimum of Months | 0.164339E+10 | 5549720.96 | 0.652881E+09 | 8583816.85 | 0.644297E+09 | 0.00 | 0.00 |
Maximum of Months | 0.238738E+10 | 0.178119E+09 | 0.114498E+10 | 0.394517E+09 | 0.761429E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770522E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162433320.9 | 81.21 | 0.00 | 0.00 |
February | 0.696261E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146645666.6 | 81.21 | 0.00 | 0.00 |
March | 0.770378E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162309142.7 | 81.21 | 0.00 | 0.00 |
April | 0.746561E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157013851.4 | 81.21 | 0.00 | 0.00 |
May | 0.770506E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162257203.2 | 81.21 | 0.00 | 0.00 |
June | 0.745753E+10 | -0.730055E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156985889.7 | 81.21 | 0.00 | 0.00 |
July | 0.771318E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162329317.0 | 81.21 | 0.00 | 0.00 |
August | 0.770519E+10 | -0.754283E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162361391.4 | 81.21 | 0.00 | 0.00 |
September | 0.746703E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157086573.7 | 81.21 | 0.00 | 0.00 |
October | 0.770385E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162407811.2 | 81.21 | 0.00 | 0.00 |
November | 0.744962E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157178024.9 | 81.21 | 0.00 | 0.00 |
December | 0.771333E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162470481.4 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907520E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191148E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696261E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162470481.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771333E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146645666.6 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.889775E+11 | -0.872273E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175026E+10 | 81.25 | 0.00 | 0.00 |
February | 0.800740E+11 | -0.784961E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157785E+10 | 81.24 | 0.00 | 0.00 |
March | 0.878845E+11 | -0.861351E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174935E+10 | 81.24 | 0.00 | 0.00 |
April | 0.840314E+11 | -0.823389E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169254E+10 | 81.24 | 0.00 | 0.00 |
May | 0.857969E+11 | -0.840509E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174595E+10 | 81.24 | 0.00 | 0.00 |
June | 0.823115E+11 | -0.806262E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168521E+10 | 81.23 | 0.00 | 0.00 |
July | 0.848167E+11 | -0.830720E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174477E+10 | 81.25 | 0.00 | 0.00 |
August | 0.851475E+11 | -0.834008E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174678E+10 | 81.23 | 0.00 | 0.00 |
September | 0.831723E+11 | -0.814818E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169051E+10 | 81.24 | 0.00 | 0.00 |
October | 0.870053E+11 | -0.852538E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175146E+10 | 81.24 | 0.00 | 0.00 |
November | 0.851916E+11 | -0.834993E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169227E+10 | 81.24 | 0.00 | 0.00 |
December | 0.887529E+11 | -0.870047E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174820E+10 | 81.24 | 0.00 | 0.00 |
Annual Sum or Average | 0.102316E+13 | -0.100259E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205751E+11 | 81.24 | 0.00 | 0.00 |
Minimum of Months | 0.800740E+11 | -0.872273E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.175146E+10 | 81.23 | 0.00 | 0.00 |
Maximum of Months | 0.889775E+11 | -0.784961E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157785E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.442473E+11 | -0.427519E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149546E+10 | 58.98 | 0.00 | 0.00 |
February | 0.397180E+11 | -0.383712E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134682E+10 | 58.97 | 0.00 | 0.00 |
March | 0.433399E+11 | -0.418453E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149462E+10 | 58.97 | 0.00 | 0.00 |
April | 0.410398E+11 | -0.395940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144582E+10 | 58.98 | 0.00 | 0.00 |
May | 0.415174E+11 | -0.400276E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148980E+10 | 58.97 | 0.00 | 0.00 |
June | 0.395704E+11 | -0.381345E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143596E+10 | 58.97 | 0.00 | 0.00 |
July | 0.406484E+11 | -0.391606E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148781E+10 | 58.97 | 0.00 | 0.00 |
August | 0.409758E+11 | -0.394845E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149134E+10 | 58.97 | 0.00 | 0.00 |
September | 0.402995E+11 | -0.388565E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144302E+10 | 58.97 | 0.00 | 0.00 |
October | 0.425408E+11 | -0.410434E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149741E+10 | 58.97 | 0.00 | 0.00 |
November | 0.420252E+11 | -0.405796E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144554E+10 | 58.97 | 0.00 | 0.00 |
December | 0.440497E+11 | -0.425565E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149314E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.499972E+12 | -0.482406E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.175667E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.395704E+11 | -0.427519E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.149741E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.442473E+11 | -0.381345E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.134682E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.87 | 0.86 | 01-JAN-07:49 | 1872.66 | 25.87 | 141.17 | 328.00 | 663.46 | 24.87 | 317.17 | 311.17 |
February | 321.17 | 0.87 | 0.86 | 01-FEB-06:49 | 1457.76 | 21.20 | 22.67 | 297.83 | 553.99 | 22.29 | 263.17 | 272.50 |
March | 361.17 | 0.87 | 0.86 | 01-MAR-07:00 | 1101.45 | 20.27 | 0.00 | 334.67 | 442.74 | 21.98 | 283.17 | 297.33 |
April | 358.33 | 0.87 | 0.86 | 01-APR-07:10 | 902.63 | 19.97 | 0.00 | 332.67 | 371.35 | 21.67 | 257.17 | 281.33 |
May | 376.33 | 0.88 | 0.86 | 01-MAY-07:10 | 770.94 | 18.82 | 0.00 | 341.50 | 307.11 | 20.52 | 146.50 | 260.17 |
June | 370.50 | 0.88 | 0.86 | 01-JUN-08:09 | 744.31 | 19.09 | 0.00 | 334.83 | 309.21 | 20.82 | 184.17 | 264.17 |
July | 383.17 | 0.88 | 0.86 | 01-JUL-07:40 | 729.24 | 18.33 | 0.00 | 336.83 | 281.09 | 20.02 | 61.50 | 251.67 |
August | 369.33 | 0.87 | 0.86 | 01-AUG-07:19 | 865.76 | 19.27 | 0.00 | 340.67 | 340.79 | 20.96 | 179.00 | 276.50 |
September | 357.83 | 0.88 | 0.86 | 01-SEP-07:10 | 993.31 | 18.93 | 0.00 | 321.33 | 376.02 | 20.60 | 159.50 | 270.00 |
October | 356.83 | 0.87 | 0.86 | 01-OCT-07:10 | 1298.32 | 19.84 | 5.67 | 333.67 | 478.14 | 21.40 | 204.33 | 280.67 |
November | 337.67 | 0.87 | 0.86 | 01-NOV-07:19 | 1677.08 | 24.03 | 107.00 | 320.50 | 590.26 | 22.69 | 254.67 | 284.33 |
December | 349.33 | 0.87 | 0.86 | 01-DEC-06:49 | 1964.02 | 26.20 | 149.83 | 326.17 | 670.85 | 24.70 | 305.83 | 303.50 |
Annual Sum or Average | 4292.33 | 0.87 | 1184.04 | 20.91 | 426.33 | 3948.67 | 444.07 | 21.84 | 2616.17 | 3353.33 | ||
Minimum of Months | 321.17 | 0.87 | 0.86 | 729.24 | 18.33 | 0.00 | 297.83 | 281.09 | 20.02 | 61.50 | 251.67 | |
Maximum of Months | 383.17 | 0.88 | 0.86 | 1964.02 | 26.20 | 149.83 | 341.50 | 670.85 | 24.87 | 317.17 | 311.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.26 | 0.22 | 01-JAN-07:10 | 2135.73 | 26.04 | 171.17 | 333.67 | 925.59 | 25.05 | 329.83 | 322.17 |
February | 321.17 | 0.27 | 0.22 | 01-FEB-06:40 | 1687.75 | 21.71 | 108.67 | 302.33 | 783.19 | 22.66 | 273.50 | 286.83 |
March | 361.17 | 0.26 | 0.22 | 01-MAR-07:30 | 1277.51 | 20.96 | 117.50 | 345.67 | 618.21 | 22.45 | 302.67 | 321.17 |
April | 358.33 | 0.25 | 0.22 | 01-APR-06:40 | 1044.75 | 20.76 | 42.83 | 346.33 | 512.95 | 22.24 | 279.33 | 314.83 |
May | 376.33 | 0.27 | 0.22 | 01-MAY-06:30 | 890.88 | 19.74 | 0.00 | 356.00 | 426.59 | 21.21 | 191.33 | 318.33 |
June | 370.50 | 0.27 | 0.22 | 01-JUN-07:10 | 864.39 | 19.98 | 0.00 | 349.83 | 428.84 | 21.48 | 227.50 | 311.83 |
July | 383.17 | 0.28 | 0.22 | 01-JUL-06:00 | 840.45 | 19.31 | 0.00 | 353.50 | 391.87 | 20.76 | 154.67 | 312.17 |
August | 369.33 | 0.26 | 0.22 | 01-AUG-06:40 | 996.17 | 20.15 | 9.50 | 354.50 | 470.69 | 21.61 | 224.00 | 318.00 |
September | 357.83 | 0.28 | 0.22 | 01-SEP-06:40 | 1134.35 | 19.80 | 51.83 | 331.50 | 516.45 | 21.25 | 230.33 | 302.33 |
October | 356.83 | 0.26 | 0.22 | 01-OCT-06:30 | 1476.51 | 20.59 | 76.50 | 342.50 | 655.40 | 21.95 | 257.50 | 313.00 |
November | 337.67 | 0.25 | 0.22 | 01-NOV-06:49 | 1903.10 | 24.36 | 146.17 | 329.67 | 815.27 | 23.09 | 280.67 | 307.33 |
December | 349.33 | 0.26 | 0.22 | 01-DEC-06:30 | 2226.78 | 26.36 | 165.00 | 331.83 | 932.82 | 24.90 | 322.50 | 318.50 |
Annual Sum or Average | 4292.33 | 0.26 | 1357.18 | 21.58 | 889.17 | 4077.33 | 616.55 | 22.35 | 3073.83 | 3746.50 | ||
Minimum of Months | 321.17 | 0.25 | 0.22 | 840.45 | 19.31 | 0.00 | 302.33 | 391.87 | 20.76 | 154.67 | 286.83 | |
Maximum of Months | 383.17 | 0.28 | 0.22 | 2226.78 | 26.36 | 171.17 | 356.00 | 932.82 | 25.05 | 329.83 | 322.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.65 | 0.60 | 01-JAN-08:30 | 569.83 | 16.45 | 0.00 | 313.33 | 260.52 | 19.65 | 0.00 | 259.33 |
February | 321.17 | 0.64 | 0.60 | 01-FEB-07:49 | 626.01 | 16.93 | 0.00 | 289.67 | 286.74 | 20.10 | 0.00 | 254.83 |
March | 361.17 | 0.63 | 0.60 | 01-MAR-07:00 | 719.28 | 17.77 | 0.00 | 337.33 | 330.14 | 20.93 | 101.17 | 302.67 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:49 | 908.59 | 18.54 | 0.00 | 347.17 | 398.03 | 21.71 | 206.67 | 313.17 |
May | 376.33 | 0.62 | 0.60 | 01-MAY-06:10 | 1080.31 | 19.15 | 28.00 | 361.67 | 440.28 | 21.76 | 201.00 | 330.17 |
June | 370.50 | 0.61 | 0.60 | 01-JUN-07:10 | 1313.38 | 22.50 | 103.00 | 359.17 | 517.66 | 23.62 | 304.83 | 338.33 |
July | 383.17 | 0.62 | 0.60 | 01-JUL-06:30 | 1137.29 | 20.35 | 72.00 | 362.33 | 442.20 | 23.25 | 218.33 | 334.83 |
August | 369.33 | 0.62 | 0.60 | 01-AUG-06:10 | 1008.59 | 18.26 | 0.00 | 358.50 | 418.31 | 21.41 | 183.67 | 323.83 |
September | 357.83 | 0.64 | 0.60 | 01-SEP-06:40 | 809.33 | 17.19 | 0.00 | 327.67 | 335.14 | 20.26 | 92.83 | 288.17 |
October | 356.83 | 0.64 | 0.60 | 01-OCT-07:10 | 706.94 | 17.02 | 0.00 | 330.50 | 296.22 | 20.11 | 21.67 | 276.67 |
November | 337.67 | 0.64 | 0.60 | 01-NOV-07:30 | 623.69 | 16.74 | 0.00 | 309.67 | 269.37 | 19.87 | 0.00 | 252.17 |
December | 349.33 | 0.65 | 0.60 | 01-DEC-07:30 | 559.63 | 16.24 | 0.00 | 310.33 | 252.36 | 19.43 | 0.00 | 250.50 |
Annual Sum or Average | 4292.33 | 0.63 | 847.01 | 18.15 | 203.00 | 4007.33 | 356.79 | 21.05 | 1330.17 | 3524.67 | ||
Minimum of Months | 321.17 | 0.61 | 0.60 | 559.63 | 16.24 | 0.00 | 289.67 | 252.36 | 19.43 | 0.00 | 250.50 | |
Maximum of Months | 383.17 | 0.65 | 0.60 | 1313.38 | 22.50 | 103.00 | 362.33 | 517.66 | 23.62 | 304.83 | 338.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.65 | 0.60 | 01-JAN-08:30 | 569.83 | 16.45 | 0.00 | 313.33 | 260.52 | 19.65 | 0.00 | 259.33 |
February | 321.17 | 0.64 | 0.60 | 01-FEB-07:49 | 626.01 | 16.93 | 0.00 | 289.67 | 286.74 | 20.10 | 0.00 | 254.83 |
March | 361.17 | 0.63 | 0.60 | 01-MAR-07:00 | 719.28 | 17.77 | 0.00 | 337.33 | 330.14 | 20.93 | 101.17 | 302.67 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:49 | 908.59 | 18.54 | 0.00 | 347.17 | 398.03 | 21.71 | 206.67 | 313.17 |
May | 376.33 | 0.62 | 0.60 | 01-MAY-06:10 | 1080.31 | 19.15 | 28.00 | 361.67 | 440.28 | 21.76 | 201.00 | 330.17 |
June | 370.50 | 0.61 | 0.60 | 01-JUN-07:10 | 1313.38 | 22.50 | 103.00 | 359.17 | 517.66 | 23.62 | 304.83 | 338.33 |
July | 383.17 | 0.62 | 0.60 | 01-JUL-06:30 | 1137.29 | 20.35 | 72.00 | 362.33 | 442.20 | 23.25 | 218.33 | 334.83 |
August | 369.33 | 0.62 | 0.60 | 01-AUG-06:10 | 1008.59 | 18.26 | 0.00 | 358.50 | 418.31 | 21.41 | 183.67 | 323.83 |
September | 357.83 | 0.64 | 0.60 | 01-SEP-06:40 | 809.33 | 17.19 | 0.00 | 327.67 | 335.14 | 20.26 | 92.83 | 288.17 |
October | 356.83 | 0.64 | 0.60 | 01-OCT-07:10 | 706.94 | 17.02 | 0.00 | 330.50 | 296.22 | 20.11 | 21.67 | 276.67 |
November | 337.67 | 0.64 | 0.60 | 01-NOV-07:30 | 623.69 | 16.74 | 0.00 | 309.67 | 269.37 | 19.87 | 0.00 | 252.17 |
December | 349.33 | 0.65 | 0.60 | 01-DEC-07:30 | 559.63 | 16.24 | 0.00 | 310.33 | 252.36 | 19.43 | 0.00 | 250.50 |
Annual Sum or Average | 4292.33 | 0.63 | 847.01 | 18.15 | 203.00 | 4007.33 | 356.79 | 21.05 | 1330.17 | 3524.67 | ||
Minimum of Months | 321.17 | 0.61 | 0.60 | 559.63 | 16.24 | 0.00 | 289.67 | 252.36 | 19.43 | 0.00 | 250.50 | |
