Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860

Simulation Timestamp: 2023-10-16 08:41:37


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 11391.45 1004.07 1004.07
Net Site Energy 11391.45 1004.07 1004.07
Total Source Energy 24175.81 2130.91 2130.91
Net Source Energy 24175.81 2130.91 2130.91


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 745.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1191.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 867.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 262.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 650.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 564.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 107.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 224.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.75 3178.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 5678.10 5713.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 745.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1191.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 867.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 262.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 31.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 564.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 107.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 224.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 3178.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 745.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1191.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 867.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 262.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 650.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 564.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 107.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 224.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.75 3178.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 172.26 345.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 228.68 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 500.48 503.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 172.26 345.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 228.68 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 500.48 503.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 5678.099 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 5678.099 100.00
     
Total On-Site and Utility Electric Sources 5678.099 100.00
Total Electricity End Uses 5678.099 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 546.02 15.70
Air to Air Heat Recovery for Heating 2931.10 84.30
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3477.12 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 11.67
Time Setpoint Not Met During Occupied Cooling 410.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 8107.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
RunPeriod RUNPERIOD 1
Weather File New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Latitude [deg] 40.65
Longitude [deg] -73.8
Elevation [m] 5.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 10.3255 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.5625 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.5625 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.5208 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 7.7005 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 6.4583 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 11.5174 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 9.6875 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 9.7951 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 9.7951 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 7.1042 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 9.7951 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 11.5174 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 11.5174 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 13.0243 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 7.1042 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 9.4981 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 9.4981 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 10.3255 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.5625 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.5625 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.5208 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 7.7005 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 6.4583 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 11.5174 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 9.6875 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 9.7951 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 9.7951 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 9.7951 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 9.7951 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 9.7951 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 9.7951 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 7.1042 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 9.7951 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 9.7951 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 9.7951 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 11.5174 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 11.5174 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 13.0243 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 7.1042 18.58 0.0000  
Total 11345.29             9.4981 3.54 41.0709  
Conditioned Total 11345.29             9.4981 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 5.0165 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 04-AUG-19:10 14-JAN-17:30 - - - - - - - - - - 12-JAN-21:10
Heating 0.00 201177.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 198798.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 71560.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86439.81 89612.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32080.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 32042.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 5611.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3539.47 256292.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1874.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 458577.10 547081.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 201177.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 198798.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 71560.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56456.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 14636.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1777.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 32042.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 5611.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3539.47 256292.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 536.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1096.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 808.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3772.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2746.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 829.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5251.45 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2058.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1787.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 341.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 709.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.39 3445.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 196.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 17982.54 6193.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 71.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 332.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 242.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 157.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 30.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 62.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 303.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1585.02 545.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 71.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 332.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 242.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 157.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 30.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 62.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 303.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1585.02 545.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.69 0.561069 0.518000 1.39 1.00 0.500000 0.000679 0.000064 1.39 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.389515 0.131210 0.518000 0.201769 0.518000 0.500000 0.002904 0.000036 0.201769 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.240202 0.246392 0.518000 0.124425 0.657044 0.500000 0.001546 0.000014 0.124425 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.188661 0.663376 0.518000 0.097727 1.00 0.500000 0.000574 0.000020 0.097727 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.124169 0.581517 0.518000 0.064320 1.00 0.500000 0.000655 0.000014 0.064320 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.27 0.072236 0.518000 1.69 0.518000 0.500000 0.020930 0.000099 1.69 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.58 0.091001 0.518000 0.819184 0.518000 0.500000 0.004187 0.000104 0.819184 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.84 0.206044 0.518000 2.51 0.549452 0.500000 0.001849 0.000270 2.51 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.59 0.744479 0.518000 0.825835 1.00 0.500000 0.000512 0.000131 0.825835 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.20 0.114792 0.518000 1.14 0.518000 0.500000 0.003319 0.000109 1.14 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.31 0.109566 0.518000 1.19 0.518000 0.500000 0.003477 0.000113 1.19 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.28 0.062127 0.518000 1.18 0.518000 0.500000 0.011030 0.000075 1.18 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.794578 0.395228 0.518000 0.411591 1.00 0.500000 0.000964 0.000078 0.411591 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 7346.88 0.000064 153.21
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4073.90 0.000036 99.83
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1645.40 0.000014 37.24
MECH_FLR_1 VAV BOX REHEAT COIL 2341.15 0.000020 60.10
STORAGE_FLR_1 VAV BOX REHEAT COIL 1621.21 0.000014 42.29
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11322.91 0.000099 239.45
CAFE_FLR_1 VAV BOX REHEAT COIL 11915.04 0.000104 273.62
LOBBY_FLR_1 VAV BOX REHEAT COIL 30896.11 0.000270 692.57
ROOM_1_FLR_3 FAN COIL HEATING COIL 6759.96 0.000059 193.18
ROOM_2_FLR_3 FAN COIL HEATING COIL 6781.05 0.000059 193.78
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 38437.21 0.000336 1098.42
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 38840.75 0.000340 1109.95
ROOM_5_FLR_3 FAN COIL HEATING COIL 6717.22 0.000059 191.96
ROOM_6_FLR_3 FAN COIL HEATING COIL 6738.34 0.000059 192.56
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 15002.30 0.000131 358.94
ROOM_1_FLR_6 FAN COIL HEATING COIL 2015.63 0.000018 57.60
ROOM_2_FLR_6 FAN COIL HEATING COIL 2022.59 0.000018 57.80
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 9574.27 0.000084 273.59
BANQUET_FLR_6 VAV BOX REHEAT COIL 12511.64 0.000109 276.44
DINING_FLR_6 VAV BOX REHEAT COIL 12938.46 0.000113 285.44
KITCHEN_FLR_6 VAV BOX REHEAT COIL 8587.68 0.000075 182.67
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 8877.75 0.000078 221.21
VAV WITH REHEAT HEATING COIL 222401.12 0.001946 3670.81
FLR_3_DOAS HEATING COIL 20393.42 0.000178 336.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.20 0.000059 0.000490
ROOM_2_FLR_3 FAN COIL 1.17 0.000059 0.000477
ROOM_3_MULT19_FLR_3 FAN COIL 7.46 0.000336 0.002974
ROOM_4_MULT19_FLR_3 FAN COIL 6.67 0.000340 0.002819
ROOM_5_FLR_3 FAN COIL 1.11 0.000059 0.000452
ROOM_6_FLR_3 FAN COIL 1.08 0.000059 0.000440
ROOM_1_FLR_6 FAN COIL 0.316016 0.000018 0.000128
ROOM_2_FLR_6 FAN COIL 0.306636 0.000018 0.000125
ROOM_3_MULT9_FLR_6 FAN COIL 1.47 0.000084 0.000606
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.20
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.17
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 7.46
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.67
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.11
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.08
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.316016
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.306636
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.47
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008658 12.80 0.008500 0.000490 1.20  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008663 12.80 0.008500 0.000477 1.17  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008584 12.80 0.008500 0.002974 7.46  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008802 12.80 0.008500 0.002819 6.67  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008673 12.80 0.008500 0.000452 1.11  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008678 12.80 0.008500 0.000440 1.08  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008651 12.80 0.008500 0.000128 0.316016  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008656 12.80 0.008500 0.000125 0.306636  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008704 12.80 0.008500 0.000606 1.47  
VAV WITH REHEAT COOLING COIL 28.22 6.70 0.011985 10.99 0.008500 0.025475 22.37 713237.72
FLR_3_DOAS COOLING COIL 32.10 6.70 0.014120 11.94 0.008500 0.003084 2.05 86334.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.65 11.65 22.49 11.65 22.37 22.37 0.300000 0.520812 22.37
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 22.37 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.025475 0.000019
VAV WITH REHEAT_HEATC_CONTROLLER 0.001946  
FLR_3_DOAS_COOLC_CONTROLLER 0.003084 0.000154
FLR_3_DOAS_HEATC_CONTROLLER 0.000178  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.037071 6052.51  
HEATSYS1 PUMP 0.004285 1290.35 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.004285 0.514158
COOLSYS1 0.037071 4.45
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 489761.98 489761.98 0.004285
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.037071 4190.36
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.037071 1037880.30 1038496.74 118.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 14.00 7.30 3.30 1.20 -0.20 5.60 10.90 16.10 21.70 25.00 24.80 19.90


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 40.65 -73.80 -5.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 12.47 25.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 10.325 5.380 0.000 0.000 0.000 0.000 15.705 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.563 10.760 0.000 0.000 0.000 0.000 24.323 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.563 10.760 0.000 0.000 0.000 0.000 24.323 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.521 5.380 0.000 0.000 0.000 0.000 9.901 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 7.700 2.690 0.000 0.000 0.000 0.000 10.390 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 6.458 61.680 535.850 0.000 0.000 0.000 603.988 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 11.517 5.380 0.000 0.000 0.000 0.000 16.897 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 9.795 10.520 0.000 0.000 0.000 0.000 20.315 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 9.795 10.520 0.000 0.000 0.000 0.000 20.315 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 9.795 10.520 0.000 0.000 0.000 0.000 20.315 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 11.517 67.820 0.000 0.000 0.000 0.000 79.337 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 11.517 67.820 0.000 0.000 0.000 0.000 79.337 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 13.024 515.227 2419.260 0.000 0.000 0.000 2947.512 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 20432.332 10.325 191.855 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 20432.332
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 909.656 13.563 84.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 909.656
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1053.385 13.563 84.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1053.385
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 742.517 4.521 279.984 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 742.517
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 729.693 7.700 357.693 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 729.693
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 504.005 6.458 60.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 504.005
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 2175.192 11.517 15.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2175.192
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 12673.066 9.688 30.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 12673.066
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 382.227 9.795 254.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.227
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 382.182 9.795 254.788 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.182
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 240.215 9.795 160.143 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 240.215
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 240.280 9.795 160.187 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 240.280
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 382.227 9.795 254.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.227
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 382.182 9.795 254.788 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.182
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2766.397 7.104 132.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2766.397
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 382.227 9.795 254.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.227
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 382.182 9.795 254.788 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.182
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 240.280 9.795 160.187 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 240.280
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3819.822 11.517 15.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3819.822
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3819.822 11.517 15.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3819.822
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1345.470 13.024 60.503 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1345.470
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2927.804 7.104 132.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2927.804


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.839 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 2.839 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.8203 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.021 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.034 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 0.9169 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 0.9299 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.2277 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.2277 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3522
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.3522
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.052
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8120
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7993
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9233
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.9080
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.131
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.131
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.8391315 2.8391315 2.8391315  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 2.8391315 2.8391315 2.8391315  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.15703352E-14 0.29012323E-16 -0.15483104E-09 0.40370831E-16
29 8 0.22592825E-07 0.11106548E-12 0.38529762E-03 -0.25688817E-09
30 7 -0.12465369E-01 0.57225352E-08 -0.23408026E-01 0.14173579E-03
31 6 0.41143163 0.19878644E-05 0.47726710 -0.48194459E-02
32 5 -5.2499075 0.74130146E-04 -4.4810026 0.63919688E-01
33 4 33.265337 0.60571720E-03 21.595652 -0.42560793
34 3 -111.78466 0.13187857E-02 -55.931065 1.5232626
35 2 197.68466 0.74115454E-03 78.156489 -2.9095067
36 1 -171.36898 0.79055603E-04 -55.336681 2.7491709
37 0 57.057407 0.44959794E-06 15.545184  
38 9 0.14302076E-15 0.35792568E-16 -0.14541430E-09 -0.27421543E-17
39 8 0.21269444E-07 0.13686051E-12 0.37140784E-03 -0.24184090E-09
40 7 -0.12050952E-01 0.71525680E-08 -0.22811354E-01 0.13702371E-03
41 6 0.40017121 0.24988627E-05 0.46767819 -0.46867126E-02
42 5 -5.1400200 0.93645327E-04 -4.4073602 0.62557131E-01
43 4 32.779281 0.76858103E-03 21.307814 -0.41915444
44 3 -110.75053 0.16800125E-02 -55.362013 1.5083221
45 2 196.65975 0.94749847E-03 77.634567 -2.8932310
46 1 -170.99041 0.10139533E-03 -55.184883 2.7425359
47 0 57.057407 0.57877233E-06 15.570231  
48 9 0.33566835E-16 0.35384250E-16 -0.14478218E-09 -0.87565041E-18
49 8 0.21180494E-07 0.13854999E-12 0.37046393E-03 -0.24082951E-09
50 7 -0.12022754E-01 0.72481687E-08 -0.22770744E-01 0.13670309E-03
51 6 0.39940498 0.25332696E-05 0.46702484 -0.46776806E-02
52 5 -5.1325420 0.94967185E-04 -4.4023386 0.62464408E-01
53 4 32.746200 0.77967008E-03 21.288178 -0.41871522
54 3 -110.68014 0.17047184E-02 -55.323188 1.5073051
55 2 196.58997 0.96166638E-03 77.598974 -2.8921229
56 1 -170.96463 0.10293464E-03 -55.174560 2.7420841
57 0 57.057407 0.58770932E-06 15.571958  
58 9 -0.29206544E-14 0.31488305E-16 -0.15031727E-09 0.48064473E-16
59 8 0.21958778E-07 0.12356532E-12 0.37867817E-03 -0.24967887E-09
60 7 -0.12267989E-01 0.64094198E-08 -0.23123879E-01 0.13949151E-03
61 6 0.40606866 0.22324768E-05 0.47270315 -0.47562292E-02
62 5 -5.1975737 0.83445227E-04 -4.4459647 0.63270770E-01
63 4 33.033866 0.68326082E-03 21.458733 -0.42253461
64 3 -111.29222 0.14903991E-02 -55.660391 1.5161481
65 2 197.19665 0.83899866E-03 77.908180 -2.9017570
66 1 -171.18874 0.89630080E-04 -55.264364 2.7460119
67 0 57.057407 0.51068186E-06 15.557036  
68 9 -0.29497736E-14 0.32939851E-16 -0.14970570E-09 0.45584202E-16
69 8 0.21872815E-07 0.12523736E-12 0.37777579E-03 -0.24870145E-09
70 7 -0.12241065E-01 0.65023057E-08 -0.23085114E-01 0.13918537E-03
71 6 0.40533708 0.22656711E-05 0.47208016 -0.47476058E-02
72 5 -5.1904345 0.84713026E-04 -4.4411801 0.63182247E-01
73 4 33.002288 0.69384191E-03 21.440032 -0.42211534
74 3 -111.22504 0.15138688E-02 -55.623419 1.5151774
75 2 197.13007 0.85240592E-03 77.874271 -2.9006996
76 1 -171.16415 0.91081681E-04 -55.254501 2.7455809
77 0 57.057407 0.51907125E-06 15.558664  
78 7 -0.14139450E-14 -0.18802902E-16 -0.22311785E-13 0.54375338E-15
79 6 0.16999971E-10 0.27590984E-11 0.52267399E-09 -0.18616555E-10
80 5 -0.63950587E-07 0.13451749E-07 -0.21905428E-05 0.17144787E-06
81 4 0.72477507E-04 0.50724086E-05 0.17668371E-02 -0.28223350E-03
82 3 -0.10573811E-01 0.17927531E-03 -0.21549182 0.43318087E-01
83 2 0.15010112 0.77388015E-03 2.8998331 -0.61891034
84 1 -0.37982851 0.49528818E-03 -7.1368477 1.5694772
85 0 0.24168561 0.34021171E-05 4.4521969  
86 7 -0.22311785E-13 -0.18802902E-16 -0.14139450E-14 0.54375338E-15
87 6 0.52267399E-09 0.27590984E-11 0.16999971E-10 -0.18616555E-10
88 5 -0.21905428E-05 0.13451749E-07 -0.63950587E-07 0.17144787E-06
89 4 0.17668371E-02 0.50724086E-05 0.72477507E-04 -0.28223350E-03
90 3 -0.21549182 0.17927531E-03 -0.10573811E-01 0.43318087E-01
91 2 2.8998331 0.77388015E-03 0.15010112 -0.61891034
92 1 -7.1368477 0.49528818E-03 -0.37982851 1.5694772
93 0 4.4521969 0.34021171E-05 0.24168561  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.42_SHGC_0.4 37 1 VerySmooth 2.387 2.387 1.000 0.401    
2 RESWINDOW_U_0.42_SHGC_0.4 38 1 VerySmooth 2.387 2.387 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.02786E-002 0.31435 0.47495 0.47495 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12239 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.02786E-002 0.31435 0.47495 0.47495 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12239 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.260 2.5713E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1581
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 7.8112E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1770
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7259E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1154
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.4606E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.6285E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.5376E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1796
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 9.4634E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.2018
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1055
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1277
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.5906E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 5.1970E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 2.1022E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.8423E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.2142E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.9480E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.6669E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8449E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.1387E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.5560E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.6155E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.8423E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.2142E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.9480E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.6669E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8449E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.1387E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.5560E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.6155E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 36971.10676 36971.10676 2.68749 2.68749 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 28.94267 1.41140E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 5357.66882 5357.66882 0.38952 0.38952 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 3010.25887 3010.25887 0.12908 0.12908 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3303.95777 3303.95777 0.24020 0.24020 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 31.87800 1.41192E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 989.50099 989.50099 4.24321E-002 9.17347E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2595.55883 2595.55883 0.18866 0.18866 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 31.73000 1.41190E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1826.13272 1826.13272 7.83085E-002 7.83085E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1708.28061 1708.28061 0.12417 0.12417 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 32.10000 1.41196E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1282.17162 1282.17162 5.49823E-002 5.77652E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44937.50522 44937.50522 3.26673 3.26673 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 32.10000 1.41196E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2407.16878 2407.16878 0.10322 0.10322 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 21734.95386 21734.95386 1.58144 1.58144 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 7596.03452 7596.03452 0.32573 0.67639 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 66527.88759 66527.88759 4.83797 4.83797 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 17684.39473 17684.39473 0.75835 1.89399 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 12295.92494 12295.92494 1.20449 1.20449 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 31.36000 1.41183E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 6760.08134 6760.08134 0.29158 0.29158 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11955.47373 11955.47373 1.17114 1.17114 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 6781.17594 6781.17594 0.29249 0.29249 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 76113.91660 76113.91660 7.45541 7.45541 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 38437.53933 38437.53933 1.65797 1.65797 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 68086.58943 68086.58943 6.66964 6.66964 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 32.10000 1.41196E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 38841.08526 38841.08526 1.67537 1.67537 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 11285.44991 11285.44991 1.10551 1.10551 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 28.86867 1.41138E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 6717.34602 6717.34602 0.28974 0.28974 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10979.43702 10979.43702 1.07553 1.07553 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 28.44933 1.41131E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 6738.45814 6738.45814 0.29065 0.29065 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 21932.35261 21932.35261 1.59428 1.59428 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 32.10000 1.41196E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 10647.40453 10647.40453 0.45659 0.47476 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3226.02163 3226.02163 0.31602 0.31602 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 31.45867 1.41185E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 2015.66177 2015.66177 8.69406E-002 8.69406E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 3130.25848 3130.25848 0.30664 0.30664 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 2022.62307 2022.62307 8.72409E-002 8.72409E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 15009.85747 15009.85747 1.47036 1.47036 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 9574.40309 9574.40309 0.41297 0.41297 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 30249.79757 30249.79757 2.20158 2.20158 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 32.10000 1.41196E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 6497.27298 6497.27298 0.27862 1.18780 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -10.70000 1.50390E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31693.04747 31693.04747 2.30659 2.30659 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 32.10000 1.41196E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 6637.33035 6637.33035 0.28462 1.18780 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 -10.70000 1.50390E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 31269.54167 31269.54167 2.27896 2.27896 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 31.43400 1.41184E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 2378.03720 2378.03720 0.10196 0.36735 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -10.70000 1.50390E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10930.95896 10930.95896 0.79458 0.79458 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 31.97667 1.41194E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 6706.84936 6706.84936 0.28761 0.28761 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 -10.70000 1.50390E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 416800.08 22.37071 22.37071 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 244903.68 7.39026 7.39026 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00
3 FLR_3_DOAS Cooling Sensible 47880.67 19.63208 2.05125 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 67975.66 5.08494 2.05125 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.68749
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.56107
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.39212
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.79061E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.42737E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.39212
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7346.88425
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.42737E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 153.20661
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.38952
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13121
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20177
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51800
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.90374E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.56402E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20177
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4073.89817
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.56402E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 99.83010
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24020
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24639
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12442
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65704
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54632E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.43947E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12442
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1645.39902
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.43947E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 37.24181
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.18866
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.66338
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.77266E-002
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.74335E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.04814E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.77266E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2341.15177
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.04814E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 60.09543
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12417
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.58152
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.43197E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.55183E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.41830E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.43197E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1621.20973
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.41830E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 42.28822
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.26673
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.22356E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.69216
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51800
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09300E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.90578E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.69216
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11322.91280
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.90578E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 239.44892
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.58144
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.10013E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.81918
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51800
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.18675E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.04238E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.81918
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11915.03830
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.04238E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 273.61797
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.83797
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20604
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.50607
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54945
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.84912E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.70293E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.50607
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30896.11119
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.70293E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 692.56947
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.20449
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.20449
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.91391E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.90259E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68269
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65824E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.90259E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.20449
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6759.95897
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.91391E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 193.18225
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.17114
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.17114
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.93236E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.77264E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68269
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.66277E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.77264E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.17114
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6781.05319
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.93236E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 193.78489
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 7.45541
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 7.45541
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.36265E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.97443E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68343
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58413E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.97443E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.45541
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 38437.20895
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.36265E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1098.42139
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.66964
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.66964
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.39796E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.81912E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68257
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.80158E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.81912E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.66964
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 38840.75160
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.39796E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1109.95045
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.10551
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.10551
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.87652E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.51764E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68266
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.67310E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.51764E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.10551
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6717.22438
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.87652E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 191.96135
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.07553
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.07553
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.89499E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.40091E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68265
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.67802E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.40091E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.07553
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6738.33613
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.89499E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 192.56449
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.59428
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.74448
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.82584
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.11767E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.31247E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.82584
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15002.29942
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.31247E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 358.93730
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.31602
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.31602
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.76336E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.28372E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68271
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65086E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.28372E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.31602
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2015.62616
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.76336E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 57.59876
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30664
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.30664
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.76945E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.24721E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68270
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65563E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.24721E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30664
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2022.58733
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.76945E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 57.79764
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.47036
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.47036
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.37599E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 6.05793E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68255
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.70386E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.05793E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.47036
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 9574.26839
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.37599E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 273.59386
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.20158
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11479
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.14042
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51800
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.31906E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.09457E-004
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.14042
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12511.64440
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.09457E-004
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 276.44162
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.30659
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10957
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19481
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51800
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.47737E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.13191E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.19481
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12938.46370
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.13191E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 285.44423
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.27896
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.21267E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.18050
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51800
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10303E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.51287E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.18050
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8587.67530
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.51287E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 182.67107
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.79458
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.39523
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51800
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41159
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.64001E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.76664E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41159
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8877.74827
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.76664E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 221.21412
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65094
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65094
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.49216
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65094
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.37071
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.37071
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.52081
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.37071
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.37071
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.22172
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.98753
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.19854E-002
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 713237.71998
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.54752E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.37071
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 222401.11627
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.94566E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3670.81456
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.37071
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.54752E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.86923E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.94566E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 32.10000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.93776
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.41196E-002
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 86334.70852
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.08368E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 20393.41537
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.78410E-004
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 336.60104
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.08368E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.54423E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.78410E-004
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.70707E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 6052.50919
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 4.28465E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.51416
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 4.28465E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1290.34887
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 489761.98307
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 489761.98000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 4.28465E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.70707E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 4.44848
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.70707E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 4190.35625
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.70707E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1037880.29699
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1038496.74000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 118.38863
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 7384.83
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4091.31
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1653.14
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2350.55
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1627.60
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11380.62
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 11970.24
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 31042.83
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 7281.04
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 7303.76
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 41399.97
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 41834.56
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 7235.02
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 7257.76
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 15068.11
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2170.94
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2178.44
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 10312.00
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 12571.96
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 13000.94
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 8631.20
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 8915.03
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 157600.44
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 14451.42


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 20195.30 16277.53 3917.77 0.81 2263.62 22.96
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 19651.64 15834.61 3817.03 0.81 2202.48 22.34
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 123380.84 99939.37 23441.47 0.81 13851.04 140.48
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 114583.31 91510.86 23072.46 0.80 12809.12 129.92
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 18583.62 14963.88 3619.74 0.81 2082.34 21.12
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 18095.12 14565.84 3529.28 0.80 2027.41 20.56
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5291.72 4267.24 1024.48 0.81 593.22 6.02
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 5138.91 4142.71 996.20 0.81 576.03 5.84
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 24848.08 19968.12 4879.95 0.80 2782.62 28.22
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 649703.95 433341.31 216362.64 0.67 76638.21 777.31
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 63544.84 41523.88 22020.96 0.65 7288.25 73.92


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.839 2.839   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.42_SHGC_0.4 N/A 2.387 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.8554006178E-002 2.2633254777E-002 Pass Pass 3.3391879234E-003 8.4396169006E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 9.3370369031E-003 2.7006793170E-002 Pass Pass 0.3941105402 2.8097666057 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 7.3607592357E-003 1.6575702488E-002 Pass Pass 2.7291752831E-002 5.6345837397E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 3.9651284151E-004 3.2452181746E-004 Pass Pass 7.1390074144E-002 0.2233940396 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 5.6943873414E-004 4.2242317439E-004 Pass Pass 2.1339645828E-002 2.9927592305E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 7.4235114538E-002 0.2198315091 Pass Pass 1.9555186132E-002 5.2350844087E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 3.6078085129E-002 7.9579355052E-002 Pass Pass 5.5964180194E-002 0.1044107785 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.9263018255E-002 4.1729352298E-002 Pass Pass 1.9198264063E-002 4.6874317657E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.6036823599E-002 0.3008280401 Pass Pass 0.2845099198 1.1419698610 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.2647327290E-002 0.3119030828 Pass Pass 0.1427420661 0.4814723308 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.0070019194E-002 5.2961833236E-002 Pass Pass 0.2759006040 1.0113991753 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 6.5836932293E-002 0.1782960199 Pass Pass 0.1428318390 0.4443215451 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 7.7524155132E-002 0.2500107395 Pass Pass 0.1878835849 0.5550836881 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 8.4340554256E-002 0.2787520987 Pass Pass 0.4070563330 2.5248767975 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.9129061764E-004 4.0393544550E-004 Pass Pass 1.1040099974 9.1352631745 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2651677198E-002 0.3208976677 Pass Pass 0.2087857952 0.7703605490 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2681583273E-002 0.3268190526 Pass Pass 0.1436420422 0.4914105160 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.9800398502E-002 0.2206256463 Pass Pass 0.2545074684 1.3564801131 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 5.4715272216E-002 0.1003145613 Pass Pass 8.7295340941E-003 1.9123630343E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 4.7710144899E-002 8.3471681680E-002 Pass Pass 9.1170799779E-003 2.3721572775E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.4803218239E-002 0.1068133696 Pass Pass 2.2459625577E-002 4.0853809994E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 8.5077570333E-004 6.4939138436E-004 Pass Pass 1.5070786214 16.3297377109 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4402.06 103.69 1298.07 5416.82 5561.03 16781.67



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -10.70 0.00 -10.70 Wetbulb [C] 7.50 320.00
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 32.10 7.40 23.10 Wetbulb [C] 5.60 230.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 172.00 59      
Feb 49.00 37      
Mar 40.00 38      
Apr 70.00 48      
May 70.00 36      
Jun 25.00 15      
Jul 64.00 20      
Aug 2.00 4      
Sep 73.00 32      
Oct 7.00 8      
Nov 88.00 34      
Dec 62.00 39      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.806 0.917 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.806 0.917 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.806 0.917 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.806 0.917 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.806 0.917 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.806 0.917 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.816 0.930 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.816 0.930 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.816 0.930 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.816 0.930 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.816 0.930 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.896 1.034 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.215 0.228 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.215 0.228 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.215 0.228 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.215 0.228 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.215 0.228 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.215 0.228 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.215 0.228 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.215 0.228 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.215 0.228 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.215 0.228 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.217 0.228 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.212 0.228 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.212 0.228 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.212 0.228 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.217 0.228 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.217 0.228 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.217 0.228 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 2.387 0.401 0.442             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 2.387 0.401 0.442             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 2.387 0.401 0.442             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.387 0.401 0.442             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.42_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.387 0.401 0.442             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.387 0.401 0.442             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.42_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.387 0.401 0.442             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 2.387 0.401 0.442             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 2.387 0.401 0.442             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.42_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.387 0.401 0.442             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.387 0.401 0.442             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.387 0.401 0.442             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.42_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.387 0.401 0.442             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.387 0.401 0.442             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 2.387 0.401 0.442             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 2.387 0.401 0.442             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.387 0.401 0.442             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.387 0.401 0.442             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.42_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.387 0.401 0.442             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.387 0.401 0.442             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.42_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.387 0.401 0.442             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.42_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 2.387 0.401 0.442             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.387 0.401 0.442             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.387 0.401 0.442             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.387 0.401 0.442             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.387 0.401 0.442             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.387 0.401 0.442             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 2.387 0.401 0.442             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 2.387 0.401 0.442             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.42_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.387 0.401 0.442             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.387 0.401 0.442                      
North Total or Average             432.95 2.387 0.401 0.442                      
Non-North Total or Average             780.84 2.387 0.401 0.442                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.992 2.839 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.992 2.839 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.992 2.839 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.992 2.839 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 10.3255 1978.83 20432.33 LightsWired LTG_SCH_BASEMENT 49.32 168.00 49.26 0.0000 Y 188.94
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.5625 67.07 909.66 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.76
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.5625 77.67 1053.39 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 10.14
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.5208 164.24 742.52 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.17
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 7.7005 94.76 729.69 LightsWired LTG_SCH_STORAGE 30.30 168.00 30.27 0.0000 Y 4.15
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 6.4583 78.04 504.01 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 5.55
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 11.5174 188.86 2175.19 LightsWired LTG_SCH_DINING 58.69 168.00 39.59 0.0000 Y 16.17
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 9.6875 1308.19 12673.07 LightsWired LTG_SCH_LOBBY 44.02 168.00 41.56 0.0000 Y 98.86
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 9.7951 156.09 1528.91 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.93
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 9.7951 156.07 1528.73 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.92
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 9.7951 1863.81 18256.32 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 130.45
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 9.7951 1864.32 18261.31 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 130.49
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 9.7951 156.09 1528.91 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.93
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 9.7951 156.07 1528.73 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.92
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 7.1042 1557.62 11065.59 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 91.33
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 9.7951 39.02 382.23 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.73
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 9.7951 39.02 382.18 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.73
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 9.7951 220.77 2162.52 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 15.45
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 11.5174 331.66 3819.82 LightsWired LTG_SCH_DINING 58.69 168.00 49.30 0.0000 Y 35.35
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 11.5174 331.66 3819.82 LightsWired LTG_SCH_DINING 58.69 168.00 49.30 0.0000 Y 35.35
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 13.0243 103.30 1345.47 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 14.81
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 7.1042 412.12 2927.80 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 24.17
Interior Lighting Total       9.4981 11345.29 107758.18               494.79


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 12673.07 887.11
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 12673.07 887.11
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 2175.19 848.32
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 2175.19 848.32
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 16690.39 AstronomicalClock -   83.64 83.64 262.05
Exterior Lighting Total 16690.39           262.05



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 489761.98 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1038496.74 2.96 1038679.28 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13726.20 20195.30 16277.53 3917.77 0.81 - 2263.62 22.96
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13362.38 19651.64 15834.61 3817.03 0.81 - 2202.48 22.34
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 83277.55 123380.84 99939.37 23441.47 0.81 - 13851.04 140.48
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 78929.22 114583.31 91510.86 23072.46 0.80 - 12809.12 129.92
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12648.41 18583.62 14963.88 3619.74 0.81 - 2082.34 21.12
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12321.61 18095.12 14565.84 3529.28 0.80 - 2027.41 20.56
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3594.14 5291.72 4267.24 1024.48 0.81 - 593.22 6.02
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3491.93 5138.91 4142.71 996.20 0.81 - 576.03 5.84
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 16960.90 24848.08 19968.12 4879.95 0.80 - 2782.62 28.22
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 713237.72 649703.95 433341.31 216362.64 0.67 - 76638.21 777.31
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 86334.71 63544.84 41523.88 22020.96 0.65 - 7288.25 73.92
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 7346.88 7384.83 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4073.90 4091.31 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1645.40 1653.14 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2341.15 2350.55 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1621.21 1627.60 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11322.91 11380.62 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11915.04 11970.24 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 30896.11 31042.83 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6759.96 7281.04 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6781.05 7303.76 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 38437.21 41399.97 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 38840.75 41834.56 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6717.22 7235.02 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6738.34 7257.76 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 15002.30 15068.11 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2015.63 2170.94 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2022.59 2178.44 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 9574.27 10312.00 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 12511.64 12571.96 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 12938.46 13000.94 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 8587.68 8631.20 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 8877.75 8915.03 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 222401.12 157600.44 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 20393.42 14451.42 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.20 847.52 703.64 1.00 1.15 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.17 824.06 703.64 1.00 1.16 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 7.46 5245.90 703.64 1.00 0.95 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.67 4693.00 703.64 1.00 0.95 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.11 777.88 703.64 1.00 1.17 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.08 756.78 703.64 1.00 1.18 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.32 222.36 703.64 1.00 1.68 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.31 215.76 703.64 1.00 1.70 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.47 1034.60 703.64 1.00 1.12 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.37 50124.68 2240.64 1.00 1.11 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.037071 6052.51 163269.44 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.004285 1290.35 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.037071 4190.36 113036.94 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 36971.11 36971.11 18.68 2.687 2.687 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 24.00 24.00 0.00915 28.94 0.01411 0.854 0.00
RETAIL_1_FLR_1 5357.67 5357.67 79.88 0.390 0.390 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 24.00 0.00908 31.79 0.01412 0.079 0.00
RETAIL_2_FLR_1 3303.96 3303.96 42.54 0.240 0.240 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00943 31.88 0.01412 0.092 0.00
MECH_FLR_1 2595.56 2595.56 15.80 0.189 0.189 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 24.00 24.00 0.00896 31.73 0.01412 0.000 0.00
STORAGE_FLR_1 1708.28 1708.28 18.03 0.124 0.124 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00897 32.10 0.01412 0.058 0.00
LAUNDRY_FLR_1 44937.51 44937.51 575.83 3.267 3.267 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00856 32.10 0.01412 0.000 0.00
CAFE_FLR_1 21734.95 21734.95 115.08 1.581 1.581 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 23.99 0.01003 31.79 0.01412 0.676 0.00
LOBBY_FLR_1 66527.89 66527.89 50.86 4.838 4.838 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 23.99 0.00999 31.85 0.01412 1.894 0.00
ROOM_1_FLR_3 12295.92 12295.92 315.10 1.204 1.204 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00866 31.36 0.01412 0.062 0.00
ROOM_2_FLR_3 11955.47 11955.47 306.41 1.171 1.171 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00866 31.26 0.01412 0.062 0.00
ROOM_3_MULT19_FLR_3 76113.92 76113.92 3103.67 7.455 7.455 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 21.11 21.11 0.00858 31.85 0.01412 0.837 0.00
ROOM_4_MULT19_FLR_3 68086.59 68086.59 2775.58 6.670 6.670 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 21.11 21.11 0.00880 32.10 0.01412 0.837 0.00
ROOM_5_FLR_3 11285.45 11285.45 289.21 1.106 1.106 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 21.11 21.11 0.00867 28.87 0.01411 0.062 0.00
ROOM_6_FLR_3 10979.44 10979.44 281.40 1.076 1.076 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 21.11 21.11 0.00868 28.45 0.01411 0.062 0.00
CORRIDOR_FLR_3 21932.35 21932.35 56.32 1.594 1.594 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00945 32.10 0.01412 0.475 0.00
ROOM_1_FLR_6 3226.02 3226.02 82.67 0.316 0.316 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 21.11 21.11 0.00865 31.46 0.01412 0.015 0.00
ROOM_2_FLR_6 3130.26 3130.26 80.23 0.307 0.307 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00866 31.26 0.01412 0.015 0.00
ROOM_3_MULT9_FLR_6 15009.86 15009.86 611.88 1.470 1.470 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 21.11 21.11 0.00870 31.85 0.01412 0.099 0.00
BANQUET_FLR_6 30249.80 30249.80 91.21 2.202 2.202 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.98 0.01039 32.10 0.01412 1.188 0.00
DINING_FLR_6 31693.05 31693.05 95.56 2.307 2.307 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.99 0.01030 32.10 0.01412 1.188 0.00
KITCHEN_FLR_6 31269.54 31269.54 302.69 2.279 2.279 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01008 31.43 0.01412 0.367 0.00
CORRIDOR_FLR_6 10930.96 10930.96 26.52 0.795 0.795 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00903 31.98 0.01412 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.33 0.00150 -10.70 0.00150 0.854 0.00
RETAIL_1_FLR_1 3010.26 3010.26 44.88 0.129 0.129 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00749 -10.70 0.00150 0.079 0.00
RETAIL_2_FLR_1 989.50 989.50 12.74 0.042 0.092 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00741 -10.70 0.00150 0.092 0.00
MECH_FLR_1 1826.13 1826.13 11.12 0.078 0.078 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00727 -10.70 0.00150 0.000 0.00
STORAGE_FLR_1 1282.17 1282.17 13.53 0.055 0.058 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00739 -10.70 0.00150 0.058 0.00
LAUNDRY_FLR_1 2407.17 2407.17 30.85 0.103 0.103 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00724 -10.70 0.00150 0.000 0.00
CAFE_FLR_1 7596.03 7596.03 40.22 0.326 0.676 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00755 -10.70 0.00150 0.676 0.00
LOBBY_FLR_1 17684.39 17684.39 13.52 0.758 1.894 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00746 -10.70 0.00150 1.894 0.00
ROOM_1_FLR_3 6760.08 6760.08 173.24 0.292 0.292 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00748 -10.70 0.00150 0.062 0.00
ROOM_2_FLR_3 6781.18 6781.18 173.80 0.292 0.292 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00748 -10.70 0.00150 0.062 0.00
ROOM_3_MULT19_FLR_3 38437.54 38437.54 1567.35 1.658 1.658 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00751 -10.70 0.00150 0.837 0.00
ROOM_4_MULT19_FLR_3 38841.09 38841.09 1583.38 1.675 1.675 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00752 -10.70 0.00150 0.837 0.00
ROOM_5_FLR_3 6717.35 6717.35 172.14 0.290 0.290 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00748 -10.70 0.00150 0.062 0.00
ROOM_6_FLR_3 6738.46 6738.46 172.70 0.291 0.291 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00748 -10.70 0.00150 0.062 0.00
CORRIDOR_FLR_3 10647.40 10647.40 27.34 0.457 0.475 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00759 -10.70 0.00150 0.475 0.00
ROOM_1_FLR_6 2015.66 2015.66 51.65 0.087 0.087 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00756 -10.70 0.00150 0.015 0.00
ROOM_2_FLR_6 2022.62 2022.62 51.84 0.087 0.087 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00756 -10.70 0.00150 0.015 0.00
ROOM_3_MULT9_FLR_6 9574.40 9574.40 390.31 0.413 0.413 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00757 -10.70 0.00150 0.099 0.00
BANQUET_FLR_6 6497.27 6497.27 19.59 0.279 1.188 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00766 -10.70 0.00150 1.188 0.00
DINING_FLR_6 6637.33 6637.33 20.01 0.285 1.188 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 21.00 21.00 0.00766 -10.70 0.00150 1.188 0.00
KITCHEN_FLR_6 2378.04 2378.04 23.02 0.102 0.367 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00662 -10.70 0.00150 0.367 0.00
CORRIDOR_FLR_6 6706.85 6706.85 16.27 0.288 0.288 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 21.00 21.00 0.00771 -10.70 0.00150 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 22.37 22.37 7.39 7.39 22.3707 11.6509 22.3707 0.5208 0.3000
FLR_3_DOAS 19.63 2.05 5.08 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 7346.884 7346.884 1.392121 0.00006427 153.207 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 7346.88 7346.88 1.392121 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 0.00 0.00 7388.18 7388.18
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4073.898 4073.898 0.201769 0.00003564 99.830 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4073.90 4073.90 0.201769 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00749331 48.4603 3010.26 0.00 4095.04 4095.04
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1645.399 1645.399 0.124425 0.00001439 37.242 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1645.40 1645.40 0.124425 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00741289 47.9447 989.50 0.00 1654.27 1654.27
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2341.152 2341.152 0.097727 0.00002048 60.095 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2341.15 2341.15 0.097727 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00726669 47.0101 1826.13 0.00 2352.99 2352.99
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1621.210 1621.210 0.064320 0.00001418 42.288 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1621.21 1621.21 0.064320 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00738509 47.7672 1282.17 0.00 1629.36 1629.36
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11322.913 11322.913 1.692164 0.00009906 239.449 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 11322.91 11322.91 1.692164 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00724354 46.8643 2407.17 0.00 11386.24 11386.24
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 11915.038 11915.038 0.819184 0.00010424 273.618 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 11915.04 11915.04 0.819184 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00755179 48.8335 7596.03 0.00 11978.98 11978.98
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 30896.111 30896.111 2.506071 0.00027029 692.569 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 30896.11 30896.11 2.506071 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00745835 48.2353 17684.39 0.00 31063.37 31063.37
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 13726.197 -999.000 1.204491 0.00049026 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 13726.20 13210.42 1.204491 21.68 15.69 0.00865824 12.80 12.09 0.00850000 31.36 0.01411830 22.93 0.0000 21.11 0.00865824 55.5110 12295.92 0.00 13748.95 13028.68
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 6759.959 6759.959 0.291579 0.00005914 193.182 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 6759.96 6759.96 0.291579 21.11 14.41 0.00748032 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00748032 48.0486 6760.08 0.00 7287.37 7287.37
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 13362.378 -999.000 1.171142 0.00047726 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 13362.38 12846.45 1.171142 21.68 15.69 0.00866277 12.80 12.09 0.00850000 31.26 0.01411813 22.90 0.0000 21.11 0.00866277 55.5397 11955.47 0.00 13384.50 12670.50
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 6781.053 6781.053 0.292489 0.00005932 193.785 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 6781.05 6781.05 0.292489 21.11 14.41 0.00748185 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00748185 48.0583 6781.18 0.00 7310.11 7310.11
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 83277.547 -999.000 7.455415 0.00297443 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown 7/21 13:20:00 83277.55 81584.14 7.455415 21.68 15.62 0.00858413 12.80 12.09 0.00850000 31.85 0.01411920 23.06 0.0000 21.11 0.00858413 55.0401 76113.92 0.00 83418.65 80378.48
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 38437.209 38437.209 1.657965 0.00033627 1098.421 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 38437.21 38437.21 1.657965 21.11 14.44 0.00751284 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00751284 48.2536 38437.54 0.00 41436.40 41436.40
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 78929.215 -999.000 6.669636 0.00281912 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown 7/21 15:00:00 78929.22 73462.89 6.669636 21.68 15.81 0.00880158 12.80 12.09 0.00850000 32.10 0.01411964 23.13 0.0000 21.11 0.00880158 56.4171 68086.59 0.00 79054.98 72590.18
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 38840.752 38840.752 1.675372 0.00033980 1109.950 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 38840.75 38840.75 1.675372 21.11 14.44 0.00751740 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00751740 48.2825 38841.09 0.00 41871.43 41871.43
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 12648.412 -999.000 1.105509 0.00045176 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 unknown 7/21 09:40:00 12648.41 12130.33 1.105509 21.68 15.70 0.00867310 12.80 12.09 0.00850000 28.87 0.01411382 22.22 0.0000 21.11 0.00867310 55.6050 11285.45 0.00 12669.29 11965.88
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 6717.224 6717.224 0.289736 0.00005877 191.961 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 6717.22 6717.22 0.289736 21.11 14.41 0.00747728 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00747728 48.0293 6717.35 0.00 7241.30 7241.30
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 12321.607 -999.000 1.075533 0.00044009 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown 7/21 09:20:00 12321.61 11803.18 1.075533 21.68 15.71 0.00867802 12.80 12.09 0.00850000 28.45 0.01411307 22.10 0.0000 21.11 0.00867802 55.6361 10979.44 0.00 12341.92 11643.95
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 6738.336 6738.336 0.290647 0.00005895 192.564 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 6738.34 6738.34 0.290647 21.11 14.41 0.00747882 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00747882 48.0391 6738.46 0.00 7264.06 7264.06
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 15002.299 15002.299 0.825835 0.00013125 358.937 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 15002.30 15002.30 0.825835 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00759123 49.0839 10647.40 0.00 15080.84 15080.84
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3594.142 -999.000 0.316016 0.00012837 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 unknown 7/21 16:20:00 3594.14 3465.16 0.316016 21.68 15.68 0.00865086 12.80 12.09 0.00850000 31.46 0.01411849 22.95 0.0000 21.11 0.00865086 55.4643 3226.02 0.00 3600.11 3417.15
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2015.626 2015.626 0.086941 0.00001763 57.599 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 2015.63 2015.63 0.086941 21.11 14.48 0.00755849 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00755849 48.5447 2015.66 0.00 2172.89 2172.89
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3491.925 -999.000 0.306636 0.00012472 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 3491.93 3362.80 0.306636 21.68 15.69 0.00865563 12.80 12.09 0.00850000 31.26 0.01411813 22.90 0.0000 21.11 0.00865563 55.4945 3130.26 0.00 3497.72 3316.42
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2022.587 2022.587 0.087241 0.00001769 57.798 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 2022.59 2022.59 0.087241 21.11 14.48 0.00755994 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00755994 48.5539 2022.62 0.00 2180.39 2180.39
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 16960.895 -999.000 1.470361 0.00060579 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown 7/21 13:20:00 16960.90 16148.64 1.470361 21.68 15.73 0.00870386 12.80 12.09 0.00850000 31.85 0.01411920 23.06 0.0000 21.11 0.00870386 55.7998 15009.86 0.00 16988.65 15936.35
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 9574.268 9574.268 0.412973 0.00008376 273.594 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 9574.27 9574.27 0.412973 21.11 14.49 0.00757110 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00757110 48.6242 9574.40 0.00 10321.28 10321.28
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 12511.644 12511.644 1.140420 0.00010946 276.442 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 12511.64 12511.64 1.140420 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00765805 49.5110 6497.27 0.00 12579.76 12579.76
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 12938.464 12938.464 1.194813 0.00011319 285.444 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 12938.46 12938.46 1.194813 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00766490 49.5551 6637.33 0.00 13008.95 13008.95
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 8587.675 8587.675 1.180501 0.00007513 182.671 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 8587.68 8587.68 1.180501 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00662023 42.8799 2378.04 0.00 8635.61 8635.61
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 8877.748 8877.748 0.411591 0.00007767 221.214 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 8877.75 8877.75 0.411591 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00770743 49.8261 6706.85 0.00 8923.56 8923.56
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 713237.720 -999.000 22.370713 0.02547520 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 713237.72 467906.38 22.370713 28.22 20.53 0.01198539 10.99 10.99 0.00850000 32.10 0.01411964 23.13 52.1282 23.99 0.00961913 51.6874 307213.80 0.00 714044.88 462437.88
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 222401.116 222401.116 6.711214 0.00194566 3670.815 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 222401.12 222401.12 6.711214 -10.70 -10.70 0.00150390 16.70 13.18 0.00800000 -10.70 0.00150390 -10.70 173.7608 21.07 0.00649056 41.8720 67312.46 0.00 190559.29 190559.29
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 86334.709 -999.000 2.051317 0.00308368 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 86334.71 51162.86 2.051317 32.10 23.13 0.01411964 11.94 11.74 0.00850000 32.10 0.01411964 23.13 99.9965 21.11 0.00868931 55.7063 200417.98 0.00 86433.83 51479.65
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 20393.415 20393.415 0.615395 0.00017841 336.601 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 20393.42 20393.42 0.615395 -10.70 -10.70 0.00150390 16.70 13.18 0.00800000 -10.70 0.00150390 -10.70 333.3216 21.11 0.00751532 48.2694 117888.37 0.00 17473.63 17473.63



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 7346.884 7346.884 1.392121 0.00006427 153.207 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.4705 1.500093 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 7346.88 7346.88 1.0000 1.67554996 1.392121 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.06426719 60.00 32.22 27.78 0.000 7346.88 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6928 0.00 0.00 7388.18 7388.18 1.67554996 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4073.898 4073.898 0.201769 0.00003564 99.830 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 0.8154 0.831812 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4073.90 4073.90 1.0000 0.24284819 0.201769 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.03563660 60.00 32.22 27.78 0.000 4073.90 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00749331 21.00 0.00749331 48.4603 3010.26 0.00 4095.04 4095.04 0.24284819 16.60 13.15 0.00800000 36934.7 33.14 19.07 0.00800000 53797.3
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1645.399 1645.399 0.124425 0.00001439 37.242 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 0.3293 0.335959 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1645.40 1645.40 1.0000 0.14975674 0.124425 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.01439320 60.00 32.22 27.78 0.000 1645.40 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00741289 21.00 0.00741289 47.9447 989.50 0.00 1654.27 1654.27 0.14975674 16.60 13.15 0.00800000 36934.7 27.43 17.17 0.00800000 47981.1
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2341.152 2341.152 0.097727 0.00002048 60.095 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 0.4686 0.478018 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2341.15 2341.15 1.0000 0.11762321 0.097727 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.02047933 60.00 32.22 27.78 0.000 2341.15 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00726669 21.00 0.00726669 47.0101 1826.13 0.00 2352.99 2352.99 0.11762321 16.60 13.15 0.00800000 36934.7 36.22 20.04 0.00800000 56939.2
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1621.210 1621.210 0.064320 0.00001418 42.288 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 0.3245 0.331020 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1621.21 1621.21 1.0000 0.07741486 0.064320 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.01418160 60.00 32.22 27.78 0.000 1621.21 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00738509 21.00 0.00738509 47.7672 1282.17 0.00 1629.36 1629.36 0.07741486 16.60 13.15 0.00800000 36934.7 37.24 20.35 0.00800000 57981.8
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 11322.913 11322.913 1.692164 0.00009906 239.449 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 2.2663 2.311922 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 11322.91 11322.91 1.0000 2.03667983 1.692164 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.09904768 60.00 32.22 27.78 0.000 11322.91 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00724354 21.00 0.00724354 46.8643 2407.17 0.00 11386.24 11386.24 2.03667983 16.60 13.15 0.00800000 36934.7 22.08 15.25 0.00800000 42525.3
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 11915.038 11915.038 0.819184 0.00010424 273.618 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 2.3848 2.432822 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 11915.04 11915.04 1.0000 0.98596564 0.819184 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.10422732 60.00 32.22 27.78 0.000 11915.04 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00755179 21.00 0.00755179 48.8335 7596.03 0.00 11978.98 11978.98 0.98596564 16.60 13.15 0.00800000 36934.7 28.51 17.54 0.00800000 49084.2
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 30896.111 30896.111 2.506071 0.00027029 692.569 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 6.1839 6.308393 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 30896.11 30896.11 1.0000 3.01629424 2.506071 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.27026509 60.00 32.22 27.78 0.000 30896.11 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00745835 21.00 0.00745835 48.2353 17684.39 0.00 31063.37 31063.37 3.01629424 16.60 13.15 0.00800000 36934.7 26.70 16.91 0.00800000 47233.3
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 13726.197 -999.000 1.204491 0.00049026 -999.000 -999.0000 1.00000 1.00000 1020.9352 1004.8586 1.2036 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.204491 1.44971931   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 1.3225 1.322497 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 13726.20 13210.42 1.0000 1.44971931 1.204491 21.68 15.69 0.00865824 43790.4 12.80 12.09 0.00850000 34322.2 0.49020879 6.70 13.37 6.67 0.000 13726.20 31.36 0.01411830 22.93 0.00000000 0.0000 21.11 0.00865824 21.11 0.00865824 55.5110 12295.92 0.00 13748.95 13028.68 1.44971931 21.68 15.69 0.00865824 43790.4 12.88 12.09 0.00846147 34306.5
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 6759.959 6759.959 0.291579 0.00005914 193.182 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.204491 1.44971931   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.3530 1.380254 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 6759.96 6759.96 1.0000 0.35094333 0.291579 21.11 14.41 0.00748032 40213.7 40.00 21.18 0.00800000 60796.0 0.05913304 60.00 32.22 27.78 0.000 6759.96 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00748032 21.11 0.00748032 48.0486 6760.08 0.00 7287.37 7287.37 0.35094333 16.60 12.64 0.00748032 35619.0 36.98 19.88 0.00748032 56384.1
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 13362.378 -999.000 1.171142 0.00047726 -999.000 -999.0000 1.00000 1.00000 1020.9437 1004.8586 1.2036 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.171142 1.40958024   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 1.2875 1.287444 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 13362.38 12846.45 1.0000 1.40958024 1.171142 21.68 15.69 0.00866277 43801.9 12.80 12.09 0.00850000 34322.2 0.47721557 6.70 13.37 6.67 0.000 13362.38 31.26 0.01411813 22.90 0.00000000 0.0000 21.11 0.00866277 21.11 0.00866277 55.5397 11955.47 0.00 13384.50 12670.50 1.40958024 21.68 15.70 0.00866277 43801.9 12.88 12.09 0.00846216 34306.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 6781.053 6781.053 0.292489 0.00005932 193.785 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.171142 1.40958024   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.3572 1.384561 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 6781.05 6781.05 1.0000 0.35203843 0.292489 21.11 14.41 0.00748185 40217.5 40.00 21.18 0.00800000 60796.0 0.05931756 60.00 32.22 27.78 0.000 6781.05 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00748185 21.11 0.00748185 48.0583 6781.18 0.00 7310.11 7310.11 0.35203843 16.60 12.64 0.00748185 35622.9 36.98 19.88 0.00748185 56388.0
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 83277.547 -999.000 7.455415 0.00297443 -999.000 -999.0000 1.00000 1.00000 1020.7975 1004.8586 1.2036 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.455415 8.97329950   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 8.0238 8.023661 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown unknown unknown 7/21 13:20:00 Sensible 83277.55 81584.14 1.0000 8.97329950 7.455415 21.68 15.62 0.00858413 43602.8 12.80 12.09 0.00850000 34322.2 2.97412207 6.70 13.37 6.67 0.000 83277.55 31.85 0.01411920 23.06 0.00000000 0.0000 21.11 0.00858413 21.11 0.00858413 55.0401 76113.92 0.00 83418.65 80378.48 8.97329950 21.68 15.63 0.00858413 43602.8 12.91 12.09 0.00844995 34306.5
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 38437.209 38437.209 1.657965 0.00033627 1098.421 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.455415 8.97329950   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 7.6933 7.848141 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 38437.21 38437.21 1.0000 1.99551887 1.657965 21.11 14.44 0.00751284 40296.7 40.00 21.18 0.00800000 60796.0 0.33623117 60.00 32.22 27.78 0.000 38437.21 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00751284 21.11 0.00751284 48.2536 38437.54 0.00 41436.40 41436.40 1.99551887 16.60 12.67 0.00751284 35701.3 36.98 19.91 0.00751284 56466.1
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 78929.215 -999.000 6.669636 0.00281912 -999.000 -999.0000 1.00000 1.00000 1021.2017 1004.8586 1.2036 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.669636 8.02753992   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 7.6048 7.604706 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown unknown unknown 7/21 15:00:00 Sensible 78929.22 73462.89 1.0000 8.02753992 6.669636 21.68 15.81 0.00880158 44154.5 12.80 12.09 0.00850000 34322.2 2.81882846 6.70 13.37 6.67 0.000 78929.22 32.10 0.01411964 23.13 0.00000000 0.0000 21.11 0.00880158 21.11 0.00880158 56.4171 68086.59 0.00 79054.98 72590.18 8.02753992 21.68 15.82 0.00880158 44154.5 12.83 12.09 0.00848261 34306.5
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 38840.752 38840.752 1.675372 0.00033980 1109.950 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.669636 8.02753992   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 7.7741 7.930536 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 38840.75 38840.75 1.0000 2.01646932 1.675372 21.11 14.44 0.00751740 40308.3 40.00 21.18 0.00800000 60796.0 0.33976118 60.00 32.22 27.78 0.000 38840.75 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00751740 21.11 0.00751740 48.2825 38841.09 0.00 41871.43 41871.43 2.01646932 16.60 12.68 0.00751740 35712.9 36.98 19.91 0.00751740 56477.6
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 12648.412 -999.000 1.105509 0.00045176 -999.000 -999.0000 1.00000 1.00000 1020.9629 1004.8586 1.2036 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.105509 1.33058468   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 1.2187 1.218655 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 unknown unknown unknown 7/21 09:40:00 Sensible 12648.41 12130.33 1.0000 1.33058468 1.105509 21.68 15.70 0.00867310 43828.1 12.80 12.09 0.00850000 34322.2 0.45171745 6.70 13.37 6.67 0.000 12648.41 28.87 0.01411382 22.22 0.00000000 0.0000 21.11 0.00867310 21.11 0.00867310 55.6050 11285.45 0.00 12669.29 11965.88 1.33058468 21.68 15.71 0.00867310 43828.1 12.87 12.09 0.00846373 34306.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 6717.224 6717.224 0.289736 0.00005877 191.961 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.105509 1.33058468   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.3445 1.371528 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 6717.22 6717.22 1.0000 0.34872476 0.289736 21.11 14.41 0.00747728 40205.9 40.00 21.18 0.00800000 60796.0 0.05875921 60.00 32.22 27.78 0.000 6717.22 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00747728 21.11 0.00747728 48.0293 6717.35 0.00 7241.30 7241.30 0.34872476 16.60 12.64 0.00747728 35611.3 36.98 19.88 0.00747728 56376.4
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 12321.607 -999.000 1.075533 0.00044009 -999.000 -999.0000 1.00000 1.00000 1020.9720 1004.8586 1.2036 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.075533 1.29450558   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 1.1872 1.187167 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown unknown unknown 7/21 09:20:00 Sensible 12321.61 11803.18 1.0000 1.29450558 1.075533 21.68 15.71 0.00867802 43840.6 12.80 12.09 0.00850000 34322.2 0.44004613 6.70 13.37 6.67 0.000 12321.61 28.45 0.01411307 22.10 0.00000000 0.0000 21.11 0.00867802 21.11 0.00867802 55.6361 10979.44 0.00 12341.92 11643.95 1.29450558 21.68 15.71 0.00867802 43840.6 12.87 12.09 0.00846447 34306.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 6738.336 6738.336 0.290647 0.00005895 192.564 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.075533 1.29450558   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.3487 1.375839 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 6738.34 6738.34 1.0000 0.34982078 0.290647 21.11 14.41 0.00747882 40209.9 40.00 21.18 0.00800000 60796.0 0.05894389 60.00 32.22 27.78 0.000 6738.34 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00747882 21.11 0.00747882 48.0391 6738.46 0.00 7264.06 7264.06 0.34982078 16.60 12.64 0.00747882 35615.2 36.98 19.88 0.00747882 56380.3
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 15002.299 15002.299 0.825835 0.00013125 358.937 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 3.0028 3.063182 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 15002.30 15002.30 1.0000 0.99397145 0.825835 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.13123327 60.00 32.22 27.78 0.000 15002.30 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00759123 21.00 0.00759123 49.0839 10647.40 0.00 15080.84 15080.84 0.99397145 16.60 13.15 0.00800000 36934.7 31.48 18.53 0.00800000 52107.0
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3594.142 -999.000 0.316016 0.00012837 -999.000 -999.0000 1.00000 1.00000 1020.9215 1004.8586 1.2036 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.316016 0.38035556   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 0.3463 0.346290 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 unknown unknown unknown 7/21 16:20:00 Sensible 3594.14 3465.16 1.0000 0.38035556 0.316016 21.68 15.68 0.00865086 43771.6 12.80 12.09 0.00850000 34322.2 0.12835894 6.70 13.37 6.67 0.000 3594.14 31.46 0.01411849 22.95 0.00000000 0.0000 21.11 0.00865086 21.11 0.00865086 55.4643 3226.02 0.00 3600.11 3417.15 0.38035556 21.68 15.69 0.00865086 43771.6 12.88 12.09 0.00846034 34306.5
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2015.626 2015.626 0.086941 0.00001763 57.599 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.316016 0.38035556   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 0.4034 0.411552 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 2015.63 2015.63 1.0000 0.10464129 0.086941 21.11 14.48 0.00755849 40412.2 40.00 21.18 0.00800000 60796.0 0.01763178 60.00 32.22 27.78 0.000 2015.63 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00755849 21.11 0.00755849 48.5447 2015.66 0.00 2172.89 2172.89 0.10464129 16.60 12.72 0.00755849 35816.9 36.98 19.94 0.00755849 56582.0
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3491.925 -999.000 0.306636 0.00012472 -999.000 -999.0000 1.00000 1.00000 1020.9304 1004.8586 1.2036 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.306636 0.36906499   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 0.3364 0.336442 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 3491.93 3362.80 1.0000 0.36906499 0.306636 21.68 15.69 0.00865563 43783.7 12.80 12.09 0.00850000 34322.2 0.12470843 6.70 13.37 6.67 0.000 3491.93 31.26 0.01411813 22.90 0.00000000 0.0000 21.11 0.00865563 21.11 0.00865563 55.4945 3130.26 0.00 3497.72 3316.42 0.36906499 21.68 15.69 0.00865563 43783.7 12.88 12.09 0.00846107 34306.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2022.587 2022.587 0.087241 0.00001769 57.798 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.306636 0.36906499   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 0.4048 0.412974 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 2022.59 2022.59 1.0000 0.10500268 0.087241 21.11 14.48 0.00755994 40415.9 40.00 21.18 0.00800000 60796.0 0.01769267 60.00 32.22 27.78 0.000 2022.59 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00755994 21.11 0.00755994 48.5539 2022.62 0.00 2180.39 2180.39 0.10500268 16.60 12.72 0.00755994 35820.6 36.98 19.94 0.00755994 56585.7
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 16960.895 -999.000 1.470361 0.00060579 -999.000 -999.0000 1.00000 1.00000 1021.0200 1004.8586 1.2036 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.470361 1.76971969   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 1.6342 1.634156 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown unknown unknown 7/21 13:20:00 Sensible 16960.90 16148.64 1.0000 1.76971969 1.470361 21.68 15.73 0.00870386 43906.1 12.80 12.09 0.00850000 34322.2 0.60573077 6.70 13.37 6.67 0.000 16960.90 31.85 0.01411920 23.06 0.00000000 0.0000 21.11 0.00870386 21.11 0.00870386 55.7998 15009.86 0.00 16988.65 15936.35 1.76971969 21.68 15.73 0.00870386 43906.1 12.86 12.09 0.00846835 34306.5
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 9574.268 9574.268 0.412973 0.00008376 273.594 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.470361 1.76971969   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.9163 1.954882 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 9574.27 9574.27 1.0000 0.49705278 0.412973 21.11 14.49 0.00757110 40444.4 40.00 21.18 0.00800000 60796.0 0.08375133 60.00 32.22 27.78 0.000 9574.27 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00757110 21.11 0.00757110 48.6242 9574.40 0.00 10321.28 10321.28 0.49705278 16.60 12.73 0.00757110 35848.8 36.98 19.95 0.00757110 56613.8
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 12511.644 12511.644 1.140420 0.00010946 276.442 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 2.5042 2.554638 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 12511.64 12511.64 1.0000 1.37260350 1.140420 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.10944616 60.00 32.22 27.78 0.000 12511.64 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00765805 21.00 0.00765805 49.5110 6497.27 0.00 12579.76 12579.76 1.37260350 16.60 13.15 0.00800000 36934.7 25.59 16.52 0.00800000 46099.6
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 12938.464 12938.464 1.194813 0.00011319 285.444 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 2.5897 2.641786 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 Sensible 12938.46 12938.46 1.0000 1.43807090 1.194813 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.11317978 60.00 32.22 27.78 0.000 12938.46 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00766490 21.00 0.00766490 49.5551 6637.33 0.00 13008.95 13008.95 1.43807090 16.60 13.15 0.00800000 36934.7 25.47 16.48 0.00800000 45980.8
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 8587.675 8587.675 1.180501 0.00007513 182.671 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.7188 1.753439 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 8587.68 8587.68 1.0000 1.42084493 1.180501 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.07512107 60.00 32.22 27.78 0.000 8587.68 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.57 0.00662023 21.00 0.00662023 42.8799 2378.04 0.00 8635.61 8635.61 1.42084493 16.60 13.15 0.00800000 36934.7 22.56 15.43 0.00800000 43012.5
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 8877.748 8877.748 0.411591 0.00007767 221.214 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 1.7769 1.812666 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 Sensible 8877.75 8877.75 1.0000 0.49538914 0.411591 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.07765849 60.00 32.22 27.78 0.000 8877.75 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00770743 21.00 0.00770743 49.8261 6706.85 0.00 8923.56 8923.56 0.49538914 16.60 13.15 0.00800000 36934.7 34.27 19.43 0.00800000 54948.0
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 713237.720 -999.000 22.370713 0.02547520 -999.000 -999.0000 1.00000 1.00000 1027.1202 1004.8586 1.2036 VAV WITH REHEAT FAN Fan:VariableVolume 22.370713 26.92527800   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 68.7206 68.720615 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 Sensible 713237.72 467906.38 1.0000 26.92527800 22.370713 28.22 20.53 0.01198539 58961.8 10.99 10.99 0.00850000 32472.3 25.47260004 6.70 13.37 6.67 50124.683 663113.04 32.10 0.01411964 23.13 11.66146000 52.1282 23.99 0.00965612 23.99 0.00961913 51.6874 307213.80 0.00 714044.88 462437.88 26.92527800 28.22 20.54 0.01198539 58961.8 11.50 11.33 0.00828061 32442.3
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 222401.116 222401.116 6.711214 0.00194566 3670.815 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV WITH REHEAT FAN Fan:VariableVolume 22.370713 26.92527800   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 44.5142 45.410041 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 222401.12 222401.12 1.0000 8.07758340 6.711214 -10.70 -10.70 0.00150390 -7020.5 16.70 13.18 0.00800000 37036.7 1.94546351 60.00 32.22 27.78 0.000 222401.12 -10.70 0.00150390 -10.70 11.66146000 173.7608 18.55 0.00681610 21.07 0.00649056 41.8720 67312.46 0.00 190559.29 190559.29 8.07758340 2.80 -1.97 0.00150390 6582.5 26.21 10.51 0.00150390 30173.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 86334.709 -999.000 2.051317 0.00308368 -999.000 -999.0000 1.00000 1.00000 1031.0877 1004.8586 1.2036 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46886833   4197.9300 999.8980 37.06689783 13.37 6.70 6.67 1037880.30 8.3184 8.318369 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 86334.71 51162.86 1.0000 2.46895513 2.051317 32.10 23.13 0.01411964 68410.3 11.94 11.74 0.00850000 33442.2 3.08336118 6.70 13.37 6.67 2195.006 84139.70 32.10 0.01411964 23.13 2.05124512 99.9965 21.11 0.00869284 21.11 0.00868931 55.7063 200417.98 0.00 86433.83 51479.65 2.46895513 32.10 23.14 0.01411964 68410.3 11.88 11.73 0.00850831 33402.0
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 20393.415 20393.415 0.615395 0.00017841 336.601 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46886833   4197.9300 999.8980 4.28421440 54.44 82.22 27.78 499618.64 4.0818 4.163944 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 20393.42 20393.42 1.0000 0.74068654 0.615395 -10.70 -10.70 0.00150390 -7020.5 16.70 13.18 0.00800000 37036.7 0.17839229 60.00 32.22 27.78 0.000 20393.42 -10.70 0.00150390 -10.70 2.05124512 333.3216 21.11 0.00751304 21.11 0.00751532 48.2694 117888.37 0.00 17473.63 17473.63 0.74068654 2.80 -1.97 0.00150390 6582.5 26.21 10.51 0.00150390 30173.7



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 11.66 22.37 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 692.33 6596.83 0.00
RETAIL_1_FLR_1 2635.00 6537.00 1147.00
RETAIL_2_FLR_1 1862.00 6106.00 179.83
MECH_FLR_1 1485.67 6967.50 790.67
STORAGE_FLR_1 1170.00 7659.33 966.50
LAUNDRY_FLR_1 7194.33 3377.00 2737.67
CAFE_FLR_1 3476.50 5695.33 1158.67
LOBBY_FLR_1 2770.50 5861.33 902.67
ROOM_1_FLR_3 3156.33 7583.33 2541.50
ROOM_2_FLR_3 3561.50 7792.33 3097.17
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 2202.17 8702.67 2186.67
ROOM_5_FLR_3 2979.50 7599.17 2502.67
ROOM_6_FLR_3 3316.00 7819.67 3040.67
CORRIDOR_FLR_3 861.50 7236.17 659.83
ROOM_1_FLR_6 3847.50 7588.00 3137.50
ROOM_2_FLR_6 4139.33 7753.50 3598.00
ROOM_3_MULT9_FLR_6 2345.67 7621.00 1870.33
BANQUET_FLR_6 4448.83 3335.50 874.50
DINING_FLR_6 5144.33 2268.33 778.50
KITCHEN_FLR_6 8187.67 6495.67 6282.00
CORRIDOR_FLR_6 1904.17 6715.67 681.83
Facility 8757.00 8760.00 8107.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 152.67 0.00 152.67
CAFE_FLR_1 0.00 0.17 0.00 0.17
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 2.50 20.33 2.50 20.33
ROOM_2_FLR_3 5.17 13.00 5.17 13.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8.83 17.67 8.83 17.67
ROOM_5_FLR_3 2.83 31.17 2.83 31.17
ROOM_6_FLR_3 6.17 27.33 6.17 27.33
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 2.50 25.50 2.50 25.50
ROOM_2_FLR_6 5.17 18.67 5.17 18.67
ROOM_3_MULT9_FLR_6 1.33 22.67 1.33 22.67
BANQUET_FLR_6 0.00 12.00 0.00 12.00
DINING_FLR_6 0.00 18.33 0.00 18.33
KITCHEN_FLR_6 0.00 303.67 0.00 303.67
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 11.67 410.50 11.67 410.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.999 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.611 0.137 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.382 0.046 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.507 0.051 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.574 0.051 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 21.302 0.147 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 3.794 0.108 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.678 0.045 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.473 0.178 0.000 0.058
ROOM_2_FLR_3 0.95 1.50 118.93 0.473 0.178 0.000 0.060
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.079 0.000 0.103
ROOM_5_FLR_3 0.95 1.50 118.94 0.473 0.178 0.000 0.069
ROOM_6_FLR_3 0.95 1.50 118.93 0.473 0.178 0.000 0.066
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.584 0.022 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.473 0.178 0.000 0.063
ROOM_2_FLR_6 0.95 1.50 118.93 0.473 0.178 0.000 0.066
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.145 0.000 0.131
BANQUET_FLR_6 144.99 249.90 1010.89 4.498 0.052 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 4.854 0.052 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 20.179 0.148 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.108 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.611 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.524 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.819 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.302 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.344 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 12.107 0.002 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.270 0.002 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.079 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.453 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.452 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.514 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.454 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.452 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.350 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.453 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.452 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.516 0.002 0.000 0.000
BANQUET_FLR_6 144.99 249.90 1010.89 2.819 0.001 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 2.964 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 8.424 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.658 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.79 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.56 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.09 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.25 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 41476641.23 0.00 41476641.23 0.00 41476641.23 26946214.98 1.61 1.12 8757.26 0.00
RETAIL_1_FLR_1 5996072.66 0.00 5996072.66 315162.19 6311234.84 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3665842.63 0.00 3665842.63 121653.00 3787495.63 2892943.94 102.86 22.13 8635.01 0.00
MECH_FLR_1 2849331.01 0.00 2849331.01 287515.42 3136846.43 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1864506.28 0.00 1864506.28 165880.56 2030386.85 1821682.01 2553.74 516.64 5689.62 0.00
LAUNDRY_FLR_1 56740545.59 0.00 56740545.59 392587.63 57133133.21 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 24440180.12 0.00 24440180.12 696683.85 25136863.98 21330615.53 893.80 175.01 7691.19 0.00
LOBBY_FLR_1 74815609.44 0.00 74815609.44 1990584.90 76806194.34 59728886.00 109.18 39.83 8610.98 0.00
ROOM_1_FLR_3 1946875.62 58853.64 2005729.26 182929.66 2188658.92 1946875.62 0.00 8007.41 752.59 0.00
ROOM_2_FLR_3 1946647.51 60568.23 2007215.74 182915.70 2190131.45 1946647.51 0.00 7966.38 793.62 0.00
ROOM_3_MULT19_FLR_3 26397887.27 70045.85 26467933.12 51039.43 26518972.55 26397887.27 0.00 7879.11 880.89 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 66286.61 26471392.34 51053.38 26522445.73 26405105.73 0.00 7882.81 877.19 0.00
ROOM_5_FLR_3 1946875.62 69777.05 2016652.67 182929.66 2199582.33 1946875.62 0.00 7889.42 870.58 0.00
ROOM_6_FLR_3 1946647.51 67287.48 2013935.00 182915.70 2196850.70 1946647.51 0.00 7888.03 871.97 0.00
CORRIDOR_FLR_3 23937903.20 0.00 23937903.20 221198.76 24159101.96 14972100.18 0.81 0.46 8758.74 0.00
ROOM_1_FLR_6 486718.90 64374.50 551093.40 182967.83 734061.23 486718.90 0.00 8061.66 698.34 0.00
ROOM_2_FLR_6 486661.88 67311.30 553973.18 182953.87 736927.05 486661.88 0.00 8016.18 743.82 0.00
ROOM_3_MULT9_FLR_6 3126920.42 83697.64 3210618.06 93612.75 3304230.80 3126920.42 0.00 7872.30 887.70 0.00
BANQUET_FLR_6 38982877.08 0.00 38982877.08 446761.45 39429638.53 37458366.31 4726.34 338.46 3695.20 0.00
DINING_FLR_6 42056572.22 0.00 42056572.22 446761.45 42503333.67 37458366.31 2710.99 815.72 5233.29 0.00
KITCHEN_FLR_6 54480403.72 0.00 54480403.72 399955.08 54880358.80 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12028966.47 0.00 12028966.47 391453.71 12420420.19 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 12272177.65 0.45E+10 18434047.20 0.46E+10 0.43E+10 6239.52 8207.83 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.3152 0.0000 1.3152 0.0000 1.3152 0.8545 1.61 1.12 8757.26
RETAIL_1_FLR_1 0.1901 0.0000 0.1901 0.0100 0.2001 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1162 0.0000 0.1162 0.0039 0.1201 0.0917 102.86 22.13 8635.01
MECH_FLR_1 0.0904 0.0000 0.0904 0.0091 0.0995 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0591 0.0000 0.0591 0.0053 0.0644 0.0578 2553.74 516.64 5689.62
LAUNDRY_FLR_1 1.7992 0.0000 1.7992 0.0124 1.8117 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7750 0.0000 0.7750 0.0221 0.7971 0.6764 893.80 175.01 7691.19
LOBBY_FLR_1 2.3724 0.0000 2.3724 0.0631 2.4355 1.8940 109.18 39.83 8610.98
ROOM_1_FLR_3 0.0617 0.0019 0.0636 0.0058 0.0694 0.0617 0.00 8007.41 752.59
ROOM_2_FLR_3 0.0617 0.0019 0.0636 0.0058 0.0694 0.0617 0.00 7966.38 793.62
ROOM_4_MULT19_FLR_3 0.8373 0.0021 0.8394 0.0016 0.8410 0.8373 0.00 7882.81 877.19
ROOM_5_FLR_3 0.0617 0.0022 0.0639 0.0058 0.0697 0.0617 0.00 7889.42 870.58
ROOM_6_FLR_3 0.0617 0.0021 0.0639 0.0058 0.0697 0.0617 0.00 7888.03 871.97
CORRIDOR_FLR_3 0.7591 0.0000 0.7591 0.0070 0.7661 0.4748 0.81 0.46 8758.74
ROOM_1_FLR_6 0.0154 0.0020 0.0175 0.0058 0.0233 0.0154 0.00 8061.66 698.34
ROOM_2_FLR_6 0.0154 0.0021 0.0176 0.0058 0.0234 0.0154 0.00 8016.18 743.82
ROOM_3_MULT9_FLR_6 0.0992 0.0027 0.1018 0.0030 0.1048 0.0992 0.00 7872.30 887.70
BANQUET_FLR_6 1.2361 0.0000 1.2361 0.0142 1.2503 1.1878 4726.34 338.46 3695.20
DINING_FLR_6 1.3336 0.0000 1.3336 0.0142 1.3478 1.1878 2710.99 815.72 5233.29
KITCHEN_FLR_6 1.7276 0.0000 1.7276 0.0127 1.7402 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3814 0.0000 0.3814 0.0124 0.3938 0.1256 0.00 0.00 8760.00
Total Facility 79.9785 0.2203 80.1988 0.4615 80.6603 73.9670 6239.52 8207.83 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.56E+09 0.00 0.56E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 93713071.71 608202.31 94321274.02 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.6095 0.0000 17.6095 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9716 0.0193 2.9909 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 5964.62 2548.13 0.00 247.25 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 7345.66 1414.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.8950 19.3581 0.0000 16.8952 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9719 2.9723 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1333
Defaulted Fields 1181
Fields with Defaults 4001
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
Electricity:Building 2532.59 31781.30 03-JUN-05:00 158241.73 02-JAN-20:10
Electricity:Zone:BASEMENT 332.05 3744.83 02-JAN-02:10 25084.28 02-JAN-20:10
Electricity:SpaceType:GENERAL 2525.50 31640.15 03-JUN-05:00 158000.40 02-JAN-20:10
InteriorLights:Electricity 867.32 7438.18 03-JUN-05:00 71560.59 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 188.95 1716.93 02-JAN-02:10 15451.75 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 867.32 7438.18 03-JUN-05:00 71560.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity 867.32 7438.18 03-JUN-05:00 71560.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 188.95 1716.93 02-JAN-02:10 15451.75 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 867.32 7438.18 03-JUN-05:00 71560.59 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.95 223.93 02-JAN-02:10 1401.96 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.76 79.59 02-JAN-02:10 716.35 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.76 79.59 02-JAN-02:10 716.35 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.94 259.31 02-JAN-02:10 1623.47 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 10.14 92.17 02-JAN-02:10 829.54 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 10.14 92.17 02-JAN-02:10 829.54 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.64 250.98 02-JAN-02:10 1507.71 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.17 74.25 02-JAN-02:10 668.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.17 74.25 02-JAN-02:10 668.27 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 7.74 88.65 02-JAN-02:10 581.19 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 4.15 37.67 02-JAN-02:10 339.04 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 4.15 37.67 02-JAN-02:10 339.04 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 73.48 1013.10 02-JAN-02:10 5026.41 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 5.55 50.40 02-JAN-02:10 453.60 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 5.55 50.40 02-JAN-02:10 453.60 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 30.51 307.62 20-MAY-05:00 2922.95 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 16.17 95.71 01-JAN-13:10 1957.67 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 16.17 95.71 01-JAN-13:10 1957.67 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 247.86 2995.36 20-MAY-05:00 18583.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 98.86 883.95 20-MAY-05:00 8554.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 98.86 883.95 20-MAY-05:00 8554.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 21.40 271.61 01-JAN-02:10 1567.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 21.40 271.58 01-JAN-02:10 1567.69 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 325.45 4437.75 01-JAN-02:10 23570.01 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 130.46 1104.51 01-JAN-02:10 10040.97 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 130.46 1104.51 01-JAN-02:10 10040.97 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 325.54 4438.96 01-JAN-02:10 23576.46 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 130.49 1104.81 01-JAN-02:10 10043.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 130.49 1104.81 01-JAN-02:10 10043.72 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 21.40 271.61 01-JAN-02:10 1567.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 21.40 271.58 01-JAN-02:10 1567.69 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 5.35 67.90 01-JAN-02:10 391.97 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.73 23.12 01-JAN-02:10 210.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.73 23.12 01-JAN-02:10 210.22 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 5.35 67.89 01-JAN-02:10 391.92 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.73 23.12 01-JAN-02:10 210.20 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.73 23.12 01-JAN-02:10 210.20 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 38.55 525.67 01-JAN-02:10 2791.95 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 15.45 130.83 01-JAN-02:10 1189.39 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 15.45 130.83 01-JAN-02:10 1189.39 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 211.21 2478.49 03-JUN-05:00 10185.74 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 35.35 229.19 03-JUN-05:00 3437.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 35.35 229.19 03-JUN-05:00 3437.84 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 211.21 2478.49 03-JUN-05:00 10185.74 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 35.35 229.19 03-JUN-05:00 3437.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 35.35 229.19 03-JUN-05:00 3437.84 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 455.64 6266.47 02-JAN-02:10 18984.42 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 14.81 134.55 02-JAN-02:10 1210.92 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 14.81 134.55 02-JAN-02:10 1210.92 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorEquipment:Electricity 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.08 1114.64 06-FEB-23:30 3421.03 27-OCT-07:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 1444.75 2597.68 12-APR-01:20 211690.01 16-AUG-15:20
LowTempRefrigeration:Refrigeration:Electricity 20.48 0.00 01-JAN-11:10 2032.30 13-JAN-11:40
MedTempRefrigeration:Refrigeration:Electricity 34.50 938.05 06-FEB-04:10 1245.48 04-DEC-08:00
Fans:Electricity 564.57 12709.15 10-OCT-04:20 44381.45 01-SEP-20:10
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 819.67 14138.38 22-OCT-01:40 56167.83 01-SEP-20:10
ExteriorEquipment:Electricity 650.09 9607.53 02-JAN-02:20 39721.54 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 31.07 542.63 03-JUN-05:00 1847.44 12-JAN-21:10
ElectricityPurchased:Facility 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
ElectricityPurchased:Plant 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
Cogeneration:ElectricityPurchased 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
General:Cogeneration:ElectricityPurchased 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
ElectricityNet:Plant 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
Cogeneration:ElectricityNet 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
General:Cogeneration:ElectricityNet 5678.10 77503.94 01-NOV-02:30 458577.10 04-AUG-19:10
General:Fans:Electricity 564.57 12709.15 10-OCT-04:20 44381.45 01-SEP-20:10
ExteriorLights:Electricity 262.05 0.00 01-JAN-07:30 16690.39 01-JAN-00:10
General:ExteriorLights:Electricity 262.05 0.00 01-JAN-07:30 16690.39 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 224.04 0.00 02-MAR-15:40 9938.94 03-JAN-19:40
General:HeatRecovery:Electricity 224.04 0.00 02-MAR-15:40 9938.94 03-JAN-19:40
WaterSystems:Electricity 90.75 1086.56 17-AUG-00:20 4738.70 15-FEB-19:10
Water Heater:WaterSystems:Electricity 90.75 1086.56 17-AUG-00:20 4738.70 15-FEB-19:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1191.16 0.00 01-JAN-00:10 202267.42 16-AUG-15:20
General:Cooling:Electricity 1191.16 0.00 01-JAN-00:10 202267.42 16-AUG-15:20
Pumps:Electricity 107.86 47.91 13-APR-10:20 5899.36 16-AUG-18:10
General:Pumps:Electricity 107.86 47.91 13-APR-10:20 5899.36 16-AUG-18:10
WIRED_LTG_ELECTRICITY 30.53 0.00 01-JAN-00:10 2518.93 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5713.35 31829.34 07-APR-01:10 547081.94 14-JAN-17:30
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3924.51 18467.44 10-SEP-15:40 496906.07 05-FEB-23:50
WaterSystems:NaturalGas 3178.71 18467.44 09-JAN-13:10 291395.33 09-FEB-21:30
Water Heater:WaterSystems:NaturalGas 3178.71 18467.44 09-JAN-13:10 291395.33 09-FEB-21:30
Heating:NaturalGas 745.80 0.00 02-MAR-19:20 238365.65 02-JAN-09:10
Boiler:Heating:NaturalGas 745.80 0.00 02-MAR-19:20 238365.65 02-JAN-09:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 3822.44 0.00 01-JAN-00:10 663233.24 11-AUG-22:00
PlantLoopCoolingDemand:HVAC 3822.44 0.00 01-JAN-00:10 663233.24 11-AUG-22:00
CoolingCoils:PlantLoopCoolingDemand 3822.44 0.00 01-JAN-00:10 663233.24 11-AUG-22:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 04-MAR-02:20 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 04-MAR-02:20 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 18-JAN-07:20
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 18-JAN-07:20


