Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:42:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10870.15 | 958.12 | 958.12 |
Net Site Energy | 10870.15 | 958.12 | 958.12 |
Total Source Energy | 23294.31 | 2053.21 | 2053.21 |
Net Source Energy | 23294.31 | 2053.21 | 2053.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 431.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1041.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 866.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 619.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 94.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 181.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5526.20 | 5343.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 431.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1041.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 866.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 619.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 94.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 181.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 431.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1041.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 866.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 619.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 94.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 181.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 162.70 | 313.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.86 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 487.09 | 471.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 162.70 | 313.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.86 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 487.09 | 471.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5526.196 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5526.196 | 100.00 |
Total On-Site and Utility Electric Sources | 5526.196 | 100.00 |
Total Electricity End Uses | 5526.196 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 96.76 | 4.76 |
Air to Air Heat Recovery for Heating | 1937.88 | 95.24 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2034.64 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 518.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7779.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.3255 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.5208 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.7005 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 11.5174 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.6875 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 9.7951 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.3255 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.5208 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.7005 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 11.5174 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.6875 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 9.7951 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 13.0243 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 5.0165 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:19 | 06-DEC-19:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:49 |
Heating | 0.00 | 184134.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 142947.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32090.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41610.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3667.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3975.54 | 248294.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1828.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 410749.35 | 520048.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 184134.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 142947.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1786.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 41610.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3667.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3975.54 | 248294.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 467.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3297.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2745.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 830.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2058.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1960.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 300.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3386.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17501.46 | 5792.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 41.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 290.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 50.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 298.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1542.62 | 510.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 41.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 290.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 50.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 298.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1542.62 | 510.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.32 | 0.454449 | 0.430000 | 1.43 | 1.00 | 0.500000 | 0.000838 | 0.000054 | 1.43 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.436186 | 0.117171 | 0.430000 | 0.187560 | 0.430000 | 0.500000 | 0.003252 | 0.000030 | 0.187560 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.291660 | 0.202920 | 0.430000 | 0.125414 | 0.541121 | 0.500000 | 0.001878 | 0.000012 | 0.125414 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.228328 | 0.548130 | 0.430000 | 0.098181 | 1.00 | 0.500000 | 0.000695 | 0.000017 | 0.098181 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.152016 | 0.474994 | 0.430000 | 0.065367 | 1.00 | 0.500000 | 0.000802 | 0.000012 | 0.065367 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.97 | 0.059423 | 0.430000 | 1.71 | 0.430000 | 0.500000 | 0.025443 | 0.000083 | 1.71 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.82 | 0.079274 | 0.430000 | 0.780615 | 0.430000 | 0.500000 | 0.004806 | 0.000088 | 0.780615 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.73 | 0.174042 | 0.430000 | 2.46 | 0.464112 | 0.500000 | 0.002189 | 0.000227 | 2.46 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.89 | 0.627754 | 0.430000 | 0.813008 | 1.00 | 0.500000 | 0.000607 | 0.000112 | 0.813008 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.71 | 0.093116 | 0.430000 | 1.17 | 0.430000 | 0.500000 | 0.004092 | 0.000095 | 1.17 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.84 | 0.088875 | 0.430000 | 1.22 | 0.430000 | 0.500000 | 0.004287 | 0.000098 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.77 | 0.051027 | 0.430000 | 1.19 | 0.430000 | 0.500000 | 0.013430 | 0.000062 | 1.19 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.973294 | 0.322656 | 0.430000 | 0.418516 | 0.860416 | 0.500000 | 0.001181 | 0.000069 | 0.418516 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6195.94 | 0.000054 | 129.21 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3443.12 | 0.000030 | 86.58 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1400.99 | 0.000012 | 31.83 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1985.39 | 0.000017 | 51.37 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1378.33 | 0.000012 | 36.15 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9492.03 | 0.000083 | 200.86 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10035.24 | 0.000088 | 233.24 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 25955.73 | 0.000227 | 584.83 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5806.73 | 0.000051 | 165.93 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5806.46 | 0.000051 | 165.93 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33394.00 | 0.000292 | 954.25 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33404.80 | 0.000292 | 954.56 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5806.73 | 0.000051 | 165.93 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5806.46 | 0.000051 | 165.93 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12809.86 | 0.000112 | 310.03 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1761.49 | 0.000015 | 50.33 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1762.56 | 0.000015 | 50.36 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8443.70 | 0.000074 | 241.28 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10871.61 | 0.000095 | 241.09 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11241.57 | 0.000098 | 248.91 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7069.40 | 0.000062 | 150.26 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7900.95 | 0.000069 | 200.25 |
VAV WITH REHEAT HEATING COIL | 198208.60 | 0.001734 | 3316.93 |
FLR_3_DOAS HEATING COIL | 15066.37 | 0.000132 | 252.13 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.52 | 0.000051 | 0.000498 |
ROOM_2_FLR_3 FAN COIL | 1.51 | 0.000051 | 0.000493 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.31 | 0.000292 | 0.002701 |
ROOM_4_MULT19_FLR_3 FAN COIL | 8.21 | 0.000292 | 0.002793 |
ROOM_5_FLR_3 FAN COIL | 1.35 | 0.000051 | 0.000440 |
ROOM_6_FLR_3 FAN COIL | 1.33 | 0.000051 | 0.000436 |
ROOM_1_FLR_6 FAN COIL | 0.403200 | 0.000015 | 0.000132 |
ROOM_2_FLR_6 FAN COIL | 0.398322 | 0.000015 | 0.000130 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.65 | 0.000074 | 0.000549 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.52 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.51 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.31 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.21 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.35 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.33 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.403200 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.398322 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.65 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000498 | 1.52 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000493 | 1.51 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008462 | 12.80 | 0.008462 | 0.002701 | 8.31 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008667 | 12.80 | 0.008500 | 0.002793 | 8.21 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008521 | 12.80 | 0.008500 | 0.000440 | 1.35 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008521 | 12.80 | 0.008500 | 0.000436 | 1.33 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000132 | 0.403200 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000130 | 0.398322 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008580 | 12.80 | 0.008500 | 0.000549 | 1.65 | |
VAV WITH REHEAT COOLING COIL | 28.79 | 6.70 | 0.007913 | 10.58 | 0.007913 | 0.017723 | 26.99 | 496199.66 |
FLR_3_DOAS COOLING COIL | 35.10 | 6.70 | 0.005699 | 11.74 | 0.005699 | 0.001722 | 2.05 | 48199.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.57 | 11.67 | 27.14 | 11.67 | 26.99 | 26.99 | 0.300000 | 0.432392 | 26.99 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 26.99 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 26.99 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.017723 | 0.000027 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001734 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001722 | 0.000277 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000132 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.027616 | 4508.93 | |
HEATSYS1 PUMP | 0.003719 | 1119.85 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003719 | 0.446221 |
COOLSYS1 | 0.027616 | 3.31 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 425048.03 | 425048.03 | 0.003719 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.027616 | 3121.68 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.027616 | 773188.44 | 773899.61 | 88.22 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.325 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.705 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.521 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.901 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.700 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.390 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 11.517 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.897 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 20432.332 | 10.325 | 191.855 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20432.332 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.656 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.656 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.385 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.385 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 742.517 | 4.521 | 279.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 742.517 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 729.693 | 7.700 | 357.693 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 729.693 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2175.192 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2175.192 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 12673.066 | 9.688 | 30.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12673.066 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.470 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.470 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8203 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.052 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.15703352E-14 | 0.29012323E-16 | -0.15483104E-09 | 0.40370831E-16 |
29 | 8 | 0.22592825E-07 | 0.11106548E-12 | 0.38529762E-03 | -0.25688817E-09 |
30 | 7 | -0.12465369E-01 | 0.57225352E-08 | -0.23408026E-01 | 0.14173579E-03 |
31 | 6 | 0.41143163 | 0.19878644E-05 | 0.47726710 | -0.48194459E-02 |
32 | 5 | -5.2499075 | 0.74130146E-04 | -4.4810026 | 0.63919688E-01 |
33 | 4 | 33.265337 | 0.60571720E-03 | 21.595652 | -0.42560793 |
34 | 3 | -111.78466 | 0.13187857E-02 | -55.931065 | 1.5232626 |
35 | 2 | 197.68466 | 0.74115454E-03 | 78.156489 | -2.9095067 |
36 | 1 | -171.36898 | 0.79055603E-04 | -55.336681 | 2.7491709 |
37 | 0 | 57.057407 | 0.44959794E-06 | 15.545184 | |
38 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
39 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
40 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
41 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
42 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
43 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
44 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
45 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
46 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
47 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
48 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
49 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
50 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
51 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
52 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
53 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
54 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
55 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
56 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
57 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
58 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
59 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
60 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
61 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
62 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
63 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
64 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
65 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
66 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
67 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
68 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
69 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
70 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
71 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
72 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
73 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
74 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
75 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
76 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
77 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 37 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.42_SHGC_0.4 | 38 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1551 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.3468E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1730 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.1188E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1153 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3863E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.6285E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5376E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1759 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.9363E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1967 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.8587E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1277 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.5108E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1970E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.1022E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7661E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.1659E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8940E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6324E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7808E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1136E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.5560E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6155E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7661E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.1659E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8940E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6324E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7808E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1136E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.5560E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6155E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 37559.67784 | 37559.67784 | 3.31802 | 3.31802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 28.35000 | 5.68899E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4937.25304 | 4937.25304 | 0.43619 | 0.43619 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2629.32317 | 2629.32317 | 0.13702 | 0.13702 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3301.19480 | 3301.19480 | 0.29166 | 0.29166 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 856.86069 | 856.86069 | 4.46536E-002 | 9.17347E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2584.97940 | 2584.97940 | 0.22833 | 0.22833 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.86000 | 5.69436E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1559.51927 | 1559.51927 | 8.12706E-002 | 8.12706E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1721.00750 | 1721.00750 | 0.15202 | 0.15202 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 32.31000 | 5.69506E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1094.74501 | 1094.74501 | 5.70504E-002 | 5.77652E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44954.33056 | 44954.33056 | 3.97110 | 3.97110 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2086.24141 | 2086.24141 | 0.10872 | 0.10872 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20529.92686 | 20529.92686 | 1.81538 | 1.81538 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6647.88768 | 6647.88768 | 0.34643 | 0.67639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64808.37096 | 64808.37096 | 5.72757 | 5.72757 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15269.61777 | 15269.61777 | 0.79574 | 1.89399 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12788.91904 | 12788.91904 | 1.52230 | 1.52230 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5806.85111 | 5806.85111 | 0.30438 | 0.30438 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12655.52154 | 12655.52154 | 1.50642 | 1.50642 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5806.57817 | 5806.57817 | 0.30436 | 0.30436 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 69776.15416 | 69776.15416 | 8.30538 | 8.30538 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33394.34038 | 33394.34038 | 1.75049 | 1.75049 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 68974.15431 | 68974.15431 | 8.21060 | 8.21060 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33405.13882 | 33405.13882 | 1.75106 | 1.75106 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11305.60865 | 11305.60865 | 1.34574 | 1.34574 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.58750 | 5.69088E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5806.85111 | 5806.85111 | 0.30438 | 0.30438 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 11206.32063 | 11206.32063 | 1.33392 | 1.33392 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5806.57817 | 5806.57817 | 0.30436 | 0.30436 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21403.43718 | 21403.43718 | 1.89072 | 1.89072 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9281.43070 | 9281.43070 | 0.48369 | 0.48369 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3387.30591 | 3387.30591 | 0.40320 | 0.40320 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1761.52563 | 1761.52563 | 9.23344E-002 | 9.23344E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3346.32756 | 3346.32756 | 0.39832 | 0.39832 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1762.59169 | 1762.59169 | 9.23902E-002 | 9.23902E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13878.80428 | 13878.80428 | 1.65209 | 1.65209 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8443.83457 | 8443.83457 | 0.44261 | 0.44261 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30683.14450 | 30683.14450 | 2.71408 | 2.71408 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5806.22459 | 5806.22459 | 0.30258 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32147.64944 | 32147.64944 | 2.84357 | 2.84357 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5934.51481 | 5934.51481 | 0.30926 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31323.31246 | 31323.31246 | 2.77469 | 2.77469 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1904.40171 | 1904.40171 | 9.92303E-002 | 0.36735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11018.09108 | 11018.09108 | 0.97329 | 0.97329 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 35.10000 | 5.69938E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6084.29673 | 6084.29673 | 0.31707 | 0.31707 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 429453.71 | 26.98651 | 26.98651 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 182272.48 | 7.44503 | 7.44503 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45524.16 | 23.29382 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 50219.47 | 5.34637 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.31802 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.45445 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.42675 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.38379E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.42048E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.42675 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6195.94483 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.42048E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 129.20575 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.43619 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11717 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18756 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25166E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01219E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18756 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3443.11742 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01219E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 86.58062 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29166 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20292 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12541 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54112 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87758E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22565E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12541 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1400.98906 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22565E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.83145 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22833 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54813 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.81809E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.95090E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73690E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.81809E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1985.38628 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73690E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 51.36742 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15202 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.47499 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.53667E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.02115E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20583E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.53667E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1378.33254 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20583E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.14981 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.97110 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.94228E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.70757 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54429E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.30404E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.70757 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9492.03224 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.30404E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 200.85905 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.81538 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.92740E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78062 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.80612E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.77927E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78062 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10035.24285 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.77927E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 233.23573 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.72757 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17404 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.46286 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46411 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18913E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.27072E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.46286 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25955.72597 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27072E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 584.83333 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.52230 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.52230 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.07998E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.97668E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51921E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.97668E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.52230 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5806.72813 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.07998E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 165.93298 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.50642 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.50642 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.07974E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.92501E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51939E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.92501E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.50642 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5806.45519 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.07974E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 165.92518 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.30538 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.30538 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.92145E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.70075E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80726 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.46215E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.46215E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.70075E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.30538 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33394.00038 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.92145E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 954.25284 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.21060 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.21060 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.92240E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.79343E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80631 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66743E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.79343E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.21060 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33404.79870 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.92240E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 954.56140 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.34574 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.34574 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.07998E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.40155E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52093E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.40155E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.34574 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5806.72813 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.07998E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 165.93298 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.33392 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.33392 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.07974E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.36292E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52096E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.36292E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.33392 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5806.45519 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.07974E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 165.92518 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.89072 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.62775 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81301 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.06925E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12066E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81301 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12809.85538 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12066E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 310.02904 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.40320 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.40320 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.54103E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.31776E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51816E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.31776E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.40320 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1761.48948 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54103E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 50.33420 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.39832 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.39832 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.54196E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.30188E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51835E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.30188E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.39832 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1762.55552 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54196E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 50.36466 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.65209 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.65209 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.38691E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.49048E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80657 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57961E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.49048E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.65209 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8443.69602 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.38691E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 241.27536 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.71408 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.31155E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16705 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.09169E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.51096E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16705 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10871.60876 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.51096E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 241.09405 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.84357 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.88751E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22274 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.28691E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.83462E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22274 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11241.57372 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.83462E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 248.90899 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.77469 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.10270E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19312 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34297E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.18462E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19312 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7069.39699 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.18462E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 150.26332 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97329 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32266 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41852 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86042 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18082E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.91209E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41852 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7900.94776 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.91209E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 200.25104 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.56831 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66875 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 27.13662 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66875 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.98651 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.98651 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43239 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.98651 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.98651 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.79006 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.58104 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.91328E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.91328E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 496199.66189 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.77231E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 26.98651 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 198208.60095 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73402E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3316.92527 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 26.98651 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.77231E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.68683E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.73402E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.10000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.73601 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 48199.92810 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.72159E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15066.37152 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31807E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 252.12846 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.72159E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.76599E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.31807E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.76165E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4508.93049 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.71851E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.44622 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.71851E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1119.85059 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 425048.03300 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 425048.03000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.71851E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.76165E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.31398 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.76165E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3121.68466 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.76165E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 773188.43663 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 773899.61000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 88.22456 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6228.49 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3458.84 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1407.88 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1994.18 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1384.38 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9541.46 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10083.94 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 26084.09 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6256.93 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6256.64 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 35982.91 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 35994.54 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6256.93 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6256.64 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12869.72 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1898.01 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1899.16 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9098.10 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10925.94 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11297.81 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7106.11 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7936.86 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 144841.56 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11009.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 25902.10 | 18962.68 | 6939.43 | 0.73 | 5732.99 | 58.15 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 25632.72 | 18765.13 | 6867.59 | 0.73 | 5672.99 | 57.54 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 141336.75 | 103542.46 | 37794.29 | 0.73 | 32483.65 | 329.47 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 143370.70 | 103435.80 | 39934.91 | 0.72 | 30129.86 | 305.59 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 22904.93 | 16765.51 | 6139.42 | 0.73 | 5066.21 | 51.38 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 22703.88 | 16618.31 | 6085.58 | 0.73 | 5021.69 | 50.93 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6859.20 | 5022.10 | 1837.10 | 0.73 | 1518.79 | 15.40 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 6776.45 | 4961.41 | 1815.04 | 0.73 | 1500.36 | 15.22 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28412.59 | 20674.29 | 7738.30 | 0.73 | 6147.94 | 62.36 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 733946.38 | 435166.83 | 298779.55 | 0.59 | 154168.43 | 1563.66 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 47472.21 | 29284.36 | 18187.85 | 0.62 | 4618.55 | 46.84 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.3367391093E-002 | 4.9080884658E-002 | Pass | Pass | 5.8630972694E-002 | 0.1321838008 | Pass | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.9278401573E-002 | 0.1414575312 | Fail | Pass | 8.8638417444E-002 | 0.1531548616 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7387585419E-002 | 8.2815569992E-002 | Pass | Pass | 8.4330499128E-002 | 0.2068171687 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.2121680714E-002 | 3.1722319000E-002 | Pass | Pass | 0.1011421270 | 0.2613279825 | Fail | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1671652974E-002 | 3.2580661779E-002 | Pass | Pass | 0.1080257998 | 0.2891234426 | Fail | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1636884258 | 0.3644969850 | Fail | Pass | 5.4028450994E-002 | 0.1253432102 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.8912324404E-002 | 0.1929673558 | Fail | Pass | 6.3490038765E-002 | 0.1499264531 | Pass | Fail |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3173132207E-002 | 0.1003997288 | Pass | Pass | 6.3745544602E-002 | 0.1613459480 | Pass | Fail |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1203687211E-002 | 0.2138608837 | Pass | Pass | 0.2197732915 | 0.6352866065 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.6474606712E-002 | 0.2191529164 | Pass | Pass | 0.3311126082 | 1.1054295134 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.6720822497E-002 | 3.4433287607E-002 | Pass | Pass | 3.5353831972E-002 | 5.9880468343E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.3414590550E-002 | 5.2613226512E-002 | Pass | Pass | 0.3708317311 | 1.4547644674 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.1047324251E-002 | 0.2953048766 | Pass | Pass | 0.5089546115 | 3.8467735428 | Pass | Fail |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.6446493127E-002 | 0.1482906799 | Pass | Pass | 1.7581181599 | 19.0609158313 | Pass | Fail |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3367089571E-002 | 3.1561644764E-002 | Pass | Pass | 9.6700835893E-002 | 0.2373179325 | Fail | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1036751923E-002 | 0.2059114618 | Pass | Pass | 0.2247975596 | 0.6029876048 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.7837371554E-002 | 0.2622752911 | Pass | Pass | 0.2201050768 | 0.9505206151 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.0700702260E-002 | 0.3462105207 | Pass | Pass | 0.2664080193 | 1.0136429391 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.8973029523E-002 | 0.1648355094 | Fail | Pass | 6.1828478936E-002 | 0.1403952549 | Pass | Fail |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.7935102689E-002 | 0.1743498563 | Fail | Pass | 6.4260475551E-002 | 0.1546824797 | Pass | Fail |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1415233718 | 0.3797447328 | Fail | Pass | 5.7656493142E-002 | 0.1071524810 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.0879851514E-002 | 5.7269894608E-002 | Pass | Pass | 9.9991698328E-002 | 0.2434814339 | Fail | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5187.39 | 107.84 | 1221.41 | 5938.27 | 4651.22 | 17106.14 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.387 | 0.401 | 0.442 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.387 | 0.401 | 0.442 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.387 | 0.401 | 0.442 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.387 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.387 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.387 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.387 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.387 | 0.401 | 0.442 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.387 | 0.401 | 0.442 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.387 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.387 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.387 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.387 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.387 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.387 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.387 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.387 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.387 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.387 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.387 | 0.401 | 0.442 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.387 | 0.401 | 0.442 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.387 | 0.401 | 0.442 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.387 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.387 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.387 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.387 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 432.95 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.387 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.3255 | 1978.83 | 20432.33 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 188.94 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.5625 | 67.07 | 909.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.76 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.5625 | 77.67 | 1053.39 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 10.14 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.5208 | 164.24 | 742.52 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.17 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.7005 | 94.76 | 729.69 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 4.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 11.5174 | 188.86 | 2175.19 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.30 | 0.0000 | Y | 16.05 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.6875 | 1308.19 | 12673.07 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.51 | 0.0000 | Y | 98.74 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 9.7951 | 1863.81 | 18256.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.45 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 9.7951 | 1864.32 | 18261.31 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.49 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.23 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.18 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 9.7951 | 220.77 | 2162.52 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 15.45 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.22 | 0.0000 | Y | 35.29 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.22 | 0.0000 | Y | 35.29 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 13.0243 | 103.30 | 1345.47 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 9.4981 | 11345.29 | 107758.18 | 494.43 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.71 | 83.71 | 262.25 | |
Exterior Lighting Total | 16690.39 | 262.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 425048.03 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 773899.61 | 2.96 | 774035.64 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13933.65 | 25902.10 | 18962.68 | 6939.43 | 0.73 | - | 5732.99 | 58.15 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13788.96 | 25632.72 | 18765.13 | 6867.59 | 0.73 | - | 5672.99 | 57.54 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75615.30 | 141336.75 | 103542.46 | 37794.29 | 0.73 | - | 32483.65 | 329.47 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 78209.96 | 143370.70 | 103435.80 | 39934.91 | 0.72 | - | 30129.86 | 305.59 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12323.39 | 22904.93 | 16765.51 | 6139.42 | 0.73 | - | 5066.21 | 51.38 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12215.25 | 22703.88 | 16618.31 | 6085.58 | 0.73 | - | 5021.69 | 50.93 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3689.43 | 6859.20 | 5022.10 | 1837.10 | 0.73 | - | 1518.79 | 15.40 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3644.99 | 6776.45 | 4961.41 | 1815.04 | 0.73 | - | 1500.36 | 15.22 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15372.17 | 28412.59 | 20674.29 | 7738.30 | 0.73 | - | 6147.94 | 62.36 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 496199.66 | 733946.38 | 435166.83 | 298779.55 | 0.59 | - | 154168.43 | 1563.66 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 48199.93 | 47472.21 | 29284.36 | 18187.85 | 0.62 | - | 4618.55 | 46.84 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6195.94 | 6228.49 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3443.12 | 3458.84 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1400.99 | 1407.88 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1985.39 | 1994.18 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1378.33 | 1384.38 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9492.03 | 9541.46 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10035.24 | 10083.94 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25955.73 | 26084.09 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5806.73 | 6256.93 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5806.46 | 6256.64 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33394.00 | 35982.91 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33404.80 | 35994.54 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5806.73 | 6256.93 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5806.46 | 6256.64 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12809.86 | 12869.72 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1761.49 | 1898.01 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1762.56 | 1899.16 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8443.70 | 9098.10 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10871.61 | 10925.94 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11241.57 | 11297.81 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7069.40 | 7106.11 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7900.95 | 7936.86 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 198208.60 | 144841.56 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15066.37 | 11009.80 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.52 | 1071.14 | 703.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.51 | 1059.97 | 703.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.31 | 5843.97 | 703.64 | 1.00 | 0.94 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.21 | 5777.27 | 703.64 | 1.00 | 0.94 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.35 | 946.91 | 703.64 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.33 | 938.59 | 703.64 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.40 | 283.71 | 703.64 | 1.00 | 1.53 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.40 | 280.27 | 703.64 | 1.00 | 1.54 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.65 | 1162.47 | 703.64 | 1.00 | 1.09 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.99 | 60467.01 | 2240.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.027616 | 4508.93 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003719 | 1119.85 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027616 | 3121.68 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 37559.68 | 37559.68 | 18.98 | 3.318 | 3.318 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 24.00 | 24.00 | 0.00914 | 28.35 | 0.00569 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4937.25 | 4937.25 | 73.61 | 0.436 | 0.436 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00893 | 34.76 | 0.00570 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3301.19 | 3301.19 | 42.50 | 0.292 | 0.292 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00932 | 33.21 | 0.00570 | 0.092 | 0.00 |
MECH_FLR_1 | 2584.98 | 2584.98 | 15.74 | 0.228 | 0.228 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00862 | 31.86 | 0.00569 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1721.01 | 1721.01 | 18.16 | 0.152 | 0.152 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00867 | 32.31 | 0.00570 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44954.33 | 44954.33 | 576.05 | 3.971 | 3.971 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00853 | 34.97 | 0.00570 | 0.000 | 0.00 |
CAFE_FLR_1 | 20529.93 | 20529.93 | 108.70 | 1.815 | 1.815 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01002 | 34.76 | 0.00570 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64808.37 | 64808.37 | 49.54 | 5.728 | 5.728 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00993 | 34.88 | 0.00570 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12788.92 | 12788.92 | 327.74 | 1.522 | 1.522 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12655.52 | 12655.52 | 324.36 | 1.506 | 1.506 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 33.21 | 0.00570 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 69776.15 | 69776.15 | 2845.24 | 8.305 | 8.305 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00846 | 34.88 | 0.00570 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 68974.15 | 68974.15 | 2811.77 | 8.211 | 8.211 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00867 | 35.10 | 0.00570 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11305.61 | 11305.61 | 289.72 | 1.346 | 1.346 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00852 | 29.59 | 0.00569 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 11206.32 | 11206.32 | 287.21 | 1.334 | 1.334 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00852 | 28.82 | 0.00569 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21403.44 | 21403.44 | 54.96 | 1.891 | 1.891 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00934 | 35.10 | 0.00570 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3387.31 | 3387.31 | 86.80 | 0.403 | 0.403 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3346.33 | 3346.33 | 85.76 | 0.398 | 0.398 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 33.21 | 0.00570 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13878.80 | 13878.80 | 565.78 | 1.652 | 1.652 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00858 | 34.99 | 0.00570 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30683.14 | 30683.14 | 92.51 | 2.714 | 2.714 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01032 | 35.10 | 0.00570 | 1.188 | 0.00 |
DINING_FLR_6 | 32147.65 | 32147.65 | 96.93 | 2.844 | 2.844 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01024 | 35.10 | 0.00570 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31323.31 | 31323.31 | 303.21 | 2.775 | 2.775 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01004 | 33.89 | 0.00570 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11018.09 | 11018.09 | 26.73 | 0.973 | 0.973 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00892 | 35.10 | 0.00570 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.76 | 0.00234 | -7.90 | 0.00234 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2629.32 | 2629.32 | 39.20 | 0.137 | 0.137 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00759 | -7.90 | 0.00234 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 856.86 | 856.86 | 11.03 | 0.045 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00752 | -7.90 | 0.00234 | 0.092 | 0.00 |
MECH_FLR_1 | 1559.52 | 1559.52 | 9.50 | 0.081 | 0.081 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00739 | -7.90 | 0.00234 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1094.75 | 1094.75 | 11.55 | 0.057 | 0.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00749 | -7.90 | 0.00234 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2086.24 | 2086.24 | 26.73 | 0.109 | 0.109 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00738 | -7.90 | 0.00234 | 0.000 | 0.00 |
CAFE_FLR_1 | 6647.89 | 6647.89 | 35.20 | 0.346 | 0.676 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15269.62 | 15269.62 | 11.67 | 0.796 | 1.894 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00755 | -7.90 | 0.00234 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5806.85 | 5806.85 | 148.81 | 0.304 | 0.304 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5806.58 | 5806.58 | 148.82 | 0.304 | 0.304 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33394.34 | 33394.34 | 1361.71 | 1.750 | 1.750 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33405.14 | 33405.14 | 1361.78 | 1.751 | 1.751 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5806.85 | 5806.85 | 148.81 | 0.304 | 0.304 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5806.58 | 5806.58 | 148.82 | 0.304 | 0.304 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -7.90 | 0.00234 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9281.43 | 9281.43 | 23.83 | 0.484 | 0.484 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -7.90 | 0.00234 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1761.53 | 1761.53 | 45.14 | 0.092 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00764 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1762.59 | 1762.59 | 45.17 | 0.092 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00764 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8443.83 | 8443.83 | 344.22 | 0.443 | 0.443 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | -7.90 | 0.00234 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5806.22 | 5806.22 | 17.51 | 0.303 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 1.188 | 0.00 |
DINING_FLR_6 | 5934.51 | 5934.51 | 17.89 | 0.309 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1904.40 | 1904.40 | 18.43 | 0.099 | 0.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00665 | -7.90 | 0.00234 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6084.30 | 6084.30 | 14.76 | 0.317 | 0.317 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00777 | -7.90 | 0.00234 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 26.99 | 26.99 | 7.45 | 7.45 | 26.9865 | 11.6687 | 26.9865 | 0.4324 | 0.3000 |
FLR_3_DOAS | 23.29 | 2.05 | 5.35 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6195.945 | 6195.945 | 1.426748 | 0.00005420 | 129.206 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6195.94 | 6195.94 | 1.426748 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 6230.77 | 6230.77 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3443.117 | 3443.117 | 0.187560 | 0.00003012 | 86.581 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3443.12 | 3443.12 | 0.187560 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00758701 | 40.3687 | 2629.32 | 0.00 | 3460.83 | 3460.83 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1400.989 | 1400.989 | 0.125414 | 0.00001226 | 31.831 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1400.99 | 1400.99 | 0.125414 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00751726 | 40.0011 | 856.86 | 0.00 | 1408.54 | 1408.54 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1985.386 | 1985.386 | 0.098181 | 0.00001737 | 51.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1985.39 | 1985.39 | 0.098181 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00738865 | 39.3250 | 1559.52 | 0.00 | 1995.39 | 1995.39 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1378.333 | 1378.333 | 0.065367 | 0.00001206 | 36.150 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1378.33 | 1378.33 | 0.065367 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00748773 | 39.8460 | 1094.75 | 0.00 | 1385.25 | 1385.25 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9492.032 | 9492.032 | 1.707573 | 0.00008304 | 200.859 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 9492.03 | 9492.03 | 1.707573 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00737748 | 39.2673 | 2086.24 | 0.00 | 9545.11 | 9545.11 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10035.243 | 10035.243 | 0.780615 | 0.00008779 | 233.236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10035.24 | 10035.24 | 0.780615 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763557 | 40.6237 | 6647.89 | 0.00 | 10088.89 | 10088.89 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 25955.726 | 25955.726 | 2.462856 | 0.00022707 | 584.833 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 25955.73 | 25955.73 | 2.462856 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00755362 | 40.1924 | 15269.62 | 0.00 | 26095.96 | 26095.96 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13933.649 | -999.000 | 1.522298 | 0.00049767 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 13933.65 | 13883.06 | 1.522298 | 21.81 | 13.66 | 0.00851921 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00851921 | 44.9529 | 12788.92 | 0.00 | 17238.91 | 16234.55 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5806.728 | 5806.728 | 0.304379 | 0.00005080 | 165.933 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5806.73 | 5806.73 | 0.304379 | 21.11 | 12.60 | 0.00756979 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00756979 | 40.0047 | 5806.85 | 0.00 | 6259.79 | 6259.79 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13788.963 | -999.000 | 1.506420 | 0.00049250 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 13788.96 | 13738.45 | 1.506420 | 21.81 | 13.66 | 0.00851939 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00851939 | 44.9538 | 12655.52 | 0.00 | 17059.81 | 16065.23 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5806.455 | 5806.455 | 0.304365 | 0.00005080 | 165.925 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5806.46 | 5806.46 | 0.304365 | 21.11 | 12.60 | 0.00756980 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00756980 | 40.0048 | 5806.58 | 0.00 | 6259.50 | 6259.50 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 75615.303 | -999.000 | 8.305381 | 0.00270075 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 75615.30 | 75615.30 | 8.305381 | 21.81 | 13.61 | 0.00846215 | 12.80 | 10.30 | 0.00846215 | 34.88 | 0.00569904 | 15.70 | 0.0000 | 21.11 | 0.00846215 | 44.6551 | 69776.15 | 0.00 | 93699.37 | 88982.02 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 33394.000 | 33394.000 | 1.750492 | 0.00029215 | 954.253 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 33394.00 | 33394.00 | 1.750492 | 21.11 | 12.63 | 0.00760104 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00760104 | 40.1670 | 33394.34 | 0.00 | 35999.74 | 35999.74 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 78209.964 | -999.000 | 8.210597 | 0.00279343 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 78209.96 | 75802.60 | 8.210597 | 21.81 | 13.78 | 0.00866743 | 12.80 | 10.33 | 0.00850000 | 35.10 | 0.00569938 | 15.77 | 0.0000 | 21.11 | 0.00866743 | 45.7254 | 68974.15 | 0.00 | 96335.40 | 87666.99 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33404.799 | 33404.799 | 1.751058 | 0.00029224 | 954.561 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 33404.80 | 33404.80 | 1.751058 | 21.11 | 12.63 | 0.00760106 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00760106 | 40.1671 | 33405.14 | 0.00 | 36011.38 | 36011.38 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12323.390 | -999.000 | 1.345735 | 0.00044015 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 12323.39 | 12274.65 | 1.345735 | 21.81 | 13.66 | 0.00852093 | 12.80 | 10.33 | 0.00850000 | 29.59 | 0.00569088 | 13.95 | 0.0000 | 21.11 | 0.00852093 | 44.9618 | 11305.61 | 0.00 | 15245.84 | 14351.77 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5806.728 | 5806.728 | 0.304379 | 0.00005080 | 165.933 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5806.73 | 5806.73 | 0.304379 | 21.11 | 12.60 | 0.00756979 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00756979 | 40.0047 | 5806.85 | 0.00 | 6259.79 | 6259.79 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12215.252 | -999.000 | 1.333917 | 0.00043629 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 12215.25 | 12166.88 | 1.333917 | 21.81 | 13.66 | 0.00852096 | 12.80 | 10.33 | 0.00850000 | 28.82 | 0.00568971 | 13.69 | 0.0000 | 21.11 | 0.00852096 | 44.9620 | 11206.32 | 0.00 | 15112.05 | 14225.74 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5806.455 | 5806.455 | 0.304365 | 0.00005080 | 165.925 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5806.46 | 5806.46 | 0.304365 | 21.11 | 12.60 | 0.00756980 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00756980 | 40.0048 | 5806.58 | 0.00 | 6259.50 | 6259.50 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12809.855 | 12809.855 | 0.813008 | 0.00011207 | 310.029 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12809.86 | 12809.86 | 0.813008 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00766647 | 40.7852 | 9281.43 | 0.00 | 12876.62 | 12876.62 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3689.433 | -999.000 | 0.403200 | 0.00013178 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3689.43 | 3676.77 | 0.403200 | 21.81 | 13.66 | 0.00851816 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00851816 | 44.9474 | 3387.31 | 0.00 | 4564.77 | 4299.89 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1761.489 | 1761.489 | 0.092334 | 0.00001541 | 50.334 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1761.49 | 1761.49 | 0.092334 | 21.11 | 12.66 | 0.00764057 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00764057 | 40.3742 | 1761.53 | 0.00 | 1898.93 | 1898.93 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3644.994 | -999.000 | 0.398322 | 0.00013019 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3644.99 | 3632.35 | 0.398322 | 21.81 | 13.66 | 0.00851835 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00851835 | 44.9484 | 3346.33 | 0.00 | 4509.76 | 4247.88 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1762.556 | 1762.556 | 0.092390 | 0.00001542 | 50.365 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1762.56 | 1762.56 | 0.092390 | 21.11 | 12.66 | 0.00764080 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00764080 | 40.3754 | 1762.59 | 0.00 | 1900.08 | 1900.08 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15372.171 | -999.000 | 1.652086 | 0.00054905 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 15372.17 | 15143.50 | 1.652086 | 21.81 | 13.71 | 0.00857961 | 12.80 | 10.33 | 0.00850000 | 34.99 | 0.00569921 | 15.74 | 0.0000 | 21.11 | 0.00857961 | 45.2680 | 13878.80 | 0.00 | 18982.64 | 17626.19 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8443.696 | 8443.696 | 0.442608 | 0.00007387 | 241.275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8443.70 | 8443.70 | 0.442608 | 21.11 | 12.67 | 0.00765386 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00765386 | 40.4433 | 8443.83 | 0.00 | 9102.52 | 9102.52 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10871.609 | 10871.609 | 1.167054 | 0.00009511 | 241.094 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10871.61 | 10871.61 | 1.167054 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00772776 | 41.1076 | 5806.22 | 0.00 | 10930.71 | 10930.71 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11241.574 | 11241.574 | 1.222736 | 0.00009835 | 248.909 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11241.57 | 11241.57 | 1.222736 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00773336 | 41.1371 | 5934.51 | 0.00 | 11302.73 | 11302.73 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7069.397 | 7069.397 | 1.193118 | 0.00006185 | 150.263 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7069.40 | 7069.40 | 1.193118 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00665298 | 35.4569 | 1904.40 | 0.00 | 7108.87 | 7108.87 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7900.948 | 7900.948 | 0.418516 | 0.00006912 | 200.251 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7900.95 | 7900.95 | 0.418516 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00777055 | 41.3323 | 6084.30 | 0.00 | 7941.52 | 7941.52 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 496199.662 | -999.000 | 26.986506 | 0.01772310 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 496199.66 | 496199.66 | 26.986506 | 28.79 | 15.49 | 0.00791328 | 10.58 | 8.88 | 0.00791328 | 35.10 | 0.00569938 | 15.77 | 43.2122 | 23.99 | 0.00955385 | 42.2490 | 305277.35 | 0.00 | 580129.03 | 533504.06 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 198208.601 | 198208.601 | 8.095952 | 0.00173402 | 3316.925 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 198208.60 | 198208.60 | 8.095952 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 144.0406 | 21.30 | 0.00674897 | 35.2922 | 58883.62 | 0.00 | 175070.45 | 175070.45 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 48199.93 | 48199.93 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 11.74 | 7.07 | 0.00569938 | 35.10 | 0.00569938 | 15.77 | 99.9965 | 21.11 | 0.00856467 | 45.1898 | 195690.77 | 0.00 | 48236.96 | 48236.96 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15066.37 | 15066.37 | 0.615395 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 333.3216 | 21.11 | 0.00760129 | 40.1683 | 101994.29 | 0.00 | 13307.58 | 13307.58 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6195.945 | 6195.945 | 1.426748 | 0.00005420 | 129.206 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.4289 | 1.457705 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6195.94 | 6195.94 | 1.0000 | 1.41306366 | 1.426748 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05419930 | 60.00 | 32.22 | 27.78 | 0.000 | 6195.94 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 6230.77 | 6230.77 | 1.41306366 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3443.117 | 3443.117 | 0.187560 | 0.00003012 | 86.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 0.7941 | 0.810054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3443.12 | 3443.12 | 1.0000 | 0.18576117 | 0.187560 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.03011882 | 60.00 | 32.22 | 27.78 | 0.000 | 3443.12 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00758701 | 21.00 | 0.00758701 | 40.3687 | 2629.32 | 0.00 | 3460.83 | 3460.83 | 0.18576117 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.87 | 19.62 | 0.00800000 | 55565.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1400.989 | 1400.989 | 0.125414 | 0.00001226 | 31.831 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 0.3231 | 0.329607 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1400.99 | 1400.99 | 1.0000 | 0.12421081 | 0.125414 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01225521 | 60.00 | 32.22 | 27.78 | 0.000 | 1400.99 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00751726 | 21.00 | 0.00751726 | 40.0011 | 856.86 | 0.00 | 1408.54 | 1408.54 | 0.12421081 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.72 | 17.27 | 0.00800000 | 48274.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1985.386 | 1985.386 | 0.098181 | 0.00001737 | 51.367 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 0.4579 | 0.467097 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1985.39 | 1985.39 | 1.0000 | 0.09723924 | 0.098181 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01736725 | 60.00 | 32.22 | 27.78 | 0.000 | 1985.39 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00738865 | 21.00 | 0.00738865 | 39.3250 | 1559.52 | 0.00 | 1995.39 | 1995.39 | 0.09723924 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.72 | 20.19 | 0.00800000 | 57455.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1378.333 | 1378.333 | 0.065367 | 0.00001206 | 36.150 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 0.3179 | 0.324277 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1378.33 | 1378.33 | 1.0000 | 0.06473977 | 0.065367 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01205702 | 60.00 | 32.22 | 27.78 | 0.000 | 1378.33 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00748773 | 21.00 | 0.00748773 | 39.8460 | 1094.75 | 0.00 | 1385.25 | 1385.25 | 0.06473977 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.58 | 20.46 | 0.00800000 | 58331.9 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9492.032 | 9492.032 | 1.707573 | 0.00008304 | 200.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 2.1891 | 2.233167 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 9492.03 | 9492.03 | 1.0000 | 1.69119564 | 1.707573 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.08303197 | 60.00 | 32.22 | 27.78 | 0.000 | 9492.03 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00737748 | 21.00 | 0.00737748 | 39.2673 | 2086.24 | 0.00 | 9545.11 | 9545.11 | 1.69119564 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.13 | 15.27 | 0.00800000 | 42578.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10035.243 | 10035.243 | 0.780615 | 0.00008779 | 233.236 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 2.3144 | 2.360967 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10035.24 | 10035.24 | 1.0000 | 0.77312813 | 0.780615 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.08778373 | 60.00 | 32.22 | 27.78 | 0.000 | 10035.24 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00763557 | 21.00 | 0.00763557 | 40.6237 | 6647.89 | 0.00 | 10088.89 | 10088.89 | 0.77312813 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.40 | 17.84 | 0.00800000 | 49984.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25955.726 | 25955.726 | 2.462856 | 0.00022707 | 584.833 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 5.9861 | 6.106539 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 25955.73 | 25955.73 | 1.0000 | 2.43923480 | 2.462856 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.22704885 | 60.00 | 32.22 | 27.78 | 0.000 | 25955.73 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00755362 | 21.00 | 0.00755362 | 40.1924 | 15269.62 | 0.00 | 26095.96 | 26095.96 | 2.43923480 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.09 | 17.05 | 0.00800000 | 47633.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13933.649 | -999.000 | 1.522298 | 0.00049767 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6768 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.522298 | 1.50769779 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 1.8021 | 1.802069 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 13933.65 | 13883.06 | 1.0000 | 1.50769779 | 1.522298 | 21.81 | 13.66 | 0.00851921 | 43563.9 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.49761760 | 6.70 | 13.37 | 6.67 | 0.000 | 13933.65 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00851921 | 21.11 | 0.00851921 | 44.9529 | 12788.92 | 0.00 | 17238.91 | 16234.55 | 1.50769779 | 21.81 | 15.62 | 0.00851921 | 43563.9 | 11.26 | 11.20 | 0.00825506 | 32129.