Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:42:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11705.96 | 1031.79 | 1031.79 |
Net Site Energy | 11705.96 | 1031.79 | 1031.79 |
Total Source Energy | 25700.19 | 2265.27 | 2265.27 |
Net Source Energy | 25700.19 | 2265.27 | 2265.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 682.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1840.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 869.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 488.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 123.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 201.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.76 | 2988.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6246.24 | 5459.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 682.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1840.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 869.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 488.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 123.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 201.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.76 | 2988.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 682.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1840.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 869.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 488.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 123.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 201.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.76 | 2988.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 224.15 | 323.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 226.67 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 550.56 | 481.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 224.15 | 323.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 226.67 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 550.56 | 481.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6246.244 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6246.244 | 100.00 |
Total On-Site and Utility Electric Sources | 6246.244 | 100.00 |
Total Electricity End Uses | 6246.244 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1155.41 | 50.35 |
Air to Air Heat Recovery for Heating | 1139.48 | 49.65 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2294.90 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 19.67 |
Time Setpoint Not Met During Occupied Cooling | 137.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7729.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.3255 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.5208 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.7005 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 11.5174 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.6875 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 9.7951 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.3255 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.5208 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.7005 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 11.5174 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.6875 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 9.7951 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 13.0243 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 5.0165 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-19:19 | 14-JAN-19:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 232452.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 180003.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 83438.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32090.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25808.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5523.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3752.21 | 251120.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1868.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 433675.71 | 567011.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 232452.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 180003.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 33453.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1786.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25808.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5523.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3752.21 | 251120.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1091.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 739.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5828.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2058.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1547.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 390.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 639.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.44 | 3239.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19781.85 | 5918.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 56.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 285.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1743.62 | 521.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 56.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 285.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1743.62 | 521.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.74 | 0.549605 | 0.520000 | 1.43 | 1.00 | 0.500000 | 0.000693 | 0.000076 | 1.43 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.327917 | 0.155858 | 0.520000 | 0.170517 | 0.520000 | 0.500000 | 0.002445 | 0.000033 | 0.170517 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.250480 | 0.236281 | 0.520000 | 0.130250 | 0.630083 | 0.500000 | 0.001612 | 0.000014 | 0.130250 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.203288 | 0.615645 | 0.520000 | 0.105710 | 1.00 | 0.500000 | 0.000619 | 0.000020 | 0.105710 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.133557 | 0.540642 | 0.520000 | 0.069450 | 1.00 | 0.500000 | 0.000705 | 0.000013 | 0.069450 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.39 | 0.069679 | 0.520000 | 1.76 | 0.520000 | 0.500000 | 0.021698 | 0.000098 | 1.76 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.41 | 0.101978 | 0.520000 | 0.733828 | 0.520000 | 0.500000 | 0.003736 | 0.000097 | 0.733828 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.73 | 0.210559 | 0.520000 | 2.46 | 0.561491 | 0.500000 | 0.001809 | 0.000259 | 2.46 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.52 | 0.780451 | 0.520000 | 0.790813 | 1.00 | 0.500000 | 0.000488 | 0.000124 | 0.790813 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.27 | 0.111443 | 0.520000 | 1.18 | 0.520000 | 0.500000 | 0.003419 | 0.000108 | 1.18 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.38 | 0.106353 | 0.520000 | 1.24 | 0.520000 | 0.500000 | 0.003582 | 0.000112 | 1.24 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.32 | 0.060956 | 0.520000 | 1.21 | 0.520000 | 0.500000 | 0.011242 | 0.000073 | 1.21 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.767882 | 0.408968 | 0.520000 | 0.399299 | 1.00 | 0.500000 | 0.000932 | 0.000076 | 0.399299 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8695.86 | 0.000076 | 183.21 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3762.85 | 0.000033 | 95.29 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1621.20 | 0.000014 | 36.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2284.32 | 0.000020 | 57.51 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1538.16 | 0.000013 | 38.99 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11240.37 | 0.000098 | 237.53 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11073.40 | 0.000097 | 257.43 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29638.01 | 0.000259 | 665.46 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6336.91 | 0.000055 | 181.09 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6349.78 | 0.000056 | 181.45 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 36302.91 | 0.000318 | 1037.39 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 36557.80 | 0.000320 | 1044.68 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6310.54 | 0.000055 | 180.33 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6323.43 | 0.000055 | 180.70 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14174.44 | 0.000124 | 340.78 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1917.97 | 0.000017 | 54.81 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1923.07 | 0.000017 | 54.95 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9167.58 | 0.000080 | 261.96 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12375.16 | 0.000108 | 273.16 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12797.76 | 0.000112 | 282.07 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8339.65 | 0.000073 | 177.19 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8684.35 | 0.000076 | 219.02 |
VAV WITH REHEAT HEATING COIL | 179689.55 | 0.001572 | 3032.80 |
FLR_3_DOAS HEATING COIL | 16512.40 | 0.000144 | 278.70 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.05 | 0.000055 | 0.000415 |
ROOM_2_FLR_3 FAN COIL | 1.03 | 0.000056 | 0.000411 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.44 | 0.000318 | 0.002497 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.79 | 0.000320 | 0.002779 |
ROOM_5_FLR_3 FAN COIL | 0.947529 | 0.000055 | 0.000378 |
ROOM_6_FLR_3 FAN COIL | 0.939595 | 0.000055 | 0.000375 |
ROOM_1_FLR_6 FAN COIL | 0.274686 | 0.000017 | 0.000109 |
ROOM_2_FLR_6 FAN COIL | 0.271546 | 0.000017 | 0.000108 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.25 | 0.000080 | 0.000504 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.05 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.03 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.44 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.79 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.947529 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.939595 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.274686 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.271546 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.25 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008691 | 12.80 | 0.008500 | 0.000415 | 1.05 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008693 | 12.80 | 0.008500 | 0.000411 | 1.03 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008602 | 12.80 | 0.008500 | 0.002497 | 6.44 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008809 | 12.80 | 0.008500 | 0.002779 | 6.79 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008711 | 12.80 | 0.008500 | 0.000378 | 0.947529 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008713 | 12.80 | 0.008500 | 0.000375 | 0.939595 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008681 | 12.80 | 0.008500 | 0.000109 | 0.274686 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008684 | 12.80 | 0.008500 | 0.000108 | 0.271546 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008750 | 12.80 | 0.008500 | 0.000504 | 1.25 | |
VAV WITH REHEAT COOLING COIL | 29.43 | 6.70 | 0.012194 | 10.92 | 0.008500 | 0.026222 | 22.32 | 734144.50 |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.003256 | 2.05 | 91161.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.67 | 11.67 | 22.45 | 11.67 | 22.32 | 22.32 | 0.300000 | 0.522879 | 22.32 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.32 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.32 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.026222 | 0.000018 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001572 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003256 | 0.000146 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000144 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.037054 | 6049.80 | |
HEATSYS1 PUMP | 0.003793 | 1142.43 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003793 | 0.455217 |
COOLSYS1 | 0.037054 | 4.45 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 433617.45 | 433617.45 | 0.003793 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.037054 | 4188.48 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.037054 | 1037416.05 | 1038031.28 | 118.34 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.325 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.705 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.521 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.901 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.700 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.390 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 11.517 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.897 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 20432.332 | 10.325 | 191.855 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20432.332 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.656 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.656 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.385 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.385 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 742.517 | 4.521 | 279.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 742.517 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 729.693 | 7.700 | 357.693 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 729.693 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2175.192 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2175.192 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 12673.066 | 9.688 | 30.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12673.066 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.470 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.470 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.496_SHGC_0.25 | 37 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.496_SHGC_0.25 | 38 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.16139 | 0.61164 | 0.61164 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.16139 | 0.61164 | 0.61164 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.8537E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0323E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1102 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3566E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1969E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.5953E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1080 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.9517E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1204 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3475E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9001E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.2853E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3109E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3137E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7873E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9610E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7300E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.9150E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3109E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3137E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7873E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9610E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7300E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.9150E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 36405.74442 | 36405.74442 | 2.74355 | 2.74355 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 28.93750 | 1.44633E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1433.83787 | 1433.83787 | 6.37449E-002 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4350.63304 | 4350.63304 | 0.32792 | 0.32792 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2895.62353 | 2895.62353 | 0.12873 | 0.12873 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3323.31373 | 3323.31373 | 0.25048 | 0.25048 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 32.43667 | 1.44697E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 958.78692 | 958.78692 | 4.26245E-002 | 9.17347E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2697.75428 | 2697.75428 | 0.20329 | 0.20329 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 31.17000 | 1.44674E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1746.84170 | 1746.84170 | 7.76586E-002 | 7.76586E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1772.36943 | 1772.36943 | 0.13356 | 0.13356 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1184.98859 | 1184.98859 | 5.26805E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44936.45552 | 44936.45552 | 3.38658 | 3.38658 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2287.71251 | 2287.71251 | 0.10170 | 0.10170 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18707.61449 | 18707.61449 | 1.41121 | 1.41121 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7340.78171 | 7340.78171 | 0.32634 | 0.67639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 62795.23327 | 62795.23327 | 4.73425 | 4.73425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17117.34822 | 17117.34822 | 0.76098 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10295.63406 | 10295.63406 | 1.04558 | 1.04558 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6337.07554 | 6337.07554 | 0.28337 | 0.28337 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10187.43382 | 10187.43382 | 1.03459 | 1.03459 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6349.95170 | 6349.95170 | 0.28394 | 0.28394 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 63440.60398 | 63440.60398 | 6.44218 | 6.44218 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 36303.37408 | 36303.37408 | 1.62340 | 1.62340 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 66851.20350 | 66851.20350 | 6.78904 | 6.78904 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 36558.26775 | 36558.26775 | 1.63479 | 1.63479 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9330.16403 | 9330.16403 | 0.94753 | 0.94753 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6310.70826 | 6310.70826 | 0.28219 | 0.28219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9252.03967 | 9252.03967 | 0.93959 | 0.93959 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6323.59269 | 6323.59269 | 0.28277 | 0.28277 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20180.55438 | 20180.55438 | 1.52079 | 1.52079 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10151.43104 | 10151.43104 | 0.45130 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2704.80013 | 2704.80013 | 0.27469 | 0.27469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44708E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1918.01579 | 1918.01579 | 8.57661E-002 | 8.57661E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2673.87710 | 2673.87710 | 0.27155 | 0.27155 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1923.12292 | 1923.12292 | 8.59945E-002 | 8.59945E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12312.49387 | 12312.49387 | 1.25041 | 1.25041 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9167.76734 | 9167.76734 | 0.40995 | 0.40995 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30054.56380 | 30054.56380 | 2.26774 | 2.26774 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6375.66752 | 6375.66752 | 0.28344 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31493.33875 | 31493.33875 | 2.37626 | 2.37626 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6511.20336 | 6511.20336 | 0.28946 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30739.69489 | 30739.69489 | 2.32272 | 2.32272 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2210.46638 | 2210.46638 | 9.82563E-002 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10189.62342 | 10189.62342 | 0.76788 | 0.76788 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6652.67125 | 6652.67125 | 0.29576 | 0.29576 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 433015.36 | 22.32263 | 22.32263 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 198447.45 | 7.39587 | 7.39587 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 18.36695 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 4.97217 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.74355 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54960 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.42665 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.93225E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.60752E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.42665 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8695.85746 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.60752E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 183.21275 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32792 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15586 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17052 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44454E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29191E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17052 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3762.85352 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29191E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 95.29307 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.25048 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23628 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13025 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63008 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61248E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41829E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13025 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1621.19616 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41829E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.56681 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20329 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61564 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10571 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.18863E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99842E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10571 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2284.31647 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99842E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 57.50824 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13356 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54064 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.94497E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.04718E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34565E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.94497E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1538.15635 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34565E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 38.99402 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.38658 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.96791E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.76102 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16979E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.83356E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.76102 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11240.36675 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.83356E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.52726 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41121 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10198 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73383 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.73608E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.68749E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73383 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11073.39660 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.68749E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 257.42524 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.73425 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21056 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.46181 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56149 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80947E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.59286E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.46181 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29638.00979 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.59286E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 665.45769 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04558 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.04558 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.54380E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.15012E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70363 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69073E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.15012E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.04558 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6336.90785 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.54380E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 181.08668 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.03459 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.03459 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.55507E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.10904E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70362 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69305E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.10904E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.03459 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6349.78369 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.55507E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 181.45453 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.44218 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.44218 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.17594E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.49725E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70441 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60233E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.49725E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.44218 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 36302.90588 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.17594E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1037.39492 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.78904 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.78904 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.19824E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.77926E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70355 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.80892E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.77926E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.78904 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 36557.79651 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.19824E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1044.67706 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94753 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.94753 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.52074E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.78110E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70359 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71092E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.78110E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94753 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6310.54121 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.52074E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 180.33340 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.93959 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.93959 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.53201E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.75129E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70358 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71278E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.75129E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.93959 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6323.42532 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.53201E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 180.70149 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.52079 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.78045 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79081 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.88179E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24004E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79081 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14174.44173 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24004E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 340.78022 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27469 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27469 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.67792E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.08761E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70364 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68146E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.08761E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27469 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1917.96676 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67792E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 54.80638 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27155 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27155 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.68239E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.07583E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70364 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68375E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.07583E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27155 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1923.07377 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68239E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 54.95228 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.25041 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.25041 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.02020E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.04084E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70346 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74974E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.04084E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.25041 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9167.57905 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.02020E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 261.96418 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26774 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11144 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17922 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41880E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08263E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17922 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12375.15724 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08263E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 273.16245 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.37626 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10635 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23566 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58241E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11960E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23566 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12797.75834 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11960E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.06817 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32272 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.09562E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20781 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12421E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.29589E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20781 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8339.65124 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.29589E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.18778 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76788 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40897 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39930 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.31614E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.59745E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39930 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8684.35435 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.59745E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 219.02478 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.67204 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.67204 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.44622 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.67204 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.32263 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.32263 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52288 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.32263 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.32263 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.42760 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92171 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.21938E-002 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 734144.50329 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.62219E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.32263 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 179689.55332 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57200E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3032.80095 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.32263 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.62219E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.81600E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.57200E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25606E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 16512.40431 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44458E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 278.69642 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.25606E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.46247E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44458E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.70541E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6049.80188 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.79347E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.45522 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.79347E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1142.42797 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 433617.45367 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 433617.45000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.79347E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.70541E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.44649 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.70541E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4188.48189 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.70541E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1037416.04878 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1038031.28000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 118.33557 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8740.49 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3778.67 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1628.91 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2293.97 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1544.61 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11297.90 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11124.60 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 29779.61 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6825.78 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6839.65 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 39103.39 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 39377.91 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6797.39 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6811.26 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14237.09 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2065.88 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2071.38 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9874.56 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12435.27 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12860.02 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8382.14 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8720.99 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 133638.59 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 12280.59 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 17715.33 | 14026.15 | 3689.18 | 0.79 | 2104.31 | 21.34 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17536.11 | 13881.97 | 3654.14 | 0.79 | 2082.84 | 21.13 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 107493.71 | 85651.45 | 21842.27 | 0.80 | 12810.72 | 129.93 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 117360.31 | 92164.31 | 25196.00 | 0.79 | 13895.07 | 140.93 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16109.32 | 12736.47 | 3372.85 | 0.79 | 1912.17 | 19.39 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15979.49 | 12632.17 | 3347.32 | 0.79 | 1896.63 | 19.24 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4646.68 | 3681.44 | 965.24 | 0.79 | 552.14 | 5.60 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4595.36 | 3640.18 | 955.17 | 0.79 | 545.99 | 5.54 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21397.98 | 16872.29 | 4525.69 | 0.79 | 2536.53 | 25.73 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 660744.61 | 427555.77 | 233188.84 | 0.65 | 80260.93 | 814.05 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64688.92 | 41041.02 | 23647.90 | 0.63 | 7608.06 | 77.17 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.6294377263E-002 | 3.8642590894E-002 | Fail | Pass | 2.6835269918E-002 | 8.0150947923E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2205153450E-003 | 1.0116304511E-003 | Pass | Pass | 0.3342839837 | 1.2328194121 | Pass | Fail |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8225458781E-002 | 4.4023023142E-002 | Fail | Pass | 4.1450438794E-002 | 0.1041772340 | Pass | Fail |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7978820494E-003 | 5.2127083418E-003 | Pass | Pass | 7.7985066300E-002 | 0.1513079378 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.6153093791E-004 | 6.6804875047E-004 | Pass | Pass | 0.1812090650 | 0.6538788767 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.6230172315E-002 | 0.2133236186 | Fail | Pass | 3.0180609961E-002 | 6.7173552700E-002 | Pass | Fail |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7134435184E-002 | 7.8428539600E-002 | Fail | Pass | 5.2730327054E-002 | 0.1083365297 | Pass | Fail |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0402924932E-002 | 5.5541437915E-002 | Fail | Pass | 3.8921191956E-002 | 9.6556926349E-002 | Pass | Fail |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3296819226E-002 | 0.2120676511 | Pass | Pass | 0.2950431241 | 1.3137791531 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.5003316022E-002 | 0.2176831501 | Pass | Pass | 0.2468219145 | 0.9834567227 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.1177588176E-002 | 3.7124343404E-002 | Pass | Pass | 0.2604442786 | 1.2196042734 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.8556351922E-002 | 7.3619010028E-002 | Pass | Pass | 0.1548290237 | 0.4752088703 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.2112715607E-002 | 0.2070783043 | Pass | Pass | 0.2538375278 | 1.0810449501 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3819504218E-002 | 0.2125707398 | Pass | Pass | 0.3175424643 | 1.5639113344 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0920551297E-003 | 2.6518256072E-003 | Pass | Pass | 6.7095949620E-002 | 0.1303642737 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.1432631126E-002 | 0.2698625872 | Pass | Pass | 0.1934739446 | 0.7879044788 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2135745246E-002 | 0.2730606468 | Pass | Pass | 0.2146378251 | 0.8431333596 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.6587859452E-002 | 0.1641144688 | Pass | Pass | 0.1660205309 | 0.5269478788 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.8634325908E-002 | 0.1437667233 | Fail | Pass | 3.3120893201E-002 | 7.3817298971E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.4206191318E-002 | 0.1345294853 | Fail | Pass | 3.2701399980E-002 | 7.7130309009E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1202679124 | 0.2197709995 | Fail | Pass | 4.5014846499E-002 | 7.2637907400E-002 | Pass | Fail |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.8223208874E-004 | 1.8402168276E-003 | Pass | Pass | 6.3017563323E-002 | 0.1879402101 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3010.77 | 34.80 | 444.12 | 1631.96 | 8279.97 | 13401.61 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.820 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.820 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.820 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.820 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.820 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.820 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.820 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.820 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.820 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.3255 | 1978.83 | 20432.33 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 188.94 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.5625 | 67.07 | 909.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.76 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.5625 | 77.67 | 1053.39 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 10.14 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.5208 | 164.24 | 742.52 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.17 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.7005 | 94.76 | 729.69 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 4.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 11.5174 | 188.86 | 2175.19 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.20 | 0.0000 | Y | 16.42 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.6875 | 1308.19 | 12673.07 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.70 | 0.0000 | Y | 99.21 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 9.7951 | 1863.81 | 18256.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.45 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 9.7951 | 1864.32 | 18261.31 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.49 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.23 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.18 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 9.7951 | 220.77 | 2162.52 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 15.45 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.07 | 0.0000 | Y | 35.90 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.07 | 0.0000 | Y | 35.90 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 13.0243 | 103.30 | 1345.47 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 9.4981 | 11345.29 | 107758.18 | 496.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.77 | 83.77 | 262.45 | |
Exterior Lighting Total | 16690.39 | 262.45 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 433617.45 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1038031.28 | 2.96 | 1038213.74 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11619.46 | 17715.33 | 14026.15 | 3689.18 | 0.79 | - | 2104.31 | 21.34 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11504.43 | 17536.11 | 13881.97 | 3654.14 | 0.79 | - | 2082.84 | 21.13 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 69917.75 | 107493.71 | 85651.45 | 21842.27 | 0.80 | - | 12810.72 | 129.93 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 77813.26 | 117360.31 | 92164.31 | 25196.00 | 0.79 | - | 13895.07 | 140.93 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10586.26 | 16109.32 | 12736.47 | 3372.85 | 0.79 | - | 1912.17 | 19.39 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10502.80 | 15979.49 | 12632.17 | 3347.32 | 0.79 | - | 1896.63 | 19.24 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3045.08 | 4646.68 | 3681.44 | 965.24 | 0.79 | - | 552.14 | 5.60 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3012.10 | 4595.36 | 3640.18 | 955.17 | 0.79 | - | 545.99 | 5.54 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14113.27 | 21397.98 | 16872.29 | 4525.69 | 0.79 | - | 2536.53 | 25.73 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 734144.50 | 660744.61 | 427555.77 | 233188.84 | 0.65 | - | 80260.93 | 814.05 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64688.92 | 41041.02 | 23647.90 | 0.63 | - | 7608.06 | 77.17 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8695.86 | 8740.49 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3762.85 | 3778.67 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1621.20 | 1628.91 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2284.32 | 2293.97 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1538.16 | 1544.61 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11240.37 | 11297.90 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11073.40 | 11124.60 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29638.01 | 29779.61 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6336.91 | 6825.78 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6349.78 | 6839.65 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 36302.91 | 39103.39 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 36557.80 | 39377.91 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6310.54 | 6797.39 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6323.43 | 6811.26 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14174.44 | 14237.09 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1917.97 | 2065.88 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1923.07 | 2071.38 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 9167.58 | 9874.56 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12375.16 | 12435.27 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12797.76 | 12860.02 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8339.65 | 8382.14 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8684.35 | 8720.99 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 179689.55 | 133638.59 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 16512.40 | 12280.59 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 735.70 | 703.64 | 1.00 | 1.19 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 727.97 | 703.64 | 1.00 | 1.19 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.44 | 4532.95 | 703.64 | 1.00 | 0.95 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.79 | 4777.01 | 703.64 | 1.00 | 0.95 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 666.72 | 703.64 | 1.00 | 1.21 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.94 | 661.13 | 703.64 | 1.00 | 1.21 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 193.28 | 703.64 | 1.00 | 1.78 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 191.07 | 703.64 | 1.00 | 1.79 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.25 | 879.84 | 703.64 | 1.00 | 1.15 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.32 | 50016.94 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.037054 | 6049.80 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003793 | 1142.43 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.037054 | 4188.48 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 36405.74 | 36405.74 | 18.40 | 2.744 | 2.744 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00916 | 28.94 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4350.63 | 4350.63 | 64.87 | 0.328 | 0.328 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00921 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3323.31 | 3323.31 | 42.79 | 0.250 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00943 | 32.44 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 2697.75 | 2697.75 | 16.43 | 0.203 | 0.203 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 24.00 | 24.00 | 0.00895 | 31.17 | 0.01447 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1772.37 | 1772.37 | 18.70 | 0.134 | 0.134 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00896 | 31.88 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44936.46 | 44936.46 | 575.82 | 3.387 | 3.387 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00856 | 34.02 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 18707.61 | 18707.61 | 99.05 | 1.411 | 1.411 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01028 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 62795.23 | 62795.23 | 48.00 | 4.734 | 4.734 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01008 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10295.63 | 10295.63 | 263.84 | 1.046 | 1.046 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00869 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10187.43 | 10187.43 | 261.10 | 1.035 | 1.035 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 63440.60 | 63440.60 | 2586.89 | 6.442 | 6.442 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00860 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 66851.20 | 66851.20 | 2725.22 | 6.789 | 6.789 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00881 | 34.02 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9330.16 | 9330.16 | 239.10 | 0.948 | 0.948 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00871 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9252.04 | 9252.04 | 237.13 | 0.940 | 0.940 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00871 | 31.26 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20180.55 | 20180.55 | 51.82 | 1.521 | 1.521 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00953 | 34.30 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2704.80 | 2704.80 | 69.31 | 0.275 | 0.275 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00868 | 33.07 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2673.88 | 2673.88 | 68.53 | 0.272 | 0.272 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00868 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12312.49 | 12312.49 | 501.92 | 1.250 | 1.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00875 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30054.56 | 30054.56 | 90.62 | 2.268 | 2.268 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01040 | 34.40 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 31493.34 | 31493.34 | 94.96 | 2.376 | 2.376 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01032 | 34.40 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30739.69 | 30739.69 | 297.56 | 2.323 | 2.323 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01011 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10189.62 | 10189.62 | 24.72 | 0.768 | 0.768 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00907 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1433.84 | 1433.84 | 0.72 | 0.064 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2895.62 | 2895.62 | 43.17 | 0.129 | 0.129 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 958.79 | 958.79 | 12.34 | 0.043 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00750 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1746.84 | 1746.84 | 10.64 | 0.078 | 0.078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00736 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1184.99 | 1184.99 | 12.51 | 0.053 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00745 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2287.71 | 2287.71 | 29.31 | 0.102 | 0.102 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00734 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 7340.78 | 7340.78 | 38.87 | 0.326 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00761 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17117.35 | 17117.35 | 13.08 | 0.761 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00753 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6337.08 | 6337.08 | 162.40 | 0.283 | 0.283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6349.95 | 6349.95 | 162.75 | 0.284 | 0.284 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 36303.37 | 36303.37 | 1480.33 | 1.623 | 1.623 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00757 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 36558.27 | 36558.27 | 1490.32 | 1.635 | 1.635 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00757 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6310.71 | 6310.71 | 161.72 | 0.282 | 0.282 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6323.59 | 6323.59 | 162.07 | 0.283 | 0.283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10151.43 | 10151.43 | 26.07 | 0.451 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00764 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1918.02 | 1918.02 | 49.15 | 0.086 | 0.086 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00761 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1923.12 | 1923.12 | 49.29 | 0.086 | 0.086 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00762 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9167.77 | 9167.77 | 373.73 | 0.410 | 0.410 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00763 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6375.67 | 6375.67 | 19.22 | 0.283 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00771 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 6511.20 | 6511.20 | 19.63 | 0.289 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00772 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2210.47 | 2210.47 | 21.40 | 0.098 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00667 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6652.67 | 6652.67 | 16.14 | 0.296 | 0.296 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00775 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.32 | 22.32 | 7.40 | 7.40 | 22.3226 | 11.6720 | 22.3226 | 0.5229 | 0.3000 |
FLR_3_DOAS | 18.37 | 2.05 | 4.97 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8695.857 | 8695.857 | 1.426646 | 0.00007608 | 183.213 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8695.86 | 8695.86 | 1.426646 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00796460 | 49.6445 | 1433.84 | 0.00 | 8744.55 | 8744.55 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3762.854 | 3762.854 | 0.170517 | 0.00003292 | 95.293 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 3762.85 | 3762.85 | 0.170517 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00756152 | 47.1639 | 2895.62 | 0.00 | 3782.18 | 3782.18 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1621.196 | 1621.196 | 0.130250 | 0.00001418 | 36.567 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1621.20 | 1621.20 | 0.130250 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00749526 | 46.7544 | 958.79 | 0.00 | 1629.95 | 1629.95 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2284.316 | 2284.316 | 0.105710 | 0.00001998 | 57.508 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2284.32 | 2284.32 | 0.105710 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00736201 | 45.9330 | 1746.84 | 0.00 | 2296.07 | 2296.07 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1538.156 | 1538.156 | 0.069450 | 0.00001346 | 38.994 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1538.16 | 1538.16 | 0.069450 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00744817 | 46.4643 | 1184.99 | 0.00 | 1546.05 | 1546.05 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11240.367 | 11240.367 | 1.761020 | 0.00009834 | 237.527 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 11240.37 | 11240.37 | 1.761020 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00733798 | 45.7859 | 2287.71 | 0.00 | 11303.25 | 11303.25 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11073.397 | 11073.397 | 0.733828 | 0.00009687 | 257.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 11073.40 | 11073.40 | 0.733828 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00761386 | 47.4861 | 7340.78 | 0.00 | 11132.58 | 11132.58 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29638.010 | 29638.010 | 2.461808 | 0.00025929 | 665.458 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 29638.01 | 29638.01 | 2.461808 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00753397 | 46.9933 | 17117.35 | 0.00 | 29798.36 | 29798.36 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11619.458 | -999.000 | 1.045575 | 0.00041501 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 11619.46 | 11123.73 | 1.045575 | 21.70 | 15.36 | 0.00869073 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00869073 | 53.7437 | 10295.63 | 0.00 | 12025.76 | 11290.31 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6336.908 | 6336.908 | 0.283369 | 0.00005544 | 181.087 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6336.91 | 6336.91 | 0.283369 | 21.11 | 14.12 | 0.00753948 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00753948 | 46.7088 | 6337.08 | 0.00 | 6831.34 | 6831.34 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11504.433 | -999.000 | 1.034587 | 0.00041090 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 11504.43 | 11007.89 | 1.034587 | 21.70 | 15.37 | 0.00869305 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00869305 | 53.7579 | 10187.43 | 0.00 | 11906.60 | 11172.59 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6349.784 | 6349.784 | 0.283945 | 0.00005555 | 181.455 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6349.78 | 6349.78 | 0.283945 | 21.11 | 14.12 | 0.00754038 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00754038 | 46.7142 | 6349.95 | 0.00 | 6845.22 | 6845.22 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 69917.745 | -999.000 | 6.442180 | 0.00249725 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 69917.75 | 68285.11 | 6.442180 | 21.70 | 15.29 | 0.00860233 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00860233 | 53.2023 | 63440.60 | 0.00 | 72390.56 | 69341.43 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 36302.906 | 36302.906 | 1.623396 | 0.00031759 | 1037.395 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 36302.91 | 36302.91 | 1.623396 | 21.11 | 14.15 | 0.00757126 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00757126 | 46.9022 | 36303.37 | 0.00 | 39135.64 | 39135.64 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 77813.255 | -999.000 | 6.789036 | 0.00277926 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 77813.26 | 72574.67 | 6.789036 | 21.70 | 15.47 | 0.00880892 | 12.80 | 11.77 | 0.00850000 | 34.02 | 0.01447257 | 23.44 | 0.0000 | 21.11 | 0.00880892 | 54.4642 | 66851.20 | 0.00 | 80521.22 | 73639.64 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 36557.797 | 36557.797 | 1.634795 | 0.00031982 | 1044.677 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 36557.80 | 36557.80 | 1.634795 | 21.11 | 14.15 | 0.00757392 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00757392 | 46.9185 | 36558.27 | 0.00 | 39410.42 | 39410.42 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10586.263 | -999.000 | 0.947529 | 0.00037811 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 10586.26 | 10089.05 | 0.947529 | 21.70 | 15.38 | 0.00871092 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00871092 | 53.8669 | 9330.16 | 0.00 | 10955.49 | 10239.04 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6310.541 | 6310.541 | 0.282190 | 0.00005521 | 180.333 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6310.54 | 6310.54 | 0.282190 | 21.11 | 14.12 | 0.00753772 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00753772 | 46.6979 | 6310.71 | 0.00 | 6802.91 | 6802.91 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10502.799 | -999.000 | 0.939595 | 0.00037513 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 10502.80 | 10005.34 | 0.939595 | 21.70 | 15.38 | 0.00871278 | 12.80 | 11.77 | 0.00850000 | 31.26 | 0.01446754 | 22.70 | 0.0000 | 21.11 | 0.00871278 | 53.8783 | 9252.04 | 0.00 | 10869.03 | 10153.99 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6323.425 | 6323.425 | 0.282766 | 0.00005532 | 180.701 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6323.43 | 6323.43 | 0.282766 | 21.11 | 14.12 | 0.00753861 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00753861 | 46.7034 | 6323.59 | 0.00 | 6816.80 | 6816.80 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14174.442 | 14174.442 | 0.790813 | 0.00012400 | 340.780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14174.44 | 14174.44 | 0.790813 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00764340 | 47.6670 | 10151.43 | 0.00 | 14248.50 | 14248.50 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3045.076 | -999.000 | 0.274686 | 0.00010876 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3045.08 | 2921.22 | 0.274686 | 21.70 | 15.36 | 0.00868146 | 12.80 | 11.77 | 0.00850000 | 33.07 | 0.01447082 | 23.19 | 0.0000 | 21.11 | 0.00868146 | 53.6872 | 2704.80 | 0.00 | 3151.68 | 2965.11 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1917.967 | 1917.967 | 0.085766 | 0.00001678 | 54.806 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1917.97 | 1917.97 | 0.085766 | 21.11 | 14.19 | 0.00761412 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00761412 | 47.1656 | 1918.02 | 0.00 | 2067.61 | 2067.61 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3012.098 | -999.000 | 0.271546 | 0.00010758 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 3012.10 | 2888.10 | 0.271546 | 21.70 | 15.36 | 0.00868375 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00868375 | 53.7011 | 2673.88 | 0.00 | 3117.52 | 2931.46 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1923.074 | 1923.074 | 0.085995 | 0.00001682 | 54.952 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1923.07 | 1923.07 | 0.085995 | 21.11 | 14.19 | 0.00761510 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00761510 | 47.1716 | 1923.12 | 0.00 | 2073.12 | 2073.12 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14113.271 | -999.000 | 1.250413 | 0.00050408 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 14113.27 | 13335.11 | 1.250413 | 21.70 | 15.42 | 0.00874974 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00874974 | 54.1039 | 12312.49 | 0.00 | 14603.10 | 13530.63 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9167.579 | 9167.579 | 0.409951 | 0.00008020 | 261.964 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 9167.58 | 9167.58 | 0.409951 | 21.11 | 14.20 | 0.00762733 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00762733 | 47.2461 | 9167.77 | 0.00 | 9882.89 | 9882.89 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12375.157 | 12375.157 | 1.179224 | 0.00010826 | 273.162 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12375.16 | 12375.16 | 1.179224 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770976 | 48.0761 | 6375.67 | 0.00 | 12442.56 | 12442.56 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12797.758 | 12797.758 | 1.235657 | 0.00011196 | 282.068 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12797.76 | 12797.76 | 1.235657 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00771550 | 48.1118 | 6511.20 | 0.00 | 12867.51 | 12867.51 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8339.651 | 8339.651 | 1.207814 | 0.00007296 | 177.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8339.65 | 8339.65 | 1.207814 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00666637 | 41.6462 | 2210.47 | 0.00 | 8386.22 | 8386.22 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8684.354 | 8684.354 | 0.399299 | 0.00007597 | 219.025 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 8684.35 | 8684.35 | 0.399299 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775428 | 48.3502 | 6652.67 | 0.00 | 8729.00 | 8729.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 734144.503 | -999.000 | 22.322629 | 0.02622194 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 734144.50 | 488385.10 | 22.322629 | 29.43 | 20.63 | 0.01219375 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 52.2405 | 23.99 | 0.00967177 | 50.1268 | 296011.24 | 0.00 | 748925.28 | 485018.08 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 179689.553 | 179689.553 | 6.696789 | 0.00157200 | 3032.801 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 179689.55 | 179689.55 | 6.696789 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 174.1351 | 21.02 | 0.00760793 | 47.3968 | 66106.67 | 0.00 | 161596.59 | 161596.59 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00325606 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00870986 | 53.8592 | 180455.69 | 0.00 | 92644.03 | 56011.80 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00757282 | 46.9118 | 111191.88 | 0.00 | 14849.77 | 14849.77 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8695.857 | 8695.857 | 1.426646 | 0.00007608 | 183.213 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 1.9659 | 2.005421 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8695.86 | 8695.86 | 1.0000 | 1.65630311 | 1.426646 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07606739 | 60.00 | 32.22 | 27.78 | 0.000 | 8695.86 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00796460 | 21.00 | 0.00796460 | 49.6445 | 1433.84 | 0.00 | 8744.55 | 8744.55 | 1.65630311 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.78 | 15.14 | 0.00800000 | 42214.3 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3762.854 | 3762.854 | 0.170517 | 0.00003292 | 95.293 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 0.8507 | 0.867782 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 3762.85 | 3762.85 | 1.0000 | 0.19796618 | 0.170517 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03291573 | 60.00 | 32.22 | 27.78 | 0.000 | 3762.85 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00756152 | 21.00 | 0.00756152 | 47.1639 | 2895.62 | 0.00 | 3782.18 | 3782.18 | 0.19796618 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.34 | 19.76 | 0.00800000 | 56039.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1621.196 | 1621.196 | 0.130250 | 0.00001418 | 36.567 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 0.3665 | 0.373877 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1621.20 | 1621.20 | 1.0000 | 0.15121662 | 0.130250 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01418148 | 60.00 | 32.22 | 27.78 | 0.000 | 1621.20 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00749526 | 21.00 | 0.00749526 | 46.7544 | 958.79 | 0.00 | 1629.95 | 1629.95 | 0.15121662 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.17 | 17.08 | 0.00800000 | 47713.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2284.316 | 2284.316 | 0.105710 | 0.00001998 | 57.508 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 0.5164 | 0.526805 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2284.32 | 2284.32 | 1.0000 | 0.12272665 | 0.105710 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01998216 | 60.00 | 32.22 | 27.78 | 0.000 | 2284.32 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00736201 | 21.00 | 0.00736201 | 45.9330 | 1746.84 | 0.00 | 2296.07 | 2296.07 | 0.12272665 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.95 | 19.64 | 0.00800000 | 55643.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1538.156 | 1538.156 | 0.069450 | 0.00001346 | 38.994 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 0.3477 | 0.354727 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1538.16 | 1538.16 | 1.0000 | 0.08062945 | 0.069450 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01345509 | 60.00 | 32.22 | 27.78 | 0.000 | 1538.16 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00744817 | 21.00 | 0.00744817 | 46.4643 | 1184.99 | 0.00 | 1546.05 | 1546.05 | 0.08062945 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.40 | 19.78 | 0.00800000 | 56109.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11240.367 | 11240.367 | 1.761020 | 0.00009834 | 237.527 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 2.5411 | 2.592231 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 11240.37 | 11240.37 | 1.0000 | 2.04450332 | 1.761020 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.09832560 | 60.00 | 32.22 | 27.78 | 0.000 | 11240.37 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00733798 | 21.00 | 0.00733798 | 45.7859 | 2287.71 | 0.00 | 11303.25 | 11303.25 | 2.04450332 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.02 | 15.23 | 0.00800000 | 42463.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11073.397 | 11073.397 | 0.733828 | 0.00009687 | 257.425 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 2.5033 | 2.553725 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 11073.40 | 11073.40 | 1.0000 | 0.85195688 | 0.733828 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.09686502 | 60.00 | 32.22 | 27.78 | 0.000 | 11073.40 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00761386 | 21.00 | 0.00761386 | 47.4861 | 7340.78 | 0.00 | 11132.58 | 11132.58 | 0.85195688 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.41 | 17.84 | 0.00800000 | 50001.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29638.010 | 29638.010 | 2.461808 | 0.00025929 | 665.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 6.7002 | 6.835059 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 29638.01 | 29638.01 | 1.0000 | 2.85810126 | 2.461808 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.25925979 | 60.00 | 32.22 | 27.78 | 0.000 | 29638.01 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00753397 | 21.00 | 0.00753397 | 46.9933 | 17117.35 | 0.00 | 29798.36 | 29798.36 | 2.85810126 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.82 | 16.96 | 0.00800000 | 47360.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11619.458 | -999.000 | 1.045575 | 0.00041501 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9956 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.045575 | 1.21388821 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 1.1200 | 1.120017 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 11619.46 | 11123.73 | 1.0000 | 1.21388821 | 1.045575 | 21.70 | 15.36 | 0.00869073 | 43894.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.41497001 | 6.70 | 13.37 | 6.67 | 0.000 | 11619.46 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00869073 | 21.11 | 0.00869073 | 53.7437 | 10295.63 | 0.00 | 12025.76 | 11290.31 | 1.21388821 | 21.70 | 15.73 | 0.00869073 | 43894.3 | 12.59 | 11.97 | 0.00845072 | 33987.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6336.908 | 6336.908 | 0.283369 | 0.00005544 | 181.087 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.045575 | 1.21388821 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 1.4326 | 1.461405 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6336.91 | 6336.91 | 1.0000 | 0.32898466 | 0.283369 | 21.11 | 14.12 | 0.00753948 | 40364.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05543238 | 60.00 | 32.22 | 27.78 | 0.000 | 6336.91 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00753948 | 21.11 | 0.00753948 | 46.7088 | 6337.08 | 0.00 | 6831.34 | 6831.34 | 0.32898466 | 16.60 | 12.70 | 0.00753948 | 35768.8 | 36.98 | 19.93 | 0.00753948 | 56533.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11504.433 | -999.000 | 1.034587 | 0.00041090 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9999 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.034587 | 1.20113112 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 1.1090 | 1.108930 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 11504.43 | 11007.89 | 1.0000 | 1.20113112 | 1.034587 | 21.70 | 15.37 | 0.00869305 | 43900.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.41086210 | 6.70 | 13.37 | 6.67 | 0.000 | 11504.43 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00869305 | 21.11 | 0.00869305 | 53.7579 | 10187.43 | 0.00 | 11906.60 | 11172.59 | 1.20113112 | 21.70 | 15.73 | 0.00869305 | 43900.2 | 12.59 | 11.97 | 0.00845097 | 33987.4 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6349.784 | 6349.784 | 0.283945 | 0.00005555 | 181.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.034587 | 1.20113112 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 1.4355 | 1.464375 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6349.78 | 6349.78 | 1.0000 | 0.32965311 | 0.283945 | 21.11 | 14.12 | 0.00754038 | 40366.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05554501 | 60.00 | 32.22 | 27.78 | 0.000 | 6349.78 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00754038 | 21.11 | 0.00754038 | 46.7142 | 6349.95 | 0.00 | 6845.22 | 6845.22 | 0.32965311 | 16.60 | 12.70 | 0.00754038 | 35771.1 | 36.98 | 19.93 | 0.00754038 | 56536.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 69917.745 | -999.000 | 6.442180 | 0.00249725 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8313 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.442180 | 7.47921934 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 6.7396 | 6.739479 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 69917.75 | 68285.11 | 1.0000 | 7.47921934 | 6.442180 | 21.70 | 15.29 | 0.00860233 | 43670.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.49699847 | 6.70 | 13.37 | 6.67 | 0.000 | 69917.75 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00860233 | 21.11 | 0.00860233 | 53.2023 | 63440.60 | 0.00 | 72390.56 | 69341.43 | 7.47921934 | 21.70 | 15.65 | 0.00860233 | 43670.5 | 12.62 | 11.97 | 0.00844084 | 33991.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36302.906 | 36302.906 | 1.623396 | 0.00031759 | 1037.395 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.442180 | 7.47921934 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 8.2069 | 8.372104 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 36302.91 | 36302.91 | 1.0000 | 1.88472503 | 1.623396 | 21.11 | 14.15 | 0.00757126 | 40445.