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 23485.67 143877.77 07-MAY-13:50 2745715.40 16-AUG-15:20
EnergyTransfer:Building 5298.16 50846.26 16-FEB-15:20 356829.75 19-JUN-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 721.00 8164.92 18-OCT-02:10 36803.17 09-JUL-10:40
Refrigeration:EnergyTransfer 184.06 4010.21 06-FEB-04:00 10613.31 27-OCT-07:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.03 2005.11 06-FEB-04:00 5306.65 27-OCT-07:20
General:Refrigeration:EnergyTransfer 92.03 2005.11 06-FEB-04:00 5306.65 27-OCT-07:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.03 2005.11 06-FEB-04:00 5306.65 27-OCT-07:20
EnergyTransfer:Plant 10365.20 15047.76 02-NOV-01:20 1549172.69 11-AUG-22:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.63 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.40 1764.16 06-FEB-04:10 2686.44 04-DEC-08:00
EnergyTransfer:Zone:BASEMENT 436.43 1817.23 27-MAR-03:10 28524.06 28-NOV-22:00
Heating:EnergyTransfer 168.10 0.00 03-JAN-18:40 97853.85 14-JAN-16:20
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 412.23 15-MAY-01:50
General:Heating:EnergyTransfer 168.10 0.00 03-JAN-18:40 97853.85 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 412.23 15-MAY-01:50
Cooling:EnergyTransfer 5038.03 45074.05 16-FEB-15:20 353207.15 19-JUN-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 436.42 1817.23 27-MAR-03:10 28524.06 28-NOV-22:00
General:Cooling:EnergyTransfer 5038.03 45074.05 16-FEB-15:20 353207.15 19-JUN-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 436.42 1817.23 27-MAR-03:10 28524.06 28-NOV-22:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 43.33 0.10 15-NOV-03:50 4480.61 04-OCT-12:10
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 1.26 0.00 01-JAN-08:30 1365.11 02-JAN-07:20
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 1.26 0.00 01-JAN-08:30 1365.11 02-JAN-07:20
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 42.07 0.00 01-JAN-00:10 4480.61 04-OCT-12:10
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 42.07 0.00 01-JAN-00:10 4480.61 04-OCT-12:10
EnergyTransfer:Zone:RETAIL_2_FLR_1 35.59 72.10 13-JAN-11:30 2236.87 04-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 101.32 25-DEC-06:30
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 101.32 25-DEC-06:30
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 35.59 11.23 16-FEB-15:20 2236.87 04-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 35.59 11.23 16-FEB-15:20 2236.87 04-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 22.55 0.03 30-DEC-14:20 1809.89 17-AUG-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.40 0.00 01-JAN-20:10 634.57 02-JAN-05:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.40 0.00 01-JAN-20:10 634.57 02-JAN-05:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 22.15 0.00 01-JAN-00:10 1809.89 17-AUG-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 22.15 0.00 01-JAN-00:10 1809.89 17-AUG-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 13.36 0.01 20-NOV-03:20 906.34 04-AUG-21:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.72 0.00 03-JAN-18:30 572.06 02-JAN-05:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.72 0.00 03-JAN-18:30 572.06 02-JAN-05:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 12.64 0.00 01-JAN-00:10 906.34 04-AUG-21:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 12.64 0.00 01-JAN-00:10 906.34 04-AUG-21:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 594.86 5602.29 27-MAR-03:10 39069.07 04-AUG-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 415.83 07-OCT-03:40
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 415.83 07-OCT-03:40
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 594.86 5602.29 27-MAR-03:10 39069.07 04-AUG-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 594.86 5602.29 27-MAR-03:10 39069.07 04-AUG-20:00
EnergyTransfer:Zone:CAFE_FLR_1 235.59 5.96 14-JAN-12:30 15168.96 30-SEP-12:40
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.04 0.00 01-JAN-00:10 713.75 13-NOV-09:50
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.04 0.00 01-JAN-00:10 713.75 13-NOV-09:50
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 235.55 0.00 08-JAN-13:50 15168.96 30-SEP-12:40
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 235.55 0.00 08-JAN-13:50 15168.96 30-SEP-12:40
EnergyTransfer:Zone:LOBBY_FLR_1 764.74 1305.53 13-JAN-11:30 42299.28 04-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.02 0.00 01-JAN-00:10 1330.36 13-NOV-09:50
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.02 0.00 01-JAN-00:10 1330.36 13-NOV-09:50
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 764.72 513.16 16-FEB-15:20 42299.28 04-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 764.72 513.16 16-FEB-15:20 42299.28 04-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 66.91 0.17 17-APR-21:20 13309.51 21-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 17.37 0.00 01-JAN-08:10 6540.24 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 17.37 0.00 01-JAN-08:10 6540.24 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 49.55 0.00 01-JAN-00:10 13309.51 21-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 49.55 0.00 01-JAN-00:10 13309.51 21-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 64.33 0.18 23-JAN-15:50 12177.19 02-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 21.98 0.00 01-JAN-08:10 6608.61 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 21.98 0.00 01-JAN-08:10 6608.61 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 42.35 0.00 01-JAN-00:10 12177.19 02-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 42.35 0.00 01-JAN-00:10 12177.19 02-AUG-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 422.20 5.78 27-FEB-02:40 59539.24 04-OCT-12:00
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 8.41 0.00 01-JAN-08:10 18135.39 02-JAN-05:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 8.41 0.00 01-JAN-08:10 18135.39 02-JAN-05:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 413.79 0.00 01-JAN-00:10 59539.24 04-OCT-12:00
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 413.79 0.00 01-JAN-00:10 59539.24 04-OCT-12:00
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 421.33 1.21 19-JAN-09:50 72430.35 26-JUN-18:30
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 48.04 0.00 01-JAN-08:10 36017.32 02-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 48.04 0.00 01-JAN-08:10 36017.32 02-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 373.30 0.00 01-JAN-00:10 72430.35 26-JUN-18:30
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 373.30 0.00 01-JAN-00:10 72430.35 26-JUN-18:30
EnergyTransfer:Zone:ROOM_5_FLR_3 66.76 0.12 09-MAY-00:40 13271.02 10-SEP-09:00
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 17.18 0.00 01-JAN-08:10 6481.55 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 17.18 0.00 01-JAN-08:10 6481.55 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 49.58 0.00 01-JAN-00:10 13271.02 10-SEP-09:00
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 49.58 0.00 01-JAN-00:10 13271.02 10-SEP-09:00
EnergyTransfer:Zone:ROOM_6_FLR_3 63.47 0.05 31-OCT-09:40 12705.63 29-MAY-09:00
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 21.49 0.00 01-JAN-08:10 6471.61 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 21.49 0.00 01-JAN-08:10 6471.61 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 41.98 0.00 01-JAN-00:10 12705.63 29-MAY-09:00
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 41.98 0.00 01-JAN-00:10 12705.63 29-MAY-09:00
EnergyTransfer:Zone:CORRIDOR_FLR_3 186.14 0.41 23-DEC-13:10 11000.79 06-SEP-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.97 0.00 01-JAN-07:40 3531.26 14-JAN-16:50
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.97 0.00 01-JAN-07:40 3531.26 14-JAN-16:50
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 185.17 0.00 01-JAN-00:10 11000.79 06-SEP-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 185.17 0.00 01-JAN-00:10 11000.79 06-SEP-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 18.97 0.07 15-MAR-09:30 3508.94 21-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.37 0.00 01-JAN-08:10 1957.69 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.37 0.00 01-JAN-08:10 1957.69 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.61 0.00 01-JAN-00:10 3508.94 21-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.61 0.00 01-JAN-00:10 3508.94 21-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 18.55 0.01 10-MAR-09:00 3277.18 02-AUG-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 7.83 0.00 01-JAN-11:10 1952.99 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 7.83 0.00 01-JAN-11:10 1952.99 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 10.72 0.00 01-JAN-00:10 3277.18 02-AUG-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 10.72 0.00 01-JAN-00:10 3277.18 02-AUG-15:20
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 97.20 0.46 30-JAN-19:40 16810.32 04-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 15.06 0.00 01-JAN-08:10 9137.58 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 15.06 0.00 01-JAN-08:10 9137.58 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 82.14 0.00 01-JAN-00:10 16810.32 04-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 82.14 0.00 01-JAN-00:10 16810.32 04-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 436.18 2661.73 03-DEC-15:40 23894.39 04-AUG-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 436.18 2661.73 03-DEC-15:40 23894.39 04-AUG-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 436.18 2661.73 03-DEC-15:40 23894.39 04-AUG-21:20
EnergyTransfer:Zone:DINING_FLR_6 476.15 3614.35 03-DEC-15:40 25104.44 04-AUG-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 476.15 3614.35 03-DEC-15:40 25104.44 04-AUG-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 476.15 3614.35 03-DEC-15:40 25104.44 04-AUG-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 628.97 5964.05 18-OCT-02:10 31712.72 09-JUL-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 628.97 5964.05 18-OCT-02:10 31712.72 09-JUL-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 92.50 0.08 10-DEC-14:40 7071.84 16-AUG-12:50
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.96 0.00 01-JAN-09:00 2472.85 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.96 0.00 01-JAN-09:00 2472.85 02-JAN-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 91.55 0.00 01-JAN-00:10 7071.84 16-AUG-12:50
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 91.55 0.00 01-JAN-00:10 7071.84 16-AUG-12:50
PlantLoopHeatingDemand:Facility 1265.47 8506.14 14-AUG-01:20 247942.47 06-FEB-07:10
PlantLoopHeatingDemand:Plant 742.72 8506.14 14-AUG-01:20 56499.56 09-FEB-07:10
WaterSystems:PlantLoopHeatingDemand 742.72 8506.14 14-AUG-01:20 56499.56 09-FEB-07:10
General:WaterSystems:PlantLoopHeatingDemand 742.72 8506.14 14-AUG-01:20 56499.56 09-FEB-07:10
EnergyTransfer:HVAC 7822.31 15.10 20-MAY-07:40 891370.76 16-AUG-15:20
HeatingCoils:EnergyTransfer 522.75 0.00 02-MAR-19:20 196648.75 14-JAN-16:10
PlantLoopHeatingDemand:HVAC 522.75 0.00 02-MAR-19:20 196648.75 14-JAN-16:10
HeatingCoils:PlantLoopHeatingDemand 522.75 0.00 02-MAR-19:20 196648.75 14-JAN-16:10
CoolingCoils:EnergyTransfer 3822.44 0.00 01-JAN-00:10 663233.24 11-AUG-22:00
HeatRecoveryForHeating:EnergyTransfer 2931.10 0.00 02-MAR-15:40 487628.62 06-FEB-03:00
HeatRecoveryForCooling:EnergyTransfer 546.02 0.00 01-JAN-00:10 279166.78 08-JUL-12:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 742.72 8506.14 14-AUG-01:20 56499.56 09-FEB-07:10
WaterUse:WaterSystems:EnergyTransfer 742.72 8506.14 14-AUG-01:20 56499.56 09-FEB-07:10
Boilers:EnergyTransfer 517.66 0.00 02-MAR-19:20 193467.74 14-JAN-16:20
Chillers:EnergyTransfer 3910.81 0.00 01-JAN-00:10 674452.73 11-AUG-22:00
HeatRejection:EnergyTransfer 5101.97 0.00 01-JAN-00:10 852163.38 16-AUG-15:20
General:HeatRejection:EnergyTransfer 5101.97 0.00 01-JAN-00:10 852163.38 16-AUG-15:20



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.003 -436.425 0.000 0.000 139.420 188.948 143.105 0.000 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -35.051
RETAIL_1_FLR_1 0.000 0.000 1.259 -42.067 0.000 0.000 15.468 8.760 10.186 27.070 0.000 0.175 0.000 0.000 -10.730 0.000 -3.938 -6.182
RETAIL_2_FLR_1 0.000 0.000 0.005 -35.589 0.000 0.000 16.946 10.144 11.795 0.000 0.000 0.064 0.000 0.000 0.000 0.000 -1.621 -1.743
MECH_FLR_1 0.000 0.000 0.397 -22.149 0.000 0.000 3.709 8.172 12.471 0.000 0.000 0.150 0.897 0.000 0.000 0.000 -3.648 -0.000
STORAGE_FLR_1 0.000 0.000 0.717 -12.639 0.000 0.000 2.890 4.146 3.598 0.000 0.000 0.093 3.265 0.000 0.000 0.000 -2.069 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.004 -594.860 0.000 0.000 11.225 5.547 658.131 0.000 0.000 0.251 0.000 0.000 0.000 0.000 -5.465 -74.832
CAFE_FLR_1 0.000 0.000 0.038 -235.557 0.000 0.000 192.008 16.167 14.341 75.170 0.000 0.359 0.000 0.000 -32.309 0.000 -9.334 -20.882
LOBBY_FLR_1 0.000 0.000 0.025 -764.724 0.000 0.000 557.791 98.863 148.998 99.685 0.000 1.038 0.000 0.000 -43.774 0.000 -27.369 -70.534
ROOM_1_FLR_3 21.548 -36.854 0.000 -16.872 0.000 0.000 9.552 10.925 10.478 51.122 0.000 0.609 0.000 0.000 -24.478 0.000 -10.161 -15.869
ROOM_2_FLR_3 26.616 -30.473 0.000 -16.516 0.000 0.000 9.594 10.924 10.477 36.521 0.000 0.610 0.000 0.000 -25.177 0.000 -10.017 -12.558
ROOM_3_MULT19_FLR_3 14.298 -175.813 0.000 -243.860 0.000 0.000 0.000 130.455 194.997 324.859 0.000 2.333 0.002 0.000 -135.578 0.000 -70.805 -40.886
ROOM_4_MULT19_FLR_3 90.066 -195.594 0.000 -219.715 0.000 0.000 183.634 130.491 195.050 100.456 0.000 3.826 0.000 0.000 -140.739 0.000 -63.219 -84.255
ROOM_5_FLR_3 21.289 -36.827 0.000 -16.857 0.000 0.000 9.575 10.925 10.478 50.683 0.000 0.607 0.000 0.000 -24.080 0.000 -10.290 -15.503
ROOM_6_FLR_3 26.114 -30.071 0.000 -16.524 0.000 0.000 9.614 10.924 10.477 35.740 0.000 0.607 0.000 0.000 -24.460 0.000 -10.055 -12.366
CORRIDOR_FLR_3 0.000 0.000 0.972 -185.170 0.000 0.000 117.830 91.336 0.000 47.317 0.000 0.468 0.000 0.000 -31.537 0.000 -11.203 -30.014
ROOM_1_FLR_6 7.508 -9.543 0.000 -4.207 0.000 0.000 2.387 2.731 2.620 12.678 0.000 0.151 0.000 0.000 -6.109 0.000 -2.561 -5.655
ROOM_2_FLR_6 9.100 -7.870 0.000 -4.118 0.000 0.000 2.398 2.731 2.619 9.060 0.000 0.151 0.000 0.000 -6.277 0.000 -2.530 -5.264
ROOM_3_MULT9_FLR_6 20.463 -60.195 0.000 -27.346 0.000 0.000 21.508 15.453 23.098 70.230 0.000 0.724 0.000 0.000 -28.623 0.000 -13.711 -21.600
BANQUET_FLR_6 0.000 0.000 0.000 -436.182 0.000 0.000 317.093 35.351 175.857 9.926 0.000 0.198 0.000 0.000 -19.892 0.000 -6.541 -75.810
DINING_FLR_6 0.000 0.000 0.000 -476.159 0.000 0.000 315.704 35.351 175.857 9.705 0.000 0.197 0.000 0.000 -20.502 0.000 -6.603 -33.550
KITCHEN_FLR_6 0.000 0.000 0.000 -628.958 0.000 0.000 28.299 14.807 550.372 22.934 0.000 0.175 32.268 0.000 -13.955 0.000 -5.943 -0.000
CORRIDOR_FLR_6 0.000 0.000 0.958 -91.545 0.000 0.000 31.238 24.166 0.000 22.987 0.000 0.185 31.198 0.000 -14.217 0.000 -4.969 -0.001
Total Facility 237.001 -583.241 4.377 -4528.038 0.000 0.000 1997.881 867.318 2365.005 1006.142 0.000 12.972 67.637 0.000 -602.439 0.000 -282.052 -562.556


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 04-DEC-07:51 0.00 0.00 0.00 -50176.84 0.00 0.00 2852.24 8584.24 6083.70 0.00 0.00 0.00 32656.66 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 03-DEC-12:49 0.00 0.00 0.00 -5631.14 0.00 0.00 225.86 238.78 288.68 6547.91 0.00 0.00 0.00 0.00 -0.00 0.00 -196.45 -1473.64
RETAIL_2_FLR_1 30-OCT-23:56 0.00 0.00 0.00 -2271.57 0.00 0.00 816.16 184.34 250.72 0.00 0.00 0.00 1098.55 0.00 -0.00 0.00 -78.20 0.00
MECH_FLR_1 17-AUG-20:00 0.00 0.00 0.00 -1809.82 0.00 0.00 129.09 668.27 839.45 0.00 0.00 51.44 121.58 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 11-APR-06:16 0.00 0.00 0.00 -1060.61 0.00 0.00 64.57 188.35 152.94 0.00 0.00 0.00 756.02 0.00 -0.00 0.00 -101.27 0.00
LAUNDRY_FLR_1 24-MAR-20:49 0.00 0.00 0.00 -51510.58 0.00 0.00 441.64 403.20 41967.83 0.00 0.00 0.00 9003.94 0.00 -0.00 0.00 -306.04 0.00
CAFE_FLR_1 03-DEC-12:49 0.00 0.00 0.00 -22895.23 0.00 0.00 2967.70 143.56 406.43 18346.55 0.00 0.00 1465.49 0.00 -0.00 0.00 -434.51 0.00
LOBBY_FLR_1 27-OCT-23:02 0.00 0.00 0.00 -82031.02 0.00 0.00 25811.17 1900.96 3167.12 0.00 0.00 0.00 55603.76 0.00 -3151.78 0.00 -1300.21 0.00
ROOM_1_FLR_3 04-JUN-21:51 0.00 -14969.33 0.00 -740.07 0.00 0.00 293.95 714.76 358.22 0.00 0.00 0.00 15634.68 0.00 -1089.07 0.00 -203.15 0.00
ROOM_2_FLR_3 29-MAY-18:31 0.00 -14202.17 0.00 -899.04 0.00 0.00 244.75 840.80 484.60 2635.47 0.00 3.46 10892.12 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 04-OCT-12:00 0.00 -48708.07 0.00 -10831.51 0.00 0.00 0.00 2811.47 2352.88 78973.70 0.00 147.61 0.00 0.00 -0.00 0.00 0.00 -24746.07
ROOM_4_MULT19_FLR_3 27-MAY-21:51 0.00 -82765.67 0.00 -9652.50 0.00 0.00 6247.24 8537.16 6668.31 0.00 0.00 0.00 74925.09 0.00 -3312.79 0.00 -646.84 0.00
ROOM_5_FLR_3 30-AUG-08:32 0.00 -15238.19 0.00 -1047.31 0.00 0.00 59.49 370.00 453.05 10452.80 0.00 0.00 5060.75 0.00 -0.00 0.00 -110.58 0.00
ROOM_6_FLR_3 30-MAY-08:62 0.00 -14626.14 0.00 -1055.46 0.00 0.00 59.18 369.95 452.99 9630.03 0.00 0.00 5211.54 0.00 -0.00 0.00 -42.09 0.00
CORRIDOR_FLR_3 08-OCT-23:16 0.00 0.00 0.00 -14122.73 0.00 0.00 4538.64 2489.76 0.00 0.00 0.00 0.00 9926.17 0.00 -2282.02 0.00 -549.81 0.00
ROOM_1_FLR_6 04-JUN-21:51 0.00 -4031.27 0.00 -194.12 0.00 0.00 70.36 178.69 89.56 0.00 0.00 0.00 4231.77 0.00 -290.43 0.00 -54.56 0.00
ROOM_2_FLR_6 04-JUN-21:51 0.00 -3900.62 0.00 -192.14 0.00 0.00 71.12 178.67 89.55 0.00 0.00 0.00 4093.51 0.00 -286.26 0.00 -53.83 0.00
ROOM_3_MULT9_FLR_6 30-OCT-16:41 0.00 -18975.17 0.00 -1064.46 0.00 0.00 471.04 333.03 1114.83 0.00 0.00 0.00 19934.16 0.00 -1477.03 0.00 -336.38 0.00
BANQUET_FLR_6 22-JAN-22:52 0.00 0.00 0.00 -34018.21 0.00 0.00 13560.69 1909.91 6747.90 0.00 0.00 0.00 13380.36 0.00 -1255.80 0.00 -324.85 0.00
DINING_FLR_6 22-JAN-22:52 0.00 0.00 0.00 -37414.80 0.00 0.00 13524.33 1909.91 6747.90 0.00 0.00 0.00 16848.46 0.00 -1290.69 0.00 -325.12 0.00
KITCHEN_FLR_6 04-DEC-07:51 0.00 0.00 0.00 -39671.39 0.00 0.00 440.41 672.74 19261.50 0.00 0.00 0.00 20242.37 0.00 -650.48 0.00 -295.14 0.00
CORRIDOR_FLR_6 16-AUG-12:50 0.00 0.00 0.00 -7072.11 0.00 0.00 308.46 548.96 0.00 4084.66 0.00 111.28 2018.75 0.00 -0.00 0.00 0.00 0.00
Total Facility 10-JUL-18:02 0.00 -171445.05 0.00 -216053.94 0.00 0.00 74583.45 58948.06 120482.43 43486.14 0.00 4383.17 85615.73 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 15-MAY-02:00 0.00 0.00 920.60 0.00 0.00 0.00 7163.31 1716.93 2027.90 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -11828.73
RETAIL_1_FLR_1 02-JAN-07:20 0.00 0.00 1366.01 0.00 0.00 0.00 359.24 397.97 433.01 0.00 0.00 0.00 0.00 0.00 -1449.36 0.00 -440.84 -666.04
RETAIL_2_FLR_1 26-NOV-06:27 0.00 0.00 250.76 0.00 0.00 0.00 708.47 276.51 334.29 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -62.60 -1507.43
MECH_FLR_1 02-JAN-05:00 0.00 0.00 634.59 0.00 0.00 0.00 197.28 74.25 176.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -412.78 -670.07
STORAGE_FLR_1 02-JAN-05:00 0.00 0.00 572.08 0.00 0.00 0.00 151.75 37.67 50.98 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -238.15 -574.33
LAUNDRY_FLR_1 07-OCT-03:39 0.00 0.00 2065.89 0.00 0.00 0.00 622.87 50.40 9326.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -205.86 -11859.48
CAFE_FLR_1 13-NOV-09:02 0.00 0.00 1727.63 0.00 0.00 0.00 2352.15 191.42 508.04 0.00 0.00 0.00 0.00 0.00 -290.52 0.00 -400.97 -4087.74
LOBBY_FLR_1 28-FEB-09:59 0.00 0.00 4132.45 0.00 0.00 0.00 6983.60 3358.36 5278.53 0.00 0.00 0.00 0.00 0.00 -1618.73 0.00 -1094.76 -17039.45
ROOM_1_FLR_3 14-JAN-16:13 6894.45 366.56 0.00 -366.56 0.00 0.00 148.79 277.50 221.25 0.00 0.00 0.00 0.00 0.00 -2757.82 0.00 -816.97 -3967.21
ROOM_2_FLR_3 12-JAN-19:01 6887.37 289.17 0.00 -289.17 0.00 0.00 418.01 748.31 484.60 0.00 0.00 0.00 0.00 0.00 -1572.59 0.00 -395.81 -6569.90
ROOM_3_MULT19_FLR_3 02-JAN-05:00 18135.56 3440.37 0.00 -3440.37 0.00 0.00 0.00 1104.51 3333.24 0.00 0.00 0.00 642.60 0.00 -17993.80 0.00 -5222.11 0.00
ROOM_4_MULT19_FLR_3 02-JAN-16:02 37952.55 3701.79 0.00 -3701.79 0.00 0.00 5585.70 2812.24 3726.41 0.00 0.00 0.00 0.00 0.00 -12865.31 0.00 -4118.65 -33092.94
ROOM_5_FLR_3 14-JAN-16:13 6732.33 360.99 0.00 -360.99 0.00 0.00 149.51 277.50 221.25 0.00 0.00 0.00 0.00 0.00 -2801.78 0.00 -814.69 -3764.11
ROOM_6_FLR_3 14-JAN-16:13 6711.69 358.18 0.00 -358.18 0.00 0.00 149.87 277.46 221.23 0.00 0.00 0.00 0.00 0.00 -2822.78 0.00 -813.49 -3723.98
CORRIDOR_FLR_3 14-JAN-16:17 0.00 0.00 3531.57 0.00 0.00 0.00 2078.71 2074.80 0.00 0.00 0.00 0.00 0.00 0.00 -3626.28 0.00 -1010.89 -3047.91
ROOM_1_FLR_6 14-JAN-16:13 2021.32 88.90 0.00 -88.90 0.00 0.00 37.60 69.37 55.31 0.00 0.00 0.00 0.00 0.00 -685.35 0.00 -203.62 -1294.63
ROOM_2_FLR_6 14-JAN-16:13 2013.55 88.12 0.00 -88.12 0.00 0.00 37.70 69.37 55.31 0.00 0.00 0.00 0.00 0.00 -691.77 0.00 -203.29 -1280.87
ROOM_3_MULT9_FLR_6 14-JAN-16:13 9442.82 568.39 0.00 -568.39 0.00 0.00 338.19 392.50 487.74 0.00 0.00 0.00 0.00 0.00 -3213.35 0.00 -936.78 -6511.12
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 02-JAN-07:10 0.00 0.00 2473.74 0.00 0.00 0.00 733.29 1097.93 0.00 0.00 0.00 0.00 0.00 0.00 -1899.78 0.00 -552.89 -1852.28
Total Facility 14-JAN-16:13 19826.75 83701.00 7722.19 -83701.00 0.00 0.00 35939.51 21186.59 74838.26 0.00 0.00 0.00 0.00 0.00 -65175.38 0.00 -20544.61 -73793.32



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.4922 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.3707 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6509 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6509 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6875 2.6875 1.3921 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3895 0.3895 0.2018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2402 0.2402 0.1244 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1887 0.1887 0.0977 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1242 0.1242 0.0643 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2667 3.2667 1.6922 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5814 1.5814 0.8192 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8380 4.8380 2.5061 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5943 1.5943 0.8258 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2016 2.2016 1.1404 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3066 2.3066 1.1948 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2790 2.2790 1.1805 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7946 0.7946 0.4116 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.4922 22.3707 22.4922 11.6509 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3921 1.3921 1.3921 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2018 0.2018 0.2018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1244 0.1244 0.1244 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0977 0.0977 0.0977 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0643 0.0643 0.0643 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6922 1.6922 1.6922 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8192 0.8192 0.8192 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5061 2.5061 2.5061 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8258 0.8258 0.8258 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1404 1.1404 1.1404 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1948 1.1948 1.1948 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1805 1.1805 1.1805 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4116 0.4116 0.4116 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6509 11.6509 11.6509 11.6509 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 11.67
Number of hours cooling loads not met 410.50
Number of hours not met 422.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 745.80 238365.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1191.16 202267.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 867.32 71560.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 262.05 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 31.07 1847.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 564.57 44381.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 107.86 5899.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 224.04 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.70 3178.71 291395.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.48 2032.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.50 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1720.26 5678.10
Natural Gas 1788.84 5713.35
Additional 0.00 0.00
Total 3509.10 11391.45


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 76.45
Space Heating 0.00
Space Cooling 104.99
Fans (All) 49.76
Service Water Heating 8.00
Receptacle Equipment 146.16
Miscellaneous (All) 500.48
Subtotal 500.48


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 65.74
Service Water Heating 280.18
Miscellaneous (All) 503.59
Subtotal 503.59


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.61
Space Heating 6.55
Space Cooling 10.46
Fans (All) 4.96
Service Water Heating 28.70
Receptacle Equipment 30.26
Miscellaneous 11.47


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2572. 8760.
LTG_SCH_LOBBY 2295. 8760.
LTG_SCH_STORAGE 1580. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8759.83 0.17 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8727.17 32.83 0.00 0.00 0.00
ROOM_2_FLR_3 8736.17 23.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8732.33 27.67 0.00 0.00 0.00
ROOM_6_FLR_3 8733.83 26.17 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8678.67 81.33 0.00 0.00 0.00
ROOM_2_FLR_6 8699.50 60.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8759.33 0.67 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8678.67 0.00 0.00 0.00 0.00
Max 8760.00 81.33 0.00 0.00 0.00
Average 8748.49 11.51 0.00 0.00 0.00
Sum 192466.83 253.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37202.50 0.50 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4150.50 3.50 0.00 0.00 0.00
ROOM_2_FLR_3 4150.17 3.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4137.00 17.00 0.00 0.00 0.00
ROOM_2_FLR_6 4137.67 16.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108261.67 7.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 17.00 0.00 0.00 0.00
Average 288884.84 2.20 0.00 0.00 0.00
Sum 6355466.50 48.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8554.83 205.17 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 7782.33 977.67 0.00 0.00 0.00
LOBBY_FLR_1 7776.67 983.33 0.00 0.00 0.00
ROOM_1_FLR_3 8455.83 304.17 0.00 0.00 0.00
ROOM_2_FLR_3 8489.50 270.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8734.33 25.67 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8633.83 126.17 0.00 0.00 0.00
ROOM_5_FLR_3 8457.33 302.67 0.00 0.00 0.00
ROOM_6_FLR_3 8482.33 277.67 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8387.00 373.00 0.00 0.00 0.00
ROOM_2_FLR_6 8432.33 327.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8478.17 281.83 0.00 0.00 0.00
BANQUET_FLR_6 7706.17 1053.83 0.00 0.00 0.00
DINING_FLR_6 7802.83 957.17 0.00 0.00 0.00
KITCHEN_FLR_6 8608.33 151.67 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 7706.17 0.00 0.00 0.00 0.00
Max 8760.00 1053.83 0.00 0.00 0.00
Average 8459.17 300.83 0.00 0.00 0.00
Sum 186101.83 6618.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 56967.67 2188.33 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 592239.33 118177.67 0.00 0.00 0.00
LOBBY_FLR_1 1770652.33 344776.67 0.00 0.00 0.00
ROOM_1_FLR_3 4000.33 153.67 0.00 0.00 0.00
ROOM_2_FLR_3 4017.83 136.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4080.33 73.67 0.00 0.00 0.00
ROOM_5_FLR_3 4031.33 122.67 0.00 0.00 0.00
ROOM_6_FLR_3 4043.33 110.67 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 3977.00 177.00 0.00 0.00 0.00
ROOM_2_FLR_6 3996.83 157.17 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4009.83 144.17 0.00 0.00 0.00
BANQUET_FLR_6 1030277.17 215437.83 0.00 0.00 0.00
DINING_FLR_6 1047388.83 198326.17 0.00 0.00 0.00
KITCHEN_FLR_6 106898.50 1370.50 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1770652.33 344776.67 0.00 0.00 0.00
Average 248825.58 40061.47 0.00 0.00 0.00
Sum 5474162.67 881352.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.357169E+11 32537.37 24-JAN-21:57 6.70 4.17 0.788283E+10 4920.44 19-JAN-22:49 6.70 4.17
February 0.306242E+11 27242.87 01-FEB-21:08 5.50 3.11 0.687352E+10 4837.11 01-FEB-22:10 4.90 2.79
March 0.326232E+11 26017.48 05-MAR-07:37 6.70 6.70 0.747761E+10 4777.49 31-MAR-21:40 7.27 7.27
April 0.312529E+11 25429.18 13-APR-06:47 6.60 2.59 0.710929E+10 4703.06 18-APR-21:40 7.20 6.24
May 0.326572E+11 21101.82 01-MAY-01:13 9.20 6.54 0.716788E+10 4501.05 04-MAY-21:10 14.40 12.58
June 0.339947E+11 17466.70 22-JUN-18:10 28.72 17.28 0.718562E+10 4639.47 30-JUN-21:19 20.00 18.86
July 0.373676E+11 17208.49 11-JUL-17:08 28.12 17.29 0.766999E+10 4812.09 28-JUL-22:10 24.32 20.84
August 0.396019E+11 20929.45 24-AUG-18:53 29.40 16.45 0.797783E+10 4837.38 30-AUG-21:19 22.43 18.00
September 0.402237E+11 25944.93 24-SEP-05:49 10.10 8.60 0.787593E+10 4837.12 28-SEP-21:10 16.42 11.03
October 0.430587E+11 38159.79 27-OCT-23:56 7.20 3.22 0.819274E+10 4989.52 18-OCT-02:20 7.20 3.22
November 0.404237E+11 38716.81 08-NOV-00:14 7.23 6.45 0.792175E+10 4971.79 17-NOV-22:49 5.10 2.91
December 0.388779E+11 50179.54 04-DEC-07:51 6.10 5.88 0.810656E+10 4889.63 04-DEC-22:30 8.05 7.50
                     
Annual Sum or Average 0.436423E+12         0.914415E+11        
Minimum of Months 0.306242E+11 17208.49   5.50 2.59 0.687352E+10 4501.05   4.90 2.79
Maximum of Months 0.430587E+11 50179.54   29.40 17.29 0.819274E+10 4989.52   24.32 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105843E+10 3247.91 19-JAN-14:10 9.32 3.68 0.624763E+09 384.04 19-JAN-22:00 5.60 1.07
February 0.133149E+10 3510.93 17-FEB-12:20 7.03 1.88 0.567988E+09 365.89 01-FEB-22:10 7.03 1.88
March 0.236528E+10 4860.33 29-MAR-12:48 7.80 5.26 0.640177E+09 410.88 03-MAR-22:19 7.80 5.26
April 0.299664E+10 3578.94 07-APR-12:30 26.15 15.90 0.628729E+09 458.71 07-APR-21:30 18.85 13.63
May 0.406279E+10 2802.03 30-MAY-12:50 29.90 17.93 0.664546E+09 462.23 31-MAY-21:30 20.25 17.49
June 0.484072E+10 3128.22 19-JUN-12:50 35.28 24.00 0.702531E+09 491.82 19-JUN-21:19 28.53 20.50
July 0.552609E+10 3315.88 08-JUL-12:00 32.20 26.10 0.759737E+09 491.83 10-JUL-21:19 27.03 20.02
August 0.606750E+10 4062.23 18-AUG-12:40 33.13 20.27 0.778787E+09 491.82 18-AUG-21:00 23.90 17.61
September 0.510527E+10 4353.14 01-SEP-13:57 31.10 17.34 0.699121E+09 491.83 01-SEP-21:10 26.60 18.09
October 0.492206E+10 4480.61 04-OCT-12:10 24.50 18.64 0.697264E+09 467.34 04-OCT-21:30 16.95 15.74
November 0.230205E+10 4425.70 18-NOV-12:23 7.20 3.93 0.614589E+09 418.03 03-NOV-21:30 7.20 3.93
December 0.148821E+10 5631.24 03-DEC-12:49 8.22 3.55 0.628179E+09 375.99 19-DEC-22:10 5.40 2.50
                     
Annual Sum or Average 0.420665E+11         0.800641E+10        
Minimum of Months 0.105843E+10 2802.03   7.03 1.88 0.567988E+09 365.89   5.40 1.07
Maximum of Months 0.606750E+10 5631.24   35.28 26.10 0.778787E+09 491.83   28.53 20.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.225024E+10 1958.59 21-JAN-22:48 6.10 5.16 0.768607E+09 544.22 19-JAN-22:00 6.10 5.16
February 0.210333E+10 1932.99 20-FEB-16:28 6.95 4.30 0.699551E+09 521.36 01-FEB-22:10 6.95 4.30
March 0.262515E+10 2225.76 12-MAR-00:37 7.20 4.85 0.826685E+09 568.00 28-MAR-21:30 8.05 5.61
April 0.274537E+10 2246.67 13-APR-06:47 6.60 2.59 0.831977E+09 569.59 12-APR-21:00 6.60 2.59
May 0.313791E+10 1896.01 31-MAY-21:00 20.60 17.62 0.891619E+09 569.55 31-MAY-22:10 19.78 17.36
June 0.342848E+10 2152.54 19-JUN-21:00 28.90 20.74 0.908371E+09 569.55 20-JUN-22:10 20.60 17.54
July 0.376841E+10 2172.27 10-JUL-21:00 27.20 20.22 0.950205E+09 569.55 11-JUL-22:10 22.62 17.84
August 0.390644E+10 2236.87 04-AUG-21:00 32.20 23.82 0.960304E+09 569.57 30-AUG-21:19 22.43 18.00
September 0.338508E+10 2145.87 01-SEP-21:00 26.70 18.23 0.900516E+09 569.55 28-SEP-22:10 14.90 10.57
October 0.323543E+10 2271.64 30-OCT-23:56 7.20 2.57 0.910879E+09 569.55 04-OCT-22:10 7.20 2.57
November 0.256730E+10 2090.49 13-NOV-07:05 6.10 5.08 0.799945E+09 568.36 03-NOV-21:30 6.10 5.08
December 0.243612E+10 2116.68 04-DEC-07:51 6.10 5.88 0.788885E+09 543.42 19-DEC-22:10 5.40 2.50
                     
Annual Sum or Average 0.355893E+11         0.102375E+11        
Minimum of Months 0.210333E+10 1896.01   6.10 2.57 0.699551E+09 521.36   5.40 2.50
Maximum of Months 0.390644E+10 2271.64   32.20 23.82 0.960304E+09 569.59   22.62 18.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.596206E+09 1392.27 21-JAN-22:48 6.10 5.16 0.152230E+09 95.67 19-JAN-22:00 6.10 5.16
February 0.507739E+09 1088.23 20-FEB-15:34 7.57 4.52 0.137418E+09 93.15 01-FEB-22:10 7.57 4.52
March 0.134407E+10 1609.11 05-MAR-07:37 6.70 6.70 0.155970E+09 102.83 28-MAR-21:30 8.05 5.61
April 0.180444E+10 1671.11 11-APR-06:16 6.47 1.88 0.158506E+09 110.02 10-APR-21:10 6.47 1.88
May 0.227412E+10 1372.58 01-MAY-01:13 9.20 6.54 0.176692E+09 119.45 31-MAY-21:19 20.37 17.53
June 0.257844E+10 1543.07 19-JUN-21:00 28.90 20.74 0.188043E+09 120.45 20-JUN-21:19 20.93 17.07
July 0.290148E+10 1773.86 10-JUL-20:00 28.30 20.24 0.200404E+09 120.46 11-JUL-21:19 22.80 17.52
August 0.294792E+10 1809.89 17-AUG-20:00 28.90 22.33 0.201801E+09 120.46 30-AUG-21:19 22.43 18.00
September 0.249939E+10 1490.73 01-SEP-21:00 26.70 18.23 0.184608E+09 120.45 01-SEP-21:10 26.60 18.09
October 0.226474E+10 1660.92 08-OCT-23:16 6.83 3.54 0.177520E+09 115.87 05-OCT-21:10 6.83 3.54
November 0.148295E+10 1569.94 13-NOV-07:05 6.10 5.08 0.153805E+09 104.63 03-NOV-21:10 6.10 5.08
December 0.947582E+09 1489.06 04-DEC-07:51 6.10 5.88 0.152455E+09 96.31 19-DEC-22:10 5.40 2.50
                     
Annual Sum or Average 0.221491E+11         0.203945E+10        
Minimum of Months 0.507739E+09 1088.23   6.10 1.88 0.137418E+09 93.15   5.40 1.88
Maximum of Months 0.294792E+10 1809.89   28.90 22.33 0.201801E+09 120.46   26.60 18.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.166279E+09 819.06 22-JAN-22:52 6.10 5.88 0.116724E+09 70.37 19-JAN-22:00 6.10 5.88
February 0.133501E+09 704.96 19-FEB-11:32 7.97 4.38 0.105503E+09 69.05 01-FEB-22:10 7.97 4.38
March 0.618200E+09 1033.61 05-MAR-07:37 6.70 6.70 0.118170E+09 75.11 28-MAR-21:30 8.05 5.61
April 0.103651E+10 1060.63 11-APR-06:16 6.47 1.88 0.118382E+09 80.37 07-APR-21:40 6.47 1.88
May 0.142750E+10 875.12 01-MAY-01:13 9.20 6.54 0.131110E+09 87.75 31-MAY-22:10 19.78 17.36
June 0.162140E+10 847.93 22-JUN-18:10 28.72 17.28 0.140073E+09 92.41 19-JUN-21:40 28.72 17.28
July 0.179620E+10 859.80 08-JUL-10:33 30.53 25.21 0.150374E+09 92.66 10-JUL-21:19 27.03 20.02
August 0.180933E+10 959.20 24-AUG-18:53 29.40 16.45 0.151482E+09 92.66 18-AUG-22:10 29.40 16.45
September 0.156671E+10 859.13 01-SEP-17:06 27.80 17.38 0.137109E+09 92.03 01-SEP-21:40 26.30 17.68
October 0.141427E+10 1055.78 08-OCT-23:16 6.83 3.54 0.131311E+09 85.07 05-OCT-22:10 6.83 3.54
November 0.762864E+09 978.93 01-NOV-06:40 6.10 3.87 0.115427E+09 76.63 03-NOV-22:10 12.80 10.38
December 0.286508E+09 966.23 04-DEC-07:51 6.10 5.88 0.116740E+09 70.69 19-DEC-22:10 5.40 2.50
                     
Annual Sum or Average 0.126393E+11         0.153241E+10        
Minimum of Months 0.133501E+09 704.96   6.10 1.88 0.105503E+09 69.05   5.40 1.88
Maximum of Months 0.180933E+10 1060.63   30.53 25.21 0.151482E+09 92.66   29.40 20.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.473061E+11 51077.66 03-JAN-21:00 5.60 4.81 0.584236E+09 484.31 19-JAN-22:49 5.60 1.07
February 0.427700E+11 51247.65 23-FEB-21:07 4.90 3.92 0.526152E+09 431.08 01-FEB-21:49 4.90 3.92
March 0.488982E+11 51506.02 24-MAR-20:49 6.20 5.60 0.594770E+09 507.23 28-MAR-21:30 8.05 5.61
April 0.483892E+11 50767.36 14-APR-18:06 7.12 4.88 0.578324E+09 543.03 18-APR-22:10 7.30 6.22
May 0.515923E+11 39167.11 01-MAY-19:50 9.60 5.35 0.595144E+09 407.85 16-MAY-04:30 8.90 7.23
June 0.512737E+11 39527.86 22-JUN-20:03 26.60 16.66 0.577341E+09 382.51 22-JUN-20:10 26.60 16.66
July 0.535070E+11 38923.65 10-JUL-20:00 28.30 20.24 0.596534E+09 381.68 25-JUL-21:19 22.60 20.76
August 0.539081E+11 41643.26 24-AUG-18:29 30.25 17.47 0.598581E+09 381.79 18-AUG-21:10 30.25 17.47
September 0.507556E+11 38635.42 06-SEP-20:00 22.80 20.83 0.575885E+09 387.39 01-SEP-21:10 22.80 20.83
October 0.511738E+11 48596.12 28-OCT-20:56 6.70 2.41 0.595521E+09 447.69 27-OCT-23:10 6.70 2.41
November 0.474504E+11 50018.06 17-NOV-21:54 5.60 3.18 0.575000E+09 493.73 28-NOV-21:00 6.10 5.30
December 0.478331E+11 50033.62 07-DEC-20:08 4.40 1.07 0.586857E+09 447.73 04-DEC-22:30 4.40 1.07
                     
Annual Sum or Average 0.594858E+12         0.698435E+10        
Minimum of Months 0.427700E+11 38635.42   4.40 1.07 0.526152E+09 381.68   4.40 1.07
Maximum of Months 0.539081E+11 51506.02   30.25 20.83 0.598581E+09 543.03   30.25 20.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141195E+11 14183.50 19-JAN-11:08 7.70 4.65 0.876885E+10 6395.62 19-JAN-22:49 5.60 1.07
February 0.140176E+11 17217.29 19-FEB-12:40 8.13 4.20 0.803708E+10 5970.26 01-FEB-22:10 8.13 4.20
March 0.174509E+11 19717.93 29-MAR-12:48 7.80 5.26 0.947217E+10 6756.78 27-MAR-03:20 7.80 5.26
April 0.180431E+11 17875.08 25-APR-02:40 9.40 8.82 0.944466E+10 6606.96 12-APR-22:30 9.40 8.82
May 0.204432E+11 12489.61 02-MAY-02:63 8.30 4.40 0.100866E+11 6725.08 15-MAY-02:49 7.38 6.57
June 0.219880E+11 12099.99 19-JUN-21:10 28.72 20.62 0.102497E+11 6462.78 02-JUN-21:00 28.72 20.62
July 0.243680E+11 11924.16 10-JUL-21:10 27.12 20.12 0.107371E+11 6462.78 11-JUL-22:10 22.62 17.84
August 0.261009E+11 13486.92 19-AUG-11:50 27.02 16.40 0.108802E+11 6462.80 25-AUG-22:10 20.92 14.50
September 0.231332E+11 15168.96 30-SEP-12:40 20.40 12.36 0.102306E+11 6462.79 11-SEP-22:10 20.40 12.36
October 0.232901E+11 16249.26 29-OCT-09:10 8.17 4.68 0.104527E+11 6890.22 18-OCT-02:20 8.17 4.68
November 0.169869E+11 20087.06 07-NOV-23:55 7.80 6.71 0.910664E+10 6621.05 06-NOV-23:19 7.80 6.71
December 0.156134E+11 22895.90 03-DEC-12:49 8.22 3.55 0.899434E+10 6274.75 05-DEC-03:30 7.25 6.25
                     
Annual Sum or Average 0.235555E+12         0.116460E+12        
Minimum of Months 0.140176E+11 11924.16   7.70 3.55 0.803708E+10 5970.26   5.60 1.07
Maximum of Months 0.261009E+11 22895.90   28.72 20.62 0.108802E+11 6890.22   28.72 20.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.511449E+11 40936.82 18-JAN-07:09 8.40 8.15 0.275528E+11 19279.01 19-JAN-22:49 5.60 1.07
February 0.477498E+11 39861.11 18-FEB-15:22 6.70 3.06 0.250928E+11 18609.65 01-FEB-22:10 6.70 3.06
March 0.572109E+11 59070.28 04-MAR-03:10 8.12 5.84 0.294422E+11 19760.62 28-MAR-21:30 8.05 5.61
April 0.589279E+11 54543.63 12-APR-21:50 7.30 2.28 0.293389E+11 19689.82 12-APR-22:30 7.20 2.66
May 0.664742E+11 56841.89 15-MAY-02:44 7.38 6.57 0.311598E+11 19862.50 15-MAY-02:49 7.38 6.57
June 0.716761E+11 40644.26 19-JUN-21:10 28.72 20.62 0.310351E+11 19186.24 20-JUN-22:10 20.60 17.54
July 0.785733E+11 41032.17 10-JUL-21:10 27.12 20.12 0.321776E+11 19186.24 11-JUL-22:10 22.62 17.84
August 0.810965E+11 42299.28 04-AUG-21:10 31.55 23.93 0.324763E+11 19186.29 25-AUG-22:10 20.92 14.50
September 0.717965E+11 41239.32 01-SEP-21:10 26.60 18.09 0.309953E+11 19186.27 28-SEP-22:10 14.90 10.57
October 0.696500E+11 82042.13 27-OCT-23:02 7.20 3.22 0.317622E+11 20024.83 18-OCT-02:20 7.20 3.22
November 0.562571E+11 53899.04 08-NOV-00:18 7.23 6.45 0.285938E+11 19715.17 06-NOV-23:19 7.23 6.45
December 0.541604E+11 44892.22 17-DEC-09:03 6.05 2.94 0.283088E+11 19188.34 19-DEC-22:10 5.40 2.50
                     
Annual Sum or Average 0.764718E+12         0.357935E+12        
Minimum of Months 0.477498E+11 39861.11   6.05 2.28 0.250928E+11 18609.65   5.40 1.07
Maximum of Months 0.810965E+11 82042.13   31.55 23.93 0.324763E+11 20024.83   22.62 17.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 64460733.87 3534.35 19-JAN-16:01 8.22 2.84 93493313.07 56.69 03-JAN-04:19 8.22 2.84
February 88036176.79 3500.96 24-FEB-16:01 7.62 1.74 85028785.38 56.69 07-FEB-04:19 7.62 1.74
March 0.312309E+09 3642.15 24-MAR-15:01 9.90 5.68 96052566.19 69.37 27-MAR-21:10 14.13 10.87
April 0.630764E+09 3869.36 09-APR-18:11 14.43 12.85 95316052.94 76.34 07-APR-21:30 14.43 12.85
May 0.114847E+10 3877.53 29-MAY-18:31 24.80 18.16 0.104400E+09 89.93 31-MAY-21:10 20.48 17.58
June 0.189224E+10 3927.35 04-JUN-21:51 17.20 12.24 0.107455E+09 88.09 28-JUN-21:10 21.20 18.58
July 0.255491E+10 3642.64 03-JUL-18:51 24.40 21.27 0.104542E+09 83.57 05-JUL-21:30 22.50 21.72
August 0.277840E+10 3771.66 30-AUG-08:51 22.80 14.85 0.104117E+09 85.32 10-AUG-21:10 22.80 14.85
September 0.157289E+10 3768.05 03-SEP-08:51 22.80 14.85 0.104473E+09 88.27 06-SEP-21:10 22.70 20.80
October 0.107458E+10 3784.97 30-OCT-16:41 14.18 6.99 0.103173E+09 80.87 04-OCT-21:40 14.18 6.99
November 0.192092E+09 3550.21 03-NOV-15:01 16.83 10.88 92180998.28 56.69 03-NOV-03:20 16.83 10.88
December 77248154.10 3458.37 17-DEC-16:01 9.82 4.16 93929864.48 56.69 05-DEC-03:20 9.82 4.16
                     
Annual Sum or Average 0.123864E+11         0.118416E+10        
Minimum of Months 64460733.87 3458.37   7.62 1.74 85028785.38 56.69   7.62 1.74
Maximum of Months 0.277840E+10 3927.35   24.80 21.27 0.107455E+09 89.93   22.80 21.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 36116623.01 2072.65 17-JAN-16:01 9.45 4.59 92724854.14 56.69 03-JAN-04:19 9.45 4.59
February 41296769.86 3150.35 20-FEB-16:01 7.12 4.40 83985709.02 56.69 03-FEB-04:19 7.12 4.40
March 0.177141E+09 3505.66 07-MAR-16:01 7.93 4.57 94925498.05 66.31 27-MAR-21:10 14.13 10.87
April 0.472813E+09 3723.64 09-APR-18:11 14.43 12.85 94566387.24 73.16 07-APR-21:30 14.43 12.85
May 0.104436E+10 3775.53 29-MAY-18:31 24.80 18.16 0.104037E+09 89.24 31-MAY-21:10 20.48 17.58
June 0.180805E+10 3705.84 10-JUN-08:51 23.30 15.08 0.107314E+09 87.61 28-JUN-21:10 21.20 18.58
July 0.243984E+10 3560.70 03-JUL-18:51 24.40 21.27 0.104504E+09 83.30 05-JUL-21:30 22.50 21.72
August 0.249347E+10 3602.98 25-AUG-21:51 21.10 14.56 0.103760E+09 84.09 10-AUG-21:10 21.10 14.56
September 0.128072E+10 3546.45 11-SEP-21:51 17.80 13.02 0.102969E+09 84.00 06-SEP-21:10 17.80 13.02
October 0.658474E+09 3444.58 30-OCT-16:41 14.18 6.99 0.101116E+09 75.92 04-OCT-21:40 14.18 6.99
November 94592216.02 3411.22 03-NOV-15:01 16.83 10.88 91109024.32 56.69 03-NOV-03:20 16.83 10.88
December 41624134.37 1149.77 17-DEC-16:01 9.82 4.16 92844831.62 56.69 01-DEC-03:39 9.82 4.16
                     
Annual Sum or Average 0.105885E+11         0.117386E+10        
Minimum of Months 36116623.01 1149.77   7.12 4.16 83985709.02 56.69   7.12 4.16
Maximum of Months 0.249347E+10 3775.53   24.80 21.27 0.107314E+09 89.24   22.50 21.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.114489E+09 201.88 19-JAN-14:27 9.15 3.65 0.00 0.00 01-JAN-00:10 9.15 3.65
February 0.164878E+09 337.81 20-FEB-13:30 9.15 4.45 0.00 0.00 01-FEB-00:10 9.15 4.45
March 0.254520E+09 490.31 03-MAR-13:30 14.70 8.33 0.00 0.00 01-MAR-00:10 14.70 8.33
April 0.320045E+09 621.85 08-APR-12:30 23.60 16.18 0.00 0.00 01-APR-00:10 23.60 16.18
May 0.423563E+09 495.88 30-MAY-12:50 29.90 17.93 0.00 0.00 01-MAY-00:10 29.90 17.93
June 0.590489E+09 521.95 19-JUN-13:10 34.90 23.89 0.00 0.00 01-JUN-00:10 34.90 23.89
July 0.808162E+09 545.47 10-JUL-13:10 32.30 20.52 0.00 0.00 01-JUL-00:10 32.30 20.52
August 0.924302E+09 680.21 30-AUG-12:50 27.12 15.44 0.00 0.00 01-AUG-00:10 27.12 15.44
September 0.695027E+09 728.20 30-SEP-12:30 20.30 12.33 0.00 0.00 01-SEP-00:10 20.30 12.33
October 0.670137E+09 783.41 04-OCT-12:00 24.40 18.65 0.00 0.00 01-OCT-00:10 24.40 18.65
November 0.288199E+09 644.93 02-NOV-12:40 15.40 8.14 0.00 0.00 01-NOV-00:10 15.40 8.14
December 0.190808E+09 498.57 17-DEC-13:30 12.20 5.12 0.00 0.00 01-DEC-00:10 12.20 5.12
                     
Annual Sum or Average 0.544462E+10         0.00        
Minimum of Months 0.114489E+09 201.88   9.15 3.65 0.00 0.00   9.15 3.65
Maximum of Months 0.924302E+09 783.41   34.90 23.89 0.00 0.00   34.90 23.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 61233132.23 380.36 19-JAN-19:03 5.82 1.55 93863254.61 56.69 12-JAN-22:40 5.82 1.55
February 51098989.00 422.47 20-FEB-09:02 5.87 1.96 84756322.95 56.69 01-FEB-22:19 5.87 1.96
March 0.145615E+09 1041.24 28-MAR-18:01 10.00 6.79 95124046.36 65.31 27-MAR-21:10 10.00 6.79
April 0.315869E+09 1142.14 10-APR-20:41 13.68 6.84 93348635.33 69.19 07-APR-21:49 13.68 6.84
May 0.554098E+09 1216.03 27-MAY-21:51 18.90 10.64 0.100232E+09 76.96 31-MAY-21:40 20.13 17.44
June 0.740360E+09 1202.31 04-JUN-08:51 23.30 12.88 0.101570E+09 78.14 28-JUN-21:40 21.50 18.92
July 0.948724E+09 1152.63 03-JUL-18:51 24.40 21.27 0.102605E+09 78.15 25-JUL-21:10 22.70 20.79
August 0.891716E+09 1143.55 28-AUG-21:51 19.40 14.50 0.101588E+09 76.48 10-AUG-21:10 19.40 14.50
September 0.596210E+09 1181.55 10-SEP-21:51 16.70 9.96 99086185.08 77.17 05-SEP-21:10 16.70 9.96
October 0.377746E+09 1126.87 25-OCT-21:51 16.10 7.75 97801642.98 69.96 04-OCT-21:00 16.10 7.75
November 0.162876E+09 1026.98 11-NOV-09:02 10.60 10.32 91976433.25 56.69 09-NOV-22:10 10.60 10.32
December 66242414.27 440.97 25-DEC-09:02 10.50 10.22 94052703.42 56.69 01-DEC-03:39 10.50 10.22
                     
Annual Sum or Average 0.491179E+10         0.115600E+10        
Minimum of Months 51098989.00 380.36   5.82 1.55 84756322.95 56.69   5.82 1.55
Maximum of Months 0.948724E+09 1216.03   24.40 21.27 0.102605E+09 78.15   22.70 20.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 78528769.74 2354.25 17-JAN-16:01 9.45 4.59 93442386.00 56.69 03-JAN-04:19 9.45 4.59
February 0.100924E+09 3117.12 25-FEB-09:02 -2.0 -5.5 85078465.17 56.69 14-FEB-04:19 -2.0 -5.5
March 0.289778E+09 3335.54 24-MAR-15:01 9.90 5.68 95925144.61 62.17 27-MAR-21:10 14.13 10.87
April 0.659083E+09 3765.70 08-APR-08:51 21.70 15.33 94854586.80 74.84 07-APR-21:30 21.70 15.33
May 0.121509E+10 4010.46 30-MAY-08:62 25.18 15.91 0.103158E+09 82.87 31-MAY-21:30 20.25 17.49
June 0.180163E+10 3940.73 02-JUN-08:51 16.10 9.46 0.104968E+09 80.96 28-JUN-21:30 21.40 18.80
July 0.249856E+10 3867.98 11-JUL-08:32 23.53 16.28 0.104826E+09 82.35 25-JUL-21:10 22.70 20.79
August 0.272528E+10 4071.43 30-AUG-08:32 22.60 14.90 0.104432E+09 82.51 10-AUG-21:10 22.60 14.90
September 0.160799E+10 3927.61 10-SEP-08:32 19.63 13.49 0.103388E+09 85.00 05-SEP-21:10 19.63 13.49
October 0.106339E+10 3742.80 15-OCT-08:51 17.20 12.24 0.102001E+09 77.10 04-OCT-21:40 17.20 12.24
November 0.244662E+09 3254.69 03-NOV-15:01 16.83 10.88 92364722.31 56.69 03-NOV-04:10 16.83 10.88
December 0.110355E+09 3097.42 17-DEC-09:02 6.05 2.94 93937950.37 56.69 05-DEC-03:20 6.05 2.94
                     
Annual Sum or Average 0.123953E+11         0.117838E+10        
Minimum of Months 78528769.74 2354.25   -2.0 -5.5 85078465.17 56.69   -2.0 -5.5
Maximum of Months 0.272528E+10 4071.43   25.18 16.28 0.104968E+09 85.00   22.70 20.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 34800729.39 738.73 26-JAN-09:03 0.87 -2.0 92713259.44 56.69 03-JAN-04:30 0.87 -2.0
February 42847411.30 2302.94 19-FEB-09:02 4.37 2.79 84014834.58 56.69 28-FEB-04:19 1.10 0.87
March 0.161808E+09 3090.61 29-MAR-08:62 4.60 2.26 94719143.45 59.34 27-MAR-21:10 4.60 2.26
April 0.493056E+09 3609.25 08-APR-08:51 21.70 15.33 94215739.19 71.92 07-APR-21:30 21.70 15.33
May 0.110201E+10 3920.69 30-MAY-08:62 25.18 15.91 0.102981E+09 82.37 31-MAY-21:30 20.25 17.49
June 0.171746E+10 3847.40 26-JUN-08:32 24.63 19.00 0.104932E+09 80.80 20-JUN-21:19 24.63 19.00
July 0.238318E+10 3778.95 11-JUL-08:32 23.53 16.28 0.104790E+09 81.60 25-JUL-21:10 22.70 20.79
August 0.243735E+10 3882.87 30-AUG-08:32 22.60 14.90 0.104099E+09 81.33 10-AUG-21:10 22.60 14.90
September 0.130805E+10 3763.85 06-SEP-08:32 25.03 18.89 0.102203E+09 82.39 05-SEP-21:10 25.03 18.89
October 0.644180E+09 3435.38 15-OCT-08:51 17.20 12.24 0.100013E+09 72.67 05-OCT-21:40 17.20 12.24
November 0.124725E+09 2898.25 06-NOV-09:02 7.98 4.28 91259613.30 56.69 17-NOV-01:39 8.30 7.37
December 44762755.00 1257.36 17-DEC-09:02 6.05 2.94 92861793.31 56.69 01-DEC-03:39 6.05 2.94
                     
Annual Sum or Average 0.104942E+11         0.116880E+10        
Minimum of Months 34800729.39 738.73   0.87 -2.0 84014834.58 56.69   0.87 -2.0
Maximum of Months 0.243735E+10 3920.69   25.18 19.00 0.104932E+09 82.39   25.03 20.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138569E+10 2647.31 22-JAN-22:52 6.10 5.88 0.119989E+10 735.82 19-JAN-23:19 6.10 5.88
February 0.154413E+10 2981.79 20-FEB-16:28 6.95 4.30 0.108459E+10 717.98 01-FEB-22:10 6.95 4.30
March 0.303669E+10 3344.27 12-MAR-00:37 7.20 4.85 0.122472E+10 775.59 28-MAR-21:30 8.05 5.61
April 0.373241E+10 3505.74 13-APR-06:47 6.60 2.59 0.124070E+10 849.74 10-APR-21:30 6.60 2.59
May 0.473561E+10 2844.28 01-MAY-01:13 9.20 6.54 0.137807E+10 933.37 31-MAY-21:40 20.13 17.44
June 0.539200E+10 2775.43 22-JUN-18:10 28.72 17.28 0.147842E+10 948.23 20-JUN-21:40 28.72 17.28
July 0.580555E+10 2769.23 11-JUL-17:08 28.12 17.29 0.155329E+10 951.85 11-JUL-22:10 22.62 17.84
August 0.590532E+10 3111.03 24-AUG-18:53 29.40 16.45 0.157683E+10 951.87 30-AUG-21:49 21.88 17.79
September 0.521207E+10 2827.80 01-SEP-17:06 27.80 17.38 0.144514E+10 951.85 06-SEP-22:10 22.20 20.63
October 0.479324E+10 3530.68 08-OCT-23:16 6.83 3.54 0.139846E+10 904.80 05-OCT-22:10 6.83 3.54
November 0.283819E+10 3158.99 01-NOV-06:40 6.10 3.87 0.119096E+10 794.37 03-NOV-21:49 12.80 10.30
December 0.191134E+10 3096.66 04-DEC-07:51 6.10 5.88 0.120050E+10 726.41 19-DEC-22:10 5.40 2.50
                     
Annual Sum or Average 0.462922E+11         0.159716E+11        
Minimum of Months 0.138569E+10 2647.31   6.10 2.59 0.108459E+10 717.98   5.40 2.50
Maximum of Months 0.590532E+10 3530.68   29.40 17.38 0.157683E+10 951.87   28.72 20.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 52812189.17 3702.02 19-JAN-16:01 8.22 2.84 93127663.53 56.69 03-JAN-04:30 8.22 2.84
February 80194877.10 3646.66 24-FEB-16:01 7.62 1.74 84685022.41 56.69 28-FEB-04:19 1.10 0.87
March 0.304825E+09 3806.28 24-MAR-15:01 9.90 5.68 95808051.16 71.74 27-MAR-21:10 14.13 10.87
April 0.631547E+09 4206.82 10-APR-20:41 13.68 6.84 95404985.09 78.32 07-APR-21:30 13.68 6.84
May 0.118357E+10 4185.44 02-MAY-18:21 14.15 8.82 0.105223E+09 94.59 31-MAY-21:10 20.48 17.58
June 0.199113E+10 4225.40 04-JUN-21:51 17.20 12.24 0.108399E+09 92.19 14-JUN-21:10 21.02 19.55
July 0.267352E+10 3773.94 01-JUL-21:51 19.40 18.28 0.104601E+09 84.87 05-JUL-21:40 22.40 21.60
August 0.287943E+10 3933.55 30-AUG-08:51 22.80 14.85 0.104080E+09 88.41 29-AUG-21:10 22.80 14.85
September 0.158770E+10 4069.65 11-SEP-21:51 17.80 13.02 0.105122E+09 90.40 06-SEP-21:10 17.80 13.02
October 0.100557E+10 4048.73 30-OCT-16:41 14.18 6.99 0.103605E+09 87.33 04-OCT-21:10 14.18 6.99
November 0.155316E+09 3707.48 03-NOV-15:01 16.83 10.88 91749681.93 56.69 04-NOV-23:19 11.50 7.55
December 62529918.55 3623.03 17-DEC-16:01 9.82 4.16 93508754.36 56.69 01-DEC-03:39 9.82 4.16
                     
Annual Sum or Average 0.126082E+11         0.118531E+10        
Minimum of Months 52812189.17 3623.03   7.62 1.74 84685022.41 56.69   1.10 0.87
Maximum of Months 0.287943E+10 4225.40   22.80 18.28 0.108399E+09 94.59   22.80 21.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 21020659.62 1356.23 17-JAN-16:01 9.45 4.59 92495334.95 56.69 12-JAN-23:00 9.45 4.59
February 28878993.93 2841.65 20-FEB-16:01 7.12 4.40 83749561.27 56.69 10-FEB-04:19 7.12 4.40
March 0.161444E+09 3650.86 07-MAR-16:01 7.93 4.57 94628852.70 67.45 27-MAR-21:10 14.13 10.87
April 0.462721E+09 3973.73 09-APR-18:11 14.43 12.85 94612530.21 74.88 07-APR-21:30 14.43 12.85
May 0.106992E+10 4006.97 02-MAY-18:21 14.15 8.82 0.104934E+09 94.03 31-MAY-21:10 20.48 17.58
June 0.190468E+10 4092.76 04-JUN-21:51 17.20 12.24 0.108351E+09 91.56 14-JUN-21:10 21.02 19.55
July 0.255390E+10 3683.34 03-JUL-18:51 24.40 21.27 0.104569E+09 84.67 05-JUL-21:40 22.40 21.60
August 0.257806E+10 3742.42 28-AUG-21:51 19.40 14.50 0.103675E+09 85.40 10-AUG-21:10 19.40 14.50
September 0.126715E+10 3740.79 11-SEP-21:51 17.80 13.02 0.103333E+09 87.09 06-SEP-21:10 17.80 13.02
October 0.574568E+09 3613.67 30-OCT-16:41 14.18 6.99 0.101037E+09 77.56 04-OCT-21:40 14.18 6.99
November 71475831.65 3538.15 03-NOV-15:01 16.83 10.88 90686281.86 56.69 02-NOV-03:00 16.83 10.88
December 27796966.42 693.82 08-DEC-16:03 5.92 1.77 92519763.22 56.69 01-DEC-03:39 5.92 1.77
                     
Annual Sum or Average 0.107216E+11         0.117459E+10        
Minimum of Months 21020659.62 693.82   5.92 1.77 83749561.27 56.69   5.92 1.77
Maximum of Months 0.257806E+10 4092.76   24.40 21.27 0.108351E+09 94.03   22.40 21.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.164476E+09 2009.01 19-JAN-16:01 8.22 2.84 94914080.25 56.69 19-JAN-22:19 5.60 1.07
February 0.221584E+09 2007.55 18-FEB-16:01 6.52 2.91 86636533.93 56.69 07-FEB-04:19 6.52 2.91
March 0.378330E+09 2039.05 24-MAR-15:01 9.90 5.68 96721970.64 70.81 27-MAR-21:10 14.13 10.87
April 0.495723E+09 2097.09 07-APR-21:51 18.30 13.42 94977878.07 79.38 07-APR-21:40 18.30 13.42
May 0.715627E+09 2129.62 27-MAY-21:51 18.90 10.64 0.102055E+09 80.96 31-MAY-21:40 20.13 17.44
June 0.106521E+10 2123.64 04-JUN-08:51 23.30 12.88 0.103289E+09 81.94 28-JUN-21:40 21.50 18.92
July 0.150081E+10 2029.68 11-JUL-08:51 23.90 16.36 0.103778E+09 82.87 25-JUL-21:19 22.60 20.76
August 0.170452E+10 2118.19 30-AUG-08:51 22.80 14.85 0.103418E+09 83.03 29-AUG-21:19 22.80 14.85
September 0.118421E+10 2204.11 03-SEP-08:51 22.80 14.85 0.103894E+09 89.96 28-SEP-21:10 16.42 11.03
October 0.108080E+10 2226.63 30-OCT-16:41 14.18 6.99 0.103544E+09 92.11 04-OCT-21:10 14.18 6.99
November 0.360451E+09 1995.05 02-NOV-15:01 16.60 8.91 93733522.05 56.69 08-NOV-22:10 11.78 11.28
December 0.254917E+09 1984.17 17-DEC-16:01 9.82 4.16 95511950.55 56.69 01-DEC-03:39 9.82 4.16
                     
Annual Sum or Average 0.912666E+10         0.118247E+10        
Minimum of Months 0.164476E+09 1984.17   6.52 2.84 86636533.93 56.69   5.60 1.07
Maximum of Months 0.170452E+10 2226.63   23.90 16.36 0.103894E+09 92.11   22.80 20.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.299865E+11 34021.30 22-JAN-22:52 6.10 5.88 0.185848E+11 12298.48 24-JAN-22:00 6.10 3.24
February 0.269530E+11 31415.85 23-FEB-21:07 4.90 3.92 0.167713E+11 11384.89 01-FEB-22:10 4.90 3.92
March 0.329024E+11 32302.12 28-MAR-21:37 7.97 5.50 0.190633E+11 13138.47 27-MAR-03:20 7.97 5.50
April 0.346128E+11 33011.94 12-APR-22:10 7.20 2.49 0.185572E+11 12890.69 18-APR-22:10 7.30 6.22
May 0.395573E+11 33545.97 16-MAY-03:39 8.90 6.68 0.192823E+11 12639.59 15-MAY-02:49 8.90 6.68
June 0.420246E+11 23734.00 19-JUN-21:20 28.53 20.50 0.187422E+11 11357.68 23-JUN-21:19 22.80 20.95
July 0.452339E+11 23508.52 07-JUL-22:00 28.30 24.28 0.193050E+11 11364.20 21-JUL-21:19 25.60 23.73
August 0.449699E+11 23894.39 04-AUG-21:20 30.90 23.99 0.193802E+11 11371.82 18-AUG-21:19 24.63 17.59
September 0.398994E+11 26628.33 24-SEP-05:49 10.10 8.60 0.186654E+11 11809.20 30-SEP-01:19 10.77 9.56
October 0.373738E+11 31843.23 27-OCT-23:56 7.20 3.22 0.191837E+11 12958.77 18-OCT-02:20 7.20 3.22
November 0.318574E+11 32131.77 09-NOV-02:15 8.90 8.58 0.183226E+11 12718.45 17-NOV-05:00 7.80 7.25
December 0.308070E+11 31513.19 04-DEC-23:30 8.05 7.50 0.187569E+11 12144.41 05-DEC-02:20 7.80 6.94
                     
Annual Sum or Average 0.436178E+12         0.224615E+12        
Minimum of Months 0.269530E+11 23508.52   4.90 2.49 0.167713E+11 11357.68   4.90 3.22
Maximum of Months 0.452339E+11 34021.30   30.90 24.28 0.193802E+11 13138.47   25.60 23.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.334718E+11 37418.61 22-JAN-22:52 6.10 5.88 0.188643E+11 12414.89 24-JAN-22:00 6.10 3.24
February 0.300271E+11 33153.67 23-FEB-21:07 4.90 3.92 0.170316E+11 11417.21 01-FEB-22:10 4.90 3.92
March 0.366481E+11 34207.62 28-MAR-21:37 7.97 5.50 0.192358E+11 13247.35 27-MAR-03:20 7.97 5.50
April 0.382520E+11 34756.41 12-APR-22:10 7.20 2.49 0.186686E+11 13000.10 18-APR-22:10 7.30 6.22
May 0.431528E+11 35142.30 16-MAY-03:39 8.90 6.68 0.193284E+11 12722.59 15-MAY-02:49 8.90 6.68
June 0.450248E+11 24986.07 19-JUN-21:20 28.53 20.50 0.187554E+11 11373.57 23-JUN-21:19 22.80 20.95
July 0.481493E+11 24697.35 10-JUL-21:20 27.03 20.02 0.193088E+11 11375.16 21-JUL-21:19 25.60 23.73
August 0.478353E+11 25104.44 04-AUG-21:20 30.90 23.99 0.193879E+11 11382.33 18-AUG-21:19 24.63 17.59
September 0.429608E+11 29533.41 24-SEP-05:49 10.10 8.60 0.186930E+11 11877.98 30-SEP-01:19 10.77 9.56
October 0.407689E+11 33464.25 27-OCT-23:56 7.20 3.22 0.192611E+11 13050.36 18-OCT-02:20 7.20 3.22
November 0.354442E+11 33893.19 08-NOV-00:14 7.23 6.45 0.184934E+11 12879.62 17-NOV-05:00 7.80 7.25
December 0.344197E+11 36836.00 04-DEC-07:51 6.10 5.88 0.189760E+11 12232.31 01-DEC-04:10 6.10 5.88
                     
Annual Sum or Average 0.476155E+12         0.226004E+12        
Minimum of Months 0.300271E+11 24697.35   4.90 2.49 0.170316E+11 11373.57   4.90 3.22
Maximum of Months 0.481493E+11 37418.61   30.90 23.99 0.193879E+11 13247.35   25.60 23.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.475666E+11 37092.77 13-JAN-11:31 8.13 5.29 0.188025E+11 11389.25 21-JAN-18:49 7.20 6.67
February 0.431879E+11 37795.65 20-FEB-16:28 6.95 4.30 0.169760E+11 11364.18 01-FEB-18:40 6.95 4.30
March 0.504840E+11 35628.44 20-MAR-14:44 6.28 4.42 0.188399E+11 11548.82 04-MAR-18:49 6.28 4.42
April 0.511193E+11 36060.19 14-APR-18:06 7.12 4.88 0.182442E+11 11502.40 01-APR-17:40 7.12 4.88
May 0.556776E+11 33442.29 02-MAY-05:34 8.70 5.33 0.188510E+11 11319.66 13-MAY-17:19 13.53 8.09
June 0.560728E+11 32294.09 22-JUN-18:10 28.72 17.28 0.182575E+11 11319.55 10-JUN-17:19 28.72 17.28
July 0.592137E+11 31754.58 09-JUL-10:40 29.60 25.14 0.188634E+11 11319.69 15-JUL-17:19 25.93 22.25
August 0.594605E+11 33074.50 22-AUG-15:18 29.80 17.39 0.188714E+11 11319.69 19-AUG-17:19 29.80 17.39
September 0.549507E+11 32120.82 01-SEP-17:01 27.80 17.38 0.182473E+11 11319.56 30-SEP-17:19 17.77 12.98
October 0.542354E+11 37457.77 29-OCT-08:62 6.88 3.93 0.188465E+11 11384.96 28-OCT-17:00 6.88 3.93
November 0.486031E+11 37266.73 29-NOV-10:49 7.12 4.21 0.182242E+11 11390.20 18-NOV-18:30 7.12 4.21
December 0.483993E+11 39688.05 04-DEC-07:51 6.10 5.88 0.188126E+11 11483.47 16-DEC-18:19 5.97 2.30
                     