Maximum of Months | 383.17 | 0.65 | 0.60 | 1313.38 | 22.50 | 103.00 | 362.33 | 517.66 | 23.62 | 304.83 | 338.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121324E+10 | 4622.85 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.920952E+09 | 4136.14 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100787E+10 | 4912.74 | 04-MAR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.870682E+09 | 4842.61 | 10-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101612E+10 | 4622.85 | 26-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.849725E+09 | 4222.06 | 05-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101377E+10 | 4697.70 | 01-JUL-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122515E+10 | 5364.99 | 21-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104372E+10 | 5304.25 | 16-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127153E+10 | 5424.59 | 23-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116694E+10 | 4981.44 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125688E+10 | 4622.85 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.849725E+09 | 4136.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127153E+10 | 5424.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 167521.19 | 137.84 | 20-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 167521.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 167521.19 | 137.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5797.56 | 0.51 | 01-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4674.87 | 0.50 | 12-FEB-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3790.60 | 0.51 | 25-MAR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5134.28 | 0.51 | 19-APR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4140.66 | 0.51 | 19-MAY-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4113.25 | 0.51 | 21-JUN-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6574.07 | 0.51 | 01-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2846.76 | 0.50 | 28-AUG-22:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4859.26 | 0.51 | 12-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5175.66 | 0.51 | 29-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4722.57 | 0.51 | 05-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8589.47 | 0.51 | 06-DEC-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60419.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2846.76 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8589.47 | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 684827.60 | 1563.92 | 01-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 322830.13 | 1593.61 | 20-FEB-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1419689.52 | 1409.77 | 04-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 911127.43 | 1591.63 | 21-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1295134.10 | 1592.55 | 26-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1205715.61 | 1481.60 | 22-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3805970.39 | 1593.92 | 12-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2181040.35 | 1594.73 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2042083.40 | 1593.84 | 19-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2758866.64 | 1594.26 | 27-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 992294.61 | 1594.17 | 18-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 619661.29 | 1507.85 | 22-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18239241.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 322830.13 | 1409.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3805970.39 | 1594.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1719954.06 | 1595.53 | 12-JAN-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1108782.16 | 1596.24 | 20-FEB-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3008911.69 | 1592.29 | 08-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1033021.83 | 1592.59 | 21-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1165408.49 | 1593.31 | 18-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 658539.88 | 1411.16 | 22-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2856427.71 | 1594.74 | 07-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1890207.74 | 1595.65 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2725955.71 | 1594.90 | 19-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4239789.39 | 1595.07 | 12-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3079664.24 | 1593.59 | 01-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1112755.73 | 1546.30 | 17-DEC-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24599418.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 658539.88 | 1411.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4239789.39 | 1596.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 42049809.56 | 16177.60 | 11-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34181255.97 | 16105.10 | 24-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31397842.54 | 20175.37 | 13-MAR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18565618.29 | 15822.32 | 21-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18134125.11 | 20448.15 | 17-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9879959.80 | 14517.98 | 30-JUN-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22946765.10 | 19019.58 | 12-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28363221.31 | 20463.49 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26574703.10 | 20457.16 | 19-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48595221.82 | 20467.65 | 27-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36224923.40 | 20426.59 | 01-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45157050.25 | 16194.09 | 27-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9879959.80 | 14517.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48595221.82 | 20467.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 102620.13 | 1197.23 | 10-JAN-07:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35119.21 | 409.72 | 15-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 186057.73 | 1581.04 | 17-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 374733.37 | 1377.24 | 07-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 236779.36 | 1579.95 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 276175.47 | 1029.05 | 19-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 169960.79 | 1027.78 | 24-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13694.15 | 85.13 | 26-NOV-09:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 245587.66 | 1257.35 | 21-DEC-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1640727.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 374733.37 | 1581.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 120287.77 | 1041.87 | 10-JAN-07:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57796.07 | 674.29 | 15-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 174099.31 | 1581.71 | 17-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 342593.03 | 1303.19 | 07-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 225292.59 | 1580.94 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 293829.87 | 1305.71 | 19-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299983.97 | 1382.44 | 24-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24214.19 | 257.22 | 27-NOV-09:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 173291.79 | 1090.68 | 21-DEC-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1711388.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 342593.03 | 1581.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 232523.12 | 400.69 | 12-JAN-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216329.21 | 400.56 | 15-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 789827.88 | 399.52 | 16-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 631969.20 | 400.63 | 21-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 551678.28 | 400.76 | 18-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 426336.18 | 400.12 | 25-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1128104.37 | 400.72 | 17-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 950363.86 | 400.75 | 31-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 884427.35 | 400.25 | 15-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1025278.17 | 400.81 | 24-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 328243.09 | 400.63 | 01-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 169706.88 | 362.87 | 27-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7334787.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 169706.88 | 362.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1128104.37 | 400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 487669.80 | 401.07 | 23-JAN-09:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 330293.77 | 401.13 | 14-FEB-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 980176.46 | 400.30 | 16-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 606068.18 | 400.81 | 21-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 480132.97 | 400.91 | 18-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 307539.89 | 377.56 | 20-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 972846.76 | 400.72 | 17-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 868362.51 | 400.91 | 31-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 943992.10 | 400.48 | 15-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1208226.85 | 400.79 | 09-OCT-06:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 943989.85 | 401.11 | 29-NOV-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 524792.58 | 401.20 | 15-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8654091.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 307539.89 | 377.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1208226.85 | 401.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 105477.38 | 1230.57 | 23-JAN-22:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44605.71 | 306.01 | 15-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40667.24 | 474.45 | 16-MAR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 165967.45 | 850.04 | 21-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 904491.48 | 2497.74 | 17-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 277574.54 | 1439.15 | 01-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1593313.70 | 2497.74 | 07-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1116423.72 | 2495.99 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 998485.91 | 2493.40 | 19-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 996734.84 | 2132.09 | 24-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 187739.34 | 1131.14 | 22-DEC-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6431481.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1593313.70 | 2497.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.932200E+12 | 0.510207E+12 | 463652.18 | 08-JAN-07:40 | 168993.81 | 1.00 |
February | 0.00 | 0.00 | 0.856379E+12 | 0.485734E+12 | 470611.75 | 14-FEB-19:20 | 244914.14 | 1.00 |
March | 0.00 | 0.00 | 0.989988E+12 | 0.550251E+12 | 537444.54 | 14-MAR-21:20 | 210847.09 | 1.00 |
April | 0.00 | 0.00 | 0.108269E+13 | 0.547138E+12 | 538134.53 | 10-APR-18:20 | 246438.16 | 1.00 |
May | 0.00 | 0.00 | 0.122583E+13 | 0.568067E+12 | 600063.56 | 31-MAY-20:20 | 231793.16 | 1.00 |
June | 0.00 | 0.00 | 0.120141E+13 | 0.557106E+12 | 589241.25 | 14-JUN-20:10 | 286612.10 | 1.00 |
July | 0.00 | 0.00 | 0.104107E+13 | 0.532114E+12 | 554634.56 | 06-JUL-21:20 | 212831.35 | 1.00 |
August | 0.00 | 0.00 | 0.116372E+13 | 0.533222E+12 | 589794.65 | 14-AUG-21:00 | 262594.87 | 1.00 |
September | 0.00 | 0.00 | 0.110296E+13 | 0.517075E+12 | 570013.43 | 30-SEP-11:00 | 229672.82 | 1.00 |
October | 0.00 | 0.00 | 0.109382E+13 | 0.517911E+12 | 534910.40 | 09-OCT-22:00 | 191576.00 | 1.00 |
November | 0.00 | 0.00 | 0.100930E+13 | 0.501210E+12 | 556029.38 | 30-NOV-23:00 | 201093.42 | 1.00 |
December | 0.00 | 0.00 | 0.994618E+12 | 0.501270E+12 | 557028.78 | 05-DEC-23:07 | 197459.43 | 1.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126940E+14 | 0.632131E+13 | 1.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.856379E+12 | 0.485734E+12 | 463652.18 | 168993.81 | 1.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122583E+13 | 0.568067E+12 | 600063.56 | 286612.10 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.132338E+12 | 0.772683E+11 | 81153.21 | 08-JAN-08:30 | 28466.63 | 1.00 |
February | 0.00 | 0.00 | 0.120192E+12 | 0.722705E+11 | 75985.20 | 10-FEB-07:20 | 28296.85 | 1.00 |
March | 0.00 | 0.00 | 0.138626E+12 | 0.812970E+11 | 63720.48 | 27-MAR-13:00 | 36003.87 | 1.00 |
April | 0.00 | 0.00 | 0.154072E+12 | 0.804173E+11 | 74311.54 | 10-APR-18:02 | 33907.01 | 1.00 |
May | 0.00 | 0.00 | 0.175770E+12 | 0.831930E+11 | 90888.03 | 10-MAY-21:30 | 29946.18 | 1.00 |
June | 0.00 | 0.00 | 0.170193E+12 | 0.803660E+11 | 85687.76 | 25-JUN-19:04 | 28800.67 | 1.00 |
July | 0.00 | 0.00 | 0.149804E+12 | 0.796971E+11 | 79535.40 | 19-JUL-21:51 | 29340.59 | 1.00 |
August | 0.00 | 0.00 | 0.170212E+12 | 0.803970E+11 | 85563.31 | 19-AUG-18:10 | 28756.93 | 1.00 |
September | 0.00 | 0.00 | 0.160323E+12 | 0.777978E+11 | 87705.47 | 15-SEP-20:00 | 29156.46 | 1.00 |
October | 0.00 | 0.00 | 0.160080E+12 | 0.790772E+11 | 88367.53 | 30-OCT-17:40 | 29246.52 | 1.00 |
November | 0.00 | 0.00 | 0.145277E+12 | 0.761487E+11 | 80394.72 | 16-NOV-19:40 | 29178.86 | 1.00 |
December | 0.00 | 0.00 | 0.141781E+12 | 0.768266E+11 | 85981.44 | 24-DEC-08:70 | 28802.80 | 1.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181867E+13 | 0.944757E+12 | 1.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.120192E+12 | 0.722705E+11 | 63720.48 | 28296.85 | 1.00 | |
Maximum of Months | 0.00 | 0.00 | 0.175770E+12 | 0.831930E+11 | 90888.03 | 36003.87 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112833E+11 | 0.699822E+10 | 17517.23 | 08-JAN-09:51 | 11488.24 | 0.87 |