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.31756126 | 60.00 | 32.22 | 27.78 | 0.000 | 36302.91 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00757126 | 21.11 | 0.00757126 | 46.9022 | 36303.37 | 0.00 | 39135.64 | 39135.64 | 1.88472503 | 16.60 | 12.73 | 0.00757126 | 35849.3 | 36.98 | 19.95 | 0.00757126 | 56613.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 77813.255 | -999.000 | 6.789036 | 0.00277926 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2153 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.789036 | 7.88191142 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 7.5007 | 7.500540 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 77813.26 | 72574.67 | 1.0000 | 7.88191142 | 6.789036 | 21.70 | 15.47 | 0.00880892 | 44194.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.77897377 | 6.70 | 13.37 | 6.67 | 0.000 | 77813.26 | 34.02 | 0.01447257 | 23.44 | 0.00000000 | 0.0000 | 21.11 | 0.00880892 | 21.11 | 0.00880892 | 54.4642 | 66851.20 | 0.00 | 80521.22 | 73639.64 | 7.88191142 | 21.70 | 15.83 | 0.00880892 | 44194.6 | 12.55 | 11.96 | 0.00846304 | 33978.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36557.797 | 36557.797 | 1.634795 | 0.00031982 | 1044.677 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.789036 | 7.88191142 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 8.2646 | 8.430887 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 36557.80 | 36557.80 | 1.0000 | 1.89795808 | 1.634795 | 21.11 | 14.15 | 0.00757392 | 40452.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.31979093 | 60.00 | 32.22 | 27.78 | 0.000 | 36557.80 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00757392 | 21.11 | 0.00757392 | 46.9185 | 36558.27 | 0.00 | 39410.42 | 39410.42 | 1.89795808 | 16.60 | 12.73 | 0.00757392 | 35856.0 | 36.98 | 19.95 | 0.00757392 | 56620.6 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10586.263 | -999.000 | 0.947529 | 0.00037811 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0332 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.947529 | 1.10005850 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 1.0204 | 1.020426 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 10586.26 | 10089.05 | 1.0000 | 1.10005850 | 0.947529 | 21.70 | 15.38 | 0.00871092 | 43945.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.37807114 | 6.70 | 13.37 | 6.67 | 0.000 | 10586.26 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00871092 | 21.11 | 0.00871092 | 53.8669 | 9330.16 | 0.00 | 10955.49 | 10239.04 | 1.10005850 | 21.70 | 15.75 | 0.00871092 | 43945.6 | 12.59 | 11.96 | 0.00845291 | 33986.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6310.541 | 6310.541 | 0.282190 | 0.00005521 | 180.333 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.947529 | 1.10005850 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 1.4266 | 1.455325 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6310.54 | 6310.54 | 1.0000 | 0.32761582 | 0.282190 | 21.11 | 14.12 | 0.00753772 | 40359.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05520174 | 60.00 | 32.22 | 27.78 | 0.000 | 6310.54 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00753772 | 21.11 | 0.00753772 | 46.6979 | 6310.71 | 0.00 | 6802.91 | 6802.91 | 0.32761582 | 16.60 | 12.70 | 0.00753772 | 35764.3 | 36.98 | 19.92 | 0.00753772 | 56529.2 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10502.799 | -999.000 | 0.939595 | 0.00037513 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0366 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.939595 | 1.09084754 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 1.0124 | 1.012381 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 10502.80 | 10005.34 | 1.0000 | 1.09084754 | 0.939595 | 21.70 | 15.38 | 0.00871278 | 43950.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.37509038 | 6.70 | 13.37 | 6.67 | 0.000 | 10502.80 | 31.26 | 0.01446754 | 22.70 | 0.00000000 | 0.0000 | 21.11 | 0.00871278 | 21.11 | 0.00871278 | 53.8783 | 9252.04 | 0.00 | 10869.03 | 10153.99 | 1.09084754 | 21.70 | 15.75 | 0.00871278 | 43950.3 | 12.59 | 11.96 | 0.00845312 | 33986.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6323.425 | 6323.425 | 0.282766 | 0.00005532 | 180.701 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.939595 | 1.09084754 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 1.4295 | 1.458296 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6323.43 | 6323.43 | 1.0000 | 0.32828470 | 0.282766 | 21.11 | 14.12 | 0.00753861 | 40362.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05531444 | 60.00 | 32.22 | 27.78 | 0.000 | 6323.43 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00753861 | 21.11 | 0.00753861 | 46.7034 | 6323.59 | 0.00 | 6816.80 | 6816.80 | 0.32828470 | 16.60 | 12.70 | 0.00753861 | 35766.6 | 36.98 | 19.92 | 0.00753861 | 56531.5 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14174.442 | 14174.442 | 0.790813 | 0.00012400 | 340.780 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 3.2044 | 3.268882 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 14174.44 | 14174.44 | 1.0000 | 0.91811481 | 0.790813 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.12399155 | 60.00 | 32.22 | 27.78 | 0.000 | 14174.44 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00764340 | 21.00 | 0.00764340 | 47.6670 | 10151.43 | 0.00 | 14248.50 | 14248.50 | 0.91811481 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.82 | 18.64 | 0.00800000 | 52454.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3045.076 | -999.000 | 0.274686 | 0.00010876 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9784 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.274686 | 0.31890438 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 0.2935 | 0.293520 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3045.08 | 2921.22 | 1.0000 | 0.31890438 | 0.274686 | 21.70 | 15.36 | 0.00868146 | 43870.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.10874994 | 6.70 | 13.37 | 6.67 | 0.000 | 3045.08 | 33.07 | 0.01447082 | 23.19 | 0.00000000 | 0.0000 | 21.11 | 0.00868146 | 21.11 | 0.00868146 | 53.6872 | 2704.80 | 0.00 | 3151.68 | 2965.11 | 0.31890438 | 21.70 | 15.72 | 0.00868146 | 43870.8 | 12.60 | 11.97 | 0.00844970 | 33987.9 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1917.967 | 1917.967 | 0.085766 | 0.00001678 | 54.806 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.274686 | 0.31890438 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 0.4336 | 0.442318 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1917.97 | 1917.97 | 1.0000 | 0.09957248 | 0.085766 | 21.11 | 14.19 | 0.00761412 | 40553.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01677750 | 60.00 | 32.22 | 27.78 | 0.000 | 1917.97 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00761412 | 21.11 | 0.00761412 | 47.1656 | 1918.02 | 0.00 | 2067.61 | 2067.61 | 0.09957248 | 16.60 | 12.77 | 0.00761412 | 35957.8 | 36.98 | 19.98 | 0.00761412 | 56722.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3012.098 | -999.000 | 0.271546 | 0.00010758 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9827 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.271546 | 0.31525849 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 0.2903 | 0.290341 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 3012.10 | 2888.10 | 1.0000 | 0.31525849 | 0.271546 | 21.70 | 15.36 | 0.00868375 | 43876.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.10757217 | 6.70 | 13.37 | 6.67 | 0.000 | 3012.10 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00868375 | 21.11 | 0.00868375 | 53.7011 | 2673.88 | 0.00 | 3117.52 | 2931.46 | 0.31525849 | 21.70 | 15.72 | 0.00868375 | 43876.6 | 12.60 | 11.97 | 0.00844995 | 33987.8 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1923.074 | 1923.074 | 0.085995 | 0.00001682 | 54.952 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.271546 | 0.31525849 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 0.4347 | 0.443495 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1923.07 | 1923.07 | 1.0000 | 0.09983762 | 0.085995 | 21.11 | 14.19 | 0.00761510 | 40556.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01682217 | 60.00 | 32.22 | 27.78 | 0.000 | 1923.07 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00761510 | 21.11 | 0.00761510 | 47.1716 | 1923.12 | 0.00 | 2073.12 | 2073.12 | 0.09983762 | 16.60 | 12.78 | 0.00761510 | 35960.3 | 36.98 | 19.98 | 0.00761510 | 56725.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14113.271 | -999.000 | 1.250413 | 0.00050408 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1053 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.250413 | 1.45170020 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 1.3604 | 1.360400 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 14113.27 | 13335.11 | 1.0000 | 1.45170020 | 1.250413 | 21.70 | 15.42 | 0.00874974 | 44044.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.50403252 | 6.70 | 13.37 | 6.67 | 0.000 | 14113.27 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00874974 | 21.11 | 0.00874974 | 54.1039 | 12312.49 | 0.00 | 14603.10 | 13530.63 | 1.45170020 | 21.70 | 15.78 | 0.00874974 | 44044.1 | 12.58 | 11.96 | 0.00845708 | 33984.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9167.579 | 9167.579 | 0.409951 | 0.00008020 | 261.964 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.250413 | 1.45170020 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 2.0725 | 2.114209 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 9167.58 | 9167.58 | 1.0000 | 0.47594396 | 0.409951 | 21.11 | 14.20 | 0.00762733 | 40587.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.08019380 | 60.00 | 32.22 | 27.78 | 0.000 | 9167.58 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00762733 | 21.11 | 0.00762733 | 47.2461 | 9167.77 | 0.00 | 9882.89 | 9882.89 | 0.47594396 | 16.60 | 12.79 | 0.00762733 | 35991.2 | 36.98 | 19.99 | 0.00762733 | 56756.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12375.157 | 12375.157 | 1.179224 | 0.00010826 | 273.162 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 2.7976 | 2.853934 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 12375.16 | 12375.16 | 1.0000 | 1.36905189 | 1.179224 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10825223 | 60.00 | 32.22 | 27.78 | 0.000 | 12375.16 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00770976 | 21.00 | 0.00770976 | 48.0761 | 6375.67 | 0.00 | 12442.56 | 12442.56 | 1.36905189 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.51 | 16.50 | 0.00800000 | 46023.2 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12797.758 | 12797.758 | 1.235657 | 0.00011196 | 282.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 2.8932 | 2.951394 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 12797.76 | 12797.76 | 1.0000 | 1.43456903 | 1.235657 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.11194895 | 60.00 | 32.22 | 27.78 | 0.000 | 12797.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00771550 | 21.00 | 0.00771550 | 48.1118 | 6511.20 | 0.00 | 12867.51 | 12867.51 | 1.43456903 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.40 | 16.45 | 0.00800000 | 45904.3 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8339.651 | 8339.651 | 1.207814 | 0.00007296 | 177.188 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 1.8853 | 1.923274 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 8339.65 | 8339.65 | 1.0000 | 1.40224426 | 1.207814 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07295146 | 60.00 | 32.22 | 27.78 | 0.000 | 8339.65 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.54 | 0.00666637 | 21.00 | 0.00666637 | 41.6462 | 2210.47 | 0.00 | 8386.22 | 8386.22 | 1.40224426 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.46 | 15.40 | 0.00800000 | 42915.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8684.354 | 8684.354 | 0.399299 | 0.00007597 | 219.025 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 1.9633 | 2.002769 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 8684.35 | 8684.35 | 1.0000 | 0.46357653 | 0.399299 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07596677 | 60.00 | 32.22 | 27.78 | 0.000 | 8684.35 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00775428 | 21.00 | 0.00775428 | 48.3502 | 6652.67 | 0.00 | 8729.00 | 8729.00 | 0.46357653 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.07 | 19.68 | 0.00800000 | 55764.4 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 734144.503 | -999.000 | 22.322629 | 0.02622194 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.5076 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.322629 | 25.91604881 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 70.7666 | 70.766642 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 734144.50 | 488385.10 | 1.0000 | 25.91604881 | 22.322629 | 29.43 | 20.63 | 0.01219375 | 60732.9 | 10.92 | 10.92 | 0.00850000 | 32405.1 | 26.21926573 | 6.70 | 13.37 | 6.67 | 50016.945 | 684127.56 | 34.40 | 0.01447326 | 23.54 | 11.66146000 | 52.2405 | 23.99 | 0.00970037 | 23.99 | 0.00967177 | 50.1268 | 296011.24 | 0.00 | 748925.28 | 485018.08 | 25.91604881 | 29.43 | 21.05 | 0.01219375 | 60732.9 | 11.21 | 11.08 | 0.00815568 | 31834.8 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 179689.553 | 179689.553 | 6.696789 | 0.00157200 | 3032.801 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.322629 | 25.91604881 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 40.6221 | 41.439650 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 179689.55 | 179689.55 | 1.0000 | 7.77481464 | 6.696789 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 1.57184224 | 60.00 | 32.22 | 27.78 | 0.000 | 179689.55 | -6.30 | 0.00229779 | -6.30 | 11.66146000 | 174.1351 | 20.98 | 0.00760721 | 21.02 | 0.00760793 | 47.3968 | 66106.67 | 0.00 | 161596.59 | 161596.59 | 7.77481464 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00325606 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 37.05031766 | 13.37 | 6.70 | 6.67 | 1037416.05 | 8.7873 | 8.787324 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 3.25573143 | 6.70 | 13.37 | 6.67 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00871588 | 21.11 | 0.00870986 | 53.8592 | 180455.69 | 0.00 | 92644.03 | 56011.80 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.60 | 11.47 | 0.00837545 | 32787.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 3.79308767 | 54.44 | 82.22 | 27.78 | 442344.18 | 3.7329 | 3.808058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 0.14444298 | 60.00 | 32.22 | 27.78 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00757092 | 21.11 | 0.00757282 | 46.9118 | 111191.88 | 0.00 | 14849.77 | 14849.77 | 0.71445936 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 11.66 | 22.32 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 61.50 | 8719.33 | 61.50 |
RETAIL_1_FLR_1 | 1511.33 | 7618.50 | 897.33 |
RETAIL_2_FLR_1 | 333.50 | 8126.50 | 69.50 |
MECH_FLR_1 | 930.83 | 8648.67 | 930.83 |
STORAGE_FLR_1 | 1028.83 | 8759.50 | 1028.83 |
LAUNDRY_FLR_1 | 4890.00 | 3903.67 | 1813.83 |
CAFE_FLR_1 | 1903.00 | 6499.83 | 404.83 |
LOBBY_FLR_1 | 870.67 | 7339.33 | 7.67 |
ROOM_1_FLR_3 | 1903.67 | 7940.50 | 1769.67 |
ROOM_2_FLR_3 | 2281.83 | 8121.00 | 2207.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1517.33 | 8753.67 | 1517.17 |
ROOM_5_FLR_3 | 1815.50 | 7893.33 | 1722.67 |
ROOM_6_FLR_3 | 2233.33 | 8037.33 | 2152.17 |
CORRIDOR_FLR_3 | 536.00 | 8760.00 | 536.00 |
ROOM_1_FLR_6 | 2576.17 | 7737.50 | 2224.33 |
ROOM_2_FLR_6 | 2861.17 | 7918.83 | 2635.83 |
ROOM_3_MULT9_FLR_6 | 1281.17 | 7869.50 | 1215.00 |
BANQUET_FLR_6 | 3842.67 | 4522.67 | 601.00 |
DINING_FLR_6 | 4597.67 | 3331.33 | 271.17 |
KITCHEN_FLR_6 | 7704.33 | 6885.50 | 6128.50 |
CORRIDOR_FLR_6 | 892.17 | 8127.67 | 763.67 |
Facility | 8498.00 | 8760.00 | 7729.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 10.33 | 0.00 | 10.33 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 41.83 | 0.00 | 41.83 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 2.50 | 1.83 | 2.50 | 1.83 |
ROOM_2_FLR_3 | 5.00 | 1.83 | 5.00 | 1.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4.00 | 6.33 | 4.00 | 6.33 |
ROOM_5_FLR_3 | 2.00 | 23.50 | 2.00 | 23.50 |
ROOM_6_FLR_3 | 4.33 | 22.33 | 4.33 | 22.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 2.33 | 3.67 | 2.33 | 3.67 |
ROOM_2_FLR_6 | 4.67 | 2.67 | 4.67 | 2.67 |
ROOM_3_MULT9_FLR_6 | 0.83 | 12.83 | 0.83 | 12.83 |
BANQUET_FLR_6 | 0.00 | 1.33 | 0.00 | 1.33 |
DINING_FLR_6 | 0.00 | 1.17 | 0.00 | 1.17 |
KITCHEN_FLR_6 | 0.00 | 89.83 | 0.00 | 89.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 19.67 | 137.50 | 19.67 | 137.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 1.041 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.260 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.492 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.572 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.650 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 21.403 | 0.144 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 3.466 | 0.106 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.678 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.071 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.175 | 0.000 | 0.069 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.537 | 0.078 | 0.000 | 0.107 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.071 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.175 | 0.000 | 0.068 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.587 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.083 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.175 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.143 | 0.000 | 0.135 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 4.281 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 4.536 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 17.834 | 0.145 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 1.119 | 0.035 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.737 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.508 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.000 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.382 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.434 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 15.954 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 2.327 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.126 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.516 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.455 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.391 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.516 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.180 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.493 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 11.625 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.746 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 43479398.83 | 0.00 | 43479398.83 | 0.00 | 43479398.83 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5199933.82 | 0.00 | 5199933.82 | 310220.85 | 5510154.67 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3970657.89 | 0.00 | 3970657.89 | 119745.64 | 4090403.53 | 2892943.94 | 0.14 | 6.34 | 8753.52 | 0.00 |
MECH_FLR_1 | 3221654.32 | 0.00 | 3221654.32 | 283007.56 | 3504661.88 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2116575.41 | 0.00 | 2116575.41 | 163279.77 | 2279855.18 | 1821682.01 | 163.29 | 126.53 | 8470.17 | 0.00 |
LAUNDRY_FLR_1 | 57259991.14 | 0.00 | 57259991.14 | 386432.37 | 57646423.51 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 22386130.19 | 0.00 | 22386130.19 | 685760.76 | 23071890.95 | 21330615.53 | 937.13 | 379.82 | 7443.05 | 0.00 |
LOBBY_FLR_1 | 75068446.70 | 0.00 | 75068446.70 | 1959375.13 | 77027821.83 | 59728886.00 | 8.62 | 1.16 | 8750.23 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 72659.60 | 2019535.21 | 180061.18 | 2199596.39 | 1946875.62 | 0.00 | 7640.70 | 1119.30 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 70341.89 | 2016989.41 | 180047.44 | 2197036.84 | 1946647.51 | 0.00 | 7634.00 | 1126.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 73918.04 | 26471805.31 | 50239.09 | 26522044.40 | 26397887.27 | 0.00 | 7682.33 | 1077.67 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 68790.36 | 26473896.08 | 50252.83 | 26524148.91 | 26405105.73 | 0.00 | 7692.03 | 1067.97 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 72557.25 | 2019432.87 | 180061.18 | 2199494.05 | 1946875.62 | 0.00 | 7631.42 | 1128.58 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 69678.85 | 2016326.37 | 180047.44 | 2196373.81 | 1946647.51 | 0.00 | 7631.67 | 1128.33 | 0.00 |
CORRIDOR_FLR_3 | 24101110.85 | 0.00 | 24101110.85 | 217730.19 | 24318841.04 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 84790.71 | 571509.61 | 180098.20 | 751607.82 | 486718.90 | 0.00 | 7655.18 | 1104.82 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 82505.61 | 569167.49 | 180084.46 | 749251.95 | 486661.88 | 0.00 | 7641.67 | 1118.33 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 86842.78 | 3213763.19 | 92144.54 | 3305907.74 | 3126920.42 | 0.00 | 7626.54 | 1133.46 | 0.00 |
BANQUET_FLR_6 | 37215294.49 | 0.00 | 37215294.49 | 439754.55 | 37655049.04 | 37458366.31 | 3576.52 | 3555.18 | 1628.30 | 0.00 |
DINING_FLR_6 | 39414146.19 | 0.00 | 39414146.19 | 439754.55 | 39853900.74 | 37458366.31 | 1400.19 | 1028.77 | 6331.03 | 0.00 |
KITCHEN_FLR_6 | 48215434.10 | 0.00 | 48215434.10 | 393682.28 | 48609116.37 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12170497.19 | 0.00 | 12170497.19 | 385314.24 | 12555811.43 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 12935669.79 | 0.45E+10 | 18144986.26 | 0.46E+10 | 0.43E+10 | 4059.92 | 8352.27 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3787 | 0.0000 | 1.3787 | 0.0000 | 1.3787 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1649 | 0.0000 | 0.1649 | 0.0098 | 0.1747 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1259 | 0.0000 | 0.1259 | 0.0038 | 0.1297 | 0.0917 | 0.14 | 6.34 | 8753.52 |
MECH_FLR_1 | 0.1022 | 0.0000 | 0.1022 | 0.0090 | 0.1111 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0671 | 0.0000 | 0.0671 | 0.0052 | 0.0723 | 0.0578 | 163.29 | 126.53 | 8470.17 |
LAUNDRY_FLR_1 | 1.8157 | 0.0000 | 1.8157 | 0.0123 | 1.8280 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7099 | 0.0000 | 0.7099 | 0.0217 | 0.7316 | 0.6764 | 937.13 | 379.82 | 7443.05 |
LOBBY_FLR_1 | 2.3804 | 0.0000 | 2.3804 | 0.0621 | 2.4425 | 1.8940 | 8.62 | 1.16 | 8750.23 |
ROOM_1_FLR_3 | 0.0617 | 0.0023 | 0.0640 | 0.0057 | 0.0697 | 0.0617 | 0.00 | 7640.70 | 1119.30 |
ROOM_2_FLR_3 | 0.0617 | 0.0022 | 0.0640 | 0.0057 | 0.0697 | 0.0617 | 0.00 | 7634.00 | 1126.00 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0022 | 0.8395 | 0.0016 | 0.8411 | 0.8373 | 0.00 | 7692.03 | 1067.97 |
ROOM_5_FLR_3 | 0.0617 | 0.0023 | 0.0640 | 0.0057 | 0.0697 | 0.0617 | 0.00 | 7631.42 | 1128.58 |
ROOM_6_FLR_3 | 0.0617 | 0.0022 | 0.0639 | 0.0057 | 0.0696 | 0.0617 | 0.00 | 7631.67 | 1128.33 |
CORRIDOR_FLR_3 | 0.7642 | 0.0000 | 0.7642 | 0.0069 | 0.7711 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0027 | 0.0181 | 0.0057 | 0.0238 | 0.0154 | 0.00 | 7655.18 | 1104.82 |
ROOM_2_FLR_6 | 0.0154 | 0.0026 | 0.0180 | 0.0057 | 0.0238 | 0.0154 | 0.00 | 7641.67 | 1118.33 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0028 | 0.1019 | 0.0029 | 0.1048 | 0.0992 | 0.00 | 7626.54 | 1133.46 |
BANQUET_FLR_6 | 1.1801 | 0.0000 | 1.1801 | 0.0139 | 1.1940 | 1.1878 | 3576.52 | 3555.18 | 1628.30 |
DINING_FLR_6 | 1.2498 | 0.0000 | 1.2498 | 0.0139 | 1.2638 | 1.1878 | 1400.19 | 1028.77 | 6331.03 |
KITCHEN_FLR_6 | 1.5289 | 0.0000 | 1.5289 | 0.0125 | 1.5414 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3859 | 0.0000 | 0.3859 | 0.0122 | 0.3981 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 79.6922 | 0.2320 | 79.9243 | 0.4543 | 80.3786 | 73.9670 | 4059.92 | 8352.27 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.50E+09 | 0.00 | 0.50E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 87193944.56 | 682085.09 | 87876029.65 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 15.9831 | 0.0000 | 15.9831 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.7649 | 0.0216 | 2.7865 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 5568.88 | 3191.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 15.7206 | 16.4462 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.7649 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 3997 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
Electricity:Building | 2534.28 | 32266.52 | 02-JAN-02:10 | 158241.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 332.05 | 3744.83 | 02-JAN-02:10 | 25084.28 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2527.19 | 32125.38 | 02-JAN-02:10 | 158000.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 869.01 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 869.01 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 869.01 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 869.01 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.95 | 223.93 | 02-JAN-02:10 | 1401.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.94 | 259.31 | 02-JAN-02:10 | 1623.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.64 | 250.98 | 02-JAN-02:10 | 1507.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 7.74 | 88.65 | 02-JAN-02:10 | 581.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 30.76 | 400.53 | 01-JAN-13:10 | 2922.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.42 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.42 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 248.21 | 3061.89 | 02-JAN-02:10 | 18583.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.21 | 950.48 | 02-JAN-02:10 | 8554.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.21 | 950.48 | 02-JAN-02:10 | 8554.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 325.45 | 4437.75 | 01-JAN-02:10 | 23570.01 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 325.54 | 4438.96 | 01-JAN-02:10 | 23576.46 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.35 | 67.90 | 01-JAN-02:10 | 391.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.35 | 67.89 | 01-JAN-02:10 | 391.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 38.55 | 525.67 | 01-JAN-02:10 | 2791.95 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 211.76 | 2631.28 | 02-JAN-02:10 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.90 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.90 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 211.76 | 2631.28 | 02-JAN-02:10 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.90 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.90 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.57 | 1103.62 | 11-FEB-23:30 | 3368.65 | 07-APR-07:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2109.04 | 2597.51 | 25-MAR-00:40 | 212236.91 | 08-JUL-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.23 | 0.00 | 01-JAN-11:10 | 1986.03 | 01-DEC-23:40 |
MedTempRefrigeration:Refrigeration:Electricity | 34.24 | 929.79 | 12-FEB-03:20 | 1214.48 | 02-JAN-07:20 |
Fans:Electricity | 488.53 | 12364.48 | 22-APR-05:30 | 27190.98 | 07-JUL-18:30 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 721.44 | 13229.99 | 22-APR-05:30 | 38627.53 | 07-JUL-18:30 |
ExteriorEquipment:Electricity | 650.10 | 9607.53 | 02-JAN-02:20 | 39721.54 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 31.07 | 542.72 | 02-JAN-04:10 | 1847.44 | 04-JAN-21:10 |
ElectricityPurchased:Facility | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
ElectricityPurchased:Plant | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
Cogeneration:ElectricityPurchased | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
General:Cogeneration:ElectricityPurchased | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
ElectricityNet:Plant | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
Cogeneration:ElectricityNet | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
General:Cogeneration:ElectricityNet | 6246.24 | 75874.55 | 17-MAR-01:30 | 433675.71 | 18-AUG-19:20 |
General:Fans:Electricity | 488.53 | 12364.48 | 22-APR-05:30 | 27190.98 | 07-JUL-18:30 |
ExteriorLights:Electricity | 262.45 | 0.00 | 01-JAN-07:50 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.45 | 0.00 | 01-JAN-07:50 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 201.85 | 0.00 | 19-JAN-10:20 | 9938.94 | 02-JAN-07:00 |
General:HeatRecovery:Electricity | 201.85 | 0.00 | 19-JAN-10:20 | 9938.94 | 02-JAN-07:00 |
WaterSystems:Electricity | 90.76 | 1086.76 | 08-JUL-00:40 | 4739.33 | 26-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 90.76 | 1086.76 | 08-JUL-00:40 | 4739.33 | 26-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1840.41 | 0.00 | 01-JAN-00:10 | 202735.36 | 08-JUL-15:20 |
General:Cooling:Electricity | 1840.41 | 0.00 | 01-JAN-00:10 | 202735.36 | 08-JUL-15:20 |
Pumps:Electricity | 123.39 | 56.98 | 03-OCT-07:50 | 5905.32 | 23-AUG-23:00 |
General:Pumps:Electricity | 123.39 | 56.98 | 03-OCT-07:50 | 5905.32 | 23-AUG-23:00 |
WIRED_LTG_ELECTRICITY | 30.59 | 0.00 | 01-JAN-00:10 | 2518.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5459.72 | 35148.34 | 11-AUG-00:10 | 567011.01 | 14-JAN-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3670.88 | 18467.44 | 03-MAY-23:10 | 483572.98 | 14-JAN-19:10 |
WaterSystems:NaturalGas | 2988.55 | 18467.44 | 02-JAN-04:10 | 272764.72 | 10-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2988.55 | 18467.44 | 02-JAN-04:10 | 272764.72 | 10-FEB-21:20 |
Heating:NaturalGas | 682.33 | 0.00 | 21-FEB-21:00 | 277275.66 | 17-JAN-10:20 |
Boiler:Heating:NaturalGas | 682.33 | 0.00 | 21-FEB-21:00 | 277275.66 | 17-JAN-10:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5938.37 | -588.14 | 08-NOV-00:50 | 691769.84 | 25-JUL-22:00 |
PlantLoopCoolingDemand:HVAC | 5938.37 | -588.14 | 08-NOV-00:50 | 691769.84 | 25-JUL-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5938.37 | -588.14 | 08-NOV-00:50 | 691769.84 | 25-JUL-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 08-NOV-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 08-NOV-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:30 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 29420.70 | 179789.42 | 29-NOV-11:30 | 2617481.76 | 06-JUL-18:10 |
EnergyTransfer:Building | 5530.21 | 66680.82 | 18-MAR-05:30 | 339780.16 | 07-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 726.77 | 9259.87 | 25-JAN-03:40 | 36128.20 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 182.44 | 3949.65 | 11-FEB-23:20 | 10473.01 | 03-JAN-07:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.22 | 1974.83 | 11-FEB-23:20 | 5236.50 | 03-JAN-07:40 |
General:Refrigeration:EnergyTransfer | 91.22 | 1974.83 | 11-FEB-23:20 | 5236.50 | 03-JAN-07:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.22 | 1974.83 | 11-FEB-23:20 | 5236.50 | 03-JAN-07:40 |
EnergyTransfer:Plant | 15167.52 | 20314.83 | 27-APR-00:30 | 1591942.58 | 25-JUL-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.62 | 1739.37 | 12-FEB-03:20 | 2593.44 | 02-JAN-07:20 |
EnergyTransfer:Zone:BASEMENT | 454.52 | 2688.56 | 18-MAR-05:30 | 22011.77 | 17-NOV-06:40 |
Heating:EnergyTransfer | 104.24 | 0.00 | 01-JAN-08:10 | 86021.15 | 07-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 104.24 | 0.00 | 01-JAN-08:10 | 86021.15 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5334.75 | 53568.68 | 18-MAR-05:30 | 337079.91 | 07-JUL-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 454.52 | 2688.56 | 18-MAR-05:30 | 22011.77 | 17-NOV-06:40 |
General:Cooling:EnergyTransfer | 5334.75 | 53568.68 | 18-MAR-05:30 | 337079.91 | 07-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 454.52 | 2688.56 | 18-MAR-05:30 | 22011.77 | 17-NOV-06:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 43.23 | 0.20 | 05-JAN-19:00 | 2799.01 | 19-AUG-13:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.94 | 0.00 | 01-JAN-00:20 | 1205.43 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.94 | 0.00 | 01-JAN-00:20 | 1205.43 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.29 | 0.00 | 01-JAN-15:50 | 2799.01 | 19-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.29 | 0.00 | 01-JAN-15:50 | 2799.01 | 19-AUG-13:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.90 | 152.14 | 08-JAN-15:50 | 2076.21 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.90 | 152.14 | 08-JAN-15:50 | 2076.21 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.90 | 152.14 | 08-JAN-15:50 | 2076.21 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 27.49 | 0.10 | 03-DEC-01:40 | 1396.30 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.46 | 0.00 | 01-JAN-00:10 | 564.03 | 13-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.46 | 0.00 | 01-JAN-00:10 | 564.03 | 13-FEB-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.03 | 0.00 | 03-JAN-10:10 | 1396.30 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.03 | 0.00 | 03-JAN-10:10 | 1396.30 | 18-AUG-21:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 16.33 | 0.06 | 14-FEB-16:50 | 880.09 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.65 | 0.00 | 01-JAN-00:10 | 426.09 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.65 | 0.00 | 01-JAN-00:10 | 426.09 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.68 | 0.00 | 01-JAN-16:30 | 880.09 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.68 | 0.00 | 01-JAN-16:30 | 880.09 | 18-AUG-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.49 | 6697.74 | 25-MAR-04:40 | 38766.32 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.49 | 6697.74 | 25-MAR-04:40 | 38766.32 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.49 | 6697.74 | 25-MAR-04:40 | 38766.32 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 240.57 | 30.21 | 07-JAN-16:20 | 12016.13 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 630.63 | 09-JAN-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 630.63 | 09-JAN-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 240.57 | 0.00 | 07-JAN-16:30 | 12016.13 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 240.57 | 0.00 | 07-JAN-16:30 | 12016.13 | 18-AUG-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 830.09 | 5213.35 | 08-JAN-16:00 | 38703.85 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 830.09 | 5213.35 | 08-JAN-16:00 | 38703.85 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 830.09 | 5213.35 | 08-JAN-16:00 | 38703.85 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 60.22 | 0.00 | 16-MAR-04:50 | 10492.55 | 18-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.41 | 0.00 | 01-JAN-08:10 | 5695.05 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.41 | 0.00 | 01-JAN-08:10 | 5695.05 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 49.81 | 0.00 | 01-JAN-00:10 | 10492.55 | 18-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 49.81 | 0.00 | 01-JAN-00:10 | 10492.55 | 18-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 58.97 | 0.01 | 09-FEB-12:40 | 10516.58 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.78 | 0.00 | 01-JAN-08:10 | 6097.07 | 12-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.78 | 0.00 | 01-JAN-08:10 | 6097.07 | 12-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 45.19 | 0.00 | 01-JAN-00:10 | 10516.58 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 45.19 | 0.00 | 01-JAN-00:10 | 10516.58 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 412.26 | 4.86 | 03-FEB-05:40 | 43756.24 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 4.57 | 0.00 | 01-JAN-00:40 | 21549.09 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 4.57 | 0.00 | 01-JAN-00:40 | 21549.09 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 407.69 | 0.00 | 01-JAN-00:10 | 43756.24 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 407.69 | 0.00 | 01-JAN-00:10 | 43756.24 | 10-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 476.09 | 0.38 | 01-FEB-04:10 | 68007.28 | 08-JUL-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 29.32 | 0.00 | 01-JAN-00:10 | 34165.31 | 27-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 29.32 | 0.00 | 01-JAN-00:10 | 34165.31 | 27-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 446.77 | 0.00 | 01-JAN-16:30 | 68007.28 | 08-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 446.77 | 0.00 | 01-JAN-16:30 | 68007.28 | 08-JUL-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 60.58 | 0.14 | 14-OCT-05:20 | 10020.42 | 04-JUN-09:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.39 | 0.00 | 01-JAN-08:10 | 5882.16 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.39 | 0.00 | 01-JAN-08:10 | 5882.16 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 50.19 | 0.00 | 01-JAN-00:10 | 10020.42 | 04-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 50.19 | 0.00 | 01-JAN-00:10 | 10020.42 | 04-JUN-09:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.16 | 0.22 | 06-MAR-23:00 | 9999.93 | 04-JUN-09:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.68 | 0.00 | 01-JAN-08:10 | 5914.76 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.68 | 0.00 | 01-JAN-08:10 | 5914.76 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 45.47 | 0.00 | 01-JAN-00:10 | 9999.93 | 04-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 45.47 | 0.00 | 01-JAN-00:10 | 9999.93 | 04-JUN-09:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 217.79 | 0.51 | 07-JAN-23:00 | 9952.40 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.52 | 0.00 | 01-JAN-00:10 | 2296.44 | 07-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.52 | 0.00 | 01-JAN-00:10 | 2296.44 | 07-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 217.26 | 0.00 | 03-JAN-09:10 | 9952.40 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 217.26 | 0.00 | 03-JAN-09:10 | 9952.40 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.22 | 0.02 | 20-OCT-04:20 | 2899.22 | 18-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.05 | 0.00 | 01-JAN-08:10 | 1814.51 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.05 | 0.00 | 01-JAN-08:10 | 1814.51 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.16 | 0.00 | 01-JAN-00:10 | 2899.22 | 18-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.16 | 0.00 | 01-JAN-00:10 | 2899.22 | 18-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.13 | 0.04 | 30-OCT-14:00 | 2854.89 | 07-JUL-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.16 | 0.00 | 01-JAN-08:10 | 1839.60 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.16 | 0.00 | 01-JAN-08:10 | 1839.60 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.97 | 0.00 | 01-JAN-00:10 | 2854.89 | 07-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.97 | 0.00 | 01-JAN-00:10 | 2854.89 | 07-JUL-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 90.83 | 0.08 | 07-MAR-07:00 | 14332.17 | 10-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.86 | 0.00 | 01-JAN-08:10 | 8329.01 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.86 | 0.00 | 01-JAN-08:10 | 8329.01 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.98 | 0.00 | 01-JAN-00:10 | 14332.17 | 10-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.98 | 0.00 | 01-JAN-00:10 | 14332.17 | 10-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 465.46 | 4634.74 | 07-DEC-08:00 | 23634.46 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 465.46 | 4634.74 | 07-DEC-08:00 | 23634.46 | 07-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 465.46 | 4634.74 | 07-DEC-08:00 | 23634.46 | 07-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 502.42 | 5489.98 | 12-FEB-17:40 | 24944.34 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 502.42 | 5489.98 | 12-FEB-17:40 | 24944.34 | 07-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 502.42 | 5489.98 | 12-FEB-17:40 | 24944.34 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 635.55 | 7140.43 | 25-JAN-03:40 | 31067.00 | 08-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 635.55 | 7140.43 | 25-JAN-03:40 | 31067.00 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 104.69 | 0.00 | 10-JAN-23:40 | 6162.60 | 08-JUL-17:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.45 | 0.00 | 01-JAN-00:10 | 2389.24 | 12-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.45 | 0.00 | 01-JAN-00:10 | 2389.24 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.23 | 0.00 | 02-JAN-07:10 | 6162.60 | 08-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.23 | 0.00 | 02-JAN-07:10 | 6162.60 | 08-JUL-17:20 |
PlantLoopHeatingDemand:Facility | 1161.30 | 7573.44 | 15-JUL-00:20 | 247473.61 | 17-JAN-10:20 |
PlantLoopHeatingDemand:Plant | 671.59 | 7489.77 | 02-AUG-03:00 | 51960.39 | 30-JAN-07:50 |
WaterSystems:PlantLoopHeatingDemand | 671.59 | 7489.77 | 02-AUG-03:00 | 51960.39 | 30-JAN-07:50 |
General:WaterSystems:PlantLoopHeatingDemand | 671.59 | 7489.77 | 02-AUG-03:00 | 51960.39 | 30-JAN-07:50 |
EnergyTransfer:HVAC | 8722.97 | 8136.48 | 03-OCT-07:50 | 833135.33 | 06-JUL-18:10 |
HeatingCoils:EnergyTransfer | 489.71 | 0.00 | 21-FEB-21:00 | 223505.56 | 17-JAN-10:20 |
PlantLoopHeatingDemand:HVAC | 489.71 | 0.00 | 21-FEB-21:00 | 223505.56 | 17-JAN-10:20 |
HeatingCoils:PlantLoopHeatingDemand | 489.71 | 0.00 | 21-FEB-21:00 | 223505.56 | 17-JAN-10:20 |
CoolingCoils:EnergyTransfer | 5938.37 | -588.14 | 08-NOV-00:50 | 691769.84 | 25-JUL-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 1139.48 | 0.00 | 19-JAN-10:20 | 438391.81 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 1155.41 | 0.00 | 01-JAN-00:10 | 267114.90 | 07-JUL-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 671.59 | 7489.77 | 02-AUG-03:00 | 51960.39 | 30-JAN-07:50 |
WaterUse:WaterSystems:EnergyTransfer | 671.59 | 7489.77 | 02-AUG-03:00 | 51960.39 | 30-JAN-07:50 |
Boilers:EnergyTransfer | 485.22 | 0.00 | 21-FEB-21:00 | 222460.63 | 17-JAN-10:20 |
Chillers:EnergyTransfer | 6039.54 | 0.00 | 01-JAN-00:10 | 697902.51 | 25-JUL-22:00 |
HeatRejection:EnergyTransfer | 7879.95 | 0.00 | 01-JAN-00:10 | 868328.66 | 25-JUL-22:00 |
General:HeatRejection:EnergyTransfer | 7879.95 | 0.00 | 01-JAN-00:10 | 868328.66 | 25-JUL-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -454.525 | 0.000 | 0.000 | 151.379 | 188.948 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -28.906 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.942 | -42.293 | 0.000 | 0.000 | 15.687 | 8.760 | 10.186 | 19.160 | 0.000 | 0.451 | 0.000 | 0.000 | -8.701 | 0.000 | -2.390 | -1.802 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -40.903 | 0.000 | 0.000 | 17.779 | 10.144 | 11.795 | 0.000 | 0.000 | 0.179 | 1.962 | 0.000 | 0.000 | 0.000 | -0.956 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.460 | -27.028 | 0.000 | 0.000 | 3.820 | 8.172 | 12.471 | 0.000 | 0.000 | 0.426 | 3.876 | 0.000 | 0.000 | 0.000 | -2.196 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.646 | -15.680 | 0.000 | 0.000 | 2.967 | 4.146 | 3.598 | 0.000 | 0.000 | 0.260 | 5.315 | 0.000 | 0.000 | 0.000 | -1.251 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -607.491 | 0.000 | 0.000 | 11.840 | 5.547 | 658.131 | 0.000 | 0.000 | 0.648 | 0.000 | 0.000 | 0.000 | 0.000 | -3.223 | -65.452 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.004 | -240.570 | 0.000 | 0.000 | 198.092 | 16.416 | 14.341 | 53.287 | 0.000 | 0.950 | 0.000 | 0.000 | -26.256 | 0.000 | -5.635 | -10.629 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -830.098 | 0.000 | 0.000 | 586.224 | 99.207 | 148.998 | 71.247 | 0.000 | 2.822 | 0.000 | 0.000 | -34.850 | 0.000 | -16.227 | -27.324 |
ROOM_1_FLR_3 | 13.329 | -35.564 | 0.000 | -17.159 | 0.000 | 0.000 | 9.581 | 10.925 | 10.478 | 38.911 | 0.000 | 1.168 | 0.000 | 0.000 | -20.460 | 0.000 | -6.740 | -4.469 |
ROOM_2_FLR_3 | 17.215 | -31.792 | 0.000 | -16.832 | 0.000 | 0.000 | 9.623 | 10.924 | 10.477 | 30.348 | 0.000 | 1.179 | 0.001 | 0.000 | -21.348 | 0.000 | -6.524 | -3.270 |
ROOM_3_MULT19_FLR_3 | 7.506 | -151.321 | 0.000 | -259.308 | 0.000 | 0.000 | 0.000 | 130.455 | 194.997 | 223.941 | 0.000 | 4.644 | 21.230 | 0.000 | -117.550 | 0.000 | -54.594 | -0.003 |
ROOM_4_MULT19_FLR_3 | 54.550 | -245.702 | 0.000 | -226.286 | 0.000 | 0.000 | 183.390 | 130.491 | 195.050 | 93.283 | 0.000 | 7.267 | 0.000 | 0.000 | -119.605 | 0.000 | -45.087 | -27.350 |
ROOM_5_FLR_3 | 13.319 | -35.887 | 0.000 | -17.232 | 0.000 | 0.000 | 9.586 | 10.925 | 10.478 | 38.640 | 0.000 | 1.164 | 0.000 | 0.000 | -19.694 | 0.000 | -6.689 | -4.611 |
ROOM_6_FLR_3 | 17.109 | -31.991 | 0.000 | -16.906 | 0.000 | 0.000 | 9.628 | 10.924 | 10.477 | 29.541 | 0.000 | 1.175 | 0.000 | 0.000 | -20.053 | 0.000 | -6.465 | -3.439 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.521 | -217.266 | 0.000 | 0.000 | 120.814 | 91.336 | 0.000 | 36.261 | 0.000 | 1.303 | 0.001 | 0.000 | -25.452 | 0.000 | -6.801 | -0.715 |
ROOM_1_FLR_6 | 4.875 | -9.709 | 0.000 | -4.278 | 0.000 | 0.000 | 2.395 | 2.731 | 2.620 | 9.610 | 0.000 | 0.290 | 0.000 | 0.000 | -5.106 | 0.000 | -1.732 | -1.697 |
ROOM_2_FLR_6 | 6.105 | -8.722 | 0.000 | -4.198 | 0.000 | 0.000 | 2.406 | 2.731 | 2.619 | 7.496 | 0.000 | 0.292 | 0.000 | 0.000 | -5.322 | 0.000 | -1.672 | -1.735 |
ROOM_3_MULT9_FLR_6 | 12.278 | -57.355 | 0.000 | -28.039 | 0.000 | 0.000 | 21.481 | 15.453 | 23.098 | 49.098 | 0.000 | 1.374 | 0.000 | 0.000 | -23.766 | 0.000 | -9.567 | -4.055 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -465.466 | 0.000 | 0.000 | 327.852 | 35.901 | 175.857 | 9.258 | 0.000 | 0.502 | 0.000 | 0.000 | -16.881 | 0.000 | -4.032 | -62.990 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -502.419 | 0.000 | 0.000 | 325.097 | 35.901 | 175.857 | 8.906 | 0.000 | 0.483 | 0.000 | 0.000 | -17.552 | 0.000 | -4.102 | -22.171 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -635.530 | 0.000 | 0.000 | 29.378 | 14.807 | 550.372 | 17.285 | 0.000 | 0.404 | 39.384 | 0.000 | -12.335 | 0.000 | -3.765 | -0.004 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.452 | -103.234 | 0.000 | 0.000 | 31.911 | 24.166 | 0.000 | 17.028 | 0.000 | 0.523 | 42.684 | 0.000 | -11.521 | 0.000 | -3.008 | -0.000 |
Total Facility | 146.287 | -608.043 | 4.023 | -4772.743 | 0.000 | 0.000 | 2070.933 | 869.010 | 2365.005 | 753.300 | 0.000 | 27.502 | 114.454 | 0.000 | -506.453 | 0.000 | -192.654 | -270.625 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-DEC-08:13 | 0.00 | 0.00 | 0.00 | -30596.62 | 0.00 | 0.00 | 4055.67 | 6867.51 | 5069.75 | 0.00 | 0.00 | 0.00 | 14603.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 11-JAN-14:15 | 0.00 | 0.00 | 0.00 | -2844.96 | 0.00 | 0.00 | 164.47 | 198.99 | 252.59 | 4155.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -184.60 | -1742.35 |
RETAIL_2_FLR_1 | 21-FEB-07:07 | 0.00 | 0.00 | 0.00 | -2205.82 | 0.00 | 0.00 | 402.42 | 460.86 | 501.43 | 0.00 | 0.00 | 0.00 | 914.31 | 0.00 | -0.00 | 0.00 | -73.19 | 0.00 |
MECH_FLR_1 | 21-FEB-07:07 | 0.00 | 0.00 | 0.00 | -1736.80 | 0.00 | 0.00 | 87.68 | 371.26 | 530.18 | 0.00 | 0.00 | 0.00 | 916.39 | 0.00 | -0.00 | 0.00 | -168.71 | 0.00 |
STORAGE_FLR_1 | 12-OCT-06:32 | 0.00 | 0.00 | 0.00 | -1017.95 | 0.00 | 0.00 | 67.25 | 188.35 | 152.94 | 0.00 | 0.00 | 0.00 | 694.46 | 0.00 | -0.00 | 0.00 | -85.06 | 0.00 |
LAUNDRY_FLR_1 | 30-NOV-21:55 | 0.00 | 0.00 | 0.00 | -50688.80 | 0.00 | 0.00 | 455.20 | 403.20 | 41967.83 | 0.00 | 0.00 | 0.00 | 8178.27 | 0.00 | -0.00 | 0.00 | -315.71 | 0.00 |
CAFE_FLR_1 | 24-FEB-23:26 | 0.00 | 0.00 | 0.00 | -12847.27 | 0.00 | 0.00 | 9567.08 | 652.56 | 406.43 | 0.00 | 0.00 | 0.00 | 5272.35 | 0.00 | -2631.04 | 0.00 | -420.11 | 0.00 |
LOBBY_FLR_1 | 09-DEC-08:13 | 0.00 | 0.00 | 0.00 | -49043.96 | 0.00 | 0.00 | 17251.98 | 3269.65 | 5278.53 | 2894.46 | 0.00 | 0.00 | 21832.96 | 0.00 | -0.00 | 0.00 | -1483.62 | 0.00 |
ROOM_1_FLR_3 | 18-SEP-16:01 | 0.00 | -13214.92 | 0.00 | -867.39 | 0.00 | 0.00 | 202.43 | 235.45 | 505.73 | 5557.54 | 0.00 | 18.76 | 7562.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 18-SEP-16:01 | 0.00 | -12410.33 | 0.00 | -829.35 | 0.00 | 0.00 | 211.64 | 235.42 | 505.67 | 5060.21 | 0.00 | 32.50 | 7194.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:30 | 0.00 | -33315.26 | 0.00 | -10438.91 | 0.00 | 0.00 | 0.00 | 2811.47 | 2352.88 | 50786.99 | 0.00 | 751.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12948.25 |
ROOM_4_MULT19_FLR_3 | 09-MAY-20:41 | 0.00 | -84712.08 | 0.00 | -7667.91 | 0.00 | 0.00 | 7203.42 | 8938.91 | 13532.74 | 0.00 | 0.00 | 0.00 | 71920.97 | 0.00 | -7831.01 | 0.00 | -1385.05 | 0.00 |
ROOM_5_FLR_3 | 04-JUN-08:51 | 0.00 | -11913.61 | 0.00 | -923.86 | 0.00 | 0.00 | 107.49 | 470.90 | 653.23 | 6839.43 | 0.00 | 0.00 | 4793.58 | 0.00 | -0.00 | 0.00 | -27.16 | 0.00 |
ROOM_6_FLR_3 | 04-JUN-08:51 | 0.00 | -11842.41 | 0.00 | -924.41 | 0.00 | 0.00 | 107.49 | 470.85 | 653.15 | 6843.47 | 0.00 | 0.00 | 4719.27 | 0.00 | -0.00 | 0.00 | -27.41 | 0.00 |
CORRIDOR_FLR_3 | 24-FEB-23:26 | 0.00 | 0.00 | 0.00 | -12334.83 | 0.00 | 0.00 | 6173.36 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 6600.82 | 0.00 | -2447.41 | 0.00 | -481.69 | 0.00 |
ROOM_1_FLR_6 | 15-OCT-16:21 | 0.00 | -3482.08 | 0.00 | -217.42 | 0.00 | 0.00 | 49.62 | 69.37 | 105.36 | 656.77 | 0.00 | 0.00 | 2822.50 | 0.00 | -0.00 | 0.00 | -4.12 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-20:41 | 0.00 | -3417.49 | 0.00 | -151.89 | 0.00 | 0.00 | 88.85 | 187.08 | 181.72 | 0.00 | 0.00 | 0.00 | 3602.60 | 0.00 | -421.33 | 0.00 | -69.54 | 0.00 |
ROOM_3_MULT9_FLR_6 | 15-OCT-16:21 | 0.00 | -16162.26 | 0.00 | -1400.68 | 0.00 | 0.00 | 450.76 | 392.50 | 929.02 | 1577.71 | 0.00 | 0.00 | 14232.95 | 0.00 | -0.00 | 0.00 | -20.00 | 0.00 |
BANQUET_FLR_6 | 30-NOV-23:41 | 0.00 | 0.00 | 0.00 | -34358.00 | 0.00 | 0.00 | 15392.89 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 13247.46 | 0.00 | -1801.01 | 0.00 | -375.19 | 0.00 |
DINING_FLR_6 | 30-NOV-23:41 | 0.00 | 0.00 | 0.00 | -36152.95 | 0.00 | 0.00 | 15374.24 | 1145.95 | 6747.90 | 0.00 | 0.00 | 0.00 | 15101.02 | 0.00 | -1840.00 | 0.00 | -376.16 | 0.00 |
KITCHEN_FLR_6 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | -35542.80 | 0.00 | 0.00 | 617.78 | 269.09 | 26759.11 | 0.00 | 0.00 | 0.00 | 9338.88 | 0.00 | -1134.64 | 0.00 | -307.43 | 0.00 |
CORRIDOR_FLR_6 | 08-JUL-17:12 | 0.00 | 0.00 | 0.00 | -6163.07 | 0.00 | 0.00 | 925.36 | 1317.51 | 0.00 | 1330.22 | 0.00 | 139.92 | 2450.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-AUG-18:02 | 0.00 | -164144.42 | 0.00 | -208212.81 | 0.00 | 0.00 | 75323.36 | 59125.48 | 120482.43 | 47011.18 | 0.00 | 6715.88 | 63698.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-07:00 | 0.00 | 0.00 | 1205.47 | 0.00 | 0.00 | 0.00 | 661.85 | 238.78 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1747.38 | 0.00 | -429.42 | -217.98 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 13-FEB-05:00 | 0.00 | 0.00 | 564.04 | 0.00 | 0.00 | 0.00 | 197.29 | 74.25 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -304.29 | -708.02 |
STORAGE_FLR_1 | 12-FEB-07:05 | 0.00 | 0.00 | 426.11 | 0.00 | 0.00 | 0.00 | 120.09 | 150.68 | 127.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -231.16 | -593.18 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 09-JAN-09:20 | 0.00 | 0.00 | 634.79 | 0.00 | 0.00 | 0.00 | 2359.36 | 191.42 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2233.78 | 0.00 | -667.33 | -792.49 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 03-JAN-16:01 | 6353.66 | 269.36 | 0.00 | -269.36 | 0.00 | 0.00 | 293.99 | 235.45 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1195.37 | 0.00 | -467.84 | -5420.08 |
ROOM_2_FLR_3 | 03-JAN-16:01 | 6351.40 | 269.06 | 0.00 | -269.06 | 0.00 | 0.00 | 293.99 | 235.42 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1264.17 | 0.00 | -467.70 | -5349.10 |
ROOM_3_MULT19_FLR_3 | 12-FEB-06:00 | 21548.89 | 3320.97 | 0.00 | -3320.97 | 0.00 | 0.00 | 0.00 | 1104.51 | 3333.24 | 0.00 | 0.00 | 0.00 | 997.30 | 0.00 | -21953.27 | 0.00 | -5030.67 | 0.00 |
ROOM_4_MULT19_FLR_3 | 27-JAN-16:01 | 36166.75 | 3576.95 | 0.00 | -3576.95 | 0.00 | 0.00 | 5585.70 | 2812.24 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7248.27 | 0.00 | -2238.89 | -38803.95 |
ROOM_5_FLR_3 | 03-JAN-16:01 | 6188.70 | 268.34 | 0.00 | -268.34 | 0.00 | 0.00 | 293.99 | 235.45 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1350.19 | 0.00 | -467.44 | -5100.69 |
ROOM_6_FLR_3 | 03-JAN-16:01 | 6192.95 | 267.78 | 0.00 | -267.78 | 0.00 | 0.00 | 293.99 | 235.42 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1419.13 | 0.00 | -467.20 | -5036.19 |
CORRIDOR_FLR_3 | 07-JAN-17:00 | 0.00 | 0.00 | 2296.41 | 0.00 | 0.00 | 0.00 | 2089.86 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3559.56 | 0.00 | -918.20 | -1983.30 |
ROOM_1_FLR_6 | 03-JAN-16:01 | 1862.33 | 67.56 | 0.00 | -67.56 | 0.00 | 0.00 | 73.50 | 58.86 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -295.37 | 0.00 | -117.49 | -1631.88 |
ROOM_2_FLR_6 | 12-FEB-09:13 | 1874.68 | 83.51 | 0.00 | -83.51 | 0.00 | 0.00 | 37.79 | 117.71 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -762.95 | 0.00 | -227.85 | -1202.67 |
ROOM_3_MULT9_FLR_6 | 03-JAN-16:01 | 8696.95 | 432.20 | 0.00 | -432.20 | 0.00 | 0.00 | 661.47 | 333.03 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1435.63 | 0.00 | -540.50 | -8156.60 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 12-FEB-07:05 | 0.00 | 0.00 | 2390.04 | 0.00 | 0.00 | 0.00 | 1312.13 | 878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2395.69 | 0.00 | -545.44 | -1639.38 |
Total Facility | 07-JAN-16:13 | 10744.09 | 82460.80 | 6075.17 | -82460.80 | 0.00 | 0.00 | 36939.45 | 19975.89 | 74838.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53732.22 | 0.00 | -18090.79 | -76749.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.4462 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.3226 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6720 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6720 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7436 | 2.7436 | 1.4266 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3279 | 0.3279 | 0.1705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2505 | 0.2505 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2033 | 0.2033 | 0.1057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1336 | 0.1336 | 0.0694 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3866 | 3.3866 | 1.7610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4112 | 1.4112 | 0.7338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7342 | 4.7342 | 2.4618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5208 | 1.5208 | 0.7908 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2677 | 2.2677 | 1.1792 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3763 | 2.3763 | 1.2357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3227 | 2.3227 | 1.2078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7679 | 0.7679 | 0.3993 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.4462 | 22.3226 | 22.4462 | 11.6720 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4266 | 1.4266 | 1.4266 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1705 | 0.1705 | 0.1705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1302 | 0.1302 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1057 | 0.1057 | 0.1057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0694 | 0.0694 | 0.0694 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7610 | 1.7610 | 1.7610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7338 | 0.7338 | 0.7338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4618 | 2.4618 | 2.4618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7908 | 0.7908 | 0.7908 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1792 | 1.1792 | 1.1792 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2357 | 1.2357 | 1.2357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2078 | 1.2078 | 1.2078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3993 | 0.3993 | 0.3993 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6720 | 11.6720 | 11.6720 | 11.6720 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 19.67 |
Number of hours cooling loads not met | 137.50 |
Number of hours not met | 156.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 682.33 | 277275.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1840.41 | 202735.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 869.01 | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.45 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.07 | 1847.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 488.53 | 27190.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 123.39 | 5905.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 201.85 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.76 | 4739.33 | 2988.55 | 272764.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.23 | 1986.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.24 | 1214.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.75 | 6246.24 |
Natural Gas | 1788.84 | 5459.72 |
Additional | 0.00 | 0.00 |
Total | 3508.58 | 11705.96 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 76.60 |
Space Heating | 0.00 |
Space Cooling | 162.22 |
Fans (All) | 43.06 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 550.56 |
Subtotal | 550.56 |
Natural Gas [MJ/m2] | |
Space Heating | 60.14 |
Service Water Heating | 263.42 |
Miscellaneous (All) | 481.23 |
Subtotal | 481.23 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.42 |
Space Heating | 5.83 |
Space Cooling | 15.72 |
Fans (All) | 4.17 |
Service Water Heating | 26.31 |
Receptacle Equipment | 29.45 |
Miscellaneous | 11.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Average | 8759.98 | 0.02 | 0.00 | 0.00 | 0.00 |
Sum | 192719.67 | 0.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8644.83 | 115.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8645.83 | 114.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8694.50 | 65.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8566.00 | 194.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8566.00 | 194.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8579.33 | 180.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8582.00 | 178.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8607.17 | 152.83 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8673.67 | 86.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8566.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 194.00 | 0.00 | 0.00 | 0.00 |
Average | 8701.27 | 58.73 | 0.00 | 0.00 | 0.00 |
Sum | 191428.00 | 1292.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4113.33 | 40.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4115.67 | 38.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4120.17 | 33.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4112.17 | 41.83 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4113.33 | 40.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4098.17 | 55.83 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4102.17 | 51.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4097.50 | 56.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1226376.33 | 19338.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 19338.67 | 0.00 | 0.00 | 0.00 |
Average | 287991.67 | 895.37 | 0.00 | 0.00 | 0.00 |
Sum | 6335816.83 | 19698.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376119E+11 | 26254.45 | 22-JAN-17:49 | 2.98 | -0.3 | 0.644097E+10 | 4344.90 | 23-JAN-22:00 | 4.40 | 0.70 |
February | 0.311772E+11 | 24139.62 | 21-FEB-07:07 | 5.60 | 3.82 | 0.567066E+10 | 4057.52 | 06-FEB-22:10 | 5.60 | 3.82 |
March | 0.310422E+11 | 20490.01 | 22-MAR-19:15 | 5.60 | 4.80 | 0.620580E+10 | 3938.96 | 22-MAR-22:10 | 5.60 | 4.80 |
April | 0.265911E+11 | 18528.47 | 05-APR-22:12 | 2.77 | 0.63 | 0.593284E+10 | 4023.05 | 05-APR-21:40 | 2.77 | 0.63 |
May | 0.315623E+11 | 15602.02 | 11-MAY-06:03 | 8.17 | 5.64 | 0.618886E+10 | 3854.19 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.368433E+11 | 15834.62 | 30-JUN-21:00 | 22.80 | 21.19 | 0.620859E+10 | 4038.14 | 30-JUN-21:10 | 22.77 | 21.16 |
July | 0.407292E+11 | 16668.63 | 14-JUL-21:00 | 28.30 | 21.42 | 0.668965E+10 | 4243.35 | 14-JUL-21:10 | 28.22 | 21.44 |
August | 0.431791E+11 | 17560.71 | 18-AUG-21:00 | 31.10 | 22.83 | 0.709648E+10 | 4468.42 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.438315E+11 | 18379.57 | 15-SEP-21:00 | 25.00 | 18.13 | 0.717527E+10 | 4689.17 | 14-SEP-21:10 | 25.00 | 18.13 |
October | 0.456216E+11 | 24327.65 | 12-OCT-06:32 | 7.57 | 5.73 | 0.748449E+10 | 4800.22 | 25-OCT-21:40 | 5.77 | 4.06 |
November | 0.438619E+11 | 26110.40 | 09-NOV-07:17 | 6.83 | 3.62 | 0.725590E+10 | 4810.73 | 25-NOV-00:10 | 3.22 | 2.02 |
December | 0.424733E+11 | 30598.10 | 09-DEC-08:13 | 2.23 | -1.1 | 0.713326E+10 | 4731.10 | 01-DEC-00:10 | 2.23 | -1.1 |
Annual Sum or Average | 0.454525E+12 | 0.794828E+11 | ||||||||
Minimum of Months | 0.265911E+11 | 15602.02 | 2.23 | -1.1 | 0.567066E+10 | 3854.19 | 2.23 | -1.1 | ||
Maximum of Months | 0.456216E+11 | 30598.10 | 31.10 | 22.83 | 0.748449E+10 | 4810.73 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126685E+10 | 2845.06 | 11-JAN-14:15 | 6.70 | 2.05 | 0.620894E+09 | 378.13 | 23-JAN-22:19 | 4.07 | 0.42 |
February | 0.169472E+10 | 2613.05 | 04-FEB-15:10 | 6.88 | 1.11 | 0.564945E+09 | 400.02 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.313831E+10 | 2156.87 | 30-MAR-14:20 | 27.80 | 17.60 | 0.636588E+09 | 439.50 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.355504E+10 | 2241.02 | 15-APR-14:03 | 27.80 | 15.12 | 0.622813E+09 | 432.34 | 17-APR-21:10 | 20.00 | 14.08 |
May | 0.430221E+10 | 2090.71 | 19-MAY-19:20 | 27.40 | 17.96 | 0.654688E+09 | 444.90 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.480410E+10 | 2189.27 | 13-JUN-19:20 | 30.20 | 22.02 | 0.675300E+09 | 470.66 | 13-JUN-21:10 | 28.12 | 21.63 |
July | 0.518200E+10 | 2550.25 | 08-JUL-17:04 | 34.40 | 23.36 | 0.719493E+09 | 491.78 | 07-JUL-21:10 | 34.40 | 23.36 |
August | 0.543174E+10 | 2799.01 | 19-AUG-13:40 | 33.70 | 23.70 | 0.745489E+09 | 491.78 | 18-AUG-21:19 | 33.70 | 23.70 |
September | 0.461748E+10 | 2619.13 | 25-SEP-15:03 | 29.40 | 19.56 | 0.662779E+09 | 480.27 | 07-SEP-21:10 | 29.40 | 19.56 |
October | 0.372884E+10 | 2768.85 | 10-OCT-13:40 | 29.03 | 20.94 | 0.650530E+09 | 452.18 | 10-OCT-21:10 | 21.10 | 18.77 |
November | 0.277768E+10 | 2425.69 | 26-NOV-09:30 | 6.65 | 4.96 | 0.609255E+09 | 392.22 | 08-NOV-22:10 | 6.65 | 4.96 |
December | 0.179366E+10 | 2607.50 | 18-DEC-13:20 | 7.07 | 1.00 | 0.624419E+09 | 388.70 | 12-DEC-22:10 | 7.07 | 1.00 |
Annual Sum or Average | 0.422926E+11 | 0.778719E+10 | ||||||||
Minimum of Months | 0.126685E+10 | 2090.71 | 6.65 | 1.00 | 0.564945E+09 | 378.13 | 4.07 | 0.42 | ||
Maximum of Months | 0.543174E+10 | 2845.06 | 34.40 | 23.70 | 0.745489E+09 | 491.78 | 34.40 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238644E+10 | 2205.39 | 25-JAN-23:40 | 1.30 | -1.7 | 0.728638E+09 | 509.65 | 23-JAN-22:00 | 1.30 | -1.7 |
February | 0.246095E+10 | 2205.95 | 21-FEB-07:07 | 5.60 | 3.82 | 0.667123E+09 | 505.11 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.332781E+10 | 1880.59 | 22-MAR-19:15 | 5.60 | 4.80 | 0.767189E+09 | 533.67 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.344651E+10 | 1900.06 | 06-APR-22:40 | 6.30 | 3.11 | 0.762795E+09 | 537.58 | 14-APR-21:10 | 19.53 | 13.39 |
May | 0.377027E+10 | 1680.94 | 19-MAY-21:00 | 23.90 | 16.26 | 0.811676E+09 | 551.72 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.388325E+10 | 1723.49 | 27-JUN-21:00 | 27.20 | 20.99 | 0.831906E+09 | 566.01 | 27-JUN-21:10 | 27.02 | 21.02 |
July | 0.411477E+10 | 2005.20 | 07-JUL-21:00 | 30.60 | 22.80 | 0.874160E+09 | 569.55 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.419652E+10 | 2076.21 | 18-AUG-21:00 | 31.10 | 22.83 | 0.893849E+09 | 569.52 | 18-AUG-22:19 | 29.23 | 23.14 |
September | 0.380618E+10 | 1845.45 | 08-SEP-21:00 | 25.60 | 21.61 | 0.814052E+09 | 569.49 | 08-SEP-21:19 | 25.40 | 21.58 |
October | 0.356922E+10 | 2054.37 | 12-OCT-06:32 | 7.57 | 5.73 | 0.786922E+09 | 547.27 | 11-OCT-21:10 | 7.57 | 5.73 |
November | 0.314768E+10 | 2115.39 | 09-NOV-07:17 | 6.83 | 3.62 | 0.729736E+09 | 501.58 | 08-NOV-22:10 | 6.83 | 3.62 |
December | 0.279284E+10 | 1917.06 | 08-DEC-20:12 | 5.93 | 1.30 | 0.736137E+09 | 498.70 | 09-DEC-00:10 | 2.12 | -1.1 |
Annual Sum or Average | 0.409024E+11 | 0.940418E+10 | ||||||||
Minimum of Months | 0.238644E+10 | 1680.94 | 1.30 | -1.7 | 0.667123E+09 | 498.70 | 1.30 | -1.7 | ||
Maximum of Months | 0.419652E+10 | 2205.95 | 31.10 | 22.83 | 0.893849E+09 | 569.55 | 29.23 | 23.14 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477885E+09 | 1216.29 | 20-JAN-23:53 | 10.00 | 6.79 | 0.151773E+09 | 92.01 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.932235E+09 | 1736.82 | 21-FEB-07:07 | 5.60 | 3.82 | 0.137463E+09 | 95.89 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.194612E+10 | 1363.96 | 02-MAR-23:15 | 9.03 | 7.01 | 0.154171E+09 | 101.24 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.242995E+10 | 1342.59 | 05-APR-22:12 | 2.77 | 0.63 | 0.152035E+09 | 102.53 | 19-APR-21:10 | 18.72 | 16.07 |
May | 0.294475E+10 | 1258.68 | 19-MAY-21:00 | 23.90 | 16.26 | 0.164106E+09 | 107.76 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.314398E+10 | 1342.95 | 29-JUN-21:10 | 25.92 | 21.53 | 0.173398E+09 | 114.87 | 29-JUN-21:10 | 25.92 | 21.53 |
July | 0.336612E+10 | 1393.01 | 07-JUL-21:10 | 30.40 | 22.79 | 0.184510E+09 | 119.30 | 07-JUL-21:10 | 30.40 | 22.79 |
August | 0.340569E+10 | 1396.30 | 18-AUG-21:10 | 30.82 | 22.88 | 0.187349E+09 | 119.61 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.303596E+10 | 1330.91 | 08-SEP-21:00 | 25.60 | 21.61 | 0.167145E+09 | 113.85 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.253859E+10 | 1611.48 | 12-OCT-06:32 | 7.57 | 5.73 | 0.156870E+09 | 103.21 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.180127E+10 | 1604.14 | 28-NOV-24:00 | 7.20 | 3.22 | 0.147822E+09 | 96.43 | 03-NOV-21:10 | 7.20 | 3.22 |
December | 0.100570E+10 | 1445.22 | 08-DEC-20:12 | 5.93 | 1.30 | 0.151911E+09 | 94.63 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.270282E+11 | 0.192855E+10 | ||||||||
Minimum of Months | 0.477885E+09 | 1216.29 | 2.77 | 0.63 | 0.137463E+09 | 92.01 | 7.20 | 3.22 | ||
Maximum of Months | 0.340569E+10 | 1736.82 | 30.82 | 22.88 | 0.187349E+09 | 119.61 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140697E+09 | 622.04 | 31-JAN-21:30 | 16.05 | 11.74 | 0.116653E+09 | 68.72 | 23-JAN-22:19 | 16.05 | 11.74 |
February | 0.407022E+09 | 729.45 | 21-FEB-07:07 | 5.60 | 3.82 | 0.105449E+09 | 70.85 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.994406E+09 | 741.26 | 30-MAR-21:00 | 23.90 | 16.89 | 0.117630E+09 | 74.61 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.140175E+10 | 845.46 | 05-APR-22:12 | 2.77 | 0.63 | 0.114683E+09 | 74.92 | 19-APR-21:10 | 18.72 | 16.07 |
May | 0.183561E+10 | 787.71 | 19-MAY-21:00 | 23.90 | 16.26 | 0.122526E+09 | 79.04 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.200217E+10 | 842.83 | 29-JUN-21:10 | 25.92 | 21.53 | 0.129064E+09 | 84.26 | 29-JUN-21:10 | 25.92 | 21.53 |
July | 0.214421E+10 | 878.46 | 07-JUL-21:10 | 30.40 | 22.79 | 0.137331E+09 | 87.87 | 07-JUL-21:10 | 30.40 | 22.79 |
August | 0.216958E+10 | 880.09 | 18-AUG-21:10 | 30.82 | 22.88 | 0.139463E+09 | 88.05 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.191850E+10 | 834.29 | 07-SEP-21:10 | 25.40 | 21.43 | 0.124102E+09 | 83.40 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.143209E+10 | 1017.95 | 12-OCT-06:32 | 7.57 | 5.73 | 0.118417E+09 | 75.79 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.874631E+09 | 706.57 | 08-NOV-00:30 | 5.60 | 2.82 | 0.112980E+09 | 71.06 | 03-NOV-21:10 | 5.60 | 2.82 |
December | 0.359288E+09 | 692.73 | 12-DEC-22:10 | 18.30 | 14.66 | 0.116709E+09 | 69.97 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.156799E+11 | 0.145501E+10 | ||||||||
Minimum of Months | 0.140697E+09 | 622.04 | 2.77 | 0.63 | 0.105449E+09 | 68.72 | 5.60 | 2.82 | ||
Maximum of Months | 0.216958E+10 | 1017.95 | 30.82 | 22.88 | 0.139463E+09 | 88.05 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479041E+11 | 49802.31 | 04-JAN-21:40 | 2.40 | -0.4 | 0.536342E+09 | 482.40 | 23-JAN-22:19 | 4.07 | 0.42 |
February | 0.442348E+11 | 47334.76 | 06-FEB-21:29 | 4.70 | 3.57 | 0.485954E+09 | 483.07 | 06-FEB-22:00 | 3.90 | 3.15 |
March | 0.508330E+11 | 46934.52 | 22-MAR-19:15 | 5.60 | 4.80 | 0.540755E+09 | 417.83 | 22-MAR-21:00 | 5.60 | 4.80 |
April | 0.500655E+11 | 49477.39 | 05-APR-20:43 | 4.18 | 1.21 | 0.523289E+09 | 548.25 | 05-APR-21:40 | 3.50 | 0.98 |
May | 0.529094E+11 | 38868.93 | 16-MAY-18:50 | 27.88 | 17.10 | 0.541923E+09 | 381.53 | 15-MAY-21:40 | 27.88 | 17.10 |
June | 0.523433E+11 | 38478.26 | 13-JUN-20:00 | 29.40 | 21.98 | 0.527667E+09 | 381.56 | 08-JUN-21:30 | 29.40 | 21.98 |
July | 0.543034E+11 | 38766.32 | 07-JUL-20:00 | 31.10 | 23.22 | 0.543971E+09 | 381.51 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.546652E+11 | 38663.27 | 18-AUG-20:00 | 31.70 | 22.32 | 0.546862E+09 | 381.51 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.514224E+11 | 38352.72 | 07-SEP-20:00 | 27.20 | 22.45 | 0.524551E+09 | 381.56 | 14-SEP-21:00 | 18.90 | 14.00 |
October | 0.514152E+11 | 41170.42 | 25-OCT-20:08 | 7.02 | 4.56 | 0.538544E+09 | 439.21 | 25-OCT-21:49 | 5.68 | 4.06 |
November | 0.485900E+11 | 50686.09 | 30-NOV-21:55 | 4.40 | 4.40 | 0.520892E+09 | 439.51 | 21-NOV-22:10 | 4.40 | 4.40 |
December | 0.488047E+11 | 49258.96 | 08-DEC-21:46 | 4.60 | 0.53 | 0.537754E+09 | 478.23 | 18-DEC-22:19 | 2.93 | -1.3 |
Annual Sum or Average | 0.607491E+12 | 0.636850E+10 | ||||||||
Minimum of Months | 0.442348E+11 | 38352.72 | 2.40 | -0.4 | 0.485954E+09 | 381.51 | 2.93 | -1.3 | ||
Maximum of Months | 0.546652E+11 | 50686.09 | 31.70 | 23.22 | 0.546862E+09 | 548.25 | 29.40 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149596E+11 | 12383.20 | 25-JAN-23:40 | 1.30 | -1.7 | 0.839544E+10 | 6242.45 | 23-JAN-22:00 | 1.30 | -1.7 |
February | 0.150904E+11 | 12848.04 | 24-FEB-23:26 | 6.95 | 2.53 | 0.779632E+10 | 6095.80 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.196855E+11 | 10293.18 | 02-MAR-23:15 | 9.03 | 7.01 | 0.911684E+10 | 6396.15 | 30-MAR-21:19 | 23.53 | 16.75 |
April | 0.198904E+11 | 10700.36 | 06-APR-22:40 | 6.30 | 3.11 | 0.896687E+10 | 6383.83 | 05-APR-21:40 | 6.30 | 3.11 |
May | 0.216493E+11 | 9689.34 | 19-MAY-21:12 | 23.33 | 16.07 | 0.953569E+10 | 6389.93 | 19-MAY-21:19 | 23.33 | 16.07 |
June | 0.222836E+11 | 10716.54 | 13-JUN-21:10 | 28.12 | 21.63 | 0.970074E+10 | 6461.59 | 14-JUN-22:19 | 25.20 | 19.70 |
July | 0.236413E+11 | 11553.98 | 07-JUL-21:10 | 30.40 | 22.79 | 0.101759E+11 | 6462.54 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.243860E+11 | 12016.13 | 18-AUG-21:10 | 30.82 | 22.88 | 0.104581E+11 | 6462.46 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.221482E+11 | 11369.82 | 25-SEP-15:05 | 29.40 | 19.56 | 0.960328E+10 | 6462.54 | 11-SEP-22:10 | 29.40 | 19.56 |
October | 0.210069E+11 | 11346.65 | 11-OCT-15:03 | 27.02 | 19.63 | 0.939422E+10 | 6462.55 | 10-OCT-22:10 | 27.02 | 19.63 |
November | 0.187953E+11 | 12054.41 | 26-NOV-09:30 | 6.65 | 4.96 | 0.863981E+10 | 6356.51 | 25-NOV-00:10 | 6.65 | 4.96 |
December | 0.170321E+11 | 11368.57 | 09-DEC-10:37 | 6.67 | 1.58 | 0.859266E+10 | 6390.25 | 09-DEC-00:10 | 6.67 | 1.58 |
Annual Sum or Average | 0.240569E+12 | 0.110376E+12 | ||||||||
Minimum of Months | 0.149596E+11 | 9689.34 | 1.30 | -1.7 | 0.779632E+10 | 6095.80 | 1.30 | -1.7 | ||
Maximum of Months | 0.243860E+11 | 12848.04 | 30.82 | 22.88 | 0.104581E+11 | 6462.55 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560089E+11 | 43547.62 | 25-JAN-23:40 | 1.30 | -1.7 | 0.253228E+11 | 18562.98 | 23-JAN-22:00 | 1.30 | -1.7 |
February | 0.543833E+11 | 43425.17 | 24-FEB-23:26 | 6.95 | 2.53 | 0.234320E+11 | 17780.33 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.679752E+11 | 36652.70 | 22-MAR-19:15 | 5.60 | 4.80 | 0.271255E+11 | 18471.07 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.684014E+11 | 37455.97 | 06-APR-22:40 | 6.30 | 3.11 | 0.267982E+11 | 18955.65 | 05-APR-21:40 | 6.30 | 3.11 |
May | 0.739240E+11 | 32216.87 | 19-MAY-22:00 | 22.20 | 15.66 | 0.284771E+11 | 18813.83 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.753728E+11 | 34149.76 | 13-JUN-22:00 | 27.20 | 20.99 | 0.289403E+11 | 19182.13 | 14-JUN-21:10 | 26.52 | 21.00 |
July | 0.796334E+11 | 37589.30 | 07-JUL-21:10 | 30.40 | 22.79 | 0.302789E+11 | 19185.93 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.810817E+11 | 38703.85 | 18-AUG-21:10 | 30.82 | 22.88 | 0.308766E+11 | 19185.82 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.745942E+11 | 35459.36 | 07-SEP-21:10 | 25.40 | 21.43 | 0.285291E+11 | 19185.94 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.716707E+11 | 39170.92 | 12-OCT-06:32 | 7.57 | 5.73 | 0.278650E+11 | 18771.78 | 10-OCT-22:10 | 7.57 | 5.73 |
November | 0.653228E+11 | 41320.11 | 28-NOV-24:00 | 7.20 | 3.22 | 0.259306E+11 | 18296.32 | 25-NOV-00:10 | 7.20 | 3.22 |
December | 0.617249E+11 | 49047.84 | 09-DEC-08:13 | 2.23 | -1.1 | 0.259262E+11 | 18311.39 | 09-DEC-00:10 | 2.23 | -1.1 |
Annual Sum or Average | 0.830093E+12 | 0.329502E+12 | ||||||||
Minimum of Months | 0.543833E+11 | 32216.87 | 1.30 | -1.7 | 0.234320E+11 | 17780.33 | 1.30 | -1.7 | ||
Maximum of Months | 0.810817E+11 | 49047.84 | 30.82 | 22.88 | 0.308766E+11 | 19185.94 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89154948.72 | 3098.75 | 29-JAN-16:01 | 16.52 | 6.64 | 93746325.97 | 59.07 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.178247E+09 | 3208.93 | 28-FEB-16:01 | 23.40 | 12.60 | 86455829.72 | 69.22 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.527178E+09 | 3174.16 | 12-MAR-19:01 | 14.22 | 6.79 | 0.100062E+09 | 73.35 | 13-MAR-21:10 | 21.02 | 14.24 |
April | 0.919393E+09 | 3341.15 | 09-APR-20:11 | 13.70 | 8.28 | 99513477.63 | 77.01 | 14-APR-21:30 | 18.60 | 13.02 |
May | 0.138071E+10 | 3366.00 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104218E+09 | 75.78 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.199709E+10 | 3156.96 | 05-JUN-21:51 | 22.20 | 17.55 | 99138394.14 | 82.79 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.226491E+10 | 3106.08 | 06-JUL-18:02 | 32.12 | 24.13 | 0.102042E+09 | 80.68 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.240272E+10 | 3124.74 | 14-AUG-15:02 | 31.02 | 23.06 | 0.101380E+09 | 76.55 | 07-AUG-21:00 | 31.02 | 23.06 |
September | 0.154047E+10 | 3520.55 | 18-SEP-16:01 | 25.40 | 17.60 | 99700157.31 | 77.56 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.717656E+09 | 3392.59 | 15-OCT-16:21 | 24.15 | 17.28 | 0.101467E+09 | 75.78 | 10-OCT-21:10 | 24.15 | 17.28 |
November | 0.300043E+09 | 3200.24 | 11-NOV-16:01 | 21.32 | 11.45 | 94424302.48 | 65.05 | 02-NOV-21:40 | 21.32 | 11.45 |
December | 0.134589E+09 | 3144.39 | 10-DEC-16:01 | 18.62 | 9.23 | 94765833.51 | 64.24 | 12-DEC-22:40 | 18.30 | 14.79 |
Annual Sum or Average | 0.124522E+11 | 0.117691E+10 | ||||||||
Minimum of Months | 89154948.72 | 3098.75 | 13.68 | 6.54 | 86455829.72 | 59.07 | 14.52 | 10.34 | ||
Maximum of Months | 0.240272E+10 | 3520.55 | 32.12 | 24.13 | 0.104218E+09 | 82.79 | 31.02 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46066062.08 | 1216.83 | 29-JAN-16:01 | 16.52 | 6.64 | 92817560.85 | 56.80 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.106979E+09 | 3148.29 | 28-FEB-16:01 | 23.40 | 12.60 | 85350542.13 | 66.27 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.391528E+09 | 3109.63 | 10-MAR-16:01 | 20.10 | 8.83 | 98327385.75 | 71.39 | 29-MAR-21:19 | 22.43 | 16.94 |