Annual Sum or Average 0.628971E+12         0.221837E+12        
Minimum of Months 0.431879E+11 31754.58   6.10 3.93 0.169760E+11 11319.55   5.97 2.30
Maximum of Months 0.594605E+11 39688.05   29.80 25.14 0.188714E+11 11548.82   29.80 22.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.241491E+10 5291.61 22-JAN-22:52 6.10 5.88 0.127023E+10 775.74 19-JAN-23:19 6.10 5.88
February 0.243152E+10 6089.07 20-FEB-16:07 7.12 4.40 0.114902E+10 755.77 01-FEB-22:10 7.12 4.40
March 0.570363E+10 6621.16 12-MAR-00:37 7.20 4.85 0.129931E+10 834.47 28-MAR-21:30 8.05 5.61
April 0.741731E+10 6682.92 11-APR-06:16 6.47 1.88 0.131403E+10 909.41 07-APR-21:40 6.47 1.88
May 0.955909E+10 5579.20 01-MAY-01:13 9.20 6.54 0.145858E+10 983.06 31-MAY-21:40 20.13 17.44
June 0.108524E+11 6416.37 01-JUN-13:50 28.30 17.32 0.155579E+10 1007.39 19-JUN-21:19 28.53 20.50
July 0.122025E+11 6899.70 08-JUL-12:00 32.20 26.10 0.166028E+10 1007.40 11-JUL-22:10 22.62 17.84
August 0.125053E+11 7071.84 16-AUG-12:50 31.93 25.44 0.166845E+10 1007.39 14-AUG-21:19 31.93 25.44
September 0.103667E+11 6376.91 01-SEP-14:10 31.02 17.36 0.150535E+10 1007.40 01-SEP-21:10 26.60 18.09
October 0.924311E+10 6712.13 08-OCT-23:16 6.83 3.54 0.143772E+10 939.57 05-OCT-21:40 6.83 3.54
November 0.548145E+10 6080.84 29-NOV-10:49 7.12 4.21 0.125242E+10 829.77 03-NOV-21:40 7.12 4.21
December 0.336725E+10 6197.36 04-DEC-07:51 6.10 5.88 0.127128E+10 766.06 04-DEC-23:10 8.22 7.50
                     
Annual Sum or Average 0.915452E+11         0.168425E+11        
Minimum of Months 0.241491E+10 5291.61   6.10 1.88 0.114902E+10 755.77   6.10 1.88
Maximum of Months 0.125053E+11 7071.84   32.20 26.10 0.166845E+10 1007.40   31.93 25.44



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 84401.29 222.93 27-MAR-05:07 7.88
April 928925.95 670.76 24-APR-05:08 7.98
May 2416530.36 920.56 15-MAY-02:00 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 3429857.60      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 2416530.36 920.56   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.519779E+09 1366.27 02-JAN-07:20 -11.5
February 0.362028E+09 1349.01 06-FEB-05:00 -13.3
March 63404407.64 1171.87 30-MAR-17:38 6.30
April 15498566.69 549.13 17-APR-23:19 7.80
May 4579232.70 502.01 15-MAY-02:30 7.75
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 68007.62 378.56 24-SEP-05:47 10.10
October 5743332.64 545.67 07-OCT-05:56 8.30
November 60854068.12 612.17 23-NOV-06:00 -3.9
December 0.227033E+09 738.69 31-DEC-06:00 -1.7
         
Annual Sum or Average 0.125899E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.519779E+09 1366.27   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 624116.52 166.26 03-JAN-08:45 8.22
February 627466.86 208.44 28-FEB-09:59 7.20
March 635823.65 173.52 01-MAR-07:40 6.67
April 592251.62 150.42 21-APR-14:25 7.20
May 1647.83 5.07 02-MAY-02:15 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 44560.08 65.88 09-OCT-07:32 7.40
November 1560295.88 250.76 26-NOV-06:27 8.60
December 569957.45 202.65 25-DEC-06:25 8.60
         
Annual Sum or Average 4656119.88      
Minimum of Months 0.00 0.00   6.67
Maximum of Months 1560295.88 250.76   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.174018E+09 634.57 02-JAN-05:00 -12.2
February 0.189256E+09 591.00 07-FEB-05:00 -8.9
March 8256961.06 250.28 02-MAR-07:22 6.40
April 3719804.58 234.67 23-APR-05:57 8.30
May 877466.69 149.47 02-MAY-02:15 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 1349.34 15.74 24-SEP-05:47 10.10
October 1215678.87 157.09 29-OCT-08:37 7.43
November 9500964.30 282.73 26-NOV-06:43 8.40
December 9986966.16 261.66 25-DEC-06:25 8.60
         
Annual Sum or Average 0.396833E+09      
Minimum of Months 0.00 0.00   -12.2
Maximum of Months 0.189256E+09 634.57   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.296600E+09 572.06 02-JAN-05:00 -12.2
February 0.289436E+09 560.24 06-FEB-05:00 -13.3
March 25816715.34 200.48 17-MAR-12:30 -1.1
April 3413398.91 167.70 24-APR-05:08 7.98
May 906118.17 125.95 02-MAY-02:15 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 3983.42 46.47 24-SEP-05:47 10.10
October 1553331.87 135.09 09-OCT-07:32 7.40
November 31276188.20 193.85 23-NOV-05:50 -3.9
December 67719069.31 320.70 31-DEC-18:00 -5.0
         
Annual Sum or Average 0.716725E+09      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.296600E+09 572.06   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 207740.35 1049.09 03-MAR-04:47 8.40
April 51583.89 728.15 11-APR-01:30 8.85
May 440548.92 854.04 15-MAY-02:30 7.75
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 1372020.87 2065.57 07-OCT-03:39 9.07
November 1276772.41 1766.22 03-NOV-03:09 9.32
December 254439.73 1790.15 01-DEC-03:38 7.63
         
Annual Sum or Average 3603106.17      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 1372020.87 2065.57   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 12140283.18 965.83 13-JAN-09:03 6.88
February 1767012.35 1360.24 28-FEB-09:59 7.20
March 5247786.52 1329.27 01-MAR-07:40 6.67
April 6151060.87 1379.48 18-APR-07:58 6.70
May 66498.01 314.37 14-MAY-05:05 8.48
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 1456630.75 1235.88 27-OCT-07:00 6.10
November 8233083.55 1727.65 13-NOV-09:02 6.78
December 2728737.14 1267.20 04-DEC-09:08 7.20
         
Annual Sum or Average 37791092.38      
Minimum of Months 0.00 0.00   6.10
Maximum of Months 12140283.18 1727.65   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5859169.72 2696.56 09-JAN-15:30 7.10
February 4516522.24 4132.43 28-FEB-09:59 7.20
March 2739542.63 2168.51 01-MAR-07:40 6.67
April 3733702.02 2418.42 21-APR-14:25 7.20
May 0.00 0.00 01-MAY-00:03 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 19831.13 330.52 09-OCT-07:32 7.40
November 6446751.71 2734.06 26-NOV-06:09 8.80
December 1371525.40 1587.79 25-DEC-06:25 8.60
         
Annual Sum or Average 24687044.84      
Minimum of Months 0.00 0.00   6.67
Maximum of Months 6446751.71 4132.43   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122936E+10 1723.61 14-JAN-16:13 -6.1
February 0.100604E+10 1694.24 06-FEB-19:02 -8.2
March 0.439549E+09 1683.65 05-MAR-16:01 7.12
April 0.171012E+09 1639.53 20-APR-08:61 7.20
May 7113495.76 1081.47 09-MAY-21:54 18.30
June 402643.71 702.91 07-JUN-21:54 22.80
July 240823.21 725.44 14-JUL-06:24 25.25
August 93209.83 515.05 08-AUG-08:54 23.30
September 1243509.21 865.63 24-SEP-08:03 14.08
October 23962404.32 1030.20 31-OCT-15:02 13.30
November 0.510009E+09 1708.90 28-NOV-16:01 9.32
December 0.952246E+09 1687.10 07-DEC-19:11 4.80
         
Annual Sum or Average 0.434127E+10      
Minimum of Months 93209.83 515.05   -8.2
Maximum of Months 0.122936E+10 1723.61   25.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147069E+10 1721.89 12-JAN-19:01 5.78
February 0.130491E+10 1716.38 06-FEB-09:13 -11.8
March 0.575908E+09 1684.63 05-MAR-16:01 7.12
April 0.202044E+09 1641.49 20-APR-08:61 7.20
May 7946853.25 1163.59 17-MAY-08:53 18.30
June 425647.18 686.53 07-JUN-21:54 22.80
July 167776.94 597.97 18-JUL-08:04 24.32
August 185279.01 651.93 20-AUG-08:54 21.70
September 1463363.95 986.56 28-SEP-08:53 20.60
October 52285283.39 1614.50 18-OCT-08:61 7.38
November 0.672577E+09 1717.33 20-NOV-19:01 5.03
December 0.120626E+10 1686.98 07-DEC-19:11 4.80
         
Annual Sum or Average 0.549486E+10      
Minimum of Months 167776.94 597.97   -11.8
Maximum of Months 0.147069E+10 1721.89   24.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 68882987.28 238.62 02-JAN-05:00 -12.2
February 17632035.30 184.76 07-FEB-06:00 -9.4
March 1721039.18 90.33 01-MAR-06:00 3.90
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:03 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 241154.61 29.60 29-NOV-05:00 3.90
December 22197922.45 167.68 31-DEC-06:00 -1.7
         
Annual Sum or Average 0.110675E+09      
Minimum of Months 0.00 0.00   -12.2
Maximum of Months 68882987.28 238.62   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204771E+09 499.37 02-JAN-16:02 -6.0
February 0.205283E+09 497.32 07-FEB-16:02 -4.0
March 40718404.01 481.10 16-MAR-15:02 0.68
April 2616141.22 467.84 06-APR-15:03 16.93
May 863283.69 369.47 03-MAY-15:07 15.92
June 47925.05 177.08 04-JUN-08:56 23.30
July 28667.76 151.72 14-JUL-08:07 27.98
August 81140.05 132.30 07-AUG-18:07 24.35
September 553896.23 369.40 12-SEP-06:15 16.10
October 1108742.66 440.54 31-OCT-15:02 13.30
November 47939297.25 486.66 24-NOV-16:02 1.20
December 0.128045E+09 492.26 31-DEC-16:02 -3.1
         
Annual Sum or Average 0.632056E+09      
Minimum of Months 28667.76 132.30   -6.0
Maximum of Months 0.205283E+09 499.37   27.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121942E+10 1683.08 14-JAN-16:13 -6.1
February 0.979980E+09 1654.54 23-FEB-19:01 5.00
March 0.467509E+09 1652.82 05-MAR-16:01 7.12
April 0.175182E+09 1601.20 20-APR-08:61 7.20
May 7635868.84 764.32 05-MAY-18:33 14.27
June 278437.34 636.62 07-JUN-21:54 22.80
July 41553.96 232.12 22-JUL-21:54 23.90
August 60706.12 265.95 27-AUG-21:55 22.20
September 790683.93 758.32 24-SEP-19:44 15.60
October 26618659.98 881.54 09-OCT-18:03 11.28
November 0.478470E+09 1667.34 28-NOV-16:01 9.32
December 0.939914E+09 1639.85 07-DEC-19:11 4.80
         
Annual Sum or Average 0.429590E+10      
Minimum of Months 41553.96 232.12   -6.1
Maximum of Months 0.121942E+10 1683.08   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.145172E+10 1677.92 14-JAN-16:13 -6.1
February 0.126486E+10 1661.11 06-FEB-16:13 -7.0
March 0.606178E+09 1653.69 05-MAR-16:01 7.12
April 0.204975E+09 1602.81 20-APR-08:61 7.20
May 8716523.12 998.80 09-MAY-21:54 18.30
June 280927.24 620.44 07-JUN-21:54 22.80
July 31011.14 179.70 22-JUL-21:54 23.90
August 62234.24 250.34 06-AUG-21:55 20.00
September 1094603.64 882.15 27-SEP-21:53 19.40
October 54935825.22 1555.59 28-OCT-18:01 8.22
November 0.614062E+09 1666.78 28-NOV-16:01 9.32
December 0.116654E+10 1647.42 26-DEC-16:01 8.12
         
Annual Sum or Average 0.537345E+10      
Minimum of Months 31011.14 179.70   -7.0
Maximum of Months 0.145172E+10 1677.92   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107007E+09 882.89 14-JAN-16:17 -6.1
February 55692345.08 684.00 06-FEB-07:05 -13.2
March 13910172.15 550.29 02-MAR-07:22 6.40
April 8924301.89 509.94 23-APR-05:57 8.30
May 2096626.45 345.45 02-MAY-02:15 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 10952.18 127.78 24-SEP-05:47 10.10
October 2874790.89 349.53 31-OCT-08:35 7.93
November 17126053.16 596.49 26-NOV-06:43 8.40
December 35358914.27 550.10 25-DEC-06:25 8.60
         
Annual Sum or Average 0.243001E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.107007E+09 882.89   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.170891E+10 2021.32 14-JAN-16:13 -6.1
February 0.142637E+10 1995.30 06-FEB-19:13 -8.1
March 0.682328E+09 1973.99 05-MAR-16:01 7.12
April 0.295410E+09 1919.52 20-APR-08:61 7.20
May 21802942.86 1262.17 17-MAY-08:53 18.30
June 355800.91 650.92 06-JUN-08:54 17.20
July 268842.45 675.82 18-JUL-08:04 24.32
August 111445.56 883.08 01-AUG-06:54 25.60
September 2663456.22 859.20 20-SEP-08:53 18.30
October 73633344.41 1855.72 18-OCT-08:61 7.38
November 0.783314E+09 1984.36 20-NOV-19:01 5.03
December 0.137056E+10 1963.67 07-DEC-19:11 4.80
         
Annual Sum or Average 0.636572E+10      
Minimum of Months 111445.56 650.92   -8.1
Maximum of Months 0.170891E+10 2021.32   25.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.199976E+10 2013.55 14-JAN-16:13 -6.1
February 0.178209E+10 2011.44 06-FEB-09:13 -11.8
March 0.858524E+09 1968.29 05-MAR-16:01 7.12
April 0.340239E+09 1921.20 04-APR-08:61 7.57
May 23816511.70 1084.27 17-MAY-08:53 18.30
June 368125.59 687.53 06-JUN-08:54 17.20
July 294612.21 730.56 18-JUL-08:04 24.32
August 300775.70 581.52 23-AUG-08:54 22.80
September 3297666.43 1151.13 10-SEP-08:53 20.00
October 0.134908E+09 1909.99 18-OCT-08:61 7.38
November 0.100515E+10 1976.66 20-NOV-19:01 5.03
December 0.168426E+10 1967.13 04-DEC-09:01 7.20
         
Annual Sum or Average 0.783301E+10      
Minimum of Months 294612.21 581.52   -11.8
Maximum of Months 0.199976E+10 2013.55   24.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.524461E+09 1049.19 14-JAN-16:13 -6.1
February 0.374320E+09 1016.55 27-FEB-16:13 0.60
March 0.175269E+09 1015.34 05-MAR-16:01 7.12
April 74086968.02 986.28 21-APR-15:02 7.30
May 2865050.81 479.35 07-MAY-08:04 12.88
June 318622.27 453.78 07-JUN-21:54 22.80
July 165146.83 443.66 18-JUL-08:04 24.32
August 106770.16 265.04 13-AUG-06:54 25.00
September 405412.84 334.37 17-SEP-21:55 18.90
October 4310768.99 400.08 28-OCT-18:03 8.22
November 0.150483E+09 1023.21 28-NOV-16:01 9.32
December 0.366380E+09 1018.21 11-DEC-16:13 1.10
         
Annual Sum or Average 0.167317E+10      
Minimum of Months 106770.16 265.04   -6.1
Maximum of Months 0.524461E+09 1049.19   25.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:03 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:03 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:03 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.447936E+09 2474.02 02-JAN-07:10 -11.6
February 0.355129E+09 2424.26 06-FEB-07:10 -13.2
March 28580263.37 1073.63 02-MAR-07:22 6.40
April 18148947.47 1041.72 24-APR-05:08 7.98
May 5062104.42 724.68 01-MAY-05:49 7.02
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 45833.50 486.83 24-SEP-05:47 10.10
October 10914784.52 1004.36 09-OCT-07:32 7.40
November 52507631.17 1174.33 26-NOV-07:17 8.50
December 39976797.35 1151.16 04-DEC-07:54 6.10
         
Annual Sum or Average 0.958301E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.447936E+09 2474.02   23.90



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160421E+11 15451.75 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.144845E+11 15451.75 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.160915E+11 15451.75 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.154982E+11 15451.75 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.160699E+11 15451.75 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.155692E+11 15451.75 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.159988E+11 15451.75 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.160977E+11 15451.75 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.155043E+11 15451.75 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.160359E+11 15451.75 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.155569E+11 15451.75 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.159988E+11 15451.75 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.188948E+12     0.143105E+12    
Minimum of Months 0.144845E+11 15451.75   0.109726E+11 9632.53  
Maximum of Months 0.160977E+11 15451.75   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.743719E+09 716.35 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.671510E+09 716.35 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.746011E+09 716.35 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.718503E+09 716.35 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.745008E+09 716.35 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.721798E+09 716.35 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.741713E+09 716.35 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.746298E+09 716.35 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.718790E+09 716.35 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.743432E+09 716.35 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.721225E+09 716.35 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.741713E+09 716.35 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.875972E+10     0.101856E+11    
Minimum of Months 0.671510E+09 716.35   0.780982E+09 685.60  
Maximum of Months 0.746298E+09 716.35   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.861229E+09 829.54 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.777612E+09 829.54 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.863884E+09 829.54 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.832029E+09 829.54 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.862722E+09 829.54 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.835845E+09 829.54 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.858907E+09 829.54 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.864216E+09 829.54 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.832361E+09 829.54 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.860897E+09 829.54 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.835182E+09 829.54 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.858907E+09 829.54 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.101438E+11     0.117950E+11    
Minimum of Months 0.777612E+09 829.54   0.904380E+09 793.93  
Maximum of Months 0.864216E+09 829.54   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.693793E+09 668.27 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.626432E+09 668.27 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.695932E+09 668.27 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.670270E+09 668.27 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.694996E+09 668.27 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.673344E+09 668.27 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.691922E+09 668.27 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.696199E+09 668.27 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.670538E+09 668.27 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.693526E+09 668.27 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.672810E+09 668.27 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.691922E+09 668.27 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.817168E+10     0.124712E+11    
Minimum of Months 0.626432E+09 668.27   0.956227E+09 839.45  
Maximum of Months 0.696199E+09 668.27   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.351983E+09 339.04 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.317809E+09 339.04 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.353068E+09 339.04 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.340049E+09 339.04 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.352593E+09 339.04 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.341609E+09 339.04 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.351034E+09 339.04 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.353204E+09 339.04 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.340185E+09 339.04 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.351847E+09 339.04 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.341337E+09 339.04 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.351034E+09 339.04 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.414575E+10     0.359760E+10    
Minimum of Months 0.317809E+09 339.04   0.275845E+09 242.16  
Maximum of Months 0.353204E+09 339.04   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.470933E+09 453.60 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.425209E+09 453.60 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.472384E+09 453.60 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.454966E+09 453.60 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.471749E+09 453.60 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.457052E+09 453.60 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.469662E+09 453.60 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.472566E+09 453.60 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.455147E+09 453.60 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.470751E+09 453.60 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.456689E+09 453.60 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.469662E+09 453.60 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.554677E+10     0.679355E+11    
Minimum of Months 0.425209E+09 453.60   0.520895E+10 4572.80  
Maximum of Months 0.472566E+09 453.60   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.157343E+10 1957.67 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.134590E+10 1957.67 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.141307E+10 1957.67 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.127013E+10 1957.67 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.119290E+10 1957.67 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.111610E+10 1957.67 01-JUN-19:19 0.118076E+10 965.27 01-JUN-19:10
July 0.115878E+10 1957.67 03-JUL-19:19 0.121533E+10 965.27 03-JUL-19:10
August 0.126152E+10 1957.67 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.132661E+10 1957.67 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.147152E+10 1957.67 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.147684E+10 1957.67 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.156046E+10 1957.67 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.161673E+11     0.143405E+11    
Minimum of Months 0.111610E+10 1957.67   0.109956E+10 965.27  
Maximum of Months 0.157343E+10 1957.67   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.854278E+10 8554.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.765077E+10 8554.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.844468E+10 8554.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.807461E+10 8554.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.827696E+10 8554.32 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.799539E+10 8554.32 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.822877E+10 8554.32 03-JUL-19:19 0.126273E+11 10029.21 03-JUL-19:10
August 0.833614E+10 8554.32 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.811350E+10 8554.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.845204E+10 8554.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.823893E+10 8554.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.850879E+10 8554.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.988634E+11     0.148998E+12    
Minimum of Months 0.765077E+10 8554.32   0.114244E+11 10029.21  
Maximum of Months 0.854278E+10 8554.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232348E+09 210.22 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.209833E+09 210.22 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.230501E+09 210.22 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.225120E+09 210.22 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.231424E+09 210.22 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.223334E+09 210.22 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.233241E+09 210.22 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.230501E+09 210.22 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.225181E+09 210.22 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.232318E+09 210.22 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.224227E+09 210.22 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.233271E+09 210.22 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.273130E+10     0.261953E+10    
Minimum of Months 0.209833E+09 210.22   0.200969E+09 237.06  
Maximum of Months 0.233271E+09 210.22   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232321E+09 210.20 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.209808E+09 210.20 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.230474E+09 210.20 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.225094E+09 210.20 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.231397E+09 210.20 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.223308E+09 210.20 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.233213E+09 210.20 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.230474E+09 210.20 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.225154E+09 210.20 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.232290E+09 210.20 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.224201E+09 210.20 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.233244E+09 210.20 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.273098E+10     0.261922E+10    
Minimum of Months 0.209808E+09 210.20   0.200945E+09 237.03  
Maximum of Months 0.233244E+09 210.20   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146022E+09 132.12 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 0.131872E+09 132.12 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 0.144861E+09 132.12 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 0.141479E+09 132.12 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 0.145441E+09 132.12 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 0.140357E+09 132.12 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 0.146583E+09 132.12 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 0.144861E+09 132.12 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 0.141518E+09 132.12 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 0.146003E+09 132.12 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 0.140918E+09 132.12 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 0.146602E+09 132.12 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.171652E+10     0.256575E+10    
Minimum of Months 0.131872E+09 132.12   0.196843E+09 232.19  
Maximum of Months 0.146602E+09 132.12   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146062E+09 132.15 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.131908E+09 132.15 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.144901E+09 132.15 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.141518E+09 132.15 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.145481E+09 132.15 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.140395E+09 132.15 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.146623E+09 132.15 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.144901E+09 132.15 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.141556E+09 132.15 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.146043E+09 132.15 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.140957E+09 132.15 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.146642E+09 132.15 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.171699E+10     0.256645E+10    
Minimum of Months 0.131908E+09 132.15   0.196897E+09 232.26  
Maximum of Months 0.146642E+09 132.15   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232348E+09 210.22 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.209833E+09 210.22 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.230501E+09 210.22 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.225120E+09 210.22 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.231424E+09 210.22 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.223334E+09 210.22 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.233241E+09 210.22 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.230501E+09 210.22 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.225181E+09 210.22 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.232318E+09 210.22 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.224227E+09 210.22 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.233271E+09 210.22 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.273130E+10     0.261953E+10    
Minimum of Months 0.209833E+09 210.22   0.200969E+09 237.06  
Maximum of Months 0.233271E+09 210.22   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232321E+09 210.20 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.209808E+09 210.20 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.230474E+09 210.20 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.225094E+09 210.20 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.231397E+09 210.20 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.223308E+09 210.20 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.233213E+09 210.20 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.230474E+09 210.20 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.225154E+09 210.20 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.232290E+09 210.20 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.224201E+09 210.20 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.233244E+09 210.20 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.273098E+10     0.261922E+10    
Minimum of Months 0.209808E+09 210.20   0.200945E+09 237.03  
Maximum of Months 0.233244E+09 210.20   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.193865E+10 1867.32 02-JAN-20:10 0.00 0.00
February 0.175042E+10 1867.32 01-FEB-20:10 0.00 0.00
March 0.194462E+10 1867.32 01-MAR-20:10 0.00 0.00
April 0.187292E+10 1867.32 03-APR-19:10 0.00 0.00
May 0.194201E+10 1867.32 01-MAY-19:10 0.00 0.00
June 0.188151E+10 1867.32 01-JUN-19:10 0.00 0.00
July 0.193342E+10 1867.32 03-JUL-19:10 0.00 0.00
August 0.194537E+10 1867.32 01-AUG-19:10 0.00 0.00
September 0.187367E+10 1867.32 01-SEP-19:10 0.00 0.00
October 0.193790E+10 1867.32 02-OCT-19:10 0.00 0.00
November 0.188002E+10 1867.32 01-NOV-19:10 0.00 0.00
December 0.193342E+10 1867.32 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.228339E+11     0.00 0.00
Minimum of Months 0.175042E+10 1867.32   0.00 0.00
Maximum of Months 0.194537E+10 1867.32   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232348E+09 210.22 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.209833E+09 210.22 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.230501E+09 210.22 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.225120E+09 210.22 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.231424E+09 210.22 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.223334E+09 210.22 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.233241E+09 210.22 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.230501E+09 210.22 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.225181E+09 210.22 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.232318E+09 210.22 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.224227E+09 210.22 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.233271E+09 210.22 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.273130E+10     0.261953E+10    
Minimum of Months 0.209833E+09 210.22   0.200969E+09 237.06  
Maximum of Months 0.233271E+09 210.22   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232321E+09 210.20 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.209808E+09 210.20 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.230474E+09 210.20 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.225094E+09 210.20 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.231397E+09 210.20 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.223308E+09 210.20 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.233213E+09 210.20 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.230474E+09 210.20 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.225154E+09 210.20 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.232290E+09 210.20 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.224201E+09 210.20 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.233244E+09 210.20 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.273098E+10     0.261922E+10    
Minimum of Months 0.209808E+09 210.20   0.200945E+09 237.03  
Maximum of Months 0.233244E+09 210.20   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146062E+09 132.15 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.131908E+09 132.15 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.144901E+09 132.15 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.141518E+09 132.15 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.145481E+09 132.15 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.140395E+09 132.15 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.146623E+09 132.15 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.144901E+09 132.15 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.141556E+09 132.15 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.146043E+09 132.15 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.140957E+09 132.15 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.146642E+09 132.15 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.171699E+10     0.256645E+10    
Minimum of Months 0.131908E+09 132.15   0.196897E+09 232.26  
Maximum of Months 0.146642E+09 132.15   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.321914E+10 3437.84 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.283234E+10 3437.84 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.305205E+10 3437.84 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.283733E+10 3437.84 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.280492E+10 3437.84 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.267504E+10 3437.84 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.276440E+10 3437.84 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.287926E+10 3437.84 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.289796E+10 3437.84 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.309726E+10 3437.84 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.306532E+10 3437.84 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.322641E+10 3437.84 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.353514E+11     0.175857E+12    
Minimum of Months 0.267504E+10 3437.84   0.134904E+11 6747.90  
Maximum of Months 0.322641E+10 3437.84   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.321914E+10 3437.84 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.283234E+10 3437.84 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.305205E+10 3437.84 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.283733E+10 3437.84 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.280492E+10 3437.84 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.267504E+10 3437.84 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.276440E+10 3437.84 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.287926E+10 3437.84 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.289796E+10 3437.84 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.309726E+10 3437.84 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.306532E+10 3437.84 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.322641E+10 3437.84 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.353514E+11     0.175857E+12    
Minimum of Months 0.267504E+10 3437.84   0.134904E+11 6747.90  
Maximum of Months 0.322641E+10 3437.84   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.125718E+10 1210.92 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.113512E+10 1210.92 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.126106E+10 1210.92 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.121456E+10 1210.92 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.125936E+10 1210.92 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.122013E+10 1210.92 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.125379E+10 1210.92 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.126154E+10 1210.92 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.121504E+10 1210.92 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.125670E+10 1210.92 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.121916E+10 1210.92 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.125379E+10 1210.92 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.148074E+11     0.433742E+12    
Minimum of Months 0.113512E+10 1210.92   0.332733E+11 16487.34  
Maximum of Months 0.126154E+10 1210.92   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.205176E+10 1976.27 02-JAN-20:10 0.00 0.00
February 0.185255E+10 1976.27 01-FEB-20:10 0.00 0.00
March 0.205809E+10 1976.27 01-MAR-20:10 0.00 0.00
April 0.198220E+10 1976.27 03-APR-19:10 0.00 0.00
May 0.205532E+10 1976.27 01-MAY-19:10 0.00 0.00
June 0.199129E+10 1976.27 01-JUN-19:10 0.00 0.00
July 0.204623E+10 1976.27 03-JUL-19:10 0.00 0.00
August 0.205888E+10 1976.27 01-AUG-19:10 0.00 0.00
September 0.198299E+10 1976.27 01-SEP-19:10 0.00 0.00
October 0.205097E+10 1976.27 02-OCT-19:10 0.00 0.00
November 0.198971E+10 1976.27 01-NOV-19:10 0.00 0.00
December 0.204623E+10 1976.27 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.241662E+11     0.00 0.00
Minimum of Months 0.185255E+10 1976.27   0.00 0.00
Maximum of Months 0.205888E+10 1976.27   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.160421E+11 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.144845E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.160915E+11 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.154982E+11 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.160699E+11 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.155692E+11 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.159988E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.160977E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.155043E+11 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.160359E+11 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.155569E+11 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.159988E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.188948E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.144845E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.160977E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.743719E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.689631E+09
February 0.179968E+10 0.671510E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.665483E+09
March 0.199990E+10 0.746011E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.535978E+09
April 0.192973E+10 0.718503E+09 0.835931E+09 0.00 0.00 0.00 0.00 597174.12 0.342358E+09
May 0.199475E+10 0.745008E+09 0.865939E+09 0.00 0.00 0.00 0.00 4423271.06 0.191383E+09
June 0.193394E+10 0.721798E+09 0.838659E+09 0.00 0.00 0.00 0.00 25593841.86 53807068.99
July 0.199054E+10 0.741713E+09 0.863211E+09 0.00 0.00 0.00 0.00 67458400.90 6543567.43
August 0.199896E+10 0.746298E+09 0.866978E+09 0.00 0.00 0.00 0.00 66611364.16 21324818.64
September 0.192879E+10 0.718790E+09 0.836191E+09 0.00 0.00 0.00 0.00 10398830.72 93988204.16
October 0.199148E+10 0.743432E+09 0.864640E+09 0.00 0.00 0.00 0.00 140886.74 0.275904E+09
November 0.192552E+10 0.721225E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.457043E+09
December 0.199054E+10 0.741713E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.604947E+09
                   
Annual Sum or Average 0.234744E+11 0.875972E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.175224E+09 0.393839E+10
Minimum of Months 0.179968E+10 0.671510E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 6543567.43
Maximum of Months 0.199990E+10 0.746298E+09 0.866978E+09 0.00 0.00 0.00 0.00 67458400.90 0.689631E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.861229E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.270675E+09
February 0.208403E+10 0.777612E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.260590E+09
March 0.231589E+10 0.863884E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.216192E+09
April 0.223463E+10 0.832029E+09 0.968011E+09 0.00 0.00 0.00 0.00 358062.76 0.144458E+09
May 0.230993E+10 0.862722E+09 0.100276E+10 0.00 0.00 0.00 0.00 1903727.48 88564798.72
June 0.223950E+10 0.835845E+09 0.971170E+09 0.00 0.00 0.00 0.00 9525066.32 30908122.82
July 0.230505E+10 0.858907E+09 0.999601E+09 0.00 0.00 0.00 0.00 23330497.66 6974214.36
August 0.231480E+10 0.864216E+09 0.100396E+10 0.00 0.00 0.00 0.00 24998733.55 13075996.96
September 0.223354E+10 0.832361E+09 0.968312E+09 0.00 0.00 0.00 0.00 4109307.79 46300989.38
October 0.230614E+10 0.860897E+09 0.100126E+10 0.00 0.00 0.00 0.00 140922.55 0.117134E+09
November 0.222975E+10 0.835182E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.186508E+09
December 0.230505E+10 0.858907E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.239982E+09
                   
Annual Sum or Average 0.271834E+11 0.101438E+11 0.117950E+11 0.00 0.00 0.00 0.00 64366318.10 0.162136E+10
Minimum of Months 0.208403E+10 0.777612E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 6974214.36
Maximum of Months 0.231589E+10 0.864216E+09 0.100396E+10 0.00 0.00 0.00 0.00 24998733.55 0.270675E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.693793E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.624450E+09
February 0.440737E+09 0.626432E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.599714E+09
March 0.489771E+09 0.695932E+09 0.106120E+10 0.00 0.00 0.00 0.00 19899.64 0.481554E+09
April 0.472586E+09 0.670270E+09 0.102351E+10 0.00 0.00 0.00 0.00 1302418.32 0.315368E+09
May 0.488511E+09 0.694996E+09 0.106025E+10 0.00 0.00 0.00 0.00 4857820.35 0.193441E+09
June 0.473617E+09 0.673344E+09 0.102685E+10 0.00 0.00 0.00 0.00 22190597.92 68851919.67
July 0.487480E+09 0.691922E+09 0.105691E+10 0.00 0.00 0.00 0.00 53048091.03 15588603.27
August 0.489542E+09 0.696199E+09 0.106152E+10 0.00 0.00 0.00 0.00 58249630.32 29722327.53
September 0.472357E+09 0.670538E+09 0.102382E+10 0.00 0.00 0.00 0.00 9992449.03 0.102512E+09
October 0.487709E+09 0.693526E+09 0.105866E+10 0.00 0.00 0.00 0.00 641651.91 0.254462E+09
November 0.471555E+09 0.672810E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.417079E+09
December 0.487480E+09 0.691922E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.544779E+09
                   
Annual Sum or Average 0.574883E+10 0.817168E+10 0.124712E+11 0.00 0.00 0.00 0.00 0.150303E+09 0.364752E+10
Minimum of Months 0.440737E+09 0.626432E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 15588603.27
Maximum of Months 0.489771E+09 0.696199E+09 0.106152E+10 0.00 0.00 0.00 0.00 58249630.32 0.624450E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.351983E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.359883E+09
February 0.339028E+09 0.317809E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.345793E+09
March 0.376747E+09 0.353068E+09 0.306128E+09 0.00 0.00 0.00 0.00 14238.69 0.275773E+09
April 0.363528E+09 0.340049E+09 0.295253E+09 0.00 0.00 0.00 0.00 804361.99 0.177811E+09
May 0.375778E+09 0.352593E+09 0.305852E+09 0.00 0.00 0.00 0.00 3041829.13 0.106217E+09
June 0.364321E+09 0.341609E+09 0.296217E+09 0.00 0.00 0.00 0.00 13855105.90 35737661.44
July 0.374985E+09 0.351034E+09 0.304889E+09 0.00 0.00 0.00 0.00 32982490.64 7206799.39
August 0.376571E+09 0.353204E+09 0.306219E+09 0.00 0.00 0.00 0.00 35688097.13 15069582.09
September 0.363352E+09 0.340185E+09 0.295345E+09 0.00 0.00 0.00 0.00 6552475.68 54344751.23
October 0.375161E+09 0.351847E+09 0.305393E+09 0.00 0.00 0.00 0.00 458773.64 0.140598E+09
November 0.362735E+09 0.341337E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.237154E+09
December 0.374985E+09 0.351034E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.313756E+09
                   
Annual Sum or Average 0.442217E+10 0.414575E+10 0.359760E+10 0.00 0.00 0.00 0.00 93397372.80 0.206934E+10
Minimum of Months 0.339028E+09 0.317809E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 7206799.39
Maximum of Months 0.376747E+09 0.353204E+09 0.306219E+09 0.00 0.00 0.00 0.00 35688097.13 0.359883E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.470933E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.934112E+09
February 0.139600E+10 0.425209E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.891514E+09
March 0.155131E+10 0.472384E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.737124E+09
April 0.149688E+10 0.454966E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 1265446.69 0.489822E+09
May 0.154732E+10 0.471749E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 6674721.66 0.292815E+09
June 0.150015E+10 0.457052E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 35721956.21 90187390.11
July 0.154405E+10 0.469662E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 90909475.48 15687836.14
August 0.155059E+10 0.472566E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 97365580.72 33227395.80
September 0.149615E+10 0.455147E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 18066498.43 0.141506E+09
October 0.154478E+10 0.470751E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 822762.41 0.374817E+09
November 0.149361E+10 0.456689E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.638045E+09
December 0.154405E+10 0.469662E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.825773E+09
                   
Annual Sum or Average 0.182090E+11 0.554677E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.250826E+09 0.546463E+10
Minimum of Months 0.139600E+10 0.425209E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 15687836.14
Maximum of Months 0.155131E+10 0.472566E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 97365580.72 0.934112E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.157343E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.156001E+10
February 0.236489E+11 0.134590E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.150928E+10
March 0.262800E+11 0.141307E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.125010E+10
April 0.253579E+11 0.127013E+10 0.117692E+10 0.00 0.00 0.00 0.00 1210872.00 0.827759E+09
May 0.262123E+11 0.119290E+10 0.121917E+10 0.00 0.00 0.00 0.00 9127753.12 0.501631E+09
June 0.254132E+11 0.111610E+10 0.118076E+10 0.00 0.00 0.00 0.00 52810080.60 0.168688E+09
July 0.261570E+11 0.115878E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.134950E+09 37775769.88
August 0.262677E+11 0.126152E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.139272E+09 71394605.11
September 0.253456E+11 0.132661E+10 0.117729E+10 0.00 0.00 0.00 0.00 21377712.16 0.264681E+09
October 0.261693E+11 0.147152E+10 0.121734E+10 0.00 0.00 0.00 0.00 329380.44 0.684621E+09
November 0.253025E+11 0.147684E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.107415E+10
December 0.261570E+11 0.156046E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.138397E+10
                   
Annual Sum or Average 0.308468E+12 0.161673E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.359077E+09 0.933405E+10
Minimum of Months 0.236489E+11 0.111610E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 37775769.88
Maximum of Months 0.262800E+11 0.157343E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.139272E+09 0.156001E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.854278E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.454029E+10
February 0.702046E+11 0.765077E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.436881E+10
March 0.780153E+11 0.844468E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.364335E+10
April 0.752779E+11 0.807461E+10 0.122282E+11 0.00 0.00 0.00 0.00 4651852.15 0.244535E+10
May 0.778146E+11 0.827696E+10 0.126672E+11 0.00 0.00 0.00 0.00 29134147.44 0.151309E+10
June 0.754422E+11 0.799539E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.153795E+09 0.526016E+09
July 0.776503E+11 0.822877E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.381595E+09 0.121659E+09
August 0.779788E+11 0.833614E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.404539E+09 0.218324E+09
September 0.752414E+11 0.811350E+10 0.122320E+11 0.00 0.00 0.00 0.00 62964756.14 0.796764E+09
October 0.776868E+11 0.845204E+10 0.126482E+11 0.00 0.00 0.00 0.00 1389848.44 0.199146E+10
November 0.751137E+11 0.823893E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.316085E+10
December 0.776503E+11 0.850879E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.404269E+10
                   
Annual Sum or Average 0.915726E+12 0.988634E+11 0.148998E+12 0.00 0.00 0.00 0.00 0.103807E+10 0.273687E+11
Minimum of Months 0.702046E+11 0.765077E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.121659E+09
Maximum of Months 0.780153E+11 0.854278E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.404539E+09 0.454029E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232348E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.392511E+09
February 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.379697E+09
March 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.306703E+09
April 0.293479E+09 0.225120E+09 0.215344E+09 0.00 0.00 0.00 0.00 617233.83 0.198374E+09
May 0.303504E+09 0.231424E+09 0.222446E+09 0.00 0.00 0.00 0.00 3116588.79 0.118709E+09
June 0.293842E+09 0.223334E+09 0.215230E+09 0.00 0.00 0.00 0.00 19729367.75 39630568.63
July 0.303141E+09 0.233241E+09 0.222560E+09 0.00 0.00 0.00 0.00 55773822.83 5221110.98
August 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 58122893.90 12058983.76
September 0.293479E+09 0.225181E+09 0.215344E+09 0.00 0.00 0.00 0.00 10475964.15 57664265.69
October 0.303322E+09 0.232318E+09 0.222503E+09 0.00 0.00 0.00 0.00 231131.94 0.154525E+09
November 0.293661E+09 0.224227E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.260007E+09
December 0.303141E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.343606E+09
                   
Annual Sum or Average 0.357224E+10 0.273130E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.148067E+09 0.226871E+10
Minimum of Months 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 5221110.98
Maximum of Months 0.303685E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 58122893.90 0.392511E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232321E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.388949E+09
February 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.375123E+09
March 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.302102E+09
April 0.293479E+09 0.225094E+09 0.215319E+09 0.00 0.00 0.00 0.00 670130.98 0.195909E+09
May 0.303504E+09 0.231397E+09 0.222420E+09 0.00 0.00 0.00 0.00 3128416.32 0.117777E+09
June 0.293842E+09 0.223308E+09 0.215205E+09 0.00 0.00 0.00 0.00 19750072.92 39442006.96
July 0.303141E+09 0.233213E+09 0.222534E+09 0.00 0.00 0.00 0.00 55802036.66 5186566.69
August 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 58294894.30 11561952.15
September 0.293479E+09 0.225154E+09 0.215319E+09 0.00 0.00 0.00 0.00 10572031.40 54940957.39
October 0.303322E+09 0.232290E+09 0.222477E+09 0.00 0.00 0.00 0.00 278524.05 0.149553E+09
November 0.293661E+09 0.224201E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.255626E+09
December 0.303141E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.339012E+09
                   
Annual Sum or Average 0.357224E+10 0.273098E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.148496E+09 0.223518E+10
Minimum of Months 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 5186566.69
Maximum of Months 0.303685E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 58294894.30 0.388949E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.146022E+09 0.217935E+09 0.00 0.00 0.00 0.00 0.00 0.104271E+09
February 0.00 0.131872E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 0.104834E+09
March 0.00 0.144861E+09 0.217824E+09 0.00 0.00 0.00 0.00 0.00 87689947.13
April 0.00 0.141479E+09 0.210923E+09 0.00 0.00 0.00 0.00 122033.08 58494106.27
May 0.00 0.145441E+09 0.217879E+09 0.00 0.00 0.00 0.00 689787.57 37433197.89
June 0.00 0.140357E+09 0.210812E+09 0.00 0.00 0.00 0.00 3964057.81 12043042.49
July 0.00 0.146583E+09 0.217991E+09 0.00 0.00 0.00 0.00 10545860.70 2130342.83
August 0.00 0.144861E+09 0.217824E+09 0.00 0.00 0.00 0.00 11548399.20 4581106.58
September 0.00 0.141518E+09 0.210923E+09 0.00 0.00 0.00 0.00 1859037.46 18820427.21
October 0.00 0.146003E+09 0.217935E+09 0.00 0.00 0.00 0.00 46926.50 49131356.49
November 0.00 0.140918E+09 0.210867E+09 0.00 0.00 0.00 0.00 0.00 75464719.08
December 0.00 0.146602E+09 0.217991E+09 0.00 0.00 0.00 0.00 0.00 94238300.14
                   
Annual Sum or Average 0.00 0.171652E+10 0.256575E+10 0.00 0.00 0.00 0.00 28776102.31 0.649132E+09
Minimum of Months 0.00 0.131872E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 2130342.83
Maximum of Months 0.00 0.146602E+09 0.217991E+09 0.00 0.00 0.00 0.00 11548399.20 0.104834E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.146062E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.109668E+09
February 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 0.105413E+09
March 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 1113.82 84687018.17
April 0.293479E+09 0.141518E+09 0.210981E+09 0.00 0.00 0.00 0.00 250680.60 54092495.36
May 0.303504E+09 0.145481E+09 0.217939E+09 0.00 0.00 0.00 0.00 965931.88 30920844.60
June 0.293842E+09 0.140395E+09 0.210869E+09 0.00 0.00 0.00 0.00 5790130.71 8580232.72
July 0.303141E+09 0.146623E+09 0.218051E+09 0.00 0.00 0.00 0.00 16053739.10 950902.57
August 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 16885146.67 2617353.85
September 0.293479E+09 0.141556E+09 0.210981E+09 0.00 0.00 0.00 0.00 3324873.81 13541857.94
October 0.303322E+09 0.146043E+09 0.217995E+09 0.00 0.00 0.00 0.00 217965.32 39816627.66
November 0.293661E+09 0.140957E+09 0.210925E+09 0.00 0.00 0.00 0.00 0.00 72159696.05
December 0.303141E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 0.00 95765398.53
                   
Annual Sum or Average 0.357224E+10 0.171699E+10 0.256645E+10 0.00 0.00 0.00 0.00 43489581.90 0.618213E+09
Minimum of Months 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 950902.57
Maximum of Months 0.303685E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 16885146.67 0.109668E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232348E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.392305E+09
February 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.379850E+09
March 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.307327E+09
April 0.293479E+09 0.225120E+09 0.215344E+09 0.00 0.00 0.00 0.00 616157.52 0.198490E+09
May 0.303504E+09 0.231424E+09 0.222446E+09 0.00 0.00 0.00 0.00 3041541.91 0.117782E+09
June 0.293842E+09 0.223334E+09 0.215230E+09 0.00 0.00 0.00 0.00 19610232.55 37016218.32
July 0.303141E+09 0.233241E+09 0.222560E+09 0.00 0.00 0.00 0.00 55479099.55 5995037.43
August 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 57889284.39 13469589.79
September 0.293479E+09 0.225181E+09 0.215344E+09 0.00 0.00 0.00 0.00 10403215.31 56904575.46
October 0.303322E+09 0.232318E+09 0.222503E+09 0.00 0.00 0.00 0.00 233434.58 0.153377E+09
November 0.293661E+09 0.224227E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.260623E+09
December 0.303141E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.343522E+09
                   
Annual Sum or Average 0.357224E+10 0.273130E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.147273E+09 0.226666E+10
Minimum of Months 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 5995037.43
Maximum of Months 0.303685E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 57889284.39 0.392305E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232321E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.388905E+09
February 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.375163E+09
March 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 2324.98 0.302573E+09
April 0.293479E+09 0.225094E+09 0.215319E+09 0.00 0.00 0.00 0.00 622482.40 0.196472E+09
May 0.303504E+09 0.231397E+09 0.222420E+09 0.00 0.00 0.00 0.00 3045445.49 0.117379E+09
June 0.293842E+09 0.223308E+09 0.215205E+09 0.00 0.00 0.00 0.00 19610122.52 36962785.48
July 0.303141E+09 0.233213E+09 0.222534E+09 0.00 0.00 0.00 0.00 55481414.55 5960336.87
August 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 57968852.67 12983482.27
September 0.293479E+09 0.225154E+09 0.215319E+09 0.00 0.00 0.00 0.00 10483419.96 54851010.76
October 0.303322E+09 0.232290E+09 0.222477E+09 0.00 0.00 0.00 0.00 247503.91 0.148615E+09
November 0.293661E+09 0.224201E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.256199E+09
December 0.303141E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.338924E+09
                   
Annual Sum or Average 0.357224E+10 0.273098E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.147462E+09 0.223499E+10
Minimum of Months 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 5960336.87
Maximum of Months 0.303685E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 57968852.67 0.388905E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.193865E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.481069E+09
February 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.462217E+09
March 0.387034E+10 0.194462E+10 0.00 0.00 0.00 0.00 0.00 10380.10 0.370547E+09
April 0.373454E+10 0.187292E+10 0.00 0.00 0.00 0.00 0.00 937786.51 0.242032E+09
May 0.386038E+10 0.194201E+10 0.00 0.00 0.00 0.00 0.00 3507039.72 0.147059E+09
June 0.374269E+10 0.188151E+10 0.00 0.00 0.00 0.00 0.00 16977436.08 53061560.91
July 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 42792234.45 10636504.93
August 0.386853E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 45272243.04 21975247.95
September 0.373273E+10 0.187367E+10 0.00 0.00 0.00 0.00 0.00 7157586.54 77599266.20
October 0.385404E+10 0.193790E+10 0.00 0.00 0.00 0.00 0.00 379617.03 0.196753E+09
November 0.372639E+10 0.188002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.318174E+09
December 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.419677E+09
                   
Annual Sum or Average 0.454292E+11 0.228339E+11 0.00 0.00 0.00 0.00 0.00 0.117034E+09 0.280080E+10
Minimum of Months 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 0.00 10636504.93
Maximum of Months 0.387034E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 45272243.04 0.481069E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232348E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.392270E+09
February 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.379448E+09
March 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.306765E+09
April 0.293479E+09 0.225120E+09 0.215344E+09 0.00 0.00 0.00 0.00 598263.56 0.199220E+09
May 0.303504E+09 0.231424E+09 0.222446E+09 0.00 0.00 0.00 0.00 3042320.84 0.120797E+09
June 0.293842E+09 0.223334E+09 0.215230E+09 0.00 0.00 0.00 0.00 19362377.38 41374051.31
July 0.303141E+09 0.233241E+09 0.222560E+09 0.00 0.00 0.00 0.00 54934950.25 5488557.93
August 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 57358380.05 12156807.95
September 0.293479E+09 0.225181E+09 0.215344E+09 0.00 0.00 0.00 0.00 10219012.23 59123054.50
October 0.303322E+09 0.232318E+09 0.222503E+09 0.00 0.00 0.00 0.00 215987.09 0.155904E+09
November 0.293661E+09 0.224227E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.259576E+09
December 0.303141E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.343248E+09
                   
Annual Sum or Average 0.357224E+10 0.273130E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.145731E+09 0.227537E+10
Minimum of Months 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 5488557.93
Maximum of Months 0.303685E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 57358380.05 0.392270E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232321E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.389279E+09
February 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.375309E+09
March 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.302053E+09
April 0.293479E+09 0.225094E+09 0.215319E+09 0.00 0.00 0.00 0.00 635478.42 0.196696E+09
May 0.303504E+09 0.231397E+09 0.222420E+09 0.00 0.00 0.00 0.00 3048440.05 0.120055E+09
June 0.293842E+09 0.223308E+09 0.215205E+09 0.00 0.00 0.00 0.00 19373883.11 41306359.97
July 0.303141E+09 0.233213E+09 0.222534E+09 0.00 0.00 0.00 0.00 54952170.18 5455632.76
August 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 57521671.85 11601311.96
September 0.293479E+09 0.225154E+09 0.215319E+09 0.00 0.00 0.00 0.00 10309287.42 56065365.81
October 0.303322E+09 0.232290E+09 0.222477E+09 0.00 0.00 0.00 0.00 259915.86 0.150004E+09
November 0.293661E+09 0.224201E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.255211E+09
December 0.303141E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.338985E+09
                   
Annual Sum or Average 0.357224E+10 0.273098E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.146101E+09 0.224202E+10
Minimum of Months 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 5455632.76
Maximum of Months 0.303685E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 57521671.85 0.389279E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.146062E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.204449E+09
February 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 0.198117E+09
March 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 0.00 0.159160E+09
April 0.293479E+09 0.141518E+09 0.210981E+09 0.00 0.00 0.00 0.00 305502.43 0.102206E+09
May 0.303504E+09 0.145481E+09 0.217939E+09 0.00 0.00 0.00 0.00 1570651.77 59488919.60
June 0.293842E+09 0.140395E+09 0.210869E+09 0.00 0.00 0.00 0.00 9965876.57 17480775.02
July 0.303141E+09 0.146623E+09 0.218051E+09 0.00 0.00 0.00 0.00 28197283.33 2289172.98
August 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 29392035.95 5853416.70
September 0.293479E+09 0.141556E+09 0.210981E+09 0.00 0.00 0.00 0.00 5217138.43 29508929.98
October 0.303322E+09 0.146043E+09 0.217995E+09 0.00 0.00 0.00 0.00 105639.03 80178090.59
November 0.293661E+09 0.140957E+09 0.210925E+09 0.00 0.00 0.00 0.00 0.00 0.136522E+09
December 0.303141E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 0.00 0.179515E+09
                   
Annual Sum or Average 0.357224E+10 0.171699E+10 0.256645E+10 0.00 0.00 0.00 0.00 74754127.51 0.117477E+10
Minimum of Months 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 2289172.98
Maximum of Months 0.303685E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 29392035.95 0.204449E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.321914E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.108543E+10
February 0.415303E+11 0.283234E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.103506E+10
March 0.461508E+11 0.305205E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.868596E+09
April 0.445315E+11 0.283733E+10 0.144540E+11 0.00 0.00 0.00 0.00 763122.33 0.590264E+09
May 0.460320E+11 0.280492E+10 0.149358E+11 0.00 0.00 0.00 0.00 4601698.65 0.372198E+09
June 0.446286E+11 0.267504E+10 0.144540E+11 0.00 0.00 0.00 0.00 27315152.53 0.132102E+09
July 0.459349E+11 0.276440E+10 0.149358E+11 0.00 0.00 0.00 0.00 71897883.55 30555137.12
August 0.461292E+11 0.287926E+10 0.149358E+11 0.00 0.00 0.00 0.00 81793333.24 52594872.53
September 0.445099E+11 0.289796E+10 0.144540E+11 0.00 0.00 0.00 0.00 11668277.16 0.193467E+09
October 0.459565E+11 0.309726E+10 0.149358E+11 0.00 0.00 0.00 0.00 256049.32 0.463252E+09
November 0.444343E+11 0.306532E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.752717E+09
December 0.459349E+11 0.322641E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.964946E+09
                   
Annual Sum or Average 0.541708E+12 0.353514E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.198296E+09 0.654118E+10
Minimum of Months 0.415303E+11 0.267504E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 30555137.12
Maximum of Months 0.461508E+11 0.322641E+10 0.149358E+11 0.00 0.00 0.00 0.00 81793333.24 0.108543E+10



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.321914E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.109675E+10
February 0.415303E+11 0.283234E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.104530E+10
March 0.461508E+11 0.305205E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.876743E+09
April 0.445315E+11 0.283733E+10 0.144540E+11 0.00 0.00 0.00 0.00 711290.25 0.595727E+09
May 0.460320E+11 0.280492E+10 0.149358E+11 0.00 0.00 0.00 0.00 4563468.08 0.374955E+09
June 0.446286E+11 0.267504E+10 0.144540E+11 0.00 0.00 0.00 0.00 27146007.03 0.132845E+09
July 0.459349E+11 0.276440E+10 0.149358E+11 0.00 0.00 0.00 0.00 71698202.16 30592230.79
August 0.461292E+11 0.287926E+10 0.149358E+11 0.00 0.00 0.00 0.00 81393177.82 52712499.22
September 0.445099E+11 0.289796E+10 0.144540E+11 0.00 0.00 0.00 0.00 11456733.40 0.195010E+09
October 0.459565E+11 0.309726E+10 0.149358E+11 0.00 0.00 0.00 0.00 186041.91 0.467239E+09
November 0.444343E+11 0.306532E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.760452E+09
December 0.459349E+11 0.322641E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.974578E+09
                   
Annual Sum or Average 0.541708E+12 0.353514E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.197155E+09 0.660291E+10
Minimum of Months 0.415303E+11 0.267504E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 30592230.79
Maximum of Months 0.461508E+11 0.322641E+10 0.149358E+11 0.00 0.00 0.00 0.00 81393177.82 0.109675E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.125718E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.991208E+09
February 0.369574E+10 0.113512E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.943155E+09
March 0.410691E+10 0.126106E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.790365E+09
April 0.396281E+10 0.121456E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 551359.62 0.536110E+09
May 0.409635E+10 0.125936E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 3972813.52 0.333749E+09
June 0.397146E+10 0.122013E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 23898430.81 0.117451E+09
July 0.408770E+10 0.125379E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 64230818.32 26609776.37
August 0.410499E+10 0.126154E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 72231661.08 46330812.82
September 0.396089E+10 0.121504E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 10041909.37 0.172897E+09
October 0.408962E+10 0.125670E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 109137.39 0.418593E+09
November 0.395417E+10 0.121916E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.686289E+09
December 0.408770E+10 0.125379E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.879771E+09
                   
Annual Sum or Average 0.482060E+11 0.148074E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 0.175036E+09 0.594253E+10
Minimum of Months 0.369574E+10 0.113512E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 26609776.37
Maximum of Months 0.410691E+10 0.126154E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 72231661.08 0.991208E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.205176E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.854248E+09
February 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.821182E+09
March 0.409620E+10 0.205809E+10 0.00 0.00 0.00 0.00 0.00 834.42 0.660887E+09
April 0.395248E+10 0.198220E+10 0.00 0.00 0.00 0.00 0.00 1084762.15 0.432847E+09
May 0.408566E+10 0.205532E+10 0.00 0.00 0.00 0.00 0.00 4741560.28 0.264430E+09
June 0.396110E+10 0.199129E+10 0.00 0.00 0.00 0.00 0.00 26076357.68 92713826.86
July 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 67018316.34 18970293.24
August 0.409429E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 74113806.41 37332128.32
September 0.395056E+10 0.198299E+10 0.00 0.00 0.00 0.00 0.00 11249589.63 0.134573E+09
October 0.407896E+10 0.205097E+10 0.00 0.00 0.00 0.00 0.00 364703.35 0.341594E+09
November 0.394385E+10 0.198971E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.564491E+09
December 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.745922E+09
                   
