Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:42:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10911.44 | 961.76 | 961.76 |
Net Site Energy | 10911.44 | 961.76 | 961.76 |
Total Source Energy | 24118.51 | 2125.86 | 2125.86 |
Net Source Energy | 24118.51 | 2125.86 | 2125.86 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 297.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1420.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 868.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 603.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 100.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 183.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2924.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5900.39 | 5011.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 297.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1420.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 868.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 603.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 100.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 183.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2924.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 297.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1420.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 868.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 650.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 603.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 100.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 183.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2924.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.24 | 284.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.12 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 520.07 | 441.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.24 | 284.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.12 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 520.07 | 441.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5900.391 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5900.391 | 100.00 |
Total On-Site and Utility Electric Sources | 5900.391 | 100.00 |
Total Electricity End Uses | 5900.391 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 309.58 | 21.50 |
Air to Air Heat Recovery for Heating | 1130.13 | 78.50 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1439.71 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 289.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7844.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.3255 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.5208 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.7005 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 11.5174 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.6875 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7951 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7951 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 9.7951 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 11.5174 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 9.4981 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.3255 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.5625 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.5208 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.7005 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 11.5174 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.6875 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 9.7951 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 9.7951 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 9.7951 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 9.7951 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 11.5174 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 13.0243 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 9.4981 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 5.0165 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JUN-19:10 | 26-NOV-17:40 | - | - | - | - | - | - | - | - | - | - | 06-JAN-21:10 |
Heating | 0.00 | 161599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 155485.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 87521.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32080.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34545.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4922.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4037.67 | 242418.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2366.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 418067.96 | 491539.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 161599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 155485.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 12545.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1777.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 34545.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4922.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4037.67 | 242418.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1057.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1067.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 322.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4498.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2751.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2058.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1912.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 316.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 582.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3170.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 18686.54 | 5431.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 28.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 396.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 279.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1647.08 | 478.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 28.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 396.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 279.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1647.08 | 478.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.12 | 0.482825 | 0.459000 | 1.43 | 1.00 | 0.500000 | 0.000789 | 0.000057 | 1.43 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.376862 | 0.135616 | 0.459000 | 0.172980 | 0.459000 | 0.500000 | 0.002809 | 0.000030 | 0.172980 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.283903 | 0.208464 | 0.459000 | 0.130311 | 0.555905 | 0.500000 | 0.001828 | 0.000013 | 0.130311 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.235946 | 0.530432 | 0.459000 | 0.108299 | 1.00 | 0.500000 | 0.000718 | 0.000018 | 0.108299 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.156452 | 0.461526 | 0.459000 | 0.071811 | 1.00 | 0.500000 | 0.000826 | 0.000012 | 0.071811 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.78 | 0.062505 | 0.459000 | 1.73 | 0.459000 | 0.500000 | 0.024188 | 0.000088 | 1.73 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.60 | 0.089919 | 0.459000 | 0.734620 | 0.459000 | 0.500000 | 0.004237 | 0.000089 | 0.734620 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.34 | 0.186694 | 0.459000 | 2.45 | 0.497851 | 0.500000 | 0.002041 | 0.000233 | 2.45 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.76 | 0.676034 | 0.459000 | 0.805862 | 1.00 | 0.500000 | 0.000564 | 0.000114 | 0.805862 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.57 | 0.098326 | 0.459000 | 1.18 | 0.459000 | 0.500000 | 0.003875 | 0.000100 | 1.18 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.69 | 0.093888 | 0.459000 | 1.24 | 0.459000 | 0.500000 | 0.004058 | 0.000104 | 1.24 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.59 | 0.054639 | 0.459000 | 1.19 | 0.459000 | 0.500000 | 0.012542 | 0.000065 | 1.19 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.894041 | 0.351258 | 0.459000 | 0.410365 | 0.936688 | 0.500000 | 0.001085 | 0.000073 | 0.410365 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6564.04 | 0.000057 | 136.88 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3481.75 | 0.000030 | 88.53 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1458.90 | 0.000013 | 32.91 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2047.10 | 0.000018 | 51.14 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1383.86 | 0.000012 | 34.76 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10030.33 | 0.000088 | 212.07 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10179.92 | 0.000089 | 237.53 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26640.50 | 0.000233 | 598.46 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5827.75 | 0.000051 | 166.53 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5821.41 | 0.000051 | 166.35 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33597.29 | 0.000294 | 960.05 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33495.08 | 0.000293 | 957.13 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5815.75 | 0.000051 | 166.19 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5809.41 | 0.000051 | 166.01 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13065.33 | 0.000114 | 314.50 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1788.68 | 0.000016 | 51.11 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1787.91 | 0.000016 | 51.09 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8621.77 | 0.000075 | 246.36 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 11472.18 | 0.000100 | 254.11 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11855.52 | 0.000104 | 262.19 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7407.24 | 0.000065 | 157.41 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8301.58 | 0.000073 | 211.39 |
VAV WITH REHEAT HEATING COIL | 174204.76 | 0.001524 | 2957.31 |
FLR_3_DOAS HEATING COIL | 14143.00 | 0.000124 | 240.09 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.22 | 0.000051 | 0.000420 |
ROOM_2_FLR_3 FAN COIL | 1.21 | 0.000051 | 0.000417 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.37 | 0.000294 | 0.002517 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.96 | 0.000293 | 0.002852 |
ROOM_5_FLR_3 FAN COIL | 1.07 | 0.000051 | 0.000371 |
ROOM_6_FLR_3 FAN COIL | 1.06 | 0.000051 | 0.000368 |
ROOM_1_FLR_6 FAN COIL | 0.322453 | 0.000016 | 0.000111 |
ROOM_2_FLR_6 FAN COIL | 0.320015 | 0.000016 | 0.000110 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.45 | 0.000075 | 0.000509 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.22 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.21 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.37 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.96 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.07 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.06 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.322453 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.320015 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.45 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008541 | 12.80 | 0.008500 | 0.000420 | 1.22 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008541 | 12.80 | 0.008500 | 0.000417 | 1.21 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008476 | 12.80 | 0.008476 | 0.002517 | 7.37 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008678 | 12.80 | 0.008500 | 0.002852 | 7.96 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008546 | 12.80 | 0.008500 | 0.000371 | 1.07 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008546 | 12.80 | 0.008500 | 0.000368 | 1.06 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008539 | 12.80 | 0.008500 | 0.000111 | 0.322453 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008539 | 12.80 | 0.008500 | 0.000110 | 0.320015 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008603 | 12.80 | 0.008500 | 0.000509 | 1.45 | |
VAV WITH REHEAT COOLING COIL | 30.50 | 6.70 | 0.008351 | 10.70 | 0.008351 | 0.019045 | 25.27 | 533215.33 |
FLR_3_DOAS COOLING COIL | 38.10 | 6.70 | 0.006871 | 11.79 | 0.006871 | 0.002048 | 2.05 | 57348.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.70 | 11.66 | 25.39 | 11.66 | 25.27 | 25.27 | 0.300000 | 0.461316 | 25.27 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 25.27 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 25.27 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.019045 | 0.000025 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001524 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002048 | 0.000232 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000124 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.028767 | 4696.83 | |
HEATSYS1 PUMP | 0.003541 | 1066.51 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003541 | 0.424965 |
COOLSYS1 | 0.028767 | 3.45 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 404801.06 | 404801.06 | 0.003541 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.028767 | 3251.78 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.028767 | 805410.07 | 806087.68 | 91.89 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.325 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.705 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.521 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.901 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.700 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.390 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 11.517 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.897 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 11.517 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 79.337 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 20432.332 | 10.325 | 191.855 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20432.332 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.656 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.656 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.385 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.385 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 742.517 | 4.521 | 279.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 742.517 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 729.693 | 7.700 | 357.693 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 729.693 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2175.192 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2175.192 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 12673.066 | 9.688 | 30.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12673.066 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.280 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.280 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3819.822 | 11.517 | 15.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3819.822 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.470 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.470 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.496_SHGC_0.25 | 37 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.496_SHGC_0.25 | 38 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.16139 | 0.61164 | 0.61164 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.16139 | 0.61164 | 0.61164 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.3945E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.1877E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1040 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.5473E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1944E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6614E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1062 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.1341E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1179 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.5711E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9683E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3635E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3060E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3169E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7765E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9456E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6976E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.7808E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3060E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3169E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7765E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9456E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6976E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.7808E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 37277.16441 | 37277.16441 | 3.12302 | 3.12302 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 30.82000 | 6.85992E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4497.96308 | 4497.96308 | 0.37686 | 0.37686 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2690.33270 | 2690.33270 | 0.13296 | 0.13296 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3388.36674 | 3388.36674 | 0.28390 | 0.28390 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 36.06333 | 6.86822E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 862.71241 | 862.71241 | 4.26372E-002 | 9.17347E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2816.65192 | 2816.65192 | 0.23595 | 0.23595 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 33.68000 | 6.86443E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1551.73847 | 1551.73847 | 7.66899E-002 | 7.66899E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1867.65993 | 1867.65993 | 0.15645 | 0.15645 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 36.06333 | 6.86822E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1055.34870 | 1055.34870 | 5.21574E-002 | 5.77652E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45064.29935 | 45064.29935 | 3.77530 | 3.77530 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 37.32000 | 6.87023E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2105.07492 | 2105.07492 | 0.10403 | 0.10403 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19085.14679 | 19085.14679 | 1.60048 | 1.60048 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6818.48550 | 6818.48550 | 0.33697 | 0.67639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 63706.48433 | 63706.48433 | 5.33942 | 5.33942 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15427.21630 | 15427.21630 | 0.76244 | 1.89399 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10763.44063 | 10763.44063 | 1.21506 | 1.21506 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5827.86602 | 5827.86602 | 0.28971 | 0.28971 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10692.39517 | 10692.39517 | 1.20704 | 1.20704 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5821.52905 | 5821.52905 | 0.28939 | 0.28939 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 65275.01992 | 65275.01992 | 7.36849 | 7.36849 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33597.61082 | 33597.61082 | 1.67022 | 1.67022 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 70473.83056 | 70473.83056 | 7.95599 | 7.95599 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33495.39785 | 33495.39785 | 1.66513 | 1.66513 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9489.71860 | 9489.71860 | 1.07127 | 1.07127 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5815.86565 | 5815.86565 | 0.28911 | 0.28911 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9418.79860 | 9418.79860 | 1.06327 | 1.06327 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 33.16000 | 6.86360E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5809.52691 | 5809.52691 | 0.28880 | 0.28880 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20957.00716 | 20957.00716 | 1.75569 | 1.75569 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9377.37698 | 9377.37698 | 0.46346 | 0.47476 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2856.40475 | 2856.40475 | 0.32245 | 0.32245 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1788.71500 | 1788.71500 | 8.89188E-002 | 8.89188E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2834.80115 | 2834.80115 | 0.32001 | 0.32001 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1787.94001 | 1787.94001 | 8.88802E-002 | 8.88802E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12832.28447 | 12832.28447 | 1.44865 | 1.44865 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8621.90181 | 8621.90181 | 0.42861 | 0.42861 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30640.05217 | 30640.05217 | 2.57024 | 2.57024 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6072.75031 | 6072.75031 | 0.30013 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32089.10910 | 32089.10910 | 2.69175 | 2.69175 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6200.77282 | 6200.77282 | 0.30645 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30846.37646 | 30846.37646 | 2.59127 | 2.59127 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1977.33762 | 1977.33762 | 9.77115E-002 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10671.93880 | 10671.93880 | 0.89404 | 0.89404 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6423.25596 | 6423.25596 | 0.31745 | 0.31745 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 469358.96 | 25.26686 | 25.26686 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 170599.36 | 7.42318 | 7.42318 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 54460.49 | 21.48472 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 47141.68 | 5.09877 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.12302 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48282 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.43346 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.89107E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.74251E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.43346 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6564.03855 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.74251E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 136.88171 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.37686 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13562 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17298 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80941E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.04599E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17298 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3481.75377 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04599E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 88.52929 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28390 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20846 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13031 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55591 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82765E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27631E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13031 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1458.90271 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27631E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 32.90588 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23595 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53043 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10830 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.18282E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.79089E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10830 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2047.09678 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79089E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 51.14433 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15645 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46153 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.18114E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.25523E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21066E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.18114E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1383.86083 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21066E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.75580 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.77530 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.25047E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.73286 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41884E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.77497E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.73286 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10030.32740 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.77497E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 212.07114 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60048 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.99186E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73462 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23717E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.90584E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73462 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10179.91699 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.90584E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.52716 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.33942 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18669 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.45079 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49785 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04077E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33063E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.45079 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26640.49608 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33063E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 598.45630 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21506 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.21506 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.09837E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.19696E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54101E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.19696E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21506 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5827.75047 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.09837E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 166.53176 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.20704 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.20704 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.09283E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.16956E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54128E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.16956E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.20704 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5821.41363 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.09283E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 166.35071 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.36849 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.36849 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.93924E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.51651E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77125 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47553E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47553E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.51651E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.36849 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33597.29110 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93924E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 960.05079 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.95599 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.95599 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.93030E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.85162E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77033 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67849E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.85162E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.95599 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33495.07902 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93030E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 957.13071 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07127 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.07127 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.08787E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.70520E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77085 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54584E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.70520E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07127 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5815.75033 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.08787E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 166.18892 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06327 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.06327 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.08233E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.67780E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77085 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54612E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.67780E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.06327 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5809.41171 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.08233E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 166.00783 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.75569 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67603 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80586 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.63581E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14301E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80586 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13065.33119 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14301E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 314.49643 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32245 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32245 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.56482E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.11308E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77087 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53870E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.11308E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32245 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1788.68063 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56482E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 51.11058 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32001 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32001 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.56414E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.10474E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53896E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.10474E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32001 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1787.90566 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56414E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 51.08844 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.44865 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.44865 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.54270E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.08942E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77053 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60348E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.08942E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.44865 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8621.76934 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.54270E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 246.36066 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.57024 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.83264E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17974 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45900 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.87485E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00364E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17974 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11472.18335 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00364E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 254.10789 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.69175 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.38878E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23552 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45900 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.05803E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03717E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23552 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11855.51805 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03717E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 262.18757 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.59127 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.46390E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18939 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45900 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25419E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.48018E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18939 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7407.24235 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.48018E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 157.40794 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89404 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35126 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45900 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41036 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93669 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08467E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.26259E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41036 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8301.58410 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.26259E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 211.39284 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.69718 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65602 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.39437 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65602 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.26686 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 25.26686 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 25.26686 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.26686 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.50152 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.69730 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.35102E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.35102E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 533215.32954 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.90452E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 25.26686 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 174204.75611 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52402E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2957.30557 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 25.26686 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.90452E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.50032E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.52402E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 38.10000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.79311 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 57348.72296 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04836E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 14143.00265 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23729E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 240.09207 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.04836E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.32474E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23729E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.87674E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4696.83438 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.54138E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.42497 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.54138E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1066.50702 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 404801.06280 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 404801.06000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.54138E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.87674E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.45209 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.87674E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3251.77685 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.87674E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 805410.07125 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 806087.68000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 91.89400 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6598.35 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3497.12 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1466.02 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2056.24 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1390.02 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10082.25 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10228.37 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 26770.82 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6278.73 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6271.91 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 36197.05 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 36086.95 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6265.81 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6258.98 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13125.34 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1927.05 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1926.22 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9288.72 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 11528.91 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11914.22 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7445.45 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8338.20 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 131198.09 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 10651.46 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 20488.47 | 15514.70 | 4973.77 | 0.76 | 3295.97 | 33.43 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20354.20 | 15412.63 | 4941.57 | 0.76 | 3274.23 | 33.21 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 123649.08 | 93964.20 | 29684.88 | 0.76 | 20251.42 | 205.40 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 137394.94 | 102730.39 | 34664.55 | 0.75 | 21657.80 | 219.67 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 18079.34 | 13684.09 | 4395.24 | 0.76 | 2906.12 | 29.48 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 17945.13 | 13582.15 | 4362.99 | 0.76 | 2884.41 | 29.26 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5435.01 | 4116.52 | 1318.49 | 0.76 | 874.66 | 8.87 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5394.15 | 4085.47 | 1308.68 | 0.76 | 868.05 | 8.80 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 24695.18 | 18590.92 | 6104.26 | 0.75 | 3933.43 | 39.90 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 667011.94 | 415448.39 | 251563.55 | 0.62 | 95569.28 | 969.32 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51198.70 | 32051.32 | 19147.38 | 0.63 | 5018.41 | 50.90 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.25 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 4.5911635930E-002 | 6.9161851830E-002 | Pass | Pass | 0.2602487760 | 0.7497347560 | Pass | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.7485294133E-002 | 0.1444883143 | Pass | Pass | 0.5062325177 | 2.4977244771 | Fail | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.6480605365E-002 | 0.1048778026 | Pass | Pass | 0.3453340833 | 1.3101638826 | Pass | Fail |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.4836437128E-002 | 4.5395379909E-002 | Pass | Pass | 1.0236831129 | 6.9723606462 | Pass | Fail |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5242901659E-002 | 4.9668107826E-002 | Pass | Pass | 0.3151226514 | 0.8606265810 | Pass | Fail |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2498975806 | 0.4666503151 | Fail | Fail | 0.1115592370 | 0.2088757740 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1251401211 | 0.2165866368 | Pass | Fail | 0.2475076488 | 0.7054392126 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.1992677601E-002 | 0.1192913987 | Pass | Fail | 0.2598376279 | 0.7462794622 | Pass | Fail |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.9547736257E-002 | 0.1952871013 | Pass | Pass | 0.2144272523 | 0.5132622617 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.6183929216E-002 | 0.1639768018 | Pass | Pass | 0.1618096700 | 0.3406156198 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.4107602053E-002 | 2.8232902037E-002 | Pass | Pass | 3.1320162131E-002 | 6.2080887991E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.5303743041E-002 | 5.9437922315E-002 | Pass | Pass | 0.1223315822 | 0.3081912569 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5854537966E-002 | 0.1678805242 | Pass | Pass | 0.1537934574 | 0.4691595252 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.6083449816E-002 | 8.5749323215E-002 | Pass | Pass | 0.1226468613 | 0.2811515510 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.2508033208E-002 | 4.4103235975E-002 | Pass | Pass | 0.3539269364 | 1.0666595998 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3966536379E-002 | 0.1985919830 | Pass | Pass | 0.1982049831 | 0.4834207811 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9354463240E-002 | 0.1825121229 | Pass | Pass | 0.1886749727 | 0.5617397607 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.7821446174E-002 | 0.2738229211 | Pass | Pass | 0.2955801905 | 1.1074672945 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1069550367 | 0.2099161847 | Pass | Fail | 0.2706646352 | 1.2902640896 | Pass | Fail |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1062167961 | 0.2264565360 | Pass | Fail | 0.2907276922 | 1.4715178715 | Pass | Fail |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.2002576928 | 0.4016423606 | Fail | Fail | 0.1283145232 | 0.2428825200 | Pass | Fail |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3527945223E-002 | 7.2078153654E-002 | Pass | Pass | 0.2660977458 | 0.6785588465 | Fail | Fail |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3239.64 | 70.91 | 805.57 | 3914.46 | 6114.21 | 14144.80 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.820 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.820 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.820 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.820 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.820 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.820 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.820 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.820 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.820 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.3255 | 1978.83 | 20432.33 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 188.94 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.5625 | 67.07 | 909.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.76 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.5625 | 77.67 | 1053.39 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 10.14 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.5208 | 164.24 | 742.52 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.17 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.7005 | 94.76 | 729.69 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 4.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 11.5174 | 188.86 | 2175.19 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.22 | 0.0000 | Y | 16.42 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.6875 | 1308.19 | 12673.07 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 99.15 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 9.7951 | 1863.81 | 18256.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.45 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 9.7951 | 1864.32 | 18261.31 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 130.49 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 9.7951 | 156.09 | 1528.91 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.93 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 9.7951 | 156.07 | 1528.73 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 10.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.23 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 9.7951 | 39.02 | 382.18 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.73 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 9.7951 | 220.77 | 2162.52 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 15.45 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.99 | 0.0000 | Y | 35.84 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 11.5174 | 331.66 | 3819.82 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.99 | 0.0000 | Y | 35.84 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 13.0243 | 103.30 | 1345.47 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 9.4981 | 11345.29 | 107758.18 | 496.31 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 12673.07 | 887.11 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2175.19 | 848.32 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3819.82 | 763.96 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.77 | 83.77 | 262.44 | |
Exterior Lighting Total | 16690.39 | 262.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 404801.06 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 806087.68 | 2.96 | 806229.37 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11750.58 | 20488.47 | 15514.70 | 4973.77 | 0.76 | - | 3295.97 | 33.43 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11673.89 | 20354.20 | 15412.63 | 4941.57 | 0.76 | - | 3274.23 | 33.21 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 70456.84 | 123649.08 | 93964.20 | 29684.88 | 0.76 | - | 20251.42 | 205.40 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 79839.17 | 137394.94 | 102730.39 | 34664.55 | 0.75 | - | 21657.80 | 219.67 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10373.77 | 18079.34 | 13684.09 | 4395.24 | 0.76 | - | 2906.12 | 29.48 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10297.05 | 17945.13 | 13582.15 | 4362.99 | 0.76 | - | 2884.41 | 29.26 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3116.40 | 5435.01 | 4116.52 | 1318.49 | 0.76 | - | 874.66 | 8.87 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3093.05 | 5394.15 | 4085.47 | 1308.68 | 0.76 | - | 868.05 | 8.80 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14249.30 | 24695.18 | 18590.92 | 6104.26 | 0.75 | - | 3933.43 | 39.90 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 533215.33 | 667011.94 | 415448.39 | 251563.55 | 0.62 | - | 95569.28 | 969.32 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 57348.72 | 51198.70 | 32051.32 | 19147.38 | 0.63 | - | 5018.41 | 50.90 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6564.04 | 6598.35 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3481.75 | 3497.12 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1458.90 | 1466.02 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2047.10 | 2056.24 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1383.86 | 1390.02 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10030.33 | 10082.25 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10179.92 | 10228.37 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26640.50 | 26770.82 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5827.75 | 6278.73 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5821.41 | 6271.91 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33597.29 | 36197.05 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33495.08 | 36086.95 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5815.75 | 6265.81 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5809.41 | 6258.98 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13065.33 | 13125.34 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1788.68 | 1927.05 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1787.91 | 1926.22 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8621.77 | 9288.72 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11472.18 | 11528.91 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11855.52 | 11914.22 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7407.24 | 7445.45 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8301.58 | 8338.20 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 174204.76 | 131198.09 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 14143.00 | 10651.46 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.22 | 854.96 | 703.64 | 1.00 | 1.15 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 849.32 | 703.64 | 1.00 | 1.15 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.37 | 5184.73 | 703.64 | 1.00 | 0.95 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.96 | 5598.12 | 703.64 | 1.00 | 0.94 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 753.79 | 703.64 | 1.00 | 1.18 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.06 | 748.15 | 703.64 | 1.00 | 1.18 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 226.89 | 703.64 | 1.00 | 1.66 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 225.17 | 703.64 | 1.00 | 1.67 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.45 | 1019.33 | 703.64 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 25.27 | 56613.89 | 2240.64 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.028767 | 4696.83 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003541 | 1066.51 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028767 | 3251.78 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 37277.16 | 37277.16 | 18.84 | 3.123 | 3.123 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 24.00 | 24.00 | 0.00915 | 30.82 | 0.00686 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4497.96 | 4497.96 | 67.06 | 0.377 | 0.377 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00899 | 37.99 | 0.00687 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3388.37 | 3388.37 | 43.63 | 0.284 | 0.284 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00931 | 36.06 | 0.00687 | 0.092 | 0.00 |
MECH_FLR_1 | 2816.65 | 2816.65 | 17.15 | 0.236 | 0.236 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 24.00 | 24.00 | 0.00865 | 33.68 | 0.00686 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1867.66 | 1867.66 | 19.71 | 0.156 | 0.156 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00869 | 36.06 | 0.00687 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45064.30 | 45064.30 | 577.46 | 3.775 | 3.775 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00854 | 37.32 | 0.00687 | 0.000 | 0.00 |
CAFE_FLR_1 | 19085.15 | 19085.15 | 101.05 | 1.600 | 1.600 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.01014 | 37.99 | 0.00687 | 0.676 | 0.00 |
LOBBY_FLR_1 | 63706.48 | 63706.48 | 48.70 | 5.339 | 5.339 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00997 | 38.10 | 0.00687 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10763.44 | 10763.44 | 275.83 | 1.215 | 1.215 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00854 | 36.80 | 0.00687 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10692.40 | 10692.40 | 274.04 | 1.207 | 1.207 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00854 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 65275.02 | 65275.02 | 2661.70 | 7.368 | 7.368 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00848 | 38.10 | 0.00687 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 70473.83 | 70473.83 | 2872.90 | 7.956 | 7.956 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 21.11 | 21.11 | 0.00868 | 37.84 | 0.00687 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9489.72 | 9489.72 | 243.19 | 1.071 | 1.071 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00855 | 33.48 | 0.00686 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9418.80 | 9418.80 | 241.40 | 1.063 | 1.063 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00855 | 33.16 | 0.00686 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20957.01 | 20957.01 | 53.82 | 1.756 | 1.756 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00937 | 37.84 | 0.00687 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2856.40 | 2856.40 | 73.20 | 0.322 | 0.322 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00854 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2834.80 | 2834.80 | 72.65 | 0.320 | 0.320 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00854 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12832.28 | 12832.28 | 523.11 | 1.449 | 1.449 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00860 | 38.10 | 0.00687 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30640.05 | 30640.05 | 92.38 | 2.570 | 2.570 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01033 | 38.10 | 0.00687 | 1.188 | 0.00 |
DINING_FLR_6 | 32089.11 | 32089.11 | 96.75 | 2.692 | 2.692 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01024 | 38.10 | 0.00687 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30846.38 | 30846.38 | 298.60 | 2.591 | 2.591 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 36.93 | 0.00687 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10671.94 | 10671.94 | 25.89 | 0.894 | 0.894 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00894 | 38.10 | 0.00687 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.93 | 0.00281 | -5.20 | 0.00281 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2690.33 | 2690.33 | 40.11 | 0.133 | 0.133 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00761 | -5.20 | 0.00281 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 862.71 | 862.71 | 11.11 | 0.043 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00754 | -5.20 | 0.00281 | 0.092 | 0.00 |
MECH_FLR_1 | 1551.74 | 1551.74 | 9.45 | 0.077 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00741 | -5.20 | 0.00281 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1055.35 | 1055.35 | 11.14 | 0.052 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00749 | -5.20 | 0.00281 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2105.07 | 2105.07 | 26.97 | 0.104 | 0.104 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00741 | -5.20 | 0.00281 | 0.000 | 0.00 |
CAFE_FLR_1 | 6818.49 | 6818.49 | 36.10 | 0.337 | 0.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00766 | -5.20 | 0.00281 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15427.22 | 15427.22 | 11.79 | 0.762 | 1.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00758 | -5.20 | 0.00281 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5827.87 | 5827.87 | 149.35 | 0.290 | 0.290 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5821.53 | 5821.53 | 149.20 | 0.289 | 0.289 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33597.61 | 33597.61 | 1370.00 | 1.670 | 1.670 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33495.40 | 33495.40 | 1365.46 | 1.665 | 1.665 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5815.87 | 5815.87 | 149.04 | 0.289 | 0.289 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5809.53 | 5809.53 | 148.90 | 0.289 | 0.289 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9377.38 | 9377.38 | 24.08 | 0.463 | 0.475 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -5.20 | 0.00281 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1788.71 | 1788.71 | 45.84 | 0.089 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1787.94 | 1787.94 | 45.82 | 0.089 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8621.90 | 8621.90 | 351.48 | 0.429 | 0.429 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00768 | -5.20 | 0.00281 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6072.75 | 6072.75 | 18.31 | 0.300 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00775 | -5.20 | 0.00281 | 1.188 | 0.00 |
DINING_FLR_6 | 6200.77 | 6200.77 | 18.70 | 0.306 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1977.34 | 1977.34 | 19.14 | 0.098 | 0.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00671 | -5.20 | 0.00281 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6423.26 | 6423.26 | 15.59 | 0.317 | 0.317 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00779 | -5.20 | 0.00281 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 25.27 | 25.27 | 7.42 | 7.42 | 25.2669 | 11.6560 | 25.2669 | 0.4613 | 0.3000 |
FLR_3_DOAS | 21.48 | 2.05 | 5.10 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6564.039 | 6564.039 | 1.433464 | 0.00005743 | 136.882 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6564.04 | 6564.04 | 1.433464 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 6600.93 | 6600.93 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3481.754 | 3481.754 | 0.172980 | 0.00003046 | 88.529 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3481.75 | 3481.75 | 0.172980 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00761411 | 42.7170 | 2690.33 | 0.00 | 3499.62 | 3499.62 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1458.903 | 1458.903 | 0.130311 | 0.00001276 | 32.906 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1458.90 | 1458.90 | 0.130311 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00754238 | 42.3182 | 862.71 | 0.00 | 1466.78 | 1466.78 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2047.097 | 2047.097 | 0.108299 | 0.00001791 | 51.144 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2047.10 | 2047.10 | 0.108299 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00741484 | 41.6112 | 1551.74 | 0.00 | 2057.65 | 2057.65 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1383.861 | 1383.861 | 0.071811 | 0.00001211 | 34.756 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1383.86 | 1383.86 | 0.071811 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00749500 | 42.0557 | 1055.35 | 0.00 | 1390.98 | 1390.98 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10030.327 | 10030.327 | 1.732861 | 0.00008775 | 212.071 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10030.33 | 10030.33 | 1.732861 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00741154 | 41.5940 | 2105.07 | 0.00 | 10086.43 | 10086.43 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10179.917 | 10179.917 | 0.734620 | 0.00008906 | 237.527 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10179.92 | 10179.92 | 0.734620 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00766020 | 42.9721 | 6818.49 | 0.00 | 10234.27 | 10234.27 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26640.496 | 26640.496 | 2.450793 | 0.00023306 | 598.456 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 26640.50 | 26640.50 | 2.450793 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00757810 | 42.5163 | 15427.22 | 0.00 | 26784.60 | 26784.60 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11750.579 | -999.000 | 1.215062 | 0.00041970 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 11750.58 | 11653.89 | 1.215062 | 21.77 | 14.20 | 0.00854101 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00854101 | 47.5203 | 10763.44 | 0.00 | 13596.80 | 13008.66 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5827.750 | 5827.750 | 0.289709 | 0.00005098 | 166.532 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5827.75 | 5827.75 | 0.289709 | 21.11 | 13.14 | 0.00759083 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00759083 | 42.2985 | 5827.87 | 0.00 | 6282.46 | 6282.46 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11673.885 | -999.000 | 1.207042 | 0.00041696 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 11673.89 | 11577.20 | 1.207042 | 21.77 | 14.20 | 0.00854128 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00854128 | 47.5217 | 10692.40 | 0.00 | 13507.98 | 12922.84 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5821.414 | 5821.414 | 0.289394 | 0.00005093 | 166.351 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5821.41 | 5821.41 | 0.289394 | 21.11 | 13.13 | 0.00759045 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00759045 | 42.2964 | 5821.53 | 0.00 | 6275.63 | 6275.63 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 70456.843 | -999.000 | 7.368486 | 0.00251651 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 70456.84 | 70456.84 | 7.368486 | 21.77 | 14.14 | 0.00847553 | 12.80 | 10.79 | 0.00847553 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00847553 | 47.1600 | 65275.02 | 0.00 | 81631.47 | 79125.60 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 33597.291 | 33597.291 | 1.670216 | 0.00029392 | 960.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 33597.29 | 33597.29 | 1.670216 | 21.11 | 13.16 | 0.00762134 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00762134 | 42.4656 | 33597.61 | 0.00 | 36218.91 | 36218.91 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 79839.166 | -999.000 | 7.955988 | 0.00285162 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | 7/21 15:20:00 | 79839.17 | 77056.26 | 7.955988 | 21.77 | 14.31 | 0.00867849 | 12.80 | 10.82 | 0.00850000 | 37.84 | 0.00687107 | 18.09 | 0.0000 | 21.11 | 0.00867849 | 48.2757 | 70473.83 | 0.00 | 92156.10 | 85354.12 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33495.079 | 33495.079 | 1.665134 | 0.00029303 | 957.131 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 33495.08 | 33495.08 | 1.665134 | 21.11 | 13.16 | 0.00762017 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00762017 | 42.4591 | 33495.40 | 0.00 | 36108.72 | 36108.72 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10373.767 | -999.000 | 1.071274 | 0.00037052 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 10373.77 | 10278.45 | 1.071274 | 21.77 | 14.20 | 0.00854584 | 12.80 | 10.82 | 0.00850000 | 33.48 | 0.00686412 | 16.74 | 0.0000 | 21.11 | 0.00854584 | 47.5468 | 9489.72 | 0.00 | 12002.50 | 11470.01 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5815.750 | 5815.750 | 0.289112 | 0.00005088 | 166.189 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5815.75 | 5815.75 | 0.289112 | 21.11 | 13.13 | 0.00759006 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00759006 | 42.2942 | 5815.87 | 0.00 | 6269.52 | 6269.52 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10297.049 | -999.000 | 1.063268 | 0.00036778 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 10297.05 | 10201.85 | 1.063268 | 21.77 | 14.20 | 0.00854612 | 12.80 | 10.82 | 0.00850000 | 33.16 | 0.00686360 | 16.64 | 0.0000 | 21.11 | 0.00854612 | 47.5483 | 9418.80 | 0.00 | 11913.67 | 11384.33 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5809.412 | 5809.412 | 0.288797 | 0.00005082 | 166.008 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5809.41 | 5809.41 | 0.288797 | 21.11 | 13.13 | 0.00758967 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00758967 | 42.2921 | 5809.53 | 0.00 | 6262.69 | 6262.69 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13065.331 | 13065.331 | 0.805862 | 0.00011430 | 314.496 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13065.33 | 13065.33 | 0.805862 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00768456 | 43.1060 | 9377.38 | 0.00 | 13133.57 | 13133.57 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3116.397 | -999.000 | 0.322453 | 0.00011131 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3116.40 | 3092.19 | 0.322453 | 21.77 | 14.19 | 0.00853870 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00853870 | 47.5076 | 2856.40 | 0.00 | 3606.20 | 3452.13 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1788.681 | 1788.681 | 0.088919 | 0.00001565 | 51.111 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1788.68 | 1788.68 | 0.088919 | 21.11 | 13.20 | 0.00766171 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00766171 | 42.6886 | 1788.71 | 0.00 | 1928.24 | 1928.24 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3093.046 | -999.000 | 0.320015 | 0.00011047 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3093.05 | 3068.86 | 0.320015 | 21.77 | 14.19 | 0.00853896 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00853896 | 47.5090 | 2834.80 | 0.00 | 3579.16 | 3426.03 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1787.906 | 1787.906 | 0.088880 | 0.00001564 | 51.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1787.91 | 1787.91 | 0.088880 | 21.11 | 13.20 | 0.00766160 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00766160 | 42.6880 | 1787.94 | 0.00 | 1927.41 | 1927.41 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14249.299 | -999.000 | 1.448655 | 0.00050894 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 14249.30 | 13957.07 | 1.448655 | 21.77 | 14.25 | 0.00860348 | 12.80 | 10.82 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00860348 | 47.8639 | 12832.28 | 0.00 | 16467.74 | 15522.63 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8621.769 | 8621.769 | 0.428607 | 0.00007543 | 246.361 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8621.77 | 8621.77 | 0.428607 | 21.11 | 13.21 | 0.00767589 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00767589 | 42.7663 | 8621.90 | 0.00 | 9294.50 | 9294.50 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11472.183 | 11472.183 | 1.179742 | 0.00010036 | 254.108 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11472.18 | 11472.18 | 1.179742 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775077 | 43.4732 | 6072.75 | 0.00 | 11534.58 | 11534.58 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11855.518 | 11855.518 | 1.235515 | 0.00010372 | 262.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11855.52 | 11855.52 | 1.235515 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775567 | 43.5003 | 6200.77 | 0.00 | 11920.04 | 11920.04 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7407.242 | 7407.242 | 1.189392 | 0.00006480 | 157.408 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7407.24 | 7407.24 | 1.189392 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00670760 | 37.6907 | 1977.34 | 0.00 | 7448.60 | 7448.60 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8301.584 | 8301.584 | 0.410365 | 0.00007263 | 211.393 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 8301.58 | 8301.58 | 0.410365 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00779182 | 43.7004 | 6423.26 | 0.00 | 8344.16 | 8344.16 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 533215.330 | -999.000 | 25.266857 | 0.01904522 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 533215.33 | 533215.32 | 25.266857 | 30.50 | 16.94 | 0.00835102 | 10.70 | 9.82 | 0.00835102 | 38.10 | 0.00687148 | 18.17 | 46.1532 | 23.99 | 0.00957742 | 44.6572 | 301390.22 | 0.00 | 589433.38 | 544375.78 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 174204.756 | 174204.756 | 7.580057 | 0.00152402 | 2957.306 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 174204.76 | 174204.76 | 7.580057 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 153.8440 | 21.34 | 0.00682274 | 37.5307 | 60279.07 | 0.00 | 158645.66 | 158645.66 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 57348.72 | 57348.72 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 11.79 | 8.78 | 0.00687148 | 38.10 | 0.00687148 | 18.17 | 99.9965 | 21.11 | 0.00858103 | 47.7401 | 190095.33 | 0.00 | 51614.51 | 51614.51 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14143.00 | 14143.00 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 333.3216 | 21.11 | 0.00762106 | 42.4640 | 102566.35 | 0.00 | 12879.82 | 12879.82 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6564.039 | 6564.039 | 1.433464 | 0.00005743 | 136.882 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 1.5896 | 1.621547 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6564.04 | 6564.04 | 1.0000 | 1.49701209 | 1.433464 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05741921 | 60.00 | 32.22 | 27.78 | 0.000 | 6564.04 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 6600.93 | 6600.93 | 1.49701209 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3481.754 | 3481.754 | 0.172980 | 0.00003046 | 88.529 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 0.8431 | 0.860115 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 3481.75 | 3481.75 | 1.0000 | 0.18064799 | 0.172980 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.03045679 | 60.00 | 32.22 | 27.78 | 0.000 | 3481.75 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00761411 | 21.00 | 0.00761411 | 42.7170 | 2690.33 | 0.00 | 3499.62 | 3499.62 | 0.18064799 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.60 | 19.84 | 0.00800000 | 56307.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1458.903 | 1458.903 | 0.130311 | 0.00001276 | 32.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 0.3533 | 0.360400 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1458.90 | 1458.90 | 1.0000 | 0.13608843 | 0.130311 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01276182 | 60.00 | 32.22 | 27.78 | 0.000 | 1458.90 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00754238 | 21.00 | 0.00754238 | 42.3182 | 862.71 | 0.00 | 1466.78 | 1466.78 | 0.13608843 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.17 | 17.08 | 0.00800000 | 47712.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2047.097 | 2047.097 | 0.108299 | 0.00001791 | 51.144 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 0.4957 | 0.505704 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2047.10 | 2047.10 | 1.0000 | 0.11310031 | 0.108299 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01790707 | 60.00 | 32.22 | 27.78 | 0.000 | 2047.10 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00741484 | 21.00 | 0.00741484 | 41.6112 | 1551.74 | 0.00 | 2057.65 | 2057.65 | 0.11310031 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.44 | 19.48 | 0.00800000 | 55127.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1383.861 | 1383.861 | 0.071811 | 0.00001211 | 34.756 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 0.3351 | 0.341862 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1383.86 | 1383.86 | 1.0000 | 0.07499496 | 0.071811 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01210538 | 60.00 | 32.22 | 27.78 | 0.000 | 1383.86 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00749500 | 21.00 | 0.00749500 | 42.0557 | 1055.35 | 0.00 | 1390.98 | 1390.98 | 0.07499496 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.79 | 19.59 | 0.00800000 | 55482.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10030.327 | 10030.327 | 1.732861 | 0.00008775 | 212.071 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 2.4290 | 2.477841 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 10030.33 | 10030.33 | 1.0000 | 1.80968219 | 1.732861 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08774073 | 60.00 | 32.22 | 27.78 | 0.000 | 10030.33 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00741154 | 21.00 | 0.00741154 | 41.5940 | 2105.07 | 0.00 | 10086.43 | 10086.43 | 1.80968219 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.07 | 15.25 | 0.00800000 | 42508.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10179.917 | 10179.917 | 0.734620 | 0.00008906 | 237.527 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 2.4652 | 2.514795 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 10179.92 | 10179.92 | 1.0000 | 0.76718654 | 0.734620 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08904927 | 60.00 | 32.22 | 27.78 | 0.000 | 10179.92 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766020 | 21.00 | 0.00766020 | 42.9721 | 6818.49 | 0.00 | 10234.27 | 10234.27 | 0.76718654 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.68 | 17.93 | 0.00800000 | 50274.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26640.496 | 26640.496 | 2.450793 | 0.00023306 | 598.456 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 6.4513 | 6.581133 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 26640.50 | 26640.50 | 1.0000 | 2.55944080 | 2.450793 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.23303891 | 60.00 | 32.22 | 27.78 | 0.000 | 26640.50 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00757810 | 21.00 | 0.00757810 | 42.5163 | 15427.22 | 0.00 | 26784.60 | 26784.60 | 2.55944080 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.86 | 16.97 | 0.00800000 | 47399.8 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11750.579 | -999.000 | 1.215062 | 0.00041970 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7173 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.215062 | 1.26892808 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 1.4590 | 1.458929 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 11750.58 | 11653.89 | 1.0000 | 1.26892808 | 1.215062 | 21.77 | 14.20 | 0.00854101 | 43582.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.41965279 | 6.70 | 13.37 | 6.67 | 0.000 | 11750.58 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00854101 | 21.11 | 0.00854101 | 47.5203 | 10763.44 | 0.00 | 13596.80 | 13008.66 | 1.26892808 | 21.77 | 15.62 | 0.00854101 | 43582.4 | 11.73 | 11.51 | 0.00835728 | 32867.3 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5827.750 | 5827.750 | 0.289709 | 0.00005098 | 166.532 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.215062 | 1.26892808 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 1.4113 | 1.439658 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5827.75 | 5827.75 | 1.0000 | 0.30255189 | 0.289709 | 21.11 | 13.14 | 0.00759083 | 40494.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05097850 | 60.00 | 32.22 | 27.78 | 0.000 | 5827.75 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00759083 | 21.11 | 0.00759083 | 42.2985 | 5827.87 | 0.00 | 6282.46 | 6282.46 | 0.30255189 | 16.60 | 12.75 | 0.00759083 | 35898.8 | 36.98 | 19.96 | 0.00759083 | 56663.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11673.885 | -999.000 | 1.207042 | 0.00041696 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7178 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.207042 | 1.26055237 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 1.4494 | 1.449407 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 11673.89 | 11577.20 | 1.0000 | 1.26055237 | 1.207042 | 21.77 | 14.20 | 0.00854128 | 43583.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.41691381 | 6.70 | 13.37 | 6.67 | 0.000 | 11673.89 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00854128 | 21.11 | 0.00854128 | 47.5217 | 10692.40 | 0.00 | 13507.98 | 12922.84 | 1.26055237 | 21.77 | 15.62 | 0.00854128 | 43583.1 | 11.73 | 11.51 | 0.00835727 | 32867.2 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5821.414 | 5821.414 | 0.289394 | 0.00005093 | 166.351 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.207042 | 1.26055237 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 1.4097 | 1.438092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5821.41 | 5821.41 | 1.0000 | 0.30222291 | 0.289394 | 21.11 | 13.13 | 0.00759045 | 40493.