April | 0.796102E+09 | 3246.62 | 26-APR-18:41 | 14.60 | 7.53 | 98739941.12 | 74.73 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.132013E+10 | 3297.01 | 09-MAY-20:41 | 13.68 | 6.54 | 0.103938E+09 | 75.58 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.198184E+10 | 3121.06 | 05-JUN-21:51 | 22.20 | 17.55 | 99189455.89 | 82.67 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.223465E+10 | 3091.52 | 04-JUL-15:02 | 31.28 | 22.90 | 0.102073E+09 | 80.54 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.228273E+10 | 3086.84 | 03-AUG-15:02 | 33.90 | 23.88 | 0.101311E+09 | 76.04 | 07-AUG-21:00 | 22.20 | 21.48 |
September | 0.136220E+10 | 3310.02 | 18-SEP-16:01 | 25.40 | 17.60 | 99178497.69 | 75.70 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.517420E+09 | 3096.39 | 15-OCT-16:21 | 24.15 | 17.28 | 99528963.84 | 72.42 | 10-OCT-21:10 | 24.15 | 17.28 |
November | 0.181252E+09 | 3124.40 | 11-NOV-16:01 | 21.32 | 11.45 | 92661256.10 | 62.21 | 02-NOV-21:40 | 21.32 | 11.45 |
December | 76648217.47 | 2781.92 | 10-DEC-16:01 | 18.62 | 9.23 | 93427025.81 | 60.33 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.112975E+11 | 0.116654E+10 | ||||||||
Minimum of Months | 46066062.08 | 1216.83 | 13.68 | 6.54 | 85350542.13 | 56.80 | 14.52 | 7.53 | ||
Maximum of Months | 0.228273E+10 | 3310.02 | 33.90 | 23.88 | 0.103938E+09 | 82.67 | 25.40 | 21.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140803E+09 | 259.80 | 29-JAN-13:30 | 14.45 | 6.22 | 0.00 | 0.00 | 01-JAN-00:10 | 14.45 | 6.22 |
February | 0.201866E+09 | 434.16 | 26-FEB-14:50 | 24.90 | 12.71 | 0.00 | 0.00 | 01-FEB-00:10 | 24.90 | 12.71 |
March | 0.347068E+09 | 407.11 | 13-MAR-16:20 | 24.40 | 14.34 | 0.00 | 0.00 | 01-MAR-00:10 | 24.40 | 14.34 |
April | 0.397940E+09 | 408.48 | 15-APR-14:00 | 27.80 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 27.80 | 15.01 |
May | 0.478613E+09 | 363.90 | 19-MAY-19:10 | 27.85 | 18.11 | 0.00 | 0.00 | 01-MAY-00:10 | 27.85 | 18.11 |
June | 0.619024E+09 | 411.35 | 24-JUN-19:10 | 30.22 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 30.22 | 21.43 |
July | 0.704845E+09 | 452.31 | 08-JUL-17:30 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.796272E+09 | 483.20 | 19-AUG-13:50 | 33.80 | 23.78 | 0.00 | 0.00 | 01-AUG-00:10 | 33.80 | 23.78 |
September | 0.622811E+09 | 532.53 | 24-SEP-12:50 | 28.80 | 19.88 | 0.00 | 0.00 | 01-SEP-00:10 | 28.80 | 19.88 |
October | 0.476739E+09 | 575.74 | 10-OCT-13:30 | 28.85 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 28.85 | 20.88 |
November | 0.339964E+09 | 478.06 | 08-NOV-14:20 | 20.97 | 9.81 | 0.00 | 0.00 | 01-NOV-00:10 | 20.97 | 9.81 |
December | 0.238453E+09 | 450.28 | 10-DEC-14:30 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.536440E+10 | 0.00 | ||||||||
Minimum of Months | 0.140803E+09 | 259.80 | 14.45 | 6.22 | 0.00 | 0.00 | 14.45 | 6.22 | ||
Maximum of Months | 0.796272E+09 | 575.74 | 34.40 | 23.78 | 0.00 | 0.00 | 34.40 | 23.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81833826.60 | 962.19 | 01-JAN-09:02 | 11.78 | 10.88 | 94001242.98 | 63.67 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.149296E+09 | 1145.17 | 28-FEB-22:51 | 17.30 | 10.02 | 85854212.06 | 68.00 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.325307E+09 | 1132.35 | 31-MAR-20:12 | 13.87 | 8.46 | 97106914.93 | 70.22 | 28-MAR-21:10 | 13.87 | 8.46 |
April | 0.477466E+09 | 1155.13 | 16-APR-21:51 | 19.40 | 13.90 | 96782965.72 | 72.11 | 21-APR-21:49 | 19.40 | 17.21 |
May | 0.671240E+09 | 1215.53 | 09-MAY-20:41 | 13.68 | 6.54 | 0.101965E+09 | 74.30 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.863973E+09 | 1205.44 | 10-JUN-18:01 | 28.62 | 13.87 | 98016782.48 | 78.27 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.941102E+09 | 1142.09 | 16-JUL-18:02 | 32.52 | 22.45 | 0.101209E+09 | 77.09 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.937941E+09 | 1139.15 | 25-AUG-18:02 | 29.82 | 19.04 | 0.100407E+09 | 74.83 | 31-AUG-21:19 | 21.67 | 19.98 |
September | 0.672287E+09 | 1150.00 | 14-SEP-21:51 | 18.90 | 14.00 | 97908818.01 | 75.60 | 01-SEP-21:10 | 18.90 | 14.00 |
October | 0.402403E+09 | 1154.59 | 11-OCT-21:51 | 14.40 | 8.97 | 98353628.85 | 72.78 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.235503E+09 | 1074.43 | 08-NOV-21:11 | 14.63 | 7.29 | 92972511.67 | 67.47 | 03-NOV-21:49 | 14.63 | 7.29 |
December | 0.120238E+09 | 991.59 | 12-DEC-22:51 | 18.30 | 14.87 | 94628311.34 | 64.69 | 12-DEC-22:00 | 18.30 | 14.87 |
Annual Sum or Average | 0.587859E+10 | 0.115921E+10 | ||||||||
Minimum of Months | 81833826.60 | 962.19 | 11.78 | 6.54 | 85854212.06 | 63.67 | 13.87 | 7.29 | ||
Maximum of Months | 0.941102E+09 | 1215.53 | 32.52 | 22.45 | 0.101965E+09 | 78.27 | 23.22 | 22.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83481702.84 | 2661.57 | 29-JAN-16:01 | 16.52 | 6.64 | 93813333.06 | 59.60 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.202574E+09 | 2920.01 | 28-FEB-16:01 | 23.40 | 12.60 | 86399659.14 | 68.35 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.508295E+09 | 2890.31 | 26-MAR-15:01 | 20.10 | 9.52 | 99244218.41 | 71.38 | 13-MAR-21:10 | 20.10 | 9.52 |
April | 0.911720E+09 | 3129.50 | 14-APR-08:51 | 19.40 | 14.17 | 98847872.82 | 74.13 | 14-APR-21:30 | 18.60 | 13.02 |
May | 0.140965E+10 | 3191.84 | 18-MAY-08:51 | 24.40 | 17.97 | 0.104087E+09 | 76.67 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.201383E+10 | 3209.59 | 04-JUN-08:51 | 24.40 | 18.28 | 99550106.95 | 79.46 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.230913E+10 | 3069.77 | 25-JUL-08:51 | 24.40 | 20.24 | 0.102648E+09 | 81.36 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.240193E+10 | 3118.73 | 26-AUG-08:51 | 24.40 | 19.19 | 0.101676E+09 | 78.13 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.154024E+10 | 3154.05 | 15-SEP-08:51 | 21.70 | 14.94 | 99753242.70 | 76.64 | 11-SEP-21:00 | 21.70 | 14.94 |
October | 0.730595E+09 | 2889.57 | 13-OCT-15:02 | 21.78 | 12.23 | 0.100745E+09 | 74.48 | 10-OCT-21:10 | 21.78 | 12.23 |
November | 0.301965E+09 | 2897.72 | 11-NOV-16:01 | 21.32 | 11.45 | 94137649.24 | 64.31 | 02-NOV-21:40 | 21.32 | 11.45 |
December | 0.134136E+09 | 2750.16 | 10-DEC-16:01 | 18.62 | 9.23 | 94768645.86 | 63.67 | 12-DEC-22:40 | 18.30 | 14.79 |
Annual Sum or Average | 0.125475E+11 | 0.117567E+10 | ||||||||
Minimum of Months | 83481702.84 | 2661.57 | 16.52 | 6.64 | 86399659.14 | 59.60 | 14.52 | 9.52 | ||
Maximum of Months | 0.240193E+10 | 3209.59 | 24.40 | 20.24 | 0.104087E+09 | 81.36 | 24.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47312724.43 | 577.71 | 29-JAN-17:44 | 14.60 | 5.92 | 92844002.67 | 57.35 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.128153E+09 | 2771.15 | 28-FEB-16:01 | 23.40 | 12.60 | 85214554.73 | 65.36 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.373289E+09 | 2714.55 | 30-MAR-18:02 | 26.02 | 17.62 | 97405874.90 | 68.35 | 30-MAR-21:00 | 22.80 | 16.45 |
April | 0.780763E+09 | 3082.06 | 14-APR-08:51 | 19.40 | 14.17 | 98181069.11 | 72.38 | 17-APR-21:00 | 20.00 | 13.85 |
May | 0.134441E+10 | 3168.82 | 18-MAY-08:51 | 24.40 | 17.97 | 0.103897E+09 | 76.48 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.199768E+10 | 3191.92 | 04-JUN-08:51 | 24.40 | 18.28 | 99599250.59 | 79.36 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.227775E+10 | 3049.77 | 03-JUL-08:41 | 25.40 | 20.44 | 0.102671E+09 | 81.16 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.228000E+10 | 3090.40 | 26-AUG-08:51 | 24.40 | 19.19 | 0.101616E+09 | 77.62 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.135313E+10 | 3054.40 | 15-SEP-08:51 | 21.70 | 14.94 | 99318574.81 | 75.48 | 01-SEP-21:10 | 21.70 | 14.94 |
October | 0.524735E+09 | 2654.01 | 10-OCT-18:02 | 25.63 | 20.24 | 98875173.45 | 72.06 | 17-OCT-21:10 | 23.22 | 20.61 |
November | 0.185338E+09 | 2444.15 | 06-NOV-09:02 | 12.57 | 11.17 | 92167956.89 | 62.57 | 03-NOV-21:30 | 12.57 | 11.17 |
December | 76179439.72 | 1566.83 | 12-DEC-22:51 | 18.30 | 14.87 | 93383376.33 | 59.78 | 12-DEC-22:30 | 18.30 | 14.87 |
Annual Sum or Average | 0.113687E+11 | 0.116517E+10 | ||||||||
Minimum of Months | 47312724.43 | 577.71 | 12.57 | 5.92 | 85214554.73 | 57.35 | 12.57 | 10.34 | ||
Maximum of Months | 0.228000E+10 | 3191.92 | 26.02 | 20.44 | 0.103897E+09 | 81.16 | 24.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171548E+10 | 2259.25 | 23-JAN-22:13 | 4.07 | 0.42 | 0.119912E+10 | 725.22 | 23-JAN-22:00 | 4.40 | 0.70 |
February | 0.238484E+10 | 3083.71 | 24-FEB-23:26 | 6.95 | 2.53 | 0.108780E+10 | 754.79 | 28-FEB-22:30 | 18.10 | 10.49 |
March | 0.441690E+10 | 2557.76 | 02-MAR-23:15 | 9.03 | 7.01 | 0.122530E+10 | 780.85 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.500374E+10 | 2488.91 | 05-APR-22:12 | 2.77 | 0.63 | 0.122412E+10 | 809.84 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.565173E+10 | 2290.02 | 31-MAY-21:10 | 22.13 | 18.80 | 0.131688E+10 | 825.46 | 31-MAY-22:10 | 21.73 | 18.83 |
June | 0.585488E+10 | 2416.91 | 29-JUN-21:10 | 25.92 | 21.53 | 0.135925E+10 | 869.83 | 29-JUN-21:19 | 25.73 | 21.59 |
July | 0.621703E+10 | 2467.23 | 07-JUL-21:10 | 30.40 | 22.79 | 0.143469E+10 | 888.34 | 07-JUL-21:19 | 30.20 | 22.78 |
August | 0.624312E+10 | 2488.10 | 18-AUG-21:10 | 30.82 | 22.88 | 0.144639E+10 | 895.92 | 18-AUG-21:19 | 30.53 | 22.93 |
September | 0.568539E+10 | 2379.19 | 08-SEP-21:10 | 25.50 | 21.60 | 0.131868E+10 | 856.72 | 08-SEP-21:19 | 25.40 | 21.58 |
October | 0.487701E+10 | 2994.01 | 12-OCT-06:32 | 7.57 | 5.73 | 0.124783E+10 | 803.55 | 11-OCT-21:19 | 7.57 | 5.73 |
November | 0.373041E+10 | 2881.67 | 07-NOV-23:10 | 7.85 | 3.87 | 0.116553E+10 | 735.76 | 02-NOV-21:40 | 7.85 | 3.87 |
December | 0.253568E+10 | 2700.43 | 08-DEC-20:12 | 5.93 | 1.30 | 0.120007E+10 | 733.35 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.543162E+11 | 0.152256E+11 | ||||||||
Minimum of Months | 0.171548E+10 | 2259.25 | 2.77 | 0.42 | 0.108780E+10 | 725.22 | 4.40 | 0.70 | ||
Maximum of Months | 0.624312E+10 | 3083.71 | 30.82 | 22.88 | 0.144639E+10 | 895.92 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68882983.17 | 3227.61 | 29-JAN-16:01 | 16.52 | 6.64 | 93213809.46 | 57.23 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.158340E+09 | 3359.50 | 28-FEB-16:01 | 23.40 | 12.60 | 86185751.39 | 70.50 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.521237E+09 | 3397.32 | 12-MAR-19:01 | 14.22 | 6.79 | 0.100174E+09 | 74.99 | 13-MAR-21:10 | 21.02 | 14.24 |
April | 0.970997E+09 | 3694.62 | 09-APR-20:11 | 13.70 | 8.28 | 0.100078E+09 | 79.54 | 14-APR-21:30 | 18.60 | 13.02 |
May | 0.152089E+10 | 3646.34 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104787E+09 | 79.68 | 10-MAY-21:10 | 14.72 | 7.99 |
June | 0.216323E+10 | 3276.65 | 05-JUN-21:51 | 22.20 | 17.55 | 99135391.27 | 84.92 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.244684E+10 | 3253.57 | 23-JUL-15:02 | 28.98 | 23.33 | 0.101954E+09 | 81.43 | 18-JUL-21:00 | 28.98 | 23.33 |
August | 0.258126E+10 | 3266.36 | 21-AUG-18:02 | 29.82 | 24.23 | 0.101287E+09 | 77.02 | 07-AUG-21:00 | 29.82 | 24.23 |
September | 0.162486E+10 | 3673.12 | 18-SEP-16:01 | 25.40 | 17.60 | 99737488.37 | 77.89 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.726437E+09 | 3699.50 | 15-OCT-16:21 | 24.15 | 17.28 | 0.101812E+09 | 76.90 | 10-OCT-21:30 | 24.15 | 17.28 |
November | 0.270307E+09 | 3348.97 | 11-NOV-16:01 | 21.32 | 11.45 | 94233077.35 | 65.30 | 02-NOV-21:40 | 21.32 | 11.45 |
December | 0.111699E+09 | 3283.53 | 10-DEC-16:01 | 18.62 | 9.23 | 94235450.46 | 63.84 | 12-DEC-22:40 | 18.30 | 14.79 |
Annual Sum or Average | 0.131650E+11 | 0.117683E+10 | ||||||||
Minimum of Months | 68882983.17 | 3227.61 | 13.68 | 6.54 | 86185751.39 | 57.23 | 14.52 | 7.99 | ||
Maximum of Months | 0.258126E+10 | 3699.50 | 29.82 | 24.23 | 0.104787E+09 | 84.92 | 29.82 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32666689.23 | 647.21 | 11-JAN-16:05 | 7.02 | 2.10 | 92491749.04 | 56.69 | 03-JAN-23:49 | 7.02 | 2.10 |
February | 92790289.59 | 3290.48 | 28-FEB-16:01 | 23.40 | 12.60 | 85105412.19 | 67.09 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.383022E+09 | 3249.60 | 10-MAR-16:01 | 20.10 | 8.83 | 98280037.90 | 72.18 | 29-MAR-21:19 | 22.43 | 16.94 |
April | 0.834705E+09 | 3524.94 | 09-APR-20:11 | 13.70 | 8.28 | 99336903.63 | 77.23 | 14-APR-21:30 | 18.60 | 13.02 |
May | 0.145221E+10 | 3569.38 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104536E+09 | 78.33 | 10-MAY-21:10 | 14.72 | 7.99 |
June | 0.214724E+10 | 3242.76 | 07-JUN-21:51 | 17.80 | 12.14 | 99190664.76 | 84.85 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.241573E+10 | 3225.78 | 19-JUL-15:02 | 30.78 | 23.68 | 0.101985E+09 | 81.24 | 18-JUL-21:19 | 30.78 | 23.68 |
August | 0.245553E+10 | 3239.42 | 21-AUG-15:02 | 30.00 | 24.22 | 0.101220E+09 | 76.50 | 07-AUG-21:00 | 30.00 | 24.22 |
September | 0.143016E+10 | 3562.82 | 18-SEP-16:01 | 25.40 | 17.60 | 99212427.19 | 75.99 | 01-SEP-21:10 | 25.40 | 17.60 |
October | 0.510405E+09 | 3320.30 | 15-OCT-16:21 | 24.15 | 17.28 | 99618375.15 | 73.18 | 10-OCT-21:19 | 24.15 | 17.28 |
November | 0.159690E+09 | 3257.60 | 11-NOV-16:01 | 21.32 | 11.45 | 92293351.90 | 61.83 | 02-NOV-21:40 | 21.32 | 11.45 |
December | 60048078.26 | 2582.13 | 11-DEC-16:01 | 21.02 | 15.88 | 92944091.26 | 59.24 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.119742E+11 | 0.116621E+10 | ||||||||
Minimum of Months | 32666689.23 | 647.21 | 7.02 | 2.10 | 85105412.19 | 56.69 | 7.02 | 2.10 | ||
Maximum of Months | 0.245553E+10 | 3569.38 | 30.78 | 24.22 | 0.104536E+09 | 84.85 | 30.78 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167325E+09 | 1788.70 | 29-JAN-17:41 | 14.60 | 5.92 | 95592868.82 | 67.41 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.248978E+09 | 1800.80 | 21-FEB-22:11 | 14.23 | 7.93 | 87975091.69 | 77.05 | 21-FEB-22:10 | 14.23 | 7.93 |
March | 0.517718E+09 | 1818.84 | 13-MAR-21:51 | 20.60 | 14.62 | 0.100943E+09 | 78.26 | 13-MAR-21:40 | 20.60 | 14.62 |
April | 0.660077E+09 | 1824.74 | 09-APR-20:11 | 13.70 | 8.28 | 99279556.49 | 77.57 | 12-APR-21:40 | 18.33 | 13.45 |
May | 0.881774E+09 | 1808.70 | 09-MAY-20:41 | 13.68 | 6.54 | 0.103594E+09 | 76.59 | 31-MAY-21:19 | 22.07 | 18.80 |
June | 0.117957E+10 | 1711.05 | 12-JUN-15:02 | 33.30 | 22.58 | 98676474.58 | 81.54 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.135197E+10 | 1714.87 | 04-JUL-15:02 | 31.28 | 22.90 | 0.101866E+09 | 80.07 | 25-JUL-21:19 | 22.80 | 21.95 |
August | 0.150625E+10 | 1722.45 | 21-AUG-15:02 | 30.00 | 24.22 | 0.101317E+09 | 77.95 | 31-AUG-21:40 | 21.63 | 19.82 |
September | 0.110110E+10 | 1895.99 | 18-SEP-16:01 | 25.40 | 17.60 | 99992569.42 | 78.61 | 01-SEP-21:19 | 25.40 | 17.60 |
October | 0.737078E+09 | 1951.44 | 15-OCT-16:21 | 24.15 | 17.28 | 0.102909E+09 | 80.28 | 10-OCT-21:49 | 24.15 | 17.28 |
November | 0.477321E+09 | 1808.91 | 08-NOV-21:11 | 14.63 | 7.29 | 96529115.60 | 73.03 | 02-NOV-21:40 | 14.63 | 7.29 |
December | 0.279224E+09 | 1772.70 | 10-DEC-19:21 | 14.15 | 7.08 | 96771191.38 | 73.73 | 12-DEC-22:49 | 18.30 | 14.83 |
Annual Sum or Average | 0.910837E+10 | 0.118545E+10 | ||||||||
Minimum of Months | 0.167325E+09 | 1711.05 | 13.68 | 5.92 | 87975091.69 | 67.41 | 14.13 | 7.29 | ||
Maximum of Months | 0.150625E+10 | 1951.44 | 33.30 | 24.22 | 0.103594E+09 | 81.54 | 25.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333717E+11 | 29904.61 | 23-JAN-22:53 | 4.40 | 0.70 | 0.166892E+11 | 12201.01 | 23-JAN-22:19 | 4.40 | 0.70 |
February | 0.315854E+11 | 33263.68 | 08-FEB-22:27 | 0.85 | -2.6 | 0.155201E+11 | 11830.94 | 08-FEB-00:49 | 0.85 | -2.6 |
March | 0.378130E+11 | 27152.52 | 22-MAR-22:03 | 5.60 | 4.80 | 0.179935E+11 | 11724.22 | 25-MAR-04:49 | 5.10 | 2.72 |
April | 0.382864E+11 | 30789.27 | 05-APR-22:04 | 3.03 | 0.78 | 0.178075E+11 | 12943.04 | 05-APR-21:40 | 3.03 | 0.78 |
May | 0.417137E+11 | 22317.59 | 16-MAY-18:50 | 27.88 | 17.10 | 0.187978E+11 | 11348.73 | 10-MAY-21:40 | 27.88 | 17.10 |
June | 0.428411E+11 | 22870.89 | 13-JUN-21:10 | 28.12 | 21.63 | 0.184739E+11 | 11348.72 | 07-JUN-22:10 | 28.12 | 21.63 |
July | 0.450980E+11 | 23634.46 | 07-JUL-21:10 | 30.40 | 22.79 | 0.190586E+11 | 11348.71 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.452729E+11 | 23376.93 | 18-AUG-21:10 | 30.82 | 22.88 | 0.191600E+11 | 11348.54 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.406031E+11 | 22043.36 | 07-SEP-21:10 | 25.40 | 21.43 | 0.181996E+11 | 11348.79 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.386353E+11 | 29043.40 | 25-OCT-22:03 | 5.50 | 4.00 | 0.180893E+11 | 11663.62 | 25-OCT-21:30 | 5.50 | 4.00 |
November | 0.354471E+11 | 34369.63 | 30-NOV-23:41 | 2.20 | 2.20 | 0.169822E+11 | 12505.40 | 25-NOV-00:10 | 2.20 | 2.20 |
December | 0.347953E+11 | 34287.65 | 01-DEC-23:31 | 2.97 | -0.7 | 0.170844E+11 | 12808.59 | 09-DEC-00:10 | 2.12 | -1.1 |
Annual Sum or Average | 0.465463E+12 | 0.213856E+12 | ||||||||
Minimum of Months | 0.315854E+11 | 22043.36 | 0.85 | -2.6 | 0.155201E+11 | 11348.54 | 0.85 | -2.6 | ||
Maximum of Months | 0.452729E+11 | 34369.63 | 30.82 | 22.88 | 0.191600E+11 | 12943.04 | 28.12 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363240E+11 | 32240.07 | 04-JAN-21:43 | 2.30 | -0.4 | 0.170073E+11 | 12329.86 | 23-JAN-22:19 | 4.07 | 0.42 |
February | 0.343395E+11 | 35265.94 | 08-FEB-22:27 | 0.85 | -2.6 | 0.158238E+11 | 12235.82 | 06-FEB-22:00 | 0.85 | -2.6 |
March | 0.410257E+11 | 31525.74 | 22-MAR-22:03 | 5.60 | 4.80 | 0.183252E+11 | 11887.21 | 25-MAR-04:49 | 5.10 | 2.72 |
April | 0.415092E+11 | 32542.85 | 05-APR-22:04 | 3.03 | 0.78 | 0.180642E+11 | 13020.52 | 05-APR-21:40 | 3.03 | 0.78 |
May | 0.451099E+11 | 24464.09 | 16-MAY-18:50 | 27.88 | 17.10 | 0.189677E+11 | 11348.74 | 10-MAY-21:40 | 27.88 | 17.10 |
June | 0.459215E+11 | 24342.62 | 13-JUN-21:10 | 28.12 | 21.63 | 0.185547E+11 | 11348.72 | 07-JUN-22:10 | 28.12 | 21.63 |
July | 0.481336E+11 | 24944.34 | 07-JUL-21:10 | 30.40 | 22.79 | 0.191267E+11 | 11348.71 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.482610E+11 | 24665.84 | 18-AUG-21:10 | 30.82 | 22.88 | 0.192164E+11 | 11348.55 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.437430E+11 | 23515.89 | 07-SEP-21:10 | 25.40 | 21.43 | 0.183464E+11 | 11348.80 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.418518E+11 | 32260.57 | 25-OCT-22:03 | 5.50 | 4.00 | 0.183993E+11 | 11784.74 | 25-OCT-21:30 | 5.50 | 4.00 |
November | 0.384350E+11 | 36165.32 | 30-NOV-23:41 | 2.20 | 2.20 | 0.173329E+11 | 12607.41 | 25-NOV-00:10 | 2.20 | 2.20 |
December | 0.377616E+11 | 36073.55 | 01-DEC-23:31 | 2.97 | -0.7 | 0.174464E+11 | 12901.90 | 09-DEC-00:10 | 2.12 | -1.1 |
Annual Sum or Average | 0.502416E+12 | 0.216611E+12 | ||||||||
Minimum of Months | 0.343395E+11 | 23515.89 | 0.85 | -2.6 | 0.158238E+11 | 11348.55 | 0.85 | -2.6 | ||
Maximum of Months | 0.482610E+11 | 36165.32 | 30.82 | 22.88 | 0.192164E+11 | 13020.52 | 28.12 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476908E+11 | 35542.50 | 22-JAN-17:49 | 2.98 | -0.3 | 0.187106E+11 | 11360.87 | 21-JAN-18:10 | 2.98 | -0.3 |
February | 0.447285E+11 | 33894.69 | 06-FEB-11:36 | 1.83 | 0.46 | 0.169103E+11 | 11456.34 | 04-FEB-18:40 | 1.83 | 0.46 |
March | 0.525806E+11 | 33069.19 | 22-MAR-18:07 | 5.60 | 4.80 | 0.187395E+11 | 11321.99 | 18-MAR-17:49 | 5.60 | 4.80 |
April | 0.528375E+11 | 33426.32 | 07-APR-07:03 | 3.53 | 2.17 | 0.181431E+11 | 11340.78 | 15-APR-17:19 | 26.13 | 15.35 |
May | 0.565369E+11 | 31573.44 | 15-MAY-18:07 | 27.70 | 16.54 | 0.187627E+11 | 11337.07 | 13-MAY-17:10 | 27.70 | 16.54 |
June | 0.564051E+11 | 30523.98 | 25-JUN-10:40 | 29.80 | 23.29 | 0.181752E+11 | 11321.13 | 10-JUN-17:30 | 29.80 | 23.29 |
July | 0.588055E+11 | 31067.00 | 08-JUL-10:50 | 33.53 | 24.57 | 0.187808E+11 | 11319.65 | 08-JUL-17:19 | 34.40 | 23.36 |
August | 0.589018E+11 | 30899.43 | 27-AUG-10:50 | 30.03 | 22.67 | 0.187905E+11 | 11319.65 | 26-AUG-17:19 | 30.03 | 22.67 |
September | 0.547628E+11 | 30358.57 | 09-SEP-10:50 | 30.32 | 23.97 | 0.181628E+11 | 11319.62 | 23-SEP-17:19 | 27.23 | 18.81 |
October | 0.535213E+11 | 33348.01 | 26-OCT-06:50 | 2.20 | 1.95 | 0.187420E+11 | 11319.51 | 28-OCT-17:19 | 17.03 | 17.03 |
November | 0.495908E+11 | 35480.75 | 25-NOV-08:09 | 1.65 | 0.80 | 0.181214E+11 | 11319.52 | 04-NOV-17:19 | 1.65 | 0.80 |
December | 0.491865E+11 | 35443.13 | 21-DEC-07:40 | 1.70 | 0.71 | 0.187185E+11 | 11383.39 | 02-DEC-18:19 | 1.70 | 0.71 |
Annual Sum or Average | 0.635548E+12 | 0.220757E+12 | ||||||||
Minimum of Months | 0.447285E+11 | 30358.57 | 1.65 | -0.3 | 0.169103E+11 | 11319.51 | 1.65 | -0.3 | ||
Maximum of Months | 0.589018E+11 | 35542.50 | 33.53 | 24.57 | 0.187905E+11 | 11456.34 | 34.40 | 23.36 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219829E+10 | 4193.53 | 23-JAN-22:13 | 4.07 | 0.42 | 0.126864E+10 | 758.54 | 23-JAN-22:19 | 4.07 | 0.42 |
February | 0.385165E+10 | 4134.64 | 28-FEB-22:10 | 18.63 | 10.80 | 0.114952E+10 | 791.02 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.789829E+10 | 4471.46 | 30-MAR-21:10 | 23.72 | 16.82 | 0.129163E+10 | 848.43 | 30-MAR-21:19 | 23.53 | 16.75 |
April | 0.950133E+10 | 4891.32 | 17-APR-17:12 | 27.77 | 16.46 | 0.128809E+10 | 871.71 | 17-APR-21:10 | 20.00 | 14.08 |
May | 0.113974E+11 | 4865.85 | 20-MAY-15:20 | 28.50 | 18.87 | 0.139584E+10 | 908.54 | 19-MAY-21:10 | 28.50 | 18.87 |
June | 0.120841E+11 | 5120.93 | 24-JUN-18:02 | 31.93 | 22.02 | 0.146363E+10 | 956.22 | 13-JUN-21:10 | 31.93 | 22.02 |
July | 0.129017E+11 | 6163.06 | 08-JUL-17:12 | 34.40 | 23.36 | 0.155248E+10 | 1003.95 | 07-JUL-21:10 | 34.40 | 23.36 |
August | 0.130173E+11 | 5618.01 | 18-AUG-15:25 | 34.70 | 23.13 | 0.157413E+10 | 1002.44 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.113291E+11 | 5025.24 | 07-SEP-16:00 | 31.70 | 23.71 | 0.137909E+10 | 937.20 | 07-SEP-21:10 | 25.40 | 21.43 |
October | 0.900010E+10 | 4589.93 | 11-OCT-15:50 | 26.28 | 17.62 | 0.130639E+10 | 849.59 | 10-OCT-21:10 | 26.28 | 17.62 |
November | 0.632808E+10 | 4149.69 | 05-NOV-15:10 | 23.98 | 18.38 | 0.123077E+10 | 771.35 | 02-NOV-21:30 | 23.98 | 18.38 |
December | 0.372645E+10 | 4040.24 | 07-DEC-23:17 | 6.50 | 3.27 | 0.126923E+10 | 768.06 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.103234E+12 | 0.161694E+11 | ||||||||
Minimum of Months | 0.219829E+10 | 4040.24 | 4.07 | 0.42 | 0.114952E+10 | 758.54 | 4.07 | 0.42 | ||
Maximum of Months | 0.130173E+11 | 6163.06 | 34.70 | 23.71 | 0.157413E+10 | 1003.95 | 34.40 | 23.36 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510821E+09 | 1096.37 | 08-JAN-06:00 | -5.0 |
February | 0.257586E+09 | 1205.43 | 12-FEB-07:00 | -12.8 |
March | 9093397.63 | 263.13 | 18-MAR-06:47 | 2.30 |
April | 3536226.94 | 287.79 | 06-APR-06:07 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 1229132.43 | 127.80 | 26-OCT-06:42 | 2.20 |
November | 33214062.16 | 755.09 | 21-NOV-07:10 | -2.8 |
December | 0.126109E+09 | 896.49 | 01-DEC-07:03 | -3.8 |
Annual Sum or Average | 0.941589E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.510821E+09 | 1205.43 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272721E+09 | 563.55 | 08-JAN-06:00 | -5.0 |
February | 0.158906E+09 | 564.03 | 13-FEB-05:00 | -5.0 |
March | 10171.07 | 132.68 | 18-MAR-06:02 | 2.70 |
April | 3195.73 | 32.20 | 07-APR-04:06 | 3.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 1193823.43 | 97.28 | 22-NOV-04:50 | -2.8 |
December | 26733806.64 | 281.65 | 18-DEC-05:00 | -5.0 |
Annual Sum or Average | 0.459568E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.272721E+09 | 564.03 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355919E+09 | 414.13 | 08-JAN-06:00 | -5.0 |
February | 0.199429E+09 | 426.12 | 12-FEB-07:05 | -12.7 |
March | 1601165.41 | 80.68 | 19-MAR-04:50 | 2.12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 11557661.62 | 184.18 | 22-NOV-05:00 | -2.8 |
December | 77295482.84 | 315.52 | 18-DEC-05:00 | -5.0 |
Annual Sum or Average | 0.645802E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.7 | |
Maximum of Months | 0.355919E+09 | 426.12 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3893477.06 | 634.87 | 09-JAN-09:20 | -3.1 |
February | 61889.68 | 618.90 | 21-FEB-07:08 | 5.60 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 3955366.74 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 3893477.06 | 634.87 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.999585E+09 | 1588.41 | 03-JAN-16:01 | 2.80 |
February | 0.580195E+09 | 1563.11 | 12-FEB-09:02 | -10.2 |
March | 98364218.65 | 1491.84 | 22-MAR-08:62 | 4.90 |
April | 30692026.41 | 1482.31 | 06-APR-08:62 | 5.37 |
May | 1657086.61 | 1004.81 | 16-MAY-08:53 | 21.70 |
June | 529392.04 | 869.50 | 07-JUN-08:53 | 18.90 |
July | 279400.77 | 496.01 | 30-JUL-08:55 | 23.90 |
August | 180071.20 | 611.40 | 09-AUG-08:04 | 26.38 |
September | 1246949.89 | 1000.28 | 15-SEP-08:53 | 21.70 |
October | 61531264.66 | 1483.96 | 31-OCT-08:62 | 7.80 |
November | 0.213065E+09 | 1512.80 | 30-NOV-16:02 | 7.20 |
December | 0.615745E+09 | 1569.78 | 31-DEC-19:01 | 5.50 |
Annual Sum or Average | 0.260307E+10 | |||
Minimum of Months | 180071.20 | 496.01 | -10.2 | |
Maximum of Months | 0.999585E+09 | 1588.41 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126063E+10 | 1587.85 | 03-JAN-16:01 | 2.80 |
February | 0.742135E+09 | 1582.73 | 12-FEB-09:02 | -10.2 |
March | 0.145192E+09 | 1520.11 | 18-MAR-08:11 | 3.17 |
April | 38254954.50 | 1489.40 | 06-APR-08:62 | 5.37 |
May | 1714492.90 | 1025.15 | 16-MAY-08:53 | 21.70 |
June | 455783.83 | 1015.52 | 07-JUN-08:53 | 18.90 |
July | 287859.49 | 503.96 | 30-JUL-08:55 | 23.90 |
August | 204074.30 | 622.12 | 09-AUG-08:04 | 26.38 |
September | 1296210.51 | 912.49 | 23-SEP-08:53 | 22.20 |
October | 87441529.09 | 1504.65 | 26-OCT-08:62 | 5.05 |
November | 0.334358E+09 | 1536.19 | 21-NOV-09:02 | -0.1 |
December | 0.832696E+09 | 1573.67 | 21-DEC-19:01 | 5.60 |
Annual Sum or Average | 0.344466E+10 | |||
Minimum of Months | 204074.30 | 503.96 | -10.2 | |
Maximum of Months | 0.126063E+10 | 1587.85 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45865777.23 | 259.92 | 08-JAN-05:10 | -5.5 |
February | 12987663.31 | 283.54 | 12-FEB-06:00 | -12.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 1247027.60 | 76.65 | 26-DEC-05:00 | 3.90 |
Annual Sum or Average | 60100468.14 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 45865777.23 | 283.54 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185797E+09 | 475.88 | 27-JAN-16:01 | 4.40 |
February | 0.102456E+09 | 473.30 | 12-FEB-16:02 | 3.40 |
March | 3161275.46 | 436.42 | 22-MAR-15:02 | 5.10 |
April | 950215.76 | 410.84 | 06-APR-08:62 | 5.37 |
May | 280450.36 | 214.12 | 12-MAY-08:05 | 15.28 |
June | 117830.27 | 229.58 | 03-JUN-21:56 | 20.60 |
July | 29481.43 | 161.94 | 07-JUL-08:07 | 27.15 |
August | 157873.21 | 126.35 | 17-AUG-08:07 | 26.47 |
September | 418584.14 | 316.79 | 15-SEP-08:53 | 21.70 |
October | 1709825.27 | 431.32 | 26-OCT-08:62 | 5.05 |
November | 16537737.81 | 449.50 | 22-NOV-16:02 | 12.02 |
December | 74124711.19 | 464.82 | 03-DEC-16:01 | 6.52 |
Annual Sum or Average | 0.385741E+09 | |||
Minimum of Months | 29481.43 | 126.35 | 3.40 | |
Maximum of Months | 0.185797E+09 | 475.88 | 27.15 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100442E+10 | 1547.17 | 03-JAN-16:01 | 2.80 |
February | 0.571842E+09 | 1509.98 | 11-FEB-19:02 | -6.2 |
March | 0.107337E+09 | 1457.39 | 22-MAR-08:62 | 4.90 |
April | 30581900.56 | 850.79 | 24-APR-21:04 | 13.22 |
May | 739407.67 | 853.66 | 10-MAY-21:23 | 14.15 |
June | 89070.47 | 473.18 | 07-JUN-21:54 | 17.80 |
July | 136808.73 | 465.01 | 28-JUL-21:55 | 17.80 |
August | 9933.30 | 79.34 | 21-AUG-08:56 | 23.30 |
September | 620082.05 | 453.59 | 03-SEP-08:55 | 22.80 |
October | 64955137.59 | 1449.39 | 31-OCT-08:62 | 7.80 |
November | 0.212789E+09 | 1478.77 | 30-NOV-16:02 | 7.20 |
December | 0.603321E+09 | 1528.91 | 21-DEC-19:01 | 5.60 |
Annual Sum or Average | 0.259684E+10 | |||
Minimum of Months | 9933.30 | 79.34 | -6.2 | |
Maximum of Months | 0.100442E+10 | 1547.17 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126993E+10 | 1548.23 | 03-JAN-16:01 | 2.80 |
February | 0.724709E+09 | 1518.87 | 05-FEB-19:01 | 3.30 |
March | 0.150724E+09 | 1462.81 | 22-MAR-08:62 | 4.90 |
April | 37932918.99 | 1181.35 | 09-APR-20:13 | 13.70 |
May | 828397.55 | 1013.31 | 10-MAY-21:23 | 14.15 |
June | 96453.58 | 511.62 | 07-JUN-21:54 | 17.80 |
July | 139576.84 | 463.00 | 28-JUL-21:55 | 17.80 |
August | 14582.92 | 100.14 | 31-AUG-08:55 | 21.10 |
September | 764084.74 | 556.53 | 17-SEP-18:05 | 24.03 |
October | 92989712.19 | 1449.94 | 31-OCT-08:62 | 7.80 |
November | 0.325567E+09 | 1480.67 | 30-NOV-16:02 | 7.20 |
December | 0.817277E+09 | 1534.21 | 21-DEC-19:01 | 5.60 |
Annual Sum or Average | 0.342097E+10 | |||
Minimum of Months | 14582.92 | 100.14 | 2.80 | |
Maximum of Months | 0.126993E+10 | 1548.23 | 24.03 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96640684.78 | 574.11 | 07-JAN-17:00 | -5.0 |
February | 32102798.10 | 550.87 | 12-FEB-08:03 | -11.9 |
March | 14620.85 | 194.94 | 18-MAR-06:02 | 2.70 |
April | 3211.28 | 21.41 | 07-APR-06:40 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 21585.60 | 37.83 | 14-NOV-06:38 | 3.50 |
December | 1412253.75 | 543.28 | 09-DEC-08:15 | 2.23 |
Annual Sum or Average | 0.130195E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 96640684.78 | 574.11 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146350E+10 | 1862.33 | 03-JAN-16:01 | 2.80 |
February | 0.875598E+09 | 1849.11 | 12-FEB-09:13 | -9.8 |
March | 0.188879E+09 | 1788.92 | 18-MAR-08:11 | 3.17 |
April | 57254838.44 | 1759.49 | 06-APR-08:62 | 5.37 |
May | 1414753.40 | 948.50 | 17-MAY-08:53 | 22.20 |
June | 493542.61 | 951.28 | 10-JUN-08:53 | 20.60 |
July | 314336.52 | 457.05 | 30-JUL-08:55 | 23.90 |
August | 208185.51 | 798.61 | 09-AUG-08:04 | 26.38 |
September | 2174549.91 | 781.53 | 23-SEP-08:53 | 22.20 |
October | 0.123327E+09 | 1758.91 | 26-OCT-08:62 | 5.05 |
November | 0.376583E+09 | 1779.32 | 22-NOV-09:02 | 1.05 |
December | 0.962464E+09 | 1842.72 | 21-DEC-19:01 | 5.60 |
Annual Sum or Average | 0.405221E+10 | |||
Minimum of Months | 208185.51 | 457.05 | -9.8 | |
Maximum of Months | 0.146350E+10 | 1862.33 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178657E+10 | 1862.89 | 03-JAN-16:01 | 2.80 |
February | 0.107903E+10 | 1874.70 | 12-FEB-09:13 | -9.8 |
March | 0.262684E+09 | 1802.62 | 18-MAR-08:11 | 3.17 |
April | 69277893.05 | 1765.73 | 06-APR-08:62 | 5.37 |
May | 1466878.73 | 971.34 | 16-MAY-08:53 | 21.70 |
June | 459570.24 | 1029.56 | 10-JUN-08:53 | 20.60 |
July | 264671.87 | 464.11 | 30-JUL-08:55 | 23.90 |
August | 232087.42 | 806.95 | 09-AUG-08:04 | 26.38 |
September | 2402454.15 | 756.81 | 29-SEP-21:53 | 18.30 |
October | 0.169358E+09 | 1775.41 | 26-OCT-08:62 | 5.05 |
November | 0.549644E+09 | 1805.46 | 22-NOV-09:02 | 1.05 |
December | 0.123727E+10 | 1843.93 | 21-DEC-19:01 | 5.60 |
Annual Sum or Average | 0.515865E+10 | |||
Minimum of Months | 232087.42 | 464.11 | -9.8 | |
Maximum of Months | 0.178657E+10 | 1874.70 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412998E+09 | 966.32 | 03-JAN-16:01 | 2.80 |
February | 0.229545E+09 | 935.66 | 12-FEB-09:02 | -10.2 |
March | 34788068.64 | 903.65 | 22-MAR-15:02 | 5.10 |
April | 16679234.66 | 898.20 | 06-APR-08:62 | 5.37 |
May | 686730.62 | 645.12 | 13-MAY-08:53 | 20.00 |
June | 181751.96 | 465.17 | 07-JUN-08:53 | 18.90 |
July | 96966.69 | 248.37 | 02-JUL-08:55 | 25.00 |
August | 75167.73 | 322.06 | 10-AUG-08:05 | 27.48 |
September | 365441.04 | 450.58 | 19-SEP-08:54 | 19.40 |
October | 20100323.21 | 896.71 | 30-OCT-15:02 | 11.60 |
November | 58473535.96 | 921.98 | 30-NOV-16:02 | 7.20 |
December | 0.209965E+09 | 941.62 | 31-DEC-19:01 | 5.50 |
Annual Sum or Average | 0.983955E+09 | |||
Minimum of Months | 75167.73 | 248.37 | -10.2 | |
Maximum of Months | 0.412998E+09 | 966.32 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839640E+09 | 2252.66 | 08-JAN-06:00 | -5.0 |
February | 0.431427E+09 | 2390.11 | 12-FEB-07:05 | -12.7 |
March | 1394743.42 | 259.21 | 19-MAR-07:02 | 1.57 |
April | 39659.12 | 38.81 | 06-APR-06:10 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 36592864.09 | 1213.70 | 22-NOV-07:10 | -3.2 |
December | 0.142611E+09 | 1760.89 | 18-DEC-07:40 | -5.4 |
Annual Sum or Average | 0.145170E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.7 | |
Maximum of Months | 0.839640E+09 | 2390.11 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160421E+11 | 15451.75 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.144845E+11 | 15451.75 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.160915E+11 | 15451.75 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.154982E+11 | 15451.75 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.160699E+11 | 15451.75 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.155692E+11 | 15451.75 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.159988E+11 | 15451.75 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.160977E+11 | 15451.75 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.155043E+11 | 15451.75 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.160359E+11 | 15451.75 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.155569E+11 | 15451.75 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.159988E+11 | 15451.75 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.188948E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.144845E+11 | 15451.75 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.160977E+11 | 15451.75 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743719E+09 | 716.35 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.671510E+09 | 716.35 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.746011E+09 | 716.35 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.718503E+09 | 716.35 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.745008E+09 | 716.35 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.721798E+09 | 716.35 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.741713E+09 | 716.35 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.746298E+09 | 716.35 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.718790E+09 | 716.35 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.743432E+09 | 716.35 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.721225E+09 | 716.35 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.741713E+09 | 716.35 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.875972E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.671510E+09 | 716.35 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.746298E+09 | 716.35 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861229E+09 | 829.54 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.777612E+09 | 829.54 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.863884E+09 | 829.54 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.832029E+09 | 829.54 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.862722E+09 | 829.54 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.835845E+09 | 829.54 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.858907E+09 | 829.54 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.864216E+09 | 829.54 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.832361E+09 | 829.54 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.860897E+09 | 829.54 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.835182E+09 | 829.54 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.858907E+09 | 829.54 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.101438E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.777612E+09 | 829.54 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.864216E+09 | 829.54 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693793E+09 | 668.27 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.626432E+09 | 668.27 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.695932E+09 | 668.27 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.670270E+09 | 668.27 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.694996E+09 | 668.27 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.673344E+09 | 668.27 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.691922E+09 | 668.27 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.696199E+09 | 668.27 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.670538E+09 | 668.27 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.693526E+09 | 668.27 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.672810E+09 | 668.27 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.691922E+09 | 668.27 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.817168E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.626432E+09 | 668.27 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.696199E+09 | 668.27 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351983E+09 | 339.04 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.317809E+09 | 339.04 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.353068E+09 | 339.04 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.340049E+09 | 339.04 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.352593E+09 | 339.04 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.341609E+09 | 339.04 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.351034E+09 | 339.04 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.353204E+09 | 339.04 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.340185E+09 | 339.04 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.351847E+09 | 339.04 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.341337E+09 | 339.04 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.351034E+09 | 339.04 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.414575E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.317809E+09 | 339.04 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.353204E+09 | 339.04 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154494E+10 | 1957.67 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.139099E+10 | 1957.67 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.142210E+10 | 1957.67 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.128097E+10 | 1957.67 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.124373E+10 | 1957.67 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.116303E+10 | 1957.67 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.122085E+10 | 1957.67 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.128128E+10 | 1957.67 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.135542E+10 | 1957.67 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.149881E+10 | 1957.67 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.147438E+10 | 1957.67 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.153976E+10 | 1957.67 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.164163E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.116303E+10 | 1957.67 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.154494E+10 | 1957.67 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.851490E+10 | 8554.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.769197E+10 | 8554.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.846354E+10 | 8554.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.810214E+10 | 8554.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.834247E+10 | 8554.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.805243E+10 | 8554.32 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.829167E+10 | 8554.32 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.837129E+10 | 8554.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.815030E+10 | 8554.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.849471E+10 | 8554.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.823951E+10 | 8554.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.849238E+10 | 8554.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.992073E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.769197E+10 | 8554.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.851490E+10 | 8554.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146022E+09 | 132.12 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.131872E+09 | 132.12 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.144861E+09 | 132.12 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.141479E+09 | 132.12 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.145441E+09 | 132.12 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.140357E+09 | 132.12 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.146583E+09 | 132.12 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.144861E+09 | 132.12 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.141518E+09 | 132.12 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.146003E+09 | 132.12 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.140918E+09 | 132.12 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.146602E+09 | 132.12 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.171652E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.131872E+09 | 132.12 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.146602E+09 | 132.12 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.325408E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.292572E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.309669E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.286578E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.283416E+10 | 3437.84 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.269093E+10 | 3437.84 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.280405E+10 | 3437.84 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289668E+10 | 3437.84 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.294989E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.321109E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.312289E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.324915E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.359011E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.269093E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.325408E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.325408E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.292572E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.309669E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.286578E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.283416E+10 | 3437.84 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.269093E+10 | 3437.84 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.280405E+10 | 3437.84 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289668E+10 | 3437.84 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.294989E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.321109E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.312289E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.324915E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.359011E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.269093E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.325408E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126106E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121504E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125670E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148074E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.160421E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.160915E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.154982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.160699E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.155692E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.155043E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.160359E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.155569E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.188948E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.743719E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 761.77 | 0.564641E+09 |
February | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 688151.27 | 0.391972E+09 |
March | 0.199990E+10 | 0.746011E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4567898.72 | 0.244441E+09 |
April | 0.192973E+10 | 0.718503E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18301914.54 | 0.147464E+09 |
May | 0.199475E+10 | 0.745008E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43158442.86 | 65999534.33 |
June | 0.193394E+10 | 0.721798E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96362147.97 | 18844405.90 |
July | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115410E+09 | 6957691.48 |
August | 0.199896E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114238E+09 | 1282467.96 |
September | 0.192879E+10 | 0.718790E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48180818.37 | 33938256.57 |
October | 0.199148E+10 | 0.743432E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9234541.25 | 0.185625E+09 |
November | 0.192552E+10 | 0.721225E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1254595.55 | 0.290880E+09 |
December | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52306.70 | 0.437589E+09 |
Annual Sum or Average | 0.234744E+11 | 0.875972E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451449E+09 | 0.238963E+10 |
Minimum of Months | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 761.77 | 1282467.96 |
Maximum of Months | 0.199990E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115410E+09 | 0.564641E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.861229E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.55 | 0.218589E+09 |
February | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 681944.21 | 0.152364E+09 |
March | 0.231589E+10 | 0.863884E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2356535.88 | 96994358.90 |
April | 0.223463E+10 | 0.832029E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8545721.89 | 62030892.07 |
May | 0.230993E+10 | 0.862722E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17539133.47 | 31582344.18 |
June | 0.223950E+10 | 0.835845E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36776833.39 | 11551665.38 |
July | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44032764.73 | 5639959.83 |
August | 0.231480E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43694972.05 | 1721160.96 |
September | 0.223354E+10 | 0.832361E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19481413.41 | 17804074.01 |
October | 0.230614E+10 | 0.860897E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5009691.69 | 74731063.00 |
November | 0.222975E+10 | 0.835182E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 631828.20 | 0.113442E+09 |
December | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85966.27 | 0.169326E+09 |
Annual Sum or Average | 0.271834E+11 | 0.101438E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178837E+09 | 0.955776E+09 |
Minimum of Months | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 291.55 | 1721160.96 |
Maximum of Months | 0.231589E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44032764.73 | 0.218589E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.693793E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.26 | 0.513584E+09 |
February | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1727591.12 | 0.355595E+09 |
March | 0.489771E+09 | 0.695932E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6447770.16 | 0.219945E+09 |
April | 0.472586E+09 | 0.670270E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22228489.73 | 0.136660E+09 |
May | 0.488511E+09 | 0.694996E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43011734.42 | 67554658.62 |
June | 0.473617E+09 | 0.673344E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85674890.05 | 25582939.64 |
July | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101561E+09 | 13630356.21 |
August | 0.489542E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102179E+09 | 3822222.28 |
September | 0.472357E+09 | 0.670538E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47315838.68 | 38745270.08 |
October | 0.487709E+09 | 0.693526E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13570500.55 | 0.165718E+09 |
November | 0.471555E+09 | 0.672810E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1648121.81 | 0.259909E+09 |
December | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 209387.18 | 0.395377E+09 |
Annual Sum or Average | 0.574883E+10 | 0.817168E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425574E+09 | 0.219612E+10 |
Minimum of Months | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 696.26 | 3822222.28 |
Maximum of Months | 0.489771E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102179E+09 | 0.513584E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.351983E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 396.96 | 0.296199E+09 |
February | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1001106.71 | 0.204852E+09 |
March | 0.376747E+09 | 0.353068E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3882961.20 | 0.126103E+09 |
April | 0.363528E+09 | 0.340049E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13313784.67 | 76920135.68 |
May | 0.375778E+09 | 0.352593E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26016841.43 | 36114818.27 |
June | 0.364321E+09 | 0.341609E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51964069.10 | 12696218.85 |
July | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61724467.19 | 6128440.47 |
August | 0.376571E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63093020.34 | 1461326.95 |
September | 0.363352E+09 | 0.340185E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29732073.43 | 19767388.90 |
October | 0.375161E+09 | 0.351847E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8284904.65 | 93639062.37 |
November | 0.362735E+09 | 0.341337E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 973218.15 | 0.149273E+09 |
December | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 120796.15 | 0.227972E+09 |
Annual Sum or Average | 0.442217E+10 | 0.414575E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260108E+09 | 0.125113E+10 |
Minimum of Months | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 396.96 | 1461326.95 |
Maximum of Months | 0.376747E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63093020.34 | 0.296199E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 997.82 | 0.738011E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 2248443.21 | 0.517982E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 6859577.77 | 0.331697E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 26895302.93 | 0.209921E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 56548314.28 | 0.103256E+09 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.128837E+09 | 30583514.46 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.163630E+09 | 14849370.86 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.170729E+09 | 3946216.59 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 72366176.09 | 55344032.65 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 17437893.38 | 0.251523E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 2091601.17 | 0.388482E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 285373.25 | 0.576961E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.647929E+09 | 0.322256E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 997.82 | 3946216.59 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.170729E+09 | 0.738011E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.154494E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.41 | 0.126237E+10 |
February | 0.236489E+11 | 0.139099E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1551083.45 | 0.887167E+09 |
March | 0.262800E+11 | 0.142210E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8798068.02 | 0.578770E+09 |
April | 0.253579E+11 | 0.128097E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39082190.97 | 0.365185E+09 |
May | 0.262123E+11 | 0.124373E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92569577.80 | 0.190393E+09 |
June | 0.254132E+11 | 0.116303E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205611E+09 | 72225891.06 |
July | 0.261570E+11 | 0.122085E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245503E+09 | 36983209.02 |
August | 0.262677E+11 | 0.128128E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237288E+09 | 13327659.99 |
September | 0.253456E+11 | 0.135542E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98074118.12 | 0.110092E+09 |
October | 0.261693E+11 | 0.149881E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19184521.94 | 0.452739E+09 |
November | 0.253025E+11 | 0.147438E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2542149.54 | 0.676801E+09 |
December | 0.261570E+11 | 0.153976E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112664.42 | 0.988888E+09 |
Annual Sum or Average | 0.308468E+12 | 0.164163E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950318E+09 | 0.563495E+10 |
Minimum of Months | 0.236489E+11 | 0.116303E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.41 | 13327659.99 |
Maximum of Months | 0.262800E+11 | 0.154494E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245503E+09 | 0.126237E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.851490E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.81 | 0.361840E+10 |
February | 0.702046E+11 | 0.769197E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9188536.16 | 0.254431E+10 |
March | 0.780153E+11 | 0.846354E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34252329.96 | 0.165325E+10 |
April | 0.752779E+11 | 0.810214E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131957E+09 | 0.106812E+10 |
May | 0.778146E+11 | 0.834247E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276011E+09 | 0.566868E+09 |
June | 0.754422E+11 | 0.805243E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587946E+09 | 0.221020E+09 |
July | 0.776503E+11 | 0.829167E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706155E+09 | 0.119068E+09 |
August | 0.779788E+11 | 0.837129E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692625E+09 | 42096537.04 |
September | 0.752414E+11 | 0.815030E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300726E+09 | 0.334022E+09 |
October | 0.776868E+11 | 0.849471E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72872369.17 | 0.129332E+10 |
November | 0.751137E+11 | 0.823951E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8931096.92 | 0.193351E+10 |
December | 0.776503E+11 | 0.849238E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1027164.78 | 0.283266E+10 |
Annual Sum or Average | 0.915726E+12 | 0.992073E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282170E+10 | 0.162266E+11 |
Minimum of Months | 0.702046E+11 | 0.769197E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.81 | 42096537.04 |
Maximum of Months | 0.780153E+11 | 0.851490E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706155E+09 | 0.361840E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323328E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 273106.95 | 0.226493E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2385738.36 | 0.148552E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9048525.78 | 93874073.16 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22061310.47 | 46673993.73 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58628544.49 | 13562341.83 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76070132.05 | 7086950.86 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80439204.40 | 1813022.71 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30463527.35 | 23926403.80 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5205763.05 | 0.112229E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 252918.27 | 0.170972E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.51 | 0.251538E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284833E+09 | 0.142005E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1813022.71 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80439204.40 | 0.323328E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 360.55 | 0.319607E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483234.74 | 0.223208E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2610149.53 | 0.144171E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9602033.19 | 92481013.35 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22243504.52 | 46271060.17 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58597093.95 | 13655801.08 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76024030.71 | 7129193.07 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80514299.15 | 1739164.58 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30908460.82 | 23254142.49 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5790226.16 | 0.107992E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 463576.40 | 0.165818E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65761.77 | 0.246649E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287303E+09 | 0.139198E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 360.55 | 1739164.58 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80514299.15 | 0.319607E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.146022E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87156203.03 |
February | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52544.38 | 62361286.63 |
March | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 397307.17 | 46467867.42 |
April | 0.00 | 0.141479E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1827040.36 | 30615225.75 |
May | 0.00 | 0.145441E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4597957.68 | 16807037.17 |
June | 0.00 | 0.140357E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12755848.27 | 6191517.96 |
July | 0.00 | 0.146583E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16479192.63 | 3522302.38 |
August | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16444753.14 | 1164374.33 |
September | 0.00 | 0.141518E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5860976.02 | 9731599.15 |
October | 0.00 | 0.146003E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 989735.33 | 36387627.91 |
November | 0.00 | 0.140918E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16092.91 | 53899743.43 |
December | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72250526.81 |
Annual Sum or Average | 0.00 | 0.171652E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59421447.89 | 0.426555E+09 |
Minimum of Months | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1164374.33 |
Maximum of Months | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16479192.63 | 87156203.03 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 577.19 | 90261263.60 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 233034.85 | 62932917.80 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 907317.66 | 39841271.34 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3216052.20 | 25297387.38 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6829296.37 | 12381952.62 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16825706.78 | 3555713.03 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21617909.47 | 1797008.93 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23049480.33 | 376178.43 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9336868.60 | 6329606.02 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2007639.46 | 29931094.10 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 202140.27 | 46590309.61 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39468.05 | 69945581.79 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84265491.24 | 0.389240E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 577.19 | 376178.43 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23049480.33 | 90261263.60 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323781E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 272542.31 | 0.226962E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2474749.93 | 0.148308E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9033401.01 | 94113681.58 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21790266.23 | 47518633.09 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58055478.82 | 14775536.87 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75424747.02 | 8156822.23 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79996759.82 | 2324337.82 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30256643.81 | 24581736.27 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5255445.82 | 0.111856E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 338167.99 | 0.170837E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4822.46 | 0.251809E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282903E+09 | 0.142502E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2324337.82 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79996759.82 | 0.323781E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 274.96 | 0.319828E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 504444.42 | 0.223438E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2805140.81 | 0.143860E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9218932.68 | 92807810.07 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21823088.64 | 47227566.30 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58038271.88 | 14884648.14 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75407109.97 | 8209951.61 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80041183.35 | 2247296.87 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30400426.87 | 23967957.24 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5671226.26 | 0.107869E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 628200.54 | 0.165146E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104323.53 | 0.246776E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284643E+09 | 0.139626E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 274.96 | 2247296.87 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80041183.35 | 0.319828E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.07 | 0.396074E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1206190.46 | 0.274553E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4664713.01 | 0.170861E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15341696.94 | 0.107948E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30904192.71 | 54278446.13 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65807259.42 | 19407437.16 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79610810.34 | 10048205.79 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81672498.06 | 2479459.96 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35575598.18 | 29945390.42 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9562413.59 | 0.129122E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1182971.46 | 0.200501E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152389.33 | 0.305087E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325681E+09 | 0.170030E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.07 | 2479459.96 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81672498.06 | 0.396074E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322590E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 255291.11 | 0.226394E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2285504.95 | 0.149357E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8746036.12 | 95318769.49 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21563293.26 | 47992409.94 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57898336.75 | 13786837.01 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75257281.32 | 7140699.42 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79539497.29 | 1781702.94 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29879313.78 | 24260582.38 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5011048.45 | 0.113308E+09 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 225444.60 | 0.171221E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3260.92 | 0.250812E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280664E+09 | 0.142396E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1781702.94 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79539497.29 | 0.322590E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2446.57 | 0.319764E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 456053.56 | 0.223398E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2464810.36 | 0.144653E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9100646.12 | 93903661.89 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21628428.97 | 47600100.25 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57857977.76 | 13883201.50 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75207521.11 | 7179621.19 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79612079.34 | 1707243.30 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30195432.29 | 23532261.52 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5437835.63 | 0.108555E+09 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 439737.19 | 0.165657E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68763.10 | 0.246146E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282472E+09 | 0.139598E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2446.57 | 1707243.30 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79612079.34 | 0.319764E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169518E+09 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121211.00 | 0.118905E+09 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159630.91 | 77898984.27 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4475496.16 | 48539813.66 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11101012.04 | 23797964.89 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29742104.51 | 6810401.07 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38589162.23 | 3623719.49 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40710607.92 | 937825.88 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15248343.74 | 12705001.65 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521114.41 | 59497588.46 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78840.79 | 90793782.00 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.63 | 0.132644E+09 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143749E+09 | 0.745672E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 937825.88 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40710607.92 | 0.169518E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.325408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854927E+09 |
February | 0.415303E+11 | 0.292572E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1232114.81 | 0.612071E+09 |
March | 0.461508E+11 | 0.309669E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4311847.50 | 0.418401E+09 |
April | 0.445315E+11 | 0.286578E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18043739.42 | 0.281730E+09 |
May | 0.460320E+11 | 0.283416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41223075.69 | 0.161936E+09 |
June | 0.446286E+11 | 0.269093E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106358E+09 | 66043640.15 |
July | 0.459349E+11 | 0.280405E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134189E+09 | 40234606.20 |
August | 0.461292E+11 | 0.289668E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131765E+09 | 16460899.63 |
September | 0.445099E+11 | 0.294989E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51799673.52 | 97263865.30 |
October | 0.459565E+11 | 0.321109E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11571129.94 | 0.327699E+09 |
November | 0.444343E+11 | 0.312289E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 903978.55 | 0.475023E+09 |
December | 0.459349E+11 | 0.324915E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120600.19 | 0.679930E+09 |
Annual Sum or Average | 0.541708E+12 | 0.359011E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501518E+09 | 0.403172E+10 |
Minimum of Months | 0.415303E+11 | 0.269093E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16460899.63 |
Maximum of Months | 0.461508E+11 | 0.325408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134189E+09 | 0.854927E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.325408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863423E+09 |
February | 0.415303E+11 | 0.292572E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 961734.29 | 0.620339E+09 |
March | 0.461508E+11 | 0.309669E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3640333.86 | 0.428159E+09 |
April | 0.445315E+11 | 0.286578E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16011887.88 | 0.288210E+09 |
May | 0.460320E+11 | 0.283416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38300682.24 | 0.165466E+09 |
June | 0.446286E+11 | 0.269093E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103642E+09 | 66990745.48 |
July | 0.459349E+11 | 0.280405E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131904E+09 | 41086936.94 |
August | 0.461292E+11 | 0.289668E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129341E+09 | 16866813.10 |
September | 0.445099E+11 | 0.294989E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48789604.40 | 99822865.28 |
October | 0.459565E+11 | 0.321109E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10075915.43 | 0.336039E+09 |
November | 0.444343E+11 | 0.312289E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 624187.15 | 0.485327E+09 |
December | 0.459349E+11 | 0.324915E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71499.71 | 0.690289E+09 |
Annual Sum or Average | 0.541708E+12 | 0.359011E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483362E+09 | 0.410202E+10 |
Minimum of Months | 0.415303E+11 | 0.269093E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16866813.10 |
Maximum of Months | 0.461508E+11 | 0.325408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131904E+09 | 0.863423E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813760E+09 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 145139.19 | 0.581683E+09 |
March | 0.410691E+10 | 0.126106E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1911201.83 | 0.395012E+09 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9982651.99 | 0.256906E+09 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 28253472.06 | 0.139383E+09 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 87690644.89 | 48991603.74 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.116637E+09 | 28728201.85 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.116895E+09 | 10533713.57 |
September | 0.396089E+10 | 0.121504E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 37283565.69 | 81496953.31 |
October | 0.408962E+10 | 0.125670E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5262995.46 | 0.307019E+09 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12752.11 | 0.452958E+09 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648560E+09 |
Annual Sum or Average | 0.482060E+11 | 0.148074E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.404074E+09 | 0.376503E+10 |
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10533713.57 |
Maximum of Months | 0.410691E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.116895E+09 | 0.813760E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703257E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1807595.50 | 0.487560E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7292921.99 | 0.303318E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23689475.71 | 0.189417E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48278546.21 | 94297867.80 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106405E+09 | 34249039.65 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128265E+09 | 17246186.53 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130234E+09 | 4445706.96 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59380357.06 | 48724622.47 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15270309.38 | 0.226845E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1803494.60 | 0.356624E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226689.46 | 0.542111E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522654E+09 | 0.300810E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4445706.96 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130234E+09 | 0.703257E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 15451.75 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 15451.75 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 15451.75 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 15451.75 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 15451.75 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 15451.75 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 15451.75 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 15451.75 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 15451.75 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 15451.75 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 15451.75 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 15451.75 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 716.35 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 31-JAN-15:00 | 354.87 | 27-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 716.35 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 | 28-FEB-14:40 | 429.42 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 716.35 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.98 | 30-MAR-16:00 | 246.25 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 716.35 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 | 17-APR-16:00 | 259.90 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 716.35 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 | 19-MAY-17:00 | 158.39 | 11-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 716.35 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.66 | 06-JUN-15:00 | 117.47 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 716.35 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.23 | 08-JUL-16:00 | 44.45 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 716.35 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.66 | 01-AUG-17:00 | 35.49 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 716.35 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.49 | 03-SEP-17:00 | 110.08 | 29-SEP-04:00 |
October | 1169.53 | 01-OCT-23:10 | 716.35 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 | 10-OCT-16:00 | 230.87 | 26-OCT-06:57 |
November | 1169.53 | 01-NOV-00:10 | 716.35 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.99 | 19-NOV-15:40 | 303.43 | 22-NOV-06:05 |
December | 1169.53 | 01-DEC-00:10 | 716.35 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.59 | 12-DEC-15:50 | 338.34 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 35.49 | |||||