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5806.728 | 5806.728 | 0.304379 | 0.00005080 | 165.933 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.522298 | 1.50769779 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.3392 | 1.366135 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5806.73 | 5806.73 | 1.0000 | 0.30145961 | 0.304379 | 21.11 | 12.60 | 0.00756979 | 40441.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05079461 | 60.00 | 32.22 | 27.78 | 0.000 | 5806.73 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756979 | 21.11 | 0.00756979 | 40.0047 | 5806.85 | 0.00 | 6259.79 | 6259.79 | 0.30145961 | 16.60 | 12.73 | 0.00756979 | 35845.5 | 36.98 | 19.95 | 0.00756979 | 56610.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13788.963 | -999.000 | 1.506420 | 0.00049250 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6771 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.506420 | 1.49197144 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 1.7834 | 1.783356 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 13788.96 | 13738.45 | 1.0000 | 1.49197144 | 1.506420 | 21.81 | 13.66 | 0.00851939 | 43564.3 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.49245038 | 6.70 | 13.37 | 6.67 | 0.000 | 13788.96 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00851939 | 21.11 | 0.00851939 | 44.9538 | 12655.52 | 0.00 | 17059.81 | 16065.23 | 1.49197144 | 21.81 | 15.62 | 0.00851939 | 43564.3 | 11.26 | 11.20 | 0.00825505 | 32129.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5806.455 | 5806.455 | 0.304365 | 0.00005080 | 165.925 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.506420 | 1.49197144 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.3391 | 1.366070 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5806.46 | 5806.46 | 1.0000 | 0.30144544 | 0.304365 | 21.11 | 12.60 | 0.00756980 | 40441.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05079222 | 60.00 | 32.22 | 27.78 | 0.000 | 5806.46 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756980 | 21.11 | 0.00756980 | 40.0048 | 5806.58 | 0.00 | 6259.50 | 6259.50 | 0.30144544 | 16.60 | 12.73 | 0.00756980 | 35845.5 | 36.98 | 19.95 | 0.00756980 | 56610.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75615.303 | -999.000 | 8.305381 | 0.00270075 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5707 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.305381 | 8.22572309 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 9.7797 | 9.779491 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 75615.30 | 75615.30 | 1.0000 | 8.22572309 | 8.305381 | 21.81 | 13.61 | 0.00846215 | 43419.2 | 12.80 | 10.30 | 0.00846215 | 34226.6 | 2.70047749 | 6.70 | 13.37 | 6.67 | 0.000 | 75615.30 | 34.88 | 0.00569904 | 15.70 | 0.00000000 | 0.0000 | 21.11 | 0.00846215 | 21.11 | 0.00846215 | 44.6551 | 69776.15 | 0.00 | 93699.37 | 88982.02 | 8.22572309 | 21.81 | 15.57 | 0.00846215 | 43419.2 | 11.21 | 11.16 | 0.00823473 | 32028.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33394.000 | 33394.000 | 1.750492 | 0.00029215 | 954.253 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.305381 | 8.22572309 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 7.7015 | 7.856524 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 33394.00 | 33394.00 | 1.0000 | 1.73370269 | 1.750492 | 21.11 | 12.63 | 0.00760104 | 40520.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.29211548 | 60.00 | 32.22 | 27.78 | 0.000 | 33394.00 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00760104 | 21.11 | 0.00760104 | 40.1670 | 33394.34 | 0.00 | 35999.74 | 35999.74 | 1.73370269 | 16.60 | 12.76 | 0.00760104 | 35924.6 | 36.98 | 19.97 | 0.00760104 | 56689.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 78209.964 | -999.000 | 8.210597 | 0.00279343 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9523 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.210597 | 8.13184812 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 10.1153 | 10.115064 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 78209.96 | 75802.60 | 1.0000 | 8.13184812 | 8.210597 | 21.81 | 13.78 | 0.00866743 | 43939.9 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 2.79314156 | 6.70 | 13.37 | 6.67 | 0.000 | 78209.96 | 35.10 | 0.00569938 | 15.77 | 0.00000000 | 0.0000 | 21.11 | 0.00866743 | 21.11 | 0.00866743 | 45.7254 | 68974.15 | 0.00 | 96335.40 | 87666.99 | 8.13184812 | 21.81 | 15.75 | 0.00866743 | 43939.9 | 11.25 | 11.19 | 0.00824473 | 32093.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33404.799 | 33404.799 | 1.751058 | 0.00029224 | 954.561 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.210597 | 8.13184812 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 7.7040 | 7.859064 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 33404.80 | 33404.80 | 1.0000 | 1.73426330 | 1.751058 | 21.11 | 12.63 | 0.00760106 | 40520.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.29220994 | 60.00 | 32.22 | 27.78 | 0.000 | 33404.80 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00760106 | 21.11 | 0.00760106 | 40.1671 | 33405.14 | 0.00 | 36011.38 | 36011.38 | 1.73426330 | 16.60 | 12.76 | 0.00760106 | 35924.7 | 36.98 | 19.97 | 0.00760106 | 56689.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12323.390 | -999.000 | 1.345735 | 0.00044015 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6800 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.345735 | 1.33282802 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 1.5938 | 1.593811 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 12323.39 | 12274.65 | 1.0000 | 1.33282802 | 1.345735 | 21.81 | 13.66 | 0.00852093 | 43568.2 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.44010981 | 6.70 | 13.37 | 6.67 | 0.000 | 12323.39 | 29.59 | 0.00569088 | 13.95 | 0.00000000 | 0.0000 | 21.11 | 0.00852093 | 21.11 | 0.00852093 | 44.9618 | 11305.61 | 0.00 | 15245.84 | 14351.77 | 1.33282802 | 21.81 | 15.62 | 0.00852093 | 43568.2 | 11.26 | 11.20 | 0.00825494 | 32129.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5806.728 | 5806.728 | 0.304379 | 0.00005080 | 165.933 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.345735 | 1.33282802 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.3392 | 1.366135 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5806.73 | 5806.73 | 1.0000 | 0.30145961 | 0.304379 | 21.11 | 12.60 | 0.00756979 | 40441.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05079461 | 60.00 | 32.22 | 27.78 | 0.000 | 5806.73 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756979 | 21.11 | 0.00756979 | 40.0047 | 5806.85 | 0.00 | 6259.79 | 6259.79 | 0.30145961 | 16.60 | 12.73 | 0.00756979 | 35845.5 | 36.98 | 19.95 | 0.00756979 | 56610.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12215.252 | -999.000 | 1.333917 | 0.00043629 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6800 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.333917 | 1.32112281 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 1.5799 | 1.579825 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 12215.25 | 12166.88 | 1.0000 | 1.32112281 | 1.333917 | 21.81 | 13.66 | 0.00852096 | 43568.3 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.43624783 | 6.70 | 13.37 | 6.67 | 0.000 | 12215.25 | 28.82 | 0.00568971 | 13.69 | 0.00000000 | 0.0000 | 21.11 | 0.00852096 | 21.11 | 0.00852096 | 44.9620 | 11206.32 | 0.00 | 15112.05 | 14225.74 | 1.32112281 | 21.81 | 15.62 | 0.00852096 | 43568.3 | 11.26 | 11.20 | 0.00825494 | 32129.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5806.455 | 5806.455 | 0.304365 | 0.00005080 | 165.925 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.333917 | 1.32112281 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.3391 | 1.366070 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5806.46 | 5806.46 | 1.0000 | 0.30144544 | 0.304365 | 21.11 | 12.60 | 0.00756980 | 40441.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05079222 | 60.00 | 32.22 | 27.78 | 0.000 | 5806.46 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00756980 | 21.11 | 0.00756980 | 40.0048 | 5806.58 | 0.00 | 6259.50 | 6259.50 | 0.30144544 | 16.60 | 12.73 | 0.00756980 | 35845.5 | 36.98 | 19.95 | 0.00756980 | 56610.5 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12809.855 | 12809.855 | 0.813008 | 0.00011207 | 310.029 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 2.9543 | 3.013743 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12809.86 | 12809.86 | 1.0000 | 0.80521050 | 0.813008 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.11205477 | 60.00 | 32.22 | 27.78 | 0.000 | 12809.86 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00766647 | 21.00 | 0.00766647 | 40.7852 | 9281.43 | 0.00 | 12876.62 | 12876.62 | 0.80521050 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.28 | 18.79 | 0.00800000 | 52926.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3689.433 | -999.000 | 0.403200 | 0.00013178 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6748 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.403200 | 0.39933263 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 0.4772 | 0.477162 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3689.43 | 3676.77 | 1.0000 | 0.39933263 | 0.403200 | 21.81 | 13.66 | 0.00851816 | 43561.2 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.13176209 | 6.70 | 13.37 | 6.67 | 0.000 | 3689.43 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00851816 | 21.11 | 0.00851816 | 44.9474 | 3387.31 | 0.00 | 4564.77 | 4299.89 | 0.39933263 | 21.81 | 15.62 | 0.00851816 | 43561.2 | 11.26 | 11.20 | 0.00825513 | 32130.2 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1761.489 | 1761.489 | 0.092334 | 0.00001541 | 50.334 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.403200 | 0.39933263 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 0.4062 | 0.414421 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1761.49 | 1761.49 | 1.0000 | 0.09144877 | 0.092334 | 21.11 | 12.66 | 0.00764057 | 40620.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01540871 | 60.00 | 32.22 | 27.78 | 0.000 | 1761.49 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00764057 | 21.11 | 0.00764057 | 40.3742 | 1761.53 | 0.00 | 1898.93 | 1898.93 | 0.09144877 | 16.60 | 12.80 | 0.00764057 | 36024.7 | 36.98 | 20.00 | 0.00764057 | 56789.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3644.994 | -999.000 | 0.398322 | 0.00013019 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6752 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.398322 | 0.39450166 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 0.4714 | 0.471415 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3644.99 | 3632.35 | 1.0000 | 0.39450166 | 0.398322 | 21.81 | 13.66 | 0.00851835 | 43561.7 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.13017503 | 6.70 | 13.37 | 6.67 | 0.000 | 3644.99 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00851835 | 21.11 | 0.00851835 | 44.9484 | 3346.33 | 0.00 | 4509.76 | 4247.88 | 0.39450166 | 21.81 | 15.62 | 0.00851835 | 43561.7 | 11.26 | 11.20 | 0.00825512 | 32130.1 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1762.556 | 1762.556 | 0.092390 | 0.00001542 | 50.365 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.398322 | 0.39450166 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 0.4065 | 0.414672 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1762.56 | 1762.56 | 1.0000 | 0.09150411 | 0.092390 | 21.11 | 12.66 | 0.00764080 | 40621.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01541803 | 60.00 | 32.22 | 27.78 | 0.000 | 1762.56 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00764080 | 21.11 | 0.00764080 | 40.3754 | 1762.59 | 0.00 | 1900.08 | 1900.08 | 0.09150411 | 16.60 | 12.80 | 0.00764080 | 36025.3 | 36.98 | 20.00 | 0.00764080 | 56790.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15372.171 | -999.000 | 1.652086 | 0.00054905 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7891 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.652086 | 1.63624105 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 1.9882 | 1.988116 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 15372.17 | 15143.50 | 1.0000 | 1.63624105 | 1.652086 | 21.81 | 13.71 | 0.00857961 | 43717.0 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.54899209 | 6.70 | 13.37 | 6.67 | 0.000 | 15372.17 | 34.99 | 0.00569921 | 15.74 | 0.00000000 | 0.0000 | 21.11 | 0.00857961 | 21.11 | 0.00857961 | 45.2680 | 13878.80 | 0.00 | 18982.64 | 17626.19 | 1.63624105 | 21.81 | 15.67 | 0.00857961 | 43717.0 | 11.25 | 11.20 | 0.00825088 | 32115.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8443.696 | 8443.696 | 0.442608 | 0.00007387 | 241.275 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.652086 | 1.63624105 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.9473 | 1.986527 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8443.70 | 8443.70 | 1.0000 | 0.43836249 | 0.442608 | 21.11 | 12.67 | 0.00765386 | 40654.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.07386160 | 60.00 | 32.22 | 27.78 | 0.000 | 8443.70 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00765386 | 21.11 | 0.00765386 | 40.4433 | 8443.83 | 0.00 | 9102.52 | 9102.52 | 0.43836249 | 16.60 | 12.81 | 0.00765386 | 36058.4 | 36.98 | 20.01 | 0.00765386 | 56823.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10871.609 | 10871.609 | 1.167054 | 0.00009511 | 241.094 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 2.5073 | 2.557737 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10871.61 | 10871.61 | 1.0000 | 1.15586090 | 1.167054 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09509987 | 60.00 | 32.22 | 27.78 | 0.000 | 10871.61 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00772776 | 21.00 | 0.00772776 | 41.1076 | 5806.22 | 0.00 | 10930.71 | 10930.71 | 1.15586090 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.87 | 16.62 | 0.00800000 | 46391.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11241.574 | 11241.574 | 1.222736 | 0.00009835 | 248.909 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 2.5926 | 2.644777 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11241.57 | 11241.57 | 1.0000 | 1.21100910 | 1.222736 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09833616 | 60.00 | 32.22 | 27.78 | 0.000 | 11241.57 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773336 | 21.00 | 0.00773336 | 41.1371 | 5934.51 | 0.00 | 11302.73 | 11302.73 | 1.21100910 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.75 | 16.58 | 0.00800000 | 46268.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7069.397 | 7069.397 | 1.193118 | 0.00006185 | 150.263 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.6304 | 1.663200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7069.40 | 7069.40 | 1.0000 | 1.18167469 | 1.193118 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06183986 | 60.00 | 32.22 | 27.78 | 0.000 | 7069.40 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.46 | 0.00665298 | 21.00 | 0.00665298 | 35.4569 | 1904.40 | 0.00 | 7108.87 | 7108.87 | 1.18167469 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.50 | 15.41 | 0.00800000 | 42950.7 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7900.948 | 7900.948 | 0.418516 | 0.00006912 | 200.251 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 1.8222 | 1.858836 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7900.95 | 7900.95 | 1.0000 | 0.41450229 | 0.418516 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06911389 | 60.00 | 32.22 | 27.78 | 0.000 | 7900.95 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00777055 | 21.00 | 0.00777055 | 41.3323 | 6084.30 | 0.00 | 7941.52 | 7941.52 | 0.41450229 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.39 | 19.78 | 0.00800000 | 56093.9 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 496199.662 | -999.000 | 26.986506 | 0.01772310 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5504 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.986506 | 26.72767520 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 64.1758 | 64.175774 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 496199.66 | 496199.66 | 1.0000 | 26.72767520 | 26.986506 | 28.79 | 15.49 | 0.00791328 | 49143.6 | 10.58 | 8.88 | 0.00791328 | 30578.5 | 17.72129428 | 6.70 | 13.37 | 6.67 | 60467.006 | 435732.66 | 35.10 | 0.00569938 | 15.77 | 11.66146000 | 43.2122 | 23.99 | 0.00959793 | 23.99 | 0.00955385 | 42.2490 | 305277.35 | 0.00 | 580129.03 | 533504.06 | 26.72767520 | 28.79 | 17.56 | 0.00791328 | 49143.6 | 9.21 | 9.20 | 0.00722051 | 27438.4 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 198208.601 | 198208.601 | 8.095952 | 0.00173402 | 3316.925 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.986506 | 26.72767520 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 45.7121 | 46.632048 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 198208.60 | 198208.60 | 1.0000 | 8.01830256 | 8.095952 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 1.73383842 | 60.00 | 32.22 | 27.78 | 0.000 | 198208.60 | -7.90 | 0.00234317 | -7.90 | 11.66146000 | 144.0406 | 18.56 | 0.00698937 | 21.30 | 0.00674897 | 35.2922 | 58883.62 | 0.00 | 175070.45 | 175070.45 | 8.01830256 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.4349 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 27.61368230 | 13.37 | 6.70 | 6.67 | 773188.44 | 6.2339 | 6.233917 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 48199.93 | 48199.93 | 1.0000 | 2.03164284 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 49895.6 | 11.74 | 7.07 | 0.00569938 | 26171.0 | 1.72141413 | 6.70 | 13.37 | 6.67 | 2195.006 | 46004.92 | 35.10 | 0.00569938 | 15.77 | 2.05124512 | 99.9965 | 21.11 | 0.00855684 | 21.11 | 0.00856467 | 45.1898 | 195690.77 | 0.00 | 48236.96 | 48236.96 | 2.03164284 | 35.10 | 17.86 | 0.00569938 | 49895.6 | 11.72 | 8.65 | 0.00569938 | 26152.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 3.71812629 | 54.44 | 82.22 | 27.78 | 433602.29 | 3.4747 | 3.544628 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15066.37 | 15066.37 | 1.0000 | 0.60949285 | 0.615395 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 0.13179374 | 60.00 | 32.22 | 27.78 | 0.000 | 15066.37 | -7.90 | 0.00234317 | -7.90 | 2.05124512 | 333.3216 | 21.11 | 0.00759967 | 21.11 | 0.00760129 | 40.1683 | 101994.29 | 0.00 | 13307.58 | 13307.58 | 0.60949285 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 26.99 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1501.50 | 5823.50 | 506.67 |
RETAIL_1_FLR_1 | 2880.50 | 5199.17 | 525.17 |
RETAIL_2_FLR_1 | 2381.50 | 5615.00 | 590.17 |
MECH_FLR_1 | 1301.33 | 6626.00 | 270.17 |
STORAGE_FLR_1 | 1160.83 | 7082.17 | 343.50 |
LAUNDRY_FLR_1 | 8164.00 | 3748.67 | 3585.50 |
CAFE_FLR_1 | 4422.50 | 3471.83 | 1008.00 |
LOBBY_FLR_1 | 2932.17 | 3650.67 | 909.83 |
ROOM_1_FLR_3 | 1689.67 | 7398.50 | 1026.83 |
ROOM_2_FLR_3 | 2543.17 | 7656.83 | 2062.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1693.67 | 8724.50 | 1686.67 |
ROOM_5_FLR_3 | 1858.83 | 7446.00 | 1117.83 |
ROOM_6_FLR_3 | 2646.17 | 7640.83 | 2151.33 |
CORRIDOR_FLR_3 | 1497.00 | 6851.50 | 668.33 |
ROOM_1_FLR_6 | 2561.00 | 7347.83 | 1781.33 |
ROOM_2_FLR_6 | 3333.50 | 7584.83 | 2760.67 |
ROOM_3_MULT9_FLR_6 | 1071.83 | 7221.83 | 480.50 |
BANQUET_FLR_6 | 3772.33 | 2303.50 | 941.67 |
DINING_FLR_6 | 4170.00 | 1313.33 | 887.00 |
KITCHEN_FLR_6 | 8646.67 | 6425.33 | 6424.83 |
CORRIDOR_FLR_6 | 1778.50 | 6353.83 | 393.67 |
Facility | 8759.17 | 8760.00 | 7779.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 3.33 | 0.00 | 3.33 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 264.00 | 0.00 | 264.00 |
CAFE_FLR_1 | 0.00 | 11.50 | 0.00 | 11.50 |
LOBBY_FLR_1 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_1_FLR_3 | 0.00 | 4.17 | 0.00 | 4.17 |
ROOM_2_FLR_3 | 0.00 | 2.33 | 0.00 | 2.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.17 | 2.83 | 0.17 | 2.83 |
ROOM_5_FLR_3 | 0.00 | 30.00 | 0.00 | 30.00 |
ROOM_6_FLR_3 | 0.00 | 28.50 | 0.00 | 28.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 9.00 | 0.00 | 9.00 |
ROOM_2_FLR_6 | 0.00 | 5.50 | 0.00 | 5.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 17.33 | 0.00 | 17.33 |
BANQUET_FLR_6 | 0.00 | 38.67 | 0.00 | 38.67 |
DINING_FLR_6 | 0.00 | 48.50 | 0.00 | 48.50 |
KITCHEN_FLR_6 | 0.00 | 416.50 | 0.00 | 416.50 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 518.17 | 0.17 | 518.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 1.065 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.605 | 0.137 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.443 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.504 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.560 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 22.602 | 0.147 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 4.067 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.788 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.178 | 0.000 | 0.052 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.177 | 0.000 | 0.055 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.534 | 0.079 | 0.000 | 0.093 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.178 | 0.000 | 0.060 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.178 | 0.000 | 0.057 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.562 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.471 | 0.178 | 0.000 | 0.058 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.471 | 0.178 | 0.000 | 0.061 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.535 | 0.145 | 0.000 | 0.112 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.149 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.567 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 22.997 | 0.148 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 1.114 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.504 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.172 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.681 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.250 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.288 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 9.401 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 1.781 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 0.811 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.518 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.284 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.455 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.521 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 1.954 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.048 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 6.443 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.552 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 44347513.37 | 0.00 | 44347513.37 | 0.00 | 44347513.37 | 26946214.98 | 10.57 | 1.30 | 8748.13 | 0.00 |
RETAIL_1_FLR_1 | 5992597.33 | 0.00 | 5992597.33 | 315975.89 | 6308573.22 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3831730.99 | 0.00 | 3831730.99 | 121967.09 | 3953698.08 | 2892943.94 | 418.01 | 84.22 | 8257.78 | 0.00 |
MECH_FLR_1 | 2841946.38 | 0.00 | 2841946.38 | 288257.75 | 3130204.12 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1821718.39 | 0.00 | 1821718.39 | 166308.84 | 1988027.23 | 1821682.01 | 4149.33 | 431.92 | 4178.76 | 0.00 |
LAUNDRY_FLR_1 | 60355374.36 | 0.00 | 60355374.36 | 393601.23 | 60748975.60 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26227146.56 | 0.00 | 26227146.56 | 698482.59 | 26925629.14 | 21330615.53 | 2011.51 | 328.16 | 6420.33 | 0.00 |
LOBBY_FLR_1 | 79824095.45 | 0.00 | 79824095.45 | 1995724.30 | 81819819.74 | 59728886.00 | 270.93 | 68.88 | 8420.19 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 53699.29 | 2000574.90 | 183401.85 | 2183976.75 | 1946875.62 | 0.00 | 8059.47 | 700.53 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 56770.60 | 2003418.11 | 183387.86 | 2186805.97 | 1946647.51 | 0.00 | 8005.53 | 754.47 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 64377.70 | 26462264.98 | 51171.17 | 26513436.15 | 26397887.27 | 0.00 | 7937.50 | 822.50 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 60279.27 | 26465384.99 | 51185.17 | 26516570.16 | 26405105.73 | 0.00 | 7947.79 | 812.21 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 61446.65 | 2008322.27 | 183401.85 | 2191724.12 | 1946875.62 | 0.00 | 8004.82 | 755.18 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 58692.51 | 2005340.02 | 183387.86 | 2188727.88 | 1946647.51 | 0.00 | 8005.96 | 754.04 | 0.00 |
CORRIDOR_FLR_3 | 23051241.57 | 0.00 | 23051241.57 | 221769.73 | 23273011.31 | 14972100.18 | 53.99 | 11.02 | 8694.99 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 59350.83 | 546069.74 | 183439.96 | 729509.70 | 486718.90 | 0.00 | 8092.25 | 667.75 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 62955.72 | 549617.60 | 183425.97 | 733043.57 | 486661.88 | 0.00 | 8037.75 | 722.25 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 72015.17 | 3198935.58 | 93854.31 | 3292789.89 | 3126920.42 | 0.00 | 7970.40 | 789.60 | 0.00 |
BANQUET_FLR_6 | 44789430.99 | 0.00 | 44789430.99 | 447914.29 | 45237345.28 | 37458366.31 | 2658.42 | 280.19 | 5821.39 | 0.00 |
DINING_FLR_6 | 48427074.73 | 0.00 | 48427074.73 | 447914.29 | 48874989.02 | 37458366.31 | 1416.76 | 129.48 | 7213.76 | 0.00 |
KITCHEN_FLR_6 | 62351427.88 | 0.00 | 62351427.88 | 400987.13 | 62752415.02 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12115128.49 | 0.00 | 12115128.49 | 392463.83 | 12507592.32 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.46E+10 | 11166809.02 | 0.46E+10 | 18481630.20 | 0.46E+10 | 0.43E+10 | 5042.53 | 8203.20 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4063 | 0.0000 | 1.4063 | 0.0000 | 1.4063 | 0.8545 | 10.57 | 1.30 | 8748.13 |
RETAIL_1_FLR_1 | 0.1900 | 0.0000 | 0.1900 | 0.0100 | 0.2000 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1215 | 0.0000 | 0.1215 | 0.0039 | 0.1254 | 0.0917 | 418.01 | 84.22 | 8257.78 |
MECH_FLR_1 | 0.0901 | 0.0000 | 0.0901 | 0.0091 | 0.0993 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0578 | 0.0000 | 0.0578 | 0.0053 | 0.0630 | 0.0578 | 4149.33 | 431.92 | 4178.76 |
LAUNDRY_FLR_1 | 1.9139 | 0.0000 | 1.9139 | 0.0125 | 1.9263 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8317 | 0.0000 | 0.8317 | 0.0221 | 0.8538 | 0.6764 | 2011.51 | 328.16 | 6420.33 |
LOBBY_FLR_1 | 2.5312 | 0.0000 | 2.5312 | 0.0633 | 2.5945 | 1.8940 | 270.93 | 68.88 | 8420.19 |
ROOM_1_FLR_3 | 0.0617 | 0.0017 | 0.0634 | 0.0058 | 0.0693 | 0.0617 | 0.00 | 8059.47 | 700.53 |
ROOM_2_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0058 | 0.0693 | 0.0617 | 0.00 | 8005.53 | 754.47 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0019 | 0.8392 | 0.0016 | 0.8408 | 0.8373 | 0.00 | 7947.79 | 812.21 |
ROOM_5_FLR_3 | 0.0617 | 0.0019 | 0.0637 | 0.0058 | 0.0695 | 0.0617 | 0.00 | 8004.82 | 755.18 |
ROOM_6_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0058 | 0.0694 | 0.0617 | 0.00 | 8005.96 | 754.04 |
CORRIDOR_FLR_3 | 0.7310 | 0.0000 | 0.7310 | 0.0070 | 0.7380 | 0.4748 | 53.99 | 11.02 | 8694.99 |
ROOM_1_FLR_6 | 0.0154 | 0.0019 | 0.0173 | 0.0058 | 0.0231 | 0.0154 | 0.00 | 8092.25 | 667.75 |
ROOM_2_FLR_6 | 0.0154 | 0.0020 | 0.0174 | 0.0058 | 0.0232 | 0.0154 | 0.00 | 8037.75 | 722.25 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0023 | 0.1014 | 0.0030 | 0.1044 | 0.0992 | 0.00 | 7970.40 | 789.60 |
BANQUET_FLR_6 | 1.4203 | 0.0000 | 1.4203 | 0.0142 | 1.4345 | 1.1878 | 2658.42 | 280.19 | 5821.39 |
DINING_FLR_6 | 1.5356 | 0.0000 | 1.5356 | 0.0142 | 1.5498 | 1.1878 | 1416.76 | 129.48 | 7213.76 |
KITCHEN_FLR_6 | 1.9772 | 0.0000 | 1.9772 | 0.0127 | 1.9899 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3842 | 0.0000 | 0.3842 | 0.0124 | 0.3966 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.9292 | 0.1990 | 81.1281 | 0.4627 | 81.5908 | 73.9670 | 5042.53 | 8203.20 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.41E+09 | 0.00 | 0.41E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 63455387.45 | 549587.74 | 64004975.19 | 64690340.46 | 7915.50 | 21.35 | 823.15 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 12.9310 | 0.0000 | 12.9310 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.0122 | 0.0174 | 2.0296 | 2.0513 | 7915.50 | 21.35 | 823.15 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 4836.89 | 3923.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 11.4410 | 14.7711 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.0124 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
Electricity:Building | 2532.23 | 31904.86 | 17-JUN-05:00 | 158241.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 332.05 | 3744.83 | 02-JAN-02:10 | 25084.28 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2525.14 | 31763.71 | 17-JUN-05:00 | 158000.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 866.96 | 7561.74 | 17-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 866.96 | 7561.74 | 17-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 866.96 | 7561.74 | 17-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 866.96 | 7561.74 | 17-JUN-05:00 | 71560.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.95 | 223.93 | 02-JAN-02:10 | 1401.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.94 | 259.31 | 02-JAN-02:10 | 1623.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.64 | 250.98 | 02-JAN-02:10 | 1507.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 7.74 | 88.65 | 02-JAN-02:10 | 581.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 30.39 | 335.90 | 17-JUN-05:00 | 2922.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.05 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.05 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 247.74 | 3039.71 | 03-JUN-05:00 | 18583.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 98.74 | 928.30 | 03-JUN-05:00 | 8554.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 98.74 | 928.30 | 03-JUN-05:00 | 8554.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 325.45 | 4437.75 | 01-JAN-02:10 | 23570.01 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 325.54 | 4438.96 | 01-JAN-02:10 | 23576.46 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.35 | 67.90 | 01-JAN-02:10 | 391.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.35 | 67.89 | 01-JAN-02:10 | 391.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 38.55 | 525.67 | 01-JAN-02:10 | 2791.95 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 211.15 | 2503.96 | 17-JUN-05:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.29 | 254.65 | 17-JUN-05:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.29 | 254.65 | 17-JUN-05:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 211.15 | 2503.96 | 17-JUN-05:00 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.29 | 254.65 | 17-JUN-05:00 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.29 | 254.65 | 17-JUN-05:00 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.61 | 1095.82 | 29-DEC-23:30 | 3517.39 | 14-FEB-08:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1281.34 | 2605.59 | 01-APR-02:30 | 176662.20 | 21-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.50 | 0.00 | 01-JAN-11:10 | 2090.68 | 17-FEB-08:10 |
MedTempRefrigeration:Refrigeration:Electricity | 34.02 | 955.11 | 24-NOV-02:40 | 1245.48 | 16-JAN-08:00 |
Fans:Electricity | 619.04 | 11223.02 | 31-MAR-23:30 | 56045.46 | 19-NOV-09:30 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 831.35 | 13998.91 | 09-NOV-15:00 | 61314.75 | 18-AUG-21:10 |
ExteriorEquipment:Electricity | 650.09 | 9607.53 | 02-JAN-02:20 | 39721.54 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 31.07 | 542.72 | 11-JAN-02:20 | 1847.44 | 10-JAN-21:10 |
ElectricityPurchased:Facility | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
ElectricityPurchased:Plant | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
Cogeneration:ElectricityPurchased | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
General:Cogeneration:ElectricityPurchased | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
ElectricityNet:Plant | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
Cogeneration:ElectricityNet | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
General:Cogeneration:ElectricityNet | 5526.20 | 77465.69 | 29-MAR-03:50 | 410749.35 | 21-JUL-19:20 |
General:Fans:Electricity | 619.04 | 11223.02 | 31-MAR-23:30 | 56045.46 | 19-NOV-09:30 |
ExteriorLights:Electricity | 262.25 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.25 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 181.25 | 0.00 | 01-JAN-13:30 | 9938.94 | 04-JAN-09:40 |
General:HeatRecovery:Electricity | 181.25 | 0.00 | 01-JAN-13:30 | 9938.94 | 04-JAN-09:40 |
WaterSystems:Electricity | 90.74 | 1086.56 | 27-MAY-03:00 | 4738.75 | 14-DEC-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 27-MAY-03:00 | 4738.75 | 14-DEC-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1041.30 | 0.00 | 01-JAN-02:10 | 166884.95 | 21-JUL-18:10 |
General:Cooling:Electricity | 1041.30 | 0.00 | 01-JAN-02:10 | 166884.95 | 21-JUL-18:10 |
Pumps:Electricity | 94.77 | 47.91 | 21-FEB-11:50 | 4565.10 | 26-JUN-18:30 |
General:Pumps:Electricity | 94.77 | 47.91 | 21-FEB-11:50 | 4565.10 | 26-JUN-18:30 |
WIRED_LTG_ELECTRICITY | 30.52 | 0.00 | 01-JAN-00:10 | 2518.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5343.95 | 31829.34 | 11-APR-01:20 | 520048.43 | 06-DEC-20:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3555.11 | 18467.44 | 14-FEB-16:20 | 444281.06 | 02-JAN-24:00 |
WaterSystems:NaturalGas | 3124.01 | 18467.44 | 11-JAN-01:40 | 290662.75 | 29-MAR-21:00 |
Water Heater:WaterSystems:NaturalGas | 3124.01 | 18467.44 | 11-JAN-01:40 | 290662.75 | 29-MAR-21:00 |
Heating:NaturalGas | 431.11 | 0.00 | 01-JAN-11:50 | 195910.24 | 23-FEB-22:20 |
Boiler:Heating:NaturalGas | 431.11 | 0.00 | 01-JAN-11:50 | 195910.24 | 23-FEB-22:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3163.38 | -1435.12 | 08-APR-01:30 | 477384.28 | 21-JUL-18:10 |
PlantLoopCoolingDemand:HVAC | 3163.38 | -1435.12 | 08-APR-01:30 | 477384.28 | 21-JUL-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 3163.38 | -1435.12 | 08-APR-01:30 | 477384.28 | 21-JUL-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 11-JAN-01:40 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 11-JAN-01:40 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 11-JAN-07:50 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 11-JAN-07:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19809.88 | 140533.36 | 28-MAR-10:10 | 2062313.98 | 21-JUL-18:10 |
EnergyTransfer:Building | 5670.74 | 44524.36 | 05-FEB-15:00 | 378811.67 | 20-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 736.49 | 7811.27 | 01-APR-01:10 | 37121.05 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 180.95 | 3899.32 | 14-NOV-23:10 | 10745.76 | 14-FEB-08:00 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.48 | 1949.66 | 14-NOV-23:10 | 5372.88 | 14-FEB-08:00 |
General:Refrigeration:EnergyTransfer | 90.48 | 1949.66 | 14-NOV-23:10 | 5372.88 | 14-FEB-08:00 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.48 | 1949.66 | 14-NOV-23:10 | 5372.88 | 14-FEB-08:00 |
EnergyTransfer:Plant | 8638.13 | 14538.80 | 15-MAR-01:20 | 1153654.25 | 21-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.54 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.93 | 1815.34 | 24-NOV-02:40 | 2686.44 | 16-JAN-08:00 |
EnergyTransfer:Zone:BASEMENT | 440.91 | 1175.08 | 05-FEB-15:00 | 28384.20 | 01-NOV-05:20 |
Heating:EnergyTransfer | 71.01 | 0.00 | 01-JAN-08:10 | 51015.94 | 21-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.02 | 0.00 | 01-JAN-00:10 | 1509.17 | 07-NOV-01:40 |
General:Heating:EnergyTransfer | 71.01 | 0.00 | 01-JAN-08:10 | 51015.94 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.02 | 0.00 | 01-JAN-00:10 | 1509.17 | 07-NOV-01:40 |
Cooling:EnergyTransfer | 5509.25 | 38725.63 | 05-FEB-15:00 | 375580.80 | 21-JUL-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 440.89 | 1175.08 | 05-FEB-15:00 | 28384.20 | 01-NOV-05:20 |
General:Cooling:EnergyTransfer | 5509.25 | 38725.63 | 05-FEB-15:00 | 375580.80 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 440.89 | 1175.08 | 05-FEB-15:00 | 28384.20 | 01-NOV-05:20 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.34 | 0.66 | 10-DEC-06:20 | 4929.28 | 05-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 573.44 | 09-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 573.44 | 09-DEC-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.20 | 0.00 | 12-JAN-07:10 | 4929.28 | 05-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.20 | 0.00 | 12-JAN-07:10 | 4929.28 | 05-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.15 | 34.19 | 24-FEB-09:50 | 2401.06 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 160.48 | 07-NOV-02:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 160.48 | 07-NOV-02:00 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.14 | 0.00 | 19-JAN-13:50 | 2401.06 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.14 | 0.00 | 19-JAN-13:50 | 2401.06 | 21-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 25.02 | 0.49 | 19-JAN-11:30 | 1975.85 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 200.97 | 16-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 200.97 | 16-JAN-07:50 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 24.99 | 0.00 | 19-JAN-11:30 | 1975.85 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 24.99 | 0.00 | 19-JAN-11:30 | 1975.85 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 14.92 | 0.29 | 17-JAN-12:30 | 1065.01 | 21-JUL-18:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 167.42 | 14-DEC-13:30 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 167.42 | 14-DEC-13:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.88 | 0.00 | 17-JAN-10:10 | 1065.01 | 21-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.88 | 0.00 | 17-JAN-10:10 | 1065.01 | 21-JUL-18:30 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 602.30 | 6044.52 | 27-OCT-01:20 | 39565.06 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 564.04 | 28-OCT-05:00 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 564.04 | 28-OCT-05:00 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 602.29 | 6044.52 | 27-OCT-01:20 | 39565.06 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 602.29 | 6044.52 | 27-OCT-01:20 | 39565.06 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 257.87 | 231.88 | 05-FEB-15:00 | 17849.25 | 30-DEC-11:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 889.34 | 16-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 889.34 | 16-JAN-07:50 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 257.84 | 231.88 | 05-FEB-15:00 | 17849.25 | 30-DEC-11:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 257.84 | 231.88 | 05-FEB-15:00 | 17849.25 | 30-DEC-11:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 794.09 | 321.53 | 05-FEB-15:00 | 43032.21 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 3147.25 | 16-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 3147.25 | 16-JAN-07:50 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 794.04 | 321.53 | 05-FEB-15:00 | 43032.21 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 794.04 | 321.53 | 05-FEB-15:00 | 43032.21 | 21-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 75.03 | 0.33 | 06-DEC-22:00 | 14636.09 | 25-APR-16:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 6.37 | 0.00 | 01-JAN-08:10 | 4137.47 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 6.37 | 0.00 | 01-JAN-08:10 | 4137.47 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 68.66 | 0.00 | 01-JAN-00:10 | 14636.09 | 25-APR-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 68.66 | 0.00 | 01-JAN-00:10 | 14636.09 | 25-APR-16:30 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 66.58 | 0.07 | 09-APR-02:10 | 14218.07 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 11.12 | 0.00 | 01-JAN-08:10 | 4528.59 | 15-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 11.12 | 0.00 | 01-JAN-08:10 | 4528.59 | 15-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 55.46 | 0.00 | 01-JAN-00:10 | 14218.07 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 55.46 | 0.00 | 01-JAN-00:10 | 14218.07 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 579.57 | 48.27 | 19-JAN-02:10 | 65303.00 | 14-FEB-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2589.46 | 19-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2589.46 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 579.55 | 0.00 | 19-JAN-02:10 | 65303.00 | 14-FEB-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 579.55 | 0.00 | 19-JAN-02:10 | 65303.00 | 14-FEB-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 429.07 | 0.20 | 04-MAR-01:50 | 73845.42 | 26-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.69 | 0.00 | 01-JAN-00:10 | 28534.86 | 15-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.69 | 0.00 | 01-JAN-00:10 | 28534.86 | 15-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 406.38 | 0.00 | 01-JAN-00:30 | 73845.42 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 406.38 | 0.00 | 01-JAN-00:30 | 73845.42 | 26-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 79.73 | 0.05 | 20-APR-02:10 | 15538.02 | 14-JUN-08:30 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.71 | 0.00 | 01-JAN-07:40 | 4107.66 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.71 | 0.00 | 01-JAN-07:40 | 4107.66 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.02 | 0.00 | 01-JAN-00:10 | 15538.02 | 14-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.02 | 0.00 | 01-JAN-00:10 | 15538.02 | 14-JUN-08:30 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 70.78 | 0.14 | 09-APR-01:10 | 15787.09 | 14-JUN-08:30 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.21 | 0.00 | 01-JAN-08:00 | 4228.96 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.21 | 0.00 | 01-JAN-08:00 | 4228.96 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.57 | 0.00 | 01-JAN-00:10 | 15787.09 | 14-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.57 | 0.00 | 01-JAN-00:10 | 15787.09 | 14-JUN-08:30 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 204.13 | 3.51 | 20-JAN-10:50 | 13782.31 | 21-JUL-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.30 | 0.00 | 01-JAN-00:10 | 1671.17 | 16-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.30 | 0.00 | 01-JAN-00:10 | 1671.17 | 16-JAN-07:50 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 203.83 | 0.00 | 19-JAN-09:10 | 13782.31 | 21-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 203.83 | 0.00 | 19-JAN-09:10 | 13782.31 | 21-JUL-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.15 | 0.02 | 28-MAR-00:20 | 4135.36 | 25-APR-16:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.92 | 0.00 | 01-JAN-08:10 | 1159.36 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.92 | 0.00 | 01-JAN-08:10 | 1159.36 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.23 | 0.00 | 01-JAN-00:10 | 4135.36 | 25-APR-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.23 | 0.00 | 01-JAN-00:10 | 4135.36 | 25-APR-16:30 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.54 | 0.06 | 19-APR-00:50 | 3896.24 | 25-APR-16:40 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.63 | 0.00 | 01-JAN-08:10 | 1383.97 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.63 | 0.00 | 01-JAN-08:10 | 1383.97 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.91 | 0.00 | 01-JAN-00:10 | 3896.24 | 25-APR-16:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.91 | 0.00 | 01-JAN-00:10 | 3896.24 | 25-APR-16:40 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 121.68 | 0.35 | 04-MAY-03:00 | 19569.03 | 19-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.51 | 0.00 | 01-JAN-00:10 | 4729.92 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.51 | 0.00 | 01-JAN-00:10 | 4729.92 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 117.17 | 0.00 | 01-JAN-03:30 | 19569.03 | 19-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 117.17 | 0.00 | 01-JAN-03:30 | 19569.03 | 19-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 450.69 | 1965.75 | 05-FEB-15:00 | 24038.13 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 689.45 | 10-JAN-11:20 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 689.45 | 10-JAN-11:20 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 450.69 | 1965.75 | 05-FEB-15:00 | 24038.13 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 450.69 | 1965.75 | 05-FEB-15:00 | 24038.13 | 21-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 489.31 | 2494.00 | 19-JAN-13:50 | 25237.19 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 584.56 | 13-DEC-10:50 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 584.56 | 13-DEC-10:50 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 489.31 | 2494.00 | 19-JAN-13:50 | 25237.19 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 489.31 | 2494.00 | 19-JAN-13:50 | 25237.19 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 252.19 | 20-NOV-01:50 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 252.19 | 20-NOV-01:50 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 646.02 | 5711.42 | 01-APR-01:10 | 32069.25 | 22-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 646.02 | 5711.42 | 01-APR-01:10 | 32069.25 | 22-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 104.37 | 0.14 | 18-JAN-06:20 | 7559.35 | 20-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.21 | 0.00 | 01-JAN-00:10 | 894.38 | 16-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.21 | 0.00 | 01-JAN-00:10 | 894.38 | 16-JAN-07:50 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 104.16 | 0.00 | 17-JAN-07:10 | 7559.35 | 20-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 104.16 | 0.00 | 17-JAN-07:10 | 7559.35 | 20-AUG-13:10 |
PlantLoopHeatingDemand:Facility | 1025.64 | 8272.10 | 05-AUG-01:30 | 188507.39 | 03-MAR-07:30 |
PlantLoopHeatingDemand:Plant | 722.65 | 8272.10 | 05-AUG-01:30 | 54954.76 | 08-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 722.65 | 8272.10 | 05-AUG-01:30 | 54954.76 | 08-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 722.65 | 8272.10 | 05-AUG-01:30 | 54954.76 | 08-FEB-07:40 |
EnergyTransfer:HVAC | 5501.01 | 4.18 | 28-MAR-10:20 | 545732.57 | 28-JUN-18:10 |
HeatingCoils:EnergyTransfer | 302.99 | 0.00 | 01-JAN-11:50 | 146117.79 | 02-DEC-23:40 |
PlantLoopHeatingDemand:HVAC | 302.99 | 0.00 | 01-JAN-11:50 | 146117.79 | 02-DEC-23:40 |
HeatingCoils:PlantLoopHeatingDemand | 302.99 | 0.00 | 01-JAN-11:50 | 146117.79 | 02-DEC-23:40 |
CoolingCoils:EnergyTransfer | 3163.38 | -1435.12 | 08-APR-01:30 | 477384.28 | 21-JUL-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 1937.88 | 0.00 | 01-JAN-13:30 | 396808.68 | 15-DEC-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 96.76 | 0.00 | 01-JAN-00:10 | 102661.49 | 28-JUN-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 722.65 | 8272.10 | 05-AUG-01:30 | 54954.76 | 08-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 722.65 | 8272.10 | 05-AUG-01:30 | 54954.76 | 08-FEB-07:40 |
Boilers:EnergyTransfer | 299.37 | 0.00 | 01-JAN-11:50 | 144888.48 | 02-DEC-23:40 |
Chillers:EnergyTransfer | 3242.17 | 0.00 | 01-JAN-02:10 | 478609.62 | 21-JUL-18:10 |
HeatRejection:EnergyTransfer | 4283.47 | 0.00 | 01-JAN-02:10 | 645494.57 | 21-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 4283.47 | 0.00 | 01-JAN-02:10 | 645494.57 | 21-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.018 | -440.896 | 0.000 | 0.000 | 135.079 | 188.948 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -26.254 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.139 | -52.199 | 0.000 | 0.000 | 14.791 | 8.760 | 10.186 | 37.346 | 0.000 | 0.227 | 0.000 | 0.000 | -11.073 | 0.000 | -3.234 | -4.943 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.004 | -37.144 | 0.000 | 0.000 | 16.124 | 10.144 | 11.795 | 0.000 | 0.000 | 0.089 | 0.328 | 0.000 | 0.000 | 0.000 | -1.340 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.038 | -24.986 | 0.000 | 0.000 | 3.585 | 8.172 | 12.471 | 0.000 | 0.000 | 0.213 | 3.443 | 0.000 | 0.000 | 0.000 | -2.936 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.043 | -14.881 | 0.000 | 0.000 | 2.808 | 4.146 | 3.598 | 0.000 | 0.000 | 0.126 | 5.808 | 0.000 | 0.000 | 0.000 | -1.648 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.008 | -602.291 | 0.000 | 0.000 | 10.838 | 5.547 | 658.131 | 0.000 | 0.000 | 0.292 | 0.000 | 0.000 | 0.000 | 0.000 | -4.378 | -68.146 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.024 | -257.845 | 0.000 | 0.000 | 182.054 | 16.046 | 14.341 | 104.012 | 0.000 | 0.501 | 0.003 | 0.000 | -33.314 | 0.000 | -7.751 | -18.066 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.045 | -794.053 | 0.000 | 0.000 | 534.787 | 98.744 | 148.998 | 137.897 | 0.000 | 1.435 | 0.000 | 0.000 | -44.088 | 0.000 | -22.446 | -61.320 |
ROOM_1_FLR_3 | 8.453 | -56.281 | 0.000 | -14.463 | 0.000 | 0.000 | 9.480 | 10.925 | 10.478 | 72.612 | 0.000 | 0.761 | 0.000 | 0.000 | -24.151 | 0.000 | -7.950 | -9.864 |
ROOM_2_FLR_3 | 13.960 | -44.240 | 0.000 | -14.064 | 0.000 | 0.000 | 9.539 | 10.924 | 10.477 | 50.999 | 0.000 | 0.761 | 0.000 | 0.000 | -24.657 | 0.000 | -7.865 | -5.834 |
ROOM_3_MULT19_FLR_3 | 0.067 | -353.693 | 0.000 | -225.898 | 0.000 | 0.000 | 0.000 | 130.455 | 194.997 | 453.270 | 0.000 | 3.240 | 0.012 | 0.000 | -140.557 | 0.000 | -59.655 | -2.226 |
ROOM_4_MULT19_FLR_3 | 49.209 | -248.709 | 0.000 | -184.186 | 0.000 | 0.000 | 183.178 | 130.491 | 195.050 | 121.237 | 0.000 | 4.570 | 0.000 | 0.000 | -131.725 | 0.000 | -49.823 | -69.293 |
ROOM_5_FLR_3 | 8.812 | -60.528 | 0.000 | -14.599 | 0.000 | 0.000 | 9.476 | 10.925 | 10.478 | 76.127 | 0.000 | 0.758 | 0.001 | 0.000 | -23.358 | 0.000 | -8.186 | -9.905 |
ROOM_6_FLR_3 | 13.959 | -48.104 | 0.000 | -14.207 | 0.000 | 0.000 | 9.533 | 10.924 | 10.477 | 53.941 | 0.000 | 0.759 | 0.002 | 0.000 | -23.317 | 0.000 | -7.936 | -6.027 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.300 | -203.833 | 0.000 | 0.000 | 112.998 | 91.336 | 0.000 | 63.879 | 0.000 | 0.637 | 0.000 | 0.000 | -31.285 | 0.000 | -9.128 | -24.904 |
ROOM_1_FLR_6 | 3.565 | -14.276 | 0.000 | -3.604 | 0.000 | 0.000 | 2.370 | 2.731 | 2.620 | 18.047 | 0.000 | 0.189 | 0.000 | 0.000 | -5.997 | 0.000 | -2.000 | -3.646 |
ROOM_2_FLR_6 | 5.447 | -11.226 | 0.000 | -3.496 | 0.000 | 0.000 | 2.386 | 2.731 | 2.619 | 12.688 | 0.000 | 0.189 | 0.000 | 0.000 | -6.105 | 0.000 | -1.981 | -3.253 |
ROOM_3_MULT9_FLR_6 | 6.888 | -96.279 | 0.000 | -23.270 | 0.000 | 0.000 | 21.363 | 15.453 | 23.098 | 98.512 | 0.000 | 0.897 | 0.003 | 0.000 | -27.761 | 0.000 | -10.615 | -8.287 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.006 | -450.693 | 0.000 | 0.000 | 314.521 | 35.294 | 175.857 | 12.024 | 0.000 | 0.309 | 0.000 | 0.000 | -18.627 | 0.000 | -5.119 | -63.571 |
DINING_FLR_6 | 0.000 | 0.000 | 0.004 | -489.312 | 0.000 | 0.000 | 314.056 | 35.294 | 175.857 | 11.817 | 0.000 | 0.309 | 0.000 | 0.000 | -19.047 | 0.000 | -5.140 | -23.839 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.002 | -646.000 | 0.000 | 0.000 | 27.931 | 14.807 | 550.372 | 34.528 | 0.000 | 0.277 | 35.931 | 0.000 | -13.221 | 0.000 | -4.627 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.211 | -104.158 | 0.000 | 0.000 | 30.260 | 24.166 | 0.000 | 31.587 | 0.000 | 0.272 | 35.549 | 0.000 | -13.889 | 0.000 | -3.999 | -0.001 |
Total Facility | 110.360 | -933.336 | 0.841 | -4616.077 | 0.000 | 0.000 | 1947.158 | 866.962 | 2365.005 | 1390.524 | 0.000 | 16.812 | 81.082 | 0.000 | -592.171 | 0.000 | -227.759 | -409.380 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-FEB-17:10 | 0.00 | 0.00 | 0.00 | -51980.17 | 0.00 | 0.00 | 3797.92 | 4292.22 | 3548.83 | 0.00 | 0.00 | 0.00 | 40341.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 31-DEC-10:38 | 0.00 | 0.00 | 0.00 | -7405.45 | 0.00 | 0.00 | 376.53 | 238.78 | 288.68 | 7470.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -224.78 | -744.61 |
RETAIL_2_FLR_1 | 12-OCT-04:20 | 0.00 | 0.00 | 0.00 | -4579.64 | 0.00 | 0.00 | 804.85 | 184.34 | 250.72 | 0.00 | 0.00 | 0.00 | 3407.54 | 0.00 | -0.00 | 0.00 | -67.80 | 0.00 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1975.88 | 0.00 | 0.00 | 129.08 | 668.27 | 839.45 | 0.00 | 0.00 | 57.03 | 282.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 29-DEC-23:14 | 0.00 | 0.00 | 0.00 | -1114.02 | 0.00 | 0.00 | 149.56 | 113.01 | 101.96 | 0.00 | 0.00 | 0.00 | 854.27 | 0.00 | -0.00 | 0.00 | -104.78 | 0.00 |
LAUNDRY_FLR_1 | 15-DEC-20:55 | 0.00 | 0.00 | 0.00 | -57682.18 | 0.00 | 0.00 | 300.45 | 453.60 | 44299.38 | 0.00 | 0.00 | 0.00 | 12930.15 | 0.00 | -0.00 | 0.00 | -301.40 | 0.00 |
CAFE_FLR_1 | 31-DEC-10:38 | 0.00 | 0.00 | 0.00 | -30809.15 | 0.00 | 0.00 | 4948.55 | 143.56 | 406.43 | 20955.73 | 0.00 | 0.00 | 4852.64 | 0.00 | -0.00 | 0.00 | -497.76 | 0.00 |
LOBBY_FLR_1 | 01-DEC-01:00 | 0.00 | 0.00 | 0.00 | -94818.15 | 0.00 | 0.00 | 26448.80 | 1900.96 | 3167.12 | 0.00 | 0.00 | 0.00 | 67935.54 | 0.00 | -3426.19 | 0.00 | -1208.07 | 0.00 |
ROOM_1_FLR_3 | 25-APR-16:21 | 0.00 | -21588.75 | 0.00 | -747.51 | 0.00 | 0.00 | 193.47 | 235.45 | 505.73 | 11748.91 | 0.00 | 0.00 | 9664.05 | 0.00 | -0.00 | 0.00 | -11.34 | 0.00 |
ROOM_2_FLR_3 | 25-APR-16:21 | 0.00 | -21318.29 | 0.00 | -745.55 | 0.00 | 0.00 | 193.47 | 235.42 | 505.67 | 11727.48 | 0.00 | 0.00 | 9412.47 | 0.00 | -0.00 | 0.00 | -10.68 | 0.00 |
ROOM_3_MULT19_FLR_3 | 19-OCT-12:30 | 0.00 | -56644.48 | 0.00 | -8654.40 | 0.00 | 0.00 | 0.00 | 2811.47 | 2352.88 | 85899.80 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -341.83 | -25423.44 |
ROOM_4_MULT19_FLR_3 | 18-JUN-08:51 | 0.00 | -108296.55 | 0.00 | -8917.54 | 0.00 | 0.00 | 2381.86 | 5624.48 | 12159.85 | 10793.38 | 0.00 | 258.12 | 85996.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-JUN-08:21 | 0.00 | -19386.52 | 0.00 | -762.31 | 0.00 | 0.00 | 71.66 | 370.00 | 453.05 | 10342.32 | 0.00 | 22.32 | 8889.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 14-JUN-08:62 | 0.00 | -19708.87 | 0.00 | -835.20 | 0.00 | 0.00 | 58.85 | 369.95 | 452.99 | 10802.04 | 0.00 | 0.00 | 8880.80 | 0.00 | -0.00 | 0.00 | -20.58 | 0.00 |
CORRIDOR_FLR_3 | 29-DEC-23:14 | 0.00 | 0.00 | 0.00 | -14234.84 | 0.00 | 0.00 | 6010.64 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 8905.31 | 0.00 | -2597.94 | 0.00 | -572.93 | 0.00 |
ROOM_1_FLR_6 | 25-APR-16:21 | 0.00 | -5722.31 | 0.00 | -187.05 | 0.00 | 0.00 | 48.37 | 58.86 | 126.43 | 2909.68 | 0.00 | 0.00 | 2769.25 | 0.00 | -0.00 | 0.00 | -3.23 | 0.00 |
ROOM_2_FLR_6 | 25-APR-16:21 | 0.00 | -5639.55 | 0.00 | -186.50 | 0.00 | 0.00 | 48.37 | 58.86 | 126.42 | 2905.12 | 0.00 | 0.00 | 2690.33 | 0.00 | -0.00 | 0.00 | -3.04 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17-OCT-19:21 | 0.00 | -23689.38 | 0.00 | -944.31 | 0.00 | 0.00 | 620.88 | 1189.39 | 1439.98 | 0.00 | 0.00 | 0.00 | 23457.26 | 0.00 | -1780.53 | 0.00 | -293.29 | 0.00 |
BANQUET_FLR_6 | 29-DEC-23:14 | 0.00 | 0.00 | 0.00 | -44258.17 | 0.00 | 0.00 | 15657.08 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 22413.01 | 0.00 | -1393.18 | 0.00 | -312.59 | 0.00 |
DINING_FLR_6 | 29-DEC-23:14 | 0.00 | 0.00 | 0.00 | -50015.48 | 0.00 | 0.00 | 15641.75 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 28207.62 | 0.00 | -1416.46 | 0.00 | -311.27 | 0.00 |
KITCHEN_FLR_6 | 19-JAN-13:37 | 0.00 | 0.00 | 0.00 | -44669.97 | 0.00 | 0.00 | 201.54 | 336.37 | 21760.70 | 1207.70 | 0.00 | 0.00 | 21422.87 | 0.00 | -0.00 | 0.00 | -259.20 | 0.00 |
CORRIDOR_FLR_6 | 20-AUG-13:10 | 0.00 | 0.00 | 0.00 | -7558.34 | 0.00 | 0.00 | 308.46 | 439.17 | 0.00 | 3587.57 | 0.00 | 105.22 | 3117.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JUL-18:02 | 0.00 | -226424.48 | 0.00 | -224228.78 | 0.00 | 0.00 | 73716.78 | 59351.70 | 120482.43 | 72585.01 | 0.00 | 6867.42 | 117649.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-DEC-07:35 | 0.00 | 0.00 | 5765.34 | 0.00 | 0.00 | 0.00 | 5183.72 | 6867.51 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22886.33 |
RETAIL_1_FLR_1 | 11-NOV-08:59 | 0.00 | 0.00 | 1229.60 | 0.00 | 0.00 | 0.00 | 447.55 | 318.38 | 360.84 | 1253.43 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -165.40 | -3444.41 |
RETAIL_2_FLR_1 | 12-MAR-00:22 | 0.00 | 0.00 | 450.77 | 0.00 | 0.00 | 0.00 | 616.35 | 276.51 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -80.53 | -1597.39 |
MECH_FLR_1 | 23-DEC-11:57 | 0.00 | 0.00 | 598.31 | 0.00 | 0.00 | 0.00 | 65.51 | 185.63 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -170.88 | -987.84 |
STORAGE_FLR_1 | 23-DEC-11:57 | 0.00 | 0.00 | 543.91 | 0.00 | 0.00 | 0.00 | 50.53 | 94.17 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -98.59 | -679.25 |
LAUNDRY_FLR_1 | 20-APR-04:54 | 0.00 | 0.00 | 3142.40 | 0.00 | 0.00 | 0.00 | 558.52 | 100.80 | 13989.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -262.31 | -17528.70 |
CAFE_FLR_1 | 12-MAR-00:22 | 0.00 | 0.00 | 2465.68 | 0.00 | 0.00 | 0.00 | 7154.69 | 652.56 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2762.14 | 0.00 | -465.53 | -7451.69 |
LOBBY_FLR_1 | 03-DEC-07:35 | 0.00 | 0.00 | 10051.05 | 0.00 | 0.00 | 0.00 | 20770.45 | 3535.79 | 5278.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2138.51 | 0.00 | -1271.07 | -36226.24 |
ROOM_1_FLR_3 | 05-JAN-17:03 | 6737.42 | 345.81 | 0.00 | -345.81 | 0.00 | 0.00 | 220.54 | 235.45 | 505.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1477.29 | 0.00 | -192.50 | -6029.34 |
ROOM_2_FLR_3 | 19-FEB-16:03 | 6816.27 | 356.30 | 0.00 | -356.30 | 0.00 | 0.00 | 133.20 | 277.46 | 221.23 | 2008.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1047.22 | -8409.28 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:00 | 2589.55 | 2845.33 | 0.00 | -2845.33 | 0.00 | 0.00 | 0.00 | 1104.51 | 3333.24 | 0.00 | 0.00 | 0.00 | 8170.37 | 0.00 | -12342.74 | 0.00 | -2854.93 | 0.00 |
ROOM_4_MULT19_FLR_3 | 15-DEC-16:01 | 34833.29 | 3341.61 | 0.00 | -3341.61 | 0.00 | 0.00 | 5498.15 | 2812.24 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7729.83 | 0.00 | -1983.52 | -37156.74 |
ROOM_5_FLR_3 | 20-OCT-20:23 | 6401.97 | 347.96 | 0.00 | -347.96 | 0.00 | 0.00 | 373.47 | 748.40 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1167.57 | 0.00 | -149.90 | -6933.34 |
ROOM_6_FLR_3 | 12-APR-21:53 | 6311.76 | 384.23 | 0.00 | -384.23 | 0.00 | 0.00 | 421.08 | 563.34 | 358.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1011.52 | 0.00 | -102.95 | -6539.89 |
CORRIDOR_FLR_3 | 25-DEC-18:58 | 0.00 | 0.00 | 3804.55 | 0.00 | 0.00 | 0.00 | 2771.57 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2663.92 | 0.00 | -558.51 | -7503.28 |
ROOM_1_FLR_6 | 05-JAN-17:03 | 1969.42 | 87.34 | 0.00 | -87.34 | 0.00 | 0.00 | 53.53 | 58.86 | 126.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -382.46 | 0.00 | -48.81 | -1776.97 |
ROOM_2_FLR_6 | 19-FEB-16:03 | 1963.13 | 89.63 | 0.00 | -89.63 | 0.00 | 0.00 | 33.36 | 69.37 | 55.31 | 495.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -322.47 | -2294.19 |
ROOM_3_MULT9_FLR_6 | 24-APR-21:53 | 8692.65 | 564.53 | 0.00 | -564.53 | 0.00 | 0.00 | 963.25 | 796.89 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1286.04 | 0.00 | -149.39 | -9807.03 |
BANQUET_FLR_6 | 25-DEC-01:29 | 0.00 | 0.00 | 4052.42 | 0.00 | 0.00 | 0.00 | 12122.53 | 1145.95 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1457.14 | 0.00 | -306.33 | -17806.72 |
DINING_FLR_6 | 29-OCT-03:28 | 0.00 | 0.00 | 3605.36 | 0.00 | 0.00 | 0.00 | 12367.08 | 763.96 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1389.40 | 0.00 | -292.84 | -17303.46 |
KITCHEN_FLR_6 | 29-OCT-03:28 | 0.00 | 0.00 | 2490.90 | 0.00 | 0.00 | 0.00 | 1116.25 | 269.09 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1147.50 | 0.00 | -266.98 | -7877.74 |
CORRIDOR_FLR_6 | 25-JAN-08:53 | 0.00 | 0.00 | 2909.56 | 0.00 | 0.00 | 0.00 | 733.35 | 878.34 | 0.00 | 1304.95 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -244.50 | -5581.71 |
Total Facility | 21-DEC-16:02 | -27239.11 | 101288.06 | 0.00 | -101288.06 | 0.00 | 0.00 | 58502.67 | 19609.53 | 73912.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46907.48 | 0.00 | -13620.44 | -64257.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 27.1366 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.9865 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.5683 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6687 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3180 | 3.3180 | 1.4267 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4362 | 0.4362 | 0.1876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2917 | 0.2917 | 0.1254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2283 | 0.2283 | 0.0982 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1520 | 0.1520 | 0.0654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9711 | 3.9711 | 1.7076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8154 | 1.8154 | 0.7806 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7276 | 5.7276 | 2.4629 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8907 | 1.8907 | 0.8130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7141 | 2.7141 | 1.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8436 | 2.8436 | 1.2227 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7747 | 2.7747 | 1.1931 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9733 | 0.9733 | 0.4185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 27.1366 | 26.9865 | 27.1366 | 11.6687 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6590 | 1.6590 | 1.4267 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2181 | 0.2181 | 0.1876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1458 | 0.1458 | 0.1254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1142 | 0.1142 | 0.0982 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0760 | 0.0760 | 0.0654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9856 | 1.9856 | 1.7076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9077 | 0.9077 | 0.7806 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8638 | 2.8638 | 2.4629 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9454 | 0.9454 | 0.8130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3570 | 1.3570 | 1.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4218 | 1.4218 | 1.2227 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3873 | 1.3873 | 1.1931 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4866 | 0.4866 | 0.4185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.5683 | 11.6687 | 11.6687 | 11.6687 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 518.17 |
Number of hours not met | 518.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 431.11 | 195910.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1041.30 | 166884.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 866.96 | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.25 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.07 | 1847.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 619.04 | 56045.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 94.77 | 4565.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 181.25 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.75 | 3124.01 | 290662.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.50 | 2090.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.02 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.79 | 5526.20 |
Natural Gas | 1788.84 | 5343.95 |
Additional | 0.00 | 0.00 |
Total | 3508.63 | 10870.15 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 76.42 |
Space Heating | 0.00 |
Space Cooling | 91.78 |
Fans (All) | 54.56 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 487.09 |
Subtotal | 487.09 |
Natural Gas [MJ/m2] | |
Space Heating | 38.00 |
Service Water Heating | 275.36 |
Miscellaneous (All) | 471.03 |
Subtotal | 471.03 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.98 |
Space Heating | 3.97 |
Space Cooling | 9.58 |
Fans (All) | 5.69 |
Service Water Heating | 29.57 |
Receptacle Equipment | 31.71 |
Miscellaneous | 11.50 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8666.00 | 94.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8664.50 | 95.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8711.67 | 48.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8664.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 95.50 | 0.00 | 0.00 | 0.00 |
Average | 8746.97 | 13.03 | 0.00 | 0.00 | 0.00 |
Sum | 192433.33 | 286.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37201.67 | 1.33 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4151.50 | 2.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4146.17 | 7.83 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4147.33 | 6.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108242.33 | 26.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 26.67 | 0.00 | 0.00 | 0.00 |
Average | 288884.88 | 2.17 | 0.00 | 0.00 | 0.00 |
Sum | 6355467.33 | 47.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8637.17 | 122.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8686.83 | 73.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8640.67 | 119.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8641.83 | 118.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8676.00 | 84.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8688.00 | 72.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8637.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 122.83 | 0.00 | 0.00 | 0.00 |
Average | 8729.98 | 30.02 | 0.00 | 0.00 | 0.00 |
Sum | 192059.67 | 660.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 696223.33 | 14193.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2090500.00 | 24929.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4143.50 | 10.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4147.33 | 6.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4143.50 | 10.50 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4144.50 | 9.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4139.67 | 14.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4141.33 | 12.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4150.00 | 4.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1228499.00 | 17216.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1230987.00 | 14728.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108264.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2090500.00 | 24929.00 | 0.00 | 0.00 | 0.00 |
Average | 285653.42 | 3233.63 | 0.00 | 0.00 | 0.00 |
Sum | 6284375.17 | 71139.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:40
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365741E+11 | 40334.30 | 13-JAN-18:19 | 1.67 | -1.7 | 0.819531E+10 | 5029.04 | 23-JAN-22:49 | 1.60 | -3.0 |
February | 0.304062E+11 | 51984.29 | 03-FEB-17:10 | 3.35 | -1.7 | 0.732501E+10 | 4960.26 | 23-FEB-22:10 | 0.68 | 0.38 |
March | 0.316997E+11 | 37753.96 | 17-MAR-06:03 | 6.02 | 1.23 | 0.799978E+10 | 4884.87 | 22-MAR-22:10 | 5.82 | 1.80 |
April | 0.310391E+11 | 32398.16 | 08-APR-07:23 | 3.30 | -0.3 | 0.769047E+10 | 4902.38 | 06-APR-00:40 | 3.30 | -0.3 |
May | 0.329060E+11 | 45299.96 | 05-MAY-04:20 | 5.60 | 1.69 | 0.797256E+10 | 4838.01 | 01-MAY-22:10 | 5.60 | 1.69 |
June | 0.340693E+11 | 20308.46 | 09-JUN-04:25 | 7.80 | 5.54 | 0.784638E+10 | 4837.38 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.377292E+11 | 20771.22 | 27-JUL-21:00 | 21.70 | 14.57 | 0.815963E+10 | 4837.19 | 21-JUL-21:19 | 21.70 | 14.57 |
August | 0.399816E+11 | 22299.31 | 23-AUG-21:00 | 21.10 | 15.01 | 0.822634E+10 | 4837.20 | 21-AUG-00:40 | 21.10 | 15.01 |
September | 0.412644E+11 | 24026.49 | 08-SEP-21:00 | 16.10 | 12.69 | 0.795899E+10 | 4842.86 | 09-SEP-04:10 | 12.20 | 10.82 |
October | 0.437113E+11 | 40219.80 | 25-OCT-17:36 | 3.57 | 0.12 | 0.822534E+10 | 5031.11 | 27-OCT-01:30 | 3.60 | -0.8 |
November | 0.412255E+11 | 44336.83 | 12-NOV-08:49 | 2.52 | 0.12 | 0.795855E+10 | 5083.87 | 21-NOV-02:00 | 3.30 | -0.8 |
December | 0.402863E+11 | 48441.96 | 11-DEC-09:01 | 2.48 | -1.9 | 0.822406E+10 | 5055.64 | 06-DEC-22:00 | 2.48 | -1.9 |
Annual Sum or Average | 0.440893E+12 | 0.957824E+11 | ||||||||
Minimum of Months | 0.304062E+11 | 20308.46 | 1.67 | -1.9 | 0.732501E+10 | 4837.19 | 0.68 | -3.0 | ||
Maximum of Months | 0.437113E+11 | 51984.29 | 21.70 | 15.01 | 0.822634E+10 | 5083.87 | 26.60 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342883E+10 | 5319.70 | 27-JAN-11:15 | 6.47 | -0.6 | 0.670667E+09 | 448.98 | 02-JAN-22:19 | 6.47 | -0.6 |
February | 0.332954E+10 | 5556.27 | 06-FEB-14:13 | 6.70 | 0.30 | 0.616878E+09 | 474.33 | 14-FEB-22:19 | 10.60 | 3.54 |
March | 0.375123E+10 | 4554.12 | 04-MAR-11:05 | 6.38 | 0.36 | 0.693886E+09 | 472.95 | 08-MAR-22:19 | 10.53 | 4.18 |
April | 0.390109E+10 | 3378.59 | 13-APR-12:50 | 23.62 | 8.92 | 0.706080E+09 | 491.84 | 13-APR-22:10 | 17.75 | 6.12 |
May | 0.399326E+10 | 2643.58 | 13-MAY-13:00 | 28.30 | 11.84 | 0.741193E+09 | 491.84 | 15-MAY-22:10 | 20.32 | 6.87 |
June | 0.449075E+10 | 3057.97 | 29-JUN-14:30 | 37.25 | 15.80 | 0.758278E+09 | 491.86 | 23-JUN-21:10 | 37.25 | 15.80 |
July | 0.522235E+10 | 3260.55 | 22-JUL-13:30 | 36.95 | 17.78 | 0.809012E+09 | 491.85 | 21-JUL-21:19 | 36.95 | 17.78 |
August | 0.557003E+10 | 4042.59 | 22-AUG-13:20 | 31.13 | 16.59 | 0.813187E+09 | 491.85 | 21-AUG-00:10 | 31.13 | 16.59 |
September | 0.549726E+10 | 4851.83 | 28-SEP-13:10 | 29.08 | 15.59 | 0.769068E+09 | 491.89 | 22-SEP-21:00 | 29.08 | 15.59 |
October | 0.523595E+10 | 4929.28 | 05-OCT-12:50 | 25.32 | 13.42 | 0.754463E+09 | 491.84 | 04-OCT-22:10 | 25.32 | 13.42 |
November | 0.423053E+10 | 6209.51 | 28-NOV-10:46 | 4.53 | -0.5 | 0.676981E+09 | 471.36 | 02-NOV-21:19 | 4.53 | -0.5 |
December | 0.354785E+10 | 7406.30 | 31-DEC-10:38 | 2.57 | -2.3 | 0.673487E+09 | 446.39 | 29-DEC-22:10 | 2.57 | -2.3 |
Annual Sum or Average | 0.521987E+11 | 0.868318E+10 | ||||||||
Minimum of Months | 0.332954E+10 | 2643.58 | 2.57 | -2.3 | 0.616878E+09 | 446.39 | 2.57 | -2.3 | ||
Maximum of Months | 0.557003E+10 | 7406.30 | 37.25 | 17.78 | 0.813187E+09 | 491.89 | 37.25 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255317E+10 | 3187.05 | 26-JAN-22:30 | 1.65 | -3.8 | 0.892284E+09 | 585.49 | 23-JAN-22:49 | 1.65 | -3.8 |
February | 0.238120E+10 | 3148.88 | 09-FEB-22:08 | 4.22 | 0.21 | 0.819259E+09 | 586.28 | 09-FEB-22:40 | 3.67 | -0.5 |
March | 0.276609E+10 | 2981.26 | 09-MAR-23:45 | 3.07 | -1.0 | 0.928624E+09 | 583.30 | 09-MAR-23:49 | 3.07 | -1.0 |
April | 0.295768E+10 | 2847.28 | 06-APR-00:58 | 3.30 | -1.5 | 0.917013E+09 | 588.62 | 06-APR-00:40 | 3.30 | -1.5 |
May | 0.321305E+10 | 3690.89 | 02-MAY-04:02 | 6.60 | 3.41 | 0.953320E+09 | 571.36 | 01-MAY-22:49 | 6.60 | 3.41 |
June | 0.352848E+10 | 2338.84 | 28-JUN-20:10 | 29.82 | 16.20 | 0.935090E+09 | 570.49 | 20-JUN-03:00 | 29.82 | 16.20 |
July | 0.387282E+10 | 2401.06 | 21-JUL-21:00 | 30.00 | 14.72 | 0.967397E+09 | 569.64 | 01-JUL-00:40 | 30.00 | 14.72 |
August | 0.387404E+10 | 2339.17 | 18-AUG-20:10 | 27.02 | 13.59 | 0.971719E+09 | 569.56 | 29-AUG-22:49 | 18.07 | 16.08 |
September | 0.352297E+10 | 2187.52 | 13-SEP-20:03 | 23.53 | 12.84 | 0.935966E+09 | 569.60 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.323313E+10 | 4580.18 | 12-OCT-04:20 | 6.30 | 1.73 | 0.949932E+09 | 570.44 | 30-OCT-01:39 | 4.63 | -0.8 |
November | 0.270048E+10 | 3730.61 | 10-NOV-02:10 | 4.50 | 2.13 | 0.895108E+09 | 587.33 | 17-NOV-22:49 | 4.97 | -0.4 |
December | 0.254058E+10 | 3833.21 | 01-DEC-02:27 | 4.05 | -0.8 | 0.893882E+09 | 584.58 | 29-DEC-22:30 | 1.95 | -1.5 |
Annual Sum or Average | 0.371437E+11 | 0.110596E+11 | ||||||||
Minimum of Months | 0.238120E+10 | 2187.52 | 1.65 | -3.8 | 0.819259E+09 | 569.56 | 1.65 | -3.8 | ||
Maximum of Months | 0.387404E+10 | 4580.18 | 30.00 | 16.20 | 0.971719E+09 | 588.62 | 30.00 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146804E+10 | 1577.58 | 15-JAN-21:59 | 1.70 | -1.8 | 0.159647E+09 | 104.29 | 05-JAN-22:00 | 1.70 | -1.8 |
February | 0.143016E+10 | 1582.18 | 21-FEB-00:20 | 2.97 | 0.33 | 0.147160E+09 | 108.85 | 15-FEB-22:10 | 2.97 | 0.33 |
March | 0.177555E+10 | 1666.53 | 12-MAR-00:48 | 3.98 | -1.8 | 0.173306E+09 | 110.40 | 16-MAR-21:10 | 14.17 | 4.07 |
April | 0.193515E+10 | 1626.63 | 06-APR-00:58 | 3.30 | -1.5 | 0.178854E+09 | 120.45 | 28-APR-22:10 | 19.40 | 6.69 |
May | 0.220542E+10 | 1479.80 | 02-MAY-04:02 | 6.60 | 3.41 | 0.194039E+09 | 120.46 | 17-MAY-21:00 | 18.90 | 9.98 |
June | 0.265679E+10 | 1950.24 | 28-JUN-20:00 | 30.00 | 16.25 | 0.196390E+09 | 120.46 | 23-JUN-21:10 | 30.00 | 16.25 |
July | 0.302915E+10 | 1975.85 | 21-JUL-20:00 | 30.60 | 12.57 | 0.204826E+09 | 120.46 | 01-JUL-00:40 | 30.60 | 12.57 |
August | 0.285614E+10 | 1857.12 | 18-AUG-20:00 | 27.20 | 13.67 | 0.205103E+09 | 120.46 | 21-AUG-00:49 | 24.78 | 16.59 |
September | 0.236165E+10 | 1535.31 | 01-SEP-20:00 | 22.80 | 14.95 | 0.194528E+09 | 120.46 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.208265E+10 | 1504.00 | 12-OCT-04:20 | 6.30 | 1.73 | 0.186499E+09 | 120.45 | 04-OCT-22:10 | 6.30 | 1.73 |
November | 0.170028E+10 | 1688.40 | 12-NOV-09:01 | 2.98 | 0.38 | 0.164712E+09 | 111.76 | 02-NOV-21:10 | 2.98 | 0.38 |
December | 0.148505E+10 | 1720.72 | 29-DEC-23:14 | 2.23 | -1.5 | 0.158321E+09 | 104.58 | 01-DEC-22:10 | 2.23 | -1.5 |
Annual Sum or Average | 0.249860E+11 | 0.216339E+10 | ||||||||
Minimum of Months | 0.143016E+10 | 1479.80 | 1.70 | -1.8 | 0.147160E+09 | 104.29 | 1.70 | -1.8 | ||
Maximum of Months | 0.302915E+10 | 1975.85 | 30.60 | 16.25 | 0.205103E+09 | 120.46 | 30.60 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801262E+09 | 1016.55 | 15-JAN-21:59 | 1.70 | -1.8 | 0.118658E+09 | 75.63 | 05-JAN-22:00 | 1.70 | -1.8 |
February | 0.827218E+09 | 1023.59 | 21-FEB-00:20 | 2.97 | 0.33 | 0.108977E+09 | 78.70 | 15-FEB-22:10 | 2.97 | 0.33 |
March | 0.111079E+10 | 1077.40 | 12-MAR-00:48 | 3.98 | -1.8 | 0.127402E+09 | 80.52 | 16-MAR-21:30 | 12.50 | 3.30 |
April | 0.122369E+10 | 1052.19 | 06-APR-00:58 | 3.30 | -1.5 | 0.132011E+09 | 88.46 | 28-APR-21:40 | 19.60 | 6.84 |
May | 0.138267E+10 | 954.96 | 02-MAY-04:02 | 6.60 | 3.41 | 0.143817E+09 | 92.23 | 19-MAY-21:40 | 22.57 | 7.89 |
June | 0.157133E+10 | 1004.77 | 28-JUN-19:10 | 31.83 | 17.06 | 0.148311E+09 | 92.66 | 23-JUN-21:10 | 31.83 | 17.06 |
July | 0.173220E+10 | 1065.01 | 21-JUL-18:30 | 35.25 | 14.38 | 0.156461E+09 | 92.66 | 01-JUL-00:40 | 35.25 | 14.38 |
August | 0.165332E+10 | 927.38 | 18-AUG-18:40 | 31.13 | 15.72 | 0.155927E+09 | 92.66 | 21-AUG-00:49 | 24.78 | 16.59 |
September | 0.144478E+10 | 717.42 | 03-SEP-10:35 | 28.53 | 16.32 | 0.145301E+09 | 92.66 | 01-SEP-22:10 | 28.53 | 16.32 |
October | 0.130475E+10 | 969.26 | 12-OCT-04:20 | 6.30 | 1.73 | 0.137706E+09 | 91.39 | 02-OCT-21:30 | 6.30 | 1.73 |
November | 0.105954E+10 | 1092.04 | 12-NOV-09:01 | 2.98 | 0.38 | 0.121032E+09 | 81.30 | 02-NOV-21:30 | 2.98 | 0.38 |
December | 0.769580E+09 | 1114.03 | 29-DEC-23:14 | 2.23 | -1.5 | 0.118239E+09 | 75.81 | 01-DEC-22:30 | 2.23 | -1.5 |
Annual Sum or Average | 0.148811E+11 | 0.161384E+10 | ||||||||
Minimum of Months | 0.769580E+09 | 717.42 | 1.70 | -1.8 | 0.108977E+09 | 75.63 | 1.70 | -1.8 | ||
Maximum of Months | 0.173220E+10 | 1114.03 | 35.25 | 17.06 | 0.156461E+09 | 92.66 | 35.25 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485735E+11 | 57167.26 | 08-JAN-19:58 | 1.10 | -2.1 | 0.622843E+09 | 552.64 | 23-JAN-22:49 | 1.60 | -3.0 |
February | 0.442477E+11 | 54893.61 | 02-FEB-19:23 | 1.40 | -2.2 | 0.563226E+09 | 497.73 | 23-FEB-22:10 | 0.68 | 0.38 |
March | 0.501382E+11 | 52901.80 | 04-MAR-21:57 | 1.70 | -2.4 | 0.627442E+09 | 477.31 | 22-MAR-23:19 | 4.03 | 0.85 |
April | 0.496476E+11 | 45710.74 | 05-APR-06:46 | 4.50 | -2.0 | 0.607016E+09 | 438.80 | 05-APR-04:40 | 4.50 | -2.0 |
May | 0.520668E+11 | 39020.06 | 19-MAY-20:00 | 25.60 | 9.31 | 0.626643E+09 | 430.15 | 05-MAY-04:49 | 25.60 | 9.31 |
June | 0.516281E+11 | 39541.62 | 28-JUN-20:00 | 30.00 | 16.25 | 0.609428E+09 | 382.01 | 23-JUN-21:10 | 30.00 | 16.25 |
July | 0.536596E+11 | 39565.06 | 21-JUL-20:00 | 30.60 | 12.57 | 0.628797E+09 | 382.00 | 13-JUL-21:10 | 30.60 | 12.57 |
August | 0.536331E+11 | 39395.01 | 17-AUG-20:00 | 28.30 | 14.86 | 0.629831E+09 | 382.03 | 30-AUG-21:10 | 23.72 | 13.61 |
September | 0.509506E+11 | 38999.57 | 01-SEP-20:00 | 22.80 | 14.95 | 0.605975E+09 | 381.94 | 11-SEP-21:10 | 21.52 | 12.92 |
October | 0.512205E+11 | 51481.39 | 25-OCT-20:50 | 3.30 | -0.3 | 0.622821E+09 | 442.18 | 27-OCT-01:30 | 3.60 | -0.8 |
November | 0.481112E+11 | 51088.74 | 27-NOV-20:13 | 1.70 | -1.7 | 0.603694E+09 | 501.14 | 17-NOV-22:49 | 1.70 | -1.7 |
December | 0.484147E+11 | 57683.31 | 15-DEC-20:55 | 1.70 | -4.6 | 0.623510E+09 | 549.60 | 06-DEC-22:00 | 1.70 | -4.6 |
Annual Sum or Average | 0.602292E+12 | 0.737123E+10 | ||||||||
Minimum of Months | 0.442477E+11 | 38999.57 | 1.10 | -4.6 | 0.563226E+09 | 381.94 | 0.68 | -4.6 | ||
Maximum of Months | 0.536596E+11 | 57683.31 | 30.60 | 16.25 | 0.629831E+09 | 552.64 | 30.60 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195788E+11 | 22112.13 | 08-JAN-10:08 | 4.97 | 0.88 | 0.103342E+11 | 7012.43 | 23-JAN-22:49 | 1.60 | -3.0 |