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05092307 | 60.00 | 32.22 | 27.78 | 0.000 | 5821.41 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00759045 | 21.11 | 0.00759045 | 42.2964 | 5821.53 | 0.00 | 6275.63 | 6275.63 | 0.30222291 | 16.60 | 12.75 | 0.00759045 | 35897.8 | 36.98 | 19.96 | 0.00759045 | 56662.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70456.843 | -999.000 | 7.368486 | 0.00251651 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5956 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.368486 | 7.69514388 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 8.7479 | 8.747783 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 70456.84 | 70456.84 | 1.0000 | 7.69514388 | 7.368486 | 21.77 | 14.14 | 0.00847553 | 43416.4 | 12.80 | 10.79 | 0.00847553 | 34260.4 | 2.51625147 | 6.70 | 13.37 | 6.67 | 0.000 | 70456.84 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00847553 | 21.11 | 0.00847553 | 47.1600 | 65275.02 | 0.00 | 81631.47 | 79125.60 | 7.69514388 | 21.77 | 15.56 | 0.00847553 | 43416.4 | 11.70 | 11.48 | 0.00834644 | 32808.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33597.291 | 33597.291 | 1.670216 | 0.00029392 | 960.051 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.368486 | 7.69514388 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 8.1360 | 8.299704 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 33597.29 | 33597.29 | 1.0000 | 1.74425928 | 1.670216 | 21.11 | 13.16 | 0.00762134 | 40572.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.29389378 | 60.00 | 32.22 | 27.78 | 0.000 | 33597.29 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00762134 | 21.11 | 0.00762134 | 42.4656 | 33597.61 | 0.00 | 36218.91 | 36218.91 | 1.74425928 | 16.60 | 12.78 | 0.00762134 | 35976.0 | 36.98 | 19.99 | 0.00762134 | 56740.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 79839.166 | -999.000 | 7.955988 | 0.00285162 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9729 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.955988 | 8.30869041 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 9.9129 | 9.912674 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | unknown | unknown | 7/21 15:20:00 | Sensible | 79839.17 | 77056.26 | 1.0000 | 8.30869041 | 7.955988 | 21.77 | 14.31 | 0.00867849 | 43931.3 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 2.85132589 | 6.70 | 13.37 | 6.67 | 0.000 | 79839.17 | 37.84 | 0.00687107 | 18.09 | 0.00000000 | 0.0000 | 21.11 | 0.00867849 | 21.11 | 0.00867849 | 48.2757 | 70473.83 | 0.00 | 92156.10 | 85354.12 | 8.30869041 | 21.77 | 15.74 | 0.00867849 | 43931.3 | 11.71 | 11.50 | 0.00835398 | 32839.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33495.079 | 33495.079 | 1.665134 | 0.00029303 | 957.131 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.955988 | 8.30869041 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 8.1112 | 8.274454 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 33495.08 | 33495.08 | 1.0000 | 1.73895277 | 1.665134 | 21.11 | 13.16 | 0.00762017 | 40569.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.29299967 | 60.00 | 32.22 | 27.78 | 0.000 | 33495.08 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00762017 | 21.11 | 0.00762017 | 42.4591 | 33495.40 | 0.00 | 36108.72 | 36108.72 | 1.73895277 | 16.60 | 12.78 | 0.00762017 | 35973.1 | 36.98 | 19.99 | 0.00762017 | 56737.7 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10373.767 | -999.000 | 1.071274 | 0.00037052 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7263 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.071274 | 1.11876586 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 1.2880 | 1.287987 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 10373.77 | 10278.45 | 1.0000 | 1.11876586 | 1.071274 | 21.77 | 14.20 | 0.00854584 | 43594.7 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.37048221 | 6.70 | 13.37 | 6.67 | 0.000 | 10373.77 | 33.48 | 0.00686412 | 16.74 | 0.00000000 | 0.0000 | 21.11 | 0.00854584 | 21.11 | 0.00854584 | 47.5468 | 9489.72 | 0.00 | 12002.50 | 11470.01 | 1.11876586 | 21.77 | 15.63 | 0.00854584 | 43594.7 | 11.73 | 11.51 | 0.00835716 | 32866.4 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5815.750 | 5815.750 | 0.289112 | 0.00005088 | 166.189 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.071274 | 1.11876586 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 1.4083 | 1.436693 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5815.75 | 5815.75 | 1.0000 | 0.30192890 | 0.289112 | 21.11 | 13.13 | 0.00759006 | 40492.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05087353 | 60.00 | 32.22 | 27.78 | 0.000 | 5815.75 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00759006 | 21.11 | 0.00759006 | 42.2942 | 5815.87 | 0.00 | 6269.52 | 6269.52 | 0.30192890 | 16.60 | 12.75 | 0.00759006 | 35896.8 | 36.98 | 19.96 | 0.00759006 | 56661.7 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10297.049 | -999.000 | 1.063268 | 0.00036778 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7268 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.063268 | 1.11040493 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 1.2785 | 1.278461 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 10297.05 | 10201.85 | 1.0000 | 1.11040493 | 1.063268 | 21.77 | 14.20 | 0.00854612 | 43595.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.36774234 | 6.70 | 13.37 | 6.67 | 0.000 | 10297.05 | 33.16 | 0.00686360 | 16.64 | 0.00000000 | 0.0000 | 21.11 | 0.00854612 | 21.11 | 0.00854612 | 47.5483 | 9418.80 | 0.00 | 11913.67 | 11384.33 | 1.11040493 | 21.77 | 15.63 | 0.00854612 | 43595.4 | 11.73 | 11.51 | 0.00835716 | 32866.3 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5809.412 | 5809.412 | 0.288797 | 0.00005082 | 166.008 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.063268 | 1.11040493 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 1.4068 | 1.435128 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5809.41 | 5809.41 | 1.0000 | 0.30159982 | 0.288797 | 21.11 | 13.13 | 0.00758967 | 40491.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05081808 | 60.00 | 32.22 | 27.78 | 0.000 | 5809.41 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758967 | 21.11 | 0.00758967 | 42.2921 | 5809.53 | 0.00 | 6262.69 | 6262.69 | 0.30159982 | 16.60 | 12.75 | 0.00758967 | 35895.9 | 36.98 | 19.96 | 0.00758967 | 56660.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13065.331 | 13065.331 | 0.805862 | 0.00011430 | 314.496 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 3.1639 | 3.227593 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13065.33 | 13065.33 | 1.0000 | 0.84158681 | 0.805862 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.11428956 | 60.00 | 32.22 | 27.78 | 0.000 | 13065.33 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00768456 | 21.00 | 0.00768456 | 43.1060 | 9377.38 | 0.00 | 13133.57 | 13133.57 | 0.84158681 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.90 | 18.67 | 0.00800000 | 52540.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3116.397 | -999.000 | 0.322453 | 0.00011131 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7130 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.322453 | 0.33674837 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 0.3869 | 0.386926 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3116.40 | 3092.19 | 1.0000 | 0.33674837 | 0.322453 | 21.77 | 14.19 | 0.00853870 | 43576.6 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.11129703 | 6.70 | 13.37 | 6.67 | 0.000 | 3116.40 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00853870 | 21.11 | 0.00853870 | 47.5076 | 2856.40 | 0.00 | 3606.20 | 3452.13 | 0.33674837 | 21.77 | 15.62 | 0.00853870 | 43576.6 | 11.73 | 11.51 | 0.00835733 | 32867.7 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1788.681 | 1788.681 | 0.088919 | 0.00001565 | 51.111 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.322453 | 0.33674837 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 0.4331 | 0.441867 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1788.68 | 1788.68 | 1.0000 | 0.09286068 | 0.088919 | 21.11 | 13.20 | 0.00766171 | 40674.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01564656 | 60.00 | 32.22 | 27.78 | 0.000 | 1788.68 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00766171 | 21.11 | 0.00766171 | 42.6886 | 1788.71 | 0.00 | 1928.24 | 1928.24 | 0.09286068 | 16.60 | 12.82 | 0.00766171 | 36078.2 | 36.98 | 20.02 | 0.00766171 | 56843.1 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3093.046 | -999.000 | 0.320015 | 0.00011047 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7135 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.320015 | 0.33420150 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 0.3840 | 0.384027 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3093.05 | 3068.86 | 1.0000 | 0.33420150 | 0.320015 | 21.77 | 14.19 | 0.00853896 | 43577.2 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.11046311 | 6.70 | 13.37 | 6.67 | 0.000 | 3093.05 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00853896 | 21.11 | 0.00853896 | 47.5090 | 2834.80 | 0.00 | 3579.16 | 3426.03 | 0.33420150 | 21.77 | 15.62 | 0.00853896 | 43577.2 | 11.73 | 11.51 | 0.00835733 | 32867.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1787.906 | 1787.906 | 0.088880 | 0.00001564 | 51.088 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.320015 | 0.33420150 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 0.4330 | 0.441675 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1787.91 | 1787.91 | 1.0000 | 0.09282045 | 0.088880 | 21.11 | 13.20 | 0.00766160 | 40674.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01563978 | 60.00 | 32.22 | 27.78 | 0.000 | 1787.91 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00766160 | 21.11 | 0.00766160 | 42.6880 | 1787.94 | 0.00 | 1927.41 | 1927.41 | 0.09282045 | 16.60 | 12.82 | 0.00766160 | 36078.0 | 36.98 | 20.02 | 0.00766160 | 56842.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14249.299 | -999.000 | 1.448655 | 0.00050894 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8334 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.448655 | 1.51287618 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 1.7692 | 1.769165 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 14249.30 | 13957.07 | 1.0000 | 1.51287618 | 1.448655 | 21.77 | 14.25 | 0.00860348 | 43740.9 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.50889053 | 6.70 | 13.37 | 6.67 | 0.000 | 14249.30 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00860348 | 21.11 | 0.00860348 | 47.8639 | 12832.28 | 0.00 | 16467.74 | 15522.63 | 1.51287618 | 21.77 | 15.68 | 0.00860348 | 43740.9 | 11.72 | 11.50 | 0.00835585 | 32855.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8621.769 | 8621.769 | 0.428607 | 0.00007543 | 246.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.448655 | 1.51287618 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 2.0879 | 2.129878 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8621.77 | 8621.77 | 1.0000 | 0.44760839 | 0.428607 | 21.11 | 13.21 | 0.00767589 | 40710.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07541930 | 60.00 | 32.22 | 27.78 | 0.000 | 8621.77 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00767589 | 21.11 | 0.00767589 | 42.7663 | 8621.90 | 0.00 | 9294.50 | 9294.50 | 0.44760839 | 16.60 | 12.83 | 0.00767589 | 36114.1 | 36.98 | 20.03 | 0.00767589 | 56878.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11472.183 | 11472.183 | 1.179742 | 0.00010036 | 254.108 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 2.7781 | 2.834030 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11472.18 | 11472.18 | 1.0000 | 1.23204224 | 1.179742 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10035343 | 60.00 | 32.22 | 27.78 | 0.000 | 11472.18 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775077 | 21.00 | 0.00775077 | 43.4732 | 6072.75 | 0.00 | 11534.58 | 11534.58 | 1.23204224 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.78 | 16.59 | 0.00800000 | 46296.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11855.518 | 11855.518 | 1.235515 | 0.00010372 | 262.188 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 2.8709 | 2.928727 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11855.52 | 11855.52 | 1.0000 | 1.29028774 | 1.235515 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10370666 | 60.00 | 32.22 | 27.78 | 0.000 | 11855.52 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775567 | 21.00 | 0.00775567 | 43.5003 | 6200.77 | 0.00 | 11920.04 | 11920.04 | 1.29028774 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.66 | 16.55 | 0.00800000 | 46173.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7407.242 | 7407.242 | 1.189392 | 0.00006480 | 157.408 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 1.7937 | 1.829848 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7407.24 | 7407.24 | 1.0000 | 1.24211986 | 1.189392 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06479518 | 60.00 | 32.22 | 27.78 | 0.000 | 7407.24 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.48 | 0.00670760 | 21.00 | 0.00670760 | 37.6907 | 1977.34 | 0.00 | 7448.60 | 7448.60 | 1.24211986 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.48 | 15.40 | 0.00800000 | 42931.4 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8301.584 | 8301.584 | 0.410365 | 0.00007263 | 211.393 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 2.0103 | 2.050781 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 8301.58 | 8301.58 | 1.0000 | 0.42855686 | 0.410365 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07261847 | 60.00 | 32.22 | 27.78 | 0.000 | 8301.58 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00779182 | 21.00 | 0.00779182 | 43.7004 | 6423.26 | 0.00 | 8344.16 | 8344.16 | 0.42855686 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.69 | 19.87 | 0.00800000 | 56405.1 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 533215.330 | -999.000 | 25.266857 | 0.01904522 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3641 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 25.266857 | 26.38698007 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 66.2042 | 66.204204 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 533215.33 | 533215.32 | 1.0000 | 26.38698007 | 25.266857 | 30.50 | 16.94 | 0.00835102 | 52008.1 | 10.70 | 9.82 | 0.00835102 | 31800.5 | 19.04327330 | 6.70 | 13.37 | 6.67 | 56613.894 | 476601.44 | 38.10 | 0.00687148 | 18.17 | 11.66146000 | 46.1532 | 23.99 | 0.00961918 | 23.99 | 0.00957742 | 44.6572 | 301390.22 | 0.00 | 589433.38 | 544375.78 | 26.38698007 | 30.50 | 18.49 | 0.00835102 | 52008.1 | 10.28 | 10.17 | 0.00767343 | 29670.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 174204.756 | 174204.756 | 7.580057 | 0.00152402 | 2957.306 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 25.266857 | 26.38698007 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 42.1857 | 43.034659 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 174204.76 | 174204.76 | 1.0000 | 7.91609402 | 7.580057 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 1.52386374 | 60.00 | 32.22 | 27.78 | 0.000 | 174204.76 | -5.20 | 0.00280840 | -5.20 | 11.66146000 | 153.8440 | 18.56 | 0.00706310 | 21.34 | 0.00682274 | 37.5307 | 60279.07 | 0.00 | 158645.66 | 158645.66 | 7.91609402 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6137 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 28.76444703 | 13.37 | 6.70 | 6.67 | 805410.07 | 7.1204 | 7.120438 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 57348.72 | 57348.72 | 1.0000 | 2.14225568 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 55956.2 | 11.79 | 8.78 | 0.00687148 | 29186.0 | 2.04815455 | 6.70 | 13.37 | 6.67 | 2195.006 | 55153.72 | 38.10 | 0.00687148 | 18.17 | 2.05124512 | 99.9965 | 21.11 | 0.00857518 | 21.11 | 0.00858103 | 47.7401 | 190095.33 | 0.00 | 51614.51 | 51614.51 | 2.14225568 | 38.10 | 19.77 | 0.00687148 | 55956.2 | 14.42 | 11.12 | 0.00687148 | 31862.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 3.54101503 | 54.44 | 82.22 | 27.78 | 412947.85 | 3.4249 | 3.493816 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14143.00 | 14143.00 | 1.0000 | 0.64267671 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 0.12371654 | 60.00 | 32.22 | 27.78 | 0.000 | 14143.00 | -5.20 | 0.00280840 | -5.20 | 2.05124512 | 333.3216 | 21.11 | 0.00761990 | 21.11 | 0.00762106 | 42.4640 | 102566.35 | 0.00 | 12879.82 | 12879.82 | 0.64267671 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 25.27 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2036.17 | 6149.00 | 916.17 |
RETAIL_1_FLR_1 | 3269.50 | 5391.17 | 987.00 |
RETAIL_2_FLR_1 | 2865.00 | 5678.83 | 1085.50 |
MECH_FLR_1 | 2063.17 | 6308.33 | 593.33 |
STORAGE_FLR_1 | 1781.17 | 6639.00 | 681.17 |
LAUNDRY_FLR_1 | 8077.67 | 3975.33 | 3730.83 |
CAFE_FLR_1 | 4477.67 | 4519.50 | 1871.67 |
LOBBY_FLR_1 | 3464.50 | 5257.67 | 1726.67 |
ROOM_1_FLR_3 | 1132.50 | 7742.33 | 832.50 |
ROOM_2_FLR_3 | 1860.67 | 7967.83 | 1658.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1250.67 | 8751.00 | 1250.67 |
ROOM_5_FLR_3 | 1135.83 | 7602.67 | 836.50 |
ROOM_6_FLR_3 | 1898.83 | 7777.33 | 1660.17 |
CORRIDOR_FLR_3 | 2090.67 | 7166.50 | 1309.83 |
ROOM_1_FLR_6 | 1927.67 | 7680.50 | 1508.67 |
ROOM_2_FLR_6 | 2723.33 | 7903.17 | 2434.17 |
ROOM_3_MULT9_FLR_6 | 658.17 | 7835.17 | 464.50 |
BANQUET_FLR_6 | 4478.00 | 3273.83 | 1789.00 |
DINING_FLR_6 | 4977.33 | 2211.50 | 1680.17 |
KITCHEN_FLR_6 | 8568.17 | 6732.67 | 6728.50 |
CORRIDOR_FLR_6 | 2522.17 | 6267.17 | 857.67 |
Facility | 8758.83 | 8760.00 | 7844.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 158.83 | 0.00 | 158.83 |
CAFE_FLR_1 | 0.00 | 0.83 | 0.00 | 0.83 |
LOBBY_FLR_1 | 0.00 | 0.67 | 0.00 | 0.67 |
ROOM_1_FLR_3 | 0.00 | 4.33 | 0.00 | 4.33 |
ROOM_2_FLR_3 | 0.00 | 2.83 | 0.00 | 2.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 1.50 | 0.00 | 1.50 |
ROOM_5_FLR_3 | 0.00 | 28.17 | 0.00 | 28.17 |
ROOM_6_FLR_3 | 0.00 | 27.00 | 0.00 | 27.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 6.67 | 0.00 | 6.67 |
ROOM_2_FLR_6 | 0.00 | 4.33 | 0.00 | 4.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 11.33 | 0.00 | 11.33 |
BANQUET_FLR_6 | 0.00 | 17.33 | 0.00 | 17.33 |
DINING_FLR_6 | 0.00 | 21.50 | 0.00 | 21.50 |
KITCHEN_FLR_6 | 0.00 | 224.50 | 0.00 | 224.50 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 289.83 | 0.00 | 289.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 1.067 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.270 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.482 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.559 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.624 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 22.349 | 0.145 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 3.646 | 0.107 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.736 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.059 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.175 | 0.000 | 0.059 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.077 | 0.000 | 0.089 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.058 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.175 | 0.000 | 0.057 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.554 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.067 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.175 | 0.000 | 0.068 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.142 | 0.000 | 0.108 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.032 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.425 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 22.265 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 1.098 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.539 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.153 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.760 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.295 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.338 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 10.558 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 1.825 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 0.914 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.460 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.523 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.460 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.300 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.524 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.133 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.234 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 6.920 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.577 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 44306378.35 | 0.00 | 44306378.35 | 0.00 | 44306378.35 | 26946214.98 | 46.11 | 18.70 | 8695.19 | 0.00 |
RETAIL_1_FLR_1 | 5200263.98 | 0.00 | 5200263.98 | 309826.10 | 5510090.08 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3921708.67 | 0.00 | 3921708.67 | 119593.27 | 4041301.94 | 2892943.94 | 116.06 | 49.68 | 8594.26 | 0.00 |
MECH_FLR_1 | 3138510.64 | 0.00 | 3138510.64 | 282647.43 | 3421158.08 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2021618.70 | 0.00 | 2021618.70 | 163072.00 | 2184690.70 | 1821682.01 | 1549.36 | 280.88 | 6929.76 | 0.00 |
LAUNDRY_FLR_1 | 59475832.86 | 0.00 | 59475832.86 | 385940.64 | 59861773.49 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23411531.41 | 0.00 | 23411531.41 | 684888.14 | 24096419.55 | 21330615.53 | 3143.35 | 452.30 | 5164.35 | 0.00 |
LOBBY_FLR_1 | 77198117.75 | 0.00 | 77198117.75 | 1956881.84 | 79154999.60 | 59728886.00 | 217.00 | 52.46 | 8490.54 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 60126.83 | 2007002.45 | 179831.92 | 2186834.37 | 1946875.62 | 0.00 | 7881.80 | 878.20 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 59978.79 | 2006626.30 | 179818.20 | 2186444.51 | 1946647.51 | 0.00 | 7866.42 | 893.58 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 61131.41 | 26459018.68 | 50175.12 | 26509193.81 | 26397887.27 | 0.00 | 7930.08 | 829.92 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 57309.84 | 26462415.57 | 50188.84 | 26512604.41 | 26405105.73 | 0.00 | 7941.65 | 818.35 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 59813.94 | 2006689.56 | 179831.92 | 2186521.48 | 1946875.62 | 0.00 | 7899.17 | 860.83 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 58254.53 | 2004902.04 | 179818.20 | 2184720.24 | 1946647.51 | 0.00 | 7901.46 | 858.54 | 0.00 |
CORRIDOR_FLR_3 | 22688293.55 | 0.00 | 22688293.55 | 217452.98 | 22905746.53 | 14972100.18 | 20.12 | 26.94 | 8712.95 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 68539.64 | 555258.54 | 179868.73 | 735127.27 | 486718.90 | 0.00 | 7893.52 | 866.48 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 69467.60 | 556129.47 | 179855.01 | 735984.48 | 486661.88 | 0.00 | 7866.50 | 893.50 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 69643.69 | 3196564.10 | 92027.14 | 3288591.24 | 3126920.42 | 0.00 | 7876.79 | 883.21 | 0.00 |
BANQUET_FLR_6 | 43594391.24 | 0.00 | 43594391.24 | 439194.23 | 44033585.47 | 37458366.31 | 2143.10 | 949.75 | 5667.15 | 0.00 |
DINING_FLR_6 | 47002171.22 | 0.00 | 47002171.22 | 439194.23 | 47441365.46 | 37458366.31 | 1041.17 | 186.81 | 7532.02 | 0.00 |
KITCHEN_FLR_6 | 60139838.03 | 0.00 | 60139838.03 | 393180.66 | 60533018.69 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11896248.43 | 0.00 | 11896248.43 | 384823.29 | 12281071.72 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 10719031.98 | 0.46E+10 | 18121884.23 | 0.46E+10 | 0.43E+10 | 4455.75 | 8072.14 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4049 | 0.0000 | 1.4049 | 0.0000 | 1.4049 | 0.8545 | 46.11 | 18.70 | 8695.19 |
RETAIL_1_FLR_1 | 0.1649 | 0.0000 | 0.1649 | 0.0098 | 0.1747 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1244 | 0.0000 | 0.1244 | 0.0038 | 0.1281 | 0.0917 | 116.06 | 49.68 | 8594.26 |
MECH_FLR_1 | 0.0995 | 0.0000 | 0.0995 | 0.0090 | 0.1085 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0641 | 0.0000 | 0.0641 | 0.0052 | 0.0693 | 0.0578 | 1549.36 | 280.88 | 6929.76 |
LAUNDRY_FLR_1 | 1.8860 | 0.0000 | 1.8860 | 0.0122 | 1.8982 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7424 | 0.0000 | 0.7424 | 0.0217 | 0.7641 | 0.6764 | 3143.35 | 452.30 | 5164.35 |
LOBBY_FLR_1 | 2.4479 | 0.0000 | 2.4479 | 0.0621 | 2.5100 | 1.8940 | 217.00 | 52.46 | 8490.54 |
ROOM_1_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0057 | 0.0693 | 0.0617 | 0.00 | 7881.80 | 878.20 |
ROOM_2_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0057 | 0.0693 | 0.0617 | 0.00 | 7866.42 | 893.58 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0018 | 0.8391 | 0.0016 | 0.8407 | 0.8373 | 0.00 | 7941.65 | 818.35 |
ROOM_5_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0057 | 0.0693 | 0.0617 | 0.00 | 7899.17 | 860.83 |
ROOM_6_FLR_3 | 0.0617 | 0.0018 | 0.0636 | 0.0057 | 0.0693 | 0.0617 | 0.00 | 7901.46 | 858.54 |
CORRIDOR_FLR_3 | 0.7194 | 0.0000 | 0.7194 | 0.0069 | 0.7263 | 0.4748 | 20.12 | 26.94 | 8712.95 |
ROOM_1_FLR_6 | 0.0154 | 0.0022 | 0.0176 | 0.0057 | 0.0233 | 0.0154 | 0.00 | 7893.52 | 866.48 |
ROOM_2_FLR_6 | 0.0154 | 0.0022 | 0.0176 | 0.0057 | 0.0233 | 0.0154 | 0.00 | 7866.50 | 893.50 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0022 | 0.1014 | 0.0029 | 0.1043 | 0.0992 | 0.00 | 7876.79 | 883.21 |
BANQUET_FLR_6 | 1.3824 | 0.0000 | 1.3824 | 0.0139 | 1.3963 | 1.1878 | 2143.10 | 949.75 | 5667.15 |
DINING_FLR_6 | 1.4904 | 0.0000 | 1.4904 | 0.0139 | 1.5044 | 1.1878 | 1041.17 | 186.81 | 7532.02 |
KITCHEN_FLR_6 | 1.9070 | 0.0000 | 1.9070 | 0.0125 | 1.9195 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3772 | 0.0000 | 0.3772 | 0.0122 | 0.3894 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.5147 | 0.1926 | 80.7073 | 0.4537 | 81.1610 | 73.9670 | 4455.75 | 8072.14 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 70553146.19 | 564266.26 | 71117412.45 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 13.9740 | 0.0000 | 13.9740 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.2372 | 0.0179 | 2.2551 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 4891.23 | 3838.10 | 0.00 | 30.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 12.7189 | 15.5846 | 0.0000 | 12.9974 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.2372 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
Electricity:Building | 2534.12 | 32266.52 | 02-JAN-02:10 | 158241.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 332.05 | 3744.83 | 02-JAN-02:10 | 25084.28 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2527.03 | 32125.38 | 02-JAN-02:10 | 158000.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 868.85 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 868.85 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 868.85 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 188.95 | 1716.93 | 02-JAN-02:10 | 15451.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 868.85 | 7923.41 | 02-JAN-02:10 | 71560.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.95 | 223.93 | 02-JAN-02:10 | 1401.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.76 | 79.59 | 02-JAN-02:10 | 716.35 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.94 | 259.31 | 02-JAN-02:10 | 1623.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.14 | 92.17 | 02-JAN-02:10 | 829.54 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.64 | 250.98 | 02-JAN-02:10 | 1507.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.17 | 74.25 | 02-JAN-02:10 | 668.27 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 7.74 | 88.65 | 02-JAN-02:10 | 581.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.15 | 37.67 | 02-JAN-02:10 | 339.04 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 30.76 | 400.53 | 01-JAN-13:10 | 2922.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.42 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 16.42 | 95.71 | 01-JAN-13:10 | 1957.67 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 248.15 | 3061.89 | 02-JAN-02:10 | 18583.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.15 | 950.48 | 02-JAN-02:10 | 8554.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 99.15 | 950.48 | 02-JAN-02:10 | 8554.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 325.45 | 4437.75 | 01-JAN-02:10 | 23570.01 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 130.46 | 1104.51 | 01-JAN-02:10 | 10040.97 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 325.54 | 4438.96 | 01-JAN-02:10 | 23576.46 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 130.49 | 1104.81 | 01-JAN-02:10 | 10043.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.40 | 271.61 | 01-JAN-02:10 | 1567.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.93 | 92.50 | 01-JAN-02:10 | 840.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.40 | 271.58 | 01-JAN-02:10 | 1567.69 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.92 | 92.49 | 01-JAN-02:10 | 840.80 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.35 | 67.90 | 01-JAN-02:10 | 391.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.35 | 67.89 | 01-JAN-02:10 | 391.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.73 | 23.12 | 01-JAN-02:10 | 210.20 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 38.55 | 525.67 | 01-JAN-02:10 | 2791.95 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 15.45 | 130.83 | 01-JAN-02:10 | 1189.39 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 211.70 | 2631.28 | 02-JAN-02:10 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.84 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 35.84 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 211.70 | 2631.28 | 02-JAN-02:10 | 10185.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.84 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 35.84 | 381.98 | 02-JAN-02:10 | 3437.84 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.84 | 1104.96 | 24-FEB-23:30 | 3493.54 | 13-JAN-07:40 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1665.89 | 2619.35 | 12-APR-02:30 | 179824.61 | 14-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.50 | 0.00 | 01-JAN-11:10 | 2056.82 | 13-JAN-07:40 |
MedTempRefrigeration:Refrigeration:Electricity | 34.24 | 957.62 | 21-NOV-01:20 | 1245.48 | 13-JAN-07:40 |
Fans:Electricity | 603.96 | 11624.89 | 19-MAR-02:30 | 49371.23 | 31-JAN-05:40 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 818.91 | 13766.11 | 15-OCT-04:00 | 59815.78 | 07-AUG-21:10 |
ExteriorEquipment:Electricity | 650.10 | 9607.53 | 02-JAN-02:20 | 39721.54 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 31.07 | 542.72 | 03-JAN-04:10 | 1847.44 | 01-FEB-21:10 |
ElectricityPurchased:Facility | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
ElectricityPurchased:Plant | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
Cogeneration:ElectricityPurchased | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
ElectricityNet:Plant | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
Cogeneration:ElectricityNet | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
General:Cogeneration:ElectricityNet | 5900.39 | 76258.53 | 16-DEC-04:00 | 418067.96 | 05-JUN-19:10 |
General:Fans:Electricity | 603.96 | 11624.89 | 19-MAR-02:30 | 49371.23 | 31-JAN-05:40 |
ExteriorLights:Electricity | 262.44 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.44 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 183.89 | 0.00 | 01-JAN-12:10 | 9938.94 | 03-JAN-07:50 |
General:HeatRecovery:Electricity | 183.89 | 0.00 | 01-JAN-12:10 | 9938.94 | 03-JAN-07:50 |
WaterSystems:Electricity | 90.74 | 1086.56 | 08-NOV-01:20 | 4738.68 | 28-SEP-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 08-NOV-01:20 | 4738.68 | 28-SEP-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1420.33 | 0.00 | 01-JAN-03:20 | 169424.88 | 14-JUN-18:10 |
General:Cooling:Electricity | 1420.33 | 0.00 | 01-JAN-03:20 | 169424.88 | 14-JUN-18:10 |
Pumps:Electricity | 100.08 | 47.91 | 24-APR-07:10 | 4956.73 | 05-JUN-18:10 |
General:Pumps:Electricity | 100.08 | 47.91 | 24-APR-07:10 | 4956.73 | 05-JUN-18:10 |
WIRED_LTG_ELECTRICITY | 30.58 | 0.00 | 01-JAN-00:10 | 2518.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5011.04 | 31829.34 | 16-MAR-01:10 | 491539.08 | 26-NOV-17:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3222.21 | 18467.44 | 01-JAN-11:20 | 411972.44 | 01-FEB-21:30 |
WaterSystems:NaturalGas | 2924.78 | 18467.44 | 13-JAN-01:40 | 255720.02 | 09-FEB-18:20 |
Water Heater:WaterSystems:NaturalGas | 2924.78 | 18467.44 | 13-JAN-01:40 | 255720.02 | 09-FEB-18:20 |
Heating:NaturalGas | 297.42 | 0.00 | 01-JAN-11:20 | 176750.39 | 25-DEC-07:40 |
Boiler:Heating:NaturalGas | 297.42 | 0.00 | 01-JAN-11:20 | 176750.39 | 25-DEC-07:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4302.79 | -165.52 | 29-JAN-02:30 | 606028.96 | 20-JUL-22:00 |
PlantLoopCoolingDemand:HVAC | 4302.79 | -165.52 | 29-JAN-02:30 | 606028.96 | 20-JUL-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 4302.79 | -165.52 | 29-JAN-02:30 | 606028.96 | 20-JUL-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 04-JAN-01:30 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 04-JAN-01:30 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-07:50 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-07:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22718.00 | 131749.47 | 24-MAR-13:30 | 2292055.63 | 21-JUL-21:00 |
EnergyTransfer:Building | 5629.70 | 52869.25 | 03-MAR-03:00 | 368190.03 | 15-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 734.64 | 7159.46 | 03-MAR-03:00 | 36287.45 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 182.38 | 3934.84 | 30-MAR-22:20 | 10745.76 | 13-JAN-07:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.19 | 1967.42 | 30-MAR-22:20 | 5372.88 | 13-JAN-07:40 |
General:Refrigeration:EnergyTransfer | 91.19 | 1967.42 | 30-MAR-22:20 | 5372.88 | 13-JAN-07:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.19 | 1967.42 | 30-MAR-22:20 | 5372.88 | 13-JAN-07:40 |
EnergyTransfer:Plant | 11137.91 | 13405.39 | 12-APR-02:30 | 1398079.54 | 20-JUL-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.58 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.61 | 1822.85 | 21-NOV-01:20 | 2686.44 | 13-JAN-07:40 |
EnergyTransfer:Zone:BASEMENT | 438.05 | 572.37 | 06-MAR-06:00 | 26011.90 | 22-SEP-21:00 |
Heating:EnergyTransfer | 44.75 | 0.00 | 01-JAN-08:10 | 48884.36 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.01 | 0.00 | 01-JAN-00:10 | 522.56 | 22-NOV-05:30 |
General:Heating:EnergyTransfer | 44.75 | 0.00 | 01-JAN-08:10 | 48884.36 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.01 | 0.00 | 01-JAN-00:10 | 522.56 | 22-NOV-05:30 |
Cooling:EnergyTransfer | 5493.75 | 41304.45 | 03-MAR-03:00 | 364714.78 | 15-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 438.04 | 572.37 | 06-MAR-06:00 | 26011.90 | 22-SEP-21:00 |
General:Cooling:EnergyTransfer | 5493.75 | 41304.45 | 03-MAR-03:00 | 364714.78 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 438.04 | 572.37 | 06-MAR-06:00 | 26011.90 | 22-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.81 | 0.52 | 04-DEC-01:30 | 3662.43 | 18-OCT-13:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.09 | 0.00 | 01-JAN-00:10 | 775.75 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.09 | 0.00 | 01-JAN-00:10 | 775.75 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.72 | 0.00 | 07-JAN-07:00 | 3662.43 | 18-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.72 | 0.00 | 07-JAN-07:00 | 3662.43 | 18-OCT-13:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.29 | 72.15 | 03-DEC-11:30 | 2445.59 | 15-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 99.07 | 22-NOV-05:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 99.07 | 22-NOV-05:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.29 | 72.15 | 03-DEC-11:30 | 2445.59 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.29 | 72.15 | 03-DEC-11:30 | 2445.59 | 15-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 28.96 | 7.86 | 22-FEB-03:10 | 2140.18 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 182.01 | 22-NOV-05:30 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 182.01 | 22-NOV-05:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 28.94 | 0.00 | 23-JAN-09:50 | 2140.18 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 28.94 | 0.00 | 23-JAN-09:50 | 2140.18 | 15-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 17.53 | 0.22 | 27-DEC-08:00 | 1134.98 | 15-JUN-18:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 150.00 | 10-FEB-10:20 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 150.00 | 10-FEB-10:20 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 17.51 | 0.00 | 13-JAN-07:30 | 1134.98 | 15-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 17.51 | 0.00 | 13-JAN-07:30 | 1134.98 | 15-JUN-18:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.34 | 5181.50 | 03-MAR-03:00 | 39542.73 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 152.17 | 18-NOV-04:40 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 152.17 | 18-NOV-04:40 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.34 | 5181.50 | 03-MAR-03:00 | 39542.73 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.34 | 5181.50 | 03-MAR-03:00 | 39542.73 | 15-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 238.07 | 458.21 | 03-DEC-11:30 | 12868.61 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 468.87 | 27-NOV-11:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 468.87 | 27-NOV-11:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 238.07 | 458.21 | 03-DEC-11:30 | 12868.61 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 238.07 | 458.21 | 03-DEC-11:30 | 12868.61 | 18-OCT-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 792.52 | 2969.13 | 03-DEC-11:30 | 43606.99 | 07-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1489.51 | 22-NOV-05:30 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1489.51 | 22-NOV-05:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 792.52 | 2969.13 | 03-DEC-11:30 | 43606.99 | 07-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 792.52 | 2969.13 | 03-DEC-11:30 | 43606.99 | 07-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 71.94 | 0.10 | 20-DEC-22:20 | 11655.49 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.58 | 0.00 | 01-JAN-08:10 | 4074.56 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.58 | 0.00 | 01-JAN-08:10 | 4074.56 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 67.36 | 0.00 | 01-JAN-00:10 | 11655.49 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 67.36 | 0.00 | 01-JAN-00:10 | 11655.49 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 67.15 | 0.07 | 07-FEB-05:30 | 11942.52 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 7.82 | 0.00 | 01-JAN-08:10 | 4282.74 | 27-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 7.82 | 0.00 | 01-JAN-08:10 | 4282.74 | 27-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 59.33 | 0.00 | 01-JAN-00:10 | 11942.52 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 59.33 | 0.00 | 01-JAN-00:10 | 11942.52 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 510.92 | 3223.58 | 27-DEC-06:00 | 49048.81 | 22-OCT-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 510.92 | 3223.58 | 27-DEC-06:00 | 49048.81 | 22-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 510.92 | 3223.58 | 27-DEC-06:00 | 49048.81 | 22-OCT-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 486.06 | 0.57 | 07-NOV-05:40 | 72103.43 | 19-JUN-19:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 10.46 | 0.00 | 01-JAN-00:10 | 25089.59 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 10.46 | 0.00 | 01-JAN-00:10 | 25089.59 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 475.60 | 0.00 | 02-JAN-02:50 | 72103.43 | 19-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 475.60 | 0.00 | 02-JAN-02:50 | 72103.43 | 19-JUN-19:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 72.86 | 0.37 | 04-JAN-23:00 | 11931.48 | 14-JUN-08:30 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.76 | 0.00 | 01-JAN-08:10 | 4070.49 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.76 | 0.00 | 01-JAN-08:10 | 4070.49 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 68.10 | 0.00 | 01-JAN-00:10 | 11931.48 | 14-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 68.10 | 0.00 | 01-JAN-00:10 | 11931.48 | 14-JUN-08:30 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 67.59 | 0.16 | 15-MAR-03:20 | 12070.00 | 14-JUN-08:30 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 7.76 | 0.00 | 01-JAN-08:10 | 4143.77 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 7.76 | 0.00 | 01-JAN-08:10 | 4143.77 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.83 | 0.00 | 01-JAN-00:10 | 12070.00 | 14-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.83 | 0.00 | 01-JAN-00:10 | 12070.00 | 14-JUN-08:30 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 203.92 | 78.35 | 27-DEC-08:00 | 12601.72 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.20 | 0.00 | 01-JAN-00:10 | 1293.70 | 22-NOV-05:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.20 | 0.00 | 01-JAN-00:10 | 1293.70 | 22-NOV-05:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 203.72 | 0.00 | 13-JAN-07:30 | 12601.72 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 203.72 | 0.00 | 13-JAN-07:30 | 12601.72 | 15-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 18.92 | 0.01 | 08-MAR-03:00 | 3167.82 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.23 | 0.00 | 01-JAN-08:10 | 1215.17 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.23 | 0.00 | 01-JAN-08:10 | 1215.17 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.69 | 0.00 | 01-JAN-00:10 | 3167.82 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.69 | 0.00 | 01-JAN-00:10 | 3167.82 | 15-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.17 | 0.04 | 19-NOV-20:00 | 3197.69 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.43 | 0.00 | 01-JAN-08:10 | 1321.37 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.43 | 0.00 | 01-JAN-08:10 | 1321.37 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.75 | 0.00 | 01-JAN-00:10 | 3197.69 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.75 | 0.00 | 01-JAN-00:10 | 3197.69 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 107.36 | 0.02 | 18-DEC-03:30 | 15721.20 | 18-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.21 | 0.00 | 01-JAN-00:10 | 4832.40 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.21 | 0.00 | 01-JAN-00:10 | 4832.40 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 104.15 | 0.00 | 01-JAN-05:30 | 15721.20 | 18-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 104.15 | 0.00 | 01-JAN-05:30 | 15721.20 | 18-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 458.57 | 3272.97 | 10-FEB-10:30 | 24091.47 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 458.57 | 3272.97 | 10-FEB-10:30 | 24091.47 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 458.57 | 3272.97 | 10-FEB-10:30 | 24091.47 | 15-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 496.77 | 3572.53 | 23-JAN-09:50 | 25290.03 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 496.77 | 3572.53 | 23-JAN-09:50 | 25290.03 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 496.77 | 3572.53 | 23-JAN-09:50 | 25290.03 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 643.45 | 4991.75 | 03-MAR-03:00 | 31204.22 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 643.45 | 4991.75 | 03-MAR-03:00 | 31204.22 | 02-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.26 | 1.84 | 02-MAR-08:00 | 7006.87 | 03-JUL-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.17 | 0.00 | 01-JAN-00:10 | 1100.78 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.17 | 0.00 | 01-JAN-00:10 | 1100.78 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.09 | 0.00 | 07-JAN-07:10 | 7006.87 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.09 | 0.00 | 07-JAN-07:10 | 7006.87 | 03-JUL-12:50 |
PlantLoopHeatingDemand:Facility | 856.42 | 7206.41 | 02-AUG-02:30 | 186563.82 | 09-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 648.51 | 7206.41 | 02-AUG-02:30 | 50255.56 | 01-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 648.51 | 7206.41 | 02-AUG-02:30 | 50255.56 | 01-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 648.51 | 7206.41 | 02-AUG-02:30 | 50255.56 | 01-FEB-07:10 |
EnergyTransfer:HVAC | 5950.40 | 53.00 | 11-APR-12:20 | 671168.19 | 21-JUL-18:10 |
HeatingCoils:EnergyTransfer | 207.91 | 0.00 | 01-JAN-11:20 | 136776.03 | 09-JAN-07:30 |
PlantLoopHeatingDemand:HVAC | 207.91 | 0.00 | 01-JAN-11:20 | 136776.03 | 09-JAN-07:30 |
HeatingCoils:PlantLoopHeatingDemand | 207.91 | 0.00 | 01-JAN-11:20 | 136776.03 | 09-JAN-07:30 |
CoolingCoils:EnergyTransfer | 4302.79 | -165.52 | 29-JAN-02:30 | 606028.96 | 20-JUL-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 1130.13 | 0.00 | 01-JAN-12:10 | 359107.69 | 03-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 309.58 | 0.00 | 01-JAN-00:10 | 149987.48 | 20-JUL-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 648.51 | 7206.41 | 02-AUG-02:30 | 50255.56 | 01-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 648.51 | 7206.41 | 02-AUG-02:30 | 50255.56 | 01-FEB-07:10 |
Boilers:EnergyTransfer | 205.46 | 0.00 | 01-JAN-11:20 | 128545.45 | 25-DEC-07:40 |
Chillers:EnergyTransfer | 4386.21 | 0.00 | 01-JAN-03:20 | 614869.31 | 20-JUL-22:00 |
HeatRejection:EnergyTransfer | 5806.54 | 0.00 | 01-JAN-03:20 | 757511.02 | 20-JUL-22:00 |
General:HeatRejection:EnergyTransfer | 5806.54 | 0.00 | 01-JAN-03:20 | 757511.02 | 20-JUL-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.008 | -438.041 | 0.000 | 0.000 | 138.447 | 188.948 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -32.466 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.090 | -46.716 | 0.000 | 0.000 | 14.705 | 8.760 | 10.186 | 23.522 | 0.000 | 0.462 | 0.258 | 0.000 | -9.110 | 0.000 | -2.156 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.001 | -39.293 | 0.000 | 0.000 | 16.215 | 10.144 | 11.795 | 0.000 | 0.000 | 0.181 | 1.868 | 0.000 | 0.000 | 0.000 | -0.910 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.020 | -28.941 | 0.000 | 0.000 | 3.576 | 8.172 | 12.471 | 0.000 | 0.000 | 0.435 | 6.230 | 0.000 | 0.000 | 0.000 | -1.964 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.021 | -17.506 | 0.000 | 0.000 | 2.795 | 4.146 | 3.598 | 0.000 | 0.000 | 0.258 | 7.783 | 0.000 | 0.000 | 0.000 | -1.095 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.002 | -608.341 | 0.000 | 0.000 | 10.949 | 5.547 | 658.131 | 0.000 | 0.000 | 0.608 | 0.000 | 0.000 | 0.000 | 0.000 | -2.992 | -63.902 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.006 | -238.069 | 0.000 | 0.000 | 182.339 | 16.421 | 14.341 | 65.143 | 0.000 | 1.020 | 0.000 | 0.000 | -27.911 | 0.000 | -5.324 | -7.966 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.003 | -792.530 | 0.000 | 0.000 | 537.612 | 99.154 | 148.998 | 86.902 | 0.000 | 2.944 | 0.000 | 0.000 | -37.018 | 0.000 | -15.399 | -30.666 |
ROOM_1_FLR_3 | 6.482 | -53.359 | 0.000 | -15.895 | 0.000 | 0.000 | 9.541 | 10.925 | 10.478 | 50.623 | 0.000 | 1.524 | 4.636 | 0.000 | -19.368 | 0.000 | -5.588 | -0.002 |
ROOM_2_FLR_3 | 10.333 | -46.315 | 0.000 | -15.534 | 0.000 | 0.000 | 9.592 | 10.924 | 10.477 | 38.390 | 0.000 | 1.530 | 5.933 | 0.000 | -19.958 | 0.000 | -5.371 | -0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -260.797 | 0.000 | -250.117 | 0.000 | 0.000 | 0.000 | 130.455 | 194.997 | 287.406 | 0.000 | 6.402 | 53.227 | 0.000 | -115.837 | 0.000 | -45.737 | -0.000 |
ROOM_4_MULT19_FLR_3 | 28.973 | -288.385 | 0.000 | -205.726 | 0.000 | 0.000 | 183.460 | 130.491 | 195.050 | 102.899 | 0.000 | 9.126 | 0.001 | 0.000 | -107.494 | 0.000 | -35.164 | -13.230 |
ROOM_5_FLR_3 | 6.633 | -53.945 | 0.000 | -16.031 | 0.000 | 0.000 | 9.531 | 10.925 | 10.478 | 50.461 | 0.000 | 1.519 | 4.567 | 0.000 | -18.541 | 0.000 | -5.598 | -0.000 |
ROOM_6_FLR_3 | 10.213 | -46.625 | 0.000 | -15.661 | 0.000 | 0.000 | 9.584 | 10.924 | 10.477 | 37.600 | 0.000 | 1.525 | 5.830 | 0.000 | -18.508 | 0.000 | -5.359 | -0.002 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.199 | -203.725 | 0.000 | 0.000 | 113.602 | 91.336 | 0.000 | 42.770 | 0.000 | 1.337 | 0.001 | 0.000 | -25.356 | 0.000 | -6.011 | -14.152 |
ROOM_1_FLR_6 | 2.826 | -13.342 | 0.000 | -3.950 | 0.000 | 0.000 | 2.389 | 2.731 | 2.620 | 12.582 | 0.000 | 0.379 | 0.000 | 0.000 | -4.768 | 0.000 | -1.418 | -0.048 |
ROOM_2_FLR_6 | 4.165 | -11.632 | 0.000 | -3.851 | 0.000 | 0.000 | 2.403 | 2.731 | 2.619 | 9.562 | 0.000 | 0.381 | 0.000 | 0.000 | -4.895 | 0.000 | -1.360 | -0.122 |
ROOM_3_MULT9_FLR_6 | 5.231 | -80.405 | 0.000 | -25.764 | 0.000 | 0.000 | 21.432 | 15.453 | 23.098 | 63.467 | 0.000 | 1.786 | 5.602 | 0.000 | -22.209 | 0.000 | -7.692 | -0.002 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -458.576 | 0.000 | 0.000 | 314.851 | 35.844 | 175.857 | 9.435 | 0.000 | 0.625 | 0.000 | 0.000 | -16.318 | 0.000 | -3.566 | -58.153 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -496.775 | 0.000 | 0.000 | 314.280 | 35.844 | 175.857 | 9.206 | 0.000 | 0.625 | 0.001 | 0.000 | -16.819 | 0.000 | -3.592 | -18.624 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -643.434 | 0.000 | 0.000 | 28.017 | 14.807 | 550.372 | 22.421 | 0.000 | 0.560 | 42.389 | 0.000 | -11.903 | 0.000 | -3.229 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.171 | -105.087 | 0.000 | 0.000 | 30.243 | 24.166 | 0.000 | 20.582 | 0.000 | 0.562 | 43.327 | 0.000 | -11.330 | 0.000 | -2.634 | 0.000 |
Total Facility | 74.856 | -854.804 | 0.520 | -4669.564 | 0.000 | 0.000 | 1955.562 | 868.847 | 2365.005 | 932.970 | 0.000 | 33.789 | 181.654 | 0.000 | -487.343 | 0.000 | -162.160 | -239.336 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-DEC-22:57 | 0.00 | 0.00 | 0.00 | -49373.16 | 0.00 | 0.00 | 6664.34 | 10301.16 | 7097.65 | 0.00 | 0.00 | 0.00 | 25310.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 18-OCT-13:10 | 0.00 | 0.00 | 0.00 | -3662.48 | 0.00 | 0.00 | 150.60 | 198.99 | 252.59 | 4380.23 | 0.00 | 39.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1359.11 |
RETAIL_2_FLR_1 | 08-FEB-20:40 | 0.00 | 0.00 | 0.00 | -2847.46 | 0.00 | 0.00 | 614.34 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 693.90 | 0.00 | -0.00 | 0.00 | -84.25 | 0.00 |
MECH_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2140.31 | 0.00 | 0.00 | 129.08 | 668.27 | 839.45 | 0.00 | 0.00 | 88.47 | 415.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 04-DEC-22:57 | 0.00 | 0.00 | 0.00 | -1233.56 | 0.00 | 0.00 | 150.55 | 226.02 | 178.43 | 0.00 | 0.00 | 0.00 | 782.05 | 0.00 | -0.00 | 0.00 | -103.50 | 0.00 |
LAUNDRY_FLR_1 | 01-MAR-20:46 | 0.00 | 0.00 | 0.00 | -53393.76 | 0.00 | 0.00 | 400.93 | 453.60 | 44299.38 | 0.00 | 0.00 | 0.00 | 8571.53 | 0.00 | -0.00 | 0.00 | -331.69 | 0.00 |
CAFE_FLR_1 | 07-DEC-00:14 | 0.00 | 0.00 | 0.00 | -19212.02 | 0.00 | 0.00 | 8782.44 | 435.04 | 304.82 | 0.00 | 0.00 | 0.00 | 13148.81 | 0.00 | -3006.77 | 0.00 | -452.33 | 0.00 |
LOBBY_FLR_1 | 07-DEC-00:14 | 0.00 | 0.00 | 0.00 | -66107.56 | 0.00 | 0.00 | 26153.60 | 1900.96 | 3167.12 | 0.00 | 0.00 | 0.00 | 40166.60 | 0.00 | -3963.23 | 0.00 | -1317.49 | 0.00 |
ROOM_1_FLR_3 | 06-APR-18:11 | 0.00 | -15671.80 | 0.00 | -549.98 | 0.00 | 0.00 | 301.98 | 748.40 | 484.65 | 0.00 | 0.00 | 0.00 | 15342.34 | 0.00 | -428.36 | 0.00 | -227.24 | 0.00 |
ROOM_2_FLR_3 | 14-JUN-08:11 | 0.00 | -15326.97 | 0.00 | -709.45 | 0.00 | 0.00 | 79.95 | 369.95 | 452.99 | 1553.43 | 0.00 | 99.17 | 13480.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-13:20 | 0.00 | -39670.84 | 0.00 | -9379.45 | 0.00 | 0.00 | 0.00 | 3313.52 | 2548.95 | 53070.29 | 0.00 | 322.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10205.00 |
ROOM_4_MULT19_FLR_3 | 20-MAY-08:51 | 0.00 | -100384.60 | 0.00 | -9223.56 | 0.00 | 0.00 | 2419.85 | 5624.48 | 12159.85 | 9140.18 | 0.00 | 428.54 | 79835.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 20-MAY-08:51 | 0.00 | -14982.93 | 0.00 | -811.98 | 0.00 | 0.00 | 107.49 | 470.90 | 653.23 | 6837.32 | 0.00 | 34.19 | 7691.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 20-MAY-08:51 | 0.00 | -14878.75 | 0.00 | -812.33 | 0.00 | 0.00 | 107.49 | 470.85 | 653.15 | 6747.34 | 0.00 | 34.03 | 7678.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 04-DEC-22:57 | 0.00 | 0.00 | 0.00 | -13985.00 | 0.00 | 0.00 | 6146.94 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 6175.73 | 0.00 | -2759.34 | 0.00 | -557.83 | 0.00 |
ROOM_1_FLR_6 | 06-APR-18:11 | 0.00 | -4178.69 | 0.00 | -139.21 | 0.00 | 0.00 | 74.43 | 187.10 | 121.16 | 0.00 | 0.00 | 0.00 | 4112.17 | 0.00 | -119.14 | 0.00 | -57.83 | 0.00 |
ROOM_2_FLR_6 | 06-APR-18:11 | 0.00 | -4087.81 | 0.00 | -135.21 | 0.00 | 0.00 | 75.96 | 187.08 | 121.15 | 0.00 | 0.00 | 0.00 | 3998.76 | 0.00 | -103.59 | 0.00 | -56.34 | 0.00 |
ROOM_3_MULT9_FLR_6 | 09-NOV-09:51 | 0.00 | -19688.43 | 0.00 | -1103.46 | 0.00 | 0.00 | 166.95 | 523.33 | 998.70 | 10678.59 | 0.00 | 0.00 | 8602.98 | 0.00 | -0.00 | 0.00 | -178.66 | 0.00 |
BANQUET_FLR_6 | 24-FEB-05:14 | 0.00 | 0.00 | 0.00 | -43473.31 | 0.00 | 0.00 | 14924.77 | 763.96 | 2249.30 | 0.00 | 0.00 | 0.00 | 27535.27 | 0.00 | -1719.19 | 0.00 | -280.81 | 0.00 |
DINING_FLR_6 | 04-DEC-22:57 | 0.00 | 0.00 | 0.00 | -43384.95 | 0.00 | 0.00 | 15625.74 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 20598.31 | 0.00 | -1562.51 | 0.00 | -316.39 | 0.00 |
KITCHEN_FLR_6 | 31-DEC-22:29 | 0.00 | 0.00 | 0.00 | -41686.38 | 0.00 | 0.00 | 1241.63 | 672.74 | 16762.29 | 0.00 | 0.00 | 0.00 | 24604.61 | 0.00 | -1336.98 | 0.00 | -257.90 | 0.00 |
CORRIDOR_FLR_6 | 03-JUL-12:50 | 0.00 | 0.00 | 0.00 | -7005.64 | 0.00 | 0.00 | 308.46 | 548.96 | 0.00 | 2016.31 | 0.00 | 151.15 | 3980.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-18:02 | 0.00 | -199319.98 | 0.00 | -224068.07 | 0.00 | 0.00 | 74051.14 | 59755.35 | 120482.43 | 62900.91 | 0.00 | 7221.89 | 98976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-MAR-03:28 | 0.00 | 0.00 | 1389.88 | 0.00 | 0.00 | 0.00 | 7441.55 | 1716.93 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12576.26 |
RETAIL_1_FLR_1 | 27-NOV-08:38 | 0.00 | 0.00 | 1304.27 | 0.00 | 0.00 | 0.00 | 358.03 | 318.38 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -583.46 | 0.00 | -189.58 | -1568.47 |
RETAIL_2_FLR_1 | 22-NOV-05:30 | 0.00 | 0.00 | 198.17 | 0.00 | 0.00 | 0.00 | 832.48 | 184.34 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -76.58 | -1389.13 |
MECH_FLR_1 | 30-DEC-10:18 | 0.00 | 0.00 | 717.63 | 0.00 | 0.00 | 0.00 | 65.76 | 222.76 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -171.32 | -1188.28 |
STORAGE_FLR_1 | 30-DEC-10:18 | 0.00 | 0.00 | 495.17 | 0.00 | 0.00 | 0.00 | 50.59 | 113.01 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -98.77 | -661.95 |
LAUNDRY_FLR_1 | 24-FEB-04:28 | 0.00 | 0.00 | 1150.30 | 0.00 | 0.00 | 0.00 | 607.20 | 50.40 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -230.32 | -10903.76 |
CAFE_FLR_1 | 26-NOV-18:03 | 0.00 | 0.00 | 1111.57 | 0.00 | 0.00 | 0.00 | 4704.31 | 1087.60 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2506.42 | 0.00 | -369.44 | -4637.27 |
LOBBY_FLR_1 | 19-NOV-00:37 | 0.00 | 0.00 | 3370.95 | 0.00 | 0.00 | 0.00 | 20967.48 | 2851.44 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4141.70 | 0.00 | -1375.62 | -25895.38 |
ROOM_1_FLR_3 | 28-NOV-09:01 | 5926.69 | 278.86 | 0.00 | -278.86 | 0.00 | 0.00 | 106.85 | 370.00 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -217.45 | 0.00 | -400.27 | -6238.87 |
ROOM_2_FLR_3 | 28-NOV-09:01 | 6001.12 | 254.28 | 0.00 | -254.28 | 0.00 | 0.00 | 108.50 | 369.95 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -722.05 | 0.00 | -390.63 | -5819.88 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 08-MAR-09:03 | 34089.87 | 4960.78 | 0.00 | -4960.78 | 0.00 | 0.00 | 1806.89 | 4419.24 | 8433.45 | 915.08 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1177.42 | -48487.10 |
ROOM_5_FLR_3 | 03-DEC-19:01 | 5753.16 | 283.83 | 0.00 | -283.83 | 0.00 | 0.00 | 345.62 | 840.90 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1783.20 | 0.00 | -351.22 | -5289.92 |
ROOM_6_FLR_3 | 19-DEC-19:01 | 5858.82 | 248.05 | 0.00 | -248.05 | 0.00 | 0.00 | 418.34 | 748.31 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1973.48 | 0.00 | -366.25 | -5170.34 |
CORRIDOR_FLR_3 | 02-DEC-18:56 | 0.00 | 0.00 | 3247.92 | 0.00 | 0.00 | 0.00 | 4157.41 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2595.79 | 0.00 | -492.58 | -9296.48 |
ROOM_1_FLR_6 | 28-NOV-09:01 | 1767.52 | 63.11 | 0.00 | -63.11 | 0.00 | 0.00 | 27.22 | 92.50 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.35 | 0.00 | -97.87 | -1858.28 |
ROOM_2_FLR_6 | 03-DEC-19:01 | 1783.06 | 62.94 | 0.00 | -62.94 | 0.00 | 0.00 | 88.42 | 210.20 | 121.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -428.63 | 0.00 | -85.10 | -1689.10 |
ROOM_3_MULT9_FLR_6 | 28-NOV-09:01 | 8040.14 | 520.85 | 0.00 | -520.85 | 0.00 | 0.00 | 233.25 | 523.33 | 998.70 | 778.74 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -483.09 | -10091.07 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 27-NOV-08:38 | 0.00 | 0.00 | 3091.37 | 0.00 | 0.00 | 0.00 | 733.35 | 878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -812.09 | 0.00 | -237.83 | -3653.14 |
Total Facility | 26-DEC-16:02 | -24733.31 | 97972.19 | 64.09 | -97972.19 | 0.00 | 0.00 | 59268.94 | 19174.48 | 73912.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42970.40 | 0.00 | -12029.67 | -72686.72 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 25.3944 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 25.2669 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.6972 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6560 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1230 | 3.1230 | 1.4335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3769 | 0.3769 | 0.1730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2839 | 0.2839 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2359 | 0.2359 | 0.1083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1565 | 0.1565 | 0.0718 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7753 | 3.7753 | 1.7329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6005 | 1.6005 | 0.7346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3394 | 5.3394 | 2.4508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7557 | 1.7557 | 0.8059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5702 | 2.5702 | 1.1797 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6918 | 2.6918 | 1.2355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5913 | 2.5913 | 1.1894 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8940 | 0.8940 | 0.4104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 25.3944 | 25.2669 | 25.3944 | 11.6560 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5615 | 1.5615 | 1.4335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1884 | 0.1884 | 0.1730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1420 | 0.1420 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1180 | 0.1180 | 0.1083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0782 | 0.0782 | 0.0718 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8876 | 1.8876 | 1.7329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8002 | 0.8002 | 0.7346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6697 | 2.6697 | 2.4508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8778 | 0.8778 | 0.8059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2851 | 1.2851 | 1.1797 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3459 | 1.3459 | 1.2355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2956 | 1.2956 | 1.1894 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4470 | 0.4470 | 0.4104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.6972 | 11.6560 | 11.6560 | 11.6560 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 289.83 |
Number of hours not met | 289.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 297.42 | 176750.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1420.33 | 169424.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 868.85 | 71560.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.44 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.07 | 1847.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 603.96 | 49371.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 100.08 | 4956.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 183.89 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.68 | 2924.78 | 255720.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.50 | 2056.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.24 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.01 | 5900.39 |
Natural Gas | 1788.84 | 5011.04 |
Additional | 0.00 | 0.00 |
Total | 3508.85 | 10911.44 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 76.58 |
Space Heating | 0.00 |
Space Cooling | 125.19 |
Fans (All) | 53.23 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 520.07 |
Subtotal | 520.07 |
Natural Gas [MJ/m2] | |
Space Heating | 26.22 |
Service Water Heating | 257.80 |
Miscellaneous (All) | 441.69 |
Subtotal | 441.69 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.96 |
Space Heating | 2.73 |
Space Cooling | 13.02 |
Fans (All) | 5.54 |
Service Water Heating | 27.64 |
Receptacle Equipment | 31.59 |
Miscellaneous | 11.53 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8741.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 19.00 | 0.00 | 0.00 | 0.00 |
Average | 8758.32 | 1.68 | 0.00 | 0.00 | 0.00 |
Sum | 192683.00 | 37.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108258.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 11.00 | 0.00 | 0.00 | 0.00 |
Average | 288886.55 | 0.50 | 0.00 | 0.00 | 0.00 |
Sum | 6355504.00 | 11.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8174.00 | 586.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8319.17 | 440.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8649.67 | 110.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8651.17 | 108.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8297.17 | 462.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8334.17 | 425.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8174.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 586.00 | 0.00 | 0.00 | 0.00 |
Average | 8657.36 | 102.64 | 0.00 | 0.00 | 0.00 |
Sum | 190462.00 | 2258.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59000.83 | 155.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 641423.67 | 68993.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1960368.67 | 155060.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4149.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4149.83 | 4.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4150.17 | 3.83 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4151.17 | 2.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4148.83 | 5.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4149.00 | 5.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4146.17 | 7.83 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1148611.17 | 97103.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1155524.17 | 90190.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108223.83 | 45.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1960368.67 | 155060.33 | 0.00 | 0.00 | 0.00 |
Average | 270178.77 | 18708.27 | 0.00 | 0.00 | 0.00 |
Sum | 5943933.00 | 411582.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:42:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353654E+11 | 37996.26 | 26-JAN-21:56 | 3.90 | -2.9 | 0.810185E+10 | 4965.35 | 23-JAN-22:49 | 3.90 | -2.9 |
February | 0.277645E+11 | 33051.10 | 01-FEB-20:58 | 3.30 | -1.9 | 0.686387E+10 | 4925.51 | 02-FEB-22:30 | 3.30 | -2.4 |
March | 0.281050E+11 | 23018.04 | 13-MAR-05:18 | 5.20 | 1.53 | 0.712620E+10 | 4704.00 | 01-MAR-01:49 | 5.20 | 1.53 |
April | 0.284112E+11 | 22501.61 | 13-APR-05:17 | 4.63 | -1.3 | 0.692083E+10 | 4478.42 | 07-APR-21:19 | 4.63 | -1.3 |
May | 0.311904E+11 | 17427.27 | 02-MAY-04:55 | 10.00 | 4.04 | 0.735920E+10 | 4597.02 | 12-MAY-22:10 | 21.52 | 10.32 |
June | 0.320364E+11 | 15285.73 | 15-JUN-18:10 | 35.92 | 14.47 | 0.734549E+10 | 4737.19 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.376819E+11 | 20253.40 | 19-JUL-21:00 | 23.90 | 20.39 | 0.808146E+10 | 4837.13 | 05-JUL-21:00 | 23.90 | 20.39 |
August | 0.425830E+11 | 23570.55 | 24-AUG-21:00 | 26.70 | 16.71 | 0.823403E+10 | 4837.27 | 22-AUG-00:10 | 26.70 | 16.71 |
September | 0.454501E+11 | 26011.90 | 22-SEP-21:00 | 25.00 | 17.90 | 0.797250E+10 | 4837.40 | 19-SEP-04:10 | 25.00 | 17.90 |
October | 0.462460E+11 | 38165.71 | 25-OCT-06:23 | 7.25 | 5.26 | 0.823294E+10 | 4963.11 | 25-OCT-03:20 | 7.25 | 5.26 |
November | 0.428805E+11 | 44687.01 | 16-NOV-01:41 | 5.00 | 2.18 | 0.796077E+10 | 5056.83 | 20-NOV-00:20 | 4.80 | -1.0 |
December | 0.403239E+11 | 49375.25 | 04-DEC-22:57 | 3.30 | 2.03 | 0.821538E+10 | 5001.79 | 12-DEC-22:40 | 6.70 | 3.06 |
Annual Sum or Average | 0.438038E+12 | 0.924145E+11 | ||||||||
Minimum of Months | 0.277645E+11 | 15285.73 | 3.30 | -2.9 | 0.686387E+10 | 4478.42 | 3.30 | -2.9 | ||
Maximum of Months | 0.462460E+11 | 49375.25 | 35.92 | 20.39 | 0.823403E+10 | 5056.83 | 26.70 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279046E+10 | 2994.02 | 27-JAN-13:44 | 8.22 | 0.11 | 0.666773E+09 | 443.00 | 12-JAN-22:19 | 8.22 | 0.11 |
February | 0.277430E+10 | 2860.27 | 07-FEB-13:30 | 20.30 | 9.54 | 0.611347E+09 | 467.26 | 06-FEB-22:30 | 20.30 | 9.54 |
March | 0.311966E+10 | 2374.57 | 28-MAR-21:35 | 4.27 | 1.35 | 0.688054E+09 | 469.53 | 16-MAR-21:19 | 4.27 | 1.35 |
April | 0.368044E+10 | 2384.01 | 03-APR-14:10 | 26.70 | 11.67 | 0.718498E+09 | 491.84 | 28-APR-22:10 | 21.52 | 12.87 |
May | 0.420804E+10 | 2412.84 | 31-MAY-18:15 | 30.73 | 15.09 | 0.784402E+09 | 491.84 | 17-MAY-22:10 | 30.73 | 15.09 |
June | 0.472248E+10 | 2817.44 | 15-JUN-18:15 | 35.73 | 14.50 | 0.792312E+09 | 491.86 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.490740E+10 | 2796.51 | 26-JUL-18:03 | 33.77 | 19.75 | 0.817160E+09 | 491.84 | 05-JUL-21:00 | 33.77 | 19.75 |
August | 0.495551E+10 | 2938.73 | 27-AUG-12:00 | 33.30 | 15.93 | 0.814536E+09 | 491.86 | 22-AUG-00:10 | 33.30 | 15.93 |
September | 0.496488E+10 | 3559.34 | 20-SEP-12:50 | 32.12 | 17.95 | 0.778750E+09 | 491.85 | 19-SEP-23:10 | 32.12 | 17.95 |
October | 0.459176E+10 | 3662.43 | 18-OCT-13:10 | 27.88 | 18.10 | 0.762657E+09 | 491.85 | 05-OCT-23:49 | 27.88 | 18.10 |
November | 0.347935E+10 | 3391.31 | 10-NOV-12:00 | 21.10 | 12.09 | 0.676658E+09 | 491.79 | 09-NOV-22:19 | 21.10 | 12.09 |
December | 0.252143E+10 | 3149.52 | 07-DEC-10:10 | 7.25 | 2.02 | 0.657892E+09 | 429.32 | 15-DEC-22:30 | 14.15 | 4.60 |
Annual Sum or Average | 0.467157E+11 | 0.876904E+10 | ||||||||
Minimum of Months | 0.252143E+10 | 2374.57 | 4.27 | 0.11 | 0.611347E+09 | 429.32 | 4.27 | 0.11 | ||
Maximum of Months | 0.496488E+10 | 3662.43 | 35.73 | 19.75 | 0.817160E+09 | 491.86 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268919E+10 | 2433.92 | 04-JAN-22:03 | 4.50 | -1.6 | 0.880077E+09 | 570.93 | 05-JAN-22:19 | 5.77 | -2.1 |
February | 0.250919E+10 | 2847.55 | 08-FEB-20:40 | 3.50 | -0.4 | 0.805247E+09 | 585.93 | 22-FEB-03:20 | 5.37 | -0.4 |
March | 0.285851E+10 | 2620.48 | 17-MAR-20:58 | 5.00 | -1.0 | 0.907641E+09 | 576.89 | 28-MAR-21:30 | 4.45 | 1.48 |
April | 0.315453E+10 | 2227.19 | 11-APR-01:50 | 6.10 | 0.63 | 0.910703E+09 | 570.23 | 17-APR-21:00 | 8.90 | 6.05 |
May | 0.362613E+10 | 2236.24 | 19-MAY-21:00 | 30.00 | 13.65 | 0.959151E+09 | 569.58 | 18-MAY-00:10 | 30.00 | 13.65 |
June | 0.388785E+10 | 2445.59 | 15-JUN-21:00 | 33.30 | 13.72 | 0.937675E+09 | 569.57 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.401277E+10 | 2397.91 | 25-JUL-21:00 | 31.70 | 17.64 | 0.965527E+09 | 569.55 | 19-JUL-21:19 | 31.70 | 17.64 |
August | 0.395074E+10 | 2432.51 | 07-AUG-21:00 | 31.70 | 16.85 | 0.968517E+09 | 569.57 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.372385E+10 | 2303.88 | 20-SEP-20:10 | 25.40 | 15.25 | 0.934804E+09 | 569.58 | 19-SEP-04:10 | 25.40 | 15.25 |
October | 0.341130E+10 | 2227.53 | 05-OCT-20:10 | 23.80 | 16.56 | 0.949142E+09 | 571.70 | 27-OCT-00:10 | 10.87 | 6.05 |
November | 0.284614E+10 | 2286.62 | 19-NOV-00:12 | 5.03 | -1.2 | 0.881921E+09 | 582.56 | 20-NOV-00:20 | 4.80 | -1.0 |
December | 0.262292E+10 | 2546.87 | 04-DEC-22:57 | 3.30 | 2.03 | 0.867779E+09 | 575.52 | 21-DEC-23:10 | 3.72 | -0.6 |
Annual Sum or Average | 0.392931E+11 | 0.109682E+11 | ||||||||
Minimum of Months | 0.250919E+10 | 2227.19 | 3.30 | -1.6 | 0.805247E+09 | 569.55 | 3.72 | -2.1 | ||
Maximum of Months | 0.401277E+10 | 2847.55 | 33.30 | 17.64 | 0.968517E+09 | 585.93 | 31.70 | 17.64 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180557E+10 | 1591.86 | 02-JAN-08:55 | 4.40 | 2.61 | 0.161005E+09 | 104.46 | 04-JAN-22:49 | 4.90 | -1.3 |
February | 0.171383E+10 | 1665.45 | 24-FEB-02:31 | 5.37 | 2.12 | 0.148680E+09 | 107.33 | 23-FEB-22:10 | 5.37 | 2.12 |
March | 0.200530E+10 | 1694.65 | 13-MAR-05:18 | 5.20 | 1.53 | 0.170136E+09 | 110.84 | 16-MAR-21:10 | 17.02 | 5.96 |
April | 0.227465E+10 | 1647.06 | 11-APR-01:57 | 6.10 | 0.60 | 0.179339E+09 | 120.45 | 21-APR-21:19 | 24.80 | 9.48 |
May | 0.272500E+10 | 1783.72 | 31-MAY-20:00 | 29.40 | 14.60 | 0.198608E+09 | 120.45 | 24-MAY-21:49 | 29.40 | 14.60 |
June | 0.316813E+10 | 2140.18 | 15-JUN-20:00 | 33.90 | 14.00 | 0.198358E+09 | 120.46 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.329969E+10 | 2096.39 | 03-JUL-20:00 | 28.30 | 19.12 | 0.204348E+09 | 120.46 | 05-JUL-21:00 | 27.80 | 17.53 |
August | 0.310445E+10 | 2060.70 | 07-AUG-20:00 | 31.70 | 17.36 | 0.204092E+09 | 120.46 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.272961E+10 | 1739.07 | 22-SEP-20:00 | 26.10 | 18.64 | 0.194554E+09 | 120.46 | 20-SEP-21:00 | 26.10 | 18.64 |
October | 0.244599E+10 | 1531.61 | 05-OCT-20:00 | 23.90 | 16.65 | 0.189071E+09 | 120.45 | 04-OCT-21:19 | 23.90 | 16.65 |
November | 0.197450E+10 | 1750.84 | 19-NOV-00:12 | 5.03 | -1.2 | 0.165850E+09 | 114.01 | 10-NOV-22:10 | 5.03 | -1.2 |
December | 0.169380E+10 | 1910.64 | 04-DEC-22:57 | 3.30 | 2.03 | 0.158823E+09 | 101.71 | 15-DEC-22:10 | 14.32 | 4.61 |
Annual Sum or Average | 0.289405E+11 | 0.217286E+10 | ||||||||
Minimum of Months | 0.169380E+10 | 1531.61 | 3.30 | -1.2 | 0.148680E+09 | 101.71 | 4.90 | -1.3 | ||
Maximum of Months | 0.329969E+10 | 2140.18 | 33.90 | 19.12 | 0.204348E+09 | 120.46 | 29.40 | 18.64 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107216E+10 | 1013.63 | 01-JAN-00:45 | 6.70 | 0.39 | 0.119642E+09 | 76.17 | 03-JAN-22:30 | 11.70 | 5.76 |
February | 0.103940E+10 | 1075.62 | 24-FEB-02:31 | 5.37 | 2.12 | 0.110465E+09 | 78.85 | 07-FEB-23:10 | 5.37 | 2.12 |
March | 0.125007E+10 | 1089.22 | 13-MAR-05:18 | 5.20 | 1.53 | 0.125995E+09 | 81.30 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.144352E+10 | 1057.93 | 11-APR-01:57 | 6.10 | 0.60 | 0.133177E+09 | 89.30 | 21-APR-21:40 | 24.60 | 9.22 |
May | 0.168789E+10 | 870.37 | 02-MAY-04:55 | 10.00 | 4.04 | 0.148618E+09 | 92.66 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.186188E+10 | 1134.98 | 15-JUN-18:40 | 35.37 | 14.55 | 0.151115E+09 | 92.66 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.192813E+10 | 1120.90 | 03-JUL-18:30 | 34.45 | 19.49 | 0.155816E+09 | 92.66 | 05-JUL-21:00 | 27.80 | 17.53 |
August | 0.184344E+10 | 1068.15 | 07-AUG-21:00 | 31.70 | 16.85 | 0.154659E+09 | 92.66 | 07-AUG-21:00 | 29.00 | 17.81 |
September | 0.167548E+10 | 896.15 | 25-SEP-05:25 | 9.45 | 8.52 | 0.145658E+09 | 92.66 | 20-SEP-21:00 | 9.45 | 8.52 |
October | 0.153954E+10 | 964.98 | 25-OCT-02:12 | 8.67 | 6.39 | 0.140295E+09 | 92.21 | 05-OCT-21:40 | 8.67 | 6.39 |
November | 0.121904E+10 | 1126.11 | 19-NOV-00:12 | 5.03 | -1.2 | 0.122690E+09 | 83.63 | 09-NOV-22:30 | 5.03 | -1.2 |
December | 0.945616E+09 | 1233.58 | 04-DEC-22:57 | 3.30 | 2.03 | 0.118670E+09 | 74.63 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.175062E+11 | 0.162680E+10 | ||||||||
Minimum of Months | 0.945616E+09 | 870.37 | 3.30 | -1.2 | 0.110465E+09 | 74.63 | 5.03 | -1.2 | ||
Maximum of Months | 0.192813E+10 | 1233.58 | 35.37 | 19.49 | 0.155816E+09 | 92.66 | 29.00 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490470E+11 | 51298.64 | 26-JAN-21:56 | 3.90 | -2.9 | 0.612201E+09 | 503.74 | 23-JAN-22:49 | 3.90 | -2.9 |
February | 0.448746E+11 | 51911.36 | 08-FEB-21:57 | 3.30 | 0.16 | 0.553860E+09 | 507.50 | 17-FEB-00:30 | 5.55 | 1.70 |
March | 0.503939E+11 | 53400.24 | 01-MAR-20:46 | 1.88 | -2.8 | 0.616150E+09 | 481.00 | 28-MAR-21:30 | 4.45 | 1.48 |
April | 0.502532E+11 | 41474.31 | 13-APR-06:34 | 6.83 | 0.43 | 0.597231E+09 | 489.02 | 11-APR-04:49 | 6.83 | 0.43 |
May | 0.531345E+11 | 39149.23 | 30-MAY-20:00 | 28.90 | 14.28 | 0.619538E+09 | 381.76 | 23-MAY-21:10 | 28.90 | 14.28 |
June | 0.524559E+11 | 39542.73 | 15-JUN-20:00 | 33.90 | 14.00 | 0.602204E+09 | 381.83 | 27-JUN-21:10 | 28.62 | 16.18 |
July | 0.539370E+11 | 39478.74 | 03-JUL-20:00 | 28.30 | 19.12 | 0.619934E+09 | 381.84 | 28-JUL-21:10 | 29.03 | 16.95 |
August | 0.538369E+11 | 39419.37 | 04-AUG-20:00 | 33.30 | 17.89 | 0.620880E+09 | 381.85 | 25-AUG-21:10 | 27.62 | 14.77 |
September | 0.515226E+11 | 39080.14 | 20-SEP-20:00 | 25.60 | 15.27 | 0.598396E+09 | 381.87 | 19-SEP-21:10 | 25.60 | 15.27 |
October | 0.517488E+11 | 38852.35 | 05-OCT-20:00 | 23.90 | 16.65 | 0.614338E+09 | 381.82 | 31-OCT-21:10 | 10.60 | 4.71 |
November | 0.484679E+11 | 48282.93 | 26-NOV-20:43 | 3.48 | 0.29 | 0.592891E+09 | 450.80 | 22-NOV-05:40 | 3.48 | 0.29 |
December | 0.486666E+11 | 53210.38 | 04-DEC-22:57 | 3.30 | 2.03 | 0.612686E+09 | 503.77 | 12-DEC-22:40 | 6.70 | 3.06 |
Annual Sum or Average | 0.608339E+12 | 0.726031E+10 | ||||||||
Minimum of Months | 0.448746E+11 | 38852.35 | 1.88 | -2.9 | 0.553860E+09 | 381.76 | 3.48 | -2.9 | ||
Maximum of Months | 0.539370E+11 | 53400.24 | 33.90 | 19.12 | 0.620880E+09 | 507.50 | 29.03 | 16.95 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170836E+11 | 17062.08 | 23-JAN-02:07 | 4.72 | 3.22 | 0.103428E+11 | 6872.83 | 19-JAN-23:30 | 4.72 | 3.22 |
February | 0.159514E+11 | 18099.81 | 24-FEB-03:04 | 4.90 | 1.74 | 0.946091E+10 | 7234.07 | 22-FEB-03:20 | 4.90 | 1.74 |
March | 0.174365E+11 | 17061.43 | 13-MAR-03:12 | 5.53 | 2.27 | 0.105771E+11 | 7073.17 | 06-MAR-02:00 | 5.53 | 2.27 |
April | 0.187495E+11 | 16483.56 | 13-APR-04:53 | 5.00 | -1.0 | 0.104340E+11 | 6957.29 | 11-APR-04:49 | 5.00 | -1.0 |
May | 0.206651E+11 | 11633.06 | 19-MAY-21:10 | 29.90 | 13.55 | 0.108880E+11 | 6464.95 | 02-MAY-01:19 | 29.90 | 13.55 |
June | 0.220592E+11 | 12253.00 | 15-JUN-21:10 | 32.57 | 13.55 | 0.106203E+11 | 6462.68 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.229214E+11 | 12166.27 | 25-JUL-21:10 | 31.42 | 17.57 | 0.109401E+11 | 6462.60 | 19-JUL-22:10 | 31.42 | 17.57 |
August | 0.231594E+11 | 12596.11 | 07-AUG-21:10 | 31.25 | 17.07 | 0.109799E+11 | 6462.72 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.228423E+11 | 12367.29 | 19-SEP-15:03 | 33.40 | 16.39 | 0.106116E+11 | 6462.78 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.220381E+11 | 18542.33 | 07-OCT-02:00 | 10.60 | 9.03 | 0.108549E+11 | 6536.02 | 24-OCT-01:30 | 9.40 | 5.38 |
November | 0.186220E+11 | 17341.03 | 20-NOV-04:26 | 5.30 | -1.0 | 0.102146E+11 | 6948.05 | 22-NOV-05:40 | 5.73 | 0.24 |
December | 0.165381E+11 | 19216.83 | 07-DEC-00:14 | 4.63 | 0.01 | 0.102054E+11 | 6851.92 | 07-DEC-23:00 | 4.40 | 1.20 |
Annual Sum or Average | 0.238067E+12 | 0.126130E+12 | ||||||||
Minimum of Months | 0.159514E+11 | 11633.06 | 4.63 | -1.0 | 0.946091E+10 | 6462.60 | 4.40 | -1.0 | ||
Maximum of Months | 0.231594E+11 | 19216.83 | 33.40 | 17.57 | 0.109799E+11 | 7234.07 | 31.42 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560889E+11 | 63110.92 | 04-JAN-22:28 | 4.70 | -1.4 | 0.313869E+11 | 19924.12 | 19-JAN-23:30 | 5.00 | 3.16 |
February | 0.520840E+11 | 62706.19 | 24-FEB-03:04 | 4.90 | 1.74 | 0.285696E+11 | 20587.92 | 22-FEB-03:20 | 4.90 | 1.74 |
March | 0.588164E+11 | 66022.44 | 06-MAR-07:35 | 7.97 | 2.35 | 0.318466E+11 | 20546.39 | 17-MAR-04:10 | 5.32 | -0.8 |
April | 0.636687E+11 | 61759.21 | 11-APR-04:41 | 5.10 | 0.59 | 0.311595E+11 | 20499.00 | 11-APR-04:49 | 5.10 | 0.59 |
May | 0.717518E+11 | 44004.44 | 02-MAY-05:18 | 9.80 | 4.02 | 0.324075E+11 | 19310.94 | 06-MAY-04:49 | 11.05 | 2.59 |
June | 0.756044E+11 | 43231.95 | 15-JUN-21:10 | 32.57 | 13.55 | 0.315661E+11 | 19186.08 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.784733E+11 | 42831.13 | 26-JUL-21:10 | 28.62 | 18.19 | 0.325142E+11 | 19186.02 | 19-JUL-22:10 | 28.62 | 18.19 |