February | 0.00 | 0.00 | 0.111005E+11 | 0.710682E+10 | 17458.41 | 12-FEB-09:41 | 11935.21 | 0.90 |
March | 0.00 | 0.00 | 0.127273E+11 | 0.817868E+10 | 17040.52 | 15-MAR-08:62 | 10924.71 | 0.94 |
April | 0.00 | 0.00 | 0.126238E+11 | 0.797206E+10 | 16424.64 | 14-APR-17:02 | 12966.55 | 0.95 |
May | 0.00 | 0.00 | 0.127228E+11 | 0.772450E+10 | 17935.85 | 10-MAY-21:51 | 11911.21 | 0.94 |
June | 0.00 | 0.00 | 0.127450E+11 | 0.788757E+10 | 18992.24 | 25-JUN-21:51 | 11163.57 | 0.94 |
July | 0.00 | 0.00 | 0.110132E+11 | 0.649842E+10 | 19029.77 | 19-JUL-21:51 | 11441.59 | 0.92 |
August | 0.00 | 0.00 | 0.112645E+11 | 0.654012E+10 | 18650.08 | 19-AUG-20:11 | 10537.71 | 0.92 |
September | 0.00 | 0.00 | 0.110934E+11 | 0.647254E+10 | 18671.79 | 15-SEP-21:51 | 10703.56 | 0.93 |
October | 0.00 | 0.00 | 0.108702E+11 | 0.625129E+10 | 18816.86 | 30-OCT-20:41 | 10862.70 | 0.92 |
November | 0.00 | 0.00 | 0.107827E+11 | 0.635352E+10 | 18210.46 | 16-NOV-21:41 | 11653.00 | 0.90 |
December | 0.00 | 0.00 | 0.108977E+11 | 0.657763E+10 | 18385.43 | 24-DEC-09:41 | 11441.63 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.139124E+12 | 0.845614E+11 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.107827E+11 | 0.625129E+10 | 16424.64 | 10537.71 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.127450E+11 | 0.817868E+10 | 19029.77 | 12966.55 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.979428E+10 | 0.580001E+10 | 17473.65 | 08-JAN-09:51 | 11302.19 | 0.86 |
February | 0.00 | 0.00 | 0.100087E+11 | 0.616030E+10 | 17370.70 | 12-FEB-09:41 | 11806.06 | 0.89 |
March | 0.00 | 0.00 | 0.121619E+11 | 0.764285E+10 | 17415.01 | 15-MAR-08:62 | 10949.03 | 0.94 |
April | 0.00 | 0.00 | 0.126955E+11 | 0.799336E+10 | 16672.35 | 14-APR-17:02 | 13102.09 | 0.95 |
May | 0.00 | 0.00 | 0.131416E+11 | 0.802390E+10 | 18192.43 | 10-MAY-21:51 | 12104.61 | 0.95 |
June | 0.00 | 0.00 | 0.135145E+11 | 0.854048E+10 | 19311.95 | 25-JUN-21:51 | 11399.22 | 0.95 |
July | 0.00 | 0.00 | 0.114979E+11 | 0.688791E+10 | 19365.88 | 19-JUL-21:51 | 11697.34 | 0.93 |
August | 0.00 | 0.00 | 0.114880E+11 | 0.670526E+10 | 18875.86 | 19-AUG-20:11 | 10672.39 | 0.93 |
September | 0.00 | 0.00 | 0.109459E+11 | 0.632753E+10 | 18884.34 | 15-SEP-21:51 | 10800.96 | 0.93 |
October | 0.00 | 0.00 | 0.102940E+11 | 0.576781E+10 | 18918.44 | 30-OCT-20:41 | 10984.03 | 0.91 |
November | 0.00 | 0.00 | 0.973254E+10 | 0.553481E+10 | 18219.58 | 16-NOV-21:41 | 11687.33 | 0.89 |
December | 0.00 | 0.00 | 0.939111E+10 | 0.538419E+10 | 18223.84 | 24-DEC-09:41 | 11179.67 | 0.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.134666E+12 | 0.807684E+11 | 0.91 | |||
Minimum of Months | 0.00 | 0.00 | 0.939111E+10 | 0.538419E+10 | 16672.35 | 10672.39 | 0.85 | |
Maximum of Months | 0.00 | 0.00 | 0.135145E+11 | 0.854048E+10 | 19365.88 | 13102.09 | 0.95 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.579905E+11 | 0.365571E+11 | 40775.99 | 05-JAN-14:30 | 29100.10 | 1.00 |
February | 0.00 | 0.00 | 0.516054E+11 | 0.316397E+11 | 41020.67 | 04-FEB-15:40 | 31520.17 | 1.00 |
March | 0.00 | 0.00 | 0.469450E+11 | 0.245055E+11 | 31671.33 | 05-MAR-09:00 | 19943.32 | 1.00 |
April | 0.00 | 0.00 | 0.397891E+11 | 0.180689E+11 | 28318.65 | 01-APR-20:10 | 18138.26 | 1.00 |
May | 0.00 | 0.00 | 0.414982E+11 | 0.186574E+11 | 31072.70 | 07-MAY-08:00 | 19686.36 | 1.00 |
June | 0.00 | 0.00 | 0.402025E+11 | 0.179025E+11 | 28883.19 | 13-JUN-20:20 | 18448.40 | 1.00 |
July | 0.00 | 0.00 | 0.345252E+11 | 0.143254E+11 | 27142.88 | 19-JUL-20:40 | 10142.07 | 1.00 |
August | 0.00 | 0.00 | 0.339977E+11 | 0.136315E+11 | 27341.73 | 13-AUG-08:00 | 15244.81 | 0.98 |
September | 0.00 | 0.00 | 0.376677E+11 | 0.164599E+11 | 27355.28 | 13-SEP-20:20 | 16783.36 | 0.99 |
October | 0.00 | 0.00 | 0.423580E+11 | 0.201730E+11 | 33839.84 | 29-OCT-08:00 | 23127.26 | 0.99 |
November | 0.00 | 0.00 | 0.501931E+11 | 0.285609E+11 | 40880.48 | 19-NOV-14:40 | 31473.90 | 1.00 |
December | 0.00 | 0.00 | 0.569699E+11 | 0.348160E+11 | 41831.57 | 31-DEC-08:40 | 31390.40 | 1.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.533742E+12 | 0.275298E+12 | 1.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.339977E+11 | 0.136315E+11 | 27142.88 | 10142.07 | 0.98 | |
Maximum of Months | 0.00 | 0.00 | 0.579905E+11 | 0.365571E+11 | 41831.57 | 31520.17 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.622963E+11 | 0.385246E+11 | 109459.80 | 27-JAN-09:02 | 74879.93 | 0.63 |
February | 0.00 | 0.00 | 0.610518E+11 | 0.389849E+11 | 106562.91 | 26-FEB-09:02 | 79506.26 | 0.67 |
March | 0.00 | 0.00 | 0.728180E+11 | 0.475684E+11 | 109257.16 | 15-MAR-08:62 | 74261.86 | 0.72 |
April | 0.00 | 0.00 | 0.774560E+11 | 0.518655E+11 | 105870.13 | 14-APR-18:02 | 79487.27 | 0.76 |
May | 0.00 | 0.00 | 0.869019E+11 | 0.586463E+11 | 113052.40 | 31-MAY-21:51 | 78664.52 | 0.81 |
June | 0.00 | 0.00 | 0.905206E+11 | 0.618304E+11 | 123829.49 | 25-JUN-21:51 | 73727.04 | 0.86 |
July | 0.00 | 0.00 | 0.811451E+11 | 0.551612E+11 | 124113.01 | 19-JUL-21:51 | 74139.22 | 0.78 |
August | 0.00 | 0.00 | 0.767645E+11 | 0.496397E+11 | 123393.48 | 19-AUG-20:11 | 71260.68 | 0.74 |
September | 0.00 | 0.00 | 0.713198E+11 | 0.453725E+11 | 122338.89 | 15-SEP-21:51 | 71040.00 | 0.71 |
October | 0.00 | 0.00 | 0.685594E+11 | 0.421122E+11 | 121674.95 | 30-OCT-20:41 | 74965.91 | 0.69 |
November | 0.00 | 0.00 | 0.639880E+11 | 0.394432E+11 | 114957.88 | 26-NOV-22:51 | 76686.04 | 0.66 |
December | 0.00 | 0.00 | 0.609146E+11 | 0.370156E+11 | 114630.57 | 24-DEC-09:41 | 73497.11 | 0.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.873736E+12 | 0.566164E+12 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.609146E+11 | 0.370156E+11 | 105870.13 | 71040.00 | 0.63 | |
Maximum of Months | 0.00 | 0.00 | 0.905206E+11 | 0.618304E+11 | 124113.01 | 79506.26 | 0.86 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112120E+11 | 0.716367E+10 | 16105.19 | 07-JAN-09:11 | 11414.47 | 0.88 |
February | 0.00 | 0.00 | 0.111351E+11 | 0.736938E+10 | 16267.26 | 12-FEB-09:41 | 11283.99 | 0.91 |
March | 0.00 | 0.00 | 0.126752E+11 | 0.829144E+10 | 15003.50 | 02-MAR-07:41 | 11080.68 | 0.96 |
April | 0.00 | 0.00 | 0.126879E+11 | 0.817176E+10 | 14476.10 | 14-APR-17:02 | 11042.65 | 0.97 |
May | 0.00 | 0.00 | 0.128087E+11 | 0.797596E+10 | 15752.12 | 10-MAY-21:51 | 10377.79 | 0.96 |
June | 0.00 | 0.00 | 0.127860E+11 | 0.807285E+10 | 16731.68 | 25-JUN-21:51 | 9750.91 | 0.96 |
July | 0.00 | 0.00 | 0.109831E+11 | 0.657543E+10 | 16646.12 | 19-JUL-21:51 | 9859.14 | 0.94 |
August | 0.00 | 0.00 | 0.112803E+11 | 0.664657E+10 | 16582.57 | 19-AUG-20:11 | 9360.41 | 0.94 |
September | 0.00 | 0.00 | 0.111748E+11 | 0.669876E+10 | 16543.36 | 15-SEP-21:51 | 9445.90 | 0.94 |
October | 0.00 | 0.00 | 0.108613E+11 | 0.638506E+10 | 16750.31 | 30-OCT-20:41 | 9659.46 | 0.93 |
November | 0.00 | 0.00 | 0.107702E+11 | 0.652785E+10 | 16225.60 | 25-NOV-22:51 | 10231.47 | 0.91 |
December | 0.00 | 0.00 | 0.108188E+11 | 0.671411E+10 | 16878.18 | 24-DEC-09:41 | 10625.01 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.139193E+12 | 0.865928E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.107702E+11 | 0.638506E+10 | 14476.10 | 9360.41 | 0.87 | |
Maximum of Months | 0.00 | 0.00 | 0.128087E+11 | 0.829144E+10 | 16878.18 | 11414.47 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.965337E+10 | 0.567599E+10 | 16003.14 | 07-JAN-09:11 | 11168.93 | 0.87 |
February | 0.00 | 0.00 | 0.100059E+11 | 0.621381E+10 | 16202.01 | 12-FEB-09:41 | 11148.52 | 0.90 |
March | 0.00 | 0.00 | 0.120904E+11 | 0.769307E+10 | 15149.05 | 02-MAR-07:41 | 11063.21 | 0.96 |
April | 0.00 | 0.00 | 0.127603E+11 | 0.821485E+10 | 14649.06 | 14-APR-17:02 | 11127.89 | 0.97 |
May | 0.00 | 0.00 | 0.132346E+11 | 0.834742E+10 | 15931.03 | 10-MAY-21:51 | 10517.59 | 0.96 |
June | 0.00 | 0.00 | 0.135578E+11 | 0.874064E+10 | 16964.49 | 25-JUN-21:51 | 9930.23 | 0.96 |
July | 0.00 | 0.00 | 0.114760E+11 | 0.700539E+10 | 16890.99 | 19-JUL-21:51 | 10056.77 | 0.94 |
August | 0.00 | 0.00 | 0.115054E+11 | 0.682510E+10 | 16734.02 | 19-AUG-20:11 | 9452.08 | 0.94 |
September | 0.00 | 0.00 | 0.110216E+11 | 0.653746E+10 | 16685.80 | 15-SEP-21:51 | 9502.51 | 0.94 |
October | 0.00 | 0.00 | 0.102736E+11 | 0.586165E+10 | 16795.15 | 30-OCT-20:41 | 9738.80 | 0.93 |
November | 0.00 | 0.00 | 0.968022E+10 | 0.556445E+10 | 16197.44 | 25-NOV-22:51 | 10192.83 | 0.90 |
December | 0.00 | 0.00 | 0.925405E+10 | 0.530970E+10 | 16726.69 | 24-DEC-09:41 | 10396.10 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.134513E+12 | 0.819895E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.925405E+10 | 0.530970E+10 | 14649.06 | 9452.08 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.135578E+11 | 0.874064E+10 | 16964.49 | 11168.93 | 0.97 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.293395E+10 | 0.181981E+10 | 5091.94 | 08-JAN-09:51 | 3128.11 | 0.88 |
February | 0.00 | 0.00 | 0.286642E+10 | 0.181958E+10 | 5052.40 | 12-FEB-09:41 | 3295.84 | 0.90 |
March | 0.00 | 0.00 | 0.332423E+10 | 0.210756E+10 | 4913.35 | 15-MAR-08:62 | 2902.89 | 0.95 |
April | 0.00 | 0.00 | 0.333642E+10 | 0.206969E+10 | 4610.48 | 14-APR-17:02 | 3710.84 | 0.95 |
May | 0.00 | 0.00 | 0.331182E+10 | 0.195868E+10 | 5026.94 | 10-MAY-21:51 | 3312.74 | 0.95 |
June | 0.00 | 0.00 | 0.329693E+10 | 0.198961E+10 | 5474.39 | 25-JUN-21:51 | 3089.63 | 0.94 |
July | 0.00 | 0.00 | 0.285635E+10 | 0.161861E+10 | 5504.02 | 19-JUL-21:51 | 3202.89 | 0.93 |
August | 0.00 | 0.00 | 0.293560E+10 | 0.164192E+10 | 5543.22 | 19-AUG-20:11 | 2776.41 | 0.93 |
September | 0.00 | 0.00 | 0.292017E+10 | 0.166231E+10 | 5383.85 | 15-SEP-21:51 | 2937.33 | 0.93 |
October | 0.00 | 0.00 | 0.282585E+10 | 0.157883E+10 | 5448.22 | 30-OCT-20:41 | 2984.32 | 0.92 |
November | 0.00 | 0.00 | 0.279124E+10 | 0.161972E+10 | 5191.14 | 25-NOV-22:51 | 3178.27 | 0.90 |
December | 0.00 | 0.00 | 0.281588E+10 | 0.170216E+10 | 5380.57 | 24-DEC-09:41 | 3139.07 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.362149E+11 | 0.215885E+11 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.279124E+10 | 0.157883E+10 | 4610.48 | 2776.41 | 0.87 | |
Maximum of Months | 0.00 | 0.00 | 0.333642E+10 | 0.210756E+10 | 5543.22 | 3710.84 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.253807E+10 | 0.147819E+10 | 5077.93 | 08-JAN-09:51 | 3046.34 | 0.87 |
February | 0.00 | 0.00 | 0.258126E+10 | 0.157528E+10 | 5013.16 | 12-FEB-09:41 | 3230.34 | 0.89 |
March | 0.00 | 0.00 | 0.317919E+10 | 0.196688E+10 | 5019.07 | 15-MAR-08:62 | 2901.64 | 0.94 |
April | 0.00 | 0.00 | 0.335586E+10 | 0.207719E+10 | 4680.22 | 14-APR-17:02 | 3744.72 | 0.95 |
May | 0.00 | 0.00 | 0.342125E+10 | 0.204469E+10 | 5115.98 | 10-MAY-21:51 | 3351.59 | 0.95 |
June | 0.00 | 0.00 | 0.349582E+10 | 0.215732E+10 | 5558.74 | 25-JUN-21:51 | 3157.71 | 0.95 |
July | 0.00 | 0.00 | 0.298283E+10 | 0.172685E+10 | 5593.76 | 19-JUL-21:51 | 3279.60 | 0.93 |
August | 0.00 | 0.00 | 0.299328E+10 | 0.168509E+10 | 5604.97 | 19-AUG-20:11 | 2809.32 | 0.93 |
September | 0.00 | 0.00 | 0.288138E+10 | 0.162071E+10 | 5442.95 | 15-SEP-21:51 | 2958.54 | 0.93 |
October | 0.00 | 0.00 | 0.267445E+10 | 0.143715E+10 | 5478.14 | 30-OCT-20:41 | 3014.62 | 0.92 |
November | 0.00 | 0.00 | 0.251232E+10 | 0.137204E+10 | 5198.00 | 25-NOV-22:51 | 3160.83 | 0.89 |
December | 0.00 | 0.00 | 0.241375E+10 | 0.134971E+10 | 5330.72 | 24-DEC-09:41 | 3019.55 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.350295E+11 | 0.204911E+11 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.241375E+10 | 0.134971E+10 | 4680.22 | 2809.32 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.349582E+10 | 0.215732E+10 | 5604.97 | 3744.72 | 0.95 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.174395E+11 | 0.122640E+11 | 20235.88 | 08-JAN-09:51 | 13892.34 | 0.88 |
February | 0.00 | 0.00 | 0.158264E+11 | 0.111184E+11 | 20053.21 | 12-FEB-09:41 | 14258.87 | 0.90 |
March | 0.00 | 0.00 | 0.161808E+11 | 0.107979E+11 | 19047.94 | 15-MAR-08:62 | 12323.06 | 0.94 |
April | 0.00 | 0.00 | 0.150180E+11 | 0.948309E+10 | 18441.41 | 14-APR-17:02 | 13747.04 | 0.94 |
May | 0.00 | 0.00 | 0.155393E+11 | 0.963992E+10 | 20081.36 | 10-MAY-21:51 | 13118.51 | 0.93 |
June | 0.00 | 0.00 | 0.150831E+11 | 0.936780E+10 | 21665.38 | 25-JUN-21:51 | 12226.29 | 0.93 |
July | 0.00 | 0.00 | 0.136800E+11 | 0.828219E+10 | 21596.79 | 19-JUL-21:51 | 12411.64 | 0.91 |
August | 0.00 | 0.00 | 0.137446E+11 | 0.809507E+10 | 22682.94 | 19-AUG-20:11 | 11343.22 | 0.91 |
September | 0.00 | 0.00 | 0.142167E+11 | 0.861104E+10 | 21643.38 | 15-SEP-21:51 | 12029.75 | 0.92 |
October | 0.00 | 0.00 | 0.149861E+11 | 0.931799E+10 | 21946.27 | 30-OCT-20:41 | 12844.63 | 0.92 |
November | 0.00 | 0.00 | 0.160127E+11 | 0.106434E+11 | 20982.35 | 25-NOV-22:51 | 13454.14 | 0.91 |
December | 0.00 | 0.00 | 0.171341E+11 | 0.118881E+11 | 21633.40 | 24-DEC-09:41 | 13865.68 | 0.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.184861E+12 | 0.119509E+12 | 0.91 | |||
Minimum of Months | 0.00 | 0.00 | 0.136800E+11 | 0.809507E+10 | 18441.41 | 11343.22 | 0.88 | |