February | 0.182241E+11 | 22355.62 | 04-FEB-13:13 | 4.60 | -1.6 | 0.946623E+10 | 6924.87 | 09-FEB-22:40 | 3.67 | -0.5 |
March | 0.197139E+11 | 21192.70 | 04-MAR-11:05 | 6.38 | 0.36 | 0.106552E+11 | 7093.09 | 27-MAR-03:20 | 5.40 | 0.78 |
April | 0.196546E+11 | 18817.32 | 07-APR-02:26 | 4.40 | -1.5 | 0.104516E+11 | 7085.87 | 06-APR-00:40 | 4.40 | -1.5 |
May | 0.200072E+11 | 27090.75 | 02-MAY-04:02 | 6.60 | 3.41 | 0.108157E+11 | 6555.45 | 06-MAY-03:20 | 6.83 | -0.6 |
June | 0.212766E+11 | 11980.71 | 27-JUN-21:10 | 28.85 | 14.13 | 0.105837E+11 | 6485.90 | 20-JUN-03:00 | 28.85 | 14.13 |
July | 0.239445E+11 | 12246.60 | 21-JUL-21:10 | 29.72 | 14.71 | 0.109615E+11 | 6463.33 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.251131E+11 | 13390.85 | 20-AUG-12:00 | 32.80 | 17.08 | 0.110082E+11 | 6462.71 | 23-AUG-22:10 | 19.40 | 14.62 |
September | 0.246777E+11 | 15534.67 | 28-SEP-13:10 | 29.08 | 15.59 | 0.106106E+11 | 6482.01 | 09-SEP-04:10 | 29.08 | 15.59 |
October | 0.244120E+11 | 19118.48 | 30-OCT-03:14 | 4.43 | -0.8 | 0.108190E+11 | 7029.95 | 27-OCT-01:30 | 4.43 | -0.8 |
November | 0.211558E+11 | 25097.83 | 28-NOV-10:46 | 4.53 | -0.5 | 0.103213E+11 | 7165.89 | 07-NOV-02:09 | 4.53 | -0.5 |
December | 0.200850E+11 | 30813.66 | 31-DEC-10:38 | 2.57 | -2.3 | 0.103872E+11 | 6937.87 | 01-DEC-03:30 | 2.57 | -2.3 |
Annual Sum or Average | 0.257843E+12 | 0.126414E+12 | ||||||||
Minimum of Months | 0.182241E+11 | 11980.71 | 2.57 | -2.3 | 0.946623E+10 | 6462.71 | 1.60 | -3.0 | ||
Maximum of Months | 0.251131E+11 | 30813.66 | 32.80 | 17.08 | 0.110082E+11 | 7165.89 | 29.72 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.566150E+11 | 64334.80 | 24-JAN-21:43 | 1.28 | -3.4 | 0.317639E+11 | 20253.74 | 23-JAN-22:49 | 1.28 | -3.4 |
February | 0.526444E+11 | 64780.88 | 21-FEB-00:48 | 3.22 | 0.43 | 0.289387E+11 | 19979.84 | 09-FEB-22:40 | 3.22 | 0.43 |
March | 0.606854E+11 | 69769.95 | 26-MAR-01:22 | 4.45 | -0.6 | 0.323591E+11 | 20852.64 | 27-MAR-03:20 | 5.40 | 0.78 |
April | 0.631740E+11 | 63730.60 | 04-APR-01:51 | 5.60 | -1.5 | 0.313600E+11 | 20732.29 | 04-APR-04:30 | 3.85 | -1.9 |
May | 0.676760E+11 | 59520.88 | 02-MAY-02:37 | 6.50 | 3.69 | 0.324247E+11 | 19971.25 | 05-MAY-04:49 | 5.60 | 1.69 |
June | 0.720912E+11 | 42363.25 | 28-JUN-21:10 | 28.62 | 15.82 | 0.315784E+11 | 19231.15 | 20-JUN-03:00 | 28.62 | 15.82 |
July | 0.786951E+11 | 43032.21 | 21-JUL-21:10 | 29.72 | 14.71 | 0.325989E+11 | 19188.68 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.795405E+11 | 42404.54 | 18-AUG-21:10 | 25.73 | 12.99 | 0.327508E+11 | 19186.16 | 23-AUG-22:10 | 19.40 | 14.62 |
September | 0.747353E+11 | 40881.51 | 13-SEP-20:03 | 23.53 | 12.84 | 0.316058E+11 | 19224.04 | 09-SEP-04:10 | 23.53 | 12.84 |
October | 0.707810E+11 | 85692.07 | 22-OCT-05:16 | 7.60 | 5.17 | 0.324853E+11 | 20274.47 | 27-OCT-01:30 | 3.60 | -0.8 |
November | 0.605901E+11 | 67469.16 | 15-NOV-18:10 | 5.50 | 1.89 | 0.312291E+11 | 20747.15 | 21-NOV-02:00 | 3.30 | -0.8 |
December | 0.568162E+11 | 94848.37 | 01-DEC-01:00 | 4.80 | -0.5 | 0.318442E+11 | 20024.42 | 01-DEC-03:30 | 3.55 | -0.9 |
Annual Sum or Average | 0.794044E+12 | 0.380939E+12 | ||||||||
Minimum of Months | 0.526444E+11 | 40881.51 | 1.28 | -3.4 | 0.289387E+11 | 19186.16 | 1.28 | -3.4 | ||
Maximum of Months | 0.795405E+11 | 94848.37 | 29.72 | 15.82 | 0.327508E+11 | 20852.64 | 29.72 | 15.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394131E+09 | 4930.65 | 05-JAN-17:01 | 12.85 | 5.27 | 96413442.67 | 56.69 | 02-JAN-22:10 | 12.85 | 5.27 |
February | 0.513257E+09 | 5148.69 | 15-FEB-18:01 | 12.23 | 3.61 | 88118224.89 | 60.33 | 14-FEB-19:10 | 12.23 | 3.61 |
March | 0.731598E+09 | 5319.19 | 30-MAR-18:11 | 13.50 | 4.61 | 0.100836E+09 | 78.30 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.128966E+10 | 5584.06 | 25-APR-16:21 | 24.40 | 9.58 | 0.102693E+09 | 82.11 | 25-APR-21:30 | 18.35 | 6.56 |
May | 0.167223E+10 | 5206.44 | 06-MAY-19:41 | 14.18 | 3.71 | 0.105205E+09 | 88.19 | 26-MAY-21:10 | 17.62 | 10.50 |
June | 0.239638E+10 | 5204.79 | 13-JUN-21:51 | 22.20 | 10.36 | 0.100081E+09 | 88.01 | 09-JUN-21:10 | 22.20 | 10.36 |
July | 0.274777E+10 | 4779.90 | 20-JUL-18:02 | 35.73 | 14.77 | 0.103389E+09 | 86.10 | 31-JUL-21:19 | 21.63 | 17.69 |
August | 0.270992E+10 | 4709.34 | 23-AUG-17:21 | 24.15 | 16.31 | 0.104802E+09 | 91.44 | 23-AUG-21:10 | 20.82 | 14.97 |
September | 0.218056E+10 | 5178.16 | 26-SEP-21:51 | 18.30 | 8.74 | 0.103688E+09 | 84.06 | 12-SEP-21:10 | 18.30 | 8.74 |
October | 0.148052E+10 | 5285.26 | 17-OCT-19:21 | 14.15 | 5.78 | 0.106135E+09 | 87.44 | 19-OCT-21:10 | 15.60 | 9.18 |
November | 0.703684E+09 | 4699.98 | 01-NOV-15:01 | 12.43 | 7.32 | 94571615.26 | 62.41 | 02-NOV-18:10 | 15.00 | 8.23 |
December | 0.345489E+09 | 4699.81 | 05-DEC-16:01 | 6.02 | 0.20 | 96313047.66 | 56.69 | 25-DEC-04:40 | 5.03 | 0.33 |
Annual Sum or Average | 0.171652E+11 | 0.120225E+10 | ||||||||
Minimum of Months | 0.345489E+09 | 4699.81 | 6.02 | 0.20 | 88118224.89 | 56.69 | 5.03 | 0.33 | ||
Maximum of Months | 0.274777E+10 | 5584.06 | 35.73 | 16.31 | 0.106135E+09 | 91.44 | 22.20 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116557E+09 | 4494.25 | 06-JAN-16:01 | 8.77 | 2.64 | 94426487.58 | 56.69 | 24-JAN-22:10 | 0.73 | -3.6 |
February | 0.202210E+09 | 4604.93 | 14-FEB-16:01 | 22.02 | 7.76 | 86379647.29 | 56.69 | 14-FEB-22:10 | 10.60 | 3.54 |
March | 0.399870E+09 | 5251.12 | 30-MAR-18:11 | 13.50 | 4.61 | 98998080.51 | 72.40 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.103365E+10 | 5515.95 | 25-APR-16:21 | 24.40 | 9.58 | 0.101503E+09 | 80.04 | 25-APR-21:30 | 18.35 | 6.56 |
May | 0.156723E+10 | 5128.28 | 20-MAY-21:51 | 21.10 | 7.48 | 0.104911E+09 | 87.88 | 26-MAY-21:10 | 17.62 | 10.50 |
June | 0.238932E+10 | 5165.93 | 13-JUN-21:51 | 22.20 | 10.36 | 0.100300E+09 | 88.23 | 09-JUN-21:10 | 22.20 | 10.36 |
July | 0.267212E+10 | 4746.91 | 20-JUL-18:02 | 35.73 | 14.77 | 0.103488E+09 | 85.43 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.248066E+10 | 4711.22 | 23-AUG-17:21 | 24.15 | 16.31 | 0.104572E+09 | 90.20 | 23-AUG-21:10 | 20.82 | 14.97 |
September | 0.175251E+10 | 4981.88 | 21-SEP-21:51 | 18.90 | 9.64 | 0.102666E+09 | 81.27 | 12-SEP-21:10 | 18.90 | 9.64 |
October | 0.926647E+09 | 4935.57 | 05-OCT-21:51 | 19.40 | 9.99 | 0.103374E+09 | 79.27 | 04-OCT-21:10 | 19.40 | 9.99 |
November | 0.235807E+09 | 4565.13 | 02-NOV-15:01 | 17.12 | 9.39 | 92888195.21 | 56.69 | 01-NOV-01:39 | 17.12 | 9.39 |
December | 88973457.94 | 4454.94 | 29-DEC-16:01 | 11.42 | 3.74 | 94021509.40 | 56.69 | 25-DEC-01:39 | 11.42 | 3.74 |
Annual Sum or Average | 0.138656E+11 | 0.118753E+10 | ||||||||
Minimum of Months | 88973457.94 | 4454.94 | 8.77 | 2.64 | 86379647.29 | 56.69 | 0.73 | -3.6 | ||
Maximum of Months | 0.267212E+10 | 5515.95 | 35.73 | 16.31 | 0.104911E+09 | 90.20 | 22.20 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532995E+09 | 838.15 | 03-JAN-12:40 | 13.17 | 5.04 | 0.00 | 0.00 | 01-JAN-00:10 | 13.17 | 5.04 |
February | 0.501369E+09 | 859.25 | 14-FEB-13:00 | 19.40 | 6.65 | 0.00 | 0.00 | 01-FEB-00:10 | 19.40 | 6.65 |
March | 0.486938E+09 | 732.33 | 08-MAR-13:30 | 21.40 | 9.29 | 0.00 | 0.00 | 01-MAR-00:10 | 21.40 | 9.29 |
April | 0.491962E+09 | 558.26 | 13-APR-13:20 | 24.07 | 9.13 | 0.00 | 0.00 | 01-APR-00:10 | 24.07 | 9.13 |
May | 0.479485E+09 | 409.55 | 13-MAY-13:10 | 28.40 | 11.85 | 0.00 | 0.00 | 01-MAY-00:10 | 28.40 | 11.85 |
June | 0.599789E+09 | 452.02 | 29-JUN-14:30 | 37.25 | 15.80 | 0.00 | 0.00 | 01-JUN-00:10 | 37.25 | 15.80 |
July | 0.772221E+09 | 497.01 | 23-JUL-13:30 | 36.15 | 17.47 | 0.00 | 0.00 | 01-JUL-00:10 | 36.15 | 17.47 |
August | 0.836760E+09 | 630.00 | 22-AUG-13:30 | 31.40 | 16.68 | 0.00 | 0.00 | 01-AUG-00:10 | 31.40 | 16.68 |
September | 0.847093E+09 | 800.65 | 28-SEP-13:20 | 29.27 | 15.43 | 0.00 | 0.00 | 01-SEP-00:10 | 29.27 | 15.43 |
October | 0.826194E+09 | 859.24 | 19-OCT-12:30 | 20.55 | 8.60 | 0.00 | 0.00 | 01-OCT-00:10 | 20.55 | 8.60 |
November | 0.675607E+09 | 845.22 | 20-NOV-12:10 | 12.88 | 3.87 | 0.00 | 0.00 | 01-NOV-00:10 | 12.88 | 3.87 |
December | 0.575292E+09 | 847.06 | 31-DEC-13:35 | 9.43 | 1.41 | 0.00 | 0.00 | 01-DEC-00:10 | 9.43 | 1.41 |
Annual Sum or Average | 0.762570E+10 | 0.00 | ||||||||
Minimum of Months | 0.479485E+09 | 409.55 | 9.43 | 1.41 | 0.00 | 0.00 | 9.43 | 1.41 | ||
Maximum of Months | 0.847093E+09 | 859.25 | 37.25 | 17.47 | 0.00 | 0.00 | 37.25 | 17.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68965796.14 | 327.30 | 06-JAN-19:03 | 2.62 | -1.2 | 94583525.84 | 56.69 | 06-JAN-22:10 | 0.73 | -2.0 |
February | 0.102292E+09 | 1293.07 | 14-FEB-19:01 | 12.93 | 4.07 | 85814404.26 | 56.69 | 14-FEB-22:10 | 10.60 | 3.54 |
March | 0.244446E+09 | 1383.57 | 13-MAR-20:41 | 12.35 | 3.74 | 96340092.05 | 59.19 | 13-MAR-20:40 | 12.35 | 3.74 |
April | 0.431493E+09 | 1491.33 | 27-APR-21:51 | 17.80 | 7.06 | 96526936.98 | 73.30 | 27-APR-21:49 | 17.80 | 7.06 |
May | 0.616343E+09 | 1509.48 | 20-MAY-21:51 | 21.10 | 7.48 | 0.101285E+09 | 75.90 | 26-MAY-21:49 | 16.88 | 10.38 |
June | 0.850634E+09 | 1542.30 | 18-JUN-08:51 | 25.60 | 11.91 | 98252941.31 | 76.01 | 05-JUN-21:49 | 25.60 | 11.91 |
July | 0.950695E+09 | 1463.17 | 04-JUL-18:02 | 33.62 | 13.65 | 0.102107E+09 | 78.27 | 31-JUL-21:49 | 21.53 | 17.38 |
August | 0.860841E+09 | 1354.58 | 22-AUG-21:51 | 20.60 | 15.18 | 0.102412E+09 | 78.20 | 23-AUG-21:40 | 19.97 | 14.83 |
September | 0.625630E+09 | 1509.18 | 30-SEP-21:51 | 18.00 | 8.68 | 99433935.24 | 74.75 | 12-SEP-21:10 | 18.00 | 8.68 |
October | 0.382113E+09 | 1470.87 | 05-OCT-21:51 | 19.40 | 9.99 | 98680235.36 | 74.38 | 02-OCT-21:49 | 19.40 | 9.99 |
November | 0.152048E+09 | 1324.37 | 02-NOV-18:11 | 15.00 | 7.63 | 92268375.66 | 56.69 | 01-NOV-00:00 | 15.00 | 7.63 |
December | 61638786.91 | 761.71 | 03-DEC-09:01 | 4.32 | -1.8 | 94288775.88 | 56.69 | 19-DEC-22:10 | 2.02 | -3.5 |
Annual Sum or Average | 0.534714E+10 | 0.116199E+10 | ||||||||
Minimum of Months | 61638786.91 | 327.30 | 2.62 | -1.8 | 85814404.26 | 56.69 | 0.73 | -3.5 | ||
Maximum of Months | 0.950695E+09 | 1542.30 | 33.62 | 15.18 | 0.102412E+09 | 78.27 | 25.60 | 17.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388758E+09 | 4202.73 | 29-JAN-09:01 | 2.85 | 0.18 | 96722578.44 | 56.69 | 02-JAN-22:10 | 2.85 | 0.18 |
February | 0.474795E+09 | 4237.05 | 14-FEB-19:01 | 12.93 | 4.07 | 88124488.94 | 56.69 | 14-FEB-23:00 | 10.00 | 3.44 |
March | 0.845992E+09 | 4303.21 | 13-MAR-20:41 | 12.35 | 3.74 | 99801821.35 | 66.86 | 13-MAR-20:30 | 12.35 | 3.74 |
April | 0.153853E+10 | 4980.43 | 28-APR-08:51 | 18.30 | 7.75 | 0.100634E+09 | 79.41 | 27-APR-21:40 | 18.30 | 7.75 |
May | 0.186357E+10 | 5005.28 | 14-MAY-08:51 | 21.10 | 9.79 | 0.104734E+09 | 79.66 | 26-MAY-21:30 | 17.25 | 10.44 |
June | 0.254573E+10 | 5037.21 | 14-JUN-08:21 | 26.10 | 11.81 | 0.101618E+09 | 80.10 | 13-JUN-21:00 | 26.10 | 11.81 |
July | 0.293908E+10 | 4639.43 | 13-JUL-08:32 | 25.77 | 16.35 | 0.105629E+09 | 84.33 | 31-JUL-21:19 | 21.63 | 17.69 |
August | 0.283822E+10 | 4690.88 | 03-AUG-08:32 | 23.50 | 15.48 | 0.106489E+09 | 85.69 | 03-AUG-21:19 | 23.13 | 13.71 |
September | 0.221809E+10 | 4589.49 | 02-SEP-08:32 | 21.67 | 14.85 | 0.104125E+09 | 83.42 | 11-SEP-21:19 | 21.33 | 12.92 |
October | 0.155108E+10 | 4534.04 | 05-OCT-21:51 | 19.40 | 9.99 | 0.104058E+09 | 82.50 | 02-OCT-21:40 | 19.40 | 9.99 |
November | 0.710132E+09 | 4203.25 | 22-NOV-09:01 | 5.47 | 1.09 | 94794047.52 | 56.69 | 01-NOV-02:20 | 5.47 | 1.09 |
December | 0.341720E+09 | 4220.17 | 29-DEC-09:01 | 1.38 | -1.1 | 96624313.85 | 56.69 | 25-DEC-02:30 | 1.38 | -1.1 |
Annual Sum or Average | 0.182557E+11 | 0.120335E+10 | ||||||||
Minimum of Months | 0.341720E+09 | 4202.73 | 1.38 | -1.1 | 88124488.94 | 56.69 | 1.38 | -1.1 | ||
Maximum of Months | 0.293908E+10 | 5037.21 | 26.10 | 16.35 | 0.106489E+09 | 85.69 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117219E+09 | 3941.18 | 29-JAN-09:01 | 2.85 | 0.18 | 94369532.96 | 56.69 | 06-JAN-22:10 | 2.85 | 0.18 |
February | 0.177885E+09 | 4079.42 | 14-FEB-09:01 | 7.25 | 1.90 | 86090451.40 | 56.69 | 15-FEB-04:30 | 7.50 | 2.54 |
March | 0.486414E+09 | 4201.66 | 11-MAR-09:01 | 6.23 | 0.26 | 98444857.16 | 62.17 | 13-MAR-20:30 | 13.65 | 4.40 |
April | 0.125975E+10 | 4930.73 | 28-APR-08:51 | 18.30 | 7.75 | 0.100006E+09 | 77.92 | 27-APR-21:40 | 18.30 | 7.75 |
May | 0.175019E+10 | 4963.13 | 14-MAY-08:51 | 21.10 | 9.79 | 0.104582E+09 | 79.54 | 26-MAY-21:30 | 17.25 | 10.44 |
June | 0.253599E+10 | 5136.01 | 14-JUN-08:62 | 25.37 | 11.65 | 0.101815E+09 | 80.35 | 13-JUN-21:00 | 25.37 | 11.65 |
July | 0.286193E+10 | 4611.04 | 13-JUL-08:32 | 25.77 | 16.35 | 0.105704E+09 | 83.62 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.260523E+10 | 4658.65 | 03-AUG-08:32 | 23.50 | 15.48 | 0.106277E+09 | 85.03 | 03-AUG-21:10 | 23.22 | 13.75 |
September | 0.177889E+10 | 4557.26 | 02-SEP-08:32 | 21.67 | 14.85 | 0.103185E+09 | 80.39 | 12-SEP-21:10 | 21.32 | 12.19 |
October | 0.969335E+09 | 4331.14 | 05-OCT-21:51 | 19.40 | 9.99 | 0.101957E+09 | 78.82 | 02-OCT-21:40 | 19.40 | 9.99 |
November | 0.254624E+09 | 4062.34 | 22-NOV-09:01 | 5.47 | 1.09 | 92839308.85 | 56.69 | 01-NOV-00:49 | 5.47 | 1.09 |
December | 94403150.93 | 3918.72 | 29-DEC-09:01 | 1.38 | -1.1 | 93841459.91 | 56.69 | 26-DEC-22:19 | 1.38 | -1.1 |
Annual Sum or Average | 0.148919E+11 | 0.118911E+10 | ||||||||
Minimum of Months | 94403150.93 | 3918.72 | 1.38 | -1.1 | 86090451.40 | 56.69 | 1.38 | -1.1 | ||
Maximum of Months | 0.286193E+10 | 5136.01 | 25.77 | 16.35 | 0.106277E+09 | 85.03 | 25.37 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309107E+10 | 3263.88 | 26-JAN-23:27 | 1.95 | -3.5 | 0.126895E+10 | 825.12 | 02-JAN-22:40 | 1.95 | -3.5 |
February | 0.301925E+10 | 3280.56 | 21-FEB-00:20 | 2.97 | 0.33 | 0.116720E+10 | 855.22 | 15-FEB-22:00 | 2.97 | 0.33 |
March | 0.371629E+10 | 3505.89 | 12-MAR-00:48 | 3.98 | -1.8 | 0.137333E+10 | 875.74 | 13-MAR-21:40 | 12.43 | 3.82 |
April | 0.408901E+10 | 3413.48 | 06-APR-00:58 | 3.30 | -1.5 | 0.142939E+10 | 940.76 | 28-APR-22:10 | 19.40 | 6.69 |
May | 0.450476E+10 | 3117.04 | 02-MAY-04:02 | 6.60 | 3.41 | 0.152936E+10 | 951.86 | 17-MAY-21:00 | 18.90 | 9.98 |
June | 0.504247E+10 | 3269.75 | 23-JUN-18:15 | 33.17 | 12.63 | 0.154196E+10 | 951.90 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.559568E+10 | 3445.58 | 21-JUL-18:30 | 35.25 | 14.38 | 0.161457E+10 | 951.89 | 01-JUL-00:40 | 35.25 | 14.38 |
August | 0.563555E+10 | 3240.38 | 18-AUG-18:15 | 31.67 | 15.79 | 0.162073E+10 | 951.87 | 21-AUG-00:49 | 24.78 | 16.59 |
September | 0.502060E+10 | 2675.60 | 13-SEP-15:03 | 28.30 | 14.80 | 0.154988E+10 | 951.90 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.455130E+10 | 3167.74 | 12-OCT-04:20 | 6.30 | 1.73 | 0.151593E+10 | 951.85 | 19-OCT-21:00 | 15.60 | 9.18 |
November | 0.360461E+10 | 3484.53 | 12-NOV-09:01 | 2.98 | 0.38 | 0.131551E+10 | 879.85 | 02-NOV-21:40 | 2.98 | 0.38 |
December | 0.308749E+10 | 3558.72 | 29-DEC-23:14 | 2.23 | -1.5 | 0.125287E+10 | 801.32 | 01-DEC-03:09 | 2.23 | -1.5 |
Annual Sum or Average | 0.509581E+11 | 0.171797E+11 | ||||||||
Minimum of Months | 0.301925E+10 | 2675.60 | 1.95 | -3.5 | 0.116720E+10 | 801.32 | 1.95 | -3.5 | ||
Maximum of Months | 0.563555E+10 | 3558.72 | 35.25 | 15.79 | 0.162073E+10 | 951.90 | 35.25 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369264E+09 | 5315.49 | 05-JAN-17:01 | 12.85 | 5.27 | 96007260.05 | 56.69 | 06-JAN-22:10 | 0.73 | -2.0 |
February | 0.498040E+09 | 5562.21 | 15-FEB-18:01 | 12.23 | 3.61 | 87935805.46 | 63.88 | 14-FEB-19:10 | 12.23 | 3.61 |
March | 0.686281E+09 | 5757.99 | 30-MAR-18:11 | 13.50 | 4.61 | 0.101058E+09 | 86.83 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.127576E+10 | 5909.35 | 25-APR-16:21 | 24.40 | 9.58 | 0.103585E+09 | 89.07 | 24-APR-18:10 | 24.40 | 9.58 |
May | 0.168279E+10 | 5638.20 | 06-MAY-19:41 | 14.18 | 3.71 | 0.105423E+09 | 94.38 | 26-MAY-21:10 | 17.62 | 10.50 |
June | 0.248763E+10 | 5467.15 | 13-JUN-21:51 | 22.20 | 10.36 | 0.100051E+09 | 93.84 | 09-JUN-21:10 | 22.20 | 10.36 |
July | 0.287898E+10 | 5062.79 | 21-JUL-18:02 | 35.82 | 14.43 | 0.103027E+09 | 86.90 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.282348E+10 | 4981.13 | 23-AUG-17:02 | 24.32 | 16.96 | 0.104544E+09 | 94.81 | 23-AUG-21:10 | 20.82 | 14.97 |
September | 0.218653E+10 | 5438.34 | 26-SEP-21:51 | 18.30 | 8.74 | 0.103380E+09 | 84.23 | 11-SEP-21:30 | 18.30 | 8.74 |
October | 0.140530E+10 | 5712.20 | 17-OCT-19:21 | 14.15 | 5.78 | 0.106805E+09 | 90.82 | 19-OCT-21:10 | 15.60 | 9.18 |
November | 0.619560E+09 | 4952.84 | 02-NOV-15:01 | 17.12 | 9.39 | 94238032.66 | 66.61 | 02-NOV-18:10 | 15.00 | 8.23 |
December | 0.317713E+09 | 4960.82 | 05-DEC-16:01 | 6.02 | 0.20 | 95894517.70 | 56.69 | 26-DEC-00:20 | 1.67 | 0.04 |
Annual Sum or Average | 0.172313E+11 | 0.120195E+10 | ||||||||
Minimum of Months | 0.317713E+09 | 4952.84 | 6.02 | 0.20 | 87935805.46 | 56.69 | 0.73 | -2.0 | ||
Maximum of Months | 0.287898E+10 | 5909.35 | 35.82 | 16.96 | 0.106805E+09 | 94.81 | 24.40 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104467E+09 | 4711.72 | 05-JAN-17:01 | 12.85 | 5.27 | 93917431.41 | 56.69 | 06-JAN-22:10 | 0.73 | -2.0 |
February | 0.186638E+09 | 4845.89 | 14-FEB-19:01 | 12.93 | 4.07 | 86072255.27 | 56.69 | 15-FEB-04:30 | 7.50 | 2.54 |
March | 0.361864E+09 | 5591.38 | 30-MAR-18:11 | 13.50 | 4.61 | 99029888.33 | 78.65 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.100158E+10 | 5826.04 | 25-APR-16:21 | 24.40 | 9.58 | 0.102256E+09 | 86.61 | 24-APR-18:10 | 24.40 | 9.58 |
May | 0.157012E+10 | 5558.94 | 06-MAY-19:41 | 14.18 | 3.71 | 0.105155E+09 | 94.25 | 26-MAY-21:10 | 17.62 | 10.50 |
June | 0.248065E+10 | 5421.23 | 13-JUN-21:51 | 22.20 | 10.36 | 0.100269E+09 | 95.58 | 09-JUN-18:49 | 22.20 | 10.36 |
July | 0.280107E+10 | 5020.52 | 21-JUL-18:02 | 35.82 | 14.43 | 0.103114E+09 | 86.27 | 31-JUL-21:40 | 21.57 | 17.49 |
August | 0.258171E+10 | 4907.00 | 23-AUG-17:21 | 24.15 | 16.31 | 0.104292E+09 | 93.41 | 23-AUG-21:10 | 20.82 | 14.97 |
September | 0.172910E+10 | 5197.94 | 21-SEP-21:51 | 18.90 | 9.64 | 0.102288E+09 | 80.79 | 12-SEP-21:10 | 18.90 | 9.64 |
October | 0.827164E+09 | 5357.57 | 13-OCT-17:41 | 14.60 | 3.63 | 0.103482E+09 | 78.87 | 04-OCT-21:10 | 14.60 | 3.63 |
November | 0.190999E+09 | 4786.94 | 02-NOV-15:01 | 17.12 | 9.39 | 92345487.82 | 58.23 | 02-NOV-18:10 | 15.00 | 8.23 |
December | 73787262.93 | 4672.95 | 31-DEC-16:01 | 9.82 | 1.41 | 93524739.63 | 56.69 | 15-DEC-22:30 | 9.82 | 1.41 |
Annual Sum or Average | 0.139091E+11 | 0.118574E+10 | ||||||||
Minimum of Months | 73787262.93 | 4672.95 | 9.82 | 1.41 | 86072255.27 | 56.69 | 0.73 | -2.0 | ||
Maximum of Months | 0.280107E+10 | 5826.04 | 35.82 | 16.31 | 0.105155E+09 | 95.58 | 24.40 | 17.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.806419E+09 | 2616.97 | 05-JAN-17:01 | 12.85 | 5.27 | 97801018.88 | 56.69 | 09-JAN-22:40 | 6.30 | 0.49 |
February | 0.775862E+09 | 2705.24 | 14-FEB-19:01 | 12.93 | 4.07 | 89085378.13 | 68.93 | 14-FEB-19:10 | 12.93 | 4.07 |
March | 0.743247E+09 | 2672.79 | 12-MAR-19:31 | 12.60 | 3.42 | 0.100584E+09 | 74.33 | 13-MAR-20:30 | 13.65 | 4.40 |
April | 0.808149E+09 | 2673.10 | 12-APR-16:21 | 24.40 | 9.38 | 99977392.09 | 79.91 | 13-APR-21:40 | 19.23 | 6.82 |
May | 0.858547E+09 | 2470.06 | 20-MAY-21:51 | 21.10 | 7.48 | 0.102888E+09 | 78.07 | 26-MAY-21:40 | 17.07 | 10.41 |
June | 0.115935E+10 | 2486.54 | 18-JUN-08:51 | 25.60 | 11.91 | 98603262.56 | 77.79 | 02-JUN-21:40 | 25.60 | 11.91 |
July | 0.148418E+10 | 2329.17 | 21-JUL-18:02 | 35.82 | 14.43 | 0.102667E+09 | 82.62 | 31-JUL-21:40 | 21.57 | 17.49 |
August | 0.158241E+10 | 2370.47 | 29-AUG-16:31 | 24.07 | 16.33 | 0.103793E+09 | 84.78 | 22-AUG-21:40 | 24.07 | 16.33 |
September | 0.149824E+10 | 2617.08 | 26-SEP-21:51 | 18.30 | 8.74 | 0.103165E+09 | 86.15 | 11-SEP-21:40 | 18.30 | 8.74 |
October | 0.136524E+10 | 2737.09 | 17-OCT-19:21 | 14.15 | 5.78 | 0.106879E+09 | 97.52 | 19-OCT-21:10 | 15.60 | 9.18 |
November | 0.105425E+10 | 2377.41 | 01-NOV-15:01 | 12.43 | 7.32 | 95407605.47 | 65.46 | 02-NOV-18:10 | 15.00 | 8.23 |
December | 0.883372E+09 | 2373.83 | 05-DEC-16:01 | 6.02 | 0.20 | 97710879.82 | 56.69 | 18-DEC-22:00 | 1.70 | -2.4 |
Annual Sum or Average | 0.130193E+11 | 0.119856E+10 | ||||||||
Minimum of Months | 0.743247E+09 | 2329.17 | 6.02 | 0.20 | 89085378.13 | 56.69 | 1.70 | -2.4 | ||
Maximum of Months | 0.158241E+10 | 2737.09 | 35.82 | 16.33 | 0.106879E+09 | 97.52 | 25.60 | 17.49 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310268E+11 | 34542.29 | 30-JAN-23:24 | 3.60 | -0.3 | 0.191670E+11 | 13095.68 | 23-JAN-22:49 | 3.60 | -0.3 |
February | 0.291288E+11 | 32894.83 | 27-FEB-23:54 | 2.20 | -0.3 | 0.173675E+11 | 12523.61 | 09-FEB-22:40 | 2.20 | -0.3 |
March | 0.350109E+11 | 38754.70 | 03-MAR-23:51 | 1.70 | -2.0 | 0.193834E+11 | 13744.88 | 27-MAR-03:20 | 5.40 | 0.78 |
April | 0.373984E+11 | 36144.84 | 19-APR-04:42 | 3.80 | 0.98 | 0.187337E+11 | 13473.90 | 04-APR-04:30 | 3.80 | 0.98 |
May | 0.412056E+11 | 33224.61 | 02-MAY-01:58 | 6.10 | 3.62 | 0.193445E+11 | 12788.79 | 04-MAY-04:49 | 5.68 | 2.80 |
June | 0.434138E+11 | 30683.07 | 09-JUN-04:28 | 7.80 | 5.54 | 0.187608E+11 | 11471.89 | 09-JUN-04:40 | 7.80 | 5.54 |
July | 0.461388E+11 | 24038.13 | 21-JUL-21:20 | 29.43 | 14.70 | 0.193106E+11 | 11397.90 | 21-JUL-21:19 | 29.43 | 14.70 |
August | 0.452903E+11 | 23306.52 | 17-AUG-21:20 | 26.87 | 14.49 | 0.193918E+11 | 11384.07 | 18-AUG-21:19 | 25.37 | 12.82 |
September | 0.411132E+11 | 22297.56 | 01-SEP-21:10 | 20.92 | 14.02 | 0.187095E+11 | 11398.24 | 09-SEP-04:10 | 12.20 | 10.82 |
October | 0.379394E+11 | 34410.05 | 30-OCT-03:12 | 4.43 | -0.8 | 0.192826E+11 | 13114.08 | 27-OCT-01:30 | 4.43 | -0.8 |
November | 0.323837E+11 | 37456.00 | 24-NOV-03:07 | 3.72 | -1.3 | 0.185976E+11 | 13515.51 | 21-NOV-02:00 | 3.72 | -1.3 |
December | 0.306387E+11 | 44265.96 | 29-DEC-23:14 | 2.23 | -1.5 | 0.191380E+11 | 13048.30 | 06-DEC-22:00 | 2.23 | -1.5 |
Annual Sum or Average | 0.450688E+12 | 0.227187E+12 | ||||||||
Minimum of Months | 0.291288E+11 | 22297.56 | 1.70 | -2.0 | 0.173675E+11 | 11384.07 | 2.20 | -1.5 | ||
Maximum of Months | 0.461388E+11 | 44265.96 | 29.43 | 14.70 | 0.193918E+11 | 13744.88 | 29.43 | 14.70 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347064E+11 | 36784.39 | 30-JAN-23:24 | 3.60 | -0.3 | 0.192731E+11 | 13223.73 | 23-JAN-22:49 | 3.60 | -0.3 |
February | 0.324625E+11 | 35788.67 | 07-FEB-22:08 | 1.78 | -1.2 | 0.174437E+11 | 12609.56 | 16-FEB-22:30 | 1.40 | 0.87 |
March | 0.386907E+11 | 42149.96 | 03-MAR-23:51 | 1.70 | -2.0 | 0.194256E+11 | 13817.88 | 27-MAR-03:20 | 5.40 | 0.78 |
April | 0.406885E+11 | 39156.40 | 19-APR-04:42 | 3.80 | 0.98 | 0.187499E+11 | 13558.34 | 04-APR-04:30 | 3.80 | 0.98 |
May | 0.443934E+11 | 34900.18 | 02-MAY-01:58 | 6.10 | 3.62 | 0.193491E+11 | 12864.72 | 04-MAY-04:49 | 5.68 | 2.80 |
June | 0.462829E+11 | 32315.62 | 09-JUN-04:23 | 7.80 | 5.54 | 0.187613E+11 | 11408.71 | 23-JUN-21:19 | 26.50 | 15.84 |
July | 0.489598E+11 | 25237.19 | 21-JUL-21:20 | 29.43 | 14.70 | 0.193110E+11 | 11405.72 | 21-JUL-21:19 | 29.43 | 14.70 |
August | 0.480993E+11 | 24500.44 | 17-AUG-21:20 | 26.87 | 14.49 | 0.193923E+11 | 11393.88 | 18-AUG-21:19 | 25.37 | 12.82 |
September | 0.438713E+11 | 23437.15 | 01-SEP-21:20 | 20.73 | 13.98 | 0.187104E+11 | 11399.76 | 09-SEP-04:10 | 12.20 | 10.82 |
October | 0.410509E+11 | 36121.05 | 30-OCT-03:12 | 4.43 | -0.8 | 0.193091E+11 | 13216.80 | 27-OCT-01:30 | 4.43 | -0.8 |
November | 0.358003E+11 | 40633.55 | 24-NOV-03:07 | 3.72 | -1.3 | 0.186667E+11 | 13606.95 | 21-NOV-02:00 | 3.72 | -1.3 |
December | 0.343005E+11 | 50025.59 | 29-DEC-23:14 | 2.23 | -1.5 | 0.192600E+11 | 13191.11 | 06-DEC-22:00 | 2.23 | -1.5 |
Annual Sum or Average | 0.489307E+12 | 0.227652E+12 | ||||||||
Minimum of Months | 0.324625E+11 | 23437.15 | 1.70 | -2.0 | 0.174437E+11 | 11393.88 | 1.40 | -1.5 | ||
Maximum of Months | 0.489598E+11 | 50025.59 | 29.43 | 14.70 | 0.194256E+11 | 13817.88 | 29.43 | 15.84 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496823E+11 | 44686.95 | 19-JAN-13:37 | 3.87 | 1.00 | 0.188671E+11 | 11512.88 | 14-JAN-18:00 | 3.87 | 1.00 |
February | 0.457369E+11 | 40659.69 | 21-FEB-07:28 | 4.15 | 1.65 | 0.170460E+11 | 11551.19 | 04-FEB-18:49 | 4.15 | 1.65 |
March | 0.526944E+11 | 43877.02 | 05-MAR-09:14 | 3.33 | -1.1 | 0.188794E+11 | 11340.77 | 04-MAR-18:40 | 3.33 | -1.1 |
April | 0.536483E+11 | 36915.50 | 23-APR-07:08 | 4.68 | 0.12 | 0.182671E+11 | 11372.05 | 15-APR-17:10 | 4.68 | 0.12 |
May | 0.567849E+11 | 35482.83 | 05-MAY-07:06 | 6.88 | 0.86 | 0.188716E+11 | 11321.37 | 06-MAY-17:19 | 17.77 | 5.04 |
June | 0.573450E+11 | 31806.58 | 29-JUN-10:40 | 32.60 | 16.86 | 0.182660E+11 | 11319.64 | 03-JUN-17:19 | 32.60 | 16.86 |
July | 0.602493E+11 | 32098.49 | 23-JUL-10:40 | 31.83 | 17.15 | 0.188685E+11 | 11323.02 | 01-JUL-17:19 | 31.83 | 17.15 |
August | 0.598195E+11 | 32074.98 | 20-AUG-10:40 | 30.17 | 17.03 | 0.188757E+11 | 11323.04 | 26-AUG-17:19 | 22.43 | 16.14 |
September | 0.560104E+11 | 31883.14 | 03-SEP-10:40 | 28.53 | 16.32 | 0.182616E+11 | 11323.03 | 23-SEP-17:19 | 19.63 | 15.23 |
October | 0.547485E+11 | 43302.38 | 25-OCT-11:29 | 3.60 | 0.17 | 0.188672E+11 | 11395.32 | 25-OCT-16:10 | 3.90 | 0.39 |
November | 0.498549E+11 | 44025.79 | 27-NOV-18:47 | 2.98 | -1.0 | 0.182619E+11 | 11467.51 | 04-NOV-17:00 | 2.98 | -1.0 |
December | 0.494416E+11 | 44040.56 | 20-DEC-17:21 | 3.60 | -2.7 | 0.188723E+11 | 11503.65 | 15-DEC-16:30 | 3.60 | -2.7 |
Annual Sum or Average | 0.646016E+12 | 0.222204E+12 | ||||||||
Minimum of Months | 0.457369E+11 | 31806.58 | 2.98 | -2.7 | 0.170460E+11 | 11319.64 | 2.98 | -2.7 | ||
Maximum of Months | 0.602493E+11 | 44686.95 | 32.60 | 17.15 | 0.188794E+11 | 11551.19 | 32.60 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552923E+10 | 6587.65 | 15-JAN-21:59 | 1.70 | -1.8 | 0.131446E+10 | 842.28 | 02-JAN-22:40 | 1.70 | -1.8 |
February | 0.566538E+10 | 6553.40 | 21-FEB-00:20 | 2.97 | 0.33 | 0.121442E+10 | 893.68 | 14-FEB-22:30 | 2.97 | 0.33 |
March | 0.739196E+10 | 6995.69 | 12-MAR-00:48 | 3.98 | -1.8 | 0.141303E+10 | 908.33 | 13-MAR-21:30 | 12.25 | 3.71 |
April | 0.830209E+10 | 6766.33 | 06-APR-00:58 | 3.30 | -1.5 | 0.147651E+10 | 997.90 | 13-APR-21:30 | 19.70 | 7.05 |
May | 0.937541E+10 | 6089.04 | 02-MAY-04:02 | 6.60 | 3.41 | 0.159267E+10 | 1007.40 | 31-MAY-22:10 | 20.52 | 8.76 |
June | 0.110247E+11 | 7376.38 | 28-JUN-15:03 | 38.40 | 14.30 | 0.161653E+10 | 1007.46 | 23-JUN-21:10 | 38.40 | 14.30 |
July | 0.125368E+11 | 7465.78 | 22-JUL-13:30 | 36.95 | 17.78 | 0.169797E+10 | 1007.50 | 01-JUL-00:40 | 36.95 | 17.78 |
August | 0.123408E+11 | 7559.35 | 20-AUG-13:10 | 33.07 | 17.06 | 0.169965E+10 | 1007.43 | 21-AUG-00:30 | 25.55 | 16.53 |
September | 0.105523E+11 | 7491.96 | 03-SEP-13:30 | 31.95 | 16.76 | 0.160717E+10 | 1007.47 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.902743E+10 | 6842.33 | 01-OCT-13:30 | 27.75 | 13.90 | 0.154268E+10 | 1007.40 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.701139E+10 | 7062.30 | 12-NOV-09:01 | 2.98 | 0.38 | 0.133691E+10 | 904.56 | 02-NOV-21:30 | 2.98 | 0.38 |
December | 0.540006E+10 | 7176.79 | 29-DEC-23:14 | 2.23 | -1.5 | 0.130781E+10 | 823.80 | 29-DEC-22:30 | 2.23 | -1.5 |
Annual Sum or Average | 0.104158E+12 | 0.178198E+11 | ||||||||
Minimum of Months | 0.540006E+10 | 6089.04 | 1.70 | -1.8 | 0.121442E+10 | 823.80 | 1.70 | -1.8 | ||
Maximum of Months | 0.125368E+11 | 7559.35 | 38.40 | 17.78 | 0.169965E+10 | 1007.50 | 38.40 | 17.78 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2573956.84 | 4945.06 | 05-JAN-01:00 | 3.30 |
February | 726761.70 | 1500.79 | 26-FEB-23:05 | 3.43 |
March | 1721227.54 | 2549.57 | 04-MAR-21:56 | 1.70 |
April | 455951.17 | 2384.73 | 20-APR-04:54 | 4.40 |
May | 57170.04 | 354.73 | 02-MAY-03:17 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 3035346.78 | 5020.98 | 30-OCT-03:02 | 4.72 |
November | 4395916.38 | 4823.19 | 29-NOV-02:58 | 4.40 |
December | 4550449.39 | 5765.19 | 03-DEC-07:35 | 4.40 |
Annual Sum or Average | 17516779.84 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 4550449.39 | 5765.19 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43345966.07 | 809.81 | 05-JAN-01:00 | 3.30 |
February | 11057766.01 | 610.32 | 26-FEB-23:05 | 3.43 |
March | 15901928.58 | 664.67 | 09-MAR-06:11 | 4.40 |
April | 11434718.36 | 791.45 | 20-APR-04:54 | 4.40 |
May | 3273842.22 | 487.14 | 06-MAY-03:36 | 6.47 |
June | 47731.37 | 409.19 | 09-JUN-04:22 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 9762407.56 | 755.98 | 29-OCT-05:57 | 4.40 |
November | 11295107.13 | 1229.65 | 11-NOV-08:59 | 5.00 |
December | 32796842.59 | 876.62 | 03-DEC-07:35 | 4.40 |
Annual Sum or Average | 0.138916E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.30 | |
Maximum of Months | 43345966.07 | 1229.65 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 940016.96 | 292.18 | 10-JAN-11:13 | 2.40 |
February | 672136.90 | 151.56 | 26-FEB-23:05 | 3.43 |
March | 349383.91 | 450.77 | 12-MAR-00:22 | 4.15 |
April | 58925.76 | 217.84 | 20-APR-04:54 | 4.40 |
May | 29706.49 | 71.27 | 06-MAY-03:36 | 6.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 494059.07 | 244.16 | 29-OCT-05:57 | 4.40 |
November | 676707.84 | 320.95 | 07-NOV-02:00 | 4.40 |
December | 1144829.46 | 303.66 | 03-DEC-07:35 | 4.40 |
Annual Sum or Average | 4365766.39 | |||
Minimum of Months | 0.00 | 0.00 | 2.40 | |
Maximum of Months | 1144829.46 | 450.77 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6492147.09 | 401.94 | 16-JAN-07:50 | 3.30 |
February | 6786346.63 | 316.40 | 26-FEB-23:05 | 3.43 |
March | 4686895.00 | 322.09 | 12-MAR-00:22 | 4.15 |
April | 1917644.66 | 296.18 | 07-APR-04:08 | 4.40 |
May | 444556.21 | 151.90 | 06-MAY-03:36 | 6.47 |
June | 785.81 | 12.57 | 09-JUN-04:22 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 2358406.22 | 360.51 | 29-OCT-05:57 | 4.40 |
November | 5461837.59 | 390.38 | 29-NOV-02:58 | 4.40 |
December | 9716164.85 | 598.33 | 23-DEC-11:57 | 3.30 |
Annual Sum or Average | 37864784.05 | |||
Minimum of Months | 0.00 | 0.00 | 3.30 | |
Maximum of Months | 9716164.85 | 598.33 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12356882.34 | 306.07 | 19-JAN-12:53 | 2.80 |
February | 6508553.17 | 241.67 | 26-FEB-23:05 | 3.43 |
March | 5066963.19 | 245.34 | 12-MAR-00:22 | 4.15 |
April | 2452212.26 | 224.31 | 07-APR-04:08 | 4.40 |
May | 569115.89 | 129.94 | 06-MAY-03:36 | 6.47 |
June | 4425.99 | 40.83 | 09-JUN-04:22 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 2458042.89 | 268.73 | 29-OCT-05:57 | 4.40 |
November | 5368655.03 | 279.70 | 29-NOV-02:58 | 4.40 |
December | 8670777.91 | 543.92 | 23-DEC-11:57 | 3.30 |
Annual Sum or Average | 43455628.66 | |||
Minimum of Months | 0.00 | 0.00 | 2.80 | |
Maximum of Months | 12356882.34 | 543.92 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 138638.28 | 1412.81 | 11-JAN-02:09 | 3.90 |
February | 156303.22 | 923.59 | 21-FEB-00:35 | 3.13 |
March | 1563596.97 | 1876.38 | 03-MAR-04:40 | 4.40 |
April | 807412.28 | 3141.31 | 20-APR-04:54 | 4.40 |
May | 678307.14 | 2248.85 | 02-MAY-03:17 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1596230.43 | 2878.73 | 29-OCT-03:28 | 4.45 |
November | 2164230.93 | 2460.90 | 20-NOV-01:47 | 5.00 |
December | 662802.76 | 2476.49 | 01-DEC-05:54 | 3.90 |
Annual Sum or Average | 7767522.01 | |||
Minimum of Months | 0.00 | 0.00 | 3.13 | |
Maximum of Months | 2164230.93 | 3141.31 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2053185.29 | 1778.69 | 16-JAN-07:50 | 3.30 |
February | 1167854.12 | 1050.70 | 21-FEB-11:08 | 7.07 |
March | 5338852.61 | 2465.91 | 12-MAR-00:22 | 4.15 |
April | 1384919.30 | 2317.93 | 20-APR-04:54 | 4.40 |
May | 263478.09 | 740.27 | 02-MAY-04:05 | 6.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 4106663.05 | 2451.90 | 29-OCT-05:57 | 4.40 |
November | 5518520.33 | 2129.93 | 20-NOV-01:47 | 5.00 |
December | 3900669.04 | 2071.69 | 01-DEC-02:07 | 4.22 |
Annual Sum or Average | 23734141.82 | |||
Minimum of Months | 0.00 | 0.00 | 3.30 | |
Maximum of Months | 5518520.33 | 2465.91 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6389527.12 | 7514.07 | 05-JAN-01:00 | 3.30 |
February | 2561777.78 | 5163.60 | 26-FEB-23:05 | 3.43 |
March | 4722885.14 | 9194.17 | 12-MAR-00:22 | 4.15 |
April | 1142931.38 | 6782.61 | 07-APR-04:08 | 4.40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 10234934.83 | 8779.73 | 29-OCT-05:57 | 4.40 |
November | 9871884.02 | 7450.26 | 20-NOV-01:47 | 5.00 |
December | 10199497.82 | 10051.22 | 03-DEC-07:35 | 4.40 |
Annual Sum or Average | 45123438.11 | |||
Minimum of Months | 0.00 | 0.00 | 3.30 | |
Maximum of Months | 10234934.83 | 10051.22 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481287E+09 | 1684.35 | 05-JAN-17:03 | 12.85 |
February | 0.304662E+09 | 1585.33 | 14-FEB-19:03 | 12.93 |
March | 0.105501E+09 | 1679.87 | 26-MAR-19:43 | 12.77 |
April | 10306465.48 | 1668.22 | 17-APR-21:53 | 13.90 |
May | 5720840.59 | 1648.46 | 08-MAY-21:53 | 21.70 |
June | 1479702.28 | 1637.60 | 21-JUN-08:53 | 26.10 |
July | 298671.45 | 833.17 | 17-JUL-21:53 | 21.70 |
August | 671819.48 | 1255.75 | 29-AUG-08:53 | 20.00 |
September | 1608149.93 | 1238.21 | 30-SEP-21:53 | 18.00 |
October | 48742483.39 | 1677.20 | 28-OCT-18:33 | 14.27 |
November | 0.145670E+09 | 1447.48 | 10-NOV-19:02 | 6.10 |
December | 0.485982E+09 | 1509.33 | 07-DEC-16:01 | 8.03 |
Annual Sum or Average | 0.159193E+10 | |||
Minimum of Months | 298671.45 | 833.17 | 6.10 | |
Maximum of Months | 0.485982E+09 | 1684.35 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.799137E+09 | 1552.83 | 12-JAN-19:01 | 2.38 |
February | 0.515076E+09 | 1704.15 | 19-FEB-16:03 | 15.82 |
March | 0.174631E+09 | 1690.50 | 24-MAR-19:03 | 12.93 |
April | 17407864.03 | 1680.50 | 04-APR-19:13 | 14.43 |
May | 6335177.69 | 1660.02 | 10-MAY-21:53 | 17.20 |
June | 1385737.21 | 1380.66 | 20-JUN-08:53 | 23.30 |
July | 353906.62 | 855.21 | 17-JUL-21:53 | 21.70 |
August | 755595.17 | 1249.55 | 29-AUG-08:53 | 20.00 |
September | 2598110.45 | 1657.66 | 25-SEP-21:53 | 17.80 |
October | 78945128.62 | 1671.01 | 17-OCT-19:23 | 14.15 |
November | 0.305007E+09 | 1542.11 | 26-NOV-16:03 | 6.23 |
December | 0.877778E+09 | 1640.08 | 05-DEC-16:02 | 6.02 |
Annual Sum or Average | 0.277941E+10 | |||
Minimum of Months | 353906.62 | 855.21 | 2.38 | |
Maximum of Months | 0.877778E+09 | 1704.15 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 281858.95 | 34.07 | 19-JAN-05:00 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 281858.95 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 281858.95 | 34.07 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93454713.11 | 450.98 | 19-JAN-16:01 | 3.62 |
February | 54348708.28 | 446.57 | 06-FEB-16:01 | 5.82 |
March | 4633757.99 | 451.96 | 11-MAR-09:02 | 6.23 |
April | 1711096.37 | 449.94 | 01-APR-21:54 | 12.20 |
May | 1090522.60 | 440.14 | 06-MAY-15:03 | 17.88 |
June | 291193.45 | 383.16 | 21-JUN-08:54 | 26.10 |
July | 84117.16 | 277.82 | 29-JUL-21:54 | 23.30 |
August | 131151.07 | 261.64 | 28-AUG-08:54 | 20.00 |
September | 741843.95 | 424.52 | 25-SEP-21:54 | 17.80 |
October | 3816799.56 | 453.53 | 15-OCT-21:43 | 15.60 |
November | 17003021.10 | 436.89 | 27-NOV-16:01 | 6.52 |
December | 0.121243E+09 | 458.33 | 15-DEC-16:01 | 4.13 |
Annual Sum or Average | 0.298550E+09 | |||
Minimum of Months | 84117.16 | 261.64 | 3.62 | |
Maximum of Months | 0.121243E+09 | 458.33 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507134E+09 | 1482.58 | 12-JAN-19:01 | 2.38 |
February | 0.328881E+09 | 1461.44 | 21-FEB-09:01 | 4.68 |
March | 0.107837E+09 | 1589.79 | 13-MAR-20:43 | 12.35 |
April | 11771200.17 | 1506.47 | 22-APR-21:53 | 16.10 |
May | 3242793.37 | 1580.77 | 12-MAY-21:53 | 17.80 |
June | 528809.61 | 1263.53 | 17-JUN-21:53 | 23.30 |
July | 103422.96 | 613.18 | 26-JUL-21:54 | 22.20 |
August | 257301.79 | 663.07 | 02-AUG-21:54 | 22.20 |
September | 736467.30 | 1006.99 | 23-SEP-08:54 | 18.30 |
October | 49874914.55 | 1600.43 | 20-OCT-20:23 | 14.70 |
November | 0.156574E+09 | 1413.11 | 10-NOV-19:02 | 6.10 |
December | 0.509503E+09 | 1552.15 | 05-DEC-16:02 | 6.02 |
Annual Sum or Average | 0.167644E+10 | |||
Minimum of Months | 103422.96 | 613.18 | 2.38 | |
Maximum of Months | 0.509503E+09 | 1600.43 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.813421E+09 | 1534.63 | 19-JAN-16:01 | 3.62 |
February | 0.534454E+09 | 1491.29 | 06-FEB-16:01 | 5.82 |
March | 0.167833E+09 | 1441.95 | 14-MAR-16:22 | 12.50 |
April | 20096389.71 | 1577.92 | 12-APR-21:53 | 16.70 |
May | 3842156.53 | 1546.67 | 08-MAY-21:53 | 21.70 |
June | 500617.15 | 1298.85 | 17-JUN-21:53 | 23.30 |
July | 110823.98 | 671.24 | 26-JUL-21:54 | 22.20 |
August | 398506.72 | 636.21 | 29-AUG-16:34 | 24.07 |
September | 1258556.65 | 1516.86 | 25-SEP-21:53 | 17.80 |
October | 76258351.71 | 1563.44 | 05-OCT-21:53 | 19.40 |
November | 0.304123E+09 | 1436.18 | 27-NOV-16:01 | 6.52 |
December | 0.880854E+09 | 1527.13 | 15-DEC-16:01 | 4.13 |
Annual Sum or Average | 0.280315E+10 | |||
Minimum of Months | 110823.98 | 636.21 | 3.62 | |
Maximum of Months | 0.880854E+09 | 1577.92 | 24.07 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13945591.69 | 835.58 | 16-JAN-07:50 | 3.30 |
February | 13311230.45 | 709.50 | 26-FEB-23:05 | 3.43 |
March | 10669630.74 | 614.72 | 12-MAR-00:22 | 4.15 |
April | 3249106.73 | 560.78 | 07-APR-04:08 | 4.40 |
May | 762384.48 | 275.59 | 06-MAY-03:36 | 6.47 |
June | 6177.76 | 63.87 | 09-JUN-04:22 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 3983237.69 | 731.81 | 29-OCT-05:57 | 4.40 |
November | 10235132.21 | 720.47 | 29-NOV-02:58 | 4.40 |
December | 18736850.99 | 951.15 | 25-DEC-18:58 | 2.20 |
Annual Sum or Average | 74899342.74 | |||
Minimum of Months | 0.00 | 0.00 | 2.20 | |
Maximum of Months | 18736850.99 | 951.15 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.809528E+09 | 1969.41 | 05-JAN-17:03 | 12.85 |
February | 0.537841E+09 | 1783.79 | 21-FEB-09:01 | 4.68 |
March | 0.245774E+09 | 1815.28 | 08-MAR-21:03 | 13.62 |
April | 45250307.02 | 1809.47 | 29-APR-21:53 | 17.20 |
May | 18035458.80 | 1766.40 | 15-MAY-21:53 | 20.60 |
June | 3718992.26 | 1633.98 | 21-JUN-08:53 | 26.10 |
July | 515325.35 | 1279.36 | 29-JUL-21:53 | 23.30 |
August | 899027.25 | 1196.75 | 28-AUG-08:53 | 20.00 |
September | 2315552.52 | 1692.52 | 30-SEP-21:53 | 18.00 |
October | 0.110661E+09 | 1793.72 | 25-OCT-15:01 | 4.32 |
November | 0.327635E+09 | 1731.88 | 10-NOV-19:02 | 6.10 |
December | 0.813932E+09 | 1795.47 | 07-DEC-16:01 | 8.03 |
Annual Sum or Average | 0.291611E+10 | |||
Minimum of Months | 515325.35 | 1196.75 | 4.32 | |
Maximum of Months | 0.813932E+09 | 1969.41 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123805E+10 | 1835.67 | 08-JAN-09:01 | 1.65 |
February | 0.826368E+09 | 1963.24 | 19-FEB-16:03 | 15.82 |
March | 0.369988E+09 | 1913.71 | 25-MAR-19:33 | 13.13 |
April | 63652308.50 | 1805.57 | 13-APR-21:53 | 18.30 |
May | 20141223.67 | 1827.77 | 15-MAY-21:53 | 20.60 |
June | 3524472.52 | 1629.64 | 21-JUN-08:53 | 26.10 |
July | 527170.40 | 1267.83 | 29-JUL-21:53 | 23.30 |
August | 957501.32 | 1400.63 | 27-AUG-08:53 | 21.70 |
September | 2760063.17 | 1727.36 | 21-SEP-21:53 | 18.90 |
October | 0.174189E+09 | 1813.25 | 25-OCT-15:01 | 4.32 |
November | 0.601850E+09 | 1777.56 | 28-NOV-09:01 | -0.1 |
December | 0.133188E+10 | 1834.56 | 29-DEC-09:01 | 1.38 |
Annual Sum or Average | 0.463389E+10 | |||
Minimum of Months | 527170.40 | 1267.83 | -0.1 | |
Maximum of Months | 0.133188E+10 | 1963.24 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149038E+09 | 896.82 | 19-JAN-09:02 | -2.1 |
February | 95008573.11 | 887.34 | 21-FEB-09:01 | 4.68 |
March | 39602376.12 | 867.19 | 22-MAR-08:62 | 4.87 |
April | 8595508.30 | 965.83 | 24-APR-21:53 | 15.60 |
May | 4642274.35 | 943.33 | 31-MAY-21:53 | 20.70 |
June | 912188.44 | 948.62 | 19-JUN-21:53 | 20.00 |
July | 554731.29 | 549.68 | 16-JUL-21:54 | 22.80 |
August | 361895.54 | 520.26 | 02-AUG-21:54 | 22.20 |
September | 510626.62 | 686.96 | 08-SEP-21:54 | 15.60 |
October | 21145227.30 | 891.62 | 25-OCT-15:01 | 4.32 |
November | 38100454.05 | 862.88 | 10-NOV-19:02 | 6.10 |
December | 0.142499E+09 | 891.21 | 08-DEC-09:02 | -0.5 |
Annual Sum or Average | 0.500971E+09 | |||
Minimum of Months | 361895.54 | 520.26 | -2.1 | |
Maximum of Months | 0.149038E+09 | 965.83 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 977570.49 | 2757.80 | 10-JAN-11:13 | 2.40 |
February | 84125.96 | 420.63 | 05-FEB-14:50 | 3.30 |
March | 473042.76 | 1559.31 | 09-MAR-06:11 | 4.40 |
April | 188834.14 | 1277.93 | 20-APR-04:54 | 4.40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1146103.40 | 3593.78 | 29-OCT-03:28 | 4.45 |
November | 959455.50 | 2741.81 | 29-NOV-02:10 | 4.40 |
December | 2081004.36 | 4052.37 | 25-DEC-01:29 | 3.85 |
Annual Sum or Average | 5910136.60 | |||
Minimum of Months | 0.00 | 0.00 | 2.40 | |
Maximum of Months | 2081004.36 | 4052.37 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 601543.25 | 1962.22 | 10-JAN-11:13 | 2.40 |
February | 9941.03 | 49.71 | 05-FEB-14:50 | 3.30 |
March | 395206.51 | 1438.96 | 09-MAR-06:11 | 4.40 |
April | 295467.35 | 2788.23 | 20-APR-04:54 | 4.40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 956880.44 | 3605.39 | 29-OCT-03:28 | 4.45 |
November | 814404.39 | 2376.08 | 29-NOV-02:10 | 4.40 |
December | 1382253.78 | 1959.24 | 17-DEC-21:25 | 1.95 |
Annual Sum or Average | 4455696.75 | |||
Minimum of Months | 0.00 | 0.00 | 1.95 | |
Maximum of Months | 1382253.78 | 3605.39 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21081.02 | 351.35 | 11-JAN-02:37 | 3.90 |
February | 54569.41 | 909.49 | 16-FEB-05:06 | 3.53 |
March | 156889.84 | 786.05 | 26-MAR-01:24 | 4.45 |
April | 251306.75 | 1771.56 | 20-APR-04:54 | 4.40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 310787.78 | 2490.89 | 29-OCT-03:28 | 4.45 |
November | 515189.34 | 1765.34 | 20-NOV-01:47 | 5.00 |
December | 489798.38 | 2467.53 | 25-DEC-01:29 | 3.85 |
Annual Sum or Average | 1799622.52 | |||
Minimum of Months | 0.00 | 0.00 | 3.53 | |
Maximum of Months | 515189.34 | 2490.89 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36470953.77 | 2909.64 | 25-JAN-08:53 | 2.20 |
February | 27803722.54 | 1461.65 | 26-FEB-23:05 | 3.43 |
March | 31731464.16 | 1398.53 | 12-MAR-00:22 | 4.15 |
April | 16158882.63 | 1452.38 | 20-APR-04:54 | 4.40 |
May | 4431645.43 | 924.46 | 06-MAY-03:36 | 6.47 |
June | 46369.48 | 414.81 | 09-JUN-04:22 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 15441345.39 | 1691.37 | 29-OCT-05:57 | 4.40 |
November | 31314830.34 | 1690.15 | 29-NOV-02:58 | 4.40 |
December | 47329379.13 | 1938.09 | 03-DEC-07:35 | 4.40 |
Annual Sum or Average | 0.210729E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.20 | |
Maximum of Months | 47329379.13 | 2909.64 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160421E+11 | 15451.75 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.144845E+11 | 15451.75 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.160915E+11 | 15451.75 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.154982E+11 | 15451.75 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.160699E+11 | 15451.75 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.155692E+11 | 15451.75 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.159988E+11 | 15451.75 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.160977E+11 | 15451.75 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.155043E+11 | 15451.75 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.160359E+11 | 15451.75 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.155569E+11 | 15451.75 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.159988E+11 | 15451.75 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.188948E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.144845E+11 | 15451.75 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.160977E+11 | 15451.75 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743719E+09 | 716.35 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.671510E+09 | 716.35 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.746011E+09 | 716.35 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.718503E+09 | 716.35 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.745008E+09 | 716.35 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.721798E+09 | 716.35 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.741713E+09 | 716.35 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.746298E+09 | 716.35 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.718790E+09 | 716.35 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.743432E+09 | 716.35 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.721225E+09 | 716.35 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.741713E+09 | 716.35 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.875972E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.671510E+09 | 716.35 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.746298E+09 | 716.35 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861229E+09 | 829.54 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.777612E+09 | 829.54 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.863884E+09 | 829.54 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.832029E+09 | 829.54 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.862722E+09 | 829.54 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.835845E+09 | 829.54 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.858907E+09 | 829.54 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.864216E+09 | 829.54 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.832361E+09 | 829.54 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.860897E+09 | 829.54 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.835182E+09 | 829.54 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.858907E+09 | 829.54 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.101438E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.777612E+09 | 829.54 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.864216E+09 | 829.54 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693793E+09 | 668.27 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.626432E+09 | 668.27 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.695932E+09 | 668.27 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.670270E+09 | 668.27 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.694996E+09 | 668.27 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.673344E+09 | 668.27 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.691922E+09 | 668.27 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.696199E+09 | 668.27 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.670538E+09 | 668.27 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.693526E+09 | 668.27 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.672810E+09 | 668.27 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.691922E+09 | 668.27 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.817168E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.626432E+09 | 668.27 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.696199E+09 | 668.27 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351983E+09 | 339.04 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.317809E+09 | 339.04 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.353068E+09 | 339.04 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.340049E+09 | 339.04 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.352593E+09 | 339.04 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.341609E+09 | 339.04 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.351034E+09 | 339.04 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.353204E+09 | 339.04 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.340185E+09 | 339.04 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.351847E+09 | 339.04 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.341337E+09 | 339.04 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.351034E+09 | 339.04 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.414575E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.317809E+09 | 339.04 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.353204E+09 | 339.04 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.150154E+10 | 1957.67 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.132396E+10 | 1957.67 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.139697E+10 | 1957.67 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.124640E+10 | 1957.67 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.124549E+10 | 1957.67 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.113381E+10 | 1957.67 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.121358E+10 | 1957.67 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.125455E+10 | 1957.67 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.131092E+10 | 1957.67 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.144931E+10 | 1957.67 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.143812E+10 | 1957.67 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.153111E+10 | 1957.67 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.160457E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.113381E+10 | 1957.67 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.153111E+10 | 1957.67 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.847367E+10 | 8554.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.762950E+10 | 8554.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.843309E+10 | 8554.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.804493E+10 | 8554.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.831593E+10 | 8554.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.803420E+10 | 8554.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.826841E+10 | 8554.32 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.833108E+10 | 8554.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.809994E+10 | 8554.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.843550E+10 | 8554.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.820283E+10 | 8554.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.847501E+10 | 8554.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.987441E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.762950E+10 | 8554.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.847501E+10 | 8554.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146022E+09 | 132.12 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.131872E+09 | 132.12 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.144861E+09 | 132.12 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.141479E+09 | 132.12 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.145441E+09 | 132.12 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.140357E+09 | 132.12 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.146583E+09 | 132.12 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.144861E+09 | 132.12 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.141518E+09 | 132.12 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.146003E+09 | 132.12 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.140918E+09 | 132.12 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.146602E+09 | 132.12 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.171652E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.131872E+09 | 132.12 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.146602E+09 | 132.12 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317479E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.281892E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.304777E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.280358E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.284677E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.267926E+10 | 3437.84 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.280842E+10 | 3437.84 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.286855E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.289021E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.312028E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.303531E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.319999E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.352938E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.267926E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.319999E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317479E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.281892E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.304777E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.280358E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.284677E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.267926E+10 | 3437.84 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.280842E+10 | 3437.84 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.286855E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.289021E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.312028E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.303531E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.319999E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.352938E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.267926E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.319999E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126106E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121504E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125670E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148074E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.160421E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.160915E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.154982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.160699E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.155692E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.155043E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.160359E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.155569E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.188948E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.743719E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548576E+09 |
February | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453711E+09 |
March | 0.199990E+10 | 0.746011E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371581E+09 |
April | 0.192973E+10 | 0.718503E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1110117.51 | 0.232481E+09 |
May | 0.199475E+10 | 0.745008E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11384242.52 | 0.145814E+09 |
June | 0.193394E+10 | 0.721798E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60755313.86 | 67030340.24 |
July | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77669002.27 | 29704954.18 |
August | 0.199896E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53670856.90 | 45805659.19 |
September | 0.192879E+10 | 0.718790E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19253677.15 | 98608688.74 |
October | 0.199148E+10 | 0.743432E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3241502.69 | 0.258746E+09 |
November | 0.192552E+10 | 0.721225E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416634E+09 |
December | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565045E+09 |
Annual Sum or Average | 0.234744E+11 | 0.875972E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227085E+09 | 0.323374E+10 |
Minimum of Months | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29704954.18 |
Maximum of Months | 0.199990E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77669002.27 | 0.565045E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.861229E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222075E+09 |
February | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184299E+09 |
March | 0.231589E+10 | 0.863884E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155169E+09 |
April | 0.223463E+10 | 0.832029E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 516593.80 | 98940421.70 |
May | 0.230993E+10 | 0.862722E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4567449.42 | 65586992.80 |
June | 0.223950E+10 | 0.835845E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23465371.27 | 31313935.08 |
July | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30072128.39 | 14264324.62 |
August | 0.231480E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20949528.56 | 20583083.09 |
September | 0.223354E+10 | 0.832361E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7676520.14 | 42376884.26 |
October | 0.230614E+10 | 0.860897E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1323531.80 | 0.106695E+09 |
November | 0.222975E+10 | 0.835182E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170557E+09 |
December | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227781E+09 |
Annual Sum or Average | 0.271834E+11 | 0.101438E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88571123.37 | 0.133964E+10 |
Minimum of Months | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14264324.62 |
Maximum of Months | 0.231589E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30072128.39 | 0.227781E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.693793E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484606E+09 |
February | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 441.42 | 0.399726E+09 |
March | 0.489771E+09 | 0.695932E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23529.56 | 0.336820E+09 |
April | 0.472586E+09 | 0.670270E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2442067.07 | 0.216218E+09 |
May | 0.488511E+09 | 0.694996E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12070448.42 | 0.147565E+09 |
June | 0.473617E+09 | 0.673344E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55127667.86 | 72775081.96 |
July | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70240729.84 | 33719869.15 |
August | 0.489542E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49327149.55 | 48297747.58 |
September | 0.472357E+09 | 0.670538E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19606665.80 | 97206150.69 |
October | 0.487709E+09 | 0.693526E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3881766.42 | 0.234123E+09 |
November | 0.471555E+09 | 0.672810E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369867E+09 |
December | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495281E+09 |
Annual Sum or Average | 0.574883E+10 | 0.817168E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212720E+09 | 0.293620E+10 |
Minimum of Months | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33719869.15 |
Maximum of Months | 0.489771E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70240729.84 | 0.495281E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.351983E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275308E+09 |
February | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1867.82 | 0.226315E+09 |
March | 0.376747E+09 | 0.353068E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21643.05 | 0.188438E+09 |
April | 0.363528E+09 | 0.340049E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635863.34 | 0.119657E+09 |
May | 0.375778E+09 | 0.352593E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7661529.44 | 80762647.84 |
June | 0.364321E+09 | 0.341609E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32337376.04 | 39934253.54 |
July | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40907854.83 | 18750385.87 |
August | 0.376571E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28972476.39 | 26537222.37 |
September | 0.363352E+09 | 0.340185E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12115438.17 | 52811953.08 |
October | 0.375161E+09 | 0.351847E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2512319.06 | 0.129739E+09 |
November | 0.362735E+09 | 0.341337E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207557E+09 |
December | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282139E+09 |
Annual Sum or Average | 0.442217E+10 | 0.414575E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126166E+09 | 0.164795E+10 |
Minimum of Months | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18750385.87 |
Maximum of Months | 0.376747E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40907854.83 | 0.282139E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738664E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609774E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512201E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1580610.18 | 0.321876E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 14223482.93 | 0.211046E+09 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 76095314.45 | 96493437.57 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 98582735.88 | 39908205.47 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 69432210.57 | 59919201.19 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 26969071.34 | 0.130477E+09 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 5179736.34 | 0.342373E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558714E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756394E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.292063E+09 | 0.437784E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39908205.47 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 98582735.88 | 0.756394E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.150154E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129036E+10 |
February | 0.236489E+11 | 0.132396E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107168E+10 |
March | 0.262800E+11 | 0.139697E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898319E+09 |
April | 0.253579E+11 | 0.124640E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2240028.62 | 0.571226E+09 |
May | 0.262123E+11 | 0.124549E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24132747.84 | 0.373301E+09 |
June | 0.254132E+11 | 0.113381E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133896E+09 | 0.176045E+09 |
July | 0.261570E+11 | 0.121358E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172010E+09 | 80273960.23 |
August | 0.262677E+11 | 0.125455E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118968E+09 | 0.115670E+09 |
September | 0.253456E+11 | 0.131092E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42584997.26 | 0.241434E+09 |
October | 0.261693E+11 | 0.144931E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7167752.56 | 0.615539E+09 |
November | 0.253025E+11 | 0.143812E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990926E+09 |
December | 0.261570E+11 | 0.153111E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132638E+10 |
Annual Sum or Average | 0.308468E+12 | 0.160457E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500999E+09 | 0.775115E+10 |
Minimum of Months | 0.236489E+11 | 0.113381E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80273960.23 |
Maximum of Months | 0.262800E+11 | 0.153111E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172010E+09 | 0.132638E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.847367E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374019E+10 |
February | 0.702046E+11 | 0.762950E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309997E+10 |
March | 0.780153E+11 | 0.843309E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260553E+10 |
April | 0.752779E+11 | 0.804493E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6763190.08 | 0.164874E+10 |
May | 0.778146E+11 | 0.831593E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71198390.74 | 0.108909E+10 |
June | 0.754422E+11 | 0.803420E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383022E+09 | 0.516034E+09 |
July | 0.776503E+11 | 0.826841E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491068E+09 | 0.233450E+09 |
August | 0.779788E+11 | 0.833108E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340657E+09 | 0.336926E+09 |
September | 0.752414E+11 | 0.809994E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121985E+09 | 0.697967E+09 |
October | 0.776868E+11 | 0.843550E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20503181.09 | 0.177983E+10 |
November | 0.751137E+11 | 0.820283E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286165E+10 |
December | 0.776503E+11 | 0.847501E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383689E+10 |
Annual Sum or Average | 0.915726E+12 | 0.987441E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143520E+10 | 0.224463E+11 |
Minimum of Months | 0.702046E+11 | 0.762950E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233450E+09 |
Maximum of Months | 0.780153E+11 | 0.847501E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491068E+09 | 0.383689E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306969E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3434.54 | 0.252838E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6239.24 | 0.208860E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2073129.53 | 0.129815E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10940662.29 | 79904031.59 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46785192.64 | 33641465.99 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60908019.71 | 10979593.57 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44666845.74 | 19111354.53 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17360151.49 | 46952384.60 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3273468.31 | 0.139816E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227836E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315145E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186017E+09 | 0.177187E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10979593.57 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60908019.71 | 0.315145E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300431E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3497.01 | 0.247400E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6460.77 | 0.204555E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2078337.97 | 0.127639E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10958883.11 | 79372622.13 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46740523.55 | 33951532.32 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60891918.99 | 11150496.67 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44743373.98 | 18843231.63 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17487497.18 | 45610124.81 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3304220.55 | 0.134991E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222723E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307400E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186215E+09 | 0.173407E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11150496.67 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60891918.99 | 0.307400E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.146022E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91064942.04 |
February | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75914781.22 |
March | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63372917.91 |
April | 0.00 | 0.141479E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 320267.67 | 39812918.77 |
May | 0.00 | 0.145441E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2188424.48 | 25789604.49 |
June | 0.00 | 0.140357E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10732765.82 | 11846122.90 |
July | 0.00 | 0.146583E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13876618.66 | 4818673.09 |
August | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9895131.29 | 7291790.59 |
September | 0.00 | 0.141518E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3825183.29 | 16068473.04 |
October | 0.00 | 0.146003E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 713619.80 | 42813762.01 |
November | 0.00 | 0.140918E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69964738.49 |
December | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94076781.17 |
Annual Sum or Average | 0.00 | 0.171652E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41552011.02 | 0.542836E+09 |
Minimum of Months | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4818673.09 |
Maximum of Months | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13876618.66 | 94076781.17 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83900829.72 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13163.46 | 68660663.15 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22438.14 | 55724625.30 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 759581.41 | 33608024.73 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3379322.10 | 20883766.02 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13299561.03 | 8801633.59 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17258327.65 | 2713632.14 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12807965.53 | 4585860.37 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5400956.27 | 11800842.14 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216000.79 | 35773628.98 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61549023.56 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85916710.08 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54157316.38 | 0.473919E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2713632.14 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17258327.65 | 85916710.08 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307769E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3501.62 | 0.253239E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6569.76 | 0.208210E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2101185.66 | 0.128118E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10926545.76 | 80755805.77 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46464724.94 | 36987022.38 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60580421.72 | 14819974.83 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44497955.84 | 22828288.70 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17328122.65 | 48821111.19 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3295213.48 | 0.137736E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228538E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315988E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185204E+09 | 0.178381E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14819974.83 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60580421.72 | 0.315988E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300354E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4189.40 | 0.247087E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7219.72 | 0.205182E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2121458.46 | 0.127246E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10934272.53 | 80558629.83 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46441846.84 | 37262371.77 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60570577.47 | 14947110.98 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44525231.26 | 22582745.88 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17417218.51 | 47712217.79 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3338806.44 | 0.134310E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222566E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306829E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185361E+09 | 0.174664E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14947110.98 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60570577.47 | 0.306829E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375595E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309686E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.81 | 0.261096E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1419596.86 | 0.169334E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8903456.78 | 0.113775E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42153100.96 | 55327444.95 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53686626.27 | 25861673.50 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37289397.39 | 37390940.10 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13524851.24 | 76042638.35 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2292650.58 | 0.186425E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288220E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383129E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159270E+09 | 0.228188E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25861673.50 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53686626.27 | 0.383129E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306839E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.37 | 0.253065E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5651.91 | 0.209713E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2016315.87 | 0.131431E+09 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10740981.99 | 80616191.69 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46347634.05 | 33864280.11 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60322615.97 | 10738682.95 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44153616.18 | 18995254.83 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17084230.13 | 46989609.40 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3200571.34 | 0.141115E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227931E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315003E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183875E+09 | 0.177630E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10738682.95 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60322615.97 | 0.315003E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299862E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.84 | 0.247263E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5901.12 | 0.205065E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2020562.32 | 0.129170E+09 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10755019.68 | 80130893.66 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46292958.89 | 34160176.17 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60296768.02 | 10887528.65 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44227109.61 | 18703440.54 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17208291.44 | 45572231.53 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3233076.64 | 0.135548E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222093E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306877E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184043E+09 | 0.173533E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10887528.65 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60296768.02 | 0.306877E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159477E+09 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1353.98 | 0.131160E+09 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2689.86 | 0.107543E+09 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1043000.79 | 65290038.33 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5529661.95 | 39882675.38 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23811145.92 | 16508571.09 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30960037.56 | 5311764.98 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22621663.92 | 9306038.07 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8703042.45 | 24039303.13 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1601437.32 | 72511287.52 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118070E+09 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163661E+09 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94274033.76 | 0.912761E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5311764.98 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30960037.56 | 0.163661E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.317479E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850904E+09 |
February | 0.415303E+11 | 0.281892E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704587E+09 |
March | 0.461508E+11 | 0.304777E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596309E+09 |
April | 0.445315E+11 | 0.280358E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1246362.69 | 0.380259E+09 |
May | 0.460320E+11 | 0.284677E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14016124.36 | 0.253364E+09 |
June | 0.446286E+11 | 0.267926E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82478555.71 | 0.119876E+09 |
July | 0.459349E+11 | 0.280842E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106767E+09 | 54211130.76 |
August | 0.461292E+11 | 0.286855E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74113774.96 | 78205031.63 |