Maximum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 138.23 | 429.42 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 829.54 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 31-JAN-15:00 | 136.97 | 27-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 829.54 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 26-FEB-15:00 | 171.87 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 829.54 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | 30-MAR-14:00 | 95.05 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 829.54 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 | 12-APR-14:00 | 100.40 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 829.54 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 | 30-MAY-14:00 | 64.14 | 11-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 829.54 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 | 06-JUN-15:00 | 49.89 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 829.54 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 | 08-JUL-15:00 | 23.73 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 829.54 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 01-AUG-15:00 | 19.87 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 829.54 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.31 | 07-SEP-15:00 | 46.01 | 14-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 829.54 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 | 10-OCT-16:00 | 91.11 | 26-OCT-06:35 |
November | 1354.32 | 01-NOV-00:10 | 829.54 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 19-NOV-15:00 | 117.12 | 22-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 829.54 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 | 12-DEC-15:00 | 130.59 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 19.87 | |||||
Maximum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 | 171.87 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 668.27 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 31-JAN-15:00 | 323.69 | 27-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 668.27 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 | 26-FEB-15:00 | 406.18 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 668.27 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.31 | 30-MAR-14:00 | 224.63 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 668.27 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 12-APR-14:00 | 237.07 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 668.27 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.63 | 30-MAY-14:00 | 144.79 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 668.27 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.86 | 06-JUN-15:00 | 114.47 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 668.27 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 | 08-JUL-15:00 | 54.14 | 28-JUL-23:00 |
August | 286.42 | 01-AUG-00:10 | 668.27 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.42 | 01-AUG-15:00 | 46.62 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 668.27 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.71 | 07-SEP-15:00 | 106.23 | 14-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 668.27 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.49 | 10-OCT-16:00 | 211.23 | 26-OCT-06:35 |
November | 286.42 | 01-NOV-00:10 | 668.27 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.05 | 05-NOV-16:00 | 276.79 | 22-NOV-06:50 |
December | 286.42 | 01-DEC-00:10 | 668.27 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 12-DEC-14:00 | 308.64 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 46.62 | |||||
Maximum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 | 406.18 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 339.04 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 31-JAN-15:00 | 186.75 | 27-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 339.04 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 26-FEB-15:00 | 231.85 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 339.04 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.37 | 30-MAR-14:00 | 129.60 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 339.04 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.89 | 12-APR-14:00 | 136.78 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 339.04 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.29 | 30-MAY-14:00 | 83.37 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 339.04 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | 06-JUN-15:00 | 63.67 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 339.04 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.46 | 08-JUL-15:00 | 28.66 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 339.04 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 | 01-AUG-15:00 | 24.25 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 339.04 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.26 | 07-SEP-15:00 | 58.50 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 339.04 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 10-OCT-16:00 | 121.51 | 26-OCT-06:57 |
November | 220.32 | 01-NOV-00:10 | 339.04 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 05-NOV-16:00 | 159.69 | 22-NOV-06:50 |
December | 220.32 | 01-DEC-00:10 | 339.04 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 12-DEC-14:00 | 178.06 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 24.25 | |||||
Maximum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 78.46 | 231.85 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 1.44 | 31-JAN-15:00 | 474.70 | 27-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 56.33 | 28-FEB-14:30 | 559.82 | 12-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 94.63 | 30-MAR-15:00 | 378.77 | 19-MAR-07:07 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 110.86 | 12-APR-14:00 | 374.49 | 05-APR-21:30 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 132.90 | 19-MAY-15:00 | 226.87 | 11-MAY-05:40 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 180.74 | 06-JUN-15:00 | 166.58 | 08-JUN-06:10 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 210.85 | 08-JUL-15:00 | 90.05 | 28-JUL-22:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 190.06 | 01-AUG-15:00 | 74.09 | 25-AUG-06:20 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 146.07 | 07-SEP-15:00 | 162.66 | 14-SEP-06:20 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 124.38 | 10-OCT-16:00 | 364.52 | 26-OCT-06:35 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 47.91 | 05-NOV-16:00 | 405.23 | 22-NOV-07:20 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 25.74 | 12-DEC-14:10 | 453.93 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 1.44 | 74.09 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 210.85 | 559.82 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1957.67 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 31-JAN-15:00 | 784.40 | 27-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1957.67 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.33 | 28-FEB-14:40 | 984.32 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1957.67 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.79 | 30-MAR-14:00 | 546.96 | 19-MAR-07:07 |
April | 15368.40 | 01-APR-00:10 | 1957.67 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.68 | 12-APR-14:00 | 576.58 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1957.67 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.52 | 30-MAY-14:00 | 360.38 | 11-MAY-05:40 |
June | 15368.40 | 01-JUN-00:10 | 1957.67 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.44 | 06-JUN-15:00 | 295.31 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1957.67 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.13 | 08-JUL-16:00 | 148.14 | 28-JUL-23:00 |
August | 15368.40 | 01-AUG-00:10 | 1957.67 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.96 | 01-AUG-15:00 | 112.82 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1957.67 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.91 | 08-SEP-14:00 | 272.36 | 29-SEP-04:00 |
October | 15368.40 | 01-OCT-23:10 | 1957.67 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.11 | 10-OCT-16:00 | 519.88 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1957.67 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 | 19-NOV-15:30 | 670.81 | 22-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 1957.67 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 | 12-DEC-15:50 | 747.92 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 112.82 | |||||
Maximum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 322.13 | 984.32 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 8554.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 31-JAN-15:00 | 2244.46 | 14-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 8554.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.24 | 28-FEB-14:40 | 2812.20 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 8554.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.02 | 30-MAR-14:00 | 1573.04 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 8554.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 525.59 | 12-APR-14:00 | 1704.46 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 8554.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.19 | 30-MAY-14:00 | 1080.69 | 11-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 8554.32 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 843.10 | 06-JUN-15:00 | 868.22 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 8554.32 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 959.48 | 08-JUL-16:00 | 437.74 | 28-JUL-23:00 |
August | 45622.98 | 01-AUG-00:10 | 8554.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 875.09 | 01-AUG-15:00 | 353.53 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 8554.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.68 | 07-SEP-15:00 | 808.90 | 29-SEP-04:00 |
October | 45622.98 | 01-OCT-23:10 | 8554.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.55 | 10-OCT-16:00 | 1527.44 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 8554.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.87 | 19-NOV-15:00 | 1950.32 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 8554.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.99 | 12-DEC-15:00 | 2136.73 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 353.53 | |||||
Maximum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 959.48 | 2812.20 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 207.09 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:08 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 35.32 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 27.13 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.09 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 12-DEC-16:08 | 197.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 31-JAN-15:00 | 207.07 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:08 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 30-MAR-15:10 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:08 | 151.92 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 35.21 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 26.81 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.92 | 10-OCT-16:00 | 135.08 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:20 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 | 12-DEC-14:00 | 197.47 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 26.81 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 132.12 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 54.64 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 132.12 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 26-FEB-15:00 | 67.69 | 12-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 132.12 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 30-MAR-14:00 | 40.64 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 132.12 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 12-APR-14:00 | 42.09 | 06-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 132.12 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 19-MAY-14:00 | 28.50 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 132.12 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 06-JUN-15:00 | 22.26 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 132.12 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 08-JUL-15:00 | 11.32 | 28-JUL-23:00 |
August | 0.00 | 01-AUG-00:10 | 132.12 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 02-AUG-16:00 | 9.28 | 25-AUG-06:10 |
September | 0.00 | 01-SEP-00:10 | 132.12 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | 07-SEP-16:00 | 21.30 | 14-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 132.12 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 10-OCT-16:00 | 38.95 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 132.12 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 05-NOV-16:00 | 47.99 | 21-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 132.12 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 53.80 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | |||||
Maximum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 67.69 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 31-JAN-15:00 | 57.80 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 26-FEB-15:00 | 72.45 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 30-MAR-16:00 | 40.19 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 17-APR-15:08 | 42.40 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 19-MAY-16:00 | 25.96 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 06-JUN-15:10 | 19.32 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 08-JUL-15:10 | 10.61 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 02-AUG-16:00 | 7.21 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.82 | 07-SEP-16:00 | 18.12 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 10-OCT-16:00 | 37.70 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-NOV-16:00 | 49.46 | 22-NOV-06:20 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 12-DEC-14:00 | 55.12 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 7.21 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 72.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 207.08 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:08 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 | 08-JUL-15:10 | 34.67 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 26.19 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.09 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 12-DEC-16:08 | 197.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.19 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 31-JAN-15:00 | 207.07 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:07 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 30-MAR-15:40 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.93 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 34.55 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 25.87 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.41 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.08 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 12-DEC-15:00 | 197.47 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 25.87 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.58 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 31-JAN-15:00 | 249.42 | 27-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 26-FEB-15:00 | 312.90 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.07 | 30-MAR-14:00 | 173.18 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.26 | 12-APR-14:00 | 182.76 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.70 | 30-MAY-14:00 | 114.50 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.57 | 06-JUN-15:00 | 90.28 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 | 08-JUL-15:00 | 42.55 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.21 | 01-AUG-15:00 | 33.87 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.43 | 07-SEP-15:00 | 82.45 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 | 10-OCT-16:00 | 162.51 | 26-OCT-06:41 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.55 | 19-NOV-15:00 | 213.33 | 22-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 12-DEC-14:50 | 237.84 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 33.87 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 | 312.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 207.57 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 26-FEB-16:10 | 260.12 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 144.48 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 17-APR-15:10 | 152.39 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.44 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 | 06-JUN-15:10 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.73 | 08-JUL-15:10 | 35.31 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 02-AUG-16:00 | 25.88 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.35 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.54 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.68 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 12-DEC-16:08 | 197.97 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 97.73 | 260.12 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 31-JAN-15:00 | 207.56 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 26-FEB-16:08 | 259.64 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 144.46 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 17-APR-15:10 | 152.38 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.43 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 | 06-JUN-15:10 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.75 | 08-JUL-15:10 | 35.16 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 02-AUG-16:00 | 25.56 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.35 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.55 | 10-OCT-16:00 | 135.53 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.67 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 12-DEC-14:00 | 197.96 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 25.56 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.75 | 259.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 106.20 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 26-FEB-16:10 | 133.08 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 30-MAR-16:00 | 73.92 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.48 | 17-APR-15:10 | 77.97 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 | 19-MAY-16:00 | 47.81 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 06-JUN-15:10 | 35.64 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 | 08-JUL-15:10 | 19.06 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 02-AUG-16:00 | 13.36 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 | 07-SEP-16:00 | 33.44 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 10-OCT-16:00 | 69.35 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 05-NOV-16:00 | 90.91 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 12-DEC-16:10 | 101.29 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 | 133.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 527.42 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.20 | 26-FEB-15:00 | 644.37 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.64 | 30-MAR-14:00 | 389.07 | 19-MAR-07:07 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 | 12-APR-14:00 | 404.75 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.66 | 19-MAY-14:00 | 269.35 | 11-MAY-05:40 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.47 | 06-JUN-15:00 | 215.19 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 08-JUL-15:00 | 114.25 | 28-JUL-23:07 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.27 | 01-AUG-15:00 | 94.75 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.07 | 07-SEP-15:00 | 202.45 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.48 | 10-OCT-14:00 | 365.47 | 26-OCT-06:15 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 19-NOV-15:00 | 458.82 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 12-DEC-15:00 | 493.05 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.75 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 644.37 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 529.72 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 | 26-FEB-15:00 | 647.32 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.81 | 30-MAR-14:00 | 394.05 | 19-MAR-07:07 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.60 | 12-APR-14:00 | 407.65 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 19-MAY-14:00 | 272.38 | 11-MAY-05:40 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.49 | 06-JUN-15:00 | 217.04 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 08-JUL-15:00 | 114.25 | 28-JUL-23:07 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.30 | 01-AUG-15:00 | 94.76 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.23 | 07-SEP-15:00 | 204.72 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.90 | 10-OCT-14:00 | 370.26 | 26-OCT-06:35 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 19-NOV-15:00 | 461.42 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 12-DEC-15:00 | 495.54 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.76 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 647.32 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 500.46 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 13.02 | 28-FEB-14:00 | 596.41 | 12-FEB-08:10 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 52.61 | 30-MAR-15:40 | 384.44 | 19-MAR-07:07 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 68.81 | 12-APR-14:00 | 378.84 | 07-APR-06:33 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 91.83 | 19-MAY-15:40 | 246.83 | 11-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 141.74 | 06-JUN-15:00 | 185.09 | 08-JUN-06:00 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 174.08 | 08-JUL-15:00 | 102.18 | 28-JUL-23:00 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 152.09 | 02-AUG-16:00 | 84.75 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 106.44 | 07-SEP-15:40 | 177.51 | 14-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 83.23 | 10-OCT-16:00 | 372.88 | 26-OCT-06:35 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 4.48 | 05-NOV-16:00 | 426.97 | 22-NOV-07:40 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 477.81 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 174.08 | 596.41 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 442.36 | 27-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.75 | 28-FEB-14:40 | 547.13 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.55 | 30-MAR-14:00 | 307.39 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.92 | 12-APR-14:00 | 324.35 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.47 | 19-MAY-14:00 | 198.27 | 11-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.42 | 06-JUN-15:00 | 151.65 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 08-JUL-15:00 | 70.11 | 28-JUL-23:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.35 | 01-AUG-15:00 | 57.84 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.52 | 07-SEP-15:00 | 138.20 | 29-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.46 | 10-OCT-16:00 | 288.31 | 26-OCT-06:53 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.15 | 19-NOV-15:00 | 378.44 | 22-NOV-06:30 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 12-DEC-15:00 | 421.84 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.84 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 547.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26254.45 | 22-JAN-17:49 | 40895.62 | 27469.23 | 24334.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24139.62 | 21-FEB-07:07 | 30671.71 | 51505.41 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20490.01 | 22-MAR-19:15 | 35783.66 | 61806.99 | 38530.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18528.47 | 05-APR-22:12 | 57509.46 | 25752.91 | 20279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15602.02 | 11-MAY-06:03 | 15335.86 | 25752.71 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15834.62 | 30-JUN-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16668.63 | 14-JUL-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17560.71 | 18-AUG-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18379.57 | 15-SEP-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24327.65 | 12-OCT-06:32 | 30671.71 | 51505.41 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26110.40 | 09-NOV-07:17 | 15335.86 | 25752.71 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30598.10 | 09-DEC-08:13 | 25559.76 | 27470.04 | 20279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15602.02 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30598.10 | 57509.46 | 61806.99 | 38530.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2845.06 | 11-JAN-14:15 | 519.79 | 397.97 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.60 |
February | 2613.05 | 04-FEB-15:10 | 1169.53 | 596.96 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.53 |
March | 2156.87 | 30-MAR-14:20 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 48.39 | 0.00 |
April | 2241.02 | 15-APR-14:03 | 1169.53 | 596.96 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 43.38 | 0.00 |
May | 2090.71 | 19-MAY-19:20 | 909.64 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 0.00 |
June | 2189.27 | 13-JUN-19:20 | 909.64 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 73.14 | 0.00 |
July | 2550.25 | 08-JUL-17:04 | 6237.50 | 3820.56 | 4041.45 | 0.00 | 0.00 | 0.00 | 0.00 | 113.75 | 0.00 |
August | 2799.01 | 19-AUG-13:40 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 0.00 |
September | 2619.13 | 25-SEP-15:03 | 3898.44 | 1193.92 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 60.09 | 0.00 |
October | 2768.85 | 10-OCT-13:40 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 56.07 | 0.00 |
November | 2425.69 | 26-NOV-09:30 | 2598.96 | 955.14 | 1154.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.62 |
December | 2607.50 | 18-DEC-13:20 | 519.79 | 397.97 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2090.71 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2845.06 | 6237.50 | 3820.56 | 4041.45 | 0.00 | 0.00 | 0.00 | 0.00 | 113.75 | 184.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2205.39 | 25-JAN-23:40 | 5417.28 | 1106.05 | 1337.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.59 |
February | 2205.95 | 21-FEB-07:07 | 3611.52 | 2765.14 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.19 |
March | 1880.59 | 22-MAR-19:15 | 4213.44 | 3318.16 | 3175.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.44 |
April | 1900.06 | 06-APR-22:40 | 2708.64 | 553.03 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 |
May | 1680.94 | 19-MAY-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.00 |
June | 1723.49 | 27-JUN-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 0.00 |
July | 2005.20 | 07-JUL-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 0.00 |
August | 2076.21 | 18-AUG-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 0.00 |
September | 1845.45 | 08-SEP-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 | 0.00 |
October | 2054.37 | 12-OCT-06:32 | 3611.52 | 2765.14 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.68 |
November | 2115.39 | 09-NOV-07:17 | 1805.76 | 1382.57 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 |
December | 1917.06 | 08-DEC-20:12 | 4213.44 | 3318.16 | 3175.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1680.94 | 1203.84 | 553.03 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2205.95 | 5417.28 | 3318.16 | 3175.73 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 93.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1216.29 | 20-JAN-23:53 | 859.25 | 668.27 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.91 |
February | 1736.82 | 21-FEB-07:07 | 763.78 | 2227.55 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.71 |
March | 1363.96 | 02-MAR-23:15 | 572.83 | 445.51 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.80 |
April | 1342.59 | 05-APR-22:12 | 1432.08 | 1113.78 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.77 |
May | 1258.68 | 19-MAY-21:00 | 254.59 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 0.00 |
June | 1342.95 | 29-JUN-21:10 | 286.42 | 445.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 | 0.00 |
July | 1393.01 | 07-JUL-21:10 | 286.42 | 445.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 0.00 |
August | 1396.30 | 18-AUG-21:10 | 286.42 | 445.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 69.86 | 0.00 |
September | 1330.91 | 08-SEP-21:00 | 254.59 | 594.01 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 0.00 |
October | 1611.48 | 12-OCT-06:32 | 763.78 | 2227.55 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.89 |
November | 1604.14 | 28-NOV-24:00 | 859.25 | 668.27 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.89 |
December | 1445.22 | 08-DEC-20:12 | 891.07 | 2673.06 | 3357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1216.29 | 254.59 | 445.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1736.82 | 1432.08 | 2673.06 | 3357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 69.86 | 208.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 622.04 | 31-JAN-21:30 | 195.84 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
February | 729.45 | 21-FEB-07:07 | 587.52 | 1130.09 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 |
March | 741.26 | 30-MAR-21:00 | 195.84 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 0.00 |
April | 845.46 | 05-APR-22:12 | 1101.60 | 565.04 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.56 |
May | 787.71 | 19-MAY-21:00 | 195.84 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 0.00 |
June | 842.83 | 29-JUN-21:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 0.00 |
July | 878.46 | 07-JUL-21:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 40.68 | 0.00 |
August | 880.09 | 18-AUG-21:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 0.00 |
September | 834.29 | 07-SEP-21:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 0.00 |
October | 1017.95 | 12-OCT-06:32 | 587.52 | 1130.09 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.06 |
November | 706.57 | 08-NOV-00:30 | 440.64 | 150.68 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 |
December | 692.73 | 12-DEC-22:10 | 220.32 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 622.04 | 195.84 | 150.68 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1017.95 | 1101.60 | 1130.09 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 117.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49802.31 | 04-JAN-21:40 | 4838.40 | 2419.23 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 349.63 |
February | 47334.76 | 06-FEB-21:29 | 7257.60 | 3628.84 | 38989.14 | 338721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 298.08 |
March | 46934.52 | 22-MAR-19:15 | 2822.40 | 1814.42 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 0.00 | 265.70 |
April | 49477.39 | 05-APR-20:43 | 5644.80 | 2822.43 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 318.03 |
May | 38868.93 | 16-MAY-18:50 | 2116.80 | 1209.61 | 12996.38 | 112907.11 | 0.00 | 0.00 | 0.00 | 59.42 | 0.00 |
June | 38478.26 | 13-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.92 | 0.00 |
July | 38766.32 | 07-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 97.79 | 0.00 |
August | 38663.27 | 18-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 105.81 | 0.00 |
September | 38352.72 | 07-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.59 | 0.00 |
October | 41170.42 | 25-OCT-20:08 | 4838.40 | 2419.23 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 258.36 |
November | 50686.09 | 30-NOV-21:55 | 8064.00 | 4032.04 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 315.71 |
December | 49258.96 | 08-DEC-21:46 | 7257.60 | 3628.84 | 38989.14 | 338721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 312.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38352.72 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50686.09 | 8064.00 | 4032.04 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 105.81 | 349.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12383.20 | 25-JAN-23:40 | 61473.60 | 2610.23 | 1625.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.85 |
February | 12848.04 | 24-FEB-23:26 | 76842.00 | 3262.79 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.11 |
March | 10293.18 | 02-MAR-23:15 | 30736.80 | 1305.12 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.80 |
April | 10700.36 | 06-APR-22:40 | 30736.80 | 1305.12 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.03 |
May | 9689.34 | 19-MAY-21:12 | 61473.60 | 5220.46 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
June | 10716.54 | 13-JUN-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 0.00 |
July | 11553.98 | 07-JUL-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 156.92 | 0.00 |
August | 12016.13 | 18-AUG-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 166.90 | 0.00 |
September | 11369.82 | 25-SEP-15:05 | 51228.00 | 717.81 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 132.84 | 0.00 |
October | 11346.65 | 11-OCT-15:03 | 51228.00 | 717.81 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 74.49 | 0.00 |
November | 12054.41 | 26-NOV-09:30 | 34152.00 | 574.25 | 1625.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.60 |
December | 11368.57 | 09-DEC-10:37 | 15368.40 | 430.69 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9689.34 | 15368.40 | 430.69 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12848.04 | 76842.00 | 5220.46 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 166.90 | 533.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 43547.62 | 25-JAN-23:40 | 182491.92 | 11405.76 | 16891.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1579.03 |
February | 43425.17 | 24-FEB-23:26 | 228114.90 | 14257.20 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.57 |
March | 36652.70 | 22-MAR-19:15 | 141938.16 | 34217.28 | 40116.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.89 |
April | 37455.97 | 06-APR-22:40 | 91245.96 | 5702.88 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1219.03 |
May | 32216.87 | 19-MAY-22:00 | 319360.86 | 39920.16 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.95 |
June | 34149.76 | 13-JUN-22:00 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 227.04 | 0.00 |
July | 37589.30 | 07-JUL-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 448.14 | 0.00 |
August | 38703.85 | 18-AUG-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 476.65 | 0.00 |
September | 35459.36 | 07-SEP-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.55 | 0.00 |
October | 39170.92 | 12-OCT-06:32 | 121661.28 | 28514.40 | 38005.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.67 |
November | 41320.11 | 28-NOV-24:00 | 136868.94 | 8554.32 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.52 |
December | 49047.84 | 09-DEC-08:13 | 101384.40 | 13078.60 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32216.87 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49047.84 | 319360.86 | 39920.16 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 476.65 | 1579.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3098.75 | 29-JAN-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.38 |
February | 3208.93 | 28-FEB-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 0.00 |
March | 3174.16 | 12-MAR-19:01 | 936.00 | 1681.80 | 1306.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.84 |
April | 3341.15 | 09-APR-20:11 | 1386.00 | 2102.25 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.74 |
May | 3366.00 | 09-MAY-20:41 | 1602.00 | 1871.00 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.63 |
June | 3156.96 | 05-JUN-21:51 | 1440.00 | 1126.80 | 716.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 |
July | 3106.08 | 06-JUL-18:02 | 831.60 | 1122.60 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 59.98 | 0.00 |
August | 3124.74 | 14-AUG-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 | 0.00 |
September | 3520.55 | 18-SEP-16:01 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | 0.00 |
October | 3392.59 | 15-OCT-16:21 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
November | 3200.24 | 11-NOV-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 |
December | 3144.39 | 10-DEC-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3098.75 | 378.00 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3520.55 | 1602.00 | 2102.25 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 59.98 | 66.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1216.83 | 29-JAN-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.85 |
February | 3148.29 | 28-FEB-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 0.00 |
March | 3109.63 | 10-MAR-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 |
April | 3246.62 | 26-APR-18:41 | 1247.40 | 1683.70 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 |
May | 3297.01 | 09-MAY-20:41 | 1602.00 | 1870.78 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.49 |
June | 3121.06 | 05-JUN-21:51 | 1440.00 | 1126.67 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
July | 3091.52 | 04-JUL-15:02 | 324.00 | 416.20 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 0.00 |
August | 3086.84 | 03-AUG-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 71.46 | 0.00 |
September | 3310.02 | 18-SEP-16:01 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 | 0.00 |
October | 3096.39 | 15-OCT-16:21 | 954.00 | 693.66 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
November | 3124.40 | 11-NOV-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 |
December | 2781.92 | 10-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1216.83 | 324.00 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3310.02 | 1602.00 | 1870.78 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 71.46 | 65.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 259.80 | 29-JAN-13:30 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 |
February | 434.16 | 26-FEB-14:50 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 0.00 |
March | 407.11 | 13-MAR-16:20 | 0.00 | 36.99 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
April | 408.48 | 15-APR-14:00 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 | 0.00 |
May | 363.90 | 19-MAY-19:10 | 0.00 | 132.12 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 | 0.00 |
June | 411.35 | 24-JUN-19:10 | 0.00 | 132.12 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 0.00 |
July | 452.31 | 08-JUL-17:30 | 0.00 | 224.60 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 0.00 |
August | 483.20 | 19-AUG-13:50 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 0.00 |
September | 532.53 | 24-SEP-12:50 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 0.00 |
October | 575.74 | 10-OCT-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 |
November | 478.06 | 08-NOV-14:20 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 |
December | 450.28 | 10-DEC-14:30 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 259.80 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 575.74 | 0.00 | 224.60 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 17.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 962.19 | 01-JAN-09:02 | 270.00 | 370.03 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 |
February | 1145.17 | 28-FEB-22:51 | 1260.00 | 619.80 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
March | 1132.35 | 31-MAR-20:12 | 961.20 | 705.70 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 |
April | 1155.13 | 16-APR-21:51 | 1108.80 | 898.65 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 |
May | 1215.53 | 09-MAY-20:41 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 |
June | 1205.44 | 10-JUN-18:01 | 819.00 | 925.08 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 0.00 |
July | 1142.09 | 16-JUL-18:02 | 702.00 | 792.93 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 0.00 |
August | 1139.15 | 25-AUG-18:02 | 831.60 | 705.70 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 0.00 |
September | 1150.00 | 14-SEP-21:51 | 1620.00 | 796.89 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 |
October | 1154.59 | 11-OCT-21:51 | 1440.00 | 708.35 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 |
November | 1074.43 | 08-NOV-21:11 | 1281.60 | 940.94 | 1424.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 |
December | 991.59 | 12-DEC-22:51 | 1260.00 | 619.80 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 962.19 | 270.00 | 370.03 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1215.53 | 1620.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 18.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2661.57 | 29-JAN-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 |
February | 2920.01 | 28-FEB-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 0.00 |
March | 2890.31 | 26-MAR-15:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
April | 3129.50 | 14-APR-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 |
May | 3191.84 | 18-MAY-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 |
June | 3209.59 | 04-JUN-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 |
July | 3069.77 | 25-JUL-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 |
August | 3118.73 | 26-AUG-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 |
September | 3154.05 | 15-SEP-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
October | 2889.57 | 13-OCT-15:02 | 583.20 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
November | 2897.72 | 11-NOV-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 |
December | 2750.16 | 10-DEC-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2661.57 | 360.00 | 353.18 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3209.59 | 680.40 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 35.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 577.71 | 29-JAN-17:44 | 763.20 | 554.93 | 842.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.18 |
February | 2771.15 | 28-FEB-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 0.00 |
March | 2714.55 | 30-MAR-18:02 | 831.60 | 1122.47 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 0.00 |
April | 3082.06 | 14-APR-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 |
May | 3168.82 | 18-MAY-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
June | 3191.92 | 04-JUN-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 |
July | 3049.77 | 03-JUL-08:41 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
August | 3090.40 | 26-AUG-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
September | 3054.40 | 15-SEP-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 |
October | 2654.01 | 10-OCT-18:02 | 831.60 | 1122.47 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | 0.00 |
November | 2444.15 | 06-NOV-09:02 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.04 |
December | 1566.83 | 12-DEC-22:51 | 1260.00 | 985.84 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 577.71 | 216.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3191.92 | 1260.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 62.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2259.25 | 23-JAN-22:13 | 6790.07 | 3734.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.76 |
February | 3083.71 | 24-FEB-23:26 | 11316.78 | 3112.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.42 |
March | 2557.76 | 02-MAR-23:15 | 4526.71 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.10 |
April | 2488.91 | 05-APR-22:12 | 11316.78 | 3112.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.04 |
May | 2290.02 | 31-MAY-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 |
June | 2416.91 | 29-JUN-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 0.00 |
July | 2467.23 | 07-JUL-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.12 | 0.00 |
August | 2488.10 | 18-AUG-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 | 0.00 |
September | 2379.19 | 08-SEP-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 | 0.00 |
October | 2994.01 | 12-OCT-06:32 | 6035.62 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.10 |
November | 2881.67 | 07-NOV-23:10 | 9053.42 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.02 |
December | 2700.43 | 08-DEC-20:12 | 7041.55 | 7469.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2259.25 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3083.71 | 11316.78 | 7469.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 | 160.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3227.61 | 29-JAN-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.43 |
February | 3359.50 | 28-FEB-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.78 | 0.00 |
March | 3397.32 | 12-MAR-19:01 | 936.00 | 1681.80 | 1306.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.56 |
April | 3694.62 | 09-APR-20:11 | 1386.00 | 2102.25 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.15 |
May | 3646.34 | 09-MAY-20:41 | 1602.00 | 1871.00 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.70 |
June | 3276.65 | 05-JUN-21:51 | 1440.00 | 1126.80 | 716.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 |
July | 3253.57 | 23-JUL-15:02 | 324.00 | 416.24 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 40.65 | 0.00 |
August | 3266.36 | 21-AUG-18:02 | 831.60 | 1122.60 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 45.45 | 0.00 |
September | 3673.12 | 18-SEP-16:01 | 972.00 | 588.63 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
October | 3699.50 | 15-OCT-16:21 | 954.00 | 693.74 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
November | 3348.97 | 11-NOV-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 |
December | 3283.53 | 10-DEC-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3227.61 | 324.00 | 412.04 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3699.50 | 1602.00 | 2102.25 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 45.45 | 73.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 647.21 | 11-JAN-16:05 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.91 |
February | 3290.48 | 28-FEB-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 0.00 |
March | 3249.60 | 10-MAR-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
April | 3524.94 | 09-APR-20:11 | 1386.00 | 2102.00 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 |
May | 3569.38 | 09-MAY-20:41 | 1602.00 | 1870.78 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.54 |
June | 3242.76 | 07-JUN-21:51 | 1620.00 | 1267.51 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 |
July | 3225.78 | 19-JUL-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 0.00 |
August | 3239.42 | 21-AUG-15:02 | 583.20 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 0.00 |
September | 3562.82 | 18-SEP-16:01 | 972.00 | 588.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | 0.00 |
October | 3320.30 | 15-OCT-16:21 | 954.00 | 693.66 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 0.00 |
November | 3257.60 | 11-NOV-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 |
December | 2582.13 | 11-DEC-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 647.21 | 378.00 | 353.14 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3569.38 | 1620.00 | 2102.00 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 99.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1788.70 | 29-JAN-17:41 | 763.20 | 348.89 | 825.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.63 |
February | 1800.80 | 21-FEB-22:11 | 1440.00 | 708.35 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 |
March | 1818.84 | 13-MAR-21:51 | 1620.00 | 796.89 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 |
April | 1824.74 | 09-APR-20:11 | 1386.00 | 1321.54 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 |
May | 1808.70 | 09-MAY-20:41 | 1602.00 | 1176.17 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.58 |
June | 1711.05 | 12-JUN-15:02 | 583.20 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 34.16 | 0.00 |
July | 1714.87 | 04-JUL-15:02 | 324.00 | 261.67 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 | 0.00 |
August | 1722.45 | 21-AUG-15:02 | 583.20 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 | 0.00 |
September | 1895.99 | 18-SEP-16:01 | 972.00 | 370.03 | 1238.69 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | 0.00 |
October | 1951.44 | 15-OCT-16:21 | 954.00 | 436.11 | 1032.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
November | 1808.91 | 08-NOV-21:11 | 1281.60 | 940.94 | 1424.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
December | 1772.70 | 10-DEC-19:21 | 936.00 | 1057.23 | 949.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1711.05 | 324.00 | 222.02 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1951.44 | 1620.00 | 1321.54 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 34.16 | 34.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29904.61 | 23-JAN-22:53 | 188921.38 | 16043.25 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.30 |
February | 33263.68 | 08-FEB-22:27 | 80966.30 | 6875.68 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.01 |
March | 27152.52 | 22-MAR-22:03 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.47 |
April | 30789.27 | 05-APR-22:04 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.68 |
May | 22317.59 | 16-MAY-18:50 | 62973.79 | 5500.54 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 62.56 | 0.00 |
June | 22870.89 | 13-JUN-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.75 | 0.00 |
July | 23634.46 | 07-JUL-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 | 0.00 |
August | 23376.93 | 18-AUG-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 0.00 |
September | 22043.36 | 07-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 0.00 |
October | 29043.40 | 25-OCT-22:03 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.03 |
November | 34369.63 | 30-NOV-23:41 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.19 |
December | 34287.65 | 01-DEC-23:31 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22043.36 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34369.63 | 188921.38 | 16043.25 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 375.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32240.07 | 04-JAN-21:43 | 71970.05 | 9167.57 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.58 |
February | 35265.94 | 08-FEB-22:27 | 80966.30 | 6875.68 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.61 |
March | 31525.74 | 22-MAR-22:03 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.71 |
April | 32542.85 | 05-APR-22:04 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.48 |
May | 24464.09 | 16-MAY-18:50 | 62973.79 | 5500.54 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 62.71 | 0.00 |
June | 24342.62 | 13-JUN-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.75 | 0.00 |
July | 24944.34 | 07-JUL-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 99.03 | 0.00 |
August | 24665.84 | 18-AUG-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 0.00 |
September | 23515.89 | 07-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 0.00 |
October | 32260.57 | 25-OCT-22:03 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.91 |
November | 36165.32 | 30-NOV-23:41 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.16 |
December | 36073.55 | 01-DEC-23:31 | 188921.38 | 8021.63 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23515.89 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36165.32 | 188921.38 | 9167.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 376.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35542.50 | 22-JAN-17:49 | 8539.39 | 2152.75 | 119302.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 0.00 | 307.43 |
February | 33894.69 | 06-FEB-11:36 | 5337.12 | 3363.68 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 367.58 |
March | 33069.19 | 22-MAR-18:07 | 11207.95 | 6458.26 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 294.41 |
April | 33426.32 | 07-APR-07:03 | 6404.54 | 3229.13 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 334.57 |
May | 31573.44 | 15-MAY-18:07 | 11207.95 | 6458.26 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 48.84 | 0.00 |
June | 30523.98 | 25-JUN-10:40 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 80.81 | 0.00 |
July | 31067.00 | 08-JUL-10:50 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 131.22 | 0.00 |
August | 30899.43 | 27-AUG-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 83.94 | 0.00 |
September | 30358.57 | 09-SEP-10:50 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 87.74 | 0.00 |
October | 33348.01 | 26-OCT-06:50 | 8539.39 | 5381.88 | 119302.85 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 337.04 |
November | 35480.75 | 25-NOV-08:09 | 10674.24 | 4305.51 | 119302.85 | 119961.77 | 0.00 | 0.00 | 0.00 | 0.00 | 342.98 |
December | 35443.13 | 21-DEC-07:40 | 10674.24 | 6727.35 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 344.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 30358.57 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35542.50 | 11207.95 | 6727.35 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 131.22 | 367.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4193.53 | 23-JAN-22:13 | 7186.32 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.69 |
February | 4134.64 | 28-FEB-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.24 |
March | 4471.46 | 30-MAR-21:10 | 9581.76 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
April | 4891.32 | 17-APR-17:12 | 5323.20 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.77 | 0.00 |
May | 4865.85 | 20-MAY-15:20 | 1596.96 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 | 0.00 |
June | 5120.93 | 24-JUN-18:02 | 9581.76 | 9222.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.01 | 0.00 |
July | 6163.06 | 08-JUL-17:12 | 6387.84 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.92 | 0.00 |
August | 5618.01 | 18-AUG-15:25 | 2661.60 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 | 0.00 |
September | 5025.24 | 07-SEP-16:00 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.12 | 0.00 |
October | 4589.93 | 11-OCT-15:50 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.38 | 0.00 |
November | 4149.69 | 05-NOV-15:10 | 4790.88 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 | 0.00 |
December | 4040.24 | 07-DEC-23:17 | 9581.76 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4040.24 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6163.06 | 9581.76 | 9222.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 | 256.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.385685E+12 | 302817.10 | 19-JAN-20:49 | 0.629908E+12 | 567011.01 | 14-JAN-19:10 |
February | 0.362085E+12 | 295842.23 | 28-FEB-20:49 | 0.509487E+12 | 553327.49 | 05-FEB-17:10 |
March | 0.430145E+12 | 355836.01 | 30-MAR-19:10 | 0.486654E+12 | 501405.95 | 22-MAR-17:00 |
April | 0.472403E+12 | 353021.88 | 04-APR-19:00 | 0.436371E+12 | 446043.13 | 05-APR-20:30 |
May | 0.574221E+12 | 384739.19 | 30-MAY-19:40 | 0.417629E+12 | 353171.21 | 01-MAY-17:10 |
June | 0.648238E+12 | 408142.68 | 28-JUN-19:49 | 0.380998E+12 | 339013.29 | 02-JUN-17:10 |
July | 0.728935E+12 | 430484.58 | 07-JUL-19:49 | 0.384929E+12 | 320734.03 | 03-JUL-17:00 |
August | 0.743806E+12 | 433675.71 | 18-AUG-19:19 | 0.384475E+12 | 320684.63 | 30-AUG-17:10 |
September | 0.613802E+12 | 408154.94 | 07-SEP-19:10 | 0.379809E+12 | 336467.82 | 29-SEP-17:30 |
October | 0.484037E+12 | 392608.13 | 18-OCT-19:00 | 0.429822E+12 | 403841.62 | 25-OCT-21:49 |
November | 0.411904E+12 | 330673.11 | 27-NOV-20:10 | 0.464619E+12 | 505545.98 | 20-NOV-19:30 |
December | 0.390983E+12 | 285829.21 | 13-DEC-20:10 | 0.555018E+12 | 532106.54 | 02-DEC-18:40 |
Annual Sum or Average | 0.624624E+13 | 0.545972E+13 | ||||
Minimum of Months | 0.362085E+12 | 285829.21 | 0.379809E+12 | 320684.63 | ||
Maximum of Months | 0.743806E+12 | 433675.71 | 0.629908E+12 | 567011.01 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.744902E+11 | 0.259769E+11 | 0.140828E+12 | 0.552134E+11 | 0.407675E+11 | 0.567951E+10 | 0.00 | 0.919896E+10 | 0.00 | 0.00 | 0.206835E+11 | 0.770616E+10 | 0.00 |
February | 0.672380E+11 | 0.221715E+11 | 0.127191E+12 | 0.498703E+11 | 0.359067E+11 | 0.663228E+10 | 0.00 | 0.268788E+11 | 0.00 | 0.00 | 0.145771E+11 | 0.696342E+10 | 0.00 |
March | 0.738742E+11 | 0.226722E+11 | 0.140882E+12 | 0.552167E+11 | 0.388356E+11 | 0.995930E+10 | 0.00 | 0.653600E+11 | 0.00 | 0.00 | 0.104517E+11 | 0.770473E+10 | 0.00 |
April | 0.711505E+11 | 0.200685E+11 | 0.136245E+12 | 0.534313E+11 | 0.387457E+11 | 0.110572E+11 | 0.00 | 0.119573E+12 | 0.00 | 0.00 | 0.960589E+10 | 0.746631E+10 | 0.00 |
May | 0.731190E+11 | 0.191072E+11 | 0.140860E+12 | 0.552141E+11 | 0.416259E+11 | 0.121124E+11 | 0.00 | 0.205079E+12 | 0.00 | 0.00 | 0.141205E+11 | 0.770566E+10 | 0.00 |
June | 0.705542E+11 | 0.177753E+11 | 0.136336E+12 | 0.534342E+11 | 0.432909E+11 | 0.123930E+11 | 0.00 | 0.281417E+12 | 0.00 | 0.00 | 0.204582E+11 | 0.745799E+10 | 0.00 |
July | 0.730677E+11 | 0.186365E+11 | 0.140770E+12 | 0.552105E+11 | 0.456685E+11 | 0.133042E+11 | 0.00 | 0.344060E+12 | 0.00 | 0.00 | 0.252281E+11 | 0.771345E+10 | 0.00 |
August | 0.732528E+11 | 0.199984E+11 | 0.140892E+12 | 0.552161E+11 | 0.462299E+11 | 0.134882E+11 | 0.00 | 0.355672E+12 | 0.00 | 0.00 | 0.260466E+11 | 0.770520E+10 | 0.00 |
September | 0.714602E+11 | 0.211300E+11 | 0.136256E+12 | 0.534317E+11 | 0.410470E+11 | 0.121636E+11 | 0.00 | 0.247944E+12 | 0.00 | 0.00 | 0.177770E+11 | 0.746756E+10 | 0.00 |
October | 0.743226E+11 | 0.237738E+11 | 0.140818E+12 | 0.552132E+11 | 0.395458E+11 | 0.110785E+11 | 0.00 | 0.114474E+12 | 0.00 | 0.00 | 0.118610E+11 | 0.770440E+10 | 0.00 |
November | 0.719997E+11 | 0.247051E+11 | 0.136330E+12 | 0.534333E+11 | 0.375242E+11 | 0.892716E+10 | 0.00 | 0.537821E+11 | 0.00 | 0.00 | 0.127398E+11 | 0.745053E+10 | 0.00 |
December | 0.744811E+11 | 0.264376E+11 | 0.140770E+12 | 0.552118E+11 | 0.393400E+11 | 0.659519E+10 | 0.00 | 0.169718E+11 | 0.00 | 0.00 | 0.182999E+11 | 0.771431E+10 | 0.00 |
Annual Sum or Average | 0.869010E+12 | 0.262453E+12 | 0.165818E+13 | 0.650097E+12 | 0.488528E+12 | 0.123391E+12 | 0.00 | 0.184041E+13 | 0.00 | 0.00 | 0.201849E+12 | 0.907597E+11 | 0.00 |
Minimum of Months | 0.672380E+11 | 0.177753E+11 | 0.127191E+12 | 0.498703E+11 | 0.359067E+11 | 0.567951E+10 | 0.00 | 0.919896E+10 | 0.00 | 0.00 | 0.960589E+10 | 0.696342E+10 | 0.00 |
Maximum of Months | 0.744902E+11 | 0.264376E+11 | 0.140892E+12 | 0.552167E+11 | 0.462299E+11 | 0.134882E+11 | 0.00 | 0.355672E+12 | 0.00 | 0.00 | 0.260466E+11 | 0.771431E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.199808E+12 | 0.00 | 0.278181E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.120680E+12 | 0.00 | 0.251604E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.619503E+11 | 0.00 | 0.272680E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.362790E+11 | 0.00 | 0.253136E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.171710E+11 | 0.00 | 0.248480E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.473985E+10 | 0.00 | 0.229144E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.341719E+10 | 0.00 | 0.229691E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.324823E+10 | 0.00 | 0.229188E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.515231E+10 | 0.00 | 0.227686E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.314862E+11 | 0.00 | 0.246433E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.663466E+11 | 0.00 | 0.251181E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.132056E+12 | 0.00 | 0.271142E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.682334E+12 | 0.00 | 0.298855E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.324823E+10 | 0.00 | 0.227686E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.199808E+12 | 0.00 | 0.278181E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 71560.59 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39721.54 | 02-JAN-07:19 | 23959.71 | 14-JAN-19:10 | 5056.57 | 16-JAN-10:09 | 0.00 | 01-JAN-00:10 |
February | 71560.59 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39721.54 | 01-FEB-07:19 | 26284.05 | 08-FEB-21:40 | 5076.02 | 09-FEB-09:50 | 0.00 | 01-FEB-00:10 |
March | 71560.59 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39721.54 | 01-MAR-07:19 | 22118.01 | 30-MAR-18:10 | 4975.15 | 18-MAR-09:09 | 0.00 | 01-MAR-00:10 |
April | 71560.59 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39721.54 | 03-APR-06:19 | 24624.98 | 17-APR-18:10 | 5234.61 | 15-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 71560.59 | 01-MAY-19:19 | 16690.39 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39721.54 | 08-MAY-06:19 | 25581.50 | 16-MAY-18:10 | 5471.33 | 30-MAY-21:00 | 0.00 | 01-MAY-00:10 |
June | 71560.59 | 01-JUN-19:30 | 16690.39 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39721.06 | 23-JUN-06:19 | 26065.28 | 12-JUN-18:30 | 5775.57 | 26-JUN-21:00 | 0.00 | 01-JUN-00:10 |
July | 71560.59 | 03-JUL-19:30 | 16690.39 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39721.37 | 28-JUL-06:19 | 27190.98 | 07-JUL-18:30 | 5888.94 | 25-JUL-21:00 | 0.00 | 01-JUL-00:10 |
August | 71560.59 | 01-AUG-19:19 | 16690.39 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39721.54 | 14-AUG-06:19 | 26630.27 | 18-AUG-18:30 | 5905.32 | 23-AUG-22:00 | 0.00 | 01-AUG-00:10 |
September | 71560.59 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39721.54 | 01-SEP-06:19 | 24896.23 | 07-SEP-18:10 | 5690.09 | 09-SEP-21:00 | 0.00 | 01-SEP-00:10 |
October | 71560.59 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39721.54 | 02-OCT-06:19 | 24127.17 | 25-OCT-21:00 | 5699.71 | 18-OCT-21:00 | 0.00 | 01-OCT-00:10 |
November | 71560.59 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39721.54 | 01-NOV-06:19 | 26548.45 | 21-NOV-20:30 | 5009.57 | 22-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 71560.59 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39721.54 | 01-DEC-07:19 | 21787.17 | 04-DEC-22:10 | 5080.93 | 18-DEC-10:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.06 | 21787.17 | 4975.15 | 0.00 | |||||||
Maximum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.54 | 27190.98 | 5905.32 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 76503.90 | 19-JAN-22:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4739.33 | 26-JAN-07:10 | 0.00 |
February | 89051.31 | 28-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:40 | 4738.62 | 09-FEB-19:10 | 0.00 |
March | 112030.91 | 30-MAR-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-02:20 | 4738.43 | 13-MAR-18:10 | 0.00 |
April | 112367.25 | 12-APR-15:30 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.74 | 06-APR-06:10 | 0.00 |
May | 150287.74 | 30-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-15:39 | 4738.58 | 15-MAY-18:10 | 0.00 |
June | 177161.33 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-08:39 | 4738.70 | 21-JUN-18:10 | 0.00 |
July | 202735.36 | 08-JUL-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.74 | 19-JUL-18:10 | 0.00 |
August | 195243.87 | 18-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.73 | 16-AUG-18:10 | 0.00 |
September | 172431.18 | 07-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-11:09 | 4738.60 | 11-SEP-18:10 | 0.00 |
October | 161661.78 | 18-OCT-21:00 | 0.00 | 0.00 | 9938.94 | 01-OCT-12:00 | 4738.58 | 02-OCT-18:10 | 0.00 |
November | 103891.52 | 19-NOV-22:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:20 | 4738.43 | 08-NOV-07:19 | 0.00 |
December | 80409.28 | 12-DEC-13:20 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.40 | 26-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 76503.90 | 0.00 | 0.00 | 9938.94 | 4738.40 | 0.00 | |||
Maximum of Months | 202735.36 | 0.00 | 0.00 | 9938.94 | 4739.33 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 302817.10 | 19-JAN-20:49 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 16204.15 | 4377.92 | 0.00 | 69192.53 | 0.00 |
February | 295842.23 | 28-FEB-20:49 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 17043.73 | 4305.00 | 0.00 | 61785.06 | 0.00 |
March | 355836.01 | 30-MAR-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 21165.36 | 4837.99 | 0.00 | 106634.01 | 0.00 |
April | 353021.88 | 04-APR-19:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 20631.63 | 4783.89 | 0.00 | 104963.58 | 0.00 |
May | 384739.19 | 30-MAY-19:40 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 22582.69 | 5264.76 | 0.00 | 134755.64 | 0.00 |
June | 408142.68 | 28-JUN-19:49 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 24049.46 | 5399.60 | 0.00 | 155545.09 | 0.00 |
July | 430484.58 | 07-JUL-19:49 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 25711.33 | 5549.92 | 0.00 | 176597.54 | 0.00 |
August | 433675.71 | 18-AUG-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.00 | 25808.95 | 5523.04 | 0.00 | 180003.66 | 0.00 |
September | 408154.94 | 07-SEP-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 24034.40 | 5410.51 | 0.00 | 155703.52 | 0.00 |
October | 392608.13 | 18-OCT-19:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 18199.43 | 5371.62 | 0.00 | 146301.76 | 0.00 |
November | 330673.11 | 27-NOV-20:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 16447.74 | 4513.92 | 0.00 | 88049.49 | 0.00 |
December | 285829.21 | 13-DEC-20:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 16335.36 | 4313.68 | 0.00 | 52344.37 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 285829.21 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 16204.15 | 4305.00 | 0.00 | 52344.37 | 0.00 | |
Maximum of Months | 433675.71 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 25808.95 | 5549.92 | 0.00 | 180003.66 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 277275.66 | 17-JAN-10:20 | 0.00 | 271201.55 | 19-JAN-21:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 231820.17 | 12-FEB-07:10 | 0.00 | 272764.72 | 10-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 197648.11 | 22-MAR-09:00 | 0.00 | 254514.46 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 144456.68 | 26-APR-06:30 | 0.00 | 250052.10 | 06-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 57082.24 | 10-MAY-03:49 | 0.00 | 247100.98 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 24444.88 | 08-JUN-15:20 | 0.00 | 234898.11 | 02-JUN-19:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 11220.18 | 29-JUL-04:49 | 0.00 | 217053.01 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 9559.46 | 21-AUG-03:00 | 0.00 | 216906.71 | 31-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 35717.22 | 30-SEP-15:09 | 0.00 | 231982.99 | 28-SEP-20:10 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 138761.91 | 26-OCT-06:40 | 0.00 | 246821.97 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 203170.25 | 14-NOV-07:49 | 0.00 | 250395.15 | 30-NOV-18:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 232552.50 | 18-DEC-10:50 | 0.00 | 253576.86 | 18-DEC-18:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 9559.46 | 0.00 | 216906.71 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 277275.66 | 0.00 | 272764.72 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 20.38 | 4.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 6.17 | 20.03 | 6.17 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.33 | 20.17 | 10.33 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 20.38 | 6.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 25.17 | 14.17 | 25.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.09 | 8.17 | 25.09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.16 | 1.83 | 25.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.37 | 2.67 | 25.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.01 | 1.83 | 25.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.85 | 3.67 | 24.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.09 | 9.50 | 25.09 |
Annual Sum or Average | 0.00 | 0.00 | 41.83 | 25.11 | 41.83 | 25.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 25.37 | 14.17 | 25.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.48 | 1.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.67 | 20.51 | 0.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.90 | 0.33 | 21.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.04 | 0.33 | 22.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 20.49 | 2.50 | 20.49 | 1.83 | 20.85 | 1.83 | 21.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.51 | 1.83 | 20.51 | 0.67 | 22.04 | 0.67 | 22.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.47 | 3.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.17 | 20.43 | 1.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.54 | 0.67 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 5.00 | 20.47 | 5.00 | 20.47 | 1.83 | 20.67 | 1.83 | 20.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.54 | 3.17 | 20.54 | 0.83 | 21.81 | 0.83 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.25 | 2.33 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
February | 1.50 | 20.38 | 1.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.71 | 1.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.82 | 2.33 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 4.00 | 20.31 | 4.00 | 20.31 | 6.33 | 20.96 | 6.33 | 21.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.53 | 2.33 | 20.53 | 2.33 | 21.82 | 2.33 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.45 | 1.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 0.17 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.97 | 0.83 | 21.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.07 | 2.50 | 22.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.08 | 5.67 | 22.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 22.14 | 6.50 | 22.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.07 | 4.00 | 22.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.07 | 3.50 | 22.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 20.46 | 2.00 | 20.46 | 23.50 | 21.84 | 23.50 | 21.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.50 | 1.83 | 20.50 | 6.50 | 22.14 | 6.50 | 22.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.47 | 3.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.17 | 20.51 | 1.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.88 | 0.83 | 21.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.10 | 2.33 | 22.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.10 | 5.83 | 22.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.16 | 6.67 | 22.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.05 | 4.00 | 22.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.07 | 2.67 | 22.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.33 | 20.48 | 4.33 | 20.48 | 22.33 | 21.64 | 22.33 | 21.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.51 | 3.17 | 20.51 | 6.67 | 22.16 | 6.67 | 22.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.44 | 1.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.50 | 20.45 | 0.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.90 | 0.50 | 21.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.00 | 0.50 | 22.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 20.44 | 2.33 | 20.44 | 3.67 | 21.04 | 3.67 | 21.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.45 | 1.83 | 20.45 | 1.17 | 22.00 | 1.17 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.42 | 3.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 1.17 | 20.35 | 1.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.89 | 0.17 | 21.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 4.67 | 20.41 | 4.67 | 20.41 | 2.67 | 20.72 | 2.67 | 20.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.52 | 3.17 | 20.52 | 1.33 | 21.89 | 1.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.45 | 0.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.83 | 0.50 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.73 | 2.33 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.78 | 3.00 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.85 | 4.33 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.45 | 0.83 | 20.45 | 12.83 | 21.64 | 12.83 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.45 | 0.83 | 20.45 | 4.33 | 21.85 | 4.33 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.20 | 0.17 | 25.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.73 | 0.50 | 24.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.96 | 0.50 | 24.96 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 24.86 | 1.33 | 24.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.20 | 0.50 | 25.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.68 | 0.17 | 24.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.28 | 0.17 | 25.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.85 | 0.33 | 24.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.05 | 0.50 | 25.05 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 24.97 | 1.17 | 24.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.28 | 0.50 | 25.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 24.94 | 28.17 | 24.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 25.00 | 16.33 | 25.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.92 | 4.50 | 24.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.04 | 4.83 | 25.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.92 | 2.33 | 24.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 24.91 | 10.50 | 24.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 24.98 | 23.00 | 24.98 |
Annual Sum or Average | 0.00 | 0.00 | 89.83 | 24.96 | 89.83 | 24.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 25.04 | 28.17 | 25.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.42 | 0.67 | 21.42 | 0.67 | 21.42 |
February | 672.00 | 21.20 | 32.83 | 21.20 | 32.83 | 21.19 |
March | 744.00 | 21.09 | 17.33 | 21.09 | 17.33 | 21.09 |
April | 720.00 | 21.00 | 10.67 | 21.00 | 10.67 | 21.00 |
May | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
June | 720.00 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
July | 744.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
August | 744.00 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
September | 699.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
October | 729.67 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
November | 714.67 | 22.92 | 0.00 | 22.92 | 0.00 | 22.92 |
December | 744.00 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
Annual Sum or Average | 8719.33 | 21.85 | 61.50 | 21.85 | 61.50 | 21.84 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.92 | 32.83 | 22.92 | 32.83 | 22.92 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 381.17 | 21.03 | 381.17 | 21.02 |
February | 666.67 | 21.12 | 220.00 | 21.08 | 220.00 | 21.06 |
March | 731.50 | 21.24 | 36.67 | 21.24 | 33.67 | 21.23 |
April | 691.17 | 21.31 | 14.50 | 21.31 | 12.00 | 21.31 |
May | 731.50 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
June | 568.17 | 21.82 | 33.67 | 21.91 | 0.00 | 21.91 |
July | 463.50 | 21.88 | 164.83 | 22.32 | 0.00 | 22.32 |
August | 363.67 | 22.06 | 274.17 | 22.73 | 0.00 | 22.73 |
September | 556.67 | 21.58 | 98.83 | 21.89 | 0.00 | 21.89 |
October | 670.67 | 21.37 | 35.50 | 21.48 | 0.00 | 21.48 |
November | 693.33 | 21.18 | 47.33 | 21.17 | 46.67 | 21.16 |
December | 737.67 | 21.13 | 204.67 | 21.10 | 203.83 | 21.09 |
Annual Sum or Average | 7618.50 | 21.38 | 1511.33 | 21.49 | 897.33 | 21.45 |