Maximum of Months | 0.00 | 0.00 | 0.174395E+11 | 0.122640E+11 | 22682.94 | 14258.87 | 0.94 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 467.91 | 24149.38 | 11-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 391.78 | 22391.90 | 24-FEB-09:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 387.31 | 24728.46 | 13-MAR-08:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 341.48 | 23074.23 | 21-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 384.79 | 29596.27 | 17-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 330.53 | 18967.54 | 30-JUN-18:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 388.14 | 29457.35 | 11-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 467.40 | 26873.66 | 21-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 412.38 | 29332.55 | 19-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 493.49 | 28457.26 | 24-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 461.70 | 24327.79 | 01-NOV-08:05 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 483.34 | 20663.44 | 15-DEC-09:05 |
Annual Sum or Average | 0.00 | 418.07 | ||||
Minimum of Months | 0.00 | 0.00 | 330.53 | 18967.54 | ||
Maximum of Months | 0.00 | 0.00 | 493.49 | 29596.27 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 471222.15 | 699507.63 | 10-JAN-19:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 481159.36 | 724866.25 | 14-FEB-19:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 497784.81 | 717453.70 | 28-MAR-18:05 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 555102.60 | 810069.36 | 10-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 603784.67 | 829449.50 | 22-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 613208.55 | 857985.16 | 13-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 516587.06 | 815648.81 | 19-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 568511.20 | 835575.27 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 558974.11 | 838372.82 | 15-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 537735.28 | 766778.77 | 16-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 518227.53 | 765213.48 | 17-NOV-19:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 496386.72 | 741635.07 | 29-DEC-19:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 535041.68 | 0.00 | ||||
Minimum of Months | 471222.15 | 699507.63 | 0.00 | 0.00 | ||
Maximum of Months | 613208.55 | 857985.16 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17552.26 | 35128.48 | 09-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17453.83 | 34997.76 | 06-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17216.52 | 34671.14 | 02-MAR-07:46 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16868.57 | 33782.32 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16539.90 | 33137.50 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 16309.22 | 32548.00 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16217.07 | 32297.46 | 19-JUL-06:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16338.06 | 32628.61 | 31-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16586.78 | 33292.74 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16918.41 | 33984.62 | 30-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17248.79 | 34672.47 | 29-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 17480.67 | 34945.91 | 27-DEC-07:15 |
Annual Sum or Average | 0.00 | 16891.12 | ||||
Minimum of Months | 0.00 | 0.00 | 16217.07 | 32297.46 | ||
Maximum of Months | 0.00 | 0.00 | 17552.26 | 35128.48 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.87 | 2194.93 | 01-JAN-00:10 | 0.87 |
February | 0.530997E+10 | 0.87 | 2194.93 | 01-FEB-00:03 | 0.87 |
March | 0.587890E+10 | 0.87 | 2194.93 | 01-MAR-00:03 | 0.87 |
April | 0.568926E+10 | 0.87 | 2194.93 | 01-APR-00:10 | 0.87 |
May | 0.587890E+10 | 0.87 | 2194.93 | 01-MAY-00:05 | 0.87 |
June | 0.568926E+10 | 0.87 | 2194.93 | 01-JUN-00:05 | 0.87 |
July | 0.587890E+10 | 0.87 | 2194.93 | 01-JUL-00:10 | 0.87 |
August | 0.587890E+10 | 0.87 | 2194.93 | 01-AUG-00:10 | 0.87 |
September | 0.568926E+10 | 0.87 | 2194.93 | 01-SEP-00:10 | 0.87 |
October | 0.587890E+10 | 0.87 | 2194.93 | 01-OCT-00:10 | 0.87 |
November | 0.568926E+10 | 0.87 | 2194.93 | 01-NOV-00:10 | 0.87 |
December | 0.587890E+10 | 0.87 | 2194.93 | 01-DEC-00:03 | 0.87 |
Annual Sum or Average | 0.692193E+11 | 0.87 | |||
Minimum of Months | 0.530997E+10 | 0.87 | 2194.93 | 0.87 | |
Maximum of Months | 0.587890E+10 | 0.87 | 2194.93 | 0.87 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.298702E+11 | 0.72 | 17196.12 | 05-JAN-21:10 | 0.92 |
February | 0.274310E+11 | 0.72 | 17110.66 | 22-FEB-21:10 | 0.91 |
March | 0.304927E+11 | 0.72 | 17447.08 | 29-MAR-20:10 | 0.92 |
April | 0.297898E+11 | 0.73 | 18057.16 | 27-APR-20:10 | 0.94 |
May | 0.311187E+11 | 0.73 | 19745.04 | 05-MAY-20:10 | 0.99 |
June | 0.311153E+11 | 0.74 | 21462.77 | 13-JUN-20:10 | 1.05 |
July | 0.302045E+11 | 0.72 | 18475.85 | 14-JUL-20:10 | 0.96 |
August | 0.298670E+11 | 0.72 | 17945.22 | 14-AUG-20:10 | 0.94 |
September | 0.289169E+11 | 0.72 | 17506.17 | 13-SEP-20:10 | 0.93 |
October | 0.293077E+11 | 0.71 | 16774.56 | 04-OCT-20:10 | 0.90 |
November | 0.286299E+11 | 0.71 | 16515.37 | 21-NOV-21:10 | 0.89 |
December | 0.295603E+11 | 0.71 | 17010.08 | 08-DEC-21:10 | 0.91 |
Annual Sum or Average | 0.356304E+12 | 0.72 | |||
Minimum of Months | 0.274310E+11 | 0.71 | 16515.37 | 0.89 | |
Maximum of Months | 0.311187E+11 | 0.74 | 21462.77 | 1.05 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.26 | 76.61 | 01-JAN-00:10 | 0.26 |
February | 0.185347E+09 | 0.26 | 76.61 | 01-FEB-00:03 | 0.26 |
March | 0.205205E+09 | 0.26 | 76.61 | 01-MAR-00:03 | 0.26 |
April | 0.198586E+09 | 0.26 | 76.61 | 01-APR-00:10 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:05 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:05 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:10 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:10 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.26 | 76.61 | 01-NOV-00:10 | 0.26 |
December | 0.205205E+09 | 0.26 | 76.61 | 01-DEC-00:03 | 0.26 |
Annual Sum or Average | 0.241613E+10 | 0.26 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.26 | 76.61 | 0.26 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.26 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:03 | 0.26 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.26 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.26 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.26 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.26 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:03 | 0.26 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.26 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.514624E+09 | 0.50 | 722.23 | 01-JAN-09:02 | 0.57 |
February | 0.507361E+09 | 0.51 | 722.23 | 01-FEB-09:11 | 0.57 |
March | 0.577289E+09 | 0.54 | 722.23 | 01-MAR-09:02 | 0.57 |
April | 0.564541E+09 | 0.54 | 722.23 | 01-APR-08:62 | 0.57 |
May | 0.554445E+09 | 0.54 | 722.23 | 01-MAY-08:62 | 0.57 |
June | 0.563441E+09 | 0.54 | 722.23 | 01-JUN-08:62 | 0.57 |
July | 0.481594E+09 | 0.53 | 722.23 | 01-JUL-08:61 | 0.57 |
August | 0.481449E+09 | 0.53 | 722.23 | 01-AUG-08:62 | 0.57 |
September | 0.478084E+09 | 0.53 | 722.23 | 01-SEP-08:62 | 0.57 |
October | 0.465624E+09 | 0.53 | 722.23 | 01-OCT-08:62 | 0.57 |
November | 0.468963E+09 | 0.51 | 722.23 | 01-NOV-08:62 | 0.57 |
December | 0.486234E+09 | 0.50 | 722.23 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.614365E+10 | 0.53 | |||
Minimum of Months | 0.465624E+09 | 0.50 | 722.23 | 0.57 | |
Maximum of Months | 0.577289E+09 | 0.54 | 722.23 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.430039E+09 | 0.49 | 730.98 | 01-JAN-09:02 | 0.57 |
February | 0.445735E+09 | 0.51 | 730.98 | 01-FEB-09:11 | 0.57 |
March | 0.547531E+09 | 0.54 | 730.98 | 01-MAR-09:02 | 0.57 |
April | 0.568635E+09 | 0.55 | 730.98 | 01-APR-08:62 | 0.57 |
May | 0.579237E+09 | 0.54 | 730.98 | 01-MAY-08:62 | 0.57 |
June | 0.605666E+09 | 0.54 | 730.98 | 01-JUN-08:62 | 0.57 |
July | 0.505202E+09 | 0.53 | 730.98 | 01-JUL-08:61 | 0.57 |
August | 0.492150E+09 | 0.53 | 730.98 | 01-AUG-08:62 | 0.57 |
September | 0.470406E+09 | 0.53 | 730.98 | 01-SEP-08:62 | 0.57 |
October | 0.437544E+09 | 0.52 | 730.98 | 01-OCT-08:62 | 0.57 |
November | 0.412063E+09 | 0.51 | 730.98 | 01-NOV-08:62 | 0.57 |
December | 0.402397E+09 | 0.49 | 730.98 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.589661E+10 | 0.52 | |||
Minimum of Months | 0.402397E+09 | 0.49 | 730.98 | 0.57 | |
Maximum of Months | 0.605666E+09 | 0.55 | 730.98 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.228176E+10 | 0.57 | 2004.00 | 05-JAN-14:30 | 0.57 |
February | 0.200712E+10 | 0.57 | 1813.35 | 03-FEB-13:30 | 0.57 |
March | 0.188817E+10 | 0.57 | 1086.38 | 11-MAR-09:00 | 0.57 |
April | 0.162588E+10 | 0.57 | 1031.91 | 01-APR-20:20 | 0.57 |
May | 0.167108E+10 | 0.57 | 1083.71 | 06-MAY-08:00 | 0.57 |
June | 0.161796E+10 | 0.57 | 1039.74 | 13-JUN-20:20 | 0.57 |
July | 0.146744E+10 | 0.57 | 969.30 | 15-JUL-20:10 | 0.57 |
August | 0.142206E+10 | 0.56 | 961.21 | 14-AUG-20:40 | 0.57 |
September | 0.153656E+10 | 0.57 | 995.74 | 13-SEP-20:30 | 0.57 |
October | 0.169817E+10 | 0.56 | 1168.35 | 29-OCT-09:00 | 0.57 |
November | 0.195469E+10 | 0.57 | 1796.69 | 19-NOV-12:40 | 0.57 |
December | 0.226028E+10 | 0.57 | 2008.80 | 07-DEC-13:50 | 0.57 |
Annual Sum or Average | 0.214312E+11 | 0.57 | |||
Minimum of Months | 0.142206E+10 | 0.56 | 961.21 | 0.57 | |
Maximum of Months | 0.228176E+10 | 0.57 | 2008.80 | 0.57 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.281651E+10 | 0.36 | 4835.87 | 01-JAN-09:02 | 0.57 |
February | 0.279057E+10 | 0.38 | 4835.87 | 01-FEB-09:11 | 0.57 |
March | 0.326591E+10 | 0.41 | 4835.87 | 01-MAR-09:02 | 0.57 |
April | 0.348467E+10 | 0.44 | 4835.87 | 01-APR-08:62 | 0.57 |
May | 0.399779E+10 | 0.47 | 4835.87 | 01-MAY-08:62 | 0.57 |
June | 0.435496E+10 | 0.49 | 4835.87 | 01-JUN-08:62 | 0.57 |
July | 0.370706E+10 | 0.45 | 4835.87 | 01-JUL-08:61 | 0.57 |
August | 0.339904E+10 | 0.42 | 4835.87 | 01-AUG-08:62 | 0.57 |
September | 0.312710E+10 | 0.41 | 4835.87 | 01-SEP-08:62 | 0.57 |
October | 0.299826E+10 | 0.40 | 4835.87 | 01-OCT-08:62 | 0.57 |
November | 0.282043E+10 | 0.38 | 4835.87 | 01-NOV-08:62 | 0.57 |
December | 0.271044E+10 | 0.36 | 4835.87 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.394727E+11 | 0.41 | |||
Minimum of Months | 0.271044E+10 | 0.36 | 4835.87 | 0.57 | |
Maximum of Months | 0.435496E+10 | 0.49 | 4835.87 | 0.57 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.513031E+09 | 0.50 | 638.00 | 01-JAN-09:02 | 0.57 |
February | 0.513005E+09 | 0.52 | 638.00 | 01-FEB-09:11 | 0.57 |
March | 0.578592E+09 | 0.55 | 638.00 | 01-MAR-09:02 | 0.57 |
April | 0.571744E+09 | 0.56 | 638.00 | 01-APR-08:62 | 0.57 |
May | 0.568460E+09 | 0.55 | 638.00 | 01-MAY-08:62 | 0.57 |
June | 0.570693E+09 | 0.55 | 638.00 | 01-JUN-08:62 | 0.57 |
July | 0.487878E+09 | 0.54 | 638.00 | 01-JUL-08:61 | 0.57 |
August | 0.489762E+09 | 0.54 | 638.00 | 01-AUG-08:62 | 0.57 |
September | 0.487367E+09 | 0.54 | 638.00 | 01-SEP-08:62 | 0.57 |
October | 0.471792E+09 | 0.53 | 638.00 | 01-OCT-08:62 | 0.57 |
November | 0.477306E+09 | 0.52 | 638.00 | 01-NOV-08:62 | 0.57 |
December | 0.488973E+09 | 0.50 | 638.00 | 01-DEC-08:42 | 0.57 |
Annual Sum or Average | 0.621860E+10 | 0.53 | |||
Minimum of Months | 0.471792E+09 | 0.50 | 638.00 | 0.57 | |
Maximum of Months | 0.578592E+09 | 0.56 | 638.00 | 0.57 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.439180E+09 | 0.50 | 643.82 | 01-JAN-09:02 | 0.57 |
February | 0.458004E+09 | 0.51 | 643.82 | 01-FEB-09:11 | 0.57 |
March | 0.550014E+09 | 0.55 | 643.82 | 01-MAR-09:02 | 0.57 |
April | 0.575292E+09 | 0.56 | 643.82 | 01-APR-08:62 | 0.57 |
May | 0.591690E+09 | 0.55 | 643.82 | 01-MAY-08:62 | 0.57 |
June | 0.616935E+09 | 0.55 | 643.82 | 01-JUN-08:62 | 0.57 |
July | 0.511442E+09 | 0.54 | 643.82 | 01-JUL-08:61 | 0.57 |
August | 0.500829E+09 | 0.54 | 643.82 | 01-AUG-08:62 | 0.57 |
September | 0.480228E+09 | 0.54 | 643.82 | 01-SEP-08:62 | 0.57 |
October | 0.444039E+09 | 0.53 | 643.82 | 01-OCT-08:62 | 0.57 |
November | 0.424651E+09 | 0.51 | 643.82 | 01-NOV-08:62 | 0.57 |
December | 0.412296E+09 | 0.49 | 643.82 | 01-DEC-08:42 | 0.57 |
Annual Sum or Average | 0.600460E+10 | 0.53 | |||
Minimum of Months | 0.412296E+09 | 0.49 | 643.82 | 0.57 | |
Maximum of Months | 0.616935E+09 | 0.56 | 643.82 | 0.57 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133160E+09 | 0.50 | 200.51 | 01-JAN-09:02 | 0.57 |
February | 0.130203E+09 | 0.52 | 200.51 | 01-FEB-09:11 | 0.57 |
March | 0.151020E+09 | 0.54 | 200.51 | 01-MAR-09:02 | 0.57 |
April | 0.149513E+09 | 0.55 | 200.51 | 01-APR-08:62 | 0.57 |
May | 0.144199E+09 | 0.54 | 200.51 | 01-MAY-08:62 | 0.57 |
June | 0.144378E+09 | 0.54 | 200.51 | 01-JUN-08:62 | 0.57 |
July | 0.125756E+09 | 0.53 | 200.51 | 01-JUL-08:61 | 0.57 |
August | 0.126854E+09 | 0.53 | 200.51 | 01-AUG-08:62 | 0.57 |
September | 0.126208E+09 | 0.53 | 200.51 | 01-SEP-08:62 | 0.57 |
October | 0.121446E+09 | 0.53 | 200.51 | 01-OCT-08:62 | 0.57 |
November | 0.120536E+09 | 0.52 | 200.51 | 01-NOV-08:62 | 0.57 |
December | 0.125159E+09 | 0.50 | 200.51 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.159843E+10 | 0.53 | |||
Minimum of Months | 0.120536E+09 | 0.50 | 200.51 | 0.57 | |
Maximum of Months | 0.151020E+09 | 0.55 | 200.51 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111528E+09 | 0.50 | 202.75 | 01-JAN-09:02 | 0.57 |
February | 0.113978E+09 | 0.51 | 202.75 | 01-FEB-09:11 | 0.57 |