August | 0.778436E+11 | 43606.99 | 07-AUG-21:10 | 31.25 | 17.07 | 0.326561E+11 | 19186.16 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.740145E+11 | 41590.68 | 21-SEP-21:10 | 26.10 | 17.46 | 0.315532E+11 | 19186.27 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.701391E+11 | 63206.91 | 25-OCT-05:20 | 7.03 | 5.37 | 0.324257E+11 | 19828.78 | 25-OCT-03:20 | 7.03 | 5.37 |
November | 0.592802E+11 | 63254.88 | 25-NOV-02:28 | 5.85 | 3.25 | 0.308940E+11 | 20281.67 | 20-NOV-00:20 | 5.85 | 3.25 |
December | 0.547567E+11 | 66114.52 | 07-DEC-00:14 | 4.63 | 0.01 | 0.311349E+11 | 19923.38 | 07-DEC-23:00 | 4.40 | 1.20 |
Annual Sum or Average | 0.792522E+12 | 0.378114E+12 | ||||||||
Minimum of Months | 0.520840E+11 | 41590.68 | 4.63 | -1.4 | 0.285696E+11 | 19186.02 | 4.40 | -0.8 | ||
Maximum of Months | 0.784733E+11 | 66114.52 | 32.57 | 18.19 | 0.326561E+11 | 20587.92 | 28.62 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262035E+09 | 3650.42 | 12-JAN-16:01 | 18.72 | 10.12 | 96384643.48 | 56.69 | 17-JAN-02:49 | 6.20 | 4.72 |
February | 0.340494E+09 | 3728.68 | 20-FEB-16:01 | 23.12 | 8.59 | 88833680.56 | 68.11 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.555253E+09 | 3741.53 | 13-MAR-19:41 | 12.35 | 4.81 | 0.101145E+09 | 73.41 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.137667E+10 | 4055.40 | 06-APR-18:11 | 14.63 | 6.39 | 99434675.50 | 76.84 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.213027E+10 | 4021.24 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101910E+09 | 80.04 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.265916E+10 | 3991.00 | 14-JUN-08:11 | 27.93 | 12.20 | 98044657.09 | 80.36 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.264832E+10 | 3529.67 | 25-JUL-06:51 | 25.60 | 18.41 | 0.101429E+09 | 76.71 | 21-JUL-21:00 | 25.60 | 18.41 |
August | 0.247819E+10 | 3645.88 | 26-AUG-08:11 | 27.07 | 15.12 | 0.101999E+09 | 82.02 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.219972E+10 | 4007.23 | 29-SEP-21:51 | 19.40 | 9.20 | 0.100412E+09 | 80.86 | 13-SEP-21:19 | 19.40 | 9.20 |
October | 0.140924E+10 | 3957.13 | 29-OCT-21:51 | 17.80 | 9.05 | 0.105511E+09 | 84.37 | 05-OCT-21:10 | 17.80 | 9.05 |
November | 0.593085E+09 | 3736.59 | 09-NOV-16:01 | 23.22 | 12.98 | 96051543.40 | 74.22 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 0.186974E+09 | 3614.47 | 16-DEC-16:01 | 14.72 | 4.08 | 95935240.51 | 56.69 | 21-DEC-22:10 | 4.32 | 0.15 |
Annual Sum or Average | 0.168394E+11 | 0.118709E+10 | ||||||||
Minimum of Months | 0.186974E+09 | 3529.67 | 12.35 | 4.08 | 88833680.56 | 56.69 | 4.32 | 0.15 | ||
Maximum of Months | 0.265916E+10 | 4055.40 | 27.93 | 18.41 | 0.105511E+09 | 84.37 | 27.07 | 18.41 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105321E+09 | 3500.35 | 12-JAN-16:01 | 18.72 | 10.12 | 94476850.26 | 56.69 | 14-JAN-03:09 | 8.90 | 3.51 |
February | 0.163151E+09 | 3656.80 | 20-FEB-16:01 | 23.12 | 8.59 | 86872858.16 | 63.75 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.363762E+09 | 3658.04 | 16-MAR-15:01 | 22.70 | 8.66 | 99362123.81 | 70.03 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.121174E+10 | 3983.72 | 06-APR-18:11 | 14.63 | 6.39 | 98789029.55 | 75.81 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.208216E+10 | 4004.62 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101865E+09 | 80.33 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.266819E+10 | 4009.12 | 14-JUN-08:11 | 27.93 | 12.20 | 98166842.72 | 80.33 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.263238E+10 | 3522.88 | 25-JUL-06:51 | 25.60 | 18.41 | 0.101514E+09 | 76.68 | 21-JUL-21:00 | 25.60 | 18.41 |
August | 0.235032E+10 | 3613.61 | 26-AUG-08:11 | 27.07 | 15.12 | 0.101923E+09 | 81.16 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.189085E+10 | 3889.01 | 29-SEP-21:51 | 19.40 | 9.20 | 99829831.60 | 79.74 | 13-SEP-21:10 | 19.40 | 9.20 |
October | 0.102606E+10 | 3755.66 | 29-OCT-21:51 | 17.80 | 9.05 | 0.103501E+09 | 81.79 | 05-OCT-21:10 | 17.80 | 9.05 |
November | 0.262263E+09 | 3668.30 | 09-NOV-16:01 | 23.22 | 12.98 | 94024814.32 | 69.51 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 77027515.63 | 3417.32 | 16-DEC-16:01 | 14.72 | 4.08 | 94009119.51 | 56.69 | 21-DEC-22:10 | 4.32 | 0.15 |
Annual Sum or Average | 0.148332E+11 | 0.117433E+10 | ||||||||
Minimum of Months | 77027515.63 | 3417.32 | 14.63 | 4.08 | 86872858.16 | 56.69 | 4.32 | 0.15 | ||
Maximum of Months | 0.266819E+10 | 4009.12 | 27.93 | 18.41 | 0.103501E+09 | 81.79 | 27.07 | 18.41 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395678E+09 | 544.83 | 12-JAN-14:30 | 18.60 | 9.87 | 0.00 | 0.00 | 01-JAN-00:10 | 18.60 | 9.87 |
February | 0.376276E+09 | 525.81 | 07-FEB-13:40 | 20.20 | 9.50 | 0.00 | 0.00 | 01-FEB-00:10 | 20.20 | 9.50 |
March | 0.362188E+09 | 426.04 | 16-MAR-12:50 | 22.02 | 8.91 | 0.00 | 0.00 | 01-MAR-00:10 | 22.02 | 8.91 |
April | 0.474402E+09 | 411.80 | 04-APR-13:30 | 26.95 | 10.78 | 0.00 | 0.00 | 01-APR-00:10 | 26.95 | 10.78 |
May | 0.576736E+09 | 407.44 | 19-MAY-20:20 | 30.73 | 14.26 | 0.00 | 0.00 | 01-MAY-00:10 | 30.73 | 14.26 |
June | 0.700020E+09 | 451.29 | 15-JUN-20:20 | 33.70 | 13.91 | 0.00 | 0.00 | 01-JUN-00:10 | 33.70 | 13.91 |
July | 0.736703E+09 | 455.76 | 02-JUL-21:00 | 32.80 | 17.58 | 0.00 | 0.00 | 01-JUL-00:10 | 32.80 | 17.58 |
August | 0.744918E+09 | 473.48 | 27-AUG-13:40 | 34.40 | 16.46 | 0.00 | 0.00 | 01-AUG-00:10 | 34.40 | 16.46 |
September | 0.774963E+09 | 578.95 | 19-SEP-13:30 | 33.35 | 16.80 | 0.00 | 0.00 | 01-SEP-00:10 | 33.35 | 16.80 |
October | 0.700603E+09 | 645.38 | 22-OCT-13:20 | 25.97 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 14.61 |
November | 0.525657E+09 | 604.42 | 09-NOV-13:50 | 23.22 | 12.39 | 0.00 | 0.00 | 01-NOV-00:10 | 23.22 | 12.39 |
December | 0.354457E+09 | 462.69 | 16-DEC-13:40 | 14.63 | 4.10 | 0.00 | 0.00 | 01-DEC-00:10 | 14.63 | 4.10 |
Annual Sum or Average | 0.672260E+10 | 0.00 | ||||||||
Minimum of Months | 0.354457E+09 | 407.44 | 14.63 | 4.10 | 0.00 | 0.00 | 14.63 | 4.10 | ||
Maximum of Months | 0.774963E+09 | 645.38 | 34.40 | 17.58 | 0.00 | 0.00 | 34.40 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124084E+09 | 1223.35 | 01-JAN-09:01 | 8.17 | 5.96 | 94852900.11 | 56.69 | 03-JAN-22:10 | 12.43 | 6.06 |
February | 0.173772E+09 | 1311.54 | 21-FEB-21:31 | 14.60 | 4.38 | 86313210.15 | 66.99 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.285527E+09 | 1354.05 | 15-MAR-21:51 | 19.40 | 7.29 | 97093810.73 | 69.67 | 09-MAR-22:10 | 19.40 | 7.29 |
April | 0.536494E+09 | 1388.18 | 05-APR-21:51 | 18.30 | 8.91 | 96144919.71 | 71.98 | 05-APR-21:49 | 18.30 | 8.91 |
May | 0.794003E+09 | 1442.21 | 20-MAY-08:51 | 26.70 | 12.19 | 0.100313E+09 | 75.14 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.971803E+09 | 1440.95 | 11-JUN-08:31 | 25.53 | 11.17 | 97264916.79 | 75.43 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.987804E+09 | 1300.86 | 16-JUL-18:01 | 29.40 | 19.87 | 0.100550E+09 | 72.34 | 20-JUL-21:00 | 21.10 | 21.10 |
August | 0.881279E+09 | 1294.34 | 03-AUG-18:01 | 30.10 | 19.18 | 0.100686E+09 | 76.73 | 14-AUG-21:10 | 22.20 | 18.45 |
September | 0.700514E+09 | 1399.52 | 29-SEP-21:51 | 19.40 | 9.20 | 97776063.93 | 73.97 | 13-SEP-21:10 | 19.40 | 9.20 |
October | 0.493358E+09 | 1388.38 | 19-OCT-21:51 | 19.40 | 9.71 | 99990254.60 | 75.00 | 05-OCT-21:10 | 19.40 | 9.71 |
November | 0.208183E+09 | 1304.93 | 08-NOV-22:51 | 14.40 | 8.09 | 92673323.00 | 67.74 | 09-NOV-22:49 | 17.07 | 10.34 |
December | 0.101114E+09 | 1214.45 | 09-DEC-09:01 | 14.40 | 6.77 | 94628172.53 | 56.69 | 21-DEC-22:10 | 4.32 | 0.15 |
Annual Sum or Average | 0.625793E+10 | 0.115829E+10 | ||||||||
Minimum of Months | 0.101114E+09 | 1214.45 | 8.17 | 4.38 | 86313210.15 | 56.69 | 4.32 | 0.15 | ||
Maximum of Months | 0.987804E+09 | 1442.21 | 30.10 | 19.87 | 0.100686E+09 | 76.73 | 23.30 | 21.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259063E+09 | 3225.14 | 12-JAN-16:01 | 18.72 | 10.12 | 96344484.70 | 56.69 | 12-JAN-05:49 | 18.72 | 10.12 |
February | 0.406396E+09 | 3307.65 | 18-FEB-09:01 | 6.75 | 3.32 | 88856402.52 | 69.39 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.618517E+09 | 3287.74 | 16-MAR-15:01 | 22.70 | 8.66 | 0.100423E+09 | 71.31 | 15-MAR-21:30 | 22.70 | 8.66 |
April | 0.144169E+10 | 3918.71 | 27-APR-08:51 | 20.60 | 11.74 | 99455472.46 | 75.52 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.212127E+10 | 3948.72 | 20-MAY-08:51 | 26.70 | 12.19 | 0.103012E+09 | 76.46 | 17-MAY-21:00 | 26.70 | 12.19 |
June | 0.268467E+10 | 3943.29 | 14-JUN-08:11 | 27.93 | 12.20 | 99086646.43 | 79.39 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.267598E+10 | 3504.86 | 11-JUL-07:51 | 27.20 | 17.69 | 0.102337E+09 | 75.24 | 20-JUL-21:00 | 21.10 | 21.10 |
August | 0.249380E+10 | 3589.80 | 28-AUG-08:51 | 25.00 | 16.33 | 0.102807E+09 | 82.09 | 11-AUG-21:10 | 25.00 | 16.33 |
September | 0.216659E+10 | 3610.95 | 19-SEP-08:51 | 26.10 | 16.81 | 0.101199E+09 | 79.75 | 06-SEP-21:00 | 26.10 | 16.81 |
October | 0.136256E+10 | 3559.71 | 18-OCT-08:51 | 20.00 | 15.32 | 0.104145E+09 | 82.40 | 05-OCT-21:10 | 20.00 | 15.32 |
November | 0.580499E+09 | 3810.76 | 09-NOV-09:51 | 18.30 | 8.77 | 95880293.37 | 73.20 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 0.214304E+09 | 3216.48 | 16-DEC-09:01 | 8.48 | 2.42 | 95930666.67 | 56.69 | 01-DEC-04:30 | 8.48 | 2.42 |
Annual Sum or Average | 0.170253E+11 | 0.118948E+10 | ||||||||
Minimum of Months | 0.214304E+09 | 3216.48 | 6.75 | 2.42 | 88856402.52 | 56.69 | 8.48 | 2.42 | ||
Maximum of Months | 0.268467E+10 | 3948.72 | 27.93 | 17.69 | 0.104145E+09 | 82.40 | 26.70 | 21.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97176220.72 | 2353.55 | 04-JAN-09:02 | 8.98 | 3.34 | 94274413.09 | 56.69 | 12-JAN-05:49 | 6.10 | 3.28 |
February | 0.213001E+09 | 3209.44 | 20-FEB-09:01 | 11.23 | 4.20 | 86724960.38 | 65.18 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.424991E+09 | 3220.98 | 07-MAR-09:01 | 15.18 | 7.16 | 98615091.72 | 68.68 | 15-MAR-21:30 | 19.70 | 7.47 |
April | 0.126458E+10 | 3890.28 | 27-APR-08:51 | 20.60 | 11.74 | 98984857.83 | 74.52 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.206960E+10 | 3922.76 | 20-MAY-08:51 | 26.70 | 12.19 | 0.103003E+09 | 76.26 | 17-MAY-21:00 | 26.70 | 12.19 |
June | 0.269400E+10 | 3920.65 | 14-JUN-08:11 | 27.93 | 12.20 | 99185280.25 | 79.37 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.265995E+10 | 3493.38 | 11-JUL-07:51 | 27.20 | 17.69 | 0.102406E+09 | 75.24 | 20-JUL-21:00 | 21.10 | 21.10 |
August | 0.236342E+10 | 3565.61 | 28-AUG-08:51 | 25.00 | 16.33 | 0.102749E+09 | 81.25 | 11-AUG-21:10 | 25.00 | 16.33 |
September | 0.184922E+10 | 3543.77 | 19-SEP-08:51 | 26.10 | 16.81 | 0.100697E+09 | 77.96 | 06-SEP-21:19 | 26.10 | 16.81 |
October | 0.964903E+09 | 3455.20 | 03-OCT-08:51 | 23.30 | 15.83 | 0.102306E+09 | 79.81 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.276364E+09 | 3488.25 | 09-NOV-09:51 | 18.30 | 8.77 | 93379734.94 | 68.36 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 81140340.86 | 3009.11 | 09-DEC-09:01 | 14.40 | 6.77 | 93939098.69 | 56.69 | 19-DEC-22:19 | 2.60 | -3.4 |
Annual Sum or Average | 0.149584E+11 | 0.117626E+10 | ||||||||
Minimum of Months | 81140340.86 | 2353.55 | 8.98 | 3.34 | 86724960.38 | 56.69 | 2.60 | -3.4 | ||
Maximum of Months | 0.269400E+10 | 3922.76 | 27.93 | 17.69 | 0.103003E+09 | 81.25 | 26.70 | 21.10 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316825E+10 | 2928.11 | 02-JAN-08:55 | 4.40 | 2.61 | 0.124509E+10 | 798.18 | 04-JAN-22:49 | 4.90 | -1.3 |
February | 0.315028E+10 | 3084.72 | 24-FEB-02:31 | 5.37 | 2.12 | 0.116188E+10 | 832.40 | 22-FEB-22:00 | 5.37 | 2.12 |
March | 0.372139E+10 | 3129.01 | 13-MAR-05:18 | 5.20 | 1.53 | 0.133958E+10 | 860.86 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.421091E+10 | 3072.37 | 13-APR-05:17 | 4.63 | -1.3 | 0.140799E+10 | 917.37 | 21-APR-21:49 | 24.50 | 9.08 |
May | 0.483551E+10 | 2556.46 | 02-MAY-04:55 | 10.00 | 4.04 | 0.155104E+10 | 951.85 | 23-MAY-22:10 | 20.92 | 15.65 |
June | 0.524558E+10 | 3150.43 | 15-JUN-18:30 | 35.55 | 14.53 | 0.155878E+10 | 951.86 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.532792E+10 | 2936.42 | 26-JUL-18:15 | 33.13 | 19.73 | 0.160146E+10 | 951.86 | 05-JUL-21:00 | 33.13 | 19.73 |
August | 0.521843E+10 | 2927.41 | 07-AUG-18:20 | 33.50 | 18.31 | 0.159843E+10 | 951.85 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.491453E+10 | 2670.03 | 19-SEP-18:03 | 31.23 | 16.53 | 0.153536E+10 | 951.85 | 06-SEP-22:10 | 31.23 | 16.53 |
October | 0.453956E+10 | 2847.19 | 25-OCT-02:12 | 8.67 | 6.39 | 0.149449E+10 | 951.85 | 03-OCT-22:10 | 8.67 | 6.39 |
November | 0.365546E+10 | 3240.41 | 19-NOV-00:12 | 5.03 | -1.2 | 0.130913E+10 | 883.20 | 01-NOV-00:10 | 5.03 | -1.2 |
December | 0.294303E+10 | 3496.30 | 04-DEC-22:57 | 3.30 | 2.03 | 0.122540E+10 | 757.16 | 15-DEC-22:49 | 13.98 | 4.58 |
Annual Sum or Average | 0.509309E+11 | 0.170286E+11 | ||||||||
Minimum of Months | 0.294303E+10 | 2556.46 | 3.30 | -1.3 | 0.116188E+10 | 757.16 | 4.90 | -1.3 | ||
Maximum of Months | 0.532792E+10 | 3496.30 | 35.55 | 19.73 | 0.160146E+10 | 951.86 | 33.13 | 19.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215452E+09 | 3857.18 | 12-JAN-16:01 | 18.72 | 10.12 | 95915772.97 | 56.69 | 03-JAN-22:10 | 18.72 | 10.12 |
February | 0.287903E+09 | 3940.25 | 20-FEB-16:01 | 23.12 | 8.59 | 88550046.84 | 67.14 | 06-FEB-22:40 | 23.12 | 8.59 |
March | 0.479851E+09 | 4036.22 | 13-MAR-19:41 | 12.35 | 4.81 | 0.101097E+09 | 73.36 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.134935E+10 | 4317.85 | 06-APR-18:11 | 14.63 | 6.39 | 99280593.27 | 76.52 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.214546E+10 | 4232.78 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101574E+09 | 79.44 | 23-MAY-21:19 | 21.83 | 16.14 |
June | 0.276211E+10 | 4182.59 | 14-JUN-08:11 | 27.93 | 12.20 | 97785622.64 | 79.80 | 23-JUN-21:00 | 23.30 | 15.34 |
July | 0.275399E+10 | 3658.12 | 16-JUL-06:51 | 25.60 | 17.70 | 0.101175E+09 | 76.00 | 21-JUL-21:00 | 23.90 | 20.39 |
August | 0.254719E+10 | 3767.28 | 26-AUG-08:11 | 27.07 | 15.12 | 0.101657E+09 | 81.54 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.220660E+10 | 4192.50 | 29-SEP-21:51 | 19.40 | 9.20 | 99913912.67 | 80.10 | 13-SEP-21:30 | 19.40 | 9.20 |
October | 0.130726E+10 | 4171.05 | 29-OCT-21:51 | 17.80 | 9.05 | 0.105456E+09 | 83.71 | 05-OCT-21:10 | 17.80 | 9.05 |
November | 0.482959E+09 | 3946.90 | 09-NOV-16:01 | 23.22 | 12.98 | 95729542.02 | 73.71 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 0.154380E+09 | 3815.13 | 16-DEC-16:01 | 14.72 | 4.08 | 95462290.70 | 56.69 | 18-DEC-04:19 | 5.20 | -1.8 |
Annual Sum or Average | 0.166925E+11 | 0.118360E+10 | ||||||||
Minimum of Months | 0.154380E+09 | 3658.12 | 12.35 | 4.08 | 88550046.84 | 56.69 | 5.20 | -1.8 | ||
Maximum of Months | 0.276211E+10 | 4317.85 | 27.93 | 17.70 | 0.105456E+09 | 83.71 | 27.07 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83913247.70 | 3686.99 | 12-JAN-16:01 | 18.72 | 10.12 | 93874994.31 | 56.69 | 15-JAN-02:00 | 7.80 | 7.22 |
February | 0.132379E+09 | 3853.53 | 20-FEB-16:01 | 23.12 | 8.59 | 86389564.29 | 61.33 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.301190E+09 | 3849.78 | 16-MAR-15:01 | 22.70 | 8.66 | 99043990.54 | 69.43 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.117706E+10 | 4222.97 | 06-APR-18:11 | 14.63 | 6.39 | 98606735.65 | 75.51 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.209478E+10 | 4213.87 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101497E+09 | 79.75 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.277234E+10 | 4200.07 | 14-JUN-08:11 | 27.93 | 12.20 | 97903023.29 | 79.75 | 23-JUN-21:00 | 23.30 | 15.34 |
July | 0.273829E+10 | 3659.59 | 16-JUL-06:51 | 25.60 | 17.70 | 0.101256E+09 | 75.99 | 21-JUL-21:00 | 23.90 | 20.39 |
August | 0.241352E+10 | 3720.10 | 26-AUG-08:11 | 27.07 | 15.12 | 0.101583E+09 | 80.62 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.187985E+10 | 4057.53 | 29-SEP-21:51 | 19.40 | 9.20 | 99306862.94 | 78.94 | 13-SEP-21:19 | 19.40 | 9.20 |
October | 0.900604E+09 | 3915.57 | 29-OCT-21:51 | 17.80 | 9.05 | 0.103128E+09 | 81.10 | 05-OCT-21:10 | 17.80 | 9.05 |
November | 0.189352E+09 | 3862.88 | 09-NOV-16:01 | 23.22 | 12.98 | 93401948.86 | 68.21 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 62456844.00 | 3551.82 | 16-DEC-16:01 | 14.72 | 4.08 | 93441937.74 | 56.69 | 09-DEC-03:00 | 14.72 | 4.08 |
Annual Sum or Average | 0.147457E+11 | 0.116943E+10 | ||||||||
Minimum of Months | 62456844.00 | 3551.82 | 14.63 | 4.08 | 86389564.29 | 56.69 | 7.80 | 4.08 | ||
Maximum of Months | 0.277234E+10 | 4222.97 | 27.93 | 17.70 | 0.103128E+09 | 81.10 | 27.07 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540327E+09 | 2107.98 | 12-JAN-19:41 | 12.77 | 7.23 | 98023957.51 | 59.74 | 12-JAN-19:30 | 12.77 | 7.23 |
February | 0.526420E+09 | 2143.05 | 20-FEB-21:11 | 14.33 | 5.02 | 90373185.37 | 76.57 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.515831E+09 | 2110.06 | 14-MAR-21:01 | 13.62 | 5.68 | 0.101355E+09 | 77.50 | 14-MAR-21:10 | 13.62 | 5.68 |
April | 0.825704E+09 | 2084.00 | 04-APR-19:51 | 24.40 | 9.46 | 98461327.78 | 74.68 | 05-APR-21:40 | 18.50 | 9.00 |
May | 0.109103E+10 | 2169.35 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101100E+09 | 76.05 | 23-MAY-21:19 | 21.83 | 16.14 |
June | 0.138187E+10 | 2113.74 | 11-JUN-08:31 | 25.53 | 11.17 | 97572727.10 | 77.63 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.143883E+10 | 1891.66 | 30-JUL-08:51 | 25.60 | 19.09 | 0.101036E+09 | 74.18 | 18-JUL-21:00 | 25.60 | 19.09 |
August | 0.142867E+10 | 1963.57 | 28-AUG-08:51 | 25.00 | 16.33 | 0.101581E+09 | 80.96 | 11-AUG-21:10 | 25.00 | 16.33 |
September | 0.141048E+10 | 2193.44 | 29-SEP-21:51 | 19.40 | 9.20 | 0.100035E+09 | 79.87 | 29-SEP-21:40 | 19.40 | 9.20 |
October | 0.115189E+10 | 2284.39 | 26-OCT-21:51 | 18.30 | 8.76 | 0.106177E+09 | 88.90 | 27-OCT-21:10 | 16.23 | 10.99 |
November | 0.766694E+09 | 2310.18 | 09-NOV-09:51 | 18.30 | 8.77 | 97376814.17 | 81.44 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 0.494519E+09 | 2076.20 | 07-DEC-17:01 | 13.80 | 5.73 | 97774153.14 | 56.69 | 07-DEC-22:19 | 5.73 | 1.70 |
Annual Sum or Average | 0.115723E+11 | 0.119087E+10 | ||||||||
Minimum of Months | 0.494519E+09 | 1891.66 | 12.77 | 5.02 | 90373185.37 | 56.69 | 5.73 | 1.70 | ||
Maximum of Months | 0.143883E+10 | 2310.18 | 26.70 | 19.09 | 0.106177E+09 | 88.90 | 25.60 | 19.09 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319247E+11 | 31656.84 | 04-JAN-22:56 | 5.00 | -1.3 | 0.191047E+11 | 12598.73 | 19-JAN-23:30 | 5.00 | 3.16 |
February | 0.300526E+11 | 43481.82 | 24-FEB-05:14 | 5.20 | 0.22 | 0.173369E+11 | 13454.47 | 22-FEB-03:20 | 5.20 | 0.22 |
March | 0.350380E+11 | 32659.11 | 13-MAR-05:15 | 5.20 | 1.53 | 0.193130E+11 | 13431.68 | 17-MAR-04:10 | 5.32 | -0.8 |
April | 0.382868E+11 | 31753.83 | 18-APR-02:07 | 8.90 | 6.05 | 0.186961E+11 | 13488.78 | 11-APR-04:49 | 8.90 | 6.05 |
May | 0.431291E+11 | 27381.32 | 02-MAY-05:06 | 9.90 | 4.03 | 0.193450E+11 | 11519.98 | 06-MAY-04:49 | 11.05 | 2.59 |
June | 0.447832E+11 | 24091.47 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187605E+11 | 11364.31 | 15-JUN-21:19 | 31.83 | 13.36 |
July | 0.460001E+11 | 23907.92 | 25-JUL-21:10 | 31.42 | 17.57 | 0.193094E+11 | 11368.55 | 25-JUL-22:00 | 30.00 | 16.46 |
August | 0.449423E+11 | 24040.54 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193900E+11 | 11370.75 | 04-AUG-22:00 | 30.80 | 17.26 |
September | 0.415279E+11 | 22838.83 | 22-SEP-22:00 | 25.00 | 17.90 | 0.187066E+11 | 11349.17 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.389629E+11 | 27242.34 | 24-OCT-01:58 | 9.40 | 5.63 | 0.192814E+11 | 12467.62 | 25-OCT-03:20 | 7.57 | 5.72 |
November | 0.328325E+11 | 31662.14 | 28-NOV-23:50 | 8.30 | 3.95 | 0.185494E+11 | 12997.92 | 22-NOV-05:40 | 8.30 | 3.95 |
December | 0.310905E+11 | 38246.57 | 04-DEC-22:57 | 3.30 | 2.03 | 0.190633E+11 | 12745.90 | 06-DEC-00:40 | 5.00 | 2.61 |
Annual Sum or Average | 0.458571E+12 | 0.226856E+12 | ||||||||
Minimum of Months | 0.300526E+11 | 22838.83 | 3.30 | -1.3 | 0.173369E+11 | 11349.17 | 5.00 | -0.8 | ||
Maximum of Months | 0.460001E+11 | 43481.82 | 31.83 | 17.90 | 0.193900E+11 | 13488.78 | 31.83 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356304E+11 | 41992.50 | 23-JAN-00:03 | 5.00 | 3.64 | 0.192342E+11 | 12712.33 | 23-JAN-22:49 | 7.30 | 5.77 |
February | 0.333895E+11 | 34413.40 | 08-FEB-22:06 | 3.03 | 0.14 | 0.174242E+11 | 13572.82 | 17-FEB-00:30 | 5.55 | 1.70 |
March | 0.387258E+11 | 34605.08 | 13-MAR-05:15 | 5.20 | 1.53 | 0.193856E+11 | 13496.49 | 17-MAR-04:10 | 5.32 | -0.8 |
April | 0.415217E+11 | 33407.15 | 07-APR-05:54 | 6.10 | 2.75 | 0.187141E+11 | 13554.45 | 11-APR-04:49 | 5.10 | 0.59 |
May | 0.461039E+11 | 29358.65 | 02-MAY-05:06 | 9.90 | 4.03 | 0.193489E+11 | 11525.09 | 06-MAY-04:49 | 11.05 | 2.59 |
June | 0.474813E+11 | 25290.03 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187613E+11 | 11371.70 | 16-JUN-21:19 | 32.23 | 15.08 |
July | 0.487774E+11 | 25099.56 | 25-JUL-21:10 | 31.42 | 17.57 | 0.193102E+11 | 11369.01 | 25-JUL-22:00 | 30.00 | 16.46 |
August | 0.477417E+11 | 25222.19 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193912E+11 | 11370.77 | 04-AUG-22:00 | 30.80 | 17.26 |
September | 0.442761E+11 | 23995.52 | 22-SEP-21:10 | 25.00 | 17.90 | 0.187094E+11 | 11349.17 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.421075E+11 | 29233.22 | 07-OCT-05:08 | 10.10 | 8.79 | 0.193019E+11 | 12510.06 | 25-OCT-03:20 | 7.57 | 5.72 |
November | 0.362345E+11 | 33422.69 | 28-NOV-23:50 | 8.30 | 3.95 | 0.186321E+11 | 13088.88 | 22-NOV-05:40 | 8.30 | 3.95 |
December | 0.347800E+11 | 43390.45 | 04-DEC-22:57 | 3.30 | 2.03 | 0.192152E+11 | 12876.47 | 06-DEC-00:40 | 5.00 | 2.61 |
Annual Sum or Average | 0.496770E+12 | 0.227428E+12 | ||||||||
Minimum of Months | 0.333895E+11 | 23995.52 | 3.03 | 0.14 | 0.174242E+11 | 11349.17 | 5.00 | -0.8 | ||
Maximum of Months | 0.487774E+11 | 43390.45 | 31.83 | 17.90 | 0.193912E+11 | 13572.82 | 32.23 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497259E+11 | 39560.72 | 22-JAN-08:44 | 5.82 | 2.93 | 0.188566E+11 | 11364.80 | 14-JAN-18:49 | 5.82 | 2.93 |
February | 0.459850E+11 | 35085.38 | 18-FEB-08:18 | 5.37 | 2.49 | 0.170324E+11 | 11386.54 | 08-FEB-18:30 | 5.37 | 2.49 |
March | 0.520912E+11 | 35442.01 | 17-MAR-07:38 | 4.83 | -1.1 | 0.188665E+11 | 11319.19 | 11-MAR-18:19 | 4.83 | -1.1 |
April | 0.534104E+11 | 34813.73 | 11-APR-07:27 | 6.15 | 1.25 | 0.182593E+11 | 11319.65 | 15-APR-17:19 | 27.43 | 11.91 |
May | 0.573485E+11 | 30465.10 | 21-MAY-10:50 | 30.03 | 14.61 | 0.188711E+11 | 11319.66 | 13-MAY-17:19 | 30.03 | 14.61 |
June | 0.574544E+11 | 31041.92 | 18-JUN-10:50 | 32.62 | 16.28 | 0.182662E+11 | 11319.65 | 24-JUN-17:19 | 31.67 | 16.29 |
July | 0.593014E+11 | 31211.52 | 02-JUL-10:37 | 32.23 | 20.13 | 0.188684E+11 | 11319.66 | 15-JUL-17:19 | 32.20 | 17.96 |
August | 0.586763E+11 | 31112.27 | 06-AUG-10:33 | 31.67 | 18.03 | 0.188756E+11 | 11319.65 | 12-AUG-17:19 | 33.70 | 18.99 |
September | 0.558590E+11 | 30726.09 | 17-SEP-10:50 | 30.03 | 15.56 | 0.182612E+11 | 11320.08 | 23-SEP-17:19 | 17.80 | 17.32 |
October | 0.547609E+11 | 32799.15 | 25-OCT-06:23 | 7.25 | 5.26 | 0.188627E+11 | 11320.19 | 28-OCT-17:19 | 22.23 | 13.64 |
November | 0.496294E+11 | 36839.69 | 27-NOV-08:37 | 3.70 | -0.8 | 0.182450E+11 | 11335.81 | 25-NOV-18:10 | 3.70 | -0.8 |
December | 0.492053E+11 | 41695.71 | 31-DEC-22:29 | 3.85 | 0.22 | 0.188536E+11 | 11407.57 | 02-DEC-18:19 | 3.85 | 0.22 |
Annual Sum or Average | 0.643448E+12 | 0.222119E+12 | ||||||||
Minimum of Months | 0.459850E+11 | 30465.10 | 3.70 | -1.1 | 0.170324E+11 | 11319.19 | 3.70 | -1.1 | ||
Maximum of Months | 0.593014E+11 | 41695.71 | 32.62 | 20.13 | 0.188756E+11 | 11407.57 | 33.70 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578619E+10 | 5644.58 | 13-JAN-01:33 | 6.30 | 2.94 | 0.130235E+10 | 830.93 | 12-JAN-22:40 | 6.30 | 2.94 |
February | 0.595041E+10 | 6099.58 | 24-FEB-02:31 | 5.37 | 2.12 | 0.120853E+10 | 866.57 | 22-FEB-22:19 | 5.37 | 2.12 |
March | 0.724838E+10 | 6098.39 | 13-MAR-05:18 | 5.20 | 1.53 | 0.138464E+10 | 903.13 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.860323E+10 | 5970.43 | 11-APR-01:57 | 6.10 | 0.60 | 0.148347E+10 | 1002.96 | 21-APR-21:40 | 24.60 | 9.22 |
May | 0.102174E+11 | 5781.90 | 30-MAY-15:02 | 34.32 | 17.72 | 0.164548E+10 | 1007.39 | 17-MAY-22:10 | 34.32 | 17.72 |
June | 0.118670E+11 | 6664.01 | 15-JUN-18:03 | 35.92 | 14.47 | 0.164935E+10 | 1007.44 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.121684E+11 | 7006.87 | 03-JUL-12:50 | 36.52 | 18.58 | 0.169813E+10 | 1007.42 | 03-JUL-03:09 | 36.52 | 18.58 |
August | 0.116590E+11 | 6848.77 | 07-AUG-15:03 | 35.37 | 18.63 | 0.169278E+10 | 1007.44 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.105104E+11 | 6330.44 | 20-SEP-15:03 | 33.30 | 17.34 | 0.160720E+10 | 1007.41 | 06-SEP-21:19 | 33.30 | 17.34 |
October | 0.914182E+10 | 5866.61 | 05-OCT-15:03 | 30.68 | 17.34 | 0.154603E+10 | 1007.40 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.685963E+10 | 6311.60 | 19-NOV-00:12 | 5.03 | -1.2 | 0.133018E+10 | 922.06 | 09-NOV-22:30 | 5.03 | -1.2 |
December | 0.507490E+10 | 6185.89 | 30-DEC-10:17 | 3.87 | 0.67 | 0.128882E+10 | 807.25 | 15-DEC-22:40 | 3.87 | 0.67 |
Annual Sum or Average | 0.105087E+12 | 0.178370E+11 | ||||||||
Minimum of Months | 0.507490E+10 | 5644.58 | 3.87 | -1.2 | 0.120853E+10 | 807.25 | 3.87 | -1.2 | ||
Maximum of Months | 0.121684E+11 | 7006.87 | 36.52 | 18.63 | 0.169813E+10 | 1007.44 | 36.52 | 18.58 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 27959.01 | 158.54 | 21-FEB-02:17 | 8.87 |
March | 6140239.32 | 1389.82 | 20-MAR-03:28 | 8.85 |
April | 1174172.09 | 1246.80 | 18-APR-02:06 | 8.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 491532.98 | 1045.11 | 22-NOV-05:30 | 5.55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 7833903.40 | |||
Minimum of Months | 0.00 | 0.00 | 5.55 | |
Maximum of Months | 6140239.32 | 1389.82 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15606508.30 | 1289.65 | 14-JAN-13:48 | 8.40 |
February | 9002644.83 | 375.93 | 26-FEB-04:56 | 8.30 |
March | 12110405.43 | 356.71 | 20-MAR-03:28 | 8.85 |
April | 2966353.13 | 351.99 | 23-APR-04:19 | 8.53 |
May | 35578.05 | 154.28 | 02-MAY-05:04 | 9.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 345706.86 | 278.52 | 25-OCT-06:48 | 7.62 |
November | 10385884.65 | 1304.32 | 27-NOV-08:38 | 3.70 |
December | 39374695.49 | 775.75 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 89827776.75 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 39374695.49 | 1304.32 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 168197.76 | 110.77 | 16-JAN-04:14 | 8.30 |
February | 56286.56 | 106.22 | 02-FEB-12:14 | 7.07 |
March | 45105.98 | 64.17 | 02-MAR-10:21 | 4.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 309881.53 | 198.14 | 22-NOV-05:30 | 5.55 |
December | 409438.51 | 99.74 | 28-DEC-11:14 | 4.83 |
Annual Sum or Average | 988910.33 | |||
Minimum of Months | 0.00 | 0.00 | 4.20 | |
Maximum of Months | 409438.51 | 198.14 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5950998.99 | 222.64 | 21-JAN-01:38 | 5.73 |
February | 2974702.07 | 212.17 | 02-FEB-12:14 | 7.07 |
March | 2847187.76 | 195.59 | 03-MAR-01:08 | 7.12 |
April | 144250.77 | 94.45 | 12-APR-01:47 | 7.48 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 10581.32 | 26.11 | 25-OCT-06:48 | 7.62 |
November | 2456713.08 | 364.02 | 22-NOV-05:30 | 5.55 |
December | 5960017.88 | 717.64 | 30-DEC-10:18 | 3.87 |
Annual Sum or Average | 20344451.88 | |||
Minimum of Months | 0.00 | 0.00 | 3.87 | |
Maximum of Months | 5960017.88 | 717.64 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5841127.59 | 173.08 | 21-JAN-01:38 | 5.73 |
February | 3253182.28 | 405.56 | 10-FEB-10:17 | 7.43 |
March | 3269596.48 | 150.29 | 03-MAR-01:08 | 7.12 |
April | 360894.28 | 91.95 | 12-APR-01:47 | 7.48 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 42197.39 | 58.13 | 25-OCT-06:48 | 7.62 |
November | 2668887.73 | 490.43 | 27-NOV-08:38 | 3.70 |
December | 5585711.10 | 495.18 | 30-DEC-10:18 | 3.87 |
Annual Sum or Average | 21021596.85 | |||
Minimum of Months | 0.00 | 0.00 | 3.70 | |
Maximum of Months | 5841127.59 | 495.18 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80324.93 | 810.05 | 14-JAN-02:57 | 8.90 |
February | 319247.05 | 1150.36 | 24-FEB-04:28 | 5.00 |
March | 394954.09 | 1028.12 | 13-MAR-03:07 | 5.82 |
April | 108486.89 | 590.02 | 11-APR-02:29 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 411571.70 | 1010.41 | 04-NOV-03:38 | 8.50 |
December | 231618.58 | 987.24 | 01-DEC-04:15 | 5.40 |
Annual Sum or Average | 1546203.24 | |||
Minimum of Months | 0.00 | 0.00 | 5.00 | |
Maximum of Months | 411571.70 | 1150.36 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2020490.02 | 880.33 | 17-JAN-09:18 | 6.87 |
February | 44112.73 | 414.83 | 26-FEB-08:37 | 7.60 |
March | 337601.04 | 755.18 | 24-MAR-08:04 | 6.05 |
April | 209101.45 | 450.20 | 11-APR-08:34 | 7.43 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 27837.23 | 164.92 | 25-OCT-06:48 | 7.62 |
November | 2054102.15 | 1111.54 | 26-NOV-18:03 | 5.92 |
December | 1418573.99 | 761.47 | 02-DEC-16:57 | 7.20 |
Annual Sum or Average | 6111818.60 | |||
Minimum of Months | 0.00 | 0.00 | 5.92 | |
Maximum of Months | 2054102.15 | 1111.54 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 8904.76 | 148.41 | 10-FEB-09:53 | 6.70 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 2353209.78 | 3371.04 | 19-NOV-00:37 | 4.47 |
December | 242772.31 | 479.31 | 03-DEC-17:40 | 7.40 |
Annual Sum or Average | 2604886.85 | |||
Minimum of Months | 0.00 | 0.00 | 4.47 | |
Maximum of Months | 2353209.78 | 3371.04 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310241E+09 | 1466.55 | 14-JAN-16:11 | 7.97 |
February | 0.179986E+09 | 1416.06 | 24-FEB-09:01 | 5.87 |
March | 80120639.37 | 1424.05 | 24-MAR-08:61 | 6.05 |
April | 5769894.74 | 1358.45 | 02-APR-08:53 | 22.00 |
May | 1261759.45 | 1194.06 | 10-MAY-08:53 | 21.70 |
June | 385715.03 | 770.77 | 04-JUN-08:54 | 26.10 |
July | 481026.91 | 833.04 | 28-JUL-06:54 | 25.60 |
August | 768204.67 | 826.72 | 17-AUG-21:54 | 22.80 |
September | 899695.38 | 772.26 | 24-SEP-08:54 | 21.10 |
October | 1746997.15 | 1031.86 | 17-OCT-08:53 | 18.30 |
November | 0.131068E+09 | 1481.68 | 28-NOV-09:01 | 4.18 |
December | 0.433387E+09 | 1467.02 | 02-DEC-19:11 | 4.80 |
Annual Sum or Average | 0.114612E+10 | |||
Minimum of Months | 385715.03 | 770.77 | 4.18 | |
Maximum of Months | 0.433387E+09 | 1481.68 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542967E+09 | 1477.59 | 10-JAN-09:11 | 5.20 |
February | 0.315966E+09 | 1455.09 | 02-FEB-19:01 | 7.43 |
March | 0.130922E+09 | 1447.62 | 01-MAR-19:01 | 4.13 |
April | 7883341.29 | 1380.38 | 11-APR-08:61 | 6.88 |
May | 1266466.16 | 1182.25 | 10-MAY-08:53 | 21.70 |
June | 520134.35 | 874.73 | 04-JUN-08:54 | 26.10 |
July | 340680.09 | 553.92 | 19-JUL-08:54 | 21.70 |
August | 840561.28 | 1028.12 | 17-AUG-21:54 | 22.80 |
September | 1015688.52 | 1145.72 | 29-SEP-08:53 | 23.30 |
October | 2758454.90 | 1334.79 | 31-OCT-19:13 | 12.60 |
November | 0.226527E+09 | 1500.29 | 28-NOV-09:01 | 4.18 |
December | 0.722863E+09 | 1493.19 | 27-DEC-19:01 | 4.90 |
Annual Sum or Average | 0.195387E+10 | |||
Minimum of Months | 340680.09 | 553.92 | 4.13 | |
Maximum of Months | 0.722863E+09 | 1500.29 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34040776.78 | 444.14 | 16-JAN-09:02 | 8.40 |
February | 20647157.30 | 447.77 | 22-FEB-20:33 | 15.73 |
March | 5091885.54 | 448.56 | 08-MAR-09:03 | 12.15 |
April | 1448447.97 | 428.97 | 26-APR-08:53 | 18.30 |
May | 727973.64 | 435.97 | 05-MAY-08:53 | 17.80 |
June | 125447.69 | 367.38 | 13-JUN-08:34 | 26.87 |
July | 125946.48 | 190.70 | 21-JUL-21:55 | 23.90 |
August | 308547.29 | 303.50 | 24-AUG-08:54 | 21.10 |
September | 514669.55 | 374.59 | 30-SEP-18:04 | 24.45 |
October | 971389.32 | 445.64 | 27-OCT-08:03 | 14.68 |
November | 9480862.98 | 440.95 | 27-NOV-16:01 | 8.22 |
December | 64091090.70 | 446.08 | 09-DEC-09:03 | 14.40 |
Annual Sum or Average | 0.137574E+09 | |||
Minimum of Months | 125447.69 | 190.70 | 8.22 | |
Maximum of Months | 64091090.70 | 448.56 | 26.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330925E+09 | 1418.14 | 14-JAN-16:11 | 7.97 |
February | 0.173154E+09 | 1383.63 | 02-FEB-19:01 | 7.43 |
March | 87778246.25 | 1388.60 | 01-MAR-19:01 | 4.13 |
April | 5607553.19 | 1257.25 | 06-APR-18:13 | 14.63 |
May | 537752.48 | 913.36 | 06-MAY-21:54 | 19.40 |
June | 22062.67 | 126.18 | 22-JUN-21:54 | 23.30 |
July | 86430.87 | 444.56 | 19-JUL-21:54 | 22.20 |
August | 284302.67 | 682.27 | 24-AUG-08:54 | 21.10 |
September | 208712.41 | 537.17 | 28-SEP-21:54 | 24.40 |
October | 1647691.88 | 825.40 | 09-OCT-21:54 | 18.30 |
November | 0.145861E+09 | 1435.55 | 27-NOV-19:01 | 5.40 |
December | 0.443049E+09 | 1438.33 | 03-DEC-19:01 | 6.02 |
Annual Sum or Average | 0.118916E+10 | |||
Minimum of Months | 22062.67 | 126.18 | 4.13 | |
Maximum of Months | 0.443049E+09 | 1438.33 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552720E+09 | 1426.81 | 14-JAN-16:11 | 7.97 |
February | 0.285465E+09 | 1430.09 | 02-FEB-19:01 | 7.43 |
March | 0.138087E+09 | 1419.17 | 01-MAR-19:01 | 4.13 |
April | 8365800.25 | 1211.72 | 11-APR-15:03 | 16.78 |
May | 609400.42 | 964.21 | 07-MAY-21:54 | 20.60 |
June | 28601.77 | 251.55 | 19-JUN-18:55 | 27.20 |
July | 82879.30 | 461.67 | 19-JUL-21:54 | 22.20 |
August | 330872.60 | 659.35 | 24-AUG-08:54 | 21.10 |
September | 309541.25 | 443.00 | 02-SEP-21:54 | 22.80 |
October | 4121769.39 | 1286.69 | 30-OCT-21:53 | 20.00 |
November | 0.239681E+09 | 1458.61 | 27-NOV-16:01 | 8.22 |
December | 0.709655E+09 | 1464.73 | 19-DEC-19:01 | 4.90 |
Annual Sum or Average | 0.193946E+10 | |||
Minimum of Months | 28601.77 | 251.55 | 4.13 | |
Maximum of Months | 0.709655E+09 | 1464.73 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16117250.23 | 519.34 | 17-JAN-10:04 | 7.48 |
February | 6781454.24 | 386.44 | 02-FEB-12:14 | 7.07 |
March | 6036995.38 | 370.34 | 03-MAR-01:08 | 7.12 |
April | 271448.73 | 140.22 | 18-APR-02:06 | 8.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 27469.72 | 74.04 | 25-OCT-06:48 | 7.62 |
November | 5219368.70 | 646.85 | 22-NOV-05:30 | 5.55 |
December | 15269454.08 | 811.98 | 02-DEC-18:56 | 5.00 |
Annual Sum or Average | 49723441.09 | |||
Minimum of Months | 0.00 | 0.00 | 5.00 | |
Maximum of Months | 16117250.23 | 811.98 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582468E+09 | 1762.74 | 14-JAN-16:11 | 7.97 |
February | 0.365330E+09 | 1710.11 | 24-FEB-09:01 | 5.87 |
March | 0.198831E+09 | 1722.74 | 24-MAR-08:61 | 6.05 |
April | 23871921.43 | 1660.25 | 11-APR-08:61 | 6.88 |
May | 1758629.79 | 1332.35 | 11-MAY-08:53 | 23.30 |
June | 387039.61 | 740.00 | 10-JUN-06:54 | 24.40 |
July | 639157.39 | 841.03 | 04-JUL-08:24 | 25.55 |
August | 849031.81 | 1024.80 | 17-AUG-21:54 | 22.80 |
September | 1004077.40 | 1003.42 | 27-SEP-08:53 | 21.10 |
October | 6043591.43 | 1178.16 | 18-OCT-08:53 | 20.00 |
November | 0.288647E+09 | 1767.50 | 28-NOV-09:01 | 4.18 |
December | 0.756720E+09 | 1763.04 | 02-DEC-19:11 | 4.80 |
Annual Sum or Average | 0.222655E+10 | |||
Minimum of Months | 387039.61 | 740.00 | 4.18 | |
Maximum of Months | 0.756720E+09 | 1767.50 | 25.55 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908125E+09 | 1766.70 | 14-JAN-16:11 | 7.97 |
February | 0.571012E+09 | 1752.33 | 15-FEB-09:01 | 7.57 |
March | 0.291223E+09 | 1732.60 | 01-MAR-19:01 | 4.13 |
April | 31299302.93 | 1664.09 | 11-APR-08:61 | 6.88 |
May | 1772106.84 | 1336.17 | 11-MAY-08:53 | 23.30 |
June | 322871.12 | 710.09 | 04-JUN-08:54 | 26.10 |
July | 529625.41 | 796.13 | 12-JUL-08:14 | 26.33 |
August | 905665.92 | 1171.39 | 30-AUG-08:53 | 23.30 |
September | 1068001.66 | 1066.50 | 30-SEP-21:53 | 17.20 |
October | 13432706.49 | 1607.25 | 25-OCT-08:62 | 11.15 |
November | 0.467409E+09 | 1779.12 | 26-NOV-19:01 | 4.90 |
December | 0.113984E+10 | 1783.10 | 03-DEC-19:01 | 6.02 |
Annual Sum or Average | 0.342693E+10 | |||
Minimum of Months | 322871.12 | 710.09 | 4.13 | |
Maximum of Months | 0.113984E+10 | 1783.10 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85754607.78 | 884.01 | 15-JAN-19:01 | 9.40 |
February | 53033668.23 | 843.73 | 13-FEB-16:02 | 12.30 |
March | 34033169.74 | 882.08 | 24-MAR-08:61 | 6.05 |
April | 4503918.54 | 866.05 | 06-APR-18:13 | 14.63 |
May | 1002468.72 | 804.24 | 04-MAY-21:54 | 20.60 |
June | 249876.50 | 476.57 | 23-JUN-21:54 | 23.30 |
July | 290383.68 | 488.32 | 06-JUL-08:04 | 26.38 |
August | 383081.35 | 463.10 | 10-AUG-08:04 | 25.78 |
September | 252354.59 | 443.12 | 02-SEP-21:54 | 22.80 |
October | 637300.72 | 420.87 | 07-OCT-20:44 | 15.10 |
November | 45512333.99 | 893.44 | 28-NOV-09:01 | 4.18 |
December | 0.131024E+09 | 891.97 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.356677E+09 | |||
Minimum of Months | 249876.50 | 420.87 | 2.12 | |
Maximum of Months | 0.131024E+09 | 893.44 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40706751.28 | 1036.25 | 21-JAN-01:38 | 5.73 |
February | 25618170.94 | 847.28 | 26-FEB-04:56 | 8.30 |
March | 22009195.38 | 849.48 | 03-MAR-01:08 | 7.12 |
April | 3179031.79 | 573.98 | 12-APR-01:47 | 7.48 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 488790.70 | 501.04 | 25-OCT-06:48 | 7.62 |
November | 18547839.44 | 3091.45 | 27-NOV-08:38 | 3.70 |
December | 60736611.90 | 2413.82 | 02-DEC-18:56 | 5.00 |
Annual Sum or Average | 0.171286E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.70 | |
Maximum of Months | 60736611.90 | 3091.45 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160421E+11 | 15451.75 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.144845E+11 | 15451.75 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.160915E+11 | 15451.75 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.154982E+11 | 15451.75 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.160699E+11 | 15451.75 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.155692E+11 | 15451.75 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.159988E+11 | 15451.75 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.160977E+11 | 15451.75 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.155043E+11 | 15451.75 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.160359E+11 | 15451.75 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.155569E+11 | 15451.75 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.159988E+11 | 15451.75 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.188948E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.144845E+11 | 15451.75 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.160977E+11 | 15451.75 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743719E+09 | 716.35 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.671510E+09 | 716.35 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.746011E+09 | 716.35 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.718503E+09 | 716.35 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.745008E+09 | 716.35 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.721798E+09 | 716.35 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.741713E+09 | 716.35 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.746298E+09 | 716.35 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.718790E+09 | 716.35 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.743432E+09 | 716.35 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.721225E+09 | 716.35 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.741713E+09 | 716.35 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.875972E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.671510E+09 | 716.35 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.746298E+09 | 716.35 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861229E+09 | 829.54 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.777612E+09 | 829.54 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.863884E+09 | 829.54 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.832029E+09 | 829.54 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.862722E+09 | 829.54 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.835845E+09 | 829.54 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.858907E+09 | 829.54 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.864216E+09 | 829.54 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.832361E+09 | 829.54 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.860897E+09 | 829.54 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.835182E+09 | 829.54 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.858907E+09 | 829.54 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.101438E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.777612E+09 | 829.54 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.864216E+09 | 829.54 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693793E+09 | 668.27 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.626432E+09 | 668.27 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.695932E+09 | 668.27 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.670270E+09 | 668.27 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.694996E+09 | 668.27 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.673344E+09 | 668.27 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.691922E+09 | 668.27 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.696199E+09 | 668.27 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.670538E+09 | 668.27 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.693526E+09 | 668.27 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.672810E+09 | 668.27 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.691922E+09 | 668.27 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.817168E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.626432E+09 | 668.27 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.696199E+09 | 668.27 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351983E+09 | 339.04 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.317809E+09 | 339.04 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.353068E+09 | 339.04 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.340049E+09 | 339.04 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.352593E+09 | 339.04 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.341609E+09 | 339.04 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.351034E+09 | 339.04 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.353204E+09 | 339.04 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.340185E+09 | 339.04 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.351847E+09 | 339.04 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.341337E+09 | 339.04 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.351034E+09 | 339.04 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.414575E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.317809E+09 | 339.04 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.353204E+09 | 339.04 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.152522E+10 | 1957.67 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.133028E+10 | 1957.67 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.141594E+10 | 1957.67 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.128930E+10 | 1957.67 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.129357E+10 | 1957.67 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.121590E+10 | 1957.67 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.125966E+10 | 1957.67 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.133919E+10 | 1957.67 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.133401E+10 | 1957.67 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.147719E+10 | 1957.67 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.142841E+10 | 1957.67 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.151280E+10 | 1957.67 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.164215E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.121590E+10 | 1957.67 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.152522E+10 | 1957.67 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.849469E+10 | 8554.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.763825E+10 | 8554.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.845797E+10 | 8554.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.809562E+10 | 8554.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.836949E+10 | 8554.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.809727E+10 | 8554.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.833275E+10 | 8554.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.841342E+10 | 8554.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.813725E+10 | 8554.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.845840E+10 | 8554.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.819767E+10 | 8554.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.846093E+10 | 8554.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.991537E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.763825E+10 | 8554.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.849469E+10 | 8554.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146022E+09 | 132.12 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.131872E+09 | 132.12 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.144861E+09 | 132.12 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.141479E+09 | 132.12 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.145441E+09 | 132.12 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.140357E+09 | 132.12 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.146583E+09 | 132.12 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.144861E+09 | 132.12 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.141518E+09 | 132.12 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.146003E+09 | 132.12 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.140918E+09 | 132.12 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.146602E+09 | 132.12 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.171652E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.131872E+09 | 132.12 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.146602E+09 | 132.12 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232348E+09 | 210.22 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.209833E+09 | 210.22 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.230501E+09 | 210.22 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.225120E+09 | 210.22 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.231424E+09 | 210.22 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.223334E+09 | 210.22 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.233241E+09 | 210.22 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.230501E+09 | 210.22 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.225181E+09 | 210.22 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.232318E+09 | 210.22 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.224227E+09 | 210.22 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.233271E+09 | 210.22 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.273130E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.209833E+09 | 210.22 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.233271E+09 | 210.22 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232321E+09 | 210.20 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.209808E+09 | 210.20 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.230474E+09 | 210.20 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.225094E+09 | 210.20 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.231397E+09 | 210.20 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.223308E+09 | 210.20 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.233213E+09 | 210.20 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.230474E+09 | 210.20 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.225154E+09 | 210.20 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.232290E+09 | 210.20 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.224201E+09 | 210.20 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.233244E+09 | 210.20 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.273098E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.209808E+09 | 210.20 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.233244E+09 | 210.20 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146062E+09 | 132.15 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.131908E+09 | 132.15 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.144901E+09 | 132.15 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.141518E+09 | 132.15 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.145481E+09 | 132.15 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.140395E+09 | 132.15 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.146623E+09 | 132.15 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.144901E+09 | 132.15 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.141556E+09 | 132.15 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.146043E+09 | 132.15 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.140957E+09 | 132.15 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.146642E+09 | 132.15 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.171699E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.131908E+09 | 132.15 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.146642E+09 | 132.15 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.323026E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.285645E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.309551E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.285602E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.288045E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.274304E+10 | 3437.84 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.282735E+10 | 3437.84 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.294986E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.294665E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.315708E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.309305E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.320800E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.358437E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.274304E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.323026E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.323026E+10 | 3437.84 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.285645E+10 | 3437.84 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.309551E+10 | 3437.84 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.285602E+10 | 3437.84 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.288045E+10 | 3437.84 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.274304E+10 | 3437.84 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.282735E+10 | 3437.84 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.294986E+10 | 3437.84 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.294657E+10 | 3437.84 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.315708E+10 | 3437.84 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.309305E+10 | 3437.84 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.320800E+10 | 3437.84 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.358437E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.274304E+10 | 3437.84 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.323026E+10 | 3437.84 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126106E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121504E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125670E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148074E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.160421E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.160915E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.154982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.160699E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.155692E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.155043E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.160359E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.155569E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.159988E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.188948E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.144845E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.160977E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.743719E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400745E+09 |
February | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308296E+09 |
March | 0.199990E+10 | 0.746011E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228899.45 | 0.274973E+09 |
April | 0.192973E+10 | 0.718503E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22074909.18 | 0.121108E+09 |
May | 0.199475E+10 | 0.745008E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60987887.80 | 48691764.02 |
June | 0.193394E+10 | 0.721798E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119500E+09 | 14125531.64 |
July | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109968E+09 | 8992896.00 |
August | 0.199896E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88695544.69 | 19906806.39 |
September | 0.192879E+10 | 0.718790E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48811199.97 | 57614537.17 |
October | 0.199148E+10 | 0.743432E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11619884.62 | 0.148467E+09 |
November | 0.192552E+10 | 0.721225E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313362E+09 |
December | 0.199054E+10 | 0.741713E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440178E+09 |
Annual Sum or Average | 0.234744E+11 | 0.875972E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461887E+09 | 0.215646E+10 |
Minimum of Months | 0.179968E+10 | 0.671510E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8992896.00 |
Maximum of Months | 0.199990E+10 | 0.746298E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119500E+09 | 0.440178E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.861229E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164574E+09 |
February | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.71 | 0.127916E+09 |
March | 0.231589E+10 | 0.863884E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239311.43 | 0.116978E+09 |
April | 0.223463E+10 | 0.832029E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9298877.03 | 55107350.51 |
May | 0.230993E+10 | 0.862722E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23727939.28 | 23785689.61 |
June | 0.223950E+10 | 0.835845E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46256661.79 | 7313032.26 |
July | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42399325.48 | 5055249.43 |
August | 0.231480E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34504296.59 | 10209308.16 |
September | 0.223354E+10 | 0.832361E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19541990.69 | 25764741.73 |
October | 0.230614E+10 | 0.860897E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4876793.47 | 63777599.31 |
November | 0.222975E+10 | 0.835182E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6632.87 | 0.130010E+09 |
December | 0.230505E+10 | 0.858907E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179592E+09 |
Annual Sum or Average | 0.271834E+11 | 0.101438E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180853E+09 | 0.910083E+09 |
Minimum of Months | 0.208403E+10 | 0.777612E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5055249.43 |
Maximum of Months | 0.231589E+10 | 0.864216E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46256661.79 | 0.179592E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.693793E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353786E+09 |
February | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 338717.60 | 0.272882E+09 |
March | 0.489771E+09 | 0.695932E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1838497.58 | 0.249033E+09 |
April | 0.472586E+09 | 0.670270E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25926118.45 | 0.117762E+09 |
May | 0.488511E+09 | 0.694996E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57061026.36 | 52728127.07 |
June | 0.473617E+09 | 0.673344E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108060E+09 | 17026697.74 |
July | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98870067.18 | 11756153.69 |
August | 0.489542E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81043164.34 | 23459906.45 |
September | 0.472357E+09 | 0.670538E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47598898.30 | 58427950.34 |
October | 0.487709E+09 | 0.693526E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13745625.07 | 0.137993E+09 |
November | 0.471555E+09 | 0.672810E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249589.90 | 0.279273E+09 |
December | 0.487480E+09 | 0.691922E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389431E+09 |
Annual Sum or Average | 0.574883E+10 | 0.817168E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434732E+09 | 0.196356E+10 |
Minimum of Months | 0.440737E+09 | 0.626432E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11756153.69 |
Maximum of Months | 0.489771E+09 | 0.696199E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108060E+09 | 0.389431E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.351983E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199612E+09 |
February | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 235694.31 | 0.153401E+09 |
March | 0.376747E+09 | 0.353068E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205586.80 | 0.138769E+09 |
April | 0.363528E+09 | 0.340049E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15967382.67 | 64276787.61 |
May | 0.375778E+09 | 0.352593E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34576132.56 | 28078145.12 |
June | 0.364321E+09 | 0.341609E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63080644.20 | 9038704.13 |
July | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57841416.98 | 6140227.50 |
August | 0.376571E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47806855.44 | 12206196.51 |
September | 0.363352E+09 | 0.340185E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28801567.17 | 31167036.58 |
October | 0.375161E+09 | 0.351847E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8603849.41 | 75178624.68 |
November | 0.362735E+09 | 0.341337E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 183322.33 | 0.156060E+09 |
December | 0.374985E+09 | 0.351034E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220991E+09 |
Annual Sum or Average | 0.442217E+10 | 0.414575E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258302E+09 | 0.109492E+10 |
Minimum of Months | 0.339028E+09 | 0.317809E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6140227.50 |
Maximum of Months | 0.376747E+09 | 0.353204E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63080644.20 | 0.220991E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553732E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 6688.79 | 0.429379E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 438525.55 | 0.391746E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 28760214.07 | 0.176826E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 77647143.33 | 70639186.12 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.155268E+09 | 18717016.65 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.144259E+09 | 11933014.86 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.117291E+09 | 27161150.73 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 66494262.11 | 74522093.34 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 17371857.35 | 0.201292E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 15742.64 | 0.428523E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607729E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.607552E+09 | 0.299220E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11933014.86 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.155268E+09 | 0.607729E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.152522E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970451E+09 |
February | 0.236489E+11 | 0.133028E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757467E+09 |
March | 0.262800E+11 | 0.141594E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318699.30 | 0.688657E+09 |
April | 0.253579E+11 | 0.128930E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46870356.60 | 0.316212E+09 |
May | 0.262123E+11 | 0.129357E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133459E+09 | 0.133039E+09 |
June | 0.254132E+11 | 0.121590E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265451E+09 | 40104550.97 |
July | 0.261570E+11 | 0.125966E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243377E+09 | 27614612.03 |
August | 0.262677E+11 | 0.133919E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196169E+09 | 55769865.23 |
September | 0.253456E+11 | 0.133401E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108306E+09 | 0.145526E+09 |
October | 0.261693E+11 | 0.147719E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25549315.23 | 0.370003E+09 |
November | 0.253025E+11 | 0.142841E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760946E+09 |
December | 0.261570E+11 | 0.151280E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105821E+10 |
Annual Sum or Average | 0.308468E+12 | 0.164215E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101950E+10 | 0.532400E+10 |
Minimum of Months | 0.236489E+11 | 0.121590E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27614612.03 |
Maximum of Months | 0.262800E+11 | 0.152522E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265451E+09 | 0.105821E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.849469E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279818E+10 |
February | 0.702046E+11 | 0.763825E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217950E+10 |
March | 0.780153E+11 | 0.845797E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2398647.87 | 0.198626E+10 |
April | 0.752779E+11 | 0.809562E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146192E+09 | 0.923849E+09 |
May | 0.778146E+11 | 0.836949E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387611E+09 | 0.392845E+09 |
June | 0.754422E+11 | 0.809727E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759696E+09 | 0.119197E+09 |
July | 0.776503E+11 | 0.833275E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695736E+09 | 82496775.47 |
August | 0.779788E+11 | 0.841342E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563314E+09 | 0.167395E+09 |
September | 0.752414E+11 | 0.813725E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314485E+09 | 0.422806E+09 |
October | 0.776868E+11 | 0.845840E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74825232.68 | 0.107053E+10 |
November | 0.751137E+11 | 0.819767E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4248.47 | 0.220199E+10 |
December | 0.776503E+11 | 0.846093E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305425E+10 |
Annual Sum or Average | 0.915726E+12 | 0.991537E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294426E+10 | 0.153993E+11 |
Minimum of Months | 0.702046E+11 | 0.763825E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82496775.47 |
Maximum of Months | 0.780153E+11 | 0.849469E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759696E+09 | 0.305425E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221982E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25071.68 | 0.171190E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 463631.87 | 0.155039E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19246277.61 | 64827107.23 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49775826.85 | 22524139.08 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91879985.88 | 4891059.50 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88081810.72 | 2502272.32 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72995371.80 | 7654992.13 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41414662.02 | 24634225.85 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11088316.20 | 76829918.97 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33576.25 | 0.170494E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245743E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375005E+09 | 0.116831E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2502272.32 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91879985.88 | 0.245743E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215727E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46377.07 | 0.165811E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 589743.99 | 0.150832E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19553513.85 | 63727428.70 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49828870.07 | 22463051.36 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91797287.18 | 5051332.55 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88029909.36 | 2616568.47 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73065326.65 | 7559304.29 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41720737.56 | 23890171.69 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11383874.24 | 73514458.71 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43143.24 | 0.165232E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239260E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376059E+09 | 0.113568E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2616568.47 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91797287.18 | 0.239260E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.146022E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68298969.33 |
February | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53368329.11 |
March | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65002.09 | 48227344.02 |
April | 0.00 | 0.141479E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4003826.31 | 21814334.33 |
May | 0.00 | 0.145441E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10702810.58 | 8802783.23 |
June | 0.00 | 0.140357E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20951937.84 | 2395927.50 |
July | 0.00 | 0.146583E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19492269.90 | 1488723.12 |
August | 0.00 | 0.144861E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15911041.94 | 3426218.08 |
September | 0.00 | 0.141518E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9116429.75 | 9467840.13 |
October | 0.00 | 0.146003E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2322954.22 | 25388186.75 |
November | 0.00 | 0.140918E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4323.96 | 53035981.85 |
December | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74738038.93 |
Annual Sum or Average | 0.00 | 0.171652E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82570596.59 | 0.370453E+09 |
Minimum of Months | 0.00 | 0.131872E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1488723.12 |
Maximum of Months | 0.00 | 0.146602E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20951937.84 | 74738038.93 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60500817.47 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 126216.21 | 46052280.50 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 405503.36 | 41157726.26 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6119200.99 | 16987913.75 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14487493.51 | 5888816.07 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26006723.63 | 1221155.22 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24986727.07 | 547600.20 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20902759.52 | 1823287.71 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12363344.93 | 6221904.22 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3862673.85 | 19357204.73 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 126061.58 | 45309315.77 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67235765.49 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109387E+09 | 0.312304E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547600.20 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26006723.63 | 67235765.49 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222090E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26229.40 | 0.171754E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 494356.94 | 0.154999E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19206472.00 | 66155033.61 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49528851.07 | 25331125.11 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91473631.63 | 6776140.50 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87646797.12 | 4034813.76 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72640781.49 | 9340398.17 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41224158.67 | 26836925.70 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11139484.78 | 75497904.10 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38276.46 | 0.170614E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245754E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373419E+09 | 0.117918E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4034813.76 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91473631.63 | 0.245754E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215387E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98652.69 | 0.166008E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 639545.62 | 0.150904E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19274664.88 | 65359336.48 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49531030.18 | 25340153.27 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91447463.75 | 6939658.96 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87627160.68 | 4147643.94 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72660212.72 | 9261245.10 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41334518.35 | 26167894.68 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11401254.49 | 72700897.32 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 134387.78 | 0.164121E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239054E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374149E+09 | 0.114539E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4147643.94 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91447463.75 | 0.239054E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269479E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174551.84 | 0.209189E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079884.13 | 0.191769E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19730298.93 | 90306100.13 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44420140.21 | 39612705.21 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83347092.36 | 12700315.11 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76914245.39 | 8558651.06 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62863851.20 | 17285582.60 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35765919.98 | 44793337.32 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9909006.58 | 0.106672E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131353.42 | 0.215962E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296527E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334336E+09 | 0.150285E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8558651.06 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83347092.36 | 0.296527E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232348E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221578E+09 |
February | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23642.21 | 0.171213E+09 |
March | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 444052.55 | 0.155501E+09 |
April | 0.293479E+09 | 0.225120E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18947879.06 | 65025398.66 |
May | 0.303504E+09 | 0.231424E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49250978.49 | 22288124.99 |
June | 0.293842E+09 | 0.223334E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91196746.63 | 4667315.25 |
July | 0.303141E+09 | 0.233241E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87353474.95 | 2295732.08 |
August | 0.303685E+09 | 0.230501E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72343844.62 | 7335812.30 |
September | 0.293479E+09 | 0.225181E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40951097.47 | 24204495.09 |
October | 0.303322E+09 | 0.232318E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10913372.19 | 77257839.07 |
November | 0.293661E+09 | 0.224227E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30140.39 | 0.170525E+09 |
December | 0.303141E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245372E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273130E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371455E+09 | 0.116726E+10 |
Minimum of Months | 0.273974E+09 | 0.209833E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2295732.08 |
Maximum of Months | 0.303685E+09 | 0.233271E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91196746.63 | 0.245372E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.232321E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214886E+09 |
February | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47760.83 | 0.165364E+09 |
March | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 565917.86 | 0.150795E+09 |
April | 0.293479E+09 | 0.225094E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19180836.35 | 63836855.81 |
May | 0.303504E+09 | 0.231397E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49289754.75 | 22180866.81 |
June | 0.293842E+09 | 0.223308E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91101112.86 | 4811056.16 |
July | 0.303141E+09 | 0.233213E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87292840.70 | 2397034.65 |
August | 0.303685E+09 | 0.230474E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72407279.86 | 7239770.19 |
September | 0.293479E+09 | 0.225154E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41272487.42 | 23432757.33 |
October | 0.303322E+09 | 0.232290E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11202584.72 | 73453142.19 |
November | 0.293661E+09 | 0.224201E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39239.73 | 0.164501E+09 |
December | 0.303141E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238531E+09 |
Annual Sum or Average | 0.357224E+10 | 0.273098E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372400E+09 | 0.113143E+10 |
Minimum of Months | 0.273974E+09 | 0.209808E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397034.65 |
Maximum of Months | 0.303685E+09 | 0.233244E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91101112.86 | 0.238531E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.146062E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116499E+09 |
February | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11255.11 | 90018000.24 |
March | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 226267.23 | 80495654.94 |
April | 0.293479E+09 | 0.141518E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9713867.98 | 32890838.36 |
May | 0.303504E+09 | 0.145481E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25302360.14 | 11155249.06 |
June | 0.293842E+09 | 0.140395E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46800741.74 | 2294051.09 |
July | 0.303141E+09 | 0.146623E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44797842.41 | 1118967.16 |
August | 0.303685E+09 | 0.144901E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37061995.85 | 3733376.13 |
September | 0.293479E+09 | 0.141556E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20910693.57 | 12547797.35 |
October | 0.303322E+09 | 0.146043E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5548343.23 | 40134375.71 |
November | 0.293661E+09 | 0.140957E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14039.41 | 89199827.53 |
December | 0.303141E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129051E+09 |