Annual Sum or Average 0.480803E+11 0.241662E+11 0.00 0.00 0.00 0.00 0.00 0.184650E+09 0.496919E+10
Minimum of Months 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 0.00 18970293.24
Maximum of Months 0.409620E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 74113806.41 0.854248E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 15451.75 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 15451.75 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 15451.75 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 15451.75 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 15451.75 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 15451.75 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 15451.75 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 15451.75 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 15451.75 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 15451.75 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 15451.75 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 15451.75 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   15451.75   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   15451.75   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 716.35 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 451.83 02-JAN-05:00
February 1169.53 01-FEB-00:10 716.35 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 464.91 06-FEB-03:00
March 1169.53 01-MAR-00:10 716.35 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 343.26 23-MAR-06:00
April 1169.53 01-APR-00:10 716.35 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 31.40 08-APR-10:00 242.02 03-APR-06:00
May 1169.53 01-MAY-00:10 716.35 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 69.45 30-MAY-13:00 187.93 01-MAY-05:00
June 1169.53 01-JUN-00:10 716.35 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 142.94 19-JUN-12:00 98.56 03-JUN-03:10
July 1169.53 01-JUL-00:10 716.35 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 112.65 07-JUL-12:00 40.96 01-JUL-23:00
August 1169.53 01-AUG-00:10 716.35 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 111.87 24-AUG-15:00 79.95 08-AUG-05:00
September 1169.53 01-SEP-00:10 716.35 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 80.73 01-SEP-14:00 141.41 24-SEP-05:55
October 1169.53 01-OCT-23:10 716.35 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 11.68 04-OCT-13:00 243.49 09-OCT-06:00
November 1169.53 01-NOV-00:10 716.35 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 334.30 24-NOV-07:00
December 1169.53 01-DEC-00:10 716.35 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 389.33 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   716.35   685.60   0.00 0.00 0.00 0.00 0.00   40.96  
Maximum of Months 1169.53   716.35   685.60   0.00 0.00 0.00 0.00 142.94   464.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 829.54 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 174.66 02-JAN-05:00
February 1354.32 01-FEB-00:10 829.54 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 179.45 06-FEB-03:00
March 1354.32 01-MAR-00:10 829.54 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 136.83 23-MAR-06:00
April 1354.32 01-APR-00:10 829.54 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 17.51 07-APR-13:00 98.33 03-APR-06:00
May 1354.32 01-MAY-00:10 829.54 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 31.18 30-MAY-13:00 79.64 01-MAY-05:00
June 1354.32 01-JUN-00:10 829.54 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 58.76 19-JUN-12:00 47.82 03-JUN-03:10
July 1354.32 01-JUL-00:10 829.54 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 46.21 07-JUL-12:00 24.06 02-JUL-03:00
August 1354.32 01-AUG-00:10 829.54 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 44.41 24-AUG-15:00 40.52 08-AUG-05:00
September 1354.32 01-SEP-00:10 829.54 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 32.10 01-SEP-13:53 62.98 24-SEP-06:00
October 1354.32 01-OCT-23:10 829.54 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 9.03 25-OCT-10:55 101.79 09-OCT-06:00
November 1354.32 01-NOV-00:10 829.54 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 131.47 24-NOV-07:00
December 1354.32 01-DEC-00:10 829.54 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 152.23 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   829.54   793.93   0.00 0.00 0.00 0.00 0.00   24.06  
Maximum of Months 1354.32   829.54   793.93   0.00 0.00 0.00 0.00 58.76   179.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 668.27 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 412.78 02-JAN-05:00
February 286.42 01-FEB-00:10 668.27 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 424.10 06-FEB-03:00
March 286.42 01-MAR-00:10 668.27 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 9.68 27-MAR-15:55 313.09 23-MAR-06:00
April 286.42 01-APR-00:10 668.27 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 50.17 07-APR-13:00 220.79 03-APR-06:00
May 286.42 01-MAY-00:10 668.27 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 73.84 30-MAY-13:00 178.94 01-MAY-05:00
June 286.42 01-JUN-00:10 668.27 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 136.78 19-JUN-12:00 107.66 03-JUN-03:10
July 286.42 01-JUL-00:10 668.27 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 106.26 07-JUL-12:00 54.70 02-JUL-03:00
August 286.42 01-AUG-00:10 668.27 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 105.58 24-AUG-16:00 93.23 08-AUG-05:00
September 286.42 01-SEP-00:10 668.27 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 77.12 01-SEP-13:53 143.63 24-SEP-06:00
October 286.42 01-OCT-23:10 668.27 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 24.47 25-OCT-10:55 230.63 09-OCT-06:00
November 286.42 01-NOV-00:10 668.27 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 304.93 24-NOV-07:00
December 286.42 01-DEC-00:10 668.27 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 355.13 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   668.27   839.45   0.00 0.00 0.00 0.00 0.00   54.70  
Maximum of Months 286.42   668.27   839.45   0.00 0.00 0.00 0.00 136.78   424.10  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 339.04 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 238.15 02-JAN-05:00
February 220.32 01-FEB-00:10 339.04 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 244.68 06-FEB-03:00
March 220.32 01-MAR-00:10 339.04 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 6.17 27-MAR-15:55 180.64 23-MAR-06:00
April 220.32 01-APR-00:10 339.04 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 29.43 07-APR-13:00 127.39 03-APR-06:00
May 220.32 01-MAY-00:10 339.04 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 43.36 30-MAY-13:00 100.62 01-MAY-05:00
June 220.32 01-JUN-00:10 339.04 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 79.50 19-JUN-12:00 59.72 03-JUN-03:10
July 220.32 01-JUL-00:10 339.04 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 61.98 07-JUL-12:00 29.19 02-JUL-03:00
August 220.32 01-AUG-00:10 339.04 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 61.58 24-AUG-16:00 51.29 08-AUG-05:00
September 220.32 01-SEP-00:10 339.04 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 45.36 01-SEP-13:53 79.91 24-SEP-06:00
October 220.32 01-OCT-23:10 339.04 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 15.37 25-OCT-10:55 129.78 09-OCT-04:00
November 220.32 01-NOV-00:10 339.04 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 175.93 24-NOV-07:00
December 220.32 01-DEC-00:10 339.04 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 204.88 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   339.04   242.16   0.00 0.00 0.00 0.00 0.00   29.19  
Maximum of Months 220.32   339.04   242.16   0.00 0.00 0.00 0.00 79.50   244.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 453.60 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 602.76 02-JAN-07:10
February 907.20 01-FEB-00:10 453.60 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 615.69 06-FEB-07:10
March 907.20 01-MAR-00:10 453.60 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:03 476.39 23-MAR-06:00
April 907.20 01-APR-00:10 453.60 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 56.88 07-APR-13:00 349.32 03-APR-06:00
May 907.20 01-MAY-00:10 453.60 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 106.32 30-MAY-10:50 288.24 01-MAY-06:05
June 907.20 01-JUN-00:10 453.60 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 201.97 19-JUN-12:00 152.39 02-JUN-06:00
July 907.20 01-JUL-00:10 453.60 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 164.97 07-JUL-10:50 76.05 01-JUL-23:20
August 907.20 01-AUG-00:10 453.60 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 164.38 24-AUG-16:00 129.97 08-AUG-05:10
September 907.20 01-SEP-00:10 453.60 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 112.48 01-SEP-14:20 229.56 24-SEP-05:55
October 907.20 01-OCT-23:10 453.60 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 43.84 25-OCT-10:50 349.91 29-OCT-07:00
November 907.20 01-NOV-00:10 453.60 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:05 464.77 24-NOV-07:00
December 907.20 01-DEC-00:10 453.60 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 525.42 31-DEC-24:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   453.60   4572.80   39726.58   0.00 0.00 0.00 0.00   76.05  
Maximum of Months 907.20   453.60   4572.80   39726.58   0.00 0.00 0.00 201.97   615.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1957.67 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1000.31 02-JAN-05:00
February 15368.40 01-FEB-00:10 1957.67 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1027.81 06-FEB-03:00
March 15368.40 01-MAR-00:10 1957.67 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 783.94 23-MAR-04:20
April 15368.40 01-APR-00:10 1957.67 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 69.19 07-APR-13:00 557.79 01-APR-04:00
May 15368.40 01-MAY-00:10 1957.67 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 153.54 30-MAY-13:00 467.58 15-MAY-02:40
June 15368.40 01-JUN-00:10 1957.67 01-JUN-19:19 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 317.76 19-JUN-10:55 277.73 03-JUN-03:10
July 15368.40 01-JUL-00:10 1957.67 03-JUL-19:19 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 249.03 07-JUL-12:00 129.33 02-JUL-03:00
August 15368.40 01-AUG-00:10 1957.67 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 247.32 24-AUG-15:30 234.50 08-AUG-05:00
September 15368.40 01-SEP-00:10 1957.67 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 178.54 01-SEP-13:53 364.43 30-SEP-01:10
October 15368.40 01-OCT-23:10 1957.67 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 25.84 04-OCT-13:00 569.90 29-OCT-07:00
November 15368.40 01-NOV-00:10 1957.67 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 757.33 24-NOV-06:00
December 15368.40 01-DEC-00:10 1957.67 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 861.07 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1957.67   965.27   0.00 0.00 0.00 0.00 0.00   129.33  
Maximum of Months 15368.40   1957.67   965.27   0.00 0.00 0.00 0.00 317.76   1027.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 8554.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2907.03 02-JAN-05:00
February 45622.98 01-FEB-00:10 8554.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3000.10 06-FEB-03:00
March 45622.98 01-MAR-00:10 8554.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 2303.79 23-MAR-04:40
April 45622.98 01-APR-00:10 8554.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 245.02 07-APR-13:00 1655.30 03-APR-06:00
May 45622.98 01-MAY-00:10 8554.32 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 495.05 30-MAY-13:00 1367.66 01-MAY-05:00
June 45622.98 01-JUN-00:10 8554.32 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 956.40 19-JUN-12:00 824.43 03-JUN-03:10
July 45622.98 01-JUL-00:10 8554.32 03-JUL-19:19 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 755.55 07-JUL-12:00 414.76 02-JUL-03:00
August 45622.98 01-AUG-00:10 8554.32 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 716.95 24-AUG-15:00 694.66 08-AUG-05:00
September 45622.98 01-SEP-00:10 8554.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 511.57 01-SEP-14:00 1082.66 24-SEP-06:00
October 45622.98 01-OCT-23:10 8554.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 115.47 25-OCT-10:55 1703.68 09-OCT-06:00
November 45622.98 01-NOV-00:10 8554.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 2227.31 24-NOV-06:00
December 45622.98 01-DEC-00:10 8554.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 2545.34 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   8554.32   10029.21   0.00 0.00 0.00 0.00 0.00   414.76  
Maximum of Months 45622.98   8554.32   10029.21   0.00 0.00 0.00 0.00 956.40   3000.10  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.22 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 263.84 02-JAN-05:00
February 180.00 01-FEB-00:10 210.22 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.01 06-FEB-03:00
March 180.00 01-MAR-00:10 210.22 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 200.38 23-MAR-06:00
April 180.00 01-APR-00:10 210.22 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 33.43 08-APR-10:00 141.62 03-APR-06:00
May 180.00 01-MAY-00:10 210.22 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 48.23 30-MAY-16:00 110.20 01-MAY-05:00
June 180.00 01-JUN-00:10 210.22 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 87.04 19-JUN-12:00 71.52 02-JUN-19:00
July 180.00 01-JUL-00:10 210.22 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 77.82 10-JUL-15:10 42.69 01-JUL-20:00
August 180.00 01-AUG-00:10 210.22 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 83.59 24-AUG-15:50 43.66 08-AUG-05:00
September 180.00 01-SEP-00:10 210.22 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 60.00 01-SEP-15:10 80.65 24-SEP-05:55
October 180.00 01-OCT-00:10 210.22 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 17.37 04-OCT-15:10 142.49 09-OCT-06:00
November 180.00 01-NOV-00:10 210.22 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.18 24-NOV-07:00
December 180.00 01-DEC-00:10 210.22 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.12 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 0.00   42.69  
Maximum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 87.04   271.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.20 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 263.82 02-JAN-05:00
February 180.00 01-FEB-00:10 210.20 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.00 06-FEB-03:00
March 180.00 01-MAR-00:10 210.20 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 200.36 23-MAR-06:00
April 180.00 01-APR-00:10 210.20 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 33.43 08-APR-10:00 141.61 03-APR-06:00
May 180.00 01-MAY-00:10 210.20 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 48.22 30-MAY-16:00 110.19 01-MAY-05:00
June 180.00 01-JUN-00:10 210.20 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 87.03 19-JUN-12:00 71.97 02-JUN-19:00
July 180.00 01-JUL-00:10 210.20 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 77.81 10-JUL-15:10 42.67 01-JUL-20:00
August 180.00 01-AUG-00:10 210.20 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 83.58 24-AUG-15:10 43.66 08-AUG-05:00
September 180.00 01-SEP-00:10 210.20 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 60.01 01-SEP-15:10 80.64 24-SEP-05:55
October 180.00 01-OCT-00:10 210.20 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 17.47 04-OCT-15:10 142.47 09-OCT-06:00
November 180.00 01-NOV-00:10 210.20 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.17 24-NOV-07:00
December 180.00 01-DEC-00:10 210.20 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.11 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 0.00   42.67  
Maximum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 87.03   271.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 132.12 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 68.71 02-JAN-05:00
February 0.00 01-FEB-00:10 132.12 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 70.82 06-FEB-03:00
March 0.00 01-MAR-00:10 132.12 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 54.07 23-MAR-06:00
April 0.00 01-APR-00:10 132.12 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 6.24 07-APR-13:00 38.51 12-APR-06:20
May 0.00 01-MAY-00:10 132.12 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 12.42 30-MAY-13:00 31.17 01-MAY-05:10
June 0.00 01-JUN-00:10 132.12 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 24.28 19-JUN-12:00 18.90 03-JUN-03:00
July 0.00 01-JUL-00:10 132.12 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 19.39 07-JUL-12:00 9.40 02-JUL-03:00
August 0.00 01-AUG-00:10 132.12 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 19.26 24-AUG-15:00 15.95 08-AUG-05:00
September 0.00 01-SEP-00:10 132.12 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 14.23 01-SEP-13:53 25.53 30-SEP-01:00
October 0.00 01-OCT-00:10 132.12 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 3.07 04-OCT-13:00 42.16 29-OCT-07:00
November 0.00 01-NOV-00:10 132.12 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 52.19 24-NOV-08:00
December 0.00 01-DEC-00:10 132.12 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 58.59 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   132.12   232.19   0.00 0.00 0.00 0.00 0.00   9.40  
Maximum of Months 0.00   132.12   232.19   0.00 0.00 0.00 0.00 24.28   70.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 132.15 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 73.64 02-JAN-05:00
February 180.00 01-FEB-00:10 132.15 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 75.64 06-FEB-03:00
March 180.00 01-MAR-00:10 132.15 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 1.09 27-MAR-15:55 55.92 23-MAR-06:00
April 180.00 01-APR-00:10 132.15 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 9.33 08-APR-10:00 39.52 03-APR-06:00
May 180.00 01-MAY-00:10 132.15 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 13.46 30-MAY-16:00 30.76 01-MAY-05:00
June 180.00 01-JUN-00:10 132.15 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 24.37 19-JUN-12:00 15.66 02-JUN-21:20
July 180.00 01-JUL-00:10 132.15 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 21.72 10-JUL-15:10 9.05 01-JUL-21:50
August 180.00 01-AUG-00:10 132.15 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 23.33 24-AUG-15:10 12.19 08-AUG-05:00
September 180.00 01-SEP-00:10 132.15 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 16.75 01-SEP-15:10 22.51 24-SEP-05:55
October 180.00 01-OCT-00:10 132.15 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 5.75 25-OCT-10:55 39.77 09-OCT-06:00
November 180.00 01-NOV-00:10 132.15 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 54.47 24-NOV-07:00
December 180.00 01-DEC-00:10 132.15 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 63.39 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 0.00   9.05  
Maximum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 24.37   75.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.22 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 263.84 02-JAN-05:00
February 180.00 01-FEB-00:10 210.22 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.01 06-FEB-03:00
March 180.00 01-MAR-00:10 210.22 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 200.38 23-MAR-06:00
April 180.00 01-APR-00:10 210.22 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 33.43 08-APR-10:00 141.62 03-APR-06:00
May 180.00 01-MAY-00:10 210.22 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 48.24 30-MAY-16:00 110.20 01-MAY-05:00
June 180.00 01-JUN-00:10 210.22 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 87.04 19-JUN-12:00 69.39 02-JUN-08:50
July 180.00 01-JUL-00:10 210.22 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 77.82 10-JUL-15:10 35.69 01-JUL-21:50
August 180.00 01-AUG-00:10 210.22 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 83.60 24-AUG-15:10 50.21 25-AUG-08:20
September 180.00 01-SEP-00:10 210.22 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 60.01 01-SEP-15:08 80.65 24-SEP-05:55
October 180.00 01-OCT-00:10 210.22 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 17.47 04-OCT-15:10 142.48 09-OCT-06:00
November 180.00 01-NOV-00:10 210.22 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.19 24-NOV-07:00
December 180.00 01-DEC-00:10 210.22 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.13 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 0.00   35.69  
Maximum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 87.04   271.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.20 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 263.82 02-JAN-05:00
February 180.00 01-FEB-00:10 210.20 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.00 06-FEB-03:00
March 180.00 01-MAR-00:10 210.20 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 2.87 27-MAR-15:55 200.36 23-MAR-06:00
April 180.00 01-APR-00:10 210.20 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 33.42 08-APR-10:00 141.61 03-APR-06:00
May 180.00 01-MAY-00:10 210.20 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 48.24 30-MAY-16:00 110.19 01-MAY-05:00
June 180.00 01-JUN-00:10 210.20 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 87.03 19-JUN-12:00 69.38 02-JUN-08:50
July 180.00 01-JUL-00:10 210.20 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 77.81 10-JUL-15:10 35.60 01-JUL-21:50
August 180.00 01-AUG-00:10 210.20 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 83.59 24-AUG-15:10 47.61 25-AUG-08:20
September 180.00 01-SEP-00:10 210.20 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 60.01 01-SEP-15:10 80.64 24-SEP-05:55
October 180.00 01-OCT-00:10 210.20 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 17.47 04-OCT-15:10 142.48 09-OCT-06:00
November 180.00 01-NOV-00:10 210.20 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.17 24-NOV-07:00
December 180.00 01-DEC-00:10 210.20 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.11 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 0.00   35.60  
Maximum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 87.03   271.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1867.32 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 317.99 02-JAN-05:00
February 2263.36 01-FEB-00:10 1867.32 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 326.68 06-FEB-03:00
March 2263.36 01-MAR-00:10 1867.32 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 6.09 27-MAR-15:55 241.28 23-MAR-06:00
April 2263.36 01-APR-00:10 1867.32 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 36.87 07-APR-13:00 170.25 03-APR-06:00
May 2263.36 01-MAY-00:10 1867.32 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 55.20 30-MAY-13:00 136.18 01-MAY-05:00
June 2263.36 01-JUN-00:10 1867.32 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 105.23 19-JUN-12:00 84.68 03-JUN-03:10
July 2263.36 01-JUL-00:10 1867.32 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 82.34 07-JUL-12:00 41.90 02-JUL-03:00
August 2263.36 01-AUG-00:10 1867.32 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 78.88 24-AUG-16:00 70.15 08-AUG-05:00
September 2263.36 01-SEP-00:10 1867.32 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 57.38 01-SEP-13:53 107.63 24-SEP-06:00
October 2263.36 01-OCT-23:10 1867.32 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 18.37 25-OCT-10:55 179.07 09-OCT-04:00
November 2263.36 01-NOV-00:10 1867.32 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 235.00 24-NOV-07:00
December 2263.36 01-DEC-00:10 1867.32 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 273.63 31-DEC-24:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 0.00   41.90  
Maximum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 105.23   326.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.22 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 264.38 02-JAN-05:00
February 180.00 01-FEB-00:10 210.22 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.54 06-FEB-03:00
March 180.00 01-MAR-00:10 210.22 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 200.88 23-MAR-06:00
April 180.00 01-APR-00:10 210.22 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 33.03 08-APR-10:00 142.09 03-APR-06:00
May 180.00 01-MAY-00:10 210.22 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 47.82 30-MAY-16:00 110.66 01-MAY-05:00
June 180.00 01-JUN-00:10 210.22 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 86.67 19-JUN-12:00 78.89 03-JUN-19:00
July 180.00 01-JUL-00:10 210.22 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 77.42 10-JUL-15:10 48.80 01-JUL-20:00
August 180.00 01-AUG-00:10 210.22 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 83.21 24-AUG-16:00 44.09 08-AUG-05:00
September 180.00 01-SEP-00:10 210.22 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 59.61 01-SEP-15:10 81.10 24-SEP-05:55
October 180.00 01-OCT-00:10 210.22 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 17.02 04-OCT-15:10 142.96 09-OCT-06:00
November 180.00 01-NOV-00:10 210.22 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.68 24-NOV-07:00
December 180.00 01-DEC-00:10 210.22 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.64 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 0.00   44.09  
Maximum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 86.67   271.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.20 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 264.35 02-JAN-05:00
February 180.00 01-FEB-00:10 210.20 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.51 06-FEB-03:00
March 180.00 01-MAR-00:10 210.20 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 200.86 23-MAR-06:00
April 180.00 01-APR-00:10 210.20 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 33.03 08-APR-10:00 142.08 03-APR-06:00
May 180.00 01-MAY-00:10 210.20 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 47.82 30-MAY-16:00 110.65 01-MAY-05:00
June 180.00 01-JUN-00:10 210.20 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 86.66 19-JUN-12:00 79.16 03-JUN-18:50
July 180.00 01-JUL-00:10 210.20 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 77.42 10-JUL-15:10 49.11 01-JUL-20:00
August 180.00 01-AUG-00:10 210.20 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 83.20 24-AUG-16:00 44.09 08-AUG-05:00
September 180.00 01-SEP-00:10 210.20 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 59.62 01-SEP-15:10 81.09 24-SEP-05:55
October 180.00 01-OCT-00:10 210.20 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 17.06 04-OCT-15:10 142.95 09-OCT-06:00
November 180.00 01-NOV-00:10 210.20 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.66 24-NOV-07:00
December 180.00 01-DEC-00:10 210.20 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.62 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 0.00   44.09  
Maximum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 86.66   271.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 132.15 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 135.26 02-JAN-05:00
February 180.00 01-FEB-00:10 132.15 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 138.93 06-FEB-03:00
March 180.00 01-MAR-00:10 132.15 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 102.78 23-MAR-06:00
April 180.00 01-APR-00:10 132.15 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 16.90 08-APR-10:00 72.70 03-APR-06:00
May 180.00 01-MAY-00:10 132.15 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 24.48 30-MAY-16:00 56.62 01-MAY-05:00
June 180.00 01-JUN-00:10 132.15 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 44.34 19-JUN-12:00 29.84 02-JUN-21:20
July 180.00 01-JUL-00:10 132.15 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 39.62 10-JUL-15:10 17.65 01-JUL-21:50
August 180.00 01-AUG-00:10 132.15 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 42.58 24-AUG-15:50 22.56 08-AUG-05:00
September 180.00 01-SEP-00:10 132.15 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 30.50 01-SEP-15:10 41.49 24-SEP-05:55
October 180.00 01-OCT-00:10 132.15 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 7.19 25-OCT-10:00 73.14 09-OCT-06:00
November 180.00 01-NOV-00:10 132.15 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 100.12 24-NOV-07:00
December 180.00 01-DEC-00:10 132.15 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 116.47 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 0.00   17.65  
Maximum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 44.34   138.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3437.84 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 688.63 02-JAN-05:00
February 26988.77 01-FEB-00:10 3437.84 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 705.81 06-FEB-03:00
March 26988.77 01-MAR-00:10 3437.84 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 543.26 23-MAR-04:30
April 26988.77 01-APR-00:10 3437.84 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 48.44 07-APR-13:00 399.59 03-APR-06:00
May 26988.77 01-MAY-00:10 3437.84 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 96.79 30-MAY-13:00 321.76 01-MAY-05:00
June 26988.77 01-JUN-00:10 3437.84 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 201.01 19-JUN-12:00 186.83 03-JUN-04:50
July 26988.77 01-JUL-00:10 3437.84 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 158.05 07-JUL-12:00 98.67 02-JUL-05:00
August 26988.77 01-AUG-00:10 3437.84 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 156.97 24-AUG-15:40 157.62 08-AUG-05:00
September 26988.77 01-SEP-00:10 3437.84 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 112.85 01-SEP-13:53 260.90 24-SEP-05:55
October 26988.77 01-OCT-23:10 3437.84 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 27.55 25-OCT-10:55 402.04 09-OCT-06:00
November 26988.77 01-NOV-00:10 3437.84 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 528.50 24-NOV-06:00
December 26988.77 01-DEC-00:10 3437.84 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 610.14 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 0.00   98.67  
Maximum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 201.01   705.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3437.84 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 693.00 02-JAN-05:00
February 26988.77 01-FEB-00:10 3437.84 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 710.18 06-FEB-03:00
March 26988.77 01-MAR-00:10 3437.84 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 544.47 23-MAR-06:00
April 26988.77 01-APR-00:10 3437.84 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 43.73 07-APR-13:00 399.59 03-APR-06:00
May 26988.77 01-MAY-00:10 3437.84 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 96.79 30-MAY-13:00 321.76 01-MAY-05:00
June 26988.77 01-JUN-00:10 3437.84 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 201.00 19-JUN-12:00 186.83 03-JUN-04:50
July 26988.77 01-JUL-00:10 3437.84 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 158.05 07-JUL-12:00 98.67 02-JUL-05:00
August 26988.77 01-AUG-00:10 3437.84 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 156.97 24-AUG-15:40 157.62 08-AUG-05:00
September 26988.77 01-SEP-00:10 3437.84 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 112.85 01-SEP-13:53 262.09 24-SEP-05:55
October 26988.77 01-OCT-23:10 3437.84 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 23.82 25-OCT-10:55 402.05 09-OCT-06:00
November 26988.77 01-NOV-00:10 3437.84 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 531.61 24-NOV-07:00
December 26988.77 01-DEC-00:10 3437.84 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 610.15 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 0.00   98.67  
Maximum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 201.00   710.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1210.92 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 618.39 02-JAN-07:00
February 2401.70 01-FEB-00:10 1210.92 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 631.17 06-FEB-07:00
March 2401.70 01-MAR-00:10 1210.92 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 487.33 23-MAR-06:00
April 2401.70 01-APR-00:10 1210.92 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 38.35 07-APR-13:00 357.64 03-APR-06:00
May 2401.70 01-MAY-00:10 1210.92 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 86.79 30-MAY-13:00 296.33 01-MAY-06:05
June 2401.70 01-JUN-00:10 1210.92 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 180.11 19-JUN-12:00 167.15 03-JUN-05:00
July 2401.70 01-JUL-00:10 1210.92 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 141.66 07-JUL-12:00 88.32 02-JUL-05:00
August 2401.70 01-AUG-00:10 1210.92 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 140.71 24-AUG-15:40 141.11 08-AUG-05:00
September 2401.70 01-SEP-00:10 1210.92 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 100.16 01-SEP-14:00 250.83 24-SEP-05:55
October 2401.70 01-OCT-23:10 1210.92 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 13.46 04-OCT-13:00 359.85 09-OCT-06:00
November 2401.70 01-NOV-00:10 1210.92 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:05 475.83 24-NOV-07:00
December 2401.70 01-DEC-00:10 1210.92 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 546.19 31-DEC-24:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1210.92   14912.86   22492.83   0.00 0.00 0.00 0.00   88.32  
Maximum of Months 2401.70   1210.92   14912.86   22492.83   0.00 0.00 0.00 180.11   631.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1976.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 563.79 02-JAN-05:00
February 2395.44 01-FEB-00:10 1976.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 579.11 06-FEB-03:00
March 2395.44 01-MAR-00:10 1976.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 1.42 27-MAR-15:55 427.96 23-MAR-06:00
April 2395.44 01-APR-00:10 1976.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 50.07 07-APR-13:00 302.24 03-APR-06:00
May 2395.44 01-MAY-00:10 1976.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 84.79 30-MAY-13:00 236.11 01-MAY-05:00
June 2395.44 01-JUN-00:10 1976.27 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 176.10 19-JUN-12:00 143.74 03-JUN-03:10
July 2395.44 01-JUL-00:10 1976.27 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 138.46 07-JUL-12:00 68.57 02-JUL-03:00
August 2395.44 01-AUG-00:10 1976.27 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 137.51 24-AUG-15:00 119.13 08-AUG-05:00
September 2395.44 01-SEP-00:10 1976.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 98.86 01-SEP-13:53 185.21 24-SEP-06:00
October 2395.44 01-OCT-23:10 1976.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 26.45 25-OCT-10:55 304.08 09-OCT-06:00
November 2395.44 01-NOV-00:10 1976.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 416.84 24-NOV-07:00
December 2395.44 01-DEC-00:10 1976.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 485.20 31-DEC-24:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 0.00   68.57  
Maximum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 176.10   579.11  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 32537.37 24-JAN-21:57 102239.04 137348.18 91255.54 0.00 0.00 0.00 0.00 0.00 0.00
February 27242.87 01-FEB-21:08 102239.04 137348.18 91255.54 0.00 0.00 0.00 0.00 0.00 0.00
March 26017.48 05-MAR-07:37 53675.50 41205.07 30418.51 0.00 0.00 0.00 0.00 0.00 0.00
April 25429.18 13-APR-06:47 30671.71 51505.41 36502.22 0.00 0.00 0.00 0.00 0.00 0.00
May 21101.82 01-MAY-01:13 34505.68 5150.79 6083.70 0.00 0.00 0.00 0.00 0.00 0.00
June 17466.70 22-JUN-18:10 53675.50 82408.91 54753.33 0.00 0.00 0.00 0.00 0.00 0.00
July 17208.49 11-JUL-17:08 51119.52 82409.32 56781.23 0.00 0.00 0.00 0.00 0.00 0.00
August 20929.45 24-AUG-18:53 35783.66 54939.27 36502.22 0.00 0.00 0.00 0.00 0.00 0.00
September 25944.93 24-SEP-05:49 62621.41 36054.08 28390.61 0.00 0.00 0.00 0.00 0.00 0.00
October 38159.79 27-OCT-23:56 115018.92 34336.53 30418.51 0.00 0.00 0.00 0.00 0.00 0.00
November 38716.81 08-NOV-00:14 57509.46 17168.27 15209.26 0.00 0.00 0.00 0.00 0.00 0.00
December 50179.54 04-DEC-07:51 35783.66 60089.65 42585.92 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17208.49   30671.71 5150.79 6083.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 50179.54   115018.92 137348.18 91255.54 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3247.91 19-JAN-14:10 519.79 397.97 505.18 0.00 0.00 0.00 0.00 0.00 181.23
February 3510.93 17-FEB-12:20 2598.96 1989.87 2525.91 0.00 0.00 0.00 0.00 0.00 210.64
March 4860.33 29-MAR-12:48 2598.96 1989.87 2525.91 0.00 0.00 0.00 0.00 0.00 204.38
April 3578.94 07-APR-12:30 259.90 198.99 252.59 0.00 0.00 0.00 0.00 24.95 0.00
May 2802.03 30-MAY-12:50 259.90 198.99 252.59 0.00 0.00 0.00 0.00 68.32 0.00
June 3128.22 19-JUN-12:50 259.90 198.99 252.59 0.00 0.00 0.00 0.00 127.58 0.00
July 3315.88 08-JUL-12:00 389.84 198.99 252.59 0.00 0.00 0.00 0.00 94.12 0.00
August 4062.23 18-AUG-12:40 259.90 198.99 252.59 0.00 0.00 0.00 0.00 103.70 0.00
September 4353.14 01-SEP-13:57 779.69 596.96 757.77 0.00 0.00 0.00 0.00 80.62 0.00
October 4480.61 04-OCT-12:10 259.90 198.99 252.59 0.00 0.00 0.00 0.00 5.84 0.00
November 4425.70 18-NOV-12:23 3898.44 1989.87 2525.91 0.00 0.00 0.00 0.00 0.00 209.74
December 5631.24 03-DEC-12:49 3898.44 2387.85 2886.75 0.00 0.00 0.00 0.00 0.00 196.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2802.03   259.90 198.99 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5631.24   3898.44 2387.85 2886.75 0.00 0.00 0.00 0.00 127.58 210.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1958.59 21-JAN-22:48 6320.16 3318.16 3510.01 0.00 0.00 0.00 0.00 0.00 79.31
February 1932.99 20-FEB-16:28 4514.40 1843.42 2507.15 0.00 0.00 0.00 0.00 0.00 71.79
March 2225.76 12-MAR-00:37 6320.16 1659.08 2005.72 0.00 0.00 0.00 0.00 0.00 73.27
April 2246.67 13-APR-06:47 3611.52 2765.14 3008.58 0.00 0.00 0.00 0.00 0.00 78.65
May 1896.01 31-MAY-21:00 1203.84 737.37 752.15 0.00 0.00 0.00 0.00 0.00 15.66
June 2152.54 19-JUN-21:00 1203.84 737.37 752.15 0.00 0.00 0.00 0.00 21.89 0.00
July 2172.27 10-JUL-21:00 1203.84 737.37 752.15 0.00 0.00 0.00 0.00 14.34 0.00
August 2236.87 04-AUG-21:00 1203.84 737.37 752.15 0.00 0.00 0.00 0.00 36.16 0.00
September 2145.87 01-SEP-21:00 1203.84 737.37 752.15 0.00 0.00 0.00 0.00 12.05 0.00
October 2271.64 30-OCT-23:56 13543.20 1843.42 2507.15 0.00 0.00 0.00 0.00 0.00 78.20
November 2090.49 13-NOV-07:05 1203.84 921.71 1002.86 0.00 0.00 0.00 0.00 0.00 75.86
December 2116.68 04-DEC-07:51 4213.44 3225.99 3510.01 0.00 0.00 0.00 0.00 0.00 79.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1896.01   1203.84 737.37 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2271.64   13543.20 3318.16 3510.01 0.00 0.00 0.00 0.00 36.16 79.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1392.27 21-JAN-22:48 1336.61 2673.06 3711.24 0.00 0.00 0.00 0.00 0.00 173.64
February 1088.23 20-FEB-15:34 572.83 1336.53 2385.80 0.00 0.00 0.00 0.00 0.00 151.62
March 1609.11 05-MAR-07:37 1336.61 1782.04 2650.88 0.00 0.00 0.00 0.00 0.00 167.84
April 1671.11 11-APR-06:16 1018.37 2970.07 4241.42 0.00 0.00 0.00 0.00 0.00 181.26
May 1372.58 01-MAY-01:13 859.25 222.76 530.18 0.00 0.00 0.00 0.00 0.00 144.87
June 1543.07 19-JUN-21:00 254.59 594.01 795.27 0.00 0.00 0.00 0.00 51.72 0.00
July 1773.86 10-JUL-20:00 222.77 668.27 839.45 0.00 0.00 0.00 0.00 45.33 0.00
August 1809.89 17-AUG-20:00 222.77 668.27 839.45 0.00 0.00 0.00 0.00 51.44 0.00
September 1490.73 01-SEP-21:00 254.59 594.01 795.27 0.00 0.00 0.00 0.00 28.48 0.00
October 1660.92 08-OCT-23:16 2227.68 2227.55 3534.51 0.00 0.00 0.00 0.00 0.00 177.40
November 1569.94 13-NOV-07:05 254.59 742.52 1060.35 0.00 0.00 0.00 0.00 0.00 172.66
December 1489.06 04-DEC-07:51 891.07 2598.81 3711.24 0.00 0.00 0.00 0.00 0.00 171.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1088.23   222.77 222.76 530.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1809.89   2227.68 2970.07 4241.42 0.00 0.00 0.00 0.00 51.72 181.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 819.06 22-JAN-22:52 1175.04 1130.09 917.65 0.00 0.00 0.00 0.00 0.00 100.04
February 704.96 19-FEB-11:32 440.64 678.05 611.77 0.00 0.00 0.00 0.00 0.00 85.84
March 1033.61 05-MAR-07:37 1028.16 904.09 764.71 0.00 0.00 0.00 0.00 0.00 94.69
April 1060.63 11-APR-06:16 783.36 1506.79 1223.53 0.00 0.00 0.00 0.00 0.00 101.27
May 875.12 01-MAY-01:13 660.96 113.02 152.94 0.00 0.00 0.00 0.00 0.00 81.24
June 847.93 22-JUN-18:10 1028.16 1808.18 1376.47 0.00 0.00 0.00 0.00 31.80 0.00
July 859.80 08-JUL-10:33 220.32 282.52 267.65 0.00 0.00 0.00 0.00 41.85 0.00
August 959.20 24-AUG-18:53 685.44 1205.45 917.65 0.00 0.00 0.00 0.00 33.59 0.00
September 859.13 01-SEP-17:06 856.80 1582.16 1249.02 0.00 0.00 0.00 0.00 26.40 0.00
October 1055.78 08-OCT-23:16 1713.60 1130.08 1019.61 0.00 0.00 0.00 0.00 0.00 99.15
November 978.93 01-NOV-06:40 195.84 376.70 305.88 0.00 0.00 0.00 0.00 0.00 98.64
December 966.23 04-DEC-07:51 685.44 1318.44 1070.59 0.00 0.00 0.00 0.00 0.00 97.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 704.96   195.84 113.02 152.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1060.63   1713.60 1808.18 1376.47 0.00 0.00 0.00 0.00 41.85 101.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 51077.66 03-JAN-21:00 4939.20 3175.23 32009.60 278086.04 0.00 0.00 0.00 0.00 305.70
February 51247.65 23-FEB-21:07 8064.00 4032.04 43321.27 376357.04 0.00 0.00 0.00 0.00 315.93
March 51506.02 24-MAR-20:49 7257.60 3628.84 38989.14 338721.34 0.00 0.00 0.00 0.00 306.04
April 50767.36 14-APR-18:06 7056.00 4032.04 43321.27 376357.04 0.00 0.00 0.00 0.00 269.60
May 39167.11 01-MAY-19:50 2116.80 1360.81 13718.40 119179.73 0.00 0.00 0.00 0.00 226.59
June 39527.86 22-JUN-20:03 2419.20 1209.61 12996.38 112907.11 0.00 0.00 0.00 28.98 0.00
July 38923.65 10-JUL-20:00 705.60 453.60 4572.80 39726.58 0.00 0.00 0.00 61.90 0.00
August 41643.26 24-AUG-18:29 4939.20 2822.43 30324.89 263449.93 0.00 0.00 0.00 86.64 0.00
September 38635.42 06-SEP-20:00 705.60 453.60 4572.80 39726.58 0.00 0.00 0.00 0.00 17.78
October 48596.12 28-OCT-20:56 7056.00 3528.04 38507.80 334539.59 0.00 0.00 0.00 0.00 289.44
November 50018.06 17-NOV-21:54 8064.00 4032.04 43321.27 376357.04 0.00 0.00 0.00 0.00 307.27
December 50033.62 07-DEC-20:08 7056.00 4536.05 45728.01 397265.76 0.00 0.00 0.00 0.00 325.51
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 38635.42   705.60 453.60 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 51506.02   8064.00 4536.05 45728.01 397265.76 0.00 0.00 0.00 86.64 325.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14183.50 19-JAN-11:08 17076.00 598.18 1778.13 0.00 0.00 0.00 0.00 0.00 431.58
February 17217.29 19-FEB-12:40 51228.00 1435.63 4064.31 0.00 0.00 0.00 0.00 0.00 437.85
March 19717.93 29-MAR-12:48 34152.00 1196.36 3556.27 0.00 0.00 0.00 0.00 0.00 451.98
April 17875.08 25-APR-02:40 30736.80 435.04 406.43 0.00 0.00 0.00 0.00 0.00 341.32
May 12489.61 02-MAY-02:63 46105.20 652.56 609.65 0.00 0.00 0.00 0.00 0.00 400.17
June 12099.99 19-JUN-21:10 15368.40 1305.12 711.25 0.00 0.00 0.00 0.00 120.79 0.00
July 11924.16 10-JUL-21:10 15368.40 1305.12 711.25 0.00 0.00 0.00 0.00 80.09 0.00
August 13486.92 19-AUG-11:50 5122.80 119.64 355.63 0.00 0.00 0.00 0.00 82.34 0.00
September 15168.96 30-SEP-12:40 5122.80 119.64 355.63 0.00 0.00 0.00 0.00 0.00 95.63
October 16249.26 29-OCT-09:10 42690.00 717.81 2032.15 0.00 0.00 0.00 0.00 0.00 442.72
November 20087.06 07-NOV-23:55 30736.80 1305.12 812.86 0.00 0.00 0.00 0.00 0.00 378.78
December 22895.90 03-DEC-12:49 51228.00 1435.63 4064.31 0.00 0.00 0.00 0.00 0.00 434.51
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11924.16   5122.80 119.64 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22895.90   51228.00 1435.63 4064.31 0.00 0.00 0.00 0.00 120.79 451.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 40936.82 18-JAN-07:09 182491.92 42771.60 57008.13 0.00 0.00 0.00 0.00 0.00 1127.53
February 39861.11 18-FEB-15:22 152076.60 20435.32 36949.72 0.00 0.00 0.00 0.00 0.00 1233.44
March 59070.28 04-MAR-03:10 364983.84 7603.84 16891.30 0.00 0.00 0.00 0.00 0.00 1237.32
April 54543.63 12-APR-21:50 228114.90 28514.40 36949.72 0.00 0.00 0.00 0.00 0.00 1337.41
May 56841.89 15-MAY-02:44 228114.90 4752.40 10557.06 0.00 0.00 0.00 0.00 0.00 1312.28
June 40644.26 19-JUN-21:10 45622.98 5702.88 7389.94 0.00 0.00 0.00 0.00 344.97 0.00
July 41032.17 10-JUL-21:10 45622.98 5702.88 7389.94 0.00 0.00 0.00 0.00 228.67 0.00
August 42299.28 04-AUG-21:10 45622.98 5702.88 7389.94 0.00 0.00 0.00 0.00 545.99 0.00
September 41239.32 01-SEP-21:10 45622.98 5702.88 7389.94 0.00 0.00 0.00 0.00 190.04 0.00
October 82042.13 27-OCT-23:02 273737.88 11405.76 19002.71 0.00 0.00 0.00 0.00 0.00 1300.21
November 53899.04 08-NOV-00:18 228114.90 9504.80 15835.59 0.00 0.00 0.00 0.00 0.00 1282.23
December 44892.22 17-DEC-09:03 152076.60 14713.43 25336.95 0.00 0.00 0.00 0.00 0.00 1310.14
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 39861.11   45622.98 4752.40 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 82042.13   364983.84 42771.60 57008.13 0.00 0.00 0.00 0.00 545.99 1337.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3534.35 19-JAN-16:01 874.80 529.77 450.41 0.00 0.00 0.00 0.00 0.00 102.22
February 3500.96 24-FEB-16:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 105.43
March 3642.15 24-MAR-15:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 93.49
April 3869.36 09-APR-18:11 1170.00 2102.25 1211.63 0.00 0.00 0.00 0.00 0.00 73.18
May 3877.53 29-MAY-18:31 1170.00 2102.25 1211.63 0.00 0.00 0.00 0.00 0.64 0.00
June 3927.35 04-JUN-21:51 1386.00 1786.91 895.56 0.00 0.00 0.00 0.00 0.00 50.79
July 3642.64 03-JUL-18:51 1386.00 1871.00 1211.63 0.00 0.00 0.00 0.00 1.01 0.00
August 3771.66 30-AUG-08:51 324.00 832.49 1019.35 0.00 0.00 0.00 0.00 0.00 7.16
September 3768.05 03-SEP-08:51 540.00 1177.26 1633.07 0.00 0.00 0.00 0.00 0.00 8.03
October 3784.97 30-OCT-16:41 972.00 588.63 1264.31 0.00 0.00 0.00 0.00 0.00 66.11
November 3550.21 03-NOV-15:01 680.40 412.04 350.32 0.00 0.00 0.00 0.00 0.00 39.60
December 3458.37 17-DEC-16:01 378.00 485.62 387.20 0.00 0.00 0.00 0.00 0.00 88.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3458.37   324.00 412.04 350.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3927.35   1386.00 2102.25 1633.07 0.00 0.00 0.00 0.00 1.01 105.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2072.65 17-JAN-16:01 680.40 411.99 350.28 0.00 0.00 0.00 0.00 0.00 84.85
February 3150.35 20-FEB-16:01 378.00 485.56 387.15 0.00 0.00 0.00 0.00 0.00 101.76
March 3505.66 07-MAR-16:01 972.00 588.56 500.40 0.00 0.00 0.00 0.00 0.00 105.41
April 3723.64 09-APR-18:11 1170.00 2102.00 1211.49 0.00 0.00 0.00 0.00 0.00 71.23
May 3775.53 29-MAY-18:31 1170.00 2102.00 1211.49 0.00 0.00 0.00 0.00 0.87 0.00
June 3705.84 10-JUN-08:51 540.00 1177.12 1632.88 0.00 0.00 0.00 0.00 0.00 3.79
July 3560.70 03-JUL-18:51 1386.00 1870.78 1211.49 0.00 0.00 0.00 0.00 0.64 0.00
August 3602.98 25-AUG-21:51 1800.00 1408.34 895.45 0.00 0.00 0.00 0.00 0.00 18.21
September 3546.45 11-SEP-21:51 1800.00 1408.34 895.45 0.00 0.00 0.00 0.00 0.00 40.78
October 3444.58 30-OCT-16:41 972.00 588.56 1264.17 0.00 0.00 0.00 0.00 0.00 58.87
November 3411.22 03-NOV-15:01 680.40 411.99 350.28 0.00 0.00 0.00 0.00 0.00 38.73
December 1149.77 17-DEC-16:01 378.00 485.56 387.15 0.00 0.00 0.00 0.00 0.00 80.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1149.77   378.00 411.99 350.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3775.53   1800.00 2102.00 1632.88 0.00 0.00 0.00 0.00 0.87 105.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 201.88 19-JAN-14:27 0.00 110.98 92.88 0.00 0.00 0.00 0.00 0.00 28.37
February 337.81 20-FEB-13:30 0.00 87.20 67.08 0.00 0.00 0.00 0.00 0.00 28.27
March 490.31 03-MAR-13:30 0.00 36.99 30.96 0.00 0.00 0.00 0.00 0.00 17.13
April 621.85 08-APR-12:30 0.00 43.60 33.54 0.00 0.00 0.00 0.00 0.42 0.00
May 495.88 30-MAY-12:50 0.00 36.99 30.96 0.00 0.00 0.00 0.00 12.23 0.00
June 521.95 19-JUN-13:10 0.00 36.99 30.96 0.00 0.00 0.00 0.00 21.13 0.00
July 545.47 10-JUL-13:10 0.00 36.99 30.96 0.00 0.00 0.00 0.00 16.50 0.00
August 680.21 30-AUG-12:50 0.00 36.99 30.96 0.00 0.00 0.00 0.00 7.05 0.00
September 728.20 30-SEP-12:30 0.00 43.60 33.54 0.00 0.00 0.00 0.00 0.00 5.99
October 783.41 04-OCT-12:00 0.00 36.99 30.96 0.00 0.00 0.00 0.00 1.94 0.00
November 644.93 02-NOV-12:40 0.00 36.99 30.96 0.00 0.00 0.00 0.00 0.00 15.65
December 498.57 17-DEC-13:30 0.00 43.60 33.54 0.00 0.00 0.00 0.00 0.00 21.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 201.88   0.00 36.99 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 783.41   0.00 110.98 92.88 0.00 0.00 0.00 0.00 21.13 28.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 380.36 19-JAN-19:03 1386.00 1176.17 1187.08 0.00 0.00 0.00 0.00 0.00 31.05
February 422.47 20-FEB-09:02 270.00 370.03 799.99 0.00 0.00 0.00 0.00 0.00 30.87
March 1041.24 28-MAR-18:01 1108.80 940.94 949.67 0.00 0.00 0.00 0.00 0.00 23.26
April 1142.14 10-APR-20:41 1602.00 1176.17 1780.62 0.00 0.00 0.00 0.00 0.00 17.66
May 1216.03 27-MAY-21:51 1386.00 1123.31 877.41 0.00 0.00 0.00 0.00 0.00 8.51
June 1202.31 04-JUN-08:51 486.00 666.06 1439.98 0.00 0.00 0.00 0.00 0.58 0.00
July 1152.63 03-JUL-18:51 1386.00 1176.17 1187.08 0.00 0.00 0.00 0.00 1.51 0.00
August 1143.55 28-AUG-21:51 1800.00 885.43 877.41 0.00 0.00 0.00 0.00 0.00 7.61
September 1181.55 10-SEP-21:51 1386.00 1123.31 877.41 0.00 0.00 0.00 0.00 0.00 12.51
October 1126.87 25-OCT-21:51 1440.00 708.35 701.93 0.00 0.00 0.00 0.00 0.00 12.41
November 1026.98 11-NOV-09:02 324.00 444.04 959.99 0.00 0.00 0.00 0.00 0.00 21.91
December 440.97 25-DEC-09:02 270.00 370.03 799.99 0.00 0.00 0.00 0.00 0.00 21.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 380.36   270.00 370.03 701.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1216.03   1800.00 1176.17 1780.62 0.00 0.00 0.00 0.00 1.51 31.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2354.25 17-JAN-16:01 680.40 412.04 350.32 0.00 0.00 0.00 0.00 0.00 85.00
February 3117.12 25-FEB-09:02 324.00 706.35 979.84 0.00 0.00 0.00 0.00 0.00 180.42
March 3335.54 24-MAR-15:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 92.96
April 3765.70 08-APR-08:51 540.00 1177.26 1633.07 0.00 0.00 0.00 0.00 0.00 24.63
May 4010.46 30-MAY-08:62 216.00 554.99 679.57 0.00 0.00 0.00 0.00 0.00 10.33
June 3940.73 02-JUN-08:51 360.00 924.99 1132.61 0.00 0.00 0.00 0.00 0.00 64.03
July 3867.98 11-JUL-08:32 180.00 462.49 566.31 0.00 0.00 0.00 0.00 0.00 18.76
August 4071.43 30-AUG-08:32 216.00 554.99 679.57 0.00 0.00 0.00 0.00 0.00 27.65
September 3927.61 10-SEP-08:32 324.00 706.35 979.84 0.00 0.00 0.00 0.00 0.00 49.66
October 3742.80 15-OCT-08:51 540.00 1177.26 1633.07 0.00 0.00 0.00 0.00 0.00 55.50
November 3254.69 03-NOV-15:01 680.40 412.04 350.32 0.00 0.00 0.00 0.00 0.00 39.16
December 3097.42 17-DEC-09:02 324.00 706.35 979.84 0.00 0.00 0.00 0.00 0.00 114.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2354.25   180.00 412.04 350.32 0.00 0.00 0.00 0.00 0.00 10.33
Maximum of Months 4071.43   972.00 1177.26 1633.07 0.00 0.00 0.00 0.00 0.00 180.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 738.73 26-JAN-09:03 216.00 554.93 679.49 0.00 0.00 0.00 0.00 0.00 152.13
February 2302.94 19-FEB-09:02 324.00 706.27 979.73 0.00 0.00 0.00 0.00 0.00 124.19
March 3090.61 29-MAR-08:62 216.00 554.93 679.49 0.00 0.00 0.00 0.00 0.00 130.00
April 3609.25 08-APR-08:51 540.00 1177.12 1632.88 0.00 0.00 0.00 0.00 0.00 22.94
May 3920.69 30-MAY-08:62 216.00 554.93 679.49 0.00 0.00 0.00 0.00 0.00 10.52
June 3847.40 26-JUN-08:32 216.00 554.93 679.49 0.00 0.00 0.00 0.00 0.00 15.52
July 3778.95 11-JUL-08:32 180.00 462.44 566.24 0.00 0.00 0.00 0.00 0.00 18.75
August 3882.87 30-AUG-08:32 216.00 554.93 679.49 0.00 0.00 0.00 0.00 0.00 24.73
September 3763.85 06-SEP-08:32 216.00 554.93 679.49 0.00 0.00 0.00 0.00 0.00 12.63
October 3435.38 15-OCT-08:51 540.00 1177.12 1632.88 0.00 0.00 0.00 0.00 0.00 49.41
November 2898.25 06-NOV-09:02 216.00 554.93 679.49 0.00 0.00 0.00 0.00 0.00 95.89
December 1257.36 17-DEC-09:02 324.00 706.27 979.73 0.00 0.00 0.00 0.00 0.00 109.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 738.73   180.00 462.44 566.24 0.00 0.00 0.00 0.00 0.00 10.52
Maximum of Months 3920.69   540.00 1177.12 1632.88 0.00 0.00 0.00 0.00 0.00 152.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2647.31 22-JAN-22:52 12071.23 6224.39 0.00 0.00 0.00 0.00 0.00 0.00 134.32
February 2981.79 20-FEB-16:28 7544.52 4149.60 0.00 0.00 0.00 0.00 0.00 0.00 123.19
March 3344.27 12-MAR-00:37 10562.33 3734.64 0.00 0.00 0.00 0.00 0.00 0.00 121.68
April 3505.74 13-APR-06:47 6035.62 6224.39 0.00 0.00 0.00 0.00 0.00 0.00 135.47
May 2844.28 01-MAY-01:13 6790.07 622.44 0.00 0.00 0.00 0.00 0.00 0.00 109.78
June 2775.43 22-JUN-18:10 10562.33 9959.03 0.00 0.00 0.00 0.00 0.00 40.44 0.00
July 2769.23 11-JUL-17:08 10059.36 9959.03 0.00 0.00 0.00 0.00 0.00 35.80 0.00
August 3111.03 24-AUG-18:53 7041.55 6639.35 0.00 0.00 0.00 0.00 0.00 43.53 0.00
September 2827.80 01-SEP-17:06 8801.94 8714.15 0.00 0.00 0.00 0.00 0.00 32.71 0.00
October 3530.68 08-OCT-23:16 17603.88 6224.39 0.00 0.00 0.00 0.00 0.00 0.00 137.45
November 3158.99 01-NOV-06:40 2011.87 2074.80 0.00 0.00 0.00 0.00 0.00 0.00 132.35
December 3096.66 04-DEC-07:51 7041.55 7261.79 0.00 0.00 0.00 0.00 0.00 0.00 130.64
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2647.31   2011.87 622.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3530.68   17603.88 9959.03 0.00 0.00 0.00 0.00 0.00 43.53 137.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3702.02 19-JAN-16:01 874.80 529.77 450.41 0.00 0.00 0.00 0.00 0.00 102.89
February 3646.66 24-FEB-16:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 105.43
March 3806.28 24-MAR-15:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 93.84
April 4206.82 10-APR-20:41 1602.00 1871.00 1817.45 0.00 0.00 0.00 0.00 0.00 75.59
May 4185.44 02-MAY-18:21 1386.00 1871.00 1211.63 0.00 0.00 0.00 0.00 0.00 72.39
June 4225.40 04-JUN-21:51 1386.00 1786.91 895.56 0.00 0.00 0.00 0.00 0.00 54.56
July 3773.94 01-JUL-21:51 1386.00 1786.91 895.56 0.00 0.00 0.00 0.00 0.00 40.87
August 3933.55 30-AUG-08:51 324.00 832.49 1019.35 0.00 0.00 0.00 0.00 0.00 7.22
September 4069.65 11-SEP-21:51 1800.00 1408.50 895.56 0.00 0.00 0.00 0.00 0.00 47.33
October 4048.73 30-OCT-16:41 972.00 588.63 1264.31 0.00 0.00 0.00 0.00 0.00 69.14
November 3707.48 03-NOV-15:01 680.40 412.04 350.32 0.00 0.00 0.00 0.00 0.00 39.90
December 3623.03 17-DEC-16:01 378.00 485.62 387.20 0.00 0.00 0.00 0.00 0.00 89.34
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3623.03   324.00 412.04 350.32 0.00 0.00 0.00 0.00 0.00 7.22
Maximum of Months 4225.40   1800.00 1871.00 1817.45 0.00 0.00 0.00 0.00 0.00 105.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1356.23 17-JAN-16:01 680.40 411.99 350.28 0.00 0.00 0.00 0.00 0.00 85.11
February 2841.65 20-FEB-16:01 378.00 485.56 387.15 0.00 0.00 0.00 0.00 0.00 101.57
March 3650.86 07-MAR-16:01 972.00 588.56 500.40 0.00 0.00 0.00 0.00 0.00 105.66
April 3973.73 09-APR-18:11 1170.00 2102.00 1211.49 0.00 0.00 0.00 0.00 0.00 73.66
May 4006.97 02-MAY-18:21 1386.00 1870.78 1211.49 0.00 0.00 0.00 0.00 0.00 70.57
June 4092.76 04-JUN-21:51 1386.00 1786.70 895.45 0.00 0.00 0.00 0.00 0.00 53.83
July 3683.34 03-JUL-18:51 1386.00 1870.78 1211.49 0.00 0.00 0.00 0.00 0.00 0.25
August 3742.42 28-AUG-21:51 1800.00 1408.34 895.45 0.00 0.00 0.00 0.00 0.00 33.34
September 3740.79 11-SEP-21:51 1800.00 1408.34 895.45 0.00 0.00 0.00 0.00 0.00 42.33
October 3613.67 30-OCT-16:41 972.00 588.56 1264.17 0.00 0.00 0.00 0.00 0.00 59.89
November 3538.15 03-NOV-15:01 680.40 411.99 350.28 0.00 0.00 0.00 0.00 0.00 38.69
December 693.82 08-DEC-16:03 583.20 353.14 300.24 0.00 0.00 0.00 0.00 0.00 110.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 693.82   378.00 353.14 300.24 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 4092.76   1800.00 2102.00 1264.17 0.00 0.00 0.00 0.00 0.00 110.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2009.01 19-JAN-16:01 874.80 333.03 441.28 0.00 0.00 0.00 0.00 0.00 53.62
February 2007.55 18-FEB-16:01 540.00 436.11 541.93 0.00 0.00 0.00 0.00 0.00 61.16
March 2039.05 24-MAR-15:01 972.00 370.03 490.32 0.00 0.00 0.00 0.00 0.00 48.53
April 2097.09 07-APR-21:51 1620.00 796.89 789.67 0.00 0.00 0.00 0.00 0.00 19.59
May 2129.62 27-MAY-21:51 1386.00 1123.31 877.41 0.00 0.00 0.00 0.00 0.00 16.40
June 2123.64 04-JUN-08:51 486.00 666.06 1439.98 0.00 0.00 0.00 0.00 0.00 0.43
July 2029.68 11-JUL-08:51 324.00 523.33 998.70 0.00 0.00 0.00 0.00 1.31 0.00
August 2118.19 30-AUG-08:51 324.00 523.33 998.70 0.00 0.00 0.00 0.00 0.00 4.98
September 2204.11 03-SEP-08:51 540.00 740.06 1599.98 0.00 0.00 0.00 0.00 0.00 5.89
October 2226.63 30-OCT-16:41 972.00 370.03 1238.69 0.00 0.00 0.00 0.00 0.00 37.38
November 1995.05 02-NOV-15:01 680.40 259.02 343.22 0.00 0.00 0.00 0.00 0.00 21.91
December 1984.17 17-DEC-16:01 378.00 305.28 379.35 0.00 0.00 0.00 0.00 0.00 46.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1984.17   324.00 259.02 343.22 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2226.63   1620.00 1123.31 1599.98 0.00 0.00 0.00 0.00 1.31 61.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 34021.30 22-JAN-22:52 143940.10 11459.46 40487.42 0.00 0.00 0.00 0.00 0.00 324.85
February 31415.85 23-FEB-21:07 239900.16 30558.57 67479.03 0.00 0.00 0.00 0.00 0.00 339.97
March 32302.12 28-MAR-21:37 80966.30 6875.68 20243.71 0.00 0.00 0.00 0.00 0.00 296.37
April 33011.94 12-APR-22:10 215910.14 9167.57 53983.22 0.00 0.00 0.00 0.00 0.00 307.40
May 33545.97 16-MAY-03:39 269887.68 3819.82 22493.01 0.00 0.00 0.00 0.00 0.00 269.95
June 23734.00 19-JUN-21:20 26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 72.81 0.00
July 23508.52 07-JUL-22:00 26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 69.22 0.00
August 23894.39 04-AUG-21:20 26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 110.57 0.00
September 26628.33 24-SEP-05:49 146938.85 7486.85 39362.76 0.00 0.00 0.00 0.00 0.00 247.47
October 31843.23 27-OCT-23:56 269887.68 7639.64 22493.01 0.00 0.00 0.00 0.00 0.00 300.40
November 32131.77 09-NOV-02:15 269887.68 3819.82 22493.01 0.00 0.00 0.00 0.00 0.00 266.06
December 31513.19 04-DEC-23:30 134943.84 5729.73 33739.51 0.00 0.00 0.00 0.00 0.00 282.58
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 23508.52   26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34021.30   269887.68 30558.57 67479.03 0.00 0.00 0.00 0.00 110.57 339.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37418.61 22-JAN-22:52 143940.10 11459.46 40487.42 0.00 0.00 0.00 0.00 0.00 325.12
February 33153.67 23-FEB-21:07 239900.16 30558.57 67479.03 0.00 0.00 0.00 0.00 0.00 341.56
March 34207.62 28-MAR-21:37 80966.30 6875.68 20243.71 0.00 0.00 0.00 0.00 0.00 298.73
April 34756.41 12-APR-22:10 215910.14 9167.57 53983.22 0.00 0.00 0.00 0.00 0.00 308.54
May 35142.30 16-MAY-03:39 269887.68 3819.82 22493.01 0.00 0.00 0.00 0.00 0.00 269.99
June 24986.07 19-JUN-21:20 26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 72.76 0.00
July 24697.35 10-JUL-21:20 26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 48.23 0.00
August 25104.44 04-AUG-21:20 26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 110.54 0.00
September 29533.41 24-SEP-05:49 146938.85 7486.85 39362.76 0.00 0.00 0.00 0.00 0.00 247.57
October 33464.25 27-OCT-23:56 269887.68 7639.64 22493.01 0.00 0.00 0.00 0.00 0.00 301.13
November 33893.19 08-NOV-00:14 134943.84 3819.82 11246.50 0.00 0.00 0.00 0.00 0.00 302.21
December 36836.00 04-DEC-07:51 83965.06 12478.08 47235.32 0.00 0.00 0.00 0.00 0.00 317.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 24697.35   26988.77 2291.89 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37418.61   269887.68 30558.57 67479.03 0.00 0.00 0.00 0.00 110.54 341.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37092.77 13-JAN-11:31 3735.98 2354.57 104389.99 131208.19 0.00 0.00 0.00 0.00 271.72
February 37795.65 20-FEB-16:28 8005.68 2690.94 149128.56 224928.32 0.00 0.00 0.00 0.00 251.80
March 35628.44 20-MAR-14:44 5603.98 2354.57 104389.99 104966.55 0.00 0.00 0.00 0.00 260.70
April 36060.19 14-APR-18:06 18679.92 10763.76 149128.56 149952.21 0.00 0.00 0.00 0.00 279.24
May 33442.29 02-MAY-05:34 18679.92 5381.88 125511.30 74976.11 0.00 0.00 0.00 0.00 254.32
June 32294.09 22-JUN-18:10 11207.95 6458.26 89477.13 89971.33 0.00 0.00 0.00 63.74 0.00
July 31754.58 09-JUL-10:40 2401.70 1210.92 44738.57 56232.08 0.00 0.00 0.00 79.08 0.00
August 33074.50 22-AUG-15:18 5337.12 1345.47 59651.42 89971.33 0.00 0.00 0.00 81.28 0.00
September 32120.82 01-SEP-17:01 9339.96 5650.98 104389.99 157449.82 0.00 0.00 0.00 51.49 0.00
October 37457.77 29-OCT-08:62 8005.68 2421.85 89477.13 67478.50 0.00 0.00 0.00 0.00 276.69
November 37266.73 29-NOV-10:49 4269.70 2690.94 119302.85 149952.21 0.00 0.00 0.00 0.00 248.45
December 39688.05 04-DEC-07:51 7471.97 4709.15 104389.99 78724.91 0.00 0.00 0.00 0.00 295.14
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 31754.58   2401.70 1210.92 44738.57 56232.08 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39688.05   18679.92 10763.76 149128.56 224928.32 0.00 0.00 0.00 81.28 295.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5291.61 22-JAN-22:52 12775.68 6587.56 0.00 0.00 0.00 0.00 0.00 0.00 239.15
February 6089.07 20-FEB-16:07 5589.36 3074.19 0.00 0.00 0.00 0.00 0.00 0.00 223.24
March 6621.16 12-MAR-00:37 11178.72 3952.54 0.00 0.00 0.00 0.00 0.00 0.00 214.93
April 6682.92 11-APR-06:16 8517.12 8783.41 0.00 0.00 0.00 0.00 0.00 0.00 237.23
May 5579.20 01-MAY-01:13 7186.32 658.76 0.00 0.00 0.00 0.00 0.00 0.00 192.69
June 6416.37 01-JUN-13:50 1064.64 1097.93 0.00 0.00 0.00 0.00 0.00 62.11 0.00
July 6899.70 08-JUL-12:00 798.48 548.96 0.00 0.00 0.00 0.00 0.00 115.44 0.00
August 7071.84 16-AUG-12:50 532.32 548.96 0.00 0.00 0.00 0.00 0.00 111.28 0.00
September 6376.91 01-SEP-14:10 798.48 548.96 0.00 0.00 0.00 0.00 0.00 97.70 0.00
October 6712.13 08-OCT-23:16 18631.20 6587.56 0.00 0.00 0.00 0.00 0.00 0.00 234.06
November 6080.84 29-NOV-10:49 4258.56 4391.71 0.00 0.00 0.00 0.00 0.00 0.00 219.30
December 6197.36 04-DEC-07:51 7452.48 7685.49 0.00 0.00 0.00 0.00 0.00 0.00 232.95
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5291.61   532.32 548.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7071.84   18631.20 8783.41 0.00 0.00 0.00 0.00 0.00 115.44 239.15



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.387885E+12 253367.40 18-JAN-20:40 0.635787E+12 547081.94 14-JAN-17:30
February 0.348811E+12 249313.67 02-FEB-20:19 0.570225E+12 540703.37 06-FEB-17:19
March 0.387132E+12 270500.54 27-MAR-19:10 0.531394E+12 473157.08 05-MAR-19:40
April 0.388957E+12 323863.09 07-APR-19:10 0.470615E+12 492851.89 01-APR-18:00
May 0.441050E+12 356958.97 29-MAY-19:19 0.432514E+12 354855.93 04-MAY-18:10
June 0.583061E+12 426124.44 19-JUN-19:30 0.395090E+12 351822.03 01-JUN-17:00
July 0.713060E+12 424907.13 20-JUL-19:19 0.399465E+12 352162.89 11-JUL-17:10
August 0.675591E+12 458577.10 04-AUG-19:10 0.398013E+12 349365.79 31-AUG-17:19
September 0.529644E+12 419179.40 07-SEP-19:00 0.390543E+12 350548.98 29-SEP-17:00
October 0.452297E+12 341888.44 05-OCT-19:10 0.432366E+12 396045.94 28-OCT-19:00
November 0.379948E+12 258378.13 06-NOV-20:49 0.497351E+12 524031.33 30-NOV-18:00
December 0.390662E+12 256809.03 19-DEC-20:49 0.559987E+12 506036.28 31-DEC-17:00
             
Annual Sum or Average 0.567810E+13     0.571335E+13    
Minimum of Months 0.348811E+12 249313.67   0.390543E+12 349365.79  
Maximum of Months 0.713060E+12 458577.10   0.635787E+12 547081.94  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.744766E+11 0.271185E+11 0.140828E+12 0.552134E+11 0.450269E+11 0.469721E+10 0.00 0.148795E+10 0.00 0.00 0.261378E+11 0.770493E+10 0.00
February 0.669650E+11 0.227423E+11 0.127191E+12 0.498701E+11 0.399643E+11 0.464997E+10 0.00 0.194949E+10 0.00 0.00 0.238515E+11 0.696263E+10 0.00
March 0.737571E+11 0.227724E+11 0.140882E+12 0.552165E+11 0.442438E+11 0.662904E+10 0.00 0.646853E+10 0.00 0.00 0.242276E+11 0.770322E+10 0.00
April 0.710552E+11 0.196279E+11 0.136245E+12 0.534312E+11 0.439241E+11 0.837124E+10 0.00 0.261074E+11 0.00 0.00 0.176395E+11 0.746493E+10 0.00
May 0.729442E+11 0.181458E+11 0.140860E+12 0.552139E+11 0.467993E+11 0.112328E+11 0.00 0.751823E+11 0.00 0.00 0.766991E+10 0.770462E+10 0.00
June 0.704184E+11 0.164334E+11 0.136336E+12 0.534341E+11 0.488954E+11 0.117433E+11 0.00 0.220098E+12 0.00 0.00 0.130629E+11 0.745682E+10 0.00
July 0.728634E+11 0.174849E+11 0.140770E+12 0.552104E+11 0.541960E+11 0.128105E+11 0.00 0.322119E+12 0.00 0.00 0.245478E+11 0.771251E+10 0.00
August 0.731630E+11 0.193074E+11 0.140892E+12 0.552160E+11 0.555785E+11 0.126482E+11 0.00 0.288002E+12 0.00 0.00 0.177206E+11 0.770432E+10 0.00
September 0.712907E+11 0.209798E+11 0.136256E+12 0.534315E+11 0.486383E+11 0.115064E+11 0.00 0.165780E+12 0.00 0.00 0.913092E+10 0.746642E+10 0.00
October 0.740250E+11 0.241844E+11 0.140818E+12 0.552130E+11 0.482676E+11 0.108972E+11 0.00 0.737737E+11 0.00 0.00 0.121235E+11 0.770308E+10 0.00
November 0.718864E+11 0.256064E+11 0.136330E+12 0.534332E+11 0.443438E+11 0.684978E+10 0.00 0.727884E+10 0.00 0.00 0.217074E+11 0.744906E+10 0.00
December 0.744728E+11 0.276493E+11 0.140770E+12 0.552118E+11 0.446872E+11 0.582068E+10 0.00 0.291658E+10 0.00 0.00 0.262244E+11 0.771298E+10 0.00
                           
Annual Sum or Average 0.867318E+12 0.262052E+12 0.165818E+13 0.650095E+12 0.564565E+12 0.107856E+12 0.00 0.119116E+13 0.00 0.00 0.224044E+12 0.907455E+11 0.00
Minimum of Months 0.669650E+11 0.164334E+11 0.127191E+12 0.498701E+11 0.399643E+11 0.464997E+10 0.00 0.148795E+10 0.00 0.00 0.766991E+10 0.696263E+10 0.00
Maximum of Months 0.744766E+11 0.276493E+11 0.140892E+12 0.552165E+11 0.555785E+11 0.128105E+11 0.00 0.322119E+12 0.00 0.00 0.262244E+11 0.771298E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.191208E+12 0.00 0.292661E+12 0.00 0.00
February 0.137204E+12 0.00 0.166830E+12 0.00 0.266191E+12 0.00 0.00
March 0.152024E+12 0.00 0.890228E+11 0.00 0.290348E+12 0.00 0.00
April 0.146956E+12 0.00 0.522305E+11 0.00 0.271429E+12 0.00 0.00
May 0.151978E+12 0.00 0.126713E+11 0.00 0.267864E+12 0.00 0.00
June 0.147114E+12 0.00 0.432272E+09 0.00 0.247543E+12 0.00 0.00
July 0.151820E+12 0.00 0.117192E+09 0.00 0.247527E+12 0.00 0.00
August 0.152039E+12 0.00 0.571115E+09 0.00 0.245403E+12 0.00 0.00
September 0.146971E+12 0.00 0.176436E+10 0.00 0.241808E+12 0.00 0.00
October 0.151903E+12 0.00 0.206441E+11 0.00 0.259818E+12 0.00 0.00
November 0.147091E+12 0.00 0.865848E+11 0.00 0.263675E+12 0.00 0.00
December 0.151820E+12 0.00 0.123718E+12 0.00 0.284448E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.745795E+12 0.00 0.317871E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.117192E+09 0.00 0.241808E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.191208E+12 0.00 0.292661E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 71560.59 02-JAN-20:10 16690.39 01-JAN-00:10 89171.45 02-JAN-07:10 39721.54 02-JAN-07:19 34316.47 19-JAN-22:49 4993.98 17-JAN-10:30 0.00 01-JAN-00:10
February 71560.59 01-FEB-20:10 16690.39 01-FEB-00:10 89171.45 01-FEB-07:10 39721.54 01-FEB-07:19 30029.18 01-FEB-21:40 5078.23 06-FEB-09:00 0.00 01-FEB-00:10
March 71560.59 01-MAR-20:10 16690.39 01-MAR-00:10 89171.45 01-MAR-07:10 39721.54 13-MAR-06:19 35736.85 04-MAR-06:49 4976.52 24-MAR-08:30 0.00 01-MAR-00:10
April 71560.59 03-APR-19:10 16690.39 01-APR-00:10 89171.45 03-APR-06:10 39720.28 14-APR-06:19 30216.08 07-APR-21:00 4954.07 15-APR-06:40 0.00 01-APR-00:10
May 71560.59 01-MAY-19:10 16690.39 01-MAY-00:10 89171.45 01-MAY-06:10 39720.28 04-MAY-06:19 34608.75 31-MAY-21:00 4928.26 01-MAY-02:30 0.00 01-MAY-00:10
June 71560.59 01-JUN-19:19 16690.39 01-JUN-00:10 89171.45 01-JUN-06:10 39719.36 21-JUN-06:19 35596.74 23-JUN-21:00 5620.55 19-JUN-18:10 0.00 01-JUN-00:10
July 71560.59 03-JUL-19:30 16690.39 01-JUL-00:10 89171.45 03-JUL-06:10 39719.67 24-JUL-06:19 36075.25 25-JUL-21:00 5833.18 20-JUL-18:10 0.00 01-JUL-00:10
August 71560.59 01-AUG-19:10 16690.39 01-AUG-00:10 89171.45 01-AUG-06:10 39719.36 07-AUG-06:19 37980.59 18-AUG-21:10 5899.36 16-AUG-18:10 0.00 01-AUG-00:10
September 71560.59 01-SEP-19:10 16690.39 01-SEP-00:10 89171.45 01-SEP-06:10 39721.06 27-SEP-06:19 44381.45 01-SEP-20:10 5785.58 07-SEP-19:00 0.00 01-SEP-00:10
October 71560.59 02-OCT-19:10 16690.39 01-OCT-00:10 89171.45 02-OCT-06:10 39721.54 10-OCT-06:19 34926.31 05-OCT-21:00 4959.20 28-OCT-00:10 0.00 01-OCT-00:10
November 71560.59 01-NOV-19:10 16690.39 01-NOV-00:10 89171.45 01-NOV-06:10 39721.54 01-NOV-06:19 34237.59 07-NOV-21:40 5006.16 27-NOV-06:49 0.00 01-NOV-00:10
December 71560.59 01-DEC-20:10 16690.39 01-DEC-00:10 89171.45 01-DEC-07:10 39721.54 01-DEC-07:19 30795.20 26-DEC-21:40 5068.12 16-DEC-21:49 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 71560.59   16690.39   89171.45   39719.36   30029.18   4928.26   0.00  
Maximum of Months 71560.59   16690.39   89171.45   39721.54   44381.45   5899.36   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 6386.72 21-JAN-22:00 0.00 0.00 9938.94 01-JAN-00:10 4738.69 30-JAN-19:10 0.00
February 10147.90 02-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 4738.70 15-FEB-19:10 0.00
March 64246.48 27-MAR-16:10 0.00 0.00 9938.94 01-MAR-00:20 4738.36 17-MAR-18:10 0.00
April 106362.55 07-APR-15:09 0.00 0.00 9938.94 01-APR-00:10 4738.42 26-APR-18:19 0.00
May 124064.70 31-MAY-15:20 0.00 0.00 9938.94 01-MAY-00:10 4738.52 02-MAY-18:30 0.00
June 189793.27 19-JUN-18:10 0.00 0.00 9938.94 01-JUN-10:50 4738.28 12-JUN-06:10 0.00
July 181435.32 20-JUL-15:20 0.00 0.00 9938.94 01-JUL-08:09 4738.28 03-JUL-06:40 0.00
August 202267.42 16-AUG-15:20 0.00 0.00 9938.94 01-AUG-00:10 4738.70 17-AUG-18:10 0.00
September 159449.91 07-SEP-19:00 0.00 0.00 9938.94 01-SEP-00:10 4738.19 13-SEP-18:19 0.00
October 121842.33 04-OCT-15:09 0.00 0.00 9938.94 01-OCT-00:10 4738.34 20-OCT-06:10 0.00
November 43232.37 04-NOV-11:00 0.00 0.00 9938.94 01-NOV-00:10 4738.58 22-NOV-19:10 0.00
December 14124.32 18-DEC-10:00 0.00 0.00 9938.94 01-DEC-00:20 4738.57 13-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 6386.72   0.00 0.00 9938.94   4738.19   0.00
Maximum of Months 202267.42   0.00 0.00 9938.94   4738.70   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 253367.40 18-JAN-20:40 71560.59 86439.81 16690.39 32090.84 23946.13 4622.94 0.00 1822.26 0.00
February 249313.67 02-FEB-20:19 71560.59 86439.81 16690.39 32090.84 20143.42 4492.57 0.00 1577.75 0.00
March 270500.54 27-MAR-19:10 71560.59 86439.81 16690.39 32081.53 20679.37 4278.36 0.00 32727.14 0.00
April 323863.09 07-APR-19:10 71560.59 86439.81 16690.39 32081.53 23343.36 4473.90 0.00 81848.74 0.00
May 356958.97 29-MAY-19:19 66393.55 84978.71 16690.39 32035.84 26268.15 4744.37 0.00 110528.66 0.00
June 426124.44 19-JUN-19:30 71560.59 86439.81 16690.39 32090.84 30189.35 5338.72 0.00 167383.60 0.00
July 424907.13 20-JUL-19:19 71560.59 86439.81 16690.39 32090.00 28881.20 5689.52 0.00 167465.96 0.00
August 458577.10 04-AUG-19:10 71560.59 86439.81 16690.39 32080.78 32042.67 5611.84 0.00 198798.26 0.00
September 419179.40 07-SEP-19:00 71560.59 86439.81 16690.39 32090.84 31202.89 5785.58 0.00 159449.91 0.00
October 341888.44 05-OCT-19:10 71560.59 86439.81 16690.39 32081.53 24482.96 4521.27 0.00 91601.44 0.00
November 258378.13 06-NOV-20:49 71560.59 86439.81 16690.39 32090.84 25116.86 4411.74 0.00 5884.42 0.00
December 256809.03 19-DEC-20:49 71560.59 86439.81 16690.39 32090.84 28024.28 4558.96 0.00 2052.29 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 249313.67   66393.55 84978.71 16690.39 32035.84 20143.42 4278.36 0.00 1577.75 0.00
Maximum of Months 458577.10   71560.59 86439.81 16690.39 32090.84 32042.67 5785.58 0.00 198798.26 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 238365.65 02-JAN-09:09 0.00 291059.40 30-JAN-21:30 0.00
February 104248.32 01-FEB-18:10 0.00 236739.53 06-FEB-09:09 0.00 291395.33 09-FEB-21:30 0.00
March 104248.32 01-MAR-18:10 0.00 183956.49 25-MAR-23:30 0.00 289486.69 06-MAR-21:49 0.00
April 104248.32 01-APR-17:10 0.00 182505.34 15-APR-06:49 0.00 280876.97 04-APR-20:10 0.00
May 104248.32 01-MAY-17:10 0.00 126664.68 15-MAY-02:39 0.00 253570.07 01-MAY-20:19 0.00
June 104248.32 01-JUN-17:10 0.00 34441.49 01-JUN-14:50 0.00 248222.38 02-JUN-20:40 0.00
July 104248.32 01-JUL-17:10 0.00 20415.75 11-JUL-17:00 0.00 245913.03 06-JUL-20:10 0.00
August 104248.32 01-AUG-17:10 0.00 40856.83 20-AUG-13:39 0.00 245485.56 22-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 51785.10 24-SEP-05:00 0.00 246953.87 29-SEP-20:49 0.00
October 104248.32 02-OCT-17:10 0.00 136264.71 18-OCT-00:49 0.00 250084.94 30-OCT-20:30 0.00
November 104248.32 01-NOV-17:10 0.00 176146.44 15-NOV-16:30 0.00 261829.59 29-NOV-21:00 0.00
December 104248.32 01-DEC-18:10 0.00 189379.97 04-DEC-09:00 0.00 286532.00 29-DEC-21:00 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 20415.75   0.00 245485.56   0.00
Maximum of Months 104248.32   0.00 238365.65   0.00 291395.33   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 16.17 25.11 16.17 25.11
February 0.00 0.00 0.00 0.00 4.83 25.33 4.83 25.33
March 0.00 0.00 0.00 0.00 37.67 25.06 37.67 25.06
April 0.00 0.00 0.00 0.00 29.17 24.99 29.17 24.99
May 0.00 0.00 0.00 0.00 1.50 25.04 1.50 25.04
June 0.00 0.00 0.00 0.00 0.67 25.08 0.67 25.08
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.50 24.77 0.50 24.77
September 0.00 0.00 0.00 0.00 0.83 24.69 0.83 24.69
October 0.00 0.00 0.00 0.00 12.00 25.08 12.00 25.08
November 0.00 0.00 0.00 0.00 30.00 24.94 30.00 24.94
December 0.00 0.00 0.00 0.00 19.33 25.15 19.33 25.15
                 
Annual Sum or Average 0.00   0.00   152.67 25.05 152.67 25.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 37.67 25.33 37.67 25.33



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 24.62 0.17 24.62
                 
Annual Sum or Average 0.00   0.00   0.17 24.62 0.17 24.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 24.62 0.17 24.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 20.48 1.50 20.48 0.00 20.48 0.00 20.48
February 0.67 20.51 0.67 20.51 0.00 20.51 0.00 20.51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 21.82 0.67 21.82
May 0.00 0.00 0.00 0.00 2.50 21.82 2.50 21.82
June 0.00 0.00 0.00 0.00 4.33 21.80 4.33 21.80
July 0.00 0.00 0.00 0.00 3.67 21.76 3.67 21.76
August 0.00 0.00 0.00 0.00 5.00 21.81 5.00 21.81
September 0.00 0.00 0.00 0.00 3.50 21.79 3.50 21.79
October 0.00 0.00 0.00 0.00 0.67 21.75 0.67 21.75
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 20.55 0.33 20.55 0.00 20.55 0.00 20.55
                 
Annual Sum or Average 2.50 20.50 2.50 20.50 20.33 21.54 20.33 21.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 20.55 1.50 20.55 5.00 21.82 5.00 21.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 20.46 2.50 20.46 0.00 20.46 0.00 20.46
February 2.17 20.48 2.17 20.48 0.00 20.48 0.00 20.48
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.82 0.33 21.82
May 0.00 0.00 0.00 0.00 1.67 21.86 1.67 21.86
June 0.00 0.00 0.00 0.00 4.17 21.80 4.17 21.80
July 0.00 0.00 0.00 0.00 3.00 21.77 3.00 21.77
August 0.00 0.00 0.00 0.00 2.67 21.74 2.67 21.74
September 0.00 0.00 0.00 0.00 1.17 21.75 1.17 21.75
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.54 0.50 20.54 0.00 20.54 0.00 20.54
                 
Annual Sum or Average 5.17 20.47 5.17 20.47 13.00 21.20 13.00 21.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.50 20.54 2.50 20.54 4.17 21.86 4.17 21.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.50 20.26 3.50 20.26 0.00 20.26 0.00 20.26
February 3.33 20.26 3.33 20.26 0.00 20.26 0.00 20.26
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.33 21.79 1.33 21.79
June 0.00 0.00 0.00 0.00 5.50 21.85 5.50 21.85
July 0.00 0.00 0.00 0.00 6.17 21.83 6.17 21.83
August 0.00 0.00 0.00 0.00 3.00 21.76 3.00 21.76
September 0.00 0.00 0.00 0.00 1.67 21.80 1.67 21.80
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.42 0.50 20.42 0.00 20.42 0.00 20.42
December 1.50 20.44 1.50 20.44 0.00 20.44 0.00 20.44
                 
Annual Sum or Average 8.83 20.30 8.83 20.30 17.67 21.06 17.67 21.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 20.44 3.50 20.44 6.17 21.85 6.17 21.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 20.47 1.67 20.47 0.00 20.47 0.00 20.47
February 0.67 20.52 0.67 20.52 0.00 20.52 0.00 20.52
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 22.08 0.50 22.08
May 0.00 0.00 0.00 0.00 3.50 22.26 3.50 22.26
June 0.00 0.00 0.00 0.00 5.67 22.19 5.67 22.19
July 0.00 0.00 0.00 0.00 6.33 22.12 6.33 22.12
August 0.00 0.00 0.00 0.00 7.17 22.20 7.17 22.20
September 0.00 0.00 0.00 0.00 6.33 22.20 6.33 22.20
October 0.00 0.00 0.00 0.00 1.67 22.17 1.67 22.17
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.54 0.50 20.54 0.00 20.54 0.00 20.54
                 
Annual Sum or Average 2.83 20.49 2.83 20.49 31.17 21.92 31.17 22.04
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 20.54 1.67 20.54 7.17 22.26 7.17 22.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.00 20.46 3.00 20.46 0.00 20.46 0.00 20.46
February 2.50 20.50 2.50 20.50 0.00 20.50 0.00 20.50
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 22.12 0.33 22.12
May 0.00 0.00 0.00 0.00 3.50 22.26 3.50 22.26
June 0.00 0.00 0.00 0.00 6.17 22.17 6.17 22.17
July 0.00 0.00 0.00 0.00 6.67 22.13 6.67 22.13
August 0.00 0.00 0.00 0.00 5.50 22.22 5.50 22.22
September 0.00 0.00 0.00 0.00 4.00 22.22 4.00 22.22
October 0.00 0.00 0.00 0.00 1.17 22.03 1.17 22.03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 20.52 0.67 20.52 0.00 20.52 0.00 20.52
                 
Annual Sum or Average 6.17 20.48 6.17 20.48 27.33 21.65 27.33 21.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.00 20.52 3.00 20.52 6.67 22.26 6.67 22.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 20.45 1.50 20.45 0.00 20.45 0.00 20.45
February 0.67 20.51 0.67 20.51 0.00 20.51 0.00 20.51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 21.87 1.00 21.87
May 0.00 0.00 0.00 0.00 3.67 21.88 3.67 21.88
June 0.00 0.00 0.00 0.00 5.00 21.88 5.00 21.88
July 0.00 0.00 0.00 0.00 4.67 21.78 4.67 21.78
August 0.00 0.00 0.00 0.00 6.00 21.83 6.00 21.83
September 0.00 0.00 0.00 0.00 4.17 21.82 4.17 21.82
October 0.00 0.00 0.00 0.00 0.83 21.81 0.83 21.81
November 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
December 0.33 20.54 0.33 20.54 0.00 20.54 0.00 20.54
                 
Annual Sum or Average 2.50 20.48 2.50 20.48 25.50 21.61 25.50 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 20.54 1.50 20.54 6.00 21.88 6.00 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.83 20.44 2.83 20.44 0.00 20.44 0.00 20.44
February 1.83 20.43 1.83 20.43 0.00 20.43 0.00 20.43
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 21.83 0.67 21.83
May 0.00 0.00 0.00 0.00 3.33 21.87 3.33 21.87
June 0.00 0.00 0.00 0.00 5.00 21.88 5.00 21.88
July 0.00 0.00 0.00 0.00 4.67 21.77 4.67 21.77
August 0.00 0.00 0.00 0.00 3.83 21.77 3.83 21.77
September 0.00 0.00 0.00 0.00 1.17 21.78 1.17 21.78
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.53 0.50 20.53 0.00 20.53 0.00 20.53
                 
Annual Sum or Average 5.17 20.44 5.17 20.44 18.67 21.33 18.67 21.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.83 20.53 2.83 20.53 5.00 21.88 5.00 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 20.41 0.83 20.41 0.00 20.41 0.00 20.41
February 0.17 20.53 0.17 20.53 0.00 20.53 0.00 20.53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.73 0.33 21.73
May 0.00 0.00 0.00 0.00 0.83 21.73 0.83 21.73
June 0.00 0.00 0.00 0.00 2.33 21.76 2.33 21.76
July 0.00 0.00 0.00 0.00 3.17 21.77 3.17 21.77
August 0.00 0.00 0.00 0.00 5.50 21.78 5.50 21.78
September 0.00 0.00 0.00 0.00 6.50 21.87 6.50 21.87
October 0.00 0.00 0.00 0.00 3.83 21.89 3.83 21.89
November 0.00 0.00 0.00 0.00 0.17 21.87 0.17 21.87
December 0.33 20.53 0.33 20.53 0.00 20.53 0.00 20.53
                 
Annual Sum or Average 1.33 20.45 1.33 20.45 22.67 21.68 22.67 21.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 20.53 0.83 20.53 6.50 21.89 6.50 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.00 24.69 1.00 24.69
February 0.00 0.00 0.00 0.00 0.17 24.63 0.17 24.63
March 0.00 0.00 0.00 0.00 3.33 24.72 3.33 24.72
April 0.00 0.00 0.00 0.00 2.50 24.68 2.50 24.68
May 0.00 0.00 0.00 0.00 1.17 24.65 1.17 24.65
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 1.00 24.78 1.00 24.78
November 0.00 0.00 0.00 0.00 2.00 24.69 2.00 24.69
December 0.00 0.00 0.00 0.00 0.83 24.63 0.83 24.63
                 
Annual Sum or Average 0.00   0.00   12.00 24.70 12.00 24.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.33 24.78 3.33 24.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.83 24.72 1.83 24.72
February 0.00 0.00 0.00 0.00 0.17 24.80 0.17 24.80
March 0.00 0.00 0.00 0.00 4.83 24.74 4.83 24.74
April 0.00 0.00 0.00 0.00 3.50 24.71 3.50 24.71
May 0.00 0.00 0.00 0.00 1.67 24.67 1.67 24.67
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 1.33 24.81 1.33 24.81
November 0.00 0.00 0.00 0.00 3.50 24.69 3.50 24.69
December 0.00 0.00 0.00 0.00 1.50 24.76 1.50 24.76
                 
Annual Sum or Average 0.00   0.00   18.33 24.72 18.33 24.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.83 24.81 4.83 24.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 38.83 25.03 38.83 25.03
February 0.00 0.00 0.00 0.00 17.50 25.23 17.50 25.23
March 0.00 0.00 0.00 0.00 58.33 25.10 58.33 25.10
April 0.00 0.00 0.00 0.00 54.67 24.99 54.67 24.99
May 0.00 0.00 0.00 0.00 5.50 24.86 5.50 24.86
June 0.00 0.00 0.00 0.00 6.33 24.82 6.33 24.82
July 0.00 0.00 0.00 0.00 1.17 24.74 1.17 24.74
August 0.00 0.00 0.00 0.00 5.33 24.90 5.33 24.90
September 0.00 0.00 0.00 0.00 0.83 24.78 0.83 24.78
October 0.00 0.00 0.00 0.00 20.67 25.13 20.67 25.13
November 0.00 0.00 0.00 0.00 54.50 25.03 54.50 25.03
December 0.00 0.00 0.00 0.00 40.00 25.06 40.00 25.06
                 
Annual Sum or Average 0.00   0.00   303.67 25.05 303.67 25.05
Minimum of Months 0.00 0.00 0.00 0.00 0.83 24.74 0.83 24.74
Maximum of Months 0.00 0.00 0.00 0.00 58.33 25.23 58.33 25.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 717.33 23.43 0.00 23.43 0.00 23.43
February 672.00 23.06 0.00 23.06 0.00 23.06
March 744.00 22.84 0.00 22.84 0.00 22.84
April 720.00 22.69 0.00 22.69 0.00 22.69
May 744.00 22.43 0.00 22.43 0.00 22.43
June 718.00 22.76 0.00 22.76 0.00 22.76
July 576.83 23.01 4.50 23.01 0.00 23.01
August 296.17 23.19 169.67 23.43 0.00 23.43
September 133.50 23.55 272.67 23.81 0.00 23.81
October 247.33 23.87 225.67 23.92 0.00 23.92
November 348.00 23.84 19.83 23.85 0.00 23.85
December 679.67 23.76 0.00 23.76 0.00 23.76
             
Annual Sum or Average 6596.83 23.09 692.33 23.17 0.00 23.17
Minimum of Months 133.50 22.43 0.00 22.43 0.00 22.43
Maximum of Months 744.00 23.87 272.67 23.92 0.00 23.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 727.67 21.12 343.83 21.09 341.33 21.07
February 645.33 21.17 312.00 21.12 311.83 21.09
March 691.67 21.24 114.83 21.29 92.17 21.26
April 649.33 21.34 40.83 21.43 14.33 21.42
May 655.50 21.54 33.17 21.65 0.00 21.65
June 447.17 22.11 164.83 22.51 0.00 22.51
July 229.50 22.38 365.50 23.13 0.00 23.13
August 179.67 22.37 452.00 23.35 0.00 23.35
September 428.33 21.91 215.83 22.55 0.00 22.55
October 498.50 21.72 176.33 22.28 0.00 22.28
November 673.17 21.23 108.67 21.28 87.67 21.25
December 711.17 21.15 307.17 21.13 299.67 21.10
             
Annual Sum or Average 6537.00 21.46 2635.00 21.77 1147.00 21.68
Minimum of Months 179.67 21.12 33.17 21.09 0.00 21.07
Maximum of Months 727.67 22.38 452.00 23.35 341.33 23.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.52 30.83 21.50 30.83 21.48
February 672.00 21.59 29.33 21.57 29.33 21.54
March 744.00 22.14 0.00 22.14 0.00 22.14
April 679.17 22.48 8.50 22.50 0.00 22.50
May 617.67 22.76 48.33 22.84 4.33 22.84
June 242.83 23.07 314.83 23.50 24.50 23.51
July 101.67 23.49 519.00 23.79 61.50 23.79
August 48.50 23.34 540.00 23.83 12.50 23.83
September 306.83 23.01 249.50 23.39 14.17 23.40
October 490.50 22.99 119.83 23.15 0.83 23.15
November 714.83 22.20 0.00 22.20 0.00 22.20
December 744.00 21.76 1.83 21.76 1.83 21.76
             
Annual Sum or Average 6106.00 22.25 1862.00 22.60 179.83 22.60
Minimum of Months 48.50 21.52 0.00 21.50 0.00 21.48
Maximum of Months 744.00 23.49 540.00 23.83 61.50 23.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 281.67 21.02 281.67 21.01
February 672.00 21.01 309.33 21.01 309.33 21.01
March 744.00 21.18 56.00 21.17 56.00 21.15
April 720.00 21.64 0.00 21.64 0.00 21.64
May 734.67 22.36 0.00 22.36 0.00 22.36
June 438.50 23.11 63.50 23.21 0.00 23.21
July 63.33 23.27 321.83 23.80 0.00 23.80
August 138.00 23.45 283.83 23.78 0.00 23.78
September 506.83 22.96 25.83 23.00 0.00 23.00
October 742.17 22.44 0.00 22.44 0.00 22.44
November 720.00 21.40 47.67 21.38 47.67 21.35
December 744.00 21.03 96.00 21.03 96.00 21.03
             
Annual Sum or Average 6967.50 21.78 1485.67 21.88 790.67 21.80
Minimum of Months 63.33 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 23.45 321.83 23.80 309.33 23.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 324.83 21.00 324.83 21.00
February 672.00 21.00 353.17 21.00 353.17 21.00
March 744.00 21.06 79.33 21.05 79.33 21.05
April 720.00 21.39 1.17 21.39 1.17 21.39
May 744.00 22.04 0.00 22.04 0.00 22.04
June 608.67 22.92 2.33 22.93 0.00 22.93
July 228.50 23.20 72.33 23.35 0.00 23.35
August 329.50 23.27 128.83 23.43 0.00 23.43
September 660.67 22.76 0.00 22.76 0.00 22.76
October 744.00 22.08 0.00 22.08 0.00 22.08
November 720.00 21.19 57.33 21.18 57.33 21.17
December 744.00 21.00 150.67 21.00 150.67 21.00
             
Annual Sum or Average 7659.33 21.74 1170.00 21.70 966.50 21.63
Minimum of Months 228.50 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.27 353.17 23.43 353.17 23.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 285.00 22.77 454.83 23.30 145.33 23.44
February 236.50 22.64 372.00 23.29 115.33 23.41
March 268.83 23.28 547.00 23.46 182.33 23.61
April 262.33 23.63 612.00 23.49 215.17 23.62
May 287.50 23.78 676.50 23.41 265.33 23.53
June 302.50 23.93 700.17 23.37 297.67 23.51
July 327.33 23.96 742.00 23.36 327.33 23.50
August 322.17 23.97 734.17 23.38 322.17 23.52
September 296.33 23.88 680.50 23.40 285.33 23.53
October 280.33 23.76 655.33 23.45 252.33 23.58
November 260.67 23.38 557.67 23.47 188.67 23.61
December 247.50 22.91 462.17 23.40 140.67 23.53
             
Annual Sum or Average 3377.00 23.53 7194.33 23.40 2737.67 23.54
Minimum of Months 236.50 22.64 372.00 23.29 115.33 23.41
Maximum of Months 327.33 23.97 742.00 23.49 327.33 23.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 710.83 21.55 96.00 21.53 83.50 21.48
February 619.00 21.68 72.50 21.71 49.67 21.66
March 642.67 22.08 47.83 22.20 0.00 22.20
April 524.00 22.20 100.17 22.45 0.00 22.45
May 481.83 22.55 180.00 22.84 53.00 22.89
June 305.67 23.38 528.33 23.53 215.83 23.59
July 291.17 23.84 714.50 23.72 283.33 23.76
August 223.00 23.87 712.50 23.82 213.33 23.84
September 265.83 23.07 515.33 23.53 146.00 23.56
October 334.50 22.99 403.67 23.45 94.67 23.49
November 607.17 22.05 59.17 22.20 2.83 22.21
December 689.67 21.75 46.50 21.82 16.50 21.81
             
Annual Sum or Average 5695.33 22.31 3476.50 22.80 1158.67 22.88
Minimum of Months 223.00 21.55 46.50 21.53 0.00 21.48
Maximum of Months 710.83 23.87 714.50 23.82 283.33 23.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.03 7.50 22.02 7.50 22.01
February 672.00 22.13 0.83 22.13 0.83 22.12
March 715.33 22.58 0.00 22.58 0.00 22.58
April 556.33 22.73 52.17 22.83 0.00 22.83
May 462.67 22.94 149.00 23.16 48.67 23.21
June 291.50 23.61 450.50 23.75 193.17 23.79
July 256.17 23.97 657.33 23.84 254.00 23.87
August 187.33 23.99 681.67 23.87 186.00 23.89
September 235.83 23.47 444.67 23.72 131.83 23.76
October 343.50 23.39 311.67 23.59 77.67 23.63
November 653.00 22.63 15.17 22.66 3.00 22.66
December 743.67 22.31 0.00 22.31 0.00 22.31
             
Annual Sum or Average 5861.33 22.71 2770.50 23.07 902.67 23.15
Minimum of Months 187.33 22.03 0.00 22.02 0.00 22.01
Maximum of Months 744.00 23.99 681.67 23.87 254.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.74 604.67 20.69 604.67 20.66
February 672.00 20.87 544.17 20.80 544.17 20.78
March 740.83 21.14 246.67 21.04 244.00 20.97
April 671.67 21.29 83.67 21.35 58.67 21.29
May 622.67 21.65 71.67 22.03 6.67 22.07
June 497.83 22.18 208.00 22.93 92.33 23.17
July 542.00 21.73 160.50 22.24 68.00 22.42
August 504.17 21.47 149.00 22.03 16.67 22.07
September 519.50 21.86 153.67 22.48 41.33 22.60
October 605.50 21.61 89.17 21.94 19.83 21.98
November 719.17 21.07 271.00 20.96 271.00 20.91
December 744.00 20.84 574.17 20.77 574.17 20.75
             
Annual Sum or Average 7583.33 21.31 3156.33 21.43 2541.50 21.35
Minimum of Months 497.83 20.74 71.67 20.69 6.67 20.66
Maximum of Months 744.00 22.18 604.67 22.93 604.67 23.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.56 689.50 20.54 689.50 20.53
February 672.00 20.61 637.17 20.60 637.17 20.59
March 741.50 20.91 356.83 20.81 354.83 20.75
April 687.67 21.22 105.17 21.20 91.00 21.13
May 635.50 21.63 64.67 21.97 4.00 21.99
June 507.50 22.18 198.17 22.91 90.33 23.14
July 551.50 21.74 147.33 22.22 67.33 22.40
August 538.17 21.56 112.50 21.97 17.50 22.02
September 574.67 21.88 108.83 22.29 37.67 22.38
October 675.83 21.55 74.00 21.67 40.50 21.66
November 720.00 20.84 368.00 20.74 368.00 20.69
December 744.00 20.60 699.33 20.59 699.33 20.58
             
