Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885

Simulation Timestamp: 2023-10-16 08:41:37


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10578.33 932.40 932.40
Net Site Energy 10578.33 932.40 932.40
Total Source Energy 21226.06 1870.91 1870.91
Net Source Energy 21226.06 1870.91 1870.91


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 775.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 268.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 867.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 650.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 534.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 69.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 221.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 3328.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4685.14 5893.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 775.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 268.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 867.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 31.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 534.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 69.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 221.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 3328.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 775.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 268.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 867.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 650.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 534.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 69.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 221.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 3328.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 84.95 361.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 228.48 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 412.96 519.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 99.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 84.95 361.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 228.48 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 412.96 519.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4685.143 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4685.143 100.00
     
Total On-Site and Utility Electric Sources 4685.143 100.00
Total Electricity End Uses 4685.143 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1.39 0.04
Air to Air Heat Recovery for Heating 3088.81 99.96
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3090.20 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 27.83
Time Setpoint Not Met During Occupied Cooling 541.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 7392.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
RunPeriod RUNPERIOD 1
Weather File William R Fairchild WA USA TMY3 WMO#=727885
Latitude [deg] 48.12
Longitude [deg] -123.5
Elevation [m] 91.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 10.3255 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.5625 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.5625 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.5208 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 7.7005 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 6.4583 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 11.5174 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 9.6875 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 9.7951 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 9.7951 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 7.1042 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 9.7951 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 9.7951 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 11.5174 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 11.5174 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 13.0243 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 7.1042 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 9.4981 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 9.4981 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 10.3255 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.5625 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.5625 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.5208 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 7.7005 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 6.4583 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 11.5174 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 9.6875 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 9.7951 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 9.7951 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 9.7951 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 9.7951 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 9.7951 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 9.7951 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 7.1042 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 9.7951 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 9.7951 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 9.7951 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 11.5174 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 11.5174 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 13.0243 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 7.1042 18.58 0.0000  
Total 11345.29             9.4981 3.54 41.0709  
Conditioned Total 11345.29             9.4981 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 5.0165 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 22-JUL-18:19 22-JAN-18:30 - - - - - - - - - - 06-JAN-21:19
Heating 0.00 156757.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 120773.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 56968.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 74651.16 100066.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31717.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27645.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4096.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4060.69 270897.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2385.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 332236.78 527721.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 156757.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 120773.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 56968.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 44668.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 25090.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1413.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 27645.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 4096.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4060.69 270897.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 216.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1088.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1080.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 840.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 850.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2747.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 828.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5251.45 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2058.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1694.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 220.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 702.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.39 3608.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 196.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 14837.85 6388.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 74.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 242.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 149.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 19.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 61.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 318.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1307.84 563.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 74.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 242.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 149.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 19.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 61.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 318.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1307.84 563.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.70 0.557571 0.506000 1.37 1.00 0.500000 0.000683 0.000076 1.37 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.472138 0.108249 0.506000 0.238902 0.506000 0.500000 0.003520 0.000031 0.238902 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.240678 0.245904 0.506000 0.121783 0.655745 0.500000 0.001549 0.000012 0.121783 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.168552 0.742519 0.506000 0.085287 1.00 0.500000 0.000513 0.000016 0.085287 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.110580 0.652980 0.506000 0.055954 1.00 0.500000 0.000583 0.000011 0.055954 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.28 0.071839 0.506000 1.66 0.506000 0.500000 0.021045 0.000092 1.66 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.84 0.078196 0.506000 0.931254 0.506000 0.500000 0.004872 0.000095 0.931254 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.11 0.195263 0.506000 2.58 0.520702 0.500000 0.001951 0.000238 2.58 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.63 0.729585 0.506000 0.823172 1.00 0.500000 0.000522 0.000108 0.823172 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.15 0.117696 0.506000 1.09 0.506000 0.500000 0.003237 0.000095 1.09 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.25 0.112379 0.506000 1.14 0.506000 0.500000 0.003390 0.000099 1.14 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.29 0.061931 0.506000 1.16 0.506000 0.500000 0.011065 0.000064 1.16 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.832958 0.377017 0.506000 0.421477 1.00 0.500000 0.001011 0.000067 0.421477 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 8634.70 0.000076 182.03
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3580.83 0.000031 82.78
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1397.95 0.000012 31.09
MECH_FLR_1 VAV BOX REHEAT COIL 1824.80 0.000016 45.50
STORAGE_FLR_1 VAV BOX REHEAT COIL 1266.84 0.000011 32.08
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10471.30 0.000092 220.72
CAFE_FLR_1 VAV BOX REHEAT COIL 10804.03 0.000095 240.62
LOBBY_FLR_1 VAV BOX REHEAT COIL 27205.86 0.000238 599.02
ROOM_1_FLR_3 FAN COIL HEATING COIL 5056.40 0.000044 144.50
ROOM_2_FLR_3 FAN COIL HEATING COIL 5062.01 0.000044 144.66
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 28947.87 0.000253 827.25
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 29066.92 0.000254 830.65
ROOM_5_FLR_3 FAN COIL HEATING COIL 5044.60 0.000044 144.16
ROOM_6_FLR_3 FAN COIL HEATING COIL 5050.21 0.000044 144.32
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12293.46 0.000108 284.01
ROOM_1_FLR_6 FAN COIL HEATING COIL 1553.13 0.000014 44.38
ROOM_2_FLR_6 FAN COIL HEATING COIL 1554.52 0.000014 44.42
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 7456.79 0.000065 213.09
BANQUET_FLR_6 VAV BOX REHEAT COIL 10889.18 0.000095 238.49
DINING_FLR_6 VAV BOX REHEAT COIL 11263.32 0.000099 246.37
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7368.27 0.000064 155.42
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7714.35 0.000067 185.27
VAV WITH REHEAT HEATING COIL 173055.20 0.001514 2952.81
FLR_3_DOAS HEATING COIL 15471.26 0.000135 263.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.24 0.000044 0.000487
ROOM_2_FLR_3 FAN COIL 1.11 0.000044 0.000437
ROOM_3_MULT19_FLR_3 FAN COIL 8.96 0.000253 0.003460
ROOM_4_MULT19_FLR_3 FAN COIL 5.70 0.000254 0.002352
ROOM_5_FLR_3 FAN COIL 1.13 0.000044 0.000444
ROOM_6_FLR_3 FAN COIL 1.02 0.000044 0.000401
ROOM_1_FLR_6 FAN COIL 0.326693 0.000014 0.000128
ROOM_2_FLR_6 FAN COIL 0.290900 0.000014 0.000114
ROOM_3_MULT9_FLR_6 FAN COIL 1.81 0.000065 0.000715
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.24
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.11
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 8.96
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.70
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.13
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.02
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.326693
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.290900
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.81
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008558 12.80 0.008500 0.000487 1.24  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008564 12.80 0.008500 0.000437 1.11  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008499 12.80 0.008499 0.003460 8.96  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008743 12.80 0.008500 0.002352 5.70  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008563 12.80 0.008500 0.000444 1.13  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008570 12.80 0.008500 0.000401 1.02  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008555 12.80 0.008500 0.000128 0.326693  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008561 12.80 0.008500 0.000114 0.290900  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008591 12.80 0.008500 0.000715 1.81  
VAV WITH REHEAT COOLING COIL 25.21 6.70 0.008989 10.96 0.008500 0.015423 22.95 431806.07
FLR_3_DOAS COOLING COIL 26.40 6.70 0.008407 11.92 0.008407 0.001290 2.05 36112.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.67 11.67 23.07 11.67 22.95 22.95 0.300000 0.508721 22.95
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 22.95 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.95
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.015423 0.000031
VAV WITH REHEAT_HEATC_CONTROLLER 0.001514  
FLR_3_DOAS_COOLC_CONTROLLER 0.001290 0.000369
FLR_3_DOAS_HEATC_CONTROLLER 0.000135  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.025252 4122.85  
HEATSYS1 PUMP 0.003430 1032.87 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003430 0.411562
COOLSYS1 0.025252 3.03
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 392033.80 392033.80 0.003430
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.025252 2854.39
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.025252 706983.42 707615.30 80.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.30 6.70 4.10 4.20 4.20 5.90 9.00 10.00 13.30 15.00 15.70 13.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 William R Fairchild WA USA TMY3 WMO#=727885 48.12 -123.50 -8.00 91.00 100237 1.1914


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.23 11.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 10.325 5.380 0.000 0.000 0.000 0.000 15.705 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.563 10.760 0.000 0.000 0.000 0.000 24.323 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.563 10.760 0.000 0.000 0.000 0.000 24.323 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.521 5.380 0.000 0.000 0.000 0.000 9.901 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 7.700 2.690 0.000 0.000 0.000 0.000 10.390 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 6.458 61.680 535.850 0.000 0.000 0.000 603.988 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 11.517 5.380 0.000 0.000 0.000 0.000 16.897 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 9.795 10.520 0.000 0.000 0.000 0.000 20.315 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 9.795 10.520 0.000 0.000 0.000 0.000 20.315 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 9.795 6.750 0.000 0.000 0.000 0.000 16.545 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 9.795 10.520 0.000 0.000 0.000 0.000 20.315 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 11.517 67.820 0.000 0.000 0.000 0.000 79.337 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 11.517 67.820 0.000 0.000 0.000 0.000 79.337 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 13.024 515.227 2419.260 0.000 0.000 0.000 2947.512 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 20432.332 10.325 191.855 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 20432.332
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 909.656 13.563 84.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 909.656
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1053.385 13.563 84.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1053.385
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 742.517 4.521 279.984 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 742.517
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 729.693 7.700 357.693 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 729.693
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 504.005 6.458 60.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 504.005
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 2175.192 11.517 15.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2175.192
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 12673.066 9.688 30.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 12673.066
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 382.227 9.795 254.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.227
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 382.182 9.795 254.788 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.182
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 240.215 9.795 160.143 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 240.215
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 240.280 9.795 160.187 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 240.280
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 382.227 9.795 254.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.227
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 382.182 9.795 254.788 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.182
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2766.397 7.104 132.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2766.397
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 382.227 9.795 254.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.227
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 382.182 9.795 254.788 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 382.182
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 240.280 9.795 160.187 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 240.280
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3819.822 11.517 15.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3819.822
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3819.822 11.517 15.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3819.822
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1345.470 13.024 60.503 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1345.470
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2927.804 7.104 132.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2927.804


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.839 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 2.839 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.7214 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 0.9169 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 0.9299 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 0.8441 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 0.8569 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.2277 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.2277 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3522
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.3522
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.219
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9233
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.9080
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.017
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.9996
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.131
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.131
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.8391315 2.8391315 2.8391315  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 2.8391315 2.8391315 2.8391315  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.17110984E-14 0.24103936E-16 -0.15943139E-09 0.44685538E-16
29 8 0.23237837E-07 0.98082464E-13 0.39196772E-03 -0.26422217E-09
30 7 -0.12664044E-01 0.50206963E-08 -0.23693971E-01 0.14399480E-03
31 6 0.41682950 0.17394333E-05 0.48185553 -0.48830741E-02
32 5 -5.3025782 0.64717486E-04 -4.5162048 0.64572787E-01
33 4 33.498276 0.52771084E-03 21.733161 -0.42870077
34 3 -112.28016 0.11468200E-02 -56.202879 1.5304215
35 2 198.17562 0.64344368E-03 78.405936 -2.9173034
36 1 -171.55028 0.68528185E-04 -55.409506 2.7523484
37 0 57.057407 0.38903588E-06 15.533392  
38 9 -0.29206544E-14 0.31488305E-16 -0.15031727E-09 0.48064473E-16
39 8 0.21958778E-07 0.12356532E-12 0.37867817E-03 -0.24967887E-09
40 7 -0.12267989E-01 0.64094198E-08 -0.23123879E-01 0.13949151E-03
41 6 0.40606866 0.22324768E-05 0.47270315 -0.47562292E-02
42 5 -5.1975737 0.83445227E-04 -4.4459647 0.63270770E-01
43 4 33.033866 0.68326082E-03 21.458733 -0.42253461
44 3 -111.29222 0.14903991E-02 -55.660391 1.5161481
45 2 197.19665 0.83899866E-03 77.908180 -2.9017570
46 1 -171.18874 0.89630080E-04 -55.264364 2.7460119
47 0 57.057407 0.51068186E-06 15.557036  
48 9 -0.29497736E-14 0.32939851E-16 -0.14970570E-09 0.45584202E-16
49 8 0.21872815E-07 0.12523736E-12 0.37777579E-03 -0.24870145E-09
50 7 -0.12241065E-01 0.65023057E-08 -0.23085114E-01 0.13918537E-03
51 6 0.40533708 0.22656711E-05 0.47208016 -0.47476058E-02
52 5 -5.1904345 0.84713026E-04 -4.4411801 0.63182247E-01
53 4 33.002288 0.69384191E-03 21.440032 -0.42211534
54 3 -111.22504 0.15138688E-02 -55.623419 1.5151774
55 2 197.13007 0.85240592E-03 77.874271 -2.9006996
56 1 -171.16415 0.91081681E-04 -55.254501 2.7455809
57 0 57.057407 0.51907125E-06 15.558664  
58 9 -0.24257523E-14 0.33690592E-16 -0.15372093E-09 0.39666009E-16
59 8 0.22436951E-07 0.11417013E-12 0.38367618E-03 -0.25511586E-09
60 7 -0.12417040E-01 0.58916776E-08 -0.23338459E-01 0.14118628E-03
61 6 0.41011853 0.20479623E-05 0.47615013 -0.48039676E-02
62 5 -5.2370942 0.76414309E-04 -4.4724296 0.63760808E-01
63 4 33.208666 0.62469949E-03 21.562156 -0.42485549
64 3 -111.66410 0.13607335E-02 -55.864850 1.5215209
65 2 197.56520 0.76503996E-03 78.095736 -2.9076095
66 1 -171.32486 0.81633884E-04 -55.318971 2.7483976
67 0 57.057407 0.46449959E-06 15.548073  
68 9 -0.24053431E-14 0.30582108E-16 -0.15312349E-09 0.40258954E-16
69 8 0.22353057E-07 0.11582316E-12 0.38280191E-03 -0.25416195E-09
70 7 -0.12390977E-01 0.59826426E-08 -0.23300939E-01 0.14088992E-03
71 6 0.40941037 0.20803184E-05 0.47554760 -0.47956200E-02
72 5 -5.2301838 0.77645268E-04 -4.4678046 0.63675121E-01
73 4 33.178102 0.63493787E-03 21.544084 -0.42444968
74 3 -111.59908 0.13833754E-02 -55.829123 1.5205815
75 2 197.50076 0.77794062E-03 78.062960 -2.9065863
76 1 -171.30107 0.83027327E-04 -55.309421 2.7479805
77 0 57.057407 0.47253235E-06 15.549635  
78 7 -0.14139450E-14 -0.18802902E-16 -0.22311785E-13 0.54375338E-15
79 6 0.16999971E-10 0.27590984E-11 0.52267399E-09 -0.18616555E-10
80 5 -0.63950587E-07 0.13451749E-07 -0.21905428E-05 0.17144787E-06
81 4 0.72477507E-04 0.50724086E-05 0.17668371E-02 -0.28223350E-03
82 3 -0.10573811E-01 0.17927531E-03 -0.21549182 0.43318087E-01
83 2 0.15010112 0.77388015E-03 2.8998331 -0.61891034
84 1 -0.37982851 0.49528818E-03 -7.1368477 1.5694772
85 0 0.24168561 0.34021171E-05 4.4521969  
86 7 -0.22311785E-13 -0.18802902E-16 -0.14139450E-14 0.54375338E-15
87 6 0.52267399E-09 0.27590984E-11 0.16999971E-10 -0.18616555E-10
88 5 -0.21905428E-05 0.13451749E-07 -0.63950587E-07 0.17144787E-06
89 4 0.17668371E-02 0.50724086E-05 0.72477507E-04 -0.28223350E-03
90 3 -0.21549182 0.17927531E-03 -0.10573811E-01 0.43318087E-01
91 2 2.8998331 0.77388015E-03 0.15010112 -0.61891034
92 1 -7.1368477 0.49528818E-03 -0.37982851 1.5694772
93 0 4.4521969 0.34021171E-05 0.24168561  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.418_SHGC_0.4 37 1 VerySmooth 2.375 2.375 1.000 0.401    
2 RESWINDOW_U_0.418_SHGC_0.4 38 1 VerySmooth 2.375 2.375 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.05070E-002 0.31435 0.47518 0.47518 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12234 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.05070E-002 0.31435 0.47518 0.47518 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 0.12234 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.260 2.5713E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1688
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.6533E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1928
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1124
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1122
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.5543E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.6285E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.5376E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1921
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1152
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.2202
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1335
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1241
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.6724E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 5.1970E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 2.1022E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.2325E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.4454E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.2610E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.8519E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.1029E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.2380E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.5560E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.6155E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.2325E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.4454E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.2610E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.8519E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.1029E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.2380E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.5560E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.6155E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 36825.22145 36825.22145 2.70435 2.70435 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 23.53350 8.40259E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 1486.69508 1486.69508 6.44085E-002 0.85446 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 6428.60649 6428.60649 0.47214 0.47214 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2334.12551 2334.12551 0.10112 0.10112 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3276.95715 3276.95715 0.24068 0.24068 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 26.21800 8.40679E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 762.48300 762.48300 3.30328E-002 9.17347E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2295.41768 2295.41768 0.16855 0.16855 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 26.30900 8.40693E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1379.89632 1379.89632 5.97805E-002 5.97805E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1505.91567 1505.91567 0.11058 0.11058 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 26.40000 8.40708E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 974.89556 974.89556 4.22350E-002 5.77652E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44728.95337 44728.95337 3.28474 3.28474 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 26.40000 8.40708E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1802.04345 1802.04345 7.80672E-002 7.80672E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 25039.27323 25039.27323 1.84042 1.84042 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 5943.66498 5943.66498 0.25749 0.67639 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 69489.94269 69489.94269 5.10510 5.10510 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 13725.59874 13725.59874 0.59463 1.89399 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 12539.00297 12539.00297 1.24082 1.24082 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 25.36867 8.40546E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 5056.48933 5056.48933 0.22034 0.22034 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11249.87606 11249.87606 1.11325 1.11325 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 25.12600 8.40508E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 5062.09447 5062.09447 0.22058 0.22058 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 90558.90142 90558.90142 8.96101 8.96101 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 28948.10642 28948.10642 1.26147 1.26147 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 57646.14341 57646.14341 5.70466 5.70466 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26.40000 8.40708E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 29067.16044 29067.16044 1.26666 1.26666 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 11411.92103 11411.92103 1.12928 1.12928 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 22.94200 8.40167E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 5044.68859 5044.68859 0.21983 0.21983 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10308.33752 10308.33752 1.02008 1.02008 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.65283 8.39969E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 5050.29612 5050.29612 0.22007 0.22007 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 22153.02747 22153.02747 1.62682 1.62682 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 26.40000 8.40708E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 7996.71509 7996.71509 0.34644 0.47476 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3301.37459 3301.37459 0.32669 0.32669 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 25.49000 8.40565E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1553.15479 1553.15479 6.76800E-002 6.76800E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2939.67401 2939.67401 0.29090 0.29090 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 25.12600 8.40508E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1554.54331 1554.54331 6.77405E-002 6.77405E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 18264.61324 18264.61324 1.80745 1.80745 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 7456.88911 7456.88911 0.32494 0.32494 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29203.81804 29203.81804 2.14725 2.14725 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 26.40000 8.40708E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5217.09721 5217.09721 0.22602 1.18780 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30586.12172 30586.12172 2.24885 2.24885 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 26.40000 8.40708E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 5323.24370 5323.24370 0.23061 1.18780 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 -4.30000 2.65759E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 31051.10640 31051.10640 2.28616 2.28616 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 25.58100 8.40579E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1357.43409 1357.43409 5.87980E-002 0.36735 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -4.30000 2.65759E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 11342.77600 11342.77600 0.83296 0.83296 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 26.40000 8.40708E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 5513.91199 5513.91199 0.23888 0.23888 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 -4.30000 2.65759E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 340907.87 22.94520 22.94520 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 182766.73 7.26985 7.26985 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00
3 FLR_3_DOAS Cooling Sensible 33397.10 20.19801 2.05125 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 FLR_3_DOAS Heating Sensible 51569.06 3.86931 2.05125 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.70435
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.55757
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.36840
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.83321E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.55401E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.36840
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8634.70238
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.55401E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 182.02514
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.47214
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10825
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23890
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50600
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.51967E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.13266E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23890
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3580.82661
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.13266E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 82.77808
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24068
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24590
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12178
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65574
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54938E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22299E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12178
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1397.95323
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22299E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 31.09268
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.16855
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.74252
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.52874E-002
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.13118E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.59641E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.52874E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1824.79912
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.59641E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 45.49569
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.11058
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.65298
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.59535E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.83479E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.10829E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.59535E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1266.84434
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.10829E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 32.08079
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.28474
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.18393E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.66208
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50600
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.10454E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.16075E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.66208
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10471.29527
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.16075E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 220.71966
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.84042
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.81955E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.93125
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50600
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.87240E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.45183E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.93125
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10804.02530
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.45183E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 240.61518
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.10510
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19526
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.58318
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52070
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.95121E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.38009E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.58318
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27205.85924
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.38009E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 599.01679
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.24082
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.24082
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.42356E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.86754E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68926
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55751E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.86754E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.24082
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5056.40403
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.42356E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 144.50116
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.11325
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.11325
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.42847E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.37491E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68925
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56400E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.37491E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.11325
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5062.00908
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.42847E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 144.66129
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.96101
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 8.96101
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.53249E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.45969E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68967
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49880E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49880E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.45969E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.96101
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 28947.86890
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.53249E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 827.25316
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.70466
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.70466
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.54290E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.35196E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68878
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.74269E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.35196E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.70466
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 29066.92199
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.54290E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 830.65453
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.12928
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.12928
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.41324E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.43689E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68925
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56315E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.43689E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.12928
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5044.60348
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.41324E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 144.16402
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.02008
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.02008
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.41814E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.01496E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68924
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56962E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.01496E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.02008
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5050.21092
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.41814E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 144.32422
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.62682
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.72958
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.82317
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.22215E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07549E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.82317
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12293.46463
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07549E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 284.01419
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.32669
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.32669
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.35875E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.28055E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68926
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55464E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.28055E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.32669
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1553.12941
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.35875E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 44.38270
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.29090
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.29090
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.35996E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.14236E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68926
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56132E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.14236E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.29090
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1554.51791
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.35996E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 44.42237
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.80745
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.80745
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.52353E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.15480E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68903
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.59059E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.15480E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.80745
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7456.79116
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.52353E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 213.08568
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14725
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11770
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.08651
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50600
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.23715E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.52633E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.08651
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10889.17651
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.52633E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 238.49289
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.24885
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11238
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.13792
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50600
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.39032E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.85364E-005
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.13792
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11263.31505
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.85364E-005
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 246.36508
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.28616
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.19311E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.15680
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50600
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10652E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.44608E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.15680
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7368.27065
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.44608E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 155.42089
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.83296
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37702
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50600
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.42148
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.01057E-003
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.74885E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42148
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7714.34610
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.74885E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 185.27008
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.67271
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.67271
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 23.06860
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.67271
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.94520
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.94520
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.50872
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.94520
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.94520
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.21499
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.95895
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.98897E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 431806.06566
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.54231E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.94520
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 173055.20466
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.51396E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2952.80989
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.94520
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.54231E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.08751E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.51396E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 26.40000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91985
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 36112.10278
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.28984E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 15471.26131
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.35349E-004
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 263.98335
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.28984E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 3.69186E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.35349E-004
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.52518E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 4122.84892
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.42968E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.41156
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.42968E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1032.86982
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 392033.80127
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 392033.80000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.42968E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.52518E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.03022
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.52518E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 2854.38737
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.52518E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 706983.42314
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 707615.30000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 80.66814
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 8678.88
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3597.35
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1404.66
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1832.49
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1272.10
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10524.88
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 10855.78
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 27337.74
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 5446.35
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 5452.39
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 31180.09
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 31308.31
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5433.64
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5439.68
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12350.24
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1672.85
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1674.35
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8031.57
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 10943.02
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 11319.07
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 7405.95
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7748.17
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 131662.71
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 11770.74


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 20457.70 16541.47 3916.23 0.81 2332.06 23.65
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 18375.95 14851.44 3524.51 0.81 2094.38 21.24
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 146243.06 118733.61 27509.45 0.81 16707.62 169.46
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 97142.19 77566.38 19575.82 0.80 11023.50 111.81
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 18637.78 15063.95 3573.83 0.81 2124.27 21.55
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 16855.06 13616.87 3238.19 0.81 1920.75 19.48
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5383.48 4353.80 1029.68 0.81 613.73 6.22
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4799.45 3879.65 919.80 0.81 547.05 5.55
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 29976.99 24182.47 5794.52 0.81 3414.19 34.63
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 540053.09 385361.47 154691.62 0.71 66179.06 671.22
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 45302.65 32936.56 12366.09 0.73 5220.86 52.95


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.839 2.839   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.839 2.839   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.721 0.651   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.844 0.749   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.917 0.806   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.917 0.806   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.917 0.806   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.917 0.806   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.857 0.759   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.857 0.759   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.857 0.759   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.857 0.759   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.857 0.759   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.930 0.816   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.418_SHGC_0.4 N/A 2.375 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.9325464862E-002 2.4953089788E-002 Pass Pass 5.3284856795E-003 1.7761691047E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 2.5053593351E-002 4.5592684384E-002 Pass Pass 5.8668362162E-002 8.7569842000E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.7571804801E-002 2.9112985226E-002 Pass Pass 7.1146407630E-003 1.9854424412E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 3.8560152449E-003 9.4044400817E-003 Pass Pass 2.5254992014E-002 5.5303985384E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 3.7701071392E-004 2.7695440522E-004 Pass Pass 0.1553855975 0.6382855927 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 6.6659322867E-002 0.1956967772 Pass Pass 1.9505026266E-002 5.2536414983E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 5.3407497030E-002 7.1226396090E-002 Pass Pass 1.8978393552E-002 4.4050696308E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 3.7384543053E-002 4.2521127922E-002 Pass Pass 7.7768624232E-003 1.8619930303E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 4.6416225934E-002 0.1613511166 Pass Pass 0.5570077795 4.5127209915 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 8.7574851756E-002 0.2580160219 Pass Pass 0.2280564347 0.9483240078 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.1936420006E-002 4.7431168809E-002 Pass Pass 2.4167796759E-002 6.5007082971E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.9754296911E-002 0.1045965654 Pass Pass 0.1958540254 0.5393117699 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 5.4905768679E-002 0.1570452783 Pass Pass 0.3082826629 2.5191747243 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 7.8647296953E-002 0.2381196774 Pass Pass 0.2782778891 1.0496950301 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 1.2821526122E-003 4.1266206776E-003 Pass Pass 3.1916467518E-002 5.3613484935E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 6.8288427545E-002 0.2269864832 Pass Pass 0.2091683127 0.9242455347 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.3744938697E-002 0.3090864295 Pass Pass 0.4311209993 2.1870634798 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 4.4640523838E-002 0.2112049711 Pass Pass 0.2294657500 1.0427227218 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 3.2598017040E-002 7.1005601260E-002 Pass Pass 1.3069148961E-002 4.0271682643E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 2.1772338301E-002 5.4341886450E-002 Pass Pass 1.3832194206E-002 4.0734731265E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 2.1842887725E-002 6.2786080183E-002 Pass Pass 2.0964218424E-002 4.2685052832E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 5.1373963633E-003 1.3053792595E-002 Pass Pass 3.0450387667E-002 3.9092838771E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3465.62 153.79 1962.37 8239.72 1586.64 15408.15



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB -4.30 0.00 -4.30 Wetbulb [C] 1.20 110.00
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 26.40 9.10 17.00 Wetbulb [C] 2.10 90.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 42.00 35      
Mar 0.00 0      
Apr 0.00 0      
May 40.00 22      
Jun 4.00 8      
Jul 5.00 4      
Aug 7.00 8      
Sep 17.00 10      
Oct 50.00 49      
Nov 69.00 59      
Dec 95.00 53      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.651 0.721 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.651 0.721 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.651 0.721 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.651 0.721 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.651 0.721 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.651 0.721 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.749 0.844 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.749 0.844 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.749 0.844 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.749 0.844 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.749 0.844 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.749 0.844 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.749 0.844 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.749 0.844 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.749 0.844 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.749 0.844 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.806 0.917 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.806 0.917 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.806 0.917 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.806 0.917 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.759 0.857 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.759 0.857 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.759 0.857 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.759 0.857 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.759 0.857 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.816 0.930 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.816 0.930 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.816 0.930 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.816 0.930 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.816 0.930 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.816 0.930 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.816 0.930 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.816 0.930 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.215 0.228 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.215 0.228 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.215 0.228 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.215 0.228 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.215 0.228 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.215 0.228 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.215 0.228 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.215 0.228 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.215 0.228 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.215 0.228 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.217 0.228 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.212 0.228 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.212 0.228 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.212 0.228 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.217 0.228 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.217 0.228 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.217 0.228 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 2.375 0.401 0.442             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 2.375 0.401 0.442             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 2.375 0.401 0.442             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.375 0.401 0.442             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.418_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.375 0.401 0.442             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.375 0.401 0.442             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.418_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.375 0.401 0.442             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 2.375 0.401 0.442             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 2.375 0.401 0.442             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.418_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.375 0.401 0.442             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.375 0.401 0.442             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.375 0.401 0.442             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.418_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.375 0.401 0.442             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.375 0.401 0.442             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 2.375 0.401 0.442             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 2.375 0.401 0.442             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.375 0.401 0.442             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.375 0.401 0.442             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.418_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.375 0.401 0.442             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.375 0.401 0.442             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.418_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.375 0.401 0.442             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.418_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 2.375 0.401 0.442             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.375 0.401 0.442             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.375 0.401 0.442             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.375 0.401 0.442             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.375 0.401 0.442             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.375 0.401 0.442             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 2.375 0.401 0.442             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 2.375 0.401 0.442             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.418_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.375 0.401 0.442             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.375 0.401 0.442                      
North Total or Average             432.95 2.375 0.401 0.442                      
Non-North Total or Average             780.84 2.375 0.401 0.442                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.992 2.839 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.992 2.839 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.992 2.839 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.992 2.839 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.992 2.839 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.992 2.839 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 10.3255 1978.83 20432.33 LightsWired LTG_SCH_BASEMENT 49.32 168.00 49.26 0.0000 Y 188.94
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.5625 67.07 909.66 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.76
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.5625 77.67 1053.39 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 10.14
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.5208 164.24 742.52 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.17
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 7.7005 94.76 729.69 LightsWired LTG_SCH_STORAGE 30.30 168.00 30.27 0.0000 Y 4.15
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 6.4583 78.04 504.01 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 5.55
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 11.5174 188.86 2175.19 LightsWired LTG_SCH_DINING 58.69 168.00 39.61 0.0000 Y 16.18
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 9.6875 1308.19 12673.07 LightsWired LTG_SCH_LOBBY 44.02 168.00 41.56 0.0000 Y 98.88
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 9.7951 156.09 1528.91 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.93
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 9.7951 156.07 1528.73 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.92
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 9.7951 1863.81 18256.32 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 130.45
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 9.7951 1864.32 18261.31 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 130.49
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 9.7951 156.09 1528.91 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.93
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 9.7951 156.07 1528.73 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 10.92
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 7.1042 1557.62 11065.59 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 91.33
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 9.7951 39.02 382.23 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.73
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 9.7951 39.02 382.18 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.73
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 9.7951 220.77 2162.52 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 15.45
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 11.5174 331.66 3819.82 LightsWired LTG_SCH_DINING 58.69 168.00 49.36 0.0000 Y 35.39
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 11.5174 331.66 3819.82 LightsWired LTG_SCH_DINING 58.69 168.00 49.36 0.0000 Y 35.39
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 13.0243 103.30 1345.47 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 14.81
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 7.1042 412.12 2927.80 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 24.17
Interior Lighting Total       9.4981 11345.29 107758.18               494.89


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 12673.07 887.11
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 12673.07 887.11
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 2175.19 848.32
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 2175.19 848.32
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3819.82 763.96


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 16690.39 AstronomicalClock -   83.54 83.54 261.73
Exterior Lighting Total 16690.39           261.73



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 392033.80 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 707615.30 2.96 707739.68 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13628.06 20457.70 16541.47 3916.23 0.81 - 2332.06 23.65
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12248.81 18375.95 14851.44 3524.51 0.81 - 2094.38 21.24
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 96864.00 146243.06 118733.61 27509.45 0.81 - 16707.62 169.46
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 65849.93 97142.19 77566.38 19575.82 0.80 - 11023.50 111.81
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12422.34 18637.78 15063.95 3573.83 0.81 - 2124.27 21.55
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11241.03 16855.06 13616.87 3238.19 0.81 - 1920.75 19.48
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3585.27 5383.48 4353.80 1029.68 0.81 - 613.73 6.22
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3198.35 4799.45 3879.65 919.80 0.81 - 547.05 5.55
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 20031.92 29976.99 24182.47 5794.52 0.81 - 3414.19 34.63
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 431806.07 540053.09 385361.47 154691.62 0.71 - 66179.06 671.22
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 36112.10 45302.65 32936.56 12366.09 0.73 - 5220.86 52.95
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 8634.70 8678.88 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3580.83 3597.35 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1397.95 1404.66 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1824.80 1832.49 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1266.84 1272.10 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10471.30 10524.88 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10804.03 10855.78 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 27205.86 27337.74 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5056.40 5446.35 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5062.01 5452.39 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 28947.87 31180.09 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 29066.92 31308.31 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5044.60 5433.64 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5050.21 5439.68 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 12293.46 12350.24 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1553.13 1672.85 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1554.52 1674.35 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 7456.79 8031.57 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10889.18 10943.02 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11263.32 11319.07 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7368.27 7405.95 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7714.35 7748.17 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 173055.20 131662.71 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 15471.26 11770.74 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.24 873.08 703.64 1.00 1.15 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.11 783.32 703.64 1.00 1.17 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 8.96 6305.30 703.64 1.00 0.94 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.70 4014.01 703.64 1.00 0.96 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.13 794.61 703.64 1.00 1.17 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.02 717.76 703.64 1.00 1.19 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.33 229.87 703.64 1.00 1.66 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.29 204.69 703.64 1.00 1.73 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.81 1271.78 703.64 1.00 1.08 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.95 51411.89 2240.64 1.00 1.11 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.025252 4122.85 163269.44 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003430 1032.87 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.025252 2854.39 113036.94 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 36825.22 36825.22 18.61 2.704 2.704 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 24.00 24.00 0.00916 23.53 0.00840 0.854 0.00
RETAIL_1_FLR_1 6428.61 6428.61 95.85 0.472 0.472 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00887 26.17 0.00841 0.079 0.00
RETAIL_2_FLR_1 3276.96 3276.96 42.19 0.241 0.241 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00935 26.22 0.00841 0.092 0.00
MECH_FLR_1 2295.42 2295.42 13.98 0.169 0.169 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00875 26.31 0.00841 0.000 0.00
STORAGE_FLR_1 1505.92 1505.92 15.89 0.111 0.111 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00879 26.40 0.00841 0.058 0.00
LAUNDRY_FLR_1 44728.95 44728.95 573.16 3.285 3.285 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00854 26.40 0.00841 0.000 0.00
CAFE_FLR_1 25039.27 25039.27 132.58 1.840 1.840 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 23.99 0.00977 26.17 0.00841 0.676 0.00
LOBBY_FLR_1 69489.94 69489.94 53.12 5.105 5.105 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 23.99 0.00986 26.25 0.00841 1.894 0.00
ROOM_1_FLR_3 12539.00 12539.00 321.33 1.241 1.241 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 21.11 21.11 0.00856 25.37 0.00841 0.062 0.00
ROOM_2_FLR_3 11249.88 11249.88 288.33 1.113 1.113 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00856 25.13 0.00841 0.062 0.00
ROOM_3_MULT19_FLR_3 90558.90 90558.90 3692.69 8.961 8.961 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00850 26.17 0.00841 0.837 0.00
ROOM_4_MULT19_FLR_3 57646.14 57646.14 2349.97 5.705 5.705 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 21.11 21.11 0.00874 26.40 0.00841 0.837 0.00
ROOM_5_FLR_3 11411.92 11411.92 292.45 1.129 1.129 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 21.11 21.11 0.00856 22.94 0.00840 0.062 0.00
ROOM_6_FLR_3 10308.34 10308.34 264.20 1.020 1.020 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.11 21.11 0.00857 21.65 0.00840 0.062 0.00
CORRIDOR_FLR_3 22153.03 22153.03 56.89 1.627 1.627 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00935 26.40 0.00841 0.475 0.00
ROOM_1_FLR_6 3301.37 3301.37 84.60 0.327 0.327 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00855 25.49 0.00841 0.015 0.00
ROOM_2_FLR_6 2939.67 2939.67 75.34 0.291 0.291 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00856 25.13 0.00841 0.015 0.00
ROOM_3_MULT9_FLR_6 18264.61 18264.61 744.57 1.807 1.807 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 21.11 21.11 0.00859 26.25 0.00841 0.099 0.00
BANQUET_FLR_6 29203.82 29203.82 88.05 2.147 2.147 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.99 0.01042 26.40 0.00841 1.188 0.00
DINING_FLR_6 30586.12 30586.12 92.22 2.249 2.249 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.99 0.01033 26.40 0.00841 1.188 0.00
KITCHEN_FLR_6 31051.11 31051.11 300.58 2.286 2.286 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01006 25.58 0.00841 0.367 0.00
CORRIDOR_FLR_6 11342.78 11342.78 27.52 0.833 0.833 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00894 26.40 0.00841 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 1486.70 1486.70 0.75 0.064 0.854 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00797 -4.30 0.00266 0.854 0.00
RETAIL_1_FLR_1 2334.13 2334.13 34.80 0.101 0.101 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00749 -4.30 0.00266 0.079 0.00
RETAIL_2_FLR_1 762.48 762.48 9.82 0.033 0.092 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00741 -4.30 0.00266 0.092 0.00
MECH_FLR_1 1379.90 1379.90 8.40 0.060 0.060 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00725 -4.30 0.00266 0.000 0.00
STORAGE_FLR_1 974.90 974.90 10.29 0.042 0.058 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00737 -4.30 0.00266 0.058 0.00
LAUNDRY_FLR_1 1802.04 1802.04 23.09 0.078 0.078 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00722 -4.30 0.00266 0.000 0.00
CAFE_FLR_1 5943.66 5943.66 31.47 0.257 0.676 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00755 -4.30 0.00266 0.676 0.00
LOBBY_FLR_1 13725.60 13725.60 10.49 0.595 1.894 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00746 -4.30 0.00266 1.894 0.00
ROOM_1_FLR_3 5056.49 5056.49 129.58 0.220 0.220 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00746 -4.30 0.00266 0.062 0.00
ROOM_2_FLR_3 5062.09 5062.09 129.74 0.221 0.221 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00746 -4.30 0.00266 0.062 0.00
ROOM_3_MULT19_FLR_3 28948.11 28948.11 1180.41 1.261 1.261 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00750 -4.30 0.00266 0.837 0.00
ROOM_4_MULT19_FLR_3 29067.16 29067.16 1184.94 1.267 1.267 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00750 -4.30 0.00266 0.837 0.00
ROOM_5_FLR_3 5044.69 5044.69 129.28 0.220 0.220 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00746 -4.30 0.00266 0.062 0.00
ROOM_6_FLR_3 5050.30 5050.30 129.44 0.220 0.220 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00746 -4.30 0.00266 0.062 0.00
CORRIDOR_FLR_3 7996.72 7996.72 20.54 0.346 0.475 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00758 -4.30 0.00266 0.475 0.00
ROOM_1_FLR_6 1553.15 1553.15 39.80 0.068 0.068 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00755 -4.30 0.00266 0.015 0.00
ROOM_2_FLR_6 1554.54 1554.54 39.84 0.068 0.068 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00755 -4.30 0.00266 0.015 0.00
ROOM_3_MULT9_FLR_6 7456.89 7456.89 303.98 0.325 0.325 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00757 -4.30 0.00266 0.099 0.00
BANQUET_FLR_6 5217.10 5217.10 15.73 0.226 1.188 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00767 -4.30 0.00266 1.188 0.00
DINING_FLR_6 5323.24 5323.24 16.05 0.231 1.188 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 21.00 21.00 0.00767 -4.30 0.00266 1.188 0.00
KITCHEN_FLR_6 1357.43 1357.43 13.14 0.059 0.367 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00556 -4.30 0.00266 0.367 0.00
CORRIDOR_FLR_6 5513.91 5513.91 13.38 0.239 0.239 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 21.00 21.00 0.00772 -4.30 0.00266 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 22.95 22.95 7.27 7.27 22.9452 11.6727 22.9452 0.5087 0.3000
FLR_3_DOAS 20.20 2.05 3.87 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 8634.702 8634.702 1.368403 0.00007554 182.025 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8634.70 8634.70 1.368403 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00797204 50.9913 1486.70 0.00 8683.05 8683.05
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3580.827 3580.827 0.238902 0.00003133 82.778 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 3580.83 3580.83 0.238902 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00749121 47.9538 2334.13 0.00 3600.00 3600.00
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1397.953 1397.953 0.121783 0.00001223 31.093 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 1397.95 1397.95 0.121783 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00740898 47.4326 762.48 0.00 1405.54 1405.54
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1824.799 1824.799 0.085287 0.00001596 45.496 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1824.80 1824.80 0.085287 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00725343 46.4484 1379.90 0.00 1834.21 1834.21
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1266.844 1266.844 0.055954 0.00001108 32.081 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 1266.84 1266.84 0.055954 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00737429 47.2133 974.90 0.00 1273.35 1273.35
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10471.295 10471.295 1.662080 0.00009161 220.720 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 10471.30 10471.30 1.662080 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00722434 46.2651 1802.04 0.00 10529.92 10529.92
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 10804.025 10804.025 0.931254 0.00009452 240.615 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 10804.03 10804.03 0.931254 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00755270 48.3424 5943.66 0.00 10862.66 10862.66
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 27205.859 27205.859 2.583180 0.00023801 599.017 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 27205.86 27205.86 2.583180 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00745733 47.7386 13725.60 0.00 27354.19 27354.19
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 13628.058 -999.000 1.240816 0.00048675 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown 8/21 16:40:00 13628.06 13440.33 1.240816 21.69 15.50 0.00855751 12.80 12.00 0.00850000 25.37 0.00840546 16.68 0.0000 21.11 0.00855751 54.3148 12539.00 0.00 13770.72 13345.11
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 5056.404 5056.404 0.220341 0.00004424 144.501 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5056.40 5056.40 0.220341 21.11 14.29 0.00746126 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00746126 47.4400 5056.49 0.00 5450.93 5450.93
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 12248.814 -999.000 1.113250 0.00043749 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 12248.81 12061.35 1.113250 21.69 15.51 0.00856400 12.80 12.00 0.00850000 25.13 0.00840508 16.59 0.0000 21.11 0.00856400 54.3554 11249.88 0.00 12376.92 11976.58
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 5062.009 5062.009 0.220585 0.00004428 144.661 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5062.01 5062.01 0.220585 21.11 14.29 0.00746184 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00746184 47.4436 5062.09 0.00 5456.97 5456.97
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 96863.998 -999.000 8.961015 0.00345969 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 96864.00 96864.00 8.961015 21.69 15.45 0.00849880 12.80 12.00 0.00849880 26.17 0.00840672 16.96 0.0000 21.11 0.00849880 53.9460 90558.90 0.00 97903.20 96162.69
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 28947.869 28947.869 1.261469 0.00025325 827.253 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 28947.87 28947.87 1.261469 21.11 14.33 0.00749737 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00749737 47.6659 28948.11 0.00 31206.70 31206.70
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 65849.933 -999.000 5.704659 0.00235196 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown 8/21 15:00:00 65849.93 62184.61 5.704659 21.69 15.66 0.00874269 12.80 12.00 0.00850000 26.40 0.00840708 17.04 0.0000 21.11 0.00874269 55.4748 57646.14 0.00 66521.53 61840.02
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 29066.922 29066.922 1.266657 0.00025429 830.655 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 29066.92 29066.92 1.266657 21.11 14.33 0.00749911 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00749911 47.6768 29067.16 0.00 31335.05 31335.05
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 12422.341 -999.000 1.129285 0.00044369 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown 8/21 10:00:00 12422.34 12234.71 1.129285 21.69 15.50 0.00856315 12.80 12.00 0.00850000 22.94 0.00840167 15.82 0.0000 21.11 0.00856315 54.3500 11411.92 0.00 12552.27 12148.63
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 5044.603 5044.603 0.219826 0.00004413 144.164 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5044.60 5044.60 0.219826 21.11 14.29 0.00746013 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00746013 47.4329 5044.69 0.00 5438.21 5438.21
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 11241.028 -999.000 1.020078 0.00040150 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown 8/21 09:10:00 11241.03 11054.12 1.020078 21.69 15.51 0.00856962 12.80 12.00 0.00850000 21.65 0.00839969 15.35 0.0000 21.11 0.00856962 54.3906 10308.34 0.00 11358.50 10976.97
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 5050.211 5050.211 0.220071 0.00004418 144.324 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5050.21 5050.21 0.220071 21.11 14.29 0.00746070 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00746070 47.4365 5050.30 0.00 5444.26 5444.26
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 12293.465 12293.465 0.823172 0.00010755 284.014 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 12293.46 12293.46 0.823172 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00757576 48.4873 7996.72 0.00 12359.30 12359.30
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3585.273 -999.000 0.326693 0.00012806 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 3585.27 3538.32 0.326693 21.69 15.50 0.00855464 12.80 12.00 0.00850000 25.49 0.00840565 16.72 0.0000 21.11 0.00855464 54.2968 3301.37 0.00 3622.82 3513.16
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1553.129 1553.129 0.067680 0.00001359 44.383 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 1553.13 1553.13 0.067680 21.11 14.38 0.00755305 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00755305 48.0166 1553.15 0.00 1674.31 1674.31
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3198.350 -999.000 0.290900 0.00011424 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 3198.35 3151.42 0.290900 21.69 15.50 0.00856132 12.80 12.00 0.00850000 25.13 0.00840508 16.59 0.0000 21.11 0.00856132 54.3386 2939.67 0.00 3231.81 3129.19
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1554.518 1554.518 0.067741 0.00001360 44.422 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 1554.52 1554.52 0.067741 21.11 14.38 0.00755345 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00755345 48.0191 1554.54 0.00 1675.81 1675.81
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 20031.923 -999.000 1.807446 0.00071548 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown 8/21 13:40:00 20031.92 19600.68 1.807446 21.69 15.53 0.00859059 12.80 12.00 0.00850000 26.25 0.00840684 16.99 0.0000 21.11 0.00859059 54.5225 18264.61 0.00 20240.62 19467.40
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 7456.791 7456.791 0.324943 0.00006524 213.086 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 7456.79 7456.79 0.324943 21.11 14.39 0.00756986 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00756986 48.1219 7456.89 0.00 8038.63 8038.63
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10889.177 10889.177 1.086507 0.00009526 238.493 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 10889.18 10889.18 1.086507 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00766567 49.0561 5217.10 0.00 10949.44 10949.44
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11263.315 11263.315 1.137918 0.00009854 246.365 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 11263.32 11263.32 1.137918 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00767193 49.0967 5323.24 0.00 11325.67 11325.67
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7368.271 7368.271 1.156796 0.00006446 155.421 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 7368.27 7368.27 1.156796 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00556330 35.7292 1357.43 0.00 7409.52 7409.52
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7714.346 7714.346 0.421477 0.00006749 185.270 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 7714.35 7714.35 0.421477 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00771983 49.3990 5513.91 0.00 7754.67 7754.67
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 431806.066 -999.000 22.945196 0.01542311 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 431806.07 396665.11 22.945196 25.21 17.12 0.00898897 10.96 10.96 0.00850000 26.40 0.00840708 17.04 50.8231 23.99 0.00954832 50.7906 312140.73 0.00 435578.10 379696.56
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 173055.205 173055.205 6.883559 0.00151396 2952.810 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 173055.20 173055.20 6.883559 -4.30 -4.30 0.00265759 16.70 13.09 0.00800000 -4.30 0.00265759 -4.30 169.4103 21.02 0.00753999 48.1994 53352.84 0.00 159246.80 159246.80
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 36112.103 -999.000 2.051317 0.00128984 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 36112.10 36112.10 2.051317 26.40 17.04 0.00840708 11.92 11.55 0.00840708 26.40 0.00840708 17.04 99.9965 21.11 0.00859456 54.5464 204111.13 0.00 36425.73 35509.87
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 15471.261 15471.261 0.615395 0.00013535 263.983 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 15471.26 15471.26 0.615395 -4.30 -4.30 0.00265759 16.70 13.09 0.00800000 -4.30 0.00265759 -4.30 333.3216 21.11 0.00749867 47.6741 88793.42 0.00 14236.78 14236.78



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 8634.702 8634.702 1.368403 0.00007554 182.025 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 2.1591 2.202540 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8634.70 8634.70 1.0000 1.63027711 1.368403 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.07553244 60.00 32.22 27.78 0.000 8634.70 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00797204 21.00 0.00797204 50.9913 1486.70 0.00 8683.05 8683.05 1.63027711 16.60 13.15 0.00800000 36934.7 21.82 15.16 0.00800000 42260.8
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3580.827 3580.827 0.238902 0.00003133 82.778 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 0.8954 0.913397 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 3580.83 3580.83 1.0000 0.28462121 0.238902 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.03132344 60.00 32.22 27.78 0.000 3580.83 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00749121 21.00 0.00749121 47.9538 2334.13 0.00 3600.00 3600.00 0.28462121 16.60 13.15 0.00800000 36934.7 29.00 17.70 0.00800000 49583.1
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1397.953 1397.953 0.121783 0.00001223 31.093 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 0.3496 0.356590 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 1397.95 1397.95 1.0000 0.14508882 0.121783 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01222866 60.00 32.22 27.78 0.000 1397.95 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00740898 21.00 0.00740898 47.4326 762.48 0.00 1405.54 1405.54 0.14508882 16.60 13.15 0.00800000 36934.7 26.10 16.70 0.00800000 46622.2
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1824.799 1824.799 0.085287 0.00001596 45.496 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 0.4563 0.465470 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1824.80 1824.80 1.0000 0.10160906 0.085287 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01596251 60.00 32.22 27.78 0.000 1824.80 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00725343 21.00 0.00725343 46.4484 1379.90 0.00 1834.21 1834.21 0.10160906 16.60 13.15 0.00800000 36934.7 34.30 19.44 0.00800000 54986.4
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1266.844 1266.844 0.055954 0.00001108 32.081 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 0.3168 0.323147 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 1266.84 1266.84 1.0000 0.06666145 0.055954 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01108178 60.00 32.22 27.78 0.000 1266.84 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00737429 21.00 0.00737429 47.2133 974.90 0.00 1273.35 1273.35 0.06666145 16.60 13.15 0.00800000 36934.7 35.33 19.76 0.00800000 56036.5
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10471.295 10471.295 1.662080 0.00009161 220.720 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 2.6183 2.671018 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 10471.30 10471.30 1.0000 1.98015543 1.662080 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.09159811 60.00 32.22 27.78 0.000 10471.30 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00722434 21.00 0.00722434 46.2651 1802.04 0.00 10529.92 10529.92 1.98015543 16.60 13.15 0.00800000 36934.7 21.81 15.16 0.00800000 42252.5
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 10804.025 10804.025 0.931254 0.00009452 240.615 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 2.7015 2.755891 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 10804.03 10804.03 1.0000 1.10946944 0.931254 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.09450868 60.00 32.22 27.78 0.000 10804.03 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00755270 21.00 0.00755270 48.3424 5943.66 0.00 10862.66 10862.66 1.10946944 16.60 13.15 0.00800000 36934.7 26.20 16.74 0.00800000 46725.6
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 27205.859 27205.859 2.583180 0.00023801 599.017 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 6.8028 6.939672 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 27205.86 27205.86 1.0000 3.07752812 2.583180 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.23798445 60.00 32.22 27.78 0.000 27205.86 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00745733 21.00 0.00745733 47.7386 13725.60 0.00 27354.19 27354.19 3.07752812 16.60 13.15 0.00800000 36934.7 25.32 16.43 0.00800000 45823.1
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 13628.058 -999.000 1.240816 0.00048675 -999.000 -999.0000 1.00000 1.00000 1020.7480 1004.8586 1.1914 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.240816 1.47827396   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 1.9276 1.927599 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown unknown unknown 8/21 16:40:00 Sensible 13628.06 13440.33 1.0000 1.47827396 1.240816 21.69 15.50 0.00855751 43541.1 12.80 12.00 0.00850000 34322.2 0.48670391 6.70 13.37 6.67 0.000 13628.06 25.37 0.00840546 16.68 0.00000000 0.0000 21.11 0.00855751 21.11 0.00855751 54.3148 12539.00 0.00 13770.72 13345.11 1.47827396 21.69 15.61 0.00855751 43541.1 12.85 12.06 0.00844348 34225.7
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 5056.404 5056.404 0.220341 0.00004424 144.501 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.240816 1.47827396   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 1.2643 1.289788 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5056.40 5056.40 1.0000 0.26250771 0.220341 21.11 14.29 0.00746126 40165.6 40.00 21.06 0.00800000 60796.0 0.04423112 60.00 32.22 27.78 0.000 5056.40 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00746126 21.11 0.00746126 47.4400 5056.49 0.00 5450.93 5450.93 0.26250771 16.60 12.62 0.00746126 35570.8 36.98 19.87 0.00746126 56335.6
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 12248.814 -999.000 1.113250 0.00043749 -999.000 -999.0000 1.00000 1.00000 1020.7600 1004.8586 1.1914 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.113250 1.32629461   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 1.7325 1.732514 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 12248.81 12061.35 1.0000 1.32629461 1.113250 21.69 15.51 0.00856400 43557.6 12.80 12.00 0.00850000 34322.2 0.43744646 6.70 13.37 6.67 0.000 12248.81 25.13 0.00840508 16.59 0.00000000 0.0000 21.11 0.00856400 21.11 0.00856400 54.3554 11249.88 0.00 12376.92 11976.58 1.32629461 21.69 15.61 0.00856400 43557.6 12.84 12.06 0.00844445 34225.6
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 5062.009 5062.009 0.220585 0.00004428 144.661 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.113250 1.32629461   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 1.2657 1.291218 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5062.01 5062.01 1.0000 0.26279870 0.220585 21.11 14.29 0.00746184 40167.0 40.00 21.06 0.00800000 60796.0 0.04428015 60.00 32.22 27.78 0.000 5062.01 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00746184 21.11 0.00746184 47.4436 5062.09 0.00 5456.97 5456.97 0.26279870 16.60 12.62 0.00746184 35572.2 36.98 19.87 0.00746184 56337.1
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 96863.998 -999.000 8.961015 0.00345969 -999.000 -999.0000 1.00000 1.00000 1020.6388 1004.8586 1.1914 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.961015 10.67590203   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 13.7010 13.700772 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 96864.00 96864.00 1.0000 10.67590203 8.961015 21.69 15.45 0.00849880 43392.3 12.80 12.00 0.00849880 34319.2 3.45934005 6.70 13.37 6.67 0.000 96864.00 26.17 0.00840672 16.96 0.00000000 0.0000 21.11 0.00849880 21.11 0.00849880 53.9460 90558.90 0.00 97903.20 96162.69 10.67590203 21.69 15.56 0.00849880 43392.3 12.86 12.06 0.00843423 34221.8
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 28947.869 28947.869 1.261469 0.00025325 827.253 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.961015 10.67590203   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 7.2383 7.384024 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 28947.87 28947.87 1.0000 1.50287944 1.261469 21.11 14.33 0.00749737 40257.6 40.00 21.06 0.00800000 60796.0 0.25322275 60.00 32.22 27.78 0.000 28947.87 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00749737 21.11 0.00749737 47.6659 28948.11 0.00 31206.70 31206.70 1.50287944 16.60 12.66 0.00749737 35662.2 36.98 19.89 0.00749737 56426.8
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 65849.933 -999.000 5.704659 0.00235196 -999.000 -999.0000 1.00000 1.00000 1021.0922 1004.8586 1.1914 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.704659 6.79637114   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 9.3142 9.314038 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown unknown unknown 8/21 15:00:00 Sensible 65849.93 62184.61 1.0000 6.79637114 5.704659 21.69 15.66 0.00874269 44011.2 12.80 12.00 0.00850000 34322.2 2.35172319 6.70 13.37 6.67 0.000 65849.93 26.40 0.00840708 17.04 0.00000000 0.0000 21.11 0.00874269 21.11 0.00874269 55.4748 57646.14 0.00 66521.53 61840.02 6.79637114 21.69 15.77 0.00874269 44011.2 12.78 12.06 0.00846985 34223.4
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 29066.922 29066.922 1.266657 0.00025429 830.655 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.704659 6.79637114   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 7.2681 7.414392 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 29066.92 29066.92 1.0000 1.50906029 1.266657 21.11 14.33 0.00749911 40262.0 40.00 21.06 0.00800000 60796.0 0.25426417 60.00 32.22 27.78 0.000 29066.92 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00749911 21.11 0.00749911 47.6768 29067.16 0.00 31335.05 31335.05 1.50906029 16.60 12.66 0.00749911 35666.6 36.98 19.90 0.00749911 56431.2
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 12422.341 -999.000 1.129285 0.00044369 -999.000 -999.0000 1.00000 1.00000 1020.7585 1004.8586 1.1914 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.129285 1.34539795   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 1.7571 1.757058 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown unknown unknown 8/21 10:00:00 Sensible 12422.34 12234.71 1.0000 1.34539795 1.129285 21.69 15.50 0.00856315 43555.4 12.80 12.00 0.00850000 34322.2 0.44364371 6.70 13.37 6.67 0.000 12422.34 22.94 0.00840167 15.82 0.00000000 0.0000 21.11 0.00856315 21.11 0.00856315 54.3500 11411.92 0.00 12552.27 12148.63 1.34539795 21.69 15.61 0.00856315 43555.4 12.84 12.06 0.00844432 34225.6
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 5044.603 5044.603 0.219826 0.00004413 144.164 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.129285 1.34539795   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 1.2614 1.286778 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5044.60 5044.60 1.0000 0.26189507 0.219826 21.11 14.29 0.00746013 40162.7 40.00 21.06 0.00800000 60796.0 0.04412789 60.00 32.22 27.78 0.000 5044.60 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00746013 21.11 0.00746013 47.4329 5044.69 0.00 5438.21 5438.21 0.26189507 16.60 12.62 0.00746013 35567.9 36.98 19.87 0.00746013 56332.7
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 11241.028 -999.000 1.020078 0.00040150 -999.000 -999.0000 1.00000 1.00000 1020.7705 1004.8586 1.1914 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.020078 1.21529284   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 1.5900 1.589969 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown unknown unknown 8/21 09:10:00 Sensible 11241.03 11054.12 1.0000 1.21529284 1.020078 21.69 15.51 0.00856962 43571.8 12.80 12.00 0.00850000 34322.2 0.40145503 6.70 13.37 6.67 0.000 11241.03 21.65 0.00839969 15.35 0.00000000 0.0000 21.11 0.00856962 21.11 0.00856962 54.3906 10308.34 0.00 11358.50 10976.97 1.21529284 21.69 15.62 0.00856962 43571.8 12.84 12.06 0.00844528 34225.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 5050.211 5050.211 0.220071 0.00004418 144.324 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.020078 1.21529284   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 1.2628 1.288208 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5050.21 5050.21 1.0000 0.26218619 0.220071 21.11 14.29 0.00746070 40164.1 40.00 21.06 0.00800000 60796.0 0.04417694 60.00 32.22 27.78 0.000 5050.21 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00746070 21.11 0.00746070 47.4365 5050.30 0.00 5444.26 5444.26 0.26218619 16.60 12.62 0.00746070 35569.3 36.98 19.87 0.00746070 56334.2
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 12293.465 12293.465 0.823172 0.00010755 284.014 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 3.0740 3.135818 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 12293.46 12293.46 1.0000 0.98070450 0.823172 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.10753762 60.00 32.22 27.78 0.000 12293.46 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00757576 21.00 0.00757576 48.4873 7996.72 0.00 12359.30 12359.30 0.98070450 16.60 13.15 0.00800000 36934.7 28.96 17.69 0.00800000 49537.2
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3585.273 -999.000 0.326693 0.00012806 -999.000 -999.0000 1.00000 1.00000 1020.7427 1004.8586 1.1914 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.326693 0.38921239   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 0.5071 0.507113 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 3585.27 3538.32 1.0000 0.38921239 0.326693 21.69 15.50 0.00855464 43533.8 12.80 12.00 0.00850000 34322.2 0.12804219 6.70 13.37 6.67 0.000 3585.27 25.49 0.00840565 16.72 0.00000000 0.0000 21.11 0.00855464 21.11 0.00855464 54.2968 3301.37 0.00 3622.82 3513.16 0.38921239 21.69 15.60 0.00855464 43533.8 12.85 12.06 0.00844305 34225.7
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1553.129 1553.129 0.067680 0.00001359 44.383 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.326693 0.38921239   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 0.3884 0.396172 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 1553.13 1553.13 1.0000 0.08063208 0.067680 21.11 14.38 0.00755305 40398.7 40.00 21.06 0.00800000 60796.0 0.01358607 60.00 32.22 27.78 0.000 1553.13 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00755305 21.11 0.00755305 48.0166 1553.15 0.00 1674.31 1674.31 0.08063208 16.60 12.71 0.00755305 35803.2 36.98 19.94 0.00755305 56568.0
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3198.350 -999.000 0.290900 0.00011424 -999.000 -999.0000 1.00000 1.00000 1020.7551 1004.8586 1.1914 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.290900 0.34657027   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 0.4524 0.452385 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 3198.35 3151.42 1.0000 0.34657027 0.290900 21.69 15.50 0.00856132 43550.8 12.80 12.00 0.00850000 34322.2 0.11422386 6.70 13.37 6.67 0.000 3198.35 25.13 0.00840508 16.59 0.00000000 0.0000 21.11 0.00856132 21.11 0.00856132 54.3386 2939.67 0.00 3231.81 3129.19 0.34657027 21.69 15.61 0.00856132 43550.8 12.84 12.06 0.00844405 34225.6
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1554.518 1554.518 0.067741 0.00001360 44.422 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.290900 0.34657027   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 0.3887 0.396527 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 1554.52 1554.52 1.0000 0.08070417 0.067741 21.11 14.38 0.00755345 40399.7 40.00 21.06 0.00800000 60796.0 0.01359821 60.00 32.22 27.78 0.000 1554.52 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00755345 21.11 0.00755345 48.0191 1554.54 0.00 1675.81 1675.81 0.08070417 16.60 12.71 0.00755345 35804.2 36.98 19.94 0.00755345 56569.0
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 20031.923 -999.000 1.807446 0.00071548 -999.000 -999.0000 1.00000 1.00000 1020.8095 1004.8586 1.1914 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.807446 2.15334004   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 2.8334 2.833383 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown unknown unknown 8/21 13:40:00 Sensible 20031.92 19600.68 1.0000 2.15334004 1.807446 21.69 15.53 0.00859059 43624.9 12.80 12.00 0.00850000 34322.2 0.71540752 6.70 13.37 6.67 0.000 20031.92 26.25 0.00840684 16.99 0.00000000 0.0000 21.11 0.00859059 21.11 0.00859059 54.5225 18264.61 0.00 20240.62 19467.40 2.15334004 21.69 15.64 0.00859059 43624.9 12.83 12.06 0.00844837 34225.3
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 7456.791 7456.791 0.324943 0.00006524 213.086 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.807446 2.15334004   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 1.8646 1.902079 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 7456.79 7456.79 1.0000 0.38712812 0.324943 21.11 14.39 0.00756986 40441.5 40.00 21.06 0.00800000 60796.0 0.06522861 60.00 32.22 27.78 0.000 7456.79 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00756986 21.11 0.00756986 48.1219 7456.89 0.00 8038.63 8038.63 0.38712812 16.60 12.73 0.00756986 35845.7 36.98 19.95 0.00756986 56610.5
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 10889.177 10889.177 1.086507 0.00009526 238.493 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 2.7228 2.777612 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 10889.18 10889.18 1.0000 1.29443419 1.086507 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.09525355 60.00 32.22 27.78 0.000 10889.18 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00766567 21.00 0.00766567 49.0561 5217.10 0.00 10949.44 10949.44 1.29443419 16.60 13.15 0.00800000 36934.7 24.90 16.28 0.00800000 45393.6
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 11263.315 11263.315 1.137918 0.00009854 246.365 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 2.8164 2.873047 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 11263.32 11263.32 1.0000 1.35568376 1.137918 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.09852634 60.00 32.22 27.78 0.000 11263.32 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00767193 21.00 0.00767193 49.0967 5323.24 0.00 11325.67 11325.67 1.35568376 16.60 13.15 0.00800000 36934.7 24.79 16.24 0.00800000 45288.9
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7368.271 7368.271 1.156796 0.00006446 155.421 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 1.8424 1.879499 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 7368.27 7368.27 1.0000 1.37817491 1.156796 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.06445427 60.00 32.22 27.78 0.000 7368.27 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.23 0.00556330 21.00 0.00556330 35.7292 1357.43 0.00 7409.52 7409.52 1.37817491 16.60 13.15 0.00800000 36934.7 21.87 15.18 0.00800000 42311.1
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7714.346 7714.346 0.421477 0.00006749 185.270 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 1.9290 1.967776 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 7714.35 7714.35 1.0000 0.50213543 0.421477 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.06748158 60.00 32.22 27.78 0.000 7714.35 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00771983 21.00 0.00771983 49.3990 5513.91 0.00 7754.67 7754.67 0.50213543 16.60 13.15 0.00800000 36934.7 31.74 18.61 0.00800000 52378.1
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 431806.066 -999.000 22.945196 0.01542311 -999.000 -999.0000 1.00000 1.00000 1021.5500 1004.8586 1.1914 VAV WITH REHEAT FAN Fan:VariableVolume 22.945196 27.33626442   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 61.0773 61.077255 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 Sensible 431806.07 396665.11 1.0000 27.33626442 22.945196 25.21 17.12 0.00898897 48239.2 10.96 10.96 0.00850000 32443.1 15.42153885 6.70 13.37 6.67 51411.892 380394.17 26.40 0.00840708 17.04 11.66146000 50.8231 23.99 0.00959076 23.99 0.00954832 50.7906 312140.73 0.00 435578.10 379696.56 27.33626442 25.21 17.23 0.00898897 48239.2 11.62 11.28 0.00817858 32305.2
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 173055.205 173055.205 6.883559 0.00151396 2952.810 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV WITH REHEAT FAN Fan:VariableVolume 22.945196 27.33626442   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 43.2721 44.142930 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 Sensible 173055.20 173055.20 1.0000 8.20087933 6.883559 -4.30 -4.30 0.00265759 2304.4 16.70 13.09 0.00800000 37036.7 1.51380798 60.00 32.22 27.78 0.000 173055.20 -4.30 0.00265759 -4.30 11.66146000 169.4103 20.96 0.00751301 21.02 0.00753999 48.1994 53352.84 0.00 159246.80 159246.80 8.20087933 2.80 0.02 0.00265759 9473.9 22.03 9.93 0.00265759 28892.1
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 36112.103 -999.000 2.051317 0.00128984 -999.000 -999.0000 1.00000 1.00000 1020.4683 1004.8586 1.1914 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.44379602   4197.9300 999.8980 25.24923384 13.37 6.70 6.67 706983.42 5.1079 5.107914 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 36112.10 36112.10 1.0000 2.44388195 2.051317 26.40 17.04 0.00840708 47966.0 11.92 11.55 0.00840708 33189.4 1.28970906 6.70 13.37 6.67 2195.006 33917.10 26.40 0.00840708 17.04 2.05124512 99.9965 21.11 0.00859184 21.11 0.00859456 54.5464 204111.13 0.00 36425.73 35509.87 2.44388195 26.40 17.15 0.00840708 47966.0 12.16 11.59 0.00825857 33061.1
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15471.261 15471.261 0.615395 0.00013535 263.983 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.44379602   4197.9300 999.8980 3.42933285 54.44 82.22 27.78 399923.64 3.8686 3.946410 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 15471.26 15471.26 1.0000 0.73316458 0.615395 -4.30 -4.30 0.00265759 2304.4 16.70 13.09 0.00800000 37036.7 0.13533554 60.00 32.22 27.78 0.000 15471.26 -4.30 0.00265759 -4.30 2.05124512 333.3216 21.11 0.00749770 21.11 0.00749867 47.6741 88793.42 0.00 14236.78 14236.78 0.73316458 2.80 0.02 0.00265759 9473.9 22.03 9.93 0.00265759 28892.1



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 11.66 22.95 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 13.50 7946.33 0.00
RETAIL_1_FLR_1 897.50 8052.00 463.00
RETAIL_2_FLR_1 229.17 7933.00 0.00
MECH_FLR_1 43.33 8735.00 43.33
STORAGE_FLR_1 84.33 8760.00 84.33
LAUNDRY_FLR_1 7473.83 3296.50 2717.33
CAFE_FLR_1 939.67 7133.50 18.83
LOBBY_FLR_1 785.50 6771.67 16.33
ROOM_1_FLR_3 2360.50 8139.67 2040.17
ROOM_2_FLR_3 2903.83 8316.00 2645.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 784.33 8757.67 784.33
ROOM_5_FLR_3 2075.67 7997.67 1896.00
ROOM_6_FLR_3 2646.67 8425.17 2553.67
CORRIDOR_FLR_3 33.00 8751.67 33.00
ROOM_1_FLR_6 3246.33 8116.17 2903.00
ROOM_2_FLR_6 3710.00 8292.17 3453.67
ROOM_3_MULT9_FLR_6 1544.50 7802.17 1137.33
BANQUET_FLR_6 4133.83 1733.67 12.50
DINING_FLR_6 5851.00 629.00 7.17
KITCHEN_FLR_6 8508.50 6247.17 6232.50
CORRIDOR_FLR_6 74.17 8591.00 50.17
Facility 8756.83 8760.00 7392.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 269.00 0.00 269.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 12.33 11.67 12.33 11.67
ROOM_2_FLR_3 22.83 8.67 22.83 8.67
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 3.67 4.83 3.67 4.83
ROOM_5_FLR_3 11.33 7.67 11.33 7.67
ROOM_6_FLR_3 22.83 8.33 22.83 8.33
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 6.17 16.17 6.17 16.17
ROOM_2_FLR_6 13.50 13.50 13.50 13.50
ROOM_3_MULT9_FLR_6 2.67 5.00 2.67 5.00
BANQUET_FLR_6 0.00 21.17 0.00 21.17
DINING_FLR_6 0.00 35.00 0.00 35.00
KITCHEN_FLR_6 0.00 440.83 0.00 440.83
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 27.83 541.50 27.83 541.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.958 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 3.008 0.139 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.327 0.046 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.437 0.052 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.496 0.052 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 21.084 0.149 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 4.177 0.109 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.678 0.045 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.017
ROOM_2_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.020
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.080 0.000 0.045
ROOM_5_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.031
ROOM_6_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.030
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.578 0.022 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.472 0.180 0.000 0.016
ROOM_2_FLR_6 0.95 1.50 118.93 0.472 0.180 0.000 0.020
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.146 0.000 0.052
BANQUET_FLR_6 145.01 249.90 1010.89 4.302 0.052 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 4.701 0.052 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 20.054 0.150 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.118 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.594 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.765 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.817 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.258 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.292 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 12.445 0.002 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 2.556 0.002 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.031 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.456 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.518 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.456 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.341 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.456 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.518 0.002 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 2.746 0.001 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 3.123 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 8.722 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.659 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 39834444.05 0.00 39834444.05 0.00 39834444.05 26946214.98 2.89 0.18 8756.93 0.00
RETAIL_1_FLR_1 6933081.14 0.00 6933081.14 319403.00 7252484.14 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3527307.37 0.00 3527307.37 123289.96 3650597.33 2892943.94 204.06 110.40 8445.54 0.00
MECH_FLR_1 2462426.39 0.00 2462426.39 291384.23 2753810.62 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1615493.47 0.00 1615493.47 168112.65 1783606.12 1821682.01 8760.00 0.00 0.00 0.00
LAUNDRY_FLR_1 56209206.08 0.00 56209206.08 397870.28 56607076.36 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 27007123.08 0.00 27007123.08 706058.42 27713181.50 21330615.53 145.15 28.66 8586.18 0.00
LOBBY_FLR_1 74986393.72 0.00 74986393.72 2017370.18 77003763.91 59728886.00 141.88 23.83 8594.29 0.00
ROOM_1_FLR_3 1946875.62 17092.47 1963968.09 185391.43 2149359.53 1946875.62 0.00 8521.95 238.05 0.00
ROOM_2_FLR_3 1946647.51 20919.89 1967567.40 185377.29 2152944.69 1946647.51 0.00 8469.65 290.35 0.00
ROOM_3_MULT19_FLR_3 26397887.27 31348.84 26429236.12 51726.29 26480962.40 26397887.27 0.00 8317.67 442.33 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 29116.90 26434222.63 51740.43 26485963.06 26405105.73 0.00 8318.08 441.92 0.00
ROOM_5_FLR_3 1946875.62 31756.29 1978631.91 185391.43 2164023.34 1946875.62 0.00 8316.50 443.50 0.00
ROOM_6_FLR_3 1946647.51 31078.67 1977726.18 185377.29 2163103.47 1946647.51 0.00 8316.50 443.50 0.00
CORRIDOR_FLR_3 23766685.62 0.00 23766685.62 224175.54 23990861.16 14972100.18 1.20 0.17 8758.63 0.00
ROOM_1_FLR_6 486718.90 16316.55 503035.45 185430.49 688465.95 486718.90 0.00 8551.44 208.56 0.00
ROOM_2_FLR_6 486661.88 19954.29 506616.17 185416.35 692032.52 486661.88 0.00 8507.81 252.19 0.00
ROOM_3_MULT9_FLR_6 3126920.42 33612.43 3160532.84 94872.73 3255405.57 3126920.42 0.00 8340.28 419.72 0.00
BANQUET_FLR_6 37321790.68 0.00 37321790.68 452774.66 37774565.34 37458366.31 4850.59 276.42 3632.99 0.00
DINING_FLR_6 40777551.71 0.00 40777551.71 452774.66 41230326.37 37458366.31 3432.79 231.26 5095.95 0.00
KITCHEN_FLR_6 54200193.68 0.00 54200193.68 405338.30 54605531.98 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12169189.29 0.00 12169189.29 396722.51 12565911.80 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 5337568.48 0.45E+10 18682123.06 0.45E+10 0.43E+10 8760.00 8574.64 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.2631 0.0000 1.2631 0.0000 1.2631 0.8545 2.89 0.18 8756.93
RETAIL_1_FLR_1 0.2198 0.0000 0.2198 0.0101 0.2300 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1119 0.0000 0.1119 0.0039 0.1158 0.0917 204.06 110.40 8445.54
MECH_FLR_1 0.0781 0.0000 0.0781 0.0092 0.0873 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0512 0.0000 0.0512 0.0053 0.0566 0.0578 8760.00 0.00 0.00
LAUNDRY_FLR_1 1.7824 0.0000 1.7824 0.0126 1.7950 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8564 0.0000 0.8564 0.0224 0.8788 0.6764 145.15 28.66 8586.18
LOBBY_FLR_1 2.3778 0.0000 2.3778 0.0640 2.4418 1.8940 141.88 23.83 8594.29
ROOM_1_FLR_3 0.0617 0.0005 0.0623 0.0059 0.0682 0.0617 0.00 8521.95 238.05
ROOM_2_FLR_3 0.0617 0.0007 0.0624 0.0059 0.0683 0.0617 0.00 8469.65 290.35
ROOM_4_MULT19_FLR_3 0.8373 0.0009 0.8382 0.0016 0.8399 0.8373 0.00 8318.08 441.92
ROOM_5_FLR_3 0.0617 0.0010 0.0627 0.0059 0.0686 0.0617 0.00 8316.50 443.50
ROOM_6_FLR_3 0.0617 0.0010 0.0627 0.0059 0.0686 0.0617 0.00 8316.50 443.50
CORRIDOR_FLR_3 0.7536 0.0000 0.7536 0.0071 0.7607 0.4748 1.20 0.17 8758.63
ROOM_1_FLR_6 0.0154 0.0005 0.0160 0.0059 0.0218 0.0154 0.00 8551.44 208.56
ROOM_2_FLR_6 0.0154 0.0006 0.0161 0.0059 0.0219 0.0154 0.00 8507.81 252.19
ROOM_3_MULT9_FLR_6 0.0992 0.0011 0.1002 0.0030 0.1032 0.0992 0.00 8340.28 419.72
BANQUET_FLR_6 1.1835 0.0000 1.1835 0.0144 1.1978 1.1878 4850.59 276.42 3632.99
DINING_FLR_6 1.2930 0.0000 1.2930 0.0144 1.3074 1.1878 3432.79 231.26 5095.95
KITCHEN_FLR_6 1.7187 0.0000 1.7187 0.0129 1.7315 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3859 0.0000 0.3859 0.0126 0.3985 0.1256 0.00 0.00 8760.00
Total Facility 79.8821 0.0937 79.9758 0.4677 80.4436 73.9670 8760.00 8574.64 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.54E+09 0.00 0.54E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 91819351.87 231196.34 92050548.21 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.1489 0.0000 17.1489 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9116 0.0073 2.9189 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 5976.69 2783.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.5538 18.4330 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9119 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1333
Defaulted Fields 1181
Fields with Defaults 4001
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
Electricity:Building 2532.69 31781.30 10-JUN-05:00 158241.73 02-JAN-20:10
Electricity:Zone:BASEMENT 332.05 3744.83 02-JAN-02:10 25084.28 02-JAN-20:10
Electricity:SpaceType:GENERAL 2525.60 31640.15 10-JUN-05:00 158000.40 02-JAN-20:10
InteriorLights:Electricity 867.42 7438.18 10-JUN-05:00 71560.59 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 188.95 1716.93 02-JAN-02:10 15451.75 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 867.42 7438.18 10-JUN-05:00 71560.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity 867.42 7438.18 10-JUN-05:00 71560.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 188.95 1716.93 02-JAN-02:10 15451.75 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 867.42 7438.18 10-JUN-05:00 71560.59 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.95 223.93 02-JAN-02:10 1401.96 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.76 79.59 02-JAN-02:10 716.35 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.76 79.59 02-JAN-02:10 716.35 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.94 259.31 02-JAN-02:10 1623.47 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 10.14 92.17 02-JAN-02:10 829.54 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 10.14 92.17 02-JAN-02:10 829.54 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.64 250.98 02-JAN-02:10 1507.71 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.17 74.25 02-JAN-02:10 668.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.17 74.25 02-JAN-02:10 668.27 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 7.74 88.65 02-JAN-02:10 581.19 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 4.15 37.67 02-JAN-02:10 339.04 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 4.15 37.67 02-JAN-02:10 339.04 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 73.48 1013.10 02-JAN-02:10 5026.41 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 5.55 50.40 02-JAN-02:10 453.60 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 5.55 50.40 02-JAN-02:10 453.60 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 30.52 307.62 10-JUN-05:00 2922.95 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 16.18 95.71 01-JAN-13:10 1957.67 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 16.18 95.71 01-JAN-13:10 1957.67 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 247.88 2995.36 10-JUN-05:00 18583.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 98.88 883.95 10-JUN-05:00 8554.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 98.88 883.95 10-JUN-05:00 8554.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 21.40 271.61 01-JAN-02:10 1567.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 21.40 271.58 01-JAN-02:10 1567.69 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 325.45 4437.75 01-JAN-02:10 23570.01 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 130.46 1104.51 01-JAN-02:10 10040.97 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 130.46 1104.51 01-JAN-02:10 10040.97 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 325.54 4438.96 01-JAN-02:10 23576.46 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 130.49 1104.81 01-JAN-02:10 10043.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 130.49 1104.81 01-JAN-02:10 10043.72 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 21.40 271.61 01-JAN-02:10 1567.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 10.93 92.50 01-JAN-02:10 840.90 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 21.40 271.58 01-JAN-02:10 1567.69 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 10.92 92.49 01-JAN-02:10 840.80 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 5.35 67.90 01-JAN-02:10 391.97 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.73 23.12 01-JAN-02:10 210.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.73 23.12 01-JAN-02:10 210.22 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 5.35 67.89 01-JAN-02:10 391.92 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.73 23.12 01-JAN-02:10 210.20 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.73 23.12 01-JAN-02:10 210.20 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 38.55 525.67 01-JAN-02:10 2791.95 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 15.45 130.83 01-JAN-02:10 1189.39 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 15.45 130.83 01-JAN-02:10 1189.39 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 211.25 2478.49 20-MAY-05:00 10185.74 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 35.39 229.19 20-MAY-05:00 3437.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 35.39 229.19 20-MAY-05:00 3437.84 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 211.25 2478.49 20-MAY-05:00 10185.74 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 35.39 229.19 20-MAY-05:00 3437.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 35.39 229.19 20-MAY-05:00 3437.84 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 455.64 6266.47 02-JAN-02:10 18984.42 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 14.81 134.55 02-JAN-02:10 1210.92 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 14.81 134.55 02-JAN-02:10 1210.92 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorEquipment:Electricity 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.08 1117.35 10-JAN-23:30 3438.60 11-APR-06:40
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 483.83 2613.69 27-APR-01:40 131474.04 22-JUL-18:10
LowTempRefrigeration:Refrigeration:Electricity 20.51 0.00 01-JAN-11:10 2018.27 11-APR-06:40
MedTempRefrigeration:Refrigeration:Electricity 34.49 972.85 11-JAN-04:10 1245.48 01-FEB-07:20
Fans:Electricity 534.94 12523.58 22-SEP-01:30 41877.08 19-MAY-21:20
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 787.86 14623.94 13-AUG-01:20 44589.52 19-MAY-21:20
ExteriorEquipment:Electricity 650.09 9607.53 02-JAN-02:20 39721.54 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 31.07 542.62 01-JUL-05:00 1847.44 24-JAN-21:10
ElectricityPurchased:Facility 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
ElectricityPurchased:Plant 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
Cogeneration:ElectricityPurchased 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
General:Cogeneration:ElectricityPurchased 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
ElectricityNet:Plant 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
Cogeneration:ElectricityNet 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
General:Cogeneration:ElectricityNet 4685.14 72849.39 03-JUN-04:40 332236.78 22-JUL-18:20
General:Fans:Electricity 534.94 12523.58 22-SEP-01:30 41877.08 19-MAY-21:20
ExteriorLights:Electricity 261.73 0.00 01-JAN-08:20 16690.39 01-JAN-00:10
General:ExteriorLights:Electricity 261.73 0.00 01-JAN-08:20 16690.39 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 221.85 0.00 20-APR-15:20 9938.94 06-JAN-21:20
General:HeatRecovery:Electricity 221.85 0.00 20-APR-15:20 9938.94 06-JAN-21:20
WaterSystems:Electricity 90.74 1086.57 12-JUL-00:30 4738.56 28-APR-18:50
Water Heater:WaterSystems:Electricity 90.74 1086.57 12-JUL-00:30 4738.56 28-APR-18:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 268.59 0.00 01-JAN-00:10 120944.72 22-JUL-18:10
General:Cooling:Electricity 268.59 0.00 01-JAN-00:10 120944.72 22-JUL-18:10
Pumps:Electricity 69.50 47.91 04-APR-10:30 4471.33 14-AUG-18:10
General:Pumps:Electricity 69.50 47.91 04-APR-10:30 4471.33 14-AUG-18:10
WIRED_LTG_ELECTRICITY 30.53 0.00 01-JAN-00:10 2518.93 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5893.18 31829.34 29-APR-01:10 527721.50 22-JAN-18:30
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 4104.34 18467.44 14-APR-10:40 427654.93 22-JAN-18:30
WaterSystems:NaturalGas 3328.63 18467.44 15-JAN-14:30 296341.77 27-FEB-21:30
Water Heater:WaterSystems:NaturalGas 3328.63 18467.44 15-JAN-14:30 296341.77 27-FEB-21:30
Heating:NaturalGas 775.71 0.00 25-MAR-13:00 180675.89 02-DEC-16:10
Boiler:Heating:NaturalGas 775.71 0.00 25-MAR-13:00 180675.89 02-DEC-16:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 772.30 0.00 01-JAN-00:10 405697.43 22-JUL-18:20
PlantLoopCoolingDemand:HVAC 772.30 0.00 01-JAN-00:10 405697.43 22-JUL-18:20
CoolingCoils:PlantLoopCoolingDemand 772.30 0.00 01-JAN-00:10 405697.43 22-JUL-18:20