September | 0.445099E+11 | 0.289021E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26381818.91 | 0.160119E+09 |
October | 0.459565E+11 | 0.312028E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4390626.66 | 0.404749E+09 |
November | 0.444343E+11 | 0.303531E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647534E+09 |
December | 0.459349E+11 | 0.319999E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869373E+09 |
Annual Sum or Average | 0.541708E+12 | 0.352938E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309394E+09 | 0.511949E+10 |
Minimum of Months | 0.415303E+11 | 0.267926E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54211130.76 |
Maximum of Months | 0.461508E+11 | 0.319999E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106767E+09 | 0.869373E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.317479E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855727E+09 |
February | 0.415303E+11 | 0.281892E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708049E+09 |
March | 0.461508E+11 | 0.304777E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598329E+09 |
April | 0.445315E+11 | 0.280358E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1246283.98 | 0.380930E+09 |
May | 0.460320E+11 | 0.284677E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14010567.54 | 0.253576E+09 |
June | 0.446286E+11 | 0.267926E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82476044.76 | 0.119895E+09 |
July | 0.459349E+11 | 0.280842E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106764E+09 | 54212823.73 |
August | 0.461292E+11 | 0.286855E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74110006.91 | 78213181.18 |
September | 0.445099E+11 | 0.289021E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26360515.62 | 0.160143E+09 |
October | 0.459565E+11 | 0.312028E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4366431.25 | 0.406038E+09 |
November | 0.444343E+11 | 0.303531E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650758E+09 |
December | 0.459349E+11 | 0.319999E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874597E+09 |
Annual Sum or Average | 0.541708E+12 | 0.352938E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309334E+09 | 0.514047E+10 |
Minimum of Months | 0.415303E+11 | 0.267926E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54212823.73 |
Maximum of Months | 0.461508E+11 | 0.319999E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106764E+09 | 0.874597E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771018E+09 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638198E+09 |
March | 0.410691E+10 | 0.126106E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537946E+09 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1131058.25 | 0.342252E+09 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12597441.59 | 0.227185E+09 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 73919201.26 | 0.107272E+09 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 95662661.47 | 48522380.01 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 66413732.04 | 69987556.50 |
September | 0.396089E+10 | 0.121504E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 23672385.65 | 0.143317E+09 |
October | 0.408962E+10 | 0.125670E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3926443.97 | 0.364719E+09 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586519E+09 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790205E+09 |
Annual Sum or Average | 0.482060E+11 | 0.148074E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.277323E+09 | 0.462714E+10 |
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48522380.01 |
Maximum of Months | 0.410691E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 95662661.47 | 0.790205E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662965E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548033E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457918E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1448066.52 | 0.295443E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12951986.35 | 0.197590E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72526117.66 | 95995803.72 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93614482.17 | 44720980.39 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64966726.30 | 64470331.48 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23115838.96 | 0.130089E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3876411.51 | 0.320812E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502364E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678800E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272500E+09 | 0.399920E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44720980.39 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93614482.17 | 0.678800E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 15451.75 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 15451.75 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 15451.75 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 15451.75 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 15451.75 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 15451.75 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 15451.75 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 15451.75 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 15451.75 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 15451.75 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 15451.75 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 15451.75 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 716.35 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 320.64 | 21-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 716.35 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 299.52 | 04-FEB-06:40 |
March | 1169.53 | 01-MAR-00:10 | 716.35 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 268.35 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 716.35 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 13-APR-17:00 | 203.83 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 716.35 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.12 | 22-MAY-13:00 | 174.40 | 07-MAY-04:52 |
June | 1169.53 | 01-JUN-00:10 | 716.35 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 28-JUN-16:00 | 137.86 | 09-JUN-04:28 |
July | 1169.53 | 01-JUL-00:10 | 716.35 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.05 | 22-JUL-15:00 | 65.15 | 08-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 716.35 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.15 | 20-AUG-15:00 | 98.69 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 716.35 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 03-SEP-14:00 | 120.75 | 20-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 716.35 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.80 | 01-OCT-16:00 | 254.62 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 716.35 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 272.96 | 27-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 716.35 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 334.75 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | |||||
Maximum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 334.75 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 829.54 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 128.84 | 21-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 829.54 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 122.62 | 05-FEB-08:00 |
March | 1354.32 | 01-MAR-00:10 | 829.54 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 111.09 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 829.54 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | 13-APR-17:00 | 87.48 | 08-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 829.54 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 22-MAY-13:00 | 76.20 | 07-MAY-04:54 |
June | 1354.32 | 01-JUN-00:10 | 829.54 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 28-JUN-16:00 | 62.88 | 09-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 829.54 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.97 | 22-JUL-15:00 | 30.45 | 08-JUL-04:00 |
August | 1354.32 | 01-AUG-00:10 | 829.54 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 | 20-AUG-15:00 | 43.63 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 829.54 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 | 03-SEP-14:00 | 52.66 | 25-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 829.54 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 | 01-OCT-16:00 | 105.97 | 27-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 829.54 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 113.40 | 27-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 829.54 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 136.36 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 | |||||
Maximum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 136.36 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 668.27 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 292.51 | 21-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 668.27 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 14-FEB-16:00 | 273.23 | 04-FEB-06:30 |
March | 286.42 | 01-MAR-00:10 | 668.27 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.62 | 08-MAR-14:00 | 248.55 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 668.27 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 | 13-APR-17:00 | 195.71 | 06-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 668.27 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 | 22-MAY-13:00 | 170.50 | 07-MAY-04:54 |
June | 286.42 | 01-JUN-00:10 | 668.27 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 28-JUN-16:00 | 145.21 | 09-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 668.27 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 | 22-JUL-15:00 | 71.20 | 08-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 668.27 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 | 20-AUG-15:00 | 101.71 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 668.27 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 | 03-SEP-14:00 | 120.57 | 20-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 668.27 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.46 | 01-OCT-16:00 | 238.62 | 27-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 668.27 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 253.02 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 668.27 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 305.38 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.20 | |||||
Maximum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 305.38 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 339.04 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 168.76 | 21-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 339.04 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 14-FEB-16:00 | 157.64 | 04-FEB-06:40 |
March | 220.32 | 01-MAR-00:10 | 339.04 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 08-MAR-14:00 | 141.25 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 339.04 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 | 13-APR-17:00 | 110.04 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 339.04 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 | 22-MAY-13:00 | 95.82 | 07-MAY-04:54 |
June | 220.32 | 01-JUN-00:10 | 339.04 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.47 | 28-JUN-16:00 | 81.29 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 339.04 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 22-JUL-15:00 | 39.69 | 08-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 339.04 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.29 | 20-AUG-15:00 | 56.35 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 339.04 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 03-SEP-14:00 | 66.86 | 20-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 339.04 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 01-OCT-16:00 | 134.28 | 27-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 339.04 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 143.66 | 27-NOV-06:50 |
December | 220.32 | 01-DEC-00:10 | 339.04 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 176.18 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.69 | |||||
Maximum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 72.47 | 176.18 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 438.55 | 21-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 412.96 | 04-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 374.52 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 31.09 | 13-APR-17:00 | 316.20 | 08-APR-07:05 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 76.83 | 19-MAY-16:50 | 278.42 | 04-MAY-06:03 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 176.24 | 28-JUN-16:00 | 203.88 | 09-JUN-04:23 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 165.87 | 21-JUL-17:00 | 90.74 | 08-JUL-01:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 142.38 | 20-AUG-16:00 | 140.66 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 111.04 | 03-SEP-13:50 | 170.43 | 09-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 72.12 | 01-OCT-16:00 | 357.09 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 380.10 | 27-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 438.55 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 90.74 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 176.24 | 438.55 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1957.67 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 740.67 | 26-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1957.67 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 705.45 | 04-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1957.67 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 632.56 | 06-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1957.67 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 13-APR-17:00 | 492.49 | 08-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1957.67 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.70 | 22-MAY-13:00 | 434.97 | 07-MAY-04:54 |
June | 15368.40 | 01-JUN-00:10 | 1957.67 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.44 | 28-JUN-16:00 | 367.50 | 09-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1957.67 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.93 | 22-JUL-15:00 | 174.30 | 08-JUL-03:20 |
August | 15368.40 | 01-AUG-00:10 | 1957.67 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.03 | 20-AUG-15:00 | 249.82 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1957.67 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.95 | 03-SEP-14:00 | 301.54 | 25-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1957.67 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.47 | 01-OCT-16:00 | 600.89 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1957.67 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 654.08 | 27-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1957.67 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 786.28 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.30 | |||||
Maximum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 304.44 | 786.28 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 8554.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2167.09 | 20-JAN-02:00 |
February | 45622.98 | 01-FEB-00:10 | 8554.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2066.18 | 04-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 8554.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1861.27 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 8554.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.99 | 13-APR-17:00 | 1465.96 | 08-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 8554.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.53 | 22-MAY-13:00 | 1280.96 | 07-MAY-04:52 |
June | 45622.98 | 01-JUN-00:10 | 8554.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 869.76 | 28-JUN-16:00 | 1057.09 | 09-JUN-04:55 |
July | 45622.98 | 01-JUL-00:10 | 8554.32 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 834.05 | 22-JUL-15:00 | 498.18 | 08-JUL-03:50 |
August | 45622.98 | 01-AUG-00:10 | 8554.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 651.49 | 20-AUG-15:00 | 713.92 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 8554.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.70 | 03-SEP-14:00 | 865.88 | 09-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 8554.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.60 | 01-OCT-16:00 | 1780.40 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 8554.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1915.64 | 27-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 8554.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2295.47 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.18 | |||||
Maximum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 869.76 | 2295.47 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 187.08 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:09 | 174.80 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:07 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | 13-APR-17:00 | 119.24 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:10 | 100.84 | 07-MAY-04:54 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.46 | 22-JUL-15:10 | 37.12 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.19 | 01-AUG-15:10 | 49.09 | 25-AUG-21:30 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.72 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 159.37 | 27-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.27 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.12 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 187.07 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:10 | 174.79 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:10 | 156.71 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | 13-APR-17:00 | 119.23 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:10 | 100.83 | 07-MAY-04:54 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.87 | 22-JUL-15:10 | 36.80 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 | 20-AUG-15:10 | 48.94 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 01-OCT-16:00 | 148.71 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 159.36 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.26 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.80 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 132.12 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 51.93 | 26-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 132.12 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 49.72 | 05-FEB-08:10 |
March | 0.00 | 01-MAR-00:10 | 132.12 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 44.38 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 132.12 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 13-APR-17:00 | 34.76 | 06-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 132.12 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 22-MAY-13:00 | 29.51 | 07-MAY-04:52 |
June | 0.00 | 01-JUN-00:10 | 132.12 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 28-JUN-16:00 | 24.18 | 09-JUN-05:10 |
July | 0.00 | 01-JUL-00:10 | 132.12 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 22-JUL-15:00 | 11.70 | 08-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 132.12 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 | 20-AUG-15:00 | 17.29 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 132.12 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 03-SEP-14:00 | 21.06 | 20-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 132.12 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-OCT-16:00 | 44.02 | 27-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 132.12 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.03 | 27-NOV-07:10 |
December | 0.00 | 01-DEC-00:10 | 132.12 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 54.86 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 | |||||
Maximum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 54.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 52.21 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 14-FEB-16:00 | 48.79 | 04-FEB-06:20 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 08-MAR-16:04 | 43.74 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 13-APR-17:00 | 33.28 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 19-MAY-15:20 | 28.14 | 07-MAY-04:56 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 28-JUN-16:00 | 22.26 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 22-JUL-15:10 | 10.00 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 20-AUG-15:10 | 13.66 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 02-SEP-15:09 | 17.49 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 01-OCT-16:00 | 41.51 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 44.48 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 54.50 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 54.50 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 187.08 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:09 | 174.80 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:10 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 13-APR-17:00 | 123.74 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.84 | 07-MAY-04:54 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 | 22-JUL-15:10 | 43.66 | 08-JUL-07:40 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.34 | 20-AUG-15:10 | 52.59 | 11-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:09 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 01-OCT-16:00 | 148.72 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 159.38 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.27 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 187.07 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:07 | 174.79 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:07 | 156.71 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 13-APR-17:00 | 122.87 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.83 | 07-MAY-04:56 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 | 22-JUL-15:10 | 44.47 | 08-JUL-07:40 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.34 | 20-AUG-15:10 | 52.40 | 11-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:07 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.71 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 159.36 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.26 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 | 195.26 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 225.38 | 21-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 210.54 | 04-FEB-06:40 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 08-MAR-14:00 | 190.51 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 13-APR-17:00 | 151.63 | 08-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 | 22-MAY-13:00 | 131.77 | 07-MAY-04:54 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 28-JUN-16:00 | 110.73 | 09-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 | 22-JUL-15:00 | 54.61 | 08-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 20-AUG-15:00 | 77.37 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.80 | 03-SEP-14:00 | 93.36 | 20-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 01-OCT-16:00 | 183.28 | 26-OCT-04:30 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 196.61 | 27-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 235.54 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 235.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 187.50 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 14-FEB-16:10 | 175.22 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 08-MAR-16:07 | 157.13 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 13-APR-17:00 | 119.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 19-MAY-15:10 | 101.22 | 07-MAY-04:56 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 | 28-JUN-16:00 | 80.13 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 | 21-JUL-17:00 | 36.61 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.57 | 01-AUG-16:00 | 49.30 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.65 | 02-SEP-15:10 | 63.05 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.62 | 01-OCT-16:00 | 149.13 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 159.78 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.70 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.61 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 | 195.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 187.48 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 14-FEB-16:10 | 175.20 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 08-MAR-16:10 | 157.12 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 13-APR-17:00 | 119.62 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 19-MAY-15:10 | 101.21 | 07-MAY-04:56 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 28-JUN-16:00 | 80.12 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 | 21-JUL-17:00 | 36.28 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.82 | 01-AUG-16:00 | 49.30 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 | 02-SEP-15:10 | 63.04 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.62 | 01-OCT-16:00 | 149.11 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 159.77 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.68 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 195.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 95.93 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 14-FEB-16:10 | 89.65 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 08-MAR-16:10 | 80.39 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 13-APR-17:00 | 61.21 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 | 19-MAY-15:07 | 51.79 | 07-MAY-04:56 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 28-JUN-16:00 | 40.99 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 22-JUL-15:10 | 19.25 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.35 | 01-AUG-15:10 | 25.23 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 02-SEP-15:10 | 32.26 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.72 | 01-OCT-16:00 | 76.30 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 81.75 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 100.13 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 100.13 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 502.56 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 472.09 | 04-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 427.73 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.15 | 13-APR-17:00 | 336.79 | 08-APR-07:05 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 22-MAY-13:00 | 298.67 | 07-MAY-04:52 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 28-JUN-16:00 | 241.05 | 09-JUN-04:27 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 | 22-JUL-15:00 | 113.20 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 20-AUG-15:00 | 161.65 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.96 | 03-SEP-14:00 | 195.78 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 01-OCT-16:00 | 407.35 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 434.11 | 27-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 522.84 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.20 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 522.84 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 502.56 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 472.09 | 04-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 427.74 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.15 | 13-APR-17:00 | 338.88 | 08-APR-07:05 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 22-MAY-13:00 | 299.29 | 07-MAY-04:52 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 28-JUN-16:00 | 241.52 | 09-JUN-04:27 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 | 22-JUL-15:00 | 113.20 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 20-AUG-15:00 | 161.65 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.96 | 03-SEP-14:00 | 195.78 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 01-OCT-16:00 | 407.89 | 26-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 434.11 | 27-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 522.84 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.20 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 522.84 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 449.84 | 21-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 422.60 | 04-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 382.86 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 24.46 | 13-APR-17:00 | 338.22 | 08-APR-07:05 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 71.74 | 22-MAY-13:00 | 284.46 | 04-MAY-06:03 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 173.75 | 28-JUN-16:00 | 222.35 | 09-JUN-04:27 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 166.53 | 22-JUL-15:00 | 101.36 | 08-JUL-03:00 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 129.84 | 20-AUG-15:00 | 144.66 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 103.93 | 03-SEP-14:00 | 175.21 | 09-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 58.35 | 01-OCT-16:00 | 365.04 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 388.54 | 27-NOV-06:10 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 468.07 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 101.36 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 173.75 | 468.07 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 399.67 | 21-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 373.41 | 04-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 334.70 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 | 13-APR-17:00 | 258.53 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.06 | 22-MAY-13:00 | 224.31 | 07-MAY-04:54 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.85 | 28-JUN-16:00 | 188.60 | 09-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.83 | 22-JUL-15:00 | 92.98 | 08-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.92 | 20-AUG-15:00 | 131.57 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.59 | 03-SEP-14:00 | 158.35 | 20-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 | 01-OCT-16:00 | 317.59 | 26-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 340.39 | 27-NOV-06:40 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 417.19 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.98 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.85 | 417.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 40334.30 | 13-JAN-18:19 | 63899.40 | 103011.64 | 70976.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51984.29 | 03-FEB-17:10 | 12779.88 | 8584.44 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37753.96 | 17-MAR-06:03 | 20447.81 | 34336.94 | 24334.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32398.16 | 08-APR-07:23 | 19169.82 | 20602.53 | 15209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45299.96 | 05-MAY-04:20 | 34505.68 | 10300.96 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20308.46 | 09-JUN-04:25 | 115018.92 | 34336.53 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20771.22 | 27-JUL-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22299.31 | 23-AUG-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24026.49 | 08-SEP-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40219.80 | 25-OCT-17:36 | 44729.58 | 72108.15 | 49683.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44336.83 | 12-NOV-08:49 | 63899.40 | 68675.11 | 50697.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48441.96 | 11-DEC-09:01 | 20447.81 | 54940.09 | 40558.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20308.46 | 10223.90 | 8584.44 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51984.29 | 115018.92 | 103011.64 | 70976.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5319.70 | 27-JAN-11:15 | 1559.38 | 1193.92 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.61 |
February | 5556.27 | 06-FEB-14:13 | 1039.58 | 795.95 | 1010.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.62 |
March | 4554.12 | 04-MAR-11:05 | 2339.06 | 1193.92 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.01 |
April | 3378.59 | 13-APR-12:50 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
May | 2643.58 | 13-MAY-13:00 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 0.00 |
June | 3057.97 | 29-JUN-14:30 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 0.00 |
July | 3260.55 | 22-JUL-13:30 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 120.37 | 0.00 |
August | 4042.59 | 22-AUG-13:20 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 0.00 |
September | 4851.83 | 28-SEP-13:10 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 | 0.00 |
October | 4929.28 | 05-OCT-12:50 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
November | 6209.51 | 28-NOV-10:46 | 1819.27 | 1392.91 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.62 |
December | 7406.30 | 31-DEC-10:38 | 3898.44 | 1432.71 | 1732.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2643.58 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7406.30 | 3898.44 | 1432.71 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 224.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3187.05 | 26-JAN-22:30 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.99 |
February | 3148.88 | 09-FEB-22:08 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.64 |
March | 2981.26 | 09-MAR-23:45 | 2708.64 | 553.03 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.60 |
April | 2847.28 | 06-APR-00:58 | 13543.20 | 1382.57 | 2089.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.31 |
May | 3690.89 | 02-MAY-04:02 | 8125.92 | 1106.05 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 |
June | 2338.84 | 28-JUN-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 0.00 |
July | 2401.06 | 21-JUL-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 0.00 |
August | 2339.17 | 18-AUG-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 0.00 |
September | 2187.52 | 13-SEP-20:03 | 7223.04 | 4424.22 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 |
October | 4580.18 | 12-OCT-04:20 | 13543.20 | 1843.42 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 |
November | 3730.61 | 10-NOV-02:10 | 2708.64 | 184.34 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.63 |
December | 3833.21 | 01-DEC-02:27 | 4062.96 | 276.51 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2187.52 | 1203.84 | 184.34 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4580.18 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 89.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1577.58 | 15-JAN-21:59 | 2545.92 | 4455.10 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 |
February | 1582.18 | 21-FEB-00:20 | 1145.66 | 594.01 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.39 |
March | 1666.53 | 12-MAR-00:48 | 2227.68 | 2227.55 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.99 |
April | 1626.63 | 06-APR-00:58 | 2864.16 | 1113.78 | 2209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.15 |
May | 1479.80 | 02-MAY-04:02 | 1718.50 | 891.02 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.38 |
June | 1950.24 | 28-JUN-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 52.12 | 0.00 |
July | 1975.85 | 21-JUL-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 0.00 |
August | 1857.12 | 18-AUG-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 | 0.00 |
September | 1535.31 | 01-SEP-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 |
October | 1504.00 | 12-OCT-04:20 | 2864.16 | 1485.03 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.98 |
November | 1688.40 | 12-NOV-09:01 | 1113.84 | 1559.29 | 2474.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.96 |
December | 1720.72 | 29-DEC-23:14 | 2864.16 | 2227.55 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1479.80 | 222.77 | 594.01 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1975.85 | 2864.16 | 4455.10 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 191.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1016.55 | 15-JAN-21:59 | 1958.40 | 2260.22 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.55 |
February | 1023.59 | 21-FEB-00:20 | 881.28 | 301.36 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.15 |
March | 1077.40 | 12-MAR-00:48 | 1713.60 | 1130.08 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.67 |
April | 1052.19 | 06-APR-00:58 | 2203.20 | 565.07 | 637.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.94 |
May | 954.96 | 02-MAY-04:02 | 1321.92 | 452.04 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 |
June | 1004.77 | 28-JUN-19:10 | 171.36 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 | 0.00 |
July | 1065.01 | 21-JUL-18:30 | 171.36 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 | 0.00 |
August | 927.38 | 18-AUG-18:40 | 171.36 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 | 0.00 |
September | 717.42 | 03-SEP-10:35 | 146.88 | 226.02 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 | 0.00 |
October | 969.26 | 12-OCT-04:20 | 2203.20 | 753.41 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 |
November | 1092.04 | 12-NOV-09:01 | 856.80 | 791.05 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 |
December | 1114.03 | 29-DEC-23:14 | 2203.20 | 1130.08 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 717.42 | 146.88 | 226.02 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1114.03 | 2203.20 | 2260.22 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 | 107.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 57167.26 | 08-JAN-19:58 | 5443.20 | 3175.23 | 34657.02 | 301085.63 | 0.00 | 0.00 | 0.00 | 0.00 | 295.77 |
February | 54893.61 | 02-FEB-19:23 | 7056.00 | 4032.04 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 301.31 |
March | 52901.80 | 04-MAR-21:57 | 7056.00 | 3528.04 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 317.33 |
April | 45710.74 | 05-APR-06:46 | 4032.00 | 2520.03 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 251.95 |
May | 39020.06 | 19-MAY-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.11 | 0.00 |
June | 39541.62 | 28-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 71.16 | 0.00 |
July | 39565.06 | 21-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.88 | 0.00 |
August | 39395.01 | 17-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 51.34 | 0.00 |
September | 38999.57 | 01-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 |
October | 51481.39 | 25-OCT-20:50 | 7257.60 | 3628.84 | 38989.14 | 338721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 287.07 |
November | 51088.74 | 27-NOV-20:13 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 310.07 |
December | 57683.31 | 15-DEC-20:55 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 301.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38999.57 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57683.31 | 7257.60 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 77.88 | 317.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22112.13 | 08-JAN-10:08 | 34152.00 | 574.25 | 1625.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.03 |
February | 22355.62 | 04-FEB-13:13 | 30736.80 | 717.81 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.11 |
March | 21192.70 | 04-MAR-11:05 | 30736.80 | 717.81 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.06 |
April | 18817.32 | 07-APR-02:26 | 153684.00 | 2175.19 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.15 |
May | 27090.75 | 02-MAY-04:02 | 92210.40 | 2610.23 | 1828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.21 |
June | 11980.71 | 27-JUN-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 102.76 | 0.00 |
July | 12246.60 | 21-JUL-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 120.33 | 0.00 |
August | 13390.85 | 20-AUG-12:00 | 5122.80 | 143.56 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 184.29 | 0.00 |
September | 15534.67 | 28-SEP-13:10 | 3415.20 | 119.64 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 | 0.00 |
October | 19118.48 | 30-OCT-03:14 | 153684.00 | 2175.19 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.00 |
November | 25097.83 | 28-NOV-10:46 | 23906.40 | 837.45 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.83 |
December | 30813.66 | 31-DEC-10:38 | 51228.00 | 861.38 | 2438.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11980.71 | 3415.20 | 119.64 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30813.66 | 153684.00 | 2610.23 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 184.29 | 497.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 64334.80 | 24-JAN-21:43 | 405537.60 | 76038.40 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.14 |
February | 64780.88 | 21-FEB-00:48 | 456229.80 | 19009.60 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.36 |
March | 69769.95 | 26-MAR-01:22 | 354845.40 | 19009.60 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1252.70 |
April | 63730.60 | 04-APR-01:51 | 319360.86 | 6653.36 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.59 |
May | 59520.88 | 02-MAY-02:37 | 456229.80 | 9504.80 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1130.34 |
June | 42363.25 | 28-JUN-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 279.42 | 0.00 |
July | 43032.21 | 21-JUL-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 343.69 | 0.00 |
August | 42404.54 | 18-AUG-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 106.09 | 0.00 |
September | 40881.51 | 13-SEP-20:03 | 243322.56 | 45623.04 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 |
October | 85692.07 | 22-OCT-05:16 | 354845.40 | 28514.40 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.19 |
November | 67469.16 | 15-NOV-18:10 | 76038.30 | 17108.64 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.88 |
December | 94848.37 | 01-DEC-01:00 | 273737.88 | 11405.76 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 40881.51 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94848.37 | 456229.80 | 76038.40 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 343.69 | 1498.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4930.65 | 05-JAN-17:01 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
February | 5148.69 | 15-FEB-18:01 | 777.60 | 1126.80 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.73 |
March | 5319.19 | 30-MAR-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.52 |
April | 5584.06 | 25-APR-16:21 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 |
May | 5206.44 | 06-MAY-19:41 | 1170.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.77 |
June | 5204.79 | 13-JUN-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 |
July | 4779.90 | 20-JUL-18:02 | 831.60 | 1122.60 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 | 0.00 |
August | 4709.34 | 23-AUG-17:21 | 680.40 | 985.95 | 885.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.55 |
September | 5178.16 | 26-SEP-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 |
October | 5285.26 | 17-OCT-19:21 | 1386.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.34 |
November | 4699.98 | 01-NOV-15:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 |
December | 4699.81 | 05-DEC-16:01 | 972.00 | 588.63 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4699.81 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5584.06 | 1800.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 | 98.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4494.25 | 06-JAN-16:01 | 972.00 | 588.56 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.75 |
February | 4604.93 | 14-FEB-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
March | 5251.12 | 30-MAR-18:11 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.40 |
April | 5515.95 | 25-APR-16:21 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
May | 5128.28 | 20-MAY-21:51 | 1386.00 | 1786.70 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 |
June | 5165.93 | 13-JUN-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 |
July | 4746.91 | 20-JUL-18:02 | 831.60 | 1122.47 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 72.27 | 0.00 |
August | 4711.22 | 23-AUG-17:21 | 680.40 | 985.84 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 |
September | 4981.88 | 21-SEP-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 |
October | 4935.57 | 05-OCT-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 |
November | 4565.13 | 02-NOV-15:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 |
December | 4454.94 | 29-DEC-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4454.94 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5515.95 | 1800.00 | 1870.78 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 72.27 | 77.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 838.15 | 03-JAN-12:40 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 |
February | 859.25 | 14-FEB-13:00 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 |
March | 732.33 | 08-MAR-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
April | 558.26 | 13-APR-13:20 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
May | 409.55 | 13-MAY-13:10 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 0.00 |
June | 452.02 | 29-JUN-14:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 0.00 |
July | 497.01 | 23-JUL-13:30 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 0.00 |
August | 630.00 | 22-AUG-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 0.00 |
September | 800.65 | 28-SEP-13:20 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 | 0.00 |
October | 859.24 | 19-OCT-12:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
November | 845.22 | 20-NOV-12:10 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
December | 847.06 | 31-DEC-13:35 | 0.00 | 87.20 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 409.55 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 859.25 | 0.00 | 87.20 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 23.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 327.30 | 06-JAN-19:03 | 1386.00 | 1176.17 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 |
February | 1293.07 | 14-FEB-19:01 | 1386.00 | 1176.17 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
March | 1383.57 | 13-MAR-20:41 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
April | 1491.33 | 27-APR-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
May | 1509.48 | 20-MAY-21:51 | 1386.00 | 1123.31 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 |
June | 1542.30 | 18-JUN-08:51 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 0.00 |
July | 1463.17 | 04-JUL-18:02 | 702.00 | 792.93 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 0.00 |
August | 1354.58 | 22-AUG-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
September | 1509.18 | 30-SEP-21:51 | 1386.00 | 1123.31 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 |
October | 1470.87 | 05-OCT-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 |
November | 1324.37 | 02-NOV-18:11 | 1386.00 | 1176.17 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
December | 761.71 | 03-DEC-09:01 | 432.00 | 592.05 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 327.30 | 432.00 | 592.05 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1542.30 | 1800.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 31.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4202.73 | 29-JAN-09:01 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.36 |
February | 4237.05 | 14-FEB-19:01 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.82 |
March | 4303.21 | 13-MAR-20:41 | 1602.00 | 1871.00 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.23 |
April | 4980.43 | 28-APR-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 |
May | 5005.28 | 14-MAY-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 |
June | 5037.21 | 14-JUN-08:21 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
July | 4639.43 | 13-JUL-08:32 | 216.00 | 554.99 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
August | 4690.88 | 03-AUG-08:32 | 216.00 | 554.99 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 |
September | 4589.49 | 02-SEP-08:32 | 324.00 | 706.35 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 |
October | 4534.04 | 05-OCT-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
November | 4203.25 | 22-NOV-09:01 | 324.00 | 832.49 | 1019.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.42 |
December | 4220.17 | 29-DEC-09:01 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4202.73 | 216.00 | 554.99 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5037.21 | 1800.00 | 1871.00 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 128.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3941.18 | 29-JAN-09:01 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.38 |
February | 4079.42 | 14-FEB-09:01 | 252.00 | 647.42 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.60 |
March | 4201.66 | 11-MAR-09:01 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 |
April | 4930.73 | 28-APR-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.48 |
May | 4963.13 | 14-MAY-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 |
June | 5136.01 | 14-JUN-08:62 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
July | 4611.04 | 13-JUL-08:32 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
August | 4658.65 | 03-AUG-08:32 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 |
September | 4557.26 | 02-SEP-08:32 | 324.00 | 706.27 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 |
October | 4331.14 | 05-OCT-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 |
November | 4062.34 | 22-NOV-09:01 | 324.00 | 832.39 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.37 |
December | 3918.72 | 29-DEC-09:01 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3918.72 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | |
Maximum of Months | 5136.01 | 1800.00 | 1408.34 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3263.88 | 26-JAN-23:27 | 20370.20 | 5601.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 |
February | 3280.56 | 21-FEB-00:20 | 9053.42 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.83 |
March | 3505.89 | 12-MAR-00:48 | 17603.88 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.95 |
April | 3413.48 | 06-APR-00:58 | 22633.56 | 3112.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.03 |
May | 3117.04 | 02-MAY-04:02 | 13580.14 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.39 |
June | 3269.75 | 23-JUN-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 | 0.00 |
July | 3445.58 | 21-JUL-18:30 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 0.00 |
August | 3240.38 | 18-AUG-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.79 | 0.00 |
September | 2675.60 | 13-SEP-15:03 | 7544.52 | 3112.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 |
October | 3167.74 | 12-OCT-04:20 | 22633.56 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.71 |
November | 3484.53 | 12-NOV-09:01 | 8801.94 | 4357.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.96 |
December | 3558.72 | 29-DEC-23:14 | 22633.56 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2675.60 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3558.72 | 22633.56 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 145.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5315.49 | 05-JAN-17:01 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.53 |
February | 5562.21 | 15-FEB-18:01 | 777.60 | 1126.80 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.22 |
March | 5757.99 | 30-MAR-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.18 |
April | 5909.35 | 25-APR-16:21 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 |
May | 5638.20 | 06-MAY-19:41 | 1170.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.44 |
June | 5467.15 | 13-JUN-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 |
July | 5062.79 | 21-JUL-18:02 | 831.60 | 1122.60 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 | 0.00 |
August | 4981.13 | 23-AUG-17:02 | 583.20 | 845.10 | 758.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 |
September | 5438.34 | 26-SEP-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.09 |
October | 5712.20 | 17-OCT-19:21 | 1386.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 |
November | 4952.84 | 02-NOV-15:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
December | 4960.82 | 05-DEC-16:01 | 972.00 | 588.63 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4952.84 | 583.20 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5909.35 | 1800.00 | 2102.25 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 | 98.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4711.72 | 05-JAN-17:01 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.02 |
February | 4845.89 | 14-FEB-19:01 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 |
March | 5591.38 | 30-MAR-18:11 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.53 |
April | 5826.04 | 25-APR-16:21 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
May | 5558.94 | 06-MAY-19:41 | 1170.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.22 |
June | 5421.23 | 13-JUN-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 |
July | 5020.52 | 21-JUL-18:02 | 831.60 | 1122.47 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 72.10 | 0.00 |
August | 4907.00 | 23-AUG-17:21 | 680.40 | 985.84 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
September | 5197.94 | 21-SEP-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 |
October | 5357.57 | 13-OCT-17:41 | 777.60 | 1126.67 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.99 |
November | 4786.94 | 02-NOV-15:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 |
December | 4672.95 | 31-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4672.95 | 378.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5826.04 | 1800.00 | 2102.00 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 72.10 | 70.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2616.97 | 05-JAN-17:01 | 972.00 | 370.03 | 1238.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 |
February | 2705.24 | 14-FEB-19:01 | 1386.00 | 1176.17 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.55 |
March | 2672.79 | 12-MAR-19:31 | 1170.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.15 |
April | 2673.10 | 12-APR-16:21 | 972.00 | 370.03 | 1238.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
May | 2470.06 | 20-MAY-21:51 | 1386.00 | 1123.31 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 |
June | 2486.54 | 18-JUN-08:51 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 0.00 |
July | 2329.17 | 21-JUL-18:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 | 0.00 |
August | 2370.47 | 29-AUG-16:31 | 972.00 | 370.03 | 1238.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
September | 2617.08 | 26-SEP-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 |
October | 2737.09 | 17-OCT-19:21 | 1386.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 |
November | 2377.41 | 01-NOV-15:01 | 680.40 | 259.02 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 |
December | 2373.83 | 05-DEC-16:01 | 972.00 | 370.03 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2329.17 | 540.00 | 259.02 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2737.09 | 1800.00 | 1321.54 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 | 51.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34542.29 | 30-JAN-23:24 | 215910.14 | 9167.57 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 |
February | 32894.83 | 27-FEB-23:54 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.58 |
March | 38754.70 | 03-MAR-23:51 | 215910.14 | 9167.57 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.69 |
April | 36144.84 | 19-APR-04:42 | 134943.84 | 3819.82 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.00 |
May | 33224.61 | 02-MAY-01:58 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.23 |
June | 30683.07 | 09-JUN-04:28 | 269887.68 | 7639.64 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.37 |
July | 24038.13 | 21-JUL-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 71.84 | 0.00 |
August | 23306.52 | 17-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.78 | 0.00 |
September | 22297.56 | 01-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 |
October | 34410.05 | 30-OCT-03:12 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.33 |
November | 37456.00 | 24-NOV-03:07 | 80966.30 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.85 |
December | 44265.96 | 29-DEC-23:14 | 269887.68 | 11459.46 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22297.56 | 26988.77 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44265.96 | 269887.68 | 11459.46 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.84 | 333.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36784.39 | 30-JAN-23:24 | 215910.14 | 9167.57 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.35 |
February | 35788.67 | 07-FEB-22:08 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.41 |
March | 42149.96 | 03-MAR-23:51 | 215910.14 | 9167.57 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.89 |
April | 39156.40 | 19-APR-04:42 | 134943.84 | 3819.82 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.00 |
May | 34900.18 | 02-MAY-01:58 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.73 |
June | 32315.62 | 09-JUN-04:23 | 269887.68 | 7639.64 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.86 |
July | 25237.19 | 21-JUL-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 71.80 | 0.00 |
August | 24500.44 | 17-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.74 | 0.00 |
September | 23437.15 | 01-SEP-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 |
October | 36121.05 | 30-OCT-03:12 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.73 |
November | 40633.55 | 24-NOV-03:07 | 80966.30 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.40 |
December | 50025.59 | 29-DEC-23:14 | 269887.68 | 11459.46 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23437.15 | 26988.77 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50025.59 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.80 | 333.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 44686.95 | 19-JAN-13:37 | 3735.98 | 2354.57 | 104389.99 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 259.20 |
February | 40659.69 | 21-FEB-07:28 | 10674.24 | 6727.35 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 264.99 |
March | 43877.02 | 05-MAR-09:14 | 13342.80 | 4036.41 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 283.05 |
April | 36915.50 | 23-APR-07:08 | 8005.68 | 3229.13 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 258.29 |
May | 35482.83 | 05-MAY-07:06 | 5337.12 | 2690.94 | 74564.28 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 238.13 |
June | 31806.58 | 29-JUN-10:40 | 1601.14 | 1009.10 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 101.20 | 0.00 |
July | 32098.49 | 23-JUL-10:40 | 1601.14 | 807.28 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 90.81 | 0.00 |
August | 32074.98 | 20-AUG-10:40 | 1601.14 | 807.28 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 71.63 | 0.00 |
September | 31883.14 | 03-SEP-10:40 | 1601.14 | 807.28 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 52.52 | 0.00 |
October | 43302.38 | 25-OCT-11:29 | 5337.12 | 3363.68 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 245.90 |
November | 44025.79 | 27-NOV-18:47 | 13342.80 | 8072.82 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 288.51 |
December | 44040.56 | 20-DEC-17:21 | 12008.52 | 3027.31 | 134215.70 | 202435.49 | 0.00 | 0.00 | 0.00 | 0.00 | 287.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31806.58 | 1601.14 | 807.28 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44686.95 | 13342.80 | 8072.82 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 101.20 | 288.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6587.65 | 15-JAN-21:59 | 21292.80 | 13175.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.41 |
February | 6553.40 | 21-FEB-00:20 | 9581.76 | 1756.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.19 |
March | 6995.69 | 12-MAR-00:48 | 18631.20 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.63 |
April | 6766.33 | 06-APR-00:58 | 23954.40 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.55 |
May | 6089.04 | 02-MAY-04:02 | 14372.64 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.63 |
June | 7376.38 | 28-JUN-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.55 | 0.00 |
July | 7465.78 | 22-JUL-13:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.32 | 0.00 |
August | 7559.35 | 20-AUG-13:10 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.22 | 0.00 |
September | 7491.96 | 03-SEP-13:30 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.92 | 0.00 |
October | 6842.33 | 01-OCT-13:30 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 0.00 |
November | 7062.30 | 12-NOV-09:01 | 9315.60 | 4611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.42 |
December | 7176.79 | 29-DEC-23:14 | 23954.40 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6089.04 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7559.35 | 23954.40 | 13175.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.55 | 257.41 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.399731E+12 | 270596.49 | 27-JAN-20:49 | 0.529513E+12 | 518943.10 | 02-JAN-21:30 |
February | 0.361900E+12 | 261274.23 | 22-FEB-20:19 | 0.468348E+12 | 503737.84 | 23-FEB-20:40 |
March | 0.401407E+12 | 274934.90 | 27-MAR-19:19 | 0.481916E+12 | 467255.29 | 03-MAR-19:00 |
April | 0.419958E+12 | 323854.78 | 28-APR-18:49 | 0.437170E+12 | 415253.63 | 23-APR-20:40 |
May | 0.468331E+12 | 360812.79 | 19-MAY-19:10 | 0.422638E+12 | 353192.15 | 01-MAY-17:10 |
June | 0.532334E+12 | 395950.63 | 27-JUN-19:19 | 0.390516E+12 | 350967.31 | 01-JUN-17:10 |
July | 0.604699E+12 | 410749.35 | 21-JUL-19:19 | 0.395012E+12 | 348887.84 | 07-JUL-17:30 |
August | 0.583766E+12 | 393187.57 | 18-AUG-19:10 | 0.393684E+12 | 344636.80 | 28-AUG-17:49 |
September | 0.504450E+12 | 362842.49 | 13-SEP-19:19 | 0.386025E+12 | 349955.59 | 29-SEP-17:30 |
October | 0.452636E+12 | 327871.66 | 05-OCT-18:10 | 0.435179E+12 | 469218.12 | 24-OCT-17:00 |
November | 0.393774E+12 | 273524.20 | 02-NOV-19:10 | 0.467773E+12 | 493965.47 | 27-NOV-19:30 |
December | 0.403210E+12 | 269301.73 | 06-DEC-20:49 | 0.536178E+12 | 520048.43 | 06-DEC-19:00 |
Annual Sum or Average | 0.552620E+13 | 0.534395E+13 | ||||
Minimum of Months | 0.361900E+12 | 261274.23 | 0.386025E+12 | 344636.80 | ||
Maximum of Months | 0.604699E+12 | 410749.35 | 0.536178E+12 | 520048.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.742469E+11 | 0.261372E+11 | 0.140828E+12 | 0.552132E+11 | 0.468415E+11 | 0.615230E+10 | 0.00 | 0.139164E+11 | 0.00 | 0.00 | 0.234927E+11 | 0.770411E+10 | 0.00 |
February | 0.668950E+11 | 0.222616E+11 | 0.127191E+12 | 0.498700E+11 | 0.421919E+11 | 0.607443E+10 | 0.00 | 0.161157E+11 | 0.00 | 0.00 | 0.196376E+11 | 0.696163E+10 | 0.00 |
March | 0.737208E+11 | 0.227023E+11 | 0.140882E+12 | 0.552165E+11 | 0.464909E+11 | 0.746935E+10 | 0.00 | 0.255044E+11 | 0.00 | 0.00 | 0.165197E+11 | 0.770268E+10 | 0.00 |
April | 0.709343E+11 | 0.199784E+11 | 0.136245E+12 | 0.534311E+11 | 0.473376E+11 | 0.818377E+10 | 0.00 | 0.607884E+11 | 0.00 | 0.00 | 0.105863E+11 | 0.746479E+10 | 0.00 |
May | 0.731195E+11 | 0.189469E+11 | 0.140860E+12 | 0.552141E+11 | 0.504708E+11 | 0.872577E+10 | 0.00 | 0.982351E+11 | 0.00 | 0.00 | 0.983800E+10 | 0.770424E+10 | 0.00 |
June | 0.704834E+11 | 0.174348E+11 | 0.136336E+12 | 0.534341E+11 | 0.553657E+11 | 0.880152E+10 | 0.00 | 0.165391E+12 | 0.00 | 0.00 | 0.125380E+11 | 0.745690E+10 | 0.00 |
July | 0.730459E+11 | 0.184863E+11 | 0.140770E+12 | 0.552105E+11 | 0.610111E+11 | 0.936488E+10 | 0.00 | 0.218901E+12 | 0.00 | 0.00 | 0.148907E+11 | 0.771235E+10 | 0.00 |
August | 0.731296E+11 | 0.198783E+11 | 0.140892E+12 | 0.552160E+11 | 0.617826E+11 | 0.937490E+10 | 0.00 | 0.197879E+12 | 0.00 | 0.00 | 0.125833E+11 | 0.770439E+10 | 0.00 |
September | 0.712459E+11 | 0.211300E+11 | 0.136256E+12 | 0.534314E+11 | 0.567805E+11 | 0.876040E+10 | 0.00 | 0.136440E+12 | 0.00 | 0.00 | 0.781880E+10 | 0.746627E+10 | 0.00 |
October | 0.740323E+11 | 0.238539E+11 | 0.140818E+12 | 0.552130E+11 | 0.542292E+11 | 0.841094E+10 | 0.00 | 0.724387E+11 | 0.00 | 0.00 | 0.107168E+11 | 0.770285E+10 | 0.00 |
November | 0.717516E+11 | 0.248253E+11 | 0.136330E+12 | 0.534331E+11 | 0.482239E+11 | 0.721643E+10 | 0.00 | 0.212461E+11 | 0.00 | 0.00 | 0.182735E+11 | 0.744858E+10 | 0.00 |
December | 0.743568E+11 | 0.266178E+11 | 0.140770E+12 | 0.552117E+11 | 0.483093E+11 | 0.623818E+10 | 0.00 | 0.144465E+11 | 0.00 | 0.00 | 0.243500E+11 | 0.771213E+10 | 0.00 |
Annual Sum or Average | 0.866962E+12 | 0.262253E+12 | 0.165818E+13 | 0.650095E+12 | 0.619035E+12 | 0.947729E+11 | 0.00 | 0.104130E+13 | 0.00 | 0.00 | 0.181245E+12 | 0.907409E+11 | 0.00 |
Minimum of Months | 0.668950E+11 | 0.174348E+11 | 0.127191E+12 | 0.498700E+11 | 0.421919E+11 | 0.607443E+10 | 0.00 | 0.139164E+11 | 0.00 | 0.00 | 0.781880E+10 | 0.696163E+10 | 0.00 |
Maximum of Months | 0.743568E+11 | 0.266178E+11 | 0.140892E+12 | 0.552165E+11 | 0.617826E+11 | 0.937490E+10 | 0.00 | 0.218901E+12 | 0.00 | 0.00 | 0.243500E+11 | 0.771235E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.899171E+11 | 0.00 | 0.287678E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.699351E+11 | 0.00 | 0.261209E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.453169E+11 | 0.00 | 0.284575E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.243720E+11 | 0.00 | 0.265842E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.828335E+10 | 0.00 | 0.262376E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.651480E+09 | 0.00 | 0.242751E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 52219063.98 | 0.00 | 0.243139E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 57536003.96 | 0.00 | 0.241588E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.605957E+09 | 0.00 | 0.238448E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.269861E+11 | 0.00 | 0.256290E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.607021E+11 | 0.00 | 0.259980E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.104228E+12 | 0.00 | 0.280130E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.431107E+12 | 0.00 | 0.312401E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 52219063.98 | 0.00 | 0.238448E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.104228E+12 | 0.00 | 0.287678E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 71560.59 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39721.54 | 02-JAN-07:19 | 51960.00 | 30-JAN-22:10 | 3982.81 | 26-JAN-09:50 | 0.00 | 01-JAN-00:10 |
February | 71560.59 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39721.54 | 01-FEB-07:19 | 49481.83 | 03-FEB-13:00 | 3949.59 | 02-FEB-10:39 | 0.00 | 01-FEB-00:10 |
March | 71560.59 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39721.54 | 13-MAR-06:19 | 52612.20 | 06-MAR-23:10 | 3937.94 | 29-MAR-00:00 | 0.00 | 01-MAR-00:10 |
April | 71560.59 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39718.92 | 05-APR-06:19 | 47824.30 | 19-APR-06:19 | 3896.77 | 16-APR-04:40 | 0.00 | 01-APR-00:10 |
May | 71560.59 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39720.45 | 22-MAY-06:19 | 40098.82 | 19-MAY-21:00 | 3974.74 | 21-MAY-19:30 | 0.00 | 01-MAY-00:10 |
June | 71560.59 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39719.36 | 08-JUN-06:19 | 47759.80 | 27-JUN-21:10 | 4565.10 | 26-JUN-18:30 | 0.00 | 01-JUN-00:10 |
July | 71560.59 | 03-JUL-19:19 | 16690.39 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39719.39 | 28-JUL-06:19 | 49593.37 | 21-JUL-21:10 | 4472.50 | 03-JUL-19:00 | 0.00 | 01-JUL-00:10 |
August | 71560.59 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39719.09 | 23-AUG-06:19 | 50172.07 | 18-AUG-21:10 | 4513.46 | 15-AUG-18:19 | 0.00 | 01-AUG-00:10 |
September | 71560.59 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39721.54 | 08-SEP-06:19 | 46826.61 | 13-SEP-21:10 | 4291.59 | 02-SEP-20:30 | 0.00 | 01-SEP-00:10 |
October | 71560.59 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39721.54 | 02-OCT-06:19 | 52645.03 | 12-OCT-22:40 | 4095.42 | 04-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 71560.59 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39721.54 | 01-NOV-06:19 | 56045.46 | 19-NOV-09:30 | 3958.52 | 27-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 71560.59 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39721.54 | 01-DEC-07:19 | 53384.99 | 29-DEC-23:40 | 3976.63 | 06-DEC-10:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 71560.59 | 16690.39 | 89171.45 | 39718.92 | 40098.82 | 3896.77 | 0.00 | |||||||
Maximum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.54 | 56045.46 | 4565.10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 40036.26 | 01-JAN-14:09 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.18 | 02-JAN-19:10 | 0.00 |
February | 74843.62 | 14-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.18 | 13-FEB-19:10 | 0.00 |
March | 74806.76 | 08-MAR-16:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4738.30 | 06-MAR-19:10 | 0.00 |
April | 95074.51 | 13-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:30 | 4738.52 | 05-APR-18:49 | 0.00 |
May | 116669.34 | 19-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-01:00 | 4738.46 | 16-MAY-18:30 | 0.00 |
June | 164770.71 | 28-JUN-15:09 | 0.00 | 0.00 | 9938.94 | 02-JUN-14:00 | 4738.69 | 20-JUN-06:30 | 0.00 |
July | 166884.95 | 21-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 02-JUL-09:30 | 4738.63 | 20-JUL-18:10 | 0.00 |
August | 148293.17 | 20-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 01-AUG-07:49 | 4738.28 | 16-AUG-06:19 | 0.00 |
September | 122332.50 | 02-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-09:50 | 4738.70 | 28-SEP-18:10 | 0.00 |
October | 110008.75 | 06-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-11:09 | 4738.28 | 19-OCT-18:10 | 0.00 |
November | 45704.05 | 02-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:49 | 4738.59 | 08-NOV-19:10 | 0.00 |
December | 31134.23 | 31-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.75 | 14-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 31134.23 | 0.00 | 0.00 | 9938.94 | 4738.18 | 0.00 | |||
Maximum of Months | 166884.95 | 0.00 | 0.00 | 9938.94 | 4738.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 270596.49 | 27-JAN-20:49 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 40624.10 | 3483.94 | 0.00 | 4394.93 | 0.00 |
February | 261274.23 | 22-FEB-20:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 32969.46 | 3498.69 | 0.00 | 2171.83 | 0.00 |
March | 274934.90 | 27-MAR-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 27321.93 | 3290.75 | 0.00 | 30161.60 | 0.00 |
April | 323854.78 | 28-APR-18:49 | 63637.18 | 77573.37 | 16690.39 | 31806.12 | 29699.89 | 3512.01 | 0.00 | 84675.03 | 0.00 |
May | 360812.79 | 19-MAY-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 33513.61 | 3557.80 | 0.00 | 101647.19 | 0.00 |
June | 395950.63 | 27-JUN-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.30 | 38373.96 | 3671.33 | 0.00 | 131500.92 | 0.00 |
July | 410749.35 | 21-JUL-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.30 | 41610.06 | 3667.99 | 0.00 | 142947.55 | 0.00 |
August | 393187.57 | 18-AUG-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 41258.29 | 4118.59 | 0.00 | 125658.60 | 0.00 |
September | 362842.49 | 13-SEP-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 36744.10 | 4199.44 | 0.00 | 98906.03 | 0.00 |
October | 327871.66 | 05-OCT-18:10 | 63637.18 | 77573.37 | 16690.39 | 31790.09 | 31279.92 | 3595.97 | 0.00 | 94676.14 | 0.00 |
November | 273524.20 | 02-NOV-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 30510.67 | 3244.35 | 0.00 | 26882.51 | 0.00 |
December | 269301.73 | 06-DEC-20:49 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 39753.00 | 3678.35 | 0.00 | 3082.84 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 261274.23 | 63637.18 | 77573.37 | 16690.39 | 31790.09 | 27321.93 | 3244.35 | 0.00 | 2171.83 | 0.00 | |
Maximum of Months | 410749.35 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 41610.06 | 4199.44 | 0.00 | 142947.55 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 184725.08 | 26-JAN-23:19 | 0.00 | 286522.90 | 25-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 195910.24 | 23-FEB-22:19 | 0.00 | 289935.96 | 23-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 168258.99 | 02-MAR-23:30 | 0.00 | 290662.75 | 29-MAR-20:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 175863.19 | 04-APR-05:40 | 0.00 | 272106.15 | 04-APR-20:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 156972.95 | 06-MAY-04:49 | 0.00 | 249602.34 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 45780.82 | 09-JUN-04:30 | 0.00 | 247363.65 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4865.30 | 12-JUL-21:00 | 0.00 | 244639.52 | 07-JUL-17:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 4201.71 | 23-AUG-08:00 | 0.00 | 240388.48 | 28-AUG-17:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 40224.30 | 24-SEP-05:00 | 0.00 | 246280.89 | 28-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 164720.46 | 24-OCT-22:19 | 0.00 | 249109.51 | 26-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 188584.94 | 15-NOV-06:40 | 0.00 | 259553.68 | 20-NOV-21:10 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 193995.49 | 02-DEC-23:00 | 0.00 | 287741.54 | 19-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 4201.71 | 0.00 | 240388.48 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 195910.24 | 0.00 | 290662.75 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.80 | 0.67 | 24.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.84 | 0.50 | 24.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.76 | 0.33 | 24.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.67 | 1.83 | 24.67 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 24.73 | 3.33 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.84 | 1.83 | 24.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 25.31 | 51.00 | 25.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 25.22 | 45.67 | 25.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 25.21 | 37.83 | 25.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 25.14 | 17.00 | 25.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.18 | 3.33 | 25.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 25.15 | 14.67 | 25.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 25.15 | 37.33 | 25.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 25.30 | 57.17 | 25.30 |
Annual Sum or Average | 0.00 | 0.00 | 264.00 | 25.23 | 264.00 | 25.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 25.31 | 57.17 | 25.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.88 | 2.00 | 24.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.77 | 2.17 | 24.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.17 | 24.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.69 | 0.83 | 24.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.69 | 1.50 | 24.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.73 | 4.83 | 24.73 |