Minimum of Months | 363.67 | 21.06 | 0.00 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 22.06 | 381.17 | 22.73 | 381.17 | 22.73 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.11 | 22.50 | 21.10 | 22.50 | 21.10 |
February | 672.00 | 21.19 | 47.00 | 21.18 | 47.00 | 21.17 |
March | 743.50 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
April | 719.67 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 726.83 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
June | 612.67 | 22.31 | 34.83 | 22.39 | 0.00 | 22.39 |
July | 557.50 | 22.42 | 86.00 | 22.61 | 0.00 | 22.61 |
August | 498.83 | 22.58 | 119.17 | 22.81 | 0.00 | 22.81 |
September | 646.83 | 22.18 | 24.00 | 22.24 | 0.00 | 22.24 |
October | 740.67 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
November | 720.00 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
December | 744.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
Annual Sum or Average | 8126.50 | 21.70 | 333.50 | 21.76 | 69.50 | 21.76 |
Minimum of Months | 498.83 | 21.11 | 0.00 | 21.10 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 22.58 | 119.17 | 22.81 | 47.00 | 22.81 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 439.50 | 21.00 | 439.50 | 21.00 |
February | 672.00 | 21.02 | 217.17 | 21.01 | 217.17 | 21.01 |
March | 744.00 | 21.08 | 55.67 | 21.08 | 55.67 | 21.07 |
April | 720.00 | 21.25 | 1.83 | 21.25 | 1.83 | 21.25 |
May | 744.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
June | 720.00 | 22.47 | 0.00 | 22.47 | 0.00 | 22.47 |
July | 686.67 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
August | 690.00 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
September | 720.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
October | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
November | 720.00 | 21.05 | 26.67 | 21.05 | 26.67 | 21.05 |
December | 744.00 | 21.01 | 190.00 | 21.01 | 190.00 | 21.01 |
Annual Sum or Average | 8648.67 | 21.62 | 930.83 | 21.56 | 930.83 | 21.51 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.88 | 439.50 | 22.88 | 439.50 | 22.88 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 476.00 | 21.00 | 476.00 | 21.00 |
February | 672.00 | 21.00 | 226.33 | 20.99 | 226.33 | 20.99 |
March | 744.00 | 21.02 | 64.00 | 21.02 | 64.00 | 21.02 |
April | 720.00 | 21.10 | 3.00 | 21.10 | 3.00 | 21.10 |
May | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
June | 720.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
July | 744.00 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
August | 743.50 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
September | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
October | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
November | 720.00 | 21.01 | 46.33 | 21.01 | 46.33 | 21.01 |
December | 744.00 | 21.00 | 213.17 | 21.00 | 213.17 | 21.00 |
Annual Sum or Average | 8759.50 | 21.48 | 1028.83 | 21.43 | 1028.83 | 21.39 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 20.99 | 0.00 | 20.99 |
Maximum of Months | 744.00 | 22.62 | 476.00 | 22.62 | 476.00 | 22.62 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 526.50 | 21.76 | 234.00 | 22.30 | 120.83 | 22.55 |
February | 447.67 | 21.82 | 241.33 | 22.35 | 115.50 | 22.60 |
March | 421.67 | 22.01 | 307.17 | 22.50 | 141.33 | 22.74 |
April | 302.00 | 22.47 | 361.50 | 22.69 | 147.50 | 22.93 |
May | 228.00 | 23.14 | 486.17 | 22.70 | 167.00 | 22.93 |
June | 192.33 | 23.64 | 560.17 | 22.66 | 174.50 | 22.89 |
July | 190.17 | 23.79 | 607.83 | 22.64 | 183.83 | 22.88 |
August | 191.50 | 23.86 | 624.00 | 22.64 | 190.33 | 22.88 |
September | 196.50 | 23.48 | 520.00 | 22.68 | 167.17 | 22.91 |
October | 302.00 | 22.47 | 379.17 | 22.66 | 150.00 | 22.89 |
November | 417.33 | 21.95 | 299.50 | 22.45 | 129.50 | 22.69 |
December | 488.00 | 21.83 | 269.17 | 22.37 | 126.33 | 22.61 |
Annual Sum or Average | 3903.67 | 22.39 | 4890.00 | 22.55 | 1813.83 | 22.80 |
Minimum of Months | 190.17 | 21.76 | 234.00 | 22.30 | 115.50 | 22.55 |
Maximum of Months | 526.50 | 23.86 | 624.00 | 22.70 | 190.33 | 22.93 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.50 | 21.25 | 96.67 | 21.22 | 96.67 | 21.20 |
February | 661.67 | 21.44 | 56.50 | 21.40 | 56.50 | 21.37 |
March | 687.50 | 21.74 | 21.00 | 21.79 | 0.00 | 21.79 |
April | 608.33 | 21.78 | 29.83 | 21.86 | 0.00 | 21.86 |
May | 565.83 | 21.91 | 76.17 | 22.09 | 0.00 | 22.09 |
June | 351.33 | 22.06 | 279.83 | 22.68 | 21.00 | 22.71 |
July | 282.33 | 22.24 | 393.67 | 22.98 | 48.33 | 23.02 |
August | 278.33 | 22.83 | 532.33 | 23.29 | 138.00 | 23.35 |
September | 363.00 | 22.03 | 289.67 | 22.67 | 27.50 | 22.71 |
October | 564.00 | 21.88 | 105.33 | 22.12 | 8.67 | 22.14 |
November | 668.17 | 21.67 | 10.83 | 21.69 | 0.00 | 21.69 |
December | 726.83 | 21.41 | 11.17 | 21.42 | 8.17 | 21.41 |
Annual Sum or Average | 6499.83 | 21.74 | 1903.00 | 22.09 | 404.83 | 22.11 |
Minimum of Months | 278.33 | 21.25 | 10.83 | 21.22 | 0.00 | 21.20 |
Maximum of Months | 742.50 | 22.83 | 532.33 | 23.29 | 138.00 | 23.35 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.31 | 6.00 | 21.31 | 6.00 | 21.30 |
February | 672.00 | 21.48 | 1.67 | 21.48 | 1.67 | 21.48 |
March | 737.50 | 21.78 | 1.33 | 21.78 | 0.00 | 21.78 |
April | 700.50 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
May | 669.33 | 22.13 | 17.00 | 22.17 | 0.00 | 22.17 |
June | 447.67 | 22.29 | 154.33 | 22.64 | 0.00 | 22.64 |
July | 382.50 | 22.35 | 249.50 | 22.88 | 0.00 | 22.88 |
August | 314.00 | 22.44 | 332.83 | 23.08 | 0.00 | 23.08 |
September | 497.17 | 22.29 | 101.17 | 22.52 | 0.00 | 22.52 |
October | 710.67 | 22.04 | 6.83 | 22.05 | 0.00 | 22.05 |
November | 720.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
December | 744.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
Annual Sum or Average | 7339.33 | 21.87 | 870.67 | 22.06 | 7.67 | 22.06 |
Minimum of Months | 314.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.30 |
Maximum of Months | 744.00 | 22.44 | 332.83 | 23.08 | 6.00 | 23.08 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 553.00 | 20.73 | 553.00 | 20.71 |
February | 669.33 | 21.03 | 316.50 | 20.90 | 316.50 | 20.83 |
March | 725.17 | 21.55 | 51.17 | 21.51 | 48.67 | 21.46 |
April | 654.67 | 21.70 | 27.33 | 21.75 | 15.33 | 21.74 |
May | 628.67 | 21.80 | 62.83 | 21.98 | 33.00 | 22.03 |
June | 590.83 | 21.73 | 64.50 | 21.91 | 53.17 | 22.03 |
July | 596.50 | 21.70 | 104.67 | 21.95 | 85.33 | 22.11 |
August | 589.33 | 21.61 | 87.83 | 21.85 | 65.67 | 21.99 |
September | 596.50 | 21.73 | 64.83 | 21.91 | 49.33 | 22.00 |
October | 682.67 | 21.58 | 71.67 | 21.67 | 50.33 | 21.66 |
November | 718.83 | 21.37 | 110.33 | 21.30 | 110.33 | 21.24 |
December | 744.00 | 20.98 | 389.00 | 20.89 | 389.00 | 20.84 |
Annual Sum or Average | 7940.50 | 21.44 | 1903.67 | 21.43 | 1769.67 | 21.38 |
Minimum of Months | 589.33 | 20.78 | 27.33 | 20.73 | 15.33 | 20.71 |
Maximum of Months | 744.00 | 21.80 | 553.00 | 21.98 | 553.00 | 22.11 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.58 | 623.00 | 20.55 | 623.00 | 20.54 |
February | 672.00 | 20.84 | 361.50 | 20.72 | 361.50 | 20.66 |
March | 739.67 | 21.35 | 100.00 | 21.26 | 100.00 | 21.18 |
April | 688.17 | 21.70 | 33.33 | 21.70 | 25.83 | 21.68 |
May | 646.33 | 21.82 | 55.50 | 21.96 | 35.50 | 22.01 |
June | 594.33 | 21.74 | 64.50 | 21.93 | 52.67 | 22.05 |
July | 598.50 | 21.71 | 103.17 | 21.96 | 84.17 | 22.12 |
August | 602.67 | 21.64 | 79.33 | 21.85 | 68.50 | 21.99 |
September | 644.00 | 21.80 | 55.83 | 21.93 | 50.83 | 22.02 |
October | 727.33 | 21.46 | 67.50 | 21.43 | 67.50 | 21.41 |
November | 720.00 | 21.07 | 207.33 | 20.97 | 207.33 | 20.91 |
December | 744.00 | 20.71 | 530.83 | 20.64 | 530.83 | 20.62 |
Annual Sum or Average | 8121.00 | 21.34 | 2281.83 | 21.28 | 2207.67 | 21.22 |
Minimum of Months | 594.33 | 20.58 | 33.33 | 20.55 | 25.83 | 20.54 |
Maximum of Months | 744.00 | 21.82 | 623.00 | 21.96 | 623.00 | 22.12 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 519.17 | 20.73 | 519.17 | 20.71 |
February | 672.00 | 20.95 | 270.83 | 20.85 | 270.83 | 20.80 |
March | 744.00 | 21.24 | 64.00 | 21.21 | 64.00 | 21.18 |
April | 720.00 | 21.58 | 6.67 | 21.57 | 6.67 | 21.57 |
May | 740.83 | 21.83 | 18.83 | 21.86 | 18.83 | 21.89 |
June | 718.83 | 21.89 | 39.33 | 21.96 | 39.33 | 22.02 |
July | 742.83 | 21.91 | 70.00 | 22.02 | 69.83 | 22.11 |
August | 744.00 | 21.82 | 54.67 | 21.91 | 54.67 | 21.98 |
September | 719.17 | 21.79 | 31.33 | 21.85 | 31.33 | 21.90 |
October | 744.00 | 21.39 | 28.33 | 21.42 | 28.33 | 21.44 |
November | 720.00 | 21.12 | 101.33 | 21.07 | 101.33 | 21.04 |
December | 744.00 | 20.92 | 312.83 | 20.85 | 312.83 | 20.81 |
Annual Sum or Average | 8753.67 | 21.44 | 1517.33 | 21.38 | 1517.17 | 21.34 |
Minimum of Months | 672.00 | 20.78 | 6.67 | 20.73 | 6.67 | 20.71 |
Maximum of Months | 744.00 | 21.91 | 519.17 | 22.02 | 519.17 | 22.11 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.81 | 530.50 | 20.76 | 530.50 | 20.74 |
February | 672.00 | 21.08 | 309.67 | 20.94 | 309.67 | 20.87 |
March | 740.33 | 21.58 | 46.50 | 21.54 | 46.50 | 21.50 |
April | 678.83 | 21.82 | 17.50 | 21.83 | 14.83 | 21.82 |
May | 609.33 | 21.84 | 60.17 | 22.02 | 31.50 | 22.06 |
June | 555.83 | 21.74 | 73.00 | 22.02 | 53.00 | 22.18 |
July | 567.67 | 21.73 | 103.33 | 22.08 | 86.17 | 22.29 |
August | 567.83 | 21.61 | 74.33 | 21.88 | 65.83 | 22.06 |
September | 583.50 | 21.77 | 64.83 | 21.98 | 51.00 | 22.10 |
October | 710.00 | 21.68 | 57.00 | 21.67 | 55.00 | 21.66 |
November | 720.00 | 21.36 | 101.50 | 21.30 | 101.50 | 21.25 |
December | 744.00 | 20.99 | 377.17 | 20.92 | 377.17 | 20.88 |
Annual Sum or Average | 7893.33 | 21.48 | 1815.50 | 21.47 | 1722.67 | 21.44 |
Minimum of Months | 555.83 | 20.81 | 17.50 | 20.76 | 14.83 | 20.74 |
Maximum of Months | 744.00 | 21.84 | 530.50 | 22.08 | 530.50 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.60 | 610.33 | 20.56 | 610.33 | 20.55 |
February | 672.00 | 20.85 | 345.83 | 20.73 | 345.83 | 20.68 |
March | 744.00 | 21.33 | 95.50 | 21.27 | 95.50 | 21.23 |
April | 715.67 | 21.82 | 19.83 | 21.82 | 17.83 | 21.80 |
May | 624.17 | 21.86 | 59.33 | 22.02 | 34.33 | 22.07 |
June | 553.67 | 21.74 | 74.00 | 22.03 | 53.00 | 22.19 |
July | 567.50 | 21.74 | 102.50 | 22.08 | 85.67 | 22.30 |
August | 573.50 | 21.62 | 74.83 | 21.88 | 68.17 | 22.06 |
September | 636.67 | 21.87 | 60.33 | 22.02 | 51.00 | 22.13 |
October | 742.17 | 21.51 | 68.00 | 21.49 | 67.67 | 21.47 |
November | 720.00 | 21.02 | 206.33 | 20.95 | 206.33 | 20.91 |
December | 744.00 | 20.71 | 516.50 | 20.65 | 516.50 | 20.62 |
Annual Sum or Average | 8037.33 | 21.36 | 2233.33 | 21.31 | 2152.17 | 21.27 |
Minimum of Months | 553.67 | 20.60 | 19.83 | 20.56 | 17.83 | 20.55 |
Maximum of Months | 744.00 | 21.87 | 610.33 | 22.08 | 610.33 | 22.30 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 236.00 | 21.00 | 236.00 | 21.00 |
February | 672.00 | 21.03 | 174.50 | 21.02 | 174.50 | 21.02 |
March | 744.00 | 21.13 | 17.00 | 21.12 | 17.00 | 21.12 |
April | 720.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
May | 744.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
June | 720.00 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
July | 744.00 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
August | 744.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
September | 720.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
October | 744.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
November | 720.00 | 21.04 | 6.83 | 21.04 | 6.83 | 21.04 |
December | 744.00 | 21.01 | 101.67 | 21.01 | 101.67 | 21.01 |
Annual Sum or Average | 8760.00 | 21.65 | 536.00 | 21.61 | 536.00 | 21.58 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.72 | 236.00 | 22.72 | 236.00 | 22.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 600.00 | 20.64 | 600.00 | 20.62 |
February | 667.50 | 20.96 | 367.00 | 20.82 | 365.67 | 20.75 |
March | 710.83 | 21.49 | 100.83 | 21.41 | 96.67 | 21.34 |
April | 606.33 | 21.57 | 71.33 | 21.72 | 38.50 | 21.70 |
May | 582.00 | 21.69 | 111.67 | 22.00 | 57.33 | 22.06 |
June | 569.50 | 21.66 | 104.50 | 21.94 | 62.50 | 22.06 |
July | 586.17 | 21.67 | 160.50 | 22.02 | 98.50 | 22.16 |
August | 579.50 | 21.58 | 148.83 | 21.94 | 78.00 | 22.07 |
September | 575.17 | 21.65 | 104.67 | 21.94 | 60.17 | 22.05 |
October | 655.33 | 21.48 | 112.67 | 21.64 | 72.83 | 21.60 |
November | 717.17 | 21.32 | 195.17 | 21.21 | 195.17 | 21.14 |
December | 744.00 | 20.87 | 499.00 | 20.79 | 499.00 | 20.75 |
Annual Sum or Average | 7737.50 | 21.36 | 2576.17 | 21.39 | 2224.33 | 21.33 |
Minimum of Months | 569.50 | 20.68 | 71.33 | 20.64 | 38.50 | 20.62 |
Maximum of Months | 744.00 | 21.69 | 600.00 | 22.02 | 600.00 | 22.16 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 648.00 | 20.51 | 648.00 | 20.50 |
February | 671.33 | 20.78 | 413.17 | 20.67 | 413.17 | 20.62 |
March | 735.67 | 21.31 | 164.67 | 21.18 | 164.67 | 21.09 |
April | 640.33 | 21.59 | 65.00 | 21.65 | 44.83 | 21.62 |
May | 598.50 | 21.72 | 105.00 | 21.99 | 59.83 | 22.05 |
June | 570.17 | 21.67 | 99.17 | 21.95 | 61.67 | 22.07 |
July | 587.00 | 21.68 | 152.17 | 22.01 | 98.17 | 22.16 |
August | 587.17 | 21.59 | 128.33 | 21.90 | 79.33 | 22.03 |
September | 610.83 | 21.71 | 77.00 | 21.89 | 61.67 | 21.99 |
October | 709.83 | 21.39 | 98.50 | 21.35 | 94.33 | 21.31 |
November | 720.00 | 21.00 | 310.83 | 20.90 | 310.83 | 20.85 |
December | 744.00 | 20.62 | 599.33 | 20.57 | 599.33 | 20.55 |
Annual Sum or Average | 7918.83 | 21.26 | 2861.17 | 21.23 | 2635.83 | 21.17 |
Minimum of Months | 570.17 | 20.53 | 65.00 | 20.51 | 44.83 | 20.50 |
Maximum of Months | 744.00 | 21.72 | 648.00 | 22.01 | 648.00 | 22.16 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.14 | 345.67 | 21.02 | 345.67 | 20.95 |
February | 664.67 | 21.31 | 213.17 | 21.17 | 213.17 | 21.08 |
March | 711.17 | 21.67 | 29.50 | 21.64 | 28.00 | 21.60 |
April | 647.83 | 21.74 | 16.83 | 21.74 | 15.17 | 21.74 |
May | 641.83 | 21.83 | 46.50 | 21.93 | 38.50 | 21.99 |
June | 614.50 | 21.76 | 65.50 | 21.91 | 63.67 | 22.02 |
July | 617.00 | 21.73 | 98.33 | 21.94 | 97.50 | 22.10 |
August | 603.67 | 21.64 | 76.17 | 21.84 | 75.67 | 21.99 |
September | 583.33 | 21.74 | 71.00 | 21.94 | 55.67 | 22.06 |
October | 613.33 | 21.57 | 85.67 | 21.74 | 49.17 | 21.75 |
November | 691.17 | 21.62 | 48.00 | 21.58 | 48.00 | 21.55 |
December | 737.00 | 21.31 | 184.83 | 21.20 | 184.83 | 21.13 |
Annual Sum or Average | 7869.50 | 21.58 | 1281.17 | 21.59 | 1215.00 | 21.58 |
Minimum of Months | 583.33 | 21.14 | 16.83 | 21.02 | 15.17 | 20.95 |
Maximum of Months | 744.00 | 21.83 | 345.67 | 21.94 | 345.67 | 22.10 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 713.83 | 22.06 | 22.17 | 22.11 | 8.83 | 22.13 |
February | 585.00 | 22.20 | 40.33 | 22.30 | 6.50 | 22.31 |
March | 523.00 | 22.45 | 122.33 | 22.72 | 26.33 | 22.76 |
April | 327.33 | 22.60 | 288.17 | 23.18 | 43.33 | 23.23 |
May | 223.50 | 23.12 | 495.00 | 23.58 | 105.00 | 23.62 |
June | 99.33 | 23.69 | 616.50 | 23.76 | 78.83 | 23.79 |
July | 70.33 | 23.80 | 695.17 | 23.78 | 62.50 | 23.79 |
August | 67.33 | 23.91 | 690.17 | 23.79 | 63.50 | 23.80 |
September | 206.83 | 23.22 | 516.50 | 23.63 | 114.83 | 23.67 |
October | 430.83 | 22.46 | 240.67 | 22.94 | 49.67 | 23.01 |
November | 585.33 | 22.37 | 83.00 | 22.54 | 28.83 | 22.59 |
December | 690.00 | 22.23 | 32.67 | 22.30 | 12.83 | 22.32 |
Annual Sum or Average | 4522.67 | 22.47 | 3842.67 | 23.07 | 601.00 | 23.13 |
Minimum of Months | 67.33 | 22.06 | 22.17 | 22.11 | 6.50 | 22.13 |
Maximum of Months | 713.83 | 23.91 | 695.17 | 23.79 | 114.83 | 23.80 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 670.83 | 22.16 | 33.83 | 22.24 | 6.17 | 22.25 |
February | 495.83 | 22.23 | 73.00 | 22.43 | 5.50 | 22.44 |
March | 404.33 | 22.53 | 192.83 | 22.94 | 21.00 | 22.98 |
April | 207.17 | 22.72 | 399.17 | 23.43 | 31.83 | 23.46 |
May | 101.83 | 23.37 | 600.50 | 23.70 | 60.83 | 23.72 |
June | 14.33 | 23.36 | 684.50 | 23.76 | 7.50 | 23.77 |
July | 11.33 | 23.67 | 730.33 | 23.79 | 9.00 | 23.80 |
August | 3.17 | 23.99 | 738.33 | 23.78 | 3.17 | 23.78 |
September | 85.33 | 23.48 | 616.17 | 23.71 | 58.33 | 23.73 |
October | 268.17 | 22.53 | 346.50 | 23.24 | 40.67 | 23.28 |
November | 468.00 | 22.45 | 132.17 | 22.74 | 21.33 | 22.78 |
December | 601.00 | 22.31 | 50.33 | 22.42 | 5.83 | 22.44 |
Annual Sum or Average | 3331.33 | 22.43 | 4597.67 | 23.21 | 271.17 | 23.24 |
Minimum of Months | 3.17 | 22.16 | 33.83 | 22.24 | 3.17 | 22.25 |
Maximum of Months | 670.83 | 23.99 | 738.33 | 23.79 | 60.83 | 23.80 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 611.50 | 23.29 | 557.50 | 23.61 | 450.17 | 23.74 |
February | 556.83 | 23.38 | 516.17 | 23.65 | 428.00 | 23.76 |
March | 608.50 | 23.55 | 609.50 | 23.68 | 509.83 | 23.77 |
April | 553.33 | 23.79 | 623.00 | 23.77 | 510.00 | 23.84 |
May | 554.33 | 23.94 | 709.17 | 23.76 | 544.67 | 23.82 |
June | 539.17 | 23.97 | 704.83 | 23.77 | 536.00 | 23.84 |
July | 560.50 | 23.98 | 743.00 | 23.77 | 560.50 | 23.83 |
August | 562.67 | 23.98 | 744.00 | 23.78 | 562.67 | 23.84 |
September | 532.33 | 23.98 | 705.00 | 23.76 | 531.17 | 23.82 |
October | 581.50 | 23.73 | 643.67 | 23.73 | 526.50 | 23.81 |
November | 599.00 | 23.50 | 575.83 | 23.68 | 488.83 | 23.77 |
December | 625.83 | 23.37 | 572.67 | 23.64 | 480.17 | 23.75 |
Annual Sum or Average | 6885.50 | 23.69 | 7704.33 | 23.72 | 6128.50 | 23.80 |
Minimum of Months | 532.33 | 23.29 | 516.17 | 23.61 | 428.00 | 23.74 |
Maximum of Months | 625.83 | 23.98 | 744.00 | 23.78 | 562.67 | 23.84 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 366.67 | 21.00 | 366.67 | 21.00 |
February | 672.00 | 21.02 | 200.33 | 21.02 | 200.33 | 21.01 |
March | 744.00 | 21.12 | 23.67 | 21.11 | 23.67 | 21.11 |
April | 720.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
May | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
June | 642.00 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
July | 489.50 | 22.62 | 72.83 | 22.78 | 0.00 | 22.78 |
August | 454.67 | 22.76 | 55.67 | 22.88 | 0.00 | 22.88 |
September | 709.50 | 22.06 | 0.00 | 22.06 | 0.00 | 22.06 |
October | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
November | 720.00 | 21.03 | 26.17 | 21.03 | 26.17 | 21.03 |
December | 744.00 | 21.00 | 146.83 | 21.00 | 146.83 | 21.00 |
Annual Sum or Average | 8127.67 | 21.57 | 892.17 | 21.55 | 763.67 | 21.51 |
Minimum of Months | 454.67 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.76 | 366.67 | 22.88 | 366.67 | 22.88 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41654 | 29.11138 | -0.3539 | 7.80200 |
February | 672.00000 | 21.20412 | 32.13723 | -0.3966 | 8.48883 |
March | 744.00000 | 21.09171 | 38.75442 | -0.3951 | 8.43905 |
April | 720.00000 | 21.00491 | 48.50612 | -0.3711 | 8.01845 |
May | 744.00000 | 21.08978 | 56.03190 | -1.4889 | 50.31806 |
June | 720.00000 | 21.34656 | 56.14259 | -1.3730 | 44.16853 |
July | 744.00000 | 21.77761 | 57.06905 | -1.2068 | 35.73593 |
August | 744.00000 | 22.31674 | 55.39813 | -1.0207 | 27.20863 |
September | 720.00000 | 22.79351 | 53.55140 | -0.8581 | 20.78643 |
October | 744.00000 | 22.89527 | 46.27433 | 0.13645 | 5.52716 |
November | 720.00000 | 22.92431 | 35.55025 | 0.07304 | 5.31444 |
December | 744.00000 | 22.41321 | 31.68100 | -0.0837 | 5.35737 |
Annual Sum or Average | 8760.00000 | 21.85978 | 45.08570 | -0.6131 | 19.00920 |
Minimum of Months | 672.00000 | 21.00491 | 29.11138 | -1.4889 | 5.31444 |
Maximum of Months | 744.00000 | 22.92431 | 57.06905 | 0.13645 | 50.31806 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05557 | 28.72673 | -0.5094 | 10.95876 |
February | 672.00000 | 21.13849 | 31.41505 | -0.4346 | 9.78854 |
March | 744.00000 | 21.27129 | 37.66772 | -0.2905 | 7.66154 |
April | 720.00000 | 21.38474 | 47.02701 | -0.1840 | 6.67858 |
May | 744.00000 | 21.51035 | 54.69791 | -1.1846 | 35.38301 |
June | 720.00000 | 22.08563 | 54.36498 | -0.9491 | 25.45444 |
July | 744.00000 | 22.42283 | 56.26009 | -0.8080 | 20.60411 |
August | 744.00000 | 22.76605 | 55.40965 | -0.6795 | 16.33233 |
September | 720.00000 | 21.98989 | 56.46497 | -0.9804 | 27.64001 |
October | 744.00000 | 21.56941 | 49.32921 | -0.1231 | 6.68184 |
November | 720.00000 | 21.26844 | 38.08438 | -0.3034 | 7.90272 |
December | 744.00000 | 21.14742 | 32.89696 | -0.4209 | 9.39888 |
Annual Sum or Average | 8760.00000 | 21.63772 | 45.26712 | -0.5731 | 15.40270 |
Minimum of Months | 672.00000 | 21.05557 | 28.72673 | -1.1846 | 6.67858 |
Maximum of Months | 744.00000 | 22.76605 | 56.46497 | -0.1231 | 35.38301 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.10591 | 30.25843 | -0.4240 | 8.96524 |
February | 672.00000 | 21.19188 | 32.91391 | -0.3729 | 8.25684 |
March | 744.00000 | 21.43621 | 38.90221 | -0.2514 | 6.83963 |
April | 720.00000 | 21.68927 | 47.72756 | -0.1286 | 5.93442 |
May | 744.00000 | 21.94334 | 54.71601 | -1.0981 | 31.12949 |
June | 720.00000 | 22.49056 | 54.26099 | -0.8988 | 22.90710 |
July | 744.00000 | 22.70984 | 56.11687 | -0.8053 | 19.60431 |
August | 744.00000 | 22.89690 | 55.66713 | -0.7384 | 17.15825 |
September | 720.00000 | 22.31593 | 56.47542 | -0.9474 | 24.81954 |
October | 744.00000 | 21.69603 | 50.37595 | -0.1092 | 5.73258 |
November | 720.00000 | 21.34857 | 39.37350 | -0.2730 | 6.92221 |
December | 744.00000 | 21.17368 | 34.40978 | -0.3653 | 8.07434 |
Annual Sum or Average | 8760.00000 | 21.83704 | 46.00151 | -0.5354 | 13.89400 |
Minimum of Months | 672.00000 | 21.10591 | 30.25843 | -1.0981 | 5.73258 |
Maximum of Months | 744.00000 | 22.89690 | 56.47542 | -0.1092 | 31.12949 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.90440 | 25.13598 | 0.32109 | 10.83169 |
February | 672.00000 | 21.91318 | 27.69188 | 0.36235 | 11.47891 |
March | 744.00000 | 21.93008 | 33.86812 | 0.44278 | 12.83252 |
April | 720.00000 | 21.96618 | 42.95198 | 0.52702 | 14.45338 |
May | 744.00000 | 21.98055 | 50.30623 | -0.2112 | 13.11715 |
June | 720.00000 | 22.03104 | 51.05507 | -0.1543 | 12.79673 |
July | 744.00000 | 22.04968 | 53.28349 | -0.1245 | 12.38104 |
August | 744.00000 | 22.06384 | 53.24648 | -0.1123 | 12.47106 |
September | 720.00000 | 21.99825 | 52.90254 | -0.1800 | 12.75589 |
October | 744.00000 | 21.92641 | 45.53884 | 0.52691 | 14.30812 |
November | 720.00000 | 21.93083 | 34.17214 | 0.43164 | 12.49563 |
December | 744.00000 | 21.93094 | 29.11257 | 0.37167 | 11.52329 |
Annual Sum or Average | 8760.00000 | 21.96910 | 41.67964 | 0.18225 | 12.62430 |
Minimum of Months | 672.00000 | 21.90440 | 25.13598 | -0.2112 | 10.83169 |
Maximum of Months | 744.00000 | 22.06384 | 53.28349 | 0.52702 | 14.45338 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25393 | 34.41212 | -0.3565 | 8.29512 |
February | 672.00000 | 21.46269 | 36.87252 | -0.2588 | 7.39014 |
March | 744.00000 | 21.84205 | 42.59941 | -0.0753 | 6.15630 |
April | 720.00000 | 21.98982 | 51.48492 | 0.03055 | 6.05836 |
May | 744.00000 | 22.20086 | 58.48433 | -0.8807 | 22.59974 |
June | 720.00000 | 22.66220 | 58.36765 | -0.6849 | 16.23788 |
July | 744.00000 | 22.88056 | 60.22527 | -0.5800 | 13.40080 |
August | 744.00000 | 23.14513 | 59.56986 | -0.4735 | 10.79186 |
September | 720.00000 | 22.65025 | 60.06566 | -0.6821 | 16.67759 |
October | 744.00000 | 22.19807 | 53.58008 | 0.10315 | 6.46621 |
November | 720.00000 | 21.76989 | 43.00104 | -0.0969 | 6.22111 |
December | 744.00000 | 21.45096 | 38.35190 | -0.2474 | 7.09836 |
Annual Sum or Average | 8760.00000 | 22.12942 | 49.81896 | -0.3509 | 10.63516 |
Minimum of Months | 672.00000 | 21.25393 | 34.41212 | -0.8807 | 6.05836 |
Maximum of Months | 744.00000 | 23.14513 | 60.22527 | 0.10315 | 22.59974 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30828 | 33.39297 | -0.3439 | 7.83680 |
February | 672.00000 | 21.48352 | 35.88224 | -0.2731 | 7.13152 |
March | 744.00000 | 21.78925 | 41.75667 | -0.1379 | 6.08350 |
April | 720.00000 | 22.00758 | 50.45793 | -0.0233 | 5.72138 |
May | 744.00000 | 22.25611 | 57.31906 | -0.9567 | 25.29503 |
June | 720.00000 | 22.73570 | 57.09921 | -0.7729 | 18.64434 |
July | 744.00000 | 22.92262 | 58.97177 | -0.6872 | 15.90839 |
August | 744.00000 | 23.08597 | 58.60079 | -0.6261 | 14.01600 |
September | 720.00000 | 22.64022 | 59.01378 | -0.7959 | 19.33135 |
October | 744.00000 | 22.09846 | 52.82875 | 0.01858 | 5.60263 |
November | 720.00000 | 21.75384 | 42.06836 | -0.1459 | 5.99122 |
December | 744.00000 | 21.47932 | 37.36444 | -0.2605 | 6.88234 |
Annual Sum or Average | 8760.00000 | 22.13370 | 48.79767 | -0.4181 | 11.56355 |
Minimum of Months | 672.00000 | 21.30828 | 33.39297 | -0.9567 | 5.60263 |
Maximum of Months | 744.00000 | 23.08597 | 59.01378 | 0.01858 | 25.29503 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78177 | 34.52415 | -0.6152 | 13.55772 |
February | 672.00000 | 21.04872 | 37.20335 | -0.4979 | 11.49615 |
March | 744.00000 | 21.61283 | 41.69992 | -0.2563 | 7.63796 |
April | 720.00000 | 21.90867 | 50.13881 | -0.0949 | 6.64845 |
May | 744.00000 | 22.10442 | 55.85933 | -1.0471 | 30.10176 |
June | 720.00000 | 22.03498 | 54.80202 | -1.0113 | 28.49982 |
July | 744.00000 | 22.02843 | 57.63319 | -0.9770 | 27.03350 |
August | 744.00000 | 21.97219 | 56.83967 | -0.9875 | 27.41971 |
September | 720.00000 | 22.04282 | 58.08687 | -1.0341 | 29.54115 |
October | 744.00000 | 21.78479 | 53.97457 | -0.1258 | 6.82348 |
November | 720.00000 | 21.37605 | 43.77720 | -0.3346 | 8.35116 |
December | 744.00000 | 20.97568 | 39.08999 | -0.5126 | 11.18873 |
Annual Sum or Average | 8760.00000 | 21.64193 | 48.69613 | -0.6256 | 17.39660 |
Minimum of Months | 672.00000 | 20.78177 | 34.52415 | -1.0471 | 6.64845 |
Maximum of Months | 744.00000 | 22.10442 | 58.08687 | -0.0949 | 30.10176 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.58480 | 34.87183 | -0.6881 | 15.67190 |
February | 672.00000 | 20.83845 | 37.58248 | -0.5710 | 13.01719 |
March | 744.00000 | 21.35927 | 42.41377 | -0.3332 | 8.35680 |
April | 720.00000 | 21.79698 | 50.56114 | -0.1315 | 6.70125 |
May | 744.00000 | 22.07160 | 56.14269 | -1.0631 | 30.66129 |
June | 720.00000 | 22.04203 | 54.82897 | -1.0102 | 28.46226 |
July | 744.00000 | 22.03312 | 57.73435 | -0.9779 | 27.07074 |
August | 744.00000 | 21.96339 | 57.31004 | -0.9998 | 27.85634 |
September | 720.00000 | 21.97763 | 59.00076 | -1.0713 | 30.89035 |
October | 744.00000 | 21.51685 | 55.23300 | -0.2063 | 7.01430 |
November | 720.00000 | 21.07065 | 44.57328 | -0.4322 | 9.70185 |
December | 744.00000 | 20.70860 | 39.64551 | -0.6011 | 13.25095 |
Annual Sum or Average | 8760.00000 | 21.49990 | 49.21951 | -0.6748 | 18.25618 |
Minimum of Months | 672.00000 | 20.58480 | 34.87183 | -1.0713 | 6.70125 |
Maximum of Months | 744.00000 | 22.07160 | 59.00076 | -0.1315 | 30.89035 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78466 | 33.29391 | -0.5884 | 12.81506 |
February | 672.00000 | 20.94847 | 35.80918 | -0.5107 | 11.12836 |
March | 744.00000 | 21.24138 | 40.91104 | -0.3673 | 8.26838 |
April | 720.00000 | 21.57714 | 48.89930 | -0.2158 | 6.62959 |
May | 744.00000 | 21.83740 | 55.19423 | -1.2037 | 36.21719 |
June | 720.00000 | 21.88856 | 54.93470 | -1.1569 | 34.24317 |
July | 744.00000 | 21.91250 | 57.77161 | -1.1240 | 32.81516 |
August | 744.00000 | 21.82280 | 57.61876 | -1.1579 | 34.21108 |
September | 720.00000 | 21.79328 | 57.70087 | -1.2027 | 36.16218 |
October | 744.00000 | 21.39275 | 53.21991 | -0.2484 | 6.73824 |
November | 720.00000 | 21.11508 | 42.45002 | -0.4069 | 8.92931 |
December | 744.00000 | 20.91564 | 37.86336 | -0.5129 | 10.94058 |
Annual Sum or Average | 8760.00000 | 21.43808 | 48.03907 | -0.7262 | 19.97999 |
Minimum of Months | 672.00000 | 20.78466 | 33.29391 | -1.2037 | 6.62959 |
Maximum of Months | 744.00000 | 21.91250 | 57.77161 | -0.2158 | 36.21719 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80503 | 34.46893 | -0.6103 | 13.41189 |
February | 672.00000 | 21.07527 | 37.14914 | -0.4884 | 11.21526 |
March | 744.00000 | 21.59240 | 41.69272 | -0.2638 | 7.48284 |
April | 720.00000 | 21.92201 | 49.89245 | -0.0930 | 6.44228 |
May | 744.00000 | 22.16642 | 55.26205 | -1.0240 | 29.26234 |
June | 720.00000 | 22.13906 | 54.28503 | -0.9746 | 27.60535 |
July | 744.00000 | 22.12525 | 56.92000 | -0.9418 | 26.43564 |
August | 744.00000 | 22.02619 | 56.51788 | -0.9695 | 27.15094 |
September | 720.00000 | 22.09289 | 57.66952 | -1.0182 | 29.14605 |
October | 744.00000 | 21.76023 | 53.73018 | -0.1320 | 6.62718 |
November | 720.00000 | 21.36199 | 43.77108 | -0.3383 | 8.23382 |
December | 744.00000 | 20.98911 | 39.03341 | -0.5082 | 11.00553 |
Annual Sum or Average | 8760.00000 | 21.67394 | 48.42493 | -0.6146 | 17.03978 |
Minimum of Months | 672.00000 | 20.80503 | 34.46893 | -1.0240 | 6.44228 |
Maximum of Months | 744.00000 | 22.16642 | 57.66952 | -0.0930 | 29.26234 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59603 | 34.82813 | -0.6858 | 15.60443 |
February | 672.00000 | 20.84978 | 37.54295 | -0.5639 | 12.74065 |
March | 744.00000 | 21.32907 | 42.43748 | -0.3425 | 8.21437 |
April | 720.00000 | 21.83673 | 50.21928 | -0.1247 | 6.48356 |
May | 744.00000 | 22.14838 | 55.53053 | -1.0358 | 29.69922 |
June | 720.00000 | 22.14622 | 54.35520 | -0.9733 | 27.58768 |
July | 744.00000 | 22.12895 | 57.02399 | -0.9429 | 26.50552 |
August | 744.00000 | 22.01897 | 56.97972 | -0.9812 | 27.55455 |
September | 720.00000 | 22.04882 | 58.37432 | -1.0500 | 30.25938 |
October | 744.00000 | 21.51576 | 54.88796 | -0.2080 | 6.87409 |
November | 720.00000 | 21.02098 | 44.65577 | -0.4426 | 9.72428 |
December | 744.00000 | 20.71229 | 39.60367 | -0.5988 | 13.14987 |
Annual Sum or Average | 8760.00000 | 21.53235 | 48.92979 | -0.6634 | 17.90150 |
Minimum of Months | 672.00000 | 20.59603 | 34.82813 | -1.0500 | 6.48356 |
Maximum of Months | 744.00000 | 22.14838 | 58.37432 | -0.1247 | 30.25938 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67867 | 35.00711 | -0.6773 | 15.35584 |
February | 672.00000 | 20.98197 | 37.75157 | -0.5415 | 12.80368 |
March | 744.00000 | 21.60209 | 42.03502 | -0.2679 | 8.15944 |
April | 720.00000 | 21.94885 | 50.43501 | -0.0823 | 7.06858 |
May | 744.00000 | 22.14686 | 56.04604 | -1.0151 | 29.34516 |
June | 720.00000 | 22.03236 | 55.05322 | -0.9916 | 27.95645 |
July | 744.00000 | 22.01933 | 57.98521 | -0.9580 | 26.47338 |
August | 744.00000 | 21.96341 | 57.15876 | -0.9690 | 26.85353 |
September | 720.00000 | 22.03744 | 58.64204 | -1.0239 | 29.45717 |
October | 744.00000 | 21.79542 | 54.57714 | -0.1273 | 7.34726 |
November | 720.00000 | 21.33050 | 44.35034 | -0.3636 | 9.07684 |
December | 744.00000 | 20.87408 | 39.67435 | -0.5673 | 12.59187 |
Annual Sum or Average | 8760.00000 | 21.62040 | 49.11905 | -0.6330 | 17.74026 |
Minimum of Months | 672.00000 | 20.67867 | 35.00711 | -1.0239 | 7.06858 |
Maximum of Months | 744.00000 | 22.14686 | 58.64204 | -0.0823 | 29.45717 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52856 | 35.31715 | -0.7424 | 17.37329 |
February | 672.00000 | 20.78844 | 38.11983 | -0.6135 | 14.28840 |
March | 744.00000 | 21.33330 | 42.79411 | -0.3510 | 8.93325 |
April | 720.00000 | 21.84757 | 50.90398 | -0.1176 | 7.09462 |
May | 744.00000 | 22.12131 | 56.35240 | -1.0293 | 29.80294 |
June | 720.00000 | 22.04012 | 55.08897 | -0.9902 | 27.90135 |
July | 744.00000 | 22.02404 | 58.07236 | -0.9588 | 26.50102 |
August | 744.00000 | 21.95472 | 57.59311 | -0.9817 | 27.28130 |
September | 720.00000 | 21.97660 | 59.61450 | -1.0608 | 30.75517 |
October | 744.00000 | 21.50781 | 55.92115 | -0.2150 | 7.49010 |
November | 720.00000 | 21.00127 | 45.20118 | -0.4696 | 10.62674 |
December | 744.00000 | 20.61805 | 40.23768 | -0.6555 | 14.82142 |
Annual Sum or Average | 8760.00000 | 21.48154 | 49.66176 | -0.6829 | 18.60196 |
Minimum of Months | 672.00000 | 20.52856 | 35.31715 | -1.0608 | 7.09462 |
Maximum of Months | 744.00000 | 22.12131 | 59.61450 | -0.1176 | 30.75517 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.14174 | 35.58332 | -0.4915 | 11.20363 |
February | 672.00000 | 21.33833 | 37.95483 | -0.3973 | 9.80404 |
March | 744.00000 | 21.76083 | 41.75844 | -0.2070 | 7.30885 |
April | 720.00000 | 21.92208 | 49.96336 | -0.0994 | 6.63709 |
May | 744.00000 | 22.05613 | 55.89465 | -1.0845 | 31.57925 |
June | 720.00000 | 21.99077 | 55.48367 | -1.0624 | 30.60225 |
July | 744.00000 | 22.00656 | 58.10940 | -1.0202 | 28.85045 |
August | 744.00000 | 21.96453 | 57.02766 | -1.0194 | 28.83224 |
September | 720.00000 | 22.07469 | 57.23290 | -1.0325 | 29.66839 |
October | 744.00000 | 21.96377 | 52.70284 | -0.0662 | 6.87130 |
November | 720.00000 | 21.68738 | 43.37321 | -0.2241 | 7.49659 |
December | 744.00000 | 21.32827 | 39.60862 | -0.3864 | 9.34566 |
Annual Sum or Average | 8760.00000 | 21.77150 | 48.78236 | -0.5923 | 17.39829 |
Minimum of Months | 672.00000 | 21.14174 | 35.58332 | -1.0845 | 6.63709 |
Maximum of Months | 744.00000 | 22.07469 | 58.10940 | -0.0662 | 31.57925 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.12882 | 34.40918 | -0.1143 | 6.45748 |
February | 672.00000 | 22.39903 | 36.53166 | -0.0127 | 6.49618 |
March | 744.00000 | 22.82245 | 41.90720 | 0.16253 | 6.72460 |
April | 720.00000 | 23.15892 | 49.64443 | 0.31926 | 8.05279 |
May | 744.00000 | 23.42764 | 55.65270 | -0.4515 | 10.19567 |
June | 720.00000 | 23.64658 | 55.51233 | -0.3361 | 7.90680 |
July | 744.00000 | 23.70244 | 57.34101 | -0.2907 | 7.19196 |
August | 744.00000 | 23.70302 | 57.32226 | -0.2890 | 7.14204 |
September | 720.00000 | 23.44527 | 58.01256 | -0.4256 | 9.64753 |
October | 744.00000 | 22.94790 | 52.55043 | 0.27344 | 7.50037 |
November | 720.00000 | 22.62036 | 42.44179 | 0.10074 | 6.39930 |
December | 744.00000 | 22.34411 | 38.05536 | -0.0202 | 6.21148 |
Annual Sum or Average | 8760.00000 | 23.03199 | 48.34412 | -0.0910 | 7.49649 |
Minimum of Months | 672.00000 | 22.12882 | 34.40918 | -0.4515 | 6.21148 |
Maximum of Months | 744.00000 | 23.70302 | 58.01256 | 0.31926 | 10.19567 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.31238 | 33.69957 | -0.0367 | 6.29265 |
February | 672.00000 | 22.60722 | 35.72628 | 0.07081 | 6.64865 |
March | 744.00000 | 23.05613 | 40.93983 | 0.25166 | 7.36542 |
April | 720.00000 | 23.35829 | 48.60621 | 0.39993 | 9.10887 |
May | 744.00000 | 23.57621 | 54.62357 | -0.3547 | 8.31633 |
June | 720.00000 | 23.73511 | 54.69389 | -0.2643 | 6.84984 |
July | 744.00000 | 23.77570 | 56.58119 | -0.2264 | 6.37173 |
August | 744.00000 | 23.76944 | 56.58681 | -0.2279 | 6.37218 |
September | 720.00000 | 23.57853 | 57.02534 | -0.3362 | 7.99177 |
October | 744.00000 | 23.17014 | 51.44890 | 0.35924 | 8.50141 |
November | 720.00000 | 22.86455 | 41.48736 | 0.19216 | 6.88912 |
December | 744.00000 | 22.57214 | 37.22812 | 0.06739 | 6.30062 |
Annual Sum or Average | 8760.00000 | 23.20080 | 47.44950 | -0.0095 | 7.25063 |
Minimum of Months | 672.00000 | 22.31238 | 33.69957 | -0.3547 | 6.29265 |
Maximum of Months | 744.00000 | 23.77570 | 57.02534 | 0.39993 | 9.10887 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.29674 | 33.13722 | 0.80059 | 23.76357 |
February | 672.00000 | 23.33827 | 34.96088 | 0.86017 | 25.62889 |
March | 744.00000 | 23.38801 | 39.79342 | 0.96623 | 29.15116 |
April | 720.00000 | 23.45126 | 47.42946 | 1.07041 | 33.17661 |
May | 744.00000 | 23.51420 | 53.53193 | 0.56886 | 19.89305 |
June | 720.00000 | 23.58441 | 53.93950 | 0.64470 | 20.99575 |
July | 744.00000 | 23.60861 | 55.86572 | 0.68194 | 21.61951 |
August | 744.00000 | 23.62549 | 55.80123 | 0.68810 | 21.50663 |
September | 720.00000 | 23.54441 | 55.79386 | 0.59439 | 19.73257 |
October | 744.00000 | 23.42684 | 49.87999 | 1.05806 | 32.45231 |
November | 720.00000 | 23.36290 | 40.36998 | 0.93628 | 28.08074 |
December | 744.00000 | 23.32880 | 36.41560 | 0.85947 | 25.47282 |
Annual Sum or Average | 8760.00000 | 23.45647 | 46.47142 | 0.81035 | 25.11455 |
Minimum of Months | 672.00000 | 23.29674 | 33.13722 | 0.56886 | 19.73257 |
Maximum of Months | 744.00000 | 23.62549 | 55.86572 | 1.07041 | 33.17661 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99706 | 27.26015 | -0.5379 | 11.21105 |
February | 672.00000 | 20.99509 | 30.15473 | -0.5016 | 10.48811 |
March | 744.00000 | 21.02271 | 36.71939 | -0.4224 | 8.94851 |
April | 720.00000 | 21.10233 | 46.26117 | -0.3305 | 7.51975 |
May | 744.00000 | 21.38624 | 53.73677 | -1.3540 | 43.22723 |
June | 720.00000 | 22.17787 | 52.84139 | -1.0773 | 29.84622 |
July | 744.00000 | 22.50820 | 54.86926 | -0.9480 | 24.35903 |
August | 744.00000 | 22.62163 | 54.79909 | -0.9079 | 22.55914 |
September | 720.00000 | 21.82352 | 55.71310 | -1.1832 | 34.71246 |
October | 744.00000 | 21.10502 | 49.23042 | -0.3112 | 7.18294 |
November | 720.00000 | 21.00619 | 37.08920 | -0.4276 | 8.99357 |
December | 744.00000 | 21.00117 | 31.63305 | -0.4869 | 10.12946 |
Annual Sum or Average | 8760.00000 | 21.48236 | 44.26622 | -0.7086 | 18.30675 |
Minimum of Months | 672.00000 | 20.99509 | 27.26015 | -1.3540 | 7.18294 |
Maximum of Months | 744.00000 | 22.62163 | 55.71310 | -0.3112 | 43.22723 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00210 | 30.82197 | -0.5008 | 10.35443 |
February | 672.00000 | 21.02695 | 33.62311 | -0.4664 | 9.71574 |
March | 744.00000 | 21.12701 | 39.92718 | -0.3833 | 8.31950 |
April | 720.00000 | 21.42957 | 48.69041 | -0.2510 | 6.70670 |
May | 744.00000 | 21.80290 | 55.56011 | -1.2368 | 37.24016 |
June | 720.00000 | 22.42456 | 54.96560 | -1.0213 | 27.24867 |
July | 744.00000 | 22.67989 | 56.79337 | -0.9196 | 23.05620 |
August | 744.00000 | 22.72040 | 56.81978 | -0.9053 | 22.39876 |
September | 720.00000 | 22.15024 | 57.48466 | -1.1009 | 30.78441 |
October | 744.00000 | 21.32565 | 51.83038 | -0.2605 | 6.61279 |
November | 720.00000 | 21.03654 | 40.40971 | -0.4091 | 8.64827 |
December | 744.00000 | 21.00717 | 35.14857 | -0.4626 | 9.61130 |
Annual Sum or Average | 8760.00000 | 21.64822 | 46.90932 | -0.6610 | 16.76457 |
Minimum of Months | 672.00000 | 21.00210 | 30.82197 | -1.2368 | 6.61279 |
Maximum of Months | 744.00000 | 22.72040 | 57.48466 | -0.2510 | 37.24016 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99975 | 28.60513 | -0.5172 | 10.75872 |
February | 672.00000 | 21.02375 | 31.38727 | -0.4698 | 9.87302 |
March | 744.00000 | 21.11727 | 37.67769 | -0.3675 | 8.16302 |
April | 720.00000 | 21.42241 | 46.47365 | -0.2238 | 6.61531 |
May | 744.00000 | 21.86999 | 53.00844 | -1.1538 | 33.59873 |
June | 720.00000 | 22.64281 | 51.86009 | -0.8811 | 22.09915 |
July | 744.00000 | 22.94676 | 53.51417 | -0.7606 | 18.01516 |
August | 744.00000 | 23.04724 | 53.31893 | -0.7259 | 16.54650 |
September | 720.00000 | 22.07583 | 55.32990 | -1.0648 | 29.55648 |
October | 744.00000 | 21.26808 | 49.65757 | -0.2505 | 6.61185 |
November | 720.00000 | 21.03230 | 38.19295 | -0.3999 | 8.55038 |
December | 744.00000 | 21.00365 | 32.90127 | -0.4677 | 9.75009 |
Annual Sum or Average | 8760.00000 | 21.70877 | 44.39375 | -0.6076 | 15.03521 |
Minimum of Months | 672.00000 | 20.99975 | 28.60513 | -1.1538 | 6.61185 |
Maximum of Months | 744.00000 | 23.04724 | 55.32990 | -0.2238 | 33.59873 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00354 | 27.02689 | -0.5264 | 10.94689 |
February | 672.00000 | 21.01530 | 29.91639 | -0.4896 | 10.23228 |
March | 744.00000 | 21.08112 | 36.37960 | -0.4065 | 8.71889 |
April | 720.00000 | 21.25484 | 45.64617 | -0.2973 | 7.17524 |
May | 744.00000 | 21.63692 | 52.85788 | -1.2815 | 39.58766 |
June | 720.00000 | 22.47458 | 51.93338 | -0.9919 | 26.22848 |
July | 744.00000 | 22.81237 | 53.99341 | -0.8597 | 21.04467 |
August | 744.00000 | 22.92844 | 53.95542 | -0.8187 | 19.35964 |
September | 720.00000 | 22.14585 | 54.66278 | -1.0887 | 30.36484 |
October | 744.00000 | 21.25324 | 48.68261 | -0.2775 | 6.84140 |
November | 720.00000 | 21.05008 | 36.79708 | -0.4130 | 8.76350 |
December | 744.00000 | 21.00950 | 31.40313 | -0.4769 | 9.93141 |
Annual Sum or Average | 8760.00000 | 21.64293 | 43.67701 | -0.6616 | 16.63510 |
Minimum of Months | 672.00000 | 21.00354 | 27.02689 | -1.2815 | 6.84140 |
Maximum of Months | 744.00000 | 22.92844 | 54.66278 | -0.2775 | 39.58766 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.919896E+10 | 82995.59 | 19-JAN-22:53 | 288.35 | 0.272682E+11 | 0.00 | 0.364672E+11 | 1.19 | 3.56 | 19-JAN-22:53 | 0.00 | 0.00 |
February | 0.268788E+11 | 103166.52 | 28-FEB-16:01 | 380.63 | 0.774662E+11 | 0.00 | 0.104345E+12 | 1.71 | 3.46 | 28-FEB-16:01 | 0.00 | 0.00 |
March | 0.653600E+11 | 124636.01 | 30-MAR-18:03 | 617.57 | 0.190961E+12 | 0.00 | 0.256321E+12 | 2.49 | 3.87 | 31-MAR-08:52 | 0.00 | 0.00 |
April | 0.119573E+12 | 127574.96 | 04-APR-15:02 | 688.57 | 0.356951E+12 | 0.00 | 0.476524E+12 | 2.87 | 4.10 | 22-APR-21:53 | 0.00 | 0.00 |
May | 0.205079E+12 | 162791.54 | 30-MAY-18:03 | 742.25 | 0.651949E+12 | 0.00 | 0.857028E+12 | 3.13 | 4.24 | 26-MAY-21:53 | 0.00 | 0.00 |
June | 0.281417E+12 | 187303.18 | 28-JUN-18:03 | 720.00 | 0.930223E+12 | 0.00 | 0.121164E+13 | 3.27 | 4.25 | 22-JUN-21:52 | 0.00 | 0.00 |
July | 0.344060E+12 | 209567.41 | 08-JUL-15:03 | 744.00 | 0.117088E+13 | 0.00 | 0.151494E+13 | 3.43 | 4.26 | 27-JUL-21:54 | 0.00 | 0.00 |
August | 0.355672E+12 | 205777.89 | 18-AUG-18:03 | 744.00 | 0.121556E+13 | 0.00 | 0.157124E+13 | 3.43 | 4.18 | 07-AUG-21:52 | 0.00 | 0.00 |
September | 0.247944E+12 | 180441.45 | 07-SEP-18:03 | 720.00 | 0.836683E+12 | 0.00 | 0.108463E+13 | 3.31 | 4.20 | 21-SEP-21:53 | 0.00 | 0.00 |
October | 0.114474E+12 | 182741.81 | 18-OCT-21:53 | 686.79 | 0.369842E+12 | 0.00 | 0.484316E+12 | 2.88 | 4.22 | 19-OCT-08:52 | 0.00 | 0.00 |
November | 0.537821E+11 | 121253.29 | 19-NOV-22:52 | 547.18 | 0.161244E+12 | 0.00 | 0.215026E+12 | 2.31 | 4.07 | 27-NOV-22:52 | 0.00 | 0.00 |
December | 0.169718E+11 | 89064.07 | 13-DEC-09:53 | 369.14 | 0.505085E+11 | 0.00 | 0.674803E+11 | 1.52 | 3.74 | 13-DEC-09:53 | 0.00 | 0.00 |
Annual Sum or Average | 0.184041E+13 | 7248.49 | 0.603954E+13 | 0.00 | 0.787995E+13 | 2.63 | 0.00 | 0.00 | ||||
Minimum of Months | 0.919896E+10 | 82995.59 | 288.35 | 0.272682E+11 | 0.00 | 0.364672E+11 | 1.19 | 3.46 | 0.00 | 0.00 | ||
Maximum of Months | 0.355672E+12 | 209567.41 | 744.00 | 0.121556E+13 | 0.00 | 0.157124E+13 | 3.43 | 4.26 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.148597E+12 | 0.00 | 744.00 | 222460.63 | 17-JAN-10:20 | 0.00 | 38.16 | 60.00 | 0.64 | 0.00 | 0.13 | 0.51 | 17-JAN-10:20 |
February | 0.878839E+11 | 0.00 | 662.58 | 189632.31 | 07-FEB-10:50 | 0.00 | 36.56 | 59.53 | 0.43 | 0.00 | 0.08 | 0.44 | 07-FEB-10:50 |
March | 0.422140E+11 | 0.00 | 691.64 | 162608.51 | 22-MAR-10:00 | 0.00 | 35.20 | 58.15 | 0.18 | 0.00 | 0.04 | 0.38 | 22-MAR-10:00 |
April | 0.236756E+11 | 0.00 | 631.31 | 130752.84 | 06-APR-06:47 | 0.00 | 36.04 | 57.33 | 0.10 | 0.00 | 0.02 | 0.30 | 06-APR-06:47 |
May | 0.108045E+11 | 0.00 | 564.19 | 56584.88 | 12-MAY-08:05 | 0.00 | 33.42 | 53.94 | 0.04 | 0.00 | 0.01 | 0.13 | 12-MAY-08:05 |
June | 0.311009E+10 | 0.00 | 376.68 | 39923.00 | 03-JUN-21:56 | 0.00 | 29.56 | 45.44 | 0.01 | 0.00 | 0.00 | 0.09 | 03-JUN-21:56 |
July | 0.223172E+10 | 0.00 | 271.49 | 35946.50 | 28-JUL-15:05 | 0.00 | 30.36 | 41.36 | 0.01 | 0.00 | 0.00 | 0.08 | 28-JUL-15:05 |
August | 0.212051E+10 | 0.00 | 254.89 | 39142.87 | 10-AUG-08:05 | 0.00 | 31.11 | 41.11 | 0.01 | 0.00 | 0.00 | 0.09 | 10-AUG-08:05 |
September | 0.331585E+10 | 0.00 | 419.79 | 64433.91 | 30-SEP-15:07 | 0.00 | 30.66 | 47.82 | 0.01 | 0.00 | 0.00 | 0.15 | 30-SEP-15:07 |
October | 0.209965E+11 | 0.00 | 615.33 | 136008.83 | 26-OCT-06:40 | 0.00 | 31.72 | 54.54 | 0.09 | 0.00 | 0.02 | 0.31 | 26-OCT-06:40 |
November | 0.460939E+11 | 0.00 | 695.24 | 169027.24 | 21-NOV-19:02 | 0.00 | 35.06 | 58.80 | 0.23 | 0.00 | 0.04 | 0.39 | 21-NOV-19:02 |
December | 0.941743E+11 | 0.00 | 739.79 | 183238.80 | 21-DEC-09:02 | 0.00 | 38.11 | 59.81 | 0.44 | 0.00 | 0.08 | 0.42 | 21-DEC-09:02 |
Annual Sum or Average | 0.485218E+12 | 0.00 | 6666.94 | 0.00 | 33.82 | 53.11 | 0.18 | 0.00 | 0.04 | ||||
Minimum of Months | 0.212051E+10 | 0.00 | 254.89 | 35946.50 | 0.00 | 29.56 | 41.11 | 0.01 | 0.00 | 0.00 | 0.08 | ||
Maximum of Months | 0.148597E+12 | 0.00 | 744.00 | 222460.63 | 0.00 | 38.16 | 60.00 | 0.64 | 0.00 | 0.13 | 0.51 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.197625E+11 | 0.00 | 192.27 | 0.146284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195542.66 | 19-JAN-22:00 | 128136.28 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.584604E+11 | 0.00 | 312.82 | 0.503831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179079.09 | 26-FEB-15:10 | 179079.09 | 26-FEB-15:10 | 0.00 | 0.00 | 0.00 |
March | 0.140115E+12 | 0.00 | 469.30 | 0.123514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 246952.17 | 28-MAR-20:20 | 212675.88 | 30-MAR-19:40 | 0.00 | 0.00 | 0.00 |
April | 0.264713E+12 | 0.00 | 619.46 | 0.210896E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 287809.48 | 21-APR-18:10 | 248659.75 | 13-APR-15:25 | 0.00 | 0.00 | 0.00 |
May | 0.490355E+12 | 0.00 | 725.64 | 0.322913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 414946.96 | 30-MAY-21:20 | 260954.47 | 16-MAY-18:43 | 0.00 | 0.00 | 0.00 |
June | 0.689394E+12 | 0.00 | 715.61 | 0.420294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 453253.90 | 26-JUN-21:00 | 263898.70 | 10-JUN-18:06 | 0.00 | 0.00 | 0.00 |
July | 0.879693E+12 | 0.00 | 744.00 | 0.470355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 491471.96 | 26-JUL-23:00 | 258264.02 | 07-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.909664E+12 | 0.00 | 744.00 | 0.490367E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 500119.08 | 23-AUG-22:50 | 257952.44 | 18-AUG-19:10 | 0.00 | 0.00 | 0.00 |
September | 0.632866E+12 | 0.00 | 719.00 | 0.367977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 447191.68 | 27-SEP-18:20 | 229527.63 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.276161E+12 | 0.00 | 571.00 | 0.177661E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 493318.44 | 18-OCT-21:00 | 203656.49 | 11-OCT-16:10 | 0.00 | 0.00 | 0.00 |
November | 0.121535E+12 | 0.00 | 408.05 | 0.898825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 264448.47 | 19-NOV-23:50 | 159942.47 | 05-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.360171E+11 | 0.00 | 234.62 | 0.265886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 218657.34 | 13-DEC-11:40 | 153382.07 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451874E+13 | 0.00 | 6455.77 | 0.276546E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.197625E+11 | 0.00 | 192.27 | 0.146284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179079.09 | 128136.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.909664E+12 | 0.00 | 744.00 | 0.490367E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 500119.08 | 263898.70 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.176252E+10 | 0.00 | 46.33 | 0.137197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23359.34 | 19-JAN-16:00 | 22285.22 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.553714E+10 | 0.00 | 130.69 | 0.548254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27402.34 | 28-FEB-15:00 | 27402.34 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.175170E+11 | 0.00 | 332.33 | 0.157853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42240.28 | 31-MAR-11:00 | 29934.08 | 30-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.355772E+11 | 0.00 | 498.33 | 0.290035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50832.28 | 04-APR-10:30 | 30528.55 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.711301E+11 | 0.00 | 686.67 | 0.482488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66370.94 | 30-MAY-21:40 | 32427.04 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.104696E+12 | 0.00 | 702.83 | 0.653233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74918.98 | 29-JUN-08:00 | 34791.01 | 06-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.131516E+12 | 0.00 | 744.00 | 0.728173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81814.81 | 26-JUL-07:50 | 36307.35 | 08-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.133952E+12 | 0.00 | 744.00 | 0.756290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79625.68 | 24-AUG-07:00 | 35277.90 | 01-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.946430E+11 | 0.00 | 699.00 | 0.569375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75442.06 | 17-SEP-07:50 | 33179.80 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.386077E+11 | 0.00 | 416.33 | 0.249505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79680.67 | 18-OCT-20:20 | 30803.96 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.147638E+11 | 0.00 | 246.17 | 0.110234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46083.92 | 19-NOV-24:00 | 27177.84 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.325294E+10 | 0.00 | 74.17 | 0.253804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35337.19 | 13-DEC-13:00 | 25564.22 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.652956E+12 | 0.00 | 5320.86 | 0.409111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.176252E+10 | 0.00 | 46.33 | 0.137197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23359.34 | 22285.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.133952E+12 | 0.00 | 744.00 | 0.756290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81814.81 | 36307.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 64215622.37 | 0.00 | 21.32 | 61813714.92 | 0.00 | 0.00 | 0.00 | 0.00 | 13779.24 | 29-JAN-16:01 | 13779.24 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.250716E+09 | 0.00 | 74.27 | 0.230472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13805.07 | 28-FEB-16:01 | 13805.07 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.125946E+10 | 0.00 | 222.70 | 0.796075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15216.62 | 30-MAR-08:52 | 13930.84 | 12-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.274297E+10 | 0.00 | 368.56 | 0.156338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16733.26 | 30-APR-21:52 | 14410.85 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.489706E+10 | 0.00 | 470.84 | 0.267656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17144.52 | 26-MAY-21:51 | 14517.00 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.790888E+10 | 0.00 | 553.31 | 0.474655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18971.75 | 26-JUN-21:51 | 13655.81 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.932685E+10 | 0.00 | 576.57 | 0.564649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18897.84 | 25-JUL-21:51 | 13364.63 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.100982E+11 | 0.00 | 613.87 | 0.609427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18711.03 | 20-AUG-21:51 | 13365.03 | 14-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.581424E+10 | 0.00 | 478.56 | 0.318571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18567.71 | 09-SEP-21:51 | 14840.31 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.205536E+10 | 0.00 | 302.40 | 0.100262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18537.44 | 18-OCT-21:51 | 14375.58 | 15-OCT-16:21 | 0.00 | 0.00 | 0.00 |
November | 0.480602E+09 | 0.00 | 145.98 | 0.330406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16412.42 | 05-NOV-21:51 | 13802.64 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.140649E+09 | 0.00 | 41.79 | 0.106924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14407.67 | 12-DEC-22:51 | 13787.84 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450393E+11 | 0.00 | 3870.17 | 0.264413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 64215622.37 | 0.00 | 21.32 | 61813714.92 | 0.00 | 0.00 | 0.00 | 0.00 | 13779.24 | 13364.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100982E+11 | 0.00 | 613.87 | 0.609427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18971.75 | 14840.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4765423.11 | 0.00 | 2.43 | 3314265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 4782.90 | 29-JAN-16:01 | 4782.90 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 72801857.44 | 0.00 | 25.58 | 65118742.16 | 0.00 | 0.00 | 0.00 | 0.00 | 13663.55 | 28-FEB-16:01 | 13663.55 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.796487E+09 | 0.00 | 151.76 | 0.462271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15003.06 | 30-MAR-08:52 | 13657.38 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.223894E+10 | 0.00 | 330.30 | 0.122206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16492.30 | 30-APR-21:52 | 14126.23 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.462547E+10 | 0.00 | 452.29 | 0.250756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16946.00 | 26-MAY-21:51 | 14219.18 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.783787E+10 | 0.00 | 551.73 | 0.473060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18769.18 | 26-JUN-21:51 | 13480.55 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.918587E+10 | 0.00 | 575.87 | 0.556694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18684.86 | 25-JUL-21:51 | 13214.91 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.954976E+10 | 0.00 | 611.66 | 0.566886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18435.18 | 20-AUG-21:51 | 13230.92 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.498832E+10 | 0.00 | 449.29 | 0.261146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18238.49 | 09-SEP-21:51 | 13964.94 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.125540E+10 | 0.00 | 208.60 | 0.566299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18267.29 | 18-OCT-21:51 | 13576.73 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.134108E+09 | 0.00 | 53.91 | 78270230.10 | 0.00 | 0.00 | 0.00 | 0.00 | 15986.71 | 05-NOV-21:51 | 13660.06 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 17422881.44 | 0.00 | 10.01 | 11032430.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12892.81 | 11-DEC-16:01 | 12329.24 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407072E+11 | 0.00 | 3423.41 | 0.234938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4765423.11 | 0.00 | 2.43 | 3314265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 4782.90 | 4782.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.954976E+10 | 0.00 | 611.66 | 0.566886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18769.18 | 14219.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.203439E+09 | 0.00 | 12.50 | 0.202136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12712.09 | 29-JAN-13:30 | 12712.09 | 29-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.282952E+10 | 0.00 | 87.49 | 0.282217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23664.91 | 26-FEB-14:50 | 23664.91 | 26-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.625097E+10 | 0.00 | 193.26 | 0.417849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24237.53 | 30-MAR-13:30 | 21540.32 | 13-MAR-16:20 | 0.00 | 0.00 | 0.00 |
April | 0.872971E+10 | 0.00 | 295.05 | 0.412144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21681.31 | 15-APR-14:00 | 15189.22 | 15-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.125558E+11 | 0.00 | 410.87 | 0.438822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19750.59 | 19-MAY-19:10 | 13031.35 | 09-MAY-20:00 | 0.00 | 0.00 | 0.00 |
June | 0.247158E+11 | 0.00 | 582.00 | 0.990409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26283.86 | 25-JUN-08:00 | 14450.82 | 10-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.316989E+11 | 0.00 | 653.08 | 0.131808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31402.85 | 13-JUL-21:00 | 18312.54 | 08-JUL-17:30 | 0.00 | 0.00 | 0.00 |
August | 0.399439E+11 | 0.00 | 728.58 | 0.183057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31373.38 | 19-AUG-13:30 | 21748.32 | 19-AUG-13:50 | 0.00 | 0.00 | 0.00 |
September | 0.257421E+11 | 0.00 | 541.19 | 0.118540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35551.68 | 24-SEP-12:30 | 27828.77 | 24-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.158466E+11 | 0.00 | 343.97 | 0.947929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39345.42 | 10-OCT-13:30 | 33786.92 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.676800E+10 | 0.00 | 179.55 | 0.613738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27712.67 | 12-NOV-14:00 | 27712.67 | 12-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.263946E+10 | 0.00 | 77.01 | 0.217541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26824.40 | 10-DEC-14:00 | 26824.40 | 10-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177924E+12 | 0.00 | 4104.55 | 0.867492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.203439E+09 | 0.00 | 12.50 | 0.202136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12712.09 | 12712.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.399439E+11 | 0.00 | 728.58 | 0.183057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39345.42 | 33786.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.722444E+09 | 0.00 | 45.22 | 0.284172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84932.09 | 19-JAN-22:53 | 76332.90 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.326834E+10 | 0.00 | 138.25 | 0.200583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98111.36 | 18-FEB-09:02 | 88428.86 | 28-FEB-22:51 | 0.00 | 0.00 | 0.00 |
March | 0.109395E+11 | 0.00 | 302.08 | 0.666732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100092.33 | 28-MAR-21:51 | 88805.05 | 31-MAR-20:12 | 0.00 | 0.00 | 0.00 |
April | 0.226849E+11 | 0.00 | 348.59 | 0.128476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110455.69 | 30-APR-21:52 | 87533.08 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.387006E+11 | 0.00 | 364.57 | 0.230966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113868.02 | 26-MAY-21:51 | 92691.54 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.550657E+11 | 0.00 | 442.27 | 0.357730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120107.90 | 26-JUN-21:51 | 90840.10 | 10-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.625376E+11 | 0.00 | 474.46 | 0.404013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122413.74 | 25-JUL-21:51 | 85704.47 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.626550E+11 | 0.00 | 481.04 | 0.392414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119036.04 | 07-AUG-21:51 | 86050.98 | 25-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.394254E+11 | 0.00 | 364.92 | 0.225566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118571.79 | 02-SEP-21:51 | 86635.07 | 14-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.166665E+11 | 0.00 | 345.81 | 0.771697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122792.15 | 18-OCT-21:51 | 89367.87 | 11-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.635435E+10 | 0.00 | 217.28 | 0.339229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108380.75 | 05-NOV-21:51 | 83801.84 | 08-NOV-21:11 | 0.00 | 0.00 | 0.00 |
December | 0.161785E+10 | 0.00 | 95.23 | 0.705632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104088.92 | 13-DEC-21:02 | 75940.35 | 12-DEC-22:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320638E+12 | 0.00 | 3619.72 | 0.194689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.722444E+09 | 0.00 | 45.22 | 0.284172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84932.09 | 75940.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.626550E+11 | 0.00 | 481.04 | 0.404013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122792.15 | 92691.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 36917005.37 | 0.00 | 17.72 | 32148763.89 | 0.00 | 0.00 | 0.00 | 0.00 | 11763.41 | 29-JAN-16:01 | 11763.41 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.344643E+09 | 0.00 | 82.21 | 0.308582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12539.78 | 28-FEB-16:01 | 12539.78 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.118699E+10 | 0.00 | 231.21 | 0.750768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13999.13 | 30-MAR-08:52 | 12534.59 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.274284E+10 | 0.00 | 373.63 | 0.156500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15039.49 | 30-APR-21:52 | 13106.65 | 14-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.508130E+10 | 0.00 | 496.66 | 0.280365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15996.88 | 07-MAY-08:51 | 13268.89 | 18-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.802228E+10 | 0.00 | 572.05 | 0.476018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17316.28 | 29-JUN-08:51 | 13277.16 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.959771E+10 | 0.00 | 589.11 | 0.585461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17584.65 | 23-JUL-08:51 | 12715.06 | 25-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.101521E+11 | 0.00 | 622.66 | 0.614381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17780.05 | 29-AUG-08:31 | 12905.42 | 26-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.586160E+10 | 0.00 | 488.17 | 0.324228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16795.81 | 09-SEP-21:51 | 13157.16 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.216454E+10 | 0.00 | 328.18 | 0.109672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16868.39 | 18-OCT-21:51 | 12538.68 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.492388E+09 | 0.00 | 128.06 | 0.330461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14716.60 | 05-NOV-21:51 | 12529.89 | 06-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.127565E+09 | 0.00 | 43.75 | 86939173.60 | 0.00 | 0.00 | 0.00 | 0.00 | 13046.45 | 12-DEC-22:51 | 12025.64 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458109E+11 | 0.00 | 3973.42 | 0.269751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 36917005.37 | 0.00 | 17.72 | 32148763.89 | 0.00 | 0.00 | 0.00 | 0.00 | 11763.41 | 11763.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101521E+11 | 0.00 | 622.66 | 0.614381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17780.05 | 13277.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4957936.94 | 0.00 | 2.88 | 3584133.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2304.44 | 20-JAN-09:05 | 2014.94 | 29-JAN-17:44 | 0.00 | 0.00 | 0.00 |
February | 0.145741E+09 | 0.00 | 36.09 | 0.119279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11964.04 | 28-FEB-16:01 | 11964.04 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.707508E+09 | 0.00 | 157.43 | 0.397089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13829.56 | 30-MAR-08:52 | 11817.36 | 30-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.220910E+10 | 0.00 | 334.59 | 0.121255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14849.17 | 30-APR-21:52 | 12911.57 | 14-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.478652E+10 | 0.00 | 485.15 | 0.263117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15871.75 | 07-MAY-08:51 | 13159.19 | 18-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.794510E+10 | 0.00 | 572.47 | 0.471046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17218.91 | 29-JUN-08:51 | 13183.93 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.945143E+10 | 0.00 | 589.05 | 0.574649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17506.62 | 23-JUL-08:51 | 12648.83 | 03-JUL-08:41 | 0.00 | 0.00 | 0.00 |
August | 0.959337E+10 | 0.00 | 620.71 | 0.564761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17549.18 | 13-AUG-08:31 | 12782.40 | 26-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.500820E+10 | 0.00 | 479.86 | 0.265239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16598.16 | 06-SEP-08:31 | 12750.27 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.132804E+10 | 0.00 | 207.08 | 0.616563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16660.47 | 18-OCT-21:51 | 11557.15 | 10-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.148917E+09 | 0.00 | 58.54 | 74559392.95 | 0.00 | 0.00 | 0.00 | 0.00 | 14342.11 | 05-NOV-21:51 | 10927.39 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 14510196.42 | 0.00 | 8.31 | 6766894.65 | 0.00 | 0.00 | 0.00 | 0.00 | 9066.92 | 12-DEC-22:51 | 5735.20 | 12-DEC-22:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413434E+11 | 0.00 | 3552.16 | 0.238185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4957936.94 | 0.00 | 2.88 | 3584133.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2304.44 | 2014.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.959337E+10 | 0.00 | 620.71 | 0.574649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17549.18 | 13183.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 10776280.83 | 0.00 | 10.98 | 10311860.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3615.79 | 29-JAN-16:01 | 3615.79 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 57258693.09 | 0.00 | 58.66 | 53231155.45 | 0.00 | 0.00 | 0.00 | 0.00 | 3622.83 | 28-FEB-16:01 | 3622.83 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.329075E+09 | 0.00 | 200.16 | 0.212127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4091.55 | 28-MAR-21:51 | 3742.09 | 12-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.752929E+09 | 0.00 | 354.98 | 0.450859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4548.79 | 30-APR-21:52 | 3988.84 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.138585E+10 | 0.00 | 482.64 | 0.790996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4640.74 | 26-MAY-21:51 | 3941.30 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.216984E+10 | 0.00 | 558.99 | 0.132889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5155.46 | 26-JUN-21:51 | 3568.16 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.254457E+10 | 0.00 | 580.02 | 0.157210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5140.05 | 25-JUL-21:51 | 3506.32 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.273484E+10 | 0.00 | 616.13 | 0.167601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5057.39 | 20-AUG-21:51 | 3500.56 | 21-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.155415E+10 | 0.00 | 474.73 | 0.870734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4884.18 | 09-SEP-21:51 | 3887.22 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.541428E+09 | 0.00 | 276.08 | 0.280539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5086.03 | 18-OCT-21:51 | 3935.91 | 15-OCT-16:21 | 0.00 | 0.00 | 0.00 |
November | 0.107965E+09 | 0.00 | 111.35 | 76550771.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4441.52 | 05-NOV-21:51 | 3622.24 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 27279548.47 | 0.00 | 31.18 | 21205799.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3852.66 | 12-DEC-22:51 | 3618.33 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122160E+11 | 0.00 | 3755.89 | 0.734356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10776280.83 | 0.00 | 10.98 | 10311860.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3615.79 | 3500.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.273484E+10 | 0.00 | 616.13 | 0.167601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5155.46 | 3988.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 925457.11 | 0.00 | 0.94 | 547871.02 | 0.00 | 0.00 | 0.00 | 0.00 | 626.83 | 19-JAN-22:57 | 572.29 | 11-JAN-16:05 | 0.00 | 0.00 | 0.00 |
February | 17245678.84 | 0.00 | 15.22 | 15593862.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.38 | 28-FEB-16:01 | 3582.38 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.204691E+09 | 0.00 | 136.13 | 0.122295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.78 | 28-MAR-21:51 | 3580.80 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.610754E+09 | 0.00 | 317.75 | 0.347766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4479.83 | 30-APR-21:52 | 3812.85 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.130849E+10 | 0.00 | 471.17 | 0.740655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4583.27 | 26-MAY-21:51 | 3856.64 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.215105E+10 | 0.00 | 557.71 | 0.131972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5097.04 | 26-JUN-21:51 | 3513.14 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.250855E+10 | 0.00 | 579.40 | 0.154735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.67 | 25-JUL-21:51 | 3465.00 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.259294E+10 | 0.00 | 613.90 | 0.155875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.06 | 20-AUG-21:51 | 3467.99 | 22-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.132959E+10 | 0.00 | 453.16 | 0.709660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4915.59 | 09-SEP-21:51 | 3775.42 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.327435E+09 | 0.00 | 185.33 | 0.156852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5007.16 | 18-OCT-21:51 | 3580.24 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 28898524.26 | 0.00 | 29.09 | 17621134.51 | 0.00 | 0.00 | 0.00 | 0.00 | 4321.51 | 05-NOV-21:51 | 3581.59 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 2666607.63 | 0.00 | 3.72 | 1705361.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3088.39 | 11-DEC-16:01 | 2652.33 | 11-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110832E+11 | 0.00 | 3363.52 | 0.653852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 925457.11 | 0.00 | 0.94 | 547871.02 | 0.00 | 0.00 | 0.00 | 0.00 | 626.83 | 572.29 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.259294E+10 | 0.00 | 613.90 | 0.155875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5097.04 | 3856.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.778744E+09 | 0.00 | 110.42 | 0.739107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17166.02 | 29-JAN-17:41 | 17166.02 | 29-JAN-17:41 | 0.00 | 0.00 | 0.00 |
February | 0.131648E+10 | 0.00 | 160.49 | 0.117974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17310.92 | 21-FEB-22:11 | 17310.92 | 21-FEB-22:11 | 0.00 | 0.00 | 0.00 |
March | 0.321050E+10 | 0.00 | 349.39 | 0.222985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18915.89 | 28-MAR-21:51 | 17251.75 | 15-MAR-21:01 | 0.00 | 0.00 | 0.00 |
April | 0.449148E+10 | 0.00 | 397.20 | 0.266521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20531.75 | 30-APR-21:52 | 17282.20 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.682015E+10 | 0.00 | 477.01 | 0.374238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21137.52 | 26-MAY-21:51 | 17163.59 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.100839E+11 | 0.00 | 549.45 | 0.597928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22958.97 | 26-JUN-21:51 | 16044.68 | 12-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.120873E+11 | 0.00 | 572.85 | 0.732867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23324.63 | 25-JUL-21:51 | 16086.74 | 04-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.138146E+11 | 0.00 | 610.66 | 0.865670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22879.39 | 20-AUG-21:51 | 16077.99 | 21-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.929747E+10 | 0.00 | 487.17 | 0.561852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22620.70 | 09-SEP-21:51 | 17465.17 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.540515E+10 | 0.00 | 417.69 | 0.325903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23402.35 | 18-OCT-21:51 | 18003.52 | 15-OCT-16:21 | 0.00 | 0.00 | 0.00 |
November | 0.297433E+10 | 0.00 | 334.90 | 0.225405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20538.03 | 05-NOV-21:51 | 17340.74 | 08-NOV-21:11 | 0.00 | 0.00 | 0.00 |
December | 0.163179E+10 | 0.00 | 195.53 | 0.138233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19282.04 | 13-DEC-21:02 | 17028.07 | 10-DEC-19:21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.719119E+11 | 0.00 | 4662.76 | 0.450349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.778744E+09 | 0.00 | 110.42 | 0.739107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17166.02 | 16044.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.138146E+11 | 0.00 | 610.66 | 0.865670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23402.35 | 18003.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.26 | 366.27 | 160.99 | 592.97 | 629.76 | 0.00 | 0.00 | 0.00 |
February | 491.15 | 327.66 | 163.48 | 607.31 | 518.81 | 0.00 | 0.00 | 0.00 |
March | 449.12 | 235.68 | 213.44 | 630.07 | 321.68 | 0.00 | 0.00 | 0.00 |
April | 338.00 | 112.77 | 225.23 | 544.24 | 247.45 | 0.00 | 0.00 | 0.00 |
May | 271.69 | 33.25 | 238.45 | 483.64 | 142.13 | 0.00 | 0.00 | 0.00 |
June | 249.47 | 13.93 | 235.54 | 526.03 | 78.21 | 0.00 | 0.00 | 0.00 |
July | 250.25 | 16.88 | 233.37 | 549.35 | 45.65 | 0.00 | 0.00 | 0.00 |
August | 301.54 | 56.67 | 244.87 | 650.68 | 35.26 | 0.00 | 0.00 | 0.00 |
September | 340.43 | 132.46 | 207.97 | 625.01 | 109.82 | 0.00 | 0.00 | 0.00 |
October | 478.03 | 308.97 | 169.06 | 733.25 | 283.10 | 0.00 | 0.00 | 0.00 |
November | 522.27 | 348.52 | 173.76 | 710.62 | 395.88 | 0.00 | 0.00 | 0.00 |
December | 523.54 | 368.30 | 155.25 | 636.69 | 517.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 394.80 | 192.80 | 202.00 | 607.56 | 275.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.47 | 13.93 | 155.25 | 483.64 | 35.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 527.26 | 368.30 | 244.87 | 733.25 | 629.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1484.72 | 1031.40 | 453.32 | 1648.75 | 1814.64 | 0.00 | 0.00 | 0.00 |
February | 1383.03 | 922.68 | 460.35 | 1689.02 | 1515.09 | 0.00 | 0.00 | 0.00 |
March | 1264.70 | 663.66 | 601.04 | 1749.47 | 972.91 | 0.00 | 0.00 | 0.00 |
April | 951.78 | 317.55 | 634.23 | 1508.93 | 758.65 | 0.00 | 0.00 | 0.00 |
May | 765.07 | 93.63 | 671.45 | 1335.52 | 462.83 | 0.00 | 0.00 | 0.00 |
June | 702.49 | 39.22 | 663.27 | 1460.03 | 269.66 | 0.00 | 0.00 | 0.00 |
July | 704.68 | 47.53 | 657.15 | 1532.37 | 169.46 | 0.00 | 0.00 | 0.00 |
August | 849.11 | 159.58 | 689.52 | 1823.60 | 137.62 | 0.00 | 0.00 | 0.00 |
September | 958.64 | 373.00 | 585.64 | 1736.71 | 371.99 | 0.00 | 0.00 | 0.00 |
October | 1346.11 | 870.05 | 476.06 | 2041.83 | 870.42 | 0.00 | 0.00 | 0.00 |
November | 1470.69 | 981.40 | 489.29 | 1977.55 | 1179.75 | 0.00 | 0.00 | 0.00 |
December | 1474.27 | 1037.10 | 437.17 | 1770.23 | 1509.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1111.73 | 542.91 | 568.82 | 1689.71 | 832.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 702.49 | 39.22 | 437.17 | 1335.52 | 137.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.72 | 1037.10 | 689.52 | 2041.83 | 1814.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1928.74 | 1339.84 | 588.89 | 2186.08 | 2436.45 | 0.00 | 0.00 | 0.00 |
February | 1796.64 | 1198.62 | 598.02 | 2247.87 | 2026.80 | 0.00 | 0.00 | 0.00 |
March | 1642.92 | 862.13 | 780.79 | 2342.01 | 1285.34 | 0.00 | 0.00 | 0.00 |
April | 1236.41 | 412.51 | 823.90 | 2022.46 | 1006.60 | 0.00 | 0.00 | 0.00 |
May | 993.87 | 121.63 | 872.25 | 1789.60 | 609.66 | 0.00 | 0.00 | 0.00 |
June | 912.57 | 50.95 | 861.62 | 1954.62 | 350.58 | 0.00 | 0.00 | 0.00 |
July | 915.42 | 61.75 | 853.67 | 2055.82 | 216.55 | 0.00 | 0.00 | 0.00 |
August | 1103.04 | 207.31 | 895.73 | 2454.35 | 166.42 | 0.00 | 0.00 | 0.00 |
September | 1245.33 | 484.54 | 760.78 | 2325.56 | 482.31 | 0.00 | 0.00 | 0.00 |
October | 1748.68 | 1130.24 | 618.43 | 2734.70 | 1145.37 | 0.00 | 0.00 | 0.00 |
November | 1910.51 | 1274.89 | 635.62 | 2638.68 | 1568.81 | 0.00 | 0.00 | 0.00 |