March | 0.143415E+09 | 0.54 | 202.75 | 01-MAR-09:02 | 0.57 |
April | 0.150594E+09 | 0.55 | 202.75 | 01-APR-08:62 | 0.57 |
May | 0.150279E+09 | 0.54 | 202.75 | 01-MAY-08:62 | 0.57 |
June | 0.155439E+09 | 0.54 | 202.75 | 01-JUN-08:62 | 0.57 |
July | 0.131557E+09 | 0.53 | 202.75 | 01-JUL-08:61 | 0.57 |
August | 0.129616E+09 | 0.53 | 202.75 | 01-AUG-08:62 | 0.57 |
September | 0.124352E+09 | 0.53 | 202.75 | 01-SEP-08:62 | 0.57 |
October | 0.114728E+09 | 0.52 | 202.75 | 01-OCT-08:62 | 0.57 |
November | 0.106917E+09 | 0.51 | 202.75 | 01-NOV-08:62 | 0.57 |
December | 0.104070E+09 | 0.49 | 202.75 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.153647E+10 | 0.53 | |||
Minimum of Months | 0.104070E+09 | 0.49 | 202.75 | 0.57 | |
Maximum of Months | 0.155439E+09 | 0.55 | 202.75 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.844615E+09 | 0.51 | 802.02 | 01-JAN-09:02 | 0.57 |
February | 0.752712E+09 | 0.52 | 802.02 | 01-FEB-09:11 | 0.57 |
March | 0.742696E+09 | 0.54 | 802.02 | 01-MAR-09:02 | 0.57 |
April | 0.676063E+09 | 0.54 | 802.02 | 01-APR-08:62 | 0.57 |
May | 0.688954E+09 | 0.53 | 802.02 | 01-MAY-08:62 | 0.57 |
June | 0.671139E+09 | 0.53 | 802.02 | 01-JUN-08:62 | 0.57 |
July | 0.609251E+09 | 0.52 | 802.02 | 01-JUL-08:61 | 0.57 |
August | 0.600538E+09 | 0.52 | 802.02 | 01-AUG-08:62 | 0.57 |
September | 0.629350E+09 | 0.53 | 802.02 | 01-SEP-08:62 | 0.57 |
October | 0.666787E+09 | 0.52 | 802.02 | 01-OCT-08:62 | 0.57 |
November | 0.736510E+09 | 0.52 | 802.02 | 01-NOV-08:62 | 0.57 |
December | 0.821328E+09 | 0.50 | 802.02 | 01-DEC-08:42 | 0.57 |
Annual Sum or Average | 0.843994E+10 | 0.52 | |||
Minimum of Months | 0.600538E+09 | 0.50 | 802.02 | 0.57 | |
Maximum of Months | 0.844615E+09 | 0.54 | 802.02 | 0.57 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 9727173.77 | 8754456.39 | 167.23 | 11-JAN-09:05 | 150.50 | 150.50 | 29.98 | 0.19 |
February | 7226347.06 | 6503712.35 | 152.01 | 24-FEB-09:15 | 136.81 | 136.81 | 28.99 | 0.17 |
March | 7869502.04 | 7082551.84 | 169.05 | 13-MAR-08:05 | 152.15 | 152.15 | 29.64 | 0.19 |
April | 6658895.65 | 5993006.09 | 162.24 | 21-APR-08:05 | 146.01 | 146.01 | 30.30 | 0.19 |
May | 7767412.62 | 6990671.36 | 203.25 | 17-MAY-08:05 | 182.92 | 182.92 | 30.67 | 0.24 |
June | 6252205.66 | 5626985.09 | 134.02 | 30-JUN-18:07 | 120.62 | 120.62 | 29.76 | 0.15 |
July | 7905228.54 | 7114705.69 | 197.88 | 11-JUL-08:05 | 178.09 | 178.09 | 29.88 | 0.23 |
August | 9710212.64 | 8739191.37 | 203.76 | 21-AUG-08:05 | 183.38 | 183.38 | 33.42 | 0.24 |
September | 8205512.22 | 7384960.99 | 201.31 | 19-SEP-08:05 | 181.18 | 181.18 | 30.60 | 0.24 |
October | 10511245.90 | 9460121.31 | 199.92 | 24-OCT-08:05 | 179.93 | 179.93 | 31.24 | 0.24 |
November | 9369678.45 | 8432710.61 | 171.27 | 01-NOV-08:05 | 154.14 | 154.14 | 30.57 | 0.20 |
December | 10247923.22 | 9223130.90 | 150.32 | 15-DEC-09:05 | 135.29 | 135.29 | 31.01 | 0.17 |
Annual Sum or Average | 0.101451E+09 | 91306203.99 | ||||||
Minimum of Months | 6252205.66 | 5626985.09 | 134.02 | 120.62 | 120.62 | 28.99 | 0.15 | |
Maximum of Months | 10511245.90 | 9460121.31 | 203.76 | 183.38 | 183.38 | 33.42 | 0.24 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.212449E+10 | 0.191204E+10 | 1552.99 | 10-JAN-19:02 | 1397.69 | 1397.69 | 6.72 | 23.13 |
February | 0.200152E+10 | 0.180137E+10 | 1749.61 | 15-FEB-19:02 | 1574.65 | 1574.65 | 6.72 | 24.33 |
March | 0.238680E+10 | 0.214812E+10 | 1874.68 | 14-MAR-22:00 | 1687.21 | 1687.21 | 6.72 | 25.04 |
April | 0.285099E+10 | 0.256589E+10 | 2189.43 | 10-APR-18:02 | 1970.49 | 1970.49 | 6.72 | 26.72 |
May | 0.351280E+10 | 0.316152E+10 | 2509.06 | 31-MAY-20:20 | 2258.15 | 2258.15 | 6.72 | 28.27 |
June | 0.351863E+10 | 0.316677E+10 | 2746.10 | 13-JUN-18:02 | 2471.49 | 2471.49 | 6.72 | 29.34 |
July | 0.253150E+10 | 0.227835E+10 | 2013.90 | 19-JUL-21:52 | 1812.51 | 1812.51 | 6.72 | 25.80 |
August | 0.307593E+10 | 0.276834E+10 | 2550.25 | 14-AUG-20:20 | 2295.22 | 2295.22 | 6.72 | 28.46 |
September | 0.285867E+10 | 0.257281E+10 | 2130.05 | 08-SEP-18:03 | 1917.05 | 1917.05 | 6.72 | 26.41 |
October | 0.273846E+10 | 0.246462E+10 | 1961.85 | 16-OCT-18:02 | 1765.67 | 1765.67 | 6.72 | 25.52 |
November | 0.248496E+10 | 0.223647E+10 | 1954.42 | 30-NOV-23:00 | 1758.98 | 1758.98 | 6.72 | 25.48 |
December | 0.233962E+10 | 0.210566E+10 | 1957.84 | 05-DEC-23:07 | 1762.06 | 1762.06 | 6.72 | 25.50 |
Annual Sum or Average | 0.324244E+11 | 0.291820E+11 | ||||||
Minimum of Months | 0.200152E+10 | 0.180137E+10 | 1552.99 | 1397.69 | 1397.69 | 6.72 | 23.13 | |
Maximum of Months | 0.351863E+10 | 0.316677E+10 | 2746.10 | 2471.49 | 2471.49 | 6.72 | 29.34 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.129381E+11 | 0.116443E+11 | 4830.53 | 01-JAN-00:10 | 4347.48 | 4347.48 | 9.22 | 42.73 |
February | 0.116860E+11 | 0.105174E+11 | 4830.53 | 01-FEB-00:03 | 4347.48 | 4347.48 | 9.27 | 42.73 |
March | 0.129381E+11 | 0.116443E+11 | 4830.53 | 01-MAR-00:03 | 4347.48 | 4347.48 | 9.33 | 42.73 |
April | 0.125207E+11 | 0.112687E+11 | 4830.53 | 01-APR-00:10 | 4347.48 | 4347.48 | 9.63 | 42.73 |
May | 0.129381E+11 | 0.116443E+11 | 4830.53 | 01-MAY-00:05 | 4347.48 | 4347.48 | 9.98 | 42.73 |
June | 0.125207E+11 | 0.112687E+11 | 4830.53 | 01-JUN-00:05 | 4347.48 | 4347.48 | 9.51 | 42.73 |
July | 0.129381E+11 | 0.116443E+11 | 4830.53 | 01-JUL-00:10 | 4347.48 | 4347.48 | 9.38 | 42.73 |
August | 0.129381E+11 | 0.116443E+11 | 4830.53 | 01-AUG-00:10 | 4347.48 | 4347.48 | 9.53 | 42.73 |
September | 0.125207E+11 | 0.112687E+11 | 4830.53 | 01-SEP-00:10 | 4347.48 | 4347.48 | 9.65 | 42.73 |
October | 0.129381E+11 | 0.116443E+11 | 4830.53 | 01-OCT-00:10 | 4347.48 | 4347.48 | 9.58 | 42.73 |
November | 0.125207E+11 | 0.112687E+11 | 4830.53 | 01-NOV-00:10 | 4347.48 | 4347.48 | 9.40 | 42.73 |
December | 0.129381E+11 | 0.116443E+11 | 4830.53 | 01-DEC-00:03 | 4347.48 | 4347.48 | 9.30 | 42.73 |
Annual Sum or Average | 0.152336E+12 | 0.137102E+12 | ||||||
Minimum of Months | 0.116860E+11 | 0.105174E+11 | 4830.53 | 4347.48 | 4347.48 | 9.22 | 42.73 | |
Maximum of Months | 0.129381E+11 | 0.116443E+11 | 4830.53 | 4347.48 | 4347.48 | 9.98 | 42.73 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 52.74 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 52.24 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 52.86 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.31 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 54.13 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 54.70 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.63 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.99 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.90 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.46 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 54.22 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 52.48 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 52.24 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.99 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 23.77 | 23.77 | 467.91 | 24149.38 | 11-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 31.95 | 31.95 | 391.78 | 22391.90 | 24-FEB-09:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 28.88 | 28.88 | 387.31 | 24728.46 | 13-MAR-08:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.28 | 29.28 | 341.48 | 23074.23 | 21-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.64 | 28.64 | 384.79 | 29596.27 | 17-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.46 | 28.46 | 330.53 | 18967.54 | 30-JUN-18:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.15 | 30.15 | 388.14 | 29457.35 | 11-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 30.41 | 60.00 | 467.40 | 26873.66 | 21-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 32.17 | 60.00 | 412.38 | 29332.55 | 19-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.77 | 30.77 | 493.49 | 28457.26 | 24-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 34.04 | 60.00 | 461.70 | 24327.79 | 01-NOV-08:05 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 30.91 | 30.91 | 483.34 | 20663.44 | 15-DEC-09:05 |
Annual Sum or Average | 0.00 | 418.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.77 | 23.77 | 330.53 | 18967.54 | ||
Maximum of Months | 0.00 | 0.00 | 34.04 | 60.00 | 493.49 | 29596.27 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 471222.15 | 699507.63 | 10-JAN-19:03 | 10.61 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 481159.36 | 724866.25 | 14-FEB-19:03 | 10.75 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 497784.81 | 717453.70 | 28-MAR-18:05 | 10.71 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 555102.60 | 810069.36 | 10-APR-18:03 | 11.23 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 603784.67 | 829449.50 | 22-MAY-18:03 | 11.33 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 613208.55 | 857985.16 | 13-JUN-18:03 | 11.49 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 516587.06 | 815648.81 | 19-JUL-21:52 | 11.26 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 568511.20 | 835575.27 | 14-AUG-18:03 | 11.37 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 558974.11 | 838372.82 | 15-SEP-21:52 | 11.38 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 537735.28 | 766778.77 | 16-OCT-18:03 | 10.98 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 518227.53 | 765213.48 | 17-NOV-19:03 | 10.97 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 496386.72 | 741635.07 | 29-DEC-19:03 | 10.84 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 535041.68 | 0.00 | ||||||
Minimum of Months | 471222.15 | 699507.63 | 10.61 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 613208.55 | 857985.16 | 11.49 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 52.74 | 59.63 | 17552.26 | 35128.48 | 09-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 52.24 | 58.19 | 17453.83 | 34997.76 | 06-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.86 | 58.84 | 17216.52 | 34671.14 | 02-MAR-07:46 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.31 | 58.54 | 16868.57 | 33782.32 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 54.13 | 58.49 | 16539.90 | 33137.50 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.70 | 58.90 | 16309.22 | 32548.00 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.63 | 58.80 | 16217.07 | 32297.46 | 19-JUL-06:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.99 | 59.36 | 16338.06 | 32628.61 | 31-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.90 | 59.05 | 16586.78 | 33292.74 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.46 | 59.42 | 16918.41 | 33984.62 | 30-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54.22 | 58.54 | 17248.79 | 34672.47 | 29-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.48 | 58.72 | 17480.67 | 34945.91 | 27-DEC-07:15 |
Annual Sum or Average | 0.00 | 16891.12 | ||||||
Minimum of Months | 0.00 | 0.00 | 52.24 | 58.19 | 16217.07 | 32297.46 | ||
Maximum of Months | 0.00 | 0.00 | 54.99 | 59.63 | 17552.26 | 35128.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.121324E+10 | 0.00 | 0.932200E+12 | 0.298702E+11 | 0.00 | 0.00 |
February | 0.920952E+09 | 0.00 | 0.856379E+12 | 0.274310E+11 | 0.00 | 0.00 |
March | 0.100787E+10 | 0.00 | 0.989988E+12 | 0.304927E+11 | 0.00 | 0.00 |
April | 0.870682E+09 | 0.00 | 0.108269E+13 | 0.297898E+11 | 0.00 | 0.00 |
May | 0.101612E+10 | 0.00 | 0.122583E+13 | 0.311187E+11 | 0.00 | 0.00 |
June | 0.849725E+09 | 0.00 | 0.120141E+13 | 0.311153E+11 | 0.00 | 0.00 |
July | 0.101377E+10 | 0.00 | 0.104107E+13 | 0.302045E+11 | 0.00 | 0.00 |
August | 0.122532E+10 | 0.00 | 0.116372E+13 | 0.298670E+11 | 0.00 | 0.00 |
September | 0.104372E+10 | 0.00 | 0.110296E+13 | 0.289169E+11 | 0.00 | 0.00 |
October | 0.127153E+10 | 0.00 | 0.109382E+13 | 0.293077E+11 | 0.00 | 0.00 |
November | 0.116694E+10 | 0.00 | 0.100930E+13 | 0.286299E+11 | 0.00 | 0.00 |
December | 0.125688E+10 | 0.00 | 0.994618E+12 | 0.295603E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.128567E+11 | 0.00 | 0.126940E+14 | 0.356304E+12 | 0.00 | 0.00 |
Minimum of Months | 0.849725E+09 | 0.00 | 0.856379E+12 | 0.274310E+11 | 0.00 | 0.00 |
Maximum of Months | 0.127153E+10 | 0.00 | 0.122583E+13 | 0.311187E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 5797.56 | 0.00 | 0.132338E+12 | 0.587890E+10 | 0.00 | 0.00 |
February | 4674.87 | 0.00 | 0.120192E+12 | 0.530997E+10 | 0.00 | 0.00 |
March | 3790.60 | 0.00 | 0.138626E+12 | 0.587890E+10 | 0.00 | 0.00 |
April | 5134.28 | 0.00 | 0.154072E+12 | 0.568926E+10 | 0.00 | 0.00 |
May | 4140.66 | 0.00 | 0.175770E+12 | 0.587890E+10 | 0.00 | 0.00 |
June | 4113.25 | 0.00 | 0.170193E+12 | 0.568926E+10 | 0.00 | 0.00 |
July | 6574.07 | 0.00 | 0.149804E+12 | 0.587890E+10 | 0.00 | 0.00 |
August | 2846.76 | 0.00 | 0.170212E+12 | 0.587890E+10 | 0.00 | 0.00 |
September | 4859.26 | 0.00 | 0.160323E+12 | 0.568926E+10 | 0.00 | 0.00 |
October | 5175.66 | 0.00 | 0.160080E+12 | 0.587890E+10 | 0.00 | 0.00 |
November | 4722.57 | 0.00 | 0.145277E+12 | 0.568926E+10 | 0.00 | 0.00 |
December | 8589.47 | 0.00 | 0.141781E+12 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 60419.00 | 0.00 | 0.181867E+13 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 2846.76 | 0.00 | 0.120192E+12 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 8589.47 | 0.00 | 0.175770E+12 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.298702E+11 | 0.932200E+12 | 0.121324E+10 | 0.00 | 0.310158E+12 | 0.00 | 0.00 | 0.00 |