Annual Sum or Average | 0.357224E+10 | 0.171699E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190387E+09 | 0.609138E+09 |
Minimum of Months | 0.273974E+09 | 0.131908E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1118967.16 |
Maximum of Months | 0.303685E+09 | 0.146642E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46800741.74 | 0.129051E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.323026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645040E+09 |
February | 0.415303E+11 | 0.285645E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504345E+09 |
March | 0.461508E+11 | 0.309551E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185558.06 | 0.464358E+09 |
April | 0.445315E+11 | 0.285602E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27973503.34 | 0.216935E+09 |
May | 0.460320E+11 | 0.288045E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79325692.99 | 92422257.82 |
June | 0.446286E+11 | 0.274304E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163703E+09 | 28279500.89 |
July | 0.459349E+11 | 0.282735E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149622E+09 | 19866894.54 |
August | 0.461292E+11 | 0.294986E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121233E+09 | 40165876.30 |
September | 0.445099E+11 | 0.294665E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67385423.99 | 97734393.08 |
October | 0.459565E+11 | 0.315708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15802608.83 | 0.247237E+09 |
November | 0.444343E+11 | 0.309305E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.504900E+09 |
December | 0.459349E+11 | 0.320800E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704803E+09 |
Annual Sum or Average | 0.541708E+12 | 0.358437E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625232E+09 | 0.356609E+10 |
Minimum of Months | 0.415303E+11 | 0.274304E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19866894.54 |
Maximum of Months | 0.461508E+11 | 0.323026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163703E+09 | 0.704803E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.323026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650764E+09 |
February | 0.415303E+11 | 0.285645E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508475E+09 |
March | 0.461508E+11 | 0.309551E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159745.85 | 0.467918E+09 |
April | 0.445315E+11 | 0.285602E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27886988.05 | 0.217860E+09 |
May | 0.460320E+11 | 0.288045E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79274973.20 | 92601199.69 |
June | 0.446286E+11 | 0.274304E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163673E+09 | 28285194.49 |
July | 0.459349E+11 | 0.282735E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149590E+09 | 19870245.03 |
August | 0.461292E+11 | 0.294986E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121195E+09 | 40198639.90 |
September | 0.445099E+11 | 0.294657E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67318842.59 | 97829426.84 |
October | 0.459565E+11 | 0.315708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15768054.00 | 0.248413E+09 |
November | 0.444343E+11 | 0.309305E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508794E+09 |
December | 0.459349E+11 | 0.320800E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711217E+09 |
Annual Sum or Average | 0.541708E+12 | 0.358437E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624867E+09 | 0.359222E+10 |
Minimum of Months | 0.415303E+11 | 0.274304E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19870245.03 |
Maximum of Months | 0.461508E+11 | 0.323026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163673E+09 | 0.711217E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587358E+09 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457126E+09 |
March | 0.410691E+10 | 0.126106E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 145763.76 | 0.420004E+09 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 25013900.51 | 0.195119E+09 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 71046117.75 | 82804930.09 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.146645E+09 | 25309435.47 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.134013E+09 | 17775454.74 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.108567E+09 | 35968759.42 |
September | 0.396089E+10 | 0.121504E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 60319437.82 | 87499314.73 |
October | 0.408962E+10 | 0.125670E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 14132068.63 | 0.222019E+09 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456821E+09 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641547E+09 |
Annual Sum or Average | 0.482060E+11 | 0.148074E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.559882E+09 | 0.322935E+10 |
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17775454.74 |
Maximum of Months | 0.410691E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.146645E+09 | 0.641547E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477521E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36438.48 | 0.369038E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236801.18 | 0.335180E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29948126.42 | 0.157279E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72720476.01 | 68885648.26 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143865E+09 | 21982823.17 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131900E+09 | 14986888.94 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107107E+09 | 30030069.02 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60104724.38 | 75852003.90 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15141427.73 | 0.182607E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82334.75 | 0.373357E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527082E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562143E+09 | 0.263380E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14986888.94 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143865E+09 | 0.527082E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 15451.75 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 15451.75 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 15451.75 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 15451.75 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 15451.75 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 15451.75 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 15451.75 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 15451.75 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 15451.75 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 15451.75 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 15451.75 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 15451.75 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 15451.75 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 716.35 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 286.20 | 27-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 716.35 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 300.75 | 03-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 716.35 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 21-MAR-16:00 | 282.97 | 02-MAR-05:00 |
April | 1169.53 | 01-APR-00:10 | 716.35 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 | 21-APR-14:00 | 192.62 | 12-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 716.35 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.34 | 21-MAY-14:00 | 128.33 | 02-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 716.35 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 02-JUN-16:00 | 82.74 | 13-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 716.35 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.37 | 02-JUL-16:00 | 50.41 | 05-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 716.35 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.08 | 07-AUG-16:00 | 64.92 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 716.35 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.60 | 19-SEP-14:00 | 146.33 | 30-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 716.35 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 | 01-OCT-15:00 | 158.73 | 25-OCT-06:10 |
November | 1169.53 | 01-NOV-00:10 | 716.35 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 242.58 | 28-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 716.35 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 287.31 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.41 | |||||
Maximum of Months | 1169.53 | 716.35 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 300.75 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 829.54 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 116.48 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 829.54 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 20-FEB-15:00 | 122.54 | 03-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 829.54 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 | 22-MAR-13:00 | 115.37 | 02-MAR-05:50 |
April | 1354.32 | 01-APR-00:10 | 829.54 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 | 21-APR-14:00 | 83.26 | 12-APR-06:10 |
May | 1354.32 | 01-MAY-00:10 | 829.54 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 19-MAY-14:00 | 58.67 | 02-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 829.54 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.86 | 02-JUN-16:00 | 36.47 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 829.54 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 | 02-JUL-16:00 | 24.95 | 05-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 829.54 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 07-AUG-16:00 | 29.64 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 829.54 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.69 | 19-SEP-14:00 | 64.53 | 30-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 829.54 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 01-OCT-15:00 | 70.20 | 11-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 829.54 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 03-NOV-16:00 | 101.49 | 17-NOV-04:00 |
December | 1354.32 | 01-DEC-00:10 | 829.54 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 116.30 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | |||||
Maximum of Months | 1354.32 | 829.54 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 55.86 | 122.54 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 668.27 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 261.10 | 27-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 668.27 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 20-FEB-15:00 | 274.37 | 03-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 668.27 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.43 | 21-MAR-16:00 | 258.11 | 02-MAR-05:00 |
April | 286.42 | 01-APR-00:10 | 668.27 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.69 | 21-APR-14:00 | 186.79 | 12-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 668.27 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 | 19-MAY-14:00 | 132.45 | 02-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 668.27 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.97 | 02-JUN-16:00 | 85.65 | 13-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 668.27 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.14 | 02-JUL-16:00 | 57.68 | 05-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 668.27 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.75 | 07-AUG-16:00 | 68.69 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 668.27 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.31 | 19-SEP-16:00 | 147.30 | 30-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 668.27 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.76 | 01-OCT-15:00 | 158.63 | 11-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 668.27 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 | 03-NOV-16:00 | 226.09 | 17-NOV-04:00 |
December | 286.42 | 01-DEC-00:10 | 668.27 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 262.08 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | |||||
Maximum of Months | 286.42 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 131.97 | 274.37 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 339.04 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 150.64 | 27-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 339.04 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 20-FEB-15:00 | 158.30 | 03-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 339.04 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | 21-MAR-16:00 | 148.92 | 02-MAR-05:00 |
April | 220.32 | 01-APR-00:10 | 339.04 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 | 21-APR-14:00 | 104.93 | 12-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 339.04 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.11 | 19-MAY-14:00 | 73.87 | 02-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 339.04 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 | 02-JUN-16:00 | 47.48 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 339.04 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.39 | 02-JUL-16:00 | 31.60 | 05-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 339.04 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 07-AUG-16:00 | 37.45 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 339.04 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.46 | 19-SEP-16:00 | 82.16 | 30-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 339.04 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.12 | 01-OCT-15:00 | 88.64 | 11-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 339.04 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 | 03-NOV-16:00 | 127.98 | 17-NOV-04:00 |
December | 220.32 | 01-DEC-00:10 | 339.04 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 151.20 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 | |||||
Maximum of Months | 220.32 | 339.04 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 | 158.30 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 398.56 | 27-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 1.72 | 20-FEB-16:00 | 416.84 | 03-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 22.05 | 21-MAR-16:00 | 388.14 | 02-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 103.59 | 21-APR-15:08 | 313.16 | 12-APR-06:05 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 147.03 | 21-MAY-16:00 | 204.51 | 02-MAY-05:16 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 192.05 | 02-JUN-16:30 | 113.42 | 13-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 193.17 | 02-JUL-16:00 | 80.52 | 05-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 171.75 | 07-AUG-16:00 | 95.63 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 131.82 | 19-SEP-16:00 | 209.31 | 30-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 120.71 | 01-OCT-15:20 | 272.68 | 25-OCT-06:10 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 8.64 | 03-NOV-16:00 | 338.36 | 17-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 400.04 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.52 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 193.17 | 416.84 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1957.67 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 658.75 | 27-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1957.67 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 690.96 | 03-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1957.67 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 21-MAR-16:00 | 665.54 | 02-MAR-05:10 |
April | 15368.40 | 01-APR-00:10 | 1957.67 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.86 | 21-APR-14:00 | 472.87 | 12-APR-06:10 |
May | 15368.40 | 01-MAY-00:10 | 1957.67 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.51 | 21-MAY-14:00 | 330.88 | 02-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1957.67 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.80 | 02-JUN-16:00 | 208.80 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1957.67 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.11 | 02-JUL-16:00 | 142.83 | 05-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1957.67 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.40 | 07-AUG-16:00 | 169.68 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1957.67 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.81 | 19-SEP-14:00 | 363.12 | 30-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1957.67 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.91 | 01-OCT-15:00 | 400.60 | 25-OCT-03:10 |
November | 15368.40 | 01-NOV-00:10 | 1957.67 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 588.56 | 17-NOV-04:00 |
December | 15368.40 | 01-DEC-00:10 | 1957.67 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 671.71 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.83 | |||||
Maximum of Months | 15368.40 | 1957.67 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 319.80 | 690.96 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 8554.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1955.48 | 27-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 8554.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2048.70 | 03-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 8554.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.99 | 22-MAR-13:00 | 1954.77 | 02-MAR-05:50 |
April | 45622.98 | 01-APR-00:10 | 8554.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.62 | 21-APR-14:00 | 1396.61 | 12-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 8554.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 703.87 | 19-MAY-14:00 | 982.08 | 02-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 8554.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 913.63 | 02-JUN-16:00 | 596.75 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 8554.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 897.49 | 02-JUL-16:00 | 408.22 | 05-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 8554.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.33 | 07-AUG-16:00 | 484.95 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 8554.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.58 | 19-SEP-14:00 | 1065.57 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 8554.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.23 | 01-OCT-15:00 | 1179.35 | 11-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 8554.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 08-NOV-15:00 | 1715.34 | 17-NOV-04:00 |
December | 45622.98 | 01-DEC-00:10 | 8554.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1967.80 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.22 | |||||
Maximum of Months | 45622.98 | 8554.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 913.63 | 2048.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:06 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.23 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:08 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 37.92 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 | 02-JUL-16:00 | 28.54 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 34.92 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.75 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 | 01-OCT-15:10 | 91.19 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 03-NOV-15:08 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.75 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.11 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:09 | 175.56 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.22 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:10 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 19-MAY-16:00 | 72.66 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 | 02-JUN-16:00 | 38.72 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 28.57 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 33.95 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 01-OCT-15:10 | 91.18 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 03-NOV-15:08 | 141.78 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.74 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 | 175.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 132.12 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 46.57 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 132.12 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 49.54 | 03-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 132.12 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 21-MAR-16:00 | 45.11 | 02-MAR-05:00 |
April | 0.00 | 01-APR-00:10 | 132.12 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 21-APR-14:00 | 32.85 | 12-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 132.12 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 21-MAY-14:00 | 23.40 | 02-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 132.12 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 02-JUN-16:00 | 14.22 | 13-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 132.12 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 02-JUL-16:00 | 9.06 | 05-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 132.12 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 | 07-AUG-16:00 | 11.00 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 132.12 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 19-SEP-14:00 | 25.86 | 30-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 132.12 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 01-OCT-15:00 | 28.57 | 25-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 132.12 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 08-NOV-15:00 | 40.94 | 17-NOV-04:00 |
December | 0.00 | 01-DEC-00:10 | 132.12 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 46.69 | 19-DEC-04:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | |||||
Maximum of Months | 0.00 | 132.12 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 49.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 46.64 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 20-FEB-16:06 | 49.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 21-MAR-16:00 | 46.11 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 21-APR-15:08 | 31.47 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 | 19-MAY-16:00 | 20.28 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 02-JUN-16:00 | 10.47 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 02-JUL-16:00 | 7.58 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.42 | 07-AUG-16:00 | 9.65 | 16-AUG-21:40 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 19-SEP-16:00 | 22.38 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 | 01-OCT-15:10 | 25.45 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 | 08-NOV-15:00 | 39.57 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 46.82 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 49.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:09 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.23 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:10 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 40.29 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 33.80 | 05-JUL-06:40 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.08 | 07-AUG-16:00 | 38.33 | 30-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 | 01-OCT-15:10 | 91.19 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 03-NOV-15:08 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.74 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.11 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:07 | 175.56 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.22 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:10 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 | 02-JUN-16:00 | 41.04 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.98 | 02-JUL-16:00 | 34.17 | 05-JUL-06:40 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 37.51 | 30-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 01-OCT-15:10 | 91.18 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 03-NOV-15:07 | 141.78 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.73 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 | 175.56 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 201.21 | 27-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 20-FEB-16:00 | 211.43 | 03-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 21-MAR-16:00 | 198.93 | 02-MAR-05:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.99 | 21-APR-14:00 | 144.22 | 12-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.61 | 21-MAY-14:00 | 101.57 | 02-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 | 02-JUN-16:00 | 64.89 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.54 | 02-JUL-16:00 | 43.45 | 05-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 | 07-AUG-16:00 | 51.53 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.22 | 19-SEP-14:00 | 113.24 | 30-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.18 | 01-OCT-15:00 | 121.18 | 25-OCT-05:55 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 08-NOV-15:00 | 176.15 | 17-NOV-04:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 201.97 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 | 211.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.22 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.55 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.22 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 20-FEB-16:06 | 176.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.22 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 21-MAR-16:00 | 165.66 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 210.22 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.84 | 21-APR-15:08 | 113.16 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.22 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.22 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.68 | 02-JUN-16:00 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.22 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 02-JUL-16:00 | 27.40 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.22 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 07-AUG-16:00 | 32.93 | 16-AUG-21:30 |
September | 180.00 | 01-SEP-00:10 | 210.22 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.76 | 19-SEP-16:00 | 80.57 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.22 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.09 | 01-OCT-15:10 | 91.58 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 210.22 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 03-NOV-15:08 | 142.21 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 210.22 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 168.18 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | |||||
Maximum of Months | 180.00 | 210.22 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.68 | 176.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 210.20 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.53 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 210.20 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-FEB-16:09 | 175.99 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 210.20 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 21-MAR-16:00 | 165.65 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 210.20 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.84 | 21-APR-15:07 | 113.15 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 210.20 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 210.20 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 | 02-JUN-16:00 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 210.20 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.66 | 02-JUL-16:00 | 27.19 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 210.20 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 07-AUG-16:00 | 32.55 | 16-AUG-21:30 |
September | 180.00 | 01-SEP-00:10 | 210.20 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.52 | 19-SEP-16:00 | 80.56 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 210.20 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.68 | 01-OCT-15:10 | 91.58 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 210.20 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 03-NOV-15:07 | 142.19 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 210.20 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 168.16 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 | |||||
Maximum of Months | 180.00 | 210.20 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 | 175.99 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 132.15 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 85.72 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 132.15 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 20-FEB-16:10 | 90.05 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 132.15 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 21-MAR-16:00 | 84.76 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 132.15 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 21-APR-15:08 | 57.90 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 132.15 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 19-MAY-16:00 | 37.38 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 132.15 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 02-JUN-16:00 | 19.38 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 132.15 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.46 | 02-JUL-16:00 | 13.59 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 132.15 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 07-AUG-16:00 | 17.79 | 16-AUG-21:30 |
September | 180.00 | 01-SEP-00:10 | 132.15 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 19-SEP-16:00 | 41.22 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 132.15 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.85 | 01-OCT-15:10 | 46.86 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 132.15 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 | 03-NOV-15:10 | 72.76 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 132.15 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 86.04 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | |||||
Maximum of Months | 180.00 | 132.15 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 90.05 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 455.17 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 475.98 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.98 | 22-MAR-13:00 | 450.99 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 | 21-APR-14:00 | 321.99 | 12-APR-06:10 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.17 | 21-MAY-14:00 | 223.65 | 02-MAY-05:16 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 02-JUN-16:00 | 135.39 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.17 | 02-JUL-16:00 | 93.09 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.97 | 19-SEP-14:00 | 240.66 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 01-OCT-15:00 | 272.88 | 25-OCT-03:10 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 08-NOV-15:00 | 393.13 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 456.87 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 475.98 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3437.84 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 455.17 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3437.84 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 475.98 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3437.84 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 21-MAR-16:00 | 450.99 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 3437.84 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 | 21-APR-14:00 | 328.54 | 12-APR-06:10 |
May | 26988.77 | 01-MAY-00:10 | 3437.84 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.17 | 21-MAY-14:00 | 224.10 | 02-MAY-05:16 |
June | 26988.77 | 01-JUN-00:10 | 3437.84 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 02-JUN-16:00 | 135.40 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3437.84 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.17 | 02-JUL-16:00 | 93.09 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3437.84 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3437.84 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.97 | 19-SEP-14:00 | 240.67 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3437.84 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 01-OCT-15:00 | 276.02 | 25-OCT-06:10 |
November | 26988.77 | 01-NOV-00:10 | 3437.84 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 393.13 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 3437.84 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 456.88 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | |||||
Maximum of Months | 26988.77 | 3437.84 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 475.98 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 407.41 | 27-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 426.04 | 03-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 11.66 | 21-MAR-16:00 | 397.75 | 02-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 101.50 | 21-APR-14:00 | 319.33 | 12-APR-06:10 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 136.32 | 21-MAY-14:00 | 215.17 | 02-MAY-05:16 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 182.50 | 02-JUN-16:00 | 121.20 | 13-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 175.80 | 02-JUL-16:00 | 83.29 | 05-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 162.76 | 07-AUG-16:00 | 98.71 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 122.73 | 19-SEP-14:00 | 215.38 | 30-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 109.59 | 01-OCT-15:00 | 273.70 | 25-OCT-06:10 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 351.96 | 28-NOV-05:00 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 408.94 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.29 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 182.50 | 426.04 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 356.93 | 27-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 20-FEB-16:00 | 375.02 | 03-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 | 21-MAR-16:00 | 352.89 | 02-MAR-05:40 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.38 | 21-APR-14:00 | 243.30 | 12-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.32 | 21-MAY-14:00 | 172.69 | 02-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 02-JUN-16:00 | 111.55 | 13-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.86 | 02-JUL-16:00 | 72.86 | 05-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.08 | 07-AUG-16:00 | 87.48 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.99 | 19-SEP-14:00 | 191.82 | 30-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.12 | 01-OCT-15:00 | 204.41 | 11-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 08-NOV-15:00 | 302.71 | 28-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 358.28 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.86 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 375.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 37996.26 | 26-JAN-21:56 | 102239.04 | 137348.18 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33051.10 | 01-FEB-20:58 | 89459.16 | 154517.47 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23018.04 | 13-MAR-05:18 | 53675.50 | 41205.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22501.61 | 13-APR-05:17 | 89459.16 | 68675.11 | 50697.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17427.27 | 02-MAY-04:55 | 23003.78 | 6867.31 | 6083.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15285.73 | 15-JUN-18:10 | 53675.50 | 82408.91 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20253.40 | 19-JUL-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23570.55 | 24-AUG-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26011.90 | 22-SEP-21:00 | 10223.90 | 13734.82 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38165.71 | 25-OCT-06:23 | 35783.66 | 60089.65 | 42585.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44687.01 | 16-NOV-01:41 | 103517.03 | 23177.62 | 22813.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49375.25 | 04-DEC-22:57 | 115018.92 | 103011.64 | 70976.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15285.73 | 10223.90 | 6867.31 | 6083.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49375.25 | 115018.92 | 154517.47 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2994.02 | 27-JAN-13:44 | 2598.96 | 1989.87 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.68 |
February | 2860.27 | 07-FEB-13:30 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
March | 2374.57 | 28-MAR-21:35 | 7017.19 | 2865.42 | 3031.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.66 |
April | 2384.01 | 03-APR-14:10 | 389.84 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 | 0.00 |
May | 2412.84 | 31-MAY-18:15 | 1819.27 | 1273.52 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 67.14 | 0.00 |
June | 2817.44 | 15-JUN-18:15 | 1819.27 | 1273.52 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 114.74 | 0.00 |
July | 2796.51 | 26-JUL-18:03 | 5457.82 | 3820.56 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 96.65 | 0.00 |
August | 2938.73 | 27-AUG-12:00 | 389.84 | 238.78 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 | 0.00 |
September | 3559.34 | 20-SEP-12:50 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 80.63 | 0.00 |
October | 3662.43 | 18-OCT-13:10 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 0.00 |
November | 3391.31 | 10-NOV-12:00 | 519.79 | 397.97 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 |
December | 3149.52 | 07-DEC-10:10 | 519.79 | 397.97 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2374.57 | 259.90 | 198.99 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3662.43 | 7017.19 | 3820.56 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 114.74 | 188.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2433.92 | 04-JAN-22:03 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.07 |
February | 2847.55 | 08-FEB-20:40 | 4213.44 | 3318.16 | 3175.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.25 |
March | 2620.48 | 17-MAR-20:58 | 12038.40 | 7373.70 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.41 |
April | 2227.19 | 11-APR-01:50 | 2708.64 | 184.34 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.37 |
May | 2236.24 | 19-MAY-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 0.00 |
June | 2445.59 | 15-JUN-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 0.00 |
July | 2397.91 | 25-JUL-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 0.00 |
August | 2432.51 | 07-AUG-21:00 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 0.00 |
September | 2303.88 | 20-SEP-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
October | 2227.53 | 05-OCT-20:10 | 1203.84 | 737.37 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
November | 2286.62 | 19-NOV-00:12 | 10533.60 | 2765.14 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.52 |
December | 2546.87 | 04-DEC-22:57 | 13543.20 | 5530.27 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2227.19 | 1203.84 | 184.34 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2847.55 | 13543.20 | 7373.70 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 85.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1591.86 | 02-JAN-08:55 | 254.59 | 594.01 | 883.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.81 |
February | 1665.45 | 24-FEB-02:31 | 2004.91 | 519.76 | 1237.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.10 |
March | 1694.65 | 13-MAR-05:18 | 1336.61 | 1782.04 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.38 |
April | 1647.06 | 11-APR-01:57 | 1718.50 | 445.51 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.52 |
May | 1783.72 | 31-MAY-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 0.00 |
June | 2140.18 | 15-JUN-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 | 0.00 |
July | 2096.39 | 03-JUL-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 0.00 |
August | 2060.70 | 07-AUG-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 0.00 |
September | 1739.07 | 22-SEP-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
October | 1531.61 | 05-OCT-20:00 | 222.77 | 668.27 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
November | 1750.84 | 19-NOV-00:12 | 2227.68 | 2227.55 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.46 |
December | 1910.64 | 04-DEC-22:57 | 2864.16 | 4455.10 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1531.61 | 222.77 | 445.51 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2140.18 | 2864.16 | 4455.10 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 | 183.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1013.63 | 01-JAN-00:45 | 342.72 | 226.02 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.68 |
February | 1075.62 | 24-FEB-02:31 | 1542.24 | 263.72 | 356.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.11 |
March | 1089.22 | 13-MAR-05:18 | 1028.16 | 904.09 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.38 |
April | 1057.93 | 11-APR-01:57 | 1321.92 | 226.04 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.63 |
May | 870.37 | 02-MAY-04:55 | 440.64 | 150.68 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.06 |
June | 1134.98 | 15-JUN-18:40 | 171.36 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 | 0.00 |
July | 1120.90 | 03-JUL-18:30 | 171.36 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 54.15 | 0.00 |
August | 1068.15 | 07-AUG-21:00 | 195.84 | 301.36 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 | 0.00 |
September | 896.15 | 25-SEP-05:25 | 342.72 | 301.36 | 254.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.52 |
October | 964.98 | 25-OCT-02:12 | 1321.92 | 226.04 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.52 |
November | 1126.11 | 19-NOV-00:12 | 1713.60 | 1130.08 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.68 |
December | 1233.58 | 04-DEC-22:57 | 2203.20 | 2260.22 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 870.37 | 171.36 | 150.68 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1233.58 | 2203.20 | 2260.22 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 | 103.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51298.64 | 26-JAN-21:56 | 8064.00 | 4032.04 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 292.91 |
February | 51911.36 | 08-FEB-21:57 | 5644.80 | 2822.43 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 298.70 |
March | 53400.24 | 01-MAR-20:46 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 331.69 |
April | 41474.31 | 13-APR-06:34 | 3628.80 | 2268.02 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 236.47 |
May | 39149.23 | 30-MAY-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 61.21 | 0.00 |
June | 39542.73 | 15-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 120.81 | 0.00 |
July | 39478.74 | 03-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 53.78 | 0.00 |
August | 39419.37 | 04-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 114.36 | 0.00 |
September | 39080.14 | 20-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 20.15 | 0.00 |
October | 38852.35 | 05-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
November | 48282.93 | 26-NOV-20:43 | 3628.80 | 2419.23 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 298.91 |
December | 53210.38 | 04-DEC-22:57 | 9072.00 | 3024.03 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 254.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38852.35 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53400.24 | 9072.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 120.81 | 331.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17062.08 | 23-JAN-02:07 | 61473.60 | 870.08 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.44 |
February | 18099.81 | 24-FEB-03:04 | 122947.20 | 1740.15 | 1625.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.20 |
March | 17061.43 | 13-MAR-03:12 | 76842.00 | 1087.60 | 1016.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.23 |
April | 16483.56 | 13-APR-04:53 | 61473.60 | 1740.15 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.37 |
May | 11633.06 | 19-MAY-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 130.00 | 0.00 |
June | 12253.00 | 15-JUN-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.22 | 0.00 |
July | 12166.27 | 25-JUL-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 163.86 | 0.00 |
August | 12596.11 | 07-AUG-21:10 | 15368.40 | 1305.12 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.89 | 0.00 |
September | 12367.29 | 19-SEP-15:03 | 51228.00 | 717.81 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 204.97 | 0.00 |
October | 18542.33 | 07-OCT-02:00 | 76842.00 | 1087.60 | 1016.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.72 |
November | 17341.03 | 20-NOV-04:26 | 153684.00 | 2175.19 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.22 |
December | 19216.83 | 07-DEC-00:14 | 138315.60 | 3915.35 | 2743.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11633.06 | 15368.40 | 717.81 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19216.83 | 153684.00 | 3915.35 | 2743.41 | 0.00 | 0.00 | 0.00 | 0.00 | 204.97 | 452.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 63110.92 | 04-JAN-22:28 | 456229.80 | 57028.80 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.75 |
February | 62706.19 | 24-FEB-03:04 | 364983.84 | 7603.84 | 16891.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.37 |
March | 66022.44 | 06-MAR-07:35 | 40553.76 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.91 |
April | 61759.21 | 11-APR-04:41 | 319360.86 | 13306.72 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.97 |
May | 44004.44 | 02-MAY-05:18 | 177422.70 | 19009.60 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 955.83 |
June | 43231.95 | 15-JUN-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 534.78 | 0.00 |
July | 42831.13 | 26-JUL-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 293.47 | 0.00 |
August | 43606.99 | 07-AUG-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 456.69 | 0.00 |
September | 41590.68 | 21-SEP-21:10 | 45622.98 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 134.26 | 0.00 |
October | 63206.91 | 25-OCT-05:20 | 70969.08 | 7603.84 | 10557.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.61 |
November | 63254.88 | 25-NOV-02:28 | 456229.80 | 9504.80 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.46 |
December | 66114.52 | 07-DEC-00:14 | 410606.82 | 17108.64 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1317.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41590.68 | 40553.76 | 5702.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66114.52 | 456229.80 | 57028.80 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 534.78 | 1329.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3650.42 | 12-JAN-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.72 |
February | 3728.68 | 20-FEB-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 0.00 |
March | 3741.53 | 13-MAR-19:41 | 1247.40 | 1892.02 | 1469.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.92 |
April | 4055.40 | 06-APR-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.81 |
May | 4021.24 | 20-MAY-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 | 0.00 |
June | 3991.00 | 14-JUN-08:11 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 0.00 |
July | 3529.67 | 25-JUL-06:51 | 774.00 | 1177.26 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 0.00 |
August | 3645.88 | 26-AUG-08:11 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 0.00 |
September | 4007.23 | 29-SEP-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 |
October | 3957.13 | 29-OCT-21:51 | 1386.00 | 1786.91 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 |
November | 3736.59 | 09-NOV-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 0.00 |
December | 3614.47 | 16-DEC-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3529.67 | 360.00 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4055.40 | 1800.00 | 1892.02 | 2370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 63.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3500.35 | 12-JAN-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 |
February | 3656.80 | 20-FEB-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 |
March | 3658.04 | 16-MAR-15:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 0.00 |
April | 3983.72 | 06-APR-18:11 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 |
May | 4004.62 | 20-MAY-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 0.00 |
June | 4009.12 | 14-JUN-08:11 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 0.00 |
July | 3522.88 | 25-JUL-06:51 | 774.00 | 1177.12 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 0.00 |
August | 3613.61 | 26-AUG-08:11 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 0.00 |
September | 3889.01 | 29-SEP-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 |
October | 3755.66 | 29-OCT-21:51 | 1386.00 | 1786.70 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 |
November | 3668.30 | 09-NOV-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 0.00 |
December | 3417.32 | 16-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3417.32 | 360.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4009.12 | 1800.00 | 1870.78 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 55.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 544.83 | 12-JAN-14:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
February | 525.81 | 07-FEB-13:40 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
March | 426.04 | 16-MAR-12:50 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 |
April | 411.80 | 04-APR-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
May | 407.44 | 19-MAY-20:20 | 0.00 | 117.59 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 | 0.00 |
June | 451.29 | 15-JUN-20:20 | 0.00 | 117.59 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 0.00 |
July | 455.76 | 02-JUL-21:00 | 0.00 | 132.12 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 0.00 |
August | 473.48 | 27-AUG-13:40 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
September | 578.95 | 19-SEP-13:30 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 0.00 |
October | 645.38 | 22-OCT-13:20 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
November | 604.42 | 09-NOV-13:50 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
December | 462.69 | 16-DEC-13:40 | 0.00 | 43.60 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 407.44 | 0.00 | 36.99 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 645.38 | 0.00 | 132.12 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 15.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1223.35 | 01-JAN-09:01 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 |
February | 1311.54 | 21-FEB-21:31 | 1441.80 | 1058.56 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
March | 1354.05 | 15-MAR-21:51 | 1440.00 | 708.35 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 |
April | 1388.18 | 05-APR-21:51 | 1440.00 | 708.35 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 |
May | 1442.21 | 20-MAY-08:51 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 0.00 |
June | 1440.95 | 11-JUN-08:31 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
July | 1300.86 | 16-JUL-18:01 | 819.00 | 925.08 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 0.00 |
August | 1294.34 | 03-AUG-18:01 | 970.20 | 823.32 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 0.00 |
September | 1399.52 | 29-SEP-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 |
October | 1388.38 | 19-OCT-21:51 | 1620.00 | 796.89 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.65 |
November | 1304.93 | 08-NOV-22:51 | 1620.00 | 796.89 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
December | 1214.45 | 09-DEC-09:01 | 378.00 | 518.04 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1214.45 | 378.00 | 518.04 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1442.21 | 1800.00 | 1058.56 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 22.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3225.14 | 12-JAN-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.43 |
February | 3307.65 | 18-FEB-09:01 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 |
March | 3287.74 | 16-MAR-15:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 0.00 |
April | 3918.71 | 27-APR-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 |
May | 3948.72 | 20-MAY-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 0.00 |
June | 3943.29 | 14-JUN-08:11 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 0.00 |
July | 3504.86 | 11-JUL-07:51 | 619.20 | 739.99 | 906.09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 0.00 |
August | 3589.80 | 28-AUG-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 |
September | 3610.95 | 19-SEP-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
October | 3559.71 | 18-OCT-08:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 |
November | 3810.76 | 09-NOV-09:51 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.02 |
December | 3216.48 | 16-DEC-09:01 | 378.00 | 824.08 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3216.48 | 360.00 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3948.72 | 680.40 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 100.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2353.55 | 04-JAN-09:02 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.27 |
February | 3209.44 | 20-FEB-09:01 | 378.00 | 823.98 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.13 |
March | 3220.98 | 07-MAR-09:01 | 252.00 | 647.42 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 |
April | 3890.28 | 27-APR-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 |
May | 3922.76 | 20-MAY-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 0.00 |
June | 3920.65 | 14-JUN-08:11 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
July | 3493.38 | 11-JUL-07:51 | 619.20 | 739.90 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 | 0.00 |
August | 3565.61 | 28-AUG-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
September | 3543.77 | 19-SEP-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 0.00 |
October | 3455.20 | 03-OCT-08:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
November | 3488.25 | 09-NOV-09:51 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 |
December | 3009.11 | 09-DEC-09:01 | 378.00 | 823.98 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2353.55 | 216.00 | 554.93 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3922.76 | 619.20 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 76.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2928.11 | 02-JAN-08:55 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.64 |
February | 3084.72 | 24-FEB-02:31 | 15843.49 | 1452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.64 |
March | 3129.01 | 13-MAR-05:18 | 10562.33 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.26 |
April | 3072.37 | 13-APR-05:17 | 17603.88 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.70 |
May | 2556.46 | 02-MAY-04:55 | 4526.71 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.24 |
June | 3150.43 | 15-JUN-18:30 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | 0.00 |
July | 2936.42 | 26-JUL-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 0.00 |
August | 2927.41 | 07-AUG-18:20 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.64 | 0.00 |
September | 2670.03 | 19-SEP-18:03 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 | 0.00 |
October | 2847.19 | 25-OCT-02:12 | 13580.14 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.11 |
November | 3240.41 | 19-NOV-00:12 | 17603.88 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.69 |
December | 3496.30 | 04-DEC-22:57 | 22633.56 | 12448.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2556.46 | 1760.39 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3496.30 | 22633.56 | 12448.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | 139.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3857.18 | 12-JAN-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 |
February | 3940.25 | 20-FEB-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 | 0.00 |
March | 4036.22 | 13-MAR-19:41 | 1247.40 | 1892.02 | 1469.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.10 |
April | 4317.85 | 06-APR-18:11 | 1386.00 | 1871.00 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.83 |
May | 4232.78 | 20-MAY-08:51 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 | 0.00 |
June | 4182.59 | 14-JUN-08:11 | 360.00 | 924.99 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 0.00 |
July | 3658.12 | 16-JUL-06:51 | 954.00 | 861.92 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 0.00 |
August | 3767.28 | 26-AUG-08:11 | 540.00 | 1177.26 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 0.00 |
September | 4192.50 | 29-SEP-21:51 | 1800.00 | 1408.50 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.60 |
October | 4171.05 | 29-OCT-21:51 | 1386.00 | 1786.91 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 |
November | 3946.90 | 09-NOV-16:01 | 680.40 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
December | 3815.13 | 16-DEC-16:01 | 378.00 | 485.62 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3658.12 | 360.00 | 412.04 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4317.85 | 1800.00 | 1892.02 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 66.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3686.99 | 12-JAN-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 |
February | 3853.53 | 20-FEB-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
March | 3849.78 | 16-MAR-15:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
April | 4222.97 | 06-APR-18:11 | 1386.00 | 1870.78 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 |
May | 4213.87 | 20-MAY-08:51 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 0.00 |
June | 4200.07 | 14-JUN-08:11 | 360.00 | 924.88 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 0.00 |
July | 3659.59 | 16-JUL-06:51 | 954.00 | 861.82 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 0.00 |
August | 3720.10 | 26-AUG-08:11 | 540.00 | 1177.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 0.00 |
September | 4057.53 | 29-SEP-21:51 | 1800.00 | 1408.34 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
October | 3915.57 | 29-OCT-21:51 | 1386.00 | 1786.70 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 |
November | 3862.88 | 09-NOV-16:01 | 680.40 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 0.00 |
December | 3551.82 | 16-DEC-16:01 | 378.00 | 485.56 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3551.82 | 360.00 | 411.99 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4222.97 | 1800.00 | 1870.78 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 56.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2107.98 | 12-JAN-19:41 | 1247.40 | 1058.56 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 |
February | 2143.05 | 20-FEB-21:11 | 1247.40 | 1189.39 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
March | 2110.06 | 14-MAR-21:01 | 1620.00 | 796.89 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
April | 2084.00 | 04-APR-19:51 | 1108.80 | 1057.23 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
May | 2169.35 | 20-MAY-08:51 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 0.00 |
June | 2113.74 | 11-JUN-08:31 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 0.00 |
July | 1891.66 | 30-JUL-08:51 | 540.00 | 740.06 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | 0.00 |
August | 1963.57 | 28-AUG-08:51 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
September | 2193.44 | 29-SEP-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
October | 2284.39 | 26-OCT-21:51 | 1800.00 | 885.43 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 |
November | 2310.18 | 09-NOV-09:51 | 360.00 | 581.48 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 |
December | 2076.20 | 07-DEC-17:01 | 777.60 | 296.03 | 990.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1891.66 | 360.00 | 296.03 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2310.18 | 1800.00 | 1189.39 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 33.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31656.84 | 04-JAN-22:56 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.53 |
February | 43481.82 | 24-FEB-05:14 | 269887.68 | 7639.64 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.81 |
March | 32659.11 | 13-MAR-05:15 | 125947.58 | 9167.57 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.37 |
April | 31753.83 | 18-APR-02:07 | 269887.68 | 3819.82 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.89 |
May | 27381.32 | 02-MAY-05:06 | 104956.32 | 7639.64 | 28116.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.27 |
June | 24091.47 | 15-JUN-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 108.53 | 0.00 |
July | 23907.92 | 25-JUL-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 0.00 |
August | 24040.54 | 07-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.85 | 0.00 |
September | 22838.83 | 22-SEP-22:00 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
October | 27242.34 | 24-OCT-01:58 | 161932.61 | 2291.89 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.52 |
November | 31662.14 | 28-NOV-23:50 | 161932.61 | 6875.68 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.25 |
December | 38246.57 | 04-DEC-22:57 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22838.83 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43481.82 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 108.53 | 317.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41992.50 | 23-JAN-00:03 | 80966.30 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.52 |
February | 34413.40 | 08-FEB-22:06 | 188921.38 | 16043.25 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.84 |
March | 34605.08 | 13-MAR-05:15 | 125947.58 | 9167.57 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.80 |
April | 33407.15 | 07-APR-05:54 | 104956.32 | 6111.71 | 28116.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.04 |
May | 29358.65 | 02-MAY-05:06 | 104956.32 | 7639.64 | 28116.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.43 |
June | 25290.03 | 15-JUN-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 108.49 | 0.00 |
July | 25099.56 | 25-JUL-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 | 0.00 |
August | 25222.19 | 07-AUG-21:20 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 0.00 |
September | 23995.52 | 22-SEP-21:10 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
October | 29233.22 | 07-OCT-05:08 | 125947.58 | 6875.68 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.23 |
November | 33422.69 | 28-NOV-23:50 | 161932.61 | 6875.68 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.73 |
December | 43390.45 | 04-DEC-22:57 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23995.52 | 26988.77 | 2291.89 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43390.45 | 269887.68 | 22918.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 108.49 | 326.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39560.72 | 22-JAN-08:44 | 13342.80 | 5381.88 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 257.84 |
February | 35085.38 | 18-FEB-08:18 | 13342.80 | 5381.88 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 269.18 |
March | 35442.01 | 17-MAR-07:38 | 5337.12 | 2690.94 | 74564.28 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 278.57 |
April | 34813.73 | 11-APR-07:27 | 6404.54 | 3229.13 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 261.49 |
May | 30465.10 | 21-MAY-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 75.33 | 0.00 |
June | 31041.92 | 18-JUN-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 107.47 | 0.00 |
July | 31211.52 | 02-JUL-10:37 | 2401.70 | 1210.92 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 102.21 | 0.00 |
August | 31112.27 | 06-AUG-10:33 | 2401.70 | 1210.92 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 95.99 | 0.00 |
September | 30726.09 | 17-SEP-10:50 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 75.60 | 0.00 |
October | 32799.15 | 25-OCT-06:23 | 7471.97 | 4709.15 | 104389.99 | 78724.91 | 0.00 | 0.00 | 0.00 | 0.00 | 239.19 |
November | 36839.69 | 27-NOV-08:37 | 9606.82 | 4843.69 | 134215.70 | 134956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 262.12 |
December | 41695.71 | 31-DEC-22:29 | 21348.48 | 6727.35 | 149128.56 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 257.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 30465.10 | 800.57 | 403.64 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41695.71 | 21348.48 | 6727.35 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 107.47 | 278.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5644.58 | 13-JAN-01:33 | 21558.96 | 2964.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.24 |
February | 6099.58 | 24-FEB-02:31 | 16768.08 | 1537.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.44 |
March | 6098.39 | 13-MAR-05:18 | 11178.72 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.69 |
April | 5970.43 | 11-APR-01:57 | 14372.64 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.77 |
May | 5781.90 | 30-MAY-15:02 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.38 | 0.00 |
June | 6664.01 | 15-JUN-18:03 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.44 | 0.00 |
July | 7006.87 | 03-JUL-12:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.15 | 0.00 |
August | 6848.77 | 07-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.67 | 0.00 |
September | 6330.44 | 20-SEP-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.86 | 0.00 |
October | 5866.61 | 05-OCT-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.57 | 0.00 |
November | 6311.60 | 19-NOV-00:12 | 18631.20 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.17 |
December | 6185.89 | 30-DEC-10:17 | 7984.80 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5644.58 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7006.87 | 21558.96 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.15 | 234.53 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.390947E+12 | 267055.90 | 03-JAN-20:40 | 0.498492E+12 | 460498.20 | 26-JAN-17:00 |
February | 0.361154E+12 | 275134.93 | 06-FEB-20:10 | 0.429522E+12 | 487096.20 | 01-FEB-21:30 |
March | 0.409345E+12 | 295167.23 | 15-MAR-19:10 | 0.452619E+12 | 462357.02 | 01-MAR-18:49 |
April | 0.467446E+12 | 361289.38 | 19-APR-19:10 | 0.403353E+12 | 351678.68 | 03-APR-17:30 |
May | 0.552915E+12 | 388292.66 | 19-MAY-19:10 | 0.395017E+12 | 349648.92 | 02-MAY-17:10 |
June | 0.606753E+12 | 418067.96 | 05-JUN-19:10 | 0.370746E+12 | 322223.32 | 08-JUN-17:19 |
July | 0.660559E+12 | 417977.77 | 25-JUL-19:10 | 0.376371E+12 | 318841.11 | 10-JUL-17:10 |
August | 0.621611E+12 | 413522.11 | 04-AUG-19:19 | 0.376733E+12 | 319406.38 | 31-AUG-17:10 |
September | 0.561346E+12 | 388627.29 | 22-SEP-19:10 | 0.371066E+12 | 322046.14 | 29-SEP-17:10 |
October | 0.482282E+12 | 383192.73 | 04-OCT-19:10 | 0.399831E+12 | 349726.96 | 31-OCT-17:40 |
November | 0.396498E+12 | 300915.66 | 09-NOV-20:00 | 0.438869E+12 | 491539.08 | 26-NOV-17:40 |
December | 0.389535E+12 | 264363.83 | 28-DEC-20:40 | 0.498424E+12 | 467651.18 | 02-DEC-17:49 |
Annual Sum or Average | 0.590039E+13 | 0.501104E+13 | ||||
Minimum of Months | 0.361154E+12 | 264363.83 | 0.370746E+12 | 318841.11 | ||
Maximum of Months | 0.660559E+12 | 418067.96 | 0.498492E+12 | 491539.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.744026E+11 | 0.257766E+11 | 0.140828E+12 | 0.552133E+11 | 0.445334E+11 | 0.646437E+10 | 0.00 | 0.112019E+11 | 0.00 | 0.00 | 0.196114E+11 | 0.770426E+10 | 0.00 |
February | 0.669851E+11 | 0.220513E+11 | 0.127191E+12 | 0.498701E+11 | 0.397568E+11 | 0.653704E+10 | 0.00 | 0.232326E+11 | 0.00 | 0.00 | 0.138804E+11 | 0.696190E+10 | 0.00 |
March | 0.738601E+11 | 0.226622E+11 | 0.140882E+12 | 0.552166E+11 | 0.441674E+11 | 0.775965E+10 | 0.00 | 0.390806E+11 | 0.00 | 0.00 | 0.128281E+11 | 0.770292E+10 | 0.00 |
April | 0.711328E+11 | 0.201687E+11 | 0.136245E+12 | 0.534312E+11 | 0.468647E+11 | 0.872836E+10 | 0.00 | 0.107382E+12 | 0.00 | 0.00 | 0.110032E+11 | 0.746492E+10 | 0.00 |
May | 0.732885E+11 | 0.193275E+11 | 0.140860E+12 | 0.552143E+11 | 0.530545E+11 | 0.942250E+10 | 0.00 | 0.174077E+12 | 0.00 | 0.00 | 0.147164E+11 | 0.770427E+10 | 0.00 |
June | 0.707561E+11 | 0.179455E+11 | 0.136336E+12 | 0.534344E+11 | 0.571659E+11 | 0.949742E+10 | 0.00 | 0.229712E+12 | 0.00 | 0.00 | 0.193236E+11 | 0.745688E+10 | 0.00 |
July | 0.731942E+11 | 0.188768E+11 | 0.140770E+12 | 0.552106E+11 | 0.590766E+11 | 0.997106E+10 | 0.00 | 0.269101E+12 | 0.00 | 0.00 | 0.213094E+11 | 0.771236E+10 | 0.00 |
August | 0.734592E+11 | 0.201687E+11 | 0.140892E+12 | 0.552163E+11 | 0.592122E+11 | 0.982177E+10 | 0.00 | 0.232177E+12 | 0.00 | 0.00 | 0.176130E+11 | 0.770438E+10 | 0.00 |
September | 0.714191E+11 | 0.211501E+11 | 0.136256E+12 | 0.534316E+11 | 0.561580E+11 | 0.932927E+10 | 0.00 | 0.188375E+12 | 0.00 | 0.00 | 0.125987E+11 | 0.746627E+10 | 0.00 |
October | 0.741566E+11 | 0.236937E+11 | 0.140818E+12 | 0.552131E+11 | 0.525494E+11 | 0.914226E+10 | 0.00 | 0.105611E+12 | 0.00 | 0.00 | 0.811355E+10 | 0.770295E+10 | 0.00 |
November | 0.718522E+11 | 0.244648E+11 | 0.136330E+12 | 0.534331E+11 | 0.462776E+11 | 0.724501E+10 | 0.00 | 0.318663E+11 | 0.00 | 0.00 | 0.125505E+11 | 0.744892E+10 | 0.00 |
December | 0.743404E+11 | 0.261572E+11 | 0.140770E+12 | 0.552117E+11 | 0.451420E+11 | 0.615855E+10 | 0.00 | 0.850762E+10 | 0.00 | 0.00 | 0.203382E+11 | 0.771234E+10 | 0.00 |
Annual Sum or Average | 0.868847E+12 | 0.262443E+12 | 0.165818E+13 | 0.650096E+12 | 0.603959E+12 | 0.100077E+12 | 0.00 | 0.142033E+13 | 0.00 | 0.00 | 0.183887E+12 | 0.907424E+11 | 0.00 |
Minimum of Months | 0.669851E+11 | 0.179455E+11 | 0.127191E+12 | 0.498701E+11 | 0.397568E+11 | 0.615855E+10 | 0.00 | 0.850762E+10 | 0.00 | 0.00 | 0.811355E+10 | 0.696190E+10 | 0.00 |
Maximum of Months | 0.744026E+11 | 0.261572E+11 | 0.140892E+12 | 0.552166E+11 | 0.592122E+11 | 0.997106E+10 | 0.00 | 0.269101E+12 | 0.00 | 0.00 | 0.213094E+11 | 0.771236E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.741962E+11 | 0.00 | 0.272378E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.463518E+11 | 0.00 | 0.245967E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.344690E+11 | 0.00 | 0.266127E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.961256E+10 | 0.00 | 0.246785E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.868829E+09 | 0.00 | 0.242170E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 48547919.85 | 0.00 | 0.223584E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 56688316.59 | 0.00 | 0.224494E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.111058E+09 | 0.00 | 0.224583E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.483337E+09 | 0.00 | 0.223612E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.570868E+10 | 0.00 | 0.242219E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.449746E+11 | 0.00 | 0.246803E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.805433E+11 | 0.00 | 0.266060E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.297425E+12 | 0.00 | 0.292478E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 48547919.85 | 0.00 | 0.223584E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.805433E+11 | 0.00 | 0.272378E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 71560.59 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39721.54 | 02-JAN-07:19 | 49371.23 | 31-JAN-05:40 | 4038.37 | 28-JAN-09:50 | 0.00 | 01-JAN-00:10 |
February | 71560.59 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39721.54 | 01-FEB-07:19 | 47067.64 | 01-FEB-19:40 | 4029.96 | 02-FEB-10:30 | 0.00 | 01-FEB-00:10 |
March | 71560.59 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39721.54 | 13-MAR-06:19 | 33525.47 | 28-MAR-21:10 | 3983.64 | 01-MAR-10:20 | 0.00 | 01-MAR-00:10 |
April | 71560.59 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39721.37 | 04-APR-06:19 | 36725.63 | 21-APR-21:10 | 4265.15 | 28-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 71560.59 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39721.06 | 03-MAY-06:19 | 41125.56 | 31-MAY-21:10 | 4502.76 | 19-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 71560.59 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39718.92 | 28-JUN-06:19 | 44306.14 | 15-JUN-21:10 | 4956.73 | 05-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 71560.59 | 03-JUL-19:19 | 16690.39 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39719.36 | 18-JUL-06:19 | 45866.36 | 26-JUL-21:10 | 4708.71 | 05-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 71560.59 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39721.37 | 14-AUG-06:19 | 48673.10 | 07-AUG-21:10 | 4679.16 | 01-AUG-20:49 | 0.00 | 01-AUG-00:10 |
September | 71560.59 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39721.54 | 25-SEP-06:19 | 47454.11 | 22-SEP-21:10 | 4776.42 | 18-SEP-19:10 | 0.00 | 01-SEP-00:10 |
October | 71560.59 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39721.54 | 02-OCT-06:19 | 45088.33 | 05-OCT-21:00 | 4499.76 | 01-OCT-18:30 | 0.00 | 01-OCT-00:10 |
November | 71560.59 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39721.54 | 01-NOV-06:19 | 48725.89 | 15-NOV-04:49 | 4011.60 | 17-NOV-00:20 | 0.00 | 01-NOV-00:10 |
December | 71560.59 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39721.54 | 11-DEC-07:19 | 37623.37 | 18-DEC-21:19 | 4052.17 | 28-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 71560.59 | 16690.39 | 89171.45 | 39718.92 | 33525.47 | 3983.64 | 0.00 | |||||||
Maximum of Months | 71560.59 | 16690.39 | 89171.45 | 39721.54 | 49371.23 | 4956.73 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 48751.35 | 03-JAN-14:39 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:40 | 4738.44 | 25-JAN-19:10 | 0.00 |
February | 72088.93 | 20-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.52 | 16-FEB-19:30 | 0.00 |
March | 76219.42 | 22-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4737.86 | 27-MAR-06:10 | 0.00 |
April | 115852.22 | 21-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.45 | 10-APR-18:10 | 0.00 |
May | 137247.84 | 19-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 02-MAY-00:00 | 4738.59 | 25-MAY-18:10 | 0.00 |
June | 169424.88 | 14-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.61 | 08-JUN-18:10 | 0.00 |
July | 166911.06 | 26-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.51 | 27-JUL-18:10 | 0.00 |
August | 158689.15 | 04-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.39 | 08-AUG-06:30 | 0.00 |
September | 134837.75 | 20-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-08:30 | 4738.68 | 28-SEP-18:10 | 0.00 |
October | 131077.37 | 04-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-09:50 | 4738.63 | 03-OCT-18:30 | 0.00 |
November | 77997.47 | 09-NOV-16:10 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.37 | 06-NOV-19:30 | 0.00 |
December | 30891.14 | 23-DEC-14:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.33 | 20-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 30891.14 | 0.00 | 0.00 | 9938.94 | 4737.86 | 0.00 | |||
Maximum of Months | 169424.88 | 0.00 | 0.00 | 9938.94 | 4738.68 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 267055.90 | 03-JAN-20:40 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 26198.18 | 3406.98 | 0.00 | 24983.84 | 0.00 |
February | 275134.93 | 06-FEB-20:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 22773.21 | 3325.76 | 0.00 | 36040.04 | 0.00 |
March | 295167.23 | 15-MAR-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 23060.25 | 3361.16 | 0.00 | 56054.29 | 0.00 |
April | 361289.38 | 19-APR-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 28365.16 | 3784.02 | 0.00 | 106229.73 | 0.00 |