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:20
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:20
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:20
Water Heater:WaterSystems:Water 5742.51 0.00 18-APR-01:40 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:20
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:20
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:20
Water Heater:WaterSystems:MainsWater 5742.51 0.00 18-APR-01:40 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 17-JAN-07:30
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 17-JAN-07:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 12540.79 146409.23 17-OCT-13:10 1741312.71 22-JUL-18:20
EnergyTransfer:Building 4772.99 54032.01 02-MAR-10:10 342309.75 22-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 711.33 9901.15 17-JUN-01:50 36522.21 23-JUL-10:40
Refrigeration:EnergyTransfer 183.94 4032.98 10-JAN-23:20 10647.43 11-APR-06:40
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.97 2016.49 10-JAN-23:20 5323.71 11-APR-06:40
General:Refrigeration:EnergyTransfer 91.97 2016.49 10-JAN-23:20 5323.71 11-APR-06:40
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.97 2016.49 10-JAN-23:20 5323.71 11-APR-06:40
EnergyTransfer:Plant 3357.93 14689.49 11-OCT-01:30 970282.43 22-JUL-18:20
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.63 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.34 1868.55 11-JAN-04:10 2686.44 01-FEB-07:20
EnergyTransfer:Zone:BASEMENT 411.53 2941.79 20-MAY-06:20 23244.55 13-DEC-23:10
Heating:EnergyTransfer 121.83 0.00 01-JAN-08:10 58777.46 30-DEC-16:20
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 121.83 0.00 01-JAN-08:10 58777.46 30-DEC-16:20
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 4559.18 48322.58 02-MAR-10:10 338736.19 22-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 411.53 2941.79 20-MAY-06:20 23244.55 13-DEC-23:10
General:Cooling:EnergyTransfer 4559.18 48322.58 02-MAR-10:10 338736.19 22-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 411.53 2941.79 20-MAY-06:20 23244.55 13-DEC-23:10
EnergyTransfer:Zone:RETAIL_1_FLR_1 36.18 0.00 15-DEC-01:00 4201.04 27-SEP-13:20
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.49 0.00 01-JAN-00:10 688.31 10-JAN-08:00
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.49 0.00 01-JAN-00:10 688.31 10-JAN-08:00
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 35.69 0.00 02-JAN-07:10 4201.04 27-SEP-13:20
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 35.69 0.00 02-JAN-07:10 4201.04 27-SEP-13:20
EnergyTransfer:Zone:RETAIL_2_FLR_1 32.76 88.07 23-NOV-06:20 1774.77 21-JUL-20:50
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 47.11 05-MAR-13:50
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 47.11 05-MAR-13:50
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.76 88.07 23-NOV-06:20 1774.77 21-JUL-20:50
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.76 88.07 23-NOV-06:20 1774.77 21-JUL-20:50
EnergyTransfer:Zone:MECH_FLR_1 19.39 0.61 13-JAN-03:40 1090.62 23-JUL-10:40
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.02 0.00 01-JAN-00:10 158.56 12-JAN-15:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.02 0.00 01-JAN-00:10 158.56 12-JAN-15:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 19.38 0.00 10-JAN-04:10 1090.62 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 19.38 0.00 10-JAN-04:10 1090.62 23-JUL-10:40
EnergyTransfer:Zone:STORAGE_FLR_1 10.72 0.00 26-FEB-07:30 696.47 23-JUL-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.10 0.00 01-JAN-00:10 218.18 12-JAN-15:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.10 0.00 01-JAN-00:10 218.18 12-JAN-15:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.62 0.00 01-JAN-17:00 696.47 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.62 0.00 01-JAN-17:00 696.47 23-JUL-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 588.50 6987.48 14-NOV-04:30 38563.52 26-APR-19:50
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 105.65 01-FEB-04:40
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 105.65 01-FEB-04:40
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 588.50 6987.48 14-NOV-04:30 38563.52 26-APR-19:50
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 588.50 6987.48 14-NOV-04:30 38563.52 26-APR-19:50
EnergyTransfer:Zone:CAFE_FLR_1 226.96 419.99 01-NOV-09:30 14461.57 27-SEP-13:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.04 0.00 01-JAN-00:10 562.71 01-FEB-09:50
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.04 0.00 01-JAN-00:10 562.71 01-FEB-09:50
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 226.92 419.99 01-NOV-09:30 14461.57 27-SEP-13:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 226.92 419.99 01-NOV-09:30 14461.57 27-SEP-13:10
EnergyTransfer:Zone:LOBBY_FLR_1 727.78 2886.50 04-DEC-09:50 42044.19 22-JUN-06:00
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.01 0.00 01-JAN-00:10 854.60 05-MAR-13:50
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.01 0.00 01-JAN-00:10 854.60 05-MAR-13:50
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 727.76 2886.50 04-DEC-09:50 42044.19 22-JUN-06:00
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 727.76 2886.50 04-DEC-09:50 42044.19 22-JUN-06:00
EnergyTransfer:Zone:ROOM_1_FLR_3 45.66 0.12 28-MAY-03:00 12792.85 15-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 15.69 0.00 01-JAN-08:10 4502.64 27-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 15.69 0.00 01-JAN-08:10 4502.64 27-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 29.96 0.00 01-JAN-00:10 12792.85 15-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 29.96 0.00 01-JAN-00:10 12792.85 15-JUN-18:20
EnergyTransfer:Zone:ROOM_2_FLR_3 42.47 0.07 12-OCT-15:30 11986.17 15-JUN-18:30
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 19.35 0.00 01-JAN-08:10 4758.06 27-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 19.35 0.00 01-JAN-08:10 4758.06 27-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 23.13 0.00 01-JAN-00:10 11986.17 15-JUN-18:30
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 23.13 0.00 01-JAN-00:10 11986.17 15-JUN-18:30
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 318.38 1.70 16-DEC-18:30 58815.74 27-SEP-13:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 4.13 0.00 01-JAN-00:10 11270.45 17-DEC-04:40
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 4.13 0.00 01-JAN-00:10 11270.45 17-DEC-04:40
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 314.25 0.00 05-JAN-01:00 58815.74 27-SEP-13:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 314.25 0.00 05-JAN-01:00 58815.74 27-SEP-13:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 287.70 0.55 19-NOV-01:50 64756.11 22-JUL-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 20.07 0.00 01-JAN-07:10 27340.35 11-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 20.07 0.00 01-JAN-07:10 27340.35 11-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 267.63 0.00 01-JAN-00:10 64756.11 22-JUL-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 267.63 0.00 01-JAN-00:10 64756.11 22-JUL-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 47.08 0.21 27-FEB-17:30 12899.80 22-JUL-08:50
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 15.69 0.00 01-JAN-08:10 4500.68 30-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 15.69 0.00 01-JAN-08:10 4500.68 30-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 31.39 0.00 01-JAN-00:10 12899.80 22-JUL-08:50
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 31.39 0.00 01-JAN-00:10 12899.80 22-JUL-08:50
EnergyTransfer:Zone:ROOM_6_FLR_3 43.19 0.24 04-SEP-02:50 11913.41 22-JUL-08:50
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 19.23 0.00 01-JAN-08:10 4864.32 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 19.23 0.00 01-JAN-08:10 4864.32 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 23.97 0.00 01-JAN-00:10 11913.41 22-JUL-08:50
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 23.97 0.00 01-JAN-00:10 11913.41 22-JUL-08:50
EnergyTransfer:Zone:CORRIDOR_FLR_3 168.56 1.74 04-DEC-14:00 10389.76 23-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.31 0.00 01-JAN-00:10 1194.24 10-DEC-16:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.31 0.00 01-JAN-00:10 1194.24 10-DEC-16:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 168.25 0.00 03-JAN-11:40 10389.76 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 168.25 0.00 03-JAN-11:40 10389.76 23-JUL-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 13.64 0.06 02-MAR-17:10 3634.12 15-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.13 0.00 01-JAN-08:10 1497.27 27-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.13 0.00 01-JAN-08:10 1497.27 27-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.51 0.00 01-JAN-00:10 3634.12 15-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.51 0.00 01-JAN-00:10 3634.12 15-JUN-18:20
EnergyTransfer:Zone:ROOM_2_FLR_6 12.97 0.04 27-OCT-13:30 3307.90 15-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 7.33 0.00 01-JAN-08:10 1543.19 27-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 7.33 0.00 01-JAN-08:10 1543.19 27-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.64 0.00 01-JAN-00:10 3307.90 15-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.64 0.00 01-JAN-00:10 3307.90 15-JUN-18:20
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 69.38 0.04 01-NOV-06:00 18460.56 12-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 13.12 0.00 01-JAN-08:10 6570.65 10-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 13.12 0.00 01-JAN-08:10 6570.65 10-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 56.25 0.00 01-JAN-00:10 18460.56 12-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 56.25 0.00 01-JAN-00:10 18460.56 12-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 414.97 3676.51 01-NOV-09:30 21531.45 21-JUL-21:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 414.97 3676.51 01-NOV-09:30 21531.45 21-JUL-21:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 414.97 3676.51 01-NOV-09:30 21531.45 21-JUL-21:10
EnergyTransfer:Zone:DINING_FLR_6 459.17 5112.81 01-NOV-09:30 22913.28 21-JUL-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 459.17 5112.81 01-NOV-09:30 22913.28 21-JUL-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 459.17 5112.81 01-NOV-09:30 22913.28 21-JUL-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 619.36 7301.31 11-MAY-04:30 31453.76 23-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 619.36 7301.31 11-MAY-04:30 31453.76 23-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 84.66 5.54 11-JAN-08:50 5450.68 23-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.12 0.00 01-JAN-00:10 683.74 10-JAN-08:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.12 0.00 01-JAN-00:10 683.74 10-JAN-08:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 84.54 0.00 04-JAN-09:10 5450.68 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 84.54 0.00 04-JAN-09:10 5450.68 23-JUL-10:40
PlantLoopHeatingDemand:Facility 1345.76 10164.36 18-AUG-00:30 184641.95 24-JAN-07:20
PlantLoopHeatingDemand:Plant 798.38 10162.28 12-AUG-00:40 55882.93 17-FEB-07:40
WaterSystems:PlantLoopHeatingDemand 798.38 10162.28 12-AUG-00:40 55882.93 17-FEB-07:40
General:WaterSystems:PlantLoopHeatingDemand 798.38 10162.28 12-AUG-00:40 55882.93 17-FEB-07:40
EnergyTransfer:HVAC 4409.87 184.29 16-JUN-12:20 457830.71 12-JAN-00:10
HeatingCoils:EnergyTransfer 547.38 0.00 25-MAR-13:00 144507.88 02-DEC-16:10
PlantLoopHeatingDemand:HVAC 547.38 0.00 25-MAR-13:00 144507.88 02-DEC-16:10
HeatingCoils:PlantLoopHeatingDemand 547.38 0.00 25-MAR-13:00 144507.88 02-DEC-16:10
CoolingCoils:EnergyTransfer 772.30 0.00 01-JAN-00:10 405697.43 22-JUL-18:20
HeatRecoveryForHeating:EnergyTransfer 3088.81 0.00 20-APR-15:20 403233.29 12-JAN-00:10
HeatRecoveryForCooling:EnergyTransfer 1.39 0.00 01-JAN-00:10 28918.39 22-JUL-15:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 798.38 10162.28 12-AUG-00:40 55882.93 17-FEB-07:40
WaterUse:WaterSystems:EnergyTransfer 798.38 10162.28 12-AUG-00:40 55882.93 17-FEB-07:40
Boilers:EnergyTransfer 541.85 0.00 25-MAR-13:00 145536.06 02-DEC-16:10
Chillers:EnergyTransfer 828.57 0.00 01-JAN-00:10 407181.40 22-JUL-18:20
HeatRejection:EnergyTransfer 1097.16 0.00 01-JAN-00:10 527954.69 22-JUL-18:20
General:HeatRejection:EnergyTransfer 1097.16 0.00 01-JAN-00:10 527954.69 22-JUL-18:20



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -411.535 0.000 0.000 139.632 188.948 143.105 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -60.150
RETAIL_1_FLR_1 0.000 0.000 0.487 -35.691 0.000 0.000 15.948 8.760 10.186 23.069 0.000 0.005 0.000 0.000 -12.421 0.000 -4.732 -5.611
RETAIL_2_FLR_1 0.000 0.000 0.001 -32.758 0.000 0.000 17.151 10.144 11.795 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -1.987 -4.349
MECH_FLR_1 0.000 0.000 0.016 -19.377 0.000 0.000 3.777 8.172 12.471 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -4.480 -0.585
STORAGE_FLR_1 0.000 0.000 0.103 -10.622 0.000 0.000 2.952 4.146 3.598 0.000 0.000 0.003 2.351 0.000 0.000 0.000 -2.531 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -588.495 0.000 0.000 11.176 5.547 658.131 0.000 0.000 0.008 0.000 0.000 0.000 0.000 -6.741 -79.627
CAFE_FLR_1 0.000 0.000 0.039 -226.926 0.000 0.000 199.433 16.176 14.341 64.051 0.000 0.011 0.000 0.000 -36.872 0.000 -11.057 -19.195
LOBBY_FLR_1 0.000 0.000 0.015 -727.763 0.000 0.000 565.340 98.878 148.998 84.311 0.000 0.032 0.000 0.000 -51.188 0.000 -33.256 -85.366
ROOM_1_FLR_3 20.806 -20.562 0.000 -14.513 0.000 0.000 9.625 10.925 10.478 42.658 0.000 0.017 0.000 0.000 -28.349 0.000 -11.609 -19.477
ROOM_2_FLR_3 24.886 -14.535 0.000 -14.131 0.000 0.000 9.670 10.924 10.477 29.388 0.000 0.017 0.000 0.000 -28.561 0.000 -11.571 -16.564
ROOM_3_MULT19_FLR_3 9.551 -111.743 0.000 -207.924 0.000 0.000 0.000 130.455 194.997 274.828 0.000 0.060 0.016 0.000 -158.014 0.000 -76.398 -55.813
ROOM_4_MULT19_FLR_3 58.280 -117.867 0.000 -187.977 0.000 0.000 185.121 130.491 195.050 69.844 0.000 0.146 0.000 0.000 -157.071 0.000 -69.347 -106.671
ROOM_5_FLR_3 20.708 -22.010 0.000 -14.400 0.000 0.000 9.673 10.925 10.478 43.266 0.000 0.017 0.000 0.000 -27.767 0.000 -11.949 -18.941
ROOM_6_FLR_3 24.709 -15.355 0.000 -14.096 0.000 0.000 9.708 10.924 10.477 29.685 0.000 0.017 0.000 0.000 -27.752 0.000 -11.760 -16.557
CORRIDOR_FLR_3 0.000 0.000 0.315 -168.249 0.000 0.000 120.642 91.336 0.000 38.815 0.000 0.016 0.000 0.000 -36.100 0.000 -13.652 -33.124
ROOM_1_FLR_6 7.559 -5.310 0.000 -3.622 0.000 0.000 2.403 2.731 2.620 10.570 0.000 0.004 0.000 0.000 -7.046 0.000 -2.906 -7.003
ROOM_2_FLR_6 8.889 -3.670 0.000 -3.528 0.000 0.000 2.415 2.731 2.619 7.268 0.000 0.004 0.000 0.000 -7.086 0.000 -2.896 -6.746
ROOM_3_MULT9_FLR_6 19.838 -39.424 0.000 -23.540 0.000 0.000 21.689 15.453 23.098 59.321 0.000 0.021 0.000 0.000 -33.309 0.000 -15.097 -28.049
BANQUET_FLR_6 0.000 0.000 0.000 -414.969 0.000 0.000 315.935 35.392 175.857 6.477 0.000 0.005 0.000 0.000 -21.790 0.000 -8.075 -88.831
DINING_FLR_6 0.000 0.000 0.000 -459.174 0.000 0.000 314.687 35.392 175.857 6.237 0.000 0.005 0.000 0.000 -22.401 0.000 -8.137 -42.465
KITCHEN_FLR_6 0.000 0.000 0.000 -619.348 0.000 0.000 28.212 14.807 550.372 19.580 0.000 0.004 29.075 0.000 -15.401 0.000 -7.302 -0.000
CORRIDOR_FLR_6 0.000 0.000 0.116 -84.541 0.000 0.000 32.079 24.166 0.000 19.091 0.000 0.005 31.330 0.000 -16.197 0.000 -6.049 -0.000
Total Facility 195.226 -350.475 1.091 -4283.175 0.000 0.000 2017.267 867.422 2365.005 828.459 0.000 0.406 62.774 0.000 -687.326 0.000 -321.532 -695.124


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 19-DEC-21:32 0.00 0.00 0.00 -36203.91 0.00 0.00 5771.09 13734.82 9125.55 0.00 0.00 0.00 7572.45 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 04-FEB-14:33 0.00 0.00 0.00 -5357.10 0.00 0.00 226.86 198.99 252.59 5405.14 0.00 0.00 0.00 0.00 -0.00 0.00 -183.50 -542.97
RETAIL_2_FLR_1 04-OCT-20:30 0.00 0.00 0.00 -2458.22 0.00 0.00 704.27 737.37 752.15 0.00 0.00 0.00 346.64 0.00 -0.00 0.00 -82.21 0.00
MECH_FLR_1 03-MAY-06:17 0.00 0.00 0.00 -1542.54 0.00 0.00 81.58 371.26 530.18 0.00 0.00 0.00 739.91 0.00 -0.00 0.00 -180.38 0.00
STORAGE_FLR_1 03-MAY-06:17 0.00 0.00 0.00 -975.59 0.00 0.00 64.51 188.35 152.94 0.00 0.00 0.00 670.31 0.00 -0.00 0.00 -100.52 0.00
LAUNDRY_FLR_1 16-NOV-19:27 0.00 0.00 0.00 -53822.07 0.00 0.00 408.01 403.20 41967.83 0.00 0.00 0.00 11328.95 0.00 -0.00 0.00 -285.92 0.00
CAFE_FLR_1 04-FEB-14:33 0.00 0.00 0.00 -21814.04 0.00 0.00 2982.91 119.64 355.63 15146.33 0.00 0.00 3615.00 0.00 -0.00 0.00 -405.47 0.00
LOBBY_FLR_1 01-MAY-02:26 0.00 0.00 0.00 -65435.50 0.00 0.00 26770.25 950.48 2111.41 0.00 0.00 0.00 39947.46 0.00 -3042.18 0.00 -1301.92 0.00
ROOM_1_FLR_3 29-SEP-16:01 0.00 -16161.97 0.00 -699.88 0.00 0.00 196.33 235.45 505.73 7631.70 0.00 0.00 8600.71 0.00 -0.00 0.00 -308.06 0.00
ROOM_2_FLR_3 22-JUN-19:01 0.00 -14328.76 0.00 -714.66 0.00 0.00 282.43 840.80 653.15 1295.44 0.00 0.00 12290.33 0.00 -0.00 0.00 -318.72 0.00
ROOM_3_MULT19_FLR_3 27-SEP-13:20 0.00 -48769.60 0.00 -10041.99 0.00 0.00 0.00 2811.47 2352.88 76668.68 0.00 0.00 0.00 0.00 -0.00 0.00 -294.88 -22726.57
ROOM_4_MULT19_FLR_3 22-JUL-08:41 0.00 -67905.06 0.00 -10483.65 0.00 0.00 2467.13 5624.48 12159.85 11563.45 0.00 123.78 46450.01 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 22-JUL-08:22 0.00 -15170.09 0.00 -1046.33 0.00 0.00 88.23 470.90 653.23 9963.20 0.00 0.00 5114.93 0.00 -0.00 0.00 -74.07 0.00
ROOM_6_FLR_3 22-JUL-08:22 0.00 -13831.12 0.00 -1053.09 0.00 0.00 88.27 470.85 653.15 9632.72 0.00 0.00 4115.75 0.00 -0.00 0.00 -76.53 0.00
CORRIDOR_FLR_3 03-MAY-06:17 0.00 0.00 0.00 -14639.56 0.00 0.00 2602.07 4149.60 0.00 0.00 0.00 0.00 9960.07 0.00 -1525.11 0.00 -547.07 0.00
ROOM_1_FLR_6 11-JUL-18:52 0.00 -4404.82 0.00 -206.32 0.00 0.00 57.77 187.10 121.16 534.38 0.00 0.00 3798.84 0.00 -0.00 0.00 -88.12 0.00
ROOM_2_FLR_6 11-JUL-18:52 0.00 -3972.90 0.00 -208.26 0.00 0.00 57.60 187.08 121.15 674.50 0.00 0.00 3229.66 0.00 -0.00 0.00 -88.83 0.00
ROOM_3_MULT9_FLR_6 29-SEP-16:01 0.00 -23129.38 0.00 -1079.57 0.00 0.00 456.25 333.03 1114.83 3744.14 0.00 0.00 18905.28 0.00 -0.00 0.00 -344.58 0.00
BANQUET_FLR_6 26-APR-22:18 0.00 0.00 0.00 -35552.55 0.00 0.00 15394.08 1145.95 6747.90 0.00 0.00 0.00 13709.19 0.00 -1138.37 0.00 -306.20 0.00
DINING_FLR_6 26-APR-22:18 0.00 0.00 0.00 -38321.51 0.00 0.00 15360.27 1145.95 6747.90 0.00 0.00 0.00 16532.51 0.00 -1158.77 0.00 -306.35 0.00
KITCHEN_FLR_6 08-DEC-11:00 0.00 0.00 0.00 -40476.87 0.00 0.00 309.52 336.37 24259.91 1898.34 0.00 0.00 13937.99 0.00 -0.00 0.00 -265.24 0.00
CORRIDOR_FLR_6 03-MAY-06:17 0.00 0.00 0.00 -7105.80 0.00 0.00 705.23 1097.93 0.00 0.00 0.00 0.00 6199.46 0.00 -665.45 0.00 -231.37 0.00
Total Facility 22-JUL-18:02 0.00 -155955.13 0.00 -207456.63 0.00 0.00 64110.44 56968.49 113378.48 66041.42 0.00 4354.36 58558.58 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 24-OCT-06:30 0.00 0.00 794.22 0.00 0.00 0.00 358.04 397.97 433.01 0.00 0.00 0.00 0.00 0.00 -709.80 0.00 -184.42 -1089.03
RETAIL_2_FLR_1 13-DEC-11:20 0.00 0.00 101.45 0.00 0.00 0.00 206.98 230.43 292.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -66.21 -765.15
MECH_FLR_1 12-JAN-15:00 0.00 0.00 158.56 0.00 0.00 0.00 43.84 185.63 309.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -254.85 -442.45
STORAGE_FLR_1 12-JAN-15:00 0.00 0.00 218.18 0.00 0.00 0.00 33.72 94.17 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -147.03 -288.27
LAUNDRY_FLR_1 14-NOV-04:18 0.00 0.00 575.54 0.00 0.00 0.00 614.38 50.40 9326.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -214.09 -10352.41
CAFE_FLR_1 28-JAN-09:38 0.00 0.00 1134.21 0.00 0.00 0.00 3527.86 304.53 508.04 0.00 0.00 0.00 0.00 0.00 -1217.37 0.00 -366.00 -3891.27
LOBBY_FLR_1 13-DEC-11:20 0.00 0.00 2027.53 0.00 0.00 0.00 6976.28 2098.98 3694.97 0.00 0.00 0.00 0.00 0.00 -1162.13 0.00 -1086.52 -12549.11
ROOM_1_FLR_3 23-DEC-16:01 5542.34 275.32 0.00 -275.32 0.00 0.00 163.32 277.50 221.25 0.00 0.00 0.00 0.00 0.00 -1164.31 0.00 -290.55 -4749.55
ROOM_2_FLR_3 19-DEC-19:01 5435.60 285.17 0.00 -285.17 0.00 0.00 417.29 748.31 484.60 0.00 0.00 0.00 0.00 0.00 -1289.47 0.00 -351.20 -5445.12
ROOM_3_MULT19_FLR_3 17-DEC-04:40 11270.15 3428.77 0.00 -3428.77 0.00 0.00 0.00 1104.51 3333.24 0.00 0.00 0.00 0.00 0.00 -12583.92 0.00 -2815.69 -308.29
ROOM_4_MULT19_FLR_3 11-JAN-16:01 28790.22 3631.80 0.00 -3631.80 0.00 0.00 5585.52 2812.24 3726.41 0.00 0.00 0.00 0.00 0.00 -10295.37 0.00 -3322.28 -27296.74
ROOM_5_FLR_3 23-DEC-16:01 5427.19 274.81 0.00 -274.81 0.00 0.00 163.33 277.50 221.25 0.00 0.00 0.00 0.00 0.00 -1159.88 0.00 -290.36 -4639.03
ROOM_6_FLR_3 22-DEC-16:01 5326.17 273.53 0.00 -273.53 0.00 0.00 293.99 235.42 200.16 0.00 0.00 0.00 0.00 0.00 -1374.93 0.00 -359.20 -4321.61
CORRIDOR_FLR_3 24-OCT-06:30 0.00 0.00 2613.19 0.00 0.00 0.00 2771.60 4149.60 0.00 0.00 0.00 0.00 0.00 0.00 -2007.98 0.00 -522.61 -7003.80
ROOM_1_FLR_6 23-DEC-16:01 1650.31 69.28 0.00 -69.28 0.00 0.00 40.83 69.37 55.31 0.00 0.00 0.00 0.00 0.00 -283.31 0.00 -73.24 -1459.28
ROOM_2_FLR_6 22-DEC-16:01 1613.55 68.98 0.00 -68.98 0.00 0.00 73.50 58.86 50.04 0.00 0.00 0.00 0.00 0.00 -335.58 0.00 -90.47 -1369.89
ROOM_3_MULT9_FLR_6 08-JUL-19:13 8109.87 677.94 0.00 -677.94 0.00 0.00 653.51 1189.39 1439.98 0.00 0.00 0.00 0.00 0.00 -448.85 0.00 -213.37 -10730.53
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 24-OCT-06:30 0.00 0.00 2268.36 0.00 0.00 0.00 733.34 1097.93 0.00 0.00 0.00 0.00 0.00 0.00 -893.70 0.00 -232.25 -2973.67
Total Facility 30-DEC-16:13 -19173.28 93476.15 1548.74 -93476.15 0.00 0.00 35359.84 21186.59 74838.26 0.00 0.00 0.00 0.00 0.00 -40488.23 0.00 -13807.21 -59464.70



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 23.0686 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.9452 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6727 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6727 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7044 2.7044 1.3684 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4721 0.4721 0.2389 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2407 0.2407 0.1218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1686 0.1686 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1106 0.1106 0.0560 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2847 3.2847 1.6621 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8404 1.8404 0.9313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1051 5.1051 2.5832 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6268 1.6268 0.8232 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1472 2.1472 1.0865 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2488 2.2488 1.1379 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2862 2.2862 1.1568 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8330 0.8330 0.4215 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 23.0686 22.9452 23.0686 11.6727 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3684 1.3684 1.3684 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2389 0.2389 0.2389 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1218 0.1218 0.1218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0853 0.0853 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0560 0.0560 0.0560 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6621 1.6621 1.6621 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9313 0.9313 0.9313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5832 2.5832 2.5832 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8232 0.8232 0.8232 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0865 1.0865 1.0865 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1379 1.1379 1.1379 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1568 1.1568 1.1568 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4215 0.4215 0.4215 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6727 11.6727 11.6727 11.6727 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 27.83
Number of hours cooling loads not met 541.50
Number of hours not met 568.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 775.71 180675.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 268.59 120944.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 867.42 71560.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 261.73 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 31.07 1847.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 534.94 41877.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 69.50 4471.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 221.85 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.56 3328.63 296341.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.51 2018.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.49 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1720.26 4685.14
Natural Gas 1788.84 5893.18
Additional 0.00 0.00
Total 3509.10 10578.33


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 76.46
Space Heating 0.00
Space Cooling 23.67
Fans (All) 47.15
Service Water Heating 8.00
Receptacle Equipment 146.16
Miscellaneous (All) 412.96
Subtotal 412.96


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 68.37
Service Water Heating 293.39
Miscellaneous (All) 519.44
Subtotal 519.44


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.20
Space Heating 7.33
Space Cooling 2.54
Fans (All) 5.06
Service Water Heating 32.32
Receptacle Equipment 32.59
Miscellaneous 11.96


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2572. 8760.
LTG_SCH_LOBBY 2295. 8760.
LTG_SCH_STORAGE 1580. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8759.33 0.67 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8623.83 136.17 0.00 0.00 0.00
ROOM_2_FLR_3 8669.83 90.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8753.83 6.17 0.00 0.00 0.00
ROOM_6_FLR_3 8754.83 5.17 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8561.83 198.17 0.00 0.00 0.00
ROOM_2_FLR_6 8610.17 149.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8756.33 3.67 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8757.33 2.67 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8561.83 0.00 0.00 0.00 0.00
Max 8760.00 198.17 0.00 0.00 0.00
Average 8733.06 26.94 0.00 0.00 0.00
Sum 192127.33 592.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37200.17 2.83 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4119.33 34.67 0.00 0.00 0.00
ROOM_2_FLR_3 4126.33 27.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4096.17 57.83 0.00 0.00 0.00
ROOM_2_FLR_6 4105.33 48.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108242.50 26.50 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 57.83 0.00 0.00 0.00
Average 288878.04 9.01 0.00 0.00 0.00
Sum 6355316.83 198.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8758.50 1.50 0.00 0.00 0.00
LOBBY_FLR_1 8734.50 25.50 0.00 0.00 0.00
ROOM_1_FLR_3 8584.83 175.17 0.00 0.00 0.00
ROOM_2_FLR_3 8630.50 129.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8746.83 13.17 0.00 0.00 0.00
ROOM_6_FLR_3 8748.50 11.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8541.83 218.17 0.00 0.00 0.00
ROOM_2_FLR_6 8577.33 182.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8738.33 21.67 0.00 0.00 0.00
BANQUET_FLR_6 8726.67 33.33 0.00 0.00 0.00
DINING_FLR_6 8749.67 10.33 0.00 0.00 0.00
KITCHEN_FLR_6 8756.50 3.50 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8541.83 0.00 0.00 0.00 0.00
Max 8760.00 218.17 0.00 0.00 0.00
Average 8722.45 37.55 0.00 0.00 0.00
Sum 191894.00 826.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710225.00 192.00 0.00 0.00 0.00
LOBBY_FLR_1 2105824.00 9605.00 0.00 0.00 0.00
ROOM_1_FLR_3 4082.83 71.17 0.00 0.00 0.00
ROOM_2_FLR_3 4100.33 53.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4153.17 0.83 0.00 0.00 0.00
ROOM_6_FLR_3 4153.50 0.50 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4066.50 87.50 0.00 0.00 0.00
ROOM_2_FLR_6 4074.33 79.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4145.00 9.00 0.00 0.00 0.00
BANQUET_FLR_6 1238377.50 7337.50 0.00 0.00 0.00
DINING_FLR_6 1243492.00 2223.00 0.00 0.00 0.00
KITCHEN_FLR_6 108236.50 32.50 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2105824.00 9605.00 0.00 0.00 0.00
Average 287991.94 895.11 0.00 0.00 0.00
Sum 6335822.67 19692.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:41:37

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.339734E+11 26569.28 22-JAN-21:00 5.00 4.51 0.774642E+10 4837.23 17-JAN-22:10 5.00 4.51
February 0.301128E+11 25942.74 22-FEB-07:24 6.50 6.50 0.690143E+10 4833.80 07-FEB-23:10 6.50 6.50
March 0.323906E+11 25057.81 23-MAR-06:14 7.00 4.89 0.753227E+10 4814.34 30-MAR-21:10 5.92 4.10
April 0.323024E+11 25129.13 19-APR-06:32 6.67 3.53 0.725778E+10 4754.47 13-APR-21:49 6.67 3.53
May 0.333360E+11 26203.50 03-MAY-06:17 6.33 5.23 0.751007E+10 4801.49 03-MAY-21:40 7.10 6.62
June 0.333041E+11 24823.14 06-JUN-23:17 7.33 5.33 0.731952E+10 4797.05 07-JUN-21:10 7.17 6.42
July 0.355826E+11 22470.23 06-JUL-04:14 7.67 6.97 0.769970E+10 4806.84 28-JUL-21:19 12.20 11.48
August 0.362641E+11 20905.28 23-AUG-05:07 9.33 7.24 0.781329E+10 4837.09 18-AUG-22:10 9.33 7.24
September 0.360193E+11 32343.58 30-SEP-20:26 7.50 5.82 0.771998E+10 4848.11 19-SEP-22:10 7.50 5.82
October 0.370881E+11 36021.54 05-OCT-20:07 5.17 4.18 0.802527E+10 4940.26 10-OCT-23:40 6.33 6.33
November 0.357037E+11 35876.33 16-NOV-19:06 6.00 4.61 0.777369E+10 4940.24 16-NOV-23:00 5.00 3.66
December 0.354571E+11 36205.02 19-DEC-21:32 5.33 4.84 0.792977E+10 4904.00 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.411534E+12         0.912292E+11        
Minimum of Months 0.301128E+11 20905.28   5.00 3.53 0.690143E+10 4754.47   5.00 3.53
Maximum of Months 0.370881E+11 36205.02   9.33 7.24 0.802527E+10 4940.26   12.20 11.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.137478E+10 3657.53 15-JAN-15:03 7.83 6.09 0.623498E+09 378.84 17-JAN-22:10 5.05 4.56
February 0.157283E+10 5357.11 04-FEB-14:33 9.00 6.43 0.565431E+09 382.92 27-FEB-22:40 4.33 4.33
March 0.144442E+10 3327.73 31-MAR-15:02 7.33 4.46 0.623540E+09 379.47 30-MAR-21:10 7.33 4.46
April 0.363631E+10 3417.27 30-APR-12:50 22.00 13.22 0.623653E+09 415.03 28-APR-21:30 22.00 13.22
May 0.366868E+10 3077.43 10-MAY-23:07 7.00 6.47 0.638584E+09 416.18 22-MAY-21:30 14.50 12.46
June 0.418692E+10 2792.76 13-JUN-10:33 22.00 15.85 0.624315E+09 425.68 13-JUN-21:30 14.00 12.84
July 0.473617E+10 3336.25 22-JUL-13:30 28.00 16.51 0.656538E+09 433.29 21-JUL-21:30 28.00 16.51
August 0.508092E+10 3370.83 19-AUG-13:10 20.67 15.34 0.668015E+09 435.16 14-AUG-21:30 20.67 15.34
September 0.479993E+10 4201.04 27-SEP-13:20 21.33 13.25 0.643731E+09 433.50 12-SEP-21:30 21.33 13.25
October 0.287175E+10 3812.35 07-OCT-13:10 17.00 9.32 0.635056E+09 409.77 04-OCT-21:30 17.00 9.32
November 0.157509E+10 3889.25 17-NOV-09:57 6.00 3.77 0.603108E+09 378.60 14-NOV-22:49 6.00 3.77
December 0.742829E+09 4129.81 08-DEC-11:00 6.00 4.15 0.621032E+09 376.63 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.356906E+11         0.752650E+10        
Minimum of Months 0.742829E+09 2792.76   6.00 3.77 0.565431E+09 376.63   4.33 3.77
Maximum of Months 0.508092E+10 5357.11   28.00 16.51 0.668015E+09 435.16   28.00 16.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.244120E+10 2137.79 18-JAN-07:14 7.00 6.47 0.796522E+09 549.35 17-JAN-22:10 7.00 6.47
February 0.225159E+10 2158.64 22-FEB-07:24 6.50 6.50 0.726704E+09 536.54 27-FEB-22:40 4.33 4.33
March 0.249007E+10 2091.49 23-MAR-06:14 7.00 4.89 0.810497E+09 544.83 30-MAR-21:10 5.92 4.10
April 0.278936E+10 2155.62 19-APR-06:32 6.67 3.53 0.839898E+09 569.89 13-APR-21:49 6.67 3.53
May 0.289872E+10 2285.04 03-MAY-06:17 6.33 5.23 0.874506E+09 570.61 02-MAY-21:40 6.33 5.23
June 0.297790E+10 2210.83 06-JUN-23:17 7.33 5.33 0.867834E+09 569.55 26-JUN-21:19 14.00 14.00
July 0.317638E+10 1952.68 06-JUL-04:14 7.67 6.97 0.906005E+09 569.55 19-JUL-21:19 14.00 12.84
August 0.322823E+10 1837.90 30-AUG-03:15 9.33 9.14 0.917257E+09 569.55 07-AUG-21:49 9.33 9.14
September 0.302461E+10 2167.59 20-SEP-21:19 8.00 7.29 0.877016E+09 569.55 11-SEP-21:19 8.00 7.29
October 0.272877E+10 2458.40 04-OCT-20:30 6.50 5.98 0.850114E+09 580.27 02-OCT-21:19 6.50 5.98
November 0.242683E+10 1989.14 17-NOV-09:57 6.00 3.77 0.786849E+09 541.07 15-NOV-22:10 6.00 3.77
December 0.232383E+10 1983.20 08-DEC-11:00 6.00 4.15 0.778905E+09 520.62 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.327575E+11         0.100321E+11        
Minimum of Months 0.225159E+10 1837.90   6.00 3.53 0.726704E+09 520.62   4.33 3.53
Maximum of Months 0.322823E+10 2458.40   9.33 9.14 0.917257E+09 580.27   14.00 14.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.110885E+10 1390.83 18-JAN-07:14 7.00 6.47 0.153740E+09 98.28 17-JAN-22:10 7.00 6.47
February 0.108909E+10 1399.89 22-FEB-07:24 6.50 6.50 0.138889E+09 96.99 07-FEB-23:10 6.50 6.50
March 0.138809E+10 1388.48 23-MAR-06:32 7.00 4.62 0.156060E+09 99.38 30-MAR-21:10 5.92 4.10
April 0.172832E+10 1453.01 19-APR-06:32 6.67 3.53 0.161774E+09 109.15 30-APR-23:10 11.87 8.94
May 0.184284E+10 1542.60 03-MAY-06:17 6.33 5.23 0.171216E+09 112.00 23-MAY-21:19 12.00 9.78
June 0.197201E+10 1469.55 06-JUN-23:17 7.33 5.33 0.174841E+09 117.18 13-JUN-21:10 14.00 12.84
July 0.212121E+10 1308.27 06-JUL-04:14 7.67 6.97 0.184740E+09 118.73 24-JUL-21:10 13.83 13.36
August 0.214535E+10 1227.95 30-AUG-05:30 9.50 8.92 0.186206E+09 117.08 18-AUG-21:10 9.50 8.92
September 0.196132E+10 1443.17 28-SEP-04:17 7.33 6.17 0.175060E+09 115.18 13-SEP-21:10 7.33 6.17
October 0.170900E+10 1492.08 15-OCT-08:06 6.33 6.25 0.165251E+09 108.62 02-OCT-21:19 6.33 6.25
November 0.137798E+10 1337.91 03-NOV-08:59 6.00 4.16 0.151347E+09 99.71 15-NOV-22:10 5.67 5.16
December 0.932546E+09 1241.67 19-DEC-22:45 5.00 4.51 0.152673E+09 94.29 22-DEC-22:10 3.83 3.37
                     
Annual Sum or Average 0.193766E+11         0.197180E+10        
Minimum of Months 0.932546E+09 1227.95   5.00 3.53 0.138889E+09 94.29   3.83 3.37
Maximum of Months 0.214535E+10 1542.60   9.50 8.92 0.186206E+09 118.73   14.00 13.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.410164E+09 891.14 18-JAN-07:14 7.00 6.47 0.116878E+09 71.81 17-JAN-22:10 7.00 6.47
February 0.398370E+09 900.87 22-FEB-07:24 6.50 6.50 0.105599E+09 71.45 07-FEB-23:10 6.50 6.50
March 0.617548E+09 856.75 25-MAR-23:43 7.38 6.99 0.117715E+09 72.36 30-MAR-21:10 5.92 4.10
April 0.105368E+10 919.54 19-APR-06:32 6.67 3.53 0.119358E+09 80.76 30-APR-23:10 11.87 8.94
May 0.113910E+10 975.63 03-MAY-06:17 6.33 5.23 0.126160E+09 81.80 23-MAY-21:40 12.00 9.78
June 0.122918E+10 931.25 06-JUN-23:17 7.33 5.33 0.129252E+09 85.78 13-JUN-21:30 14.00 12.84
July 0.132562E+10 830.67 06-JUL-04:14 7.67 6.97 0.136708E+09 86.46 24-JUL-21:40 13.33 13.15
August 0.133969E+10 776.59 05-AUG-04:13 9.00 8.43 0.137676E+09 85.44 18-AUG-21:30 14.50 12.51
September 0.121772E+10 919.41 28-SEP-04:17 7.33 6.17 0.129100E+09 83.88 13-SEP-21:40 7.33 6.17
October 0.100917E+10 945.11 01-OCT-02:45 7.13 6.52 0.121747E+09 78.66 02-OCT-21:19 8.00 6.98
November 0.639702E+09 789.23 10-NOV-06:37 7.33 6.80 0.113595E+09 72.11 08-NOV-22:00 7.33 6.80
December 0.241538E+09 786.46 19-DEC-22:45 5.00 4.51 0.116710E+09 69.42 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.106215E+11         0.147050E+10        
Minimum of Months 0.241538E+09 776.59   5.00 3.53 0.105599E+09 69.42   5.00 4.10
Maximum of Months 0.133969E+10 975.63   9.00 8.43 0.137676E+09 86.46   14.50 13.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.483496E+11 49365.91 30-JAN-20:34 5.67 5.17 0.592457E+09 456.55 25-JAN-22:10 5.67 5.17
February 0.438064E+11 50049.68 01-FEB-20:50 6.00 5.12 0.535592E+09 474.19 07-FEB-23:10 6.83 6.83
March 0.489260E+11 51346.94 29-MAR-20:26 5.50 4.13 0.598215E+09 506.61 30-MAR-21:10 5.92 4.10
April 0.487847E+11 49160.83 19-APR-20:53 6.00 4.60 0.579248E+09 508.96 25-APR-21:00 5.00 4.51
May 0.506001E+11 49395.80 04-MAY-20:54 6.00 6.00 0.600862E+09 496.26 03-MAY-21:30 6.00 6.00
June 0.498089E+11 42680.07 06-JUN-21:08 8.00 6.83 0.579166E+09 460.53 07-JUN-21:10 7.17 6.42
July 0.516473E+11 38450.76 21-JUL-20:00 21.00 15.02 0.597659E+09 391.15 05-JUL-22:49 21.00 15.02
August 0.520461E+11 38338.69 14-AUG-20:00 20.70 12.26 0.598035E+09 384.00 02-AUG-22:40 20.70 12.26
September 0.496743E+11 49354.05 30-SEP-20:26 7.50 5.82 0.580526E+09 423.10 19-SEP-23:30 7.50 5.82
October 0.496954E+11 50269.96 04-OCT-19:49 6.33 5.75 0.601179E+09 490.09 10-OCT-21:00 8.00 8.00
November 0.472355E+11 53828.32 16-NOV-19:27 6.00 4.61 0.579048E+09 506.92 17-NOV-22:10 6.00 5.12
December 0.479222E+11 50676.56 07-DEC-19:37 5.00 4.51 0.591043E+09 490.13 19-DEC-21:40 5.33 4.84
                     
Annual Sum or Average 0.588496E+12         0.703303E+10        
Minimum of Months 0.438064E+11 38338.69   5.00 4.13 0.535592E+09 384.00   5.00 4.10
Maximum of Months 0.520461E+11 53828.32   21.00 15.02 0.601179E+09 508.96   21.00 15.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159469E+11 15087.77 18-JAN-07:14 7.00 6.47 0.869199E+10 6111.82 23-JAN-23:30 7.50 6.96
February 0.152733E+11 21814.35 04-FEB-14:33 9.00 6.43 0.794148E+10 6156.90 27-FEB-22:40 4.33 4.33
March 0.159373E+11 13718.02 25-MAR-23:43 7.38 6.99 0.876839E+10 6171.44 06-MAR-23:00 7.38 6.99
April 0.203430E+11 15582.43 28-APR-00:30 6.75 5.18 0.915655E+10 6348.84 28-APR-21:40 11.33 8.56
May 0.204124E+11 15658.98 11-MAY-04:47 7.17 6.56 0.941248E+10 6522.64 11-MAY-04:40 7.17 6.56
June 0.209156E+11 16086.43 06-JUN-23:17 7.33 5.33 0.930105E+10 6381.57 12-JUN-21:40 16.67 12.64
July 0.225385E+11 14336.30 15-JUL-04:05 8.33 7.78 0.977303E+10 6462.76 21-JUL-22:10 16.83 13.34
August 0.235717E+11 13766.23 30-AUG-03:15 9.33 9.14 0.100137E+11 6462.76 14-AUG-22:10 9.33 9.14
September 0.228884E+11 18480.64 28-SEP-04:40 7.67 6.33 0.964629E+10 6462.78 11-SEP-21:19 7.67 6.33
October 0.190579E+11 16756.67 02-OCT-02:53 9.00 7.01 0.926317E+10 6545.43 10-OCT-23:40 6.33 6.33
November 0.158469E+11 15404.48 17-NOV-09:57 6.00 3.77 0.855370E+10 6245.07 16-NOV-23:00 6.00 3.77
December 0.141929E+11 16294.36 08-DEC-11:00 6.00 4.15 0.851399E+10 5941.56 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.226925E+12         0.109036E+12        
Minimum of Months 0.141929E+11 13718.02   6.00 3.77 0.794148E+10 5941.56   4.33 3.77
Maximum of Months 0.235717E+11 21814.35   9.33 9.14 0.100137E+11 6545.43   16.83 13.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.551272E+11 46429.58 18-JAN-07:14 7.00 6.47 0.281422E+11 19182.60 17-JAN-22:10 7.00 6.47
February 0.507670E+11 47000.91 22-FEB-07:24 6.50 6.50 0.256432E+11 19079.11 07-FEB-23:10 6.50 6.50
March 0.557913E+11 44928.24 23-MAR-06:14 7.00 4.89 0.285631E+11 19119.76 30-MAR-21:10 5.92 4.10
April 0.617739E+11 56462.66 22-APR-00:15 7.03 6.02 0.292581E+11 19364.77 25-APR-21:00 5.00 4.51
May 0.638092E+11 65440.67 01-MAY-02:26 7.15 6.39 0.303592E+11 19864.46 11-MAY-04:40 7.33 6.64
June 0.650387E+11 57953.60 22-JUN-06:00 10.00 10.00 0.299786E+11 19351.03 02-JUN-00:00 10.00 10.00
July 0.692302E+11 52167.04 15-JUL-04:05 8.33 7.78 0.312125E+11 19366.32 26-JUL-23:19 11.00 10.27
August 0.707407E+11 51643.48 20-AUG-03:55 9.00 7.94 0.316319E+11 19352.72 30-AUG-03:20 9.33 9.14
September 0.670776E+11 54522.06 30-SEP-23:05 7.68 5.79 0.304220E+11 19449.99 27-SEP-01:30 7.68 5.79
October 0.609961E+11 58925.07 01-OCT-03:47 7.02 6.10 0.298255E+11 19835.90 10-OCT-23:40 6.33 6.33
November 0.545760E+11 43482.32 17-NOV-09:57 6.00 3.77 0.277738E+11 19169.78 16-NOV-23:00 6.00 3.77
December 0.528328E+11 43803.14 08-DEC-11:00 6.00 4.15 0.275762E+11 18574.85 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.727761E+12         0.350386E+12        
Minimum of Months 0.507670E+11 43482.32   6.00 3.77 0.256432E+11 18574.85   5.00 3.77
Maximum of Months 0.707407E+11 65440.67   10.00 10.00 0.316319E+11 19864.46   11.00 10.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 72621531.68 2751.12 25-JAN-16:01 9.00 8.43 93906170.80 56.69 13-JAN-22:30 9.00 8.43
February 0.120589E+09 3543.01 18-FEB-16:01 5.83 4.00 85446487.26 56.69 01-FEB-04:40 5.83 4.00
March 0.102485E+09 3416.70 20-MAR-18:01 7.83 5.10 94492282.35 56.69 09-MAR-22:19 7.83 5.10
April 0.753238E+09 3726.28 28-APR-19:01 13.83 10.09 95791900.99 80.36 28-APR-18:10 13.83 10.09
May 0.885482E+09 4101.94 25-MAY-17:02 14.17 12.32 0.100237E+09 90.18 22-MAY-21:10 14.17 12.32
June 0.125136E+10 4140.93 22-JUN-19:01 13.67 11.71 99848635.71 89.35 21-JUN-21:10 13.67 11.71
July 0.142337E+10 4039.38 14-JUL-18:01 14.42 11.60 0.108195E+09 90.62 12-JUL-21:10 14.42 11.60
August 0.135696E+10 4065.70 01-AUG-19:31 14.33 11.35 0.108300E+09 87.30 17-AUG-21:10 14.83 13.13
September 0.106884E+10 4215.47 29-SEP-16:01 13.83 8.60 99514697.01 82.59 11-SEP-21:10 13.83 8.60
October 0.330931E+09 3818.01 05-OCT-17:12 13.67 7.89 96080785.22 56.69 05-OCT-21:40 5.33 4.26
November 79620270.27 3559.28 03-NOV-15:01 8.83 5.57 91173358.24 56.69 07-NOV-00:10 8.00 8.00
December 45555775.13 435.82 21-DEC-16:04 6.83 6.31 92984247.59 56.69 04-DEC-22:10 6.83 6.31
                     
Annual Sum or Average 0.749106E+10         0.116597E+10        
Minimum of Months 45555775.13 435.82   5.83 4.00 85446487.26 56.69   5.33 4.00
Maximum of Months 0.142337E+10 4215.47   14.42 12.32 0.108300E+09 90.62   14.83 13.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 48332891.05 1029.36 19-JAN-16:02 7.67 7.22 93050704.40 56.69 13-JAN-22:30 7.67 7.22
February 70591373.82 2605.67 19-FEB-16:02 5.17 4.17 84461992.15 56.69 01-FEB-04:40 5.17 4.17
March 82536011.58 3017.84 20-MAR-18:01 7.83 5.10 94045952.48 56.69 03-MAR-22:10 7.83 5.10
April 0.506705E+09 3559.71 20-APR-18:01 13.67 8.59 94774009.15 76.15 28-APR-18:10 15.67 10.95
May 0.714669E+09 3642.14 25-MAY-17:21 14.50 12.46 99528190.64 87.60 22-MAY-21:10 14.50 12.46
June 0.112198E+10 3760.83 22-JUN-19:01 13.67 11.71 99388888.10 89.24 26-JUN-21:10 14.00 14.00
July 0.124388E+10 3659.35 28-JUL-18:11 13.67 12.72 0.107331E+09 89.03 12-JUL-21:10 13.67 12.72
August 0.105502E+10 3645.84 01-AUG-19:31 14.33 11.35 0.106546E+09 83.20 17-AUG-21:10 14.83 13.13
September 0.673685E+09 3590.25 29-SEP-16:01 13.83 8.60 97601969.75 76.73 11-SEP-21:10 13.83 8.60
October 0.174610E+09 3235.33 07-OCT-15:02 18.83 10.03 95064012.37 56.69 01-OCT-01:30 18.83 10.03
November 57926946.37 1375.76 10-NOV-16:01 10.33 8.12 90398758.99 56.69 18-NOV-01:39 6.67 5.10
December 31787319.11 103.13 02-DEC-08:61 6.17 5.65 92503068.98 56.69 04-DEC-23:49 7.00 7.00
                     
Annual Sum or Average 0.578173E+10         0.115469E+10        
Minimum of Months 31787319.11 103.13   5.17 4.17 84461992.15 56.69   5.17 4.17
Maximum of Months 0.124388E+10 3760.83   18.83 12.72 0.107331E+09 89.24   18.83 14.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.185751E+09 389.20 21-JAN-11:30 6.00 5.05 0.00 0.00 01-JAN-00:10 6.00 5.05
February 0.178191E+09 308.20 04-FEB-14:21 9.00 6.35 0.00 0.00 01-FEB-00:10 9.00 6.35
March 0.153970E+09 87.51 25-MAR-11:50 11.92 8.82 0.00 0.00 01-MAR-00:10 11.92 8.82
April 0.429759E+09 640.72 30-APR-12:50 22.00 13.22 0.00 0.00 01-APR-00:10 22.00 13.22
May 0.381828E+09 487.32 23-MAY-13:20 18.33 14.52 0.00 0.00 01-MAY-00:10 18.33 14.52
June 0.430545E+09 513.60 13-JUN-13:20 24.37 17.19 0.00 0.00 01-JUN-00:10 24.37 17.19
July 0.511167E+09 592.79 22-JUL-13:30 28.00 16.51 0.00 0.00 01-JUL-00:10 28.00 16.51
August 0.591561E+09 631.58 20-AUG-13:00 23.00 14.82 0.00 0.00 01-AUG-00:10 23.00 14.82
September 0.643546E+09 773.89 27-SEP-13:20 21.33 13.25 0.00 0.00 01-SEP-00:10 21.33 13.25
October 0.355606E+09 699.70 07-OCT-13:10 17.00 9.32 0.00 0.00 01-OCT-00:10 17.00 9.32
November 0.183166E+09 330.91 11-NOV-13:30 9.00 7.22 0.00 0.00 01-NOV-00:10 9.00 7.22
December 89761980.92 101.10 18-DEC-14:30 8.00 5.66 0.00 0.00 01-DEC-00:10 8.00 5.66
                     
Annual Sum or Average 0.413485E+10         0.00        
Minimum of Months 89761980.92 87.51   6.00 5.05 0.00 0.00   6.00 5.05
Maximum of Months 0.643546E+09 773.89   28.00 17.19 0.00 0.00   28.00 17.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 95021071.54 815.11 29-JAN-09:01 11.00 8.46 94420745.40 56.69 06-JAN-22:10 11.00 8.46
February 86452043.25 355.47 01-FEB-19:03 6.00 5.92 85456059.83 56.69 02-FEB-22:19 6.00 5.05
March 0.167997E+09 879.86 20-MAR-18:01 7.83 5.10 95307151.20 56.69 16-MAR-21:10 7.83 5.10
April 0.323911E+09 944.46 20-APR-18:01 13.67 8.59 93386147.22 59.83 27-APR-20:10 11.50 8.67
May 0.411606E+09 977.97 11-MAY-19:31 13.67 8.80 97102231.33 72.74 22-MAY-21:19 14.67 12.52
June 0.535432E+09 982.27 22-JUN-19:01 13.67 11.71 95372188.78 76.77 26-JUN-21:10 14.00 14.00
July 0.566184E+09 1031.43 22-JUL-08:41 24.00 16.56 99961790.13 74.38 10-JUL-21:40 24.00 16.56
August 0.503571E+09 966.07 03-AUG-19:31 13.67 11.76 99826997.61 73.04 17-AUG-21:10 14.83 13.13
September 0.400217E+09 933.41 13-SEP-19:31 15.00 12.66 94177310.77 71.11 11-SEP-21:10 15.00 12.66
October 0.233121E+09 882.60 05-OCT-18:01 10.33 6.62 95528416.09 56.84 30-OCT-22:19 5.67 5.67
November 0.125637E+09 749.70 25-NOV-09:01 7.17 5.17 91747417.99 56.69 08-NOV-22:10 7.17 5.17
December 72340243.74 389.31 24-DEC-09:02 7.00 5.53 94144752.36 56.69 04-DEC-22:10 7.00 5.53
                     
Annual Sum or Average 0.352149E+10         0.113643E+10        
Minimum of Months 72340243.74 355.47   6.00 5.10 85456059.83 56.69   5.67 5.05
Maximum of Months 0.566184E+09 1031.43   24.00 16.56 99961790.13 76.77   24.00 16.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 87455224.17 1097.62 21-JAN-16:02 5.75 4.88 93866780.19 56.69 26-JAN-22:10 4.00 3.53
February 0.106469E+09 2992.01 04-FEB-16:01 7.00 5.54 85338130.43 56.69 01-FEB-04:40 7.00 5.54
March 99067969.54 1760.49 20-MAR-15:01 10.83 7.32 94552836.19 56.69 25-MAR-23:30 7.55 7.13
April 0.857666E+09 3691.65 28-APR-08:51 16.00 11.54 95708378.37 65.44 27-APR-20:10 16.00 11.54
May 0.907948E+09 3808.63 23-MAY-08:51 19.00 14.78 99345380.07 77.81 22-MAY-21:10 19.00 14.78
June 0.119056E+10 3804.68 12-JUN-08:51 19.00 14.27 97991638.58 80.13 26-JUN-21:10 14.00 14.00
July 0.140504E+10 4054.26 22-JUL-08:22 24.00 16.56 0.103906E+09 79.56 10-JUL-21:40 24.00 16.56
August 0.147139E+10 3886.76 14-AUG-08:51 21.00 15.45 0.104807E+09 78.66 21-AUG-21:10 14.17 12.31
September 0.122131E+10 3887.20 13-SEP-08:51 19.00 15.28 98190600.85 78.05 11-SEP-21:10 19.00 15.28
October 0.356495E+09 3284.58 07-OCT-15:02 18.83 10.03 96144262.23 56.69 07-OCT-23:10 10.83 9.32
November 89595794.20 3011.64 03-NOV-15:01 8.83 5.57 91145507.71 56.69 14-NOV-04:30 8.00 8.00
December 54456248.40 348.12 11-DEC-09:05 3.50 2.91 93052340.72 56.69 04-DEC-23:49 3.50 2.91
                     
Annual Sum or Average 0.784745E+10         0.115405E+10        
Minimum of Months 54456248.40 348.12   3.50 2.91 85338130.43 56.69   3.50 2.91
Maximum of Months 0.147139E+10 4054.26   24.00 16.56 0.104807E+09 80.13   24.00 16.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 48763452.95 583.79 21-JAN-09:04 3.35 3.02 93044490.53 56.69 13-JAN-22:30 3.35 3.02
February 61856111.92 1426.85 20-FEB-09:02 3.33 2.81 84334937.95 56.69 01-FEB-04:40 3.33 2.81
March 76706667.93 632.30 30-MAR-18:03 7.00 4.68 94112852.04 56.69 25-MAR-23:30 7.00 4.68
April 0.586804E+09 3337.70 28-APR-08:51 16.00 11.54 94920248.67 61.97 27-APR-20:10 16.00 11.54
May 0.727229E+09 3488.75 23-MAY-08:51 19.00 14.78 98846763.65 75.76 22-MAY-21:10 19.00 14.78
June 0.105309E+10 3537.54 13-JUN-08:32 21.40 15.97 97700437.03 79.10 26-JUN-21:10 14.00 14.00
July 0.121335E+10 3721.19 22-JUL-08:22 24.00 16.56 0.103395E+09 78.19 10-JUL-21:40 24.00 16.56
August 0.114944E+10 3577.11 14-AUG-08:51 21.00 15.45 0.103743E+09 75.37 17-AUG-21:10 14.83 13.13
September 0.791618E+09 3441.20 23-SEP-08:51 17.00 13.96 96927294.97 73.06 11-SEP-21:10 17.00 13.96
October 0.191170E+09 2810.97 07-OCT-15:02 18.83 10.03 95161592.74 56.69 02-OCT-03:20 18.83 10.03
November 58947512.53 681.38 25-NOV-09:02 7.17 5.17 90371523.94 56.69 22-NOV-05:40 7.17 5.17
December 33133487.39 313.77 02-DEC-09:06 7.00 6.47 92573273.48 56.69 04-DEC-23:49 7.00 7.00
                     
Annual Sum or Average 0.599211E+10         0.114513E+10        
Minimum of Months 33133487.39 313.77   3.33 2.81 84334937.95 56.69   3.33 2.81
Maximum of Months 0.121335E+10 3721.19   24.00 16.56 0.103743E+09 79.10   24.00 16.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213696E+10 2857.08 20-JAN-15:46 7.17 6.09 0.120060E+10 735.15 17-JAN-22:10 7.17 6.09
February 0.222854E+10 3119.50 13-FEB-15:08 6.00 3.74 0.108605E+10 733.52 27-FEB-22:40 4.33 4.33
March 0.258473E+10 2758.61 25-MAR-23:16 7.63 7.20 0.120909E+10 736.89 30-MAR-21:10 5.92 4.10
April 0.403556E+10 3396.79 19-APR-06:32 6.67 3.53 0.125077E+10 853.46 30-APR-23:19 11.63 8.77
May 0.434984E+10 3660.14 03-MAY-06:17 6.33 5.23 0.132831E+10 862.46 23-MAY-21:30 12.00 9.78
June 0.461368E+10 3470.01 06-JUN-23:17 7.33 5.33 0.134694E+10 899.16 26-JUN-21:19 14.00 14.00
July 0.499311E+10 3088.92 06-JUL-04:14 7.67 6.97 0.142910E+10 916.85 24-JUL-21:30 13.50 13.22
August 0.508241E+10 2940.92 05-AUG-04:13 9.00 8.43 0.144644E+10 903.61 21-AUG-21:19 14.33 12.38
September 0.461566E+10 3474.73 28-SEP-04:17 7.33 6.17 0.135295E+10 883.49 13-SEP-21:40 7.33 6.17
October 0.353510E+10 3545.28 01-OCT-02:45 7.13 6.52 0.125557E+10 827.25 02-OCT-21:19 8.00 6.98
November 0.236034E+10 2880.05 10-NOV-06:37 7.33 6.80 0.116369E+10 731.29 14-NOV-00:30 8.00 8.00
December 0.152619E+10 2907.90 19-DEC-22:45 5.00 4.51 0.119905E+10 718.05 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.420621E+11         0.152686E+11        
Minimum of Months 0.152619E+10 2758.61   5.00 3.53 0.108605E+10 718.05   4.33 4.10
Maximum of Months 0.508241E+10 3660.14   9.00 8.43 0.144644E+10 916.85   14.33 14.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 58682325.90 2872.02 25-JAN-16:01 9.00 8.43 93461722.90 56.69 13-JAN-22:30 9.00 8.43
February 0.114190E+09 3712.37 09-FEB-16:01 7.67 5.50 85044279.31 56.69 01-FEB-04:40 7.67 5.50
March 93078086.32 3634.15 20-MAR-18:01 7.83 5.10 94104345.79 56.69 06-MAR-23:10 7.83 5.10
April 0.785535E+09 4117.00 28-APR-18:42 14.33 10.41 95990658.51 89.75 28-APR-18:10 14.33 10.41
May 0.897089E+09 4373.67 23-MAY-19:42 14.33 10.77 0.100662E+09 99.45 22-MAY-21:10 14.33 10.77
June 0.127509E+10 4539.78 22-JUN-18:42 14.33 11.96 0.100567E+09 95.59 26-JUN-20:10 15.67 14.65
July 0.149134E+10 4611.07 11-JUL-18:52 14.00 12.24 0.109856E+09 98.53 10-JUL-21:10 14.00 12.24
August 0.137849E+10 4333.70 01-AUG-19:12 14.67 11.47 0.109735E+09 90.50 02-AUG-21:10 14.67 12.54
September 0.101650E+10 4442.99 29-SEP-16:01 13.83 8.60 0.100200E+09 87.61 11-SEP-21:10 13.83 8.60
October 0.296690E+09 4088.51 05-OCT-17:12 13.67 7.89 95753875.91 56.69 05-OCT-21:19 5.67 4.44
November 67880334.45 3708.19 03-NOV-15:01 8.83 5.57 90719357.85 56.69 22-NOV-05:40 7.67 7.31
December 31844873.96 484.32 21-DEC-16:04 6.83 6.31 92643617.55 56.69 04-DEC-23:49 6.83 6.31
                     
Annual Sum or Average 0.750642E+10         0.116874E+10        
Minimum of Months 31844873.96 484.32   6.83 5.10 85044279.31 56.69   5.67 4.44
Maximum of Months 0.149134E+10 4611.07   14.67 12.24 0.109856E+09 99.45   15.67 14.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 32299025.60 687.62 15-JAN-16:03 6.67 5.70 92689386.86 56.69 06-JAN-22:10 6.67 5.70
February 54817994.36 2495.52 27-FEB-16:02 8.00 6.56 84043854.50 56.69 02-FEB-22:19 8.00 6.56
March 72446291.76 3172.36 20-MAR-18:01 7.83 5.10 93631075.27 56.69 16-MAR-21:10 7.83 5.10
April 0.520535E+09 3638.15 28-APR-18:42 14.33 10.41 94969088.02 84.51 28-APR-18:10 14.33 10.41
May 0.711256E+09 3963.14 23-MAY-19:42 14.33 10.77 99933905.47 96.63 22-MAY-21:10 14.33 10.77
June 0.112646E+10 4110.29 22-JUN-18:42 14.33 11.96 0.100147E+09 94.63 26-JUN-20:10 15.67 14.65
July 0.128878E+10 4181.12 11-JUL-18:52 14.00 12.24 0.108973E+09 96.78 10-JUL-21:10 14.00 12.24
August 0.103814E+10 3914.29 01-AUG-19:12 14.67 11.47 0.107876E+09 89.33 17-AUG-21:10 14.83 13.13
September 0.592241E+09 3758.22 14-SEP-18:01 14.00 12.84 98012858.61 79.99 11-SEP-21:10 14.00 12.84
October 0.147355E+09 3362.02 07-OCT-15:02 18.83 10.03 94641500.19 56.69 21-OCT-03:30 7.50 4.96
November 41994326.73 905.93 03-NOV-15:02 8.83 5.57 89963175.92 56.69 22-NOV-05:40 7.67 7.31
December 14856640.80 102.47 02-DEC-08:61 6.17 5.65 92306756.01 56.69 04-DEC-22:00 7.00 7.00
                     
Annual Sum or Average 0.564118E+10         0.115719E+10        
Minimum of Months 14856640.80 102.47   6.17 5.10 84043854.50 56.69   6.67 4.96
Maximum of Months 0.128878E+10 4181.12   18.83 12.84 0.108973E+09 96.78   15.67 14.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.197904E+09 2303.61 11-JAN-16:01 -2.2 -4.4 95411477.07 56.69 06-JAN-22:10 -2.2 -4.4
February 0.231188E+09 2388.22 24-FEB-16:01 6.00 4.60 86642743.88 56.69 02-FEB-22:19 6.00 4.60
March 0.121162E+09 2307.17 20-MAR-15:01 10.83 7.32 95400255.02 56.69 03-MAR-22:10 10.83 7.32
April 0.694751E+09 2395.11 07-APR-15:01 8.83 5.31 95814912.21 71.86 27-APR-20:10 11.50 8.67
May 0.596177E+09 2536.95 11-MAY-19:31 13.67 8.80 99178130.69 81.42 22-MAY-21:19 14.67 12.52
June 0.734410E+09 2462.45 22-JUN-19:01 13.67 11.71 97576433.67 81.95 21-JUN-21:10 13.67 11.71
July 0.880271E+09 2480.63 06-JUL-20:31 14.33 12.22 0.103688E+09 81.19 10-JUL-21:40 17.00 13.49
August 0.101592E+10 2532.34 20-AUG-20:11 15.00 12.49 0.105306E+09 84.12 21-AUG-21:10 14.17 12.31
September 0.104651E+10 2689.89 29-SEP-16:01 13.83 8.60 99621366.39 90.27 11-SEP-21:10 13.83 8.60
October 0.471543E+09 2527.46 07-OCT-17:32 12.33 8.70 97003322.66 56.69 07-OCT-23:19 10.67 9.24
November 0.173225E+09 2403.58 03-NOV-15:01 8.83 5.57 92460536.59 56.69 22-NOV-05:40 7.67 7.31
December 87109866.62 2140.22 18-DEC-16:02 5.17 3.90 94286355.99 56.69 04-DEC-22:10 5.17 3.90
                     
Annual Sum or Average 0.625018E+10         0.116239E+10        
Minimum of Months 87109866.62 2140.22   -2.2 -4.4 86642743.88 56.69   -2.2 -4.4
Maximum of Months 0.104651E+10 2689.89   15.00 12.49 0.105306E+09 90.27   17.00 13.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.313625E+11 30898.35 29-JAN-23:23 6.85 6.25 0.189534E+11 12279.01 19-JAN-01:49 6.85 6.25
February 0.286947E+11 29604.61 07-FEB-22:10 7.00 7.00 0.171701E+11 12272.67 07-FEB-23:10 6.83 6.83
March 0.329906E+11 30948.68 29-MAR-20:26 5.50 4.13 0.191883E+11 12749.99 06-MAR-23:00 5.50 4.13
April 0.348331E+11 35555.94 26-APR-22:18 6.67 6.14 0.186341E+11 12548.94 25-APR-21:00 6.67 6.14
May 0.368385E+11 32374.13 11-MAY-04:32 7.33 6.64 0.193016E+11 13245.10 11-MAY-04:40 7.33 6.64
June 0.379365E+11 30684.95 07-JUN-24:00 7.00 5.15 0.187370E+11 12445.66 07-JUN-23:49 7.00 5.15
July 0.399433E+11 31299.01 06-JUL-04:20 7.67 6.97 0.192886E+11 12190.96 15-JUL-03:49 8.45 7.89
August 0.396126E+11 30213.97 30-AUG-03:30 9.50 9.21 0.193536E+11 12225.57 30-AUG-03:20 9.50 9.21
September 0.363170E+11 30553.42 20-SEP-22:47 7.17 6.56 0.186551E+11 12310.24 30-SEP-04:19 8.33 5.96
October 0.341647E+11 33922.07 04-OCT-22:30 6.00 5.49 0.191617E+11 13049.21 10-OCT-23:40 6.33 6.33
November 0.313368E+11 31599.94 14-NOV-04:41 8.00 8.00 0.184147E+11 12630.63 16-NOV-23:00 5.00 3.66
December 0.309372E+11 31055.34 04-DEC-23:37 7.00 7.00 0.189149E+11 12263.70 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.414967E+12         0.225773E+12        
Minimum of Months 0.286947E+11 29604.61   5.50 4.13 0.171701E+11 12190.96   5.00 3.66
Maximum of Months 0.399433E+11 35555.94   9.50 9.21 0.193536E+11 13245.10   9.50 9.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.351894E+11 32579.08 29-JAN-23:23 6.85 6.25 0.191357E+11 12336.18 19-JAN-01:49 6.85 6.25
February 0.321573E+11 31492.73 07-FEB-22:37 7.00 7.00 0.173333E+11 12400.37 27-FEB-22:40 4.33 4.33
March 0.370114E+11 32558.20 29-MAR-20:26 5.50 4.13 0.193286E+11 12830.32 06-MAR-23:00 5.50 4.13
April 0.385655E+11 38325.52 26-APR-22:18 6.67 6.14 0.187121E+11 12991.17 25-APR-21:00 6.67 6.14
May 0.406386E+11 33958.47 11-MAY-04:32 7.33 6.64 0.193671E+11 13320.65 11-MAY-04:40 7.33 6.64
June 0.414412E+11 33156.54 07-JUN-24:00 7.00 5.15 0.187700E+11 12519.02 07-JUN-23:49 7.00 5.15
July 0.434336E+11 32908.03 06-JUL-04:20 7.67 6.97 0.193131E+11 12239.62 15-JUL-03:49 8.45 7.89
August 0.430572E+11 31724.17 30-AUG-03:30 9.50 9.21 0.193823E+11 12276.30 30-AUG-03:20 9.50 9.21
September 0.397622E+11 32151.83 08-SEP-03:53 7.00 6.47 0.187049E+11 12359.45 30-SEP-04:19 8.33 5.96
October 0.380702E+11 36750.32 04-OCT-22:30 6.00 5.49 0.192789E+11 13164.91 10-OCT-23:40 6.33 6.33
November 0.351129E+11 33207.93 14-NOV-04:41 8.00 8.00 0.185769E+11 12713.48 16-NOV-23:00 5.00 3.66
December 0.347323E+11 32624.32 04-DEC-23:37 7.00 7.00 0.191181E+11 12390.13 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.459172E+12         0.227021E+12        
Minimum of Months 0.321573E+11 31492.73   5.50 4.13 0.173333E+11 12239.62   4.33 3.66
Maximum of Months 0.434336E+11 38325.52   9.50 9.21 0.193823E+11 13320.65   9.50 9.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.493077E+11 37344.33 30-JAN-16:58 7.00 6.47 0.188307E+11 11435.79 20-JAN-17:10 7.00 6.47
February 0.449625E+11 36607.63 12-FEB-11:31 6.00 3.75 0.170096E+11 11507.19 11-FEB-18:10 6.00 3.75
March 0.504362E+11 38026.91 23-MAR-06:32 7.00 4.62 0.188527E+11 11491.68 04-MAR-18:49 7.00 4.62
April 0.521120E+11 37377.27 12-APR-08:41 7.00 4.34 0.182464E+11 11373.93 08-APR-17:19 7.00 4.34
May 0.541417E+11 35451.74 10-MAY-06:36 7.33 5.17 0.188604E+11 11351.79 13-MAY-17:19 11.33 9.41
June 0.538885E+11 33548.49 07-JUN-09:26 8.50 7.05 0.182486E+11 11319.68 10-JUN-17:19 13.67 11.59
July 0.562783E+11 32226.12 05-JUL-06:00 9.00 7.94 0.188529E+11 11319.65 22-JUL-17:19 29.33 16.65
August 0.563395E+11 32205.62 30-AUG-06:07 9.50 8.94 0.188586E+11 11319.52 26-AUG-17:19 9.50 8.94
September 0.533183E+11 35936.45 21-SEP-06:54 7.00 6.47 0.182458E+11 11326.20 30-SEP-17:00 11.00 8.39
October 0.517357E+11 37008.16 31-OCT-06:10 6.83 6.83 0.188557E+11 11442.28 28-OCT-17:19 6.83 6.83
November 0.482303E+11 38420.58 16-NOV-19:27 6.00 4.61 0.182363E+11 11407.04 01-NOV-15:30 6.00 4.61
December 0.486110E+11 40479.17 08-DEC-11:00 6.00 4.15 0.188263E+11 11610.42 02-DEC-18:40 6.00 4.15
                     