Annual Sum or Average | 0.00 | 0.00 | 11.50 | 24.75 | 11.50 | 24.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.88 | 4.83 | 24.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.69 | 0.17 | 24.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.17 | 24.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.62 | 0.50 | 24.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.68 | 0.17 | 24.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 24.65 | 1.00 | 24.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.69 | 0.50 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.81 | 0.33 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.86 | 1.00 | 21.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.17 | 21.78 | 4.17 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.86 | 1.50 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.84 | 1.00 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 21.78 | 2.33 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.84 | 1.00 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 0.17 | 20.52 | 0.17 | 20.52 | 2.83 | 21.59 | 2.83 | 21.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.52 | 0.17 | 20.52 | 1.00 | 21.74 | 1.00 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.86 | 0.33 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.10 | 2.50 | 22.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.26 | 7.00 | 22.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.11 | 7.17 | 22.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 22.19 | 6.50 | 22.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.23 | 6.00 | 22.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.03 | 0.50 | 22.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 30.00 | 22.18 | 30.00 | 22.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.26 | 7.17 | 22.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.84 | 0.33 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.09 | 2.50 | 22.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 22.31 | 7.33 | 22.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 22.12 | 7.67 | 22.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.17 | 6.17 | 22.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.13 | 4.00 | 22.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.87 | 0.50 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.50 | 22.17 | 28.50 | 22.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 22.31 | 7.67 | 22.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.82 | 0.17 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.77 | 1.67 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.82 | 3.17 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.81 | 2.50 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.81 | 0.50 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.00 | 21.80 | 9.00 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.82 | 3.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.81 | 1.50 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.84 | 2.67 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 21.81 | 5.50 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.84 | 2.67 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.73 | 2.50 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.85 | 7.00 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.94 | 6.83 | 21.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.33 | 21.86 | 17.33 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.94 | 7.00 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.77 | 5.17 | 24.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.85 | 3.17 | 24.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.76 | 7.17 | 24.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.89 | 6.00 | 24.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.80 | 1.17 | 24.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.71 | 3.67 | 24.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.81 | 6.00 | 24.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.79 | 6.33 | 24.79 |
Annual Sum or Average | 0.00 | 0.00 | 38.67 | 24.80 | 38.67 | 24.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.89 | 7.17 | 24.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.83 | 6.17 | 24.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.86 | 4.33 | 24.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.80 | 8.33 | 24.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.89 | 7.00 | 24.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.81 | 1.33 | 24.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.74 | 4.17 | 24.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.81 | 8.50 | 24.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.83 | 8.67 | 24.83 |
Annual Sum or Average | 0.00 | 0.00 | 48.50 | 24.83 | 48.50 | 24.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.89 | 8.67 | 24.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 | 25.18 | 74.67 | 25.18 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 69.83 | 25.23 | 69.83 | 25.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 | 25.26 | 54.33 | 25.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 25.11 | 34.33 | 25.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25.18 | 7.17 | 25.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 25.16 | 24.83 | 25.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 25.16 | 60.00 | 25.16 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 91.33 | 25.24 | 91.33 | 25.24 |
Annual Sum or Average | 0.00 | 0.00 | 416.50 | 25.20 | 416.50 | 25.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 91.33 | 25.26 | 91.33 | 25.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 662.17 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
February | 642.83 | 23.75 | 0.00 | 23.75 | 0.00 | 23.75 |
March | 738.83 | 23.55 | 0.00 | 23.55 | 0.00 | 23.55 |
April | 720.00 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
May | 659.50 | 23.50 | 8.00 | 23.51 | 0.00 | 23.51 |
June | 413.00 | 23.57 | 80.83 | 23.63 | 19.83 | 23.63 |
July | 294.17 | 23.85 | 508.83 | 23.88 | 267.17 | 23.88 |
August | 175.17 | 23.94 | 534.00 | 23.93 | 171.33 | 23.94 |
September | 68.00 | 23.90 | 299.33 | 23.96 | 48.33 | 23.96 |
October | 345.33 | 23.96 | 70.50 | 23.96 | 0.00 | 23.96 |
November | 478.00 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
December | 626.50 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
Annual Sum or Average | 5823.50 | 23.73 | 1501.50 | 23.77 | 506.67 | 23.78 |
Minimum of Months | 68.00 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
Maximum of Months | 738.83 | 23.97 | 534.00 | 23.97 | 267.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 587.50 | 21.56 | 141.17 | 21.86 | 43.50 | 21.81 |
February | 509.67 | 21.69 | 108.83 | 22.03 | 14.83 | 22.01 |
March | 599.33 | 21.86 | 70.17 | 22.07 | 3.50 | 22.06 |
April | 531.50 | 22.29 | 27.33 | 22.37 | 0.00 | 22.37 |
May | 517.50 | 22.36 | 49.17 | 22.50 | 0.00 | 22.50 |
June | 305.50 | 22.64 | 272.33 | 23.24 | 13.83 | 23.25 |
July | 238.33 | 23.40 | 652.33 | 23.66 | 217.50 | 23.61 |
August | 197.17 | 23.31 | 602.50 | 23.70 | 137.00 | 23.67 |
September | 236.67 | 22.81 | 431.67 | 23.49 | 43.33 | 23.48 |
October | 387.00 | 22.27 | 243.17 | 22.90 | 5.33 | 22.89 |
November | 523.00 | 21.90 | 126.50 | 22.32 | 0.00 | 22.32 |
December | 566.00 | 21.56 | 155.33 | 21.91 | 46.33 | 21.85 |
Annual Sum or Average | 5199.17 | 22.12 | 2880.50 | 22.71 | 525.17 | 22.72 |
Minimum of Months | 197.17 | 21.56 | 27.33 | 21.86 | 0.00 | 21.81 |
Maximum of Months | 599.33 | 23.40 | 652.33 | 23.70 | 217.50 | 23.67 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.50 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
February | 656.17 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
March | 699.67 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
April | 632.33 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
May | 423.33 | 23.54 | 69.50 | 23.59 | 1.33 | 23.59 |
June | 115.67 | 23.55 | 257.50 | 23.84 | 24.33 | 23.85 |
July | 296.83 | 23.94 | 715.67 | 23.95 | 296.83 | 23.95 |
August | 198.00 | 23.96 | 727.00 | 23.96 | 198.00 | 23.96 |
September | 72.33 | 23.88 | 489.00 | 23.94 | 67.83 | 23.94 |
October | 387.50 | 23.48 | 122.83 | 23.59 | 1.83 | 23.59 |
November | 651.00 | 23.35 | 0.00 | 23.35 | 0.00 | 23.35 |
December | 743.67 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 5615.00 | 23.35 | 2381.50 | 23.53 | 590.17 | 23.56 |
Minimum of Months | 72.33 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
Maximum of Months | 743.67 | 23.96 | 727.00 | 23.96 | 296.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
February | 672.00 | 21.61 | 2.67 | 21.61 | 2.67 | 21.61 |
March | 744.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
April | 720.00 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
May | 702.00 | 23.30 | 1.17 | 23.30 | 0.00 | 23.30 |
June | 359.17 | 23.69 | 80.67 | 23.74 | 3.33 | 23.74 |
July | 139.00 | 23.97 | 617.00 | 23.98 | 139.00 | 23.98 |
August | 86.17 | 23.90 | 483.50 | 23.95 | 86.00 | 23.94 |
September | 334.67 | 23.60 | 100.00 | 23.66 | 30.00 | 23.67 |
October | 661.00 | 22.83 | 7.17 | 22.84 | 0.00 | 22.84 |
November | 720.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
December | 744.00 | 21.36 | 9.17 | 21.35 | 9.17 | 21.35 |
Annual Sum or Average | 6626.00 | 22.40 | 1301.33 | 22.65 | 270.17 | 22.69 |
Minimum of Months | 86.17 | 21.36 | 0.00 | 21.35 | 0.00 | 21.35 |
Maximum of Months | 744.00 | 23.97 | 617.00 | 23.98 | 139.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.14 | 3.50 | 21.14 | 3.50 | 21.14 |
February | 672.00 | 21.29 | 6.67 | 21.28 | 6.67 | 21.28 |
March | 744.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
April | 720.00 | 22.43 | 0.00 | 22.43 | 0.00 | 22.43 |
May | 742.33 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
June | 442.50 | 23.44 | 59.33 | 23.51 | 4.17 | 23.51 |
July | 152.33 | 23.82 | 597.50 | 23.88 | 152.33 | 23.87 |
August | 119.00 | 23.63 | 385.83 | 23.80 | 93.50 | 23.78 |
September | 549.67 | 23.36 | 53.50 | 23.38 | 32.33 | 23.38 |
October | 732.33 | 22.53 | 3.50 | 22.53 | 0.00 | 22.53 |
November | 720.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
December | 744.00 | 21.11 | 51.00 | 21.10 | 51.00 | 21.10 |
Annual Sum or Average | 7082.17 | 22.15 | 1160.83 | 22.37 | 343.50 | 22.40 |
Minimum of Months | 119.00 | 21.11 | 0.00 | 21.10 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 23.82 | 597.50 | 23.88 | 152.33 | 23.87 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 208.83 | 23.86 | 651.00 | 23.88 | 167.83 | 23.97 |
February | 198.83 | 23.98 | 592.17 | 23.91 | 171.00 | 23.99 |
March | 233.33 | 24.11 | 667.67 | 23.95 | 221.67 | 24.01 |
April | 210.50 | 24.01 | 652.67 | 23.89 | 203.00 | 23.93 |
May | 277.83 | 23.99 | 700.50 | 23.83 | 275.50 | 23.87 |
June | 375.50 | 23.98 | 711.83 | 23.81 | 375.50 | 23.86 |
July | 585.17 | 23.89 | 744.00 | 23.79 | 585.17 | 23.82 |
August | 556.00 | 23.90 | 744.00 | 23.79 | 556.00 | 23.82 |
September | 409.50 | 23.96 | 715.17 | 23.77 | 409.50 | 23.82 |
October | 269.50 | 24.00 | 694.83 | 23.80 | 263.33 | 23.85 |
November | 215.17 | 24.00 | 646.17 | 23.89 | 195.50 | 23.95 |
December | 208.50 | 23.84 | 644.00 | 23.89 | 161.50 | 23.99 |
Annual Sum or Average | 3748.67 | 23.95 | 8164.00 | 23.84 | 3585.50 | 23.89 |
Minimum of Months | 198.83 | 23.84 | 592.17 | 23.77 | 161.50 | 23.82 |
Maximum of Months | 585.17 | 24.11 | 744.00 | 23.95 | 585.17 | 24.01 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.17 | 22.87 | 154.50 | 23.17 | 0.00 | 23.17 |
February | 348.00 | 23.01 | 158.83 | 23.33 | 0.00 | 23.33 |
March | 359.00 | 23.08 | 133.17 | 23.33 | 0.00 | 23.33 |
April | 243.33 | 23.25 | 156.83 | 23.54 | 0.00 | 23.54 |
May | 216.17 | 23.20 | 315.17 | 23.63 | 32.33 | 23.63 |
June | 99.67 | 23.55 | 548.00 | 23.85 | 65.50 | 23.86 |
July | 435.50 | 23.94 | 744.00 | 23.93 | 435.50 | 23.93 |
August | 328.33 | 23.93 | 743.50 | 23.93 | 328.33 | 23.93 |
September | 135.00 | 23.84 | 677.17 | 23.94 | 128.00 | 23.93 |
October | 159.33 | 23.13 | 410.67 | 23.74 | 18.33 | 23.75 |
November | 263.17 | 23.09 | 206.67 | 23.50 | 0.00 | 23.50 |
December | 440.17 | 22.97 | 174.00 | 23.28 | 0.00 | 23.28 |
Annual Sum or Average | 3471.83 | 23.29 | 4422.50 | 23.66 | 1008.00 | 23.69 |
Minimum of Months | 99.67 | 22.87 | 133.17 | 23.17 | 0.00 | 23.17 |
Maximum of Months | 444.17 | 23.94 | 744.00 | 23.94 | 435.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.67 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
February | 352.33 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
March | 348.50 | 23.49 | 1.33 | 23.49 | 0.00 | 23.49 |
April | 377.67 | 23.65 | 2.67 | 23.65 | 0.00 | 23.65 |
May | 224.00 | 23.55 | 159.83 | 23.72 | 12.67 | 23.72 |
June | 74.83 | 23.76 | 417.00 | 23.92 | 47.33 | 23.93 |
July | 408.83 | 23.96 | 739.67 | 23.96 | 408.83 | 23.96 |
August | 309.50 | 23.97 | 744.00 | 23.96 | 309.50 | 23.96 |
September | 118.67 | 23.96 | 627.33 | 23.97 | 118.33 | 23.97 |
October | 132.17 | 23.57 | 222.17 | 23.83 | 13.17 | 23.84 |
November | 269.00 | 23.57 | 18.17 | 23.60 | 0.00 | 23.60 |
December | 544.50 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
Annual Sum or Average | 3650.67 | 23.63 | 2932.17 | 23.78 | 909.83 | 23.80 |
Minimum of Months | 74.83 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
Maximum of Months | 544.50 | 23.97 | 744.00 | 23.97 | 408.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.83 | 21.31 | 295.17 | 21.19 | 295.17 | 21.12 |
February | 653.33 | 21.40 | 138.00 | 21.34 | 133.50 | 21.28 |
March | 698.33 | 21.57 | 56.83 | 21.74 | 33.00 | 21.75 |
April | 626.33 | 21.84 | 44.67 | 22.16 | 9.17 | 22.24 |
May | 637.83 | 21.83 | 27.00 | 22.01 | 5.33 | 22.06 |
June | 549.67 | 21.63 | 65.33 | 21.92 | 4.00 | 21.96 |
July | 521.17 | 21.62 | 171.00 | 22.14 | 54.00 | 22.28 |
August | 495.67 | 21.58 | 190.83 | 22.22 | 38.67 | 22.32 |
September | 447.67 | 21.49 | 164.33 | 22.17 | 8.17 | 22.19 |
October | 581.83 | 21.69 | 129.67 | 22.20 | 42.33 | 22.26 |
November | 702.00 | 21.47 | 63.67 | 21.45 | 60.33 | 21.41 |
December | 743.83 | 21.32 | 343.17 | 21.19 | 343.17 | 21.12 |
Annual Sum or Average | 7398.50 | 21.55 | 1689.67 | 21.75 | 1026.83 | 21.72 |
Minimum of Months | 447.67 | 21.31 | 27.00 | 21.19 | 4.00 | 21.12 |
Maximum of Months | 743.83 | 21.84 | 343.17 | 22.22 | 343.17 | 22.32 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 605.67 | 20.85 | 605.67 | 20.83 |
February | 668.67 | 21.08 | 315.67 | 20.98 | 315.67 | 20.92 |
March | 718.00 | 21.38 | 100.00 | 21.41 | 85.50 | 21.36 |
April | 655.33 | 21.79 | 35.67 | 22.01 | 7.33 | 22.05 |
May | 658.50 | 21.85 | 23.67 | 22.00 | 6.33 | 22.04 |
June | 549.67 | 21.64 | 69.50 | 21.96 | 4.67 | 22.00 |
July | 524.17 | 21.63 | 165.83 | 22.15 | 53.83 | 22.29 |
August | 514.50 | 21.61 | 163.17 | 22.17 | 39.67 | 22.27 |
September | 515.33 | 21.67 | 89.00 | 22.00 | 8.00 | 22.01 |
October | 646.67 | 21.57 | 94.33 | 21.71 | 56.00 | 21.66 |
November | 718.00 | 21.19 | 242.33 | 21.11 | 241.00 | 21.06 |
December | 744.00 | 20.84 | 638.33 | 20.79 | 638.33 | 20.77 |
Annual Sum or Average | 7656.83 | 21.40 | 2543.17 | 21.45 | 2062.00 | 21.37 |
Minimum of Months | 514.50 | 20.84 | 23.67 | 20.79 | 4.67 | 20.77 |
Maximum of Months | 744.00 | 21.85 | 638.33 | 22.17 | 638.33 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 508.00 | 20.88 | 508.00 | 20.86 |
February | 672.00 | 20.99 | 241.17 | 20.94 | 241.17 | 20.91 |
March | 744.00 | 21.20 | 32.00 | 21.19 | 32.00 | 21.18 |
April | 720.00 | 21.57 | 0.17 | 21.57 | 0.17 | 21.57 |
May | 744.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
June | 715.83 | 21.91 | 0.17 | 21.91 | 0.00 | 21.91 |
July | 733.00 | 22.00 | 40.17 | 22.07 | 38.17 | 22.13 |
August | 725.00 | 21.95 | 25.50 | 22.00 | 20.67 | 22.03 |
September | 718.83 | 21.91 | 3.33 | 21.91 | 3.33 | 21.92 |
October | 743.83 | 21.44 | 28.17 | 21.42 | 28.17 | 21.40 |
November | 720.00 | 21.05 | 218.17 | 21.01 | 218.17 | 20.99 |
December | 744.00 | 20.86 | 596.83 | 20.83 | 596.83 | 20.82 |
Annual Sum or Average | 8724.50 | 21.46 | 1693.67 | 21.38 | 1686.67 | 21.31 |
Minimum of Months | 672.00 | 20.86 | 0.00 | 20.83 | 0.00 | 20.82 |
Maximum of Months | 744.00 | 22.00 | 596.83 | 22.07 | 596.83 | 22.13 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 285.83 | 21.24 | 285.83 | 21.17 |
February | 671.50 | 21.50 | 156.50 | 21.40 | 156.50 | 21.33 |
March | 742.33 | 21.75 | 32.33 | 21.72 | 32.33 | 21.69 |
April | 682.83 | 22.03 | 2.00 | 22.04 | 0.17 | 22.05 |
May | 622.33 | 21.91 | 38.83 | 22.10 | 7.67 | 22.14 |
June | 507.17 | 21.84 | 119.00 | 22.45 | 34.00 | 22.71 |
July | 505.00 | 21.97 | 264.50 | 22.76 | 74.67 | 23.06 |
August | 476.67 | 21.90 | 274.17 | 22.79 | 61.83 | 23.06 |
September | 432.83 | 21.63 | 197.50 | 22.42 | 21.00 | 22.55 |
October | 602.83 | 21.73 | 74.83 | 21.87 | 30.50 | 21.85 |
November | 714.50 | 21.56 | 69.17 | 21.50 | 69.17 | 21.46 |
December | 744.00 | 21.37 | 344.17 | 21.24 | 344.17 | 21.17 |
Annual Sum or Average | 7446.00 | 21.69 | 1858.83 | 21.89 | 1117.83 | 21.90 |
Minimum of Months | 432.83 | 21.37 | 2.00 | 21.24 | 0.17 | 21.17 |
Maximum of Months | 744.00 | 22.03 | 344.17 | 22.79 | 344.17 | 23.06 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 584.17 | 20.87 | 584.17 | 20.86 |
February | 672.00 | 21.07 | 338.83 | 21.00 | 338.83 | 20.97 |
March | 744.00 | 21.56 | 81.33 | 21.51 | 81.33 | 21.47 |
April | 703.17 | 22.02 | 9.83 | 22.02 | 7.83 | 22.01 |
May | 648.00 | 21.96 | 35.50 | 22.13 | 8.83 | 22.17 |
June | 510.00 | 21.88 | 107.33 | 22.48 | 36.83 | 22.78 |
July | 506.00 | 21.99 | 240.50 | 22.76 | 76.17 | 23.08 |
August | 482.67 | 21.89 | 222.17 | 22.72 | 60.83 | 23.00 |
September | 476.00 | 21.72 | 77.50 | 22.15 | 15.83 | 22.25 |
October | 691.17 | 21.77 | 62.33 | 21.76 | 54.00 | 21.72 |
November | 719.83 | 21.18 | 244.67 | 21.13 | 244.67 | 21.09 |
December | 744.00 | 20.80 | 642.00 | 20.78 | 642.00 | 20.77 |
Annual Sum or Average | 7640.83 | 21.52 | 2646.17 | 21.60 | 2151.33 | 21.56 |
Minimum of Months | 476.00 | 20.80 | 9.83 | 20.78 | 7.83 | 20.77 |
Maximum of Months | 744.00 | 22.02 | 642.00 | 22.76 | 642.00 | 23.08 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
February | 672.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
March | 744.00 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
April | 720.00 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
May | 723.67 | 23.31 | 0.00 | 23.31 | 0.00 | 23.31 |
June | 420.67 | 23.63 | 83.67 | 23.67 | 28.33 | 23.68 |
July | 333.00 | 23.93 | 635.67 | 23.95 | 333.00 | 23.94 |
August | 227.33 | 23.93 | 564.50 | 23.95 | 227.33 | 23.94 |
September | 222.50 | 23.72 | 180.33 | 23.78 | 73.33 | 23.78 |
October | 580.33 | 23.09 | 28.67 | 23.13 | 2.17 | 23.13 |
November | 720.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
December | 744.00 | 21.42 | 4.17 | 21.42 | 4.17 | 21.42 |
Annual Sum or Average | 6851.50 | 22.55 | 1497.00 | 22.80 | 668.33 | 22.88 |
Minimum of Months | 222.50 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 744.00 | 23.93 | 635.67 | 23.95 | 333.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.67 | 21.22 | 437.33 | 21.10 | 437.33 | 21.04 |
February | 646.17 | 21.32 | 275.00 | 21.24 | 268.67 | 21.17 |
March | 695.17 | 21.57 | 160.83 | 21.70 | 138.00 | 21.68 |
April | 616.83 | 21.85 | 93.67 | 22.25 | 47.67 | 22.34 |
May | 626.50 | 21.82 | 51.50 | 22.06 | 23.33 | 22.14 |
June | 536.33 | 21.59 | 87.00 | 21.95 | 5.83 | 22.01 |
July | 519.50 | 21.62 | 210.33 | 22.18 | 61.67 | 22.30 |
August | 497.50 | 21.61 | 224.17 | 22.27 | 48.17 | 22.38 |
September | 452.67 | 21.49 | 186.67 | 22.18 | 15.00 | 22.20 |
October | 583.83 | 21.74 | 184.33 | 22.28 | 88.67 | 22.35 |
November | 696.33 | 21.40 | 203.67 | 21.33 | 200.50 | 21.27 |
December | 740.33 | 21.24 | 446.50 | 21.10 | 446.50 | 21.04 |
Annual Sum or Average | 7347.83 | 21.52 | 2561.00 | 21.71 | 1781.33 | 21.67 |
Minimum of Months | 452.67 | 21.22 | 51.50 | 21.10 | 5.83 | 21.04 |
Maximum of Months | 740.33 | 21.85 | 446.50 | 22.28 | 446.50 | 22.38 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.81 | 661.33 | 20.76 | 661.33 | 20.74 |
February | 667.50 | 21.00 | 445.83 | 20.91 | 444.83 | 20.87 |
March | 711.50 | 21.30 | 240.00 | 21.32 | 218.33 | 21.24 |
April | 639.67 | 21.76 | 99.17 | 22.04 | 59.00 | 22.05 |
May | 643.00 | 21.83 | 49.17 | 22.04 | 23.67 | 22.11 |
June | 534.83 | 21.60 | 85.00 | 21.97 | 6.00 | 22.03 |
July | 521.17 | 21.63 | 191.00 | 22.16 | 61.83 | 22.29 |
August | 513.00 | 21.60 | 186.83 | 22.18 | 47.50 | 22.29 |
September | 510.67 | 21.61 | 106.33 | 21.96 | 16.00 | 21.98 |
October | 638.33 | 21.50 | 161.00 | 21.67 | 115.67 | 21.60 |
November | 717.17 | 21.08 | 428.50 | 21.00 | 427.17 | 20.96 |
December | 744.00 | 20.74 | 679.33 | 20.71 | 679.33 | 20.70 |
Annual Sum or Average | 7584.83 | 21.34 | 3333.50 | 21.40 | 2760.67 | 21.31 |
Minimum of Months | 510.67 | 20.74 | 49.17 | 20.71 | 6.00 | 20.70 |
Maximum of Months | 744.00 | 21.83 | 679.33 | 22.18 | 679.33 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 660.17 | 21.32 | 124.67 | 21.26 | 120.83 | 21.21 |
February | 584.17 | 21.37 | 64.67 | 21.38 | 58.00 | 21.34 |
March | 644.83 | 21.50 | 23.67 | 21.55 | 12.67 | 21.54 |
April | 690.50 | 21.97 | 0.50 | 21.97 | 0.00 | 21.97 |
May | 699.00 | 21.89 | 5.00 | 21.88 | 5.00 | 21.88 |
June | 620.33 | 21.75 | 6.83 | 21.77 | 0.50 | 21.78 |
July | 562.17 | 21.66 | 114.67 | 21.99 | 50.83 | 22.10 |
August | 523.00 | 21.57 | 185.83 | 22.12 | 32.50 | 22.18 |
September | 463.00 | 21.53 | 187.17 | 22.17 | 6.33 | 22.18 |
October | 511.33 | 21.42 | 172.33 | 22.18 | 20.83 | 22.16 |
November | 618.33 | 21.37 | 24.33 | 21.40 | 12.17 | 21.39 |
December | 645.00 | 21.27 | 162.17 | 21.21 | 160.83 | 21.17 |
Annual Sum or Average | 7221.83 | 21.56 | 1071.83 | 21.73 | 480.50 | 21.72 |
Minimum of Months | 463.00 | 21.27 | 0.50 | 21.21 | 0.00 | 21.17 |
Maximum of Months | 699.00 | 21.97 | 187.17 | 22.18 | 160.83 | 22.18 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.33 | 23.53 | 2.17 | 23.54 | 0.00 | 23.54 |
February | 203.00 | 23.51 | 8.17 | 23.54 | 0.00 | 23.54 |
March | 83.17 | 23.57 | 46.83 | 23.76 | 0.00 | 23.76 |
April | 20.33 | 23.64 | 74.17 | 23.96 | 0.00 | 23.96 |
May | 21.33 | 23.86 | 400.00 | 23.99 | 13.83 | 23.99 |
June | 49.17 | 24.00 | 677.17 | 24.00 | 49.17 | 24.00 |
July | 421.67 | 24.00 | 744.00 | 24.00 | 421.67 | 24.00 |
August | 318.17 | 24.00 | 744.00 | 24.00 | 318.17 | 24.00 |
September | 121.33 | 23.99 | 719.17 | 23.99 | 121.33 | 23.99 |
October | 64.33 | 23.60 | 305.17 | 23.92 | 17.50 | 23.93 |
November | 213.00 | 23.55 | 50.33 | 23.65 | 0.00 | 23.65 |
December | 442.67 | 23.57 | 1.17 | 23.58 | 0.00 | 23.58 |
Annual Sum or Average | 2303.50 | 23.73 | 3772.33 | 23.90 | 941.67 | 23.91 |
Minimum of Months | 20.33 | 23.51 | 1.17 | 23.54 | 0.00 | 23.54 |
Maximum of Months | 442.67 | 24.00 | 744.00 | 24.00 | 421.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.67 | 23.47 | 14.83 | 23.57 | 0.00 | 23.57 |
February | 54.00 | 23.51 | 58.50 | 23.81 | 0.00 | 23.81 |
March | 1.50 | 23.19 | 117.67 | 24.06 | 0.00 | 24.06 |
April | 0.33 | 23.32 | 150.00 | 24.04 | 0.00 | 24.04 |
May | 11.33 | 23.93 | 450.00 | 24.00 | 10.00 | 24.00 |
June | 44.50 | 24.00 | 698.67 | 24.00 | 44.50 | 24.00 |
July | 402.50 | 24.00 | 744.00 | 24.00 | 402.50 | 24.00 |
August | 302.00 | 24.00 | 744.00 | 24.00 | 302.00 | 24.00 |
September | 113.17 | 24.00 | 720.00 | 24.00 | 113.17 | 24.00 |
October | 25.83 | 23.73 | 358.67 | 23.98 | 14.83 | 23.98 |
November | 50.67 | 23.50 | 102.17 | 23.88 | 0.00 | 23.88 |
December | 191.83 | 23.55 | 11.50 | 23.60 | 0.00 | 23.60 |
Annual Sum or Average | 1313.33 | 23.84 | 4170.00 | 23.97 | 887.00 | 23.97 |
Minimum of Months | 0.33 | 23.19 | 11.50 | 23.57 | 0.00 | 23.57 |
Maximum of Months | 402.50 | 24.00 | 744.00 | 24.06 | 402.50 | 24.06 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.33 | 24.23 | 708.33 | 24.16 | 485.33 | 24.18 |
February | 454.83 | 24.25 | 655.33 | 24.17 | 454.83 | 24.19 |
March | 517.33 | 24.15 | 742.17 | 24.10 | 517.33 | 24.12 |
April | 509.83 | 24.07 | 718.67 | 24.06 | 509.83 | 24.06 |
May | 540.83 | 24.01 | 742.83 | 24.01 | 540.83 | 24.01 |
June | 556.00 | 23.99 | 720.00 | 23.99 | 556.00 | 23.99 |
July | 664.17 | 23.99 | 744.00 | 23.99 | 664.17 | 23.99 |
August | 632.33 | 23.99 | 744.00 | 23.99 | 632.33 | 23.99 |
September | 558.67 | 23.99 | 720.00 | 23.99 | 558.67 | 23.99 |
October | 528.67 | 24.06 | 740.83 | 24.04 | 528.67 | 24.04 |
November | 497.33 | 24.17 | 712.33 | 24.11 | 497.33 | 24.13 |
December | 480.00 | 24.30 | 698.17 | 24.21 | 479.50 | 24.24 |
Annual Sum or Average | 6425.33 | 24.09 | 8646.67 | 24.06 | 6424.83 | 24.07 |
Minimum of Months | 454.83 | 23.99 | 655.33 | 23.99 | 454.83 | 23.99 |
Maximum of Months | 664.17 | 24.30 | 744.00 | 24.21 | 664.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
February | 672.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
March | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
April | 704.67 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
May | 589.67 | 23.07 | 4.00 | 23.08 | 0.00 | 23.08 |
June | 256.83 | 23.34 | 176.33 | 23.59 | 12.83 | 23.60 |
July | 197.50 | 23.82 | 655.33 | 23.90 | 197.50 | 23.88 |
August | 140.50 | 23.75 | 608.83 | 23.89 | 129.00 | 23.87 |
September | 254.17 | 23.32 | 273.50 | 23.61 | 43.83 | 23.61 |
October | 586.50 | 22.70 | 50.00 | 22.79 | 0.00 | 22.79 |
November | 720.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
December | 744.00 | 21.38 | 10.50 | 21.38 | 10.50 | 21.37 |
Annual Sum or Average | 6353.83 | 22.27 | 1778.50 | 22.63 | 393.67 | 22.68 |
Minimum of Months | 140.50 | 21.38 | 0.00 | 21.38 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 23.82 | 655.33 | 23.90 | 197.50 | 23.88 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.90335 | 21.24960 | 0.19017 | 5.82097 |
February | 672.00000 | 23.75717 | 22.67610 | 0.15565 | 5.61084 |
March | 744.00000 | 23.55150 | 21.68883 | 0.09346 | 5.32426 |
April | 720.00000 | 23.50138 | 18.60054 | 0.06053 | 5.23140 |
May | 744.00000 | 23.53304 | 26.97568 | -0.8331 | 19.92730 |
June | 720.00000 | 23.69966 | 36.57032 | -0.7011 | 15.58542 |
July | 744.00000 | 23.83207 | 50.73453 | -0.5470 | 11.40877 |
August | 744.00000 | 23.89711 | 48.96910 | -0.5272 | 10.90471 |
September | 720.00000 | 23.94980 | 40.99962 | -0.5522 | 11.48825 |
October | 744.00000 | 23.97057 | 26.62348 | 0.26408 | 6.55380 |
November | 720.00000 | 23.98184 | 20.89083 | 0.22397 | 6.08669 |
December | 744.00000 | 23.96933 | 19.08057 | 0.20202 | 5.88783 |
Annual Sum or Average | 8760.00000 | 23.79602 | 29.64862 | -0.1660 | 9.17675 |
Minimum of Months | 672.00000 | 23.50138 | 18.60054 | -0.8331 | 5.23140 |
Maximum of Months | 744.00000 | 23.98184 | 50.73453 | 0.26408 | 19.92730 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07209 | 22.34008 | -0.1786 | 8.62687 |
February | 672.00000 | 22.24705 | 23.37380 | -0.1157 | 8.08336 |
March | 744.00000 | 22.26838 | 22.02653 | -0.1153 | 7.40794 |
April | 720.00000 | 22.72107 | 18.22581 | -0.0175 | 6.65147 |
May | 744.00000 | 22.80717 | 26.99762 | -0.9281 | 25.47536 |
June | 720.00000 | 23.31629 | 36.24211 | -0.6577 | 15.93592 |
July | 744.00000 | 23.68410 | 50.17675 | -0.4029 | 9.18394 |
August | 744.00000 | 23.69144 | 48.68806 | -0.3905 | 9.27747 |
September | 720.00000 | 23.51827 | 41.52850 | -0.4940 | 12.24520 |
October | 744.00000 | 23.06358 | 27.37289 | 0.17072 | 8.16455 |
November | 720.00000 | 22.47248 | 22.12921 | -0.0416 | 7.70263 |
December | 744.00000 | 22.15263 | 20.20317 | -0.1670 | 8.77983 |
Annual Sum or Average | 8760.00000 | 22.83748 | 30.00053 | -0.2793 | 10.64873 |
Minimum of Months | 672.00000 | 22.07209 | 18.22581 | -0.9281 | 6.65147 |
Maximum of Months | 744.00000 | 23.69144 | 50.17675 | 0.17072 | 25.47536 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.00833 | 23.48224 | 0.00054 | 5.32253 |
February | 672.00000 | 23.17527 | 24.37785 | 0.05043 | 5.31276 |
March | 744.00000 | 23.36497 | 22.85634 | 0.09051 | 5.40723 |
April | 720.00000 | 23.61612 | 19.28364 | 0.13817 | 5.59965 |
May | 744.00000 | 23.68650 | 27.44308 | -0.7091 | 16.03010 |
June | 720.00000 | 23.85878 | 36.66620 | -0.5635 | 11.91143 |
July | 744.00000 | 23.94862 | 50.76650 | -0.4220 | 8.78202 |
August | 744.00000 | 23.95100 | 49.36658 | -0.4302 | 8.92886 |
September | 720.00000 | 23.92248 | 42.11674 | -0.5009 | 10.36515 |
October | 744.00000 | 23.69806 | 28.41048 | 0.22943 | 6.48068 |
November | 720.00000 | 23.40778 | 23.21560 | 0.10512 | 5.43283 |
December | 744.00000 | 23.03761 | 21.54545 | -0.0054 | 5.25595 |
Annual Sum or Average | 8760.00000 | 23.55784 | 30.85215 | -0.1695 | 7.91906 |
Minimum of Months | 672.00000 | 23.00833 | 19.28364 | -0.7091 | 5.25595 |
Maximum of Months | 744.00000 | 23.95100 | 50.76650 | 0.22943 | 16.03010 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.63884 | 18.41725 | 0.71443 | 17.78583 |
February | 672.00000 | 23.65644 | 19.46407 | 0.73531 | 18.35883 |
March | 744.00000 | 23.70504 | 18.02879 | 0.75983 | 18.86290 |
April | 720.00000 | 23.69909 | 14.85972 | 0.76266 | 18.74222 |
May | 744.00000 | 23.68537 | 23.23747 | 0.17863 | 8.75979 |
June | 720.00000 | 23.70497 | 33.13285 | 0.29028 | 9.79526 |
July | 744.00000 | 23.71348 | 47.81318 | 0.40557 | 11.19980 |
August | 744.00000 | 23.69651 | 46.44909 | 0.38660 | 11.02046 |
September | 720.00000 | 23.65752 | 38.89198 | 0.29605 | 9.77289 |
October | 744.00000 | 23.60934 | 24.41325 | 0.80471 | 20.32922 |
November | 720.00000 | 23.65740 | 18.46793 | 0.74343 | 18.39648 |
December | 744.00000 | 23.64841 | 16.57763 | 0.70209 | 17.44397 |
Annual Sum or Average | 8760.00000 | 23.67276 | 26.70851 | 0.56402 | 15.02113 |
Minimum of Months | 672.00000 | 23.60934 | 14.85972 | 0.17863 | 8.75979 |
Maximum of Months | 744.00000 | 23.71348 | 47.81318 | 0.80471 | 20.32922 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.31481 | 26.67835 | 0.18557 | 7.32070 |
February | 672.00000 | 23.47227 | 27.50849 | 0.24182 | 7.41939 |
March | 744.00000 | 23.52946 | 26.16673 | 0.24267 | 7.02744 |
April | 720.00000 | 23.71205 | 22.64043 | 0.27673 | 7.07426 |
May | 744.00000 | 23.68360 | 31.06691 | -0.5677 | 12.59445 |
June | 720.00000 | 23.81026 | 40.22779 | -0.4166 | 9.16989 |
July | 744.00000 | 23.92830 | 53.96046 | -0.2352 | 6.39147 |
August | 744.00000 | 23.93118 | 52.37806 | -0.2216 | 6.44591 |
September | 720.00000 | 23.92600 | 45.03792 | -0.2697 | 7.35747 |
October | 744.00000 | 23.78249 | 31.20190 | 0.41095 | 9.59844 |
November | 720.00000 | 23.64783 | 26.19428 | 0.30190 | 7.93845 |
December | 744.00000 | 23.39332 | 24.66396 | 0.19867 | 7.42323 |
Annual Sum or Average | 8760.00000 | 23.67826 | 34.03523 | 0.01084 | 7.98574 |
Minimum of Months | 672.00000 | 23.31481 | 22.64043 | -0.5677 | 6.39147 |
Maximum of Months | 744.00000 | 23.93118 | 53.96046 | 0.41095 | 12.59445 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60954 | 26.07086 | 0.17800 | 5.96543 |
February | 672.00000 | 23.70613 | 26.90607 | 0.21293 | 6.11204 |
March | 744.00000 | 23.75012 | 25.35813 | 0.21940 | 6.16073 |
April | 720.00000 | 23.80758 | 21.78899 | 0.22226 | 6.15077 |
May | 744.00000 | 23.80186 | 29.89171 | -0.6220 | 13.44657 |
June | 720.00000 | 23.88704 | 39.09475 | -0.5017 | 10.46587 |
July | 744.00000 | 23.95512 | 53.11231 | -0.3630 | 7.80114 |
August | 744.00000 | 23.96494 | 51.65512 | -0.3659 | 7.84071 |
September | 720.00000 | 23.97350 | 44.31307 | -0.4206 | 8.79624 |
October | 744.00000 | 23.90278 | 30.63724 | 0.32478 | 7.44117 |
November | 720.00000 | 23.82603 | 25.57056 | 0.24653 | 6.39788 |
December | 744.00000 | 23.65620 | 24.13676 | 0.17716 | 5.87928 |
Annual Sum or Average | 8760.00000 | 23.82042 | 33.26881 | -0.0593 | 7.71519 |
Minimum of Months | 672.00000 | 23.60954 | 21.78899 | -0.6220 | 5.87928 |
Maximum of Months | 744.00000 | 23.97350 | 53.11231 | 0.32478 | 13.44657 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.31717 | 25.93041 | -0.4622 | 10.61242 |
February | 672.00000 | 21.47670 | 27.36932 | -0.3884 | 9.54529 |
March | 744.00000 | 21.79669 | 26.65640 | -0.2840 | 8.76366 |
April | 720.00000 | 22.24510 | 23.25419 | -0.1427 | 8.05646 |
May | 744.00000 | 22.17133 | 31.61097 | -1.1382 | 35.29753 |
June | 720.00000 | 22.12103 | 39.99480 | -1.0290 | 29.99693 |
July | 744.00000 | 22.17030 | 47.31905 | -0.9406 | 26.16991 |
August | 744.00000 | 22.25813 | 46.87201 | -0.9132 | 25.56012 |
September | 720.00000 | 22.36375 | 43.75504 | -0.9365 | 26.53386 |
October | 744.00000 | 22.27047 | 32.62165 | -0.0710 | 8.34532 |
November | 720.00000 | 21.52606 | 27.61443 | -0.3459 | 8.70929 |
December | 744.00000 | 21.31783 | 24.20287 | -0.4763 | 10.91339 |
Annual Sum or Average | 8760.00000 | 21.92160 | 33.14112 | -0.5955 | 17.42931 |
Minimum of Months | 672.00000 | 21.31717 | 23.25419 | -1.1382 | 8.05646 |
Maximum of Months | 744.00000 | 22.36375 | 47.31905 | -0.0710 | 35.29753 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90826 | 26.43070 | -0.6158 | 13.43504 |
February | 672.00000 | 21.09893 | 27.82716 | -0.5313 | 11.70061 |
March | 744.00000 | 21.52111 | 26.87412 | -0.3853 | 9.36503 |
April | 720.00000 | 22.09987 | 23.29274 | -0.1992 | 8.03388 |
May | 744.00000 | 22.13587 | 31.62100 | -1.1615 | 36.17399 |
June | 720.00000 | 22.14496 | 39.95613 | -1.0218 | 29.76328 |
July | 744.00000 | 22.18231 | 47.43604 | -0.9430 | 26.26292 |
August | 744.00000 | 22.23534 | 47.38761 | -0.9402 | 26.36129 |
September | 720.00000 | 22.26486 | 44.59566 | -1.0106 | 28.93397 |
October | 744.00000 | 21.95802 | 33.11733 | -0.1907 | 8.09963 |
November | 720.00000 | 21.19577 | 28.01771 | -0.4852 | 10.51710 |
December | 744.00000 | 20.83880 | 24.77329 | -0.6511 | 14.38680 |
Annual Sum or Average | 8760.00000 | 21.71809 | 33.48458 | -0.6792 | 18.63477 |
Minimum of Months | 672.00000 | 20.83880 | 23.29274 | -1.1615 | 8.03388 |
Maximum of Months | 744.00000 | 22.26486 | 47.43604 | -0.1907 | 36.17399 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91360 | 25.37069 | -0.5973 | 12.57181 |
February | 672.00000 | 20.99232 | 26.84889 | -0.5564 | 11.58430 |
March | 744.00000 | 21.19556 | 25.79644 | -0.4811 | 9.89621 |
April | 720.00000 | 21.56725 | 22.22142 | -0.3839 | 8.44854 |
May | 744.00000 | 21.76184 | 30.41999 | -1.3883 | 45.39090 |
June | 720.00000 | 21.91894 | 39.33670 | -1.2399 | 38.15540 |
July | 744.00000 | 22.02575 | 48.78778 | -1.1365 | 33.53541 |
August | 744.00000 | 22.00118 | 48.70639 | -1.1576 | 34.36387 |
September | 720.00000 | 21.91244 | 44.51424 | -1.2475 | 38.37278 |
October | 744.00000 | 21.44272 | 32.48765 | -0.3630 | 8.32440 |
November | 720.00000 | 21.04980 | 26.97196 | -0.5293 | 10.96502 |
December | 744.00000 | 20.86221 | 23.80772 | -0.6235 | 13.32121 |
Annual Sum or Average | 8760.00000 | 21.47267 | 32.98569 | -0.8103 | 22.14282 |
Minimum of Months | 672.00000 | 20.86221 | 22.22142 | -1.3883 | 8.32440 |
Maximum of Months | 744.00000 | 22.02575 | 48.78778 | -0.3630 | 45.39090 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36569 | 25.85729 | -0.4533 | 10.45898 |
February | 672.00000 | 21.50199 | 27.28077 | -0.3883 | 9.34741 |
March | 744.00000 | 21.75060 | 26.49378 | -0.2849 | 8.00087 |
April | 720.00000 | 22.12528 | 23.08315 | -0.1499 | 7.07555 |
May | 744.00000 | 22.22583 | 31.13088 | -1.0982 | 33.47748 |
June | 720.00000 | 22.36918 | 39.47877 | -0.9288 | 28.70028 |
July | 744.00000 | 22.44401 | 46.49035 | -0.8311 | 25.47425 |
August | 744.00000 | 22.51199 | 46.22933 | -0.8163 | 24.94295 |
September | 720.00000 | 22.49109 | 43.36755 | -0.8900 | 25.93587 |
October | 744.00000 | 22.13141 | 32.49082 | -0.0977 | 7.36468 |
November | 720.00000 | 21.57007 | 27.54025 | -0.3363 | 8.54082 |
December | 744.00000 | 21.36850 | 24.12773 | -0.4672 | 10.64881 |
Annual Sum or Average | 8760.00000 | 21.99031 | 32.83666 | -0.5631 | 16.71428 |
Minimum of Months | 672.00000 | 21.36569 | 23.08315 | -1.0982 | 7.07555 |
Maximum of Months | 744.00000 | 22.51199 | 46.49035 | -0.0977 | 33.47748 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90022 | 26.37340 | -0.6184 | 13.34311 |
February | 672.00000 | 21.07337 | 27.77455 | -0.5420 | 11.61356 |
March | 744.00000 | 21.55674 | 26.67321 | -0.3685 | 8.61140 |
April | 720.00000 | 22.06600 | 23.12880 | -0.1880 | 7.14782 |
May | 744.00000 | 22.21278 | 31.16382 | -1.1147 | 34.12902 |
June | 720.00000 | 22.38930 | 39.47858 | -0.9229 | 28.72070 |
July | 744.00000 | 22.45276 | 46.59249 | -0.8346 | 25.71063 |
August | 744.00000 | 22.49400 | 46.54234 | -0.8426 | 25.64974 |
September | 720.00000 | 22.41052 | 44.05121 | -0.9586 | 27.89340 |
October | 744.00000 | 21.90781 | 32.91231 | -0.1986 | 7.45592 |
November | 720.00000 | 21.18298 | 27.96026 | -0.4863 | 10.37533 |
December | 744.00000 | 20.80069 | 24.72181 | -0.6595 | 14.47343 |
Annual Sum or Average | 8760.00000 | 21.79067 | 33.15237 | -0.6455 | 17.97224 |
Minimum of Months | 672.00000 | 20.80069 | 23.12880 | -1.1147 | 7.14782 |
Maximum of Months | 744.00000 | 22.49400 | 46.59249 | -0.1880 | 34.12902 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.24531 | 26.21582 | -0.5127 | 11.86293 |
February | 672.00000 | 21.42960 | 27.64165 | -0.4269 | 10.59845 |
March | 744.00000 | 21.78952 | 26.86353 | -0.3070 | 9.76044 |
April | 720.00000 | 22.29660 | 23.44067 | -0.1382 | 8.89855 |
May | 744.00000 | 22.17069 | 31.92973 | -1.1405 | 36.19514 |
June | 720.00000 | 22.10706 | 40.33470 | -1.0239 | 30.33071 |
July | 744.00000 | 22.13513 | 47.71661 | -0.9372 | 26.25879 |
August | 744.00000 | 22.22596 | 47.28748 | -0.9107 | 25.80510 |
September | 720.00000 | 22.32548 | 44.39164 | -0.9474 | 27.30078 |
October | 744.00000 | 22.29854 | 32.97027 | -0.0787 | 9.36759 |
November | 720.00000 | 21.46966 | 27.85744 | -0.3891 | 9.64671 |
December | 744.00000 | 21.24535 | 24.42865 | -0.5272 | 12.21672 |
Annual Sum or Average | 8760.00000 | 21.89704 | 33.46431 | -0.6130 | 18.23980 |
Minimum of Months | 672.00000 | 21.24531 | 23.44067 | -1.1405 | 8.89855 |
Maximum of Months | 744.00000 | 22.32548 | 47.71661 | -0.0787 | 36.19514 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80812 | 26.75480 | -0.6768 | 15.16582 |
February | 672.00000 | 21.02600 | 28.12890 | -0.5806 | 13.04981 |
March | 744.00000 | 21.49181 | 27.11640 | -0.4174 | 10.38126 |
April | 720.00000 | 22.14575 | 23.44058 | -0.1984 | 8.76785 |
May | 744.00000 | 22.13856 | 31.95890 | -1.1636 | 37.02256 |
June | 720.00000 | 22.13072 | 40.29583 | -1.0168 | 30.07671 |
July | 744.00000 | 22.14634 | 47.82660 | -0.9399 | 26.32615 |
August | 744.00000 | 22.20182 | 47.79075 | -0.9390 | 26.60128 |
September | 720.00000 | 22.22178 | 45.30862 | -1.0254 | 29.81197 |
October | 744.00000 | 21.93799 | 33.50244 | -0.2145 | 8.93719 |
November | 720.00000 | 21.09210 | 28.31232 | -0.5456 | 11.93836 |
December | 744.00000 | 20.74201 | 25.03099 | -0.7126 | 16.20056 |
Annual Sum or Average | 8760.00000 | 21.67645 | 33.82942 | -0.7036 | 19.56965 |
Minimum of Months | 672.00000 | 20.74201 | 23.44058 | -1.1636 | 8.76785 |
Maximum of Months | 744.00000 | 22.22178 | 47.82660 | -0.1984 | 37.02256 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.54582 | 27.74828 | -0.3301 | 9.19315 |
February | 672.00000 | 21.65563 | 29.17379 | -0.2819 | 8.64443 |
March | 744.00000 | 21.81690 | 28.20649 | -0.2522 | 8.19939 |
April | 720.00000 | 22.03519 | 24.55593 | -0.2039 | 7.44572 |
May | 744.00000 | 21.99146 | 32.62101 | -1.2514 | 39.38883 |
June | 720.00000 | 21.98609 | 40.87779 | -1.1527 | 34.68791 |
July | 744.00000 | 22.09901 | 48.20552 | -1.0262 | 29.43745 |
August | 744.00000 | 22.16901 | 47.62765 | -0.9880 | 28.23961 |
September | 720.00000 | 22.32999 | 44.21412 | -0.9574 | 27.51662 |
October | 744.00000 | 22.33996 | 33.89140 | -0.0210 | 8.44928 |
November | 720.00000 | 21.65231 | 29.44116 | -0.2479 | 8.08659 |
December | 744.00000 | 21.54523 | 26.19370 | -0.3295 | 9.25266 |
Annual Sum or Average | 8760.00000 | 21.93204 | 34.43521 | -0.5888 | 18.27704 |
Minimum of Months | 672.00000 | 21.54523 | 24.55593 | -1.2514 | 7.44572 |
Maximum of Months | 744.00000 | 22.33996 | 48.20552 | -0.0210 | 39.38883 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.79042 | 26.63015 | 0.22466 | 6.21999 |
February | 672.00000 | 23.84992 | 27.34854 | 0.25997 | 6.54438 |
March | 744.00000 | 23.94627 | 25.39479 | 0.30282 | 6.97284 |
April | 720.00000 | 23.99026 | 21.72644 | 0.33001 | 7.34771 |
May | 744.00000 | 23.99016 | 29.58888 | -0.4371 | 9.20287 |
June | 720.00000 | 23.99583 | 38.89195 | -0.3162 | 7.22220 |
July | 744.00000 | 23.99659 | 53.14264 | -0.1969 | 5.85880 |
August | 744.00000 | 23.99628 | 51.85225 | -0.2193 | 6.05880 |
September | 720.00000 | 23.99467 | 44.72001 | -0.3099 | 7.11706 |
October | 744.00000 | 23.94329 | 31.18655 | 0.37666 | 8.19985 |
November | 720.00000 | 23.86278 | 26.20968 | 0.26987 | 6.65520 |
December | 744.00000 | 23.75874 | 24.85131 | 0.19956 | 6.03678 |
Annual Sum or Average | 8760.00000 | 23.92652 | 33.51848 | 0.03906 | 6.95495 |
Minimum of Months | 672.00000 | 23.75874 | 21.72644 | -0.4371 | 5.85880 |
Maximum of Months | 744.00000 | 23.99659 | 53.14264 | 0.37666 | 9.20287 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.91302 | 25.69229 | 0.29383 | 6.88494 |
February | 672.00000 | 23.94786 | 26.47160 | 0.32236 | 7.23612 |
March | 744.00000 | 23.99878 | 24.64975 | 0.35254 | 7.62825 |
April | 720.00000 | 24.00830 | 21.15263 | 0.36742 | 7.88196 |
May | 744.00000 | 23.99588 | 29.10368 | -0.3912 | 8.38585 |
June | 720.00000 | 23.99642 | 38.50409 | -0.2766 | 6.73553 |
July | 744.00000 | 23.99671 | 52.79686 | -0.1599 | 5.59143 |
August | 744.00000 | 23.99660 | 51.49457 | -0.1821 | 5.75437 |
September | 720.00000 | 23.99593 | 44.30939 | -0.2708 | 6.64699 |
October | 744.00000 | 23.97745 | 30.61006 | 0.41524 | 8.78996 |
November | 720.00000 | 23.94826 | 25.41179 | 0.32685 | 7.31167 |
December | 744.00000 | 23.89067 | 23.93051 | 0.27139 | 6.65133 |
Annual Sum or Average | 8760.00000 | 23.97219 | 32.90178 | 0.08774 | 7.12374 |
Minimum of Months | 672.00000 | 23.89067 | 21.15263 | -0.3912 | 5.59143 |
Maximum of Months | 744.00000 | 24.00830 | 52.79686 | 0.41524 | 8.78996 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.05576 | 24.81531 | 0.97426 | 27.24211 |
February | 672.00000 | 24.08627 | 25.70673 | 1.00849 | 28.63457 |
March | 744.00000 | 24.06516 | 24.13820 | 1.03403 | 29.40964 |
April | 720.00000 | 24.04422 | 20.90961 | 1.06289 | 30.64249 |
May | 744.00000 | 23.99924 | 28.79157 | 0.58968 | 16.40480 |
June | 720.00000 | 23.99182 | 38.22114 | 0.71826 | 19.86740 |
July | 744.00000 | 23.99379 | 52.27179 | 0.83952 | 23.60393 |
August | 744.00000 | 23.99356 | 50.94167 | 0.81712 | 22.93788 |
September | 720.00000 | 23.99213 | 43.75056 | 0.71505 | 19.76484 |
October | 744.00000 | 24.01200 | 30.13532 | 1.10257 | 32.40252 |
November | 720.00000 | 24.06457 | 24.79582 | 1.01556 | 28.65827 |
December | 744.00000 | 24.09700 | 23.19719 | 0.96919 | 27.13705 |
Annual Sum or Average | 8760.00000 | 24.03263 | 32.36473 | 0.90331 | 25.54256 |
Minimum of Months | 672.00000 | 23.99182 | 20.90961 | 0.58968 | 16.40480 |
Maximum of Months | 744.00000 | 24.09700 | 52.27179 | 1.10257 | 32.40252 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.14421 | 21.97646 | -0.4811 | 9.87068 |
February | 672.00000 | 21.28675 | 23.10908 | -0.4366 | 9.08241 |
March | 744.00000 | 21.75635 | 21.16808 | -0.3314 | 7.38860 |
April | 720.00000 | 22.43459 | 17.14954 | -0.1927 | 6.02730 |
May | 744.00000 | 22.96563 | 25.30038 | -1.0204 | 27.58997 |
June | 720.00000 | 23.62997 | 34.31748 | -0.7258 | 16.48338 |
July | 744.00000 | 23.90566 | 48.35504 | -0.5300 | 10.91361 |
August | 744.00000 | 23.81157 | 47.26605 | -0.5737 | 11.97832 |
September | 720.00000 | 23.43173 | 40.57894 | -0.7558 | 17.26514 |
October | 744.00000 | 22.54343 | 26.86617 | -0.1006 | 6.05548 |
November | 720.00000 | 21.63415 | 21.71372 | -0.3564 | 7.81410 |
December | 744.00000 | 21.11053 | 19.91877 | -0.5016 | 10.30252 |
Annual Sum or Average | 8760.00000 | 22.47754 | 29.03075 | -0.5009 | 11.75090 |
Minimum of Months | 672.00000 | 21.11053 | 17.14954 | -1.0204 | 6.02730 |
Maximum of Months | 744.00000 | 23.90566 | 48.35504 | -0.1006 | 27.58997 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.53515 | 25.12793 | -0.3865 | 8.25503 |
February | 672.00000 | 21.69471 | 26.18473 | -0.3391 | 7.59677 |
March | 744.00000 | 22.22823 | 24.26167 | -0.2205 | 6.18880 |
April | 720.00000 | 22.97033 | 20.28862 | -0.0650 | 5.29744 |
May | 744.00000 | 23.31954 | 28.45799 | -0.9090 | 22.93427 |
June | 720.00000 | 23.75756 | 37.56797 | -0.6895 | 15.23102 |
July | 744.00000 | 23.95738 | 51.47998 | -0.5193 | 10.67280 |
August | 744.00000 | 23.95128 | 50.09790 | -0.5300 | 10.91574 |
September | 720.00000 | 23.84959 | 43.02077 | -0.6187 | 13.15920 |
October | 744.00000 | 23.26744 | 29.39989 | 0.07240 | 5.89495 |
November | 720.00000 | 22.20101 | 24.69811 | -0.2235 | 6.20519 |
December | 744.00000 | 21.42008 | 23.18371 | -0.4252 | 8.85869 |
Annual Sum or Average | 8760.00000 | 22.85167 | 32.03484 | -0.4051 | 10.12280 |
Minimum of Months | 672.00000 | 21.42008 | 20.28862 | -0.9090 | 5.29744 |
Maximum of Months | 744.00000 | 23.95738 | 51.47998 | 0.07240 | 22.93427 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43030 | 23.05410 | -0.4017 | 8.63705 |
February | 672.00000 | 21.63968 | 24.06985 | -0.3380 | 7.79099 |
March | 744.00000 | 22.05287 | 22.17948 | -0.2407 | 6.59523 |
April | 720.00000 | 22.81904 | 18.02253 | -0.0735 | 5.64431 |
May | 744.00000 | 23.23706 | 26.14862 | -0.8854 | 22.63773 |
June | 720.00000 | 23.70657 | 35.26482 | -0.6397 | 14.11968 |
July | 744.00000 | 23.91005 | 49.29087 | -0.4590 | 9.53334 |
August | 744.00000 | 23.87265 | 48.05043 | -0.4830 | 10.07885 |
September | 720.00000 | 23.67801 | 41.11551 | -0.6149 | 13.43899 |
October | 744.00000 | 22.94735 | 27.49508 | 0.02487 | 6.20882 |
November | 720.00000 | 21.91342 | 22.72079 | -0.2717 | 6.92694 |
December | 744.00000 | 21.38455 | 20.98609 | -0.4259 | 9.02704 |
Annual Sum or Average | 8760.00000 | 22.72138 | 29.92058 | -0.4013 | 10.07207 |
Minimum of Months | 672.00000 | 21.38455 | 18.02253 | -0.8854 | 5.64431 |
Maximum of Months | 744.00000 | 23.91005 | 49.29087 | 0.02487 | 22.63773 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43429 | 21.38481 | -0.4179 | 8.74040 |
February | 672.00000 | 21.61218 | 22.43991 | -0.3675 | 7.99877 |
March | 744.00000 | 22.16494 | 20.45413 | -0.2465 | 6.39373 |
April | 720.00000 | 22.82265 | 16.57969 | -0.1125 | 5.53176 |
May | 744.00000 | 23.32796 | 24.53212 | -0.9136 | 23.26650 |
June | 720.00000 | 23.82163 | 33.66310 | -0.6684 | 14.63158 |
July | 744.00000 | 23.98453 | 47.83228 | -0.5056 | 10.37956 |
August | 744.00000 | 23.94458 | 46.58363 | -0.5333 | 10.99796 |
September | 720.00000 | 23.73346 | 39.57743 | -0.6659 | 14.50943 |
October | 744.00000 | 22.93763 | 26.06450 | -0.0187 | 5.80442 |
November | 720.00000 | 22.04787 | 20.98306 | -0.2699 | 6.70558 |
December | 744.00000 | 21.35577 | 19.42259 | -0.4471 | 9.27170 |
Annual Sum or Average | 8760.00000 | 22.77137 | 28.34770 | -0.4311 | 10.37205 |
Minimum of Months | 672.00000 | 21.35577 | 16.57969 | -0.9136 | 5.53176 |
Maximum of Months | 744.00000 | 23.98453 | 47.83228 | -0.0187 | 23.26650 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.139164E+11 | 45681.69 | 01-JAN-16:01 | 476.64 | 0.430869E+11 | 0.00 | 0.570033E+11 | 1.99 | 3.12 | 01-JAN-16:47 | 0.00 | 0.00 |
February | 0.161157E+11 | 83225.53 | 14-FEB-16:01 | 482.52 | 0.499311E+11 | 0.00 | 0.660469E+11 | 2.23 | 3.76 | 14-FEB-16:01 | 0.00 | 0.00 |
March | 0.255044E+11 | 88421.15 | 08-MAR-16:01 | 619.85 | 0.763410E+11 | 0.00 | 0.101845E+12 | 2.56 | 3.78 | 26-MAR-15:01 | 0.00 | 0.00 |
April | 0.607884E+11 | 117736.70 | 28-APR-18:01 | 693.86 | 0.183850E+12 | 0.00 | 0.244639E+12 | 2.93 | 4.12 | 13-APR-21:52 | 0.00 | 0.00 |
May | 0.982351E+11 | 133712.98 | 19-MAY-18:01 | 740.67 | 0.301116E+12 | 0.00 | 0.399351E+12 | 3.02 | 4.13 | 17-MAY-21:52 | 0.00 | 0.00 |
June | 0.165391E+12 | 187423.91 | 28-JUN-15:03 | 719.93 | 0.503503E+12 | 0.00 | 0.668893E+12 | 3.02 | 4.15 | 19-JUN-21:51 | 0.00 | 0.00 |
July | 0.218901E+12 | 184526.10 | 21-JUL-18:03 | 744.00 | 0.686644E+12 | 0.00 | 0.905545E+12 | 3.12 | 4.38 | 15-JUL-21:52 | 0.00 | 0.00 |
August | 0.197879E+12 | 159091.13 | 20-AUG-15:13 | 744.00 | 0.627960E+12 | 0.00 | 0.825839E+12 | 3.13 | 4.18 | 25-AUG-21:52 | 0.00 | 0.00 |
September | 0.136440E+12 | 141656.67 | 20-SEP-15:02 | 720.00 | 0.432395E+12 | 0.00 | 0.568835E+12 | 3.10 | 4.33 | 12-SEP-21:51 | 0.00 | 0.00 |
October | 0.724387E+11 | 130497.47 | 06-OCT-15:01 | 702.80 | 0.226651E+12 | 0.00 | 0.299090E+12 | 2.92 | 4.15 | 05-OCT-21:52 | 0.00 | 0.00 |
November | 0.212461E+11 | 55266.18 | 02-NOV-15:01 | 587.62 | 0.656774E+11 | 0.00 | 0.869235E+11 | 2.53 | 3.56 | 02-NOV-18:11 | 0.00 | 0.00 |
December | 0.144465E+11 | 41474.17 | 31-DEC-16:01 | 475.01 | 0.450132E+11 | 0.00 | 0.594597E+11 | 1.99 | 3.12 | 04-DEC-12:35 | 0.00 | 0.00 |
Annual Sum or Average | 0.104130E+13 | 7706.89 | 0.324217E+13 | 0.00 | 0.428347E+13 | 2.71 | 0.00 | 0.00 | ||||
Minimum of Months | 0.139164E+11 | 41474.17 | 475.01 | 0.430869E+11 | 0.00 | 0.570033E+11 | 1.99 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.218901E+12 | 187423.91 | 744.00 | 0.686644E+12 | 0.00 | 0.905545E+12 | 3.13 | 4.38 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.615408E+11 | 0.00 | 696.21 | 170238.75 | 21-JAN-19:02 | 0.00 | 41.33 | 58.42 | 0.30 | 0.00 | 0.05 | 0.40 | 21-JAN-19:02 |
February | 0.481765E+11 | 0.00 | 594.02 | 148044.66 | 16-FEB-23:17 | 0.00 | 41.37 | 57.42 | 0.27 | 0.00 | 0.05 | 0.35 | 16-FEB-23:17 |
March | 0.318417E+11 | 0.00 | 508.04 | 142573.35 | 03-MAR-05:22 | 0.00 | 39.57 | 52.51 | 0.16 | 0.00 | 0.03 | 0.34 | 03-MAR-05:22 |
April | 0.175588E+11 | 0.00 | 269.73 | 132096.08 | 05-APR-04:48 | 0.00 | 33.50 | 42.36 | 0.08 | 0.00 | 0.02 | 0.31 | 05-APR-04:48 |
May | 0.573301E+10 | 0.00 | 137.63 | 118762.70 | 06-MAY-04:35 | 0.00 | 32.99 | 37.80 | 0.02 | 0.00 | 0.01 | 0.28 | 06-MAY-04:35 |
June | 0.419900E+09 | 0.00 | 21.97 | 75881.46 | 09-JUN-04:27 | 0.00 | 33.05 | 33.81 | 0.00 | 0.00 | 0.00 | 0.18 | 09-JUN-04:27 |
July | 32508994.52 | 0.00 | 1.41 | 20923.71 | 12-JUL-21:54 | 0.00 | 40.00 | 40.04 | 0.00 | 0.00 | 0.00 | 0.05 | 12-JUL-21:54 |
August | 35819057.15 | 0.00 | 1.64 | 20797.23 | 16-AUG-08:54 | 0.00 | 44.53 | 44.56 | 0.00 | 0.00 | 0.00 | 0.05 | 16-AUG-08:54 |
September | 0.389822E+09 | 0.00 | 18.38 | 40092.25 | 25-SEP-21:54 | 0.00 | 38.95 | 39.52 | 0.00 | 0.00 | 0.00 | 0.09 | 25-SEP-21:54 |
October | 0.190379E+11 | 0.00 | 275.47 | 143234.00 | 27-OCT-08:61 | 0.00 | 38.26 | 45.43 | 0.09 | 0.00 | 0.02 | 0.34 | 27-OCT-08:61 |
November | 0.423160E+11 | 0.00 | 610.62 | 156502.96 | 25-NOV-09:03 | 0.00 | 41.58 | 56.57 | 0.23 | 0.00 | 0.04 | 0.37 | 25-NOV-09:03 |
December | 0.722849E+11 | 0.00 | 731.23 | 174436.88 | 04-DEC-19:02 | 0.00 | 41.90 | 59.63 | 0.36 | 0.00 | 0.06 | 0.41 | 04-DEC-19:02 |
Annual Sum or Average | 0.299368E+12 | 0.00 | 3866.37 | 0.00 | 38.92 | 47.30 | 0.13 | 0.00 | 0.02 | ||||
Minimum of Months | 32508994.52 | 0.00 | 1.41 | 20797.23 | 0.00 | 32.99 | 33.81 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.722849E+11 | 0.00 | 731.23 | 174436.88 | 0.00 | 44.53 | 59.63 | 0.36 | 0.00 | 0.06 | 0.41 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.216558E+10 | 0.00 | 178.56 | 0.216558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68963.65 | 26-JAN-22:50 | 68963.65 | 26-JAN-22:50 | 0.00 | 0.00 | 0.00 |
February | 0.739146E+10 | 0.00 | 180.67 | 0.739146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126948.93 | 14-FEB-16:03 | 126948.93 | 14-FEB-16:03 | 0.00 | 0.00 | 0.00 |
March | 0.241175E+11 | 0.00 | 246.75 | 0.241175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133161.12 | 08-MAR-16:03 | 133161.12 | 08-MAR-16:03 | 0.00 | 0.00 | 0.00 |
April | 0.974810E+11 | 0.00 | 386.44 | 0.974810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200105.71 | 28-APR-18:40 | 200105.71 | 28-APR-18:40 | 0.00 | 0.00 | 0.00 |
May | 0.182373E+12 | 0.00 | 537.01 | 0.182373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228636.76 | 19-MAY-18:20 | 228636.76 | 19-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.321926E+12 | 0.00 | 650.66 | 0.321706E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271948.43 | 27-JUN-20:10 | 271948.43 | 27-JUN-20:10 | 0.00 | 0.00 | 0.00 |
July | 0.444156E+12 | 0.00 | 744.00 | 0.421356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 348424.04 | 31-JUL-20:00 | 289177.59 | 21-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.397825E+12 | 0.00 | 742.17 | 0.385938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 292457.81 | 14-AUG-21:00 | 267885.99 | 18-AUG-18:30 | 0.00 | 0.00 | 0.00 |
September | 0.257631E+12 | 0.00 | 658.51 | 0.256742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235358.00 | 13-SEP-19:20 | 235358.00 | 13-SEP-19:20 | 0.00 | 0.00 | 0.00 |
October | 0.110679E+12 | 0.00 | 419.85 | 0.110621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 206354.02 | 05-OCT-18:10 | 206354.02 | 05-OCT-18:10 | 0.00 | 0.00 | 0.00 |
November | 0.426069E+10 | 0.00 | 189.45 | 0.426069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84376.19 | 27-NOV-22:50 | 84376.19 | 27-NOV-22:50 | 0.00 | 0.00 | 0.00 |
December | 0.133015E+10 | 0.00 | 173.21 | 0.133015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69263.66 | 19-DEC-22:58 | 69263.66 | 19-DEC-22:58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185134E+13 | 0.00 | 5107.28 | 0.181548E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.133015E+10 | 0.00 | 173.21 | 0.133015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68963.65 | 68963.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.444156E+12 | 0.00 | 744.00 | 0.421356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 348424.04 | 289177.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119142E+09 | 0.00 | 16.87 | 0.119142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4033.62 | 05-JAN-14:00 | 4033.62 | 05-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.100795E+10 | 0.00 | 33.54 | 0.100795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21463.19 | 14-FEB-16:00 | 21463.19 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.393961E+10 | 0.00 | 136.67 | 0.393961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22393.53 | 08-MAR-16:00 | 22393.53 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.151750E+11 | 0.00 | 322.17 | 0.151750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24754.08 | 29-APR-15:01 | 24754.08 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.282246E+11 | 0.00 | 507.00 | 0.282234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27342.90 | 19-MAY-15:00 | 27342.90 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.460860E+11 | 0.00 | 649.83 | 0.460141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31625.90 | 28-JUN-15:01 | 31625.90 | 28-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.682682E+11 | 0.00 | 744.00 | 0.601133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44602.88 | 01-JUL-01:00 | 31721.12 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.596034E+11 | 0.00 | 742.50 | 0.548217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42304.56 | 26-AUG-10:00 | 30014.45 | 20-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.382980E+11 | 0.00 | 657.92 | 0.373756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39969.02 | 05-SEP-12:30 | 28940.45 | 03-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.161610E+11 | 0.00 | 350.00 | 0.160445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28113.12 | 11-OCT-10:07 | 26356.52 | 01-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.449883E+09 | 0.00 | 40.85 | 0.449883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14180.63 | 09-NOV-14:00 | 14180.63 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 14984.70 | 0.00 | 0.27 | 14984.70 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 | 29-DEC-16:07 | 39.75 | 29-DEC-16:07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277333E+12 | 0.00 | 4201.62 | 0.263284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14984.70 | 0.00 | 0.27 | 14984.70 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 | 39.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.682682E+11 | 0.00 | 744.00 | 0.601133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44602.88 | 31721.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.117519E+10 | 0.00 | 178.59 | 0.117519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22313.12 | 05-JAN-17:01 | 22313.12 | 05-JAN-17:01 | 0.00 | 0.00 | 0.00 |
February | 0.162216E+10 | 0.00 | 218.74 | 0.162143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23689.10 | 15-FEB-18:01 | 23689.10 | 15-FEB-18:01 | 0.00 | 0.00 | 0.00 |
March | 0.223651E+10 | 0.00 | 336.04 | 0.223305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23973.80 | 23-MAR-17:41 | 23973.80 | 23-MAR-17:41 | 0.00 | 0.00 | 0.00 |
April | 0.426525E+10 | 0.00 | 469.16 | 0.422059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24399.80 | 25-APR-16:21 | 24399.80 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.579945E+10 | 0.00 | 521.41 | 0.499956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23429.77 | 06-MAY-19:41 | 23429.77 | 06-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.895086E+10 | 0.00 | 564.58 | 0.678588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23232.28 | 13-JUN-21:51 | 23232.28 | 13-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.110324E+11 | 0.00 | 589.79 | 0.696358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25140.44 | 31-JUL-21:51 | 21152.82 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.108419E+11 | 0.00 | 574.53 | 0.678714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24309.87 | 25-AUG-21:51 | 21115.06 | 23-AUG-17:21 | 0.00 | 0.00 | 0.00 |
September | 0.829604E+10 | 0.00 | 519.99 | 0.543210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23493.84 | 05-SEP-21:51 | 23191.14 | 26-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.516394E+10 | 0.00 | 471.95 | 0.410632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24029.34 | 13-OCT-17:41 | 24029.34 | 13-OCT-17:41 | 0.00 | 0.00 | 0.00 |
November | 0.227287E+10 | 0.00 | 336.57 | 0.218594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21150.60 | 02-NOV-15:01 | 21150.60 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.972562E+09 | 0.00 | 180.26 | 0.972562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21112.19 | 26-DEC-16:01 | 21112.19 | 26-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626292E+11 | 0.00 | 4961.61 | 0.474833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.972562E+09 | 0.00 | 178.59 | 0.972562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21112.19 | 21112.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.110324E+11 | 0.00 | 589.79 | 0.696358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25140.44 | 24399.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.208285E+09 | 0.00 | 35.99 | 0.208285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20885.09 | 05-JAN-16:01 | 20885.09 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.487749E+09 | 0.00 | 79.59 | 0.487697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20893.61 | 17-FEB-16:01 | 20893.61 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.100070E+10 | 0.00 | 193.71 | 0.998807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23611.03 | 30-MAR-18:11 | 23611.03 | 30-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.323487E+10 | 0.00 | 408.29 | 0.319413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24145.13 | 25-APR-16:21 | 24145.13 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.536641E+10 | 0.00 | 501.20 | 0.460226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22900.08 | 06-MAY-19:41 | 22900.08 | 06-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.891926E+10 | 0.00 | 562.24 | 0.679777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23026.48 | 13-JUN-21:51 | 23026.48 | 13-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.106946E+11 | 0.00 | 588.05 | 0.671678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24801.31 | 31-JUL-21:51 | 20935.06 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.981757E+10 | 0.00 | 569.28 | 0.590290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23862.62 | 25-AUG-21:51 | 21144.48 | 23-AUG-17:21 | 0.00 | 0.00 | 0.00 |
September | 0.642653E+10 | 0.00 | 500.86 | 0.383931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23005.03 | 05-SEP-21:51 | 22322.41 | 21-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.290746E+10 | 0.00 | 366.03 | 0.206653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22191.71 | 02-OCT-21:51 | 22117.31 | 05-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.534035E+09 | 0.00 | 126.45 | 0.509761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20929.10 | 02-NOV-15:01 | 20929.10 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.120795E+09 | 0.00 | 23.93 | 0.120795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20867.84 | 02-DEC-16:01 | 20867.84 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497183E+11 | 0.00 | 3955.62 | 0.354450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120795E+09 | 0.00 | 23.93 | 0.120795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20867.84 | 20867.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.106946E+11 | 0.00 | 588.05 | 0.679777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24801.31 | 24145.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.259962E+11 | 0.00 | 315.16 | 0.259962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59942.43 | 03-JAN-12:40 | 59942.43 | 03-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.243098E+11 | 0.00 | 328.66 | 0.243098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59957.71 | 14-FEB-13:00 | 59957.71 | 14-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.208572E+11 | 0.00 | 359.11 | 0.208572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49185.49 | 08-MAR-13:30 | 49185.49 | 08-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.201830E+11 | 0.00 | 459.38 | 0.201830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35099.92 | 13-APR-13:20 | 35099.92 | 13-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.172298E+11 | 0.00 | 474.30 | 0.154490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23303.17 | 13-MAY-13:10 | 23303.17 | 13-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.257747E+11 | 0.00 | 588.78 | 0.193242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27413.28 | 29-JUN-13:30 | 26484.70 | 29-JUN-16:10 | 0.00 | 0.00 | 0.00 |
July | 0.400646E+11 | 0.00 | 716.75 | 0.181112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31221.04 | 23-JUL-13:30 | 27129.86 | 21-JUL-17:13 | 0.00 | 0.00 | 0.00 |
August | 0.457672E+11 | 0.00 | 713.94 | 0.235081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42540.60 | 22-AUG-13:00 | 36853.99 | 22-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.472268E+11 | 0.00 | 669.46 | 0.339209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55541.07 | 28-SEP-13:30 | 52850.47 | 27-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.464267E+11 | 0.00 | 575.76 | 0.428497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59444.67 | 19-OCT-12:30 | 59444.67 | 19-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.366912E+11 | 0.00 | 429.42 | 0.366912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60517.45 | 20-NOV-12:10 | 60517.45 | 20-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.289439E+11 | 0.00 | 348.37 | 0.289439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60665.43 | 31-DEC-13:35 | 60665.43 | 31-DEC-13:35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379471E+12 | 0.00 | 5979.08 | 0.310144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.172298E+11 | 0.00 | 315.16 | 0.154490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23303.17 | 23303.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.472268E+11 | 0.00 | 716.75 | 0.428497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60665.43 | 60665.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.393412E+09 | 0.00 | 46.88 | 0.393412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21223.24 | 06-JAN-19:03 | 21223.24 | 06-JAN-19:03 | 0.00 | 0.00 | 0.00 |
February | 0.165617E+10 | 0.00 | 113.40 | 0.165309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103404.11 | 14-FEB-19:01 | 103404.11 | 14-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.755003E+10 | 0.00 | 305.94 | 0.736041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111031.76 | 27-MAR-19:11 | 111031.76 | 27-MAR-19:11 | 0.00 | 0.00 | 0.00 |
April | 0.192882E+11 | 0.00 | 383.71 | 0.190435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116649.21 | 27-APR-21:51 | 116649.21 | 27-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.327974E+11 | 0.00 | 415.88 | 0.281316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117424.67 | 16-MAY-21:51 | 117424.67 | 16-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.514697E+11 | 0.00 | 483.47 | 0.404254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119035.54 | 18-JUN-08:51 | 119035.54 | 18-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.625003E+11 | 0.00 | 522.23 | 0.406348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131289.20 | 31-JUL-21:51 | 114771.27 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.551029E+11 | 0.00 | 472.70 | 0.345773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129298.00 | 25-AUG-21:51 | 103941.51 | 22-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.355578E+11 | 0.00 | 368.73 | 0.229204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125625.89 | 05-SEP-21:51 | 117883.11 | 30-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.165191E+11 | 0.00 | 344.68 | 0.123214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118640.34 | 02-OCT-21:51 | 115391.91 | 11-OCT-21:21 | 0.00 | 0.00 | 0.00 |
November | 0.340518E+10 | 0.00 | 200.46 | 0.307600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105673.97 | 02-NOV-18:11 | 105673.97 | 02-NOV-18:11 | 0.00 | 0.00 | 0.00 |
December | 0.282791E+09 | 0.00 | 32.09 | 0.282791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57847.65 | 03-DEC-09:01 | 57847.65 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286523E+12 | 0.00 | 3690.17 | 0.210820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.282791E+09 | 0.00 | 32.09 | 0.282791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21223.24 | 21223.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.625003E+11 | 0.00 | 522.23 | 0.406348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131289.20 | 119035.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.114727E+10 | 0.00 | 190.84 | 0.114727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18680.31 | 03-JAN-09:01 | 18680.31 | 03-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.145533E+10 | 0.00 | 216.94 | 0.144696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18908.39 | 14-FEB-19:01 | 18908.39 | 14-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.273085E+10 | 0.00 | 366.40 | 0.271555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19187.85 | 13-MAR-20:41 | 19187.85 | 13-MAR-20:41 | 0.00 | 0.00 | 0.00 |
April | 0.533740E+10 | 0.00 | 518.08 | 0.529117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21590.61 | 27-APR-08:51 | 21590.61 | 27-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.663950E+10 | 0.00 | 569.69 | 0.568335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21601.96 | 13-MAY-08:51 | 21601.96 | 13-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.959634E+10 | 0.00 | 594.21 | 0.742303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22353.41 | 14-JUN-08:62 | 22353.41 | 14-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.118986E+11 | 0.00 | 606.34 | 0.778403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23009.81 | 09-JUL-08:32 | 20819.68 | 06-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.114266E+11 | 0.00 | 589.07 | 0.744597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23405.98 | 13-AUG-08:32 | 21030.49 | 16-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.848682E+10 | 0.00 | 536.49 | 0.568224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21009.54 | 06-SEP-08:51 | 20774.28 | 02-SEP-08:32 | 0.00 | 0.00 | 0.00 |
October | 0.549853E+10 | 0.00 | 498.76 | 0.444914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20276.20 | 02-OCT-21:51 | 20026.56 | 05-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.230072E+10 | 0.00 | 351.20 | 0.221708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18700.52 | 05-NOV-08:61 | 18700.52 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 |
December | 0.954661E+09 | 0.00 | 148.76 | 0.954661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18680.09 | 29-DEC-09:01 | 18680.09 | 29-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.674727E+11 | 0.00 | 5186.76 | 0.522404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.954661E+09 | 0.00 | 148.76 | 0.954661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18680.09 | 18680.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.118986E+11 | 0.00 | 606.34 | 0.778403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23405.98 | 22353.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.204359E+09 | 0.00 | 39.37 | 0.204359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17755.57 | 01-JAN-09:01 | 17755.57 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.376451E+09 | 0.00 | 70.70 | 0.373098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18525.76 | 19-FEB-09:01 | 18525.76 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.132598E+10 | 0.00 | 223.21 | 0.131466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18529.90 | 08-MAR-09:01 | 18529.90 | 08-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.419186E+10 | 0.00 | 478.53 | 0.414734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21400.87 | 27-APR-08:51 | 21400.87 | 27-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.616557E+10 | 0.00 | 558.37 | 0.523193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21412.59 | 14-MAY-08:51 | 21412.59 | 14-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.955267E+10 | 0.00 | 593.88 | 0.740251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22838.54 | 14-JUN-08:62 | 22838.54 | 14-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.115589E+11 | 0.00 | 606.26 | 0.745071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22784.17 | 09-JUL-08:32 | 20627.12 | 13-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.104106E+11 | 0.00 | 587.95 | 0.644464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23248.68 | 13-AUG-08:32 | 20864.32 | 16-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.657121E+10 | 0.00 | 529.08 | 0.398807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20663.63 | 02-SEP-08:32 | 20663.63 | 02-SEP-08:32 | 0.00 | 0.00 | 0.00 |
October | 0.310669E+10 | 0.00 | 399.78 | 0.223656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19718.77 | 02-OCT-21:51 | 19161.87 | 05-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.594949E+09 | 0.00 | 120.34 | 0.560628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18516.70 | 12-NOV-09:01 | 18516.70 | 12-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.126013E+09 | 0.00 | 36.13 | 0.126013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17904.00 | 30-DEC-09:01 | 17904.00 | 30-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541853E+11 | 0.00 | 4243.59 | 0.394805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.126013E+09 | 0.00 | 36.13 | 0.126013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17755.57 | 17755.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115589E+11 | 0.00 | 606.26 | 0.745071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23248.68 | 22838.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.286247E+09 | 0.00 | 136.17 | 0.286247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6045.00 | 05-JAN-17:01 | 6045.00 | 05-JAN-17:01 | 0.00 | 0.00 | 0.00 |
February | 0.405061E+09 | 0.00 | 179.59 | 0.405029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6432.46 | 15-FEB-18:01 | 6432.46 | 15-FEB-18:01 | 0.00 | 0.00 | 0.00 |
March | 0.537070E+09 | 0.00 | 264.00 | 0.537022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6456.24 | 30-MAR-18:11 | 6456.24 | 30-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.106231E+10 | 0.00 | 435.26 | 0.105226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6462.49 | 25-APR-16:21 | 6462.49 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.146589E+10 | 0.00 | 498.53 | 0.127912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6360.73 | 06-MAY-19:41 | 6360.73 | 06-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.233421E+10 | 0.00 | 562.02 | 0.179366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6145.18 | 13-JUN-21:51 | 6145.18 | 13-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.290012E+10 | 0.00 | 592.24 | 0.185683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6754.48 | 31-JUL-21:51 | 5602.85 | 21-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.283188E+10 | 0.00 | 576.19 | 0.180066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6482.88 | 25-AUG-21:51 | 5533.17 | 23-AUG-17:02 | 0.00 | 0.00 | 0.00 |
September | 0.207472E+10 | 0.00 | 518.84 | 0.138044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6259.08 | 05-SEP-21:51 | 6133.11 | 26-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.122221E+10 | 0.00 | 426.41 | 0.969639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6443.10 | 17-OCT-19:21 | 6443.10 | 17-OCT-19:21 | 0.00 | 0.00 | 0.00 |
November | 0.504682E+09 | 0.00 | 265.54 | 0.490186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5601.85 | 02-NOV-15:01 | 5601.85 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.234724E+09 | 0.00 | 129.67 | 0.234724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5591.63 | 26-DEC-16:01 | 5591.63 | 26-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158591E+11 | 0.00 | 4584.45 | 0.120858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.234724E+09 | 0.00 | 129.67 | 0.234724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5591.63 | 5533.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.290012E+10 | 0.00 | 592.24 | 0.185683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6754.48 | 6462.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 49253723.38 | 0.00 | 30.96 | 49253723.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5522.16 | 05-JAN-16:01 | 5522.16 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.117427E+09 | 0.00 | 64.34 | 0.117427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5524.32 | 17-FEB-16:01 | 5524.32 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.234006E+09 | 0.00 | 137.16 | 0.233958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6306.54 | 23-MAR-17:41 | 6306.54 | 23-MAR-17:41 | 0.00 | 0.00 | 0.00 |
April | 0.786903E+09 | 0.00 | 370.79 | 0.778111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6384.11 | 25-APR-16:21 | 6384.11 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.134957E+10 | 0.00 | 483.29 | 0.117198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6271.86 | 06-MAY-19:41 | 6271.86 | 06-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.232658E+10 | 0.00 | 561.17 | 0.179554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6083.44 | 13-JUN-21:51 | 6083.44 | 13-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.281275E+10 | 0.00 | 590.71 | 0.179034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.52 | 31-JUL-21:51 | 5535.35 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.256288E+10 | 0.00 | 570.61 | 0.156313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6356.12 | 25-AUG-21:51 | 5501.17 | 23-AUG-17:21 | 0.00 | 0.00 | 0.00 |
September | 0.157387E+10 | 0.00 | 502.71 | 0.952410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6121.24 | 05-SEP-21:51 | 5866.31 | 21-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.638602E+09 | 0.00 | 308.03 | 0.452350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6192.35 | 13-OCT-17:41 | 6192.35 | 13-OCT-17:41 | 0.00 | 0.00 | 0.00 |
November | 0.109665E+09 | 0.00 | 73.04 | 0.108015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5533.78 | 02-NOV-15:01 | 5533.78 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 25710156.24 | 0.00 | 20.47 | 25710156.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5517.59 | 02-DEC-16:01 | 5517.59 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125872E+11 | 0.00 | 3713.29 | 0.903822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 25710156.24 | 0.00 | 20.47 | 25710156.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5517.59 | 5501.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.281275E+10 | 0.00 | 590.71 | 0.179554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.52 | 6384.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.654664E+10 | 0.00 | 347.09 | 0.654664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25602.11 | 05-JAN-17:01 | 25602.11 | 05-JAN-17:01 | 0.00 | 0.00 | 0.00 |
February | 0.622860E+10 | 0.00 | 364.21 | 0.621579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26378.66 | 14-FEB-19:01 | 26378.66 | 14-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.554949E+10 | 0.00 | 418.72 | 0.552881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26105.42 | 12-MAR-19:31 | 26105.42 | 12-MAR-19:31 | 0.00 | 0.00 | 0.00 |