May | 388292.66 | 19-MAY-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 34286.44 | 4413.53 | 0.00 | 127467.33 | 0.00 |
June | 418067.96 | 05-JUN-19:10 | 71560.59 | 86439.81 | 16690.39 | 32080.78 | 34545.25 | 4922.13 | 0.00 | 155485.82 | 0.00 |
July | 417977.77 | 25-JUL-19:10 | 71560.59 | 86439.81 | 16690.39 | 32080.31 | 37338.40 | 4179.52 | 0.00 | 154191.71 | 0.00 |
August | 413522.11 | 04-AUG-19:19 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 40155.33 | 4119.94 | 0.00 | 146701.25 | 0.00 |
September | 388627.29 | 22-SEP-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 38012.44 | 4144.03 | 0.00 | 124308.77 | 0.00 |
October | 383192.73 | 04-OCT-19:10 | 71560.59 | 86439.81 | 16690.39 | 32081.53 | 33220.51 | 4235.27 | 0.00 | 122912.00 | 0.00 |
November | 300915.66 | 09-NOV-20:00 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 28738.18 | 3369.59 | 0.00 | 55890.81 | 0.00 |
December | 264363.83 | 28-DEC-20:40 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 36142.12 | 3737.17 | 0.00 | 1426.14 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 264363.83 | 71560.59 | 86439.81 | 16690.39 | 32080.31 | 22773.21 | 3325.76 | 0.00 | 1426.14 | 0.00 | |
Maximum of Months | 418067.96 | 71560.59 | 86439.81 | 16690.39 | 32090.84 | 40155.33 | 4922.13 | 0.00 | 155485.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 173508.42 | 29-JAN-07:19 | 0.00 | 254877.17 | 18-JAN-18:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 161625.95 | 01-FEB-21:30 | 0.00 | 255720.02 | 09-FEB-18:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 148968.45 | 31-MAR-01:49 | 0.00 | 250919.76 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 140283.72 | 12-APR-01:39 | 0.00 | 248119.50 | 04-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 55066.60 | 06-MAY-05:49 | 0.00 | 245869.35 | 03-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 4740.61 | 29-JUN-08:00 | 0.00 | 221496.50 | 01-JUN-19:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4006.46 | 06-JUL-08:09 | 0.00 | 215382.02 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 6485.03 | 16-AUG-08:00 | 0.00 | 215561.27 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 67083.73 | 30-SEP-05:49 | 0.00 | 223404.35 | 30-SEP-21:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 120483.65 | 25-OCT-05:49 | 0.00 | 245980.99 | 30-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 163790.68 | 26-NOV-17:00 | 0.00 | 249273.20 | 27-NOV-18:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 176750.39 | 25-DEC-07:40 | 0.00 | 253221.84 | 21-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 4006.46 | 0.00 | 215382.02 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 176750.39 | 0.00 | 255720.02 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 25.24 | 34.83 | 25.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 25.23 | 25.00 | 25.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 25.24 | 21.83 | 25.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 25.24 | 6.17 | 25.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.44 | 1.17 | 25.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 25.17 | 17.50 | 25.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 25.18 | 52.33 | 25.18 |
Annual Sum or Average | 0.00 | 0.00 | 158.83 | 25.22 | 158.83 | 25.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 25.44 | 52.33 | 25.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.72 | 0.50 | 24.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.77 | 0.17 | 24.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.91 | 0.17 | 24.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 24.77 | 0.83 | 24.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.91 | 0.50 | 24.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.56 | 0.33 | 24.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.57 | 0.67 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.00 | 0.33 | 22.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.84 | 1.83 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 21.83 | 4.33 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 22.00 | 1.83 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.89 | 0.33 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.82 | 2.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 21.82 | 2.83 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.89 | 2.17 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 21.72 | 1.50 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.00 | 2.17 | 22.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.07 | 4.67 | 22.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 22.07 | 4.17 | 22.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.05 | 4.83 | 22.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.08 | 4.67 | 22.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.17 | 5.67 | 22.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.12 | 1.50 | 22.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.93 | 0.50 | 21.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.17 | 22.08 | 28.17 | 22.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.17 | 5.67 | 22.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.98 | 2.00 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.07 | 4.67 | 22.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.02 | 5.33 | 22.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 22.08 | 5.00 | 22.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.09 | 4.33 | 22.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.18 | 4.33 | 22.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.95 | 1.17 | 21.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.00 | 22.07 | 27.00 | 22.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.18 | 5.33 | 22.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.86 | 2.50 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.84 | 1.33 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.86 | 0.33 | 21.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 21.83 | 6.67 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.87 | 2.50 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.97 | 0.33 | 21.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.88 | 2.67 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 21.84 | 4.33 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.97 | 2.67 | 21.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.80 | 2.83 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.83 | 6.67 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.87 | 1.33 | 21.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.33 | 21.82 | 11.33 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.87 | 6.67 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.72 | 4.17 | 24.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.91 | 3.00 | 24.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.04 | 3.50 | 25.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.84 | 1.67 | 24.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.83 | 2.33 | 24.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.72 | 2.67 | 24.72 |
Annual Sum or Average | 0.00 | 0.00 | 17.33 | 24.84 | 17.33 | 24.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.04 | 4.17 | 25.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.79 | 5.00 | 24.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.91 | 3.83 | 24.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.01 | 4.33 | 25.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.92 | 1.67 | 24.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.86 | 2.67 | 24.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.75 | 4.00 | 24.75 |
Annual Sum or Average | 0.00 | 0.00 | 21.50 | 24.87 | 21.50 | 24.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.01 | 5.00 | 25.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 | 25.14 | 58.00 | 25.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 25.21 | 32.67 | 25.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 25.25 | 29.17 | 25.25 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.27 | 9.67 | 25.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.31 | 1.17 | 25.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 25.07 | 32.00 | 25.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 25.16 | 61.83 | 25.16 |
Annual Sum or Average | 0.00 | 0.00 | 224.50 | 25.17 | 224.50 | 25.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 25.31 | 61.83 | 25.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 666.17 | 23.74 | 0.00 | 23.74 | 0.00 | 23.74 |
February | 672.00 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
March | 744.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
April | 720.00 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
May | 744.00 | 22.69 | 10.50 | 22.70 | 10.50 | 22.70 |
June | 697.83 | 22.97 | 56.83 | 22.98 | 56.50 | 22.99 |
July | 407.83 | 23.77 | 519.67 | 23.82 | 367.33 | 23.83 |
August | 228.00 | 23.98 | 614.50 | 23.95 | 224.67 | 23.95 |
September | 211.00 | 24.00 | 504.17 | 23.99 | 210.50 | 23.99 |
October | 100.33 | 23.99 | 312.67 | 23.99 | 46.67 | 23.99 |
November | 399.33 | 23.98 | 17.83 | 23.98 | 0.00 | 23.98 |
December | 558.50 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 6149.00 | 23.18 | 2036.17 | 23.36 | 916.17 | 23.42 |
Minimum of Months | 100.33 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
Maximum of Months | 744.00 | 24.00 | 614.50 | 23.99 | 367.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 641.33 | 21.64 | 49.83 | 21.70 | 25.17 | 21.68 |
February | 580.50 | 21.79 | 18.67 | 21.78 | 14.17 | 21.77 |
March | 668.50 | 21.92 | 10.33 | 21.90 | 10.33 | 21.89 |
April | 533.67 | 22.44 | 41.17 | 22.55 | 0.00 | 22.55 |
May | 366.83 | 22.80 | 223.83 | 23.20 | 9.50 | 23.21 |
June | 113.00 | 23.20 | 517.50 | 23.73 | 40.67 | 23.70 |
July | 353.83 | 23.57 | 740.00 | 23.70 | 353.33 | 23.67 |
August | 242.33 | 23.35 | 662.17 | 23.63 | 208.00 | 23.59 |
September | 300.50 | 23.20 | 578.50 | 23.56 | 210.83 | 23.53 |
October | 394.33 | 22.44 | 290.83 | 23.04 | 45.83 | 23.06 |
November | 541.17 | 21.88 | 78.50 | 22.08 | 13.83 | 22.06 |
December | 655.17 | 21.56 | 58.17 | 21.53 | 55.33 | 21.49 |
Annual Sum or Average | 5391.17 | 22.24 | 3269.50 | 22.79 | 987.00 | 22.83 |
Minimum of Months | 113.00 | 21.56 | 10.33 | 21.53 | 0.00 | 21.49 |
Maximum of Months | 668.50 | 23.57 | 740.00 | 23.73 | 353.33 | 23.70 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.33 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
February | 666.00 | 22.95 | 0.00 | 22.95 | 0.00 | 22.95 |
March | 737.67 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
April | 545.67 | 23.39 | 14.50 | 23.41 | 0.00 | 23.41 |
May | 261.17 | 23.52 | 204.33 | 23.69 | 20.67 | 23.70 |
June | 115.17 | 23.86 | 436.83 | 23.92 | 65.33 | 23.93 |
July | 401.17 | 23.95 | 735.83 | 23.92 | 401.17 | 23.93 |
August | 271.17 | 23.89 | 687.50 | 23.90 | 269.50 | 23.90 |
September | 271.50 | 23.91 | 542.67 | 23.92 | 249.83 | 23.92 |
October | 306.17 | 23.44 | 239.33 | 23.62 | 79.00 | 23.64 |
November | 626.83 | 23.13 | 4.00 | 23.13 | 0.00 | 23.13 |
December | 744.00 | 22.70 | 0.00 | 22.70 | 0.00 | 22.70 |
Annual Sum or Average | 5678.83 | 23.21 | 2865.00 | 23.45 | 1085.50 | 23.50 |
Minimum of Months | 115.17 | 22.70 | 0.00 | 22.70 | 0.00 | 22.70 |
Maximum of Months | 744.00 | 23.95 | 735.83 | 23.92 | 401.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.50 | 18.17 | 21.49 | 18.17 | 21.48 |
February | 672.00 | 21.70 | 10.83 | 21.69 | 10.83 | 21.68 |
March | 744.00 | 21.97 | 3.83 | 21.97 | 3.83 | 21.96 |
April | 719.33 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
May | 490.17 | 23.45 | 52.00 | 23.49 | 0.83 | 23.49 |
June | 131.00 | 23.92 | 251.83 | 23.94 | 11.17 | 23.94 |
July | 249.67 | 23.93 | 726.33 | 23.95 | 249.67 | 23.94 |
August | 131.00 | 23.76 | 522.00 | 23.88 | 123.67 | 23.87 |
September | 327.33 | 23.62 | 400.83 | 23.74 | 147.83 | 23.75 |
October | 635.83 | 22.97 | 61.83 | 23.04 | 11.83 | 23.05 |
November | 720.00 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
December | 744.00 | 21.38 | 15.50 | 21.38 | 15.50 | 21.37 |
Annual Sum or Average | 6308.33 | 22.39 | 2063.17 | 22.75 | 593.33 | 22.81 |
Minimum of Months | 131.00 | 21.38 | 0.00 | 21.38 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 23.93 | 726.33 | 23.95 | 249.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.21 | 25.83 | 21.20 | 25.83 | 21.19 |
February | 672.00 | 21.40 | 22.00 | 21.39 | 22.00 | 21.38 |
March | 744.00 | 21.63 | 6.50 | 21.63 | 6.50 | 21.62 |
April | 720.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
May | 607.67 | 23.22 | 18.50 | 23.24 | 1.50 | 23.24 |
June | 148.00 | 23.73 | 186.50 | 23.81 | 13.00 | 23.80 |
July | 271.00 | 23.78 | 718.83 | 23.83 | 271.00 | 23.82 |
August | 194.67 | 23.54 | 449.33 | 23.71 | 136.33 | 23.69 |
September | 397.83 | 23.32 | 287.50 | 23.45 | 157.50 | 23.45 |
October | 675.83 | 22.65 | 34.17 | 22.70 | 15.50 | 22.71 |
November | 720.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
December | 744.00 | 21.14 | 32.00 | 21.14 | 32.00 | 21.13 |
Annual Sum or Average | 6639.00 | 22.16 | 1781.17 | 22.47 | 681.17 | 22.54 |
Minimum of Months | 148.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.13 |
Maximum of Months | 744.00 | 23.78 | 718.83 | 23.83 | 271.00 | 23.82 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 248.17 | 23.68 | 641.33 | 23.72 | 197.00 | 23.82 |
February | 205.83 | 23.67 | 576.00 | 23.73 | 165.67 | 23.81 |
March | 220.50 | 23.68 | 640.50 | 23.73 | 181.33 | 23.81 |
April | 231.00 | 23.88 | 646.33 | 23.75 | 215.83 | 23.80 |
May | 312.83 | 23.96 | 698.50 | 23.74 | 309.33 | 23.80 |
June | 389.17 | 23.93 | 708.83 | 23.70 | 389.17 | 23.76 |
July | 579.83 | 23.72 | 744.00 | 23.63 | 579.83 | 23.66 |
August | 508.33 | 23.81 | 744.00 | 23.65 | 508.33 | 23.69 |
September | 476.33 | 23.77 | 715.17 | 23.63 | 476.33 | 23.67 |
October | 346.83 | 23.93 | 706.67 | 23.70 | 344.83 | 23.76 |
November | 226.83 | 23.72 | 627.83 | 23.72 | 192.67 | 23.80 |
December | 229.67 | 23.62 | 628.50 | 23.74 | 170.50 | 23.85 |
Annual Sum or Average | 3975.33 | 23.79 | 8077.67 | 23.70 | 3730.83 | 23.76 |
Minimum of Months | 205.83 | 23.62 | 576.00 | 23.63 | 165.67 | 23.66 |
Maximum of Months | 579.83 | 23.96 | 744.00 | 23.75 | 579.83 | 23.85 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.67 | 22.94 | 90.00 | 23.10 | 0.00 | 23.10 |
February | 420.67 | 23.10 | 64.50 | 23.22 | 1.83 | 23.22 |
March | 454.17 | 23.09 | 52.67 | 23.18 | 1.67 | 23.18 |
April | 257.17 | 23.19 | 189.33 | 23.52 | 0.00 | 23.52 |
May | 187.17 | 23.48 | 434.17 | 23.76 | 89.50 | 23.77 |
June | 185.67 | 23.86 | 645.17 | 23.87 | 177.83 | 23.87 |
July | 600.33 | 23.88 | 743.83 | 23.88 | 600.33 | 23.88 |
August | 448.33 | 23.84 | 740.83 | 23.86 | 448.17 | 23.85 |
September | 385.67 | 23.91 | 687.83 | 23.93 | 379.83 | 23.93 |
October | 233.67 | 23.55 | 549.83 | 23.81 | 170.17 | 23.82 |
November | 315.17 | 22.93 | 206.17 | 23.34 | 2.33 | 23.35 |
December | 548.83 | 22.90 | 73.33 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 4519.50 | 23.37 | 4477.67 | 23.63 | 1871.67 | 23.68 |
Minimum of Months | 185.67 | 22.90 | 52.67 | 23.03 | 0.00 | 23.03 |
Maximum of Months | 600.33 | 23.91 | 743.83 | 23.93 | 600.33 | 23.93 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 616.00 | 23.31 | 0.00 | 23.31 | 0.00 | 23.31 |
February | 579.83 | 23.42 | 8.17 | 23.43 | 0.00 | 23.43 |
March | 625.17 | 23.40 | 10.00 | 23.41 | 0.00 | 23.41 |
April | 405.33 | 23.49 | 61.17 | 23.56 | 0.00 | 23.56 |
May | 214.17 | 23.57 | 278.17 | 23.75 | 66.00 | 23.77 |
June | 165.00 | 23.87 | 524.17 | 23.90 | 144.33 | 23.90 |
July | 561.50 | 23.92 | 740.83 | 23.90 | 561.50 | 23.91 |
August | 423.17 | 23.90 | 739.00 | 23.90 | 423.17 | 23.90 |
September | 379.00 | 23.95 | 647.33 | 23.95 | 379.00 | 23.95 |
October | 201.83 | 23.76 | 411.83 | 23.87 | 152.33 | 23.89 |
November | 395.00 | 23.43 | 43.83 | 23.48 | 0.33 | 23.48 |
December | 691.67 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
Annual Sum or Average | 5257.67 | 23.56 | 3464.50 | 23.70 | 1726.67 | 23.73 |
Minimum of Months | 165.00 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
Maximum of Months | 691.67 | 23.95 | 740.83 | 23.95 | 561.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.28 | 162.67 | 21.20 | 162.67 | 21.14 |
February | 666.83 | 21.49 | 121.00 | 21.42 | 121.00 | 21.37 |
March | 723.17 | 21.69 | 62.00 | 21.66 | 57.33 | 21.61 |
April | 679.83 | 21.86 | 8.50 | 21.91 | 0.00 | 21.91 |
May | 651.33 | 21.77 | 13.33 | 21.82 | 0.00 | 21.82 |
June | 573.17 | 21.59 | 31.33 | 21.70 | 0.00 | 21.70 |
July | 570.83 | 21.57 | 111.67 | 21.90 | 52.00 | 22.03 |
August | 566.33 | 21.57 | 90.00 | 21.84 | 30.00 | 21.91 |
September | 530.83 | 21.66 | 112.83 | 22.00 | 52.17 | 22.11 |
October | 587.50 | 21.74 | 71.67 | 22.03 | 12.50 | 22.05 |
November | 704.50 | 21.59 | 82.33 | 21.52 | 79.67 | 21.45 |
December | 744.00 | 21.22 | 265.17 | 21.14 | 265.17 | 21.09 |
Annual Sum or Average | 7742.33 | 21.58 | 1132.50 | 21.64 | 832.50 | 21.61 |
Minimum of Months | 530.83 | 21.22 | 8.50 | 21.14 | 0.00 | 21.09 |
Maximum of Months | 744.00 | 21.86 | 265.17 | 22.03 | 265.17 | 22.11 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 387.33 | 20.82 | 387.33 | 20.78 |
February | 672.00 | 21.15 | 277.50 | 21.06 | 277.50 | 21.00 |
March | 737.00 | 21.48 | 110.50 | 21.40 | 110.50 | 21.34 |
April | 694.83 | 21.81 | 7.17 | 21.84 | 1.00 | 21.84 |
May | 657.17 | 21.78 | 13.00 | 21.82 | 0.00 | 21.82 |
June | 570.00 | 21.58 | 41.17 | 21.74 | 0.67 | 21.74 |
July | 572.17 | 21.59 | 111.33 | 21.92 | 53.17 | 22.05 |
August | 589.83 | 21.63 | 73.17 | 21.84 | 30.50 | 21.91 |
September | 592.00 | 21.79 | 75.67 | 21.97 | 52.00 | 22.07 |
October | 676.67 | 21.81 | 29.67 | 21.89 | 12.17 | 21.91 |
November | 718.17 | 21.30 | 169.33 | 21.21 | 168.67 | 21.14 |
December | 744.00 | 20.83 | 564.83 | 20.79 | 564.83 | 20.77 |
Annual Sum or Average | 7967.83 | 21.45 | 1860.67 | 21.42 | 1658.33 | 21.36 |
Minimum of Months | 570.00 | 20.83 | 7.17 | 20.79 | 0.00 | 20.77 |
Maximum of Months | 744.00 | 21.81 | 564.83 | 21.97 | 564.83 | 22.07 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.96 | 298.83 | 20.92 | 298.83 | 20.90 |
February | 672.00 | 21.07 | 209.00 | 21.01 | 209.00 | 20.98 |
March | 744.00 | 21.25 | 78.33 | 21.22 | 78.33 | 21.19 |
April | 720.00 | 21.56 | 2.00 | 21.56 | 2.00 | 21.56 |
May | 742.67 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
June | 717.33 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
July | 740.17 | 21.86 | 34.83 | 21.92 | 34.83 | 21.97 |
August | 743.17 | 21.83 | 21.17 | 21.86 | 21.17 | 21.89 |
September | 719.67 | 21.81 | 35.83 | 21.86 | 35.83 | 21.91 |
October | 744.00 | 21.59 | 5.00 | 21.60 | 5.00 | 21.61 |
November | 720.00 | 21.09 | 145.67 | 21.05 | 145.67 | 21.02 |
December | 744.00 | 20.93 | 420.00 | 20.88 | 420.00 | 20.86 |
Annual Sum or Average | 8751.00 | 21.46 | 1250.67 | 21.41 | 1250.67 | 21.36 |
Minimum of Months | 672.00 | 20.93 | 0.00 | 20.88 | 0.00 | 20.86 |
Maximum of Months | 744.00 | 21.86 | 420.00 | 21.92 | 420.00 | 21.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.28 | 157.67 | 21.22 | 157.67 | 21.17 |
February | 672.00 | 21.55 | 104.67 | 21.49 | 104.67 | 21.44 |
March | 744.00 | 21.77 | 59.33 | 21.72 | 59.33 | 21.67 |
April | 675.83 | 21.94 | 13.83 | 22.01 | 0.50 | 22.01 |
May | 598.83 | 21.71 | 50.50 | 22.00 | 1.50 | 22.02 |
June | 512.83 | 21.44 | 58.67 | 21.84 | 5.83 | 21.89 |
July | 538.67 | 21.61 | 87.17 | 22.02 | 52.83 | 22.24 |
August | 524.00 | 21.50 | 91.17 | 21.94 | 32.17 | 22.05 |
September | 505.67 | 21.76 | 122.33 | 22.26 | 54.83 | 22.45 |
October | 629.67 | 21.85 | 36.00 | 21.96 | 15.00 | 21.98 |
November | 713.17 | 21.62 | 88.00 | 21.54 | 85.67 | 21.48 |
December | 744.00 | 21.22 | 266.50 | 21.15 | 266.50 | 21.11 |
Annual Sum or Average | 7602.67 | 21.60 | 1135.83 | 21.71 | 836.50 | 21.71 |
Minimum of Months | 505.67 | 21.22 | 13.83 | 21.15 | 0.50 | 21.11 |
Maximum of Months | 744.00 | 21.94 | 266.50 | 22.26 | 266.50 | 22.45 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.88 | 417.67 | 20.83 | 417.67 | 20.81 |
February | 672.00 | 21.16 | 247.00 | 21.09 | 247.00 | 21.04 |
March | 744.00 | 21.51 | 101.17 | 21.44 | 101.17 | 21.39 |
April | 692.00 | 21.92 | 15.17 | 21.97 | 3.50 | 21.97 |
May | 607.17 | 21.73 | 51.33 | 22.02 | 1.67 | 22.04 |
June | 517.67 | 21.47 | 61.17 | 21.89 | 7.33 | 21.95 |
July | 538.17 | 21.61 | 85.67 | 22.03 | 53.50 | 22.26 |
August | 533.50 | 21.53 | 81.67 | 21.93 | 32.83 | 22.04 |
September | 560.67 | 21.87 | 84.00 | 22.22 | 52.67 | 22.38 |
October | 705.67 | 21.85 | 25.50 | 21.90 | 15.00 | 21.91 |
November | 718.50 | 21.22 | 170.00 | 21.15 | 169.33 | 21.10 |
December | 744.00 | 20.82 | 558.50 | 20.78 | 558.50 | 20.76 |
Annual Sum or Average | 7777.33 | 21.44 | 1898.83 | 21.48 | 1660.17 | 21.43 |
Minimum of Months | 517.67 | 20.82 | 15.17 | 20.78 | 1.67 | 20.76 |
Maximum of Months | 744.00 | 21.92 | 558.50 | 22.22 | 558.50 | 22.38 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 16.50 | 21.32 | 16.50 | 21.32 |
February | 672.00 | 21.62 | 2.33 | 21.62 | 2.33 | 21.62 |
March | 744.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
April | 720.00 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
May | 595.83 | 23.39 | 50.83 | 23.42 | 31.17 | 23.43 |
June | 221.67 | 23.81 | 229.67 | 23.84 | 73.00 | 23.83 |
July | 470.33 | 23.82 | 706.67 | 23.83 | 470.33 | 23.83 |
August | 368.50 | 23.70 | 519.17 | 23.76 | 323.50 | 23.75 |
September | 485.33 | 23.68 | 442.67 | 23.73 | 296.33 | 23.73 |
October | 680.83 | 23.04 | 106.67 | 23.09 | 80.50 | 23.11 |
November | 720.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
December | 744.00 | 21.19 | 16.17 | 21.19 | 16.17 | 21.18 |
Annual Sum or Average | 7166.50 | 22.49 | 2090.67 | 22.78 | 1309.83 | 22.89 |
Minimum of Months | 221.67 | 21.19 | 0.00 | 21.19 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 23.82 | 706.67 | 23.84 | 470.33 | 23.83 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.19 | 314.67 | 21.08 | 314.67 | 21.02 |
February | 663.00 | 21.41 | 227.83 | 21.30 | 225.83 | 21.22 |
March | 717.67 | 21.62 | 149.67 | 21.57 | 138.83 | 21.48 |
April | 665.67 | 21.78 | 35.17 | 21.82 | 23.50 | 21.80 |
May | 640.33 | 21.71 | 24.17 | 21.78 | 2.00 | 21.78 |
June | 559.00 | 21.53 | 52.50 | 21.70 | 6.17 | 21.71 |
July | 565.50 | 21.55 | 146.17 | 21.93 | 60.33 | 22.05 |
August | 568.00 | 21.55 | 122.00 | 21.87 | 43.67 | 21.95 |
September | 535.17 | 21.63 | 149.83 | 22.00 | 67.17 | 22.10 |
October | 576.83 | 21.65 | 95.67 | 22.02 | 20.83 | 22.03 |
November | 701.33 | 21.51 | 171.00 | 21.40 | 166.67 | 21.31 |
December | 744.00 | 21.14 | 439.00 | 21.04 | 439.00 | 21.00 |
Annual Sum or Average | 7680.50 | 21.51 | 1927.67 | 21.56 | 1508.67 | 21.51 |
Minimum of Months | 535.17 | 21.14 | 24.17 | 21.04 | 2.00 | 21.00 |
Maximum of Months | 744.00 | 21.78 | 439.00 | 22.02 | 439.00 | 22.10 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 563.00 | 20.73 | 563.00 | 20.71 |
February | 672.00 | 21.06 | 398.50 | 20.95 | 398.50 | 20.90 |
March | 733.67 | 21.41 | 227.50 | 21.27 | 227.50 | 21.19 |
April | 685.50 | 21.75 | 43.33 | 21.76 | 35.17 | 21.73 |
May | 648.33 | 21.72 | 20.50 | 21.78 | 1.50 | 21.78 |
June | 552.33 | 21.52 | 56.17 | 21.70 | 5.83 | 21.72 |
July | 565.83 | 21.56 | 142.17 | 21.94 | 61.67 | 22.06 |
August | 583.67 | 21.59 | 106.17 | 21.86 | 45.50 | 21.94 |
September | 586.83 | 21.72 | 113.50 | 21.94 | 68.33 | 22.02 |
October | 669.50 | 21.73 | 50.67 | 21.83 | 26.33 | 21.84 |
November | 717.50 | 21.19 | 309.33 | 21.07 | 308.33 | 21.01 |
December | 744.00 | 20.73 | 692.50 | 20.71 | 692.50 | 20.70 |
Annual Sum or Average | 7903.17 | 21.37 | 2723.33 | 21.33 | 2434.17 | 21.26 |
Minimum of Months | 552.33 | 20.73 | 20.50 | 20.71 | 1.50 | 20.70 |
Maximum of Months | 744.00 | 21.75 | 692.50 | 21.94 | 692.50 | 22.06 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 727.00 | 21.52 | 69.50 | 21.46 | 69.50 | 21.42 |
February | 654.33 | 21.72 | 44.50 | 21.68 | 44.50 | 21.65 |
March | 741.00 | 21.85 | 44.83 | 21.80 | 44.83 | 21.76 |
April | 705.50 | 21.88 | 5.17 | 21.87 | 5.17 | 21.87 |
May | 708.00 | 21.83 | 0.50 | 21.83 | 0.00 | 21.83 |
June | 639.33 | 21.73 | 3.17 | 21.74 | 0.00 | 21.74 |
July | 603.17 | 21.62 | 54.83 | 21.77 | 52.67 | 21.89 |
August | 597.50 | 21.62 | 34.00 | 21.72 | 28.00 | 21.78 |
September | 541.50 | 21.68 | 119.67 | 22.00 | 49.67 | 22.10 |
October | 531.67 | 21.59 | 112.67 | 22.06 | 10.83 | 22.09 |
November | 643.67 | 21.60 | 46.00 | 21.60 | 36.00 | 21.56 |
December | 742.50 | 21.54 | 123.33 | 21.46 | 123.33 | 21.40 |
Annual Sum or Average | 7835.17 | 21.69 | 658.17 | 21.74 | 464.50 | 21.74 |
Minimum of Months | 531.67 | 21.52 | 0.50 | 21.46 | 0.00 | 21.40 |
Maximum of Months | 742.50 | 21.88 | 123.33 | 22.06 | 123.33 | 22.10 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 353.67 | 23.44 | 41.67 | 23.51 | 0.00 | 23.51 |
February | 270.83 | 23.51 | 45.50 | 23.59 | 0.00 | 23.59 |
March | 189.67 | 23.51 | 24.50 | 23.57 | 0.00 | 23.57 |
April | 29.67 | 23.55 | 229.83 | 23.94 | 0.00 | 23.94 |
May | 72.83 | 23.99 | 544.17 | 23.99 | 72.50 | 23.99 |
June | 152.17 | 24.00 | 680.50 | 24.00 | 152.17 | 24.00 |
July | 568.00 | 24.00 | 744.00 | 24.00 | 568.00 | 24.00 |
August | 436.00 | 23.99 | 744.00 | 23.99 | 436.00 | 23.99 |
September | 392.50 | 24.00 | 715.17 | 23.99 | 392.50 | 23.99 |
October | 173.83 | 23.96 | 597.00 | 23.97 | 167.00 | 23.97 |
November | 201.83 | 23.47 | 107.00 | 23.65 | 0.83 | 23.65 |
December | 432.83 | 23.47 | 4.67 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 3273.83 | 23.76 | 4478.00 | 23.89 | 1789.00 | 23.91 |
Minimum of Months | 29.67 | 23.44 | 4.67 | 23.48 | 0.00 | 23.48 |
Maximum of Months | 568.00 | 24.00 | 744.00 | 24.00 | 568.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 150.33 | 23.47 | 153.50 | 23.75 | 0.00 | 23.75 |
February | 75.33 | 23.43 | 72.17 | 23.73 | 0.00 | 23.73 |
March | 52.17 | 23.51 | 57.00 | 23.80 | 0.00 | 23.80 |
April | 3.33 | 23.53 | 319.67 | 23.99 | 0.00 | 23.99 |
May | 64.33 | 24.00 | 597.33 | 24.00 | 64.33 | 24.00 |
June | 140.33 | 24.00 | 691.33 | 24.00 | 140.33 | 24.00 |
July | 533.33 | 24.00 | 744.00 | 24.00 | 533.33 | 24.00 |
August | 414.00 | 24.00 | 744.00 | 24.00 | 414.00 | 24.00 |
September | 377.17 | 24.00 | 720.00 | 23.99 | 377.17 | 24.00 |
October | 152.17 | 23.99 | 657.00 | 23.99 | 151.00 | 23.99 |
November | 57.33 | 23.41 | 177.17 | 23.84 | 0.00 | 23.84 |
December | 191.67 | 23.46 | 44.17 | 23.57 | 0.00 | 23.57 |
Annual Sum or Average | 2211.50 | 23.87 | 4977.33 | 23.96 | 1680.17 | 23.96 |
Minimum of Months | 3.33 | 23.41 | 44.17 | 23.57 | 0.00 | 23.57 |
Maximum of Months | 533.33 | 24.00 | 744.00 | 24.00 | 533.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.00 | 24.18 | 700.17 | 24.11 | 498.67 | 24.13 |
February | 456.50 | 24.10 | 636.67 | 24.05 | 455.17 | 24.07 |
March | 506.83 | 24.07 | 725.50 | 24.03 | 506.17 | 24.04 |
April | 510.00 | 24.02 | 715.50 | 24.00 | 510.00 | 24.01 |
May | 551.83 | 23.99 | 744.00 | 23.99 | 551.83 | 23.99 |
June | 589.33 | 23.99 | 720.00 | 23.99 | 589.33 | 23.99 |
July | 739.33 | 23.99 | 744.00 | 23.99 | 739.33 | 23.99 |
August | 681.67 | 23.99 | 744.00 | 23.99 | 681.67 | 23.99 |
September | 646.67 | 23.99 | 720.00 | 23.99 | 646.67 | 23.99 |
October | 564.50 | 23.99 | 744.00 | 23.98 | 564.50 | 23.98 |
November | 495.83 | 24.07 | 694.00 | 24.02 | 495.83 | 24.04 |
December | 491.17 | 24.18 | 680.33 | 24.12 | 489.33 | 24.14 |
Annual Sum or Average | 6732.67 | 24.04 | 8568.17 | 24.02 | 6728.50 | 24.03 |
Minimum of Months | 456.50 | 23.99 | 636.67 | 23.98 | 455.17 | 23.98 |
Maximum of Months | 739.33 | 24.18 | 744.00 | 24.12 | 739.33 | 24.14 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.29 | 17.83 | 21.28 | 17.83 | 21.28 |
February | 672.00 | 21.54 | 1.67 | 21.54 | 1.67 | 21.54 |
March | 744.00 | 21.80 | 1.17 | 21.80 | 1.17 | 21.80 |
April | 680.17 | 22.76 | 1.17 | 22.77 | 0.00 | 22.77 |
May | 382.67 | 23.22 | 127.00 | 23.39 | 6.67 | 23.39 |
June | 89.83 | 23.65 | 391.67 | 23.88 | 34.83 | 23.87 |
July | 334.00 | 23.81 | 742.00 | 23.87 | 334.00 | 23.86 |
August | 211.67 | 23.65 | 619.83 | 23.80 | 191.67 | 23.77 |
September | 339.00 | 23.40 | 479.50 | 23.62 | 202.50 | 23.61 |
October | 605.83 | 22.74 | 113.17 | 22.89 | 40.17 | 22.91 |
November | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
December | 744.00 | 21.19 | 27.17 | 21.19 | 27.17 | 21.18 |
Annual Sum or Average | 6267.17 | 22.21 | 2522.17 | 22.67 | 857.67 | 22.74 |
Minimum of Months | 89.83 | 21.19 | 0.00 | 21.19 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 23.81 | 742.00 | 23.88 | 334.00 | 23.87 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76254 | 24.82328 | 0.17693 | 5.76949 |
February | 672.00000 | 23.04265 | 22.67448 | -0.0246 | 5.20864 |
March | 744.00000 | 22.34981 | 21.87949 | -0.2025 | 6.01875 |
April | 720.00000 | 22.41295 | 25.29765 | -0.1636 | 5.75205 |
May | 744.00000 | 22.69248 | 36.04797 | -1.0648 | 29.24347 |
June | 720.00000 | 22.98612 | 44.59907 | -0.9010 | 22.53109 |
July | 744.00000 | 23.71705 | 56.99694 | -0.5444 | 11.42570 |
August | 744.00000 | 23.91786 | 52.64315 | -0.4845 | 9.99175 |
September | 720.00000 | 23.98705 | 49.07992 | -0.4683 | 9.69887 |
October | 744.00000 | 23.99181 | 39.75806 | 0.36677 | 7.93504 |
November | 720.00000 | 23.99044 | 24.38928 | 0.25474 | 6.41673 |
December | 744.00000 | 23.95325 | 21.99737 | 0.21827 | 6.04782 |
Annual Sum or Average | 8760.00000 | 23.40389 | 35.10794 | -0.2372 | 10.54027 |
Minimum of Months | 672.00000 | 22.34981 | 21.87949 | -1.0648 | 5.20864 |
Maximum of Months | 744.00000 | 23.99181 | 56.99694 | 0.36677 | 29.24347 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.96107 | 26.44692 | -0.2059 | 7.74990 |
February | 672.00000 | 22.08152 | 22.99773 | -0.1852 | 7.40868 |
March | 744.00000 | 22.12100 | 21.34599 | -0.1826 | 7.11596 |
April | 720.00000 | 22.80320 | 23.85230 | 0.02637 | 6.43469 |
May | 744.00000 | 23.30983 | 33.82770 | -0.7029 | 17.12309 |
June | 720.00000 | 23.72602 | 41.77434 | -0.4692 | 10.21337 |
July | 744.00000 | 23.75273 | 56.32244 | -0.3580 | 8.08658 |
August | 744.00000 | 23.67519 | 52.90160 | -0.4062 | 9.23041 |
September | 720.00000 | 23.62389 | 49.93883 | -0.4323 | 10.27797 |
October | 744.00000 | 23.11600 | 41.73126 | 0.25173 | 7.89296 |
November | 720.00000 | 22.39531 | 26.40967 | -0.0659 | 7.41456 |
December | 744.00000 | 21.84895 | 24.01853 | -0.2605 | 8.20807 |
Annual Sum or Average | 8760.00000 | 22.87140 | 35.22635 | -0.2499 | 8.94596 |
Minimum of Months | 672.00000 | 21.84895 | 21.34599 | -0.7029 | 6.43469 |
Maximum of Months | 744.00000 | 23.75273 | 56.32244 | 0.25173 | 17.12309 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.83875 | 26.99487 | -0.0128 | 5.32721 |
February | 672.00000 | 22.96124 | 23.65401 | -0.0014 | 5.28962 |
March | 744.00000 | 23.08141 | 22.05408 | 0.02054 | 5.33327 |
April | 720.00000 | 23.51852 | 24.63668 | 0.15853 | 5.86977 |
May | 744.00000 | 23.75609 | 34.47710 | -0.6147 | 13.40074 |
June | 720.00000 | 23.89188 | 42.60884 | -0.4915 | 10.27684 |
July | 744.00000 | 23.90462 | 56.84512 | -0.3885 | 8.24656 |
August | 744.00000 | 23.88440 | 53.47265 | -0.4223 | 8.86354 |
September | 720.00000 | 23.89182 | 50.48361 | -0.4430 | 9.32390 |
October | 744.00000 | 23.66782 | 41.95922 | 0.32050 | 7.41880 |
November | 720.00000 | 23.22630 | 27.00309 | 0.09243 | 5.60039 |
December | 744.00000 | 22.70222 | 24.75490 | -0.0630 | 5.37458 |
Annual Sum or Average | 8760.00000 | 23.44566 | 35.83993 | -0.1548 | 7.54286 |
Minimum of Months | 672.00000 | 22.70222 | 22.05408 | -0.6147 | 5.28962 |
Maximum of Months | 744.00000 | 23.90462 | 56.84512 | 0.32050 | 13.40074 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.47107 | 21.84893 | 0.70486 | 17.59981 |
February | 672.00000 | 23.47677 | 18.75257 | 0.69914 | 17.31299 |
March | 744.00000 | 23.49662 | 17.26035 | 0.70805 | 17.45366 |
April | 720.00000 | 23.52691 | 20.46080 | 0.77093 | 19.34647 |
May | 744.00000 | 23.54693 | 31.01003 | 0.21491 | 9.70846 |
June | 720.00000 | 23.55972 | 39.81422 | 0.30970 | 10.41210 |
July | 744.00000 | 23.55621 | 54.19492 | 0.40040 | 11.45952 |
August | 744.00000 | 23.53987 | 50.77730 | 0.36532 | 11.12801 |
September | 720.00000 | 23.52913 | 47.66677 | 0.32770 | 10.62637 |
October | 744.00000 | 23.49124 | 38.25137 | 0.87842 | 23.03120 |
November | 720.00000 | 23.48487 | 22.34325 | 0.73385 | 18.30624 |
December | 744.00000 | 23.48131 | 19.58528 | 0.68471 | 17.11105 |
Annual Sum or Average | 8760.00000 | 23.51356 | 31.92985 | 0.56575 | 15.28149 |
Minimum of Months | 672.00000 | 23.47107 | 17.26035 | 0.21491 | 9.70846 |
Maximum of Months | 744.00000 | 23.55972 | 54.19492 | 0.87842 | 23.03120 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.28009 | 30.87984 | 0.16810 | 6.52221 |
February | 672.00000 | 23.40088 | 27.60749 | 0.18641 | 6.39945 |
March | 744.00000 | 23.40332 | 26.14575 | 0.17549 | 6.28978 |
April | 720.00000 | 23.64028 | 28.61984 | 0.28370 | 7.20893 |
May | 744.00000 | 23.74563 | 38.49129 | -0.4820 | 10.53027 |
June | 720.00000 | 23.85302 | 46.36303 | -0.3428 | 7.75963 |
July | 744.00000 | 23.87403 | 60.49642 | -0.2334 | 6.32029 |
August | 744.00000 | 23.86486 | 57.01988 | -0.2574 | 6.69759 |
September | 720.00000 | 23.92051 | 53.84373 | -0.2499 | 6.79962 |
October | 744.00000 | 23.78562 | 45.36705 | 0.47532 | 10.30017 |
November | 720.00000 | 23.49811 | 30.77735 | 0.25678 | 7.48972 |
December | 744.00000 | 23.16959 | 28.68390 | 0.11680 | 6.28197 |
Annual Sum or Average | 8760.00000 | 23.62027 | 39.61845 | 0.00685 | 7.39214 |
Minimum of Months | 672.00000 | 23.16959 | 26.14575 | -0.4820 | 6.28197 |
Maximum of Months | 744.00000 | 23.92051 | 60.49642 | 0.47532 | 10.53027 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.41534 | 29.79163 | 0.15115 | 5.76031 |
February | 672.00000 | 23.48885 | 26.56364 | 0.15225 | 5.72563 |
March | 744.00000 | 23.49130 | 25.03283 | 0.14592 | 5.71287 |
April | 720.00000 | 23.68286 | 27.51235 | 0.23059 | 6.36731 |
May | 744.00000 | 23.78054 | 37.24552 | -0.5637 | 12.05424 |
June | 720.00000 | 23.87194 | 45.31358 | -0.4510 | 9.48545 |
July | 744.00000 | 23.89184 | 59.47246 | -0.3441 | 7.56280 |
August | 744.00000 | 23.89384 | 56.04790 | -0.3700 | 7.96854 |
September | 720.00000 | 23.93105 | 53.01340 | -0.3807 | 8.18797 |
October | 744.00000 | 23.84856 | 44.36252 | 0.40211 | 8.58296 |
November | 720.00000 | 23.65189 | 29.73984 | 0.22568 | 6.37947 |
December | 744.00000 | 23.33094 | 27.61899 | 0.11174 | 5.54728 |
Annual Sum or Average | 8760.00000 | 23.69053 | 38.56955 | -0.0588 | 7.45694 |
Minimum of Months | 672.00000 | 23.33094 | 25.03283 | -0.5637 | 5.54728 |
Maximum of Months | 744.00000 | 23.93105 | 59.47246 | 0.40211 | 12.05424 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.27914 | 31.40868 | -0.4442 | 9.78632 |
February | 672.00000 | 21.51686 | 27.43850 | -0.3886 | 9.09088 |
March | 744.00000 | 21.78084 | 25.75180 | -0.3063 | 8.23672 |
April | 720.00000 | 21.98867 | 28.74568 | -0.1669 | 6.93647 |
May | 744.00000 | 21.99204 | 37.10976 | -1.1243 | 33.32040 |
June | 720.00000 | 21.97638 | 42.46499 | -1.0409 | 29.56975 |
July | 744.00000 | 21.99418 | 50.93855 | -0.9909 | 27.61921 |
August | 744.00000 | 22.01954 | 49.62434 | -1.0061 | 28.24348 |
September | 720.00000 | 22.15634 | 48.60727 | -0.9810 | 27.47722 |
October | 744.00000 | 22.22605 | 44.59995 | -0.0105 | 6.60804 |
November | 720.00000 | 21.63834 | 31.64436 | -0.3055 | 8.30029 |
December | 744.00000 | 21.22229 | 28.39227 | -0.4922 | 10.65070 |
Annual Sum or Average | 8760.00000 | 21.81699 | 37.30064 | -0.6064 | 17.20950 |
Minimum of Months | 672.00000 | 21.22229 | 25.75180 | -1.1243 | 6.60804 |
Maximum of Months | 744.00000 | 22.22605 | 50.93855 | -0.0105 | 33.32040 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90204 | 31.97312 | -0.5737 | 12.23356 |
February | 672.00000 | 21.15264 | 27.89330 | -0.5105 | 11.01950 |
March | 744.00000 | 21.51389 | 26.07713 | -0.3929 | 9.11407 |
April | 720.00000 | 21.89840 | 28.88317 | -0.2021 | 7.05001 |
May | 744.00000 | 21.98468 | 37.13463 | -1.1316 | 33.62381 |
June | 720.00000 | 21.99172 | 42.44100 | -1.0349 | 29.37143 |
July | 744.00000 | 22.00418 | 50.97308 | -0.9888 | 27.56794 |
August | 744.00000 | 22.00883 | 49.92169 | -1.0209 | 28.77786 |
September | 720.00000 | 22.08832 | 49.41589 | -1.0324 | 29.30123 |
October | 744.00000 | 22.00240 | 45.65507 | -0.0906 | 6.30413 |
November | 720.00000 | 21.30662 | 32.19347 | -0.4266 | 9.60709 |
December | 744.00000 | 20.83322 | 28.92057 | -0.6251 | 13.48617 |
Annual Sum or Average | 8760.00000 | 21.64261 | 37.69680 | -0.6704 | 18.17198 |
Minimum of Months | 672.00000 | 20.83322 | 26.07713 | -1.1316 | 6.30413 |
Maximum of Months | 744.00000 | 22.08832 | 50.97308 | -0.0906 | 33.62381 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96221 | 30.51469 | -0.5406 | 11.28261 |
February | 672.00000 | 21.06544 | 26.51480 | -0.5229 | 10.88823 |
March | 744.00000 | 21.24692 | 24.89501 | -0.4687 | 9.72575 |
April | 720.00000 | 21.55894 | 27.79999 | -0.3405 | 7.82054 |
May | 744.00000 | 21.76684 | 36.60837 | -1.3240 | 42.11009 |
June | 720.00000 | 21.85679 | 42.54463 | -1.2273 | 37.45731 |
July | 744.00000 | 21.86821 | 52.27956 | -1.1665 | 34.67886 |
August | 744.00000 | 21.82870 | 50.78058 | -1.2057 | 36.34832 |
September | 720.00000 | 21.81566 | 49.86558 | -1.2392 | 37.88445 |
October | 744.00000 | 21.58900 | 45.12814 | -0.2376 | 6.55603 |
November | 720.00000 | 21.09351 | 31.00602 | -0.4845 | 10.09699 |
December | 744.00000 | 20.92871 | 27.52604 | -0.5737 | 12.04565 |
Annual Sum or Average | 8760.00000 | 21.46709 | 37.20166 | -0.7792 | 21.47347 |
Minimum of Months | 672.00000 | 20.92871 | 24.89501 | -1.3240 | 6.55603 |
Maximum of Months | 744.00000 | 21.86821 | 52.27956 | -0.2376 | 42.11009 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28434 | 31.37013 | -0.4455 | 9.68157 |
February | 672.00000 | 21.55250 | 27.35748 | -0.3723 | 8.72685 |
March | 744.00000 | 21.77330 | 25.74162 | -0.3030 | 7.90214 |
April | 720.00000 | 22.07523 | 28.55001 | -0.1399 | 6.83312 |
May | 744.00000 | 22.18265 | 36.82639 | -1.0598 | 31.70475 |
June | 720.00000 | 22.12501 | 42.35606 | -0.9865 | 28.71611 |
July | 744.00000 | 22.11750 | 50.72608 | -0.9457 | 27.02962 |
August | 744.00000 | 22.14718 | 49.48381 | -0.9603 | 27.54512 |
September | 720.00000 | 22.31049 | 48.30210 | -0.9315 | 26.81716 |
October | 744.00000 | 22.13969 | 44.95428 | -0.0336 | 6.36042 |
November | 720.00000 | 21.64427 | 31.63094 | -0.3074 | 8.22371 |
December | 744.00000 | 21.22162 | 28.35140 | -0.4904 | 10.49921 |
Annual Sum or Average | 8760.00000 | 21.88212 | 37.21164 | -0.5829 | 16.72455 |
Minimum of Months | 672.00000 | 21.22162 | 25.74162 | -1.0598 | 6.36042 |
Maximum of Months | 744.00000 | 22.31049 | 50.72608 | -0.0336 | 31.70475 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.87974 | 31.94884 | -0.5806 | 12.30602 |
February | 672.00000 | 21.15924 | 27.81630 | -0.4988 | 10.63252 |
March | 744.00000 | 21.51208 | 26.04794 | -0.3882 | 8.74829 |
April | 720.00000 | 22.02004 | 28.65164 | -0.1678 | 6.89683 |
May | 744.00000 | 22.18295 | 36.85244 | -1.0649 | 31.93325 |
June | 720.00000 | 22.13689 | 42.38778 | -0.9813 | 28.62092 |
July | 744.00000 | 22.12539 | 50.79789 | -0.9441 | 27.03567 |
August | 744.00000 | 22.14071 | 49.72825 | -0.9739 | 28.01346 |
September | 720.00000 | 22.26011 | 48.75594 | -0.9795 | 28.34382 |
October | 744.00000 | 21.95042 | 45.74127 | -0.1083 | 6.21933 |
November | 720.00000 | 21.22868 | 32.26722 | -0.4447 | 9.72788 |
December | 744.00000 | 20.81930 | 28.86944 | -0.6256 | 13.51153 |
Annual Sum or Average | 8760.00000 | 21.70345 | 37.56247 | -0.6477 | 17.71558 |
Minimum of Months | 672.00000 | 20.81930 | 26.04794 | -1.0649 | 6.21933 |
Maximum of Months | 744.00000 | 22.26011 | 50.79789 | -0.1083 | 31.93325 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.19236 | 31.75638 | -0.4963 | 10.95819 |
February | 672.00000 | 21.45678 | 27.69633 | -0.4301 | 10.08094 |
March | 744.00000 | 21.74950 | 25.94031 | -0.3349 | 9.01375 |
April | 720.00000 | 21.96090 | 28.87063 | -0.1793 | 7.31906 |
May | 744.00000 | 21.95178 | 37.36570 | -1.1359 | 34.06109 |
June | 720.00000 | 21.94909 | 42.73164 | -1.0370 | 29.58183 |
July | 744.00000 | 21.96945 | 51.32345 | -0.9855 | 27.52982 |
August | 744.00000 | 21.98270 | 50.18256 | -1.0082 | 28.49088 |
September | 720.00000 | 22.10009 | 49.35597 | -0.9968 | 28.29209 |
October | 744.00000 | 22.20355 | 45.39604 | -0.0233 | 6.93715 |
November | 720.00000 | 21.57918 | 31.98013 | -0.3480 | 9.19221 |
December | 744.00000 | 21.13717 | 28.71284 | -0.5459 | 11.94205 |
Annual Sum or Average | 8760.00000 | 21.77055 | 37.68396 | -0.6282 | 17.83765 |
Minimum of Months | 672.00000 | 21.13717 | 25.94031 | -1.1359 | 6.93715 |
Maximum of Months | 744.00000 | 22.20355 | 51.32345 | -0.0233 | 34.06109 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78845 | 32.36763 | -0.6343 | 13.85690 |
February | 672.00000 | 21.06040 | 28.19097 | -0.5624 | 12.35283 |
March | 744.00000 | 21.45193 | 26.27736 | -0.4314 | 10.02578 |
April | 720.00000 | 21.86980 | 29.01264 | -0.2160 | 7.44440 |
May | 744.00000 | 21.94245 | 37.38573 | -1.1440 | 34.37083 |
June | 720.00000 | 21.96421 | 42.70391 | -1.0310 | 29.36024 |
July | 744.00000 | 21.97918 | 51.37042 | -0.9833 | 27.45747 |
August | 744.00000 | 21.97238 | 50.51279 | -1.0229 | 29.01016 |
September | 720.00000 | 22.02930 | 50.25384 | -1.0503 | 30.21800 |
October | 744.00000 | 21.95007 | 46.59042 | -0.1132 | 6.60450 |
November | 720.00000 | 21.19918 | 32.60212 | -0.4852 | 10.87171 |
December | 744.00000 | 20.72607 | 29.28152 | -0.6860 | 15.23465 |
Annual Sum or Average | 8760.00000 | 21.57998 | 38.12023 | -0.6978 | 18.94816 |
Minimum of Months | 672.00000 | 20.72607 | 26.27736 | -1.1440 | 6.60450 |
Maximum of Months | 744.00000 | 22.02930 | 51.37042 | -0.1132 | 34.37083 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56028 | 32.71263 | -0.3209 | 8.42821 |
February | 672.00000 | 21.77335 | 28.62956 | -0.2821 | 8.08584 |
March | 744.00000 | 21.85915 | 26.95871 | -0.2742 | 7.88527 |
April | 720.00000 | 21.91055 | 29.80069 | -0.2042 | 7.05004 |
May | 744.00000 | 21.90854 | 38.15735 | -1.2146 | 37.29261 |
June | 720.00000 | 21.91895 | 43.58045 | -1.1293 | 33.30440 |
July | 744.00000 | 21.94960 | 52.08911 | -1.0643 | 30.58355 |
August | 744.00000 | 21.97417 | 50.43607 | -1.0664 | 30.74545 |
September | 720.00000 | 22.12586 | 49.22884 | -1.0152 | 29.01534 |
October | 744.00000 | 22.28037 | 44.68497 | 0.01150 | 6.88357 |
November | 720.00000 | 21.81766 | 32.57369 | -0.2215 | 7.87213 |
December | 744.00000 | 21.54770 | 29.82980 | -0.3507 | 8.83157 |
Annual Sum or Average | 8760.00000 | 21.88580 | 38.29607 | -0.5964 | 18.06525 |
Minimum of Months | 672.00000 | 21.54770 | 26.95871 | -1.2146 | 6.88357 |
Maximum of Months | 744.00000 | 22.28037 | 52.08911 | 0.01150 | 37.29261 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.72924 | 29.97753 | 0.24147 | 6.50873 |
February | 672.00000 | 23.80096 | 26.69091 | 0.25353 | 6.56646 |
March | 744.00000 | 23.86189 | 24.86829 | 0.27723 | 6.74811 |
April | 720.00000 | 23.96108 | 27.28790 | 0.37026 | 8.03460 |
May | 744.00000 | 23.98802 | 37.01815 | -0.3588 | 7.96534 |
June | 720.00000 | 23.99535 | 45.19506 | -0.2534 | 6.49263 |
July | 744.00000 | 23.99515 | 59.19883 | -0.1589 | 5.54563 |
August | 744.00000 | 23.99354 | 55.95890 | -0.1988 | 5.88523 |
September | 720.00000 | 23.98995 | 53.19884 | -0.2479 | 6.45653 |
October | 744.00000 | 23.94727 | 44.59401 | 0.48114 | 10.06641 |
November | 720.00000 | 23.81980 | 30.12451 | 0.28999 | 6.97616 |
December | 744.00000 | 23.69603 | 27.97718 | 0.20842 | 6.18210 |
Annual Sum or Average | 8760.00000 | 23.89851 | 38.59977 | 0.07428 | 6.95509 |
Minimum of Months | 672.00000 | 23.69603 | 24.86829 | -0.3588 | 5.54563 |
Maximum of Months | 744.00000 | 23.99535 | 59.19883 | 0.48114 | 10.06641 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.87002 | 29.02171 | 0.31526 | 7.25563 |
February | 672.00000 | 23.91420 | 25.81528 | 0.31933 | 7.26683 |
March | 744.00000 | 23.95153 | 24.08105 | 0.33624 | 7.43952 |
April | 720.00000 | 23.98744 | 26.70423 | 0.40875 | 8.64003 |
May | 744.00000 | 23.99393 | 36.58495 | -0.3166 | 7.35762 |
June | 720.00000 | 23.99633 | 44.83699 | -0.2165 | 6.13661 |
July | 744.00000 | 23.99607 | 58.83320 | -0.1222 | 5.33371 |
August | 744.00000 | 23.99536 | 55.57485 | -0.1611 | 5.60473 |
September | 720.00000 | 23.99425 | 52.76996 | -0.2082 | 6.07026 |
October | 744.00000 | 23.97782 | 43.99252 | 0.51862 | 10.82815 |
November | 720.00000 | 23.91942 | 29.28719 | 0.35023 | 7.70456 |
December | 744.00000 | 23.85273 | 27.01783 | 0.28678 | 6.87469 |
Annual Sum or Average | 8760.00000 | 23.95420 | 37.97005 | 0.12475 | 7.20967 |
Minimum of Months | 672.00000 | 23.85273 | 24.08105 | -0.3166 | 5.33371 |
Maximum of Months | 744.00000 | 23.99633 | 58.83320 | 0.51862 | 10.82815 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.00250 | 28.19850 | 0.98221 | 27.46762 |
February | 672.00000 | 23.97369 | 25.09192 | 0.97875 | 27.16935 |
March | 744.00000 | 23.98255 | 23.57621 | 0.99504 | 27.74169 |
April | 720.00000 | 23.98826 | 26.37665 | 1.07830 | 31.29278 |
May | 744.00000 | 23.98900 | 36.29609 | 0.64780 | 17.86695 |
June | 720.00000 | 23.99229 | 44.52060 | 0.75930 | 20.63754 |
July | 744.00000 | 23.99290 | 58.15816 | 0.84745 | 23.25922 |
August | 744.00000 | 23.99279 | 54.90233 | 0.80651 | 22.00046 |
September | 720.00000 | 23.99030 | 51.99824 | 0.75996 | 20.71280 |
October | 744.00000 | 23.96733 | 43.17560 | 1.17499 | 35.44579 |
November | 720.00000 | 23.95794 | 28.52737 | 1.00630 | 28.31356 |
December | 744.00000 | 23.98643 | 26.11283 | 0.95340 | 26.40746 |
Annual Sum or Average | 8760.00000 | 23.98478 | 37.33773 | 0.91548 | 25.68577 |
Minimum of Months | 672.00000 | 23.95794 | 23.57621 | 0.64780 | 17.86695 |
Maximum of Months | 744.00000 | 24.00250 | 58.15816 | 1.17499 | 35.44579 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20732 | 25.80394 | -0.4351 | 9.06898 |
February | 672.00000 | 21.40152 | 22.00064 | -0.4092 | 8.65470 |
March | 744.00000 | 21.63454 | 20.17245 | -0.3618 | 7.88871 |
April | 720.00000 | 22.52002 | 22.59530 | -0.1299 | 5.69809 |
May | 744.00000 | 23.30112 | 32.21044 | -0.8474 | 20.79969 |
June | 720.00000 | 23.82560 | 40.02615 | -0.6067 | 12.88131 |
July | 744.00000 | 23.85128 | 54.65189 | -0.4965 | 10.20462 |
August | 744.00000 | 23.71379 | 51.35149 | -0.5708 | 11.99457 |
September | 720.00000 | 23.45540 | 49.02748 | -0.6784 | 15.07426 |
October | 744.00000 | 22.73573 | 40.97486 | 0.04319 | 5.44395 |
November | 720.00000 | 21.76222 | 25.57730 | -0.2975 | 7.17002 |
December | 744.00000 | 21.14009 | 23.21369 | -0.4707 | 9.68899 |
Annual Sum or Average | 8760.00000 | 22.55134 | 34.06177 | -0.4388 | 10.39676 |
Minimum of Months | 672.00000 | 21.14009 | 20.17245 | -0.8474 | 5.44395 |
Maximum of Months | 744.00000 | 23.85128 | 54.65189 | 0.04319 | 20.79969 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32775 | 29.25872 | -0.4120 | 8.65150 |
February | 672.00000 | 21.62233 | 25.36629 | -0.3614 | 7.86278 |
March | 744.00000 | 21.95699 | 23.49781 | -0.2906 | 6.91887 |
April | 720.00000 | 22.80283 | 25.99254 | -0.0675 | 5.35314 |
May | 744.00000 | 23.45924 | 35.74536 | -0.8091 | 19.32858 |
June | 720.00000 | 23.85956 | 43.65881 | -0.6110 | 12.97902 |
July | 744.00000 | 23.83906 | 58.12493 | -0.5199 | 10.69528 |
August | 744.00000 | 23.76968 | 54.82430 | -0.5685 | 11.89963 |
September | 720.00000 | 23.72814 | 51.94068 | -0.6022 | 12.84891 |
October | 744.00000 | 23.10029 | 43.87954 | 0.12445 | 5.62653 |
November | 720.00000 | 22.12987 | 28.74778 | -0.2156 | 6.36199 |
December | 744.00000 | 21.18787 | 26.74778 | -0.4626 | 9.51204 |
Annual Sum or Average | 8760.00000 | 22.73673 | 37.41064 | -0.4002 | 9.85768 |
Minimum of Months | 672.00000 | 21.18787 | 23.49781 | -0.8091 | 5.35314 |
Maximum of Months | 744.00000 | 23.85956 | 58.12493 | 0.12445 | 19.32858 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28795 | 27.04972 | -0.4110 | 8.69579 |
February | 672.00000 | 21.53903 | 23.25603 | -0.3656 | 8.03983 |
March | 744.00000 | 21.80288 | 21.35876 | -0.3074 | 7.26291 |
April | 720.00000 | 22.82363 | 23.55466 | -0.0338 | 5.66392 |
May | 744.00000 | 23.54162 | 33.17201 | -0.7249 | 16.97101 |
June | 720.00000 | 23.89828 | 41.09583 | -0.5238 | 10.97535 |
July | 744.00000 | 23.90109 | 55.38628 | -0.4254 | 8.85070 |
August | 744.00000 | 23.81792 | 52.18168 | -0.4833 | 10.10386 |
September | 720.00000 | 23.66581 | 49.59998 | -0.5626 | 12.24755 |
October | 744.00000 | 22.93787 | 41.83239 | 0.11504 | 5.94743 |
November | 720.00000 | 21.82288 | 26.86684 | -0.2708 | 7.07228 |
December | 744.00000 | 21.19425 | 24.52944 | -0.4556 | 9.43031 |
Annual Sum or Average | 8760.00000 | 22.69151 | 35.08358 | -0.3710 | 9.28496 |
Minimum of Months | 672.00000 | 21.19425 | 21.35876 | -0.7249 | 5.66392 |
Maximum of Months | 744.00000 | 23.90109 | 55.38628 | 0.11504 | 16.97101 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50366 | 25.15518 | -0.3730 | 8.07683 |
February | 672.00000 | 21.70079 | 21.41840 | -0.3474 | 7.73566 |
March | 744.00000 | 21.97218 | 19.59545 | -0.2926 | 6.98161 |
April | 720.00000 | 22.84935 | 21.98127 | -0.0631 | 5.44127 |
May | 744.00000 | 23.57832 | 31.46818 | -0.7663 | 17.97204 |
June | 720.00000 | 23.93502 | 39.52316 | -0.5739 | 12.03612 |
July | 744.00000 | 23.95152 | 54.12185 | -0.4659 | 9.56278 |
August | 744.00000 | 23.87854 | 50.63889 | -0.5214 | 10.79207 |
September | 720.00000 | 23.73226 | 48.07064 | -0.5958 | 12.78449 |
October | 744.00000 | 23.08216 | 39.98456 | 0.11438 | 5.65623 |
November | 720.00000 | 22.11128 | 24.86971 | -0.2250 | 6.43281 |
December | 744.00000 | 21.38176 | 22.69664 | -0.4186 | 8.77658 |
Annual Sum or Average | 8760.00000 | 22.81165 | 33.38779 | -0.3778 | 9.36932 |
Minimum of Months | 672.00000 | 21.38176 | 19.59545 | -0.7663 | 5.44127 |
Maximum of Months | 744.00000 | 23.95152 | 54.12185 | 0.11438 | 17.97204 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.112019E+11 | 54104.78 | 03-JAN-16:01 | 492.14 | 0.338468E+11 | 0.00 | 0.450487E+11 | 2.04 | 3.12 | 01-JAN-00:50 | 0.00 | 0.00 |
February | 0.232326E+11 | 87531.30 | 22-FEB-16:01 | 516.04 | 0.672003E+11 | 0.00 | 0.904329E+11 | 2.33 | 3.71 | 06-FEB-22:51 | 0.00 | 0.00 |
March | 0.390806E+11 | 97816.21 | 22-MAR-15:01 | 626.53 | 0.111764E+12 | 0.00 | 0.150844E+12 | 2.52 | 3.94 | 15-MAR-21:51 | 0.00 | 0.00 |
April | 0.107382E+12 | 135213.86 | 21-APR-18:03 | 708.74 | 0.318699E+12 | 0.00 | 0.426081E+12 | 2.92 | 4.15 | 28-APR-21:51 | 0.00 | 0.00 |
May | 0.174077E+12 | 148535.27 | 19-MAY-18:03 | 743.72 | 0.521769E+12 | 0.00 | 0.695846E+12 | 2.97 | 4.02 | 24-MAY-21:52 | 0.00 | 0.00 |
June | 0.229712E+12 | 188928.28 | 14-JUN-18:03 | 720.00 | 0.680111E+12 | 0.00 | 0.909823E+12 | 2.96 | 3.90 | 24-JUN-21:53 | 0.00 | 0.00 |
July | 0.269101E+12 | 180850.80 | 26-JUL-18:03 | 744.00 | 0.874227E+12 | 0.00 | 0.114333E+13 | 3.26 | 4.50 | 18-JUL-21:52 | 0.00 | 0.00 |
August | 0.232177E+12 | 172575.56 | 04-AUG-18:03 | 744.00 | 0.727324E+12 | 0.00 | 0.959502E+12 | 3.11 | 4.28 | 16-AUG-21:53 | 0.00 | 0.00 |
September | 0.188375E+12 | 148901.93 | 01-SEP-18:03 | 720.00 | 0.607097E+12 | 0.00 | 0.795472E+12 | 3.17 | 4.40 | 03-SEP-21:52 | 0.00 | 0.00 |
October | 0.105611E+12 | 148873.69 | 04-OCT-18:02 | 740.67 | 0.324842E+12 | 0.00 | 0.430453E+12 | 3.02 | 4.37 | 03-OCT-21:52 | 0.00 | 0.00 |
November | 0.318663E+11 | 91640.73 | 09-NOV-16:01 | 575.45 | 0.933600E+11 | 0.00 | 0.125226E+12 | 2.42 | 3.70 | 09-NOV-16:01 | 0.00 | 0.00 |
December | 0.850762E+10 | 30891.14 | 23-DEC-15:00 | 463.11 | 0.259711E+11 | 0.00 | 0.344787E+11 | 1.93 | 3.12 | 01-DEC-05:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.142033E+13 | 7794.40 | 0.438621E+13 | 0.00 | 0.580654E+13 | 2.72 | 0.00 | 0.00 | ||||
Minimum of Months | 0.850762E+10 | 30891.14 | 463.11 | 0.259711E+11 | 0.00 | 0.344787E+11 | 1.93 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.269101E+12 | 188928.28 | 744.00 | 0.874227E+12 | 0.00 | 0.114333E+13 | 3.26 | 4.50 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.514339E+11 | 0.00 | 666.33 | 149205.86 | 18-JAN-09:02 | 0.00 | 42.24 | 58.04 | 0.27 | 0.00 | 0.05 | 0.37 | 18-JAN-09:02 |
February | 0.319792E+11 | 0.00 | 509.25 | 128509.30 | 01-FEB-21:50 | 0.00 | 41.47 | 55.23 | 0.18 | 0.00 | 0.03 | 0.32 | 01-FEB-21:50 |
March | 0.239133E+11 | 0.00 | 408.55 | 117320.47 | 26-MAR-03:32 | 0.00 | 39.90 | 50.31 | 0.12 | 0.00 | 0.02 | 0.29 | 26-MAR-03:32 |
April | 0.674448E+10 | 0.00 | 121.43 | 118723.87 | 11-APR-04:55 | 0.00 | 35.85 | 39.61 | 0.03 | 0.00 | 0.01 | 0.29 | 11-APR-04:55 |
May | 0.585764E+09 | 0.00 | 17.18 | 65411.41 | 02-MAY-05:16 | 0.00 | 37.72 | 38.30 | 0.00 | 0.00 | 0.00 | 0.16 | 02-MAY-05:16 |
June | 30260768.65 | 0.00 | 1.25 | 21178.56 | 12-JUN-08:54 | 0.00 | 44.36 | 44.39 | 0.00 | 0.00 | 0.00 | 0.05 | 12-JUN-08:54 |
July | 35291329.12 | 0.00 | 1.68 | 18720.06 | 18-JUL-08:55 | 0.00 | 45.47 | 45.51 | 0.00 | 0.00 | 0.00 | 0.05 | 18-JUL-08:55 |
August | 69664890.33 | 0.00 | 2.39 | 30804.32 | 24-AUG-08:54 | 0.00 | 45.53 | 45.57 | 0.00 | 0.00 | 0.00 | 0.08 | 24-AUG-08:54 |
September | 0.322698E+09 | 0.00 | 16.20 | 50372.18 | 30-SEP-05:50 | 0.00 | 42.82 | 43.23 | 0.00 | 0.00 | 0.00 | 0.12 | 30-SEP-05:50 |
October | 0.381508E+10 | 0.00 | 130.49 | 98177.04 | 11-OCT-06:24 | 0.00 | 36.21 | 40.16 | 0.02 | 0.00 | 0.00 | 0.24 | 11-OCT-06:24 |
November | 0.310860E+11 | 0.00 | 477.59 | 153591.71 | 27-NOV-09:03 | 0.00 | 42.90 | 54.38 | 0.17 | 0.00 | 0.03 | 0.38 | 27-NOV-09:03 |
December | 0.554409E+11 | 0.00 | 679.56 | 144345.48 | 02-DEC-16:02 | 0.00 | 41.78 | 58.21 | 0.29 | 0.00 | 0.05 | 0.36 | 02-DEC-16:02 |
Annual Sum or Average | 0.205457E+12 | 0.00 | 3031.89 | 0.00 | 41.35 | 47.71 | 0.09 | 0.00 | 0.02 | ||||
Minimum of Months | 30260768.65 | 0.00 | 1.25 | 18720.06 | 0.00 | 35.85 | 38.30 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.554409E+11 | 0.00 | 679.56 | 153591.71 | 0.00 | 45.53 | 58.21 | 0.29 | 0.00 | 0.05 | 0.38 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.670646E+10 | 0.00 | 190.79 | 0.670646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89112.50 | 03-JAN-17:00 | 89112.50 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.328647E+11 | 0.00 | 262.24 | 0.328647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124107.99 | 21-FEB-16:14 | 124107.99 | 21-FEB-16:14 | 0.00 | 0.00 | 0.00 |
March | 0.669157E+11 | 0.00 | 356.82 | 0.669157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160199.08 | 14-MAR-18:20 | 160199.08 | 14-MAR-18:20 | 0.00 | 0.00 | 0.00 |
April | 0.210684E+12 | 0.00 | 571.73 | 0.210684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 230788.60 | 19-APR-21:00 | 230788.60 | 19-APR-21:00 | 0.00 | 0.00 | 0.00 |
May | 0.350048E+12 | 0.00 | 716.06 | 0.348354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256095.91 | 19-MAY-20:10 | 256095.91 | 19-MAY-20:10 | 0.00 | 0.00 | 0.00 |
June | 0.455412E+12 | 0.00 | 720.00 | 0.450111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 301404.06 | 19-JUN-18:20 | 285582.75 | 05-JUN-20:10 | 0.00 | 0.00 | 0.00 |
July | 0.608638E+12 | 0.00 | 744.00 | 0.472381E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 462494.73 | 18-JUL-20:45 | 283393.30 | 25-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.494963E+12 | 0.00 | 744.00 | 0.441397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 459333.72 | 01-AUG-20:50 | 291207.79 | 04-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.403396E+12 | 0.00 | 694.74 | 0.346353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 341060.45 | 09-SEP-20:00 | 258198.89 | 19-SEP-18:20 | 0.00 | 0.00 | 0.00 |
October | 0.198517E+12 | 0.00 | 562.28 | 0.189811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 389083.32 | 03-OCT-19:55 | 243424.78 | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.409353E+11 | 0.00 | 306.33 | 0.409353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149023.86 | 03-NOV-15:45 | 149023.86 | 03-NOV-15:45 | 0.00 | 0.00 | 0.00 |
December | 0.410164E+10 | 0.00 | 173.37 | 0.410164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58732.09 | 19-DEC-22:10 | 58732.09 | 19-DEC-22:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287318E+13 | 0.00 | 6042.36 | 0.261061E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.410164E+10 | 0.00 | 173.37 | 0.410164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58732.09 | 58732.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.608638E+12 | 0.00 | 744.00 | 0.472381E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 462494.73 | 291207.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.122869E+10 | 0.00 | 63.67 | 0.122869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18651.05 | 03-JAN-15:00 | 18651.05 | 03-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.619310E+10 | 0.00 | 159.50 | 0.619310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23708.25 | 20-FEB-16:28 | 23708.25 | 20-FEB-16:28 | 0.00 | 0.00 | 0.00 |
March | 0.122686E+11 | 0.00 | 278.17 | 0.122686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24845.34 | 22-MAR-16:30 | 24845.34 | 22-MAR-16:30 | 0.00 | 0.00 | 0.00 |
April | 0.349245E+11 | 0.00 | 548.50 | 0.349245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29749.47 | 21-APR-15:00 | 29749.47 | 21-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.560482E+11 | 0.00 | 713.33 | 0.548594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35949.88 | 27-MAY-21:20 | 31570.77 | 19-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.684145E+11 | 0.00 | 720.00 | 0.659318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41761.79 | 27-JUN-24:00 | 33169.36 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.926654E+11 | 0.00 | 744.00 | 0.690670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57668.34 | 21-JUL-08:00 | 33164.62 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.773791E+11 | 0.00 | 744.00 | 0.651902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52523.34 | 03-AUG-07:00 | 32201.13 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.662244E+11 | 0.00 | 692.83 | 0.524076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50715.99 | 22-SEP-08:65 | 30715.41 | 19-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.334833E+11 | 0.00 | 534.83 | 0.306253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47393.11 | 03-OCT-20:05 | 30322.60 | 03-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.751668E+10 | 0.00 | 211.33 | 0.751668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24834.53 | 03-NOV-16:00 | 24834.53 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.724489E+09 | 0.00 | 54.02 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11238.20 | 10-DEC-15:00 | 11238.20 | 10-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457071E+12 | 0.00 | 5464.18 | 0.400937E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.724489E+09 | 0.00 | 54.02 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11238.20 | 11238.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.926654E+11 | 0.00 | 744.00 | 0.690670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57668.34 | 33169.36 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.560329E+09 | 0.00 | 148.52 | 0.548153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16319.15 | 01-JAN-16:02 | 16319.15 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.749985E+09 | 0.00 | 182.10 | 0.738841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16530.95 | 20-FEB-21:11 | 16530.95 | 20-FEB-21:11 | 0.00 | 0.00 | 0.00 |
March | 0.134487E+10 | 0.00 | 289.41 | 0.132194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16641.21 | 26-MAR-20:11 | 16641.21 | 26-MAR-20:11 | 0.00 | 0.00 | 0.00 |
April | 0.446552E+10 | 0.00 | 492.29 | 0.410249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17826.34 | 06-APR-18:11 | 17826.34 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.763766E+10 | 0.00 | 583.60 | 0.633740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17875.25 | 23-MAY-21:51 | 17484.64 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.101100E+11 | 0.00 | 611.47 | 0.781275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17533.36 | 04-JUN-08:51 | 17354.37 | 14-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.108604E+11 | 0.00 | 628.95 | 0.688900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20437.43 | 21-JUL-08:51 | 15497.20 | 16-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.978554E+10 | 0.00 | 604.06 | 0.635468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19440.00 | 14-AUG-21:51 | 15870.31 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.859540E+10 | 0.00 | 549.44 | 0.558154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19725.56 | 03-SEP-21:51 | 17468.87 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.485031E+10 | 0.00 | 504.69 | 0.307566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18891.84 | 03-OCT-21:51 | 17302.61 | 29-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.165033E+10 | 0.00 | 306.42 | 0.144981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16395.55 | 09-NOV-09:51 | 16395.55 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.310252E+09 | 0.00 | 103.94 | 0.309970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16289.67 | 07-DEC-16:01 | 16289.67 | 07-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609206E+11 | 0.00 | 5004.88 | 0.445222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.310252E+09 | 0.00 | 103.94 | 0.309970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16289.67 | 15497.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108604E+11 | 0.00 | 628.95 | 0.781275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20437.43 | 17826.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 99006641.34 | 0.00 | 30.74 | 98770899.67 | 0.00 | 0.00 | 0.00 | 0.00 | 15854.38 | 12-JAN-16:01 | 15854.38 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.181452E+09 | 0.00 | 63.27 | 0.179582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16185.09 | 18-FEB-16:01 | 16185.09 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.676113E+09 | 0.00 | 175.68 | 0.659645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16188.09 | 12-MAR-15:01 | 16188.09 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.379530E+10 | 0.00 | 451.84 | 0.346584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17517.17 | 06-APR-18:11 | 17517.17 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.743544E+10 | 0.00 | 576.39 | 0.615594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17779.36 | 23-MAY-21:51 | 17397.52 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.101497E+11 | 0.00 | 611.25 | 0.788166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17564.85 | 16-JUN-07:21 | 17564.85 | 16-JUN-07:21 | 0.00 | 0.00 | 0.00 |
July | 0.107885E+11 | 0.00 | 628.30 | 0.687558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20378.74 | 21-JUL-08:51 | 15408.87 | 16-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.921687E+10 | 0.00 | 597.27 | 0.588892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19266.61 | 14-AUG-21:51 | 15725.73 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.721938E+10 | 0.00 | 531.72 | 0.437877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19448.42 | 03-SEP-21:51 | 16970.28 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.320196E+10 | 0.00 | 436.17 | 0.182298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18556.97 | 03-OCT-21:51 | 16470.09 | 29-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.441583E+09 | 0.00 | 143.51 | 0.340254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16212.36 | 09-NOV-16:01 | 16212.36 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 36708287.70 | 0.00 | 13.87 | 36690601.74 | 0.00 | 0.00 | 0.00 | 0.00 | 15582.29 | 16-DEC-16:01 | 15582.29 | 16-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.532420E+11 | 0.00 | 4260.02 | 0.377846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 36708287.70 | 0.00 | 13.87 | 36690601.74 | 0.00 | 0.00 | 0.00 | 0.00 | 15582.29 | 15408.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107885E+11 | 0.00 | 628.30 | 0.788166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20378.74 | 17564.85 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.137093E+11 | 0.00 | 312.42 | 0.137093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34565.92 | 12-JAN-14:30 | 34565.92 | 12-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.128567E+11 | 0.00 | 300.13 | 0.128567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32356.28 | 07-FEB-13:40 | 32356.28 | 07-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.928705E+10 | 0.00 | 293.07 | 0.924436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24145.40 | 16-MAR-12:50 | 24145.40 | 16-MAR-12:50 | 0.00 | 0.00 | 0.00 |
April | 0.158417E+11 | 0.00 | 447.11 | 0.149489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23014.31 | 04-APR-13:30 | 23014.31 | 04-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.213545E+11 | 0.00 | 573.48 | 0.169716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22722.27 | 19-MAY-20:20 | 22506.53 | 19-MAY-20:30 | 0.00 | 0.00 | 0.00 |
June | 0.311081E+11 | 0.00 | 674.28 | 0.210525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26112.38 | 15-JUN-20:20 | 26112.38 | 15-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.360065E+11 | 0.00 | 720.58 | 0.142582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28079.29 | 26-JUL-17:20 | 18630.48 | 02-JUL-20:40 | 0.00 | 0.00 | 0.00 |
August | 0.355999E+11 | 0.00 | 688.83 | 0.167249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28842.60 | 29-AUG-13:10 | 27819.55 | 27-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.403645E+11 | 0.00 | 672.47 | 0.233232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38342.18 | 20-SEP-12:40 | 32418.30 | 30-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.343680E+11 | 0.00 | 575.24 | 0.264270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43907.43 | 18-OCT-13:20 | 40266.75 | 18-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.233955E+11 | 0.00 | 383.55 | 0.227352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38181.46 | 09-NOV-13:50 | 38181.46 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.107504E+11 | 0.00 | 275.40 | 0.107504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29524.91 | 16-DEC-13:40 | 29524.91 | 16-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284642E+12 | 0.00 | 5916.57 | 0.203002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.928705E+10 | 0.00 | 275.40 | 0.924436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22722.27 | 18630.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.403645E+11 | 0.00 | 720.58 | 0.264270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43907.43 | 40266.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.176301E+10 | 0.00 | 136.64 | 0.161315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97437.52 | 01-JAN-09:01 | 97437.52 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.379246E+10 | 0.00 | 197.09 | 0.340924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103920.96 | 22-FEB-22:01 | 103920.96 | 22-FEB-22:01 | 0.00 | 0.00 | 0.00 |
March | 0.858814E+10 | 0.00 | 308.27 | 0.821001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105891.62 | 15-MAR-21:51 | 105891.62 | 15-MAR-21:51 | 0.00 | 0.00 | 0.00 |
April | 0.250270E+11 | 0.00 | 403.58 | 0.230815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108777.94 | 05-APR-21:51 | 108777.94 | 05-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.443263E+11 | 0.00 | 452.82 | 0.367029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113766.52 | 23-MAY-21:51 | 110433.45 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.600724E+11 | 0.00 | 518.95 | 0.465879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110332.81 | 11-JUN-08:31 | 110332.81 | 11-JUN-08:31 | 0.00 | 0.00 | 0.00 |
July | 0.668446E+11 | 0.00 | 524.96 | 0.421883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130230.57 | 20-JUL-21:51 | 100777.78 | 04-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.559279E+11 | 0.00 | 473.72 | 0.351378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125601.48 | 16-AUG-21:51 | 100434.93 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.418242E+11 | 0.00 | 392.92 | 0.257478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126445.89 | 23-SEP-21:51 | 108474.84 | 11-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.238960E+11 | 0.00 | 387.50 | 0.135137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122516.86 | 03-OCT-21:51 | 107785.35 | 19-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.513867E+10 | 0.00 | 240.57 | 0.393546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103458.53 | 08-NOV-22:51 | 103458.53 | 08-NOV-22:51 | 0.00 | 0.00 | 0.00 |
December | 0.116270E+10 | 0.00 | 93.84 | 0.113541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98322.46 | 09-DEC-09:01 | 98322.46 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338363E+12 | 0.00 | 4130.85 | 0.241263E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.116270E+10 | 0.00 | 93.84 | 0.113541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97437.52 | 97437.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.668446E+11 | 0.00 | 524.96 | 0.465879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130230.57 | 110433.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.543289E+09 | 0.00 | 127.95 | 0.508691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14347.72 | 12-JAN-16:01 | 14347.72 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.992924E+09 | 0.00 | 209.56 | 0.962479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14391.67 | 18-FEB-09:01 | 14391.67 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.161407E+10 | 0.00 | 319.07 | 0.159026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14387.41 | 08-MAR-09:01 | 14387.41 | 08-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.473065E+10 | 0.00 | 532.50 | 0.436084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16657.06 | 27-APR-08:51 | 16657.06 | 27-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.758588E+10 | 0.00 | 611.51 | 0.630241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16657.44 | 16-MAY-08:51 | 16657.44 | 16-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.102068E+11 | 0.00 | 628.74 | 0.792088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16657.46 | 02-JUN-08:11 | 16657.46 | 02-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.109934E+11 | 0.00 | 642.39 | 0.701564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19092.19 | 21-JUL-08:51 | 14990.97 | 11-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.985807E+10 | 0.00 | 619.37 | 0.638798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17916.92 | 03-AUG-08:61 | 15178.24 | 28-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.846737E+10 | 0.00 | 563.18 | 0.544440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17690.51 | 14-SEP-08:51 | 15214.93 | 19-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.466477E+10 | 0.00 | 507.88 | 0.303689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16730.51 | 03-OCT-21:51 | 15144.57 | 18-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.160886E+10 | 0.00 | 308.91 | 0.145199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16323.87 | 09-NOV-09:51 | 16323.87 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.405158E+09 | 0.00 | 102.63 | 0.399554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14387.13 | 09-DEC-09:01 | 14387.13 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.616711E+11 | 0.00 | 5173.70 | 0.453820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.405158E+09 | 0.00 | 102.63 | 0.399554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14347.72 | 14347.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109934E+11 | 0.00 | 642.39 | 0.792088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19092.19 | 16657.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 63742529.00 | 0.00 | 30.14 | 55951419.20 | 0.00 | 0.00 | 0.00 | 0.00 | 10500.17 | 04-JAN-09:02 | 10500.17 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.349602E+09 | 0.00 | 86.39 | 0.326560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14280.75 | 19-FEB-09:01 | 14280.75 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.904411E+09 | 0.00 | 193.22 | 0.888315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14278.64 | 05-MAR-09:01 | 14278.64 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.400027E+10 | 0.00 | 488.53 | 0.366370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16532.76 | 27-APR-08:51 | 16532.76 | 27-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.736627E+10 | 0.00 | 610.54 | 0.609428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16533.81 | 16-MAY-08:51 | 16533.81 | 16-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.102431E+11 | 0.00 | 629.25 | 0.797042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16533.69 | 02-JUN-08:11 | 16533.69 | 02-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.109169E+11 | 0.00 | 642.27 | 0.696915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19008.17 | 21-JUL-08:51 | 14911.89 | 11-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.928072E+10 | 0.00 | 617.14 | 0.587987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17784.78 | 03-AUG-08:61 | 15089.99 | 28-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.707926E+10 | 0.00 | 557.44 | 0.428536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17590.93 | 09-SEP-08:51 | 14983.24 | 19-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.298246E+10 | 0.00 | 415.61 | 0.178810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16386.23 | 03-OCT-21:51 | 14690.72 | 03-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.509762E+09 | 0.00 | 124.59 | 0.430665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15037.26 | 09-NOV-09:51 | 15037.26 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 42924760.51 | 0.00 | 19.41 | 40951691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13554.34 | 09-DEC-09:01 | 13554.34 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.537395E+11 | 0.00 | 4414.52 | 0.383933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 42924760.51 | 0.00 | 19.41 | 40951691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 10500.17 | 10500.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109169E+11 | 0.00 | 642.27 | 0.797042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19008.17 | 16533.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.113910E+09 | 0.00 | 94.31 | 0.112436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4329.98 | 01-JAN-16:02 | 4329.98 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.155849E+09 | 0.00 | 125.63 | 0.154289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4390.82 | 20-FEB-21:11 | 4390.82 | 20-FEB-21:11 | 0.00 | 0.00 | 0.00 |
March | 0.284037E+09 | 0.00 | 216.25 | 0.280903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4509.97 | 13-MAR-19:41 | 4509.97 | 13-MAR-19:41 | 0.00 | 0.00 | 0.00 |