December | 1915.16 | 1347.25 | 567.91 | 2354.92 | 2022.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1444.20 | 705.27 | 738.93 | 2259.24 | 1105.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 912.57 | 50.95 | 567.91 | 1789.60 | 166.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1928.74 | 1347.25 | 895.73 | 2734.70 | 2436.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 117.31 | 128.28 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 119.36 | 105.92 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 121.84 | 66.46 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 104.79 | 52.28 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 92.46 | 29.99 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 105.05 | 13.85 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 112.65 | 6.92 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 135.41 | 3.52 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 124.02 | 20.73 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.22 | 57.26 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 140.35 | 79.97 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 126.08 | 104.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.32 | 55.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 92.46 | 3.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.22 | 128.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 61.91 | 271.80 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 94.36 | 220.22 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 174.96 | 128.68 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 233.69 | 95.77 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 264.03 | 55.10 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 320.57 | 25.61 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 318.40 | 12.77 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 315.49 | 6.54 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 219.22 | 38.76 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 156.90 | 112.84 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 100.46 | 165.24 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 60.85 | 222.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 193.94 | 112.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 60.85 | 6.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 320.57 | 271.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.76 | 154.05 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.88 | 122.81 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 23.04 | 69.81 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 45.43 | 51.11 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 69.78 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 101.40 | 12.72 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 104.14 | 6.58 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 96.40 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 54.83 | 20.39 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 24.51 | 59.83 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.87 | 88.35 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.49 | 121.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.92 | 61.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.76 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 104.14 | 154.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.47 | 267.48 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 98.51 | 216.38 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 180.03 | 125.52 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 236.42 | 94.52 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 264.95 | 54.70 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 320.61 | 25.59 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 318.58 | 12.71 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 316.67 | 6.35 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 221.53 | 37.75 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 162.14 | 109.41 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 106.01 | 160.60 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 65.27 | 217.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 196.88 | 110.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 65.27 | 6.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 320.61 | 267.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.38 | 57.92 | 25.46 | 92.32 | 101.76 | 0.00 | 0.00 | 0.00 |
February | 77.67 | 51.82 | 25.85 | 93.71 | 86.09 | 0.00 | 0.00 | 0.00 |
March | 71.03 | 37.27 | 33.75 | 94.18 | 60.17 | 0.00 | 0.00 | 0.00 |
April | 53.45 | 17.83 | 35.62 | 81.26 | 47.27 | 0.00 | 0.00 | 0.00 |
May | 42.97 | 5.26 | 37.71 | 72.01 | 28.53 | 0.00 | 0.00 | 0.00 |
June | 39.45 | 2.20 | 37.25 | 81.76 | 15.05 | 0.00 | 0.00 | 0.00 |
July | 39.57 | 2.67 | 36.91 | 87.35 | 8.80 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 8.96 | 38.72 | 104.84 | 6.06 | 0.00 | 0.00 | 0.00 |
September | 53.84 | 20.95 | 32.89 | 96.54 | 21.58 | 0.00 | 0.00 | 0.00 |
October | 75.60 | 48.86 | 26.74 | 112.21 | 53.17 | 0.00 | 0.00 | 0.00 |
November | 82.59 | 55.11 | 27.48 | 107.59 | 73.42 | 0.00 | 0.00 | 0.00 |
December | 82.79 | 58.24 | 24.55 | 97.29 | 88.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.43 | 30.49 | 31.95 | 93.44 | 49.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.45 | 2.20 | 24.55 | 72.01 | 6.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.38 | 58.24 | 38.72 | 112.21 | 101.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.71 | 0.00 | 15.71 | 2.02 | 128.81 | 0.00 | 0.00 | 0.00 |
February | 17.41 | 0.00 | 17.41 | 7.98 | 102.11 | 0.00 | 0.00 | 0.00 |
March | 24.45 | 0.00 | 24.45 | 19.57 | 56.00 | 0.00 | 0.00 | 0.00 |
April | 29.65 | 0.17 | 29.48 | 38.83 | 40.02 | 0.00 | 0.00 | 0.00 |
May | 35.37 | 1.11 | 34.27 | 59.28 | 21.20 | 0.00 | 0.00 | 0.00 |
June | 38.91 | 2.55 | 36.35 | 85.60 | 8.97 | 0.00 | 0.00 | 0.00 |
July | 36.85 | 1.89 | 34.96 | 88.13 | 4.35 | 0.00 | 0.00 | 0.00 |
August | 32.73 | 0.38 | 32.34 | 82.56 | 1.89 | 0.00 | 0.00 | 0.00 |
September | 24.70 | 0.01 | 24.69 | 47.21 | 15.23 | 0.00 | 0.00 | 0.00 |
October | 18.77 | 0.00 | 18.77 | 20.93 | 48.04 | 0.00 | 0.00 | 0.00 |
November | 16.80 | 0.00 | 16.80 | 10.36 | 72.91 | 0.00 | 0.00 | 0.00 |
December | 14.52 | 0.00 | 14.52 | 2.43 | 102.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.53 | 0.51 | 25.02 | 38.92 | 49.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.52 | 0.00 | 14.52 | 2.02 | 1.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.91 | 2.55 | 36.35 | 88.13 | 128.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 51.56 | 263.79 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 94.05 | 208.10 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 146.99 | 118.68 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 222.60 | 87.94 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 277.00 | 50.55 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 332.11 | 23.12 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 339.94 | 12.23 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 319.93 | 6.04 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 221.74 | 36.63 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 146.07 | 104.59 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 85.96 | 151.60 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 51.90 | 208.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 191.34 | 105.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 51.56 | 6.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 339.94 | 263.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 116.74 | 127.96 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 118.41 | 105.57 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 121.20 | 65.38 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 103.75 | 51.41 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 91.14 | 29.58 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 103.58 | 13.66 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 111.35 | 6.89 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 134.73 | 3.41 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 123.16 | 20.42 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 143.58 | 56.44 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 139.88 | 79.32 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 125.54 | 104.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 119.45 | 55.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 91.14 | 3.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 143.58 | 127.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.62 | 154.06 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.52 | 122.93 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.72 | 68.96 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 44.40 | 50.44 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 68.33 | 27.53 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 99.85 | 12.49 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 102.80 | 6.55 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.67 | 3.23 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.84 | 20.15 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 23.79 | 59.16 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.73 | 87.74 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.36 | 122.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.17 | 60.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.62 | 3.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 102.80 | 154.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 53.50 | 257.68 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 97.55 | 203.48 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 151.77 | 115.17 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 224.90 | 86.64 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 277.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 332.14 | 23.10 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 340.12 | 12.17 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 321.08 | 5.87 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 223.77 | 35.70 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 150.75 | 101.02 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 91.20 | 146.25 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 54.98 | 202.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 193.81 | 102.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 53.50 | 5.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 340.12 | 257.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 2.98 | 211.31 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 12.29 | 166.17 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 31.22 | 89.32 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 62.81 | 63.46 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 95.90 | 34.39 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 133.88 | 17.54 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 135.03 | 10.28 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 124.13 | 6.21 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 73.41 | 27.03 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 33.26 | 76.99 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 16.05 | 117.03 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 3.34 | 167.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 60.63 | 81.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 2.98 | 6.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 135.03 | 211.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.17 | 0.00 | 9.17 | 1.10 | 77.90 | 0.00 | 0.00 | 0.00 |
February | 10.16 | 0.00 | 10.16 | 4.53 | 61.26 | 0.00 | 0.00 | 0.00 |
March | 14.27 | 0.00 | 14.27 | 11.51 | 32.93 | 0.00 | 0.00 | 0.00 |
April | 17.30 | 0.10 | 17.20 | 23.15 | 23.39 | 0.00 | 0.00 | 0.00 |
May | 20.64 | 0.65 | 19.99 | 35.35 | 12.68 | 0.00 | 0.00 | 0.00 |
June | 22.70 | 1.49 | 21.21 | 49.35 | 6.46 | 0.00 | 0.00 | 0.00 |
July | 21.50 | 1.10 | 20.40 | 49.78 | 3.79 | 0.00 | 0.00 | 0.00 |
August | 19.10 | 0.22 | 18.87 | 45.76 | 2.29 | 0.00 | 0.00 | 0.00 |
September | 14.41 | 0.01 | 14.41 | 27.06 | 9.96 | 0.00 | 0.00 | 0.00 |
October | 10.95 | 0.00 | 10.95 | 12.26 | 28.38 | 0.00 | 0.00 | 0.00 |
November | 9.80 | 0.00 | 9.80 | 5.92 | 43.14 | 0.00 | 0.00 | 0.00 |
December | 8.47 | 0.00 | 8.47 | 1.23 | 61.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.90 | 0.30 | 14.60 | 22.35 | 30.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.47 | 0.00 | 8.47 | 1.10 | 2.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.70 | 1.49 | 21.21 | 49.78 | 77.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.64 | 33.79 | 14.85 | 53.95 | 63.11 | 0.00 | 0.00 | 0.00 |
February | 45.31 | 30.23 | 15.08 | 55.80 | 51.49 | 0.00 | 0.00 | 0.00 |
March | 41.43 | 21.74 | 19.69 | 58.85 | 30.59 | 0.00 | 0.00 | 0.00 |
April | 31.18 | 10.40 | 20.78 | 51.39 | 23.54 | 0.00 | 0.00 | 0.00 |
May | 25.07 | 3.07 | 22.00 | 46.01 | 13.43 | 0.00 | 0.00 | 0.00 |
June | 23.01 | 1.28 | 21.73 | 50.99 | 6.99 | 0.00 | 0.00 | 0.00 |
July | 23.09 | 1.56 | 21.53 | 53.74 | 3.94 | 0.00 | 0.00 | 0.00 |
August | 27.82 | 5.23 | 22.59 | 64.17 | 2.32 | 0.00 | 0.00 | 0.00 |
September | 31.41 | 12.22 | 19.19 | 59.83 | 9.87 | 0.00 | 0.00 | 0.00 |
October | 44.10 | 28.50 | 15.60 | 69.50 | 26.42 | 0.00 | 0.00 | 0.00 |
November | 48.18 | 32.15 | 16.03 | 66.61 | 37.78 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 33.98 | 14.32 | 58.53 | 51.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.42 | 17.79 | 18.64 | 57.46 | 26.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.01 | 1.28 | 14.32 | 46.01 | 2.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.64 | 33.98 | 22.59 | 69.50 | 63.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.02 | 91.71 | 40.31 | 146.43 | 171.28 | 0.00 | 0.00 | 0.00 |
February | 122.98 | 82.05 | 40.94 | 151.44 | 139.75 | 0.00 | 0.00 | 0.00 |
March | 112.46 | 59.01 | 53.45 | 159.72 | 83.02 | 0.00 | 0.00 | 0.00 |
April | 84.63 | 28.24 | 56.40 | 139.49 | 63.90 | 0.00 | 0.00 | 0.00 |
May | 68.03 | 8.33 | 59.71 | 124.87 | 36.44 | 0.00 | 0.00 | 0.00 |
June | 62.47 | 3.49 | 58.98 | 138.41 | 18.96 | 0.00 | 0.00 | 0.00 |
July | 62.66 | 4.23 | 58.43 | 145.86 | 10.70 | 0.00 | 0.00 | 0.00 |
August | 75.50 | 14.19 | 61.31 | 174.16 | 6.30 | 0.00 | 0.00 | 0.00 |
September | 85.24 | 33.17 | 52.08 | 162.39 | 26.80 | 0.00 | 0.00 | 0.00 |
October | 119.70 | 77.37 | 42.33 | 188.65 | 71.71 | 0.00 | 0.00 | 0.00 |
November | 130.78 | 87.27 | 43.51 | 180.80 | 102.53 | 0.00 | 0.00 | 0.00 |
December | 131.09 | 92.22 | 38.87 | 158.85 | 138.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.86 | 48.28 | 50.58 | 155.97 | 72.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.47 | 3.49 | 38.87 | 124.87 | 6.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.02 | 92.22 | 61.31 | 188.65 | 171.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 116.70 | 127.86 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 118.37 | 105.66 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 120.13 | 66.58 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 102.94 | 52.85 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 90.56 | 30.50 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 103.78 | 13.70 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 111.45 | 6.73 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 134.09 | 3.29 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 122.58 | 20.61 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 142.53 | 57.43 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 139.32 | 79.58 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 125.37 | 104.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 119.01 | 55.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 90.56 | 3.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 142.53 | 127.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 61.66 | 271.17 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 93.32 | 219.56 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 171.90 | 128.66 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 229.63 | 96.61 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 259.54 | 55.84 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 316.83 | 25.24 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 315.28 | 12.38 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 312.45 | 6.12 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 216.51 | 38.46 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 154.30 | 112.99 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 99.29 | 164.47 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 60.61 | 220.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 191.48 | 112.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 60.61 | 6.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 316.83 | 271.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.85 | 153.90 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.94 | 122.51 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.61 | 69.73 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 44.23 | 51.63 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 68.05 | 28.43 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 100.19 | 12.60 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 103.03 | 6.45 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.44 | 3.13 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.99 | 20.20 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 24.12 | 59.73 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.01 | 87.68 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.71 | 121.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.30 | 61.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.85 | 3.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 103.03 | 153.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.19 | 267.20 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 97.64 | 215.66 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 177.48 | 125.09 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 232.39 | 95.28 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 260.41 | 55.41 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 316.85 | 25.22 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 315.46 | 12.32 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 313.66 | 5.93 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 218.86 | 37.36 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 160.02 | 109.03 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 105.45 | 159.32 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 65.38 | 216.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 194.59 | 109.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 65.19 | 5.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 316.85 | 267.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.89 | 106.21 | 46.68 | 162.72 | 195.80 | 0.00 | 0.00 | 0.00 |
February | 142.42 | 95.01 | 47.41 | 167.20 | 161.82 | 0.00 | 0.00 | 0.00 |
March | 130.23 | 68.34 | 61.89 | 173.01 | 100.04 | 0.00 | 0.00 | 0.00 |
April | 98.01 | 32.70 | 65.31 | 151.26 | 76.41 | 0.00 | 0.00 | 0.00 |
May | 78.78 | 9.64 | 69.14 | 135.56 | 42.76 | 0.00 | 0.00 | 0.00 |
June | 72.34 | 4.04 | 68.30 | 156.53 | 18.50 | 0.00 | 0.00 | 0.00 |
July | 72.57 | 4.89 | 67.67 | 167.98 | 8.97 | 0.00 | 0.00 | 0.00 |
August | 87.44 | 16.43 | 71.00 | 200.76 | 4.21 | 0.00 | 0.00 | 0.00 |
September | 98.72 | 38.41 | 60.31 | 180.52 | 30.01 | 0.00 | 0.00 | 0.00 |
October | 138.62 | 89.59 | 49.02 | 205.97 | 87.30 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 101.06 | 50.39 | 198.03 | 123.14 | 0.00 | 0.00 | 0.00 |
December | 151.81 | 106.80 | 45.02 | 175.55 | 160.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.48 | 55.91 | 58.58 | 172.99 | 83.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.34 | 4.04 | 45.02 | 135.56 | 4.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.89 | 106.80 | 71.00 | 205.97 | 195.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 12.67 | 1267.45 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 55.19 | 1028.46 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 136.42 | 603.86 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 292.09 | 442.57 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 458.42 | 263.57 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 666.20 | 145.52 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 677.46 | 94.73 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 620.87 | 72.32 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 355.63 | 213.57 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 150.91 | 528.28 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 67.64 | 756.86 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 12.91 | 1035.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 293.56 | 535.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 12.67 | 72.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 677.46 | 1267.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 11.02 | 1300.89 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 50.37 | 1061.30 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 124.46 | 631.39 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 276.14 | 462.45 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 440.48 | 276.57 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 650.08 | 153.42 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 662.73 | 101.41 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 606.81 | 78.74 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 340.84 | 227.51 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 139.85 | 554.91 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 59.27 | 788.13 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 10.82 | 1071.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 282.42 | 556.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 10.82 | 78.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 662.73 | 1300.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 1.69 | 184.66 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 7.80 | 149.99 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 20.50 | 86.65 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 46.84 | 62.30 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 74.84 | 37.31 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 107.55 | 21.10 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 111.07 | 13.57 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 102.60 | 10.27 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 58.93 | 28.82 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 23.96 | 74.96 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 10.13 | 108.33 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 1.74 | 150.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 47.53 | 77.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 1.69 | 10.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 111.07 | 184.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.23 | 73.86 | 88.36 | 94.76 | 618.99 | 0.00 | 0.00 | 0.00 |
February | 203.60 | 109.60 | 94.00 | 181.49 | 499.99 | 0.00 | 0.00 | 0.00 |
March | 256.16 | 116.85 | 139.31 | 292.98 | 292.16 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 141.33 | 168.31 | 459.07 | 216.39 | 0.00 | 0.00 | 0.00 |
May | 339.21 | 143.45 | 195.76 | 579.62 | 136.92 | 0.00 | 0.00 | 0.00 |
June | 350.85 | 146.95 | 203.90 | 695.18 | 78.49 | 0.00 | 0.00 | 0.00 |
July | 341.97 | 143.47 | 198.50 | 710.03 | 51.20 | 0.00 | 0.00 | 0.00 |
August | 313.43 | 124.33 | 189.10 | 666.32 | 38.70 | 0.00 | 0.00 | 0.00 |
September | 256.88 | 113.51 | 143.37 | 468.23 | 104.89 | 0.00 | 0.00 | 0.00 |
October | 219.71 | 114.36 | 105.35 | 301.32 | 257.84 | 0.00 | 0.00 | 0.00 |
November | 174.98 | 78.93 | 96.05 | 168.37 | 361.10 | 0.00 | 0.00 | 0.00 |
December | 151.85 | 69.12 | 82.73 | 95.11 | 499.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 256.97 | 114.63 | 142.34 | 393.84 | 261.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.85 | 69.12 | 82.73 | 94.76 | 38.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.85 | 146.95 | 203.90 | 710.03 | 618.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 112.11 | 148.34 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 115.56 | 125.48 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 121.38 | 79.85 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 107.43 | 62.27 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 98.18 | 38.83 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 111.63 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 119.40 | 13.89 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 142.03 | 10.33 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 130.01 | 28.38 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 146.79 | 69.16 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 139.73 | 94.12 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 121.94 | 123.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 122.24 | 67.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 98.18 | 10.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 146.79 | 148.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 2.70 | 215.66 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 11.32 | 169.89 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 28.72 | 91.82 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 59.29 | 65.20 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 91.01 | 36.29 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 127.25 | 19.70 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 127.38 | 12.18 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 116.09 | 8.44 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 70.02 | 28.00 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 30.98 | 78.94 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 14.50 | 120.03 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 2.85 | 171.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 57.10 | 84.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 2.70 | 8.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 127.38 | 215.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 0.00 | 22.25 | 2.41 | 192.95 | 0.00 | 0.00 | 0.00 |
February | 24.66 | 0.00 | 24.66 | 10.13 | 152.00 | 0.00 | 0.00 | 0.00 |
March | 34.63 | 0.00 | 34.63 | 25.69 | 82.15 | 0.00 | 0.00 | 0.00 |
April | 41.99 | 0.25 | 41.74 | 53.04 | 58.33 | 0.00 | 0.00 | 0.00 |
May | 50.10 | 1.57 | 48.53 | 81.43 | 32.47 | 0.00 | 0.00 | 0.00 |
June | 55.10 | 3.61 | 51.48 | 113.85 | 17.62 | 0.00 | 0.00 | 0.00 |
July | 52.18 | 2.67 | 49.51 | 113.97 | 10.89 | 0.00 | 0.00 | 0.00 |
August | 46.35 | 0.54 | 45.80 | 103.87 | 7.55 | 0.00 | 0.00 | 0.00 |
September | 34.98 | 0.01 | 34.97 | 62.65 | 25.05 | 0.00 | 0.00 | 0.00 |
October | 26.58 | 0.00 | 26.58 | 27.72 | 70.63 | 0.00 | 0.00 | 0.00 |
November | 23.79 | 0.00 | 23.79 | 12.97 | 107.39 | 0.00 | 0.00 | 0.00 |
December | 20.57 | 0.00 | 20.57 | 2.55 | 153.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.16 | 0.73 | 35.43 | 51.09 | 75.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.57 | 0.00 | 20.57 | 2.41 | 7.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.10 | 3.61 | 51.48 | 113.97 | 192.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.19 | 270.36 | 118.83 | 422.76 | 512.87 | 0.00 | 0.00 | 0.00 |
February | 362.53 | 241.86 | 120.67 | 436.72 | 420.49 | 0.00 | 0.00 | 0.00 |
March | 331.52 | 173.96 | 157.55 | 458.15 | 251.16 | 0.00 | 0.00 | 0.00 |
April | 249.49 | 83.24 | 166.25 | 398.12 | 193.92 | 0.00 | 0.00 | 0.00 |
May | 200.55 | 24.54 | 176.01 | 352.84 | 113.68 | 0.00 | 0.00 | 0.00 |
June | 184.14 | 10.28 | 173.86 | 388.32 | 62.87 | 0.00 | 0.00 | 0.00 |
July | 184.72 | 12.46 | 172.26 | 407.23 | 37.69 | 0.00 | 0.00 | 0.00 |
August | 222.58 | 41.83 | 180.75 | 488.32 | 25.53 | 0.00 | 0.00 | 0.00 |
September | 251.29 | 97.77 | 153.51 | 466.41 | 82.33 | 0.00 | 0.00 | 0.00 |
October | 352.86 | 228.06 | 124.79 | 544.47 | 216.57 | 0.00 | 0.00 | 0.00 |
November | 385.51 | 257.25 | 128.26 | 522.53 | 308.97 | 0.00 | 0.00 | 0.00 |
December | 386.45 | 271.85 | 114.60 | 458.76 | 416.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.42 | 142.31 | 149.11 | 445.47 | 219.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.14 | 10.28 | 114.60 | 352.84 | 25.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.19 | 271.85 | 180.75 | 544.47 | 512.87 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.158821E+10 | 0.168676E+10 |
February | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.146921E+10 | 0.125510E+10 |
March | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.168757E+10 | 0.861578E+09 |
April | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.141068E+10 | 0.641389E+09 |
May | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.129538E+10 | 0.380681E+09 |
June | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.136347E+10 | 0.202716E+09 |
July | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.147138E+10 | 0.122261E+09 |
August | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.174279E+10 | 94452923.40 |
September | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.162003E+10 | 0.284643E+09 |
October | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.196392E+10 | 0.758265E+09 |
November | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.184192E+10 | 0.102612E+10 |
December | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.170530E+10 | 0.138693E+10 |
Annual Sum or Average | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.191599E+11 | 0.870089E+10 |
Minimum of Months | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.129538E+10 | 94452923.40 |
Maximum of Months | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.196392E+10 | 0.168676E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.441602E+10 | 0.486032E+10 |
February | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.408608E+10 | 0.366530E+10 |
March | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.468578E+10 | 0.260584E+10 |
April | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.391114E+10 | 0.196642E+10 |
May | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.357705E+10 | 0.123963E+10 |
June | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.378440E+10 | 0.698962E+09 |
July | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.410429E+10 | 0.453888E+09 |
August | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.488433E+10 | 0.368605E+09 |
September | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.450156E+10 | 0.964202E+09 |
October | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.546883E+10 | 0.233134E+10 |
November | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.512582E+10 | 0.305791E+10 |
December | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.474139E+10 | 0.404343E+10 |
Annual Sum or Average | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.532867E+11 | 0.262559E+11 |
Minimum of Months | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.357705E+10 | 0.368605E+09 |
Maximum of Months | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.546883E+10 | 0.486032E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.585520E+10 | 0.652579E+10 |
February | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.543805E+10 | 0.490323E+10 |
March | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.627283E+10 | 0.344266E+10 |
April | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.524223E+10 | 0.260910E+10 |
May | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.479326E+10 | 0.163292E+10 |
June | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.506638E+10 | 0.908709E+09 |
July | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.550632E+10 | 0.580001E+09 |
August | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.657374E+10 | 0.445744E+09 |
September | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.602786E+10 | 0.125015E+10 |
October | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.732461E+10 | 0.306775E+10 |
November | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.683946E+10 | 0.406637E+10 |
December | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.630742E+10 | 0.541777E+10 |
Annual Sum or Average | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.712474E+11 | 0.348502E+11 |
Minimum of Months | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.479326E+10 | 0.445744E+09 |
Maximum of Months | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.732461E+10 | 0.652579E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.314200E+09 | 0.343590E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.288749E+09 | 0.256237E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.326347E+09 | 0.177994E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.271612E+09 | 0.135508E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.247644E+09 | 80330446.75 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.272288E+09 | 35900719.98 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.301729E+09 | 18547376.51 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.362675E+09 | 9432933.82 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.321462E+09 | 53720358.15 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.386289E+09 | 0.153374E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.363797E+09 | 0.207270E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.337683E+09 | 0.280242E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.379447E+10 | 0.175215E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.247644E+09 | 9432933.82 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.386289E+09 | 0.343590E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.165807E+09 | 0.727994E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.228283E+09 | 0.532749E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.468611E+09 | 0.344669E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.605718E+09 | 0.248248E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.707166E+09 | 0.147576E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.830926E+09 | 66368960.42 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.852810E+09 | 34197694.87 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.845000E+09 | 17527517.37 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.568214E+09 | 0.100474E+09 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.420239E+09 | 0.302223E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.260388E+09 | 0.428307E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162989E+09 | 0.595266E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.611615E+10 | 0.354560E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162989E+09 | 17527517.37 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.852810E+09 | 0.727994E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7392885.65 | 0.412606E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 23910477.96 | 0.297108E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 61709874.58 | 0.186979E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.117766E+09 | 0.132464E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.186904E+09 | 74803050.27 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.262832E+09 | 32977956.64 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.278930E+09 | 17613369.96 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.258189E+09 | 8965522.66 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.142117E+09 | 52838524.72 |
October | 62833545.17 | 0.00 | 62833545.17 | 65644714.53 | 0.160238E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 33359656.26 | 0.228991E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 9345726.16 | 0.326738E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.144810E+10 | 0.193232E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7392885.65 | 8965522.66 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.278930E+09 | 0.412606E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.175352E+09 | 0.716424E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.238315E+09 | 0.523457E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.482180E+09 | 0.336187E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.612798E+09 | 0.244997E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.709655E+09 | 0.146500E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.831016E+09 | 66321068.53 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.853293E+09 | 34034766.14 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.848160E+09 | 17020735.01 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.574206E+09 | 97851052.22 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.434270E+09 | 0.293057E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.274778E+09 | 0.416273E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174828E+09 | 0.582298E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.620885E+10 | 0.347442E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174828E+09 | 17020735.01 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.853293E+09 | 0.716424E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.247269E+09 | 0.272559E+09 |
February | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.226701E+09 | 0.208279E+09 |
March | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.252249E+09 | 0.161165E+09 |
April | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.210627E+09 | 0.122512E+09 |
May | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.192858E+09 | 76416944.72 |
June | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.211918E+09 | 39002581.25 |
July | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.233947E+09 | 23582513.15 |
August | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.280793E+09 | 16240462.58 |
September | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.250227E+09 | 55946611.20 |
October | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.300550E+09 | 0.142409E+09 |
November | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.278874E+09 | 0.190295E+09 |
December | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.260579E+09 | 0.238305E+09 |
Annual Sum or Average | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.294659E+10 | 0.154671E+10 |
Minimum of Months | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.192858E+09 | 16240462.58 |
Maximum of Months | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.300550E+09 | 0.272559E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42076451.99 | 0.00 | 42076451.99 | 5421408.67 | 0.344995E+09 |
February | 42124339.93 | 0.00 | 42124339.93 | 19294008.35 | 0.247030E+09 |
March | 65492691.15 | 1318.99 | 65491372.16 | 52427841.94 | 0.150002E+09 |
April | 76848851.72 | 448829.91 | 76400021.81 | 0.100647E+09 | 0.103723E+09 |
May | 94747450.04 | 2971603.27 | 91775846.77 | 0.158767E+09 | 56784623.29 |
June | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.221881E+09 | 23244921.56 |
July | 98689421.90 | 5056973.36 | 93632448.53 | 0.236036E+09 | 11664315.23 |
August | 87654522.95 | 1029768.70 | 86624754.24 | 0.221140E+09 | 5065206.55 |
September | 64031230.67 | 25170.94 | 64006059.72 | 0.122367E+09 | 39473164.15 |
October | 50273499.29 | 0.00 | 50273499.29 | 56063803.84 | 0.128676E+09 |
November | 43541540.27 | 0.00 | 43541540.27 | 26860538.01 | 0.188971E+09 |
December | 38896548.34 | 0.00 | 38896548.34 | 6497326.46 | 0.274127E+09 |
Annual Sum or Average | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.122740E+10 | 0.157376E+10 |
Minimum of Months | 38896548.34 | 0.00 | 38896548.34 | 5421408.67 | 5065206.55 |
Maximum of Months | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.236036E+09 | 0.344995E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.138090E+09 | 0.706526E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.227523E+09 | 0.503425E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.393703E+09 | 0.317884E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.576988E+09 | 0.227932E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.741909E+09 | 0.135393E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.860836E+09 | 59925051.69 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.910491E+09 | 32753216.44 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.856891E+09 | 16189680.83 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.574753E+09 | 94956872.13 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.391239E+09 | 0.280134E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.222802E+09 | 0.392957E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.139016E+09 | 0.558533E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.603424E+10 | 0.332661E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.138090E+09 | 16189680.83 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.910491E+09 | 0.706526E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.312682E+09 | 0.342734E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.286458E+09 | 0.255397E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.324626E+09 | 0.175124E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.268916E+09 | 0.133248E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.244110E+09 | 79226561.53 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.268475E+09 | 35410904.15 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.298234E+09 | 18465619.16 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.360861E+09 | 9136385.12 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.319236E+09 | 52922007.01 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.384574E+09 | 0.151180E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.362578E+09 | 0.205595E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.336236E+09 | 0.279531E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.376698E+10 | 0.173797E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.244110E+09 | 9136385.12 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.384574E+09 | 0.342734E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7030130.15 | 0.412622E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 23025871.87 | 0.297380E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 60844229.57 | 0.184699E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.115090E+09 | 0.130748E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.183014E+09 | 73747125.09 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.258806E+09 | 32373588.82 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.275330E+09 | 17531497.14 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.256238E+09 | 8653655.62 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.139541E+09 | 52238929.04 |
October | 62833545.17 | 0.00 | 62833545.17 | 63706496.43 | 0.158443E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 32992211.17 | 0.227426E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 8994560.56 | 0.326870E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.142461E+10 | 0.192273E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7030130.15 | 8653655.62 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.275330E+09 | 0.412622E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.143295E+09 | 0.690176E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.236000E+09 | 0.492267E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.406498E+09 | 0.308477E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.582934E+09 | 0.224583E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.743855E+09 | 0.134392E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.860904E+09 | 59874352.67 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.910990E+09 | 32606282.04 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.859983E+09 | 15725422.12 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.580014E+09 | 92529473.69 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.403772E+09 | 0.270564E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.236386E+09 | 0.379071E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.147248E+09 | 0.541561E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.611188E+10 | 0.324183E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.143295E+09 | 15725422.12 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.910990E+09 | 0.690176E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 7982409.95 | 0.565984E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 29728419.94 | 0.402001E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 83630827.41 | 0.239248E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.162801E+09 | 0.164495E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.256858E+09 | 92119203.85 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.347026E+09 | 45450924.27 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.361656E+09 | 27526851.44 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.332465E+09 | 16635902.14 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.190275E+09 | 70051177.85 |
October | 79574720.39 | 0.00 | 79574720.39 | 89073945.40 | 0.206203E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 41598809.64 | 0.303351E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 8955615.37 | 0.447343E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.191205E+10 | 0.258041E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 7982409.95 | 16635902.14 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.361656E+09 | 0.565984E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24551567.91 | 0.00 | 24551567.91 | 2942646.83 | 0.208645E+09 |
February | 24579510.47 | 0.00 | 24579510.47 | 10959126.55 | 0.148194E+09 |
March | 38214920.19 | 769.63 | 38214150.56 | 30829785.86 | 88196742.05 |
April | 44841228.59 | 261891.81 | 44579336.78 | 60015338.99 | 60639702.84 |
May | 55285042.92 | 1733927.56 | 53551115.36 | 94688669.03 | 33958952.90 |
June | 58842496.02 | 3858865.82 | 54983630.20 | 0.127928E+09 | 16755092.66 |
July | 57585179.58 | 2950738.93 | 54634440.65 | 0.133322E+09 | 10147537.24 |
August | 51146327.01 | 600869.02 | 50545457.99 | 0.122560E+09 | 6132682.37 |
September | 37362159.44 | 14687.22 | 37347472.22 | 70143426.78 | 25823764.75 |
October | 29334536.86 | 0.00 | 29334536.86 | 32836344.54 | 76015049.48 |
November | 25406445.47 | 0.00 | 25406445.47 | 15335043.71 | 0.111828E+09 |
December | 22696097.29 | 0.00 | 22696097.29 | 3301410.65 | 0.164909E+09 |
Annual Sum or Average | 0.469846E+09 | 9421749.97 | 0.460424E+09 | 0.704862E+09 | 0.951246E+09 |
Minimum of Months | 22696097.29 | 0.00 | 22696097.29 | 2942646.83 | 6132682.37 |
Maximum of Months | 58842496.02 | 3858865.82 | 54983630.20 | 0.133322E+09 | 0.208645E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130282E+09 | 90503082.87 | 39778691.28 | 0.144497E+09 | 0.169023E+09 |
February | 0.109615E+09 | 73128454.63 | 36486217.96 | 0.134982E+09 | 0.124564E+09 |
March | 0.110976E+09 | 58234705.39 | 52740862.99 | 0.157616E+09 | 81926162.60 |
April | 80823152.87 | 26965191.36 | 53857961.51 | 0.133211E+09 | 61025548.85 |
May | 67134435.80 | 8215580.81 | 58918854.99 | 0.123224E+09 | 35961621.08 |
June | 59654024.21 | 3330445.64 | 56323578.57 | 0.132178E+09 | 18106952.03 |
July | 61834899.83 | 4170846.82 | 57664053.01 | 0.143938E+09 | 10563706.32 |
August | 74508055.00 | 14002973.25 | 60505081.75 | 0.171860E+09 | 6216723.16 |
September | 81405849.48 | 31674060.78 | 49731788.71 | 0.155081E+09 | 25594783.50 |
October | 0.118119E+09 | 76345167.07 | 41774144.65 | 0.186159E+09 | 70759665.76 |
November | 0.124888E+09 | 83337782.51 | 41549955.12 | 0.172661E+09 | 97914627.98 |
December | 0.129365E+09 | 91003310.47 | 38361315.54 | 0.156756E+09 | 0.136710E+09 |
Annual Sum or Average | 0.114860E+10 | 0.560912E+09 | 0.587693E+09 | 0.181216E+10 | 0.838367E+09 |
Minimum of Months | 59654024.21 | 3330445.64 | 36486217.96 | 0.123224E+09 | 6216723.16 |
Maximum of Months | 0.130282E+09 | 91003310.47 | 60505081.75 | 0.186159E+09 | 0.169023E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353611E+09 | 0.245644E+09 | 0.107968E+09 | 0.392193E+09 | 0.458763E+09 |
February | 0.297517E+09 | 0.198486E+09 | 99031058.63 | 0.366369E+09 | 0.338092E+09 |
March | 0.301210E+09 | 0.158061E+09 | 0.143149E+09 | 0.427803E+09 | 0.222364E+09 |
April | 0.219371E+09 | 73189044.97 | 0.146182E+09 | 0.361561E+09 | 0.165636E+09 |
May | 0.182217E+09 | 22298766.77 | 0.159918E+09 | 0.334454E+09 | 97607195.40 |
June | 0.161913E+09 | 9039510.68 | 0.152874E+09 | 0.358757E+09 | 49145971.52 |
July | 0.167833E+09 | 11320531.40 | 0.156512E+09 | 0.390677E+09 | 28672059.71 |
August | 0.202230E+09 | 38006933.66 | 0.164223E+09 | 0.466464E+09 | 16873455.86 |
September | 0.220952E+09 | 85969879.73 | 0.134982E+09 | 0.420921E+09 | 69469477.71 |
October | 0.320600E+09 | 0.207216E+09 | 0.113384E+09 | 0.505274E+09 | 0.192056E+09 |
November | 0.338971E+09 | 0.226196E+09 | 0.112775E+09 | 0.468638E+09 | 0.265760E+09 |
December | 0.351122E+09 | 0.247002E+09 | 0.104120E+09 | 0.425468E+09 | 0.371059E+09 |
Annual Sum or Average | 0.311755E+10 | 0.152243E+10 | 0.159512E+10 | 0.491858E+10 | 0.227550E+10 |
Minimum of Months | 0.161913E+09 | 9039510.68 | 99031058.63 | 0.334454E+09 | 16873455.86 |
Maximum of Months | 0.353611E+09 | 0.247002E+09 | 0.164223E+09 | 0.505274E+09 | 0.458763E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.312556E+09 | 0.342449E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.286365E+09 | 0.255622E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.321769E+09 | 0.178316E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.266828E+09 | 0.136985E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.242565E+09 | 81691655.49 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.268988E+09 | 35500437.62 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.298505E+09 | 18032067.26 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.359140E+09 | 8817432.82 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.317722E+09 | 53411452.38 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.381753E+09 | 0.153824E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.361108E+09 | 0.206275E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.335798E+09 | 0.278580E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.375310E+10 | 0.174950E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.242565E+09 | 8817432.82 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.381753E+09 | 0.342449E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.165163E+09 | 0.726302E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.225762E+09 | 0.531166E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.460430E+09 | 0.344603E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.595197E+09 | 0.250424E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.695158E+09 | 0.149552E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.821228E+09 | 65409899.05 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.844455E+09 | 33153219.01 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.836868E+09 | 16381314.15 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.561192E+09 | 99676523.09 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.413284E+09 | 0.302629E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.257348E+09 | 0.426306E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162330E+09 | 0.591751E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.603841E+10 | 0.353735E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162330E+09 | 16381314.15 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.844455E+09 | 0.726302E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7626132.37 | 0.412209E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 24039907.73 | 0.296382E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 60560577.44 | 0.186771E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.114657E+09 | 0.133819E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.182278E+09 | 76136411.57 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.259683E+09 | 32671485.99 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.275968E+09 | 17264641.41 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.255633E+09 | 8380667.01 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.139938E+09 | 52369344.87 |
October | 62833545.17 | 0.00 | 62833545.17 | 64603398.19 | 0.159969E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 33731950.43 | 0.227267E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 9947032.43 | 0.324613E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.142867E+10 | 0.192785E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7626132.37 | 8380667.01 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.275968E+09 | 0.412209E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.174593E+09 | 0.715660E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.236213E+09 | 0.521720E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.475352E+09 | 0.335051E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.602345E+09 | 0.246979E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.697478E+09 | 0.148416E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.821278E+09 | 65370367.92 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.844928E+09 | 32996190.08 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.840103E+09 | 15879639.66 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.567282E+09 | 96844731.33 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.428598E+09 | 0.292023E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.273338E+09 | 0.412957E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.175114E+09 | 0.579029E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.613662E+10 | 0.346292E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174593E+09 | 15879639.66 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.844928E+09 | 0.715660E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.435816E+09 | 0.524429E+09 |
February | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.404499E+09 | 0.391464E+09 |
March | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.463400E+09 | 0.267944E+09 |
April | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.392067E+09 | 0.198054E+09 |
May | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.363076E+09 | 0.114528E+09 |
June | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.405734E+09 | 47960011.78 |
July | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.449919E+09 | 24034660.14 |
August | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.537716E+09 | 11288265.07 |
September | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.467916E+09 | 77791061.04 |
October | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.551671E+09 | 0.233830E+09 |
November | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.513293E+09 | 0.319186E+09 |
December | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.470197E+09 | 0.430163E+09 |
Annual Sum or Average | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.545530E+10 | 0.264067E+10 |
Minimum of Months | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.363076E+09 | 11288265.07 |
Maximum of Months | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.551671E+09 | 0.524429E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 33933746.45 | 0.339474E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.133515E+09 | 0.248806E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.365380E+09 | 0.161739E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.757093E+09 | 0.114714E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.122782E+10 | 0.705949E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.172678E+10 | 0.377177E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.181450E+10 | 0.253728E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.166294E+10 | 0.193707E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.921791E+09 | 0.553573E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.404193E+09 | 0.141494E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.175315E+09 | 0.196178E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 34567714.36 | 0.277294E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.925783E+10 | 0.168811E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 33933746.45 | 0.193707E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.181450E+10 | 0.339474E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 29517777.04 | 0.348429E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.121866E+09 | 0.256749E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.333351E+09 | 0.169111E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.715750E+09 | 0.119867E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.117978E+10 | 0.740756E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.168501E+10 | 0.397673E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.177505E+10 | 0.271610E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.162529E+10 | 0.210896E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.883467E+09 | 0.589711E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.374573E+09 | 0.148628E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.153635E+09 | 0.204284E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 28986607.16 | 0.287111E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.890627E+10 | 0.175525E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 28986607.16 | 0.210896E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.177505E+10 | 0.348429E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 4535703.84 | 0.494583E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 18867955.48 | 0.362855E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 54893945.27 | 0.232087E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.121412E+09 | 0.161481E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.200461E+09 | 99933128.68 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.278765E+09 | 54699577.85 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.297477E+09 | 36348489.64 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.274804E+09 | 27505773.35 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.152734E+09 | 74702595.66 |
October | 62833545.17 | 0.00 | 62833545.17 | 64170840.85 | 0.200762E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 26250241.21 | 0.280788E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 4664200.05 | 0.403563E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.149904E+10 | 0.242931E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 4535703.84 | 27505773.35 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.297477E+09 | 0.494583E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434507E+09 | 0.197839E+09 | 0.236668E+09 | 0.253794E+09 | 0.165790E+10 |
February | 0.492555E+09 | 0.265149E+09 | 0.227406E+09 | 0.439051E+09 | 0.120957E+10 |
March | 0.686097E+09 | 0.312962E+09 | 0.373136E+09 | 0.784714E+09 | 0.782534E+09 |
April | 0.802608E+09 | 0.366340E+09 | 0.436268E+09 | 0.118990E+10 | 0.560881E+09 |
May | 0.908547E+09 | 0.384217E+09 | 0.524331E+09 | 0.155247E+10 | 0.366726E+09 |
June | 0.909412E+09 | 0.380907E+09 | 0.528506E+09 | 0.180190E+10 | 0.203436E+09 |
July | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.190174E+10 | 0.137147E+09 |
August | 0.839504E+09 | 0.333007E+09 | 0.506497E+09 | 0.178467E+10 | 0.103662E+09 |
September | 0.665833E+09 | 0.294206E+09 | 0.371628E+09 | 0.121366E+10 | 0.271877E+09 |
October | 0.588469E+09 | 0.306304E+09 | 0.282165E+09 | 0.807050E+09 | 0.690588E+09 |
November | 0.453550E+09 | 0.204592E+09 | 0.248958E+09 | 0.436423E+09 | 0.935978E+09 |
December | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.254731E+09 | 0.133862E+10 |
Annual Sum or Average | 0.810373E+10 | 0.361493E+10 | 0.448879E+10 | 0.124201E+11 | 0.825892E+10 |
Minimum of Months | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.253794E+09 | 0.103662E+09 |
Maximum of Months | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.190174E+10 | 0.165790E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.300263E+09 | 0.397306E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.279568E+09 | 0.303564E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.325113E+09 | 0.213869E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.278451E+09 | 0.161396E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.262972E+09 | 0.104012E+09 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.289349E+09 | 57700434.08 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.319788E+09 | 37197216.15 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.380416E+09 | 27670189.60 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.336978E+09 | 73561636.21 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.393165E+09 | 0.185230E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.362189E+09 | 0.243960E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.326608E+09 | 0.330783E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.385486E+10 | 0.213625E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.262972E+09 | 27670189.60 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.393165E+09 | 0.397306E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 7228125.54 | 0.577623E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 27390279.76 | 0.411000E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 76914756.48 | 0.245940E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.153673E+09 | 0.168998E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.243770E+09 | 97205846.61 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.329819E+09 | 51059922.92 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.341187E+09 | 32611898.42 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.310940E+09 | 22605570.76 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.181496E+09 | 72575897.90 |
October | 79574720.39 | 0.00 | 79574720.39 | 82978430.54 | 0.211432E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 37577897.47 | 0.311118E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 7641385.53 | 0.458125E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.180062E+10 | 0.266030E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 7228125.54 | 22605570.76 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.341187E+09 | 0.577623E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59587394.23 | 0.00 | 59587394.23 | 6467031.31 | 0.516793E+09 |
February | 59655211.68 | 0.00 | 59655211.68 | 24506187.08 | 0.367724E+09 |
March | 92748761.43 | 1867.91 | 92746893.52 | 68815924.05 | 0.220043E+09 |
April | 0.108831E+09 | 635619.29 | 0.108195E+09 | 0.137492E+09 | 0.151203E+09 |
May | 0.134178E+09 | 4208294.36 | 0.129970E+09 | 0.218102E+09 | 86970439.27 |
June | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.295090E+09 | 45683506.50 |
July | 0.139761E+09 | 7161532.19 | 0.132599E+09 | 0.305262E+09 | 29177989.08 |
August | 0.124134E+09 | 1458327.18 | 0.122675E+09 | 0.278199E+09 | 20225289.81 |
September | 90679085.44 | 35646.33 | 90643439.12 | 0.162385E+09 | 64933930.84 |
October | 71195803.84 | 0.00 | 71195803.84 | 74241116.20 | 0.189169E+09 |
November | 61662207.79 | 0.00 | 61662207.79 | 33621087.25 | 0.278356E+09 |
December | 55084111.20 | 0.00 | 55084111.20 | 6836776.58 | 0.409871E+09 |
Annual Sum or Average | 0.114033E+10 | 22866870.75 | 0.111746E+10 | 0.161102E+10 | 0.238015E+10 |
Minimum of Months | 55084111.20 | 0.00 | 55084111.20 | 6467031.31 | 20225289.81 |
Maximum of Months | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.305262E+09 | 0.516793E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104240E+10 | 0.724128E+09 | 0.318275E+09 | 0.113232E+10 | 0.137368E+10 |
February | 0.877042E+09 | 0.585111E+09 | 0.291931E+09 | 0.105652E+10 | 0.101724E+10 |
March | 0.887931E+09 | 0.465944E+09 | 0.421987E+09 | 0.122711E+10 | 0.672711E+09 |
April | 0.646677E+09 | 0.215752E+09 | 0.430925E+09 | 0.103192E+10 | 0.502634E+09 |
May | 0.537152E+09 | 65733982.34 | 0.471418E+09 | 0.945057E+09 | 0.304479E+09 |
June | 0.477300E+09 | 26647349.68 | 0.450653E+09 | 0.100652E+10 | 0.162958E+09 |
July | 0.494749E+09 | 33371514.17 | 0.461378E+09 | 0.109073E+10 | 0.100939E+09 |
August | 0.596149E+09 | 0.112040E+09 | 0.484109E+09 | 0.130791E+10 | 68370988.63 |
September | 0.651339E+09 | 0.253428E+09 | 0.397911E+09 | 0.120894E+10 | 0.213395E+09 |
October | 0.945089E+09 | 0.610848E+09 | 0.334241E+09 | 0.145831E+10 | 0.580060E+09 |
November | 0.999244E+09 | 0.666797E+09 | 0.332447E+09 | 0.135441E+10 | 0.800852E+09 |
December | 0.103506E+10 | 0.728130E+09 | 0.306934E+09 | 0.122875E+10 | 0.111556E+10 |
Annual Sum or Average | 0.919014E+10 | 0.448793E+10 | 0.470221E+10 | 0.140485E+11 | 0.691288E+10 |
Minimum of Months | 0.477300E+09 | 26647349.68 | 0.291931E+09 | 0.945057E+09 | 68370988.63 |
Maximum of Months | 0.104240E+10 | 0.728130E+09 | 0.484109E+09 | 0.145831E+10 | 0.137368E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 592.97 | 629.76 | 527.26 | 366.27 | 160.99 | 0.00 | 0.00 |
February | 607.31 | 518.81 | 491.15 | 327.66 | 163.48 | 0.00 | 0.00 |
March | 630.07 | 321.68 | 449.12 | 235.68 | 213.44 | 0.00 | 0.00 |
April | 544.24 | 247.45 | 338.00 | 112.77 | 225.23 | 0.00 | 0.00 |
May | 483.64 | 142.13 | 271.69 | 33.25 | 238.45 | 0.00 | 0.00 |
June | 526.03 | 78.21 | 249.47 | 13.93 | 235.54 | 0.00 | 0.00 |
July | 549.35 | 45.65 | 250.25 | 16.88 | 233.37 | 0.00 | 0.00 |
August | 650.68 | 35.26 | 301.54 | 56.67 | 244.87 | 0.00 | 0.00 |
September | 625.01 | 109.82 | 340.43 | 132.46 | 207.97 | 0.00 | 0.00 |
October | 733.25 | 283.10 | 478.03 | 308.97 | 169.06 | 0.00 | 0.00 |
November | 710.62 | 395.88 | 522.27 | 348.52 | 173.76 | 0.00 | 0.00 |
December | 636.69 | 517.82 | 523.54 | 368.30 | 155.25 | 0.00 | 0.00 |
Annual Sum or Average | 607.56 | 275.90 | 394.80 | 192.80 | 202.00 | 0.00 | 0.00 |
Minimum of Months | 483.64 | 35.26 | 249.47 | 13.93 | 155.25 | 0.00 | 0.00 |
Maximum of Months | 733.25 | 629.76 | 527.26 | 368.30 | 244.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1648.75 | 1814.64 | 1484.72 | 1031.40 | 453.32 | 0.00 | 0.00 |
February | 1689.02 | 1515.09 | 1383.03 | 922.68 | 460.35 | 0.00 | 0.00 |
March | 1749.47 | 972.91 | 1264.70 | 663.66 | 601.04 | 0.00 | 0.00 |
April | 1508.93 | 758.65 | 951.78 | 317.55 | 634.23 | 0.00 | 0.00 |
May | 1335.52 | 462.83 | 765.07 | 93.63 | 671.45 | 0.00 | 0.00 |
June | 1460.03 | 269.66 | 702.49 | 39.22 | 663.27 | 0.00 | 0.00 |
July | 1532.37 | 169.46 | 704.68 | 47.53 | 657.15 | 0.00 | 0.00 |
August | 1823.60 | 137.62 | 849.11 | 159.58 | 689.52 | 0.00 | 0.00 |
September | 1736.71 | 371.99 | 958.64 | 373.00 | 585.64 | 0.00 | 0.00 |
October | 2041.83 | 870.42 | 1346.11 | 870.05 | 476.06 | 0.00 | 0.00 |
November | 1977.55 | 1179.75 | 1470.69 | 981.40 | 489.29 | 0.00 | 0.00 |
December | 1770.23 | 1509.64 | 1474.27 | 1037.10 | 437.17 | 0.00 | 0.00 |
Annual Sum or Average | 1689.71 | 832.57 | 1111.73 | 542.91 | 568.82 | 0.00 | 0.00 |
Minimum of Months | 1335.52 | 137.62 | 702.49 | 39.22 | 437.17 | 0.00 | 0.00 |
Maximum of Months | 2041.83 | 1814.64 | 1484.72 | 1037.10 | 689.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2186.08 | 2436.45 | 1928.74 | 1339.84 | 588.89 | 0.00 | 0.00 |
February | 2247.87 | 2026.80 | 1796.64 | 1198.62 | 598.02 | 0.00 | 0.00 |
March | 2342.01 | 1285.34 | 1642.92 | 862.13 | 780.79 | 0.00 | 0.00 |
April | 2022.46 | 1006.60 | 1236.41 | 412.51 | 823.90 | 0.00 | 0.00 |
May | 1789.60 | 609.66 | 993.87 | 121.63 | 872.25 | 0.00 | 0.00 |
June | 1954.62 | 350.58 | 912.57 | 50.95 | 861.62 | 0.00 | 0.00 |
July | 2055.82 | 216.55 | 915.42 | 61.75 | 853.67 | 0.00 | 0.00 |
August | 2454.35 | 166.42 | 1103.04 | 207.31 | 895.73 | 0.00 | 0.00 |
September | 2325.56 | 482.31 | 1245.33 | 484.54 | 760.78 | 0.00 | 0.00 |
October | 2734.70 | 1145.37 | 1748.68 | 1130.24 | 618.43 | 0.00 | 0.00 |
November | 2638.68 | 1568.81 | 1910.51 | 1274.89 | 635.62 | 0.00 | 0.00 |
December | 2354.92 | 2022.76 | 1915.16 | 1347.25 | 567.91 | 0.00 | 0.00 |
Annual Sum or Average | 2259.24 | 1105.09 | 1444.20 | 705.27 | 738.93 | 0.00 | 0.00 |
Minimum of Months | 1789.60 | 166.42 | 912.57 | 50.95 | 567.91 | 0.00 | 0.00 |
Maximum of Months | 2734.70 | 2436.45 | 1928.74 | 1347.25 | 895.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.15 | 380.02 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 198.83 | 311.25 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 292.56 | 190.89 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 336.81 | 146.39 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 356.09 | 84.69 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 425.54 | 39.37 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 431.03 | 19.67 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 450.89 | 10.06 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 343.05 | 59.30 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 297.79 | 166.76 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 232.10 | 236.49 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 170.52 | 310.47 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 308.47 | 162.19 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 159.15 | 10.06 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 450.89 | 380.02 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.74 | 413.04 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 102.50 | 333.30 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 200.97 | 193.24 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 280.80 | 144.57 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 334.11 | 81.99 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 421.22 | 37.52 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 422.37 | 18.93 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 412.99 | 9.63 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 276.25 | 58.03 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 185.45 | 168.04 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 117.07 | 247.13 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 64.50 | 335.13 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 240.59 | 169.23 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 59.74 | 9.63 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 422.37 | 413.04 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.32 | 101.76 | 83.38 | 57.92 | 25.46 | 0.00 | 0.00 |
February | 93.71 | 86.09 | 77.67 | 51.82 | 25.85 | 0.00 | 0.00 |
March | 94.18 | 60.17 | 71.03 | 37.27 | 33.75 | 0.00 | 0.00 |
April | 81.26 | 47.27 | 53.45 | 17.83 | 35.62 | 0.00 | 0.00 |
May | 72.01 | 28.53 | 42.97 | 5.26 | 37.71 | 0.00 | 0.00 |
June | 81.76 | 15.05 | 39.45 | 2.20 | 37.25 | 0.00 | 0.00 |
July | 87.35 | 8.80 | 39.57 | 2.67 | 36.91 | 0.00 | 0.00 |
August | 104.84 | 6.06 | 47.69 | 8.96 | 38.72 | 0.00 | 0.00 |
September | 96.54 | 21.58 | 53.84 | 20.95 | 32.89 | 0.00 | 0.00 |
October | 112.21 | 53.17 | 75.60 | 48.86 | 26.74 | 0.00 | 0.00 |
November | 107.59 | 73.42 | 82.59 | 55.11 | 27.48 | 0.00 | 0.00 |
December | 97.29 | 88.97 | 82.79 | 58.24 | 24.55 | 0.00 | 0.00 |
Annual Sum or Average | 93.44 | 49.05 | 62.43 | 30.49 | 31.95 | 0.00 | 0.00 |
Minimum of Months | 72.01 | 6.06 | 39.45 | 2.20 | 24.55 | 0.00 | 0.00 |
Maximum of Months | 112.21 | 101.76 | 83.38 | 58.24 | 38.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.02 | 128.81 | 15.71 | 0.00 | 15.71 | 0.00 | 0.00 |
February | 7.98 | 102.11 | 17.41 | 0.00 | 17.41 | 0.00 | 0.00 |
March | 19.57 | 56.00 | 24.45 | 0.00 | 24.45 | 0.00 | 0.00 |
April | 38.83 | 40.02 | 29.65 | 0.17 | 29.48 | 0.00 | 0.00 |
May | 59.28 | 21.20 | 35.37 | 1.11 | 34.27 | 0.00 | 0.00 |
June | 85.60 | 8.97 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
July | 88.13 | 4.35 | 36.85 | 1.89 | 34.96 | 0.00 | 0.00 |
August | 82.56 | 1.89 | 32.73 | 0.38 | 32.34 | 0.00 | 0.00 |
September | 47.21 | 15.23 | 24.70 | 0.01 | 24.69 | 0.00 | 0.00 |
October | 20.93 | 48.04 | 18.77 | 0.00 | 18.77 | 0.00 | 0.00 |
November | 10.36 | 72.91 | 16.80 | 0.00 | 16.80 | 0.00 | 0.00 |
December | 2.43 | 102.35 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Annual Sum or Average | 38.92 | 49.90 | 25.53 | 0.51 | 25.02 | 0.00 | 0.00 |
Minimum of Months | 2.02 | 1.89 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Maximum of Months | 88.13 | 128.81 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.93 | 374.38 | 185.37 | 109.35 | 76.01 | 0.00 | 0.00 |
February | 202.64 | 303.85 | 198.92 | 119.59 | 79.33 | 0.00 | 0.00 |
March | 264.81 | 180.69 | 216.89 | 105.03 | 111.86 | 0.00 | 0.00 |
April | 322.56 | 135.55 | 221.66 | 92.97 | 128.69 | 0.00 | 0.00 |
May | 366.09 | 78.09 | 223.34 | 78.30 | 145.03 | 0.00 | 0.00 |
June | 434.57 | 35.66 | 224.76 | 76.24 | 148.53 | 0.00 | 0.00 |
July | 450.97 | 18.81 | 220.48 | 75.08 | 145.40 | 0.00 | 0.00 |
August | 454.50 | 9.30 | 216.35 | 73.37 | 142.97 | 0.00 | 0.00 |
September | 344.20 | 56.35 | 195.76 | 82.95 | 112.81 | 0.00 | 0.00 |
October | 287.63 | 159.01 | 204.38 | 118.27 | 86.10 | 0.00 | 0.00 |
November | 222.43 | 227.51 | 190.76 | 108.38 | 82.38 | 0.00 | 0.00 |
December | 167.63 | 303.09 | 179.44 | 107.38 | 72.06 | 0.00 | 0.00 |
Annual Sum or Average | 306.32 | 156.12 | 206.55 | 95.44 | 111.11 | 0.00 | 0.00 |
Minimum of Months | 150.93 | 9.30 | 179.44 | 73.37 | 72.06 | 0.00 | 0.00 |
Maximum of Months | 454.50 | 374.38 | 224.76 | 119.59 | 148.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.21 | 399.82 | 100.75 | 36.93 | 63.82 | 0.00 | 0.00 |
February | 95.36 | 314.70 | 123.57 | 54.80 | 68.77 | 0.00 | 0.00 |
March | 168.30 | 177.95 | 158.65 | 58.43 | 100.22 | 0.00 | 0.00 |
April | 265.52 | 133.31 | 191.89 | 70.89 | 121.00 | 0.00 | 0.00 |
May | 345.31 | 76.97 | 213.83 | 73.12 | 140.71 | 0.00 | 0.00 |
June | 431.84 | 35.44 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
July | 442.91 | 18.70 | 217.05 | 74.10 | 142.95 | 0.00 | 0.00 |
August | 416.72 | 9.07 | 197.63 | 62.65 | 134.98 | 0.00 | 0.00 |
September | 276.77 | 55.01 | 159.32 | 56.77 | 102.56 | 0.00 | 0.00 |
October | 169.97 | 155.60 | 133.32 | 57.18 | 76.14 | 0.00 | 0.00 |
November | 96.58 | 226.64 | 108.49 | 39.47 | 69.02 | 0.00 | 0.00 |
December | 47.63 | 313.53 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 234.19 | 158.97 | 160.41 | 57.96 | 102.45 | 0.00 | 0.00 |
Minimum of Months | 44.21 | 9.07 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 442.91 | 399.82 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.04 | 487.19 | 214.70 | 125.50 | 89.19 | 0.00 | 0.00 |
February | 200.57 | 395.18 | 206.01 | 112.27 | 93.74 | 0.00 | 0.00 |
March | 257.14 | 231.69 | 206.86 | 80.76 | 126.11 | 0.00 | 0.00 |
April | 276.39 | 173.85 | 180.04 | 39.01 | 141.03 | 0.00 | 0.00 |
May | 301.40 | 96.21 | 169.73 | 13.80 | 155.93 | 0.00 | 0.00 |
June | 371.67 | 48.97 | 169.76 | 10.30 | 159.46 | 0.00 | 0.00 |
July | 383.99 | 28.30 | 165.57 | 9.87 | 155.70 | 0.00 | 0.00 |
August | 408.13 | 17.04 | 174.22 | 20.25 | 153.97 | 0.00 | 0.00 |
September | 322.61 | 73.58 | 170.17 | 45.41 | 124.76 | 0.00 | 0.00 |
October | 299.76 | 199.59 | 204.46 | 105.87 | 98.59 | 0.00 | 0.00 |
November | 257.50 | 288.60 | 215.35 | 119.42 | 95.93 | 0.00 | 0.00 |
December | 196.37 | 392.59 | 210.85 | 126.20 | 84.66 | 0.00 | 0.00 |
Annual Sum or Average | 287.45 | 201.77 | 190.59 | 67.17 | 123.42 | 0.00 | 0.00 |
Minimum of Months | 168.04 | 17.04 | 165.57 | 9.87 | 84.66 | 0.00 | 0.00 |