April | 0.583525E+10 | 0.00 | 470.24 | 0.577441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25852.95 | 12-APR-16:21 | 25852.95 | 12-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.619210E+10 | 0.00 | 506.41 | 0.516683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24039.41 | 11-MAY-21:51 | 24039.41 | 11-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.913294E+10 | 0.00 | 558.60 | 0.657180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24146.35 | 18-JUN-08:51 | 24146.35 | 18-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.130089E+11 | 0.00 | 587.12 | 0.802690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27010.40 | 31-JUL-21:51 | 23013.49 | 21-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.139324E+11 | 0.00 | 574.06 | 0.911012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26576.85 | 25-AUG-21:51 | 22878.39 | 29-AUG-16:31 | 0.00 | 0.00 | 0.00 |
September | 0.127596E+11 | 0.00 | 522.59 | 0.911253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25866.03 | 05-SEP-21:51 | 25441.38 | 26-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.111738E+11 | 0.00 | 523.66 | 0.969651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26604.89 | 18-OCT-21:51 | 26604.89 | 18-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.864285E+10 | 0.00 | 478.44 | 0.843311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23008.19 | 01-NOV-15:01 | 23008.19 | 01-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.726257E+10 | 0.00 | 363.94 | 0.726257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22987.11 | 29-DEC-09:01 | 22987.11 | 29-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106265E+12 | 0.00 | 5715.08 | 0.874460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.554949E+10 | 0.00 | 347.09 | 0.516683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22987.11 | 22878.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.139324E+11 | 0.00 | 587.12 | 0.969651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27010.40 | 26604.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1365.45 | 1061.86 | 303.59 | 1520.05 | 625.54 | 0.00 | 0.00 | 0.00 |
February | 1345.94 | 985.04 | 360.90 | 1527.15 | 576.89 | 0.00 | 0.00 | 0.00 |
March | 1000.83 | 610.71 | 390.12 | 1163.75 | 457.12 | 0.00 | 0.00 | 0.00 |
April | 768.64 | 315.00 | 453.64 | 928.81 | 316.98 | 0.00 | 0.00 | 0.00 |
May | 517.30 | 117.03 | 400.27 | 639.58 | 223.25 | 0.00 | 0.00 | 0.00 |
June | 432.45 | 51.93 | 380.52 | 627.49 | 143.82 | 0.00 | 0.00 | 0.00 |
July | 478.69 | 75.11 | 403.58 | 752.76 | 89.15 | 0.00 | 0.00 | 0.00 |
August | 651.18 | 205.38 | 445.80 | 972.75 | 108.91 | 0.00 | 0.00 | 0.00 |
September | 924.44 | 520.38 | 404.06 | 1278.36 | 198.66 | 0.00 | 0.00 | 0.00 |
October | 1245.45 | 916.13 | 329.32 | 1547.75 | 346.70 | 0.00 | 0.00 | 0.00 |
November | 1404.90 | 1081.24 | 323.66 | 1610.72 | 498.30 | 0.00 | 0.00 | 0.00 |
December | 1489.03 | 1229.18 | 259.85 | 1665.23 | 641.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 966.54 | 595.38 | 371.15 | 1184.22 | 351.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.45 | 51.93 | 259.85 | 627.49 | 89.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1489.03 | 1229.18 | 453.64 | 1665.23 | 641.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3845.01 | 2990.13 | 854.88 | 4234.25 | 1875.23 | 0.00 | 0.00 | 0.00 |
February | 3790.08 | 2773.82 | 1016.26 | 4254.31 | 1734.82 | 0.00 | 0.00 | 0.00 |
March | 2818.28 | 1719.73 | 1098.54 | 3228.61 | 1393.23 | 0.00 | 0.00 | 0.00 |
April | 2164.44 | 887.02 | 1277.42 | 2572.28 | 966.54 | 0.00 | 0.00 | 0.00 |
May | 1456.68 | 329.54 | 1127.14 | 1759.13 | 687.14 | 0.00 | 0.00 | 0.00 |
June | 1217.75 | 146.22 | 1071.52 | 1739.70 | 432.95 | 0.00 | 0.00 | 0.00 |
July | 1347.97 | 211.51 | 1136.46 | 2100.28 | 261.14 | 0.00 | 0.00 | 0.00 |
August | 1833.69 | 578.34 | 1255.35 | 2718.99 | 317.72 | 0.00 | 0.00 | 0.00 |
September | 2603.16 | 1465.35 | 1137.81 | 3573.81 | 584.53 | 0.00 | 0.00 | 0.00 |
October | 3507.10 | 2579.76 | 927.34 | 4324.34 | 1033.06 | 0.00 | 0.00 | 0.00 |
November | 3956.12 | 3044.70 | 911.42 | 4491.41 | 1505.85 | 0.00 | 0.00 | 0.00 |
December | 4193.02 | 3461.29 | 731.73 | 4647.40 | 1926.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2721.70 | 1676.56 | 1045.14 | 3298.19 | 1056.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1217.75 | 146.22 | 731.73 | 1739.70 | 261.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4193.02 | 3461.29 | 1277.42 | 4647.40 | 1926.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4994.88 | 3884.35 | 1110.53 | 5592.12 | 2499.67 | 0.00 | 0.00 | 0.00 |
February | 4923.53 | 3603.35 | 1320.18 | 5627.55 | 2307.41 | 0.00 | 0.00 | 0.00 |
March | 3661.10 | 2234.03 | 1427.07 | 4274.30 | 1853.69 | 0.00 | 0.00 | 0.00 |
April | 2811.73 | 1152.28 | 1659.44 | 3423.01 | 1279.26 | 0.00 | 0.00 | 0.00 |
May | 1892.31 | 428.09 | 1464.22 | 2344.15 | 912.68 | 0.00 | 0.00 | 0.00 |
June | 1581.92 | 189.95 | 1391.97 | 2324.59 | 571.95 | 0.00 | 0.00 | 0.00 |
July | 1751.09 | 274.76 | 1476.33 | 2808.89 | 337.03 | 0.00 | 0.00 | 0.00 |
August | 2382.07 | 751.30 | 1630.78 | 3623.48 | 406.86 | 0.00 | 0.00 | 0.00 |
September | 3381.65 | 1903.57 | 1478.08 | 4741.48 | 754.57 | 0.00 | 0.00 | 0.00 |
October | 4555.93 | 3351.26 | 1204.67 | 5722.27 | 1354.62 | 0.00 | 0.00 | 0.00 |
November | 5139.22 | 3955.24 | 1183.98 | 5937.42 | 1990.17 | 0.00 | 0.00 | 0.00 |
December | 5446.97 | 4496.41 | 950.56 | 6139.89 | 2564.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3535.64 | 2177.95 | 1357.69 | 4372.67 | 1398.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1581.92 | 189.95 | 950.56 | 2324.59 | 337.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5446.97 | 4496.41 | 1659.44 | 6139.89 | 2564.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 305.68 | 122.18 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 306.41 | 112.57 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 231.95 | 89.93 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 184.98 | 62.09 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 128.26 | 42.09 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 129.46 | 23.74 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 156.22 | 11.45 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 198.48 | 15.37 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 257.67 | 34.15 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 310.60 | 65.41 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 324.09 | 94.79 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 335.47 | 124.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 238.72 | 66.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 128.26 | 11.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 335.47 | 124.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 177.36 | 250.46 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 245.16 | 225.48 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 293.01 | 172.96 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 408.92 | 112.45 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 419.08 | 76.75 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 507.55 | 44.06 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 483.27 | 21.35 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 473.33 | 28.59 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 401.81 | 64.18 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 321.91 | 130.87 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 210.53 | 191.98 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 165.47 | 257.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 342.64 | 130.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 165.47 | 21.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 507.55 | 257.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 8.64 | 135.52 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 17.06 | 121.83 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 36.38 | 93.30 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 60.09 | 58.99 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 84.47 | 39.09 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 131.75 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 132.45 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 111.41 | 14.43 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 75.18 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 34.57 | 69.42 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 12.78 | 103.63 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 2.96 | 139.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 59.20 | 69.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 2.96 | 11.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 132.45 | 139.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 185.70 | 244.72 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 253.75 | 220.31 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 299.62 | 169.65 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 412.93 | 110.84 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 420.38 | 76.29 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 507.35 | 43.98 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 483.63 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 475.21 | 28.02 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 405.75 | 62.20 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 328.97 | 126.43 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 218.45 | 186.74 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 173.68 | 249.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 347.46 | 127.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 173.68 | 21.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 507.35 | 249.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.94 | 167.92 | 48.01 | 240.19 | 106.70 | 0.00 | 0.00 | 0.00 |
February | 212.85 | 155.78 | 57.07 | 241.24 | 99.14 | 0.00 | 0.00 | 0.00 |
March | 158.27 | 96.58 | 61.69 | 183.04 | 78.84 | 0.00 | 0.00 | 0.00 |
April | 121.56 | 49.81 | 71.74 | 147.13 | 53.18 | 0.00 | 0.00 | 0.00 |
May | 81.81 | 18.51 | 63.30 | 102.05 | 36.78 | 0.00 | 0.00 | 0.00 |
June | 68.39 | 8.21 | 60.18 | 103.76 | 22.10 | 0.00 | 0.00 | 0.00 |
July | 75.70 | 11.88 | 63.82 | 125.04 | 12.01 | 0.00 | 0.00 | 0.00 |
August | 102.98 | 32.48 | 70.50 | 158.99 | 15.06 | 0.00 | 0.00 | 0.00 |
September | 146.19 | 82.29 | 63.90 | 205.58 | 30.35 | 0.00 | 0.00 | 0.00 |
October | 196.96 | 144.88 | 52.08 | 246.95 | 56.99 | 0.00 | 0.00 | 0.00 |
November | 222.18 | 170.99 | 51.19 | 255.26 | 85.14 | 0.00 | 0.00 | 0.00 |
December | 235.48 | 194.39 | 41.09 | 263.81 | 109.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.85 | 94.16 | 58.70 | 189.12 | 58.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.39 | 8.21 | 41.09 | 102.05 | 12.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.48 | 194.39 | 71.74 | 263.81 | 109.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.27 | 0.00 | 29.27 | 6.80 | 110.33 | 0.00 | 0.00 | 0.00 |
February | 36.58 | 0.00 | 36.58 | 14.43 | 98.06 | 0.00 | 0.00 | 0.00 |
March | 46.15 | 0.00 | 46.15 | 31.47 | 73.48 | 0.00 | 0.00 | 0.00 |
April | 58.87 | 0.79 | 58.08 | 52.83 | 44.46 | 0.00 | 0.00 | 0.00 |
May | 63.72 | 4.14 | 59.58 | 72.57 | 29.24 | 0.00 | 0.00 | 0.00 |
June | 72.54 | 12.06 | 60.48 | 111.17 | 15.91 | 0.00 | 0.00 | 0.00 |
July | 66.52 | 5.67 | 60.85 | 111.71 | 7.26 | 0.00 | 0.00 | 0.00 |
August | 61.73 | 1.51 | 60.22 | 94.97 | 9.63 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 0.04 | 49.25 | 64.84 | 23.83 | 0.00 | 0.00 | 0.00 |
October | 36.74 | 0.00 | 36.74 | 30.86 | 52.40 | 0.00 | 0.00 | 0.00 |
November | 31.20 | 0.00 | 31.20 | 10.88 | 82.96 | 0.00 | 0.00 | 0.00 |
December | 24.91 | 0.00 | 24.91 | 2.18 | 114.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.17 | 2.02 | 46.15 | 50.58 | 54.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.91 | 0.00 | 24.91 | 2.18 | 7.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.54 | 12.06 | 60.85 | 111.71 | 114.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.37 | 105.99 | 83.38 | 154.29 | 236.54 | 0.00 | 0.00 | 0.00 |
February | 229.33 | 123.28 | 106.05 | 206.83 | 213.65 | 0.00 | 0.00 | 0.00 |
March | 304.76 | 173.62 | 131.14 | 316.68 | 161.54 | 0.00 | 0.00 | 0.00 |
April | 413.42 | 235.26 | 178.16 | 481.33 | 104.88 | 0.00 | 0.00 | 0.00 |
May | 394.96 | 224.96 | 169.99 | 489.20 | 73.07 | 0.00 | 0.00 | 0.00 |
June | 425.94 | 262.36 | 163.58 | 584.93 | 40.50 | 0.00 | 0.00 | 0.00 |
July | 393.93 | 225.19 | 168.74 | 568.30 | 20.74 | 0.00 | 0.00 | 0.00 |
August | 389.89 | 214.90 | 174.99 | 540.58 | 26.99 | 0.00 | 0.00 | 0.00 |
September | 325.12 | 181.92 | 143.20 | 423.83 | 60.39 | 0.00 | 0.00 | 0.00 |
October | 283.26 | 179.87 | 103.38 | 321.19 | 120.61 | 0.00 | 0.00 | 0.00 |
November | 220.30 | 129.24 | 91.06 | 205.98 | 184.15 | 0.00 | 0.00 | 0.00 |
December | 179.45 | 109.46 | 69.99 | 148.67 | 249.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.79 | 180.74 | 132.05 | 370.90 | 123.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.45 | 105.99 | 69.99 | 148.67 | 20.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 425.94 | 262.36 | 178.16 | 584.93 | 249.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 304.87 | 121.65 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 305.67 | 111.62 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 230.63 | 88.87 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 183.33 | 60.69 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 125.80 | 41.38 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 125.96 | 23.28 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 152.91 | 11.54 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 195.47 | 15.26 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 255.78 | 33.62 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 309.96 | 63.88 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 323.12 | 94.19 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 334.68 | 123.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 236.96 | 65.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 125.80 | 11.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 334.68 | 123.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 8.01 | 134.82 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 16.56 | 120.81 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 35.07 | 92.92 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 58.07 | 58.01 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 82.00 | 38.52 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 128.20 | 21.65 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 129.08 | 11.11 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 108.21 | 14.25 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 73.24 | 32.95 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 33.50 | 68.10 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 12.03 | 102.94 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 2.55 | 139.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 57.43 | 69.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 2.55 | 11.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 129.08 | 139.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.37 | 105.99 | 83.38 | 161.81 | 229.18 | 0.00 | 0.00 | 0.00 |
February | 229.33 | 123.28 | 106.05 | 215.01 | 207.29 | 0.00 | 0.00 | 0.00 |
March | 304.76 | 173.62 | 131.14 | 322.17 | 158.28 | 0.00 | 0.00 | 0.00 |
April | 413.42 | 235.26 | 178.16 | 484.24 | 103.41 | 0.00 | 0.00 | 0.00 |
May | 394.96 | 224.96 | 169.99 | 490.26 | 72.64 | 0.00 | 0.00 | 0.00 |
June | 425.94 | 262.36 | 163.58 | 584.83 | 40.51 | 0.00 | 0.00 | 0.00 |
July | 393.93 | 225.19 | 168.74 | 568.73 | 20.60 | 0.00 | 0.00 | 0.00 |
August | 389.89 | 214.90 | 174.99 | 542.40 | 26.46 | 0.00 | 0.00 | 0.00 |
September | 325.12 | 181.92 | 143.20 | 427.58 | 58.48 | 0.00 | 0.00 | 0.00 |
October | 283.26 | 179.87 | 103.38 | 327.09 | 116.15 | 0.00 | 0.00 | 0.00 |
November | 220.30 | 129.24 | 91.06 | 213.14 | 177.39 | 0.00 | 0.00 | 0.00 |
December | 179.45 | 109.46 | 69.99 | 154.22 | 238.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.79 | 180.74 | 132.05 | 375.02 | 120.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.45 | 105.99 | 69.99 | 154.22 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 425.94 | 262.36 | 178.16 | 584.83 | 238.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 46.33 | 0.00 | 46.33 | 7.91 | 184.71 | 0.00 | 0.00 | 0.00 |
February | 57.90 | 0.00 | 57.90 | 19.35 | 164.87 | 0.00 | 0.00 | 0.00 |
March | 73.05 | 0.00 | 73.05 | 45.22 | 126.52 | 0.00 | 0.00 | 0.00 |
April | 93.17 | 1.25 | 91.93 | 76.78 | 80.49 | 0.00 | 0.00 | 0.00 |
May | 100.85 | 6.55 | 94.30 | 106.86 | 55.44 | 0.00 | 0.00 | 0.00 |
June | 114.82 | 19.10 | 95.73 | 165.76 | 33.82 | 0.00 | 0.00 | 0.00 |
July | 105.29 | 8.97 | 96.32 | 165.64 | 20.13 | 0.00 | 0.00 | 0.00 |
August | 97.72 | 2.39 | 95.32 | 139.09 | 24.63 | 0.00 | 0.00 | 0.00 |
September | 78.01 | 0.06 | 77.95 | 93.22 | 50.33 | 0.00 | 0.00 | 0.00 |
October | 58.15 | 0.00 | 58.15 | 41.15 | 98.51 | 0.00 | 0.00 | 0.00 |
November | 49.38 | 0.00 | 49.38 | 13.15 | 145.08 | 0.00 | 0.00 | 0.00 |
December | 39.43 | 0.00 | 39.43 | 2.12 | 192.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.24 | 3.20 | 73.04 | 73.31 | 97.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.43 | 0.00 | 39.43 | 2.12 | 20.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.82 | 19.10 | 96.32 | 165.76 | 192.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.08 | 0.00 | 17.08 | 2.91 | 68.09 | 0.00 | 0.00 | 0.00 |
February | 21.35 | 0.00 | 21.35 | 7.13 | 60.78 | 0.00 | 0.00 | 0.00 |
March | 26.93 | 0.00 | 26.93 | 16.67 | 46.64 | 0.00 | 0.00 | 0.00 |
April | 34.35 | 0.46 | 33.89 | 28.30 | 29.67 | 0.00 | 0.00 | 0.00 |
May | 37.18 | 2.42 | 34.76 | 39.39 | 20.44 | 0.00 | 0.00 | 0.00 |
June | 42.33 | 7.04 | 35.29 | 61.11 | 12.47 | 0.00 | 0.00 | 0.00 |
July | 38.81 | 3.31 | 35.51 | 61.06 | 7.42 | 0.00 | 0.00 | 0.00 |
August | 36.02 | 0.88 | 35.14 | 51.28 | 9.08 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 0.02 | 28.74 | 34.37 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 15.17 | 36.32 | 0.00 | 0.00 | 0.00 |
November | 18.20 | 0.00 | 18.20 | 4.85 | 53.48 | 0.00 | 0.00 | 0.00 |
December | 14.54 | 0.00 | 14.54 | 0.78 | 70.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.11 | 1.18 | 26.93 | 27.02 | 36.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.54 | 0.00 | 14.54 | 0.78 | 7.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.33 | 7.04 | 35.51 | 61.11 | 70.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.97 | 97.96 | 28.01 | 143.39 | 59.44 | 0.00 | 0.00 | 0.00 |
February | 124.17 | 90.87 | 33.29 | 144.23 | 54.71 | 0.00 | 0.00 | 0.00 |
March | 92.33 | 56.34 | 35.99 | 109.36 | 44.09 | 0.00 | 0.00 | 0.00 |
April | 70.91 | 29.06 | 41.85 | 87.34 | 30.61 | 0.00 | 0.00 | 0.00 |
May | 47.72 | 10.80 | 36.93 | 60.09 | 21.83 | 0.00 | 0.00 | 0.00 |
June | 39.90 | 4.79 | 35.11 | 60.06 | 13.56 | 0.00 | 0.00 | 0.00 |
July | 44.16 | 6.93 | 37.23 | 72.21 | 7.71 | 0.00 | 0.00 | 0.00 |
August | 60.07 | 18.95 | 41.13 | 92.34 | 9.51 | 0.00 | 0.00 | 0.00 |
September | 85.28 | 48.01 | 37.28 | 120.22 | 18.37 | 0.00 | 0.00 | 0.00 |
October | 114.90 | 84.52 | 30.38 | 145.49 | 33.02 | 0.00 | 0.00 | 0.00 |
November | 129.61 | 99.75 | 29.86 | 151.94 | 47.19 | 0.00 | 0.00 | 0.00 |
December | 137.37 | 113.40 | 23.97 | 157.59 | 60.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.17 | 54.93 | 34.24 | 111.83 | 33.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.90 | 4.79 | 23.97 | 60.06 | 7.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.37 | 113.40 | 41.85 | 157.59 | 60.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 341.90 | 265.89 | 76.02 | 389.19 | 161.34 | 0.00 | 0.00 | 0.00 |
February | 337.02 | 246.65 | 90.37 | 391.47 | 148.48 | 0.00 | 0.00 | 0.00 |
March | 250.61 | 152.92 | 97.68 | 296.83 | 119.68 | 0.00 | 0.00 | 0.00 |
April | 192.47 | 78.87 | 113.59 | 237.05 | 83.07 | 0.00 | 0.00 | 0.00 |
May | 129.53 | 29.30 | 100.23 | 163.09 | 59.24 | 0.00 | 0.00 | 0.00 |
June | 108.29 | 13.00 | 95.28 | 163.02 | 36.80 | 0.00 | 0.00 | 0.00 |
July | 119.86 | 18.81 | 101.06 | 195.98 | 20.92 | 0.00 | 0.00 | 0.00 |
August | 163.06 | 51.43 | 111.63 | 250.63 | 25.81 | 0.00 | 0.00 | 0.00 |
September | 231.48 | 130.30 | 101.18 | 326.29 | 49.87 | 0.00 | 0.00 | 0.00 |
October | 311.86 | 229.40 | 82.46 | 394.88 | 89.63 | 0.00 | 0.00 | 0.00 |
November | 351.78 | 270.74 | 81.05 | 412.40 | 128.08 | 0.00 | 0.00 | 0.00 |
December | 372.85 | 307.78 | 65.07 | 427.73 | 163.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.02 | 149.08 | 92.94 | 303.54 | 90.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.29 | 13.00 | 65.07 | 163.02 | 20.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 372.85 | 307.78 | 113.59 | 427.73 | 163.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 304.58 | 121.61 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 304.94 | 112.24 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 230.48 | 89.83 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 183.32 | 62.32 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 127.10 | 41.81 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 128.81 | 23.28 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 155.42 | 10.91 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 197.27 | 14.93 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 256.21 | 33.61 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 309.28 | 65.34 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 323.06 | 93.87 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 334.53 | 123.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 237.53 | 65.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 127.10 | 10.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 334.53 | 123.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 176.12 | 248.89 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 242.98 | 224.70 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 290.31 | 172.38 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 405.06 | 112.47 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 415.90 | 76.13 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 505.04 | 43.22 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 480.94 | 20.36 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 470.85 | 27.78 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 399.60 | 63.11 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 319.80 | 130.27 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 209.15 | 189.71 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 164.28 | 255.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 340.36 | 129.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 164.28 | 20.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 505.04 | 255.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 8.95 | 134.55 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 17.15 | 121.32 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 36.31 | 92.92 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 59.35 | 59.03 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 83.68 | 38.80 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 131.09 | 21.66 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 131.94 | 10.51 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 110.87 | 14.03 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 74.86 | 32.68 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 34.61 | 68.73 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 13.13 | 102.17 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 3.15 | 138.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 58.98 | 69.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 3.15 | 10.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 131.94 | 138.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 185.41 | 242.88 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 252.48 | 219.13 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 297.62 | 168.63 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 409.35 | 110.63 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 417.25 | 75.64 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 504.83 | 43.15 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 481.32 | 20.19 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 472.82 | 27.18 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 403.74 | 60.94 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 327.63 | 124.96 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 218.23 | 183.80 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 173.54 | 247.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 345.69 | 126.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 173.54 | 20.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 504.83 | 247.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.94 | 307.91 | 88.03 | 438.54 | 185.11 | 0.00 | 0.00 | 0.00 |
February | 390.28 | 285.63 | 104.65 | 440.60 | 169.86 | 0.00 | 0.00 | 0.00 |
March | 290.21 | 177.09 | 113.12 | 334.91 | 133.31 | 0.00 | 0.00 | 0.00 |
April | 222.88 | 91.34 | 131.54 | 270.24 | 87.70 | 0.00 | 0.00 | 0.00 |
May | 150.00 | 33.93 | 116.07 | 189.83 | 58.05 | 0.00 | 0.00 | 0.00 |
June | 125.40 | 15.06 | 110.34 | 194.92 | 31.68 | 0.00 | 0.00 | 0.00 |
July | 138.81 | 21.78 | 117.03 | 233.28 | 14.62 | 0.00 | 0.00 | 0.00 |
August | 188.83 | 59.55 | 129.27 | 293.34 | 20.27 | 0.00 | 0.00 | 0.00 |
September | 268.06 | 150.89 | 117.17 | 376.08 | 48.41 | 0.00 | 0.00 | 0.00 |
October | 361.15 | 265.65 | 95.49 | 450.67 | 97.45 | 0.00 | 0.00 | 0.00 |
November | 407.38 | 313.53 | 93.85 | 467.20 | 142.68 | 0.00 | 0.00 | 0.00 |
December | 431.78 | 356.43 | 75.35 | 481.95 | 188.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 280.27 | 172.64 | 107.62 | 347.09 | 97.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.40 | 15.06 | 75.35 | 189.83 | 14.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 431.78 | 356.43 | 131.54 | 481.95 | 188.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 256.06 | 0.00 | 256.06 | 26.77 | 1133.32 | 0.00 | 0.00 | 0.00 |
February | 320.04 | 0.00 | 320.04 | 78.74 | 1014.83 | 0.00 | 0.00 | 0.00 |
March | 403.77 | 0.01 | 403.75 | 210.02 | 772.63 | 0.00 | 0.00 | 0.00 |
April | 514.99 | 6.90 | 508.09 | 383.48 | 479.63 | 0.00 | 0.00 | 0.00 |
May | 557.42 | 36.22 | 521.20 | 549.68 | 327.44 | 0.00 | 0.00 | 0.00 |
June | 634.64 | 105.54 | 529.10 | 888.22 | 198.36 | 0.00 | 0.00 | 0.00 |
July | 581.96 | 49.60 | 532.35 | 895.89 | 119.69 | 0.00 | 0.00 | 0.00 |
August | 540.08 | 13.22 | 526.86 | 750.81 | 144.26 | 0.00 | 0.00 | 0.00 |
September | 431.15 | 0.31 | 430.84 | 499.67 | 285.42 | 0.00 | 0.00 | 0.00 |
October | 321.40 | 0.00 | 321.40 | 212.29 | 571.68 | 0.00 | 0.00 | 0.00 |
November | 272.95 | 0.00 | 272.95 | 54.93 | 878.52 | 0.00 | 0.00 | 0.00 |
December | 217.95 | 0.00 | 217.95 | 5.19 | 1186.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.40 | 17.68 | 403.72 | 381.27 | 590.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.95 | 0.00 | 217.95 | 5.19 | 119.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.64 | 105.54 | 532.35 | 895.89 | 1186.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 256.06 | 0.00 | 256.06 | 22.48 | 1158.23 | 0.00 | 0.00 | 0.00 |
February | 320.04 | 0.00 | 320.04 | 72.23 | 1035.66 | 0.00 | 0.00 | 0.00 |
March | 403.77 | 0.01 | 403.75 | 201.40 | 787.44 | 0.00 | 0.00 | 0.00 |
April | 514.99 | 6.90 | 508.09 | 374.94 | 489.42 | 0.00 | 0.00 | 0.00 |
May | 557.42 | 36.22 | 521.20 | 541.01 | 334.67 | 0.00 | 0.00 | 0.00 |
June | 634.64 | 105.54 | 529.10 | 880.08 | 203.60 | 0.00 | 0.00 | 0.00 |
July | 581.96 | 49.60 | 532.35 | 888.16 | 124.41 | 0.00 | 0.00 | 0.00 |
August | 540.08 | 13.22 | 526.86 | 743.41 | 149.48 | 0.00 | 0.00 | 0.00 |
September | 431.15 | 0.31 | 430.84 | 493.51 | 292.65 | 0.00 | 0.00 | 0.00 |
October | 321.40 | 0.00 | 321.40 | 206.33 | 583.67 | 0.00 | 0.00 | 0.00 |
November | 272.95 | 0.00 | 272.95 | 49.55 | 897.95 | 0.00 | 0.00 | 0.00 |
December | 217.95 | 0.00 | 217.95 | 3.99 | 1215.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.40 | 17.68 | 403.72 | 374.73 | 603.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.95 | 0.00 | 217.95 | 3.99 | 124.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.64 | 105.54 | 532.35 | 888.16 | 1215.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 7.37 | 149.13 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 16.56 | 135.34 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 39.10 | 104.49 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 68.85 | 66.10 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 96.19 | 46.33 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 148.30 | 29.26 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 150.34 | 18.35 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 128.99 | 21.55 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 89.14 | 38.28 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 41.66 | 75.17 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 12.95 | 114.57 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 2.14 | 155.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 67.07 | 79.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 2.14 | 18.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 150.34 | 155.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.72 | 211.97 | 166.75 | 322.81 | 510.27 | 0.00 | 0.00 | 0.00 |
February | 458.63 | 246.53 | 212.09 | 432.85 | 466.09 | 0.00 | 0.00 | 0.00 |
March | 609.47 | 347.21 | 262.26 | 663.03 | 359.85 | 0.00 | 0.00 | 0.00 |
April | 826.77 | 470.48 | 356.29 | 1012.72 | 238.09 | 0.00 | 0.00 | 0.00 |
May | 789.86 | 449.90 | 339.96 | 1034.99 | 174.11 | 0.00 | 0.00 | 0.00 |
June | 851.82 | 524.69 | 327.13 | 1243.94 | 109.72 | 0.00 | 0.00 | 0.00 |
July | 787.80 | 450.35 | 337.45 | 1217.14 | 68.79 | 0.00 | 0.00 | 0.00 |
August | 779.72 | 429.77 | 349.95 | 1163.03 | 80.97 | 0.00 | 0.00 | 0.00 |
September | 650.19 | 363.81 | 286.38 | 917.32 | 139.65 | 0.00 | 0.00 | 0.00 |
October | 566.48 | 359.72 | 206.75 | 690.42 | 260.66 | 0.00 | 0.00 | 0.00 |
November | 440.57 | 258.46 | 182.12 | 432.82 | 396.56 | 0.00 | 0.00 | 0.00 |
December | 358.87 | 218.90 | 139.97 | 309.12 | 533.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.54 | 361.45 | 264.09 | 788.33 | 277.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.87 | 211.97 | 139.97 | 309.12 | 68.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 851.82 | 524.69 | 356.29 | 1243.94 | 533.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 311.62 | 132.30 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 313.26 | 122.50 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 239.40 | 98.82 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 195.81 | 67.93 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 140.31 | 48.71 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 145.19 | 30.98 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 173.81 | 18.62 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 216.81 | 22.09 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 273.96 | 38.17 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 324.28 | 69.59 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 332.34 | 103.03 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 341.89 | 134.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 250.36 | 73.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 140.31 | 18.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 341.89 | 134.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 46.33 | 0.00 | 46.33 | 6.38 | 186.98 | 0.00 | 0.00 | 0.00 |
February | 57.90 | 0.00 | 57.90 | 16.73 | 167.22 | 0.00 | 0.00 | 0.00 |
March | 73.05 | 0.00 | 73.05 | 42.36 | 126.99 | 0.00 | 0.00 | 0.00 |
April | 93.17 | 1.25 | 91.93 | 73.39 | 80.33 | 0.00 | 0.00 | 0.00 |
May | 100.85 | 6.55 | 94.30 | 103.16 | 55.85 | 0.00 | 0.00 | 0.00 |
June | 114.82 | 19.10 | 95.73 | 161.99 | 34.74 | 0.00 | 0.00 | 0.00 |
July | 105.29 | 8.97 | 96.32 | 161.91 | 21.29 | 0.00 | 0.00 | 0.00 |
August | 97.72 | 2.39 | 95.32 | 135.59 | 25.78 | 0.00 | 0.00 | 0.00 |
September | 78.01 | 0.06 | 77.95 | 90.39 | 50.74 | 0.00 | 0.00 | 0.00 |
October | 58.15 | 0.00 | 58.15 | 38.91 | 97.49 | 0.00 | 0.00 | 0.00 |
November | 49.38 | 0.00 | 49.38 | 11.49 | 145.17 | 0.00 | 0.00 | 0.00 |
December | 39.43 | 0.00 | 39.43 | 1.43 | 196.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.24 | 3.20 | 73.04 | 70.60 | 98.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.43 | 0.00 | 39.43 | 1.43 | 21.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.82 | 19.10 | 96.32 | 161.99 | 196.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.45 | 0.00 | 41.45 | 5.71 | 167.26 | 0.00 | 0.00 | 0.00 |
February | 51.81 | 0.00 | 51.81 | 14.97 | 149.61 | 0.00 | 0.00 | 0.00 |
March | 65.36 | 0.00 | 65.36 | 37.90 | 113.62 | 0.00 | 0.00 | 0.00 |
April | 83.36 | 1.12 | 82.25 | 65.66 | 71.87 | 0.00 | 0.00 | 0.00 |
May | 90.23 | 5.86 | 84.37 | 92.30 | 49.97 | 0.00 | 0.00 | 0.00 |
June | 102.73 | 17.08 | 85.65 | 144.94 | 31.08 | 0.00 | 0.00 | 0.00 |
July | 94.20 | 8.03 | 86.17 | 144.87 | 19.05 | 0.00 | 0.00 | 0.00 |
August | 87.43 | 2.14 | 85.29 | 121.32 | 23.06 | 0.00 | 0.00 | 0.00 |
September | 69.79 | 0.05 | 69.74 | 80.88 | 45.39 | 0.00 | 0.00 | 0.00 |
October | 52.03 | 0.00 | 52.03 | 34.82 | 87.23 | 0.00 | 0.00 | 0.00 |
November | 44.18 | 0.00 | 44.18 | 10.28 | 129.87 | 0.00 | 0.00 | 0.00 |
December | 35.28 | 0.00 | 35.28 | 1.28 | 175.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.21 | 2.86 | 65.35 | 63.17 | 88.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.28 | 0.00 | 35.28 | 1.28 | 19.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.73 | 17.08 | 86.17 | 144.94 | 175.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1007.89 | 783.80 | 224.09 | 1134.04 | 478.74 | 0.00 | 0.00 | 0.00 |
February | 993.49 | 727.10 | 266.39 | 1138.79 | 441.73 | 0.00 | 0.00 | 0.00 |
March | 738.75 | 450.79 | 287.96 | 861.87 | 354.19 | 0.00 | 0.00 | 0.00 |
April | 567.37 | 232.51 | 334.85 | 685.53 | 244.95 | 0.00 | 0.00 | 0.00 |
May | 381.84 | 86.38 | 295.46 | 468.30 | 176.15 | 0.00 | 0.00 | 0.00 |
June | 319.21 | 38.33 | 280.88 | 469.45 | 111.25 | 0.00 | 0.00 | 0.00 |
July | 353.35 | 55.44 | 297.90 | 565.84 | 65.37 | 0.00 | 0.00 | 0.00 |
August | 480.67 | 151.60 | 329.07 | 726.53 | 79.76 | 0.00 | 0.00 | 0.00 |
September | 682.37 | 384.11 | 298.26 | 949.96 | 148.59 | 0.00 | 0.00 | 0.00 |
October | 919.32 | 676.23 | 243.09 | 1153.70 | 261.70 | 0.00 | 0.00 | 0.00 |
November | 1037.01 | 798.10 | 238.91 | 1204.84 | 376.04 | 0.00 | 0.00 | 0.00 |
December | 1099.11 | 907.30 | 191.81 | 1247.67 | 487.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.44 | 439.47 | 273.96 | 882.40 | 267.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.21 | 38.33 | 191.81 | 468.30 | 65.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1099.11 | 907.30 | 334.85 | 1247.67 | 487.35 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365721E+10 | 0.284409E+10 | 0.813124E+09 | 0.407130E+10 | 0.167545E+10 |
February | 0.325610E+10 | 0.238302E+10 | 0.873079E+09 | 0.369447E+10 | 0.139562E+10 |
March | 0.268063E+10 | 0.163574E+10 | 0.104489E+10 | 0.311699E+10 | 0.122436E+10 |
April | 0.199231E+10 | 0.816477E+09 | 0.117584E+10 | 0.240748E+10 | 0.821614E+09 |
May | 0.138554E+10 | 0.313445E+09 | 0.107209E+10 | 0.171306E+10 | 0.597954E+09 |
June | 0.112091E+10 | 0.134596E+09 | 0.986310E+09 | 0.162645E+10 | 0.372776E+09 |
July | 0.128213E+10 | 0.201175E+09 | 0.108095E+10 | 0.201619E+10 | 0.238767E+09 |
August | 0.174413E+10 | 0.550093E+09 | 0.119404E+10 | 0.260542E+10 | 0.291701E+09 |
September | 0.239615E+10 | 0.134882E+10 | 0.104733E+10 | 0.331352E+10 | 0.514931E+09 |
October | 0.333581E+10 | 0.245376E+10 | 0.882050E+09 | 0.414548E+10 | 0.928596E+09 |
November | 0.364151E+10 | 0.280257E+10 | 0.838938E+09 | 0.417500E+10 | 0.129159E+10 |
December | 0.398823E+10 | 0.329223E+10 | 0.695993E+09 | 0.446014E+10 | 0.171917E+10 |
Annual Sum or Average | 0.304806E+11 | 0.187760E+11 | 0.117046E+11 | 0.373455E+11 | 0.110725E+11 |
Minimum of Months | 0.112091E+10 | 0.134596E+09 | 0.695993E+09 | 0.162645E+10 | 0.238767E+09 |
Maximum of Months | 0.398823E+10 | 0.329223E+10 | 0.119404E+10 | 0.446014E+10 | 0.171917E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102985E+11 | 0.800876E+10 | 0.228970E+10 | 0.113410E+11 | 0.502261E+10 |
February | 0.916896E+10 | 0.671042E+10 | 0.245853E+10 | 0.102920E+11 | 0.419688E+10 |
March | 0.754847E+10 | 0.460613E+10 | 0.294234E+10 | 0.864751E+10 | 0.373163E+10 |
April | 0.561022E+10 | 0.229915E+10 | 0.331108E+10 | 0.666735E+10 | 0.250528E+10 |
May | 0.390158E+10 | 0.882641E+09 | 0.301894E+10 | 0.471166E+10 | 0.184044E+10 |
June | 0.315640E+10 | 0.379014E+09 | 0.277738E+10 | 0.450930E+10 | 0.112221E+10 |
July | 0.361039E+10 | 0.566496E+09 | 0.304390E+10 | 0.562538E+10 | 0.699428E+09 |
August | 0.491137E+10 | 0.154903E+10 | 0.336234E+10 | 0.728255E+10 | 0.850975E+09 |
September | 0.674739E+10 | 0.379819E+10 | 0.294920E+10 | 0.926332E+10 | 0.151510E+10 |
October | 0.939343E+10 | 0.690963E+10 | 0.248379E+10 | 0.115823E+11 | 0.276696E+10 |
November | 0.102543E+11 | 0.789186E+10 | 0.236239E+10 | 0.116417E+11 | 0.390316E+10 |
December | 0.112306E+11 | 0.927071E+10 | 0.195987E+10 | 0.124476E+11 | 0.515976E+10 |
Annual Sum or Average | 0.858315E+11 | 0.528720E+11 | 0.329595E+11 | 0.104012E+12 | 0.333144E+11 |
Minimum of Months | 0.315640E+10 | 0.379014E+09 | 0.195987E+10 | 0.450930E+10 | 0.699428E+09 |
Maximum of Months | 0.112306E+11 | 0.927071E+10 | 0.336234E+10 | 0.124476E+11 | 0.515976E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133783E+11 | 0.104038E+11 | 0.297446E+10 | 0.149779E+11 | 0.669512E+10 |
February | 0.119110E+11 | 0.871722E+10 | 0.319378E+10 | 0.136142E+11 | 0.558209E+10 |
March | 0.980589E+10 | 0.598362E+10 | 0.382227E+10 | 0.114483E+11 | 0.496491E+10 |
April | 0.728800E+10 | 0.298672E+10 | 0.430128E+10 | 0.887245E+10 | 0.331583E+10 |
May | 0.506838E+10 | 0.114660E+10 | 0.392177E+10 | 0.627858E+10 | 0.244453E+10 |
June | 0.410034E+10 | 0.492361E+09 | 0.360798E+10 | 0.602534E+10 | 0.148249E+10 |
July | 0.469011E+10 | 0.735911E+09 | 0.395420E+10 | 0.752334E+10 | 0.902690E+09 |
August | 0.638014E+10 | 0.201227E+10 | 0.436787E+10 | 0.970512E+10 | 0.108974E+10 |
September | 0.876524E+10 | 0.493407E+10 | 0.383118E+10 | 0.122899E+11 | 0.195585E+10 |
October | 0.122026E+11 | 0.897601E+10 | 0.322659E+10 | 0.153265E+11 | 0.362823E+10 |
November | 0.133209E+11 | 0.102520E+11 | 0.306888E+10 | 0.153898E+11 | 0.515853E+10 |
December | 0.145892E+11 | 0.120432E+11 | 0.254598E+10 | 0.164451E+11 | 0.686764E+10 |
Annual Sum or Average | 0.111500E+12 | 0.686838E+11 | 0.428162E+11 | 0.137897E+12 | 0.440876E+11 |
Minimum of Months | 0.410034E+10 | 0.492361E+09 | 0.254598E+10 | 0.602534E+10 | 0.902690E+09 |
Maximum of Months | 0.145892E+11 | 0.120432E+11 | 0.436787E+10 | 0.164451E+11 | 0.686764E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.818722E+09 | 0.327256E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.741258E+09 | 0.272338E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.621242E+09 | 0.240873E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.479471E+09 | 0.160932E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.343524E+09 | 0.112725E+09 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.335570E+09 | 61521898.23 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.418409E+09 | 30661622.11 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.531600E+09 | 41156659.11 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.667891E+09 | 88509138.46 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.831898E+09 | 0.175206E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.840032E+09 | 0.245695E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.898530E+09 | 0.333313E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.752815E+10 | 0.209019E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.335570E+09 | 30661622.11 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.898530E+09 | 0.333313E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.475045E+09 | 0.670845E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.593081E+09 | 0.545483E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.784798E+09 | 0.463265E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.105992E+10 | 0.291469E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.112247E+10 | 0.205579E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131557E+10 | 0.114209E+09 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.129438E+10 | 57195982.94 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.126777E+10 | 76566619.43 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.104150E+10 | 0.166352E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.862195E+09 | 0.350532E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.545694E+09 | 0.497615E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.443197E+09 | 0.689055E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.108056E+11 | 0.412817E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.443197E+09 | 57195982.94 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131557E+10 | 0.689055E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 23139218.56 | 0.362966E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 41276950.36 | 0.294734E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 97442710.69 | 0.249890E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.155756E+09 | 0.152911E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.226256E+09 | 0.104692E+09 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.341508E+09 | 57010661.08 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.354754E+09 | 29469282.52 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.298396E+09 | 38639221.81 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.194878E+09 | 86426872.81 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 92602808.44 | 0.185944E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 33119305.25 | 0.268616E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 7932725.46 | 0.374662E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.186706E+10 | 0.220596E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 7932725.46 | 29469282.52 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.354754E+09 | 0.374662E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.497370E+09 | 0.655462E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.613860E+09 | 0.532985E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.802508E+09 | 0.454401E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.107032E+10 | 0.287286E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.112594E+10 | 0.204322E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131504E+10 | 0.113987E+09 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.129534E+10 | 56741210.13 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.127280E+10 | 75048345.65 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.105170E+10 | 0.161227E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.881104E+09 | 0.338626E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.566220E+09 | 0.484026E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.465183E+09 | 0.668790E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.109574E+11 | 0.403290E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.465183E+09 | 56741210.13 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131504E+10 | 0.668790E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578361E+09 | 0.449770E+09 | 0.128590E+09 | 0.643324E+09 | 0.285782E+09 |
February | 0.514928E+09 | 0.376856E+09 | 0.138072E+09 | 0.583609E+09 | 0.239849E+09 |
March | 0.423922E+09 | 0.258679E+09 | 0.165243E+09 | 0.490248E+09 | 0.211164E+09 |
April | 0.315071E+09 | 0.129120E+09 | 0.185952E+09 | 0.381358E+09 | 0.137847E+09 |
May | 0.219114E+09 | 49568964.22 | 0.169545E+09 | 0.273332E+09 | 98500879.21 |
June | 0.177265E+09 | 21285372.45 | 0.155980E+09 | 0.268950E+09 | 57288916.70 |
July | 0.202761E+09 | 31814303.90 | 0.170947E+09 | 0.334919E+09 | 32163284.31 |
August | 0.275824E+09 | 86993003.94 | 0.188831E+09 | 0.425845E+09 | 40323875.31 |
September | 0.378934E+09 | 0.213306E+09 | 0.165628E+09 | 0.532859E+09 | 78668215.86 |
October | 0.527535E+09 | 0.388044E+09 | 0.139491E+09 | 0.661418E+09 | 0.152638E+09 |
November | 0.575878E+09 | 0.443205E+09 | 0.132673E+09 | 0.661640E+09 | 0.220684E+09 |
December | 0.630708E+09 | 0.520641E+09 | 0.110067E+09 | 0.706584E+09 | 0.294528E+09 |
Annual Sum or Average | 0.482030E+10 | 0.296928E+10 | 0.185102E+10 | 0.596409E+10 | 0.184944E+10 |
Minimum of Months | 0.177265E+09 | 21285372.45 | 0.110067E+09 | 0.268950E+09 | 32163284.31 |
Maximum of Months | 0.630708E+09 | 0.520641E+09 | 0.188831E+09 | 0.706584E+09 | 0.294528E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78395194.18 | 0.00 | 78395194.18 | 18217267.24 | 0.295519E+09 |
February | 88498821.31 | 0.00 | 88498821.31 | 34912514.49 | 0.237228E+09 |
March | 0.123615E+09 | 4297.01 | 0.123611E+09 | 84280125.49 | 0.196806E+09 |
April | 0.152580E+09 | 2043871.97 | 0.150536E+09 | 0.136942E+09 | 0.115247E+09 |
May | 0.170657E+09 | 11088084.06 | 0.159568E+09 | 0.194378E+09 | 78307020.56 |
June | 0.188031E+09 | 31269876.03 | 0.156761E+09 | 0.288161E+09 | 41237931.25 |
July | 0.178169E+09 | 15186292.66 | 0.162983E+09 | 0.299191E+09 | 19453814.81 |
August | 0.165349E+09 | 4046567.42 | 0.161302E+09 | 0.254362E+09 | 25804560.72 |
September | 0.127739E+09 | 91026.49 | 0.127648E+09 | 0.168069E+09 | 61773350.74 |
October | 98399454.57 | 0.00 | 98399454.57 | 82651627.33 | 0.140351E+09 |
November | 80868758.46 | 0.00 | 80868758.46 | 28206678.69 | 0.215044E+09 |
December | 66726175.04 | 0.00 | 66726175.04 | 5851226.62 | 0.306455E+09 |
Annual Sum or Average | 0.151903E+10 | 63730015.63 | 0.145530E+10 | 0.159522E+10 | 0.173323E+10 |
Minimum of Months | 66726175.04 | 0.00 | 66726175.04 | 5851226.62 | 19453814.81 |
Maximum of Months | 0.188031E+09 | 31269876.03 | 0.162983E+09 | 0.299191E+09 | 0.306455E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507216E+09 | 0.283893E+09 | 0.223323E+09 | 0.413249E+09 | 0.633546E+09 |
February | 0.554793E+09 | 0.298227E+09 | 0.256566E+09 | 0.500365E+09 | 0.516871E+09 |
March | 0.816260E+09 | 0.465022E+09 | 0.351239E+09 | 0.848188E+09 | 0.432681E+09 |
April | 0.107158E+10 | 0.609786E+09 | 0.461789E+09 | 0.124761E+10 | 0.271853E+09 |
May | 0.105785E+10 | 0.602543E+09 | 0.455309E+09 | 0.131029E+10 | 0.195712E+09 |
June | 0.110403E+10 | 0.680041E+09 | 0.423991E+09 | 0.151614E+10 | 0.104974E+09 |
July | 0.105510E+10 | 0.603154E+09 | 0.451944E+09 | 0.152214E+10 | 55547011.37 |
August | 0.104428E+10 | 0.575590E+09 | 0.468689E+09 | 0.144790E+10 | 72293271.03 |
September | 0.842711E+09 | 0.471538E+09 | 0.371174E+09 | 0.109857E+10 | 0.156520E+09 |
October | 0.758679E+09 | 0.481775E+09 | 0.276904E+09 | 0.860267E+09 | 0.323053E+09 |
November | 0.571024E+09 | 0.334984E+09 | 0.236040E+09 | 0.533899E+09 | 0.477322E+09 |
December | 0.480632E+09 | 0.293171E+09 | 0.187461E+09 | 0.398194E+09 | 0.668393E+09 |
Annual Sum or Average | 0.986415E+10 | 0.569972E+10 | 0.416443E+10 | 0.116968E+11 | 0.390877E+10 |
Minimum of Months | 0.480632E+09 | 0.283893E+09 | 0.187461E+09 | 0.398194E+09 | 55547011.37 |
Maximum of Months | 0.110403E+10 | 0.680041E+09 | 0.468689E+09 | 0.152214E+10 | 0.668393E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.816566E+09 | 0.325839E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.739475E+09 | 0.270036E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.617711E+09 | 0.238024E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.475203E+09 | 0.157314E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.336935E+09 | 0.110822E+09 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.326496E+09 | 60337952.92 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.409563E+09 | 30914129.88 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.523552E+09 | 40874514.10 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.662982E+09 | 87141440.56 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.830197E+09 | 0.171086E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.837532E+09 | 0.244139E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.896411E+09 | 0.331895E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.747262E+10 | 0.206842E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.326496E+09 | 30914129.88 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.896411E+09 | 0.331895E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 21452399.43 | 0.361106E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 40050016.24 | 0.292262E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 93936316.32 | 0.248874E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.150511E+09 | 0.150358E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.219622E+09 | 0.103177E+09 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.332293E+09 | 56112538.72 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.345731E+09 | 29756484.27 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.289834E+09 | 38178876.33 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.189830E+09 | 85414298.85 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 89732787.91 | 0.182409E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 31192639.42 | 0.266809E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 6833136.03 | 0.373416E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.181102E+10 | 0.218787E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 6833136.03 | 29756484.27 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.345731E+09 | 0.373416E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507216E+09 | 0.283893E+09 | 0.223323E+09 | 0.433405E+09 | 0.613843E+09 |
February | 0.554793E+09 | 0.298227E+09 | 0.256566E+09 | 0.520150E+09 | 0.501482E+09 |
March | 0.816260E+09 | 0.465022E+09 | 0.351239E+09 | 0.862902E+09 | 0.423934E+09 |
April | 0.107158E+10 | 0.609786E+09 | 0.461789E+09 | 0.125515E+10 | 0.268046E+09 |
May | 0.105785E+10 | 0.602543E+09 | 0.455309E+09 | 0.131310E+10 | 0.194566E+09 |
June | 0.110403E+10 | 0.680041E+09 | 0.423991E+09 | 0.151588E+10 | 0.104996E+09 |
July | 0.105510E+10 | 0.603154E+09 | 0.451944E+09 | 0.152327E+10 | 55174578.87 |
August | 0.104428E+10 | 0.575590E+09 | 0.468689E+09 | 0.145277E+10 | 70869532.47 |
September | 0.842711E+09 | 0.471538E+09 | 0.371174E+09 | 0.110828E+10 | 0.151589E+09 |
October | 0.758679E+09 | 0.481775E+09 | 0.276904E+09 | 0.876084E+09 | 0.311099E+09 |
November | 0.571024E+09 | 0.334984E+09 | 0.236040E+09 | 0.552462E+09 | 0.459796E+09 |
December | 0.480632E+09 | 0.293171E+09 | 0.187461E+09 | 0.413059E+09 | 0.638179E+09 |
Annual Sum or Average | 0.986415E+10 | 0.569972E+10 | 0.416443E+10 | 0.118265E+11 | 0.379357E+10 |
Minimum of Months | 0.480632E+09 | 0.283893E+09 | 0.187461E+09 | 0.413059E+09 | 55174578.87 |
Maximum of Months | 0.110403E+10 | 0.680041E+09 | 0.468689E+09 | 0.152327E+10 | 0.638179E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124087E+09 | 0.00 | 0.124087E+09 | 21178405.08 | 0.494719E+09 |
February | 0.140079E+09 | 0.00 | 0.140079E+09 | 46811896.76 | 0.398845E+09 |
March | 0.195663E+09 | 6801.46 | 0.195656E+09 | 0.121107E+09 | 0.338866E+09 |
April | 0.241509E+09 | 3235114.78 | 0.238274E+09 | 0.199008E+09 | 0.208627E+09 |
May | 0.270121E+09 | 17550622.12 | 0.252571E+09 | 0.286218E+09 | 0.148485E+09 |
June | 0.297622E+09 | 49495095.36 | 0.248127E+09 | 0.429659E+09 | 87651650.30 |
July | 0.282012E+09 | 24037415.51 | 0.257975E+09 | 0.443658E+09 | 53918091.80 |
August | 0.261720E+09 | 6405053.86 | 0.255315E+09 | 0.372547E+09 | 65959003.11 |
September | 0.202191E+09 | 144080.03 | 0.202047E+09 | 0.241628E+09 | 0.130444E+09 |
October | 0.155750E+09 | 0.00 | 0.155750E+09 | 0.110206E+09 | 0.263852E+09 |
November | 0.128002E+09 | 0.00 | 0.128002E+09 | 34084666.68 | 0.376056E+09 |
December | 0.105617E+09 | 0.00 | 0.105617E+09 | 5671987.98 | 0.515148E+09 |
Annual Sum or Average | 0.240437E+10 | 0.100874E+09 | 0.230350E+10 | 0.231178E+10 | 0.308257E+10 |
Minimum of Months | 0.105617E+09 | 0.00 | 0.105617E+09 | 5671987.98 | 53918091.80 |
Maximum of Months | 0.297622E+09 | 49495095.36 | 0.257975E+09 | 0.443658E+09 | 0.515148E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45743517.88 | 0.00 | 45743517.88 | 7807237.04 | 0.182374E+09 |
February | 51638974.26 | 0.00 | 51638974.26 | 17256803.47 | 0.147030E+09 |
March | 72129348.61 | 2507.30 | 72126841.31 | 44644916.14 | 0.124920E+09 |
April | 89030149.10 | 1192597.26 | 87837551.84 | 73362636.85 | 76908369.93 |
May | 99577941.81 | 6469886.03 | 93108055.78 | 0.105512E+09 | 54737604.47 |
June | 0.109716E+09 | 18245941.58 | 91469732.72 | 0.158390E+09 | 32312027.67 |
July | 0.103961E+09 | 8861186.67 | 95100166.05 | 0.163551E+09 | 19876441.21 |
August | 96480877.97 | 2361168.07 | 94119709.91 | 0.137336E+09 | 24315219.69 |
September | 74535836.68 | 53113.86 | 74482722.82 | 89074171.34 | 48087228.10 |
October | 57415983.93 | 0.00 | 57415983.93 | 40626346.89 | 97266839.14 |
November | 47186840.17 | 0.00 | 47186840.17 | 12565019.47 | 0.138630E+09 |
December | 38934656.81 | 0.00 | 38934656.81 | 2090929.63 | 0.189905E+09 |
Annual Sum or Average | 0.886351E+09 | 37186400.77 | 0.849165E+09 | 0.852217E+09 | 0.113636E+10 |
Minimum of Months | 38934656.81 | 0.00 | 38934656.81 | 2090929.63 | 19876441.21 |
Maximum of Months | 0.109716E+09 | 18245941.58 | 95100166.05 | 0.163551E+09 | 0.189905E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337393E+09 | 0.262378E+09 | 75014586.89 | 0.384052E+09 | 0.159215E+09 |
February | 0.300389E+09 | 0.219843E+09 | 80545831.06 | 0.348921E+09 | 0.132344E+09 |
March | 0.247300E+09 | 0.150903E+09 | 96396323.39 | 0.292916E+09 | 0.118098E+09 |
April | 0.183800E+09 | 75323316.63 | 0.108477E+09 | 0.226375E+09 | 79329820.87 |
May | 0.127823E+09 | 28916598.29 | 98906174.13 | 0.160939E+09 | 58458592.25 |
June | 0.103410E+09 | 12417055.19 | 90992515.30 | 0.155679E+09 | 35142226.85 |
July | 0.118283E+09 | 18559222.69 | 99723891.11 | 0.193395E+09 | 20640709.65 |
August | 0.160905E+09 | 50748321.82 | 0.110156E+09 | 0.247328E+09 | 25467138.61 |
September | 0.221055E+09 | 0.124434E+09 | 96621084.81 | 0.311599E+09 | 47626458.35 |
October | 0.307743E+09 | 0.226370E+09 | 81373553.20 | 0.389671E+09 | 88445300.53 |
November | 0.335945E+09 | 0.258549E+09 | 77396069.05 | 0.393836E+09 | 0.122311E+09 |
December | 0.367930E+09 | 0.303722E+09 | 64208705.21 | 0.422087E+09 | 0.161776E+09 |
Annual Sum or Average | 0.281198E+10 | 0.173216E+10 | 0.107981E+10 | 0.352680E+10 | 0.104885E+10 |
Minimum of Months | 0.103410E+09 | 12417055.19 | 64208705.21 | 0.155679E+09 | 20640709.65 |
Maximum of Months | 0.367930E+09 | 0.303722E+09 | 0.110156E+09 | 0.422087E+09 | 0.161776E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.915754E+09 | 0.712149E+09 | 0.203605E+09 | 0.104240E+10 | 0.432143E+09 |
February | 0.815317E+09 | 0.596699E+09 | 0.218618E+09 | 0.947042E+09 | 0.359209E+09 |
March | 0.671222E+09 | 0.409583E+09 | 0.261639E+09 | 0.795033E+09 | 0.320542E+09 |
April | 0.498871E+09 | 0.204443E+09 | 0.294428E+09 | 0.614428E+09 | 0.215317E+09 |
May | 0.346937E+09 | 78485562.51 | 0.268452E+09 | 0.436822E+09 | 0.158669E+09 |
June | 0.280675E+09 | 33702427.65 | 0.246972E+09 | 0.422543E+09 | 95383191.85 |
July | 0.321045E+09 | 50373526.60 | 0.270671E+09 | 0.524915E+09 | 56023107.95 |
August | 0.436728E+09 | 0.137741E+09 | 0.298987E+09 | 0.671299E+09 | 69122780.59 |
September | 0.599989E+09 | 0.337740E+09 | 0.262249E+09 | 0.845744E+09 | 0.129268E+09 |
October | 0.835278E+09 | 0.614413E+09 | 0.220864E+09 | 0.105765E+10 | 0.240059E+09 |
November | 0.911822E+09 | 0.701754E+09 | 0.210069E+09 | 0.106895E+10 | 0.331977E+09 |
December | 0.998639E+09 | 0.824363E+09 | 0.174276E+09 | 0.114563E+10 | 0.439093E+09 |
Annual Sum or Average | 0.763228E+10 | 0.470145E+10 | 0.293083E+10 | 0.957245E+10 | 0.284681E+10 |
Minimum of Months | 0.280675E+09 | 33702427.65 | 0.174276E+09 | 0.422543E+09 | 56023107.95 |
Maximum of Months | 0.998639E+09 | 0.824363E+09 | 0.298987E+09 | 0.114563E+10 | 0.439093E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.815795E+09 | 0.325732E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.737719E+09 | 0.271526E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.617307E+09 | 0.240606E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.475172E+09 | 0.161525E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.340421E+09 | 0.111975E+09 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.333882E+09 | 60352487.71 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.416283E+09 | 29218958.08 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.528362E+09 | 39999303.19 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.664103E+09 | 87115143.10 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.828384E+09 | 0.175008E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.837368E+09 | 0.243310E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.896007E+09 | 0.331324E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.749080E+10 | 0.207769E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.333882E+09 | 29218958.08 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.896007E+09 | 0.331324E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.471707E+09 | 0.666639E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.587812E+09 | 0.543603E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.777569E+09 | 0.461712E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.104993E+10 | 0.291510E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.111395E+10 | 0.203893E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.130906E+10 | 0.112028E+09 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.128815E+10 | 54530091.05 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.126113E+10 | 74400705.31 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.103577E+10 | 0.163588E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.856542E+09 | 0.348914E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.542109E+09 | 0.491730E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.440002E+09 | 0.683759E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.107337E+11 | 0.409631E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.440002E+09 | 54530091.05 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.130906E+10 | 0.683759E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 23968507.42 | 0.360380E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 41498297.03 | 0.293501E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 97247787.37 | 0.248865E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.153844E+09 | 0.153015E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.224119E+09 | 0.103931E+09 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.339781E+09 | 56132758.68 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.353377E+09 | 28143365.63 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.296956E+09 | 37577562.69 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.194047E+09 | 84716024.45 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 92709377.96 | 0.184094E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 34039300.92 | 0.264818E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 8430401.78 | 0.371388E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.186002E+10 | 0.218656E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 8430401.78 | 28143365.63 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.353377E+09 | 0.371388E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.496591E+09 | 0.650530E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.610795E+09 | 0.530130E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.797145E+09 | 0.451661E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.106104E+10 | 0.286763E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.111756E+10 | 0.202604E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.130853E+10 | 0.111836E+09 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.128917E+10 | 54072253.87 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.126639E+10 | 72788967.88 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.104650E+10 | 0.157960E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.877525E+09 | 0.334681E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.565650E+09 | 0.476422E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.464822E+09 | 0.663017E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.109017E+11 | 0.399247E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.464822E+09 | 54072253.87 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.130853E+10 | 0.663017E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106049E+10 | 0.824703E+09 | 0.235784E+09 | 0.117460E+10 | 0.495809E+09 |
February | 0.944177E+09 | 0.691007E+09 | 0.253170E+09 | 0.106589E+10 | 0.410932E+09 |
March | 0.777308E+09 | 0.474317E+09 | 0.302991E+09 | 0.897014E+09 | 0.357049E+09 |
April | 0.577717E+09 | 0.236755E+09 | 0.340963E+09 | 0.700455E+09 | 0.227331E+09 |
May | 0.401770E+09 | 90890125.98 | 0.310880E+09 | 0.508433E+09 | 0.155484E+09 |
June | 0.325035E+09 | 39029062.12 | 0.286006E+09 | 0.505237E+09 | 82104397.18 |
July | 0.371785E+09 | 58335011.33 | 0.313450E+09 | 0.624822E+09 | 39146136.38 |
August | 0.505753E+09 | 0.159511E+09 | 0.346242E+09 | 0.785671E+09 | 54296032.74 |
September | 0.694817E+09 | 0.391119E+09 | 0.303698E+09 | 0.974801E+09 | 0.125488E+09 |
October | 0.967293E+09 | 0.711521E+09 | 0.255772E+09 | 0.120706E+10 | 0.260999E+09 |
November | 0.105593E+10 | 0.812665E+09 | 0.243270E+09 | 0.121099E+10 | 0.369834E+09 |
December | 0.115647E+10 | 0.954653E+09 | 0.201820E+09 | 0.129086E+10 | 0.506091E+09 |
Annual Sum or Average | 0.883855E+10 | 0.544450E+10 | 0.339405E+10 | 0.109458E+11 | 0.308456E+10 |
Minimum of Months | 0.325035E+09 | 39029062.12 | 0.201820E+09 | 0.505237E+09 | 39146136.38 |
Maximum of Months | 0.115647E+10 | 0.954653E+09 | 0.346242E+09 | 0.129086E+10 | 0.506091E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.685841E+09 | 0.00 | 0.685841E+09 | 71690021.79 | 0.303549E+10 |
February | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.190476E+09 | 0.245509E+10 |
March | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.562510E+09 | 0.206940E+10 |
April | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.993983E+09 | 0.124320E+10 |
May | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.147226E+10 | 0.877010E+09 |
June | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.230227E+10 | 0.514139E+09 |
July | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.239954E+10 | 0.320566E+09 |
August | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.201097E+10 | 0.386393E+09 |
September | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.129514E+10 | 0.739799E+09 |
October | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.568589E+09 | 0.153120E+10 |
November | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.142385E+09 | 0.227713E+10 |
December | 0.583755E+09 | 0.00 | 0.583755E+09 | 13911311.93 | 0.317747E+10 |
Annual Sum or Average | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.120237E+11 | 0.186269E+11 |
Minimum of Months | 0.583755E+09 | 0.00 | 0.583755E+09 | 13911311.93 | 0.320566E+09 |
Maximum of Months | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.239954E+10 | 0.317747E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.685841E+09 | 0.00 | 0.685841E+09 | 60216376.95 | 0.310219E+10 |
February | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.174736E+09 | 0.250547E+10 |
March | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.539442E+09 | 0.210907E+10 |
April | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.971834E+09 | 0.126857E+10 |
May | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.144904E+10 | 0.896380E+09 |
June | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.228117E+10 | 0.527743E+09 |
July | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.237886E+10 | 0.333208E+09 |
August | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.199115E+10 | 0.400378E+09 |
September | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.127918E+10 | 0.758557E+09 |
October | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.552640E+09 | 0.156331E+10 |
November | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.128436E+09 | 0.232750E+10 |
December | 0.583755E+09 | 0.00 | 0.583755E+09 | 10683855.72 | 0.325431E+10 |
Annual Sum or Average | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.118174E+11 | 0.190467E+11 |
Minimum of Months | 0.583755E+09 | 0.00 | 0.583755E+09 | 10683855.72 | 0.333208E+09 |
Maximum of Months | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.237886E+10 | 0.325431E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 19736516.33 | 0.399438E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 40070991.42 | 0.327404E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.104721E+09 | 0.279866E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.178464E+09 | 0.171340E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.257647E+09 | 0.124095E+09 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.384394E+09 | 75832617.41 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.402660E+09 | 49146748.16 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.345494E+09 | 57714099.04 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.231042E+09 | 99224136.07 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 0.111588E+09 | 0.201347E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 33565964.32 | 0.296960E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 5738162.49 | 0.415422E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.211512E+10 | 0.249779E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 5738162.49 | 49146748.16 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.402660E+09 | 0.415422E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101436E+10 | 0.567746E+09 | 0.446614E+09 | 0.864609E+09 | 0.136670E+10 |
February | 0.110951E+10 | 0.596411E+09 | 0.513096E+09 | 0.104715E+10 | 0.112756E+10 |
March | 0.163240E+10 | 0.929977E+09 | 0.702427E+09 | 0.177585E+10 | 0.963810E+09 |
April | 0.214300E+10 | 0.121949E+10 | 0.923513E+09 | 0.262497E+10 | 0.617126E+09 |
May | 0.211555E+10 | 0.120500E+10 | 0.910554E+09 | 0.277212E+10 | 0.466327E+09 |
June | 0.220791E+10 | 0.135999E+10 | 0.847922E+09 | 0.322430E+10 | 0.284400E+09 |
July | 0.211005E+10 | 0.120622E+10 | 0.903823E+09 | 0.325999E+10 | 0.184246E+09 |
August | 0.208841E+10 | 0.115110E+10 | 0.937312E+09 | 0.311506E+10 | 0.216877E+09 |
September | 0.168530E+10 | 0.943008E+09 | 0.742295E+09 | 0.237770E+10 | 0.361972E+09 |
October | 0.151725E+10 | 0.963481E+09 | 0.553769E+09 | 0.184923E+10 | 0.698141E+09 |
November | 0.114197E+10 | 0.669921E+09 | 0.472046E+09 | 0.112187E+10 | 0.102787E+10 |
December | 0.961196E+09 | 0.586300E+09 | 0.374896E+09 | 0.827945E+09 | 0.142795E+10 |
Annual Sum or Average | 0.197269E+11 | 0.113986E+11 | 0.832827E+10 | 0.248608E+11 | 0.874299E+10 |
Minimum of Months | 0.961196E+09 | 0.567746E+09 | 0.374896E+09 | 0.827945E+09 | 0.184246E+09 |
Maximum of Months | 0.220791E+10 | 0.135999E+10 | 0.937312E+09 | 0.325999E+10 | 0.142795E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.834643E+09 | 0.354345E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.757830E+09 | 0.296347E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.641204E+09 | 0.264671E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.507551E+09 | 0.176075E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.375802E+09 | 0.130463E+09 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.376325E+09 | 80311431.27 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.465527E+09 | 49867174.14 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.580710E+09 | 59177196.46 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.710106E+09 | 98942246.05 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.868562E+09 | 0.186380E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.861434E+09 | 0.267041E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.915715E+09 | 0.360120E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.789541E+10 | 0.232374E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.375802E+09 | 49867174.14 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.915715E+09 | 0.360120E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124087E+09 | 0.00 | 0.124087E+09 | 17101255.49 | 0.500810E+09 |
February | 0.140079E+09 | 0.00 | 0.140079E+09 | 40484331.26 | 0.404533E+09 |
March | 0.195663E+09 | 6801.46 | 0.195656E+09 | 0.113470E+09 | 0.340122E+09 |
April | 0.241509E+09 | 3235114.78 | 0.238274E+09 | 0.190232E+09 | 0.208211E+09 |
May | 0.270121E+09 | 17550622.12 | 0.252571E+09 | 0.276301E+09 | 0.149596E+09 |
June | 0.297622E+09 | 49495095.36 | 0.248127E+09 | 0.419890E+09 | 90043662.83 |
July | 0.282012E+09 | 24037415.51 | 0.257975E+09 | 0.433672E+09 | 57031062.05 |
August | 0.261720E+09 | 6405053.86 | 0.255315E+09 | 0.363175E+09 | 69042146.08 |
September | 0.202191E+09 | 144080.03 | 0.202047E+09 | 0.234302E+09 | 0.131508E+09 |
October | 0.155750E+09 | 0.00 | 0.155750E+09 | 0.104227E+09 | 0.261125E+09 |
November | 0.128002E+09 | 0.00 | 0.128002E+09 | 29771608.74 | 0.376272E+09 |
December | 0.105617E+09 | 0.00 | 0.105617E+09 | 3843405.31 | 0.525081E+09 |
Annual Sum or Average | 0.240437E+10 | 0.100874E+09 | 0.230350E+10 | 0.222647E+10 | 0.311337E+10 |
Minimum of Months | 0.105617E+09 | 0.00 | 0.105617E+09 | 3843405.31 | 57031062.05 |
Maximum of Months | 0.297622E+09 | 49495095.36 | 0.257975E+09 | 0.433672E+09 | 0.525081E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111021E+09 | 0.00 | 0.111021E+09 | 15300558.09 | 0.448001E+09 |
February | 0.125329E+09 | 0.00 | 0.125329E+09 | 36221484.57 | 0.361940E+09 |
March | 0.175060E+09 | 6085.29 | 0.175054E+09 | 0.101522E+09 | 0.304308E+09 |
April | 0.216079E+09 | 2894469.45 | 0.213184E+09 | 0.170201E+09 | 0.186287E+09 |
May | 0.241679E+09 | 15702608.11 | 0.225976E+09 | 0.247207E+09 | 0.133844E+09 |
June | 0.266283E+09 | 44283449.36 | 0.222000E+09 | 0.375678E+09 | 80562406.31 |
July | 0.252317E+09 | 21506366.74 | 0.230811E+09 | 0.388008E+09 | 51025907.30 |
August | 0.234162E+09 | 5730625.96 | 0.228431E+09 | 0.324934E+09 | 61772269.70 |
September | 0.180901E+09 | 128908.95 | 0.180772E+09 | 0.209631E+09 | 0.117661E+09 |
October | 0.139350E+09 | 0.00 | 0.139350E+09 | 93252208.73 | 0.233629E+09 |
November | 0.114524E+09 | 0.00 | 0.114524E+09 | 26636771.15 | 0.336632E+09 |
December | 94495583.87 | 0.00 | 94495583.87 | 3438709.29 | 0.469756E+09 |
Annual Sum or Average | 0.215120E+10 | 90252513.85 | 0.206095E+10 | 0.199203E+10 | 0.278542E+10 |
Minimum of Months | 94495583.87 | 0.00 | 94495583.87 | 3438709.29 | 51025907.30 |
Maximum of Months | 0.266283E+09 | 44283449.36 | 0.230811E+09 | 0.388008E+09 | 0.469756E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269953E+10 | 0.209933E+10 | 0.600202E+09 | 0.303740E+10 | 0.128225E+10 |
February | 0.240345E+10 | 0.175899E+10 | 0.644458E+09 | 0.275496E+10 | 0.106863E+10 |
March | 0.197868E+10 | 0.120740E+10 | 0.771280E+09 | 0.230843E+10 | 0.948667E+09 |
April | 0.147061E+10 | 0.602672E+09 | 0.867938E+09 | 0.177689E+10 | 0.634917E+09 |
May | 0.102273E+10 | 0.231366E+09 | 0.791362E+09 | 0.125430E+10 | 0.471805E+09 |
June | 0.827394E+09 | 99350551.84 | 0.728044E+09 | 0.121681E+10 | 0.288355E+09 |
July | 0.946399E+09 | 0.148495E+09 | 0.797904E+09 | 0.151556E+10 | 0.175095E+09 |
August | 0.128742E+10 | 0.406044E+09 | 0.881376E+09 | 0.194593E+10 | 0.213629E+09 |
September | 0.176869E+10 | 0.995615E+09 | 0.773078E+09 | 0.246230E+10 | 0.385140E+09 |
October | 0.246229E+10 | 0.181121E+10 | 0.651081E+09 | 0.309006E+10 | 0.700946E+09 |
November | 0.268794E+10 | 0.206868E+10 | 0.619257E+09 | 0.312294E+10 | 0.974701E+09 |
December | 0.294386E+10 | 0.243012E+10 | 0.513743E+09 | 0.334176E+10 | 0.130531E+10 |
Annual Sum or Average | 0.224990E+11 | 0.138593E+11 | 0.863972E+10 | 0.278273E+11 | 0.844945E+10 |
Minimum of Months | 0.827394E+09 | 99350551.84 | 0.513743E+09 | 0.121681E+10 | 0.175095E+09 |
Maximum of Months | 0.294386E+10 | 0.243012E+10 | 0.881376E+09 | 0.334176E+10 | 0.130531E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1520.05 | 625.54 | 1365.45 | 1061.86 | 303.59 | 0.00 | 0.00 |
February | 1527.15 | 576.89 | 1345.94 | 985.04 | 360.90 | 0.00 | 0.00 |
March | 1163.75 | 457.12 | 1000.83 | 610.71 | 390.12 | 0.00 | 0.00 |
April | 928.81 | 316.98 | 768.64 | 315.00 | 453.64 | 0.00 | 0.00 |
May | 639.58 | 223.25 | 517.30 | 117.03 | 400.27 | 0.00 | 0.00 |
June | 627.49 | 143.82 | 432.45 | 51.93 | 380.52 | 0.00 | 0.00 |
July | 752.76 | 89.15 | 478.69 | 75.11 | 403.58 | 0.00 | 0.00 |
August | 972.75 | 108.91 | 651.18 | 205.38 | 445.80 | 0.00 | 0.00 |
September | 1278.36 | 198.66 | 924.44 | 520.38 | 404.06 | 0.00 | 0.00 |
October | 1547.75 | 346.70 | 1245.45 | 916.13 | 329.32 | 0.00 | 0.00 |
November | 1610.72 | 498.30 | 1404.90 | 1081.24 | 323.66 | 0.00 | 0.00 |
December | 1665.23 | 641.86 | 1489.03 | 1229.18 | 259.85 | 0.00 | 0.00 |
Annual Sum or Average | 1184.22 | 351.11 | 966.54 | 595.38 | 371.15 | 0.00 | 0.00 |
Minimum of Months | 627.49 | 89.15 | 432.45 | 51.93 | 259.85 | 0.00 | 0.00 |
Maximum of Months | 1665.23 | 641.86 | 1489.03 | 1229.18 | 453.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4234.25 | 1875.23 | 3845.01 | 2990.13 | 854.88 | 0.00 | 0.00 |
February | 4254.31 | 1734.82 | 3790.08 | 2773.82 | 1016.26 | 0.00 | 0.00 |
March | 3228.61 | 1393.23 | 2818.28 | 1719.73 | 1098.54 | 0.00 | 0.00 |
April | 2572.28 | 966.54 | 2164.44 | 887.02 | 1277.42 | 0.00 | 0.00 |
May | 1759.13 | 687.14 | 1456.68 | 329.54 | 1127.14 | 0.00 | 0.00 |
June | 1739.70 | 432.95 | 1217.75 | 146.22 | 1071.52 | 0.00 | 0.00 |
July | 2100.28 | 261.14 | 1347.97 | 211.51 | 1136.46 | 0.00 | 0.00 |
August | 2718.99 | 317.72 | 1833.69 | 578.34 | 1255.35 | 0.00 | 0.00 |
September | 3573.81 | 584.53 | 2603.16 | 1465.35 | 1137.81 | 0.00 | 0.00 |
October | 4324.34 | 1033.06 | 3507.10 | 2579.76 | 927.34 | 0.00 | 0.00 |
November | 4491.41 | 1505.85 | 3956.12 | 3044.70 | 911.42 | 0.00 | 0.00 |
December | 4647.40 | 1926.43 | 4193.02 | 3461.29 | 731.73 | 0.00 | 0.00 |
Annual Sum or Average | 3298.19 | 1056.39 | 2721.70 | 1676.56 | 1045.14 | 0.00 | 0.00 |
Minimum of Months | 1739.70 | 261.14 | 1217.75 | 146.22 | 731.73 | 0.00 | 0.00 |
Maximum of Months | 4647.40 | 1926.43 | 4193.02 | 3461.29 | 1277.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5592.12 | 2499.67 | 4994.88 | 3884.35 | 1110.53 | 0.00 | 0.00 |
February | 5627.55 | 2307.41 | 4923.53 | 3603.35 | 1320.18 | 0.00 | 0.00 |
March | 4274.30 | 1853.69 | 3661.10 | 2234.03 | 1427.07 | 0.00 | 0.00 |
April | 3423.01 | 1279.26 | 2811.73 | 1152.28 | 1659.44 | 0.00 | 0.00 |
May | 2344.15 | 912.68 | 1892.31 | 428.09 | 1464.22 | 0.00 | 0.00 |
June | 2324.59 | 571.95 | 1581.92 | 189.95 | 1391.97 | 0.00 | 0.00 |
July | 2808.89 | 337.03 | 1751.09 | 274.76 | 1476.33 | 0.00 | 0.00 |
August | 3623.48 | 406.86 | 2382.07 | 751.30 | 1630.78 | 0.00 | 0.00 |
September | 4741.48 | 754.57 | 3381.65 | 1903.57 | 1478.08 | 0.00 | 0.00 |
October | 5722.27 | 1354.62 | 4555.93 | 3351.26 | 1204.67 | 0.00 | 0.00 |
November | 5937.42 | 1990.17 | 5139.22 | 3955.24 | 1183.98 | 0.00 | 0.00 |
December | 6139.89 | 2564.08 | 5446.97 | 4496.41 | 950.56 | 0.00 | 0.00 |
Annual Sum or Average | 4372.67 | 1398.01 | 3535.64 | 2177.95 | 1357.69 | 0.00 | 0.00 |
Minimum of Months | 2324.59 | 337.03 | 1581.92 | 189.95 | 950.56 | 0.00 | 0.00 |
Maximum of Months | 6139.89 | 2564.08 | 5446.97 | 4496.41 | 1659.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 468.26 | 357.87 | 465.27 | 321.33 | 143.94 | 0.00 | 0.00 |
February | 542.09 | 328.58 | 517.02 | 339.53 | 177.48 | 0.00 | 0.00 |
March | 520.02 | 257.96 | 477.84 | 269.46 | 208.38 | 0.00 | 0.00 |
April | 591.67 | 172.31 | 510.15 | 252.91 | 257.24 | 0.00 | 0.00 |
May | 546.27 | 117.77 | 442.88 | 199.12 | 243.76 | 0.00 | 0.00 |
June | 636.88 | 67.66 | 448.43 | 212.39 | 236.04 | 0.00 | 0.00 |
July | 639.47 | 32.79 | 422.33 | 174.97 | 247.36 | 0.00 | 0.00 |
August | 671.77 | 43.92 | 463.93 | 195.41 | 268.52 | 0.00 | 0.00 |
September | 659.16 | 98.00 | 486.90 | 263.45 | 223.44 | 0.00 | 0.00 |
October | 627.18 | 190.97 | 524.56 | 354.49 | 170.07 | 0.00 | 0.00 |
November | 523.64 | 275.80 | 495.25 | 341.71 | 153.54 | 0.00 | 0.00 |
December | 481.41 | 362.18 | 481.15 | 359.64 | 121.51 | 0.00 | 0.00 |
Annual Sum or Average | 575.63 | 191.45 | 477.58 | 273.23 | 204.35 | 0.00 | 0.00 |