April | 0.109916E+10 | 0.00 | 463.45 | 0.101154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4775.56 | 06-APR-18:11 | 4775.56 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.192744E+10 | 0.00 | 583.72 | 0.158766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4768.76 | 23-MAY-21:51 | 4634.53 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.264037E+10 | 0.00 | 614.19 | 0.203742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4771.58 | 04-JUN-08:51 | 4580.37 | 14-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.283697E+10 | 0.00 | 630.15 | 0.180242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5581.40 | 21-JUL-08:51 | 4069.26 | 16-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.252336E+10 | 0.00 | 604.41 | 0.163191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5253.82 | 14-AUG-21:51 | 4133.08 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.215422E+10 | 0.00 | 548.91 | 0.139456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5303.50 | 03-SEP-21:51 | 4603.91 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.110938E+10 | 0.00 | 460.56 | 0.709532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.77 | 03-OCT-21:51 | 4590.75 | 29-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.321484E+09 | 0.00 | 238.96 | 0.283777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4330.11 | 09-NOV-16:01 | 4330.11 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 63719756.54 | 0.00 | 63.74 | 63639779.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4327.75 | 04-DEC-16:01 | 4327.75 | 04-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152299E+11 | 0.00 | 4644.28 | 0.110701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 63719756.54 | 0.00 | 63.74 | 63639779.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4327.75 | 4069.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.283697E+10 | 0.00 | 630.15 | 0.203742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5581.40 | 4775.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 16874195.62 | 0.00 | 20.54 | 16809232.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4206.35 | 12-JAN-16:01 | 4206.35 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 29872416.16 | 0.00 | 36.77 | 29709805.07 | 0.00 | 0.00 | 0.00 | 0.00 | 4290.24 | 18-FEB-16:01 | 4290.24 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.128684E+09 | 0.00 | 118.57 | 0.126876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4291.01 | 04-MAR-16:01 | 4291.01 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.924381E+09 | 0.00 | 424.55 | 0.846182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.15 | 06-APR-18:11 | 4670.15 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.187422E+10 | 0.00 | 576.88 | 0.153954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4740.69 | 23-MAY-21:51 | 4608.99 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.265217E+10 | 0.00 | 613.90 | 0.205469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4742.59 | 04-JUN-08:51 | 4594.02 | 14-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.281880E+10 | 0.00 | 630.08 | 0.179400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5555.95 | 21-JUL-08:51 | 4043.27 | 16-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.237432E+10 | 0.00 | 599.62 | 0.150449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5202.05 | 14-AUG-21:51 | 4079.70 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.178937E+10 | 0.00 | 530.17 | 0.107613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5230.80 | 03-SEP-21:51 | 4460.32 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.679076E+09 | 0.00 | 366.39 | 0.393533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4988.48 | 03-OCT-21:51 | 4325.47 | 29-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 65753005.21 | 0.00 | 71.45 | 49565470.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4297.48 | 09-NOV-16:01 | 4297.48 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 5888024.03 | 0.00 | 8.50 | 5888024.03 | 0.00 | 0.00 | 0.00 | 0.00 | 4082.15 | 16-DEC-16:01 | 4082.15 | 16-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133594E+11 | 0.00 | 3997.42 | 0.943741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5888024.03 | 0.00 | 8.50 | 5888024.03 | 0.00 | 0.00 | 0.00 | 0.00 | 4082.15 | 4043.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.281880E+10 | 0.00 | 630.08 | 0.205469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5555.95 | 4670.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.387039E+10 | 0.00 | 357.84 | 0.372700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20510.67 | 12-JAN-19:41 | 20510.67 | 12-JAN-19:41 | 0.00 | 0.00 | 0.00 |
February | 0.359774E+10 | 0.00 | 350.92 | 0.352918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20820.91 | 20-FEB-21:11 | 20820.91 | 20-FEB-21:11 | 0.00 | 0.00 | 0.00 |
March | 0.315157E+10 | 0.00 | 385.30 | 0.309770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20590.05 | 14-MAR-21:01 | 20590.05 | 14-MAR-21:01 | 0.00 | 0.00 | 0.00 |
April | 0.571051E+10 | 0.00 | 491.11 | 0.517675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20216.32 | 02-APR-21:51 | 20216.32 | 02-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.814451E+10 | 0.00 | 575.50 | 0.639706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20952.47 | 23-MAY-21:51 | 20658.16 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.112095E+11 | 0.00 | 603.72 | 0.819275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21021.27 | 19-JUN-18:51 | 20187.13 | 14-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.128209E+11 | 0.00 | 620.56 | 0.764077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24502.32 | 20-JUL-21:51 | 18169.45 | 16-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.122860E+11 | 0.00 | 600.69 | 0.769340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23351.30 | 14-AUG-21:51 | 18686.70 | 28-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.121552E+11 | 0.00 | 552.74 | 0.811722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23901.85 | 03-SEP-21:51 | 20972.46 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.920019E+10 | 0.00 | 517.71 | 0.661310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23436.62 | 03-OCT-21:51 | 21816.86 | 26-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.571492E+10 | 0.00 | 415.73 | 0.536394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21974.04 | 09-NOV-09:51 | 21974.04 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.350382E+10 | 0.00 | 336.11 | 0.347401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20396.66 | 07-DEC-17:01 | 20396.66 | 07-DEC-17:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.913653E+11 | 0.00 | 5807.94 | 0.690229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.315157E+10 | 0.00 | 336.11 | 0.309770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20216.32 | 18169.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128209E+11 | 0.00 | 620.56 | 0.819275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24502.32 | 21974.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.15 | 535.07 | 171.08 | 934.24 | 537.22 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 471.17 | 193.21 | 898.89 | 475.60 | 0.00 | 0.00 | 0.00 |
March | 519.74 | 294.46 | 225.28 | 726.40 | 414.47 | 0.00 | 0.00 | 0.00 |
April | 362.15 | 135.95 | 226.20 | 580.37 | 247.13 | 0.00 | 0.00 | 0.00 |
May | 257.00 | 37.69 | 219.31 | 466.52 | 140.77 | 0.00 | 0.00 | 0.00 |
June | 219.82 | 13.83 | 205.99 | 495.64 | 66.98 | 0.00 | 0.00 | 0.00 |
July | 223.23 | 19.79 | 203.44 | 503.21 | 50.45 | 0.00 | 0.00 | 0.00 |
August | 281.79 | 71.59 | 210.20 | 588.84 | 76.59 | 0.00 | 0.00 | 0.00 |
September | 446.25 | 231.85 | 214.40 | 834.84 | 165.71 | 0.00 | 0.00 | 0.00 |
October | 612.55 | 416.17 | 196.38 | 970.71 | 270.63 | 0.00 | 0.00 | 0.00 |
November | 737.24 | 563.91 | 173.33 | 1025.23 | 454.38 | 0.00 | 0.00 | 0.00 |
December | 724.95 | 544.65 | 180.31 | 938.89 | 577.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 478.50 | 276.88 | 201.63 | 745.87 | 288.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.82 | 13.83 | 171.08 | 466.52 | 50.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.24 | 563.91 | 226.20 | 1025.23 | 577.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1988.48 | 1506.73 | 481.75 | 2581.00 | 1652.99 | 0.00 | 0.00 | 0.00 |
February | 1870.85 | 1326.79 | 544.06 | 2477.60 | 1472.69 | 0.00 | 0.00 | 0.00 |
March | 1463.55 | 829.18 | 634.37 | 1990.80 | 1288.97 | 0.00 | 0.00 | 0.00 |
April | 1019.80 | 382.82 | 636.98 | 1594.44 | 769.17 | 0.00 | 0.00 | 0.00 |
May | 723.68 | 106.13 | 617.55 | 1288.36 | 430.74 | 0.00 | 0.00 | 0.00 |
June | 618.99 | 38.95 | 580.04 | 1385.26 | 198.08 | 0.00 | 0.00 | 0.00 |
July | 628.60 | 55.73 | 572.87 | 1405.53 | 150.46 | 0.00 | 0.00 | 0.00 |
August | 793.51 | 201.60 | 591.90 | 1643.12 | 230.89 | 0.00 | 0.00 | 0.00 |
September | 1256.61 | 652.87 | 603.74 | 2329.81 | 487.32 | 0.00 | 0.00 | 0.00 |
October | 1724.89 | 1171.91 | 552.99 | 2699.71 | 822.57 | 0.00 | 0.00 | 0.00 |
November | 2076.02 | 1587.93 | 488.09 | 2840.05 | 1388.32 | 0.00 | 0.00 | 0.00 |
December | 2041.42 | 1533.69 | 507.73 | 2588.75 | 1762.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 779.68 | 567.76 | 2065.69 | 885.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 618.99 | 38.95 | 481.75 | 1288.36 | 150.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.02 | 1587.93 | 636.98 | 2840.05 | 1762.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2583.15 | 1957.32 | 625.82 | 3428.74 | 2209.91 | 0.00 | 0.00 | 0.00 |
February | 2430.34 | 1723.58 | 706.76 | 3296.17 | 1960.20 | 0.00 | 0.00 | 0.00 |
March | 1901.24 | 1077.15 | 824.09 | 2654.51 | 1717.49 | 0.00 | 0.00 | 0.00 |
April | 1324.78 | 497.31 | 827.47 | 2136.44 | 1017.02 | 0.00 | 0.00 | 0.00 |
May | 940.11 | 137.87 | 802.24 | 1731.90 | 565.06 | 0.00 | 0.00 | 0.00 |
June | 804.10 | 50.59 | 753.51 | 1869.43 | 255.65 | 0.00 | 0.00 | 0.00 |
July | 816.59 | 72.40 | 744.19 | 1894.88 | 192.23 | 0.00 | 0.00 | 0.00 |
August | 1030.81 | 261.90 | 768.91 | 2206.16 | 296.54 | 0.00 | 0.00 | 0.00 |
September | 1632.41 | 848.12 | 784.29 | 3108.95 | 629.07 | 0.00 | 0.00 | 0.00 |
October | 2240.73 | 1522.37 | 718.36 | 3586.12 | 1077.69 | 0.00 | 0.00 | 0.00 |
November | 2696.87 | 2062.81 | 634.06 | 3765.34 | 1848.21 | 0.00 | 0.00 | 0.00 |
December | 2651.92 | 1992.35 | 659.58 | 3436.70 | 2362.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1750.40 | 1012.84 | 737.56 | 2755.64 | 1173.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 804.10 | 50.59 | 625.82 | 1731.90 | 192.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2696.87 | 2062.81 | 827.47 | 3765.34 | 2362.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 188.29 | 103.90 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 180.77 | 92.17 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 144.24 | 81.29 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.71 | 44.55 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.41 | 21.10 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.87 | 7.32 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 112.82 | 4.32 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.66 | 8.70 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 171.92 | 25.15 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 196.15 | 48.90 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 206.71 | 86.49 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 190.36 | 112.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.79 | 52.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.41 | 4.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 206.71 | 112.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 113.05 | 215.30 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 137.44 | 190.39 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 209.26 | 157.35 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 291.92 | 81.82 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 360.73 | 38.99 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 409.50 | 13.61 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 368.95 | 7.84 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 339.11 | 16.13 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 317.52 | 47.65 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 230.81 | 95.67 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 152.09 | 179.35 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 101.13 | 236.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 253.13 | 106.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 101.13 | 7.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 409.50 | 236.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.16 | 116.12 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.56 | 102.01 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.25 | 85.02 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 48.54 | 42.94 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 82.92 | 19.40 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 118.13 | 6.96 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 110.14 | 4.07 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 86.42 | 8.22 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.79 | 24.77 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 32.02 | 50.34 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.27 | 96.37 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.95 | 128.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 49.38 | 56.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.95 | 4.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 118.13 | 128.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 119.83 | 208.55 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 144.29 | 184.44 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 215.10 | 153.84 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 294.75 | 80.63 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 361.28 | 38.82 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 409.18 | 13.62 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 368.94 | 7.82 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 340.35 | 15.87 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 320.65 | 46.25 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 236.12 | 92.02 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 158.83 | 173.28 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 107.72 | 229.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 256.91 | 103.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 107.72 | 7.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 409.18 | 229.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.67 | 84.62 | 27.06 | 145.35 | 93.88 | 0.00 | 0.00 | 0.00 |
February | 105.07 | 74.51 | 30.55 | 139.75 | 83.56 | 0.00 | 0.00 | 0.00 |
March | 82.19 | 46.57 | 35.63 | 112.04 | 71.92 | 0.00 | 0.00 | 0.00 |
April | 57.27 | 21.50 | 35.77 | 92.21 | 40.70 | 0.00 | 0.00 | 0.00 |
May | 40.64 | 5.96 | 34.68 | 77.97 | 20.92 | 0.00 | 0.00 | 0.00 |
June | 34.76 | 2.19 | 32.58 | 87.32 | 8.46 | 0.00 | 0.00 | 0.00 |
July | 35.30 | 3.13 | 32.17 | 87.66 | 5.88 | 0.00 | 0.00 | 0.00 |
August | 44.56 | 11.32 | 33.24 | 99.76 | 10.05 | 0.00 | 0.00 | 0.00 |
September | 70.57 | 36.67 | 33.91 | 136.31 | 24.24 | 0.00 | 0.00 | 0.00 |
October | 96.87 | 65.81 | 31.06 | 154.56 | 44.30 | 0.00 | 0.00 | 0.00 |
November | 116.59 | 89.18 | 27.41 | 161.39 | 77.87 | 0.00 | 0.00 | 0.00 |
December | 114.65 | 86.13 | 28.51 | 146.52 | 100.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 43.79 | 31.89 | 119.92 | 48.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.76 | 2.19 | 27.06 | 77.97 | 5.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.59 | 89.18 | 35.77 | 161.39 | 100.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.32 | 0.00 | 16.32 | 3.17 | 95.28 | 0.00 | 0.00 | 0.00 |
February | 19.93 | 0.00 | 19.93 | 9.82 | 82.51 | 0.00 | 0.00 | 0.00 |
March | 26.09 | 0.00 | 26.09 | 20.50 | 66.99 | 0.00 | 0.00 | 0.00 |
April | 30.29 | 0.39 | 29.91 | 43.11 | 32.20 | 0.00 | 0.00 | 0.00 |
May | 35.78 | 2.64 | 33.15 | 72.06 | 13.90 | 0.00 | 0.00 | 0.00 |
June | 38.05 | 4.74 | 33.31 | 101.28 | 4.54 | 0.00 | 0.00 | 0.00 |
July | 35.16 | 3.45 | 31.71 | 94.65 | 2.39 | 0.00 | 0.00 | 0.00 |
August | 29.73 | 0.71 | 29.03 | 75.29 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 25.87 | 0.03 | 25.84 | 54.55 | 17.45 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 28.96 | 37.38 | 0.00 | 0.00 | 0.00 |
November | 17.31 | 0.00 | 17.31 | 7.55 | 76.46 | 0.00 | 0.00 | 0.00 |
December | 16.19 | 0.00 | 16.19 | 2.15 | 105.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.04 | 1.00 | 25.04 | 42.93 | 44.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.19 | 0.00 | 16.19 | 2.15 | 2.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.05 | 4.74 | 33.31 | 101.28 | 105.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 93.65 | 203.75 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 150.92 | 176.58 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 205.83 | 144.20 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 307.23 | 73.68 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 364.12 | 35.33 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 424.45 | 12.57 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 385.96 | 7.49 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 350.73 | 14.94 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 313.41 | 43.25 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 198.75 | 88.80 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 131.67 | 166.55 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 89.40 | 223.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 251.70 | 98.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 89.40 | 7.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 424.45 | 223.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 187.74 | 103.21 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 179.28 | 91.67 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 142.86 | 80.21 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 115.80 | 44.07 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 97.20 | 20.95 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 110.00 | 7.18 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 111.27 | 4.20 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 126.22 | 8.60 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 170.26 | 24.91 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 195.89 | 47.37 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 205.91 | 85.51 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 189.75 | 111.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 152.49 | 52.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 97.20 | 4.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 205.91 | 111.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 3.89 | 115.65 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 10.87 | 102.14 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 22.31 | 84.48 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 46.52 | 42.66 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 80.50 | 19.12 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 116.29 | 6.81 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 108.61 | 3.95 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 84.88 | 8.08 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 60.16 | 24.70 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 31.40 | 48.80 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 7.86 | 95.19 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.66 | 128.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 48.19 | 56.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.66 | 3.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 116.29 | 128.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 98.73 | 195.06 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 156.93 | 169.62 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 210.98 | 140.31 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 309.52 | 72.56 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 364.57 | 35.17 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 424.20 | 12.59 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 386.00 | 7.48 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 351.93 | 14.71 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 316.44 | 42.00 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 203.41 | 85.01 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 138.03 | 158.99 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 93.56 | 214.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 254.86 | 95.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 93.56 | 7.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 424.20 | 214.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 3.67 | 159.13 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 13.19 | 139.47 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 29.18 | 114.54 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 61.80 | 60.73 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 102.84 | 31.17 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 143.74 | 14.06 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 133.17 | 9.94 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 103.88 | 16.39 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 75.37 | 40.10 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 38.23 | 72.27 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 8.44 | 135.09 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 2.58 | 175.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 59.92 | 80.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 2.58 | 9.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 143.74 | 175.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 1.35 | 58.66 | 0.00 | 0.00 | 0.00 |
February | 11.63 | 0.00 | 11.63 | 4.86 | 51.41 | 0.00 | 0.00 | 0.00 |
March | 15.22 | 0.00 | 15.22 | 10.76 | 42.22 | 0.00 | 0.00 | 0.00 |
April | 17.68 | 0.23 | 17.45 | 22.78 | 22.39 | 0.00 | 0.00 | 0.00 |
May | 20.88 | 1.54 | 19.34 | 37.91 | 11.49 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 2.77 | 19.44 | 52.99 | 5.18 | 0.00 | 0.00 | 0.00 |
July | 20.51 | 2.01 | 18.50 | 49.09 | 3.67 | 0.00 | 0.00 | 0.00 |
August | 17.35 | 0.41 | 16.94 | 38.29 | 6.04 | 0.00 | 0.00 | 0.00 |
September | 15.09 | 0.02 | 15.07 | 27.79 | 14.78 | 0.00 | 0.00 | 0.00 |
October | 12.51 | 0.00 | 12.51 | 14.09 | 26.64 | 0.00 | 0.00 | 0.00 |
November | 10.10 | 0.00 | 10.10 | 3.11 | 49.80 | 0.00 | 0.00 | 0.00 |
December | 9.45 | 0.00 | 9.45 | 0.95 | 64.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.20 | 0.58 | 14.61 | 22.09 | 29.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.45 | 0.00 | 9.45 | 0.95 | 3.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 2.77 | 19.44 | 52.99 | 64.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.15 | 49.36 | 15.78 | 88.43 | 50.51 | 0.00 | 0.00 | 0.00 |
February | 61.29 | 43.47 | 17.82 | 85.07 | 44.84 | 0.00 | 0.00 | 0.00 |
March | 47.95 | 27.17 | 20.78 | 68.35 | 39.40 | 0.00 | 0.00 | 0.00 |
April | 33.41 | 12.54 | 20.87 | 55.59 | 22.78 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 3.48 | 20.23 | 45.80 | 12.39 | 0.00 | 0.00 | 0.00 |
June | 20.28 | 1.28 | 19.00 | 49.99 | 5.44 | 0.00 | 0.00 | 0.00 |
July | 20.59 | 1.83 | 18.77 | 50.34 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 26.00 | 6.60 | 19.39 | 57.82 | 6.29 | 0.00 | 0.00 | 0.00 |
September | 41.17 | 21.39 | 19.78 | 79.71 | 14.58 | 0.00 | 0.00 | 0.00 |
October | 56.51 | 38.39 | 18.12 | 91.75 | 24.94 | 0.00 | 0.00 | 0.00 |
November | 68.01 | 52.02 | 15.99 | 96.84 | 42.96 | 0.00 | 0.00 | 0.00 |
December | 66.88 | 50.25 | 16.63 | 89.24 | 54.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.14 | 25.54 | 18.60 | 71.48 | 26.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.28 | 1.28 | 15.78 | 45.80 | 3.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.01 | 52.02 | 20.87 | 96.84 | 54.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.82 | 133.98 | 42.84 | 240.01 | 137.11 | 0.00 | 0.00 | 0.00 |
February | 166.36 | 117.98 | 48.38 | 230.90 | 121.69 | 0.00 | 0.00 | 0.00 |
March | 130.14 | 73.73 | 56.41 | 185.51 | 106.95 | 0.00 | 0.00 | 0.00 |
April | 90.68 | 34.04 | 56.64 | 150.88 | 61.83 | 0.00 | 0.00 | 0.00 |
May | 64.35 | 9.44 | 54.91 | 124.31 | 33.62 | 0.00 | 0.00 | 0.00 |
June | 55.04 | 3.46 | 51.58 | 135.68 | 14.78 | 0.00 | 0.00 | 0.00 |
July | 55.90 | 4.96 | 50.94 | 136.64 | 10.51 | 0.00 | 0.00 | 0.00 |
August | 70.56 | 17.93 | 52.63 | 156.93 | 17.07 | 0.00 | 0.00 | 0.00 |
September | 111.74 | 58.05 | 53.69 | 216.35 | 39.57 | 0.00 | 0.00 | 0.00 |
October | 153.38 | 104.21 | 49.17 | 249.04 | 67.69 | 0.00 | 0.00 | 0.00 |
November | 184.60 | 141.20 | 43.40 | 262.84 | 116.60 | 0.00 | 0.00 | 0.00 |
December | 181.53 | 136.38 | 45.15 | 242.22 | 147.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.82 | 69.33 | 50.49 | 194.01 | 72.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.04 | 3.46 | 42.84 | 124.31 | 10.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.60 | 141.20 | 56.64 | 262.84 | 147.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 187.14 | 102.88 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 179.52 | 91.27 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 142.78 | 80.70 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 116.54 | 43.81 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.15 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 112.07 | 6.80 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 112.63 | 3.97 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.21 | 8.16 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 170.79 | 24.27 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 194.69 | 48.39 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 205.61 | 85.41 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 189.66 | 111.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 152.95 | 52.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.15 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 205.61 | 111.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 112.03 | 212.84 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 136.01 | 188.12 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 206.72 | 155.70 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 289.24 | 80.26 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 358.45 | 37.35 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 407.96 | 12.69 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 367.27 | 7.19 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 337.50 | 15.13 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 315.54 | 45.92 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 228.99 | 94.31 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 150.90 | 176.60 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 100.63 | 233.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 251.44 | 104.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 100.63 | 7.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 407.96 | 233.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.44 | 114.57 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.83 | 100.48 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.39 | 83.96 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 48.30 | 42.13 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 82.89 | 18.62 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 118.11 | 6.52 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 109.91 | 3.75 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 86.43 | 7.73 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.62 | 23.82 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 32.10 | 49.34 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.69 | 94.48 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.20 | 126.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 49.44 | 55.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.20 | 3.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 118.11 | 126.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 119.63 | 205.80 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 143.69 | 181.64 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 213.31 | 151.69 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 292.25 | 78.97 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 359.04 | 37.15 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 407.62 | 12.71 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 367.25 | 7.17 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 338.79 | 14.87 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 318.86 | 44.43 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 234.89 | 90.00 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 158.71 | 169.62 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 107.98 | 226.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 255.65 | 101.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 107.98 | 7.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 407.62 | 226.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.76 | 155.16 | 49.61 | 266.36 | 158.34 | 0.00 | 0.00 | 0.00 |
February | 192.65 | 136.63 | 56.02 | 256.49 | 140.07 | 0.00 | 0.00 | 0.00 |
March | 150.71 | 85.38 | 65.33 | 205.92 | 120.12 | 0.00 | 0.00 | 0.00 |
April | 105.01 | 39.42 | 65.59 | 172.39 | 62.46 | 0.00 | 0.00 | 0.00 |
May | 74.52 | 10.93 | 63.59 | 150.57 | 27.96 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 4.01 | 59.73 | 171.46 | 8.93 | 0.00 | 0.00 | 0.00 |
July | 64.73 | 5.74 | 58.99 | 171.45 | 5.00 | 0.00 | 0.00 | 0.00 |
August | 81.71 | 20.76 | 60.95 | 191.18 | 11.15 | 0.00 | 0.00 | 0.00 |
September | 129.40 | 67.23 | 62.17 | 252.01 | 34.69 | 0.00 | 0.00 | 0.00 |
October | 177.62 | 120.68 | 56.94 | 283.85 | 72.32 | 0.00 | 0.00 | 0.00 |
November | 213.78 | 163.52 | 50.26 | 295.75 | 130.63 | 0.00 | 0.00 | 0.00 |
December | 210.22 | 157.93 | 52.28 | 269.03 | 170.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.75 | 80.29 | 58.47 | 223.61 | 78.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.74 | 4.01 | 49.61 | 150.57 | 5.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.78 | 163.52 | 65.59 | 295.75 | 170.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 7.02 | 1044.19 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 45.18 | 907.09 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 115.16 | 740.85 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 288.29 | 392.32 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 520.15 | 199.54 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 757.96 | 91.54 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 697.91 | 69.70 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 539.05 | 108.52 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 390.82 | 240.39 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 180.05 | 448.75 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 27.61 | 853.77 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 5.16 | 1134.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 299.19 | 517.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 5.16 | 69.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 757.96 | 1134.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 4.94 | 1077.40 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 39.57 | 933.76 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 105.45 | 761.31 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 278.69 | 403.81 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 510.44 | 206.31 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 747.89 | 95.50 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 687.96 | 73.67 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 529.70 | 113.55 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 383.64 | 248.05 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 172.50 | 461.34 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 22.90 | 878.63 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 3.63 | 1169.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 291.93 | 533.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 3.63 | 73.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 747.89 | 1169.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 1.56 | 145.21 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 8.83 | 126.60 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 20.12 | 104.99 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 50.39 | 57.51 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 86.76 | 31.88 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 123.38 | 16.31 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 115.67 | 13.21 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 92.24 | 18.50 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 69.83 | 35.00 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 34.06 | 63.23 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 6.39 | 118.08 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 1.29 | 156.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 51.09 | 73.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 1.29 | 13.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 123.38 | 156.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.40 | 110.21 | 93.19 | 179.87 | 489.90 | 0.00 | 0.00 | 0.00 |
February | 272.98 | 155.65 | 117.32 | 301.09 | 423.75 | 0.00 | 0.00 | 0.00 |
March | 336.47 | 185.26 | 151.21 | 411.99 | 350.49 | 0.00 | 0.00 | 0.00 |
April | 405.62 | 224.97 | 180.65 | 632.35 | 198.30 | 0.00 | 0.00 | 0.00 |
May | 418.14 | 227.15 | 190.99 | 752.34 | 117.48 | 0.00 | 0.00 | 0.00 |
June | 418.31 | 232.60 | 185.71 | 873.30 | 60.97 | 0.00 | 0.00 | 0.00 |
July | 375.38 | 196.25 | 179.13 | 796.14 | 50.03 | 0.00 | 0.00 | 0.00 |
August | 357.58 | 183.11 | 174.47 | 730.57 | 68.91 | 0.00 | 0.00 | 0.00 |
September | 354.77 | 202.59 | 152.18 | 670.69 | 124.34 | 0.00 | 0.00 | 0.00 |
October | 271.54 | 146.27 | 125.28 | 415.85 | 222.80 | 0.00 | 0.00 | 0.00 |
November | 243.14 | 141.22 | 101.92 | 264.95 | 395.78 | 0.00 | 0.00 | 0.00 |
December | 203.55 | 107.86 | 95.69 | 173.31 | 525.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.77 | 176.00 | 145.77 | 517.62 | 251.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.40 | 107.86 | 93.19 | 173.31 | 50.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.31 | 232.60 | 190.99 | 873.30 | 525.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 186.19 | 124.04 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 179.64 | 110.36 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 143.50 | 97.07 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 120.11 | 58.10 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 102.57 | 33.66 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 116.32 | 16.69 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 117.91 | 13.57 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 134.02 | 18.92 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 181.46 | 34.74 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 201.77 | 59.62 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 208.12 | 101.90 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 188.40 | 130.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 156.48 | 66.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 102.57 | 13.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 208.12 | 130.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 2.68 | 162.64 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 11.39 | 141.40 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 26.85 | 115.11 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 57.86 | 61.91 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 98.03 | 32.52 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 138.71 | 15.16 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 127.66 | 11.27 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 99.00 | 17.78 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 71.85 | 41.11 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 35.48 | 72.55 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 7.22 | 134.59 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 2.00 | 178.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 56.80 | 81.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 2.00 | 11.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 138.71 | 178.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 2.40 | 145.52 | 0.00 | 0.00 | 0.00 |
February | 28.22 | 0.00 | 28.22 | 10.19 | 126.51 | 0.00 | 0.00 | 0.00 |
March | 36.94 | 0.00 | 36.94 | 24.03 | 102.99 | 0.00 | 0.00 | 0.00 |
April | 42.90 | 0.55 | 42.35 | 51.77 | 55.39 | 0.00 | 0.00 | 0.00 |
May | 50.68 | 3.73 | 46.94 | 87.71 | 29.10 | 0.00 | 0.00 | 0.00 |
June | 53.89 | 6.72 | 47.17 | 124.11 | 13.56 | 0.00 | 0.00 | 0.00 |
July | 49.79 | 4.88 | 44.90 | 114.22 | 10.08 | 0.00 | 0.00 | 0.00 |
August | 42.11 | 1.00 | 41.11 | 88.57 | 15.91 | 0.00 | 0.00 | 0.00 |
September | 36.63 | 0.05 | 36.59 | 64.29 | 36.79 | 0.00 | 0.00 | 0.00 |
October | 30.37 | 0.00 | 30.37 | 31.75 | 64.91 | 0.00 | 0.00 | 0.00 |
November | 24.51 | 0.00 | 24.51 | 6.46 | 120.42 | 0.00 | 0.00 | 0.00 |
December | 22.93 | 0.00 | 22.93 | 1.79 | 159.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.88 | 1.42 | 35.46 | 50.82 | 73.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.93 | 0.00 | 22.93 | 1.79 | 10.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.89 | 6.72 | 47.17 | 124.11 | 159.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.24 | 394.96 | 126.28 | 693.80 | 409.76 | 0.00 | 0.00 | 0.00 |
February | 490.41 | 347.79 | 142.61 | 667.09 | 362.49 | 0.00 | 0.00 | 0.00 |
March | 383.64 | 217.35 | 166.29 | 533.58 | 316.56 | 0.00 | 0.00 | 0.00 |
April | 267.32 | 100.35 | 166.97 | 429.64 | 186.10 | 0.00 | 0.00 | 0.00 |
May | 189.70 | 27.82 | 161.88 | 351.51 | 103.47 | 0.00 | 0.00 | 0.00 |
June | 162.26 | 10.21 | 152.05 | 385.76 | 46.90 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 14.61 | 150.17 | 386.64 | 35.20 | 0.00 | 0.00 | 0.00 |
August | 208.00 | 52.85 | 155.16 | 446.81 | 54.74 | 0.00 | 0.00 | 0.00 |
September | 329.40 | 171.14 | 158.26 | 624.19 | 119.90 | 0.00 | 0.00 | 0.00 |
October | 452.15 | 307.19 | 144.96 | 721.01 | 200.54 | 0.00 | 0.00 | 0.00 |
November | 544.19 | 416.24 | 127.94 | 764.90 | 341.26 | 0.00 | 0.00 | 0.00 |
December | 535.12 | 402.02 | 133.09 | 701.37 | 439.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.20 | 204.38 | 148.83 | 558.05 | 217.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.26 | 10.21 | 126.28 | 351.51 | 35.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 544.19 | 416.24 | 166.97 | 764.90 | 439.55 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.250226E+10 | 0.143890E+10 |
February | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.217459E+10 | 0.115058E+10 |
March | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.194558E+10 | 0.111012E+10 |
April | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.150431E+10 | 0.640562E+09 |
May | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.124952E+10 | 0.377038E+09 |
June | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.128469E+10 | 0.173619E+09 |
July | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.134781E+10 | 0.135115E+09 |
August | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.157716E+10 | 0.205134E+09 |
September | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.216390E+10 | 0.429517E+09 |
October | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.259995E+10 | 0.724862E+09 |
November | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.265738E+10 | 0.117776E+10 |
December | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.251471E+10 | 0.154650E+10 |
Annual Sum or Average | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.235219E+11 | 0.910970E+10 |
Minimum of Months | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.124952E+10 | 0.135115E+09 |
Maximum of Months | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.265738E+10 | 0.154650E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.691295E+10 | 0.442736E+10 |
February | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.599381E+10 | 0.356273E+10 |
March | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.533215E+10 | 0.345238E+10 |
April | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.413279E+10 | 0.199369E+10 |
May | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.345076E+10 | 0.115370E+10 |
June | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.359060E+10 | 0.513422E+09 |
July | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.376458E+10 | 0.402994E+09 |
August | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.440093E+10 | 0.618411E+09 |
September | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.603886E+10 | 0.126313E+10 |
October | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.723091E+10 | 0.220318E+10 |
November | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.736142E+10 | 0.359852E+10 |
December | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.693370E+10 | 0.472162E+10 |
Annual Sum or Average | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.651435E+11 | 0.279111E+11 |
Minimum of Months | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.345076E+10 | 0.402994E+09 |
Maximum of Months | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.736142E+10 | 0.472162E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.918355E+10 | 0.591902E+10 |
February | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.797410E+10 | 0.474212E+10 |
March | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.710985E+10 | 0.460012E+10 |
April | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.553766E+10 | 0.263612E+10 |
May | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.463871E+10 | 0.151344E+10 |
June | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.484556E+10 | 0.662634E+09 |
July | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.507526E+10 | 0.514870E+09 |
August | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.590897E+10 | 0.794253E+09 |
September | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.805840E+10 | 0.163055E+10 |
October | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.960505E+10 | 0.288647E+10 |
November | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.975976E+10 | 0.479057E+10 |
December | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.920486E+10 | 0.632744E+10 |
Annual Sum or Average | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.869017E+11 | 0.370176E+11 |
Minimum of Months | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.463871E+10 | 0.514870E+09 |
Maximum of Months | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.975976E+10 | 0.632744E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.504324E+09 | 0.278277E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.437330E+09 | 0.222969E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.386328E+09 | 0.217737E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.305093E+09 | 0.115475E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.266256E+09 | 56510671.02 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.289966E+09 | 18970209.05 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.302173E+09 | 11578478.47 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.341930E+09 | 23308846.30 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.445618E+09 | 65198765.95 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.525375E+09 | 0.130970E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.535781E+09 | 0.224176E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.509864E+09 | 0.300668E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.485004E+10 | 0.166584E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.266256E+09 | 11578478.47 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.535781E+09 | 0.300668E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.302789E+09 | 0.576664E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.332493E+09 | 0.460602E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.560478E+09 | 0.421447E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.756666E+09 | 0.212074E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.966171E+09 | 0.104440E+09 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.106141E+10 | 35266347.17 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.988206E+09 | 21007586.96 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.908266E+09 | 43201618.53 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.823010E+09 | 0.123508E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.618202E+09 | 0.256236E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.394226E+09 | 0.464881E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.270878E+09 | 0.633923E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.798280E+10 | 0.335325E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.270878E+09 | 21007586.96 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.106141E+10 | 0.633923E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 11140234.30 | 0.311010E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 27965876.72 | 0.246794E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 62270970.00 | 0.227729E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.125810E+09 | 0.111297E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.222100E+09 | 51953864.13 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.306197E+09 | 18034762.73 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.295002E+09 | 10891139.97 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.231468E+09 | 22014039.79 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.160158E+09 | 64207475.38 |
October | 71778804.06 | 0.00 | 71778804.06 | 85757599.77 | 0.134821E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 21424721.26 | 0.249781E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7905821.39 | 0.343314E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.155720E+10 | 0.179185E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7905821.39 | 10891139.97 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.306197E+09 | 0.343314E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.320949E+09 | 0.558589E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.349062E+09 | 0.446197E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.576118E+09 | 0.412045E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.763999E+09 | 0.209005E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.967651E+09 | 0.103981E+09 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.106058E+10 | 35314005.66 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.988179E+09 | 20956497.08 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.911596E+09 | 42514620.54 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.831121E+09 | 0.119879E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.632428E+09 | 0.246456E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.411682E+09 | 0.449131E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.288524E+09 | 0.615245E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.810189E+10 | 0.325931E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.288524E+09 | 20956497.08 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.106058E+10 | 0.615245E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.389306E+09 | 0.251439E+09 |
February | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.338086E+09 | 0.202150E+09 |
March | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.300085E+09 | 0.192640E+09 |
April | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.239003E+09 | 0.105504E+09 |
May | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.208824E+09 | 56031095.55 |
June | 90105188.78 | 5669429.11 | 84435759.67 | 0.226325E+09 | 21931649.71 |
July | 94554156.30 | 8383125.91 | 86171030.39 | 0.234789E+09 | 15757240.01 |
August | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.267184E+09 | 26917692.74 |
September | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.353306E+09 | 62831233.49 |
October | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.413986E+09 | 0.118658E+09 |
November | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.418315E+09 | 0.201840E+09 |
December | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.392446E+09 | 0.268473E+09 |
Annual Sum or Average | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.378166E+10 | 0.152417E+10 |
Minimum of Months | 90105188.78 | 5669429.11 | 71050625.13 | 0.208824E+09 | 15757240.01 |
Maximum of Months | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.418315E+09 | 0.268473E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43713969.60 | 0.00 | 43713969.60 | 8497966.30 | 0.255199E+09 |
February | 48213648.10 | 0.00 | 48213648.10 | 23749057.48 | 0.199615E+09 |
March | 69870982.94 | 2765.95 | 69868216.99 | 54916988.00 | 0.179430E+09 |
April | 78518344.10 | 1000279.47 | 77518064.63 | 0.111753E+09 | 83467718.60 |
May | 95843144.60 | 7063304.15 | 88779840.45 | 0.193008E+09 | 37229087.74 |
June | 98633813.54 | 12290815.53 | 86342998.01 | 0.262524E+09 | 11776281.33 |
July | 94160895.41 | 9236150.10 | 84924745.31 | 0.253509E+09 | 6393602.57 |
August | 79637162.39 | 1894638.37 | 77742524.03 | 0.201667E+09 | 14406813.50 |
September | 67049393.63 | 84739.01 | 66964654.62 | 0.141406E+09 | 45240152.10 |
October | 57430655.00 | 0.00 | 57430655.00 | 77568648.14 | 0.100127E+09 |
November | 44867884.08 | 0.00 | 44867884.08 | 19569249.85 | 0.198184E+09 |
December | 43375413.74 | 0.00 | 43375413.74 | 5760890.96 | 0.283328E+09 |
Annual Sum or Average | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.135393E+10 | 0.141440E+10 |
Minimum of Months | 43375413.74 | 0.00 | 43375413.74 | 5760890.96 | 6393602.57 |
Maximum of Months | 98633813.54 | 12290815.53 | 88779840.45 | 0.262524E+09 | 0.283328E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.250823E+09 | 0.545717E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.365109E+09 | 0.427193E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.551303E+09 | 0.386238E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.796329E+09 | 0.190978E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.975257E+09 | 94625958.04 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.110017E+10 | 32585605.94 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.103375E+10 | 20054810.09 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.939394E+09 | 40024943.02 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.812369E+09 | 0.112108E+09 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.532322E+09 | 0.237848E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.341291E+09 | 0.431688E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.239455E+09 | 0.598473E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.793757E+10 | 0.311753E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.239455E+09 | 20054810.09 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.110017E+10 | 0.598473E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.502841E+09 | 0.276430E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.433709E+09 | 0.221772E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.382628E+09 | 0.214824E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.300158E+09 | 0.114238E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.260344E+09 | 56125087.63 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.285125E+09 | 18599510.01 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.298030E+09 | 11249109.50 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.338069E+09 | 23036158.83 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.441303E+09 | 64570173.63 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.524675E+09 | 0.126885E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.533714E+09 | 0.221650E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.508239E+09 | 0.299422E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.480884E+10 | 0.164880E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.260344E+09 | 11249109.50 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.533714E+09 | 0.299422E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 10417120.61 | 0.309750E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 26298159.06 | 0.247099E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 59754969.62 | 0.226272E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.120585E+09 | 0.110583E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.215599E+09 | 51218344.06 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.301414E+09 | 17660526.82 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.290890E+09 | 10583214.48 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.227338E+09 | 21630874.41 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.155922E+09 | 64034736.15 |
October | 71778804.06 | 0.00 | 71778804.06 | 84106048.76 | 0.130702E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 20382485.98 | 0.246744E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7126071.33 | 0.343057E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.151983E+10 | 0.177934E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7126071.33 | 10583214.48 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.301414E+09 | 0.343057E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.264449E+09 | 0.522459E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.379647E+09 | 0.410356E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.565100E+09 | 0.375801E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.802271E+09 | 0.188066E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.976453E+09 | 94209298.12 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.109954E+10 | 32641468.94 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.103387E+10 | 20028186.41 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.942608E+09 | 39407450.84 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.820211E+09 | 0.108875E+09 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.544814E+09 | 0.227691E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.357771E+09 | 0.412098E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.250582E+09 | 0.573290E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.803731E+10 | 0.300492E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.250582E+09 | 20028186.41 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.109954E+10 | 0.573290E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 9838808.89 | 0.426210E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 31906388.78 | 0.337405E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 78159019.18 | 0.306782E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.160178E+09 | 0.157403E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.275445E+09 | 83472603.12 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.372578E+09 | 36441443.05 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.356695E+09 | 26628586.39 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.278223E+09 | 43896974.95 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.195363E+09 | 0.103930E+09 |
October | 90903326.35 | 0.00 | 90903326.35 | 0.102388E+09 | 0.193580E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 21873665.49 | 0.350142E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 6904037.21 | 0.469032E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.188955E+10 | 0.253492E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 6904037.21 | 26628586.39 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.372578E+09 | 0.469032E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25507057.81 | 0.00 | 25507057.81 | 3626992.35 | 0.157119E+09 |
February | 28132615.74 | 0.00 | 28132615.74 | 11762016.04 | 0.124381E+09 |
March | 40769649.09 | 1613.93 | 40768035.16 | 28812650.78 | 0.113092E+09 |
April | 45815375.73 | 583662.08 | 45231713.65 | 59048309.92 | 58025134.27 |
May | 55924379.60 | 4121430.95 | 51802948.65 | 0.101540E+09 | 30771457.84 |
June | 57552732.16 | 7171678.64 | 50381053.51 | 0.137348E+09 | 13433824.83 |
July | 54942788.87 | 5389284.40 | 49553504.47 | 0.131493E+09 | 9816399.55 |
August | 46468205.09 | 1105519.60 | 45362685.49 | 0.102564E+09 | 16182242.60 |
September | 39123254.53 | 49445.13 | 39073809.41 | 72018800.09 | 38313056.62 |
October | 33510730.10 | 0.00 | 33510730.10 | 37744631.86 | 71361724.26 |
November | 26180365.76 | 0.00 | 26180365.76 | 8063538.82 | 0.129077E+09 |
December | 25309510.80 | 0.00 | 25309510.80 | 2545113.99 | 0.172905E+09 |
Annual Sum or Average | 0.479237E+09 | 18422634.73 | 0.460814E+09 | 0.696567E+09 | 0.934477E+09 |
Minimum of Months | 25309510.80 | 0.00 | 25309510.80 | 2545113.99 | 9816399.55 |
Maximum of Months | 57552732.16 | 7171678.64 | 51802948.65 | 0.137348E+09 | 0.172905E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174486E+09 | 0.132213E+09 | 42273150.31 | 0.236848E+09 | 0.135299E+09 |
February | 0.148278E+09 | 0.105157E+09 | 43120481.20 | 0.205800E+09 | 0.108465E+09 |
March | 0.128425E+09 | 72758842.37 | 55665836.43 | 0.183065E+09 | 0.105537E+09 |
April | 86599719.45 | 32508424.18 | 54091295.27 | 0.144086E+09 | 59043299.97 |
May | 63502666.49 | 9312782.27 | 54189884.22 | 0.122672E+09 | 33178981.80 |
June | 52563848.94 | 3307323.58 | 49256525.36 | 0.129574E+09 | 14113208.59 |
July | 55159202.88 | 4890388.33 | 50268814.55 | 0.134834E+09 | 10371614.22 |
August | 69629375.31 | 17690456.23 | 51938919.07 | 0.154862E+09 | 16842680.95 |
September | 0.106709E+09 | 55440358.52 | 51268838.62 | 0.206609E+09 | 37789917.80 |
October | 0.151357E+09 | 0.102833E+09 | 48524052.02 | 0.245756E+09 | 66795532.79 |
November | 0.176291E+09 | 0.134843E+09 | 41448160.50 | 0.251004E+09 | 0.111348E+09 |
December | 0.179131E+09 | 0.134578E+09 | 44553106.94 | 0.239028E+09 | 0.145449E+09 |
Annual Sum or Average | 0.139213E+10 | 0.805533E+09 | 0.586599E+09 | 0.225414E+10 | 0.844232E+09 |
Minimum of Months | 52563848.94 | 3307323.58 | 41448160.50 | 0.122672E+09 | 10371614.22 |
Maximum of Months | 0.179131E+09 | 0.134843E+09 | 55665836.43 | 0.251004E+09 | 0.145449E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473590E+09 | 0.358852E+09 | 0.114738E+09 | 0.642853E+09 | 0.367228E+09 |
February | 0.402456E+09 | 0.285418E+09 | 0.117038E+09 | 0.558583E+09 | 0.294396E+09 |
March | 0.348571E+09 | 0.197482E+09 | 0.151088E+09 | 0.496877E+09 | 0.286450E+09 |
April | 0.235049E+09 | 88234512.68 | 0.146815E+09 | 0.391078E+09 | 0.160256E+09 |
May | 0.172359E+09 | 25276795.96 | 0.147082E+09 | 0.332956E+09 | 90054543.21 |
June | 0.142669E+09 | 8976752.69 | 0.133692E+09 | 0.351689E+09 | 38306134.91 |
July | 0.149713E+09 | 13273514.24 | 0.136440E+09 | 0.365967E+09 | 28150682.47 |
August | 0.188988E+09 | 48015516.72 | 0.140973E+09 | 0.420328E+09 | 45714481.20 |
September | 0.289631E+09 | 0.150476E+09 | 0.139154E+09 | 0.560778E+09 | 0.102570E+09 |
October | 0.410813E+09 | 0.279109E+09 | 0.131704E+09 | 0.667033E+09 | 0.181297E+09 |
November | 0.478491E+09 | 0.365992E+09 | 0.112499E+09 | 0.681277E+09 | 0.302220E+09 |
December | 0.486199E+09 | 0.365273E+09 | 0.120926E+09 | 0.648772E+09 | 0.394778E+09 |
Annual Sum or Average | 0.377853E+10 | 0.218638E+10 | 0.159215E+10 | 0.611819E+10 | 0.229142E+10 |
Minimum of Months | 0.142669E+09 | 8976752.69 | 0.112499E+09 | 0.332956E+09 | 28150682.47 |
Maximum of Months | 0.486199E+09 | 0.365992E+09 | 0.151088E+09 | 0.681277E+09 | 0.394778E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.501243E+09 | 0.275561E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.434290E+09 | 0.220802E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.382420E+09 | 0.216143E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.302083E+09 | 0.113560E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.265552E+09 | 54212386.77 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.290475E+09 | 17614361.77 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.301668E+09 | 10624278.10 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.340721E+09 | 21854879.16 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.442681E+09 | 62898212.96 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.521464E+09 | 0.129595E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.532952E+09 | 0.221378E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.507973E+09 | 0.297528E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.482352E+10 | 0.164177E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.265552E+09 | 10624278.10 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.532952E+09 | 0.297528E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.300055E+09 | 0.570078E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.329047E+09 | 0.455089E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.553670E+09 | 0.417015E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.749714E+09 | 0.208046E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.960078E+09 | 0.100033E+09 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105744E+10 | 32889254.68 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.983684E+09 | 19255113.74 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.903972E+09 | 40529669.39 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.817878E+09 | 0.119024E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.613323E+09 | 0.252600E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.391135E+09 | 0.457738E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.269525E+09 | 0.625669E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.792952E+10 | 0.329797E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.269525E+09 | 19255113.74 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105744E+10 | 0.625669E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 11897224.84 | 0.306856E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 28610585.40 | 0.243078E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 62657752.61 | 0.224866E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.125182E+09 | 0.109191E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.222015E+09 | 49864616.26 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.306132E+09 | 16889855.10 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.294381E+09 | 10046616.02 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.231505E+09 | 20691071.88 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.159725E+09 | 61746188.34 |
October | 71778804.06 | 0.00 | 71778804.06 | 85979871.82 | 0.132146E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 22518070.86 | 0.244900E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 8583771.44 | 0.338475E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.155919E+10 | 0.175875E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 8583771.44 | 10046616.02 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.306132E+09 | 0.338475E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.320419E+09 | 0.551211E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.347605E+09 | 0.439416E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.571320E+09 | 0.406283E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.757509E+09 | 0.204681E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.961642E+09 | 99498308.73 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105656E+10 | 32937086.96 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.983637E+09 | 19213358.36 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.907412E+09 | 39835029.06 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.826493E+09 | 0.115160E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.629129E+09 | 0.241049E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.411376E+09 | 0.439663E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.289226E+09 | 0.606649E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.806233E+10 | 0.319560E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.289226E+09 | 19213358.36 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105656E+10 | 0.606649E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.713425E+09 | 0.424104E+09 |
February | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.620498E+09 | 0.338855E+09 |
March | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.551547E+09 | 0.321726E+09 |
April | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.446832E+09 | 0.161902E+09 |
May | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.403294E+09 | 74881139.47 |
June | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.444429E+09 | 23144141.52 |
July | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.459206E+09 | 13395788.82 |
August | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.512057E+09 | 29862912.39 |
September | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.653218E+09 | 89923212.11 |
October | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.760271E+09 | 0.193689E+09 |
November | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.766577E+09 | 0.338592E+09 |
December | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.720563E+09 | 0.457614E+09 |
Annual Sum or Average | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.705192E+10 | 0.246769E+10 |
Minimum of Months | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.403294E+09 | 13395788.82 |
Maximum of Months | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.766577E+09 | 0.457614E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 18797852.72 | 0.279677E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.109307E+09 | 0.219443E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.308443E+09 | 0.198430E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.747247E+09 | 0.101690E+10 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.139318E+10 | 0.534457E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.196464E+10 | 0.237261E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.186928E+10 | 0.186688E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.144379E+10 | 0.290657E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.101301E+10 | 0.623103E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.482257E+09 | 0.120194E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 71569684.66 | 0.221298E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 13831816.65 | 0.303823E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.943535E+10 | 0.163177E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 13831816.65 | 0.186688E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.196464E+10 | 0.303823E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 13236277.75 | 0.288570E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 95718219.96 | 0.225895E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.282439E+09 | 0.203909E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.722374E+09 | 0.104667E+10 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.136717E+10 | 0.552593E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.193854E+10 | 0.247533E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.184262E+10 | 0.197314E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.141874E+10 | 0.304135E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.994400E+09 | 0.642933E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.462011E+09 | 0.123566E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 59350578.14 | 0.227740E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 9711224.88 | 0.313141E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.920631E+10 | 0.168194E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 9711224.88 | 0.197314E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.193854E+10 | 0.313141E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 4184762.06 | 0.388926E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 21364913.92 | 0.306274E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 53884447.98 | 0.281204E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.130599E+09 | 0.149065E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.232376E+09 | 85376797.81 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.319805E+09 | 42270970.60 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.309816E+09 | 35385206.99 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.247054E+09 | 49558808.31 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.181000E+09 | 90710193.28 |
October | 71778804.06 | 0.00 | 71778804.06 | 91226264.99 | 0.169352E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 16559618.76 | 0.306061E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 3453789.42 | 0.419220E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.161132E+10 | 0.232340E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 3453789.42 | 35385206.99 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.319805E+09 | 0.419220E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544774E+09 | 0.295186E+09 | 0.249587E+09 | 0.481766E+09 | 0.131216E+10 |
February | 0.660391E+09 | 0.376560E+09 | 0.283831E+09 | 0.728407E+09 | 0.102513E+10 |
March | 0.901204E+09 | 0.496210E+09 | 0.404994E+09 | 0.110349E+10 | 0.938748E+09 |
April | 0.105137E+10 | 0.583122E+09 | 0.468243E+09 | 0.163905E+10 | 0.513994E+09 |
May | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.201507E+10 | 0.314651E+09 |
June | 0.108427E+10 | 0.602903E+09 | 0.481366E+09 | 0.226358E+10 | 0.158038E+09 |
July | 0.100542E+10 | 0.525641E+09 | 0.479782E+09 | 0.213239E+10 | 0.133995E+09 |
August | 0.957753E+09 | 0.490444E+09 | 0.467309E+09 | 0.195676E+10 | 0.184560E+09 |
September | 0.919563E+09 | 0.525105E+09 | 0.394458E+09 | 0.173843E+10 | 0.322298E+09 |
October | 0.727299E+09 | 0.391760E+09 | 0.335538E+09 | 0.111380E+10 | 0.596739E+09 |
November | 0.630213E+09 | 0.366045E+09 | 0.264168E+09 | 0.686738E+09 | 0.102587E+10 |
December | 0.545185E+09 | 0.288898E+09 | 0.256287E+09 | 0.464205E+09 | 0.140708E+10 |
Annual Sum or Average | 0.101474E+11 | 0.555027E+10 | 0.459710E+10 | 0.163237E+11 | 0.793326E+10 |
Minimum of Months | 0.544774E+09 | 0.288898E+09 | 0.249587E+09 | 0.464205E+09 | 0.133995E+09 |
Maximum of Months | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.226358E+10 | 0.140708E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.498700E+09 | 0.332240E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.434580E+09 | 0.266981E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.384341E+09 | 0.259984E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.311316E+09 | 0.150590E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.274724E+09 | 90156805.49 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.301511E+09 | 43269782.75 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.315801E+09 | 36345345.86 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.358954E+09 | 50665456.29 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.470356E+09 | 90045546.43 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.540420E+09 | 0.159675E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.539445E+09 | 0.264121E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.504603E+09 | 0.350501E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.493475E+10 | 0.209458E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.274724E+09 | 36345345.86 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.540420E+09 | 0.350501E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 7190121.35 | 0.435623E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 27564931.10 | 0.342070E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 71921817.27 | 0.308311E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.149967E+09 | 0.160471E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.262558E+09 | 87108497.03 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.359545E+09 | 39296615.23 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.341938E+09 | 30189102.25 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.265156E+09 | 47617195.11 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.186237E+09 | 0.106569E+09 |
October | 90903326.35 | 0.00 | 90903326.35 | 95034211.52 | 0.194323E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 18705811.48 | 0.348869E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 5345363.51 | 0.478897E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.179116E+10 | 0.257935E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 5345363.51 | 30189102.25 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.359545E+09 | 0.478897E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61906396.97 | 0.00 | 61906396.97 | 6433028.81 | 0.389753E+09 |
February | 68278705.09 | 0.00 | 68278705.09 | 24662448.30 | 0.306052E+09 |
March | 98949165.36 | 3917.06 | 98945248.31 | 64348722.43 | 0.275847E+09 |
April | 0.111195E+09 | 1416565.43 | 0.109779E+09 | 0.134176E+09 | 0.143574E+09 |
May | 0.135730E+09 | 10002836.96 | 0.125727E+09 | 0.234912E+09 | 77936302.34 |
June | 0.139682E+09 | 17405879.91 | 0.122276E+09 | 0.321686E+09 | 35158830.54 |
July | 0.133348E+09 | 13079955.45 | 0.120268E+09 | 0.305933E+09 | 27010304.17 |
August | 0.112780E+09 | 2683129.35 | 0.110097E+09 | 0.237236E+09 | 42603284.89 |
September | 94953316.23 | 120004.81 | 94833311.42 | 0.166627E+09 | 95348083.55 |
October | 81331550.52 | 0.00 | 81331550.52 | 85027469.13 | 0.173862E+09 |
November | 63540535.64 | 0.00 | 63540535.64 | 16736160.40 | 0.312134E+09 |
December | 61426944.44 | 0.00 | 61426944.44 | 4782516.99 | 0.428454E+09 |
Annual Sum or Average | 0.116312E+10 | 44712288.96 | 0.111841E+10 | 0.160256E+10 | 0.230773E+10 |
Minimum of Months | 61426944.44 | 0.00 | 61426944.44 | 4782516.99 | 27010304.17 |
Maximum of Months | 0.139682E+09 | 17405879.91 | 0.125727E+09 | 0.321686E+09 | 0.428454E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139608E+10 | 0.105785E+10 | 0.338233E+09 | 0.185829E+10 | 0.109750E+10 |
February | 0.118639E+10 | 0.841376E+09 | 0.345013E+09 | 0.161383E+10 | 0.876926E+09 |
March | 0.102754E+10 | 0.582153E+09 | 0.445390E+09 | 0.142915E+10 | 0.847887E+09 |
April | 0.692896E+09 | 0.260104E+09 | 0.432792E+09 | 0.111364E+10 | 0.482379E+09 |
May | 0.508093E+09 | 74512840.84 | 0.433581E+09 | 0.941475E+09 | 0.277136E+09 |
June | 0.420571E+09 | 26462346.95 | 0.394108E+09 | 0.999890E+09 | 0.121568E+09 |
July | 0.441336E+09 | 39128663.92 | 0.402208E+09 | 0.103558E+10 | 94290095.18 |
August | 0.557114E+09 | 0.141544E+09 | 0.415570E+09 | 0.119673E+10 | 0.146610E+09 |
September | 0.853795E+09 | 0.443586E+09 | 0.410209E+09 | 0.161791E+10 | 0.310773E+09 |
October | 0.121103E+10 | 0.822779E+09 | 0.388248E+09 | 0.193116E+10 | 0.537117E+09 |
November | 0.141053E+10 | 0.107890E+10 | 0.331632E+09 | 0.198262E+10 | 0.884540E+09 |
December | 0.143326E+10 | 0.107678E+10 | 0.356475E+09 | 0.187854E+10 | 0.117728E+10 |
Annual Sum or Average | 0.111386E+11 | 0.644518E+10 | 0.469346E+10 | 0.175988E+11 | 0.685401E+10 |
Minimum of Months | 0.420571E+09 | 26462346.95 | 0.331632E+09 | 0.941475E+09 | 94290095.18 |
Maximum of Months | 0.143326E+10 | 0.107890E+10 | 0.445390E+09 | 0.198262E+10 | 0.117728E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 934.24 | 537.22 | 706.15 | 535.07 | 171.08 | 0.00 | 0.00 |
February | 898.89 | 475.60 | 664.38 | 471.17 | 193.21 | 0.00 | 0.00 |
March | 726.40 | 414.47 | 519.74 | 294.46 | 225.28 | 0.00 | 0.00 |
April | 580.37 | 247.13 | 362.15 | 135.95 | 226.20 | 0.00 | 0.00 |
May | 466.52 | 140.77 | 257.00 | 37.69 | 219.31 | 0.00 | 0.00 |
June | 495.64 | 66.98 | 219.82 | 13.83 | 205.99 | 0.00 | 0.00 |
July | 503.21 | 50.45 | 223.23 | 19.79 | 203.44 | 0.00 | 0.00 |
August | 588.84 | 76.59 | 281.79 | 71.59 | 210.20 | 0.00 | 0.00 |
September | 834.84 | 165.71 | 446.25 | 231.85 | 214.40 | 0.00 | 0.00 |
October | 970.71 | 270.63 | 612.55 | 416.17 | 196.38 | 0.00 | 0.00 |
November | 1025.23 | 454.38 | 737.24 | 563.91 | 173.33 | 0.00 | 0.00 |
December | 938.89 | 577.40 | 724.95 | 544.65 | 180.31 | 0.00 | 0.00 |
Annual Sum or Average | 745.87 | 288.87 | 478.50 | 276.88 | 201.63 | 0.00 | 0.00 |
Minimum of Months | 466.52 | 50.45 | 219.82 | 13.83 | 171.08 | 0.00 | 0.00 |
Maximum of Months | 1025.23 | 577.40 | 737.24 | 563.91 | 226.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2581.00 | 1652.99 | 1988.48 | 1506.73 | 481.75 | 0.00 | 0.00 |
February | 2477.60 | 1472.69 | 1870.85 | 1326.79 | 544.06 | 0.00 | 0.00 |
March | 1990.80 | 1288.97 | 1463.55 | 829.18 | 634.37 | 0.00 | 0.00 |
April | 1594.44 | 769.17 | 1019.80 | 382.82 | 636.98 | 0.00 | 0.00 |
May | 1288.36 | 430.74 | 723.68 | 106.13 | 617.55 | 0.00 | 0.00 |
June | 1385.26 | 198.08 | 618.99 | 38.95 | 580.04 | 0.00 | 0.00 |
July | 1405.53 | 150.46 | 628.60 | 55.73 | 572.87 | 0.00 | 0.00 |
August | 1643.12 | 230.89 | 793.51 | 201.60 | 591.90 | 0.00 | 0.00 |
September | 2329.81 | 487.32 | 1256.61 | 652.87 | 603.74 | 0.00 | 0.00 |
October | 2699.71 | 822.57 | 1724.89 | 1171.91 | 552.99 | 0.00 | 0.00 |
November | 2840.05 | 1388.32 | 2076.02 | 1587.93 | 488.09 | 0.00 | 0.00 |
December | 2588.75 | 1762.85 | 2041.42 | 1533.69 | 507.73 | 0.00 | 0.00 |
Annual Sum or Average | 2065.69 | 885.06 | 1347.44 | 779.68 | 567.76 | 0.00 | 0.00 |
Minimum of Months | 1288.36 | 150.46 | 618.99 | 38.95 | 481.75 | 0.00 | 0.00 |