Annual Sum or Average 0.619362E+12         0.221924E+12        
Minimum of Months 0.449625E+11 32205.62   6.00 3.75 0.170096E+11 11319.52   6.00 3.75
Maximum of Months 0.563395E+11 40479.17   9.50 8.94 0.188604E+11 11610.42   29.33 16.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.398409E+10 5983.21 20-JAN-15:46 7.17 6.09 0.127122E+10 780.99 17-JAN-22:10 7.17 6.09
February 0.426684E+10 6601.13 13-FEB-15:08 6.00 3.74 0.115052E+10 780.96 27-FEB-22:40 4.33 4.33
March 0.539631E+10 6017.49 11-MAR-16:03 6.67 3.64 0.128034E+10 788.40 30-MAR-21:10 5.92 4.10
April 0.816940E+10 6739.34 28-APR-00:13 6.80 5.27 0.131797E+10 899.29 30-APR-23:19 11.63 8.77
May 0.879494E+10 7106.47 03-MAY-06:17 6.33 5.23 0.138586E+10 911.09 23-MAY-21:30 12.00 9.78
June 0.944038E+10 6922.40 06-JUN-23:17 7.33 5.33 0.141245E+10 950.43 13-JUN-21:30 14.00 12.84
July 0.101567E+11 6105.84 06-JUL-04:14 7.67 6.97 0.149108E+10 952.94 21-JUL-21:30 17.00 13.72
August 0.101977E+11 5716.12 30-AUG-03:15 9.33 9.14 0.149413E+10 932.30 14-AUG-21:30 9.33 9.14
September 0.916808E+10 6733.40 28-SEP-04:17 7.33 6.17 0.138890E+10 912.05 12-SEP-21:40 7.33 6.17
October 0.709085E+10 6858.21 01-OCT-02:20 7.23 6.39 0.130810E+10 846.25 02-OCT-21:19 8.00 6.98
November 0.485667E+10 5809.86 18-NOV-01:44 6.33 4.85 0.123161E+10 776.85 14-NOV-00:30 6.33 4.85
December 0.301909E+10 5417.79 17-DEC-13:28 7.00 5.16 0.126942E+10 762.88 19-DEC-22:49 5.00 4.51
                     
Annual Sum or Average 0.845411E+11         0.160016E+11        
Minimum of Months 0.301909E+10 5417.79   6.00 3.64 0.115052E+10 762.88   4.33 4.10
Maximum of Months 0.101977E+11 7106.47   9.33 9.14 0.149413E+10 952.94   17.00 13.72



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.102518E+09 790.25 26-JAN-09:05 6.00
February 41901938.33 773.95 27-FEB-07:46 6.00
March 25779922.95 773.15 20-MAR-06:30 6.00
April 4696674.87 623.64 11-APR-07:48 7.00
May 9546928.17 523.81 04-MAY-05:54 7.00
June 4321378.85 336.76 06-JUN-05:10 8.42
July 5146829.94 386.30 02-JUL-02:38 9.00
August 739584.72 388.93 30-AUG-03:29 9.50
September 8750879.13 392.15 04-SEP-01:56 9.00
October 10570208.10 794.27 24-OCT-06:30 6.00
November 38919486.48 733.84 14-NOV-04:43 8.00
December 0.233929E+09 698.41 05-DEC-09:07 7.00
         
Annual Sum or Average 0.486821E+09      
Minimum of Months 739584.72 336.76   6.00
Maximum of Months 0.233929E+09 794.27   9.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 322118.96 81.83 14-JAN-15:17 7.00
February 169050.99 84.90 01-FEB-16:06 7.00
March 354853.25 94.21 05-MAR-13:45 7.00
April 9673.92 38.06 10-APR-14:45 7.00
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 72142.94 41.82 12-NOV-15:55 7.00
December 485991.34 101.45 13-DEC-11:20 7.07
         
Annual Sum or Average 1413831.40      
Minimum of Months 0.00 0.00   7.00
Maximum of Months 485991.34 101.45   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5604435.18 158.56 12-JAN-15:00 -1.0
February 1441364.51 127.43 27-FEB-15:41 8.00
March 1747651.60 106.76 09-MAR-06:17 7.30
April 258767.82 75.15 02-APR-08:13 7.67
May 298830.71 65.82 19-MAY-05:03 9.00
June 5332.71 10.58 06-JUN-05:10 8.42
July 676.56 3.13 02-JUL-02:23 9.00
August 0.00 0.00 01-AUG-00:05 11.43
September 7878.85 16.96 07-SEP-05:10 8.83
October 885697.47 82.35 25-OCT-03:59 8.00
November 2423941.08 112.71 22-NOV-06:42 8.00
December 3549636.81 109.79 24-DEC-05:27 7.50
         
Annual Sum or Average 16224213.31      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 5604435.18 158.56   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 44800995.96 218.18 12-JAN-15:00 -1.0
February 4916853.73 110.17 27-FEB-08:28 6.00
March 2351797.81 80.38 18-MAR-06:16 9.00
April 619302.96 69.64 02-APR-08:13 7.67
May 772846.05 68.57 19-MAY-05:03 9.00
June 147107.64 30.77 06-JUN-05:10 8.42
July 141795.94 29.95 02-JUL-02:23 9.00
August 671.37 10.07 30-AUG-03:29 9.50
September 267586.21 40.95 07-SEP-05:10 8.83
October 1612131.48 78.97 16-OCT-23:25 9.00
November 6670263.58 104.88 29-NOV-16:00 4.00
December 40218404.26 189.49 30-DEC-17:00 1.00
         
Annual Sum or Average 0.102520E+09      
Minimum of Months 671.37 10.07   -1.0
Maximum of Months 44800995.96 218.18   9.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 119088.94 489.93 01-FEB-04:33 7.67
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 63318.91 575.30 30-MAY-03:44 8.00
June 42132.69 455.53 06-JUN-03:39 8.33
July 0.00 0.00 01-JUL-00:10 11.00
August 22513.62 291.51 23-AUG-04:00 8.00
September 0.00 0.00 01-SEP-00:05 12.43
October 51103.49 495.84 25-OCT-03:59 8.00
November 73960.86 575.51 14-NOV-04:18 8.00
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 372118.52      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 119088.94 575.51   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5985475.96 1134.22 28-JAN-09:38 7.70
February 4996202.25 1075.14 01-FEB-09:04 7.00
March 7785447.19 1069.81 22-MAR-08:57 7.00
April 2828247.64 898.49 06-APR-07:34 6.93
May 1287612.21 1088.81 04-MAY-06:36 8.33
June 70584.25 481.85 08-JUN-06:19 8.00
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 200821.13 689.14 17-SEP-05:32 8.67
October 3101019.24 985.88 26-OCT-06:57 8.00
November 6254024.76 1075.99 08-NOV-07:29 6.50
December 6601483.71 995.12 02-DEC-09:23 7.00
         
Annual Sum or Average 39110918.36      
Minimum of Months 0.00 0.00   6.50
Maximum of Months 7785447.19 1134.22   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3447391.63 1116.01 30-JAN-10:05 6.33
February 1713067.92 1279.05 26-FEB-16:45 7.00
March 4244503.33 1709.19 05-MAR-13:45 7.00
April 183775.38 608.33 10-APR-14:45 7.00
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 415783.77 793.41 12-NOV-15:55 7.00
December 4788053.70 2027.51 13-DEC-11:20 7.07
         
Annual Sum or Average 14792575.73      
Minimum of Months 0.00 0.00   6.33
Maximum of Months 4788053.70 2027.51   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.774502E+09 1368.84 31-JAN-19:01 6.00
February 0.566994E+09 1378.03 01-FEB-19:01 6.00
March 0.526713E+09 1346.81 08-MAR-19:01 5.83
April 88916213.84 1301.89 11-APR-08:61 7.17
May 52107404.71 1243.78 05-MAY-08:62 8.17
June 3150954.11 928.71 18-JUN-08:03 13.17
July 3424711.25 1110.36 19-JUL-08:53 17.00
August 1423258.49 1080.47 27-AUG-08:53 16.00
September 8058357.60 925.51 22-SEP-08:53 18.00
October 0.238469E+09 1362.34 19-OCT-15:01 9.00
November 0.596145E+09 1382.38 30-NOV-19:01 4.83
December 0.106374E+10 1385.58 23-DEC-16:01 8.83
         
Annual Sum or Average 0.392364E+10      
Minimum of Months 1423258.49 925.51   4.83
Maximum of Months 0.106374E+10 1385.58   18.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.986418E+09 1344.76 14-JAN-19:01 5.83
February 0.739087E+09 1352.62 01-FEB-19:01 6.00
March 0.608542E+09 1327.22 08-MAR-19:01 5.83
April 0.131879E+09 1291.10 11-APR-08:61 7.17
May 62490159.17 1226.98 05-MAY-08:62 8.17
June 3176221.03 797.30 20-JUN-08:03 15.17
July 3541060.02 938.52 06-JUL-08:53 18.00
August 1623239.75 1021.96 21-AUG-08:53 17.00
September 15393452.17 966.52 14-SEP-08:53 17.00
October 0.329205E+09 1336.30 19-OCT-15:01 9.00
November 0.748984E+09 1354.55 30-NOV-19:01 4.83
December 0.120637E+10 1358.94 19-DEC-19:01 7.00
         
Annual Sum or Average 0.483671E+10      
Minimum of Months 1623239.75 797.30   4.83
Maximum of Months 0.120637E+10 1358.94   18.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2783587.92 68.36 31-JAN-05:00 1.00
February 3761050.51 93.27 02-FEB-04:50 4.00
March 1888614.00 48.20 06-MAR-05:00 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 716415.78 30.79 30-NOV-05:00 3.00
December 45212283.58 148.30 17-DEC-04:40 1.00
         
Annual Sum or Average 54361951.79      
Minimum of Months 0.00 0.00   1.00
Maximum of Months 45212283.58 148.30   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 77687045.47 378.82 11-JAN-16:01 -2.2
February 45084930.29 355.63 24-FEB-16:01 6.00
March 9187159.53 348.42 15-MAR-15:02 3.00
April 813424.70 335.75 10-APR-15:02 7.17
May 702705.95 308.95 26-MAY-15:04 15.67
June 601602.28 350.29 01-JUN-15:04 16.00
July 536456.28 319.11 28-JUL-08:15 15.33
August 524255.15 263.48 03-AUG-08:05 14.17
September 803039.32 362.83 29-SEP-15:03 15.67
October 1536317.36 350.10 27-OCT-15:01 9.00
November 30516203.58 361.69 20-NOV-16:01 6.83
December 96038893.16 366.08 19-DEC-16:01 7.00
         
Annual Sum or Average 0.264032E+09      
Minimum of Months 524255.15 263.48   -2.2
Maximum of Months 96038893.16 378.82   16.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.780120E+09 1343.09 31-JAN-19:01 6.00
February 0.597326E+09 1351.64 01-FEB-19:01 6.00
March 0.532567E+09 1310.37 24-MAR-08:61 7.00
April 83017676.30 1236.28 10-APR-15:02 7.17
May 53234740.90 826.84 14-MAY-18:02 9.00
June 5788747.41 849.78 05-JUN-18:03 10.83
July 2037667.03 1162.17 08-JUL-19:13 14.67
August 938682.91 795.56 26-AUG-21:14 14.67
September 5189231.03 1062.05 19-SEP-16:53 13.00
October 0.238035E+09 1334.92 27-OCT-15:01 9.00
November 0.599175E+09 1353.16 30-NOV-19:01 4.83
December 0.102441E+10 1356.80 23-DEC-16:01 8.83
         
Annual Sum or Average 0.392184E+10      
Minimum of Months 938682.91 795.56   4.83
Maximum of Months 0.102441E+10 1356.80   14.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.979746E+09 1321.87 14-JAN-19:01 5.83
February 0.781742E+09 1327.54 01-FEB-19:01 6.00
March 0.612587E+09 1296.07 02-MAR-19:01 3.67
April 0.120686E+09 1222.89 10-APR-15:02 7.17
May 66633282.77 936.19 17-MAY-15:01 9.50
June 6711895.65 837.26 17-JUN-15:04 15.83
July 2117347.62 697.75 07-JUL-15:04 15.83
August 1262695.18 695.36 11-AUG-15:04 17.00
September 11117107.41 965.07 21-SEP-18:33 13.00
October 0.325429E+09 1310.62 27-OCT-15:01 9.00
November 0.744203E+09 1328.38 20-NOV-16:01 6.83
December 0.115426E+10 1331.54 22-DEC-16:01 6.67
         
Annual Sum or Average 0.480650E+10      
Minimum of Months 1262695.18 695.36   3.67
Maximum of Months 0.115426E+10 1331.54   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11785613.30 471.88 26-JAN-09:05 6.00
February 4472189.11 651.92 08-FEB-07:18 6.00
March 6273433.72 297.76 25-MAR-23:20 7.63
April 2005311.08 252.79 12-APR-08:44 7.00
May 1863784.60 268.85 19-MAY-05:03 9.00
June 229993.35 106.17 06-JUN-05:10 8.42
July 487978.36 102.31 05-JUL-05:20 7.67
August 0.00 0.00 01-AUG-00:05 11.43
September 640488.25 138.71 09-SEP-06:09 9.33
October 7212934.99 653.31 24-OCT-06:30 6.00
November 13482506.89 348.44 09-NOV-06:06 9.00
December 30181852.61 642.80 02-DEC-09:06 7.00
         
Annual Sum or Average 78636086.26      
Minimum of Months 0.00 0.00   6.00
Maximum of Months 30181852.61 653.31   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117190E+10 1641.05 31-JAN-19:01 6.00
February 0.866498E+09 1637.87 01-FEB-19:01 6.00
March 0.823255E+09 1621.09 08-MAR-19:01 5.83
April 0.191685E+09 1566.45 11-APR-08:61 7.17
May 0.127880E+09 1519.07 17-MAY-15:01 9.50
June 10529182.52 929.17 03-JUN-08:03 11.17
July 13945734.22 1001.93 19-JUL-08:53 17.00
August 1720626.25 994.80 01-AUG-08:53 17.00
September 35188255.33 1271.39 23-SEP-08:53 17.00
October 0.445104E+09 1634.37 19-OCT-15:01 9.00
November 0.922993E+09 1647.28 30-NOV-19:01 4.83
December 0.152245E+10 1650.31 23-DEC-16:01 8.83
         
Annual Sum or Average 0.613315E+10      
Minimum of Months 1720626.25 929.17   4.83
Maximum of Months 0.152245E+10 1650.31   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143360E+10 1605.40 11-JAN-09:13 -3.7
February 0.108041E+10 1601.57 01-FEB-19:01 6.00
March 0.925772E+09 1593.86 08-MAR-19:01 5.83
April 0.261515E+09 1548.66 11-APR-08:61 7.17
May 0.151361E+09 1504.66 06-MAY-08:61 8.17
June 11738901.42 882.14 03-JUN-08:03 11.17
July 14671846.61 968.81 19-JUL-08:53 17.00
August 2133636.71 1095.30 20-AUG-08:53 17.00
September 61359063.20 1448.55 20-SEP-08:62 11.50
October 0.583850E+09 1597.74 19-OCT-15:01 9.00
November 0.111083E+10 1609.77 30-NOV-19:01 4.83
December 0.169473E+10 1613.55 22-DEC-16:01 6.67
         
Annual Sum or Average 0.733197E+10      
Minimum of Months 2133636.71 882.14   -3.7
Maximum of Months 0.169473E+10 1613.55   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279656E+09 876.28 04-JAN-16:13 3.83
February 0.197550E+09 874.38 01-FEB-19:01 6.00
March 0.208493E+09 852.50 24-MAR-08:61 7.00
April 25772532.44 806.01 10-APR-15:02 7.17
May 23021547.79 695.91 05-MAY-08:62 8.17
June 3024910.82 715.53 23-JUN-08:53 16.00
July 1623698.32 901.11 08-JUL-19:13 14.67
August 1058757.03 688.03 01-AUG-08:53 17.00
September 1843116.13 569.68 09-SEP-08:03 13.33
October 67137170.32 875.74 27-OCT-15:01 9.00
November 0.193595E+09 881.84 30-NOV-19:01 4.83
December 0.455467E+09 894.63 23-DEC-16:01 8.83
         
Annual Sum or Average 0.145824E+10      
Minimum of Months 1058757.03 569.68   3.83
Maximum of Months 0.455467E+09 901.11   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 19749046.57 683.74 10-JAN-08:00 -6.0
February 8229786.55 1053.49 01-FEB-10:03 7.00
March 10527834.37 597.11 25-MAR-23:20 7.63
April 5040614.45 1507.13 11-APR-07:48 7.00
May 7337352.83 651.76 19-MAY-05:03 9.00
June 1681250.78 388.15 07-JUN-05:32 7.33
July 2203839.16 379.06 05-JUL-05:20 7.67
August 50489.79 161.98 30-AUG-03:29 9.50
September 6005477.22 556.29 17-SEP-05:32 8.67
October 15073520.17 2268.44 24-OCT-06:30 6.00
November 19496463.94 707.24 09-NOV-06:09 9.00
December 20107058.44 636.22 07-DEC-11:33 7.00
         
Annual Sum or Average 0.115503E+09      
Minimum of Months 50489.79 161.98   -6.0
Maximum of Months 20107058.44 2268.44   9.50



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160421E+11 15451.75 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.144845E+11 15451.75 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.160915E+11 15451.75 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.154982E+11 15451.75 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.160699E+11 15451.75 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.155692E+11 15451.75 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.159988E+11 15451.75 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.160977E+11 15451.75 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.155043E+11 15451.75 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.160359E+11 15451.75 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.155569E+11 15451.75 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.159988E+11 15451.75 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.188948E+12     0.143105E+12    
Minimum of Months 0.144845E+11 15451.75   0.109726E+11 9632.53  
Maximum of Months 0.160977E+11 15451.75   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.743719E+09 716.35 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.671510E+09 716.35 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.746011E+09 716.35 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.718503E+09 716.35 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.745008E+09 716.35 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.721798E+09 716.35 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.741713E+09 716.35 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.746298E+09 716.35 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.718790E+09 716.35 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.743432E+09 716.35 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.721225E+09 716.35 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.741713E+09 716.35 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.875972E+10     0.101856E+11    
Minimum of Months 0.671510E+09 716.35   0.780982E+09 685.60  
Maximum of Months 0.746298E+09 716.35   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.861229E+09 829.54 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.777612E+09 829.54 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.863884E+09 829.54 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.832029E+09 829.54 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.862722E+09 829.54 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.835845E+09 829.54 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.858907E+09 829.54 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.864216E+09 829.54 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.832361E+09 829.54 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.860897E+09 829.54 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.835182E+09 829.54 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.858907E+09 829.54 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.101438E+11     0.117950E+11    
Minimum of Months 0.777612E+09 829.54   0.904380E+09 793.93  
Maximum of Months 0.864216E+09 829.54   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.693793E+09 668.27 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.626432E+09 668.27 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.695932E+09 668.27 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.670270E+09 668.27 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.694996E+09 668.27 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.673344E+09 668.27 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.691922E+09 668.27 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.696199E+09 668.27 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.670538E+09 668.27 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.693526E+09 668.27 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.672810E+09 668.27 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.691922E+09 668.27 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.817168E+10     0.124712E+11    
Minimum of Months 0.626432E+09 668.27   0.956227E+09 839.45  
Maximum of Months 0.696199E+09 668.27   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.351983E+09 339.04 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.317809E+09 339.04 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.353068E+09 339.04 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.340049E+09 339.04 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.352593E+09 339.04 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.341609E+09 339.04 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.351034E+09 339.04 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.353204E+09 339.04 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.340185E+09 339.04 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.351847E+09 339.04 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.341337E+09 339.04 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.351034E+09 339.04 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.414575E+10     0.359760E+10    
Minimum of Months 0.317809E+09 339.04   0.275845E+09 242.16  
Maximum of Months 0.353204E+09 339.04   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.470933E+09 453.60 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.425209E+09 453.60 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.472384E+09 453.60 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.454966E+09 453.60 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.471749E+09 453.60 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.457052E+09 453.60 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.469662E+09 453.60 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.472566E+09 453.60 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.455147E+09 453.60 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.470751E+09 453.60 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.456689E+09 453.60 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.469662E+09 453.60 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.554677E+10     0.679355E+11    
Minimum of Months 0.425209E+09 453.60   0.520895E+10 4572.80  
Maximum of Months 0.472566E+09 453.60   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.163015E+10 1957.67 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.138924E+10 1957.67 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.144407E+10 1957.67 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.122787E+10 1957.67 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.110934E+10 1957.67 01-MAY-19:19 0.121917E+10 965.27 01-MAY-19:10
June 0.994585E+09 1957.67 01-JUN-19:30 0.118076E+10 965.27 01-JUN-19:10
July 0.105174E+10 1957.67 17-JUL-19:30 0.121533E+10 965.27 03-JUL-19:10
August 0.121509E+10 1957.67 01-AUG-19:30 0.122063E+10 965.27 01-AUG-19:10
September 0.132378E+10 1957.67 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.153395E+10 1957.67 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.156784E+10 1957.67 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.168803E+10 1957.67 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.161757E+11     0.143405E+11    
Minimum of Months 0.994585E+09 1957.67   0.109956E+10 965.27  
Maximum of Months 0.168803E+10 1957.67   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.858362E+10 8554.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.768471E+10 8554.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.847500E+10 8554.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.803109E+10 8554.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.821276E+10 8554.32 01-MAY-19:19 0.126672E+11 10029.21 01-MAY-19:10
June 0.790249E+10 8554.32 01-JUN-19:19 0.122682E+11 10029.21 01-JUN-19:10
July 0.813728E+10 8554.32 17-JUL-19:30 0.126273E+11 10029.21 03-JUL-19:10
August 0.830206E+10 8554.32 01-AUG-19:30 0.126824E+11 10029.21 01-AUG-19:10
September 0.810650E+10 8554.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.850846E+10 8554.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.831980E+10 8554.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.861426E+10 8554.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.988780E+11     0.148998E+12    
Minimum of Months 0.768471E+10 8554.32   0.114244E+11 10029.21  
Maximum of Months 0.861426E+10 8554.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232348E+09 210.22 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.209833E+09 210.22 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.230501E+09 210.22 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.225120E+09 210.22 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.231424E+09 210.22 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.223334E+09 210.22 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.233241E+09 210.22 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.230501E+09 210.22 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.225181E+09 210.22 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.232318E+09 210.22 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.224227E+09 210.22 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.233271E+09 210.22 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.273130E+10     0.261953E+10    
Minimum of Months 0.209833E+09 210.22   0.200969E+09 237.06  
Maximum of Months 0.233271E+09 210.22   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232321E+09 210.20 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.209808E+09 210.20 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.230474E+09 210.20 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.225094E+09 210.20 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.231397E+09 210.20 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.223308E+09 210.20 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.233213E+09 210.20 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.230474E+09 210.20 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.225154E+09 210.20 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.232290E+09 210.20 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.224201E+09 210.20 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.233244E+09 210.20 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.273098E+10     0.261922E+10    
Minimum of Months 0.209808E+09 210.20   0.200945E+09 237.03  
Maximum of Months 0.233244E+09 210.20   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146022E+09 132.12 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 0.131872E+09 132.12 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 0.144861E+09 132.12 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 0.141479E+09 132.12 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 0.145441E+09 132.12 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 0.140357E+09 132.12 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 0.146583E+09 132.12 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 0.144861E+09 132.12 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 0.141518E+09 132.12 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 0.146003E+09 132.12 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 0.140918E+09 132.12 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 0.146602E+09 132.12 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.171652E+10     0.256575E+10    
Minimum of Months 0.131872E+09 132.12   0.196843E+09 232.19  
Maximum of Months 0.146602E+09 132.12   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146062E+09 132.15 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.131908E+09 132.15 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.144901E+09 132.15 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.141518E+09 132.15 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.145481E+09 132.15 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.140395E+09 132.15 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.146623E+09 132.15 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.144901E+09 132.15 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.141556E+09 132.15 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.146043E+09 132.15 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.140957E+09 132.15 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.146642E+09 132.15 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.171699E+10     0.256645E+10    
Minimum of Months 0.131908E+09 132.15   0.196897E+09 232.26  
Maximum of Months 0.146642E+09 132.15   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232348E+09 210.22 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.209833E+09 210.22 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.230501E+09 210.22 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.225120E+09 210.22 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.231424E+09 210.22 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.223334E+09 210.22 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.233241E+09 210.22 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.230501E+09 210.22 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.225181E+09 210.22 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.232318E+09 210.22 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.224227E+09 210.22 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.233271E+09 210.22 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.273130E+10     0.261953E+10    
Minimum of Months 0.209833E+09 210.22   0.200969E+09 237.06  
Maximum of Months 0.233271E+09 210.22   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232321E+09 210.20 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.209808E+09 210.20 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.230474E+09 210.20 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.225094E+09 210.20 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.231397E+09 210.20 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.223308E+09 210.20 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.233213E+09 210.20 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.230474E+09 210.20 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.225154E+09 210.20 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.232290E+09 210.20 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.224201E+09 210.20 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.233244E+09 210.20 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.273098E+10     0.261922E+10    
Minimum of Months 0.209808E+09 210.20   0.200945E+09 237.03  
Maximum of Months 0.233244E+09 210.20   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.193865E+10 1867.32 02-JAN-20:10 0.00 0.00
February 0.175042E+10 1867.32 01-FEB-20:10 0.00 0.00
March 0.194462E+10 1867.32 01-MAR-20:10 0.00 0.00
April 0.187292E+10 1867.32 03-APR-19:10 0.00 0.00
May 0.194201E+10 1867.32 01-MAY-19:10 0.00 0.00
June 0.188151E+10 1867.32 01-JUN-19:10 0.00 0.00
July 0.193342E+10 1867.32 03-JUL-19:10 0.00 0.00
August 0.194537E+10 1867.32 01-AUG-19:10 0.00 0.00
September 0.187367E+10 1867.32 01-SEP-19:10 0.00 0.00
October 0.193790E+10 1867.32 02-OCT-19:10 0.00 0.00
November 0.188002E+10 1867.32 01-NOV-19:10 0.00 0.00
December 0.193342E+10 1867.32 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.228339E+11     0.00 0.00
Minimum of Months 0.175042E+10 1867.32   0.00 0.00
Maximum of Months 0.194537E+10 1867.32   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232348E+09 210.22 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.209833E+09 210.22 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.230501E+09 210.22 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.225120E+09 210.22 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.231424E+09 210.22 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.223334E+09 210.22 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.233241E+09 210.22 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.230501E+09 210.22 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.225181E+09 210.22 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.232318E+09 210.22 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.224227E+09 210.22 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.233271E+09 210.22 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.273130E+10     0.261953E+10    
Minimum of Months 0.209833E+09 210.22   0.200969E+09 237.06  
Maximum of Months 0.233271E+09 210.22   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232321E+09 210.20 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.209808E+09 210.20 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.230474E+09 210.20 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.225094E+09 210.20 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.231397E+09 210.20 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.223308E+09 210.20 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.233213E+09 210.20 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.230474E+09 210.20 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.225154E+09 210.20 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.232290E+09 210.20 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.224201E+09 210.20 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.233244E+09 210.20 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.273098E+10     0.261922E+10    
Minimum of Months 0.209808E+09 210.20   0.200945E+09 237.03  
Maximum of Months 0.233244E+09 210.20   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.146062E+09 132.15 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.131908E+09 132.15 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.144901E+09 132.15 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.141518E+09 132.15 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.145481E+09 132.15 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.140395E+09 132.15 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.146623E+09 132.15 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.144901E+09 132.15 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.141556E+09 132.15 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.146043E+09 132.15 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.140957E+09 132.15 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.146642E+09 132.15 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.171699E+10     0.256645E+10    
Minimum of Months 0.131908E+09 132.15   0.196897E+09 232.26  
Maximum of Months 0.146642E+09 132.15   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.328722E+10 3437.84 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.287524E+10 3437.84 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.308582E+10 3437.84 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279127E+10 3437.84 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.272194E+10 3437.84 01-MAY-19:19 0.149358E+11 6747.90 01-MAY-06:10
June 0.256339E+10 3437.84 01-JUN-19:30 0.144540E+11 6747.90 01-JUN-06:10
July 0.265693E+10 3437.84 17-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.283406E+10 3437.84 01-AUG-19:40 0.149358E+11 6747.90 01-AUG-06:10
September 0.289833E+10 3437.84 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.317196E+10 3437.84 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.317158E+10 3437.84 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.333410E+10 3437.84 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.353918E+11     0.175857E+12    
Minimum of Months 0.256339E+10 3437.84   0.134904E+11 6747.90  
Maximum of Months 0.333410E+10 3437.84   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.328722E+10 3437.84 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.287524E+10 3437.84 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.308582E+10 3437.84 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279127E+10 3437.84 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.272194E+10 3437.84 01-MAY-19:19 0.149358E+11 6747.90 01-MAY-06:10
June 0.256339E+10 3437.84 01-JUN-19:30 0.144540E+11 6747.90 01-JUN-06:10
July 0.265693E+10 3437.84 17-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.283406E+10 3437.84 01-AUG-19:40 0.149358E+11 6747.90 01-AUG-06:10
September 0.289833E+10 3437.84 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.317196E+10 3437.84 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.317158E+10 3437.84 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.333410E+10 3437.84 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.353918E+11     0.175857E+12    
Minimum of Months 0.256339E+10 3437.84   0.134904E+11 6747.90  
Maximum of Months 0.333410E+10 3437.84   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.125718E+10 1210.92 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.113512E+10 1210.92 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.126106E+10 1210.92 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.121456E+10 1210.92 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.125936E+10 1210.92 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.122013E+10 1210.92 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.125379E+10 1210.92 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.126154E+10 1210.92 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.121504E+10 1210.92 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.125670E+10 1210.92 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.121916E+10 1210.92 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.125379E+10 1210.92 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.148074E+11     0.433742E+12    
Minimum of Months 0.113512E+10 1210.92   0.332733E+11 16487.34  
Maximum of Months 0.126154E+10 1210.92   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.205176E+10 1976.27 02-JAN-20:10 0.00 0.00
February 0.185255E+10 1976.27 01-FEB-20:10 0.00 0.00
March 0.205809E+10 1976.27 01-MAR-20:10 0.00 0.00
April 0.198220E+10 1976.27 03-APR-19:10 0.00 0.00
May 0.205532E+10 1976.27 01-MAY-19:10 0.00 0.00
June 0.199129E+10 1976.27 01-JUN-19:10 0.00 0.00
July 0.204623E+10 1976.27 03-JUL-19:10 0.00 0.00
August 0.205888E+10 1976.27 01-AUG-19:10 0.00 0.00
September 0.198299E+10 1976.27 01-SEP-19:10 0.00 0.00
October 0.205097E+10 1976.27 02-OCT-19:10 0.00 0.00
November 0.198971E+10 1976.27 01-NOV-19:10 0.00 0.00
December 0.204623E+10 1976.27 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.241662E+11     0.00 0.00
Minimum of Months 0.185255E+10 1976.27   0.00 0.00
Maximum of Months 0.205888E+10 1976.27   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.160421E+11 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.144845E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.160915E+11 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.154982E+11 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.160699E+11 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.155692E+11 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.159988E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.160977E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.155043E+11 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.160359E+11 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.155569E+11 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.159988E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.188948E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.144845E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.160977E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.743719E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.568621E+09
February 0.179968E+10 0.671510E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.510273E+09
March 0.199990E+10 0.746011E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.503891E+09
April 0.192973E+10 0.718503E+09 0.835931E+09 0.00 0.00 0.00 0.00 164603.30 0.400822E+09
May 0.199475E+10 0.745008E+09 0.865939E+09 0.00 0.00 0.00 0.00 3837.48 0.375763E+09
June 0.193394E+10 0.721798E+09 0.838659E+09 0.00 0.00 0.00 0.00 1065325.60 0.257636E+09
July 0.199054E+10 0.741713E+09 0.863211E+09 0.00 0.00 0.00 0.00 3513901.32 0.220004E+09
August 0.199896E+10 0.746298E+09 0.866978E+09 0.00 0.00 0.00 0.00 510028.39 0.201594E+09
September 0.192879E+10 0.718790E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.00 0.266218E+09
October 0.199148E+10 0.743432E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.395369E+09
November 0.192552E+10 0.721225E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.466775E+09
December 0.199054E+10 0.741713E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.564932E+09
                   
Annual Sum or Average 0.234744E+11 0.875972E+10 0.101856E+11 0.00 0.00 0.00 0.00 5257696.09 0.473190E+10
Minimum of Months 0.179968E+10 0.671510E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.201594E+09
Maximum of Months 0.199990E+10 0.746298E+09 0.866978E+09 0.00 0.00 0.00 0.00 3513901.32 0.568621E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.861229E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.228626E+09
February 0.208403E+10 0.777612E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.205554E+09
March 0.231589E+10 0.863884E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.206028E+09
April 0.223463E+10 0.832029E+09 0.968011E+09 0.00 0.00 0.00 0.00 57720.79 0.168715E+09
May 0.230993E+10 0.862722E+09 0.100276E+10 0.00 0.00 0.00 0.00 18373.35 0.161986E+09
June 0.223950E+10 0.835845E+09 0.971170E+09 0.00 0.00 0.00 0.00 425556.20 0.117704E+09
July 0.230505E+10 0.858907E+09 0.999601E+09 0.00 0.00 0.00 0.00 1302619.19 0.102732E+09
August 0.231480E+10 0.864216E+09 0.100396E+10 0.00 0.00 0.00 0.00 248764.59 94433439.98
September 0.223354E+10 0.832361E+09 0.968312E+09 0.00 0.00 0.00 0.00 0.00 0.117654E+09
October 0.230614E+10 0.860897E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 0.166569E+09
November 0.222975E+10 0.835182E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.191408E+09
December 0.230505E+10 0.858907E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.225347E+09
                   
Annual Sum or Average 0.271834E+11 0.101438E+11 0.117950E+11 0.00 0.00 0.00 0.00 2053034.13 0.198676E+10
Minimum of Months 0.208403E+10 0.777612E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 94433439.98
Maximum of Months 0.231589E+10 0.864216E+09 0.100396E+10 0.00 0.00 0.00 0.00 1302619.19 0.228626E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.693793E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.517833E+09
February 0.440737E+09 0.626432E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.462981E+09
March 0.489771E+09 0.695932E+09 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.464020E+09
April 0.472586E+09 0.670270E+09 0.102351E+10 0.00 0.00 0.00 0.00 256359.03 0.375006E+09
May 0.488511E+09 0.694996E+09 0.106025E+10 0.00 0.00 0.00 0.00 107870.82 0.363240E+09
June 0.473617E+09 0.673344E+09 0.102685E+10 0.00 0.00 0.00 0.00 1184444.35 0.267548E+09
July 0.487480E+09 0.691922E+09 0.105691E+10 0.00 0.00 0.00 0.00 3139884.80 0.234906E+09
August 0.489542E+09 0.696199E+09 0.106152E+10 0.00 0.00 0.00 0.00 764757.66 0.213980E+09
September 0.472357E+09 0.670538E+09 0.102382E+10 0.00 0.00 0.00 0.00 21717.35 0.263810E+09
October 0.487709E+09 0.693526E+09 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.372177E+09
November 0.471555E+09 0.672810E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.429330E+09
December 0.487480E+09 0.691922E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.514979E+09
                   
Annual Sum or Average 0.574883E+10 0.817168E+10 0.124712E+11 0.00 0.00 0.00 0.00 5475034.00 0.447981E+10
Minimum of Months 0.440737E+09 0.626432E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.213980E+09
Maximum of Months 0.489771E+09 0.696199E+09 0.106152E+10 0.00 0.00 0.00 0.00 3139884.80 0.517833E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.351983E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.297258E+09
February 0.339028E+09 0.317809E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.265833E+09
March 0.376747E+09 0.353068E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.265186E+09
April 0.363528E+09 0.340049E+09 0.295253E+09 0.00 0.00 0.00 0.00 169371.15 0.210230E+09
May 0.375778E+09 0.352593E+09 0.305852E+09 0.00 0.00 0.00 0.00 72124.57 0.202856E+09
June 0.364321E+09 0.341609E+09 0.296217E+09 0.00 0.00 0.00 0.00 750815.11 0.148349E+09
July 0.374985E+09 0.351034E+09 0.304889E+09 0.00 0.00 0.00 0.00 1930547.86 0.129464E+09
August 0.376571E+09 0.353204E+09 0.306219E+09 0.00 0.00 0.00 0.00 505780.02 0.117207E+09
September 0.363352E+09 0.340185E+09 0.295345E+09 0.00 0.00 0.00 0.00 31609.14 0.145722E+09
October 0.375161E+09 0.351847E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 0.208110E+09
November 0.362735E+09 0.341337E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.244396E+09
December 0.374985E+09 0.351034E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.296383E+09
                   
Annual Sum or Average 0.442217E+10 0.414575E+10 0.359760E+10 0.00 0.00 0.00 0.00 3460247.86 0.253099E+10
Minimum of Months 0.339028E+09 0.317809E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.117207E+09
Maximum of Months 0.376747E+09 0.353204E+09 0.306219E+09 0.00 0.00 0.00 0.00 1930547.86 0.297258E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.470933E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.790271E+09
February 0.139600E+10 0.425209E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.707326E+09
March 0.155131E+10 0.472384E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.714929E+09
April 0.149688E+10 0.454966E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 306906.33 0.564230E+09
May 0.154732E+10 0.471749E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 77039.52 0.541585E+09
June 0.150015E+10 0.457052E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 1579890.29 0.386927E+09
July 0.154405E+10 0.469662E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 4526110.57 0.333065E+09
August 0.155059E+10 0.472566E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 1093465.63 0.301378E+09
September 0.149615E+10 0.455147E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 84324.75 0.381713E+09
October 0.154478E+10 0.470751E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.568220E+09
November 0.149361E+10 0.456689E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.664055E+09
December 0.154405E+10 0.469662E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.786904E+09
                   
Annual Sum or Average 0.182090E+11 0.554677E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 7667737.09 0.674060E+10
Minimum of Months 0.139600E+10 0.425209E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.301378E+09
Maximum of Months 0.155131E+10 0.472566E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 4526110.57 0.790271E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.163015E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.128729E+10
February 0.236489E+11 0.138924E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.115923E+10
March 0.262800E+11 0.144407E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.114743E+10
April 0.253579E+11 0.122787E+10 0.117692E+10 0.00 0.00 0.00 0.00 325031.94 0.943994E+09
May 0.262123E+11 0.110934E+10 0.121917E+10 0.00 0.00 0.00 0.00 3593.26 0.891976E+09
June 0.254132E+11 0.994585E+09 0.118076E+10 0.00 0.00 0.00 0.00 2125475.23 0.633566E+09
July 0.261570E+11 0.105174E+10 0.121533E+10 0.00 0.00 0.00 0.00 7227232.19 0.552642E+09
August 0.262677E+11 0.121509E+10 0.122063E+10 0.00 0.00 0.00 0.00 1023711.49 0.516020E+09
September 0.253456E+11 0.132378E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.00 0.657456E+09
October 0.261693E+11 0.153395E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.928203E+09
November 0.253025E+11 0.156784E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.106934E+10
December 0.261570E+11 0.168803E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.126950E+10
                   
Annual Sum or Average 0.308468E+12 0.161757E+11 0.143405E+11 0.00 0.00 0.00 0.00 10705044.12 0.110566E+11
Minimum of Months 0.236489E+11 0.994585E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.516020E+09
Maximum of Months 0.262800E+11 0.168803E+10 0.122063E+10 0.00 0.00 0.00 0.00 7227232.19 0.128729E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.858362E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.382167E+10
February 0.702046E+11 0.768471E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.343684E+10
March 0.780153E+11 0.847500E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.344439E+10
April 0.752779E+11 0.803109E+10 0.122282E+11 0.00 0.00 0.00 0.00 987840.18 0.282115E+10
May 0.778146E+11 0.821276E+10 0.126672E+11 0.00 0.00 0.00 0.00 197945.48 0.270336E+10
June 0.754422E+11 0.790249E+10 0.122682E+11 0.00 0.00 0.00 0.00 6592359.06 0.196609E+10
July 0.776503E+11 0.813728E+10 0.126273E+11 0.00 0.00 0.00 0.00 20609618.34 0.171978E+10
August 0.779788E+11 0.830206E+10 0.126824E+11 0.00 0.00 0.00 0.00 3548646.53 0.158795E+10
September 0.752414E+11 0.810650E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.00 0.198199E+10
October 0.776868E+11 0.850846E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.279709E+10
November 0.751137E+11 0.831980E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.320786E+10
December 0.776503E+11 0.861426E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.376769E+10
                   
Annual Sum or Average 0.915726E+12 0.988780E+11 0.148998E+12 0.00 0.00 0.00 0.00 31936409.59 0.332559E+11
Minimum of Months 0.702046E+11 0.768471E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.158795E+10
Maximum of Months 0.780153E+11 0.861426E+10 0.126824E+11 0.00 0.00 0.00 0.00 20609618.34 0.382167E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232348E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.324772E+09
February 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.292842E+09
March 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.290513E+09
April 0.293479E+09 0.225120E+09 0.215344E+09 0.00 0.00 0.00 0.00 225663.17 0.234937E+09
May 0.303504E+09 0.231424E+09 0.222446E+09 0.00 0.00 0.00 0.00 15721.11 0.224685E+09
June 0.293842E+09 0.223334E+09 0.215230E+09 0.00 0.00 0.00 0.00 870296.19 0.160681E+09
July 0.303141E+09 0.233241E+09 0.222560E+09 0.00 0.00 0.00 0.00 2313950.29 0.143122E+09
August 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 577046.22 0.129516E+09
September 0.293479E+09 0.225181E+09 0.215344E+09 0.00 0.00 0.00 0.00 17587.73 0.157798E+09
October 0.303322E+09 0.232318E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.227208E+09
November 0.293661E+09 0.224227E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.266890E+09
December 0.303141E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.320761E+09
                   
Annual Sum or Average 0.357224E+10 0.273130E+10 0.261953E+10 0.00 0.00 0.00 0.00 4020264.71 0.277373E+10
Minimum of Months 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.129516E+09
Maximum of Months 0.303685E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 2313950.29 0.324772E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232321E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.321073E+09
February 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.288803E+09
March 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.288603E+09
April 0.293479E+09 0.225094E+09 0.215319E+09 0.00 0.00 0.00 0.00 228668.08 0.231336E+09
May 0.303504E+09 0.231397E+09 0.222420E+09 0.00 0.00 0.00 0.00 16188.87 0.222368E+09
June 0.293842E+09 0.223308E+09 0.215205E+09 0.00 0.00 0.00 0.00 870375.00 0.159386E+09
July 0.303141E+09 0.233213E+09 0.222534E+09 0.00 0.00 0.00 0.00 2325012.00 0.141391E+09
August 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 581563.88 0.126107E+09
September 0.293479E+09 0.225154E+09 0.215319E+09 0.00 0.00 0.00 0.00 20835.60 0.153050E+09
October 0.303322E+09 0.232290E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.223366E+09
November 0.293661E+09 0.224201E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.263611E+09
December 0.303141E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.318455E+09
                   
Annual Sum or Average 0.357224E+10 0.273098E+10 0.261922E+10 0.00 0.00 0.00 0.00 4042643.44 0.273755E+10
Minimum of Months 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.126107E+09
Maximum of Months 0.303685E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 2325012.00 0.321073E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.146022E+09 0.217935E+09 0.00 0.00 0.00 0.00 0.00 89889986.15
February 0.00 0.131872E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 81921409.27
March 0.00 0.144861E+09 0.217824E+09 0.00 0.00 0.00 0.00 0.00 76216194.97
April 0.00 0.141479E+09 0.210923E+09 0.00 0.00 0.00 0.00 18503.86 71415671.23
May 0.00 0.145441E+09 0.217879E+09 0.00 0.00 0.00 0.00 2652.99 68388205.69
June 0.00 0.140357E+09 0.210812E+09 0.00 0.00 0.00 0.00 138799.64 50237160.38
July 0.00 0.146583E+09 0.217991E+09 0.00 0.00 0.00 0.00 506447.57 43546441.21
August 0.00 0.144861E+09 0.217824E+09 0.00 0.00 0.00 0.00 94345.09 39816392.06
September 0.00 0.141518E+09 0.210923E+09 0.00 0.00 0.00 0.00 0.00 49823754.79
October 0.00 0.146003E+09 0.217935E+09 0.00 0.00 0.00 0.00 0.00 67839441.54
November 0.00 0.140918E+09 0.210867E+09 0.00 0.00 0.00 0.00 0.00 74061372.03
December 0.00 0.146602E+09 0.217991E+09 0.00 0.00 0.00 0.00 0.00 82510701.35
                   
Annual Sum or Average 0.00 0.171652E+10 0.256575E+10 0.00 0.00 0.00 0.00 760749.15 0.795667E+09
Minimum of Months 0.00 0.131872E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 39816392.06
Maximum of Months 0.00 0.146602E+09 0.217991E+09 0.00 0.00 0.00 0.00 506447.57 89889986.15



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.146062E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 90969945.53
February 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 81586319.19
March 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 0.00 81831141.17
April 0.293479E+09 0.141518E+09 0.210981E+09 0.00 0.00 0.00 0.00 79921.80 63791366.59
May 0.303504E+09 0.145481E+09 0.217939E+09 0.00 0.00 0.00 0.00 19421.88 60759393.06
June 0.293842E+09 0.140395E+09 0.210869E+09 0.00 0.00 0.00 0.00 295282.95 42345544.74
July 0.303141E+09 0.146623E+09 0.218051E+09 0.00 0.00 0.00 0.00 720310.92 35906214.33
August 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 231657.07 31650424.50
September 0.293479E+09 0.141556E+09 0.210981E+09 0.00 0.00 0.00 0.00 38287.88 40641138.43
October 0.303322E+09 0.146043E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 62850505.00
November 0.293661E+09 0.140957E+09 0.210925E+09 0.00 0.00 0.00 0.00 0.00 74908107.42
December 0.303141E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 0.00 90527637.21
                   
Annual Sum or Average 0.357224E+10 0.171699E+10 0.256645E+10 0.00 0.00 0.00 0.00 1384882.49 0.757768E+09
Minimum of Months 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 31650424.50
Maximum of Months 0.303685E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 720310.92 90969945.53



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232348E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.324678E+09
February 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.292557E+09
March 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.291038E+09
April 0.293479E+09 0.225120E+09 0.215344E+09 0.00 0.00 0.00 0.00 235030.80 0.236271E+09
May 0.303504E+09 0.231424E+09 0.222446E+09 0.00 0.00 0.00 0.00 17511.65 0.224667E+09
June 0.293842E+09 0.223334E+09 0.215230E+09 0.00 0.00 0.00 0.00 877104.77 0.158940E+09
July 0.303141E+09 0.233241E+09 0.222560E+09 0.00 0.00 0.00 0.00 2289789.85 0.137936E+09
August 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 584647.14 0.125263E+09
September 0.293479E+09 0.225181E+09 0.215344E+09 0.00 0.00 0.00 0.00 21217.18 0.156624E+09
October 0.303322E+09 0.232318E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.227783E+09
November 0.293661E+09 0.224227E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.266790E+09
December 0.303141E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.321030E+09
                   
Annual Sum or Average 0.357224E+10 0.273130E+10 0.261953E+10 0.00 0.00 0.00 0.00 4025301.41 0.276358E+10
Minimum of Months 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.125263E+09
Maximum of Months 0.303685E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 2289789.85 0.324678E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232321E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.321095E+09
February 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.288416E+09
March 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.289180E+09
April 0.293479E+09 0.225094E+09 0.215319E+09 0.00 0.00 0.00 0.00 237756.38 0.233769E+09
May 0.303504E+09 0.231397E+09 0.222420E+09 0.00 0.00 0.00 0.00 18536.41 0.223164E+09
June 0.293842E+09 0.223308E+09 0.215205E+09 0.00 0.00 0.00 0.00 878170.69 0.158195E+09
July 0.303141E+09 0.233213E+09 0.222534E+09 0.00 0.00 0.00 0.00 2285675.86 0.137005E+09
August 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 589787.47 0.123416E+09
September 0.293479E+09 0.225154E+09 0.215319E+09 0.00 0.00 0.00 0.00 23867.13 0.153918E+09
October 0.303322E+09 0.232290E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.224290E+09
November 0.293661E+09 0.224201E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.263501E+09
December 0.303141E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.318746E+09
                   
Annual Sum or Average 0.357224E+10 0.273098E+10 0.261922E+10 0.00 0.00 0.00 0.00 4033793.93 0.273469E+10
Minimum of Months 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.123416E+09
Maximum of Months 0.303685E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 2285675.86 0.321095E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.193865E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.397420E+09
February 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.355619E+09
March 0.387034E+10 0.194462E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.354592E+09
April 0.373454E+10 0.187292E+10 0.00 0.00 0.00 0.00 0.00 162147.44 0.285463E+09
May 0.386038E+10 0.194201E+10 0.00 0.00 0.00 0.00 0.00 71318.38 0.276875E+09
June 0.374269E+10 0.188151E+10 0.00 0.00 0.00 0.00 0.00 897773.85 0.201656E+09
July 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 2410608.73 0.177227E+09
August 0.386853E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 527109.23 0.162148E+09
September 0.373273E+10 0.187367E+10 0.00 0.00 0.00 0.00 0.00 1270.07 0.199696E+09
October 0.385404E+10 0.193790E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.279511E+09
November 0.372639E+10 0.188002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.326446E+09
December 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.396234E+09
                   
Annual Sum or Average 0.454292E+11 0.228339E+11 0.00 0.00 0.00 0.00 0.00 4070227.70 0.341289E+10
Minimum of Months 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.162148E+09
Maximum of Months 0.387034E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 2410608.73 0.397420E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232348E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.324302E+09
February 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.292422E+09
March 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.290223E+09
April 0.293479E+09 0.225120E+09 0.215344E+09 0.00 0.00 0.00 0.00 206187.61 0.236245E+09
May 0.303504E+09 0.231424E+09 0.222446E+09 0.00 0.00 0.00 0.00 13452.86 0.226233E+09
June 0.293842E+09 0.223334E+09 0.215230E+09 0.00 0.00 0.00 0.00 843532.64 0.162670E+09
July 0.303141E+09 0.233241E+09 0.222560E+09 0.00 0.00 0.00 0.00 2267241.42 0.146321E+09
August 0.303685E+09 0.230501E+09 0.222390E+09 0.00 0.00 0.00 0.00 559086.69 0.132432E+09
September 0.293479E+09 0.225181E+09 0.215344E+09 0.00 0.00 0.00 0.00 15216.03 0.159701E+09
October 0.303322E+09 0.232318E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.227127E+09
November 0.293661E+09 0.224227E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.266349E+09
December 0.303141E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.320679E+09
                   
Annual Sum or Average 0.357224E+10 0.273130E+10 0.261953E+10 0.00 0.00 0.00 0.00 3904717.25 0.278470E+10
Minimum of Months 0.273974E+09 0.209833E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.132432E+09
Maximum of Months 0.303685E+09 0.233271E+09 0.222560E+09 0.00 0.00 0.00 0.00 2267241.42 0.324302E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.232321E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.320937E+09
February 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.288306E+09
March 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.288196E+09
April 0.293479E+09 0.225094E+09 0.215319E+09 0.00 0.00 0.00 0.00 212025.94 0.232684E+09
May 0.303504E+09 0.231397E+09 0.222420E+09 0.00 0.00 0.00 0.00 14044.99 0.223963E+09
June 0.293842E+09 0.223308E+09 0.215205E+09 0.00 0.00 0.00 0.00 842620.59 0.161568E+09
July 0.303141E+09 0.233213E+09 0.222534E+09 0.00 0.00 0.00 0.00 2272272.07 0.144701E+09
August 0.303685E+09 0.230474E+09 0.222364E+09 0.00 0.00 0.00 0.00 564724.81 0.129090E+09
September 0.293479E+09 0.225154E+09 0.215319E+09 0.00 0.00 0.00 0.00 18973.13 0.154534E+09
October 0.303322E+09 0.232290E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.222929E+09
November 0.293661E+09 0.224201E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.263116E+09
December 0.303141E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.318957E+09
                   
Annual Sum or Average 0.357224E+10 0.273098E+10 0.261922E+10 0.00 0.00 0.00 0.00 3924661.53 0.274898E+10
Minimum of Months 0.273974E+09 0.209808E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.129090E+09
Maximum of Months 0.303685E+09 0.233244E+09 0.222534E+09 0.00 0.00 0.00 0.00 2272272.07 0.320937E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.146062E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.169743E+09
February 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 0.152667E+09
March 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 0.00 0.151088E+09
April 0.293479E+09 0.141518E+09 0.210981E+09 0.00 0.00 0.00 0.00 115651.32 0.121459E+09
May 0.303504E+09 0.145481E+09 0.217939E+09 0.00 0.00 0.00 0.00 7901.68 0.115136E+09
June 0.293842E+09 0.140395E+09 0.210869E+09 0.00 0.00 0.00 0.00 438636.38 81122730.22
July 0.303141E+09 0.146623E+09 0.218051E+09 0.00 0.00 0.00 0.00 1168917.71 70529600.14
August 0.303685E+09 0.144901E+09 0.217883E+09 0.00 0.00 0.00 0.00 289630.34 64588033.08
September 0.293479E+09 0.141556E+09 0.210981E+09 0.00 0.00 0.00 0.00 7560.34 81605453.13
October 0.303322E+09 0.146043E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.118478E+09
November 0.293661E+09 0.140957E+09 0.210925E+09 0.00 0.00 0.00 0.00 0.00 0.139624E+09
December 0.303141E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 0.00 0.167390E+09
                   
Annual Sum or Average 0.357224E+10 0.171699E+10 0.256645E+10 0.00 0.00 0.00 0.00 2028297.76 0.143343E+10
Minimum of Months 0.273974E+09 0.131908E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 64588033.08
Maximum of Months 0.303685E+09 0.146642E+09 0.218051E+09 0.00 0.00 0.00 0.00 1168917.71 0.169743E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.328722E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.927366E+09
February 0.415303E+11 0.287524E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.832121E+09
March 0.461508E+11 0.308582E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.845503E+09
April 0.445315E+11 0.279127E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.678185E+09
May 0.460320E+11 0.272194E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.654425E+09
June 0.446286E+11 0.256339E+10 0.144540E+11 0.00 0.00 0.00 0.00 665282.91 0.479752E+09
July 0.459349E+11 0.265693E+10 0.149358E+11 0.00 0.00 0.00 0.00 3517446.93 0.419482E+09
August 0.461292E+11 0.283406E+10 0.149358E+11 0.00 0.00 0.00 0.00 498885.97 0.384363E+09
September 0.445099E+11 0.289833E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.470973E+09
October 0.459565E+11 0.317196E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.677333E+09
November 0.444343E+11 0.317158E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.782108E+09
December 0.459349E+11 0.333410E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.923199E+09
                   
Annual Sum or Average 0.541708E+12 0.353918E+11 0.175857E+12 0.00 0.00 0.00 0.00 4681615.81 0.807481E+10
Minimum of Months 0.415303E+11 0.256339E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.384363E+09
Maximum of Months 0.461508E+11 0.333410E+10 0.149358E+11 0.00 0.00 0.00 0.00 3517446.93 0.927366E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.328722E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.935995E+09
February 0.415303E+11 0.287524E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.839711E+09
March 0.461508E+11 0.308582E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.852747E+09
April 0.445315E+11 0.279127E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.682400E+09
May 0.460320E+11 0.272194E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.658108E+09
June 0.446286E+11 0.256339E+10 0.144540E+11 0.00 0.00 0.00 0.00 665263.36 0.481820E+09
July 0.459349E+11 0.265693E+10 0.149358E+11 0.00 0.00 0.00 0.00 3474690.59 0.420967E+09
August 0.461292E+11 0.283406E+10 0.149358E+11 0.00 0.00 0.00 0.00 498874.19 0.386286E+09
September 0.445099E+11 0.289833E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.473925E+09
October 0.459565E+11 0.317196E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.683421E+09
November 0.444343E+11 0.317158E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.789771E+09
December 0.459349E+11 0.333410E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.932337E+09
                   
Annual Sum or Average 0.541708E+12 0.353918E+11 0.175857E+12 0.00 0.00 0.00 0.00 4638828.14 0.813749E+10
Minimum of Months 0.415303E+11 0.256339E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.386286E+09
Maximum of Months 0.461508E+11 0.333410E+10 0.149358E+11 0.00 0.00 0.00 0.00 3474690.59 0.935995E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.125718E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.842730E+09
February 0.369574E+10 0.113512E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.754059E+09
March 0.410691E+10 0.126106E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.766754E+09
April 0.396281E+10 0.121456E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.611626E+09
May 0.409635E+10 0.125936E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.589988E+09
June 0.397146E+10 0.122013E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 600071.22 0.429091E+09
July 0.408770E+10 0.125379E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 3109068.77 0.374419E+09
August 0.410499E+10 0.126154E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 449079.37 0.343526E+09
September 0.396089E+10 0.121504E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.423062E+09
October 0.408962E+10 0.125670E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.615663E+09
November 0.395417E+10 0.121916E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.712192E+09
December 0.408770E+10 0.125379E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.839156E+09
                   
Annual Sum or Average 0.482060E+11 0.148074E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 4158219.37 0.730227E+10
Minimum of Months 0.369574E+10 0.113512E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.343526E+09
Maximum of Months 0.410691E+10 0.126154E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 3109068.77 0.842730E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.205176E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.706473E+09
February 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.632710E+09
March 0.409620E+10 0.205809E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.630745E+09
April 0.395248E+10 0.198220E+10 0.00 0.00 0.00 0.00 0.00 101817.49 0.509279E+09
May 0.408566E+10 0.205532E+10 0.00 0.00 0.00 0.00 0.00 14400.16 0.490061E+09
June 0.396110E+10 0.199129E+10 0.00 0.00 0.00 0.00 0.00 877091.12 0.358247E+09
July 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 3592810.36 0.313268E+09
August 0.409429E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 632427.31 0.282973E+09
September 0.395056E+10 0.198299E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.347298E+09
October 0.407896E+10 0.205097E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.493129E+09
November 0.394385E+10 0.198971E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.580754E+09
December 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.703966E+09
                   