February | 0.274310E+11 | 0.856379E+12 | 0.920952E+09 | 18296357.07 | 0.336083E+12 | 0.00 | 0.00 | 0.00 |
March | 0.304927E+11 | 0.989988E+12 | 0.100787E+10 | 0.00 | 0.439198E+12 | 0.00 | 0.00 | 0.00 |
April | 0.297898E+11 | 0.108269E+13 | 0.870682E+09 | 0.00 | 0.563475E+12 | 0.00 | 0.00 | 0.00 |
May | 0.311187E+11 | 0.122583E+13 | 0.101612E+10 | 0.00 | 0.675624E+12 | 0.00 | 0.00 | 0.00 |
June | 0.311153E+11 | 0.120141E+13 | 0.849725E+09 | 0.00 | 0.643526E+12 | 0.00 | 0.00 | 0.00 |
July | 0.302045E+11 | 0.104107E+13 | 0.101377E+10 | 0.00 | 0.486278E+12 | 0.00 | 0.00 | 0.00 |
August | 0.298670E+11 | 0.116372E+13 | 0.122532E+10 | 0.00 | 0.615306E+12 | 0.00 | 0.00 | 0.00 |
September | 0.289169E+11 | 0.110296E+13 | 0.104372E+10 | 0.00 | 0.569154E+12 | 0.00 | 0.00 | 0.00 |
October | 0.293077E+11 | 0.109382E+13 | 0.127153E+10 | 0.00 | 0.547561E+12 | 0.00 | 0.00 | 0.00 |
November | 0.286299E+11 | 0.100930E+13 | 0.116694E+10 | 0.00 | 0.441794E+12 | 0.00 | 0.00 | 0.00 |
December | 0.295603E+11 | 0.994618E+12 | 0.125688E+10 | 0.00 | 0.311732E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356304E+12 | 0.126940E+14 | 0.128567E+11 | 18296357.07 | 0.593989E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274310E+11 | 0.856379E+12 | 0.849725E+09 | 0.00 | 0.310158E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.311187E+11 | 0.122583E+13 | 0.127153E+10 | 18296357.07 | 0.675624E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.132338E+12 | 5797.56 | 0.00 | 0.808186E+11 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.120192E+12 | 4674.87 | 0.00 | 0.842012E+11 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.138626E+12 | 3790.60 | 0.00 | 0.106581E+12 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.154072E+12 | 5134.28 | 0.00 | 0.128875E+12 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.175770E+12 | 4140.66 | 0.00 | 0.151168E+12 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.170193E+12 | 4113.25 | 0.00 | 0.145357E+12 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.149804E+12 | 6574.07 | 0.00 | 0.113103E+12 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.170212E+12 | 2846.76 | 0.00 | 0.137459E+12 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.160323E+12 | 4859.26 | 0.00 | 0.128707E+12 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.160080E+12 | 5175.66 | 0.00 | 0.124466E+12 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.145277E+12 | 4722.57 | 0.00 | 0.105490E+12 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.141781E+12 | 8589.47 | 0.00 | 0.832683E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.181867E+13 | 60419.00 | 0.00 | 0.138950E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.120192E+12 | 2846.76 | 0.00 | 0.808186E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.175770E+12 | 8589.47 | 0.00 | 0.151168E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.298702E+11 | 0.121324E+10 | 0.932200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274310E+11 | 0.920952E+09 | 0.856379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304927E+11 | 0.100787E+10 | 0.989988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297898E+11 | 0.870682E+09 | 0.108269E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.311187E+11 | 0.101612E+10 | 0.122583E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.311153E+11 | 0.849725E+09 | 0.120141E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302045E+11 | 0.101377E+10 | 0.104107E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298670E+11 | 0.122532E+10 | 0.116372E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289169E+11 | 0.104372E+10 | 0.110296E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293077E+11 | 0.127153E+10 | 0.109382E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286299E+11 | 0.116694E+10 | 0.100930E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295603E+11 | 0.125688E+10 | 0.994618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356304E+12 | 0.128567E+11 | 0.126940E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274310E+11 | 0.849725E+09 | 0.856379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.311187E+11 | 0.127153E+10 | 0.122583E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 5797.56 | 0.132338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 4674.87 | 0.120192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 3790.60 | 0.138626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 5134.28 | 0.154072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 4140.66 | 0.175770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 4113.25 | 0.170193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 6574.07 | 0.149804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 2846.76 | 0.170212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 4859.26 | 0.160323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 5175.66 | 0.160080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 4722.57 | 0.145277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 8589.47 | 0.141781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 60419.00 | 0.181867E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 2846.76 | 0.120192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 8589.47 | 0.175770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 61194203.76 | 0.121592E+11 | 0.00 | 390.18 | 0.312310E+11 | 0.00 | 2824679.35 | 0.00 | 1.14 |
February | 0.00 | 0.143448E+11 | 0.00 | 12675.28 | 0.252066E+11 | 0.00 | 2634759.97 | 0.00 | 1.13 |
March | 0.00 | 0.133111E+11 | 0.00 | 0.00 | 0.356040E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
April | 0.00 | 0.189086E+11 | 0.00 | 0.00 | 0.431204E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
May | 0.00 | 0.307352E+11 | 0.00 | 0.00 | 0.456871E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
June | 0.00 | 0.430734E+11 | 0.00 | 0.00 | 0.305693E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
July | 0.00 | 0.256525E+11 | 0.00 | 0.00 | 0.301599E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
August | 0.00 | 0.258099E+11 | 0.00 | 0.00 | 0.462008E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 0.00 | 0.245891E+11 | 0.00 | 0.00 | 0.420066E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
October | 0.00 | 0.145338E+11 | 0.00 | 0.00 | 0.501030E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
November | 0.00 | 0.174963E+11 | 0.00 | 0.00 | 0.379801E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
December | 13870443.00 | 0.174128E+11 | 0.00 | 0.00 | 0.344319E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
Annual Sum or Average | 75064646.76 | 0.258027E+12 | 0.00 | 13065.45 | 0.452301E+12 | 0.00 | 5459439.31 | 0.00 | 1.14 |
Minimum of Months | 0.00 | 0.121592E+11 | 0.00 | 0.00 | 0.252066E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
Maximum of Months | 61194203.76 | 0.430734E+11 | 0.00 | 12675.28 | 0.501030E+11 | 0.00 | 2824679.35 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6666482.47 | 0.429819E+10 | 0.00 | 0.00 | 0.912328E+09 | 0.00 | 0.00 | 0.00 | 2.47 |
February | 0.00 | 0.439972E+10 | 0.00 | 4324.03 | 0.451191E+09 | 0.00 | 271359.83 | 0.00 | 2.48 |
March | 0.00 | 0.507905E+10 | 0.00 | 0.00 | 0.600756E+09 | 0.00 | 0.00 | 0.00 | 2.37 |
April | 0.00 | 0.605590E+10 | 0.00 | 0.00 | 0.867396E+09 | 0.00 | 0.00 | 0.00 | 2.28 |
May | 0.00 | 0.691231E+10 | 0.00 | 0.00 | 0.151072E+10 | 0.00 | 0.00 | 0.00 | 2.25 |
June | 0.00 | 0.710206E+10 | 0.00 | 0.00 | 0.110265E+10 | 0.00 | 0.00 | 0.00 | 2.24 |
July | 0.00 | 0.444419E+10 | 0.00 | 0.00 | 0.147356E+10 | 0.00 | 0.00 | 0.00 | 2.19 |
August | 0.00 | 0.530595E+10 | 0.00 | 0.00 | 0.239603E+10 | 0.00 | 0.00 | 0.00 | 2.22 |
September | 0.00 | 0.551242E+10 | 0.00 | 0.00 | 0.172296E+10 | 0.00 | 0.00 | 0.00 | 2.25 |
October | 0.00 | 0.509059E+10 | 0.00 | 0.00 | 0.194007E+10 | 0.00 | 0.00 | 0.00 | 2.26 |
November | 0.00 | 0.523310E+10 | 0.00 | 0.00 | 0.113564E+10 | 0.00 | 0.00 | 0.00 | 2.37 |
December | 1444362.93 | 0.481316E+10 | 0.00 | 0.00 | 0.126722E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
Annual Sum or Average | 8110845.40 | 0.642466E+11 | 0.00 | 4324.03 | 0.153805E+11 | 0.00 | 271359.83 | 0.00 | 2.32 |
Minimum of Months | 0.00 | 0.429819E+10 | 0.00 | 0.00 | 0.451191E+09 | 0.00 | 0.00 | 0.00 | 2.19 |
Maximum of Months | 6666482.47 | 0.710206E+10 | 0.00 | 4324.03 | 0.239603E+10 | 0.00 | 271359.83 | 0.00 | 2.48 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5210687.33 | 0.187704E+10 | 0.00 | 1096.37 | 0.212416E+10 | 0.00 | 665084.57 | 0.00 | 1.65 |
February | 0.00 | 0.223375E+10 | 0.00 | 3599.19 | 0.143906E+10 | 0.00 | 239431.19 | 0.00 | 1.65 |
March | 0.00 | 0.291427E+10 | 0.00 | 0.00 | 0.165893E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
April | 0.00 | 0.381332E+10 | 0.00 | 0.00 | 0.200572E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
May | 0.00 | 0.442350E+10 | 0.00 | 0.00 | 0.270435E+10 | 0.00 | 0.00 | 0.00 | 1.65 |
June | 0.00 | 0.480042E+10 | 0.00 | 0.00 | 0.214150E+10 | 0.00 | 0.00 | 0.00 | 1.65 |
July | 0.00 | 0.245111E+10 | 0.00 | 0.00 | 0.270480E+10 | 0.00 | 0.00 | 0.00 | 1.65 |
August | 0.00 | 0.307634E+10 | 0.00 | 0.00 | 0.359657E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
September | 0.00 | 0.303139E+10 | 0.00 | 0.00 | 0.313920E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
October | 0.00 | 0.228090E+10 | 0.00 | 0.00 | 0.366897E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
November | 0.00 | 0.229184E+10 | 0.00 | 0.00 | 0.282024E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
December | 1273284.78 | 0.217593E+10 | 0.00 | 0.00 | 0.259587E+10 | 0.00 | 0.00 | 0.00 | 1.65 |
Annual Sum or Average | 6483972.11 | 0.353698E+11 | 0.00 | 4695.56 | 0.305994E+11 | 0.00 | 904515.76 | 0.00 | 1.66 |
Minimum of Months | 0.00 | 0.187704E+10 | 0.00 | 0.00 | 0.143906E+10 | 0.00 | 0.00 | 0.00 | 1.65 |
Maximum of Months | 5210687.33 | 0.480042E+10 | 0.00 | 3599.19 | 0.366897E+10 | 0.00 | 665084.57 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5856671.08 | 0.393750E+09 | 0.00 | 0.00 | 0.357572E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
February | 242195.15 | 0.759178E+09 | 0.00 | 0.00 | 0.285910E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
March | 0.00 | 0.141981E+10 | 0.00 | 0.00 | 0.306819E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
April | 0.00 | 0.348945E+10 | 0.00 | 0.00 | 0.230551E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
May | 0.00 | 0.554963E+10 | 0.00 | 0.00 | 0.193372E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
June | 0.00 | 0.700155E+10 | 0.00 | 0.00 | 0.790977E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
July | 0.00 | 0.372683E+10 | 0.00 | 0.00 | 0.157632E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
August | 0.00 | 0.300370E+10 | 0.00 | 0.00 | 0.371104E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
September | 0.00 | 0.215433E+10 | 0.00 | 0.00 | 0.396640E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
October | 0.00 | 0.716022E+09 | 0.00 | 0.00 | 0.519720E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
November | 0.00 | 0.617285E+09 | 0.00 | 0.00 | 0.445786E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
December | 1268908.85 | 0.358553E+09 | 0.00 | 0.00 | 0.438435E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
Annual Sum or Average | 7367775.08 | 0.291901E+11 | 0.00 | 0.00 | 0.378264E+11 | 0.00 | 0.00 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.358553E+09 | 0.00 | 0.00 | 0.790977E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
Maximum of Months | 5856671.08 | 0.700155E+10 | 0.00 | 0.00 | 0.519720E+10 | 0.00 | 0.00 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3610698.64 | 15693201.46 | 0.00 | 0.00 | 0.243152E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
February | 149315.83 | 0.154702E+09 | 0.00 | 0.00 | 0.207600E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
March | 0.00 | 0.554400E+09 | 0.00 | 0.00 | 0.220442E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
April | 0.00 | 0.159022E+10 | 0.00 | 0.00 | 0.191885E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
May | 0.00 | 0.302818E+10 | 0.00 | 0.00 | 0.142509E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
June | 0.00 | 0.397500E+10 | 0.00 | 0.00 | 0.630030E+09 | 0.00 | 0.00 | 0.00 | 0.89 |
July | 0.00 | 0.189524E+10 | 0.00 | 0.00 | 0.127731E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.138930E+10 | 0.00 | 0.00 | 0.268498E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.829647E+09 | 0.00 | 0.00 | 0.292636E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
October | 0.00 | 0.136362E+09 | 0.00 | 0.00 | 0.350917E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
November | 0.00 | 72633157.04 | 0.00 | 0.00 | 0.305625E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
December | 782295.50 | 12100310.20 | 0.00 | 0.00 | 0.291195E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
Annual Sum or Average | 4542309.97 | 0.136535E+11 | 0.00 | 0.00 | 0.270519E+11 | 0.00 | 0.00 | 0.00 | 0.83 |
Minimum of Months | 0.00 | 12100310.20 | 0.00 | 0.00 | 0.630030E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