Annual Sum or Average 7792.33 21.21 3561.50 21.24 3097.17 21.16
Minimum of Months 507.50 20.56 64.67 20.54 4.00 20.53
Maximum of Months 744.00 22.18 699.33 22.91 699.33 23.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.76 513.17 20.71 513.17 20.68
February 672.00 20.75 546.83 20.72 546.83 20.71
March 744.00 20.98 243.83 20.93 243.83 20.90
April 720.00 21.22 18.33 21.21 18.33 21.20
May 737.17 21.64 2.83 21.65 0.00 21.65
June 701.50 22.13 83.17 22.28 76.17 22.38
July 728.33 21.97 62.83 22.10 57.50 22.19
August 735.00 21.87 15.67 21.90 15.67 21.93
September 712.67 21.87 32.17 21.93 31.83 21.98
October 744.00 21.37 9.67 21.38 9.67 21.38
November 720.00 20.99 175.33 20.92 175.33 20.88
December 744.00 20.81 498.33 20.76 498.33 20.74
             
Annual Sum or Average 8702.67 21.36 2202.17 21.28 2186.67 21.21
Minimum of Months 672.00 20.75 2.83 20.71 0.00 20.68
Maximum of Months 744.00 22.13 546.83 22.28 546.83 22.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.73 597.83 20.68 597.83 20.66
February 672.00 20.88 531.17 20.82 531.17 20.80
March 744.00 21.19 241.00 21.07 241.00 21.00
April 690.67 21.41 66.83 21.35 63.83 21.29
May 649.00 21.78 43.33 21.98 6.33 22.02
June 477.83 22.01 181.83 22.63 93.83 22.83
July 532.17 21.77 154.83 22.32 72.50 22.54
August 484.83 21.49 179.50 22.19 24.17 22.30
September 507.00 21.89 126.83 22.37 44.67 22.51
October 633.67 21.69 48.50 21.83 19.50 21.86
November 720.00 21.10 249.83 21.00 249.83 20.94
December 744.00 20.83 558.00 20.77 558.00 20.75
             
Annual Sum or Average 7599.17 21.34 2979.50 21.40 2502.67 21.34
Minimum of Months 477.83 20.73 43.33 20.68 6.33 20.66
Maximum of Months 744.00 22.01 597.83 22.63 597.83 22.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.56 678.33 20.53 678.33 20.53
February 672.00 20.61 637.00 20.60 637.00 20.60
March 744.00 20.94 340.83 20.85 340.83 20.81
April 710.83 21.36 96.17 21.28 93.50 21.21
May 668.50 21.81 38.50 21.99 6.83 22.04
June 486.00 22.03 165.83 22.62 91.33 22.81
July 532.33 21.77 116.67 22.25 71.00 22.49
August 494.50 21.49 92.33 21.98 22.83 22.08
September 590.17 22.00 86.17 22.30 41.83 22.41
October 713.33 21.63 47.83 21.66 40.83 21.65
November 720.00 20.87 337.67 20.77 337.67 20.71
December 744.00 20.60 678.67 20.58 678.67 20.57
             
Annual Sum or Average 7819.67 21.25 3316.00 21.23 3040.67 21.15
Minimum of Months 486.00 20.56 38.50 20.53 6.83 20.53
Maximum of Months 744.00 22.03 678.67 22.62 678.67 22.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 238.00 21.01 238.00 21.01
February 672.00 21.01 242.67 21.01 242.67 21.01
March 744.00 21.14 21.33 21.13 21.33 21.13
April 720.00 21.57 0.00 21.57 0.00 21.57
May 737.17 22.25 0.00 22.25 0.00 22.25
June 521.17 23.19 15.33 23.20 4.33 23.21
July 197.83 23.34 64.17 23.44 17.17 23.44
August 175.83 23.46 123.50 23.62 14.83 23.62
September 516.17 22.86 39.33 22.93 4.33 22.93
October 744.00 22.45 0.00 22.45 0.00 22.45
November 720.00 21.24 29.33 21.23 29.33 21.22
December 744.00 21.02 87.83 21.01 87.83 21.01
             
Annual Sum or Average 7236.17 21.79 861.50 21.79 659.83 21.74
Minimum of Months 175.83 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 23.46 242.67 23.62 242.67 23.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.66 668.67 20.63 668.67 20.61
February 672.00 20.79 589.00 20.74 589.00 20.72
March 739.17 21.07 326.83 20.96 323.33 20.89
April 666.67 21.26 176.50 21.31 145.17 21.24
May 615.83 21.72 93.67 22.20 24.67 22.35
June 511.33 22.37 248.83 23.13 126.50 23.42
July 547.50 21.77 199.83 22.32 82.50 22.51
August 505.00 21.48 177.50 22.09 22.83 22.14
September 520.67 21.91 185.33 22.62 56.00 22.79
October 603.00 21.58 164.83 21.94 82.33 21.95
November 718.83 20.98 371.00 20.87 371.00 20.82
December 744.00 20.76 645.50 20.71 645.50 20.69
             
Annual Sum or Average 7588.00 21.30 3847.50 21.43 3137.50 21.36
Minimum of Months 505.00 20.66 93.67 20.63 22.83 20.61
Maximum of Months 744.00 22.37 668.67 23.13 668.67 23.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.51 712.17 20.50 712.17 20.50
February 672.00 20.56 652.83 20.55 652.83 20.55
March 741.00 20.84 436.17 20.74 433.83 20.69
April 677.83 21.15 207.00 21.15 183.67 21.06
May 631.17 21.71 87.00 22.15 23.67 22.27
June 516.50 22.36 236.50 23.11 124.00 23.39
July 553.17 21.78 181.50 22.30 84.17 22.50
August 531.17 21.53 137.67 22.00 22.67 22.06
September 556.00 21.81 132.33 22.33 46.67 22.44
October 666.67 21.46 162.67 21.58 120.83 21.54
November 720.00 20.75 460.83 20.67 460.83 20.63
December 744.00 20.54 732.67 20.53 732.67 20.53
             
Annual Sum or Average 7753.50 21.18 4139.33 21.24 3598.00 21.16
Minimum of Months 516.50 20.51 87.00 20.50 22.67 20.50
Maximum of Months 744.00 22.36 732.67 23.11 732.67 23.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 738.67 21.01 444.17 20.90 444.17 20.85
February 670.83 21.22 376.50 21.08 376.50 21.01
March 717.17 21.24 179.33 21.14 179.33 21.08
April 676.00 21.37 62.50 21.35 52.50 21.30
May 658.00 21.68 14.17 21.73 1.17 21.74
June 559.00 22.04 131.67 22.38 103.33 22.56
July 581.17 21.78 132.83 22.15 84.00 22.34
August 535.17 21.54 152.50 22.01 21.00 22.07
September 499.17 21.79 177.17 22.40 44.17 22.50
October 550.50 21.51 131.50 21.97 21.33 22.02
November 698.67 21.31 143.50 21.23 143.00 21.18
December 736.67 21.13 399.83 21.00 399.83 20.94
             
Annual Sum or Average 7621.00 21.44 2345.67 21.51 1870.33 21.47
Minimum of Months 499.17 21.01 14.17 20.90 1.17 20.85
Maximum of Months 738.67 22.04 444.17 22.40 444.17 22.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 550.00 23.05 16.67 23.08 0.00 23.08
February 530.50 23.08 0.00 23.08 0.00 23.08
March 333.00 23.14 99.50 23.34 0.00 23.34
April 137.17 23.20 304.83 23.74 0.00 23.74
May 66.33 23.81 599.00 23.93 50.67 23.93
June 184.33 24.00 708.33 23.97 184.33 23.98
July 231.50 24.00 744.00 23.99 231.50 23.99
August 177.67 24.00 743.17 23.98 177.67 23.98
September 132.33 24.00 673.17 23.95 132.33 23.96
October 185.83 23.64 430.17 23.82 90.50 23.85
November 325.00 23.14 121.33 23.37 7.50 23.38
December 481.83 23.10 8.67 23.11 0.00 23.11
             
Annual Sum or Average 3335.50 23.34 4448.83 23.70 874.50 23.73
Minimum of Months 66.33 23.05 0.00 23.08 0.00 23.08
Maximum of Months 550.00 24.00 744.00 23.99 231.50 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 382.50 23.12 73.17 23.27 0.00 23.27
February 395.00 23.18 17.67 23.22 0.00 23.22
March 164.67 23.15 235.50 23.67 0.00 23.67
April 44.17 23.30 432.67 23.93 0.00 23.93
May 39.67 24.00 685.83 23.97 39.67 23.97
June 168.00 24.00 715.83 23.99 168.00 23.99
July 214.50 24.00 744.00 23.99 214.50 23.99
August 162.17 24.00 744.00 23.99 162.17 23.99
September 118.33 24.00 703.17 23.97 118.33 23.98
October 93.83 23.84 488.33 23.93 71.17 23.94
November 167.50 23.17 252.17 23.68 4.67 23.68
December 318.00 23.14 52.00 23.27 0.00 23.27
             
Annual Sum or Average 2268.33 23.45 5144.33 23.82 778.50 23.84
Minimum of Months 39.67 23.12 17.67 23.22 0.00 23.22
Maximum of Months 395.00 24.00 744.00 23.99 214.50 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 530.33 23.86 612.00 23.95 460.83 24.00
February 488.00 23.78 536.83 23.90 414.50 23.94
March 525.33 24.11 671.33 24.07 507.33 24.10
April 517.67 24.16 690.00 24.08 517.67 24.11
May 555.50 24.01 744.00 23.95 555.50 23.97
June 564.00 24.01 720.00 23.98 564.00 23.99
July 603.33 23.99 744.00 23.98 603.33 23.99
August 597.83 24.01 744.00 24.00 597.83 24.00
September 548.67 24.00 720.00 23.96 548.67 23.97
October 541.33 24.06 724.17 24.00 541.33 24.02
November 509.67 24.10 658.50 24.05 494.33 24.08
December 514.00 23.99 622.83 24.01 476.67 24.04
             
Annual Sum or Average 6495.67 24.01 8187.67 23.99 6282.00 24.02
Minimum of Months 488.00 23.78 536.83 23.90 414.50 23.94
Maximum of Months 603.33 24.16 744.00 24.08 603.33 24.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 266.83 21.01 266.83 21.01
February 672.00 21.03 276.83 21.02 276.83 21.02
March 744.00 21.20 20.83 21.20 20.83 21.19
April 717.17 21.64 0.00 21.64 0.00 21.64
May 700.67 22.27 19.67 22.31 0.00 22.31
June 342.50 22.97 162.00 23.25 0.00 23.25
July 34.67 23.04 502.50 23.79 0.00 23.79
August 99.17 23.13 430.83 23.74 0.00 23.74
September 483.00 22.68 99.17 22.88 0.00 22.88
October 714.50 22.19 8.17 22.21 0.00 22.21
November 720.00 21.21 35.33 21.20 35.33 21.19
December 744.00 21.03 82.00 21.03 82.00 21.03
             
Annual Sum or Average 6715.67 21.64 1904.17 21.91 681.83 21.84
Minimum of Months 34.67 21.02 0.00 21.01 0.00 21.01
Maximum of Months 744.00 23.13 502.50 23.79 276.83 23.79



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.44858 27.52108 0.12062 5.52150
February 672.00000 23.06218 23.99972 -0.0019 5.18734
March 744.00000 22.83907 32.90925 -0.0020 5.22884
April 720.00000 22.68640 39.49504 0.00051 5.22829
May 744.00000 22.42784 48.06667 -1.0740 29.61168
June 720.00000 22.76515 57.73483 -0.8848 21.86217
July 744.00000 23.13776 60.38284 -0.7271 16.37723
August 744.00000 23.51271 56.34124 -0.6127 13.11765
September 720.00000 23.79328 51.23639 -0.5400 11.33395
October 744.00000 23.89634 42.72594 0.35521 7.86136
November 720.00000 23.90241 32.90792 0.28511 6.80344
December 744.00000 23.77408 26.92257 0.20498 5.97444
           
Annual Sum or Average 8760.00000 23.27202 41.79226 -0.2411 11.22344
Minimum of Months 672.00000 22.42784 23.99972 -1.0740 5.18734
Maximum of Months 744.00000 23.90241 60.38284 0.35521 29.61168



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.17486 29.29658 -0.4837 10.83358
February 672.00000 21.27918 24.56634 -0.4544 10.60108
March 744.00000 21.42271 34.01976 -0.3089 8.42484
April 720.00000 21.56764 40.60978 -0.2021 7.52856
May 744.00000 21.76862 48.76730 -1.1416 34.32276
June 720.00000 22.58509 57.76474 -0.7473 18.56176
July 744.00000 23.08438 60.58950 -0.5261 12.08989
August 744.00000 23.30112 56.50622 -0.4482 10.96855
September 720.00000 22.59767 53.92025 -0.7529 20.60316
October 744.00000 22.37751 45.29138 0.10979 8.00643
November 720.00000 21.39553 36.42369 -0.3036 8.37175
December 744.00000 21.26780 29.11355 -0.4296 10.05888
           
Annual Sum or Average 8760.00000 21.99042 43.17952 -0.4739 13.38258
Minimum of Months 672.00000 21.17486 24.56634 -1.1416 7.52856
Maximum of Months 744.00000 23.30112 60.58950 0.10979 34.32276



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.51559 30.96036 -0.3248 7.67350
February 672.00000 21.59012 26.39299 -0.3292 7.65455
March 744.00000 22.13518 34.93566 -0.1345 5.91595
April 720.00000 22.54970 40.66924 0.00986 5.73654
May 744.00000 22.92018 47.89377 -0.8398 20.67386
June 720.00000 23.46317 56.88329 -0.5681 12.27362
July 744.00000 23.66875 60.19985 -0.4612 9.69549
August 744.00000 23.75181 56.78645 -0.4471 9.41305
September 720.00000 23.41926 53.51053 -0.6063 13.48825
October 744.00000 23.20411 45.58277 0.22418 6.66275
November 720.00000 22.20714 37.06001 -0.1032 5.90742
December 744.00000 21.76459 30.62091 -0.2594 6.76298
           
Annual Sum or Average 8760.00000 22.68895 43.55909 -0.3199 9.33487
Minimum of Months 672.00000 21.51559 26.39299 -0.8398 5.73654
Maximum of Months 744.00000 23.75181 60.19985 0.22418 20.67386



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.93593 24.67981 0.55781 14.54012
February 672.00000 22.90416 20.62845 0.52644 13.72049
March 744.00000 23.07485 28.97406 0.65402 16.98475
April 720.00000 23.13895 35.12627 0.73298 19.00160
May 744.00000 23.08120 42.96688 0.08784 10.13582
June 720.00000 23.08304 53.39714 0.19762 10.74335
July 744.00000 23.09579 57.21770 0.24513 10.86394
August 744.00000 23.09679 54.26501 0.23577 10.93192
September 720.00000 23.08849 49.92219 0.16466 10.53567
October 744.00000 23.11325 41.40532 0.79551 20.87706
November 720.00000 23.10419 31.09387 0.67729 17.46132
December 744.00000 22.98951 24.59038 0.58268 14.94039
           
Annual Sum or Average 8760.00000 23.05963 38.79686 0.45435 14.22993
Minimum of Months 672.00000 22.90416 20.62845 0.08784 10.13582
Maximum of Months 744.00000 23.13895 57.21770 0.79551 20.87706



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64634 34.18587 -0.2710 7.76419
February 672.00000 21.84048 29.50637 -0.2227 7.47388
March 744.00000 22.29936 38.16734 -0.0224 6.47607
April 720.00000 22.57211 44.10442 0.10280 6.79940
May 744.00000 22.86925 51.59035 -0.7109 17.13708
June 720.00000 23.36782 60.62771 -0.4196 9.54287
July 744.00000 23.61955 63.58406 -0.2728 7.05871
August 744.00000 23.75921 59.90526 -0.2139 6.59662
September 720.00000 23.44475 56.75370 -0.3953 10.15038
October 744.00000 23.40495 48.39781 0.41904 10.17776
November 720.00000 22.29295 40.26333 -0.0107 6.58099
December 744.00000 21.89524 33.76971 -0.1861 7.09361
           
Annual Sum or Average 8760.00000 22.75664 46.83908 -0.1833 8.58330
Minimum of Months 672.00000 21.64634 29.50637 -0.7109 6.47607
Maximum of Months 744.00000 23.75921 63.58406 0.41904 17.13708



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.02918 33.47639 -0.1798 6.33389
February 672.00000 22.12720 29.01453 -0.1757 6.19485
March 744.00000 22.63213 37.40244 0.01284 5.61329
April 720.00000 22.95942 43.09418 0.14066 6.16626
May 744.00000 23.24144 50.31278 -0.6846 15.65753
June 720.00000 23.57744 59.39649 -0.4727 10.14556
July 744.00000 23.70717 62.64899 -0.3860 8.34007
August 744.00000 23.79629 59.25706 -0.3674 7.98466
September 720.00000 23.63963 55.81093 -0.4725 10.23415
October 744.00000 23.56991 47.86038 0.35680 8.19371
November 720.00000 22.74117 39.36057 0.05511 5.84779
December 744.00000 22.30952 33.08984 -0.1042 5.80134
           
Annual Sum or Average 8760.00000 23.03273 45.99385 -0.1899 8.05734
Minimum of Months 672.00000 22.02918 29.01453 -0.6846 5.61329
Maximum of Months 744.00000 23.79629 62.64899 0.35680 15.65753



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.73938 32.87211 -0.6506 14.54202
February 672.00000 20.86825 27.46525 -0.6320 14.13476
March 744.00000 21.15473 37.87245 -0.4348 9.93949
April 720.00000 21.49317 44.48831 -0.2664 8.28718
May 744.00000 22.10670 50.54411 -1.0960 34.19568
June 720.00000 22.73428 54.45374 -0.7708 22.75920
July 744.00000 22.20562 56.42180 -0.8888 24.67077
August 744.00000 22.16837 53.50492 -0.8989 24.87802
September 720.00000 22.47792 53.52184 -0.8994 26.36807
October 744.00000 22.03294 47.48164 -0.0558 7.53084
November 720.00000 21.06986 41.20816 -0.4592 10.25490
December 744.00000 20.83814 32.88086 -0.6078 13.35627
           
Annual Sum or Average 8760.00000 21.66079 44.48795 -0.6389 17.61194
Minimum of Months 672.00000 20.73938 27.46525 -1.0960 7.53084
Maximum of Months 744.00000 22.73428 56.42180 -0.0558 34.19568



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.56094 33.14611 -0.7159 16.38556
February 672.00000 20.61199 27.80538 -0.7259 16.64842
March 744.00000 20.91909 38.28885 -0.5163 11.29458
April 720.00000 21.35685 44.94342 -0.3148 8.54969
May 744.00000 22.05664 50.73166 -1.1238 35.13989
June 720.00000 22.72266 54.65713 -0.7821 23.00219
July 744.00000 22.20195 56.76742 -0.8990 24.96822
August 744.00000 22.13177 54.22492 -0.9342 25.90095
September 720.00000 22.32166 54.57515 -0.9782 28.54142
October 744.00000 21.76716 49.31592 -0.1497 7.36933
November 720.00000 20.83535 41.71967 -0.5406 11.81662
December 744.00000 20.60265 33.26675 -0.6898 15.44815
           
Annual Sum or Average 8760.00000 21.51145 45.05042 -0.6978 18.78126
Minimum of Months 672.00000 20.56094 27.80538 -1.1238 7.36933
Maximum of Months 744.00000 22.72266 56.76742 -0.1497 35.13989



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.76273 31.63399 -0.6076 13.21020
February 672.00000 20.75492 26.45356 -0.6409 14.01497
March 744.00000 20.98418 37.03027 -0.4874 10.21319
April 720.00000 21.22499 43.83248 -0.3552 7.95866
May 744.00000 21.66218 49.59533 -1.3129 41.58897
June 720.00000 22.17919 56.46473 -1.0560 30.15418
July 744.00000 22.01079 57.78184 -1.0868 31.45914
August 744.00000 21.89195 55.31502 -1.1511 33.95138
September 720.00000 21.88824 54.49212 -1.1965 36.06726
October 744.00000 21.36921 49.21632 -0.2747 7.11371
November 720.00000 20.98968 40.17408 -0.4668 9.87597
December 744.00000 20.81299 31.80371 -0.5869 12.48264
           
Annual Sum or Average 8760.00000 21.38059 44.58431 -0.7696 20.72520
Minimum of Months 672.00000 20.75492 26.45356 -1.3129 7.11371
Maximum of Months 744.00000 22.17919 57.78184 -0.2747 41.58897



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.72853 32.86371 -0.6506 14.48470
February 672.00000 20.87588 27.42705 -0.6260 13.87281
March 744.00000 21.18521 37.85707 -0.4324 9.80686
April 720.00000 21.49768 44.39843 -0.2634 7.96234
May 744.00000 22.06055 50.49149 -1.1044 33.79253
June 720.00000 22.59482 55.48815 -0.8188 22.90607
July 744.00000 22.26406 56.42732 -0.8729 24.70837
August 744.00000 22.25758 53.50033 -0.8720 24.78184
September 720.00000 22.43942 53.68542 -0.9068 26.14506
October 744.00000 21.96987 47.94975 -0.0708 7.06062
November 720.00000 21.10274 41.08134 -0.4433 9.99767
December 744.00000 20.83333 32.87515 -0.6045 13.23601
           
Annual Sum or Average 8760.00000 21.65435 44.59854 -0.6393 17.43225
Minimum of Months 672.00000 20.72853 27.42705 -1.1044 7.06062
Maximum of Months 744.00000 22.59482 56.42732 -0.0708 33.79253



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.55825 33.12998 -0.7146 16.37081
February 672.00000 20.61342 27.76578 -0.7212 16.49997
March 744.00000 20.94123 38.25409 -0.5159 11.07794
April 720.00000 21.38882 44.72944 -0.3065 8.19630
May 744.00000 22.03921 50.59210 -1.1242 34.53036
June 720.00000 22.59190 55.70260 -0.8275 23.16279
July 744.00000 22.26183 56.77461 -0.8826 25.00711
August 744.00000 22.22668 54.09687 -0.9060 25.68564
September 720.00000 22.32107 54.53888 -0.9755 28.18558
October 744.00000 21.71753 49.36338 -0.1646 7.01798
November 720.00000 20.86561 41.60520 -0.5241 11.44323
December 744.00000 20.59756 33.25434 -0.6863 15.40085
           
Annual Sum or Average 8760.00000 21.51455 45.07987 -0.6960 18.57383
Minimum of Months 672.00000 20.55825 27.76578 -1.1242 7.01798
Maximum of Months 744.00000 22.59190 56.77461 -0.1646 34.53036



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.66301 33.28151 -0.7068 16.21364
February 672.00000 20.78983 27.79470 -0.6885 15.80073
March 744.00000 21.09537 38.30290 -0.4717 10.91400
April 720.00000 21.47916 44.97850 -0.2821 8.99051
May 744.00000 22.16183 51.11815 -1.0756 34.61300
June 720.00000 22.79290 54.81408 -0.7371 22.97955
July 744.00000 22.20735 56.98416 -0.8727 24.43526
August 744.00000 22.15695 54.10600 -0.8893 24.85321
September 720.00000 22.51329 54.26625 -0.8841 26.91617
October 744.00000 22.04657 48.03892 -0.0636 8.22095
November 720.00000 20.98438 41.78540 -0.5072 11.40153
December 744.00000 20.75622 33.31134 -0.6627 14.88704
           
Annual Sum or Average 8760.00000 21.64086 44.99455 -0.6537 18.38165
Minimum of Months 672.00000 20.66301 27.79470 -1.0756 8.22095
Maximum of Months 744.00000 22.79290 56.98416 -0.0636 34.61300



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.51315 33.52954 -0.7680 18.07160
February 672.00000 20.55754 28.13118 -0.7796 18.40577
March 744.00000 20.85372 38.74010 -0.5573 12.40059
April 720.00000 21.34064 45.42945 -0.3328 9.24813
May 744.00000 22.12227 51.27943 -1.1015 35.43100
June 720.00000 22.78854 54.94881 -0.7469 23.16384
July 744.00000 22.20439 57.29666 -0.8829 24.71748
August 744.00000 22.11768 54.76074 -0.9269 25.89042
September 720.00000 22.33897 55.35447 -0.9717 29.07557
October 744.00000 21.73171 50.13360 -0.1722 7.99946
November 720.00000 20.75002 42.32435 -0.5917 13.13034
December 744.00000 20.53749 33.69033 -0.7434 17.12435
           
Annual Sum or Average 8760.00000 21.49219 45.56638 -0.7146 19.57419
Minimum of Months 672.00000 20.51315 28.13118 -1.1015 7.99946
Maximum of Months 744.00000 22.78854 57.29666 -0.1722 35.43100



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.03158 34.00037 -0.5398 12.28905
February 672.00000 21.22471 28.59051 -0.4948 11.53679
March 744.00000 21.31532 39.12558 -0.3711 9.16582
April 720.00000 21.50576 45.45896 -0.2597 7.92566
May 744.00000 21.91673 51.31895 -1.1826 36.44737
June 720.00000 22.38353 56.65676 -0.9200 25.70932
July 744.00000 22.14259 57.48383 -0.9509 26.71223
August 744.00000 22.11317 54.22172 -0.9520 26.83189
September 720.00000 22.43361 53.58079 -0.9082 26.18222
October 744.00000 22.08745 47.42647 -0.0141 7.59763
November 720.00000 21.37197 41.89453 -0.3417 8.63755
December 744.00000 21.14749 33.91851 -0.4842 11.20829
           
Annual Sum or Average 8760.00000 21.72472 45.39897 -0.6194 17.57395
Minimum of Months 672.00000 21.03158 28.59051 -1.1826 7.59763
Maximum of Months 744.00000 22.43361 57.48383 -0.0141 36.44737



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.29436 33.92394 0.13981 6.29884
February 672.00000 23.26939 30.03264 0.10653 6.06341
March 744.00000 23.59378 37.35421 0.27326 7.07233
April 720.00000 23.77806 42.42672 0.38681 8.50030
May 744.00000 23.89391 49.16078 -0.3608 8.00093
June 720.00000 23.96565 58.31959 -0.2131 6.07092
July 744.00000 23.98801 61.71959 -0.1543 5.51574
August 744.00000 23.97761 59.00172 -0.1823 5.76329
September 720.00000 23.92682 55.53669 -0.2786 6.86684
October 744.00000 23.81907 48.24906 0.45734 9.84171
November 720.00000 23.58330 39.32430 0.28355 7.25771
December 744.00000 23.41443 33.59817 0.17722 6.26699
           
Annual Sum or Average 8760.00000 23.71116 45.81470 0.05260 6.96494
Minimum of Months 672.00000 23.26939 30.03264 -0.3608 5.51574
Maximum of Months 744.00000 23.98801 61.71959 0.45734 9.84171



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.52747 32.85147 0.23565 6.84194
February 672.00000 23.50325 29.03494 0.20184 6.46874
March 744.00000 23.76464 36.27183 0.35352 7.97211
April 720.00000 23.90013 41.45731 0.45373 9.57071
May 744.00000 23.95494 48.35005 -0.2901 6.95280
June 720.00000 23.98664 57.74883 -0.1649 5.67330
July 744.00000 23.99335 61.24476 -0.1146 5.29227
August 744.00000 23.98926 58.51728 -0.1410 5.47571
September 720.00000 23.96683 54.86318 -0.2221 6.21710
October 744.00000 23.90672 47.39257 0.51123 10.85444
November 720.00000 23.75261 38.25080 0.36323 8.17029
December 744.00000 23.61677 32.50188 0.26552 6.89354
           
Annual Sum or Average 8760.00000 23.82363 44.96879 0.12049 7.20228
Minimum of Months 672.00000 23.50325 29.03494 -0.2901 5.29227
Maximum of Months 744.00000 23.99335 61.24476 0.51123 10.85444



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.74621 31.48262 0.90036 25.22319
February 672.00000 23.69454 27.59635 0.86825 24.04679
March 744.00000 23.89546 35.30767 1.02262 29.72174
April 720.00000 23.97230 40.77698 1.12301 33.73775
May 744.00000 23.91185 47.55463 0.64701 18.19807
June 720.00000 23.95983 56.89120 0.78691 21.83138
July 744.00000 23.97297 60.36172 0.85082 23.64859
August 744.00000 23.98411 57.61936 0.84194 23.57321
September 720.00000 23.93057 53.87061 0.72469 20.04608
October 744.00000 23.91655 46.32662 1.17493 35.98601
November 720.00000 23.88997 37.30430 1.02835 29.81931
December 744.00000 23.79056 31.23514 0.92683 25.83386
           
Annual Sum or Average 8760.00000 23.88980 43.95756 0.90822 25.98375
Minimum of Months 672.00000 23.69454 27.59635 0.64701 18.19807
Maximum of Months 744.00000 23.98411 60.36172 1.17493 35.98601



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00250 28.32100 -0.5198 10.78511
February 672.00000 21.00065 23.65904 -0.5476 11.35211
March 744.00000 21.06050 33.39671 -0.4443 9.25877
April 720.00000 21.39169 39.73067 -0.3106 7.46936
May 744.00000 22.04403 46.78315 -1.1914 35.26529
June 720.00000 23.01535 55.62091 -0.7905 18.57723
July 744.00000 23.46042 59.02250 -0.6091 12.89722
August 744.00000 23.49024 55.37595 -0.6220 13.33320
September 720.00000 22.82527 52.31796 -0.8781 21.97552
October 744.00000 22.08079 45.00425 -0.0942 5.83090
November 720.00000 21.19289 35.70784 -0.3926 8.48082
December 744.00000 21.00343 28.34060 -0.5028 10.32863
           
Annual Sum or Average 8760.00000 21.97034 42.04751 -0.5753 13.81266
Minimum of Months 672.00000 21.00065 23.65904 -1.1914 5.83090
Maximum of Months 744.00000 23.49024 59.02250 -0.0942 35.26529



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00869 31.78697 -0.4974 10.26974
February 672.00000 21.00927 27.13634 -0.5172 10.64780
March 744.00000 21.13749 36.68299 -0.4144 8.71212
April 720.00000 21.57430 42.69768 -0.2657 6.92090
May 744.00000 22.26471 49.51027 -1.1291 32.46322
June 720.00000 23.29251 57.61714 -0.7088 15.78505
July 744.00000 23.51807 61.10452 -0.6040 12.70344
August 744.00000 23.63755 57.65674 -0.5839 12.24084
September 720.00000 23.09165 54.64623 -0.7992 19.37431
October 744.00000 22.45111 47.42054 -0.0079 5.52146
November 720.00000 21.23607 38.99786 -0.3792 8.26491
December 744.00000 21.01547 31.74896 -0.4879 10.01486
           
Annual Sum or Average 8760.00000 22.10992 44.85432 -0.5330 12.76216
Minimum of Months 672.00000 21.00869 27.13634 -1.1291 5.52146
Maximum of Months 744.00000 23.63755 61.10452 -0.0079 32.46322



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01753 29.67494 -0.4980 10.32691
February 672.00000 21.03358 25.01455 -0.5159 10.66963
March 744.00000 21.20273 34.45692 -0.3862 8.35102
April 720.00000 21.64756 40.39471 -0.2253 6.74210
May 744.00000 22.34795 47.14790 -1.0500 29.14922
June 720.00000 23.30908 55.24792 -0.6436 14.24374
July 744.00000 23.68711 58.12158 -0.4803 10.02808
August 744.00000 23.69423 55.02097 -0.4956 10.45980
September 720.00000 22.99962 52.61734 -0.7739 18.78902
October 744.00000 22.24162 45.61055 -0.0293 5.95940
November 720.00000 21.21244 36.88413 -0.3713 8.17739
December 744.00000 21.03335 29.61862 -0.4804 9.88376
           
Annual Sum or Average 8760.00000 22.12592 42.58610 -0.4956 11.90745
Minimum of Months 672.00000 21.01753 25.01455 -1.0500 5.95940
Maximum of Months 744.00000 23.69423 58.12158 -0.0293 29.14922



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.02466 27.99745 -0.5034 10.44353
February 672.00000 21.01366 23.36016 -0.5336 11.03374
March 744.00000 21.17728 32.89805 -0.4147 8.79210
April 720.00000 21.64128 38.92338 -0.2571 6.92169
May 744.00000 22.37356 45.68404 -1.0956 30.83040
June 720.00000 23.32667 54.52975 -0.6993 15.70849
July 744.00000 23.71153 58.14032 -0.5347 11.09826
August 744.00000 23.74071 54.43898 -0.5478 11.45754
September 720.00000 23.16687 51.14813 -0.7773 18.44520
October 744.00000 22.44602 43.89996 -0.0180 5.61218
November 720.00000 21.39987 35.01763 -0.3444 7.87571
December 744.00000 21.03470 28.02957 -0.4866 10.00168
           
Annual Sum or Average 8760.00000 22.17859 41.27778 -0.5176 12.36379
Minimum of Months 672.00000 21.01366 23.36016 -1.0956 5.61218
Maximum of Months 744.00000 23.74071 58.14032 -0.0180 30.83040



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.148795E+10 11959.48 19-JAN-19:03 225.51 0.463635E+10 0.00 0.612429E+10 0.94 3.12 22-JAN-21:26 0.00 0.00
February 0.194949E+10 16552.38 20-FEB-09:02 234.24 0.607449E+10 0.00 0.802398E+10 1.09 3.12 19-FEB-14:43 0.00 0.00
March 0.646853E+10 77846.50 27-MAR-15:02 388.86 0.195739E+11 0.00 0.260425E+11 1.62 3.22 27-MAR-15:02 0.00 0.00
April 0.261074E+11 113521.94 07-APR-15:02 519.47 0.762511E+11 0.00 0.102359E+12 2.20 3.48 08-APR-08:52 0.00 0.00
May 0.751823E+11 129819.19 29-MAY-18:32 720.54 0.218595E+12 0.00 0.293777E+12 2.88 3.95 31-MAY-21:53 0.00 0.00
June 0.220098E+12 198385.27 19-JUN-18:03 720.00 0.729652E+12 0.00 0.949750E+12 3.22 4.23 13-JUN-21:53 0.00 0.00
July 0.322119E+12 193163.36 20-JUL-18:03 744.00 0.111879E+13 0.00 0.144091E+13 3.46 4.20 14-JUL-21:52 0.00 0.00
August 0.288002E+12 209504.18 16-AUG-15:03 744.00 0.947577E+12 0.00 0.123558E+13 3.23 4.11 06-AUG-08:53 0.00 0.00
September 0.165780E+12 173421.14 07-SEP-21:52 719.00 0.531942E+12 0.00 0.697722E+12 3.08 4.19 21-SEP-21:52 0.00 0.00
October 0.737737E+11 132015.39 04-OCT-15:03 693.36 0.226414E+12 0.00 0.300188E+12 2.85 4.13 23-OCT-21:52 0.00 0.00
November 0.727884E+10 54166.17 04-NOV-15:01 404.88 0.222125E+11 0.00 0.294913E+11 1.74 3.12 20-NOV-09:00 0.00 0.00
December 0.291658E+10 19590.35 25-DEC-09:02 318.65 0.908787E+10 0.00 0.120045E+11 1.33 3.12 05-DEC-07:15 0.00 0.00
                         
Annual Sum or Average 0.119116E+13     6432.52 0.391081E+13 0.00 0.510197E+13 2.31     0.00 0.00
Minimum of Months 0.148795E+10 11959.48   225.51 0.463635E+10 0.00 0.612429E+10 0.94 3.12   0.00 0.00
Maximum of Months 0.322119E+12 209504.18   744.00 0.111879E+13 0.00 0.144091E+13 3.46 4.23   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.136806E+12 0.00 744.00 197059.18 02-JAN-09:05 0.00 39.36 60.00 0.58 0.00 0.10 0.40 02-JAN-09:05
February 0.118212E+12 0.00 671.97 196461.49 06-FEB-09:02 0.00 39.97 60.00 0.54 0.00 0.10 0.40 06-FEB-09:02
March 0.597398E+11 0.00 719.32 173765.19 05-MAR-19:02 0.00 39.92 59.11 0.28 0.00 0.05 0.35 05-MAR-19:02
April 0.353568E+11 0.00 544.53 147518.95 04-APR-18:02 0.00 36.07 53.11 0.16 0.00 0.03 0.30 04-APR-18:02
May 0.865456E+10 0.00 283.93 105213.03 15-MAY-02:00 0.00 32.90 42.77 0.03 0.00 0.01 0.21 15-MAY-02:00
June 0.279172E+09 0.00 13.69 39463.30 04-JUN-08:56 0.00 32.21 32.78 0.00 0.00 0.00 0.08 04-JUN-08:56
July 76311939.72 0.00 3.41 32003.50 14-JUL-08:07 0.00 35.39 35.50 0.00 0.00 0.00 0.07 14-JUL-08:07
August 0.368769E+09 0.00 14.78 33854.87 24-AUG-18:50 0.00 34.43 34.98 0.00 0.00 0.00 0.07 24-AUG-18:50
September 0.115226E+10 0.00 95.23 64180.31 30-SEP-01:10 0.00 35.58 38.43 0.01 0.00 0.00 0.13 30-SEP-01:10
October 0.140050E+11 0.00 337.17 140098.87 18-OCT-08:02 0.00 37.18 46.65 0.07 0.00 0.01 0.29 18-OCT-08:02
November 0.587265E+11 0.00 681.62 169113.33 20-NOV-19:02 0.00 40.40 58.82 0.28 0.00 0.05 0.35 20-NOV-19:02
December 0.842845E+11 0.00 744.00 169292.81 07-DEC-19:02 0.00 41.16 60.00 0.40 0.00 0.06 0.35 07-DEC-19:02
                           
Annual Sum or Average 0.517662E+12 0.00 4853.65     0.00 37.03 48.45 0.19 0.00 0.03    
Minimum of Months 76311939.72 0.00 3.41 32003.50   0.00 32.21 32.78 0.00 0.00 0.00 0.07  
Maximum of Months 0.136806E+12 0.00 744.00 197059.18   0.00 41.16 60.00 0.58 0.00 0.10 0.40  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.216898E+09 0.00 132.02 0.216898E+09 0.00 0.00 0.00 0.00 29707.88 21-JAN-23:00 29707.88 21-JAN-23:00 0.00 0.00 0.00
February 0.216674E+09 0.00 122.27 0.216674E+09 0.00 0.00 0.00 0.00 23332.73 16-FEB-21:07 23332.73 16-FEB-21:07 0.00 0.00 0.00
March 0.358594E+10 0.00 151.94 0.355603E+10 0.00 0.00 0.00 0.00 130712.11 27-MAR-16:00 130712.11 27-MAR-16:00 0.00 0.00 0.00
April 0.343480E+11 0.00 234.22 0.340976E+11 0.00 0.00 0.00 0.00 210469.64 09-APR-10:50 206756.63 07-APR-17:04 0.00 0.00 0.00
May 0.125664E+12 0.00 488.42 0.108539E+12 0.00 0.00 0.00 0.00 291325.25 31-MAY-17:20 221914.31 29-MAY-12:30 0.00 0.00 0.00
June 0.516176E+12 0.00 707.42 0.310625E+12 0.00 0.00 0.00 0.00 471530.61 24-JUN-17:20 293592.77 22-JUN-18:20 0.00 0.00 0.00
July 0.811626E+12 0.00 744.00 0.444384E+12 0.00 0.00 0.00 0.00 486469.21 27-JUL-21:00 271123.20 11-JUL-18:05 0.00 0.00 0.00
August 0.661412E+12 0.00 744.00 0.436384E+12 0.00 0.00 0.00 0.00 498203.56 11-AUG-22:00 378733.55 24-AUG-18:50 0.00 0.00 0.00
September 0.360155E+12 0.00 651.36 0.249856E+12 0.00 0.00 0.00 0.00 476607.58 13-SEP-21:00 290414.32 14-SEP-19:20 0.00 0.00 0.00
October 0.124982E+12 0.00 402.43 0.808578E+11 0.00 0.00 0.00 0.00 285266.21 05-OCT-19:10 181339.40 25-OCT-10:33 0.00 0.00 0.00
November 0.365666E+10 0.00 155.38 0.336387E+10 0.00 0.00 0.00 0.00 64285.84 04-NOV-10:50 64285.84 04-NOV-10:50 0.00 0.00 0.00
December 0.441034E+09 0.00 202.14 0.441034E+09 0.00 0.00 0.00 0.00 35746.95 17-DEC-21:40 35746.95 17-DEC-21:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.264248E+13 0.00 4735.59 0.167254E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.216674E+09 0.00 122.27 0.216674E+09 0.00 0.00 0.00 0.00 23332.73   23332.73   0.00 0.00 0.00
Maximum of Months 0.811626E+12 0.00 744.00 0.444384E+12 0.00 0.00 0.00 0.00 498203.56   378733.55   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 9597.49 0.00 0.08 9597.49 0.00 0.00 0.00 0.00 31.99 24-JAN-19:55 31.99 24-JAN-19:55 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.697388E+09 0.00 19.83 0.589428E+09 0.00 0.00 0.00 0.00 32905.75 27-MAR-13:00 25911.69 27-MAR-15:55 0.00 0.00 0.00
April 0.635538E+10 0.00 144.75 0.618073E+10 0.00 0.00 0.00 0.00 40374.00 09-APR-10:55 29715.03 07-APR-13:00 0.00 0.00 0.00
May 0.233997E+11 0.00 446.00 0.197067E+11 0.00 0.00 0.00 0.00 52967.83 31-MAY-16:43 32870.67 30-MAY-13:00 0.00 0.00 0.00
June 0.987929E+11 0.00 707.83 0.559559E+11 0.00 0.00 0.00 0.00 81926.34 24-JUN-17:20 37482.67 19-JUN-12:00 0.00 0.00 0.00
July 0.135125E+12 0.00 744.00 0.753175E+11 0.00 0.00 0.00 0.00 81374.00 26-JUL-17:10 35550.59 07-JUL-12:00 0.00 0.00 0.00
August 0.108838E+12 0.00 744.00 0.714963E+11 0.00 0.00 0.00 0.00 78804.96 06-AUG-06:40 35442.00 24-AUG-15:00 0.00 0.00 0.00
September 0.681274E+11 0.00 641.83 0.451308E+11 0.00 0.00 0.00 0.00 78294.96 22-SEP-17:00 33388.54 14-SEP-14:00 0.00 0.00 0.00
October 0.246553E+11 0.00 338.00 0.148233E+11 0.00 0.00 0.00 0.00 52291.09 24-OCT-14:00 28971.28 04-OCT-13:00 0.00 0.00 0.00
November 0.605285E+09 0.00 33.17 0.541329E+09 0.00 0.00 0.00 0.00 12350.93 10-NOV-08:00 10814.20 04-NOV-13:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.466597E+12 0.00 3819.50 0.289742E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.135125E+12 0.00 744.00 0.753175E+11 0.00 0.00 0.00 0.00 81926.34   37482.67   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 41260615.74 0.00 9.86 40736214.82 0.00 0.00 0.00 0.00 15761.45 17-JAN-16:01 15761.45 17-JAN-16:01 0.00 0.00 0.00
February 0.113137E+09 0.00 21.41 0.113137E+09 0.00 0.00 0.00 0.00 15763.03 20-FEB-16:01 15763.03 20-FEB-16:01 0.00 0.00 0.00
March 0.781929E+09 0.00 121.47 0.705571E+09 0.00 0.00 0.00 0.00 16719.45 27-MAR-15:02 15769.22 29-MAR-15:02 0.00 0.00 0.00
April 0.186412E+10 0.00 266.91 0.122273E+10 0.00 0.00 0.00 0.00 18425.37 27-APR-18:21 16853.16 10-APR-20:41 0.00 0.00 0.00
May 0.366506E+10 0.00 434.35 0.218933E+10 0.00 0.00 0.00 0.00 20629.51 31-MAY-21:51 16944.74 02-MAY-18:21 0.00 0.00 0.00
June 0.717652E+10 0.00 455.35 0.426289E+10 0.00 0.00 0.00 0.00 21995.00 21-JUN-21:51 17015.93 04-JUN-21:51 0.00 0.00 0.00
July 0.106188E+11 0.00 587.62 0.643056E+10 0.00 0.00 0.00 0.00 22719.58 05-JUL-21:51 15653.86 03-JUL-18:51 0.00 0.00 0.00
August 0.112908E+11 0.00 596.40 0.742293E+10 0.00 0.00 0.00 0.00 21889.83 10-AUG-21:51 16340.74 30-AUG-08:51 0.00 0.00 0.00
September 0.555702E+10 0.00 438.17 0.324845E+10 0.00 0.00 0.00 0.00 21453.25 13-SEP-21:51 16212.36 11-SEP-21:51 0.00 0.00 0.00
October 0.358995E+10 0.00 427.59 0.212271E+10 0.00 0.00 0.00 0.00 20600.99 05-OCT-21:51 16567.46 30-OCT-16:41 0.00 0.00 0.00
November 0.325491E+09 0.00 90.99 0.212436E+09 0.00 0.00 0.00 0.00 15775.73 03-NOV-15:01 15775.73 03-NOV-15:01 0.00 0.00 0.00
December 49033308.87 0.00 14.95 48169176.85 0.00 0.00 0.00 0.00 15686.88 17-DEC-16:01 15686.88 17-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.450731E+11 0.00 3465.07 0.280197E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 41260615.74 0.00 9.86 40736214.82 0.00 0.00 0.00 0.00 15686.88   15653.86   0.00 0.00 0.00
Maximum of Months 0.112908E+11 0.00 596.40 0.742293E+10 0.00 0.00 0.00 0.00 22719.58   17015.93   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3855089.01 0.00 1.37 3698308.04 0.00 0.00 0.00 0.00 8823.29 17-JAN-16:01 8823.29 17-JAN-16:01 0.00 0.00 0.00
February 17018556.57 0.00 6.84 17017562.22 0.00 0.00 0.00 0.00 14320.68 20-FEB-16:01 14320.68 20-FEB-16:01 0.00 0.00 0.00
March 0.333316E+09 0.00 57.89 0.301051E+09 0.00 0.00 0.00 0.00 15818.19 27-MAR-15:02 15341.25 29-MAR-15:02 0.00 0.00 0.00
April 0.124655E+10 0.00 208.30 0.783829E+09 0.00 0.00 0.00 0.00 17815.18 27-APR-18:21 16176.28 09-APR-18:11 0.00 0.00 0.00
May 0.322403E+10 0.00 408.34 0.187056E+10 0.00 0.00 0.00 0.00 19995.30 31-MAY-21:51 16249.55 02-MAY-18:21 0.00 0.00 0.00
June 0.679861E+10 0.00 450.35 0.400313E+10 0.00 0.00 0.00 0.00 21415.02 21-JUN-21:51 15999.49 04-JUN-21:51 0.00 0.00 0.00
July 0.100941E+11 0.00 584.36 0.603536E+10 0.00 0.00 0.00 0.00 22068.86 05-JUL-21:51 15243.64 11-JUL-08:51 0.00 0.00 0.00
August 0.100192E+11 0.00 588.84 0.631943E+10 0.00 0.00 0.00 0.00 21157.94 10-AUG-21:51 15467.02 25-AUG-21:51 0.00 0.00 0.00
September 0.426194E+10 0.00 409.32 0.227072E+10 0.00 0.00 0.00 0.00 20801.63 06-SEP-21:51 15353.21 11-SEP-21:51 0.00 0.00 0.00
October 0.180361E+10 0.00 311.36 0.893162E+09 0.00 0.00 0.00 0.00 19579.51 05-OCT-21:51 15341.05 17-OCT-15:02 0.00 0.00 0.00
November 59831274.48 0.00 20.05 40222056.40 0.00 0.00 0.00 0.00 15346.86 03-NOV-15:01 15346.86 03-NOV-15:01 0.00 0.00 0.00
December 2129852.83 0.00 0.67 1760176.73 0.00 0.00 0.00 0.00 4516.45 17-DEC-16:01 4516.45 17-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.378642E+11 0.00 3047.70 0.225400E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2129852.83 0.00 0.67 1760176.73 0.00 0.00 0.00 0.00 4516.45   4516.45   0.00 0.00 0.00
Maximum of Months 0.100941E+11 0.00 588.84 0.631943E+10 0.00 0.00 0.00 0.00 22068.86   16249.55   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.130263E+09 0.00 8.62 0.130263E+09 0.00 0.00 0.00 0.00 7851.58 19-JAN-14:27 7851.58 19-JAN-14:27 0.00 0.00 0.00
February 0.957213E+09 0.00 29.02 0.957213E+09 0.00 0.00 0.00 0.00 18601.57 20-FEB-13:30 18601.57 20-FEB-13:30 0.00 0.00 0.00
March 0.303098E+10 0.00 84.02 0.299709E+10 0.00 0.00 0.00 0.00 30593.29 03-MAR-13:30 30593.29 03-MAR-13:30 0.00 0.00 0.00
April 0.656680E+10 0.00 147.67 0.457442E+10 0.00 0.00 0.00 0.00 41050.36 08-APR-12:20 34822.59 08-APR-12:30 0.00 0.00 0.00
May 0.105050E+11 0.00 307.43 0.679988E+10 0.00 0.00 0.00 0.00 29373.35 31-MAY-12:30 21818.35 11-MAY-12:40 0.00 0.00 0.00
June 0.221816E+11 0.00 484.97 0.908612E+10 0.00 0.00 0.00 0.00 33853.09 19-JUN-12:50 22734.17 19-JUN-13:10 0.00 0.00 0.00
July 0.395828E+11 0.00 674.36 0.171644E+11 0.00 0.00 0.00 0.00 35873.57 08-JUL-12:00 25284.79 10-JUL-13:10 0.00 0.00 0.00
August 0.484406E+11 0.00 697.31 0.274412E+11 0.00 0.00 0.00 0.00 46743.89 16-AUG-12:30 42412.81 30-AUG-12:30 0.00 0.00 0.00
September 0.313142E+11 0.00 519.53 0.185488E+11 0.00 0.00 0.00 0.00 52326.91 07-SEP-14:10 41906.87 28-SEP-14:20 0.00 0.00 0.00
October 0.317291E+11 0.00 459.42 0.233585E+11 0.00 0.00 0.00 0.00 53362.96 04-OCT-15:20 48287.43 30-OCT-13:20 0.00 0.00 0.00
November 0.595808E+10 0.00 124.33 0.526646E+10 0.00 0.00 0.00 0.00 42750.64 02-NOV-12:40 42750.64 02-NOV-12:40 0.00 0.00 0.00
December 0.233834E+10 0.00 50.05 0.233834E+10 0.00 0.00 0.00 0.00 31259.79 17-DEC-13:30 31259.79 17-DEC-13:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.202735E+12 0.00 3586.72 0.118663E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.130263E+09 0.00 8.62 0.130263E+09 0.00 0.00 0.00 0.00 7851.58   7851.58   0.00 0.00 0.00
Maximum of Months 0.484406E+11 0.00 697.31 0.274412E+11 0.00 0.00 0.00 0.00 53362.96   48287.43   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.168112E+09 0.00 20.78 58700258.28 0.00 0.00 0.00 0.00 24360.45 19-JAN-19:03 24360.45 19-JAN-19:03 0.00 0.00 0.00
February 62100756.94 0.00 9.27 58122841.49 0.00 0.00 0.00 0.00 28292.89 20-FEB-09:02 28292.89 20-FEB-09:02 0.00 0.00 0.00
March 0.214719E+10 0.00 137.70 0.127831E+10 0.00 0.00 0.00 0.00 82192.60 02-MAR-21:42 82192.60 02-MAR-21:42 0.00 0.00 0.00
April 0.113307E+11 0.00 328.38 0.623725E+10 0.00 0.00 0.00 0.00 90425.09 27-APR-18:21 87150.50 10-APR-20:41 0.00 0.00 0.00
May 0.281258E+11 0.00 413.75 0.171175E+11 0.00 0.00 0.00 0.00 108263.62 31-MAY-21:51 90567.77 27-MAY-21:51 0.00 0.00 0.00
June 0.430857E+11 0.00 342.66 0.277804E+11 0.00 0.00 0.00 0.00 121147.97 24-JUN-21:51 89774.30 02-JUN-21:41 0.00 0.00 0.00
July 0.620867E+11 0.00 484.19 0.400743E+11 0.00 0.00 0.00 0.00 123891.67 05-JUL-21:51 85400.48 11-JUL-15:02 0.00 0.00 0.00
August 0.555811E+11 0.00 453.28 0.358818E+11 0.00 0.00 0.00 0.00 116418.19 10-AUG-21:51 85482.20 08-AUG-15:02 0.00 0.00 0.00
September 0.305037E+11 0.00 322.45 0.178918E+11 0.00 0.00 0.00 0.00 117944.00 13-SEP-21:51 89233.59 10-SEP-21:51 0.00 0.00 0.00
October 0.148694E+11 0.00 352.35 0.782141E+10 0.00 0.00 0.00 0.00 108755.15 05-OCT-21:51 86569.73 25-OCT-21:51 0.00 0.00 0.00
November 0.305489E+10 0.00 173.59 0.145012E+10 0.00 0.00 0.00 0.00 80949.60 11-NOV-09:02 80949.60 11-NOV-09:02 0.00 0.00 0.00
December 0.140957E+09 0.00 18.40 94114166.63 0.00 0.00 0.00 0.00 35463.36 25-DEC-09:02 27031.30 25-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.251156E+12 0.00 3056.81 0.155744E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 62100756.94 0.00 9.27 58122841.49 0.00 0.00 0.00 0.00 24360.45   24360.45   0.00 0.00 0.00
Maximum of Months 0.620867E+11 0.00 484.19 0.400743E+11 0.00 0.00 0.00 0.00 123891.67   90567.77   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 85495252.77 0.00 17.28 80450946.33 0.00 0.00 0.00 0.00 10405.53 17-JAN-16:01 10405.53 17-JAN-16:01 0.00 0.00 0.00
February 0.140679E+09 0.00 27.08 0.140549E+09 0.00 0.00 0.00 0.00 14149.67 25-FEB-09:02 14149.67 25-FEB-09:02 0.00 0.00 0.00
March 0.683041E+09 0.00 121.31 0.617701E+09 0.00 0.00 0.00 0.00 14831.80 27-MAR-15:02 14504.52 01-MAR-09:02 0.00 0.00 0.00
April 0.198946E+10 0.00 292.16 0.130790E+10 0.00 0.00 0.00 0.00 16868.16 08-APR-08:51 15925.20 08-APR-08:51 0.00 0.00 0.00
May 0.399063E+10 0.00 453.74 0.250216E+10 0.00 0.00 0.00 0.00 19863.27 31-MAY-08:32 17538.56 30-MAY-08:62 0.00 0.00 0.00
June 0.679433E+10 0.00 466.83 0.396520E+10 0.00 0.00 0.00 0.00 20723.40 25-JUN-07:51 17015.04 26-JUN-08:32 0.00 0.00 0.00
July 0.104109E+11 0.00 595.98 0.623657E+10 0.00 0.00 0.00 0.00 20744.27 01-JUL-08:32 17258.50 11-JUL-08:32 0.00 0.00 0.00
August 0.110731E+11 0.00 606.26 0.719138E+10 0.00 0.00 0.00 0.00 20478.84 12-AUG-08:61 17814.72 30-AUG-08:32 0.00 0.00 0.00
September 0.572160E+10 0.00 455.27 0.344233E+10 0.00 0.00 0.00 0.00 20118.25 04-SEP-08:32 17170.03 10-SEP-08:32 0.00 0.00 0.00
October 0.356015E+10 0.00 438.57 0.217931E+10 0.00 0.00 0.00 0.00 19259.10 24-OCT-08:51 15989.55 15-OCT-08:51 0.00 0.00 0.00
November 0.517606E+09 0.00 110.20 0.369301E+09 0.00 0.00 0.00 0.00 14506.59 03-NOV-15:01 14506.59 03-NOV-15:01 0.00 0.00 0.00
December 0.161465E+09 0.00 31.16 0.153425E+09 0.00 0.00 0.00 0.00 14076.03 17-DEC-09:02 14076.03 17-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.451285E+11 0.00 3615.85 0.281863E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 85495252.77 0.00 17.28 80450946.33 0.00 0.00 0.00 0.00 10405.53   10405.53   0.00 0.00 0.00
Maximum of Months 0.110731E+11 0.00 606.26 0.719138E+10 0.00 0.00 0.00 0.00 20744.27   17814.72   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4714085.88 0.00 2.86 2551676.07 0.00 0.00 0.00 0.00 2669.26 26-JAN-09:03 2669.26 26-JAN-09:03 0.00 0.00 0.00
February 21192545.54 0.00 7.46 21192545.54 0.00 0.00 0.00 0.00 10261.68 19-FEB-09:02 10261.68 19-FEB-09:02 0.00 0.00 0.00
March 0.266214E+09 0.00 57.11 0.229633E+09 0.00 0.00 0.00 0.00 13911.14 29-MAR-08:62 13911.14 29-MAR-08:62 0.00 0.00 0.00
April 0.133328E+10 0.00 228.69 0.831800E+09 0.00 0.00 0.00 0.00 16283.19 08-APR-08:51 15248.87 08-APR-08:51 0.00 0.00 0.00
May 0.351664E+10 0.00 432.34 0.215623E+10 0.00 0.00 0.00 0.00 19348.41 31-MAY-08:32 17068.61 30-MAY-08:62 0.00 0.00 0.00
June 0.641026E+10 0.00 465.37 0.368773E+10 0.00 0.00 0.00 0.00 20028.91 25-JUN-07:51 16564.40 26-JUN-08:32 0.00 0.00 0.00
July 0.988022E+10 0.00 595.15 0.580870E+10 0.00 0.00 0.00 0.00 20174.01 01-JUL-08:32 16783.89 11-JUL-08:32 0.00 0.00 0.00
August 0.979587E+10 0.00 602.99 0.604671E+10 0.00 0.00 0.00 0.00 19944.99 12-AUG-08:61 16863.34 30-AUG-08:32 0.00 0.00 0.00
September 0.440549E+10 0.00 432.30 0.243052E+10 0.00 0.00 0.00 0.00 19589.92 06-SEP-08:32 16391.14 10-SEP-08:32 0.00 0.00 0.00
October 0.178529E+10 0.00 295.92 0.979052E+09 0.00 0.00 0.00 0.00 18394.85 25-OCT-08:51 14698.55 15-OCT-08:51 0.00 0.00 0.00
November 0.157015E+09 0.00 39.53 87346622.69 0.00 0.00 0.00 0.00 13449.52 11-NOV-09:02 13175.08 06-NOV-09:02 0.00 0.00 0.00
December 11366206.49 0.00 6.48 10060656.72 0.00 0.00 0.00 0.00 4996.30 17-DEC-09:02 4996.30 17-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.375876E+11 0.00 3166.21 0.222915E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 4714085.88 0.00 2.86 2551676.07 0.00 0.00 0.00 0.00 2669.26   2669.26   0.00 0.00 0.00
Maximum of Months 0.988022E+10 0.00 602.99 0.604671E+10 0.00 0.00 0.00 0.00 20174.01   17068.61   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 10726546.90 0.00 7.94 10622954.20 0.00 0.00 0.00 0.00 4131.40 17-JAN-16:01 4131.40 17-JAN-16:01 0.00 0.00 0.00
February 30267576.11 0.00 19.85 30267576.11 0.00 0.00 0.00 0.00 4131.82 20-FEB-16:01 4131.82 20-FEB-16:01 0.00 0.00 0.00
March 0.203073E+09 0.00 105.13 0.185008E+09 0.00 0.00 0.00 0.00 4414.68 27-MAR-15:02 4134.92 29-MAR-18:01 0.00 0.00 0.00
April 0.483204E+09 0.00 244.69 0.330081E+09 0.00 0.00 0.00 0.00 4888.31 27-APR-18:21 4604.12 10-APR-20:41 0.00 0.00 0.00
May 0.963965E+09 0.00 407.18 0.607092E+09 0.00 0.00 0.00 0.00 5546.85 31-MAY-21:51 4584.89 02-MAY-18:21 0.00 0.00 0.00
June 0.190758E+10 0.00 457.05 0.115051E+10 0.00 0.00 0.00 0.00 5931.74 24-JUN-21:51 4592.55 04-JUN-21:51 0.00 0.00 0.00
July 0.279613E+10 0.00 589.27 0.170878E+10 0.00 0.00 0.00 0.00 6145.82 05-JUL-21:51 4091.96 11-JUL-08:51 0.00 0.00 0.00
August 0.293750E+10 0.00 597.94 0.193751E+10 0.00 0.00 0.00 0.00 5902.47 10-AUG-21:51 4287.68 30-AUG-08:51 0.00 0.00 0.00
September 0.140756E+10 0.00 425.78 0.831042E+09 0.00 0.00 0.00 0.00 5813.15 13-SEP-21:51 4424.96 11-SEP-21:51 0.00 0.00 0.00
October 0.838486E+09 0.00 379.56 0.499503E+09 0.00 0.00 0.00 0.00 5487.31 05-OCT-21:51 4446.45 30-OCT-16:41 0.00 0.00 0.00
November 63145484.51 0.00 63.07 44254208.64 0.00 0.00 0.00 0.00 4135.06 03-NOV-15:01 4135.06 03-NOV-15:01 0.00 0.00 0.00
December 9880437.26 0.00 9.28 9688432.65 0.00 0.00 0.00 0.00 4130.20 17-DEC-16:01 4130.20 17-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.116515E+11 0.00 3306.74 0.734436E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 9880437.26 0.00 7.94 9688432.65 0.00 0.00 0.00 0.00 4130.20   4091.96   0.00 0.00 0.00
Maximum of Months 0.293750E+10 0.00 597.94 0.193751E+10 0.00 0.00 0.00 0.00 6145.82   4604.12   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 524483.94 0.00 0.79 482097.37 0.00 0.00 0.00 0.00 1353.64 17-JAN-16:01 1353.64 17-JAN-16:01 0.00 0.00 0.00
February 2155926.38 0.00 4.45 2155926.38 0.00 0.00 0.00 0.00 3208.76 20-FEB-16:01 3208.76 20-FEB-16:01 0.00 0.00 0.00
March 80018211.96 0.00 50.75 72406746.23 0.00 0.00 0.00 0.00 4159.59 27-MAR-15:02 4011.22 07-MAR-16:01 0.00 0.00 0.00
April 0.316726E+09 0.00 185.17 0.208058E+09 0.00 0.00 0.00 0.00 4756.48 27-APR-18:21 4313.93 09-APR-18:11 0.00 0.00 0.00
May 0.844299E+09 0.00 382.86 0.519831E+09 0.00 0.00 0.00 0.00 5381.78 31-MAY-21:51 4380.95 02-MAY-18:21 0.00 0.00 0.00
June 0.181075E+10 0.00 453.39 0.108059E+10 0.00 0.00 0.00 0.00 5751.65 24-JUN-21:51 4434.65 04-JUN-21:51 0.00 0.00 0.00
July 0.266062E+10 0.00 586.27 0.159986E+10 0.00 0.00 0.00 0.00 5960.66 05-JUL-21:51 3988.79 11-JUL-08:51 0.00 0.00 0.00
August 0.260138E+10 0.00 590.51 0.164964E+10 0.00 0.00 0.00 0.00 5699.54 10-AUG-21:51 4059.06 30-AUG-08:51 0.00 0.00 0.00
September 0.105488E+10 0.00 388.55 0.567655E+09 0.00 0.00 0.00 0.00 5616.81 13-SEP-21:51 4067.38 11-SEP-21:51 0.00 0.00 0.00
October 0.378869E+09 0.00 252.71 0.187976E+09 0.00 0.00 0.00 0.00 5223.34 05-OCT-21:51 4012.99 17-OCT-15:02 0.00 0.00 0.00
November 10563544.26 0.00 11.16 7733680.27 0.00 0.00 0.00 0.00 4011.66 03-NOV-15:01 4011.66 03-NOV-15:01 0.00 0.00 0.00
December 475791.88 0.00 0.35 445850.57 0.00 0.00 0.00 0.00 618.37 08-DEC-16:03 618.37 08-DEC-16:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.976127E+10 0.00 2906.96 0.589684E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 475791.88 0.00 0.35 445850.57 0.00 0.00 0.00 0.00 618.37   618.37   0.00 0.00 0.00
Maximum of Months 0.266062E+10 0.00 590.51 0.164964E+10 0.00 0.00 0.00 0.00 5960.66   4434.65   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.914772E+09 0.00 93.84 0.908162E+09 0.00 0.00 0.00 0.00 19355.94 19-JAN-16:01 19355.94 19-JAN-16:01 0.00 0.00 0.00
February 0.133966E+10 0.00 145.16 0.133939E+10 0.00 0.00 0.00 0.00 19358.27 20-FEB-16:01 19358.27 20-FEB-16:01 0.00 0.00 0.00
March 0.247373E+10 0.00 231.32 0.219413E+10 0.00 0.00 0.00 0.00 20243.42 27-MAR-15:02 19368.43 28-MAR-15:01 0.00 0.00 0.00
April 0.334134E+10 0.00 316.84 0.227840E+10 0.00 0.00 0.00 0.00 21065.74 09-APR-18:11 20099.72 07-APR-21:51 0.00 0.00 0.00
May 0.486805E+10 0.00 446.47 0.283165E+10 0.00 0.00 0.00 0.00 24375.77 31-MAY-21:51 20283.01 27-MAY-21:51 0.00 0.00 0.00
June 0.859848E+10 0.00 447.78 0.485274E+10 0.00 0.00 0.00 0.00 27253.82 24-JUN-21:51 20216.05 04-JUN-08:51 0.00 0.00 0.00
July 0.135292E+11 0.00 581.47 0.804445E+10 0.00 0.00 0.00 0.00 27754.29 05-JUL-21:51 19278.13 11-JUL-08:51 0.00 0.00 0.00
August 0.151300E+11 0.00 594.18 0.100140E+11 0.00 0.00 0.00 0.00 26681.83 10-AUG-21:51 20033.21 30-AUG-08:51 0.00 0.00 0.00
September 0.952228E+10 0.00 448.34 0.614338E+10 0.00 0.00 0.00 0.00 27105.94 13-SEP-21:51 20707.44 03-SEP-08:51 0.00 0.00 0.00
October 0.876190E+10 0.00 494.37 0.636009E+10 0.00 0.00 0.00 0.00 26161.77 04-OCT-21:51 21310.51 30-OCT-16:41 0.00 0.00 0.00
November 0.231431E+10 0.00 231.28 0.181883E+10 0.00 0.00 0.00 0.00 19362.33 06-NOV-16:02 19362.33 06-NOV-16:02 0.00 0.00 0.00
December 0.161493E+10 0.00 142.25 0.160100E+10 0.00 0.00 0.00 0.00 19352.80 03-DEC-16:02 19352.80 03-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.724087E+11 0.00 4173.32 0.483862E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.914772E+09 0.00 93.84 0.908162E+09 0.00 0.00 0.00 0.00 19352.80   19278.13   0.00 0.00 0.00
Maximum of Months 0.151300E+11 0.00 594.18 0.100140E+11 0.00 0.00 0.00 0.00 27754.29   21310.51   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 701.21 460.14 241.07 664.76 680.26 0.00 0.00 0.00
February 927.98 616.76 311.22 896.77 673.44 0.00 0.00 0.00
March 822.19 452.60 369.58 843.30 480.21 0.00 0.00 0.00
April 654.44 264.77 389.67 707.86 339.05 0.00 0.00 0.00
May 562.08 115.08 447.01 661.76 193.22 0.00 0.00 0.00
June 530.75 81.78 448.97 718.02 92.70 0.00 0.00 0.00
July 552.24 93.21 459.04 822.20 40.08 0.00 0.00 0.00
August 739.68 272.86 466.82 1088.23 69.97 0.00 0.00 0.00
September 780.56 391.91 388.65 1025.11 148.09 0.00 0.00 0.00
October 1103.06 691.71 411.35 1333.18 304.01 0.00 0.00 0.00
November 763.80 458.18 305.62 787.66 472.28 0.00 0.00 0.00
December 757.58 538.07 219.51 749.04 612.03 0.00 0.00 0.00
                 
Annual Sum or Average 740.41 368.50 371.91 858.37 340.26 0.00 0.00 0.00
Minimum of Months 530.75 81.78 219.51 661.76 40.08 0.00 0.00 0.00
Maximum of Months 1103.06 691.71 466.82 1333.18 680.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1974.55 1295.73 678.82 1848.95 1977.77 0.00 0.00 0.00
February 2613.12 1736.75 876.37 2493.61 1960.72 0.00 0.00 0.00
March 2315.23 1274.50 1040.72 2342.07 1441.40 0.00 0.00 0.00
April 1842.86 745.58 1097.28 1956.16 1043.92 0.00 0.00 0.00
May 1582.79 324.05 1258.74 1813.60 620.81 0.00 0.00 0.00
June 1494.54 230.28 1264.27 1984.66 308.33 0.00 0.00 0.00
July 1555.08 262.47 1292.62 2285.63 140.61 0.00 0.00 0.00
August 2082.88 768.36 1314.52 3038.93 222.32 0.00 0.00 0.00
September 2198.00 1103.59 1094.42 2852.20 480.72 0.00 0.00 0.00
October 3106.15 1947.82 1158.33 3715.59 942.36 0.00 0.00 0.00
November 2150.80 1290.21 860.60 2181.69 1419.49 0.00 0.00 0.00
December 2133.29 1515.17 618.12 2082.82 1798.98 0.00 0.00 0.00
                 
Annual Sum or Average 2084.94 1037.67 1047.27 2383.61 1024.51 0.00 0.00 0.00
Minimum of Months 1494.54 230.28 618.12 1813.60 140.61 0.00 0.00 0.00
Maximum of Months 3106.15 1947.82 1314.52 3715.59 1977.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2565.06 1683.23 881.83 2444.47 2695.82 0.00 0.00 0.00
February 3394.59 2256.14 1138.45 3307.06 2651.22 0.00 0.00 0.00
March 3007.61 1655.65 1351.96 3106.55 1956.38 0.00 0.00 0.00
April 2393.98 968.55 1425.43 2591.97 1427.59 0.00 0.00 0.00
May 2056.14 420.96 1635.17 2401.00 850.74 0.00 0.00 0.00
June 1941.50 299.14 1642.35 2636.24 412.77 0.00 0.00 0.00
July 2020.14 340.96 1679.18 3046.03 181.96 0.00 0.00 0.00
August 2705.78 998.14 1707.64 4046.42 284.03 0.00 0.00 0.00
September 2855.33 1433.62 1421.71 3780.69 638.86 0.00 0.00 0.00
October 4035.07 2530.33 1504.74 4926.15 1250.32 0.00 0.00 0.00
November 2794.02 1676.05 1117.96 2882.45 1938.89 0.00 0.00 0.00
December 2771.26 1968.29 802.97 2752.55 2453.74 0.00 0.00 0.00
                 
Annual Sum or Average 2708.45 1347.99 1360.46 3160.98 1388.06 0.00 0.00 0.00
Minimum of Months 1941.50 299.14 802.97 2401.00 181.96 0.00 0.00 0.00
Maximum of Months 4035.07 2530.33 1707.64 4926.15 2695.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 132.40 136.52 0.00 0.00 0.00
February 183.48 121.94 61.53 178.56 135.52 0.00 0.00 0.00
March 162.56 89.49 73.07 166.91 96.81 0.00 0.00 0.00
April 129.39 52.35 77.04 139.29 68.40 0.00 0.00 0.00
May 111.13 22.75 88.38 128.09 39.97 0.00 0.00 0.00
June 104.94 16.17 88.77 140.50 18.65 0.00 0.00 0.00
July 109.19 18.43 90.76 168.02 5.24 0.00 0.00 0.00
August 146.25 53.95 92.30 222.24 10.33 0.00 0.00 0.00
September 154.33 77.49 76.84 204.06 28.33 0.00 0.00 0.00
October 218.09 136.76 81.33 265.24 58.81 0.00 0.00 0.00
November 151.02 90.59 60.43 157.57 93.12 0.00 0.00 0.00
December 149.79 106.39 43.40 149.89 121.73 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 171.12 67.40 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 128.09 5.24 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 265.24 136.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 59.09 276.11 0.00 0.00 0.00
February 151.36 66.43 84.93 97.28 279.27 0.00 0.00 0.00
March 224.83 104.19 120.64 192.98 180.48 0.00 0.00 0.00
April 244.19 104.35 139.83 243.47 124.55 0.00 0.00 0.00
May 285.26 108.44 176.82 326.87 71.60 0.00 0.00 0.00
June 311.67 125.78 185.89 404.51 33.15 0.00 0.00 0.00
July 291.59 109.58 182.02 419.56 9.56 0.00 0.00 0.00
August 322.62 149.16 173.45 459.63 19.05 0.00 0.00 0.00
September 229.53 100.21 129.33 285.70 52.54 0.00 0.00 0.00
October 227.75 110.94 116.80 248.00 112.73 0.00 0.00 0.00
November 107.25 31.33 75.92 69.59 185.51 0.00 0.00 0.00
December 94.74 40.89 53.84 55.63 250.10 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 239.55 132.06 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 55.63 9.56 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 459.63 279.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 1.56 153.36 0.00 0.00 0.00
February 36.50 0.00 36.50 3.35 156.99 0.00 0.00 0.00
March 50.63 0.00 50.63 17.71 101.38 0.00 0.00 0.00
April 60.93 0.25 60.68 38.75 67.34 0.00 0.00 0.00
May 81.04 2.97 78.07 77.29 36.77 0.00 0.00 0.00
June 85.49 4.55 80.95 106.17 17.18 0.00 0.00 0.00
July 82.98 3.24 79.74 124.69 5.02 0.00 0.00 0.00
August 73.38 0.98 72.41 109.70 9.71 0.00 0.00 0.00
September 55.25 0.03 55.22 61.55 27.62 0.00 0.00 0.00
October 47.78 0.00 47.78 36.19 60.21 0.00 0.00 0.00
November 33.51 0.00 33.51 10.11 100.71 0.00 0.00 0.00
December 23.27 0.00 23.27 1.07 138.25 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 49.33 72.40 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 1.07 5.02 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 124.69 156.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 62.24 273.26 0.00 0.00 0.00
February 151.36 66.43 84.93 101.99 274.93 0.00 0.00 0.00
March 224.83 104.19 120.64 198.43 177.79 0.00 0.00 0.00
April 244.19 104.35 139.83 247.10 123.21 0.00 0.00 0.00
May 285.26 108.44 176.82 328.48 71.15 0.00 0.00 0.00
June 311.67 125.78 185.89 405.30 32.88 0.00 0.00 0.00
July 291.59 109.58 182.02 420.50 9.39 0.00 0.00 0.00
August 322.62 149.16 173.45 462.13 18.45 0.00 0.00 0.00
September 229.53 100.21 129.33 289.53 50.62 0.00 0.00 0.00
October 227.75 110.94 116.80 254.45 109.23 0.00 0.00 0.00
November 107.25 31.33 75.92 74.01 182.19 0.00 0.00 0.00
December 94.74 40.89 53.84 59.34 246.47 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 242.98 129.98 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 59.34 9.39 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 462.13 274.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.89 72.77 38.12 105.38 106.68 0.00 0.00 0.00
February 146.75 97.54 49.22 140.79 110.43 0.00 0.00 0.00
March 130.02 71.58 58.45 131.99 81.58 0.00 0.00 0.00
April 103.50 41.87 61.62 110.26 58.62 0.00 0.00 0.00
May 88.89 18.20 70.69 101.57 35.47 0.00 0.00 0.00
June 83.93 12.93 71.00 113.60 15.91 0.00 0.00 0.00
July 87.33 14.74 72.59 132.76 5.94 0.00 0.00 0.00
August 116.97 43.15 73.82 176.11 10.23 0.00 0.00 0.00
September 123.44 61.98 61.46 162.49 25.61 0.00 0.00 0.00
October 174.44 109.39 65.05 209.97 53.35 0.00 0.00 0.00
November 120.79 72.46 48.33 122.95 80.04 0.00 0.00 0.00
December 119.81 85.09 34.71 118.09 98.67 0.00 0.00 0.00
                 
Annual Sum or Average 117.09 58.28 58.81 135.54 56.57 0.00 0.00 0.00
Minimum of Months 83.93 12.93 34.71 101.57 5.94 0.00 0.00 0.00
Maximum of Months 174.44 109.39 73.82 209.97 110.43 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 21.34 0.00 21.34 0.91 128.05 0.00 0.00 0.00
February 29.20 0.00 29.20 2.40 129.83 0.00 0.00 0.00
March 40.51 0.00 40.51 14.32 82.69 0.00 0.00 0.00
April 48.75 0.20 48.55 32.68 54.11 0.00 0.00 0.00
May 64.84 2.37 62.47 66.01 28.31 0.00 0.00 0.00
June 68.40 3.64 64.76 91.07 11.48 0.00 0.00 0.00
July 66.39 2.59 63.80 105.34 2.90 0.00 0.00 0.00
August 58.71 0.78 57.93 93.87 6.24 0.00 0.00 0.00
September 44.21 0.03 44.18 53.21 19.76 0.00 0.00 0.00
October 38.23 0.00 38.23 31.42 46.14 0.00 0.00 0.00
November 26.81 0.00 26.81 7.79 84.10 0.00 0.00 0.00
December 18.62 0.00 18.62 0.66 115.80 0.00 0.00 0.00
                 
Annual Sum or Average 43.92 0.81 43.11 41.91 58.72 0.00 0.00 0.00
Minimum of Months 18.62 0.00 18.62 0.66 2.90 0.00 0.00 0.00
Maximum of Months 68.40 3.64 64.76 105.34 129.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.76 41.46 62.31 57.58 271.12 0.00 0.00 0.00
February 161.10 75.02 86.08 103.65 268.94 0.00 0.00 0.00
March 206.88 87.92 118.96 171.69 181.02 0.00 0.00 0.00
April 247.65 108.70 138.95 245.78 120.47 0.00 0.00 0.00
May 298.99 119.15 179.84 344.61 69.01 0.00 0.00 0.00
June 277.63 100.56 177.07 361.15 30.72 0.00 0.00 0.00
July 278.48 100.26 178.22 402.42 9.03 0.00 0.00 0.00
August 314.15 141.73 172.42 446.34 17.76 0.00 0.00 0.00
September 235.00 105.87 129.14 291.75 49.78 0.00 0.00 0.00
October 212.30 96.10 116.20 228.21 109.01 0.00 0.00 0.00
November 131.49 50.53 80.96 99.37 180.43 0.00 0.00 0.00
December 102.80 48.51 54.30 63.81 243.77 0.00 0.00 0.00
                 