Minimum of Months | 468.26 | 32.79 | 422.33 | 174.97 | 121.51 | 0.00 | 0.00 |
Maximum of Months | 671.77 | 362.18 | 524.56 | 359.64 | 268.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.39 | 376.29 | 231.88 | 111.38 | 120.50 | 0.00 | 0.00 |
February | 267.01 | 338.35 | 296.62 | 144.77 | 151.85 | 0.00 | 0.00 |
March | 333.54 | 260.49 | 337.64 | 148.72 | 188.93 | 0.00 | 0.00 |
April | 471.36 | 168.16 | 431.75 | 191.61 | 240.14 | 0.00 | 0.00 |
May | 503.61 | 114.13 | 420.24 | 181.16 | 239.08 | 0.00 | 0.00 |
June | 636.66 | 63.53 | 453.60 | 217.20 | 236.39 | 0.00 | 0.00 |
July | 615.60 | 31.71 | 410.82 | 167.20 | 243.61 | 0.00 | 0.00 |
August | 586.03 | 41.86 | 412.34 | 156.69 | 255.65 | 0.00 | 0.00 |
September | 480.82 | 95.43 | 365.71 | 160.61 | 205.10 | 0.00 | 0.00 |
October | 361.77 | 194.08 | 324.23 | 173.36 | 150.88 | 0.00 | 0.00 |
November | 227.62 | 286.77 | 256.47 | 127.93 | 128.54 | 0.00 | 0.00 |
December | 170.25 | 383.19 | 217.88 | 116.61 | 101.27 | 0.00 | 0.00 |
Annual Sum or Average | 404.29 | 195.47 | 346.68 | 158.04 | 188.64 | 0.00 | 0.00 |
Minimum of Months | 170.25 | 31.71 | 217.88 | 111.38 | 101.27 | 0.00 | 0.00 |
Maximum of Months | 636.66 | 383.19 | 453.60 | 217.20 | 255.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 240.19 | 106.70 | 215.94 | 167.92 | 48.01 | 0.00 | 0.00 |
February | 241.24 | 99.14 | 212.85 | 155.78 | 57.07 | 0.00 | 0.00 |
March | 183.04 | 78.84 | 158.27 | 96.58 | 61.69 | 0.00 | 0.00 |
April | 147.13 | 53.18 | 121.56 | 49.81 | 71.74 | 0.00 | 0.00 |
May | 102.05 | 36.78 | 81.81 | 18.51 | 63.30 | 0.00 | 0.00 |
June | 103.76 | 22.10 | 68.39 | 8.21 | 60.18 | 0.00 | 0.00 |
July | 125.04 | 12.01 | 75.70 | 11.88 | 63.82 | 0.00 | 0.00 |
August | 158.99 | 15.06 | 102.98 | 32.48 | 70.50 | 0.00 | 0.00 |
September | 205.58 | 30.35 | 146.19 | 82.29 | 63.90 | 0.00 | 0.00 |
October | 246.95 | 56.99 | 196.96 | 144.88 | 52.08 | 0.00 | 0.00 |
November | 255.26 | 85.14 | 222.18 | 170.99 | 51.19 | 0.00 | 0.00 |
December | 263.81 | 109.96 | 235.48 | 194.39 | 41.09 | 0.00 | 0.00 |
Annual Sum or Average | 189.12 | 58.65 | 152.85 | 94.16 | 58.70 | 0.00 | 0.00 |
Minimum of Months | 102.05 | 12.01 | 68.39 | 8.21 | 41.09 | 0.00 | 0.00 |
Maximum of Months | 263.81 | 109.96 | 235.48 | 194.39 | 71.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.80 | 110.33 | 29.27 | 0.00 | 29.27 | 0.00 | 0.00 |
February | 14.43 | 98.06 | 36.58 | 0.00 | 36.58 | 0.00 | 0.00 |
March | 31.47 | 73.48 | 46.15 | 0.00 | 46.15 | 0.00 | 0.00 |
April | 52.83 | 44.46 | 58.87 | 0.79 | 58.08 | 0.00 | 0.00 |
May | 72.57 | 29.24 | 63.72 | 4.14 | 59.58 | 0.00 | 0.00 |
June | 111.17 | 15.91 | 72.54 | 12.06 | 60.48 | 0.00 | 0.00 |
July | 111.71 | 7.26 | 66.52 | 5.67 | 60.85 | 0.00 | 0.00 |
August | 94.97 | 9.63 | 61.73 | 1.51 | 60.22 | 0.00 | 0.00 |
September | 64.84 | 23.83 | 49.28 | 0.04 | 49.25 | 0.00 | 0.00 |
October | 30.86 | 52.40 | 36.74 | 0.00 | 36.74 | 0.00 | 0.00 |
November | 10.88 | 82.96 | 31.20 | 0.00 | 31.20 | 0.00 | 0.00 |
December | 2.18 | 114.42 | 24.91 | 0.00 | 24.91 | 0.00 | 0.00 |
Annual Sum or Average | 50.58 | 54.96 | 48.17 | 2.02 | 46.15 | 0.00 | 0.00 |
Minimum of Months | 2.18 | 7.26 | 24.91 | 0.00 | 24.91 | 0.00 | 0.00 |
Maximum of Months | 111.71 | 114.42 | 72.54 | 12.06 | 60.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 451.67 | 350.70 | 459.35 | 315.94 | 143.40 | 0.00 | 0.00 |
February | 506.97 | 319.74 | 495.45 | 318.04 | 177.41 | 0.00 | 0.00 |
March | 543.58 | 246.68 | 502.64 | 294.37 | 208.27 | 0.00 | 0.00 |
April | 660.01 | 160.92 | 565.39 | 297.54 | 267.85 | 0.00 | 0.00 |
May | 612.76 | 112.21 | 497.24 | 248.10 | 249.13 | 0.00 | 0.00 |
June | 709.29 | 62.18 | 511.44 | 272.63 | 238.81 | 0.00 | 0.00 |
July | 720.87 | 31.94 | 488.58 | 240.04 | 248.53 | 0.00 | 0.00 |
August | 735.26 | 41.46 | 518.64 | 255.51 | 263.13 | 0.00 | 0.00 |
September | 678.29 | 92.69 | 507.90 | 284.81 | 223.09 | 0.00 | 0.00 |
October | 628.79 | 182.13 | 529.51 | 361.01 | 168.50 | 0.00 | 0.00 |
November | 522.22 | 271.46 | 498.08 | 343.02 | 155.06 | 0.00 | 0.00 |
December | 467.90 | 358.01 | 473.86 | 352.49 | 121.37 | 0.00 | 0.00 |
Annual Sum or Average | 603.49 | 185.17 | 503.89 | 298.45 | 205.44 | 0.00 | 0.00 |
Minimum of Months | 451.67 | 31.94 | 459.35 | 240.04 | 121.37 | 0.00 | 0.00 |
Maximum of Months | 735.26 | 358.01 | 565.39 | 361.01 | 267.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.23 | 353.41 | 225.95 | 105.99 | 119.96 | 0.00 | 0.00 |
February | 222.87 | 319.41 | 275.05 | 123.28 | 151.78 | 0.00 | 0.00 |
March | 349.57 | 243.53 | 362.44 | 173.62 | 188.82 | 0.00 | 0.00 |
April | 539.02 | 158.13 | 486.99 | 236.24 | 250.75 | 0.00 | 0.00 |
May | 571.21 | 110.12 | 474.59 | 230.14 | 244.45 | 0.00 | 0.00 |
June | 712.91 | 62.03 | 516.60 | 277.44 | 239.17 | 0.00 | 0.00 |
July | 697.78 | 31.68 | 477.07 | 232.28 | 244.79 | 0.00 | 0.00 |
August | 650.52 | 40.62 | 467.05 | 216.79 | 250.26 | 0.00 | 0.00 |
September | 499.20 | 89.83 | 386.71 | 181.96 | 204.75 | 0.00 | 0.00 |
October | 354.75 | 178.41 | 329.17 | 179.87 | 149.30 | 0.00 | 0.00 |
November | 217.38 | 272.53 | 259.30 | 129.24 | 130.06 | 0.00 | 0.00 |
December | 145.47 | 366.38 | 210.58 | 109.46 | 101.13 | 0.00 | 0.00 |
Annual Sum or Average | 427.62 | 184.84 | 372.99 | 183.26 | 189.73 | 0.00 | 0.00 |
Minimum of Months | 145.47 | 31.68 | 210.58 | 105.99 | 101.13 | 0.00 | 0.00 |
Maximum of Months | 712.91 | 366.38 | 516.60 | 277.44 | 250.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 519.98 | 450.17 | 531.28 | 363.85 | 167.43 | 0.00 | 0.00 |
February | 547.60 | 414.25 | 540.44 | 337.53 | 202.91 | 0.00 | 0.00 |
March | 463.20 | 332.05 | 442.92 | 209.26 | 233.65 | 0.00 | 0.00 |
April | 428.74 | 223.11 | 390.90 | 109.64 | 281.26 | 0.00 | 0.00 |
May | 367.08 | 154.59 | 315.28 | 49.07 | 266.22 | 0.00 | 0.00 |
June | 446.38 | 93.06 | 305.33 | 43.93 | 261.40 | 0.00 | 0.00 |
July | 494.00 | 55.29 | 308.13 | 38.02 | 270.11 | 0.00 | 0.00 |
August | 532.46 | 68.13 | 356.87 | 73.65 | 283.22 | 0.00 | 0.00 |
September | 573.78 | 136.81 | 423.52 | 178.38 | 245.14 | 0.00 | 0.00 |
October | 588.99 | 249.78 | 506.34 | 313.91 | 192.43 | 0.00 | 0.00 |
November | 563.61 | 355.09 | 548.98 | 370.49 | 178.49 | 0.00 | 0.00 |
December | 554.54 | 453.90 | 564.19 | 421.18 | 143.01 | 0.00 | 0.00 |
Annual Sum or Average | 506.40 | 248.01 | 435.53 | 208.39 | 227.15 | 0.00 | 0.00 |
Minimum of Months | 367.08 | 55.29 | 305.33 | 38.02 | 143.01 | 0.00 | 0.00 |
Maximum of Months | 588.99 | 453.90 | 564.19 | 421.18 | 283.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 466.30 | 356.11 | 465.27 | 321.33 | 143.94 | 0.00 | 0.00 |
February | 538.64 | 327.66 | 517.02 | 339.53 | 177.48 | 0.00 | 0.00 |
March | 515.86 | 257.29 | 477.84 | 269.46 | 208.38 | 0.00 | 0.00 |
April | 585.99 | 172.38 | 510.15 | 252.91 | 257.24 | 0.00 | 0.00 |
May | 541.86 | 116.79 | 442.88 | 199.12 | 243.76 | 0.00 | 0.00 |
June | 633.69 | 66.34 | 448.43 | 212.39 | 236.04 | 0.00 | 0.00 |
July | 636.35 | 31.25 | 422.33 | 174.97 | 247.36 | 0.00 | 0.00 |
August | 668.07 | 42.67 | 463.93 | 195.41 | 268.52 | 0.00 | 0.00 |
September | 655.50 | 96.40 | 486.90 | 263.45 | 223.44 | 0.00 | 0.00 |
October | 623.97 | 190.50 | 524.56 | 354.49 | 170.07 | 0.00 | 0.00 |
November | 521.64 | 273.01 | 495.25 | 341.71 | 153.54 | 0.00 | 0.00 |
December | 479.74 | 359.92 | 481.15 | 359.64 | 121.51 | 0.00 | 0.00 |
Annual Sum or Average | 572.28 | 190.16 | 477.58 | 273.23 | 204.35 | 0.00 | 0.00 |
Minimum of Months | 466.30 | 31.25 | 422.33 | 174.97 | 121.51 | 0.00 | 0.00 |
Maximum of Months | 668.07 | 359.92 | 524.56 | 359.64 | 268.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.48 | 373.55 | 231.88 | 111.38 | 120.50 | 0.00 | 0.00 |
February | 265.80 | 336.62 | 296.62 | 144.77 | 151.85 | 0.00 | 0.00 |
March | 331.32 | 258.93 | 337.64 | 148.72 | 188.93 | 0.00 | 0.00 |
April | 466.92 | 167.88 | 431.75 | 191.61 | 240.14 | 0.00 | 0.00 |
May | 499.70 | 113.22 | 420.24 | 181.16 | 239.08 | 0.00 | 0.00 |
June | 633.62 | 62.50 | 453.60 | 217.20 | 236.39 | 0.00 | 0.00 |
July | 612.86 | 30.30 | 410.82 | 167.20 | 243.61 | 0.00 | 0.00 |
August | 583.17 | 40.69 | 412.34 | 156.69 | 255.65 | 0.00 | 0.00 |
September | 478.48 | 93.50 | 365.71 | 160.61 | 205.10 | 0.00 | 0.00 |
October | 360.38 | 191.82 | 324.23 | 173.36 | 150.88 | 0.00 | 0.00 |
November | 227.77 | 282.38 | 256.47 | 127.93 | 128.54 | 0.00 | 0.00 |
December | 170.49 | 380.00 | 217.88 | 116.61 | 101.27 | 0.00 | 0.00 |
Annual Sum or Average | 402.32 | 193.58 | 346.68 | 158.04 | 188.64 | 0.00 | 0.00 |
Minimum of Months | 170.49 | 30.30 | 217.88 | 111.38 | 101.27 | 0.00 | 0.00 |
Maximum of Months | 633.62 | 380.00 | 453.60 | 217.20 | 255.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 438.54 | 185.11 | 395.94 | 307.91 | 88.03 | 0.00 | 0.00 |
February | 440.60 | 169.86 | 390.28 | 285.63 | 104.65 | 0.00 | 0.00 |
March | 334.91 | 133.31 | 290.21 | 177.09 | 113.12 | 0.00 | 0.00 |
April | 270.24 | 87.70 | 222.88 | 91.34 | 131.54 | 0.00 | 0.00 |
May | 189.83 | 58.05 | 150.00 | 33.93 | 116.07 | 0.00 | 0.00 |
June | 194.92 | 31.68 | 125.40 | 15.06 | 110.34 | 0.00 | 0.00 |
July | 233.28 | 14.62 | 138.81 | 21.78 | 117.03 | 0.00 | 0.00 |
August | 293.34 | 20.27 | 188.83 | 59.55 | 129.27 | 0.00 | 0.00 |
September | 376.08 | 48.41 | 268.06 | 150.89 | 117.17 | 0.00 | 0.00 |
October | 450.67 | 97.45 | 361.15 | 265.65 | 95.49 | 0.00 | 0.00 |
November | 467.20 | 142.68 | 407.38 | 313.53 | 93.85 | 0.00 | 0.00 |
December | 481.95 | 188.95 | 431.78 | 356.43 | 75.35 | 0.00 | 0.00 |
Annual Sum or Average | 347.09 | 97.81 | 280.27 | 172.64 | 107.62 | 0.00 | 0.00 |
Minimum of Months | 189.83 | 14.62 | 125.40 | 15.06 | 75.35 | 0.00 | 0.00 |
Maximum of Months | 481.95 | 188.95 | 431.78 | 356.43 | 131.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.77 | 1133.32 | 256.06 | 0.00 | 256.06 | 0.00 | 0.00 |
February | 78.74 | 1014.83 | 320.04 | 0.00 | 320.04 | 0.00 | 0.00 |
March | 210.02 | 772.63 | 403.77 | 0.01 | 403.75 | 0.00 | 0.00 |
April | 383.48 | 479.63 | 514.99 | 6.90 | 508.09 | 0.00 | 0.00 |
May | 549.68 | 327.44 | 557.42 | 36.22 | 521.20 | 0.00 | 0.00 |
June | 888.22 | 198.36 | 634.64 | 105.54 | 529.10 | 0.00 | 0.00 |
July | 895.89 | 119.69 | 581.96 | 49.60 | 532.35 | 0.00 | 0.00 |
August | 750.81 | 144.26 | 540.08 | 13.22 | 526.86 | 0.00 | 0.00 |
September | 499.67 | 285.42 | 431.15 | 0.31 | 430.84 | 0.00 | 0.00 |
October | 212.29 | 571.68 | 321.40 | 0.00 | 321.40 | 0.00 | 0.00 |
November | 54.93 | 878.52 | 272.95 | 0.00 | 272.95 | 0.00 | 0.00 |
December | 5.19 | 1186.33 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Annual Sum or Average | 381.27 | 590.65 | 421.40 | 17.68 | 403.72 | 0.00 | 0.00 |
Minimum of Months | 5.19 | 119.69 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Maximum of Months | 895.89 | 1186.33 | 634.64 | 105.54 | 532.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.48 | 1158.23 | 256.06 | 0.00 | 256.06 | 0.00 | 0.00 |
February | 72.23 | 1035.66 | 320.04 | 0.00 | 320.04 | 0.00 | 0.00 |
March | 201.40 | 787.44 | 403.77 | 0.01 | 403.75 | 0.00 | 0.00 |
April | 374.94 | 489.42 | 514.99 | 6.90 | 508.09 | 0.00 | 0.00 |
May | 541.01 | 334.67 | 557.42 | 36.22 | 521.20 | 0.00 | 0.00 |
June | 880.08 | 203.60 | 634.64 | 105.54 | 529.10 | 0.00 | 0.00 |
July | 888.16 | 124.41 | 581.96 | 49.60 | 532.35 | 0.00 | 0.00 |
August | 743.41 | 149.48 | 540.08 | 13.22 | 526.86 | 0.00 | 0.00 |
September | 493.51 | 292.65 | 431.15 | 0.31 | 430.84 | 0.00 | 0.00 |
October | 206.33 | 583.67 | 321.40 | 0.00 | 321.40 | 0.00 | 0.00 |
November | 49.55 | 897.95 | 272.95 | 0.00 | 272.95 | 0.00 | 0.00 |
December | 3.99 | 1215.02 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Annual Sum or Average | 374.73 | 603.97 | 421.40 | 17.68 | 403.72 | 0.00 | 0.00 |
Minimum of Months | 3.99 | 124.41 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Maximum of Months | 888.16 | 1215.02 | 634.64 | 105.54 | 532.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 618.66 | 768.56 | 685.27 | 421.92 | 263.35 | 0.00 | 0.00 |
February | 745.90 | 707.15 | 770.46 | 441.29 | 329.17 | 0.00 | 0.00 |
March | 930.38 | 552.01 | 865.04 | 467.96 | 397.07 | 0.00 | 0.00 |
April | 1270.18 | 364.92 | 1052.32 | 533.75 | 518.57 | 0.00 | 0.00 |
May | 1268.18 | 265.84 | 971.77 | 478.21 | 493.56 | 0.00 | 0.00 |
June | 1535.58 | 168.11 | 1027.99 | 550.03 | 477.96 | 0.00 | 0.00 |
July | 1541.00 | 105.48 | 965.59 | 472.29 | 493.30 | 0.00 | 0.00 |
August | 1508.19 | 123.97 | 985.63 | 472.27 | 513.37 | 0.00 | 0.00 |
September | 1278.34 | 214.03 | 894.57 | 466.75 | 427.82 | 0.00 | 0.00 |
October | 1049.12 | 398.16 | 858.64 | 540.86 | 317.78 | 0.00 | 0.00 |
November | 760.37 | 596.41 | 757.34 | 472.24 | 285.11 | 0.00 | 0.00 |
December | 613.92 | 783.47 | 684.41 | 461.93 | 222.48 | 0.00 | 0.00 |
Annual Sum or Average | 1094.88 | 419.25 | 876.84 | 481.69 | 395.15 | 0.00 | 0.00 |
Minimum of Months | 613.92 | 105.48 | 684.41 | 421.92 | 222.48 | 0.00 | 0.00 |
Maximum of Months | 1541.00 | 783.47 | 1052.32 | 550.03 | 518.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1110.07 | 796.92 | 1095.67 | 783.80 | 311.87 | 0.00 | 0.00 |
February | 1147.58 | 735.65 | 1103.20 | 727.10 | 376.10 | 0.00 | 0.00 |
March | 934.69 | 587.34 | 877.17 | 450.80 | 426.37 | 0.00 | 0.00 |
April | 823.40 | 395.97 | 743.90 | 234.88 | 509.03 | 0.00 | 0.00 |
May | 659.44 | 277.66 | 572.93 | 98.80 | 474.13 | 0.00 | 0.00 |
June | 769.30 | 169.98 | 536.77 | 74.51 | 462.26 | 0.00 | 0.00 |
July | 870.77 | 103.86 | 552.84 | 72.45 | 480.40 | 0.00 | 0.00 |
August | 981.73 | 126.90 | 665.81 | 156.13 | 509.68 | 0.00 | 0.00 |
September | 1120.77 | 244.26 | 830.16 | 384.22 | 445.95 | 0.00 | 0.00 |
October | 1216.08 | 435.08 | 1029.49 | 676.23 | 353.26 | 0.00 | 0.00 |
November | 1198.38 | 622.86 | 1130.58 | 798.10 | 332.48 | 0.00 | 0.00 |
December | 1198.12 | 806.51 | 1173.83 | 907.30 | 266.52 | 0.00 | 0.00 |
Annual Sum or Average | 1001.60 | 440.42 | 857.89 | 445.54 | 412.36 | 0.00 | 0.00 |
Minimum of Months | 659.44 | 103.86 | 536.77 | 72.45 | 266.52 | 0.00 | 0.00 |
Maximum of Months | 1216.08 | 806.51 | 1173.83 | 907.30 | 509.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.407130E+10 | 0.167545E+10 | 0.365721E+10 | 0.284409E+10 | 0.813124E+09 | 0.00 | 0.00 |
February | 0.369447E+10 | 0.139562E+10 | 0.325610E+10 | 0.238302E+10 | 0.873079E+09 | 0.00 | 0.00 |
March | 0.311699E+10 | 0.122436E+10 | 0.268063E+10 | 0.163574E+10 | 0.104489E+10 | 0.00 | 0.00 |
April | 0.240748E+10 | 0.821614E+09 | 0.199231E+10 | 0.816477E+09 | 0.117584E+10 | 0.00 | 0.00 |
May | 0.171306E+10 | 0.597954E+09 | 0.138554E+10 | 0.313445E+09 | 0.107209E+10 | 0.00 | 0.00 |
June | 0.162645E+10 | 0.372776E+09 | 0.112091E+10 | 0.134596E+09 | 0.986310E+09 | 0.00 | 0.00 |
July | 0.201619E+10 | 0.238767E+09 | 0.128213E+10 | 0.201175E+09 | 0.108095E+10 | 0.00 | 0.00 |
August | 0.260542E+10 | 0.291701E+09 | 0.174413E+10 | 0.550093E+09 | 0.119404E+10 | 0.00 | 0.00 |
September | 0.331352E+10 | 0.514931E+09 | 0.239615E+10 | 0.134882E+10 | 0.104733E+10 | 0.00 | 0.00 |
October | 0.414548E+10 | 0.928596E+09 | 0.333581E+10 | 0.245376E+10 | 0.882050E+09 | 0.00 | 0.00 |
November | 0.417500E+10 | 0.129159E+10 | 0.364151E+10 | 0.280257E+10 | 0.838938E+09 | 0.00 | 0.00 |
December | 0.446014E+10 | 0.171917E+10 | 0.398823E+10 | 0.329223E+10 | 0.695993E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373455E+11 | 0.110725E+11 | 0.304806E+11 | 0.187760E+11 | 0.117046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.162645E+10 | 0.238767E+09 | 0.112091E+10 | 0.134596E+09 | 0.695993E+09 | 0.00 | 0.00 |
Maximum of Months | 0.446014E+10 | 0.171917E+10 | 0.398823E+10 | 0.329223E+10 | 0.119404E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113410E+11 | 0.502261E+10 | 0.102985E+11 | 0.800876E+10 | 0.228970E+10 | 0.00 | 0.00 |
February | 0.102920E+11 | 0.419688E+10 | 0.916896E+10 | 0.671042E+10 | 0.245853E+10 | 0.00 | 0.00 |
March | 0.864751E+10 | 0.373163E+10 | 0.754847E+10 | 0.460613E+10 | 0.294234E+10 | 0.00 | 0.00 |
April | 0.666735E+10 | 0.250528E+10 | 0.561022E+10 | 0.229915E+10 | 0.331108E+10 | 0.00 | 0.00 |
May | 0.471166E+10 | 0.184044E+10 | 0.390158E+10 | 0.882641E+09 | 0.301894E+10 | 0.00 | 0.00 |
June | 0.450930E+10 | 0.112221E+10 | 0.315640E+10 | 0.379014E+09 | 0.277738E+10 | 0.00 | 0.00 |
July | 0.562538E+10 | 0.699428E+09 | 0.361039E+10 | 0.566496E+09 | 0.304390E+10 | 0.00 | 0.00 |
August | 0.728255E+10 | 0.850975E+09 | 0.491137E+10 | 0.154903E+10 | 0.336234E+10 | 0.00 | 0.00 |
September | 0.926332E+10 | 0.151510E+10 | 0.674739E+10 | 0.379819E+10 | 0.294920E+10 | 0.00 | 0.00 |
October | 0.115823E+11 | 0.276696E+10 | 0.939343E+10 | 0.690963E+10 | 0.248379E+10 | 0.00 | 0.00 |
November | 0.116417E+11 | 0.390316E+10 | 0.102543E+11 | 0.789186E+10 | 0.236239E+10 | 0.00 | 0.00 |
December | 0.124476E+11 | 0.515976E+10 | 0.112306E+11 | 0.927071E+10 | 0.195987E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104012E+12 | 0.333144E+11 | 0.858315E+11 | 0.528720E+11 | 0.329595E+11 | 0.00 | 0.00 |
Minimum of Months | 0.450930E+10 | 0.699428E+09 | 0.315640E+10 | 0.379014E+09 | 0.195987E+10 | 0.00 | 0.00 |
Maximum of Months | 0.124476E+11 | 0.515976E+10 | 0.112306E+11 | 0.927071E+10 | 0.336234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149779E+11 | 0.669512E+10 | 0.133783E+11 | 0.104038E+11 | 0.297446E+10 | 0.00 | 0.00 |
February | 0.136142E+11 | 0.558209E+10 | 0.119110E+11 | 0.871722E+10 | 0.319378E+10 | 0.00 | 0.00 |
March | 0.114483E+11 | 0.496491E+10 | 0.980589E+10 | 0.598362E+10 | 0.382227E+10 | 0.00 | 0.00 |
April | 0.887245E+10 | 0.331583E+10 | 0.728800E+10 | 0.298672E+10 | 0.430128E+10 | 0.00 | 0.00 |
May | 0.627858E+10 | 0.244453E+10 | 0.506838E+10 | 0.114660E+10 | 0.392177E+10 | 0.00 | 0.00 |
June | 0.602534E+10 | 0.148249E+10 | 0.410034E+10 | 0.492361E+09 | 0.360798E+10 | 0.00 | 0.00 |
July | 0.752334E+10 | 0.902690E+09 | 0.469011E+10 | 0.735911E+09 | 0.395420E+10 | 0.00 | 0.00 |
August | 0.970512E+10 | 0.108974E+10 | 0.638014E+10 | 0.201227E+10 | 0.436787E+10 | 0.00 | 0.00 |
September | 0.122899E+11 | 0.195585E+10 | 0.876524E+10 | 0.493407E+10 | 0.383118E+10 | 0.00 | 0.00 |
October | 0.153265E+11 | 0.362823E+10 | 0.122026E+11 | 0.897601E+10 | 0.322659E+10 | 0.00 | 0.00 |
November | 0.153898E+11 | 0.515853E+10 | 0.133209E+11 | 0.102520E+11 | 0.306888E+10 | 0.00 | 0.00 |
December | 0.164451E+11 | 0.686764E+10 | 0.145892E+11 | 0.120432E+11 | 0.254598E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.137897E+12 | 0.440876E+11 | 0.111500E+12 | 0.686838E+11 | 0.428162E+11 | 0.00 | 0.00 |
Minimum of Months | 0.602534E+10 | 0.902690E+09 | 0.410034E+10 | 0.492361E+09 | 0.254598E+10 | 0.00 | 0.00 |
Maximum of Months | 0.164451E+11 | 0.686764E+10 | 0.145892E+11 | 0.120432E+11 | 0.436787E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125419E+10 | 0.958529E+09 | 0.124618E+10 | 0.860644E+09 | 0.385540E+09 | 0.00 | 0.00 |
February | 0.131142E+10 | 0.794905E+09 | 0.125077E+10 | 0.821399E+09 | 0.429371E+09 | 0.00 | 0.00 |
March | 0.139282E+10 | 0.690921E+09 | 0.127985E+10 | 0.721728E+09 | 0.558127E+09 | 0.00 | 0.00 |
April | 0.153362E+10 | 0.446627E+09 | 0.132231E+10 | 0.655531E+09 | 0.666775E+09 | 0.00 | 0.00 |
May | 0.146312E+10 | 0.315437E+09 | 0.118622E+10 | 0.533331E+09 | 0.652887E+09 | 0.00 | 0.00 |
June | 0.165079E+10 | 0.175384E+09 | 0.116234E+10 | 0.550518E+09 | 0.611824E+09 | 0.00 | 0.00 |
July | 0.171276E+10 | 87828887.24 | 0.113116E+10 | 0.468634E+09 | 0.662522E+09 | 0.00 | 0.00 |
August | 0.179927E+10 | 0.117625E+09 | 0.124260E+10 | 0.523397E+09 | 0.719205E+09 | 0.00 | 0.00 |
September | 0.170855E+10 | 0.254023E+09 | 0.126203E+10 | 0.682873E+09 | 0.579160E+09 | 0.00 | 0.00 |
October | 0.167984E+10 | 0.511489E+09 | 0.140499E+10 | 0.949466E+09 | 0.455520E+09 | 0.00 | 0.00 |
November | 0.135728E+10 | 0.714862E+09 | 0.128369E+10 | 0.885716E+09 | 0.397972E+09 | 0.00 | 0.00 |
December | 0.128942E+10 | 0.970062E+09 | 0.128872E+10 | 0.963268E+09 | 0.325450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181531E+11 | 0.603769E+10 | 0.150609E+11 | 0.861650E+10 | 0.644435E+10 | 0.00 | 0.00 |
Minimum of Months | 0.125419E+10 | 87828887.24 | 0.113116E+10 | 0.468634E+09 | 0.325450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.179927E+10 | 0.970062E+09 | 0.140499E+10 | 0.963268E+09 | 0.719205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.509946E+09 | 0.100786E+10 | 0.621070E+09 | 0.298319E+09 | 0.322751E+09 | 0.00 | 0.00 |
February | 0.645955E+09 | 0.818538E+09 | 0.717592E+09 | 0.350236E+09 | 0.367356E+09 | 0.00 | 0.00 |
March | 0.893366E+09 | 0.697706E+09 | 0.904345E+09 | 0.398320E+09 | 0.506025E+09 | 0.00 | 0.00 |
April | 0.122175E+10 | 0.435871E+09 | 0.111909E+10 | 0.496654E+09 | 0.622434E+09 | 0.00 | 0.00 |
May | 0.134886E+10 | 0.305675E+09 | 0.112556E+10 | 0.485216E+09 | 0.640348E+09 | 0.00 | 0.00 |
June | 0.165022E+10 | 0.164675E+09 | 0.117572E+10 | 0.562988E+09 | 0.612736E+09 | 0.00 | 0.00 |
July | 0.164882E+10 | 84930811.55 | 0.110034E+10 | 0.447839E+09 | 0.652497E+09 | 0.00 | 0.00 |
August | 0.156961E+10 | 0.112105E+09 | 0.110441E+10 | 0.419691E+09 | 0.684721E+09 | 0.00 | 0.00 |
September | 0.124628E+10 | 0.247357E+09 | 0.947924E+09 | 0.416301E+09 | 0.531623E+09 | 0.00 | 0.00 |
October | 0.968962E+09 | 0.519825E+09 | 0.868419E+09 | 0.464315E+09 | 0.404104E+09 | 0.00 | 0.00 |
November | 0.589997E+09 | 0.743300E+09 | 0.664771E+09 | 0.331600E+09 | 0.333171E+09 | 0.00 | 0.00 |
December | 0.456006E+09 | 0.102634E+10 | 0.583573E+09 | 0.312337E+09 | 0.271236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127498E+11 | 0.616419E+10 | 0.109328E+11 | 0.498382E+10 | 0.594900E+10 | 0.00 | 0.00 |
Minimum of Months | 0.456006E+09 | 84930811.55 | 0.583573E+09 | 0.298319E+09 | 0.271236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165022E+10 | 0.102634E+10 | 0.117572E+10 | 0.562988E+09 | 0.684721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.643324E+09 | 0.285782E+09 | 0.578361E+09 | 0.449770E+09 | 0.128590E+09 | 0.00 | 0.00 |
February | 0.583609E+09 | 0.239849E+09 | 0.514928E+09 | 0.376856E+09 | 0.138072E+09 | 0.00 | 0.00 |
March | 0.490248E+09 | 0.211164E+09 | 0.423922E+09 | 0.258679E+09 | 0.165243E+09 | 0.00 | 0.00 |
April | 0.381358E+09 | 0.137847E+09 | 0.315071E+09 | 0.129120E+09 | 0.185952E+09 | 0.00 | 0.00 |
May | 0.273332E+09 | 98500879.21 | 0.219114E+09 | 49568964.22 | 0.169545E+09 | 0.00 | 0.00 |
June | 0.268950E+09 | 57288916.70 | 0.177265E+09 | 21285372.45 | 0.155980E+09 | 0.00 | 0.00 |
July | 0.334919E+09 | 32163284.31 | 0.202761E+09 | 31814303.90 | 0.170947E+09 | 0.00 | 0.00 |
August | 0.425845E+09 | 40323875.31 | 0.275824E+09 | 86993003.94 | 0.188831E+09 | 0.00 | 0.00 |
September | 0.532859E+09 | 78668215.86 | 0.378934E+09 | 0.213306E+09 | 0.165628E+09 | 0.00 | 0.00 |
October | 0.661418E+09 | 0.152638E+09 | 0.527535E+09 | 0.388044E+09 | 0.139491E+09 | 0.00 | 0.00 |
November | 0.661640E+09 | 0.220684E+09 | 0.575878E+09 | 0.443205E+09 | 0.132673E+09 | 0.00 | 0.00 |
December | 0.706584E+09 | 0.294528E+09 | 0.630708E+09 | 0.520641E+09 | 0.110067E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.596409E+10 | 0.184944E+10 | 0.482030E+10 | 0.296928E+10 | 0.185102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.268950E+09 | 32163284.31 | 0.177265E+09 | 21285372.45 | 0.110067E+09 | 0.00 | 0.00 |
Maximum of Months | 0.706584E+09 | 0.294528E+09 | 0.630708E+09 | 0.520641E+09 | 0.188831E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18217267.24 | 0.295519E+09 | 78395194.18 | 0.00 | 78395194.18 | 0.00 | 0.00 |
February | 34912514.49 | 0.237228E+09 | 88498821.31 | 0.00 | 88498821.31 | 0.00 | 0.00 |
March | 84280125.49 | 0.196806E+09 | 0.123615E+09 | 4297.01 | 0.123611E+09 | 0.00 | 0.00 |
April | 0.136942E+09 | 0.115247E+09 | 0.152580E+09 | 2043871.97 | 0.150536E+09 | 0.00 | 0.00 |
May | 0.194378E+09 | 78307020.56 | 0.170657E+09 | 11088084.06 | 0.159568E+09 | 0.00 | 0.00 |
June | 0.288161E+09 | 41237931.25 | 0.188031E+09 | 31269876.03 | 0.156761E+09 | 0.00 | 0.00 |
July | 0.299191E+09 | 19453814.81 | 0.178169E+09 | 15186292.66 | 0.162983E+09 | 0.00 | 0.00 |
August | 0.254362E+09 | 25804560.72 | 0.165349E+09 | 4046567.42 | 0.161302E+09 | 0.00 | 0.00 |
September | 0.168069E+09 | 61773350.74 | 0.127739E+09 | 91026.49 | 0.127648E+09 | 0.00 | 0.00 |
October | 82651627.33 | 0.140351E+09 | 98399454.57 | 0.00 | 98399454.57 | 0.00 | 0.00 |
November | 28206678.69 | 0.215044E+09 | 80868758.46 | 0.00 | 80868758.46 | 0.00 | 0.00 |
December | 5851226.62 | 0.306455E+09 | 66726175.04 | 0.00 | 66726175.04 | 0.00 | 0.00 |
Annual Sum or Average | 0.159522E+10 | 0.173323E+10 | 0.151903E+10 | 63730015.63 | 0.145530E+10 | 0.00 | 0.00 |
Minimum of Months | 5851226.62 | 19453814.81 | 66726175.04 | 0.00 | 66726175.04 | 0.00 | 0.00 |
Maximum of Months | 0.299191E+09 | 0.306455E+09 | 0.188031E+09 | 31269876.03 | 0.162983E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120974E+10 | 0.939312E+09 | 0.123031E+10 | 0.846218E+09 | 0.384093E+09 | 0.00 | 0.00 |
February | 0.122645E+10 | 0.773518E+09 | 0.119858E+10 | 0.769391E+09 | 0.429191E+09 | 0.00 | 0.00 |
March | 0.145591E+10 | 0.660719E+09 | 0.134627E+10 | 0.788435E+09 | 0.557833E+09 | 0.00 | 0.00 |
April | 0.171074E+10 | 0.417095E+09 | 0.146549E+10 | 0.771218E+09 | 0.694275E+09 | 0.00 | 0.00 |
May | 0.164123E+10 | 0.300541E+09 | 0.133180E+10 | 0.664517E+09 | 0.667283E+09 | 0.00 | 0.00 |
June | 0.183848E+10 | 0.161158E+09 | 0.132566E+10 | 0.706653E+09 | 0.619005E+09 | 0.00 | 0.00 |
July | 0.193079E+10 | 85547015.69 | 0.130860E+10 | 0.642930E+09 | 0.665670E+09 | 0.00 | 0.00 |
August | 0.196932E+10 | 0.111041E+09 | 0.138913E+10 | 0.684353E+09 | 0.704775E+09 | 0.00 | 0.00 |
September | 0.175814E+10 | 0.240248E+09 | 0.131647E+10 | 0.738223E+09 | 0.578250E+09 | 0.00 | 0.00 |
October | 0.168415E+10 | 0.487829E+09 | 0.141823E+10 | 0.966926E+09 | 0.451303E+09 | 0.00 | 0.00 |
November | 0.135360E+10 | 0.703626E+09 | 0.129101E+10 | 0.889101E+09 | 0.401914E+09 | 0.00 | 0.00 |
December | 0.125321E+10 | 0.958895E+09 | 0.126917E+10 | 0.944102E+09 | 0.325072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.190318E+11 | 0.583953E+10 | 0.158907E+11 | 0.941206E+10 | 0.647866E+10 | 0.00 | 0.00 |
Minimum of Months | 0.120974E+10 | 85547015.69 | 0.119858E+10 | 0.642930E+09 | 0.325072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196932E+10 | 0.958895E+09 | 0.146549E+10 | 0.966926E+09 | 0.704775E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.426484E+09 | 0.946576E+09 | 0.605197E+09 | 0.283893E+09 | 0.321304E+09 | 0.00 | 0.00 |
February | 0.539174E+09 | 0.772718E+09 | 0.665402E+09 | 0.298227E+09 | 0.367175E+09 | 0.00 | 0.00 |
March | 0.936294E+09 | 0.652264E+09 | 0.970759E+09 | 0.465027E+09 | 0.505732E+09 | 0.00 | 0.00 |
April | 0.139713E+10 | 0.409874E+09 | 0.126228E+10 | 0.612341E+09 | 0.649934E+09 | 0.00 | 0.00 |
May | 0.152993E+10 | 0.294949E+09 | 0.127114E+10 | 0.616401E+09 | 0.654743E+09 | 0.00 | 0.00 |
June | 0.184785E+10 | 0.160792E+09 | 0.133904E+10 | 0.719123E+09 | 0.619916E+09 | 0.00 | 0.00 |
July | 0.186892E+10 | 84850931.99 | 0.127778E+10 | 0.622134E+09 | 0.655645E+09 | 0.00 | 0.00 |
August | 0.174236E+10 | 0.108795E+09 | 0.125094E+10 | 0.580648E+09 | 0.670290E+09 | 0.00 | 0.00 |
September | 0.129393E+10 | 0.232830E+09 | 0.100236E+10 | 0.471651E+09 | 0.530713E+09 | 0.00 | 0.00 |
October | 0.950175E+09 | 0.477866E+09 | 0.881662E+09 | 0.481775E+09 | 0.399887E+09 | 0.00 | 0.00 |
November | 0.563444E+09 | 0.706394E+09 | 0.672096E+09 | 0.334984E+09 | 0.337112E+09 | 0.00 | 0.00 |
December | 0.389621E+09 | 0.981324E+09 | 0.564029E+09 | 0.293171E+09 | 0.270858E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134853E+11 | 0.582923E+10 | 0.117627E+11 | 0.577938E+10 | 0.598331E+10 | 0.00 | 0.00 |
Minimum of Months | 0.389621E+09 | 84850931.99 | 0.564029E+09 | 0.283893E+09 | 0.270858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186892E+10 | 0.981324E+09 | 0.133904E+10 | 0.719123E+09 | 0.670290E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139271E+10 | 0.120573E+10 | 0.142298E+10 | 0.974527E+09 | 0.448450E+09 | 0.00 | 0.00 |
February | 0.132476E+10 | 0.100215E+10 | 0.130742E+10 | 0.816542E+09 | 0.490882E+09 | 0.00 | 0.00 |
March | 0.124063E+10 | 0.889356E+09 | 0.118631E+10 | 0.560495E+09 | 0.625818E+09 | 0.00 | 0.00 |
April | 0.111130E+10 | 0.578303E+09 | 0.101321E+10 | 0.284194E+09 | 0.729017E+09 | 0.00 | 0.00 |
May | 0.983187E+09 | 0.414045E+09 | 0.844459E+09 | 0.131423E+09 | 0.713037E+09 | 0.00 | 0.00 |
June | 0.115701E+10 | 0.241224E+09 | 0.791422E+09 | 0.113861E+09 | 0.677561E+09 | 0.00 | 0.00 |
July | 0.132314E+10 | 0.148082E+09 | 0.825301E+09 | 0.101831E+09 | 0.723470E+09 | 0.00 | 0.00 |
August | 0.142613E+10 | 0.182484E+09 | 0.955834E+09 | 0.197256E+09 | 0.758578E+09 | 0.00 | 0.00 |
September | 0.148723E+10 | 0.354614E+09 | 0.109777E+10 | 0.462371E+09 | 0.635400E+09 | 0.00 | 0.00 |
October | 0.157755E+10 | 0.669019E+09 | 0.135619E+10 | 0.840783E+09 | 0.515404E+09 | 0.00 | 0.00 |
November | 0.146087E+10 | 0.920405E+09 | 0.142296E+10 | 0.960302E+09 | 0.462654E+09 | 0.00 | 0.00 |
December | 0.148527E+10 | 0.121572E+10 | 0.151112E+10 | 0.112808E+10 | 0.383036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159698E+11 | 0.782113E+10 | 0.137350E+11 | 0.657167E+10 | 0.716331E+10 | 0.00 | 0.00 |
Minimum of Months | 0.983187E+09 | 0.148082E+09 | 0.791422E+09 | 0.101831E+09 | 0.383036E+09 | 0.00 | 0.00 |
Maximum of Months | 0.157755E+10 | 0.121572E+10 | 0.151112E+10 | 0.112808E+10 | 0.758578E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124894E+10 | 0.953807E+09 | 0.124618E+10 | 0.860644E+09 | 0.385540E+09 | 0.00 | 0.00 |
February | 0.130307E+10 | 0.792670E+09 | 0.125077E+10 | 0.821399E+09 | 0.429371E+09 | 0.00 | 0.00 |
March | 0.138168E+10 | 0.689127E+09 | 0.127985E+10 | 0.721728E+09 | 0.558127E+09 | 0.00 | 0.00 |
April | 0.151888E+10 | 0.446819E+09 | 0.132231E+10 | 0.655531E+09 | 0.666775E+09 | 0.00 | 0.00 |
May | 0.145131E+10 | 0.312807E+09 | 0.118622E+10 | 0.533331E+09 | 0.652887E+09 | 0.00 | 0.00 |
June | 0.164252E+10 | 0.171954E+09 | 0.116234E+10 | 0.550518E+09 | 0.611824E+09 | 0.00 | 0.00 |
July | 0.170439E+10 | 83710545.85 | 0.113116E+10 | 0.468634E+09 | 0.662522E+09 | 0.00 | 0.00 |
August | 0.178937E+10 | 0.114278E+09 | 0.124260E+10 | 0.523397E+09 | 0.719205E+09 | 0.00 | 0.00 |
September | 0.169904E+10 | 0.249874E+09 | 0.126203E+10 | 0.682873E+09 | 0.579160E+09 | 0.00 | 0.00 |
October | 0.167123E+10 | 0.510225E+09 | 0.140499E+10 | 0.949466E+09 | 0.455520E+09 | 0.00 | 0.00 |
November | 0.135208E+10 | 0.707648E+09 | 0.128369E+10 | 0.885716E+09 | 0.397972E+09 | 0.00 | 0.00 |
December | 0.128493E+10 | 0.964005E+09 | 0.128872E+10 | 0.963268E+09 | 0.325450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.180475E+11 | 0.599692E+10 | 0.150609E+11 | 0.861650E+10 | 0.644435E+10 | 0.00 | 0.00 |
Minimum of Months | 0.124894E+10 | 83710545.85 | 0.113116E+10 | 0.468634E+09 | 0.325450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178937E+10 | 0.964005E+09 | 0.140499E+10 | 0.963268E+09 | 0.719205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.510174E+09 | 0.100053E+10 | 0.621070E+09 | 0.298319E+09 | 0.322751E+09 | 0.00 | 0.00 |
February | 0.643015E+09 | 0.814353E+09 | 0.717592E+09 | 0.350236E+09 | 0.367356E+09 | 0.00 | 0.00 |
March | 0.887398E+09 | 0.693530E+09 | 0.904345E+09 | 0.398320E+09 | 0.506025E+09 | 0.00 | 0.00 |
April | 0.121026E+10 | 0.435147E+09 | 0.111909E+10 | 0.496654E+09 | 0.622434E+09 | 0.00 | 0.00 |
May | 0.133841E+10 | 0.303258E+09 | 0.112556E+10 | 0.485216E+09 | 0.640348E+09 | 0.00 | 0.00 |
June | 0.164233E+10 | 0.161988E+09 | 0.117572E+10 | 0.562988E+09 | 0.612736E+09 | 0.00 | 0.00 |
July | 0.164149E+10 | 81158282.24 | 0.110034E+10 | 0.447839E+09 | 0.652497E+09 | 0.00 | 0.00 |
August | 0.156197E+10 | 0.108987E+09 | 0.110441E+10 | 0.419691E+09 | 0.684721E+09 | 0.00 | 0.00 |
September | 0.124023E+10 | 0.242349E+09 | 0.947924E+09 | 0.416301E+09 | 0.531623E+09 | 0.00 | 0.00 |
October | 0.965237E+09 | 0.513778E+09 | 0.868419E+09 | 0.464315E+09 | 0.404104E+09 | 0.00 | 0.00 |
November | 0.590391E+09 | 0.731941E+09 | 0.664771E+09 | 0.331600E+09 | 0.333171E+09 | 0.00 | 0.00 |
December | 0.456640E+09 | 0.101779E+10 | 0.583573E+09 | 0.312337E+09 | 0.271236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126875E+11 | 0.610481E+10 | 0.109328E+11 | 0.498382E+10 | 0.594900E+10 | 0.00 | 0.00 |
Minimum of Months | 0.456640E+09 | 81158282.24 | 0.583573E+09 | 0.298319E+09 | 0.271236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164233E+10 | 0.101779E+10 | 0.117572E+10 | 0.562988E+09 | 0.684721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117460E+10 | 0.495809E+09 | 0.106049E+10 | 0.824703E+09 | 0.235784E+09 | 0.00 | 0.00 |
February | 0.106589E+10 | 0.410932E+09 | 0.944177E+09 | 0.691007E+09 | 0.253170E+09 | 0.00 | 0.00 |
March | 0.897014E+09 | 0.357049E+09 | 0.777308E+09 | 0.474317E+09 | 0.302991E+09 | 0.00 | 0.00 |
April | 0.700455E+09 | 0.227331E+09 | 0.577717E+09 | 0.236755E+09 | 0.340963E+09 | 0.00 | 0.00 |
May | 0.508433E+09 | 0.155484E+09 | 0.401770E+09 | 90890125.98 | 0.310880E+09 | 0.00 | 0.00 |
June | 0.505237E+09 | 82104397.18 | 0.325035E+09 | 39029062.12 | 0.286006E+09 | 0.00 | 0.00 |
July | 0.624822E+09 | 39146136.38 | 0.371785E+09 | 58335011.33 | 0.313450E+09 | 0.00 | 0.00 |
August | 0.785671E+09 | 54296032.74 | 0.505753E+09 | 0.159511E+09 | 0.346242E+09 | 0.00 | 0.00 |
September | 0.974801E+09 | 0.125488E+09 | 0.694817E+09 | 0.391119E+09 | 0.303698E+09 | 0.00 | 0.00 |
October | 0.120706E+10 | 0.260999E+09 | 0.967293E+09 | 0.711521E+09 | 0.255772E+09 | 0.00 | 0.00 |
November | 0.121099E+10 | 0.369834E+09 | 0.105593E+10 | 0.812665E+09 | 0.243270E+09 | 0.00 | 0.00 |
December | 0.129086E+10 | 0.506091E+09 | 0.115647E+10 | 0.954653E+09 | 0.201820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109458E+11 | 0.308456E+10 | 0.883855E+10 | 0.544450E+10 | 0.339405E+10 | 0.00 | 0.00 |
Minimum of Months | 0.505237E+09 | 39146136.38 | 0.325035E+09 | 39029062.12 | 0.201820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129086E+10 | 0.506091E+09 | 0.115647E+10 | 0.954653E+09 | 0.346242E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71690021.79 | 0.303549E+10 | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.00 | 0.00 |
February | 0.190476E+09 | 0.245509E+10 | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.00 | 0.00 |
March | 0.562510E+09 | 0.206940E+10 | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.00 | 0.00 |
April | 0.993983E+09 | 0.124320E+10 | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.00 | 0.00 |
May | 0.147226E+10 | 0.877010E+09 | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.00 | 0.00 |
June | 0.230227E+10 | 0.514139E+09 | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.00 | 0.00 |
July | 0.239954E+10 | 0.320566E+09 | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.00 | 0.00 |
August | 0.201097E+10 | 0.386393E+09 | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.00 | 0.00 |
September | 0.129514E+10 | 0.739799E+09 | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.00 | 0.00 |
October | 0.568589E+09 | 0.153120E+10 | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.00 | 0.00 |
November | 0.142385E+09 | 0.227713E+10 | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.00 | 0.00 |
December | 13911311.93 | 0.317747E+10 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.120237E+11 | 0.186269E+11 | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.00 | 0.00 |
Minimum of Months | 13911311.93 | 0.320566E+09 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.239954E+10 | 0.317747E+10 | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 60216376.95 | 0.310219E+10 | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.00 | 0.00 |
February | 0.174736E+09 | 0.250547E+10 | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.00 | 0.00 |
March | 0.539442E+09 | 0.210907E+10 | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.00 | 0.00 |
April | 0.971834E+09 | 0.126857E+10 | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.00 | 0.00 |
May | 0.144904E+10 | 0.896380E+09 | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.00 | 0.00 |
June | 0.228117E+10 | 0.527743E+09 | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.00 | 0.00 |
July | 0.237886E+10 | 0.333208E+09 | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.00 | 0.00 |
August | 0.199115E+10 | 0.400378E+09 | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.00 | 0.00 |
September | 0.127918E+10 | 0.758557E+09 | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.00 | 0.00 |
October | 0.552640E+09 | 0.156331E+10 | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.00 | 0.00 |
November | 0.128436E+09 | 0.232750E+10 | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.00 | 0.00 |
December | 10683855.72 | 0.325431E+10 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118174E+11 | 0.190467E+11 | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.00 | 0.00 |
Minimum of Months | 10683855.72 | 0.333208E+09 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237886E+10 | 0.325431E+10 | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165702E+10 | 0.205852E+10 | 0.183544E+10 | 0.113007E+10 | 0.705365E+09 | 0.00 | 0.00 |
February | 0.180448E+10 | 0.171074E+10 | 0.186390E+10 | 0.106758E+10 | 0.796329E+09 | 0.00 | 0.00 |
March | 0.249193E+10 | 0.147851E+10 | 0.231691E+10 | 0.125340E+10 | 0.106352E+10 | 0.00 | 0.00 |
April | 0.329231E+10 | 0.945866E+09 | 0.272762E+10 | 0.138347E+10 | 0.134414E+10 | 0.00 | 0.00 |
May | 0.339671E+10 | 0.712016E+09 | 0.260279E+10 | 0.128083E+10 | 0.132196E+10 | 0.00 | 0.00 |
June | 0.398022E+10 | 0.435743E+09 | 0.266454E+10 | 0.142568E+10 | 0.123886E+10 | 0.00 | 0.00 |
July | 0.412742E+10 | 0.282510E+09 | 0.258623E+10 | 0.126498E+10 | 0.132125E+10 | 0.00 | 0.00 |
August | 0.403953E+10 | 0.332030E+09 | 0.263992E+10 | 0.126492E+10 | 0.137500E+10 | 0.00 | 0.00 |
September | 0.331347E+10 | 0.554758E+09 | 0.231872E+10 | 0.120981E+10 | 0.110891E+10 | 0.00 | 0.00 |
October | 0.280996E+10 | 0.106644E+10 | 0.229978E+10 | 0.144863E+10 | 0.851151E+09 | 0.00 | 0.00 |
November | 0.197089E+10 | 0.154589E+10 | 0.196303E+10 | 0.122404E+10 | 0.738993E+09 | 0.00 | 0.00 |
December | 0.164434E+10 | 0.209843E+10 | 0.183313E+10 | 0.123723E+10 | 0.595904E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345283E+11 | 0.132215E+11 | 0.276520E+11 | 0.151906E+11 | 0.124614E+11 | 0.00 | 0.00 |
Minimum of Months | 0.164434E+10 | 0.282510E+09 | 0.183313E+10 | 0.106758E+10 | 0.595904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.412742E+10 | 0.209843E+10 | 0.272762E+10 | 0.144863E+10 | 0.137500E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297320E+10 | 0.213446E+10 | 0.293464E+10 | 0.209933E+10 | 0.835310E+09 | 0.00 | 0.00 |
February | 0.277624E+10 | 0.177967E+10 | 0.266886E+10 | 0.175899E+10 | 0.909867E+09 | 0.00 | 0.00 |
March | 0.250347E+10 | 0.157314E+10 | 0.234940E+10 | 0.120741E+10 | 0.114199E+10 | 0.00 | 0.00 |
April | 0.213426E+10 | 0.102634E+10 | 0.192820E+10 | 0.608802E+09 | 0.131940E+10 | 0.00 | 0.00 |
May | 0.176626E+10 | 0.743696E+09 | 0.153453E+10 | 0.264619E+09 | 0.126991E+10 | 0.00 | 0.00 |
June | 0.199402E+10 | 0.440600E+09 | 0.139130E+10 | 0.193129E+09 | 0.119817E+10 | 0.00 | 0.00 |
July | 0.233226E+10 | 0.278178E+09 | 0.148073E+10 | 0.194039E+09 | 0.128669E+10 | 0.00 | 0.00 |
August | 0.262948E+10 | 0.339884E+09 | 0.178330E+10 | 0.418180E+09 | 0.136512E+10 | 0.00 | 0.00 |
September | 0.290504E+10 | 0.633117E+09 | 0.215178E+10 | 0.995888E+09 | 0.115590E+10 | 0.00 | 0.00 |
October | 0.325714E+10 | 0.116531E+10 | 0.275740E+10 | 0.181121E+10 | 0.946181E+09 | 0.00 | 0.00 |
November | 0.310620E+10 | 0.161446E+10 | 0.293046E+10 | 0.206868E+10 | 0.861782E+09 | 0.00 | 0.00 |
December | 0.320905E+10 | 0.216017E+10 | 0.314397E+10 | 0.243012E+10 | 0.713855E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.315866E+11 | 0.138890E+11 | 0.270546E+11 | 0.140504E+11 | 0.130042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176626E+10 | 0.278178E+09 | 0.139130E+10 | 0.193129E+09 | 0.713855E+09 | 0.00 | 0.00 |
Maximum of Months | 0.325714E+10 | 0.216017E+10 | 0.314397E+10 | 0.243012E+10 | 0.136512E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770397E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161192967.6 | 81.21 | 0.00 | 0.00 |
February | 0.696149E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145529858.9 | 81.21 | 0.00 | 0.00 |
March | 0.770265E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161195457.8 | 81.21 | 0.00 | 0.00 |
April | 0.746464E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156052115.6 | 81.21 | 0.00 | 0.00 |
May | 0.770418E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161388603.6 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156204607.5 | 81.21 | 0.00 | 0.00 |
July | 0.771225E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161406001.3 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161406689.2 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203910.5 | 81.21 | 0.00 | 0.00 |
October | 0.770277E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161343300.5 | 81.21 | 0.00 | 0.00 |
November | 0.744841E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155988407.7 | 81.21 | 0.00 | 0.00 |
December | 0.771193E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161079943.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907394E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189899E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696149E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161406689.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771225E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145529858.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.120248E+12 | -0.118519E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172883E+10 | 81.26 | 0.00 | 0.00 |
February | 0.109181E+12 | -0.107615E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156563E+10 | 81.26 | 0.00 | 0.00 |
March | 0.118859E+12 | -0.117120E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173945E+10 | 81.26 | 0.00 | 0.00 |
April | 0.110912E+12 | -0.109228E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168461E+10 | 81.25 | 0.00 | 0.00 |
May | 0.109279E+12 | -0.107539E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173979E+10 | 81.25 | 0.00 | 0.00 |
June | 0.100932E+12 | -0.992537E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167873E+10 | 81.25 | 0.00 | 0.00 |
July | 0.101013E+12 | -0.992825E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173063E+10 | 81.25 | 0.00 | 0.00 |
August | 0.100308E+12 | -0.985789E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172868E+10 | 81.25 | 0.00 | 0.00 |
September | 0.990864E+11 | -0.974150E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167137E+10 | 81.25 | 0.00 | 0.00 |
October | 0.106681E+12 | -0.104955E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172650E+10 | 81.25 | 0.00 | 0.00 |
November | 0.108402E+12 | -0.106732E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167054E+10 | 81.25 | 0.00 | 0.00 |
December | 0.116967E+12 | -0.115240E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172671E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.130187E+13 | -0.128148E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203915E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.990864E+11 | -0.118519E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.173979E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.120248E+12 | -0.974150E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156563E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.711727E+11 | -0.697069E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146582E+10 | 58.98 | 0.00 | 0.00 |
February | 0.647858E+11 | -0.634562E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.132952E+10 | 58.98 | 0.00 | 0.00 |
March | 0.700560E+11 | -0.685754E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148062E+10 | 58.99 | 0.00 | 0.00 |
April | 0.642278E+11 | -0.627930E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143478E+10 | 58.98 | 0.00 | 0.00 |
May | 0.617865E+11 | -0.603053E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148122E+10 | 58.98 | 0.00 | 0.00 |
June | 0.556531E+11 | -0.542265E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142661E+10 | 58.98 | 0.00 | 0.00 |
July | 0.546202E+11 | -0.531516E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146860E+10 | 58.98 | 0.00 | 0.00 |
August | 0.540652E+11 | -0.525993E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146588E+10 | 58.98 | 0.00 | 0.00 |
September | 0.540313E+11 | -0.526148E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141650E+10 | 58.98 | 0.00 | 0.00 |
October | 0.595085E+11 | -0.580455E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146299E+10 | 58.98 | 0.00 | 0.00 |
November | 0.620357E+11 | -0.606203E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141541E+10 | 58.98 | 0.00 | 0.00 |
December | 0.683600E+11 | -0.668968E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146312E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.740303E+12 | -0.722992E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.173111E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.540313E+11 | -0.697069E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.148122E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.711727E+11 | -0.525993E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.132952E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.87 | 0.86 | 01-JAN-07:40 | 10413.21 | 38.34 | 292.50 | 291.83 | 1763.19 | 28.87 | 237.83 | 278.00 |
February | 282.00 | 0.87 | 0.86 | 01-FEB-07:40 | 12162.52 | 37.20 | 266.17 | 277.50 | 1029.06 | 25.33 | 215.67 | 259.67 |
March | 351.33 | 0.87 | 0.86 | 01-MAR-07:10 | 1922.91 | 21.92 | 127.33 | 335.83 | 651.99 | 22.32 | 251.50 | 290.33 |
April | 381.83 | 0.87 | 0.86 | 01-APR-06:00 | 1391.75 | 20.99 | 151.33 | 357.67 | 584.05 | 22.70 | 321.00 | 322.17 |
May | 378.00 | 0.87 | 0.86 | 01-MAY-06:40 | 1056.68 | 20.53 | 81.83 | 381.50 | 455.87 | 22.28 | 299.83 | 324.83 |
June | 412.83 | 0.88 | 0.86 | 01-JUN-06:19 | 822.42 | 19.76 | 47.17 | 384.00 | 354.02 | 21.56 | 203.83 | 244.00 |
July | 395.33 | 0.87 | 0.86 | 01-JUL-07:10 | 1018.62 | 20.26 | 84.33 | 383.67 | 434.44 | 22.03 | 285.00 | 314.00 |
August | 408.83 | 0.87 | 0.86 | 01-AUG-06:40 | 1303.56 | 20.71 | 162.17 | 380.17 | 544.94 | 22.44 | 325.17 | 332.17 |
September | 359.33 | 0.87 | 0.86 | 01-SEP-06:49 | 1439.70 | 20.68 | 112.83 | 335.67 | 604.21 | 22.45 | 269.67 | 295.67 |
October | 329.00 | 0.87 | 0.86 | 01-OCT-07:10 | 6550.25 | 29.66 | 209.00 | 322.83 | 749.10 | 23.06 | 236.33 | 298.50 |
November | 284.17 | 0.87 | 0.86 | 01-NOV-06:49 | 11872.71 | 39.05 | 278.67 | 286.67 | 1608.86 | 28.46 | 248.83 | 273.83 |
December | 265.67 | 0.87 | 0.86 | 01-DEC-07:49 | 11873.20 | 40.47 | 264.00 | 272.17 | 2932.32 | 32.04 | 221.83 | 261.33 |
Annual Sum or Average | 4149.83 | 0.87 | 4494.52 | 26.31 | 2077.33 | 4009.50 | 888.39 | 24.05 | 3116.50 | 3494.50 | ||
Minimum of Months | 265.67 | 0.87 | 0.86 | 822.42 | 19.76 | 47.17 | 272.17 | 354.02 | 21.56 | 203.83 | 244.00 | |
Maximum of Months | 412.83 | 0.88 | 0.86 | 12162.52 | 40.47 | 292.50 | 384.00 | 2932.32 | 32.04 | 325.17 | 332.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.24 | 0.22 | 01-JAN-07:40 | 11040.66 | 38.42 | 292.67 | 297.00 | 2388.96 | 28.30 | 208.17 | 286.83 |
February | 282.00 | 0.24 | 0.22 | 01-FEB-07:40 | 12788.25 | 37.24 | 265.83 | 285.00 | 1652.95 | 24.76 | 183.17 | 270.17 |
March | 351.33 | 0.25 | 0.22 | 01-MAR-06:00 | 2359.93 | 21.84 | 134.50 | 344.17 | 1088.10 | 22.15 | 213.33 | 320.50 |
April | 381.83 | 0.26 | 0.22 | 01-APR-06:40 | 1712.77 | 21.24 | 174.50 | 365.83 | 904.29 | 22.80 | 322.67 | 347.17 |
May | 378.00 | 0.26 | 0.22 | 01-MAY-06:19 | 1291.12 | 21.01 | 138.33 | 391.00 | 689.74 | 22.58 | 312.50 | 360.83 |
June | 412.83 | 0.26 | 0.22 | 01-JUN-05:49 | 1005.42 | 20.42 | 80.67 | 399.50 | 536.56 | 22.01 | 270.33 | 360.50 |
July | 395.33 | 0.26 | 0.22 | 01-JUL-06:40 | 1234.21 | 20.82 | 130.17 | 395.50 | 649.46 | 22.40 | 313.33 | 364.83 |
August | 408.83 | 0.26 | 0.22 | 01-AUG-06:10 | 1578.82 | 21.10 | 194.83 | 388.17 | 819.50 | 22.66 | 328.00 | 366.17 |
September | 359.33 | 0.26 | 0.22 | 01-SEP-06:30 | 1832.69 | 20.72 | 128.17 | 346.50 | 996.33 | 22.36 | 236.67 | 322.00 |
October | 329.00 | 0.25 | 0.22 | 01-OCT-06:49 | 7101.82 | 29.50 | 196.33 | 328.67 | 1299.25 | 22.56 | 170.50 | 315.00 |
November | 284.17 | 0.24 | 0.22 | 01-NOV-06:49 | 12539.73 | 39.12 | 278.67 | 291.83 | 2276.99 | 27.86 | 202.50 | 280.50 |
December | 265.67 | 0.24 | 0.22 | 01-DEC-07:40 | 12625.40 | 40.53 | 264.00 | 277.00 | 3687.48 | 31.39 | 183.67 | 271.00 |
Annual Sum or Average | 4149.83 | 0.25 | 4907.97 | 26.54 | 2278.67 | 4110.17 | 1301.29 | 23.97 | 2944.83 | 3865.50 | ||
Minimum of Months | 265.67 | 0.24 | 0.22 | 1005.42 | 20.42 | 80.67 | 277.00 | 536.56 | 22.01 | 170.50 | 270.17 | |
Maximum of Months | 412.83 | 0.26 | 0.22 | 12788.25 | 40.53 | 292.67 | 399.50 | 3687.48 | 31.39 | 328.00 | 366.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.67 | 0.60 | 01-JAN-11:20 | 446.91 | 15.44 | 0.00 | 257.17 | 222.23 | 19.01 | 0.50 | 141.83 |
February | 282.00 | 0.65 | 0.60 | 01-FEB-08:20 | 508.91 | 16.16 | 0.00 | 265.50 | 260.92 | 19.66 | 22.50 | 159.17 |
March | 351.33 | 0.64 | 0.60 | 01-MAR-07:19 | 628.52 | 16.97 | 0.00 | 333.50 | 297.74 | 20.28 | 80.83 | 234.83 |
April | 381.83 | 0.62 | 0.60 | 01-APR-06:49 | 796.77 | 18.47 | 0.00 | 368.67 | 378.89 | 21.69 | 210.00 | 343.00 |
May | 378.00 | 0.61 | 0.60 | 01-MAY-06:19 | 963.62 | 18.82 | 4.50 | 400.50 | 408.38 | 21.96 | 203.33 | 367.83 |
June | 412.83 | 0.61 | 0.60 | 01-JUN-05:40 | 1012.02 | 20.72 | 74.00 | 411.83 | 388.30 | 22.26 | 191.33 | 378.00 |
July | 395.33 | 0.61 | 0.60 | 01-JUL-06:49 | 978.69 | 19.53 | 27.33 | 404.00 | 421.50 | 22.04 | 221.17 | 376.67 |
August | 408.83 | 0.62 | 0.60 | 01-AUG-05:49 | 862.78 | 18.52 | 0.00 | 391.67 | 419.38 | 21.77 | 236.33 | 369.67 |
September | 359.33 | 0.63 | 0.60 | 01-SEP-06:40 | 651.73 | 17.45 | 0.00 | 340.50 | 319.31 | 20.75 | 113.33 | 274.17 |
October | 329.00 | 0.66 | 0.60 | 01-OCT-07:30 | 444.72 | 15.95 | 0.00 | 301.67 | 234.97 | 19.44 | 20.83 | 185.17 |
November | 284.17 | 0.65 | 0.60 | 01-NOV-07:30 | 460.66 | 15.90 | 0.00 | 268.00 | 242.47 | 19.47 | 2.33 | 187.00 |
December | 265.67 | 0.68 | 0.60 | 01-DEC-08:30 | 370.04 | 14.68 | 0.00 | 241.00 | 203.88 | 18.40 | 0.00 | 117.67 |
Annual Sum or Average | 4149.83 | 0.64 | 707.19 | 17.62 | 105.83 | 3984.00 | 327.18 | 20.74 | 1302.50 | 3135.00 | ||
Minimum of Months | 265.67 | 0.61 | 0.60 | 370.04 | 14.68 | 0.00 | 241.00 | 203.88 | 18.40 | 0.00 | 117.67 | |
Maximum of Months | 412.83 | 0.68 | 0.60 | 1012.02 | 20.72 | 74.00 | 411.83 | 421.50 | 22.26 | 236.33 | 378.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.67 | 0.60 | 01-JAN-11:20 | 446.91 | 15.44 | 0.00 | 257.17 | 222.23 | 19.01 | 0.50 | 141.83 |
February | 282.00 | 0.65 | 0.60 | 01-FEB-08:20 | 508.91 | 16.16 | 0.00 | 265.50 | 260.92 | 19.66 | 22.50 | 159.17 |
March | 351.33 | 0.64 | 0.60 | 01-MAR-07:19 | 628.52 | 16.97 | 0.00 | 333.50 | 297.74 | 20.28 | 80.83 | 234.83 |
April | 381.83 | 0.62 | 0.60 | 01-APR-06:49 | 796.77 | 18.47 | 0.00 | 368.67 | 378.89 | 21.69 | 210.00 | 343.00 |
May | 378.00 | 0.61 | 0.60 | 01-MAY-06:19 | 963.62 | 18.82 | 4.50 | 400.50 | 408.38 | 21.96 | 203.33 | 367.83 |
June | 412.83 | 0.61 | 0.60 | 01-JUN-05:40 | 1012.02 | 20.72 | 74.00 | 411.83 | 388.30 | 22.26 | 191.33 | 378.00 |
July | 395.33 | 0.61 | 0.60 | 01-JUL-06:49 | 978.69 | 19.53 | 27.33 | 404.00 | 421.50 | 22.04 | 221.17 | 376.67 |
August | 408.83 | 0.62 | 0.60 | 01-AUG-05:49 | 862.78 | 18.52 | 0.00 | 391.67 | 419.38 | 21.77 | 236.33 | 369.67 |
September | 359.33 | 0.63 | 0.60 | 01-SEP-06:40 | 651.73 | 17.45 | 0.00 | 340.50 | 319.31 | 20.75 | 113.33 | 274.17 |
October | 329.00 | 0.66 | 0.60 | 01-OCT-07:30 | 444.72 | 15.95 | 0.00 | 301.67 | 234.97 | 19.44 | 20.83 | 185.17 |
November | 284.17 | 0.65 | 0.60 | 01-NOV-07:30 | 460.66 | 15.90 | 0.00 | 268.00 | 242.47 | 19.47 | 2.33 | 187.00 |
December | 265.67 | 0.68 | 0.60 | 01-DEC-08:30 | 370.04 | 14.68 | 0.00 | 241.00 | 203.88 | 18.40 | 0.00 | 117.67 |
Annual Sum or Average | 4149.83 | 0.64 | 707.19 | 17.62 | 105.83 | 3984.00 | 327.18 | 20.74 | 1302.50 | 3135.00 | ||
Minimum of Months | 265.67 | 0.61 | 0.60 | 370.04 | 14.68 | 0.00 | 241.00 | 203.88 | 18.40 | 0.00 | 117.67 | |
Maximum of Months | 412.83 | 0.68 | 0.60 | 1012.02 | 20.72 | 74.00 | 411.83 | 421.50 | 22.26 | 236.33 | 378.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300081E+11 | 142827.65 | 11-JAN-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286037E+11 | 143449.03 | 04-FEB-18:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258054E+11 | 140663.02 | 09-MAR-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166909E+11 | 141739.44 | 07-APR-04:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.536084E+10 | 130923.05 | 07-MAY-05:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.342414E+09 | 82249.36 | 09-JUN-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281880E+09 | 27185.72 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161732E+11 | 142497.33 | 30-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318642E+11 | 144778.85 | 25-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387400E+11 | 147283.95 | 18-DEC-22:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387400E+11 | 147283.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.675019E+09 | 1534.91 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417208E+09 | 1551.52 | 17-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210288E+09 | 2214.27 | 03-MAR-02:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35136988.42 | 1964.55 | 06-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20732542.63 | 1951.31 | 05-MAY-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1039095.03 | 935.83 | 09-JUN-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93910556.46 | 1784.42 | 25-OCT-17:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186634E+09 | 2424.45 | 11-NOV-08:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.634596E+09 | 2481.34 | 25-DEC-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.675019E+09 | 2481.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 92542648.13 | 851.71 | 20-JAN-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26462992.42 | 670.48 | 06-FEB-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46920472.63 | 1141.17 | 23-DEC-11:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92542648.13 | 1141.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194885E+09 | 672.24 | 19-JAN-12:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92955374.38 | 485.94 | 06-FEB-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1600164.95 | 105.61 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 358444.52 | 146.75 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3963475.73 | 122.16 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209566E+09 | 905.15 | 23-DEC-11:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209566E+09 | 905.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6984510.21 | 4822.86 | 30-JAN-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4945533.34 | 5209.66 | 21-FEB-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29376097.83 | 7182.49 | 08-MAR-03:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14821186.44 | 7024.23 | 24-APR-01:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24808892.88 | 7124.59 | 06-MAY-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 781156.41 | 2603.85 | 09-JUN-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52990258.01 | 7099.02 | 23-OCT-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36871372.48 | 7548.60 | 03-NOV-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11832830.29 | 7473.22 | 01-DEC-02:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52990258.01 | 7548.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 89207271.47 | 2184.78 | 19-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13067117.75 | 1467.21 | 22-FEB-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3135.52 | 31.36 | 22-MAR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12059452.40 | 2543.38 | 25-OCT-10:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 132356.79 | 125.30 | 10-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39318980.43 | 2880.94 | 25-DEC-18:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89207271.47 | 2880.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.796864E+09 | 4941.85 | 19-JAN-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160604E+09 | 3923.45 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.486607E+09 | 8990.61 | 25-DEC-18:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.796864E+09 | 8990.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112943E+10 | 5560.56 | 25-JAN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.572570E+09 | 2986.75 | 17-FEB-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65364897.79 | 2153.77 | 23-MAR-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47944146.31 | 1886.33 | 26-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100939E+09 | 3086.98 | 11-NOV-08:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117047E+10 | 3601.01 | 25-DEC-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117047E+10 | 5560.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 126160.80 | 420.54 | 23-APR-03:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 272181.42 | 907.27 | 06-MAY-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 211015.92 | 299.86 | 28-OCT-02:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 637891.48 | 2100.69 | 30-NOV-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1247249.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 637891.48 | 2100.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.944939E+09 | 5491.68 | 21-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390013E+09 | 3526.91 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14609749.89 | 1495.80 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17464.88 | 0.56 | 13-APR-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49244.77 | 0.57 | 31-MAY-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79480.58 | 0.57 | 11-JUN-19:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 54221.10 | 0.58 | 16-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 57322.84 | 0.57 | 22-AUG-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48409.84 | 0.57 | 03-SEP-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16084226.56 | 1631.65 | 26-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26216283.49 | 1775.53 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.684177E+09 | 4918.45 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17464.88 | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.944939E+09 | 5491.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217606E+10 | 6058.04 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142798E+10 | 5999.53 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.586643E+09 | 5895.09 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82292472.36 | 5706.03 | 17-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35137563.25 | 5700.66 | 08-MAY-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8139986.43 | 5706.71 | 21-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1625490.54 | 3418.12 | 17-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3137713.28 | 4706.08 | 29-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6923337.18 | 4598.05 | 06-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248195E+09 | 5976.04 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.771104E+09 | 5907.24 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219399E+10 | 6057.14 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1625490.54 | 3418.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.219399E+10 | 6058.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346593E+10 | 6047.66 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230487E+10 | 6047.55 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.933249E+09 | 5937.09 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126781E+09 | 5698.08 | 29-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39447672.16 | 5697.99 | 08-MAY-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7857457.59 | 5226.56 | 20-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1979272.11 | 3507.98 | 17-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3385143.94 | 4729.85 | 29-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10398207.34 | 5700.34 | 30-SEP-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402939E+09 | 6037.66 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150208E+10 | 6019.69 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377223E+10 | 6047.81 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1979272.11 | 3507.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377223E+10 | 6047.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 57802633.13 | 4782.19 | 19-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57802633.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57802633.13 | 4782.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129451E+11 | 33884.59 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.820204E+10 | 33715.21 | 04-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177304E+10 | 32936.24 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236877E+09 | 32604.18 | 27-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110124E+09 | 32589.98 | 06-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31978044.57 | 30356.24 | 21-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12350770.65 | 24657.97 | 29-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18968456.11 | 23204.79 | 28-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80429040.80 | 31919.37 | 25-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958157E+09 | 33186.33 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441517E+10 | 33684.03 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152061E+11 | 34183.15 | 21-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12350770.65 | 23204.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152061E+11 | 34183.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229437E+10 | 5934.21 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153052E+10 | 5912.39 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.605823E+09 | 5777.07 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95654577.00 | 5288.24 | 22-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26762741.21 | 5596.17 | 12-MAY-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2869641.86 | 4842.83 | 17-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 484305.25 | 2694.01 | 26-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1269752.41 | 2890.24 | 02-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3307913.47 | 4084.14 | 23-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256618E+09 | 5848.47 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.824950E+09 | 5779.16 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230633E+10 | 5933.24 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 484305.25 | 2694.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230633E+10 | 5934.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354380E+10 | 5924.75 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238979E+10 | 5924.49 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.892925E+09 | 5782.10 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139187E+09 | 5587.04 | 12-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31643317.70 | 5588.10 | 08-MAY-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2856564.02 | 4970.42 | 17-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 512063.56 | 2922.18 | 26-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1880840.77 | 2788.77 | 29-AUG-16:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5473741.83 | 5418.84 | 25-SEP-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.391043E+09 | 5858.79 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149905E+10 | 5831.73 | 27-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379780E+10 | 5924.46 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 512063.56 | 2788.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379780E+10 | 5924.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.865856E+09 | 1796.23 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587301E+09 | 1796.40 | 22-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297378E+09 | 1778.09 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62801019.06 | 1567.63 | 29-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26433387.94 | 1606.31 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5340396.71 | 1534.71 | 21-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 573580.65 | 1224.14 | 17-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1012626.69 | 1212.12 | 28-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2411193.17 | 1482.28 | 30-SEP-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130380E+09 | 1796.25 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380950E+09 | 1778.32 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871848E+09 | 1796.06 | 25-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 573580.65 | 1212.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.871848E+09 | 1796.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128672E+10 | 1793.28 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.877584E+09 | 1793.43 | 22-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433768E+09 | 1785.91 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85360231.40 | 1734.44 | 07-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29007333.47 | 1687.39 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5038949.70 | 1517.88 | 21-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 573675.59 | 1211.58 | 17-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1063461.77 | 1328.92 | 27-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2854213.70 | 1540.26 | 27-SEP-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204424E+09 | 1793.24 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669501E+09 | 1793.04 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137910E+10 | 1793.27 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 573675.59 | 1211.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137910E+10 | 1793.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172835E+10 | 8312.13 | 17-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115044E+10 | 8248.14 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.581787E+09 | 8134.41 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167058E+09 | 7882.43 | 24-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85192670.31 | 7883.12 | 31-MAY-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13352858.26 | 7872.27 | 19-JUN-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6406119.17 | 5374.10 | 16-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4374236.58 | 5112.13 | 02-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5490248.31 | 5948.41 | 08-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.253403E+09 | 8193.05 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.562172E+09 | 8083.60 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166339E+10 | 8264.74 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.622142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4374236.58 | 5112.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172835E+10 | 8312.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.216558E+10 | 0.216558E+10 | 68963.65 | 26-JAN-22:50 | 68963.65 | 0.00 |
February | 0.00 | 0.00 | 0.739146E+10 | 0.739146E+10 | 126948.93 | 14-FEB-16:03 | 126948.93 | 0.00 |
March | 0.00 | 0.00 | 0.241175E+11 | 0.241175E+11 | 133161.12 | 08-MAR-16:03 | 133161.12 | 0.00 |
April | 0.00 | 0.00 | 0.974810E+11 | 0.974810E+11 | 200105.71 | 28-APR-18:40 | 200105.71 | 0.00 |
May | 0.00 | 0.00 | 0.182373E+12 | 0.182373E+12 | 228636.76 | 19-MAY-18:20 | 228636.76 | 0.16 |
June | 0.00 | 0.00 | 0.321926E+12 | 0.321706E+12 | 271948.43 | 27-JUN-20:10 | 271948.43 | 0.44 |
July | 0.00 | 0.00 | 0.444156E+12 | 0.421356E+12 | 348424.04 | 31-JUL-20:00 | 190466.42 | 0.94 |
August | 0.00 | 0.00 | 0.397825E+12 | 0.385938E+12 | 292457.81 | 14-AUG-21:00 | 243308.75 | 0.98 |
September | 0.00 | 0.00 | 0.257631E+12 | 0.256742E+12 | 235358.00 | 13-SEP-19:20 | 235358.00 | 0.69 |
October | 0.00 | 0.00 | 0.110679E+12 | 0.110621E+12 | 206354.02 | 05-OCT-18:10 | 206354.02 | 0.16 |
November | 0.00 | 0.00 | 0.426069E+10 | 0.426069E+10 | 84376.19 | 27-NOV-22:50 | 84376.19 | 0.00 |
December | 0.00 | 0.00 | 0.133015E+10 | 0.133015E+10 | 69263.66 | 19-DEC-22:58 | 69263.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185134E+13 | 0.181548E+13 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.133015E+10 | 0.133015E+10 | 68963.65 | 68963.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.444156E+12 | 0.421356E+12 | 348424.04 | 271948.43 | 0.98 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119142E+09 | 0.119142E+09 | 4033.62 | 05-JAN-14:00 | 4033.62 | 0.00 |
February | 0.00 | 0.00 | 0.100795E+10 | 0.100795E+10 | 21463.19 | 14-FEB-16:00 | 21463.19 | 0.00 |
March | 0.00 | 0.00 | 0.393961E+10 | 0.393961E+10 | 22393.53 | 08-MAR-16:00 | 22393.53 | 0.00 |
April | 0.00 | 0.00 | 0.151750E+11 | 0.151750E+11 | 24754.08 | 29-APR-15:01 | 24754.08 | 0.00 |
May | 0.00 | 0.00 | 0.282246E+11 | 0.282234E+11 | 27342.90 | 19-MAY-15:00 | 27342.90 | 0.15 |
June | 0.00 | 0.00 | 0.460860E+11 | 0.460141E+11 | 31625.90 | 28-JUN-15:01 | 31625.90 | 0.39 |
July | 0.00 | 0.00 | 0.682682E+11 | 0.601133E+11 | 44602.88 | 01-JUL-01:00 | 18133.08 | 0.93 |
August | 0.00 | 0.00 | 0.596034E+11 | 0.548217E+11 | 42304.56 | 26-AUG-10:00 | 19838.61 | 0.96 |
September | 0.00 | 0.00 | 0.382980E+11 | 0.373756E+11 | 39969.02 | 05-SEP-12:30 | 23300.83 | 0.66 |
October | 0.00 | 0.00 | 0.161610E+11 | 0.160445E+11 | 28113.12 | 11-OCT-10:07 | 22376.17 | 0.15 |
November | 0.00 | 0.00 | 0.449883E+09 | 0.449883E+09 | 14180.63 | 09-NOV-14:00 | 14180.63 | 0.00 |
December | 0.00 | 0.00 | 14984.70 | 14984.70 | 39.75 | 29-DEC-16:07 | 39.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.277333E+12 | 0.263284E+12 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 14984.70 | 14984.70 | 39.75 | 39.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.682682E+11 | 0.601133E+11 | 44602.88 | 31625.90 | 0.96 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.117519E+10 | 0.117519E+10 | 22313.12 | 05-JAN-17:01 | 22313.12 | 0.00 |
February | 0.00 | 0.00 | 0.162216E+10 | 0.162143E+10 | 23689.10 | 15-FEB-18:01 | 23689.10 | 0.00 |
March | 0.00 | 0.00 | 0.223651E+10 | 0.223305E+10 | 23973.80 | 23-MAR-17:41 | 23973.80 | 0.01 |
April | 0.00 | 0.00 | 0.426525E+10 | 0.422059E+10 | 24399.80 | 25-APR-16:21 | 24399.80 | 0.01 |
May | 0.00 | 0.00 | 0.579945E+10 | 0.499956E+10 | 23429.77 | 06-MAY-19:41 | 23429.77 | 0.22 |
June | 0.00 | 0.00 | 0.895086E+10 | 0.678588E+10 | 23232.28 | 13-JUN-21:51 | 23232.28 | 0.53 |
July | 0.00 | 0.00 | 0.110324E+11 | 0.696358E+10 | 25140.44 | 31-JUL-21:51 | 18346.41 | 0.77 |
August | 0.00 | 0.00 | 0.108419E+11 | 0.678714E+10 | 24309.87 | 25-AUG-21:51 | 17361.03 | 0.77 |
September | 0.00 | 0.00 | 0.829604E+10 | 0.543210E+10 | 23493.84 | 05-SEP-21:51 | 17310.04 | 0.63 |
October | 0.00 | 0.00 | 0.516394E+10 | 0.410632E+10 | 24029.34 | 13-OCT-17:41 | 24029.34 | 0.26 |
November | 0.00 | 0.00 | 0.227287E+10 | 0.218594E+10 | 21150.60 | 02-NOV-15:01 | 21150.60 | 0.05 |
December | 0.00 | 0.00 | 0.972562E+09 | 0.972562E+09 | 21112.19 | 26-DEC-16:01 | 21112.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.626292E+11 | 0.474833E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.972562E+09 | 0.972562E+09 | 21112.19 | 17310.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110324E+11 | 0.696358E+10 | 25140.44 | 24399.80 | 0.77 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.208285E+09 | 0.208285E+09 | 20885.09 | 05-JAN-16:01 | 20885.09 | 0.00 |
February | 0.00 | 0.00 | 0.487749E+09 | 0.487697E+09 | 20893.61 | 17-FEB-16:01 | 20893.61 | 0.00 |
March | 0.00 | 0.00 | 0.100070E+10 | 0.998807E+09 | 23611.03 | 30-MAR-18:11 | 23611.03 | 0.00 |
April | 0.00 | 0.00 | 0.323487E+10 | 0.319413E+10 | 24145.13 | 25-APR-16:21 | 24145.13 | 0.01 |
May | 0.00 | 0.00 | 0.536641E+10 | 0.460226E+10 | 22900.08 | 06-MAY-19:41 | 22900.08 | 0.22 |
June | 0.00 | 0.00 | 0.891926E+10 | 0.679777E+10 | 23026.48 | 13-JUN-21:51 | 23026.48 | 0.53 |
July | 0.00 | 0.00 | 0.106946E+11 | 0.671678E+10 | 24801.31 | 31-JUL-21:51 | 18087.52 | 0.77 |
August | 0.00 | 0.00 | 0.981757E+10 | 0.590290E+10 | 23862.62 | 25-AUG-21:51 | 16958.07 | 0.77 |
September | 0.00 | 0.00 | 0.642653E+10 | 0.383931E+10 | 23005.03 | 05-SEP-21:51 | 16828.18 | 0.60 |
October | 0.00 | 0.00 | 0.290746E+10 | 0.206653E+10 | 22191.71 | 02-OCT-21:51 | 18045.25 | 0.23 |
November | 0.00 | 0.00 | 0.534035E+09 | 0.509761E+09 | 20929.10 | 02-NOV-15:01 | 20929.10 | 0.02 |
December | 0.00 | 0.00 | 0.120795E+09 | 0.120795E+09 | 20867.84 | 02-DEC-16:01 | 20867.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.497183E+11 | 0.354450E+11 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.120795E+09 | 0.120795E+09 | 20867.84 | 16828.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106946E+11 | 0.679777E+10 | 24801.31 | 24145.13 | 0.77 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.259962E+11 | 0.259962E+11 | 59942.43 | 03-JAN-12:40 | 59942.43 | 0.00 |
February | 0.00 | 0.00 | 0.243098E+11 | 0.243098E+11 | 59957.71 | 14-FEB-13:00 | 59957.71 | 0.00 |
March | 0.00 | 0.00 | 0.208572E+11 | 0.208572E+11 | 49185.49 | 08-MAR-13:30 | 49185.49 | 0.00 |
April | 0.00 | 0.00 | 0.201830E+11 | 0.201830E+11 | 35099.92 | 13-APR-13:20 | 35099.92 | 0.00 |
May | 0.00 | 0.00 | 0.172298E+11 | 0.154490E+11 | 23303.17 | 13-MAY-13:10 | 23303.17 | 0.12 |
June | 0.00 | 0.00 | 0.257747E+11 | 0.193242E+11 | 27413.28 | 29-JUN-13:30 | 17196.48 | 0.34 |
July | 0.00 | 0.00 | 0.400646E+11 | 0.181112E+11 | 31221.04 | 23-JUL-13:30 | 21376.05 | 0.90 |
August | 0.00 | 0.00 | 0.457672E+11 | 0.235081E+11 | 42540.60 | 22-AUG-13:00 | 36383.28 | 0.93 |
September | 0.00 | 0.00 | 0.472268E+11 | 0.339209E+11 | 55541.07 | 28-SEP-13:30 | 46040.80 | 0.68 |
October | 0.00 | 0.00 | 0.464267E+11 | 0.428497E+11 | 59444.67 | 19-OCT-12:30 | 59444.67 | 0.17 |
November | 0.00 | 0.00 | 0.366912E+11 | 0.366912E+11 | 60517.45 | 20-NOV-12:10 | 60517.45 | 0.00 |
December | 0.00 | 0.00 | 0.289439E+11 | 0.289439E+11 | 60665.43 | 31-DEC-13:35 | 60665.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.379471E+12 | 0.310144E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.172298E+11 | 0.154490E+11 | 23303.17 | 17196.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.472268E+11 | 0.428497E+11 | 60665.43 | 60665.43 | 0.93 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.393412E+09 | 0.393412E+09 | 21223.24 | 06-JAN-19:03 | 21223.24 | 0.00 |
February | 0.00 | 0.00 | 0.165617E+10 | 0.165309E+10 | 103404.11 | 14-FEB-19:01 | 103404.11 | 0.00 |
March | 0.00 | 0.00 | 0.755003E+10 | 0.736041E+10 | 111031.76 | 27-MAR-19:11 | 111031.76 | 0.02 |
April | 0.00 | 0.00 | 0.192882E+11 | 0.190435E+11 | 116649.21 | 27-APR-21:51 | 116649.21 | 0.01 |
May | 0.00 | 0.00 | 0.327974E+11 | 0.281316E+11 | 117424.67 | 16-MAY-21:51 | 117424.67 | 0.17 |
June | 0.00 | 0.00 | 0.514697E+11 | 0.404254E+11 | 119035.54 | 18-JUN-08:51 | 119035.54 | 0.44 |
July | 0.00 | 0.00 | 0.625003E+11 | 0.406348E+11 | 131289.20 | 31-JUL-21:51 | 95570.66 | 0.68 |
August | 0.00 | 0.00 | 0.551029E+11 | 0.345773E+11 | 129298.00 | 25-AUG-21:51 | 90677.38 | 0.64 |
September | 0.00 | 0.00 | 0.355578E+11 | 0.229204E+11 | 125625.89 | 05-SEP-21:51 | 93194.97 | 0.44 |
October | 0.00 | 0.00 | 0.165191E+11 | 0.123214E+11 | 118640.34 | 02-OCT-21:51 | 97741.66 | 0.18 |
November | 0.00 | 0.00 | 0.340518E+10 | 0.307600E+10 | 105673.97 | 02-NOV-18:11 | 105673.97 | 0.04 |
December | 0.00 | 0.00 | 0.282791E+09 | 0.282791E+09 | 57847.65 | 03-DEC-09:01 | 57847.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.286523E+12 | 0.210820E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.282791E+09 | 0.282791E+09 | 21223.24 | 21223.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.625003E+11 | 0.406348E+11 | 131289.20 | 119035.54 | 0.68 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.114727E+10 | 0.114727E+10 | 18680.31 | 03-JAN-09:01 | 18680.31 | 0.00 |
February | 0.00 | 0.00 | 0.145533E+10 | 0.144696E+10 | 18908.39 | 14-FEB-19:01 | 18908.39 | 0.00 |