Maximum of Months | 408.13 | 487.19 | 215.35 | 126.20 | 159.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.52 | 379.19 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 196.95 | 310.49 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 287.78 | 190.97 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 330.79 | 147.68 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 349.63 | 85.86 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 420.51 | 38.83 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 426.71 | 19.09 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 446.53 | 9.40 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 338.88 | 58.85 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 293.47 | 167.06 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 230.08 | 235.53 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 169.84 | 308.80 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 304.74 | 161.90 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 158.52 | 9.40 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 446.53 | 379.19 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.74 | 412.80 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 101.76 | 332.36 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 197.93 | 192.67 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 275.45 | 145.75 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 327.82 | 83.20 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 416.29 | 37.08 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 418.18 | 18.45 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 409.03 | 8.99 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 272.72 | 57.44 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 182.87 | 167.49 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 116.71 | 245.24 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 65.04 | 333.33 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 237.71 | 168.76 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 59.74 | 8.99 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 418.18 | 412.80 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 162.72 | 195.80 | 152.89 | 106.21 | 46.68 | 0.00 | 0.00 |
February | 167.20 | 161.82 | 142.42 | 95.01 | 47.41 | 0.00 | 0.00 |
March | 173.01 | 100.04 | 130.23 | 68.34 | 61.89 | 0.00 | 0.00 |
April | 151.26 | 76.41 | 98.01 | 32.70 | 65.31 | 0.00 | 0.00 |
May | 135.56 | 42.76 | 78.78 | 9.64 | 69.14 | 0.00 | 0.00 |
June | 156.53 | 18.50 | 72.34 | 4.04 | 68.30 | 0.00 | 0.00 |
July | 167.98 | 8.97 | 72.57 | 4.89 | 67.67 | 0.00 | 0.00 |
August | 200.76 | 4.21 | 87.44 | 16.43 | 71.00 | 0.00 | 0.00 |
September | 180.52 | 30.01 | 98.72 | 38.41 | 60.31 | 0.00 | 0.00 |
October | 205.97 | 87.30 | 138.62 | 89.59 | 49.02 | 0.00 | 0.00 |
November | 198.03 | 123.14 | 151.44 | 101.06 | 50.39 | 0.00 | 0.00 |
December | 175.55 | 160.60 | 151.81 | 106.80 | 45.02 | 0.00 | 0.00 |
Annual Sum or Average | 172.99 | 83.74 | 114.48 | 55.91 | 58.58 | 0.00 | 0.00 |
Minimum of Months | 135.56 | 4.21 | 72.34 | 4.04 | 45.02 | 0.00 | 0.00 |
Maximum of Months | 205.97 | 195.80 | 152.89 | 106.80 | 71.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.67 | 1267.45 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 55.19 | 1028.46 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 136.42 | 603.86 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 292.09 | 442.57 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 458.42 | 263.57 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 666.20 | 145.52 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 677.46 | 94.73 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 620.87 | 72.32 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 355.63 | 213.57 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 150.91 | 528.28 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 67.64 | 756.86 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 12.91 | 1035.30 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 293.56 | 535.30 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 12.67 | 72.32 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 677.46 | 1267.45 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.02 | 1300.89 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 50.37 | 1061.30 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 124.46 | 631.39 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 276.14 | 462.45 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 440.48 | 276.57 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 650.08 | 153.42 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 662.73 | 101.41 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 606.81 | 78.74 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 340.84 | 227.51 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 139.85 | 554.91 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 59.27 | 788.13 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 10.82 | 1071.95 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 282.42 | 556.58 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 10.82 | 78.74 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 662.73 | 1300.89 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.31 | 893.73 | 286.11 | 146.28 | 139.83 | 0.00 | 0.00 |
February | 267.15 | 737.76 | 322.47 | 174.39 | 148.09 | 0.00 | 0.00 |
March | 422.72 | 446.53 | 375.52 | 163.44 | 212.08 | 0.00 | 0.00 |
April | 604.81 | 332.43 | 413.53 | 163.85 | 249.68 | 0.00 | 0.00 |
May | 749.85 | 210.26 | 437.14 | 151.41 | 285.73 | 0.00 | 0.00 |
June | 913.02 | 120.51 | 448.80 | 152.90 | 295.91 | 0.00 | 0.00 |
July | 940.20 | 78.37 | 437.50 | 149.17 | 288.33 | 0.00 | 0.00 |
August | 910.84 | 59.20 | 413.96 | 136.02 | 277.94 | 0.00 | 0.00 |
September | 655.96 | 160.88 | 355.07 | 139.71 | 215.36 | 0.00 | 0.00 |
October | 463.67 | 393.55 | 337.68 | 175.45 | 162.23 | 0.00 | 0.00 |
November | 301.64 | 546.95 | 299.24 | 147.84 | 151.40 | 0.00 | 0.00 |
December | 178.93 | 734.10 | 273.51 | 141.94 | 131.57 | 0.00 | 0.00 |
Annual Sum or Average | 548.10 | 391.15 | 366.94 | 153.39 | 213.55 | 0.00 | 0.00 |
Minimum of Months | 150.31 | 59.20 | 273.51 | 136.02 | 131.57 | 0.00 | 0.00 |
Maximum of Months | 940.20 | 893.73 | 448.80 | 175.45 | 295.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.17 | 866.78 | 436.30 | 270.36 | 165.94 | 0.00 | 0.00 |
February | 422.68 | 706.89 | 414.75 | 241.86 | 172.89 | 0.00 | 0.00 |
March | 505.86 | 418.44 | 404.85 | 173.96 | 230.88 | 0.00 | 0.00 |
April | 509.65 | 316.65 | 338.41 | 83.76 | 254.65 | 0.00 | 0.00 |
May | 523.87 | 181.03 | 306.64 | 27.87 | 278.77 | 0.00 | 0.00 |
June | 627.58 | 98.37 | 300.82 | 17.93 | 282.89 | 0.00 | 0.00 |
July | 647.67 | 59.84 | 295.22 | 18.12 | 277.10 | 0.00 | 0.00 |
August | 708.05 | 41.29 | 320.72 | 42.98 | 277.74 | 0.00 | 0.00 |
September | 598.96 | 135.26 | 325.37 | 97.80 | 227.57 | 0.00 | 0.00 |
October | 596.99 | 359.96 | 409.15 | 228.06 | 181.08 | 0.00 | 0.00 |
November | 531.66 | 518.04 | 435.89 | 257.25 | 178.64 | 0.00 | 0.00 |
December | 425.44 | 701.84 | 430.00 | 271.85 | 158.15 | 0.00 | 0.00 |
Annual Sum or Average | 539.95 | 365.33 | 367.99 | 143.85 | 224.15 | 0.00 | 0.00 |
Minimum of Months | 373.17 | 41.29 | 295.22 | 17.93 | 158.15 | 0.00 | 0.00 |
Maximum of Months | 708.05 | 866.78 | 436.30 | 271.85 | 282.89 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158821E+10 | 0.168676E+10 | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.00 | 0.00 |
February | 0.146921E+10 | 0.125510E+10 | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.00 | 0.00 |
March | 0.168757E+10 | 0.861578E+09 | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.00 | 0.00 |
April | 0.141068E+10 | 0.641389E+09 | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.00 | 0.00 |
May | 0.129538E+10 | 0.380681E+09 | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.00 | 0.00 |
June | 0.136347E+10 | 0.202716E+09 | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.00 | 0.00 |
July | 0.147138E+10 | 0.122261E+09 | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.00 | 0.00 |
August | 0.174279E+10 | 94452923.40 | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.00 | 0.00 |
September | 0.162003E+10 | 0.284643E+09 | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.00 | 0.00 |
October | 0.196392E+10 | 0.758265E+09 | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.00 | 0.00 |
November | 0.184192E+10 | 0.102612E+10 | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.00 | 0.00 |
December | 0.170530E+10 | 0.138693E+10 | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191599E+11 | 0.870089E+10 | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129538E+10 | 94452923.40 | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196392E+10 | 0.168676E+10 | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.441602E+10 | 0.486032E+10 | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.00 | 0.00 |
February | 0.408608E+10 | 0.366530E+10 | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.00 | 0.00 |
March | 0.468578E+10 | 0.260584E+10 | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.00 | 0.00 |
April | 0.391114E+10 | 0.196642E+10 | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.00 | 0.00 |
May | 0.357705E+10 | 0.123963E+10 | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.00 | 0.00 |
June | 0.378440E+10 | 0.698962E+09 | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.00 | 0.00 |
July | 0.410429E+10 | 0.453888E+09 | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.00 | 0.00 |
August | 0.488433E+10 | 0.368605E+09 | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.00 | 0.00 |
September | 0.450156E+10 | 0.964202E+09 | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.00 | 0.00 |
October | 0.546883E+10 | 0.233134E+10 | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.00 | 0.00 |
November | 0.512582E+10 | 0.305791E+10 | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.00 | 0.00 |
December | 0.474139E+10 | 0.404343E+10 | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.532867E+11 | 0.262559E+11 | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.00 | 0.00 |
Minimum of Months | 0.357705E+10 | 0.368605E+09 | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.00 | 0.00 |
Maximum of Months | 0.546883E+10 | 0.486032E+10 | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.585520E+10 | 0.652579E+10 | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.00 | 0.00 |
February | 0.543805E+10 | 0.490323E+10 | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.00 | 0.00 |
March | 0.627283E+10 | 0.344266E+10 | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.00 | 0.00 |
April | 0.524223E+10 | 0.260910E+10 | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.00 | 0.00 |
May | 0.479326E+10 | 0.163292E+10 | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.00 | 0.00 |
June | 0.506638E+10 | 0.908709E+09 | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.00 | 0.00 |
July | 0.550632E+10 | 0.580001E+09 | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.00 | 0.00 |
August | 0.657374E+10 | 0.445744E+09 | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.00 | 0.00 |
September | 0.602786E+10 | 0.125015E+10 | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.00 | 0.00 |
October | 0.732461E+10 | 0.306775E+10 | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.00 | 0.00 |
November | 0.683946E+10 | 0.406637E+10 | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.00 | 0.00 |
December | 0.630742E+10 | 0.541777E+10 | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.712474E+11 | 0.348502E+11 | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.479326E+10 | 0.445744E+09 | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.732461E+10 | 0.652579E+10 | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.426277E+09 | 0.101785E+10 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.481020E+09 | 0.752974E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.783579E+09 | 0.511285E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.873023E+09 | 0.379447E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.953740E+09 | 0.226837E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.110299E+10 | 0.102050E+09 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.115448E+10 | 52685294.59 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.120765E+10 | 26936746.29 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.889179E+09 | 0.153697E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.797593E+09 | 0.446662E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.601595E+09 | 0.612986E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.456714E+09 | 0.831550E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.972784E+10 | 0.511496E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.426277E+09 | 26936746.29 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120765E+10 | 0.101785E+10 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160003E+09 | 0.110629E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.247975E+09 | 0.806314E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.538291E+09 | 0.517567E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.727822E+09 | 0.374721E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.894868E+09 | 0.219612E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.109180E+10 | 97250517.06 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.113126E+10 | 50689759.86 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.110614E+10 | 25780737.08 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.716045E+09 | 0.150411E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.496708E+09 | 0.450088E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.303434E+09 | 0.640561E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.172744E+09 | 0.897606E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.758710E+10 | 0.533689E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.160003E+09 | 25780737.08 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113126E+10 | 0.110629E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247269E+09 | 0.272559E+09 | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.00 | 0.00 |
February | 0.226701E+09 | 0.208279E+09 | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.00 | 0.00 |
March | 0.252249E+09 | 0.161165E+09 | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.00 | 0.00 |
April | 0.210627E+09 | 0.122512E+09 | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.00 | 0.00 |
May | 0.192858E+09 | 76416944.72 | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.00 | 0.00 |
June | 0.211918E+09 | 39002581.25 | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.00 | 0.00 |
July | 0.233947E+09 | 23582513.15 | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.00 | 0.00 |
August | 0.280793E+09 | 16240462.58 | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.00 | 0.00 |
September | 0.250227E+09 | 55946611.20 | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.00 | 0.00 |
October | 0.300550E+09 | 0.142409E+09 | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.00 | 0.00 |
November | 0.278874E+09 | 0.190295E+09 | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.00 | 0.00 |
December | 0.260579E+09 | 0.238305E+09 | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.294659E+10 | 0.154671E+10 | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.00 | 0.00 |
Minimum of Months | 0.192858E+09 | 16240462.58 | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.00 | 0.00 |
Maximum of Months | 0.300550E+09 | 0.272559E+09 | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5421408.67 | 0.344995E+09 | 42076451.99 | 0.00 | 42076451.99 | 0.00 | 0.00 |
February | 19294008.35 | 0.247030E+09 | 42124339.93 | 0.00 | 42124339.93 | 0.00 | 0.00 |
March | 52427841.94 | 0.150002E+09 | 65492691.15 | 1318.99 | 65491372.16 | 0.00 | 0.00 |
April | 0.100647E+09 | 0.103723E+09 | 76848851.72 | 448829.91 | 76400021.81 | 0.00 | 0.00 |
May | 0.158767E+09 | 56784623.29 | 94747450.04 | 2971603.27 | 91775846.77 | 0.00 | 0.00 |
June | 0.221881E+09 | 23244921.56 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
July | 0.236036E+09 | 11664315.23 | 98689421.90 | 5056973.36 | 93632448.53 | 0.00 | 0.00 |
August | 0.221140E+09 | 5065206.55 | 87654522.95 | 1029768.70 | 86624754.24 | 0.00 | 0.00 |
September | 0.122367E+09 | 39473164.15 | 64031230.67 | 25170.94 | 64006059.72 | 0.00 | 0.00 |
October | 56063803.84 | 0.128676E+09 | 50273499.29 | 0.00 | 50273499.29 | 0.00 | 0.00 |
November | 26860538.01 | 0.188971E+09 | 43541540.27 | 0.00 | 43541540.27 | 0.00 | 0.00 |
December | 6497326.46 | 0.274127E+09 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Annual Sum or Average | 0.122740E+10 | 0.157376E+10 | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.00 | 0.00 |
Minimum of Months | 5421408.67 | 5065206.55 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Maximum of Months | 0.236036E+09 | 0.344995E+09 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.404262E+09 | 0.100275E+10 | 0.496486E+09 | 0.292891E+09 | 0.203596E+09 | 0.00 | 0.00 |
February | 0.490227E+09 | 0.735067E+09 | 0.481219E+09 | 0.289311E+09 | 0.191908E+09 | 0.00 | 0.00 |
March | 0.709279E+09 | 0.483958E+09 | 0.580914E+09 | 0.281299E+09 | 0.299614E+09 | 0.00 | 0.00 |
April | 0.836068E+09 | 0.351343E+09 | 0.574551E+09 | 0.240974E+09 | 0.333577E+09 | 0.00 | 0.00 |
May | 0.980547E+09 | 0.209146E+09 | 0.598187E+09 | 0.209729E+09 | 0.388458E+09 | 0.00 | 0.00 |
June | 0.112642E+10 | 92442427.68 | 0.582588E+09 | 0.197605E+09 | 0.384983E+09 | 0.00 | 0.00 |
July | 0.120788E+10 | 50378590.72 | 0.590525E+09 | 0.201092E+09 | 0.389433E+09 | 0.00 | 0.00 |
August | 0.121734E+10 | 24917009.97 | 0.579466E+09 | 0.196526E+09 | 0.382940E+09 | 0.00 | 0.00 |
September | 0.892171E+09 | 0.146062E+09 | 0.507408E+09 | 0.214997E+09 | 0.292411E+09 | 0.00 | 0.00 |
October | 0.770390E+09 | 0.425892E+09 | 0.547407E+09 | 0.316785E+09 | 0.230622E+09 | 0.00 | 0.00 |
November | 0.576543E+09 | 0.589716E+09 | 0.494448E+09 | 0.280911E+09 | 0.213537E+09 | 0.00 | 0.00 |
December | 0.448975E+09 | 0.811787E+09 | 0.480619E+09 | 0.287609E+09 | 0.193010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.966011E+10 | 0.492346E+10 | 0.651382E+10 | 0.300973E+10 | 0.350409E+10 | 0.00 | 0.00 |
Minimum of Months | 0.404262E+09 | 24917009.97 | 0.480619E+09 | 0.196526E+09 | 0.191908E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121734E+10 | 0.100275E+10 | 0.598187E+09 | 0.316785E+09 | 0.389433E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118402E+09 | 0.107087E+10 | 0.269858E+09 | 98926312.94 | 0.170931E+09 | 0.00 | 0.00 |
February | 0.230692E+09 | 0.761314E+09 | 0.298943E+09 | 0.132584E+09 | 0.166359E+09 | 0.00 | 0.00 |
March | 0.450785E+09 | 0.476618E+09 | 0.424928E+09 | 0.156494E+09 | 0.268435E+09 | 0.00 | 0.00 |
April | 0.688233E+09 | 0.345540E+09 | 0.497381E+09 | 0.183744E+09 | 0.313637E+09 | 0.00 | 0.00 |
May | 0.924878E+09 | 0.206148E+09 | 0.572725E+09 | 0.195836E+09 | 0.376889E+09 | 0.00 | 0.00 |
June | 0.111933E+10 | 91865904.43 | 0.580777E+09 | 0.198732E+09 | 0.382045E+09 | 0.00 | 0.00 |
July | 0.118628E+10 | 50098994.05 | 0.581347E+09 | 0.198474E+09 | 0.382873E+09 | 0.00 | 0.00 |
August | 0.111614E+10 | 24297566.79 | 0.529335E+09 | 0.167803E+09 | 0.361533E+09 | 0.00 | 0.00 |
September | 0.717381E+09 | 0.142594E+09 | 0.412969E+09 | 0.147145E+09 | 0.265824E+09 | 0.00 | 0.00 |
October | 0.455238E+09 | 0.416767E+09 | 0.357089E+09 | 0.153163E+09 | 0.203926E+09 | 0.00 | 0.00 |
November | 0.250342E+09 | 0.587461E+09 | 0.281211E+09 | 0.102303E+09 | 0.178908E+09 | 0.00 | 0.00 |
December | 0.127578E+09 | 0.839766E+09 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.738528E+10 | 0.501335E+10 | 0.505854E+10 | 0.182778E+10 | 0.323077E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118402E+09 | 24297566.79 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118628E+10 | 0.107087E+10 | 0.581347E+09 | 0.198732E+09 | 0.382873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.450091E+09 | 0.130489E+10 | 0.575045E+09 | 0.336147E+09 | 0.238898E+09 | 0.00 | 0.00 |
February | 0.485212E+09 | 0.956025E+09 | 0.498387E+09 | 0.271614E+09 | 0.226773E+09 | 0.00 | 0.00 |
March | 0.688712E+09 | 0.620568E+09 | 0.554065E+09 | 0.216298E+09 | 0.337767E+09 | 0.00 | 0.00 |
April | 0.716407E+09 | 0.450614E+09 | 0.466674E+09 | 0.101127E+09 | 0.365548E+09 | 0.00 | 0.00 |
May | 0.807261E+09 | 0.257683E+09 | 0.454606E+09 | 36951836.71 | 0.417654E+09 | 0.00 | 0.00 |
June | 0.963365E+09 | 0.126935E+09 | 0.440030E+09 | 26696625.66 | 0.413333E+09 | 0.00 | 0.00 |
July | 0.102847E+10 | 75788286.38 | 0.443462E+09 | 26446478.24 | 0.417015E+09 | 0.00 | 0.00 |
August | 0.109313E+10 | 45639927.53 | 0.466627E+09 | 54240731.23 | 0.412387E+09 | 0.00 | 0.00 |
September | 0.836206E+09 | 0.190724E+09 | 0.441071E+09 | 0.117698E+09 | 0.323373E+09 | 0.00 | 0.00 |
October | 0.802889E+09 | 0.534580E+09 | 0.547629E+09 | 0.283562E+09 | 0.264067E+09 | 0.00 | 0.00 |
November | 0.667441E+09 | 0.748062E+09 | 0.558184E+09 | 0.309534E+09 | 0.248651E+09 | 0.00 | 0.00 |
December | 0.525962E+09 | 0.105150E+10 | 0.564750E+09 | 0.338005E+09 | 0.226745E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.906515E+10 | 0.636301E+10 | 0.601053E+10 | 0.211832E+10 | 0.389221E+10 | 0.00 | 0.00 |
Minimum of Months | 0.450091E+09 | 45639927.53 | 0.440030E+09 | 26446478.24 | 0.226745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109313E+10 | 0.130489E+10 | 0.575045E+09 | 0.338005E+09 | 0.417654E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424585E+09 | 0.101562E+10 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.476470E+09 | 0.751132E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.770782E+09 | 0.511502E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.857413E+09 | 0.382798E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.936438E+09 | 0.229959E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.108995E+10 | 0.100647E+09 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.114291E+10 | 51136761.33 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.119598E+10 | 25166371.53 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.878377E+09 | 0.152551E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.786041E+09 | 0.447458E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.596366E+09 | 0.610491E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.454887E+09 | 0.827091E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.961020E+10 | 0.510555E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424585E+09 | 25166371.53 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119598E+10 | 0.101562E+10 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160005E+09 | 0.110565E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.246186E+09 | 0.804034E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.530135E+09 | 0.516045E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.713977E+09 | 0.377773E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.878037E+09 | 0.222834E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.107903E+10 | 96113139.79 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.112005E+10 | 49417196.72 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.109555E+10 | 24078284.98 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.706884E+09 | 0.148878E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.489812E+09 | 0.448603E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.302510E+09 | 0.635663E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.174208E+09 | 0.892789E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.749639E+10 | 0.532188E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.160005E+09 | 24078284.98 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112005E+10 | 0.110565E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.435816E+09 | 0.524429E+09 | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.00 | 0.00 |
February | 0.404499E+09 | 0.391464E+09 | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.00 | 0.00 |
March | 0.463400E+09 | 0.267944E+09 | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.00 | 0.00 |
April | 0.392067E+09 | 0.198054E+09 | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.00 | 0.00 |
May | 0.363076E+09 | 0.114528E+09 | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.00 | 0.00 |
June | 0.405734E+09 | 47960011.78 | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.00 | 0.00 |
July | 0.449919E+09 | 24034660.14 | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.00 | 0.00 |
August | 0.537716E+09 | 11288265.07 | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.00 | 0.00 |
September | 0.467916E+09 | 77791061.04 | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.00 | 0.00 |
October | 0.551671E+09 | 0.233830E+09 | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.00 | 0.00 |
November | 0.513293E+09 | 0.319186E+09 | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.00 | 0.00 |
December | 0.470197E+09 | 0.430163E+09 | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.545530E+10 | 0.264067E+10 | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.00 | 0.00 |
Minimum of Months | 0.363076E+09 | 11288265.07 | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551671E+09 | 0.524429E+09 | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 33933746.45 | 0.339474E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.133515E+09 | 0.248806E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.365380E+09 | 0.161739E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.757093E+09 | 0.114714E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.122782E+10 | 0.705949E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.172678E+10 | 0.377177E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.181450E+10 | 0.253728E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.166294E+10 | 0.193707E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.921791E+09 | 0.553573E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.404193E+09 | 0.141494E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.175315E+09 | 0.196178E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 34567714.36 | 0.277294E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.925783E+10 | 0.168811E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 33933746.45 | 0.193707E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.181450E+10 | 0.339474E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29517777.04 | 0.348429E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.121866E+09 | 0.256749E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.333351E+09 | 0.169111E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.715750E+09 | 0.119867E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.117978E+10 | 0.740756E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.168501E+10 | 0.397673E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.177505E+10 | 0.271610E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.162529E+10 | 0.210896E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.883467E+09 | 0.589711E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.374573E+09 | 0.148628E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.153635E+09 | 0.204284E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 28986607.16 | 0.287111E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.890627E+10 | 0.175525E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 28986607.16 | 0.210896E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.177505E+10 | 0.348429E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.402579E+09 | 0.239378E+10 | 0.766313E+09 | 0.391803E+09 | 0.374510E+09 | 0.00 | 0.00 |
February | 0.646287E+09 | 0.178479E+10 | 0.780127E+09 | 0.421877E+09 | 0.358251E+09 | 0.00 | 0.00 |
March | 0.113222E+10 | 0.119599E+10 | 0.100579E+10 | 0.437771E+09 | 0.568023E+09 | 0.00 | 0.00 |
April | 0.156767E+10 | 0.861661E+09 | 0.107188E+10 | 0.424692E+09 | 0.647183E+09 | 0.00 | 0.00 |
May | 0.200839E+10 | 0.563165E+09 | 0.117085E+10 | 0.405538E+09 | 0.765309E+09 | 0.00 | 0.00 |
June | 0.236655E+10 | 0.312368E+09 | 0.116330E+10 | 0.396310E+09 | 0.766990E+09 | 0.00 | 0.00 |
July | 0.251823E+10 | 0.209919E+09 | 0.117181E+10 | 0.399539E+09 | 0.772269E+09 | 0.00 | 0.00 |
August | 0.243960E+10 | 0.158556E+09 | 0.110874E+10 | 0.364305E+09 | 0.744437E+09 | 0.00 | 0.00 |
September | 0.170024E+10 | 0.417008E+09 | 0.920329E+09 | 0.362120E+09 | 0.558209E+09 | 0.00 | 0.00 |
October | 0.124189E+10 | 0.105409E+10 | 0.904454E+09 | 0.469926E+09 | 0.434528E+09 | 0.00 | 0.00 |
November | 0.781840E+09 | 0.141770E+10 | 0.775627E+09 | 0.383200E+09 | 0.392427E+09 | 0.00 | 0.00 |
December | 0.479253E+09 | 0.196621E+10 | 0.732571E+09 | 0.380168E+09 | 0.352403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172848E+11 | 0.123352E+11 | 0.115718E+11 | 0.483725E+10 | 0.673454E+10 | 0.00 | 0.00 |
Minimum of Months | 0.402579E+09 | 0.158556E+09 | 0.732571E+09 | 0.362120E+09 | 0.352403E+09 | 0.00 | 0.00 |
Maximum of Months | 0.251823E+10 | 0.239378E+10 | 0.117181E+10 | 0.469926E+09 | 0.772269E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999499E+09 | 0.232159E+10 | 0.116859E+10 | 0.724128E+09 | 0.444462E+09 | 0.00 | 0.00 |
February | 0.102255E+10 | 0.171010E+10 | 0.100337E+10 | 0.585111E+09 | 0.418262E+09 | 0.00 | 0.00 |
March | 0.135489E+10 | 0.112074E+10 | 0.108434E+10 | 0.465948E+09 | 0.618396E+09 | 0.00 | 0.00 |
April | 0.132101E+10 | 0.820758E+09 | 0.877147E+09 | 0.217098E+09 | 0.660049E+09 | 0.00 | 0.00 |
May | 0.140315E+10 | 0.484871E+09 | 0.821300E+09 | 74645838.28 | 0.746654E+09 | 0.00 | 0.00 |
June | 0.162669E+10 | 0.254965E+09 | 0.779732E+09 | 46480736.68 | 0.733252E+09 | 0.00 | 0.00 |
July | 0.173473E+10 | 0.160271E+09 | 0.790720E+09 | 48537407.44 | 0.742182E+09 | 0.00 | 0.00 |
August | 0.189645E+10 | 0.110597E+09 | 0.859026E+09 | 0.115128E+09 | 0.743898E+09 | 0.00 | 0.00 |
September | 0.155250E+10 | 0.350591E+09 | 0.843369E+09 | 0.253504E+09 | 0.589865E+09 | 0.00 | 0.00 |
October | 0.159899E+10 | 0.964124E+09 | 0.109586E+10 | 0.610848E+09 | 0.485011E+09 | 0.00 | 0.00 |
November | 0.137805E+10 | 0.134277E+10 | 0.112983E+10 | 0.666797E+09 | 0.463028E+09 | 0.00 | 0.00 |
December | 0.113949E+10 | 0.187981E+10 | 0.115171E+10 | 0.728130E+09 | 0.423585E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170280E+11 | 0.115212E+11 | 0.116050E+11 | 0.453636E+10 | 0.706864E+10 | 0.00 | 0.00 |
Minimum of Months | 0.999499E+09 | 0.110597E+09 | 0.779732E+09 | 46480736.68 | 0.418262E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189645E+10 | 0.232159E+10 | 0.116859E+10 | 0.728130E+09 | 0.746654E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770614E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163356477.1 | 81.21 | 0.00 | 0.00 |
February | 0.696340E+10 | -0.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -147443726.1 | 81.21 | 0.00 | 0.00 |
March | 0.770454E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163096878.8 | 81.21 | 0.00 | 0.00 |
April | 0.746624E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157662770.1 | 81.21 | 0.00 | 0.00 |
May | 0.770553E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162742434.8 | 81.21 | 0.00 | 0.00 |
June | 0.745784E+10 | -0.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157301019.2 | 81.21 | 0.00 | 0.00 |
July | 0.771334E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162475282.5 | 81.21 | 0.00 | 0.00 |
August | 0.770524E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162428115.2 | 81.21 | 0.00 | 0.00 |
September | 0.746734E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157409844.0 | 81.21 | 0.00 | 0.00 |
October | 0.770442E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162991195.1 | 81.21 | 0.00 | 0.00 |
November | 0.745033E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157902392.1 | 81.21 | 0.00 | 0.00 |
December | 0.771410E+10 | -0.755083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163264098.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907585E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191807E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696340E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -163356477.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771410E+10 | -0.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147443726.1 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.116110E+12 | -0.114306E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180388E+10 | 81.26 | 0.00 | 0.00 |
February | 0.105018E+12 | -0.103383E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163511E+10 | 81.26 | 0.00 | 0.00 |
March | 0.113690E+12 | -0.111877E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181368E+10 | 81.26 | 0.00 | 0.00 |
April | 0.105410E+12 | -0.103652E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175752E+10 | 81.25 | 0.00 | 0.00 |
May | 0.103261E+12 | -0.101448E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181347E+10 | 81.25 | 0.00 | 0.00 |
June | 0.950576E+11 | -0.933103E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174733E+10 | 81.25 | 0.00 | 0.00 |
July | 0.951800E+11 | -0.933874E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179256E+10 | 81.25 | 0.00 | 0.00 |
August | 0.949486E+11 | -0.931723E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177638E+10 | 81.25 | 0.00 | 0.00 |
September | 0.944526E+11 | -0.927476E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170503E+10 | 81.24 | 0.00 | 0.00 |
October | 0.102416E+12 | -0.100657E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175882E+10 | 81.25 | 0.00 | 0.00 |
November | 0.104591E+12 | -0.102890E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170134E+10 | 81.25 | 0.00 | 0.00 |
December | 0.113078E+12 | -0.111304E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177380E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.124321E+13 | -0.122213E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210789E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.944526E+11 | -0.114306E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181368E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.116110E+12 | -0.927476E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163511E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.676691E+11 | -0.660995E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156964E+10 | 58.98 | 0.00 | 0.00 |
February | 0.612588E+11 | -0.598330E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.142582E+10 | 58.98 | 0.00 | 0.00 |
March | 0.656513E+11 | -0.640680E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158328E+10 | 58.98 | 0.00 | 0.00 |
April | 0.595264E+11 | -0.579908E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153567E+10 | 58.98 | 0.00 | 0.00 |
May | 0.566342E+11 | -0.550510E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158324E+10 | 58.98 | 0.00 | 0.00 |
June | 0.506157E+11 | -0.490940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152171E+10 | 58.98 | 0.00 | 0.00 |
July | 0.496202E+11 | -0.480659E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155438E+10 | 58.98 | 0.00 | 0.00 |
August | 0.494612E+11 | -0.479293E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153186E+10 | 58.98 | 0.00 | 0.00 |
September | 0.500488E+11 | -0.485856E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146319E+10 | 58.98 | 0.00 | 0.00 |
October | 0.558458E+11 | -0.543380E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150779E+10 | 58.98 | 0.00 | 0.00 |
November | 0.587658E+11 | -0.573078E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145799E+10 | 58.98 | 0.00 | 0.00 |
December | 0.650425E+11 | -0.635145E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152799E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.690140E+12 | -0.671877E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.182626E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.494612E+11 | -0.660995E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158328E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.676691E+11 | -0.479293E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142582E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.87 | 0.86 | 01-JAN-09:30 | 5291.40 | 34.04 | 271.33 | 275.83 | 815.87 | 25.51 | 167.33 | 246.50 |
February | 263.00 | 0.88 | 0.86 | 01-FEB-13:39 | 4693.55 | 30.88 | 192.00 | 250.50 | 574.83 | 21.91 | 111.17 | 205.33 |
March | 351.67 | 0.88 | 0.86 | 01-MAR-09:09 | 1162.57 | 19.56 | 11.17 | 322.50 | 447.11 | 20.97 | 162.33 | 257.83 |
April | 369.33 | 0.88 | 0.86 | 01-APR-10:09 | 929.75 | 19.06 | 0.00 | 329.17 | 368.40 | 20.80 | 152.83 | 251.33 |
May | 407.00 | 0.88 | 0.86 | 01-MAY-07:00 | 880.72 | 19.02 | 0.00 | 363.00 | 349.28 | 20.75 | 190.50 | 279.17 |
June | 411.67 | 0.88 | 0.86 | 01-JUN-07:40 | 813.01 | 18.79 | 0.00 | 364.33 | 327.03 | 20.53 | 175.17 | 263.33 |
July | 411.00 | 0.88 | 0.86 | 01-JUL-08:39 | 860.31 | 18.88 | 0.00 | 369.00 | 343.09 | 20.61 | 208.67 | 277.83 |
August | 390.50 | 0.88 | 0.86 | 01-AUG-08:20 | 1065.38 | 19.54 | 0.83 | 355.17 | 416.56 | 21.25 | 236.33 | 289.83 |
September | 298.50 | 0.88 | 0.86 | 01-SEP-08:09 | 1120.56 | 19.48 | 0.17 | 312.67 | 442.39 | 21.21 | 176.83 | 239.67 |
October | 293.50 | 0.88 | 0.86 | 01-OCT-10:39 | 2703.03 | 24.73 | 106.17 | 294.50 | 457.32 | 21.05 | 108.67 | 222.50 |
November | 299.00 | 0.87 | 0.86 | 01-NOV-09:09 | 5262.95 | 34.79 | 286.00 | 275.67 | 661.27 | 25.18 | 182.17 | 246.00 |
December | 285.17 | 0.87 | 0.86 | 01-DEC-07:00 | 4951.97 | 34.55 | 270.50 | 271.83 | 914.41 | 26.67 | 174.83 | 236.67 |
Annual Sum or Average | 4071.00 | 0.88 | 2235.57 | 23.61 | 1138.17 | 3784.17 | 488.05 | 21.99 | 2046.83 | 3016.00 | ||
Minimum of Months | 263.00 | 0.87 | 0.86 | 813.01 | 18.79 | 0.00 | 250.50 | 327.03 | 20.53 | 108.67 | 205.33 | |
Maximum of Months | 411.67 | 0.88 | 0.86 | 5291.40 | 34.79 | 286.00 | 369.00 | 914.41 | 26.67 | 236.33 | 289.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.25 | 0.22 | 01-JAN-08:00 | 5610.83 | 34.17 | 273.00 | 283.33 | 1134.61 | 25.42 | 177.00 | 265.50 |
February | 263.00 | 0.28 | 0.22 | 01-FEB-10:30 | 4997.31 | 30.97 | 193.17 | 261.17 | 877.96 | 21.97 | 111.50 | 226.17 |
March | 351.67 | 0.27 | 0.22 | 01-MAR-08:39 | 1409.85 | 19.99 | 34.33 | 334.00 | 693.58 | 21.25 | 180.50 | 301.33 |
April | 369.33 | 0.28 | 0.22 | 01-APR-08:20 | 1112.00 | 19.73 | 14.00 | 344.83 | 550.07 | 21.25 | 191.67 | 306.67 |
May | 407.00 | 0.28 | 0.22 | 01-MAY-07:30 | 1027.85 | 19.84 | 16.83 | 384.00 | 495.86 | 21.34 | 258.00 | 335.00 |
June | 411.67 | 0.28 | 0.22 | 01-JUN-06:00 | 947.65 | 19.65 | 13.17 | 383.33 | 461.17 | 21.17 | 242.33 | 336.33 |
July | 411.00 | 0.28 | 0.22 | 01-JUL-07:10 | 999.10 | 19.73 | 22.33 | 387.00 | 481.35 | 21.23 | 258.17 | 338.50 |
August | 390.50 | 0.27 | 0.22 | 01-AUG-07:10 | 1236.39 | 20.27 | 57.67 | 369.83 | 586.92 | 21.77 | 278.67 | 333.00 |
September | 298.50 | 0.28 | 0.22 | 01-SEP-07:30 | 1332.47 | 20.05 | 36.17 | 325.67 | 653.62 | 21.58 | 199.00 | 291.83 |
October | 293.50 | 0.27 | 0.22 | 01-OCT-08:20 | 3000.10 | 24.84 | 115.67 | 307.00 | 751.50 | 21.10 | 119.67 | 268.50 |
November | 299.00 | 0.26 | 0.22 | 01-NOV-08:09 | 5569.13 | 34.88 | 287.17 | 282.50 | 965.39 | 25.14 | 184.17 | 267.00 |
December | 285.17 | 0.25 | 0.22 | 01-DEC-07:49 | 5276.78 | 34.65 | 272.33 | 280.33 | 1236.96 | 26.58 | 181.33 | 259.67 |
Annual Sum or Average | 4071.00 | 0.27 | 2456.83 | 24.11 | 1335.83 | 3943.00 | 708.31 | 22.32 | 2382.00 | 3529.50 | ||
Minimum of Months | 263.00 | 0.25 | 0.22 | 947.65 | 19.65 | 13.17 | 261.17 | 461.17 | 21.10 | 111.50 | 226.17 | |
Maximum of Months | 411.67 | 0.28 | 0.22 | 5610.83 | 34.88 | 287.17 | 387.00 | 1236.96 | 26.58 | 278.67 | 338.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.72 | 0.60 | 01-JAN-11:20 | 331.85 | 14.09 | 0.00 | 214.67 | 153.87 | 17.52 | 0.00 | 58.67 |
February | 263.00 | 0.72 | 0.60 | 01-FEB-13:50 | 342.24 | 14.28 | 0.00 | 202.17 | 162.28 | 17.66 | 0.00 | 76.83 |
March | 351.67 | 0.67 | 0.60 | 01-MAR-09:30 | 443.23 | 15.80 | 0.00 | 316.00 | 206.82 | 19.04 | 0.00 | 177.00 |
April | 369.33 | 0.65 | 0.60 | 01-APR-10:39 | 538.88 | 16.69 | 0.00 | 342.17 | 245.36 | 19.89 | 7.17 | 228.83 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 686.13 | 18.19 | 18.33 | 391.67 | 312.86 | 21.71 | 109.83 | 350.17 |
June | 411.67 | 0.62 | 0.60 | 01-JUN-06:40 | 763.10 | 19.79 | 55.83 | 393.67 | 350.28 | 23.20 | 188.83 | 367.50 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 775.45 | 18.71 | 27.50 | 395.00 | 338.79 | 22.57 | 176.17 | 356.17 |
August | 390.50 | 0.63 | 0.60 | 01-AUG-06:00 | 680.92 | 17.58 | 0.00 | 370.83 | 308.38 | 20.75 | 78.17 | 327.83 |
September | 298.50 | 0.65 | 0.60 | 01-SEP-07:40 | 498.93 | 16.52 | 0.00 | 316.17 | 234.50 | 19.70 | 0.17 | 207.00 |
October | 293.50 | 0.71 | 0.60 | 01-OCT-10:50 | 348.12 | 14.72 | 0.00 | 232.50 | 170.61 | 18.12 | 0.00 | 102.00 |
November | 299.00 | 0.71 | 0.60 | 01-NOV-10:30 | 343.34 | 14.35 | 0.00 | 242.83 | 161.75 | 17.72 | 0.00 | 63.00 |
December | 285.17 | 0.72 | 0.60 | 01-DEC-12:30 | 321.40 | 14.14 | 0.00 | 216.67 | 151.18 | 17.60 | 0.00 | 41.83 |
Annual Sum or Average | 4071.00 | 0.66 | 531.76 | 16.52 | 101.67 | 3634.33 | 244.04 | 19.91 | 560.33 | 2356.83 | ||
Minimum of Months | 263.00 | 0.62 | 0.60 | 321.40 | 14.09 | 0.00 | 202.17 | 151.18 | 17.52 | 0.00 | 41.83 | |
Maximum of Months | 411.67 | 0.72 | 0.60 | 775.45 | 19.79 | 55.83 | 395.00 | 350.28 | 23.20 | 188.83 | 367.50 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.72 | 0.60 | 01-JAN-11:20 | 331.85 | 14.09 | 0.00 | 214.67 | 153.87 | 17.52 | 0.00 | 58.67 |
February | 263.00 | 0.72 | 0.60 | 01-FEB-13:50 | 342.24 | 14.28 | 0.00 | 202.17 | 162.28 | 17.66 | 0.00 | 76.83 |
March | 351.67 | 0.67 | 0.60 | 01-MAR-09:30 | 443.23 | 15.80 | 0.00 | 316.00 | 206.82 | 19.04 | 0.00 | 177.00 |
April | 369.33 | 0.65 | 0.60 | 01-APR-10:39 | 538.88 | 16.69 | 0.00 | 342.17 | 245.36 | 19.89 | 7.17 | 228.83 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 686.13 | 18.19 | 18.33 | 391.67 | 312.86 | 21.71 | 109.83 | 350.17 |
June | 411.67 | 0.62 | 0.60 | 01-JUN-06:40 | 763.10 | 19.79 | 55.83 | 393.67 | 350.28 | 23.20 | 188.83 | 367.50 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 775.45 | 18.71 | 27.50 | 395.00 | 338.79 | 22.57 | 176.17 | 356.17 |
August | 390.50 | 0.63 | 0.60 | 01-AUG-06:00 | 680.92 | 17.58 | 0.00 | 370.83 | 308.38 | 20.75 | 78.17 | 327.83 |
September | 298.50 | 0.65 | 0.60 | 01-SEP-07:40 | 498.93 | 16.52 | 0.00 | 316.17 | 234.50 | 19.70 | 0.17 | 207.00 |
October | 293.50 | 0.71 | 0.60 | 01-OCT-10:50 | 348.12 | 14.72 | 0.00 | 232.50 | 170.61 | 18.12 | 0.00 | 102.00 |
November | 299.00 | 0.71 | 0.60 | 01-NOV-10:30 | 343.34 | 14.35 | 0.00 | 242.83 | 161.75 | 17.72 | 0.00 | 63.00 |
December | 285.17 | 0.72 | 0.60 | 01-DEC-12:30 | 321.40 | 14.14 | 0.00 | 216.67 | 151.18 | 17.60 | 0.00 | 41.83 |
Annual Sum or Average | 4071.00 | 0.66 | 531.76 | 16.52 | 101.67 | 3634.33 | 244.04 | 19.91 | 560.33 | 2356.83 | ||
Minimum of Months | 263.00 | 0.62 | 0.60 | 321.40 | 14.09 | 0.00 | 202.17 | 151.18 | 17.52 | 0.00 | 41.83 | |
Maximum of Months | 411.67 | 0.72 | 0.60 | 775.45 | 19.79 | 55.83 | 395.00 | 350.28 | 23.20 | 188.83 | 367.50 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.410079E+11 | 125891.99 | 10-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199027E+11 | 137079.82 | 08-FEB-22:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146755E+11 | 119180.57 | 18-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.510592E+10 | 127845.09 | 05-APR-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.914157E+09 | 41870.39 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113604E+09 | 26752.63 | 08-JUN-15:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101545E+09 | 10371.12 | 14-SEP-13:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716798E+10 | 125230.41 | 26-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159876E+11 | 123103.96 | 14-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295424E+11 | 125963.51 | 21-DEC-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.410079E+11 | 137079.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.458303E+09 | 6556.66 | 11-JAN-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246164E+10 | 6551.88 | 11-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622778E+10 | 6391.63 | 16-MAR-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.902607E+10 | 6326.24 | 07-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.597076E+10 | 6011.72 | 12-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.642111E+09 | 4404.92 | 01-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.902607E+10 | 6556.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.359592E+10 | 3002.50 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254847E+10 | 2867.52 | 07-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142067E+10 | 2253.10 | 18-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.904494E+09 | 2384.33 | 06-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411945E+09 | 1416.29 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65126183.92 | 758.25 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41344213.44 | 620.95 | 29-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208541E+09 | 1043.80 | 29-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101394E+10 | 2249.79 | 26-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163058E+10 | 2396.93 | 21-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272351E+10 | 2936.16 | 09-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359592E+10 | 3002.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.961415E+09 | 1287.35 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605955E+09 | 1224.86 | 11-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218274E+09 | 803.08 | 23-MAR-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80897345.64 | 784.45 | 07-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11987329.38 | 218.29 | 01-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6464618.07 | 202.06 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101002E+09 | 721.97 | 31-OCT-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228985E+09 | 976.37 | 25-NOV-09:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.575151E+09 | 1222.67 | 03-DEC-15:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.961415E+09 | 1287.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247534E+10 | 1822.28 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166015E+10 | 1718.99 | 04-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810219E+09 | 1176.00 | 18-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289156E+09 | 1054.52 | 07-APR-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19323770.47 | 275.00 | 11-MAY-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 111395.51 | 29.93 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288922E+09 | 1010.94 | 26-OCT-03:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.841161E+09 | 1306.43 | 26-NOV-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169696E+10 | 1833.96 | 09-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.808134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247534E+10 | 1833.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197476E+10 | 1227.40 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138708E+10 | 1172.22 | 07-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805181E+09 | 870.27 | 19-MAR-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352144E+09 | 822.93 | 07-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56461307.64 | 351.20 | 11-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7261445.71 | 195.60 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.392848E+09 | 785.01 | 26-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.862775E+09 | 980.39 | 26-NOV-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147413E+10 | 1235.27 | 09-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.731264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197476E+10 | 1235.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.547692E+10 | 8900.81 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429601E+10 | 8406.86 | 04-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404794E+10 | 7908.37 | 13-MAR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.326123E+10 | 7854.20 | 28-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290630E+10 | 7859.65 | 10-MAY-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.225199E+10 | 6102.02 | 10-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.216208E+10 | 6271.04 | 29-JUL-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210323E+10 | 5649.51 | 21-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.263486E+10 | 6517.25 | 29-SEP-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360920E+10 | 8343.25 | 07-OCT-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.408245E+10 | 8456.61 | 26-NOV-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479671E+10 | 8457.54 | 03-DEC-15:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.210323E+10 | 5649.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.547692E+10 | 8900.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.427126E+10 | 8804.55 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277771E+10 | 8410.71 | 07-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126542E+10 | 6964.27 | 16-MAR-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692997E+09 | 7060.31 | 07-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294997E+09 | 3365.66 | 11-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33024987.41 | 1876.87 | 08-JUN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31886054.61 | 1278.07 | 28-JUL-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162390E+09 | 3041.51 | 29-SEP-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.880836E+09 | 5617.13 | 30-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120280E+10 | 6869.74 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261031E+10 | 7013.88 | 21-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.427126E+10 | 8804.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.891776E+10 | 23530.16 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570362E+10 | 22162.36 | 11-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188280E+10 | 14785.65 | 16-MAR-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.759175E+09 | 15134.38 | 07-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102859E+09 | 3159.71 | 11-MAY-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45120804.43 | 2290.17 | 29-SEP-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.932827E+09 | 11055.18 | 30-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163431E+10 | 14432.36 | 30-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439027E+10 | 21653.57 | 03-DEC-15:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.891776E+10 | 23530.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135822E+11 | 11285.69 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.883119E+10 | 10779.86 | 07-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.308717E+10 | 8583.87 | 18-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.772326E+09 | 7754.10 | 07-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6247967.16 | 768.13 | 01-MAY-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2274670.60 | 578.99 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184555E+10 | 7307.50 | 26-OCT-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482035E+10 | 9246.63 | 26-NOV-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.988719E+10 | 10752.31 | 01-DEC-10:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135822E+11 | 11285.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.876224E+10 | 6928.34 | 22-JAN-17:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.578267E+10 | 6616.94 | 07-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256346E+10 | 4822.53 | 19-MAR-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.978403E+09 | 4940.19 | 06-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97430751.53 | 2040.75 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54372418.80 | 941.60 | 29-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170135E+10 | 4957.92 | 26-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366544E+10 | 5058.91 | 22-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.651781E+10 | 6972.74 | 09-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.876224E+10 | 6972.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.943925E+09 | 8357.68 | 15-JAN-15:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497164E+09 | 8021.35 | 04-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28637183.53 | 1646.98 | 22-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 149167.91 | 497.23 | 07-APR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8830669.75 | 1470.14 | 25-OCT-09:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67541664.24 | 3936.13 | 22-NOV-10:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292871E+09 | 8893.75 | 03-DEC-15:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.943925E+09 | 8893.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.465857E+09 | 7724.11 | 15-JAN-15:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217460E+09 | 6375.64 | 04-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4268505.98 | 559.81 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9127686.06 | 1648.80 | 22-NOV-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 65371303.00 | 8253.86 | 03-DEC-15:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.762084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.465857E+09 | 8253.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.556825E+09 | 3347.48 | 08-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308449E+09 | 3817.93 | 12-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91017521.94 | 2143.16 | 17-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23320193.71 | 1876.47 | 27-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3149784.77 | 1034.55 | 11-MAY-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96769.31 | 106.94 | 29-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38111686.83 | 1883.63 | 13-OCT-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136375E+09 | 2382.19 | 22-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300437E+09 | 2750.27 | 18-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556825E+09 | 3817.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.257617E+10 | 7054.08 | 07-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164496E+10 | 10852.35 | 12-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11178.68 | 0.36 | 14-MAR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16238.79 | 0.36 | 22-APR-21:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21168.39 | 0.35 | 01-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9836.07 | 0.36 | 29-JUN-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9761.07 | 0.35 | 01-JUL-18:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13603.50 | 0.35 | 05-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14057.96 | 0.35 | 06-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7940.99 | 0.35 | 23-OCT-16:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96287905.66 | 2757.06 | 22-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359566E+09 | 4600.31 | 18-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7940.99 | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257617E+10 | 10852.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.443307E+10 | 6274.37 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265912E+10 | 6274.29 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.609803E+09 | 6212.55 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186882E+09 | 6184.69 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8591676.32 | 4181.90 | 16-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3040828.36 | 3769.16 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1852522.63 | 2396.65 | 30-JUL-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1148741.43 | 2807.73 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9859635.87 | 4156.83 | 15-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398497E+09 | 6199.12 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115879E+10 | 6274.54 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291856E+10 | 6274.21 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1148741.43 | 2396.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.443307E+10 | 6274.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.548448E+10 | 6272.00 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.333376E+10 | 6271.26 | 10-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.863249E+09 | 6222.84 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230901E+09 | 6201.80 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9032382.89 | 4260.86 | 16-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2679513.21 | 4155.53 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1901479.32 | 2428.05 | 30-JUL-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1266541.33 | 2850.54 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10559495.79 | 4009.18 | 23-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.552863E+09 | 6241.63 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171964E+10 | 6271.17 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380983E+10 | 6271.09 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1266541.33 | 2428.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.548448E+10 | 6272.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.512000E+10 | 21765.02 | 08-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160705E+10 | 23483.54 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185791E+09 | 8452.38 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.691284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.512000E+10 | 23483.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209905E+11 | 37019.36 | 07-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118473E+11 | 37013.41 | 03-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133706E+10 | 35806.49 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392291E+09 | 34128.77 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54894871.02 | 21953.15 | 07-MAY-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21709396.15 | 23911.18 | 03-JUN-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8601177.59 | 19162.59 | 07-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32244177.59 | 16609.66 | 17-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64528817.21 | 29147.29 | 15-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.533320E+09 | 35521.52 | 30-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363570E+10 | 36263.82 | 22-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113868E+11 | 36596.13 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8601177.59 | 16609.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209905E+11 | 37019.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.446419E+10 | 6125.55 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262726E+10 | 6125.39 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.652475E+09 | 6072.96 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196946E+09 | 3587.05 | 24-APR-21:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6667682.80 | 3574.69 | 10-MAY-21:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 652738.16 | 2222.22 | 07-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 852883.44 | 2183.39 | 28-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 224713.45 | 839.40 | 21-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7210111.49 | 2250.44 | 03-SEP-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.421885E+09 | 6052.78 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116361E+10 | 6125.65 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287697E+10 | 6125.31 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 224713.45 | 839.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.446419E+10 | 6125.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.551852E+10 | 6125.01 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326800E+10 | 6124.23 | 10-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.880269E+09 | 6097.20 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.243444E+09 | 4691.38 | 09-APR-20:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8671241.36 | 4057.15 | 10-MAY-21:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 671140.97 | 2369.26 | 07-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 852798.08 | 2177.15 | 28-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 276037.70 | 901.45 | 31-AUG-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8521123.68 | 2636.48 | 17-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583595E+09 | 6054.11 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168716E+10 | 6124.13 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376386E+10 | 6123.78 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 276037.70 | 901.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.551852E+10 | 6125.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155512E+10 | 1842.81 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.954636E+09 | 1842.67 | 08-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254615E+09 | 1842.42 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80319810.24 | 1841.86 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2450660.34 | 1035.00 | 16-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 719666.07 | 1037.98 | 10-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 476855.62 | 563.12 | 30-JUL-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 311897.08 | 888.41 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5368945.60 | 871.43 | 23-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169602E+09 | 1841.48 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461280E+09 | 1842.40 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107229E+10 | 1842.35 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 311897.08 | 563.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155512E+10 | 1842.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187259E+10 | 1841.85 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116362E+10 | 1842.87 | 01-FEB-21:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338399E+09 | 1841.42 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96070121.84 | 1840.84 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2971246.05 | 1059.94 | 16-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 652778.38 | 1112.03 | 10-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 448561.01 | 570.12 | 30-JUL-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 337078.14 | 896.98 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5928516.65 | 827.94 | 29-SEP-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230397E+09 | 1841.18 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.648322E+09 | 1841.45 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134866E+10 | 1842.02 | 06-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 337078.14 | 570.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187259E+10 | 1842.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.442820E+10 | 8705.38 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258670E+10 | 8706.74 | 10-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543401E+09 | 8594.04 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241261E+09 | 8531.08 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10456057.56 | 6154.93 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2943921.26 | 4770.01 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1805412.21 | 3010.84 | 02-JUL-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1449517.86 | 3612.46 | 10-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7061247.86 | 4657.16 | 19-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315785E+09 | 8561.28 | 30-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.809692E+09 | 8701.67 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251670E+10 | 8705.76 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1449517.86 | 3010.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442820E+10 | 8706.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.197625E+11 | 0.146284E+11 | 195542.66 | 19-JAN-22:00 | 100133.54 | 0.08 |
February | 0.00 | 0.00 | 0.584604E+11 | 0.503831E+11 | 179079.09 | 26-FEB-15:10 | 179079.09 | 0.16 |
March | 0.00 | 0.00 | 0.140115E+12 | 0.123514E+12 | 246952.17 | 28-MAR-20:20 | 178413.01 | 0.31 |
April | 0.00 | 0.00 | 0.264713E+12 | 0.210896E+12 | 287809.48 | 21-APR-18:10 | 156613.19 | 0.70 |
May | 0.00 | 0.00 | 0.490355E+12 | 0.322913E+12 | 414946.96 | 30-MAY-21:20 | 185993.76 | 0.92 |
June | 0.00 | 0.00 | 0.689394E+12 | 0.420294E+12 | 453253.90 | 26-JUN-21:00 | 194524.57 | 0.92 |
July | 0.00 | 0.00 | 0.879693E+12 | 0.470355E+12 | 491471.96 | 26-JUL-23:00 | 174973.52 | 1.00 |
August | 0.00 | 0.00 | 0.909664E+12 | 0.490367E+12 | 500119.08 | 23-AUG-22:50 | 179046.30 | 1.00 |
September | 0.00 | 0.00 | 0.632866E+12 | 0.367977E+12 | 447191.68 | 27-SEP-18:20 | 183082.34 | 1.00 |
October | 0.00 | 0.00 | 0.276161E+12 | 0.177661E+12 | 493318.44 | 18-OCT-21:00 | 190589.61 | 0.63 |
November | 0.00 | 0.00 | 0.121535E+12 | 0.898825E+11 | 264448.47 | 19-NOV-23:50 | 134508.13 | 0.29 |
December | 0.00 | 0.00 | 0.360171E+11 | 0.265886E+11 | 218657.34 | 13-DEC-11:40 | 117245.15 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.451874E+13 | 0.276546E+13 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.197625E+11 | 0.146284E+11 | 179079.09 | 100133.54 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.909664E+12 | 0.490367E+12 | 500119.08 | 194524.57 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.176252E+10 | 0.137197E+10 | 23359.34 | 19-JAN-16:00 | 14579.82 | 0.05 |
February | 0.00 | 0.00 | 0.553714E+10 | 0.548254E+10 | 27402.34 | 28-FEB-15:00 | 27402.34 | 0.06 |
March | 0.00 | 0.00 | 0.175170E+11 | 0.157853E+11 | 42240.28 | 31-MAR-11:00 | 23978.20 | 0.26 |
April | 0.00 | 0.00 | 0.355772E+11 | 0.290035E+11 | 50832.28 | 04-APR-10:30 | 24650.79 | 0.59 |
May | 0.00 | 0.00 | 0.711301E+11 | 0.482488E+11 | 66370.94 | 30-MAY-21:40 | 26759.42 | 0.89 |
June | 0.00 | 0.00 | 0.104696E+12 | 0.653233E+11 | 74918.98 | 29-JUN-08:00 | 28132.53 | 0.92 |
July | 0.00 | 0.00 | 0.131516E+12 | 0.728173E+11 | 81814.81 | 26-JUL-07:50 | 27742.58 | 1.00 |
August | 0.00 | 0.00 | 0.133952E+12 | 0.756290E+11 | 79625.68 | 24-AUG-07:00 | 28174.40 | 1.00 |
September | 0.00 | 0.00 | 0.946430E+11 | 0.569375E+11 | 75442.06 | 17-SEP-07:50 | 27935.92 | 0.97 |
October | 0.00 | 0.00 | 0.386077E+11 | 0.249505E+11 | 79680.67 | 18-OCT-20:20 | 28174.99 | 0.47 |
November | 0.00 | 0.00 | 0.147638E+11 | 0.110234E+11 | 46083.92 | 19-NOV-24:00 | 22548.51 | 0.21 |
December | 0.00 | 0.00 | 0.325294E+10 | 0.253804E+10 | 35337.19 | 13-DEC-13:00 | 20785.21 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.652956E+12 | 0.409111E+12 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.176252E+10 | 0.137197E+10 | 23359.34 | 14579.82 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.133952E+12 | 0.756290E+11 | 81814.81 | 28174.99 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 64215622.37 | 61813714.92 | 13779.24 | 29-JAN-16:01 | 13779.24 | 0.00 |
February | 0.00 | 0.00 | 0.250716E+09 | 0.230472E+09 | 13805.07 | 28-FEB-16:01 | 13805.07 | 0.02 |
March | 0.00 | 0.00 | 0.125946E+10 | 0.796075E+09 | 15216.62 | 30-MAR-08:52 | 10872.27 | 0.19 |
April | 0.00 | 0.00 | 0.274297E+10 | 0.156338E+10 | 16733.26 | 30-APR-21:52 | 10753.11 | 0.46 |
May | 0.00 | 0.00 | 0.489706E+10 | 0.267656E+10 | 17144.52 | 26-MAY-21:51 | 10849.01 | 0.60 |
June | 0.00 | 0.00 | 0.790888E+10 | 0.474655E+10 | 18971.75 | 26-JUN-21:51 | 11708.53 | 0.77 |
July | 0.00 | 0.00 | 0.932685E+10 | 0.564649E+10 | 18897.84 | 25-JUL-21:51 | 11110.68 | 0.77 |
August | 0.00 | 0.00 | 0.100982E+11 | 0.609427E+10 | 18711.03 | 20-AUG-21:51 | 11545.19 | 0.83 |
September | 0.00 | 0.00 | 0.581424E+10 | 0.318571E+10 | 18567.71 | 09-SEP-21:51 | 12017.59 | 0.66 |
October | 0.00 | 0.00 | 0.205536E+10 | 0.100262E+10 | 18537.44 | 18-OCT-21:51 | 10099.94 | 0.39 |
November | 0.00 | 0.00 | 0.480602E+09 | 0.330406E+09 | 16412.42 | 05-NOV-21:51 | 10477.92 | 0.11 |
December | 0.00 | 0.00 | 0.140649E+09 | 0.106924E+09 | 14407.67 | 12-DEC-22:51 | 11363.08 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.450393E+11 | 0.264413E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 64215622.37 | 61813714.92 | 13779.24 | 10099.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100982E+11 | 0.609427E+10 | 18971.75 | 13805.07 | 0.83 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4765423.11 | 3314265.04 | 4782.90 | 29-JAN-16:01 | 4782.90 | 0.00 |
February | 0.00 | 0.00 | 72801857.44 | 65118742.16 | 13663.55 | 28-FEB-16:01 | 13663.55 | 0.01 |
March | 0.00 | 0.00 | 0.796487E+09 | 0.462271E+09 | 15003.06 | 30-MAR-08:52 | 10671.77 | 0.15 |
April | 0.00 | 0.00 | 0.223894E+10 | 0.122206E+10 | 16492.30 | 30-APR-21:52 | 10553.67 | 0.42 |
May | 0.00 | 0.00 | 0.462547E+10 | 0.250756E+10 | 16946.00 | 26-MAY-21:51 | 10697.26 | 0.58 |
June | 0.00 | 0.00 | 0.783787E+10 | 0.473060E+10 | 18769.18 | 26-JUN-21:51 | 11573.66 | 0.77 |
July | 0.00 | 0.00 | 0.918587E+10 | 0.556694E+10 | 18684.86 | 25-JUL-21:51 | 10974.06 | 0.77 |
August | 0.00 | 0.00 | 0.954976E+10 | 0.566886E+10 | 18435.18 | 20-AUG-21:51 | 11333.43 | 0.82 |
September | 0.00 | 0.00 | 0.498832E+10 | 0.261146E+10 | 18238.49 | 09-SEP-21:51 | 11704.98 | 0.62 |
October | 0.00 | 0.00 | 0.125540E+10 | 0.566299E+09 | 18267.29 | 18-OCT-21:51 | 9937.44 | 0.28 |
November | 0.00 | 0.00 | 0.134108E+09 | 78270230.10 | 15986.71 | 05-NOV-21:51 | 10055.52 | 0.05 |
December | 0.00 | 0.00 | 17422881.44 | 11032430.00 | 12892.81 | 11-DEC-16:01 | 11729.04 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.407072E+11 | 0.234938E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 4765423.11 | 3314265.04 | 4782.90 | 4782.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.954976E+10 | 0.566886E+10 | 18769.18 | 13663.55 | 0.82 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.203439E+09 | 0.202136E+09 | 12712.09 | 29-JAN-13:30 | 12712.09 | 0.00 |
February | 0.00 | 0.00 | 0.282952E+10 | 0.282217E+10 | 23664.91 | 26-FEB-14:50 | 23664.91 | 0.00 |
March | 0.00 | 0.00 | 0.625097E+10 | 0.417849E+10 | 24237.53 | 30-MAR-13:30 | 13535.98 | 0.14 |
April | 0.00 | 0.00 | 0.872971E+10 | 0.412144E+10 | 21681.31 | 15-APR-14:00 | 15189.22 | 0.36 |
May | 0.00 | 0.00 | 0.125558E+11 | 0.438822E+10 | 19750.59 | 19-MAY-19:10 | 9936.59 | 0.53 |
June | 0.00 | 0.00 | 0.247158E+11 | 0.990409E+10 | 26283.86 | 25-JUN-08:00 | 9528.39 | 0.78 |
July | 0.00 | 0.00 | 0.316989E+11 | 0.131808E+11 | 31402.85 | 13-JUL-21:00 | 12332.47 | 0.88 |
August | 0.00 | 0.00 | 0.399439E+11 | 0.183057E+11 | 31373.38 | 19-AUG-13:30 | 21662.10 | 0.98 |
September | 0.00 | 0.00 | 0.257421E+11 | 0.118540E+11 | 35551.68 | 24-SEP-12:30 | 27636.19 | 0.75 |
October | 0.00 | 0.00 | 0.158466E+11 | 0.947929E+10 | 39345.42 | 10-OCT-13:30 | 33786.92 | 0.37 |
November | 0.00 | 0.00 | 0.676800E+10 | 0.613738E+10 | 27712.67 | 12-NOV-14:00 | 27712.67 | 0.06 |
December | 0.00 | 0.00 | 0.263946E+10 | 0.217541E+10 | 26824.40 | 10-DEC-14:00 | 26824.40 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.177924E+12 | 0.867492E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.203439E+09 | 0.202136E+09 | 12712.09 | 9528.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.399439E+11 | 0.183057E+11 | 39345.42 | 33786.92 | 0.98 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.722444E+09 | 0.284172E+09 | 84932.09 | 19-JAN-22:53 | 51170.67 | 0.05 |
February | 0.00 | 0.00 | 0.326834E+10 | 0.200583E+10 | 98111.36 | 18-FEB-09:02 | 72022.04 | 0.12 |
March | 0.00 | 0.00 | 0.109395E+11 | 0.666732E+10 | 100092.33 | 28-MAR-21:51 | 78030.14 | 0.25 |
April | 0.00 | 0.00 | 0.226849E+11 | 0.128476E+11 | 110455.69 | 30-APR-21:52 | 73117.98 | 0.42 |
May | 0.00 | 0.00 | 0.387006E+11 | 0.230966E+11 | 113868.02 | 26-MAY-21:51 | 73807.82 | 0.46 |
June | 0.00 | 0.00 | 0.550657E+11 | 0.357730E+11 | 120107.90 | 26-JUN-21:51 | 75237.91 | 0.61 |
July | 0.00 | 0.00 | 0.625376E+11 | 0.404013E+11 | 122413.74 | 25-JUL-21:51 | 73055.01 | 0.64 |
August | 0.00 | 0.00 | 0.626550E+11 | 0.392414E+11 | 119036.04 | 07-AUG-21:51 | 71887.64 | 0.65 |
September | 0.00 | 0.00 | 0.394254E+11 | 0.225566E+11 | 118571.79 | 02-SEP-21:51 | 73103.83 | 0.51 |
October | 0.00 | 0.00 | 0.166665E+11 | 0.771697E+10 | 122792.15 | 18-OCT-21:51 | 67483.04 | 0.45 |
November | 0.00 | 0.00 | 0.635435E+10 | 0.339229E+10 | 108380.75 | 05-NOV-21:51 | 71009.26 | 0.18 |
December | 0.00 | 0.00 | 0.161785E+10 | 0.705632E+09 | 104088.92 | 13-DEC-21:02 | 70661.91 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.320638E+12 | 0.194689E+12 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.722444E+09 | 0.284172E+09 | 84932.09 | 51170.67 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.626550E+11 | 0.404013E+11 | 122792.15 | 78030.14 | 0.65 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 36917005.37 | 32148763.89 | 11763.41 | 29-JAN-16:01 | 11763.41 | 0.01 |
February | 0.00 | 0.00 | 0.344643E+09 | 0.308582E+09 | 12539.78 | 28-FEB-16:01 | 12539.78 | 0.02 |
March | 0.00 | 0.00 | 0.118699E+10 | 0.750768E+09 | 13999.13 | 30-MAR-08:52 | 10057.23 | 0.20 |
April | 0.00 | 0.00 | 0.274284E+10 | 0.156500E+10 | 15039.49 | 30-APR-21:52 | 9559.07 | 0.46 |
May | 0.00 | 0.00 | 0.508130E+10 | 0.280365E+10 | 15996.88 | 07-MAY-08:51 | 12757.88 | 0.64 |
June | 0.00 | 0.00 | 0.802228E+10 | 0.476018E+10 | 17316.28 | 29-JUN-08:51 | 11535.63 | 0.79 |
July | 0.00 | 0.00 | 0.959771E+10 | 0.585461E+10 | 17584.65 | 23-JUL-08:51 | 11799.03 | 0.79 |
August | 0.00 | 0.00 | 0.101521E+11 | 0.614381E+10 | 17780.05 | 29-AUG-08:31 | 11033.75 | 0.84 |
September | 0.00 | 0.00 | 0.586160E+10 | 0.324228E+10 | 16795.81 | 09-SEP-21:51 | 10799.44 | 0.68 |
October | 0.00 | 0.00 | 0.216454E+10 | 0.109672E+10 | 16868.39 | 18-OCT-21:51 | 9193.82 | 0.43 |
November | 0.00 | 0.00 | 0.492388E+09 | 0.330461E+09 | 14716.60 | 05-NOV-21:51 | 9264.64 | 0.11 |
December | 0.00 | 0.00 | 0.127565E+09 | 86939173.60 | 13046.45 | 12-DEC-22:51 | 10255.42 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.458109E+11 | 0.269751E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 36917005.37 | 32148763.89 | 11763.41 | 9193.82 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.101521E+11 | 0.614381E+10 | 17780.05 | 12757.88 | 0.84 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4957936.94 | 3584133.30 | 2304.44 | 20-JAN-09:05 | 684.06 | 0.00 |
February | 0.00 | 0.00 | 0.145741E+09 | 0.119279E+09 | 11964.04 | 28-FEB-16:01 | 11964.04 | 0.02 |
March | 0.00 | 0.00 | 0.707508E+09 | 0.397089E+09 | 13829.56 | 30-MAR-08:52 | 9889.11 | 0.15 |
April | 0.00 | 0.00 | 0.220910E+10 | 0.121255E+10 | 14849.17 | 30-APR-21:52 | 9394.88 | 0.43 |
May | 0.00 | 0.00 | 0.478652E+10 | 0.263117E+10 | 15871.75 | 07-MAY-08:51 | 12651.15 | 0.63 |