Maximum of Months | 3610698.64 | 0.397500E+10 | 0.00 | 0.00 | 0.350917E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 718304.44 | 0.463048E+11 | 0.00 | 536781.78 | 0.773888E+09 | 0.00 | 64225788.82 | 0.00 | 19.26 |
February | 0.00 | 0.424750E+11 | 0.00 | 32823.87 | 0.590731E+09 | 0.00 | 2675054.05 | 0.00 | 19.18 |
March | 0.00 | 0.527379E+11 | 0.00 | 0.00 | 0.671162E+09 | 0.00 | 0.00 | 0.00 | 19.24 |
April | 0.00 | 0.672243E+11 | 0.00 | 0.00 | 0.684959E+09 | 0.00 | 0.00 | 0.00 | 19.17 |
May | 0.00 | 0.826083E+11 | 0.00 | 0.00 | 0.880139E+09 | 0.00 | 0.00 | 0.00 | 19.10 |
June | 0.00 | 0.796359E+11 | 0.00 | 0.00 | 0.808198E+09 | 0.00 | 0.00 | 0.00 | 18.91 |
July | 0.00 | 0.600129E+11 | 0.00 | 0.00 | 0.794481E+09 | 0.00 | 0.00 | 0.00 | 19.26 |
August | 0.00 | 0.773402E+11 | 0.00 | 0.00 | 0.984251E+09 | 0.00 | 0.00 | 0.00 | 19.37 |
September | 0.00 | 0.715332E+11 | 0.00 | 0.00 | 0.978035E+09 | 0.00 | 0.00 | 0.00 | 19.29 |
October | 0.00 | 0.690178E+11 | 0.00 | 0.00 | 0.104702E+10 | 0.00 | 0.00 | 0.00 | 19.40 |
November | 0.00 | 0.596086E+11 | 0.00 | 0.00 | 0.854421E+09 | 0.00 | 0.00 | 0.00 | 19.34 |
December | 0.00 | 0.551948E+11 | 0.00 | 228169.76 | 0.786081E+09 | 0.00 | 13958944.50 | 0.00 | 19.29 |
Annual Sum or Average | 718304.44 | 0.763694E+12 | 0.00 | 797775.40 | 0.985337E+10 | 0.00 | 80859787.37 | 0.00 | 19.24 |
Minimum of Months | 0.00 | 0.424750E+11 | 0.00 | 0.00 | 0.590731E+09 | 0.00 | 0.00 | 0.00 | 18.91 |
Maximum of Months | 718304.44 | 0.826083E+11 | 0.00 | 536781.78 | 0.104702E+10 | 0.00 | 64225788.82 | 0.00 | 19.40 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2845513.26 | 0.193173E+11 | 0.00 | 317535.31 | 0.722241E+09 | 0.00 | 24121025.54 | 0.00 | 3.41 |
February | 0.00 | 0.179285E+11 | 0.00 | 31385.73 | 0.343233E+09 | 0.00 | 1218267.41 | 0.00 | 3.39 |
March | 0.00 | 0.206474E+11 | 0.00 | 0.00 | 0.133127E+10 | 0.00 | 0.00 | 0.00 | 3.30 |
April | 0.00 | 0.254253E+11 | 0.00 | 0.00 | 0.209228E+10 | 0.00 | 0.00 | 0.00 | 3.25 |
May | 0.00 | 0.305380E+11 | 0.00 | 0.00 | 0.330381E+10 | 0.00 | 0.00 | 0.00 | 3.23 |
June | 0.00 | 0.300847E+11 | 0.00 | 0.00 | 0.265786E+10 | 0.00 | 0.00 | 0.00 | 3.21 |
July | 0.00 | 0.211161E+11 | 0.00 | 0.00 | 0.312970E+10 | 0.00 | 0.00 | 0.00 | 3.21 |
August | 0.00 | 0.259748E+11 | 0.00 | 0.00 | 0.534531E+10 | 0.00 | 0.00 | 0.00 | 3.23 |
September | 0.00 | 0.258760E+11 | 0.00 | 0.00 | 0.332592E+10 | 0.00 | 0.00 | 0.00 | 3.24 |
October | 0.00 | 0.249697E+11 | 0.00 | 0.00 | 0.332286E+10 | 0.00 | 0.00 | 0.00 | 3.26 |
November | 0.00 | 0.237046E+11 | 0.00 | 0.00 | 0.117644E+10 | 0.00 | 0.00 | 0.00 | 3.33 |
December | 973451.07 | 0.230554E+11 | 0.00 | 85925.61 | 0.599104E+09 | 0.00 | 4852002.43 | 0.00 | 3.39 |
Annual Sum or Average | 3818964.33 | 0.288638E+12 | 0.00 | 434846.66 | 0.273500E+11 | 0.00 | 30191295.38 | 0.00 | 3.29 |
Minimum of Months | 0.00 | 0.179285E+11 | 0.00 | 0.00 | 0.343233E+09 | 0.00 | 0.00 | 0.00 | 3.21 |
Maximum of Months | 2845513.26 | 0.305380E+11 | 0.00 | 317535.31 | 0.534531E+10 | 0.00 | 24121025.54 | 0.00 | 3.41 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15075038.96 | 0.529780E+11 | 0.00 | 761896.24 | 0.137035E+11 | 0.00 | 80896899.64 | 0.00 | 1.64 |
February | 0.00 | 0.538453E+11 | 0.00 | 102346.28 | 0.739078E+10 | 0.00 | 3976461.88 | 0.00 | 1.64 |
March | 0.00 | 0.589093E+11 | 0.00 | 0.00 | 0.168609E+11 | 0.00 | 0.00 | 0.00 | 1.64 |
April | 0.00 | 0.737966E+11 | 0.00 | 0.00 | 0.226020E+11 | 0.00 | 0.00 | 0.00 | 1.64 |
May | 0.00 | 0.956898E+11 | 0.00 | 0.00 | 0.242267E+11 | 0.00 | 0.00 | 0.00 | 1.65 |
June | 0.00 | 0.100817E+12 | 0.00 | 0.00 | 0.167539E+11 | 0.00 | 0.00 | 0.00 | 1.67 |
July | 0.00 | 0.606428E+11 | 0.00 | 0.00 | 0.257423E+11 | 0.00 | 0.00 | 0.00 | 1.65 |
August | 0.00 | 0.709897E+11 | 0.00 | 0.00 | 0.398590E+11 | 0.00 | 0.00 | 0.00 | 1.65 |
September | 0.00 | 0.682255E+11 | 0.00 | 0.00 | 0.341556E+11 | 0.00 | 0.00 | 0.00 | 1.64 |
October | 0.00 | 0.603409E+11 | 0.00 | 0.00 | 0.382207E+11 | 0.00 | 0.00 | 0.00 | 1.64 |
November | 0.00 | 0.637608E+11 | 0.00 | 0.00 | 0.213073E+11 | 0.00 | 0.00 | 0.00 | 1.64 |
December | 5671388.62 | 0.628798E+11 | 0.00 | 191139.85 | 0.165062E+11 | 0.00 | 15095865.36 | 0.00 | 1.64 |
Annual Sum or Average | 20746427.58 | 0.822876E+12 | 0.00 | 1055382.37 | 0.277329E+12 | 0.00 | 99969226.89 | 0.00 | 1.64 |
Minimum of Months | 0.00 | 0.529780E+11 | 0.00 | 0.00 | 0.739078E+10 | 0.00 | 0.00 | 0.00 | 1.64 |
Maximum of Months | 15075038.96 | 0.100817E+12 | 0.00 | 761896.24 | 0.398590E+11 | 0.00 | 80896899.64 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 363597.47 | 0.149284E+10 | 258942.73 | 0.00 | 0.168891E+09 | 0.00 | 0.00 | 5440.68 | 0.48 |
February | 0.00 | 0.142311E+10 | 95199.99 | 0.00 | 0.125381E+09 | 0.00 | 0.00 | 4900.87 | 0.48 |
March | 0.00 | 0.181171E+10 | 912061.32 | 0.00 | 89498240.07 | 0.00 | 0.00 | 5482.60 | 0.48 |
April | 0.00 | 0.225283E+10 | 528299.24 | 0.00 | 0.102999E+09 | 0.00 | 0.00 | 5134.52 | 0.48 |
May | 0.00 | 0.271753E+10 | 928970.43 | 0.00 | 0.137818E+09 | 0.00 | 0.00 | 14164.65 | 0.48 |
June | 0.00 | 0.262109E+10 | 918086.61 | 0.00 | 0.133034E+09 | 0.00 | 0.00 | 7755.45 | 0.48 |
July | 0.00 | 0.198039E+10 | 2080481.08 | 0.00 | 0.131186E+09 | 0.00 | 0.00 | 35366.50 | 0.48 |
August | 0.00 | 0.247240E+10 | 1925330.68 | 0.00 | 0.164050E+09 | 0.00 | 0.00 | 16030.93 | 0.48 |
September | 0.00 | 0.230498E+10 | 1557694.17 | 0.00 | 0.148942E+09 | 0.00 | 0.00 | 14356.05 | 0.48 |
October | 0.00 | 0.222348E+10 | 1729677.78 | 0.00 | 0.153219E+09 | 0.00 | 0.00 | 26754.34 | 0.48 |
November | 0.00 | 0.189760E+10 | 568927.68 | 0.00 | 0.167440E+09 | 0.00 | 0.00 | 7173.22 | 0.48 |
December | 0.00 | 0.168263E+10 | 271303.13 | 0.00 | 0.202498E+09 | 0.00 | 0.00 | 3717.94 | 0.48 |
Annual Sum or Average | 363597.47 | 0.248806E+11 | 11774974.87 | 0.00 | 0.172496E+10 | 0.00 | 0.00 | 146277.76 | 0.48 |
Minimum of Months | 0.00 | 0.142311E+10 | 95199.99 | 0.00 | 89498240.07 | 0.00 | 0.00 | 3717.94 | 0.48 |
Maximum of Months | 363597.47 | 0.271753E+10 | 2080481.08 | 0.00 | 0.202498E+09 | 0.00 | 0.00 | 35366.50 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 363554.86 | 0.147311E+10 | 728275.77 | 0.00 | 0.187939E+09 | 0.00 | 0.00 | 15717.16 | 0.48 |
February | 0.00 | 0.140681E+10 | 531892.78 | 0.00 | 0.141059E+09 | 0.00 | 0.00 | 10227.15 | 0.48 |
March | 0.00 | 0.180499E+10 | 1623405.29 | 0.00 | 95264589.19 | 0.00 | 0.00 | 22908.54 | 0.48 |
April | 0.00 | 0.225438E+10 | 692586.71 | 0.00 | 0.101004E+09 | 0.00 | 0.00 | 6055.29 | 0.48 |
May | 0.00 | 0.272715E+10 | 812238.50 | 0.00 | 0.127987E+09 | 0.00 | 0.00 | 12816.23 | 0.48 |
June | 0.00 | 0.263688E+10 | 493453.61 | 0.00 | 0.117347E+09 | 0.00 | 0.00 | 2960.04 | 0.48 |
July | 0.00 | 0.198874E+10 | 1649460.47 | 0.00 | 0.123034E+09 | 0.00 | 0.00 | 23172.86 | 0.48 |
August | 0.00 | 0.248144E+10 | 1483038.96 | 0.00 | 0.155153E+09 | 0.00 | 0.00 | 13720.16 | 0.48 |
September | 0.00 | 0.230053E+10 | 1994213.15 | 0.00 | 0.152664E+09 | 0.00 | 0.00 | 21118.11 | 0.48 |
October | 0.00 | 0.220953E+10 | 2623820.42 | 0.00 | 0.165981E+09 | 0.00 | 0.00 | 41014.65 | 0.48 |
November | 0.00 | 0.187247E+10 | 1966428.57 | 0.00 | 0.190917E+09 | 0.00 | 0.00 | 25055.31 | 0.48 |
December | 0.00 | 0.166073E+10 | 432829.37 | 0.00 | 0.224016E+09 | 0.00 | 0.00 | 7211.33 | 0.48 |
Annual Sum or Average | 363554.86 | 0.248168E+11 | 15031643.59 | 0.00 | 0.178237E+10 | 0.00 | 0.00 | 201976.83 | 0.48 |
Minimum of Months | 0.00 | 0.140681E+10 | 432829.37 | 0.00 | 95264589.19 | 0.00 | 0.00 | 2960.04 | 0.48 |
Maximum of Months | 363554.86 | 0.272715E+10 | 2623820.42 | 0.00 | 0.224016E+09 | 0.00 | 0.00 | 41014.65 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.225351E+11 | 0.00 | 235005.39 | 0.00 | 0.00 | 4695050.14 | 0.00 | 0.54 |
February | 0.00 | 0.209975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.257911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
April | 0.00 | 0.319502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
May | 0.00 | 0.387288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.373560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.286598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.357743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.332943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.322497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 0.00 | 0.280080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
December | 0.00 | 0.255644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.00 | 0.360909E+12 | 0.00 | 235005.39 | 0.00 | 0.00 | 4695050.14 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.209975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.00 | 0.387288E+11 | 0.00 | 235005.39 | 0.00 | 0.00 | 4695050.14 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4931403.65 | 0.163714E+11 | 21291193.74 | 0.00 | 0.614854E+10 | 0.00 | 0.00 | 70922.68 | 0.54 |
February | 0.00 | 0.164449E+11 | 20002293.15 | 0.00 | 0.453827E+10 | 0.00 | 0.00 | 105334.20 | 0.54 |
March | 0.00 | 0.209043E+11 | 17101368.33 | 0.00 | 0.487670E+10 | 0.00 | 0.00 | 80803.26 | 0.54 |
April | 0.00 | 0.270719E+11 | 11739762.27 | 0.00 | 0.487519E+10 | 0.00 | 0.00 | 35303.11 | 0.54 |
May | 0.00 | 0.341904E+11 | 15410008.44 | 0.00 | 0.453351E+10 | 0.00 | 0.00 | 64050.83 | 0.54 |
June | 0.00 | 0.337993E+11 | 8578171.84 | 0.00 | 0.355833E+10 | 0.00 | 0.00 | 16007.47 | 0.54 |
July | 0.00 | 0.245617E+11 | 15183265.09 | 0.00 | 0.409071E+10 | 0.00 | 0.00 | 79866.32 | 0.54 |
August | 0.00 | 0.286588E+11 | 22990756.53 | 0.00 | 0.710216E+10 | 0.00 | 0.00 | 101750.91 | 0.54 |
September | 0.00 | 0.259670E+11 | 13782275.19 | 0.00 | 0.732253E+10 | 0.00 | 0.00 | 103173.53 | 0.54 |
October | 0.00 | 0.239367E+11 | 32752774.40 | 0.00 | 0.828884E+10 | 0.00 | 0.00 | 242855.64 | 0.54 |
November | 0.00 | 0.199856E+11 | 23334066.66 | 0.00 | 0.800662E+10 | 0.00 | 0.00 | 75676.92 | 0.54 |
December | 0.00 | 0.182189E+11 | 25280688.38 | 0.00 | 0.732705E+10 | 0.00 | 0.00 | 80688.61 | 0.54 |
Annual Sum or Average | 4931403.65 | 0.290111E+12 | 0.227447E+09 | 0.00 | 0.706684E+11 | 0.00 | 0.00 | 1056433.48 | 0.54 |
Minimum of Months | 0.00 | 0.163714E+11 | 8578171.84 | 0.00 | 0.355833E+10 | 0.00 | 0.00 | 16007.47 | 0.54 |
Maximum of Months | 4931403.65 | 0.341904E+11 | 32752774.40 | 0.00 | 0.828884E+10 | 0.00 | 0.00 | 242855.64 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 363597.47 | 0.150404E+10 | 59893.71 | 0.00 | 0.157889E+09 | 0.00 | 0.00 | 749.92 | 0.48 |
February | 0.00 | 0.143431E+10 | 0.00 | 0.00 | 0.114287E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.184449E+10 | 0.00 | 0.00 | 57633016.40 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.00 | 0.229657E+10 | 0.00 | 0.00 | 59792768.86 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.275374E+10 | 75484.67 | 0.00 | 0.102480E+09 | 0.00 | 0.00 | 1910.89 | 0.48 |
June | 0.00 | 0.266095E+10 | 0.00 | 0.00 | 94094435.62 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.200865E+10 | 218477.32 | 0.00 | 0.104820E+09 | 0.00 | 0.00 | 2618.52 | 0.48 |
August | 0.00 | 0.252416E+10 | 174237.40 | 0.00 | 0.114063E+09 | 0.00 | 0.00 | 2478.43 | 0.48 |
September | 0.00 | 0.234009E+10 | 140345.51 | 0.00 | 0.115263E+09 | 0.00 | 0.00 | 1016.86 | 0.48 |
October | 0.00 | 0.225618E+10 | 147030.64 | 0.00 | 0.122127E+09 | 0.00 | 0.00 | 774.11 | 0.48 |
November | 0.00 | 0.191537E+10 | 0.00 | 0.00 | 0.150255E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.00 | 0.169089E+10 | 92059.56 | 0.00 | 0.194422E+09 | 0.00 | 0.00 | 1753.63 | 0.48 |
Annual Sum or Average | 363597.47 | 0.252294E+11 | 907528.82 | 0.00 | 0.138713E+10 | 0.00 | 0.00 | 11302.35 | 0.48 |
Minimum of Months | 0.00 | 0.143431E+10 | 0.00 | 0.00 | 57633016.40 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 363597.47 | 0.275374E+10 | 218477.32 | 0.00 | 0.194422E+09 | 0.00 | 0.00 | 2618.52 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 363554.86 | 0.148561E+10 | 60056.98 | 0.00 | 0.176123E+09 | 0.00 | 0.00 | 579.54 | 0.48 |
February | 0.00 | 0.142464E+10 | 64343.02 | 0.00 | 0.123711E+09 | 0.00 | 0.00 | 166.39 | 0.48 |
March | 0.00 | 0.183834E+10 | 0.00 | 0.00 | 63563553.60 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.00 | 0.229791E+10 | 0.00 | 0.00 | 58181744.03 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.276058E+10 | 75469.53 | 0.00 | 95296810.24 | 0.00 | 0.00 | 1916.96 | 0.48 |
June | 0.00 | 0.267014E+10 | 0.00 | 0.00 | 84585062.63 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.201738E+10 | 218826.34 | 0.00 | 95849238.51 | 0.00 | 0.00 | 2243.60 | 0.48 |
August | 0.00 | 0.253102E+10 | 110101.83 | 0.00 | 0.106958E+09 | 0.00 | 0.00 | 2571.32 | 0.48 |
September | 0.00 | 0.233662E+10 | 226447.98 | 0.00 | 0.118359E+09 | 0.00 | 0.00 | 1419.61 | 0.48 |
October | 0.00 | 0.224232E+10 | 145912.70 | 0.00 | 0.135703E+09 | 0.00 | 0.00 | 1874.74 | 0.48 |
November | 0.00 | 0.189180E+10 | 0.00 | 0.00 | 0.173580E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.00 | 0.167010E+10 | 92560.55 | 0.00 | 0.214983E+09 | 0.00 | 0.00 | 1241.64 | 0.48 |
Annual Sum or Average | 363554.86 | 0.251665E+11 | 993718.93 | 0.00 | 0.144689E+10 | 0.00 | 0.00 | 12013.81 | 0.48 |