Annual Sum or Average 0.480803E+11 0.241662E+11 0.00 0.00 0.00 0.00 0.00 5218546.43 0.604890E+10
Minimum of Months 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.282973E+09
Maximum of Months 0.409620E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 3592810.36 0.706473E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 15451.75 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 15451.75 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 15451.75 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 15451.75 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 15451.75 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 15451.75 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 15451.75 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 15451.75 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 15451.75 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 15451.75 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 15451.75 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 15451.75 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   15451.75   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   15451.75   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 716.35 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 348.07 11-JAN-24:00
February 1169.53 01-FEB-00:10 716.35 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 322.59 17-FEB-07:00
March 1169.53 01-MAR-00:10 716.35 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 279.67 08-MAR-07:00
April 1169.53 01-APR-00:10 716.35 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 17.33 30-APR-18:00 265.43 08-APR-06:00
May 1169.53 01-MAY-00:10 716.35 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 2.48 22-MAY-15:00 240.84 06-MAY-05:00
June 1169.53 01-JUN-00:10 716.35 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 49.34 13-JUN-17:00 186.86 07-JUN-05:00
July 1169.53 01-JUL-00:10 716.35 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 78.67 22-JUL-18:00 174.53 06-JUL-03:57
August 1169.53 01-AUG-00:10 716.35 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 48.99 14-AUG-18:00 167.11 24-AUG-05:55
September 1169.53 01-SEP-00:10 716.35 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 200.70 21-SEP-06:00
October 1169.53 01-OCT-23:10 716.35 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 239.20 15-OCT-04:00
November 1169.53 01-NOV-00:10 716.35 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 297.50 29-NOV-02:00
December 1169.53 01-DEC-00:10 716.35 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 306.95 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   716.35   685.60   0.00 0.00 0.00 0.00 0.00   167.11  
Maximum of Months 1169.53   716.35   685.60   0.00 0.00 0.00 0.00 78.67   348.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 829.54 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 140.32 11-JAN-24:00
February 1354.32 01-FEB-00:10 829.54 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 128.19 17-FEB-21:00
March 1354.32 01-MAR-00:10 829.54 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 112.72 08-MAR-07:00
April 1354.32 01-APR-00:10 829.54 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 4.53 30-APR-17:00 109.45 08-APR-06:00
May 1354.32 01-MAY-00:10 829.54 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 4.77 22-MAY-15:00 99.57 06-MAY-05:00
June 1354.32 01-JUN-00:10 829.54 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 16.87 13-JUN-17:00 80.88 07-JUN-05:00
July 1354.32 01-JUL-00:10 829.54 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 26.85 22-JUL-18:00 76.93 06-JUL-04:00
August 1354.32 01-AUG-00:10 829.54 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 16.91 14-AUG-17:00 74.82 24-AUG-05:55
September 1354.32 01-SEP-00:10 829.54 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 88.33 20-SEP-24:00
October 1354.32 01-OCT-23:10 829.54 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 100.84 07-OCT-04:00
November 1354.32 01-NOV-00:10 829.54 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 119.53 29-NOV-02:00
December 1354.32 01-DEC-00:10 829.54 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 125.26 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   829.54   793.93   0.00 0.00 0.00 0.00 0.00   74.82  
Maximum of Months 1354.32   829.54   793.93   0.00 0.00 0.00 0.00 26.85   140.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 668.27 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 317.53 11-JAN-24:00
February 286.42 01-FEB-00:10 668.27 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 294.24 17-FEB-07:00
March 286.42 01-MAR-00:10 668.27 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 255.12 08-MAR-07:00
April 286.42 01-APR-00:10 668.27 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 16.34 30-APR-17:00 247.48 08-APR-06:00
May 286.42 01-MAY-00:10 668.27 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 18.12 22-MAY-15:00 225.20 07-MAY-05:00
June 286.42 01-JUN-00:10 668.27 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 43.13 13-JUN-17:00 182.73 07-JUN-05:00
July 286.42 01-JUL-00:10 668.27 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 67.06 22-JUL-18:00 175.19 31-JUL-05:00
August 286.42 01-AUG-00:10 668.27 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 44.55 14-AUG-17:00 168.17 24-AUG-05:55
September 286.42 01-SEP-00:10 668.27 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 3.85 11-SEP-17:00 199.15 20-SEP-24:00
October 286.42 01-OCT-23:10 668.27 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 227.48 07-OCT-04:00
November 286.42 01-NOV-00:10 668.27 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 271.39 29-NOV-02:00
December 286.42 01-DEC-00:10 668.27 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 281.03 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   668.27   839.45   0.00 0.00 0.00 0.00 0.00   168.17  
Maximum of Months 286.42   668.27   839.45   0.00 0.00 0.00 0.00 67.06   317.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 339.04 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 183.19 11-JAN-24:00
February 220.32 01-FEB-00:10 339.04 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 169.76 17-FEB-07:00
March 220.32 01-MAR-00:10 339.04 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 147.18 08-MAR-07:00
April 220.32 01-APR-00:10 339.04 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 10.30 30-APR-17:00 139.69 08-APR-06:00
May 220.32 01-MAY-00:10 339.04 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 11.27 22-MAY-15:00 126.88 07-MAY-05:00
June 220.32 01-JUN-00:10 339.04 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 25.71 13-JUN-17:00 102.87 01-JUN-05:00
July 220.32 01-JUL-00:10 339.04 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 39.92 22-JUL-18:00 98.26 31-JUL-05:00
August 220.32 01-AUG-00:10 339.04 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 26.68 14-AUG-17:00 94.09 24-AUG-05:55
September 220.32 01-SEP-00:10 339.04 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 3.41 11-SEP-17:00 111.80 20-SEP-24:00
October 220.32 01-OCT-23:10 339.04 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 128.44 07-OCT-04:00
November 220.32 01-NOV-00:10 339.04 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 156.58 29-NOV-02:00
December 220.32 01-DEC-00:10 339.04 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 161.55 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   339.04   242.16   0.00 0.00 0.00 0.00 0.00   94.09  
Maximum of Months 220.32   339.04   242.16   0.00 0.00 0.00 0.00 39.92   183.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 453.60 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:10 481.16 11-JAN-24:00
February 907.20 01-FEB-00:10 453.60 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 449.80 17-FEB-07:00
March 907.20 01-MAR-00:10 453.60 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:03 395.69 08-MAR-07:00
April 907.20 01-APR-00:10 453.60 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 36.56 30-APR-17:00 365.80 08-APR-06:00
May 907.20 01-MAY-00:10 453.60 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 16.11 22-MAY-15:20 334.72 10-MAY-06:10
June 907.20 01-JUN-00:10 453.60 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 70.06 13-JUN-17:00 309.80 08-JUN-05:55
July 907.20 01-JUL-00:10 453.60 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 98.71 21-JUL-17:00 269.73 05-JUL-05:16
August 907.20 01-AUG-00:10 453.60 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 69.60 14-AUG-17:00 260.50 24-AUG-05:50
September 907.20 01-SEP-00:10 453.60 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 10.84 11-SEP-17:00 341.27 21-SEP-06:30
October 907.20 01-OCT-23:10 453.60 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 343.01 05-OCT-20:03
November 907.20 01-NOV-00:10 453.60 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:10 401.71 28-NOV-23:00
December 907.20 01-DEC-00:10 453.60 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 430.10 29-DEC-21:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   453.60   4572.80   39726.58   0.00 0.00 0.00 0.00   260.50  
Maximum of Months 907.20   453.60   4572.80   39726.58   0.00 0.00 0.00 98.71   481.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1957.67 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 794.49 11-JAN-24:00
February 15368.40 01-FEB-00:10 1957.67 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 713.55 18-FEB-02:00
March 15368.40 01-MAR-00:10 1957.67 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 620.20 08-MAR-07:00
April 15368.40 01-APR-00:10 1957.67 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 38.04 30-APR-18:00 614.86 08-APR-05:00
May 15368.40 01-MAY-00:10 1957.67 01-MAY-19:19 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 5.89 22-MAY-15:00 560.21 06-MAY-05:00
June 15368.40 01-JUN-00:10 1957.67 01-JUN-19:30 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 101.07 13-JUN-17:00 452.51 01-JUN-05:00
July 15368.40 01-JUL-00:10 1957.67 17-JUL-19:30 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 167.73 22-JUL-18:00 440.79 06-JUL-04:00
August 15368.40 01-AUG-00:10 1957.67 01-AUG-19:30 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 104.48 14-AUG-18:00 424.52 24-AUG-05:55
September 15368.40 01-SEP-00:10 1957.67 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 497.42 20-SEP-24:00
October 15368.40 01-OCT-23:10 1957.67 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 568.80 07-OCT-04:00
November 15368.40 01-NOV-00:10 1957.67 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 676.82 29-NOV-02:00
December 15368.40 01-DEC-00:10 1957.67 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 697.32 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1957.67   965.27   0.00 0.00 0.00 0.00 0.00   424.52  
Maximum of Months 15368.40   1957.67   965.27   0.00 0.00 0.00 0.00 167.73   794.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 8554.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 2345.68 11-JAN-24:00
February 45622.98 01-FEB-00:10 8554.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2132.23 17-FEB-07:00
March 45622.98 01-MAR-00:10 8554.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 1882.82 08-MAR-07:00
April 45622.98 01-APR-00:10 8554.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 80.63 30-APR-17:00 1839.77 08-APR-05:00
May 45622.98 01-MAY-00:10 8554.32 01-MAY-19:19 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 67.92 22-MAY-15:00 1682.83 06-MAY-05:00
June 45622.98 01-JUN-00:10 8554.32 01-JUN-19:19 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 280.79 13-JUN-17:00 1369.41 07-JUN-05:00
July 45622.98 01-JUL-00:10 8554.32 17-JUL-19:30 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 449.30 22-JUL-18:00 1303.36 31-JUL-05:00
August 45622.98 01-AUG-00:10 8554.32 01-AUG-19:30 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 274.33 14-AUG-17:00 1245.90 24-AUG-05:55
September 45622.98 01-SEP-00:10 8554.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 1483.98 20-SEP-24:00
October 45622.98 01-OCT-23:10 8554.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1697.93 07-OCT-04:00
November 45622.98 01-NOV-00:10 8554.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2015.56 29-NOV-02:00
December 45622.98 01-DEC-00:10 8554.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 2089.67 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   8554.32   10029.21   0.00 0.00 0.00 0.00 0.00   1245.90  
Maximum of Months 45622.98   8554.32   10029.21   0.00 0.00 0.00 0.00 449.30   2345.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.22 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.17 11-JAN-24:00
February 180.00 01-FEB-00:10 210.22 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.36 17-FEB-07:00
March 180.00 01-MAR-00:10 210.22 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.44 08-MAR-07:00
April 180.00 01-APR-00:10 210.22 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 19.19 30-APR-18:50 155.17 08-APR-06:00
May 180.00 01-MAY-00:10 210.22 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:10 140.90 06-MAY-05:00
June 180.00 01-JUN-00:10 210.22 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.96 13-JUN-17:00 109.57 07-JUN-05:00
July 180.00 01-JUL-00:10 210.22 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.06 22-JUL-18:10 101.98 31-JUL-05:00
August 180.00 01-AUG-00:10 210.22 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.29 20-AUG-05:00
September 180.00 01-SEP-00:10 210.22 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 13-SEP-15:10 117.58 21-SEP-06:00
October 180.00 01-OCT-00:10 210.22 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.94 15-OCT-04:00
November 180.00 01-NOV-00:10 210.22 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.82 29-NOV-02:00
December 180.00 01-DEC-00:10 210.22 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.28 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 0.00   94.29  
Maximum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 57.06   203.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.20 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.16 11-JAN-24:00
February 180.00 01-FEB-00:10 210.20 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.34 17-FEB-07:00
March 180.00 01-MAR-00:10 210.20 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.42 08-MAR-07:00
April 180.00 01-APR-00:10 210.20 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 19.19 30-APR-19:00 155.15 08-APR-06:00
May 180.00 01-MAY-00:10 210.20 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:10 140.89 06-MAY-05:00
June 180.00 01-JUN-00:10 210.20 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.97 13-JUN-17:00 109.56 07-JUN-05:00
July 180.00 01-JUL-00:10 210.20 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 55.53 22-JUL-18:10 101.97 31-JUL-05:00
August 180.00 01-AUG-00:10 210.20 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.28 20-AUG-05:00
September 180.00 01-SEP-00:10 210.20 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 13-SEP-15:10 117.57 21-SEP-06:00
October 180.00 01-OCT-00:10 210.20 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.93 15-OCT-04:00
November 180.00 01-NOV-00:10 210.20 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.81 29-NOV-02:00
December 180.00 01-DEC-00:10 210.20 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.27 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 0.00   94.28  
Maximum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 55.53   203.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 132.12 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 55.78 11-JAN-24:00
February 0.00 01-FEB-00:10 132.12 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 52.05 17-FEB-21:00
March 0.00 01-MAR-00:10 132.12 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 41.49 14-MAR-21:00
April 0.00 01-APR-00:10 132.12 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 1.17 30-APR-19:00 44.15 08-APR-06:00
May 0.00 01-MAY-00:10 132.12 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 1.17 22-MAY-15:00 40.25 07-MAY-05:00
June 0.00 01-JUN-00:10 132.12 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 6.74 13-JUN-17:00 32.93 07-JUN-21:00
July 0.00 01-JUL-00:10 132.12 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 12.16 22-JUL-18:00 30.89 31-JUL-05:00
August 0.00 01-AUG-00:10 132.12 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 6.76 14-AUG-17:50 29.89 24-AUG-06:00
September 0.00 01-SEP-00:10 132.12 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 36.50 20-SEP-24:00
October 0.00 01-OCT-00:10 132.12 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 41.30 07-OCT-04:00
November 0.00 01-NOV-00:10 132.12 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 45.80 28-NOV-21:00
December 0.00 01-DEC-00:10 132.12 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 46.85 26-DEC-20:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   132.12   232.19   0.00 0.00 0.00 0.00 0.00   29.89  
Maximum of Months 0.00   132.12   232.19   0.00 0.00 0.00 0.00 12.16   55.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 132.15 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 56.70 11-JAN-24:00
February 180.00 01-FEB-00:10 132.15 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 52.57 17-FEB-07:00
March 180.00 01-MAR-00:10 132.15 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 45.61 08-MAR-07:00
April 180.00 01-APR-00:10 132.15 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 5.36 30-APR-19:00 43.31 08-APR-06:00
May 180.00 01-MAY-00:10 132.15 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 5.04 22-MAY-15:08 39.32 06-MAY-05:00
June 180.00 01-JUN-00:10 132.15 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 10.88 13-JUN-17:00 30.58 07-JUN-05:00
July 180.00 01-JUL-00:10 132.15 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 15.95 22-JUL-18:10 28.46 31-JUL-05:00
August 180.00 01-AUG-00:10 132.15 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 10.90 14-AUG-17:00 26.31 20-AUG-05:00
September 180.00 01-SEP-00:10 132.15 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 3.48 13-SEP-15:10 32.82 21-SEP-06:00
October 180.00 01-OCT-00:10 132.15 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 39.06 15-OCT-04:00
November 180.00 01-NOV-00:10 132.15 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 48.51 29-NOV-02:00
December 180.00 01-DEC-00:10 132.15 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 50.04 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 0.00   26.31  
Maximum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 15.95   56.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.22 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.17 11-JAN-24:00
February 180.00 01-FEB-00:10 210.22 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.36 17-FEB-07:00
March 180.00 01-MAR-00:10 210.22 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.44 08-MAR-07:00
April 180.00 01-APR-00:10 210.22 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 19.20 30-APR-19:00 155.17 08-APR-06:00
May 180.00 01-MAY-00:10 210.22 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:08 140.90 06-MAY-05:00
June 180.00 01-JUN-00:10 210.22 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.98 13-JUN-17:00 109.57 07-JUN-05:00
July 180.00 01-JUL-00:10 210.22 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.14 22-JUL-18:10 101.98 31-JUL-05:00
August 180.00 01-AUG-00:10 210.22 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.29 20-AUG-05:00
September 180.00 01-SEP-00:10 210.22 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 13-SEP-15:10 117.58 21-SEP-06:00
October 180.00 01-OCT-00:10 210.22 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.94 15-OCT-04:00
November 180.00 01-NOV-00:10 210.22 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.82 29-NOV-02:00
December 180.00 01-DEC-00:10 210.22 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.28 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 0.00   94.29  
Maximum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 57.14   203.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.20 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.16 11-JAN-24:00
February 180.00 01-FEB-00:10 210.20 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.34 17-FEB-07:00
March 180.00 01-MAR-00:10 210.20 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.42 08-MAR-07:00
April 180.00 01-APR-00:10 210.20 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 19.20 30-APR-19:00 155.16 08-APR-06:00
May 180.00 01-MAY-00:10 210.20 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:10 140.89 06-MAY-05:00
June 180.00 01-JUN-00:10 210.20 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.97 13-JUN-17:00 109.56 07-JUN-05:00
July 180.00 01-JUL-00:10 210.20 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 57.13 22-JUL-18:10 101.97 31-JUL-05:00
August 180.00 01-AUG-00:10 210.20 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.28 20-AUG-05:00
September 180.00 01-SEP-00:10 210.20 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 13-SEP-15:10 117.57 21-SEP-06:00
October 180.00 01-OCT-00:10 210.20 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.93 15-OCT-04:00
November 180.00 01-NOV-00:10 210.20 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.81 29-NOV-02:00
December 180.00 01-DEC-00:10 210.20 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.27 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 0.00   94.28  
Maximum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 57.13   203.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1867.32 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 244.68 11-JAN-24:00
February 2263.36 01-FEB-00:10 1867.32 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 226.77 17-FEB-07:00
March 2263.36 01-MAR-00:10 1867.32 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 196.64 08-MAR-07:00
April 2263.36 01-APR-00:10 1867.32 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 10.62 30-APR-17:00 188.68 08-APR-05:00
May 2263.36 01-MAY-00:10 1867.32 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 12.92 22-MAY-15:00 173.00 06-MAY-05:00
June 2263.36 01-JUN-00:10 1867.32 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 33.39 13-JUN-17:00 139.39 01-JUN-05:00
July 2263.36 01-JUL-00:10 1867.32 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 52.47 22-JUL-18:00 133.95 31-JUL-05:00
August 2263.36 01-AUG-00:10 1867.32 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 33.38 14-AUG-17:00 128.09 24-AUG-05:55
September 2263.36 01-SEP-00:10 1867.32 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 1.67 11-SEP-17:00 151.71 20-SEP-24:00
October 2263.36 01-OCT-23:10 1867.32 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 175.43 07-OCT-04:00
November 2263.36 01-NOV-00:10 1867.32 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 209.19 29-NOV-02:00
December 2263.36 01-DEC-00:10 1867.32 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 215.80 29-DEC-21:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 0.00   128.09  
Maximum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 52.47   244.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.22 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.66 11-JAN-24:00
February 180.00 01-FEB-00:10 210.22 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.84 17-FEB-07:00
March 180.00 01-MAR-00:10 210.22 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.91 08-MAR-07:00
April 180.00 01-APR-00:10 210.22 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 18.80 30-APR-19:00 155.64 08-APR-06:00
May 180.00 01-MAY-00:10 210.22 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 17.49 22-MAY-15:10 141.37 06-MAY-05:00
June 180.00 01-JUN-00:10 210.22 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.58 13-JUN-17:00 110.02 07-JUN-05:00
July 180.00 01-JUL-00:10 210.22 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 56.15 22-JUL-18:10 102.43 31-JUL-05:00
August 180.00 01-AUG-00:10 210.22 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.67 14-AUG-17:00 94.73 20-AUG-05:00
September 180.00 01-SEP-00:10 210.22 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.06 13-SEP-15:10 118.04 21-SEP-06:00
October 180.00 01-OCT-00:10 210.22 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 140.41 15-OCT-04:00
November 180.00 01-NOV-00:10 210.22 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 174.31 29-NOV-02:00
December 180.00 01-DEC-00:10 210.22 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.76 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 0.00   94.73  
Maximum of Months 180.00   210.22   237.06   0.00 0.00 0.00 0.00 56.15   203.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 210.20 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.64 11-JAN-24:00
February 180.00 01-FEB-00:10 210.20 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.82 17-FEB-07:00
March 180.00 01-MAR-00:10 210.20 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.90 08-MAR-07:00
April 180.00 01-APR-00:10 210.20 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 18.79 30-APR-19:00 155.63 08-APR-06:00
May 180.00 01-MAY-00:10 210.20 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 17.65 22-MAY-15:10 141.36 06-MAY-05:00
June 180.00 01-JUN-00:10 210.20 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.58 13-JUN-17:00 110.01 07-JUN-05:00
July 180.00 01-JUL-00:10 210.20 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 54.74 22-JUL-18:10 102.42 31-JUL-05:00
August 180.00 01-AUG-00:10 210.20 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.66 14-AUG-17:00 94.73 20-AUG-05:00
September 180.00 01-SEP-00:10 210.20 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.07 13-SEP-15:10 118.03 21-SEP-06:00
October 180.00 01-OCT-00:10 210.20 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 140.40 15-OCT-04:00
November 180.00 01-NOV-00:10 210.20 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 174.30 29-NOV-02:00
December 180.00 01-DEC-00:10 210.20 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.75 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 0.00   94.73  
Maximum of Months 180.00   210.20   237.03   0.00 0.00 0.00 0.00 54.74   203.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 132.15 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 104.20 11-JAN-24:00
February 180.00 01-FEB-00:10 132.15 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 96.62 17-FEB-07:00
March 180.00 01-MAR-00:10 132.15 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 83.86 08-MAR-07:00
April 180.00 01-APR-00:10 132.15 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 9.62 30-APR-19:00 79.63 08-APR-06:00
May 180.00 01-MAY-00:10 132.15 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 9.04 22-MAY-15:10 72.33 06-MAY-05:00
June 180.00 01-JUN-00:10 132.15 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 19.74 13-JUN-17:00 56.29 07-JUN-05:00
July 180.00 01-JUL-00:10 132.15 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 29.04 22-JUL-18:10 52.41 31-JUL-05:00
August 180.00 01-AUG-00:10 132.15 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 19.79 14-AUG-17:00 48.47 20-AUG-05:00
September 180.00 01-SEP-00:10 132.15 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 6.17 13-SEP-15:10 60.39 21-SEP-06:00
October 180.00 01-OCT-00:10 132.15 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 71.84 15-OCT-04:00
November 180.00 01-NOV-00:10 132.15 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 89.18 29-NOV-02:00
December 180.00 01-DEC-00:10 132.15 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 91.97 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 0.00   48.47  
Maximum of Months 180.00   132.15   232.26   0.00 0.00 0.00 0.00 29.04   104.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3437.84 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 549.97 11-JAN-24:00
February 26988.77 01-FEB-00:10 3437.84 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 513.85 17-FEB-07:00
March 26988.77 01-MAR-00:10 3437.84 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 452.20 08-MAR-07:00
April 26988.77 01-APR-00:10 3437.84 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 431.70 08-APR-06:00
May 26988.77 01-MAY-00:10 3437.84 01-MAY-19:19 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 396.99 06-MAY-05:00
June 26988.77 01-JUN-00:10 3437.84 01-JUN-19:30 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 47.22 13-JUN-17:00 319.55 07-JUN-05:00
July 26988.77 01-JUL-00:10 3437.84 17-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 94.82 22-JUL-18:00 304.18 06-JUL-03:57
August 26988.77 01-AUG-00:10 3437.84 01-AUG-19:40 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 47.34 14-AUG-17:00 293.55 24-AUG-05:55
September 26988.77 01-SEP-00:10 3437.84 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 340.09 21-SEP-06:05
October 26988.77 01-OCT-23:10 3437.84 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 393.12 07-OCT-04:00
November 26988.77 01-NOV-00:10 3437.84 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 478.48 29-NOV-02:00
December 26988.77 01-DEC-00:10 3437.84 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 491.22 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 0.00   293.55  
Maximum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 94.82   549.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3437.84 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 549.98 11-JAN-24:00
February 26988.77 01-FEB-00:10 3437.84 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 513.86 17-FEB-07:00
March 26988.77 01-MAR-00:10 3437.84 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 452.20 08-MAR-07:00
April 26988.77 01-APR-00:10 3437.84 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 431.70 08-APR-06:00
May 26988.77 01-MAY-00:10 3437.84 01-MAY-19:19 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 397.00 06-MAY-05:00
June 26988.77 01-JUN-00:10 3437.84 01-JUN-19:30 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 47.22 13-JUN-17:00 320.43 08-JUN-05:55
July 26988.77 01-JUL-00:10 3437.84 17-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 94.82 22-JUL-18:00 304.81 06-JUL-03:57
August 26988.77 01-AUG-00:10 3437.84 01-AUG-19:40 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 47.34 14-AUG-17:00 295.10 24-AUG-05:55
September 26988.77 01-SEP-00:10 3437.84 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 346.95 21-SEP-06:05
October 26988.77 01-OCT-23:10 3437.84 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 394.31 15-OCT-04:00
November 26988.77 01-NOV-00:10 3437.84 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 478.49 29-NOV-02:00
December 26988.77 01-DEC-00:10 3437.84 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 491.22 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 0.00   295.10  
Maximum of Months 26988.77   3437.84   6747.90   0.00 0.00 0.00 0.00 94.82   549.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1210.92 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:10 492.33 11-JAN-24:00
February 2401.70 01-FEB-00:10 1210.92 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 459.95 17-FEB-07:00
March 2401.70 01-MAR-00:10 1210.92 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 404.74 08-MAR-07:00
April 2401.70 01-APR-00:10 1210.92 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 0.00 01-APR-00:10 386.39 08-APR-06:00
May 2401.70 01-MAY-00:10 1210.92 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:10 352.56 06-MAY-05:10
June 2401.70 01-JUN-00:10 1210.92 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 42.45 13-JUN-17:00 311.25 08-JUN-05:55
July 2401.70 01-JUL-00:10 1210.92 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 85.05 22-JUL-18:00 280.80 05-JUL-05:16
August 2401.70 01-AUG-00:10 1210.92 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 42.57 14-AUG-17:00 276.28 24-AUG-05:55
September 2401.70 01-SEP-00:10 1210.92 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 0.00 01-SEP-00:05 340.44 21-SEP-06:30
October 2401.70 01-OCT-23:10 1210.92 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 341.30 06-OCT-07:17
November 2401.70 01-NOV-00:10 1210.92 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:10 410.89 29-NOV-00:10
December 2401.70 01-DEC-00:10 1210.92 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 439.63 29-DEC-21:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1210.92   14912.86   22492.83   0.00 0.00 0.00 0.00   276.28  
Maximum of Months 2401.70   1210.92   14912.86   22492.83   0.00 0.00 0.00 85.05   492.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1976.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 433.96 11-JAN-24:00
February 2395.44 01-FEB-00:10 1976.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 402.25 17-FEB-07:00
March 2395.44 01-MAR-00:10 1976.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 348.95 08-MAR-07:00
April 2395.44 01-APR-00:10 1976.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 9.34 30-APR-18:00 331.26 08-APR-06:00
May 2395.44 01-MAY-00:10 1976.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 7.39 22-MAY-15:00 300.72 06-MAY-05:00
June 2395.44 01-JUN-00:10 1976.27 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 46.85 13-JUN-17:00 241.04 01-JUN-04:00
July 2395.44 01-JUL-00:10 1976.27 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 85.11 22-JUL-18:00 230.00 06-JUL-04:00
August 2395.44 01-AUG-00:10 1976.27 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 51.97 14-AUG-18:00 218.71 24-AUG-05:55
September 2395.44 01-SEP-00:10 1976.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 260.86 20-SEP-24:00
October 2395.44 01-OCT-23:10 1976.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 298.69 15-OCT-04:00
November 2395.44 01-NOV-00:10 1976.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 371.16 29-NOV-02:00
December 2395.44 01-DEC-00:10 1976.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 382.85 29-DEC-21:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 0.00   218.71  
Maximum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 85.11   433.96  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 26569.28 22-JAN-21:00 15335.86 27469.64 18251.11 0.00 0.00 0.00 0.00 0.00 0.00
February 25942.74 22-FEB-07:24 51119.52 85842.36 60837.03 0.00 0.00 0.00 0.00 0.00 0.00
March 25057.81 23-MAR-06:14 51119.52 85842.36 60837.03 0.00 0.00 0.00 0.00 0.00 0.00
April 25129.13 19-APR-06:32 51119.52 85842.36 60837.03 0.00 0.00 0.00 0.00 0.00 0.00
May 26203.50 03-MAY-06:17 20447.81 34336.94 24334.81 0.00 0.00 0.00 0.00 0.00 0.00
June 24823.14 06-JUN-23:17 34505.68 10300.96 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
July 22470.23 06-JUL-04:14 80513.24 24035.57 21292.96 0.00 0.00 0.00 0.00 0.00 0.00
August 20905.28 23-AUG-05:07 26837.75 20602.53 15209.26 0.00 0.00 0.00 0.00 0.00 0.00
September 32343.58 30-SEP-20:26 89459.16 120180.93 81116.04 0.00 0.00 0.00 0.00 0.00 0.00
October 36021.54 05-OCT-20:07 30671.71 41204.45 27376.66 0.00 0.00 0.00 0.00 0.00 0.00
November 35876.33 16-NOV-19:06 89459.16 137348.18 91255.54 0.00 0.00 0.00 0.00 0.00 0.00
December 36205.02 19-DEC-21:32 51119.52 68674.09 45627.77 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 20905.28   15335.86 10300.96 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36205.02   89459.16 137348.18 91255.54 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3657.53 15-JAN-15:03 2598.96 1591.90 2165.06 0.00 0.00 0.00 0.00 0.00 185.94
February 5357.11 04-FEB-14:33 3898.44 1989.87 2525.91 0.00 0.00 0.00 0.00 0.00 183.50
March 3327.73 31-MAR-15:02 3898.44 1193.92 1515.54 0.00 0.00 0.00 0.00 0.00 172.44
April 3417.27 30-APR-12:50 259.90 159.19 216.51 0.00 0.00 0.00 0.00 0.00 23.34
May 3077.43 10-MAY-23:07 3508.60 477.57 649.52 0.00 0.00 0.00 0.00 0.00 173.96
June 2792.76 13-JUN-10:33 779.69 596.96 757.77 0.00 0.00 0.00 0.00 0.00 5.90
July 3336.25 22-JUL-13:30 389.84 198.99 252.59 0.00 0.00 0.00 0.00 45.75 0.00
August 3370.83 19-AUG-13:10 389.84 198.99 252.59 0.00 0.00 0.00 0.00 0.00 39.32
September 4201.04 27-SEP-13:20 259.90 198.99 252.59 0.00 0.00 0.00 0.00 0.00 31.27
October 3812.35 07-OCT-13:10 389.84 198.99 252.59 0.00 0.00 0.00 0.00 0.00 83.31
November 3889.25 17-NOV-09:57 2598.96 3183.80 3608.44 0.00 0.00 0.00 0.00 0.00 196.56
December 4129.81 08-DEC-11:00 2598.96 1989.87 2525.91 0.00 0.00 0.00 0.00 0.00 202.86
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2792.76   259.90 159.19 216.51 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5357.11   3898.44 3183.80 3608.44 0.00 0.00 0.00 0.00 45.75 202.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2137.79 18-JAN-07:14 6019.20 4608.56 5014.30 0.00 0.00 0.00 0.00 0.00 73.61
February 2158.64 22-FEB-07:24 6019.20 4608.56 5014.30 0.00 0.00 0.00 0.00 0.00 74.25
March 2091.49 23-MAR-06:14 6019.20 4608.56 5014.30 0.00 0.00 0.00 0.00 0.00 71.79
April 2155.62 19-APR-06:32 6019.20 4608.56 5014.30 0.00 0.00 0.00 0.00 0.00 75.07
May 2285.04 03-MAY-06:17 2407.68 1843.42 2005.72 0.00 0.00 0.00 0.00 0.00 78.93
June 2210.83 06-JUN-23:17 4062.96 553.03 752.15 0.00 0.00 0.00 0.00 0.00 75.70
July 1952.68 06-JUL-04:14 9480.24 1290.40 1755.01 0.00 0.00 0.00 0.00 0.00 72.51
August 1837.90 30-AUG-03:15 2708.64 184.34 334.29 0.00 0.00 0.00 0.00 0.00 66.87
September 2167.59 20-SEP-21:19 10834.56 4424.22 4680.02 0.00 0.00 0.00 0.00 0.00 76.42
October 2458.40 04-OCT-20:30 3611.52 2212.11 2256.44 0.00 0.00 0.00 0.00 0.00 82.21
November 1989.14 17-NOV-09:57 3009.60 3686.85 4178.59 0.00 0.00 0.00 0.00 0.00 76.05
December 1983.20 08-DEC-11:00 3009.60 2304.28 2925.01 0.00 0.00 0.00 0.00 0.00 74.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1837.90   2407.68 184.34 334.29 0.00 0.00 0.00 0.00 0.00 66.87
Maximum of Months 2458.40   10834.56 4608.56 5014.30 0.00 0.00 0.00 0.00 0.00 82.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1390.83 18-JAN-07:14 1272.96 3712.59 5301.77 0.00 0.00 0.00 0.00 0.00 162.56
February 1399.89 22-FEB-07:24 1272.96 3712.59 5301.77 0.00 0.00 0.00 0.00 0.00 163.76
March 1388.48 23-MAR-06:32 1272.96 3712.59 5301.77 0.00 0.00 0.00 0.00 0.00 160.84
April 1453.01 19-APR-06:32 1272.96 3712.59 5301.77 0.00 0.00 0.00 0.00 0.00 171.37
May 1542.60 03-MAY-06:17 509.18 1485.03 2120.71 0.00 0.00 0.00 0.00 0.00 180.38
June 1469.55 06-JUN-23:17 859.25 445.51 795.27 0.00 0.00 0.00 0.00 0.00 170.56
July 1308.27 06-JUL-04:14 2004.91 1039.52 1855.62 0.00 0.00 0.00 0.00 0.00 165.22
August 1227.95 30-AUG-05:30 445.54 594.01 883.63 0.00 0.00 0.00 0.00 0.00 148.04
September 1443.17 28-SEP-04:17 1145.66 594.01 1060.35 0.00 0.00 0.00 0.00 0.00 171.08
October 1492.08 15-OCT-08:06 795.60 1113.78 1767.26 0.00 0.00 0.00 0.00 0.00 172.00
November 1337.91 03-NOV-08:59 509.18 2376.05 3534.51 0.00 0.00 0.00 0.00 0.00 174.57
December 1241.67 19-DEC-22:45 572.83 891.02 1237.08 0.00 0.00 0.00 0.00 0.00 185.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1227.95   445.54 445.51 795.27 0.00 0.00 0.00 0.00 0.00 148.04
Maximum of Months 1542.60   2004.91 3712.59 5301.77 0.00 0.00 0.00 0.00 0.00 185.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 891.14 18-JAN-07:14 979.20 1883.48 1529.41 0.00 0.00 0.00 0.00 0.00 91.72
February 900.87 22-FEB-07:24 979.20 1883.48 1529.41 0.00 0.00 0.00 0.00 0.00 92.82
March 856.75 25-MAR-23:43 514.08 339.02 305.88 0.00 0.00 0.00 0.00 0.00 88.77
April 919.54 19-APR-06:32 979.20 1883.48 1529.41 0.00 0.00 0.00 0.00 0.00 95.64
May 975.63 03-MAY-06:17 391.68 753.39 611.77 0.00 0.00 0.00 0.00 0.00 100.52
June 931.25 06-JUN-23:17 660.96 226.02 229.41 0.00 0.00 0.00 0.00 0.00 95.24
July 830.67 06-JUL-04:14 1542.24 527.39 535.30 0.00 0.00 0.00 0.00 0.00 92.67
August 776.59 05-AUG-04:13 660.96 113.02 152.94 0.00 0.00 0.00 0.00 0.00 85.24
September 919.41 28-SEP-04:17 881.28 301.36 305.88 0.00 0.00 0.00 0.00 0.00 96.08
October 945.11 01-OCT-02:45 342.72 150.68 152.94 0.00 0.00 0.00 0.00 0.00 95.08
November 789.23 10-NOV-06:37 1713.60 1506.82 1274.51 0.00 0.00 0.00 0.00 0.00 89.84
December 786.46 19-DEC-22:45 440.64 452.04 356.86 0.00 0.00 0.00 0.00 0.00 104.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 776.59   342.72 113.02 152.94 0.00 0.00 0.00 0.00 0.00 85.24
Maximum of Months 975.63   1713.60 1883.48 1529.41 0.00 0.00 0.00 0.00 0.00 104.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 49365.91 30-JAN-20:34 7056.00 4536.05 45728.01 397265.76 0.00 0.00 0.00 0.00 293.78
February 50049.68 01-FEB-20:50 7056.00 4536.05 45728.01 397265.76 0.00 0.00 0.00 0.00 299.09
March 51346.94 29-MAR-20:26 8064.00 4032.04 43321.27 376357.04 0.00 0.00 0.00 0.00 303.20
April 49160.83 19-APR-20:53 8064.00 4032.04 43321.27 376357.04 0.00 0.00 0.00 0.00 291.66
May 49395.80 04-MAY-20:54 8064.00 4032.04 43321.27 376357.04 0.00 0.00 0.00 0.00 293.08
June 42680.07 06-JUN-21:08 7257.60 2419.23 26955.46 234177.71 0.00 0.00 0.00 0.00 250.98
July 38450.76 21-JUL-20:00 705.60 453.60 4572.80 39726.58 0.00 0.00 0.00 0.00 43.99
August 38338.69 14-AUG-20:00 705.60 453.60 4572.80 39726.58 0.00 0.00 0.00 0.00 48.41
September 49354.05 30-SEP-20:26 7056.00 3528.04 38507.80 334539.59 0.00 0.00 0.00 0.00 268.46
October 50269.96 04-OCT-19:49 5644.80 3628.84 36582.41 317812.61 0.00 0.00 0.00 0.00 292.95
November 53828.32 16-NOV-19:27 6350.40 3628.84 38989.14 338721.34 0.00 0.00 0.00 0.00 285.92
December 50676.56 07-DEC-19:37 7056.00 4032.04 43321.27 376357.04 0.00 0.00 0.00 0.00 306.81
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 38338.69   705.60 453.60 4572.80 39726.58 0.00 0.00 0.00 0.00 43.99
Maximum of Months 53828.32   8064.00 4536.05 45728.01 397265.76 0.00 0.00 0.00 0.00 306.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15087.77 18-JAN-07:14 68304.00 10875.96 6096.46 0.00 0.00 0.00 0.00 0.00 390.81
February 21814.35 04-FEB-14:33 51228.00 1196.36 3556.27 0.00 0.00 0.00 0.00 0.00 405.47
March 13718.02 25-MAR-23:43 35859.60 1957.67 1219.29 0.00 0.00 0.00 0.00 0.00 374.37
April 15582.43 28-APR-00:30 46105.20 978.84 762.06 0.00 0.00 0.00 0.00 0.00 421.66
May 15658.98 11-MAY-04:47 46105.20 1135.45 914.47 0.00 0.00 0.00 0.00 0.00 399.42
June 16086.43 06-JUN-23:17 46105.20 1305.12 914.47 0.00 0.00 0.00 0.00 0.00 413.41
July 14336.30 15-JUL-04:05 30736.80 435.04 406.43 0.00 0.00 0.00 0.00 0.00 376.21
August 13766.23 30-AUG-03:15 30736.80 435.04 406.43 0.00 0.00 0.00 0.00 0.00 375.81
September 18480.64 28-SEP-04:40 30736.80 870.08 609.65 0.00 0.00 0.00 0.00 0.00 404.79
October 16756.67 02-OCT-02:53 46105.20 652.56 609.65 0.00 0.00 0.00 0.00 0.00 368.07
November 15404.48 17-NOV-09:57 34152.00 1914.17 5080.38 0.00 0.00 0.00 0.00 0.00 440.30
December 16294.36 08-DEC-11:00 34152.00 1196.36 3556.27 0.00 0.00 0.00 0.00 0.00 453.03
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13718.02   30736.80 435.04 406.43 0.00 0.00 0.00 0.00 0.00 368.07
Maximum of Months 21814.35   68304.00 10875.96 6096.46 0.00 0.00 0.00 0.00 0.00 453.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 46429.58 18-JAN-07:14 202768.80 47524.00 63342.37 0.00 0.00 0.00 0.00 0.00 1230.27
February 47000.91 22-FEB-07:24 202768.80 46415.10 63342.37 0.00 0.00 0.00 0.00 0.00 1243.21
March 44928.24 23-MAR-06:14 202768.80 47524.00 63342.37 0.00 0.00 0.00 0.00 0.00 1187.66
April 56462.66 22-APR-00:15 91245.96 3801.92 6334.24 0.00 0.00 0.00 0.00 0.00 1258.31
May 65440.67 01-MAY-02:26 410606.82 8554.32 19002.71 0.00 0.00 0.00 0.00 0.00 1301.92
June 57953.60 22-JUN-06:00 70969.08 6716.73 10557.06 0.00 0.00 0.00 0.00 0.00 994.43
July 52167.04 15-JUL-04:05 91245.96 1900.96 4222.82 0.00 0.00 0.00 0.00 0.00 1160.26
August 51643.48 20-AUG-03:55 70969.08 3801.92 6334.24 0.00 0.00 0.00 0.00 0.00 1104.01
September 54522.06 30-SEP-23:05 70969.08 5702.88 8445.65 0.00 0.00 0.00 0.00 0.00 1214.85
October 58925.07 01-OCT-03:47 106453.62 5702.88 9501.36 0.00 0.00 0.00 0.00 0.00 1269.20
November 43482.32 17-NOV-09:57 101384.40 32696.51 52785.31 0.00 0.00 0.00 0.00 0.00 1276.62
December 43803.14 08-DEC-11:00 101384.40 20435.32 36949.72 0.00 0.00 0.00 0.00 0.00 1258.99
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 43482.32   70969.08 1900.96 4222.82 0.00 0.00 0.00 0.00 0.00 994.43
Maximum of Months 65440.67   410606.82 47524.00 63342.37 0.00 0.00 0.00 0.00 0.00 1301.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2751.12 25-JAN-16:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 88.80
February 3543.01 18-FEB-16:01 378.00 485.62 387.20 0.00 0.00 0.00 0.00 0.00 120.11
March 3416.70 20-MAR-18:01 1247.40 1683.90 1090.47 0.00 0.00 0.00 0.00 0.00 100.20
April 3726.28 28-APR-19:01 1386.00 2102.25 1633.07 0.00 0.00 0.00 0.00 0.00 78.11
May 4101.94 25-MAY-17:02 583.20 845.10 758.59 0.00 0.00 0.00 0.00 0.00 85.47
June 4140.93 22-JUN-19:01 1386.00 2102.25 1633.07 0.00 0.00 0.00 0.00 0.00 79.26
July 4039.38 14-JUL-18:01 1386.00 1871.00 1211.63 0.00 0.00 0.00 0.00 0.00 75.52
August 4065.70 01-AUG-19:31 1386.00 2102.25 1633.07 0.00 0.00 0.00 0.00 0.00 74.33
September 4215.47 29-SEP-16:01 972.00 588.63 1264.31 0.00 0.00 0.00 0.00 0.00 77.01
October 3818.01 05-OCT-17:12 583.20 845.10 758.59 0.00 0.00 0.00 0.00 0.00 69.86
November 3559.28 03-NOV-15:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 97.53
December 435.82 21-DEC-16:04 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 103.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 435.82   378.00 485.62 387.20 0.00 0.00 0.00 0.00 0.00 69.86
Maximum of Months 4215.47   1386.00 2102.25 1633.07 0.00 0.00 0.00 0.00 0.00 120.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1029.36 19-JAN-16:02 583.20 353.14 300.24 0.00 0.00 0.00 0.00 0.00 97.06
February 2605.67 19-FEB-16:02 324.00 416.20 331.84 0.00 0.00 0.00 0.00 0.00 115.70
March 3017.84 20-MAR-18:01 1247.40 1683.70 1090.34 0.00 0.00 0.00 0.00 0.00 97.91
April 3559.71 20-APR-18:01 1386.00 1870.78 1211.49 0.00 0.00 0.00 0.00 0.00 70.68
May 3642.14 25-MAY-17:21 680.40 985.84 884.92 0.00 0.00 0.00 0.00 0.00 74.38
June 3760.83 22-JUN-19:01 1386.00 2102.00 1632.88 0.00 0.00 0.00 0.00 0.00 79.68
July 3659.35 28-JUL-18:11 1386.00 1870.78 1211.49 0.00 0.00 0.00 0.00 0.00 82.08
August 3645.84 01-AUG-19:31 1386.00 2102.00 1632.88 0.00 0.00 0.00 0.00 0.00 74.69
September 3590.25 29-SEP-16:01 972.00 588.56 1264.17 0.00 0.00 0.00 0.00 0.00 70.18
October 3235.33 07-OCT-15:02 324.00 416.20 331.84 0.00 0.00 0.00 0.00 0.00 24.46
November 1375.76 10-NOV-16:01 680.40 411.99 350.28 0.00 0.00 0.00 0.00 0.00 77.09
December 103.13 02-DEC-08:61 954.00 1177.12 2370.31 0.00 0.00 0.00 0.00 0.00 106.94
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 103.13   324.00 353.14 300.24 0.00 0.00 0.00 0.00 0.00 24.46
Maximum of Months 3760.83   1386.00 2102.00 2370.31 0.00 0.00 0.00 0.00 0.00 115.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 389.20 21-JAN-11:30 0.00 87.20 67.08 0.00 0.00 0.00 0.00 0.00 34.96
February 308.20 04-FEB-14:21 0.00 435.99 335.39 0.00 0.00 0.00 0.00 0.00 28.53
March 87.51 25-MAR-11:50 0.00 87.20 67.08 0.00 0.00 0.00 0.00 0.00 19.95
April 640.72 30-APR-12:50 0.00 43.60 33.54 0.00 0.00 0.00 0.00 0.00 2.60
May 487.32 23-MAY-13:20 0.00 36.99 30.96 0.00 0.00 0.00 0.00 0.00 9.68
June 513.60 13-JUN-13:20 0.00 36.99 30.96 0.00 0.00 0.00 0.00 1.86 0.00
July 592.79 22-JUL-13:30 0.00 43.60 33.54 0.00 0.00 0.00 0.00 8.56 0.00
August 631.58 20-AUG-13:00 0.00 43.60 33.54 0.00 0.00 0.00 0.00 0.00 0.72
September 773.89 27-SEP-13:20 0.00 36.99 30.96 0.00 0.00 0.00 0.00 0.00 3.88
October 699.70 07-OCT-13:10 0.00 43.60 33.54 0.00 0.00 0.00 0.00 0.00 12.29
November 330.91 11-NOV-13:30 0.00 43.60 33.54 0.00 0.00 0.00 0.00 0.00 28.67
December 101.10 18-DEC-14:30 0.00 36.99 30.96 0.00 0.00 0.00 0.00 0.00 30.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 87.51   0.00 36.99 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 773.89   0.00 435.99 335.39 0.00 0.00 0.00 0.00 8.56 34.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 815.11 29-JAN-09:01 378.00 518.04 1119.99 0.00 0.00 0.00 0.00 0.00 20.47
February 355.47 01-FEB-19:03 1386.00 1176.17 1187.08 0.00 0.00 0.00 0.00 0.00 30.41
March 879.86 20-MAR-18:01 1247.40 1058.56 1068.37 0.00 0.00 0.00 0.00 0.00 26.88
April 944.46 20-APR-18:01 1386.00 1176.17 1187.08 0.00 0.00 0.00 0.00 0.00 16.45
May 977.97 11-MAY-19:31 1386.00 1321.54 1599.98 0.00 0.00 0.00 0.00 0.00 17.34
June 982.27 22-JUN-19:01 1386.00 1321.54 1599.98 0.00 0.00 0.00 0.00 0.00 18.60
July 1031.43 22-JUL-08:41 486.00 666.06 1439.98 0.00 0.00 0.00 0.00 1.63 0.00
August 966.07 03-AUG-19:31 1386.00 1321.54 1599.98 0.00 0.00 0.00 0.00 0.00 18.56
September 933.41 13-SEP-19:31 1386.00 1321.54 1599.98 0.00 0.00 0.00 0.00 0.00 15.06
October 882.60 05-OCT-18:01 970.20 823.32 830.96 0.00 0.00 0.00 0.00 0.00 21.79
November 749.70 25-NOV-09:01 540.00 740.06 1599.98 0.00 0.00 0.00 0.00 0.00 28.27
December 389.31 24-DEC-09:02 324.00 444.04 959.99 0.00 0.00 0.00 0.00 0.00 27.66
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 355.47   324.00 444.04 830.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1031.43   1386.00 1321.54 1599.98 0.00 0.00 0.00 0.00 1.63 30.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1097.62 21-JAN-16:02 324.00 416.24 331.88 0.00 0.00 0.00 0.00 0.00 111.62
February 2992.01 04-FEB-16:01 378.00 485.62 387.20 0.00 0.00 0.00 0.00 0.00 102.16
March 1760.49 20-MAR-15:01 680.40 412.04 350.32 0.00 0.00 0.00 0.00 0.00 73.71
April 3691.65 28-APR-08:51 360.00 924.99 1132.61 0.00 0.00 0.00 0.00 0.00 64.26
May 3808.63 23-MAY-08:51 360.00 924.99 1132.61 0.00 0.00 0.00 0.00 0.00 43.65
June 3804.68 12-JUN-08:51 360.00 924.99 1132.61 0.00 0.00 0.00 0.00 0.00 43.47
July 4054.26 22-JUL-08:22 324.00 706.35 979.84 0.00 0.00 0.00 0.00 0.00 18.52
August 3886.76 14-AUG-08:51 360.00 924.99 1132.61 0.00 0.00 0.00 0.00 0.00 29.79
September 3887.20 13-SEP-08:51 360.00 924.99 1132.61 0.00 0.00 0.00 0.00 0.00 43.26
October 3284.58 07-OCT-15:02 324.00 416.24 331.88 0.00 0.00 0.00 0.00 0.00 24.56
November 3011.64 03-NOV-15:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 89.67
December 348.12 11-DEC-09:05 216.00 554.99 679.57 0.00 0.00 0.00 0.00 0.00 127.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 348.12   216.00 412.04 331.88 0.00 0.00 0.00 0.00 0.00 18.52
Maximum of Months 4054.26   972.00 924.99 1132.61 0.00 0.00 0.00 0.00 0.00 127.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 583.79 21-JAN-09:04 270.00 588.56 816.44 0.00 0.00 0.00 0.00 0.00 129.32
February 1426.85 20-FEB-09:02 324.00 706.27 979.73 0.00 0.00 0.00 0.00 0.00 128.53
March 632.30 30-MAR-18:03 1386.00 1870.78 1211.49 0.00 0.00 0.00 0.00 0.00 101.87
April 3337.70 28-APR-08:51 360.00 924.88 1132.48 0.00 0.00 0.00 0.00 0.00 62.88
May 3488.75 23-MAY-08:51 360.00 924.88 1132.48 0.00 0.00 0.00 0.00 0.00 43.92
June 3537.54 13-JUN-08:32 180.00 462.44 566.24 0.00 0.00 0.00 0.00 0.00 33.13
July 3721.19 22-JUL-08:22 324.00 706.27 979.73 0.00 0.00 0.00 0.00 0.00 19.13
August 3577.11 14-AUG-08:51 360.00 924.88 1132.48 0.00 0.00 0.00 0.00 0.00 29.93
September 3441.20 23-SEP-08:51 540.00 1177.12 1632.88 0.00 0.00 0.00 0.00 0.00 55.10
October 2810.97 07-OCT-15:02 324.00 416.20 331.84 0.00 0.00 0.00 0.00 0.00 18.94
November 681.38 25-NOV-09:02 540.00 1177.12 1632.88 0.00 0.00 0.00 0.00 0.00 99.92
December 313.77 02-DEC-09:06 270.00 588.56 816.44 0.00 0.00 0.00 0.00 0.00 101.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 313.77   180.00 416.20 331.84 0.00 0.00 0.00 0.00 0.00 18.94
Maximum of Months 3721.19   1386.00 1870.78 1632.88 0.00 0.00 0.00 0.00 0.00 129.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2857.08 20-JAN-15:46 7544.52 5186.99 0.00 0.00 0.00 0.00 0.00 0.00 120.35
February 3119.50 13-FEB-15:08 7544.52 5186.99 0.00 0.00 0.00 0.00 0.00 0.00 129.50
March 2758.61 25-MAR-23:16 17603.88 6224.39 0.00 0.00 0.00 0.00 0.00 0.00 117.06
April 3396.79 19-APR-06:32 10059.36 10373.99 0.00 0.00 0.00 0.00 0.00 0.00 128.27
May 3660.14 03-MAY-06:17 4023.74 4149.60 0.00 0.00 0.00 0.00 0.00 0.00 136.77
June 3470.01 06-JUN-23:17 6790.07 1244.88 0.00 0.00 0.00 0.00 0.00 0.00 128.76
July 3088.92 06-JUL-04:14 15843.49 2904.72 0.00 0.00 0.00 0.00 0.00 0.00 124.95
August 2940.92 05-AUG-04:13 6790.07 622.44 0.00 0.00 0.00 0.00 0.00 0.00 116.78
September 3474.73 28-SEP-04:17 9053.42 1659.84 0.00 0.00 0.00 0.00 0.00 0.00 131.51
October 3545.28 01-OCT-02:45 3520.78 829.92 0.00 0.00 0.00 0.00 0.00 0.00 129.39
November 2880.05 10-NOV-06:37 17603.88 8299.19 0.00 0.00 0.00 0.00 0.00 0.00 119.25
December 2907.90 19-DEC-22:45 4526.71 2489.76 0.00 0.00 0.00 0.00 0.00 0.00 139.56
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2758.61   3520.78 622.44 0.00 0.00 0.00 0.00 0.00 0.00 116.78
Maximum of Months 3660.14   17603.88 10373.99 0.00 0.00 0.00 0.00 0.00 0.00 139.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2872.02 25-JAN-16:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 88.57
February 3712.37 09-FEB-16:01 680.40 412.04 350.32 0.00 0.00 0.00 0.00 0.00 105.42
March 3634.15 20-MAR-18:01 1247.40 1683.90 1090.47 0.00 0.00 0.00 0.00 0.00 102.01
April 4117.00 28-APR-18:42 831.60 1122.60 726.98 0.00 0.00 0.00 0.00 0.00 86.21
May 4373.67 23-MAY-19:42 831.60 1261.35 979.84 0.00 0.00 0.00 0.00 0.00 85.40
June 4539.78 22-JUN-18:42 831.60 1122.60 726.98 0.00 0.00 0.00 0.00 0.00 85.71
July 4611.07 11-JUL-18:52 831.60 1122.60 726.98 0.00 0.00 0.00 0.00 0.00 88.12
August 4333.70 01-AUG-19:12 831.60 1261.35 979.84 0.00 0.00 0.00 0.00 0.00 81.48
September 4442.99 29-SEP-16:01 972.00 588.63 1264.31 0.00 0.00 0.00 0.00 0.00 77.99
October 4088.51 05-OCT-17:12 583.20 845.10 758.59 0.00 0.00 0.00 0.00 0.00 72.63
November 3708.19 03-NOV-15:01 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 97.24
December 484.32 21-DEC-16:04 972.00 588.63 500.46 0.00 0.00 0.00 0.00 0.00 103.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 484.32   583.20 412.04 350.32 0.00 0.00 0.00 0.00 0.00 72.63
Maximum of Months 4611.07   1247.40 1683.90 1264.31 0.00 0.00 0.00 0.00 0.00 105.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 687.62 15-JAN-16:03 378.00 485.56 387.15 0.00 0.00 0.00 0.00 0.00 105.89
February 2495.52 27-FEB-16:02 583.20 353.14 300.24 0.00 0.00 0.00 0.00 0.00 97.75
March 3172.36 20-MAR-18:01 1247.40 1683.70 1090.34 0.00 0.00 0.00 0.00 0.00 99.22
April 3638.15 28-APR-18:42 831.60 1122.47 726.90 0.00 0.00 0.00 0.00 0.00 84.04
May 3963.14 23-MAY-19:42 831.60 1261.20 979.73 0.00 0.00 0.00 0.00 0.00 85.96
June 4110.29 22-JUN-18:42 831.60 1122.47 726.90 0.00 0.00 0.00 0.00 0.00 86.52
July 4181.12 11-JUL-18:52 831.60 1122.47 726.90 0.00 0.00 0.00 0.00 0.00 88.83
August 3914.29 01-AUG-19:12 831.60 1261.20 979.73 0.00 0.00 0.00 0.00 0.00 81.19
September 3758.22 14-SEP-18:01 1386.00 1870.78 1211.49 0.00 0.00 0.00 0.00 0.00 76.84
October 3362.02 07-OCT-15:02 324.00 416.20 331.84 0.00 0.00 0.00 0.00 0.00 24.66
November 905.93 03-NOV-15:02 972.00 588.56 500.40 0.00 0.00 0.00 0.00 0.00 89.75
December 102.47 02-DEC-08:61 954.00 1177.12 2370.31 0.00 0.00 0.00 0.00 0.00 107.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 102.47   324.00 353.14 300.24 0.00 0.00 0.00 0.00 0.00 24.66
Maximum of Months 4181.12   1386.00 1870.78 2370.31 0.00 0.00 0.00 0.00 0.00 107.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2303.61 11-JAN-16:01 680.40 259.02 343.22 0.00 0.00 0.00 0.00 0.00 92.39
February 2388.22 24-FEB-16:01 972.00 370.03 490.32 0.00 0.00 0.00 0.00 0.00 61.32
March 2307.17 20-MAR-15:01 680.40 259.02 343.22 0.00 0.00 0.00 0.00 0.00 42.17
April 2395.11 07-APR-15:01 972.00 370.03 490.32 0.00 0.00 0.00 0.00 0.00 50.41
May 2536.95 11-MAY-19:31 1386.00 1321.54 1599.98 0.00 0.00 0.00 0.00 0.00 35.67
June 2462.45 22-JUN-19:01 1386.00 1321.54 1599.98 0.00 0.00 0.00 0.00 0.00 35.99
July 2480.63 06-JUL-20:31 1602.00 1176.17 1780.62 0.00 0.00 0.00 0.00 0.00 34.99
August 2532.34 20-AUG-20:11 1386.00 1321.54 1780.62 0.00 0.00 0.00 0.00 0.00 35.41
September 2689.89 29-SEP-16:01 972.00 370.03 1238.69 0.00 0.00 0.00 0.00 0.00 38.29
October 2527.46 07-OCT-17:32 583.20 673.99 743.22 0.00 0.00 0.00 0.00 0.00 41.44
November 2403.58 03-NOV-15:01 972.00 370.03 490.32 0.00 0.00 0.00 0.00 0.00 51.74
December 2140.22 18-DEC-16:02 486.00 185.02 245.16 0.00 0.00 0.00 0.00 0.00 60.68
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2140.22   486.00 185.02 245.16 0.00 0.00 0.00 0.00 0.00 34.99
Maximum of Months 2689.89   1602.00 1321.54 1780.62 0.00 0.00 0.00 0.00 0.00 92.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 30898.35 29-JAN-23:23 167930.11 8021.63 47235.32 0.00 0.00 0.00 0.00 0.00 307.26
February 29604.61 07-FEB-22:10 134943.84 11459.46 33739.51 0.00 0.00 0.00 0.00 0.00 301.94
March 30948.68 29-MAR-20:26 239900.16 30558.57 67479.03 0.00 0.00 0.00 0.00 0.00 328.33
April 35555.94 26-APR-22:18 134943.84 5729.73 33739.51 0.00 0.00 0.00 0.00 0.00 306.20
May 32374.13 11-MAY-04:32 161932.61 4583.79 13495.81 0.00 0.00 0.00 0.00 0.00 299.25
June 30684.95 07-JUN-24:00 134943.84 3819.82 11246.50 0.00 0.00 0.00 0.00 0.00 301.54
July 31299.01 06-JUL-04:20 188921.38 5347.75 15745.11 0.00 0.00 0.00 0.00 0.00 287.92
August 30213.97 30-AUG-03:30 242898.91 3437.84 20243.71 0.00 0.00 0.00 0.00 0.00 254.56
September 30553.42 20-SEP-22:47 242898.91 10313.52 60731.12 0.00 0.00 0.00 0.00 0.00 301.63
October 33922.07 04-OCT-22:30 107955.07 4583.79 26991.61 0.00 0.00 0.00 0.00 0.00 321.41
November 31599.94 14-NOV-04:41 188921.38 2673.88 15745.11 0.00 0.00 0.00 0.00 0.00 284.49
December 31055.34 04-DEC-23:37 269887.68 11459.46 67479.03 0.00 0.00 0.00 0.00 0.00 297.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 29604.61   107955.07 2673.88 11246.50 0.00 0.00 0.00 0.00 0.00 254.56
Maximum of Months 35555.94   269887.68 30558.57 67479.03 0.00 0.00 0.00 0.00 0.00 328.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 32579.08 29-JAN-23:23 167930.11 8021.63 47235.32 0.00 0.00 0.00 0.00 0.00 308.74
February 31492.73 07-FEB-22:37 80966.30 6875.68 20243.71 0.00 0.00 0.00 0.00 0.00 303.61
March 32558.20 29-MAR-20:26 239900.16 30558.57 67479.03 0.00 0.00 0.00 0.00 0.00 329.36
April 38325.52 26-APR-22:18 134943.84 5729.73 33739.51 0.00 0.00 0.00 0.00 0.00 306.35
May 33958.47 11-MAY-04:32 161932.61 4583.79 13495.81 0.00 0.00 0.00 0.00 0.00 299.66
June 33156.54 07-JUN-24:00 134943.84 3819.82 11246.50 0.00 0.00 0.00 0.00 0.00 302.25
July 32908.03 06-JUL-04:20 188921.38 5347.75 15745.11 0.00 0.00 0.00 0.00 0.00 288.81
August 31724.17 30-AUG-03:30 242898.91 3437.84 20243.71 0.00 0.00 0.00 0.00 0.00 255.12
September 32151.83 08-SEP-03:53 188921.38 2673.88 15745.11 0.00 0.00 0.00 0.00 0.00 300.36
October 36750.32 04-OCT-22:30 107955.07 4583.79 26991.61 0.00 0.00 0.00 0.00 0.00 321.61
November 33207.93 14-NOV-04:41 188921.38 2673.88 15745.11 0.00 0.00 0.00 0.00 0.00 285.27
December 32624.32 04-DEC-23:37 269887.68 11459.46 67479.03 0.00 0.00 0.00 0.00 0.00 297.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 31492.73   80966.30 2673.88 11246.50 0.00 0.00 0.00 0.00 0.00 255.12
Maximum of Months 38325.52   269887.68 30558.57 67479.03 0.00 0.00 0.00 0.00 0.00 329.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37344.33 30-JAN-16:58 13342.80 3363.68 149128.56 224928.32 0.00 0.00 0.00 0.00 253.41
February 36607.63 12-FEB-11:31 5603.98 2825.49 104389.99 131208.19 0.00 0.00 0.00 0.00 294.99
March 38026.91 23-MAR-06:32 10674.24 6727.35 149128.56 112464.16 0.00 0.00 0.00 0.00 247.15
April 37377.27 12-APR-08:41 4269.70 4305.51 119302.85 89971.33 0.00 0.00 0.00 0.00 244.04
May 35451.74 10-MAY-06:36 7471.97 4709.15 104389.99 78724.91 0.00 0.00 0.00 0.00 273.10
June 33548.49 07-JUN-09:26 5337.12 3363.68 149128.56 187440.26 0.00 0.00 0.00 0.00 248.32
July 32226.12 05-JUL-06:00 16811.93 4843.69 112960.17 67478.50 0.00 0.00 0.00 0.00 241.10
August 32205.62 30-AUG-06:07 10674.24 6727.35 149128.56 112464.16 0.00 0.00 0.00 0.00 230.47
September 35936.45 21-SEP-06:54 9606.82 6054.62 134215.70 101217.74 0.00 0.00 0.00 0.00 273.07
October 37008.16 31-OCT-06:10 6404.54 4036.41 89477.13 67478.50 0.00 0.00 0.00 0.00 237.42
November 38420.58 16-NOV-19:27 16811.93 9687.39 134215.70 134956.99 0.00 0.00 0.00 0.00 293.94
December 40479.17 08-DEC-11:00 5337.12 3363.68 149128.56 187440.26 0.00 0.00 0.00 0.00 265.24
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 32205.62   4269.70 2825.49 89477.13 67478.50 0.00 0.00 0.00 0.00 230.47
Maximum of Months 40479.17   16811.93 9687.39 149128.56 224928.32 0.00 0.00 0.00 0.00 294.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5983.21 20-JAN-15:46 7984.80 5489.63 0.00 0.00 0.00 0.00 0.00 0.00 217.88
February 6601.13 13-FEB-15:08 7984.80 5489.63 0.00 0.00 0.00 0.00 0.00 0.00 236.48
March 6017.49 11-MAR-16:03 7984.80 5489.63 0.00 0.00 0.00 0.00 0.00 0.00 219.90
April 6739.34 28-APR-00:13 7186.32 988.13 0.00 0.00 0.00 0.00 0.00 0.00 227.65
May 7106.47 03-MAY-06:17 4258.56 4391.71 0.00 0.00 0.00 0.00 0.00 0.00 231.37
June 6922.40 06-JUN-23:17 7186.32 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 223.49
July 6105.84 06-JUL-04:14 16768.08 3074.19 0.00 0.00 0.00 0.00 0.00 0.00 215.62
August 5716.12 30-AUG-03:15 4790.88 439.17 0.00 0.00 0.00 0.00 0.00 0.00 197.80
September 6733.40 28-SEP-04:17 9581.76 1756.68 0.00 0.00 0.00 0.00 0.00 0.00 222.43
October 6858.21 01-OCT-02:20 5589.36 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 217.65
November 5809.86 18-NOV-01:44 11977.20 2195.85 0.00 0.00 0.00 0.00 0.00 0.00 229.07
December 5417.79 17-DEC-13:28 2129.28 1756.68 0.00 0.00 0.00 0.00 0.00 0.00 218.78
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5417.79   2129.28 439.17 0.00 0.00 0.00 0.00 0.00 0.00 197.80
Maximum of Months 7106.47   16768.08 5489.63 0.00 0.00 0.00 0.00 0.00 0.00 236.48



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.387415E+12 253899.50 27-JAN-20:19 0.553296E+12 527721.50 22-JAN-18:30
February 0.347869E+12 252948.62 28-FEB-20:19 0.484815E+12 513747.92 20-FEB-18:40
March 0.380177E+12 253277.82 29-MAR-19:30 0.534226E+12 497063.60 08-MAR-18:49
April 0.382758E+12 296702.45 30-APR-18:19 0.471392E+12 463362.36 10-APR-17:30
May 0.392255E+12 275912.07 31-MAY-19:00 0.487714E+12 459416.25 05-MAY-20:10
June 0.393403E+12 323204.60 12-JUN-18:10 0.441297E+12 394277.13 07-JUN-20:00
July 0.421466E+12 332236.78 22-JUL-18:19 0.440205E+12 377294.49 04-JUL-21:40
August 0.428395E+12 316247.44 14-AUG-18:10 0.433728E+12 353834.19 14-AUG-17:10
September 0.401774E+12 292197.91 13-SEP-19:49 0.435843E+12 405652.40 30-SEP-20:10
October 0.388403E+12 263161.26 03-OCT-19:19 0.509564E+12 452093.94 23-OCT-20:00
November 0.372394E+12 254565.22 20-NOV-20:00 0.535239E+12 496625.14 12-NOV-19:00
December 0.388833E+12 251047.69 13-DEC-20:40 0.565864E+12 521671.30 05-DEC-18:49
             
Annual Sum or Average 0.468514E+13     0.589318E+13    
Minimum of Months 0.347869E+12 251047.69   0.433728E+12 353834.19  
Maximum of Months 0.428395E+12 332236.78   0.565864E+12 527721.50  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.747103E+11 0.286107E+11 0.140828E+12 0.552136E+11 0.438017E+11 0.394160E+10 0.00 0.181454E+10 0.00 0.00 0.255481E+11 0.770462E+10 0.00
February 0.671281E+11 0.235435E+11 0.127191E+12 0.498703E+11 0.393103E+11 0.403773E+10 0.00 0.199214E+10 0.00 0.00 0.230980E+11 0.696218E+10 0.00
March 0.738859E+11 0.229126E+11 0.140882E+12 0.552167E+11 0.436155E+11 0.407422E+10 0.00 0.212312E+10 0.00 0.00 0.245117E+11 0.770304E+10 0.00
April 0.708773E+11 0.189870E+11 0.136245E+12 0.534310E+11 0.438715E+11 0.641694E+10 0.00 0.200610E+11 0.00 0.00 0.203278E+11 0.746488E+10 0.00
May 0.726305E+11 0.168239E+11 0.140860E+12 0.552136E+11 0.457252E+11 0.703448E+10 0.00 0.214655E+11 0.00 0.00 0.195159E+11 0.770439E+10 0.00
June 0.699807E+11 0.147910E+11 0.136336E+12 0.534336E+11 0.453772E+11 0.750775E+10 0.00 0.410492E+11 0.00 0.00 0.123293E+11 0.745688E+10 0.00
July 0.724499E+11 0.159427E+11 0.140770E+12 0.552099E+11 0.475001E+11 0.793488E+10 0.00 0.592988E+11 0.00 0.00 0.935557E+10 0.771267E+10 0.00
August 0.729921E+11 0.183761E+11 0.140892E+12 0.552159E+11 0.471813E+11 0.801490E+10 0.00 0.653395E+11 0.00 0.00 0.736131E+10 0.770445E+10 0.00
September 0.712816E+11 0.207895E+11 0.136256E+12 0.534315E+11 0.457049E+11 0.762890E+10 0.00 0.433035E+11 0.00 0.00 0.107772E+11 0.746644E+10 0.00
October 0.742932E+11 0.247552E+11 0.140818E+12 0.552132E+11 0.449424E+11 0.531298E+10 0.00 0.921140E+10 0.00 0.00 0.208656E+11 0.770288E+10 0.00
November 0.722708E+11 0.268181E+11 0.136330E+12 0.534335E+11 0.429930E+11 0.382294E+10 0.00 0.182568E+10 0.00 0.00 0.223629E+11 0.744893E+10 0.00
December 0.749212E+11 0.293818E+11 0.140770E+12 0.552121E+11 0.449204E+11 0.377224E+10 0.00 0.111043E+10 0.00 0.00 0.257959E+11 0.771281E+10 0.00
                           
Annual Sum or Average 0.867422E+12 0.261732E+12 0.165818E+13 0.650095E+12 0.534944E+12 0.694996E+11 0.00 0.268595E+12 0.00 0.00 0.221849E+12 0.907442E+11 0.00
Minimum of Months 0.671281E+11 0.147910E+11 0.127191E+12 0.498703E+11 0.393103E+11 0.377224E+10 0.00 0.111043E+10 0.00 0.00 0.736131E+10 0.696218E+10 0.00
Maximum of Months 0.749212E+11 0.293818E+11 0.140892E+12 0.552167E+11 0.475001E+11 0.801490E+10 0.00 0.653395E+11 0.00 0.00 0.257959E+11 0.771281E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.109878E+12 0.00 0.291500E+12 0.00 0.00
February 0.137204E+12 0.00 0.831220E+11 0.00 0.264490E+12 0.00 0.00
March 0.152024E+12 0.00 0.905923E+11 0.00 0.291610E+12 0.00 0.00
April 0.146956E+12 0.00 0.458120E+11 0.00 0.278624E+12 0.00 0.00
May 0.151978E+12 0.00 0.528711E+11 0.00 0.282865E+12 0.00 0.00
June 0.147114E+12 0.00 0.253534E+11 0.00 0.268830E+12 0.00 0.00
July 0.151820E+12 0.00 0.143945E+11 0.00 0.273990E+12 0.00 0.00
August 0.152039E+12 0.00 0.902346E+10 0.00 0.272666E+12 0.00 0.00
September 0.146971E+12 0.00 0.237497E+11 0.00 0.265122E+12 0.00 0.00
October 0.151903E+12 0.00 0.800353E+11 0.00 0.277625E+12 0.00 0.00
November 0.147091E+12 0.00 0.114585E+12 0.00 0.273563E+12 0.00 0.00
December 0.151820E+12 0.00 0.126293E+12 0.00 0.287751E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.775710E+12 0.00 0.332863E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.902346E+10 0.00 0.264490E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.126293E+12 0.00 0.291610E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 71560.59 02-JAN-20:10 16690.39 01-JAN-00:10 89171.45 02-JAN-07:10 39721.54 02-JAN-07:19 28147.91 17-JAN-21:30 3604.17 19-JAN-07:00 0.00 01-JAN-00:10
February 71560.59 01-FEB-20:10 16690.39 01-FEB-00:10 89171.45 01-FEB-07:10 39721.54 01-FEB-07:19 27530.04 01-FEB-21:40 3580.90 10-FEB-09:39 0.00 01-FEB-00:10
March 71560.59 01-MAR-20:10 16690.39 01-MAR-00:10 89171.45 01-MAR-07:10 39721.54 01-MAR-07:19 25716.81 16-MAR-20:30 3579.85 31-MAR-09:20 0.00 01-MAR-00:10
April 71560.59 03-APR-19:10 16690.39 01-APR-00:10 89171.45 03-APR-06:10 39721.54 10-APR-06:19 36218.88 14-APR-20:00 3611.32 29-APR-15:09 0.00 01-APR-00:10
May 71560.59 01-MAY-19:19 16690.39 01-MAY-00:10 89171.45 01-MAY-06:10 39719.36 01-MAY-06:19 41877.08 19-MAY-21:19 3536.72 28-MAY-23:10 0.00 01-MAY-00:10
June 71560.59 01-JUN-19:30 16690.39 01-JUN-00:10 89171.45 01-JUN-06:10 39718.92 15-JUN-06:19 32858.41 26-JUN-21:19 3909.78 12-JUN-18:10 0.00 01-JUN-00:10
July 71560.59 17-JUL-19:30 16690.39 01-JUL-00:10 89171.45 03-JUL-06:10 39719.09 25-JUL-06:19 32021.68 24-JUL-20:19 4118.18 22-JUL-18:10 0.00 01-JUL-00:10
August 71560.59 01-AUG-19:40 16690.39 01-AUG-00:10 89171.45 01-AUG-06:10 39721.06 15-AUG-06:19 31687.04 17-AUG-21:30 4471.33 14-AUG-18:10 0.00 01-AUG-00:10
September 71560.59 01-SEP-19:10 16690.39 01-SEP-00:10 89171.45 01-SEP-06:10 39721.54 18-SEP-06:19 32180.62 11-SEP-21:10 3913.98 25-SEP-15:09 0.00 01-SEP-00:10
October 71560.59 02-OCT-19:10 16690.39 01-OCT-00:10 89171.45 02-OCT-06:10 39721.54 02-OCT-06:19 36973.40 06-OCT-20:49 3590.86 31-OCT-06:00 0.00 01-OCT-00:10
November 71560.59 01-NOV-19:10 16690.39 01-NOV-00:10 89171.45 01-NOV-06:10 39721.54 01-NOV-06:19 35809.58 16-NOV-22:49 3591.63 13-NOV-07:00 0.00 01-NOV-00:10
December 71560.59 01-DEC-20:10 16690.39 01-DEC-00:10 89171.45 01-DEC-07:10 39721.54 01-DEC-07:19 30602.41 22-DEC-20:19 3593.52 05-DEC-07:19 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 71560.59   16690.39   89171.45   39718.92   25716.81   3536.72   0.00  
Maximum of Months 71560.59   16690.39   89171.45   39721.54   41877.08   4471.33   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 9858.70 21-JAN-10:00 0.00 0.00 9938.94 01-JAN-00:10 4738.17 26-JAN-19:10 0.00
February 10950.80 19-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 4738.50 13-FEB-19:10 0.00
March 7551.50 23-MAR-18:10 0.00 0.00 9938.94 01-MAR-00:20 4738.56 20-MAR-06:00 0.00
April 88114.82 30-APR-18:10 0.00 0.00 9938.94 01-APR-00:10 4738.56 28-APR-18:49 0.00
May 84465.74 22-MAY-15:09 0.00 0.00 9938.94 01-MAY-00:10 4738.37 09-MAY-06:49 0.00
June 108364.67 12-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 4738.54 02-JUN-18:10 0.00
July 120944.72 22-JUL-18:10 0.00 0.00 9938.94 01-JUL-00:10 4738.27 17-JUL-06:10 0.00
August 100382.98 14-AUG-18:10 0.00 0.00 9938.94 01-AUG-00:10 4738.42 30-AUG-06:10 0.00
September 84836.46 13-SEP-15:09 0.00 0.00 9938.94 01-SEP-00:10 4738.47 05-SEP-06:19 0.00
October 52102.14 07-OCT-15:09 0.00 0.00 9938.94 01-OCT-00:10 4738.54 31-OCT-06:19 0.00
November 9742.80 24-NOV-11:50 0.00 0.00 9938.94 01-NOV-00:10 4738.50 14-NOV-07:00 0.00
December 5792.80 01-DEC-21:00 0.00 0.00 9938.94 01-DEC-00:20 4738.49 04-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 5792.80   0.00 0.00 9938.94   4738.17   0.00
Maximum of Months 120944.72   0.00 0.00 9938.94   4738.56   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 253899.50 27-JAN-20:19 71560.59 86439.81 16690.39 32090.84 26320.82 3434.61 0.00 1623.45 0.00
February 252948.62 28-FEB-20:19 71560.59 86439.81 16690.39 32090.84 25772.57 3299.28 0.00 1376.69 0.00
March 253277.82 29-MAR-19:30 71560.59 86439.81 16690.39 32090.84 23806.64 3219.54 0.00 3119.24 0.00
April 296702.45 30-APR-18:19 56968.49 74651.16 0.00 31717.38 26052.22 3525.00 0.00 87608.71 0.00
May 275912.07 31-MAY-19:00 71560.59 86439.81 16690.39 32090.84 26329.38 3013.45 0.00 32349.98 0.00
June 323204.60 12-JUN-18:10 58770.64 77573.37 0.00 31786.42 25706.91 3909.78 0.00 108364.67 0.00
July 332236.78 22-JUL-18:19 56968.49 74651.16 0.00 31717.38 27645.05 4096.39 0.00 120773.29 0.00
August 316247.44 14-AUG-18:10 58948.06 77573.37 0.00 31786.42 26018.05 4471.33 0.00 100382.98 0.00
September 292197.91 13-SEP-19:49 71560.59 86439.81 16690.39 32090.84 28761.33 3112.30 0.00 47247.12 0.00
October 263161.26 03-OCT-19:19 71560.59 86439.81 16690.39 32090.84 30086.11 3167.94 0.00 10188.45 0.00
November 254565.22 20-NOV-20:00 71560.59 86439.81 16690.39 32090.84 27386.57 3272.02 0.00 1242.69 0.00
December 251047.69 13-DEC-20:40 71560.59 86439.81 16690.39 32090.84 27844.24 525.68 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 251047.69   56968.49 74651.16 0.00 31717.38 23806.64 525.68 0.00 0.00 0.00
Maximum of Months 332236.78   71560.59 86439.81 16690.39 32090.84 30086.11 4471.33 0.00 120773.29 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 169424.94 24-JAN-07:19 0.00 294007.95 25-JAN-21:49 0.00
February 104248.32 01-FEB-18:10 0.00 172916.33 26-FEB-23:00 0.00 296341.77 27-FEB-21:30 0.00
March 104248.32 01-MAR-18:10 0.00 154409.52 18-MAR-02:39 0.00 291378.72 31-MAR-20:10 0.00
April 104248.32 01-APR-17:10 0.00 151942.45 02-APR-07:30 0.00 287247.93 03-APR-20:40 0.00
May 104248.32 01-MAY-17:10 0.00 148493.33 14-MAY-03:39 0.00 284408.05 12-MAY-17:40 0.00
June 104248.32 01-JUN-17:10 0.00 137218.84 06-JUN-23:00 0.00 272303.37 02-JUN-20:00 0.00
July 104248.32 01-JUL-17:10 0.00 151499.92 05-JUL-04:30 0.00 264191.12 03-JUL-20:19 0.00
August 104248.32 01-AUG-17:10 0.00 129903.14 30-AUG-05:00 0.00 250538.20 23-AUG-20:19 0.00
September 104248.32 01-SEP-17:10 0.00 139729.43 17-SEP-05:30 0.00 257770.99 28-SEP-17:00 0.00
October 104248.32 02-OCT-17:10 0.00 163430.60 21-OCT-02:00 0.00 283352.32 24-OCT-20:40 0.00
November 104248.32 01-NOV-17:10 0.00 162735.04 25-NOV-02:49 0.00 280047.55 06-NOV-21:00 0.00
December 104248.32 01-DEC-18:10 0.00 180675.89 02-DEC-16:10 0.00 287140.10 28-DEC-21:19 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 129903.14   0.00 250538.20   0.00
Maximum of Months 104248.32   0.00 180675.89   0.00 296341.77   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 20.50 25.17 20.50 25.17
February 0.00 0.00 0.00 0.00 19.50 25.23 19.50 25.23
March 0.00 0.00 0.00 0.00 39.50 25.14 39.50 25.14
April 0.00 0.00 0.00 0.00 29.00 25.04 29.00 25.04
May 0.00 0.00 0.00 0.00 34.00 25.05 34.00 25.05
June 0.00 0.00 0.00 0.00 4.33 25.00 4.33 25.00
July 0.00 0.00 0.00 0.00 2.17 24.75 2.17 24.75
August 0.00 0.00 0.00 0.00 0.83 24.70 0.83 24.70
September 0.00 0.00 0.00 0.00 8.67 25.08 8.67 25.08
October 0.00 0.00 0.00 0.00 44.33 25.06 44.33 25.06
November 0.00 0.00 0.00 0.00 47.83 24.99 47.83 24.99
December 0.00 0.00 0.00 0.00 18.33 25.19 18.33 25.19
                 
Annual Sum or Average 0.00   0.00   269.00 25.08 269.00 25.08
Minimum of Months 0.00 0.00 0.00 0.00 0.83 24.70 0.83 24.70
Maximum of Months 0.00 0.00 0.00 0.00 47.83 25.23 47.83 25.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.67 20.50 3.67 20.50 0.00 20.50 0.00 20.50
February 0.67 20.53 0.67 20.53 0.00 20.53 0.00 20.53
March 0.17 20.50 0.17 20.50 0.00 20.50 0.00 20.50
April 0.00 0.00 0.00 0.00 1.33 21.83 1.33 21.83
May 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
June 0.00 0.00 0.00 0.00 1.67 22.03 1.67 22.03
July 0.00 0.00 0.00 0.00 3.67 21.96 3.67 21.96
August 0.00 0.00 0.00 0.00 2.67 21.83 2.67 21.83
September 0.00 0.00 0.00 0.00 1.33 21.85 1.33 21.85
October 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
November 1.17 20.49 1.17 20.49 0.00 20.49 0.00 20.49
December 6.67 20.49 6.67 20.49 0.00 20.49 0.00 20.49
                 
Annual Sum or Average 12.33 20.50 12.33 20.50 11.67 20.95 11.67 21.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 20.49 0.00 20.49
Maximum of Months 6.67 20.53 6.67 20.53 3.67 22.03 3.67 22.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.33 20.46 5.33 20.46 0.00 20.46 0.00 20.46
February 1.67 20.51 1.67 20.51 0.00 20.51 0.00 20.51
March 0.67 20.52 0.67 20.52 0.00 20.52 0.00 20.52
April 0.00 0.00 0.00 0.00 0.67 21.84 0.67 21.84
May 0.00 0.00 0.00 0.00 0.50 21.87 0.50 21.87
June 0.00 0.00 0.00 0.00 1.67 22.11 1.67 22.11
July 0.00 0.00 0.00 0.00 3.50 22.02 3.50 22.02
August 0.00 0.00 0.00 0.00 1.83 21.80 1.83 21.80
September 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 3.33 20.49 3.33 20.49 0.00 20.49 0.00 20.49
December 11.83 20.47 11.83 20.47 0.00 20.47 0.00 20.47
                 
Annual Sum or Average 22.83 20.48 22.83 20.48 8.67 20.71 8.67 20.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11.83 20.52 11.83 20.52 3.50 22.11 3.50 22.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 20.24 1.67 20.24 0.00 20.24 0.00 20.24
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
May 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
June 0.00 0.00 0.00 0.00 1.17 21.84 1.17 21.84
July 0.00 0.00 0.00 0.00 2.67 21.79 2.67 21.79
August 0.00 0.00 0.00 0.00 0.67 21.68 0.67 21.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 20.43 0.33 20.43 0.00 20.43 0.00 20.43
December 1.67 20.37 1.67 20.37 0.00 20.37 0.00 20.37
                 
Annual Sum or Average 3.67 20.32 3.67 20.32 4.83 20.90 4.83 21.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 20.43 1.67 20.43 2.67 21.84 2.67 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.83 20.49 2.83 20.49 0.00 20.49 0.00 20.49
February 0.83 20.52 0.83 20.52 0.00 20.52 0.00 20.52
March 0.17 20.49 0.17 20.49 0.00 20.49 0.00 20.49
April 0.00 0.00 0.00 0.00 0.33 22.36 0.33 22.36
May 0.00 0.00 0.00 0.00 0.33 22.40 0.33 22.40
June 0.00 0.00 0.00 0.00 1.33 22.22 1.33 22.22
July 0.00 0.00 0.00 0.00 2.17 22.24 2.17 22.24
August 0.00 0.00 0.00 0.00 2.17 22.21 2.17 22.21
September 0.00 0.00 0.00 0.00 1.33 22.23 1.33 22.23
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.50 20.50 1.50 20.50 0.00 20.50 0.00 20.50
December 6.00 20.48 6.00 20.48 0.00 20.48 0.00 20.48
                 
Annual Sum or Average 11.33 20.49 11.33 20.49 7.67 20.93 7.67 21.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.00 20.52 6.00 20.52 2.17 22.40 2.17 22.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 20.46 6.17 20.46 0.00 20.46 0.00 20.46
February 2.33 20.51 2.33 20.51 0.00 20.51 0.00 20.51
March 1.00 20.51 1.00 20.51 0.00 20.51 0.00 20.51
April 0.00 0.00 0.00 0.00 0.33 22.33 0.33 22.33
May 0.00 0.00 0.00 0.00 0.33 22.49 0.33 22.49
June 0.00 0.00 0.00 0.00 1.67 22.22 1.67 22.22
July 0.00 0.00 0.00 0.00 2.50 22.28 2.50 22.28
August 0.00 0.00 0.00 0.00 2.17 22.20 2.17 22.20
September 0.00 0.00 0.00 0.00 1.33 22.10 1.33 22.10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.83 20.48 2.83 20.48 0.00 20.48 0.00 20.48
December 10.50 20.47 10.50 20.47 0.00 20.47 0.00 20.47
                 
Annual Sum or Average 22.83 20.47 22.83 20.47 8.33 20.74 8.33 20.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.50 20.51 10.50 20.51 2.50 22.49 2.50 22.49



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 20.53 2.33 20.53 0.00 20.53 0.00 20.53
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.00 21.95 2.00 21.95
May 0.00 0.00 0.00 0.00 1.17 21.98 1.17 21.98
June 0.00 0.00 0.00 0.00 2.17 22.12 2.17 22.12
July 0.00 0.00 0.00 0.00 4.17 22.07 4.17 22.07
August 0.00 0.00 0.00 0.00 4.00 21.89 4.00 21.89
September 0.00 0.00 0.00 0.00 2.50 21.84 2.50 21.84
October 0.00 0.00 0.00 0.00 0.17 21.81 0.17 21.81
November 0.50 20.49 0.50 20.49 0.00 20.49 0.00 20.49
December 3.33 20.49 3.33 20.49 0.00 20.49 0.00 20.49
                 
Annual Sum or Average 6.17 20.50 6.17 20.50 16.17 21.34 16.17 21.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.33 20.53 3.33 20.53 4.17 22.12 4.17 22.12



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.67 20.46 3.67 20.46 0.00 20.46 0.00 20.46
February 0.33 20.55 0.33 20.55 0.00 20.55 0.00 20.55
March 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
April 0.00 0.00 0.00 0.00 1.17 21.97 1.17 21.97
May 0.00 0.00 0.00 0.00 1.33 21.93 1.33 21.93
June 0.00 0.00 0.00 0.00 2.50 22.20 2.50 22.20
July 0.00 0.00 0.00 0.00 5.00 22.07 5.00 22.07
August 0.00 0.00 0.00 0.00 2.83 21.92 2.83 21.92
September 0.00 0.00 0.00 0.00 0.67 21.88 0.67 21.88
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.83 20.50 1.83 20.50 0.00 20.50 0.00 20.50
December 7.50 20.49 7.50 20.49 0.00 20.49 0.00 20.49
                 
Annual Sum or Average 13.50 20.48 13.50 20.48 13.50 21.00 13.50 21.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.50 20.55 7.50 20.55 5.00 22.20 5.00 22.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.51 0.33 20.51 0.00 20.51 0.00 20.51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 21.78 0.67 21.78
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
July 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
August 0.00 0.00 0.00 0.00 0.83 21.75 0.83 21.75
September 0.00 0.00 0.00 0.00 2.67 21.85 2.67 21.85
October 0.00 0.00 0.00 0.00 0.33 21.78 0.33 21.78
November 0.33 20.51 0.33 20.51 0.00 20.51 0.00 20.51
December 2.00 20.50 2.00 20.50 0.00 20.50 0.00 20.50
                 
Annual Sum or Average 2.67 20.50 2.67 20.50 5.00 21.13 5.00 21.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 20.51 2.00 20.51 2.67 21.85 2.67 21.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.67 24.67 0.67 24.67
February 0.00 0.00 0.00 0.00 0.33 24.91 0.33 24.91
March 0.00 0.00 0.00 0.00 2.50 24.74 2.50 24.74
April 0.00 0.00 0.00 0.00 2.00 24.65 2.00 24.65
May 0.00 0.00 0.00 0.00 4.17 24.75 4.17 24.75
June 0.00 0.00 0.00 0.00 1.17 24.66 1.17 24.66
July 0.00 0.00 0.00 0.00 0.17 24.57 0.17 24.57
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.83 24.62 0.83 24.62
October 0.00 0.00 0.00 0.00 5.50 24.70 5.50 24.70
November 0.00 0.00 0.00 0.00 2.67 24.77 2.67 24.77
December 0.00 0.00 0.00 0.00 1.17 24.82 1.17 24.82
                 
Annual Sum or Average 0.00   0.00   21.17 24.72 21.17 24.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.50 24.91 5.50 24.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.33 24.77 1.33 24.77
February 0.00 0.00 0.00 0.00 1.33 24.90 1.33 24.90
March 0.00 0.00 0.00 0.00 3.67 24.80 3.67 24.80
April 0.00 0.00 0.00 0.00 3.50 24.75 3.50 24.75
May 0.00 0.00 0.00 0.00 6.50 24.76 6.50 24.76
June 0.00 0.00 0.00 0.00 2.00 24.66 2.00 24.66
July 0.00 0.00 0.00 0.00 0.17 24.61 0.17 24.61
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.67 24.67 1.67 24.67
October 0.00 0.00 0.00 0.00 8.17 24.73 8.17 24.73
November 0.00 0.00 0.00 0.00 5.17 24.73 5.17 24.73
December 0.00 0.00 0.00 0.00 1.50 24.86 1.50 24.86
                 
Annual Sum or Average 0.00   0.00   35.00 24.75 35.00 24.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.17 24.90 8.17 24.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 43.33 25.05 43.33 25.05
February 0.00 0.00 0.00 0.00 31.50 25.20 31.50 25.20
March 0.00 0.00 0.00 0.00 56.00 25.08 56.00 25.08
April 0.00 0.00 0.00 0.00 44.00 25.03 44.00 25.03
May 0.00 0.00 0.00 0.00 54.50 25.00 54.50 25.00
June 0.00 0.00 0.00 0.00 12.67 24.97 12.67 24.97
July 0.00 0.00 0.00 0.00 3.33 24.84 3.33 24.84
August 0.00 0.00 0.00 0.00 2.50 24.82 2.50 24.82
September 0.00 0.00 0.00 0.00 16.33 25.01 16.33 25.01
October 0.00 0.00 0.00 0.00 72.33 24.95 72.33 24.95
November 0.00 0.00 0.00 0.00 66.50 25.03 66.50 25.03
December 0.00 0.00 0.00 0.00 37.83 25.15 37.83 25.15
                 
Annual Sum or Average 0.00   0.00   440.83 25.04 440.83 25.04
Minimum of Months 0.00 0.00 0.00 0.00 2.50 24.82 2.50 24.82
Maximum of Months 0.00 0.00 0.00 0.00 72.33 25.20 72.33 25.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 740.00 23.25 0.00 23.25 0.00 23.25
February 672.00 23.10 0.00 23.10 0.00 23.10
March 744.00 22.91 0.00 22.91 0.00 22.91
April 720.00 22.90 0.00 22.90 0.00 22.90
May 744.00 22.90 0.00 22.90 0.00 22.90
June 719.33 22.96 0.00 22.96 0.00 22.96
July 690.33 23.13 0.00 23.13 0.00 23.13
August 644.67 23.21 3.67 23.21 0.00 23.21
September 479.33 23.40 7.83 23.41 0.00 23.41
October 520.17 23.53 2.00 23.53 0.00 23.53
November 556.00 23.58 0.00 23.58 0.00 23.58
December 716.50 23.50 0.00 23.50 0.00 23.50
             
Annual Sum or Average 7946.33 23.17 13.50 23.18 0.00 23.18
Minimum of Months 479.33 22.90 0.00 22.90 0.00 22.90
Maximum of Months 744.00 23.58 7.83 23.58 0.00 23.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 730.00 21.08 139.83 21.08 138.00 21.07
February 648.83 21.10 35.83 21.12 29.50 21.11
March 744.00 21.03 32.50 21.03 32.50 21.03
April 648.67 21.30 38.17 21.44 0.00 21.44
May 695.50 21.25 16.33 21.31 0.00 21.31
June 658.83 21.29 24.50 21.37 0.00 21.37
July 633.00 21.40 71.33 21.62 0.00 21.62
August 598.83 21.47 111.00 21.83 0.00 21.83
September 562.00 21.41 123.83 21.85 0.00 21.85
October 683.83 21.16 39.17 21.31 0.00 21.31
November 707.67 21.08 31.67 21.09 29.67 21.08
December 740.83 21.05 233.33 21.04 233.33 21.03
             
Annual Sum or Average 8052.00 21.21 897.50 21.32 463.00 21.30
Minimum of Months 562.00 21.03 16.33 21.03 0.00 21.03
Maximum of Months 744.00 21.47 233.33 21.85 233.33 21.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.83 0.00 21.83 0.00 21.83
February 672.00 21.92 0.00 21.92 0.00 21.92
March 744.00 21.93 0.00 21.93 0.00 21.93
April 692.67 22.61 0.00 22.61 0.00 22.61
May 701.67 22.65 3.67 22.66 0.00 22.66
June 596.33 22.79 30.33 22.85 0.00 22.85
July 517.00 22.85 83.67 23.00 0.00 23.00
August 512.83 22.96 69.67 23.08 0.00 23.08
September 557.83 22.94 41.83 23.01 0.00 23.01
October 730.67 22.43 0.00 22.43 0.00 22.43
November 720.00 22.02 0.00 22.02 0.00 22.02
December 744.00 21.62 0.00 21.62 0.00 21.62
             
Annual Sum or Average 7933.00 22.33 229.17 22.38 0.00 22.38
Minimum of Months 512.83 21.62 0.00 21.62 0.00 21.62
Maximum of Months 744.00 22.96 83.67 23.08 0.00 23.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.10 33.17 21.09 33.17 21.09
February 672.00 21.09 0.00 21.09 0.00 21.09
March 744.00 21.17 0.00 21.17 0.00 21.17
April 720.00 21.84 0.00 21.84 0.00 21.84
May 744.00 22.06 0.00 22.06 0.00 22.06
June 716.67 22.57 0.00 22.57 0.00 22.57
July 725.33 22.82 0.00 22.82 0.00 22.82
August 741.00 22.88 0.00 22.88 0.00 22.88
September 720.00 22.62 0.00 22.62 0.00 22.62
October 744.00 21.74 0.00 21.74 0.00 21.74
November 720.00 21.24 0.00 21.24 0.00 21.24
December 744.00 21.04 10.17 21.04 10.17 21.04
             