Annual Sum or Average 214.53 89.75 124.78 235.61 128.48 0.00 0.00 0.00
Minimum of Months 102.80 41.46 54.30 57.58 9.03 0.00 0.00 0.00
Maximum of Months 314.15 141.73 179.84 446.34 271.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 132.10 136.30 0.00 0.00 0.00
February 183.48 121.94 61.53 177.80 135.16 0.00 0.00 0.00
March 162.56 89.49 73.07 165.98 95.79 0.00 0.00 0.00
April 129.39 52.35 77.04 138.28 67.54 0.00 0.00 0.00
May 111.13 22.75 88.38 127.02 38.78 0.00 0.00 0.00
June 104.94 16.17 88.77 140.62 16.97 0.00 0.00 0.00
July 109.19 18.43 90.76 167.43 4.87 0.00 0.00 0.00
August 146.25 53.95 92.30 221.22 9.86 0.00 0.00 0.00
September 154.33 77.49 76.84 203.26 27.30 0.00 0.00 0.00
October 218.09 136.76 81.33 264.83 57.54 0.00 0.00 0.00
November 151.02 90.59 60.43 156.70 93.20 0.00 0.00 0.00
December 149.79 106.39 43.40 149.45 121.55 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 170.45 66.69 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 127.02 4.87 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 264.83 136.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 1.38 153.33 0.00 0.00 0.00
February 36.50 0.00 36.50 3.11 156.98 0.00 0.00 0.00
March 50.63 0.00 50.63 16.91 100.45 0.00 0.00 0.00
April 60.93 0.25 60.68 37.69 66.71 0.00 0.00 0.00
May 81.04 2.97 78.07 76.33 35.94 0.00 0.00 0.00
June 85.49 4.55 80.95 106.57 15.89 0.00 0.00 0.00
July 82.98 3.24 79.74 124.10 4.70 0.00 0.00 0.00
August 73.38 0.98 72.41 108.62 9.27 0.00 0.00 0.00
September 55.25 0.03 55.22 60.52 26.68 0.00 0.00 0.00
October 47.78 0.00 47.78 35.32 58.64 0.00 0.00 0.00
November 33.51 0.00 33.51 9.52 100.96 0.00 0.00 0.00
December 23.27 0.00 23.27 0.92 138.23 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 48.73 71.84 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 0.92 4.70 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 124.10 156.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.76 41.46 62.31 59.52 267.12 0.00 0.00 0.00
February 161.10 75.02 86.08 106.85 262.90 0.00 0.00 0.00
March 206.88 87.92 118.96 176.52 177.58 0.00 0.00 0.00
April 247.65 108.70 138.95 248.88 119.00 0.00 0.00 0.00
May 298.99 119.15 179.84 345.88 68.58 0.00 0.00 0.00
June 277.63 100.56 177.07 361.91 30.52 0.00 0.00 0.00
July 278.48 100.26 178.22 403.35 8.88 0.00 0.00 0.00
August 314.15 141.73 172.42 448.80 17.17 0.00 0.00 0.00
September 235.00 105.87 129.14 295.12 47.91 0.00 0.00 0.00
October 212.30 96.10 116.20 233.95 104.99 0.00 0.00 0.00
November 131.49 50.53 80.96 103.13 176.43 0.00 0.00 0.00
December 102.80 48.51 54.30 65.87 238.36 0.00 0.00 0.00
                 
Annual Sum or Average 214.53 89.75 124.78 238.39 125.87 0.00 0.00 0.00
Minimum of Months 102.80 41.46 54.30 59.52 8.88 0.00 0.00 0.00
Maximum of Months 314.15 141.73 179.84 448.80 267.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 33.78 0.00 33.78 1.01 209.60 0.00 0.00 0.00
February 46.23 0.00 46.23 3.17 213.02 0.00 0.00 0.00
March 64.12 0.00 64.12 21.29 134.78 0.00 0.00 0.00
April 77.16 0.32 76.84 50.32 89.75 0.00 0.00 0.00
May 102.63 3.76 98.87 102.20 48.90 0.00 0.00 0.00
June 108.27 5.76 102.51 138.47 23.80 0.00 0.00 0.00
July 105.09 4.10 100.99 156.29 9.28 0.00 0.00 0.00
August 92.93 1.23 91.70 136.15 16.06 0.00 0.00 0.00
September 69.98 0.04 69.94 78.22 39.22 0.00 0.00 0.00
October 60.51 0.00 60.51 45.09 82.90 0.00 0.00 0.00
November 42.44 0.00 42.44 11.24 138.24 0.00 0.00 0.00
December 29.46 0.00 29.46 0.77 189.93 0.00 0.00 0.00
                 
Annual Sum or Average 69.52 1.28 68.24 62.42 98.99 0.00 0.00 0.00
Minimum of Months 29.46 0.00 29.46 0.77 9.28 0.00 0.00 0.00
Maximum of Months 108.27 5.76 102.51 156.29 213.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.45 0.00 12.45 0.37 77.27 0.00 0.00 0.00
February 17.04 0.00 17.04 1.17 78.53 0.00 0.00 0.00
March 23.64 0.00 23.64 7.85 49.69 0.00 0.00 0.00
April 28.45 0.12 28.33 18.55 33.09 0.00 0.00 0.00
May 37.83 1.38 36.45 37.67 18.03 0.00 0.00 0.00
June 39.91 2.12 37.79 51.04 8.77 0.00 0.00 0.00
July 38.74 1.51 37.23 57.62 3.42 0.00 0.00 0.00
August 34.26 0.46 33.80 50.19 5.92 0.00 0.00 0.00
September 25.80 0.01 25.78 28.84 14.46 0.00 0.00 0.00
October 22.31 0.00 22.31 16.62 30.56 0.00 0.00 0.00
November 15.65 0.00 15.65 4.14 50.96 0.00 0.00 0.00
December 10.86 0.00 10.86 0.28 70.02 0.00 0.00 0.00
                 
Annual Sum or Average 25.63 0.47 25.16 23.01 36.49 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 0.28 3.42 0.00 0.00 0.00
Maximum of Months 39.91 2.12 37.79 57.62 78.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 64.69 42.45 22.24 61.37 67.39 0.00 0.00 0.00
February 85.61 56.90 28.71 83.22 66.18 0.00 0.00 0.00
March 75.85 41.75 34.10 78.69 46.70 0.00 0.00 0.00
April 60.37 24.43 35.95 66.19 33.11 0.00 0.00 0.00
May 51.85 10.62 41.24 61.55 19.28 0.00 0.00 0.00
June 48.96 7.54 41.42 67.06 9.30 0.00 0.00 0.00
July 50.95 8.60 42.35 77.97 3.50 0.00 0.00 0.00
August 68.24 25.17 43.07 103.20 6.09 0.00 0.00 0.00
September 72.01 36.16 35.85 96.15 14.29 0.00 0.00 0.00
October 101.76 63.81 37.95 125.16 28.93 0.00 0.00 0.00
November 70.46 42.27 28.19 73.56 45.83 0.00 0.00 0.00
December 69.89 49.64 20.25 69.78 59.97 0.00 0.00 0.00
                 
Annual Sum or Average 68.31 34.00 34.31 80.35 33.20 0.00 0.00 0.00
Minimum of Months 48.96 7.54 20.25 61.37 3.50 0.00 0.00 0.00
Maximum of Months 101.76 63.81 43.07 125.16 67.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 175.58 115.22 60.36 166.57 182.90 0.00 0.00 0.00
February 232.36 154.43 77.93 225.87 179.61 0.00 0.00 0.00
March 205.87 113.33 92.54 213.58 126.74 0.00 0.00 0.00
April 163.87 66.30 97.57 179.66 89.86 0.00 0.00 0.00
May 140.74 28.82 111.93 167.05 52.34 0.00 0.00 0.00
June 132.90 20.48 112.42 182.02 25.23 0.00 0.00 0.00
July 138.28 23.34 114.94 211.63 9.49 0.00 0.00 0.00
August 185.21 68.32 116.89 280.12 16.54 0.00 0.00 0.00
September 195.45 98.13 97.32 260.96 38.77 0.00 0.00 0.00
October 276.20 173.20 103.00 339.72 78.54 0.00 0.00 0.00
November 191.25 114.73 76.53 199.65 124.40 0.00 0.00 0.00
December 189.69 134.73 54.96 189.38 162.78 0.00 0.00 0.00
                 
Annual Sum or Average 185.40 92.27 93.13 218.09 90.10 0.00 0.00 0.00
Minimum of Months 132.90 20.48 54.96 166.57 9.49 0.00 0.00 0.00
Maximum of Months 276.20 173.20 116.89 339.72 182.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 131.82 136.12 0.00 0.00 0.00
February 183.48 121.94 61.53 177.68 135.29 0.00 0.00 0.00
March 162.56 89.49 73.07 165.64 96.78 0.00 0.00 0.00
April 129.39 52.35 77.04 137.88 68.47 0.00 0.00 0.00
May 111.13 22.75 88.38 126.25 40.49 0.00 0.00 0.00
June 104.94 16.17 88.77 138.84 19.25 0.00 0.00 0.00
July 109.19 18.43 90.76 166.81 5.20 0.00 0.00 0.00
August 146.25 53.95 92.30 220.95 10.10 0.00 0.00 0.00
September 154.33 77.49 76.84 202.57 28.57 0.00 0.00 0.00
October 218.09 136.76 81.33 263.48 58.78 0.00 0.00 0.00
November 151.02 90.59 60.43 156.99 92.40 0.00 0.00 0.00
December 149.79 106.39 43.40 149.42 121.12 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 169.92 67.33 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 126.25 5.20 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 263.48 136.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 58.77 275.56 0.00 0.00 0.00
February 151.36 66.43 84.93 96.30 279.26 0.00 0.00 0.00
March 224.83 104.19 120.64 191.02 180.09 0.00 0.00 0.00
April 244.19 104.35 139.83 240.81 124.26 0.00 0.00 0.00
May 285.26 108.44 176.82 322.89 72.09 0.00 0.00 0.00
June 311.67 125.78 185.89 400.35 33.90 0.00 0.00 0.00
July 291.59 109.58 182.02 416.83 9.44 0.00 0.00 0.00
August 322.62 149.16 173.45 457.34 18.60 0.00 0.00 0.00
September 229.53 100.21 129.33 283.35 52.74 0.00 0.00 0.00
October 227.75 110.94 116.80 245.73 112.45 0.00 0.00 0.00
November 107.25 31.33 75.92 69.22 184.23 0.00 0.00 0.00
December 94.74 40.89 53.84 55.37 249.00 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 237.52 131.80 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 55.37 9.44 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 457.34 279.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 1.60 153.08 0.00 0.00 0.00
February 36.50 0.00 36.50 3.38 157.10 0.00 0.00 0.00
March 50.63 0.00 50.63 17.59 101.28 0.00 0.00 0.00
April 60.93 0.25 60.68 38.27 67.23 0.00 0.00 0.00
May 81.04 2.97 78.07 75.75 37.16 0.00 0.00 0.00
June 85.49 4.55 80.95 104.80 17.67 0.00 0.00 0.00
July 82.98 3.24 79.74 123.86 5.00 0.00 0.00 0.00
August 73.38 0.98 72.41 109.31 9.48 0.00 0.00 0.00
September 55.25 0.03 55.22 61.09 27.67 0.00 0.00 0.00
October 47.78 0.00 47.78 36.19 59.70 0.00 0.00 0.00
November 33.51 0.00 33.51 10.28 99.79 0.00 0.00 0.00
December 23.27 0.00 23.27 1.15 137.50 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 48.92 72.24 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 1.15 5.00 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 123.86 157.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 61.96 272.83 0.00 0.00 0.00
February 151.36 66.43 84.93 101.21 275.03 0.00 0.00 0.00
March 224.83 104.19 120.64 196.91 177.26 0.00 0.00 0.00
April 244.19 104.35 139.83 244.69 122.79 0.00 0.00 0.00
May 285.26 108.44 176.82 324.50 71.65 0.00 0.00 0.00
June 311.67 125.78 185.89 401.13 33.70 0.00 0.00 0.00
July 291.59 109.58 182.02 417.79 9.28 0.00 0.00 0.00
August 322.62 149.16 173.45 459.97 17.94 0.00 0.00 0.00
September 229.53 100.21 129.33 287.46 50.43 0.00 0.00 0.00
October 227.75 110.94 116.80 252.97 108.11 0.00 0.00 0.00
November 107.25 31.33 75.92 74.00 180.71 0.00 0.00 0.00
December 94.74 40.89 53.84 59.30 245.44 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 241.17 129.61 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 59.30 9.28 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 459.97 275.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 203.33 133.43 69.90 186.92 207.18 0.00 0.00 0.00
February 269.09 178.84 90.24 252.31 206.27 0.00 0.00 0.00
March 238.41 131.24 107.17 238.48 145.69 0.00 0.00 0.00
April 189.77 76.78 112.99 200.74 100.94 0.00 0.00 0.00
May 162.99 33.37 129.62 187.71 56.72 0.00 0.00 0.00
June 153.90 23.71 130.19 209.23 23.77 0.00 0.00 0.00
July 160.14 27.03 133.11 248.94 6.31 0.00 0.00 0.00
August 214.49 79.12 135.36 327.42 13.51 0.00 0.00 0.00
September 226.34 113.64 112.70 297.08 40.95 0.00 0.00 0.00
October 319.86 200.58 119.28 383.17 87.88 0.00 0.00 0.00
November 221.48 132.86 88.62 223.71 142.64 0.00 0.00 0.00
December 219.68 156.02 63.65 212.15 185.47 0.00 0.00 0.00
                 
Annual Sum or Average 214.70 106.85 107.84 247.44 100.85 0.00 0.00 0.00
Minimum of Months 153.90 23.71 63.65 186.92 6.31 0.00 0.00 0.00
Maximum of Months 319.86 200.58 135.36 383.17 207.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.70 0.00 186.70 1.63 1307.75 0.00 0.00 0.00
February 255.50 0.00 255.50 9.36 1319.39 0.00 0.00 0.00
March 354.39 0.01 354.39 86.01 879.31 0.00 0.00 0.00
April 426.48 1.76 424.73 226.57 595.95 0.00 0.00 0.00
May 567.24 20.76 546.48 494.44 321.89 0.00 0.00 0.00
June 598.43 31.83 566.60 720.68 152.94 0.00 0.00 0.00
July 580.84 22.67 558.17 825.70 66.40 0.00 0.00 0.00
August 513.65 6.82 506.83 723.51 99.99 0.00 0.00 0.00
September 386.77 0.22 386.54 400.77 250.58 0.00 0.00 0.00
October 334.44 0.00 334.44 219.11 515.53 0.00 0.00 0.00
November 234.58 0.00 234.58 42.42 901.14 0.00 0.00 0.00
December 162.86 0.00 162.86 1.53 1204.93 0.00 0.00 0.00
                 
Annual Sum or Average 384.23 7.05 377.19 314.75 630.77 0.00 0.00 0.00
Minimum of Months 162.86 0.00 162.86 1.53 66.40 0.00 0.00 0.00
Maximum of Months 598.43 31.83 566.60 825.70 1319.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.70 0.00 186.70 0.97 1346.06 0.00 0.00 0.00
February 255.50 0.00 255.50 7.61 1356.13 0.00 0.00 0.00
March 354.39 0.01 354.39 78.41 905.45 0.00 0.00 0.00
April 426.48 1.76 424.73 215.66 614.05 0.00 0.00 0.00
May 567.24 20.76 546.48 481.55 331.37 0.00 0.00 0.00
June 598.43 31.83 566.60 710.88 159.11 0.00 0.00 0.00
July 580.84 22.67 558.17 817.20 71.05 0.00 0.00 0.00
August 513.65 6.82 506.83 714.82 104.88 0.00 0.00 0.00
September 386.77 0.22 386.54 391.92 259.91 0.00 0.00 0.00
October 334.44 0.00 334.44 210.02 530.11 0.00 0.00 0.00
November 234.58 0.00 234.58 37.91 930.21 0.00 0.00 0.00
December 162.86 0.00 162.86 1.14 1240.99 0.00 0.00 0.00
                 
Annual Sum or Average 384.23 7.05 377.19 307.76 650.13 0.00 0.00 0.00
Minimum of Months 162.86 0.00 162.86 0.97 71.05 0.00 0.00 0.00
Maximum of Months 598.43 31.83 566.60 817.20 1356.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 1.02 173.88 0.00 0.00 0.00
February 36.50 0.00 36.50 2.51 175.87 0.00 0.00 0.00
March 50.63 0.00 50.63 16.30 116.22 0.00 0.00 0.00
April 60.93 0.25 60.68 42.09 79.66 0.00 0.00 0.00
May 81.04 2.97 78.07 88.28 44.57 0.00 0.00 0.00
June 85.49 4.55 80.95 124.70 22.08 0.00 0.00 0.00
July 82.98 3.24 79.74 142.11 10.25 0.00 0.00 0.00
August 73.38 0.98 72.41 125.61 14.44 0.00 0.00 0.00
September 55.25 0.03 55.22 74.45 32.39 0.00 0.00 0.00
October 47.78 0.00 47.78 41.29 66.24 0.00 0.00 0.00
November 33.51 0.00 33.51 9.35 118.13 0.00 0.00 0.00
December 23.27 0.00 23.27 0.73 158.54 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 56.06 83.84 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 0.73 10.25 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 142.11 175.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 207.51 82.91 124.60 115.99 606.56 0.00 0.00 0.00
February 322.18 150.03 172.15 209.65 588.21 0.00 0.00 0.00
March 413.73 175.83 237.90 351.95 413.81 0.00 0.00 0.00
April 495.27 217.38 277.89 514.92 286.21 0.00 0.00 0.00
May 597.93 238.28 359.65 733.63 168.05 0.00 0.00 0.00
June 555.22 201.11 354.12 789.79 83.29 0.00 0.00 0.00
July 556.92 200.50 356.42 872.78 38.61 0.00 0.00 0.00
August 628.26 283.45 344.82 960.57 53.95 0.00 0.00 0.00
September 469.97 211.72 258.25 643.47 118.41 0.00 0.00 0.00
October 424.58 192.19 232.39 494.18 238.71 0.00 0.00 0.00
November 262.97 101.05 161.91 206.36 410.19 0.00 0.00 0.00
December 205.59 97.01 108.58 129.98 545.41 0.00 0.00 0.00
                 
Annual Sum or Average 429.02 179.49 249.53 503.94 294.33 0.00 0.00 0.00
Minimum of Months 205.59 82.91 108.58 115.99 38.61 0.00 0.00 0.00
Maximum of Months 628.26 283.45 359.65 960.57 606.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 132.02 152.44 0.00 0.00 0.00
February 183.48 121.94 61.53 178.92 148.07 0.00 0.00 0.00
March 162.56 89.49 73.07 169.42 109.39 0.00 0.00 0.00
April 129.39 52.35 77.04 144.69 79.68 0.00 0.00 0.00
May 111.13 22.75 88.38 139.35 46.89 0.00 0.00 0.00
June 104.94 16.17 88.77 158.19 23.16 0.00 0.00 0.00
July 109.19 18.43 90.76 185.13 10.49 0.00 0.00 0.00
August 146.25 53.95 92.30 239.37 14.63 0.00 0.00 0.00
September 154.33 77.49 76.84 219.47 32.09 0.00 0.00 0.00
October 218.09 136.76 81.33 276.06 63.94 0.00 0.00 0.00
November 151.02 90.59 60.43 159.12 106.22 0.00 0.00 0.00
December 149.79 106.39 43.40 150.00 136.30 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 179.41 76.54 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 132.02 10.49 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 276.06 152.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 33.78 0.00 33.78 0.69 214.29 0.00 0.00 0.00
February 46.23 0.00 46.23 2.57 218.09 0.00 0.00 0.00
March 64.12 0.00 64.12 18.85 138.73 0.00 0.00 0.00
April 77.16 0.32 76.84 46.73 92.32 0.00 0.00 0.00
May 102.63 3.76 98.87 97.20 50.63 0.00 0.00 0.00
June 108.27 5.76 102.51 133.83 24.86 0.00 0.00 0.00
July 105.09 4.10 100.99 150.39 11.00 0.00 0.00 0.00
August 92.93 1.23 91.70 131.21 17.15 0.00 0.00 0.00
September 69.98 0.04 69.94 75.04 40.09 0.00 0.00 0.00
October 60.51 0.00 60.51 42.61 82.99 0.00 0.00 0.00
November 42.44 0.00 42.44 9.91 141.73 0.00 0.00 0.00
December 29.46 0.00 29.46 0.55 194.75 0.00 0.00 0.00
                 
Annual Sum or Average 69.52 1.28 68.24 59.52 101.57 0.00 0.00 0.00
Minimum of Months 29.46 0.00 29.46 0.55 11.00 0.00 0.00 0.00
Maximum of Months 108.27 5.76 102.51 150.39 218.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.22 0.00 30.22 0.62 191.72 0.00 0.00 0.00
February 41.36 0.00 41.36 2.29 195.13 0.00 0.00 0.00
March 57.37 0.00 57.37 16.86 124.12 0.00 0.00 0.00
April 69.04 0.28 68.75 41.81 82.60 0.00 0.00 0.00
May 91.82 3.36 88.46 86.96 45.30 0.00 0.00 0.00
June 96.87 5.15 91.72 119.74 22.24 0.00 0.00 0.00
July 94.02 3.67 90.35 134.56 9.84 0.00 0.00 0.00
August 83.15 1.10 82.04 117.39 15.35 0.00 0.00 0.00
September 62.61 0.04 62.57 67.14 35.87 0.00 0.00 0.00
October 54.14 0.00 54.14 38.12 74.25 0.00 0.00 0.00
November 37.97 0.00 37.97 8.86 126.80 0.00 0.00 0.00
December 26.36 0.00 26.36 0.49 174.22 0.00 0.00 0.00
                 
Annual Sum or Average 62.20 1.14 61.06 53.25 90.87 0.00 0.00 0.00
Minimum of Months 26.36 0.00 26.36 0.49 9.84 0.00 0.00 0.00
Maximum of Months 96.87 5.15 91.72 134.56 195.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 517.59 339.65 177.94 483.05 549.27 0.00 0.00 0.00
February 684.98 455.25 229.72 655.23 538.63 0.00 0.00 0.00
March 606.89 334.08 272.80 616.73 383.94 0.00 0.00 0.00
April 483.07 195.44 287.63 515.42 273.26 0.00 0.00 0.00
May 414.90 84.94 329.95 476.39 160.49 0.00 0.00 0.00
June 391.77 60.36 331.40 521.26 78.09 0.00 0.00 0.00
July 407.63 68.80 338.83 604.74 33.26 0.00 0.00 0.00
August 545.99 201.41 344.58 808.24 52.16 0.00 0.00 0.00
September 576.16 289.28 286.88 756.63 117.07 0.00 0.00 0.00
October 814.21 510.58 303.63 988.77 231.90 0.00 0.00 0.00
November 563.79 338.20 225.59 578.92 374.65 0.00 0.00 0.00
December 559.20 397.17 162.03 549.77 489.57 0.00 0.00 0.00
                 
Annual Sum or Average 546.52 272.00 274.52 629.78 272.03 0.00 0.00 0.00
Minimum of Months 391.77 60.36 162.03 476.39 33.26 0.00 0.00 0.00
Maximum of Months 814.21 510.58 344.58 988.77 549.27 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.187811E+10 0.123244E+10 0.645669E+09 0.178050E+10 0.182202E+10
February 0.224496E+10 0.149206E+10 0.752897E+09 0.216947E+10 0.162918E+10
March 0.220215E+10 0.121226E+10 0.989890E+09 0.225870E+10 0.128621E+10
April 0.169631E+10 0.686285E+09 0.101002E+10 0.183477E+10 0.878822E+09
May 0.150549E+10 0.308226E+09 0.119726E+10 0.177246E+10 0.517534E+09
June 0.137569E+10 0.211965E+09 0.116373E+10 0.186112E+10 0.240285E+09
July 0.147913E+10 0.249647E+09 0.122948E+10 0.220219E+10 0.107350E+09
August 0.198115E+10 0.730828E+09 0.125032E+10 0.291472E+10 0.187407E+09
September 0.202321E+10 0.101583E+10 0.100738E+10 0.265707E+10 0.383847E+09
October 0.295444E+10 0.185269E+10 0.110176E+10 0.357080E+10 0.814268E+09
November 0.197976E+10 0.118761E+10 0.792159E+09 0.204162E+10 0.122414E+10
December 0.202909E+10 0.144117E+10 0.587926E+09 0.200623E+10 0.163926E+10
           
Annual Sum or Average 0.233495E+11 0.116210E+11 0.117285E+11 0.270697E+11 0.107303E+11
Minimum of Months 0.137569E+10 0.211965E+09 0.587926E+09 0.177246E+10 0.107350E+09
Maximum of Months 0.295444E+10 0.185269E+10 0.125032E+10 0.357080E+10 0.182202E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.528864E+10 0.347048E+10 0.181816E+10 0.495224E+10 0.529726E+10
February 0.632166E+10 0.420155E+10 0.212011E+10 0.603254E+10 0.474338E+10
March 0.620110E+10 0.341363E+10 0.278747E+10 0.627300E+10 0.386065E+10
April 0.477669E+10 0.193253E+10 0.284415E+10 0.507037E+10 0.270583E+10
May 0.423935E+10 0.867945E+09 0.337140E+10 0.485753E+10 0.166276E+10
June 0.387386E+10 0.596881E+09 0.327698E+10 0.514424E+10 0.799190E+09
July 0.416513E+10 0.702990E+09 0.346214E+10 0.612183E+10 0.376612E+09
August 0.557879E+10 0.205796E+10 0.352082E+10 0.813947E+10 0.595454E+09
September 0.569723E+10 0.286050E+10 0.283673E+10 0.739290E+10 0.124603E+10
October 0.831952E+10 0.521704E+10 0.310247E+10 0.995184E+10 0.252400E+10
November 0.557489E+10 0.334422E+10 0.223067E+10 0.565493E+10 0.367931E+10
December 0.571380E+10 0.405823E+10 0.165556E+10 0.557862E+10 0.481840E+10
           
Annual Sum or Average 0.657506E+11 0.327240E+11 0.330267E+11 0.751695E+11 0.323089E+11
Minimum of Months 0.387386E+10 0.596881E+09 0.165556E+10 0.485753E+10 0.376612E+09
Maximum of Months 0.831952E+10 0.521704E+10 0.352082E+10 0.995184E+10 0.529726E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.687025E+10 0.450835E+10 0.236190E+10 0.654728E+10 0.722050E+10
February 0.821220E+10 0.545806E+10 0.275414E+10 0.800043E+10 0.641383E+10
March 0.805558E+10 0.443450E+10 0.362108E+10 0.832058E+10 0.523996E+10
April 0.620519E+10 0.251047E+10 0.369472E+10 0.671838E+10 0.370030E+10
May 0.550715E+10 0.112751E+10 0.437965E+10 0.643084E+10 0.227863E+10
June 0.503236E+10 0.775382E+09 0.425698E+10 0.683315E+10 0.106990E+10
July 0.541074E+10 0.913224E+09 0.449752E+10 0.815848E+10 0.487365E+09
August 0.724716E+10 0.267341E+10 0.457375E+10 0.108379E+11 0.760740E+09
September 0.740102E+10 0.371595E+10 0.368507E+10 0.979956E+10 0.165592E+10
October 0.108075E+11 0.677724E+10 0.403029E+10 0.131942E+11 0.334885E+10
November 0.724209E+10 0.434433E+10 0.289776E+10 0.747131E+10 0.502561E+10
December 0.742255E+10 0.527188E+10 0.215067E+10 0.737242E+10 0.657209E+10
           
Annual Sum or Average 0.854138E+11 0.425103E+11 0.429035E+11 0.996846E+11 0.437737E+11
Minimum of Months 0.503236E+10 0.775382E+09 0.215067E+10 0.643084E+10 0.487365E+09
Maximum of Months 0.108075E+11 0.677724E+10 0.457375E+10 0.131942E+11 0.722050E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.354630E+09 0.365668E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.431971E+09 0.327860E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.447043E+09 0.259288E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.361050E+09 0.177284E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.343084E+09 0.107055E+09
June 0.272000E+09 41909203.44 0.230091E+09 0.364186E+09 48332266.82
July 0.292452E+09 49359538.74 0.243092E+09 0.450030E+09 14033215.01
August 0.391710E+09 0.144497E+09 0.247212E+09 0.595241E+09 27664883.20
September 0.400025E+09 0.200846E+09 0.199179E+09 0.528928E+09 73426804.22
October 0.584146E+09 0.366308E+09 0.217837E+09 0.710413E+09 0.157519E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.408414E+09 0.241364E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.401465E+09 0.326033E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.539645E+10 0.212553E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.343084E+09 14033215.01
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.710413E+09 0.365668E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.158277E+09 0.739520E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.235351E+09 0.675621E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.516883E+09 0.483387E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.631064E+09 0.322842E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.875477E+09 0.191782E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.104848E+10 85924331.67
July 0.781005E+09 0.293491E+09 0.487514E+09 0.112375E+10 25592364.85
August 0.864094E+09 0.399519E+09 0.464575E+09 0.123107E+10 51032383.00
September 0.594954E+09 0.259739E+09 0.335215E+09 0.740537E+09 0.136172E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.664239E+09 0.301940E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.180385E+09 0.480845E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.148989E+09 0.669867E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.755451E+10 0.416453E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.148989E+09 25592364.85
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.123107E+10 0.739520E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 4172814.58 0.410764E+09
February 88303223.66 0.00 88303223.66 8094039.41 0.379792E+09
March 0.135606E+09 2824.51 0.135604E+09 47428722.36 0.271540E+09
April 0.157926E+09 650731.43 0.157276E+09 0.100439E+09 0.174545E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.207019E+09 98492573.66
June 0.221597E+09 11786401.62 0.209811E+09 0.275194E+09 44531921.13
July 0.222253E+09 8673946.39 0.213579E+09 0.333972E+09 13441059.02
August 0.196546E+09 2611506.30 0.193935E+09 0.293830E+09 26011025.94
September 0.143220E+09 83260.91 0.143137E+09 0.159533E+09 71582902.58
October 0.127973E+09 0.00 0.127973E+09 96942793.21 0.161254E+09
November 86865075.47 0.00 86865075.47 26199358.22 0.261043E+09
December 62315669.45 0.00 62315669.45 2878047.00 0.370276E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.155570E+10 0.228327E+10
Minimum of Months 62315669.45 0.00 62315669.45 2878047.00 13441059.02
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.333972E+09 0.410764E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.166709E+09 0.731891E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.246734E+09 0.665107E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.531488E+09 0.476205E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.640473E+09 0.319361E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.879793E+09 0.190566E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.105053E+10 85218238.50
July 0.781005E+09 0.293491E+09 0.487514E+09 0.112626E+10 25157621.61
August 0.864094E+09 0.399519E+09 0.464575E+09 0.123778E+10 49411802.38
September 0.594954E+09 0.259739E+09 0.335215E+09 0.750471E+09 0.131209E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.681506E+09 0.292561E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.191821E+09 0.472249E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.158937E+09 0.660138E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.766250E+10 0.409907E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.158937E+09 25157621.61
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.123778E+10 0.731891E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.297010E+09 0.194901E+09 0.102108E+09 0.282259E+09 0.285735E+09
February 0.355024E+09 0.235958E+09 0.119066E+09 0.340588E+09 0.267162E+09
March 0.348254E+09 0.191709E+09 0.156545E+09 0.353515E+09 0.218494E+09
April 0.268259E+09 0.108531E+09 0.159729E+09 0.285786E+09 0.151951E+09
May 0.238083E+09 48743591.57 0.189339E+09 0.272033E+09 95010871.68
June 0.217557E+09 33520696.39 0.184036E+09 0.294444E+09 41244920.82
July 0.233915E+09 39479779.53 0.194435E+09 0.355594E+09 15904674.82
August 0.313305E+09 0.115575E+09 0.197731E+09 0.471693E+09 27407166.78
September 0.319956E+09 0.160645E+09 0.159311E+09 0.421185E+09 66392107.54
October 0.467223E+09 0.292988E+09 0.174235E+09 0.562387E+09 0.142879E+09
November 0.313085E+09 0.187811E+09 0.125275E+09 0.318694E+09 0.207472E+09
December 0.320886E+09 0.227910E+09 92976446.14 0.316279E+09 0.264265E+09
           
Annual Sum or Average 0.369256E+10 0.183777E+10 0.185479E+10 0.427446E+10 0.178392E+10
Minimum of Months 0.217557E+09 33520696.39 92976446.14 0.272033E+09 15904674.82
Maximum of Months 0.467223E+09 0.292988E+09 0.197731E+09 0.562387E+09 0.285735E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 57160472.40 0.00 57160472.40 2444534.02 0.342977E+09
February 70651943.00 0.00 70651943.00 5807046.51 0.314084E+09
March 0.108500E+09 2259.91 0.108497E+09 38367794.57 0.221485E+09
April 0.126358E+09 520654.15 0.125837E+09 84699764.48 0.140264E+09
May 0.173664E+09 6355606.08 0.167308E+09 0.176799E+09 75812948.57
June 0.177301E+09 9430371.18 0.167871E+09 0.236063E+09 29763368.15
July 0.177826E+09 6940076.94 0.170886E+09 0.282140E+09 7755595.40
August 0.157258E+09 2089481.97 0.155168E+09 0.251415E+09 16726499.57
September 0.114591E+09 66617.56 0.114525E+09 0.137931E+09 51230740.21
October 0.102392E+09 0.00 0.102392E+09 84163870.22 0.123587E+09
November 69501271.94 0.00 69501271.94 20188180.22 0.217984E+09
December 49859143.80 0.00 49859143.80 1774174.98 0.310164E+09
           
Annual Sum or Average 0.138506E+10 25405067.78 0.135966E+10 0.132179E+10 0.185183E+10
Minimum of Months 49859143.80 0.00 49859143.80 1774174.98 7755595.40
Maximum of Months 0.177826E+09 9430371.18 0.170886E+09 0.282140E+09 0.342977E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.277917E+09 0.111036E+09 0.166880E+09 0.154221E+09 0.726155E+09
February 0.389732E+09 0.181489E+09 0.208243E+09 0.250754E+09 0.650622E+09
March 0.554101E+09 0.235489E+09 0.318612E+09 0.459858E+09 0.484842E+09
April 0.641909E+09 0.281741E+09 0.360168E+09 0.637063E+09 0.312263E+09
May 0.800805E+09 0.319132E+09 0.481673E+09 0.923000E+09 0.184833E+09
June 0.719622E+09 0.260655E+09 0.458966E+09 0.936091E+09 79623396.24
July 0.745874E+09 0.268526E+09 0.477348E+09 0.107783E+10 24180952.68
August 0.841430E+09 0.379618E+09 0.461812E+09 0.119548E+10 47564785.21
September 0.609123E+09 0.274405E+09 0.334718E+09 0.756220E+09 0.129024E+09
October 0.568633E+09 0.257394E+09 0.311239E+09 0.611243E+09 0.291982E+09
November 0.340829E+09 0.130973E+09 0.209856E+09 0.257560E+09 0.467674E+09
December 0.275346E+09 0.129921E+09 0.145425E+09 0.170913E+09 0.652918E+09
           
Annual Sum or Average 0.676532E+10 0.283038E+10 0.393494E+10 0.743023E+10 0.405168E+10
Minimum of Months 0.275346E+09 0.111036E+09 0.145425E+09 0.154221E+09 24180952.68
Maximum of Months 0.841430E+09 0.379618E+09 0.481673E+09 0.119548E+10 0.726155E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.353816E+09 0.365073E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.430125E+09 0.326975E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.444556E+09 0.256568E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.358410E+09 0.175054E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.340199E+09 0.103881E+09
June 0.272000E+09 41909203.44 0.230091E+09 0.364491E+09 43992679.43
July 0.292452E+09 49359538.74 0.243092E+09 0.448448E+09 13043026.16
August 0.391710E+09 0.144497E+09 0.247212E+09 0.592504E+09 26404949.79
September 0.400025E+09 0.200846E+09 0.199179E+09 0.526845E+09 70751459.17
October 0.584146E+09 0.366308E+09 0.217837E+09 0.709330E+09 0.154123E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.406157E+09 0.241574E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.400281E+09 0.325568E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.537516E+10 0.210301E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.340199E+09 13043026.16
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.709330E+09 0.365073E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 3707216.41 0.410672E+09
February 88303223.66 0.00 88303223.66 7515135.39 0.379756E+09
March 0.135606E+09 2824.51 0.135604E+09 45300790.17 0.269046E+09
April 0.157926E+09 650731.43 0.157276E+09 97697571.32 0.172914E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.204433E+09 96264464.68
June 0.221597E+09 11786401.62 0.209811E+09 0.276225E+09 41198701.47
July 0.222253E+09 8673946.39 0.213579E+09 0.332387E+09 12587664.15
August 0.196546E+09 2611506.30 0.193935E+09 0.290915E+09 24825912.64
September 0.143220E+09 83260.91 0.143137E+09 0.156857E+09 69159560.28
October 0.127973E+09 0.00 0.127973E+09 94597682.33 0.157057E+09
November 86865075.47 0.00 86865075.47 24664554.13 0.261689E+09
December 62315669.45 0.00 62315669.45 2477123.75 0.370223E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.153678E+10 0.226539E+10
Minimum of Months 62315669.45 0.00 62315669.45 2477123.75 12587664.15
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.332387E+09 0.410672E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.277917E+09 0.111036E+09 0.166880E+09 0.159415E+09 0.715467E+09
February 0.389732E+09 0.181489E+09 0.208243E+09 0.258493E+09 0.636002E+09
March 0.554101E+09 0.235489E+09 0.318612E+09 0.472786E+09 0.475622E+09
April 0.641909E+09 0.281741E+09 0.360168E+09 0.645088E+09 0.308460E+09
May 0.800805E+09 0.319132E+09 0.481673E+09 0.926414E+09 0.183694E+09
June 0.719622E+09 0.260655E+09 0.458966E+09 0.938061E+09 79118223.48
July 0.745874E+09 0.268526E+09 0.477348E+09 0.108034E+10 23785259.45
August 0.841430E+09 0.379618E+09 0.461812E+09 0.120208E+10 45992456.99
September 0.609123E+09 0.274405E+09 0.334718E+09 0.764943E+09 0.124188E+09
October 0.568633E+09 0.257394E+09 0.311239E+09 0.626613E+09 0.281217E+09
November 0.340829E+09 0.130973E+09 0.209856E+09 0.267303E+09 0.457315E+09
December 0.275346E+09 0.129921E+09 0.145425E+09 0.176432E+09 0.638424E+09
           
Annual Sum or Average 0.676532E+10 0.283038E+10 0.393494E+10 0.751797E+10 0.396928E+10
Minimum of Months 0.275346E+09 0.111036E+09 0.145425E+09 0.159415E+09 23785259.45
Maximum of Months 0.841430E+09 0.379618E+09 0.481673E+09 0.120208E+10 0.715467E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 90475671.53 0.00 90475671.53 2713202.24 0.561405E+09
February 0.111830E+09 0.00 0.111830E+09 7678952.96 0.515333E+09
March 0.171737E+09 3577.06 0.171733E+09 57027709.71 0.361001E+09
April 0.200004E+09 824110.29 0.199180E+09 0.130428E+09 0.232635E+09
May 0.274881E+09 10059884.11 0.264822E+09 0.273726E+09 0.130967E+09
June 0.280639E+09 14926733.97 0.265712E+09 0.358909E+09 61684428.49
July 0.281470E+09 10985005.81 0.270485E+09 0.418617E+09 24843859.13
August 0.248914E+09 3307307.95 0.245606E+09 0.364662E+09 43017094.94
September 0.181379E+09 105444.69 0.181274E+09 0.202747E+09 0.101650E+09
October 0.162070E+09 0.00 0.162070E+09 0.120768E+09 0.222046E+09
November 0.110009E+09 0.00 0.110009E+09 29140798.91 0.358325E+09
December 78918863.46 0.00 78918863.46 2054006.51 0.508706E+09
           
Annual Sum or Average 0.219233E+10 40212063.88 0.215212E+10 0.196847E+10 0.312161E+10
Minimum of Months 78918863.46 0.00 78918863.46 2054006.51 24843859.13
Maximum of Months 0.281470E+09 14926733.97 0.270485E+09 0.418617E+09 0.561405E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33353078.83 0.00 33353078.83 1000198.69 0.206957E+09
February 41225338.51 0.00 41225338.51 2830780.02 0.189973E+09
March 63309370.74 1318.65 63308052.09 21022775.13 0.133080E+09
April 73729728.02 303801.18 73425926.85 48081303.04 85758842.40
May 0.101333E+09 3708489.83 97624177.01 0.100907E+09 48279912.24
June 0.103455E+09 5502612.21 97952429.60 0.132309E+09 22739434.49
July 0.103761E+09 4049527.99 99711821.83 0.154320E+09 9158475.18
August 91759824.79 1219210.65 90540614.14 0.134430E+09 15857882.39
September 66863956.86 38871.28 66825085.58 74740920.58 37472566.72
October 59745607.08 0.00 59745607.08 44520105.63 81855281.70
November 40553923.09 0.00 40553923.09 10742505.10 0.132093E+09
December 29092760.85 0.00 29092760.85 757191.85 0.187530E+09
           
Annual Sum or Average 0.808183E+09 14823831.80 0.793359E+09 0.725660E+09 0.115076E+10
Minimum of Months 29092760.85 0.00 29092760.85 757191.85 9158475.18
Maximum of Months 0.103761E+09 5502612.21 99711821.83 0.154320E+09 0.206957E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.173264E+09 0.113698E+09 59565921.67 0.164375E+09 0.180485E+09
February 0.207107E+09 0.137649E+09 69458271.60 0.201317E+09 0.160092E+09
March 0.203158E+09 0.111836E+09 91322098.46 0.210758E+09 0.125073E+09
April 0.156492E+09 63312522.45 93179403.01 0.171571E+09 85818531.16
May 0.138888E+09 28435108.11 0.110453E+09 0.164850E+09 51650558.92
June 0.126914E+09 19554665.45 0.107360E+09 0.173825E+09 24093243.38
July 0.136457E+09 23030961.87 0.113426E+09 0.208840E+09 9368062.86
August 0.182770E+09 67421861.27 0.115348E+09 0.276422E+09 16317501.35
September 0.186650E+09 93714060.14 92935999.63 0.249214E+09 37028339.89
October 0.272560E+09 0.170918E+09 0.101642E+09 0.335234E+09 77499063.88
November 0.182642E+09 0.109561E+09 73080255.50 0.190662E+09 0.118800E+09
December 0.187192E+09 0.132954E+09 54238828.37 0.186887E+09 0.160635E+09
           
Annual Sum or Average 0.215409E+10 0.107208E+10 0.108201E+10 0.253396E+10 0.104686E+10
Minimum of Months 0.126914E+09 19554665.45 54238828.37 0.164375E+09 9368062.86
Maximum of Months 0.272560E+09 0.170918E+09 0.115348E+09 0.335234E+09 0.180485E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.470274E+09 0.308599E+09 0.161674E+09 0.446149E+09 0.489874E+09
February 0.562131E+09 0.373607E+09 0.188524E+09 0.546416E+09 0.434521E+09
March 0.551411E+09 0.303545E+09 0.247867E+09 0.572041E+09 0.339472E+09
April 0.424751E+09 0.171843E+09 0.252908E+09 0.465678E+09 0.232929E+09
May 0.376971E+09 77178699.67 0.299792E+09 0.447436E+09 0.140190E+09
June 0.344471E+09 53075361.84 0.291396E+09 0.471795E+09 65393990.70
July 0.370372E+09 62510741.40 0.307861E+09 0.566835E+09 25426838.80
August 0.496076E+09 0.182997E+09 0.313079E+09 0.750265E+09 44289036.32
September 0.506606E+09 0.254359E+09 0.252247E+09 0.676418E+09 0.100502E+09
October 0.739783E+09 0.463906E+09 0.275877E+09 0.909895E+09 0.210348E+09
November 0.495727E+09 0.297372E+09 0.198355E+09 0.517496E+09 0.322446E+09
December 0.508078E+09 0.360863E+09 0.147215E+09 0.507249E+09 0.435996E+09
           
Annual Sum or Average 0.584665E+10 0.290986E+10 0.293680E+10 0.687767E+10 0.284139E+10
Minimum of Months 0.344471E+09 53075361.84 0.147215E+09 0.446149E+09 25426838.80
Maximum of Months 0.739783E+09 0.463906E+09 0.313079E+09 0.909895E+09 0.489874E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.353078E+09 0.364590E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.429846E+09 0.327293E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.443640E+09 0.259217E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.357373E+09 0.177470E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.338152E+09 0.108462E+09
June 0.272000E+09 41909203.44 0.230091E+09 0.359863E+09 49900981.58
July 0.292452E+09 49359538.74 0.243092E+09 0.446793E+09 13930684.40
August 0.391710E+09 0.144497E+09 0.247212E+09 0.591804E+09 27059404.23
September 0.400025E+09 0.200846E+09 0.199179E+09 0.525069E+09 74047013.41
October 0.584146E+09 0.366308E+09 0.217837E+09 0.705716E+09 0.157431E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.406928E+09 0.239508E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.400194E+09 0.324397E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.535846E+10 0.212330E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.338152E+09 13930684.40
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.705716E+09 0.364590E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.157402E+09 0.738056E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.232972E+09 0.675578E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.511616E+09 0.482364E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.624192E+09 0.322093E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.864836E+09 0.193086E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.103770E+10 87874266.10
July 0.781005E+09 0.293491E+09 0.487514E+09 0.111644E+10 25286406.63
August 0.864094E+09 0.399519E+09 0.464575E+09 0.122495E+10 49827971.42
September 0.594954E+09 0.259739E+09 0.335215E+09 0.734443E+09 0.136693E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.658160E+09 0.301188E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.179419E+09 0.477516E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.148293E+09 0.666933E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.749042E+10 0.415650E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.148293E+09 25286406.63
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.122495E+10 0.738056E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 4297012.51 0.410005E+09
February 88303223.66 0.00 88303223.66 8178298.73 0.380056E+09
March 0.135606E+09 2824.51 0.135604E+09 47122745.00 0.271272E+09
April 0.157926E+09 650731.43 0.157276E+09 99188426.30 0.174262E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.202898E+09 99517511.83
June 0.221597E+09 11786401.62 0.209811E+09 0.271639E+09 45789011.74
July 0.222253E+09 8673946.39 0.213579E+09 0.331752E+09 13384362.28
August 0.196546E+09 2611506.30 0.193935E+09 0.292780E+09 25398840.23
September 0.143220E+09 83260.91 0.143137E+09 0.158347E+09 71724128.90
October 0.127973E+09 0.00 0.127973E+09 96918057.02 0.159907E+09
November 86865075.47 0.00 86865075.47 26636013.63 0.258662E+09
December 62315669.45 0.00 62315669.45 3070131.89 0.368292E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.154283E+10 0.227827E+10
Minimum of Months 62315669.45 0.00 62315669.45 3070131.89 13384362.28
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.331752E+09 0.410005E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.165946E+09 0.730739E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.244856E+09 0.665347E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.527415E+09 0.474766E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.634236E+09 0.318265E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.869130E+09 0.191898E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.103974E+10 87343644.84
July 0.781005E+09 0.293491E+09 0.487514E+09 0.111901E+10 24867334.37
August 0.864094E+09 0.399519E+09 0.464575E+09 0.123197E+10 48057695.12
September 0.594954E+09 0.259739E+09 0.335215E+09 0.745089E+09 0.130708E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.677566E+09 0.289559E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.191798E+09 0.468399E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.158842E+09 0.657391E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.760560E+10 0.408734E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.158842E+09 24867334.37
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.123197E+10 0.730739E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544600E+09 0.357373E+09 0.187227E+09 0.500643E+09 0.554920E+09
February 0.650976E+09 0.432656E+09 0.218320E+09 0.610392E+09 0.499016E+09
March 0.638561E+09 0.351519E+09 0.287042E+09 0.638751E+09 0.390205E+09
April 0.491883E+09 0.199003E+09 0.292880E+09 0.520328E+09 0.261641E+09
May 0.436551E+09 89376714.80 0.347174E+09 0.502755E+09 0.151922E+09
June 0.398915E+09 61463868.89 0.337451E+09 0.542328E+09 61607783.17
July 0.428908E+09 72390500.62 0.356518E+09 0.666763E+09 16897386.09
August 0.574480E+09 0.211919E+09 0.362561E+09 0.876964E+09 36186667.85
September 0.586675E+09 0.294560E+09 0.292115E+09 0.770043E+09 0.106141E+09
October 0.856705E+09 0.537226E+09 0.319480E+09 0.102629E+10 0.235379E+09
November 0.574076E+09 0.344371E+09 0.229705E+09 0.579844E+09 0.369720E+09
December 0.588380E+09 0.417897E+09 0.170482E+09 0.568214E+09 0.496750E+09
           
Annual Sum or Average 0.677071E+10 0.336976E+10 0.340095E+10 0.780331E+10 0.318038E+10
Minimum of Months 0.398915E+09 61463868.89 0.170482E+09 0.500643E+09 16897386.09
Maximum of Months 0.856705E+09 0.537226E+09 0.362561E+09 0.102629E+10 0.554920E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.500069E+09 0.00 0.500069E+09 4354753.64 0.350269E+10
February 0.618099E+09 0.00 0.618099E+09 22640451.88 0.319186E+10
March 0.949209E+09 19770.80 0.949189E+09 0.230363E+09 0.235515E+10
April 0.110544E+10 4554947.47 0.110089E+10 0.587282E+09 0.154470E+10
May 0.151930E+10 55602076.65 0.146370E+10 0.132432E+10 0.862157E+09
June 0.155112E+10 82501686.62 0.146862E+10 0.186801E+10 0.396408E+09
July 0.155571E+10 60715325.16 0.149500E+10 0.221157E+10 0.177850E+09
August 0.137577E+10 18279851.73 0.135749E+10 0.193785E+10 0.267824E+09
September 0.100250E+10 582804.32 0.100192E+10 0.103878E+10 0.649504E+09
October 0.895777E+09 0.00 0.895777E+09 0.586865E+09 0.138080E+10
November 0.608032E+09 0.00 0.608032E+09 0.109942E+09 0.233575E+10
December 0.436193E+09 0.00 0.436193E+09 4110199.06 0.322727E+10
           
Annual Sum or Average 0.121172E+11 0.222256E+09 0.118950E+11 0.992609E+10 0.198920E+11
Minimum of Months 0.436193E+09 0.00 0.436193E+09 4110199.06 0.177850E+09
Maximum of Months 0.155571E+10 82501686.62 0.149500E+10 0.221157E+10 0.350269E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.500069E+09 0.00 0.500069E+09 2585893.16 0.360528E+10
February 0.618099E+09 0.00 0.618099E+09 18408818.65 0.328074E+10
March 0.949209E+09 19770.80 0.949189E+09 0.210012E+09 0.242516E+10
April 0.110544E+10 4554947.47 0.110089E+10 0.559003E+09 0.159161E+10
May 0.151930E+10 55602076.65 0.146370E+10 0.128979E+10 0.887528E+09
June 0.155112E+10 82501686.62 0.146862E+10 0.184259E+10 0.412414E+09
July 0.155571E+10 60715325.16 0.149500E+10 0.218878E+10 0.190303E+09
August 0.137577E+10 18279851.73 0.135749E+10 0.191457E+10 0.280916E+09
September 0.100250E+10 582804.32 0.100192E+10 0.101587E+10 0.673698E+09
October 0.895777E+09 0.00 0.895777E+09 0.562523E+09 0.141986E+10
November 0.608032E+09 0.00 0.608032E+09 98266663.64 0.241110E+10
December 0.436193E+09 0.00 0.436193E+09 3065637.18 0.332388E+10
           
Annual Sum or Average 0.121172E+11 0.222256E+09 0.118950E+11 0.970547E+10 0.205025E+11
Minimum of Months 0.436193E+09 0.00 0.436193E+09 2585893.16 0.190303E+09
Maximum of Months 0.155571E+10 82501686.62 0.149500E+10 0.218878E+10 0.360528E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 2728901.48 0.465707E+09
February 88303223.66 0.00 88303223.66 6071007.86 0.425463E+09
March 0.135606E+09 2824.51 0.135604E+09 43660763.08 0.311294E+09
April 0.157926E+09 650731.43 0.157276E+09 0.109093E+09 0.206469E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.236452E+09 0.119382E+09
June 0.221597E+09 11786401.62 0.209811E+09 0.323224E+09 57240022.36
July 0.222253E+09 8673946.39 0.213579E+09 0.380618E+09 27451949.01
August 0.196546E+09 2611506.30 0.193935E+09 0.336427E+09 38689479.90
September 0.143220E+09 83260.91 0.143137E+09 0.192980E+09 83964891.65
October 0.127973E+09 0.00 0.127973E+09 0.110599E+09 0.177419E+09
November 86865075.47 0.00 86865075.47 24225675.41 0.306204E+09
December 62315669.45 0.00 62315669.45 1947348.89 0.424645E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.176803E+10 0.264393E+10
Minimum of Months 62315669.45 0.00 62315669.45 1947348.89 27451949.01
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.380618E+09 0.465707E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555794E+09 0.222057E+09 0.333737E+09 0.310677E+09 0.162461E+10
February 0.779409E+09 0.362953E+09 0.416456E+09 0.507195E+09 0.142299E+10
March 0.110812E+10 0.470944E+09 0.637179E+09 0.942668E+09 0.110835E+10
April 0.128373E+10 0.563442E+09 0.720285E+09 0.133468E+10 0.741858E+09
May 0.160150E+10 0.638219E+09 0.963277E+09 0.196495E+10 0.450113E+09
June 0.143914E+10 0.521274E+09 0.917867E+09 0.204714E+10 0.215891E+09
July 0.149164E+10 0.537013E+09 0.954629E+09 0.233765E+10 0.103413E+09
August 0.168274E+10 0.759182E+09 0.923559E+09 0.257279E+10 0.144497E+09
September 0.121816E+10 0.548771E+09 0.669389E+09 0.166787E+10 0.306913E+09
October 0.113718E+10 0.514751E+09 0.622434E+09 0.132362E+10 0.639353E+09
November 0.681609E+09 0.261927E+09 0.419682E+09 0.534886E+09 0.106322E+10
December 0.550653E+09 0.259823E+09 0.290830E+09 0.348144E+09 0.146082E+10
           
Annual Sum or Average 0.135297E+11 0.566036E+10 0.786932E+10 0.158923E+11 0.928203E+10
Minimum of Months 0.550653E+09 0.222057E+09 0.290830E+09 0.310677E+09 0.103413E+09
Maximum of Months 0.168274E+10 0.759182E+09 0.963277E+09 0.257279E+10 0.162461E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.353610E+09 0.408300E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.432837E+09 0.358200E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.453767E+09 0.292995E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.375024E+09 0.206526E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.373235E+09 0.125598E+09
June 0.272000E+09 41909203.44 0.230091E+09 0.410039E+09 60025713.41
July 0.292452E+09 49359538.74 0.243092E+09 0.495845E+09 28109756.17
August 0.391710E+09 0.144497E+09 0.247212E+09 0.641115E+09 39184369.89
September 0.400025E+09 0.200846E+09 0.199179E+09 0.568857E+09 83174520.27
October 0.584146E+09 0.366308E+09 0.217837E+09 0.739407E+09 0.171270E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.412441E+09 0.275330E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.401757E+09 0.365065E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.565793E+10 0.241378E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.353610E+09 28109756.17
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.739407E+09 0.408300E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 90475671.53 0.00 90475671.53 1853836.53 0.573964E+09
February 0.111830E+09 0.00 0.111830E+09 6205316.33 0.527613E+09
March 0.171737E+09 3577.06 0.171733E+09 50479229.65 0.371572E+09
April 0.200004E+09 824110.29 0.199180E+09 0.121114E+09 0.239286E+09
May 0.274881E+09 10059884.11 0.264822E+09 0.260329E+09 0.135616E+09
June 0.280639E+09 14926733.97 0.265712E+09 0.346880E+09 64443359.80
July 0.281470E+09 10985005.81 0.270485E+09 0.402815E+09 29469480.04
August 0.248914E+09 3307307.95 0.245606E+09 0.351433E+09 45938533.98
September 0.181379E+09 105444.69 0.181274E+09 0.194515E+09 0.103905E+09
October 0.162070E+09 0.00 0.162070E+09 0.114124E+09 0.222285E+09
November 0.110009E+09 0.00 0.110009E+09 25681056.13 0.367353E+09
December 78918863.46 0.00 78918863.46 1466580.33 0.521627E+09
           
Annual Sum or Average 0.219233E+10 40212063.88 0.215212E+10 0.187689E+10 0.320307E+10
Minimum of Months 78918863.46 0.00 78918863.46 1466580.33 29469480.04
Maximum of Months 0.281470E+09 14926733.97 0.270485E+09 0.402815E+09 0.573964E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80948926.13 0.00 80948926.13 1658634.57 0.513505E+09
February 0.100055E+09 0.00 0.100055E+09 5551920.03 0.472058E+09
March 0.153654E+09 3200.41 0.153651E+09 45163958.03 0.332447E+09
April 0.178944E+09 737334.60 0.178207E+09 0.108361E+09 0.214091E+09
May 0.245937E+09 9000616.43 0.236937E+09 0.232917E+09 0.121336E+09
June 0.251089E+09 13355005.44 0.237733E+09 0.310355E+09 57657718.19
July 0.251832E+09 9828326.32 0.242004E+09 0.360400E+09 26366455.45
August 0.222704E+09 2959060.95 0.219745E+09 0.314428E+09 41101380.41
September 0.162281E+09 94341.77 0.162186E+09 0.174033E+09 92963872.86
October 0.145004E+09 0.00 0.145004E+09 0.102107E+09 0.198879E+09
November 98425591.88 0.00 98425591.88 22976938.23 0.328668E+09
December 70609006.16 0.00 70609006.16 1312154.98 0.466636E+09
           
Annual Sum or Average 0.196148E+10 35977885.91 0.192551E+10 0.167926E+10 0.286571E+10
Minimum of Months 70609006.16 0.00 70609006.16 1312154.98 26366455.45
Maximum of Months 0.251832E+09 13355005.44 0.242004E+09 0.360400E+09 0.513505E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138631E+10 0.909713E+09 0.476595E+09 0.129379E+10 0.147116E+10
February 0.165709E+10 0.110135E+10 0.555745E+09 0.158514E+10 0.130305E+10
March 0.162549E+10 0.894811E+09 0.730681E+09 0.165184E+10 0.102835E+10
April 0.125211E+10 0.506572E+09 0.745541E+09 0.133596E+10 0.708283E+09
May 0.111126E+10 0.227513E+09 0.883750E+09 0.127596E+10 0.429850E+09
June 0.101546E+10 0.156460E+09 0.858999E+09 0.135111E+10 0.202410E+09
July 0.109181E+10 0.184274E+09 0.907535E+09 0.161972E+10 89074224.50
August 0.146237E+10 0.539452E+09 0.922918E+09 0.216479E+10 0.139717E+09
September 0.149341E+10 0.749819E+09 0.743594E+09 0.196119E+10 0.303435E+09
October 0.218079E+10 0.136754E+10 0.813252E+09 0.264831E+10 0.621123E+09
November 0.146134E+10 0.876615E+09 0.584725E+09 0.150057E+10 0.971093E+09
December 0.149775E+10 0.106378E+10 0.433972E+09 0.147250E+10 0.131126E+10
           
Annual Sum or Average 0.172352E+11 0.857789E+10 0.865731E+10 0.198609E+11 0.857881E+10
Minimum of Months 0.101546E+10 0.156460E+09 0.433972E+09 0.127596E+10 89074224.50
Maximum of Months 0.218079E+10 0.136754E+10 0.922918E+09 0.264831E+10 0.147116E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 664.76 680.26 701.21 460.14 241.07 0.00 0.00
February 896.77 673.44 927.98 616.76 311.22 0.00 0.00
March 843.30 480.21 822.19 452.60 369.58 0.00 0.00
April 707.86 339.05 654.44 264.77 389.67 0.00 0.00
May 661.76 193.22 562.08 115.08 447.01 0.00 0.00
June 718.02 92.70 530.75 81.78 448.97 0.00 0.00
July 822.20 40.08 552.24 93.21 459.04 0.00 0.00
August 1088.23 69.97 739.68 272.86 466.82 0.00 0.00
September 1025.11 148.09 780.56 391.91 388.65 0.00 0.00
October 1333.18 304.01 1103.06 691.71 411.35 0.00 0.00
November 787.66 472.28 763.80 458.18 305.62 0.00 0.00
December 749.04 612.03 757.58 538.07 219.51 0.00 0.00
               
Annual Sum or Average 858.37 340.26 740.41 368.50 371.91 0.00 0.00
Minimum of Months 661.76 40.08 530.75 81.78 219.51 0.00 0.00
Maximum of Months 1333.18 680.26 1103.06 691.71 466.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1848.95 1977.77 1974.55 1295.73 678.82 0.00 0.00
February 2493.61 1960.72 2613.12 1736.75 876.37 0.00 0.00
March 2342.07 1441.40 2315.23 1274.50 1040.72 0.00 0.00
April 1956.16 1043.92 1842.86 745.58 1097.28 0.00 0.00
May 1813.60 620.81 1582.79 324.05 1258.74 0.00 0.00
June 1984.66 308.33 1494.54 230.28 1264.27 0.00 0.00
July 2285.63 140.61 1555.08 262.47 1292.62 0.00 0.00
August 3038.93 222.32 2082.88 768.36 1314.52 0.00 0.00
September 2852.20 480.72 2198.00 1103.59 1094.42 0.00 0.00
October 3715.59 942.36 3106.15 1947.82 1158.33 0.00 0.00
November 2181.69 1419.49 2150.80 1290.21 860.60 0.00 0.00
December 2082.82 1798.98 2133.29 1515.17 618.12 0.00 0.00
               
Annual Sum or Average 2383.61 1024.51 2084.94 1037.67 1047.27 0.00 0.00
Minimum of Months 1813.60 140.61 1494.54 230.28 618.12 0.00 0.00
Maximum of Months 3715.59 1977.77 3106.15 1947.82 1314.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2444.47 2695.82 2565.06 1683.23 881.83 0.00 0.00
February 3307.06 2651.22 3394.59 2256.14 1138.45 0.00 0.00
March 3106.55 1956.38 3007.61 1655.65 1351.96 0.00 0.00
April 2591.97 1427.59 2393.98 968.55 1425.43 0.00 0.00
May 2401.00 850.74 2056.14 420.96 1635.17 0.00 0.00
June 2636.24 412.77 1941.50 299.14 1642.35 0.00 0.00
July 3046.03 181.96 2020.14 340.96 1679.18 0.00 0.00
August 4046.42 284.03 2705.78 998.14 1707.64 0.00 0.00
September 3780.69 638.86 2855.33 1433.62 1421.71 0.00 0.00
October 4926.15 1250.32 4035.07 2530.33 1504.74 0.00 0.00
November 2882.45 1938.89 2794.02 1676.05 1117.96 0.00 0.00
December 2752.55 2453.74 2771.26 1968.29 802.97 0.00 0.00
               
Annual Sum or Average 3160.98 1388.06 2708.45 1347.99 1360.46 0.00 0.00
Minimum of Months 2401.00 181.96 1941.50 299.14 802.97 0.00 0.00
Maximum of Months 4926.15 2695.82 4035.07 2530.33 1707.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 177.80 398.93 241.68 133.28 108.40 0.00 0.00
February 257.44 396.39 334.84 188.37 146.47 0.00 0.00
March 354.22 271.62 387.39 193.68 193.71 0.00 0.00
April 380.47 190.66 373.58 156.70 216.88 0.00 0.00
May 453.38 109.99 396.40 131.19 265.20 0.00 0.00
June 544.28 51.06 416.61 141.95 274.66 0.00 0.00
July 587.50 14.71 400.78 128.01 272.78 0.00 0.00
August 681.78 29.30 468.86 203.11 265.75 0.00 0.00
September 489.06 80.16 383.87 177.69 206.17 0.00 0.00
October 511.45 169.76 445.84 247.71 198.14 0.00 0.00
November 220.76 272.23 258.27 121.92 136.35 0.00 0.00
December 191.19 357.50 244.52 147.28 97.24 0.00 0.00
               
Annual Sum or Average 405.27 194.05 363.00 164.20 198.80 0.00 0.00
Minimum of Months 177.80 14.71 241.68 121.92 97.24 0.00 0.00
Maximum of Months 681.78 398.93 468.86 247.71 274.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 57.91 420.73 129.71 42.30 87.41 0.00 0.00
February 97.47 424.06 187.86 66.43 121.44 0.00 0.00
March 210.34 273.37 275.46 104.19 171.27 0.00 0.00
April 284.12 188.83 305.11 104.60 200.51 0.00 0.00
May 404.75 106.90 366.30 111.40 254.89 0.00 0.00
June 510.96 49.55 397.16 130.33 266.83 0.00 0.00
July 545.08 14.30 374.57 112.82 261.76 0.00 0.00
August 571.72 28.04 396.00 150.14 245.86 0.00 0.00
September 350.52 77.68 284.79 100.24 184.55 0.00 0.00
October 288.85 167.65 275.53 110.94 164.58 0.00 0.00
November 81.50 280.29 140.77 31.33 109.43 0.00 0.00
December 54.61 378.90 118.00 40.89 77.11 0.00 0.00
               
Annual Sum or Average 289.52 199.59 271.50 92.35 179.15 0.00 0.00
Minimum of Months 54.61 14.30 118.00 31.33 77.11 0.00 0.00
Maximum of Months 571.72 424.06 397.16 150.14 266.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 105.38 106.68 110.89 72.77 38.12 0.00 0.00
February 140.79 110.43 146.75 97.54 49.22 0.00 0.00
March 131.99 81.58 130.02 71.58 58.45 0.00 0.00
April 110.26 58.62 103.50 41.87 61.62 0.00 0.00
May 101.57 35.47 88.89 18.20 70.69 0.00 0.00
June 113.60 15.91 83.93 12.93 71.00 0.00 0.00
July 132.76 5.94 87.33 14.74 72.59 0.00 0.00
August 176.11 10.23 116.97 43.15 73.82 0.00 0.00
September 162.49 25.61 123.44 61.98 61.46 0.00 0.00
October 209.97 53.35 174.44 109.39 65.05 0.00 0.00
November 122.95 80.04 120.79 72.46 48.33 0.00 0.00
December 118.09 98.67 119.81 85.09 34.71 0.00 0.00
               
Annual Sum or Average 135.54 56.57 117.09 58.28 58.81 0.00 0.00
Minimum of Months 101.57 5.94 83.93 12.93 34.71 0.00 0.00
Maximum of Months 209.97 110.43 174.44 109.39 73.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.91 128.05 21.34 0.00 21.34 0.00 0.00
February 2.40 129.83 29.20 0.00 29.20 0.00 0.00
March 14.32 82.69 40.51 0.00 40.51 0.00 0.00
April 32.68 54.11 48.75 0.20 48.55 0.00 0.00
May 66.01 28.31 64.84 2.37 62.47 0.00 0.00
June 91.07 11.48 68.40 3.64 64.76 0.00 0.00
July 105.34 2.90 66.39 2.59 63.80 0.00 0.00
August 93.87 6.24 58.71 0.78 57.93 0.00 0.00
September 53.21 19.76 44.21 0.03 44.18 0.00 0.00
October 31.42 46.14 38.23 0.00 38.23 0.00 0.00
November 7.79 84.10 26.81 0.00 26.81 0.00 0.00
December 0.66 115.80 18.62 0.00 18.62 0.00 0.00
               
Annual Sum or Average 41.91 58.72 43.92 0.81 43.11 0.00 0.00
Minimum of Months 0.66 2.90 18.62 0.00 18.62 0.00 0.00
Maximum of Months 105.34 129.83 68.40 3.64 64.76 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 178.39 396.13 242.40 132.43 109.97 0.00 0.00
February 268.23 390.89 344.58 196.96 147.61 0.00 0.00
March 333.99 273.13 369.44 177.41 192.03 0.00 0.00
April 381.30 185.26 377.04 161.05 216.00 0.00 0.00
May 470.05 106.22 410.12 141.90 268.22 0.00 0.00
June 501.30 47.22 382.57 116.73 265.84 0.00 0.00
July 569.78 13.83 387.67 118.68 268.98 0.00 0.00
August 667.26 27.32 460.40 195.68 264.72 0.00 0.00
September 494.21 76.27 389.33 183.35 205.98 0.00 0.00
October 491.37 164.88 430.40 232.86 197.53 0.00 0.00
November 251.93 269.50 282.51 141.12 141.39 0.00 0.00
December 201.41 353.48 252.59 154.89 97.70 0.00 0.00
               
Annual Sum or Average 401.79 190.90 360.92 162.61 198.31 0.00 0.00
Minimum of Months 178.39 13.83 242.40 116.73 97.70 0.00 0.00
Maximum of Months 667.26 396.13 460.40 232.86 268.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 52.93 412.48 130.44 41.46 88.98 0.00 0.00
February 96.65 406.57 197.60 75.02 122.58 0.00 0.00
March 188.81 273.41 257.51 87.92 169.58 0.00 0.00
April 283.78 182.92 308.58 108.95 199.63 0.00 0.00
May 421.27 103.58 380.02 122.12 257.91 0.00 0.00
June 468.06 46.00 363.12 105.11 258.02 0.00 0.00
July 527.40 13.53 361.46 103.49 257.96 0.00 0.00
August 557.33 26.35 387.54 142.71 244.83 0.00 0.00
September 354.62 73.58 290.26 105.90 184.36 0.00 0.00
October 267.39 161.75 260.08 96.10 163.98 0.00 0.00
November 107.88 272.63 165.01 50.53 114.48 0.00 0.00
December 58.37 368.16 126.07 48.51 77.56 0.00 0.00
               
Annual Sum or Average 283.33 193.90 269.42 90.76 178.66 0.00 0.00
Minimum of Months 52.93 13.53 126.07 41.46 77.56 0.00 0.00
Maximum of Months 557.33 412.48 387.54 142.71 258.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 203.60 511.43 286.50 157.67 128.83 0.00 0.00
February 282.83 506.74 381.24 211.33 169.91 0.00 0.00
March 316.74 353.24 369.48 155.09 214.39 0.00 0.00
April 314.13 245.22 329.85 91.16 238.69 0.00 0.00
May 366.56 136.63 333.06 44.57 288.49 0.00 0.00
June 437.51 66.01 330.05 35.90 294.14 0.00 0.00
July 503.26 25.43 333.06 37.55 295.51 0.00 0.00
August 569.48 44.43 380.64 95.19 285.46 0.00 0.00
September 463.86 106.43 363.23 134.34 228.89 0.00 0.00
October 523.44 217.78 460.78 237.02 223.77 0.00 0.00
November 277.15 347.99 319.80 157.00 162.81 0.00 0.00
December 233.50 455.99 299.91 184.37 115.54 0.00 0.00
               
Annual Sum or Average 375.10 250.00 348.85 128.01 220.84 0.00 0.00
Minimum of Months 203.60 25.43 286.50 35.90 115.54 0.00 0.00
Maximum of Months 569.48 511.43 460.78 237.02 295.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 176.90 397.99 241.68 133.28 108.40 0.00 0.00
February 255.53 396.09 334.84 188.37 146.47 0.00 0.00
March 350.93 271.16 387.39 193.68 193.71 0.00 0.00
April 376.28 190.33 373.58 156.70 216.88 0.00 0.00
May 447.35 110.79 396.40 131.19 265.20 0.00 0.00
June 538.30 52.27 416.61 141.95 274.66 0.00 0.00
July 583.54 14.54 400.78 128.01 272.78 0.00 0.00
August 678.20 28.61 468.86 203.11 265.75 0.00 0.00
September 485.13 80.51 383.87 177.69 206.17 0.00 0.00
October 507.47 169.48 445.84 247.71 198.14 0.00 0.00
November 219.93 270.35 258.27 121.92 136.35 0.00 0.00
December 190.67 356.01 244.52 147.28 97.24 0.00 0.00
               
Annual Sum or Average 402.00 193.70 363.00 164.20 198.80 0.00 0.00
Minimum of Months 176.90 14.54 241.68 121.92 97.24 0.00 0.00
Maximum of Months 678.20 397.99 468.86 247.71 274.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 57.76 420.10 129.71 42.30 87.41 0.00 0.00
February 96.81 424.35 187.86 66.43 121.44 0.00 0.00
March 208.61 272.64 275.46 104.19 171.27 0.00 0.00
April 281.11 188.18 305.11 104.60 200.51 0.00 0.00
May 399.21 107.76 366.30 111.40 254.89 0.00 0.00
June 505.41 50.84 397.16 130.33 266.83 0.00 0.00
July 541.55 14.18 374.57 112.82 261.76 0.00 0.00
August 569.16 27.31 396.00 150.14 245.86 0.00 0.00
September 347.87 77.43 284.79 100.24 184.55 0.00 0.00
October 287.29 165.94 275.53 110.94 164.58 0.00 0.00
November 81.72 277.95 140.77 31.33 109.43 0.00 0.00
December 54.82 377.32 118.00 40.89 77.11 0.00 0.00
               
Annual Sum or Average 287.30 199.06 271.50 92.35 179.15 0.00 0.00
Minimum of Months 54.82 14.18 118.00 31.33 77.11 0.00 0.00
Maximum of Months 569.16 424.35 397.16 150.14 266.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 186.92 207.18 203.33 133.43 69.90 0.00 0.00
February 252.31 206.27 269.09 178.84 90.24 0.00 0.00
March 238.48 145.69 238.41 131.24 107.17 0.00 0.00
April 200.74 100.94 189.77 76.78 112.99 0.00 0.00
May 187.71 56.72 162.99 33.37 129.62 0.00 0.00
June 209.23 23.77 153.90 23.71 130.19 0.00 0.00
July 248.94 6.31 160.14 27.03 133.11 0.00 0.00
August 327.42 13.51 214.49 79.12 135.36 0.00 0.00
September 297.08 40.95 226.34 113.64 112.70 0.00 0.00
October 383.17 87.88 319.86 200.58 119.28 0.00 0.00
November 223.71 142.64 221.48 132.86 88.62 0.00 0.00
December 212.15 185.47 219.68 156.02 63.65 0.00 0.00
               
Annual Sum or Average 247.44 100.85 214.70 106.85 107.84 0.00 0.00
Minimum of Months 186.92 6.31 153.90 23.71 63.65 0.00 0.00
Maximum of Months 383.17 207.18 319.86 200.58 135.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.63 1307.75 186.70 0.00 186.70 0.00 0.00
February 9.36 1319.39 255.50 0.00 255.50 0.00 0.00
March 86.01 879.31 354.39 0.01 354.39 0.00 0.00
April 226.57 595.95 426.48 1.76 424.73 0.00 0.00
May 494.44 321.89 567.24 20.76 546.48 0.00 0.00
June 720.68 152.94 598.43 31.83 566.60 0.00 0.00
July 825.70 66.40 580.84 22.67 558.17 0.00 0.00
August 723.51 99.99 513.65 6.82 506.83 0.00 0.00
September 400.77 250.58 386.77 0.22 386.54 0.00 0.00
October 219.11 515.53 334.44 0.00 334.44 0.00 0.00
November 42.42 901.14 234.58 0.00 234.58 0.00 0.00
December 1.53 1204.93 162.86 0.00 162.86 0.00 0.00
               
Annual Sum or Average 314.75 630.77 384.23 7.05 377.19 0.00 0.00
Minimum of Months 1.53 66.40 162.86 0.00 162.86 0.00 0.00
Maximum of Months 825.70 1319.39 598.43 31.83 566.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.97 1346.06 186.70 0.00 186.70 0.00 0.00
February 7.61 1356.13 255.50 0.00 255.50 0.00 0.00
March 78.41 905.45 354.39 0.01 354.39 0.00 0.00
April 215.66 614.05 426.48 1.76 424.73 0.00 0.00
May 481.55 331.37 567.24 20.76 546.48 0.00 0.00
June 710.88 159.11 598.43 31.83 566.60 0.00 0.00
July 817.20 71.05 580.84 22.67 558.17 0.00 0.00
August 714.82 104.88 513.65 6.82 506.83 0.00 0.00
September 391.92 259.91 386.77 0.22 386.54 0.00 0.00
October 210.02 530.11 334.44 0.00 334.44 0.00 0.00
November 37.91 930.21 234.58 0.00 234.58 0.00 0.00
December 1.14 1240.99 162.86 0.00 162.86 0.00 0.00
               
Annual Sum or Average 307.76 650.13 384.23 7.05 377.19 0.00 0.00
Minimum of Months 0.97 71.05 162.86 0.00 162.86 0.00 0.00
Maximum of Months 817.20 1356.13 598.43 31.83 566.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 214.83 898.67 372.82 173.88 198.94 0.00 0.00
February 348.87 869.93 542.15 271.97 270.18 0.00 0.00
March 528.02 629.78 626.92 265.32 361.60 0.00 0.00
April 696.10 439.95 685.59 269.98 415.61 0.00 0.00
May 958.52 256.78 790.10 264.00 526.10 0.00 0.00
June 1071.67 127.51 745.66 221.82 523.83 0.00 0.00
July 1199.81 59.16 749.08 222.16 526.92 0.00 0.00
August 1325.26 82.74 847.89 338.37 509.52 0.00 0.00
September 935.98 181.49 679.55 289.24 390.32 0.00 0.00
October 808.16 365.51 690.45 328.95 361.50 0.00 0.00
November 361.53 621.25 447.50 191.64 255.85 0.00 0.00
December 246.39 805.93 378.64 203.39 175.25 0.00 0.00
               
Annual Sum or Average 727.22 442.52 630.31 253.35 376.95 0.00 0.00
Minimum of Months 214.83 59.16 372.82 173.88 175.25 0.00 0.00
Maximum of Months 1325.26 898.67 847.89 338.37 526.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 445.13 916.06 581.59 339.65 241.94 0.00 0.00
February 612.98 904.74 772.56 455.25 317.31 0.00 0.00
March 644.72 639.08 728.38 334.09 394.29 0.00 0.00
April 602.99 447.22 629.27 196.04 433.23 0.00 0.00
May 657.08 252.95 609.35 92.06 517.29 0.00 0.00
June 772.70 123.08 596.91 71.27 525.63 0.00 0.00
July 889.09 53.50 606.75 76.57 530.18 0.00 0.00
August 1056.49 84.31 722.07 203.75 518.32 0.00 0.00
September 898.33 192.53 708.75 289.36 419.39 0.00 0.00
October 1064.68 384.33 928.86 510.58 418.28 0.00 0.00
November 579.63 625.11 644.20 338.20 306.00 0.00 0.00
December 509.85 817.59 615.02 397.17 217.85 0.00 0.00
               
Annual Sum or Average 728.91 450.83 678.24 274.42 403.82 0.00 0.00
Minimum of Months 445.13 53.50 581.59 71.27 217.85 0.00 0.00
Maximum of Months 1064.68 916.06 928.86 510.58 530.18 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.178050E+10 0.182202E+10 0.187811E+10 0.123244E+10 0.645669E+09 0.00 0.00
February 0.216947E+10 0.162918E+10 0.224496E+10 0.149206E+10 0.752897E+09 0.00 0.00
March 0.225870E+10 0.128621E+10 0.220215E+10 0.121226E+10 0.989890E+09 0.00 0.00
April 0.183477E+10 0.878822E+09 0.169631E+10 0.686285E+09 0.101002E+10 0.00 0.00
May 0.177246E+10 0.517534E+09 0.150549E+10 0.308226E+09 0.119726E+10 0.00 0.00
June 0.186112E+10 0.240285E+09 0.137569E+10 0.211965E+09 0.116373E+10 0.00 0.00
July 0.220219E+10 0.107350E+09 0.147913E+10 0.249647E+09 0.122948E+10 0.00 0.00
August 0.291472E+10 0.187407E+09 0.198115E+10 0.730828E+09 0.125032E+10 0.00 0.00
September 0.265707E+10 0.383847E+09 0.202321E+10 0.101583E+10 0.100738E+10 0.00 0.00
October 0.357080E+10 0.814268E+09 0.295444E+10 0.185269E+10 0.110176E+10 0.00 0.00
November 0.204162E+10 0.122414E+10 0.197976E+10 0.118761E+10 0.792159E+09 0.00 0.00
December 0.200623E+10 0.163926E+10 0.202909E+10 0.144117E+10 0.587926E+09 0.00 0.00
               