Maximum of Months | 2840.05 | 1762.85 | 2076.02 | 1587.93 | 636.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3428.74 | 2209.91 | 2583.15 | 1957.32 | 625.82 | 0.00 | 0.00 |
February | 3296.17 | 1960.20 | 2430.34 | 1723.58 | 706.76 | 0.00 | 0.00 |
March | 2654.51 | 1717.49 | 1901.24 | 1077.15 | 824.09 | 0.00 | 0.00 |
April | 2136.44 | 1017.02 | 1324.78 | 497.31 | 827.47 | 0.00 | 0.00 |
May | 1731.90 | 565.06 | 940.11 | 137.87 | 802.24 | 0.00 | 0.00 |
June | 1869.43 | 255.65 | 804.10 | 50.59 | 753.51 | 0.00 | 0.00 |
July | 1894.88 | 192.23 | 816.59 | 72.40 | 744.19 | 0.00 | 0.00 |
August | 2206.16 | 296.54 | 1030.81 | 261.90 | 768.91 | 0.00 | 0.00 |
September | 3108.95 | 629.07 | 1632.41 | 848.12 | 784.29 | 0.00 | 0.00 |
October | 3586.12 | 1077.69 | 2240.73 | 1522.37 | 718.36 | 0.00 | 0.00 |
November | 3765.34 | 1848.21 | 2696.87 | 2062.81 | 634.06 | 0.00 | 0.00 |
December | 3436.70 | 2362.40 | 2651.92 | 1992.35 | 659.58 | 0.00 | 0.00 |
Annual Sum or Average | 2755.64 | 1173.82 | 1750.40 | 1012.84 | 737.56 | 0.00 | 0.00 |
Minimum of Months | 1731.90 | 192.23 | 804.10 | 50.59 | 625.82 | 0.00 | 0.00 |
Maximum of Months | 3765.34 | 2362.40 | 2696.87 | 2062.81 | 827.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.73 | 303.58 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 306.31 | 270.66 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 348.30 | 233.45 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 408.28 | 125.02 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 460.01 | 59.96 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 521.36 | 20.92 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 481.70 | 12.09 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 466.72 | 24.78 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 489.17 | 72.53 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 424.40 | 142.00 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 347.34 | 254.39 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 272.38 | 329.82 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 401.31 | 153.54 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 272.38 | 12.09 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 521.36 | 329.82 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.46 | 320.15 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 152.30 | 282.90 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 235.55 | 236.07 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 342.34 | 122.62 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 443.41 | 57.42 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 526.90 | 20.18 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 478.82 | 11.62 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 426.55 | 23.87 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 382.38 | 70.97 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 267.12 | 141.34 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 163.52 | 266.07 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 105.32 | 352.53 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 304.33 | 158.22 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 105.32 | 11.62 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 526.90 | 352.53 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.35 | 93.88 | 111.67 | 84.62 | 27.06 | 0.00 | 0.00 |
February | 139.75 | 83.56 | 105.07 | 74.51 | 30.55 | 0.00 | 0.00 |
March | 112.04 | 71.92 | 82.19 | 46.57 | 35.63 | 0.00 | 0.00 |
April | 92.21 | 40.70 | 57.27 | 21.50 | 35.77 | 0.00 | 0.00 |
May | 77.97 | 20.92 | 40.64 | 5.96 | 34.68 | 0.00 | 0.00 |
June | 87.32 | 8.46 | 34.76 | 2.19 | 32.58 | 0.00 | 0.00 |
July | 87.66 | 5.88 | 35.30 | 3.13 | 32.17 | 0.00 | 0.00 |
August | 99.76 | 10.05 | 44.56 | 11.32 | 33.24 | 0.00 | 0.00 |
September | 136.31 | 24.24 | 70.57 | 36.67 | 33.91 | 0.00 | 0.00 |
October | 154.56 | 44.30 | 96.87 | 65.81 | 31.06 | 0.00 | 0.00 |
November | 161.39 | 77.87 | 116.59 | 89.18 | 27.41 | 0.00 | 0.00 |
December | 146.52 | 100.24 | 114.65 | 86.13 | 28.51 | 0.00 | 0.00 |
Annual Sum or Average | 119.92 | 48.33 | 75.67 | 43.79 | 31.89 | 0.00 | 0.00 |
Minimum of Months | 77.97 | 5.88 | 34.76 | 2.19 | 27.06 | 0.00 | 0.00 |
Maximum of Months | 161.39 | 100.24 | 116.59 | 89.18 | 35.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.17 | 95.28 | 16.32 | 0.00 | 16.32 | 0.00 | 0.00 |
February | 9.82 | 82.51 | 19.93 | 0.00 | 19.93 | 0.00 | 0.00 |
March | 20.50 | 66.99 | 26.09 | 0.00 | 26.09 | 0.00 | 0.00 |
April | 43.11 | 32.20 | 30.29 | 0.39 | 29.91 | 0.00 | 0.00 |
May | 72.06 | 13.90 | 35.78 | 2.64 | 33.15 | 0.00 | 0.00 |
June | 101.28 | 4.54 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
July | 94.65 | 2.39 | 35.16 | 3.45 | 31.71 | 0.00 | 0.00 |
August | 75.29 | 5.38 | 29.73 | 0.71 | 29.03 | 0.00 | 0.00 |
September | 54.55 | 17.45 | 25.87 | 0.03 | 25.84 | 0.00 | 0.00 |
October | 28.96 | 37.38 | 21.44 | 0.00 | 21.44 | 0.00 | 0.00 |
November | 7.55 | 76.46 | 17.31 | 0.00 | 17.31 | 0.00 | 0.00 |
December | 2.15 | 105.78 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Annual Sum or Average | 42.93 | 44.85 | 26.04 | 1.00 | 25.04 | 0.00 | 0.00 |
Minimum of Months | 2.15 | 2.39 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Maximum of Months | 101.28 | 105.78 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 272.07 | 297.64 | 241.32 | 160.90 | 80.42 | 0.00 | 0.00 |
February | 324.06 | 262.12 | 267.86 | 170.99 | 96.87 | 0.00 | 0.00 |
March | 343.41 | 219.13 | 271.01 | 150.86 | 120.15 | 0.00 | 0.00 |
April | 418.50 | 113.22 | 274.43 | 139.37 | 135.06 | 0.00 | 0.00 |
May | 459.25 | 54.22 | 259.90 | 121.04 | 138.86 | 0.00 | 0.00 |
June | 534.02 | 19.32 | 252.63 | 119.04 | 133.59 | 0.00 | 0.00 |
July | 497.03 | 11.48 | 231.84 | 102.05 | 129.80 | 0.00 | 0.00 |
August | 476.36 | 22.95 | 234.52 | 105.72 | 128.80 | 0.00 | 0.00 |
September | 481.90 | 66.39 | 265.63 | 147.14 | 118.49 | 0.00 | 0.00 |
October | 393.39 | 134.93 | 256.89 | 155.42 | 101.47 | 0.00 | 0.00 |
November | 331.61 | 246.09 | 267.34 | 182.11 | 85.23 | 0.00 | 0.00 |
December | 266.72 | 322.80 | 245.12 | 161.62 | 83.50 | 0.00 | 0.00 |
Annual Sum or Average | 400.03 | 146.98 | 255.51 | 142.75 | 112.76 | 0.00 | 0.00 |
Minimum of Months | 266.72 | 11.48 | 231.84 | 102.05 | 80.42 | 0.00 | 0.00 |
Maximum of Months | 534.02 | 322.80 | 274.43 | 182.11 | 138.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.61 | 300.70 | 122.10 | 55.11 | 66.99 | 0.00 | 0.00 |
February | 157.07 | 261.04 | 161.41 | 77.83 | 83.58 | 0.00 | 0.00 |
March | 224.78 | 216.28 | 200.85 | 92.64 | 108.21 | 0.00 | 0.00 |
April | 352.18 | 111.35 | 240.68 | 112.98 | 127.71 | 0.00 | 0.00 |
May | 444.64 | 53.88 | 253.81 | 116.88 | 136.93 | 0.00 | 0.00 |
June | 540.47 | 19.38 | 256.73 | 122.24 | 134.50 | 0.00 | 0.00 |
July | 494.56 | 11.38 | 231.64 | 102.44 | 129.20 | 0.00 | 0.00 |
August | 436.64 | 22.62 | 215.97 | 92.45 | 123.52 | 0.00 | 0.00 |
September | 374.44 | 64.56 | 209.73 | 101.34 | 108.39 | 0.00 | 0.00 |
October | 231.63 | 130.63 | 162.58 | 73.14 | 89.44 | 0.00 | 0.00 |
November | 136.78 | 245.07 | 143.21 | 70.62 | 72.60 | 0.00 | 0.00 |
December | 84.23 | 330.14 | 122.02 | 53.93 | 68.09 | 0.00 | 0.00 |
Annual Sum or Average | 298.07 | 146.72 | 193.45 | 89.26 | 104.19 | 0.00 | 0.00 |
Minimum of Months | 84.23 | 11.38 | 122.02 | 53.93 | 66.99 | 0.00 | 0.00 |
Maximum of Months | 540.47 | 330.14 | 256.73 | 122.24 | 136.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 309.71 | 381.65 | 277.32 | 183.34 | 93.98 | 0.00 | 0.00 |
February | 317.01 | 340.41 | 270.83 | 161.45 | 109.38 | 0.00 | 0.00 |
March | 288.27 | 297.59 | 234.60 | 100.90 | 133.70 | 0.00 | 0.00 |
April | 290.54 | 167.21 | 189.72 | 47.42 | 142.30 | 0.00 | 0.00 |
May | 309.80 | 87.61 | 165.58 | 18.63 | 146.95 | 0.00 | 0.00 |
June | 381.77 | 38.83 | 157.76 | 15.01 | 142.75 | 0.00 | 0.00 |
July | 368.69 | 27.44 | 152.65 | 14.25 | 138.40 | 0.00 | 0.00 |
August | 356.61 | 45.48 | 160.97 | 26.06 | 134.90 | 0.00 | 0.00 |
September | 398.88 | 108.69 | 208.95 | 79.51 | 129.43 | 0.00 | 0.00 |
October | 389.57 | 188.00 | 256.34 | 142.60 | 113.74 | 0.00 | 0.00 |
November | 353.26 | 326.47 | 290.12 | 193.22 | 96.89 | 0.00 | 0.00 |
December | 304.59 | 410.96 | 283.49 | 186.62 | 96.87 | 0.00 | 0.00 |
Annual Sum or Average | 339.05 | 201.01 | 220.38 | 97.04 | 123.34 | 0.00 | 0.00 |
Minimum of Months | 288.27 | 27.44 | 152.65 | 14.25 | 93.98 | 0.00 | 0.00 |
Maximum of Months | 398.88 | 410.96 | 290.12 | 193.22 | 146.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 284.06 | 300.61 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 304.03 | 267.89 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 344.35 | 231.25 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 404.41 | 122.70 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 457.46 | 57.45 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 520.03 | 19.48 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 479.82 | 11.08 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 464.66 | 23.24 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 486.09 | 69.94 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 421.29 | 140.30 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 345.56 | 251.05 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 271.81 | 326.21 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 398.97 | 151.21 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 271.81 | 11.08 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 520.03 | 326.21 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.76 | 316.06 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 152.08 | 278.68 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 233.89 | 232.83 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 339.57 | 120.12 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 441.16 | 55.00 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 525.37 | 18.87 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 476.93 | 10.70 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 425.03 | 22.40 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 380.43 | 68.20 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 265.95 | 138.30 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 163.97 | 260.67 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 106.15 | 347.82 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 303.22 | 155.22 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 106.15 | 10.70 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 525.37 | 347.82 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.36 | 158.34 | 204.76 | 155.16 | 49.61 | 0.00 | 0.00 |
February | 256.49 | 140.07 | 192.65 | 136.63 | 56.02 | 0.00 | 0.00 |
March | 205.92 | 120.12 | 150.71 | 85.38 | 65.33 | 0.00 | 0.00 |
April | 172.39 | 62.46 | 105.01 | 39.42 | 65.59 | 0.00 | 0.00 |
May | 150.57 | 27.96 | 74.52 | 10.93 | 63.59 | 0.00 | 0.00 |
June | 171.46 | 8.93 | 63.74 | 4.01 | 59.73 | 0.00 | 0.00 |
July | 171.45 | 5.00 | 64.73 | 5.74 | 58.99 | 0.00 | 0.00 |
August | 191.18 | 11.15 | 81.71 | 20.76 | 60.95 | 0.00 | 0.00 |
September | 252.01 | 34.69 | 129.40 | 67.23 | 62.17 | 0.00 | 0.00 |
October | 283.85 | 72.32 | 177.62 | 120.68 | 56.94 | 0.00 | 0.00 |
November | 295.75 | 130.63 | 213.78 | 163.52 | 50.26 | 0.00 | 0.00 |
December | 269.03 | 170.85 | 210.22 | 157.93 | 52.28 | 0.00 | 0.00 |
Annual Sum or Average | 223.61 | 78.25 | 138.75 | 80.29 | 58.47 | 0.00 | 0.00 |
Minimum of Months | 150.57 | 5.00 | 63.74 | 4.01 | 49.61 | 0.00 | 0.00 |
Maximum of Months | 295.75 | 170.85 | 213.78 | 163.52 | 65.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.02 | 1044.19 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 45.18 | 907.09 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 115.16 | 740.85 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 288.29 | 392.32 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 520.15 | 199.54 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 757.96 | 91.54 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 697.91 | 69.70 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 539.05 | 108.52 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 390.82 | 240.39 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 180.05 | 448.75 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 27.61 | 853.77 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 5.16 | 1134.35 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 299.19 | 517.43 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 5.16 | 69.70 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 757.96 | 1134.35 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.94 | 1077.40 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 39.57 | 933.76 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 105.45 | 761.31 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 278.69 | 403.81 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 510.44 | 206.31 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 747.89 | 95.50 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 687.96 | 73.67 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 529.70 | 113.55 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 383.64 | 248.05 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 172.50 | 461.34 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 22.90 | 878.63 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 3.63 | 1169.13 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 291.93 | 533.34 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 3.63 | 73.67 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 747.89 | 1169.13 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.50 | 722.03 | 363.41 | 216.00 | 147.41 | 0.00 | 0.00 |
February | 463.48 | 634.63 | 429.25 | 248.81 | 180.43 | 0.00 | 0.00 |
March | 558.22 | 535.16 | 471.84 | 243.48 | 228.35 | 0.00 | 0.00 |
April | 793.79 | 304.85 | 515.08 | 252.33 | 262.75 | 0.00 | 0.00 |
May | 938.70 | 180.04 | 513.67 | 237.90 | 275.77 | 0.00 | 0.00 |
June | 1112.48 | 93.45 | 509.34 | 241.26 | 268.07 | 0.00 | 0.00 |
July | 1029.42 | 76.51 | 463.46 | 204.47 | 258.98 | 0.00 | 0.00 |
August | 956.06 | 105.56 | 450.46 | 198.15 | 252.31 | 0.00 | 0.00 |
September | 918.68 | 190.78 | 475.33 | 248.47 | 226.86 | 0.00 | 0.00 |
October | 646.82 | 340.79 | 419.45 | 228.55 | 190.90 | 0.00 | 0.00 |
November | 457.01 | 593.32 | 410.54 | 252.72 | 157.82 | 0.00 | 0.00 |
December | 316.69 | 766.42 | 367.13 | 215.55 | 151.58 | 0.00 | 0.00 |
Annual Sum or Average | 710.97 | 377.43 | 448.93 | 231.99 | 216.94 | 0.00 | 0.00 |
Minimum of Months | 316.69 | 76.51 | 363.41 | 198.15 | 147.41 | 0.00 | 0.00 |
Maximum of Months | 1112.48 | 766.42 | 515.08 | 252.72 | 275.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 661.99 | 681.02 | 570.18 | 394.96 | 175.23 | 0.00 | 0.00 |
February | 662.56 | 604.28 | 550.17 | 347.79 | 202.38 | 0.00 | 0.00 |
March | 575.80 | 526.00 | 461.88 | 217.35 | 244.52 | 0.00 | 0.00 |
April | 538.47 | 302.61 | 358.17 | 101.51 | 256.66 | 0.00 | 0.00 |
May | 535.38 | 163.23 | 297.02 | 35.73 | 261.29 | 0.00 | 0.00 |
June | 647.31 | 74.35 | 276.38 | 24.43 | 251.95 | 0.00 | 0.00 |
July | 627.43 | 55.46 | 270.21 | 24.95 | 245.26 | 0.00 | 0.00 |
August | 633.79 | 87.83 | 297.17 | 54.97 | 242.20 | 0.00 | 0.00 |
September | 759.82 | 197.29 | 406.97 | 171.23 | 235.74 | 0.00 | 0.00 |
October | 782.89 | 332.66 | 516.45 | 307.19 | 209.26 | 0.00 | 0.00 |
November | 751.87 | 569.57 | 596.10 | 416.24 | 179.86 | 0.00 | 0.00 |
December | 658.21 | 731.37 | 583.68 | 402.02 | 181.66 | 0.00 | 0.00 |
Annual Sum or Average | 652.65 | 359.29 | 431.31 | 207.38 | 223.93 | 0.00 | 0.00 |
Minimum of Months | 535.38 | 55.46 | 270.21 | 24.43 | 175.23 | 0.00 | 0.00 |
Maximum of Months | 782.89 | 731.37 | 596.10 | 416.24 | 261.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250226E+10 | 0.143890E+10 | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.00 | 0.00 |
February | 0.217459E+10 | 0.115058E+10 | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.00 | 0.00 |
March | 0.194558E+10 | 0.111012E+10 | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.00 | 0.00 |
April | 0.150431E+10 | 0.640562E+09 | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.00 | 0.00 |
May | 0.124952E+10 | 0.377038E+09 | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.00 | 0.00 |
June | 0.128469E+10 | 0.173619E+09 | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.00 | 0.00 |
July | 0.134781E+10 | 0.135115E+09 | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.00 | 0.00 |
August | 0.157716E+10 | 0.205134E+09 | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.00 | 0.00 |
September | 0.216390E+10 | 0.429517E+09 | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.00 | 0.00 |
October | 0.259995E+10 | 0.724862E+09 | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.00 | 0.00 |
November | 0.265738E+10 | 0.117776E+10 | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.00 | 0.00 |
December | 0.251471E+10 | 0.154650E+10 | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.235219E+11 | 0.910970E+10 | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.00 | 0.00 |
Minimum of Months | 0.124952E+10 | 0.135115E+09 | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.265738E+10 | 0.154650E+10 | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.691295E+10 | 0.442736E+10 | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.00 | 0.00 |
February | 0.599381E+10 | 0.356273E+10 | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.00 | 0.00 |
March | 0.533215E+10 | 0.345238E+10 | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.00 | 0.00 |
April | 0.413279E+10 | 0.199369E+10 | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.00 | 0.00 |
May | 0.345076E+10 | 0.115370E+10 | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.00 | 0.00 |
June | 0.359060E+10 | 0.513422E+09 | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.00 | 0.00 |
July | 0.376458E+10 | 0.402994E+09 | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.00 | 0.00 |
August | 0.440093E+10 | 0.618411E+09 | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.00 | 0.00 |
September | 0.603886E+10 | 0.126313E+10 | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.00 | 0.00 |
October | 0.723091E+10 | 0.220318E+10 | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.00 | 0.00 |
November | 0.736142E+10 | 0.359852E+10 | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.00 | 0.00 |
December | 0.693370E+10 | 0.472162E+10 | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.651435E+11 | 0.279111E+11 | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.00 | 0.00 |
Minimum of Months | 0.345076E+10 | 0.402994E+09 | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.736142E+10 | 0.472162E+10 | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.918355E+10 | 0.591902E+10 | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.00 | 0.00 |
February | 0.797410E+10 | 0.474212E+10 | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.00 | 0.00 |
March | 0.710985E+10 | 0.460012E+10 | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.00 | 0.00 |
April | 0.553766E+10 | 0.263612E+10 | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.00 | 0.00 |
May | 0.463871E+10 | 0.151344E+10 | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.00 | 0.00 |
June | 0.484556E+10 | 0.662634E+09 | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.00 | 0.00 |
July | 0.507526E+10 | 0.514870E+09 | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.00 | 0.00 |
August | 0.590897E+10 | 0.794253E+09 | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.00 | 0.00 |
September | 0.805840E+10 | 0.163055E+10 | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.00 | 0.00 |
October | 0.960505E+10 | 0.288647E+10 | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.00 | 0.00 |
November | 0.975976E+10 | 0.479057E+10 | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.00 | 0.00 |
December | 0.920486E+10 | 0.632744E+10 | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.869017E+11 | 0.370176E+11 | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.463871E+10 | 0.514870E+09 | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.975976E+10 | 0.632744E+10 | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.765290E+09 | 0.813118E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.741035E+09 | 0.654784E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.932884E+09 | 0.625262E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.105827E+10 | 0.324057E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.123208E+10 | 0.160607E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.135138E+10 | 54233586.81 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.129018E+10 | 32391025.91 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.125005E+10 | 66364097.28 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.126792E+10 | 0.187996E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.113671E+10 | 0.380337E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.900315E+09 | 0.659366E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.729538E+09 | 0.883386E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126556E+11 | 0.484190E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.729538E+09 | 32391025.91 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135138E+10 | 0.883386E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.319975E+09 | 0.857485E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.368434E+09 | 0.684397E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.630899E+09 | 0.632283E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.887345E+09 | 0.317837E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.118762E+10 | 0.153804E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.136574E+10 | 52304782.46 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.128246E+10 | 31127185.56 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.114248E+10 | 63940096.63 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.991140E+09 | 0.183948E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.715467E+09 | 0.378558E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.423848E+09 | 0.689653E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.282096E+09 | 0.944226E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.959750E+10 | 0.498956E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.282096E+09 | 31127185.56 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136574E+10 | 0.944226E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.389306E+09 | 0.251439E+09 | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.00 | 0.00 |
February | 0.338086E+09 | 0.202150E+09 | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.00 | 0.00 |
March | 0.300085E+09 | 0.192640E+09 | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.00 | 0.00 |
April | 0.239003E+09 | 0.105504E+09 | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.00 | 0.00 |
May | 0.208824E+09 | 56031095.55 | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.00 | 0.00 |
June | 0.226325E+09 | 21931649.71 | 90105188.78 | 5669429.11 | 84435759.67 | 0.00 | 0.00 |
July | 0.234789E+09 | 15757240.01 | 94554156.30 | 8383125.91 | 86171030.39 | 0.00 | 0.00 |
August | 0.267184E+09 | 26917692.74 | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.00 | 0.00 |
September | 0.353306E+09 | 62831233.49 | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.00 | 0.00 |
October | 0.413986E+09 | 0.118658E+09 | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.00 | 0.00 |
November | 0.418315E+09 | 0.201840E+09 | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.00 | 0.00 |
December | 0.392446E+09 | 0.268473E+09 | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.378166E+10 | 0.152417E+10 | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.208824E+09 | 15757240.01 | 90105188.78 | 5669429.11 | 71050625.13 | 0.00 | 0.00 |
Maximum of Months | 0.418315E+09 | 0.268473E+09 | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8497966.30 | 0.255199E+09 | 43713969.60 | 0.00 | 43713969.60 | 0.00 | 0.00 |
February | 23749057.48 | 0.199615E+09 | 48213648.10 | 0.00 | 48213648.10 | 0.00 | 0.00 |
March | 54916988.00 | 0.179430E+09 | 69870982.94 | 2765.95 | 69868216.99 | 0.00 | 0.00 |
April | 0.111753E+09 | 83467718.60 | 78518344.10 | 1000279.47 | 77518064.63 | 0.00 | 0.00 |
May | 0.193008E+09 | 37229087.74 | 95843144.60 | 7063304.15 | 88779840.45 | 0.00 | 0.00 |
June | 0.262524E+09 | 11776281.33 | 98633813.54 | 12290815.53 | 86342998.01 | 0.00 | 0.00 |
July | 0.253509E+09 | 6393602.57 | 94160895.41 | 9236150.10 | 84924745.31 | 0.00 | 0.00 |
August | 0.201667E+09 | 14406813.50 | 79637162.39 | 1894638.37 | 77742524.03 | 0.00 | 0.00 |
September | 0.141406E+09 | 45240152.10 | 67049393.63 | 84739.01 | 66964654.62 | 0.00 | 0.00 |
October | 77568648.14 | 0.100127E+09 | 57430655.00 | 0.00 | 57430655.00 | 0.00 | 0.00 |
November | 19569249.85 | 0.198184E+09 | 44867884.08 | 0.00 | 44867884.08 | 0.00 | 0.00 |
December | 5760890.96 | 0.283328E+09 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.135393E+10 | 0.141440E+10 | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.00 | 0.00 |
Minimum of Months | 5760890.96 | 6393602.57 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Maximum of Months | 0.262524E+09 | 0.283328E+09 | 98633813.54 | 12290815.53 | 88779840.45 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.728704E+09 | 0.797187E+09 | 0.646361E+09 | 0.430960E+09 | 0.215402E+09 | 0.00 | 0.00 |
February | 0.783966E+09 | 0.634113E+09 | 0.648005E+09 | 0.413664E+09 | 0.234341E+09 | 0.00 | 0.00 |
March | 0.919795E+09 | 0.586925E+09 | 0.725871E+09 | 0.404058E+09 | 0.321813E+09 | 0.00 | 0.00 |
April | 0.108474E+10 | 0.293468E+09 | 0.711319E+09 | 0.361253E+09 | 0.350066E+09 | 0.00 | 0.00 |
May | 0.123006E+10 | 0.145214E+09 | 0.696105E+09 | 0.324180E+09 | 0.371925E+09 | 0.00 | 0.00 |
June | 0.138418E+10 | 50075300.83 | 0.654827E+09 | 0.308561E+09 | 0.346266E+09 | 0.00 | 0.00 |
July | 0.133124E+10 | 30761005.64 | 0.620963E+09 | 0.273320E+09 | 0.347643E+09 | 0.00 | 0.00 |
August | 0.127588E+10 | 61473363.77 | 0.628139E+09 | 0.283153E+09 | 0.344986E+09 | 0.00 | 0.00 |
September | 0.124908E+10 | 0.172083E+09 | 0.688511E+09 | 0.381390E+09 | 0.307121E+09 | 0.00 | 0.00 |
October | 0.105367E+10 | 0.361404E+09 | 0.688060E+09 | 0.416283E+09 | 0.271777E+09 | 0.00 | 0.00 |
November | 0.859535E+09 | 0.637869E+09 | 0.692953E+09 | 0.472029E+09 | 0.220924E+09 | 0.00 | 0.00 |
December | 0.714389E+09 | 0.864589E+09 | 0.656523E+09 | 0.432885E+09 | 0.223638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126152E+11 | 0.463516E+10 | 0.805764E+10 | 0.450174E+10 | 0.355590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.714389E+09 | 30761005.64 | 0.620963E+09 | 0.273320E+09 | 0.215402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138418E+10 | 0.864589E+09 | 0.725871E+09 | 0.472029E+09 | 0.371925E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248053E+09 | 0.805395E+09 | 0.327041E+09 | 0.147604E+09 | 0.179438E+09 | 0.00 | 0.00 |
February | 0.379992E+09 | 0.631503E+09 | 0.390478E+09 | 0.188293E+09 | 0.202185E+09 | 0.00 | 0.00 |
March | 0.602057E+09 | 0.579276E+09 | 0.537961E+09 | 0.248126E+09 | 0.289835E+09 | 0.00 | 0.00 |
April | 0.912838E+09 | 0.288631E+09 | 0.623855E+09 | 0.292832E+09 | 0.331023E+09 | 0.00 | 0.00 |
May | 0.119093E+10 | 0.144301E+09 | 0.679796E+09 | 0.313049E+09 | 0.366746E+09 | 0.00 | 0.00 |
June | 0.140089E+10 | 50236791.54 | 0.665449E+09 | 0.316834E+09 | 0.348614E+09 | 0.00 | 0.00 |
July | 0.132463E+10 | 30473942.00 | 0.620433E+09 | 0.274383E+09 | 0.346050E+09 | 0.00 | 0.00 |
August | 0.116948E+10 | 60576122.06 | 0.578444E+09 | 0.247607E+09 | 0.330837E+09 | 0.00 | 0.00 |
September | 0.970550E+09 | 0.167328E+09 | 0.543615E+09 | 0.262677E+09 | 0.280938E+09 | 0.00 | 0.00 |
October | 0.620398E+09 | 0.349871E+09 | 0.435454E+09 | 0.195894E+09 | 0.239560E+09 | 0.00 | 0.00 |
November | 0.354537E+09 | 0.635227E+09 | 0.371206E+09 | 0.183035E+09 | 0.188171E+09 | 0.00 | 0.00 |
December | 0.225606E+09 | 0.884246E+09 | 0.326824E+09 | 0.144459E+09 | 0.182365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.939995E+10 | 0.462706E+10 | 0.610055E+10 | 0.281479E+10 | 0.328576E+10 | 0.00 | 0.00 |
Minimum of Months | 0.225606E+09 | 30473942.00 | 0.326824E+09 | 0.144459E+09 | 0.179438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140089E+10 | 0.884246E+09 | 0.679796E+09 | 0.316834E+09 | 0.366746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.829530E+09 | 0.102222E+10 | 0.742775E+09 | 0.491065E+09 | 0.251710E+09 | 0.00 | 0.00 |
February | 0.766921E+09 | 0.823517E+09 | 0.655180E+09 | 0.390575E+09 | 0.264605E+09 | 0.00 | 0.00 |
March | 0.772107E+09 | 0.797054E+09 | 0.628360E+09 | 0.270247E+09 | 0.358112E+09 | 0.00 | 0.00 |
April | 0.753081E+09 | 0.433418E+09 | 0.491746E+09 | 0.122910E+09 | 0.368836E+09 | 0.00 | 0.00 |
May | 0.829781E+09 | 0.234646E+09 | 0.443490E+09 | 49891063.49 | 0.393599E+09 | 0.00 | 0.00 |
June | 0.989554E+09 | 0.100660E+09 | 0.408907E+09 | 38910104.08 | 0.369997E+09 | 0.00 | 0.00 |
July | 0.987506E+09 | 73483612.14 | 0.408857E+09 | 38172500.78 | 0.370684E+09 | 0.00 | 0.00 |
August | 0.955147E+09 | 0.121805E+09 | 0.431139E+09 | 69810394.97 | 0.361328E+09 | 0.00 | 0.00 |
September | 0.103389E+10 | 0.281721E+09 | 0.541591E+09 | 0.206100E+09 | 0.335491E+09 | 0.00 | 0.00 |
October | 0.104343E+10 | 0.503545E+09 | 0.686584E+09 | 0.381942E+09 | 0.304642E+09 | 0.00 | 0.00 |
November | 0.915648E+09 | 0.846217E+09 | 0.751982E+09 | 0.500836E+09 | 0.251146E+09 | 0.00 | 0.00 |
December | 0.815806E+09 | 0.110072E+10 | 0.759297E+09 | 0.499852E+09 | 0.259445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106924E+11 | 0.633901E+10 | 0.694991E+10 | 0.306031E+10 | 0.388960E+10 | 0.00 | 0.00 |
Minimum of Months | 0.753081E+09 | 73483612.14 | 0.408857E+09 | 38172500.78 | 0.251146E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104343E+10 | 0.110072E+10 | 0.759297E+09 | 0.500836E+09 | 0.393599E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.760819E+09 | 0.805161E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.735514E+09 | 0.648068E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.922308E+09 | 0.619376E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.104824E+10 | 0.318051E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.122525E+10 | 0.153866E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.134791E+10 | 50498098.13 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.128515E+10 | 29675317.36 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.124455E+10 | 62238080.28 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.125993E+10 | 0.181296E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.112838E+10 | 0.375790E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.895694E+09 | 0.650724E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.728028E+09 | 0.873727E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.125818E+11 | 0.476847E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.728028E+09 | 29675317.36 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134791E+10 | 0.873727E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.320778E+09 | 0.846529E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.367910E+09 | 0.674189E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.626440E+09 | 0.623612E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.880164E+09 | 0.311344E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.118161E+10 | 0.147317E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.136177E+10 | 48907817.13 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.127742E+10 | 28660351.70 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.113840E+10 | 60006942.33 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.986074E+09 | 0.176763E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.712330E+09 | 0.370416E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.425000E+09 | 0.675669E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.284299E+09 | 0.931613E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.956219E+10 | 0.489503E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.284299E+09 | 28660351.70 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136177E+10 | 0.931613E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.713425E+09 | 0.424104E+09 | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.00 | 0.00 |
February | 0.620498E+09 | 0.338855E+09 | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.00 | 0.00 |
March | 0.551547E+09 | 0.321726E+09 | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.00 | 0.00 |
April | 0.446832E+09 | 0.161902E+09 | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.00 | 0.00 |
May | 0.403294E+09 | 74881139.47 | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.00 | 0.00 |
June | 0.444429E+09 | 23144141.52 | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.00 | 0.00 |
July | 0.459206E+09 | 13395788.82 | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.00 | 0.00 |
August | 0.512057E+09 | 29862912.39 | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.00 | 0.00 |
September | 0.653218E+09 | 89923212.11 | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.00 | 0.00 |
October | 0.760271E+09 | 0.193689E+09 | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.00 | 0.00 |
November | 0.766577E+09 | 0.338592E+09 | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.00 | 0.00 |
December | 0.720563E+09 | 0.457614E+09 | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.705192E+10 | 0.246769E+10 | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.403294E+09 | 13395788.82 | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.766577E+09 | 0.457614E+09 | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18797852.72 | 0.279677E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.109307E+09 | 0.219443E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.308443E+09 | 0.198430E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.747247E+09 | 0.101690E+10 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.139318E+10 | 0.534457E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.196464E+10 | 0.237261E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.186928E+10 | 0.186688E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.144379E+10 | 0.290657E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.101301E+10 | 0.623103E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.482257E+09 | 0.120194E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 71569684.66 | 0.221298E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 13831816.65 | 0.303823E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.943535E+10 | 0.163177E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 13831816.65 | 0.186688E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196464E+10 | 0.303823E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 13236277.75 | 0.288570E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 95718219.96 | 0.225895E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.282439E+09 | 0.203909E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.722374E+09 | 0.104667E+10 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.136717E+10 | 0.552593E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.193854E+10 | 0.247533E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.184262E+10 | 0.197314E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.141874E+10 | 0.304135E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.994400E+09 | 0.642933E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.462011E+09 | 0.123566E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 59350578.14 | 0.227740E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 9711224.88 | 0.313141E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.920631E+10 | 0.168194E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 9711224.88 | 0.197314E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193854E+10 | 0.313141E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.885205E+09 | 0.193388E+10 | 0.973364E+09 | 0.578542E+09 | 0.394822E+09 | 0.00 | 0.00 |
February | 0.112125E+10 | 0.153528E+10 | 0.103844E+10 | 0.601931E+09 | 0.436505E+09 | 0.00 | 0.00 |
March | 0.149514E+10 | 0.143336E+10 | 0.126377E+10 | 0.652149E+09 | 0.611620E+09 | 0.00 | 0.00 |
April | 0.205750E+10 | 0.790181E+09 | 0.133510E+10 | 0.654044E+09 | 0.681055E+09 | 0.00 | 0.00 |
May | 0.251420E+10 | 0.482218E+09 | 0.137582E+10 | 0.637186E+09 | 0.738635E+09 | 0.00 | 0.00 |
June | 0.288355E+10 | 0.242232E+09 | 0.132020E+10 | 0.625352E+09 | 0.694846E+09 | 0.00 | 0.00 |
July | 0.275720E+10 | 0.204923E+09 | 0.124132E+10 | 0.547666E+09 | 0.693659E+09 | 0.00 | 0.00 |
August | 0.256070E+10 | 0.282719E+09 | 0.120652E+10 | 0.530726E+09 | 0.675789E+09 | 0.00 | 0.00 |
September | 0.238123E+10 | 0.494490E+09 | 0.123206E+10 | 0.644030E+09 | 0.588031E+09 | 0.00 | 0.00 |
October | 0.173245E+10 | 0.912768E+09 | 0.112346E+10 | 0.612150E+09 | 0.511313E+09 | 0.00 | 0.00 |
November | 0.118457E+10 | 0.153788E+10 | 0.106411E+10 | 0.655039E+09 | 0.409076E+09 | 0.00 | 0.00 |
December | 0.848227E+09 | 0.205277E+10 | 0.983308E+09 | 0.577324E+09 | 0.405984E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224212E+11 | 0.119027E+11 | 0.141575E+11 | 0.731614E+10 | 0.684134E+10 | 0.00 | 0.00 |
Minimum of Months | 0.848227E+09 | 0.204923E+09 | 0.973364E+09 | 0.530726E+09 | 0.394822E+09 | 0.00 | 0.00 |
Maximum of Months | 0.288355E+10 | 0.205277E+10 | 0.137582E+10 | 0.655039E+09 | 0.738635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177308E+10 | 0.182405E+10 | 0.152718E+10 | 0.105785E+10 | 0.469332E+09 | 0.00 | 0.00 |
February | 0.160288E+10 | 0.146187E+10 | 0.133098E+10 | 0.841376E+09 | 0.489606E+09 | 0.00 | 0.00 |
March | 0.154222E+10 | 0.140884E+10 | 0.123709E+10 | 0.582162E+09 | 0.654925E+09 | 0.00 | 0.00 |
April | 0.139571E+10 | 0.784352E+09 | 0.928373E+09 | 0.263104E+09 | 0.665269E+09 | 0.00 | 0.00 |
May | 0.143396E+10 | 0.437192E+09 | 0.795528E+09 | 95695732.11 | 0.699832E+09 | 0.00 | 0.00 |
June | 0.167782E+10 | 0.192728E+09 | 0.716374E+09 | 63322576.03 | 0.653051E+09 | 0.00 | 0.00 |
July | 0.168052E+10 | 0.148557E+09 | 0.723725E+09 | 66827933.17 | 0.656897E+09 | 0.00 | 0.00 |
August | 0.169753E+10 | 0.235243E+09 | 0.795946E+09 | 0.147226E+09 | 0.648721E+09 | 0.00 | 0.00 |
September | 0.196946E+10 | 0.511372E+09 | 0.105488E+10 | 0.443840E+09 | 0.611036E+09 | 0.00 | 0.00 |
October | 0.209690E+10 | 0.890985E+09 | 0.138326E+10 | 0.822779E+09 | 0.560482E+09 | 0.00 | 0.00 |
November | 0.194885E+10 | 0.147633E+10 | 0.154509E+10 | 0.107890E+10 | 0.466191E+09 | 0.00 | 0.00 |
December | 0.176295E+10 | 0.195891E+10 | 0.156334E+10 | 0.107678E+10 | 0.486559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.205819E+11 | 0.113304E+11 | 0.136018E+11 | 0.653986E+10 | 0.706190E+10 | 0.00 | 0.00 |
Minimum of Months | 0.139571E+10 | 0.148557E+09 | 0.716374E+09 | 63322576.03 | 0.466191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.209690E+10 | 0.195891E+10 | 0.156334E+10 | 0.107890E+10 | 0.699832E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770414E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161360789.3 | 81.21 | 0.00 | 0.00 |
February | 0.696177E+10 | -0.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145816573.7 | 81.21 | 0.00 | 0.00 |
March | 0.770289E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161428304.0 | 81.21 | 0.00 | 0.00 |
April | 0.746479E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156209184.1 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161419382.1 | 81.21 | 0.00 | 0.00 |
June | 0.745673E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203707.2 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408682.7 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161409088.7 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156208760.0 | 81.21 | 0.00 | 0.00 |
October | 0.770292E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161481378.1 | 81.21 | 0.00 | 0.00 |
November | 0.744872E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156288452.8 | 81.21 | 0.00 | 0.00 |
December | 0.771224E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161396326.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907410E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190063E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696177E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161481378.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771226E+10 | -0.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145816573.7 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.113625E+12 | -0.111892E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173292E+10 | 81.25 | 0.00 | 0.00 |
February | 0.102582E+12 | -0.100997E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158488E+10 | 81.26 | 0.00 | 0.00 |
March | 0.110882E+12 | -0.109106E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177564E+10 | 81.26 | 0.00 | 0.00 |
April | 0.102680E+12 | -0.100964E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171641E+10 | 81.25 | 0.00 | 0.00 |
May | 0.100562E+12 | -0.987970E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176503E+10 | 81.25 | 0.00 | 0.00 |
June | 0.926632E+11 | -0.909638E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169939E+10 | 81.24 | 0.00 | 0.00 |
July | 0.929643E+11 | -0.912303E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173399E+10 | 81.24 | 0.00 | 0.00 |
August | 0.929814E+11 | -0.912536E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172790E+10 | 81.24 | 0.00 | 0.00 |
September | 0.926948E+11 | -0.910247E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167016E+10 | 81.24 | 0.00 | 0.00 |
October | 0.100608E+12 | -0.988823E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172573E+10 | 81.24 | 0.00 | 0.00 |
November | 0.102716E+12 | -0.101046E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167022E+10 | 81.25 | 0.00 | 0.00 |
December | 0.110895E+12 | -0.109168E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172694E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.121585E+13 | -0.119533E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205292E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.926632E+11 | -0.111892E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.177564E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.113625E+12 | -0.909638E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158488E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.654976E+11 | -0.640259E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147171E+10 | 58.98 | 0.00 | 0.00 |
February | 0.591402E+11 | -0.577838E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.135641E+10 | 58.98 | 0.00 | 0.00 |
March | 0.632120E+11 | -0.616813E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153070E+10 | 58.98 | 0.00 | 0.00 |
April | 0.571510E+11 | -0.556724E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147865E+10 | 58.98 | 0.00 | 0.00 |
May | 0.542793E+11 | -0.527631E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151620E+10 | 58.98 | 0.00 | 0.00 |
June | 0.485232E+11 | -0.470678E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145537E+10 | 58.98 | 0.00 | 0.00 |
July | 0.476771E+11 | -0.462039E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147328E+10 | 58.98 | 0.00 | 0.00 |
August | 0.477362E+11 | -0.462713E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146492E+10 | 58.98 | 0.00 | 0.00 |
September | 0.485136E+11 | -0.470987E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141493E+10 | 58.98 | 0.00 | 0.00 |
October | 0.542687E+11 | -0.528067E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146198E+10 | 58.98 | 0.00 | 0.00 |
November | 0.571370E+11 | -0.557220E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141501E+10 | 58.98 | 0.00 | 0.00 |
December | 0.631389E+11 | -0.616752E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146369E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.666275E+12 | -0.648772E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.175028E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.476771E+11 | -0.640259E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.153070E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.654976E+11 | -0.462039E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.135641E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.87 | 0.86 | 01-JAN-08:20 | 7927.13 | 38.53 | 274.50 | 280.33 | 1044.76 | 27.15 | 179.17 | 259.00 |
February | 268.33 | 0.87 | 0.86 | 01-FEB-07:49 | 6427.24 | 33.89 | 210.83 | 272.17 | 656.61 | 24.04 | 167.33 | 241.17 |
March | 351.83 | 0.88 | 0.86 | 01-MAR-07:10 | 1135.36 | 19.90 | 12.33 | 323.17 | 437.93 | 21.23 | 148.67 | 256.17 |
April | 373.83 | 0.88 | 0.86 | 01-APR-07:19 | 820.80 | 19.43 | 0.33 | 339.67 | 348.43 | 21.18 | 161.00 | 260.67 |
May | 408.83 | 0.88 | 0.86 | 01-MAY-07:19 | 686.59 | 19.07 | 0.00 | 364.17 | 296.17 | 20.82 | 134.83 | 266.50 |
June | 398.00 | 0.88 | 0.86 | 01-JUN-08:09 | 602.04 | 19.00 | 0.00 | 356.50 | 266.86 | 20.80 | 76.00 | 223.50 |
July | 400.17 | 0.88 | 0.86 | 01-JUL-08:09 | 659.82 | 18.87 | 0.00 | 362.50 | 282.78 | 20.64 | 116.83 | 217.67 |
August | 377.83 | 0.88 | 0.86 | 01-AUG-07:00 | 772.66 | 19.19 | 0.00 | 351.00 | 326.71 | 20.93 | 162.83 | 259.00 |
September | 365.83 | 0.88 | 0.86 | 01-SEP-09:39 | 887.54 | 19.30 | 0.33 | 321.17 | 375.39 | 21.09 | 153.33 | 240.67 |
October | 318.83 | 0.87 | 0.86 | 01-OCT-07:19 | 3201.31 | 26.33 | 125.67 | 314.33 | 513.35 | 22.14 | 150.50 | 279.33 |
November | 295.83 | 0.87 | 0.86 | 01-NOV-12:39 | 8202.96 | 37.69 | 288.50 | 289.67 | 800.11 | 26.02 | 160.17 | 270.67 |
December | 289.50 | 0.87 | 0.86 | 01-DEC-07:19 | 7147.65 | 38.04 | 284.67 | 278.33 | 1166.43 | 27.77 | 199.50 | 268.83 |
Annual Sum or Average | 4125.67 | 0.87 | 2797.86 | 24.68 | 1197.17 | 3853.00 | 506.35 | 22.50 | 1810.17 | 3043.17 | ||
Minimum of Months | 268.33 | 0.87 | 0.86 | 602.04 | 18.87 | 0.00 | 272.17 | 266.86 | 20.64 | 76.00 | 217.67 | |
Maximum of Months | 408.83 | 0.88 | 0.86 | 8202.96 | 38.53 | 288.50 | 364.17 | 1166.43 | 27.77 | 199.50 | 279.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.24 | 0.22 | 01-JAN-08:09 | 8370.79 | 38.58 | 274.50 | 287.17 | 1487.42 | 26.73 | 164.67 | 273.33 |
February | 268.33 | 0.25 | 0.22 | 01-FEB-07:49 | 6825.17 | 33.88 | 211.17 | 281.67 | 1054.06 | 23.76 | 150.17 | 260.50 |
March | 351.83 | 0.27 | 0.22 | 01-MAR-06:00 | 1414.38 | 20.17 | 32.83 | 337.50 | 716.34 | 21.36 | 163.67 | 308.33 |
April | 373.83 | 0.27 | 0.22 | 01-APR-06:49 | 1012.58 | 20.00 | 33.00 | 355.00 | 539.73 | 21.54 | 213.00 | 320.83 |
May | 408.83 | 0.28 | 0.22 | 01-MAY-06:19 | 827.26 | 19.84 | 2.33 | 377.50 | 436.44 | 21.37 | 287.00 | 348.67 |
June | 398.00 | 0.27 | 0.22 | 01-JUN-06:19 | 727.88 | 19.85 | 0.17 | 372.67 | 392.34 | 21.42 | 245.83 | 340.00 |
July | 400.17 | 0.28 | 0.22 | 01-JUL-06:30 | 787.61 | 19.70 | 1.00 | 381.50 | 410.18 | 21.24 | 228.00 | 337.17 |
August | 377.83 | 0.28 | 0.22 | 01-AUG-06:30 | 932.54 | 19.90 | 18.83 | 365.17 | 486.15 | 21.42 | 236.50 | 328.50 |
September | 365.83 | 0.28 | 0.22 | 01-SEP-07:19 | 1119.40 | 19.73 | 19.50 | 337.33 | 606.74 | 21.33 | 166.50 | 303.50 |
October | 318.83 | 0.26 | 0.22 | 01-OCT-06:00 | 3552.33 | 26.35 | 131.33 | 318.00 | 863.29 | 22.04 | 151.17 | 302.67 |
November | 295.83 | 0.25 | 0.22 | 01-NOV-12:39 | 8617.22 | 37.76 | 288.67 | 295.33 | 1214.76 | 25.60 | 138.67 | 283.00 |
December | 289.50 | 0.24 | 0.22 | 01-DEC-07:10 | 7575.86 | 38.11 | 284.67 | 283.83 | 1596.63 | 27.43 | 181.33 | 276.67 |
Annual Sum or Average | 4125.67 | 0.27 | 3055.24 | 25.11 | 1298.00 | 3992.67 | 763.42 | 22.67 | 2326.50 | 3683.17 | ||
Minimum of Months | 268.33 | 0.24 | 0.22 | 727.88 | 19.70 | 0.17 | 281.67 | 392.34 | 21.24 | 138.67 | 260.50 | |
Maximum of Months | 408.83 | 0.28 | 0.22 | 8617.22 | 38.58 | 288.67 | 381.50 | 1596.63 | 27.43 | 287.00 | 348.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.70 | 0.60 | 01-JAN-09:20 | 310.75 | 14.42 | 0.00 | 237.00 | 163.68 | 18.04 | 0.00 | 60.83 |
February | 268.33 | 0.68 | 0.60 | 02-FEB-09:20 | 351.77 | 15.09 | 0.00 | 244.33 | 183.37 | 18.60 | 0.00 | 96.83 |
March | 351.83 | 0.67 | 0.60 | 01-MAR-08:30 | 421.96 | 15.88 | 0.00 | 311.33 | 206.93 | 19.20 | 0.00 | 155.00 |
April | 373.83 | 0.64 | 0.60 | 01-APR-07:30 | 508.76 | 17.00 | 0.00 | 357.50 | 243.39 | 20.25 | 25.50 | 259.33 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 661.14 | 17.72 | 5.33 | 389.67 | 282.83 | 20.82 | 104.50 | 360.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-06:10 | 714.89 | 20.75 | 83.67 | 386.00 | 301.97 | 21.26 | 104.83 | 361.67 |
July | 400.17 | 0.62 | 0.60 | 01-JUL-05:49 | 682.57 | 18.95 | 39.33 | 398.17 | 321.64 | 21.78 | 106.83 | 346.67 |
August | 377.83 | 0.63 | 0.60 | 01-AUG-05:00 | 562.34 | 17.19 | 0.00 | 371.17 | 267.11 | 20.44 | 53.67 | 307.33 |
September | 365.83 | 0.67 | 0.60 | 01-SEP-14:30 | 415.37 | 16.19 | 0.00 | 325.00 | 209.62 | 19.49 | 1.50 | 157.00 |
October | 318.83 | 0.68 | 0.60 | 01-OCT-14:00 | 371.36 | 15.43 | 0.00 | 290.33 | 190.53 | 18.85 | 0.00 | 108.67 |
November | 295.83 | 0.71 | 0.60 | 01-NOV-13:20 | 296.96 | 14.45 | 0.00 | 250.17 | 157.66 | 18.04 | 0.00 | 47.33 |
December | 289.50 | 0.70 | 0.60 | 01-DEC-10:39 | 318.84 | 14.44 | 0.00 | 240.33 | 165.80 | 18.03 | 0.00 | 61.00 |
Annual Sum or Average | 4125.67 | 0.66 | 487.20 | 16.69 | 128.33 | 3801.00 | 231.68 | 19.73 | 396.83 | 2322.00 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 296.96 | 14.42 | 0.00 | 237.00 | 157.66 | 18.03 | 0.00 | 47.33 | |
Maximum of Months | 408.83 | 0.71 | 0.60 | 714.89 | 20.75 | 83.67 | 398.17 | 321.64 | 21.78 | 106.83 | 361.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.70 | 0.60 | 01-JAN-09:20 | 310.75 | 14.42 | 0.00 | 237.00 | 163.68 | 18.04 | 0.00 | 60.83 |
February | 268.33 | 0.68 | 0.60 | 02-FEB-09:20 | 351.77 | 15.09 | 0.00 | 244.33 | 183.37 | 18.60 | 0.00 | 96.83 |
March | 351.83 | 0.67 | 0.60 | 01-MAR-08:30 | 421.96 | 15.88 | 0.00 | 311.33 | 206.93 | 19.20 | 0.00 | 155.00 |
April | 373.83 | 0.64 | 0.60 | 01-APR-07:30 | 508.76 | 17.00 | 0.00 | 357.50 | 243.39 | 20.25 | 25.50 | 259.33 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 661.14 | 17.72 | 5.33 | 389.67 | 282.83 | 20.82 | 104.50 | 360.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-06:10 | 714.89 | 20.75 | 83.67 | 386.00 | 301.97 | 21.26 | 104.83 | 361.67 |
July | 400.17 | 0.62 | 0.60 | 01-JUL-05:49 | 682.57 | 18.95 | 39.33 | 398.17 | 321.64 | 21.78 | 106.83 | 346.67 |
August | 377.83 | 0.63 | 0.60 | 01-AUG-05:00 | 562.34 | 17.19 | 0.00 | 371.17 | 267.11 | 20.44 | 53.67 | 307.33 |
September | 365.83 | 0.67 | 0.60 | 01-SEP-14:30 | 415.37 | 16.19 | 0.00 | 325.00 | 209.62 | 19.49 | 1.50 | 157.00 |
October | 318.83 | 0.68 | 0.60 | 01-OCT-14:00 | 371.36 | 15.43 | 0.00 | 290.33 | 190.53 | 18.85 | 0.00 | 108.67 |
November | 295.83 | 0.71 | 0.60 | 01-NOV-13:20 | 296.96 | 14.45 | 0.00 | 250.17 | 157.66 | 18.04 | 0.00 | 47.33 |
December | 289.50 | 0.70 | 0.60 | 01-DEC-10:39 | 318.84 | 14.44 | 0.00 | 240.33 | 165.80 | 18.03 | 0.00 | 61.00 |
Annual Sum or Average | 4125.67 | 0.66 | 487.20 | 16.69 | 128.33 | 3801.00 | 231.68 | 19.73 | 396.83 | 2322.00 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 296.96 | 14.42 | 0.00 | 237.00 | 157.66 | 18.03 | 0.00 | 47.33 | |
Maximum of Months | 408.83 | 0.71 | 0.60 | 714.89 | 20.75 | 83.67 | 398.17 | 321.64 | 21.78 | 106.83 | 361.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.317270E+11 | 129836.71 | 23-JAN-02:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208251E+11 | 131689.76 | 24-FEB-03:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186031E+11 | 125769.99 | 26-MAR-03:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.620577E+10 | 121596.56 | 11-APR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.471719E+09 | 69348.27 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247863E+09 | 72610.99 | 30-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358084E+10 | 90021.30 | 25-OCT-06:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222688E+11 | 130076.55 | 11-NOV-04:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280210E+11 | 134149.84 | 04-DEC-22:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317270E+11 | 134149.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.483176E+09 | 2380.65 | 14-JAN-13:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292682E+09 | 1405.04 | 21-FEB-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216071E+09 | 2165.01 | 13-MAR-05:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22893123.70 | 1702.74 | 13-APR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 107534.10 | 281.99 | 02-MAY-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1874581.00 | 951.43 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246462E+09 | 2381.75 | 27-NOV-08:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.661126E+09 | 1859.03 | 01-DEC-02:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.661126E+09 | 2381.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16822778.38 | 1026.73 | 28-JAN-09:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9188394.33 | 636.26 | 03-FEB-11:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2617998.55 | 421.72 | 02-MAR-13:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7597853.47 | 432.72 | 28-NOV-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82607674.55 | 1397.43 | 30-DEC-10:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82607674.55 | 1397.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 77827538.80 | 823.27 | 28-JAN-09:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49470416.18 | 842.75 | 10-FEB-10:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14166768.09 | 458.89 | 02-MAR-10:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27577441.04 | 945.97 | 27-NOV-08:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184806E+09 | 944.97 | 30-DEC-10:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184806E+09 | 945.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29746174.96 | 6720.04 | 13-JAN-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20815725.89 | 7538.30 | 21-FEB-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39388585.83 | 7499.48 | 25-MAR-01:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21048346.03 | 7501.10 | 11-APR-01:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 936015.94 | 3120.05 | 02-MAY-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18711275.69 | 7200.65 | 11-OCT-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44018751.91 | 7438.93 | 25-NOV-02:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12927523.68 | 7514.15 | 01-DEC-02:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44018751.91 | 7538.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29977075.71 | 2871.70 | 17-JAN-10:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7918876.07 | 1140.00 | 13-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 284505.40 | 427.63 | 24-MAR-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30454766.46 | 3330.54 | 27-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38933895.02 | 2601.09 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38933895.02 | 3330.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.520780E+09 | 7809.66 | 17-JAN-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78768448.02 | 3367.25 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43036045.60 | 2573.33 | 02-MAR-10:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190101E+09 | 4200.59 | 28-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103461E+10 | 9045.85 | 02-DEC-18:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103461E+10 | 9045.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.888344E+09 | 5126.60 | 25-JAN-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425228E+09 | 3069.71 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177678E+09 | 2651.37 | 03-MAR-07:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 328397.53 | 243.76 | 01-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338344E+09 | 5679.31 | 27-NOV-08:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147823E+10 | 5134.99 | 02-DEC-18:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147823E+10 | 5679.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 572204.52 | 1907.35 | 25-MAR-02:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 223790.27 | 720.05 | 25-NOV-02:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 795994.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 572204.52 | 1907.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43645977.91 | 2290.96 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64573998.73 | 2808.29 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29725148.62 | 2295.90 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39732.54 | 0.51 | 19-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84118.23 | 0.50 | 27-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57314.27 | 0.51 | 17-JUN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30402.37 | 0.51 | 12-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32779.23 | 0.51 | 08-AUG-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43576.14 | 0.51 | 18-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26947.49 | 0.51 | 09-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3068200.31 | 544.56 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178729E+09 | 3218.10 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 26947.49 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178729E+09 | 3218.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157099E+10 | 5850.37 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.950965E+09 | 5801.35 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486719E+09 | 5840.76 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45001662.65 | 5075.28 | 02-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5604327.42 | 4672.14 | 10-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2211346.91 | 3358.71 | 04-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2603392.90 | 3586.44 | 28-JUL-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3962034.47 | 3515.83 | 17-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4508341.85 | 3354.82 | 24-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9008780.74 | 4060.08 | 17-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709081E+09 | 5855.50 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207685E+10 | 5904.28 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2211346.91 | 3354.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207685E+10 | 5904.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255697E+10 | 5891.61 | 26-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156368E+10 | 5891.35 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.754376E+09 | 5888.50 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63194608.06 | 5661.64 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5657565.56 | 4630.17 | 10-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2723428.72 | 3750.02 | 04-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2008816.49 | 2483.20 | 14-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4291623.07 | 4070.38 | 17-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5120818.24 | 4548.05 | 29-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19933540.09 | 5069.78 | 31-OCT-19:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117944E+10 | 5891.30 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326912E+10 | 5892.51 | 04-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.942651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2008816.49 | 2483.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326912E+10 | 5892.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.700583E+10 | 34035.51 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395308E+10 | 33938.82 | 02-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140206E+10 | 33542.50 | 02-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153688E+09 | 32842.72 | 18-APR-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81946173.40 | 32827.55 | 04-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19505528.75 | 29481.77 | 13-JUN-08:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23715702.40 | 20224.83 | 21-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 52710233.68 | 26857.70 | 24-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69773325.59 | 30183.27 | 30-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102978E+09 | 32814.73 | 27-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288144E+10 | 33778.85 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100638E+11 | 34173.41 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 19505528.75 | 20224.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100638E+11 | 34173.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166049E+10 | 5716.97 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.909819E+09 | 5597.65 | 13-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.522788E+09 | 5614.86 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48766510.86 | 4847.47 | 06-APR-18:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3020141.55 | 3859.67 | 06-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 209695.59 | 948.18 | 22-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 565186.71 | 2024.16 | 19-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1605118.09 | 3026.93 | 24-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1184780.23 | 2489.01 | 28-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17622167.14 | 3503.56 | 09-OCT-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780382E+09 | 5699.83 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211411E+10 | 5752.42 | 26-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.606056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 209695.59 | 948.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.211411E+10 | 5752.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261079E+10 | 5724.90 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142771E+10 | 5672.00 | 02-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765253E+09 | 5659.13 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68674487.34 | 4697.62 | 11-APR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3309098.82 | 3880.17 | 07-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 176472.50 | 1414.94 | 19-JUN-18:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 541987.44 | 2090.09 | 19-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1874263.95 | 2943.48 | 24-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1872863.76 | 2134.58 | 02-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44279309.27 | 4882.22 | 30-OCT-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123608E+10 | 5738.38 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323208E+10 | 5739.53 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.939264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 176472.50 | 1414.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323208E+10 | 5739.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.666875E+09 | 1762.35 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431103E+09 | 1761.34 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254975E+09 | 1761.30 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36514497.68 | 1716.23 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2081380.07 | 1311.09 | 11-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 534814.89 | 813.38 | 10-JUN-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 822084.33 | 906.68 | 04-JUL-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1078195.52 | 1078.32 | 17-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1276276.38 | 1065.14 | 27-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15201551.62 | 1161.92 | 18-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345233E+09 | 1761.75 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840295E+09 | 1761.91 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 534814.89 | 813.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.840295E+09 | 1762.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.995240E+09 | 1758.99 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644309E+09 | 1758.34 | 17-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.358867E+09 | 1758.23 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46577674.27 | 1717.90 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2134080.07 | 1315.67 | 11-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 466626.38 | 784.23 | 04-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 683099.99 | 863.95 | 12-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1137399.51 | 1166.69 | 30-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1677667.26 | 1113.43 | 12-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30406110.34 | 1697.73 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.546161E+09 | 1758.39 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122105E+10 | 1758.56 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 466626.38 | 784.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122105E+10 | 1758.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116405E+10 | 8266.59 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729253E+09 | 8060.16 | 13-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510502E+09 | 8154.74 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96265461.30 | 7309.29 | 06-APR-18:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11555237.74 | 6992.73 | 04-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3430539.80 | 4823.43 | 23-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3848357.64 | 4930.23 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4834717.69 | 4720.02 | 10-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3124470.42 | 4542.22 | 02-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10136696.82 | 4079.48 | 07-OCT-20:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.630552E+09 | 8191.93 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159594E+10 | 8328.15 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3124470.42 | 4079.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159594E+10 | 8328.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.670646E+10 | 0.670646E+10 | 89112.50 | 03-JAN-17:00 | 89112.50 | 0.00 |
February | 0.00 | 0.00 | 0.328647E+11 | 0.328647E+11 | 124107.99 | 21-FEB-16:14 | 124107.99 | 0.00 |
March | 0.00 | 0.00 | 0.669157E+11 | 0.669157E+11 | 160199.08 | 14-MAR-18:20 | 160199.08 | 0.00 |
April | 0.00 | 0.00 | 0.210684E+12 | 0.210684E+12 | 230788.60 | 19-APR-21:00 | 230788.60 | 0.10 |
May | 0.00 | 0.00 | 0.350048E+12 | 0.348354E+12 | 256095.91 | 19-MAY-20:10 | 256095.91 | 0.38 |
June | 0.00 | 0.00 | 0.455412E+12 | 0.450111E+12 | 301404.06 | 19-JUN-18:20 | 212533.40 | 0.69 |
July | 0.00 | 0.00 | 0.608638E+12 | 0.472381E+12 | 462494.73 | 18-JUL-20:45 | 157202.52 | 1.00 |
August | 0.00 | 0.00 | 0.494963E+12 | 0.441397E+12 | 459333.72 | 01-AUG-20:50 | 214374.95 | 0.98 |
September | 0.00 | 0.00 | 0.403396E+12 | 0.346353E+12 | 341060.45 | 09-SEP-20:00 | 187708.86 | 0.85 |
October | 0.00 | 0.00 | 0.198517E+12 | 0.189811E+12 | 389083.32 | 03-OCT-19:55 | 212067.18 | 0.45 |
November | 0.00 | 0.00 | 0.409353E+11 | 0.409353E+11 | 149023.86 | 03-NOV-15:45 | 149023.86 | 0.04 |
December | 0.00 | 0.00 | 0.410164E+10 | 0.410164E+10 | 58732.09 | 19-DEC-22:10 | 58732.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.287318E+13 | 0.261061E+13 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.410164E+10 | 0.410164E+10 | 58732.09 | 58732.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.608638E+12 | 0.472381E+12 | 462494.73 | 256095.91 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122869E+10 | 0.122869E+10 | 18651.05 | 03-JAN-15:00 | 18651.05 | 0.00 |
February | 0.00 | 0.00 | 0.619310E+10 | 0.619310E+10 | 23708.25 | 20-FEB-16:28 | 23708.25 | 0.00 |
March | 0.00 | 0.00 | 0.122686E+11 | 0.122686E+11 | 24845.34 | 22-MAR-16:30 | 24845.34 | 0.00 |
April | 0.00 | 0.00 | 0.349245E+11 | 0.349245E+11 | 29749.47 | 21-APR-15:00 | 29749.47 | 0.09 |
May | 0.00 | 0.00 | 0.560482E+11 | 0.548594E+11 | 35949.88 | 27-MAY-21:20 | 24923.80 | 0.29 |
June | 0.00 | 0.00 | 0.684145E+11 | 0.659318E+11 | 41761.79 | 27-JUN-24:00 | 20529.80 | 0.59 |
July | 0.00 | 0.00 | 0.926654E+11 | 0.690670E+11 | 57668.34 | 21-JUL-08:00 | 19753.78 | 1.00 |
August | 0.00 | 0.00 | 0.773791E+11 | 0.651902E+11 | 52523.34 | 03-AUG-07:00 | 23598.40 | 0.95 |
September | 0.00 | 0.00 | 0.662244E+11 | 0.524076E+11 | 50715.99 | 22-SEP-08:65 | 23664.47 | 0.84 |
October | 0.00 | 0.00 | 0.334833E+11 | 0.306253E+11 | 47393.11 | 03-OCT-20:05 | 24110.11 | 0.43 |
November | 0.00 | 0.00 | 0.751668E+10 | 0.751668E+10 | 24834.53 | 03-NOV-16:00 | 24834.53 | 0.03 |
December | 0.00 | 0.00 | 0.724489E+09 | 0.724489E+09 | 11238.20 | 10-DEC-15:00 | 11238.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.457071E+12 | 0.400937E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.724489E+09 | 0.724489E+09 | 11238.20 | 11238.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.926654E+11 | 0.690670E+11 | 57668.34 | 29749.47 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.560329E+09 | 0.548153E+09 | 16319.15 | 01-JAN-16:02 | 16319.15 | 0.01 |
February | 0.00 | 0.00 | 0.749985E+09 | 0.738841E+09 | 16530.95 | 20-FEB-21:11 | 16530.95 | 0.01 |
March | 0.00 | 0.00 | 0.134487E+10 | 0.132194E+10 | 16641.21 | 26-MAR-20:11 | 16641.21 | 0.02 |
April | 0.00 | 0.00 | 0.446552E+10 | 0.410249E+10 | 17826.34 | 06-APR-18:11 | 17826.34 | 0.14 |
May | 0.00 | 0.00 | 0.763766E+10 | 0.633740E+10 | 17875.25 | 23-MAY-21:51 | 15020.15 | 0.37 |
June | 0.00 | 0.00 | 0.101100E+11 | 0.781275E+10 | 17533.36 | 04-JUN-08:51 | 14824.76 | 0.63 |
July | 0.00 | 0.00 | 0.108604E+11 | 0.688900E+10 | 20437.43 | 21-JUL-08:51 | 12485.48 | 0.85 |
August | 0.00 | 0.00 | 0.978554E+10 | 0.635468E+10 | 19440.00 | 14-AUG-21:51 | 14004.90 | 0.81 |
September | 0.00 | 0.00 | 0.859540E+10 | 0.558154E+10 | 19725.56 | 03-SEP-21:51 | 13840.34 | 0.73 |
October | 0.00 | 0.00 | 0.485031E+10 | 0.307566E+10 | 18891.84 | 03-OCT-21:51 | 13858.36 | 0.54 |
November | 0.00 | 0.00 | 0.165033E+10 | 0.144981E+10 | 16395.55 | 09-NOV-09:51 | 16395.55 | 0.09 |
December | 0.00 | 0.00 | 0.310252E+09 | 0.309970E+09 | 16289.67 | 07-DEC-16:01 | 16289.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.609206E+11 | 0.445222E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.310252E+09 | 0.309970E+09 | 16289.67 | 12485.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108604E+11 | 0.781275E+10 | 20437.43 | 17826.34 | 0.85 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 99006641.34 | 98770899.67 | 15854.38 | 12-JAN-16:01 | 15854.38 | 0.00 |
February | 0.00 | 0.00 | 0.181452E+09 | 0.179582E+09 | 16185.09 | 18-FEB-16:01 | 16185.09 | 0.00 |
March | 0.00 | 0.00 | 0.676113E+09 | 0.659645E+09 | 16188.09 | 12-MAR-15:01 | 16188.09 | 0.01 |
April | 0.00 | 0.00 | 0.379530E+10 | 0.346584E+10 | 17517.17 | 06-APR-18:11 | 17517.17 | 0.13 |
May | 0.00 | 0.00 | 0.743544E+10 | 0.615594E+10 | 17779.36 | 23-MAY-21:51 | 14932.37 | 0.37 |
June | 0.00 | 0.00 | 0.101497E+11 | 0.788166E+10 | 17564.85 | 16-JUN-07:21 | 17564.85 | 0.63 |
July | 0.00 | 0.00 | 0.107885E+11 | 0.687558E+10 | 20378.74 | 21-JUL-08:51 | 12463.15 | 0.84 |
August | 0.00 | 0.00 | 0.921687E+10 | 0.588892E+10 | 19266.61 | 14-AUG-21:51 | 13877.83 | 0.80 |
September | 0.00 | 0.00 | 0.721938E+10 | 0.437877E+10 | 19448.42 | 03-SEP-21:51 | 13538.39 | 0.71 |
October | 0.00 | 0.00 | 0.320196E+10 | 0.182298E+10 | 18556.97 | 03-OCT-21:51 | 13480.13 | 0.47 |
November | 0.00 | 0.00 | 0.441583E+09 | 0.340254E+09 | 16212.36 | 09-NOV-16:01 | 16212.36 | 0.06 |
December | 0.00 | 0.00 | 36708287.70 | 36690601.74 | 15582.29 | 16-DEC-16:01 | 15582.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.532420E+11 | 0.377846E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 36708287.70 | 36690601.74 | 15582.29 | 12463.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107885E+11 | 0.788166E+10 | 20378.74 | 17564.85 | 0.84 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137093E+11 | 0.137093E+11 | 34565.92 | 12-JAN-14:30 | 34565.92 | 0.00 |
February | 0.00 | 0.00 | 0.128567E+11 | 0.128567E+11 | 32356.28 | 07-FEB-13:40 | 32356.28 | 0.00 |
March | 0.00 | 0.00 | 0.928705E+10 | 0.924436E+10 | 24145.40 | 16-MAR-12:50 | 24145.40 | 0.01 |
April | 0.00 | 0.00 | 0.158417E+11 | 0.149489E+11 | 23014.31 | 04-APR-13:30 | 23014.31 | 0.06 |
May | 0.00 | 0.00 | 0.213545E+11 | 0.169716E+11 | 22722.27 | 19-MAY-20:20 | 14995.67 | 0.24 |
June | 0.00 | 0.00 | 0.311081E+11 | 0.210525E+11 | 26112.38 | 15-JUN-20:20 | 26112.38 | 0.55 |
July | 0.00 | 0.00 | 0.360065E+11 | 0.142582E+11 | 28079.29 | 26-JUL-17:20 | 16871.20 | 0.97 |
August | 0.00 | 0.00 | 0.355999E+11 | 0.167249E+11 | 28842.60 | 29-AUG-13:10 | 17100.36 | 0.89 |
September | 0.00 | 0.00 | 0.403645E+11 | 0.233232E+11 | 38342.18 | 20-SEP-12:40 | 31803.35 | 0.81 |
October | 0.00 | 0.00 | 0.343680E+11 | 0.264270E+11 | 43907.43 | 18-OCT-13:20 | 40196.02 | 0.42 |
November | 0.00 | 0.00 | 0.233955E+11 | 0.227352E+11 | 38181.46 | 09-NOV-13:50 | 38181.46 | 0.04 |
December | 0.00 | 0.00 | 0.107504E+11 | 0.107504E+11 | 29524.91 | 16-DEC-13:40 | 29524.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.284642E+12 | 0.203002E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.928705E+10 | 0.924436E+10 | 22722.27 | 14995.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.403645E+11 | 0.264270E+11 | 43907.43 | 40196.02 | 0.97 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.176301E+10 | 0.161315E+10 | 97437.52 | 01-JAN-09:01 | 97437.52 | 0.03 |
February | 0.00 | 0.00 | 0.379246E+10 | 0.340924E+10 | 103920.96 | 22-FEB-22:01 | 103920.96 | 0.04 |
March | 0.00 | 0.00 | 0.858814E+10 | 0.821001E+10 | 105891.62 | 15-MAR-21:51 | 105891.62 | 0.03 |
April | 0.00 | 0.00 | 0.250270E+11 | 0.230815E+11 | 108777.94 | 05-APR-21:51 | 108777.94 | 0.10 |
May | 0.00 | 0.00 | 0.443263E+11 | 0.367029E+11 | 113766.52 | 23-MAY-21:51 | 96418.65 | 0.29 |
June | 0.00 | 0.00 | 0.600724E+11 | 0.465879E+11 | 110332.81 | 11-JUN-08:31 | 110332.81 | 0.51 |
July | 0.00 | 0.00 | 0.668446E+11 | 0.421883E+11 | 130230.57 | 20-JUL-21:51 | 84220.65 | 0.71 |
August | 0.00 | 0.00 | 0.559279E+11 | 0.351378E+11 | 125601.48 | 16-AUG-21:51 | 86227.68 | 0.64 |
September | 0.00 | 0.00 | 0.418242E+11 | 0.257478E+11 | 126445.89 | 23-SEP-21:51 | 88128.01 | 0.52 |
October | 0.00 | 0.00 | 0.238960E+11 | 0.135137E+11 | 122516.86 | 03-OCT-21:51 | 88730.33 | 0.42 |
November | 0.00 | 0.00 | 0.513867E+10 | 0.393546E+10 | 103458.53 | 08-NOV-22:51 | 103458.53 | 0.11 |
December | 0.00 | 0.00 | 0.116270E+10 | 0.113541E+10 | 98322.46 | 09-DEC-09:01 | 98322.46 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.338363E+12 | 0.241263E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.116270E+10 | 0.113541E+10 | 97437.52 | 84220.65 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.668446E+11 | 0.465879E+11 | 130230.57 | 110332.81 | 0.71 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.543289E+09 | 0.508691E+09 | 14347.72 | 12-JAN-16:01 | 14347.72 | 0.02 |
February | 0.00 | 0.00 | 0.992924E+09 | 0.962479E+09 | 14391.67 | 18-FEB-09:01 | 14391.67 | 0.02 |
March | 0.00 | 0.00 | 0.161407E+10 | 0.159026E+10 | 14387.41 | 08-MAR-09:01 | 14387.41 | 0.02 |
April | 0.00 | 0.00 | 0.473065E+10 | 0.436084E+10 | 16657.06 | 27-APR-08:51 | 16657.06 | 0.15 |
May | 0.00 | 0.00 | 0.758588E+10 | 0.630241E+10 | 16657.44 | 16-MAY-08:51 | 16657.44 | 0.39 |
June | 0.00 | 0.00 | 0.102068E+11 | 0.792088E+10 | 16657.46 | 02-JUN-08:11 | 16657.46 | 0.65 |
July | 0.00 | 0.00 | 0.109934E+11 | 0.701564E+10 | 19092.19 | 21-JUL-08:51 | 12742.88 | 0.86 |
August | 0.00 | 0.00 | 0.985807E+10 | 0.638798E+10 | 17916.92 | 03-AUG-08:61 | 13765.95 | 0.83 |
September | 0.00 | 0.00 | 0.846737E+10 | 0.544440E+10 | 17690.51 | 14-SEP-08:51 | 13910.63 | 0.75 |
October | 0.00 | 0.00 | 0.466477E+10 | 0.303689E+10 | 16730.51 | 03-OCT-21:51 | 12223.04 | 0.54 |
November | 0.00 | 0.00 | 0.160886E+10 | 0.145199E+10 | 16323.87 | 09-NOV-09:51 | 16323.87 | 0.08 |