Annual Sum or Average 8735.00 21.85 43.33 21.84 43.33 21.84
Minimum of Months 672.00 21.04 0.00 21.04 0.00 21.04
Maximum of Months 744.00 22.88 33.17 22.88 33.17 22.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 62.17 21.01 62.17 21.01
February 672.00 21.01 0.00 21.01 0.00 21.01
March 744.00 21.03 0.00 21.03 0.00 21.03
April 720.00 21.47 0.00 21.47 0.00 21.47
May 744.00 21.67 0.00 21.67 0.00 21.67
June 720.00 22.21 0.00 22.21 0.00 22.21
July 744.00 22.48 0.00 22.48 0.00 22.48
August 744.00 22.51 0.00 22.51 0.00 22.51
September 720.00 22.23 0.00 22.23 0.00 22.23
October 744.00 21.36 0.00 21.36 0.00 21.36
November 720.00 21.04 0.00 21.04 0.00 21.04
December 744.00 21.00 22.17 21.00 22.17 21.00
             
Annual Sum or Average 8760.00 21.59 84.33 21.58 84.33 21.58
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.51 62.17 22.51 62.17 22.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 250.00 23.22 578.00 23.42 169.67 23.55
February 231.33 23.25 543.33 23.41 160.83 23.54
March 269.33 23.38 610.33 23.47 190.50 23.62
April 272.50 23.59 610.67 23.50 217.00 23.64
May 298.50 23.78 648.00 23.54 256.67 23.68
June 292.83 23.82 651.17 23.47 273.33 23.59
July 297.17 23.90 687.50 23.47 287.50 23.59
August 295.83 23.92 683.33 23.46 288.33 23.58
September 285.83 23.87 650.17 23.52 269.00 23.63
October 299.50 23.73 647.17 23.56 248.67 23.71
November 261.17 23.52 596.67 23.52 196.17 23.67
December 242.50 23.14 567.50 23.40 159.67 23.53
             
Annual Sum or Average 3296.50 23.61 7473.83 23.48 2717.33 23.61
Minimum of Months 231.33 23.14 543.33 23.40 159.67 23.53
Maximum of Months 299.50 23.92 687.50 23.56 288.33 23.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 715.67 21.46 13.17 21.50 0.83 21.50
February 631.50 21.54 23.17 21.61 0.00 21.61
March 743.33 21.48 0.00 21.48 0.00 21.48
April 585.83 22.10 66.33 22.26 0.00 22.26
May 641.83 22.08 47.33 22.17 0.00 22.17
June 573.17 22.19 85.50 22.33 8.83 22.35
July 436.00 22.19 172.83 22.53 0.33 22.53
August 356.00 22.34 224.50 22.81 2.17 22.82
September 372.17 22.34 226.50 22.85 0.00 22.85
October 647.67 21.89 61.83 22.05 0.00 22.05
November 696.50 21.59 9.67 21.62 0.00 21.62
December 733.83 21.31 8.83 21.32 6.67 21.31
             
Annual Sum or Average 7133.50 21.81 939.67 22.01 18.83 22.01
Minimum of Months 356.00 21.31 0.00 21.32 0.00 21.31
Maximum of Months 743.33 22.34 226.50 22.85 8.83 22.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.83 22.21 0.00 22.21 0.00 22.21
February 672.00 22.30 0.00 22.30 0.00 22.30
March 744.00 22.27 0.00 22.27 0.00 22.27
April 633.00 22.85 1.67 22.85 0.00 22.85
May 608.17 22.79 19.83 22.83 0.00 22.83
June 418.67 22.78 98.33 22.99 8.50 23.00
July 329.67 22.83 226.17 23.26 2.50 23.26
August 226.17 22.83 255.00 23.39 1.33 23.39
September 276.67 22.94 184.50 23.31 4.00 23.32
October 656.17 22.68 0.00 22.68 0.00 22.68
November 719.33 22.39 0.00 22.39 0.00 22.39
December 744.00 22.00 0.00 22.00 0.00 22.00
             
Annual Sum or Average 6771.67 22.50 785.50 22.64 16.33 22.64
Minimum of Months 226.17 22.00 0.00 22.00 0.00 22.00
Maximum of Months 744.00 22.94 255.00 23.39 8.50 23.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.81 418.33 20.72 418.33 20.67
February 672.00 20.95 273.33 20.83 273.33 20.77
March 744.00 20.88 266.50 20.80 266.50 20.75
April 688.67 21.48 28.33 21.58 16.50 21.61
May 700.50 21.53 34.17 21.74 11.83 21.84
June 637.17 21.74 60.50 22.11 22.50 22.28
July 600.17 22.03 132.50 22.73 49.33 23.04
August 559.50 21.92 126.33 22.59 30.50 22.80
September 597.83 21.59 79.33 22.02 11.00 22.10
October 731.83 21.15 45.67 21.09 44.83 21.02
November 720.00 20.86 267.83 20.74 267.83 20.67
December 744.00 20.64 627.67 20.60 627.67 20.59
             
Annual Sum or Average 8139.67 21.26 2360.50 21.32 2040.17 21.26
Minimum of Months 559.50 20.64 28.33 20.60 11.00 20.59
Maximum of Months 744.00 22.03 627.67 22.73 627.67 23.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.62 542.17 20.55 542.17 20.52
February 672.00 20.71 434.67 20.63 434.67 20.59
March 744.00 20.79 379.67 20.70 379.67 20.65
April 701.67 21.31 36.17 21.36 25.67 21.35
May 712.17 21.43 29.67 21.61 8.83 21.67
June 655.67 21.70 54.17 22.03 18.67 22.17
July 621.33 21.93 113.00 22.56 38.33 22.81
August 606.83 21.82 93.33 22.31 15.50 22.42
September 650.33 21.49 39.83 21.70 1.17 21.71
October 744.00 20.99 81.67 20.89 81.67 20.81
November 720.00 20.69 401.17 20.57 401.17 20.52
December 744.00 20.52 698.33 20.50 698.33 20.50
             
Annual Sum or Average 8316.00 21.14 2903.83 21.12 2645.83 21.04
Minimum of Months 606.83 20.52 29.67 20.50 1.17 20.50
Maximum of Months 744.00 21.93 698.33 22.56 698.33 22.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.87 238.67 20.78 238.67 20.72
February 672.00 20.92 137.83 20.82 137.83 20.75
March 744.00 21.02 47.83 20.99 47.83 20.96
April 720.00 21.24 0.00 21.24 0.00 21.24
May 744.00 21.32 0.00 21.32 0.00 21.32
June 718.83 21.50 0.00 21.50 0.00 21.50
July 742.83 21.66 0.00 21.66 0.00 21.66
August 744.00 21.61 0.00 21.61 0.00 21.61
September 720.00 21.35 0.00 21.35 0.00 21.35
October 744.00 21.09 0.00 21.09 0.00 21.09
November 720.00 20.94 106.67 20.86 106.67 20.80
December 744.00 20.83 253.33 20.70 253.33 20.62
             
Annual Sum or Average 8757.67 21.20 784.33 21.13 784.33 21.07
Minimum of Months 672.00 20.83 0.00 20.70 0.00 20.62
Maximum of Months 744.00 21.66 253.33 21.66 253.33 21.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.81 415.50 20.72 415.50 20.67
February 672.00 20.93 276.33 20.83 276.33 20.78
March 744.00 20.91 260.50 20.83 260.50 20.78
April 684.33 21.56 16.67 21.58 10.17 21.57
May 695.00 21.55 11.33 21.59 0.00 21.59
June 607.00 21.56 31.67 21.73 1.33 21.74
July 548.83 21.62 53.67 21.89 4.17 21.93
August 512.50 21.60 48.67 21.86 0.33 21.86
September 582.00 21.56 33.67 21.73 0.00 21.73
October 744.00 21.23 39.33 21.16 39.33 21.10
November 720.00 20.85 276.67 20.74 276.67 20.67
December 744.00 20.66 611.67 20.61 611.67 20.60
             
Annual Sum or Average 7997.67 21.20 2075.67 21.14 1896.00 21.05
Minimum of Months 512.50 20.66 11.33 20.61 0.00 20.60
Maximum of Months 744.00 21.62 611.67 21.89 611.67 21.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.62 545.00 20.55 545.00 20.52
February 672.00 20.69 483.33 20.63 483.33 20.60
March 744.00 20.82 365.67 20.74 365.67 20.70
April 711.17 21.50 14.50 21.50 12.00 21.49
May 719.17 21.53 6.50 21.56 0.00 21.56
June 646.33 21.64 28.33 21.78 1.17 21.79
July 638.83 21.84 34.50 22.00 3.67 22.03
August 645.00 21.92 19.67 22.00 0.00 22.00
September 696.67 21.75 6.33 21.78 0.00 21.78
October 744.00 21.04 63.67 20.96 63.67 20.88
November 720.00 20.68 407.00 20.57 407.00 20.52
December 744.00 20.54 672.17 20.51 672.17 20.50
             
Annual Sum or Average 8425.17 21.19 2646.67 21.06 2553.67 20.95
Minimum of Months 638.83 20.54 6.33 20.51 0.00 20.50
Maximum of Months 744.00 21.92 672.17 22.00 672.17 22.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 19.17 21.01 19.17 21.01
February 672.00 21.02 0.00 21.02 0.00 21.02
March 744.00 21.03 0.00 21.03 0.00 21.03
April 720.00 21.66 0.00 21.66 0.00 21.66
May 744.00 21.91 0.00 21.91 0.00 21.91
June 720.00 22.34 0.00 22.34 0.00 22.34
July 735.67 22.63 0.00 22.63 0.00 22.63
August 744.00 22.73 0.00 22.73 0.00 22.73
September 720.00 22.44 0.00 22.44 0.00 22.44
October 744.00 21.40 0.00 21.40 0.00 21.40
November 720.00 21.03 0.00 21.03 0.00 21.03
December 744.00 21.00 13.83 21.00 13.83 21.00
             
Annual Sum or Average 8751.67 21.69 33.00 21.68 33.00 21.68
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.73 19.17 22.73 19.17 22.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.72 548.50 20.66 548.50 20.63
February 672.00 20.86 424.33 20.77 424.33 20.73
March 744.00 20.81 468.33 20.74 468.33 20.71
April 679.50 21.48 62.33 21.58 50.17 21.62
May 696.33 21.56 47.00 21.82 24.67 21.97
June 626.17 21.80 74.33 22.25 31.83 22.50
July 601.17 22.23 153.00 23.02 67.50 23.44
August 560.00 22.11 157.50 22.89 52.50 23.23
September 601.50 21.67 95.67 22.19 23.33 22.37
October 727.50 21.07 100.17 20.97 96.67 20.88
November 720.00 20.77 405.17 20.67 405.17 20.62
December 744.00 20.57 710.00 20.56 710.00 20.56
             
Annual Sum or Average 8116.17 21.26 3246.33 21.31 2903.00 21.27
Minimum of Months 560.00 20.57 47.00 20.56 23.33 20.56
Maximum of Months 744.00 22.23 710.00 23.02 710.00 23.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.55 660.17 20.52 660.17 20.51
February 672.00 20.62 583.33 20.59 583.33 20.58
March 744.00 20.70 556.67 20.65 556.67 20.62
April 700.83 21.33 84.17 21.38 75.33 21.38
May 713.00 21.48 40.50 21.69 24.50 21.82
June 647.50 21.78 61.67 22.17 28.33 22.40
July 621.83 22.14 130.83 22.86 59.33 23.23
August 599.50 21.94 114.17 22.55 31.83 22.77
September 641.50 21.47 50.50 21.76 6.17 21.80
October 744.00 20.91 172.17 20.76 172.17 20.66
November 720.00 20.60 513.50 20.51 513.50 20.48
December 744.00 20.49 742.33 20.48 742.33 20.48
             
Annual Sum or Average 8292.17 21.13 3710.00 21.12 3453.67 21.05
Minimum of Months 599.50 20.49 40.50 20.48 6.17 20.48
Maximum of Months 744.00 22.14 742.33 22.86 742.33 23.23



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 731.17 21.07 243.33 20.95 243.33 20.87
February 653.00 21.14 141.67 21.05 141.67 20.99
March 744.00 21.07 152.50 21.00 152.50 20.94
April 650.67 21.46 24.00 21.53 3.50 21.53
May 668.00 21.42 16.50 21.49 0.00 21.49
June 612.33 21.51 26.17 21.62 0.00 21.62
July 548.17 21.50 84.50 21.87 0.00 21.87
August 511.00 21.52 132.50 22.05 0.00 22.05
September 541.83 21.41 119.50 21.96 0.83 21.97
October 691.67 21.20 28.83 21.20 20.50 21.16
November 708.83 21.08 145.50 20.98 145.50 20.90
December 741.50 20.90 429.50 20.79 429.50 20.74
             
Annual Sum or Average 7802.17 21.25 1544.50 21.30 1137.33 21.22
Minimum of Months 511.00 20.90 16.50 20.79 0.00 20.74
Maximum of Months 744.00 21.52 429.50 22.05 429.50 22.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 341.33 23.13 67.50 23.27 0.00 23.27
February 275.17 23.14 57.67 23.30 0.00 23.30
March 233.00 23.16 82.17 23.39 0.00 23.39
April 72.83 23.27 248.67 23.85 0.00 23.85
May 32.83 23.18 478.33 23.95 0.00 23.95
June 9.50 23.83 662.00 23.97 7.50 23.97
July 2.33 23.99 722.83 23.97 2.33 23.97
August 0.50 23.99 723.17 23.94 0.50 23.94
September 10.17 23.32 598.67 23.95 2.17 23.95
October 133.83 23.07 336.67 23.75 0.00 23.75
November 258.67 23.09 135.33 23.42 0.00 23.42
December 363.50 23.09 20.83 23.15 0.00 23.15
             
Annual Sum or Average 1733.67 23.13 4133.83 23.73 12.50 23.73
Minimum of Months 0.50 23.07 20.83 23.15 0.00 23.15
Maximum of Months 363.50 23.99 723.17 23.97 7.50 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 147.50 23.12 233.33 23.67 0.00 23.67
February 105.17 23.21 234.00 23.77 0.00 23.77
March 67.17 23.26 330.50 23.89 0.00 23.89
April 2.17 23.24 469.67 24.01 0.00 24.01
May 0.00 0.00 653.33 24.01 0.00 24.01
June 7.17 24.00 710.33 23.99 7.17 23.99
July 0.00 0.00 743.50 23.99 0.00 23.99
August 0.00 0.00 741.00 23.98 0.00 23.98
September 0.00 0.00 688.83 23.98 0.00 23.98
October 6.00 23.12 541.50 23.99 0.00 23.99
November 97.00 23.17 318.17 23.83 0.00 23.83
December 196.83 23.15 186.83 23.57 0.00 23.57
             
Annual Sum or Average 629.00 23.18 5851.00 23.92 7.17 23.92
Minimum of Months 0.00 0.00 186.83 23.57 0.00 23.57
Maximum of Months 196.83 24.00 743.50 24.01 7.17 24.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 509.33 24.10 690.17 24.03 500.67 24.06
February 462.33 24.12 619.00 24.03 460.00 24.06
March 518.83 24.18 714.83 24.08 518.83 24.11
April 513.00 24.17 713.17 24.06 513.00 24.09
May 543.17 24.16 743.33 24.07 543.17 24.10
June 534.17 24.04 719.83 23.98 534.17 23.99
July 558.17 24.00 744.00 23.96 558.17 23.97
August 549.83 24.00 744.00 23.95 549.83 23.97
September 525.17 24.04 719.50 23.98 525.17 24.00
October 531.33 24.20 741.17 24.08 531.33 24.12
November 503.17 24.20 684.67 24.09 502.83 24.12
December 498.67 24.11 674.83 24.03 495.33 24.06
             
Annual Sum or Average 6247.17 24.11 8508.50 24.03 6232.50 24.05
Minimum of Months 462.33 24.00 619.00 23.95 460.00 23.97
Maximum of Months 558.17 24.20 744.00 24.09 558.17 24.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.03 35.83 21.03 35.83 21.03
February 672.00 21.05 0.00 21.05 0.00 21.05
March 744.00 21.05 0.00 21.05 0.00 21.05
April 719.33 21.71 0.00 21.71 0.00 21.71
May 740.50 21.85 0.00 21.85 0.00 21.85
June 691.83 22.30 6.00 22.31 0.00 22.31
July 668.83 22.49 13.83 22.51 0.00 22.51
August 697.00 22.52 4.17 22.53 0.00 22.53
September 705.50 22.20 0.00 22.20 0.00 22.20
October 744.00 21.31 0.00 21.31 0.00 21.31
November 720.00 21.04 0.00 21.04 0.00 21.04
December 744.00 21.01 14.33 21.01 14.33 21.01
             
Annual Sum or Average 8591.00 21.62 74.17 21.62 50.17 21.61
Minimum of Months 668.83 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 22.52 35.83 22.53 35.83 22.53



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.25720 34.90809 0.11753 5.43811
February 672.00000 23.10421 36.08766 0.08577 5.28118
March 744.00000 22.91464 35.82228 0.03454 5.16549
April 720.00000 22.89639 35.54455 0.03034 5.18873
May 744.00000 22.90365 41.07206 -0.9528 24.40460
June 720.00000 22.95596 48.52588 -0.8816 21.62232
July 744.00000 23.18186 49.89891 -0.7889 18.35909
August 744.00000 23.28835 49.79678 -0.7498 17.06646
September 720.00000 23.55180 45.57696 -0.6808 14.97390
October 744.00000 23.64088 40.74511 0.26097 6.51769
November 720.00000 23.66595 37.13318 0.24196 6.32071
December 744.00000 23.51486 33.97055 0.17924 5.77898
           
Annual Sum or Average 8760.00000 23.24046 40.78493 -0.2608 11.38544
Minimum of Months 672.00000 22.89639 33.97055 -0.9528 5.16549
Maximum of Months 744.00000 23.66595 49.89891 0.26097 24.40460



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.12670 37.07327 -0.4162 9.28164
February 672.00000 21.18144 38.01083 -0.3743 8.76423
March 744.00000 21.02964 37.59366 -0.4280 8.97138
April 720.00000 21.52485 36.39785 -0.2024 7.42517
May 744.00000 21.38635 42.72712 -1.3288 43.11186
June 720.00000 21.45141 50.88693 -1.2172 37.57703
July 744.00000 21.68258 52.40477 -1.1056 33.07110
August 744.00000 21.87527 52.07565 -1.0226 30.23195
September 720.00000 21.90131 48.09587 -1.0459 32.15554
October 744.00000 21.35982 44.49146 -0.2414 7.52105
November 720.00000 21.12036 40.76575 -0.3830 8.57365
December 744.00000 21.05652 36.68051 -0.4793 10.14602
           
Annual Sum or Average 8760.00000 21.39189 43.13188 -0.6894 19.80747
Minimum of Months 672.00000 21.02964 36.39785 -1.3288 7.42517
Maximum of Months 744.00000 21.90131 52.40477 -0.2024 43.11186



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.83281 38.33026 -0.1959 6.15915
February 672.00000 21.91809 39.18099 -0.1674 5.85044
March 744.00000 21.92618 38.52107 -0.1705 5.93160
April 720.00000 22.65880 36.89997 0.01720 5.44584
May 744.00000 22.71602 42.43656 -0.9566 25.05745
June 720.00000 22.95242 49.53669 -0.8192 19.79127
July 744.00000 23.10964 51.05693 -0.7490 17.55166
August 744.00000 23.20118 51.06018 -0.7147 16.21218
September 720.00000 23.12344 47.66095 -0.7682 18.05736
October 744.00000 22.45722 44.52413 0.00732 5.38993
November 720.00000 22.02310 41.45446 -0.1287 5.67430
December 744.00000 21.62247 38.22774 -0.2542 6.61495
           
Annual Sum or Average 8760.00000 22.46375 43.26710 -0.4101 11.51589
Minimum of Months 672.00000 21.62247 36.89997 -0.9566 5.38993
Maximum of Months 744.00000 23.20118 51.06018 0.01720 25.05745



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.09171 31.62800 0.66500 17.01524
February 672.00000 23.09419 32.54974 0.67558 17.28753
March 744.00000 23.13858 31.81393 0.68911 17.87785
April 720.00000 23.15652 31.49310 0.72782 18.83055
May 744.00000 23.17698 36.90251 0.05555 10.51067
June 720.00000 23.12955 44.45995 0.11391 10.20935
July 744.00000 23.14000 46.44355 0.13834 10.10902
August 744.00000 23.11220 46.67781 0.13890 10.21087
September 720.00000 23.17395 42.93687 0.11851 10.08222
October 744.00000 23.21092 38.27569 0.76668 20.02750
November 720.00000 23.17944 34.64853 0.71387 18.52073
December 744.00000 23.06473 31.23086 0.64629 16.50452
           
Annual Sum or Average 8760.00000 23.13920 37.45120 0.45270 14.74866
Minimum of Months 672.00000 23.06473 31.23086 0.05555 10.08222
Maximum of Months 744.00000 23.21092 46.67781 0.76668 20.02750



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.53618 41.21680 -0.2238 6.86183
February 672.00000 21.65063 42.02120 -0.1723 6.52404
March 744.00000 21.48511 41.65475 -0.2320 6.44981
April 720.00000 22.34683 39.84997 0.06090 6.27692
May 744.00000 22.22797 45.85500 -0.9731 26.53575
June 720.00000 22.37453 53.41680 -0.8461 21.38157
July 744.00000 22.61503 54.81860 -0.7316 17.92587
August 744.00000 22.86096 54.40617 -0.6269 15.11508
September 720.00000 22.89160 50.59791 -0.6408 16.34587
October 744.00000 22.10447 47.73243 0.01124 6.27939
November 720.00000 21.64743 44.57616 -0.1692 6.30683
December 744.00000 21.33727 41.02804 -0.3095 7.48744
           
Annual Sum or Average 8760.00000 22.09097 46.45996 -0.4064 11.99539
Minimum of Months 672.00000 21.33727 39.84997 -0.9731 6.27692
Maximum of Months 744.00000 22.89160 54.81860 0.06090 26.53575



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.21393 40.54442 -0.0781 5.66082
February 672.00000 22.30398 41.35722 -0.0468 5.45126
March 744.00000 22.27385 40.79645 -0.0602 5.57417
April 720.00000 22.95897 39.31609 0.12856 5.77382
May 744.00000 22.96994 44.84482 -0.8238 20.07053
June 720.00000 23.15582 51.95795 -0.6975 15.88567
July 744.00000 23.30226 53.45869 -0.6273 13.90565
August 744.00000 23.41361 53.39057 -0.5829 12.55390
September 720.00000 23.41049 49.84089 -0.6121 13.42779
October 744.00000 22.80231 46.68503 0.12580 5.83779
November 720.00000 22.39564 43.63792 -0.0107 5.52070
December 744.00000 22.00419 40.39121 -0.1402 5.89349
           
Annual Sum or Average 8760.00000 22.76855 45.54530 -0.2873 9.65825
Minimum of Months 672.00000 22.00419 39.31609 -0.8238 5.45126
Maximum of Months 744.00000 23.41361 53.45869 0.12856 20.07053



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.81127 41.24880 -0.5557 11.98293
February 672.00000 20.94558 41.92363 -0.4992 10.75232
March 744.00000 20.88452 42.10552 -0.5116 10.72126
April 720.00000 21.60074 40.82110 -0.2387 7.81871
May 744.00000 21.69391 46.54482 -1.2923 43.02733
June 720.00000 22.01257 51.75737 -1.0988 35.12693
July 744.00000 22.45523 51.19976 -0.9373 31.08553
August 744.00000 22.49201 51.69375 -0.9247 29.16818
September 720.00000 22.04104 50.77437 -1.1154 35.59596
October 744.00000 21.19638 49.93640 -0.3444 8.24802
November 720.00000 20.86040 46.08402 -0.5073 10.80731
December 744.00000 20.64105 41.17981 -0.6270 13.68869
           
Annual Sum or Average 8760.00000 21.47212 46.29628 -0.7226 20.73181
Minimum of Months 672.00000 20.64105 40.82110 -1.2923 7.81871
Maximum of Months 744.00000 22.49201 51.75737 -0.2387 43.02733



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.62100 41.68721 -0.6223 13.60249
February 672.00000 20.71351 42.44557 -0.5775 12.31749
March 744.00000 20.78576 42.32777 -0.5455 11.47166
April 720.00000 21.40410 41.24641 -0.3115 8.19450
May 744.00000 21.57207 46.88085 -1.3536 45.51951
June 720.00000 21.94150 52.05916 -1.1363 36.30117
July 744.00000 22.36200 51.74175 -0.9853 32.11045
August 744.00000 22.30823 52.84632 -1.0139 31.32530
September 720.00000 21.77718 52.22302 -1.2468 40.06114
October 744.00000 20.99358 50.47804 -0.4169 9.00637
November 720.00000 20.68521 46.51189 -0.5659 12.08520
December 744.00000 20.52242 41.46582 -0.6680 14.86118
           
Annual Sum or Average 8760.00000 21.31051 46.84918 -0.7884 22.29851
Minimum of Months 672.00000 20.52242 41.24641 -1.3536 8.19450
Maximum of Months 744.00000 22.36200 52.84632 -0.3115 45.51951



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.87208 40.01504 -0.5143 10.79953
February 672.00000 20.91539 40.90782 -0.4949 10.22667
March 744.00000 21.02453 40.76920 -0.4480 9.27076
April 720.00000 21.24483 40.40624 -0.3674 7.95502
May 744.00000 21.31748 46.15483 -1.4789 49.86058
June 720.00000 21.50337 51.54861 -1.3553 43.50752
July 744.00000 21.65963 52.49105 -1.2916 40.36925
August 744.00000 21.60722 53.21044 -1.3153 41.37706
September 720.00000 21.35423 51.78400 -1.4338 47.45208
October 744.00000 21.08863 48.73071 -0.3756 7.98887
November 720.00000 20.94128 44.77636 -0.4590 9.55930
December 744.00000 20.82914 39.70750 -0.5342 11.18397
           
Annual Sum or Average 8760.00000 21.19809 45.90224 -0.8411 24.21073
Minimum of Months 672.00000 20.82914 39.70750 -1.4789 7.95502
Maximum of Months 744.00000 21.65963 53.21044 -0.3674 49.86058



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.80627 41.25270 -0.5558 11.97377
February 672.00000 20.92899 41.94175 -0.5075 10.78639
March 744.00000 20.91207 42.03629 -0.5059 10.61212
April 720.00000 21.67129 40.65651 -0.2107 7.29427
May 744.00000 21.69019 46.35709 -1.2890 41.44801
June 720.00000 21.91434 51.96405 -1.1363 34.78077
July 744.00000 22.17637 52.02885 -1.0249 30.37552
August 744.00000 22.26140 52.02717 -0.9871 28.61154
September 720.00000 21.97397 50.78069 -1.1188 34.09604
October 744.00000 21.22638 49.78791 -0.3351 8.12043
November 720.00000 20.85460 46.09572 -0.5078 10.77679
December 744.00000 20.65502 41.13980 -0.6189 13.48695
           
Annual Sum or Average 8760.00000 21.42465 46.36384 -0.7349 20.25735
Minimum of Months 672.00000 20.65502 40.65651 -1.2890 7.29427
Maximum of Months 744.00000 22.26140 52.02885 -0.2107 41.44801



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.62196 41.68395 -0.6211 13.57383
February 672.00000 20.69107 42.48071 -0.5875 12.54584
March 744.00000 20.81600 42.24608 -0.5393 11.31406
April 720.00000 21.53520 40.90168 -0.2710 7.51759
May 744.00000 21.61163 46.59544 -1.3383 43.50052
June 720.00000 21.87375 52.20360 -1.1653 35.83200
July 744.00000 22.12695 52.48076 -1.0606 31.48531
August 744.00000 22.16186 52.97887 -1.0516 30.63452
September 720.00000 21.82380 51.71841 -1.2180 37.72269
October 744.00000 21.04210 50.30723 -0.4033 8.75609
November 720.00000 20.67887 46.52622 -0.5665 12.09558
December 744.00000 20.53753 41.42255 -0.6598 14.63900
           
Annual Sum or Average 8760.00000 21.29632 46.81950 -0.7917 21.69130
Minimum of Months 672.00000 20.53753 40.90168 -1.3383 7.51759
Maximum of Months 744.00000 22.16186 52.97887 -0.2710 43.50052



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.72354 41.90446 -0.6097 13.39710
February 672.00000 20.85793 42.58912 -0.5479 11.94236
March 744.00000 20.80643 42.74639 -0.5555 11.79440
April 720.00000 21.61148 41.10059 -0.2462 8.46099
May 744.00000 21.71455 46.78360 -1.2988 44.53500
June 720.00000 22.06306 52.13732 -1.0822 35.96160
July 744.00000 22.56890 51.38018 -0.8945 32.05237
August 744.00000 22.58905 52.03102 -0.8899 29.90874
September 720.00000 22.08568 51.33247 -1.1137 36.95252
October 744.00000 21.12986 50.62390 -0.3833 9.03607
November 720.00000 20.76856 46.78897 -0.5579 12.04512
December 744.00000 20.57347 41.81551 -0.6793 15.19090
           
Annual Sum or Average 8760.00000 21.46073 46.79209 -0.7397 21.83656
Minimum of Months 672.00000 20.57347 41.10059 -1.2988 8.46099
Maximum of Months 744.00000 22.58905 52.13732 -0.2462 44.53500



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.55040 42.33646 -0.6745 15.10037
February 672.00000 20.62148 43.14206 -0.6295 13.72461
March 744.00000 20.70152 42.99291 -0.5915 12.65884
April 720.00000 21.41701 41.53363 -0.3220 8.80892
May 744.00000 21.59526 47.12335 -1.3625 46.98819
June 720.00000 22.00277 52.45898 -1.1183 36.96817
July 744.00000 22.48201 51.94120 -0.9428 32.80005
August 744.00000 22.40895 53.26763 -0.9821 31.73217
September 720.00000 21.79856 52.89397 -1.2589 41.50134
October 744.00000 20.90824 51.22823 -0.4628 9.96583
November 720.00000 20.59572 47.22771 -0.6175 13.46712
December 744.00000 20.48530 42.04593 -0.7156 16.30322
           
Annual Sum or Average 8760.00000 21.30111 47.37100 -0.8077 23.39360
Minimum of Months 672.00000 20.48530 41.53363 -1.3625 8.80892
Maximum of Months 744.00000 22.48201 53.26763 -0.3220 46.98819



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.10952 41.90402 -0.4457 10.27585
February 672.00000 21.20233 42.58945 -0.4018 9.36748
March 744.00000 21.07180 43.09670 -0.4512 9.65769
April 720.00000 21.67095 42.15689 -0.2029 7.45674
May 744.00000 21.64769 47.96762 -1.3209 43.15935
June 720.00000 21.83229 52.95607 -1.1917 37.06823
July 744.00000 22.11052 52.66626 -1.0724 32.41157
August 744.00000 22.25412 51.90922 -1.0022 29.82148
September 720.00000 22.07336 50.56648 -1.0746 33.92270
October 744.00000 21.36443 50.65753 -0.2719 7.71221
November 720.00000 21.11984 46.96446 -0.4103 9.36829
December 744.00000 20.91083 41.81425 -0.5354 11.86324
           
Annual Sum or Average 8760.00000 21.53177 47.12960 -0.7006 20.24304
Minimum of Months 672.00000 20.91083 41.81425 -1.3209 7.45674
Maximum of Months 744.00000 22.25412 52.95607 -0.2029 43.15935



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.57968 40.34298 0.27078 7.00570
February 672.00000 23.62758 41.08531 0.29309 7.08656
March 744.00000 23.71113 40.03375 0.32182 7.43382
April 720.00000 23.86215 39.09472 0.39021 8.33247
May 744.00000 23.89455 44.01227 -0.4379 9.22411
June 720.00000 23.94031 50.67970 -0.3375 7.52115
July 744.00000 23.95868 52.40261 -0.3070 7.07625
August 744.00000 23.93425 52.73828 -0.3202 7.23896
September 720.00000 23.89841 49.63719 -0.3869 8.32237
October 744.00000 23.76874 46.01977 0.39073 8.39681
November 720.00000 23.65510 43.00498 0.31929 7.48331
December 744.00000 23.54803 39.99513 0.25471 6.79296
           
Annual Sum or Average 8760.00000 23.78219 44.94459 0.03594 7.66145
Minimum of Months 672.00000 23.54803 39.09472 -0.4379 6.79296
Maximum of Months 744.00000 23.95868 52.73828 0.39073 9.22411



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.76203 39.12573 0.35597 7.95880
February 672.00000 23.80654 39.87506 0.37712 8.13112
March 744.00000 23.86568 38.86156 0.40082 8.50449
April 720.00000 23.95620 38.13278 0.45076 9.33429
May 744.00000 23.97388 43.08867 -0.3564 7.77438
June 720.00000 23.98694 49.88799 -0.2715 6.63297
July 744.00000 23.99220 51.67845 -0.2477 6.36135
August 744.00000 23.97676 51.98208 -0.2584 6.46384
September 720.00000 23.96545 48.77452 -0.3137 7.18236
October 744.00000 23.90055 44.89272 0.46207 9.57780
November 720.00000 23.82348 41.80851 0.40118 8.58112
December 744.00000 23.74253 38.76825 0.34301 7.72427
           
Annual Sum or Average 8760.00000 23.89635 43.93133 0.11026 7.84906
Minimum of Months 672.00000 23.74253 38.13278 -0.3564 6.36135
Maximum of Months 744.00000 23.99220 51.98208 0.46207 9.57780



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.87721 37.72900 1.01083 28.93631
February 672.00000 23.87134 38.52423 1.02448 29.56119
March 744.00000 23.94799 37.90021 1.05305 30.62061
April 720.00000 23.97604 37.43050 1.12637 33.93896
May 744.00000 23.99459 42.43786 0.60179 17.70270
June 720.00000 23.93094 49.10582 0.66581 19.03324
July 744.00000 23.93332 50.88716 0.69600 19.64398
August 744.00000 23.92150 51.02752 0.69169 19.61738
September 720.00000 23.93600 47.81645 0.64087 18.31420
October 744.00000 23.99472 43.86812 1.12815 33.82085
November 720.00000 23.95215 40.81730 1.05955 30.92403
December 744.00000 23.85209 37.36357 0.98668 27.87761
           
Annual Sum or Average 8760.00000 23.93264 42.93534 0.88953 25.80501
Minimum of Months 672.00000 23.85209 37.36357 0.60179 17.70270
Maximum of Months 744.00000 23.99472 51.02752 1.12815 33.93896



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01095 36.55095 -0.4476 9.24039
February 672.00000 21.00665 37.60058 -0.4390 9.04043
March 744.00000 21.02766 36.95745 -0.4308 8.90706
April 720.00000 21.47013 35.78084 -0.3122 7.25153
May 744.00000 21.67303 41.39516 -1.3627 43.70712
June 720.00000 22.20831 48.18728 -1.1330 32.29511
July 744.00000 22.47714 49.52794 -1.0305 27.77897
August 744.00000 22.51014 49.67175 -1.0188 27.02213
September 720.00000 22.23098 46.66446 -1.1354 32.37497
October 744.00000 21.35722 43.79859 -0.2956 6.95282
November 720.00000 21.04418 40.22430 -0.4066 8.50426
December 744.00000 21.00155 36.07576 -0.4606 9.45154
           
Annual Sum or Average 8760.00000 21.58790 41.89542 -0.7078 18.60485
Minimum of Months 672.00000 21.00155 35.78084 -1.3627 6.95282
Maximum of Months 744.00000 22.51014 49.67175 -0.2956 43.70712



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01223 39.85397 -0.4386 9.05871
February 672.00000 21.01784 40.86836 -0.4264 8.80870
March 744.00000 21.02665 40.21944 -0.4270 8.83075
April 720.00000 21.66120 38.66851 -0.2635 6.73791
May 744.00000 21.90792 44.10734 -1.2878 39.89933
June 720.00000 22.34499 51.02058 -1.0898 30.32958
July 744.00000 22.64507 52.24055 -0.9754 25.61197
August 744.00000 22.73397 52.26424 -0.9441 23.96594
September 720.00000 22.43587 49.35233 -1.0682 29.38250
October 744.00000 21.40153 46.88642 -0.2858 6.95810
November 720.00000 21.02562 43.47734 -0.4111 8.56113
December 744.00000 21.00227 39.36346 -0.4537 9.31753
           
Annual Sum or Average 8760.00000 21.68808 44.88459 -0.6743 17.34216
Minimum of Months 672.00000 21.00227 38.66851 -1.2878 6.73791
Maximum of Months 744.00000 22.73397 52.26424 -0.2635 39.89933



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.02897 37.67630 -0.4288 8.91484
February 672.00000 21.04906 38.68198 -0.4094 8.54478
March 744.00000 21.04569 38.00442 -0.4075 8.50488
April 720.00000 21.71373 36.38141 -0.2244 6.55925
May 744.00000 21.85637 41.98906 -1.2582 38.70968
June 720.00000 22.34254 48.72049 -1.0370 28.41136
July 744.00000 22.59651 50.08345 -0.9359 24.36668
August 744.00000 22.58552 50.35174 -0.9386 24.19950
September 720.00000 22.22266 47.57131 -1.0897 30.73487
October 744.00000 21.30615 44.94265 -0.2875 6.93392
November 720.00000 21.04249 41.31236 -0.3941 8.29483
December 744.00000 21.00940 37.20990 -0.4470 9.19944
           
Annual Sum or Average 8760.00000 21.65289 42.76889 -0.6565 16.99989
Minimum of Months 672.00000 21.00940 36.38141 -1.2582 6.55925
Maximum of Months 744.00000 22.59651 50.35174 -0.2244 38.70968



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.09649 36.05487 -0.4213 8.80000
February 672.00000 21.08750 37.12472 -0.4144 8.62694
March 744.00000 21.17211 36.36515 -0.3946 8.32843
April 720.00000 21.83719 34.75824 -0.2353 6.40501
May 744.00000 22.06129 40.21149 -1.2477 37.87619
June 720.00000 22.57602 46.92385 -1.0248 27.49294
July 744.00000 22.84065 48.25087 -0.9234 23.43277
August 744.00000 22.88261 48.36550 -0.9089 22.60485
September 720.00000 22.62479 45.37066 -1.0187 27.19110
October 744.00000 21.74013 42.58034 -0.2136 6.12917
November 720.00000 21.23962 39.47781 -0.3596 7.81174
December 744.00000 21.04335 35.68872 -0.4415 9.10177
           
Annual Sum or Average 8760.00000 21.85401 40.95461 -0.6352 16.20013
Minimum of Months 672.00000 21.04335 34.75824 -1.2477 6.12917
Maximum of Months 744.00000 22.88261 48.36550 -0.2136 37.87619



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.181454E+10 11290.15 13-JAN-19:06 297.81 0.565399E+10 0.00 0.746854E+10 1.25 3.12 25-JAN-19:02 0.00 0.00
February 0.199214E+10 13515.26 19-FEB-16:02 323.99 0.620737E+10 0.00 0.819952E+10 1.50 3.12 04-FEB-10:18 0.00 0.00
March 0.212312E+10 17519.44 20-MAR-18:01 322.78 0.661536E+10 0.00 0.873849E+10 1.35 3.12 16-MAR-20:40 0.00 0.00
April 0.200610E+11 94966.53 30-APR-18:03 575.74 0.624728E+11 0.00 0.825337E+11 2.48 3.85 28-APR-15:03 0.00 0.00
May 0.214655E+11 92937.52 22-MAY-15:03 634.04 0.658301E+11 0.00 0.872956E+11 2.64 3.82 23-MAY-08:52 0.00 0.00
June 0.410492E+11 118096.55 12-JUN-18:03 691.05 0.128684E+12 0.00 0.169733E+12 2.97 4.10 25-JUN-18:10 0.00 0.00
July 0.592988E+11 128438.36 22-JUL-18:03 732.84 0.182168E+12 0.00 0.241466E+12 3.01 4.02 23-JUL-08:53 0.00 0.00
August 0.653395E+11 109842.29 14-AUG-18:03 742.93 0.198701E+12 0.00 0.264040E+12 3.03 3.99 18-AUG-15:03 0.00 0.00
September 0.433035E+11 93203.09 13-SEP-15:03 700.32 0.134822E+12 0.00 0.178125E+12 3.00 3.94 12-SEP-15:03 0.00 0.00
October 0.921140E+10 58821.48 07-OCT-15:02 451.72 0.282654E+11 0.00 0.374768E+11 1.88 3.60 07-OCT-15:02 0.00 0.00
November 0.182568E+10 16071.13 11-NOV-09:02 287.19 0.568614E+10 0.00 0.751182E+10 1.24 3.12 01-NOV-05:08 0.00 0.00
December 0.111043E+10 13151.08 15-DEC-19:06 271.37 0.346002E+10 0.00 0.457045E+10 1.14 3.12 01-DEC-05:00 0.00 0.00
                         
Annual Sum or Average 0.268595E+12     6031.78 0.828565E+12 0.00 0.109716E+13 2.13     0.00 0.00
Minimum of Months 0.111043E+10 11290.15   271.37 0.346002E+10 0.00 0.457045E+10 1.14 3.12   0.00 0.00
Maximum of Months 0.653395E+11 128438.36   742.93 0.198701E+12 0.00 0.264040E+12 3.03 4.10   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.766332E+11 0.00 743.50 156232.41 14-JAN-19:02 0.00 40.91 59.98 0.35 0.00 0.07 0.40 14-JAN-19:02
February 0.571710E+11 0.00 671.90 145694.07 05-FEB-19:02 0.00 41.34 60.00 0.30 0.00 0.06 0.37 05-FEB-19:02
March 0.620499E+11 0.00 743.57 145410.65 07-MAR-19:01 0.00 40.71 59.99 0.29 0.00 0.06 0.37 07-MAR-19:01
April 0.321449E+11 0.00 602.28 131840.31 11-APR-08:02 0.00 38.34 55.51 0.14 0.00 0.03 0.34 11-APR-08:02
May 0.378504E+11 0.00 614.35 116784.39 01-MAY-23:18 0.00 35.31 54.59 0.16 0.00 0.04 0.30 01-MAY-23:18
June 0.180070E+11 0.00 420.84 104792.78 01-JUN-03:05 0.00 31.56 47.48 0.07 0.00 0.02 0.27 01-JUN-03:05
July 0.100872E+11 0.00 327.51 99234.10 06-JUL-03:57 0.00 30.77 42.95 0.04 0.00 0.01 0.25 06-JUL-03:57
August 0.623858E+10 0.00 284.12 95241.15 23-AUG-04:00 0.00 30.86 41.84 0.02 0.00 0.01 0.24 23-AUG-04:00
September 0.168906E+11 0.00 373.87 109631.68 04-SEP-05:45 0.00 34.26 46.93 0.07 0.00 0.02 0.28 04-SEP-05:45
October 0.556236E+11 0.00 696.39 142230.45 27-OCT-15:02 0.00 39.16 58.59 0.25 0.00 0.05 0.36 27-OCT-15:02
November 0.798794E+11 0.00 718.91 145412.88 25-NOV-16:04 0.00 40.29 59.96 0.38 0.00 0.08 0.37 25-NOV-16:04
December 0.892785E+11 0.00 744.00 162641.58 16-DEC-16:25 0.00 40.24 60.00 0.41 0.00 0.09 0.41 16-DEC-16:25
                           
Annual Sum or Average 0.541854E+12 0.00 6941.22     0.00 36.95 53.95 0.21 0.00 0.04    
Minimum of Months 0.623858E+10 0.00 284.12 95241.15   0.00 30.77 41.84 0.02 0.00 0.01 0.24  
Maximum of Months 0.892785E+11 0.00 744.00 162641.58   0.00 41.34 60.00 0.41 0.00 0.09 0.41  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.355681E+09 0.00 168.33 0.355681E+09 0.00 0.00 0.00 0.00 33913.20 24-JAN-21:07 33913.20 24-JAN-21:07 0.00 0.00 0.00
February 0.395107E+09 0.00 194.83 0.395107E+09 0.00 0.00 0.00 0.00 37151.92 01-FEB-22:50 37151.92 01-FEB-22:50 0.00 0.00 0.00
March 0.386217E+09 0.00 162.82 0.386217E+09 0.00 0.00 0.00 0.00 30931.20 13-MAR-18:55 30931.20 13-MAR-18:55 0.00 0.00 0.00
April 0.155165E+11 0.00 190.58 0.155012E+11 0.00 0.00 0.00 0.00 186501.22 30-APR-18:10 186501.22 30-APR-18:10 0.00 0.00 0.00
May 0.155244E+11 0.00 199.47 0.155244E+11 0.00 0.00 0.00 0.00 160583.04 22-MAY-15:11 160583.04 22-MAY-15:11 0.00 0.00 0.00
June 0.491578E+11 0.00 294.99 0.466828E+11 0.00 0.00 0.00 0.00 336219.24 25-JUN-18:00 209700.80 12-JUN-18:10 0.00 0.00 0.00
July 0.844461E+11 0.00 412.88 0.832521E+11 0.00 0.00 0.00 0.00 231598.81 22-JUL-18:10 231598.81 22-JUL-18:10 0.00 0.00 0.00
August 0.983977E+11 0.00 460.21 0.971966E+11 0.00 0.00 0.00 0.00 211842.22 14-AUG-18:10 211842.22 14-AUG-18:10 0.00 0.00 0.00
September 0.508194E+11 0.00 332.60 0.504297E+11 0.00 0.00 0.00 0.00 160602.42 11-SEP-17:07 160602.42 11-SEP-17:07 0.00 0.00 0.00
October 0.291661E+10 0.00 124.85 0.291661E+10 0.00 0.00 0.00 0.00 71677.81 07-OCT-15:03 71677.81 07-OCT-15:03 0.00 0.00 0.00
November 0.399621E+09 0.00 137.41 0.399621E+09 0.00 0.00 0.00 0.00 37135.32 03-NOV-20:10 37135.32 03-NOV-20:10 0.00 0.00 0.00
December 0.474291E+09 0.00 232.05 0.474291E+09 0.00 0.00 0.00 0.00 34176.27 05-DEC-22:10 34176.27 05-DEC-22:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.318789E+12 0.00 2911.02 0.313514E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.355681E+09 0.00 124.85 0.355681E+09 0.00 0.00 0.00 0.00 30931.20   30931.20   0.00 0.00 0.00
Maximum of Months 0.983977E+11 0.00 460.21 0.971966E+11 0.00 0.00 0.00 0.00 336219.24   231598.81   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 01-MAR-00:03 0.00 0.00 0.00
April 0.245873E+10 0.00 59.17 0.245686E+10 0.00 0.00 0.00 0.00 28330.58 30-APR-18:02 28330.58 30-APR-18:02 0.00 0.00 0.00
May 0.246834E+10 0.00 71.50 0.246834E+10 0.00 0.00 0.00 0.00 28509.14 22-MAY-15:30 28509.14 22-MAY-15:30 0.00 0.00 0.00
June 0.833990E+10 0.00 198.50 0.762539E+10 0.00 0.00 0.00 0.00 45857.70 25-JUN-18:00 29902.35 13-JUN-15:02 0.00 0.00 0.00
July 0.147687E+11 0.00 353.83 0.139319E+11 0.00 0.00 0.00 0.00 34544.29 23-JUL-15:55 31316.26 22-JUL-15:00 0.00 0.00 0.00
August 0.178806E+11 0.00 428.83 0.169152E+11 0.00 0.00 0.00 0.00 34521.68 17-AUG-15:00 28878.17 14-AUG-15:02 0.00 0.00 0.00
September 0.924215E+10 0.00 248.83 0.879557E+10 0.00 0.00 0.00 0.00 32609.72 12-SEP-14:00 27654.68 13-SEP-15:43 0.00 0.00 0.00
October 0.434541E+09 0.00 26.50 0.434541E+09 0.00 0.00 0.00 0.00 15105.81 07-OCT-15:00 15105.81 07-OCT-15:00 0.00 0.00 0.00
November 6967938.21 0.00 1.17 6967938.21 0.00 0.00 0.00 0.00 4049.57 24-NOV-11:55 4049.57 24-NOV-11:55 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.555999E+11 0.00 1388.33 0.526348E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.178806E+11 0.00 428.83 0.169152E+11 0.00 0.00 0.00 0.00 45857.70   31316.26   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 26408978.73 0.00 6.66 14201991.59 0.00 0.00 0.00 0.00 12315.67 25-JAN-16:01 12315.67 25-JAN-16:01 0.00 0.00 0.00
February 0.184665E+09 0.00 33.74 0.164306E+09 0.00 0.00 0.00 0.00 16049.39 09-FEB-16:01 16049.39 09-FEB-16:01 0.00 0.00 0.00
March 91657487.83 0.00 20.69 84390585.15 0.00 0.00 0.00 0.00 15345.29 31-MAR-15:02 15345.29 31-MAR-15:02 0.00 0.00 0.00
April 0.229591E+10 0.00 317.09 0.170794E+10 0.00 0.00 0.00 0.00 16163.06 28-APR-19:01 16163.06 28-APR-19:01 0.00 0.00 0.00
May 0.277359E+10 0.00 365.70 0.172290E+10 0.00 0.00 0.00 0.00 19016.30 22-MAY-21:31 18557.60 25-MAY-17:02 0.00 0.00 0.00
June 0.427526E+10 0.00 509.59 0.233702E+10 0.00 0.00 0.00 0.00 21107.76 26-JUN-21:01 17923.61 22-JUN-19:01 0.00 0.00 0.00
July 0.502786E+10 0.00 479.63 0.273904E+10 0.00 0.00 0.00 0.00 20431.11 23-JUL-21:31 17442.37 28-JUL-18:11 0.00 0.00 0.00
August 0.459125E+10 0.00 496.01 0.231345E+10 0.00 0.00 0.00 0.00 19870.03 17-AUG-21:11 17665.85 31-AUG-19:01 0.00 0.00 0.00
September 0.347043E+10 0.00 462.39 0.176062E+10 0.00 0.00 0.00 0.00 19734.71 12-SEP-20:11 18381.83 29-SEP-16:01 0.00 0.00 0.00
October 0.817397E+09 0.00 141.84 0.511390E+09 0.00 0.00 0.00 0.00 17524.58 05-OCT-17:12 17524.58 05-OCT-17:12 0.00 0.00 0.00
November 39633988.43 0.00 9.56 27202664.67 0.00 0.00 0.00 0.00 15697.97 03-NOV-15:01 15697.97 03-NOV-15:01 0.00 0.00 0.00
December 149701.78 0.00 0.17 51197.56 0.00 0.00 0.00 0.00 1419.47 21-DEC-16:04 503.70 21-DEC-16:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.235942E+11 0.00 2843.07 0.133825E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 149701.78 0.00 0.17 51197.56 0.00 0.00 0.00 0.00 1419.47   503.70   0.00 0.00 0.00
Maximum of Months 0.502786E+10 0.00 509.59 0.273904E+10 0.00 0.00 0.00 0.00 21107.76   18557.60   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2362020.89 0.00 1.11 786638.50 0.00 0.00 0.00 0.00 4012.87 19-JAN-16:02 3163.33 19-JAN-16:02 0.00 0.00 0.00
February 45290993.16 0.00 13.15 37462222.91 0.00 0.00 0.00 0.00 11756.90 19-FEB-16:02 11756.90 19-FEB-16:02 0.00 0.00 0.00
March 46572380.76 0.00 12.15 43048191.47 0.00 0.00 0.00 0.00 13363.53 20-MAR-18:01 13363.53 20-MAR-18:01 0.00 0.00 0.00
April 0.137310E+10 0.00 209.02 0.101914E+10 0.00 0.00 0.00 0.00 15433.44 20-APR-18:01 15433.44 20-APR-18:01 0.00 0.00 0.00
May 0.210960E+10 0.00 298.96 0.133821E+10 0.00 0.00 0.00 0.00 16844.78 22-MAY-21:31 15856.57 25-MAY-17:21 0.00 0.00 0.00
June 0.372837E+10 0.00 471.07 0.208541E+10 0.00 0.00 0.00 0.00 19078.65 26-JUN-21:01 16083.86 22-JUN-19:01 0.00 0.00 0.00
July 0.424232E+10 0.00 446.54 0.231883E+10 0.00 0.00 0.00 0.00 18305.79 23-JUL-21:31 15662.89 28-JUL-18:11 0.00 0.00 0.00
August 0.324644E+10 0.00 434.26 0.156479E+10 0.00 0.00 0.00 0.00 17401.62 11-AUG-19:11 15642.83 01-AUG-19:31 0.00 0.00 0.00
September 0.180021E+10 0.00 346.48 0.821820E+09 0.00 0.00 0.00 0.00 16869.33 12-SEP-20:11 15536.90 29-SEP-16:01 0.00 0.00 0.00
October 0.287420E+09 0.00 62.77 0.193234E+09 0.00 0.00 0.00 0.00 14407.09 07-OCT-15:02 14407.09 07-OCT-15:02 0.00 0.00 0.00
November 4286817.98 0.00 2.73 2231808.80 0.00 0.00 0.00 0.00 5511.52 10-NOV-16:01 5469.01 10-NOV-16:01 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.168860E+11 0.00 2298.24 0.942497E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.424232E+10 0.00 471.07 0.231883E+10 0.00 0.00 0.00 0.00 19078.65   16083.86   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.750351E+09 0.00 24.17 0.726168E+09 0.00 0.00 0.00 0.00 22769.74 21-JAN-11:30 22769.74 21-JAN-11:30 0.00 0.00 0.00
February 0.593111E+09 0.00 26.01 0.576327E+09 0.00 0.00 0.00 0.00 16382.93 04-FEB-14:21 16382.93 04-FEB-14:21 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 01-MAR-00:03 0.00 0.00 0.00
April 0.141784E+11 0.00 290.05 0.125471E+11 0.00 0.00 0.00 0.00 40376.91 30-APR-12:30 38241.40 30-APR-14:00 0.00 0.00 0.00
May 0.965538E+10 0.00 274.43 0.643433E+10 0.00 0.00 0.00 0.00 31459.52 23-MAY-13:00 26500.48 11-MAY-13:10 0.00 0.00 0.00
June 0.128388E+11 0.00 385.76 0.462764E+10 0.00 0.00 0.00 0.00 31499.40 13-JUN-13:10 18884.20 13-JUN-13:20 0.00 0.00 0.00
July 0.180497E+11 0.00 447.28 0.726327E+10 0.00 0.00 0.00 0.00 37264.99 22-JUL-13:10 26802.04 22-JUL-13:30 0.00 0.00 0.00
August 0.242591E+11 0.00 466.19 0.120467E+11 0.00 0.00 0.00 0.00 41798.22 19-AUG-12:50 31131.83 20-AUG-13:00 0.00 0.00 0.00
September 0.301124E+11 0.00 462.09 0.189108E+11 0.00 0.00 0.00 0.00 53621.62 12-SEP-12:30 50062.16 27-SEP-12:50 0.00 0.00 0.00
October 0.975537E+10 0.00 159.27 0.788219E+10 0.00 0.00 0.00 0.00 46421.87 07-OCT-13:10 46421.87 07-OCT-13:10 0.00 0.00 0.00
November 0.331742E+09 0.00 13.58 0.322227E+09 0.00 0.00 0.00 0.00 18165.43 11-NOV-13:30 18165.43 11-NOV-13:30 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.120524E+12 0.00 2548.84 0.713368E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.301124E+11 0.00 466.19 0.189108E+11 0.00 0.00 0.00 0.00 53621.62   50062.16   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.588070E+09 0.00 64.22 0.162558E+09 0.00 0.00 0.00 0.00 62512.81 29-JAN-09:01 62512.81 29-JAN-09:01 0.00 0.00 0.00
February 0.422653E+09 0.00 57.68 0.152265E+09 0.00 0.00 0.00 0.00 23936.69 01-FEB-19:03 19783.20 11-FEB-19:03 0.00 0.00 0.00
March 0.262398E+10 0.00 178.86 0.148824E+10 0.00 0.00 0.00 0.00 68717.74 19-MAR-08:63 67202.64 20-MAR-18:01 0.00 0.00 0.00
April 0.109242E+11 0.00 362.92 0.764635E+10 0.00 0.00 0.00 0.00 71179.36 20-APR-18:01 71179.36 20-APR-18:01 0.00 0.00 0.00
May 0.170431E+11 0.00 442.75 0.101667E+11 0.00 0.00 0.00 0.00 74254.81 31-MAY-19:51 73350.18 11-MAY-19:31 0.00 0.00 0.00
June 0.289546E+11 0.00 451.63 0.176610E+11 0.00 0.00 0.00 0.00 89822.54 26-JUN-21:01 73854.19 08-JUN-19:11 0.00 0.00 0.00
July 0.305490E+11 0.00 411.98 0.187629E+11 0.00 0.00 0.00 0.00 86701.07 17-JUL-21:51 74958.38 06-JUL-20:31 0.00 0.00 0.00
August 0.246186E+11 0.00 377.45 0.138957E+11 0.00 0.00 0.00 0.00 86603.78 16-AUG-21:51 71781.19 03-AUG-19:31 0.00 0.00 0.00
September 0.167695E+11 0.00 427.76 0.838507E+10 0.00 0.00 0.00 0.00 84414.67 10-SEP-20:31 69601.34 13-SEP-19:31 0.00 0.00 0.00
October 0.516731E+10 0.00 273.14 0.205882E+10 0.00 0.00 0.00 0.00 74620.41 09-OCT-08:63 67969.13 05-OCT-18:01 0.00 0.00 0.00
November 0.130085E+10 0.00 112.61 0.370841E+09 0.00 0.00 0.00 0.00 56848.79 25-NOV-09:01 56848.79 25-NOV-09:01 0.00 0.00 0.00
December 0.145009E+09 0.00 20.89 56217313.13 0.00 0.00 0.00 0.00 26643.54 24-DEC-09:02 22955.73 24-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.139107E+12 0.00 3181.87 0.808067E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.145009E+09 0.00 20.89 56217313.13 0.00 0.00 0.00 0.00 23936.69   19783.20   0.00 0.00 0.00
Maximum of Months 0.305490E+11 0.00 451.63 0.187629E+11 0.00 0.00 0.00 0.00 89822.54   74958.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 70890055.42 0.00 18.79 31917004.19 0.00 0.00 0.00 0.00 4332.04 21-JAN-16:02 3720.52 21-JAN-16:02 0.00 0.00 0.00
February 0.124648E+09 0.00 27.24 80555129.03 0.00 0.00 0.00 0.00 13552.59 04-FEB-16:01 13552.59 04-FEB-16:01 0.00 0.00 0.00
March 63412525.43 0.00 26.76 41216960.08 0.00 0.00 0.00 0.00 7387.05 20-MAR-15:01 7387.05 20-MAR-15:01 0.00 0.00 0.00
April 0.269853E+10 0.00 371.82 0.200315E+10 0.00 0.00 0.00 0.00 15808.61 28-APR-08:51 15808.61 28-APR-08:51 0.00 0.00 0.00
May 0.287330E+10 0.00 407.44 0.171156E+10 0.00 0.00 0.00 0.00 16108.48 23-MAY-08:51 16108.48 23-MAY-08:51 0.00 0.00 0.00
June 0.405241E+10 0.00 508.59 0.219423E+10 0.00 0.00 0.00 0.00 17977.71 26-JUN-21:01 16434.22 13-JUN-08:32 0.00 0.00 0.00
July 0.493723E+10 0.00 516.96 0.273340E+10 0.00 0.00 0.00 0.00 18942.28 23-JUL-08:32 17759.61 22-JUL-08:22 0.00 0.00 0.00
August 0.513209E+10 0.00 523.19 0.282456E+10 0.00 0.00 0.00 0.00 17471.72 17-AUG-08:51 16398.16 28-AUG-08:51 0.00 0.00 0.00
September 0.413318E+10 0.00 506.69 0.227770E+10 0.00 0.00 0.00 0.00 17147.04 10-SEP-20:31 16513.24 13-SEP-08:51 0.00 0.00 0.00
October 0.921703E+09 0.00 153.55 0.572144E+09 0.00 0.00 0.00 0.00 14613.89 07-OCT-15:02 14613.89 07-OCT-15:02 0.00 0.00 0.00
November 68040801.15 0.00 19.63 35892551.41 0.00 0.00 0.00 0.00 13257.45 03-NOV-15:01 13257.45 03-NOV-15:01 0.00 0.00 0.00
December 16100949.73 0.00 8.70 7653480.61 0.00 0.00 0.00 0.00 1049.52 11-DEC-09:05 954.36 08-DEC-10:57 0.00 0.00 0.00
                               
Annual Sum or Average 0.250915E+11 0.00 3089.36 0.145140E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 16100949.73 0.00 8.70 7653480.61 0.00 0.00 0.00 0.00 1049.52   954.36   0.00 0.00 0.00
Maximum of Months 0.513209E+10 0.00 523.19 0.282456E+10 0.00 0.00 0.00 0.00 18942.28   17759.61   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2224794.60 0.00 2.58 549521.34 0.00 0.00 0.00 0.00 2024.37 21-JAN-09:04 1050.54 21-JAN-09:04 0.00 0.00 0.00
February 17911143.07 0.00 9.04 10227948.55 0.00 0.00 0.00 0.00 6042.83 20-FEB-09:02 5321.94 20-FEB-09:02 0.00 0.00 0.00
March 18568963.62 0.00 7.65 9602426.60 0.00 0.00 0.00 0.00 2233.18 30-MAR-18:03 2233.18 30-MAR-18:03 0.00 0.00 0.00
April 0.163533E+10 0.00 267.13 0.118757E+10 0.00 0.00 0.00 0.00 14187.34 28-APR-08:51 14187.34 28-APR-08:51 0.00 0.00 0.00
May 0.214939E+10 0.00 332.46 0.131714E+10 0.00 0.00 0.00 0.00 14608.38 23-MAY-08:51 14608.38 23-MAY-08:51 0.00 0.00 0.00
June 0.347367E+10 0.00 459.35 0.193406E+10 0.00 0.00 0.00 0.00 16594.65 13-JUN-08:32 15553.39 13-JUN-08:32 0.00 0.00 0.00
July 0.410144E+10 0.00 500.55 0.229598E+10 0.00 0.00 0.00 0.00 17117.68 23-JUL-08:32 16050.61 22-JUL-08:22 0.00 0.00 0.00
August 0.370409E+10 0.00 509.67 0.198278E+10 0.00 0.00 0.00 0.00 15857.18 17-AUG-08:51 14932.27 14-AUG-08:51 0.00 0.00 0.00
September 0.233523E+10 0.00 388.50 0.126579E+10 0.00 0.00 0.00 0.00 15429.88 11-SEP-08:51 14598.94 23-SEP-08:51 0.00 0.00 0.00
October 0.327391E+09 0.00 74.26 0.191093E+09 0.00 0.00 0.00 0.00 12551.19 07-OCT-15:02 12551.19 07-OCT-15:02 0.00 0.00 0.00
November 6127350.92 0.00 4.03 1676180.03 0.00 0.00 0.00 0.00 2431.41 25-NOV-09:02 1321.89 25-NOV-09:02 0.00 0.00 0.00
December 429067.70 0.00 0.44 111029.18 0.00 0.00 0.00 0.00 888.09 02-DEC-09:06 239.90 02-DEC-09:06 0.00 0.00 0.00
                               
Annual Sum or Average 0.177718E+11 0.00 2555.66 0.101966E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 429067.70 0.00 0.44 111029.18 0.00 0.00 0.00 0.00 888.09   239.90   0.00 0.00 0.00
Maximum of Months 0.410144E+10 0.00 509.67 0.229598E+10 0.00 0.00 0.00 0.00 17117.68   16050.61   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6261740.78 0.00 5.37 3582061.81 0.00 0.00 0.00 0.00 3239.89 19-JAN-16:02 3239.89 19-JAN-16:02 0.00 0.00 0.00
February 50774368.29 0.00 30.35 46146092.46 0.00 0.00 0.00 0.00 4224.07 09-FEB-16:01 4224.07 09-FEB-16:01 0.00 0.00 0.00
March 22050069.30 0.00 17.87 20450444.41 0.00 0.00 0.00 0.00 4080.17 20-MAR-18:01 4080.17 20-MAR-18:01 0.00 0.00 0.00
April 0.628906E+09 0.00 281.87 0.492841E+09 0.00 0.00 0.00 0.00 4663.06 28-APR-18:42 4663.06 28-APR-18:42 0.00 0.00 0.00
May 0.733768E+09 0.00 320.52 0.483181E+09 0.00 0.00 0.00 0.00 4987.14 22-MAY-21:31 4919.64 25-MAY-17:02 0.00 0.00 0.00
June 0.111525E+10 0.00 458.44 0.647873E+09 0.00 0.00 0.00 0.00 5563.66 26-JUN-21:01 5165.51 22-JUN-18:42 0.00 0.00 0.00
July 0.134200E+10 0.00 464.41 0.764809E+09 0.00 0.00 0.00 0.00 5728.01 24-JUL-19:42 5192.39 11-JUL-18:52 0.00 0.00 0.00
August 0.117255E+10 0.00 488.10 0.617653E+09 0.00 0.00 0.00 0.00 5290.63 17-AUG-21:11 4897.81 01-AUG-19:12 0.00 0.00 0.00
September 0.831490E+09 0.00 407.33 0.446468E+09 0.00 0.00 0.00 0.00 5276.19 12-SEP-20:11 4869.64 29-SEP-16:01 0.00 0.00 0.00
October 0.190017E+09 0.00 112.00 0.128463E+09 0.00 0.00 0.00 0.00 4719.33 05-OCT-17:12 4719.33 05-OCT-17:12 0.00 0.00 0.00
November 9427434.73 0.00 7.25 6803183.89 0.00 0.00 0.00 0.00 4113.87 03-NOV-15:01 4113.87 03-NOV-15:01 0.00 0.00 0.00
December 24337.66 0.00 0.02 9132.24 0.00 0.00 0.00 0.00 405.63 21-DEC-16:04 152.20 21-DEC-16:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.610252E+10 0.00 2593.53 0.365828E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 24337.66 0.00 0.02 9132.24 0.00 0.00 0.00 0.00 405.63   152.20   0.00 0.00 0.00
Maximum of Months 0.134200E+10 0.00 488.10 0.764809E+09 0.00 0.00 0.00 0.00 5728.01   5192.39   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 359699.43 0.00 0.44 142149.24 0.00 0.00 0.00 0.00 617.31 15-JAN-16:03 345.36 15-JAN-16:03 0.00 0.00 0.00
February 8468982.87 0.00 11.32 6617633.92 0.00 0.00 0.00 0.00 2869.03 27-FEB-16:02 2869.03 27-FEB-16:02 0.00 0.00 0.00
March 9951512.95 0.00 10.34 9215668.28 0.00 0.00 0.00 0.00 3525.20 20-MAR-18:01 3525.20 20-MAR-18:01 0.00 0.00 0.00
April 0.377607E+09 0.00 182.12 0.295467E+09 0.00 0.00 0.00 0.00 4075.92 28-APR-18:42 4075.92 28-APR-18:42 0.00 0.00 0.00
May 0.549812E+09 0.00 262.62 0.369914E+09 0.00 0.00 0.00 0.00 4477.61 22-MAY-21:31 4399.01 25-MAY-17:02 0.00 0.00 0.00
June 0.959125E+09 0.00 420.41 0.568889E+09 0.00 0.00 0.00 0.00 4961.23 26-JUN-21:01 4598.52 22-JUN-18:42 0.00 0.00 0.00
July 0.112016E+10 0.00 435.74 0.637413E+09 0.00 0.00 0.00 0.00 5066.17 24-JUL-19:42 4646.32 11-JUL-18:52 0.00 0.00 0.00
August 0.796661E+09 0.00 426.05 0.399945E+09 0.00 0.00 0.00 0.00 4724.62 17-AUG-21:11 4357.08 01-AUG-19:12 0.00 0.00 0.00
September 0.392939E+09 0.00 271.30 0.193881E+09 0.00 0.00 0.00 0.00 4616.22 12-SEP-20:11 4069.25 14-SEP-18:01 0.00 0.00 0.00
October 61136479.49 0.00 38.67 44487414.89 0.00 0.00 0.00 0.00 3763.43 07-OCT-15:02 3763.43 07-OCT-15:02 0.00 0.00 0.00
November 488727.77 0.00 0.72 229001.21 0.00 0.00 0.00 0.00 843.69 03-NOV-15:02 843.69 03-NOV-15:02 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.427670E+10 0.00 2059.73 0.252620E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.112016E+10 0.00 435.74 0.637413E+09 0.00 0.00 0.00 0.00 5066.17   4646.32   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.109079E+10 0.00 130.34 0.715062E+09 0.00 0.00 0.00 0.00 23445.69 11-JAN-16:01 23445.69 11-JAN-16:01 0.00 0.00 0.00
February 0.136947E+10 0.00 143.41 0.107634E+10 0.00 0.00 0.00 0.00 23480.12 10-FEB-16:01 23480.12 10-FEB-16:01 0.00 0.00 0.00
March 0.368220E+09 0.00 81.47 0.274399E+09 0.00 0.00 0.00 0.00 23478.01 20-MAR-15:01 23478.01 20-MAR-15:01 0.00 0.00 0.00
April 0.501379E+10 0.00 409.69 0.362745E+10 0.00 0.00 0.00 0.00 23479.35 06-APR-15:02 23479.35 06-APR-15:02 0.00 0.00 0.00
May 0.404306E+10 0.00 408.68 0.217054E+10 0.00 0.00 0.00 0.00 25016.94 11-MAY-19:31 25016.94 11-MAY-19:31 0.00 0.00 0.00
June 0.532129E+10 0.00 504.96 0.257473E+10 0.00 0.00 0.00 0.00 28996.70 26-JUN-21:01 24235.79 22-JUN-19:01 0.00 0.00 0.00
July 0.670279E+10 0.00 493.60 0.340326E+10 0.00 0.00 0.00 0.00 28123.94 23-JUL-21:31 24400.12 06-JUL-20:31 0.00 0.00 0.00
August 0.792095E+10 0.00 510.98 0.441311E+10 0.00 0.00 0.00 0.00 28244.86 16-AUG-21:51 24786.91 20-AUG-20:11 0.00 0.00 0.00
September 0.833908E+10 0.00 524.72 0.515919E+10 0.00 0.00 0.00 0.00 30137.94 12-SEP-20:11 26371.14 29-SEP-16:01 0.00 0.00 0.00
October 0.319292E+10 0.00 287.72 0.199882E+10 0.00 0.00 0.00 0.00 25982.92 07-OCT-17:32 25982.92 07-OCT-17:32 0.00 0.00 0.00
November 0.867568E+09 0.00 110.58 0.558151E+09 0.00 0.00 0.00 0.00 23472.36 03-NOV-15:01 23472.36 03-NOV-15:01 0.00 0.00 0.00
December 0.322230E+09 0.00 40.14 0.264177E+09 0.00 0.00 0.00 0.00 22729.60 18-DEC-16:02 22729.60 18-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.445522E+11 0.00 3646.30 0.262352E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.322230E+09 0.00 40.14 0.264177E+09 0.00 0.00 0.00 0.00 22729.60   22729.60   0.00 0.00 0.00
Maximum of Months 0.833908E+10 0.00 524.72 0.515919E+10 0.00 0.00 0.00 0.00 30137.94   26371.14   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 563.62 364.98 198.64 548.60 551.02 0.00 0.00 0.00
February 683.92 416.83 267.09 683.38 533.55 0.00 0.00 0.00
March 422.12 122.02 300.10 341.91 444.82 0.00 0.00 0.00
April 865.32 383.42 481.90 974.52 368.80 0.00 0.00 0.00
May 725.42 235.00 490.43 762.19 315.49 0.00 0.00 0.00
June 669.64 161.95 507.69 742.67 231.12 0.00 0.00 0.00
July 721.80 223.30 498.49 858.13 212.32 0.00 0.00 0.00
August 847.76 379.84 467.92 1053.65 233.64 0.00 0.00 0.00
September 1015.94 599.62 416.32 1241.12 307.40 0.00 0.00 0.00
October 677.90 390.83 287.07 736.52 410.71 0.00 0.00 0.00
November 489.54 297.70 191.84 480.53 503.01 0.00 0.00 0.00
December 388.47 249.10 139.37 366.97 622.83 0.00 0.00 0.00
                 
Annual Sum or Average 671.57 317.45 354.12 731.53 393.88 0.00 0.00 0.00
Minimum of Months 388.47 122.02 139.37 341.91 212.32 0.00 0.00 0.00
Maximum of Months 1015.94 599.62 507.69 1241.12 622.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1587.11 1027.75 559.36 1526.45 1598.25 0.00 0.00 0.00
February 1925.88 1173.78 752.10 1902.73 1552.54 0.00 0.00 0.00
March 1188.66 343.60 845.06 942.71 1298.98 0.00 0.00 0.00
April 2436.68 1079.69 1356.99 2709.16 1102.42 0.00 0.00 0.00
May 2042.74 661.73 1381.00 2109.16 952.50 0.00 0.00 0.00
June 1885.66 456.04 1429.61 2050.08 712.65 0.00 0.00 0.00
July 2032.53 628.81 1403.72 2374.54 658.85 0.00 0.00 0.00
August 2387.23 1069.59 1317.63 2927.79 728.37 0.00 0.00 0.00
September 2860.82 1688.48 1172.34 3457.54 943.41 0.00 0.00 0.00
October 1908.91 1100.54 808.37 2049.06 1227.96 0.00 0.00 0.00
November 1378.50 838.29 540.21 1335.68 1477.82 0.00 0.00 0.00
December 1093.90 701.44 392.46 1021.16 1799.58 0.00 0.00 0.00
                 
Annual Sum or Average 1891.09 893.91 997.17 2031.03 1169.20 0.00 0.00 0.00
Minimum of Months 1093.90 343.60 392.46 942.71 658.85 0.00 0.00 0.00
Maximum of Months 2860.82 1688.48 1429.61 3457.54 1799.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2061.74 1335.10 726.64 2006.18 2214.34 0.00 0.00 0.00
February 2501.82 1524.80 977.02 2504.48 2142.60 0.00 0.00 0.00
March 1544.14 446.36 1097.78 1226.15 1819.94 0.00 0.00 0.00
April 3165.39 1402.59 1762.80 3580.79 1518.95 0.00 0.00 0.00
May 2653.63 859.63 1794.00 2774.58 1328.79 0.00 0.00 0.00
June 2449.58 592.43 1857.15 2687.69 1001.80 0.00 0.00 0.00
July 2640.37 816.86 1823.51 3122.87 921.08 0.00 0.00 0.00
August 3101.14 1389.46 1711.68 3867.15 1004.03 0.00 0.00 0.00
September 3716.37 2193.43 1522.94 4568.24 1289.31 0.00 0.00 0.00
October 2479.78 1429.67 1050.12 2699.39 1710.16 0.00 0.00 0.00
November 1790.75 1088.99 701.76 1751.61 2061.30 0.00 0.00 0.00
December 1421.04 911.21 509.83 1337.26 2496.01 0.00 0.00 0.00
                 
Annual Sum or Average 2456.63 1161.25 1295.39 2673.47 1623.17 0.00 0.00 0.00
Minimum of Months 1421.04 446.36 509.83 1226.15 921.08 0.00 0.00 0.00
Maximum of Months 3716.37 2193.43 1857.15 4568.24 2496.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 110.98 108.06 0.00 0.00 0.00
February 135.22 82.42 52.81 137.27 105.63 0.00 0.00 0.00
March 83.46 24.13 59.33 68.84 87.96 0.00 0.00 0.00
April 171.09 75.81 95.28 193.47 74.29 0.00 0.00 0.00
May 143.43 46.46 96.97 148.57 65.24 0.00 0.00 0.00
June 132.40 32.02 100.38 142.83 48.41 0.00 0.00 0.00
July 142.71 44.15 98.56 165.43 45.33 0.00 0.00 0.00
August 167.62 75.10 92.52 206.51 49.13 0.00 0.00 0.00
September 200.87 118.55 82.32 246.29 61.82 0.00 0.00 0.00
October 134.03 77.27 56.76 147.80 80.73 0.00 0.00 0.00
November 96.79 58.86 37.93 96.77 98.50 0.00 0.00 0.00
December 76.81 49.25 27.56 74.14 122.91 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 144.70 78.87 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 68.84 45.33 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 246.29 122.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 42.66 218.21 0.00 0.00 0.00
February 129.22 55.01 74.22 98.73 207.45 0.00 0.00 0.00
March 116.25 22.35 93.89 72.15 164.85 0.00 0.00 0.00
April 273.78 108.55 165.23 279.40 134.66 0.00 0.00 0.00
May 321.27 130.65 190.62 324.78 115.08 0.00 0.00 0.00
June 346.85 142.80 204.06 380.53 85.90 0.00 0.00 0.00
July 353.04 155.51 197.53 401.75 79.69 0.00 0.00 0.00
August 297.09 128.70 168.39 339.88 88.10 0.00 0.00 0.00
September 240.07 108.52 131.55 262.10 114.85 0.00 0.00 0.00
October 127.97 46.48 81.49 110.35 154.43 0.00 0.00 0.00
November 69.04 20.37 48.67 40.97 194.10 0.00 0.00 0.00
December 38.49 7.82 30.67 12.91 244.82 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 197.52 149.90 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 12.91 79.69 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 401.75 244.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 1.83 120.28 0.00 0.00 0.00
February 30.49 0.00 30.49 5.04 113.55 0.00 0.00 0.00
March 42.20 0.00 42.20 15.68 91.01 0.00 0.00 0.00
April 68.95 0.46 68.49 45.56 72.06 0.00 0.00 0.00
May 86.20 4.40 81.81 56.25 58.15 0.00 0.00 0.00
June 94.97 5.94 89.03 79.85 43.57 0.00 0.00 0.00
July 90.30 5.31 84.99 80.01 40.32 0.00 0.00 0.00
August 71.09 1.33 69.76 62.15 45.29 0.00 0.00 0.00
September 53.92 0.03 53.89 41.51 61.69 0.00 0.00 0.00
October 34.53 0.00 34.53 15.92 83.25 0.00 0.00 0.00
November 20.75 0.00 20.75 2.85 104.79 0.00 0.00 0.00
December 14.13 0.00 14.13 0.15 131.75 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 34.04 80.31 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.15 40.32 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 80.01 131.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 45.40 215.68 0.00 0.00 0.00
February 129.22 55.01 74.22 102.73 204.68 0.00 0.00 0.00
March 116.25 22.35 93.89 74.11 163.74 0.00 0.00 0.00
April 273.78 108.55 165.23 284.64 133.01 0.00 0.00 0.00
May 321.27 130.65 190.62 328.20 114.21 0.00 0.00 0.00
June 346.85 142.80 204.06 382.75 85.36 0.00 0.00 0.00
July 353.04 155.51 197.53 404.58 78.96 0.00 0.00 0.00
August 297.09 128.70 168.39 344.52 86.39 0.00 0.00 0.00
September 240.07 108.52 131.55 268.55 112.20 0.00 0.00 0.00
October 127.97 46.48 81.49 114.69 152.19 0.00 0.00 0.00
November 69.04 20.37 48.67 43.58 191.75 0.00 0.00 0.00
December 38.49 7.82 30.67 14.12 242.88 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 200.98 148.15 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 14.12 78.96 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 404.58 242.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.13 57.72 31.41 86.98 88.51 0.00 0.00 0.00
February 108.16 65.92 42.24 108.29 87.15 0.00 0.00 0.00
March 66.76 19.30 47.46 55.77 67.90 0.00 0.00 0.00
April 136.84 60.64 76.21 152.21 65.20 0.00 0.00 0.00
May 114.72 37.16 77.56 117.00 57.35 0.00 0.00 0.00
June 105.90 25.61 80.29 113.33 43.14 0.00 0.00 0.00
July 114.15 35.31 78.83 132.69 39.34 0.00 0.00 0.00
August 134.07 60.07 74.00 165.15 42.65 0.00 0.00 0.00
September 160.66 94.82 65.84 195.19 55.61 0.00 0.00 0.00
October 107.20 61.81 45.40 115.86 70.82 0.00 0.00 0.00
November 77.42 47.08 30.34 76.05 81.25 0.00 0.00 0.00
December 61.43 39.39 22.04 59.39 93.68 0.00 0.00 0.00
                 