Annual Sum or Average 0.270697E+11 0.107303E+11 0.233495E+11 0.116210E+11 0.117285E+11 0.00 0.00
Minimum of Months 0.177246E+10 0.107350E+09 0.137569E+10 0.211965E+09 0.587926E+09 0.00 0.00
Maximum of Months 0.357080E+10 0.182202E+10 0.295444E+10 0.185269E+10 0.125032E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.495224E+10 0.529726E+10 0.528864E+10 0.347048E+10 0.181816E+10 0.00 0.00
February 0.603254E+10 0.474338E+10 0.632166E+10 0.420155E+10 0.212011E+10 0.00 0.00
March 0.627300E+10 0.386065E+10 0.620110E+10 0.341363E+10 0.278747E+10 0.00 0.00
April 0.507037E+10 0.270583E+10 0.477669E+10 0.193253E+10 0.284415E+10 0.00 0.00
May 0.485753E+10 0.166276E+10 0.423935E+10 0.867945E+09 0.337140E+10 0.00 0.00
June 0.514424E+10 0.799190E+09 0.387386E+10 0.596881E+09 0.327698E+10 0.00 0.00
July 0.612183E+10 0.376612E+09 0.416513E+10 0.702990E+09 0.346214E+10 0.00 0.00
August 0.813947E+10 0.595454E+09 0.557879E+10 0.205796E+10 0.352082E+10 0.00 0.00
September 0.739290E+10 0.124603E+10 0.569723E+10 0.286050E+10 0.283673E+10 0.00 0.00
October 0.995184E+10 0.252400E+10 0.831952E+10 0.521704E+10 0.310247E+10 0.00 0.00
November 0.565493E+10 0.367931E+10 0.557489E+10 0.334422E+10 0.223067E+10 0.00 0.00
December 0.557862E+10 0.481840E+10 0.571380E+10 0.405823E+10 0.165556E+10 0.00 0.00
               
Annual Sum or Average 0.751695E+11 0.323089E+11 0.657506E+11 0.327240E+11 0.330267E+11 0.00 0.00
Minimum of Months 0.485753E+10 0.376612E+09 0.387386E+10 0.596881E+09 0.165556E+10 0.00 0.00
Maximum of Months 0.995184E+10 0.529726E+10 0.831952E+10 0.521704E+10 0.352082E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.654728E+10 0.722050E+10 0.687025E+10 0.450835E+10 0.236190E+10 0.00 0.00
February 0.800043E+10 0.641383E+10 0.821220E+10 0.545806E+10 0.275414E+10 0.00 0.00
March 0.832058E+10 0.523996E+10 0.805558E+10 0.443450E+10 0.362108E+10 0.00 0.00
April 0.671838E+10 0.370030E+10 0.620519E+10 0.251047E+10 0.369472E+10 0.00 0.00
May 0.643084E+10 0.227863E+10 0.550715E+10 0.112751E+10 0.437965E+10 0.00 0.00
June 0.683315E+10 0.106990E+10 0.503236E+10 0.775382E+09 0.425698E+10 0.00 0.00
July 0.815848E+10 0.487365E+09 0.541074E+10 0.913224E+09 0.449752E+10 0.00 0.00
August 0.108379E+11 0.760740E+09 0.724716E+10 0.267341E+10 0.457375E+10 0.00 0.00
September 0.979956E+10 0.165592E+10 0.740102E+10 0.371595E+10 0.368507E+10 0.00 0.00
October 0.131942E+11 0.334885E+10 0.108075E+11 0.677724E+10 0.403029E+10 0.00 0.00
November 0.747131E+10 0.502561E+10 0.724209E+10 0.434433E+10 0.289776E+10 0.00 0.00
December 0.737242E+10 0.657209E+10 0.742255E+10 0.527188E+10 0.215067E+10 0.00 0.00
               
Annual Sum or Average 0.996846E+11 0.437737E+11 0.854138E+11 0.425103E+11 0.429035E+11 0.00 0.00
Minimum of Months 0.643084E+10 0.487365E+09 0.503236E+10 0.775382E+09 0.215067E+10 0.00 0.00
Maximum of Months 0.131942E+11 0.722050E+10 0.108075E+11 0.677724E+10 0.457375E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.476224E+09 0.106850E+10 0.647322E+09 0.356975E+09 0.290347E+09 0.00 0.00
February 0.622787E+09 0.958947E+09 0.810044E+09 0.455710E+09 0.354334E+09 0.00 0.00
March 0.948755E+09 0.727504E+09 0.103759E+10 0.518749E+09 0.518839E+09 0.00 0.00
April 0.986182E+09 0.494194E+09 0.968321E+09 0.406169E+09 0.562152E+09 0.00 0.00
May 0.121433E+10 0.294603E+09 0.106171E+10 0.351385E+09 0.710324E+09 0.00 0.00
June 0.141076E+10 0.132352E+09 0.107985E+10 0.367935E+09 0.711915E+09 0.00 0.00
July 0.157355E+10 39394251.60 0.107346E+10 0.342851E+09 0.730606E+09 0.00 0.00
August 0.182608E+10 78466275.04 0.125580E+10 0.544016E+09 0.711787E+09 0.00 0.00
September 0.126765E+10 0.207787E+09 0.994979E+09 0.460585E+09 0.534394E+09 0.00 0.00
October 0.136987E+10 0.454680E+09 0.119415E+10 0.663463E+09 0.530687E+09 0.00 0.00
November 0.572212E+09 0.705622E+09 0.669436E+09 0.316026E+09 0.353410E+09 0.00 0.00
December 0.512080E+09 0.957527E+09 0.654927E+09 0.394476E+09 0.260452E+09 0.00 0.00
               
Annual Sum or Average 0.127805E+11 0.611958E+10 0.114476E+11 0.517834E+10 0.626925E+10 0.00 0.00
Minimum of Months 0.476224E+09 39394251.60 0.647322E+09 0.316026E+09 0.260452E+09 0.00 0.00
Maximum of Months 0.182608E+10 0.106850E+10 0.125580E+10 0.663463E+09 0.730606E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.155104E+09 0.112688E+10 0.347427E+09 0.113300E+09 0.234127E+09 0.00 0.00
February 0.235809E+09 0.102588E+10 0.454479E+09 0.160704E+09 0.293776E+09 0.00 0.00
March 0.563367E+09 0.732195E+09 0.737791E+09 0.279068E+09 0.458722E+09 0.00 0.00
April 0.736449E+09 0.489442E+09 0.790856E+09 0.271129E+09 0.519727E+09 0.00 0.00
May 0.108407E+10 0.286316E+09 0.981097E+09 0.298386E+09 0.682711E+09 0.00 0.00
June 0.132441E+10 0.128432E+09 0.102945E+10 0.337812E+09 0.691635E+09 0.00 0.00
July 0.145995E+10 38312806.46 0.100326E+10 0.302165E+09 0.701093E+09 0.00 0.00
August 0.153129E+10 75108257.71 0.106064E+10 0.402130E+09 0.658510E+09 0.00 0.00
September 0.908552E+09 0.201340E+09 0.738174E+09 0.259822E+09 0.478352E+09 0.00 0.00
October 0.773662E+09 0.449029E+09 0.737978E+09 0.297155E+09 0.440823E+09 0.00 0.00
November 0.211241E+09 0.726512E+09 0.364867E+09 81216406.75 0.283651E+09 0.00 0.00
December 0.146254E+09 0.101485E+10 0.316056E+09 0.109532E+09 0.206524E+09 0.00 0.00
               
Annual Sum or Average 0.913016E+10 0.629430E+10 0.856207E+10 0.291242E+10 0.564965E+10 0.00 0.00
Minimum of Months 0.146254E+09 38312806.46 0.316056E+09 81216406.75 0.206524E+09 0.00 0.00
Maximum of Months 0.153129E+10 0.112688E+10 0.106064E+10 0.402130E+09 0.701093E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.282259E+09 0.285735E+09 0.297010E+09 0.194901E+09 0.102108E+09 0.00 0.00
February 0.340588E+09 0.267162E+09 0.355024E+09 0.235958E+09 0.119066E+09 0.00 0.00
March 0.353515E+09 0.218494E+09 0.348254E+09 0.191709E+09 0.156545E+09 0.00 0.00
April 0.285786E+09 0.151951E+09 0.268259E+09 0.108531E+09 0.159729E+09 0.00 0.00
May 0.272033E+09 95010871.68 0.238083E+09 48743591.57 0.189339E+09 0.00 0.00
June 0.294444E+09 41244920.82 0.217557E+09 33520696.39 0.184036E+09 0.00 0.00
July 0.355594E+09 15904674.82 0.233915E+09 39479779.53 0.194435E+09 0.00 0.00
August 0.471693E+09 27407166.78 0.313305E+09 0.115575E+09 0.197731E+09 0.00 0.00
September 0.421185E+09 66392107.54 0.319956E+09 0.160645E+09 0.159311E+09 0.00 0.00
October 0.562387E+09 0.142879E+09 0.467223E+09 0.292988E+09 0.174235E+09 0.00 0.00
November 0.318694E+09 0.207472E+09 0.313085E+09 0.187811E+09 0.125275E+09 0.00 0.00
December 0.316279E+09 0.264265E+09 0.320886E+09 0.227910E+09 92976446.14 0.00 0.00
               
Annual Sum or Average 0.427446E+10 0.178392E+10 0.369256E+10 0.183777E+10 0.185479E+10 0.00 0.00
Minimum of Months 0.272033E+09 15904674.82 0.217557E+09 33520696.39 92976446.14 0.00 0.00
Maximum of Months 0.562387E+09 0.285735E+09 0.467223E+09 0.292988E+09 0.197731E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 2444534.02 0.342977E+09 57160472.40 0.00 57160472.40 0.00 0.00
February 5807046.51 0.314084E+09 70651943.00 0.00 70651943.00 0.00 0.00
March 38367794.57 0.221485E+09 0.108500E+09 2259.91 0.108497E+09 0.00 0.00
April 84699764.48 0.140264E+09 0.126358E+09 520654.15 0.125837E+09 0.00 0.00
May 0.176799E+09 75812948.57 0.173664E+09 6355606.08 0.167308E+09 0.00 0.00
June 0.236063E+09 29763368.15 0.177301E+09 9430371.18 0.167871E+09 0.00 0.00
July 0.282140E+09 7755595.40 0.177826E+09 6940076.94 0.170886E+09 0.00 0.00
August 0.251415E+09 16726499.57 0.157258E+09 2089481.97 0.155168E+09 0.00 0.00
September 0.137931E+09 51230740.21 0.114591E+09 66617.56 0.114525E+09 0.00 0.00
October 84163870.22 0.123587E+09 0.102392E+09 0.00 0.102392E+09 0.00 0.00
November 20188180.22 0.217984E+09 69501271.94 0.00 69501271.94 0.00 0.00
December 1774174.98 0.310164E+09 49859143.80 0.00 49859143.80 0.00 0.00
               
Annual Sum or Average 0.132179E+10 0.185183E+10 0.138506E+10 25405067.78 0.135966E+10 0.00 0.00
Minimum of Months 1774174.98 7755595.40 49859143.80 0.00 49859143.80 0.00 0.00
Maximum of Months 0.282140E+09 0.342977E+09 0.177826E+09 9430371.18 0.170886E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.477793E+09 0.106098E+10 0.649253E+09 0.354712E+09 0.294541E+09 0.00 0.00
February 0.648912E+09 0.945629E+09 0.833601E+09 0.476496E+09 0.357104E+09 0.00 0.00
March 0.894555E+09 0.731551E+09 0.989505E+09 0.475173E+09 0.514332E+09 0.00 0.00
April 0.988341E+09 0.480185E+09 0.977300E+09 0.417431E+09 0.559869E+09 0.00 0.00
May 0.125899E+10 0.284510E+09 0.109847E+10 0.380074E+09 0.718394E+09 0.00 0.00
June 0.129937E+10 0.122406E+09 0.991622E+09 0.302565E+09 0.689057E+09 0.00 0.00
July 0.152611E+10 37053050.12 0.103833E+10 0.317885E+09 0.720441E+09 0.00 0.00
August 0.178718E+10 73166201.49 0.123314E+10 0.524115E+09 0.709025E+09 0.00 0.00
September 0.128099E+10 0.197703E+09 0.100915E+10 0.475251E+09 0.533897E+09 0.00 0.00
October 0.131609E+10 0.441621E+09 0.115278E+10 0.623702E+09 0.529077E+09 0.00 0.00
November 0.653002E+09 0.698534E+09 0.732263E+09 0.365783E+09 0.366480E+09 0.00 0.00
December 0.539457E+09 0.946748E+09 0.676533E+09 0.414864E+09 0.261669E+09 0.00 0.00
               
Annual Sum or Average 0.126708E+11 0.602009E+10 0.113819E+11 0.512805E+10 0.625389E+10 0.00 0.00
Minimum of Months 0.477793E+09 37053050.12 0.649253E+09 0.302565E+09 0.261669E+09 0.00 0.00
Maximum of Months 0.178718E+10 0.106098E+10 0.123314E+10 0.623702E+09 0.720441E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.141762E+09 0.110478E+10 0.349358E+09 0.111036E+09 0.238322E+09 0.00 0.00
February 0.233820E+09 0.983569E+09 0.478035E+09 0.181489E+09 0.296546E+09 0.00 0.00
March 0.505722E+09 0.732303E+09 0.689708E+09 0.235492E+09 0.454216E+09 0.00 0.00
April 0.735551E+09 0.474140E+09 0.799836E+09 0.282392E+09 0.517444E+09 0.00 0.00
May 0.112833E+10 0.277441E+09 0.101786E+10 0.327076E+09 0.690780E+09 0.00 0.00
June 0.121320E+10 0.119232E+09 0.941219E+09 0.272442E+09 0.668777E+09 0.00 0.00
July 0.141259E+10 36234066.31 0.968127E+09 0.277199E+09 0.690928E+09 0.00 0.00
August 0.149275E+10 70572402.82 0.103798E+10 0.382230E+09 0.655747E+09 0.00 0.00
September 0.919178E+09 0.190725E+09 0.752343E+09 0.274488E+09 0.477855E+09 0.00 0.00
October 0.716167E+09 0.433230E+09 0.696606E+09 0.257394E+09 0.439212E+09 0.00 0.00
November 0.279631E+09 0.706667E+09 0.427694E+09 0.130973E+09 0.296721E+09 0.00 0.00
December 0.156330E+09 0.986068E+09 0.337662E+09 0.129921E+09 0.207741E+09 0.00 0.00
               
Annual Sum or Average 0.893503E+10 0.611496E+10 0.849642E+10 0.286213E+10 0.563429E+10 0.00 0.00
Minimum of Months 0.141762E+09 36234066.31 0.337662E+09 0.111036E+09 0.207741E+09 0.00 0.00
Maximum of Months 0.149275E+10 0.110478E+10 0.103798E+10 0.382230E+09 0.690928E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.545334E+09 0.136982E+10 0.767366E+09 0.422297E+09 0.345069E+09 0.00 0.00
February 0.684231E+09 0.122591E+10 0.922294E+09 0.511256E+09 0.411038E+09 0.00 0.00
March 0.848352E+09 0.946128E+09 0.989615E+09 0.415385E+09 0.574230E+09 0.00 0.00
April 0.814235E+09 0.635618E+09 0.854977E+09 0.236284E+09 0.618693E+09 0.00 0.00
May 0.981793E+09 0.365963E+09 0.892073E+09 0.119382E+09 0.772691E+09 0.00 0.00
June 0.113404E+10 0.171110E+09 0.855479E+09 93059373.46 0.762420E+09 0.00 0.00
July 0.134792E+10 68109475.54 0.892059E+09 0.100576E+09 0.791483E+09 0.00 0.00
August 0.152529E+10 0.118993E+09 0.101952E+10 0.254945E+09 0.764574E+09 0.00 0.00
September 0.120234E+10 0.275870E+09 0.941500E+09 0.348218E+09 0.593282E+09 0.00 0.00
October 0.140197E+10 0.583304E+09 0.123416E+10 0.634824E+09 0.599335E+09 0.00 0.00
November 0.718368E+09 0.901991E+09 0.828931E+09 0.406933E+09 0.421998E+09 0.00 0.00
December 0.625398E+09 0.122132E+10 0.803283E+09 0.493817E+09 0.309466E+09 0.00 0.00
               
Annual Sum or Average 0.118293E+11 0.788413E+10 0.110013E+11 0.403698E+10 0.696428E+10 0.00 0.00
Minimum of Months 0.545334E+09 68109475.54 0.767366E+09 93059373.46 0.309466E+09 0.00 0.00
Maximum of Months 0.152529E+10 0.136982E+10 0.123416E+10 0.634824E+09 0.791483E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.473818E+09 0.106598E+10 0.647322E+09 0.356975E+09 0.290347E+09 0.00 0.00
February 0.618175E+09 0.958229E+09 0.810044E+09 0.455710E+09 0.354334E+09 0.00 0.00
March 0.939942E+09 0.726267E+09 0.103759E+10 0.518749E+09 0.518839E+09 0.00 0.00
April 0.975324E+09 0.493322E+09 0.968321E+09 0.406169E+09 0.562152E+09 0.00 0.00
May 0.119819E+10 0.296753E+09 0.106171E+10 0.351385E+09 0.710324E+09 0.00 0.00
June 0.139527E+10 0.135481E+09 0.107985E+10 0.367935E+09 0.711915E+09 0.00 0.00
July 0.156296E+10 38946020.66 0.107346E+10 0.342851E+09 0.730606E+09 0.00 0.00
August 0.181649E+10 76627418.43 0.125580E+10 0.544016E+09 0.711787E+09 0.00 0.00
September 0.125745E+10 0.208680E+09 0.994979E+09 0.460585E+09 0.534394E+09 0.00 0.00
October 0.135920E+10 0.453947E+09 0.119415E+10 0.663463E+09 0.530687E+09 0.00 0.00
November 0.570062E+09 0.700739E+09 0.669436E+09 0.316026E+09 0.353410E+09 0.00 0.00
December 0.510697E+09 0.953539E+09 0.654927E+09 0.394476E+09 0.260452E+09 0.00 0.00
               
Annual Sum or Average 0.126776E+11 0.610852E+10 0.114476E+11 0.517834E+10 0.626925E+10 0.00 0.00
Minimum of Months 0.473818E+09 38946020.66 0.647322E+09 0.316026E+09 0.260452E+09 0.00 0.00
Maximum of Months 0.181649E+10 0.106598E+10 0.125580E+10 0.663463E+09 0.730606E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.154706E+09 0.112521E+10 0.347427E+09 0.113300E+09 0.234127E+09 0.00 0.00
February 0.234213E+09 0.102658E+10 0.454479E+09 0.160704E+09 0.293776E+09 0.00 0.00
March 0.558731E+09 0.730232E+09 0.737791E+09 0.279068E+09 0.458722E+09 0.00 0.00
April 0.728648E+09 0.487751E+09 0.790856E+09 0.271129E+09 0.519727E+09 0.00 0.00
May 0.106923E+10 0.288620E+09 0.981097E+09 0.298386E+09 0.682711E+09 0.00 0.00
June 0.131002E+10 0.131775E+09 0.102945E+10 0.337812E+09 0.691635E+09 0.00 0.00
July 0.145048E+10 37975451.76 0.100326E+10 0.302165E+09 0.701093E+09 0.00 0.00
August 0.152445E+10 73149619.96 0.106064E+10 0.402130E+09 0.658510E+09 0.00 0.00
September 0.901691E+09 0.200687E+09 0.738174E+09 0.259822E+09 0.478352E+09 0.00 0.00
October 0.769465E+09 0.444447E+09 0.737978E+09 0.297155E+09 0.440823E+09 0.00 0.00
November 0.211819E+09 0.720445E+09 0.364867E+09 81216406.75 0.283651E+09 0.00 0.00
December 0.146835E+09 0.101061E+10 0.316056E+09 0.109532E+09 0.206524E+09 0.00 0.00
               
Annual Sum or Average 0.906029E+10 0.627748E+10 0.856207E+10 0.291242E+10 0.564965E+10 0.00 0.00
Minimum of Months 0.146835E+09 37975451.76 0.316056E+09 81216406.75 0.206524E+09 0.00 0.00
Maximum of Months 0.152445E+10 0.112521E+10 0.106064E+10 0.402130E+09 0.701093E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.500643E+09 0.554920E+09 0.544600E+09 0.357373E+09 0.187227E+09 0.00 0.00
February 0.610392E+09 0.499016E+09 0.650976E+09 0.432656E+09 0.218320E+09 0.00 0.00
March 0.638751E+09 0.390205E+09 0.638561E+09 0.351519E+09 0.287042E+09 0.00 0.00
April 0.520328E+09 0.261641E+09 0.491883E+09 0.199003E+09 0.292880E+09 0.00 0.00
May 0.502755E+09 0.151922E+09 0.436551E+09 89376714.80 0.347174E+09 0.00 0.00
June 0.542328E+09 61607783.17 0.398915E+09 61463868.89 0.337451E+09 0.00 0.00
July 0.666763E+09 16897386.09 0.428908E+09 72390500.62 0.356518E+09 0.00 0.00
August 0.876964E+09 36186667.85 0.574480E+09 0.211919E+09 0.362561E+09 0.00 0.00
September 0.770043E+09 0.106141E+09 0.586675E+09 0.294560E+09 0.292115E+09 0.00 0.00
October 0.102629E+10 0.235379E+09 0.856705E+09 0.537226E+09 0.319480E+09 0.00 0.00
November 0.579844E+09 0.369720E+09 0.574076E+09 0.344371E+09 0.229705E+09 0.00 0.00
December 0.568214E+09 0.496750E+09 0.588380E+09 0.417897E+09 0.170482E+09 0.00 0.00
               
Annual Sum or Average 0.780331E+10 0.318038E+10 0.677071E+10 0.336976E+10 0.340095E+10 0.00 0.00
Minimum of Months 0.500643E+09 16897386.09 0.398915E+09 61463868.89 0.170482E+09 0.00 0.00
Maximum of Months 0.102629E+10 0.554920E+09 0.856705E+09 0.537226E+09 0.362561E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 4354753.64 0.350269E+10 0.500069E+09 0.00 0.500069E+09 0.00 0.00
February 22640451.88 0.319186E+10 0.618099E+09 0.00 0.618099E+09 0.00 0.00
March 0.230363E+09 0.235515E+10 0.949209E+09 19770.80 0.949189E+09 0.00 0.00
April 0.587282E+09 0.154470E+10 0.110544E+10 4554947.47 0.110089E+10 0.00 0.00
May 0.132432E+10 0.862157E+09 0.151930E+10 55602076.65 0.146370E+10 0.00 0.00
June 0.186801E+10 0.396408E+09 0.155112E+10 82501686.62 0.146862E+10 0.00 0.00
July 0.221157E+10 0.177850E+09 0.155571E+10 60715325.16 0.149500E+10 0.00 0.00
August 0.193785E+10 0.267824E+09 0.137577E+10 18279851.73 0.135749E+10 0.00 0.00
September 0.103878E+10 0.649504E+09 0.100250E+10 582804.32 0.100192E+10 0.00 0.00
October 0.586865E+09 0.138080E+10 0.895777E+09 0.00 0.895777E+09 0.00 0.00
November 0.109942E+09 0.233575E+10 0.608032E+09 0.00 0.608032E+09 0.00 0.00
December 4110199.06 0.322727E+10 0.436193E+09 0.00 0.436193E+09 0.00 0.00
               
Annual Sum or Average 0.992609E+10 0.198920E+11 0.121172E+11 0.222256E+09 0.118950E+11 0.00 0.00
Minimum of Months 4110199.06 0.177850E+09 0.436193E+09 0.00 0.436193E+09 0.00 0.00
Maximum of Months 0.221157E+10 0.350269E+10 0.155571E+10 82501686.62 0.149500E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 2585893.16 0.360528E+10 0.500069E+09 0.00 0.500069E+09 0.00 0.00
February 18408818.65 0.328074E+10 0.618099E+09 0.00 0.618099E+09 0.00 0.00
March 0.210012E+09 0.242516E+10 0.949209E+09 19770.80 0.949189E+09 0.00 0.00
April 0.559003E+09 0.159161E+10 0.110544E+10 4554947.47 0.110089E+10 0.00 0.00
May 0.128979E+10 0.887528E+09 0.151930E+10 55602076.65 0.146370E+10 0.00 0.00
June 0.184259E+10 0.412414E+09 0.155112E+10 82501686.62 0.146862E+10 0.00 0.00
July 0.218878E+10 0.190303E+09 0.155571E+10 60715325.16 0.149500E+10 0.00 0.00
August 0.191457E+10 0.280916E+09 0.137577E+10 18279851.73 0.135749E+10 0.00 0.00
September 0.101587E+10 0.673698E+09 0.100250E+10 582804.32 0.100192E+10 0.00 0.00
October 0.562523E+09 0.141986E+10 0.895777E+09 0.00 0.895777E+09 0.00 0.00
November 98266663.64 0.241110E+10 0.608032E+09 0.00 0.608032E+09 0.00 0.00
December 3065637.18 0.332388E+10 0.436193E+09 0.00 0.436193E+09 0.00 0.00
               
Annual Sum or Average 0.970547E+10 0.205025E+11 0.121172E+11 0.222256E+09 0.118950E+11 0.00 0.00
Minimum of Months 2585893.16 0.190303E+09 0.436193E+09 0.00 0.436193E+09 0.00 0.00
Maximum of Months 0.218878E+10 0.360528E+10 0.155571E+10 82501686.62 0.149500E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.575388E+09 0.240699E+10 0.998571E+09 0.465732E+09 0.532839E+09 0.00 0.00
February 0.843982E+09 0.210453E+10 0.131158E+10 0.657960E+09 0.653621E+09 0.00 0.00
March 0.141425E+10 0.168679E+10 0.167913E+10 0.710631E+09 0.968503E+09 0.00 0.00
April 0.180428E+10 0.114034E+10 0.177704E+10 0.699783E+09 0.107726E+10 0.00 0.00
May 0.256729E+10 0.687748E+09 0.211621E+10 0.707104E+09 0.140911E+10 0.00 0.00
June 0.277777E+10 0.330518E+09 0.193274E+10 0.574969E+09 0.135777E+10 0.00 0.00
July 0.321358E+10 0.158444E+09 0.200635E+10 0.595046E+09 0.141130E+10 0.00 0.00
August 0.354956E+10 0.221608E+09 0.227100E+10 0.906291E+09 0.136471E+10 0.00 0.00
September 0.242607E+10 0.470418E+09 0.176141E+10 0.749700E+09 0.101171E+10 0.00 0.00
October 0.216458E+10 0.978995E+09 0.184930E+10 0.881059E+09 0.968244E+09 0.00 0.00
November 0.937075E+09 0.161028E+10 0.115991E+10 0.496737E+09 0.663171E+09 0.00 0.00
December 0.659928E+09 0.215861E+10 0.101416E+10 0.544767E+09 0.469389E+09 0.00 0.00
               
Annual Sum or Average 0.229338E+11 0.139553E+11 0.198774E+11 0.798978E+10 0.118876E+11 0.00 0.00
Minimum of Months 0.575388E+09 0.158444E+09 0.998571E+09 0.465732E+09 0.469389E+09 0.00 0.00
Maximum of Months 0.354956E+10 0.240699E+10 0.227100E+10 0.906291E+09 0.141130E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.119225E+10 0.245357E+10 0.155773E+10 0.909713E+09 0.648020E+09 0.00 0.00
February 0.148292E+10 0.218875E+10 0.186898E+10 0.110135E+10 0.767631E+09 0.00 0.00
March 0.172683E+10 0.171172E+10 0.195088E+10 0.894818E+09 0.105606E+10 0.00 0.00
April 0.156296E+10 0.115919E+10 0.163106E+10 0.508134E+09 0.112293E+10 0.00 0.00
May 0.175992E+10 0.677513E+09 0.163208E+10 0.246574E+09 0.138551E+10 0.00 0.00
June 0.200285E+10 0.319018E+09 0.154719E+10 0.184741E+09 0.136244E+10 0.00 0.00
July 0.238133E+10 0.143304E+09 0.162511E+10 0.205087E+09 0.142002E+10 0.00 0.00
August 0.282971E+10 0.225817E+09 0.193399E+10 0.545718E+09 0.138827E+10 0.00 0.00
September 0.232847E+10 0.499033E+09 0.183707E+10 0.750019E+09 0.108705E+10 0.00 0.00
October 0.285165E+10 0.102939E+10 0.248786E+10 0.136754E+10 0.112033E+10 0.00 0.00
November 0.150240E+10 0.162029E+10 0.166978E+10 0.876615E+09 0.793160E+09 0.00 0.00
December 0.136558E+10 0.218982E+10 0.164728E+10 0.106378E+10 0.583500E+09 0.00 0.00
               
Annual Sum or Average 0.229869E+11 0.142174E+11 0.213890E+11 0.865408E+10 0.127349E+11 0.00 0.00
Minimum of Months 0.119225E+10 0.143304E+09 0.154719E+10 0.184741E+09 0.583500E+09 0.00 0.00
Maximum of Months 0.285165E+10 0.245357E+10 0.248786E+10 0.136754E+10 0.142002E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 1.17 -0.7 -4.4 5.65 -10.4 36.91 88.07 0.05
February -0.2 -2.6 -7.5 5.07 -13.4 46.98 136.68 0.04
March 5.59 3.43 0.29 5.58 -4.1 68.24 153.73 0.03
April 10.94 8.00 4.75 4.99 0.53 82.64 161.98 0.05
May 16.05 12.31 9.14 4.42 7.77 109.28 173.60 0.03
June 21.71 18.08 15.84 4.92 13.23 112.36 186.51 0.01
July 25.05 21.76 20.26 4.06 17.39 114.46 172.96 0.02
August 24.79 19.84 17.14 4.19 14.42 95.56 226.16 0.00
September 19.96 15.96 13.24 3.91 10.59 73.65 166.08 0.03
October 14.02 11.03 7.95 4.86 2.64 61.34 179.75 0.00
November 7.31 4.98 2.14 5.60 -4.0 48.23 90.71 0.03
December 3.33 0.91 -2.8 5.64 -8.5 30.23 98.59 0.04
                 
Annual Sum or Average 12.55 9.49 6.43 4.91 2.28 73.48 153.05 0.03
Minimum of Months -0.2 -2.6 -7.5 3.91 -13.4 30.23 88.07 0.00
Maximum of Months 25.05 21.76 20.26 5.65 17.39 114.46 226.16 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.20 24-JAN-12:20 11.81 11.50 1.00 8.15 93.67 0.00
February 10.00 20-FEB-11:00 4.36 -3.3 2.60 -3.9 151.50 540.00
March 22.20 27-MAR-15:00 16.34 12.80 6.70 11.65 136.50 590.00
April 26.70 07-APR-12:00 16.40 9.40 6.20 11.65 179.00 713.50
May 30.00 30-MAY-12:00 18.00 10.60 5.20 17.39 233.50 730.00
June 36.70 19-JUN-11:00 24.28 19.40 5.20 24.83 185.00 771.50
July 33.90 07-JUL-11:00 23.31 18.90 3.60 23.82 331.00 570.00
August 33.90 24-AUG-14:00 20.23 12.80 8.80 21.61 240.00 432.00
September 31.10 01-SEP-13:00 17.34 8.30 4.60 18.46 182.00 662.00
October 25.00 04-OCT-12:00 18.54 15.00 5.20 11.27 171.50 695.00
November 17.80 04-NOV-12:20 12.57 8.50 3.60 6.15 182.50 595.67
December 12.20 17-DEC-12:20 4.65 -6.1 4.27 -4.7 53.17 801.67
                 
Annual Sum or Average                
Minimum of Months 10.00   4.36 -6.1 1.00 -4.7 53.17 0.00
Maximum of Months 36.70   24.28 19.40 8.80 24.83 331.00 801.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -12.2 02-JAN-04:00 -13.6 -19.4 2.60 -30.7 0.00 0.00
February -13.9 06-FEB-02:00 -15.3 -22.8 7.20 -34.1 0.00 0.00
March -5.0 23-MAR-03:00 -7.6 -14.4 1.50 -23.9 0.00 0.00
April 2.20 01-APR-03:00 0.57 -1.7 3.10 -6.6 0.00 0.00
May 6.10 01-MAY-04:00 4.33 2.20 3.60 -9.7 25.50 0.00
June 13.30 03-JUN-02:00 9.35 5.60 4.60 -2.1 0.00 0.00
July 18.30 02-JUL-02:00 17.54 17.20 0.00 5.33 0.00 0.00
August 15.00 08-AUG-04:00 12.47 10.60 3.10 3.06 0.00 0.00
September 10.00 24-SEP-05:00 8.56 7.20 2.60 -3.4 18.50 158.50
October 2.20 09-OCT-03:00 1.71 1.10 0.00 -13.7 0.00 0.00
November -4.4 24-NOV-05:00 -6.2 -10.0 1.50 -19.7 0.00 0.00
December -8.3 31-DEC-23:00 -10.6 -18.9 9.30 -26.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -13.9   -15.3 -22.8 0.00 -34.1 0.00 0.00
Maximum of Months 18.30   17.54 17.20 9.30 5.33 25.50 158.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.93 24-JAN-11:00 12.20 11.70 1.50 8.15 103.00 0.00
February 6.67 28-FEB-09:00 7.20 6.10 4.10 2.01 101.50 0.00
March 16.99 27-MAR-12:00 20.60 15.00 3.60 10.50 295.50 565.50
April 17.70 09-APR-10:00 21.70 15.60 4.10 14.84 244.50 281.50
May 20.43 31-MAY-12:00 26.10 17.80 4.10 17.03 214.00 772.00
June 24.96 15-JUN-11:00 31.10 22.80 5.20 22.47 380.00 460.00
July 26.10 08-JUL-11:00 32.20 23.90 5.20 22.47 354.00 501.50
August 25.84 03-AUG-13:00 30.00 24.40 6.20 20.57 298.00 500.00
September 23.57 07-SEP-13:00 27.20 22.20 6.20 15.02 148.00 730.50
October 19.76 25-OCT-10:00 25.00 17.20 7.70 14.84 189.00 308.50
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.26 25-DEC-08:00 10.60 10.00 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.67   7.20 6.10 1.50 2.01 43.00 0.00
Maximum of Months 26.10   32.20 24.40 8.20 22.47 380.00 772.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 18-JAN-15:00 12.20 11.93 14.90 8.15 22.00 2.00
February 6.10 28-FEB-10:20 7.03 6.58 3.43 1.87 109.83 0.00
March 15.00 27-MAR-12:20 18.00 16.18 3.93 10.11 271.83 611.17
April 15.60 09-APR-10:00 21.70 17.70 4.10 14.84 244.50 281.50
May 18.00 18-MAY-09:00 18.00 18.00 4.60 15.39 265.50 12.00
June 22.80 15-JUN-11:00 31.10 24.96 5.20 22.47 380.00 460.00
July 24.40 09-JUL-07:00 27.20 25.17 2.10 15.39 195.00 504.00
August 25.00 03-AUG-19:00 26.10 25.32 5.70 19.35 0.00 0.00
September 22.20 07-SEP-13:00 27.20 23.57 6.20 15.02 148.00 730.50
October 18.30 05-OCT-18:00 19.40 18.62 7.70 6.55 0.00 0.00
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.00 25-DEC-08:00 10.60 10.26 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   7.03 6.58 2.10 1.87 0.00 0.00
Maximum of Months 25.00   31.10 25.32 14.90 22.47 380.00 730.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.03 13.58 0.00
February 18.00 13.00 16.00 9.54 21.42 0.00
March 18.00 13.00 16.00 10.65 30.29 0.00
April 18.00 13.00 16.00 13.15 37.02 0.00
May 18.00 13.00 16.00 16.36 45.86 0.00
June 18.00 13.00 16.00 19.42 49.74 0.00
July 18.00 13.00 16.00 21.50 48.12 0.00
August 18.00 13.00 16.00 22.05 49.54 0.00
September 18.00 13.00 16.00 20.89 34.71 0.00
October 18.00 13.00 16.00 18.36 29.93 0.00
November 18.00 13.00 16.00 15.14 17.00 0.00
December 18.00 13.00 16.00 12.10 12.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 15.80 32.53 0.00
Minimum of Months 18.00 13.00 16.00 9.54 12.41 0.00
Maximum of Months 18.00 13.00 16.00 22.05 49.74 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770486E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -162070961.1 81.21 0.00 0.00
February 0.696251E+10 -0.681598E+10 0.00 0.00 672.00 0.00 -146530927.7 81.21 0.00 0.00
March 0.770310E+10 -0.754148E+10 0.00 0.00 744.00 0.00 -161627071.6 81.21 0.00 0.00
April 0.746479E+10 -0.730858E+10 0.00 0.00 720.00 0.00 -156206172.6 81.21 0.00 0.00
May 0.770441E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161625235.2 81.21 0.00 0.00
June 0.745681E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156288010.6 81.21 0.00 0.00
July 0.771231E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161464936.7 81.21 0.00 0.00
August 0.770424E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161431690.8 81.21 0.00 0.00
September 0.746630E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156367792.4 81.21 0.00 0.00
October 0.770304E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161604153.9 81.21 0.00 0.00
November 0.744886E+10 -0.729242E+10 0.00 0.00 720.00 0.00 -156440702.0 81.21 0.00 0.00
December 0.771281E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -161946081.8 81.21 0.00 0.00
                     
Annual Sum or Average 0.907440E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190360E+10 81.21 0.00 0.00
Minimum of Months 0.696251E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -162070961.1 81.21 0.00 0.00
Maximum of Months 0.771281E+10 -0.681598E+10 0.00 0.00 744.00 0.00 -146530927.7 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.122412E+12 -0.120669E+12 0.00 0.00 744.00 0.00 -0.174287E+10 81.27 0.00 0.00
February 0.111348E+12 -0.109763E+12 0.00 0.00 672.00 0.00 -0.158483E+10 81.27 0.00 0.00
March 0.121356E+12 -0.119595E+12 0.00 0.00 744.00 0.00 -0.176110E+10 81.27 0.00 0.00
April 0.113317E+12 -0.111608E+12 0.00 0.00 720.00 0.00 -0.170857E+10 81.26 0.00 0.00
May 0.111638E+12 -0.109865E+12 0.00 0.00 744.00 0.00 -0.177312E+10 81.25 0.00 0.00
June 0.102997E+12 -0.101291E+12 0.00 0.00 720.00 0.00 -0.170621E+10 81.26 0.00 0.00
July 0.102885E+12 -0.101134E+12 0.00 0.00 744.00 0.00 -0.175160E+10 81.25 0.00 0.00
August 0.101951E+12 -0.100211E+12 0.00 0.00 744.00 0.00 -0.173995E+10 81.24 0.00 0.00
September 0.100549E+12 -0.988729E+11 0.00 0.00 720.00 0.00 -0.167587E+10 81.24 0.00 0.00
October 0.108194E+12 -0.106466E+12 0.00 0.00 744.00 0.00 -0.172868E+10 81.25 0.00 0.00
November 0.109994E+12 -0.108321E+12 0.00 0.00 720.00 0.00 -0.167284E+10 81.25 0.00 0.00
December 0.118845E+12 -0.117112E+12 0.00 0.00 744.00 0.00 -0.173278E+10 81.26 0.00 0.00
                     
Annual Sum or Average 0.132549E+13 -0.130491E+13 0.00 0.00 8760.00 0.00 -0.205784E+11 81.26 0.00 0.00
Minimum of Months 0.100549E+12 -0.120669E+12 0.00 0.00 672.00 0.00 -0.177312E+10 81.24 0.00 0.00
Maximum of Months 0.122412E+12 -0.988729E+11 0.00 0.00 744.00 0.00 -0.158483E+10 81.27 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.730172E+11 -0.715324E+11 0.00 0.00 744.00 0.00 -0.148482E+10 58.98 0.00 0.00
February 0.666263E+11 -0.652706E+11 0.00 0.00 672.00 0.00 -0.135571E+10 58.98 0.00 0.00
March 0.721955E+11 -0.706853E+11 0.00 0.00 744.00 0.00 -0.151023E+10 58.98 0.00 0.00
April 0.663062E+11 -0.648385E+11 0.00 0.00 720.00 0.00 -0.146770E+10 58.98 0.00 0.00
May 0.638372E+11 -0.623098E+11 0.00 0.00 744.00 0.00 -0.152744E+10 58.98 0.00 0.00
June 0.574492E+11 -0.559847E+11 0.00 0.00 720.00 0.00 -0.146448E+10 58.98 0.00 0.00
July 0.562466E+11 -0.547489E+11 0.00 0.00 744.00 0.00 -0.149765E+10 58.98 0.00 0.00
August 0.554892E+11 -0.540072E+11 0.00 0.00 744.00 0.00 -0.148197E+10 58.98 0.00 0.00
September 0.552956E+11 -0.538727E+11 0.00 0.00 720.00 0.00 -0.142287E+10 58.98 0.00 0.00
October 0.608118E+11 -0.593457E+11 0.00 0.00 744.00 0.00 -0.146606E+10 58.98 0.00 0.00
November 0.634077E+11 -0.619891E+11 0.00 0.00 720.00 0.00 -0.141852E+10 58.98 0.00 0.00
December 0.699696E+11 -0.684984E+11 0.00 0.00 744.00 0.00 -0.147119E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.760652E+12 -0.743083E+12 0.00 0.00 8760.00 0.00 -0.175686E+11 58.98 0.00 0.00
Minimum of Months 0.552956E+11 -0.715324E+11 0.00 0.00 672.00 0.00 -0.152744E+10 58.98 0.00 0.00
Maximum of Months 0.730172E+11 -0.538727E+11 0.00 0.00 744.00 0.00 -0.135571E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.87 0.86 01-JAN-07:49 6327.30 37.28 197.00 252.33 3020.13 34.08 191.17 193.50
February 216.00 0.87 0.86 01-FEB-07:49 9260.69 37.90 208.33 263.50 1310.89 27.60 211.00 232.17
March 275.00 0.87 0.86 01-MAR-06:00 4474.08 26.11 176.83 331.33 810.65 23.00 218.17 278.33
April 261.17 0.87 0.86 01-APR-14:39 1590.17 20.85 112.50 349.17 647.87 22.57 211.17 291.33
May 372.00 0.87 0.86 01-MAY-06:10 1438.84 20.57 185.67 402.50 571.11 22.27 256.67 337.67
June 351.83 0.87 0.86 01-JUN-05:00 1364.46 20.48 151.00 393.83 550.45 22.21 264.00 331.67
July 365.17 0.87 0.86 01-JUL-06:19 1521.30 20.64 170.33 401.33 602.26 22.36 281.67 334.83
August 389.17 0.87 0.86 01-AUG-06:19 1629.04 20.91 206.50 378.17 659.06 22.62 316.00 333.33
September 285.33 0.87 0.86 01-SEP-06:40 1812.87 21.02 133.00 332.17 731.62 22.78 243.00 283.33
October 305.50 0.87 0.86 01-OCT-14:39 8947.34 36.00 288.83 313.33 1120.41 25.31 281.00 286.83
November 240.83 0.87 0.86 01-NOV-06:00 6277.61 36.73 235.17 261.83 1666.11 30.22 227.33 234.00
December 211.17 0.87 0.86 01-DEC-07:40 5876.84 38.26 208.00 251.33 4539.30 38.25 207.83 212.83
                         
Annual Sum or Average 3472.67 0.87     3777.10 26.69 2273.17 3930.83 1172.35 25.24 2909.00 3349.83
Minimum of Months 199.50 0.87 0.86   1364.46 20.48 112.50 251.33 550.45 22.21 191.17 193.50
Maximum of Months 389.17 0.87 0.86   9260.69 38.26 288.83 402.50 4539.30 38.25 316.00 337.67



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.25 0.22 01-JAN-07:49 6803.44 37.34 197.00 261.67 3497.01 34.03 194.33 228.00
February 216.00 0.25 0.22 01-FEB-07:40 9805.53 37.99 208.50 271.17 1855.26 27.25 202.67 250.17
March 275.00 0.25 0.22 01-MAR-06:00 4919.37 26.21 171.67 339.50 1254.12 22.98 236.83 311.33
April 261.17 0.26 0.22 01-APR-06:30 1934.36 21.10 116.67 361.00 991.20 22.68 257.33 327.67
May 372.00 0.25 0.22 01-MAY-05:49 1686.33 21.11 196.83 415.17 817.74 22.63 290.33 379.50
June 351.83 0.26 0.22 01-JUN-05:30 1601.14 21.03 194.50 409.00 786.32 22.58 298.67 368.33
July 365.17 0.25 0.22 01-JUL-05:30 1773.34 21.17 212.50 419.00 853.38 22.72 310.17 374.83
August 389.17 0.26 0.22 01-AUG-05:49 1946.92 21.24 219.00 387.83 976.01 22.80 331.33 363.67
September 285.33 0.26 0.22 01-SEP-06:10 2210.45 21.15 132.00 343.83 1128.10 22.78 252.33 312.50
October 305.50 0.24 0.22 01-OCT-14:39 9491.56 36.04 275.17 318.83 1662.93 25.12 286.33 302.83
November 240.83 0.25 0.22 01-NOV-06:49 6721.59 36.80 235.17 269.67 2106.14 30.11 234.67 252.83
December 211.17 0.26 0.22 01-DEC-07:30 6350.49 38.32 208.00 258.67 5010.84 38.25 205.67 237.17
                         
Annual Sum or Average 3472.67 0.25     4152.25 26.96 2367.00 4055.33 1546.28 25.33 3100.67 3708.83
Minimum of Months 199.50 0.24 0.22   1601.14 21.03 116.67 258.67 786.32 22.58 194.33 228.00
Maximum of Months 389.17 0.26 0.22   9805.53 38.32 275.17 419.00 5010.84 38.25 331.33 379.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.66 0.60 01-JAN-08:00 477.96 15.57 0.00 238.67 230.54 18.97 0.00 134.67
February 216.00 0.65 0.60 01-FEB-08:50 491.26 16.26 0.00 252.50 251.89 19.71 0.17 175.00
March 275.00 0.63 0.60 01-MAR-07:30 673.57 17.59 0.00 329.83 324.85 20.82 69.50 259.33
April 261.17 0.62 0.60 01-APR-14:39 742.16 18.17 0.00 358.83 357.92 21.38 123.17 310.17
May 372.00 0.61 0.60 01-MAY-05:49 1019.23 18.85 0.00 420.33 455.32 22.73 265.33 380.17
June 351.83 0.61 0.60 01-JUN-04:00 1131.62 19.95 29.00 413.50 491.90 23.75 284.17 381.17
July 365.17 0.61 0.60 01-JUL-04:00 1137.30 18.90 0.00 422.83 490.66 23.39 292.33 382.83
August 389.17 0.62 0.60 01-AUG-05:40 901.52 18.60 0.00 390.50 417.11 21.81 269.50 361.33
September 285.33 0.63 0.60 01-SEP-06:19 680.07 17.80 0.00 337.67 332.33 21.03 99.00 283.50
October 305.50 0.63 0.60 01-OCT-14:39 615.13 17.36 0.00 304.67 315.23 20.71 31.00 257.33
November 240.83 0.65 0.60 01-NOV-07:30 537.09 16.13 0.00 252.83 251.82 19.43 0.00 172.50
December 211.17 0.69 0.60 01-DEC-09:09 378.48 14.70 0.00 228.50 190.26 18.25 0.00 92.33
                         
Annual Sum or Average 3472.67 0.63     781.88 17.78 29.00 3950.67 362.58 21.32 1434.17 3190.33
Minimum of Months 199.50 0.61 0.60   378.48 14.70 0.00 228.50 190.26 18.25 0.00 92.33
Maximum of Months 389.17 0.69 0.60   1137.30 19.95 29.00 422.83 491.90 23.75 292.33 382.83



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.66 0.60 01-JAN-08:00 477.96 15.57 0.00 238.67 230.54 18.97 0.00 134.67
February 216.00 0.65 0.60 01-FEB-08:50 491.26 16.26 0.00 252.50 251.89 19.71 0.17 175.00
March 275.00 0.63 0.60 01-MAR-07:30 673.57 17.59 0.00 329.83 324.85 20.82 69.50 259.33
April 261.17 0.62 0.60 01-APR-14:39 742.16 18.17 0.00 358.83 357.92 21.38 123.17 310.17
May 372.00 0.61 0.60 01-MAY-05:49 1019.23 18.85 0.00 420.33 455.32 22.73 265.33 380.17
June 351.83 0.61 0.60 01-JUN-04:00 1131.62 19.95 29.00 413.50 491.90 23.75 284.17 381.17
July 365.17 0.61 0.60 01-JUL-04:00 1137.30 18.90 0.00 422.83 490.66 23.39 292.33 382.83
August 389.17 0.62 0.60 01-AUG-05:40 901.52 18.60 0.00 390.50 417.11 21.81 269.50 361.33
September 285.33 0.63 0.60 01-SEP-06:19 680.07 17.80 0.00 337.67 332.33 21.03 99.00 283.50
October 305.50 0.63 0.60 01-OCT-14:39 615.13 17.36 0.00 304.67 315.23 20.71 31.00 257.33
November 240.83 0.65 0.60 01-NOV-07:30 537.09 16.13 0.00 252.83 251.82 19.43 0.00 172.50
December 211.17 0.69 0.60 01-DEC-09:09 378.48 14.70 0.00 228.50 190.26 18.25 0.00 92.33
                         
Annual Sum or Average 3472.67 0.63     781.88 17.78 29.00 3950.67 362.58 21.32 1434.17 3190.33
Minimum of Months 199.50 0.61 0.60   378.48 14.70 0.00 228.50 190.26 18.25 0.00 92.33
Maximum of Months 389.17 0.69 0.60   1137.30 19.95 29.00 422.83 491.90 23.75 292.33 382.83



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.458142E+11 111521.32 17-JAN-18:20 0.00 0.00 0.00 0.00 0.00
February 0.435123E+11 110904.28 18-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.294767E+11 131917.74 23-MAR-20:17 0.00 0.00 0.00 0.00 0.00
April 0.253747E+11 127450.21 11-APR-23:03 0.00 0.00 0.00 0.00 0.00
May 0.773333E+10 108270.65 15-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 0.255310E+09 25003.16 01-JUN-14:42 0.00 0.00 0.00 0.00 0.00
July 53074649.96 16457.65 11-JUL-18:00 0.00 0.00 0.00 0.00 0.00
August 0.346831E+09 34341.95 24-AUG-18:50 0.00 0.00 0.00 0.00 0.00
September 0.986717E+09 78064.96 24-SEP-05:47 0.00 0.00 0.00 0.00 0.00
October 0.117657E+11 134173.68 30-OCT-23:49 0.00 0.00 0.00 0.00 0.00
November 0.284123E+11 139432.63 01-NOV-06:16 0.00 0.00 0.00 0.00 0.00
December 0.201560E+11 140036.81 04-DEC-07:33 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.213887E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 53074649.96 16457.65   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.458142E+11 140036.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.309332E+10 2663.96 02-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.241180E+10 2663.89 06-FEB-05:10 0.00 0.00 0.00 0.00 0.00
March 0.154027E+10 2805.61 05-MAR-09:04 0.00 0.00 0.00 0.00 0.00
April 0.870167E+09 2621.21 18-APR-08:06 0.00 0.00 0.00 0.00 0.00
May 0.246497E+09 1727.80 04-MAY-02:23 0.00 0.00 0.00 0.00 0.00
June 131561.39 68.36 07-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 40999743.47 1526.75 24-SEP-05:12 0.00 0.00 0.00 0.00 0.00
October 0.155328E+09 2422.46 27-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.145108E+10 3021.73 13-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.247162E+10 2858.78 05-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122812E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.309332E+10 3021.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123780E+09 618.11 03-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 92948675.76 593.74 28-FEB-10:20 0.00 0.00 0.00 0.00 0.00
March 5186992.93 277.34 17-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 233481.88 67.07 21-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 5181843.41 301.27 26-NOV-13:20 0.00 0.00 0.00 0.00 0.00
December 47597561.28 401.94 12-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.274928E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.123780E+09 618.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128296E+10 1276.17 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.123789E+10 1242.60 06-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 0.420853E+09 1188.59 20-MAR-14:44 0.00 0.00 0.00 0.00 0.00
April 67413552.53 768.47 21-APR-10:36 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.293524E+09 958.87 29-NOV-09:39 0.00 0.00 0.00 0.00 0.00
December 0.777371E+09 1154.98 08-DEC-15:36 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.408000E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128296E+10 1276.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.124784E+10 994.29 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.117775E+10 982.30 06-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.539194E+09 854.65 20-MAR-14:44 0.00 0.00 0.00 0.00 0.00
April 0.145554E+09 804.80 14-APR-08:47 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.389153E+09 797.99 29-NOV-09:39 0.00 0.00 0.00 0.00 0.00
December 0.903316E+09 880.98 08-DEC-15:36 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.440281E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124784E+10 994.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.252885E+09 2713.72 24-JAN-03:03 0.00 0.00 0.00 0.00 0.00
February 0.260248E+09 2354.04 06-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.143818E+09 8215.48 04-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 70222816.21 8126.96 25-APR-02:55 0.00 0.00 0.00 0.00 0.00
May 39292581.29 8003.05 17-MAY-03:45 0.00 0.00 0.00 0.00 0.00
June 482145.47 330.62 03-JUN-05:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 4477634.68 7573.48 30-SEP-04:58 0.00 0.00 0.00 0.00 0.00
October 50289807.13 8425.62 31-OCT-00:27 0.00 0.00 0.00 0.00 0.00
November 0.127408E+09 8174.03 09-NOV-03:30 0.00 0.00 0.00 0.00 0.00
December 0.190018E+09 1995.13 01-DEC-03:57 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113914E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.260248E+09 8425.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.194891E+10 6498.19 09-JAN-12:30 0.00 0.00 0.00 0.00 0.00
February 0.115123E+10 6079.15 28-FEB-09:54 0.00 0.00 0.00 0.00 0.00
March 0.584353E+09 4289.09 06-MAR-11:45 0.00 0.00 0.00 0.00 0.00
April 0.272229E+09 8243.17 14-APR-08:47 0.00 0.00 0.00 0.00 0.00
May 55249632.91 2728.51 04-MAY-09:55 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 394316.57 568.92 26-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 4703759.96 1115.20 27-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.426281E+09 7935.80 13-NOV-07:48 0.00 0.00 0.00 0.00 0.00
December 0.131491E+10 8887.24 05-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.575825E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.194891E+10 8887.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.945417E+09 9988.15 03-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.502877E+09 7420.10 28-FEB-10:20 0.00 0.00 0.00 0.00 0.00
March 33582912.26 3836.41 17-MAR-12:30 0.00 0.00 0.00 0.00 0.00
April 1175578.47 646.76 21-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 21525642.04 3073.50 26-NOV-13:40 0.00 0.00 0.00 0.00 0.00
December 0.393657E+09 6536.14 11-DEC-15:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.189823E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.945417E+09 9988.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.925682E+10 9308.00 09-JAN-13:10 0.00 0.00 0.00 0.00 0.00
February 0.719428E+10 8158.55 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.265835E+10 10039.14 01-MAR-07:37 0.00 0.00 0.00 0.00 0.00
April 0.731819E+09 8190.38 21-APR-10:41 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.322976E+10 10043.45 13-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.694440E+10 11062.13 05-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.300154E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.925682E+10 11062.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.520549E+10 5169.44 02-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.450357E+10 5119.04 06-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.175980E+10 4872.15 01-MAR-07:37 0.00 0.00 0.00 0.00 0.00
April 0.479811E+09 4576.81 14-APR-08:47 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 28433877.97 3360.55 31-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 0.177005E+10 5182.61 13-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.389507E+10 5044.20 05-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176422E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.520549E+10 5182.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 241443.52 804.81 25-APR-02:55 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 122358.95 611.79 31-OCT-00:27 0.00 0.00 0.00 0.00 0.00
November 115915.69 386.39 09-NOV-02:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 479718.16     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 241443.52 804.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.468420E+10 10934.03 02-JAN-09:00 0.00 0.00 0.00 0.00 0.00
February 0.470086E+10 12033.19 06-FEB-08:20 0.00 0.00 0.00 0.00 0.00
March 0.483324E+09 4213.88 23-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 5557.80 0.39 16-APR-20:05 0.00 0.00 0.00 0.00 0.00
May 16753.93 0.39 26-MAY-16:50 0.00 0.00 0.00 0.00 0.00
June 16922.63 0.39 18-JUN-16:50 0.00 0.00 0.00 0.00 0.00
July 12149.09 0.39 14-JUL-08:00 0.00 0.00 0.00 0.00 0.00
August 29210.58 62.53 08-AUG-17:13 0.00 0.00 0.00 0.00 0.00
September 74683.95 88.84 19-SEP-15:00 0.00 0.00 0.00 0.00 0.00
October 12063.65 0.39 21-OCT-17:15 0.00 0.00 0.00 0.00 0.00
November 0.379611E+09 4176.02 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.859061E+09 7377.28 31-DEC-24:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.111072E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5557.80 0.39   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.470086E+10 12033.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.537798E+10 6846.65 24-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.443284E+10 6844.97 28-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.219624E+10 6843.68 17-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.956655E+09 6834.95 21-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 84406678.27 4527.48 09-MAY-21:54 0.00 0.00 0.00 0.00 0.00
June 2287921.57 3175.91 07-JUN-21:54 0.00 0.00 0.00 0.00 0.00
July 1811749.13 3284.19 14-JUL-06:24 0.00 0.00 0.00 0.00 0.00
August 1171101.46 2487.38 08-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 9991171.25 3607.13 24-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.189329E+09 4489.69 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.246349E+10 6843.60 25-NOV-19:02 0.00 0.00 0.00 0.00 0.00
December 0.430716E+10 6844.43 29-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.200234E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1171101.46 2487.38   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.537798E+10 6846.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.633492E+10 6827.89 24-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.561005E+10 6826.18 28-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.278324E+10 6825.00 09-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.111567E+10 6824.92 21-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 91416417.01 4666.72 17-MAY-08:53 0.00 0.00 0.00 0.00 0.00
June 2376496.68 3120.16 07-JUN-21:54 0.00 0.00 0.00 0.00 0.00
July 1448627.56 2778.39 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1690373.11 3008.37 20-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 11690275.16 4280.82 28-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 0.363107E+09 6604.56 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.317478E+10 6825.10 28-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.532756E+10 6825.63 30-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.248180E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1448627.56 2778.39   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.633492E+10 6827.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.770019E+10 20224.13 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.219787E+10 16311.79 07-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.227780E+09 9494.20 01-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 63447027.02 5141.08 29-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.288081E+10 15078.35 31-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.130701E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.770019E+10 20224.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.237112E+11 39038.70 08-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.230536E+11 39033.42 09-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.832863E+10 38599.08 16-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.169144E+10 37785.46 21-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.101193E+09 31040.26 03-MAY-15:07 0.00 0.00 0.00 0.00 0.00
June 8733238.96 20607.08 04-JUN-08:56 0.00 0.00 0.00 0.00 0.00
July 8318938.02 18785.58 14-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 22007461.80 17327.19 07-AUG-18:07 0.00 0.00 0.00 0.00 0.00
September 66794436.84 30961.54 12-SEP-06:15 0.00 0.00 0.00 0.00 0.00
October 0.590210E+09 37333.49 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.792213E+10 38777.89 24-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.179461E+11 38939.32 31-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.834504E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8318938.02 17327.19   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.237112E+11 39038.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.534549E+10 6700.71 24-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.433103E+10 6698.97 28-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.231585E+10 6697.61 17-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.971960E+09 6693.21 21-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 96676951.78 3289.43 09-MAY-21:54 0.00 0.00 0.00 0.00 0.00
June 1633192.72 2949.46 07-JUN-21:54 0.00 0.00 0.00 0.00 0.00
July 531608.81 1388.33 22-JUL-21:54 0.00 0.00 0.00 0.00 0.00
August 523317.58 1549.61 27-AUG-21:55 0.00 0.00 0.00 0.00 0.00
September 7848741.92 3232.67 24-SEP-19:44 0.00 0.00 0.00 0.00 0.00
October 0.211749E+09 3858.71 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.232848E+10 6697.54 25-NOV-19:02 0.00 0.00 0.00 0.00 0.00
December 0.425327E+10 6698.41 29-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.198650E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 523317.58 1388.33   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.534549E+10 6700.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.627848E+10 6680.74 24-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.547267E+10 6678.97 28-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.291333E+10 6677.62 08-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.112283E+10 6679.00 21-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.107497E+09 4240.67 09-MAY-21:54 0.00 0.00 0.00 0.00 0.00
June 1631419.82 2892.99 07-JUN-21:54 0.00 0.00 0.00 0.00 0.00
July 344555.07 1195.86 22-JUL-21:54 0.00 0.00 0.00 0.00 0.00
August 509527.35 1461.55 06-AUG-21:55 0.00 0.00 0.00 0.00 0.00
September 10219118.56 3858.51 27-SEP-21:53 0.00 0.00 0.00 0.00 0.00
October 0.383083E+09 6452.97 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.293919E+10 6677.83 28-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.518935E+10 6679.72 25-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.244191E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 344555.07 1195.86   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.627848E+10 6680.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.180782E+10 1991.09 24-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.151425E+10 1990.68 24-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.791831E+09 1990.65 05-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.370011E+09 1990.56 21-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 45394223.32 1310.99 17-MAY-08:53 0.00 0.00 0.00 0.00 0.00
June 502904.42 716.15 07-JUN-21:54 0.00 0.00 0.00 0.00 0.00
July 447141.55 771.58 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 244670.91 973.77 01-AUG-06:54 0.00 0.00 0.00 0.00 0.00
September 6128548.83 928.66 20-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 0.109423E+09 1931.28 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.892058E+09 1991.25 26-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.148632E+10 1990.64 30-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.702443E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 244670.91 716.15   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.180782E+10 1991.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.209411E+10 1984.07 24-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.186196E+10 1983.66 24-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.975391E+09 1983.62 05-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.423067E+09 1983.58 21-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 48796903.07 1177.32 04-MAY-08:63 0.00 0.00 0.00 0.00 0.00
June 522662.28 750.20 06-JUN-08:54 0.00 0.00 0.00 0.00 0.00
July 480575.80 824.67 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 530352.00 686.74 23-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 9472616.99 1220.11 10-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 0.187366E+09 1952.89 29-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.112609E+10 1984.24 26-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.180093E+10 1983.68 04-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.852871E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 480575.80 686.74   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.209411E+10 1984.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.552417E+10 9416.60 03-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.403068E+10 9414.17 28-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.220675E+10 9411.76 16-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.106681E+10 9393.81 21-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 95097764.81 4654.99 07-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 4457997.94 4758.66 07-JUN-21:54 0.00 0.00 0.00 0.00 0.00
July 2485646.09 4638.26 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1941044.58 3168.18 13-AUG-06:54 0.00 0.00 0.00 0.00 0.00
September 8344010.78 3612.55 17-SEP-21:55 0.00 0.00 0.00 0.00 0.00
October 0.122932E+09 4011.33 28-OCT-18:03 0.00 0.00 0.00 0.00 0.00
November 0.193480E+10 9339.52 28-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.406717E+10 9413.30 12-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.190656E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1941044.58 3168.18   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.552417E+10 9416.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.216898E+09 0.216898E+09 29707.88 21-JAN-23:00 29707.88 0.02
February 0.00 0.00 0.216674E+09 0.216674E+09 23332.73 16-FEB-21:07 23332.73 0.01
March 0.00 0.00 0.358594E+10 0.355603E+10 130712.11 27-MAR-16:00 130712.11 0.05
April 0.00 0.00 0.343480E+11 0.340976E+11 210469.64 09-APR-10:50 140487.87 0.21
May 0.00 0.00 0.125664E+12 0.108539E+12 291325.25 31-MAY-17:20 164505.96 0.47
June 0.00 0.00 0.516176E+12 0.310625E+12 471530.61 24-JUN-17:20 175635.76 0.92
July 0.00 0.00 0.811626E+12 0.444384E+12 486469.21 27-JUL-21:00 213942.70 1.00
August 0.00 0.00 0.661412E+12 0.436384E+12 498203.56 11-AUG-22:00 212089.05 0.98
September 0.00 0.00 0.360155E+12 0.249856E+12 476607.58 13-SEP-21:00 217903.54 0.83
October 0.00 0.00 0.124982E+12 0.808578E+11 285266.21 05-OCT-19:10 144214.47 0.44
November 0.00 0.00 0.365666E+10 0.336387E+10 64285.84 04-NOV-10:50 64285.84 0.05
December 0.00 0.00 0.441034E+09 0.441034E+09 35746.95 17-DEC-21:40 35746.95 0.02
                 
Annual Sum or Average 0.00 0.00 0.264248E+13 0.167254E+13       0.42
Minimum of Months 0.00 0.00 0.216674E+09 0.216674E+09 23332.73   23332.73 0.01
Maximum of Months 0.00 0.00 0.811626E+12 0.444384E+12 498203.56   217903.54 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 9597.49 9597.49 31.99 24-JAN-19:55 31.99 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.697388E+09 0.589428E+09 32905.75 27-MAR-13:00 21433.50 0.02
April 0.00 0.00 0.635538E+10 0.618073E+10 40374.00 09-APR-10:55 24738.54 0.16
May 0.00 0.00 0.233997E+11 0.197067E+11 52967.83 31-MAY-16:43 28274.13 0.43
June 0.00 0.00 0.987929E+11 0.559559E+11 81926.34 24-JUN-17:20 28278.14 0.92
July 0.00 0.00 0.135125E+12 0.753175E+11 81374.00 26-JUL-17:10 28474.65 1.00
August 0.00 0.00 0.108838E+12 0.714963E+11 78804.96 06-AUG-06:40 28236.71 0.99
September 0.00 0.00 0.681274E+11 0.451308E+11 78294.96 22-SEP-17:00 27809.47 0.83
October 0.00 0.00 0.246553E+11 0.148233E+11 52291.09 24-OCT-14:00 26085.88 0.42
November 0.00 0.00 0.605285E+09 0.541329E+09 12350.93 10-NOV-08:00 4466.59 0.03
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.466597E+12 0.289742E+12       0.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.135125E+12 0.753175E+11 81926.34   28474.65 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 41260615.74 40736214.82 15761.45 17-JAN-16:01 15761.45 0.00
February 0.00 0.00 0.113137E+09 0.113137E+09 15763.03 20-FEB-16:01 15763.03 0.00
March 0.00 0.00 0.781929E+09 0.705571E+09 16719.45 27-MAR-15:02 14193.05 0.05
April 0.00 0.00 0.186412E+10 0.122273E+10 18425.37 27-APR-18:21 16435.60 0.27
May 0.00 0.00 0.366506E+10 0.218933E+10 20629.51 31-MAY-21:51 15409.99 0.52
June 0.00 0.00 0.717652E+10 0.426289E+10 21995.00 21-JUN-21:51 13306.72 0.62
July 0.00 0.00 0.106188E+11 0.643056E+10 22719.58 05-JUL-21:51 13358.97 0.79
August 0.00 0.00 0.112908E+11 0.742293E+10 21889.83 10-AUG-21:51 14094.88 0.80
September 0.00 0.00 0.555702E+10 0.324845E+10 21453.25 13-SEP-21:51 13087.32 0.60
October 0.00 0.00 0.358995E+10 0.212271E+10 20600.99 05-OCT-21:51 13900.97 0.42
November 0.00 0.00 0.325491E+09 0.212436E+09 15775.73 03-NOV-15:01 15775.73 0.08
December 0.00 0.00 49033308.87 48169176.85 15686.88 17-DEC-16:01 15686.88 0.00
                 
Annual Sum or Average 0.00 0.00 0.450731E+11 0.280197E+11       0.35
Minimum of Months 0.00 0.00 41260615.74 40736214.82 15686.88   13087.32 0.00
Maximum of Months 0.00 0.00 0.112908E+11 0.742293E+10 22719.58   16435.60 0.80



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3855089.01 3698308.04 8823.29 17-JAN-16:01 8823.29 0.00
February 0.00 0.00 17018556.57 17017562.22 14320.68 20-FEB-16:01 14320.68 0.00
March 0.00 0.00 0.333316E+09 0.301051E+09 15818.19 27-MAR-15:02 13144.61 0.02
April 0.00 0.00 0.124655E+10 0.783829E+09 17815.18 27-APR-18:21 15812.76 0.22
May 0.00 0.00 0.322403E+10 0.187056E+10 19995.30 31-MAY-21:51 14905.88 0.50
June 0.00 0.00 0.679861E+10 0.400313E+10 21415.02 21-JUN-21:51 12955.07 0.62
July 0.00 0.00 0.100941E+11 0.603536E+10 22068.86 05-JUL-21:51 12968.64 0.79
August 0.00 0.00 0.100192E+11 0.631943E+10 21157.94 10-AUG-21:51 13554.57 0.79
September 0.00 0.00 0.426194E+10 0.227072E+10 20801.63 06-SEP-21:51 13724.38 0.56
October 0.00 0.00 0.180361E+10 0.893162E+09 19579.51 05-OCT-21:51 12962.28 0.33
November 0.00 0.00 59831274.48 40222056.40 15346.86 03-NOV-15:01 15346.86 0.02
December 0.00 0.00 2129852.83 1760176.73 4516.45 17-DEC-16:01 4516.45 0.00
                 
Annual Sum or Average 0.00 0.00 0.378642E+11 0.225400E+11       0.32
Minimum of Months 0.00 0.00 2129852.83 1760176.73 4516.45   4516.45 0.00
Maximum of Months 0.00 0.00 0.100941E+11 0.631943E+10 22068.86   15812.76 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.130263E+09 0.130263E+09 7851.58 19-JAN-14:27 7851.58 0.00
February 0.00 0.00 0.957213E+09 0.957213E+09 18601.57 20-FEB-13:30 18601.57 0.00
March 0.00 0.00 0.303098E+10 0.299709E+10 30593.29 03-MAR-13:30 30593.29 0.00
April 0.00 0.00 0.656680E+10 0.457442E+10 41050.36 08-APR-12:20 34720.69 0.13
May 0.00 0.00 0.105050E+11 0.679988E+10 29373.35 31-MAY-12:30 17485.25 0.25
June 0.00 0.00 0.221816E+11 0.908612E+10 33853.09 19-JUN-12:50 22664.04 0.64
July 0.00 0.00 0.395828E+11 0.171644E+11 35873.57 08-JUL-12:00 23687.64 0.91
August 0.00 0.00 0.484406E+11 0.274412E+11 46743.89 16-AUG-12:30 39160.45 0.93
September 0.00 0.00 0.313142E+11 0.185488E+11 52326.91 07-SEP-14:10 40807.20 0.66
October 0.00 0.00 0.317291E+11 0.233585E+11 53362.96 04-OCT-15:20 40727.03 0.40
November 0.00 0.00 0.595808E+10 0.526646E+10 42750.64 02-NOV-12:40 42750.64 0.06
December 0.00 0.00 0.233834E+10 0.233834E+10 31259.79 17-DEC-13:30 31259.79 0.00
                 
Annual Sum or Average 0.00 0.00 0.202735E+12 0.118663E+12       0.33
Minimum of Months 0.00 0.00 0.130263E+09 0.130263E+09 7851.58   7851.58 0.00
Maximum of Months 0.00 0.00 0.484406E+11 0.274412E+11 53362.96   42750.64 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.168112E+09 58700258.28 24360.45 19-JAN-19:03 24360.45 0.02
February 0.00 0.00 62100756.94 58122841.49 28292.89 20-FEB-09:02 28292.89 0.00
March 0.00 0.00 0.214719E+10 0.127831E+10 82192.60 02-MAR-21:42 82192.60 0.11
April 0.00 0.00 0.113307E+11 0.623725E+10 90425.09 27-APR-18:21 77821.79 0.34
May 0.00 0.00 0.281258E+11 0.171175E+11 108263.62 31-MAY-21:51 80619.90 0.50
June 0.00 0.00 0.430857E+11 0.277804E+11 121147.97 24-JUN-21:51 70979.22 0.47
July 0.00 0.00 0.620867E+11 0.400743E+11 123891.67 05-JUL-21:51 69917.73 0.65
August 0.00 0.00 0.555811E+11 0.358818E+11 116418.19 10-AUG-21:51 73423.07 0.61
September 0.00 0.00 0.305037E+11 0.178918E+11 117944.00 13-SEP-21:51 70496.42 0.44
October 0.00 0.00 0.148694E+11 0.782141E+10 108755.15 05-OCT-21:51 71311.89 0.33
November 0.00 0.00 0.305489E+10 0.145012E+10 80949.60 11-NOV-09:02 80949.60 0.18
December 0.00 0.00 0.140957E+09 94114166.63 35463.36 25-DEC-09:02 27031.30 0.01
                 
Annual Sum or Average 0.00 0.00 0.251156E+12 0.155744E+12       0.31
Minimum of Months 0.00 0.00 62100756.94 58122841.49 24360.45   24360.45 0.00
Maximum of Months 0.00 0.00 0.620867E+11 0.400743E+11 123891.67   82192.60 0.65



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 85495252.77 80450946.33 10405.53 17-JAN-16:01 10405.53 0.00
February 0.00 0.00 0.140679E+09 0.140549E+09 14149.67 25-FEB-09:02 14149.67 0.00
March 0.00 0.00 0.683041E+09 0.617701E+09 14831.80 27-MAR-15:02 12204.59 0.05
April 0.00 0.00 0.198946E+10 0.130790E+10 16868.16 08-APR-08:51 15925.20 0.30
May 0.00 0.00 0.399063E+10 0.250216E+10 19863.27 31-MAY-08:32 16896.01 0.54
June 0.00 0.00 0.679433E+10 0.396520E+10 20723.40 25-JUN-07:51 13606.29 0.64
July 0.00 0.00 0.104109E+11 0.623657E+10 20744.27 01-JUL-08:32 16287.55 0.80
August 0.00 0.00 0.110731E+11 0.719138E+10 20478.84 12-AUG-08:61 13713.14 0.81
September 0.00 0.00 0.572160E+10 0.344233E+10 20118.25 04-SEP-08:32 16771.18 0.63
October 0.00 0.00 0.356015E+10 0.217931E+10 19259.10 24-OCT-08:51 14306.21 0.43
November 0.00 0.00 0.517606E+09 0.369301E+09 14506.59 03-NOV-15:01 14506.59 0.09
December 0.00 0.00 0.161465E+09 0.153425E+09 14076.03 17-DEC-09:02 14076.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.451285E+11 0.281863E+11       0.36
Minimum of Months 0.00 0.00 85495252.77 80450946.33 10405.53   10405.53 0.00
Maximum of Months 0.00 0.00 0.110731E+11 0.719138E+10 20744.27   16896.01 0.81



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4714085.88 2551676.07 2669.26 26-JAN-09:03 2669.26 0.00
February 0.00 0.00 21192545.54 21192545.54 10261.68 19-FEB-09:02 10261.68 0.00
March 0.00 0.00 0.266214E+09 0.229633E+09 13911.14 29-MAR-08:62 13911.14 0.02
April 0.00 0.00 0.133328E+10 0.831800E+09 16283.19 08-APR-08:51 15248.87 0.25
May 0.00 0.00 0.351664E+10 0.215623E+10 19348.41 31-MAY-08:32 16438.95 0.52
June 0.00 0.00 0.641026E+10 0.368773E+10 20028.91 25-JUN-07:51 13338.45 0.64
July 0.00 0.00 0.988022E+10 0.580870E+10 20174.01 01-JUL-08:32 15869.01 0.80
August 0.00 0.00 0.979587E+10 0.604671E+10 19944.99 12-AUG-08:61 13341.88 0.81
September 0.00 0.00 0.440549E+10 0.243052E+10 19589.92 06-SEP-08:32 16289.73 0.59
October 0.00 0.00 0.178529E+10 0.979052E+09 18394.85 25-OCT-08:51 13623.06 0.32
November 0.00 0.00 0.157015E+09 87346622.69 13449.52 11-NOV-09:02 12353.97 0.04
December 0.00 0.00 11366206.49 10060656.72 4996.30 17-DEC-09:02 4996.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.375876E+11 0.222915E+11       0.34
Minimum of Months 0.00 0.00 4714085.88 2551676.07 2669.26   2669.26 0.00
Maximum of Months 0.00 0.00 0.988022E+10 0.604671E+10 20174.01   16438.95 0.81



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 10726546.90 10622954.20 4131.40 17-JAN-16:01 4131.40 0.00
February 0.00 0.00 30267576.11 30267576.11 4131.82 20-FEB-16:01 4131.82 0.00
March 0.00 0.00 0.203073E+09 0.185008E+09 4414.68 27-MAR-15:02 3770.29 0.04
April 0.00 0.00 0.483204E+09 0.330081E+09 4888.31 27-APR-18:21 4407.80 0.25
May 0.00 0.00 0.963965E+09 0.607092E+09 5546.85 31-MAY-21:51 4106.35 0.49
June 0.00 0.00 0.190758E+10 0.115051E+10 5931.74 24-JUN-21:51 3272.66 0.63
July 0.00 0.00 0.279613E+10 0.170878E+10 6145.82 05-JUL-21:51 3446.11 0.79
August 0.00 0.00 0.293750E+10 0.193751E+10 5902.47 10-AUG-21:51 3668.06 0.80
September 0.00 0.00 0.140756E+10 0.831042E+09 5813.15 13-SEP-21:51 3325.12 0.59
October 0.00 0.00 0.838486E+09 0.499503E+09 5487.31 05-OCT-21:51 3743.31 0.38
November 0.00 0.00 63145484.51 44254208.64 4135.06 03-NOV-15:01 4135.06 0.05
December 0.00 0.00 9880437.26 9688432.65 4130.20 17-DEC-16:01 4130.20 0.00
                 
Annual Sum or Average 0.00 0.00 0.116515E+11 0.734436E+10       0.34
Minimum of Months 0.00 0.00 9880437.26 9688432.65 4130.20   3272.66 0.00
Maximum of Months 0.00 0.00 0.293750E+10 0.193751E+10 6145.82   4407.80 0.80