Minimum of Months | 0.00 | 0.142464E+10 | 0.00 | 0.00 | 58181744.03 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 363554.86 | 0.276058E+10 | 226447.98 | 0.00 | 0.214983E+09 | 0.00 | 0.00 | 2571.32 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 32141000.56 | 0.585403E+09 | 0.00 | 0.00 | 0.211987E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
February | 1329150.01 | 0.273676E+10 | 0.00 | 0.00 | 0.171201E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
March | 0.00 | 0.133510E+10 | 0.00 | 0.00 | 0.232228E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.186830E+10 | 0.00 | 0.00 | 0.292735E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.755849E+10 | 0.00 | 0.00 | 0.308267E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.161404E+11 | 0.00 | 0.00 | 0.211169E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.280207E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.324351E+09 | 0.00 | 0.00 | 0.358287E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.334345E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.324510E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.429280E+09 | 0.00 | 0.00 | 0.274228E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 6963682.86 | 0.873906E+09 | 0.00 | 0.00 | 0.251548E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 40433833.43 | 0.318520E+11 | 0.00 | 0.00 | 0.325071E+12 | 0.00 | 0.00 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.171201E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 32141000.56 | 0.161404E+11 | 0.00 | 0.00 | 0.358287E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 90899.37 | 0.374770E+09 | 82006.91 | 0.00 | 40643063.83 | 0.00 | 0.00 | 2613.41 | 0.48 |
February | 0.00 | 0.356510E+09 | 119455.26 | 0.00 | 30517265.88 | 0.00 | 0.00 | 1989.73 | 0.48 |
March | 0.00 | 0.454597E+09 | 419537.63 | 0.00 | 20509583.99 | 0.00 | 0.00 | 5589.78 | 0.48 |
April | 0.00 | 0.565884E+09 | 474860.72 | 0.00 | 22727352.94 | 0.00 | 0.00 | 4857.05 | 0.48 |
May | 0.00 | 0.681073E+09 | 404628.87 | 0.00 | 32590107.08 | 0.00 | 0.00 | 5099.42 | 0.48 |
June | 0.00 | 0.656159E+09 | 306620.83 | 0.00 | 32292097.23 | 0.00 | 0.00 | 3998.32 | 0.48 |
July | 0.00 | 0.494898E+09 | 570181.72 | 0.00 | 32943257.54 | 0.00 | 0.00 | 12265.81 | 0.48 |
August | 0.00 | 0.620870E+09 | 691628.15 | 0.00 | 38026860.90 | 0.00 | 0.00 | 10471.61 | 0.48 |
September | 0.00 | 0.578555E+09 | 623269.45 | 0.00 | 34687299.81 | 0.00 | 0.00 | 7935.33 | 0.48 |
October | 0.00 | 0.557603E+09 | 710584.71 | 0.00 | 36289814.58 | 0.00 | 0.00 | 10052.67 | 0.48 |
November | 0.00 | 0.476298E+09 | 212400.84 | 0.00 | 39892643.47 | 0.00 | 0.00 | 2052.77 | 0.48 |
December | 0.00 | 0.422195E+09 | 61697.96 | 0.00 | 49093139.41 | 0.00 | 0.00 | 1172.16 | 0.48 |
Annual Sum or Average | 90899.37 | 0.623941E+10 | 4676873.05 | 0.00 | 0.410212E+09 | 0.00 | 0.00 | 68098.04 | 0.48 |
Minimum of Months | 0.00 | 0.356510E+09 | 61697.96 | 0.00 | 20509583.99 | 0.00 | 0.00 | 1172.16 | 0.48 |
Maximum of Months | 90899.37 | 0.681073E+09 | 710584.71 | 0.00 | 49093139.41 | 0.00 | 0.00 | 12265.81 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 90888.72 | 0.369939E+09 | 188711.28 | 0.00 | 45316164.79 | 0.00 | 0.00 | 5888.10 | 0.48 |
February | 0.00 | 0.353130E+09 | 148574.24 | 0.00 | 33821471.45 | 0.00 | 0.00 | 3125.60 | 0.48 |
March | 0.00 | 0.452142E+09 | 514464.86 | 0.00 | 22811630.67 | 0.00 | 0.00 | 7867.12 | 0.48 |
April | 0.00 | 0.566414E+09 | 453645.11 | 0.00 | 22150231.40 | 0.00 | 0.00 | 4340.65 | 0.48 |
May | 0.00 | 0.682740E+09 | 337645.29 | 0.00 | 30907480.72 | 0.00 | 0.00 | 4456.73 | 0.48 |
June | 0.00 | 0.659764E+09 | 255196.57 | 0.00 | 28659838.50 | 0.00 | 0.00 | 2365.39 | 0.48 |
July | 0.00 | 0.497899E+09 | 554650.88 | 0.00 | 29898572.16 | 0.00 | 0.00 | 9272.71 | 0.48 |
August | 0.00 | 0.622251E+09 | 650193.89 | 0.00 | 36611383.26 | 0.00 | 0.00 | 8771.56 | 0.48 |
September | 0.00 | 0.577610E+09 | 698388.84 | 0.00 | 35484431.74 | 0.00 | 0.00 | 8863.48 | 0.48 |
October | 0.00 | 0.553341E+09 | 738885.90 | 0.00 | 40450704.52 | 0.00 | 0.00 | 12679.41 | 0.48 |
November | 0.00 | 0.470270E+09 | 560394.39 | 0.00 | 45506775.47 | 0.00 | 0.00 | 7674.35 | 0.48 |
December | 0.00 | 0.417177E+09 | 251828.63 | 0.00 | 53861788.95 | 0.00 | 0.00 | 4536.31 | 0.48 |
Annual Sum or Average | 90888.72 | 0.622268E+10 | 5352579.88 | 0.00 | 0.425480E+09 | 0.00 | 0.00 | 79841.39 | 0.48 |
Minimum of Months | 0.00 | 0.353130E+09 | 148574.24 | 0.00 | 22150231.40 | 0.00 | 0.00 | 2365.39 | 0.48 |
Maximum of Months | 90888.72 | 0.682740E+09 | 738885.90 | 0.00 | 53861788.95 | 0.00 | 0.00 | 12679.41 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 583982.01 | 0.241761E+10 | 25905.90 | 0.00 | 0.251730E+09 | 0.00 | 0.00 | 392.30 | 0.54 |
February | 0.00 | 0.229536E+10 | 0.00 | 0.00 | 0.191867E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.289860E+10 | 0.00 | 0.00 | 0.156448E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
April | 0.00 | 0.358540E+10 | 0.00 | 0.00 | 0.199203E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
May | 0.00 | 0.431214E+10 | 703497.09 | 0.00 | 0.274704E+09 | 0.00 | 0.00 | 6600.27 | 0.54 |
June | 0.00 | 0.415473E+10 | 310342.44 | 0.00 | 0.269902E+09 | 0.00 | 0.00 | 1071.69 | 0.54 |
July | 0.00 | 0.314720E+10 | 698120.86 | 0.00 | 0.246946E+09 | 0.00 | 0.00 | 12862.59 | 0.54 |
August | 0.00 | 0.392810E+10 | 500246.22 | 0.00 | 0.308978E+09 | 0.00 | 0.00 | 5902.99 | 0.54 |
September | 0.00 | 0.367971E+10 | 676275.18 | 0.00 | 0.263435E+09 | 0.00 | 0.00 | 6209.17 | 0.54 |
October | 0.00 | 0.357481E+10 | 342431.75 | 0.00 | 0.244934E+09 | 0.00 | 0.00 | 2948.49 | 0.54 |
November | 0.00 | 0.307166E+10 | 0.00 | 0.00 | 0.245981E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
December | 0.00 | 0.272876E+10 | 55131.81 | 0.00 | 0.299376E+09 | 0.00 | 0.00 | 278.83 | 0.54 |
Annual Sum or Average | 583982.01 | 0.397941E+11 | 3311951.25 | 0.00 | 0.295351E+10 | 0.00 | 0.00 | 36266.33 | 0.54 |
Minimum of Months | 0.00 | 0.229536E+10 | 0.00 | 0.00 | 0.156448E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 583982.01 | 0.431214E+10 | 703497.09 | 0.00 | 0.308978E+09 | 0.00 | 0.00 | 12862.59 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.334077E+11 | 0.00 | 1096944.17 | 0.642745E+09 | 0.00 | 46109339.60 | 0.00 | 4.31 |
February | 0.00 | 0.309122E+11 | 0.00 | 55964.69 | 0.455860E+09 | 0.00 | 2173418.37 | 0.00 | 4.34 |
March | 0.00 | 0.388906E+11 | 0.00 | 0.00 | 0.579410E+09 | 0.00 | 0.00 | 0.00 | 4.41 |
April | 0.00 | 0.504971E+11 | 0.00 | 0.00 | 0.305413E+09 | 0.00 | 0.00 | 0.00 | 4.46 |
May | 0.00 | 0.626707E+11 | 0.00 | 0.00 | 0.550702E+09 | 0.00 | 0.00 | 0.00 | 4.49 |
June | 0.00 | 0.616619E+11 | 0.00 | 0.00 | 0.133598E+09 | 0.00 | 0.00 | 0.00 | 4.51 |
July | 0.00 | 0.447230E+11 | 0.00 | 0.00 | 0.473085E+09 | 0.00 | 0.00 | 0.00 | 4.45 |
August | 0.00 | 0.565647E+11 | 0.00 | 0.00 | 0.997800E+09 | 0.00 | 0.00 | 0.00 | 4.42 |
September | 0.00 | 0.524291E+11 | 0.00 | 0.00 | 0.715880E+09 | 0.00 | 0.00 | 0.00 | 4.40 |
October | 0.00 | 0.497227E+11 | 0.00 | 0.00 | 0.103440E+10 | 0.00 | 0.00 | 0.00 | 4.36 |
November | 0.00 | 0.428740E+11 | 0.00 | 0.00 | 0.727155E+09 | 0.00 | 0.00 | 0.00 | 4.34 |
December | 0.00 | 0.397231E+11 | 0.00 | 361366.88 | 0.698747E+09 | 0.00 | 9720715.49 | 0.00 | 4.29 |
Annual Sum or Average | 0.00 | 0.564077E+12 | 0.00 | 1514275.74 | 0.731479E+10 | 0.00 | 58003473.46 | 0.00 | 4.40 |
Minimum of Months | 0.00 | 0.309122E+11 | 0.00 | 0.00 | 0.133598E+09 | 0.00 | 0.00 | 0.00 | 4.29 |
Maximum of Months | 0.00 | 0.626707E+11 | 0.00 | 1096944.17 | 0.103440E+10 | 0.00 | 46109339.60 | 0.00 | 4.51 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.354335E+11 | 0.00 | 1163202.74 | 0.409136E+09 | 0.00 | 48437248.39 | 0.00 | 4.54 |
February | 0.00 | 0.327862E+11 | 0.00 | 58751.84 | 0.225328E+09 | 0.00 | 2281385.87 | 0.00 | 4.57 |
March | 0.00 | 0.412748E+11 | 0.00 | 0.00 | 0.269063E+09 | 0.00 | 0.00 | 0.00 | 4.64 |
April | 0.00 | 0.534477E+11 | 0.00 | 0.00 | 87201059.35 | 0.00 | 0.00 | 0.00 | 4.70 |
May | 0.00 | 0.664456E+11 | 0.00 | 0.00 | 0.210640E+09 | 0.00 | 0.00 | 0.00 | 4.73 |
June | 0.00 | 0.651292E+11 | 0.00 | 0.00 | 7473778.40 | 0.00 | 0.00 | 0.00 | 4.75 |
July | 0.00 | 0.476270E+11 | 0.00 | 0.00 | 95389352.71 | 0.00 | 0.00 | 0.00 | 4.70 |
August | 0.00 | 0.603691E+11 | 0.00 | 0.00 | 0.389006E+09 | 0.00 | 0.00 | 0.00 | 4.67 |
September | 0.00 | 0.557940E+11 | 0.00 | 0.00 | 0.282668E+09 | 0.00 | 0.00 | 0.00 | 4.64 |
October | 0.00 | 0.529082E+11 | 0.00 | 0.00 | 0.648817E+09 | 0.00 | 0.00 | 0.00 | 4.61 |
November | 0.00 | 0.455916E+11 | 0.00 | 0.00 | 0.370912E+09 | 0.00 | 0.00 | 0.00 | 4.57 |
December | 0.00 | 0.421425E+11 | 0.00 | 390108.47 | 0.435171E+09 | 0.00 | 10174823.75 | 0.00 | 4.52 |
Annual Sum or Average | 0.00 | 0.598949E+12 | 0.00 | 1612063.05 | 0.343081E+10 | 0.00 | 60893458.01 | 0.00 | 4.64 |
Minimum of Months | 0.00 | 0.327862E+11 | 0.00 | 0.00 | 7473778.40 | 0.00 | 0.00 | 0.00 | 4.52 |
Maximum of Months | 0.00 | 0.664456E+11 | 0.00 | 1163202.74 | 0.648817E+09 | 0.00 | 48437248.39 | 0.00 | 4.75 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.439933E+11 | 0.00 | 796721.49 | 0.00 | 0.00 | 45463741.36 | 0.00 | 17.49 |
February | 0.00 | 0.413269E+11 | 0.00 | 35605.55 | 0.00 | 0.00 | 1844091.03 | 0.00 | 17.58 |
March | 0.00 | 0.509331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 |
April | 0.00 | 0.652432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 |
May | 0.00 | 0.795657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 |
June | 0.00 | 0.775309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 |
July | 0.00 | 0.576359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 |
August | 0.00 | 0.742038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 |
September | 0.00 | 0.689954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 |
October | 0.00 | 0.659712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 |
November | 0.00 | 0.568724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 |
December | 0.00 | 0.515339E+11 | 0.00 | 266142.21 | 0.00 | 0.00 | 9650230.46 | 0.00 | 17.47 |
Annual Sum or Average | 0.00 | 0.733806E+12 | 0.00 | 1098469.24 | 0.00 | 0.00 | 56958062.85 | 0.00 | 17.53 |
Minimum of Months | 0.00 | 0.413269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 |
Maximum of Months | 0.00 | 0.795657E+11 | 0.00 | 796721.49 | 0.00 | 0.00 | 45463741.36 | 0.00 | 17.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16649597.94 | 0.620905E+10 | 0.00 | 0.00 | 0.522871E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
February | 0.00 | 0.715710E+10 | 0.00 | 4036.67 | 0.335456E+10 | 0.00 | 684486.18 | 0.00 | 1.16 |
March | 0.00 | 0.863771E+10 | 0.00 | 0.00 | 0.437816E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
April | 0.00 | 0.117431E+11 | 0.00 | 0.00 | 0.489106E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
May | 0.00 | 0.138796E+11 | 0.00 | 0.00 | 0.676512E+10 | 0.00 | 0.00 | 0.00 | 1.17 |
June | 0.00 | 0.154705E+11 | 0.00 | 0.00 | 0.483268E+10 | 0.00 | 0.00 | 0.00 | 1.17 |
July | 0.00 | 0.740011E+10 | 0.00 | 0.00 | 0.717249E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
August | 0.00 | 0.747186E+10 | 0.00 | 0.00 | 0.113555E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 0.00 | 0.829481E+10 | 0.00 | 0.00 | 0.913755E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
October | 0.00 | 0.661708E+10 | 0.00 | 0.00 | 0.102190E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
November | 0.00 | 0.728790E+10 | 0.00 | 0.00 | 0.725939E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
December | 3607308.98 | 0.640562E+10 | 0.00 | 0.00 | 0.720943E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
Annual Sum or Average | 20256906.92 | 0.106574E+12 | 0.00 | 4036.67 | 0.818036E+11 | 0.00 | 684486.18 | 0.00 | 1.16 |
Minimum of Months | 0.00 | 0.620905E+10 | 0.00 | 0.00 | 0.335456E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
Maximum of Months | 16649597.94 | 0.154705E+11 | 0.00 | 4036.67 | 0.113555E+11 | 0.00 | 684486.18 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:34
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.209151E+12 | -0.120934E+11 | -0.157380E+12 | -0.689851E+12 | 0.165701E+13 |
February | 0.209802E+12 | -0.120357E+11 | -0.157772E+12 | -0.689701E+12 | 0.153531E+13 |
March | 0.291308E+12 | -0.151611E+11 | -0.196197E+12 | -0.878977E+12 | 0.176139E+13 |
April | 0.291270E+12 | -0.191287E+11 | -0.254068E+12 | -0.111492E+13 | 0.189603E+13 |
May | 0.304461E+12 | -0.230921E+11 | -0.310461E+12 | -0.135095E+13 | 0.212057E+13 |
June | 0.319033E+12 | -0.222878E+11 | -0.303576E+12 | -0.129864E+13 | 0.208154E+13 |
July | 0.262885E+12 | -0.169101E+11 | -0.221011E+12 | -0.978445E+12 | 0.181155E+13 |
August | 0.328193E+12 | -0.213075E+11 | -0.287274E+12 | -0.123739E+13 | 0.198657E+13 |
September | 0.248869E+12 | -0.198133E+11 | -0.265182E+12 | -0.114700E+13 | 0.189187E+13 |
October | 0.270525E+12 | -0.190968E+11 | -0.253516E+12 | -0.110500E+13 | 0.187734E+13 |
November | 0.210291E+12 | -0.160499E+11 | -0.213052E+12 | -0.923932E+12 | 0.175351E+13 |
December | 0.195260E+12 | -0.132913E+11 | -0.175322E+12 | -0.755556E+12 | 0.173457E+13 |
Annual Sum or Average | 0.314105E+13 | -0.210268E+12 | -0.279481E+13 | -0.121704E+14 | 0.221072E+14 |
Minimum of Months | 0.195260E+12 | -0.230921E+11 | -0.310461E+12 | -0.135095E+13 | 0.153531E+13 |
Maximum of Months | 0.328193E+12 | -0.120357E+11 | -0.157380E+12 | -0.689701E+12 | 0.212057E+13 |