Annual Sum or Average 106.20 50.20 56.00 114.67 65.93 0.00 0.00 0.00
Minimum of Months 61.43 19.30 22.04 55.77 39.34 0.00 0.00 0.00
Maximum of Months 160.66 94.82 80.29 195.19 93.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.62 0.00 15.62 1.11 100.84 0.00 0.00 0.00
February 24.39 0.00 24.39 3.37 94.17 0.00 0.00 0.00
March 33.76 0.00 33.76 11.53 75.85 0.00 0.00 0.00
April 55.17 0.37 54.80 38.43 57.49 0.00 0.00 0.00
May 68.97 3.52 65.46 48.24 46.14 0.00 0.00 0.00
June 75.98 4.75 71.23 68.94 33.67 0.00 0.00 0.00
July 72.25 4.25 68.00 70.44 30.38 0.00 0.00 0.00
August 56.88 1.06 55.82 55.22 33.73 0.00 0.00 0.00
September 43.14 0.03 43.12 36.29 47.60 0.00 0.00 0.00
October 27.62 0.00 27.62 12.70 68.73 0.00 0.00 0.00
November 16.60 0.00 16.60 1.83 88.23 0.00 0.00 0.00
December 11.30 0.00 11.30 0.03 111.23 0.00 0.00 0.00
                 
Annual Sum or Average 41.89 1.17 40.71 29.14 65.54 0.00 0.00 0.00
Minimum of Months 11.30 0.00 11.30 0.03 30.38 0.00 0.00 0.00
Maximum of Months 75.98 4.75 71.23 70.44 111.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.10 29.51 44.59 41.15 214.75 0.00 0.00 0.00
February 111.90 41.69 70.20 70.48 203.00 0.00 0.00 0.00
March 116.26 22.93 93.33 70.79 163.17 0.00 0.00 0.00
April 311.45 146.03 165.42 322.78 128.71 0.00 0.00 0.00
May 327.92 143.03 184.89 330.61 111.11 0.00 0.00 0.00
June 324.49 129.63 194.86 350.82 82.68 0.00 0.00 0.00
July 331.18 140.68 190.50 373.71 75.82 0.00 0.00 0.00
August 314.61 150.61 163.99 363.64 83.00 0.00 0.00 0.00
September 282.45 150.08 132.37 314.60 109.59 0.00 0.00 0.00
October 137.38 57.45 79.93 120.18 151.58 0.00 0.00 0.00
November 71.10 24.19 46.91 39.22 189.52 0.00 0.00 0.00
December 52.88 19.79 33.09 25.05 237.51 0.00 0.00 0.00
                 
Annual Sum or Average 204.94 88.08 116.86 202.40 145.60 0.00 0.00 0.00
Minimum of Months 52.88 19.79 33.09 25.05 75.82 0.00 0.00 0.00
Maximum of Months 331.18 150.61 194.86 373.71 237.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 110.77 107.89 0.00 0.00 0.00
February 135.22 82.42 52.81 137.25 105.15 0.00 0.00 0.00
March 83.46 24.13 59.33 68.41 87.75 0.00 0.00 0.00
April 171.09 75.81 95.28 191.60 73.86 0.00 0.00 0.00
May 143.43 46.46 96.97 147.44 64.30 0.00 0.00 0.00
June 132.40 32.02 100.38 142.71 46.93 0.00 0.00 0.00
July 142.71 44.15 98.56 165.82 43.14 0.00 0.00 0.00
August 167.62 75.10 92.52 206.21 47.25 0.00 0.00 0.00
September 200.87 118.55 82.32 245.15 60.94 0.00 0.00 0.00
October 134.03 77.27 56.76 147.11 80.49 0.00 0.00 0.00
November 96.79 58.86 37.93 96.58 98.33 0.00 0.00 0.00
December 76.81 49.25 27.56 73.81 123.06 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 144.19 78.13 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 68.41 43.14 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 245.15 123.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 1.66 120.05 0.00 0.00 0.00
February 30.49 0.00 30.49 4.73 112.86 0.00 0.00 0.00
March 42.20 0.00 42.20 15.25 90.83 0.00 0.00 0.00
April 68.95 0.46 68.49 43.47 71.94 0.00 0.00 0.00
May 86.20 4.40 81.81 55.09 57.58 0.00 0.00 0.00
June 94.97 5.94 89.03 79.85 42.57 0.00 0.00 0.00
July 90.30 5.31 84.99 80.66 38.84 0.00 0.00 0.00
August 71.09 1.33 69.76 61.57 43.89 0.00 0.00 0.00
September 53.92 0.03 53.89 39.69 61.11 0.00 0.00 0.00
October 34.53 0.00 34.53 15.17 83.05 0.00 0.00 0.00
November 20.75 0.00 20.75 2.68 104.52 0.00 0.00 0.00
December 14.13 0.00 14.13 0.12 131.79 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 33.48 79.76 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.12 38.84 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 80.66 131.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.10 29.51 44.59 42.92 211.10 0.00 0.00 0.00
February 111.90 41.69 70.20 73.31 199.08 0.00 0.00 0.00
March 116.26 22.93 93.33 72.57 161.92 0.00 0.00 0.00
April 311.45 146.03 165.42 327.10 126.98 0.00 0.00 0.00
May 327.92 143.03 184.89 333.43 110.18 0.00 0.00 0.00
June 324.49 129.63 194.86 352.68 82.20 0.00 0.00 0.00
July 331.18 140.68 190.50 375.95 75.12 0.00 0.00 0.00
August 314.61 150.61 163.99 367.14 81.41 0.00 0.00 0.00
September 282.45 150.08 132.37 319.47 107.01 0.00 0.00 0.00
October 137.38 57.45 79.93 124.01 149.05 0.00 0.00 0.00
November 71.10 24.19 46.91 41.13 186.34 0.00 0.00 0.00
December 52.88 19.79 33.09 25.88 234.73 0.00 0.00 0.00
                 
Annual Sum or Average 204.94 88.08 116.86 205.11 143.50 0.00 0.00 0.00
Minimum of Months 52.88 19.79 33.09 25.88 75.12 0.00 0.00 0.00
Maximum of Months 331.18 150.61 194.86 375.95 234.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.73 0.00 24.73 1.41 164.46 0.00 0.00 0.00
February 38.61 0.00 38.61 4.45 153.02 0.00 0.00 0.00
March 53.44 0.00 53.44 17.84 121.72 0.00 0.00 0.00
April 87.32 0.58 86.74 58.84 95.12 0.00 0.00 0.00
May 109.17 5.57 103.61 73.58 77.76 0.00 0.00 0.00
June 120.27 7.52 112.75 105.47 58.82 0.00 0.00 0.00
July 114.35 6.73 107.63 106.75 54.20 0.00 0.00 0.00
August 90.03 1.68 88.35 82.06 61.17 0.00 0.00 0.00
September 68.29 0.04 68.25 52.74 84.41 0.00 0.00 0.00
October 43.73 0.00 43.73 18.44 113.06 0.00 0.00 0.00
November 26.27 0.00 26.27 2.47 143.26 0.00 0.00 0.00
December 17.89 0.00 17.89 0.02 181.47 0.00 0.00 0.00
                 
Annual Sum or Average 66.30 1.86 64.44 43.87 108.83 0.00 0.00 0.00
Minimum of Months 17.89 0.00 17.89 0.02 54.20 0.00 0.00 0.00
Maximum of Months 120.27 7.52 112.75 106.75 181.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.12 0.00 9.12 0.52 60.63 0.00 0.00 0.00
February 14.23 0.00 14.23 1.64 56.41 0.00 0.00 0.00
March 19.70 0.00 19.70 6.57 44.87 0.00 0.00 0.00
April 32.19 0.21 31.98 21.69 35.07 0.00 0.00 0.00
May 40.25 2.05 38.19 27.12 28.67 0.00 0.00 0.00
June 44.34 2.77 41.56 38.88 21.69 0.00 0.00 0.00
July 42.16 2.48 39.68 39.35 19.98 0.00 0.00 0.00
August 33.19 0.62 32.57 30.25 22.55 0.00 0.00 0.00
September 25.17 0.01 25.16 19.44 31.12 0.00 0.00 0.00
October 16.12 0.00 16.12 6.80 41.68 0.00 0.00 0.00
November 9.69 0.00 9.69 0.91 52.81 0.00 0.00 0.00
December 6.60 0.00 6.60 0.01 66.90 0.00 0.00 0.00
                 
Annual Sum or Average 24.44 0.68 23.76 16.17 40.12 0.00 0.00 0.00
Minimum of Months 6.60 0.00 6.60 0.01 19.98 0.00 0.00 0.00
Maximum of Months 44.34 2.77 41.56 39.35 66.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.00 33.67 18.33 51.43 53.08 0.00 0.00 0.00
February 63.09 38.45 24.64 64.11 51.38 0.00 0.00 0.00
March 38.94 11.26 27.69 31.70 42.94 0.00 0.00 0.00
April 79.83 35.37 44.46 91.84 35.59 0.00 0.00 0.00
May 66.92 21.68 45.24 70.84 31.69 0.00 0.00 0.00
June 61.78 14.94 46.84 68.63 23.78 0.00 0.00 0.00
July 66.59 20.60 45.99 79.56 21.97 0.00 0.00 0.00
August 78.21 35.04 43.17 98.45 23.76 0.00 0.00 0.00
September 93.72 55.32 38.41 116.47 30.43 0.00 0.00 0.00
October 62.54 36.06 26.48 69.35 39.71 0.00 0.00 0.00
November 45.16 27.46 17.70 45.00 48.62 0.00 0.00 0.00
December 35.84 22.98 12.86 34.12 61.31 0.00 0.00 0.00
                 
Annual Sum or Average 61.96 29.29 32.67 68.36 38.63 0.00 0.00 0.00
Minimum of Months 35.84 11.26 12.86 31.70 21.97 0.00 0.00 0.00
Maximum of Months 93.72 55.32 46.84 116.47 61.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.13 91.39 49.74 139.60 144.08 0.00 0.00 0.00
February 171.25 104.37 66.88 174.01 139.46 0.00 0.00 0.00
March 105.70 30.55 75.14 86.04 116.56 0.00 0.00 0.00
April 216.67 96.01 120.67 249.26 96.59 0.00 0.00 0.00
May 181.64 58.84 122.80 192.28 86.03 0.00 0.00 0.00
June 167.68 40.55 127.12 186.27 64.54 0.00 0.00 0.00
July 180.74 55.91 124.82 215.93 59.64 0.00 0.00 0.00
August 212.28 95.11 117.17 267.22 64.50 0.00 0.00 0.00
September 254.39 150.14 104.25 316.13 82.58 0.00 0.00 0.00
October 169.74 97.86 71.88 188.22 107.78 0.00 0.00 0.00
November 122.58 74.54 48.04 122.13 131.98 0.00 0.00 0.00
December 97.27 62.37 34.90 92.62 166.40 0.00 0.00 0.00
                 
Annual Sum or Average 168.16 79.49 88.67 185.55 104.85 0.00 0.00 0.00
Minimum of Months 97.27 30.55 34.90 86.04 59.64 0.00 0.00 0.00
Maximum of Months 254.39 150.14 127.12 316.13 166.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 111.16 106.74 0.00 0.00 0.00
February 135.22 82.42 52.81 137.16 104.84 0.00 0.00 0.00
March 83.46 24.13 59.33 68.86 86.92 0.00 0.00 0.00
April 171.09 75.81 95.28 191.97 74.08 0.00 0.00 0.00
May 143.43 46.46 96.97 146.94 65.53 0.00 0.00 0.00
June 132.40 32.02 100.38 140.98 48.89 0.00 0.00 0.00
July 142.71 44.15 98.56 163.34 46.30 0.00 0.00 0.00
August 167.62 75.10 92.52 204.70 49.91 0.00 0.00 0.00
September 200.87 118.55 82.32 244.81 61.95 0.00 0.00 0.00
October 134.03 77.27 56.76 147.48 79.81 0.00 0.00 0.00
November 96.79 58.86 37.93 96.79 97.40 0.00 0.00 0.00
December 76.81 49.25 27.56 74.21 122.01 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 143.82 78.57 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 68.86 46.30 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 244.81 122.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 42.94 215.22 0.00 0.00 0.00
February 129.22 55.01 74.22 98.69 205.52 0.00 0.00 0.00
March 116.25 22.35 93.89 72.17 162.78 0.00 0.00 0.00
April 273.78 108.55 165.23 276.21 133.90 0.00 0.00 0.00
May 321.27 130.65 190.62 320.55 115.24 0.00 0.00 0.00
June 346.85 142.80 204.06 375.35 86.36 0.00 0.00 0.00
July 353.04 155.51 197.53 395.98 80.69 0.00 0.00 0.00
August 297.09 128.70 168.39 335.38 88.97 0.00 0.00 0.00
September 240.07 108.52 131.55 259.54 114.74 0.00 0.00 0.00
October 127.97 46.48 81.49 109.94 152.40 0.00 0.00 0.00
November 69.04 20.37 48.67 41.19 191.72 0.00 0.00 0.00
December 38.49 7.82 30.67 13.10 242.65 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 195.41 148.91 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 13.10 80.69 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 395.98 242.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 1.97 118.61 0.00 0.00 0.00
February 30.49 0.00 30.49 5.21 112.33 0.00 0.00 0.00
March 42.20 0.00 42.20 15.89 89.82 0.00 0.00 0.00
April 68.95 0.46 68.49 44.54 71.67 0.00 0.00 0.00
May 86.20 4.40 81.81 54.78 58.17 0.00 0.00 0.00
June 94.97 5.94 89.03 77.87 43.80 0.00 0.00 0.00
July 90.30 5.31 84.99 77.85 40.91 0.00 0.00 0.00
August 71.09 1.33 69.76 60.75 45.79 0.00 0.00 0.00
September 53.92 0.03 53.89 41.11 61.45 0.00 0.00 0.00
October 34.53 0.00 34.53 16.15 81.97 0.00 0.00 0.00
November 20.75 0.00 20.75 3.04 103.27 0.00 0.00 0.00
December 14.13 0.00 14.13 0.18 130.42 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 33.42 79.69 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.18 40.91 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 77.87 130.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 45.81 212.81 0.00 0.00 0.00
February 129.22 55.01 74.22 103.00 202.66 0.00 0.00 0.00
March 116.25 22.35 93.89 74.31 161.64 0.00 0.00 0.00
April 273.78 108.55 165.23 281.78 132.10 0.00 0.00 0.00
May 321.27 130.65 190.62 324.19 114.26 0.00 0.00 0.00
June 346.85 142.80 204.06 377.61 85.79 0.00 0.00 0.00
July 353.04 155.51 197.53 398.93 79.88 0.00 0.00 0.00
August 297.09 128.70 168.39 340.21 86.97 0.00 0.00 0.00
September 240.07 108.52 131.55 266.60 111.57 0.00 0.00 0.00
October 127.97 46.48 81.49 114.77 149.91 0.00 0.00 0.00
November 69.04 20.37 48.67 44.01 189.38 0.00 0.00 0.00
December 38.49 7.82 30.67 14.29 240.93 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 199.10 147.06 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 14.29 79.88 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 398.93 240.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.43 105.83 57.60 157.26 163.11 0.00 0.00 0.00
February 198.32 120.87 77.45 195.97 159.75 0.00 0.00 0.00
March 122.40 35.38 87.02 97.24 131.34 0.00 0.00 0.00
April 250.92 111.18 139.74 279.08 109.37 0.00 0.00 0.00
May 210.35 68.14 142.21 215.58 95.18 0.00 0.00 0.00
June 194.18 46.96 147.22 209.84 69.14 0.00 0.00 0.00
July 209.30 64.75 144.55 243.66 63.69 0.00 0.00 0.00
August 245.83 110.14 135.68 301.66 70.10 0.00 0.00 0.00
September 294.59 173.87 120.72 356.77 91.67 0.00 0.00 0.00
October 196.57 113.33 83.24 212.06 121.50 0.00 0.00 0.00
November 141.95 86.32 55.63 137.38 149.56 0.00 0.00 0.00
December 112.65 72.23 40.41 105.06 186.40 0.00 0.00 0.00
                 
Annual Sum or Average 194.74 92.05 102.68 209.01 117.36 0.00 0.00 0.00
Minimum of Months 112.65 35.38 40.41 97.24 63.69 0.00 0.00 0.00
Maximum of Months 294.59 173.87 147.22 356.77 186.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.67 0.00 136.67 2.84 1038.99 0.00 0.00 0.00
February 213.42 0.00 213.42 11.24 978.89 0.00 0.00 0.00
March 295.36 0.00 295.36 65.20 789.26 0.00 0.00 0.00
April 482.63 3.21 479.42 268.00 598.94 0.00 0.00 0.00
May 603.41 30.77 572.64 332.95 492.55 0.00 0.00 0.00
June 664.75 41.58 623.17 509.28 368.20 0.00 0.00 0.00
July 632.05 37.17 594.87 526.01 333.41 0.00 0.00 0.00
August 497.63 9.31 488.32 405.15 371.85 0.00 0.00 0.00
September 377.45 0.22 377.22 253.30 516.65 0.00 0.00 0.00
October 241.68 0.00 241.68 73.67 732.58 0.00 0.00 0.00
November 145.21 0.00 145.21 5.06 934.80 0.00 0.00 0.00
December 98.89 0.00 98.89 0.00 1152.09 0.00 0.00 0.00
                 
Annual Sum or Average 366.45 10.26 356.19 205.38 690.96 0.00 0.00 0.00
Minimum of Months 98.89 0.00 98.89 0.00 333.41 0.00 0.00 0.00
Maximum of Months 664.75 41.58 623.17 526.01 1152.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.67 0.00 136.67 1.89 1070.66 0.00 0.00 0.00
February 213.42 0.00 213.42 8.67 1009.10 0.00 0.00 0.00
March 295.36 0.00 295.36 57.41 812.53 0.00 0.00 0.00
April 482.63 3.21 479.42 256.51 612.74 0.00 0.00 0.00
May 603.41 30.77 572.64 319.26 503.60 0.00 0.00 0.00
June 664.75 41.58 623.17 496.30 376.11 0.00 0.00 0.00
July 632.05 37.17 594.87 514.11 340.55 0.00 0.00 0.00
August 497.63 9.31 488.32 394.40 380.51 0.00 0.00 0.00
September 377.45 0.22 377.22 243.31 528.68 0.00 0.00 0.00
October 241.68 0.00 241.68 66.34 754.36 0.00 0.00 0.00
November 145.21 0.00 145.21 3.55 965.85 0.00 0.00 0.00
December 98.89 0.00 98.89 0.00 1186.81 0.00 0.00 0.00
                 
Annual Sum or Average 366.45 10.26 356.19 197.78 710.34 0.00 0.00 0.00
Minimum of Months 98.89 0.00 98.89 0.00 340.55 0.00 0.00 0.00
Maximum of Months 664.75 41.58 623.17 514.11 1186.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 1.80 128.50 0.00 0.00 0.00
February 30.49 0.00 30.49 4.56 122.67 0.00 0.00 0.00
March 42.20 0.00 42.20 16.57 98.84 0.00 0.00 0.00
April 68.95 0.46 68.49 52.02 78.68 0.00 0.00 0.00
May 86.20 4.40 81.81 63.55 67.96 0.00 0.00 0.00
June 94.97 5.94 89.03 92.60 51.59 0.00 0.00 0.00
July 90.30 5.31 84.99 96.48 47.41 0.00 0.00 0.00
August 71.09 1.33 69.76 76.59 50.70 0.00 0.00 0.00
September 53.92 0.03 53.89 49.90 67.34 0.00 0.00 0.00
October 34.53 0.00 34.53 17.85 92.56 0.00 0.00 0.00
November 20.75 0.00 20.75 2.87 116.22 0.00 0.00 0.00
December 14.13 0.00 14.13 0.17 145.34 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 39.76 88.82 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.17 47.41 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 96.48 145.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 148.18 59.02 89.17 88.64 455.71 0.00 0.00 0.00
February 223.78 83.38 140.39 147.95 436.31 0.00 0.00 0.00
March 232.50 45.86 186.64 151.40 355.51 0.00 0.00 0.00
April 622.85 292.03 330.82 691.74 282.01 0.00 0.00 0.00
May 655.80 286.04 369.76 701.51 257.96 0.00 0.00 0.00
June 648.94 259.24 389.70 755.40 196.72 0.00 0.00 0.00
July 662.31 281.33 380.98 811.83 179.73 0.00 0.00 0.00
August 629.17 301.20 327.96 793.57 188.10 0.00 0.00 0.00
September 564.86 300.14 264.72 683.25 240.23 0.00 0.00 0.00
October 274.74 114.89 159.85 261.17 335.13 0.00 0.00 0.00
November 142.19 48.38 93.81 83.71 417.08 0.00 0.00 0.00
December 105.76 39.58 66.18 52.79 521.70 0.00 0.00 0.00
                 
Annual Sum or Average 409.84 176.15 233.70 436.31 321.66 0.00 0.00 0.00
Minimum of Months 105.76 39.58 66.18 52.79 179.73 0.00 0.00 0.00
Maximum of Months 662.31 301.20 389.70 811.83 521.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 113.47 114.73 0.00 0.00 0.00
February 135.22 82.42 52.81 140.78 113.54 0.00 0.00 0.00
March 83.46 24.13 59.33 71.63 95.62 0.00 0.00 0.00
April 171.09 75.81 95.28 204.18 79.92 0.00 0.00 0.00
May 143.43 46.46 96.97 158.83 74.16 0.00 0.00 0.00
June 132.40 32.02 100.38 157.47 55.68 0.00 0.00 0.00
July 142.71 44.15 98.56 183.32 50.88 0.00 0.00 0.00
August 167.62 75.10 92.52 223.96 52.83 0.00 0.00 0.00
September 200.87 118.55 82.32 260.36 66.59 0.00 0.00 0.00
October 134.03 77.27 56.76 153.98 89.44 0.00 0.00 0.00
November 96.79 58.86 37.93 98.83 108.74 0.00 0.00 0.00
December 76.81 49.25 27.56 74.82 135.43 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 153.28 86.34 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 71.63 50.88 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 260.36 135.43 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.73 0.00 24.73 1.07 167.28 0.00 0.00 0.00
February 38.61 0.00 38.61 3.50 156.26 0.00 0.00 0.00
March 53.44 0.00 53.44 16.23 123.97 0.00 0.00 0.00
April 87.32 0.58 86.74 54.47 96.48 0.00 0.00 0.00
May 109.17 5.57 103.61 68.99 78.73 0.00 0.00 0.00
June 120.27 7.52 112.75 100.30 59.93 0.00 0.00 0.00
July 114.35 6.73 107.63 101.95 54.90 0.00 0.00 0.00
August 90.03 1.68 88.35 78.39 61.24 0.00 0.00 0.00
September 68.29 0.04 68.25 49.95 84.19 0.00 0.00 0.00
October 43.73 0.00 43.73 16.78 114.50 0.00 0.00 0.00
November 26.27 0.00 26.27 1.90 146.59 0.00 0.00 0.00
December 17.89 0.00 17.89 0.00 185.03 0.00 0.00 0.00
                 
Annual Sum or Average 66.30 1.86 64.44 41.32 110.54 0.00 0.00 0.00
Minimum of Months 17.89 0.00 17.89 0.00 54.90 0.00 0.00 0.00
Maximum of Months 120.27 7.52 112.75 101.95 185.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.12 0.00 22.12 0.95 149.63 0.00 0.00 0.00
February 34.55 0.00 34.55 3.13 139.80 0.00 0.00 0.00
March 47.81 0.00 47.81 14.52 110.92 0.00 0.00 0.00
April 78.13 0.52 77.61 48.73 86.32 0.00 0.00 0.00
May 97.68 4.98 92.70 61.72 70.44 0.00 0.00 0.00
June 107.61 6.73 100.88 89.74 53.62 0.00 0.00 0.00
July 102.31 6.02 96.30 91.22 49.12 0.00 0.00 0.00
August 80.55 1.51 79.05 70.13 54.79 0.00 0.00 0.00
September 61.10 0.04 61.06 44.69 75.32 0.00 0.00 0.00
October 39.12 0.00 39.12 15.02 102.44 0.00 0.00 0.00
November 23.51 0.00 23.51 1.70 131.14 0.00 0.00 0.00
December 16.01 0.00 16.01 0.00 165.53 0.00 0.00 0.00
                 
Annual Sum or Average 59.32 1.66 57.66 36.97 98.89 0.00 0.00 0.00
Minimum of Months 16.01 0.00 16.01 0.00 49.12 0.00 0.00 0.00
Maximum of Months 107.61 6.73 100.88 91.22 165.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.03 269.40 146.62 406.06 430.95 0.00 0.00 0.00
February 504.83 307.68 197.15 505.43 418.93 0.00 0.00 0.00
March 311.58 90.07 221.51 246.62 350.08 0.00 0.00 0.00
April 638.73 283.02 355.71 720.15 289.30 0.00 0.00 0.00
May 535.46 173.46 362.00 552.94 257.88 0.00 0.00 0.00
June 494.29 119.54 374.75 533.98 194.65 0.00 0.00 0.00
July 532.79 164.83 367.96 621.94 178.83 0.00 0.00 0.00
August 625.76 280.37 345.39 775.21 190.86 0.00 0.00 0.00
September 749.91 442.60 307.31 920.86 243.56 0.00 0.00 0.00
October 500.38 288.48 211.90 547.51 322.44 0.00 0.00 0.00
November 361.34 219.74 141.60 354.46 398.07 0.00 0.00 0.00
December 286.74 183.87 102.88 269.38 500.76 0.00 0.00 0.00
                 
Annual Sum or Average 495.71 234.32 261.39 537.11 314.20 0.00 0.00 0.00
Minimum of Months 286.74 90.07 102.88 246.62 178.83 0.00 0.00 0.00
Maximum of Months 749.91 442.60 374.75 920.86 500.76 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.150959E+10 0.977552E+09 0.532037E+09 0.146937E+10 0.147586E+10
February 0.165454E+10 0.100840E+10 0.646136E+09 0.165324E+10 0.129075E+10
March 0.113060E+10 0.326821E+09 0.803783E+09 0.915775E+09 0.119142E+10
April 0.224291E+10 0.993833E+09 0.124907E+10 0.252595E+10 0.955926E+09
May 0.194297E+10 0.629412E+09 0.131355E+10 0.204144E+10 0.845008E+09
June 0.173570E+10 0.419778E+09 0.131592E+10 0.192500E+10 0.599065E+09
July 0.193326E+10 0.598097E+09 0.133516E+10 0.229841E+10 0.568684E+09
August 0.227063E+10 0.101735E+10 0.125328E+10 0.282209E+10 0.625783E+09
September 0.263332E+10 0.155420E+10 0.107911E+10 0.321699E+10 0.796770E+09
October 0.181568E+10 0.104679E+10 0.768888E+09 0.197269E+10 0.110005E+10
November 0.126888E+10 0.771630E+09 0.497246E+09 0.124554E+10 0.130380E+10
December 0.104048E+10 0.667184E+09 0.373294E+09 0.982892E+09 0.166819E+10
           
Annual Sum or Average 0.211785E+11 0.100111E+11 0.111675E+11 0.230694E+11 0.124213E+11
Minimum of Months 0.104048E+10 0.326821E+09 0.373294E+09 0.915775E+09 0.568684E+09
Maximum of Months 0.263332E+10 0.155420E+10 0.133516E+10 0.321699E+10 0.166819E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.425090E+10 0.275272E+10 0.149818E+10 0.408845E+10 0.428075E+10
February 0.465908E+10 0.283960E+10 0.181948E+10 0.460308E+10 0.375591E+10
March 0.318371E+10 0.920306E+09 0.226340E+10 0.252496E+10 0.347918E+10
April 0.631588E+10 0.279857E+10 0.351731E+10 0.702213E+10 0.285748E+10
May 0.547127E+10 0.177238E+10 0.369888E+10 0.564917E+10 0.255118E+10
June 0.488762E+10 0.118207E+10 0.370556E+10 0.531380E+10 0.184719E+10
July 0.544392E+10 0.168420E+10 0.375972E+10 0.635997E+10 0.176466E+10
August 0.639395E+10 0.286480E+10 0.352915E+10 0.784178E+10 0.195086E+10
September 0.741524E+10 0.437654E+10 0.303871E+10 0.896196E+10 0.244532E+10
October 0.511283E+10 0.294769E+10 0.216514E+10 0.548820E+10 0.328896E+10
November 0.357307E+10 0.217286E+10 0.140021E+10 0.346207E+10 0.383050E+10
December 0.292991E+10 0.187874E+10 0.105117E+10 0.273508E+10 0.482000E+10
           
Annual Sum or Average 0.596374E+11 0.281905E+11 0.314469E+11 0.640507E+11 0.368720E+11
Minimum of Months 0.292991E+10 0.920306E+09 0.105117E+10 0.252496E+10 0.176466E+10
Maximum of Months 0.741524E+10 0.437654E+10 0.375972E+10 0.896196E+10 0.482000E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.552217E+10 0.357594E+10 0.194622E+10 0.537334E+10 0.593089E+10
February 0.605241E+10 0.368880E+10 0.236360E+10 0.605884E+10 0.518338E+10
March 0.413581E+10 0.119553E+10 0.294029E+10 0.328411E+10 0.487453E+10
April 0.820468E+10 0.363550E+10 0.456918E+10 0.928141E+10 0.393711E+10
May 0.710749E+10 0.230242E+10 0.480506E+10 0.743144E+10 0.355902E+10
June 0.634930E+10 0.153557E+10 0.481373E+10 0.696650E+10 0.259668E+10
July 0.707196E+10 0.218787E+10 0.488409E+10 0.836429E+10 0.246703E+10
August 0.830611E+10 0.372154E+10 0.458457E+10 0.103578E+11 0.268920E+10
September 0.963282E+10 0.568537E+10 0.394745E+10 0.118409E+11 0.334190E+10
October 0.664185E+10 0.382922E+10 0.281264E+10 0.723004E+10 0.458048E+10
November 0.464162E+10 0.282267E+10 0.181896E+10 0.454017E+10 0.534288E+10
December 0.380613E+10 0.244060E+10 0.136553E+10 0.358172E+10 0.668532E+10
           
Annual Sum or Average 0.774723E+11 0.366210E+11 0.408513E+11 0.843105E+11 0.511884E+11
Minimum of Months 0.380613E+10 0.119553E+10 0.136553E+10 0.328411E+10 0.246703E+10
Maximum of Months 0.963282E+10 0.568537E+10 0.488409E+10 0.118409E+11 0.668532E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.297254E+09 0.289429E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.332095E+09 0.255544E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.184384E+09 0.235583E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.501466E+09 0.192569E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.397938E+09 0.174742E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.370221E+09 0.125490E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.443096E+09 0.121425E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.553113E+09 0.131588E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.638386E+09 0.160236E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.395860E+09 0.216218E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.250828E+09 0.255324E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.198569E+09 0.329214E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.456321E+10 0.248736E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.184384E+09 0.121425E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.638386E+09 0.329214E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.114259E+09 0.584458E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.238853E+09 0.501862E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.193250E+09 0.441528E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.724209E+09 0.349048E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.869904E+09 0.308238E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.986328E+09 0.222649E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.107604E+10 0.213448E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.910327E+09 0.235979E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.679374E+09 0.297702E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.295574E+09 0.413634E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.106189E+09 0.503109E+09
December 0.103093E+09 20956149.08 82136943.91 34570325.21 0.655724E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.622888E+10 0.472738E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 34570325.21 0.213448E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.107604E+10 0.655724E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 4896730.91 0.322150E+09
February 73759823.15 0.00 73759823.15 12193280.38 0.274697E+09
March 0.113018E+09 763.87 0.113017E+09 41988699.32 0.243761E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.118093E+09 0.186776E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.150655E+09 0.155744E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.206963E+09 0.112943E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.214290E+09 0.107991E+09
August 0.190413E+09 3560925.39 0.186852E+09 0.166466E+09 0.121313E+09
September 0.139769E+09 82607.68 0.139686E+09 0.107599E+09 0.159902E+09
October 92475413.30 0.00 92475413.30 42627103.20 0.222982E+09
November 53771554.59 0.00 53771554.59 7388759.05 0.271616E+09
December 37838893.74 0.00 37838893.74 400539.03 0.352885E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.107356E+10 0.253276E+10
Minimum of Months 37838893.74 0.00 37838893.74 400539.03 0.107991E+09
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.214290E+09 0.352885E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.121596E+09 0.577673E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.248518E+09 0.495152E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.198498E+09 0.438573E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.737798E+09 0.344754E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.879052E+09 0.305889E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.992093E+09 0.221253E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.108362E+10 0.211477E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.922750E+09 0.231377E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.696090E+09 0.290823E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.307173E+09 0.407623E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.112959E+09 0.497028E+09
December 0.103093E+09 20956149.08 82136943.91 37806835.13 0.650534E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.633796E+10 0.467216E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 37806835.13 0.211477E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.108362E+10 0.650534E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.238730E+09 0.154592E+09 84137898.18 0.232956E+09 0.237075E+09
February 0.261653E+09 0.159471E+09 0.102182E+09 0.261970E+09 0.210822E+09
March 0.178797E+09 51684172.32 0.127113E+09 0.149375E+09 0.181867E+09
April 0.354700E+09 0.157167E+09 0.197533E+09 0.394530E+09 0.168992E+09
May 0.307267E+09 99536592.27 0.207730E+09 0.313374E+09 0.153611E+09
June 0.274490E+09 66384623.48 0.208105E+09 0.293748E+09 0.111821E+09
July 0.305732E+09 94584426.86 0.211147E+09 0.355407E+09 0.105368E+09
August 0.359085E+09 0.160887E+09 0.198198E+09 0.442325E+09 0.114225E+09
September 0.416440E+09 0.245785E+09 0.170655E+09 0.505943E+09 0.144152E+09
October 0.287136E+09 0.165542E+09 0.121594E+09 0.310327E+09 0.189690E+09
November 0.200663E+09 0.122027E+09 78636007.32 0.197132E+09 0.210608E+09
December 0.164544E+09 0.105510E+09 59033741.75 0.159075E+09 0.250901E+09
           
Annual Sum or Average 0.334924E+10 0.158317E+10 0.176607E+10 0.361616E+10 0.207913E+10
Minimum of Months 0.164544E+09 51684172.32 59033741.75 0.149375E+09 0.105368E+09
Maximum of Months 0.416440E+09 0.245785E+09 0.211147E+09 0.505943E+09 0.250901E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41842464.75 0.00 41842464.75 2961612.78 0.270088E+09
February 59015680.35 0.00 59015680.35 8158972.53 0.227827E+09
March 90426079.04 611.18 90425467.87 30886238.15 0.203159E+09
April 0.142993E+09 950366.37 0.142043E+09 99614321.14 0.149015E+09
May 0.184736E+09 9420490.59 0.175316E+09 0.129202E+09 0.123581E+09
June 0.196951E+09 12319448.80 0.184631E+09 0.178684E+09 87260444.39
July 0.193505E+09 11381086.97 0.182124E+09 0.188672E+09 81371686.01
August 0.152351E+09 2849117.93 0.149502E+09 0.147912E+09 90352484.35
September 0.111830E+09 66094.90 0.111764E+09 94070990.96 0.123375E+09
October 73990137.15 0.00 73990137.15 34018414.38 0.184091E+09
November 43022945.85 0.00 43022945.85 4733873.53 0.228687E+09
December 30275127.60 0.00 30275127.60 91599.13 0.297921E+09
           
Annual Sum or Average 0.132094E+10 36987216.73 0.128395E+10 0.919006E+09 0.206673E+10
Minimum of Months 30275127.60 0.00 30275127.60 91599.13 81371686.01
Maximum of Months 0.196951E+09 12319448.80 0.184631E+09 0.188672E+09 0.297921E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198462E+09 79042420.23 0.119420E+09 0.110215E+09 0.575190E+09
February 0.270698E+09 0.100866E+09 0.169832E+09 0.170504E+09 0.491096E+09
March 0.311380E+09 61414734.22 0.249966E+09 0.189593E+09 0.437035E+09
April 0.807271E+09 0.378498E+09 0.428772E+09 0.836638E+09 0.333616E+09
May 0.878305E+09 0.383093E+09 0.495212E+09 0.885509E+09 0.297585E+09
June 0.841083E+09 0.335996E+09 0.505087E+09 0.909336E+09 0.214306E+09
July 0.887034E+09 0.376787E+09 0.510247E+09 0.100095E+10 0.203071E+09
August 0.842638E+09 0.403400E+09 0.439238E+09 0.973970E+09 0.222302E+09
September 0.732111E+09 0.389014E+09 0.343096E+09 0.815443E+09 0.284067E+09
October 0.367956E+09 0.153873E+09 0.214083E+09 0.321900E+09 0.405979E+09
November 0.184287E+09 62706204.31 0.121580E+09 0.101650E+09 0.491239E+09
December 0.141644E+09 53003264.31 88640916.87 67083664.68 0.636134E+09
           
Annual Sum or Average 0.646287E+10 0.277770E+10 0.368517E+10 0.638279E+10 0.459162E+10
Minimum of Months 0.141644E+09 53003264.31 88640916.87 67083664.68 0.203071E+09
Maximum of Months 0.887034E+09 0.403400E+09 0.510247E+09 0.100095E+10 0.636134E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.296684E+09 0.288984E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.332037E+09 0.254374E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.183230E+09 0.235024E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.496635E+09 0.191442E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.394911E+09 0.172224E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.369892E+09 0.121655E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.444131E+09 0.115535E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.552322E+09 0.126548E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.635426E+09 0.157963E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.394018E+09 0.215588E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.250340E+09 0.254878E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.197694E+09 0.329592E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.454732E+10 0.246381E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.183230E+09 0.115535E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.635426E+09 0.329592E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 4448649.71 0.321533E+09
February 73759823.15 0.00 73759823.15 11449382.92 0.273029E+09
March 0.113018E+09 763.87 0.113017E+09 40858719.62 0.243268E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.112677E+09 0.186473E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.147559E+09 0.154216E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.206974E+09 0.110336E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.216053E+09 0.104022E+09
August 0.190413E+09 3560925.39 0.186852E+09 0.164920E+09 0.117555E+09
September 0.139769E+09 82607.68 0.139686E+09 0.102883E+09 0.158402E+09
October 92475413.30 0.00 92475413.30 40629291.71 0.222453E+09
November 53771554.59 0.00 53771554.59 6941108.91 0.270913E+09
December 37838893.74 0.00 37838893.74 315287.72 0.352999E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.105571E+10 0.251520E+10
Minimum of Months 37838893.74 0.00 37838893.74 315287.72 0.104022E+09
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.216053E+09 0.352999E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198462E+09 79042420.23 0.119420E+09 0.114948E+09 0.565408E+09
February 0.270698E+09 0.100866E+09 0.169832E+09 0.177362E+09 0.481616E+09
March 0.311380E+09 61414734.22 0.249966E+09 0.194376E+09 0.433676E+09
April 0.807271E+09 0.378498E+09 0.428772E+09 0.847850E+09 0.329137E+09
May 0.878305E+09 0.383093E+09 0.495212E+09 0.893060E+09 0.295101E+09
June 0.841083E+09 0.335996E+09 0.505087E+09 0.914149E+09 0.213073E+09
July 0.887034E+09 0.376787E+09 0.510247E+09 0.100695E+10 0.201193E+09
August 0.842638E+09 0.403400E+09 0.439238E+09 0.983347E+09 0.218036E+09
September 0.732111E+09 0.389014E+09 0.343096E+09 0.828076E+09 0.277360E+09
October 0.367956E+09 0.153873E+09 0.214083E+09 0.332160E+09 0.399213E+09
November 0.184287E+09 62706204.31 0.121580E+09 0.106606E+09 0.482997E+09
December 0.141644E+09 53003264.31 88640916.87 69312716.36 0.628688E+09
           
Annual Sum or Average 0.646287E+10 0.277770E+10 0.368517E+10 0.646820E+10 0.452550E+10
Minimum of Months 0.141644E+09 53003264.31 88640916.87 69312716.36 0.201193E+09
Maximum of Months 0.887034E+09 0.403400E+09 0.510247E+09 0.100695E+10 0.628688E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66229772.74 0.00 66229772.74 3785034.63 0.440480E+09
February 93412162.03 0.00 93412162.03 10770563.48 0.370183E+09
March 0.143130E+09 967.39 0.143129E+09 47769314.44 0.326017E+09
April 0.226335E+09 1504274.40 0.224831E+09 0.152511E+09 0.246557E+09
May 0.292407E+09 14911094.62 0.277496E+09 0.197077E+09 0.208277E+09
June 0.311741E+09 19499670.94 0.292241E+09 0.273367E+09 0.152473E+09
July 0.306286E+09 18014397.76 0.288272E+09 0.285913E+09 0.145182E+09
August 0.241146E+09 4509687.32 0.236636E+09 0.219800E+09 0.163827E+09
September 0.177008E+09 104617.41 0.176903E+09 0.136698E+09 0.218796E+09
October 0.117114E+09 0.00 0.117114E+09 49376958.89 0.302828E+09
November 68098281.09 0.00 68098281.09 6401468.35 0.371319E+09
December 47920571.43 0.00 47920571.43 54390.71 0.486039E+09
           
Annual Sum or Average 0.209083E+10 58544709.85 0.203228E+10 0.138352E+10 0.343198E+10
Minimum of Months 47920571.43 0.00 47920571.43 54390.71 0.145182E+09
Maximum of Months 0.311741E+09 19499670.94 0.292241E+09 0.285913E+09 0.486039E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 24415036.59 0.00 24415036.59 1395320.49 0.162379E+09
February 34435590.82 0.00 34435590.82 3970475.67 0.136465E+09
March 52763527.24 356.62 52763170.61 17609747.28 0.120183E+09
April 83436499.74 554537.83 82881961.91 56221970.17 90891232.13
May 0.107793E+09 5496846.90 0.102297E+09 72650705.39 76779689.03
June 0.114921E+09 7188386.13 0.107732E+09 0.100774E+09 56207689.77
July 0.112910E+09 6640852.93 0.106269E+09 0.105399E+09 53520206.43
August 88896459.85 1662457.48 87234002.37 81027427.34 60393365.51
September 65252479.21 38566.31 65213912.90 50392506.83 80657105.95
October 43173171.48 0.00 43173171.48 18202391.59 0.111635E+09
November 25103846.14 0.00 25103846.14 2359846.30 0.136883E+09
December 17665506.86 0.00 17665506.86 20050.67 0.179174E+09
           
Annual Sum or Average 0.770766E+09 21582004.20 0.749184E+09 0.510024E+09 0.126517E+10
Minimum of Months 17665506.86 0.00 17665506.86 20050.67 53520206.43
Maximum of Months 0.114921E+09 7188386.13 0.107732E+09 0.105399E+09 0.179174E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.139266E+09 90183137.34 49082764.60 0.137754E+09 0.142176E+09
February 0.152638E+09 93029421.80 59608931.11 0.155099E+09 0.124304E+09
March 0.104303E+09 30150528.10 74152630.13 84901544.71 0.115020E+09
April 0.206918E+09 91685143.13 0.115233E+09 0.238039E+09 92244764.98
May 0.179248E+09 58065761.49 0.121182E+09 0.189747E+09 84891689.46
June 0.160127E+09 38726197.32 0.121400E+09 0.177885E+09 61630245.95
July 0.178352E+09 55176861.55 0.123175E+09 0.213083E+09 58857260.27
August 0.209476E+09 93855004.78 0.115621E+09 0.263696E+09 63651700.08
September 0.242935E+09 0.143382E+09 99553201.59 0.301896E+09 78863219.48
October 0.167504E+09 96570534.75 70933434.58 0.185734E+09 0.106360E+09
November 0.117059E+09 71185959.25 45873176.30 0.116632E+09 0.126035E+09
December 95988358.37 61550378.44 34437979.94 91400149.04 0.164207E+09
           
Annual Sum or Average 0.195381E+10 0.923561E+09 0.103025E+10 0.215587E+10 0.121824E+10
Minimum of Months 95988358.37 30150528.10 34437979.94 84901544.71 58857260.27
Maximum of Months 0.242935E+09 0.143382E+09 0.123175E+09 0.301896E+09 0.164207E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.377996E+09 0.244775E+09 0.133221E+09 0.373894E+09 0.385894E+09
February 0.414292E+09 0.252501E+09 0.161791E+09 0.420970E+09 0.337387E+09
March 0.283100E+09 81834700.42 0.201265E+09 0.230440E+09 0.312187E+09
April 0.561618E+09 0.248852E+09 0.312766E+09 0.646086E+09 0.250371E+09
May 0.486515E+09 0.157602E+09 0.328912E+09 0.515011E+09 0.230413E+09
June 0.434616E+09 0.105111E+09 0.329506E+09 0.482816E+09 0.167277E+09
July 0.484084E+09 0.149761E+09 0.334322E+09 0.578351E+09 0.159751E+09
August 0.568561E+09 0.254742E+09 0.313819E+09 0.715725E+09 0.172764E+09
September 0.659375E+09 0.389167E+09 0.270208E+09 0.819408E+09 0.214051E+09
October 0.454640E+09 0.262112E+09 0.192528E+09 0.504121E+09 0.288682E+09
November 0.317722E+09 0.193213E+09 0.124509E+09 0.316564E+09 0.342084E+09
December 0.260532E+09 0.167060E+09 93471721.68 0.248079E+09 0.445691E+09
           
Annual Sum or Average 0.530305E+10 0.250673E+10 0.279632E+10 0.585146E+10 0.330655E+10
Minimum of Months 0.260532E+09 81834700.42 93471721.68 0.230440E+09 0.159751E+09
Maximum of Months 0.659375E+09 0.389167E+09 0.334322E+09 0.819408E+09 0.445691E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.297736E+09 0.285892E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.331823E+09 0.253618E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.184448E+09 0.232814E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.497588E+09 0.192016E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.393567E+09 0.175508E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.365410E+09 0.126735E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.437479E+09 0.124018E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.548256E+09 0.133692E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.634554E+09 0.160579E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.395015E+09 0.213771E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.250870E+09 0.252472E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.198772E+09 0.326789E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.453552E+10 0.247790E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.184448E+09 0.124018E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.634554E+09 0.326789E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.115000E+09 0.576439E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.238761E+09 0.497188E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.193308E+09 0.435996E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.715928E+09 0.347072E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.858573E+09 0.308652E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.972906E+09 0.223836E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.106059E+10 0.216111E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.898278E+09 0.238309E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.672716E+09 0.297399E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.294457E+09 0.408201E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.106762E+09 0.496927E+09
December 0.103093E+09 20956149.08 82136943.91 35086937.10 0.649916E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.616237E+10 0.469605E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 35086937.10 0.216111E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.106059E+10 0.649916E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 5283338.48 0.317695E+09
February 73759823.15 0.00 73759823.15 12598217.84 0.271747E+09
March 0.113018E+09 763.87 0.113017E+09 42558431.47 0.240570E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.115440E+09 0.185763E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.146709E+09 0.155807E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.201830E+09 0.113538E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.208521E+09 0.109571E+09
August 0.190413E+09 3560925.39 0.186852E+09 0.162704E+09 0.122650E+09
September 0.139769E+09 82607.68 0.139686E+09 0.106553E+09 0.159276E+09
October 92475413.30 0.00 92475413.30 43263465.18 0.219552E+09
November 53771554.59 0.00 53771554.59 7885532.38 0.267677E+09
December 37838893.74 0.00 37838893.74 485529.29 0.349309E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.105383E+10 0.251316E+10
Minimum of Months 37838893.74 0.00 37838893.74 485529.29 0.109571E+09
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.208521E+09 0.349309E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.122692E+09 0.569982E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.249173E+09 0.490266E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.199041E+09 0.432934E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.730380E+09 0.342407E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.868323E+09 0.306045E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.978774E+09 0.222356E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.106848E+10 0.213945E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.911222E+09 0.232953E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.691020E+09 0.289178E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.307390E+09 0.401531E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.114072E+09 0.490882E+09
December 0.103093E+09 20956149.08 82136943.91 38266431.25 0.645300E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.627883E+10 0.463778E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 38266431.25 0.213945E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.106848E+10 0.645300E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437738E+09 0.283462E+09 0.154276E+09 0.421214E+09 0.436861E+09
February 0.479770E+09 0.292408E+09 0.187362E+09 0.474086E+09 0.386471E+09
March 0.327844E+09 94768591.74 0.233075E+09 0.260438E+09 0.351771E+09
April 0.650381E+09 0.288183E+09 0.362198E+09 0.723385E+09 0.283489E+09
May 0.563408E+09 0.182511E+09 0.380897E+09 0.577418E+09 0.254931E+09
June 0.503307E+09 0.121723E+09 0.381584E+09 0.543900E+09 0.179208E+09
July 0.560592E+09 0.173431E+09 0.387162E+09 0.652623E+09 0.170591E+09
August 0.658421E+09 0.295003E+09 0.363418E+09 0.807979E+09 0.187744E+09
September 0.763588E+09 0.450674E+09 0.312914E+09 0.924739E+09 0.237621E+09
October 0.526495E+09 0.303539E+09 0.222957E+09 0.567974E+09 0.325414E+09
November 0.367938E+09 0.223750E+09 0.144188E+09 0.356079E+09 0.387665E+09
December 0.301709E+09 0.193464E+09 0.108245E+09 0.281387E+09 0.499254E+09
           
Annual Sum or Average 0.614119E+10 0.290292E+10 0.323827E+10 0.659122E+10 0.370102E+10
Minimum of Months 0.301709E+09 94768591.74 0.108245E+09 0.260438E+09 0.170591E+09
Maximum of Months 0.763588E+09 0.450674E+09 0.387162E+09 0.924739E+09 0.499254E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366059E+09 0.00 0.366059E+09 7595587.21 0.278282E+10
February 0.516299E+09 0.00 0.516299E+09 27183880.51 0.236813E+10
March 0.791093E+09 5346.90 0.791088E+09 0.174637E+09 0.211396E+10
April 0.125098E+10 8314288.68 0.124266E+10 0.694644E+09 0.155246E+10
May 0.161617E+10 82415246.22 0.153375E+10 0.891767E+09 0.131925E+10
June 0.172303E+10 0.107777E+09 0.161525E+10 0.132005E+10 0.954384E+09
July 0.169288E+10 99567541.14 0.159331E+10 0.140886E+10 0.893001E+09
August 0.133284E+10 24925533.69 0.130792E+10 0.108515E+10 0.995966E+09
September 0.978343E+09 578231.83 0.977764E+09 0.656552E+09 0.133917E+10
October 0.647303E+09 0.00 0.647303E+09 0.197330E+09 0.196215E+10
November 0.376387E+09 0.00 0.376387E+09 13108852.22 0.242301E+10
December 0.264862E+09 0.00 0.264862E+09 0.00 0.308575E+10
           
Annual Sum or Average 0.115562E+11 0.323583E+09 0.112327E+11 0.647687E+10 0.217900E+11
Minimum of Months 0.264862E+09 0.00 0.264862E+09 0.00 0.893001E+09
Maximum of Months 0.172303E+10 0.107777E+09 0.161525E+10 0.140886E+10 0.308575E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366059E+09 0.00 0.366059E+09 5053032.00 0.286766E+10
February 0.516299E+09 0.00 0.516299E+09 20962756.50 0.244120E+10
March 0.791093E+09 5346.90 0.791088E+09 0.153754E+09 0.217628E+10
April 0.125098E+10 8314288.68 0.124266E+10 0.664883E+09 0.158822E+10
May 0.161617E+10 82415246.22 0.153375E+10 0.855108E+09 0.134885E+10
June 0.172303E+10 0.107777E+09 0.161525E+10 0.128640E+10 0.974874E+09
July 0.169288E+10 99567541.14 0.159331E+10 0.137698E+10 0.912128E+09
August 0.133284E+10 24925533.69 0.130792E+10 0.105636E+10 0.101915E+10
September 0.978343E+09 578231.83 0.977764E+09 0.630650E+09 0.137034E+10
October 0.647303E+09 0.00 0.647303E+09 0.177674E+09 0.202047E+10
November 0.376387E+09 0.00 0.376387E+09 9214415.33 0.250349E+10
December 0.264862E+09 0.00 0.264862E+09 0.00 0.317876E+10
           
Annual Sum or Average 0.115562E+11 0.323583E+09 0.112327E+11 0.623704E+10 0.224014E+11
Minimum of Months 0.264862E+09 0.00 0.264862E+09 0.00 0.912128E+09
Maximum of Months 0.172303E+10 0.107777E+09 0.161525E+10 0.137698E+10 0.317876E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 4832213.67 0.344172E+09
February 73759823.15 0.00 73759823.15 11042386.36 0.296764E+09
March 0.113018E+09 763.87 0.113017E+09 44380802.23 0.264738E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.134846E+09 0.203927E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.170201E+09 0.182017E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.240012E+09 0.133725E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.258401E+09 0.126987E+09
August 0.190413E+09 3560925.39 0.186852E+09 0.205148E+09 0.135786E+09
September 0.139769E+09 82607.68 0.139686E+09 0.129339E+09 0.174558E+09
October 92475413.30 0.00 92475413.30 47804492.98 0.247910E+09
November 53771554.59 0.00 53771554.59 7446165.90 0.301254E+09
December 37838893.74 0.00 37838893.74 466236.58 0.389284E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.125392E+10 0.280112E+10
Minimum of Months 37838893.74 0.00 37838893.74 466236.58 0.126987E+09
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.258401E+09 0.389284E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.396896E+09 0.158074E+09 0.238823E+09 0.237405E+09 0.122057E+10
February 0.541358E+09 0.201718E+09 0.339640E+09 0.357933E+09 0.105552E+10
March 0.622717E+09 0.122821E+09 0.499896E+09 0.405521E+09 0.952207E+09
April 0.161443E+10 0.756943E+09 0.857483E+09 0.179298E+10 0.730977E+09
May 0.175648E+10 0.766132E+09 0.990353E+09 0.187891E+10 0.690914E+09
June 0.168205E+10 0.671945E+09 0.101010E+10 0.195800E+10 0.509904E+09
July 0.177394E+10 0.753521E+09 0.102042E+10 0.217440E+10 0.481378E+09
August 0.168516E+10 0.806743E+09 0.878414E+09 0.212549E+10 0.503818E+09
September 0.146412E+10 0.777974E+09 0.686144E+09 0.177098E+10 0.622687E+09
October 0.735860E+09 0.307724E+09 0.428136E+09 0.699525E+09 0.897599E+09
November 0.368547E+09 0.125404E+09 0.243143E+09 0.216982E+09 0.108107E+10
December 0.283268E+09 0.105999E+09 0.177269E+09 0.141394E+09 0.139733E+10
           
Annual Sum or Average 0.129248E+11 0.555500E+10 0.736983E+10 0.137595E+11 0.101440E+11
Minimum of Months 0.283268E+09 0.105999E+09 0.177269E+09 0.141394E+09 0.481378E+09
Maximum of Months 0.177394E+10 0.806743E+09 0.102042E+10 0.217440E+10 0.139733E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.303925E+09 0.307295E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.340578E+09 0.274664E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.191852E+09 0.256104E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.529240E+09 0.207151E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.425412E+09 0.198641E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.408164E+09 0.144333E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.490992E+09 0.136286E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.599851E+09 0.141502E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.674856E+09 0.172591E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.412408E+09 0.239555E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.256180E+09 0.281864E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.200406E+09 0.362743E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.483386E+10 0.272273E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.191852E+09 0.136286E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.674856E+09 0.362743E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66229772.74 0.00 66229772.74 2855016.23 0.448032E+09
February 93412162.03 0.00 93412162.03 8460878.94 0.378021E+09
March 0.143130E+09 967.39 0.143129E+09 43459213.66 0.332052E+09
April 0.226335E+09 1504274.40 0.224831E+09 0.141186E+09 0.250070E+09
May 0.292407E+09 14911094.62 0.277496E+09 0.184772E+09 0.210864E+09
June 0.311741E+09 19499670.94 0.292241E+09 0.259969E+09 0.155332E+09
July 0.306286E+09 18014397.76 0.288272E+09 0.273073E+09 0.147048E+09
August 0.241146E+09 4509687.32 0.236636E+09 0.209951E+09 0.164023E+09
September 0.177008E+09 104617.41 0.176903E+09 0.129459E+09 0.218213E+09
October 0.117114E+09 0.00 0.117114E+09 44950215.11 0.306672E+09
November 68098281.09 0.00 68098281.09 4936809.76 0.379952E+09
December 47920571.43 0.00 47920571.43 11329.68 0.495577E+09
           
Annual Sum or Average 0.209083E+10 58544709.85 0.203228E+10 0.130308E+10 0.348585E+10
Minimum of Months 47920571.43 0.00 47920571.43 11329.68 0.147048E+09
Maximum of Months 0.311741E+09 19499670.94 0.292241E+09 0.273073E+09 0.495577E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59256028.61 0.00 59256028.61 2554393.84 0.400780E+09
February 83576215.31 0.00 83576215.31 7569980.45 0.338216E+09
March 0.128059E+09 865.53 0.128058E+09 38883123.13 0.297088E+09
April 0.202503E+09 1345880.01 0.201157E+09 0.126319E+09 0.223739E+09
May 0.261618E+09 13341012.85 0.248277E+09 0.165317E+09 0.188660E+09
June 0.278916E+09 17446429.47 0.261469E+09 0.232596E+09 0.138976E+09
July 0.274036E+09 16117549.93 0.257918E+09 0.244319E+09 0.131564E+09
August 0.215754E+09 4034834.34 0.211720E+09 0.187844E+09 0.146752E+09
September 0.158370E+09 93601.59 0.158276E+09 0.115828E+09 0.195236E+09
October 0.104783E+09 0.00 0.104783E+09 40217127.77 0.274381E+09
November 60927790.11 0.00 60927790.11 4416982.40 0.339923E+09
December 42874716.83 0.00 42874716.83 10136.71 0.443344E+09
           
Annual Sum or Average 0.187067E+10 52380173.73 0.181829E+10 0.116587E+10 0.311866E+10
Minimum of Months 42874716.83 0.00 42874716.83 10136.71 0.131564E+09
Maximum of Months 0.278916E+09 17446429.47 0.261469E+09 0.244319E+09 0.443344E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111429E+10 0.721568E+09 0.392718E+09 0.108759E+10 0.115426E+10
February 0.122128E+10 0.744341E+09 0.476939E+09 0.122274E+10 0.101347E+10
March 0.834544E+09 0.241238E+09 0.593305E+09 0.660551E+09 0.937660E+09
April 0.165558E+10 0.733585E+09 0.921994E+09 0.186664E+10 0.749863E+09
May 0.143418E+10 0.464592E+09 0.969593E+09 0.148100E+10 0.690704E+09
June 0.128120E+10 0.309854E+09 0.971342E+09 0.138407E+10 0.504537E+09
July 0.142702E+10 0.441478E+09 0.985540E+09 0.166579E+10 0.478966E+09
August 0.167605E+10 0.750947E+09 0.925100E+09 0.207632E+10 0.511202E+09
September 0.194375E+10 0.114722E+10 0.796539E+09 0.238687E+10 0.631317E+09
October 0.134022E+10 0.772674E+09 0.567548E+09 0.146646E+10 0.863636E+09
November 0.936606E+09 0.569569E+09 0.367038E+09 0.918765E+09 0.103180E+10
December 0.768016E+09 0.492473E+09 0.275543E+09 0.721501E+09 0.134123E+10
           
Annual Sum or Average 0.156327E+11 0.738953E+10 0.824320E+10 0.169383E+11 0.990864E+10
Minimum of Months 0.768016E+09 0.241238E+09 0.275543E+09 0.660551E+09 0.478966E+09
Maximum of Months 0.194375E+10 0.114722E+10 0.985540E+09 0.238687E+10 0.134123E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 548.60 551.02 563.62 364.98 198.64 0.00 0.00
February 683.38 533.55 683.92 416.83 267.09 0.00 0.00
March 341.91 444.82 422.12 122.02 300.10 0.00 0.00
April 974.52 368.80 865.32 383.42 481.90 0.00 0.00
May 762.19 315.49 725.42 235.00 490.43 0.00 0.00
June 742.67 231.12 669.64 161.95 507.69 0.00 0.00
July 858.13 212.32 721.80 223.30 498.49 0.00 0.00
August 1053.65 233.64 847.76 379.84 467.92 0.00 0.00
September 1241.12 307.40 1015.94 599.62 416.32 0.00 0.00
October 736.52 410.71 677.90 390.83 287.07 0.00 0.00
November 480.53 503.01 489.54 297.70 191.84 0.00 0.00
December 366.97 622.83 388.47 249.10 139.37 0.00 0.00
               
Annual Sum or Average 731.53 393.88 671.57 317.45 354.12 0.00 0.00
Minimum of Months 341.91 212.32 388.47 122.02 139.37 0.00 0.00
Maximum of Months 1241.12 622.83 1015.94 599.62 507.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1526.45 1598.25 1587.11 1027.75 559.36 0.00 0.00
February 1902.73 1552.54 1925.88 1173.78 752.10 0.00 0.00
March 942.71 1298.98 1188.66 343.60 845.06 0.00 0.00
April 2709.16 1102.42 2436.68 1079.69 1356.99 0.00 0.00
May 2109.16 952.50 2042.74 661.73 1381.00 0.00 0.00
June 2050.08 712.65 1885.66 456.04 1429.61 0.00 0.00
July 2374.54 658.85 2032.53 628.81 1403.72 0.00 0.00
August 2927.79 728.37 2387.23 1069.59 1317.63 0.00 0.00
September 3457.54 943.41 2860.82 1688.48 1172.34 0.00 0.00
October 2049.06 1227.96 1908.91 1100.54 808.37 0.00 0.00
November 1335.68 1477.82 1378.50 838.29 540.21 0.00 0.00
December 1021.16 1799.58 1093.90 701.44 392.46 0.00 0.00
               
Annual Sum or Average 2031.03 1169.20 1891.09 893.91 997.17 0.00 0.00
Minimum of Months 942.71 658.85 1093.90 343.60 392.46 0.00 0.00
Maximum of Months 3457.54 1799.58 2860.82 1688.48 1429.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2006.18 2214.34 2061.74 1335.10 726.64 0.00 0.00
February 2504.48 2142.60 2501.82 1524.80 977.02 0.00 0.00
March 1226.15 1819.94 1544.14 446.36 1097.78 0.00 0.00
April 3580.79 1518.95 3165.39 1402.59 1762.80 0.00 0.00
May 2774.58 1328.79 2653.63 859.63 1794.00 0.00 0.00
June 2687.69 1001.80 2449.58 592.43 1857.15 0.00 0.00
July 3122.87 921.08 2640.37 816.86 1823.51 0.00 0.00
August 3867.15 1004.03 3101.14 1389.46 1711.68 0.00 0.00
September 4568.24 1289.31 3716.37 2193.43 1522.94 0.00 0.00
October 2699.39 1710.16 2479.78 1429.67 1050.12 0.00 0.00
November 1751.61 2061.30 1790.75 1088.99 701.76 0.00 0.00
December 1337.26 2496.01 1421.04 911.21 509.83 0.00 0.00
               
Annual Sum or Average 2673.47 1623.17 2456.63 1161.25 1295.39 0.00 0.00
Minimum of Months 1226.15 921.08 1421.04 446.36 509.83 0.00 0.00
Maximum of Months 4568.24 2496.01 3716.37 2193.43 1857.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 143.25 315.88 184.49 96.11 88.38 0.00 0.00
February 230.70 307.78 264.45 137.42 127.02 0.00 0.00
March 138.87 250.68 199.71 46.48 153.23 0.00 0.00
April 470.45 206.54 444.87 184.36 260.51 0.00 0.00
May 470.22 177.19 464.70 177.11 287.59 0.00 0.00
June 521.67 132.62 479.25 174.82 304.44 0.00 0.00
July 564.99 122.84 495.75 199.66 296.09 0.00 0.00
August 544.68 135.53 464.70 203.80 260.90 0.00 0.00
September 506.50 174.78 440.94 227.07 213.87 0.00 0.00
October 255.53 232.54 262.00 123.75 138.25 0.00 0.00
November 131.92 286.79 165.83 79.23 86.60 0.00 0.00
December 77.80 358.48 115.30 57.08 58.22 0.00 0.00
               
Annual Sum or Average 338.17 224.73 331.83 142.02 189.81 0.00 0.00
Minimum of Months 77.80 122.84 115.30 46.48 58.22 0.00 0.00
Maximum of Months 564.99 358.48 495.75 227.07 304.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 43.22 331.94 92.58 23.94 68.63 0.00 0.00
February 104.58 315.03 159.71 55.01 104.70 0.00 0.00
March 87.59 252.55 158.44 22.35 136.09 0.00 0.00
April 328.39 203.25 342.73 109.01 233.72 0.00 0.00
May 382.43 170.33 407.47 135.05 272.43 0.00 0.00
June 460.46 126.80 441.82 148.74 293.09 0.00 0.00
July 482.65 117.34 443.33 160.82 282.51 0.00 0.00
August 405.46 130.47 368.18 130.03 238.15 0.00 0.00
September 308.55 172.37 293.99 108.55 185.45 0.00 0.00
October 129.13 233.97 162.50 46.48 116.02 0.00 0.00
November 44.66 294.77 89.79 20.37 69.42 0.00 0.00
December 12.90 373.27 52.62 7.82 44.79 0.00 0.00
               
Annual Sum or Average 232.97 226.42 251.40 80.72 170.68 0.00 0.00
Minimum of Months 12.90 117.34 52.62 7.82 44.79 0.00 0.00
Maximum of Months 482.65 373.27 443.33 160.82 293.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 86.98 88.51 89.13 57.72 31.41 0.00 0.00
February 108.29 87.15 108.16 65.92 42.24 0.00 0.00
March 55.77 67.90 66.76 19.30 47.46 0.00 0.00
April 152.21 65.20 136.84 60.64 76.21 0.00 0.00
May 117.00 57.35 114.72 37.16 77.56 0.00 0.00
June 113.33 43.14 105.90 25.61 80.29 0.00 0.00
July 132.69 39.34 114.15 35.31 78.83 0.00 0.00
August 165.15 42.65 134.07 60.07 74.00 0.00 0.00
September 195.19 55.61 160.66 94.82 65.84 0.00 0.00
October 115.86 70.82 107.20 61.81 45.40 0.00 0.00
November 76.05 81.25 77.42 47.08 30.34 0.00 0.00
December 59.39 93.68 61.43 39.39 22.04 0.00 0.00
               
Annual Sum or Average 114.67 65.93 106.20 50.20 56.00 0.00 0.00
Minimum of Months 55.77 39.34 61.43 19.30 22.04 0.00 0.00
Maximum of Months 195.19 93.68 160.66 94.82 80.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.11 100.84 15.62 0.00 15.62 0.00 0.00
February 3.37 94.17 24.39 0.00 24.39 0.00 0.00
March 11.53 75.85 33.76 0.00 33.76 0.00 0.00
April 38.43 57.49 55.17 0.37 54.80 0.00 0.00
May 48.24 46.14 68.97 3.52 65.46 0.00 0.00
June 68.94 33.67 75.98 4.75 71.23 0.00 0.00
July 70.44 30.38 72.25 4.25 68.00 0.00 0.00
August 55.22 33.73 56.88 1.06 55.82 0.00 0.00
September 36.29 47.60 43.14 0.03 43.12 0.00 0.00
October 12.70 68.73 27.62 0.00 27.62 0.00 0.00
November 1.83 88.23 16.60 0.00 16.60 0.00 0.00
December 0.03 111.23 11.30 0.00 11.30 0.00 0.00
               
Annual Sum or Average 29.14 65.54 41.89 1.17 40.71 0.00 0.00
Minimum of Months 0.03 30.38 11.30 0.00 11.30 0.00 0.00
Maximum of Months 70.44 111.23 75.98 4.75 71.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 143.42 314.15 185.53 101.67 83.86 0.00 0.00
February 202.70 303.12 247.12 124.11 123.01 0.00 0.00
March 137.34 249.06 199.72 47.06 152.66 0.00 0.00
April 509.79 197.98 482.54 221.84 260.70 0.00 0.00
May 473.86 171.21 471.35 189.49 281.86 0.00 0.00
June 491.32 127.40 456.89 161.65 295.24 0.00 0.00
July 537.43 116.85 473.89 184.83 289.07 0.00 0.00
August 567.30 127.69 482.22 225.71 256.51 0.00 0.00
September 556.78 167.56 483.32 268.64 214.68 0.00 0.00
October 265.71 230.49 271.41 134.72 136.69 0.00 0.00
November 132.38 284.43 167.89 83.05 84.84 0.00 0.00
December 94.52 356.23 129.69 69.04 60.65 0.00 0.00
               
Annual Sum or Average 342.99 220.12 337.72 150.85 186.87 0.00 0.00
Minimum of Months 94.52 116.85 129.69 47.06 60.65 0.00 0.00
Maximum of Months 567.30 356.23 483.32 268.64 295.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 38.82 325.39 93.62 29.51 64.11 0.00 0.00
February 73.14 307.03 142.39 41.69 100.69 0.00 0.00
March 85.37 250.29 158.45 22.93 135.52 0.00 0.00
April 366.57 194.92 380.40 146.48 233.91 0.00 0.00
May 386.19 165.42 414.13 147.43 266.70 0.00 0.00
June 431.16 123.40 419.46 135.57 283.89 0.00 0.00
July 455.30 112.64 421.48 145.99 275.49 0.00 0.00
August 427.54 124.12 385.70 151.94 233.76 0.00 0.00
September 355.29 164.24 336.37 150.11 186.26 0.00 0.00
October 136.18 229.10 171.91 57.45 114.46 0.00 0.00
November 39.93 286.98 91.84 24.19 67.65 0.00 0.00
December 20.87 361.40 67.01 19.79 47.22 0.00 0.00
               
Annual Sum or Average 235.33 220.01 257.29 89.55 167.74 0.00 0.00
Minimum of Months 20.87 112.64 67.01 19.79 47.22 0.00 0.00
Maximum of Months 455.30 361.40 421.48 151.94 283.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 173.39 402.67 226.97 125.06 101.91 0.00 0.00
February 233.74 389.79 287.19 142.83 144.36 0.00 0.00
March 139.54 323.49 217.78 41.81 175.97 0.00 0.00
April 421.19 261.93 416.01 132.17 283.84 0.00 0.00
May 359.81 220.13 397.98 88.14 309.84 0.00 0.00
June 395.18 164.76 394.06 65.79 328.27 0.00 0.00
July 437.95 152.16 403.83 85.72 318.11 0.00 0.00
August 476.92 170.91 413.71 132.46 281.25 0.00 0.00
September 503.66 227.41 441.58 205.51 236.06 0.00 0.00
October 279.26 298.70 292.13 133.92 158.21 0.00 0.00
November 160.57 366.73 203.70 102.01 101.69 0.00 0.00
December 112.17 461.47 157.60 85.35 72.24 0.00 0.00
               
Annual Sum or Average 307.71 286.18 320.85 111.31 209.54 0.00 0.00
Minimum of Months 112.17 152.16 157.60 41.81 72.24 0.00 0.00
Maximum of Months 503.66 461.47 441.58 205.51 328.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 143.94 311.80 184.49 96.11 88.38 0.00 0.00
February 230.74 305.23 264.45 137.42 127.02 0.00 0.00
March 138.93 247.60 199.71 46.48 153.23 0.00 0.00
April 465.66 205.46 444.87 184.36 260.51 0.00 0.00
May 464.14 177.41 464.70 177.11 287.59 0.00 0.00
June 514.42 133.35 479.25 174.82 304.44 0.00 0.00
July 556.81 124.49 495.75 199.66 296.09 0.00 0.00
August 538.12 136.94 464.70 203.80 260.90 0.00 0.00
September 502.40 174.74 440.94 227.07 213.87 0.00 0.00
October 254.90 229.70 262.00 123.75 138.25 0.00 0.00
November 132.31 283.45 165.83 79.23 86.60 0.00 0.00
December 78.27 355.62 115.30 57.08 58.22 0.00 0.00
               
Annual Sum or Average 335.16 223.42 331.83 142.02 189.81 0.00 0.00
Minimum of Months 78.27 124.49 115.30 46.48 58.22 0.00 0.00
Maximum of Months 556.81 355.62 495.75 227.07 304.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 43.86 327.50 92.58 23.94 68.63 0.00 0.00
February 105.07 311.85 159.71 55.01 104.70 0.00 0.00
March 88.01 249.26 158.44 22.35 136.09 0.00 0.00
April 324.40 201.85 342.73 109.01 233.72 0.00 0.00
May 376.91 170.37 407.47 135.05 272.43 0.00 0.00
June 453.35 127.46 441.82 148.74 293.09 0.00 0.00
July 474.83 118.84 443.33 160.82 282.51 0.00 0.00
August 399.60 131.40 368.18 130.03 238.15 0.00 0.00
September 306.07 171.38 293.99 108.55 185.45 0.00 0.00
October 129.44 230.41 162.50 46.48 116.02 0.00 0.00
November 45.37 290.97 89.79 20.37 69.42 0.00 0.00
December 13.16 370.03 52.62 7.82 44.79 0.00 0.00
               
Annual Sum or Average 230.46 224.70 251.40 80.72 170.68 0.00 0.00
Minimum of Months 13.16 118.84 52.62 7.82 44.79 0.00 0.00
Maximum of Months 474.83 370.03 443.33 160.82 293.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 157.26 163.11 163.43 105.83 57.60 0.00 0.00
February 195.97 159.75 198.32 120.87 77.45 0.00 0.00
March 97.24 131.34 122.40 35.38 87.02 0.00 0.00
April 279.08 109.37 250.92 111.18 139.74 0.00 0.00
May 215.58 95.18 210.35 68.14 142.21 0.00 0.00
June 209.84 69.14 194.18 46.96 147.22 0.00 0.00
July 243.66 63.69 209.30 64.75 144.55 0.00 0.00
August 301.66 70.10 245.83 110.14 135.68 0.00 0.00
September 356.77 91.67 294.59 173.87 120.72 0.00 0.00
October 212.06 121.50 196.57 113.33 83.24 0.00 0.00
November 137.38 149.56 141.95 86.32 55.63 0.00 0.00
December 105.06 186.40 112.65 72.23 40.41 0.00 0.00
               
Annual Sum or Average 209.01 117.36 194.74 92.05 102.68 0.00 0.00
Minimum of Months 97.24 63.69 112.65 35.38 40.41 0.00 0.00
Maximum of Months 356.77 186.40 294.59 173.87 147.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2.84 1038.99 136.67 0.00 136.67 0.00 0.00
February 11.24 978.89 213.42 0.00 213.42 0.00 0.00
March 65.20 789.26 295.36 0.00 295.36 0.00 0.00
April 268.00 598.94 482.63 3.21 479.42 0.00 0.00
May 332.95 492.55 603.41 30.77 572.64 0.00 0.00
June 509.28 368.20 664.75 41.58 623.17 0.00 0.00
July 526.01 333.41 632.05 37.17 594.87 0.00 0.00
August 405.15 371.85 497.63 9.31 488.32 0.00 0.00
September 253.30 516.65 377.45 0.22 377.22 0.00 0.00
October 73.67 732.58 241.68 0.00 241.68 0.00 0.00
November 5.06 934.80 145.21 0.00 145.21 0.00 0.00
December 0.00 1152.09 98.89 0.00 98.89 0.00 0.00
               
Annual Sum or Average 205.38 690.96 366.45 10.26 356.19 0.00 0.00
Minimum of Months 0.00 333.41 98.89 0.00 98.89 0.00 0.00
Maximum of Months 526.01 1152.09 664.75 41.58 623.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.89 1070.66 136.67 0.00 136.67 0.00 0.00
February 8.67 1009.10 213.42 0.00 213.42 0.00 0.00
March 57.41 812.53 295.36 0.00 295.36 0.00 0.00
April 256.51 612.74 482.63 3.21 479.42 0.00 0.00
May 319.26 503.60 603.41 30.77 572.64 0.00 0.00
June 496.30 376.11 664.75 41.58 623.17 0.00 0.00
July 514.11 340.55 632.05 37.17 594.87 0.00 0.00
August 394.40 380.51 497.63 9.31 488.32 0.00 0.00
September 243.31 528.68 377.45 0.22 377.22 0.00 0.00
October 66.34 754.36 241.68 0.00 241.68 0.00 0.00
November 3.55 965.85 145.21 0.00 145.21 0.00 0.00
December 0.00 1186.81 98.89 0.00 98.89 0.00 0.00
               
Annual Sum or Average 197.78 710.34 366.45 10.26 356.19 0.00 0.00
Minimum of Months 0.00 340.55 98.89 0.00 98.89 0.00 0.00
Maximum of Months 514.11 1186.81 664.75 41.58 623.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 180.40 675.42 279.15 131.18 147.97 0.00 0.00
February 279.65 658.87 389.49 165.80 223.69 0.00 0.00
March 234.80 545.17 358.15 69.98 288.17 0.00 0.00
April 940.49 433.16 862.89 368.30 494.59 0.00 0.00
May 917.06 393.26 885.43 336.90 548.53 0.00 0.00
June 1001.35 299.88 876.31 297.20 579.11 0.00 0.00
July 1087.96 274.36 895.32 330.79 564.53 0.00 0.00
August 1090.89 288.41 867.87 377.63 490.24 0.00 0.00
September 987.77 368.43 819.65 418.73 400.92 0.00 0.00
October 428.60 512.73 443.30 192.16 251.13 0.00 0.00
November 175.24 631.87 259.72 107.24 152.48 0.00 0.00
December 113.36 788.05 196.69 88.83 107.87 0.00 0.00
               