December | 0.00 | 0.00 | 0.405158E+09 | 0.399554E+09 | 14387.13 | 09-DEC-09:01 | 14387.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.616711E+11 | 0.453820E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.405158E+09 | 0.399554E+09 | 14347.72 | 12223.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109934E+11 | 0.792088E+10 | 19092.19 | 16657.46 | 0.86 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 63742529.00 | 55951419.20 | 10500.17 | 04-JAN-09:02 | 10500.17 | 0.01 |
February | 0.00 | 0.00 | 0.349602E+09 | 0.326560E+09 | 14280.75 | 19-FEB-09:01 | 14280.75 | 0.01 |
March | 0.00 | 0.00 | 0.904411E+09 | 0.888315E+09 | 14278.64 | 05-MAR-09:01 | 14278.64 | 0.02 |
April | 0.00 | 0.00 | 0.400027E+10 | 0.366370E+10 | 16532.76 | 27-APR-08:51 | 16532.76 | 0.14 |
May | 0.00 | 0.00 | 0.736627E+10 | 0.609428E+10 | 16533.81 | 16-MAY-08:51 | 16533.81 | 0.39 |
June | 0.00 | 0.00 | 0.102431E+11 | 0.797042E+10 | 16533.69 | 02-JUN-08:11 | 16533.69 | 0.65 |
July | 0.00 | 0.00 | 0.109169E+11 | 0.696915E+10 | 19008.17 | 21-JUL-08:51 | 12684.82 | 0.86 |
August | 0.00 | 0.00 | 0.928072E+10 | 0.587987E+10 | 17784.78 | 03-AUG-08:61 | 13662.87 | 0.83 |
September | 0.00 | 0.00 | 0.707926E+10 | 0.428536E+10 | 17590.93 | 09-SEP-08:51 | 13781.05 | 0.74 |
October | 0.00 | 0.00 | 0.298246E+10 | 0.178810E+10 | 16386.23 | 03-OCT-21:51 | 11908.65 | 0.46 |
November | 0.00 | 0.00 | 0.509762E+09 | 0.430665E+09 | 15037.26 | 09-NOV-09:51 | 15037.26 | 0.05 |
December | 0.00 | 0.00 | 42924760.51 | 40951691.63 | 13554.34 | 09-DEC-09:01 | 13554.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.537395E+11 | 0.383933E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 42924760.51 | 40951691.63 | 10500.17 | 10500.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109169E+11 | 0.797042E+10 | 19008.17 | 16533.81 | 0.86 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113910E+09 | 0.112436E+09 | 4329.98 | 01-JAN-16:02 | 4329.98 | 0.01 |
February | 0.00 | 0.00 | 0.155849E+09 | 0.154289E+09 | 4390.82 | 20-FEB-21:11 | 4390.82 | 0.01 |
March | 0.00 | 0.00 | 0.284037E+09 | 0.280903E+09 | 4509.97 | 13-MAR-19:41 | 4509.97 | 0.01 |
April | 0.00 | 0.00 | 0.109916E+10 | 0.101154E+10 | 4775.56 | 06-APR-18:11 | 4775.56 | 0.14 |
May | 0.00 | 0.00 | 0.192744E+10 | 0.158766E+10 | 4768.76 | 23-MAY-21:51 | 3943.49 | 0.37 |
June | 0.00 | 0.00 | 0.264037E+10 | 0.203742E+10 | 4771.58 | 04-JUN-08:51 | 3855.55 | 0.64 |
July | 0.00 | 0.00 | 0.283697E+10 | 0.180242E+10 | 5581.40 | 21-JUL-08:51 | 3207.56 | 0.85 |
August | 0.00 | 0.00 | 0.252336E+10 | 0.163191E+10 | 5253.82 | 14-AUG-21:51 | 3678.53 | 0.81 |
September | 0.00 | 0.00 | 0.215422E+10 | 0.139456E+10 | 5303.50 | 03-SEP-21:51 | 3595.05 | 0.73 |
October | 0.00 | 0.00 | 0.110938E+10 | 0.709532E+09 | 5078.77 | 03-OCT-21:51 | 3580.34 | 0.49 |
November | 0.00 | 0.00 | 0.321484E+09 | 0.283777E+09 | 4330.11 | 09-NOV-16:01 | 4330.11 | 0.07 |
December | 0.00 | 0.00 | 63719756.54 | 63639779.82 | 4327.75 | 04-DEC-16:01 | 4327.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152299E+11 | 0.110701E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 63719756.54 | 63639779.82 | 4327.75 | 3207.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.283697E+10 | 0.203742E+10 | 5581.40 | 4775.56 | 0.85 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 16874195.62 | 16809232.59 | 4206.35 | 12-JAN-16:01 | 4206.35 | 0.00 |
February | 0.00 | 0.00 | 29872416.16 | 29709805.07 | 4290.24 | 18-FEB-16:01 | 4290.24 | 0.00 |
March | 0.00 | 0.00 | 0.128684E+09 | 0.126876E+09 | 4291.01 | 04-MAR-16:01 | 4291.01 | 0.01 |
April | 0.00 | 0.00 | 0.924381E+09 | 0.846182E+09 | 4670.15 | 06-APR-18:11 | 4670.15 | 0.13 |
May | 0.00 | 0.00 | 0.187422E+10 | 0.153954E+10 | 4740.69 | 23-MAY-21:51 | 3917.94 | 0.37 |
June | 0.00 | 0.00 | 0.265217E+10 | 0.205469E+10 | 4742.59 | 04-JUN-08:51 | 3853.99 | 0.64 |
July | 0.00 | 0.00 | 0.281880E+10 | 0.179400E+10 | 5555.95 | 21-JUL-08:51 | 3206.86 | 0.85 |
August | 0.00 | 0.00 | 0.237432E+10 | 0.150449E+10 | 5202.05 | 14-AUG-21:51 | 3639.54 | 0.81 |
September | 0.00 | 0.00 | 0.178937E+10 | 0.107613E+10 | 5230.80 | 03-SEP-21:51 | 3502.51 | 0.71 |
October | 0.00 | 0.00 | 0.679076E+09 | 0.393533E+09 | 4988.48 | 03-OCT-21:51 | 3465.43 | 0.40 |
November | 0.00 | 0.00 | 65753005.21 | 49565470.41 | 4297.48 | 09-NOV-16:01 | 4297.48 | 0.04 |
December | 0.00 | 0.00 | 5888024.03 | 5888024.03 | 4082.15 | 16-DEC-16:01 | 4082.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133594E+11 | 0.943741E+10 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 5888024.03 | 5888024.03 | 4082.15 | 3206.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.281880E+10 | 0.205469E+10 | 5555.95 | 4670.15 | 0.85 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.387039E+10 | 0.372700E+10 | 20510.67 | 12-JAN-19:41 | 20510.67 | 0.06 |
February | 0.00 | 0.00 | 0.359774E+10 | 0.352918E+10 | 20820.91 | 20-FEB-21:11 | 20820.91 | 0.04 |
March | 0.00 | 0.00 | 0.315157E+10 | 0.309770E+10 | 20590.05 | 14-MAR-21:01 | 20590.05 | 0.02 |
April | 0.00 | 0.00 | 0.571051E+10 | 0.517675E+10 | 20216.32 | 02-APR-21:51 | 20216.32 | 0.16 |
May | 0.00 | 0.00 | 0.814451E+10 | 0.639706E+10 | 20952.47 | 23-MAY-21:51 | 17412.33 | 0.40 |
June | 0.00 | 0.00 | 0.112095E+11 | 0.819275E+10 | 21021.27 | 19-JUN-18:51 | 18477.84 | 0.64 |
July | 0.00 | 0.00 | 0.128209E+11 | 0.764077E+10 | 24502.32 | 20-JUL-21:51 | 14933.11 | 0.83 |
August | 0.00 | 0.00 | 0.122860E+11 | 0.769340E+10 | 23351.30 | 14-AUG-21:51 | 16762.23 | 0.81 |
September | 0.00 | 0.00 | 0.121552E+11 | 0.811722E+10 | 23901.85 | 03-SEP-21:51 | 16500.36 | 0.74 |
October | 0.00 | 0.00 | 0.920019E+10 | 0.661310E+10 | 23436.62 | 03-OCT-21:51 | 16814.24 | 0.59 |
November | 0.00 | 0.00 | 0.571492E+10 | 0.536394E+10 | 21974.04 | 09-NOV-09:51 | 21974.04 | 0.12 |
December | 0.00 | 0.00 | 0.350382E+10 | 0.347401E+10 | 20396.66 | 07-DEC-17:01 | 20396.66 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.913653E+11 | 0.690229E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.315157E+10 | 0.309770E+10 | 20216.32 | 14933.11 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.128209E+11 | 0.819275E+10 | 24502.32 | 21974.04 | 0.83 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 19203.23 | 149205.86 | 18-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13218.90 | 128509.30 | 01-FEB-21:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 8928.21 | 117320.47 | 26-MAR-03:32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2602.04 | 118723.87 | 11-APR-04:55 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 218.71 | 65411.41 | 02-MAY-05:16 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.68 | 21178.56 | 12-JUN-08:54 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13.18 | 18720.06 | 18-JUL-08:55 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 26.01 | 30804.32 | 24-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 124.50 | 50372.18 | 30-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1424.39 | 98177.04 | 11-OCT-06:24 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 11993.06 | 153591.71 | 27-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 20699.25 | 144345.48 | 02-DEC-16:02 |
Annual Sum or Average | 0.00 | 6514.99 | ||||
Minimum of Months | 0.00 | 0.00 | 11.68 | 18720.06 | ||
Maximum of Months | 0.00 | 0.00 | 20699.25 | 153591.71 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12636.95 | 154886.84 | 03-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 27777.90 | 324041.99 | 22-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 41727.77 | 362791.86 | 22-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 122954.78 | 491410.90 | 28-APR-21:51 | 0.00 | 0.00 | 01-APR-00:10 |
May | 194806.05 | 465710.92 | 15-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 262388.47 | 555733.16 | 19-JUN-18:52 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 326399.15 | 708591.49 | 20-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 271551.77 | 709342.02 | 01-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 234219.50 | 581890.04 | 03-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 121281.97 | 548758.99 | 03-OCT-21:52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36018.53 | 339140.30 | 09-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 9696.49 | 92147.33 | 15-DEC-19:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 139085.82 | 0.00 | ||||
Minimum of Months | 9696.49 | 92147.33 | 0.00 | 0.00 | ||
Maximum of Months | 326399.15 | 709342.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25383.65 | 62206.57 | 21-JAN-08:41 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 25398.38 | 62199.71 | 18-FEB-08:61 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24557.97 | 59958.73 | 23-MAR-06:21 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23036.34 | 57419.94 | 11-APR-06:51 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 21277.88 | 45944.14 | 02-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 19744.00 | 40797.81 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18838.99 | 38050.70 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18864.10 | 38276.30 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19753.64 | 44757.49 | 27-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21272.29 | 50590.72 | 24-OCT-06:42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 23000.23 | 56924.33 | 23-NOV-08:31 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24520.42 | 61032.00 | 15-DEC-07:01 |
Annual Sum or Average | 0.00 | 22118.78 | ||||
Minimum of Months | 0.00 | 0.00 | 18838.99 | 38050.70 | ||
Maximum of Months | 0.00 | 0.00 | 25398.38 | 62206.57 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.01 | 2194.93 | 01-JAN-00:05 | 1.01 |
February | 0.530997E+10 | 1.01 | 2194.93 | 01-FEB-00:10 | 1.01 |
March | 0.587890E+10 | 1.01 | 2194.93 | 01-MAR-00:10 | 1.01 |
April | 0.568926E+10 | 1.01 | 2194.93 | 01-APR-00:10 | 1.02 |
May | 0.587890E+10 | 1.01 | 2194.93 | 01-MAY-00:05 | 1.01 |
June | 0.568926E+10 | 1.01 | 2194.93 | 01-JUN-00:05 | 1.01 |
July | 0.587890E+10 | 1.00 | 2194.93 | 01-JUL-00:10 | 1.00 |
August | 0.587890E+10 | 1.00 | 2194.93 | 01-AUG-00:05 | 1.00 |
September | 0.568926E+10 | 1.00 | 2194.93 | 01-SEP-00:05 | 1.00 |
October | 0.587890E+10 | 1.01 | 2194.93 | 01-OCT-00:10 | 1.01 |
November | 0.568926E+10 | 1.01 | 2194.93 | 01-NOV-00:05 | 1.01 |
December | 0.587890E+10 | 1.01 | 2194.93 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.692193E+11 | 1.01 | |||
Minimum of Months | 0.530997E+10 | 1.00 | 2194.93 | 1.00 | |
Maximum of Months | 0.587890E+10 | 1.01 | 2194.93 | 1.02 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342284E+11 | 0.86 | 46598.31 | 04-JAN-22:02 | 1.88 |
February | 0.308162E+11 | 0.86 | 45863.83 | 01-FEB-20:40 | 1.86 |
March | 0.348009E+11 | 0.87 | 38106.49 | 17-MAR-20:35 | 1.65 |
April | 0.362309E+11 | 0.91 | 37946.14 | 11-APR-01:50 | 1.65 |
May | 0.401245E+11 | 0.94 | 33492.63 | 31-MAY-21:10 | 1.51 |
June | 0.424859E+11 | 0.98 | 36196.02 | 15-JUN-21:10 | 1.59 |
July | 0.441101E+11 | 0.98 | 37929.25 | 26-JUL-21:10 | 1.62 |
August | 0.449524E+11 | 0.99 | 40441.29 | 07-AUG-21:10 | 1.69 |
September | 0.431193E+11 | 0.98 | 40739.54 | 22-SEP-21:10 | 1.70 |
October | 0.411285E+11 | 0.95 | 44686.70 | 11-OCT-04:03 | 1.81 |
November | 0.363049E+11 | 0.91 | 45774.13 | 14-NOV-05:20 | 1.85 |
December | 0.345717E+11 | 0.87 | 46598.31 | 18-DEC-21:15 | 1.88 |
Annual Sum or Average | 0.462874E+12 | 0.92 | |||
Minimum of Months | 0.308162E+11 | 0.86 | 33492.63 | 1.51 | |
Maximum of Months | 0.449524E+11 | 0.99 | 46598.31 | 1.88 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.31 | 76.61 | 01-JAN-00:05 | 0.31 |
February | 0.185347E+09 | 0.31 | 76.61 | 01-FEB-00:10 | 0.31 |
March | 0.205205E+09 | 0.31 | 76.61 | 01-MAR-00:10 | 0.31 |
April | 0.198586E+09 | 0.31 | 76.61 | 01-APR-00:10 | 0.31 |
May | 0.205205E+09 | 0.31 | 76.61 | 01-MAY-00:05 | 0.31 |
June | 0.198586E+09 | 0.30 | 76.61 | 01-JUN-00:05 | 0.31 |
July | 0.205205E+09 | 0.30 | 76.61 | 01-JUL-00:10 | 0.30 |
August | 0.205205E+09 | 0.30 | 76.61 | 01-AUG-00:05 | 0.30 |
September | 0.198586E+09 | 0.30 | 76.61 | 01-SEP-00:05 | 0.30 |
October | 0.205205E+09 | 0.30 | 76.61 | 01-OCT-00:10 | 0.31 |
November | 0.198586E+09 | 0.31 | 76.61 | 01-NOV-00:05 | 0.31 |
December | 0.205205E+09 | 0.31 | 76.61 | 01-DEC-00:10 | 0.31 |
Annual Sum or Average | 0.241613E+10 | 0.31 | |||
Minimum of Months | 0.185347E+09 | 0.30 | 76.61 | 0.30 | |
Maximum of Months | 0.205205E+09 | 0.31 | 76.61 | 0.31 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.22 | 612.92 | 01-JAN-07:10 | 0.31 |
February | 0.105030E+10 | 0.22 | 612.92 | 01-FEB-07:05 | 0.31 |
March | 0.116283E+10 | 0.22 | 612.92 | 01-MAR-07:05 | 0.31 |
April | 0.112532E+10 | 0.22 | 612.92 | 01-APR-06:05 | 0.31 |
May | 0.116283E+10 | 0.22 | 612.92 | 01-MAY-06:05 | 0.31 |
June | 0.112532E+10 | 0.22 | 612.92 | 01-JUN-06:05 | 0.31 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:10 | 0.30 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.30 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.30 |
October | 0.116283E+10 | 0.22 | 612.92 | 01-OCT-06:10 | 0.31 |
November | 0.112532E+10 | 0.22 | 612.92 | 01-NOV-06:05 | 0.30 |
December | 0.116283E+10 | 0.22 | 612.92 | 01-DEC-07:05 | 0.31 |
Annual Sum or Average | 0.136914E+11 | 0.22 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.30 | |
Maximum of Months | 0.116283E+10 | 0.22 | 612.92 | 0.31 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201796E+09 | 0.48 | 854.96 | 01-JAN-16:02 | 0.66 |
February | 0.151185E+09 | 0.46 | 854.96 | 01-FEB-09:02 | 0.66 |
March | 0.142214E+09 | 0.44 | 854.96 | 01-MAR-09:02 | 0.66 |
April | 0.254924E+09 | 0.48 | 854.96 | 01-APR-08:51 | 0.66 |
May | 0.405029E+09 | 0.52 | 854.96 | 01-MAY-08:51 | 0.67 |
June | 0.523983E+09 | 0.56 | 854.96 | 01-JUN-08:31 | 0.66 |
July | 0.513248E+09 | 0.56 | 854.96 | 01-JUL-08:61 | 0.66 |
August | 0.477751E+09 | 0.54 | 854.96 | 01-AUG-08:61 | 0.66 |
September | 0.419044E+09 | 0.50 | 854.96 | 01-SEP-08:51 | 0.66 |
October | 0.251928E+09 | 0.45 | 854.96 | 01-OCT-08:51 | 0.66 |
November | 0.176406E+09 | 0.49 | 854.96 | 02-NOV-15:01 | 0.66 |
December | 0.225833E+09 | 0.48 | 854.96 | 02-DEC-16:02 | 0.67 |
Annual Sum or Average | 0.374334E+10 | 0.50 | |||
Minimum of Months | 0.142214E+09 | 0.44 | 854.96 | 0.66 | |
Maximum of Months | 0.523983E+09 | 0.56 | 854.96 | 0.67 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.255077E+09 | 0.46 | 849.32 | 01-JAN-09:01 | 0.66 |
February | 0.172027E+09 | 0.42 | 849.32 | 01-FEB-09:02 | 0.66 |
March | 0.131855E+09 | 0.40 | 849.32 | 01-MAR-09:02 | 0.66 |
April | 0.223200E+09 | 0.45 | 849.32 | 01-APR-15:01 | 0.66 |
May | 0.395496E+09 | 0.51 | 849.32 | 01-MAY-08:51 | 0.67 |
June | 0.527572E+09 | 0.56 | 849.32 | 01-JUN-08:31 | 0.66 |
July | 0.510435E+09 | 0.56 | 849.32 | 01-JUL-08:61 | 0.66 |
August | 0.447823E+09 | 0.53 | 849.32 | 01-AUG-08:61 | 0.66 |
September | 0.352355E+09 | 0.49 | 849.32 | 01-SEP-08:51 | 0.66 |
October | 0.174350E+09 | 0.40 | 849.32 | 01-OCT-08:51 | 0.66 |
November | 0.157453E+09 | 0.44 | 849.32 | 02-NOV-15:01 | 0.66 |
December | 0.300581E+09 | 0.47 | 849.32 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.364822E+10 | 0.48 | |||
Minimum of Months | 0.131855E+09 | 0.40 | 849.32 | 0.66 | |
Maximum of Months | 0.527572E+09 | 0.56 | 849.32 | 0.67 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.682100E+09 | 0.28 | 1452.17 | 12-JAN-14:30 | 0.66 |
February | 0.640063E+09 | 0.30 | 1372.17 | 07-FEB-13:40 | 0.67 |
March | 0.499079E+09 | 0.26 | 1071.28 | 16-MAR-12:50 | 0.67 |
April | 0.834597E+09 | 0.41 | 1029.06 | 04-APR-13:30 | 0.67 |
May | 0.109477E+10 | 0.51 | 1129.16 | 19-MAY-20:20 | 0.66 |
June | 0.151520E+10 | 0.62 | 1175.56 | 21-JUN-20:20 | 0.66 |
July | 0.157942E+10 | 0.64 | 1205.27 | 02-JUL-20:40 | 0.66 |
August | 0.160747E+10 | 0.61 | 1202.24 | 27-AUG-13:40 | 0.66 |
September | 0.176938E+10 | 0.62 | 1529.28 | 20-SEP-13:20 | 0.66 |
October | 0.156394E+10 | 0.51 | 2574.58 | 22-OCT-13:20 | 0.66 |
November | 0.109007E+10 | 0.35 | 1676.45 | 10-NOV-12:00 | 0.66 |
December | 0.548302E+09 | 0.25 | 1270.75 | 16-DEC-13:40 | 0.67 |
Annual Sum or Average | 0.134244E+11 | 0.45 | |||
Minimum of Months | 0.499079E+09 | 0.25 | 1029.06 | 0.66 | |
Maximum of Months | 0.176938E+10 | 0.64 | 2574.58 | 0.67 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102599E+10 | 0.46 | 5598.12 | 01-JAN-09:01 | 0.66 |
February | 0.760798E+09 | 0.42 | 5598.12 | 01-FEB-09:02 | 0.66 |
March | 0.748038E+09 | 0.39 | 5598.12 | 01-MAR-16:01 | 0.67 |
April | 0.136946E+10 | 0.38 | 5598.12 | 01-APR-08:51 | 0.67 |
May | 0.235872E+10 | 0.40 | 5598.12 | 01-MAY-08:51 | 0.67 |
June | 0.317345E+10 | 0.48 | 5598.12 | 01-JUN-08:31 | 0.66 |
July | 0.319491E+10 | 0.47 | 5598.12 | 01-JUL-08:61 | 0.66 |
August | 0.270629E+10 | 0.42 | 5598.12 | 01-AUG-08:61 | 0.66 |
September | 0.193812E+10 | 0.36 | 5598.12 | 01-SEP-08:51 | 0.66 |
October | 0.120659E+10 | 0.35 | 5598.12 | 01-OCT-08:51 | 0.66 |
November | 0.750348E+09 | 0.42 | 5598.12 | 02-NOV-19:21 | 0.66 |
December | 0.126513E+10 | 0.46 | 5598.12 | 01-DEC-16:01 | 0.67 |
Annual Sum or Average | 0.204978E+11 | 0.42 | |||
Minimum of Months | 0.748038E+09 | 0.35 | 5598.12 | 0.66 | |
Maximum of Months | 0.319491E+10 | 0.48 | 5598.12 | 0.67 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189954E+09 | 0.46 | 753.79 | 01-JAN-16:02 | 0.66 |
February | 0.147694E+09 | 0.46 | 753.79 | 01-FEB-19:02 | 0.67 |
March | 0.150481E+09 | 0.46 | 753.79 | 01-MAR-19:01 | 0.67 |
April | 0.263021E+09 | 0.52 | 753.79 | 01-APR-08:51 | 0.66 |
May | 0.400936E+09 | 0.54 | 753.79 | 01-MAY-08:51 | 0.67 |
June | 0.533364E+09 | 0.58 | 753.79 | 01-JUN-08:31 | 0.66 |
July | 0.526905E+09 | 0.57 | 753.79 | 01-JUL-08:61 | 0.66 |
August | 0.484534E+09 | 0.55 | 753.79 | 01-AUG-07:51 | 0.66 |
September | 0.413795E+09 | 0.52 | 753.79 | 01-SEP-08:51 | 0.66 |
October | 0.245494E+09 | 0.47 | 753.79 | 01-OCT-08:51 | 0.66 |
November | 0.171768E+09 | 0.49 | 753.79 | 02-NOV-15:01 | 0.66 |
December | 0.211784E+09 | 0.46 | 753.79 | 02-DEC-16:02 | 0.67 |
Annual Sum or Average | 0.373973E+10 | 0.51 | |||
Minimum of Months | 0.147694E+09 | 0.46 | 753.79 | 0.66 | |
Maximum of Months | 0.533364E+09 | 0.58 | 753.79 | 0.67 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.232887E+09 | 0.46 | 748.15 | 04-JAN-16:01 | 0.67 |
February | 0.153850E+09 | 0.42 | 748.15 | 01-FEB-16:01 | 0.67 |
March | 0.132204E+09 | 0.39 | 748.15 | 01-MAR-16:01 | 0.67 |
April | 0.227838E+09 | 0.49 | 748.15 | 01-APR-08:51 | 0.66 |
May | 0.391228E+09 | 0.54 | 748.15 | 01-MAY-08:51 | 0.67 |
June | 0.537446E+09 | 0.58 | 748.15 | 01-JUN-08:31 | 0.66 |
July | 0.525090E+09 | 0.57 | 748.15 | 01-JUL-08:61 | 0.66 |
August | 0.455903E+09 | 0.55 | 748.15 | 01-AUG-07:51 | 0.66 |
September | 0.342250E+09 | 0.51 | 748.15 | 01-SEP-08:51 | 0.66 |
October | 0.161251E+09 | 0.41 | 748.15 | 01-OCT-08:51 | 0.66 |
November | 0.150697E+09 | 0.42 | 748.15 | 03-NOV-08:62 | 0.66 |
December | 0.269926E+09 | 0.47 | 748.15 | 01-DEC-16:01 | 0.67 |
Annual Sum or Average | 0.358057E+10 | 0.48 | |||
Minimum of Months | 0.132204E+09 | 0.39 | 748.15 | 0.66 | |
Maximum of Months | 0.537446E+09 | 0.58 | 748.15 | 0.67 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 66139388.98 | 0.49 | 226.89 | 01-JAN-09:01 | 0.66 |
February | 49035890.27 | 0.46 | 226.89 | 01-FEB-09:02 | 0.66 |
March | 43237615.99 | 0.44 | 226.89 | 01-MAR-09:02 | 0.66 |
April | 65902651.52 | 0.48 | 226.89 | 01-APR-15:01 | 0.66 |
May | 0.103298E+09 | 0.52 | 226.89 | 01-MAY-08:51 | 0.67 |
June | 0.138022E+09 | 0.56 | 226.89 | 01-JUN-08:31 | 0.66 |
July | 0.135043E+09 | 0.56 | 226.89 | 01-JUL-08:61 | 0.66 |
August | 0.124835E+09 | 0.54 | 226.89 | 01-AUG-08:61 | 0.66 |
September | 0.106501E+09 | 0.50 | 226.89 | 01-SEP-08:51 | 0.65 |
October | 60221346.74 | 0.45 | 226.89 | 01-OCT-08:51 | 0.66 |
November | 51442723.96 | 0.49 | 226.89 | 02-NOV-08:62 | 0.66 |
December | 74699035.54 | 0.48 | 226.89 | 02-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.101838E+10 | 0.50 | |||
Minimum of Months | 43237615.99 | 0.44 | 226.89 | 0.65 | |
Maximum of Months | 0.138022E+09 | 0.56 | 226.89 | 0.67 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 82884016.54 | 0.48 | 225.17 | 01-JAN-09:01 | 0.66 |
February | 57295324.29 | 0.43 | 225.17 | 01-FEB-09:02 | 0.66 |
March | 42940974.10 | 0.40 | 225.17 | 01-MAR-09:02 | 0.66 |
April | 57878205.01 | 0.46 | 225.17 | 01-APR-15:01 | 0.66 |
May | 0.100915E+09 | 0.52 | 225.17 | 01-MAY-08:51 | 0.67 |
June | 0.139319E+09 | 0.56 | 225.17 | 01-JUN-08:31 | 0.66 |
July | 0.134553E+09 | 0.56 | 225.17 | 01-JUL-08:61 | 0.66 |
August | 0.117029E+09 | 0.53 | 225.17 | 01-AUG-08:61 | 0.66 |
September | 88672938.90 | 0.49 | 225.17 | 01-SEP-08:51 | 0.66 |
October | 41074447.74 | 0.40 | 225.17 | 01-OCT-08:51 | 0.66 |
November | 53898697.31 | 0.44 | 225.17 | 02-NOV-08:62 | 0.66 |
December | 96282630.60 | 0.49 | 225.17 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.101274E+10 | 0.48 | |||
Minimum of Months | 41074447.74 | 0.40 | 225.17 | 0.66 | |
Maximum of Months | 0.139319E+09 | 0.56 | 225.17 | 0.67 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321307E+09 | 0.55 | 1019.33 | 01-JAN-09:01 | 0.66 |
February | 0.263084E+09 | 0.52 | 1019.33 | 01-FEB-16:01 | 0.67 |
March | 0.229529E+09 | 0.48 | 1019.33 | 01-MAR-16:01 | 0.67 |
April | 0.323850E+09 | 0.49 | 1019.33 | 01-APR-08:51 | 0.66 |
May | 0.432592E+09 | 0.51 | 1019.33 | 01-MAY-08:51 | 0.67 |
June | 0.578436E+09 | 0.55 | 1019.33 | 01-JUN-08:31 | 0.66 |
July | 0.599964E+09 | 0.55 | 1019.33 | 01-JUL-08:61 | 0.66 |
August | 0.591237E+09 | 0.53 | 1019.33 | 01-AUG-08:61 | 0.66 |
September | 0.595432E+09 | 0.51 | 1019.33 | 01-SEP-08:51 | 0.66 |
October | 0.469130E+09 | 0.47 | 1019.33 | 01-OCT-08:51 | 0.66 |
November | 0.357436E+09 | 0.53 | 1019.33 | 02-NOV-15:01 | 0.66 |
December | 0.330839E+09 | 0.56 | 1019.33 | 01-DEC-16:01 | 0.66 |
Annual Sum or Average | 0.509284E+10 | 0.52 | |||
Minimum of Months | 0.229529E+09 | 0.47 | 1019.33 | 0.66 | |
Maximum of Months | 0.599964E+09 | 0.56 | 1019.33 | 0.67 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.560318E+09 | 0.504286E+09 | 749.62 | 29-JAN-06:10 | 674.66 | 674.66 | 39.22 | 1.41 |
February | 0.350757E+09 | 0.315681E+09 | 739.35 | 25-FEB-03:02 | 665.41 | 665.41 | 57.99 | 1.35 |
March | 0.251474E+09 | 0.226327E+09 | 737.03 | 01-MAR-01:55 | 663.33 | 663.33 | 42.66 | 1.35 |
April | 62154714.51 | 55939243.06 | 711.16 | 11-APR-04:55 | 640.04 | 640.04 | 37.13 | 1.24 |
May | 4901089.41 | 4410980.47 | 458.47 | 02-MAY-05:16 | 412.62 | 412.62 | 34.05 | 0.60 |
June | 431824.00 | 388641.60 | 287.10 | 29-JUN-08:54 | 258.39 | 258.39 | 45.12 | 0.33 |
July | 538946.55 | 485051.89 | 263.01 | 18-JUL-08:55 | 236.71 | 236.71 | 45.20 | 0.30 |
August | 1040448.66 | 936403.79 | 393.16 | 24-AUG-08:54 | 353.85 | 353.85 | 44.98 | 0.49 |
September | 3925593.91 | 3533034.52 | 494.04 | 30-SEP-06:02 | 444.64 | 444.64 | 52.89 | 0.66 |
October | 35304623.15 | 31774160.84 | 645.27 | 25-OCT-04:37 | 580.74 | 580.74 | 42.37 | 1.02 |
November | 0.331915E+09 | 0.298724E+09 | 768.60 | 28-NOV-09:15 | 691.74 | 691.74 | 47.00 | 1.51 |
December | 0.598698E+09 | 0.538828E+09 | 752.22 | 02-DEC-05:00 | 677.00 | 677.00 | 54.40 | 1.41 |
Annual Sum or Average | 0.220146E+10 | 0.198131E+10 | ||||||
Minimum of Months | 431824.00 | 388641.60 | 263.01 | 236.71 | 236.71 | 34.05 | 0.30 | |
Maximum of Months | 0.598698E+09 | 0.538828E+09 | 768.60 | 691.74 | 691.74 | 57.99 | 1.51 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 14523108.41 | 13070797.57 | 127.37 | 03-JAN-20:31 | 114.63 | 114.63 | 6.72 | 5.98 |
February | 29361431.51 | 26425288.36 | 307.83 | 20-FEB-16:01 | 277.05 | 277.05 | 6.72 | 9.09 |
March | 45461736.41 | 40915562.77 | 353.42 | 16-MAR-15:01 | 318.08 | 318.08 | 6.72 | 9.68 |
April | 0.245250E+09 | 0.220725E+09 | 1089.79 | 28-APR-18:03 | 980.81 | 980.81 | 6.72 | 15.85 |
May | 0.583042E+09 | 0.524738E+09 | 1311.63 | 19-MAY-18:03 | 1180.47 | 1180.47 | 6.72 | 17.13 |
June | 0.944207E+09 | 0.849786E+09 | 1730.35 | 05-JUN-18:03 | 1557.32 | 1557.32 | 6.72 | 19.22 |
July | 0.113264E+10 | 0.101938E+10 | 1548.24 | 05-JUL-18:03 | 1393.42 | 1393.42 | 6.72 | 18.36 |
August | 0.982855E+09 | 0.884569E+09 | 1466.38 | 22-AUG-18:03 | 1319.74 | 1319.74 | 6.72 | 17.95 |
September | 0.772560E+09 | 0.695304E+09 | 1476.74 | 18-SEP-19:10 | 1329.07 | 1329.07 | 6.72 | 18.00 |
October | 0.308101E+09 | 0.277291E+09 | 1200.07 | 01-OCT-18:30 | 1080.06 | 1080.06 | 6.72 | 16.50 |
November | 52528753.69 | 47275878.32 | 741.51 | 03-NOV-15:02 | 667.36 | 667.36 | 6.72 | 13.44 |
December | 10148747.77 | 9133873.00 | 102.05 | 09-DEC-09:01 | 91.84 | 91.84 | 6.72 | 5.35 |
Annual Sum or Average | 0.512068E+10 | 0.460861E+10 | ||||||
Minimum of Months | 10148747.77 | 9133873.00 | 102.05 | 91.84 | 91.84 | 6.72 | 5.35 | |
Maximum of Months | 0.113264E+10 | 0.101938E+10 | 1730.35 | 1557.32 | 1557.32 | 6.72 | 19.22 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.576122E+10 | 0.518510E+10 | 3251.78 | 01-JAN-00:05 | 2926.60 | 2926.60 | 6.73 | 28.76 |
February | 0.604102E+10 | 0.543692E+10 | 3251.78 | 01-FEB-01:30 | 2926.60 | 2926.60 | 6.73 | 28.76 |
March | 0.733440E+10 | 0.660096E+10 | 3251.78 | 01-MAR-00:10 | 2926.60 | 2926.60 | 6.73 | 28.76 |
April | 0.829678E+10 | 0.746710E+10 | 3251.78 | 01-APR-00:10 | 2926.60 | 2926.60 | 6.77 | 28.76 |
May | 0.870624E+10 | 0.783562E+10 | 3251.78 | 01-MAY-00:05 | 2926.60 | 2926.60 | 7.89 | 28.76 |
June | 0.842861E+10 | 0.758575E+10 | 3251.78 | 01-JUN-00:05 | 2926.60 | 2926.60 | 8.65 | 28.76 |
July | 0.870956E+10 | 0.783860E+10 | 3251.78 | 01-JUL-00:10 | 2926.60 | 2926.60 | 8.85 | 28.76 |
August | 0.870956E+10 | 0.783860E+10 | 3251.78 | 01-AUG-00:05 | 2926.60 | 2926.60 | 9.18 | 28.76 |
September | 0.842861E+10 | 0.758575E+10 | 3251.78 | 01-SEP-00:05 | 2926.60 | 2926.60 | 8.47 | 28.76 |
October | 0.867054E+10 | 0.780348E+10 | 3251.78 | 01-OCT-00:10 | 2926.60 | 2926.60 | 7.23 | 28.76 |
November | 0.673639E+10 | 0.606275E+10 | 3251.78 | 01-NOV-00:05 | 2926.60 | 2926.60 | 6.83 | 28.76 |
December | 0.542139E+10 | 0.487925E+10 | 3251.78 | 01-DEC-05:05 | 2926.60 | 2926.60 | 6.73 | 28.76 |
Annual Sum or Average | 0.912443E+11 | 0.821199E+11 | ||||||
Minimum of Months | 0.542139E+10 | 0.487925E+10 | 3251.78 | 2926.60 | 2926.60 | 6.73 | 28.76 | |
Maximum of Months | 0.870956E+10 | 0.783860E+10 | 3251.78 | 2926.60 | 2926.60 | 9.18 | 28.76 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 49.26 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 49.75 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.41 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.70 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.95 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.35 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.91 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.95 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.49 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.52 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.20 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 50.88 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.26 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.95 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 37.57 | 60.00 | 19203.23 | 149205.86 | 18-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 49.60 | 60.00 | 13218.90 | 128509.30 | 01-FEB-21:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 39.64 | 60.00 | 8928.21 | 117320.47 | 26-MAR-03:32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 38.44 | 60.00 | 2602.04 | 118723.87 | 11-APR-04:55 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 40.34 | 40.34 | 218.71 | 65411.41 | 02-MAY-05:16 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 43.44 | 43.44 | 11.68 | 21178.56 | 12-JUN-08:54 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 44.98 | 44.98 | 13.18 | 18720.06 | 18-JUL-08:55 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 46.10 | 46.10 | 26.01 | 30804.32 | 24-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 45.15 | 45.15 | 124.50 | 50372.18 | 30-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 34.10 | 34.10 | 1424.39 | 98177.04 | 11-OCT-06:24 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 36.74 | 60.00 | 11993.06 | 153591.71 | 27-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 44.35 | 60.00 | 20699.25 | 144345.48 | 02-DEC-16:02 |
Annual Sum or Average | 0.00 | 6514.99 | ||||||
Minimum of Months | 0.00 | 0.00 | 34.10 | 34.10 | 11.68 | 18720.06 | ||
Maximum of Months | 0.00 | 0.00 | 49.60 | 60.00 | 20699.25 | 153591.71 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12636.95 | 154886.84 | 03-JAN-16:01 | 7.98 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 27777.90 | 324041.99 | 22-FEB-16:01 | 9.39 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 41727.77 | 362791.86 | 22-MAR-15:01 | 9.71 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 122954.78 | 491410.90 | 28-APR-21:51 | 10.78 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 194806.05 | 465710.92 | 15-MAY-18:03 | 10.56 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 262388.47 | 555733.16 | 19-JUN-18:52 | 11.31 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 326399.15 | 708591.49 | 20-JUL-21:52 | 12.58 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 271551.77 | 709342.02 | 01-AUG-21:51 | 12.59 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 234219.50 | 581890.04 | 03-SEP-21:52 | 11.53 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 121281.97 | 548758.99 | 03-OCT-21:52 | 11.25 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36018.53 | 339140.30 | 09-NOV-16:01 | 9.51 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 9696.49 | 92147.33 | 15-DEC-19:02 | 7.46 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 139085.82 | 0.00 | ||||||
Minimum of Months | 9696.49 | 92147.33 | 7.46 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 326399.15 | 709342.02 | 12.59 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 49.26 | 59.73 | 25383.65 | 62206.57 | 21-JAN-08:41 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 49.75 | 58.57 | 25398.38 | 62199.71 | 18-FEB-08:61 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.41 | 59.30 | 24557.97 | 59958.73 | 23-MAR-06:21 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.70 | 58.94 | 23036.34 | 57419.94 | 11-APR-06:51 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.95 | 58.79 | 21277.88 | 45944.14 | 02-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.35 | 58.65 | 19744.00 | 40797.81 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.91 | 58.76 | 18838.99 | 38050.70 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.95 | 58.79 | 18864.10 | 38276.30 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.49 | 58.62 | 19753.64 | 44757.49 | 27-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.52 | 58.29 | 21272.29 | 50590.72 | 24-OCT-06:42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.20 | 59.78 | 23000.23 | 56924.33 | 23-NOV-08:31 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 50.88 | 59.53 | 24520.42 | 61032.00 | 15-DEC-07:01 |
Annual Sum or Average | 0.00 | 22118.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.26 | 58.29 | 18838.99 | 38050.70 | ||
Maximum of Months | 0.00 | 0.00 | 53.95 | 59.78 | 25398.38 | 62206.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.337737E+11 | 0.00 | 0.670646E+10 | 0.342284E+11 | 0.00 | 0.00 |
February | 0.217092E+11 | 0.00 | 0.328647E+11 | 0.308162E+11 | 0.00 | 0.00 |
March | 0.190969E+11 | 0.00 | 0.669157E+11 | 0.348009E+11 | 0.00 | 0.00 |
April | 0.625004E+10 | 0.00 | 0.210684E+12 | 0.362309E+11 | 0.00 | 0.00 |
May | 0.472762E+09 | 0.00 | 0.350048E+12 | 0.401245E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.455412E+12 | 0.424859E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.608638E+12 | 0.441101E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.494963E+12 | 0.449524E+11 | 0.00 | 0.00 |
September | 0.247863E+09 | 0.00 | 0.403396E+12 | 0.431193E+11 | 0.00 | 0.00 |
October | 0.360143E+10 | 0.00 | 0.198517E+12 | 0.411285E+11 | 0.00 | 0.00 |
November | 0.231536E+11 | 0.00 | 0.409353E+11 | 0.363049E+11 | 0.00 | 0.00 |
December | 0.315142E+11 | 0.00 | 0.410164E+10 | 0.345717E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.139820E+12 | 0.00 | 0.287318E+13 | 0.462874E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.410164E+10 | 0.308162E+11 | 0.00 | 0.00 |
Maximum of Months | 0.337737E+11 | 0.00 | 0.608638E+12 | 0.449524E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 43645977.91 | 0.00 | 0.122869E+10 | 0.587890E+10 | 0.00 | 0.00 |
February | 64573998.73 | 0.00 | 0.619310E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 29725148.62 | 0.00 | 0.122686E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 39732.54 | 0.00 | 0.349245E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 84118.23 | 0.00 | 0.560482E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 57314.27 | 0.00 | 0.684145E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 30402.37 | 0.00 | 0.926654E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 32779.23 | 0.00 | 0.773791E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 43576.14 | 0.00 | 0.662244E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 26947.49 | 0.00 | 0.334833E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 3068200.31 | 0.00 | 0.751668E+10 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.178729E+09 | 0.00 | 0.724489E+09 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.320057E+09 | 0.00 | 0.457071E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 26947.49 | 0.00 | 0.724489E+09 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.178729E+09 | 0.00 | 0.926654E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.342284E+11 | 0.670704E+10 | 0.337737E+11 | 0.199661E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308162E+11 | 0.328647E+11 | 0.217092E+11 | 0.144218E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348009E+11 | 0.669158E+11 | 0.190969E+11 | 0.107936E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362309E+11 | 0.210684E+12 | 0.625004E+10 | 0.275652E+11 | 0.387864E+10 | 0.00 | 0.00 | 0.00 |
May | 0.401245E+11 | 0.350048E+12 | 0.472762E+09 | 0.194764E+11 | 0.170797E+11 | 0.00 | 0.00 | 0.00 |
June | 0.424859E+11 | 0.455412E+12 | 0.00 | 0.235643E+11 | 0.427262E+11 | 0.00 | 0.00 | 0.00 |
July | 0.441101E+11 | 0.608638E+12 | 0.00 | 0.931471E+10 | 0.740709E+11 | 0.00 | 0.00 | 0.00 |
August | 0.449524E+11 | 0.494963E+12 | 0.00 | 0.114047E+11 | 0.353983E+11 | 0.00 | 0.00 | 0.00 |
September | 0.431193E+11 | 0.403396E+12 | 0.247863E+09 | 0.792335E+10 | 0.196148E+11 | 0.00 | 0.00 | 0.00 |
October | 0.411285E+11 | 0.198517E+12 | 0.360143E+10 | 0.144554E+11 | 0.341705E+10 | 0.00 | 0.00 | 0.00 |
November | 0.363049E+11 | 0.409359E+11 | 0.231536E+11 | 0.110873E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345717E+11 | 0.410306E+10 | 0.315142E+11 | 0.252455E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462874E+12 | 0.287319E+13 | 0.139820E+12 | 0.928848E+12 | 0.196186E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308162E+11 | 0.410306E+10 | 0.00 | 0.792335E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449524E+11 | 0.608638E+12 | 0.337737E+11 | 0.252455E+12 | 0.740709E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.122869E+10 | 43645977.91 | 0.457328E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.619310E+10 | 64573998.73 | 0.320194E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.122686E+11 | 29725148.62 | 0.252141E+11 | 26481521.35 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.349245E+11 | 39732.54 | 0.660848E+10 | 0.243806E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.560482E+11 | 84118.23 | 0.169504E+10 | 0.910155E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.684145E+11 | 57314.27 | 0.453793E+09 | 0.195166E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.926654E+11 | 30402.37 | 163347.71 | 0.395613E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.773791E+11 | 32779.23 | 0.107541E+09 | 0.245619E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.662244E+11 | 43576.14 | 0.902723E+09 | 0.145080E+11 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.334833E+11 | 26947.49 | 0.522472E+10 | 0.364822E+10 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.751668E+10 | 3068200.31 | 0.293296E+11 | 32227267.50 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.724489E+09 | 0.178729E+09 | 0.539906E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.457071E+12 | 0.320057E+09 | 0.201279E+12 | 0.113394E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.724489E+09 | 26947.49 | 163347.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.926654E+11 | 0.178729E+09 | 0.539906E+11 | 0.395613E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.342284E+11 | 0.337737E+11 | 0.670646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308162E+11 | 0.217092E+11 | 0.328647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348009E+11 | 0.190969E+11 | 0.669157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362309E+11 | 0.625004E+10 | 0.210684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.401245E+11 | 0.472762E+09 | 0.350048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.424859E+11 | 0.00 | 0.455412E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.441101E+11 | 0.00 | 0.608638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.449524E+11 | 0.00 | 0.494963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.431193E+11 | 0.247863E+09 | 0.403396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411285E+11 | 0.360143E+10 | 0.198517E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363049E+11 | 0.231536E+11 | 0.409353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345717E+11 | 0.315142E+11 | 0.410164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462874E+12 | 0.139820E+12 | 0.287318E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308162E+11 | 0.00 | 0.410164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449524E+11 | 0.337737E+11 | 0.608638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 43645977.91 | 0.122869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 64573998.73 | 0.619310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 29725148.62 | 0.122686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 39732.54 | 0.349245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 84118.23 | 0.560482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 57314.27 | 0.684145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 30402.37 | 0.926654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 32779.23 | 0.773791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 43576.14 | 0.662244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 26947.49 | 0.334833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 3068200.31 | 0.751668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.178729E+09 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.320057E+09 | 0.457071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 26947.49 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.178729E+09 | 0.926654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133491E+11 | 0.00 | 0.00 | 53730398.49 | 0.00 | 0.00 | 0.401204E+11 | 0.00 | 1.02 |
February | 0.363369E+11 | 0.00 | 0.00 | 3547735.32 | 0.00 | 0.00 | 0.545608E+10 | 0.00 | 0.99 |
March | 0.425947E+11 | 0.00 | 0.00 | 3386.08 | 0.00 | 0.00 | 43924139.78 | 0.00 | 1.00 |
April | 0.277379E+11 | 0.00 | 0.00 | 0.00 | 90167542.50 | 0.00 | 0.00 | 0.00 | 1.00 |
May | 0.172335E+11 | 0.00 | 0.00 | 0.00 | 0.517115E+09 | 0.00 | 0.00 | 0.00 | 0.97 |
June | 0.844730E+10 | 7071059.62 | 0.00 | 1458708.22 | 0.155224E+10 | 0.00 | 0.422352E+09 | 0.00 | 0.90 |
July | 0.202853E+09 | 0.509345E+10 | 0.00 | 17118024.69 | 0.239071E+10 | 0.00 | 0.215643E+10 | 0.00 | 0.92 |
August | 15387268.12 | 0.207956E+10 | 0.00 | 58721033.20 | 0.124460E+09 | 0.00 | 0.936422E+10 | 0.00 | 1.06 |
September | 106516.84 | 0.145083E+10 | 0.00 | 85636367.86 | 4275491.52 | 0.00 | 0.187471E+11 | 0.00 | 1.26 |
October | 18564243.85 | 0.236085E+09 | 0.00 | 0.107217E+09 | 0.00 | 0.00 | 0.427212E+11 | 0.00 | 1.32 |
November | 0.151664E+09 | 0.00 | 0.00 | 0.125521E+09 | 0.00 | 0.00 | 0.584501E+11 | 0.00 | 1.24 |
December | 0.912160E+09 | 0.00 | 0.00 | 0.122884E+09 | 0.00 | 0.00 | 0.586196E+11 | 0.00 | 1.12 |
Annual Sum or Average | 0.147000E+12 | 0.886700E+10 | 0.00 | 0.575838E+09 | 0.467897E+10 | 0.00 | 0.236101E+12 | 0.00 | 1.07 |
Minimum of Months | 106516.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 |
Maximum of Months | 0.425947E+11 | 0.509345E+10 | 0.00 | 0.125521E+09 | 0.239071E+10 | 0.00 | 0.586196E+11 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.501140E+10 | 0.00 | 0.00 | 1755865.35 | 0.00 | 0.104500E+09 | 0.105995E+10 | 0.00 | 2.17 |
February | 0.424267E+10 | 0.00 | 0.00 | 1673122.29 | 0.00 | 71782275.33 | 0.810718E+09 | 0.00 | 2.25 |
March | 0.453518E+10 | 0.00 | 0.00 | 1126978.07 | 0.00 | 50134129.27 | 0.579055E+09 | 0.00 | 2.22 |
April | 0.276176E+10 | 13116815.49 | 0.00 | 2292796.20 | 67554.84 | 270884.32 | 0.589771E+09 | 0.00 | 2.23 |
May | 0.138556E+10 | 67953327.32 | 0.00 | 3165281.23 | 1804444.80 | 0.00 | 0.706399E+09 | 0.00 | 2.18 |
June | 0.358221E+09 | 0.233876E+09 | 0.00 | 3865250.19 | 942114.17 | 0.00 | 0.733845E+09 | 0.00 | 2.17 |
July | 61114545.22 | 0.824723E+09 | 0.00 | 1793589.27 | 0.127061E+09 | 0.00 | 0.226289E+09 | 0.00 | 2.16 |
August | 0.382657E+09 | 0.276477E+09 | 0.00 | 4214324.25 | 15397969.06 | 0.00 | 0.594213E+09 | 0.00 | 2.28 |
September | 0.817698E+09 | 0.197651E+09 | 0.00 | 5653922.19 | 5182348.43 | 0.00 | 0.890055E+09 | 0.00 | 2.52 |
October | 0.248722E+10 | 35413762.25 | 0.00 | 6127971.74 | 657389.51 | 0.00 | 0.154231E+10 | 0.00 | 2.57 |
November | 0.405599E+10 | 0.00 | 0.00 | 3691363.70 | 0.00 | 65317459.33 | 0.165336E+10 | 0.00 | 2.37 |
December | 0.473664E+10 | 0.00 | 0.00 | 1320595.39 | 0.00 | 0.396632E+09 | 0.936869E+09 | 0.00 | 2.12 |
Annual Sum or Average | 0.308361E+11 | 0.164921E+10 | 0.00 | 36681059.86 | 0.151113E+09 | 0.688637E+09 | 0.103228E+11 | 0.00 | 2.27 |
Minimum of Months | 61114545.22 | 0.00 | 0.00 | 1126978.07 | 0.00 | 0.00 | 0.226289E+09 | 0.00 | 2.12 |
Maximum of Months | 0.501140E+10 | 0.824723E+09 | 0.00 | 6127971.74 | 0.127061E+09 | 0.396632E+09 | 0.165336E+10 | 0.00 | 2.57 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.379779E+10 | 0.00 | 0.00 | 575507.81 | 0.00 | 0.00 | 0.753447E+09 | 0.00 | 1.37 |
February | 0.290039E+10 | 0.00 | 0.00 | 782743.87 | 0.00 | 0.00 | 0.913018E+09 | 0.00 | 1.42 |
March | 0.262444E+10 | 0.00 | 0.00 | 1264115.61 | 0.00 | 0.00 | 0.129345E+10 | 0.00 | 1.45 |
April | 0.838030E+09 | 4452034.90 | 0.00 | 3276235.11 | 3744799.02 | 0.00 | 0.179189E+10 | 0.00 | 1.50 |
May | 0.144276E+09 | 38687305.95 | 0.00 | 5309344.04 | 8381605.82 | 0.00 | 0.158582E+10 | 0.00 | 1.53 |
June | 9469867.00 | 0.143495E+09 | 0.00 | 5507865.59 | 5378237.22 | 0.00 | 0.950192E+09 | 0.00 | 1.51 |
July | 384775.45 | 0.697007E+09 | 0.00 | 2765818.33 | 39322241.46 | 0.00 | 0.257199E+09 | 0.00 | 1.50 |
August | 26292430.32 | 0.194330E+09 | 0.00 | 5112812.16 | 10521399.36 | 0.00 | 0.809818E+09 | 0.00 | 1.54 |
September | 33652387.12 | 0.116791E+09 | 0.00 | 5786561.77 | 8837556.26 | 0.00 | 0.140677E+10 | 0.00 | 1.62 |
October | 0.685385E+09 | 19013629.58 | 0.00 | 4242759.91 | 1293291.81 | 0.00 | 0.242188E+10 | 0.00 | 1.57 |
November | 0.254445E+10 | 0.00 | 0.00 | 1520994.59 | 0.00 | 0.00 | 0.162736E+10 | 0.00 | 1.42 |
December | 0.392948E+10 | 0.00 | 0.00 | 341539.63 | 0.00 | 0.00 | 0.564832E+09 | 0.00 | 1.36 |
Annual Sum or Average | 0.175340E+11 | 0.121378E+10 | 0.00 | 36486298.41 | 77479130.95 | 0.00 | 0.143757E+11 | 0.00 | 1.48 |
Minimum of Months | 384775.45 | 0.00 | 0.00 | 341539.63 | 0.00 | 0.00 | 0.257199E+09 | 0.00 | 1.36 |
Maximum of Months | 0.392948E+10 | 0.697007E+09 | 0.00 | 5786561.77 | 39322241.46 | 0.00 | 0.242188E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
February | 0.315076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.322138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 0.205452E+10 | 0.00 | 0.00 | 65626.35 | 6812220.61 | 0.00 | 41170283.18 | 0.00 | 0.56 |
May | 0.831403E+09 | 14255881.47 | 0.00 | 1556583.80 | 24822280.87 | 0.00 | 0.496464E+09 | 0.00 | 0.56 |
June | 57797451.47 | 0.124713E+09 | 0.00 | 4115934.58 | 3426892.78 | 0.00 | 0.687827E+09 | 0.00 | 0.58 |
July | 2811378.78 | 0.533641E+09 | 0.00 | 2144381.36 | 66841876.19 | 0.00 | 0.200008E+09 | 0.00 | 0.58 |
August | 0.132214E+09 | 0.155560E+09 | 0.00 | 3139088.55 | 11327353.35 | 0.00 | 0.504164E+09 | 0.00 | 0.57 |
September | 0.514120E+09 | 55746796.58 | 0.00 | 1798405.61 | 43786662.66 | 0.00 | 0.544434E+09 | 0.00 | 0.57 |
October | 0.228587E+10 | 6561090.00 | 0.00 | 285559.66 | 9205071.62 | 0.00 | 0.133936E+09 | 0.00 | 0.57 |
November | 0.340101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
December | 0.373241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232570.04 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.231580E+11 | 0.890478E+09 | 0.00 | 13105579.91 | 0.166222E+09 | 232570.04 | 0.260800E+10 | 0.00 | 0.56 |
Minimum of Months | 2811378.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.377371E+10 | 0.533641E+09 | 0.00 | 4115934.58 | 66841876.19 | 232570.04 | 0.687827E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 278698.43 | 0.00 | 0.00 | 0.61 |
February | 0.208894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 278908.56 | 0.00 | 0.00 | 0.63 |
March | 0.213573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310342.22 | 0.00 | 0.00 | 0.64 |
April | 0.138957E+10 | 0.00 | 0.00 | 0.00 | 4517071.98 | 0.00 | 0.00 | 0.00 | 0.64 |
May | 0.773889E+09 | 2473140.66 | 0.00 | 231392.25 | 23432477.17 | 0.00 | 89663532.18 | 0.00 | 0.62 |
June | 0.163760E+09 | 73883736.58 | 0.00 | 1419899.23 | 6775303.73 | 0.00 | 0.288697E+09 | 0.00 | 0.60 |
July | 22098598.48 | 0.242593E+09 | 0.00 | 834092.52 | 0.125363E+09 | 0.00 | 97366523.81 | 0.00 | 0.60 |
August | 0.237596E+09 | 77966238.25 | 0.00 | 849612.65 | 24103800.25 | 0.00 | 0.162791E+09 | 0.00 | 0.61 |
September | 0.616779E+09 | 14462606.95 | 0.00 | 215884.05 | 49871274.63 | 0.00 | 70367976.57 | 0.00 | 0.63 |
October | 0.159215E+10 | 1807093.47 | 0.00 | 20716.32 | 7966629.59 | 0.00 | 10240468.83 | 0.00 | 0.65 |
November | 0.225498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182574.74 | 0.00 | 0.00 | 0.63 |
December | 0.246229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12759660.96 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.162398E+11 | 0.413186E+09 | 0.00 | 3571597.01 | 0.242030E+09 | 13810184.91 | 0.719127E+09 | 0.00 | 0.62 |
Minimum of Months | 22098598.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.250201E+10 | 0.242593E+09 | 0.00 | 1419899.23 | 0.125363E+09 | 12759660.96 | 0.288697E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.455694E+09 | 0.00 | 0.00 | 0.158100E+09 | 0.00 | 0.00 | 0.751646E+11 | 0.00 | 22.25 |
February | 0.573370E+09 | 0.00 | 0.00 | 0.132229E+09 | 0.00 | 0.00 | 0.630035E+11 | 0.00 | 23.00 |
March | 0.817927E+09 | 0.00 | 0.00 | 0.136640E+09 | 0.00 | 0.00 | 0.646884E+11 | 0.00 | 23.69 |
April | 0.252620E+09 | 0.109157E+09 | 0.00 | 0.124626E+09 | 0.00 | 0.00 | 0.412592E+11 | 0.00 | 23.45 |
May | 0.00 | 0.631107E+09 | 0.00 | 0.114710E+09 | 0.00 | 0.00 | 0.252582E+11 | 0.00 | 22.40 |
June | 0.00 | 0.205372E+10 | 0.00 | 83815706.17 | 0.00 | 0.00 | 0.124656E+11 | 0.00 | 20.63 |
July | 0.00 | 0.106390E+11 | 0.00 | 32352251.42 | 0.00 | 0.00 | 0.317003E+10 | 0.00 | 20.35 |
August | 0.00 | 0.296604E+10 | 0.00 | 80273104.60 | 0.00 | 0.00 | 0.112302E+11 | 0.00 | 21.26 |
September | 0.00 | 0.178683E+10 | 0.00 | 95523692.24 | 0.00 | 0.00 | 0.202990E+11 | 0.00 | 22.79 |
October | 0.328613E+09 | 0.312264E+09 | 0.00 | 0.113211E+09 | 0.00 | 0.00 | 0.477474E+11 | 0.00 | 23.96 |
November | 0.861317E+09 | 0.00 | 0.00 | 0.129139E+09 | 0.00 | 0.00 | 0.678207E+11 | 0.00 | 22.71 |
December | 0.583342E+09 | 0.00 | 0.00 | 0.165403E+09 | 0.00 | 0.00 | 0.738954E+11 | 0.00 | 21.78 |
Annual Sum or Average | 0.387288E+10 | 0.184982E+11 | 0.00 | 0.136602E+10 | 0.00 | 0.00 | 0.506002E+12 | 0.00 | 22.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32352251.42 | 0.00 | 0.00 | 0.317003E+10 | 0.00 | 20.35 |
Maximum of Months | 0.861317E+09 | 0.106390E+11 | 0.00 | 0.165403E+09 | 0.00 | 0.00 | 0.751646E+11 | 0.00 | 23.96 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.656310E+10 | 0.00 | 0.00 | 26777235.28 | 0.00 | 0.00 | 0.204492E+11 | 0.00 | 3.39 |
February | 0.460851E+10 | 0.00 | 0.00 | 26274107.95 | 0.00 | 0.00 | 0.178649E+11 | 0.00 | 3.51 |
March | 0.533570E+10 | 0.00 | 0.00 | 27011450.02 | 0.00 | 0.00 | 0.174215E+11 | 0.00 | 3.49 |
April | 0.222068E+10 | 52224377.44 | 0.00 | 31712822.06 | 91279.06 | 0.00 | 0.131552E+11 | 0.00 | 3.64 |
May | 0.640592E+09 | 0.269529E+09 | 0.00 | 32758204.76 | 5041932.35 | 0.00 | 0.953187E+10 | 0.00 | 3.62 |
June | 55936577.35 | 0.869229E+09 | 0.00 | 29970099.09 | 10506044.33 | 0.00 | 0.562645E+10 | 0.00 | 3.58 |
July | 689214.31 | 0.406372E+10 | 0.00 | 15383819.15 | 0.144335E+09 | 0.00 | 0.155581E+10 | 0.00 | 3.56 |
August | 0.119058E+09 | 0.118615E+10 | 0.00 | 30328166.00 | 23942225.13 | 0.00 | 0.491758E+10 | 0.00 | 3.75 |
September | 0.139555E+09 | 0.798544E+09 | 0.00 | 37480130.61 | 7261032.93 | 0.00 | 0.839047E+10 | 0.00 | 4.08 |
October | 0.138085E+10 | 0.137894E+09 | 0.00 | 44219923.27 | 1635902.12 | 0.00 | 0.173740E+11 | 0.00 | 4.10 |
November | 0.425955E+10 | 0.00 | 0.00 | 35287464.88 | 0.00 | 0.00 | 0.213508E+11 | 0.00 | 3.71 |
December | 0.788868E+10 | 0.00 | 0.00 | 22831990.36 | 0.00 | 0.00 | 0.186026E+11 | 0.00 | 3.31 |
Annual Sum or Average | 0.332129E+11 | 0.737729E+10 | 0.00 | 0.360035E+09 | 0.192814E+09 | 0.00 | 0.156241E+12 | 0.00 | 3.65 |
Minimum of Months | 689214.31 | 0.00 | 0.00 | 15383819.15 | 0.00 | 0.00 | 0.155581E+10 | 0.00 | 3.31 |
Maximum of Months | 0.788868E+10 | 0.406372E+10 | 0.00 | 44219923.27 | 0.144335E+09 | 0.00 | 0.213508E+11 | 0.00 | 4.10 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332816E+11 | 0.00 | 0.00 | 59064073.45 | 0.00 | 0.00 | 0.546393E+11 | 0.00 | 1.57 |
February | 0.237055E+11 | 0.00 | 0.00 | 63564551.68 | 0.00 | 0.00 | 0.503900E+11 | 0.00 | 1.63 |
March | 0.229651E+11 | 0.00 | 0.00 | 73999665.11 | 0.00 | 0.00 | 0.539806E+11 | 0.00 | 1.68 |
April | 0.753305E+10 | 0.147694E+09 | 0.00 | 95230771.13 | 6465099.57 | 0.00 | 0.456942E+11 | 0.00 | 1.78 |
May | 0.173823E+10 | 0.810653E+09 | 0.00 | 0.113361E+09 | 74282770.11 | 0.00 | 0.343437E+11 | 0.00 | 1.81 |
June | 0.177674E+09 | 0.266048E+10 | 0.00 | 0.108720E+09 | 0.111811E+09 | 0.00 | 0.199728E+11 | 0.00 | 1.77 |
July | 910683.39 | 0.137108E+11 | 0.00 | 56143968.62 | 0.598024E+09 | 0.00 | 0.548459E+10 | 0.00 | 1.76 |
August | 0.335901E+09 | 0.374326E+10 | 0.00 | 0.104663E+09 | 0.179116E+09 | 0.00 | 0.173422E+11 | 0.00 | 1.82 |
September | 0.265313E+09 | 0.230760E+10 | 0.00 | 0.122107E+09 | 0.105290E+09 | 0.00 | 0.297858E+11 | 0.00 | 1.92 |
October | 0.418536E+10 | 0.377078E+09 | 0.00 | 0.129437E+09 | 13935839.86 | 0.00 | 0.594329E+11 | 0.00 | 1.88 |
November | 0.151528E+11 | 0.00 | 0.00 | 93255510.30 | 0.00 | 0.00 | 0.674665E+11 | 0.00 | 1.66 |
December | 0.378732E+11 | 0.00 | 0.00 | 51990303.78 | 0.00 | 0.00 | 0.483964E+11 | 0.00 | 1.54 |
Annual Sum or Average | 0.147215E+12 | 0.237576E+11 | 0.00 | 0.107154E+10 | 0.108892E+10 | 0.00 | 0.486929E+12 | 0.00 | 1.74 |
Minimum of Months | 910683.39 | 0.00 | 0.00 | 51990303.78 | 0.00 | 0.00 | 0.548459E+10 | 0.00 | 1.54 |
Maximum of Months | 0.378732E+11 | 0.137108E+11 | 0.00 | 0.129437E+09 | 0.598024E+09 | 0.00 | 0.674665E+11 | 0.00 | 1.92 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401091E+09 | 0.00 | 0.00 | 2829363.64 | 0.00 | 0.758399E+09 | 0.413274E+09 | 0.00 | 0.47 |
February | 0.366612E+09 | 0.00 | 0.00 | 3528234.19 | 0.00 | 0.480837E+09 | 0.474772E+09 | 0.00 | 0.47 |
March | 0.380653E+09 | 27703.48 | 0.00 | 5792440.31 | 0.00 | 0.300386E+09 | 0.676013E+09 | 0.00 | 0.47 |
April | 0.221268E+09 | 14652583.22 | 6720.02 | 10091500.04 | 1444801.80 | 28774308.05 | 0.578550E+09 | 2309.61 | 0.47 |
May | 0.113724E+09 | 76756843.52 | 20355.88 | 8335973.29 | 6592598.57 | 536698.59 | 0.310606E+09 | 11671.51 | 0.47 |
June | 37213905.68 | 0.171100E+09 | 43346.00 | 3972789.52 | 9550878.55 | 10774.53 | 59155277.79 | 13918.25 | 0.47 |
July | 1236331.90 | 0.676431E+09 | 364166.77 | 3614.25 | 0.123126E+09 | 0.00 | 2982.34 | 28532.22 | 0.47 |
August | 32257847.52 | 0.347261E+09 | 237466.93 | 1526142.63 | 56616601.94 | 40807.52 | 18689421.13 | 34245.21 | 0.47 |
September | 91156047.06 | 0.307910E+09 | 209686.39 | 5215710.94 | 50346303.86 | 277238.73 | 0.152127E+09 | 30699.52 | 0.48 |
October | 0.249673E+09 | 59799930.43 | 93169.16 | 9530335.45 | 10388388.06 | 2034002.61 | 0.633109E+09 | 7913.64 | 0.47 |
November | 0.321025E+09 | 558931.32 | 0.00 | 6316844.10 | 23847.39 | 0.378549E+09 | 0.695143E+09 | 0.00 | 0.47 |
December | 0.410888E+09 | 0.00 | 0.00 | 2061799.68 | 0.00 | 0.832411E+09 | 0.329656E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.262680E+10 | 0.165450E+10 | 974911.15 | 59204748.02 | 0.258089E+09 | 0.278225E+10 | 0.434110E+10 | 129289.95 | 0.47 |
Minimum of Months | 1236331.90 | 0.00 | 0.00 | 3614.25 | 0.00 | 0.00 | 2982.34 | 0.00 | 0.47 |
Maximum of Months | 0.410888E+09 | 0.676431E+09 | 364166.77 | 10091500.04 | 0.123126E+09 | 0.832411E+09 | 0.695143E+09 | 34245.21 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458313E+09 | 0.00 | 0.00 | 720723.94 | 0.00 | 0.994490E+09 | 0.121886E+09 | 0.00 | 0.47 |
February | 0.413993E+09 | 0.00 | 0.00 | 1253902.57 | 0.00 | 0.686593E+09 | 0.223754E+09 | 0.00 | 0.47 |
March | 0.418540E+09 | 27660.19 | 6.42 | 3313820.55 | 0.00 | 0.449365E+09 | 0.491466E+09 | 33.62 | 0.47 |
April | 0.233683E+09 | 13897670.88 | 6407.96 | 8923939.34 | 2197828.10 | 45245753.88 | 0.550733E+09 | 2620.61 | 0.47 |
May | 0.115465E+09 | 76508544.31 | 12846.21 | 8164161.85 | 6838256.31 | 536635.71 | 0.308987E+09 | 12053.29 | 0.47 |
June | 37199277.35 | 0.170953E+09 | 49736.55 | 4000656.99 | 9664944.60 | 4984.83 | 59136070.56 | 19733.76 | 0.47 |
July | 1236187.05 | 0.676097E+09 | 312678.51 | 3615.81 | 0.123426E+09 | 0.00 | 2980.01 | 19881.44 | 0.47 |
August | 32254068.04 | 0.344474E+09 | 243946.44 | 1467535.01 | 59346436.87 | 34883.07 | 18751579.87 | 37562.53 | 0.47 |
September | 92873933.75 | 0.303305E+09 | 256596.60 | 4352191.68 | 54861590.42 | 306145.82 | 0.151215E+09 | 31589.67 | 0.48 |
October | 0.282507E+09 | 53161974.41 | 78324.07 | 6496069.21 | 17027134.16 | 6175088.68 | 0.599064E+09 | 13733.22 | 0.47 |
November | 0.396422E+09 | 377508.73 | 0.00 | 2480537.32 | 205201.71 | 0.596486E+09 | 0.405481E+09 | 0.00 | 0.47 |
December | 0.446474E+09 | 0.00 | 0.00 | 381630.47 | 0.00 | 0.105947E+10 | 68511273.17 | 0.00 | 0.47 |
Annual Sum or Average | 0.292896E+10 | 0.163880E+10 | 960542.76 | 41558784.74 | 0.273568E+09 | 0.383870E+10 | 0.299899E+10 | 137208.15 | 0.47 |
Minimum of Months | 1236187.05 | 0.00 | 0.00 | 3615.81 | 0.00 | 0.00 | 2980.01 | 0.00 | 0.47 |
Maximum of Months | 0.458313E+09 | 0.676097E+09 | 312678.51 | 8923939.34 | 0.123426E+09 | 0.105947E+10 | 0.599064E+09 | 37562.53 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116240E+11 | 0.00 | 0.00 | 62514682.44 | 0.00 | 0.00 | 0.967716E+10 | 0.00 | 0.54 |
February | 0.898812E+10 | 0.00 | 0.00 | 61930742.63 | 0.00 | 0.00 | 0.892591E+10 | 0.00 | 0.54 |
March | 0.104889E+11 | 375634.31 | 0.00 | 45353170.06 | 0.00 | 0.00 | 0.794471E+10 | 0.00 | 0.54 |
April | 0.496046E+10 | 0.218389E+09 | 0.00 | 59359334.88 | 0.00 | 0.00 | 0.635198E+10 | 0.00 | 0.54 |
May | 0.168348E+10 | 0.113058E+10 | 0.00 | 46585435.97 | 0.00 | 0.00 | 0.414378E+10 | 0.00 | 0.54 |
June | 90842848.83 | 0.245017E+10 | 0.00 | 30939992.65 | 79706.25 | 0.00 | 0.123891E+10 | 0.00 | 0.54 |
July | 446824.39 | 0.108300E+11 | 0.00 | 611872.48 | 16608556.97 | 0.00 | 15794298.81 | 0.00 | 0.54 |
August | 41827315.79 | 0.545360E+10 | 0.00 | 12751507.98 | 26300720.99 | 0.00 | 0.657467E+09 | 0.00 | 0.54 |
September | 0.278392E+09 | 0.485324E+10 | 0.00 | 41661677.62 | 7662227.82 | 0.00 | 0.305313E+10 | 0.00 | 0.54 |
October | 0.261155E+10 | 0.953061E+09 | 0.00 | 90985883.80 | 0.00 | 0.00 | 0.942400E+10 | 0.00 | 0.54 |
November | 0.809197E+10 | 7901956.71 | 0.00 | 88869985.94 | 0.00 | 0.00 | 0.108159E+11 | 0.00 | 0.54 |
December | 0.122691E+11 | 0.00 | 0.00 | 52935841.48 | 0.00 | 0.00 | 0.903378E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.611290E+11 | 0.258973E+11 | 0.00 | 0.594500E+09 | 50651212.03 | 0.00 | 0.712826E+11 | 0.00 | 0.54 |
Minimum of Months | 446824.39 | 0.00 | 0.00 | 611872.48 | 0.00 | 0.00 | 15794298.81 | 0.00 | 0.53 |
Maximum of Months | 0.122691E+11 | 0.108300E+11 | 0.00 | 90985883.80 | 26300720.99 | 0.00 | 0.108159E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.627576E+10 | 0.00 | 0.00 | 19068033.60 | 0.00 | 0.570898E+10 | 0.936567E+10 | 0.00 | 0.53 |
February | 0.568480E+10 | 0.00 | 0.00 | 28658153.22 | 0.00 | 0.293094E+10 | 0.933648E+10 | 0.00 | 0.53 |
March | 0.588822E+10 | 375737.03 | 0.00 | 51400053.07 | 0.00 | 0.846889E+09 | 0.116975E+11 | 0.00 | 0.54 |
April | 0.341053E+10 | 93862385.04 | 764404.56 | 84889657.68 | 0.123628E+09 | 24634138.36 | 0.785485E+10 | 193697.90 | 0.54 |
May | 0.162388E+10 | 0.729049E+09 | 2490761.23 | 74378121.15 | 0.399002E+09 | 5201444.80 | 0.417199E+10 | 345144.47 | 0.54 |
June | 0.510265E+09 | 0.205633E+10 | 738657.75 | 33951118.94 | 0.393744E+09 | 66716.76 | 0.816782E+09 | 99208.73 | 0.54 |
July | 16768135.72 | 0.830182E+10 | 4943666.90 | 35086.43 | 0.254267E+10 | 0.00 | 54381.95 | 135329.07 | 0.54 |
August | 0.437427E+09 | 0.396813E+10 | 5674302.64 | 14601562.54 | 0.150733E+10 | 254194.34 | 0.259958E+09 | 252949.47 | 0.54 |
September | 0.132787E+10 | 0.337714E+10 | 5600106.34 | 38061695.48 | 0.147918E+10 | 4352412.32 | 0.200383E+10 | 307145.22 | 0.54 |
October | 0.404685E+10 | 0.495628E+09 | 1224658.21 | 65356166.59 | 0.456429E+09 | 29028638.77 | 0.798862E+10 | 40480.92 | 0.54 |
November | 0.572594E+10 | 258742.72 | 32502.48 | 32518505.93 | 7600325.87 | 0.219241E+10 | 0.110511E+11 | 12546.41 | 0.53 |
December | 0.627310E+10 | 0.00 | 0.00 | 14260141.54 | 0.00 | 0.803800E+10 | 0.703629E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.412214E+11 | 0.190226E+11 | 21469060.11 | 0.457178E+09 | 0.690959E+10 | 0.197808E+11 | 0.715831E+11 | 1386502.20 | 0.54 |
Minimum of Months | 16768135.72 | 0.00 | 0.00 | 35086.43 | 0.00 | 0.00 | 54381.95 | 0.00 | 0.53 |
Maximum of Months | 0.627576E+10 | 0.830182E+10 | 5674302.64 | 84889657.68 | 0.254267E+10 | 0.803800E+10 | 0.116975E+11 | 345144.47 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.448029E+09 | 0.00 | 0.00 | 3155187.22 | 0.00 | 0.757133E+09 | 0.367277E+09 | 0.00 | 0.47 |
February | 0.356767E+09 | 0.00 | 0.00 | 5121039.14 | 0.00 | 0.446441E+09 | 0.517419E+09 | 0.00 | 0.47 |
March | 0.319378E+09 | 27663.43 | 0.00 | 7137497.88 | 0.00 | 0.319073E+09 | 0.717256E+09 | 40.04 | 0.47 |
April | 0.169213E+09 | 15012571.90 | 17673.65 | 12136983.99 | 1072143.42 | 32841981.64 | 0.624492E+09 | 4025.68 | 0.47 |
May | 0.100122E+09 | 78135071.96 | 31836.74 | 9389853.01 | 5211229.36 | 281884.29 | 0.323409E+09 | 3331.42 | 0.47 |
June | 36633234.69 | 0.173743E+09 | 27334.76 | 4347544.19 | 6936927.65 | 0.00 | 59371968.63 | 1205.26 | 0.47 |
July | 1236331.90 | 0.687833E+09 | 244616.06 | 3540.61 | 0.111868E+09 | 0.00 | 3055.99 | 4311.52 | 0.47 |
August | 31700634.00 | 0.354519E+09 | 109366.61 | 1604429.27 | 49510060.73 | 15192.63 | 19193962.91 | 10716.42 | 0.47 |
September | 86089285.04 | 0.313831E+09 | 24536.81 | 5632924.60 | 44636951.32 | 164479.09 | 0.156890E+09 | 4465.55 | 0.48 |
October | 0.220280E+09 | 60638473.73 | 24208.25 | 10041692.40 | 9624073.07 | 9919019.56 | 0.654105E+09 | 2646.24 | 0.47 |
November | 0.298383E+09 | 558931.32 | 0.00 | 7180905.67 | 23847.39 | 0.399398E+09 | 0.696073E+09 | 0.00 | 0.47 |
December | 0.458196E+09 | 0.00 | 0.00 | 2585840.21 | 0.00 | 0.810324E+09 | 0.303911E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.252603E+10 | 0.168430E+10 | 479572.87 | 68337438.18 | 0.228883E+09 | 0.277559E+10 | 0.443940E+10 | 30742.13 | 0.47 |
Minimum of Months | 1236331.90 | 0.00 | 0.00 | 3540.61 | 0.00 | 0.00 | 3055.99 | 0.00 | 0.47 |
Maximum of Months | 0.458196E+09 | 0.687833E+09 | 244616.06 | 12136983.99 | 0.111868E+09 | 0.810324E+09 | 0.717256E+09 | 10716.42 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.462664E+09 | 0.00 | 0.00 | 590047.64 | 0.00 | 0.979916E+09 | 0.132239E+09 | 0.00 | 0.47 |
February | 0.414723E+09 | 0.00 | 0.00 | 2116501.35 | 0.00 | 0.613539E+09 | 0.295215E+09 | 0.00 | 0.47 |
March | 0.424102E+09 | 27700.23 | 0.00 | 4305089.48 | 0.00 | 0.423278E+09 | 0.511000E+09 | 0.00 | 0.47 |
April | 0.197752E+09 | 14935728.83 | 35887.59 | 10745522.96 | 1121882.66 | 49128918.27 | 0.580959E+09 | 11028.47 | 0.47 |
May | 0.100434E+09 | 78100627.50 | 50792.42 | 9202958.33 | 5216520.96 | 304963.32 | 0.323210E+09 | 3759.24 | 0.47 |
June | 36581692.44 | 0.173875E+09 | 15822.19 | 4378619.83 | 6794959.90 | 0.00 | 59380677.45 | 1794.67 | 0.47 |
July | 1236187.05 | 0.688186E+09 | 223543.01 | 3542.44 | 0.111442E+09 | 0.00 | 3053.39 | 4174.92 | 0.47 |
August | 31696006.33 | 0.354022E+09 | 131333.33 | 1551722.08 | 49936422.32 | 38824.46 | 19221513.12 | 11984.53 | 0.47 |
September | 87661014.09 | 0.312517E+09 | 36353.20 | 4700132.58 | 45896552.86 | 218820.63 | 0.156167E+09 | 4731.89 | 0.48 |
October | 0.259192E+09 | 55678881.68 | 88149.91 | 6641542.99 | 14500958.64 | 17660954.18 | 0.610747E+09 | 13175.63 | 0.47 |
November | 0.419518E+09 | 18934.38 | 2998.87 | 2756997.03 | 560314.19 | 0.579401E+09 | 0.399193E+09 | 462.99 | 0.47 |
December | 0.450662E+09 | 0.00 | 0.00 | 413339.50 | 0.00 | 0.102436E+10 | 99396836.81 | 0.00 | 0.47 |
Annual Sum or Average | 0.288622E+10 | 0.167736E+10 | 584880.51 | 47406016.22 | 0.235470E+09 | 0.368785E+10 | 0.318673E+10 | 51112.35 | 0.47 |
Minimum of Months | 1236187.05 | 0.00 | 0.00 | 3542.44 | 0.00 | 0.00 | 3053.39 | 0.00 | 0.47 |
Maximum of Months | 0.462664E+09 | 0.688186E+09 | 223543.01 | 10745522.96 | 0.111442E+09 | 0.102436E+10 | 0.610747E+09 | 13175.63 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6608375.81 | 0.00 | 0.00 | 0.55 |
February | 0.234450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.239705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.155936E+11 | 0.00 | 0.00 | 0.00 | 50690181.44 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.804141E+10 | 58749917.23 | 0.00 | 3770789.86 | 0.231961E+09 | 0.00 | 0.165173E+10 | 0.00 | 0.55 |
June | 0.135636E+10 | 0.789485E+09 | 0.00 | 16164156.88 | 0.104251E+09 | 0.00 | 0.374952E+10 | 0.00 | 0.54 |
July | 0.223292E+09 | 0.231472E+10 | 0.00 | 7999491.64 | 0.177739E+10 | 0.00 | 0.111048E+10 | 0.00 | 0.52 |
August | 0.221788E+10 | 0.920121E+09 | 0.00 | 10527189.20 | 0.226778E+09 | 0.00 | 0.229270E+10 | 0.00 | 0.54 |
September | 0.479861E+10 | 0.402778E+09 | 0.00 | 8875058.04 | 0.322022E+09 | 0.00 | 0.295039E+10 | 0.00 | 0.57 |
October | 0.175597E+11 | 50176210.75 | 0.00 | 1229632.02 | 59505984.49 | 0.00 | 0.428924E+09 | 0.00 | 0.58 |
November | 0.253057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1449635.16 | 0.00 | 0.00 | 0.56 |
December | 0.277341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40718066.15 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.178320E+12 | 0.453603E+10 | 0.00 | 48566317.63 | 0.277260E+10 | 48776077.11 | 0.121837E+11 | 0.00 | 0.55 |
Minimum of Months | 0.223292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.280738E+11 | 0.231472E+10 | 0.00 | 16164156.88 | 0.177739E+10 | 40718066.15 | 0.374952E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100519E+09 | 0.00 | 0.00 | 570953.52 | 0.00 | 0.222238E+09 | 70570832.13 | 0.00 | 0.47 |
February | 93116169.74 | 0.00 | 0.00 | 718980.49 | 0.00 | 0.160123E+09 | 77478760.12 | 0.00 | 0.47 |
March | 96185391.03 | 6925.87 | 0.00 | 1209001.51 | 0.00 | 0.121247E+09 | 0.122069E+09 | 0.00 | 0.47 |
April | 55803148.40 | 3684512.54 | 0.00 | 2318275.59 | 341522.99 | 22833532.63 | 0.128716E+09 | 568.13 | 0.47 |
May | 28537315.92 | 19255901.23 | 6026.27 | 1913340.14 | 1578432.54 | 136231.67 | 77713839.67 | 5007.33 | 0.47 |
June | 9300670.65 | 42958532.57 | 9254.27 | 942434.90 | 2207581.37 | 5724.47 | 14839356.86 | 1780.18 | 0.47 |
July | 309082.98 | 0.169441E+09 | 121298.79 | 805.25 | 30415259.15 | 0.00 | 843.90 | 9367.28 | 0.47 |
August | 8064461.88 | 87035269.75 | 58637.08 | 343242.00 | 13933986.23 | 10003.54 | 4710847.28 | 9328.39 | 0.47 |
September | 22788628.41 | 77046609.31 | 64617.90 | 1177802.74 | 12504540.85 | 76977.46 | 38150682.80 | 8498.09 | 0.48 |
October | 63992234.76 | 14919489.32 | 21310.40 | 2038887.34 | 2627652.74 | 12311037.38 | 0.145244E+09 | 3897.86 | 0.47 |
November | 81352218.90 | 139732.83 | 0.00 | 1254646.39 | 5961.85 | 0.135704E+09 | 0.131947E+09 | 0.00 | 0.47 |
December | 0.102431E+09 | 0.00 | 0.00 | 416547.05 | 0.00 | 0.239226E+09 | 51680224.67 | 0.00 | 0.47 |
Annual Sum or Average | 0.662400E+09 | 0.414488E+09 | 281144.70 | 12904916.92 | 63614937.73 | 0.913912E+09 | 0.863122E+09 | 38447.26 | 0.47 |
Minimum of Months | 309082.98 | 0.00 | 0.00 | 805.25 | 0.00 | 0.00 | 843.90 | 0.00 | 0.47 |
Maximum of Months | 0.102431E+09 | 0.169441E+09 | 121298.79 | 2318275.59 | 30415259.15 | 0.239226E+09 | 0.145244E+09 | 9367.28 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107264E+09 | 0.00 | 0.00 | 123677.16 | 0.00 | 0.270235E+09 | 16229267.75 | 0.00 | 0.47 |
February | 0.100745E+09 | 0.00 | 0.00 | 232834.72 | 0.00 | 0.201097E+09 | 29323526.32 | 0.00 | 0.47 |
March | 0.104784E+09 | 6925.06 | 0.00 | 664537.70 | 0.00 | 0.157009E+09 | 78212892.62 | 0.00 | 0.47 |
April | 58757183.09 | 3553690.43 | 394.16 | 2036490.48 | 471873.40 | 28155926.54 | 0.120697E+09 | 173.90 | 0.47 |
May | 28895512.64 | 19180368.19 | 6196.95 | 1869408.53 | 1651524.53 | 240353.75 | 77282763.47 | 4835.36 | 0.47 |
June | 9294868.70 | 42948624.86 | 3446.53 | 948852.51 | 2217607.02 | 3666.92 | 14837859.30 | 2176.81 | 0.47 |
July | 309046.76 | 0.169301E+09 | 104137.14 | 806.27 | 30550743.32 | 0.00 | 842.69 | 7750.71 | 0.47 |
August | 8063517.01 | 86277860.77 | 64608.87 | 329668.90 | 14674207.20 | 11688.67 | 4722141.92 | 8706.63 | 0.47 |
September | 23265154.37 | 75971370.35 | 60661.33 | 954778.53 | 13572850.89 | 53946.78 | 37912924.79 | 8882.79 | 0.48 |
October | 70967416.13 | 13430694.22 | 15947.10 | 1264456.13 | 4120915.53 | 23846015.78 | 0.127482E+09 | 2734.61 | 0.47 |
November | 98432693.47 | 88482.56 | 0.00 | 435784.62 | 57195.05 | 0.198607E+09 | 52742131.93 | 0.00 | 0.47 |
December | 0.103323E+09 | 0.00 | 0.00 | 61571.37 | 0.00 | 0.282444E+09 | 7878520.78 | 0.00 | 0.47 |
Annual Sum or Average | 0.714103E+09 | 0.410759E+09 | 255392.08 | 8922866.93 | 67316916.93 | 0.116170E+10 | 0.567322E+09 | 35260.81 | 0.47 |
Minimum of Months | 309046.76 | 0.00 | 0.00 | 806.27 | 0.00 | 0.00 | 842.69 | 0.00 | 0.47 |
Maximum of Months | 0.107264E+09 | 0.169301E+09 | 104137.14 | 2036490.48 | 30550743.32 | 0.282444E+09 | 0.127482E+09 | 8882.79 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.383323E+09 | 0.00 | 0.00 | 15559706.96 | 0.00 | 0.710051E+09 | 0.142166E+10 | 0.00 | 0.54 |
February | 0.385881E+09 | 0.00 | 0.00 | 14746332.09 | 0.00 | 0.451222E+09 | 0.127747E+10 | 0.00 | 0.54 |
March | 0.498292E+09 | 44495.17 | 0.00 | 12492026.88 | 0.00 | 0.333167E+09 | 0.134494E+10 | 0.00 | 0.54 |
April | 0.329922E+09 | 23747091.36 | 11052.49 | 13498178.93 | 2105436.11 | 63882752.99 | 0.939726E+09 | 5292.36 | 0.54 |
May | 0.180919E+09 | 0.120342E+09 | 109918.85 | 10138046.82 | 13439329.95 | 1454167.81 | 0.503265E+09 | 29733.69 | 0.54 |
June | 59910496.73 | 0.270461E+09 | 43667.03 | 4866599.71 | 19715980.75 | 18965.07 | 96382727.69 | 19654.50 | 0.54 |
July | 1985700.28 | 0.107552E+10 | 670621.07 | 4572.26 | 0.208588E+09 | 0.00 | 6022.68 | 36983.48 | 0.54 |
August | 51800512.44 | 0.556053E+09 | 318781.79 | 2066415.29 | 92704644.04 | 70686.90 | 30406645.12 | 35885.51 | 0.54 |
September | 0.146085E+09 | 0.497299E+09 | 155209.64 | 7919359.57 | 78312946.74 | 220232.60 | 0.245341E+09 | 23170.71 | 0.54 |
October | 0.373749E+09 | 98113840.95 | 38551.17 | 18995771.98 | 14738627.40 | 2317081.05 | 0.104137E+10 | 2357.85 | 0.54 |
November | 0.389805E+09 | 897712.08 | 0.00 | 19943618.04 | 38301.83 | 0.376619E+09 | 0.146386E+10 | 0.00 | 0.53 |
December | 0.380251E+09 | 0.00 | 0.00 | 15463694.01 | 0.00 | 0.825494E+09 | 0.130846E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.318192E+10 | 0.264248E+10 | 1347802.04 | 0.135694E+09 | 0.429643E+09 | 0.276452E+10 | 0.967289E+10 | 153078.10 | 0.54 |
Minimum of Months | 1985700.28 | 0.00 | 0.00 | 4572.26 | 0.00 | 0.00 | 6022.68 | 0.00 | 0.53 |
Maximum of Months | 0.498292E+09 | 0.107552E+10 | 670621.07 | 19943618.04 | 0.208588E+09 | 0.825494E+09 | 0.146386E+10 | 36983.48 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273626E+10 | 0.00 | 0.00 | 82099375.68 | 0.00 | 0.00 | 0.457167E+11 | 0.00 | 4.41 |
February | 0.147378E+10 | 0.00 | 0.00 | 78650084.65 | 0.00 | 0.00 | 0.402667E+11 | 0.00 | 4.64 |
March | 0.844665E+09 | 0.00 | 0.00 | 94350884.50 | 0.00 | 0.00 | 0.439250E+11 | 0.00 | 4.91 |
April | 89676035.41 | 85435858.67 | 0.00 | 95451550.07 | 0.00 | 0.00 | 0.316244E+11 | 0.00 | 5.33 |
May | 0.00 | 0.519445E+09 | 0.00 | 90852349.53 | 0.00 | 0.00 | 0.215431E+11 | 0.00 | 5.47 |
June | 0.00 | 0.168720E+10 | 0.00 | 73473043.13 | 0.00 | 0.00 | 0.117423E+11 | 0.00 | 5.32 |
July | 0.00 | 0.837295E+10 | 0.00 | 33064116.21 | 0.00 | 0.00 | 0.314797E+10 | 0.00 | 5.24 |
August | 0.00 | 0.225526E+10 | 0.00 | 69305334.96 | 0.00 | 0.00 | 0.101383E+11 | 0.00 | 5.34 |
September | 0.00 | 0.133356E+10 | 0.00 | 76429479.72 | 0.00 | 0.00 | 0.169258E+11 | 0.00 | 5.51 |
October | 39254374.05 | 0.208115E+09 | 0.00 | 87788266.23 | 0.00 | 0.00 | 0.356642E+11 | 0.00 | 5.31 |
November | 0.100967E+10 | 0.00 | 0.00 | 83195919.34 | 0.00 | 0.00 | 0.443871E+11 | 0.00 | 4.62 |
December | 0.249321E+10 | 0.00 | 0.00 | 81222491.21 | 0.00 | 0.00 | 0.445782E+11 | 0.00 | 4.28 |
Annual Sum or Average | 0.868653E+10 | 0.144620E+11 | 0.00 | 0.945883E+09 | 0.00 | 0.00 | 0.349660E+12 | 0.00 | 5.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33064116.21 | 0.00 | 0.00 | 0.314797E+10 | 0.00 | 4.28 |
Maximum of Months | 0.273626E+10 | 0.837295E+10 | 0.00 | 95451550.07 | 0.00 | 0.00 | 0.457167E+11 | 0.00 | 5.51 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102219E+10 | 0.00 | 0.00 | 0.104213E+09 | 0.00 | 0.00 | 0.522356E+11 | 0.00 | 4.84 |
February | 0.643054E+09 | 0.00 | 0.00 | 96335875.68 | 0.00 | 0.00 | 0.451480E+11 | 0.00 | 5.08 |
March | 0.350677E+09 | 0.00 | 0.00 | 0.111736E+09 | 0.00 | 0.00 | 0.485845E+11 | 0.00 | 5.37 |
April | 33377280.27 | 93912163.40 | 0.00 | 0.106029E+09 | 0.00 | 0.00 | 0.341217E+11 | 0.00 | 5.76 |
May | 0.00 | 0.562012E+09 | 0.00 | 97633507.78 | 0.00 | 0.00 | 0.228702E+11 | 0.00 | 5.84 |
June | 0.00 | 0.180769E+10 | 0.00 | 77787554.77 | 0.00 | 0.00 | 0.123424E+11 | 0.00 | 5.64 |
July | 0.00 | 0.892263E+10 | 0.00 | 34757066.99 | 0.00 | 0.00 | 0.329854E+10 | 0.00 | 5.56 |
August | 0.00 | 0.240737E+10 | 0.00 | 73654329.22 | 0.00 | 0.00 | 0.106948E+11 | 0.00 | 5.68 |
September | 0.00 | 0.143315E+10 | 0.00 | 81887375.90 | 0.00 | 0.00 | 0.179399E+11 | 0.00 | 5.87 |
October | 24932765.92 | 0.223468E+09 | 0.00 | 97381023.93 | 0.00 | 0.00 | 0.383955E+11 | 0.00 | 5.72 |
November | 0.293664E+09 | 0.00 | 0.00 | 0.100576E+09 | 0.00 | 0.00 | 0.492991E+11 | 0.00 | 5.04 |
December | 0.840431E+09 | 0.00 | 0.00 | 0.104651E+09 | 0.00 | 0.00 | 0.509237E+11 | 0.00 | 4.69 |
Annual Sum or Average | 0.320832E+10 | 0.154502E+11 | 0.00 | 0.108664E+10 | 0.00 | 0.00 | 0.385854E+12 | 0.00 | 5.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34757066.99 | 0.00 | 0.00 | 0.329854E+10 | 0.00 | 4.69 |
Maximum of Months | 0.102219E+10 | 0.892263E+10 | 0.00 | 0.111736E+09 | 0.00 | 0.00 | 0.522356E+11 | 0.00 | 5.87 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 44631538.18 | 0.00 | 0.00 | 0.178864E+09 | 0.00 | 0.00 | 0.703404E+11 | 0.00 | 21.12 |
February | 28767625.68 | 0.00 | 0.00 | 0.151880E+09 | 0.00 | 0.00 | 0.588743E+11 | 0.00 | 22.21 |
March | 48415742.32 | 0.00 | 0.00 | 0.159399E+09 | 0.00 | 0.00 | 0.599775E+11 | 0.00 | 23.05 |
April | 15536367.88 | 0.162442E+09 | 0.00 | 0.141453E+09 | 0.00 | 0.00 | 0.377487E+11 | 0.00 | 23.39 |
May | 0.00 | 0.933009E+09 | 0.00 | 0.122561E+09 | 0.00 | 0.00 | 0.224156E+11 | 0.00 | 22.85 |
June | 0.00 | 0.281487E+10 | 0.00 | 89606614.39 | 0.00 | 0.00 | 0.113194E+11 | 0.00 | 21.58 |
July | 0.00 | 0.119163E+11 | 0.00 | 33721989.51 | 0.00 | 0.00 | 0.281879E+10 | 0.00 | 21.39 |
August | 0.00 | 0.341139E+10 | 0.00 | 88109670.56 | 0.00 | 0.00 | 0.103004E+11 | 0.00 | 22.01 |
September | 0.00 | 0.223706E+10 | 0.00 | 0.101625E+09 | 0.00 | 0.00 | 0.179617E+11 | 0.00 | 23.08 |
October | 18867767.34 | 0.348678E+09 | 0.00 | 0.130789E+09 | 0.00 | 0.00 | 0.441066E+11 | 0.00 | 23.74 |
November | 93788123.39 | 0.00 | 0.00 | 0.149468E+09 | 0.00 | 0.00 | 0.636889E+11 | 0.00 | 22.05 |
December | 75116998.18 | 0.00 | 0.00 | 0.181013E+09 | 0.00 | 0.00 | 0.695083E+11 | 0.00 | 20.74 |
Annual Sum or Average | 0.325124E+09 | 0.218238E+11 | 0.00 | 0.152849E+10 | 0.00 | 0.00 | 0.469061E+12 | 0.00 | 22.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33721989.51 | 0.00 | 0.00 | 0.281879E+10 | 0.00 | 20.74 |
Maximum of Months | 93788123.39 | 0.119163E+11 | 0.00 | 0.181013E+09 | 0.00 | 0.00 | 0.703404E+11 | 0.00 | 23.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126624E+09 | 0.00 | 0.00 | 1.05 |
February | 0.118147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124104E+09 | 0.00 | 0.00 | 1.08 |
March | 0.121466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59777727.68 | 0.00 | 0.00 | 1.10 |
April | 0.763720E+10 | 17975781.83 | 0.00 | 984289.11 | 7849482.89 | 0.00 | 0.302860E+09 | 0.00 | 1.10 |
May | 0.357287E+10 | 0.158478E+09 | 0.00 | 6917097.31 | 10743088.31 | 0.00 | 0.137662E+10 | 0.00 | 1.09 |
June | 0.655295E+09 | 0.602322E+09 | 0.00 | 11516748.28 | 957464.13 | 0.00 | 0.195904E+10 | 0.00 | 1.13 |
July | 0.121302E+09 | 0.210247E+10 | 0.00 | 4883829.74 | 0.224558E+09 | 0.00 | 0.566462E+09 | 0.00 | 1.12 |
August | 0.949222E+09 | 0.653743E+09 | 0.00 | 9275321.24 | 33299945.69 | 0.00 | 0.135665E+10 | 0.00 | 1.12 |
September | 0.259523E+10 | 0.377273E+09 | 0.00 | 7471558.38 | 38013532.08 | 0.00 | 0.134445E+10 | 0.00 | 1.14 |
October | 0.856863E+10 | 58631580.79 | 0.00 | 2180641.75 | 4803669.40 | 0.00 | 0.589953E+09 | 0.00 | 1.13 |
November | 0.128836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3464411.28 | 0.00 | 0.00 | 1.07 |
December | 0.135887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554854E+09 | 0.00 | 0.00 | 1.04 |
Annual Sum or Average | 0.887060E+11 | 0.397090E+10 | 0.00 | 43229485.82 | 0.320225E+09 | 0.868825E+09 | 0.749604E+10 | 0.00 | 1.10 |
Minimum of Months | 0.121302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
Maximum of Months | 0.141726E+11 | 0.210247E+10 | 0.00 | 11516748.28 | 0.224558E+09 | 0.554854E+09 | 0.195904E+10 | 0.00 | 1.14 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:42:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.191471E+12 | 0.129589E+11 | 0.153877E+12 | 0.697538E+12 | 0.897705E+11 |
February | 0.198903E+12 | 0.104486E+11 | 0.118525E+12 | 0.560317E+12 | 0.123285E+12 |
March | 0.319012E+12 | 0.100624E+11 | 0.110433E+12 | 0.537056E+12 | 0.181229E+12 |
April | 0.331299E+12 | 0.551076E+10 | 0.588235E+11 | 0.302285E+12 | 0.445720E+12 |
May | 0.363764E+12 | 0.290244E+10 | 0.295696E+11 | 0.166977E+12 | 0.712497E+12 |
June | 0.346117E+12 | 0.544279E+09 | 0.173244E+10 | 0.404273E+11 | 0.925834E+12 |
July | 0.335036E+12 | -0.307643E+10 | -0.354965E+11 | -0.157832E+12 | 0.116009E+13 |
August | 0.304807E+12 | -167144865.1 | 0.126001E+10 | 0.642995E+10 | 0.975978E+12 |
September | 0.260740E+12 | 0.142207E+10 | 0.168206E+11 | 0.996968E+11 | 0.812252E+12 |
October | 0.244924E+12 | 0.572403E+10 | 0.638932E+11 | 0.337077E+12 | 0.448627E+12 |
November | 0.188486E+12 | 0.105277E+11 | 0.120313E+12 | 0.575372E+12 | 0.157856E+12 |
December | 0.155085E+12 | 0.140564E+11 | 0.165819E+12 | 0.749013E+12 | 0.810680E+11 |
Annual Sum or Average | 0.323964E+13 | 0.709139E+11 | 0.805569E+12 | 0.391436E+13 | 0.611421E+13 |
Minimum of Months | 0.155085E+12 | -0.307643E+10 | -0.354965E+11 | -0.157832E+12 | 0.810680E+11 |
Maximum of Months | 0.363764E+12 | 0.140564E+11 | 0.165819E+12 | 0.749013E+12 | 0.116009E+13 |