March | 0.00 | 0.00 | 0.273085E+10 | 0.271555E+10 | 19187.85 | 13-MAR-20:41 | 19187.85 | 0.01 |
April | 0.00 | 0.00 | 0.533740E+10 | 0.529117E+10 | 21590.61 | 27-APR-08:51 | 21590.61 | 0.01 |
May | 0.00 | 0.00 | 0.663950E+10 | 0.568335E+10 | 21601.96 | 13-MAY-08:51 | 21601.96 | 0.25 |
June | 0.00 | 0.00 | 0.959634E+10 | 0.742303E+10 | 22353.41 | 14-JUN-08:62 | 22353.41 | 0.57 |
July | 0.00 | 0.00 | 0.118986E+11 | 0.778403E+10 | 23009.81 | 09-JUL-08:32 | 19725.34 | 0.79 |
August | 0.00 | 0.00 | 0.114266E+11 | 0.744597E+10 | 23405.98 | 13-AUG-08:32 | 19522.59 | 0.79 |
September | 0.00 | 0.00 | 0.848682E+10 | 0.568224E+10 | 21009.54 | 06-SEP-08:51 | 17664.81 | 0.66 |
October | 0.00 | 0.00 | 0.549853E+10 | 0.444914E+10 | 20276.20 | 02-OCT-21:51 | 16724.52 | 0.27 |
November | 0.00 | 0.00 | 0.230072E+10 | 0.221708E+10 | 18700.52 | 05-NOV-08:61 | 18700.52 | 0.04 |
December | 0.00 | 0.00 | 0.954661E+09 | 0.954661E+09 | 18680.09 | 29-DEC-09:01 | 18680.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.674727E+11 | 0.522404E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.954661E+09 | 0.954661E+09 | 18680.09 | 16724.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.118986E+11 | 0.778403E+10 | 23405.98 | 22353.41 | 0.79 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.204359E+09 | 0.204359E+09 | 17755.57 | 01-JAN-09:01 | 17755.57 | 0.00 |
February | 0.00 | 0.00 | 0.376451E+09 | 0.373098E+09 | 18525.76 | 19-FEB-09:01 | 18525.76 | 0.00 |
March | 0.00 | 0.00 | 0.132598E+10 | 0.131466E+10 | 18529.90 | 08-MAR-09:01 | 18529.90 | 0.01 |
April | 0.00 | 0.00 | 0.419186E+10 | 0.414734E+10 | 21400.87 | 27-APR-08:51 | 21400.87 | 0.01 |
May | 0.00 | 0.00 | 0.616557E+10 | 0.523193E+10 | 21412.59 | 14-MAY-08:51 | 21412.59 | 0.25 |
June | 0.00 | 0.00 | 0.955267E+10 | 0.740251E+10 | 22838.54 | 14-JUN-08:62 | 22838.54 | 0.57 |
July | 0.00 | 0.00 | 0.115589E+11 | 0.745071E+10 | 22784.17 | 09-JUL-08:32 | 19559.41 | 0.80 |
August | 0.00 | 0.00 | 0.104106E+11 | 0.644464E+10 | 23248.68 | 13-AUG-08:32 | 19314.70 | 0.79 |
September | 0.00 | 0.00 | 0.657121E+10 | 0.398807E+10 | 20663.63 | 02-SEP-08:32 | 20663.63 | 0.65 |
October | 0.00 | 0.00 | 0.310669E+10 | 0.223656E+10 | 19718.77 | 02-OCT-21:51 | 16061.18 | 0.25 |
November | 0.00 | 0.00 | 0.594949E+09 | 0.560628E+09 | 18516.70 | 12-NOV-09:01 | 18516.70 | 0.02 |
December | 0.00 | 0.00 | 0.126013E+09 | 0.126013E+09 | 17904.00 | 30-DEC-09:01 | 17904.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.541853E+11 | 0.394805E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.126013E+09 | 0.126013E+09 | 17755.57 | 16061.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115589E+11 | 0.745071E+10 | 23248.68 | 22838.54 | 0.80 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.286247E+09 | 0.286247E+09 | 6045.00 | 05-JAN-17:01 | 6045.00 | 0.00 |
February | 0.00 | 0.00 | 0.405061E+09 | 0.405029E+09 | 6432.46 | 15-FEB-18:01 | 6432.46 | 0.00 |
March | 0.00 | 0.00 | 0.537070E+09 | 0.537022E+09 | 6456.24 | 30-MAR-18:11 | 6456.24 | 0.00 |
April | 0.00 | 0.00 | 0.106231E+10 | 0.105226E+10 | 6462.49 | 25-APR-16:21 | 6462.49 | 0.01 |
May | 0.00 | 0.00 | 0.146589E+10 | 0.127912E+10 | 6360.73 | 06-MAY-19:41 | 6360.73 | 0.22 |
June | 0.00 | 0.00 | 0.233421E+10 | 0.179366E+10 | 6145.18 | 13-JUN-21:51 | 6145.18 | 0.53 |
July | 0.00 | 0.00 | 0.290012E+10 | 0.185683E+10 | 6754.48 | 31-JUL-21:51 | 4850.44 | 0.78 |
August | 0.00 | 0.00 | 0.283188E+10 | 0.180066E+10 | 6482.88 | 25-AUG-21:51 | 4504.93 | 0.77 |
September | 0.00 | 0.00 | 0.207472E+10 | 0.138044E+10 | 6259.08 | 05-SEP-21:51 | 4455.69 | 0.63 |
October | 0.00 | 0.00 | 0.122221E+10 | 0.969639E+09 | 6443.10 | 17-OCT-19:21 | 6443.10 | 0.25 |
November | 0.00 | 0.00 | 0.504682E+09 | 0.490186E+09 | 5601.85 | 02-NOV-15:01 | 5601.85 | 0.03 |
December | 0.00 | 0.00 | 0.234724E+09 | 0.234724E+09 | 5591.63 | 26-DEC-16:01 | 5591.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158591E+11 | 0.120858E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.234724E+09 | 0.234724E+09 | 5591.63 | 4455.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.290012E+10 | 0.185683E+10 | 6754.48 | 6462.49 | 0.78 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 49253723.38 | 49253723.38 | 5522.16 | 05-JAN-16:01 | 5522.16 | 0.00 |
February | 0.00 | 0.00 | 0.117427E+09 | 0.117427E+09 | 5524.32 | 17-FEB-16:01 | 5524.32 | 0.00 |
March | 0.00 | 0.00 | 0.234006E+09 | 0.233958E+09 | 6306.54 | 23-MAR-17:41 | 6306.54 | 0.00 |
April | 0.00 | 0.00 | 0.786903E+09 | 0.778111E+09 | 6384.11 | 25-APR-16:21 | 6384.11 | 0.01 |
May | 0.00 | 0.00 | 0.134957E+10 | 0.117198E+10 | 6271.86 | 06-MAY-19:41 | 6271.86 | 0.21 |
June | 0.00 | 0.00 | 0.232658E+10 | 0.179554E+10 | 6083.44 | 13-JUN-21:51 | 6083.44 | 0.52 |
July | 0.00 | 0.00 | 0.281275E+10 | 0.179034E+10 | 6649.52 | 31-JUL-21:51 | 4772.79 | 0.78 |
August | 0.00 | 0.00 | 0.256288E+10 | 0.156313E+10 | 6356.12 | 25-AUG-21:51 | 4389.15 | 0.77 |
September | 0.00 | 0.00 | 0.157387E+10 | 0.952410E+09 | 6121.24 | 05-SEP-21:51 | 4302.86 | 0.61 |
October | 0.00 | 0.00 | 0.638602E+09 | 0.452350E+09 | 6192.35 | 13-OCT-17:41 | 6192.35 | 0.22 |
November | 0.00 | 0.00 | 0.109665E+09 | 0.108015E+09 | 5533.78 | 02-NOV-15:01 | 5533.78 | 0.01 |
December | 0.00 | 0.00 | 25710156.24 | 25710156.24 | 5517.59 | 02-DEC-16:01 | 5517.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.125872E+11 | 0.903822E+10 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 25710156.24 | 25710156.24 | 5517.59 | 4302.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.281275E+10 | 0.179554E+10 | 6649.52 | 6384.11 | 0.78 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.654664E+10 | 0.654664E+10 | 25602.11 | 05-JAN-17:01 | 25602.11 | 0.00 |
February | 0.00 | 0.00 | 0.622860E+10 | 0.621579E+10 | 26378.66 | 14-FEB-19:01 | 26378.66 | 0.00 |
March | 0.00 | 0.00 | 0.554949E+10 | 0.552881E+10 | 26105.42 | 12-MAR-19:31 | 26105.42 | 0.01 |
April | 0.00 | 0.00 | 0.583525E+10 | 0.577441E+10 | 25852.95 | 12-APR-16:21 | 25852.95 | 0.02 |
May | 0.00 | 0.00 | 0.619210E+10 | 0.516683E+10 | 24039.41 | 11-MAY-21:51 | 24039.41 | 0.24 |
June | 0.00 | 0.00 | 0.913294E+10 | 0.657180E+10 | 24146.35 | 18-JUN-08:51 | 24146.35 | 0.55 |
July | 0.00 | 0.00 | 0.130089E+11 | 0.802690E+10 | 27010.40 | 31-JUL-21:51 | 19561.54 | 0.78 |
August | 0.00 | 0.00 | 0.139324E+11 | 0.911012E+10 | 26576.85 | 25-AUG-21:51 | 18554.28 | 0.77 |
September | 0.00 | 0.00 | 0.127596E+11 | 0.911253E+10 | 25866.03 | 05-SEP-21:51 | 19246.27 | 0.67 |
October | 0.00 | 0.00 | 0.111738E+11 | 0.969651E+10 | 26604.89 | 18-OCT-21:51 | 26604.89 | 0.31 |
November | 0.00 | 0.00 | 0.864285E+10 | 0.843311E+10 | 23008.19 | 01-NOV-15:01 | 23008.19 | 0.07 |
December | 0.00 | 0.00 | 0.726257E+10 | 0.726257E+10 | 22987.11 | 29-DEC-09:01 | 22987.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.106265E+12 | 0.874460E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.554949E+10 | 0.516683E+10 | 22987.11 | 18554.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139324E+11 | 0.969651E+10 | 27010.40 | 26604.89 | 0.78 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 22976.70 | 170238.75 | 21-JAN-19:02 |
February | 0.17 | 475.91 | 01-FEB-14:50 | 19914.22 | 148044.66 | 16-FEB-23:17 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11888.33 | 142573.35 | 03-MAR-05:22 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6774.25 | 132096.08 | 05-APR-04:48 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 2140.47 | 118762.70 | 06-MAY-04:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 162.02 | 75881.46 | 09-JUN-04:27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12.15 | 20923.71 | 12-JUL-21:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13.38 | 20797.23 | 16-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 150.40 | 40092.25 | 25-SEP-21:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7107.94 | 143234.00 | 27-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 16325.63 | 156502.96 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26988.10 | 174436.88 | 04-DEC-19:02 |
Annual Sum or Average | 0.01 | 9492.89 | ||||
Minimum of Months | 0.00 | 0.00 | 12.15 | 20797.23 | ||
Maximum of Months | 0.17 | 475.91 | 26988.10 | 174436.88 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16086.80 | 137665.04 | 01-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20639.52 | 312553.50 | 14-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28502.46 | 333066.44 | 08-MAR-16:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 70929.81 | 450514.68 | 28-APR-18:01 | 0.00 | 0.00 | 01-APR-00:01 |
May | 112423.95 | 464979.32 | 18-MAY-18:01 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 194252.54 | 525128.25 | 28-JUN-18:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 256363.49 | 534279.00 | 21-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 234453.34 | 500856.27 | 13-AUG-08:52 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 166819.16 | 484288.42 | 20-SEP-18:01 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 84621.70 | 465163.62 | 06-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 25338.51 | 196635.83 | 02-NOV-18:11 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 16806.02 | 129230.64 | 31-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 102808.49 | 0.00 | ||||
Minimum of Months | 16086.80 | 129230.64 | 0.00 | 0.00 | ||
Maximum of Months | 256363.49 | 534279.00 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 27524.90 | 64100.13 | 02-JAN-21:41 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 27713.97 | 69314.49 | 21-FEB-07:51 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 27083.17 | 66469.89 | 19-MAR-07:41 |
April | 0.00 | 0.00 | 01-APR-00:01 | 25735.32 | 64382.31 | 06-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24059.15 | 55407.00 | 12-MAY-06:12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22495.66 | 49074.35 | 09-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21425.99 | 43712.38 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21220.27 | 43060.90 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21874.87 | 48103.48 | 27-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23189.59 | 55400.97 | 25-OCT-20:11 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 24829.27 | 61538.64 | 29-NOV-07:36 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26446.29 | 60336.21 | 17-DEC-09:41 |
Annual Sum or Average | 0.00 | 24447.88 | ||||
Minimum of Months | 0.00 | 0.00 | 21220.27 | 43060.90 | ||
Maximum of Months | 0.00 | 0.00 | 27713.97 | 69314.49 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.07 | 2194.93 | 01-JAN-00:10 | 1.07 |
February | 0.530997E+10 | 1.07 | 2194.93 | 01-FEB-00:10 | 1.07 |
March | 0.587890E+10 | 1.07 | 2194.93 | 01-MAR-00:05 | 1.07 |
April | 0.568926E+10 | 1.07 | 2194.93 | 01-APR-00:01 | 1.07 |
May | 0.587890E+10 | 1.07 | 2194.93 | 01-MAY-00:05 | 1.07 |
June | 0.568926E+10 | 1.06 | 2194.93 | 01-JUN-00:10 | 1.07 |
July | 0.587890E+10 | 1.06 | 2194.93 | 01-JUL-00:10 | 1.06 |
August | 0.587890E+10 | 1.06 | 2194.93 | 01-AUG-00:10 | 1.06 |
September | 0.568926E+10 | 1.06 | 2194.93 | 01-SEP-00:10 | 1.06 |
October | 0.587890E+10 | 1.06 | 2194.93 | 01-OCT-00:10 | 1.06 |
November | 0.568926E+10 | 1.07 | 2194.93 | 01-NOV-00:05 | 1.07 |
December | 0.587890E+10 | 1.07 | 2194.93 | 01-DEC-00:10 | 1.07 |
Annual Sum or Average | 0.692193E+11 | 1.06 | |||
Minimum of Months | 0.530997E+10 | 1.06 | 2194.93 | 1.06 | |
Maximum of Months | 0.587890E+10 | 1.07 | 2194.93 | 1.07 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.347750E+11 | 0.89 | 49629.26 | 15-JAN-10:02 | 1.97 |
February | 0.317744E+11 | 0.89 | 49186.69 | 02-FEB-21:30 | 1.96 |
March | 0.362533E+11 | 0.91 | 49186.69 | 04-MAR-20:40 | 1.96 |
April | 0.368551E+11 | 0.93 | 45716.08 | 07-APR-07:35 | 1.87 |
May | 0.389213E+11 | 0.94 | 44239.07 | 05-MAY-05:07 | 1.83 |
June | 0.417892E+11 | 0.99 | 39736.30 | 23-JUN-21:10 | 1.69 |
July | 0.458456E+11 | 1.02 | 41650.09 | 21-JUL-21:10 | 1.75 |
August | 0.468678E+11 | 1.03 | 42913.07 | 18-AUG-21:10 | 1.78 |
September | 0.435500E+11 | 1.01 | 42965.47 | 13-SEP-21:10 | 1.79 |
October | 0.420147E+11 | 0.98 | 49629.26 | 29-OCT-08:58 | 1.97 |
November | 0.371139E+11 | 0.93 | 49629.26 | 06-NOV-08:55 | 1.97 |
December | 0.358937E+11 | 0.90 | 49629.26 | 09-DEC-12:15 | 1.97 |
Annual Sum or Average | 0.471654E+12 | 0.95 | |||
Minimum of Months | 0.317744E+11 | 0.89 | 39736.30 | 1.69 | |
Maximum of Months | 0.468678E+11 | 1.03 | 49629.26 | 1.97 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.32 | 76.61 | 01-JAN-00:10 | 0.32 |
February | 0.185347E+09 | 0.32 | 76.61 | 01-FEB-00:10 | 0.32 |
March | 0.205205E+09 | 0.32 | 76.61 | 01-MAR-00:05 | 0.32 |
April | 0.198586E+09 | 0.32 | 76.61 | 01-APR-00:01 | 0.32 |
May | 0.205205E+09 | 0.32 | 76.61 | 01-MAY-00:05 | 0.33 |
June | 0.198586E+09 | 0.32 | 76.61 | 01-JUN-00:10 | 0.32 |
July | 0.205205E+09 | 0.32 | 76.61 | 01-JUL-00:10 | 0.32 |
August | 0.205205E+09 | 0.32 | 76.61 | 01-AUG-00:10 | 0.32 |
September | 0.198586E+09 | 0.32 | 76.61 | 01-SEP-00:10 | 0.32 |
October | 0.205205E+09 | 0.32 | 76.61 | 01-OCT-00:10 | 0.32 |
November | 0.198586E+09 | 0.32 | 76.61 | 01-NOV-00:05 | 0.32 |
December | 0.205205E+09 | 0.32 | 76.61 | 01-DEC-00:10 | 0.32 |
Annual Sum or Average | 0.241613E+10 | 0.32 | |||
Minimum of Months | 0.185347E+09 | 0.32 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.32 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.32 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.32 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.32 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.32 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:05 | 0.32 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:10 | 0.32 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:10 | 0.32 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:10 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.32 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:05 | 0.32 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:05 | 0.32 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.32 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.314344E+09 | 0.56 | 1071.14 | 01-JAN-16:01 | 0.70 |
February | 0.259351E+09 | 0.56 | 1071.14 | 01-FEB-09:02 | 0.70 |
March | 0.207898E+09 | 0.53 | 1071.14 | 03-MAR-09:01 | 0.70 |
April | 0.243278E+09 | 0.51 | 1071.14 | 01-APR-15:01 | 0.70 |
May | 0.308423E+09 | 0.51 | 1071.14 | 01-MAY-08:62 | 0.70 |
June | 0.460545E+09 | 0.55 | 1071.14 | 01-JUN-08:51 | 0.70 |
July | 0.536559E+09 | 0.55 | 1071.14 | 01-JUL-08:51 | 0.69 |
August | 0.533930E+09 | 0.54 | 1071.14 | 01-AUG-08:31 | 0.69 |
September | 0.420187E+09 | 0.50 | 1071.14 | 01-SEP-08:51 | 0.69 |
October | 0.303156E+09 | 0.52 | 1071.14 | 01-OCT-08:61 | 0.70 |
November | 0.232090E+09 | 0.58 | 1071.14 | 01-NOV-08:62 | 0.70 |
December | 0.306036E+09 | 0.56 | 1071.14 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.412580E+10 | 0.54 | |||
Minimum of Months | 0.207898E+09 | 0.50 | 1071.14 | 0.69 | |
Maximum of Months | 0.536559E+09 | 0.58 | 1071.14 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.382127E+09 | 0.51 | 1059.97 | 01-JAN-09:01 | 0.70 |
February | 0.285297E+09 | 0.51 | 1059.97 | 01-FEB-09:02 | 0.70 |
March | 0.187401E+09 | 0.48 | 1059.97 | 03-MAR-09:01 | 0.70 |
April | 0.199355E+09 | 0.47 | 1059.97 | 01-APR-15:01 | 0.70 |
May | 0.288529E+09 | 0.49 | 1059.97 | 01-MAY-08:62 | 0.70 |
June | 0.459973E+09 | 0.55 | 1059.97 | 01-JUN-08:51 | 0.70 |
July | 0.522324E+09 | 0.55 | 1059.97 | 01-JUL-08:51 | 0.69 |
August | 0.483251E+09 | 0.53 | 1059.97 | 01-AUG-08:31 | 0.69 |
September | 0.327994E+09 | 0.48 | 1059.97 | 01-SEP-08:51 | 0.69 |
October | 0.213516E+09 | 0.46 | 1059.97 | 01-OCT-08:61 | 0.70 |
November | 0.225290E+09 | 0.51 | 1059.97 | 01-NOV-15:01 | 0.70 |
December | 0.404075E+09 | 0.52 | 1059.97 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.397913E+10 | 0.51 | |||
Minimum of Months | 0.187401E+09 | 0.46 | 1059.97 | 0.69 | |
Maximum of Months | 0.522324E+09 | 0.55 | 1059.97 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120997E+10 | 0.30 | 2817.36 | 03-JAN-12:40 | 0.70 |
February | 0.111614E+10 | 0.34 | 2820.81 | 14-FEB-13:00 | 0.70 |
March | 0.959095E+09 | 0.34 | 2376.87 | 08-MAR-13:30 | 0.70 |
April | 0.969043E+09 | 0.45 | 1488.03 | 13-APR-13:20 | 0.70 |
May | 0.861013E+09 | 0.45 | 1025.32 | 13-MAY-13:10 | 0.70 |
June | 0.123766E+10 | 0.57 | 1254.50 | 29-JUN-14:50 | 0.70 |
July | 0.173849E+10 | 0.67 | 1339.26 | 23-JUL-13:30 | 0.70 |
August | 0.197133E+10 | 0.67 | 1745.49 | 22-AUG-13:30 | 0.70 |
September | 0.215422E+10 | 0.65 | 3197.28 | 28-SEP-13:30 | 0.70 |
October | 0.214274E+10 | 0.54 | 3202.92 | 01-OCT-13:30 | 0.70 |
November | 0.168777E+10 | 0.42 | 2843.53 | 20-NOV-12:10 | 0.70 |
December | 0.132389E+10 | 0.33 | 2849.89 | 31-DEC-13:35 | 0.70 |
Annual Sum or Average | 0.173713E+11 | 0.48 | |||
Minimum of Months | 0.861013E+09 | 0.30 | 1025.32 | 0.70 | |
Maximum of Months | 0.215422E+10 | 0.67 | 3202.92 | 0.70 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153966E+10 | 0.50 | 5777.27 | 01-JAN-16:01 | 0.70 |
February | 0.110461E+10 | 0.49 | 5777.27 | 01-FEB-09:02 | 0.70 |
March | 0.748749E+09 | 0.45 | 5777.27 | 04-MAR-16:01 | 0.70 |
April | 0.108125E+10 | 0.40 | 5777.27 | 01-APR-08:62 | 0.70 |
May | 0.168573E+10 | 0.39 | 5777.27 | 01-MAY-08:62 | 0.70 |
June | 0.270606E+10 | 0.47 | 5777.27 | 01-JUN-08:51 | 0.70 |
July | 0.308491E+10 | 0.49 | 5777.27 | 01-JUL-08:51 | 0.69 |
August | 0.268524E+10 | 0.44 | 5777.27 | 01-AUG-08:31 | 0.69 |
September | 0.171178E+10 | 0.36 | 5777.27 | 01-SEP-08:51 | 0.69 |
October | 0.102516E+10 | 0.40 | 5777.27 | 01-OCT-08:61 | 0.70 |
November | 0.859317E+09 | 0.49 | 5777.27 | 02-NOV-18:11 | 0.70 |
December | 0.172675E+10 | 0.50 | 5777.27 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.199592E+11 | 0.45 | |||
Minimum of Months | 0.748749E+09 | 0.36 | 5777.27 | 0.69 | |
Maximum of Months | 0.308491E+10 | 0.50 | 5777.27 | 0.70 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.298780E+09 | 0.57 | 946.91 | 01-JAN-09:01 | 0.70 |
February | 0.243195E+09 | 0.55 | 946.91 | 01-FEB-19:02 | 0.70 |
March | 0.226749E+09 | 0.56 | 946.91 | 02-MAR-09:01 | 0.70 |
April | 0.292276E+09 | 0.56 | 946.91 | 01-APR-08:62 | 0.70 |
May | 0.347208E+09 | 0.55 | 946.91 | 01-MAY-08:62 | 0.70 |
June | 0.495215E+09 | 0.58 | 946.91 | 01-JUN-08:51 | 0.70 |
July | 0.576637E+09 | 0.57 | 946.91 | 01-JUL-08:51 | 0.69 |
August | 0.553945E+09 | 0.55 | 946.91 | 01-AUG-08:31 | 0.69 |
September | 0.426920E+09 | 0.52 | 946.91 | 01-SEP-08:32 | 0.69 |
October | 0.319123E+09 | 0.54 | 946.91 | 01-OCT-08:61 | 0.70 |
November | 0.229397E+09 | 0.59 | 946.91 | 01-NOV-08:62 | 0.70 |
December | 0.289523E+09 | 0.53 | 946.91 | 02-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.429897E+10 | 0.56 | |||
Minimum of Months | 0.226749E+09 | 0.52 | 946.91 | 0.69 | |
Maximum of Months | 0.576637E+09 | 0.59 | 946.91 | 0.70 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.352312E+09 | 0.52 | 938.59 | 01-JAN-09:01 | 0.70 |
February | 0.259936E+09 | 0.49 | 938.59 | 01-FEB-09:02 | 0.70 |
March | 0.184560E+09 | 0.48 | 938.59 | 02-MAR-09:01 | 0.70 |
April | 0.243406E+09 | 0.54 | 938.59 | 01-APR-08:62 | 0.70 |
May | 0.325997E+09 | 0.55 | 938.59 | 01-MAY-08:62 | 0.70 |
June | 0.495554E+09 | 0.58 | 938.59 | 01-JUN-08:51 | 0.70 |
July | 0.561796E+09 | 0.57 | 938.59 | 01-JUL-08:51 | 0.69 |
August | 0.504068E+09 | 0.55 | 938.59 | 01-AUG-08:31 | 0.69 |
September | 0.329328E+09 | 0.51 | 938.59 | 01-SEP-08:51 | 0.69 |
October | 0.214545E+09 | 0.49 | 938.59 | 01-OCT-08:61 | 0.70 |
November | 0.207062E+09 | 0.50 | 938.59 | 01-NOV-08:62 | 0.70 |
December | 0.365654E+09 | 0.51 | 938.59 | 02-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.404422E+10 | 0.52 | |||
Minimum of Months | 0.184560E+09 | 0.48 | 938.59 | 0.69 | |
Maximum of Months | 0.561796E+09 | 0.58 | 938.59 | 0.70 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100229E+09 | 0.56 | 283.71 | 01-JAN-16:01 | 0.70 |
February | 81354482.21 | 0.56 | 283.71 | 01-FEB-09:02 | 0.70 |
March | 64547567.22 | 0.53 | 283.71 | 03-MAR-09:01 | 0.70 |
April | 65294383.01 | 0.52 | 283.71 | 01-APR-15:01 | 0.70 |
May | 80378817.11 | 0.51 | 283.71 | 01-MAY-15:01 | 0.70 |
June | 0.121333E+09 | 0.55 | 283.71 | 01-JUN-08:51 | 0.70 |
July | 0.143500E+09 | 0.55 | 283.71 | 01-JUL-08:51 | 0.69 |
August | 0.141742E+09 | 0.54 | 283.71 | 01-AUG-08:31 | 0.69 |
September | 0.106800E+09 | 0.50 | 283.71 | 01-SEP-08:51 | 0.69 |
October | 79072670.04 | 0.52 | 283.71 | 01-OCT-08:61 | 0.69 |
November | 70798468.59 | 0.57 | 283.71 | 01-NOV-15:01 | 0.70 |
December | 98341700.77 | 0.57 | 283.71 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.115339E+10 | 0.54 | |||
Minimum of Months | 64547567.22 | 0.50 | 283.71 | 0.69 | |
Maximum of Months | 0.143500E+09 | 0.57 | 283.71 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120455E+09 | 0.53 | 280.27 | 01-JAN-09:01 | 0.70 |
February | 90384766.54 | 0.52 | 280.27 | 01-FEB-09:02 | 0.70 |
March | 62815881.03 | 0.48 | 280.27 | 01-MAR-09:02 | 0.70 |
April | 54474169.16 | 0.48 | 280.27 | 01-APR-15:01 | 0.70 |
May | 75265119.32 | 0.50 | 280.27 | 01-MAY-15:01 | 0.70 |
June | 0.121370E+09 | 0.55 | 280.27 | 01-JUN-08:51 | 0.70 |
July | 0.139236E+09 | 0.55 | 280.27 | 01-JUL-08:51 | 0.69 |
August | 0.128274E+09 | 0.53 | 280.27 | 01-AUG-08:31 | 0.69 |
September | 81533958.64 | 0.49 | 280.27 | 01-SEP-08:51 | 0.69 |
October | 58494820.82 | 0.46 | 280.27 | 01-OCT-08:61 | 0.69 |
November | 77238194.28 | 0.51 | 280.27 | 01-NOV-15:01 | 0.70 |
December | 0.126747E+09 | 0.55 | 280.27 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.113629E+10 | 0.51 | |||
Minimum of Months | 54474169.16 | 0.46 | 280.27 | 0.69 | |
Maximum of Months | 0.139236E+09 | 0.55 | 280.27 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.501673E+09 | 0.61 | 1162.47 | 01-JAN-09:01 | 0.70 |
February | 0.431611E+09 | 0.62 | 1162.47 | 01-FEB-16:01 | 0.70 |
March | 0.348833E+09 | 0.56 | 1162.47 | 01-MAR-16:02 | 0.70 |
April | 0.320892E+09 | 0.53 | 1162.47 | 01-APR-15:01 | 0.70 |
May | 0.330027E+09 | 0.51 | 1162.47 | 01-MAY-08:62 | 0.70 |
June | 0.465641E+09 | 0.54 | 1162.47 | 01-JUN-08:51 | 0.70 |
July | 0.615125E+09 | 0.55 | 1162.47 | 01-JUL-08:51 | 0.69 |
August | 0.666093E+09 | 0.54 | 1162.47 | 01-AUG-08:31 | 0.69 |
September | 0.658565E+09 | 0.51 | 1162.47 | 01-SEP-08:51 | 0.69 |
October | 0.611809E+09 | 0.54 | 1162.47 | 01-OCT-08:61 | 0.70 |
November | 0.507865E+09 | 0.63 | 1162.47 | 01-NOV-08:62 | 0.70 |
December | 0.527625E+09 | 0.62 | 1162.47 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.598576E+10 | 0.56 | |||
Minimum of Months | 0.320892E+09 | 0.51 | 1162.47 | 0.69 | |
Maximum of Months | 0.666093E+09 | 0.63 | 1162.47 | 0.70 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.647361E+09 | 0.582625E+09 | 803.05 | 21-JAN-19:02 | 722.75 | 722.75 | 34.00 | 1.57 |
February | 0.510246E+09 | 0.459222E+09 | 786.43 | 05-FEB-16:02 | 707.78 | 707.78 | 36.52 | 1.48 |
March | 0.334625E+09 | 0.301162E+09 | 790.25 | 03-MAR-01:30 | 711.23 | 711.23 | 58.43 | 1.48 |
April | 0.154842E+09 | 0.139358E+09 | 773.43 | 07-APR-03:40 | 696.09 | 696.09 | 54.86 | 1.41 |
May | 51003882.12 | 45903493.91 | 713.54 | 07-MAY-04:50 | 642.18 | 642.18 | 52.31 | 1.18 |
June | 4063335.57 | 3657002.01 | 608.85 | 09-JUN-04:22 | 547.97 | 547.97 | 40.35 | 0.89 |
July | 371477.71 | 334329.94 | 223.57 | 29-JUL-21:54 | 201.21 | 201.21 | 43.26 | 0.25 |
August | 515409.93 | 463868.94 | 282.68 | 16-AUG-08:54 | 254.41 | 254.41 | 44.76 | 0.33 |
September | 3556521.79 | 3200869.61 | 306.70 | 07-SEP-08:54 | 276.03 | 276.03 | 43.39 | 0.36 |
October | 0.192330E+09 | 0.173097E+09 | 813.53 | 26-OCT-08:62 | 732.18 | 732.18 | 46.19 | 1.62 |
November | 0.454485E+09 | 0.409036E+09 | 800.09 | 05-NOV-02:50 | 720.08 | 720.08 | 55.26 | 1.54 |
December | 0.750458E+09 | 0.675412E+09 | 810.98 | 14-DEC-16:03 | 729.88 | 729.88 | 43.59 | 1.61 |
Annual Sum or Average | 0.310386E+10 | 0.279347E+10 | ||||||
Minimum of Months | 371477.71 | 334329.94 | 223.57 | 201.21 | 201.21 | 34.00 | 0.25 | |
Maximum of Months | 0.750458E+09 | 0.675412E+09 | 813.53 | 732.18 | 732.18 | 58.43 | 1.62 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 20065961.96 | 18059365.77 | 94.74 | 01-JAN-16:01 | 85.26 | 85.26 | 6.72 | 5.05 |
February | 25738630.29 | 23164767.26 | 296.88 | 13-FEB-16:03 | 267.20 | 267.20 | 6.72 | 8.74 |
March | 40469591.38 | 36422632.24 | 366.48 | 08-MAR-16:01 | 329.83 | 329.83 | 6.72 | 9.62 |
April | 0.107129E+09 | 96416522.36 | 494.70 | 13-APR-18:01 | 445.23 | 445.23 | 6.72 | 11.00 |
May | 0.222791E+09 | 0.200512E+09 | 858.71 | 21-MAY-18:01 | 772.84 | 772.84 | 6.72 | 13.99 |
June | 0.582682E+09 | 0.524414E+09 | 1417.48 | 28-JUN-18:15 | 1275.73 | 1275.73 | 6.72 | 17.28 |
July | 0.875075E+09 | 0.787568E+09 | 1302.91 | 03-JUL-20:00 | 1172.62 | 1172.62 | 6.72 | 16.68 |
August | 0.884951E+09 | 0.796456E+09 | 1388.88 | 09-AUG-18:03 | 1250.00 | 1250.00 | 6.72 | 17.13 |
September | 0.541260E+09 | 0.487134E+09 | 1214.21 | 13-SEP-18:01 | 1092.79 | 1092.79 | 6.72 | 16.20 |
October | 0.192178E+09 | 0.172960E+09 | 1024.51 | 03-OCT-15:02 | 922.06 | 922.06 | 6.72 | 15.08 |
November | 34050158.00 | 30645142.20 | 224.54 | 02-NOV-18:11 | 202.08 | 202.08 | 6.72 | 7.68 |
December | 21262042.44 | 19135838.19 | 89.67 | 31-DEC-16:01 | 80.70 | 80.70 | 6.72 | 4.91 |
Annual Sum or Average | 0.354765E+10 | 0.319289E+10 | ||||||
Minimum of Months | 20065961.96 | 18059365.77 | 89.67 | 80.70 | 80.70 | 6.72 | 4.91 | |
Maximum of Months | 0.884951E+09 | 0.796456E+09 | 1417.48 | 1275.73 | 1275.73 | 6.72 | 17.28 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.535656E+10 | 0.482091E+10 | 3121.68 | 01-JAN-00:10 | 2809.52 | 2809.52 | 6.73 | 27.61 |
February | 0.542255E+10 | 0.488030E+10 | 3121.68 | 01-FEB-01:10 | 2809.52 | 2809.52 | 6.72 | 27.61 |
March | 0.696594E+10 | 0.626934E+10 | 3121.68 | 01-MAR-00:05 | 2809.52 | 2809.52 | 6.74 | 27.61 |
April | 0.779762E+10 | 0.701786E+10 | 3121.68 | 01-APR-00:01 | 2809.52 | 2809.52 | 6.74 | 27.61 |
May | 0.832366E+10 | 0.749130E+10 | 3121.68 | 01-MAY-00:05 | 2809.52 | 2809.52 | 7.05 | 27.61 |
June | 0.809060E+10 | 0.728154E+10 | 3121.68 | 01-JUN-00:10 | 2809.52 | 2809.52 | 7.68 | 27.61 |
July | 0.836112E+10 | 0.752501E+10 | 3121.68 | 01-JUL-00:10 | 2809.52 | 2809.52 | 8.39 | 27.61 |
August | 0.836112E+10 | 0.752501E+10 | 3121.68 | 01-AUG-00:10 | 2809.52 | 2809.52 | 8.62 | 27.61 |
September | 0.809141E+10 | 0.728227E+10 | 3121.68 | 01-SEP-00:10 | 2809.52 | 2809.52 | 8.38 | 27.61 |
October | 0.789812E+10 | 0.710830E+10 | 3121.68 | 01-OCT-00:10 | 2809.52 | 2809.52 | 7.58 | 27.61 |
November | 0.660372E+10 | 0.594335E+10 | 3121.68 | 01-NOV-00:05 | 2809.52 | 2809.52 | 6.95 | 27.61 |
December | 0.533815E+10 | 0.480433E+10 | 3121.68 | 01-DEC-00:10 | 2809.52 | 2809.52 | 6.73 | 27.61 |
Annual Sum or Average | 0.866106E+11 | 0.779495E+11 | ||||||
Minimum of Months | 0.533815E+10 | 0.480433E+10 | 3121.68 | 2809.52 | 2809.52 | 6.72 | 27.61 | |
Maximum of Months | 0.836112E+10 | 0.752501E+10 | 3121.68 | 2809.52 | 2809.52 | 8.62 | 27.61 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.62 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 49.09 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 45.13 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:01 | 14.37 | 14.37 | 51.04 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.96 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.06 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.59 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.36 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.27 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.48 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.28 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 49.95 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 45.13 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.59 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 45.14 | 60.00 | 22976.70 | 170238.75 | 21-JAN-19:02 |
February | 0.17 | 475.91 | 01-FEB-14:50 | 60.17 | 60.17 | 19914.22 | 148044.66 | 16-FEB-23:17 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.56 | 60.00 | 11888.33 | 142573.35 | 03-MAR-05:22 |
April | 0.00 | 0.00 | 01-APR-00:01 | 37.18 | 60.00 | 6774.25 | 132096.08 | 05-APR-04:48 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 35.52 | 35.52 | 2140.47 | 118762.70 | 06-MAY-04:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 31.58 | 31.58 | 162.02 | 75881.46 | 09-JUN-04:27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 34.40 | 12.15 | 20923.71 | 12-JUL-21:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 43.32 | 43.32 | 13.38 | 20797.23 | 16-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 44.57 | 44.57 | 150.40 | 40092.25 | 25-SEP-21:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 38.46 | 38.46 | 7107.94 | 143234.00 | 27-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 40.85 | 40.85 | 16325.63 | 156502.96 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 55.51 | 60.00 | 26988.10 | 174436.88 | 04-DEC-19:02 |
Annual Sum or Average | 0.01 | 9492.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 31.58 | 31.58 | 12.15 | 20797.23 | ||
Maximum of Months | 0.17 | 475.91 | 60.17 | 60.17 | 26988.10 | 174436.88 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16086.80 | 137665.04 | 01-JAN-16:01 | 7.89 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20639.52 | 312553.50 | 14-FEB-16:01 | 9.40 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28502.46 | 333066.44 | 08-MAR-16:01 | 9.58 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 70929.81 | 450514.68 | 28-APR-18:01 | 10.59 | 6.70 | 0.00 | 0.00 | 01-APR-00:01 |
May | 112423.95 | 464979.32 | 18-MAY-18:01 | 10.72 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 194252.54 | 525128.25 | 28-JUN-18:10 | 11.24 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 256363.49 | 534279.00 | 21-JUL-18:03 | 11.32 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 234453.34 | 500856.27 | 13-AUG-08:52 | 11.03 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 166819.16 | 484288.42 | 20-SEP-18:01 | 10.89 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 84621.70 | 465163.62 | 06-OCT-15:01 | 10.72 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 25338.51 | 196635.83 | 02-NOV-18:11 | 8.40 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 16806.02 | 129230.64 | 31-DEC-16:01 | 7.82 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 102808.49 | 0.00 | ||||||
Minimum of Months | 16086.80 | 129230.64 | 7.82 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 256363.49 | 534279.00 | 11.32 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.62 | 59.43 | 27524.90 | 64100.13 | 02-JAN-21:41 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 49.09 | 58.94 | 27713.97 | 69314.49 | 21-FEB-07:51 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 45.13 | 59.41 | 27083.17 | 66469.89 | 19-MAR-07:41 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.04 | 58.71 | 25735.32 | 64382.31 | 06-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.96 | 58.56 | 24059.15 | 55407.00 | 12-MAY-06:12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.06 | 59.29 | 22495.66 | 49074.35 | 09-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.59 | 59.59 | 21425.99 | 43712.38 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.36 | 58.96 | 21220.27 | 43060.90 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.27 | 58.94 | 21874.87 | 48103.48 | 27-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.48 | 59.18 | 23189.59 | 55400.97 | 25-OCT-20:11 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.28 | 58.66 | 24829.27 | 61538.64 | 29-NOV-07:36 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 49.95 | 59.13 | 26446.29 | 60336.21 | 17-DEC-09:41 |
Annual Sum or Average | 0.00 | 24447.88 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.13 | 58.56 | 21220.27 | 43060.90 | ||
Maximum of Months | 0.00 | 0.00 | 53.59 | 59.59 | 27713.97 | 69314.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.329930E+11 | 0.00 | 0.216558E+10 | 0.347750E+11 | 0.00 | 0.00 |
February | 0.298915E+11 | 0.00 | 0.739146E+10 | 0.317744E+11 | 0.00 | 0.00 |
March | 0.261120E+11 | 0.00 | 0.241175E+11 | 0.362533E+11 | 0.00 | 0.00 |
April | 0.167410E+11 | 0.00 | 0.974810E+11 | 0.368551E+11 | 0.00 | 0.00 |
May | 0.540665E+10 | 0.00 | 0.182373E+12 | 0.389213E+11 | 0.00 | 0.00 |
June | 0.344234E+09 | 0.00 | 0.321926E+12 | 0.417892E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.444156E+12 | 0.458456E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.397825E+12 | 0.468678E+11 | 0.00 | 0.00 |
September | 0.281880E+09 | 0.00 | 0.257631E+12 | 0.435500E+11 | 0.00 | 0.00 |
October | 0.163807E+11 | 0.00 | 0.110679E+12 | 0.420147E+11 | 0.00 | 0.00 |
November | 0.321934E+11 | 0.00 | 0.426069E+10 | 0.371139E+11 | 0.00 | 0.00 |
December | 0.413393E+11 | 0.00 | 0.133015E+10 | 0.358937E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.201684E+12 | 0.00 | 0.185134E+13 | 0.471654E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.133015E+10 | 0.317744E+11 | 0.00 | 0.00 |
Maximum of Months | 0.413393E+11 | 0.00 | 0.444156E+12 | 0.468678E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.944939E+09 | 0.00 | 0.119142E+09 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.390013E+09 | 0.00 | 0.100795E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 14609749.89 | 0.00 | 0.393961E+10 | 0.587890E+10 | 0.00 | 0.00 |
April | 17464.88 | 0.00 | 0.151750E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 49244.77 | 0.00 | 0.282246E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 79480.58 | 0.00 | 0.460860E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 54221.10 | 0.00 | 0.682682E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 57322.84 | 0.00 | 0.596034E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 48409.84 | 0.00 | 0.382980E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 16084226.56 | 0.00 | 0.161610E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 26216283.49 | 0.00 | 0.449883E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.684177E+09 | 0.00 | 14984.70 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.207634E+10 | 0.00 | 0.277333E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 17464.88 | 0.00 | 14984.70 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.944939E+09 | 0.00 | 0.682682E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.347750E+11 | 0.216749E+10 | 0.329930E+11 | 0.375742E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317744E+11 | 0.739511E+10 | 0.298915E+11 | 0.286859E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362533E+11 | 0.241220E+11 | 0.261120E+11 | 0.168789E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368551E+11 | 0.974869E+11 | 0.167410E+11 | 0.611247E+11 | 771889.75 | 0.00 | 0.00 | 0.00 |
May | 0.389213E+11 | 0.182374E+12 | 0.540665E+10 | 0.243301E+11 | 0.480640E+09 | 0.00 | 0.00 | 0.00 |
June | 0.417892E+11 | 0.321926E+12 | 0.344234E+09 | 0.117974E+11 | 0.171943E+11 | 0.00 | 0.00 | 0.00 |
July | 0.458456E+11 | 0.444156E+12 | 0.00 | 0.978877E+10 | 0.242419E+11 | 0.00 | 0.00 | 0.00 |
August | 0.468678E+11 | 0.397825E+12 | 0.00 | 0.948810E+10 | 0.122764E+11 | 0.00 | 0.00 | 0.00 |
September | 0.435500E+11 | 0.257631E+12 | 0.281880E+09 | 0.787720E+10 | 0.213696E+10 | 0.00 | 0.00 | 0.00 |
October | 0.420147E+11 | 0.110681E+12 | 0.163807E+11 | 0.710108E+11 | 27053305.03 | 0.00 | 0.00 | 0.00 |
November | 0.371139E+11 | 0.427057E+10 | 0.321934E+11 | 0.179150E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358937E+11 | 0.134249E+10 | 0.413393E+11 | 0.377101E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471654E+12 | 0.185138E+13 | 0.201684E+12 | 0.158306E+13 | 0.563581E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317744E+11 | 0.134249E+10 | 0.00 | 0.787720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468678E+11 | 0.444156E+12 | 0.413393E+11 | 0.377101E+12 | 0.242419E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.119142E+09 | 0.944939E+09 | 0.758794E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.100795E+10 | 0.390013E+09 | 0.601750E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.393961E+10 | 14609749.89 | 0.410364E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.151750E+11 | 17464.88 | 0.181734E+11 | 0.151461E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.282246E+11 | 49244.77 | 0.747026E+10 | 0.779466E+09 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.460860E+11 | 79480.58 | 0.160432E+10 | 0.777882E+10 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.682682E+11 | 54221.10 | 89415448.96 | 0.166890E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.596034E+11 | 57322.84 | 0.123214E+09 | 0.114756E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.382980E+11 | 48409.84 | 0.986724E+09 | 0.315666E+10 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.161610E+11 | 16084226.56 | 0.209045E+11 | 0.371000E+09 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.449883E+09 | 26216283.49 | 0.484782E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 14984.70 | 0.684177E+09 | 0.798992E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.277333E+12 | 0.207634E+10 | 0.354820E+12 | 0.404020E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 14984.70 | 17464.88 | 89415448.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.682682E+11 | 0.944939E+09 | 0.798992E+11 | 0.166890E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.347750E+11 | 0.329930E+11 | 0.216558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317744E+11 | 0.298915E+11 | 0.739146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362533E+11 | 0.261120E+11 | 0.241175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368551E+11 | 0.167410E+11 | 0.974810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.389213E+11 | 0.540665E+10 | 0.182373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.417892E+11 | 0.344234E+09 | 0.321926E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.458456E+11 | 0.00 | 0.444156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.468678E+11 | 0.00 | 0.397825E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.435500E+11 | 0.281880E+09 | 0.257631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420147E+11 | 0.163807E+11 | 0.110679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371139E+11 | 0.321934E+11 | 0.426069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358937E+11 | 0.413393E+11 | 0.133015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471654E+12 | 0.201684E+12 | 0.185134E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317744E+11 | 0.00 | 0.133015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468678E+11 | 0.413393E+11 | 0.444156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.944939E+09 | 0.119142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.390013E+09 | 0.100795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 14609749.89 | 0.393961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 17464.88 | 0.151750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 49244.77 | 0.282246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 79480.58 | 0.460860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 54221.10 | 0.682682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 57322.84 | 0.596034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 48409.84 | 0.382980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 16084226.56 | 0.161610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 26216283.49 | 0.449883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.684177E+09 | 14984.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.207634E+10 | 0.277333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 17464.88 | 14984.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.944939E+09 | 0.682682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374237E+10 | 0.00 | 0.00 | 98809071.74 | 0.00 | 0.00 | 0.518251E+11 | 0.00 | 1.02 |
February | 0.123973E+11 | 0.00 | 0.00 | 54732296.12 | 0.00 | 0.00 | 0.342995E+11 | 0.00 | 0.97 |
March | 0.237828E+11 | 0.00 | 0.00 | 22831127.41 | 0.00 | 0.00 | 0.239307E+11 | 0.00 | 0.96 |
April | 0.194795E+11 | 0.00 | 0.00 | 17528264.97 | 0.00 | 0.00 | 0.197511E+11 | 0.00 | 0.99 |
May | 0.112596E+11 | 0.00 | 0.00 | 21760724.54 | 1148026.34 | 0.00 | 0.210923E+11 | 0.00 | 1.01 |
June | 0.221260E+10 | 37164865.82 | 0.00 | 35704066.06 | 0.358934E+09 | 0.00 | 0.176851E+11 | 0.00 | 0.98 |
July | 0.102948E+09 | 0.572909E+09 | 0.00 | 54466816.48 | 0.166622E+09 | 0.00 | 0.120089E+11 | 0.00 | 1.00 |
August | 0.136147E+09 | 0.219523E+09 | 0.00 | 75328995.49 | 34046840.06 | 0.00 | 0.176597E+11 | 0.00 | 1.09 |
September | 46412621.51 | 35129035.85 | 0.00 | 96249426.46 | 255814.54 | 0.00 | 0.319983E+11 | 0.00 | 1.25 |
October | 0.178371E+09 | 0.00 | 0.00 | 0.126369E+09 | 0.00 | 0.00 | 0.526605E+11 | 0.00 | 1.26 |
November | 0.267080E+09 | 0.00 | 0.00 | 0.138221E+09 | 0.00 | 0.00 | 0.622545E+11 | 0.00 | 1.15 |
December | 0.141649E+10 | 0.00 | 0.00 | 0.140781E+09 | 0.00 | 0.00 | 0.607636E+11 | 0.00 | 1.11 |
Annual Sum or Average | 0.750216E+11 | 0.864726E+09 | 0.00 | 0.882782E+09 | 0.561006E+09 | 0.00 | 0.405929E+12 | 0.00 | 1.07 |
Minimum of Months | 46412621.51 | 0.00 | 0.00 | 17528264.97 | 0.00 | 0.00 | 0.120089E+11 | 0.00 | 0.96 |
Maximum of Months | 0.237828E+11 | 0.572909E+09 | 0.00 | 0.140781E+09 | 0.358934E+09 | 0.00 | 0.622545E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.454413E+10 | 0.00 | 0.00 | 5511505.80 | 0.00 | 0.413093E+09 | 0.240830E+10 | 0.00 | 2.55 |
February | 0.407052E+10 | 0.00 | 0.00 | 5717285.27 | 0.00 | 0.120044E+09 | 0.236284E+10 | 0.00 | 2.56 |
March | 0.464372E+10 | 0.00 | 0.00 | 3952657.69 | 0.00 | 24644849.46 | 0.198000E+10 | 0.00 | 2.52 |
April | 0.367166E+10 | 0.00 | 0.00 | 3786280.60 | 0.00 | 765570.20 | 0.154959E+10 | 0.00 | 2.48 |
May | 0.329076E+10 | 155043.91 | 0.00 | 3305914.02 | 1449.47 | 161963.10 | 0.909367E+09 | 0.00 | 2.41 |
June | 0.166070E+10 | 71501252.05 | 0.00 | 3947132.83 | 32347.84 | 0.00 | 0.884393E+09 | 0.00 | 2.41 |
July | 0.469100E+09 | 0.129591E+09 | 0.00 | 5172350.33 | 467916.81 | 0.00 | 0.102212E+10 | 0.00 | 2.51 |
August | 0.652874E+09 | 55511474.57 | 0.00 | 8767142.39 | 64346.35 | 0.00 | 0.140204E+10 | 0.00 | 2.71 |
September | 0.144993E+10 | 10368547.25 | 0.00 | 10410064.97 | 0.00 | 0.00 | 0.200910E+10 | 0.00 | 2.98 |
October | 0.279513E+10 | 0.00 | 0.00 | 9725110.24 | 0.00 | 45337769.43 | 0.320997E+10 | 0.00 | 2.97 |
November | 0.427951E+10 | 0.00 | 0.00 | 6936347.02 | 0.00 | 4035702.84 | 0.328100E+10 | 0.00 | 2.61 |
December | 0.450782E+10 | 0.00 | 0.00 | 9053336.79 | 0.00 | 0.333854E+09 | 0.280195E+10 | 0.00 | 2.53 |
Annual Sum or Average | 0.360358E+11 | 0.267128E+09 | 0.00 | 76285127.93 | 566060.47 | 0.941937E+09 | 0.238207E+11 | 0.00 | 2.61 |
Minimum of Months | 0.469100E+09 | 0.00 | 0.00 | 3305914.02 | 0.00 | 0.00 | 0.884393E+09 | 0.00 | 2.41 |
Maximum of Months | 0.464372E+10 | 0.129591E+09 | 0.00 | 10410064.97 | 467916.81 | 0.413093E+09 | 0.328100E+10 | 0.00 | 2.98 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329156E+10 | 0.00 | 0.00 | 1419951.17 | 0.00 | 0.00 | 0.101466E+10 | 0.00 | 1.27 |
February | 0.265734E+10 | 0.00 | 0.00 | 1746346.02 | 0.00 | 0.00 | 0.125042E+10 | 0.00 | 1.29 |
March | 0.231199E+10 | 0.00 | 0.00 | 2216101.84 | 0.00 | 0.00 | 0.193134E+10 | 0.00 | 1.33 |
April | 0.117169E+10 | 0.00 | 0.00 | 3689104.11 | 0.00 | 0.00 | 0.247576E+10 | 0.00 | 1.46 |
May | 0.644985E+09 | 99944.36 | 0.00 | 4824451.00 | 969.20 | 0.00 | 0.240820E+10 | 0.00 | 1.51 |
June | 0.142005E+09 | 37574169.27 | 0.00 | 6170397.00 | 483946.43 | 0.00 | 0.185449E+10 | 0.00 | 1.55 |
July | 1293972.91 | 68790122.98 | 0.00 | 6935589.63 | 1143428.69 | 0.00 | 0.125898E+10 | 0.00 | 1.59 |
August | 12625694.29 | 22831238.79 | 0.00 | 8147046.52 | 700575.05 | 0.00 | 0.167724E+10 | 0.00 | 1.63 |
September | 53651318.66 | 3140384.23 | 0.00 | 7715480.10 | 0.00 | 0.00 | 0.258220E+10 | 0.00 | 1.67 |
October | 0.987942E+09 | 0.00 | 0.00 | 5021026.41 | 0.00 | 0.00 | 0.286547E+10 | 0.00 | 1.50 |
November | 0.227494E+10 | 0.00 | 0.00 | 2068672.74 | 0.00 | 0.00 | 0.206097E+10 | 0.00 | 1.27 |
December | 0.340981E+10 | 0.00 | 0.00 | 1392930.88 | 0.00 | 0.00 | 0.954850E+09 | 0.00 | 1.24 |
Annual Sum or Average | 0.169598E+11 | 0.132436E+09 | 0.00 | 51347097.43 | 2328919.37 | 0.00 | 0.223346E+11 | 0.00 | 1.44 |
Minimum of Months | 1293972.91 | 0.00 | 0.00 | 1392930.88 | 0.00 | 0.00 | 0.954850E+09 | 0.00 | 1.24 |
Maximum of Months | 0.340981E+10 | 68790122.98 | 0.00 | 8147046.52 | 1143428.69 | 0.00 | 0.286547E+10 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 471857.81 | 0.00 | 0.00 | 0.46 |
February | 0.299278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 322390.87 | 0.00 | 0.00 | 0.46 |
March | 0.321103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.259750E+10 | 0.00 | 0.00 | 75188.68 | 0.00 | 0.00 | 60774227.55 | 0.00 | 0.50 |
May | 0.187905E+10 | 0.00 | 0.00 | 770670.45 | 79000.84 | 0.00 | 0.329336E+09 | 0.00 | 0.51 |
June | 0.554802E+09 | 30908051.56 | 0.00 | 3750650.13 | 899839.01 | 0.00 | 0.885072E+09 | 0.00 | 0.55 |
July | 2052032.51 | 56821299.90 | 0.00 | 5528253.67 | 524562.44 | 0.00 | 0.928024E+09 | 0.00 | 0.58 |
August | 92777061.54 | 16284166.42 | 0.00 | 5339048.94 | 2391156.93 | 0.00 | 0.109855E+10 | 0.00 | 0.56 |
September | 0.887050E+09 | 912320.79 | 0.00 | 2063560.20 | 1522669.35 | 0.00 | 0.888790E+09 | 0.00 | 0.54 |
October | 0.250977E+10 | 0.00 | 0.00 | 371891.70 | 0.00 | 0.00 | 0.235437E+09 | 0.00 | 0.50 |
November | 0.328881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
December | 0.337689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155133.83 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.247145E+11 | 0.104926E+09 | 0.00 | 17899263.78 | 5417228.57 | 949382.51 | 0.442598E+10 | 0.00 | 0.50 |
Minimum of Months | 2052032.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.337689E+10 | 56821299.90 | 0.00 | 5528253.67 | 2391156.93 | 471857.81 | 0.109855E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138602E+09 | 0.00 | 0.00 | 0.53 |
February | 0.197273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20015441.03 | 0.00 | 0.00 | 0.54 |
March | 0.213783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
April | 0.176980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.142694E+10 | 0.00 | 0.00 | 29339.35 | 52597.03 | 0.00 | 30822409.59 | 0.00 | 0.58 |
June | 0.613084E+09 | 18135098.84 | 0.00 | 1227247.11 | 1747940.49 | 0.00 | 0.281984E+09 | 0.00 | 0.58 |
July | 83741336.29 | 33297520.24 | 0.00 | 2012512.81 | 2146399.76 | 0.00 | 0.447702E+09 | 0.00 | 0.58 |
August | 0.273466E+09 | 8392922.70 | 0.00 | 1652660.51 | 3567279.78 | 0.00 | 0.432174E+09 | 0.00 | 0.58 |
September | 0.992595E+09 | 295012.76 | 0.00 | 193814.90 | 1326150.52 | 0.00 | 0.137412E+09 | 0.00 | 0.59 |
October | 0.179511E+10 | 0.00 | 0.00 | 11574.13 | 0.00 | 0.00 | 22486917.34 | 0.00 | 0.57 |
November | 0.218962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
December | 0.221907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29296194.55 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.175474E+11 | 60120554.55 | 0.00 | 5127148.81 | 8840367.58 | 0.187914E+09 | 0.135258E+10 | 0.00 | 0.56 |
Minimum of Months | 83741336.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.221907E+10 | 33297520.24 | 0.00 | 2012512.81 | 3567279.78 | 0.138602E+09 | 0.447702E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 91228899.81 | 0.00 | 0.00 | 0.185253E+09 | 0.00 | 0.00 | 0.751099E+11 | 0.00 | 21.33 |
February | 93865119.64 | 0.00 | 0.00 | 0.169157E+09 | 0.00 | 0.00 | 0.680035E+11 | 0.00 | 21.67 |
March | 0.667471E+09 | 0.00 | 0.00 | 0.163114E+09 | 0.00 | 0.00 | 0.730528E+11 | 0.00 | 22.52 |
April | 0.461769E+09 | 0.00 | 0.00 | 0.145745E+09 | 0.00 | 0.00 | 0.599387E+11 | 0.00 | 23.93 |
May | 0.217573E+09 | 1384973.32 | 0.00 | 0.139453E+09 | 0.00 | 0.00 | 0.491191E+11 | 0.00 | 24.09 |
June | 5608350.38 | 0.527368E+09 | 0.00 | 0.119696E+09 | 0.00 | 0.00 | 0.291467E+11 | 0.00 | 22.57 |
July | 0.00 | 0.975534E+09 | 0.00 | 0.107360E+09 | 0.00 | 0.00 | 0.164498E+11 | 0.00 | 21.99 |
August | 0.00 | 0.313356E+09 | 0.00 | 0.128769E+09 | 0.00 | 0.00 | 0.229526E+11 | 0.00 | 22.66 |
September | 0.00 | 42473493.79 | 0.00 | 0.135234E+09 | 0.00 | 0.00 | 0.387805E+11 | 0.00 | 24.50 |
October | 0.650259E+09 | 0.00 | 0.00 | 0.147638E+09 | 0.00 | 0.00 | 0.616669E+11 | 0.00 | 23.68 |
November | 0.625972E+09 | 0.00 | 0.00 | 0.162427E+09 | 0.00 | 0.00 | 0.738245E+11 | 0.00 | 21.17 |
December | 0.217635E+09 | 0.00 | 0.00 | 0.197046E+09 | 0.00 | 0.00 | 0.761039E+11 | 0.00 | 21.08 |
Annual Sum or Average | 0.303138E+10 | 0.186012E+10 | 0.00 | 0.180089E+10 | 0.00 | 0.00 | 0.644149E+12 | 0.00 | 22.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107360E+09 | 0.00 | 0.00 | 0.164498E+11 | 0.00 | 21.08 |
Maximum of Months | 0.667471E+09 | 0.975534E+09 | 0.00 | 0.197046E+09 | 0.00 | 0.00 | 0.761039E+11 | 0.00 | 24.50 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.611663E+10 | 0.00 | 0.00 | 44816680.41 | 0.00 | 0.00 | 0.249821E+11 | 0.00 | 3.82 |
February | 0.392377E+10 | 0.00 | 0.00 | 45758040.44 | 0.00 | 0.00 | 0.241481E+11 | 0.00 | 3.88 |
March | 0.451306E+10 | 0.00 | 0.00 | 41326896.55 | 0.00 | 0.00 | 0.243203E+11 | 0.00 | 3.86 |
April | 0.269582E+10 | 0.00 | 0.00 | 42228523.47 | 0.00 | 0.00 | 0.208713E+11 | 0.00 | 3.96 |
May | 0.197926E+10 | 645484.74 | 0.00 | 38412265.55 | 0.00 | 0.00 | 0.170191E+11 | 0.00 | 3.88 |
June | 0.666075E+09 | 0.261016E+09 | 0.00 | 36101140.15 | 547331.74 | 0.00 | 0.114673E+11 | 0.00 | 3.89 |
July | 23225087.23 | 0.485523E+09 | 0.00 | 38686556.17 | 464585.08 | 0.00 | 0.772259E+10 | 0.00 | 4.08 |
August | 0.106390E+09 | 0.194224E+09 | 0.00 | 51002701.47 | 27315.25 | 0.00 | 0.103821E+11 | 0.00 | 4.35 |
September | 0.268836E+09 | 33918482.43 | 0.00 | 58625866.37 | 0.00 | 0.00 | 0.165463E+11 | 0.00 | 4.70 |
October | 0.219278E+10 | 0.00 | 0.00 | 59924708.54 | 0.00 | 0.00 | 0.250144E+11 | 0.00 | 4.59 |
November | 0.336393E+10 | 0.00 | 0.00 | 55417026.22 | 0.00 | 0.00 | 0.290334E+11 | 0.00 | 3.96 |
December | 0.541912E+10 | 0.00 | 0.00 | 58751134.52 | 0.00 | 0.00 | 0.269160E+11 | 0.00 | 3.82 |
Annual Sum or Average | 0.312689E+11 | 0.975327E+09 | 0.00 | 0.571052E+09 | 1039232.07 | 0.00 | 0.238423E+12 | 0.00 | 4.07 |
Minimum of Months | 23225087.23 | 0.00 | 0.00 | 36101140.15 | 0.00 | 0.00 | 0.772259E+10 | 0.00 | 3.82 |
Maximum of Months | 0.611663E+10 | 0.485523E+09 | 0.00 | 59924708.54 | 547331.74 | 0.00 | 0.290334E+11 | 0.00 | 4.70 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199576E+11 | 0.00 | 0.00 | 0.108109E+09 | 0.00 | 0.00 | 0.684607E+11 | 0.00 | 1.54 |
February | 0.149829E+11 | 0.00 | 0.00 | 0.113772E+09 | 0.00 | 0.00 | 0.658896E+11 | 0.00 | 1.58 |
March | 0.147282E+11 | 0.00 | 0.00 | 0.128787E+09 | 0.00 | 0.00 | 0.744797E+11 | 0.00 | 1.66 |
April | 0.794606E+10 | 0.00 | 0.00 | 0.131933E+09 | 0.00 | 0.00 | 0.696642E+11 | 0.00 | 1.81 |
May | 0.513327E+10 | 1962693.62 | 0.00 | 0.131224E+09 | 19032.97 | 0.00 | 0.604880E+11 | 0.00 | 1.87 |
June | 0.120251E+10 | 0.733079E+09 | 0.00 | 0.132758E+09 | 8274784.92 | 0.00 | 0.420131E+11 | 0.00 | 1.90 |
July | 45457373.52 | 0.137038E+10 | 0.00 | 0.138733E+09 | 10836171.45 | 0.00 | 0.273382E+11 | 0.00 | 1.95 |
August | 0.212201E+09 | 0.479492E+09 | 0.00 | 0.167228E+09 | 4413524.17 | 0.00 | 0.360646E+11 | 0.00 | 2.01 |
September | 0.256413E+09 | 69553510.20 | 0.00 | 0.180435E+09 | 0.00 | 0.00 | 0.565644E+11 | 0.00 | 2.09 |
October | 0.514508E+10 | 0.00 | 0.00 | 0.176677E+09 | 0.00 | 0.00 | 0.778664E+11 | 0.00 | 1.91 |
November | 0.928979E+10 | 0.00 | 0.00 | 0.145408E+09 | 0.00 | 0.00 | 0.836012E+11 | 0.00 | 1.60 |
December | 0.184093E+11 | 0.00 | 0.00 | 0.122101E+09 | 0.00 | 0.00 | 0.720088E+11 | 0.00 | 1.52 |
Annual Sum or Average | 0.973088E+11 | 0.265447E+10 | 0.00 | 0.167716E+10 | 23543513.51 | 0.00 | 0.734439E+12 | 0.00 | 1.79 |
Minimum of Months | 45457373.52 | 0.00 | 0.00 | 0.108109E+09 | 0.00 | 0.00 | 0.273382E+11 | 0.00 | 1.52 |
Maximum of Months | 0.199576E+11 | 0.137038E+10 | 0.00 | 0.180435E+09 | 10836171.45 | 0.00 | 0.836012E+11 | 0.00 | 2.09 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294851E+09 | 0.00 | 0.00 | 5219291.56 | 0.00 | 0.798435E+09 | 0.445387E+09 | 0.00 | 0.47 |
February | 0.265984E+09 | 0.00 | 0.00 | 6509766.70 | 0.00 | 0.600410E+09 | 0.520192E+09 | 0.00 | 0.47 |
March | 0.339777E+09 | 0.00 | 0.00 | 8880478.52 | 0.00 | 0.351301E+09 | 0.802703E+09 | 0.00 | 0.47 |
April | 0.290232E+09 | 322260.90 | 0.00 | 12771172.65 | 2619.11 | 64806730.28 | 0.876479E+09 | 0.00 | 0.47 |
May | 0.252522E+09 | 2691878.38 | 4029.57 | 14121255.60 | 242044.49 | 20872953.61 | 0.677008E+09 | 961.15 | 0.47 |
June | 0.130799E+09 | 47079905.94 | 3605.87 | 10319785.11 | 1172588.41 | 1772841.98 | 0.355454E+09 | 4827.17 | 0.47 |
July | 37314812.04 | 0.248474E+09 | 62828.32 | 2303615.75 | 24411232.50 | 12674.43 | 27816018.92 | 11935.21 | 0.47 |
August | 90207384.80 | 0.156164E+09 | 42284.37 | 5384303.65 | 12958386.73 | 138114.24 | 78226301.51 | 10265.51 | 0.47 |
September | 0.202822E+09 | 33703680.71 | 5404.46 | 13297785.00 | 2788403.48 | 947194.71 | 0.379813E+09 | 3349.50 | 0.47 |
October | 0.281524E+09 | 2663936.32 | 0.00 | 14472904.56 | 831209.17 | 0.116986E+09 | 0.826434E+09 | 0.00 | 0.47 |
November | 0.251590E+09 | 0.00 | 0.00 | 8548924.02 | 0.00 | 0.451538E+09 | 0.815142E+09 | 0.00 | 0.47 |
December | 0.294420E+09 | 0.00 | 0.00 | 5334138.36 | 0.00 | 0.802194E+09 | 0.451485E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.273204E+10 | 0.491100E+09 | 118152.60 | 0.107163E+09 | 42406483.89 | 0.320942E+10 | 0.625614E+10 | 31338.55 | 0.47 |
Minimum of Months | 37314812.04 | 0.00 | 0.00 | 2303615.75 | 0.00 | 12674.43 | 27816018.92 | 0.00 | 0.47 |
Maximum of Months | 0.339777E+09 | 0.248474E+09 | 62828.32 | 14472904.56 | 24411232.50 | 0.802194E+09 | 0.876479E+09 | 11935.21 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.410417E+09 | 0.00 | 0.00 | 1229193.91 | 0.00 | 0.103798E+10 | 94084377.81 | 0.00 | 0.47 |
February | 0.378682E+09 | 0.00 | 0.00 | 2233649.54 | 0.00 | 0.796392E+09 | 0.215625E+09 | 0.00 | 0.47 |
March | 0.440965E+09 | 0.00 | 0.00 | 4715071.73 | 0.00 | 0.545800E+09 | 0.511004E+09 | 0.00 | 0.47 |
April | 0.358800E+09 | 321284.67 | 0.00 | 10159705.84 | 3557.28 | 0.106550E+09 | 0.768634E+09 | 0.00 | 0.47 |
May | 0.272457E+09 | 2687030.98 | 3907.81 | 13277609.16 | 246548.14 | 23438122.41 | 0.655238E+09 | 1082.33 | 0.47 |
June | 0.133258E+09 | 47121472.93 | 4050.52 | 10307376.81 | 1123253.57 | 3053042.97 | 0.351668E+09 | 6495.90 | 0.47 |
July | 37310440.07 | 0.247646E+09 | 76051.62 | 2276606.08 | 25191544.01 | 14108.75 | 27838063.83 | 14875.57 | 0.47 |
August | 90651039.78 | 0.153543E+09 | 19550.99 | 5149354.52 | 15584245.47 | 148227.01 | 77987101.39 | 8677.80 | 0.47 |
September | 0.206519E+09 | 32165636.32 | 7078.63 | 11155905.99 | 4321499.57 | 953540.95 | 0.378182E+09 | 2347.03 | 0.47 |
October | 0.384103E+09 | 2308037.53 | 0.00 | 8950446.83 | 1186698.45 | 0.205683E+09 | 0.640536E+09 | 0.00 | 0.47 |
November | 0.406715E+09 | 0.00 | 0.00 | 2514175.88 | 0.00 | 0.752927E+09 | 0.364484E+09 | 0.00 | 0.47 |
December | 0.406559E+09 | 0.00 | 0.00 | 870378.54 | 0.00 | 0.107534E+10 | 70483428.39 | 0.00 | 0.47 |
Annual Sum or Average | 0.352644E+10 | 0.485792E+09 | 110639.57 | 72839474.82 | 47657346.50 | 0.454828E+10 | 0.415577E+10 | 33478.64 | 0.47 |
Minimum of Months | 37310440.07 | 0.00 | 0.00 | 870378.54 | 0.00 | 14108.75 | 27838063.83 | 0.00 | 0.47 |
Maximum of Months | 0.440965E+09 | 0.247646E+09 | 76051.62 | 13277609.16 | 25191544.01 | 0.107534E+10 | 0.768634E+09 | 14875.57 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110711E+11 | 0.00 | 0.00 | 0.119435E+09 | 0.00 | 0.107809E+09 | 0.963546E+10 | 0.00 | 0.53 |
February | 0.874814E+10 | 0.00 | 0.00 | 0.112008E+09 | 0.00 | 0.00 | 0.100290E+11 | 0.00 | 0.54 |
March | 0.923283E+10 | 0.00 | 0.00 | 85289920.67 | 0.00 | 0.00 | 0.110566E+11 | 0.00 | 0.54 |
April | 0.557981E+10 | 4405081.55 | 0.00 | 85485114.78 | 0.00 | 0.00 | 0.112061E+11 | 0.00 | 0.54 |
May | 0.463532E+10 | 39849032.54 | 0.00 | 78959581.53 | 0.00 | 0.00 | 0.836380E+10 | 0.00 | 0.54 |
June | 0.175661E+10 | 0.654375E+09 | 0.00 | 62321813.62 | 0.00 | 0.00 | 0.493819E+10 | 0.00 | 0.54 |
July | 38735155.64 | 0.369574E+10 | 0.00 | 23111869.22 | 5349533.29 | 0.00 | 0.852675E+09 | 0.00 | 0.54 |
August | 0.100565E+09 | 0.229328E+10 | 0.00 | 43690477.44 | 580464.80 | 0.00 | 0.221443E+10 | 0.00 | 0.54 |
September | 0.420348E+09 | 0.494919E+09 | 0.00 | 0.112375E+09 | 0.00 | 0.00 | 0.756044E+10 | 0.00 | 0.54 |
October | 0.363141E+10 | 47391038.13 | 0.00 | 0.154977E+09 | 0.00 | 0.00 | 0.130190E+11 | 0.00 | 0.54 |
November | 0.731121E+10 | 0.00 | 0.00 | 0.150842E+09 | 0.00 | 0.00 | 0.132403E+11 | 0.00 | 0.53 |
December | 0.105046E+11 | 0.00 | 0.00 | 0.160016E+09 | 0.00 | 0.00 | 0.103985E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.630307E+11 | 0.722996E+10 | 0.00 | 0.118851E+10 | 5929998.09 | 0.107809E+09 | 0.102515E+12 | 0.00 | 0.54 |
Minimum of Months | 38735155.64 | 0.00 | 0.00 | 23111869.22 | 0.00 | 0.00 | 0.852675E+09 | 0.00 | 0.53 |
Maximum of Months | 0.110711E+11 | 0.369574E+10 | 0.00 | 0.160016E+09 | 5349533.29 | 0.107809E+09 | 0.132403E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.600142E+10 | 0.00 | 0.00 | 10218529.56 | 0.00 | 0.106048E+11 | 0.432307E+10 | 0.00 | 0.53 |
February | 0.566855E+10 | 0.00 | 0.00 | 18735707.10 | 0.00 | 0.658518E+10 | 0.662184E+10 | 0.00 | 0.53 |
March | 0.675343E+10 | 0.00 | 0.00 | 49477262.29 | 0.00 | 0.931885E+09 | 0.126455E+11 | 0.00 | 0.53 |
April | 0.581644E+10 | 2948267.19 | 16761.99 | 88420751.79 | 1407677.69 | 41046143.77 | 0.109302E+11 | 33579.24 | 0.53 |
May | 0.434193E+10 | 32698533.74 | 102396.27 | 0.113593E+09 | 6975980.25 | 24883352.30 | 0.860125E+10 | 83018.93 | 0.54 |
June | 0.199780E+10 | 0.584092E+09 | 105050.55 | 89965960.78 | 70295619.77 | 6178525.52 | 0.466502E+10 | 61438.62 | 0.54 |
July | 0.506108E+09 | 0.309240E+10 | 417833.52 | 19411875.13 | 0.609216E+09 | 2826.82 | 0.389249E+09 | 70149.45 | 0.54 |
August | 0.123328E+10 | 0.176117E+10 | 440543.36 | 49983060.28 | 0.532811E+09 | 523770.45 | 0.107554E+10 | 69042.44 | 0.54 |
September | 0.292663E+10 | 0.211450E+09 | 218461.17 | 0.101073E+09 | 0.283273E+09 | 10769703.52 | 0.505690E+10 | 112263.82 | 0.54 |
October | 0.582558E+10 | 13658619.95 | 23757.04 | 74606187.10 | 33701056.10 | 0.737946E+09 | 0.101719E+11 | 20564.03 | 0.53 |
November | 0.624165E+10 | 0.00 | 0.00 | 27116498.26 | 0.00 | 0.369733E+10 | 0.107419E+11 | 0.00 | 0.53 |
December | 0.595380E+10 | 0.00 | 0.00 | 7596001.45 | 0.00 | 0.113290E+11 | 0.377855E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.532666E+11 | 0.569842E+10 | 1324803.90 | 0.650198E+09 | 0.153768E+10 | 0.339695E+11 | 0.790008E+11 | 450056.53 | 0.53 |
Minimum of Months | 0.506108E+09 | 0.00 | 0.00 | 7596001.45 | 0.00 | 2826.82 | 0.389249E+09 | 0.00 | 0.53 |
Maximum of Months | 0.675343E+10 | 0.309240E+10 | 440543.36 | 0.113593E+09 | 0.609216E+09 | 0.113290E+11 | 0.126455E+11 | 112263.82 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274754E+09 | 0.00 | 0.00 | 6688523.25 | 0.00 | 0.798044E+09 | 0.464406E+09 | 0.00 | 0.47 |
February | 0.274608E+09 | 0.00 | 0.00 | 6797009.50 | 0.00 | 0.601339E+09 | 0.510351E+09 | 0.00 | 0.47 |
March | 0.263236E+09 | 0.00 | 0.00 | 12336288.89 | 0.00 | 0.366929E+09 | 0.860160E+09 | 0.00 | 0.47 |
April | 0.178773E+09 | 319616.32 | 0.00 | 18287274.51 | 5263.69 | 87764586.57 | 0.959464E+09 | 0.00 | 0.47 |
May | 0.172579E+09 | 2772744.79 | 0.00 | 18938349.96 | 165988.12 | 19775207.03 | 0.753231E+09 | 180.69 | 0.47 |
June | 0.113186E+09 | 47758436.50 | 0.00 | 12889773.87 | 502490.89 | 391793.24 | 0.371877E+09 | 0.00 | 0.47 |
July | 37180540.87 | 0.253677E+09 | 9651.40 | 2255593.59 | 19270274.33 | 3551.79 | 28007434.90 | 3601.50 | 0.47 |
August | 88366698.49 | 0.159070E+09 | 3512.22 | 5776981.20 | 10101021.54 | 126740.37 | 79685684.15 | 814.38 | 0.47 |
September | 0.186282E+09 | 34429703.33 | 9477.49 | 15609130.97 | 2060024.99 | 526935.99 | 0.394462E+09 | 1632.34 | 0.47 |
October | 0.228174E+09 | 2730945.45 | 0.00 | 17143600.82 | 764200.04 | 0.125927E+09 | 0.868173E+09 | 0.00 | 0.47 |
November | 0.200897E+09 | 0.00 | 0.00 | 10799303.71 | 0.00 | 0.467261E+09 | 0.847863E+09 | 0.00 | 0.47 |
December | 0.334602E+09 | 0.00 | 0.00 | 5534255.82 | 0.00 | 0.816000E+09 | 0.397296E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.235264E+10 | 0.500758E+09 | 22641.11 | 0.133056E+09 | 32869263.60 | 0.328409E+10 | 0.653498E+10 | 6228.92 | 0.47 |
Minimum of Months | 37180540.87 | 0.00 | 0.00 | 2255593.59 | 0.00 | 3551.79 | 28007434.90 | 0.00 | 0.47 |
Maximum of Months | 0.334602E+09 | 0.253677E+09 | 9651.40 | 18938349.96 | 19270274.33 | 0.816000E+09 | 0.959464E+09 | 3601.50 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409486E+09 | 0.00 | 0.00 | 1606495.18 | 0.00 | 0.102664E+10 | 0.105980E+09 | 0.00 | 0.47 |
February | 0.412753E+09 | 0.00 | 0.00 | 2196297.46 | 0.00 | 0.781155E+09 | 0.196828E+09 | 0.00 | 0.47 |
March | 0.419777E+09 | 0.00 | 0.00 | 7190966.32 | 0.00 | 0.488099E+09 | 0.587418E+09 | 0.00 | 0.47 |
April | 0.221112E+09 | 318504.16 | 0.00 | 15199013.69 | 6337.78 | 0.115168E+09 | 0.892664E+09 | 0.00 | 0.47 |
May | 0.182038E+09 | 2756132.41 | 0.00 | 17961653.69 | 182256.18 | 23720123.26 | 0.740691E+09 | 180.67 | 0.47 |
June | 0.113206E+09 | 47761407.57 | 0.00 | 12898884.77 | 493865.35 | 399998.60 | 0.371782E+09 | 0.00 | 0.47 |
July | 37171762.32 | 0.253730E+09 | 9157.36 | 2233888.64 | 19184438.31 | 3551.37 | 28030016.38 | 4093.98 | 0.47 |
August | 88443119.06 | 0.158845E+09 | 1443.03 | 5523833.80 | 10306402.92 | 166021.54 | 79802748.30 | 2883.07 | 0.47 |
September | 0.189467E+09 | 34119356.44 | 6408.54 | 13105698.99 | 2366096.58 | 774628.20 | 0.393463E+09 | 4699.99 | 0.47 |
October | 0.321551E+09 | 2696051.87 | 0.00 | 10626749.97 | 798684.11 | 0.195332E+09 | 0.711762E+09 | 0.00 | 0.47 |
November | 0.446353E+09 | 0.00 | 0.00 | 3610807.80 | 0.00 | 0.701685E+09 | 0.374992E+09 | 0.00 | 0.47 |
December | 0.421486E+09 | 0.00 | 0.00 | 976764.10 | 0.00 | 0.103158E+10 | 99203373.06 | 0.00 | 0.47 |
Annual Sum or Average | 0.326284E+10 | 0.500226E+09 | 17008.93 | 93131054.41 | 33338081.23 | 0.436473E+10 | 0.458262E+10 | 11857.72 | 0.47 |
Minimum of Months | 37171762.32 | 0.00 | 0.00 | 976764.10 | 0.00 | 3551.37 | 28030016.38 | 0.00 | 0.47 |
Maximum of Months | 0.446353E+09 | 0.253730E+09 | 9157.36 | 17961653.69 | 19184438.31 | 0.103158E+10 | 0.892664E+09 | 4699.99 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141589E+09 | 0.00 | 0.00 | 0.52 |
February | 0.247850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.265896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
April | 0.215689E+11 | 0.00 | 0.00 | 188425.77 | 0.00 | 0.00 | 0.443058E+09 | 0.00 | 0.57 |
May | 0.164678E+11 | 78918.79 | 0.00 | 2826756.00 | 575264.67 | 0.00 | 0.167561E+10 | 0.00 | 0.57 |
June | 0.615936E+10 | 0.245158E+09 | 0.00 | 20479571.90 | 8940707.60 | 0.00 | 0.506325E+10 | 0.00 | 0.58 |
July | 0.376920E+09 | 0.454673E+09 | 0.00 | 31475390.00 | 6818798.35 | 0.00 | 0.638699E+10 | 0.00 | 0.59 |
August | 0.874802E+09 | 0.163833E+09 | 0.00 | 39653793.17 | 3554528.79 | 0.00 | 0.834055E+10 | 0.00 | 0.61 |
September | 0.498263E+10 | 22223828.51 | 0.00 | 28045352.68 | 0.00 | 0.00 | 0.967470E+10 | 0.00 | 0.62 |
October | 0.179206E+11 | 0.00 | 0.00 | 9892318.41 | 0.00 | 0.00 | 0.491365E+10 | 0.00 | 0.57 |
November | 0.272337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
December | 0.279624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2066760.28 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.202292E+12 | 0.885966E+09 | 0.00 | 0.132562E+09 | 19889299.42 | 0.143656E+09 | 0.364978E+11 | 0.00 | 0.56 |
Minimum of Months | 0.376920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.279624E+11 | 0.454673E+09 | 0.00 | 39653793.17 | 8940707.60 | 0.141589E+09 | 0.967470E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73178627.09 | 0.00 | 0.00 | 1135674.86 | 0.00 | 0.227039E+09 | 84619545.95 | 0.00 | 0.47 |
February | 67543666.13 | 0.00 | 0.00 | 1497874.47 | 0.00 | 0.173974E+09 | 0.105258E+09 | 0.00 | 0.47 |
March | 85849982.22 | 0.00 | 0.00 | 2021008.54 | 0.00 | 0.134604E+09 | 0.153191E+09 | 0.00 | 0.47 |
April | 73136495.99 | 80565.23 | 0.00 | 3026767.91 | 654.78 | 40474256.21 | 0.194435E+09 | 0.00 | 0.47 |
May | 63128120.65 | 671370.87 | 0.00 | 3447080.80 | 63200.34 | 17810717.72 | 0.156745E+09 | 157.19 | 0.47 |
June | 32835509.98 | 11808962.48 | 1257.18 | 2514636.65 | 254161.11 | 3499070.93 | 85737128.43 | 851.08 | 0.47 |
July | 9328703.01 | 62373834.49 | 11847.39 | 539906.93 | 5851380.10 | 1512.29 | 6991658.05 | 2951.57 | 0.47 |
August | 22555593.44 | 39110370.00 | 3558.15 | 1270631.63 | 3177134.62 | 37289.27 | 19625511.71 | 2706.68 | 0.47 |
September | 51074757.74 | 8419077.16 | 1686.93 | 3139778.49 | 703577.95 | 235151.11 | 94770341.74 | 867.50 | 0.47 |
October | 72030140.26 | 654441.46 | 0.00 | 3306179.87 | 219344.91 | 51477516.45 | 0.183041E+09 | 0.00 | 0.47 |
November | 65816893.68 | 0.00 | 0.00 | 1778699.58 | 0.00 | 0.153634E+09 | 0.160475E+09 | 0.00 | 0.47 |
December | 71163257.51 | 0.00 | 0.00 | 1184027.90 | 0.00 | 0.232911E+09 | 83100341.23 | 0.00 | 0.47 |
Annual Sum or Average | 0.687642E+09 | 0.123119E+09 | 18349.66 | 24862267.64 | 10269453.82 | 0.103570E+10 | 0.132799E+10 | 7534.02 | 0.47 |
Minimum of Months | 9328703.01 | 0.00 | 0.00 | 539906.93 | 0.00 | 1512.29 | 6991658.05 | 0.00 | 0.47 |
Maximum of Months | 85849982.22 | 62373834.49 | 11847.39 | 3447080.80 | 5851380.10 | 0.232911E+09 | 0.194435E+09 | 2951.57 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93522992.44 | 0.00 | 0.00 | 279702.83 | 0.00 | 0.273015E+09 | 19110722.42 | 0.00 | 0.47 |
February | 90181656.95 | 0.00 | 0.00 | 515986.04 | 0.00 | 0.219294E+09 | 38241632.07 | 0.00 | 0.47 |
March | 0.110614E+09 | 0.00 | 0.00 | 1085214.57 | 0.00 | 0.178201E+09 | 85720816.67 | 0.00 | 0.47 |
April | 88455797.95 | 80555.79 | 0.00 | 2366579.86 | 654.70 | 50277335.00 | 0.169936E+09 | 0.00 | 0.47 |
May | 67194277.10 | 667021.11 | 1025.59 | 3229939.53 | 66418.84 | 18888494.67 | 0.151790E+09 | 176.78 | 0.47 |
June | 33049414.29 | 11826823.26 | 1476.23 | 2511826.36 | 234240.10 | 3163979.35 | 85846528.89 | 1278.65 | 0.47 |
July | 9327610.02 | 62287588.64 | 9761.94 | 533519.80 | 5931413.50 | 1512.12 | 6997162.74 | 3254.16 | 0.47 |
August | 22571357.58 | 38654931.78 | 2612.56 | 1207902.58 | 3628832.25 | 30252.44 | 19674418.08 | 2437.54 | 0.47 |
September | 51686570.16 | 8056973.31 | 0.00 | 2583665.26 | 1066687.80 | 256241.52 | 94676068.83 | 479.28 | 0.47 |
October | 95727556.32 | 557297.07 | 0.00 | 1934963.49 | 316386.93 | 80978550.02 | 0.131177E+09 | 0.00 | 0.47 |
November | 0.103829E+09 | 0.00 | 0.00 | 506870.22 | 0.00 | 0.224607E+09 | 52717229.71 | 0.00 | 0.47 |
December | 86548991.51 | 0.00 | 0.00 | 177830.88 | 0.00 | 0.288055E+09 | 13531353.06 | 0.00 | 0.47 |
Annual Sum or Average | 0.852709E+09 | 0.122131E+09 | 14876.31 | 16934001.42 | 11244634.12 | 0.133677E+10 | 0.869419E+09 | 7626.41 | 0.47 |
Minimum of Months | 9327610.02 | 0.00 | 0.00 | 177830.88 | 0.00 | 1512.12 | 6997162.74 | 0.00 | 0.47 |
Maximum of Months | 0.110614E+09 | 62287588.64 | 9761.94 | 3229939.53 | 5931413.50 | 0.288055E+09 | 0.169936E+09 | 3254.16 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294331E+09 | 0.00 | 0.00 | 27918086.64 | 0.00 | 0.861687E+09 | 0.129574E+10 | 0.00 | 0.53 |
February | 0.242845E+09 | 0.00 | 0.00 | 25594908.09 | 0.00 | 0.625503E+09 | 0.134354E+10 | 0.00 | 0.53 |
March | 0.419671E+09 | 0.00 | 0.00 | 20255938.50 | 0.00 | 0.399772E+09 | 0.157376E+10 | 0.00 | 0.54 |
April | 0.419106E+09 | 513342.91 | 0.00 | 17946252.09 | 8454.13 | 0.143496E+09 | 0.141793E+10 | 0.00 | 0.54 |
May | 0.403429E+09 | 4227141.05 | 0.00 | 16917380.81 | 492823.51 | 57615223.08 | 0.107118E+10 | 290.22 | 0.54 |
June | 0.212159E+09 | 74828633.25 | 30386.52 | 11922751.36 | 2633944.20 | 2758436.09 | 0.573563E+09 | 19989.45 | 0.54 |
July | 59932153.07 | 0.398184E+09 | 171785.03 | 2742832.03 | 39987179.07 | 24572.55 | 45628770.08 | 64525.40 | 0.54 |
August | 0.145447E+09 | 0.250681E+09 | 68986.53 | 7202692.07 | 20944292.81 | 176780.85 | 0.126568E+09 | 21691.90 | 0.54 |
September | 0.324459E+09 | 54825854.45 | 3813.51 | 21335539.43 | 3792390.66 | 1079615.36 | 0.611788E+09 | 2752.81 | 0.54 |
October | 0.372060E+09 | 4399798.41 | 0.00 | 31894832.13 | 1213832.83 | 0.126727E+09 | 0.145997E+10 | 0.00 | 0.54 |
November | 0.228478E+09 | 0.00 | 0.00 | 32273379.63 | 0.00 | 0.390687E+09 | 0.180082E+10 | 0.00 | 0.53 |
December | 0.271508E+09 | 0.00 | 0.00 | 35726795.69 | 0.00 | 0.853128E+09 | 0.133464E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.339343E+10 | 0.787659E+09 | 274971.59 | 0.251731E+09 | 69072917.21 | 0.346265E+10 | 0.126551E+11 | 109249.77 | 0.54 |
Minimum of Months | 59932153.07 | 0.00 | 0.00 | 2742832.03 | 0.00 | 24572.55 | 45628770.08 | 0.00 | 0.53 |
Maximum of Months | 0.419671E+09 | 0.398184E+09 | 171785.03 | 35726795.69 | 39987179.07 | 0.861687E+09 | 0.180082E+10 | 64525.40 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159432E+10 | 0.00 | 0.00 | 88628828.95 | 0.00 | 0.00 | 0.459971E+11 | 0.00 | 4.22 |
February | 0.126093E+10 | 0.00 | 0.00 | 90003317.55 | 0.00 | 0.00 | 0.430706E+11 | 0.00 | 4.39 |
March | 0.393573E+09 | 0.00 | 0.00 | 0.110952E+09 | 0.00 | 0.00 | 0.505200E+11 | 0.00 | 4.79 |
April | 0.118563E+09 | 0.00 | 0.00 | 0.113903E+09 | 0.00 | 0.00 | 0.451551E+11 | 0.00 | 5.41 |
May | 12537284.34 | 1217918.77 | 0.00 | 0.111226E+09 | 0.00 | 0.00 | 0.392882E+11 | 0.00 | 5.74 |
June | 1482448.00 | 0.463811E+09 | 0.00 | 97778700.00 | 0.00 | 0.00 | 0.256920E+11 | 0.00 | 5.81 |
July | 0.00 | 0.834433E+09 | 0.00 | 89005395.59 | 0.00 | 0.00 | 0.157668E+11 | 0.00 | 5.83 |
August | 0.00 | 0.276090E+09 | 0.00 | 0.105109E+09 | 0.00 | 0.00 | 0.206668E+11 | 0.00 | 5.87 |
September | 0.00 | 33764659.73 | 0.00 | 0.105941E+09 | 0.00 | 0.00 | 0.320184E+11 | 0.00 | 5.93 |
October | 0.362357E+09 | 0.00 | 0.00 | 0.110072E+09 | 0.00 | 0.00 | 0.449834E+11 | 0.00 | 5.24 |
November | 0.104207E+10 | 0.00 | 0.00 | 97606313.80 | 0.00 | 0.00 | 0.485711E+11 | 0.00 | 4.37 |
December | 0.272878E+10 | 0.00 | 0.00 | 91366198.03 | 0.00 | 0.00 | 0.454278E+11 | 0.00 | 4.15 |
Annual Sum or Average | 0.751462E+10 | 0.160932E+10 | 0.00 | 0.121159E+10 | 0.00 | 0.00 | 0.457157E+12 | 0.00 | 5.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 88628828.95 | 0.00 | 0.00 | 0.157668E+11 | 0.00 | 4.15 |
Maximum of Months | 0.272878E+10 | 0.834433E+09 | 0.00 | 0.113903E+09 | 0.00 | 0.00 | 0.505200E+11 | 0.00 | 5.93 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.516761E+09 | 0.00 | 0.00 | 0.113311E+09 | 0.00 | 0.00 | 0.521208E+11 | 0.00 | 4.66 |
February | 0.389679E+09 | 0.00 | 0.00 | 0.111208E+09 | 0.00 | 0.00 | 0.485446E+11 | 0.00 | 4.85 |
March | 77484260.28 | 0.00 | 0.00 | 0.130039E+09 | 0.00 | 0.00 | 0.557920E+11 | 0.00 | 5.27 |
April | 40976359.40 | 0.00 | 0.00 | 0.127091E+09 | 0.00 | 0.00 | 0.490239E+11 | 0.00 | 5.87 |
May | 10550033.12 | 1317262.78 | 0.00 | 0.120663E+09 | 0.00 | 0.00 | 0.422184E+11 | 0.00 | 6.18 |
June | 1553178.25 | 0.496876E+09 | 0.00 | 0.104465E+09 | 0.00 | 0.00 | 0.272708E+11 | 0.00 | 6.19 |
July | 0.00 | 0.894045E+09 | 0.00 | 94403449.47 | 0.00 | 0.00 | 0.165738E+11 | 0.00 | 6.18 |
August | 0.00 | 0.296792E+09 | 0.00 | 0.111827E+09 | 0.00 | 0.00 | 0.217947E+11 | 0.00 | 6.22 |
September | 0.00 | 36451927.66 | 0.00 | 0.113415E+09 | 0.00 | 0.00 | 0.339958E+11 | 0.00 | 6.32 |
October | 0.176503E+09 | 0.00 | 0.00 | 0.123426E+09 | 0.00 | 0.00 | 0.487427E+11 | 0.00 | 5.65 |
November | 0.358280E+09 | 0.00 | 0.00 | 0.118199E+09 | 0.00 | 0.00 | 0.539958E+11 | 0.00 | 4.79 |
December | 0.114971E+10 | 0.00 | 0.00 | 0.117900E+09 | 0.00 | 0.00 | 0.520252E+11 | 0.00 | 4.58 |
Annual Sum or Average | 0.272149E+10 | 0.172548E+10 | 0.00 | 0.138595E+10 | 0.00 | 0.00 | 0.502099E+12 | 0.00 | 5.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 94403449.47 | 0.00 | 0.00 | 0.165738E+11 | 0.00 | 4.58 |
Maximum of Months | 0.114971E+10 | 0.894045E+09 | 0.00 | 0.130039E+09 | 0.00 | 0.00 | 0.557920E+11 | 0.00 | 6.32 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12551259.38 | 0.00 | 0.00 | 0.203974E+09 | 0.00 | 0.00 | 0.719639E+11 | 0.00 | 20.75 |
February | 6706781.03 | 0.00 | 0.00 | 0.187654E+09 | 0.00 | 0.00 | 0.655903E+11 | 0.00 | 21.24 |
March | 60180487.63 | 0.00 | 0.00 | 0.186179E+09 | 0.00 | 0.00 | 0.716242E+11 | 0.00 | 22.79 |
April | 31671002.91 | 0.00 | 0.00 | 0.172458E+09 | 0.00 | 0.00 | 0.590872E+11 | 0.00 | 24.53 |
May | 9671496.35 | 2228606.45 | 0.00 | 0.159955E+09 | 0.00 | 0.00 | 0.476359E+11 | 0.00 | 24.95 |
June | 0.00 | 0.762398E+09 | 0.00 | 0.133282E+09 | 0.00 | 0.00 | 0.274696E+11 | 0.00 | 23.96 |
July | 0.00 | 0.138820E+10 | 0.00 | 0.114511E+09 | 0.00 | 0.00 | 0.150577E+11 | 0.00 | 23.51 |
August | 0.00 | 0.490650E+09 | 0.00 | 0.144011E+09 | 0.00 | 0.00 | 0.214571E+11 | 0.00 | 23.94 |
September | 0.00 | 63493173.75 | 0.00 | 0.152889E+09 | 0.00 | 0.00 | 0.360960E+11 | 0.00 | 25.08 |
October | 57082056.13 | 0.00 | 0.00 | 0.175121E+09 | 0.00 | 0.00 | 0.598352E+11 | 0.00 | 23.83 |
November | 64609835.04 | 0.00 | 0.00 | 0.186254E+09 | 0.00 | 0.00 | 0.723328E+11 | 0.00 | 20.98 |
December | 23159220.06 | 0.00 | 0.00 | 0.223914E+09 | 0.00 | 0.00 | 0.728075E+11 | 0.00 | 20.32 |
Annual Sum or Average | 0.265632E+09 | 0.270697E+10 | 0.00 | 0.204020E+10 | 0.00 | 0.00 | 0.620957E+12 | 0.00 | 23.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114511E+09 | 0.00 | 0.00 | 0.150577E+11 | 0.00 | 20.32 |
Maximum of Months | 64609835.04 | 0.138820E+10 | 0.00 | 0.223914E+09 | 0.00 | 0.00 | 0.728075E+11 | 0.00 | 25.08 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365059E+09 | 0.00 | 0.00 | 1.02 |
February | 0.126869E+11 | 0.00 | 0.00 | 3664.53 | 0.00 | 52868940.84 | 18941318.55 | 0.00 | 1.03 |
March | 0.136202E+11 | 0.00 | 0.00 | 27335.48 | 0.00 | 0.00 | 67406299.46 | 0.00 | 1.05 |
April | 0.105249E+11 | 0.00 | 0.00 | 1864719.59 | 0.00 | 0.00 | 0.812535E+09 | 0.00 | 1.10 |
May | 0.764498E+10 | 346039.39 | 0.00 | 6542233.95 | 0.00 | 0.00 | 0.171267E+10 | 0.00 | 1.13 |
June | 0.326672E+10 | 0.180307E+09 | 0.00 | 12172019.97 | 0.00 | 0.00 | 0.246190E+10 | 0.00 | 1.19 |
July | 0.561918E+09 | 0.309464E+09 | 0.00 | 16059808.85 | 141602.40 | 0.00 | 0.282600E+10 | 0.00 | 1.24 |
August | 0.118857E+10 | 0.113799E+09 | 0.00 | 20100340.37 | 91040.36 | 0.00 | 0.340044E+10 | 0.00 | 1.25 |
September | 0.386978E+10 | 15838165.81 | 0.00 | 15057748.09 | 0.00 | 0.00 | 0.347777E+10 | 0.00 | 1.22 |
October | 0.980754E+10 | 0.00 | 0.00 | 6256133.12 | 0.00 | 0.00 | 0.186994E+10 | 0.00 | 1.12 |
November | 0.140045E+11 | 0.00 | 0.00 | 1453.23 | 0.00 | 301150.52 | 14387014.38 | 0.00 | 1.00 |
December | 0.141144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280983E+09 | 0.00 | 0.00 | 1.00 |
Annual Sum or Average | 0.105088E+12 | 0.619755E+09 | 0.00 | 78085457.18 | 232642.76 | 0.699212E+09 | 0.166620E+11 | 0.00 | 1.11 |
Minimum of Months | 0.561918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.141144E+11 | 0.309464E+09 | 0.00 | 20100340.37 | 141602.40 | 0.365059E+09 | 0.347777E+10 | 0.00 | 1.25 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:42:40
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.256031E+12 | 0.169502E+11 | 0.196003E+12 | 0.882522E+12 | 0.107515E+12 |
February | 0.325568E+12 | 0.141265E+11 | 0.161858E+12 | 0.745588E+12 | 0.108358E+12 |
March | 0.449550E+12 | 0.123093E+11 | 0.136780E+12 | 0.665916E+12 | 0.136917E+12 |
April | 0.564326E+12 | 0.854716E+10 | 0.922279E+11 | 0.475618E+12 | 0.270800E+12 |
May | 0.610433E+12 | 0.631121E+10 | 0.667056E+11 | 0.363444E+12 | 0.419557E+12 |
June | 0.570992E+12 | 0.311907E+10 | 0.291735E+11 | 0.195472E+12 | 0.685984E+12 |
July | 0.573725E+12 | 0.851574E+09 | 0.109324E+11 | 0.774673E+11 | 0.922903E+12 |
August | 0.547018E+12 | 0.203220E+10 | 0.248782E+11 | 0.144479E+12 | 0.843490E+12 |
September | 0.435933E+12 | 0.438770E+10 | 0.462825E+11 | 0.277944E+12 | 0.585825E+12 |
October | 0.347287E+12 | 0.891113E+10 | 0.998423E+11 | 0.512159E+12 | 0.327085E+12 |
November | 0.274175E+12 | 0.130082E+11 | 0.153171E+12 | 0.698304E+12 | 0.127028E+12 |
December | 0.232352E+12 | 0.172867E+11 | 0.203558E+12 | 0.899131E+12 | 0.115746E+12 |
Annual Sum or Average | 0.518739E+13 | 0.107841E+12 | 0.122141E+13 | 0.593804E+13 | 0.465121E+13 |
Minimum of Months | 0.232352E+12 | 0.851574E+09 | 0.109324E+11 | 0.774673E+11 | 0.107515E+12 |
Maximum of Months | 0.610433E+12 | 0.172867E+11 | 0.203558E+12 | 0.899131E+12 | 0.922903E+12 |