Annual Sum or Average 620.88 488.35 594.98 240.38 354.60 0.00 0.00
Minimum of Months 113.36 274.36 196.69 69.98 107.87 0.00 0.00
Maximum of Months 1090.89 788.05 895.32 418.73 579.11 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 378.05 717.83 462.88 269.40 193.48 0.00 0.00
February 495.11 698.04 577.99 307.68 270.31 0.00 0.00
March 273.04 580.65 412.83 90.07 322.76 0.00 0.00
April 822.57 471.30 804.17 284.12 520.05 0.00 0.00
May 676.75 400.14 742.31 184.01 558.31 0.00 0.00
June 716.28 300.47 722.16 133.80 588.37 0.00 0.00
July 808.30 276.04 749.45 177.57 571.88 0.00 0.00
August 921.90 305.06 796.35 283.56 512.79 0.00 0.00
September 1013.82 401.40 879.29 442.68 436.62 0.00 0.00
October 573.80 533.87 583.23 288.48 294.74 0.00 0.00
November 342.49 660.23 411.12 219.74 191.38 0.00 0.00
December 246.95 828.88 320.64 183.87 136.78 0.00 0.00
               
Annual Sum or Average 605.37 513.60 621.33 237.84 383.49 0.00 0.00
Minimum of Months 246.95 276.04 320.64 90.07 136.78 0.00 0.00
Maximum of Months 1013.82 828.88 879.29 442.68 588.37 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.146937E+10 0.147586E+10 0.150959E+10 0.977552E+09 0.532037E+09 0.00 0.00
February 0.165324E+10 0.129075E+10 0.165454E+10 0.100840E+10 0.646136E+09 0.00 0.00
March 0.915775E+09 0.119142E+10 0.113060E+10 0.326821E+09 0.803783E+09 0.00 0.00
April 0.252595E+10 0.955926E+09 0.224291E+10 0.993833E+09 0.124907E+10 0.00 0.00
May 0.204144E+10 0.845008E+09 0.194297E+10 0.629412E+09 0.131355E+10 0.00 0.00
June 0.192500E+10 0.599065E+09 0.173570E+10 0.419778E+09 0.131592E+10 0.00 0.00
July 0.229841E+10 0.568684E+09 0.193326E+10 0.598097E+09 0.133516E+10 0.00 0.00
August 0.282209E+10 0.625783E+09 0.227063E+10 0.101735E+10 0.125328E+10 0.00 0.00
September 0.321699E+10 0.796770E+09 0.263332E+10 0.155420E+10 0.107911E+10 0.00 0.00
October 0.197269E+10 0.110005E+10 0.181568E+10 0.104679E+10 0.768888E+09 0.00 0.00
November 0.124554E+10 0.130380E+10 0.126888E+10 0.771630E+09 0.497246E+09 0.00 0.00
December 0.982892E+09 0.166819E+10 0.104048E+10 0.667184E+09 0.373294E+09 0.00 0.00
               
Annual Sum or Average 0.230694E+11 0.124213E+11 0.211785E+11 0.100111E+11 0.111675E+11 0.00 0.00
Minimum of Months 0.915775E+09 0.568684E+09 0.104048E+10 0.326821E+09 0.373294E+09 0.00 0.00
Maximum of Months 0.321699E+10 0.166819E+10 0.263332E+10 0.155420E+10 0.133516E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.408845E+10 0.428075E+10 0.425090E+10 0.275272E+10 0.149818E+10 0.00 0.00
February 0.460308E+10 0.375591E+10 0.465908E+10 0.283960E+10 0.181948E+10 0.00 0.00
March 0.252496E+10 0.347918E+10 0.318371E+10 0.920306E+09 0.226340E+10 0.00 0.00
April 0.702213E+10 0.285748E+10 0.631588E+10 0.279857E+10 0.351731E+10 0.00 0.00
May 0.564917E+10 0.255118E+10 0.547127E+10 0.177238E+10 0.369888E+10 0.00 0.00
June 0.531380E+10 0.184719E+10 0.488762E+10 0.118207E+10 0.370556E+10 0.00 0.00
July 0.635997E+10 0.176466E+10 0.544392E+10 0.168420E+10 0.375972E+10 0.00 0.00
August 0.784178E+10 0.195086E+10 0.639395E+10 0.286480E+10 0.352915E+10 0.00 0.00
September 0.896196E+10 0.244532E+10 0.741524E+10 0.437654E+10 0.303871E+10 0.00 0.00
October 0.548820E+10 0.328896E+10 0.511283E+10 0.294769E+10 0.216514E+10 0.00 0.00
November 0.346207E+10 0.383050E+10 0.357307E+10 0.217286E+10 0.140021E+10 0.00 0.00
December 0.273508E+10 0.482000E+10 0.292991E+10 0.187874E+10 0.105117E+10 0.00 0.00
               
Annual Sum or Average 0.640507E+11 0.368720E+11 0.596374E+11 0.281905E+11 0.314469E+11 0.00 0.00
Minimum of Months 0.252496E+10 0.176466E+10 0.292991E+10 0.920306E+09 0.105117E+10 0.00 0.00
Maximum of Months 0.896196E+10 0.482000E+10 0.741524E+10 0.437654E+10 0.375972E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.537334E+10 0.593089E+10 0.552217E+10 0.357594E+10 0.194622E+10 0.00 0.00
February 0.605884E+10 0.518338E+10 0.605241E+10 0.368880E+10 0.236360E+10 0.00 0.00
March 0.328411E+10 0.487453E+10 0.413581E+10 0.119553E+10 0.294029E+10 0.00 0.00
April 0.928141E+10 0.393711E+10 0.820468E+10 0.363550E+10 0.456918E+10 0.00 0.00
May 0.743144E+10 0.355902E+10 0.710749E+10 0.230242E+10 0.480506E+10 0.00 0.00
June 0.696650E+10 0.259668E+10 0.634930E+10 0.153557E+10 0.481373E+10 0.00 0.00
July 0.836429E+10 0.246703E+10 0.707196E+10 0.218787E+10 0.488409E+10 0.00 0.00
August 0.103578E+11 0.268920E+10 0.830611E+10 0.372154E+10 0.458457E+10 0.00 0.00
September 0.118409E+11 0.334190E+10 0.963282E+10 0.568537E+10 0.394745E+10 0.00 0.00
October 0.723004E+10 0.458048E+10 0.664185E+10 0.382922E+10 0.281264E+10 0.00 0.00
November 0.454017E+10 0.534288E+10 0.464162E+10 0.282267E+10 0.181896E+10 0.00 0.00
December 0.358172E+10 0.668532E+10 0.380613E+10 0.244060E+10 0.136553E+10 0.00 0.00
               
Annual Sum or Average 0.843105E+11 0.511884E+11 0.774723E+11 0.366210E+11 0.408513E+11 0.00 0.00
Minimum of Months 0.328411E+10 0.246703E+10 0.380613E+10 0.119553E+10 0.136553E+10 0.00 0.00
Maximum of Months 0.118409E+11 0.668532E+10 0.963282E+10 0.568537E+10 0.488409E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.383681E+09 0.846055E+09 0.494133E+09 0.257408E+09 0.236725E+09 0.00 0.00
February 0.558118E+09 0.744575E+09 0.639747E+09 0.332452E+09 0.307294E+09 0.00 0.00
March 0.371955E+09 0.671432E+09 0.534896E+09 0.124489E+09 0.410407E+09 0.00 0.00
April 0.121941E+10 0.535352E+09 0.115310E+10 0.477853E+09 0.675246E+09 0.00 0.00
May 0.125945E+10 0.474584E+09 0.124465E+10 0.474379E+09 0.770273E+09 0.00 0.00
June 0.135217E+10 0.343762E+09 0.124223E+10 0.453123E+09 0.789105E+09 0.00 0.00
July 0.151327E+10 0.329009E+09 0.132781E+10 0.534771E+09 0.793040E+09 0.00 0.00
August 0.145887E+10 0.362994E+09 0.124466E+10 0.545860E+09 0.698800E+09 0.00 0.00
September 0.131285E+10 0.453028E+09 0.114291E+10 0.588565E+09 0.554349E+09 0.00 0.00
October 0.684413E+09 0.622831E+09 0.701746E+09 0.331451E+09 0.370295E+09 0.00 0.00
November 0.341932E+09 0.743347E+09 0.429837E+09 0.205366E+09 0.224470E+09 0.00 0.00
December 0.208367E+09 0.960165E+09 0.308814E+09 0.152870E+09 0.155944E+09 0.00 0.00
               
Annual Sum or Average 0.106645E+11 0.708713E+10 0.104645E+11 0.447859E+10 0.598595E+10 0.00 0.00
Minimum of Months 0.208367E+09 0.329009E+09 0.308814E+09 0.124489E+09 0.155944E+09 0.00 0.00
Maximum of Months 0.151327E+10 0.960165E+09 0.132781E+10 0.588565E+09 0.793040E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.115748E+09 0.889077E+09 0.247957E+09 64128920.97 0.183828E+09 0.00 0.00
February 0.252994E+09 0.762132E+09 0.386375E+09 0.133073E+09 0.253301E+09 0.00 0.00
March 0.234590E+09 0.676438E+09 0.424373E+09 59871685.24 0.364501E+09 0.00 0.00
April 0.851190E+09 0.526829E+09 0.888354E+09 0.282543E+09 0.605811E+09 0.00 0.00
May 0.102429E+10 0.456217E+09 0.109138E+10 0.361707E+09 0.729674E+09 0.00 0.00
June 0.119352E+10 0.328660E+09 0.114520E+10 0.385523E+09 0.759681E+09 0.00 0.00
July 0.129273E+10 0.314288E+09 0.118742E+10 0.430741E+09 0.756678E+09 0.00 0.00
August 0.108598E+10 0.349459E+09 0.986127E+09 0.348272E+09 0.637855E+09 0.00 0.00
September 0.799759E+09 0.446795E+09 0.762029E+09 0.281355E+09 0.480675E+09 0.00 0.00
October 0.345862E+09 0.626667E+09 0.435230E+09 0.124483E+09 0.310747E+09 0.00 0.00
November 0.115750E+09 0.764046E+09 0.232729E+09 52801937.15 0.179927E+09 0.00 0.00
December 34549002.51 0.999760E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
               
Annual Sum or Average 0.734697E+10 0.714037E+10 0.792811E+10 0.254546E+10 0.538265E+10 0.00 0.00
Minimum of Months 34549002.51 0.314288E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
Maximum of Months 0.129273E+10 0.999760E+09 0.118742E+10 0.430741E+09 0.759681E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.232956E+09 0.237075E+09 0.238730E+09 0.154592E+09 84137898.18 0.00 0.00
February 0.261970E+09 0.210822E+09 0.261653E+09 0.159471E+09 0.102182E+09 0.00 0.00
March 0.149375E+09 0.181867E+09 0.178797E+09 51684172.32 0.127113E+09 0.00 0.00
April 0.394530E+09 0.168992E+09 0.354700E+09 0.157167E+09 0.197533E+09 0.00 0.00
May 0.313374E+09 0.153611E+09 0.307267E+09 99536592.27 0.207730E+09 0.00 0.00
June 0.293748E+09 0.111821E+09 0.274490E+09 66384623.48 0.208105E+09 0.00 0.00
July 0.355407E+09 0.105368E+09 0.305732E+09 94584426.86 0.211147E+09 0.00 0.00
August 0.442325E+09 0.114225E+09 0.359085E+09 0.160887E+09 0.198198E+09 0.00 0.00
September 0.505943E+09 0.144152E+09 0.416440E+09 0.245785E+09 0.170655E+09 0.00 0.00
October 0.310327E+09 0.189690E+09 0.287136E+09 0.165542E+09 0.121594E+09 0.00 0.00
November 0.197132E+09 0.210608E+09 0.200663E+09 0.122027E+09 78636007.32 0.00 0.00
December 0.159075E+09 0.250901E+09 0.164544E+09 0.105510E+09 59033741.75 0.00 0.00
               
Annual Sum or Average 0.361616E+10 0.207913E+10 0.334924E+10 0.158317E+10 0.176607E+10 0.00 0.00
Minimum of Months 0.149375E+09 0.105368E+09 0.164544E+09 51684172.32 59033741.75 0.00 0.00
Maximum of Months 0.505943E+09 0.250901E+09 0.416440E+09 0.245785E+09 0.211147E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 2961612.78 0.270088E+09 41842464.75 0.00 41842464.75 0.00 0.00
February 8158972.53 0.227827E+09 59015680.35 0.00 59015680.35 0.00 0.00
March 30886238.15 0.203159E+09 90426079.04 611.18 90425467.87 0.00 0.00
April 99614321.14 0.149015E+09 0.142993E+09 950366.37 0.142043E+09 0.00 0.00
May 0.129202E+09 0.123581E+09 0.184736E+09 9420490.59 0.175316E+09 0.00 0.00
June 0.178684E+09 87260444.39 0.196951E+09 12319448.80 0.184631E+09 0.00 0.00
July 0.188672E+09 81371686.01 0.193505E+09 11381086.97 0.182124E+09 0.00 0.00
August 0.147912E+09 90352484.35 0.152351E+09 2849117.93 0.149502E+09 0.00 0.00
September 94070990.96 0.123375E+09 0.111830E+09 66094.90 0.111764E+09 0.00 0.00
October 34018414.38 0.184091E+09 73990137.15 0.00 73990137.15 0.00 0.00
November 4733873.53 0.228687E+09 43022945.85 0.00 43022945.85 0.00 0.00
December 91599.13 0.297921E+09 30275127.60 0.00 30275127.60 0.00 0.00
               
Annual Sum or Average 0.919006E+09 0.206673E+10 0.132094E+10 36987216.73 0.128395E+10 0.00 0.00
Minimum of Months 91599.13 81371686.01 30275127.60 0.00 30275127.60 0.00 0.00
Maximum of Months 0.188672E+09 0.297921E+09 0.196951E+09 12319448.80 0.184631E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.384135E+09 0.841410E+09 0.496934E+09 0.272321E+09 0.224613E+09 0.00 0.00
February 0.490372E+09 0.733301E+09 0.597830E+09 0.300245E+09 0.297585E+09 0.00 0.00
March 0.367858E+09 0.667095E+09 0.534921E+09 0.126033E+09 0.408888E+09 0.00 0.00
April 0.132137E+10 0.513158E+09 0.125073E+10 0.574996E+09 0.675737E+09 0.00 0.00
May 0.126919E+10 0.458582E+09 0.126247E+10 0.507539E+09 0.754926E+09 0.00 0.00
June 0.127350E+10 0.330229E+09 0.118426E+10 0.418994E+09 0.765270E+09 0.00 0.00
July 0.143946E+10 0.312983E+09 0.126927E+10 0.495041E+09 0.774234E+09 0.00 0.00
August 0.151945E+10 0.342008E+09 0.129158E+10 0.604548E+09 0.687035E+09 0.00 0.00
September 0.144316E+10 0.434323E+09 0.125276E+10 0.696307E+09 0.556457E+09 0.00 0.00
October 0.711689E+09 0.617338E+09 0.726948E+09 0.360841E+09 0.366107E+09 0.00 0.00
November 0.343128E+09 0.737254E+09 0.435166E+09 0.215271E+09 0.219895E+09 0.00 0.00
December 0.253172E+09 0.954120E+09 0.347365E+09 0.184917E+09 0.162448E+09 0.00 0.00
               
Annual Sum or Average 0.108165E+11 0.694180E+10 0.106502E+11 0.475705E+10 0.589319E+10 0.00 0.00
Minimum of Months 0.253172E+09 0.312983E+09 0.347365E+09 0.126033E+09 0.162448E+09 0.00 0.00
Maximum of Months 0.151945E+10 0.954120E+09 0.129158E+10 0.696307E+09 0.774234E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.103972E+09 0.871517E+09 0.250758E+09 79042420.23 0.171716E+09 0.00 0.00
February 0.176945E+09 0.742779E+09 0.344458E+09 0.100866E+09 0.243592E+09 0.00 0.00
March 0.228666E+09 0.670375E+09 0.424398E+09 61415498.09 0.362983E+09 0.00 0.00
April 0.950157E+09 0.505239E+09 0.985989E+09 0.379686E+09 0.606302E+09 0.00 0.00
May 0.103437E+10 0.443069E+09 0.110919E+10 0.394867E+09 0.714327E+09 0.00 0.00
June 0.111758E+10 0.319865E+09 0.108724E+10 0.351394E+09 0.735845E+09 0.00 0.00
July 0.121947E+10 0.301682E+09 0.112888E+10 0.391012E+09 0.737872E+09 0.00 0.00
August 0.114511E+10 0.332434E+09 0.103305E+10 0.406961E+09 0.626091E+09 0.00 0.00
September 0.920906E+09 0.425709E+09 0.871879E+09 0.389097E+09 0.482782E+09 0.00 0.00
October 0.364732E+09 0.613609E+09 0.460432E+09 0.153873E+09 0.306559E+09 0.00 0.00
November 0.103494E+09 0.743857E+09 0.238058E+09 62706204.31 0.175352E+09 0.00 0.00
December 55910068.00 0.967969E+09 0.179483E+09 53003264.31 0.126480E+09 0.00 0.00
               
Annual Sum or Average 0.742131E+10 0.693810E+10 0.811382E+10 0.282392E+10 0.528990E+10 0.00 0.00
Minimum of Months 55910068.00 0.301682E+09 0.179483E+09 53003264.31 0.126480E+09 0.00 0.00
Maximum of Months 0.121947E+10 0.967969E+09 0.112888E+10 0.406961E+09 0.737872E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.464415E+09 0.107852E+10 0.607907E+09 0.334959E+09 0.272948E+09 0.00 0.00
February 0.565458E+09 0.942988E+09 0.694778E+09 0.345530E+09 0.349248E+09 0.00 0.00
March 0.373742E+09 0.866428E+09 0.583296E+09 0.111987E+09 0.471310E+09 0.00 0.00
April 0.109173E+10 0.678933E+09 0.107831E+10 0.342596E+09 0.735711E+09 0.00 0.00
May 0.963725E+09 0.589602E+09 0.106596E+10 0.236076E+09 0.829887E+09 0.00 0.00
June 0.102431E+10 0.427055E+09 0.102140E+10 0.170525E+09 0.850879E+09 0.00 0.00
July 0.117299E+10 0.407558E+09 0.108163E+10 0.229593E+09 0.852038E+09 0.00 0.00
August 0.127738E+10 0.457765E+09 0.110808E+10 0.354769E+09 0.753311E+09 0.00 0.00
September 0.130548E+10 0.589453E+09 0.114457E+10 0.532692E+09 0.611878E+09 0.00 0.00
October 0.747974E+09 0.800044E+09 0.782431E+09 0.358683E+09 0.423749E+09 0.00 0.00
November 0.416198E+09 0.950562E+09 0.527984E+09 0.264399E+09 0.263584E+09 0.00 0.00
December 0.300444E+09 0.123600E+10 0.422106E+09 0.228611E+09 0.193496E+09 0.00 0.00
               
Annual Sum or Average 0.970384E+10 0.902490E+10 0.101185E+11 0.351042E+10 0.660804E+10 0.00 0.00
Minimum of Months 0.300444E+09 0.407558E+09 0.422106E+09 0.111987E+09 0.193496E+09 0.00 0.00
Maximum of Months 0.130548E+10 0.123600E+10 0.114457E+10 0.532692E+09 0.852038E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.385519E+09 0.835114E+09 0.494133E+09 0.257408E+09 0.236725E+09 0.00 0.00
February 0.558194E+09 0.738416E+09 0.639747E+09 0.332452E+09 0.307294E+09 0.00 0.00
March 0.372109E+09 0.663163E+09 0.534896E+09 0.124489E+09 0.410407E+09 0.00 0.00
April 0.120698E+10 0.532555E+09 0.115310E+10 0.477853E+09 0.675246E+09 0.00 0.00
May 0.124315E+10 0.475174E+09 0.124465E+10 0.474379E+09 0.770273E+09 0.00 0.00
June 0.133339E+10 0.345644E+09 0.124223E+10 0.453123E+09 0.789105E+09 0.00 0.00
July 0.149137E+10 0.333429E+09 0.132781E+10 0.534771E+09 0.793040E+09 0.00 0.00
August 0.144130E+10 0.366767E+09 0.124466E+10 0.545860E+09 0.698800E+09 0.00 0.00
September 0.130223E+10 0.452938E+09 0.114291E+10 0.588565E+09 0.554349E+09 0.00 0.00
October 0.682720E+09 0.615219E+09 0.701746E+09 0.331451E+09 0.370295E+09 0.00 0.00
November 0.342945E+09 0.734712E+09 0.429837E+09 0.205366E+09 0.224470E+09 0.00 0.00
December 0.209652E+09 0.952497E+09 0.308814E+09 0.152870E+09 0.155944E+09 0.00 0.00
               
Annual Sum or Average 0.105696E+11 0.704563E+10 0.104645E+11 0.447859E+10 0.598595E+10 0.00 0.00
Minimum of Months 0.209652E+09 0.333429E+09 0.308814E+09 0.124489E+09 0.155944E+09 0.00 0.00
Maximum of Months 0.149137E+10 0.952497E+09 0.132781E+10 0.588565E+09 0.793040E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117472E+09 0.877174E+09 0.247957E+09 64128920.97 0.183828E+09 0.00 0.00
February 0.254187E+09 0.754429E+09 0.386375E+09 0.133073E+09 0.253301E+09 0.00 0.00
March 0.235726E+09 0.667631E+09 0.424373E+09 59871685.24 0.364501E+09 0.00 0.00
April 0.840848E+09 0.523196E+09 0.888354E+09 0.282543E+09 0.605811E+09 0.00 0.00
May 0.100951E+10 0.456329E+09 0.109138E+10 0.361707E+09 0.729674E+09 0.00 0.00
June 0.117508E+10 0.330368E+09 0.114520E+10 0.385523E+09 0.759681E+09 0.00 0.00
July 0.127177E+10 0.318288E+09 0.118742E+10 0.430741E+09 0.756678E+09 0.00 0.00
August 0.107028E+10 0.351954E+09 0.986127E+09 0.348272E+09 0.637855E+09 0.00 0.00
September 0.793325E+09 0.444206E+09 0.762029E+09 0.281355E+09 0.480675E+09 0.00 0.00
October 0.346690E+09 0.617120E+09 0.435230E+09 0.124483E+09 0.310747E+09 0.00 0.00
November 0.117589E+09 0.754191E+09 0.232729E+09 52801937.15 0.179927E+09 0.00 0.00
December 35240029.94 0.991097E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
               
Annual Sum or Average 0.726772E+10 0.708598E+10 0.792811E+10 0.254546E+10 0.538265E+10 0.00 0.00
Minimum of Months 35240029.94 0.318288E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
Maximum of Months 0.127177E+10 0.991097E+09 0.118742E+10 0.430741E+09 0.759681E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.421214E+09 0.436861E+09 0.437738E+09 0.283462E+09 0.154276E+09 0.00 0.00
February 0.474086E+09 0.386471E+09 0.479770E+09 0.292408E+09 0.187362E+09 0.00 0.00
March 0.260438E+09 0.351771E+09 0.327844E+09 94768591.74 0.233075E+09 0.00 0.00
April 0.723385E+09 0.283489E+09 0.650381E+09 0.288183E+09 0.362198E+09 0.00 0.00
May 0.577418E+09 0.254931E+09 0.563408E+09 0.182511E+09 0.380897E+09 0.00 0.00
June 0.543900E+09 0.179208E+09 0.503307E+09 0.121723E+09 0.381584E+09 0.00 0.00
July 0.652623E+09 0.170591E+09 0.560592E+09 0.173431E+09 0.387162E+09 0.00 0.00
August 0.807979E+09 0.187744E+09 0.658421E+09 0.295003E+09 0.363418E+09 0.00 0.00
September 0.924739E+09 0.237621E+09 0.763588E+09 0.450674E+09 0.312914E+09 0.00 0.00
October 0.567974E+09 0.325414E+09 0.526495E+09 0.303539E+09 0.222957E+09 0.00 0.00
November 0.356079E+09 0.387665E+09 0.367938E+09 0.223750E+09 0.144188E+09 0.00 0.00
December 0.281387E+09 0.499254E+09 0.301709E+09 0.193464E+09 0.108245E+09 0.00 0.00
               
Annual Sum or Average 0.659122E+10 0.370102E+10 0.614119E+10 0.290292E+10 0.323827E+10 0.00 0.00
Minimum of Months 0.260438E+09 0.170591E+09 0.301709E+09 94768591.74 0.108245E+09 0.00 0.00
Maximum of Months 0.924739E+09 0.499254E+09 0.763588E+09 0.450674E+09 0.387162E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 7595587.21 0.278282E+10 0.366059E+09 0.00 0.366059E+09 0.00 0.00
February 27183880.51 0.236813E+10 0.516299E+09 0.00 0.516299E+09 0.00 0.00
March 0.174637E+09 0.211396E+10 0.791093E+09 5346.90 0.791088E+09 0.00 0.00
April 0.694644E+09 0.155246E+10 0.125098E+10 8314288.68 0.124266E+10 0.00 0.00
May 0.891767E+09 0.131925E+10 0.161617E+10 82415246.22 0.153375E+10 0.00 0.00
June 0.132005E+10 0.954384E+09 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00
July 0.140886E+10 0.893001E+09 0.169288E+10 99567541.14 0.159331E+10 0.00 0.00
August 0.108515E+10 0.995966E+09 0.133284E+10 24925533.69 0.130792E+10 0.00 0.00
September 0.656552E+09 0.133917E+10 0.978343E+09 578231.83 0.977764E+09 0.00 0.00
October 0.197330E+09 0.196215E+10 0.647303E+09 0.00 0.647303E+09 0.00 0.00
November 13108852.22 0.242301E+10 0.376387E+09 0.00 0.376387E+09 0.00 0.00
December 0.00 0.308575E+10 0.264862E+09 0.00 0.264862E+09 0.00 0.00
               
Annual Sum or Average 0.647687E+10 0.217900E+11 0.115562E+11 0.323583E+09 0.112327E+11 0.00 0.00
Minimum of Months 0.00 0.893001E+09 0.264862E+09 0.00 0.264862E+09 0.00 0.00
Maximum of Months 0.140886E+10 0.308575E+10 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 5053032.00 0.286766E+10 0.366059E+09 0.00 0.366059E+09 0.00 0.00
February 20962756.50 0.244120E+10 0.516299E+09 0.00 0.516299E+09 0.00 0.00
March 0.153754E+09 0.217628E+10 0.791093E+09 5346.90 0.791088E+09 0.00 0.00
April 0.664883E+09 0.158822E+10 0.125098E+10 8314288.68 0.124266E+10 0.00 0.00
May 0.855108E+09 0.134885E+10 0.161617E+10 82415246.22 0.153375E+10 0.00 0.00
June 0.128640E+10 0.974874E+09 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00
July 0.137698E+10 0.912128E+09 0.169288E+10 99567541.14 0.159331E+10 0.00 0.00
August 0.105636E+10 0.101915E+10 0.133284E+10 24925533.69 0.130792E+10 0.00 0.00
September 0.630650E+09 0.137034E+10 0.978343E+09 578231.83 0.977764E+09 0.00 0.00
October 0.177674E+09 0.202047E+10 0.647303E+09 0.00 0.647303E+09 0.00 0.00
November 9214415.33 0.250349E+10 0.376387E+09 0.00 0.376387E+09 0.00 0.00
December 0.00 0.317876E+10 0.264862E+09 0.00 0.264862E+09 0.00 0.00
               
Annual Sum or Average 0.623704E+10 0.224014E+11 0.115562E+11 0.323583E+09 0.112327E+11 0.00 0.00
Minimum of Months 0.00 0.912128E+09 0.264862E+09 0.00 0.264862E+09 0.00 0.00
Maximum of Months 0.137698E+10 0.317876E+10 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.483180E+09 0.180905E+10 0.747665E+09 0.351352E+09 0.396312E+09 0.00 0.00
February 0.676540E+09 0.159393E+10 0.942249E+09 0.401097E+09 0.541152E+09 0.00 0.00
March 0.628887E+09 0.146018E+10 0.959275E+09 0.187440E+09 0.771835E+09 0.00 0.00
April 0.243776E+10 0.112275E+10 0.223661E+10 0.954629E+09 0.128198E+10 0.00 0.00
May 0.245625E+10 0.105330E+10 0.237153E+10 0.902352E+09 0.146918E+10 0.00 0.00
June 0.259549E+10 0.777283E+09 0.227138E+10 0.770339E+09 0.150104E+10 0.00 0.00
July 0.291399E+10 0.734853E+09 0.239803E+10 0.885999E+09 0.151203E+10 0.00 0.00
August 0.292185E+10 0.772466E+09 0.232452E+10 0.101145E+10 0.131306E+10 0.00 0.00
September 0.256030E+10 0.954963E+09 0.212454E+10 0.108535E+10 0.103919E+10 0.00 0.00
October 0.114797E+10 0.137330E+10 0.118733E+10 0.514692E+09 0.672635E+09 0.00 0.00
November 0.454226E+09 0.163781E+10 0.673197E+09 0.277968E+09 0.395230E+09 0.00 0.00
December 0.303635E+09 0.211072E+10 0.526828E+09 0.237913E+09 0.288915E+09 0.00 0.00
               
Annual Sum or Average 0.195801E+11 0.154006E+11 0.187632E+11 0.758058E+10 0.111826E+11 0.00 0.00
Minimum of Months 0.303635E+09 0.734853E+09 0.526828E+09 0.187440E+09 0.288915E+09 0.00 0.00
Maximum of Months 0.292185E+10 0.211072E+10 0.239803E+10 0.108535E+10 0.151203E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.101257E+10 0.192264E+10 0.123977E+10 0.721568E+09 0.518204E+09 0.00 0.00
February 0.119777E+10 0.168870E+10 0.139827E+10 0.744341E+09 0.653928E+09 0.00 0.00
March 0.731317E+09 0.155522E+10 0.110573E+10 0.241240E+09 0.864492E+09 0.00 0.00
April 0.213209E+10 0.122162E+10 0.208442E+10 0.736435E+09 0.134798E+10 0.00 0.00
May 0.181261E+10 0.107175E+10 0.198821E+10 0.492844E+09 0.149537E+10 0.00 0.00
June 0.185659E+10 0.778809E+09 0.187185E+10 0.346800E+09 0.152505E+10 0.00 0.00
July 0.216495E+10 0.739337E+09 0.200734E+10 0.475610E+09 0.153173E+10 0.00 0.00
August 0.246922E+10 0.817082E+09 0.213295E+10 0.759491E+09 0.137346E+10 0.00 0.00
September 0.262782E+10 0.104043E+10 0.227913E+10 0.114741E+10 0.113172E+10 0.00 0.00
October 0.153687E+10 0.142992E+10 0.156212E+10 0.772674E+09 0.789445E+09 0.00 0.00
November 0.887746E+09 0.171130E+10 0.106563E+10 0.569569E+09 0.496064E+09 0.00 0.00
December 0.661440E+09 0.222007E+10 0.858811E+09 0.492473E+09 0.366338E+09 0.00 0.00
               
Annual Sum or Average 0.190910E+11 0.161969E+11 0.195942E+11 0.750046E+10 0.120938E+11 0.00 0.00
Minimum of Months 0.661440E+09 0.739337E+09 0.858811E+09 0.241240E+09 0.366338E+09 0.00 0.00
Maximum of Months 0.262782E+10 0.222007E+10 0.227913E+10 0.114741E+10 0.153173E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.18 3.23 2.03 1.05 -4.0 28.28 62.93 0.00
February 4.25 3.55 2.74 1.60 -5.0 43.80 86.73 0.02
March 5.90 4.45 2.76 1.18 -1.9 68.95 35.00 0.00
April 8.96 6.24 3.38 1.56 -0.7 96.13 186.12 0.00
May 9.99 8.07 6.28 3.35 -0.9 110.92 199.68 0.02
June 13.31 11.27 9.70 3.33 3.35 121.69 199.28 0.00
July 15.02 12.39 10.49 3.21 4.49 111.91 220.83 0.00
August 15.65 12.75 10.65 2.92 3.95 91.47 211.91 0.00
September 13.43 11.01 9.10 2.64 1.43 68.72 198.32 0.01
October 9.33 8.03 6.81 1.97 -1.0 48.92 91.86 0.04
November 6.66 5.66 4.54 2.05 -2.3 30.27 53.24 0.04
December 4.10 3.14 1.95 2.36 -5.1 20.52 40.74 0.04
                 
Annual Sum or Average 9.26 7.50 5.89 2.27 -0.6 70.25 132.30 0.02
Minimum of Months 4.10 3.14 1.95 1.05 -5.1 20.52 35.00 0.00
Maximum of Months 15.65 12.75 10.65 3.35 4.49 121.69 220.83 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 29-JAN-05:00 9.37 5.00 3.60 8.35 0.00 0.00
February 11.00 07-FEB-14:00 9.86 9.00 2.10 6.35 138.00 225.00
March 14.00 25-MAR-12:00 11.22 9.00 2.60 7.35 287.00 93.00
April 24.00 30-APR-14:00 13.13 4.00 1.50 7.75 167.50 716.00
May 24.00 22-MAY-14:00 16.08 11.00 2.60 9.33 159.00 769.00
June 27.00 13-JUN-16:00 17.53 12.00 3.10 12.41 141.50 652.50
July 30.00 22-JUL-17:00 16.80 8.00 0.00 14.28 122.00 407.00
August 27.00 14-AUG-17:19 14.18 3.33 2.60 10.37 133.00 358.83
September 23.00 11-SEP-16:00 16.22 12.00 2.60 8.74 108.00 325.50
October 19.00 07-OCT-14:00 10.10 1.00 1.50 2.22 131.00 540.50
November 16.00 24-NOV-11:00 12.01 9.00 4.10 9.33 61.50 0.00
December 13.00 23-DEC-10:00 7.64 2.00 7.70 6.75 70.50 0.00
                 
Annual Sum or Average                
Minimum of Months 11.00   7.64 1.00 0.00 2.22 0.00 0.00
Maximum of Months 30.00   17.53 12.00 7.70 14.28 287.00 769.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.0 10-JAN-07:00 -7.0 -9.0 0.00 -20.0 0.00 0.00
February -4.0 17-FEB-06:00 -4.0 -4.0 0.00 -20.5 0.00 0.00
March -1.0 08-MAR-06:00 -1.4 -2.0 0.00 -14.4 17.50 184.50
April 0.00 08-APR-04:00 -0.9 -2.0 0.00 -12.7 0.00 0.00
May 2.00 06-MAY-04:00 1.57 1.00 3.60 -13.7 12.50 117.00
June 6.00 01-JUN-03:00 5.05 4.00 0.00 -9.2 0.00 0.00
July 7.00 05-JUL-04:00 6.47 6.00 3.10 -7.8 28.00 155.00
August 8.00 20-AUG-04:00 7.45 7.00 0.00 -6.6 0.00 0.00
September 5.00 20-SEP-03:00 5.00 5.00 2.60 -10.0 0.00 0.00
October 2.00 07-OCT-03:00 2.00 2.00 0.00 -13.4 0.00 0.00
November -2.0 29-NOV-01:00 -2.0 -2.0 3.10 -10.7 0.00 0.00
December -3.0 29-DEC-20:00 -4.5 -7.0 3.60 -20.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -6.0   -7.0 -9.0 0.00 -20.5 0.00 0.00
Maximum of Months 8.00   7.45 7.00 3.60 -6.6 28.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.44 29-JAN-04:00 13.00 12.00 0.00 9.13 0.00 0.00
February 9.86 07-FEB-14:00 11.00 9.00 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.39 28-APR-07:00 16.00 15.00 0.00 5.54 119.50 626.00
May 16.08 22-MAY-14:00 24.00 11.00 2.60 9.33 159.00 769.00
June 19.93 25-JUN-17:00 22.00 19.00 0.00 15.94 136.50 360.50
July 17.31 22-JUL-09:00 26.00 12.00 4.60 11.46 224.50 619.50
August 17.06 14-AUG-12:00 24.00 13.00 2.60 9.91 205.50 669.50
September 16.54 10-SEP-15:00 21.00 14.00 3.60 8.54 160.50 483.00
October 13.58 17-OCT-14:00 16.00 12.00 0.00 12.03 144.00 44.50
November 12.01 24-NOV-11:00 16.00 9.00 4.10 9.33 61.50 0.00
December 7.93 02-DEC-12:00 9.00 7.00 0.00 2.01 135.50 84.00
                 
Annual Sum or Average                
Minimum of Months 7.93   9.00 7.00 0.00 2.01 0.00 0.00
Maximum of Months 19.93   26.00 19.00 4.60 15.94 224.50 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.00 29-JAN-04:00 13.00 12.44 0.00 9.13 0.00 0.00
February 9.00 07-FEB-14:00 11.00 9.86 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.00 28-APR-07:00 16.00 15.39 0.00 5.54 119.50 626.00
May 12.00 23-MAY-07:00 17.00 13.95 3.10 5.13 112.00 719.50
June 19.00 25-JUN-17:00 22.00 19.93 0.00 15.94 136.50 360.50
July 14.00 17-JUL-17:00 18.00 15.45 3.60 9.91 120.00 0.00
August 16.00 08-AUG-12:00 18.00 16.70 1.50 11.46 154.00 0.00
September 14.00 10-SEP-15:00 21.00 16.54 3.60 8.54 160.50 483.00
October 13.00 17-OCT-18:00 13.00 13.00 2.60 9.33 0.00 0.00
November 12.00 08-NOV-14:00 12.00 12.00 0.00 8.15 93.00 106.00
December 7.00 02-DEC-11:00 8.00 7.45 3.10 1.16 144.50 146.50
                 
Annual Sum or Average                
Minimum of Months 7.00   8.00 7.45 0.00 1.16 0.00 0.00
Maximum of Months 19.00   22.00 19.93 3.60 15.94 160.50 719.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.33 8.85 0.00
February 18.00 13.00 16.00 10.00 14.79 0.00
March 18.00 13.00 16.00 10.33 17.09 0.00
April 18.00 13.00 16.00 11.26 40.86 0.00
May 18.00 13.00 16.00 12.54 47.73 0.00
June 18.00 13.00 16.00 13.82 50.98 0.00
July 18.00 13.00 16.00 14.77 51.67 0.00
August 18.00 13.00 16.00 15.12 44.67 0.00
September 18.00 13.00 16.00 14.78 34.25 0.00
October 18.00 13.00 16.00 13.84 17.71 0.00
November 18.00 13.00 16.00 12.55 9.34 0.00
December 18.00 13.00 16.00 11.27 6.14 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.57 28.73 0.00
Minimum of Months 18.00 13.00 16.00 10.00 6.14 0.00
Maximum of Months 18.00 13.00 16.00 15.12 51.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770448E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161695749.8 81.21 0.00 0.00
February 0.696203E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -146063208.8 81.21 0.00 0.00
March 0.770295E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161489148.9 81.21 0.00 0.00
April 0.746477E+10 -0.730857E+10 0.00 0.00 720.00 0.00 -156192412.0 81.21 0.00 0.00
May 0.770415E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -161363936.5 81.21 0.00 0.00
June 0.745688E+10 -0.730052E+10 0.00 0.00 720.00 0.00 -156360457.2 81.21 0.00 0.00
July 0.771241E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161571488.6 81.21 0.00 0.00
August 0.770440E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161603682.3 81.21 0.00 0.00
September 0.746627E+10 -0.730992E+10 0.00 0.00 720.00 0.00 -156349874.1 81.21 0.00 0.00
October 0.770279E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -161353329.6 81.21 0.00 0.00
November 0.744870E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156269790.9 81.21 0.00 0.00
December 0.771264E+10 -0.755087E+10 0.00 0.00 744.00 0.00 -161777936.0 81.21 0.00 0.00
                     
Annual Sum or Average 0.907425E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190209E+10 81.21 0.00 0.00
Minimum of Months 0.696203E+10 -0.755087E+10 0.00 0.00 672.00 0.00 -161777936.0 81.21 0.00 0.00
Maximum of Months 0.771264E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -146063208.8 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.121896E+12 -0.120147E+12 0.00 0.00 744.00 0.00 -0.174863E+10 81.27 0.00 0.00
February 0.110619E+12 -0.109035E+12 0.00 0.00 672.00 0.00 -0.158365E+10 81.27 0.00 0.00
March 0.121897E+12 -0.120138E+12 0.00 0.00 744.00 0.00 -0.175897E+10 81.27 0.00 0.00
April 0.116428E+12 -0.114726E+12 0.00 0.00 720.00 0.00 -0.170265E+10 81.27 0.00 0.00
May 0.118123E+12 -0.116364E+12 0.00 0.00 744.00 0.00 -0.175900E+10 81.26 0.00 0.00
June 0.112189E+12 -0.110488E+12 0.00 0.00 720.00 0.00 -0.170067E+10 81.26 0.00 0.00
July 0.114312E+12 -0.112561E+12 0.00 0.00 744.00 0.00 -0.175055E+10 81.26 0.00 0.00
August 0.113705E+12 -0.111958E+12 0.00 0.00 744.00 0.00 -0.174739E+10 81.26 0.00 0.00
September 0.110597E+12 -0.108914E+12 0.00 0.00 720.00 0.00 -0.168317E+10 81.25 0.00 0.00
October 0.115886E+12 -0.114149E+12 0.00 0.00 744.00 0.00 -0.173661E+10 81.26 0.00 0.00
November 0.114263E+12 -0.112583E+12 0.00 0.00 720.00 0.00 -0.167998E+10 81.26 0.00 0.00
December 0.120265E+12 -0.118524E+12 0.00 0.00 744.00 0.00 -0.174069E+10 81.26 0.00 0.00
                     
Annual Sum or Average 0.139018E+13 -0.136959E+13 0.00 0.00 8760.00 0.00 -0.205920E+11 81.26 0.00 0.00
Minimum of Months 0.110597E+12 -0.120147E+12 0.00 0.00 672.00 0.00 -0.175900E+10 81.25 0.00 0.00
Maximum of Months 0.121897E+12 -0.108914E+12 0.00 0.00 744.00 0.00 -0.158365E+10 81.27 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.725859E+11 -0.710932E+11 0.00 0.00 744.00 0.00 -0.149277E+10 58.98 0.00 0.00
February 0.660110E+11 -0.646569E+11 0.00 0.00 672.00 0.00 -0.135411E+10 58.98 0.00 0.00
March 0.726578E+11 -0.711507E+11 0.00 0.00 744.00 0.00 -0.150709E+10 58.99 0.00 0.00
April 0.689659E+11 -0.675067E+11 0.00 0.00 720.00 0.00 -0.145920E+10 58.98 0.00 0.00
May 0.694070E+11 -0.678994E+11 0.00 0.00 744.00 0.00 -0.150760E+10 58.98 0.00 0.00
June 0.653686E+11 -0.639117E+11 0.00 0.00 720.00 0.00 -0.145687E+10 58.98 0.00 0.00
July 0.660919E+11 -0.645959E+11 0.00 0.00 744.00 0.00 -0.149600E+10 58.98 0.00 0.00
August 0.656353E+11 -0.641438E+11 0.00 0.00 744.00 0.00 -0.149152E+10 58.98 0.00 0.00
September 0.639611E+11 -0.625283E+11 0.00 0.00 720.00 0.00 -0.143277E+10 58.98 0.00 0.00
October 0.674371E+11 -0.659604E+11 0.00 0.00 744.00 0.00 -0.147673E+10 58.98 0.00 0.00
November 0.670769E+11 -0.656487E+11 0.00 0.00 720.00 0.00 -0.142812E+10 58.98 0.00 0.00
December 0.711895E+11 -0.697075E+11 0.00 0.00 744.00 0.00 -0.148202E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.816388E+12 -0.798803E+12 0.00 0.00 8760.00 0.00 -0.175848E+11 58.98 0.00 0.00
Minimum of Months 0.639611E+11 -0.711507E+11 0.00 0.00 672.00 0.00 -0.150760E+10 58.98 0.00 0.00
Maximum of Months 0.726578E+11 -0.625283E+11 0.00 0.00 744.00 0.00 -0.135411E+10 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.87 0.86 01-JAN-08:39 3548.17 36.67 191.67 227.50 2858.81 37.61 192.00 190.00
February 217.00 0.87 0.86 01-FEB-11:39 5219.29 36.01 212.17 249.00 2288.98 32.06 197.33 215.00
March 215.50 0.87 0.86 01-MAR-11:39 3384.43 29.75 164.33 316.33 702.96 21.87 143.83 256.17
April 359.67 0.87 0.86 01-APR-07:19 1964.80 21.08 205.83 361.00 774.65 22.79 287.33 321.67
May 417.17 0.87 0.86 01-MAY-07:10 1576.27 20.60 182.17 414.50 619.99 22.30 303.50 359.00
June 410.67 0.87 0.86 01-JUN-06:19 1544.56 20.81 180.83 418.33 605.10 22.50 308.67 358.33
July 429.00 0.87 0.86 01-JUL-06:30 1509.84 20.67 193.50 425.50 602.58 22.38 322.50 369.00
August 396.33 0.87 0.86 01-AUG-06:40 1718.85 20.79 220.67 386.67 689.96 22.51 306.33 338.33
September 337.67 0.87 0.86 01-SEP-07:00 5913.59 27.43 228.00 333.67 827.54 22.91 267.83 294.00
October 234.00 0.87 0.86 01-OCT-06:00 6655.88 35.28 217.00 284.50 1153.31 25.57 195.83 233.83
November 171.33 0.87 0.86 01-NOV-11:50 4136.89 36.39 167.33 223.33 3019.40 36.64 165.83 168.17
December 131.67 0.87 0.86 02-DEC-08:50 3403.47 37.46 128.67 188.17 2738.13 38.41 128.67 127.00
                         
Annual Sum or Average 3515.67 0.87     3013.62 26.14 2292.17 3828.50 1124.24 25.41 2819.67 3230.50
Minimum of Months 131.67 0.87 0.86   1509.84 20.60 128.67 188.17 602.58 21.87 128.67 127.00
Maximum of Months 429.00 0.87 0.86   6655.88 37.46 228.00 425.50 3019.40 38.41 322.50 369.00



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.26 0.22 01-JAN-08:39 3897.51 36.74 191.67 235.83 3207.60 37.66 192.17 215.17
February 217.00 0.25 0.22 01-FEB-11:39 5616.53 36.08 212.17 255.83 2681.94 32.08 203.50 237.17
March 215.50 0.27 0.22 01-MAR-11:39 3646.84 30.01 166.67 327.83 964.40 22.28 196.67 291.00
April 359.67 0.26 0.22 01-APR-06:49 2338.73 21.32 202.17 369.00 1147.39 22.89 304.67 347.50
May 417.17 0.26 0.22 01-MAY-06:49 1863.21 21.03 199.33 426.67 905.94 22.57 333.50 397.33
June 410.67 0.24 0.22 01-JUN-05:40 1810.68 21.29 206.50 431.83 870.26 22.82 331.50 394.83
July 429.00 0.26 0.22 01-JUL-05:30 1790.09 21.11 211.50 438.33 881.90 22.65 350.33 408.67
August 396.33 0.26 0.22 01-AUG-05:00 2065.83 21.07 192.33 396.17 1035.88 22.65 323.00 368.33
September 337.67 0.26 0.22 01-SEP-07:40 6361.72 27.64 220.33 341.00 1274.65 22.87 279.17 320.83
October 234.00 0.25 0.22 01-OCT-06:49 7074.90 35.41 217.33 293.00 1572.25 25.59 212.83 267.50
November 171.33 0.26 0.22 01-NOV-11:39 4496.38 36.46 167.50 234.33 3378.09 36.69 166.33 198.17
December 131.67 0.26 0.22 02-DEC-08:39 3754.05 37.53 128.67 199.33 3087.33 38.46 128.67 159.50
                         
Annual Sum or Average 3515.67 0.26     3351.95 26.42 2316.17 3949.17 1461.43 25.57 3022.33 3606.00
Minimum of Months 131.67 0.24 0.22   1790.09 21.03 128.67 199.33 870.26 22.28 128.67 159.50
Maximum of Months 429.00 0.27 0.22   7074.90 37.53 220.33 438.33 3378.09 38.46 350.33 408.67



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.69 0.60 01-JAN-10:30 388.18 14.37 0.00 208.00 180.64 17.77 0.00 79.67
February 217.00 0.65 0.60 01-FEB-11:00 506.14 15.89 0.00 238.83 234.18 19.18 0.00 147.67
March 215.50 0.64 0.60 01-MAR-11:39 648.69 16.42 0.00 316.50 271.27 19.53 6.33 230.67
April 359.67 0.62 0.60 01-APR-07:10 812.97 18.34 0.00 369.67 375.69 21.53 203.67 338.50
May 417.17 0.61 0.60 01-MAY-06:49 985.96 19.78 30.00 434.00 447.21 23.71 290.17 410.33
June 410.67 0.61 0.60 01-JUN-04:49 1127.15 20.70 49.83 438.83 514.38 24.16 308.83 411.50
July 429.00 0.61 0.60 01-JUL-04:49 1037.29 20.84 61.50 447.00 481.41 23.81 316.17 423.17
August 396.33 0.62 0.60 01-AUG-05:40 817.94 18.62 6.83 400.50 386.06 21.82 237.00 367.17
September 337.67 0.63 0.60 01-SEP-07:49 639.47 17.55 0.00 334.83 316.63 20.79 79.17 290.50
October 234.00 0.64 0.60 01-OCT-07:49 561.97 16.54 0.00 276.67 265.38 19.79 1.00 183.50
November 171.33 0.68 0.60 01-NOV-12:20 425.84 15.00 0.00 207.67 198.77 18.34 0.00 82.67
December 131.67 0.70 0.60 02-DEC-10:00 358.56 14.21 0.00 170.17 170.51 17.65 0.00 41.50
                         
Annual Sum or Average 3515.67 0.63     776.22 18.12 148.17 3842.67 359.13 21.44 1442.33 3006.83
Minimum of Months 131.67 0.61 0.60   358.56 14.21 0.00 170.17 170.51 17.65 0.00 41.50
Maximum of Months 429.00 0.70 0.60   1127.15 20.84 61.50 447.00 514.38 24.16 316.17 423.17



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.69 0.60 01-JAN-10:30 388.18 14.37 0.00 208.00 180.64 17.77 0.00 79.67
February 217.00 0.65 0.60 01-FEB-11:00 506.14 15.89 0.00 238.83 234.18 19.18 0.00 147.67
March 215.50 0.64 0.60 01-MAR-11:39 648.69 16.42 0.00 316.50 271.27 19.53 6.33 230.67
April 359.67 0.62 0.60 01-APR-07:10 812.97 18.34 0.00 369.67 375.69 21.53 203.67 338.50
May 417.17 0.61 0.60 01-MAY-06:49 985.96 19.78 30.00 434.00 447.21 23.71 290.17 410.33
June 410.67 0.61 0.60 01-JUN-04:49 1127.15 20.70 49.83 438.83 514.38 24.16 308.83 411.50
July 429.00 0.61 0.60 01-JUL-04:49 1037.29 20.84 61.50 447.00 481.41 23.81 316.17 423.17
August 396.33 0.62 0.60 01-AUG-05:40 817.94 18.62 6.83 400.50 386.06 21.82 237.00 367.17
September 337.67 0.63 0.60 01-SEP-07:49 639.47 17.55 0.00 334.83 316.63 20.79 79.00 290.50
October 234.00 0.64 0.60 01-OCT-07:49 561.97 16.54 0.00 276.67 265.38 19.79 1.00 183.50
November 171.33 0.68 0.60 01-NOV-12:20 425.84 15.00 0.00 207.67 198.77 18.34 0.00 82.67
December 131.67 0.70 0.60 02-DEC-10:00 358.56 14.21 0.00 170.17 170.51 17.65 0.00 41.50
                         
Annual Sum or Average 3515.67 0.63     776.22 18.12 148.17 3842.67 359.13 21.44 1442.17 3006.83
Minimum of Months 131.67 0.61 0.60   358.56 14.21 0.00 170.17 170.51 17.65 0.00 41.50
Maximum of Months 429.00 0.70 0.60   1127.15 20.84 61.50 447.00 514.38 24.16 316.17 423.17



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.254487E+11 113390.12 24-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.189976E+11 122156.13 28-FEB-21:06 0.00 0.00 0.00 0.00 0.00
March 0.302262E+11 117908.73 14-MAR-18:06 0.00 0.00 0.00 0.00 0.00
April 0.261826E+11 116973.40 22-APR-00:15 0.00 0.00 0.00 0.00 0.00
May 0.338825E+11 115504.13 11-MAY-04:43 0.00 0.00 0.00 0.00 0.00
June 0.171323E+11 111260.50 07-JUN-05:15 0.00 0.00 0.00 0.00 0.00
July 0.949263E+10 103692.92 06-JUL-03:45 0.00 0.00 0.00 0.00 0.00
August 0.590821E+10 97632.07 20-AUG-03:55 0.00 0.00 0.00 0.00 0.00
September 0.157081E+11 113774.31 04-SEP-05:45 0.00 0.00 0.00 0.00 0.00
October 0.405538E+11 122661.00 05-OCT-22:25 0.00 0.00 0.00 0.00 0.00
November 0.437581E+11 116347.44 08-NOV-07:40 0.00 0.00 0.00 0.00 0.00
December 0.189112E+11 113028.42 24-DEC-07:25 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.286202E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.590821E+10 97632.07   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.437581E+11 122661.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.299521E+10 2702.65 18-JAN-07:14 0.00 0.00 0.00 0.00 0.00
February 0.238177E+10 2706.02 22-FEB-07:24 0.00 0.00 0.00 0.00 0.00
March 0.277077E+10 2705.17 23-MAR-06:32 0.00 0.00 0.00 0.00 0.00
April 0.101115E+10 2688.69 19-APR-06:32 0.00 0.00 0.00 0.00 0.00
May 0.979692E+09 2733.93 03-MAY-06:17 0.00 0.00 0.00 0.00 0.00
June 0.496099E+09 2647.84 08-JUN-00:25 0.00 0.00 0.00 0.00 0.00
July 0.322096E+09 2610.51 05-JUL-03:10 0.00 0.00 0.00 0.00 0.00
August 0.212428E+09 1867.16 24-AUG-06:20 0.00 0.00 0.00 0.00 0.00
September 0.369651E+09 2643.02 04-SEP-04:43 0.00 0.00 0.00 0.00 0.00
October 0.167269E+10 2737.64 15-OCT-08:06 0.00 0.00 0.00 0.00 0.00
November 0.255302E+10 2603.79 15-NOV-07:17 0.00 0.00 0.00 0.00 0.00
December 0.368825E+10 2650.63 21-DEC-16:16 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.194528E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.212428E+09 1867.16   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.368825E+10 2737.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 16190112.40 283.07 31-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 4627798.87 276.36 27-FEB-11:38 0.00 0.00 0.00 0.00 0.00
March 2964166.61 308.46 16-MAR-10:38 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 5605010.20 347.41 30-NOV-11:48 0.00 0.00 0.00 0.00 0.00
December 42707678.50 456.43 15-DEC-11:38 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 72094766.58     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 42707678.50 456.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.411856E+09 867.12 15-JAN-09:58 0.00 0.00 0.00 0.00 0.00
February 0.282948E+09 891.98 02-FEB-16:06 0.00 0.00 0.00 0.00 0.00
March 0.148796E+09 718.08 11-MAR-16:03 0.00 0.00 0.00 0.00 0.00
April 72952.88 127.86 01-APR-10:55 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.116106E+09 756.32 19-NOV-15:20 0.00 0.00 0.00 0.00 0.00
December 0.565898E+09 995.65 11-DEC-10:42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.152568E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.565898E+09 995.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.613079E+09 706.40 15-JAN-09:58 0.00 0.00 0.00 0.00 0.00
February 0.492465E+09 709.63 02-FEB-16:06 0.00 0.00 0.00 0.00 0.00
March 0.365714E+09 664.25 23-MAR-08:06 0.00 0.00 0.00 0.00 0.00
April 16355529.89 318.13 10-APR-16:44 0.00 0.00 0.00 0.00 0.00
May 39338.57 34.22 06-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 43534653.76 440.31 31-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.311237E+09 646.76 17-NOV-09:57 0.00 0.00 0.00 0.00 0.00
December 0.771766E+09 776.48 08-DEC-11:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.261419E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.771766E+09 776.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 76085951.70 1107.32 09-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 60457102.43 3367.94 05-FEB-15:24 0.00 0.00 0.00 0.00 0.00
March 46257460.79 1946.93 18-MAR-04:19 0.00 0.00 0.00 0.00 0.00
April 21081982.30 7783.65 28-APR-00:30 0.00 0.00 0.00 0.00 0.00
May 66902456.23 7860.25 11-MAY-04:47 0.00 0.00 0.00 0.00 0.00
June 61410501.61 7715.98 08-JUN-00:25 0.00 0.00 0.00 0.00 0.00
July 18309987.45 7607.23 05-JUL-03:10 0.00 0.00 0.00 0.00 0.00
August 23295143.42 7479.16 05-AUG-04:13 0.00 0.00 0.00 0.00 0.00
September 56942373.59 7718.70 28-SEP-04:03 0.00 0.00 0.00 0.00 0.00
October 71689974.74 7869.28 01-OCT-02:45 0.00 0.00 0.00 0.00 0.00
November 84897990.24 7658.09 19-NOV-15:20 0.00 0.00 0.00 0.00 0.00
December 97865094.12 7630.15 18-DEC-15:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.685196E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 18309987.45 1107.32   0.00 0.00 0.00 0.00 0.00
Maximum of Months 97865094.12 7869.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.196776E+10 8113.18 26-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.130401E+10 8075.11 27-FEB-07:45 0.00 0.00 0.00 0.00 0.00
March 0.180861E+10 8149.95 23-MAR-06:32 0.00 0.00 0.00 0.00 0.00
April 0.182957E+09 8135.12 12-APR-08:41 0.00 0.00 0.00 0.00 0.00
May 0.253433E+09 7416.81 02-MAY-06:47 0.00 0.00 0.00 0.00 0.00
June 66459141.22 4835.11 07-JUN-10:47 0.00 0.00 0.00 0.00 0.00
July 4172753.36 1410.31 08-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 17550183.29 2132.92 09-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 28987983.15 3147.04 08-SEP-10:33 0.00 0.00 0.00 0.00 0.00
October 0.909089E+09 8246.78 15-OCT-08:06 0.00 0.00 0.00 0.00 0.00
November 0.167887E+10 7512.22 01-NOV-10:54 0.00 0.00 0.00 0.00 0.00
December 0.305314E+10 7952.34 11-DEC-10:42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.112750E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4172753.36 1410.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.305314E+10 8246.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.247245E+09 6210.96 31-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 63299491.23 4333.37 16-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 59017754.43 5550.22 16-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 411685.80 1372.29 20-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.106766E+09 8380.64 30-NOV-11:48 0.00 0.00 0.00 0.00 0.00
December 0.613315E+09 7542.02 15-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.109006E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.613315E+09 8380.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.590622E+10 9278.31 18-JAN-07:14 0.00 0.00 0.00 0.00 0.00
February 0.417324E+10 9245.40 08-FEB-07:16 0.00 0.00 0.00 0.00 0.00
March 0.412450E+10 9286.99 23-MAR-06:32 0.00 0.00 0.00 0.00 0.00
April 0.107645E+09 6877.14 11-APR-06:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.148286E+10 9263.42 31-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.446513E+10 9222.59 03-NOV-08:59 0.00 0.00 0.00 0.00 0.00
December 0.834063E+10 9061.31 11-DEC-10:42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.286002E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.834063E+10 9286.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.343185E+10 5831.20 18-JAN-07:14 0.00 0.00 0.00 0.00 0.00
February 0.246849E+10 5810.48 08-FEB-07:16 0.00 0.00 0.00 0.00 0.00
March 0.202932E+10 5190.53 23-MAR-06:32 0.00 0.00 0.00 0.00 0.00
April 0.215311E+09 4660.91 11-APR-07:48 0.00 0.00 0.00 0.00 0.00
May 40577818.67 3249.82 15-MAY-05:07 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.773248E+09 5329.09 15-OCT-08:06 0.00 0.00 0.00 0.00 0.00
November 0.227454E+10 5312.05 18-NOV-09:56 0.00 0.00 0.00 0.00 0.00
December 0.434294E+10 4812.94 05-DEC-09:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155763E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.434294E+10 5831.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 273975.64 913.25 22-APR-00:35 0.00 0.00 0.00 0.00 0.00
May 2680517.26 2750.95 31-MAY-02:40 0.00 0.00 0.00 0.00 0.00
June 267803.20 892.68 08-JUN-00:25 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 114836.89 382.79 21-SEP-03:20 0.00 0.00 0.00 0.00 0.00
October 1768167.91 4218.84 01-OCT-02:45 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 5105300.90     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2680517.26 4218.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.823927E+09 6172.33 10-JAN-08:10 0.00 0.00 0.00 0.00 0.00
February 0.280336E+09 4130.10 17-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 36365041.25 1814.65 08-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 25637.66 0.90 30-APR-18:50 0.00 0.00 0.00 0.00 0.00
May 16999.53 0.91 21-MAY-20:05 0.00 0.00 0.00 0.00 0.00
June 27476.93 0.91 13-JUN-13:30 0.00 0.00 0.00 0.00 0.00
July 54424.44 0.91 12-JUL-16:15 0.00 0.00 0.00 0.00 0.00
August 63708.02 0.91 17-AUG-18:30 0.00 0.00 0.00 0.00 0.00
September 26630.81 0.82 19-SEP-15:40 0.00 0.00 0.00 0.00 0.00
October 2492.87 0.78 11-OCT-13:50 0.00 0.00 0.00 0.00 0.00
November 61966709.05 2099.55 29-NOV-02:00 0.00 0.00 0.00 0.00 0.00
December 0.413543E+09 3379.74 29-DEC-23:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161636E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2492.87 0.78   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.823927E+09 6172.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.357425E+10 5386.58 04-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.268919E+10 5387.13 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.260345E+10 5386.10 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.592869E+09 5266.45 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.396497E+09 5192.26 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 34131908.74 3781.14 18-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 45897504.41 4291.15 19-JUL-08:53 0.00 0.00 0.00 0.00 0.00
August 6613584.00 4136.62 27-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 98107092.90 3907.61 22-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 0.137348E+10 5350.42 27-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.286935E+10 5386.70 21-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.470829E+10 5387.09 02-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.189921E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6613584.00 3781.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.470829E+10 5387.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.443138E+10 5304.03 06-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.338559E+10 5304.44 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.294785E+10 5303.35 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.836066E+09 5208.39 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.478865E+09 5121.37 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 38099308.11 3317.24 20-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 48515108.98 3766.67 06-JUL-08:53 0.00 0.00 0.00 0.00 0.00
August 7978462.76 4018.45 21-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 0.171925E+09 3858.25 14-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 0.180726E+10 5276.24 27-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.348616E+10 5304.40 23-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.530319E+10 5304.41 02-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.229429E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7978462.76 3317.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.530319E+10 5304.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.714922E+09 7683.75 31-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.652792E+09 9449.65 02-FEB-04:50 0.00 0.00 0.00 0.00 0.00
March 0.516741E+09 6266.55 06-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.272578E+09 5046.61 30-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.619383E+10 13359.06 17-DEC-04:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.835086E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.619383E+10 13359.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.126984E+11 29874.72 11-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.963857E+10 29201.35 14-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.480512E+10 29160.25 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.862719E+09 28635.72 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.297109E+09 25442.62 26-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 69843126.65 28280.44 03-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 62887059.58 25946.09 28-JUL-08:15 0.00 0.00 0.00 0.00 0.00
August 69360006.79 23158.33 03-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.115743E+09 28274.59 29-SEP-15:03 0.00 0.00 0.00 0.00 0.00
October 0.200024E+10 28807.92 16-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.752374E+10 29563.09 29-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.151154E+11 29704.47 27-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.532591E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 62887059.58 23158.33   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.151154E+11 29874.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.360075E+10 5300.59 30-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.281859E+10 5300.95 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.263556E+10 5299.87 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.556348E+09 5163.39 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.399648E+09 3472.22 14-MAY-18:02 0.00 0.00 0.00 0.00 0.00
June 61777117.27 3526.40 05-JUN-18:03 0.00 0.00 0.00 0.00 0.00
July 32517397.34 4508.45 08-JUL-19:13 0.00 0.00 0.00 0.00 0.00
August 5337550.62 3315.48 26-AUG-21:14 0.00 0.00 0.00 0.00 0.00
September 76715566.07 4111.12 19-SEP-16:53 0.00 0.00 0.00 0.00 0.00
October 0.137995E+10 5268.53 27-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.288602E+10 5300.88 23-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.456842E+10 5300.91 02-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.190216E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5337550.62 3315.48   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.456842E+10 5300.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.441596E+10 5218.94 28-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.356927E+10 5218.90 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.298123E+10 5218.00 03-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.755686E+09 5104.22 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.486396E+09 3924.24 17-MAY-15:01 0.00 0.00 0.00 0.00 0.00
June 78310931.13 3502.25 17-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 38559676.80 2997.88 07-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 9362896.21 3018.18 11-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.154039E+09 3828.22 21-SEP-18:33 0.00 0.00 0.00 0.00 0.00
October 0.178699E+10 5194.78 27-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.348178E+10 5218.92 23-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.512364E+10 5218.85 02-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.228812E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9362896.21 2997.88   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.512364E+10 5218.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128182E+10 1615.87 28-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.965014E+09 1616.02 27-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.938458E+09 1615.75 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.261876E+09 1598.59 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.192187E+09 1573.97 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 29900507.86 951.86 03-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 28716187.64 1039.51 19-JUL-08:53 0.00 0.00 0.00 0.00 0.00
August 3895696.12 1028.70 01-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 66226219.08 1231.95 23-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 0.554562E+09 1615.99 16-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.103579E+10 1616.12 24-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.162515E+10 1616.01 05-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.698360E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3895696.12 951.86   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162515E+10 1616.12   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.154363E+10 1585.28 23-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.118301E+10 1585.30 27-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.104576E+10 1585.00 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.348489E+09 1576.23 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.224474E+09 1546.62 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 34782549.18 915.73 03-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 30624994.89 1013.85 19-JUL-08:53 0.00 0.00 0.00 0.00 0.00
August 7023758.09 1090.87 07-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 0.111900E+09 1532.18 20-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.706551E+09 1585.26 16-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.122892E+10 1585.40 24-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.180596E+10 1585.29 05-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.827113E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7023758.09 915.73   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.180596E+10 1585.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.324025E+10 7928.93 31-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.238683E+10 7858.53 15-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.263470E+10 7928.57 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.532056E+09 7688.57 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.479651E+09 6716.57 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 74926900.28 6218.48 23-JUN-08:53 0.00 0.00 0.00 0.00 0.00
July 55664404.45 7368.49 08-JUL-19:13 0.00 0.00 0.00 0.00 0.00
August 11245479.65 6085.35 01-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 68886100.94 5318.21 09-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.108552E+10 7841.19 27-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.247805E+10 7929.10 30-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.491131E+10 7929.76 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.179591E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 11245479.65 5318.21   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.491131E+10 7929.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.355681E+09 0.355681E+09 33913.20 24-JAN-21:07 33913.20 0.05
February 0.00 0.00 0.395107E+09 0.395107E+09 37151.92 01-FEB-22:50 37151.92 0.06
March 0.00 0.00 0.386217E+09 0.386217E+09 30931.20 13-MAR-18:55 30931.20 0.03
April 0.00 0.00 0.155165E+11 0.155012E+11 186501.22 30-APR-18:10 186501.22 0.06
May 0.00 0.00 0.155244E+11 0.155244E+11 160583.04 22-MAY-15:11 160583.04 0.18
June 0.00 0.00 0.491578E+11 0.466828E+11 336219.24 25-JUN-18:00 149426.87 0.39
July 0.00 0.00 0.844461E+11 0.832521E+11 231598.81 22-JUL-18:10 231598.81 0.54
August 0.00 0.00 0.983977E+11 0.971966E+11 211842.22 14-AUG-18:10 211842.22 0.59
September 0.00 0.00 0.508194E+11 0.504297E+11 160602.42 11-SEP-17:07 160602.42 0.42
October 0.00 0.00 0.291661E+10 0.291661E+10 71677.81 07-OCT-15:03 71677.81 0.10
November 0.00 0.00 0.399621E+09 0.399621E+09 37135.32 03-NOV-20:10 37135.32 0.04
December 0.00 0.00 0.474291E+09 0.474291E+09 34176.27 05-DEC-22:10 34176.27 0.04
                 
Annual Sum or Average 0.00 0.00 0.318789E+12 0.313514E+12       0.21
Minimum of Months 0.00 0.00 0.355681E+09 0.355681E+09 30931.20   30931.20 0.03
Maximum of Months 0.00 0.00 0.983977E+11 0.971966E+11 336219.24   231598.81 0.59



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 0.00
April 0.00 0.00 0.245873E+10 0.245686E+10 28330.58 30-APR-18:02 28330.58 0.03
May 0.00 0.00 0.246834E+10 0.246834E+10 28509.14 22-MAY-15:30 28509.14 0.08
June 0.00 0.00 0.833990E+10 0.762539E+10 45857.70 25-JUN-18:00 20546.06 0.27
July 0.00 0.00 0.147687E+11 0.139319E+11 34544.29 23-JUL-15:55 24937.23 0.47
August 0.00 0.00 0.178806E+11 0.169152E+11 34521.68 17-AUG-15:00 25048.15 0.56
September 0.00 0.00 0.924215E+10 0.879557E+10 32609.72 12-SEP-14:00 22710.87 0.32
October 0.00 0.00 0.434541E+09 0.434541E+09 15105.81 07-OCT-15:00 15105.81 0.01
November 0.00 0.00 6967938.21 6967938.21 4049.57 24-NOV-11:55 4049.57 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.555999E+11 0.526348E+11       0.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.178806E+11 0.169152E+11 45857.70   28509.14 0.56



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 26408978.73 14201991.59 12315.67 25-JAN-16:01 12315.67 0.01
February 0.00 0.00 0.184665E+09 0.164306E+09 16049.39 09-FEB-16:01 16049.39 0.01
March 0.00 0.00 91657487.83 84390585.15 15345.29 31-MAR-15:02 15345.29 0.01
April 0.00 0.00 0.229591E+10 0.170794E+10 16163.06 28-APR-19:01 16163.06 0.30
May 0.00 0.00 0.277359E+10 0.172290E+10 19016.30 22-MAY-21:31 16782.27 0.46
June 0.00 0.00 0.427526E+10 0.233702E+10 21107.76 26-JUN-21:01 15844.35 0.71
July 0.00 0.00 0.502786E+10 0.273904E+10 20431.11 23-JUL-21:31 16086.78 0.64
August 0.00 0.00 0.459125E+10 0.231345E+10 19870.03 17-AUG-21:11 15979.88 0.67
September 0.00 0.00 0.347043E+10 0.176062E+10 19734.71 12-SEP-20:11 16000.15 0.63
October 0.00 0.00 0.817397E+09 0.511390E+09 17524.58 05-OCT-17:12 17524.58 0.17
November 0.00 0.00 39633988.43 27202664.67 15697.97 03-NOV-15:01 15697.97 0.01
December 0.00 0.00 149701.78 51197.56 1419.47 21-DEC-16:04 503.70 0.00
                 
Annual Sum or Average 0.00 0.00 0.235942E+11 0.133825E+11       0.30
Minimum of Months 0.00 0.00 149701.78 51197.56 1419.47   503.70 0.00
Maximum of Months 0.00 0.00 0.502786E+10 0.273904E+10 21107.76   17524.58 0.71



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2362020.89 786638.50 4012.87 19-JAN-16:02 3163.33 0.00
February 0.00 0.00 45290993.16 37462222.91 11756.90 19-FEB-16:02 11756.90 0.01
March 0.00 0.00 46572380.76 43048191.47 13363.53 20-MAR-18:01 13363.53 0.00
April 0.00 0.00 0.137310E+10 0.101914E+10 15433.44 20-APR-18:01 15433.44 0.21
May 0.00 0.00 0.210960E+10 0.133821E+10 16844.78 22-MAY-21:31 14759.68 0.37
June 0.00 0.00 0.372837E+10 0.208541E+10 19078.65 26-JUN-21:01 14150.54 0.65
July 0.00 0.00 0.424232E+10 0.231883E+10 18305.79 23-JUL-21:31 14328.24 0.60
August 0.00 0.00 0.324644E+10 0.156479E+10 17401.62 11-AUG-19:11 13164.49 0.58
September 0.00 0.00 0.180021E+10 0.821820E+09 16869.33 12-SEP-20:11 13637.83 0.48
October 0.00 0.00 0.287420E+09 0.193234E+09 14407.09 07-OCT-15:02 14407.09 0.07
November 0.00 0.00 4286817.98 2231808.80 5511.52 10-NOV-16:01 5469.01 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.168860E+11 0.942497E+10       0.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.424232E+10 0.231883E+10 19078.65   15433.44 0.65



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.750351E+09 0.726168E+09 22769.74 21-JAN-11:30 22769.74 0.00
February 0.00 0.00 0.593111E+09 0.576327E+09 16382.93 04-FEB-14:21 16382.93 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 0.00
April 0.00 0.00 0.141784E+11 0.125471E+11 40376.91 30-APR-12:30 35662.36 0.10
May 0.00 0.00 0.965538E+10 0.643433E+10 31459.52 23-MAY-13:00 18193.52 0.20
June 0.00 0.00 0.128388E+11 0.462764E+10 31499.40 13-JUN-13:10 18838.15 0.52
July 0.00 0.00 0.180497E+11 0.726327E+10 37264.99 22-JUL-13:10 26527.77 0.59
August 0.00 0.00 0.242591E+11 0.120467E+11 41798.22 19-AUG-12:50 30258.45 0.61
September 0.00 0.00 0.301124E+11 0.189108E+11 53621.62 12-SEP-12:30 48873.56 0.58
October 0.00 0.00 0.975537E+10 0.788219E+10 46421.87 07-OCT-13:10 46421.87 0.12
November 0.00 0.00 0.331742E+09 0.322227E+09 18165.43 11-NOV-13:30 18165.43 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.120524E+12 0.713368E+11       0.23
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.301124E+11 0.189108E+11 53621.62   48873.56 0.61



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.588070E+09 0.162558E+09 62512.81 29-JAN-09:01 62512.81 0.08
February 0.00 0.00 0.422653E+09 0.152265E+09 23936.69 01-FEB-19:03 18343.28 0.07
March 0.00 0.00 0.262398E+10 0.148824E+10 68717.74 19-MAR-08:63 65977.24 0.15
April 0.00 0.00 0.109242E+11 0.764635E+10 71179.36 20-APR-18:01 71179.36 0.34
May 0.00 0.00 0.170431E+11 0.101667E+11 74254.81 31-MAY-19:51 71389.35 0.56
June 0.00 0.00 0.289546E+11 0.176610E+11 89822.54 26-JUN-21:01 68987.60 0.63
July 0.00 0.00 0.305490E+11 0.187629E+11 86701.07 17-JUL-21:51 64856.81 0.55
August 0.00 0.00 0.246186E+11 0.138957E+11 86603.78 16-AUG-21:51 64385.52 0.51
September 0.00 0.00 0.167695E+11 0.838507E+10 84414.67 10-SEP-20:31 63918.43 0.59
October 0.00 0.00 0.516731E+10 0.205882E+10 74620.41 09-OCT-08:63 63793.95 0.35
November 0.00 0.00 0.130085E+10 0.370841E+09 56848.79 25-NOV-09:01 56848.79 0.15
December 0.00 0.00 0.145009E+09 56217313.13 26643.54 24-DEC-09:02 22955.73 0.03
                 
Annual Sum or Average 0.00 0.00 0.139107E+12 0.808067E+11       0.33
Minimum of Months 0.00 0.00 0.145009E+09 56217313.13 23936.69   18343.28 0.03
Maximum of Months 0.00 0.00 0.305490E+11 0.187629E+11 89822.54   71389.35 0.63



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 70890055.42 31917004.19 4332.04 21-JAN-16:02 3720.52 0.02
February 0.00 0.00 0.124648E+09 80555129.03 13552.59 04-FEB-16:01 13552.59 0.03
March 0.00 0.00 63412525.43 41216960.08 7387.05 20-MAR-15:01 7387.05 0.02
April 0.00 0.00 0.269853E+10 0.200315E+10 15808.61 28-APR-08:51 15808.61 0.34
May 0.00 0.00 0.287330E+10 0.171156E+10 16108.48 23-MAY-08:51 16108.48 0.52
June 0.00 0.00 0.405241E+10 0.219423E+10 17977.71 26-JUN-21:01 13562.96 0.71
July 0.00 0.00 0.493723E+10 0.273340E+10 18942.28 23-JUL-08:32 17394.26 0.69
August 0.00 0.00 0.513209E+10 0.282456E+10 17471.72 17-AUG-08:51 15681.99 0.70
September 0.00 0.00 0.413318E+10 0.227770E+10 17147.04 10-SEP-20:31 12917.75 0.70
October 0.00 0.00 0.921703E+09 0.572144E+09 14613.89 07-OCT-15:02 14613.89 0.19
November 0.00 0.00 68040801.15 35892551.41 13257.45 03-NOV-15:01 13257.45 0.02
December 0.00 0.00 16100949.73 7653480.61 1049.52 11-DEC-09:05 315.74 0.01
                 
Annual Sum or Average 0.00 0.00 0.250915E+11 0.145140E+11       0.33
Minimum of Months 0.00 0.00 16100949.73 7653480.61 1049.52   315.74 0.01
Maximum of Months 0.00 0.00 0.513209E+10 0.282456E+10 18942.28   17394.26 0.71