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 524483.94 482097.37 1353.64 17-JAN-16:01 1353.64 0.00
February 0.00 0.00 2155926.38 2155926.38 3208.76 20-FEB-16:01 3208.76 0.00
March 0.00 0.00 80018211.96 72406746.23 4159.59 27-MAR-15:02 3473.55 0.02
April 0.00 0.00 0.316726E+09 0.208058E+09 4756.48 27-APR-18:21 4274.76 0.20
May 0.00 0.00 0.844299E+09 0.519831E+09 5381.78 31-MAY-21:51 3984.85 0.46
June 0.00 0.00 0.181075E+10 0.108059E+10 5751.65 24-JUN-21:51 3161.72 0.62
July 0.00 0.00 0.266062E+10 0.159986E+10 5960.66 05-JUL-21:51 3340.42 0.79
August 0.00 0.00 0.260138E+10 0.164964E+10 5699.54 10-AUG-21:51 3515.94 0.79
September 0.00 0.00 0.105488E+10 0.567655E+09 5616.81 13-SEP-21:51 3186.24 0.53
October 0.00 0.00 0.378869E+09 0.187976E+09 5223.34 05-OCT-21:51 3381.47 0.27
November 0.00 0.00 10563544.26 7733680.27 4011.66 03-NOV-15:01 4011.66 0.01
December 0.00 0.00 475791.88 445850.57 618.37 08-DEC-16:03 618.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.976127E+10 0.589684E+10       0.31
Minimum of Months 0.00 0.00 475791.88 445850.57 618.37   618.37 0.00
Maximum of Months 0.00 0.00 0.266062E+10 0.164964E+10 5960.66   4274.76 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.914772E+09 0.908162E+09 19355.94 19-JAN-16:01 19355.94 0.00
February 0.00 0.00 0.133966E+10 0.133939E+10 19358.27 20-FEB-16:01 19358.27 0.00
March 0.00 0.00 0.247373E+10 0.219413E+10 20243.42 27-MAR-15:02 17977.90 0.11
April 0.00 0.00 0.334134E+10 0.227840E+10 21065.74 09-APR-18:11 18638.87 0.32
May 0.00 0.00 0.486805E+10 0.283165E+10 24375.77 31-MAY-21:51 17996.30 0.55
June 0.00 0.00 0.859848E+10 0.485274E+10 27253.82 24-JUN-21:51 15730.97 0.61
July 0.00 0.00 0.135292E+11 0.804445E+10 27754.29 05-JUL-21:51 15403.87 0.78
August 0.00 0.00 0.151300E+11 0.100140E+11 26681.83 10-AUG-21:51 16569.52 0.80
September 0.00 0.00 0.952228E+10 0.614338E+10 27105.94 13-SEP-21:51 15784.55 0.62
October 0.00 0.00 0.876190E+10 0.636009E+10 26161.77 04-OCT-21:51 18838.80 0.46
November 0.00 0.00 0.231431E+10 0.181883E+10 19362.33 06-NOV-16:02 19362.33 0.18
December 0.00 0.00 0.161493E+10 0.160100E+10 19352.80 03-DEC-16:02 19352.80 0.00
                 
Annual Sum or Average 0.00 0.00 0.724087E+11 0.483862E+11       0.37
Minimum of Months 0.00 0.00 0.914772E+09 0.908162E+09 19352.80   15403.87 0.00
Maximum of Months 0.00 0.00 0.151300E+11 0.100140E+11 27754.29   19362.33 0.80



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 51077.47 197059.18 02-JAN-09:05
February 0.00 0.00 01-FEB-00:03 48864.23 196461.49 06-FEB-09:02
March 0.00 0.00 01-MAR-00:03 22304.28 173765.19 05-MAR-19:02
April 0.00 0.00 01-APR-00:10 13640.75 147518.95 04-APR-18:02
May 0.00 0.00 01-MAY-00:03 3231.25 105213.03 15-MAY-02:00
June 0.00 0.00 01-JUN-00:05 107.71 39463.30 04-JUN-08:56
July 0.00 0.00 01-JUL-00:10 28.49 32003.50 14-JUL-08:07
August 0.00 0.00 01-AUG-00:05 137.68 33854.87 24-AUG-18:50
September 0.00 0.00 01-SEP-00:05 444.55 64180.31 30-SEP-01:10
October 0.00 0.00 01-OCT-00:10 5228.86 140098.87 18-OCT-08:02
November 0.01 57.62 29-NOV-14:00 22656.82 169113.33 20-NOV-19:02
December 0.00 0.00 01-DEC-00:03 31468.22 169292.81 07-DEC-19:02
             
Annual Sum or Average 0.00     16414.95    
Minimum of Months 0.00 0.00   28.49 32003.50  
Maximum of Months 0.01 57.62   51077.47 197059.18  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1731.01 37264.92 19-JAN-19:03 0.00 0.00 01-JAN-00:05
February 2510.95 51576.08 20-FEB-09:02 0.00 0.00 01-FEB-00:03
March 7308.07 250947.51 27-MAR-15:02 0.00 0.00 01-MAR-00:03
April 29417.88 382468.13 07-APR-15:02 0.00 0.00 01-APR-00:10
May 81614.05 472801.22 29-MAY-18:32 0.00 0.00 01-MAY-00:03
June 281501.51 733688.84 15-JUN-21:52 0.00 0.00 01-JUN-00:05
July 417709.41 735308.40 24-JUL-21:52 0.00 0.00 01-JUL-00:10
August 353784.54 767482.59 11-AUG-21:51 0.00 0.00 01-AUG-00:05
September 205224.57 702914.89 07-SEP-21:52 0.00 0.00 01-SEP-00:05
October 84533.44 501851.41 05-OCT-15:03 0.00 0.00 01-OCT-00:10
November 8569.64 156499.23 04-NOV-15:01 0.00 0.00 01-NOV-00:05
December 3393.02 61042.17 25-DEC-09:02 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 124010.94     0.00    
Minimum of Months 1731.01 37264.92   0.00 0.00  
Maximum of Months 417709.41 767482.59   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 28260.32 64428.84 18-JAN-07:14
February 0.00 0.00 01-FEB-00:03 28540.20 66060.69 01-FEB-21:21
March 0.00 0.00 01-MAR-00:03 27934.32 67298.66 02-MAR-07:22
April 0.00 0.00 01-APR-00:10 26550.16 62088.47 11-APR-06:21
May 0.00 0.00 01-MAY-00:03 24817.53 58268.17 02-MAY-06:24
June 0.00 0.00 01-JUN-00:05 23173.68 48183.85 01-JUN-06:25
July 0.00 0.00 01-JUL-00:10 22020.29 45011.15 03-JUL-06:10
August 0.00 0.00 01-AUG-00:05 21740.83 43965.29 31-AUG-06:10
September 0.00 0.00 01-SEP-00:05 22354.89 50829.85 30-SEP-07:03
October 0.00 0.00 01-OCT-00:10 23697.39 57812.13 27-OCT-06:52
November 0.00 0.00 01-NOV-00:05 25446.81 60828.28 30-NOV-21:11
December 0.00 0.00 01-DEC-00:03 27130.84 61709.08 26-DEC-19:41
             
Annual Sum or Average 0.00     25119.28    
Minimum of Months 0.00 0.00   21740.83 43965.29  
Maximum of Months 0.00 0.00   28540.20 67298.66  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.88 2194.93 01-JAN-00:05 0.88
February 0.530997E+10 0.88 2194.93 01-FEB-00:03 0.88
March 0.587890E+10 0.88 2194.93 01-MAR-00:03 0.88
April 0.568926E+10 0.88 2194.93 01-APR-00:10 0.87
May 0.587890E+10 0.87 2194.93 01-MAY-00:03 0.87
June 0.568926E+10 0.87 2194.93 01-JUN-00:05 0.87
July 0.587890E+10 0.87 2194.93 01-JUL-00:10 0.87
August 0.587890E+10 0.87 2194.93 01-AUG-00:05 0.87
September 0.568926E+10 0.87 2194.93 01-SEP-00:05 0.87
October 0.587890E+10 0.87 2194.93 01-OCT-00:10 0.87
November 0.568926E+10 0.88 2194.93 01-NOV-00:05 0.87
December 0.587890E+10 0.88 2194.93 01-DEC-00:03 0.88
           
Annual Sum or Average 0.692193E+11 0.87      
Minimum of Months 0.530997E+10 0.87 2194.93   0.87
Maximum of Months 0.587890E+10 0.88 2194.93   0.88



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.327740E+11 0.78 41476.14 19-JAN-22:45 1.63
February 0.292502E+11 0.78 27039.85 01-FEB-21:28 1.25
March 0.344186E+11 0.80 35431.91 28-MAR-21:33 1.47
April 0.345931E+11 0.82 35431.91 12-APR-21:48 1.48
May 0.363582E+11 0.82 34875.71 02-MAY-01:03 1.46
June 0.370682E+11 0.84 27584.20 19-JUN-21:10 1.25
July 0.397337E+11 0.86 28353.56 10-JUL-21:10 1.27
August 0.407617E+11 0.87 38174.20 24-AUG-18:50 1.54
September 0.372474E+11 0.85 36708.91 01-SEP-20:10 1.49
October 0.375130E+11 0.84 42107.32 18-OCT-22:35 1.64
November 0.346964E+11 0.82 41476.14 06-NOV-23:10 1.62
December 0.334809E+11 0.79 30992.90 03-DEC-15:40 1.36
           
Annual Sum or Average 0.427896E+12 0.82      
Minimum of Months 0.292502E+11 0.78 27039.85   1.25
Maximum of Months 0.407617E+11 0.87 42107.32   1.64



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:05 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.26 76.61 01-MAY-00:03 0.26
June 0.198586E+09 0.26 76.61 01-JUN-00:05 0.26
July 0.205205E+09 0.26 76.61 01-JUL-00:10 0.26
August 0.205205E+09 0.26 76.61 01-AUG-00:05 0.26
September 0.198586E+09 0.26 76.61 01-SEP-00:05 0.26
October 0.205205E+09 0.26 76.61 01-OCT-00:10 0.26
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.26
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.26 76.61   0.26
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:03 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:03 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:03 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:03 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.26
June 0.112532E+10 0.19 612.92 01-JUN-06:03 0.26
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.26
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.26
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.26
October 0.116283E+10 0.19 612.92 01-OCT-06:02 0.26
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.26
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.405727E+09 0.46 847.52 01-JAN-09:02 0.58
February 0.348172E+09 0.45 847.52 01-FEB-09:02 0.58
March 0.239821E+09 0.43 847.52 01-MAR-16:01 0.58
April 0.199631E+09 0.42 847.52 01-APR-08:62 0.58
May 0.211637E+09 0.38 847.52 01-MAY-15:02 0.58
June 0.331247E+09 0.36 847.52 01-JUN-08:51 0.57
July 0.476428E+09 0.45 847.52 01-JUL-08:51 0.57
August 0.529552E+09 0.46 847.52 01-AUG-06:51 0.57
September 0.265982E+09 0.35 847.52 01-SEP-08:61 0.57
October 0.204080E+09 0.40 847.52 02-OCT-15:02 0.57
November 0.230714E+09 0.42 847.52 01-NOV-15:02 0.58
December 0.339364E+09 0.44 847.52 01-DEC-09:02 0.58
           
Annual Sum or Average 0.378235E+10 0.42      
Minimum of Months 0.199631E+09 0.35 847.52   0.57
Maximum of Months 0.529552E+09 0.46 847.52   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.461296E+09 0.48 824.06 01-JAN-09:02 0.58
February 0.418711E+09 0.48 824.06 01-FEB-09:02 0.58
March 0.251357E+09 0.41 824.06 01-MAR-09:02 0.58
April 0.178303E+09 0.40 824.06 01-APR-08:62 0.58
May 0.189955E+09 0.37 824.06 01-MAY-15:02 0.58
June 0.315017E+09 0.36 824.06 01-JUN-08:51 0.57
July 0.454475E+09 0.45 824.06 01-JUL-08:51 0.57
August 0.469442E+09 0.45 824.06 01-AUG-06:51 0.57
September 0.208382E+09 0.33 824.06 01-SEP-08:61 0.57
October 0.137516E+09 0.36 824.06 02-OCT-15:02 0.57
November 0.259345E+09 0.42 824.06 01-NOV-08:62 0.57
December 0.392259E+09 0.47 824.06 01-DEC-09:02 0.58
           
Annual Sum or Average 0.373606E+10 0.42      
Minimum of Months 0.137516E+09 0.33 824.06   0.57
Maximum of Months 0.469442E+09 0.48 824.06   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.703840E+09 0.23 1351.64 02-JAN-05:00 0.58
February 0.269582E+09 0.11 1173.95 07-FEB-06:00 0.58
March 0.191971E+09 0.07 1325.17 03-MAR-13:30 0.58
April 0.336517E+09 0.12 1585.03 08-APR-12:30 0.57
May 0.583187E+09 0.24 1211.28 30-MAY-12:50 0.57
June 0.101430E+10 0.39 1305.39 19-JUN-13:10 0.57
July 0.167879E+10 0.52 1367.68 10-JUL-13:00 0.57
August 0.205398E+10 0.54 2600.98 30-AUG-13:00 0.57
September 0.143324E+10 0.41 2898.39 30-SEP-13:10 0.58
October 0.146196E+10 0.35 2619.22 04-OCT-12:00 0.57
November 0.315102E+09 0.10 2584.64 04-NOV-12:30 0.57
December 0.410629E+09 0.15 1348.36 17-DEC-13:30 0.58
           
Annual Sum or Average 0.104531E+11 0.27      
Minimum of Months 0.191971E+09 0.07 1173.95   0.57
Maximum of Months 0.205398E+10 0.54 2898.39   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.189417E+10 0.42 4693.00 01-JAN-09:02 0.58
February 0.181790E+10 0.42 4693.00 01-FEB-09:02 0.58
March 0.956505E+09 0.40 4693.00 01-MAR-16:01 0.58
April 0.842449E+09 0.38 4693.00 01-APR-15:02 0.58
May 0.139782E+10 0.32 4693.00 01-MAY-08:62 0.58
June 0.197198E+10 0.27 4693.00 01-JUN-08:51 0.57
July 0.284688E+10 0.37 4693.00 01-JUL-08:51 0.57
August 0.257529E+10 0.35 4693.00 01-AUG-06:51 0.57
September 0.139655E+10 0.26 4693.00 01-SEP-08:61 0.57
October 0.829212E+09 0.32 4693.00 01-OCT-08:62 0.57
November 0.935398E+09 0.40 4693.00 03-NOV-16:31 0.58
December 0.152101E+10 0.41 4693.00 01-DEC-09:02 0.58
           
Annual Sum or Average 0.189852E+11 0.36      
Minimum of Months 0.829212E+09 0.26 4693.00   0.57
Maximum of Months 0.284688E+10 0.42 4693.00   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.382294E+09 0.45 777.88 01-JAN-09:02 0.58
February 0.320018E+09 0.44 777.88 01-FEB-16:02 0.58
March 0.230326E+09 0.43 777.88 01-MAR-09:02 0.58
April 0.200623E+09 0.44 777.88 01-APR-08:62 0.58
May 0.229172E+09 0.40 777.88 01-MAY-08:62 0.57
June 0.316941E+09 0.37 777.88 01-JUN-08:51 0.57
July 0.465619E+09 0.46 777.88 01-JUL-08:32 0.57
August 0.516031E+09 0.47 777.88 01-AUG-06:51 0.57
September 0.276676E+09 0.37 777.88 01-SEP-08:61 0.57
October 0.209238E+09 0.42 777.88 02-OCT-08:62 0.57
November 0.217821E+09 0.42 777.88 01-NOV-08:62 0.57
December 0.320745E+09 0.44 777.88 01-DEC-16:02 0.58
           
Annual Sum or Average 0.368550E+10 0.43      
Minimum of Months 0.200623E+09 0.37 777.88   0.57
Maximum of Months 0.516031E+09 0.47 777.88   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.444473E+09 0.49 756.78 01-JAN-09:02 0.58
February 0.390726E+09 0.48 756.78 01-FEB-09:02 0.58
March 0.241269E+09 0.41 756.78 01-MAR-09:02 0.58
April 0.174877E+09 0.41 756.78 01-APR-08:62 0.58
May 0.205653E+09 0.39 756.78 01-MAY-08:62 0.57
June 0.301075E+09 0.37 756.78 01-JUN-08:51 0.57
July 0.443785E+09 0.46 756.78 01-JUL-08:32 0.57
August 0.455248E+09 0.46 756.78 01-AUG-06:51 0.57
September 0.217443E+09 0.35 756.78 01-SEP-08:61 0.57
October 0.134586E+09 0.35 756.78 02-OCT-08:62 0.57
November 0.235109E+09 0.42 756.78 04-NOV-08:62 0.57
December 0.363997E+09 0.47 756.78 01-DEC-09:02 0.58
           
Annual Sum or Average 0.360824E+10 0.42      
Minimum of Months 0.134586E+09 0.35 756.78   0.57
Maximum of Months 0.455248E+09 0.49 756.78   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.126987E+09 0.48 222.36 01-JAN-09:02 0.58
February 0.108497E+09 0.47 222.36 01-FEB-09:02 0.58
March 72703988.80 0.44 222.36 01-MAR-09:02 0.58
April 58517397.22 0.43 222.36 01-APR-08:62 0.58
May 57648672.71 0.39 222.36 01-MAY-15:02 0.58
June 89110316.01 0.36 222.36 01-JUN-08:51 0.57
July 0.126917E+09 0.45 222.36 01-JUL-08:51 0.57
August 0.139394E+09 0.46 222.36 01-AUG-06:51 0.57
September 68380785.90 0.36 222.36 01-SEP-08:61 0.57
October 52705876.25 0.40 222.36 02-OCT-15:02 0.57
November 70645069.87 0.43 222.36 01-NOV-08:62 0.57
December 0.103018E+09 0.46 222.36 01-DEC-09:02 0.58
           
Annual Sum or Average 0.107453E+10 0.43      
Minimum of Months 52705876.25 0.36 222.36   0.57
Maximum of Months 0.139394E+09 0.48 222.36   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.147133E+09 0.52 215.76 01-JAN-09:02 0.58
February 0.131164E+09 0.51 215.76 01-FEB-09:02 0.58
March 75745828.10 0.43 215.76 01-MAR-09:02 0.58
April 52800138.30 0.41 215.76 01-APR-08:62 0.58
May 51807472.72 0.38 215.76 01-MAY-15:02 0.58
June 84896859.13 0.36 215.76 01-JUN-08:51 0.57
July 0.121218E+09 0.45 215.76 01-JUL-08:51 0.57
August 0.123276E+09 0.45 215.76 01-AUG-06:51 0.57
September 52671054.45 0.34 215.76 01-SEP-08:61 0.57
October 37363273.70 0.36 215.76 02-OCT-15:02 0.57
November 80599492.75 0.44 215.76 01-NOV-08:62 0.57
December 0.118491E+09 0.50 215.76 01-DEC-09:02 0.58
           
Annual Sum or Average 0.107717E+10 0.43      
Minimum of Months 37363273.70 0.34 215.76   0.57
Maximum of Months 0.147133E+09 0.52 215.76   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.440043E+09 0.46 1034.60 01-JAN-16:02 0.58
February 0.363778E+09 0.47 1034.60 02-FEB-16:01 0.58
March 0.318518E+09 0.46 1034.60 01-MAR-09:02 0.58
April 0.274075E+09 0.44 1034.60 01-APR-08:62 0.58
May 0.267337E+09 0.39 1034.60 01-MAY-15:02 0.58
June 0.389535E+09 0.36 1034.60 01-JUN-08:51 0.57
July 0.601198E+09 0.45 1034.60 01-JUL-08:51 0.57
August 0.707627E+09 0.46 1034.60 01-AUG-06:51 0.57
September 0.458359E+09 0.36 1034.60 01-SEP-08:61 0.57
October 0.440986E+09 0.43 1034.60 02-OCT-08:62 0.57
November 0.289465E+09 0.45 1034.60 01-NOV-15:02 0.58
December 0.389836E+09 0.47 1034.60 01-DEC-19:02 0.58
           
Annual Sum or Average 0.494076E+10 0.43      
Minimum of Months 0.267337E+09 0.36 1034.60   0.57
Maximum of Months 0.707627E+09 0.47 1034.60   0.58



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.116630E+10 0.104967E+10 934.54 02-JAN-07:05 841.09 841.09 36.60 1.86
February 0.999029E+09 0.899126E+09 948.65 06-FEB-07:05 853.78 853.78 36.52 1.95
March 0.626318E+09 0.563686E+09 858.23 05-MAR-19:02 772.41 772.41 32.22 1.50
April 0.355038E+09 0.319534E+09 852.69 13-APR-15:02 767.42 767.42 57.32 1.46
May 79231838.74 71308654.87 734.15 14-MAY-03:50 660.74 660.74 38.11 1.11
June 2225690.62 2003121.56 249.96 04-JUN-08:56 224.96 224.96 26.35 0.28
July 733144.11 659829.70 236.68 14-JUL-08:07 213.01 213.01 30.98 0.26
August 3158212.39 2842391.15 257.54 20-AUG-13:30 231.78 231.78 36.81 0.29
September 12408347.97 11167513.17 590.32 24-SEP-05:47 531.29 531.29 44.65 0.79
October 0.149315E+09 0.134384E+09 774.42 18-OCT-06:22 696.98 696.98 48.99 1.21
November 0.606596E+09 0.545936E+09 861.60 13-NOV-09:02 775.44 775.44 34.26 1.51
December 0.882898E+09 0.794608E+09 884.13 07-DEC-19:02 795.72 795.72 34.71 1.60
                 
Annual Sum or Average 0.488325E+10 0.439493E+10            
Minimum of Months 733144.11 659829.70 236.68   213.01 213.01 26.35 0.26
Maximum of Months 0.116630E+10 0.104967E+10 948.65   853.78 853.78 57.32 1.95



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 677676.23 609908.61 27.09 19-JAN-19:03 24.38 24.38 6.72 2.93
February 1442929.70 1298636.73 42.53 20-FEB-09:02 38.27 38.27 6.72 3.80
March 8334616.01 7501154.41 158.17 27-MAR-15:02 142.35 142.35 6.72 7.56
April 55634137.93 50070724.14 716.64 07-APR-15:02 644.98 644.98 6.72 15.28
May 0.155624E+09 0.140062E+09 661.30 28-MAY-15:02 595.17 595.17 6.72 14.74
June 0.755519E+09 0.679967E+09 1462.60 19-JUN-18:03 1316.34 1316.34 6.72 20.78
July 0.145803E+10 0.131222E+10 1721.68 20-JUL-18:03 1549.51 1549.51 6.72 22.25
August 0.129326E+10 0.116393E+10 1777.48 03-AUG-18:03 1599.73 1599.73 6.72 22.55
September 0.523534E+09 0.471180E+09 1547.32 07-SEP-20:00 1392.58 1392.58 6.72 21.27
October 0.160161E+09 0.144145E+09 790.11 05-OCT-15:03 711.10 711.10 6.72 15.95
November 11222076.19 10099868.57 153.71 04-NOV-15:01 138.34 138.34 6.72 7.46
December 2578921.71 2321029.53 31.52 17-DEC-16:01 28.36 28.36 6.72 3.20
                 
Annual Sum or Average 0.442601E+10 0.398341E+10            
Minimum of Months 677676.23 609908.61 27.09   24.38 24.38 6.72 2.93
Maximum of Months 0.145803E+10 0.131222E+10 1777.48   1599.73 1599.73 6.72 22.55



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.340192E+10 0.306173E+10 4190.36 01-JAN-09:03 3771.32 3771.32 6.75 37.07
February 0.353360E+10 0.318024E+10 4190.36 01-FEB-00:03 3771.32 3771.32 6.72 37.07
March 0.586607E+10 0.527946E+10 4190.36 01-MAR-00:03 3771.32 3771.32 6.72 37.07
April 0.783639E+10 0.705275E+10 4190.36 01-APR-01:07 3771.32 3771.32 6.72 37.07
May 0.108696E+11 0.978265E+10 4190.36 01-MAY-00:03 3771.32 3771.32 6.76 37.07
June 0.108614E+11 0.977526E+10 4190.36 01-JUN-00:05 3771.32 3771.32 7.91 37.07
July 0.112235E+11 0.101011E+11 4190.36 01-JUL-00:10 3771.32 3771.32 8.79 37.07
August 0.112235E+11 0.101011E+11 4190.36 01-AUG-00:05 3771.32 3771.32 9.06 37.07
September 0.108463E+11 0.976169E+10 4190.36 01-SEP-00:05 3771.32 3771.32 8.93 37.07
October 0.104595E+11 0.941351E+10 4190.36 01-OCT-00:10 3771.32 3771.32 6.87 37.07
November 0.610779E+10 0.549701E+10 4190.36 01-NOV-00:05 3771.32 3771.32 6.73 37.07
December 0.480689E+10 0.432620E+10 4190.36 01-DEC-00:03 3771.32 3771.32 6.73 37.07
                 
Annual Sum or Average 0.970364E+11 0.873327E+11            
Minimum of Months 0.340192E+10 0.306173E+10 4190.36   3771.32 3771.32 6.72 37.07
Maximum of Months 0.112235E+11 0.101011E+11 4190.36   3771.32 3771.32 9.06 37.07



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 48.07 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 48.24 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 48.29 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 51.85 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:03 14.37 14.37 51.86 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 52.66 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 52.58 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 53.37 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 53.29 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 52.18 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 50.14 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 49.33 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 48.07 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 53.37 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 36.36 60.00 51077.47 197059.18 02-JAN-09:05
February 0.00 0.00 01-FEB-00:03 39.68 60.00 48864.23 196461.49 06-FEB-09:02
March 0.00 0.00 01-MAR-00:03 44.47 60.00 22304.28 173765.19 05-MAR-19:02
April 0.00 0.00 01-APR-00:10 47.12 60.00 13640.75 147518.95 04-APR-18:02
May 0.00 0.00 01-MAY-00:03 37.31 60.00 3231.25 105213.03 15-MAY-02:00
June 0.00 0.00 01-JUN-00:05 30.09 30.09 107.71 39463.30 04-JUN-08:56
July 0.00 0.00 01-JUL-00:10 33.29 33.29 28.49 32003.50 14-JUL-08:07
August 0.00 0.00 01-AUG-00:05 40.83 40.83 137.68 33854.87 24-AUG-18:50
September 0.00 0.00 01-SEP-00:05 37.67 37.67 444.55 64180.31 30-SEP-01:10
October 0.00 0.00 01-OCT-00:10 39.20 60.00 5228.86 140098.87 18-OCT-08:02
November 0.01 57.62 29-NOV-14:00 60.03 60.03 22656.82 169113.33 20-NOV-19:02
December 0.00 0.00 01-DEC-00:03 47.55 60.00 31468.22 169292.81 07-DEC-19:02
                 
Annual Sum or Average 0.00         16414.95    
Minimum of Months 0.00 0.00   30.09 30.09 28.49 32003.50  
Maximum of Months 0.01 57.62   60.03 60.03 51077.47 197059.18  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1731.01 37264.92 19-JAN-19:03 6.94 6.70 0.00 0.00 01-JAN-00:05
February 2510.95 51576.08 20-FEB-09:02 7.03 6.70 0.00 0.00 01-FEB-00:03
March 7308.07 250947.51 27-MAR-15:02 8.31 6.70 0.00 0.00 01-MAR-00:03
April 29417.88 382468.13 07-APR-15:02 9.16 6.70 0.00 0.00 01-APR-00:10
May 81614.05 472801.22 29-MAY-18:32 9.74 6.70 0.00 0.00 01-MAY-00:03
June 281501.51 733688.84 15-JUN-21:52 11.42 6.70 0.00 0.00 01-JUN-00:05
July 417709.41 735308.40 24-JUL-21:52 11.44 6.70 0.00 0.00 01-JUL-00:10
August 353784.54 767482.59 11-AUG-21:51 11.64 6.70 0.00 0.00 01-AUG-00:05
September 205224.57 702914.89 07-SEP-21:52 11.23 6.70 0.00 0.00 01-SEP-00:05
October 84533.44 501851.41 05-OCT-15:03 9.93 6.70 0.00 0.00 01-OCT-00:10
November 8569.64 156499.23 04-NOV-15:01 7.71 6.70 0.00 0.00 01-NOV-00:05
December 3393.02 61042.17 25-DEC-09:02 7.09 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 124010.94         0.00    
Minimum of Months 1731.01 37264.92   6.94 6.70 0.00 0.00  
Maximum of Months 417709.41 767482.59   11.64 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 48.07 59.70 28260.32 64428.84 18-JAN-07:14
February 0.00 0.00 01-FEB-00:03 48.24 58.87 28540.20 66060.69 01-FEB-21:21
March 0.00 0.00 01-MAR-00:03 48.29 58.41 27934.32 67298.66 02-MAR-07:22
April 0.00 0.00 01-APR-00:10 51.85 59.32 26550.16 62088.47 11-APR-06:21
May 0.00 0.00 01-MAY-00:03 51.86 59.20 24817.53 58268.17 02-MAY-06:24
June 0.00 0.00 01-JUN-00:05 52.66 59.24 23173.68 48183.85 01-JUN-06:25
July 0.00 0.00 01-JUL-00:10 52.58 58.29 22020.29 45011.15 03-JUL-06:10
August 0.00 0.00 01-AUG-00:05 53.37 59.63 21740.83 43965.29 31-AUG-06:10
September 0.00 0.00 01-SEP-00:05 53.29 59.29 22354.89 50829.85 30-SEP-07:03
October 0.00 0.00 01-OCT-00:10 52.18 59.03 23697.39 57812.13 27-OCT-06:52
November 0.00 0.00 01-NOV-00:05 50.14 58.99 25446.81 60828.28 30-NOV-21:11
December 0.00 0.00 01-DEC-00:03 49.33 59.20 27130.84 61709.08 26-DEC-19:41
                 
Annual Sum or Average 0.00         25119.28    
Minimum of Months 0.00 0.00   48.07 58.29 21740.83 43965.29  
Maximum of Months 0.00 0.00   53.37 59.70 28540.20 67298.66  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.691716E+11 0.00 0.216898E+09 0.327740E+11 0.00 0.00
February 0.620449E+11 0.00 0.216674E+09 0.292502E+11 0.00 0.00
March 0.371621E+11 0.00 0.358594E+10 0.344186E+11 0.00 0.00
April 0.280136E+11 0.00 0.343480E+11 0.345931E+11 0.00 0.00
May 0.807437E+10 0.00 0.125664E+12 0.363582E+11 0.00 0.00
June 0.255924E+09 0.00 0.516176E+12 0.370682E+11 0.00 0.00
July 53074649.96 0.00 0.811626E+12 0.397337E+11 0.00 0.00
August 0.346831E+09 0.00 0.661412E+12 0.407617E+11 0.00 0.00
September 0.103259E+10 0.00 0.360155E+12 0.372474E+11 0.00 0.00
October 0.120045E+11 0.00 0.124982E+12 0.375130E+11 0.00 0.00
November 0.361264E+11 0.00 0.365666E+10 0.346964E+11 0.00 0.00
December 0.370940E+11 0.00 0.441034E+09 0.334809E+11 0.00 0.00
             
Annual Sum or Average 0.291380E+12 0.00 0.264248E+13 0.427896E+12 0.00 0.00
Minimum of Months 53074649.96 0.00 0.216674E+09 0.292502E+11 0.00 0.00
Maximum of Months 0.691716E+11 0.00 0.811626E+12 0.407617E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.468420E+10 0.00 9597.49 0.587890E+10 0.00 0.00
February 0.470086E+10 0.00 0.00 0.530997E+10 0.00 0.00
March 0.483324E+09 0.00 0.697388E+09 0.587890E+10 0.00 0.00
April 5557.80 0.00 0.635538E+10 0.568926E+10 0.00 0.00
May 16753.93 0.00 0.233997E+11 0.587890E+10 0.00 0.00
June 16922.63 0.00 0.987929E+11 0.568926E+10 0.00 0.00
July 12149.09 0.00 0.135125E+12 0.587890E+10 0.00 0.00
August 29210.58 0.00 0.108838E+12 0.587890E+10 0.00 0.00
September 74683.95 0.00 0.681274E+11 0.568926E+10 0.00 0.00
October 12063.65 0.00 0.246553E+11 0.587890E+10 0.00 0.00
November 0.379611E+09 0.00 0.605285E+09 0.568926E+10 0.00 0.00
December 0.859061E+09 0.00 0.00 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.111072E+11 0.00 0.466597E+12 0.692193E+11 0.00 0.00
Minimum of Months 5557.80 0.00 0.00 0.530997E+10 0.00 0.00
Maximum of Months 0.470086E+10 0.00 0.135125E+12 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.327740E+11 0.216898E+09 0.691716E+11 0.545567E+12 0.00 0.00 0.00 0.00
February 0.292502E+11 0.216674E+09 0.620449E+11 0.541314E+12 0.00 0.00 0.00 0.00
March 0.344186E+11 0.358594E+10 0.371621E+11 0.367564E+12 0.00 0.00 0.00 0.00
April 0.345931E+11 0.343480E+11 0.280136E+11 0.153224E+12 0.129674E+09 0.00 0.00 0.00
May 0.363582E+11 0.125664E+12 0.807437E+10 0.228770E+11 0.273970E+10 0.00 0.00 0.00
June 0.370682E+11 0.516176E+12 0.255924E+09 0.147516E+09 0.477279E+11 0.00 0.00 0.00
July 0.397337E+11 0.811626E+12 53074649.96 0.00 0.185708E+12 0.00 0.00 0.00
August 0.407617E+11 0.661412E+12 0.346831E+09 0.00 0.149402E+12 0.00 0.00 0.00
September 0.372474E+11 0.360155E+12 0.103259E+10 0.429557E+10 0.192314E+11 0.00 0.00 0.00
October 0.375130E+11 0.124982E+12 0.120045E+11 0.738521E+11 0.502876E+09 0.00 0.00 0.00
November 0.346964E+11 0.365666E+10 0.361264E+11 0.274323E+12 0.00 0.00 0.00 0.00
December 0.334809E+11 0.441034E+09 0.370940E+11 0.479511E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.427896E+12 0.264248E+13 0.291380E+12 0.246268E+13 0.405441E+12 0.00 0.00 0.00
Minimum of Months 0.292502E+11 0.216674E+09 53074649.96 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.407617E+11 0.811626E+12 0.691716E+11 0.545567E+12 0.185708E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 9597.49 0.468420E+10 0.980078E+11 0.00 0.00 0.00 0.00
February 0.530997E+10 0.00 0.470086E+10 0.961047E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.697388E+09 0.483324E+09 0.704132E+11 0.00 0.00 0.00 0.00
April 0.568926E+10 0.635538E+10 5557.80 0.341795E+11 0.152130E+09 0.00 0.00 0.00
May 0.587890E+10 0.233997E+11 16753.93 0.720029E+10 0.117941E+10 0.00 0.00 0.00
June 0.568926E+10 0.987929E+11 16922.63 0.120057E+09 0.166073E+11 0.00 0.00 0.00
July 0.587890E+10 0.135125E+12 12149.09 1278575.07 0.623451E+11 0.00 0.00 0.00
August 0.587890E+10 0.108838E+12 29210.58 82011012.82 0.496567E+11 0.00 0.00 0.00
September 0.568926E+10 0.681274E+11 74683.95 0.139661E+10 0.101070E+11 0.00 0.00 0.00
October 0.587890E+10 0.246553E+11 12063.65 0.178100E+11 0.528242E+09 0.00 0.00 0.00
November 0.568926E+10 0.605285E+09 0.379611E+09 0.560674E+11 0.00 0.00 0.00 0.00
December 0.587890E+10 0.00 0.859061E+09 0.870417E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.466597E+12 0.111072E+11 0.468425E+12 0.140576E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.00 5557.80 1278575.07 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.135125E+12 0.470086E+10 0.980078E+11 0.623451E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.327740E+11 0.691716E+11 0.216898E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.292502E+11 0.620449E+11 0.216674E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.344186E+11 0.371621E+11 0.358594E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.345931E+11 0.280136E+11 0.343480E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.363582E+11 0.807437E+10 0.125664E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.370682E+11 0.255924E+09 0.516176E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.397337E+11 53074649.96 0.811626E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.407617E+11 0.346831E+09 0.661412E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.372474E+11 0.103259E+10 0.360155E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.375130E+11 0.120045E+11 0.124982E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.346964E+11 0.361264E+11 0.365666E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.334809E+11 0.370940E+11 0.441034E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.427896E+12 0.291380E+12 0.264248E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.292502E+11 53074649.96 0.216674E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.407617E+11 0.691716E+11 0.811626E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.468420E+10 9597.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.470086E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 0.483324E+09 0.697388E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 5557.80 0.635538E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 16753.93 0.233997E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 16922.63 0.987929E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 12149.09 0.135125E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 29210.58 0.108838E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 74683.95 0.681274E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 12063.65 0.246553E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 0.379611E+09 0.605285E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.859061E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.111072E+11 0.466597E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 5557.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.470086E+10 0.135125E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.337014E+11 0.00 0.00 18809401.45 0.00 0.00 0.187090E+11 0.00 0.98
February 0.409753E+11 0.00 0.00 3076248.57 0.00 0.00 0.629920E+10 0.00 0.98
March 0.495145E+11 0.00 0.00 202643.03 0.00 0.00 0.138630E+10 0.00 0.96
April 0.467840E+11 0.00 0.00 8682.64 10860596.77 0.00 37208635.90 0.00 0.97
May 0.396873E+11 0.00 0.00 0.00 0.240739E+09 0.00 0.00 0.00 1.02
June 0.108223E+11 0.263390E+09 0.00 28859.62 0.103885E+11 0.00 0.109854E+09 0.00 0.98
July 0.559978E+09 0.359330E+10 0.00 122301.87 0.225060E+11 0.00 37304498.73 0.00 0.91
August 0.105337E+10 0.684470E+10 0.00 10490672.25 0.916638E+10 0.00 0.564787E+10 0.00 0.96
September 0.142187E+10 0.482891E+10 0.00 40191417.63 0.104189E+10 0.00 0.219259E+11 0.00 1.05
October 0.155575E+10 0.320527E+09 0.00 89012964.60 86730213.16 0.00 0.453343E+11 0.00 1.10
November 0.327937E+10 0.00 0.00 0.108385E+09 0.00 0.00 0.531926E+11 0.00 1.07
December 0.117631E+11 0.00 0.00 54613385.21 0.00 0.00 0.409766E+11 0.00 1.02
                   
Annual Sum or Average 0.241118E+12 0.158508E+11 0.00 0.324941E+09 0.434411E+11 0.00 0.193656E+12 0.00 1.00
Minimum of Months 0.559978E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.91
Maximum of Months 0.495145E+11 0.684470E+10 0.00 0.108385E+09 0.225060E+11 0.00 0.531926E+11 0.00 1.10



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.385802E+10 0.00 0.00 458683.23 0.00 0.341637E+10 0.256298E+09 0.00 2.53
February 0.389490E+10 0.00 0.00 514505.45 0.00 0.260870E+10 0.360289E+09 0.00 2.56
March 0.608840E+10 0.00 0.00 1272730.83 0.00 0.758953E+09 0.598405E+09 0.00 2.53
April 0.624396E+10 2044900.99 0.00 760072.05 160893.29 0.168591E+09 0.383560E+09 0.00 2.56
May 0.548319E+10 28225666.21 0.00 355147.15 8658403.44 262494.24 0.268351E+09 0.00 2.67
June 0.146782E+10 0.715469E+09 0.00 356284.09 0.843807E+09 0.00 0.116412E+09 0.00 2.59
July 66887989.77 0.227681E+10 0.00 70115.71 0.162368E+10 0.00 19628464.37 0.00 2.45
August 0.749863E+09 0.208916E+10 0.00 1098824.30 0.458129E+09 0.00 0.214908E+09 0.00 2.72
September 0.259781E+10 0.419786E+09 0.00 2695430.76 0.452275E+09 0.00 0.685126E+09 0.00 2.80
October 0.478363E+10 84152381.31 0.00 3813552.42 736510.55 0.00 0.150699E+10 0.00 2.82
November 0.619755E+10 0.00 0.00 847334.72 0.00 0.616008E+09 0.479592E+09 0.00 2.53
December 0.465192E+10 0.00 0.00 929079.96 0.00 0.223652E+10 0.401963E+09 0.00 2.55
                   
Annual Sum or Average 0.460840E+11 0.561565E+10 0.00 13171760.68 0.338744E+10 0.980541E+10 0.529153E+10 0.00 2.61
Minimum of Months 66887989.77 0.00 0.00 70115.71 0.00 0.00 19628464.37 0.00 2.45
Maximum of Months 0.624396E+10 0.227681E+10 0.00 3813552.42 0.162368E+10 0.341637E+10 0.150699E+10 0.00 2.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.462869E+10 0.00 0.00 266.46 0.00 0.00 1650786.31 0.00 1.35
February 0.422273E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.36
March 0.441168E+10 0.00 0.00 52364.01 0.00 0.00 0.137912E+09 0.00 1.34
April 0.373322E+10 0.00 0.00 402621.07 970694.76 0.00 0.456581E+09 0.00 1.36
May 0.269263E+10 5957137.00 0.00 898630.65 15595054.64 0.00 0.865577E+09 0.00 1.43
June 0.327265E+09 0.572499E+09 0.00 1332372.12 0.409765E+09 0.00 0.669486E+09 0.00 1.42
July 1408954.64 0.194411E+10 0.00 370656.58 0.508410E+09 0.00 54623112.93 0.00 1.34
August 41538231.44 0.137344E+10 0.00 1888125.48 0.165619E+09 0.00 0.582129E+09 0.00 1.44
September 0.973901E+09 0.362388E+09 0.00 1695636.05 0.161991E+09 0.00 0.104417E+10 0.00 1.45
October 0.251719E+10 13287381.04 0.00 1452685.73 22927304.87 0.00 0.125164E+10 0.00 1.41
November 0.425001E+10 0.00 0.00 98221.15 0.00 0.00 0.215342E+09 0.00 1.34
December 0.446014E+10 0.00 0.00 61.95 0.00 0.00 707567.30 0.00 1.35
                   
Annual Sum or Average 0.322604E+11 0.427168E+10 0.00 8191641.27 0.128528E+10 0.00 0.527981E+10 0.00 1.38
Minimum of Months 1408954.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
Maximum of Months 0.462869E+10 0.194411E+10 0.00 1888125.48 0.508410E+09 0.00 0.125164E+10 0.00 1.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.232800E+10 0.00 0.00 0.00 0.00 0.130880E+10 0.00 0.00 0.50
February 0.206684E+10 0.00 0.00 0.00 0.00 0.124982E+10 0.00 0.00 0.50
March 0.352292E+10 0.00 0.00 0.00 0.00 50323775.89 0.00 0.00 0.49
April 0.328662E+10 0.00 0.00 0.00 762411.33 217144.63 0.00 0.00 0.50
May 0.277607E+10 5054.49 0.00 14903.30 16894784.43 0.00 9946985.71 0.00 0.53
June 0.734443E+09 0.149996E+09 0.00 139902.86 0.603225E+09 0.00 34492607.86 0.00 0.51
July 11736109.48 0.950750E+09 0.00 156272.46 0.934932E+09 0.00 31181655.49 0.00 0.49
August 0.309301E+09 0.812817E+09 0.00 584385.10 0.364066E+09 0.00 0.162964E+09 0.00 0.51
September 0.148520E+10 68793139.00 0.00 173041.64 0.326618E+09 0.00 71407655.78 0.00 0.52
October 0.293683E+10 0.00 0.00 0.00 28315500.94 0.00 0.00 0.00 0.52
November 0.340537E+10 0.00 0.00 0.00 0.00 0.101918E+09 0.00 0.00 0.49
December 0.334523E+10 0.00 0.00 0.00 0.00 0.158442E+09 0.00 0.00 0.50
                   
Annual Sum or Average 0.262086E+11 0.198236E+10 0.00 1068505.36 0.227481E+10 0.286952E+10 0.309993E+09 0.00 0.51
Minimum of Months 11736109.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
Maximum of Months 0.352292E+10 0.950750E+09 0.00 584385.10 0.934932E+09 0.130880E+10 0.162964E+09 0.00 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.963751E+09 0.00 0.00 0.00 0.00 0.142985E+10 0.00 0.00 0.57
February 0.846604E+09 0.00 0.00 0.00 0.00 0.133628E+10 0.00 0.00 0.57
March 0.207865E+10 0.00 0.00 0.00 0.00 0.273113E+09 0.00 0.00 0.56
April 0.215727E+10 0.00 0.00 0.00 501788.40 6000152.65 0.00 0.00 0.57
May 0.183366E+10 0.00 0.00 0.00 11122792.59 0.00 0.00 0.00 0.60
June 0.500973E+09 11330377.18 0.00 7571.14 0.480815E+09 0.00 4117339.63 0.00 0.58
July 21270434.59 0.178776E+09 0.00 16415.03 0.102754E+10 0.00 6314826.98 0.00 0.54
August 0.289084E+09 0.276114E+09 0.00 49437.49 0.461065E+09 0.00 18069476.19 0.00 0.57
September 0.102164E+10 2803968.35 0.00 7211.80 0.255432E+09 0.00 2384062.56 0.00 0.59
October 0.193290E+10 0.00 0.00 0.00 18636121.05 0.00 0.00 0.00 0.59
November 0.205579E+10 0.00 0.00 0.00 0.00 0.252571E+09 0.00 0.00 0.56
December 0.159083E+10 0.00 0.00 0.00 0.00 0.715152E+09 0.00 0.00 0.57
                   
Annual Sum or Average 0.152924E+11 0.469025E+09 0.00 80635.46 0.225512E+10 0.401297E+10 30885705.37 0.00 0.57
Minimum of Months 21270434.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.215727E+10 0.276114E+09 0.00 49437.49 0.102754E+10 0.142985E+10 18069476.19 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104742E+10 0.00 0.00 0.124175E+09 0.00 0.00 0.722287E+11 0.00 21.00
February 0.886335E+09 0.00 0.00 94962594.57 0.00 0.00 0.655576E+11 0.00 21.11
March 0.168362E+10 0.00 0.00 0.156280E+09 0.00 0.00 0.714959E+11 0.00 21.05
April 0.114318E+10 13201658.22 0.00 0.152267E+09 0.00 0.00 0.668010E+11 0.00 21.58
May 0.919146E+09 0.304966E+09 0.00 0.107121E+09 5981172.83 0.00 0.558447E+11 0.00 22.54
June 4630729.67 0.149714E+11 0.00 49302095.22 21592692.40 0.00 0.153485E+11 0.00 21.59
July 0.00 0.366884E+11 0.00 6006192.96 33328111.68 0.00 0.779703E+09 0.00 19.77
August 4657399.66 0.224343E+11 0.00 38363155.54 6717926.86 0.00 0.893595E+10 0.00 20.81
September 95313064.37 0.805226E+10 0.00 72706287.73 188095.79 0.00 0.310845E+11 0.00 22.08
October 0.804031E+09 0.510313E+09 0.00 0.117308E+09 0.00 0.00 0.586038E+11 0.00 22.05
November 0.167653E+10 0.00 0.00 0.151119E+09 0.00 0.00 0.701169E+11 0.00 21.07
December 0.775887E+09 0.00 0.00 0.126341E+09 0.00 0.00 0.700023E+11 0.00 21.01
                   
Annual Sum or Average 0.904075E+10 0.829749E+11 0.00 0.119595E+10 67807999.56 0.00 0.586800E+12 0.00 21.30
Minimum of Months 0.00 0.00 0.00 6006192.96 0.00 0.00 0.779703E+09 0.00 19.77
Maximum of Months 0.168362E+10 0.366884E+11 0.00 0.156280E+09 33328111.68 0.00 0.722287E+11 0.00 22.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.267019E+11 0.00 0.00 3576895.57 0.00 0.295790E+09 0.361133E+10 0.00 3.67
February 0.226519E+11 0.00 0.00 5054561.64 0.00 2441685.25 0.528738E+10 0.00 3.71
March 0.195459E+11 0.00 0.00 12148323.34 0.00 0.00 0.108111E+11 0.00 3.67
April 0.152260E+11 8426237.27 0.00 12584314.66 0.00 0.00 0.124475E+11 0.00 3.72
May 0.807489E+10 0.126095E+09 0.00 14991646.23 17352548.85 0.00 0.153310E+11 0.00 3.88
June 0.745221E+09 0.526321E+10 0.00 12980749.38 0.111108E+10 0.00 0.573198E+10 0.00 3.79
July 20425478.23 0.148466E+11 0.00 2220576.40 0.113979E+10 0.00 0.351640E+09 0.00 3.61
August 0.151968E+09 0.988686E+10 0.00 14680080.40 0.387268E+09 0.00 0.393865E+10 0.00 3.96
September 0.230535E+10 0.295522E+10 0.00 26283517.88 0.599345E+09 0.00 0.111156E+11 0.00 4.06
October 0.509605E+10 0.314434E+09 0.00 35689229.86 718168.84 0.00 0.206051E+11 0.00 4.07
November 0.188916E+11 0.00 0.00 9795144.66 0.00 0.00 0.108159E+11 0.00 3.67
December 0.235691E+11 0.00 0.00 6616667.50 0.00 0.00 0.611219E+10 0.00 3.70
                   
Annual Sum or Average 0.142980E+12 0.334009E+11 0.00 0.156622E+09 0.325555E+10 0.298231E+09 0.106159E+12 0.00 3.79
Minimum of Months 20425478.23 0.00 0.00 2220576.40 0.00 0.00 0.351640E+09 0.00 3.61
Maximum of Months 0.267019E+11 0.148466E+11 0.00 35689229.86 0.113979E+10 0.295790E+09 0.206051E+11 0.00 4.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.897285E+11 0.00 0.00 1378465.58 0.00 0.00 0.356560E+10 0.00 1.62
February 0.816198E+11 0.00 0.00 794911.78 0.00 0.00 0.343068E+10 0.00 1.63
March 0.735043E+11 0.00 0.00 14575176.96 0.00 0.00 0.185037E+11 0.00 1.61
April 0.529925E+11 16509845.48 0.00 33654748.47 3041201.16 0.00 0.319233E+11 0.00 1.64
May 0.285636E+11 0.254122E+09 0.00 54901851.27 0.179478E+09 0.00 0.438765E+11 0.00 1.73
June 0.267549E+10 0.143271E+11 0.00 48457356.99 0.576313E+10 0.00 0.179635E+11 0.00 1.74
July 9703719.36 0.441967E+11 0.00 8677839.65 0.650110E+10 0.00 0.121948E+10 0.00 1.66
August 0.389730E+09 0.288479E+11 0.00 48247814.78 0.257903E+10 0.00 0.130769E+11 0.00 1.77
September 0.716167E+10 0.854214E+10 0.00 68735672.25 0.233155E+10 0.00 0.345684E+11 0.00 1.78
October 0.199537E+11 0.675388E+09 0.00 81078108.51 55336294.36 0.00 0.576415E+11 0.00 1.73
November 0.662642E+11 0.00 0.00 18256269.98 0.00 0.00 0.240131E+11 0.00 1.61
December 0.816476E+11 0.00 0.00 2627570.64 0.00 0.00 0.821840E+10 0.00 1.62
                   
Annual Sum or Average 0.504511E+12 0.968598E+11 0.00 0.381386E+09 0.174127E+11 0.00 0.258001E+12 0.00 1.68
Minimum of Months 9703719.36 0.00 0.00 794911.78 0.00 0.00 0.121948E+10 0.00 1.61
Maximum of Months 0.897285E+11 0.441967E+11 0.00 81078108.51 0.650110E+10 0.00 0.576415E+11 0.00 1.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.321473E+09 0.00 0.00 515008.02 0.00 0.123472E+10 37894866.60 0.00 0.47
February 0.334919E+09 0.00 0.00 998578.22 0.00 0.111192E+10 71740375.95 0.00 0.47
March 0.394380E+09 90885.19 0.00 5222743.20 0.00 0.875318E+09 0.378513E+09 0.00 0.47
April 0.363008E+09 2774215.63 0.00 8209828.72 780505.13 0.488785E+09 0.656514E+09 0.00 0.47
May 0.336244E+09 19520725.04 12558.64 11234764.46 8011505.21 60719096.83 0.855054E+09 5669.81 0.47
June 0.120176E+09 0.575988E+09 233632.28 4721802.75 0.147167E+09 149715.58 0.131116E+09 8380.22 0.48
July 2446676.38 0.123337E+10 557979.79 72114.85 0.238947E+09 293.89 1286963.70 12648.22 0.48
August 38442466.98 0.913271E+09 260059.40 2983927.83 99716419.48 22408.91 52554988.47 4078.21 0.48
September 0.220359E+09 0.284983E+09 239284.00 7231363.47 0.105992E+09 1444283.39 0.358132E+09 7822.74 0.47
October 0.312899E+09 63463302.83 74380.80 9504444.39 15277989.84 0.138729E+09 0.828646E+09 3457.39 0.47
November 0.426909E+09 0.00 0.00 1754004.77 0.00 0.879370E+09 0.309575E+09 0.00 0.47
December 0.362985E+09 0.00 0.00 539663.31 0.00 0.113424E+10 63855053.35 0.00 0.47
                   
Annual Sum or Average 0.323424E+10 0.309346E+10 1377894.91 52988243.98 0.615892E+09 0.592543E+10 0.374488E+10 42056.59 0.47
Minimum of Months 2446676.38 0.00 0.00 72114.85 0.00 293.89 1286963.70 0.00 0.47
Maximum of Months 0.426909E+09 0.123337E+10 557979.79 11234764.46 0.238947E+09 0.123472E+10 0.855054E+09 12648.22 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.262866E+09 0.00 0.00 70323.75 0.00 0.132483E+10 6650601.92 0.00 0.47
February 0.265799E+09 0.00 0.00 215532.29 0.00 0.122902E+10 24366015.85 0.00 0.47
March 0.449736E+09 0.00 0.00 2407720.16 90874.54 0.100582E+10 0.195279E+09 0.00 0.47
April 0.407574E+09 1580481.47 0.00 5918704.34 1973822.80 0.549407E+09 0.553440E+09 0.00 0.47
May 0.365425E+09 18783981.80 25139.60 10277466.61 8732603.69 66669764.35 0.820732E+09 5505.67 0.47
June 0.121519E+09 0.573105E+09 239549.74 4515811.53 0.149958E+09 218565.04 0.129880E+09 9621.36 0.48
July 2446389.72 0.122742E+10 618023.94 70975.55 0.244664E+09 293.86 1287943.75 7360.01 0.48
August 38683604.23 0.905047E+09 505956.12 2645421.30 0.107574E+09 39039.90 52624712.84 5453.01 0.48
September 0.238005E+09 0.277859E+09 365865.63 5447692.17 0.112941E+09 3024459.19 0.340620E+09 10662.27 0.47
October 0.393794E+09 51005644.10 84158.19 5542481.51 27711024.15 0.239955E+09 0.650335E+09 9069.61 0.47
November 0.438609E+09 0.00 0.00 528106.40 0.00 0.103717E+10 0.141113E+09 0.00 0.47
December 0.318557E+09 0.00 0.00 35011.79 0.00 0.124037E+10 2477511.04 0.00 0.47
                   
Annual Sum or Average 0.330301E+10 0.305480E+10 1838693.22 37675247.39 0.653646E+09 0.669653E+10 0.291881E+10 47671.93 0.47
Minimum of Months 2446389.72 0.00 0.00 35011.79 0.00 293.86 1287943.75 0.00 0.47
Maximum of Months 0.449736E+09 0.122742E+10 618023.94 10277466.61 0.244664E+09 0.132483E+10 0.820732E+09 10662.27 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.146937E+11 0.00 0.00 2097502.56 0.00 0.650259E+10 0.423060E+09 0.00 0.53
February 0.171678E+11 0.00 0.00 7007627.54 0.00 0.230441E+10 0.112495E+10 0.00 0.53
March 0.189306E+11 1232321.63 0.00 23594077.64 0.00 0.235126E+09 0.322973E+10 0.00 0.53
April 0.160682E+11 48198825.30 0.00 27134407.91 0.00 0.00 0.446727E+10 0.00 0.54
May 0.982102E+10 0.355209E+09 0.00 43783313.34 18350323.33 0.00 0.726376E+10 0.00 0.54
June 0.138102E+10 0.923552E+10 0.00 24007184.84 0.573098E+09 0.00 0.206832E+10 0.00 0.54
July 0.00 0.196825E+11 0.00 1526940.85 0.288431E+09 0.00 50079667.56 0.00 0.54
August 0.178983E+09 0.137235E+11 0.00 23280519.23 15275170.53 0.00 0.107234E+10 0.00 0.54
September 0.273839E+10 0.521144E+10 0.00 59881592.83 93187783.17 0.00 0.516318E+10 0.00 0.54
October 0.580273E+10 0.104949E+10 0.00 92310602.03 19226788.62 0.00 0.115932E+11 0.00 0.54
November 0.168474E+11 0.00 0.00 29286821.07 0.00 96925727.06 0.495970E+10 0.00 0.54
December 0.164932E+11 0.00 0.00 18676087.83 0.00 0.266536E+10 0.199700E+10 0.00 0.54
                   
Annual Sum or Average 0.120123E+12 0.493071E+11 0.00 0.352587E+09 0.100757E+10 0.118044E+11 0.434126E+11 0.00 0.54
Minimum of Months 0.00 0.00 0.00 1526940.85 0.00 0.00 50079667.56 0.00 0.53
Maximum of Months 0.189306E+11 0.196825E+11 0.00 92310602.03 0.573098E+09 0.650259E+10 0.115932E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.561061E+10 0.00 0.00 5657258.05 0.00 0.133760E+11 0.263505E+10 0.00 0.53
February 0.556551E+10 0.00 0.00 2677954.96 0.00 0.129779E+11 0.206370E+10 0.00 0.53
March 0.642756E+10 0.00 0.00 31457594.54 1232658.60 0.565932E+10 0.103069E+11 0.00 0.53
April 0.603542E+10 10713073.01 61839.71 72836185.35 37431187.80 0.707458E+09 0.137525E+11 5904.66 0.54
May 0.585422E+10 0.220882E+09 160480.28 0.109190E+09 0.152581E+09 39802402.67 0.111300E+11 37501.56 0.54
June 0.173490E+10 0.659554E+10 1162303.16 43716694.23 0.321458E+10 747528.68 0.169493E+10 12526.59 0.54
July 33183808.97 0.151591E+11 3471775.05 684678.56 0.481382E+10 0.00 17752232.61 24530.88 0.54
August 0.540692E+09 0.105852E+11 6060773.62 23269976.30 0.315122E+10 300222.08 0.710694E+09 59527.90 0.54
September 0.347144E+10 0.294557E+10 2532214.59 58029169.40 0.235794E+10 18226095.08 0.441594E+10 39148.13 0.54
October 0.594196E+10 0.301222E+09 3241236.52 64124425.98 0.764491E+09 0.121508E+09 0.113654E+11 55430.95 0.54
November 0.633330E+10 0.00 0.00 32364301.20 0.00 0.484717E+10 0.107265E+11 0.00 0.54
December 0.589762E+10 0.00 0.00 5980977.74 0.00 0.118181E+11 0.345832E+10 0.00 0.54
                   
Annual Sum or Average 0.534464E+11 0.358182E+11 16690622.93 0.449989E+09 0.144933E+11 0.495666E+11 0.722777E+11 234570.68 0.54
Minimum of Months 33183808.97 0.00 0.00 684678.56 0.00 0.00 17752232.61 0.00 0.53
Maximum of Months 0.642756E+10 0.151591E+11 6060773.62 0.109190E+09 0.481382E+10 0.133760E+11 0.137525E+11 59527.90 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.338503E+09 0.00 0.00 549125.92 0.00 0.120309E+10 52462060.86 0.00 0.47
February 0.360576E+09 0.00 0.00 819593.26 0.00 0.106986E+10 88322490.78 0.00 0.47
March 0.387671E+09 0.00 0.00 4694252.05 90885.19 0.885766E+09 0.375303E+09 0.00 0.47
April 0.322384E+09 3266250.71 0.00 8413858.38 288470.05 0.478382E+09 0.707338E+09 0.00 0.47
May 0.295191E+09 21541691.36 0.00 12373325.48 6008767.33 68707218.52 0.886980E+09 0.00 0.47
June 0.112515E+09 0.581999E+09 146747.10 5410597.77 0.141243E+09 179237.81 0.138058E+09 7418.08 0.48
July 2347990.22 0.124543E+10 126930.25 91190.71 0.227323E+09 0.00 1366867.89 1940.47 0.48
August 36791955.34 0.923550E+09 146268.48 3376773.39 89552279.15 33259.28 53801804.19 2578.86 0.48
September 0.201375E+09 0.285140E+09 276455.68 8864666.16 0.105799E+09 2064369.44 0.374863E+09 7182.86 0.47
October 0.271354E+09 65815083.34 41019.39 10220150.53 12961852.73 0.149444E+09 0.858760E+09 1175.40 0.47
November 0.418974E+09 0.00 0.00 2895758.08 0.00 0.830537E+09 0.365201E+09 0.00 0.47
December 0.374136E+09 0.00 0.00 1045083.23 0.00 0.109987E+10 86576720.68 0.00 0.47
                   
Annual Sum or Average 0.312182E+10 0.312674E+10 737420.91 58754374.97 0.583268E+09 0.578794E+10 0.398903E+10 20295.66 0.47
Minimum of Months 2347990.22 0.00 0.00 91190.71 0.00 0.00 1366867.89 0.00 0.47
Maximum of Months 0.418974E+09 0.124543E+10 276455.68 12373325.48 0.227323E+09 0.120309E+10 0.886980E+09 7418.08 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.243351E+09 0.00 0.00 84821.56 0.00 0.133281E+10 18173884.18 0.00 0.47
February 0.270155E+09 0.00 0.00 187869.86 0.00 0.121670E+10 32363278.10 0.00 0.47
March 0.453055E+09 0.00 0.00 1905729.88 90874.54 0.101433E+10 0.183948E+09 0.00 0.47
April 0.391074E+09 2911753.57 0.00 5939775.63 642550.69 0.536478E+09 0.582848E+09 0.00 0.47
May 0.302400E+09 20919425.28 0.00 11320395.17 6627805.47 82138305.02 0.867245E+09 0.00 0.47
June 0.112598E+09 0.580891E+09 135073.11 5202274.48 0.142279E+09 179216.81 0.138154E+09 7632.40 0.48
July 2347715.12 0.124362E+10 127375.69 89617.85 0.228959E+09 0.00 1368269.91 1479.93 0.48
August 37004427.67 0.920534E+09 146443.15 2993575.66 92449584.47 30667.56 53964107.38 2386.75 0.48
September 0.212501E+09 0.278030E+09 325652.78 6827893.05 0.112813E+09 4210835.56 0.363558E+09 8365.62 0.47
October 0.425540E+09 62177814.92 233542.74 5579109.58 16386816.69 0.263828E+09 0.594679E+09 11721.70 0.47
November 0.432125E+09 0.00 0.00 1064809.69 0.00 0.998244E+09 0.185984E+09 0.00 0.47
December 0.307437E+09 0.00 0.00 173052.57 0.00 0.122533E+10 28501329.32 0.00 0.47
                   
Annual Sum or Average 0.318959E+10 0.310909E+10 968087.47 41368924.98 0.600247E+09 0.667428E+10 0.305079E+10 31586.40 0.47
Minimum of Months 2347715.12 0.00 0.00 84821.56 0.00 0.00 1368269.91 0.00 0.47
Maximum of Months 0.453055E+09 0.124362E+10 325652.78 11320395.17 0.228959E+09 0.133281E+10 0.867245E+09 11721.70 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.256095E+11 0.00 0.00 0.00 0.00 0.512315E+10 0.00 0.00 0.58
February 0.243777E+11 0.00 0.00 0.00 0.00 0.364956E+10 0.00 0.00 0.58
March 0.300991E+11 0.00 0.00 0.00 0.00 96438782.94 0.00 0.00 0.57
April 0.277695E+11 0.00 0.00 0.00 6442734.25 5863867.33 0.00 0.00 0.58
May 0.235227E+11 0.00 0.00 20024.91 0.142812E+09 0.00 20629169.61 0.00 0.61
June 0.638912E+10 0.399759E+09 0.00 247319.68 0.591916E+10 0.00 95851107.59 0.00 0.59
July 0.265490E+09 0.227806E+10 0.00 373645.19 0.132049E+11 0.00 89010332.41 0.00 0.55
August 0.307934E+10 0.409356E+10 0.00 2307668.32 0.534318E+10 0.00 0.865331E+09 0.00 0.57
September 0.127840E+11 0.812961E+09 0.00 514951.78 0.250812E+10 0.00 0.363516E+09 0.00 0.60
October 0.248176E+11 0.00 0.00 0.00 0.239279E+09 0.00 0.00 0.00 0.60
November 0.295766E+11 0.00 0.00 0.00 0.00 61703468.74 0.00 0.00 0.57
December 0.277986E+11 0.00 0.00 0.00 0.00 0.180912E+10 0.00 0.00 0.58
                   
Annual Sum or Average 0.236089E+12 0.758433E+10 0.00 3463609.88 0.273639E+11 0.107458E+11 0.143434E+10 0.00 0.58
Minimum of Months 0.265490E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
Maximum of Months 0.300991E+11 0.409356E+10 0.00 2307668.32 0.132049E+11 0.512315E+10 0.865331E+09 0.00 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 66702936.56 0.00 0.00 120639.56 0.00 0.325241E+09 6586849.60 0.00 0.47
February 72189553.42 0.00 0.00 246436.27 0.00 0.293528E+09 13932158.60 0.00 0.47
March 93967028.09 22721.30 0.00 1293637.58 0.00 0.239070E+09 79028049.07 0.00 0.47
April 88037961.91 694469.19 0.00 2055599.79 194211.00 0.144700E+09 0.144336E+09 0.00 0.47
May 81115351.37 5098077.60 3221.98 2862048.33 1784979.96 34084918.57 0.197751E+09 1335.13 0.47
June 29663577.96 0.144617E+09 45542.80 1227474.71 36185542.88 45887.08 33103921.69 1552.46 0.48
July 597020.25 0.308882E+09 155896.92 16369.42 59179661.11 73.47 338049.06 3056.83 0.48
August 9608834.88 0.228810E+09 32119.17 734686.52 24469196.81 8384.44 13149042.20 1258.97 0.48
September 55036601.30 71075609.71 63213.99 1765325.40 26664419.55 3099777.66 86889985.53 2426.51 0.47
October 80166311.38 15845155.61 19719.55 2074858.89 3838367.36 62658563.29 0.177545E+09 1540.19 0.47
November 0.102814E+09 0.00 0.00 337968.07 0.00 0.244708E+09 56541682.47 0.00 0.47
December 79647738.35 0.00 0.00 109038.69 0.00 0.300961E+09 9688470.27 0.00 0.47
                   
Annual Sum or Average 0.759547E+09 0.775045E+09 319714.43 12844083.24 0.152316E+09 0.164810E+10 0.818889E+09 11170.09 0.47
Minimum of Months 597020.25 0.00 0.00 16369.42 0.00 73.47 338049.06 0.00 0.47
Maximum of Months 0.102814E+09 0.308882E+09 155896.92 2862048.33 59179661.11 0.325241E+09 0.197751E+09 3056.83 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 40788532.19 0.00 0.00 9343.05 0.00 0.356654E+09 1152880.72 0.00 0.47
February 50697185.90 0.00 0.00 33082.48 0.00 0.324248E+09 4872963.39 0.00 0.47
March 0.103032E+09 0.00 0.00 577616.82 22718.63 0.270756E+09 38945195.08 0.00 0.47
April 98473628.79 412908.26 0.00 1462091.84 475667.81 0.162460E+09 0.116689E+09 0.00 0.47
May 87429320.36 4931888.54 3186.51 2610806.33 1950362.57 36350045.59 0.189386E+09 1370.07 0.47
June 30277605.96 0.144041E+09 54013.11 1176139.94 36731699.96 45881.71 32533730.52 1574.11 0.48
July 596950.30 0.307929E+09 127152.30 16063.70 60117728.10 73.46 338313.26 3517.78 0.48
August 9665301.14 0.226983E+09 108033.03 642991.97 26189333.91 6889.44 13183012.02 2700.48 0.48
September 58997065.62 69594417.54 58595.70 1281455.94 28138916.14 3640842.88 82855126.65 2281.01 0.47
October 0.100333E+09 13209607.93 16094.52 1129733.19 6474210.81 95000274.58 0.125944E+09 2560.75 0.47
November 95094549.81 0.00 0.00 104406.50 0.00 0.293575E+09 15580618.15 0.00 0.47
December 57085645.62 0.00 0.00 6624.13 0.00 0.332965E+09 303594.87 0.00 0.47
                   
Annual Sum or Average 0.732470E+09 0.767102E+09 367075.18 9050355.88 0.160101E+09 0.187570E+10 0.621784E+09 14004.19 0.47
Minimum of Months 596950.30 0.00 0.00 6624.13 0.00 73.46 303594.87 0.00 0.47
Maximum of Months 0.103032E+09 0.307929E+09 127152.30 2610806.33 60117728.10 0.356654E+09 0.189386E+09 3517.78 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.468939E+09 0.00 0.00 5191524.92 0.00 0.167515E+10 0.411851E+09 0.00 0.53
February 0.407834E+09 0.00 0.00 6837340.41 0.00 0.137479E+10 0.651179E+09 0.00 0.54
March 0.486307E+09 145972.73 0.00 14438897.87 0.00 0.105063E+10 0.110424E+10 0.00 0.53
April 0.513997E+09 4947215.49 0.00 14161343.86 762100.91 0.590548E+09 0.131701E+10 0.00 0.54
May 0.522618E+09 30089337.47 18036.71 15049520.85 14136624.37 55327533.59 0.143594E+10 5408.51 0.54
June 0.192367E+09 0.912496E+09 483333.62 6003472.07 0.248871E+09 377705.13 0.212681E+09 14270.25 0.54
July 3929661.59 0.196671E+10 769535.78 94714.62 0.398132E+09 0.00 2088603.81 16720.12 0.54
August 61634483.71 0.146043E+10 666918.57 4435137.23 0.166295E+09 11196.58 84900772.74 11010.29 0.54
September 0.342957E+09 0.456905E+09 70396.51 14085543.00 0.171372E+09 1647187.22 0.584372E+09 3957.91 0.54
October 0.413602E+09 0.106973E+09 62998.19 22876536.70 19552849.68 94091404.59 0.154097E+10 4771.80 0.54
November 0.521129E+09 0.00 0.00 10556694.82 0.00 0.970493E+09 0.109590E+10 0.00 0.54
December 0.449750E+09 0.00 0.00 8760097.66 0.00 0.140536E+10 0.644289E+09 0.00 0.54
                   
Annual Sum or Average 0.438506E+10 0.493870E+10 2071219.38 0.122491E+09 0.101912E+10 0.721842E+10 0.908542E+10 56138.89 0.54
Minimum of Months 3929661.59 0.00 0.00 94714.62 0.00 0.00 2088603.81 0.00 0.53
Maximum of Months 0.522618E+09 0.196671E+10 769535.78 22876536.70 0.398132E+09 0.167515E+10 0.154097E+10 16720.12 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109811E+11 0.00 0.00 47533044.08 0.00 0.00 0.338111E+11 0.00 3.98
February 0.947895E+10 0.00 0.00 35983807.30 0.00 0.00 0.308254E+11 0.00 3.97
March 0.504345E+10 0.00 0.00 84783631.46 0.00 0.00 0.418506E+11 0.00 4.16
April 0.200569E+10 9549371.22 0.00 0.102208E+09 0.00 0.00 0.437989E+11 0.00 4.47
May 0.108482E+09 0.218918E+09 0.00 97591407.27 157852.29 0.00 0.410047E+11 0.00 4.90
June 0.00 0.109612E+11 0.00 47709701.91 0.00 0.00 0.121906E+11 0.00 5.02
July 0.00 0.281889E+11 0.00 5912695.12 0.00 0.00 0.699766E+09 0.00 4.76
August 0.00 0.169903E+11 0.00 35709821.41 0.00 0.00 0.765536E+10 0.00 4.95
September 59067402.02 0.575414E+10 0.00 63445699.15 0.00 0.00 0.231158E+11 0.00 4.92
October 0.881451E+09 0.339576E+09 0.00 86649996.42 7114889.06 0.00 0.402784E+11 0.00 4.62
November 0.494087E+10 0.00 0.00 79121421.83 0.00 0.00 0.411249E+11 0.00 4.17
December 0.848843E+10 0.00 0.00 51832407.72 0.00 0.00 0.351029E+11 0.00 4.02
                   
Annual Sum or Average 0.419875E+11 0.624627E+11 0.00 0.738481E+09 7272741.34 0.00 0.351458E+12 0.00 4.50
Minimum of Months 0.00 0.00 0.00 5912695.12 0.00 0.00 0.699766E+09 0.00 3.97
Maximum of Months 0.109811E+11 0.281889E+11 0.00 0.102208E+09 7114889.06 0.00 0.437989E+11 0.00 5.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.627643E+10 0.00 0.00 66681856.26 0.00 0.00 0.422750E+11 0.00 4.31
February 0.578184E+10 0.00 0.00 50365540.96 0.00 0.00 0.377927E+11 0.00 4.29
March 0.221095E+10 0.00 0.00 0.111072E+09 0.00 0.00 0.490462E+11 0.00 4.54
April 0.706460E+09 10438578.31 0.00 0.126764E+09 0.00 0.00 0.493314E+11 0.00 4.87
May 13280264.22 0.236547E+09 0.00 0.111376E+09 0.00 0.00 0.445611E+11 0.00 5.31
June 0.00 0.117278E+11 0.00 52117077.62 0.00 0.00 0.130055E+11 0.00 5.37
July 0.00 0.300172E+11 0.00 6263710.66 0.00 0.00 0.736807E+09 0.00 5.06
August 0.00 0.180735E+11 0.00 38724387.53 0.00 0.00 0.809405E+10 0.00 5.26
September 817585.82 0.615256E+10 0.00 71277992.28 0.00 0.00 0.249251E+11 0.00 5.28
October 0.314585E+09 0.372438E+09 0.00 0.102216E+09 66246.38 0.00 0.442260E+11 0.00 4.99
November 0.183379E+10 0.00 0.00 0.105342E+09 0.00 0.00 0.484871E+11 0.00 4.54
December 0.297727E+10 0.00 0.00 72094007.26 0.00 0.00 0.445742E+11 0.00 4.38
                   
Annual Sum or Average 0.201154E+11 0.665905E+11 0.00 0.914294E+09 66246.38 0.00 0.407055E+12 0.00 4.85
Minimum of Months 0.00 0.00 0.00 6263710.66 0.00 0.00 0.736807E+09 0.00 4.29
Maximum of Months 0.627643E+10 0.300172E+11 0.00 0.126764E+09 66246.38 0.00 0.493314E+11 0.00 5.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 11056627.20 0.00 0.00 0.160157E+09 0.00 0.00 0.655364E+11 0.00 18.79
February 7908696.61 0.00 0.00 0.125628E+09 0.00 0.00 0.598472E+11 0.00 18.99
March 0.107806E+09 0.00 0.00 0.207381E+09 0.00 0.00 0.667667E+11 0.00 19.41
April 48155343.69 17767030.85 0.00 0.196587E+09 0.00 0.00 0.622489E+11 0.00 20.40
May 20191553.17 0.393478E+09 0.00 0.140080E+09 0.00 0.00 0.518469E+11 0.00 21.88
June 0.00 0.159732E+11 0.00 62554566.14 0.00 0.00 0.135130E+11 0.00 21.21
July 0.00 0.376644E+11 0.00 6235127.11 0.00 0.00 0.659096E+09 0.00 19.79
August 0.00 0.236752E+11 0.00 45017701.14 0.00 0.00 0.765834E+10 0.00 20.64
September 0.00 0.821321E+10 0.00 94259799.04 0.00 0.00 0.283654E+11 0.00 21.53
October 76872421.25 0.656898E+09 0.00 0.149423E+09 0.00 0.00 0.545954E+11 0.00 21.02
November 0.176873E+09 0.00 0.00 0.188817E+09 0.00 0.00 0.651941E+11 0.00 19.40
December 45650420.36 0.00 0.00 0.162004E+09 0.00 0.00 0.637087E+11 0.00 19.03
                   
Annual Sum or Average 0.494514E+09 0.865941E+11 0.00 0.153814E+10 0.00 0.00 0.539940E+12 0.00 20.18
Minimum of Months 0.00 0.00 0.00 6235127.11 0.00 0.00 0.659096E+09 0.00 18.79
Maximum of Months 0.176873E+09 0.376644E+11 0.00 0.207381E+09 0.00 0.00 0.667667E+11 0.00 21.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.113230E+11 0.00 0.00 0.00 0.00 0.399396E+10 0.00 0.00 1.09
February 0.101821E+11 0.00 0.00 0.00 0.00 0.378656E+10 0.00 0.00 1.10
March 0.148837E+11 0.00 0.00 0.00 0.00 0.165622E+09 0.00 0.00 1.08
April 0.138312E+11 0.00 0.00 8608.09 3211018.36 414263.14 11488855.55 0.00 1.10
May 0.116609E+11 56165108.05 0.00 99535.42 17410266.33 0.00 72816400.61 0.00 1.15
June 0.297003E+10 0.163948E+10 0.00 840259.77 0.154930E+10 0.00 0.261443E+09 0.00 1.12
July 79496134.05 0.579812E+10 0.00 403026.42 0.221807E+10 0.00 97083264.23 0.00 1.07
August 0.145535E+10 0.447695E+10 0.00 1669419.95 0.619419E+09 0.00 0.510081E+09 0.00 1.14
September 0.614843E+10 0.609671E+09 0.00 1074007.81 0.107291E+10 0.00 0.404258E+09 0.00 1.15
October 0.123590E+11 31771839.52 0.00 16475.86 87483462.85 0.00 9908987.05 0.00 1.13
November 0.143709E+11 0.00 0.00 0.00 0.00 0.400635E+09 0.00 0.00 1.08
December 0.139533E+11 0.00 0.00 0.00 0.00 0.803004E+09 0.00 0.00 1.09
                   
Annual Sum or Average 0.113217E+12 0.126122E+11 0.00 4111333.32 0.556780E+10 0.915020E+10 0.136708E+10 0.00 1.11
Minimum of Months 79496134.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.07
Maximum of Months 0.148837E+11 0.579812E+10 0.00 1669419.95 0.221807E+10 0.399396E+10 0.510081E+09 0.00 1.15



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.139159E+12 0.202885E+11 0.254725E+12 0.103947E+13 0.804229E+11
February 0.230815E+12 0.193730E+11 0.240497E+12 0.993653E+12 0.724661E+11
March 0.415303E+12 0.165127E+11 0.208863E+12 0.862658E+12 0.795282E+11
April 0.443313E+12 0.114618E+11 0.145142E+12 0.610927E+12 0.142261E+12
May 0.572294E+12 0.747425E+10 0.888299E+11 0.403637E+12 0.316287E+12
June 0.569247E+12 -0.120338E+10 -0.165699E+11 -0.622399E+11 0.966680E+12
July 0.541417E+12 -0.901463E+10 -0.108640E+12 -0.483433E+12 0.145822E+13
August 0.516733E+12 -0.515520E+10 -0.679233E+11 -0.281066E+12 0.125317E+13
September 0.355049E+12 0.232691E+10 0.279087E+11 0.131897E+12 0.714732E+12
October 0.341729E+12 0.899619E+10 0.105333E+12 0.477680E+12 0.326027E+12
November 0.165142E+12 0.143541E+11 0.183986E+12 0.764991E+12 0.802021E+11
December 0.111858E+12 0.182772E+11 0.235919E+12 0.958469E+12 0.710156E+11
           
Annual Sum or Average 0.440206E+13 0.103691E+12 0.129807E+13 0.541664E+13 0.556101E+13
Minimum of Months 0.111858E+12 -0.901463E+10 -0.108640E+12 -0.483433E+12 0.710156E+11
Maximum of Months 0.572294E+12 0.202885E+11 0.254725E+12 0.103947E+13 0.145822E+13