June | 0.00 | 0.00 | 0.794510E+10 | 0.471046E+10 | 17218.91 | 29-JUN-08:51 | 11491.15 | 0.80 |
July | 0.00 | 0.00 | 0.945143E+10 | 0.574649E+10 | 17506.62 | 23-JUL-08:51 | 11663.48 | 0.79 |
August | 0.00 | 0.00 | 0.959337E+10 | 0.564761E+10 | 17549.18 | 13-AUG-08:31 | 11638.25 | 0.83 |
September | 0.00 | 0.00 | 0.500820E+10 | 0.265239E+10 | 16598.16 | 06-SEP-08:31 | 11601.39 | 0.67 |
October | 0.00 | 0.00 | 0.132804E+10 | 0.616563E+09 | 16660.47 | 18-OCT-21:51 | 9071.24 | 0.28 |
November | 0.00 | 0.00 | 0.148917E+09 | 74559392.95 | 14342.11 | 05-NOV-21:51 | 8874.86 | 0.06 |
December | 0.00 | 0.00 | 14510196.42 | 6766894.65 | 9066.92 | 12-DEC-22:51 | 5735.20 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.413434E+11 | 0.238185E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 4957936.94 | 3584133.30 | 2304.44 | 684.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.959337E+10 | 0.574649E+10 | 17549.18 | 12651.15 | 0.83 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10776280.83 | 10311860.22 | 3615.79 | 29-JAN-16:01 | 3615.79 | 0.00 |
February | 0.00 | 0.00 | 57258693.09 | 53231155.45 | 3622.83 | 28-FEB-16:01 | 3622.83 | 0.02 |
March | 0.00 | 0.00 | 0.329075E+09 | 0.212127E+09 | 4091.55 | 28-MAR-21:51 | 3010.95 | 0.18 |
April | 0.00 | 0.00 | 0.752929E+09 | 0.450859E+09 | 4548.79 | 30-APR-21:52 | 2809.11 | 0.45 |
May | 0.00 | 0.00 | 0.138585E+10 | 0.790996E+09 | 4640.74 | 26-MAY-21:51 | 2801.37 | 0.62 |
June | 0.00 | 0.00 | 0.216984E+10 | 0.132889E+10 | 5155.46 | 26-JUN-21:51 | 3068.34 | 0.78 |
July | 0.00 | 0.00 | 0.254457E+10 | 0.157210E+10 | 5140.05 | 25-JUL-21:51 | 2862.20 | 0.78 |
August | 0.00 | 0.00 | 0.273484E+10 | 0.167601E+10 | 5057.39 | 20-AUG-21:51 | 2980.94 | 0.83 |
September | 0.00 | 0.00 | 0.155415E+10 | 0.870734E+09 | 4884.18 | 09-SEP-21:51 | 3308.59 | 0.66 |
October | 0.00 | 0.00 | 0.541428E+09 | 0.280539E+09 | 5086.03 | 18-OCT-21:51 | 2565.26 | 0.36 |
November | 0.00 | 0.00 | 0.107965E+09 | 76550771.45 | 4441.52 | 05-NOV-21:51 | 2698.95 | 0.08 |
December | 0.00 | 0.00 | 27279548.47 | 21205799.16 | 3852.66 | 12-DEC-22:51 | 2919.23 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.122160E+11 | 0.734356E+10 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 10776280.83 | 10311860.22 | 3615.79 | 2565.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.273484E+10 | 0.167601E+10 | 5155.46 | 3622.83 | 0.83 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 925457.11 | 547871.02 | 626.83 | 19-JAN-22:57 | 140.42 | 0.00 |
February | 0.00 | 0.00 | 17245678.84 | 15593862.46 | 3582.38 | 28-FEB-16:01 | 3582.38 | 0.00 |
March | 0.00 | 0.00 | 0.204691E+09 | 0.122295E+09 | 4020.78 | 28-MAR-21:51 | 2937.46 | 0.14 |
April | 0.00 | 0.00 | 0.610754E+09 | 0.347766E+09 | 4479.83 | 30-APR-21:52 | 2749.70 | 0.41 |
May | 0.00 | 0.00 | 0.130849E+10 | 0.740655E+09 | 4583.27 | 26-MAY-21:51 | 2755.94 | 0.61 |
June | 0.00 | 0.00 | 0.215105E+10 | 0.131972E+10 | 5097.04 | 26-JUN-21:51 | 3030.68 | 0.77 |
July | 0.00 | 0.00 | 0.250855E+10 | 0.154735E+10 | 5078.67 | 25-JUL-21:51 | 2823.93 | 0.78 |
August | 0.00 | 0.00 | 0.259294E+10 | 0.155875E+10 | 4982.06 | 20-AUG-21:51 | 2920.91 | 0.83 |
September | 0.00 | 0.00 | 0.132959E+10 | 0.709660E+09 | 4915.59 | 09-SEP-21:51 | 3127.95 | 0.63 |
October | 0.00 | 0.00 | 0.327435E+09 | 0.156852E+09 | 5007.16 | 18-OCT-21:51 | 2522.45 | 0.24 |
November | 0.00 | 0.00 | 28898524.26 | 17621134.51 | 4321.51 | 05-NOV-21:51 | 2568.27 | 0.03 |
December | 0.00 | 0.00 | 2666607.63 | 1705361.73 | 3088.39 | 11-DEC-16:01 | 2652.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110832E+11 | 0.653852E+10 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 925457.11 | 547871.02 | 626.83 | 140.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.259294E+10 | 0.155875E+10 | 5097.04 | 3582.38 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.778744E+09 | 0.739107E+09 | 17166.02 | 29-JAN-17:41 | 17166.02 | 0.02 |
February | 0.00 | 0.00 | 0.131648E+10 | 0.117974E+10 | 17310.92 | 21-FEB-22:11 | 17310.92 | 0.07 |
March | 0.00 | 0.00 | 0.321050E+10 | 0.222985E+10 | 18915.89 | 28-MAR-21:51 | 14572.30 | 0.28 |
April | 0.00 | 0.00 | 0.449148E+10 | 0.266521E+10 | 20531.75 | 30-APR-21:52 | 13396.29 | 0.50 |
May | 0.00 | 0.00 | 0.682015E+10 | 0.374238E+10 | 21137.52 | 26-MAY-21:51 | 13455.63 | 0.62 |
June | 0.00 | 0.00 | 0.100839E+11 | 0.597928E+10 | 22958.97 | 26-JUN-21:51 | 13897.82 | 0.76 |
July | 0.00 | 0.00 | 0.120873E+11 | 0.732867E+10 | 23324.63 | 25-JUL-21:51 | 13507.89 | 0.77 |
August | 0.00 | 0.00 | 0.138146E+11 | 0.865670E+10 | 22879.39 | 20-AUG-21:51 | 13815.05 | 0.82 |
September | 0.00 | 0.00 | 0.929747E+10 | 0.561852E+10 | 22620.70 | 09-SEP-21:51 | 14765.48 | 0.68 |
October | 0.00 | 0.00 | 0.540515E+10 | 0.325903E+10 | 23402.35 | 18-OCT-21:51 | 12411.20 | 0.54 |
November | 0.00 | 0.00 | 0.297433E+10 | 0.225405E+10 | 20538.03 | 05-NOV-21:51 | 13553.47 | 0.24 |
December | 0.00 | 0.00 | 0.163179E+10 | 0.138233E+10 | 19282.04 | 13-DEC-21:02 | 13016.35 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.719119E+11 | 0.450349E+11 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 0.778744E+09 | 0.739107E+09 | 17166.02 | 12411.20 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.138146E+11 | 0.865670E+10 | 23402.35 | 17310.92 | 0.82 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 55479.84 | 222460.63 | 17-JAN-10:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 36327.68 | 189632.31 | 07-FEB-10:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15760.90 | 162608.51 | 22-MAR-10:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9134.11 | 130752.84 | 06-APR-06:47 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 4033.96 | 56584.88 | 12-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1199.88 | 39923.00 | 03-JUN-21:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 833.23 | 35946.50 | 28-JUL-15:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 791.71 | 39142.87 | 10-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1279.26 | 64433.91 | 30-SEP-15:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7839.21 | 136008.83 | 26-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17783.15 | 169027.24 | 21-NOV-19:02 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 35160.66 | 183238.80 | 21-DEC-09:02 |
Annual Sum or Average | 0.00 | 15386.17 | ||||
Minimum of Months | 0.00 | 0.00 | 791.71 | 35946.50 | ||
Maximum of Months | 0.00 | 0.00 | 55479.84 | 222460.63 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10180.78 | 295824.86 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 32021.41 | 357434.98 | 28-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 71296.51 | 430428.99 | 30-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 137712.56 | 501074.89 | 02-APR-21:52 | 0.00 | 0.00 | 01-APR-00:10 |
May | 243409.87 | 652945.05 | 30-MAY-21:53 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 358882.20 | 738561.71 | 26-JUN-21:53 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 437155.74 | 763674.22 | 25-JUL-21:53 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 453839.67 | 758076.04 | 20-AUG-21:53 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 322794.19 | 718806.47 | 09-SEP-21:53 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 138083.09 | 755205.75 | 18-OCT-21:53 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 62208.20 | 474137.38 | 19-NOV-22:52 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18857.71 | 332659.21 | 13-DEC-09:53 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 191512.43 | 0.00 | ||||
Minimum of Months | 10180.78 | 295824.86 | 0.00 | 0.00 | ||
Maximum of Months | 453839.67 | 763674.22 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 26219.88 | 61209.15 | 29-JAN-08:21 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26286.97 | 60970.55 | 24-FEB-07:32 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25484.72 | 58838.69 | 18-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23942.04 | 58090.99 | 06-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22133.30 | 46364.97 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20523.47 | 42531.81 | 01-JUN-06:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19531.82 | 39624.06 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 19480.66 | 39521.57 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20327.61 | 41915.22 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21861.22 | 54206.98 | 26-OCT-06:41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23669.18 | 55134.59 | 23-NOV-08:62 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 25258.99 | 61994.46 | 20-DEC-07:21 |
Annual Sum or Average | 0.00 | 22873.95 | ||||
Minimum of Months | 0.00 | 0.00 | 19480.66 | 39521.57 | ||
Maximum of Months | 0.00 | 0.00 | 26286.97 | 61994.46 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.91 | 2194.93 | 01-JAN-00:01 | 0.91 |
February | 0.530997E+10 | 0.91 | 2194.93 | 01-FEB-00:03 | 0.91 |
March | 0.587890E+10 | 0.91 | 2194.93 | 01-MAR-00:03 | 0.91 |
April | 0.568926E+10 | 0.90 | 2194.93 | 01-APR-00:10 | 0.91 |
May | 0.587890E+10 | 0.90 | 2194.93 | 01-MAY-00:10 | 0.90 |
June | 0.568926E+10 | 0.90 | 2194.93 | 01-JUN-00:10 | 0.90 |
July | 0.587890E+10 | 0.90 | 2194.93 | 01-JUL-00:10 | 0.90 |
August | 0.587890E+10 | 0.90 | 2194.93 | 01-AUG-00:10 | 0.90 |
September | 0.568926E+10 | 0.90 | 2194.93 | 01-SEP-00:10 | 0.90 |
October | 0.587890E+10 | 0.90 | 2194.93 | 01-OCT-00:10 | 0.90 |
November | 0.568926E+10 | 0.91 | 2194.93 | 01-NOV-00:10 | 0.91 |
December | 0.587890E+10 | 0.91 | 2194.93 | 01-DEC-00:01 | 0.91 |
Annual Sum or Average | 0.692193E+11 | 0.91 | |||
Minimum of Months | 0.530997E+10 | 0.90 | 2194.93 | 0.90 | |
Maximum of Months | 0.587890E+10 | 0.91 | 2194.93 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.292461E+11 | 0.77 | 23434.26 | 23-JAN-22:47 | 1.19 |
February | 0.264620E+11 | 0.77 | 22852.51 | 07-FEB-23:00 | 1.16 |
March | 0.296950E+11 | 0.77 | 22852.51 | 18-MAR-22:20 | 1.17 |
April | 0.292003E+11 | 0.77 | 22852.51 | 05-APR-20:05 | 1.17 |
May | 0.306317E+11 | 0.78 | 19125.15 | 16-MAY-18:10 | 1.04 |
June | 0.304174E+11 | 0.79 | 16064.52 | 13-JUN-21:00 | 0.94 |
July | 0.317010E+11 | 0.79 | 17582.20 | 07-JUL-20:10 | 0.99 |
August | 0.318349E+11 | 0.79 | 17800.46 | 18-AUG-20:10 | 1.00 |
September | 0.296473E+11 | 0.78 | 16343.64 | 07-SEP-20:10 | 0.95 |
October | 0.297863E+11 | 0.77 | 27701.65 | 25-OCT-21:55 | 1.31 |
November | 0.285482E+11 | 0.77 | 22852.51 | 07-NOV-06:35 | 1.17 |
December | 0.293381E+11 | 0.77 | 22852.51 | 01-DEC-20:40 | 1.17 |
Annual Sum or Average | 0.356508E+12 | 0.78 | |||
Minimum of Months | 0.264620E+11 | 0.77 | 16064.52 | 0.94 | |
Maximum of Months | 0.318349E+11 | 0.79 | 27701.65 | 1.31 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:01 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:03 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:03 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.329199E+09 | 0.44 | 735.70 | 01-JAN-09:02 | 0.59 |
February | 0.225534E+09 | 0.41 | 735.70 | 01-FEB-09:02 | 0.60 |
March | 0.131596E+09 | 0.36 | 735.70 | 02-MAR-09:02 | 0.59 |
April | 0.165513E+09 | 0.36 | 735.70 | 02-APR-15:02 | 0.59 |
May | 0.236943E+09 | 0.38 | 735.70 | 01-MAY-15:02 | 0.59 |
June | 0.370881E+09 | 0.46 | 735.70 | 01-JUN-08:51 | 0.59 |
July | 0.427886E+09 | 0.46 | 735.70 | 01-JUL-08:31 | 0.59 |
August | 0.454994E+09 | 0.49 | 735.70 | 01-AUG-08:61 | 0.59 |
September | 0.268996E+09 | 0.40 | 735.70 | 01-SEP-08:51 | 0.59 |
October | 0.146744E+09 | 0.36 | 735.70 | 01-OCT-15:02 | 0.59 |
November | 0.134350E+09 | 0.38 | 735.70 | 01-NOV-08:62 | 0.59 |
December | 0.236138E+09 | 0.41 | 735.70 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.312877E+10 | 0.41 | |||
Minimum of Months | 0.131596E+09 | 0.36 | 735.70 | 0.59 | |
Maximum of Months | 0.454994E+09 | 0.49 | 735.70 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.403414E+09 | 0.49 | 727.97 | 01-JAN-09:02 | 0.59 |
February | 0.274532E+09 | 0.43 | 727.97 | 01-FEB-09:02 | 0.60 |
March | 0.127131E+09 | 0.34 | 727.97 | 02-MAR-09:02 | 0.59 |
April | 0.142949E+09 | 0.34 | 727.97 | 02-APR-15:02 | 0.59 |
May | 0.224118E+09 | 0.36 | 727.97 | 01-MAY-15:02 | 0.59 |
June | 0.368243E+09 | 0.46 | 727.97 | 01-JUN-08:51 | 0.59 |
July | 0.422405E+09 | 0.46 | 727.97 | 01-JUL-08:31 | 0.59 |
August | 0.429271E+09 | 0.49 | 727.97 | 01-AUG-08:61 | 0.59 |
September | 0.230546E+09 | 0.38 | 727.97 | 01-SEP-08:51 | 0.59 |
October | 0.120214E+09 | 0.33 | 727.97 | 01-OCT-15:02 | 0.59 |
November | 0.153532E+09 | 0.36 | 727.97 | 01-NOV-08:62 | 0.59 |
December | 0.283009E+09 | 0.43 | 727.97 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.317936E+10 | 0.41 | |||
Minimum of Months | 0.120214E+09 | 0.33 | 727.97 | 0.59 | |
Maximum of Months | 0.429271E+09 | 0.49 | 727.97 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.442608E+09 | 0.16 | 1317.66 | 08-JAN-05:10 | 0.60 |
February | 0.299809E+09 | 0.15 | 1386.74 | 12-FEB-06:00 | 0.60 |
March | 0.333105E+09 | 0.15 | 1021.91 | 11-MAR-12:30 | 0.60 |
April | 0.467212E+09 | 0.24 | 1047.96 | 15-APR-14:00 | 0.60 |
May | 0.624515E+09 | 0.33 | 824.34 | 19-MAY-19:10 | 0.59 |
June | 0.110329E+10 | 0.48 | 971.27 | 24-JUN-19:10 | 0.59 |
July | 0.134355E+10 | 0.52 | 1094.78 | 08-JUL-17:30 | 0.59 |
August | 0.165085E+10 | 0.58 | 1184.66 | 19-AUG-13:50 | 0.59 |
September | 0.111391E+10 | 0.45 | 1327.72 | 24-SEP-12:40 | 0.59 |
October | 0.741840E+09 | 0.27 | 1453.56 | 10-OCT-13:30 | 0.59 |
November | 0.349857E+09 | 0.15 | 1208.04 | 06-NOV-14:40 | 0.60 |
December | 0.157369E+09 | 0.07 | 1156.57 | 10-DEC-14:00 | 0.60 |
Annual Sum or Average | 0.862792E+10 | 0.30 | |||
Minimum of Months | 0.157369E+09 | 0.07 | 824.34 | 0.59 | |
Maximum of Months | 0.165085E+10 | 0.58 | 1453.56 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178203E+10 | 0.41 | 4777.01 | 01-JAN-16:02 | 0.59 |
February | 0.119870E+10 | 0.39 | 4777.01 | 01-FEB-09:02 | 0.60 |
March | 0.765212E+09 | 0.33 | 4777.01 | 02-MAR-17:42 | 0.60 |
April | 0.112510E+10 | 0.31 | 4777.01 | 01-APR-08:62 | 0.60 |
May | 0.174271E+10 | 0.29 | 4777.01 | 01-MAY-08:53 | 0.59 |
June | 0.259191E+10 | 0.37 | 4777.01 | 01-JUN-08:51 | 0.59 |
July | 0.287087E+10 | 0.38 | 4777.01 | 01-JUL-08:31 | 0.59 |
August | 0.285397E+10 | 0.38 | 4777.01 | 01-AUG-08:61 | 0.59 |
September | 0.172041E+10 | 0.30 | 4777.01 | 01-SEP-08:51 | 0.59 |
October | 0.870938E+09 | 0.32 | 4777.01 | 01-OCT-08:53 | 0.59 |
November | 0.743756E+09 | 0.36 | 4777.01 | 01-NOV-21:51 | 0.59 |
December | 0.115824E+10 | 0.41 | 4777.01 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.194239E+11 | 0.35 | |||
Minimum of Months | 0.743756E+09 | 0.29 | 4777.01 | 0.59 | |
Maximum of Months | 0.287087E+10 | 0.41 | 4777.01 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.316479E+09 | 0.44 | 666.72 | 01-JAN-09:02 | 0.59 |
February | 0.221178E+09 | 0.42 | 666.72 | 01-FEB-09:02 | 0.60 |
March | 0.124176E+09 | 0.36 | 666.72 | 03-MAR-09:02 | 0.60 |
April | 0.159692E+09 | 0.38 | 666.72 | 02-APR-15:02 | 0.59 |
May | 0.240119E+09 | 0.40 | 666.72 | 01-MAY-15:02 | 0.59 |
June | 0.375949E+09 | 0.47 | 666.72 | 01-JUN-08:51 | 0.59 |
July | 0.438659E+09 | 0.47 | 666.72 | 01-JUL-08:31 | 0.59 |
August | 0.457436E+09 | 0.50 | 666.72 | 01-AUG-07:52 | 0.59 |
September | 0.266866E+09 | 0.41 | 666.72 | 01-SEP-08:51 | 0.59 |
October | 0.146684E+09 | 0.39 | 666.72 | 01-OCT-15:02 | 0.59 |
November | 0.126125E+09 | 0.37 | 666.72 | 01-NOV-08:62 | 0.59 |
December | 0.216411E+09 | 0.41 | 666.72 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.308977E+10 | 0.42 | |||
Minimum of Months | 0.124176E+09 | 0.36 | 666.72 | 0.59 | |
Maximum of Months | 0.457436E+09 | 0.50 | 666.72 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.403418E+09 | 0.48 | 661.13 | 01-JAN-09:02 | 0.59 |
February | 0.258401E+09 | 0.43 | 661.13 | 01-FEB-09:02 | 0.60 |
March | 0.115949E+09 | 0.34 | 661.13 | 08-MAR-09:02 | 0.60 |
April | 0.135433E+09 | 0.36 | 661.13 | 02-APR-15:02 | 0.59 |
May | 0.226391E+09 | 0.39 | 661.13 | 01-MAY-15:02 | 0.59 |
June | 0.374335E+09 | 0.47 | 661.13 | 01-JUN-08:51 | 0.59 |
July | 0.432974E+09 | 0.47 | 661.13 | 01-JUL-08:31 | 0.59 |
August | 0.432646E+09 | 0.49 | 661.13 | 01-AUG-07:52 | 0.59 |
September | 0.226113E+09 | 0.40 | 661.13 | 01-SEP-08:51 | 0.59 |
October | 0.117534E+09 | 0.33 | 661.13 | 01-OCT-15:02 | 0.59 |
November | 0.142261E+09 | 0.36 | 661.13 | 01-NOV-08:62 | 0.59 |
December | 0.265578E+09 | 0.43 | 661.13 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.313103E+10 | 0.41 | |||
Minimum of Months | 0.115949E+09 | 0.33 | 661.13 | 0.59 | |
Maximum of Months | 0.432974E+09 | 0.49 | 661.13 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110628E+09 | 0.46 | 193.28 | 01-JAN-09:02 | 0.59 |
February | 74307128.60 | 0.43 | 193.28 | 01-FEB-09:02 | 0.60 |
March | 39908267.78 | 0.37 | 193.28 | 02-MAR-09:02 | 0.59 |
April | 47329038.50 | 0.38 | 193.28 | 02-APR-15:02 | 0.59 |
May | 67363379.63 | 0.39 | 193.28 | 01-MAY-15:02 | 0.59 |
June | 0.103215E+09 | 0.46 | 193.28 | 01-JUN-08:51 | 0.59 |
July | 0.118478E+09 | 0.46 | 193.28 | 01-JUL-08:31 | 0.59 |
August | 0.125012E+09 | 0.49 | 193.28 | 01-AUG-08:61 | 0.59 |
September | 72979698.21 | 0.40 | 193.28 | 01-SEP-08:51 | 0.59 |
October | 42235268.65 | 0.37 | 193.28 | 01-OCT-15:02 | 0.59 |
November | 42141260.71 | 0.38 | 193.28 | 01-NOV-08:62 | 0.59 |
December | 74891502.17 | 0.43 | 193.28 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.918489E+09 | 0.42 | |||
Minimum of Months | 39908267.78 | 0.37 | 193.28 | 0.59 | |
Maximum of Months | 0.125012E+09 | 0.49 | 193.28 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136834E+09 | 0.52 | 191.07 | 01-JAN-09:02 | 0.59 |
February | 87046048.35 | 0.45 | 191.07 | 01-FEB-09:02 | 0.60 |
March | 38696413.22 | 0.35 | 191.07 | 02-MAR-09:02 | 0.59 |
April | 41166379.34 | 0.36 | 191.07 | 02-APR-15:02 | 0.59 |
May | 63823654.15 | 0.38 | 191.07 | 01-MAY-15:02 | 0.59 |
June | 0.102701E+09 | 0.46 | 191.07 | 01-JUN-08:51 | 0.59 |
July | 0.117125E+09 | 0.46 | 191.07 | 01-JUL-08:31 | 0.59 |
August | 0.118012E+09 | 0.49 | 191.07 | 01-AUG-08:61 | 0.59 |
September | 62537088.48 | 0.39 | 191.07 | 01-SEP-08:51 | 0.59 |
October | 36275458.01 | 0.34 | 191.07 | 01-OCT-15:02 | 0.59 |
November | 49663094.31 | 0.37 | 191.07 | 01-NOV-08:62 | 0.59 |
December | 90930871.86 | 0.46 | 191.07 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.944810E+09 | 0.42 | |||
Minimum of Months | 36275458.01 | 0.34 | 191.07 | 0.59 | |
Maximum of Months | 0.136834E+09 | 0.52 | 191.07 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349852E+09 | 0.45 | 879.84 | 01-JAN-16:02 | 0.59 |
February | 0.259581E+09 | 0.43 | 879.84 | 01-FEB-09:02 | 0.60 |
March | 0.217920E+09 | 0.39 | 879.84 | 02-MAR-16:02 | 0.60 |
April | 0.247869E+09 | 0.38 | 879.84 | 01-APR-15:02 | 0.60 |
May | 0.321287E+09 | 0.38 | 879.84 | 01-MAY-08:53 | 0.59 |
June | 0.469767E+09 | 0.45 | 879.84 | 01-JUN-08:51 | 0.59 |
July | 0.548635E+09 | 0.46 | 879.84 | 01-JUL-08:31 | 0.59 |
August | 0.625834E+09 | 0.49 | 879.84 | 01-AUG-08:61 | 0.59 |
September | 0.424156E+09 | 0.40 | 879.84 | 01-SEP-08:51 | 0.59 |
October | 0.290038E+09 | 0.40 | 879.84 | 01-OCT-15:02 | 0.59 |
November | 0.221188E+09 | 0.42 | 879.84 | 01-NOV-15:02 | 0.59 |
December | 0.272376E+09 | 0.45 | 879.84 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.424850E+10 | 0.43 | |||
Minimum of Months | 0.217920E+09 | 0.38 | 879.84 | 0.59 | |
Maximum of Months | 0.625834E+09 | 0.49 | 879.84 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.119114E+10 | 0.107203E+10 | 895.64 | 17-JAN-10:20 | 806.07 | 806.07 | 35.98 | 2.22 |
February | 0.743287E+09 | 0.668958E+09 | 879.25 | 07-FEB-09:13 | 791.33 | 791.33 | 43.81 | 2.04 |
March | 0.386854E+09 | 0.348168E+09 | 824.25 | 18-MAR-06:40 | 741.82 | 741.82 | 52.64 | 1.61 |
April | 0.221902E+09 | 0.199712E+09 | 800.01 | 07-APR-04:25 | 720.01 | 720.01 | 40.23 | 1.49 |
May | 94297745.20 | 84867970.68 | 325.86 | 12-MAY-08:05 | 293.27 | 293.27 | 24.98 | 0.39 |
June | 24215226.27 | 21793703.65 | 262.15 | 03-JUN-21:56 | 235.94 | 235.94 | 28.19 | 0.30 |
July | 17445032.75 | 15700529.48 | 230.01 | 07-JUL-08:07 | 207.01 | 207.01 | 31.16 | 0.26 |
August | 16923869.95 | 15231482.95 | 286.67 | 10-AUG-08:05 | 258.00 | 258.00 | 31.82 | 0.33 |
September | 26714794.08 | 24043314.68 | 364.51 | 30-SEP-15:07 | 328.05 | 328.05 | 25.14 | 0.44 |
October | 0.194787E+09 | 0.175309E+09 | 792.28 | 26-OCT-03:32 | 713.05 | 713.05 | 46.25 | 1.45 |
November | 0.455035E+09 | 0.409532E+09 | 839.42 | 22-NOV-09:40 | 755.48 | 755.48 | 48.08 | 1.71 |
December | 0.876463E+09 | 0.788816E+09 | 864.60 | 21-DEC-10:10 | 778.14 | 778.14 | 40.85 | 1.90 |
Annual Sum or Average | 0.424906E+10 | 0.382416E+10 | ||||||
Minimum of Months | 16923869.95 | 15231482.95 | 230.01 | 207.01 | 207.01 | 24.98 | 0.26 | |
Maximum of Months | 0.119114E+10 | 0.107203E+10 | 895.64 | 806.07 | 806.07 | 52.64 | 2.22 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12155589.27 | 10940030.35 | 251.12 | 19-JAN-22:53 | 226.00 | 226.00 | 6.72 | 9.46 |
February | 33720833.25 | 30348749.92 | 366.15 | 28-FEB-16:01 | 329.53 | 329.53 | 6.72 | 11.28 |
March | 0.132048E+09 | 0.118843E+09 | 637.86 | 30-MAR-18:03 | 574.07 | 574.07 | 6.72 | 14.51 |
April | 0.328465E+09 | 0.295619E+09 | 849.81 | 13-APR-15:02 | 764.83 | 764.83 | 6.72 | 16.46 |
May | 0.697780E+09 | 0.628002E+09 | 1502.39 | 30-MAY-21:53 | 1352.15 | 1352.15 | 6.72 | 21.01 |
June | 0.138804E+10 | 0.124923E+10 | 1711.97 | 26-JUN-21:52 | 1540.77 | 1540.77 | 6.72 | 22.19 |
July | 0.193998E+10 | 0.174599E+10 | 1835.93 | 25-JUL-21:52 | 1652.34 | 1652.34 | 6.72 | 22.85 |
August | 0.212456E+10 | 0.191210E+10 | 1832.65 | 20-AUG-21:52 | 1649.38 | 1649.38 | 6.72 | 22.83 |
September | 0.115616E+10 | 0.104055E+10 | 1623.02 | 09-SEP-21:52 | 1460.72 | 1460.72 | 6.72 | 21.70 |
October | 0.399591E+09 | 0.359632E+09 | 1755.60 | 18-OCT-21:53 | 1580.04 | 1580.04 | 6.72 | 22.42 |
November | 97351736.21 | 87616562.59 | 696.00 | 19-NOV-22:52 | 626.40 | 626.40 | 6.72 | 15.08 |
December | 24293620.48 | 21864258.43 | 325.14 | 13-DEC-09:53 | 292.63 | 292.63 | 6.72 | 10.68 |
Annual Sum or Average | 0.833415E+10 | 0.750073E+10 | ||||||
Minimum of Months | 12155589.27 | 10940030.35 | 251.12 | 226.00 | 226.00 | 6.72 | 9.46 | |
Maximum of Months | 0.212456E+10 | 0.191210E+10 | 1835.93 | 1652.34 | 1652.34 | 6.72 | 22.85 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.434790E+10 | 0.391311E+10 | 4188.48 | 01-JAN-01:00 | 3769.63 | 3769.63 | 6.73 | 37.05 |
February | 0.573938E+10 | 0.516544E+10 | 4188.48 | 01-FEB-00:03 | 3769.63 | 3769.63 | 6.75 | 37.05 |
March | 0.931208E+10 | 0.838088E+10 | 4188.48 | 01-MAR-00:03 | 3769.63 | 3769.63 | 7.20 | 37.05 |
April | 0.103826E+11 | 0.934436E+10 | 4188.48 | 01-APR-00:10 | 3769.63 | 3769.63 | 6.80 | 37.05 |
May | 0.111920E+11 | 0.100728E+11 | 4188.48 | 01-MAY-00:10 | 3769.63 | 3769.63 | 8.19 | 37.05 |
June | 0.108565E+11 | 0.977089E+10 | 4188.48 | 01-JUN-00:10 | 3769.63 | 3769.63 | 9.03 | 37.05 |
July | 0.112184E+11 | 0.100966E+11 | 4188.48 | 01-JUL-00:10 | 3769.63 | 3769.63 | 9.91 | 37.05 |
August | 0.112184E+11 | 0.100966E+11 | 4188.48 | 01-AUG-00:10 | 3769.63 | 3769.63 | 9.28 | 37.05 |
September | 0.108565E+11 | 0.977089E+10 | 4188.48 | 01-SEP-00:10 | 3769.63 | 3769.63 | 8.98 | 37.05 |
October | 0.103559E+11 | 0.932027E+10 | 4188.48 | 01-OCT-00:10 | 3769.63 | 3769.63 | 7.83 | 37.05 |
November | 0.825060E+10 | 0.742554E+10 | 4188.48 | 01-NOV-00:10 | 3769.63 | 3769.63 | 6.73 | 37.05 |
December | 0.556612E+10 | 0.500951E+10 | 4188.48 | 01-DEC-00:12 | 3769.63 | 3769.63 | 6.72 | 37.05 |
Annual Sum or Average | 0.109297E+12 | 0.983669E+11 | ||||||
Minimum of Months | 0.434790E+10 | 0.391311E+10 | 4188.48 | 3769.63 | 3769.63 | 6.72 | 37.05 | |
Maximum of Months | 0.112184E+11 | 0.100966E+11 | 4188.48 | 3769.63 | 3769.63 | 9.91 | 37.05 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:01 | 14.37 | 14.37 | 47.28 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.51 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.29 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.32 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.47 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.79 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.84 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.23 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.15 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.03 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.31 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:01 | 14.37 | 14.37 | 28.71 | 0.08 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 28.71 | 0.08 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.23 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 43.50 | 60.00 | 55479.84 | 222460.63 | 17-JAN-10:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38.22 | 60.00 | 36327.68 | 189632.31 | 07-FEB-10:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27.01 | 27.01 | 15760.90 | 162608.51 | 22-MAR-10:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32.50 | 60.00 | 9134.11 | 130752.84 | 06-APR-06:47 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 31.65 | 60.00 | 4033.96 | 56584.88 | 12-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 35.05 | 60.00 | 1199.88 | 39923.00 | 03-JUN-21:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.92 | 60.00 | 833.23 | 35946.50 | 28-JUL-15:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.84 | 60.00 | 791.71 | 39142.87 | 10-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.61 | 60.00 | 1279.26 | 64433.91 | 30-SEP-15:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 29.93 | 60.00 | 7839.21 | 136008.83 | 26-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 38.12 | 60.00 | 17783.15 | 169027.24 | 21-NOV-19:02 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 50.34 | 60.00 | 35160.66 | 183238.80 | 21-DEC-09:02 |
Annual Sum or Average | 0.00 | 15386.17 | ||||||
Minimum of Months | 0.00 | 0.00 | 27.01 | 27.01 | 791.71 | 35946.50 | ||
Maximum of Months | 0.00 | 0.00 | 50.34 | 60.00 | 55479.84 | 222460.63 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10180.78 | 295824.86 | 19-JAN-22:53 | 8.60 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 32021.41 | 357434.98 | 28-FEB-16:01 | 9.00 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 71296.51 | 430428.99 | 30-MAR-18:03 | 9.47 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 137712.56 | 501074.89 | 02-APR-21:52 | 9.93 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 243409.87 | 652945.05 | 30-MAY-21:53 | 10.91 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 358882.20 | 738561.71 | 26-JUN-21:53 | 11.46 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 437155.74 | 763674.22 | 25-JUL-21:53 | 11.62 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 453839.67 | 758076.04 | 20-AUG-21:53 | 11.58 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 322794.19 | 718806.47 | 09-SEP-21:53 | 11.33 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 138083.09 | 755205.75 | 18-OCT-21:53 | 11.57 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 62208.20 | 474137.38 | 19-NOV-22:52 | 9.75 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18857.71 | 332659.21 | 13-DEC-09:53 | 8.84 | 6.70 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 191512.43 | 0.00 | ||||||
Minimum of Months | 10180.78 | 295824.86 | 8.60 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 453839.67 | 763674.22 | 11.62 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.28 | 59.92 | 26219.88 | 61209.15 | 29-JAN-08:21 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.51 | 59.53 | 26286.97 | 60970.55 | 24-FEB-07:32 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.29 | 59.09 | 25484.72 | 58838.69 | 18-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.32 | 58.75 | 23942.04 | 58090.99 | 06-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.47 | 58.37 | 22133.30 | 46364.97 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.79 | 59.63 | 20523.47 | 42531.81 | 01-JUN-06:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.84 | 59.16 | 19531.82 | 39624.06 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.23 | 59.41 | 19480.66 | 39521.57 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.15 | 59.51 | 20327.61 | 41915.22 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.03 | 59.44 | 21861.22 | 54206.98 | 26-OCT-06:41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.31 | 59.66 | 23669.18 | 55134.59 | 23-NOV-08:62 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 28.71 | 59.19 | 25258.99 | 61994.46 | 20-DEC-07:21 |
Annual Sum or Average | 0.00 | 22873.95 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.71 | 58.37 | 19480.66 | 39521.57 | ||
Maximum of Months | 0.00 | 0.00 | 54.23 | 59.92 | 26286.97 | 61994.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.934506E+11 | 0.00 | 0.197625E+11 | 0.292461E+11 | 0.00 | 0.00 |
February | 0.569802E+11 | 0.00 | 0.584604E+11 | 0.264620E+11 | 0.00 | 0.00 |
March | 0.371284E+11 | 0.00 | 0.140115E+12 | 0.296950E+11 | 0.00 | 0.00 |
April | 0.222463E+11 | 0.00 | 0.264713E+12 | 0.292003E+11 | 0.00 | 0.00 |
May | 0.107956E+11 | 0.00 | 0.490355E+12 | 0.306317E+11 | 0.00 | 0.00 |
June | 0.310586E+10 | 0.00 | 0.689394E+12 | 0.304174E+11 | 0.00 | 0.00 |
July | 0.223531E+10 | 0.00 | 0.879693E+12 | 0.317010E+11 | 0.00 | 0.00 |
August | 0.210323E+10 | 0.00 | 0.909664E+12 | 0.318349E+11 | 0.00 | 0.00 |
September | 0.322304E+10 | 0.00 | 0.632866E+12 | 0.296473E+11 | 0.00 | 0.00 |
October | 0.179814E+11 | 0.00 | 0.276161E+12 | 0.297863E+11 | 0.00 | 0.00 |
November | 0.351695E+11 | 0.00 | 0.121535E+12 | 0.285482E+11 | 0.00 | 0.00 |
December | 0.648731E+11 | 0.00 | 0.360171E+11 | 0.293381E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.349292E+12 | 0.00 | 0.451874E+13 | 0.356508E+12 | 0.00 | 0.00 |
Minimum of Months | 0.210323E+10 | 0.00 | 0.197625E+11 | 0.264620E+11 | 0.00 | 0.00 |
Maximum of Months | 0.934506E+11 | 0.00 | 0.909664E+12 | 0.318349E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.257617E+10 | 0.00 | 0.176252E+10 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.164496E+10 | 0.00 | 0.553714E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 11178.68 | 0.00 | 0.175170E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 16238.79 | 0.00 | 0.355772E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 21168.39 | 0.00 | 0.711301E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 9836.07 | 0.00 | 0.104696E+12 | 0.568926E+10 | 0.00 | 0.00 |
July | 9761.07 | 0.00 | 0.131516E+12 | 0.587890E+10 | 0.00 | 0.00 |
August | 13603.50 | 0.00 | 0.133952E+12 | 0.587890E+10 | 0.00 | 0.00 |
September | 14057.96 | 0.00 | 0.946430E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 7940.99 | 0.00 | 0.386077E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 96287905.66 | 0.00 | 0.147638E+11 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.359566E+09 | 0.00 | 0.325294E+10 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.467709E+10 | 0.00 | 0.652956E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 7940.99 | 0.00 | 0.176252E+10 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.257617E+10 | 0.00 | 0.133952E+12 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.292461E+11 | 0.197625E+11 | 0.934506E+11 | 0.318706E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264620E+11 | 0.584604E+11 | 0.569802E+11 | 0.195510E+12 | 0.173028E+09 | 0.00 | 0.00 | 0.00 |
March | 0.296950E+11 | 0.140115E+12 | 0.371284E+11 | 0.474124E+11 | 0.299515E+10 | 0.00 | 0.00 | 0.00 |
April | 0.292003E+11 | 0.264713E+12 | 0.222463E+11 | 0.222620E+11 | 0.122321E+11 | 0.00 | 0.00 | 0.00 |
May | 0.306317E+11 | 0.490355E+12 | 0.107956E+11 | 0.128565E+10 | 0.507621E+11 | 0.00 | 0.00 | 0.00 |
June | 0.304174E+11 | 0.689394E+12 | 0.310586E+10 | 0.104764E+09 | 0.161492E+12 | 0.00 | 0.00 | 0.00 |
July | 0.317010E+11 | 0.879693E+12 | 0.223531E+10 | 0.00 | 0.246686E+12 | 0.00 | 0.00 | 0.00 |
August | 0.318349E+11 | 0.909664E+12 | 0.210323E+10 | 0.00 | 0.320990E+12 | 0.00 | 0.00 | 0.00 |
September | 0.296473E+11 | 0.632866E+12 | 0.322304E+10 | 15122975.61 | 0.108426E+12 | 0.00 | 0.00 | 0.00 |
October | 0.297863E+11 | 0.276161E+12 | 0.179814E+11 | 0.211612E+11 | 0.232035E+11 | 0.00 | 0.00 | 0.00 |
November | 0.285482E+11 | 0.121536E+12 | 0.351695E+11 | 0.878411E+11 | 0.215159E+10 | 0.00 | 0.00 | 0.00 |
December | 0.293381E+11 | 0.360172E+11 | 0.648731E+11 | 0.188535E+12 | 70261879.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356508E+12 | 0.451874E+13 | 0.349292E+12 | 0.882833E+12 | 0.929182E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264620E+11 | 0.197625E+11 | 0.210323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.318349E+11 | 0.909664E+12 | 0.934506E+11 | 0.318706E+12 | 0.320990E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.176252E+10 | 0.257617E+10 | 0.780805E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.553714E+10 | 0.164496E+10 | 0.486614E+11 | 43088410.76 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.175170E+11 | 11178.68 | 0.212527E+11 | 0.969422E+09 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.355772E+11 | 16238.79 | 0.934661E+10 | 0.267010E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.711301E+11 | 21168.39 | 0.158807E+10 | 0.117355E+11 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.104696E+12 | 9836.07 | 0.377304E+09 | 0.389920E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.131516E+12 | 9761.07 | 0.00 | 0.604679E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.133952E+12 | 13603.50 | 0.00 | 0.773347E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.946430E+11 | 14057.96 | 0.315669E+09 | 0.279508E+11 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.386077E+11 | 7940.99 | 0.128329E+11 | 0.569905E+10 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.147638E+11 | 96287905.66 | 0.292871E+11 | 0.349670E+09 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.325294E+10 | 0.359566E+09 | 0.549059E+11 | 19635926.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.652956E+12 | 0.467709E+10 | 0.256648E+12 | 0.226232E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.176252E+10 | 7940.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.133952E+12 | 0.257617E+10 | 0.780805E+11 | 0.773347E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.292461E+11 | 0.934506E+11 | 0.197625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264620E+11 | 0.569802E+11 | 0.584604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296950E+11 | 0.371284E+11 | 0.140115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292003E+11 | 0.222463E+11 | 0.264713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306317E+11 | 0.107956E+11 | 0.490355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.304174E+11 | 0.310586E+10 | 0.689394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.317010E+11 | 0.223531E+10 | 0.879693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.318349E+11 | 0.210323E+10 | 0.909664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296473E+11 | 0.322304E+10 | 0.632866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.297863E+11 | 0.179814E+11 | 0.276161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285482E+11 | 0.351695E+11 | 0.121535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293381E+11 | 0.648731E+11 | 0.360171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356508E+12 | 0.349292E+12 | 0.451874E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264620E+11 | 0.210323E+10 | 0.197625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.318349E+11 | 0.934506E+11 | 0.909664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.257617E+10 | 0.176252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.164496E+10 | 0.553714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 11178.68 | 0.175170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 16238.79 | 0.355772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 21168.39 | 0.711301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 9836.07 | 0.104696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 9761.07 | 0.131516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 13603.50 | 0.133952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 14057.96 | 0.946430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 7940.99 | 0.386077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 96287905.66 | 0.147638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.359566E+09 | 0.325294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.467709E+10 | 0.652956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 7940.99 | 0.176252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.257617E+10 | 0.133952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.572590E+11 | 0.00 | 0.00 | 0.00 | 6621995.37 | 0.00 | 0.00 | 0.00 | 1.04 |
February | 0.456739E+11 | 0.00 | 0.00 | 0.00 | 9493118.72 | 0.00 | 0.00 | 0.00 | 1.05 |
March | 0.430602E+11 | 0.00 | 0.00 | 0.00 | 0.399461E+09 | 17663284.26 | 0.00 | 0.00 | 1.06 |
April | 0.279793E+11 | 0.00 | 0.110878E+09 | 0.00 | 0.189858E+10 | 0.178125E+09 | 0.00 | 1400156.47 | 1.06 |
May | 0.116873E+11 | 0.00 | 4493868.40 | 0.00 | 0.831398E+10 | 0.00 | 0.00 | 16599.09 | 1.04 |
June | 0.496140E+10 | 0.00 | 0.00 | 0.00 | 0.237100E+11 | 0.00 | 0.00 | 0.00 | 1.02 |
July | 89463244.41 | 0.00 | 0.00 | 0.00 | 0.372249E+11 | 0.00 | 0.00 | 0.00 | 1.01 |
August | 14950937.80 | 0.00 | 0.00 | 0.00 | 0.393004E+11 | 0.00 | 0.00 | 0.00 | 1.01 |
September | 0.634245E+10 | 0.103289E+10 | 0.00 | 611128.54 | 0.189723E+11 | 0.00 | 0.817023E+09 | 0.00 | 1.04 |
October | 0.304812E+11 | 0.536398E+09 | 0.00 | 1821537.94 | 0.534374E+10 | 0.00 | 0.386122E+10 | 0.00 | 1.06 |
November | 0.388481E+11 | 29506800.84 | 0.00 | 2382434.83 | 0.784702E+09 | 0.00 | 0.559330E+10 | 0.00 | 1.06 |
December | 0.552629E+11 | 0.00 | 0.00 | 28424.72 | 0.128953E+09 | 0.00 | 0.172947E+09 | 0.00 | 1.05 |
Annual Sum or Average | 0.321660E+12 | 0.159879E+10 | 0.115372E+09 | 4843526.03 | 0.136093E+12 | 0.195789E+09 | 0.104445E+11 | 1416755.56 | 1.04 |
Minimum of Months | 14950937.80 | 0.00 | 0.00 | 0.00 | 6621995.37 | 0.00 | 0.00 | 0.00 | 1.01 |
Maximum of Months | 0.572590E+11 | 0.103289E+10 | 0.110878E+09 | 2382434.83 | 0.393004E+11 | 0.178125E+09 | 0.559330E+10 | 1400156.47 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401273E+10 | 0.00 | 0.00 | 5651.48 | 791480.19 | 0.281642E+10 | 14598695.77 | 0.00 | 2.25 |
February | 0.391274E+10 | 530735.68 | 0.00 | 30808.49 | 603909.54 | 0.152753E+10 | 18779923.51 | 0.00 | 2.28 |
March | 0.489568E+10 | 5904017.70 | 0.00 | 10671.63 | 41840779.64 | 0.244236E+09 | 8874509.66 | 0.00 | 2.30 |
April | 0.328570E+10 | 10523135.57 | 0.00 | 28361.94 | 0.229821E+09 | 77209107.92 | 2526676.93 | 0.00 | 2.29 |
May | 0.139442E+10 | 30144739.32 | 0.00 | 5016.90 | 0.964105E+09 | 0.00 | 2471022.93 | 0.00 | 2.26 |
June | 0.592502E+09 | 0.697462E+09 | 0.00 | 1033.58 | 0.213642E+10 | 0.00 | 497281.42 | 0.00 | 2.22 |
July | 10692907.76 | 0.148991E+10 | 0.00 | 0.00 | 0.296167E+10 | 0.00 | 0.00 | 0.00 | 2.19 |
August | 1786979.67 | 0.223977E+10 | 0.00 | 0.00 | 0.247759E+10 | 0.00 | 0.00 | 0.00 | 2.20 |
September | 0.845307E+09 | 0.548079E+09 | 0.00 | 47249.98 | 0.184752E+10 | 0.00 | 10458972.64 | 0.00 | 2.26 |
October | 0.393693E+10 | 0.120155E+09 | 0.00 | 211581.18 | 0.587087E+09 | 59320175.70 | 0.107912E+09 | 0.00 | 2.30 |
November | 0.483389E+10 | 2697364.82 | 0.00 | 256577.99 | 94619304.10 | 0.348729E+09 | 0.128885E+09 | 0.00 | 2.29 |
December | 0.512957E+10 | 1792760.84 | 0.00 | 34360.95 | 13620045.40 | 0.143664E+10 | 59616160.61 | 0.00 | 2.26 |
Annual Sum or Average | 0.328520E+11 | 0.514697E+10 | 0.00 | 631314.12 | 0.113557E+11 | 0.651009E+10 | 0.354621E+09 | 0.00 | 2.26 |
Minimum of Months | 1786979.67 | 0.00 | 0.00 | 0.00 | 603909.54 | 0.00 | 0.00 | 0.00 | 2.19 |
Maximum of Months | 0.512957E+10 | 0.223977E+10 | 0.00 | 256577.99 | 0.296167E+10 | 0.281642E+10 | 0.128885E+09 | 0.00 | 2.30 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.522736E+10 | 0.00 | 0.00 | 0.00 | 604572.75 | 249836.01 | 0.00 | 0.00 | 1.49 |
February | 0.416992E+10 | 0.00 | 0.00 | 0.00 | 866699.62 | 0.00 | 0.00 | 0.00 | 1.50 |
March | 0.393230E+10 | 23309.54 | 0.00 | 3032.73 | 36446590.55 | 0.00 | 614562.40 | 0.00 | 1.52 |
April | 0.252240E+10 | 0.00 | 0.00 | 22623.22 | 0.183587E+09 | 0.00 | 48276559.06 | 0.00 | 1.52 |
May | 0.105164E+10 | 18604503.66 | 0.00 | 33910.51 | 0.740854E+09 | 0.00 | 15348564.32 | 0.00 | 1.49 |
June | 0.423923E+09 | 0.316041E+09 | 0.00 | 30344.66 | 0.184862E+10 | 0.00 | 29010494.98 | 0.00 | 1.47 |
July | 8167785.80 | 0.656148E+09 | 0.00 | 0.00 | 0.274657E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
August | 1364985.79 | 0.949931E+09 | 0.00 | 0.00 | 0.264552E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
September | 0.592213E+09 | 0.204359E+09 | 0.00 | 46640.88 | 0.162240E+10 | 0.00 | 61439390.80 | 0.00 | 1.49 |
October | 0.309541E+10 | 9161004.42 | 0.00 | 15825.71 | 0.527681E+09 | 0.00 | 39704564.08 | 0.00 | 1.52 |
November | 0.405739E+10 | 0.00 | 0.00 | 0.00 | 74335412.23 | 0.00 | 0.00 | 0.00 | 1.51 |
December | 0.506117E+10 | 0.00 | 0.00 | 0.00 | 11773083.88 | 0.00 | 0.00 | 0.00 | 1.49 |
Annual Sum or Average | 0.301433E+11 | 0.215427E+10 | 0.00 | 152377.71 | 0.104393E+11 | 249836.01 | 0.194394E+09 | 0.00 | 1.49 |
Minimum of Months | 1364985.79 | 0.00 | 0.00 | 0.00 | 604572.75 | 0.00 | 0.00 | 0.00 | 1.45 |
Maximum of Months | 0.522736E+10 | 0.949931E+09 | 0.00 | 46640.88 | 0.274657E+10 | 249836.01 | 61439390.80 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223065E+10 | 0.00 | 0.00 | 0.00 | 490668.22 | 0.201205E+10 | 0.00 | 0.00 | 0.57 |
February | 0.232244E+10 | 0.00 | 0.00 | 0.00 | 703409.08 | 0.106185E+10 | 0.00 | 0.00 | 0.58 |
March | 0.319169E+10 | 0.00 | 0.00 | 0.00 | 29598788.45 | 245274.84 | 0.00 | 0.00 | 0.58 |
April | 0.208610E+10 | 0.00 | 0.00 | 0.00 | 0.148998E+09 | 274749.26 | 0.00 | 0.00 | 0.58 |
May | 0.865989E+09 | 0.00 | 0.00 | 0.00 | 0.616373E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.367623E+09 | 0.00 | 0.00 | 0.00 | 0.175683E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 6628934.09 | 97797251.76 | 0.00 | 0.00 | 0.266045E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 1107815.64 | 93357286.01 | 0.00 | 0.00 | 0.281867E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.530539E+09 | 0.00 | 0.00 | 0.00 | 0.148232E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.254446E+10 | 0.00 | 0.00 | 0.00 | 0.435699E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.325359E+10 | 0.00 | 0.00 | 0.00 | 60330248.66 | 39373299.98 | 0.00 | 0.00 | 0.58 |
December | 0.370721E+10 | 0.00 | 0.00 | 0.00 | 9554975.97 | 0.400410E+09 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.211080E+11 | 0.191155E+09 | 0.00 | 0.00 | 0.100200E+11 | 0.351421E+10 | 0.00 | 0.00 | 0.57 |
Minimum of Months | 1107815.64 | 0.00 | 0.00 | 0.00 | 490668.22 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.370721E+10 | 97797251.76 | 0.00 | 0.00 | 0.281867E+10 | 0.201205E+10 | 0.00 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.776632E+09 | 0.00 | 0.00 | 0.00 | 322361.18 | 0.201076E+10 | 0.00 | 0.00 | 0.65 |
February | 0.116473E+10 | 0.00 | 0.00 | 0.00 | 462128.52 | 0.105870E+10 | 0.00 | 0.00 | 0.66 |
March | 0.204042E+10 | 0.00 | 0.00 | 0.00 | 19445931.04 | 56630661.52 | 0.00 | 0.00 | 0.66 |
April | 0.137071E+10 | 0.00 | 0.00 | 0.00 | 97889533.00 | 0.00 | 0.00 | 0.00 | 0.66 |
May | 0.568941E+09 | 0.00 | 0.00 | 0.00 | 0.404947E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
June | 0.241523E+09 | 0.00 | 0.00 | 0.00 | 0.115421E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 4355103.77 | 0.00 | 0.00 | 0.00 | 0.181212E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 727817.17 | 0.00 | 0.00 | 0.00 | 0.191316E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.348556E+09 | 0.00 | 0.00 | 0.00 | 0.973859E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.167167E+10 | 0.00 | 0.00 | 0.00 | 0.286247E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
November | 0.201062E+10 | 0.00 | 0.00 | 0.00 | 39636009.33 | 0.152799E+09 | 0.00 | 0.00 | 0.66 |
December | 0.183544E+10 | 0.00 | 0.00 | 0.00 | 6277466.53 | 0.863200E+09 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.120343E+11 | 0.00 | 0.00 | 0.00 | 0.670858E+10 | 0.414208E+10 | 0.00 | 0.00 | 0.65 |
Minimum of Months | 727817.17 | 0.00 | 0.00 | 0.00 | 322361.18 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.204042E+10 | 0.00 | 0.00 | 0.00 | 0.191316E+10 | 0.201076E+10 | 0.00 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.359135E+10 | 8174042.19 | 0.00 | 97217298.62 | 0.00 | 1686173.55 | 0.716564E+11 | 0.00 | 21.29 |
February | 0.251250E+10 | 11353878.23 | 0.00 | 79995953.20 | 364214.06 | 0.00 | 0.576214E+11 | 0.00 | 21.57 |
March | 0.111646E+10 | 0.500944E+09 | 0.00 | 82288273.46 | 10833175.22 | 0.00 | 0.555282E+11 | 0.00 | 21.85 |
April | 0.483003E+09 | 0.253038E+10 | 0.00 | 73320374.57 | 69807072.23 | 0.00 | 0.363680E+11 | 0.00 | 21.82 |
May | 0.115429E+09 | 0.106210E+11 | 0.00 | 41888265.51 | 0.289388E+09 | 0.00 | 0.149048E+11 | 0.00 | 21.47 |
June | 43877167.05 | 0.305920E+11 | 0.00 | 18230953.17 | 0.583379E+09 | 0.00 | 0.629772E+10 | 0.00 | 21.09 |
July | 0.00 | 0.480735E+11 | 0.00 | 690392.65 | 0.862909E+09 | 0.00 | 0.109741E+09 | 0.00 | 20.71 |
August | 0.00 | 0.510969E+11 | 0.00 | 237428.93 | 0.837020E+09 | 0.00 | 18217672.50 | 0.00 | 20.78 |
September | 72402129.14 | 0.257327E+11 | 0.00 | 25922320.78 | 0.450252E+09 | 0.00 | 0.936015E+10 | 0.00 | 21.36 |
October | 0.810490E+09 | 0.765213E+10 | 0.00 | 65713475.56 | 0.129735E+09 | 0.00 | 0.444095E+11 | 0.00 | 21.72 |
November | 0.186960E+10 | 0.102634E+10 | 0.00 | 80886147.96 | 25725047.94 | 0.00 | 0.569930E+11 | 0.00 | 21.74 |
December | 0.297791E+10 | 0.157187E+09 | 0.00 | 98520134.91 | 1989340.51 | 0.00 | 0.703274E+11 | 0.00 | 21.46 |
Annual Sum or Average | 0.135930E+11 | 0.178003E+12 | 0.00 | 0.664911E+09 | 0.326140E+10 | 1686173.55 | 0.423595E+12 | 0.00 | 21.40 |
Minimum of Months | 0.00 | 8174042.19 | 0.00 | 237428.93 | 0.00 | 0.00 | 18217672.50 | 0.00 | 20.71 |
Maximum of Months | 0.359135E+10 | 0.510969E+11 | 0.00 | 98520134.91 | 0.862909E+09 | 1686173.55 | 0.716564E+11 | 0.00 | 21.85 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.284625E+11 | 0.00 | 0.00 | 282245.92 | 3406172.74 | 0.120804E+09 | 0.869351E+09 | 0.00 | 3.45 |
February | 0.210303E+11 | 2405049.65 | 0.00 | 1247499.98 | 2477950.17 | 1118535.53 | 0.246080E+10 | 0.00 | 3.49 |
March | 0.163526E+11 | 49287909.19 | 0.00 | 3227678.10 | 0.156184E+09 | 0.00 | 0.580232E+10 | 0.00 | 3.53 |
April | 0.884069E+10 | 0.234484E+09 | 0.00 | 4376489.17 | 0.799848E+09 | 0.00 | 0.563836E+10 | 0.00 | 3.52 |
May | 0.261142E+10 | 0.147556E+10 | 0.00 | 4782680.42 | 0.280325E+10 | 0.00 | 0.339541E+10 | 0.00 | 3.47 |
June | 0.887175E+09 | 0.738524E+10 | 0.00 | 2137909.55 | 0.481666E+10 | 0.00 | 0.166269E+10 | 0.00 | 3.41 |
July | 6787307.56 | 0.130308E+11 | 0.00 | 206678.16 | 0.616955E+10 | 0.00 | 39023452.68 | 0.00 | 3.37 |
August | 210876.43 | 0.160359E+11 | 0.00 | 101765.78 | 0.430332E+10 | 0.00 | 7377709.99 | 0.00 | 3.38 |
September | 0.115209E+10 | 0.651766E+10 | 0.00 | 3368996.44 | 0.379144E+10 | 0.00 | 0.252752E+10 | 0.00 | 3.47 |
October | 0.108194E+11 | 0.167673E+10 | 0.00 | 5507405.72 | 0.135063E+10 | 0.00 | 0.683843E+10 | 0.00 | 3.52 |
November | 0.175847E+11 | 88200891.72 | 0.00 | 3041055.80 | 0.330606E+09 | 0.00 | 0.527168E+10 | 0.00 | 3.51 |
December | 0.260072E+11 | 7787632.91 | 0.00 | 1014886.70 | 58542113.66 | 0.00 | 0.250646E+10 | 0.00 | 3.47 |
Annual Sum or Average | 0.133755E+12 | 0.465041E+11 | 0.00 | 29295291.75 | 0.245859E+11 | 0.121923E+09 | 0.370194E+11 | 0.00 | 3.47 |
Minimum of Months | 210876.43 | 0.00 | 0.00 | 101765.78 | 2477950.17 | 0.00 | 7377709.99 | 0.00 | 3.37 |
Maximum of Months | 0.284625E+11 | 0.160359E+11 | 0.00 | 5507405.72 | 0.616955E+10 | 0.120804E+09 | 0.683843E+10 | 0.00 | 3.53 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.987778E+11 | 0.00 | 0.00 | 13053.88 | 11426853.69 | 2357176.29 | 25403425.61 | 0.00 | 1.67 |
February | 0.783089E+11 | 0.00 | 0.00 | 142781.77 | 16381237.47 | 2094899.78 | 0.503440E+09 | 0.00 | 1.69 |
March | 0.723409E+11 | 15411238.47 | 0.00 | 889265.00 | 0.673896E+09 | 0.00 | 0.199307E+10 | 0.00 | 1.71 |
April | 0.445209E+11 | 30791305.10 | 0.00 | 2694113.42 | 0.343913E+10 | 0.00 | 0.406448E+10 | 0.00 | 1.70 |
May | 0.163004E+11 | 0.206286E+10 | 0.00 | 4033162.00 | 0.122915E+11 | 0.00 | 0.386300E+10 | 0.00 | 1.68 |
June | 0.540846E+10 | 0.150851E+11 | 0.00 | 3241639.12 | 0.258393E+11 | 0.00 | 0.314964E+10 | 0.00 | 1.65 |
July | 39925011.15 | 0.254945E+11 | 0.00 | 192352.25 | 0.388743E+11 | 0.00 | 0.114260E+09 | 0.00 | 1.63 |
August | 4828076.67 | 0.317622E+11 | 0.00 | 197253.36 | 0.363181E+11 | 0.00 | 20773869.31 | 0.00 | 1.63 |
September | 0.690943E+10 | 0.107466E+11 | 0.00 | 4415964.44 | 0.237929E+11 | 0.00 | 0.544153E+10 | 0.00 | 1.68 |
October | 0.540041E+11 | 0.260659E+10 | 0.00 | 2314523.17 | 0.754012E+10 | 0.00 | 0.524972E+10 | 0.00 | 1.70 |
November | 0.751250E+11 | 11725540.56 | 0.00 | 305494.15 | 0.139327E+10 | 0.00 | 0.156229E+10 | 0.00 | 1.70 |
December | 0.953258E+11 | 0.00 | 0.00 | 58319.74 | 0.222520E+09 | 0.00 | 0.333810E+09 | 0.00 | 1.68 |
Annual Sum or Average | 0.547067E+12 | 0.878159E+11 | 0.00 | 18497922.30 | 0.150413E+12 | 4452076.07 | 0.263214E+11 | 0.00 | 1.68 |
Minimum of Months | 4828076.67 | 0.00 | 0.00 | 13053.88 | 11426853.69 | 0.00 | 20773869.31 | 0.00 | 1.63 |
Maximum of Months | 0.987778E+11 | 0.317622E+11 | 0.00 | 4415964.44 | 0.388743E+11 | 2357176.29 | 0.544153E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.348230E+09 | 0.00 | 0.00 | 527684.13 | 14566.65 | 0.107635E+10 | 75026289.71 | 3040.01 | 0.47 |
February | 0.332478E+09 | 206908.75 | 0.00 | 1302291.41 | 225862.24 | 0.766289E+09 | 0.213984E+09 | 0.00 | 0.47 |
March | 0.445165E+09 | 11708551.88 | 24405.82 | 3778079.60 | 8142066.71 | 0.344930E+09 | 0.518349E+09 | 10392.74 | 0.47 |
April | 0.279006E+09 | 47076827.83 | 242381.66 | 6320444.64 | 30295057.13 | 93031788.83 | 0.542339E+09 | 10461.04 | 0.47 |
May | 0.142806E+09 | 0.252088E+09 | 505444.93 | 4009058.55 | 72471485.65 | 730298.13 | 0.218127E+09 | 36627.14 | 0.48 |
June | 38244277.48 | 0.831345E+09 | 391720.63 | 2166455.95 | 0.174624E+09 | 79608.01 | 0.100773E+09 | 20263.25 | 0.48 |
July | 5498836.53 | 0.121624E+10 | 401691.71 | 87707.67 | 0.264507E+09 | 18612.36 | 345873.97 | 10606.93 | 0.47 |
August | 991576.61 | 0.136502E+10 | 356090.38 | 0.00 | 0.224661E+09 | 0.00 | 0.00 | 8125.92 | 0.48 |
September | 82613832.89 | 0.625090E+09 | 706940.28 | 2310929.48 | 0.210471E+09 | 485369.10 | 0.133431E+09 | 33963.70 | 0.48 |
October | 0.319380E+09 | 0.152498E+09 | 406540.28 | 4185311.58 | 68265480.46 | 0.242744E+09 | 0.485180E+09 | 24532.93 | 0.47 |
November | 0.379797E+09 | 7196217.71 | 74538.02 | 2293315.88 | 15092098.86 | 0.546017E+09 | 0.419240E+09 | 5558.06 | 0.47 |
December | 0.426698E+09 | 680323.31 | 1828.44 | 835074.28 | 1894947.12 | 0.952258E+09 | 0.142043E+09 | 2394.97 | 0.47 |
Annual Sum or Average | 0.280091E+10 | 0.450914E+10 | 3111582.15 | 27816353.16 | 0.107066E+10 | 0.402294E+10 | 0.284884E+10 | 165966.69 | 0.47 |
Minimum of Months | 991576.61 | 0.00 | 0.00 | 0.00 | 14566.65 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.445165E+09 | 0.136502E+10 | 706940.28 | 6320444.64 | 0.264507E+09 | 0.107635E+10 | 0.542339E+09 | 36627.14 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259113E+09 | 0.00 | 0.00 | 70861.62 | 14564.94 | 0.121817E+10 | 22612261.11 | 3039.65 | 0.47 |
February | 0.280572E+09 | 27892.75 | 634.79 | 547164.42 | 402840.04 | 0.909131E+09 | 0.123650E+09 | 1352.71 | 0.47 |
March | 0.470165E+09 | 9753581.85 | 29890.55 | 2286548.59 | 10087624.35 | 0.478778E+09 | 0.360839E+09 | 11990.52 | 0.47 |
April | 0.283566E+09 | 40373797.59 | 285387.19 | 5352286.35 | 36945351.77 | 0.115397E+09 | 0.516274E+09 | 11096.23 | 0.47 |
May | 0.144107E+09 | 0.245192E+09 | 524788.72 | 3795350.82 | 79311096.07 | 691796.26 | 0.217035E+09 | 35526.71 | 0.48 |
June | 38711269.00 | 0.831073E+09 | 389835.74 | 2168116.50 | 0.174785E+09 | 79598.69 | 0.100287E+09 | 15404.82 | 0.48 |
July | 5498192.26 | 0.121418E+10 | 482372.42 | 87113.97 | 0.266308E+09 | 18610.18 | 346416.87 | 11328.27 | 0.47 |
August | 991460.44 | 0.136017E+10 | 331865.18 | 0.00 | 0.229342E+09 | 0.00 | 0.00 | 9541.32 | 0.48 |
September | 83924290.70 | 0.609727E+09 | 985925.41 | 1946741.51 | 0.225447E+09 | 383640.98 | 0.132561E+09 | 42737.34 | 0.48 |
October | 0.337690E+09 | 0.131099E+09 | 614841.76 | 2432768.75 | 89425290.82 | 0.332719E+09 | 0.378525E+09 | 29263.90 | 0.47 |
November | 0.394479E+09 | 5207408.91 | 85643.66 | 887631.26 | 17065400.34 | 0.732327E+09 | 0.219496E+09 | 7338.96 | 0.47 |
December | 0.382336E+09 | 196114.51 | 1782.19 | 180228.31 | 2377637.46 | 0.109045E+10 | 48684521.65 | 3657.46 | 0.47 |
Annual Sum or Average | 0.268115E+10 | 0.444700E+10 | 3732967.60 | 19754812.08 | 0.113151E+10 | 0.487814E+10 | 0.212031E+10 | 182277.89 | 0.47 |
Minimum of Months | 991460.44 | 0.00 | 0.00 | 0.00 | 14564.94 | 0.00 | 0.00 | 1352.71 | 0.47 |
Maximum of Months | 0.470165E+09 | 0.136017E+10 | 985925.41 | 5352286.35 | 0.266308E+09 | 0.121817E+10 | 0.516274E+09 | 42737.34 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154011E+11 | 0.00 | 0.00 | 1389775.87 | 238730.50 | 0.437473E+10 | 0.563258E+09 | 0.00 | 0.53 |
February | 0.141828E+11 | 3282216.95 | 0.00 | 13002325.93 | 2585769.61 | 0.141820E+10 | 0.220335E+10 | 0.00 | 0.53 |
March | 0.128442E+11 | 0.250975E+09 | 0.00 | 21638117.39 | 18653798.87 | 0.00 | 0.492674E+10 | 0.00 | 0.54 |
April | 0.802366E+10 | 0.766777E+09 | 0.00 | 28157931.04 | 0.285745E+09 | 0.00 | 0.443202E+10 | 0.00 | 0.54 |
May | 0.295461E+10 | 0.410847E+10 | 0.00 | 16716177.13 | 0.299613E+09 | 0.00 | 0.198685E+10 | 0.00 | 0.54 |
June | 0.869455E+09 | 0.135477E+11 | 0.00 | 10277077.81 | 97903177.22 | 0.00 | 0.103567E+10 | 0.00 | 0.54 |
July | 46963594.11 | 0.196521E+11 | 0.00 | 449635.92 | 0.431070E+09 | 0.00 | 33277406.61 | 0.00 | 0.54 |
August | 0.00 | 0.215587E+11 | 0.00 | 196905.26 | 835470.93 | 0.00 | 13247984.29 | 0.00 | 0.54 |
September | 0.136637E+10 | 0.110169E+11 | 0.00 | 14145273.94 | 0.322596E+09 | 0.00 | 0.158678E+10 | 0.00 | 0.54 |
October | 0.810204E+10 | 0.250695E+10 | 0.00 | 39953211.26 | 0.492248E+09 | 0.00 | 0.611526E+10 | 0.00 | 0.54 |
November | 0.127973E+11 | 0.199606E+09 | 0.00 | 27303692.74 | 0.103690E+09 | 0.00 | 0.544419E+10 | 0.00 | 0.54 |
December | 0.177497E+11 | 34975623.06 | 0.00 | 10281508.18 | 0.00 | 0.180276E+09 | 0.269439E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.943383E+11 | 0.736464E+11 | 0.00 | 0.183512E+09 | 0.205518E+10 | 0.597320E+10 | 0.310350E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 196905.26 | 0.00 | 0.00 | 13247984.29 | 0.00 | 0.53 |
Maximum of Months | 0.177497E+11 | 0.215587E+11 | 0.00 | 39953211.26 | 0.492248E+09 | 0.437473E+10 | 0.611526E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.563833E+10 | 0.00 | 19585.44 | 7321408.22 | 197564.72 | 0.111636E+11 | 0.353681E+10 | 21645.62 | 0.53 |
February | 0.508090E+10 | 121363.74 | 17777.76 | 18668926.39 | 5724517.84 | 0.615939E+10 | 0.656331E+10 | 5931.81 | 0.53 |
March | 0.641933E+10 | 94919125.82 | 446235.75 | 44372393.88 | 0.174297E+09 | 0.756662E+09 | 0.105771E+11 | 39770.14 | 0.54 |
April | 0.390347E+10 | 0.384406E+09 | 2820333.18 | 73261966.97 | 0.665495E+09 | 0.172085E+09 | 0.833844E+10 | 88810.02 | 0.54 |
May | 0.199204E+10 | 0.240638E+10 | 5646701.96 | 48248943.06 | 0.199712E+10 | 4420955.76 | 0.291483E+10 | 132993.43 | 0.54 |
June | 0.539886E+09 | 0.100295E+11 | 2015518.60 | 22062819.42 | 0.361778E+10 | 1651788.71 | 0.135232E+10 | 44440.26 | 0.54 |
July | 74579679.71 | 0.147771E+11 | 3750726.46 | 1493789.47 | 0.530779E+10 | 0.00 | 4639232.17 | 21618.47 | 0.54 |
August | 13448566.03 | 0.160462E+11 | 14323203.63 | 0.00 | 0.550474E+10 | 0.00 | 0.00 | 117772.51 | 0.54 |
September | 0.114778E+10 | 0.654653E+10 | 11558496.46 | 27290491.73 | 0.478434E+10 | 6237241.11 | 0.178680E+10 | 169561.43 | 0.54 |
October | 0.461507E+10 | 0.147493E+10 | 6628838.03 | 46116847.23 | 0.151829E+10 | 0.265121E+09 | 0.933484E+10 | 170546.59 | 0.54 |
November | 0.550425E+10 | 66841036.00 | 844641.48 | 31470039.97 | 0.235653E+09 | 0.213135E+10 | 0.106067E+11 | 40325.57 | 0.54 |
December | 0.591811E+10 | 2554786.72 | 106426.63 | 14285490.16 | 32251225.81 | 0.784670E+10 | 0.686124E+10 | 72747.92 | 0.53 |
Annual Sum or Average | 0.408472E+11 | 0.518295E+11 | 48178485.37 | 0.334593E+09 | 0.238437E+11 | 0.285072E+11 | 0.618770E+11 | 926163.76 | 0.54 |
Minimum of Months | 13448566.03 | 0.00 | 17777.76 | 0.00 | 197564.72 | 0.00 | 0.00 | 5931.81 | 0.53 |
Maximum of Months | 0.641933E+10 | 0.160462E+11 | 14323203.63 | 73261966.97 | 0.550474E+10 | 0.111636E+11 | 0.106067E+11 | 170546.59 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.354572E+09 | 0.00 | 0.00 | 311475.69 | 14566.65 | 0.107345E+10 | 71799900.89 | 3040.01 | 0.47 |
February | 0.334471E+09 | 205134.95 | 993.23 | 1599093.29 | 225648.32 | 0.748190E+09 | 0.229793E+09 | 994.50 | 0.47 |
March | 0.426640E+09 | 12340616.20 | 68341.34 | 3890424.09 | 7460431.23 | 0.358116E+09 | 0.523576E+09 | 16028.38 | 0.47 |
April | 0.258230E+09 | 47497092.87 | 268869.15 | 6871464.28 | 29845915.59 | 93921623.62 | 0.561674E+09 | 12850.04 | 0.47 |
May | 0.132828E+09 | 0.262736E+09 | 174929.42 | 4363926.50 | 62180895.69 | 470632.01 | 0.228010E+09 | 9170.71 | 0.48 |
June | 32810066.64 | 0.844054E+09 | 127800.84 | 2421788.09 | 0.162197E+09 | 53780.71 | 0.105977E+09 | 2147.81 | 0.48 |
July | 5498836.53 | 0.123575E+10 | 191233.95 | 85271.50 | 0.245208E+09 | 18612.36 | 348310.13 | 3781.04 | 0.47 |
August | 991576.61 | 0.137999E+10 | 95214.89 | 0.00 | 0.209958E+09 | 0.00 | 0.00 | 393.90 | 0.48 |
September | 81190962.66 | 0.632213E+09 | 556221.11 | 2673610.34 | 0.203517E+09 | 474843.45 | 0.134502E+09 | 14749.88 | 0.48 |
October | 0.286453E+09 | 0.157009E+09 | 247723.78 | 4304116.06 | 63927685.46 | 0.265459E+09 | 0.495273E+09 | 10779.50 | 0.47 |
November | 0.377326E+09 | 6638482.05 | 110236.72 | 2314998.28 | 15610931.77 | 0.537712E+09 | 0.429995E+09 | 8762.10 | 0.47 |
December | 0.433013E+09 | 197354.36 | 3204.68 | 780769.33 | 2377916.07 | 0.935698E+09 | 0.152341E+09 | 1018.74 | 0.47 |
Annual Sum or Average | 0.272403E+10 | 0.457863E+10 | 1844769.10 | 29616937.45 | 0.100252E+10 | 0.401357E+10 | 0.293329E+10 | 83716.61 | 0.47 |
Minimum of Months | 991576.61 | 0.00 | 0.00 | 0.00 | 14566.65 | 0.00 | 0.00 | 393.90 | 0.47 |
Maximum of Months | 0.433013E+09 | 0.137999E+10 | 556221.11 | 6871464.28 | 0.245208E+09 | 0.107345E+10 | 0.561674E+09 | 16028.38 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268011E+09 | 0.00 | 0.00 | 57343.61 | 14564.94 | 0.120925E+10 | 22640494.14 | 3039.65 | 0.47 |
February | 0.286214E+09 | 10695.15 | 0.00 | 728915.85 | 422025.14 | 0.883184E+09 | 0.143772E+09 | 0.00 | 0.47 |
March | 0.473138E+09 | 8955938.65 | 60681.44 | 2241225.28 | 10849663.20 | 0.476482E+09 | 0.360207E+09 | 16803.98 | 0.47 |
April | 0.278419E+09 | 41421373.82 | 316282.96 | 5817080.71 | 35861503.23 | 0.127326E+09 | 0.509028E+09 | 16472.77 | 0.47 |
May | 0.135473E+09 | 0.260805E+09 | 229093.90 | 4148837.82 | 64019166.78 | 1601811.23 | 0.224405E+09 | 9523.34 | 0.48 |
June | 32589244.01 | 0.844191E+09 | 71682.61 | 2429270.87 | 0.161998E+09 | 53774.41 | 0.106174E+09 | 2238.76 | 0.48 |
July | 5498192.26 | 0.123505E+10 | 191077.52 | 84614.23 | 0.245737E+09 | 18610.18 | 348916.61 | 3914.63 | 0.47 |
August | 991460.44 | 0.137643E+10 | 95030.47 | 0.00 | 0.213326E+09 | 0.00 | 0.00 | 567.12 | 0.48 |
September | 81569266.30 | 0.622338E+09 | 829074.02 | 2306978.09 | 0.213013E+09 | 512906.91 | 0.134427E+09 | 23248.13 | 0.48 |
October | 0.339395E+09 | 0.143041E+09 | 574558.24 | 2411831.52 | 77527621.69 | 0.340193E+09 | 0.369366E+09 | 25656.28 | 0.47 |
November | 0.403634E+09 | 4915104.18 | 71527.10 | 770783.52 | 17372869.03 | 0.715948E+09 | 0.226837E+09 | 6291.56 | 0.47 |
December | 0.390614E+09 | 191769.31 | 6832.41 | 150362.54 | 2377637.46 | 0.108715E+10 | 43743337.14 | 2952.43 | 0.47 |
Annual Sum or Average | 0.269555E+10 | 0.453735E+10 | 2445840.66 | 21147244.05 | 0.104252E+10 | 0.484172E+10 | 0.214095E+10 | 110708.66 | 0.47 |
Minimum of Months | 991460.44 | 0.00 | 0.00 | 0.00 | 14564.94 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.473138E+09 | 0.137643E+10 | 829074.02 | 5817080.71 | 0.245737E+09 | 0.120925E+10 | 0.509028E+09 | 25656.28 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277719E+11 | 0.00 | 0.00 | 0.00 | 3670675.99 | 0.396765E+10 | 0.00 | 0.00 | 0.59 |
February | 0.232502E+11 | 0.00 | 0.00 | 0.00 | 5262184.73 | 0.206761E+10 | 0.00 | 0.00 | 0.59 |
March | 0.238778E+11 | 0.00 | 0.00 | 0.00 | 0.221428E+09 | 953440.52 | 0.00 | 0.00 | 0.60 |
April | 0.156062E+11 | 0.00 | 0.00 | 0.00 | 0.111465E+10 | 1912662.38 | 0.00 | 0.00 | 0.60 |
May | 0.647844E+10 | 0.00 | 0.00 | 0.00 | 0.461107E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.275018E+10 | 0.00 | 0.00 | 0.00 | 0.131428E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 49590880.75 | 0.00 | 0.00 | 0.00 | 0.206344E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 8287539.52 | 0.00 | 0.00 | 0.00 | 0.217848E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.396895E+10 | 0.00 | 0.00 | 0.00 | 0.110892E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.190350E+11 | 0.00 | 0.00 | 0.00 | 0.325945E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
November | 0.246254E+11 | 0.00 | 0.00 | 0.00 | 0.451329E+09 | 9195338.21 | 0.00 | 0.00 | 0.59 |
December | 0.304687E+11 | 0.00 | 0.00 | 0.00 | 71480522.75 | 0.260341E+09 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.177891E+12 | 0.00 | 0.00 | 0.00 | 0.763895E+11 | 0.630766E+10 | 0.00 | 0.00 | 0.59 |
Minimum of Months | 8287539.52 | 0.00 | 0.00 | 0.00 | 3670675.99 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.304687E+11 | 0.00 | 0.00 | 0.00 | 0.217848E+11 | 0.396765E+10 | 0.00 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76663501.95 | 0.00 | 0.00 | 87002.13 | 3641.66 | 0.285792E+09 | 12492161.33 | 760.00 | 0.47 |
February | 73936793.26 | 51727.19 | 0.00 | 290332.68 | 56465.56 | 0.213627E+09 | 40658774.44 | 0.00 | 0.47 |
March | 0.110194E+09 | 3126635.53 | 5292.81 | 912433.01 | 1836626.58 | 0.118385E+09 | 98564000.53 | 2799.37 | 0.47 |
April | 68940574.43 | 12567280.00 | 58885.67 | 1601666.66 | 6777652.87 | 34508731.28 | 0.125124E+09 | 2363.37 | 0.47 |
May | 35320749.87 | 64560028.94 | 112591.28 | 1029022.75 | 16595922.64 | 169147.27 | 54899081.01 | 6741.58 | 0.48 |
June | 9453788.70 | 0.208640E+09 | 94078.08 | 537239.75 | 42856677.44 | 23267.05 | 25301427.86 | 4275.92 | 0.48 |
July | 1374709.13 | 0.305439E+09 | 104250.44 | 20685.08 | 64743027.05 | 6523.13 | 85840.28 | 2700.38 | 0.47 |
August | 247894.15 | 0.342225E+09 | 90401.38 | 0.00 | 55192240.38 | 0.00 | 0.00 | 2315.27 | 0.48 |
September | 20652966.27 | 0.157716E+09 | 208693.39 | 537076.67 | 51141990.20 | 2746039.32 | 30774308.38 | 8611.66 | 0.48 |
October | 79136056.21 | 38822445.85 | 78314.67 | 1014106.62 | 16392671.02 | 81541474.71 | 0.101181E+09 | 5260.94 | 0.47 |
November | 92435009.53 | 1916413.31 | 18692.58 | 511135.58 | 3655665.83 | 0.169381E+09 | 74509366.61 | 1331.44 | 0.47 |
December | 96801431.17 | 172584.98 | 441.27 | 154588.68 | 471232.63 | 0.261490E+09 | 22012539.07 | 614.59 | 0.47 |
Annual Sum or Average | 0.665158E+09 | 0.113524E+10 | 771641.57 | 6695289.62 | 0.259724E+09 | 0.116767E+10 | 0.585602E+09 | 37774.52 | 0.47 |
Minimum of Months | 247894.15 | 0.00 | 0.00 | 0.00 | 3641.66 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.110194E+09 | 0.342225E+09 | 208693.39 | 1601666.66 | 64743027.05 | 0.285792E+09 | 0.125124E+09 | 8611.66 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 45478667.37 | 0.00 | 0.00 | 10924.84 | 3641.24 | 0.327895E+09 | 1605610.88 | 759.91 | 0.47 |
February | 60448566.72 | 10893.49 | 348.47 | 116354.48 | 96789.71 | 0.249662E+09 | 18247661.26 | 148.41 | 0.47 |
March | 0.115056E+09 | 2628526.30 | 5819.21 | 538093.91 | 2333262.97 | 0.149544E+09 | 62879101.42 | 3163.34 | 0.47 |
April | 70485349.83 | 11711991.96 | 59573.33 | 1355333.99 | 7629916.52 | 41785959.15 | 0.116521E+09 | 2426.38 | 0.47 |
May | 35694355.44 | 63935886.85 | 112360.56 | 972028.27 | 17210252.21 | 350134.16 | 54390772.08 | 7262.24 | 0.48 |
June | 9495342.05 | 0.208640E+09 | 70416.06 | 538106.96 | 42851656.15 | 23445.32 | 25254691.27 | 3657.20 | 0.48 |
July | 1374548.07 | 0.305087E+09 | 101245.19 | 20464.90 | 65055811.14 | 6522.37 | 86047.99 | 1937.89 | 0.47 |
August | 247865.11 | 0.341474E+09 | 90014.24 | 0.00 | 55896965.93 | 0.00 | 0.00 | 2691.55 | 0.48 |
September | 20930321.73 | 0.155327E+09 | 237575.79 | 441716.03 | 53475907.82 | 2817276.04 | 30514666.72 | 10506.03 | 0.48 |
October | 83451301.72 | 34736475.49 | 143280.22 | 557873.72 | 20405264.68 | 0.109124E+09 | 69708241.58 | 7193.04 | 0.47 |
November | 94145803.27 | 1380105.51 | 21277.79 | 175891.44 | 4188096.80 | 0.210982E+09 | 31493713.61 | 1967.87 | 0.47 |
December | 79536898.59 | 49028.63 | 226.46 | 28275.75 | 594409.37 | 0.293989E+09 | 6859677.28 | 1133.45 | 0.47 |
Annual Sum or Average | 0.616345E+09 | 0.112498E+10 | 842137.32 | 4755064.28 | 0.269742E+09 | 0.138618E+10 | 0.417561E+09 | 42847.32 | 0.47 |
Minimum of Months | 247865.11 | 0.00 | 0.00 | 0.00 | 3641.24 | 0.00 | 0.00 | 148.41 | 0.47 |
Maximum of Months | 0.115056E+09 | 0.341474E+09 | 237575.79 | 1355333.99 | 65055811.14 | 0.327895E+09 | 0.116521E+09 | 10506.03 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.487477E+09 | 0.00 | 1712.75 | 4561142.59 | 23395.82 | 0.139095E+10 | 0.526417E+09 | 3169.88 | 0.53 |
February | 0.497691E+09 | 332664.35 | 0.00 | 5222692.85 | 362418.81 | 0.942915E+09 | 0.664702E+09 | 0.00 | 0.53 |
March | 0.600876E+09 | 22285635.00 | 15641.81 | 9499165.22 | 9636686.89 | 0.333726E+09 | 0.116349E+10 | 448.93 | 0.54 |
April | 0.430129E+09 | 83159573.32 | 270444.62 | 10435618.88 | 41232959.45 | 0.134609E+09 | 0.903581E+09 | 11831.48 | 0.54 |
May | 0.225644E+09 | 0.407136E+09 | 330413.76 | 5869610.66 | 0.114651E+09 | 883786.03 | 0.354917E+09 | 34827.73 | 0.54 |
June | 61086213.57 | 0.132674E+10 | 420413.90 | 2579448.28 | 0.289199E+09 | 213384.92 | 0.163006E+09 | 9513.06 | 0.54 |
July | 8831804.18 | 0.194479E+10 | 420772.12 | 144608.40 | 0.433701E+09 | 1479.83 | 580190.65 | 10292.70 | 0.54 |
August | 1592593.35 | 0.218369E+10 | 418820.28 | 0.00 | 0.369680E+09 | 0.00 | 0.00 | 8703.21 | 0.54 |
September | 0.131818E+09 | 0.101100E+10 | 570628.43 | 4166395.17 | 0.331622E+09 | 793641.12 | 0.214708E+09 | 10127.80 | 0.54 |
October | 0.423417E+09 | 0.256856E+09 | 287693.90 | 11375889.03 | 98115014.24 | 0.183294E+09 | 0.107073E+10 | 7462.07 | 0.54 |
November | 0.474373E+09 | 16124824.84 | 56000.11 | 10322905.84 | 19743134.37 | 0.434740E+09 | 0.124457E+10 | 2447.85 | 0.54 |
December | 0.502405E+09 | 1968422.74 | 0.00 | 6687961.93 | 2174559.95 | 0.106741E+10 | 0.867751E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.384534E+10 | 0.725408E+10 | 2792541.67 | 70865438.85 | 0.171014E+10 | 0.448953E+10 | 0.717445E+10 | 98824.71 | 0.54 |
Minimum of Months | 1592593.35 | 0.00 | 0.00 | 0.00 | 23395.82 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.600876E+09 | 0.218369E+10 | 570628.43 | 11375889.03 | 0.433701E+09 | 0.139095E+10 | 0.124457E+10 | 34827.73 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242111E+11 | 0.00 | 0.00 | 20996564.81 | 5473548.42 | 0.00 | 0.233158E+11 | 0.00 | 4.14 |
February | 0.155882E+11 | 634351.91 | 0.00 | 25256424.67 | 7212383.41 | 0.00 | 0.223958E+11 | 0.00 | 4.20 |
March | 0.100579E+11 | 0.242261E+09 | 0.00 | 38881706.01 | 89518405.15 | 0.00 | 0.259141E+11 | 0.00 | 4.26 |
April | 0.336030E+10 | 0.151569E+10 | 0.00 | 44784714.48 | 0.160116E+09 | 0.00 | 0.204626E+11 | 0.00 | 4.31 |
May | 0.551889E+09 | 0.663963E+10 | 0.00 | 35906708.97 | 0.472782E+09 | 0.00 | 0.942039E+10 | 0.00 | 4.32 |
June | 91487440.93 | 0.205622E+11 | 0.00 | 15543787.30 | 0.571754E+09 | 0.00 | 0.419640E+10 | 0.00 | 4.39 |
July | 0.00 | 0.325691E+11 | 0.00 | 1171607.81 | 0.756680E+09 | 0.00 | 75963753.93 | 0.00 | 4.38 |
August | 0.00 | 0.346316E+11 | 0.00 | 423106.03 | 0.862099E+09 | 0.00 | 12623603.72 | 0.00 | 4.40 |
September | 0.248375E+09 | 0.165706E+11 | 0.00 | 18762262.41 | 0.732918E+09 | 0.00 | 0.587964E+10 | 0.00 | 4.32 |
October | 0.609018E+10 | 0.457335E+10 | 0.00 | 35237112.90 | 0.458698E+09 | 0.00 | 0.226446E+11 | 0.00 | 4.27 |
November | 0.118970E+11 | 0.415864E+09 | 0.00 | 31146136.14 | 0.261101E+09 | 0.00 | 0.251378E+11 | 0.00 | 4.23 |
December | 0.195889E+11 | 5373276.34 | 0.00 | 26692883.18 | 0.101215E+09 | 0.00 | 0.264795E+11 | 0.00 | 4.16 |
Annual Sum or Average | 0.916854E+11 | 0.117726E+12 | 0.00 | 0.294803E+09 | 0.447957E+10 | 0.00 | 0.185935E+12 | 0.00 | 4.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 423106.03 | 5473548.42 | 0.00 | 12623603.72 | 0.00 | 4.14 |
Maximum of Months | 0.242111E+11 | 0.346316E+11 | 0.00 | 44784714.48 | 0.862099E+09 | 0.00 | 0.264795E+11 | 0.00 | 4.40 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223609E+11 | 2335617.29 | 0.00 | 29229130.12 | 3399872.45 | 0.00 | 0.276135E+11 | 0.00 | 4.35 |
February | 0.137746E+11 | 7855463.32 | 0.00 | 33951455.77 | 366784.20 | 0.00 | 0.262593E+11 | 0.00 | 4.42 |
March | 0.778863E+10 | 0.313577E+09 | 0.00 | 50146039.73 | 35987710.09 | 0.00 | 0.303033E+11 | 0.00 | 4.52 |
April | 0.214187E+10 | 0.168064E+10 | 0.00 | 55281127.57 | 95388058.74 | 0.00 | 0.231582E+11 | 0.00 | 4.58 |
May | 0.189386E+09 | 0.727593E+10 | 0.00 | 41924378.64 | 0.283909E+09 | 0.00 | 0.104386E+11 | 0.00 | 4.61 |
June | 35566859.95 | 0.219559E+11 | 0.00 | 17866403.58 | 0.487875E+09 | 0.00 | 0.452204E+10 | 0.00 | 4.67 |
July | 0.00 | 0.347870E+11 | 0.00 | 1264446.22 | 0.538827E+09 | 0.00 | 81348650.80 | 0.00 | 4.65 |
August | 0.00 | 0.369585E+11 | 0.00 | 450516.60 | 0.652420E+09 | 0.00 | 13381372.51 | 0.00 | 4.66 |
September | 0.133864E+09 | 0.179182E+11 | 0.00 | 22321302.79 | 0.471587E+09 | 0.00 | 0.638644E+10 | 0.00 | 4.60 |
October | 0.430852E+10 | 0.503778E+10 | 0.00 | 45074293.35 | 0.330857E+09 | 0.00 | 0.261180E+11 | 0.00 | 4.52 |
November | 0.965680E+10 | 0.620004E+09 | 0.00 | 41696826.24 | 95169449.11 | 0.00 | 0.294444E+11 | 0.00 | 4.47 |
December | 0.176188E+11 | 97070660.84 | 0.00 | 36919854.63 | 14618795.35 | 0.00 | 0.308697E+11 | 0.00 | 4.38 |
Annual Sum or Average | 0.780089E+11 | 0.126655E+12 | 0.00 | 0.376126E+09 | 0.301040E+10 | 0.00 | 0.215208E+12 | 0.00 | 4.54 |
Minimum of Months | 0.00 | 2335617.29 | 0.00 | 450516.60 | 366784.20 | 0.00 | 13381372.51 | 0.00 | 4.35 |
Maximum of Months | 0.223609E+11 | 0.369585E+11 | 0.00 | 55281127.57 | 0.652420E+09 | 0.00 | 0.308697E+11 | 0.00 | 4.67 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.304159E+09 | 7218026.29 | 0.00 | 0.145631E+09 | 0.00 | 0.00 | 0.578831E+11 | 0.00 | 16.47 |
February | 0.295832E+09 | 11484892.73 | 0.00 | 0.119358E+09 | 0.00 | 0.00 | 0.463673E+11 | 0.00 | 17.08 |
March | 0.166443E+09 | 0.502283E+09 | 0.00 | 0.115524E+09 | 0.00 | 0.00 | 0.445365E+11 | 0.00 | 17.86 |
April | 95702838.15 | 0.250810E+10 | 0.00 | 92937424.43 | 0.00 | 0.00 | 0.283040E+11 | 0.00 | 18.36 |
May | 2768859.29 | 0.104993E+11 | 0.00 | 50890145.94 | 0.00 | 0.00 | 0.112976E+11 | 0.00 | 18.41 |
June | 0.00 | 0.286167E+11 | 0.00 | 22274787.72 | 0.00 | 0.00 | 0.478224E+10 | 0.00 | 18.48 |
July | 0.00 | 0.446898E+11 | 0.00 | 852512.94 | 0.00 | 0.00 | 77096619.31 | 0.00 | 18.30 |
August | 0.00 | 0.472155E+11 | 0.00 | 373203.33 | 0.00 | 0.00 | 12688199.04 | 0.00 | 18.33 |
September | 3061339.55 | 0.234631E+11 | 0.00 | 31584813.64 | 0.00 | 0.00 | 0.711114E+10 | 0.00 | 18.33 |
October | 79981883.64 | 0.683362E+10 | 0.00 | 92244892.56 | 0.00 | 0.00 | 0.351450E+11 | 0.00 | 17.94 |
November | 0.306201E+09 | 0.990424E+09 | 0.00 | 0.114918E+09 | 0.00 | 0.00 | 0.456155E+11 | 0.00 | 17.50 |
December | 0.284325E+09 | 0.151953E+09 | 0.00 | 0.144272E+09 | 0.00 | 0.00 | 0.572527E+11 | 0.00 | 16.93 |
Annual Sum or Average | 0.153847E+10 | 0.165489E+12 | 0.00 | 0.930861E+09 | 0.00 | 0.00 | 0.338385E+12 | 0.00 | 17.83 |
Minimum of Months | 0.00 | 7218026.29 | 0.00 | 373203.33 | 0.00 | 0.00 | 12688199.04 | 0.00 | 16.47 |
Maximum of Months | 0.306201E+09 | 0.472155E+11 | 0.00 | 0.145631E+09 | 0.00 | 0.00 | 0.578831E+11 | 0.00 | 18.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105098E+11 | 0.00 | 0.00 | 0.00 | 1853405.70 | 0.551622E+10 | 0.00 | 0.00 | 1.12 |
February | 0.983569E+10 | 0.00 | 0.00 | 0.00 | 2656993.76 | 0.294782E+10 | 0.00 | 0.00 | 1.13 |
March | 0.119789E+11 | 0.00 | 0.00 | 0.00 | 0.111804E+09 | 77970717.58 | 0.00 | 0.00 | 1.14 |
April | 0.787358E+10 | 0.00 | 0.00 | 0.00 | 0.562813E+09 | 7280029.10 | 0.00 | 0.00 | 1.14 |
May | 0.327111E+10 | 0.00 | 0.00 | 0.00 | 0.232823E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
June | 0.138863E+10 | 0.443696E+09 | 0.00 | 0.00 | 0.619240E+10 | 0.00 | 0.00 | 0.00 | 1.10 |
July | 25039535.36 | 0.259937E+10 | 0.00 | 0.00 | 0.783249E+10 | 0.00 | 0.00 | 0.00 | 1.09 |
August | 4184562.48 | 0.291151E+10 | 0.00 | 0.00 | 0.809093E+10 | 0.00 | 0.00 | 0.00 | 1.09 |
September | 0.200401E+10 | 26498482.72 | 0.00 | 0.00 | 0.557268E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
October | 0.961120E+10 | 0.00 | 0.00 | 0.00 | 0.164577E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
November | 0.119491E+11 | 0.00 | 0.00 | 0.00 | 0.227886E+09 | 0.489409E+09 | 0.00 | 0.00 | 1.13 |
December | 0.138100E+11 | 0.00 | 0.00 | 0.00 | 36092101.00 | 0.170576E+10 | 0.00 | 0.00 | 1.12 |
Annual Sum or Average | 0.822613E+11 | 0.598107E+10 | 0.00 | 0.00 | 0.326056E+11 | 0.107445E+11 | 0.00 | 0.00 | 1.12 |
Minimum of Months | 4184562.48 | 0.00 | 0.00 | 0.00 | 1853405.70 | 0.00 | 0.00 | 0.00 | 1.09 |
Maximum of Months | 0.138100E+11 | 0.291151E+10 | 0.00 | 0.00 | 0.809093E+10 | 0.551622E+10 | 0.00 | 0.00 | 1.14 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:42:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.180581E+12 | 0.162770E+11 | 0.208037E+12 | 0.831270E+12 | 0.107386E+12 |
February | 0.187541E+12 | 0.118516E+11 | 0.150092E+12 | 0.604075E+12 | 0.153567E+12 |
March | 0.276734E+12 | 0.844679E+10 | 0.107641E+12 | 0.424241E+12 | 0.292705E+12 |
April | 0.312308E+12 | 0.489571E+10 | 0.604311E+11 | 0.245902E+12 | 0.505209E+12 |
May | 0.343574E+12 | -46501153.3 | -0.184875E+10 | -0.186653E+11 | 0.879757E+12 |
June | 0.350436E+12 | -0.610432E+10 | -0.793925E+11 | -0.339969E+12 | 0.122929E+13 |
July | 0.326016E+12 | -0.107568E+11 | -0.137670E+12 | -0.595380E+12 | 0.153239E+13 |
August | 0.300889E+12 | -0.125450E+11 | -0.156978E+12 | -0.700273E+12 | 0.158864E+13 |
September | 0.225384E+12 | -0.408288E+10 | -0.508955E+11 | -0.230831E+12 | 0.110216E+13 |
October | 0.214990E+12 | 0.483874E+10 | 0.624053E+11 | 0.250077E+12 | 0.511201E+12 |
November | 0.149256E+12 | 0.899257E+10 | 0.114718E+12 | 0.477590E+12 | 0.252300E+12 |
December | 0.143062E+12 | 0.130292E+11 | 0.167579E+12 | 0.683897E+12 | 0.125362E+12 |
Annual Sum or Average | 0.301077E+13 | 0.347959E+11 | 0.444118E+12 | 0.163193E+13 | 0.827997E+13 |
Minimum of Months | 0.143062E+12 | -0.125450E+11 | -0.156978E+12 | -0.700273E+12 | 0.107386E+12 |
Maximum of Months | 0.350436E+12 | 0.162770E+11 | 0.208037E+12 | 0.831270E+12 | 0.158864E+13 |