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2224794.60 549521.34 2024.37 21-JAN-09:04 1050.54 0.00
February 0.00 0.00 17911143.07 10227948.55 6042.83 20-FEB-09:02 5321.94 0.01
March 0.00 0.00 18568963.62 9602426.60 2233.18 30-MAR-18:03 2233.18 0.01
April 0.00 0.00 0.163533E+10 0.118757E+10 14187.34 28-APR-08:51 14187.34 0.27
May 0.00 0.00 0.214939E+10 0.131714E+10 14608.38 23-MAY-08:51 14608.38 0.43
June 0.00 0.00 0.347367E+10 0.193406E+10 16594.65 13-JUN-08:32 15553.39 0.64
July 0.00 0.00 0.410144E+10 0.229598E+10 17117.68 23-JUL-08:32 15723.83 0.67
August 0.00 0.00 0.370409E+10 0.198278E+10 15857.18 17-AUG-08:51 14139.21 0.69
September 0.00 0.00 0.233523E+10 0.126579E+10 15429.88 11-SEP-08:51 14349.28 0.54
October 0.00 0.00 0.327391E+09 0.191093E+09 12551.19 07-OCT-15:02 12551.19 0.09
November 0.00 0.00 6127350.92 1676180.03 2431.41 25-NOV-09:02 1321.89 0.01
December 0.00 0.00 429067.70 111029.18 888.09 02-DEC-09:06 239.90 0.00
                 
Annual Sum or Average 0.00 0.00 0.177718E+11 0.101966E+11       0.28
Minimum of Months 0.00 0.00 429067.70 111029.18 888.09   239.90 0.00
Maximum of Months 0.00 0.00 0.410144E+10 0.229598E+10 17117.68   15723.83 0.69



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6261740.78 3582061.81 3239.89 19-JAN-16:02 3239.89 0.01
February 0.00 0.00 50774368.29 46146092.46 4224.07 09-FEB-16:01 4224.07 0.01
March 0.00 0.00 22050069.30 20450444.41 4080.17 20-MAR-18:01 4080.17 0.01
April 0.00 0.00 0.628906E+09 0.492841E+09 4663.06 28-APR-18:42 4663.06 0.26
May 0.00 0.00 0.733768E+09 0.483181E+09 4987.14 22-MAY-21:31 4521.61 0.40
June 0.00 0.00 0.111525E+10 0.647873E+09 5563.66 26-JUN-21:01 4199.06 0.64
July 0.00 0.00 0.134200E+10 0.764809E+09 5728.01 24-JUL-19:42 4884.31 0.62
August 0.00 0.00 0.117255E+10 0.617653E+09 5290.63 17-AUG-21:11 4302.80 0.66
September 0.00 0.00 0.831490E+09 0.446468E+09 5276.19 12-SEP-20:11 4340.48 0.56
October 0.00 0.00 0.190017E+09 0.128463E+09 4719.33 05-OCT-17:12 4719.33 0.13
November 0.00 0.00 9427434.73 6803183.89 4113.87 03-NOV-15:01 4113.87 0.01
December 0.00 0.00 24337.66 9132.24 405.63 21-DEC-16:04 152.20 0.00
                 
Annual Sum or Average 0.00 0.00 0.610252E+10 0.365828E+10       0.28
Minimum of Months 0.00 0.00 24337.66 9132.24 405.63   152.20 0.00
Maximum of Months 0.00 0.00 0.134200E+10 0.764809E+09 5728.01   4884.31 0.66



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 359699.43 142149.24 617.31 15-JAN-16:03 345.36 0.00
February 0.00 0.00 8468982.87 6617633.92 2869.03 27-FEB-16:02 2869.03 0.00
March 0.00 0.00 9951512.95 9215668.28 3525.20 20-MAR-18:01 3525.20 0.00
April 0.00 0.00 0.377607E+09 0.295467E+09 4075.92 28-APR-18:42 4075.92 0.17
May 0.00 0.00 0.549812E+09 0.369914E+09 4477.61 22-MAY-21:31 3987.15 0.32
June 0.00 0.00 0.959125E+09 0.568889E+09 4961.23 26-JUN-21:01 3727.72 0.58
July 0.00 0.00 0.112016E+10 0.637413E+09 5066.17 24-JUL-19:42 4281.67 0.59
August 0.00 0.00 0.796661E+09 0.399945E+09 4724.62 17-AUG-21:11 3794.78 0.57
September 0.00 0.00 0.392939E+09 0.193881E+09 4616.22 12-SEP-20:11 3694.93 0.37
October 0.00 0.00 61136479.49 44487414.89 3763.43 07-OCT-15:02 3763.43 0.04
November 0.00 0.00 488727.77 229001.21 843.69 03-NOV-15:02 843.69 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.427670E+10 0.252620E+10       0.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.112016E+10 0.637413E+09 5066.17   4281.67 0.59



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.109079E+10 0.715062E+09 23445.69 11-JAN-16:01 23445.69 0.13
February 0.00 0.00 0.136947E+10 0.107634E+10 23480.12 10-FEB-16:01 23480.12 0.12
March 0.00 0.00 0.368220E+09 0.274399E+09 23478.01 20-MAR-15:01 23478.01 0.05
April 0.00 0.00 0.501379E+10 0.362745E+10 23479.35 06-APR-15:02 23479.35 0.45
May 0.00 0.00 0.404306E+10 0.217054E+10 25016.94 11-MAY-19:31 25016.94 0.54
June 0.00 0.00 0.532129E+10 0.257473E+10 28996.70 26-JUN-21:01 22193.64 0.70
July 0.00 0.00 0.670279E+10 0.340326E+10 28123.94 23-JUL-21:31 22687.84 0.66
August 0.00 0.00 0.792095E+10 0.441311E+10 28244.86 16-AUG-21:51 21412.83 0.69
September 0.00 0.00 0.833908E+10 0.515919E+10 30137.94 12-SEP-20:11 23814.93 0.72
October 0.00 0.00 0.319292E+10 0.199882E+10 25982.92 07-OCT-17:32 25982.92 0.37
November 0.00 0.00 0.867568E+09 0.558151E+09 23472.36 03-NOV-15:01 23472.36 0.11
December 0.00 0.00 0.322230E+09 0.264177E+09 22729.60 18-DEC-16:02 22729.60 0.02
                 
Annual Sum or Average 0.00 0.00 0.445522E+11 0.262352E+11       0.38
Minimum of Months 0.00 0.00 0.322230E+09 0.264177E+09 22729.60   21412.83 0.02
Maximum of Months 0.00 0.00 0.833908E+10 0.515919E+10 30137.94   25982.92 0.72



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 28611.56 156232.41 14-JAN-19:02
February 0.00 0.00 01-FEB-00:03 23632.17 145694.07 05-FEB-19:02
March 0.00 0.00 01-MAR-00:03 23166.77 145410.65 07-MAR-19:01
April 0.01 132.98 29-APR-01:07 12401.58 131840.31 11-APR-08:02
May 0.00 0.00 01-MAY-00:10 14131.72 116784.39 01-MAY-23:18
June 0.00 0.00 01-JUN-00:05 6947.14 104792.78 01-JUN-03:05
July 0.00 0.00 01-JUL-00:10 3766.13 99234.10 06-JUL-03:57
August 0.00 0.00 01-AUG-00:05 2329.23 95241.15 23-AUG-04:00
September 0.00 0.00 01-SEP-00:05 6516.45 109631.68 04-SEP-05:45
October 0.00 0.00 01-OCT-00:10 20767.49 142230.45 27-OCT-15:02
November 0.00 0.00 01-NOV-00:10 30817.67 145412.88 25-NOV-16:04
December 0.00 0.00 01-DEC-00:03 33332.77 162641.58 16-DEC-16:25
             
Annual Sum or Average 0.00     17182.09    
Minimum of Months 0.00 0.00   2329.23 95241.15  
Maximum of Months 0.01 132.98   33332.77 162641.58  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2110.96 35179.32 13-JAN-19:06 0.00 0.00 01-JAN-00:10
February 2565.88 42112.60 19-FEB-16:02 0.00 0.00 01-FEB-00:03
March 2469.89 54589.35 20-MAR-18:01 0.00 0.00 01-MAR-00:03
April 24102.14 361839.41 30-APR-18:03 0.00 0.00 01-APR-00:10
May 24578.13 353813.09 22-MAY-15:03 0.00 0.00 01-MAY-00:10
June 49646.58 447838.31 12-JUN-18:03 0.00 0.00 01-JUN-00:05
July 68013.58 434996.43 22-JUL-18:03 0.00 0.00 01-JUL-00:10
August 74186.34 401518.55 14-AUG-18:03 0.00 0.00 01-AUG-00:05
September 52014.64 363898.12 13-SEP-15:03 0.00 0.00 01-SEP-00:05
October 10553.09 212015.47 07-OCT-15:02 0.00 0.00 01-OCT-00:10
November 2193.73 50076.52 11-NOV-09:02 0.00 0.00 01-NOV-00:10
December 1291.82 40977.87 15-DEC-19:06 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 26273.63     0.00    
Minimum of Months 1291.82 35179.32   0.00 0.00  
Maximum of Months 74186.34 447838.31   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 28084.32 67232.50 18-JAN-07:02
February 0.00 0.00 01-FEB-00:03 28263.92 69497.15 27-FEB-07:41
March 0.00 0.00 01-MAR-00:03 28092.67 67307.41 26-MAR-07:41
April 0.00 0.00 01-APR-00:10 27559.59 68873.79 17-APR-06:51
May 0.00 0.00 01-MAY-00:10 26859.86 64629.76 09-MAY-06:44
June 0.00 0.00 01-JUN-00:05 26178.46 60506.89 08-JUN-06:59
July 0.00 0.00 01-JUL-00:10 25656.07 57243.96 04-JUL-07:15
August 0.00 0.00 01-AUG-00:05 25497.82 57801.62 24-AUG-06:25
September 0.00 0.00 01-SEP-00:05 25646.90 63690.66 26-SEP-06:51
October 0.00 0.00 01-OCT-00:10 26115.28 63625.32 10-OCT-06:41
November 0.00 0.00 01-NOV-00:10 26836.31 66957.11 14-NOV-07:51
December 0.00 0.00 01-DEC-00:03 27574.58 66802.98 20-DEC-07:11
             
Annual Sum or Average 0.00     26855.69    
Minimum of Months 0.00 0.00   25497.82 57243.96  
Maximum of Months 0.00 0.00   28263.92 69497.15  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.89 2194.93 01-JAN-00:10 0.89
February 0.530997E+10 0.88 2194.93 01-FEB-00:03 0.88
March 0.587890E+10 0.89 2194.93 01-MAR-00:03 0.88
April 0.568926E+10 0.89 2194.93 01-APR-00:10 0.89
May 0.587890E+10 0.88 2194.93 01-MAY-00:10 0.88
June 0.568926E+10 0.88 2194.93 01-JUN-00:05 0.88
July 0.587890E+10 0.88 2194.93 01-JUL-00:10 0.88
August 0.587890E+10 0.88 2194.93 01-AUG-00:05 0.88
September 0.568926E+10 0.88 2194.93 01-SEP-00:05 0.88
October 0.587890E+10 0.88 2194.93 01-OCT-00:10 0.88
November 0.568926E+10 0.88 2194.93 01-NOV-00:10 0.89
December 0.587890E+10 0.89 2194.93 01-DEC-00:03 0.88
           
Annual Sum or Average 0.692193E+11 0.88      
Minimum of Months 0.530997E+10 0.88 2194.93   0.88
Maximum of Months 0.587890E+10 0.89 2194.93   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.331216E+11 0.78 26504.04 13-JAN-21:45 1.22
February 0.300284E+11 0.78 26504.04 01-FEB-21:35 1.22
March 0.339839E+11 0.79 21768.87 01-MAR-19:04 1.08
April 0.339705E+11 0.81 36021.46 13-APR-21:35 1.48
May 0.356740E+11 0.81 38081.70 19-MAY-21:20 1.53
June 0.349261E+11 0.82 31794.98 02-JUN-00:10 1.36
July 0.363842E+11 0.82 31330.73 02-JUL-02:15 1.35
August 0.362009E+11 0.82 32651.73 03-AUG-04:10 1.38
September 0.351015E+11 0.82 37521.98 24-SEP-04:43 1.51
October 0.353042E+11 0.81 42865.02 05-OCT-22:05 1.65
November 0.333499E+11 0.80 37521.98 16-NOV-22:45 1.52
December 0.330231E+11 0.78 26504.04 01-DEC-20:06 1.22
           
Annual Sum or Average 0.411068E+12 0.80      
Minimum of Months 0.300284E+11 0.78 21768.87   1.08
Maximum of Months 0.363842E+11 0.82 42865.02   1.65



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:10 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:10 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:10 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:02 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:05 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:10 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.345636E+09 0.43 873.08 01-JAN-09:02 0.58
February 0.277552E+09 0.42 873.08 01-FEB-09:01 0.58
March 0.276202E+09 0.41 873.08 01-MAR-09:02 0.58
April 0.220170E+09 0.45 873.08 01-APR-08:62 0.58
May 0.218088E+09 0.44 873.08 01-MAY-15:02 0.58
June 0.235920E+09 0.44 873.08 01-JUN-15:01 0.58
July 0.262746E+09 0.40 873.08 01-JUL-15:01 0.58
August 0.235431E+09 0.39 873.08 01-AUG-08:51 0.58
September 0.202787E+09 0.43 873.08 01-SEP-15:02 0.58
October 0.214215E+09 0.43 873.08 01-OCT-15:02 0.58
November 0.294174E+09 0.42 873.08 01-NOV-08:62 0.58
December 0.431996E+09 0.46 873.08 01-DEC-09:02 0.58
           
Annual Sum or Average 0.321491E+10 0.43      
Minimum of Months 0.202787E+09 0.39 873.08   0.58
Maximum of Months 0.431996E+09 0.46 873.08   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.377782E+09 0.46 783.32 01-JAN-09:02 0.58
February 0.296269E+09 0.42 783.32 01-FEB-09:01 0.58
March 0.276404E+09 0.41 783.32 01-MAR-09:02 0.58
April 0.183200E+09 0.42 783.32 01-APR-08:62 0.58
May 0.184623E+09 0.41 783.32 01-MAY-15:02 0.58
June 0.207285E+09 0.41 783.32 01-JUN-15:01 0.58
July 0.223975E+09 0.38 783.32 01-JUL-15:01 0.58
August 0.171136E+09 0.34 783.32 01-AUG-08:51 0.58
September 0.128160E+09 0.38 783.32 01-SEP-15:02 0.58
October 0.206623E+09 0.41 783.32 01-OCT-15:02 0.58
November 0.311321E+09 0.43 783.32 01-NOV-08:62 0.58
December 0.438640E+09 0.49 783.32 01-DEC-09:02 0.58
           
Annual Sum or Average 0.300542E+10 0.41      
Minimum of Months 0.128160E+09 0.34 783.32   0.58
Maximum of Months 0.438640E+09 0.49 783.32   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.167642E+09 0.07 1117.42 21-JAN-11:30 0.58
February 0.139717E+09 0.06 1071.59 02-FEB-04:50 0.58
March 89732062.25 0.04 827.31 06-MAR-05:00 0.58
April 0.784537E+09 0.23 1837.79 30-APR-12:30 0.58
May 0.581757E+09 0.21 1306.68 23-MAY-13:10 0.58
June 0.749113E+09 0.31 1325.33 13-JUN-13:20 0.58
July 0.967703E+09 0.35 1549.32 22-JUL-13:30 0.58
August 0.120841E+10 0.36 1662.63 20-AUG-13:00 0.58
September 0.147226E+10 0.37 3245.90 25-SEP-13:30 0.58
October 0.510769E+09 0.12 2009.18 03-OCT-13:20 0.58
November 70886153.44 0.03 949.82 11-NOV-13:30 0.58
December 0.843181E+09 0.26 1340.26 17-DEC-04:40 0.58
           
Annual Sum or Average 0.758571E+10 0.20      
Minimum of Months 70886153.44 0.03 827.31   0.58
Maximum of Months 0.147226E+10 0.37 3245.90   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.122611E+10 0.41 4014.01 01-JAN-16:01 0.58
February 0.961334E+09 0.41 4014.01 01-FEB-09:01 0.58
March 0.738310E+09 0.41 4014.01 01-MAR-09:02 0.58
April 0.802640E+09 0.40 4014.01 01-APR-18:02 0.58
May 0.998096E+09 0.39 4014.01 01-MAY-08:62 0.58
June 0.140967E+10 0.37 4014.01 01-JUN-08:62 0.58
July 0.146240E+10 0.32 4014.01 01-JUL-08:62 0.58
August 0.116811E+10 0.30 4014.01 01-AUG-08:51 0.58
September 0.880752E+09 0.35 4014.01 01-SEP-08:53 0.58
October 0.607850E+09 0.41 4014.01 01-OCT-08:61 0.58
November 0.868865E+09 0.41 4014.01 01-NOV-15:01 0.58
December 0.138177E+10 0.41 4014.01 01-DEC-09:02 0.58
           
Annual Sum or Average 0.125059E+11 0.38      
Minimum of Months 0.607850E+09 0.30 4014.01   0.58
Maximum of Months 0.146240E+10 0.41 4014.01   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.324710E+09 0.43 794.61 01-JAN-16:01 0.58
February 0.263320E+09 0.42 794.61 01-FEB-09:01 0.58
March 0.257796E+09 0.41 794.61 01-MAR-09:02 0.58
April 0.229693E+09 0.48 794.61 01-APR-15:01 0.58
May 0.219132E+09 0.47 794.61 01-MAY-15:02 0.58
June 0.225679E+09 0.46 794.61 01-JUN-08:62 0.58
July 0.257718E+09 0.43 794.61 01-JUL-08:62 0.58
August 0.263417E+09 0.41 794.61 01-AUG-08:51 0.58
September 0.235985E+09 0.47 794.61 01-SEP-15:02 0.58
October 0.206476E+09 0.43 794.61 01-OCT-08:61 0.58
November 0.275489E+09 0.42 794.61 01-NOV-08:62 0.58
December 0.391396E+09 0.46 794.61 01-DEC-09:02 0.58
           
Annual Sum or Average 0.315081E+10 0.44      
Minimum of Months 0.206476E+09 0.41 794.61   0.58
Maximum of Months 0.391396E+09 0.48 794.61   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.363438E+09 0.46 717.76 01-JAN-09:02 0.58
February 0.287468E+09 0.43 717.76 01-FEB-09:01 0.58
March 0.259618E+09 0.42 717.76 01-MAR-09:02 0.58
April 0.180823E+09 0.43 717.76 03-APR-08:62 0.58
May 0.182039E+09 0.43 717.76 01-MAY-15:02 0.58
June 0.196845E+09 0.43 717.76 01-JUN-08:62 0.58
July 0.218821E+09 0.42 717.76 01-JUL-08:62 0.58
August 0.199161E+09 0.40 717.76 01-AUG-08:51 0.58
September 0.152655E+09 0.41 717.76 01-SEP-15:02 0.58
October 0.193037E+09 0.40 717.76 01-OCT-08:61 0.58
November 0.291577E+09 0.43 717.76 01-NOV-08:62 0.58
December 0.403190E+09 0.49 717.76 01-DEC-09:02 0.58
           
Annual Sum or Average 0.292867E+10 0.43      
Minimum of Months 0.152655E+09 0.40 717.76   0.58
Maximum of Months 0.403190E+09 0.49 717.76   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.106424E+09 0.46 229.87 01-JAN-09:02 0.58
February 84850196.45 0.44 229.87 01-FEB-09:01 0.58
March 84121708.24 0.42 229.87 01-MAR-09:02 0.58
April 66377506.16 0.46 229.87 01-APR-08:62 0.58
May 64440044.64 0.45 229.87 01-MAY-15:02 0.58
June 64173084.38 0.45 229.87 01-JUN-15:01 0.58
July 71983253.74 0.41 229.87 01-JUL-15:01 0.58
August 60670340.58 0.39 229.87 01-AUG-08:51 0.58
September 52920822.49 0.43 229.87 01-SEP-15:02 0.58
October 66616276.63 0.43 229.87 01-OCT-15:02 0.58
November 90588732.98 0.44 229.87 01-NOV-08:62 0.58
December 0.130335E+09 0.50 229.87 01-DEC-09:02 0.58
           
Annual Sum or Average 0.943501E+09 0.44      
Minimum of Months 52920822.49 0.39 229.87   0.58
Maximum of Months 0.130335E+09 0.50 229.87   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.119698E+09 0.49 204.69 01-JAN-09:02 0.58
February 89220166.71 0.46 204.69 01-FEB-09:01 0.58
March 83309320.76 0.43 204.69 01-MAR-09:02 0.58
April 56457831.63 0.42 204.69 01-APR-08:62 0.58
May 55126747.36 0.42 204.69 01-MAY-15:02 0.58
June 56577344.71 0.42 204.69 01-JUN-15:01 0.58
July 61279464.28 0.39 204.69 01-JUL-15:01 0.58
August 43214014.23 0.35 204.69 01-AUG-08:51 0.58
September 35162427.97 0.38 204.69 01-SEP-15:02 0.58
October 65099571.51 0.41 204.69 01-OCT-08:61 0.58
November 95073224.06 0.47 204.69 01-NOV-08:62 0.58
December 0.133787E+09 0.54 204.69 01-DEC-09:02 0.58
           
Annual Sum or Average 0.894005E+09 0.43      
Minimum of Months 35162427.97 0.35 204.69   0.58
Maximum of Months 0.133787E+09 0.54 204.69   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.401739E+09 0.45 1271.78 01-JAN-16:01 0.58
February 0.336566E+09 0.45 1271.78 01-FEB-09:01 0.58
March 0.319231E+09 0.42 1271.78 01-MAR-09:02 0.58
April 0.364019E+09 0.48 1271.78 01-APR-15:01 0.58
May 0.301017E+09 0.46 1271.78 01-MAY-15:02 0.58
June 0.292685E+09 0.44 1271.78 01-JUN-15:01 0.58
July 0.342248E+09 0.41 1271.78 01-JUL-15:01 0.58
August 0.383961E+09 0.40 1271.78 01-AUG-08:51 0.58
September 0.429560E+09 0.46 1271.78 01-SEP-15:02 0.58
October 0.320556E+09 0.46 1271.78 01-OCT-08:61 0.58
November 0.331981E+09 0.44 1271.78 01-NOV-08:62 0.58
December 0.496068E+09 0.45 1271.78 01-DEC-09:02 0.58
           
Annual Sum or Average 0.431963E+10 0.44      
Minimum of Months 0.292685E+09 0.40 1271.78   0.58
Maximum of Months 0.496068E+09 0.48 1271.78   0.58



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.751266E+09 0.676139E+09 739.43 26-JAN-09:13 665.48 665.48 38.52 1.44
February 0.590673E+09 0.531605E+09 736.41 28-FEB-09:02 662.77 662.77 40.63 1.42
March 0.626675E+09 0.564007E+09 715.74 02-MAR-19:01 644.17 644.17 38.28 1.32
April 0.304930E+09 0.274437E+09 678.48 11-APR-06:25 610.63 610.63 50.32 1.16
May 0.327898E+09 0.295108E+09 657.39 18-MAY-01:55 591.65 591.65 51.41 1.08
June 0.143542E+09 0.129188E+09 647.92 08-JUN-01:55 583.13 583.13 38.08 1.06
July 81704723.20 73534250.88 598.72 05-JUL-03:38 538.85 538.85 35.50 0.92
August 49953243.57 44957919.21 577.66 23-AUG-04:00 519.90 519.90 33.60 0.86
September 0.148099E+09 0.133289E+09 656.97 08-SEP-04:10 591.27 591.27 38.16 1.09
October 0.518480E+09 0.466632E+09 722.31 24-OCT-08:62 650.08 650.08 37.34 1.35
November 0.745838E+09 0.671254E+09 732.97 12-NOV-16:35 659.67 659.67 47.79 1.40
December 0.855029E+09 0.769526E+09 758.65 16-DEC-16:25 682.79 682.79 34.96 1.55
                 
Annual Sum or Average 0.514409E+10 0.462968E+10            
Minimum of Months 49953243.57 44957919.21 577.66   519.90 519.90 33.60 0.86
Maximum of Months 0.855029E+09 0.769526E+09 758.65   682.79 682.79 51.41 1.55



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 1747051.86 1572346.67 33.50 21-JAN-16:02 30.15 30.15 6.72 2.80
February 1925243.45 1732719.11 43.86 19-FEB-16:02 39.47 39.47 6.72 3.25
March 2372534.19 2135280.77 72.89 20-MAR-18:01 65.61 65.61 6.72 4.23
April 71696670.22 64527003.20 822.09 29-APR-15:03 739.88 739.88 6.72 13.04
May 63040939.00 56736845.10 714.80 22-MAY-15:02 643.32 643.32 6.72 12.29
June 0.138915E+09 0.125024E+09 1150.04 12-JUN-18:02 1035.04 1035.04 6.72 15.03
July 0.194389E+09 0.174950E+09 1295.43 22-JUL-18:03 1165.88 1165.88 6.72 15.80
August 0.202436E+09 0.182192E+09 1736.76 14-AUG-18:03 1563.08 1563.08 6.72 17.82
September 0.160330E+09 0.144297E+09 1141.32 25-SEP-15:03 1027.18 1027.18 6.72 14.98
October 24379646.70 21941682.03 318.17 07-OCT-15:02 286.35 286.35 6.72 8.59
November 1768870.64 1591983.58 46.65 11-NOV-09:02 41.99 41.99 6.72 3.35
December 335434.31 301890.88 20.37 24-DEC-09:02 18.33 18.33 6.72 2.12
                 
Annual Sum or Average 0.863336E+09 0.777002E+09            
Minimum of Months 335434.31 301890.88 20.37   18.33 18.33 6.72 2.12
Maximum of Months 0.202436E+09 0.182192E+09 1736.76   1563.08 1563.08 6.72 17.82



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.306028E+10 0.275425E+10 2854.39 01-JAN-02:07 2568.95 2568.95 6.72 25.25
February 0.332923E+10 0.299631E+10 2854.39 01-FEB-01:20 2568.95 2568.95 6.72 25.25
March 0.331686E+10 0.298518E+10 2854.39 01-MAR-00:03 2568.95 2568.95 6.73 25.25
April 0.591614E+10 0.532452E+10 2854.39 01-APR-01:07 2568.95 2568.95 6.72 25.25
May 0.651523E+10 0.586371E+10 2854.39 01-MAY-00:10 2568.95 2568.95 7.03 25.25
June 0.710112E+10 0.639100E+10 2854.39 01-JUN-00:05 2568.95 2568.95 6.87 25.25
July 0.753047E+10 0.677743E+10 2854.39 01-JUL-00:10 2568.95 2568.95 6.80 25.25
August 0.763420E+10 0.687078E+10 2854.39 01-AUG-00:05 2568.95 2568.95 6.92 25.25
September 0.719629E+10 0.647666E+10 2854.39 01-SEP-00:05 2568.95 2568.95 6.89 25.25
October 0.464181E+10 0.417763E+10 2854.39 01-OCT-00:10 2568.95 2568.95 6.75 25.25
November 0.295115E+10 0.265604E+10 2854.39 01-NOV-00:15 2568.95 2568.95 6.72 25.25
December 0.278857E+10 0.250971E+10 2854.39 01-DEC-00:03 2568.95 2568.95 6.73 25.25
                 
Annual Sum or Average 0.619813E+11 0.557832E+11            
Minimum of Months 0.278857E+10 0.250971E+10 2854.39   2568.95 2568.95 6.72 25.25
Maximum of Months 0.763420E+10 0.687078E+10 2854.39   2568.95 2568.95 7.03 25.25



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 48.31 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 48.65 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 48.21 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 51.62 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 30.59 0.06
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 51.97 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 52.21 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 51.52 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 51.42 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 51.58 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 51.63 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 48.99 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 30.59 0.06
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 52.21 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 40.55 60.00 28611.56 156232.41 14-JAN-19:02
February 0.00 0.00 01-FEB-00:03 47.74 60.00 23632.17 145694.07 05-FEB-19:02
March 0.00 0.00 01-MAR-00:03 43.89 60.00 23166.77 145410.65 07-MAR-19:01
April 0.01 132.98 29-APR-01:07 60.04 60.04 12401.58 131840.31 11-APR-08:02
May 0.00 0.00 01-MAY-00:10 35.38 35.38 14131.72 116784.39 01-MAY-23:18
June 0.00 0.00 01-JUN-00:05 55.73 60.00 6947.14 104792.78 01-JUN-03:05
July 0.00 0.00 01-JUL-00:10 34.40 60.00 3766.13 99234.10 06-JUL-03:57
August 0.00 0.00 01-AUG-00:05 26.17 60.00 2329.23 95241.15 23-AUG-04:00
September 0.00 0.00 01-SEP-00:05 36.50 60.00 6516.45 109631.68 04-SEP-05:45
October 0.00 0.00 01-OCT-00:10 59.28 60.00 20767.49 142230.45 27-OCT-15:02
November 0.00 0.00 01-NOV-00:10 40.60 60.00 30817.67 145412.88 25-NOV-16:04
December 0.00 0.00 01-DEC-00:03 42.36 60.00 33332.77 162641.58 16-DEC-16:25
                 
Annual Sum or Average 0.00         17182.09    
Minimum of Months 0.00 0.00   26.17 35.38 2329.23 95241.15  
Maximum of Months 0.01 132.98   60.04 60.04 33332.77 162641.58  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2110.96 35179.32 13-JAN-19:06 7.03 6.70 0.00 0.00 01-JAN-00:10
February 2565.88 42112.60 19-FEB-16:02 7.10 6.70 0.00 0.00 01-FEB-00:03
March 2469.89 54589.35 20-MAR-18:01 7.22 6.70 0.00 0.00 01-MAR-00:03
April 24102.14 361839.41 30-APR-18:03 10.12 6.70 0.00 0.00 01-APR-00:10
May 24578.13 353813.09 22-MAY-15:03 10.04 6.70 0.00 0.00 01-MAY-00:10
June 49646.58 447838.31 12-JUN-18:03 10.93 6.70 0.00 0.00 01-JUN-00:05
July 68013.58 434996.43 22-JUL-18:03 10.81 6.70 0.00 0.00 01-JUL-00:10
August 74186.34 401518.55 14-AUG-18:03 10.49 6.70 0.00 0.00 01-AUG-00:05
September 52014.64 363898.12 13-SEP-15:03 10.14 6.70 0.00 0.00 01-SEP-00:05
October 10553.09 212015.47 07-OCT-15:02 8.70 6.70 0.00 0.00 01-OCT-00:10
November 2193.73 50076.52 11-NOV-09:02 7.17 6.70 0.00 0.00 01-NOV-00:10
December 1291.82 40977.87 15-DEC-19:06 7.09 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 26273.63         0.00    
Minimum of Months 1291.82 35179.32   7.03 6.70 0.00 0.00  
Maximum of Months 74186.34 447838.31   10.93 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.31 59.41 28084.32 67232.50 18-JAN-07:02
February 0.00 0.00 01-FEB-00:03 48.65 59.45 28263.92 69497.15 27-FEB-07:41
March 0.00 0.00 01-MAR-00:03 48.21 58.42 28092.67 67307.41 26-MAR-07:41
April 0.00 0.00 01-APR-00:10 51.62 59.21 27559.59 68873.79 17-APR-06:51
May 0.00 0.00 01-MAY-00:10 30.59 59.38 26859.86 64629.76 09-MAY-06:44
June 0.00 0.00 01-JUN-00:05 51.97 59.75 26178.46 60506.89 08-JUN-06:59
July 0.00 0.00 01-JUL-00:10 52.21 59.26 25656.07 57243.96 04-JUL-07:15
August 0.00 0.00 01-AUG-00:05 51.52 58.29 25497.82 57801.62 24-AUG-06:25
September 0.00 0.00 01-SEP-00:05 51.42 58.20 25646.90 63690.66 26-SEP-06:51
October 0.00 0.00 01-OCT-00:10 51.58 59.60 26115.28 63625.32 10-OCT-06:41
November 0.00 0.00 01-NOV-00:10 51.63 58.51 26836.31 66957.11 14-NOV-07:51
December 0.00 0.00 01-DEC-00:03 48.99 59.00 27574.58 66802.98 20-DEC-07:11
                 
Annual Sum or Average 0.00         26855.69    
Minimum of Months 0.00 0.00   30.59 58.20 25497.82 57243.96  
Maximum of Months 0.00 0.00   52.21 59.75 28263.92 69497.15  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.411142E+11 0.00 0.355681E+09 0.331216E+11 0.00 0.00
February 0.302289E+11 0.00 0.395107E+09 0.300284E+11 0.00 0.00
March 0.415822E+11 0.00 0.386217E+09 0.339839E+11 0.00 0.00
April 0.277374E+11 0.00 0.155165E+11 0.339705E+11 0.00 0.00
May 0.352258E+11 0.00 0.155244E+11 0.356740E+11 0.00 0.00
June 0.177565E+11 0.00 0.491578E+11 0.349261E+11 0.00 0.00
July 0.983721E+10 0.00 0.844461E+11 0.363842E+11 0.00 0.00
August 0.616149E+10 0.00 0.983977E+11 0.362009E+11 0.00 0.00
September 0.161638E+11 0.00 0.508194E+11 0.351015E+11 0.00 0.00
October 0.455091E+11 0.00 0.291661E+10 0.353042E+11 0.00 0.00
November 0.553542E+11 0.00 0.399621E+09 0.333499E+11 0.00 0.00
December 0.404277E+11 0.00 0.474291E+09 0.330231E+11 0.00 0.00
             
Annual Sum or Average 0.367099E+12 0.00 0.318789E+12 0.411068E+12 0.00 0.00
Minimum of Months 0.616149E+10 0.00 0.355681E+09 0.300284E+11 0.00 0.00
Maximum of Months 0.553542E+11 0.00 0.983977E+11 0.363842E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.823927E+09 0.00 0.00 0.587890E+10 0.00 0.00
February 0.280336E+09 0.00 0.00 0.530997E+10 0.00 0.00
March 36365041.25 0.00 0.00 0.587890E+10 0.00 0.00
April 25637.66 0.00 0.245873E+10 0.568926E+10 0.00 0.00
May 16999.53 0.00 0.246834E+10 0.587890E+10 0.00 0.00
June 27476.93 0.00 0.833990E+10 0.568926E+10 0.00 0.00
July 54424.44 0.00 0.147687E+11 0.587890E+10 0.00 0.00
August 63708.02 0.00 0.178806E+11 0.587890E+10 0.00 0.00
September 26630.81 0.00 0.924215E+10 0.568926E+10 0.00 0.00
October 2492.87 0.00 0.434541E+09 0.587890E+10 0.00 0.00
November 61966709.05 0.00 6967938.21 0.568926E+10 0.00 0.00
December 0.413543E+09 0.00 0.00 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.161636E+10 0.00 0.555999E+11 0.692193E+11 0.00 0.00
Minimum of Months 2492.87 0.00 0.00 0.530997E+10 0.00 0.00
Maximum of Months 0.823927E+09 0.00 0.178806E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.331216E+11 0.355717E+09 0.411142E+11 0.424706E+12 0.00 0.00 0.00 0.00
February 0.300284E+11 0.395126E+09 0.302289E+11 0.386668E+12 0.00 0.00 0.00 0.00
March 0.339839E+11 0.386217E+09 0.415822E+11 0.340360E+12 0.00 0.00 0.00 0.00
April 0.339705E+11 0.155165E+11 0.277374E+11 0.201663E+12 0.00 0.00 0.00 0.00
May 0.356740E+11 0.155244E+11 0.352258E+11 0.149778E+12 0.00 0.00 0.00 0.00
June 0.349261E+11 0.491578E+11 0.177565E+11 0.514569E+11 94140814.60 0.00 0.00 0.00
July 0.363842E+11 0.844461E+11 0.983721E+10 0.306973E+11 0.358653E+09 0.00 0.00 0.00
August 0.362009E+11 0.983977E+11 0.616149E+10 0.229154E+11 0.00 0.00 0.00 0.00
September 0.351015E+11 0.508194E+11 0.161638E+11 0.580500E+11 0.00 0.00 0.00 0.00
October 0.353042E+11 0.291663E+10 0.455091E+11 0.166494E+12 0.00 0.00 0.00 0.00
November 0.333499E+11 0.399984E+09 0.553542E+11 0.275760E+12 0.00 0.00 0.00 0.00
December 0.330231E+11 0.474291E+09 0.404277E+11 0.440092E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.411068E+12 0.318790E+12 0.367099E+12 0.254864E+13 0.452794E+09 0.00 0.00 0.00
Minimum of Months 0.300284E+11 0.355717E+09 0.616149E+10 0.229154E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.363842E+11 0.983977E+11 0.553542E+11 0.440092E+12 0.358653E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.00 0.823927E+09 0.796886E+11 0.00 0.00 0.00 0.00
February 0.530997E+10 0.00 0.280336E+09 0.722801E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.00 36365041.25 0.687455E+11 0.00 0.00 0.00 0.00
April 0.568926E+10 0.245873E+10 25637.66 0.456202E+11 0.00 0.00 0.00 0.00
May 0.587890E+10 0.246834E+10 16999.53 0.387693E+11 10648419.43 0.00 0.00 0.00
June 0.568926E+10 0.833990E+10 27476.93 0.167651E+11 0.330241E+09 0.00 0.00 0.00
July 0.587890E+10 0.147687E+11 54424.44 0.975118E+10 0.501868E+09 0.00 0.00 0.00
August 0.587890E+10 0.178806E+11 63708.02 0.682765E+10 71568093.43 0.00 0.00 0.00
September 0.568926E+10 0.924215E+10 26630.81 0.171499E+11 18210874.78 0.00 0.00 0.00
October 0.587890E+10 0.434541E+09 2492.87 0.424516E+11 0.00 0.00 0.00 0.00
November 0.568926E+10 6967938.21 61966709.05 0.604677E+11 0.00 0.00 0.00 0.00
December 0.587890E+10 0.00 0.413543E+09 0.816549E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.555999E+11 0.161636E+10 0.540172E+12 0.932536E+09 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.00 2492.87 0.682765E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.178806E+11 0.823927E+09 0.816549E+11 0.501868E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.331216E+11 0.411142E+11 0.355681E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.300284E+11 0.302289E+11 0.395107E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.339839E+11 0.415822E+11 0.386217E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.339705E+11 0.277374E+11 0.155165E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.356740E+11 0.352258E+11 0.155244E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.349261E+11 0.177565E+11 0.491578E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.363842E+11 0.983721E+10 0.844461E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.362009E+11 0.616149E+10 0.983977E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.351015E+11 0.161638E+11 0.508194E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.353042E+11 0.455091E+11 0.291661E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.333499E+11 0.553542E+11 0.399621E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.330231E+11 0.404277E+11 0.474291E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.411068E+12 0.367099E+12 0.318789E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.300284E+11 0.616149E+10 0.355681E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.363842E+11 0.553542E+11 0.983977E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.823927E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.280336E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 36365041.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 25637.66 0.245873E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 16999.53 0.246834E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 27476.93 0.833990E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 54424.44 0.147687E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 63708.02 0.178806E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 26630.81 0.924215E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 2492.87 0.434541E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 61966709.05 6967938.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.413543E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.161636E+10 0.555999E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 2492.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.823927E+09 0.178806E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.398583E+11 0.00 0.00 7643973.14 0.00 0.00 0.899397E+10 0.00 0.94
February 0.381313E+11 0.00 0.00 2874849.64 0.00 0.00 0.565412E+10 0.00 0.94
March 0.467319E+11 0.00 0.00 673715.58 0.00 0.00 0.260057E+10 0.00 0.93
April 0.463608E+11 0.00 0.00 445085.36 0.00 0.00 0.231146E+10 0.00 0.93
May 0.489156E+11 0.00 0.00 426316.63 0.00 0.00 0.214525E+10 0.00 0.93
June 0.418923E+11 0.00 0.00 1001318.89 40397918.30 0.00 0.381618E+10 0.00 0.96
July 0.364248E+11 0.00 0.00 4022003.09 158971.86 0.00 0.722165E+10 0.00 0.98
August 0.316313E+11 0.00 0.00 8058206.59 0.00 0.00 0.107477E+11 0.00 1.00
September 0.200779E+11 0.00 0.00 23244965.11 0.00 0.00 0.265134E+11 0.00 0.99
October 0.217118E+11 0.00 0.00 46660799.57 0.00 0.00 0.324164E+11 0.00 0.97
November 0.196994E+11 0.00 0.00 50751525.29 0.00 0.00 0.321884E+11 0.00 0.96
December 0.263642E+11 0.00 0.00 22142001.79 0.00 0.00 0.220533E+11 0.00 0.96
                   
Annual Sum or Average 0.417800E+12 0.00 0.00 0.167945E+09 40556890.17 0.00 0.156662E+12 0.00 0.96
Minimum of Months 0.196994E+11 0.00 0.00 426316.63 0.00 0.00 0.214525E+10 0.00 0.93
Maximum of Months 0.489156E+11 0.00 0.00 50751525.29 40397918.30 0.00 0.324164E+11 0.00 1.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.663328E+10 0.00 0.00 154540.21 0.00 0.170734E+10 0.171545E+09 0.00 2.95
February 0.649279E+10 0.00 0.00 386708.88 0.00 0.887399E+09 0.271103E+09 0.00 2.97
March 0.796082E+10 0.00 0.00 0.00 0.00 0.651984E+09 0.00 0.00 2.93
April 0.780789E+10 0.00 0.00 1016279.59 0.00 10275193.68 0.704575E+09 0.00 2.96
May 0.846205E+10 0.00 0.00 325920.20 0.00 24523749.38 0.427314E+09 0.00 2.93
June 0.771282E+10 0.00 0.00 332448.40 7052852.88 1696195.23 0.265365E+09 0.00 3.03
July 0.718234E+10 29728.04 0.00 809960.68 0.00 657769.55 0.439353E+09 0.00 3.10
August 0.672862E+10 0.00 0.00 1912191.43 0.00 0.00 0.698289E+09 0.00 3.19
September 0.697463E+10 0.00 0.00 3155563.72 0.00 3763455.00 0.114360E+10 0.00 3.17
October 0.841532E+10 0.00 0.00 903264.96 0.00 44977215.21 0.670424E+09 0.00 2.96
November 0.788238E+10 0.00 0.00 139111.88 0.00 0.635971E+09 0.156044E+09 0.00 2.92
December 0.480717E+10 0.00 0.00 27491.98 0.00 0.347409E+10 41836343.29 0.00 2.97
                   
Annual Sum or Average 0.870601E+11 29728.04 0.00 9163481.94 7052852.88 0.744268E+10 0.498945E+10 0.00 3.01
Minimum of Months 0.480717E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.92
Maximum of Months 0.846205E+10 29728.04 0.00 3155563.72 7052852.88 0.347409E+10 0.114360E+10 0.00 3.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.433582E+10 0.00 0.00 277.86 0.00 0.00 2918891.00 0.00 1.30
February 0.389468E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.31
March 0.438932E+10 0.00 0.00 14.77 0.00 0.00 1157176.34 0.00 1.29
April 0.382302E+10 0.00 0.00 424084.41 0.00 0.00 0.515738E+09 0.00 1.30
May 0.395780E+10 0.00 0.00 456925.97 0.00 0.00 0.593409E+09 0.00 1.30
June 0.306225E+10 932257.33 0.00 891658.15 2663012.63 0.00 0.102272E+10 0.00 1.35
July 0.252322E+10 13104.69 0.00 1584525.93 1043.24 0.00 0.140359E+10 0.00 1.39
August 0.220318E+10 0.00 0.00 1641463.41 0.00 0.00 0.161165E+10 0.00 1.41
September 0.277524E+10 0.00 0.00 1181449.85 0.00 0.00 0.134039E+10 0.00 1.37
October 0.434526E+10 0.00 0.00 306993.27 0.00 0.00 0.289896E+09 0.00 1.30
November 0.442024E+10 0.00 0.00 127.26 0.00 0.00 766695.59 0.00 1.29
December 0.424281E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.31
                   
Annual Sum or Average 0.439728E+11 945362.01 0.00 6487520.89 2664055.87 0.00 0.678225E+10 0.00 1.33
Minimum of Months 0.220318E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.29
Maximum of Months 0.442024E+10 932257.33 0.00 1641463.41 2663012.63 0.00 0.161165E+10 0.00 1.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.296084E+10 0.00 0.00 0.00 0.00 77674240.92 0.00 0.00 0.43
February 0.272714E+10 0.00 0.00 0.00 0.00 399640.25 0.00 0.00 0.43
March 0.307431E+10 0.00 0.00 0.00 0.00 443045.05 0.00 0.00 0.43
April 0.303358E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
May 0.318224E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
June 0.284890E+10 0.00 0.00 0.00 2517850.90 0.00 0.00 0.00 0.44
July 0.269018E+10 0.00 0.00 34740.23 9908.12 0.00 30368059.25 0.00 0.45
August 0.264148E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46
September 0.285445E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
October 0.324192E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
November 0.309614E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
December 0.293104E+10 0.00 0.00 0.00 0.00 40292487.68 0.00 0.00 0.43
                   
Annual Sum or Average 0.352822E+11 0.00 0.00 34740.23 2527759.02 0.118809E+09 30368059.25 0.00 0.44
Minimum of Months 0.264148E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.324192E+10 0.00 0.00 34740.23 2517850.90 77674240.92 30368059.25 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.164041E+10 0.00 0.00 0.00 0.00 0.353031E+09 0.00 0.00 0.49
February 0.169355E+10 0.00 0.00 0.00 0.00 95876038.78 0.00 0.00 0.49
March 0.199743E+10 0.00 0.00 0.00 0.00 19780302.36 0.00 0.00 0.48
April 0.199021E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
May 0.208773E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
June 0.186905E+10 0.00 0.00 0.00 1651856.48 0.00 0.00 0.00 0.50
July 0.178485E+10 0.00 0.00 0.00 6500.30 0.00 0.00 0.00 0.52
August 0.173296E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
September 0.187269E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
October 0.212689E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
November 0.198124E+10 0.00 0.00 0.00 0.00 50006649.78 0.00 0.00 0.48
December 0.150591E+10 0.00 0.00 0.00 0.00 0.443461E+09 0.00 0.00 0.49
                   
Annual Sum or Average 0.222829E+11 0.00 0.00 0.00 1658356.78 0.962155E+09 0.00 0.00 0.50
Minimum of Months 0.150591E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
Maximum of Months 0.212689E+10 0.00 0.00 0.00 1651856.48 0.443461E+09 0.00 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.688039E+09 0.00 0.00 0.137260E+09 0.00 0.00 0.695492E+11 0.00 20.63
February 0.916188E+09 0.00 0.00 0.122961E+09 0.00 0.00 0.621976E+11 0.00 20.70
March 0.110092E+10 0.00 0.00 0.162770E+09 0.00 0.00 0.706158E+11 0.00 20.58
April 0.437951E+09 0.00 0.00 0.167749E+09 0.00 0.00 0.701108E+11 0.00 20.67
May 0.101829E+10 0.00 0.00 0.170823E+09 0.00 0.00 0.731675E+11 0.00 20.74
June 0.883114E+09 62099390.34 0.00 0.118037E+09 0.00 0.00 0.654179E+11 0.00 21.46
July 0.521738E+09 193089.26 0.00 0.121339E+09 0.00 0.00 0.628103E+11 0.00 21.96
August 0.392146E+09 0.00 0.00 0.116433E+09 0.00 0.00 0.615544E+11 0.00 22.49
September 0.842137E+09 0.00 0.00 0.122848E+09 0.00 0.00 0.663939E+11 0.00 21.76
October 0.112229E+10 0.00 0.00 0.171270E+09 0.00 0.00 0.743767E+11 0.00 20.68
November 0.163282E+10 0.00 0.00 0.175598E+09 0.00 0.00 0.702405E+11 0.00 20.54
December 0.653326E+09 0.00 0.00 0.133189E+09 0.00 0.00 0.679480E+11 0.00 20.76
                   
Annual Sum or Average 0.102090E+11 62292479.60 0.00 0.172028E+10 0.00 0.00 0.814383E+12 0.00 21.08
Minimum of Months 0.392146E+09 0.00 0.00 0.116433E+09 0.00 0.00 0.615544E+11 0.00 20.54
Maximum of Months 0.163282E+10 62099390.34 0.00 0.175598E+09 0.00 0.00 0.743767E+11 0.00 22.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.303598E+11 0.00 0.00 1732430.27 0.00 2586834.19 0.282791E+10 0.00 4.10
February 0.263701E+11 0.00 0.00 2663393.09 0.00 6547128.83 0.346727E+10 0.00 4.12
March 0.318535E+11 0.00 0.00 194201.30 0.00 5109838.97 0.171441E+10 0.00 4.06
April 0.184998E+11 0.00 0.00 9611335.34 0.00 1270804.22 0.147247E+11 0.00 4.12
May 0.217368E+11 0.00 0.00 6261857.89 0.00 0.00 0.130146E+11 0.00 4.08
June 0.156998E+11 23478193.87 0.00 8098525.57 4014221.86 0.00 0.154045E+11 0.00 4.22
July 0.124718E+11 110620.06 0.00 13575275.97 0.00 0.00 0.172292E+11 0.00 4.31
August 0.780126E+10 0.00 0.00 21243293.91 0.00 0.00 0.211079E+11 0.00 4.42
September 0.109049E+11 0.00 0.00 24683454.81 0.00 0.00 0.206868E+11 0.00 4.39
October 0.239196E+11 0.00 0.00 8035311.35 0.00 0.00 0.116954E+11 0.00 4.12
November 0.297924E+11 0.00 0.00 1869333.42 0.00 0.00 0.403345E+10 0.00 4.06
December 0.316163E+11 0.00 0.00 333621.27 0.00 917532.16 0.828813E+09 0.00 4.13
                   
Annual Sum or Average 0.261026E+12 23588813.92 0.00 98302034.21 4014221.86 16432138.36 0.126735E+12 0.00 4.18
Minimum of Months 0.780126E+10 0.00 0.00 194201.30 0.00 0.00 0.828813E+09 0.00 4.06
Maximum of Months 0.318535E+11 23478193.87 0.00 24683454.81 4014221.86 6547128.83 0.211079E+11 0.00 4.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.867242E+11 0.00 0.00 1468771.17 0.00 0.00 0.530880E+10 0.00 1.64
February 0.765936E+11 0.00 0.00 1573378.38 0.00 0.00 0.601626E+10 0.00 1.65
March 0.861410E+11 0.00 0.00 1978285.28 0.00 0.00 0.698484E+10 0.00 1.63
April 0.561052E+11 0.00 0.00 26530499.53 0.00 0.00 0.361485E+11 0.00 1.65
May 0.605239E+11 0.00 0.00 30196262.66 0.00 0.00 0.363149E+11 0.00 1.64
June 0.408739E+11 20888781.46 0.00 43097631.14 55371707.82 0.00 0.461003E+11 0.00 1.71
July 0.319898E+11 277967.96 0.00 61012557.20 22128.49 0.00 0.516782E+11 0.00 1.75
August 0.221517E+11 0.00 0.00 68808712.18 0.00 0.00 0.593812E+11 0.00 1.79
September 0.287863E+11 0.00 0.00 67220297.83 0.00 0.00 0.593714E+11 0.00 1.74
October 0.681792E+11 0.00 0.00 24018666.45 0.00 0.00 0.304448E+11 0.00 1.65
November 0.842281E+11 0.00 0.00 3515348.27 0.00 0.00 0.956303E+10 0.00 1.63
December 0.879658E+11 0.00 0.00 289872.53 0.00 0.00 0.202956E+10 0.00 1.66
                   
Annual Sum or Average 0.730263E+12 21166749.42 0.00 0.329710E+09 55393836.32 0.00 0.349342E+12 0.00 1.68
Minimum of Months 0.221517E+11 0.00 0.00 289872.53 0.00 0.00 0.202956E+10 0.00 1.63
Maximum of Months 0.879658E+11 20888781.46 0.00 68808712.18 55371707.82 0.00 0.593812E+11 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.388591E+09 0.00 0.00 328333.72 0.00 0.113377E+10 35901244.73 0.00 0.47
February 0.367969E+09 0.00 0.00 1562746.55 0.00 0.949232E+09 0.107344E+09 0.00 0.47
March 0.409210E+09 0.00 0.00 596408.89 0.00 0.101373E+10 84862572.66 0.00 0.47
April 0.356723E+09 0.00 0.00 11026452.06 95318.22 0.425774E+09 0.889715E+09 0.00 0.47
May 0.383868E+09 173207.73 0.00 12744307.34 5039.64 0.298565E+09 0.103600E+10 0.00 0.47
June 0.324343E+09 6960305.09 0.00 15206129.92 3191510.75 22361445.50 0.113772E+10 0.00 0.47
July 0.387835E+09 4860054.20 0.00 16876156.56 838283.38 32107220.21 0.951769E+09 324.26 0.47
August 0.388881E+09 4315919.88 0.00 16080721.73 325401.15 1891153.11 0.916708E+09 0.00 0.47
September 0.322282E+09 2403456.00 0.00 13317125.98 564745.61 83607444.70 0.108047E+10 0.00 0.47
October 0.400385E+09 0.00 0.00 4005383.72 0.00 0.789491E+09 0.495964E+09 0.00 0.47
November 0.399484E+09 0.00 0.00 614213.48 0.00 0.106894E+10 50259991.07 0.00 0.47
December 0.291222E+09 0.00 0.00 7915.75 0.00 0.112987E+10 2847529.23 0.00 0.47
                   
Annual Sum or Average 0.442079E+10 18712942.89 0.00 92365895.70 5020298.74 0.694933E+10 0.678956E+10 324.26 0.47
Minimum of Months 0.291222E+09 0.00 0.00 7915.75 0.00 1891153.11 2847529.23 0.00 0.47
Maximum of Months 0.409210E+09 6960305.09 0.00 16876156.56 3191510.75 0.113377E+10 0.113772E+10 324.26 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.347890E+09 0.00 0.00 45402.01 0.00 0.120315E+10 7321271.44 0.00 0.47
February 0.381756E+09 0.00 0.00 461612.23 0.00 0.100525E+10 38473897.63 0.00 0.47
March 0.407967E+09 0.00 0.00 324039.18 0.00 0.104549E+10 54441011.22 0.00 0.47
April 0.458676E+09 0.00 0.00 7243264.62 95307.05 0.550388E+09 0.666734E+09 0.00 0.47
May 0.468138E+09 173187.43 0.00 10515335.75 5039.05 0.353267E+09 0.899055E+09 0.00 0.47
June 0.382617E+09 6947402.36 0.00 14146653.03 3203224.04 24963350.65 0.107772E+10 0.00 0.47
July 0.433861E+09 4754508.13 0.00 15536522.48 943161.80 37014764.68 0.902013E+09 324.22 0.47
August 0.447912E+09 3924882.94 0.00 12999591.14 715894.29 2052845.17 0.860441E+09 0.00 0.47
September 0.424475E+09 2179863.28 0.00 8574071.71 787990.56 0.151004E+09 0.915451E+09 0.00 0.47
October 0.472453E+09 0.00 0.00 1768009.15 0.00 0.969678E+09 0.245747E+09 0.00 0.47
November 0.392453E+09 0.00 0.00 104748.08 0.00 0.111306E+10 13499360.82 0.00 0.47
December 0.239018E+09 0.00 0.00 459.48 0.00 0.118467E+10 91824.78 0.00 0.47
                   
Annual Sum or Average 0.485721E+10 17979844.15 0.00 71719708.85 5750616.79 0.763999E+10 0.568099E+10 324.22 0.47
Minimum of Months 0.239018E+09 0.00 0.00 459.48 0.00 2052845.17 91824.78 0.00 0.47
Maximum of Months 0.472453E+09 6947402.36 0.00 15536522.48 3203224.04 0.120315E+10 0.107772E+10 324.22 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.192798E+11 0.00 0.00 6461449.04 0.00 0.821120E+09 0.102565E+10 0.00 0.53
February 0.175346E+11 0.00 0.00 5562742.39 0.00 0.747693E+09 0.104888E+10 0.00 0.54
March 0.198744E+11 0.00 0.00 0.00 0.00 0.578130E+09 0.00 0.00 0.53
April 0.128643E+11 188201.17 0.00 76928987.00 1104228.39 0.00 0.988201E+10 0.00 0.54
May 0.133147E+11 2416874.38 0.00 54305586.62 0.00 0.00 0.101042E+11 0.00 0.54
June 0.828240E+10 0.137650E+09 0.00 59480979.73 0.00 0.00 0.119917E+11 0.00 0.54
July 0.619681E+10 77268743.45 0.00 76930145.10 0.00 0.00 0.125543E+11 0.00 0.54
August 0.547226E+10 62932150.45 0.00 0.101521E+09 0.00 0.00 0.123725E+11 0.00 0.54
September 0.626213E+10 40246151.74 0.00 0.114554E+09 0.00 0.00 0.139576E+11 0.00 0.54
October 0.171055E+11 0.00 0.00 42590576.24 0.00 0.00 0.576466E+10 0.00 0.54
November 0.197231E+11 0.00 0.00 3112517.02 0.00 0.332205E+09 0.541897E+09 0.00 0.53
December 0.130621E+11 0.00 0.00 102.03 0.00 0.624064E+10 4649267.27 0.00 0.53
                   
Annual Sum or Average 0.158972E+12 0.320702E+09 0.00 0.541449E+09 1104228.39 0.871978E+10 0.792480E+11 0.00 0.54
Minimum of Months 0.547226E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.198744E+11 0.137650E+09 0.00 0.114554E+09 1104228.39 0.624064E+10 0.139576E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.568873E+10 0.00 0.00 13148465.99 0.00 0.828219E+10 0.715477E+10 0.00 0.53
February 0.530755E+10 0.00 0.00 10739322.37 0.00 0.769441E+10 0.632933E+10 0.00 0.54
March 0.560873E+10 0.00 0.00 34912955.63 0.00 0.237207E+10 0.124424E+11 0.00 0.53
April 0.694894E+10 0.00 0.00 84096712.22 1292782.97 57562662.23 0.157388E+11 0.00 0.54
May 0.743018E+10 219311.49 0.00 0.114249E+09 2198223.78 56378714.11 0.158788E+11 0.00 0.53
June 0.662263E+10 33196949.76 0.00 0.125294E+09 0.104490E+09 33948634.70 0.135573E+11 0.00 0.54
July 0.703846E+10 31926707.21 0.00 0.140112E+09 45363165.23 27242281.33 0.116273E+11 0.00 0.54
August 0.690590E+10 5841974.22 1162.83 0.117669E+09 57097794.43 23453105.28 0.109042E+11 8427.65 0.54
September 0.630154E+10 2628362.50 93371.81 86839491.93 37529608.09 46062121.23 0.139054E+11 5814.57 0.54
October 0.655975E+10 0.00 0.00 53052815.22 0.00 0.157492E+09 0.161487E+11 0.00 0.54
November 0.560806E+10 0.00 0.00 27301661.04 0.00 0.485820E+10 0.101124E+11 0.00 0.53
December 0.507828E+10 0.00 0.00 7219478.82 0.00 0.101062E+11 0.412103E+10 0.00 0.54
                   
Annual Sum or Average 0.750988E+11 73813305.19 94534.64 0.814635E+09 0.247972E+09 0.337152E+11 0.137921E+12 14242.22 0.54
Minimum of Months 0.507828E+10 0.00 0.00 7219478.82 0.00 23453105.28 0.412103E+10 0.00 0.53
Maximum of Months 0.743018E+10 33196949.76 93371.81 0.140112E+09 0.104490E+09 0.101062E+11 0.161487E+11 8427.65 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.391999E+09 0.00 0.00 370170.01 0.00 0.110907E+10 57147002.90 0.00 0.47
February 0.390440E+09 0.00 0.00 748925.01 0.00 0.950930E+09 83988982.52 0.00 0.47
March 0.409869E+09 0.00 0.00 461155.34 0.00 0.100287E+10 95199835.65 0.00 0.47
April 0.270781E+09 95318.22 0.00 14204019.64 0.00 0.400770E+09 0.997483E+09 0.00 0.47
May 0.301001E+09 173207.73 0.00 14176088.76 5039.64 0.302058E+09 0.111394E+10 0.00 0.47
June 0.275523E+09 6852036.74 0.00 14602744.10 3299779.09 45714296.43 0.116379E+10 0.00 0.47
July 0.313593E+09 4962502.17 0.00 15980069.90 736159.66 18770598.97 0.104024E+10 0.00 0.47
August 0.346501E+09 4479304.02 0.00 18392420.16 162017.01 1318917.85 0.957349E+09 0.00 0.47
September 0.247237E+09 2403456.00 0.00 15810825.45 564745.61 59059377.14 0.117757E+10 0.00 0.47
October 0.389733E+09 0.00 0.00 4300746.24 0.00 0.793301E+09 0.502509E+09 0.00 0.47
November 0.402229E+09 0.00 0.00 713373.73 0.00 0.105315E+10 63212041.69 0.00 0.47
December 0.295110E+09 0.00 0.00 96628.69 0.00 0.110210E+10 26642186.36 0.00 0.47
                   
Annual Sum or Average 0.403402E+10 18965824.89 0.00 99857167.03 4767741.01 0.683911E+10 0.727908E+10 0.00 0.47
Minimum of Months 0.247237E+09 0.00 0.00 96628.69 0.00 1318917.85 26642186.36 0.00 0.47
Maximum of Months 0.409869E+09 6852036.74 0.00 18392420.16 3299779.09 0.110907E+10 0.117757E+10 0.00 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.337541E+09 0.00 0.00 44450.80 0.00 0.120229E+10 18526344.40 0.00 0.47
February 0.377191E+09 0.00 0.00 156839.88 0.00 0.101161E+10 36987332.07 0.00 0.47
March 0.408264E+09 0.00 0.00 192642.04 0.00 0.104490E+10 54858826.34 0.00 0.47
April 0.419747E+09 95307.05 0.00 9587022.95 0.00 0.484884E+09 0.768824E+09 0.00 0.47
May 0.421720E+09 173187.43 0.00 11584903.66 5039.05 0.354258E+09 0.943412E+09 0.00 0.47
June 0.339857E+09 6781864.84 0.00 13314649.98 3368761.56 52443564.17 0.109383E+10 0.00 0.47
July 0.333506E+09 4936982.67 0.00 14446048.87 761011.48 21340568.66 0.101913E+10 0.00 0.47
August 0.355028E+09 4447918.36 0.00 15145698.35 192858.87 1807843.26 0.951424E+09 0.00 0.47
September 0.352833E+09 2383223.58 19118.88 10418950.24 564679.44 0.119250E+09 0.101700E+10 831.94 0.47
October 0.483600E+09 0.00 0.00 1676342.69 0.00 0.953996E+09 0.250373E+09 0.00 0.47
November 0.391417E+09 0.00 0.00 127739.04 0.00 0.110025E+10 27329454.01 0.00 0.47
December 0.243192E+09 0.00 0.00 9629.24 0.00 0.117847E+10 2112309.07 0.00 0.47
                   
Annual Sum or Average 0.446390E+10 18818483.94 19118.88 76704917.73 4892350.40 0.752550E+10 0.618382E+10 831.94 0.47
Minimum of Months 0.243192E+09 0.00 0.00 9629.24 0.00 1807843.26 2112309.07 0.00 0.47
Maximum of Months 0.483600E+09 6781864.84 19118.88 15145698.35 3368761.56 0.120229E+10 0.109383E+10 831.94 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.286611E+11 0.00 0.00 0.00 0.00 0.665915E+09 0.00 0.00 0.57
February 0.262770E+11 0.00 0.00 0.00 0.00 48484145.65 0.00 0.00 0.57
March 0.296450E+11 0.00 0.00 0.00 0.00 31735120.03 0.00 0.00 0.56
April 0.292794E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
May 0.307141E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
June 0.274969E+11 0.00 0.00 0.00 24301648.00 0.00 0.00 0.00 0.59
July 0.262264E+11 0.00 0.00 3620.66 95630.63 0.00 31828573.20 0.00 0.60
August 0.254949E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
September 0.275504E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.312834E+11 0.00 0.00 0.00 0.00 6736608.14 0.00 0.00 0.57
November 0.294687E+11 0.00 0.00 0.00 0.00 0.414415E+09 0.00 0.00 0.56
December 0.266520E+11 0.00 0.00 0.00 0.00 0.202656E+10 0.00 0.00 0.57
                   
Annual Sum or Average 0.338749E+12 0.00 0.00 3620.66 24397278.63 0.319384E+10 31828573.20 0.00 0.58
Minimum of Months 0.254949E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.56
Maximum of Months 0.312834E+11 0.00 0.00 3620.66 24301648.00 0.202656E+10 31828573.20 0.00 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 83852134.71 0.00 0.00 73334.03 0.00 0.300803E+09 4918530.23 0.00 0.47
February 85576268.78 0.00 0.00 400972.46 0.00 0.249777E+09 20772713.28 0.00 0.47
March 99357027.64 0.00 0.00 137078.25 0.00 0.263199E+09 14406276.39 0.00 0.47
April 83668807.79 0.00 0.00 2856074.71 23829.55 0.141741E+09 0.192544E+09 0.00 0.47
May 92533810.86 43301.93 0.00 3186096.36 1259.91 0.117998E+09 0.219076E+09 0.00 0.47
June 75809708.84 1743429.51 0.00 3929050.59 794524.45 20469781.29 0.274698E+09 0.00 0.47
July 90588215.32 1228325.67 0.00 4522328.28 196258.73 23635709.16 0.228401E+09 81.07 0.47
August 94897479.46 1083501.64 0.00 4137837.46 76828.61 853835.92 0.231001E+09 0.00 0.47
September 79443517.61 600864.00 0.00 3187250.87 141186.40 49934652.22 0.242355E+09 0.00 0.47
October 0.100245E+09 0.00 0.00 895094.36 0.00 0.236515E+09 84806631.85 0.00 0.47
November 93591481.06 0.00 0.00 140237.10 0.00 0.278699E+09 7394012.42 0.00 0.47
December 54192840.89 0.00 0.00 682.30 0.00 0.301747E+09 45954.70 0.00 0.47
                   
Annual Sum or Average 0.103376E+10 4699422.75 0.00 23466036.77 1233887.65 0.198537E+10 0.152042E+10 81.07 0.47
Minimum of Months 54192840.89 0.00 0.00 682.30 0.00 853835.92 45954.70 0.00 0.47
Maximum of Months 0.100245E+09 1743429.51 0.00 4522328.28 794524.45 0.301747E+09 0.274698E+09 81.07 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 63398308.38 0.00 0.00 6366.24 0.00 0.325142E+09 1054605.92 0.00 0.47
February 82314007.60 0.00 0.00 96083.79 0.00 0.265763E+09 8311951.12 0.00 0.47
March 98081609.13 0.00 0.00 68810.42 0.00 0.269307E+09 9597698.74 0.00 0.47
April 0.111835E+09 0.00 0.00 1875336.05 23826.76 0.174377E+09 0.132672E+09 0.00 0.47
May 0.112081E+09 43296.86 0.00 2599924.76 1259.76 0.136657E+09 0.181406E+09 0.00 0.47
June 87013401.34 1740697.67 0.00 3661043.67 796958.93 27047638.14 0.257141E+09 0.00 0.47
July 0.100696E+09 1203352.57 0.00 4181654.88 221064.92 24181979.20 0.218047E+09 81.06 0.47
August 0.106582E+09 1016792.99 0.00 3299539.51 143401.32 3281846.22 0.217688E+09 0.00 0.47
September 0.105015E+09 593089.30 0.00 1937299.10 148874.16 84974954.74 0.182949E+09 0.00 0.47
October 0.116673E+09 0.00 0.00 359845.08 0.00 0.268704E+09 36675263.29 0.00 0.47
November 81686816.29 0.00 0.00 12637.48 0.00 0.296074E+09 2006690.52 0.00 0.47
December 29803745.37 0.00 0.00 35.32 0.00 0.326134E+09 7537.03 0.00 0.47
                   
Annual Sum or Average 0.109518E+10 4597229.39 0.00 18098576.31 1335385.85 0.220164E+10 0.124756E+10 81.06 0.47
Minimum of Months 29803745.37 0.00 0.00 35.32 0.00 3281846.22 7537.03 0.00 0.47
Maximum of Months 0.116673E+09 1740697.67 0.00 4181654.88 796958.93 0.326134E+09 0.257141E+09 81.06 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.488294E+09 0.00 0.00 6258648.47 0.00 0.140434E+10 0.604389E+09 0.00 0.53
February 0.463686E+09 0.00 0.00 7825920.55 0.00 0.114113E+10 0.677865E+09 0.00 0.54
March 0.624676E+09 0.00 0.00 2858363.30 0.00 0.129962E+10 0.495513E+09 0.00 0.53
April 0.409569E+09 0.00 0.00 23059224.39 153092.72 0.439779E+09 0.183108E+10 0.00 0.54
May 0.533063E+09 278192.80 0.00 17908979.93 8094.28 0.398128E+09 0.183138E+10 0.00 0.54
June 0.500041E+09 11004239.20 0.00 17969601.29 5300818.96 54010814.01 0.183656E+10 0.00 0.54
July 0.592741E+09 7852596.52 0.00 20922293.30 1297118.40 21385148.08 0.159519E+10 3033.13 0.54
August 0.603120E+09 7113126.41 0.00 25288386.86 341402.96 3199558.34 0.149419E+10 0.00 0.54
September 0.420925E+09 3860244.37 0.00 27754913.04 907050.54 34032797.55 0.192596E+10 0.00 0.54
October 0.499976E+09 0.00 0.00 13568699.71 0.00 0.751293E+09 0.144926E+10 0.00 0.54
November 0.518810E+09 0.00 0.00 6467551.88 0.00 0.130446E+10 0.610440E+09 0.00 0.53
December 0.463940E+09 0.00 0.00 1648890.78 0.00 0.163729E+10 0.184155E+09 0.00 0.54
                   
Annual Sum or Average 0.611884E+10 30108399.30 0.00 0.171531E+09 8007577.86 0.848867E+10 0.145360E+11 3033.13 0.54
Minimum of Months 0.409569E+09 0.00 0.00 1648890.78 0.00 3199558.34 0.184155E+09 0.00 0.53
Maximum of Months 0.624676E+09 11004239.20 0.00 27754913.04 5300818.96 0.163729E+10 0.192596E+10 3033.13 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.509385E+10 0.00 0.00 64230405.25 0.00 0.00 0.382457E+11 0.00 3.95
February 0.298127E+10 0.00 0.00 58373571.60 0.00 0.00 0.361278E+11 0.00 3.98
March 0.273995E+10 0.00 0.00 84630694.91 0.00 0.00 0.429209E+11 0.00 4.07
April 0.113460E+10 0.00 0.00 0.106321E+09 0.00 0.00 0.459706E+11 0.00 4.26
May 0.763104E+09 0.00 0.00 0.125216E+09 0.00 0.00 0.499775E+11 0.00 4.35
June 80146760.55 39672691.74 0.00 0.104690E+09 0.00 0.00 0.472057E+11 0.00 4.64
July 12301890.58 153412.16 0.00 0.109380E+09 0.00 0.00 0.460739E+11 0.00 4.81
August 52696962.14 0.00 0.00 99196224.82 0.00 0.00 0.446144E+11 0.00 4.84
September 0.259542E+09 0.00 0.00 98943604.52 0.00 0.00 0.461355E+11 0.00 4.55
October 0.190083E+10 0.00 0.00 0.107528E+09 0.00 0.00 0.475266E+11 0.00 4.17
November 0.372789E+10 0.00 0.00 92396683.73 0.00 0.00 0.420368E+11 0.00 4.03
December 0.491603E+10 0.00 0.00 59336533.11 0.00 0.00 0.371199E+11 0.00 3.95
                   
Annual Sum or Average 0.236622E+11 39826103.91 0.00 0.111024E+10 0.00 0.00 0.523955E+12 0.00 4.30
Minimum of Months 12301890.58 0.00 0.00 58373571.60 0.00 0.00 0.361278E+11 0.00 3.95
Maximum of Months 0.509385E+10 39672691.74 0.00 0.125216E+09 0.00 0.00 0.499775E+11 0.00 4.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.168411E+10 0.00 0.00 87366418.99 0.00 0.00 0.460104E+11 0.00 4.33
February 0.103321E+10 0.00 0.00 82241772.86 0.00 0.00 0.419987E+11 0.00 4.37
March 0.953091E+09 0.00 0.00 0.112671E+09 0.00 0.00 0.494621E+11 0.00 4.48
April 0.232892E+09 0.00 0.00 0.132647E+09 0.00 0.00 0.514168E+11 0.00 4.67
May 0.173829E+09 0.00 0.00 0.149789E+09 0.00 0.00 0.553134E+11 0.00 4.75
June 5804944.31 43169670.94 0.00 0.118924E+09 0.00 0.00 0.513677E+11 0.00 5.05
July 0.00 165737.35 0.00 0.122301E+09 0.00 0.00 0.498759E+11 0.00 5.21
August 0.00 0.00 0.00 0.112566E+09 0.00 0.00 0.482760E+11 0.00 5.24
September 18796489.26 0.00 0.00 0.114794E+09 0.00 0.00 0.504201E+11 0.00 4.95
October 0.433409E+09 0.00 0.00 0.133849E+09 0.00 0.00 0.538901E+11 0.00 4.57
November 0.122524E+10 0.00 0.00 0.123025E+09 0.00 0.00 0.491511E+11 0.00 4.42
December 0.168364E+10 0.00 0.00 82344063.14 0.00 0.00 0.445734E+11 0.00 4.33
                   
Annual Sum or Average 0.744402E+10 43335408.29 0.00 0.137252E+10 0.00 0.00 0.591756E+12 0.00 4.70
Minimum of Months 0.00 0.00 0.00 82241772.86 0.00 0.00 0.419987E+11 0.00 4.33
Maximum of Months 0.168411E+10 43169670.94 0.00 0.149789E+09 0.00 0.00 0.553134E+11 0.00 5.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1748471.78 0.00 0.00 0.173985E+09 0.00 0.00 0.641056E+11 0.00 18.97
February 4415760.94 0.00 0.00 0.163438E+09 0.00 0.00 0.579532E+11 0.00 19.18
March 17026623.91 0.00 0.00 0.202861E+09 0.00 0.00 0.658457E+11 0.00 19.12
April 12733296.14 0.00 0.00 0.210846E+09 0.00 0.00 0.665645E+11 0.00 19.88
May 53529517.17 0.00 0.00 0.213357E+09 0.00 0.00 0.699570E+11 0.00 19.99
June 36828317.99 67430901.08 0.00 0.154731E+09 0.00 0.00 0.622630E+11 0.00 21.05
July 23188084.85 265212.00 0.00 0.159025E+09 0.00 0.00 0.592782E+11 0.00 21.68
August 2091347.53 0.00 0.00 0.153947E+09 0.00 0.00 0.568414E+11 0.00 22.04
September 17389423.07 0.00 0.00 0.159185E+09 0.00 0.00 0.623596E+11 0.00 21.28
October 91552311.10 0.00 0.00 0.198884E+09 0.00 0.00 0.698239E+11 0.00 19.49
November 76727575.31 0.00 0.00 0.217861E+09 0.00 0.00 0.654795E+11 0.00 18.94
December 2993955.80 0.00 0.00 0.162840E+09 0.00 0.00 0.620386E+11 0.00 18.96
                   
Annual Sum or Average 0.340225E+09 67696113.08 0.00 0.217096E+10 0.00 0.00 0.762510E+12 0.00 20.05
Minimum of Months 1748471.78 0.00 0.00 0.153947E+09 0.00 0.00 0.568414E+11 0.00 18.94
Maximum of Months 91552311.10 67430901.08 0.00 0.217861E+09 0.00 0.00 0.699570E+11 0.00 22.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145441E+11 0.00 0.00 0.00 0.00 0.471766E+09 0.00 0.00 1.10
February 0.134243E+11 0.00 0.00 0.00 0.00 54719979.49 0.00 0.00 1.11
March 0.151928E+11 0.00 0.00 0.00 0.00 2154338.26 0.00 0.00 1.09
April 0.149608E+11 0.00 0.00 40902.56 0.00 575154.03 30081485.75 0.00 1.10
May 0.157075E+11 0.00 0.00 5809.72 0.00 0.00 18627655.83 0.00 1.10
June 0.140232E+11 0.00 0.00 138633.52 12442808.70 0.00 55478353.53 0.00 1.14
July 0.131630E+11 52032.41 0.00 617806.19 0.00 0.00 0.281443E+09 0.00 1.16
August 0.128795E+11 0.00 0.00 173042.13 0.00 0.00 0.174134E+09 0.00 1.18
September 0.140592E+11 0.00 0.00 35198.18 0.00 0.00 47049619.72 0.00 1.15
October 0.160185E+11 0.00 0.00 0.00 0.00 2571811.51 0.00 0.00 1.10
November 0.152863E+11 0.00 0.00 0.00 0.00 14279378.97 0.00 0.00 1.09
December 0.142820E+11 0.00 0.00 0.00 0.00 0.401856E+09 0.00 0.00 1.11
                   
Annual Sum or Average 0.173541E+12 52032.41 0.00 1011392.30 12442808.70 0.947922E+09 0.606814E+09 0.00 1.12
Minimum of Months 0.128795E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.09
Maximum of Months 0.160185E+11 52032.41 0.00 617806.19 12442808.70 0.471766E+09 0.281443E+09 0.00 1.18



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:41:37

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.802163E+11 0.172949E+11 0.225765E+12 0.905036E+12 0.614002E+11
February 0.129868E+12 0.155835E+11 0.201485E+12 0.821312E+12 0.531656E+11
March 0.166765E+12 0.157435E+11 0.204436E+12 0.831678E+12 0.603921E+11
April 0.422129E+12 0.129772E+11 0.159967E+12 0.697797E+12 0.119422E+12
May 0.549247E+12 0.124404E+11 0.156376E+12 0.669147E+12 0.127250E+12
June 0.556305E+12 0.923643E+10 0.116513E+12 0.510913E+12 0.195917E+12
July 0.557929E+12 0.845940E+10 0.102833E+12 0.468243E+12 0.264422E+12
August 0.447593E+12 0.825905E+10 0.949659E+11 0.447669E+12 0.284702E+12
September 0.326853E+12 0.938388E+10 0.113845E+12 0.521386E+12 0.204460E+12
October 0.148608E+12 0.127014E+11 0.166029E+12 0.690151E+12 0.862112E+11
November 0.593560E+11 0.144970E+11 0.192862E+12 0.769333E+12 0.678425E+11
December 0.207523E+11 0.172109E+11 0.227287E+12 0.906799E+12 0.614414E+11
           
Annual Sum or Average 0.346562E+13 0.153788E+12 0.196237E+13 0.823946E+13 0.158663E+13
Minimum of Months 0.207523E+11 0.825905E+10 0.949659E+11 0.447669E+12 0.531656E+11
Maximum of Months 0.557929E+12 0.172949E+11 0.227287E+12 0.906799E+12 0.284702E+12